Utility Consumption List
March 7, 2017 | Author: lalitendujena | Category: N/A
Short Description
GTG utility list...
Description
105 N. Sandusky St., Mt. Vernon, OH 43050
Utility Consumption List (See Note 13)
Rolls-Royce Document Number: GED00329287 TRENT 60 WLE Gas Turbine Package - Trent 60 WLE Dual Fuel (ONPG) M.A587 Dammam Port Rev.
Date
0
13-Jun-14
1
26-Aug-14
2
28-Aug-14
3
25-Sep-14
4
1-Apr-15
Prepared by
Checked by
Rebecca Conway
Kathy Zhang
ECO 68481.61- Updated Table A for Ventilation System, VDF-MCC, and WSAC system.
Kathy Zhang
Rebecca Conway
Certified As Built
ECO 68481.62 - Revised 75WF/88WF, 75WI13/88WI1-3, 75IFW/88IFW, 75CPW1-3/88CPW1-3 and 75SRM/88SRM.
Kathy Zhang
John Stanley
Certified As Built Certified As Built
ECO 68481.65 - Revised water injection pump motor 88WI1/88WI2/88WI3 VFD rating to 90kW. ECO 68481.79 - Update Instrument Airflows - adding standard, removing ISI purge
Kathy Zhang
John Stanley
David Vics
John Stanley
Issue Certified As Built Certified As Built
ECO No. / Description ECO 68481.41 - Initial Release
Page 1 of 14
GED00329287, Rev 04
105 N. Sandusky St., Mt. Vernon, OH 43050
Date: 04-01-2015
Project: M.A587
Sheet: 1 of 13
Document: GED00329287 Utility Consumption List
Rev: 4
Engineer: Rebecca Conway, Kathy Zhang
Project Lead Engineer John Stanley
Auxiliary Power, Lube Oils, Fluids, and Air Requirements - Table A - Details of auxiliary loads.
- Table E Lube Oil Operating Requirements & Properties
- Table B - Not used.
- Table F1 Coolant Operating Requirements & Properties
- Table C - Not used.
- Table F2 Water Wash Operating Requirements & Properties
- Table D1 Gas Fuel Quality Requirements
- Table F3 Demineralized Water Operating Requirements & Properties
- Table D2 Liquid Fuel Quality Requirements
- Table G Instrument Air Operating Requirements & Properties
- Table D3 Water Quality Requirements
Power Load Table A Tag No.
Conn. No.
System/Component
95EVGT1
E257
95EVGT2
E260
95EVGT3
E263
88EVGT1
E256
Fan - GT Enclosure Ventilation #1 - See Note 15
88EVGT2
E259
Fan - GT Enclosure Ventilation #2 - See Note 15
88EVGT3
E262
Fan - GT Enclosure Ventilation #3 - See Note 15
Qty.
Power Ea.(kW) Normal Operation
Power Total (kW) Nornal Operation
3
0.05 (per heater)
0.15
Duty in Normal Operation Condition
Black Start See Note 21
Intermittent
N
Intermittent
N
Intermittent
N
Continuous
Y
Phase
Voltage
Hz
1
120VAC
60Hz
3
480VAC
60Hz
GT-Ventilation System (GED00162919) Anti-Con Heaters GT enclosure - Vent. Fans
3
74.6 (per motor)
223.8
Continuous
Y
Stand-By
N
95EVGTSH
E264
G/T Enclosure Space heater. See Note 3 & 6
1
7.5
7.5
Intermittent
N
3
480VAC
60Hz
97EVGTL1 - 4
E253
GT Enclosure - High Pressure Sodium Lamp
4
0.1
0.4
Intermittent
N
1
120VAC
60Hz
97EVGTEL1 - 2
E252
G/T Well Glass Light Fitting (emergency) 4 hours back up by UPS. See Note 24
2
0.1 (per light)
0.2
Intermittent
N
88IFS
E201
Fan - Secondary Air Duct (ASC) - See Note 25
1
55
55
Continuous
Y
3
480VAC
60Hz
95IFS
E203
Anti-Con Heater ASC Fan
1
0.08
1
Intermittent
N
1
120VAC
60Hz
97IFL1 - 2
E203
Internal Filter Access Lighting (Normal)
2
0.032 (per light)
0.064
Intermittent
N
1
120VAC
60Hz
0.072
Intermittent
N
1
120VAC
60Hz
24VDC
GT - Combustion System Air System (GED00181951)
97IFEL1 - 2
E203
Internal Filter Access Lighting (Emergency)
2
0.036 (per light)
97IFEL3
E203
External Filter Access Lighting (Emergency)
1
0.036 (per light)
0.036
Intermittent
N
1
120VAC
60Hz
E1
E202
Filter House Control Panel Anti Condensation Heater
1
0.1
0.1
Intermittent
N
1
120VAC
60Hz
E202
Filter House Control Panel Pulse Solenoid Enclosure Heaters
8
0.1 (per heater)
0.8
Intermittent
N
1
120VAC
60Hz
Anti-Con Heater Water Injection Pump Motor
3
Refer to MCC VFD Section
Heat Trace Water Injection Forwarding - See Note 6
1
26.2 watts / m (Approx. 10 m)
0.262
Intermittent
N
1
120VAC
60Hz
Motor - Pump - WLE / Water Injection - See Note 5 & 14
3
Refer to MCC VFD Section
Water Injection Metering System (GED00162923) 95WI1
E235
95WI2
E237
95WI3
E239
95WIH
E233
75WID1 / 88WI1
E234
75WID2 / 88WI2
E236
75WID3 / 88WI3
E238
88EVWI
E247
WIJ Enclosure Ventilation Fan Motor
1
1.5
1.5
Continuous
N
3
460VAC
60Hz
95EVWI
E249
WIJ Enclosure Ventilation Fan Motor Anti-Condensation Heater
1
0.05
0.05
Intermittent
N
1
120VAC
60Hz
97EVWI
E255
WIJ Enclosure - Fluorescent Lamp
2
0.032
0.064
Intermittent
N
1
120VAC
60Hz
Page 2 of 14
GED00329287, Rev 04
Power Load Table A Tag No.
Conn. No.
95FPLEGTH
E292
System/Component
Qty.
Power Ea.(kW) Normal Operation
Power Total (kW) Nornal Operation
Duty
Black Start
Phase
Voltage
Hz
1
1.8
1.8
Intermittent
N
1
120VAC
60Hz
2
7.5 (per motor)
15
3
480VAC
60Hz
0.04 (per heater)
0.08
1
120VAC
60Hz
243 (VFD) 215 (Motor)
458
3
380-690VAC (VFD)
60Hz
Fire & Gas System (GED00162924) CO2 Skid Enclosure Heater. See Note 6 GT Lube Oil System (GED00162916) 88QGH1
E240
Pump Motor- Hydraulic Control Oil
88QGH2
E241
Pump Motor - Hydraulic Control Oil
95QGH1
E242
Anti-Con Heater Pump Motor 1 - Hydraulic Cont. Oil
95QGH2
E243
Anti-Con Heater Pump Motor 2 - Hydraulic Cont. Oil
75SRM / 88SRM
E230
Electric Start Motor (Engine) See Notes 14, 18, 27
2
1
Continuous
Y
Stand-By
N
Intermittent
N
Continuous
Y
Intermittent
Y
95SRM
E330
Anti-Cond Heater Electric Start VFD Panel.
1
1
1
Intermittent
N
1
120VAC
60Hz
95QGT
E209
Gas Turbing Oil Reservoir Heater See Note 3
1
5
5
Intermittent
N
3
480VAC
60Hz
88QM
E277
AC Gen Mineral Lube Oil (GED00212216) Pump - AC Gen Lube Oil Motor
1
3.7
3.7
Intermittent
Y
3
460VAC
60Hz
95QM
E279
Anti-Con Heater Pump - AC Gen Lube Oil Motor
1
0.026
0.026
Intermittent
N
1
120VAC
60Hz
88QJ
E283
Pump - AC Gen Jacking Oil Motor
1
5.5
5.5
Intermittent
Y
3
460VAC
60Hz
95QJ
E284
Anti-Con Heater Pump - Jacking Oil Motor
1
0.035
0.035
Intermittent
N
1
120VAC
60Hz
88QMD
E220
AC Gen Blower Motor
1
1.5
1.5
Continuous
Y
3
480VAC
60Hz
95QMD
E286
Anti-Con Heater Pump - AC Gen Blower Motor
1
0.035
0.035
Intermittent
N
1
120VAC
60Hz
88QME
E280
AC Gen Lube Oil DC Motor (1 hr. UPS Backup) - See Note 4
1
0.37
0.37
Continuous
N
95QMT
E273
AC Gen Lube Oil Tank Heater- See Note 3
1
5.1
5.1
Intermittent
N
3
480VAC
60Hz
95GNS
E289
AC Gen Stator Anti-Cond Heater -See Note 19, 26
1
5.4
5.4
Intermittent
N
3
480VAC
60Hz
95GNE
E289
Heater AC Gen Exciter -See Note 19, 26
1
0.114
0.114
Continuous
N
3
480VAC
60Hz
95GNN
E289
Anti-Cond Heater Generator Neutral Cubicle -See Note 19,26 - Feeder breaker
1
0.5484
0.5484
Intermittent
N
3
480VAC
60Hz
95GNL
E289
Anti-Cond Heater Generator Line Cubicle -See Note 19,26 - Feeder breaker
1
0.5484
0.5484
Intermittent
N
3
480VAC
60Hz
2
Refer to MCC VFD Section
2
Refer to MCC VFD Section
4
Refer to MCC VFD Section
1
1.8
1.8
Intermittent
N
1
120VAC
60Hz
24VDC
AC Gen Instrumentation (GED00323699)
ISI system (GED00162921) See Note 12 75CPWD1 / 88CPW1
E294
Wet Compression Pump Motor No. 1 - See Note 14 & 16
75CPWD3 / 88CPW3
E296
Wet Compression Pump Motor No. 3 - See Note 14 & 16
75CPWD2 / 88CPW2
E298
Wet Compression Pump Motor No. 2 - See Note 14 & 16
75IFWD / 88IFW
E288
Inlet Fogging Pump Motor - See Note 14 & 16
95CPW1
E294A
Anti-Condensation Heater - Wet Compression Pump Motor No. 1
95CPW2
E296A
Anti-Condensation Heater - Wet Compression Pump Motor No. 2
95CPW3
E298A
Anti-Condensation Heater - Wet Compression Pump Motor No. 3
95IFW
E288A
Anti-Condensation Heater - Inlet Fogging Pump Motor
95CPW
E285
Demineralized Water Supply Trace Heating - See Note 6
Page 3 of 14
GED00329287, Rev 04
Power Load Table A Qty.
Power Ea.(kW) Normal Operation
Power Total (kW) Nornal Operation
Duty
Black Start
Phase
Voltage
Hz
Heat Trace Water Flush - See Note 6
1
26.2 watts / m (Approx. 3 m)
0.0786
Intermittent
N
1
120VAC
60Hz
E221
Anti-Cond heater- HP Liquid Fuel Pump Motor
1
0.26
0.26
Intermittent
N
1
120VAC
60Hz
E220
Pump - Liquid Fuel Pump Motor
1
110
110
Continuous
Y
3
460VAC
60Hz
Tag No.
Conn. No.
95WFH
E224
95FL1 88FL1
System/Component
Liquid Fuel Metering System (GED00162921)
Refer to MCC VFD Section Refer to MCC VFD Section
95WF
E224
Anti-Cond heater-Water Flush Pump Motor
1
75WFD/88WF
E225
Pump - Water Flush - (5 minutes to Gas)
1
90WSAC
E299
Power Supply to Wet Surface Air Cooler System
1
166.28
166.28
Continuous
Y
3
480VAC
60Hz
90UCP1A
E661
Unit Control Panel (GED00237475) See Note 20 Power Supply to Unit Control System (4 hr. UPS Backup)
1
2.07
2.07
Continuous
Y
1
120VAC
60Hz
90UCP1B
E661
Power Supply to Unit Control System (Commercial)
1
3.2
3.2
Continuous
Y
1
120VAC
60Hz
90UCP3
E661
Power Supply to UCP for Fire and Gas (with 24hr UPS Backup)
1
1.15
1.15
Continuous
Y
1
120VAC
60Hz
90VFD
E300
Continuous
N
3
480VAC
60HZ
75WID1 / 88WI1
E234
Continuous
N
75WID2 / 88WI2
E236
Continuous
N
3
460VAC
60Hz
75WID3 / 88WI3
E238
Continuous
N
95WI1
E235
Intermittent
N
95WI2
E237
Intermittent
N
1
120VAC
60Hz
95WI3
E239
Intermittent
N
75CPWD1 / 88CPW1
E294
Wet Compression Pump Motor No. 1 - See Note 14 & 16
75CPWD3 / 88CPW3
E296
Wet Compression Pump Motor No. 3 - See Note 14 & 16
3
460VAC
60Hz
75CPWD2 / 88CPW2
E298
Wet Compression Pump Motor No. 2 - See Note 14 & 16
75IFWD / 88IFW
E288
Inlet Fogging Pump Motor - See Note 14 & 16
3
460VAC
60Hz
1
120VAC
60Hz
Wet Surface Air Cooler (GED00327945) See Note 8
MCC VFD (GED00334581) See Note 7 Power Supply too MCC VFD Cabinet Motor - Pump - WLE / Water Injection - See Note 5 & 14
Anti-Con Heater Water Injection Pump Motor
95CPW1
E294A
Anti-Condensation Heater - Wet Compression Pump Motor No. 1
95CPW2
E296A
Anti-Condensation Heater - Wet Compression Pump Motor No. 2
95CPW3
E298A
Anti-Condensation Heater - Wet Compression Pump Motor No. 3
95IFW
E288A
Anti-Condensation Heater - Inlet Fogging Pump Motor
75WFD/88WF 95WF
1
665.09
665.09
3
90 (VFD) 45 (Motor)
Included in Power Supply 90VFD
3
0.1 (per heater)
Included in Power Supply 90VFD
2
30 (VFD) 15 (Motor)
Included in Power Supply 90VFD
Intermittent
N
Intermittent
N
2
30 (VFD) 18.7 (Motor)
Included in Power Supply 90VFD
Intermittent
N
4
0.12 (per heater)
Included in Power Supply 90VFD
Included in Power Supply 90VFD Included in Power Supply 90VFD
E225
Pump - Water Flush - (5 minutes to Gas)
1
8.4 (VFD) 2.2 (Motor)
E224
Anti-Cond heater-Water Flush Pump Motor
1
0.05
Page 4 of 14
Intermittent
N
Intermittent
N
Intermittent
N
Intermittent
N
Intermittent
N
Intermittent
N
3
460VAC
60Hz
Intermittent
N
1
120VAC
60Hz
GED00329287, Rev 04
Gas Fuel Quality Requirements - Table D1
Operating Requirements
Pressure (kPag) & Temperature (ºC)
Usage
Pressure: Maximum: Derived corresponding to ANSI Class 600 SS316L temperature or 6205 kPag (900 psig) whichever is lower. Gas Fuel See Note-22
Project Specific,See Note A,F,G,H
Temperature: Maximum:Derived corresponding to ANSI Class 600 SS316L pressure or 150° C (302° F) whichever is lower.
Where more than one gas fuel is to be used, where limits are outside these requirements, or where other fuel constituents are present, e.g. hydrogen (H 2), mercury (Hg), acetylene (C2H2), methanol (C2H3OH), ethanol (C3H5OH), benzene (C6H6), toluene (C7H8), heptane (C7H16)… , dodecane (C12H26)… , heptadecane (C17H36) and so on, refer to Rolls-Royce.
Gas fuel properties (where standard conditions; 15°C (59˚F) and 101.325kPa (14.696psia), apply to the fuel gas)
Units
Limits
Lower Calorific, or Heating, Value (LCV or LHV)
kJ/ m3 (Btu/SCF) kJ/kg (Btu/lb)
29 000 (780) minimum 34 000 (14 600) minimum
Wobbe Index {LCV / (√SG)}
kJ/ m3 (Btu/SCF)
34 500 (925) minimum 51 000 (1 370) maximum
%
(+/-) 5 maximum
Wobbe Index variation to an agreed datum (Minimum and maximum limits must also apply) Gas fuel constituents
Units
Limits
Methane (CH4)
65 minimum
Ethane (C2H6)
13.0 maximum
Propane (C3H8)
7.0 maximum
Butane (C4H10)
4.0 maximum
% Volume
Pentane (C5H12)
0.80 maximum 0.30 maximum
Hexane (C6H14)
Inert gases, including carbon dioxide (CO2) and nitrogen (N2) Any form of sulphur, including hydrogen sulphide (H2S) and sulphur dioxide (SO2) See Notes B and C Fuel contaminants / corrosive constituents Oil – Concentration Oil - Droplet size
Consult Rolls-Royce for project specific inert gas limits All sulphur entering the gas turbine will affect unit life and will result in SOx emissions “sulphur-in = sulphur out”. Consult Rolls-Royce for expected unit life.
Units
Limits
ppm by weight 10-6m (microns)
2 maximum 0.5 maximum
No other liquids or hydrates are permissible – see Note D Particle size
10-6 (microns)
20 Absolute
Sodium plus potassium B, C and E
ppm by weight
0.6 maximum
Page 5 of 14
GED00329287, Rev 04
Liquid Fuel Quality Requirements Table D2
Pressure (kPag) and Temperature (°C)
Operating Requirements
Usage
Pressure 35 - 345 Distillate (Fuel Oil)
Min. 4.4 Kg/s Max. 5.2 Kg/s Also See Note H
Temperature Min: Above Cold Filter Plugging Point, 0°C, or '5 + Cloud Point', which ever is highest of the three. Max: 10 below flash point or 50°C, whichever is lowest.
Physical properties Paramount to Acceptability
Units
Minimum
Maximum
Test Method(s) (Latest Standards Apply)
Fuels falling outside of these limits must be referred to Rolls-Royce for Evaluation Aromatic Content
% Volume
5
40
ASTM-D1319 / IP156 - See notes I and J
Consult Rolls-Royce where either the total aromatic content is over 25% volume or where control of smoke emissions is a requirement. Additional testing may be required. Carbon Residue on 10% bottoms (Conradson or Ramsbottom)
% Weight
-
0.35
Fuel Temperature must be at least 5°C above the cloud point throughout the gas turbine fuel delivery system.
Cloud Point
ASTM-D189 / ASTM-D524 / ASTM-D4530 / IP13 / IP14 ASTM-D2500 / IP219
Distillation Data 10% volume recovery
250 (482) °C (°F)
90% volume recovery
-
Final Boiling Point
ASTM-D86 / IP123
385 (725)
Flash Point
Fuel Temperature must be at least 10°C below the flash point
Smoke Point Viscosity (Kinematics) See notes L
357 (675)
ASTM-D56 / ASTM-D93 / ASTM-D3828 / IP34 / IP170 - See Notes K
Mm
17
-
ASTM-D1322 / IP57
mm /s (centistokes)
1
11
ASTM-D445 / IP71
2
Page 6 of 14
GED00329287, Rev 04
Liquid Fuel Quality Requirements Table D2 (continued) Fuel Cleanliness Properties Paramount to Acceptability
Units
Maximum
Test Method(s) Latest standards apply (Rolls-Royce should be consulted and for advice on test methods.)
Fuels falling outside of these limits must be referred to Rolls-Royce for Evaluation Ash
% Weight
0.01
ASTM-D482 / IP4 See Note N
Trace metals - see Notes O, P, and Q Calcium
0.5
Lead
0.5
ASTM-D3605
ppm by weight Sodium plus Potassium
0.6
Vanadium
0.5 Rolls-Royce should be consulted to agree any proposal fuel treatments All sulphur entering the gas turbine will affect unit life and will result in SOx emissions "sulphur-in = sulphur-out". Consult Rolls-Royce for expected unit life.
Sulphur See Notes O, P, and Q
Free water and sediment
% Weight
1.0
ASTM-D129 / ASTM-D1266 / ASTM-D1552 / ASTM-D4294 / IP61 / IP336 See Notes R and S
% Volume
0.05
ASTM-D1796 / ASTM-D2709 See Note T
mg/liter
ASTM-D2276 / ASTM-D5452
Particulates
3.0 g/m3
Particle Size
ASTM-D6217 / IP415
10-6 m (microns)
2 micron nominal
Rolls-Royce must be consulted if any other contaminants are present, e.g. arsenic, cadmium, chromium, copper, lead, manganese, mercury, nickel, selenium, zinc, or any other constituent(s) not mentioned above.
Page 7 of 14
GED00329287, Rev 04
Water Quality Requirements - Table D3
Acceptable water shall be prepared and controlled in accordance with ASTM-D1193 as Type IIIA or Type IVA and shall meet the requirements specified below - see Notes 1A and 2A Appearance
Clear and colourless
Water Temperature
Conditions shall be such that no ice or steam forms
Units
Minimum
Maximum
Test Methods(s) See Note 3A
pH
6.0
8.0
ASTM-D5128 OR ASTM-D5464
Conductivity at 25°C - see Notes 4A, 5A, 6A, 8A, 9A, 10A, and 11A
µS/cm
-
1.0
ASTM-D5391
Silica - see Note 12A
wppm
-
0.05
ASTM-D859 OR ASTM-D4517
Calcium plus Magnesium - see Notes 13A and 12A
wppm
-
0.08
Sodium - see Notes 13A and 12A
wppm
-
0.1
Potassium - see Notes 13A and 12A
wppm
-
0.1
Total metals (to include sodium, potassium, calcium, and magnesium) - see Notes 14A and 12A
wppm
-
0.3
ASTM-D3919 PLUS ASTM-D4190
Chlorides - see Note 12A
wppm
-
0.2
ASTM-D4327
Total sulphates, sulphides, and phosphates - see Note 12A
wppm
-
1.0
ASTM-D4327 PLUS ASTM-D4658
Parameter
Acidity - see Notes 4A, 5A, 6A, and 7A
µm
Filtration - see Notes 4A, 11A, and 15A
ASTM-D3919
10 nominal 40 absolute
Consult Rolls-Royce if any other constituents/contaminants are present. Refer to Note 14A.
Page 8 of 14
GED00329287, Rev 04
Lube Oils
Table E
Operating Requirements
Pressure (kPag)
Temperature (ºC)
Usage
Remarks Reservoir Capacity: 646 Liters R-R Approved Oils: BPTO 2197 Mobil Jet Oil II
Synthetic Lube Oil (TRENT) See Note 23
Supply pressure at engine 50 - 65° C (122 - 149° F) normal operation interface L20 for ISA day 15° C (59° F) start-up 1805 kPag
Mobil Jet 254 LO consumption = 0.2 l/hr. (0.05 gph)
Replenish Interval: ~ 6 months (Depending on oil condition, periodic oil analysis is recommended) Additional oil is needed for initial fill of piping and cooler Nominal capacity: 2173 liters (574 gallons) R-R Approved Oils: ISO VG 32/46 Mineral (A/C Generator) Main Lube Oil See Note 23
Oil inlet pressure 130 - 150 kPa (1.3 - 1.5 bar)
45-55°C normal operation
LO consumption = 0.003 l/hr. (0.0008 gph) Replenish Interval: ~ 6 months (Depending on oil condition, periodic oil analysis is recommended) Additional oil is needed for initial fill of piping and cooler
Page 9 of 14
GED00329287, Rev 04
Water
Table F
Coolant Table F1 Operating Requirements
WCAC, Lube Oil, & L5 See Note 23
P30 Cooler See Note 23
AC Gen Lube Oil Heat Exchanger
Pressure (kPag) Customer shall maintain a minimum differential pressure of 170 kPa between the GT Skid edge supply and return connections. Maximum supply pressure at GT skid edge shall not exceed 1000 kPag. Coolant supply pressure shall not exceed 900 kPag. Maximum pressure drop in the coolant line is 30 kPa at the required coolant flow rate. Maximum supply pressure is 10.3 bar (150psi). Allowable pressure drop between supply and return is 0.48 bar.
Temperature (ºC)
Usage
Maximum coolant temperature shall not exceed 45°C
Heat Load
Flow required to maintain the minimum Heat load differential pressure is 520 kW (Refer Note Y) 668 lpm (Refer Note X)
Maximum coolant temperature shall not exceed 50°C
Flow of 300 +/- 20 lpm shall be maintained.
Heat load 265 kW (Refer Note Y)
Maximum coolant temperature shall not exceed 51.3°C
256.2 lpm
Heat load 95 kW
Temperature (ºC)
Usage
Remarks
Coolant shall be composed of either ethylene glycol / water mixture or fresh water only. Water must conform to GER0144 standards. Coolant composition shall be determined by customer to assure that coolant does not freeze at site minimum ambient. The coolant shall not contain more than 60% ethylene glycol under any circumstance. Chloride content shall not exceed 50ppm by weight (50mg/Kg). Filtration of supply water to the exchanger shall be better than 0.5mm ( 500 micron) absolute (Beta ratio = 200). See Note U,V,W.
Water Wash Table F2 Operating Requirements
Pressure (kPag)
Remarks Water
TRENT Wash - Crank/Soak Wash Cycle (one each wash)
N/A
5 to 40°C
41 liters (each cycle) 80% Water 20% Cleaning fluid
De-mineralized total dissolved solids < 10 ppm acidity 5 < pH < 8 silica < 3 ppm conductivity < 11x10-6 mhos/cm (Siemens/cm) Cleaning fluids
Rinse Cycle (two each wash)
N/A
5 to 40°C
41 liters (each cycle) 100% Water
Pressure (kPag)
Temperature (ºC)
Usage
Ardrox 6345 Ardrox 6367 RMC G21 Techniclean GT (ZOK27) Techniclean GT2 (Castrol ICD 177) Castrol ICD 177 pre-mixed Fyrewash F3 Turbo K JAD-MA 109C ProtoKlenz GT
Demineralized WaterTable F3 Operating Requirements
Remarks Water
Water injection - See Note 23
Min. 200 Max. 600
Total matter Min. 45 lpm Max. 341 lpm
5 to 40°C
ISI - Wet Compression/ Inlet Fogging
Min. 280 Max. 320
5 to 40°C
Min. 5.71 lpm Max. 182 lpm
Water Flush
Min. 0 Max. 400
5 to 40°C
4.0 lpm
Page 10 of 14
< 2 ppm
Dissolved matter
< 0.5 ppm
Total sodium + potassium
< 0.2 ppm
GED00329287, Rev 04
Instrument Air Table G Operating Requirements
Instrument Air
Pressure (kPag)
Temperature (ºC)
Min. 550 Max. 830
10 to 40°C
Remarks
Air quality: (i) The medium supplied must be free of contamination caused by dust dirt or metallic particles and not contain any other toxic, corrosive or combustible ingredients; (ii) All particulate matter must not to exceed 10µm (micron) particle size. The total concentration of particulate matter not to exceed 0.05 mg/m³ of the medium; (iii) The total content of sodium and potassium to the medium expressed as chloride not to exceed 0.001 ppm, by weight; (iv) Oil mist to be less than 0.5 mg/m3 (v) Temperature 10°C to 40°C (vi) Shop air shall be relatively dry and shall have a Dew point of