TechRef 2 W Transformer 3Phase

June 29, 2018 | Author: Pandiyan | Category: Transformer, Electrical Impedance, Capacitor, Electricity, Physical Quantities
Share Embed Donate


Short Description

Trafo...

Description

DIgSILENT  PowerFactory  Technical Reference Documentation

Two-Winding Transformer (3-Phase) ElmTr2

DIgSILENT GmbH Heinrich-Hertz-Str. 9 72810 - Gomaringen Germany T: +49 7072 9168 00 F: +49 7072 9168 88 http://www.digsilent.de

[email protected] r1010

Copyright ©2011, DIgSILENT GmbH. Copyright of this document belongs to DIgSILENT GmbH. No part of this document may be reproduced, reproduced, copied, or transmitte transmitted d in any form, by any means electronic or mechanical, without the prior written permission of DIgSILENT GmbH. Two-Winding Transformer (3-Phase) (ElmTr2)

1

DIgSILENT GmbH Heinrich-Hertz-Str. 9 72810 - Gomaringen Germany T: +49 7072 9168 00 F: +49 7072 9168 88 http://www.digsilent.de

[email protected] r1010

Copyright ©2011, DIgSILENT GmbH. Copyright of this document belongs to DIgSILENT GmbH. No part of this document may be reproduced, reproduced, copied, or transmitte transmitted d in any form, by any means electronic or mechanical, without the prior written permission of DIgSILENT GmbH. Two-Winding Transformer (3-Phase) (ElmTr2)

1

Contents

Contents 1 Genera Generall Des Descri cripti ption on

4

1.1 Mod Model el Diagr Diagrams ams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4

1.1.1 Positiv Positive e and Negativ Negative e sequence sequence models models   . . . . . . . . . . . . . . . . . . .

4

1.1.2 1.1 .2 Tap change changerr . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6

1.1.3 1.1 .3 Zero sequen sequence ce mod models els . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7

1.2 Load-Flow Load-Flow Analysis Analysis

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8

1.2.1 Tap changer changer basic basic data . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8

1.2.2 Tap dependent dependent impedance impedance . . . . . . . . . . . . . . . . . . . . . . . . . .

9

1.2.3 Measurement Measurement protocol protocol (element-spe (element-specific) cific) . . . . . . . . . . . . . . . . . .

9

1.2.4 Automatic Automatic tap changer changer control control . . . . . . . . . . . . . . . . . . . . . . . .

10

1.3 Short-Circuit Short-Circuit Analysis Analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

14

1.3.1 Type data data for IEC S/C S/C calculat calculations ions   . . . . . . . . . . . . . . . . . . . . . .

14

1.3.2 Element Element dat data a for for IEC S/C calculations calculations   . . . . . . . . . . . . . . . . . . . .

15

1.4 RMS Simula Simulatio tion n

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

15

1.5 Harmonic Harmonic Simulatio Simulation n  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

15

1.6 EMT Simula Simulatio tion n. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

16

1.6.1 Saturation Saturation characteris characteristic tic   . . . . . . . . . . . . . . . . . . . . . . . . . . . .

16

1.6.2 Zero Sequence Sequence magnetizing magnetizing reactance reactance . . . . . . . . . . . . . . . . . . .

20

1.6.3 1.6 .3 Residu Residual al flux . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

21

1.6.4 Stray Stray capacitance capacitances s  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

21

2 Modelling Modelling Details Details and and Applicat Application ion Hints

23

2.1 Ref Reference erence Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

23

2.2 Zero Sequence Sequence Models Models of of Common Common Vector Vector Groups Groups   . . . . . . . . . . . . . . . . .

23

2.2.1 2.2 .1 Yd-tra Yd-transf nsforme ormerr   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

23

2.2.2 YNyn/YNy YNyn/YNy /Yyn -transforme -transformerr . . . . . . . . . . . . . . . . . . . . . . . . .

23

2.2.3 Model of YNyn/YN YNyn/YNy/Yyn y/Yyn-tran -transforme sformerr with closed closed tertiary delta delta winding winding . .

24

2.2.4 Model of YNzn/YNz/ YNzn/YNz/Zyn-tr Zyn-transf ansformer ormer   . . . . . . . . . . . . . . . . . . . . .

25

2.3 Auto-tra Auto-transfo nsformer rmer Model . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

26

Two-Winding Transformer (3-Phase) (ElmTr2)

2

Contents

3 Input/Output Definitions of Dynamic Models

29

4 Input Parameter Definitions

30

4.1 2-Winding-Transformer Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

30

4.2 2-Winding-Transformer Element . . . . . . . . . . . . . . . . . . . . . . . . . . . .

32

5 References

35

List of Figures

36

List of Tables

37

Two-Winding Transformer (3-Phase) (ElmTr2)

3

1

1

General Description

General Description

The two-winding transformer model is a very detailed model for various kinds of three-phase, two-winding transformers in power systems. It can represent e.g. network transformers, block transformers, phase shifters or MV-voltage regulators. The model makes special consideration for auto-transformers. This first section describes the general model and is valid for all PowerFactory calculation functions. Particular aspects, such as saturation or capacitive effects, which are only relevant for some calculation functions are described in the following sections. Section 2. provides useful hints for special applications of the 2-winding transformer model.

1.1 Model Diagrams 1.1.1 Positive and Negative sequence models The detailed positive-sequence model with absolute impedances (in Ohm) is shown in Figure 1.1.  It contains the leakage reactances and the winding resistances of the HV and LV side and the magnetization reactance and the iron loss admittance close to the ideal transformer. The model with relative impedances (in p.u.) is shown in Figure 1.2.  The ideal transformer of the per-unitized model has a complex winding ratio with a magnitude of 1:1 and models the phase shift representing the vector groups of the two windings

Figure 1.1: Positive sequence model of the 2-winding transformer (in Ohms)

Figure 1.2: Positive sequence model of the 2-winding transformer (in p.u.)

The relation between the mathematical parameters in the model and the parameters in the type and element dialogs are described as follows:

Two-Winding Transformer (3-Phase) (ElmTr2)

4

1

General Description

2 U r,HV   S r 2 U r,LV   Z r,LV   = S r zsc  =  U sc /100

Z r,HV   =

rsc  = xsc  =

(1) (2) (3)

P Cu /1000 S r

   − 2 zsc

(4)

2 rsc

rCu,HV   = γ R,HV,1 rCu,LV   = (1 γ R,LV,1 ) xσ,HV   = γ X,HV,1 xσ,LV   = (1 γ X,LV,1 )

(5)

 · r ·r  · x ·x





sc

(6)

sc

(7)

sc

(8)

sc

(9)

1 i0 /100 S r rF e  = P F e /1000 1 xM  = Z M  =

 

1 2

zM 



 

(10)

 

(11)

1

(12)

2

rF e

where,

Z r,HV   Z r,LV   U r,HV   ,  U r,LV   S r P Cu uSC  zSC  rSC  xSC  γ X,HV,1

Ω Ω kV MVA kW % p.u. p.u. p.u. p.u.

γ R,HV,1

p.u.

Share of transformer shortcircuit resistance on HV side in the positive-sequence system

rCu,HV  ,  r Cu,LV   xσ,HV   ,  x σ,LV  

p.u.

Resistances on HV/LV sides

p.u.

Leakage reactances on HV/LV side

I 0 P F e xM  rF e

Nominal impedance, HV side Nominal impedance, LV side Rated voltages on HV/LV side Rated power Copper losses Relative short-circuit voltage Short-circuit impedance Short-circuit resistance Short-circuit reactance Share of transformer shortcircuit reactance on HV side in the positive-sequence system

%

no-load current

kW

No-load losses

p.u.

Magnetizing impedance

p.u.

Shunt resistance

Two-Winding Transformer (3-Phase) (ElmTr2)

5

1

General Description

1.1.2 Tap changer The tap changer is represented by an additional, ideal transformer connected to either the HV or the LV side (see Figure 1.3 and Figure 1.4). In most application, the winding ratio of this transformer is real and is defined by the actual tap position (in number of steps) times the additional voltage per steps.

Figure 1.3: Transformer model with tap changer modelled at HV - side

Figure 1.4: Transformer model with tap changer modelled at LV - side

Figure 1.5: Complex tap changer model in PowerFactory 

Phase shifters are modelled by a complex ratio using a complex value of dutap  according to Figure 1.5. There are two possibilities of specifying a phase shifting transformer. Either by entering magniTwo-Winding Transformer (3-Phase) (ElmTr2)

6

1

General Description

tude and angle (dutap  and  ϕ tap ) of the additional voltage per tap step or by defining magnitude and angle at each individual tap-step ( U  + dutap ,  ϕ u ). The latter is supported by the measure-  ment report   in the transformer element (see also section 1.2.3).

|

|

1.1.3 Zero sequence models The zero sequence equivalent model of a Yd-transformer as a typical representation including a tap changer at the HV side is shown in Figure  1.6. More transformer models for further configurations are shown in section 2.2.

(a)

(b)

Figure 1.6: Yd transformer (a) in the zero-sequence system with HV side tap changer in detailed (a) and simplified representation (b)

Two-Winding Transformer (3-Phase) (ElmTr2)

7

1

General Description

1.2 Load-Flow Analysis The load flow ComLdf  calculation uses the detailed model for the transformer, that is all shunt and branch impedances for positive- and zero-sequence system. A component that is of special interest for load flow calculations is the tap changer. In the type data section it is modelled using its constructive properties, in the element data section it is defined in its control behaviour for steady-state simulation. There are 3 areas where the tap changer is referenced: 1. Basic data of the tap changer; 2. Tap dependent impedance for a transformer type; 3. Measurement protocol specific for a transformer element.

1.2.1 Tap changer basic data The basic data of the tap changer are listed in the following Table  1.1. Table 1.1: Basic data of tap changers Parameter

Description

Unit

At side

Side at which the tap changer is modelled (not necessarily the side to which the tap changer is connected physically)

-

Additional voltage ∆u per tap

Additional voltage per tap.

%

Phase of  ∆ u

Constant phase between fix voltage and additional voltage of the winding (parameter  φt in Figure 1.5)

degree ( )

Neutral/min./max. position

Range of possible positions for the tap changer. At the neutral position, the winding ratio corresponds to the ratio of the rated voltages

-

Two-Winding Transformer (3-Phase) (ElmTr2)



8

1

General Description

Figure 1.7: Type options for tap changers

1.2.2 Tap dependent impedance The parameter section for the tap-dependent impedance appears when this option is activated (see Figure 1.7). Parameters that can be considered to be tap-dependent are the short circuit impedances and copper losses (short circuit resistance) in the positive- and zero-sequence systems. For tap positions between min. and neutral and between neutral and max. tap dependent parameters are interpolated using splines.

1.2.3 Measurement protocol (element-specific) A very precise method tap-changer description is the so-called  measurement report . Here, all tap-dependent parameters can be entered per tap step. If the option According to measurement report   is enabled the corresponding type-parameters are overwritten by the respective element parameters. The corresponding input dialogue is shown in Figure 1.8 with a brief parameter description in Table  1.2.

Two-Winding Transformer (3-Phase) (ElmTr2)

9

1

General Description

Table 1.2: Data of measurement protocol for transformer elements Parameter

Description

Unit

Voltage

Voltage at tap position i.

kV

Angle

Absolute tap-angle (parameter φu   in Figure 1.5)

degree ( )

uk

S/C voltage of the transformer

%

PCu

Copper losses

kW

Add. rating Factor

Rating factor for considering tap-dependent transformer rating. The additional rating factor is multiplied by the general rating factor (Rating Factor  on the Basic Data page).

(p.u.)



Figure 1.8: Element-specific measurement protocol

1.2.4 Automatic tap changer control Automatic tap changer control is activated by setting the corresponding option on the load flow page of the transformer element. Additionally, automatic tap adjustment can be globally enabled or disabled by the load flow command. The information required for tap changer control is shown in Figure 1.9 and described in Table 1.3.

Two-Winding Transformer (3-Phase) (ElmTr2)

10

1

General Description

Figure 1.9: Data for automatic tap changer control

Two-Winding Transformer (3-Phase) (ElmTr2)

11

1

General Description

Table 1.3: Dialog fields for the automatic tap changer control Parameter

Description

According to Measurement report

Instead of the type data for the tap-dependent transformer values the element-specific measurement report is used

Tap position

Tap position used during the load flow calculation. If Automatic  Tap Changing   is activated this value corresponds to the initial tap position.

Automatic tap changing

Activating automatic tap adjustment in load flow analysis.

Tap changer

continuous  An idealized, continuous tap changer is assumed. As a result, the tap controller can ideally comply with the specified control condition This option is useful for voltage regulators in distribution systems having a very large number of tap steps or for thyristor controlled tap changers. discrete  Standard option. Only integer tap positions are considered.

Controlled node

Setpoint

Control mode

HV LV

Tap controls the HV-side. Tap controls the LV-side

EXT   Slave  mode. The tap changer just follows the tap position of the selected Master -transformer. Only for V  control mode: local  the voltage setpoint and voltage range settings (max./min. voltage) must be enter in the transformer dialog bus target voltage  the voltage setpoint and voltage range settings (max./min. voltage) are taken from the controlled busbar   (topological search) V Voltage control. For unbalanced load flow analysis, the controlled phase needs to be defined additionally. Q Reactive power control (see also Figure 1.10) P Active power control (only applicable to phase shifters, see also Figure 1.10)

Figure 1.10: Orientation of Power values counted positive

Two-Winding Transformer (3-Phase) (ElmTr2)

12

1

General Description

Table 1.4: Additional data for tap changer control Parameter

Description

Set Point

V-/Q-/P- reference (depending on selected control mode)

Lower/Upper bound

Lower and upper boundary of the controlled variable. In case of discrete tap changers, the tap control can drive the controlled variable just into a permitted band. In case of continuous tap changers the tap controller can ideally regulate to the reference point.

Remote Control

Allows for the selection of a bus bar different from the transformer terminals (V-control). In case of P-or Q-control the flow through any cubicle can be controlled.

Voltage control includes optional line drop compensation. This function controls the voltage at a remote busbar without measuring the voltage at that bus-bar. Instead, the actual value is estimated by measuring the voltage at the HV or LV side of the transformer and simulating the voltage drop across the line. The principle of the line drop compensation is shown in Figure 1.11, the corresponding parameters are explained in Table 1.5.

Figure 1.11: Principle of line drop compensation

Table 1.5: Line drop compensation (for voltage control) Parameter

Description

Unit

Current transformer rating

Primary CT-current-rating.

A

Voltage transformer ratio

Ratio of the voltage transformer

-

RSet, XSet

LDC-impedance, defined as voltage drop at rated current. It corresponds to the LDC-impedance in Ohm times the secondary CT current rating.

V

Two-Winding Transformer (3-Phase) (ElmTr2)

13

1

General Description

Generally, there is more than just one possible solution to a load flow problem considering automatic tap changer control. Especially in meshed networks, several transformers can control the voltage in certain areas. In case of parallel transformers, the problem can usually be solved by operating the two parallel transformers in a master slave mode. In a general configuration however, especially when parallel transformer have different short circuit impedances or different tap steps, the steady state network solution cannot be obtained that easily. PowerFactory addresses the mentioned problem by allowing the user to enter a controller time constant, specifying the speed of control actions and hence the participation of several transformers regulating the voltage of the same bus bar. The approach is based on controller block diagrams according to Figure  1.12.  In case of flowcontrollers (P-/Q-control) the controller sensitivity  translating a power mismatch into an equivalent turns-ratio percentage can be entered additionally. In the actual load flow algorithm, which just looks at steady state conditions, controller time constants and sensitivities are translated into equivalent participation factors.

(a)

(b)

Figure 1.12: Principle of simulated dynamic control for V and P/Q

The parameters offered by PowerFactory are explained in Table 1.6. Table 1.6: Dynamic and static control parameters Parameter

Description

Unit

Controller time constant

Time constant of the controller

s

Controller sensitivity dv/dP

Estimated sensitivity of active power flow towards tap changer variations

%/MW

Controller sensitivity dv/dQ

Estimated sensitivity of reactive power flow towards tap changer variations

%/Mvar

1.3 Short-Circuit Analysis 1.3.1 Type data for IEC S/C calculations Short-Circuit calculations according to IEC assume that the shunt impedances in positive- and negative-sequence (magnetizing reactance, iron losses) are neglected. The shunt impedances Two-Winding Transformer (3-Phase) (ElmTr2)

14

1

General Description

in the zero-sequence system however must be considered. These parameters are shown in the dialog of IEC S/C calculation. Another detail specific to IEC calculation is the distinction between no-load and on-load tap changers. Different impedance correction factors apply for each group. The property of on-load variation of the tap changer therefore can be enabled in the IEC S/C calculation dialog.

1.3.2 Element data for IEC S/C calculations This page contains additional information which is used to calculate the impedance correction factor of the transformer. The first criterion defines whether the transformer is a unit transformer or a network transformer. In case of unit transformers, one common correction factor is applied to transformer and generator. Network transformers are individually. Two different calculation procedures can be applied. The first is a general correction independent of the actual operating conditions of a selected transformer. The second is more specific and may lead to more precise calculation results. The selection of the correction method along with the additional data required are shown on the S/C page, as can be seen in Figure  1.13.

Figure 1.13: Type specific data for IEC short-circuit calculations

1.4 RMS Simulation The model used by the RMS simulation is identical to the load flow model. However, the tap controller definitions are not considered here. For the simulation of tap controllers, a separate dynamic model needs to be defined that can be interfaced with the transformer using the input variable nntapin   (tap-input).

1.5 Harmonic Simulation For accurately modelling high frequency effects of transformers, additional capacitances need to be considered, as shown in Figure 1.14. These capacitances are equivalent capacitances of the model and not the actual winding capacitances. For obtaining equivalent capacitances from winding capacitances, the winding connection (D/Y) must be considered additionally. The high frequency model according to Figure 1.14  provides an accurate frequency response

Two-Winding Transformer (3-Phase) (ElmTr2)

15

1

General Description

with respect to voltages and currents at the transformer terminals. However, it is not possible to simulate effects internal to the transformer, such as internal voltage stress.

(a)

(b)

Figure 1.14: HF Model for the external capacitances in positive sequence system (a) and zerosequence system (b)

1.6 EMT Simulation For simulating nonlinear, electromagnetic transient such as transformer inrush currents or ferroresonance, core saturation needs to be included into the transformer model. Furthermore, depending on the frequencies involved in the transient simulation, the transformer model has to account for the stray capacitances between windings and winding to ground.

1.6.1 Saturation characteristic Figure 1.15 shows the equivalent model of 2 winding 3-phase transformer for the positive sequence. For simplicity, the tap changer has been left aside in the figure; however it is considered in the model according to Figure 1.3, Figure 1.4 and Figure 1.5 as described in previous chapters. The exciting current of a transformer (no-load test) consist of an imaginary part, which is the magnetizing current flowing through the non-linear reactance X M  in Figure 1.15, and a smaller real part flowing through the resistance  R F e , which accounts for the excitation losses.

Two-Winding Transformer (3-Phase) (ElmTr2)

16

1

General Description

The non-linear magnetizing reactance X M  represents the saturation characteristic of the transformer and it is defined in the transformer type (TypTr2  EMT simulation page). The model supports the following options:

\

Linear:  no saturation considered Two slope:  the saturation curve is approximated by a two linear slopes Polynomial:  the saturation curve is approximated by a polynom of user-defined order. The polynom fits asymptotically into the piecewise linear definition. Current/Flux values:  the user inputs current-flux values as a sequence of points and selects among a piecewise-linear or spline interpolation.

Figure 1.15: Equivalent circuit of the 2 winding 3-phase transformer for the positive sequence

The position of the magnetizing branch in the equivalent model of Figure 1.15 is defined in terms of the distribution of the leakage reactance and resistance (TypTr2  EMT-Simulation page). Default value is 0.5 which means that the total leakage impedance of the transformer (short-circuit impedance) equally distributes between the HV and the LV winding. The user can modify the position of the magnetizing branch in the transformer model by modifying these factors.

\

Two slope and polynomial characteristic Figure 16 shows the magnetizing current-flux curves for the two slope and polynomial characteristics. The input parameters of both curves are the same except for the saturation exponent, which only applies to the polynomial characteristic. The input parameters are listed in Table 7.

Figure 1.16: Two slope and polynomial saturation curves

Two-Winding Transformer (3-Phase) (ElmTr2)

17

1

General Description

Table 1.7: Basic data of the two-slope and polynomial saturation characteristics Parameter

Description

Unit

Knee Flux

Knee-point of asymptotic piece-wise linear characteristic. Typical value around 1.1 to 1.2 times the rated flux.

p.u.

Linear (unsaturated) reactance

Magnetizing reactance for unsaturated conditions L unsat. In p.u. values, the linear reactance is equal to the reciprocal of the magnetizing current (reactive part of the exciting current).

p.u.

Saturated reactance

Magnetizing reactance for saturated conditions L sat .

p.u.

Saturation exponent

Exponent of polynomial representation (ksat). Typical values are 9,13,15. The higher the exponent the sharper the saturation curve.

-

The reciprocal of the p.u. unsaturated reactance is equal to the the p.u. magnetizing current (i.e. the imaginary part of the exciting current). Therefore, the program automatically adjusts the unsaturated reactance based on the no-load current and no-load losses entered in the load flow page (TypTr2  Load Flow) and vice-versa:

\

1 = X M 

     − I M  I rated

2

P exc S rated

2

(13)

where,

I M : Magnitude of the exciting current in the no-load test P exc :  Excitation losses in the no-load test I R , S R :  Are the rated current and apparent power of the transformer respectively The saturated reactance is also referred as the air-core reactance; it is fairly low compared with the unsaturated reactance. Typical values for two-winding transformers are 1 to 2 times the short-circuit inductance and 3 to 4 times for autotransformes [1]. The polynomial characteristic uses expression 14 to fit the curve asymptotically into the piecewise linear definition. The higher the exponent, the sharper the saturation curve:

ΨM  iM  = LM  Where,

    ·  

Two-Winding Transformer (3-Phase) (ElmTr2)

ΨM  1+ Ψ0

ksat

 

(14)

18

1

General Description

iM  ΨM  LM  Ψ0

Magnetizing current

p.u.

Magnetizing flux

p.u.

Linear reactance

p.u.

This parameter is automatically calculated so that the polynomial characteristic fits the saturated reactance in full saturation and transits steadily into the piece-wise linear characteristic at the knee flux point.

p.u.

ksat

Saturation exponent, i.e. polynome degree

-

This polynomial characteristic is always inside the corresponding linear representation. In full saturation the polynomial characteristic is extended linearly. Compared to the two-slope curve, it does not contain a singular point at the knee flux and therefore its derivate (magnetizing voltage) is continuously defined. The p.u. values used for the definition of the saturation characteristic of the positive sequence model are referred to the following bases quantities: • U base[kV]: nominal voltage of the (energizing) winding, i.e. the winding used for the no load test • S base[MVA]: nominal power of the (energizing) winding

A] √ S 3 · U [M V[kV ] × 1000 √  U  [kV ]/ 3 [V  · s] = × 1000 2πf [Hz] base

• I base [A] =

base

• ψbase

• Lbase [H ] =

base



2 U base [kV ] S base[M V A]

·

1 2πf [Hz]

Current-Flux values The user can also define the saturation curve in terms of measured current-flux values and select between a piecewise linear  or spline   interpolation. The current-flux values in the table are peak values in p.u.. In a power transformer with impressed voltage, the magnetizing flux in p.u. is equal to the magnetizing voltage in p.u., thus flux and voltage are interchangeable and the p.u. current-flux curve represents a p.u. currentvoltage curve as well. Furthermore, it can be assumed that the applied voltage remains fairly linear during the non-load tests and hence the ration between RMS and peak values of the voltage is given by 2.

√ 

On the contrary, the magnetizing current is distorted (non-sinusoidal) because of the saturation curve. As a consequence of that, the ratio between the RMS and peak value of the magnetizing current is not longer 2  and the user has to enter truly peak values in the table.

√ 

The base quantities of the p.u. values in the current-flux table are also referred to the peak values of the corresponding nominal variables:

Two-Winding Transformer (3-Phase) (ElmTr2)

19

1

General Description

√  √ S  [MV A] 2× × 1000 3 · U  [kV ] √   U  [KV ]/√ 3 [V  · s] = 2 × × 1000 2πf [kH z] base

I base[A] =

base

Ψbase

base

1.6.2 Zero Sequence magnetizing reactance The zero sequence magnetizing current strongly depends on the construction characteristic of the transformer core (three-legged, five-legged, shell-type, etc.) and its vector group. Figure 1.17 shows the equivalent circuit for the zero sequence.

Figure 1.17: Equivalent circuit of the 2 winding 3-phase transformer for the zero-sequence

Transformer with delta-connected windings If the transformer has delta-connected windings, then any zero sequence excitation approximates a zero-sequence short-circuit, as the delta-connected winding short-circuits the zerosequence current. In that cases there is no need to represent zero sequence saturation. Transformer without delta-connected windings If the transformer type does not have delta-connected windings, then the zero-sequence excitation current results generally higher than the positive-sequence excitation current and strongly depends on the core type. To account for the higher zero-sequence linear exciting current when no delta-connected winding is available,  PowerFactory allows for the definition of a linear (unsaturated) zero-sequence magnetizing impedance. This zero-sequence magnetizing impedance and its R/X ratio is defined in the load flow page (TypTr2  Load flow); the parameters are made available depending on the vector group (i.e. hidden in case of delta-connected winding).

\

To account for the core type dependency of the the zero-sequence saturation characteristic, the transformer model supports the following two options in the EMT-simulation page (TypTrf ): 3 Limbs core: use this option for three-legged core designs. In this core type, the fluxes are roughly equal in the three legs and must therefore return outside the core through the airgap and the tank. Because of the fact that the air-gap and the tanks are no-magnetic, the zero-sequence magnetizing current is nearly linear and therefore the model uses the linear zero-sequence magnetizing impedance defined in the load flow page. In other words, it does not consider zero-sequence saturation effects. 5 Limbs core: use this option for five-legged and shell-type cores. As the zero-sequence fluxes return inside the core, the model uses the saturation characteristic (of the positive sequence) in the zero-sequence magnetizing reactance as well. Two-Winding Transformer (3-Phase) (ElmTr2)

20

1

General Description

1.6.3 Residual flux The residual flux is the magnetizing flux which remains in the core after the transformer has been switched off. A residual flux, other than a remanent  1 flux, implies then the circulation of a magnetizing current (ΨM  =  L M   I M ).

 ·

Once the transformer has been switched off, this magnetizing current circulates through the noload losses resistance  Rm  and de-magnetizes the core. The flux decays then exponentially with a time constant  L m / Rm  with Lm  the linear magnetizing inductance. To simulate the decaying magnetizing current and hence the decaying residual flux it is necessary to define the no-load losses. Otherwise, if Rm =0, the magnetizing current cannot circulate and   PowerFactory will automatically set the residual flux to 0 as soon as the transformer has been switched off. The user can also define the residual flux in the EMT simulation by a parameter event. For simplicity, the residual flux is entered in dq0-components using the following signals: psimd:  residual flux, d-component in p.u. psimq:  residual flux, q-component in p.u. psim0:  residual flux, zero-sequence component in p.u. The dq0-transformation relates the dq0-fluxes with the abc-fluxes (phase or natural components) as follows:

       ψd ψq = ψ0

2 3 0

− 13 13 √ 13 − √ 13 ×

1 3

1 3

       

1 3

ψa ψb ψc

The inverse transformation is given by:

     − − ψa ψb = ψc

1 1 2 1 2

√ 03 2 √  − 23

   ×    

1 1 1

ψd ψq ψ0

The calculation parameters c:psim c, c:psim b and c:psim c  give the resulting flux (simulation result) in natural components for the phases a, b and c respectively. It is in general quite difficult to predict the residual flux of a transformer in a reliably way. However as the residual flux has a major impact on the amplitude of inrush currents, it has to be considered in the model. If it is not known, typical maximum values between 0.8 and 0.9 p.u. can be assumed for worst-case conditions.

1.6.4 Stray capacitances In high frequency EMT-applications, e.g. switching or lightning studies, transformer capacitances have to be considered. 1 The

remanent flux is the flux at i=0 in the hysteresis curve

Two-Winding Transformer (3-Phase) (ElmTr2)

21

1

General Description

The stray capacitances of a transformer do not only depend on its construction characteristics of the transformer (like for instance length of the windings, insulating material, core dimensions, etc.) but also on its installation characteristics as well (indoor or outdoor transformer, proximity to other grounded components, walls, etc.). For that reason, the stay capacitances are not part of the transformer type data but defined in the element (ElmTr2 ). On the EMT-Simulation page of the element (ElmTr2  EMT-Simulation) the user can enable the stray capacitances in the model by ticking the  Consider Capacitances  option. The model account for the following capacitances:

\

Capacitance HV to ground:  applies both for the positive and zero-sequence Capacitanve LV to ground:  applies both for the positive and zero-sequence Capacitance HV-LV, positive sequence: Capacitance HV-LV, zero sequence: For typical values the reader is referred to [2].

Two-Winding Transformer (3-Phase) (ElmTr2)

22

2

2

Modelling Details and Application Hints

Modelling Details and Application Hints

2.1 Reference Values All transformer parameters entered in p.u. or % are referred to the transformer ratings. Transformer rated voltages different from nominal bus bar voltages are correctly considered.

2.2 Zero Sequence Models of Common Vector Groups 2.2.1 Yd-transformer This model is described in detail in section  1.1.3 as a general example for the zero-sequence system modelling. Please refer to that section for further explanation. If no accurate data are available from the manufacturer, the following estimations can be used for the zero-sequence impedance voltages as seen from the grounded side: Core-type transformer (3-limb) usc,0  = 0.85  U sc,1 , Shell-type transformer (4/5-limb) usc,0

 ·  = 1.0 · U 

sc,1 ,

uRr,0  = 0 uRr,0  = 0

where u sc,0  is the positive sequence impedance voltage. Concerning the model for the magnetic flux saturation characteristics the transformer types with 3 or 4/5 limbs behave differently in general. In the 3-limb design, the zero-sequence flux defined by 15  is not guided via the transformer limbs but uses parallel paths (e.g. through the transformer vessel, oil, ) and thus can be modelled as linear without saturation effects.

Ψ0  =

1  (ΨA + Ψ B  + ΨC ) 3

 ·

 

(15)

2.2.2 YNyn/YNy /Yyn -transformer The zero sequence equivalent circuit diagram of the YNyn transformers is depicted in Figure2.1. The equivalent circuit diagram of star connected transformers with isolated star point can be derived from this equivalent circuit by assuming infinite grounding impedances at the respective side.

Two-Winding Transformer (3-Phase) (ElmTr2)

23

2

Modelling Details and Application Hints

Figure 2.1: YNyn transformer (zero-sequence system)

S/C impedance HV-side zsc,0,HV   =  r Cu, 0,HV   +  x σ,0,HV   S/C impedance LV-side zsc,0,LV   =  r Cu,0,LV   +  x σ,0,LV   S/C impedance both sides zsc,0  =  z sc,0,HV   +  z sc,0,LV   The zero-sequence magnetizing impedance ratio depends strongly on the construction of the magnetic circuit of the transformers. Typical ranges are: Core-type transformer (3-limb)

zM 0 zsc,0

Shell-type transformer (4/5-limb)

= 3 . .. 10

zM 0 zsc,0

= 10 . . . 100 (or bank of 3 single phase units)

2.2.3 Model of YNyn/YNy/Yyn-transformer with closed tertiary delta winding An internal tertiary delta winding can be considered either using the PowerFactory three-winding model or, in a simplified way, by considering that the short circuit impedance of the internal delta winding can be modeled by an impedance parallel to the zero sequence magnetizing impedance of Figure 19. Hence, an internal delta winding can be modeled by simply assuming a very low zero-sequence magnetizing reactance. Typical values are:

zM 0 = 1..2.4 zsc,0

Two-Winding Transformer (3-Phase) (ElmTr2)

24

2

Modelling Details and Application Hints

The short circuit resistance of the delta-tertiary winding can be entered as R/X ratio in the Mag. R/X  field.

Figure 2.2: Zero sequence model of YNYnd-Transformer

2.2.4 Model of YNzn/YNz/Zyn-transformer A zig-zag winding completely uncouples primary and secondary side of the zero sequence system, as shown in Figure 2.3.

Figure 2.3: YNzn transformer (zero-sequence system) with HV side tap changer in detailed representation

Two-Winding Transformer (3-Phase) (ElmTr2)

25

2

Modelling Details and Application Hints

2.3 Auto-transformer Model The  PowerFactory model for the auto-transformer is a special case of the 2-winding star/star (YY)-Transformer. As soon as an auto-transformer symbol is entered, the option Connected Star Points (Autotrans-  former) can be checked on the Basic Data page of the element (see Figure 21). This activates the interpretation as an autotransformer. This option only is shown when the type selected for the transformer is of vector group YY. The effect of this connection can be seen in Figure 22. Besides the additional connection between the star points, only one grounding impedance can be entered.

Figure 2.4: Auto-transformer option

Two-Winding Transformer (3-Phase) (ElmTr2)

26

2

Modelling Details and Application Hints

Figure 2.5: YY transformer (zero-sequence system) in auto-transformer configuration (incl. tap changer on the HV side)

For the YY autotransformer the currents of HV side and LV side both flow through the same grounding impedance Z E  = RE  + jX E . The voltage over this grounding impedance Z E   thus affects the zero-sequence system voltages on both sides. This makes it necessary to consider the absolute value of the impedances, currents and voltages and not the p.u.-values. Very often, an additional delta tertiary winding is used to reduce the zero-sequence impedance of auto-transformers. The approach for modeling this is equivalent to the internal delta tertiary winding modeling of Yy-transformers.

Two-Winding Transformer (3-Phase) (ElmTr2)

27

2

Modelling Details and Application Hints

Figure 2.6: YYd transformer (zero-sequence system) in auto-transformer configuration

Two-Winding Transformer (3-Phase) (ElmTr2)

28

3

3

Input/Output Definitions of Dynamic Models

Input/Output Definitions of Dynamic Models

Figure 3.1: Input/Output Definition of 2-winding transformer model for RMS and EMT simulation

Table 3.1: Input Variables of RMS and EMT transformer model Parameter

Description

Unit

nntapin

Tap position (input)

-

Table 3.2: State Variables of transformer model for EMT-simulation Parameter

Description

Unit

psimd

Magnetizing flux, d-component

p.u.

psimq

Magnetizing flux, q-component

p.u.

psim0

Magnetizing flux, 0-component

p.u.

Table 3.3: Additional parameters and signals of EMT transformer model (calculation parameter) Parameter

Description

Unit

psim a

Magnetizing flux, phase A

p.u.

psim b

Magnetizing flux, phase B

p.u.

psim c

Magnetizing flux, phase C

p.u.

im a

Magnetizing current, phase A

p.u.

im b

Magnetizing current, phase B

p.u.

im c

Magnetizing current, phase C

p.u.

Two-Winding Transformer (3-Phase) (ElmTr2)

29

4

4

Input Parameter Definitions

Input Parameter Definitions

4.1 2-Winding-Transformer Type Parameter

Description

loc name

Name

nt2ph

Technology

strn

Rated Power

MVA

frnom

Nominal Frequency

Hz

utrn h

Rated Voltage: HV-Side

kV

utrn l

Rated Voltage: LV-Side

kV

uktr

Positive Sequence Impedance: Short-Circuit Voltage uk

%

pcutr

Positive Sequence Impedance: Copper Losses

kW

uktrr

Positive Sequence Impedance: SHC-Voltage (Re(uk)) ukr

%

xtor

Positive Sequence Impedance: Ratio X/R

tr2cn h

Vector Group: HV-Side

tr2cn l

Vector Group: LV-Side

nt2ag

Vector Group: Phase Shift

vecgrp

Vector Group: Name

uk0tr

Zero Sequ. Impedance, Shor t-Circuit Voltage: Absolute uk0

%

ur0tr

Zero Sequ. Impedance, Shor t-Circuit Voltage: Resistive Part ukr0

%

tap side

Tap Changer: at Side

dutap

Tap Changer: Additional Voltage per Tap

%

phitr

Tap Changer: Phase of du

deg

nntap0

Tap Changer: Neutral Position

ntpmn

Tap Changer: Minimum Position

ntpmx

Tap Changer: Maximum Position

curmg

Magnetizing Impedance: No Load Current

%

pfe

Magnetizing Impedance: No Load Losses

kW

zx0hl n

Zero Sequence Magnetizing Impedance: Mag. Impedance / uk0

rtox0 n

Zero Sequence Magnetizing R/X ratio: Mag. R/X

zx0hl h

Distribution of Zero Sequ. Leakage-Impedances: z, Zero Sequ. HV-Side

Two-Winding Transformer (3-Phase) (ElmTr2)

Unit

*30deg

30

4

Input Parameter Definitions

Parameter

Description

zx0hl l

Distribution of Zero Sequ. Leakage-Impedances: z, Zero Sequ. LV-Side

itapzdep

Tap dependent impedance

uktmn

Tap dependent impedance: uk (min. tap)

%

uktmx

Tap dependent impedance: uk (max. tap)

%

pcutmn

Tap dependent impedance: Pcu (min. tap)

kW

ukr tmn

Tap dependent impedance: Re(uk) (min. tap)

%

xtortmn

Tap dependent impedance: X/R (min. tap)

pcutmx

Tap dependent impedance: Pcu (max. tap)

kW

ukr tmx

Tap dependent impedance: Re(uk) (max. tap)

%

xtortmx

Tap dependent impedance: X/R (max. tap)

uk0tmn

Tap dependent impedance: uk0 (min. tap)

%

uk0tmx

Tap dependent impedance: uk0 (max. tap)

%

uk0rtmn

Tap dependent impedance: Re(uk0) (min. tap)

%

uk0rtmx

Tap dependent impedance: Re(uk0) (max. tap)

%

itrdl

Distribution of Leakage Reactances (p.u.): x,Pos.Seq. HV-Side

itrdl lv

Distribution of Leakage Reactances (p.u.): x,Pos.Seq. LV-Side

itrdr

Distribution of Leakage Resistances (p.u.): r,Pos.Seq. HV-Side

itrdr lv

Distribution of Leakage Resistances (p.u.): r,Pos.Seq. LV-Side

oltc

On-load Tap Changer

pT

Tap Changer: Voltage Range

ansiclass

Class

pict2

Inrush Peak Current: Ratio Ip/In

p.u.

pitt2

Inrush Peak Current: Max. Time

s

itrmt

Magnetizing Reactance: Type

psi0

Magnetizing Reactance: Knee Flux

p.u.

xmlin

Magnetizing Reactance: Linear Reactance

p.u.

xmair

Magnetizing Reactance: Saturated Reactance

p.u.

Two-Winding Transformer (3-Phase) (ElmTr2)

Unit

%

31

4

Input Parameter Definitions

Parameter

Description

ksat

Saturation Exponent

it0mt

Zero Sequence Magnetizing Reactance: Type Zero Sequence

pStoch

Stochastic model

Unit

StoTyptrf

4.2 2-Winding-Transformer Element Parameter

Description

loc name

Name

typ id

Type (TypTr2 )

bushv

HV-Side (StaCubic)

bushv bar

HV-Side

buslv

LV-Side (StaCubic)

buslv bar

LV-Side

iZoneBus

Zone

outserv

Out of Service

ntnum

Number of: parallel Transformers

ratfac

Rating Factor

Snom

Rated Power

i auto

Connected Star Points (Auto Transformer)

i eahv

HV-side, phase 2 internally grounded

ignd h

Grounding Impedance, HV Side: Neutral Point

re0tr h

Grounding Impedance, HV Side: Re

Ohm

xe0tr h

Grounding Impedance, HV Side: Xe

Ohm

i ealv

LV-side, phase 2 internally grounded

ignd l

Grounding Impedance, LV Side: Neutral Point

re0tr l

Grounding Impedance, LV Side: Re

Ohm

xe0tr l

Grounding Impedance, LV Side: Xe

Ohm

rSbasepu

r (Sbase)

p.u./Sbase

xSbasepu

x (Sbase)

p.u./Sbase

r0Sbasepu

r0 (Sbase)

p.u./Sbase

x0Sbasepu

x0 (Sbase)

p.u./Sbase

Inom h

HV-Side, Rated Current

kA

Inom l

LV-Side, Rated Current

kA

iTaps

According to Measurement Repor t

nntap

Tap: Tap Position

ntrcn

Tap: Automatic Tap Changing

i cont

Tap: Tap Changer

t2ldc

Tap: Controlled Node

ilcph

Tap: Phase

Two-Winding Transformer (3-Phase) (ElmTr2)

Unit

MVA

32

4

Input Parameter Definitions

Parameter

Description

imldc

Tap: Control Mode

i rem

Tap: Remote Control

p rem

Tap: Controlled Node (StaBar,ElmTerm)

p cub

Tap: Controlled Branch (Cubicle) (StaCubic)

usetp

Tap: Voltage Setpoint

p.u.

usp low

Tap: Lower Voltage Bound

p.u.

usp up

Tap: Upper Voltage Bound

p.u.

psetp

Tap: Active Power Setpoint

MW

psp low

Tap: Lower Active Power Bound

MW

psp up

Tap: Upper Active Power Bound

MW

qsetp

Tap: Reactive Power Setpoint

Mvar

qsp low

Tap: Lower Reactive Power Bound

Mvar

qsp up

Tap: Upper Reactive Power Bound

Mvar

Tctrl

Tap: Controller Time Constant

s

ildc

Tap: Line Drop Compensation

ldcct

Tap: Current Transformer Rating

ldcpt

Tap: Voltage Transformer Ratio

ldcrs

Tap: Rset V

ldcxs

Tap: Xset V

tapctrl

Tap Controller (ElmTr2)

iMeasLoc

Measured at

mTaps

Measurement Report

iblock

Unit Transformer

ilt op

Long-term operating condition before short-circuit are known

Ub lv

Values for LV-Side: Highest Operating Voltage

kV

Ib lv

Values for LV-Side: Highest Operating Current

kA

cosphib lv

Values for LV-Side: Power factor

Ubqmin hv

Values for HV-Side (only for Unit Transformer): Minimum Operating Voltage

ifrqft

Frequent Fault ( > 10(5)/lifetime, Category II(III) )

iopt hf

Consider HF-Parameter

Cg h

HF-Parameter: Capacitance HV-Ground

myF

Cg l

HF-Parameter: Capacitance LV-Ground

myF

Cc1 hl

HF-Parameter: Capacitance HV-LV, 1-Sequence

myF

Cc0 hl

HF-Parameter: Capacitance HV-LV, 0-Sequence

myF

Two-Winding Transformer (3-Phase) (ElmTr2)

Unit

A

kV

33

4

Input Parameter Definitions

Parameter

Description

Unit

FOR1

Forced Outage Rate

1/a

FOE

Forced Outage Expectancy

h/a

FOD

Forced Outage Duration

h

iperfect

Ideal component

pTypStoch

Type model

pStoch

Element model

i uopt

OPF-Controls: Tap Position

maxload

OPF-Constraints: Max. Loading

Two-Winding Transformer (3-Phase) (ElmTr2)

StoTyptrf %

34

5

5

References

References

[1] Guidelines for representation of network elements when calculating transients. Technical report, Cigre Working Group 33.02, 1990. [2] Allan Greenwood. Electrical Transients in Power Systems . John Wiley & Sons, 1991.

Two-Winding Transformer (3-Phase) (ElmTr2)

35

List of Figures

List of Figures 1.1 Positive sequence model of the 2-winding transformer (in Ohms)   . . . . . . . . .

4

1.2 Positive sequence model of the 2-winding transformer (in p.u.) . . . . . . . . . .

4

1.3 Transformer model with tap changer modelled at HV - side . . . . . . . . . . . . .

6

1.4 Transformer model with tap changer modelled at LV - side   . . . . . . . . . . . . .

6

1.5 Complex tap changer model in PowerFactory   . . . . . . . . . . . . . . . . . . . .

6

1.6 Yd transformer (a) in the zero-sequence system with HV side tap changer in detailed (a) and simplified representation (b) . . . . . . . . . . . . . . . . . . . .

7

1.7 Type options for tap changers   . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9

1.8 Element-specific measurement protocol   . . . . . . . . . . . . . . . . . . . . . . .

10

1.9 Data for automatic tap changer control  . . . . . . . . . . . . . . . . . . . . . . . .

11

1.10 Orientation of Power values counted positive . . . . . . . . . . . . . . . . . . . .

12

1.11 Principle of line drop compensation . . . . . . . . . . . . . . . . . . . . . . . . . .

13

1.12 Principle of simulated dynamic control for V and P/Q   . . . . . . . . . . . . . . . .

14

1.13 Type specific data for IEC short-circuit calculations   . . . . . . . . . . . . . . . . .

15

1.14 HF Model for the external capacitances in positive sequence system (a) and zerosequence system (b)  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

16

1.15 Equivalent circuit of the 2 winding 3-phase transformer for the positive sequence

17

1.16 Two slope and polynomial saturation curves

. . . . . . . . . . . . . . . . . . . .

17

1.17 Equivalent circuit of the 2 winding 3-phase transformer for the zero-sequence . .

20

2.1 YNyn transformer (zero-sequence system) . . . . . . . . . . . . . . . . . . . . .

24

2.2 Zero sequence model of YNYnd-Transformer   . . . . . . . . . . . . . . . . . . . .

25

2.3 YNzn transformer (zero-sequence system) with HV side tap changer in detailed representation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

25

2.4 Auto-transformer option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

26

2.5 YY transformer (zero-sequence system) in auto-transformer configuration (incl. tap changer on the HV side) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

27

2.6 YYd transformer (zero-sequence system) in auto-transformer configuration   . . .

28

3.1 Input/Output Definition of 2-winding transformer model for RMS and EMT simulation 29

Two-Winding Transformer (3-Phase) (ElmTr2)

36

List of Tables

List of Tables 1.1 Basic data of tap changers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8

1.2 Data of measurement protocol for transformer elements   . . . . . . . . . . . . . .

10

1.3 Dialog fields for the automatic tap changer control . . . . . . . . . . . . . . . . .

12

1.4 Additional data for tap changer control   . . . . . . . . . . . . . . . . . . . . . . . .

13

1.5 Line drop compensation (for voltage control) . . . . . . . . . . . . . . . . . . . . .

13

1.6 Dynamic and static control parameters  . . . . . . . . . . . . . . . . . . . . . . . .

14

1.7 Basic data of the two-slope and polynomial saturation characteristics . . . . . . .

18

3.1 Input Variables of RMS and EMT transformer model . . . . . . . . . . . . . . . .

29

3.2 State Variables of transformer model for EMT-simulation   . . . . . . . . . . . . . .

29

3.3 Additional parameters and signals of EMT transformer model (calculation parameter)   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

29

Two-Winding Transformer (3-Phase) (ElmTr2)

37

View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF