Multimate = Mservic x1.6 5) Positve moment Steel : Diameter of bar
16 d
=35
kN.m
=56
kN.m
mm
PLEASE CHOOSE DIAMETER OF BAR
=342
π΄β π πΉπ = ππ π
mm
=.481
% of seel (Ο)
=.00117
% of seel (Ο) minmum
=.00300
Area of steel = Ο x b x h
ACI 350-01 section 14.3.2 Minimum ratio of vertical reinforcement area to gross concrete area shall be 0.003
=1200
No. of bar =( As/Abar)
=6 =1200
Area of steel Provided
Space Between Two Bar's " S "
=167
Provided " S "
=150
Use
T16 -150
mm c/c
6) Horizontal moment Steel :
Diameter of bar
12
d Area of steel =0.003x b x h For one face
mm
PLEASE CHOOSE DIAMETER OF BAR
=344
mm
=1200
mm2 2
=600
mm
=5
Bar's
Space Between Two Bar's " S "
=188
mm
Provided " S "
=175
mm
No. of bar =( As/Abar)
ACI 350-01 section 14.3.2 Minimum ratio of horizontal reinforcement area to groos concrete area shall be 0.003
Use
T12 -175
mm c/c
7) Base slab : Diameter of bar
20 d
Area of steel =0.0018x b x h No. of bar =( As/Abar) Provided " S "
mm
PLEASE CHOOSE DIAMETER OF BAR
=340
mm
=720
mm2
=2
Bar's
=436
mm
water pressure on the base slab and weight of the base will directly counteracted by the ground pressure .The pressure of water can be safely resisted by the soil under the floor . Hence : The floor slab or base slab will only requier normal rienforcement ,so as the enable if to span over any possible weak pathes at ground .
Use
T20 -200
mm c/c
Made
Date
AMY
29-Oct-14
1
Check
Date
Rev.
MMA
29-Oct-14
0
Sheet
PROJECT TITLE: PRINCE MAJED PALACE DESIGN OF UNDERGROUND WATER TANK
CASE 2 : WATER 1) Negative moment at abase : π΄ππππππβ =
ACI 350-01 section 14.3.2 Minimum ratio of horizontal reinforcement area to groos concrete area shall be 0.003
Use
T12 -175
mm c/c
6) Base slab : Diameter of bar
20
mm
d
=340
Area of steel =0.0018x b x h
PLEASE CHOOSE DIAMETER OF BAR mm
=720
mm2
No. of bar =( As/Abar)
=2
Bar's
Area of steel Provided
=436
mm
water pressure on the base slab and weight of the base will directly counteracted by the ground pressure .The pressure of water can be safely resisted by the soil under the floor . Hence : The floor slab or base slab will only requier normal rienforcement ,so as the enable if to span over any possible weak pathes at ground .
Use
T20
-
425 mm c/c
Both 2- WAY
T12 -175 T16 -150
T16 -150
EMPTY WATER
TWO LAYERS OF APPROVED WATER PROOFING MEMBRANE WITH PROTECTION BOARD (TYP)
T20 -200
GRAVEL FILL (1"-6" SIZE) (TYP) 1000mm DEEP
50 THK. BLINDING CONCRETE (TYP)
50 THK. PROTECTION SCREED (TYP)
TWO LAYERS OF APPROVED WATERPROOFING MEMBERANE (TYP)
EMPTY TANK
Water Level
T16 -150
T12 -175
WATER IN SIDE
TWO LAYERS OF APPROVED WATER PROOFING MEMBRANE WITH PROTECTION BOARD (TYP)
T20 -425
GRAVEL FILL (1"-6" SIZE) (TYP) 1000mm DEEP
50 THK. BLINDING CONCRETE (TYP)
50 THK. PROTECTION SCREED (TYP)
TWO LAYERS OF APPROVED WATERPROOFING MEMBERANE (TYP)