Type 4100Z Wizard I Gauge Pressure Controller
April 13, 2023 | Author: Anonymous | Category: N/A
Short Description
Download Type 4100Z Wizard I Gauge Pressure Controller...
Description
Bulletin 34.3:4100Z
April 2000
Type 4100Z Wizard I Gauge Pressure Controller The Type 4100Z Wizard I pneumatic controller combines a simple principle of operation and few moving parts with a rugged construction to make an ideal pressure controller for demanding installations.
Features Corrosion Resistant Latch and Hinges —Nylon shoulder bearings and stainless steel hinge pins eliminate metal-to-metal contact and prevent corrosion of moving parts Easy to Maintain —Deep-shelled cover allows easy access to all parts for adjustment or routine maintenance inspection Easy to Adjust —Controlled —Controlled pressure setting is a single knob adjustment. The proportional band is ad-
justed fulcrum pin along a graduated scale. by moving the fulcrum Easy to Reverse —Just move the orifice block block and fulcrum pin to the opposite side of the flapper and rotate each 180 degrees
W5595 / IL
Figure 1. Type 4100Z Controller
COVER
NYLON BEARINGS
A1133 / IL
CASE
W7937 / IL
Figure 2. Ty Type pe 4100Z Controller with the Cover Open
2 1 0 X 5 4 0 0 0 2 D
Bulletin 34.3:4100Z Specifications Input Signal(1) Type: Positive pressures from process gas or liquid Type: Positive Input Span(1): Maximums range from 3.4 to 517 bar (50 to 7500 psig). See table 1. Lower Range Limit(1): 0 psig Upper Range Limit(1): Maximums range from 3.4 to 517 bar (50 to 7500 psig). See table 1. Controller Output Signal(1) 0.2 to 1.0 bar (3 to 15 psig) or 0.4 to 2.0 bar (6 to 30 psig) Action: Field Action: Field reversible between direct (increasing sensed pressure increases output pressure) or reverse (increasing sensed pressure decreases output pressure). The suffix letter R is added to the type number of a construction specified for reverse action.
Control Modes(1) Proportional-Only Supply Pressure Requirements Type: Clean, non-corrosive gas(2) or air Type: Clean, Minimum Pressure Proportional: 1.4 bar (20 psig) for 0.2 to 1.0 bar (3 to 15 psig) output signal or 2.4 bar (35 psig) for 0.4 to 2.0 bar (6 to 30 psig) output signal Steady-State Air Consumption See table 2 Supply and Output Pressure Indicators 0 to 30 psig/0 to 0.2 MPa/0 to 2.0 bar triple scale gauges for 0.2 to 1.0 bar (3 to 15 psig) output signal or 0 to 60 psig/0 to 0.4 MPa/0 to 4.0 bar triple scale gauges for 0.4 to 2.0 bar (6 to 30 psig) output signal
Inlet Pressure Capability Maximum Working Pressure: Same Pressure: Same as maximum Bourdon tube rating as shown in table 1 1. 2. 3. 4.
2
Maximum Static Pressure: Same as maximum Bourdon tube rating as shown in table 1 Operative Ambient Temperature Limits(1)(3) – 40 40 to 71C ( – – 40 40 to 160F) Construction Materials Controller Case: Controller Case: Aluminum Cover: Aluminum Cover: Aluminum Aluminum Cover Gasket: Foam Gasket: Foam elastomer Gauges: Steel Gauges: Steel case with brass wetted w etted parts Bourdon Tube(4): 316 SST or K-Monel Controlled Pressure Block(4): Stainless steel Controlled Pressure Block Gasket: Neoprene Gasket: Neoprene Supply & Output Tubing: Stainless Tubing: Stainless steel Controlled Pressure Tubing(4): Stainless steel Nozzle: Stainless Nozzle: Stainless steel Orifice Block: Aluminum Block: Aluminum Connections Input Signal Connection Size: 1/4 inch NPT female or optional 1/2 inch NPT female for nipple mounting Location: On back and On side Output of case Signal ConnecSupply Pressure tions Size: 1/4 1/4 inch NPT female Location: On On back side of case Mounting Yoke, Panel, Surface, Pipestand, or Nipple Weight Approximately 3.1 kg (6.75 lbs) Options Supply Regulator: Type Regulator: Type 67CFR regulator Auxiliary Regulator: Type Regulator: Type 1301F regulator to reduce high pressures to Type 67CFR range (system must include overpressure protection) Bourdon Tube Protectors: To Protectors: To prevent corrosive or clogging fluids from entering bourdon tubes; welded diaphragm seal and flexible tubing factory-welded to control connection of controller; rated for input signal to 172 bar (2500 psig) Dual Scale Gauges: Gauges: 0 to 30 psig/0 to 2 kg/cm2 or 0 to 60 psig/0 to 4 kg/cm2
Ter Term m defined in ISA Standard S51.1. If supply gas is flammable or noxious, the controller m must ust be located in a well-ventilated, non-hazardous non-hazardous area. Also for transportation and and storage limits. Proce Process ss wetted wetted part
Bulletin 34.3:4100Z Table 1. Bourdon Tube Ranges
Bar
Psig
0 to 3.4 0 to 6.9 0 to 17.2 0 to 34.5 0 to 68.9 0 to 103 0 to 172 0 to 345 0 to 517
0 to 50 0 to 100 0 to 250 0 to 500 0 to 1000 0 to 1500 0 to250 to25 o 00 0 to 5000 0 to 7500
Table 2. Steady-State Air Consumption (1)
SUPPLY PRESSURE
WITH SMALL ORIFICE(2)
WITH LARGE ORIFICE(3)
Bar
Psig
m3/h
Scfh
m3/h
Scfh
1.4
20
0.40
15
0.94
35
2.4
35
0.54
20
1.3
50
1. m3 /h —cubic —cubic meters per hour (0C and 1.01325 bar, absolute); Scfh —standard —standard cubic feet per hour (60F and 14.7 psia) 2. Use o orifice rifice size 72 72 – 6 60 0 when controller is used with actua tors up to size 50. 3. Use o orifice rifice size 60 60 – 5 50 0 when controller is used with actua tors size 50 and larger.
Construction Features Refer to figure 3. This proportional controller, when used with suitable control valves, maintains a controlled pressure within a set range. This control range is called the proportional band and may be defined as the change in controlled pressure required to cause a full change in controller output pressure. For example, a controller with a Bourdon tube rated at 6.9 bar (100 psig) is yoke-mounted on a direct-acting control valve which is i s maintaining downstream pressure at 3.4 bar (50 psig). A proportional band adjustment of 2 percent causes the valve plug to close at 3.5 bar (51 psig) and completely open at 3.3 bar (49 psig). With proportional band set at 50 percent, the valve plug reaches the closed position at 5.2 bar (75 psig) controlled pressure and the wide open position at 1.7 bar (25 psig). psi g).
32A1473 – A 32A1473 – A1136 – 1 1/IL /IL
Figure 3. Type 4100Z Operation Schematic
clean, dry air or non-corrosive gas. If the supply gas is flammable or noxious, the controller must be located in in a well-ventilated non-hazardous area.
Ordering Information When ordering, please specify the following:
Overpressure Protection
1. Complete controller type number
To avoid personal injury and equipment damage, do not exceed the pressure limitations stated for each respective unit in the system. Pressure ratings are stamped on the instruction plate and Bourdon tube. The regulator pressure ratings are stamped on the regulator spring case. If supply or inlet pressures can exceed any of the pressure limitations, overpressure protection, such as a relief valve, is necessary.
2. Bourdon tube material 3. Process pressure range 4. Process set point 5. Desired output signal and action 6. Orifice size (if actuator requirements are known)
Installation Controller dimensions are shown in figure 4. The 4. The controller can be remote-mounted or ordered as part of a control valve assembly. The supply medium must be
7. Type of mounting (yoke, pipestand, panel, surface, or nipple) 8. Optional equipment desired
3
Bulletin 34.3:4100Z 57.2 (2.25) 28.4 (1.12)
219 (8.62)
203 (8.00) 50.8 (2.00)
95 (3.75)
50.8 (2.00)
150 (5.91)
195.1 (7.68)
160.3 (6.31) 31A6840-B B0601-3 / IL
mm (INCH)
Figure 4. Dimensions
Wizard, Fisher and Fisher-Rosemount are marks owned by Fisher Controls International, Inc. or Fisher-Rosemount Systems, Inc. All other marks are the property of their respective owners. Fisher
Controls International, Inc. 1990, 2000; All Rights Reserved
For information, contact Fisher Controls: Marshalltown, Marshalltow n, Iowa 50158 USA Cernay 68700 France Sao Paulo 05424 Brazil Singapore 128461 4
Printed in U.S.A.