SITE INSPECTION AND TEST RECORD Description:

CONTRACT no.:

Record no. :

End Client:

Sheet:

DISTANCE &DIFF RELAY MICOM P545 Customer:

AL GIHAZ

SEC-WOA

Site:

Page 1 of 14

Panel / Designation / Location no.:

ISKAN S/S 380 KV /110 KV

Project no.:

R08.1

1. RELAY CHARACTERISTICS Designation :

Type No.:

P545

Model No :

P545311A3M0510K Nominal Current : Nominal Voltage :Vn 30068149

Serial Number Firmware Version :

Aux. Volts : Vx

87L/21/67N /79 1/5 A 100- 120 VAC – 50/60 HZ

110-250 VDC 100-240 VAC

2.1 CT & VT DATA CT rated primary current set as

1200 A

CT rated secondary current set as

1.0A

Ignd-CT rated primary current set as

1200 A

Ignd-CT rated secondary current set as

1.0A

Rated primary voltage (L-L) set as

110 KV

Rated secondary voltage (L-L) set as

100 V

3. PRELIMINARY CHECKS Relay damaged? Rating information correct for installation? Case earth installed? External wiring checked against diagram? Test block connections checked? LCD front panel display Clock set to local time?

Tested by: Name : Eng. Mohamed Shokry Signature & Date :

Witnessed by: SEC-WOA-CONSULTANT Name : ENG/ MAHMOUD HAMDI Signature & Date

Witnessed by: SEC-WOA-CSD Name : ENG/GAMAL HAMMAM Signature & Date :

SITE INSPECTION AND TEST RECORD Description:

CONTRACT no.:

Record no. :

End Client:

Sheet:

DISTANCE &DIFF RELAY MICOM P545 Customer:

AL GIHAZ

SEC-WOA

Site:

Page 2 of 14

Panel / Designation / Location no.:

ISKAN S/S 380 KV /110 KV

Project no.:

R08.1

4. GENERAL CHECKS Checking

Results

Dry cell battery voltage (Remove battery isolation strip) Auxiliary voltage value on terminals M2 ( + ) and M1 ( - )

Measured FIELD SUPPLY Voltage M7 – M9 and M8 – M10 Watchdog contact when relay OFF

Terminals M11 and M12

Closed

Terminals M13 and M14

Open

Watchdog contact when relay ON

Terminals M11 and M12

Open

Terminals M13 and M14

Closed

Check if the frequency is set on required value Clock set-up, remove auxiliary supply for 30 seconds check date & time Trip relay LED operation check Alarm relay LED operation check Out of service relay LED operation check Healthy relay LED operation check

5. DISPLAY READINGS Circuit

Injected value

VOLTAGE 57.73

CURRENT

Tested by: Name : Eng. Mohamed Shokry Signature & Date :

1.0 A Phase A / 0° Phase B / -120° Phase C / 120°

Phases

Expected value

VAN

63.51 KV

VBN

63.51 KV

VCN

63.51 KV

VAB

110 KV

VBC

110 KV

VCA

110 KV

IA

1200

IB

1200

IC

1200

IN

0

Witnessed by: SEC-WOA-CONSULTANT Name : ENG/ MAHMOUD HAMDI Signature & Date

Displayed value PRIMARY

SECANDRY

Witnessed by: SEC-WOA-CSD Name : ENG/GAMAL HAMMAM Signature & Date :

SITE INSPECTION AND TEST RECORD Description:

CONTRACT no.:

Record no. :

End Client:

Sheet:

DISTANCE &DIFF RELAY MICOM P545 Customer:

AL GIHAZ

SEC-WOA

Site:

Page 3 of 14

Panel / Designation / Location no.:

ISKAN S/S 380 KV /110 KV

Project no.:

R08.1

6. FUNCTIONAL TESTS Current differential bias characteristic (87-1) Item

Description

Setting

1

IS1

0.20 A

2 3 4 5

Is2 K1 K2 T

2.0 A 30 % 150 % 0 Sec

Pick-up & Time test:*NOTE:. The Relay will be tested at loopback internal mode It should be noted that the minimum operating current is related, but not equal to, the Is1 SETTING Consider a single end fed fault with no load but fault current, I:|Idiff| = I |Ibias| = ½I Assuming |Ibias| < Is2, then, using the equations from section 2.1(from manual), the relay will operate if:|Idiff| > k1.| Ibias| + Is1 or I > k1.½I + Is1 or I> Is1 / (1 - 0.5 k1) The minimum operating current is therefore a function of the Is1 and k1 settings. Since k1 is Recommended to be set to 30%, the minimum operating current will be:Imin = 1.176 1s1

I Diff I > ( k1 * I I Bias I + Is1 )/2 = 0.118 A Fault Type

Expected Pickup In Amp

Actual Pickup In Amp

Drop-off In Amp

Expected Trip Time in m-sec

Actual Trip Time in m-sec at 2 x I Pickup

A-N

0.118 A

0.12

0.087

inhibit.

6.2.5.2 Loss of all 3 phase voltages under load condition test(detect 3p): Fixed Setting:

a- for fuse fail pick up; V1=10 volts. b- for fuse fail reset; V1=30 volts. Pick up measurement voltage(v)

Reset measurement voltage(v)

10.03

30.05

8.1.2.4 Check the blocking of the relay when the general block functions (VT MCB TRIP) is activated [

7.

Fault Locator Function:

Line Length:

80.0 Km

ФL: 79 degree.

Line impedance: 18.6 Ω

Fault Type

Fault Impedance Z (Ω)

Expected display (KM)

A-N(25)% A-B(50)% A-B-C(100)%

4.65 9.3 18.6

20 40 80

Actual display (KM)

19.75 40.59 81.16

*WE INJECT Z WITH LINE ANGLE Tested by: Name : Eng. Mohamed Shokry Signature & Date :

Witnessed by: SEC-WOA-CONSULTANT Name : ENG/ MAHMOUD HAMDI Signature & Date

Witnessed by: SEC-WOA-CSD Name : ENG/GAMAL HAMMAM Signature & Date :

]

SITE INSPECTION AND TEST RECORD Description:

CONTRACT no.:

Record no. :

End Client:

Sheet:

DISTANCE &DIFF RELAY MICOM P545 Customer:

AL GIHAZ

SEC-WOA

Site:

Page 8 of 14

Panel / Designation / Location no.:

ISKAN S/S 380 KV /110 KV

Project no.:

R08.1

Event and Disturbance recorder check [

OK

]

6.2 Directional earth fault protection - DEF (67N-1) DEF status :

8.1

ENABLE

DEF VNpol set :

3V

DEF Char angle :

-60°

DEF polarizing :

ZERO SEQUENCE

DEF threshold :

100 mA

Pick up current 3Io: Pick-up current

Drop-off current Expected 95% set Measured ±5%

Phases

Expected Set ±5%

A

100mA

103.44

95mA

96

B

100mA

102

95mA

99

C

100mA

103.95

95mA

98

Measured

-Apply 3 phase volts of rated value (57.73 volt) with balanced angles. -for the phase under test start reducing voltage till you get Vn more thane vpolarizing Apply 3 phase current with balanced angles for the phase under test start increasing current till you get pick-up; then decrease again till you get reset.

8.2 Directional Test (FW) Angle 60°

Pick-up Expected Measured Set ±2° 150

149.9

Drop-off Expected Measured Hyst. < 3° 330

329.6

We will inject and change the voltage angle not current angle so the angle will be as added 180

8.3 POLARIZING VOLTAGE (3V0) PICKUP AND DROP OFF TEST: Vn(3V0) setting

3V

Vn (3V0) measured Pick up 3.009

Drop off 2.958

NOTE: -Apply balanced current at 3 phase for phase under testing up slowly till get In more than 3Io setting Tested by: Name : Eng. Mohamed Shokry Signature & Date :

Witnessed by: SEC-WOA-CONSULTANT Name : ENG/ MAHMOUD HAMDI Signature & Date

Witnessed by: SEC-WOA-CSD Name : ENG/GAMAL HAMMAM Signature & Date :

SITE INSPECTION AND TEST RECORD Description:

CONTRACT no.:

Record no. :

End Client:

Sheet:

DISTANCE &DIFF RELAY MICOM P545 Customer:

AL GIHAZ

SEC-WOA

Site:

Page 9 of 14

Panel / Designation / Location no.:

ISKAN S/S 380 KV /110 KV

Project no.:

R08.1

-Apply 3 phase volts of rated value (57.73 volt) with balanced angles. -for the phase under test start reducing voltage till you get pick-up; then increase again till you get reset.

8.4  III

DEF Scheme check: Aid DEF delay =

90

m sec

Scheme: permissive over reach SEND: DEF STFW : 29.6 DEF AIDED TRIP : DEF STFW + CR: 120 DEF AIDED TRIP : DEF STFW w/o CR 1.53

II.

m sec m sec SEC (trip with EF element. no trip with aid -2)

Current Reversal Logic Check (Permissive Over Reach Scheme):  Apply a reverse / forward fault to check: t rev guard: Fault type Reverse/ forward

t rev guard setting (m sec)

t rev guard measured (m sec)

150

263.9

THIS MEASURED VALUE INCLUDE DELAY TIME AND DEF PICK UP TIME

III

III

Weak End Infeed Echo (Permissive over reach Scheme): 

Apply a short pulse to DEF Channel Receive Input Without any fault Injection and check Channel send is given: [ OK ]



Operating time

25.4

m sec

Weak End Infeed Trip (Permissive over reach Scheme): Setting WI V< V thresh = 45 V WI trip delay = 60 m sec U ph setting (V)

U ph measured (V)

Remark

45

45.03

OK

Start at 3ph voltage more than setting value and go down gradually and apply send signal each time and check at which value will come ECHO/WI trip

 III

Measured WI Trip time =

79.2

Scheme: BLOCKING reach SEND: DEF STRV : DEF AIDED TRIP : DEF STFW W/O CR : DEF AIDED TRIP : DEF STFW + CR

Tested by: Name : Eng. Mohamed Shokry Signature & Date :

m sec 41.3 118.1 1.53

Witnessed by: SEC-WOA-CONSULTANT Name : ENG/ MAHMOUD HAMDI Signature & Date

m sec m sec sec (trip with EF element no trip with aid-2)

Witnessed by: SEC-WOA-CSD Name : ENG/GAMAL HAMMAM Signature & Date :

SITE INSPECTION AND TEST RECORD Description:

CONTRACT no.:

Record no. :

End Client:

Sheet:

DISTANCE &DIFF RELAY MICOM P545 Customer:

AL GIHAZ

SEC-WOA

Site:

ISKAN S/S 380 KV /110 KV

6.

Page 10 of 14

Panel / Designation / Location no.:

Project no.:

R08.1

OVER CURRENT PROTECTION ( NON DIRECTIONAL ) : PICK UP VALUE: PHASE A B C

SETTING

PICK UP 1.001 1.00 1.00

1 A.&1 sec

OPERATING TIME STAGE (1)

2 Times 5 Times 2 Times 5 Times 2 Times 5 Times 2 Times 5 Times

SI VI EI LTI

DT TIME 1.02 1.02 1.02

(Is > 1 A)

CAL TIME @

CURVE

DROP OFF 0.951 0.950 0.950

OPERATING TIME

LIMIT(as per curve)

A

B

C

10.02 4.29 13.46 3.38 26.53 3.32 119 29.88

10.02 4.29 13.46 3.38 26.53 3.33 119 29.90

10.02 4.29 13.45 3.38 26.51 3.32 119 29.87

10.03+/-5% 4.28+/-5% 13.5+/-5% 3.375+/-5% 26.67+/-5% 3.333+/-5% 120+/-5% 30+/-5%

1) System check:-

No

Item description

Setting values

1 2 3 4 5 6 7

Dead voltage Live voltage Under voltage Over voltage U diff CS1 angle CS1 freq

20 40. 43 70 6.5 20 50 mH

Tested by: Name : Eng. Mohamed Shokry Signature & Date :

Measured values BB LINE 20.0 20.04 40.01 40.06 43.04 42.97 70.04 69.97 6.58 6.56 19.1 19.1 50 50

Witnessed by: SEC-WOA-CONSULTANT Name : ENG/ MAHMOUD HAMDI Signature & Date

Remark

Witnessed by: SEC-WOA-CSD Name : ENG/GAMAL HAMMAM Signature & Date :

SITE INSPECTION AND TEST RECORD Description:

CONTRACT no.:

Record no. :

End Client:

Sheet:

DISTANCE &DIFF RELAY MICOM P545 Customer:

AL GIHAZ

SEC-WOA

Site:

Page 11 of 14

Panel / Designation / Location no.:

ISKAN S/S 380 KV /110 KV

Project no.:

R08.1

2) AUTO RECLOSER No 1 2 3 4 5    

Item description Dead time 1 CB READY Reclaim time A/R inhibit time Check system time

Setting values

Measured values

Remark

3 Sec 5 Sec 30 Sec 7 Sec 2 Sec

3.1

First shot

5.1 30.1 7.1 2.08

Check that A/R block from Z2 , Z4 as we make in A/R setting Check that A/R NOT block from multi phase as we make in A/R setting Check that A/R WILL START FROM EXTERNAL BI AR START Check that A/R WILL BLOCK FROM EXTERNAL BI AR BLOCK

[ OK [ OK [ OK [ OK

] ] ] ]

1-Dead time :- start timer protection trip and stop with close command (auto close) BO 2-CB HEALTY : When AR finish dead time before giving close command go to chick CB healthy BI if not come will wait this time to chick it .if come before time finish will make close. if not come it will make lock out after this time -A-first way start timer trip BO and stop AR LOCK OUT BO and remove CB HEALTHY BI(time=dead time + CB healthy time -B-other way when AR start shot it make blocking until finish shot. if condition CB HEALTHY not come at end of dead time it will remove blocking through this time and return blocking again after this time finish So to measure this time we can start timer by AR BLOCK BO NC and stop by AR BLOCK BO NO THIS WILL measure CB HEALTHY time only and accurate 3-CHICK SYSTEM TIME:it will be measured same ways as CB HEALTHY TIME unless we will remove CHECK SYSTEM BI and will activate syncrocheck with 1st shot 4-AR inhibit time:this time coming after closing the C.B. through this time inhibit AR for this time. to measure it will make freja sequence first page will take freja BO to relay BI MANUAL CLOSE COMMAND will function it at relay (CLOSE CB) and but the time for page one as this inhibit time setting and stage two will make fault to start the AR and change stage one duration till get AR START so inhibit time will be the time of stage one at freja (CB.READY, SYNCROCHECK BI .must be available) 5-RECLAIM TIME:At last shot When A/R start reclaim time it make A/R LOCK OUT OR still making blocking during reclaim time To measure it take BO close command (auto close) to start timer .and take BO A/R BLOCK NC to stop timer

Tested by: Name : Eng. Mohamed Shokry Signature & Date :

Witnessed by: SEC-WOA-CONSULTANT Name : ENG/ MAHMOUD HAMDI Signature & Date

Witnessed by: SEC-WOA-CSD Name : ENG/GAMAL HAMMAM Signature & Date :

SITE INSPECTION AND TEST RECORD Description:

CONTRACT no.:

Record no. :

End Client:

Sheet:

DISTANCE &DIFF RELAY MICOM P545 Customer:

AL GIHAZ

SEC-WOA

Site:

Page 12 of 14

Panel / Designation / Location no.:

ISKAN S/S 380 KV /110 KV

Project no.:

R08.1

8.LOGICAL INPUTS CHECK:Input

Terminal

BI-1

E1 − E2

OK

BI-2

E3 − E4

OK

BI-3

E5 − E6

OK

BI-4

E7 − E8

OK

BI-5

E9 – E10

OK

BI-6

E11 − E12

OK

BI-7

E13 − E14

OK

BI-8

E15 − E16

OK

BI-9

C1 − C2

OK

BI-10

C3 − C4

OK

BI-11

C5 − C6

OK

BI-12

C7 − C8

OK

BI-13

C9 – C10

OK

BI-14

C11 − C12

OK

BI-15

C13 − C14

OK

BI-16

C15 − C16

OK

BI-17

G1 − G2

OK

BI-18

G3 − G4

OK

BI-19

G5 − G6

OK

BI-20

G7 − G8

OK

BI-21

G9 – G10

OK

BI-22

G11 − G12

OK

BI-23

G13 − G14

OK

BI-24

G15 − G16

OK

Tested by: Name : Eng. Mohamed Shokry Signature & Date :

Circuit

Witnessed by: SEC-WOA-CONSULTANT Name : ENG/ MAHMOUD HAMDI Signature & Date

Result

Witnessed by: SEC-WOA-CSD Name : ENG/GAMAL HAMMAM Signature & Date :

SITE INSPECTION AND TEST RECORD Description:

CONTRACT no.:

Record no. :

End Client:

Sheet:

DISTANCE &DIFF RELAY MICOM P545 Customer:

AL GIHAZ

SEC-WOA

Site:

Page 13 of 14

Panel / Designation / Location no.:

ISKAN S/S 380 KV /110 KV

Project no.:

R08.1

9.OUTPUT RELAYS CHECK Relay

Terminal

Contact

RL1

L1 – L2

NO

Result OK

RL2

L3 – L4

NO

OK

RL3

L5 – L6

NO

OK

RL4

L7 – L8

NO

OK

RL5

L9 – L10

NO

OK

RL6

L11 – L12

NO

OK

RL7

L13–L14–L15

C/O

OK

RL8

L16–L17–L18

C/O

OK

RL9

K1 – K2

NO

OK

RL10

K3 – K4

NO

OK

RL11

K5 – K6

NO

OK

RL12

K7 – K8

NO

OK

RL13

K9 – K10

NO

OK

RL14

K11 – K12

NO

OK

RL15

K13–K14–K15

C/O

OK

RL16

K16–K17–K18

C/O

OK

RL17

J1 – J2

NO

OK

RL18

J3 – J4

NO

OK

RL19

J5 – J6

NO

OK

RL20

J7 – J8

NO

OK

RL21

J9 – J10

NO

OK

RL22

J11 – J12

NO

OK

RL23

J13–J14–J15

C/O

OK

RL24

J16–J17–J18

C/O

OK

RL25

H1 – H2

NO

OK

RL26

H3 – H4

NO

OK

RL27

H5 – H6

NO

OK

RL28

H7 – H8

NO

OK

RL29

H9 – H10

NO

OK

RL30

H11 – H12

NO

OK

Tested by: Name : Eng. Mohamed Shokry Signature & Date :

Circuit

Witnessed by: SEC-WOA-CONSULTANT Name : ENG/ MAHMOUD HAMDI Signature & Date

Witnessed by: SEC-WOA-CSD Name : ENG/GAMAL HAMMAM Signature & Date :

SITE INSPECTION AND TEST RECORD Description:

CONTRACT no.:

Record no. :

End Client:

Sheet:

DISTANCE &DIFF RELAY MICOM P545 Customer:

AL GIHAZ

SEC-WOA

Site:

Page 14 of 14

Panel / Designation / Location no.:

ISKAN S/S 380 KV /110 KV

Project no.:

R08.1

RL31

H13–H14–H15

C/O

OK

RL32

H16–H17–H18

C/O

OK

Tested by: Name : Eng. Mohamed Shokry Signature & Date :

Witnessed by: SEC-WOA-CONSULTANT Name : ENG/ MAHMOUD HAMDI Signature & Date

Witnessed by: SEC-WOA-CSD Name : ENG/GAMAL HAMMAM Signature & Date :