Txr to 11kv Ais Cab Size
Short Description
Txr to 11kv Ais Cab Size...
Description
This document is the property of Larsen & Toubro Limited, ECC Division - EDRC and must not be passed on to any third person or firm not authorised by us, nor be copied/made use of in full or part by such person or firm without our prior permission writing
DATE
REV. NO.
DESCRIPTION REVISIONS
CHECKED
APPROVED
LARSEN & TOUBRO LIMITED ECC Division – EDRC CLIENT :
CONSULTANT :
PROJECT : MAGADI PURE ASH PROJECT O3324-E-NF
JOB No.
TOTAL NO. OF PAGES NAME SIGN
TITLE : DATE
DSGN
PTS
21.03.05
CHKD
SKW
24.03.05
APPD
HVB
26.03.05
DESIGN CALCULATION - MV CABLE SIZE
CODE DOC.No. 2
RELEASED FOR
0
7
6
-
L
PRELIMINARY
T
-
0
0
0
TENDER
-
E
L
-
D
INFORMATION
C
-
3
0
APPROVAL
5
9
CONSTRUCTION
REV. 0
2 of 16
LARSEN & TOUBRO LIMITED ECC Division - EDRC PROJECT
TITLE
:
:
DOCUMENT NO
ADWEA
DATE
2076-LT-000-EL-DC-3059-00
DESIGN CALCULATION - MV CABLE SIZING
PREPARED
DESIGN CALCULATION
MV CABLE SIZING
CHECKED
3/12/2016 SHEET
3 of 16
LARSEN & TOUBRO LIMITED ECC Division - EDRC PROJECT
TITLE
:
:
ADWEA
DESIGN CALCULATION - MV CABLE SIZING
DOCUMENT NO
DATE
2076-LT-000-EL-DC-3059-00 PREPARED
CHECKED
3/12/2016 SHEET
4 of 16
LARSEN & TOUBRO LIMITED ECC Division - EDRC PROJECT
TITLE
:
:
DOCUMENT NO
ADWEA
DATE
2076-LT-000-EL-DC-3059-00
DESIGN CALCULATION - MV CABLE SIZING
PREPARED
CHECKED
INDEX 0.0.0
SYMBOLS & UNITS
3
1.0.0
DESIGN INPUTS
4
2.0.0
ENVIRONMENTAL DETAILS
4
3.0.0
CABLE DATA
4
4.0.0
TYPE OF LAYING
5
5.0.0
CHECKING OF SHORT CIRCUIT WITHSTAND CAPABILITY
5
6.0.0
CHECKING OF THERMAL AMPACITY
5
7.0.0
CHECKING OF STEADY STATE VOLTAGE DROP
6
8.0.0
RESULT
7
9.0.0
ANNEXURE-1 : TABLE FOR ALL CABLES
8
3/12/2016 SHEET
5 of 16
LARSEN & TOUBRO LIMITED ECC Division - EDRC PROJECT
TITLE
:
:
ADWEA
DESIGN CALCULATION - MV CABLE SIZING
DOCUMENT NO
DATE
2076-LT-000-EL-DC-3059-00 PREPARED
CHECKED
3/12/2016 SHEET
6 of 16
LARSEN & TOUBRO LIMITED ECC Division - EDRC PROJECT
TITLE
0.0.0
ADWEA
:
:
DESIGN CALCULATION - MV CABLE SIZING
DOCUMENT NO 2076-LT-000-EL-DC-3059-00 PREPARED
SYMBOLS & UNITS A
Area of cross section of conductor
A1
De-rating factor for Air temperature
A2
De-rating factor for grouping
A3
De-rating factor for
Sq.mm
cosQ Power factor E/UE Earthed / un-earthed voltage rating of cable
kV
Eff
Efficiency
%
f
Supply Frequency
Hz
G1
De-rating factor for Variation in Ground temperature
G2
De-rating factor for Variation in Thermal Resistivity of soil
G3
De-rating factor for Depth of laying
G4
De-rating factor for Horizontal formation
Ic-Air
Current carrying capacity of conductor in Air
A
Ic-DR
De-rated Continuous rating of conductor
A
Ic-Gd
Current carrying capacity of conductor in Ground
A
IF
Short Circuit withstand capacity required
kA
IL
Load Current
A
Isc
Short circuit withstand current of Conductor
kA
K-Air Overall de-rating factor for Air Kd
DATE
Derating factor
K-Gd Overall de-rating factor for Ground L
Length of Cable
n
No. of runs of cables
Mtrs
P
Real Power of Load
kW
Q
Reactive Power of Load
kVAR
R
Resistance of Cable for the length selected
Ohm
Rc
AC Resistance per unit length of Cable
ohm/Km
S
Apparent Power of Load
kVA
T
Design Ambient Temperature
o
t
Duration of Fault withstand capability
seconds
V
System Voltage
Volts
Vc
Voltage Grade of Cable
Vd
Voltage drop
V
X
Reactance of of Cable for the length selected
Ohm
Xc
Inductive reactance of cable
ohm/Km
C
CHECKED
3/12/2016 SHEET
7 of 16
LARSEN & TOUBRO LIMITED ECC Division - EDRC PROJECT
TITLE
:
:
ADWEA
DESIGN CALCULATION - MV CABLE SIZING
DOCUMENT NO
DATE
2076-LT-000-EL-DC-3059-00 PREPARED
CHECKED
3/12/2016 SHEET
8 of 16
LARSEN & TOUBRO LIMITED ECC Division - EDRC PROJECT
TITLE
1.0.0
DOCUMENT NO
ADWEA
:
:
DATE
2076-LT-000-EL-DC-3059-00 PREPARED
DESIGN CALCULATION - MV CABLE SIZING
CHECKED
3/12/2016 SHEET
DESIGN INPUTS
Load Details 1.1.1
Load Description
:
11Kv SWGR
1.1.2
Fed By
:
Transformer
Inputs 1.2.1
System Voltage
V
:
11 kV
1.2.2
Frequency
f
:
50 Hz
1.2.3
Short Circuit withstand capacity required
IF
:
31.5 kA
1.2.4
Duration of fault withstand capacity
t
:
1.2.5
Load
S
:
1.2.6
Load power factor
CosQ :
1.2.7
Length of cable
L
:
1.2.8
Efficiency
Eff
:
2.0.0
ENVIRONMENTAL DETAILS
2.1.1
Design Ambient Temperature
T
:
3.0.0
CABLE DATA
3.1.0
Voltage Rating
:
3.1.1
No. of Cores
:
3.1.2
Cross Section Area
3.1.3
Conductor Material (Copper / Aluminium)
:
Copper
3.1.4
Insulation
:
XLPE
3.1.5
Catalogue Reference
:
Polycab
3.1.6
Current carrying Capacity
3.1.7
Resistance of Conductor
A
(Refer Spec E-005, 250MVA)
1 s 20000 kVA 0.9 50 m 90.00%
50 oC
(Std Tech & Site Data -AppendixA)
6.6kV(UE)/11kV(E) 1
:
500 Sq.mm
Ic-Air
:
800 A
Table-24
Ic-Gd
:
565 A
Table-24
Rc
:
0.0468 Ohm/KM
Table-1
9 of 16
LARSEN & TOUBRO LIMITED ECC Division - EDRC PROJECT
TITLE
:
:
DOCUMENT NO
ADWEA
DATE
2076-LT-000-EL-DC-3059-00 PREPARED
DESIGN CALCULATION - MV CABLE SIZING
3.1.8
Reactance of Conductor
Xc
:
3.1.9
Short circuit withstand current of Conductor
Isc
:
3.1.10
No. of Runs selected
n
:
CHECKED
0.107 Ohm/KM 71.4 kA for 1 sec 2
3/12/2016 SHEET
Table-4 Table-2
10 of 16
LARSEN & TOUBRO LIMITED ECC Division - EDRC PROJECT
TITLE
:
:
DOCUMENT NO
ADWEA
DATE
2076-LT-000-EL-DC-3059-00 PREPARED
DESIGN CALCULATION - MV CABLE SIZING
CHECKED
4.0.0
Type of Laying
4.1.0
Laying in Ground
4.1.1
Ground Temperature
:
45
4.1.2
Variation in Thermal Resistivity of Soil
:
150
4.1.3
Depth of Laying
:
1
m
4.1.4
Horizontal formation, No. of Cables and & space
:
4, 30
cm
4.2.0
Laid in Air
4.2.1
Air Temperature
:
50
o
4.2.2
Horizontal formation (Touching or Spacing)
:
1 Dia
4.2.3
No. of Cables and No. of Tiers
:
3, 1
5.0.0
CHECKING OF SHORT CIRCUIT WITHSTAND CAPABILITY Fault withstand capacity of cable for 1 sec
:
Duration of Fault withstand capacity of cable required
t :
Fault withstand capacity of cable for required duration
:
3/12/2016 SHEET
C
o
C
71.4 kA
(From 3.1.9)
1 sec Isc /Sqrt(t) x n
:
142.8 kA
----- (1)
IF
:
31.5 kA
----- (2)
G1
:
0.87
Table 5-1B
De-rating factor for variation in Thermal Resistivity of Soil G2
:
1
Table-5-3
De-rating factor for Depth of Laying
G3
:
0.99
Table-5-2
Horizontal formation (Touching or Spacing)
G4
:
0.72
Table-6 D
Over all derating factor for Ground
K-Gd
:
G1xG2xG3xG4xG5
Short circuit withstand capacity required
(From 1.2.3)
Since (1) is greater than (2), the cable is safe
6.0.0
CHECKING OF THERMAL AMPACITY
6.1.0
Calculation of De-rating factor for laying in Ground De-rating factor for variation in Ground Temperature
11 of 16
LARSEN & TOUBRO LIMITED ECC Division - EDRC PROJECT
TITLE
:
:
DOCUMENT NO
ADWEA
DATE
2076-LT-000-EL-DC-3059-00 PREPARED
DESIGN CALCULATION - MV CABLE SIZING
: K-Gd
:
CHECKED
0.87 x 1 x 0.99 x 0.72 0.620136
3/12/2016 SHEET
12 of 16
LARSEN & TOUBRO LIMITED ECC Division - EDRC PROJECT
TITLE
6.2.0
6.3.0
:
:
DOCUMENT NO
ADWEA
2076-LT-000-EL-DC-3059-00 PREPARED
DESIGN CALCULATION - MV CABLE SIZING
CHECKED
De-rating factor for Air Temperature
A1
:
0.9
De-rating factor for grouping
A2
:
0.96
Over all derating factor for Air
K-Air
:
A1 x A2
:
0.9 x 0.96
SHEET
K-Air
:
Ic-DR
:
Ic-Air x K-Air A
:
800 x 0.864 A
:
691 A
:
Ic-GD x K-Gd A
:
565 x 0.6201A
:
350 A
Table 5-1A
0.864
Calculation of De-rated current carrying capacity
De-rated Current Carrying capacity of Cable in Ground
Ic-DR
De-rated Current Carrying capacity of cables selected
: :
Current Carrying capacity required Load Current
IL
Minimum of Ground & Air x n 1382 A
----- (3)
:
Load Current
:
S / Sqrt(3) / V / Eff
:
20000/1.732/11/0.9
:
1166 A
----- (4)
Since (3) is greater than (4), the cable is safe 7.0.0
3/12/2016
Calculation of De-rating factor for laying in Air
De-rated Current Carrying capacity of Cable in Air
6.4.0
DATE
CHECKING OF STEADY STATE VOLTAGE DROP Steady state voltage drop
Vd
:
I (R CosQ + X SinQ)
Resistance of cable for the length selected
R
:
Rc x L / 1000 / n
:
0.0468 x 50/1000 / 2
:
0.00115 Ohm
Reactance of cable for the length selected
X
:
Xc x L / 1000 / n
:
0.107 x 50/1000 / 2
:
0.0027 Ohm
13 of 16
LARSEN & TOUBRO LIMITED ECC Division - EDRC PROJECT
TITLE
:
:
DOCUMENT NO
ADWEA
2076-LT-000-EL-DC-3059-00 PREPARED
DESIGN CALCULATION - MV CABLE SIZING
Steady state voltage drop
Percentage Voltage drop
DATE
Vd
3/12/2016
CHECKED
SHEET
:
1166( 0.00115x0.9+0.0027x0.435889894354067)
:
2.57907857 v
%VD : : :
Vd / V /1000 / 1.732 * 100 2.57907856540547/11/1000/1.732*100 0.01 %
----(5)
14 of 16
LARSEN & TOUBRO LIMITED ECC Division - EDRC PROJECT
TITLE
DOCUMENT NO
ADWEA
:
:
DESIGN CALCULATION - MV CABLE SIZING
Allowed voltage drop
DATE
2076-LT-000-EL-DC-3059-00 PREPARED
:
CHECKED
5 %
3/12/2016 SHEET
----(6)
Since (5) is lesser than (6), the cable is safe
11.0.0
RESULT a)
Cable Selected
:
6.6kV(UE)/11kV(E)Core x 500 Sq.mm XLPE Copper Cable
b)
No.of runs
:
2 run
c)
Maximum Voltage Drop (%)
:
0.01%
d)
SC Withstand Capability
:
142.8
kA
15 of 16
LARSEN & TOUBRO LIMITED ECC Division - EDRC PROJECT
TITLE
:
:
ADWEA
DESIGN CALCULATION - MV CABLE SIZING
DOCUMENT NO
DATE
2076-LT-000-EL-DC-3059-00 PREPARED
CHECKED
3/12/2016 SHEET
Annexure-I to MV Cable Sizing Calculation Design Inputs
SI.No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
From 000SG911 000SG911 000SG911 OH-1 OH-2 OH-3 000SG911 000SG911 000CM911 000CM911 000CM911 000CM911 000CM911 000CM911 000CM911
To OH line-1 OH line-2 OH line-2 000TF922 000TF922 000TF922 000CM911 000CM911 400FN020 400FN030 400FN035 400FN050 400ML010 510FN010 600FN020
Description Power supply to Transformer 000TF922 Power supply to Transformer 000TF923 Power supply to Transformer 000TF924 Power supply to Transformer 000TF922 Power supply to Transformer 000TF923 Power supply to Transformer 000TF924 Power supply to 000CM911 Power supply to 000CM912 Roller Mill Fan Roller Mill ESP ID Fan Dilution Air Recirculation Fan Primary combustion Air Fan Roller Mill First Stage Crystaliser Vent Fan Dryer Air Blower
Voltage (kV) 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5
Fault Current IF (kA) 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2
Fault w/s time (sec) 1 1 1 1 1 1 1 1 0.1 0.1 0.1 0.1 0.1 0.1 0.1
kW Rating
870 825 350 250 780 186.4 230
kVA Rating
Cable Data
Efficiency Cos Q SinQ
3000 3000 3000 3000 3000 3000 3610 3610 0 0 0 0 0 0 0
0.985 0.985 0.985 0.985 0.985 0.985 0.9 0.9 0.95 0.95 0.95 0.95 0.95 0.95 0.95
0.83 0.85 0.85 0.83 0.85 0.85 0.87 0.87 0.86 0.86 0.87 0.89 0.86 0.88 0.88
0.56 0.53 0.53 0.56 0.53 0.53 0.49 0.49 0.51 0.51 0.49 0.46 0.51 0.47 0.47
Length (m) 160 160 160 65 65 65 160 85 180 130 130 150 200 134 100
Insulation HT-XLPE HT-XLPE HT-XLPE HT-XLPE HT-XLPE HT-XLPE HT-XLPE HT-XLPE HT-XLPE HT-XLPE HT-XLPE HT-XLPE HT-XLPE HT-XLPE HT-XLPE
SC w/s Capability SI.No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
SI.No 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
From 000SG911 000SG911 000SG911 OH-1 OH-2 OH-3 000SG911 000SG911 000CM911 000CM911 000CM911 000CM911 000CM911 000CM911 000CM911
From 000SG911 000SG911 000SG911 OH-1 OH-2 OH-3 000SG911 000SG911 000CM911 000CM911 000CM911 000CM911 000CM911 000CM911 000CM911
To OH line-1 OH line-2 OH line-2 000TF922 000TF922 000TF922 000CM911 000CM911 400FN020 400FN030 400FN035 400FN050 400ML010 510FN010 600FN020
To OH line-1 OH line-2 OH line-2 000TF922 000TF922 000TF922 000CM911 000CM911 400FN020 400FN030 400FN035 400FN050 400ML010 510FN010 600FN020
Description Power supply to Transformer 000TF922 Power supply to Transformer 000TF923 Power supply to Transformer 000TF924 Power supply to Transformer 000TF922 Power supply to Transformer 000TF923 Power supply to Transformer 000TF924 Power supply to 000CM911 Power supply to 000CM912 Roller Mill Fan Roller Mill ESP ID Fan Dilution Air Recirculation Fan Primary combustion Air Fan Roller Mill First Stage Crystaliser Vent Fan Dryer Air Blower
Description Power supply to Transformer 000TF922 Power supply to Transformer 000TF923 Power supply to Transformer 000TF924 Power supply to Transformer 000TF922 Power supply to Transformer 000TF923 Power supply to Transformer 000TF924 Power supply to 000CM911 Power supply to 000CM912 Roller Mill Fan Roller Mill ESP ID Fan Dilution Air Recirculation Fan Primary combustion Air Fan Roller Mill First Stage Crystaliser Vent Fan Dryer Air Blower
Cable w/s 1s 57.10 57.10 57.10 57.10 57.10 57.10 34.30 34.30 13.60 13.60 10.00 10.00 13.60 10.00 10.00
Rc1 (pu) 0.009632 0.009632 0.009632 0.003913 0.003913 0.003913 0.00772 0.004101 0.04446 0.03211 0.04459 0.05145 0.0494 0.045962 0.0343
Cable w/s for t 57.10 57.10 57.10 57.10 57.10 57.10 68.60 68.60 43.01 43.01 31.62 31.62 43.01 31.62 31.62
26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2 26.2
Result
G1
Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
Steady State Voltage Drop Voltage Allowed %VD Xc1 (pu) Drop %VD 0.01264 4.81014 0.05% 5% 0.01264 4.74653 0.05% 5% 0.01264 4.74653 0.05% 5% 0.00514 1.95412 0.02% 5% 0.00514 1.92828 0.02% 5% 0.00514 1.92828 0.02% 5% 0.0068 3.80614 0.04% 5% 0.00361 2.02201 0.02% 5% 0.0171 6.29939 0.07% 5% 0.01235 4.31424 0.05% 5% 0.013 2.41129 0.03% 5% 0.015 1.96027 0.02% 5% 0.019 6.27525 0.07% 5% 0.0134 1.31476 0.01% 5% 0.01 1.21067 0.01% 5%
0.87 0.87 0.87 0.87 0.87 0.87 0.87 0.87
Result Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
G2 1.00 1.00 1.00 1.00 1.00 1.00 1.00 1.00
G3 0.99 0.99 0.99 0.99 0.99 0.99 0.99 0.99
G4 0.72 0.72 0.72 0.72 0.72 0.72 0.72 0.72
Type 3Cx400 3Cx400 3Cx400 3Cx400 3Cx400 3Cx400 3Cx240 3Cx240 3Cx95 3Cx95 3Cx70 3Cx70 3Cx95 3Cx70 3Cx70
Runs 1 1 1 1 1 1 2 2 1 1 1 1 1 1 1
Grd. 517 517 517 517 517 517 387 387 237 237 202 202 237 202 202
Thermal Ampacity Derating-Air
De-rating factor for Ground Reqd.
Type of Laying
K-Gd 0.62 0.62 0.62 0.62 0.62 0.62 0.62 0.62
A1
A2 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90
0.96 0.96 0.96 0.96 0.96 0.96 0.68 0.68 0.68 0.68 0.68 0.68 0.68 0.68 0.68
Air 602 602 602 602 602 602 442 442 257 257 217 217 257 217 217
Rac / Km 0.0602 0.0602 0.0602 0.0602 0.0602 0.0602 0.0965 0.0965 0.247 0.247 0.343 0.343 0.247 0.343 0.343
Ground X / Grd. Ther Dept km Temp mal h 0.079 45 Resis 150 1 t. 0.079 45 150 1 0.079 45 150 1 0.079 45 150 1 0.079 45 150 1 0.079 45 150 1 0.085 45 150 1 0.085 45 150 1 0.095 0.095 0.1 0.1 0.095 0.1 0.1
Derated Current K-Air Grd 0.86 0.86 0.86 0.86 0.86 0.86 0.61 0.61 0.61 0.61 0.61 0.61 0.61 0.61 0.61
321 321 321 321 321 321 480 480 0 0 0 0 0 0 0
Air 520 520 520 520 520 520 541 541 157 157 133 133 157 133 133
Final 321 321 321 321 321 321 480 480 157 157 133 133 157 133 133
Reqd. I 319.72 319.72 319.72 319.72 319.72 319.72 378.00 378.00 134.14 127.20 53.34 37.25 120.26 28.09 34.66
Resu lt Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass Pass
Air Hor. Air Hori. Form Temp Form 5, 30 50 1t, 3 5, 30 50 1t, 3 5, 30 50 1t, 3 5, 30 50 1t, 3 5, 30 50 1t, 3 5, 30 50 1t, 3 5, 30 50 1t, 3 5, 30 50 1t, 3 50 6t, 6 50 6t, 6 50 6t, 6 50 6t, 6 50 6t, 6 50 6t, 6 50 6t, 6
Cabl es, touch 1D 1D 1D 1D 1D 1D 1D 1D Touch Touch Touch Touch Touch Touch Touch