SV POWER Lightning Protection Calculation Sheet_T.G Building
December 19, 2016 | Author: Prabhash Arvind Verma | Category: N/A
Short Description
Download SV POWER Lightning Protection Calculation Sheet_T.G Building...
Description
PROJECT : CLIENT :CLIENT'S CONSULTANT :E-BOP CONTRACTOR :-
1x 63 MW TPP AT KORBA,CHATTISGARH S V POWER PVT LTD DESEIN PVT LTD ABB LTD,FARIDABAD
LIGHTNING PROTECTION CALCULATION FOR TG BLDG.AB-BC BAY ( REFERENCE : IS 2309 ) Symbol / Formulae / Description / Parameter References A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION i) Input Data :a) Dimensions of Building / Structure L ( Refer the Relevant Layout W Drawings of the Building / H Structure )
Length of the Building Width of the Building Height of the Building
b)
Probable Number of Strikes to Building / Structure per Year ( Refer Clause 8.1.2 of IS 2309 ) Overall Multiplying Factor Overall Risk Factor Calculated
m m m
N Ng A B C D E
( Refer Fig. 1 of IS 2309 ) ( Refer Clause 8.1.2 of ( Refer Table 1A of IS 2309 ) ( Refer Table 1B of IS 2309 ) ( Refer Table 1C of IS 2309 ) ( Refer Table 1D of IS 2309 ) ( Refer Table 1E of IS 2309 )
= = = = = = =
Ac
=
(L x W) + 2 (L x H) + 2(W x H) + 3.14 H2
=
P
= Ac x Ng x 10-6 times/year =
100 No. of Days / Year 9.2 Nos./km2/year 1 0.8 1 0.4 0.3
Rf-C
= AxBxCxDxE Overall Multiplying = Factor x P
= = ie
7389.06 Meter2 0.067979 Times per year 0.096000 0.006526 6.5260E-03
Maximum Acceptable Overall Risk Factor:Maximum Acceptable Overall Risk Factor
iv)
60.00 28.00 23.00
Calculations :Collection Area ( Refer Clause 8.1.2 of IS 2309 )
iii)
= = =
Unit
Lightning Flash Density & Weighing Factors Number of Thunderstorm Days / Year Lightning Flash Density (Flashes to Ground /km2/year) Weighting Factor A ( Use of Structure ) Weighting Factor B ( Type of Construction ) Weighting Factor C ( Content of Consequential Effects ) Weighting Factor D ( Degree of Isolation ) Weighting Factor E ( Type of Country )
ii)
Value
Rf-A
( Refer Clauses 8.1.3 & 8.1.6 of IS 2309 )
=
0.000001
ie
1.000E-06
Result / Conclusion :Since Overall Risk Factor Calculated Maximum Acceptable Overall Risk Factor > Hence, Lightning Protection is Required.
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS Calculations (As per Clause 12.2.3 of IS-2309):Ab = ( L x W ) Base Area of Structure P = 2(L+W) Perimeter of Structure i) For Base Area (Ab) < 100m2 a) Number of Down Conductors Required
ii)
= =
1680 Meter2 176 Meter
= For Ab < 100m2
=
1 Nos
= 1+(Ab-100)/300
=
6 Nos
For Base Area (Ab) > 100m2 b) Based on Base Area of Structure:Number of Down Conductors Required c) Based on Parimeter of Structure:Number of Down Conductors Required
REVISION DETAILS
= P/30 = 6 Nos. Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309) = Hence, Required Number of Down Conductors 6 Nos.
Rev.
Date
Drg/Doc. No.
Remarks
Prepared
Reviewed
Approved
R0
12.10.2009
3VYN855200
First Submission
HK
KVP
KVP
1x70 MW TPP AT KORBA,CHATTISGARH RRVUNL DCPL, New Delhi Indure, New Delhi
PROJECT : CLIENT :CONSULTANT :BOP CONTRACTOR :-
LIGHTNING PROTECTION CALCULATION ( REFERENCE : IS 2309 ) FOR
CW PUMP HOUSE
Symbol / Formulae / References A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION i) Input Data :a) Dimensions of Building / Structure Description / Parameter
L ( Refer the Relevant Layout W Drawings of the Building / H Structure )
Length of the Building Width of the Building Height of the Building
b)
Probable Number of Strikes to Building / Structure per Year ( Refer Clause 8.1.2 of IS 2309 ) Overall Multiplying Factor Overall Risk Factor Calculated
m m m
N Ng A B C D E
( Refer Fig. 1 of IS 2309 ) ( Refer Clause 8.1.2 of ( Refer Table 1A of IS 2309 ) ( Refer Table 1B of IS 2309 ) ( Refer Table 1C of IS 2309 ) ( Refer Table 1D of IS 2309 ) ( Refer Table 1E of IS 2309 )
= = = = = = =
Ac
=
(L x W) + 2 (L x H) + 2(W x H) + 3.14 H2
=
P
= Ac x Ng x 10-6 times/year =
27 No. of Days / Year 5 Nos./km2/year 1 0.2 1 0.4 0.3
Rf-C
= AxBxCxDxE Overall Multiplying = Factor x P
= = ie
3452.79 Meter2 0.017264 Times per year 0.024000 0.000414 4.1434E-04
Maximum Acceptable Overall Risk Factor:Maximum Acceptable Overall Risk Factor
iv)
43.62 12.20 17.53
Calculations :Collection Area ( Refer Clause 8.1.2 of IS 2309 )
iii)
= = =
Unit
Lightning Flash Density & Weighing Factors Number of Thunderstorm Days / Year Lightning Flash Density (Flashes to Ground /km2/year) Weighting Factor A ( Use of Structure ) Weighting Factor B ( Type of Construction ) Weighting Factor C ( Content of Consequential Effects ) Weighting Factor D ( Degree of Isolation ) Weighting Factor E ( Type of Country )
ii)
Value
Rf-A
( Refer Clauses 8.1.3 & 8.1.6 of IS 2309 )
=
0.000001
ie
1.000E-06
Result / Conclusion :Since Overall Risk Factor Calculated Maximum Acceptable Overall Risk Factor > Hence, Lightning Protection is Required.
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS Calculations (As per Clause 12.2.3 of IS-2309):Ab = ( L x W ) Base Area of Structure P = 2(L+W) Perimeter of Structure i) For Base Area (Ab) < 100m2 a) Number of Down Conductors Required
ii)
= =
532.10 Meter2 111.63 Meter
= For Ab < 100m2
=
1 Nos
= 1+(Ab-100)/300
=
2 Nos
For Base Area (Ab) > 100m2 b) Based on Base Area of Structure:Number of Down Conductors Required c) Based on Parimeter of Structure:Number of Down Conductors Required
REVISION DETAILS
= P/30 = 4 Nos. Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309) = Hence, Required Number of Down Conductors 2 Nos.
Rev.
Date
Drg/Doc. No.
Remarks
Prepared
Reviewed
Approved
R0
30.06.2009
3VYN855200
First Submission
RK
PS
PAS
1x250MW SURATGARH S.T.P.S. Unit-6 (Stage-IV) RRVUNL DCPL, New Delhi Indure, New Delhi
PROJECT : CLIENT :CONSULTANT :BOP CONTRACTOR :-
LIGHTNING PROTECTION CALCULATION ( REFERENCE : IS 2309 ) FOR CW TREATMENT AREA Symbol / Formulae / References A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION i) Input Data :a) Dimensions of Building / Structure Description / Parameter
L ( Refer the Relevant Layout W Drawings of the Building / H Structure )
Length of the Building Width of the Building Height of the Building
b)
Probable Number of Strikes to Building / Structure per Year ( Refer Clause 8.1.2 of IS 2309 ) Overall Multiplying Factor Overall Risk Factor Calculated
m m m
N Ng A B C D E
( Refer Fig. 1 of IS 2309 ) ( Refer Clause 8.1.2 of ( Refer Table 1A of IS 2309 ) ( Refer Table 1B of IS 2309 ) ( Refer Table 1C of IS 2309 ) ( Refer Table 1D of IS 2309 ) ( Refer Table 1E of IS 2309 )
= = = = = = =
Ac
=
(L x W) + 2 (L x H) + 2(W x H) + 3.14 H2
=
P
= Ac x Ng x 10-6 times/year =
27 No. of Days / Year 5 Nos./km2/year 1 0.2 1 0.4 0.3
Rf-C
= AxBxCxDxE Overall Multiplying = Factor x P
= = ie
1999.25 Meter2 0.009996 Times per year 0.024000 0.000240 2.3991E-04
Maximum Acceptable Overall Risk Factor:Maximum Acceptable Overall Risk Factor
iv)
40.23 30.23 5.00
Calculations :Collection Area ( Refer Clause 8.1.2 of IS 2309 )
iii)
= = =
Unit
Lightning Flash Density & Weighing Factors Number of Thunderstorm Days / Year Lightning Flash Density (Flashes to Ground /km2/year) Weighting Factor A ( Use of Structure ) Weighting Factor B ( Type of Construction ) Weighting Factor C ( Content of Consequential Effects ) Weighting Factor D ( Degree of Isolation ) Weighting Factor E ( Type of Country )
ii)
Value
Rf-A
( Refer Clauses 8.1.3 & 8.1.6 of IS 2309 )
=
0.000001
ie
1.000E-06
Result / Conclusion :Since Overall Risk Factor Calculated Maximum Acceptable Overall Risk Factor > Hence, Lightning Protection is Required.
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS Calculations (As per Clause 12.2.3 of IS-2309):Ab = ( L x W ) Base Area of Structure P = 2(L+W) Perimeter of Structure i) For Base Area (Ab) < 100m2 a) Number of Down Conductors Required
ii)
= =
1216.15 Meter2 140.92 Meter
= For Ab < 100m2
=
1 Nos
= 1+(Ab-100)/300
=
5 Nos
For Base Area (Ab) > 100m2 b) Based on Base Area of Structure:Number of Down Conductors Required c) Based on Parimeter of Structure:Number of Down Conductors Required
REVISION DETAILS
= P/30 = 5 Nos. Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309) = Hence, Required Number of Down Conductors 5 Nos.
Rev. R0
Date
Drg/Doc. No.
30.06.2009 3VYN855200
Remarks
Prepared
Reviewed
Approved
First Submission
RK
PS
PAS
1x250MW SURATGARH S.T.P.S. Unit-6 (Stage-IV) RRVUNL DCPL, New Delhi Indure, New Delhi
PROJECT : CLIENT :CONSULTANT :BOP CONTRACTOR :-
LIGHTNING PROTECTION CALCULATION ( REFERENCE : IS 2309 ) FOR RAW WATER PUMP HOUSE Symbol / Formulae / References A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION i) Input Data :a) Dimensions of Building / Structure Description / Parameter
L ( Refer the Relevant Layout W Drawings of the Building / H Structure )
Length of the Building Width of the Building Height of the Building
b)
Probable Number of Strikes to Building / Structure per Year ( Refer Clause 8.1.2 of IS 2309 ) Overall Multiplying Factor Overall Risk Factor Calculated
m m m
N Ng A B C D E
( Refer Fig. 1 of IS 2309 ) ( Refer Clause 8.1.2 of ( Refer Table 1A of IS 2309 ) ( Refer Table 1B of IS 2309 ) ( Refer Table 1C of IS 2309 ) ( Refer Table 1D of IS 2309 ) ( Refer Table 1E of IS 2309 )
= = = = = = =
Ac
=
(L x W) + 2 (L x H) + 2(W x H) + 3.14 H2
=
P
= Ac x Ng x 10-6 times/year =
27 No. of Days / Year 5 Nos./km2/year 1 0.2 1 0.4 0.3
Rf-C
= AxBxCxDxE Overall Multiplying = Factor x P
= = ie
1542.54 Meter2 0.007713 Times per year 0.024000 0.000185 1.8510E-04
Maximum Acceptable Overall Risk Factor:Maximum Acceptable Overall Risk Factor
iv)
33.30 8.60 10.70
Calculations :Collection Area ( Refer Clause 8.1.2 of IS 2309 )
iii)
= = =
Unit
Lightning Flash Density & Weighing Factors Number of Thunderstorm Days / Year Lightning Flash Density (Flashes to Ground /km2/year) Weighting Factor A ( Use of Structure ) Weighting Factor B ( Type of Construction ) Weighting Factor C ( Content of Consequential Effects ) Weighting Factor D ( Degree of Isolation ) Weighting Factor E ( Type of Country )
ii)
Value
Rf-A
( Refer Clauses 8.1.3 & 8.1.6 of IS 2309 )
=
0.000001
ie
1.000E-06
Result / Conclusion :Since Overall Risk Factor Calculated Maximum Acceptable Overall Risk Factor > Hence, Lightning Protection is Required.
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS Calculations (As per Clause 12.2.3 of IS-2309):Ab = ( L x W ) Base Area of Structure P = 2(L+W) Perimeter of Structure i) For Base Area (Ab) < 100m2 a) Number of Down Conductors Required
ii)
= =
286.38 Meter2 83.8 Meter
= For Ab < 100m2
=
1 Nos
= 1+(Ab-100)/300
=
2 Nos
For Base Area (Ab) > 100m2 b) Based on Base Area of Structure:Number of Down Conductors Required c) Based on Parimeter of Structure:Number of Down Conductors Required
REVISION DETAILS
= P/30 = 3 Nos. Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309) = Hence, Required Number of Down Conductors 2 Nos.
Rev.
Date
Drg/Doc. No.
Remarks
Prepared
Reviewed
Approved
R0
30.06.2009
3VYN855200
First Submission
RK
PS
PAS
1x250MW SURATGARH S.T.P.S. Unit-6 (Stage-IV) RRVUNL DCPL, New Delhi Indure, New Delhi
PROJECT : CLIENT :CONSULTANT :BOP CONTRACTOR :-
LIGHTNING PROTECTION CALCULATION ( Reference : IS 2309 ) for Description / Parameter
RWPH MCC Room
Symbol / Formulae / References
Value
Unit
A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION i) Input Data :a) Dimensions of Building / Structure L ( Refer the Relevant Layout W Drawings of the Building / H Structure )
Length of the Building Width of the Building Height of the Building
b)
Lightning Flash Density (Flashes to Ground /km2/year) Weighting Factor A ( Use of Structure ) Weighting Factor B ( Type of Construction ) Weighting Factor C ( Content of Consequential Effects ) Weighting Factor D ( Degree of Isolation ) Weighting Factor E ( Type of Country )
Probable Number of Strikes to Building / Structure per Year ( Refer Clause 8.1.2 of IS 2309 ) Overall Multiplying Factor Overall Risk Factor Calculated
N Ng A B C D E
( Refer Fig. 1 of IS 2309 ) = (Refer Clause 8.1.2 of IS 2309) = ( Refer Table 1A of IS 2309 ) = ( Refer Table 1B of IS 2309 ) = ( Refer Table 1C of IS 2309 ) = ( Refer Table 1D of IS 2309 ) = ( Refer Table 1E of IS 2309 ) =
Ac
=
(L x W) + 2 (L x H) + 2(W x H) + 3.14 H2
=
P
= Ac x Ng x 10-6 times/year
=
27 No. of Days / Year 5 Nos./km2/year 1 0.2 1 0.4 0.3
Rf-C
= AxBxCxDxE = Overall Multiplying Factor = = xP ie
628.27 Meter2 0.003141 Times per year 0.024000 0.000075 7.5392E-05
Maximum Acceptable Overall Risk Factor:Maximum Acceptable Overall Risk Factor
iv)
m m m
Calculations :Collection Area ( Refer Clause 8.1.2 of IS 2309 )
iii)
22.80 9.81 5.00
Lightning Flash Density & Weighing Factors Number of Thunderstorm Days / Year
ii)
= = =
Rf-A
( Refer Clauses 8.1.3 & 8.1.6 of IS 2309 )
=
0.000001
ie
1.000E-06
Result / Conclusion :Since Overall Risk Factor Calculated Maximum Acceptable Overall Risk Factor > Hence, Lightning Protection is Required.
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS Calculations (As per Clause 12.2.3 of IS-2309):Ab = ( L x W ) Base Area of Structure P = 2(L+W) Perimeter of Structure i) For Base Area (Ab) < 100m2 a) Number of Down Conductors Required
ii)
= =
223.67 Meter2 65.22 Meter
= For Ab < 100m2
=
1 Nos
= 1+(Ab-100)/300
=
1 Nos
For Base Area (Ab) > 100m2 b) Based on Base Area of Structure:Number of Down Conductors Required c) Based on Parimeter of Structure:Number of Down Conductors Required
REVISION DETAILS
= P/30 = 2 Nos. Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309) = Hence, Required Number of Down Conductors 1 Nos.
Rev.
Date
Drg/Doc. No.
Remarks
Prepared
Reviewed
Approved
R0
30.06.2009
3VYN855200
First Submission
RK
PS
PAS
1x250MW SURATGARH S.T.P.S. Unit-6 (Stage-IV) RRVUNL DCPL, New Delhi Indure, New Delhi
PROJECT : CLIENT :CONSULTANT :BOP CONTRACTOR :-
LIGHTNING PROTECTION CALCULATION ( REFERENCE : IS 2309 ) FOR Description / Parameter
PRIMARY CRUSHER HOUSE
Symbol / Formulae / References
Value
Unit
A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION i) Input Data :a) Dimensions of Building / Structure L ( Refer the Relevant Layout W Drawings of the Building / H Structure )
Length of the Building Width of the Building Height of the Building
b)
Lightning Flash Density (Flashes to Ground /km2/year) Weighting Factor A ( Use of Structure ) Weighting Factor B ( Type of Construction ) Weighting Factor C ( Content of Consequential Effects ) Weighting Factor D ( Degree of Isolation ) Weighting Factor E ( Type of Country )
Probable Number of Strikes to Building / Structure per Year ( Refer Clause 8.1.2 of IS 2309 ) Overall Multiplying Factor Overall Risk Factor Calculated
N Ng A B C D E
( Refer Fig. 1 of IS 2309 ) = (Refer Clause 8.1.2 of IS 2309) = ( Refer Table 1A of IS 2309 ) = ( Refer Table 1B of IS 2309 ) = ( Refer Table 1C of IS 2309 ) = ( Refer Table 1D of IS 2309 ) = ( Refer Table 1E of IS 2309 ) =
Ac
=
(L x W) + 2 (L x H) + 2(W x H) + 3.14 H2
=
P
= Ac x Ng x 10-6 times/year
=
27 No. of Days / Year 5 Nos./km2/year 1 0.2 1 0.4 0.3
Rf-C
= AxBxCxDxE = Overall Multiplying Factor = = xP ie
3904.39 Meter2 0.019522 Times per year 0.024000 0.000469 4.6853E-04
Maximum Acceptable Overall Risk Factor:Maximum Acceptable Overall Risk Factor
iv)
m m m
Calculations :Collection Area ( Refer Clause 8.1.2 of IS 2309 )
iii)
23.00 21.50 21.70
Lightning Flash Density & Weighing Factors Number of Thunderstorm Days / Year
ii)
= = =
Rf-A
( Refer Clauses 8.1.3 & 8.1.6 of IS 2309 )
=
0.000001
ie
1.000E-06
Result / Conclusion :Since Overall Risk Factor Calculated Maximum Acceptable Overall Risk Factor > Hence, Lightning Protection is Required.
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS Calculations (As per Clause 12.2.3 of IS-2309):Ab = ( L x W ) Base Area of Structure P = 2(L+W) Perimeter of Structure i) For Base Area (Ab) < 100m2 a) Number of Down Conductors Required
ii)
For Base Area (Ab) > 100m
= =
494.50 Meter2 89 Meter
= For Ab < 100m2
=
1 Nos
= 1+(Ab-100)/300
=
2 Nos
2
b) Based on Base Area of Structure:Number of Down Conductors Required c) Based on Parimeter of Structure:Number of Down Conductors Required
REVISION DETAILS
= P/30 = 3 Nos. Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309) = Hence, Required Number of Down Conductors 2 Nos.
Rev.
Date
Drg/Doc. No.
Remarks
Prepared
Reviewed
Approved
R0
30.06.2009
3VYN855200
First Submission
RK
PS
PAS
1x250MW SURATGARH S.T.P.S. Unit-6 (Stage-IV) RRVUNL DCPL, New Delhi Indure, New Delhi
PROJECT : CLIENT :CONSULTANT :BOP CONTRACTOR :-
LIGHTNING PROTECTION CALCULATION ( REFERENCE : IS 2309 ) FOR Description / Parameter
SECONDARY CRUSHER HOUSE
Symbol / Formulae / References
Value
Unit
A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION i) Input Data :a) Dimensions of Building / Structure L ( Refer the Relevant Layout W Drawings of the Building / H Structure )
Length of the Building Width of the Building Height of the Building
b)
Lightning Flash Density (Flashes to Ground /km2/year) Weighting Factor A ( Use of Structure ) Weighting Factor B ( Type of Construction ) Weighting Factor C ( Content of Consequential Effects ) Weighting Factor D ( Degree of Isolation ) Weighting Factor E ( Type of Country )
Probable Number of Strikes to Building / Structure per Year ( Refer Clause 8.1.2 of IS 2309 ) Overall Multiplying Factor Overall Risk Factor Calculated
N Ng A B C D E
( Refer Fig. 1 of IS 2309 ) = (Refer Clause 8.1.2 of IS 2309) = ( Refer Table 1A of IS 2309 ) = ( Refer Table 1B of IS 2309 ) = ( Refer Table 1C of IS 2309 ) = ( Refer Table 1D of IS 2309 ) = ( Refer Table 1E of IS 2309 ) =
Ac
=
(L x W) + 2 (L x H) + 2(W x H) + 3.14 H2
=
P
= Ac x Ng x 10-6 times/year
=
27 No. of Days / Year 5 Nos./km2/year 1 0.2 1 0.4 0.3
Rf-C
= AxBxCxDxE = Overall Multiplying Factor = = xP ie
5181.47 Meter2 0.025907 Times per year 0.024000 0.000622 6.2178E-04
Maximum Acceptable Overall Risk Factor:Maximum Acceptable Overall Risk Factor
iv)
m m m
Calculations :Collection Area ( Refer Clause 8.1.2 of IS 2309 )
iii)
38.00 17.40 24.20
Lightning Flash Density & Weighing Factors Number of Thunderstorm Days / Year
ii)
= = =
Rf-A
( Refer Clauses 8.1.3 & 8.1.6 of IS 2309 )
=
0.000001
ie
1.000E-06
Result / Conclusion :Since Overall Risk Factor Calculated Maximum Acceptable Overall Risk Factor > Hence, Lightning Protection is Required.
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS Calculations (As per Clause 12.2.3 of IS-2309):Ab = ( L x W ) Base Area of Structure P = 2(L+W) Perimeter of Structure i) For Base Area (Ab) < 100m2 a) Number of Down Conductors Required
ii)
= =
661.20 Meter2 110.8 Meter
= For Ab < 100m2
=
1 Nos
= 1+(Ab-100)/300
=
3 Nos
For Base Area (Ab) > 100m2 b) Based on Base Area of Structure:Number of Down Conductors Required c) Based on Parimeter of Structure:Number of Down Conductors Required
REVISION DETAILS
= P/30 = 4 Nos. Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309) = Hence, Required Number of Down Conductors 3 Nos.
Rev.
Date
Drg/Doc. No.
Remarks
Prepared
Reviewed
Approved
R0
30.06.2009
3VYN855200
First Submission
RK
PS
PAS
1x250MW SURATGARH S.T.P.S. Unit-6 (Stage-IV) RRVUNL DCPL, New Delhi Indure, New Delhi
PROJECT : CLIENT :CONSULTANT :BOP CONTRACTOR :-
LIGHTNING PROTECTION CALCULATION ( REFERENCE : IS 2309 ) FOR WAGON TIPPLER AREA Description / Parameter
Symbol / Formulae / References
Value
Unit
A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION i) Input Data :a) Dimensions of Building / Structure L ( Refer the Relevant Layout W Drawings of the Building / H Structure )
Length of the Building Width of the Building Height of the Building
b)
Lightning Flash Density (Flashes to Ground /km2/year) Weighting Factor A ( Use of Structure ) Weighting Factor B ( Type of Construction ) Weighting Factor C ( Content of Consequential Effects ) Weighting Factor D ( Degree of Isolation ) Weighting Factor E ( Type of Country )
Probable Number of Strikes to Building / Structure per Year ( Refer Clause 8.1.2 of IS 2309 ) Overall Multiplying Factor Overall Risk Factor Calculated
N Ng A B C D E
( Refer Fig. 1 of IS 2309 ) = (Refer Clause 8.1.2 of IS 2309) = ( Refer Table 1A of IS 2309 ) = ( Refer Table 1B of IS 2309 ) = ( Refer Table 1C of IS 2309 ) = ( Refer Table 1D of IS 2309 ) = ( Refer Table 1E of IS 2309 ) =
Ac
=
(L x W) + 2 (L x H) + 2(W x H) + 3.14 H2
=
P
= Ac x Ng x 10-6 times/year
=
27 No. of Days / Year 5 Nos./km2/year 1 0.8 1 0.4 0.3
Rf-C
= AxBxCxDxE = Overall Multiplying Factor = = xP ie
4113.54 Meter2 0.020568 Times per year 0.096000 0.001974 1.9745E-03
Maximum Acceptable Overall Risk Factor:Maximum Acceptable Overall Risk Factor
iv)
m m m
Calculations :Collection Area ( Refer Clause 8.1.2 of IS 2309 )
iii)
41.00 18.00 19.00
Lightning Flash Density & Weighing Factors Number of Thunderstorm Days / Year
ii)
= = =
Rf-A
( Refer Clauses 8.1.3 & 8.1.6 of IS 2309 )
=
0.000001
ie
1.000E-06
Result / Conclusion :Since Overall Risk Factor Calculated Maximum Acceptable Overall Risk Factor > Hence, Lightning Protection is Required.
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS Calculations (As per Clause 12.2.3 of IS-2309):Ab = ( L x W ) Base Area of Structure P = 2(L+W) Perimeter of Structure i) For Base Area (Ab) < 100m2 a) Number of Down Conductors Required
ii)
For Base Area (Ab) > 100m
= =
738.00 Meter2 118 Meter
= For Ab < 100m2
=
1 Nos
= 1+(Ab-100)/300
=
3 Nos
2
b) Based on Base Area of Structure:Number of Down Conductors Required c) Based on Parimeter of Structure:Number of Down Conductors Required
REVISION DETAILS
= P/30 = 4 Nos. Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309) = Hence, Required Number of Down Conductors 3 Nos.
Rev.
Date
Drg/Doc. No.
Remarks
Prepared
Reviewed
Approved
R0
30.06.2009
3VYN855200
First Submission
RK
PS
PAS
1x250MW SURATGARH S.T.P.S. Unit-6 (Stage-IV) RRVUNL DCPL, New Delhi Indure, New Delhi
PROJECT : CLIENT :CONSULTANT :BOP CONTRACTOR :-
LIGHTNING PROTECTION CALCULATION ( REFERENCE : IS 2309 ) FOR DRIVE HOUSE Description / Parameter
Symbol / Formulae / References
Value
Unit
A) CHECK FOR NEED OF PROVIDING LIGHTNING PROTECTION i) Input Data :a) Dimensions of Building / Structure L ( Refer the Relevant Layout W Drawings of the Building / H Structure )
Length of the Building Width of the Building Height of the Building
b)
Lightning Flash Density (Flashes to Ground /km2/year) Weighting Factor A ( Use of Structure ) Weighting Factor B ( Type of Construction ) Weighting Factor C ( Content of Consequential Effects ) Weighting Factor D ( Degree of Isolation ) Weighting Factor E ( Type of Country )
Probable Number of Strikes to Building / Structure per Year ( Refer Clause 8.1.2 of IS 2309 ) Overall Multiplying Factor Overall Risk Factor Calculated
N Ng A B C D E
( Refer Fig. 1 of IS 2309 ) = (Refer Clause 8.1.2 of IS 2309) = ( Refer Table 1A of IS 2309 ) = ( Refer Table 1B of IS 2309 ) = ( Refer Table 1C of IS 2309 ) = ( Refer Table 1D of IS 2309 ) = ( Refer Table 1E of IS 2309 ) =
Ac
=
(L x W) + 2 (L x H) + 2(W x H) + 3.14 H2
=
P
= Ac x Ng x 10-6 times/year
=
27 No. of Days / Year 5 Nos./km2/year 1 0.2 1 0.4 0.3
Rf-C
= AxBxCxDxE = Overall Multiplying Factor = = xP ie
450.25 Meter2 0.002251 Times per year 0.024000 0.000054 5.4030E-05
Maximum Acceptable Overall Risk Factor:Maximum Acceptable Overall Risk Factor
iv)
m m m
Calculations :Collection Area ( Refer Clause 8.1.2 of IS 2309 )
iii)
15.50 8.50 5.00
Lightning Flash Density & Weighing Factors Number of Thunderstorm Days / Year
ii)
= = =
Rf-A
( Refer Clauses 8.1.3 & 8.1.6 of IS 2309 )
=
0.000001
ie
1.000E-06
Result / Conclusion :Since Overall Risk Factor Calculated Maximum Acceptable Overall Risk Factor > Hence, Lightning Protection is Required.
B) CHECK FOR ADEQUACY OF NUMBER OF DOWN CONDUCTORS Calculations (As per Clause 12.2.3 of IS-2309):Ab = ( L x W ) Base Area of Structure P = 2(L+W) Perimeter of Structure i) For Base Area (Ab) < 100m2 a) Number of Down Conductors Required
ii)
= =
131.75 Meter2 48 Meter
= For Ab < 100m2
=
1 Nos
= 1+(Ab-100)/300
=
1 Nos
For Base Area (Ab) > 100m2 b) Based on Base Area of Structure:Number of Down Conductors Required c) Based on Parimeter of Structure:Number of Down Conductors Required
REVISION DETAILS
= P/30 = 2 Nos. Note:- The Number of Down Conductor should be at least the smaller between b) & c) (as per clause 12.2.3b of IS-2309) = Hence, Required Number of Down Conductors 1 Nos.
Rev.
Date
Drg/Doc. No.
Remarks
Prepared
Reviewed
Approved
R0
30.06.2009
3VYN855200
First Submission
RK
PS
PAS
View more...
Comments