P545311A3M0510K Nominal Current : Nominal Voltage :Vn 30068149
Serial Number Firmware Version :
Aux. Volts : Vx
87L/21/67N /79 1/5 A 100- 120 VAC – 50/60 HZ
110-250 VDC 100-240 VAC
2.1 CT & VT DATA CT rated primary current set as
1200 A
CT rated secondary current set as
1.0A
Ignd-CT rated primary current set as
1200 A
Ignd-CT rated secondary current set as
1.0A
Rated primary voltage (L-L) set as
110 KV
Rated secondary voltage (L-L) set as
100 V
3. PRELIMINARY CHECKS Relay damaged? Rating information correct for installation? Case earth installed? External wiring checked against diagram? Test block connections checked? LCD front panel display Clock set to local time?
Tested by: Name : Eng. Mohamed Shokry Signature & Date :
Witnessed by: SEC-WOA-CONSULTANT Name : ENG/ MAHMOUD HAMDI Signature & Date
Witnessed by: SEC-WOA-CSD Name : ENG/GAMAL HAMMAM Signature & Date :
SITE INSPECTION AND TEST RECORD Description:
CONTRACT no.:
Record no. :
End Client:
Sheet:
DISTANCE &DIFF RELAY MICOM P545 Customer:
AL GIHAZ
SEC-WOA
Site:
Page 2 of 14
Panel / Designation / Location no.:
ISKAN S/S 380 KV /110 KV
Project no.:
R08.1
4. GENERAL CHECKS Checking
Results
Dry cell battery voltage (Remove battery isolation strip) Auxiliary voltage value on terminals M2 ( + ) and M1 ( - )
Measured FIELD SUPPLY Voltage M7 – M9 and M8 – M10 Watchdog contact when relay OFF
Terminals M11 and M12
Closed
Terminals M13 and M14
Open
Watchdog contact when relay ON
Terminals M11 and M12
Open
Terminals M13 and M14
Closed
Check if the frequency is set on required value Clock set-up, remove auxiliary supply for 30 seconds check date & time Trip relay LED operation check Alarm relay LED operation check Out of service relay LED operation check Healthy relay LED operation check
5. DISPLAY READINGS Circuit
Injected value
VOLTAGE 57.73
CURRENT
Tested by: Name : Eng. Mohamed Shokry Signature & Date :
1.0 A Phase A / 0° Phase B / -120° Phase C / 120°
Phases
Expected value
VAN
63.51 KV
VBN
63.51 KV
VCN
63.51 KV
VAB
110 KV
VBC
110 KV
VCA
110 KV
IA
1200
IB
1200
IC
1200
IN
0
Witnessed by: SEC-WOA-CONSULTANT Name : ENG/ MAHMOUD HAMDI Signature & Date
Displayed value PRIMARY
SECANDRY
Witnessed by: SEC-WOA-CSD Name : ENG/GAMAL HAMMAM Signature & Date :
SITE INSPECTION AND TEST RECORD Description:
CONTRACT no.:
Record no. :
End Client:
Sheet:
DISTANCE &DIFF RELAY MICOM P545 Customer:
AL GIHAZ
SEC-WOA
Site:
Page 3 of 14
Panel / Designation / Location no.:
ISKAN S/S 380 KV /110 KV
Project no.:
R08.1
6. FUNCTIONAL TESTS Current differential bias characteristic (87-1) Item
Description
Setting
1
IS1
0.20 A
2 3 4 5
Is2 K1 K2 T
2.0 A 30 % 150 % 0 Sec
Pick-up & Time test:*NOTE:. The Relay will be tested at loopback internal mode It should be noted that the minimum operating current is related, but not equal to, the Is1 SETTING Consider a single end fed fault with no load but fault current, I:|Idiff| = I |Ibias| = ½I Assuming |Ibias| < Is2, then, using the equations from section 2.1(from manual), the relay will operate if:|Idiff| > k1.| Ibias| + Is1 or I > k1.½I + Is1 or I> Is1 / (1 - 0.5 k1) The minimum operating current is therefore a function of the Is1 and k1 settings. Since k1 is Recommended to be set to 30%, the minimum operating current will be:Imin = 1.176 1s1
I Diff I > ( k1 * I I Bias I + Is1 )/2 = 0.118 A Fault Type
Expected Pickup In Amp
Actual Pickup In Amp
Drop-off In Amp
Expected Trip Time in m-sec
Actual Trip Time in m-sec at 2 x I Pickup
A-N
0.118 A
0.12
0.087
inhibit.
6.2.5.2 Loss of all 3 phase voltages under load condition test(detect 3p): Fixed Setting:
a- for fuse fail pick up; V1=10 volts. b- for fuse fail reset; V1=30 volts. Pick up measurement voltage(v)
Reset measurement voltage(v)
10.03
30.05
8.1.2.4 Check the blocking of the relay when the general block functions (VT MCB TRIP) is activated [
7.
Fault Locator Function:
Line Length:
80.0 Km
ФL: 79 degree.
Line impedance: 18.6 Ω
Fault Type
Fault Impedance Z (Ω)
Expected display (KM)
A-N(25)% A-B(50)% A-B-C(100)%
4.65 9.3 18.6
20 40 80
Actual display (KM)
19.75 40.59 81.16
*WE INJECT Z WITH LINE ANGLE Tested by: Name : Eng. Mohamed Shokry Signature & Date :
Witnessed by: SEC-WOA-CONSULTANT Name : ENG/ MAHMOUD HAMDI Signature & Date
Witnessed by: SEC-WOA-CSD Name : ENG/GAMAL HAMMAM Signature & Date :
-Apply 3 phase volts of rated value (57.73 volt) with balanced angles. -for the phase under test start reducing voltage till you get Vn more thane vpolarizing Apply 3 phase current with balanced angles for the phase under test start increasing current till you get pick-up; then decrease again till you get reset.
8.2 Directional Test (FW) Angle 60°
Pick-up Expected Measured Set ±2° 150
149.9
Drop-off Expected Measured Hyst. < 3° 330
329.6
We will inject and change the voltage angle not current angle so the angle will be as added 180
8.3 POLARIZING VOLTAGE (3V0) PICKUP AND DROP OFF TEST: Vn(3V0) setting
3V
Vn (3V0) measured Pick up 3.009
Drop off 2.958
NOTE: -Apply balanced current at 3 phase for phase under testing up slowly till get In more than 3Io setting Tested by: Name : Eng. Mohamed Shokry Signature & Date :
Witnessed by: SEC-WOA-CONSULTANT Name : ENG/ MAHMOUD HAMDI Signature & Date
Witnessed by: SEC-WOA-CSD Name : ENG/GAMAL HAMMAM Signature & Date :
SITE INSPECTION AND TEST RECORD Description:
CONTRACT no.:
Record no. :
End Client:
Sheet:
DISTANCE &DIFF RELAY MICOM P545 Customer:
AL GIHAZ
SEC-WOA
Site:
Page 9 of 14
Panel / Designation / Location no.:
ISKAN S/S 380 KV /110 KV
Project no.:
R08.1
-Apply 3 phase volts of rated value (57.73 volt) with balanced angles. -for the phase under test start reducing voltage till you get pick-up; then increase again till you get reset.
Witnessed by: SEC-WOA-CONSULTANT Name : ENG/ MAHMOUD HAMDI Signature & Date
Remark
Witnessed by: SEC-WOA-CSD Name : ENG/GAMAL HAMMAM Signature & Date :
SITE INSPECTION AND TEST RECORD Description:
CONTRACT no.:
Record no. :
End Client:
Sheet:
DISTANCE &DIFF RELAY MICOM P545 Customer:
AL GIHAZ
SEC-WOA
Site:
Page 11 of 14
Panel / Designation / Location no.:
ISKAN S/S 380 KV /110 KV
Project no.:
R08.1
2) AUTO RECLOSER No 1 2 3 4 5
Item description Dead time 1 CB READY Reclaim time A/R inhibit time Check system time
Setting values
Measured values
Remark
3 Sec 5 Sec 30 Sec 7 Sec 2 Sec
3.1
First shot
5.1 30.1 7.1 2.08
Check that A/R block from Z2 , Z4 as we make in A/R setting Check that A/R NOT block from multi phase as we make in A/R setting Check that A/R WILL START FROM EXTERNAL BI AR START Check that A/R WILL BLOCK FROM EXTERNAL BI AR BLOCK
[ OK [ OK [ OK [ OK
] ] ] ]
1-Dead time :- start timer protection trip and stop with close command (auto close) BO 2-CB HEALTY : When AR finish dead time before giving close command go to chick CB healthy BI if not come will wait this time to chick it .if come before time finish will make close. if not come it will make lock out after this time -A-first way start timer trip BO and stop AR LOCK OUT BO and remove CB HEALTHY BI(time=dead time + CB healthy time -B-other way when AR start shot it make blocking until finish shot. if condition CB HEALTHY not come at end of dead time it will remove blocking through this time and return blocking again after this time finish So to measure this time we can start timer by AR BLOCK BO NC and stop by AR BLOCK BO NO THIS WILL measure CB HEALTHY time only and accurate 3-CHICK SYSTEM TIME:it will be measured same ways as CB HEALTHY TIME unless we will remove CHECK SYSTEM BI and will activate syncrocheck with 1st shot 4-AR inhibit time:this time coming after closing the C.B. through this time inhibit AR for this time. to measure it will make freja sequence first page will take freja BO to relay BI MANUAL CLOSE COMMAND will function it at relay (CLOSE CB) and but the time for page one as this inhibit time setting and stage two will make fault to start the AR and change stage one duration till get AR START so inhibit time will be the time of stage one at freja (CB.READY, SYNCROCHECK BI .must be available) 5-RECLAIM TIME:At last shot When A/R start reclaim time it make A/R LOCK OUT OR still making blocking during reclaim time To measure it take BO close command (auto close) to start timer .and take BO A/R BLOCK NC to stop timer
Tested by: Name : Eng. Mohamed Shokry Signature & Date :
Witnessed by: SEC-WOA-CONSULTANT Name : ENG/ MAHMOUD HAMDI Signature & Date
Witnessed by: SEC-WOA-CSD Name : ENG/GAMAL HAMMAM Signature & Date :
SITE INSPECTION AND TEST RECORD Description:
CONTRACT no.:
Record no. :
End Client:
Sheet:
DISTANCE &DIFF RELAY MICOM P545 Customer:
AL GIHAZ
SEC-WOA
Site:
Page 12 of 14
Panel / Designation / Location no.:
ISKAN S/S 380 KV /110 KV
Project no.:
R08.1
8.LOGICAL INPUTS CHECK:Input
Terminal
BI-1
E1 − E2
OK
BI-2
E3 − E4
OK
BI-3
E5 − E6
OK
BI-4
E7 − E8
OK
BI-5
E9 – E10
OK
BI-6
E11 − E12
OK
BI-7
E13 − E14
OK
BI-8
E15 − E16
OK
BI-9
C1 − C2
OK
BI-10
C3 − C4
OK
BI-11
C5 − C6
OK
BI-12
C7 − C8
OK
BI-13
C9 – C10
OK
BI-14
C11 − C12
OK
BI-15
C13 − C14
OK
BI-16
C15 − C16
OK
BI-17
G1 − G2
OK
BI-18
G3 − G4
OK
BI-19
G5 − G6
OK
BI-20
G7 − G8
OK
BI-21
G9 – G10
OK
BI-22
G11 − G12
OK
BI-23
G13 − G14
OK
BI-24
G15 − G16
OK
Tested by: Name : Eng. Mohamed Shokry Signature & Date :
Circuit
Witnessed by: SEC-WOA-CONSULTANT Name : ENG/ MAHMOUD HAMDI Signature & Date
Result
Witnessed by: SEC-WOA-CSD Name : ENG/GAMAL HAMMAM Signature & Date :
SITE INSPECTION AND TEST RECORD Description:
CONTRACT no.:
Record no. :
End Client:
Sheet:
DISTANCE &DIFF RELAY MICOM P545 Customer:
AL GIHAZ
SEC-WOA
Site:
Page 13 of 14
Panel / Designation / Location no.:
ISKAN S/S 380 KV /110 KV
Project no.:
R08.1
9.OUTPUT RELAYS CHECK Relay
Terminal
Contact
RL1
L1 – L2
NO
Result OK
RL2
L3 – L4
NO
OK
RL3
L5 – L6
NO
OK
RL4
L7 – L8
NO
OK
RL5
L9 – L10
NO
OK
RL6
L11 – L12
NO
OK
RL7
L13–L14–L15
C/O
OK
RL8
L16–L17–L18
C/O
OK
RL9
K1 – K2
NO
OK
RL10
K3 – K4
NO
OK
RL11
K5 – K6
NO
OK
RL12
K7 – K8
NO
OK
RL13
K9 – K10
NO
OK
RL14
K11 – K12
NO
OK
RL15
K13–K14–K15
C/O
OK
RL16
K16–K17–K18
C/O
OK
RL17
J1 – J2
NO
OK
RL18
J3 – J4
NO
OK
RL19
J5 – J6
NO
OK
RL20
J7 – J8
NO
OK
RL21
J9 – J10
NO
OK
RL22
J11 – J12
NO
OK
RL23
J13–J14–J15
C/O
OK
RL24
J16–J17–J18
C/O
OK
RL25
H1 – H2
NO
OK
RL26
H3 – H4
NO
OK
RL27
H5 – H6
NO
OK
RL28
H7 – H8
NO
OK
RL29
H9 – H10
NO
OK
RL30
H11 – H12
NO
OK
Tested by: Name : Eng. Mohamed Shokry Signature & Date :
Circuit
Witnessed by: SEC-WOA-CONSULTANT Name : ENG/ MAHMOUD HAMDI Signature & Date
Witnessed by: SEC-WOA-CSD Name : ENG/GAMAL HAMMAM Signature & Date :
SITE INSPECTION AND TEST RECORD Description:
CONTRACT no.:
Record no. :
End Client:
Sheet:
DISTANCE &DIFF RELAY MICOM P545 Customer:
AL GIHAZ
SEC-WOA
Site:
Page 14 of 14
Panel / Designation / Location no.:
ISKAN S/S 380 KV /110 KV
Project no.:
R08.1
RL31
H13–H14–H15
C/O
OK
RL32
H16–H17–H18
C/O
OK
Tested by: Name : Eng. Mohamed Shokry Signature & Date :
Witnessed by: SEC-WOA-CONSULTANT Name : ENG/ MAHMOUD HAMDI Signature & Date
Witnessed by: SEC-WOA-CSD Name : ENG/GAMAL HAMMAM Signature & Date :