Replacement of 132/11kV Transformers, Transformer Protection Panels and 110 V Batteries at W13 Substation (CONTRACT No. N6399) Consultant
Name of the Equipment Name of the Feeder Manufacturer Date
ENERGO
Main Contractor
40MVA Power Transformer-T201 E03 / K09 Transformer Feeder ABB 20.02.2013
Page 1 – 10
40 MVA Power Transformer Stability Test 1. TRANSFORMER DETAILS: MAKE
: ABB
SERIAL NO.
:4359245110
FREQUENCY
: 50Hz
TYPE OF COOLING
: ONAN/ONAF
VECTOR GROUP
: YN yn0+d11
NO OF TAPS
: 25
NOMINAL TAP
: 13
Feeder name- Bay- E03 at 132kV side and Bay K09 at 11kV side RATING WINDING
RATED POWER(MVA)
RATED VOLTAGE
RATED CURRENTS
ONAN/ONAF
(KV)
(A)
HV
31.5/40
132
137.8/175.0
MV
31.5/40
11.5
1581/2008
SW
10.5/13.3
8
757.7/962
IMPEDANCE VOLTAGE
IMPEDANCE
WINDING
POWER
HV VOLTAGES(KV)
%
HV-LV
AT 40MVA
Tap1—151.8
19.51
Tap13---132.0
17.69
Tap25---112.2
16.28
VOLTAGE
The CT T1 used For Differential protection (F87T) CT ratio for 132kV Line side CT’s = 300/1A
Relay- RET670- ABB
CT ratio for 11kV Line side CT’s = 2500/1A The CT T3 used For REF protection at HV side (F64HV)
Date Name Signature
Tested by ABB Transmission & Distribution
Witnessed by
ENERGO
20.02.2013 R.Krishna Murthy
20.02.2013 Mohammad Rasheed
Approved by
SITE TEST REPORT
Replacement of 132/11kV Transformers, Transformer Protection Panels and 110 V Batteries at W13 Substation (CONTRACT No. N6399) Consultant
ENERGO
Main Contractor
Name of the Equipment Name of the Feeder Manufacturer Date
CT ratio for 132kV Line side CT’s = 300/1A
40MVA Power Transformer-T201 E03 / K09 Transformer Feeder ABB 20.02.2013
Page 2 – 10
Relay- RET615- ABB
CT ratio for HV neutral side= 300/1A The CT5 used For REF protection at MV side (F64MV) CT ratio for 11kV Line side CT’s = 2500/1A
Relay- RET615- ABB
CT ratio for MV neutral side= 2500/1A The CT1 used For SBEF protection at HV Neutral side (F51NHV ) CT ratio for HV neutral side= 300/1A
Relay- REF615- ABB
The CT4 used For SBEF protection at MV neutral side (F51NMV) CT ratio for MV neutral side= 2500/1A
Relay- REF615- ABB
The CT9 used For SBEF protection at tertiary side (F51NT) CT ratio for Tertiary neutral side= 300/1A
Relay- REF615- ABB
The CT T1 used For O/C & E/F protection at HV Line side (F51/51NHV) CT ratio for 132kV Line side CT’s = 300/1A
Relay- REF615- ABB
Relay used for Over Voltage protection (F59) VT Ratio 11kV/√3/110V/√3
Relay- REF615- ABB
A. Transformer Stability Test( RET 670) 1a) STABLE CONDITION (132kV BB2 Earth Q25 Closed) Three phase voltage injected in 11kV side thru Bay K09(I/C-1), K11 and all CTs are normal
Date Name Signature
Tested by ABB Transmission & Distribution
Witnessed by
ENERGO
20.02.2013 R.Krishna Murthy
20.02.2013 Mohammad Rasheed
Approved by
SITE TEST REPORT
Replacement of 132/11kV Transformers, Transformer Protection Panels and 110 V Batteries at W13 Substation (CONTRACT No. N6399) Consultant
ENERGO
Main Contractor
PHASE
Name of the Equipment Name of the Feeder Manufacturer Date
40MVA Power Transformer-T201 E03 / K09 Transformer Feeder ABB 20.02.2013
Page 3 – 10
Primary
Relay Display
Diff. Display
CT Terminals Sec
current (A)
Measurement (A)
Measurement (A)
Current (A)
132kV
11kV
132kV
11kV
Diff.
Rest
132kV
11kV
R
111
151
34.17
392
0
34.32
0.103
0.186
Y
112
150
34.55
392
0
0.107
0.192
B
109
151
33.98
387
0
0.104
0.187
N 1b) UNSTABLE CONDITION (132kV side CT Bypassed by closing the Earth switch Q8 ) a)Three phase voltage injected in 11kV side thru Bay K09(I/C-1)**and all CT’s are Normal PHASE
Primary
Relay Display
Diff. Display
CT Terminals Sec
current (A)
Measurement (A)
Measurement (A)
Current (mA)
132kV
11kV
132kV
11kV
Diff.
Rest
132kV
11kV
R
10
150
3.2
393
31.20
34
9.6
153
Y
8
152
3.1
390
31.8
9.2
152
B
10
151
3.0
385
31.2
9.0
149
1.6
5.1
N 1c) STABLE CONDITION (132kV BB2 Earth Q25 Closed)
Three phase voltage injected in 11kV side thru Bay K09(I/C-1)** and all CTs are normal PHASE
Primary
Test Plug (A)
current (A)
Diff. Display
Relay Display (A)
Measurement (A)
132kV
11kV
132kV
11kV
Diff.
Rest
132kV
11kV
R
111
152
110
151
0
34.2
34.2
193
Y
111
150
111
153
0
34.2
389
B
110
151
110
151
0
33.0
388
N
-
-
-
-
-
-
-
REMARKS:
-
40 MVA Transformer diff Stability circuit found :- OK
B. 40 MVA TRANSFORMER HV REF PROTECTION STABILITY / SENSITIVITY TEST Phase CT Ratio
Date Name Signature
: 300/1 A Tested by ABB Transmission & Distribution
Witnessed by
ENERGO
20.02.2013 R.Krishna Murthy
20.02.2013 Mohammad Rasheed
Approved by
SITE TEST REPORT
Replacement of 132/11kV Transformers, Transformer Protection Panels and 110 V Batteries at W13 Substation (CONTRACT No. N6399) Consultant
Name of the Equipment Name of the Feeder Manufacturer Date
ENERGO
Main Contractor
Neutral CT Ratio
: 300/1 A
Relay Setting (Is)
:.
40MVA Power Transformer-T201 E03 / K09 Transformer Feeder ABB 20.02.2013
Page 4 – 10
A
Stabilizing resistor (final setting)
:_
Stabilizing resistor set at
:
Transformer Tap position
: 13
Primary current measured
:
Ohm Ohm A
(132kV Earth switch Q25 (BB2 ESW) Close (BUSBAR -2 under Shutdown)
Remarks -:- CT circuits for Tr Diff.Stability, HV & MV REF stable confirmed. ** Three phase generator voltage injected through K11 spare bay at 11kV side