Transformer protection.ppt

October 16, 2017 | Author: muaz_aminu1422 | Category: Transformer, Relay, Electrical Impedance, Manufactured Goods, Electricity
Share Embed Donate


Short Description

Download Transformer protection.ppt...

Description

TRANSFORMER PROTECTION Target Audiance

• Electrical Engineers • Protection Engineers • Test & Commissioning Engineers • Power System Engineers • Utility Engineers • Electrical Technicians

1

> Transformer Protection

2

> Transformer Protection

3

> Transformer Protection

4

> Transformer Protection

5

> Transformer Protection

6

> Transformer Protection

TRANSFORMER PROTECTION Introduction Transformers are a critical and expensive component of the power system. Due to long lead time for repair and replacement of transformers, a major goal of transformer protection is limiting the damage to a faulted transformer. The comprehensive transformer protection provided by multiple function protective relays is appropriate for critical transformers of all applications.

7

> Transformer Protection

TRANSFORMER PROTECTION

The type of protection for the transformers varies depending on the application and importance of the transformer. Transformers are protected primarily against faults and overloads. The type of protection used should minimize the time of disconnection for faults within the transformer and to reduce the risk of catastrophic failure to simplify eventual repair.

8

> Transformer Protection

TRANSFORMER PROTECTION

Any extended operation of the transformer under abnormal condition such as faults or overloads compromises the life of the transformer, which means adequate protection should be provided for quicker isolation of the transformer under such condition.

9

> Transformer Protection

TYPES OF FAULTS

The various possible transformer faults are,  1. Overheating  2. Winding faults  3. Open circuits  4. External faults  5. Over fluxing

10

> Transformer Protection

OVERHEATING

They are due to  Sustained overloads and short circuits  Failure of cooling system Protection  The thermal overload relays and temperature relays, sounding the alarm are used  The thermocouples or resistance temperature indicators are also provided near the winding.  These are connected in a bridge circuits.  When the bridge balance gets disturbed for more than the permissible duration circuit breaker trips. 11

> Transformer Protection

WINDING FAULTS The winding faults are called internal faults. The overheating or mechanical shocks deteriorates the winding insulation. If the winding insulation-is weak, there is a possibility of  Phase to phase faults  Earth faults  Inter turn faults Persistent fault would have a possibility of oil-fire. PROTECTION  Differential protection  Over current protection is also used as a backup protection  For earth fault protection, the restricted earth fault protection system, neutral current relays or leakage to frame protection system is used.

12

> Transformer Protection

OPEN CIRCUIT

 The open circuit in one of the three phases causes the undesirable heating of the transformer.  Open circuits are much harmless compared to other faults.  Transformers can be manually disconnected from the system during such faults.

13

> Transformer Protection

THROUGH FAULTS  Through faults are the external faults which occur outside the protected zone.  These are not detected by the differential protection.  If faults persists the transformer gets subjected to thermal and mechanical stresses which can damage the transformer. PROTECTION  The overcurrent relays with undervoltage blocking, zero sequence protection and negative sequence protection are used to give protection  The setting of the overcurrent protection not only protects transformer but also covers the station busbar and portion of a transmission line.

14

> Transformer Protection

OVERFLUXING  The flux density in the transformer core is proportional to the ratio of the voltage to frequency i.e. V/f  Transformers are designed to work with certain value of flux density in the core. In the generator transformer unit, if full excitation is applied before generator reaches its synchronous speed then due to high V/f the overfluxing of core may occur. PROTECTION  V/f relay called volts/hertz relay is provided to give the protection against overfluxing operation.

15

> Transformer Protection

Other faults  Tap changer faults  High voltage surges due to lightning  Switching surges  Incipient faults

16

> Transformer Protection

Importance of Protection  Detect and isolate fault  Maintain system stability  To limit the damage in adjacent equipment  Minimize fire risk  Minimize risk to personnel

17

> Transformer Protection

Transformer Connections

18

> Transformer Protection

Transformer Connections a a2

A C1

A2

C2 C B1

A B C

19

A2 B2

C2

A1 B1 C1

> Transformer Protection

a1 b1 c1

c1

A1 B2 B

a2

b2 c2

a1 b1

b2

b

c2 c a b

c

“Clock face” numbers refer to position of low voltage phase neutral vector with respect to high voltage phase - neutral vector.

Line connections made to highest numbered winding terminal available. Line phase designation is same as winding.

Transformer Vector Groups

Phase displacement

Yy0 Dd0 Zd0

Phase displacement

Yy6 Dd6 Dz6

Lag phase displacement

Yd1 Dy1 Yz1

Lead phase displacement

Yd11 Dy11 Yz11

Group 1 0 Group 2 180 Group 3 30 Group 4 30

20

> Transformer Protection

Transformer Connections 

“Clock Face” numbers refer to position of low voltage phase-neutral vector with respect to high voltage phase neutral vector



Line connections made to highest numbered winding terminal available



Line phase designation is same as winding Example 1 : Dy 11 Transformer High Voltage Windings A Phase Winding s B Phase Winding s C Phase Winding s

A2 B2 C2

Low Voltage Windings

a1

a2

B1

b1

b2

C1

c1

c2

A1

Question : How to connect windings ?

21

> Transformer Protection

Overcurrent Protection

22

> Transformer Protection

Transformer Overcurrent Protection

Requirements  Fast operation for primary short circuits  Discrimination with downstream protections  Operation within transformer withstand  Non-operation for short or long term overloads  Non-operation for magnetising inrush

23

> Transformer Protection

Use of Instantaneous Overcurrent Protection

HV



LV

50 51 50 set to 1.2 - 1.3 x through fault level 24

> Transformer Protection

Transient Overreach Concerns relay response to offset waveforms (DC transient) Definition

I1 - I2 x 100 I2

I2 I1

25

D. C . > Transformer Protection

I1 = Steady state rms pick up current I2 = Fully offset rms pickup current

Instantaneous High Set Overcurrent Relay Applied to a Transformer

5 1 LV

5 1 HV 1

5 1 HV 2

HV1 Tim e

HV2

LV

IF(LV)

IF(HV)

1.2IF(LV) 26

> Transformer Protection

Curren t

Current Distribution

I3Ø

I3Ø

0.866 I3Ø I3Ø

27

> Transformer Protection

HV relay

0.4 sec LV relay

0.866 I3Ø I3Ø 28

> Transformer Protection

29

> Transformer Protection

30

> Transformer Protection

31

> Transformer Protection

32

> Transformer Protection

Parallel Transformers Directional Relays (1)

51 Grid supply

67 Feeders

51

67 51 33

> Transformer Protection

51

Parallel Transformers Directional Relays (2)

51 Grid supply

51

Bus Section

Feeders

51

51 34

> Transformer Protection

51

35

> Transformer Protection

Earth Fault Protection

36

> Transformer Protection

Transformer Earth Faults 3 p.u. turns 1 p.u. turns

x

IP

PR

Protective Relay

R

ResistorlimitsE/Fcurrentto fullloadvalues

IF

Thus,primarycurrent, P 

2  . F.L. 3

For a fault at  : Faultcurrent   . F.L. Effectiveturnsratio  3 : 

If C.T. ratio (on primary side) is based on full load current of transforme r, then C.T. secondary

2 circuit  3 37

> Transformer Protection

 x .F.L. 3

Overcurrent Relay Sensitivity to Earth Faults (1) If as multiple of IF.L. 1.0 0.9



IF

0.8

Star Side

0.7 0.6

51

0.5

Overcurrent Relay

0.4

Delta Side

0.3 0.2 0.1



0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0

Overcurrent Relay Setting > IF.L. 38

> Transformer Protection

p.u..

Overcurrent Relay Sensitivity to Earth Faults (2) If as multiple of IF.L. 10 9 8 

IF

Star Side

7 6

51

5

Overcurrent Relay

4 3 2

Delta Side

1



0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 p.u..

39

> Transformer Protection

Overcurrent Relay Sensitivity to Earth Faults (3) If as multiple of IF.L. 10 IF 

IF

9 8 7 6

IP

IN

IP

5 4 3 2

IN

1

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0

40

> Transformer Protection

 p.u..

Earth Fault on Transformer Winding



I=

2 3

For relay operation, I > IS

I

e.g. If IS = 20%, then  > 20% for operation 3 2

Differential Relay Setting = IS

41

i.e.  > 59% Thus 59% of

winding is not protected

Differential Relay Setting 10%

% of Star Winding Protected 58%

20%

41%

30%

28%

40%

17%

50%

7%

> Transformer Protection

Unrestricted Earthfault Protection (1)

51 N

5 1

 Provides back-up protection for system  Time delay required for co-ordination

42

> Transformer Protection

5 1

5 1

Unrestricted Earth fault Protection

51 N

51 N

5 1

5 1

5 1

 Can provide better sensitivity (C.T. ratio not related to full load current) (Improved “effective” setting)  Provides back up protection for transformer and system 43

> Transformer Protection

Star Winding REF

Protected Zone

RE F

 Relay only operates for earth faults within protected zone.  Uses high impedance principle.  Stability level : usually maximum through fault level of transformer 44

> Transformer Protection

Restricted E/F Protection

A B C N

LV restricted E/F protection trips both HV and LV breaker Recommended setting : 10% rated

45

> Transformer Protection

Restricted E/F Protection

A B C N

LV restricted E/F protection trips both HV and LV breaker Recommended setting : 10% rated

46

> Transformer Protection

Delta Winding Restricted Earth Fault

Source

Protected zone REF

 Delta winding cannot supply zero sequence current to system  Stability : Consider max LV fault level  Recommended setting : less than 30% minimum earth fault level 47

> Transformer Protection

High Impedance Principle Protected Circuit Z M

RCT

RCT RL

IF

M

IS

VS RL

RL

Z

RS RT

Voltage Across Relay Circuit

RL

VS = IF (RCT + 2RL)

Stabilising resistor RST limits spill current to IS (relay setting) VS  RST = - RR where RR = relay burden IS CT knee point VKP = 2VS = 2IF (RCT + 2RL) 48

> Transformer Protection

The Use Of Non-Linear Resistors (Metrosils)

 During internal faults the high impedance relay circuit constitutes an excessive burden to the CT’s.  A very high voltage develops across the relay circuit and the CT’s.  Causes damage to insulation of CT, secondary winding and relay.  Magnitude of peak voltage VP is given by an approximate formula (based on experimental results) VP = 2  2VK (VF - VK) Where VF = Swgr. Fault Rating in amps x Z of relay circuit CT ratio @ setting  Metrosil required if VP > 3kV 49

> Transformer Protection

Non-Linear Resistors (Metrosils) IOP RST VM

VS RR

Metrosil Characteristic V = CI

 Suitable values of C &  chosen based on :  Max secondary current under fault conditions  Relay setting voltage 50

> Transformer Protection

REF Protection Example

1MVA (5%) 11000V 415V

1600/1 RCT = 4.9

Calculate : 1) Setting voltage (VS)

80MV A

2) Value of stabilising resistor required 3) Effective setting 1600/1 RCT = 4.8

51

> Transformer Protection

RS

MCAG14 IS = 0.1 Amp 2 Core 7/0.67mm (7.41/km) 100m Long

4) Peak voltage developed by CT’s for internal fault

Solution (1) Earth fault calculation :Using 80MVA base Source impedance = 1 p.u. Transformer impedance = 0.05 x 80 = 4 p.u. 1 p.u.

1 P.U.

Total impedance = 14 1

4  I1 = 1 = 0.0714 p.u. 14

I1

Base current = 80 x 106  3 x 415

4

= 111296 Amps

I2  IF 4 I0 Sequence Diagram 52

> Transformer Protection

= 3 x 0.0714 x 111296 = 23840 Amps (primary) = 14.9 Amps (secondary)

Solution (2)

(1) Setting voltage VS = IF (RCT + 2RL) Assuming “earth” CT saturates, RCT = 4.8 ohms 2RL = 2 x 100 x 7.41 x 10-3 = 1.482 ohms  Setting voltage = 14.9 (4.8 + 1.482) = 93.6 Volts

(2) Stabilising Resistor (RS) RS = VS - 1 IS IS2

Where IS = relay current setting

 RS = 93.6 - 1 = 836 ohms 0.1 0.12

53

> Transformer Protection

Solution (4)

Peak voltage = 22VK (VF - VK) VF = 14.9 x VS = 14.9 x 936 = 13946 Volts IS For ‘Earth’ CT, VK = 1.4 x 236 = 330 Volts (from graph)  VPEAK = 22 x 330 x (13946 - 330) = 6kV Thus, Metrosil voltage limiter will be required.

54

> Transformer Protection

Traditional Large Transformer Protection Package 33K V

200/5

51 5 0

10MVA 33/11KV 600/5

51 N

64

600/5 5/5A

55

> Transformer Protection

87

Differential Protection

56

> Transformer Protection

Differential Protection  Overall differential protection may be justified for larger transformers (generally > 5MVA).  Provides fast operation on any winding

 Measuring principle :  Based on the same circulating current principle as the restricted earth fault protection  However, it employs the biasing technique, to maintain stability for heavy through fault current

 Biasing allows mismatch between CT outputs.  It is essential for transformers with tap changing facility.  Another important requirement of transformer differential protection is immunity to magnetising in rush current. 57

> Transformer Protection

Biased Differential Scheme

Differential Current

I1

BIAS

OPERATE

BIAS I 2

I1 I2

OPERATE

I1 I2

RESTRAIN

I1 + I2 2

58

> Transformer Protection

Mean Through Current

Differential Protection

HV

PROTECTED ZONE

LV

R

Correct application of differential protection requires CT ratio and winding connections to match those of transformer. CT secondary circuit should be a “replica” of primary system. Consider : (1) (2) (3) 59

> Transformer Protection

Difference in current magnitude Phase shift Zero sequence currents

Differential Connections And polarity markings

P1

P2

A2

A1

A

60

> Transformer Protection

a1

B

a2

C

P2

P1

Use of Interposing CT P1

S1

P2

A2

A1 a1

P1

S2

R

R

S1 P1

R

Interposing CT provides :  Vector correction  Ratio correction  Zero sequence compensation > Transformer Protection

P2

S2

S2

61

a2

P2

S1

Interposing current transformers

62

> Transformer Protection

Interposing current transformers

63

> Transformer Protection

Interposing current transformers

64

> Transformer Protection

65

> Transformer Protection

66

> Transformer Protection

67

> Transformer Protection

68

> Transformer Protection

69

> Transformer Protection

70

> Transformer Protection

71

> Transformer Protection

72

> Transformer Protection

73

> Transformer Protection

74

> Transformer Protection

75

> Transformer Protection

76

> Transformer Protection

77

> Transformer Protection

78

> Transformer Protection

79

> Transformer Protection

80

> Transformer Protection

Differential Protection 150/5 P2 P1 S1

15MVA 66kV / 11kV A2

A1 a1

a2

800/5 P2 P1 S2

S2

S1

Dy1

Given above: Need to consider (1) Winding full load current (2) Effect of tap changer (if any) (3) C.T. polarities Assuming no tap changer Full load currents:66kV: 131 Amp = 4.37 Amps secondary 11kV: 787 Amp = 4.92 Amps secondary However, require 11kV C.T.’s to be connected in  Thus, secondary current = 3 x 4.92 = 8.52A

 RATIO CORRECTION IS REQUIRED 81

> Transformer Protection

Differential Protection 800/5

150/5 P1 S1

P2

A2

A1 a1

a2

P2

P1

S2

S2

4.37A

4.92A

S1

S2 P1

(2.56)

R

S1

P2

(5)

R R

It is usual to connect 11kV C.T.’s in and utilise a / interposing C.T. (this method reduces lead VA burden on the line C.T.’s) Current from 66kV side = 4.37 Amp Thus, current required from winding of int. C.T. = 4.37 Amp Current input to winding of int. C.T. = 4.92 Amp Required int C.T. ratio = 4.92 / 4.37 = 4.92 / 2.52 3 May also be expressed as : 5 / 2.56 82

> Transformer Protection

Effect of Tap Changer

e.g. Assume 66kV +5%, -15% Interposing C.T. ratio should be based on mid tap position Mid Tap (-5%)

= 62.7 kV

Primary current (15 MVA)

= 138 Amp

Secondary current

= 4.6 Amp

 Interposing C.T. ratio required = 4.92 / 4.6 3 ( / ) = 4.92 / 2.66 May also be expressed as : 5 / 2.7 Compared with 5 / 2.56 based on nominal voltage

83

> Transformer Protection

Combined Differential and Restricted Earth Fault Protection A1 a1

A2

a2

P1

P2

S1

P1

P2

S1 S2

REF

S2

P2 P1 S1 S2

To differential relay 84

> Transformer Protection

Three Winding Transformer 63MV A 132KV

300/5

25MV A 11KV

1600/5

50MV A 33KV

1000/5 4.59

5.51

10.33

2.88

5

2.88

5

All interposing C.T. ratio’s refer to common MVA base (63MVA) 85

> Transformer Protection

Traditional Use of Interposing CT Dy1(-30°)

Yd11(+30°)

R

R R

Interposing CT provides : Vector correction  Ratio correction  Zero sequence compensation 86

> Transformer Protection

Integral Vectorial and Ratio Compensation Power transformer

Numeric Relay

Ratio correction

Vectorial correction Virtual interposing CT

87

> Transformer Protection

Differential element

Virtual interposing CT

Transformer Magnetising Characteristic Twice Normal Flux

Normal Flux

Normal No Load Current No Load Current at Twice Normal Flux 88

> Transformer Protection

Magnetising Inrush Current Steady State

+ m

V  Im

- m

89

> Transformer Protection

Magnetising Inrush Current Switch on at Voltage Zero - No residual flux

Im

2m

 V

90

> Transformer Protection

Transformer Differential Protection Effect of Magnetising Current

 Appears on one side of transformer only  Seen as fault by differential relay  Normal steady state magnetising current is less than relay setting  Transient magnetising inrush could cause relay to operate

91

> Transformer Protection

Transformer Differential Protection Effect of Magnetising Inrush

 SOLUTION 1 : TIME DELAY

 Allows magnetising current to die away before relay can operate

 Slow operation for genuine transformer faults

92

> Transformer Protection

Transformer Differential Protection Effect of Magnetising Inrush

 SOLUTION 2 : 2ND (and 5TH) HARMONIC RESTRAINT

 Makes relay immune to magnetising inrush  Slower operation may result for genuine transformer faults if CT saturation occurs

93

> Transformer Protection

Typical Magnetising Inrush Waveforms

A B C

94

> Transformer Protection

Inter-Turn Fault Protection

95

> Transformer Protection

Inter-Turn Fault

CT E Load Shorted turn

Nominal turns ratio Fault turns ratio Current ratio

- 11,000 / 240 - 11,000 / 1 - 1 / 11,000

Requires Buchholz relay

96

> Transformer Protection

Interturn Fault Current / Number of Turns Short Circuited 100

10 Fault current in short circuited turns

80 Fault current (multiples of rated current)

8

60

6 Primary input current

40

4

20

2

0

5

10

15

20

25

Turn short-circuited (percentage of winding)

97

> Transformer Protection

Primary current (multiples of rated current)

Non-electrical Protection  Buchholz Protection  Pressure Relief Protection  Sudden Pressure Protection  Winding Temperature Protection  Oil Temperature Protection  Oil Level Abnormal Protection

98

> Transformer Protection

Buchholz Protection

 The function of the relay is to detect an abnormal condition within the tank and send an alarm or trip signal.

99

> Transformer Protection

Buchholz operate when:

 Gas produced from the transformer due to fault  An oil surge from the tank to the conservator  A complete loss of oil from the conservator (very low oil level)

100

> Transformer Protection

Pressure Relief Device

 Transformers’ last line of defense against internal pressure

101

> Transformer Protection

Sudden Pressure Protection

 Used to detect sudden increase in gas pressure caused by internal arcing  Set to operate before pressure relief device

102

> Transformer Protection

Oil Temperature Protection

 Typically sealed spiral-bourdon-tube dial indicators with liquidfilled bulb sensor

103

> Transformer Protection

Buchholz Relay Installation

3 x internal pipe diameter (minimum)

Conservator

5 x internal pipe diameter (minimum)

Oil conservator 3 minimum Transformer

104

> Transformer Protection

Buchholz Relay

Petcock Alarm bucket

Counter balance weight

Mercury switch

Oil level

To oil conservator

From transformer

Trip bucket

Aperture adjuster Drain plug

105

> Transformer Protection

Deflector plate

Overfluxing Protection

106

> Transformer Protection

Transformer protection

Over fluxing protection Over fluxing arises principally from the following system conditions.  High system voltage  Low system frequency  Geomagnetic disturbances The latter result in low frequency earth currents circulating through a transmission system. 107

> Transformer Protection

Overfluxing  Generator transformers  Grid transformers Usually only a problem during run-up or shut down, but can be caused by loss of load / load shedding etc.

Flux   V f  Effects of overfluxing :

   

Increase in magnetising current Increase in winding temperature Increase in noise and vibration Overheating of laminations and metal parts (caused by stray flux)

 Protective relay responds to V/f ratio

 Stage 1 - lower A.V.R.  Stage 2 - Trip field

108

> Transformer Protection

Overfluxing Basic Theory

V = kf

2m

m

 CAUSES

 Low frequency  High voltage  Geomagnetic disturbances  EFFECTS

 Tripping of differential element (Transient overfluxing)  Damage to transformers (Prolonged overfluxing)

109

> Transformer Protection

Ie

V/Hz Overfluxing Protection

V  K f Trip and alarm outputs for clearing prolonged overfluxing Alarm : Definite time characteristic to initiate corrective action Trip : IDMT or DT characteristic to clear overfluxing condition Settings Pick-up 1.5 to 3.0 i.e.

110V x 1.05 = 2.31 50Hz

DT setting range 0.1 to 60 seconds

110

> Transformer Protection

V/Hz Characteristics  Enables co-ordination with plant withstand characteristics

t = 0.8 + 0.18 x K (M - 1)2 1000 K = 63 K = 40 K = 20 K=5 K=1

100 Operating time (s)

10 1

1

1.1

1.2

1.3

1.4

M = V Hz Setting 111

> Transformer Protection

1.5

1.6

Thermal Overload Protection

112

> Transformer Protection

Over temperature  Generally regarded as overload protection also deals with failure of or interference with pumps and fans or shutting of valves to pumps  Winding hot spot temperature is the main issue, but both oil and winding temperature are usually measured and used to:  … initiate an alarm  … trip circuit breakers  … control fans and pumps

113

> Transformer Protection

Over temperature  Two temperatures must be monitored:  …Winding temperature (‘WTI’) -(short  thermal τ) this can rise rapidly, without  much of an increase in oil temperature  …Oil temperature (‘OTI’) -(long thermal τ)  this can rise slowly to a critical point  without an unacceptable winding  temperature increase

114

> Transformer Protection

Typical alarm and trip levels

winding alarm - 90ºC to 110ºC „ winding trip - 110ºC to 135ºC „ oil alarm - 80ºC to 95ºC „ oil trip - 95ºC to 115ºC 115

> Transformer Protection

Overheating Protection

I load

Alarm

TD setting Top oil of power transformer

Trip

I load

On

Fan control Off On

Pump control

Off

Heater

Temp. indication Local

Thermal replica

116

> Transformer Protection

Temperature sensing resistor

Remote

Typical Transformer Protection to Feeders

117

> Transformer Protection

Protection of Parallel Transformer Feeders

Higher voltage busbar Z

OC

OC

Z

FTS

FTS REF

REF

DP

DP Bh

WT

WT

Bh

REF

2

1

DOC

REF

SBEF 2 stage

SBEF 2 stage

OC

OC

Load Load 118

> Transformer Protection

Lower voltage busbar

1

DOC

2

Transformer Feeders FEEDE R

PW

PILOT S

P W

 For use where no breaker separates the transformer from the feeder.  Transformer inrush current must be considered.  Inrush is a transient condition which may occur at the instant of transformer energisation.  Mag. Inrush current is not a fault condition  Protection must remain stable.  MCTH provides a blocking signal in the presence of inrush current and allows protection to be used on transformer feeders. 119

> Transformer Protection

Transformer Feeder Protection Dy11 A B

P1 S1

P2 S2

C

23 24 25 26 27 28

I

i

II

ii

III

iii

MCTH

MBCI

27 28

MFAC 14

19 17

17

PILOTS

18 19

18 17 19 1

+ MVTW 02

3

13 14

120

> Transformer Protection

S1

A B C

17

19

P1 S2

MCTH 23

17

23 24 25 26 27 28

P2

MBCI 18

24 25 26 27 28 23 24 25 26 27 28

Protection of Transformer Feeders

Power transformer

P540 Scheme

Ratio correction Vectorial correction

Virtual interposing CT

121

> Transformer Protection

Virtual interposing CT

View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF