Visio-C System Overview JEC PAS V2-0

September 18, 2017 | Author: باسم العوفي | Category: Ethernet, Electrical Substation, Communications Protocols, Networking Standards, Computer Standards
Share Embed Donate


Short Description

Download Visio-C System Overview JEC PAS V2-0...

Description

1

2

3

4

5

Control Center

6

7

Ethernet Switch for IEC61850:

RS232 or RS485

RS900G:

Ethernet - TCP/IP (RJ45)

2xFO; 8xRJ45

RSG2100: 2+6xFO; 8xRJ45

A

Parallel Connection

HMI Client I Operation Station

HMI Client II Operation Station

2x IEC 101/ RS232

Engineering and Operation Station

B

Colour Laser Printer

Copyright (C) Siemens AG 1998 All Rights Reserved

Event Printer

C

D

A

Ethernet (Fibre Optic) IEC 60870-5-103 (RS485 Cu)

2x IEC 60870-5-101

B

8

Switch RS900G

C

Switch RS900G

SICAM PAS CC red. HMI Server

SICAM Station Unit (1x FS)

SICAM Station Unit (1x FS)

Redundant Time Server GPS

Event Printer

Station-LAN: Ethernet 1Gbps, Fibre-Optic double loop with redundancy-function

2x SerielHub

D

Switch 2x RSG2100 Control-LAN: IEC 61850; Ethernet 100Mbps Fibre-Optic double loops with redundancy-function

E

E

380Kv Control Loop 132Kv Control Loop 132Kv Protection Loop 380Kv Protection Loop F

F

Index

Modification 1

Date

Date 2008-11-01 Name Ainousah Appr. Name Norm 2

Jizan Economic City 380/132Kv GIS Substation

SIEMENS AG

P-SAR 010

System Overview

Page: 1 5 P.

Overview

Item/Project 3

4

5

6

7

8

1

2

3

4

5

6

7

8

Ethernet Switch for IEC61850:

RS232 or RS485

RS900: 2xFO; 6xRJ45

Ethernet - TCP/IP (RJ45)

RS400: 2xFO; 2xRJ45, 4x RS485

A

A

Ethernet (Fibre Optic) IEC 60870-5-103 (RS485 Cu) Parallel Connection

B

B

380Kv Control Loop

Copyright (C) Siemens AG 1998 All Rights Reserved

C

D

Redundant Station-Bus 100MBit/s Ethernet TCPIP, Fiber optic, IEC 61850 Protocol

BCU 6MD63

BCU 6MD63

BCU 6MD63

1 x S/S Common Alarm Unit Building Signals, Fire Fighting, Telecommunication Signals

C

AC/DC and UPS Signals

D

MV Compartment

BCU 6MD66 or 6MD63

BCU 6MD66 or 6MD63

BCU 6MD63

BCU 6MD63

BCU 6MD63

E

Bay Control Panel

Bay Control Panel

BCU 6MD66 or 6MD63

E

(Shall be supplied by others)

2x13.8Kv Bays

1 xBusbar Measuring

2x 380Kv Diameter F

Index

Modification 1

Date

Date 2008-11-01 Name Ainousah Appr. Name Norm 2

Jizan Economic City 380/132Kv GIS Substation

SIEMENS AG

7SJ6

F

P-SAR 010 Page: 2 5 P.

Overview

Item/Project 3

4

5

6

7

8

1

2

3

4

5

A

6

7

8

Ethernet Switch for IEC61850:

RS232 or RS485

RS900: 2xFO; 6xRJ45

Ethernet - TCP/IP (RJ45)

RS400: 2xFO; 2xRJ45, 4x RS485

Ethernet (Fibre Optic)

A

IEC 60870-5-103 (RS485 Cu) Parallel Connection

B

D

BCU 6MD66

BCU 6MD66 Bay Control Panel

E

BCU 6MD63

Bay Control Panel

BCU 6MD66

2x Transformer Feeder

BCU 6MD66 Bay Control Panel

D

C

Bay Control Panel

C

Redundant Station-Bus 100MBit/s Ethernet TCPIP, Fiber optic, IEC 61850 Protocol 132Kv Control Loop

Copyright (C) Siemens AG 1998 All Rights Reserved

B

2x Bussectionalizer

5x Cable Feeder

E

2x Buscoupler

F

F

Index

Modification 1

Date

Date 2008-11-01 Name Ainousah Appr. Name Norm 2

Jizan Economic City 380/132Kv GIS Substation

SIEMENS AG

P-SAR 010 Page: 3 5 P.

Overview

Item/Project 3

4

5

6

7

8

1

2

3

4

5

Redundant Station-Bus 100MBit/s Ethernet TCPIP, Fiber optic, IEC 61850 Protocol

A

6

7

8

Ethernet Switch for IEC61850:

RS232 or RS485

RS900: 2xFO; 6xRJ45

Ethernet - TCP/IP (RJ45)

RS400: 2xFO; 2xRJ45, 4x RS485

Ethernet (Fibre Optic)

A

IEC 60870-5-103 (RS485 Cu) Parallel Connection

B

B

D

7SD522 Protection Panel

1x Synch-Check Relay Panel

7SA522 Protection Panel

Protection Panel

380Kv Protection Loop

Copyright (C) Siemens AG 1998 All Rights Reserved

C

RED670 (ABB) Protection Panel

4x 7VK611

4x 7VK61

1x CB Failure Prot. Panel

2x Line Prot. Panel, SET-2

2x Line Prot. Panel, SET-1

C

D

RS900

3x 7SJ61

Index

Modification 1

Date

Date 2008-11-01 Name Ainousah Appr. Name Norm 2

Protection Panel

Protection Panel

7SA522

2x 380/132/13.8KV RTCC. Panel

2x 380/132/13.8KV Trafo. Panel, Group-2,SET-2

2x 380/132/13.8KV Trafo. Panel, Group-1,SET-2

E

F

2x 7SJ61

7SJ62

Protection Panel

TAPCON 260

3x 7SJ61

Jizan Economic City 380/132Kv GIS Substation

SIEMENS AG

7RW600

7UT63 Protection Panel

1x RS485/ F.O. IEC-103

RJ45

E

2x 380/132/13.8KV Trafo. Panel, SET-1

F

P-SAR 010 Page: 4 5 P.

Overview

Item/Project 3

4

5

6

7

8

1

2

3

4

5

6

7

8

RS232 or RS485

Ethernet Switch for IEC61850:

Redundant Station-Bus 100MBit/s Ethernet TCPIP, Fiber optic, IEC 61850 Protocol

A

Ethernet - TCP/IP (RJ45)

RS900: 2xFO; 6xRJ45 A

Ethernet (Fibre Optic)

RS400: 2xFO; 2xRJ45, 4x RS485 IEC 60870-5-103 (RS485 Cu) Parallel Connection

B

Protection Panel

Protection Panel

Protection Panel

1x Synch-Check Relay Panel

3x B/S or B/C Prot. Panel

2x Line Prot. Panel, SET-2

2x Line Prot. Panel, SET-1

C

D

RS900

RS900

IEC-61850/ RJ45

23x

1x Busbar Protection, SET-2

Modification 1

Date

Date 2008-11-01 Name Ainousah Appr. Name Norm 2

7SS 523

7SS 523

7RW600

1x Busbar Protection, SET-1

Jizan Economic City 380/132Kv GIS Substation

Protection Panel

Protection Panel

REB (ABB

23x

F

4x 7VK61

7SS522

E

REB (ABB

1x RS485/ F.O. IEC-103

IEC-61850/ RJ45

REB (ABB)

Index

7SD522

Protection Panel

D

RED670 (ABB)

7SJ61 Protection Panel

C

10x 7VK61

132Kv Protection Loop

Copyright (C) Siemens AG 1998 All Rights Reserved

B

1x UV & UF Relay Panel

SIEMENS AG

F

P-SAR 010 Page: 5 5 P.

Overview

Item/Project 3

4

E

5

6

7

8