Inbreathing: If tank capacity 3500 m3 Total Inbreathing = Pumpout + 3.2*(tank capacity (m3))0.651 Outbreathing: Liquids with flashpoint >37.8 deg C or NBP above 149 deg C If tank capacity 3500 m3 Total Outbreathing = 1.069*Pump-in + 1.92*(Tank Capacity(m3))0.651 Liquids with flashpoint