Square D Wiring Diagram Book
Short Description
Download Square D Wiring Diagram Book...
Description
File 0140
L1
L2
GND
L3
L1
OFF
F U 1
F U 2 460 V
H1
H3
230 V H2
H1
H4
H3
H2
A1 B1 15 B2 B2 STOP B3STOP STOP 1B1 15
Supply voltage
ON
H4
START 2
M
OL
3
16 18 B3 A2
16 18
Electrostatically Shielded Transformer
F U 5
Power On
F U 6
X1A
F U 4
H
M
L
21
31 43
53
14
22
32 44
54
AC 1
Status (N.O. or N.C.)
2
5
6
8
9
10
12 14 (+)
13 (–)
A1/+ 15 25 Z1 Z2
NONHAZARDOUS LOCATIONS
FIBER OPTIC TRANSCEIVER
Supply voltage
FIBER OPTIC PUSH BUTTON, SELECTOR SWITCH, LIMIT SWITCH, ETC.
A1 15 B2 B1 B3
15
H
16 18 B3 A2
16 18
CLASS 9005 TYPE FT
B1 B2
16 18 26 28 A2/–
L M
Vs
2 Levels FIBER OPTIC CABLE ELECTRICAL CONNECTIONS
1 3 5 L1 L2 L3
A1
BOUNDARY SEAL TO BE IN ACCORDANCE WITH ARTICLE 501-5 OF THE NATIONAL ELECTRICAL CODE
L2
A1 A2
A2 L3
3 L1 T1 T2 T3
L2
1CT
M L1
CIRCUIT BREAKER OR DISCONNECT SWITCH
FIBER OPTIC CABLE
L2
4
Optional
HAZARDOUS LOCATIONS CLASS I GROUPS A, B, C & D CLASS II GROUPS E, F & G CLASS III
X2 Green X1
M
2 Levels
13
X3
Orange LOAD
Location
X2A
22
14
R F U 3
L1
21
13
START
Optional Connection X1 115 V X2
AC
L2
START
T1
T2
M
MOTOR
3CT
M
L3
T3
SOLID STATE OVERLOAD RELAY
1 TO 120 V SEPARATE CONTROL
MOTOR
STOP
2
T1
T1 T2 T3 2 4 6
Wiring Diagram Book
T2
START OT*
T3
M
M
* OT is a switch that opens when an overtemperature condition exists (Type MFO and MGO only)
TRADEMARKS
QWIK-STOP® and ALHPA-PAK® are registered trademarks of Square D. NEC® is a registered trademark of the National Fire Protection Association.
COPYRIGHT NOTICE
© 1993 Square D. All rights reserved. This document may not be copied in whole or in part, or transferred to any other media, without the written permission of Square D.
PLEASE NOTE:
Electrical equipment should be serviced only by qualified electrical maintenance personnel, and this document should not be viewed as sufficient instruction for those who are not otherwise qualified to operate, service or maintain the equipment discussed. Although reasonable care has been taken to provide accurate and authoritative information in this document, no responsibility is assumed by Square D for any consequences arising out of the use of this material.
Table of Contents
Standard Elementary Diagram Symbols ..................... 1-3 NEMA and IEC Markings and Schematic Diagrams ...... 4 Control and Power Connection Table 4 Terminology ...................................................................... 5 Examples of Control Circuits .......................................... 6 2-Wire Control 6 3-Wire Control 6-9 Shunting Thermal Units During Starting Period 10 Overcurrent Protection for 3-Wire Control Circuits 11 AC Manual Starters and Manual Motor Starting Switches ........................................................... 12 Class 2510 12 Class 2511 and 2512 13 2-Speed AC Manual Starters and IEC Motor Protectors...................................................... 14 Class 2512 and 2520 14 GV1/GV3 14 Drum Switches................................................................ 15 Class 2601 15 DC Starters, Constant and Adjustable Speed.............. 16 Class 7135 and 7136 16 Reversing DC Starters, Constant and Adjustable Speed ........................................................... 17 Class 7145 and 7146 17 Mechanically Latched Contactors ................................ 18 Class 8196 18 Medium Voltage Motor Controllers.......................... 18-25 Class 8198 18-25 Solid State Protective Relays ................................... 26-27 Class 8430 26-27 General Purpose Relays ................................................ 28 Class 8501 28 NEMA Control Relays..................................................... 29 Class 8501 and 9999 29 General Purpose Relays ................................................ 30 Class 8501 30
Sensing Relays............................................................... 30 RM2 LA1/LG1 30 IEC Relays.................................................................. 31-32 IEC D-Line Control Relays 31 Class 8501 32 Type P Contactors..................................................... 33-35 Class 8502 33-35 Class 8702 35 Type T Overload Relays............................................ 33-35 Class 9065 33-35 Type S AC Magnetic Contactors.............................. 36-40 Class 8502 36-40 IEC Contactors .......................................................... 41-42 IEC Contactors and Auxiliary Contact Blocks 41 Input Modules and Reversing Contactors 42 Type S AC Magnetic Starters ................................... 43-50 Class 8536 43-50 8538 and 8539 45,49 1-Phase, Size 00 to 3 43 2-Phase and 3-Phase, Size 00 to 5 44 3-Phase, Size 6 45 3-Phase, Size 7 46 3-Phase Additions and Special Features 47-50 Integral Self-Protected Starters ............................... 51-57 Integral 18 State of Auxiliary Contacts 51-52 Integral 32 and 63 State of Auxiliary Contacts 53-54 Wiring Diagrams 55-57 Type S AC Combination Magnetic Starters ............ 58-59 Class 8538 and 8539 58-59 3-Phase, Size 0-5 58 3-Phase Additions and Special Features 59 Reduced Voltage Controllers ................................... 60-66 Class 8606 Autotransformer Type 60-61 Class 8630 Wye-Delta Type 62-63 Class 8640 2-Step Part-Winding Type 64 Class 8647 Primary-Resistor Type 65 Class 8650 and 8651 Wound-Rotor Type 66 Solid State Reduced Voltage Starters .......................... 67 Class 8660 ALPHA PAK®, Type MD-MG 67 Solid State Reduced Voltage Controllers ............... 68-70 Class 8660 Type MH, MJ, MK and MM 68-70
®
i
Table of Contents
Type S AC Reversing Magnetic Starters71-72 Class 873671-72 2- and 3-Pole71 3- and 4-Pole72 Type S AC 2-Speed Magnetic Starters73-76 Class 881073-76 Special Control Circuits75-76 Multispeed Motor Connections76-77 1- Phase76 3-Phase76-77 Programmable Lighting Controllers78 Class 886578
Pneumatic Timing Relays and Solid State Industrial Timing Relays95-96 Class 905095-96 Timers97 Class 905097 Transformer Disconnects98 Class 907098 Enclosure Selection Guide99 Conductor Ampacity and Conduit Tables100-101 Wire Data102
AC Lighting Contactors79-81 Class 890379-81 Load Connections79 Control Circuit Connections80 Panelboard Type Wiring81
Electrical Formulas103-104
Electronic Motor Brakes81-82 Class 8922 QWIK-STOP®81-82
List of Tables Table 1 Standard Elementary Diagram Symbols 1 Table 2
NEMA and IEC Terminal Markings 4
Table 3
NEMA and IEC Controller Markings and Elementary Diagrams 4
Fiber Optic Transceivers82 Class 900582
Table 4
Control and Power Connections for Across-the-Line Starters, 600 V or less4
Table 5
Motor Lead Connections 64
Photoelectric and Inductive Proximity Switches83 Class 900683
Table 6
Enclosures for Non-Hazardous Locations 99
Table 7
Enclosures for Hazardous Locations 99
Table 8
Conductor Ampacity100
Table 9
Ampacity Correction Factors 101
Table 10
Adjustment Factors 101
Table 11
Ratings for 120/240 V, 3-Wire, Single-Phase Dwelling Services101
Table 12
AWG and Metric Wire Data 102
Table 13
Electrical Formulas for Amperes, Horsepower, Kilowatts and KVA 103
Table 14
Ratings for 3-Phase, Single-Speed, Full-Voltage Magnetic Controllers for Nonplugglng and Nonjogging Duty 103
Table 15
Ratings for 3-Phase, Single-Speed, Full-Voltage Magnetic Controllers for PlugStop, Plug-Reverse or Jogging Duty 104
Table 16
Power Conversions 104
Duplex Motor Controllers82 Class 894182
Photoelectric and Proximity Sensors84-89 XS, XSC, XSF and XSD84 XS and XTA85 SG, ST and XUB86 XUM, XUH, XUG, XUL and XUJ87 XUE, XUR, XUD, XUG and XUE S88 XUV89 Limit Switches and Safety Interlocks90-92 Class 900791 XCK and MS92 Pressure Switches and Transducers93 Class 9012, 9013, 9022 and 902593 Level Sensors and Electric Alternators94 Class 9034 and 903994
®
ii
Standard Elementary Diagram Symbols
The diagram symbols in Table 1 are used by Square D and, where applicable, conform to NEMA (National Electrical Manufacturers Association) standards.
Table 1
Standard Elementary Diagram Symbols SWITCHES
Disconnect
Circuit Interrupter
SELECTORS
Circuit Breakers w/ Thermal OL
Circuit Breakers w/ Magnetic OL
2-Position Selector Switch J
K A1 A2 J
K
A1 A2
Pressure & Vacuum Switches N.O. N.C.
Liquid Level Switches N.O.
Temperature Actuated Switches N.O. N.C.
N.C.
3-Position Selector Switch K L
J
A1 A2 J
Limit Switches N.O.
Speed (Plugging)
N.C.
F
F
Anti-Plug
A1
F
A2
K
L
2-Position Selector Push Button Held Closed
A
Held Open
R Flow Switches N.O. N.C.
R
N.O.
1
2
3
4
Selector Position
Foot Switches
A
N.C.
B
B
Push Button
Contacts 1-2 3-4
Free Depressed Free Depressed = contact closed
PUSH BUTTONS – MOMENTARY CONTACT
N.O.
N.C.
N.O. & N.C. (double circuit)
Mushroom Head
Wobble Stick
PUSH BUTTONS – MAINTAINED CONTACT 2 Single Circuits
Illuminated
1 Double Circuit
R
PILOT LIGHTS Non Push-to-Test
INSTANT OPERATING CONTACTS
Push-to-Test
w/ Blowout N.O. N.C.
w/o Blowout N.O. N.C.
TIMED CONTACTS Contact action retarded after coil is: Energized Deenergized N.O.T.C.
A
N.C.T.O.
N.O.T.O.
N.C.T.C.
G (indicate color by letter)
1
Standard Elementary Diagram Symbols
Table 1
Standard Elementary Diagram Symbols (cont'd) TRANSFORMERS
INDUCTORS Iron Core
Auto
Air Core
Iron Core
Air Core
OVERLOAD RELAYS Thermal
Current
Dual Voltage
AC MOTORS Single Phase
Magnetic
3-Phase Squirrel Cage
2-Phase, 4-Wire
Wound Rotor
DC MOTORS Armature
Shunt Field (show 4 loops)
Series Field (show 3 loops)
Commutating or Compensating Field (show 2 loops)
WIRING Not Connected
Connected
Power
Control
Terminal
CAPACITORS Fixed
Ground
Mechanical Connection
Mechanical Interlock Connection
RESISTORS
Adjustable
Fixed
Heating Element
Adjustable, by Fixed Taps
Rheostat, Potentiometer or Adjustable Taps
RES
H
RES
RES
SEMICONDUCTORS Diode or Half Wave Rectifier
Tunnel Diode
Full Wave Rectifier
NPN Transistor C
AC + DC
Zener Diode
DC
B
Bidirectional Breakdown Diode
Triac
PNP Transistor
UJT, N Base
C
SCR
AC
2
Photosensitive Cell
Gate Turn-Of Thyristor A
B2 E G
B1 E
UJT, P Base
B2 E
B
PUT
E
B1
K
Standard Elementary Diagram Symbols
Table 1
Standard Elementary Diagram Symbols (cont'd) OTHER COMPONENTS Bell
Annunciator
Buzzer
Horn, Alarm, Siren,etc.
Meter (indicate type by letters) VM
+
Battery –
Fuse
Meter Shunt
Thermocouple
SUPPLEMENTARY CONTACT SYMBOLS SPST, N.O. Single Break Double Break
SPST, N.C. Single Break Double Break
SPDT Single Break Double Break
DPST, 2 N.O. Single Break Double Break
DPST, 2 N.C. Single Break Double Break
DPDT Single Break Double Break
IEC SYMBOLS Push Buttons N.C. N.O.
Coil
Aux. Contacts N.O. N.C.
Contactor Breakers
STATIC SWITCHING CONTROL Limit Switch, N.O., Static Control
Static switching control is a method of switching electrical circuits without the use of contacts, primarily by solid state devices. To indicate static switching control, use the symbols shown in this table, enclosing them in a diamond as shown.
TERMS SPST: SPDT: DPST: DPDT:
Single Pole, Single Throw Single Pole, Double Throw Double Pole, Single Throw Double Pole, Double Throw
N.O.: N.C.: T.O.: T.C.:
Normally Open Normally Closed Timed Open Timed Closed
PUT: SCR: Triac: UJT:
Programmable Unijunction Transistor Silicon Controlled Rectifier Bidirectional Triode Thyristor Unijunction Transistor
3
NEMA and IEC Markings and Schematic Diagrams Control and Power Connection Table Table 2
NEMA and IEC Terminal Markings NEMA L1
L2
L3
T1
T2
T3 No standard designation
No specific marking
Alphanumeric, corresponding to incoming line and motor terminal designations
Control Terminals
Power Terminals
Coil Terminals
IEC 1
3
5
2
4
6
A1
14
A1 A3
A1 B1
A2 B2
22
Single digit numeric, odd for supply lines, even for load connections
2-digit numeric, 1st designates sequence, 2nd designates function (1-2 for N.C., 3-4 for N.O.)
Power Terminals
Control Terminals
Table 3
A1
A2
A2 A3
A2
One Winding
Tapped Winding
Tapped Winding
Two Windings
Coil Terminals
NEMA and IEC Controller Markings and Elementary Diagrams NEMA 3
1/L1
L2
L1
L3
L2 START 1
2
T1
T2
STOP
2
3
M
OL
T3
Typical Controller Markings
Typical Elementary Diagram
IEC A1
1
3
5
13
21
A2
2
4
6
14
22
11 STOP 12 23 START
Table 4
96
Typical Elementary Diagram
Control and Power Connections for Across-the-Line Starters, 600 V or less (From NEMA standard ICS 2-321A.60)
Line Markings Ground, when used Motor Running Overcurrent, units in:
1 element 2 element 3 element
Control Circuit Connected to For Reversing, Interchange Lines
4
A2 95
24
23
Typical Controller Markings
24 A1
1-Phase
2-Phase, 4-Wire
3-Phase
L1, L2
L1, L3: Phase 1 L2, L4: Phase 2
L1, L2, L3
L1 is always ungrounded
—
L2
L1 — —
— L1, L4 —
— — L1, L2, L3
L1, L2
L1, L3
L1, L2
—
L1, L3
L1, L3
Terminology
WIRING DIAGRAM A wiring diagram shows, as closely as possible, the actual location of all component parts of the device. The open terminals (marked by an open circle) and arrows represent connections made by the user. Since wiring connections and terminal markings are shown, this type of diagram is helpful when wiring the device or tracing wires when troubleshooting. Bold lines denote the power circuit and thin lines are used to show the control circuit. Black wires are conventionally used in power circuits and red wire in control circuits for AC magnetic equipment. A wiring diagram is limited in its ability to completely convey the controller’s sequence of operation. The elementary diagram is used where an illustration of the circuit in its simplest form is desired.
ELEMENTARY DIAGRAM An elementary diagram is a simplified circuit illustration. Devices and components are not shown in their actual positions. All control circuit components are shown as directly as possible, between a pair of vertical lines representing the control power supply. Components are arranged to show the sequence of operation of the devices and how the device operates. The effect of operating various auxiliary contacts and control devices can be readily seen. This helps in troubleshooting, particularly with the more complex controllers. This form of electrical diagram is sometimes referred to as a “schematic” or “line” diagram.
5
Examples of Control Circuits 2- and 3-Wire Control Elementary Diagrams Low Voltage Release and Low Voltage Protection are the basic control circuits encountered in motor control applications. The simplest schemes are shown below. Other variations shown in this section may appear more complicated, but can always be resolved into these two basic schemes. Note: The control circuits shown in this section may not include overcurrent protective devices required by applicable electrical codes. See page 11 for examples of control circuit overcurrent protective devices and their use.
Low Voltage Release: 2-Wire Control FIG. 1
Low Voltage Protection: 3-Wire Control
L1
L2
M
3
1
FIG. 2
OL
L1
1
L2
STOP
START
M
3
2
OL
M
PILOT DEVICE SUCH AS LIMIT SWITCH, PRESSURE SWITCH, ETC.
Low voltage release is a 2-wire control scheme using a maintained contact pilot device in series with the starter coil. This scheme is used when a starter is required to function automatically without the attention of an operator. If a power failure occurs while the contacts of the pilot device are closed, the starter will drop out. When power is restored, the starter will automatically pickup through the closed contacts of the pilot device. The term “2-wire” control is derived from the fact that in the basic circuit, only two wires are required to connect the pilot device to the starter.
Low voltage protection is a 3-wire control scheme using momentary contact push buttons or similar pilot devices to energize the starter coil. This scheme is designed to prevent the unexpected starting of motors, which could result in injury to machine operators or damage to the driven machinery. The starter is energized by pressing the Start button. An auxiliary holding circuit contact on the starter forms a parallel circuit around the Start button contacts, holding the starter in after the button is released. If a power failure occurs, the starter will drop out and will open the holding circuit contact. When power is restored, the Start button must be operated again before the motor will restart. The term “3-wire” control is derived from the fact that in the basic circuit, at least three wires are required to connect the pilot devices to the starter.
2-Wire Control: Maintained Contact Hand-OFF-Auto Selector Switch FIG. 3
L1
L2 A1 A2
3-Wire Control: Momentary Contact Multiple Push Button Station FIG. 4
L1
L2
START
I I HAND OFF AUTO A1
3A
M
OL
1 STOP STOP STOP
START 2
M 3
OL
START 1A
2A
A2 M 2-WIRE CONTROL DEVICE
A Hand-Off-Auto selector switch is used on 2-wire control applications where it is desirable to operate the starter manually as well as automatically. The starter coil is manually energized when the switch is turned to the Hand position and is automatically energized by the pilot device when the switch is in the Auto position.
6
When a motor must be started and stopped from more than one location, any number of Start and Stop push buttons may be wired together. It is also possible to use only one Start-Stop station and have several Stop buttons at different locations to serve as an emergency stop.
Examples of Control Circuits 3-Wire Control Elementary Diagrams 3-Wire Control: Pilot Light Indicates when Motor is Running FIG. 1
L1 1
3-Wire Control: Pilot Light Indicates when Motor is Stopped L2
STOP
START
M
3
2
FIG. 2
L1
OL
L2
1
STOP
START 3
2
M
OL
M
M M
R
G
A pilot light can be wired in parallel with the starter coil to indicate when the starter is energized, indicating the motor is running.
3-Wire Control: Push-to-Test Pilot Light Indicates when Motor is Running FIG. 3
L1 1
L2 STOP
START
M
3
2
A pilot light may be required to indicate when the motor is stopped. This can be implemented by wiring a normally-closed auxiliary contact on the starter in series with the pilot light, as shown above. When the starter is deenergized, the pilot light illuminates. When the starter picks up, the auxiliary contact opens, turning off the light.
3-Wire Control: Illuminated Push Button Indicates when Motor is Running FIG. 4
L1
OL
L2
1
STOP
2
START*
3
M
OL
M M
R
TEST
R
*
* Pushing on pilot light operates Start contacts. When the Motor Running pilot light is not lit, there may be doubt as to whether the circuit is open or whether the pilot light bulb is burned out. To test the bulb, push the color cap of the Pushto-Test pilot light.
3-Wire Control: Fused Control Circuit Transformer and Control Relay
3-Wire Control: Fused Control Circuit Transformer FIG. 5
The illuminated push button combines a Start button and pilot light in one unit. Pressing the pilot light lens operates the Start contacts. Space is saved by using a two-unit push button station instead of three.
L1
L2
FIG. 6
L1
L2
CR
FU2
FU1
START STOP
M
M
OL START
M
STOP GROUND (If used)
CR
OL
M GROUND (If used)
As an operator safety precaution, a step-down transformer can be used to provide a control circuit voltage lower than line voltage. The diagram above shows one way to provide overcurrent protection for control circuits.
A starter coil with a high VA rating may require a control transformer of considerable size. A control relay and a transformer with a low VA rating can be connected so the normally-open relay contact controls the starter coil on the primary or line side. Square D Size 5 Combination Starter Form F4T starters use this scheme.
7
Examples of Control Circuits 3-Wire Control Elementary Diagrams Jogging: Selector Switch and Start Push Button FIG. 1
Jogging: Selector Push Button FIG. 2
FPO 7-2 FPO 7-1
Jogging, or inching, is defined by NEMA as the momentary operation of a motor from rest for the purpose of accomplishing small movements of the driven machine. One method of jogging is shown above. The selector switch disconnects the holding circuit contact and jogging may be accomplished by pressing the Start push button.
A selector push button may be used to obtain jogging, as shown above. In the Run position, the selector-push button provides normal 3-wire control. In the Jog position, the holding circuit is broken and jogging is accomplished by depressing the push button.
Jogging: Control Relay
Jogging: Control Relay for Reversing Starter
FIG. 3
FIG. 4
FPO 7-4
FPO 7-3 When the Start push button is pressed, the control relay is energized, which in turn energizes the starter coil. The normallyopen starter auxiliary contact and relay contact then form a holding circuit around the Start push button. When the Jog push button is pressed, the starter coil is energized (independent of the relay) and no holding circuit forms, thus jogging can be obtained.
This control scheme permits jogging the motor either in the forward or reverse direction, whether the motor is at standstill or rotating. Pressing the Start-Forward or Start-Reverse push button energizes the corresponding starter coil, which closes the circuit to the control relay.The relay picks up and completes the holding circuit around the Start button. As long as the relay is energized, either the forward or reverse contactor remains energized. Pressing either Jog push button will deenergize the relay, releasing the closed contactor. Further pressing of the Jog button permits jogging in the desired direction.
3-Wire Control: More than 1 Starter, 1 Push Button Station Controls all
3-Wire Control: Reversing Starter
FIG. 5
FIG. 6
FPO 7-5
When one Start-Stop station is required to control more than one starter, the scheme above can be used. A maintained overload on any one of the motors will drop out all three starters.
8
FPO 7-6 3-wire control of a reversing starter can be implemented with a Forward-Reverse-Stop push button station as shown above. Limit switches may be added to stop the motor at a certain point in either direction. Jumpers 6 to 3 and 7 to 5 must then be removed.
Examples of Control Circuits 3-Wire Control Elementary Diagrams 3-Wire Control: Reversing Starter Multiple Push Button Station
3-Wire Control: Reversing Starter w/ Pilot Lights to Indicate Motor Direction FIG. 2
FIG. 1
More than one Forward-Reverse-Stop push button station may be required and can be connected in the manner shown above.
3-Wire Control: 2-Speed Starter
Pilot lights may be connected in parallel with the forward and reverse contactor coils, indicating which contactor is energized and thus which direction the motor is running.
3-Wire Control: 2-Speed Starter w/ 1 Pilot Light to Indicate Motor Operation at Each Speed FIG. 4
FIG. 3
3-wire control of a 2-speed starter with a High-Low-Stop push button station is shown above. This scheme allows the operator to start the motor from rest at either speed or to change from low to high speed. The Stop button must be operated before it is possible to change from high to low speed. This arrangement is intended to prevent excessive line current and shock to motor and driven machinery, which results when motors running at high speed are reconnected for a lower speed.
One pilot light may be used to indicate operation at both low and high speeds. One extra normally-open auxiliary contact on each contactor is required. Two pilot lights, one for each speed, may be used by connecting pilot lights in parallel with high and low coils (see reversing starter diagram above).
Plugging: Plugging a Motor to a Stop from 1 Direction Only
Anti-Plugging: Motor to be Reversed but Must Not be Plugged
FIG. 5
Plugging is defined by NEMA as a braking system in which the motor connections are reversed so the motor develops a counter torque, thus exerting a retarding force. In the above scheme, forward rotation of the motor closes the normally-open plugging switch contact and energizing control relay CR. When the Stop push button is operated, the forward contactor drops out, the reverse contactor is energized through the plugging switch, control relay contact and normally-closed forward auxiliary contact. This reverses the motor connections and the motor is braked to a stop. The plugging switch then opens and disconnects the reverse contactor. The control relay also drops out. The control relay makes it impossible for the motor to be plugged in reverse by rotating the motor rotor closing the plugging switch. This type of control is not used for running in reverse.
FIG. 6
Anti-plugging protection is defined by NEMA as the effect of a device that operates to prevent application of counter-torque by the motor until the motor speed has been reduced to an acceptable value. In the scheme above, with the motor operating in one direction, a contact on the anti-plugging switch opens the control circuit of the contactor used for the opposite direction. This contact will not close until the motor has slowed down, after which the other contactor can be energized.
9
Examples of Control Circuits Shunting Thermal Units During Starting Period Elementary Diagrams Shunting Thermal Units During Starting Period FIG. 1
Article 430-35 of the NEC describes circumstances under which it is acceptable to shunt thermal units during abnormally long accelerating periods. 430-35. Shunting During Starting Period. (a) Nonautomatically Started. For a nonautomatically started motor, the overload protection shall be permitted to be shunted or cut out of the circuit during the starting period of the motor if the device by which the overload protection is shunted or cut out cannot be left in the starting position and if fuses or inverse time circuit breakers rated or set at not over 400 percent of the full-load current of the motor are so located in the circuit as to be operative during the starting period of the motor.
FPO 9-1
(b) Automatically Started. The motor overload protection shall not be shunted or cut out during the starting period if the motor is automatically started.
Exception. The motor overload protection shall be permitted to be shunted or cut out during the starting period on an automatically started motor where: (1) The motor starting period exceeds the time delay of available motor overload protective devices, and (2) Listed means are provided to: a. Sense motor rotation and to automatically prevent the shunting or cut out in the event that the motor fails to start, and b. Limit the time of overload protection shunting or cut out to less than the locked rotor time rating of the protected motor, and c. Provide for shutdown and manual restart if motor running condition is not reached. Figures 1 and 2 show possible circuits for use in conjunction with 3-wire control schemes. Figure 1 complies with NEC requirements. Figure 2 exceeds NEC requirements, but the additional safety provided by the zero speed switch might be desirable. Figure 3 shows a circuit for use with a 2-wire, automatically started control scheme that complies with NEC requirements. UL or other listed devices must be used in this arrangement.
FIG. 2
FPO 9-2
FIG. 3
FPO 9-3
10
Examples of Control Circuits Overcurrent Protection for 3-Wire Control Circuits Elementary Diagrams 3-Wire Control: Fusing in 1 Line Only FIG. 1
3-Wire Control: Fusing in Both Lines
L1
L2
FIG. 2
L1
FU1
FU2
FU1 START
STOP
M
OL
M
START
STOP
3-Wire Control: Fusing in Both Primary and Secondary Lines
L1
L2
FIG. 4
L1
FU2
L2 FU4
FU3
PRI
PRI FU1
X1 STOP
SEC
START
X2
FU2 X1
M
OL
STOP
X2 M
OL
M
Control circuit transformer with fusing in both primary lines, no secondary fusing and all lines ungrounded.
Control circuit transformer with fusing in both primary lines and both secondary lines, with all lines ungrounded.
3-Wire Control: Fusing in Both Primary Lines and 1 Secondary Line L1
L2 FU1
SEC
START
M
FIG. 5
OL
Common control with fusing in both lines and with both lines ungrounded.
3-Wire Control: Fusing in Both Primary Lines
FU1
M
M
GND
Common control with fusing in one line only and with both lines ungrounded or, if user’s conditions permit, with one line grounded.
FIG. 3
L2
3-Wire Control: Fusing in Both Primary and Secondary Lines For Large Starters using Small Transformer FIG. 6
L1
L2
FU2 FU3
PRI
FU4
M
CR
FU3
STOP
SEC START
PRI M
OL
FU1
FU2 X1
M GND
STOP
SEC
START
X2 CR
OL
M
Control circuit transformer with fusing in one secondary line and both primary lines, with one line grounded.
Control circuit transformer with fusing in both primary lines and both secondary lines, with all lines ungrounded. Used for large VA coils only.
11
AC Manual Starters and Manual Motor Starting Switches Class 2510
Manual Motor Starting Switches: Class 2510 Type K FIG. 1
T1
FIG. 2
L1
T1 L1
L1 T2 T3
L2
L3
T3 L2
T1
L3
PILOT LIGHT (IF USED)
R
PILOT LIGHT (IF USED)
R
T3
T1 T2 T3
MOTOR
MOTOR
2-Pole, 1-Phase
3-Pole, 3-Phase
Fractional Horsepower Manual Starters: Class 2510 Type F FIG. 3
FIG. 4
T2
FIG. 5
T2
L2
L2
L1
L1
T2
A O H
R
T1 T1
PILOT LIGHT (IF USED)
PILOT LIGHT (IF USED)
R
T1
T2
T1
MOTOR
2 1 L1
4 3
PILOT LIGHT (IF USED)
R
T1
T2
2
MOTOR
1-Pole
L2
A O H
4
2-WIRE CONTROL DEVICE
2-Pole
T2
4
MOTOR
2-Pole w/ Selector Switch
Integral Horsepower Manual Starters: Class 2510 Size M0 and M1 FIG. 6
L1
L2
FIG. 7
L1
L2
T2
FIG. 8
L1
L2
FIG. 9
L1
L2
L3
T1
T2
T3
FIG. 10
L1
L2
L3
T1
T2
T3
L2 L3
L1
T1
T2 T1
T1
T2
T1
T2
T1 MOTOR
T2 T1
T3
T1 T2 T3
T1 T2 T3
MOTOR
MOTOR
T3
MOTOR MOTOR
2-Pole, 1-Phase
3-Pole, DC
3-Pole, 1-Phase
3-Pole, 3-Phase
3-Pole, 3-Phase w/ additional Interlock (Form X)
®
12
AC Manual Starters and Manual Motor Starting Switches Class 2511 and 2512
AC Reversing Manual Starters and Manual Motor Starting Switches: Class 2511 FIG. 1
FIG. 2
REV
FWD
T1
L1
T2
L2
T3
L3
L1
L2
L3
T1
T2
T3
T1 T2 T3
T1 T2 T3
MOTOR
MOTOR
Reversing Manual Motor Starting Switch Type K, 3-Pole, 3-Phase
Reversing Manual Starter Sizes M0 and M1, 3-Pole, 3-Phase
AC 2-Speed Manual Motor Starting Switches: Class 2512 Type K FIG. 4
FIG. 3
FPO 12-6b
FPO 12-6a
2-Pole, 1-Phase w/ Pilot Lights
3-Pole, 3-Phase
AC 2-Speed Manual Motor Starters: Class 2512 Type F FIG. 5
FIG. 6
FPO 13-1a 2-Unit, 2-Pole w/ Mechanical Interlock and Pilot Lights
FPO 13-1b
3-Unit, 2-Pole w/ Selector Switch and Pilot Lights
®
13
2-Speed AC Manual Starters and IEC Motor Protectors Class 2512 and 2520 and Telemecanique GV1/GV3
2-Speed AC Manual Motor Starters: Class 2512 Size M0 and M1 FIG. 1
L1
L2
L3
T2 T11 T13 T1 T3 T12
MOTOR T1
T2
T3
T11
T12
T13
2-Speed Manual Starter for Wye-Connected, Separate Winding Motor
Motor Protective Switches: Class 2520 FIG. 2
1/L1
3/L2
FIG. 3
5/L3
1/L1
3/L2
5/L3
FIG. 4
1/L1
3/L2
5/L3
2/T1 4/T2 6/T3
2/T1 4/T2 6/T3
2/T1 4/T2 6/T3
T1 T2 T3
T1
T3
T3
MOTOR
MOTOR
MOTOR
3-Pole, 3-Phase
2-Pole Application
1-Pole Application
IEC Manual Starters: GV1/GV3
FIG. 5
1/L1 3/L2
5/L3
FIG. 6
FIG. 7
GV3 B• D1
I> I> I> 2/T1 4/T2 6/T3
GV3 A08 95
D2 GV3 D• C1
GV3 M• Motor Protector FIG. 8
<
GV3 A09 97
96
I>
98
GV3 A0• Fault Signalling Contacts
GV1 A02
13
21
13
23
14
22
14
24
GV1 A03 13 23 31
GV1 A05 13 23 33
14 24 32
14 24 34
GV1 A06 C2
I>
GV1 A01
GV3 Voltage Trips
GV1 A07
13 23 33
13 23 31
14 24 34
14 24 33
GV1 A0• Contact Block
®
14
Drum Switches Class 2601
Drum Switches: Class 2601
REVERSE
OFF
MOTOR
FORWARD
1
2 1
2
1
2
3
4 3
4
3
4
5
6 5
6
5
6
1
2
3
4
5
6
DRUM SW.
MOTOR
1
2
3
4
5
6
MOTOR
DRUM SW.
FIG. 3
MOTOR
DRUM SW. 1
2
3
4
5
6
LINE
1-Phase, Capacitor or Split-Phase Motor
FIG. 5
LINE
MOTOR
1-Phase, 4-Lead Repulsion Induction Motor FIG. 6
LINE
3-Phase, 3-Wire Motor
Internal Switching FIG. 4
DRUM SW.
START
FIG. 2
HANDLE END
RUN
FIG. 1
DRUM SW. 1
2
3
4
5
6
LINE
1-Phase, 3-Lead Repulsion Induction Motor FIG. 7
LINE
DRUM SW. LINE
MOTOR
1
2
1
2
3
4
3
4
5
6
5
6
COMMON
2-Phase, 4-Wire Motor MOTOR
LINE 1
2
3
4
5
6
DC, Shunt Motor
DRUM SW. 1
2
ARMATURE 3
4
5
6
DC, Series Motor
LINE
FIG. 10
MOTOR
DRUM SW. LINE
1 2 ARMATURE SERIES FIELD
DRUM SW.
SERIES FIELD
ARMATURE
SHUNT FIELD
MOTOR
FIG. 9
SHUNT FIELD
2-Phase, 3-Wire Motor FIG. 8
3
4
5
6
DC, Compound Motor
®
15
DC Starters, Constant and Adjustable Speed Class 7135 and 7136
Constant Speed DC Starter: Class 7135 FIG. 1
FPO 15-1
Typical Elementary Diagram for NEMA Size 2, 3 and 4
Adjustable Speed DC Starter: Class 7136 FIG. 2
FPO 15-2
Typical Elementary Diagram for NEMA Size 2, 3 and 4
Acceleration Contactors: Class 7135, 7136, 7145 and 7146 NEMA Size
1
2
3
4
5
No. of Acceleration Contactors
1
2
2
2
3
®
16
Reversing DC Starters, Constant and Adjustable Speed Class 7145 and 7146
Reversing Constant Speed DC Starter: Class 7145 FIG. 1
FPO 16-1
Typical Elementary Diagram for NEMA Size 2, 3 and 4
Reversing Adjustable Speed DC Starter: Class 7146 FIG. 2
FPO 16-2
Typical Elementary Diagram for NEMA Size 2, 3 and 4
®
17
Mechanically Latched Contactors and Medium Voltage Motor Controllers Class 8196 and 8198
Mechanically Latched Contactor: Class 8196 Type FL13, FL23, FL12 and FL22 FIG. 1
FPO 17-2 150%
Full-Voltage, Non-Reversing Squirrel Cage Motor Controller: Class 8198 Type FC11, FC21, FC13, FC23, FC12 and FC22 FIG. 2
FPO 17-1 145%
®
18
Medium Voltage Motor Controllers Class 8198
Full-Voltage Squirrel Cage Motor Controller: Class 8198 Type FCR1 and FCR2 FIG. 1
FPO 17-3 160%
®
19
Medium Voltage Motor Controllers Class 8198
Reduced-Voltage, Primary Reactor, Non-Reversing Squirrel Cage Motor Controller: Class 8198 Type RCR1 and RCR2 FIG. 1
FPO 18-1 130%
®
20
Medium Voltage Motor Controllers Class 8198
Reduced-Voltage, Primary Reactor, Autotransformer, Non-Reversing Squirrel Cage Motor Controller: Class 8198 Type RCA1 and RCA2 FIG. 1
FPO 18-2 150%
®
21
Medium Voltage Motor Controllers Class 8198
Full Voltage, Non-Reversing Synchronous Motor Controller: Class 8198 Type FS1 and FS2 FIG. 1
FPO 19-1 170%
®
22
Medium Voltage Motor Controllers Class 8198
Reduced-Voltage, Primary Reactor, Non-Reversing Synchronous Motor Controller: Class 8198 Type RS1 and RS2 FIG. 1
FPO 19-2 140%
®
23
Medium Voltage Motor Controllers Class 8198
Reduced-Voltage, Autotransformer, Non-Reversing Synchronous Motor Controller: Class 8198 Type RSA1 and RSA2 FIG. 1
FPO 20-1 160%
®
24
Medium Voltage Motor Controllers Class 8198
Full-Voltage, Non-Reversing, Brushless Synchronous Motor Controller: Class 8198 Type FSB1 and FSB2 FIG. 1
FPO 20-2 155%
®
25
Solid State Protective Relays Class 8430
Solid State Protective Relays: Class 8430 Type DAS, DASW, DASV and DASVW FIG. 1 L1 L2 L3
M
OL
T1
M
OL
T2
M
OL
T3
MOTOR
START
STOP
OL M
Dashed lines represent optional contacts
12
L1
14 22
L2 L3
24
11
With the line voltage connections directly at the motor terminals, the relay will detect all phase loss conditions ahead of the connection points. However, the motor may sustain a momentary “bump” in the reverse condition if the proper phase sequence is not present.
M
21 FIG. 2 L1 L2 L3
STOP
START
M
12
L1
14 22
L2 L3
24
11
Dashed lines represent optional contacts
M
OL
T1
M
OL
T2
M
OL
T3
MOTOR
With the line voltage connections ahead of the starter, the motor can be started in the reverse direction. The relay cannot detect a phase loss on the load side of the starter.
OL M
21
Solid State Protective Relays: Class 8430 FIG. 3
FIG. 4
FIG. 5
4
5
3 Input Signal
2 L1 L2 L3
A1 11 21 B1 B2
1
2
3
4
5
6
1
8
6
L1
7
L2 L3
Type MPS 240V FIG. 6
1
2
3
4
5
6
7
8
9
12 14 22 24 A2 VS
7
8
9 10 11 12
Dashed lines represent optional contacts (DIAW and DUAW devices only)
Type DIA, DIAW, DUA and DUAW
A
B L3 L2 L1
Type MPD
Type MPS 480V
®
26
Solid State Protective Relays Class 8430
Load Detector Relay: Class 8430 Type V FIG. 1
FPO 22-1
Wiring Diagram
FPO 22-3
Elementary Diagram (Common Control)
Load Converter Relay: Class 8430 Type G FIG. 2
FPO 22-2
®
27
General Purpose Relays Class 8501
Control Relays: Class 8501 Type CO and CDO FIG. 2
FIG. 1
Type CO6 and CDO6
FIG. 3
Type CO7 and CDO7
FIG. 4
Type CO8 and CDO8
FIG. 5
Type CO21 and CDO21
FIG. 6
Type CO15 and CDO15
Type CO16, CDO16, CO22 and CDO22
Control Relays: Class 8501 Type UBS FIG. 7
START
L1
M
STOP
L2
M
9
10
8
5
TERMINAL NUMBERS
Control Relays: Class 8501 Type K FIG. 8
FIG. 9
FIG. 10
1
3
4
6
1
3
7
9
4
6
7
9
8 RESET A
B
COMMON
LATCH
4 3
B
A
FIG. 12
FIG. 11
1
6
2
7 1
Type KU, KF, KX, KUD, KFD and KXD 2-Pole
Type KL
6
7
9
FIG. 13
6
A
B
– +
+ –
LATCH RESET Type KLD
8
Type KP and KPD 2-Pole
3
4
5
1
2
3
4
5
6
7
8
9
A
B
5
7
4
8
3
9 2
10 1
Type KU, KF, KX, KUD, KFD and KXD 3-Pole
11
Type KP and KPD 3-Pole
®
28
NEMA Control Relays Class 8501 and 9999
10 A Control Relay w/ Convertible Contacts: Class 8501 Type X FIG. 1
FPO 27-1
* Note: Class 8501 Type XO••••XL, XDO••••XL, XDO••••XDL and XO••••XDL latch relays use the same diagram except for the addition of an unlatch coil (8 poles maximum).
Timer Attachment: Class 9999 Type XTD and XTE FIG. 2
TIMED CONTACTS 14
2 N.O.
1 N.C. 1 N.O. 14
14
13
13
13
14 POLE #13
14
2 N.C.
14
POLE #14
Note: All contacts are convertible.
13
13
ON DELAY (TDE)
13
OFF DELAY (TDD)
No. of Timed Contacts
Class 9999 Type
2
XTD XTE
Pole No.* 13
14
O
1
* O = N.O. Contact 1 = N.C. Contact
®
29
General Purpose Relays and Sensing Relays Class 8501 and Telemecanique RM2 LA1/LG1
Miniature Control Relays: Class 8501 Type RS and RSD FIG. 1
FIG. 2
1
1
4
5
5
8
9
9
12
14 (+)
13 (–)
Type RS42 and RSD42
Type RS41 and RSD41 FIG. 3
FIG. 4
1
2
3
4
8
5
6
7
8
12
9
10
11
12
1
2
4
5
6
9
10
14 (+)
13 (–)
14 (+)
13 (–)
14 (+)
13 (–)
Type RS4, RSD4, RS14, RSD14, RS24, RSD24, RS34, RSD34, RS44 and RSD44
Type RS43 and RSD43
Control Relays w/ Intrinsically Safe Terminals: Class 8501 Type TO41 and TO43 FIG. 6
FIG. 5
1
ON
2
3
4
5
6
OFF
SUPPLY VOLTAGE
OFF
ON
7
8
9
10
11
12
Non-Hazardous Location Terminals
Intrinsically Safe Terminals
Sensing Relays: RM2 LA1/LG1 FIG. 7
M H
16 18
B1 B2
A1 15 B3 B1 B2
B1 B2
15
16 18 B3 A2
H
L M
B2 B1 B3
15
H = High level electrode L = Low level electrode
16 18 16 18 X
2 Levels RM2 LG1
H M
Supply voltage
Supply voltage
L A1 15 B2 B1 B3
X A2
1 Level
M = Reference electrode (common)
RM2 LA1
®
30
IEC Relays IEC D-Line Control Relays (for input modules see page 42) Control Relays: CA2 and CA3 FIG. 1 A1
13 23 33 43 NO NO NO NO
A2
14
24
34
FIG. 2
44
13 21 33 43 NO NC NO NO
A2
14
22
34
FIG. 3
44
3 N.O. & 1 N.C. Instantaneous CA2 DN31 and CA3 DN31
4 N.O. Instantaneous CA2 DN40 and CA3 DN40 FIG. 4
A1
A1
13 21 35 NO NC NC
47 NO
A2
14
48
22
36
13 21 31 43 NO NC NC NO
A2
14
22
32
44
2 N.O. & 2 N.C. Instantaneous CA2 DN22 and CA3 DN22
FIG. 5
2 N.O. & 2 N.C. Instantaneous, w/ 2 Make-Before-Break CA2 DC22 and CA3 DC22
A1
E1
A1
E2
A2
13 21 31 NO NC NC
14
22
43 NO
32
44
2 N.O. & 2 N.C. Instantaneous w/ Mechanical Latch CA2 DK22 and CA3 DK22
Front-Mounted Standard Instantaneous Auxiliary Contact Blocks: LA1 FIG. 6
FIG. 7
53 61 NO NC
54
53 63 NO NO
62
54
52
54
62
76
54
54
64
74
FIG. 13
72
52
62
72
53 61 71 81 NO NC NC NC
84
51 61 71 81 NC NC NC NC
84
4 N.O. LA1 DN40
2 N.O. & 2 N.C. w/ 2 Make-Before-Break LA1 DC22
62
FIG. 10
54
2 N.O. & 2 N.C. LA1 DN22
53 63 73 83 NO NO NO NO
88
53 61 71 83 NO NC NC NO
62
2 N.C. LA1 DN02 FIG. 12
53 61 75 87 NO NC NC NO
FIG. 9
51 61 NC NC
64
2 N.O. LA1 DN20
1 N.O. & 1 N.C. LA1 DN11 FIG. 11
FIG. 8
62
72
82
1 N.O. & 3 N.C. LA1 DN13 FIG. 14
53 61 73 83 NO NC NO NO
82
54
4 N.C. LA1 DN04
62
74
84
3 N.O. & 1 N.C. LA1 DN31
Front-Mounted Damp- and Dust-Protected Instantaneous Auxiliary Contact Blocks: LA1 FIG. 15
53 NO
63 NO
54
64
FIG. 16
53 NO
63 NO
54
64
FIG. 17
54
2 N.O. w/ Grounding Screw LA1 DY20
2 N.O. LA1 DX20
FIG. 18
53 63 73 83 NO NO NO NO
64
74
53 61 73 83 NO NC NO NO
84
54
2 Dusttight N.O. & 2 N.O. LA1 DZ40
62
74
84
2 Dusttight N.O. & 1 N.O. & 1 N.C. LA1 DZ31
Front-Mounted Time Delay Auxiliary Contacts: LA2 and LA3
E1
46
E2
A2 E2
LA6 DK2
65 NC
58
66
Off Delay, 1 N.O. & 1 N.C. LA3 DR
Side-Mounted Auxiliary Contact Blocks: LA8 FIG. 24
53/ NO
83 NO
45 A1
A2
LA6 DK1
FIG. 23
57 NO
54/
61/ NC
71 NC
E1
68
FIG. 21
62/
1 N.O. & 1 N.C. Instantaneous LA8 DN11
FIG. 25
53/ NO
83 NO
Front-Mounted Mechanical Latch Adder Blocks: LA6 A1
56
On Delay, 1 N.C. w/ 1 Offset N.O. LA2 DS
On Delay, 1 N.O. & 1 N.C. LA2 DT
FIG. 22
67 NO
54/
63/ NO
73 NO
68
55 NC
84
56
FIG. 20
72
67 NO
84
55 NC
74
FIG. 19
64/
2 N.O. Instantaneous LA8 DN20
®
31
IEC Relays Class 8501
Miniature IEC Relays: Class 8501 Type PR 1 FIG. 1 A1
13 21 NO NC
A2
14
PR 1.11 E
FIG. 2
33 41 NO NC
PRD 1.11 E
A1
PV 11
22
34
42
14
44
PV 02
PRD 1.20 E A2
PV 20 34
31 41 NC NC
13 23 NO NO
PR 1.20 E
33 43 NO NO
32
24
Type PR 1 and PRD 1 Relays
42
Type PV Adder Decks for PR 1.20 E
Alternating Relays: Class 8501 Type PHA FIG. 3
relay coil
A1 13
23 13
14
energized deenergized closed open
14 A2
24
23
24
closed open
®
32
Type P Contactors and Type T Overload Relays Class 8502 and 9065
Power Terminals FIG. 1
Coil Terminals
1
3
5
2
4
6
FIG. 2
A1
A2
Power terminals on contactors, overloads and switches are single digits – odd for line side terminals and even for load side terminals.
Coil terminals are designated by a letter and a number. Terminals for a single winding coil are designated “A1” and “A2”.
Overload Relay Contact Terminals
Auxiliary Contact Terminals FIG. 3
FIG. 4
Location 13
21
31 43
53
95
97
96 98 With Isolated N.O. Alarm Contact 14
22
32 44
95
Status (N.O. or N.C.)
54
Auxiliary contacts on contactors, relays and push button contacts use 2-digit terminal designations, as shown in the diagram above. The first digit indicates the location of the contact on the device. The second digit indicates the status of the contacts, N.O. or N.C. “1” and “2” indicate N.C. contacts. “3” and “4” indicate N.O. contacts.
96 98 With Non-Isolated N.O. Alarm Contact
Overload contact terminals are marked with two digits. The first digit is “9”. The second digits are “5” and “6” for a N.C. and “7” and “8” for a N.O. isolated contact. If the device has a non-isolated alarm contact (single pole), the second digits of the N.O. terminals are “5” and “8”.
Class 8502 Type PD or PE Contactor w/ Class 9065 Type TR Overload Relay FIG. 5
FPO 30-2 120% Wiring Diagram
FPO 30-2 120%
Elementary Diagram
®
33
Type P Contactors and Type T Overload Relays Class 8502 and 9065
Class 8502 Type PG or PD Contactor w/ Class 9065 Type TD Overload Relay FIG. 1
FPO 30-3 120% FPO 30-3 120% Wiring Diagram
Elementary Diagram
Class 8502 Type PE Contactor w/ Class 9065 Type TE Overload Relay FIG. 2
FPO 30-4 120% FPO 30-4 120% Wiring Diagram
Elementary Diagram
Class 8502 Type PF, PG or PJ Contactor w/ Class 9065 Type TF, TG or TJ Overload Relay FIG. 3
FPO 31-1 120% FPO 31-1 120% Wiring Diagram
Elementary Diagram
®
34
Type P Reversing Contactors and Type T Overload Relays Class 8502, 8702 and 9065
Class 8502 Type PJ or PK Contactor w/ Class 9065 Type TJE Overload Relay FIG. 4
FPO 31-2 120%
FPO 31-2 120% Wiring Diagram
Elementary Diagram
Class 8702 Type PDV or PEV Reversing Contactor w/ Class 9065 Type TR Overload Relay FIG. 1
FPO 31-3 Elementary Diagram
FPO 31-3 120% Elementary Diagram
®
35
Type S AC Magnetic Contactors Class 8502
AC Magnetic Contactors: Class 8502 Type S FIG. 1
3
L1
FIG. 2
L2
3 T1
L2
T1
MOTOR
T1
T2
T2
T1
2
1-Pole, Size 0 and 1 FIG. 3
2-Pole, Size 00, 0 and 1 FIG. 4
3 L1
3
L2
1
T2
T1 T2 T3
MOTOR
L1
L2
L3
T1
T2
T3
1
MOTOR 2
T1
T2
2
3-Pole, Size 00 to 5
2-Pole, Size 2 to 5 FIG. 5
L2
MOTOR 2
T1
L1 1
1
FIG. 6
3 L1 T1 T3 T4 T2
L3
L4
3
L2
L1
1
L2
L3
T2
T3
T1 T2 T3 X2
MOTOR
MOTOR 2
T1
T3
T4
T2
2
4-Pole, Size 0, 1 and 2 FIG. 7
T1
5-Pole, Size 0, 1 and 2 FIG. 8
TO SEPARATE CONTROL
2- and 3-Wire Control for Figure 1 to 5
3 X2
Separate Control for Figure 6
®
36
Type S AC Magnetic Contactors Class 8502
Size 6, 3-Pole Contactor – Common Control Class 8502 Type SH Series B FIG. 1
Wiring Diagram This symbol denotes the coil function, provided by a solid-state control module, 30 VA transformer, two fuses in the secondary of the transformer, N.C. electrical interlock and DC magnet coil. Short-Circuit Protection Rating of branch circuit protective device must comply with applicable electrical codes and the following limitations: Max. Rating Type of Device Class K5 or RK5 time-delay fuse 600 A Class J, T or L fuse 1200 A Inverse-time circuit breaker 800 A
Elementary Diagram
®
37
Type S AC Magnetic Contactors Class 8502
Size 6, 3-Pole Contactor – Separate Control Class 8502 Type SH Form S Series B FIG. 1
Wiring Diagram
This symbol denotes the coil function, provided by a solid-state control module, 30 VA transformer, two fuses in the secondary of the transformer, N.C. electrical interlock and DC magnet coil. Short-Circuit Protection Rating of branch circuit protective device must comply with applicable electrical codes and the following limitations: Max. Rating Type of Device Class K5 or RK5 time-delay fuse 600 A Class J, T or L fuse 1200 A Inverse-time circuit breaker 800 A
Elementary Diagram
®
38
Type S AC Magnetic Contactors Class 8502
Size 7, 3-Pole Contactor – Common Control Class 8502 Type SJ Series A FIG. 1
Wiring Diagram This symbol denotes the coil function, provided by a solid-state control module, 30 VA transformer, two fuses in the secondary of the transformer, N.C. electrical interlock and DC magnet coil. Short-Circuit Protection Rating of branch circuit protective device must comply with applicable electrical codes and the following limitations: Max. Rating Type of Device Class K5 or RK5 time-delay fuse 600 A Class J, T or L fuse 1600 A Inverse-time circuit breaker 2000 A
Elementary Diagram
®
39
Type S AC Magnetic Contactors Class 8502
Size 7, 3-Pole Contactor – Separate Control Class 8502 Type SJ Form S Series A FIG. 1
Wiring Diagram
This symbol denotes the coil function, provided by a solid-state control module, 30 VA transformer, two fuses in the secondary of the transformer, N.C. electrical interlock and DC magnet coil. Short-Circuit Protection Rating of branch circuit protective device must comply with applicable electrical codes and the following limitations: Max. Rating Type of Device Class K5 or RK5 time-delay fuse 600 A Class J, T or L fuse 1600 A Inverse-time circuit breaker 2000 A
Elementary Diagram
®
40
IEC Contactors IEC Contactors and Auxiliary Contact Blocks (for Input Modules see page 42) 3- and 4-Pole Contactors: LC1 and LP1 (Terminal markings conform to standards EN 50011 and 50012) FIG. 1 A1
A2
1 L1
3 L2
5 13 L3 NO
T1 2
T2 4
T3 6
FIG. 2 A1
A2 14
A1
A2
5 21 L3 NC
T1 2
T3 6 22
T2 4
FIG. 3
1 L1
3 L2
5 L3
7 L4
T1 2
T2 4
T3 6
T4 8
FIG. 5 A1
1
A2
R1
2
A2
FIG. 6
3
R4
4
D12 008 and D25 008
D12 004 to D80 004
T1 2
5 L3
T2 4
13 21 NO NC
T3 6
14
22
D40 11 to D95 11
R3
R2
1 3 L1 L2
A1
D09 01 to D32 01
D09 10 to D32 10 FIG. 4
1 3 L1 L2
A1
R1
1
3 R3
A2
R2
2
4 R4
D40 008 to D80 008
Front-Mounted Standard Instantaneous Auxiliary Contact Blocks: LA1 FIG. 8
94
FIG. 7
43
54
FIG. 10
53 63 NO NO
62
54
FIG. 11
51 61 NO NO
64
52
53 NO
62
54
61 71 NC NC
83 NO
62
84
72
FIG. 12
53 NO
61 71 NC NC
54
62
81 NC
72
82
93
44
1 N.O. & 1 N.C LA1 DN 11
1 N.O. LA1 DN 10
FIG. 14
92
FIG. 13
FIG. 9
53 61 NO NC
NO
41 NO
2 N.O. LA1 DN 20
53 NO
61 75 NC NC
54
62
FIG. 15
87 NO
76
2 N.C. LA1 DN 02 53 NC
54
88
63 73 NC NC
64
74
2 N.O. & 2 N.C. LA1 DN 22 FIG. 16
83 NC
51 NC
84
61 71 NC NC
52
62
72
1 N.O. & 3 N.C. LA1 DN 13 FIG. 17
81 NC
82
53 NO
61 73 NC NO
83 NO
54
62
84
74
91
42
2 N.O. & 2 N.C. w/ 2 Make-Before-Break LA1 DC 22
1 N.C. LA1 DN 01
4 N.O. LA1 DN 40
4 N.C. LA1 DN 04
3 N.O. & 1 N.C. LA1 DN 31
Front-Mounted Damp- and Dust-Protected (IP 54) Instantaneous Auxiliary Contact Blocks: LA1 FIG. 18
53 N0
63 NO
54
64
FIG. 19
53 N0
63 NO
54
64
FIG. 20
53 N0
63 N0
73 N0
83 N0
54
64
74
84
FIG. 21
53 61 N0 NC
73 N0
83 N0
54 62
74
84
2 N.O. (5-24 V) w/ Grounding Screw 2 Dusttight N.O. (24-50 V) & 2 N.O. 2 Dusttight N.O. (24-50 V) & 1 N.O. & 1 N.C. LA1 DY 20 LA1 DZ 40 LA1 DZ 31
2 N.O. LA1 DX 20
Front-Mounted Time Delay Auxiliary Contacts: LA2 and LA3
56
On Delay, 1 N.O. w/ 1 Offset N.O. LA2 DS•
45
E1
46
E2
A1
A2
A2 E2
LA6 DK 1
FIG. 26
LA6 DK 2, LA6 DK 3
Side-Mounted Auxiliary Contact Blocks: LA8 FIG. 27
53/ NO
83 NO
E1
Off Delay, 1 N.O. & 1 N.C. LA3 DR•
54/
61/ NC
71 NC
A1
66
62/
1 N.O. & 1 N.C. Instantaneous LA8 DN 11
FIG. 28
53/ NO
83 NO
Front-Mounted Mechanical Latch Adder Blocks: LA6 FIG. 25
58
84
On Delay, 1 N.O. & 1 N.C. LA2 DT•
68
54/
63/ NO
73 NO
68
57 65 NO NC
72
56
FIG. 24
55 67 NC NO
84
FIG. 23
55 67 NC NO
74
FIG. 22
64/
2 N.O. Instantaneous LA8 DN 20
®
41
IEC Contactors Input Modules and Reversing Contactors
Input Modules: LA4 FIG. 2
FIG. 1
FIG. 3
AC/DC
PLC
AC
A1
A2
B2
A1
A2
AC/DC B1
A1
A2
A/M 0
0
t
A2
A1
A1
+ E1
A1
A2 K
K Off Delay Timer Module LA4 DR
On Delay Timer Module LA4 DT
AC A1
1/0
A2
K
FIG. 4
t
E2
AC A2
A1
FIG. 5
AC A1
+ E1
E2
A1
A2
Auto-Manual-Off Control Module LA4 DM
AC A2
FIG. 6
AC A1
A2
+ E1
A1 K
Relay Interface Amplifier Module w/ Manual Override, LA4 DL
Relay Interface Amplifier Module LA4 DF
AC A2
A2
K
K
E2
Solid State Interface Amplifier Module LA4 DW
Contactors: LC2, LP2 and LA9 FIG. 8
FIG. 7
A1
1
3
5
1
3
5 A1
A2
2
4
6
2
4
6 A2
FIG. 9
01 01
U
V W
A1
1
3
5
7
1
3
5
7
A1
A2
2
4
6
8
2
4
6
8
A2
A1
A1
A2
A2 02
21
21 02
KM2
KM2
22 KM1
22 KM1
A2
A2
Reversing Contactor 3-Pole, for Motor Control LC2, LP2 D0901 to D3201
Transfer Contactor, 4-Pole, Mechanically Interlocked LC2, LP2 D12004 to D8004
Mechanical Interlock w/ Electrical Interlock LA9 D0902, D4002 and D8002
®
42
Type S AC Magnetic Starters Class 8536 1-Phase, Size 00 to 3 1-Pole, 1-Phase Magnetic Starters, Size 00 to 3: Class 8536 Type S FIG. 1
* Marked “OL” if alarm contact is supplied
Wiring Diagram
Elementary Diagram Single Phase Starter w/ Single Voltage Motor
FIG. 2
* Marked “OL” if alarm contact is supplied
Note: Starters are factory-wired with coil connected for the higher voltage. If starter is used on lower voltage, connect per coil diagram.
Wiring Diagram
Elementary Diagram Single Phase Starter w/ Dual Voltage Motor
3-Pole, 3-Phase Magnetic Starters, Size 00 to 3, Connected for Single Phase: Class 8536 Type S FIG. 3
* Marked “OL” if alarm contact is supplied Wiring Diagram
Elementary Diagram
3-Phase Starter Connected for Single Phase, Single Voltage Motor
®
43
Type S AC Magnetic Starters Class 8536 2-Phase and 3-Phase, Size 00 to 5 4-Pole, 2-Phase Magnetic Starters: Class 8536 Type S FIG. 1
* Marked “OL” if alarm contact is supplied Elementary Diagram
Wiring Diagram Size 0, 1 and 2 FIG. 2
* Marked “OL” if alarm contact is supplied
Elementary Diagram
Wiring Diagram Size 3 and 4
3-Pole, 3-Phase Magnetic Starters: Class 8536 Type S FIG. 3
* Marked “OL” if alarm contact is supplied Elementary Diagram
Wiring Diagram Size 00 to 4 FIG. 4
▲ If alarm contact is supplied, a single (3 thermal unit) overload block is furnished, fed from 3 current transformers. * Marked “OL” if alarm contact is supplied
Elementary Diagram
Wiring Diagram Size 5
®
44
Type S AC Magnetic Starters Class 8536, 8538 and 8539 3-Phase, Size 6 3-Pole, 3-Phase Magnetic Starters, Size 6 – Common Control Class 8536/8538/8539 Type SH Series B FIG. 1
Wiring Diagram
This symbol denotes the coil function, provided by a solid-state control module, 30 VA transformer, two fuses in the secondary of the transformer, N.C. electrical interlock and DC magnet coil.
Elementary Diagram
®
45
Type S AC Magnetic Starters Class 8536 3-Phase, Size 7 3-Pole, 3-Phase Magnetic Starters, Size 7 – Common Control Class 8536 Type SJ Series A FIG. 1
Wiring Diagram
This symbol denotes the coil function, provided by a solid-state control module, 30 VA transformer, two fuses in the secondary of the transformer, N.C. electrical interlock and DC magnet coil.
Elementary Diagram
®
46
Type S AC Magnetic Starters Class 8536 3-Phase Additions and Special Features 3-Pole, 3-Phase Magnetic Starters, Size 00 to 4: Class 8536 Type S FIG. 1
* Marked “OL” if alarm contact is supplied Elementary Diagram
Wiring Diagram Form A – Start-Stop Push Button Mounted in Cover FIG. 2
* Marked “OL” if alarm contact is supplied
Wiring Diagram
Elementary Diagram
Form C – Hand-Off-Auto Selector Switch Mounted in Cover FIG. 3
* Marked “OL” if alarm contact is supplied ∆ Single or dual voltage primary connection per transformer nameplate.
Wiring Diagram
∆ Single or dual voltage primary connection per transformer nameplate.
Elementary Diagram
Form F4T – Control Circuit Transformer and Primary Fuses
®
47
Type S AC Magnetic Starters Class 8536 3-Phase Additions and Special Features 3-Pole, 3-Phase Magnetic Starters, Size 00 to 4: Class 8536 Type S FIG. 1
* Marked “OL” if alarm contact is supplied
Elementary Diagram
Wiring Diagram Form S – Separate Control FIG. 2
* Marked “OL” if alarm contact is supplied On NEMA Size 3 and 4 starters, holding circuit contact is in position #1. Max. of 3 external auxiliary contacts on NEMA Size 00. Wiring Diagram
Elementary Diagram Form X – Additional Auxiliary Contacts
3-Pole, 3-Phase Magnetic Starters, Size 5: Class 8536 Type S FIG. 3
∆
* Marked “OL” if alarm contact is supplied ∆ If alarm contact is supplied, a single (3 thermal unit) overload block is furnished, fed from 3 current transformers
Wiring Diagram
Elementary Diagram
Form F4T – Control Circuit Transformer and Primary Fuses
®
48
Type S AC Magnetic Starters Class 8536, 8538 and 8539 3-Phase Additions and Special Features 3-Pole, 3-Phase Magnetic Starters, Size 6 – Separate Control Class 8536/8538/8539 Type SH Form S Series B FIG. 1
Wiring Diagram
This symbol denotes the coil function, provided by a solid-state control module, 30 VA transformer, two fuses in the secondary of the transformer, N.C. electrical interlock and DC magnet coil.
Elementary Diagram
®
49
Type S AC Magnetic Starters Class 8536 3-Phase Additions and Special Features 3-Pole, 3-Phase Magnetic Starters, Size 7 – Separate Control Class 8536 Type SJ Form S Series A FIG. 1
Wiring Diagram
This symbol denotes the coil function, provided by a solid-state control module, 30 VA transformer, two fuses in the secondary of the transformer, N.C. electrical interlock and DC magnet coil.
Elementary Diagram
®
50
Integral Self-Protected Starters Integral 18 State of Auxiliary Contacts State of Auxiliary Contacts for LD1 FIG. 1
LD1
Auxiliary contact actuators
1 3 5 L1 L2 L3
AUTO
+
0
AUTO
+
0
A1 A2
Auxiliary contacts
2
LA1-LB019
LA1-LB017
LA1-LB015
LA1LB001
LA1LB031
LA1-LB034
T1 T2 T3 4 6
Contact open Contact closed
Off
AUTO
On, contactor open
AUTO
On, contactor closed
13 23 31
95 97
13 31
97
13 31
95
41
16 18
16 18
6
8
14 24 32
96 98
14 32
98
14 32
96
42
15 17
15 17
5
7
13 23 31
95 97
13
31
97
13
31
95
41
16 18
16 18
6
8
14 24 32
96 98
14 32
98
14 32
96
42
15 17
15 17
5
7
13 23 31
95 97
13
31
97
13
31
95
41
16 18
16 18
6
8
14 24 32
96 98
14 32
98
14 32
96
42
15 17
15 17
5
7
13 23 31
95 97
13
31
97
13
31
95
41
16 18
16 18
6
8
14 24 32
96 98
14 32
98
14 32
96
42
15 17
15 17
5
7
13 23 31
95 97
13
31
97
13
31
95
41
16 18
16 18
6
8
14 24 32
96 98
14 32
98
14 32
96
42
15 17
15 17
5
7
13 23 31
95 97
13
31
97
13
31
95
41
16 18
16 18
6
8
14 24 32
96 98
14 32
98
14 32
96
42
15 17
15 17
5
7
13 23 31
95 97
13
31
97
13
31
95
41
16 18
16 18
6
8
14 24 32
96 98
14 32
98
14 32
96
42
15 17
15 17
5
7
13 23 31
95 97
13
31
97
13
31
95
41
16 18
16 18
6
8
14 24 32
96 98
14 32
98
14 32
96
42
15 17
15 17
5
7
TRIP. +
Tripped on overload
Tripped on short circuit
Off after short circuit
Manual reset
TRIP. +
TRIP. +
TRIP. +
RESET
®
51
Integral Self-Protected Starters Integral 18 State of Auxiliary Contacts State of Auxiliary Contacts for LD5 FIG. 1
LD5
Auxiliary contact actuators 1 3 5 L1 L2 L3
A1A2
AUTO
+ 0
A1A2
Auxiliary contacts LA1-LB015
2
Contact open Contact closed
T1 T2 T3 4 6
Off
AUTO
On, contactor open
AUTO
On, contactor II closed
AUTO
On, contactor I closed
Tripped on overload
Tripped on short circuit
Off after short circuit
Manual reset
LA1-LB019
LA1-LB017
LA1LB001
LA1-LB021
LA1LB001
On Integral
13 23 31
95 97
13 31
97
13 31
95
41
13 23 31
16 18
41
6
8
14 24 32
96 98
14 32
98
14 32
96
42
14 24 32
15 17
42
5
7
13 23 31
95 97
13
31
97
13
31
95
41
13 23 31
16 18
41
6
8
14 24 32
96 98
14 32
98
14 32
96
42
14 24 32
15 17
42
5
7
13 23 31
95 97
13
31
97
13
31
95
41
13 23 31
16 18
41
6
8
14 24 32
96 98
14 32
98
14 32
96
42
14 24 32
15 17
42
5
7
13 23 31
95 97
13
31
97
13
31
95
41
13 23 31
16 18
41
6
8
14 24 32
96 98
14 32
98
14 32
96
42
14 24 32
15 17
42
5
7
13 23 31
95 97
13
31
97
13
31
95
41
13 23 31
16 18
41
6
8
14 24 32
96 98
14 32
98
14 32
96
42
14 24 32
15 17
42
5
7
13 23 31
95 97
13
31
97
13
31
95
41
13 23 31
16 18
41
6
8
14 24 32
96 98
14 32
98
14 32
96
42
14 24 32
15 17
42
5
7
13 23 31
95 97
13
31
97
13
31
95
41
13 23 31
16 18
41
6
8
14 24 32
96 98
14 32
98
14 32
96
42
14 24 32
15 17
42
5
7
13 23 31
95 97
13
31
97
13
31
95
41
13 23 31
16 18
41
6
8
14 24 32
96 98
14 32
98
14 32
96
42
14 24 32
15 17
42
5
7
13 23 31
95 97
13
31
97
13
31
95
41
13 23 31
16 18
41
6
8
14 24 32
96 98
14 32
98
14 32
96
42
14 24 32
15 17
42
5
7
TRIP. +
TRIP. +
TRIP. +
TRIP. +
RESET
®
52
Integral Self-Protected Starters Integral 32 and 63 State of Auxiliary Contacts State of Auxiliary Contacts for LD4 FIG. 1
LD4
Auxiliary contact actuators 1 3 5 L1 L2 L3 AUTO
+ 0 U
U
A1 A2
Auxiliary contacts T1 T2 T3 2 4 6
Contact open Contact closed LD4
LA1-LC010
LA1-LC012
LA1-LC020
LA1-LC030
98
13 23 31
(63) 53
05
95
14 24 32
54 (64)
08
98
13 23 31
53
14 24 32
05
95
14 24 32
54
13 23 31
08
98
13 23 31
53
14 24 32
05
95
14 24 32
54
13 23 31
08
98
13 23 31
53
14 24 32
05
95
14 24 32
54
96 98
13 23 31
08
98
13 23 31
53
95
14 24 32
05
95
14 24 32
54
06 08
96 98
13 23 31
08
98
13 23 31
53
05
95
14 24 32
05
95
14 24 32
54
16 18
06 08
96 98
13 23 31
08
98
13 23 31
53
14 24 32
15
05
95
14 24 32
05
95
14 24 32
54
13 23 31
16 18
06 08
96 98
13 23 31
08
98
13 23 31
53
14 24 32
15
05
95
14 24 32
05
95
14 24 32
54
13 23 31
16 18
06 08
96 98
13 23 31
08
98
13 23 31
53
14 24 32
15
05
95
14 24 32
05
95
14 24 32
54
13 23 31
16 18
06 08
96 98
13 23 31
08
98
13 23 31
53
14 24 32
15
05
95
14 24 32
05
95
14 24 32
54
13 23 31
16 18
06 08
96 98
13 23 31
14 24 32
15
05
95
14 24 32
13 23 31
16 18
06 08
96 98
13 23 31
14 24 32
15
05
95
13 23 31
16 18
06 08
96 98
14 24 32
15
05
95
13 23 31
16 18
06 08
96 98
14 24 32
15
05
95
13 23 31
16 18
06 08
14 24 32
15
05
13 23 31
16 18
14 24 32
15
13 23 31
08
Off + isolation
Off
On, contactor open AUTO
On, contactor closed AUTO
Tripped, on overload TRIP. +
Off, after overload TRIP. +
Tripped, on short circuit TRIP. +
Off, after short circuit TRIP. +
Manual reset TRIP. +
RESET
®
53
Integral Self-Protected Starters Integral 32 and 63 State of Auxiliary Contacts State of Auxiliary Contacts for LD5 FIG. 1
LD5
Auxiliary contact actuators
1 3 5 L1 L2 L3
AUTO
A2 A1
+ 0 U
A2 A1
U
Auxiliary contacts LA1-LC010
T1 T2 T3 2 4 6
LA1-LC012
LA1-LC020
LA1-LC021
98
13 23 31
13 23 31
53 63
LA1-LC031
13 23 31
16 18
06 08
96 98
13 23 31
14 24 32
15
05
95
14 24 32
05
95
14 24 32
14 24 32
54 64
08
Contact open Contact closed
Off + isolation 13 23 31
16 18
06 08
96 98
13 23 31
08
98
13 23 31
13 23 31
53 63
14 24 32
15
05
95
14 24 32
05
95
14 24 32
14 24 32
54 64
13 23 31
16 18
06 08
96 98
13 23 31
08
98
13 23 31
13 23 31
53 63
14 24 32
15
05
95
14 24 32
05
95
14 24 32
14 24 32
54 64
13 23 31
16 18
06 08
96 98
13 23 31
08
98
13 23 31
13 23 31
53 63
14 24 32
15
05
95
14 24 32
05
95
14 24 32
14 24 32
54 64
13 23 31
16 18
06 08
96 98
13 23 31
08
98
13 23 31
13 23 31
53 63
14 24 32
15
05
95
14 24 32
05
95
14 24 32
14 24 32
54 64
13 23 31
16 18
06 08
96 98
13 23 31
08
98
13 23 31
13 23 31
53 63
14 24 32
15
05
95
14 24 32
05
95
14 24 32
14 24 32
54 64
13 23 31
16 18
06 08
96 98
13 23 31
08
98
13 23 31
13 23 31
53 63
14 24 32
15
05
95
14 24 32
05
95
14 24 32
14 24 32
54 64
13 23 31
16 18
06 08
96 98
13 23 31
08
98
13 23 31
13 23 31
53 63
14 24 32
15
05
95
14 24 32
05
95
14 24 32
14 24 32
54 64
13 23 31
16 18
06 08
96 98
13 23 31
08
98
13 23 31
13 23 31
53 63
14 24 32
15
05
95
14 24 32
05
95
14 24 32
14 24 32
54 64
13 23 31
16 18
06 08
96 98
13 23 31
08
98
13 23 31
13 23 31
53 63
14 24 32
15
05
95
14 24 32
05
95
14 24 32
14 24 32
54 64
13 23 31
16 18
06 08
96 98
13 23 31
08
98
13 23 31
13 23 31
53 63
15
05
95
14 24 32
05
95
14 24 32
14 24 32
54 64
Off
On, both contactors open AUTO
On, contactor
open AUTO
On, contactor
closed AUTO
Tripped on overload TRIP. +
Off, after overload TRIP. +
Tripped on short circuit TRIP. +
Off after short circuit TRIP. +
Manual reset TRIP. +
14 24 32 RESET
®
54
Integral Self-Protected Starters Wiring Diagrams
Integral 18 FIG. 1
FIG. 2
1 3 5 L2 L1 L3
1 3 5 L1 L2 L3
A1 A2
A1 A2
A1 A2
I
T1 2
II
T2 T3 4 6 T1
T2 4
2
T3 6
Self-Protected Reversing Starter w/ Protection Module LB• Integral 18 LD5 LB130 + LB1 LB03P
Self-Protected Starter w/ Protection Module LB• Integral 18 LD1 L80
Integral 32 FIG. 3
FIG. 5
1 3 5 L1 L2 L3
A1 A2
g
( 1 L1
T1 T2 T3 2 4 6
A1
3 L2
)
5 L3
A2
A1
A2
Starter w/ Isolator Integral 32 LD4 FIG. 4 External control circuit
1 3 5 L1 L2 L3
A1 A2
Handle operator Control circuit contact
Instantaneous trip mechanism (Trip coil)
Protection module trip mechanism
T1 T2 T3 2 4 6
Protection module Thermal trip Magnetic trip T1 T2 T3 2 4 6
Reversing Starter w/ Isolator Integral 32 LD5
Starter w/o Isolator Integral 32 LD1
Protection Modules: LB• FIG. 6
FIG. 7
T1 T2 T3 2 4 6
Thermal and Magnetic Trip LB1
T1 T2 T3 2 4 6
Magnetic Trip Only LB6
®
55
Integral Self-Protected Starters Wiring Diagrams
Auxiliary Contact Blocks FIG. 1
LA1 LC010
LA1 LC012
LA1 LC020
13 23 31
13 23 31
13 23 31
14 24 32
14 24 32
14 24 32
9698
98
95
95
0608
08
05
05
Trip signal
1
Short-circuit signal
Knob position signal Auto + O
16
1
Contactor signalling placed on the right
18
15
For LD1 or LD4 and reverser LD5 (mounted on right) LA1 LC010, LA1 LC012 and LA1 LC020 FIG. 2
FIG. 3
LA1 LC030 (63) 53
(63) 53
54 (64)
54 (64)
1 or 2 LA1 LC030
For LD4 w/ isolating contacts (mounted on left) LA1 LC030
Remote Reset Units1 for LD1, LD4 and LD5 FIG. 5 AUTO TRIP + O RESET
AC B4
AC
M
B1
LA1 LC021 13 23 31
LA1 LC031 14 24 32
2
Contactor signalling placed on the left
For reversing LD5 (mounted on left) LA1 LC021
Use of the LA1 LC020 contact block prevents the mounting of trip or remote units
FIG. 6
Interface Modules FIG. 7 AC A1 + E1 - E1 AC A2
C1
A1
A2
D1
LA1 LC180, LA1 LD180
U< C2
D2
FIG. 8 AC A1 + E1 - E1 AC A2
For starter and reverser already fitted with a block, LA1 LC010 or LA1 LC012.
LA1 LC052
Isolating contacts (mounted on left) LA1 LC031
Trip Units for LD1, LD4 and LD5
B2 B3
FIG. 4
2
LA1 LC07••
A1
A2
LA1 LC580, LA1 LD580
®
56
Integral Self-Protected Starters Wiring Diagrams
Add-on Blocks: LA1 LB0•• FIG. 1
Contactor breakers
Trip signal
LA1 LB015 13 23 31
LA1 LB017 13 31
LA1 LB019 13 31
14
24 32
14
14
95
97
97
95
96
98
98
96
32
LA1 LB001 41
32
42
and
For LD1 (mounted on right) FIG. 2
FIG. 3 LA1 - LB034 5 7
6 15
LA1 - LB031
8
Knob position
17
Auto
15 17
Short circuit signal
42
18
Contacts integrated into device
14 24 32
5
7
6
8
Short circuit signal
0 15 17
Signal 16
Contactor breakers
LA1 - LB021 13 23 31
LA1 - LB001 41
Auto
0
Signal
16 18 16 18
For LD1 (mounted on left)
For LD5 (mounted on left)
Time Delay Modules FIG. 4
Control Module
FIG. 5 AC
A1
Knob position
AC
A1
A2
FIG. 6 A2
B2
TSX
AC B1
A1
0
t
0
A1
A2
A/M 1/0
t
A2
A1
A1
K
K
On Module LA4 DT
A2
A2 K
Off Module LA4 DR
Auto-Man-Stop Module LA4 DM
Interface Modules FIG. 7
AC A1
+
-
E1
AC A2
E2
A1
FIG. 8
+
AC A1
-
E1
A1
A2
AC A2
E2
FIG. 9
AC A1
Solid State Module LA4 DW
-
AC A2
E2
A1
A2
A2 K
K
K
+
E1
Relay Module LA4 DF
Relay Module w/ Manual Override LA4 DL
Voltage Converters: LA1 LC080 and LA1 LD080 FIG. 11 Control by supply switching 24 or 48V E1 + A1 DC - (OV) E3
AC
A2
FIG. 12 110V +
A1
DC - (OV) E2
Low voltage control 24 or 48V E1
E1 AC
A2
Supply
FIG. 10
E3 +
{-
A1
DC AC
A2
E2
E2 Low voltage input
For 24 or 48 V Supply
For 110 V Supply
For 24 or 48 V Supply w/ Low Voltage Input
®
57
Type S AC Combination Magnetic Starters Class 8538 and 8539 3-Phase, Size 0-5 (see pages 45 and 49 for Size 6) 3-Pole, 3-Phase Combination Starters: Class 8538 and 8539 Type S FIG. 1
* Marked “OL” if alarm contact is supplied Elementary Diagram
Wiring Diagram Size 0-4 FIG. 2
* Marked “OL” if alarm contact is supplied Elementary Diagram
Wiring Diagram Size 5
®
58
Type S AC Combination Magnetic Starters Class 8538 and 8539 3-Phase Additions and Special Features 3-Pole, 3-Phase Combination Starters w/ Control Circuit Transformer and Primary Fuses: Class 8538 and 8539 Type S Form F4T FIG. 1
L1
L2
L3
2-WIRE CONTROL (If used)
2 START
DISCONNECTING MEANS, PROVIDED BY USER OR WITH CONTROLLER
3
START 1 STOP
2
OL
3 M M
STOP
L1
1
L2
L3
FU2 X2
X1
3-WIRE CONTROL
FU1
SEC
3
1
PRI
FU2
FU1
GROUND (If used)
PRI
X2
M
SEC
3 A
2-WIRE CONTROL
GROUND (If used)
ALARM (IF SUPPLIED)
T1 T2 T3
A
*
MOTOR
T1
L1 L2
OL
COM
1
DISCONNECTING MEANS
2
T2
L3
T3
M
OL
M
OL
M
OL
* Marked “OL” if alarm contact is supplied Elementary Diagram
Wiring Diagram Size 0-4 FIG. 2
L1
L2
L3
2-WIRE CONTROL (If used)
2 START DISCONNECTING MEANS, PROVIDED BY USER OR WITH CONTROLLER
3
START 1 STOP
2
OL
3 CR
STOP
M
CR
1 3-WIRE CONTROL
X2
X1 1
L1
L2
L3
SEC FU2 FU1 FU1
3
PRI
M
X2
M
T1 T2 T3 A
A GROUND (If used)
ALARM (IF SUPPLIED)
* COM
1
L1 L2
OL L3
T1
T2
DISCONNECTING MEANS
SEC 2
MOTOR
GROUND (If used)
CR
3
2-WIRE CONTROL
FU2 PRI
M
OL
M
OL
M
OL
T3
* Marked “OL” if alarm contact is supplied Elementary Diagram
Wiring Diagram Size 5
®
59
Reduced Voltage Controllers Class 8606 Autotransformer Type, Size 2-6 Reduced Voltage Autotransformer Controllers w/ Closed Transition Starting: Class 8606 Size 2-5 FIG. 1
L3
50 0
100 84 65
OL
T1
OL
T2
1S
AT
R 2S
MOTOR AT
2S
1S
R
TR
0
L2
2S
100 84 65 50
L1
CIRCUIT BREAKER OR DISCONNECT SWITCH
R
OL
T3
1S
TR
R
R 1S 1S 2S 2S 2 WIRE CONTROL DEVICE (IF USED) START
STOP
OL
3
2
1
TR
TR
Reduced Voltage Autotransformer Controller w/ Closed Transition Starting: Class 8606 Size 6 FIG. 2
L3
50 0
100 84 65
2S
T1
1OL 1S
AT
R
2CT
T2
2S
MOTOR 2OL AT
2S R
1S 0
L2
1CT
100 84 65 50
L1
CIRCUIT BREAKER OR DISCONNECT SWITCH
R
3CT
T3
3OL 1TR
R
1TR
1S 1S 2TR
2TR 2S R 1S 2S
(H1) PRI
(X1) SEC
(X2)
R (H1)
PRI
(X1)
SEC
(X2)
2 WIRE CONTROL DEVICE (if used) START
STOP 1
GROUND (if used)
3
2
OL 1TR
1TR
®
60
Reduced Voltage Controllers Class 8606 Autotransformer Type, Size 7 Reduced Voltage Autotransformer Controllers w/ Closed Transition Starting: Class 8606 Size 7 FIG. 1
L3
50 0
100 84 65
1CT
T1
2CT
T2
1S
AT
R 2S
MOTOR AT
2S
1S
R
0
L2
2S
100 84 65 50
L1
CIRCUIT BREAKER OR DISCONNECT SWITCH
R
3CT
T3
SOLID STATE OVERLOAD RELAY 1TR
R
(H1) PRI
1TR
(X1) SEC
(X2)
1S 1S 2TR
2TR
(H1) PRI
(X1) SEC
(X2)
2S
R 1S 2S
(H1) PRI
(X1) SEC
(X2)
R (H1)
PRI
(X1)
SEC
(X2)
2 WIRE CONTROL DEVICE (If used) START
STOP 1
GROUND (If used)
3
2
OL 1TR
1TR
®
61
Reduced Voltage Controllers Class 8630 Wye-Delta Type, Size 1Y∆-5Y∆ Wye-Delta Type Reduced Voltage Controllers, Size 1Y∆-5Y∆: Class 8630 FIG. 1
FPO 46-1 110%
Size 1Y∆-5Y∆ Controllers with Open-Transition Starting FIG. 2
FPO 46-2 110%
Size 1Y∆-5Y∆ Controllers with Closed-Transition Starting
®
62
Reduced Voltage Controllers Class 8630 Wye-Delta Type, Size 6Y∆ Wye-Delta Type Reduced Voltage Controllers, Size 6Y∆: Class 8630 FIG. 1
FPO 46-3 110%
Size 6Y∆ Controller with Open-Transition Starting FIG. 2
FPO 46-4 110%
Size 6Y∆ Controller with Closed-Transition Starting
®
63
Reduced Voltage Controllers Class 8640 2-Step, Part-Winding Type Table 5
Motor Lead Connections
Part Winding Schemes 1/2 Wye or Delta 6 Leads 1/2 Wye 9 Leads
[1]
1/2 Delta 9 Leads [1]
[2]
A T1
Lettered Terminals in Panel B C D E F T2 T3 T7 T8 T9
T1
T2
T3
T7
T8
T9
T1
T8
T3
T6
T2
T9
Connect terminals T4, T5 and T6 together at terminal box.
[2]
Part Winding Schemes
Lettered Terminals in Panel B C D E F T2 T9 T7 T8 T3
2/3 Wye or Delta 6 Leads
A T1
2/3 Wye 9 Leads [1]
T1
T2
T9
T7
T8
T3
T1
T4
T9
T6
T2
T3
2/3 Delta 9 Leads
[2]
Connect terminals T4 and T8, T5 and T9, T6 and T7 together in 3 separate pairs at terminal box.
Part-Winding Reduced Voltage Controllers: Class 8640, Size 1PW-7PW FIG. 2
FIG. 1
Size 1PW-4PW, 2-Step Part-Winding Controllers
Size 5PW, 2-Step Part-Winding Controller FIG. 4
FIG. 3
Size 6PW, 2-Step Part-Winding Controller ➀ Disconnect means (optional): 2 required, 1 for each motor winding.
Size 7PW, 2-Step Part-Winding Controller ➁ See Table 5 for motor lead connections.
®
64
Reduced Voltage Controllers Class 8647 Primary-Resistor Type 3-Phase Primary-Resistor Reduced Voltage Controllers: Class 8647, Size 1-7 RES
M
L2
L3
OL
FIG. 2
T1
M L1
DISCONNECT MEANS (OPTIONAL)
L1
A RES
M
OL
T2 L2
MOTOR A RES
M
OL
T3 L3
DISCONNECT MEANS (OPTIONAL)
FIG. 1
RES
OL
T1
RES
OL
T2
A M
MOTOR
A RES
M
OL
T3
A
A
TR
A
TR M
M
TR
TR A
A
2 WIRE CONTROL DEVICE (if used)
2 WIRE CONTROL DEVICE (if used)
START
STOP 1
3
2
START
STOP
OL
1
TR
TR
Size 5
L3
1CT
RES A
M
2CT
M L1
T2 MOTOR
A
L2
2OL 3CT
RES A
F U 2
T1
1OL RES
M
FIG. 4
T3 L3
3OL
F U 3
DISCONNECT MEANS (OPTIONAL)
L2
DISCONNECT MEANS (OPTIONAL)
M L1
1TR
M
1CT
T1
RES
2CT
T2 MOTOR
A M
RES
3CT
T3
A SOLID STATE OVERLOAD RELAY
F U 3 1TR
2TR
RES A
F U 2
1TR
TR
TR
Size 1-4 FIG. 3
OL
3
2
1TR 2TR
2TR
2TR
M
(H1) PRI
M A
(X1) SEC
(H1) PRI
(X1) SEC
M
M
(X2)
A
(H1) PRI
A (H1)
PRI
FU1 (X1)
SEC
(X1) SEC (X2)
(X2)
A
2 WIRE CONTROL DEVICE (if used)
(H1)
PRI
FU1 (X1)
SEC
GROUND (if used)
START
STOP 1
(X2)
3
2 1TR
OL 1TR
(X2)
2 WIRE CONTROL DEVICE (if used) START
STOP 1
GROUND (if used)
3
2
OL 1TR
1TR
Size 6
Size 7
®
65
Reduced Voltage Controllers Class 8650 and 8651 Wound-Rotor Type Wound-Rotor Reduced Voltage Controllers: Class 8650 and 8651 FIG. 1
FPO 49-3 135%
Non-Reversing Wound-Rotor Motor Controller w/ 3 Points of Acceleration Class 8650 FIG. 2
FPO 49-4 135%
Reversing Wound-Rotor Motor Controller w/ 3 Points of Acceleration Class 8651
®
66
Solid State Reduced Voltage Starters Class 8660 ®, Type MD-MG ALPHA PAK ALPHA PAK® Solid State Reduced Voltage Starters: Class 8660 Type MD-MG FIG. 1
1CT
CIRCUIT BREAKER OR DISCONNECT SWITCH
M L1
L2
L3
T1
T2
M
MOTOR
3CT
M
T3
SOLID STATE OVERLOAD RELAY TO 120 V SEPARATE CONTROL STOP
START OT*
* OT is a switch that opens when an overtemperature condition exists (Type MFO and MGO only)
M
M
Type MD (16 A), ME (32 A), MF (64 A) and MG (128 A)
L1
L2
L3
CIRCUIT BREAKER OR DISCONNECT SWITCH
FIG. 2
ISO
M
ISO
M
1CT
T1
T2
MOTOR
ISO
3CT
M
T3
SOLID STATE OVERLOAD RELAY TO 120 V SEPARATE CONTROL STOP
START OT* M
M CR
* OT is a switch that opens when an overtemperature condition exists (Type MFO and MGO only)
TR
TR ISO
ALARM CR
Type MD (16 A), ME (32 A), MF (64 A) and MG (128 A) w/ Isolation Contactor
®
67
Solid State Reduced Voltage Controllers Class 8660 Type MH, MJ, MK and MM Solid State Reduced Voltage Controllers: Class 8660 Type MH, MJ, MK and MM FIG. 1
Type MH (200 A), MJ (320 A), MK (500 A) and MM (750 A) FIG. 2
Type MH (200 A) w/ Shorting Contactor FIG. 3
Type MJ (320 A), MK (500 A) and MM (750 A) w/ Shorting Contactor
®
68
Solid State Reduced Voltage Controllers Class 8660 Type MH, MJ, MK and MM Solid State Reduced Voltage Controllers: Class 8660 Type MH, MJ, MK and MM FIG. 1
FPO 51-1 130%
Type MH (200 A) w/ Isolation Contactor FIG. 2
FPO 51-2 130%
Type MJ (320 A), MK (500 A) and MM (750 A) w/ Isolation Contactor
®
69
Solid State Reduced Voltage Controllers Class 8660 Type MH, MJ, MK and MM Solid State Reduced Voltage Controllers: Class 8660 Type MH, MJ, MK and MM FIG. 1
FPO 51-3 130%
Type MH (200 A) w/ Isolation Contactor and Shorting Contactor FIG. 2
FPO 51-4 130%
Type MJ (320 A), MK (500 A) and MM (750 A) w/ Isolation Contactor and Shorting Contactor
®
70
Type S AC Reversing Magnetic Starters Class 8736 2- and 3-Pole Reversing Starters, 2- and 3-Pole, Size 00-1: Class 8736 Type S
FPO 52-1
FIG. 1
FPO 52-1 * Marked “OL” if alarm contact is supplied Elementary Diagram
Wiring Diagram 2-Pole, w/ Single Phase, 3-Lead Motor FIG. 2
FPO 52-2 * Marked “OL” if alarm contact is supplied
FPO 52-2 Elementary Diagram
Wiring Diagram
3-Pole, w/ Single Phase, 4-Lead Repulsion-Induction Motor
FPO 53-1
FIG. 3
FPO 53-1 * Marked “OL” if alarm contact is supplied Wiring Diagram
Elementary Diagram
3-Pole, w/ Single Phase, 4-Lead Capacitor or Split-Phase Motor
®
71
Type S AC Reversing Magnetic Starters Class 8736 3- and 4-Pole Reversing Starters, 3- and 4-Pole: Class 8736 Type S FIG. 1
FPO 53-2
FPO 53-2
* Marked “OL” if alarm contact is supplied Elementary Diagram
Wiring Diagram Size 00-2, 4-Pole, 2-Phase FIG. 2
FPO 53-3 * Marked “OL” if alarm contact is supplied
FPO 53-3 Elementary Diagram
Wiring Diagram Size 00-4, 3-Pole, 3-Phase FIG. 3
FPO 54-1 FPO 54-1 Elementary Diagram
Wiring Diagram Size 5, 3-Pole, 3-Phase
®
72
Type S AC 2-Speed Magnetic Starters Class 8810
Starters for 2-Speed, 2-Winding (Separate Winding), 3-Phase Motors: Class 8810 Type S
FPO 54-2
FIG. 1
FPO 54-2 Elementary Diagram
Wiring Diagram Size 0-4 FIG. 2
FPO 54-3 Size 5 Wiring Diagram
Starters for 2-Speed, 1-Winding (Consequent Pole), Constant or Variable Torque, 3-Phase Motors: Class 8810 Type S
FPO 55-1
FIG. 3
FPO 55-1 * Marked “OL” if alarm contact is supplied Elementary Diagram
Wiring Diagram Size 0-2
®
73
Type S AC Reversing Magnetic Starters Class 8810
Starters for 2-Speed, 1-Winding (Consequent Pole), Constant or Variable Torque, 3-Phase Motors: Class 8810 Type S FIG. 2
FIG. 1
FPO 55-3
FPO 55-2 * Marked “OL” if alarm contact is supplied
Size 5 Wiring Diagram
Size 3 and 4 Wiring Diagram
Starters for 2-Speed, 1-Winding (Consequent Pole), Constant Horsepower, 3-Phase Motors: Class 8810 Type S
FPO 55-4
FIG. 3
FPO 55-4 * Marked “OL” if alarm contact is supplied Elementary Diagram
Wiring Diagram Size 0-2 FIG. 4
FIG. 5
FPO 56-2 75%
FPO 56-1 75% * Marked “OL” if alarm contact is supplied Size 3 and 4 Wiring Diagram
* Marked “OL” if alarm contact is supplied Size 0, w/ High-Off-Low Selector Switch (Form C7) Wiring Diagram
®
74
2-Speed Magnetic Starters Class 8810 Special Control Circuits Form R1
Form R2
FIG. 1
FIG. 2
FPO 57-1
FPO 57-2
Compelling Relay, Requiring Motor Starting in Low Speed
Accelerating Relay, Providing Timed Acceleration to Selected Speed
Form R3
Form R2R3 FIG. 4
FIG. 3
FPO 57-3 FPO 57-4 Accelerating Relay and Decelerating Relay
Decelerating Relay, w/ Time Delay During Transfer from Higher to Lower Speed
Form R1R3 FIG. 5
Form A10C
FPO 57-5
FIG. 6
FPO 57-6 Compelling Relay and Decelerating Relay
Hand-Off-Auto Selector Switch and High-Low Push Button
Form CC17
Form A10CR1
FIG. 7
FIG. 8
FPO 57-7 Hand-Off-Auto Selector Switch and High-Low Selector Switch
FPO 57-8 Hand-Off-Auto Selector Switch and High-Low Push Button w/ Compelling Relay/Timer
®
75
2-Speed Magnetic Starters and Multispeed Motor Connections Class 8810 Special Control Circuits and 1- and 3-Phase Motor Connections Form C25
Form CC17 R2R3
FIG. 1
FIG. 2
FPO 57-10 120% FPO 57-9
Hand-Off-Auto Selector Switch and High-Low Selector Switch w/ Accelerating and Decelerating Relay/Timer
High-Low-Off-Auto Selector Switch
Multispeed Motor Connections: 1-Phase, 2-Speed Motors FIG. 3
T1
T2
T3
FIG. 4
T4
T1
T2
T3
FIG. 5
T4
COM
A
B
Speed
L1
L2
Open
Together
Speed
L1
L2
Open
Together
Speed
L1
L2
Open
Together
Low High
T1 T3
T2 T4
T3,T4 T1,T2
— —
Low High
T3 T1
T4 T2
T1,T2 T3,T4
— —
Low High
COM COM
A B
B A
— —
2 Windings FIG. 6
T1
2 Windings
COM
FIG. 7
T4
T1
1 Winding
COM
FIG. 8
T4
T1
COM
T4
Speed
L1
L2
Open
Together
Speed
L1
L2
Open
Together
Speed
L1
L2
Open
Together
Low High
COM COM
T1 T4
T4 T1
— —
Low High
T1 T1
T4 COM
COM —
— T1,T4
Low High
T1 T1
COM T4
— COM
T1,T4 —
1 Winding
1 Winding
1 Winding
Multispeed Motor Connections: 3-Phase, 2-Speed Motors FIG. 9
FIG. 10
T4 T3
FIG. 11
T4
T1
T3
T4
T1
T1
T3 T5 Speed
L1
L2
L3
Low High
T1 T6
T2 T4
T3 T5
Open
Together
— T4,T5,T6 All others —
1 Winding, Constant Horsepower FIG. 12
T1
T3 Speed Low High
L1
L2
T13 L3
T1 T2 T3 T11 T12 T13
Separate Windings
Speed
L1
L2
L3
Low High
T1 T6
T2 T4
T3 T5
T12 Open All others All others
T6 Open
Together
All others — — T1,T2,T3
T3 Speed Low High
T2 L1
L2
T13 T17 L3
T1 T2 T3 T11 T12 T13,T17
Separate Windings
T6
Speed
L1
L2
L3
Low High
T1 T6
T2 T4
T3 T5
Open
Together
All others — — T1,T2,T3
1 Winding, Variable Torque FIG. 14
T11
T1
T2
T5
1 Winding, Constant Torque FIG. 13
T11
T2
T2
T5
T6
T2
T12
T1
T3
T11
T2 T13
T7
Open
Speed
All others All others
Low High
L1
L2
T1 T2 T11 T12
T12
L3
Open
T3,T7 T13
All others All others
Separate Windings
®
76
Multispeed Motor Connections 3-Phase
Multispeed Motor Connections: 3-Phase, 2-Speed Motors FIG. 1
T1
FIG. 2
T11
T1
FIG. 3
T5
T11
T1
T2 T4
T4
T2
T14
L3
L2
T12
T6 T3
T7
T2 T13 T17
Speed
L1
Low High
L2
T12
L3
Open
T1 T2 T3,T7 T11 T12 T13,T17
T3
T3 Speed
All others All others
L1
Low High
Separate Windings
L3
T1 T1,T5
L2
L4
Open
T5 T2 T6 T3 T2,T6 T4
T13
Speed L1 Low High
T3,T4 —
2-Phase, 1 Winding, Variable Torque
L4
Open
T1 T3 T2 T4 All others T11 T13 T12 T14 All others
2-Phase, Separate Windings
Multispeed Motor Connections: 3-Phase, 3-Speed Motors FIG. 4
T4
FIG. 5
T11
T4
T3 T1
T7
L1
Low 2nd High
L2
L3
T12
Open
Together
Speed L1 Low 2nd High
T1
L1
Low 2nd High
T13
T12
L3
Open
Together
Speed
T3 T5 T13
All others All others All others
— T1,T2,T3 —
Low 2nd High
T6
L2
T1 T2 T6 T4 T11 T12
Together
2 Windings, Variable Torque
L1
L2
T1 T2 T11 T12 T6 T4
Together
2 Windings, Constant Torque FIG. 9
T14
T1
T11
T13 T3
T13
T12
L3
Open
Together
Speed
T3 T13 T5
All others All others All others
— — T1,T2,T3
Low 2nd High
T6
T16
Open
Low T1 T2 T3 All others — 2nd T11 T12 T13,T17 All others — High T16 T14 T15 All others T11,T12,T13,T17
T11
T2
T5
T11
T12
T15
L3
T1
T3
T2
Open
T4
T11
T3
L3
T2
Speed L1 L2
T1 T2 T3,T7 All others — T11 T12 T13 All others — T6 T4 T5 All others T1,T2,T3,T7
FIG. 8
T4
T5
L2
T3
T12
2 Windings, Constant Torque
2 Windings, Constant Torque
Speed
T13 T17
T6 T13
T2
T5
T1 T2 T3,T7 All others — T6 T4 T5 — T1,T2,T3,T7 T11 T12 T13 All others —
FIG. 7
T14
T1
T1
T7 T6 T13
T2
T5 Speed
FIG. 6
T11
T3
2 Windings, Variable Torque
L1
T2
T15
L2
L3
T1 T2 T11 T12 T16 T14
T3 T13 T15
T12
T16
Open
Together
All others — All others — All others T11,T12,T13
2 Windings, Variable Torque
Multispeed Motor Connections: 3-Phase, 4-Speed Motors FIG. 10
T4 T3
FIG. 11
T14 T1
T13
T4
T11
FIG. 12
T14
T3
T1
T13
T4
T14 T13
T3
T11
T1
T7
T7 T2
T5 Speed Low 2nd 3rd High
L1
L2
T6 L3
T1 T2 T3 T6 T4 T5,T7 T11 T12 T13 T16 T14 T15,T17
T15 T17 T12 Open
T16
Speed
All others T4,T5,T6,T7 All others — All others T14,T15,T16,T17 All others —
T4 T1
T7 T2
T5
Low 2nd 3rd High
T15 T17 T12
T6 L3
Open
T1 T2 T3 T11 T12 T13 T6 T4 T5,T7 T16 T14 T15,T17
T16
Speed
All others T4,T5,T6,T7 All others T14,T15,T16,T17 All others — All others —
T4
T2
T5
Together
L1
Low 2nd 3rd High
2 Windings, Constant Horsepower FIG. 14
T14
L2
T6
L2
L3
T12
T15 Open
T16 Together
T1 T2 T3,T7 All others — T6 T4 T5 All others T1,T2,T3,T7 T11 T12 T13,T17 All others — T16 T14 T15 All others T11,T12,T13,T17
2 Windings, Constant Torque FIG. 15
T14
T4
T14
T13
T3
Speed
L1
Low 2nd 3rd High
2 Windings, Constant Horsepower FIG. 13
T7 T2
T5
Together
T11
T17
L1
L2
T11
T17 T6 L3
T15 Open
T1
T3 T12
T16 Together
T1 T2 T3,T7 All others — T11 T12 T13,T17 All others — T6 T4 T5 All others T1,T2,T3,T7 T16 T14 T15 All others T11,T12,T13,T17
2 Windings, Constant Torque
T5 Speed Low 2nd 3rd High
T2 L1
T6 L2
T11
T13
L3
T1 T2 T3 T6 T4 T5 T11 T12 T13 T16 T14 T15
T15
T12
T16
T5
Open
Together
Speed
All others All others All others All others
— T1,T2,T3 — T11,T12,T13
Low 2nd 3rd High
2 Windings, Variable Torque
T1
T3 T2 L1
T6 L2
T11
T13
L3
T1 T2 T3 T11 T12 T13 T6 T4 T5 T16 T14 T15
T15
T12
T16
Open
Together
All others All others All others All others
— — T1,T2,T3 T11,T12,T13
2 Windings, Variable Torque
®
77
Programmable Lighting Controllers Class 8865
Programmable Lighting Controller: Class 8865 Type TC12 FIG. 1
CIRCUIT 12 CIRCUIT 9 CIRCUIT 8
RELAY OUTPUT CONNECTIONS CIRCUITS 7-12
CIRCUIT 11 CIRCUIT 10
35
CIRCUIT 7
18
19
17
20
16
CIRCUIT 6
21
15
22
14
23
13
CIRCUIT 5
24
12
25
11
26
10
CIRCUIT 4
27
9
28
8
29
7
30
6 CIRCUIT 3
RELAY OUTPUT CONNECTIONS CIRCUITS 1-6
31
5
32
4
CIRCUIT 2
33
3
34
2
CIRCUIT 1
1
INPUTS
Demand Input
36
+1– +2– +3– +4– +5– +6– +7– +8–
24 VAC INPUT
®
78
AC Lighting Contactors Class 8903 Load Connections Load Connections for AC Lighting Contactors: Class 8903 FIG. 1
FIG. 2
L1
L2
L2
L1
IF USED
LOAD LOAD
IF USED
LOAD
LOAD
Vload = Vline-tol-line
Vload L2 = Vline-to-lineLN
L1 1-Phase, 2-Wire, Single Load FIG. 3
L1
L2
1-Phase, 2-Wire, Multiple Loads FIG. 4
LN
L1
L2
IF USED
LN
IF USED
LOAD LOAD Vload = Vline-to-neu-
LOAD Vload = Vline-to-line
1-Phase, 3-Wire, Loads Connected Line-to-Neutral FIG. 5
L1
L2
1-Phase, 3-Wire, Load Connected Line-to-Line FIG. 6
L3
LOAD
L1
L2
LOAD
L3
LOAD
LOAD LOAD Vload = Vline-to-line L1
L2
1.732
L3
Vload = Vline-to-line LN
3-Phase, 3-Wire, Wye-Connected Load FIG. 7
L1
L2
L3
LOAD Iload = Icontacts 1.732
3-Phase, 3-Wire, Delta-Connected Load
LN
LOAD
IF USED
LOAD LOAD Vload = Vline-to-neu-
Application Limits: 1. Voltage between line side conductors must not exceed line-to-line voltage rating of contactor. 2. Vload must not exceed volts-per-load rating of contactor. 3. Line current carried by any contact must not exceed ampere rating of contactor. For contact ratings, refer to the Square D Digest.
3-Phase, 4-Wire, Loads Connected Line-to-Neutral
®
79
AC Lighting Contactors Class 8903 Control Circuit Connections Control Circuit Connections for Electrically-Held Contactors: Class 8903 Type L and S FIG. 1
ON
OFF To AC common or separate control supply
COIL
FIG. 4
M
On-Off Push Button (Form A12) FIG. 2
2-WIRE PILOT DEVICE
A1 A2
COIL
I I HAND OFF AUTO
To AC common or separate control supply
A1 A2
A1
To AC common or separate control supply
Direct Control from Pilot Device FIG. 3
COIL
2-WIRE PILOT DEVICE
A2
I I ON OFF
COIL
A1
To AC common or separate control supply
A2
On-Off Selector Switch (Form C6)
Hand-Off-Auto Selector Switch (Form C)
Control Circuit Connections for Mechanically-Held Contactors: Class 8903 Type LX and S FIG. 5
COIL CLEARING CONTACTS (Supplied)
ON
FIG. 6
A1 A2
LATCH
I ON OFF
LATCH
14
17
14
A OFF
UNLATCH 15
18
A2
To AC common or separate control supply
On-Off Push Button (Form A3)
B
On-Off Selector Switch (Form C6) COIL CLEARING CONTACTS (Supplied)
FIG. 8
1-POLE PILOT DEVICE
CR
CR
LATCH
COIL CLEARING CONTACTS (Supplied)
LATCH 14
17 A
To AC common or separate control supply
A UNLATCH 15
B
2-POLE PILOT DEVICE
17
A1 18
To AC common or separate control supply
FIG. 7
COIL CLEARING CONTACTS (Supplied)
I
14
UNLATCH 15
Control from 2-Pole Pilot Device
17 A
18 B
CR To AC common or separate control supply
UNLATCH 15
18 B
1-Pole Pilot Device w/ CR relay (Form R6)
®
80
AC Lighting Contactors and Electronic Motor Brakes Class 8903 and 8922
Panelboard Type Wiring: Class 8903 Type PB, 30-225 A FIG. 1
FIG. 3
FIG. 4
L1
L2/N
O
ON
ON
Control Circuit – Standard
O
CR1 CR2
CR2
L2/N
CR1
CR
+
L
C
Control Circuit – 2-Wire Control (Form R6)
–
SC L = Line (common) O = Open (unlatch) C = Close (latch)
C
L1
BR
SO
O
CR
T3
O
L1
L
CR
T2
L
C OFF
FIG. 2 2-Wire Pilot Device
T1
L2/N
C
L1
L3
C
L OFF
L2
Control Circuit – Long-Distance Control (Form R62)
Omit middle pole for 2-pole unit
Power Circuit
QWIK-STOP® Electronic Motor Brake: Class 8922 FIG. 5
CUSTOMER CONTROL CIRCUIT F1
F1 ETB 10/18 15 18 Xo
START OL M
Xo
M
OL
T1
F2
M
OL
T2
F2
M
OL
T3
L2
[1]
STOP
F2 L1
MOTOR
L3
+
M
24 VDC
–
M
F3
[3]
ETB 10/18 [2]
F3
[3]
L1
L+
L2
L–
[4]
[1] Contacts 15 and 18 close when
L1 and L2 are energized.
PLC
[2] When controlling electronic motor brake
ETB 10/18 with a PLC (programmable logic control), terminals Xo-Xo must be jumpered.
B– B1
[3] Semiconductor fuses.
B+
[4] Connection for ETBS only.
POWER CIRCUIT
Type ETB10, ETB18 and ETBS18 w/ Internal Braking Contactor FIG. 6 CUSTOMER CONTROL CIRCUIT F1
F1 ETB 20/800
B
STOP
START OL
T1
F2
M
OL
T2
F2
M
OL
T3
MOTOR
+
24 VDC
M B
Xo
OL
L3
M M 25 28
M
L2
[1]
15 18
F2 L1
–
F3
[3]
ETB 20/800
Xo F3
M PLC
[2]
[3]
L1
L+
B
L2
L–
B
[4]
[1] Contacts 15 and 18 close when L1 and L2 are energized. [2] When controlling electronic motor brake ETB 20/800 with a PLC
B– B1
(programmable logic control), terminals Xo-Xo must be jumpered. [3] Semiconductor fuses. [4]
B+ POWER CIRCUIT QWIK-STOP is a registered trademark of Square D.
Connection for ETBS only.
Type ETB20-ETB800 and ETBS20-ETBS800
®
81
Electronic Motor Brakes, Duplex Motor Controllers and Fiber Optic Transceivers Class 8922, 8941 and 9005
QWIK-STOP® Electronic Motor Brake: Class 8922 Type ETBC FIG. 1
CUSTOMER CONTROL CIRCUIT
F1
F2
M
OL
T1
F2
M
OL
T2
F2
M
OL
T3
L1 F1 L2
1 2
L3
[1]
3
MOTOR
M START
4 5
ETBC
M M
F3
[2]
L1
B
T1/2
L2
B
T2/4
[1] To control electronic motor
PLC
9
+
B– 10
–
B+
[2]
M
6 7
F3
OL
STOP
24 VDC INPUT
brake ETBC with input B+/B–, terminals 3 and 4 must be jumpered. [2] Semiconductor fuses.
QWIK-STOP is a registered trademark of Square D.
Type ETBC
AC Duplex Motor Controller: Class 8941 FIG. 2
Fiber Optic Transceiver: Class 9005 FIG. 3 14
OUTPUT 12 11
POWER
86 GAIN ADJ. SCREW
GAIN OUTPUT STATUS LED
SETUP LED SETUP
OUTPUT
FIBER RELEASE
FIBER RELEASE LEVER
FIBER A1
Elementary Diagram for Duplex Motor Controller w/ Electric Alternator
INPUT
A2
Transceiver, Front View FIG. 4
HAZARDOUS LOCATIONS CLASS I GROUPS A, B, C & D CLASS II GROUPS E, F & G CLASS III
NONHAZARDOUS LOCATIONS
FIBER OPTIC TRANSCEIVER
FIBER OPTIC PUSH BUTTON, SELECTOR SWITCH, LIMIT SWITCH, ETC. FIBER OPTIC CABLE
CLASS 9005 TYPE FT FIBER OPTIC CABLE ELECTRICAL CONNECTIONS BOUNDARY SEAL TO BE IN ACCORDANCE WITH ARTICLE 501-5 OF THE NATIONAL ELECTRICAL CODE
Location
®
82
Photoelectric and Inductive Proximity Switches Class 9006
Photoelectric Switches: Class 9006 Type PE1 (Obsolete) FIG. 1
FIG. 2 AC thru-beam emitter has no output switching capability, therefore leakage current is not applicable. Thru-beam emitter is connected directly across the AC line and typically draws 15 mA.
Connect load in series. To prevent damage, all switches except emitters must have load connected to switch.
2-Wire AC, Single Device Operation
AC Emitter
FIG. 3
FIG. 4 DC thru-beam emitter has no output switching capability, therefore it requires only a 2-wire cable connected directly across the DC. Thru-beam emitter draws a maximum of 45 mA.
DC switches cannot be wired in series. To prevent damage, all switches except emitters must have load connected to switch.
4-Wire DC, Single Device Operation, 10-30 VDC, 250 mA Max. Load
DC Emitter
Photoelectric Switches: Class 9006 Type PE6 and PE7 (Obsolete)
Photoelectric Switches: Class 9006 Type PEA120 (Obsolete)
FIG. 5
FIG. 8
12-24 VDC, Sinking (NPN) FIG. 6
These switches are light operated only.
12-24 VDC, Sourcing (PNP)
Beam broken = load deenergized Beam unbroken = load energized
FIG. 7
Diagram shows contact arrangement with beam broken. 120 VAC, Emitter Only
120 VAC Amplifier
Inductive Proximity Switches: Class 9006 Type PS (Obsolete) FIG. 9
FIG. 10
2-Wire AC, N.O. FIG. 12
FIG. 11
2-Wire AC, N.C. FIG. 13
2-Wire DC, N.O.
2-Wire AC, N.O. or N.C. FIG. 14
4-Wire DC, Sinking (NPN)
4-Wire DC, Sourcing (PNP)
®
83
Inductive Proximity Sensors XS, XSC, XSF and XSD
XS Tubular Inductive Proximity Sensors FIG. 1
+/–
BN/3
FIG. 2
for connector version only BN/2
NO BU/4
–/+ BU/3
2-Wire DC, Non-Polarized FIG. 3
BN/1
FIG. 5
BN/1
+
PNP
BK/4 NO BK/2 NC
NO NC
NO –
BU/3 BN/1
BN/1
–
3-Wire DC, N.O. or N.C.
WH/2 – BU/3 (NO), BN/1 (NC) +
NC
BU/3
+
BK/4
PNP
–
NO
NO
BK/4
NPN
BK/2 NC BK/4 NO
BN/1 (NO), BU/3 (NC)
+
BU/3
+
NPN
L2 –/+
2-Wire AC/DC FIG. 4
PNP
L1 +/– AC/DC
BU/3
+
NPN
BK/4
BK/4
WH/2
–
– BN/1 (NO), BU/3 (NC)
3-Wire DC, N.O. and N.C., Complementary
3-Wire DC, Selectable PNP/NPN, N.O./N.C.
XSC Rectangular Inductive Proximity Sensors FIG. 6
+/–
3
FIG. 7
5
FIG. 8
L1
FIG. 9
5
1 PNP
AC/DC NO
NC
4
–/+
3
+/–
4
–/+
NO 6
NO 7 8
L2
8 BK 5
L1
6
L2
5 AC/DC
NC
NC 7
7 BK
2-Wire AC, Programmable
2-Wire DC, Non-Polarized
NO NC
6
2
3
–
1 NPN
+ NO
6
NC
8
3
2-Wire AC/DC, Programmable
+
4
4 2
–
3-Wire DC, N.O. or N.C.
XSF Rectangular Inductive Proximity Sensors FIG. 11
FIG. 10 1 NO
NC
L1
1 PNP
4 NO NC
+
2
2
L2
3
–
1
L1
1 NPN
+
4
L2
NO NC 3
2-Wire AC, Programmable N.O. or N.C.
4 2
–
3-Wire DC, N.O. or N.C.
XSD Rectangular Inductive Proximity Sensors FIG. 13
FIG. 12 3 NO
FIG. 14
+/–
4
–/+
3
+/–
NO 7
NC
4
8
–/+
NC 7
NO
2 –
1 NPN
+ NO
L2
2-Wire AC, Programmable N.O. or N.C.
+
3
NC 3
2-Wire DC, Non-Polarized
4 NC
L1
LOAD 8
1 PNP
4 2
–
3-Wire DC, N.O. or N.C.
®
84
Inductive and Capacitive Proximity Sensors XS and XTA
A AA
XS Tubular Inductive Proximity NAMUR Sensors
ed to a solid state in ut (e.g. : ST1 CC/CS, TSX DET 466) Ri = 1K BN-1 + Object + present 7...12V DC
_
FIG. 1
Object absent
BU-2
-
BN-1
+
BU-2
-
I < 1mA Ri = 1K
FIG. 2
Wiring diagram
-
+
+ BN
+
proximity sensor
_
1
BU
-
(110...240 V) (110...240V) ACHzP= AC P = 5 VA, 50
XZD
7...12V DC I > 3mA
A 2
}
4 2.F 2.0 1.+
Non-Intrinsically Safe Applications (Normal Safe Zone), Connected to a Solid State Input
With XZD Power Supply/Relay Amplifier Unit
XS Inductive Proximity Sensors w/ Analog Output FIG. 3
FIG. 4
Output current @ 24 V: 0-10 mA 0-16 mA @ 48 V: 0-10 mA
Value of Load R (max.) 1800 Ω 1125 Ω 4200 Ω
Output current @ 24 V: 4-14 mA 4-20 mA @ 48 V: 4-14 mA
2-Wire DC
FIG. 5
Value of Load R (max.) 640 Ω 450 Ω
These sensors may be wired in the 2- or 3-wire mode, depending on the current output characteristics required.
2350 Ω
3-Wire DC
XTA Tubular Capacitive Proximity Sensors
, BN BU
FIG. 6
BN
L1 L2
PNP
BN
+ NPN
BK
+ BK
Gn* BU
* Ground for XTA A115 only 2-Wire AC
-
BU
-
3-Wire DC
®
85
Magnet Actuated Proximity Sensors and Photoelectric Sensors SG, ST and XUB
SG Magnet Actuated Proximity Sensors, Surface Mount Style FIG. 1
FIG. 2
L2
L1
FIG. 3
L2
L1
Black
Red
LOAD
LOAD
White
SGA 8016, SGA 8031, SGA 8182, SGA 8053, SGA 8176, SGA 8177, SG0 8168 and SG08239
SGB 8175
LOAD LOAD
SG2 8195
SG Magnet Actuated Proximity Sensors, Limit Switch Style FIG. 4
FIG. 5
L2
L1
FIG. 6
L2
L1
NO Com
LOAD
LOAD
NC
SG0 8003, SG1 8004, SGA 8005 and SGA 8040 FIG. 7
+
+
SG0 L8003 and SG1 L8004 FIG. 8
Com
–
+
+
SG1 8056 is normally closed. Connect red terminal (+) to power source. Connect minus (-) terminal to load. Housing must be connected to minus.
LOAD
SG0 B8114, SG1 B8147, SG0 BL8114, SG0 BL8147 and SGC 8142-T-P
LOAD
SGC 8027 and SGC 8025
-
L
LOAD
LOAD
SG0 8079 and SG1 8056
SG Magnet Actuated Proximity Sensors, Tubular Style FIG. 9
FIG. 10
L2
L1
NO
LOAD
Com
LOAD
LOAD
NC
SGC 8058 and SGC 8181
SGA 8057, SGA 8189, SGA 8072, SGA 8179, SGA 8180 and SGA 8038
SG Magnet Actuated Proximity Sensors, Maintained Contact FIG. 11
FIG. 12
L2
L1
L1
LOAD
2
1
6.8k
SGA 8018, SGO 8026
L2 LOAD
3
SGO 8110
ST Grounded Probe Switch FIG. 13
FIG. 14 Blk Gnd Wht Red
L1
L2
LOAD
hot
1 L1 hot housing
neutral
Target connected to ground
2
3
4
Not used
L2 LOAD neutral
Target connected to ground. Housing must be grounded for proper operation.
Cable Wiring
ST switches may be wired in series or parallel. For series operation, connect red lead (terminal 4) to black lead (terminal 1) of other switch. The voltage drop across each switch (in the closed state) does not exceed 2 VAC.
Terminal strip Wiring
XUB Short Range Tubular Photoelectric Sensors FIG. 16
FIG. 15
2-Wire AC
FIG. 17
AC Emitter
DC Emitter
®
86
Photoelectric Sensors XUM, XUH, XUG, XUL and XUJ
XUM Miniature High Performance Photoelectric Sensors FIG. 1
+ Light
Prog.
FIG. 2
FIG. 3
Test W
OG
- Dark
BN BK
J
BN BK
H
LOAD
LOAD
+ Light
Prog .
OG Test
LOAD
BU
BU W
XUH and XUG Medium Range Photoelectric Sensors
LOAD
- Dark
NPN Output
PNP Output
5-Wire AC
XUL Subcompact Photoelectric Sensors FIG. 4
Emitter DC
FIG. 5
Connector, PNP output BN 1 4
BU
3 Prog.
2
Emitter
+ light - dark
DC 3 wire Connector, NPN output
PNP output
Prog.
2
+ light
+ light
BK
DC connector
NPN output BN
1 + light - dark
AC/DC OG RD
+
BK BU OG
AC/DC
Relay output AC/DC versions
- dark
- dark
Prog.
BU
4 3
BU OG
AC/DC
1
BN BK
Prog.
BN
2 prog.
BU
BN
AC/DC
4 Output –
DC
AC/DC
XUJ Compact High Performance Photoelectric Sensors FIG. 7
FIG. 6
FIG. 8
FIG. 9 1 Dark 2 Light 3
– NPN
– or
+ +
4
+ PNP
1 kΩ
5-Wire Relay, AC/DC
AC/DC Microchange DC Connector
5
6
DC Output
LOAD
Test
DC Output Microchange DC Connector
®
87
Photoelectric Sensors and Security Light Barriers XUE, XUR, XUD, XUG and XUE S
XUE Long Range Plug-In Photoelectric Sensors FIG. 1
FIG. 2
FIG. 3
XUE A
DC Emitter
XUE H, NPN
FIG. 5
FIG. 4
FIG. 6
XUE F
XUE H, PNP
XUE T
XUR Color Registration Photoelectric Sensors FIG. 8
FIG. 7
PNP
NPN
XUD Amplifiers FIG. 9
XUG Amplifiers
FIG. 10 BN
PNP H
+ OG BK
BU
FIG. 11
Light Mode: Connect to +
BN
Dark Mode: Connect to –
NPN J
+ BK
–
OG
–
BU
Light Mode: Connect to + Dark Mode: Connect to –
XUD J
XUD H
for XUF N Plastic Fiber Optics – DC models
XUE S Security Light Barriers FIG. 12
FIG. 13 5 6 T1 T2
Open to test
A1
L1
A2
L2
Emitter
3
4 1
L1
2
L2
Receiver
®
88
Photoelectric Sensors XUV
XUV Photoelectric Sensors w/ Separate Optical Heads FIG. 1
+ H
Grey
Test W J
+ LOAD
BU W
Gating Sensor
BN BK
H
FIG. 2
PNP
Synchro
LOAD
BK BU
LOAD
+ –
Grey Synchro
–
NPN
–
LOAD
Test
J
PNP Output FIG. 3
BN
Gating Sensor
NPN Output
1 CHANNEL AMPLIFIER
Terminals
13 15 17 19
A
Potentiometers
2 4 6-8 13 15 17 19
TERMINALS L1 Supply L2 Supply Relay output (1 contact) Receiver (white wire) Receiver shielded cable Emitter shield Emitter (red wire)
1 2 A 1 2 3
SWITCHES Light/Dark Monostable timer (pulse stretcher) POTENTIOMETERS Sensitivity adjustment LED INDICATORS Green: power supply Red: unstable Yellow: output
Switches 1
LED indicators
2
4
2
1 2 3
6
8
Terminals
2 CHANNEL AMPLIFIER – FORM C RELAY
10 12 14 16 18 20 Terminals
9 11 13 15 17 19
A
Potentiometers
B
Switches 2
1 23 4 3 4
2
4
6
8
1
3
5
7
1
LED indicators
5
Terminals
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
TERMINALS L1 Supply L2 Supply NC output, Channel 2 NC output, Channel 1 Common, Channel 2 Common, Channel 1 NO output, Channel 2 NO output, Channel 1 12 VDC output for synchro sensors 12 VDC output for synchro sensors Synchronization, Channel 2, NPN Synchronization, Channel 1, NPN Emitter shield, Channel 1 Receiver, Channel 1 (white wire) Emitter, Channel 1 (red wire) Receiver shield, Channel 1 Emitter shield, Channel 2 Receiver, Channel 2 (white wire) Emitter, Channel 2 (red wire) Receiver shield, Channel 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
TERMINALS L1 Supply L2 Supply Output test (1 contact relay) Output test (1 contact relay) Channel 1 output (1 contact relay) Channel 1 output (1 contact relay) Channel 2 output (1 contact relay) Channel 2 output (1 contact relay) 12 VDC output for synchro sensors 12 VDC output for synchro sensors Synchronization, Channel 2, NPN Synchronization, Channel 1, NPN Emitter shield, Channel 1 Receiver, Channel 1 (white wire) Emitter, Channel 1 (red wire) Receiver shield, Channel 1 Emitter shield, Channel 2 Receiver, Channel 2 (white wire) Emitter, Channel 2 (red wire) Receiver shield, Channel 2
1 2 3 4 A B 1 2 3 4 5
SWITCHES Monostable timer (pulse stretcher), Channel 1 Light/Dark, Channel 1 Monostable timer (pulse stretcher), Channel 2 Light/Dark, Channel 2 POTENTIOMETERS Sensitivity adjustment, Channel 1 Sensitivity adjustment, Channel 2 LED INDICATORS Green: power supply Red: unstable, Channel 1 Yellow: output, Channel 1 Red: unstable, Channel 2 Yellow: output, Channel 2
2 CHANNEL LOGIC MODULE
10 12 14 16 18 20 Terminals
9 11 13 15 17 19 LED indicators
5 6
Potentiometers
A
7
8
9 10
B
C
Switches 1 23 4 5 67 8 1 2 3 4
LED indicators
2
4
6
8
1
3
5
7
Terminals
SWITCHES Time delay, Channel 1 (0.05 to 3 s or 1 to 60 s) Time delay, Channel 1 (On/Off) Time delay mode (mono. or adjustable time delay) Leading/Trailing edge selection Logic function (And/Or) Logic function (On/Off) Light/Dark, Channel 1 Light/Dark, Channel 2 POTENTIOMETERS A Time delay, Channel 1 B Sensitivity adjustment, Channel 1 C Sensitivity adjustment, Channel 2 LED INDICATORS 1 Green: power supply 2 Red: output test 3 Yellow: output, Channel 1 4 Yellow: output, Channel 2 5 Green: synchronization, Channel 1 6 Yellow: detection, Channel 1 7 Red: unstable, Channel 1 8 Green: synchronization, Channel 2 9 Yellow: detection, Channel 2 10 Red: unstable, Channel 2 1 2 3 4 5 6 7 8
AC Wiring Diagrams
®
89
Limit Switches Class 9007
Contact Forms for Class 9007 Limit Switches FIG. 1
Limit Switches: Class 9007 Type C FIG. 2
FIG. 3
Types C52, C54 1-Pole
FIG. 4
Type C62 2-Pole, Same Polarity Each Pole
Type C66 2-Pole, 2-Stage, Same Polarity Each Pole
FIG. 5
FIG. 6
[1]
On CR switches, terminals 1-4 on left side are for CW rotation and terminals 5-8 on right side are for CCW rotation.
Types C68T5, C68T10, CR67T5 [1] and CR67T10 [1] 2-Pole Neutral Position, Same Polarity Each Pole
Type C Reeds
Limit Switches: Class 9007 Type XA FIG. 8
FIG. 7
Type XA73 Reeds
Type XA75 Reeds
®
90
Limit Switches Class 9007
Limit Switches: Class 9007 Type AW FIG. 2
FIG. 1
Type AW12 and AW14
Type AW18
FIG. 3
FIG. 4
[1]
FIG. 5
[1]
If lever arm is placed at same end of box as conduit, N.O. contacts become N.C. and vice versa.
Type AW16 w/ Lever Arm Opposite Conduit Hole [1] FIG. 6
If lever arm is placed at same end of box as conduit, N.O. contacts become N.C. and vice versa.
Type AW19 w/ Lever Arm Opposite Conduit Hole [1] FIG. 7
Type AW32, AW34, AW42 and AW44 FIG. 8
Type AW36 and AW46
Type AW38 and AW48
Type AW39 and AW49
Limit Switches: Class 9007 Type SG – GATE GARDTM Switch FIG. 9
FIG. 10
Type SGS1DK
Type SGP1
®
91
Limit Switches and Safety Interlocks XCK and MS
XCK Limit Switches FIG. 1
FIG. 2
SPDT, 1 N.O. and 1 N.C. Positive Opening, Snap Action
FIG. 3
2 SPDT, 2 N.O. and 2 N.C.
SPDT, Isolated N.O. and N.C. Positive Opening, Slow-Make Slow-Break
XCK Safety Interlocks FIG. 4
FIG. 5
13 21
FIG. 6
LED 24 VDC
AC
24 VDC
21
13
22
14
L1
21
13 14
22
14
Orange LOAD
No polarity
SPDT, Positive Opening, Slow-Make Slow-Break
X3 X1
22 X3
Orange LOAD
X2 Green X1
0V
SPDT, w/ 24 VDC LED, Positive Opening, Slow-Make Slow-Break
AC
Note: N.O. and N.C. contacts are shown with key inserted and fully engaged.
L2
SPDT, w/ 2 Pilot Lights, Positive Opening, Slow-Make Slow-Break
Contact Blocks for XY2CE Limit Switches FIG. 7
21
13
FIG. 8
21
11
FIG. 9
11
FIG. 10
13
FIG. 11
X1
X1
X2 22
Zb 14
XEN P2151, Isolated N.C. and N.O.
22
12
Zb 12
XEN P2141, Isolated N.C. and N.O.
X2
Za 14
XEN P2051, N.C./N.O., 12 and 14 same polarity
Indicator Light, Direct
Indicator Light w/ Resistance
MS Miniature Limit Switches FIG. 12
FIG. 13 Black Green
White
Black
Orange
Red Red
SPST
White
Green
SPDT
®
92
Pressure Switches and Transducers Class 9012, 9013, 9022 and 9025
Pressure and Temperature Switches: Class 9012 and 9025 Type G FIG. 1
FIG. 2
FIG. 3
Machine Tool, SPDT, 1 N.O. and 1 N.C.
Machine Tool, DPDT, 2 N.O. and 2 N.C.
FIG. 4
Industrial, SPST, 1 N.O. and 1 N.C.
FIG. 5
Machine Tool, SPDT, 1 N.O. and 1 N.C. w/ Form H10
Machine Tool, SPDT, 1 N.O. and 1 N.C. w/ Form H11
Commercial Pressure Switches: Class 9013 Type CS FIG. 6
Acceptable Wiring Schematics
Pressure Transducers: Class 9022 Type PTA and PTB FIG. 7
+
–
DC SUPPLY
FIG. 8
Black
DC SUPPLY
TRANSDUCER White or Red Brown
TRANSDUCER Red
+
LOAD
–
FIG. 9
+
DC SUPPLY
–
TRANSDUCER 4
LOAD
Black
2 1
3
LOAD
Type PTA, 2-Wire FIG. 10
+
Type PTA, 3-Wire –
DC SUPPLY
Green
+
Type PTA, 4-Wire
DC SUPPLY
–
TRANSDUCER
TRANSDUCER Red
FIG. 11
LOAD
A
B C
FIG. 12
+
DC SUPPLY
–
TRANSDUCER LOAD
Red
Green
Black
White
LOAD
Type PTB, 2-Wire
Type PTB, 3-Wire
Type PTB, 4-Wire
®
93
Level Sensors and Electric Alternators Class 9034 and 9039
Level Sensors: Class 9034 Types LSD and LSV FIG. 1
Wiring Diagram
Elementary Diagram
Output selection of both sensors in maximum (N.C. when absent). Both devices at max. setting.
Fill Cycle, Tank Full FIG. 2
Wiring Diagram
Elementary Diagram
Output selection of both sensors in minimum (N.O. when absent). Both devices at min. setting.
Drain Cycle, Tank Empty
Electric Alternators: Class 9039 Type X FIG. 3
Set pilot device A contacts to close before pilot device B contacts. Connections shown are for common control. If motor line voltage is different from voltage rating stamped on alternator coil terminals, alternator must be connected to motor lines thru control transformers. Control circuit conductors require overcurrent protection in accordance with applicable electrical codes. * Overlapping contact.
FPO 69-1
®
94
Pneumatic Timing Relays Class 9050
Pneumatic Timing Relays: Class 9050: Type AO FIG. 1
FIG. 2
Type AO10E
FIG. 3
Type AO10D
FIG. 7
FIG. 8
Type AO11E
Type AO20E FIG. 9
Type AO11D
FIG. 13
FIG. 14
Type AO12E
FIG. 20
Type AO210DE
Type AO20D
Type AO21E
FIG. 21
Type AO21D
FIG. 22
FIG. 25
FIG. 26
Type HO10D, Off Delay
Type AO111DE
Type AO121DE FIG. 18
Type AO112DE
Type AO122DE FIG. 24
Type AO221DE
Type AO222DE
Pneumatic Timing Relays: Class 9050: Types B and C FIG. 27
FIG. 28
Off Delay Type HO10E, On Delay
Type AO120DE FIG. 12
FIG. 23
Type AO220DE
Pneumatic Timing Relays: Class 9050: Type HO
Type AO110DE
FIG. 17
Type AO22D
Type AO212DE
FIG. 6
FIG. 11
FIG. 16
Type AO22E
Type AO211DE
FIG. 5
FIG. 10
FIG. 15
Type AO12D
FIG. 19
FIG. 4
Type B
On Delay
Off Delay
On Delay
Type C
®
95
Pneumatic Timing Relays and Solid State Industrial Timing Relays Class 9050
Class 9050 Pneumatic Timing Relays: Typical Elementary Diagrams FIG. 1
FIG. 2
Interval, Momentary Start FIG. 3
On Delay
Interval, Maintained Start
FIG. 4
FIG. 5
Off Delay
Repeat Cycle
Solid State Industrial Timing Relays: Class 9050 Types FS and FSR FIG. 6
FIG. 7
L1
L2 AC Supply Voltage
FPO 71-1
L1
L2 C1 Timed Contacts C2
C3
Instantaneous C5 Contacts (optional) P1 C6
C7
C4
C8
External Initiating Contact
Elementary Diagram
Wiring Diagram
Solid State Industrial Timing Relays: Class 9050 Type FT FIG. 8
FIG. 9
L1
L2 AC Supply Voltage
FPO 71-2
C1
C3
C5
C7
L1 L2 Instantaneous Contacts (optional) P C2 C4 Timed Contacts
C6
C8
External Initiating Contact
Elementary Diagram
Wiring Diagram
®
96
Timers Class 9050
Solid State Industrial Timing Relays: Class 9050 Type JCK FIG. 1
FIG. 2
FIG. 3
External Initiating Contact
4
External Initiating Contact (used in one-shot and off-delay mode only)
6
5 5
3
6
7 8
4
6 5
7
7
2
3 1
8
+
9
–
1
11
+ – Control Power
Polarity markings are for DC units only. JCK 60 is AC only.
8
3
9
10
2
Control Power
4
1
Terminals 5 and 10 are internally jumpered. Applying power to terminal 7 or jumpering from terminal 5 to 7 through an external contact initiates the timer.
Type JCK 11-19, 31-39 and 51-60
10
2
Polarity markings are for DC units only.
11
Control Power
Type JCK 21-29 and 41-49
Type JCK 70
Solid State Timers: Class 9050 Type D FIG. 4
FIG. 5
A1/+ 15 25
FIG. 6
A1 15 25
A1/+ 15 25 Z1 Z2
16 18 26 28 A2/–
A1 15 25 Z1 Z2
16 18 26 28 A2
16 18 26 28 A2/–
Vs
Vs
Vs
Type DER, DZM, DTR, DWE, DEW and DBR
FIG. 7
Type DERP, DERLP, DWEP and DZMP
16 18 26 28 A2 Vs
Type DAR
Type DARP
Solid State Timers: Class 9050 Type M FIG. 8
FIG. 9
17 25 A1
15
18 26 A2
16 18 A2
Vs Type MAN, MBR, MER, MEW, MTG, MWE and MZM
A1
Vs Type MAR
®
97
Transformer Disconnects Class 9070
Transformer Disconnects: Class 9070 Note: Some factory modifications, depending on enclosure and transformer VA size selected, are not available. Consult factory modification chart. FIG. 1
L1
L2
FIG. 2
GND
L3
L1
L2
GND
L3 OFF
OFF
ON
ON F U 1
F U 2
F U 1
460 V H1
F U 2 460 V
230 V
H3
H2
H4
H1
H3
H2
H4
H1
H3
230 V H2
H1
H4
Optional Connection
F U 5
X1A
F U 4
R
R Power On
F U 3 X2B
X2A
F U 5
F U 4 X2A
Optional
For Size 1 Enclosures except w/ Form E23 L1
F U 6
X1A
Optional
FIG. 3
L2
For Size 1 Enclosures w/ Form E23 FIG. 4
GND
L3
L1
L2
GND
L3
OFF
OFF
ON F U 1
ON
F U 2
F U 1
H3
F U 2
230 V
460 V H1
H2
H4
H1
H3
230 V
460 V H2
H4
H1
H3
H2
H4
Optional Connection
F U 5
X1A
F U 4
R
R Power On
F U 3 X2B
X2A
Optional
For Size 2 Enclosures except w/ Form E23
H3
H2
H4
Electrostatically Shielded Transformer
X1 115 V X2
Power On
X1B
H1
Optional Connection
X1 115 V X2
F U 3
H4
Electrostatically Shielded Transformer
X1 115 V X2
Power On
X1B
H2
Optional Connection
X1 115 V X2
F U 3
H3
X1A
F U 7
F U 5
X1B
F U 6
F U 8 X2B
F U 4 X2A
Optional
For Size 2 Enclosures w/ Form E23
®
98
Enclosure Selection Guide
Table 6
Enclosures for Non-Hazardous Locations
Provides Protection Against
NEMA NEMA NEMA NEMA NEMA NEMA Type 5 Type 1 Type 3 [1] Type 3R [1] Type 4 [2] Type 4X [2] Type 12 [3]
Type 12K
NEMA Type 13
Accidental contact w/ enclosed equipment
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Falling dirt
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Falling liquids and light splashing
…
Yes
Yes
Yes
Yes
…
Yes
Yes
Yes
Dust, lint, fibers and flyings
…
…
…
Yes
Yes
Yes
Yes
Yes
Yes
Hosedown and splashing water
…
…
…
Yes
Yes
…
…
…
…
Oil and coolant seepage
…
…
…
…
…
…
Yes
Yes
Yes
Oil and coolant spraying and splashing
…
…
…
…
…
…
…
…
Yes
Corrosive agents
…
…
…
…
Yes
…
…
…
…
Rain, snow and sleet [4]
…
Yes
Yes
[5]
Yes
…
…
…
…
…
[5]
Yes
Yes
…
…
…
Windblown dust [1]
…
Yes
Intended for outdoor use.
[2]
Intended for indoor and outdoor use.
[3]
Square D Industrial Control design NEMA Type 12 enclosures may be field modified for outdoor applications.
[4]
External operating mechanisms are not required to be operable when the enclosure is ice covered.
[5]
Square D Industrial Control design NEMA Type 4 enclosures provide protection against these environments.
Table 7
Enclosures for Hazardous Locations Enclosure Class [1]
Group [1] 7B
7C
7D
9E
9F
9G
Hydrogen, manufactured gas
I
B
Yes
…
…
…
…
…
Ethyl ether, ethylene, cyclopropane
I
C
Yes
Yes
…
…
…
…
Gasoline, hexane, naphtha, benzine, butane, propane, alcohol, acetone, benzol, natural gas, lacquer solvent
I
D
Yes
Yes
Yes
…
…
…
Metal dust
Il
E
…
…
…
Yes
…
…
Carbon black, coal dust, coke dust
Il
F
…
…
…
…
Yes
…
Flour, starch, grain dust
Il
G
…
…
…
…
Yes
Yes
Provides Protection Against
[1]
NEMA Type 7
NEMA Type 9
As described in Article 500 of the National Electrical Code.
®
99
Conductor Ampacity and Conduit Tables Based on 1993 National Electrical Code
Ampacity Based on NEC® Table 310-16 — Allowable Ampacities of Insulated Conductors Rated 0-2000 Volts, Not More Than Three Conductors in Raceway or Cable. Based on 30 °C Ambient Temperature. Trade Size of Conduit or Tubing Based on NEC Chapter 9, Table 1 and Tables 3A, 3B, 3C, 4 and 5B. Refer to Chapter 9 for Maximum Number of Conductors in Trade Sizes of Conduit or Tubing. Dimensions of Insulated Conductors for Conduit Fill Determined from NEC Chapter 9 Tables 5 and 5A. For information on temperature ratings of terminations to equipment, see NEC Section 110-14c. Underlined conductor insulation types indicates ampacity is for WET locations. See NEC Table 310-13.
Table 8
Conductor Ampacity based on NEC Table 310-16 ALUMINUM CONDUCTORS
THWN, XHHW
Conduit Conduit Conduit Conduit 3W 3W 4W [2] 4W [2]
THHN, XHHW Conduit Conduit 3W 4W [2]
Wire Size AWG kcmil
Table 310-16 Ampacity Insulated Copper
THHW, THW, RW, USE
90 °C (194 °F) Conductor Insulation [1] Table 310-16 Ampacity Insulated Copper
Wire Size AWG kcmil
Table 310-16 Ampacity Insulated Copper
75 °C (167 °F) Conductor Insulation [1]
75 °C (167 °F) Conductor Insulation [1]
90 °C (194 °F) Conductor Insulation [1]
THHW, THW, USE
Table 310-16 Ampacity Insulated Copper
COPPER CONDUCTORS
XHHW
Conduit Conduit Conduit Conduit 3W 3W 4W [2] 4W [2]
THHN, XHHW Conduit Conduit 3W 4W [2]
†14
20
…
…
1/2
1/2
25
1/2
1/2
…
…
…
…
…
…
…
…
…
†12
25
…
…
1/2
1/2
30
1/2
1/2
†12
20
…
…
1/2
1/2
25
1/2
1/2
†10
35
…
…
1/2
1/2
40
1/2
1/2
†10
30
…
…
1/2
1/2
35
1/2
1/2
8
50
3/4
1
1/2 [3]
3/4
55
1/2 [3]
3/4
8
40
3/4
3/4
1/2
3/4
45
1/2
3/4
3/4
[4]
3/4
[4]
6
65
1
1
3/4
75
3/4
6
50
3/4
1
3/4
3/4
60
3/4
3/4
4
85
1
1-1/4
1
1
95
1
1
4
65
1
1
3/4
1
75
3/4
1
3
100
1-1/4
1-1/4
1
1-1/4
110
1
1-1/4
3
75
…
…
…
…
85
…
…
2
115
1-1/4
1-1/4
1
1-1/4
130
1
1-1/4
2
90
1
1-1/4
1
1-1/4
100
1
1-1/4
1
130
1-1/4
1-1/2
1-1/4
1-1/2
150
1-1/4
1-1/2
1
100
1-1/4
1-1/2
1-1/4
1-1/2
115
1-1/4
1-1/2
1/0
150
1-1/2
2
1-1/4
1-1/2
170
1-1/4
1-1/2
1/0
120
1-1/4
1-1/2
1-1/4
1-1/2
135
1-1/4
1-1/2
2/0
175
1-1/2
2
1-1/2
2
195
1-1/2
2
2/0
135
1-1/2
2
1-1/4
1-1/2
150
1-1/4
1-1/2
3/0
200
2
2
1-1/2
2
225
1-1/2
2
3/0
155
1-1/2
2
1-1/2
2
175
1-1/2
2
4/0
230
2
2-1/2
2
2
260
2
2
4/0
180
2
2
1-1 /2
2
205
1-1/2
2
250
255
2-1/2
2-1/2
2
2-1/2
290
2
2-1/2
250
205
2
2-1/2
2
2
230
2
2
300
285
2-1/2
3
2
2-1/2
320
2
2-1/2
300
230
2
2-1/2
2
2-1/2
255
2
2-1/2
350
310
2-1/2
3
2-1/2
3
350
2-1/2
3
350
250
2-1/2
3
2-1/2
3
280
2-1/2
3
305
2-1/2
2-1/2 [5]
3
350
2-1/2
3
400
335
3
3
2-1/2
3
380
2-1/2
3
400
270
2-1/2
3
2-1/2
500
380
3
3-1/2
3
3
430
3
3
500
310
3
3
2-1/2
600
420
3
3-1/2
3
3-1/2
475
3
3-1/2
600
340
3
3-1/2
3
3
385
3
3
700
460
3-1/2
4
3
3-1/2
520
3
3-1/2
700
375
3
3-1/2
3
3-1/2
420
3
3-1/2
750
475
3-1/2
4
3-1/2
4
535
3-1/2
4
750
385
3
3-1/2
3
3-1/2
435
3
3-1/2
800
490
3-1/2
4
3-1/2
4
555
3-1/2
4
800
395
…
…
…
…
450
…
…
900
520
4
5
3-1/2
4
585
3-1/2
4
900
425
…
…
…
…
480
…
…
1000
545
4
5
3-1/2
5
615
3-1/2
5
1000
445
3-1/2
4
3-1/2
4
500
3-1/2
4
[1]
[2]
Unless otherwise permitted in the Code, the overcurrent protection for conductor types marked with an with an obelisk (†) shall not exceed 15 A for No. 14, 20 A for No. 12 and 30 A for No. 10 copper, or 15 A for No. 12 and 25 A for No. 10 aluminum after any correction factors for ambient temperature and number of conductors have been applied..
[3]
2-1/2
[5]
#8 XHHW copper wire requires 3/4" conduit for 3W.
[4]
#6 XHHW copper wire requires 1" conduit for 3Ø4W.
[5]
400 kcmil aluminum wire requires 3" conduit for 3Ø4W.
On a 4-wire, 3-phase wye circuit where the major portion of the load consists of nonlinear loads such as electric discharge lighting, electronic computer/data processing, or similar equipment there are harmonic currents present in the neutral conductor and the neutral shall be considered to be a current-carrying conductor.
NEC is a Registered Trademark of the National Fire Protection Association.
®
100
Conductor Ampacity and Conduit Tables Based on 1993 National Electrical Code
Ampacity Correction Factors: For ambient temperatures other than 30 °C (86 °F), multiply the ampacities listed in Table 8 by the appropriate factor listed in Table 9. Adjustment Factors: Where the number of current-carrying conductors in a raceway or cable exceeds three, reduce the allowable ampacities as shown in Table 9.
Table 9
Ampacity Correction Factors
Ambient Temperature (°C)
75 °C (167 °F) Conductors
90 °C (194 °F) Conductors
Table 10
Adjustment Factors
Ambient Temperature (°F)
No. of Current-Carrying Inductors
Values in Tables as Adjusted for Ambient Temperature
4-6
80%
21-25
1.05
1.04
70-77
26-30
1.00
1.00
78-86
7-9
70%
31-35
.94
.96
87-95
10-20
50%
36-40
.88
.91
96-104
21-30
45%
41-45
.82
.87
105-113
31-40
40%
46-50
.75
.82
114-122
41 and above
35%
51-55
.67
.76
123-131
56-60
.58
.71
132-140
61-70
.33
.58
141-158
71-80
…
.41
159-176
For exceptions, see exceptions to Note 8 of NEC® Table 310-16.
Ratings for 120/240 V, 3-Wire, Single-Phase Dwelling Services: The ratings in Table 11 are permitted ratings for dwelling unit service and feeder conductors which carry the total load of the dwelling. The grounded conductor (neutral) shall be permitted to be not more than 2 AWG sizes smaller than the ungrounded conductors, provided the requirements of 215-2, 220-22 and 230-42 are met.
Table 11
Ratings for 120/240 V, 3-Wire, Single-Phase Dwelling Services – see NEC 310-16 Note 3
Rating (A)
100
110
125
150
175
200
225
250
300
350
400
Copper
4 AWG
3 AWG
2 AWG
1 AWG
1/0 AWG
2/0 AWG
3/0 AWG
4/0 AWG
250 kcmil
350 kcmil
400 kcmil
Aluminum
2 AWG
1 AWG
1/0 AWG
2/0 AWG
3/0 AWG
4/0 AWG
250 kcmil
300 kcmil
350 kcmil
500 kcmil
600 kcmil
NEC 240-3 Protection of Conductors: Conductors, other than flexible cords and fixture wires, shall be protected against overcurrent in accordance with their ampacities as specified in NEC Section 310-15, unless otherwise permitted in parts (a) through (m). NEC 220-3 (a) Continuous and Noncontinuous Loads: The branch circuit rating shall not be less than the noncontinuous load plus 125% of the continuous load (see exception for 100% rated devices). NEC 220-10 (b) Continuous and Noncontinuous Loads: Where a feeder supplies continuous loads or any combination of continuous and noncontinuous loads, the rating of the overcurrent device shall not be less than the noncontinuous load plus 125% of the continuous load (see exception for 100% rated devices). NEC 430-22 (a) Single Motor Circuit Conductors: Branch circuit conductors supplying a single motor shall have an ampacity not less than 125% of the motor full-load current rating (see exceptions). NEC is a Registered Trademark of the National Fire Protection Association.
®
101
Wire Data
Table 12 AWG Size
Conductor dia. (mm)
29
Conductor dia. (in)
Resistance @ 20 °C (68 °F) Ohm per ft .08180
.2684
.01240
.06743
.2212
.01264
.06491
.2130
.01398
.05309
.1742
.01420
.05143
.1687
.01575
.04182
.1372
.01594
.04082
.1339
.01772
.03304
.1084
.01790
.03237
.1062
.01969
.02676
.08781
.02010
.02567
.08781
.02205
.02134
.07000
.02257
.02036
.06679
.02480
.01686
.05531
.02535
.01614
.05531
.02795
.01280
.04201
.02846
.01280
.04201
.750
.02953
.01190
.03903
.800
.03150
.01045
.03430
.315
.355 27 .400 26 .450 25 .500 24 .560 23 .630 22 .710 21
20
AWG Size
Ohm per m
.01126
28
13
Conductor dia. (mm)
Conductor dia. (in)
Resistance @ 20 °C (68 °F) Ohm per ft
Ohm per m
1.900
.07480
.001853
.006081
2.000
.07874
.001673
.005488
.08081
.001588
.005210
2.120
.08346
.001489
.004884
2.240
.08819
.001333
.004375
12
11
.09074
.001260
.004132
2.360
.09291
.001201
.003941
2.500
.09843
.001071
.003512
.1019
.0009988
.003277
2.650
.1043
.0009528
.003126
2.800
.1102
.0008534
.002800
10
9
.1144
.0007924
.002500
3.000
.1181
.0007434
.002439
3.150
.1240
.0006743
.002212
.1285
.0006281
.002061
3.350
.1319
.0005662
.001956
3.550
.1398
.0005309
.001742
8
7
.1443
.0004981
.001634
3.750
.1476
.0004758
.001561
4.000
.1575
.0004182
.001372
.1620
.0003952
.001296
.03196
.01015
.03331
.850
.03346
.009261
.05038
.900
.03543
.008260
.02642
4.250
.1673
.0003704
.001215
.03589
.008051
.02642
4.500
.1772
.0003304
.001084
.950
.03740
.007414
.02432
1.000
.03937
.006991
.02195
19
18
.04030
.006386
.02095
1.060
.04173
.005955
.01954
1.120
.04409
.005334
.01750
.04526
.005063
.01661
1.180
.04646
.004805
.01577
1.250
.04921
.004282
.01405
17
16
.05082
.004016
.01317
1.320
.05197
.003840
.01260
1.400
.05512
.004016
.01317
.05707
.003414
.01045
1.500
.05906
.002974
.009756
1.600
.06299
.002526
.008286
15
14
13
AWG and Metric Wire Data
6
5
.1819
.0003134
.001028
4.750
.1870
.0002966
.0009729
5.000
.1968
.0002676
.0008781
.2043
.0002485
.0008152
.2205
.0002134
.0007000
.2294
.0001971
.0006466
.2480
.0001686
.0005531
.2576
.0001563
0005128
.2795
.0001327
.0004355
.2893
.0001239
.0004065
.3150
.0001045
.0003430
.3249
.00009825
.0003223
.3543
.00008260
.0002710
.3648
.00007793
.0002557
.3937
.00006691
.0002195
.4096
.00006182
.0002195
.4600
.00004901
.0001608
.4646
.00004805
.0001577
4 5.600 3 6.300 2 7.100 1 8.000 0 9.000 2/0
.06408
.002315
.007596
1.700
.06693
.002315
.007596
3/0
10.000
1.800
.07087
.002065
.006775
4/0
.07196
.002003
.006571
11.800
®
102
Electrical Formulas
Table 13
Electrical formulas for Amperes, Horsepower, Kilowatts and KVA Single phase
3-phase
Direct current
I x E x PF 1000
I x E x 1.73 x PF 1000
IxF 1000
IxE 1000
I x E x 1.73 1000
—
I x E x % Eff x PF 746
I x E x 1.73 x %Eff x PF 746
I x E x %Eff 746
HP x 746 E x %Eff x PF
HP x 746 1.73 x E x %Eff x PF
HP x 746 E x %Eff
Amperes when Kilowatts is known
KW x 1000 E x PF
KW x 1000 1.73 x E x PF
KW x 1000 E
Amperes
KVA x 1000 E
KVA x 1000 1.73 x E
—
To find Kilowatts KVA Horsepower (output) Amperes when Horsepower is known
E=Volts
l = Amperes
%Eff = Percent efficiency
PF = Power factor
HP = Horsepower
KVA = Kilovolt-Amps
Average Efficiency and Power Factor Values of Motors: When actual efficiencies and power factors of the motors to be controlled are not known, the following approximations may be used: Efficiencies: DC motors, 35 hp and less: DC motors, above 35 hp: Synchronous motors (at 100% PF):
80% to 85% 85% to 90% 92% to 95%
“Apparent” efficiencies (Efficiency x PF): 3-phase induction motors, 25 hp and less: 3-phase induction motors above 25 hp: Decrease these figures slightly for single phase induction motors.
Table 14
Ratings for 3-Phase, Single-Speed, Full-Voltage Magnetic Controllers for Nonplugglng and Nonjogging Duty Continous Current Rating (A)
Size of Controller
[1]
70% 80%
Horsepower at [1] 60 Hz 200 V
60 Hz 230 V
50 Hz 380 V
60 Hz 460 or 575 V
Service-Limit Current Rating (A)
00
9
1-1/2
1-1/2
1-1/2
2
11
0
18
3
3
5
5
21
1
27
7-1/2
7-1/2
10
10
32
2
45
10
15
25
25
52
3
90
25
30
50
50
104
4
135
40
50
75
100
156
5
270
75
100
150
200
311
6
540
150
200
300
400
621
7
810
—
300
—
600
932
These horsepower ratings are based on typical locked-rotor current ratings. For motors having higher locked-rotor currents, use a larger controller to ensure its locked-rotor current rating is not exceeded.
®
103
Electrical Formulas
Table 15
Ratings for 3-Phase, Single-Speed, Full-Voltage Magnetic Controllers for Plug-Stop, Plug-Reverse or Jogging Duty
[1]
Horsepower at [1]
Continous Current Rating (A)
Size of Controller
60 Hz 200 V
60 Hz 230 V
50 Hz 380 V
1-1/2
1-1/2
1-1/2
0
18
1
27
3
3
2
45
7-1/2
10
3
90
15
20
4
135
25
30
5
270
60
6
540
125
60 Hz 460 or 575 V
Service-Limit Current Rating (A)
2
21
5
5
32
15
15
52
30
30
104
50
60
156
75
125
150
311
150
250
300
621
These horsepower ratings are based on typical locked-rotor current ratings. For motors having higher locked-rotor currents, use a larger controller to ensure its locked-rotor current rating is not exceeded.
Table 16
Power Conversions
From
to kW
to PS
to hp
to ft-lb/s
1 kW (kilowatt) = 1010 erg/s
1
1.360
1.341
737.6
1 PS (metric horsepower)
0.7355
1
0.9863
542.5
1 hp (horsepower)
0.7457
1.014
1
1 ft-lb/s (foot-pound per sec)
1.356 x
10-3
1.843 x
10-3
1.818 x
550.0 10-3
1
®
104
From single products to complete systems, look to Square D. Square D Company is a leading manufacturer and supplier of electrical distribution, automation and industrial control products. The full line of Square D and Telemecanique brand products are available from an extensive network of Square D distributors located throughout North America. Square D Company is part of Groupe Schneider, an $11 billion global manufacturer of electrical distribution, automation and industrial equipment, a company whose primary business resides in those markets. Square D has been serving industrial and construction markets, as well as public utilities, individual consumers and government agencies for over 85 years. We offer unsurpassed quality, innovative design and a committed staff of trained sales representatives and service technicians willing to stand behind every product we sell. For further information on how we can help fill your electrical needs, call your local Square D field representative or authorized Square D distributor.
Square D Company Automation and Control Business P.O. Box 27446, Raleigh, N.C. 27611, USA Square D Canada 6675 Rexwood Road Mississauga, Ontario L4V 1V1 Square D Company Mexico, SA de C.V. Calz. Javier Rojo Gomez No. 1121 Col. Guadalupe del Moral, Iztapalapa 09300 Mexico D.F., Mexico 0140CT9201 (Supersedes SM304R10) Printed in USA © 1993 Square D All Rights Reserved
View more...
Comments