DETAILED DETAILED STRUCTURA STRUCTURAL L CALCULA CALCULATIONS TIONS Data
Conversion factors 1 N/sqmm = 1 pound = Length W idth height Earth cover over top slab Soil density Angle of internal friction for soil Coeff of earth pressure at rest = 1- sin Density of water Density of concrete Live load on roof f c', specified compressive strength of concrete G30 cube strength
p si N
145 4.45
m m m m kN/cum degrees
3.00 2.00 3.50 0.20 19 30 As per soil report 0.50 10 25 5 25 3625
f
kN/cum kN/cum kN/sqm N/sqmm p si
(equivalent to G25 cylinder strength)
Yield strength of rebar Allowable bearing pressure ( net )
p si N/sqmm kN/sqm
60000 414 100
Allowable bearing pressure ( gross) at founding level = net bearing pr + gd kN/sqm Strength reduction factor for flexure & tension f Strength reduction factor for shear f
168
0.90 As per cl. 9.3.2.1 9.3.2.1 0.85 As per cl. 9.3.2.3 9.3.2.3
Durability coefficient for flexure as per ACI 350 for water retaining structures for limiting crackwidths
1.30 Reinforcement required to be multiplied by this factor as per cl.9.2.8.1
Durability coefficient for direct tension as per ACI 350 for water retaining structures for limiting crackwidths
1.65 Reinforcement required to be multiplied by this factor asper cl.9.2.8.2
E:\DSA_1\PEN_DRIVE_G\CONC_STRUCT\WATER_TANK\water tank_Design of Underground _R3.xls
Sheet 10
Tabouk Power Plant # 2 Expansion Project - Unit 7 & 8
7.2.0
Assumed thickness Top slab thickness Long wall thickness Short wall thickness Base slab Base slab projection
7.3.0
FUELOIL STORAGE AREA - U/G DRAIN TANK TBKII-BOP-C-1962 Rev-A
m m m m m
0.15 0.25 0.25 0.25 0.25
Weight calculations Nos Top slab Long wall Short wall Base slab Soil cover above roof slab Soil over base projection
1 2 2 1 1 1
Length m 3.50 3.25 2.25 4.00 3.50 13.00 (perimeter)
Total weight ( DL ) water weight Live load on roof
3.00 3.50
Breadth thickness m m 2.50 0.15 3.50 0.25 3.50 0.25 3.00 0.25 2.50 0.20 3.85 0.25
Density kN/cum 25 25 25 25 19 19
Weight kN 32.81 142.19 98.44 75.00 33.25 237.74
10 5
619.43 210.00 43.75
(height)
2.00 2.50
3.50
(kN/sqmm)
7.4.0
Total live load (water+roof live load ) Check for bearing capacity Total load Base area Bearing press due to DL Bearing press due to LL Total Bearing pressure
253.75
<
E:\DSA_1\PEN_DRIVE_G\CONC_STRUCT\WATER_TANK\water tank_Design of Underground _R3.xls
873.18 12.00 51.62 21.15 72.76 168
kN sqm kN/sqm kN/sqm kN/sqm OK
Sheet 11
Tabouk Power Plant # 2 Expansion Project - Unit 7 & 8
FUELOIL STORAGE AREA - U/G DRAIN TANK TBKII-BOP-C-1962 Rev-A
7.5.0
Analysis & Design
7.5.1
Top slab Dead load (DL) Self weight of slab kN/sqm 3.75 Soil weight kN/sqm 3.80 Total DL kN/sqm 7.55 Live Load(LL) kN/sqm 5.00 Load factor -DL 1.40 Load factor- LL 1.70 Factored total Load kN/sqm 19.07 Simply supported condition- coefficients from table 50 of Reynold's handbook Short span - lx Long span- ly Span ratio Remarks span support span support (ly/lx) Effective span (clear+ wall thickness) m 2.25 3.25 1.44 Shear coeff 0.50 0.50 Max at the centre of span (approx) Moment coeff ax3, ay3 0.548 0.126 Shear = Coeff x wlx kN/m 21.45 21.45 Moment Mu =Coeff *wl^2/8 kNm/m 6.62 3.18 generally Partia fixity factors at span 1.00 0.25 Design Mu considering partial fixity kNm/m 6.62 6.62 3.18 3.18 Partia fixity factors at support 1 0.75 tension Tu kN/m 24.26 24.26 23.36 23.36 Shear from wall due water pressure ( from 7.5.2, b) & 7.5.3, b) ) Overall depth mm 150 150 150 150 clear cover mm 50 50 effective depth d mm 92 94 78 80 64.95 55.07 Safe as actual stress less than Allowable Shear = f x Vc Vc kN/m allowable =2*fc'^0.5*b*d as per cl.11.3.1.1 Ast from solving fMu = f [Ast x fy x d (1-0.59 x r x (fy/fc'))], sqmm/m 270 264 151 147 Solving qua equation. Ast for tension on each face = sqmm/m 54 54 52 52 1.65*Tu/( f f y)/ 2 Total Ast sqmm/m 323 317 203 199 Min Ast per face(0.15% of gross area ) sqmm/m 225 225 225 225 as per table 7.12.2.1 of ACI 350
E:\DSA_1\PEN_DRIVE_G\CONC_STRUCT\WATER_TANK\water tank_Design of Underground _R3.xls
Sheet 12
Tabouk Power Plant # 2 Expansion Project - Unit 7 & 8
7.5.2 a)
FUELOIL STORAGE AREA - U/G DRAIN TANK TBKII-BOP-C-1962 Rev-A
Long wall w ear ou s e+surc arge an no water inside earth pressure at top kN/sqm 3.32 earth pressure at bottom kN/sqm 38.94 Earth pressure due to surcharge load of 20 kN/sqm (UDL) kN/sqm 2.50 The earth pressure due to soil weight is split up into two components-udl and triangular udl kN/sqm 3.32 triangular kN/sqm 35.61 inside Load Factor for Earth pressure 1.70 As per ACI 350 Load factor for surchage load 1.70 Factored loads udl (soil+surcharge) kN/sqm 9.90 triangular kN/sqm 60.54
9.90 60.54
Slab fixed at sides& bottom, top hinged Walls analysed using Moody's charts- fig 10 for udl and fig 13 for triangular vertical span - b horizontal span- 2a Span ratio Remarks span support span support (a/b) Effective span (clear+ wall thickness) 3.70 3.25 0.4392 Coefficients corresponding to a/b=1.0 are taken udl Shear coeff - top 0.4020 Shear coeff - bottom 0.5980 shear coeff -sides 0.5491 Moment coeff 0.0617 0.1093 0.0227 0.0664 Shear - top kN/m 14.72 Shear - bottom kN/m 21.90 Shear - sides kN/m 20.11 Moment Mu kNm/m 8.36 14.81 3.08 9.00 tension kN/m No tension under this condition triangular load Shear coeff - top 0.1102 Shear coeff - bottom 0.3988 shear coeff -sides 0.2583 Moment coeff 0.0259 0.0593 0.0098 0.0289 Shear - top kN/m 24.68 Shear - bottom kN/m 89.33 Shear - sides kN/m 57.86 Moment Mu kNm/m 21.47 49.15 8.12 23.95 tension kN/m No tension under this condition Total Shear - top kN/m 39.41 Shear - bottom kN/m 111.23
E:\DSA_1\PEN_DRIVE_G\CONC_STRUCT\WATER_TANK\water tank_Design of Underground _R3.xls
Sheet 13
Tabouk Power Plant # 2 Expansion Project - Unit 7 & 8
Shear - sides Moment Mu Redistributed moment Mu Design Moment Mu (higher of the two) tension Tu Overall depth clear cover effective depth Allowable Shear = f x Vc Vc =2*fc'^0.5*b*d as per cl.11.3.1.1 Ast from solving fMu = f [Ast x fy x d (1-0.59 x r x (fy/fc'))], Ast for tension on each face = 1.65*Tu/( f f y)/ 2
b)
FUELOIL STORAGE AREA - U/G DRAIN TANK TBKII-BOP-C-1962 Rev-A
kN/m kNm/m kNm/m kNm/m kN/m mm mm mm kN/m
29.83 49.39 49.39
63.96 44.39 63.96
11.20
250
250
94
90 66.36
250 50 74
11.20
77.97 32.95 32.96 32.96
No tension under this condition 250 50 74 52.24
sqmm/m sqmm/m
2635 0
4608 0
598 0
2352 0
Total Ast sqmm/m Min Ast per face(0.15% of gross area) sqmm/m
2635 375
4608 375
598 375
2352 375
with no earth outside and wate r inside water pressure at bottom Load Factor Factored loads
35.00 kN/sqm 1.70 59.50 kN/sqm
Slab fixed at sides& bottom, top hinged Walls analysed using Moody's charts- fig 13 for triangular load
Effective span (clear+ wall thickness) Shear coeff - top Shear coeff - bottom shear coeff -sides Moment coeff Shear - top Shear - bottom Shear - sides Moment Mu Resistributed Moment Mu Design Moment Mu (higher of the two)
kN/m kN/m kN/m kNm/m kNm/m kNm/m
Refer Moment distribution in Annex A
Safe as actual stress less than allowable
Solving qua.equation
as per table 7.12.2.1 of ACI 350
As per ACI 350
inside
59.50
vertical span - b horizontal span- 2a Span ratio Remarks span support span support (a/b) 3.70 3.25 0.44 Coefficients corresponding to a/b=1.0 are 0.1102 taken 0.3988 0.2583 0.0259 0.0593 0.0098 0.0289 24.26 87.80 56.86 21.10 48.30 7.98 23.54 53.21 16.19 24.60 Refer Moment distribution in Annex A 53.21 16.19 7.98 24.60
E:\DSA_1\PEN_DRIVE_G\CONC_STRUCT\WATER_TANK\water tank_Design of Underground _R3.xls
Sheet 14
Tabouk Power Plant # 2 Expansion Project - Unit 7 & 8
Tension Overall depth clear cover effective depth Allowable Shear = f x Vc Vc =2*fc'^0.5*b*d as per cl.11.3.1.1 Ast from solving fMu = f [Ast x fy x d (1-0.59 x r x (fy/fc'))], Ast for tension on each face = 1.65*Tu/( f f y)/ 2
FUELOIL STORAGE AREA - U/G DRAIN TANK TBKII-BOP-C-1962 Rev-A
kN/m mm mm mm
250
250
94
90
kN/m
57.59
57.59
250 50 74
250 50 74
66.36
Shear from short wall due water pressure (from 7.5.3, b) )
52.24
sqmm/m
2990 0
710 0
416 128
1512 128
Total Ast sqmm/m Min Ast per face(0.15% of gross area) sqmm/m
2990 375
710 375
543 375
1640 375
7.5.3
Short wall
a)
with earth outside and no water inside earth pressure at top(mid depth of top slab) kN/sqm 2.61 inside earth pressure at bottom(mid-depth of bottom slab) kN/sqm 37.75 Earth pressure due to surcharge load of 20 kN/sqm (UDL) kN/sqm 2.50 The earth pressure due to soil weight is split up into two components-udl and triangular udl kN/sqm 2.61 triangular kN/sqm 35.14 Load Factor for earth pressure 1.70 Load factor for surchage load 1.70 Factored loads udl (soil+surcharge) kN/sqm 8.69 triangular kN/sqm 59.73
Solving qua.equation
as per table 7.12.2.1 of ACI 350
8.69 59.73
Slab fixed at sides& bottom, top hinged Walls analysed using Moody's charts- fig 10 for udl and fig 13 for triangular
E:\DSA_1\PEN_DRIVE_G\CONC_STRUCT\WATER_TANK\water tank_Design of Underground _R3.xls
Sheet 15
Tabouk Power Plant # 2 Expansion Project - Unit 7 & 8
Effective span (clear+ wall thickness) udl Shear coeff - top Shear coeff - bottom shear coeff -sides Moment coeff Shear - top (kN/m) Shear - bottom (kN/m) Shear - sides (kN/m) Moment Mu (kNm/m) tension triangular load Shear coeff - top Shear coeff - bottom shear coeff -sides Moment coeff Shear - top Shear - bottom Shear - sides Moment Mu (kNm/m) tension Total Load Shear - top Shear - bottom Shear - sides Moment Mu (kNm/m) Redistributed Moment Mu Design Moment Mu (higher of the two) tension Overall depth clear cover effective depth Allowable Shear = f x Vc Vc =2*fc'^0.5*b*d as per cl.11.3.1.1 Ast from solving fMu = f [Ast x fy x d (1-0.59 x r x (fy/fc'))], Ast for tension on each face = 1.65*Tu/( f f y)/ 2 Total Ast Min Ast per face(0.15% of gross area)
FUELOIL STORAGE AREA - U/G DRAIN TANK TBKII-BOP-C-1962 Rev-A
kN/m kN/m kN/m kNm/m kN/m
vertical span - b horizontal span- 2a Span ratio Remarks span support span support (a/b) 3.70 2.25 0.30 Coefficients corresponding to a/b=0.75 are taken 0.3874 0.5837 0.5465 0.0473 0.0898 0.0274 0.0695 12.45 18.76 17.57 5.63 10.68 3.26 8.27 No tension under this condition 0.1061 0.3828 0.0198
0.0505 23.45 84.60
0.0119
0.2616 0.0302
16.19
41.30
9.73
57.82 24.70
kN/m kN/m kN/m kNm/m kN/m kN/m kN/m kN/m kNm/m kNm/m kNm/m kN/m mm mm mm
No tension under this condition 35.90 103.37 21.82 43.69 43.69
51.98 30.11 51.98
12.99
75.38 32.96
12.99
32.96
250
250
94
92 66.36
250 50 78
250 50 78 55.07
Refer Moment distribution in Annex A No tension under this condition
Safe as actual stress less than allowable
kN/m sqmm/m sqmm/m
2191 0
3035 0
661 0
2081 0
sqmm/m sqmm/m
2191 375
3035 375
661 375
2081 375
E:\DSA_1\PEN_DRIVE_G\CONC_STRUCT\WATER_TANK\water tank_Design of Underground _R3.xls
Solving qua.equation
as per table 7.12.2.1 of ACI 350
Sheet 16
Tabouk Power Plant # 2 Expansion Project - Unit 7 & 8
b)
FUELOIL STORAGE AREA - U/G DRAIN TANK TBKII-BOP-C-1962 Rev-A
with no earth outside and wate r inside water pressure at bottom Load Factor Factored loads
35.00 kN/sqm 1.70 59.50 kN/sqm
inside
Slab fixed at sides& bottom, top hinged Walls analysed using Moody's charts- fig 13 for triangular load 59.50
Effective span (clear+ wall thickness) Shear coeff - top Shear coeff - bottom shear coeff -sides Moment coeff Shear - top Shear - bottom Shear - sides Moment Mu (kNm/m) Resistributed Moment Mu Design moment tension Overall depth clear cover effective depth Allowable Shear = f x Vc Vc =2*fc'^0.5*b*d as per cl.11.3.1.1 Ast from solving fMu = f [Ast x fy x d (1-0.59 x r x (fy/fc'))], Ast for tension on each face = 1.65*Tu/( f f y)/ 2
kN/m kN/m kN/m kNm/m kNm/m kNm/m kN/m
vertical span - b horizontal span- 2a Span ratio Remarks span support span support (a/b) 3.70 2.25 0.30 Coefficients corresponding to a/b=0.75 0.1061 are taken 0.3828 0.2616 0.0198 0.0505 0.0119 0.0302 23.36 84.27 57.59 16.13 41.14 9.69 24.60 49.58 7.69 Refer Moment distribution in Annex A 49.58 7.69 9.69 24.60 56.86 56.86 Shear from long wall due water pressure (from 7.5.2, b) )
mm mm mm
250
250
94
92
kN/m
250 50 78
66.36
250 50 78 55.07
sqmm/m sqmm/m
2650 0
315 0
482 126
1391 126
Total Ast sqmm/m Min Ast per face(0.15% of gross area) sqmm/m
2650 375
315 375
607 375
1516 375
E:\DSA_1\PEN_DRIVE_G\CONC_STRUCT\WATER_TANK\water tank_Design of Underground _R3.xls
Solving qua.equation
as per table 7.12.2.1 of ACI 350
Sheet 17
Tabouk Power Plant # 2 Expansion Project - Unit 7 & 8
7.5.4 a)
FUELOIL STORAGE AREA - U/G DRAIN TANK TBKII-BOP-C-1962 Rev-A
Bottom slab with earth outside and no water inside Dead load (DL) Self weight of slab Load factor Factored DL due to self weight Soil pressure due to Dead loads Soil pressure due to live load on roof Factored Bearing pressure Net upward factored bearing pressure ( Soil pressure - slab self weight)
Base slab support condition - All four sides fixed based onfig 34 of Moody's chart Short span - a Long span- b Span ratio Remarks span support span support (a/b) Effective span (clear+ wall thickness) 2.25 3.25 0.69 Coefficients corresponding to a/b=0.625 Shear coeff 0.5143 0.4648 are taken Moment coeff 0.0376 0.0765 0.0159 0.0547 Shear kN/m 80.67 72.91 Moment Mu kNm/m 13.27 27.00 5.61 19.31 Redistributed moment Mu kNm/m -4.12 44.39 -5.19 30.11 tension Tu kN/m 0.00 0.00 No tension under this condition Overall depth mm 250 250 250 250 clear cover effective depth d Allowable Shear = f x Vc Vc =2*fc'^0.5*b*d as per cl.11.3.1.1 Ast from solving fMu = f [Ast x fy x d (1-0.59 x r x (fy/fc'))], Ast for tension on each face = 1.65*Tu/( f f y)/ 2
mm mm
50 192
kN/m
75 167
178
135.55
151 125.67
sqmm/m sqmm/m
-78 0
1030 0
-106 0
764 0
Total Ast sqmm/m Min Ast per face(0.15% of gross area) sqmm/m
-78 375
1030 375
-106 375
764 375
E:\DSA_1\PEN_DRIVE_G\CONC_STRUCT\WATER_TANK\water tank_Design of Underground _R3.xls
Safe as actual stress less than allowable Solving qua equation
as per table 7.12.2.1 of ACI 350
Sheet 18
Tabouk Power Plant # 2 Expansion Project - Unit 7 & 8
FUELOIL STORAGE AREA - U/G DRAIN TANK TBKII-BOP-C-1962 Rev-A
with no earth outside and water inside Dead load (DL) Self weight of slab Load factor Factored DL due to self weight Soil pressure due to Dead loads (without soil load ) Soil pressure due to live loads
b)
kN/sqm
6.25 1.40 8.75
kN/sqm kN/sqm kN/sqm
29.04 0.00 Water load not considered as it cancels each other while calculating the net upward pressure
Base slab support condition - All four sides fixed based on fig 34 of Moody's chart Short span - a Long span- b Span ratio Remarks span support span support (a/b) Effective span (clear+ wall thickness) 2.25 3.25 0.69 Coefficients corresponding to a/b=0.692 Shear coeff 0.5143 0.4648 are taken Moment coeff 0.0376 0.0765 0.0159 0.0547 Shear kN/m 36.92 33.36 Moment Mu kNm/m 6.07 12.35 2.57 8.83 Redistributed moment kNm/m 34.62 -16.19 19.09 -7.69 Minus sign indicates tension on inner face Shear from wall due water pressure (from tension Tu kN/m 87.80 87.80 84.27 84.27 7.5.2, b) & 7.5.3, b)) Overall depth clear cover effective depth d Allowable Shear = f x Vc =2*fc'^0.5*b*d as per cl.11.3.1.1
mm mm mm
250 50 192
250 75 167
250
250
178
151
Vc kN/m fMn
M b d a b c r
M(kN-m) b(in) d(in) a b c r
As(req.)
As(req.) in sq in.
= = = = = = = = =
135.55 125.67 This portion should be hidden = f [ As x fy x d (1-0.59 x p x (fy/ f' c))] Short span-top Long Span Top Bottom Top Bottom 34.62 16.19 19.09 -7.69 39.37 39.37 39.37 39.37 7.56 6.57 7.01 5.94 9.765517 9.765517 9.76552 9.76552 -1 -1 -1 -1 0.0034 0.0021 0.002 -0.001 0.0035 0.0022 0.0022 -0.0012 rxbxd rxbxd rxbxd rxbxd
E:\DSA_1\PEN_DRIVE_G\CONC_STRUCT\WATER_TANK\water tank_Design of Underground _R3.xls
1.054
0.559
0.619
Safe as actual stress less than allowable
-0.284
Sheet 19
Tabouk Power Plant # 2 Expansion Project - Unit 7 & 8
As(req.)
FUELOIL STORAGE AREA - U/G DRAIN TANK TBKII-BOP-C-1962 Rev-A
As(req.) mm2 = Ast from solving fMu = f [Ast x fy x d (1-0.59 x r x (fy/fc'))], sqmm/m Ast for tension on each face = sqmm/m 1.65*Tu/( f f y)/ 2
680
361
399
-183
680 194
361 194
399 187
-183 187
Total Ast sqmm/m Min Ast per face(0.15% of gross area) sqmm/m
874 375
555 375
586 375
187 375