Description
DOCUMENT NO:
60-0000-L-SPE-0002 DOCUMENT TITLE:
SPECIFICATION FOR PIPE SUPPORTS ДОКУМЕНТ №
60-0000-L-SPE-0002 НАИМЕНОВАНИЕ
XXXXX
TENGIZCHEVROIL PFD Project No. 571500
ТЕНГИЗШЕВРОЙЛ PFD Проект № 571500
4
29/06/05
22
RE-ISSUED FOR CONSTRUCTION
PO
BW
SM
RH
3
12/07/04
21
RE-ISSUED FOR CONSTRUCTION
PO
BW
SM
DB
2
28/01/04
21
RE-ISSUED FOR CONSTRUCTION
PO
BW
MB
DB
1
10/04/03
19
RE-ISSUED FOR CONSTRUCTION
PO
BW
MB
JH
0
22/08/02
18
ISSUED FOR CONSTRUCTION
PO
BW
MB
JH
REV
DATE
PAGES
DESCRIPTION
BY
CHKD
APPR
CLIENT
ИЗМ.
ДАТА
СТР.
ПОЯСНЕНИЯ
ИСП.
ПРОВ.
УТВ.
ЗАКАЗЧИК
Pagee 1 of 22
PFD PROJECT №. 571500
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
DOC №. : 60-0000-L-SPE-0002 Rev. 4
REVISION DESCRIPTION SHEET REV.
PARA.
REVISION DESCRIPTION
4
4.2
4
8
COLD CONSERVATION INSULATION THICKNESS TABLE REVISED TO INCLUDE COLD PERSONNEL PROTECTION
4
10
NOTES REVISED
NSPS MATERIAL REVISED
ATTACHMENTS SHEET NO. 4
A15, A18
PIPE SIZE RANGE REVISED
4
A32
4
A34 - A36
4
B7
4
B50 - B57
4
C3
PIPE SIZE RANGE REVISED
4
C5
SUPPORT REVISED FOR TRUNNION SIZES 18” - 24”
4
C12, C13
4
C15, C18, C19
4
D30 - D34
SUPPORT NUMBER REVISED NEW PIPE SUPPORTS PIPE SIZE RANGE REVISED NEW PIPE SUPPORTS
NOTE ADDED TO DRAWING SUPPORT REVISED FOR TRUNNION SIZES 18” - 24” NEW PIPE SUPPORTS
4
E40
NOTE REVISED
4
E44
DIMENSION REVISED
4
E51
NEW PIPE SUPPORT
4
F16, F20, F21
4
F32, F33
DIMENSION REVISED
4
F36 – F39
PIPE SIZE RANGE REVISED
4
F40
4
F43 – F49
4
G12
4
H9
4
H23, H24
4
J1- J13
PIPE SIZE RANGE REVISED
DETAIL REVISED NEW PIPE SUPPORTS THREADED BAR LENGTH REVISED TRUNNION END PLATE REVISED DIMENSION REVISED GENERAL REVISION OF SELECTION SHEETS
Pagee 2 of 22
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
PFD PROJECT №. 571500 DOC №. : 60-0000-L-SPE-0002 Rev. 4
TABLE OF CONTENTS 1. 2. 3. 4. 5. 6. 7. 8. 9.
SCOPE CODES, STANDARDS AND SPECIFICATIONS ABBREVIATIONS PIPE SUPPORT CATEGORIES GENERAL NOTES MAXIMUM PIPE SPANS MAXIMUM GUIDE SPACING PIPE SHOE HEIGHTS ALLOWABLE LOADS FOR NON-INSULATED PIPES, PIPE SHOES, PIPE ANCHORS 10. PROCEDURE FOR INSTALLATION OF ANCHOR BOLTS AND GROUTING OF BASE PLATES 15 ATTACHMENTS A. B. C. D. E. F. G. H. J.
SHOES ANCHORS, GUIDES & VERTICAL PIPE SUPPORTS TRUNNIONS & BASE SUPPORTS HANGERS & SPRINGS STRUCTURAL SUPPORTS SMALL BORE & ANCILLARY SUPPORTS PIPE SUPPORT FOUNDATIONS COLD PIPE SUPPORTS & ANTI VIBRATION SUPPORTS PIPE SUPPORT SELECTION CHART
Pagee 3 of 22
4 4 4 4 5 6 10 11 13
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
1.
PFD PROJECT №. 571500 DOC №. : 60-0000-L-SPE-0002 Rev. 4
SCOPE This specification describes the general requirements for the selection and design of Standard Pipe Supports. These include pipe shoes, guides, anchors, hangers, spring supports, base supports, supports for vertical lines, stainless steel pipes, cold insulated pipes, small bore pipes (≤ 1 1/2”), structural pipe supports and small pipe support foundations.
2.
CODES, STANDARDS AND SPECIFICATIONS This specification has been reviewed by the Kazakh Design Institutes and now meets the requirements of the Kazakh Codes and Standards. The publications listed below form part of this Specification. Each publication shall be the latest revision and addendum in effect on the date this specification is issued for construction UNO. Except as modified by the requirements specified herein or the details of the drawings, work included in this specification shall conform to the applicable provisions of these publications. In the event of a conflict between codes and specifications the more stringent shall apply. • • • • • •
3.
ANSI/MSS SP-58
Pipe Hangers and Supports, Materials, Design and Manufacture ANSI/MSS SP-69 Pipe Hangers and Supports, Selection and Application BS-3974-1 Pipe hangers, slider and roller type supports DS-60-W-0045 Welding and NDT Pipe Supports Data Sheet 60-0000-L-SPE-0007 Paint & Protective Coatings. 60-0000-L-SPE-1003 Purchase Specification for Special Pipe Supports
ABBREVIATIONS AND DEFINITIONS The following abbreviations are used in this document: PDS PTFE TCO TOS UNO
4.
Plant Design System Polytetrafluroethylene Tengizchevroil Top of steel Unless Noted Otherwise
PIPE SUPPORT CATEGORIES 4.1
Standard Pipe Supports
These shall be used wherever possible and practical, the details of which are shown in the attachments to this specification. The piping designer shall model standard pipe supports in PDS Piping, and the support material will be supplied by piping.
Pagee 4 of 22
PFD PROJECT №. 571500
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
4.2
DOC №. : 60-0000-L-SPE-0002 Rev. 4
Non-Standard Pipe Supports (NSPS)
These are pipe supports that cannot be produced using the standard pipe supports, but do not require any design input from the Civil engineering group. The piping designer shall model NSPSs in PDS Piping where they are required for clashing, otherwise they shall be modelled as a logical. The support material will be supplied by piping. A support drawing, produced by a pipe supporter or piping designer, shall include the following information as a minimum: • • • • • • • •
Outline support shape including inset details and sections where required. Standard items; e.g. shoes, anchors. Where these items are called up on the isometric they shall be referenced on the detail. Major adjacent civil supplied steelwork. TOS elevations, dimensions including dimensions back to grid lines. Material Summary. Line numbers for supported pipes. Welded attachment references back to the isometric.
The pipe supporter shall maintain an index of these supports. The steel sections used to design the NSPS shall be the same as those used for the standard supports. These are: CS. Plate Thickness: 6, 10, 12, 15, 20 HEA Section: 100, 160, 200 IPE Section: 100, 160, 200 UPN Section: 100, 160, 200 Angle 40 x 6, 60 x 6, 70 x 8, 80 x 8, 100 x 10 Round bar Diameter: 12, 16, 20, 24, 30, 36, 42 SS Plate Thickness: 5 4.3
Civil/Structural Pipe Supports (CPS/SPS)
These are pipe supports that cannot be produced using the standard pipe supports because: (a)- the support dimensions, or (b)- the support loads are greater than those specified in the standard supports. These supports shall be modeled by Piping in Equipment to obtain location and initial space reservation. Notification of the support details including dimensions, TOS elevation, support orientation, support loads and pipe sizes will be given to Civil/ Structural. Civil/ Structural shall model this support in ‘Frameworks’ and piping shall remove the support in Equipment. 5.
GENERAL NOTES • • • • •
All pipes, including pipes ≤ 1 1/2”, shall be supported. Dimensions are in mm. All welds are 6mm fillet welds u.n.o. Threaded connections are right hand thread u.n.o. The allowable axial displacement for shoes is: Pagee 5 of 22
PFD PROJECT №. 571500
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
•
• • •
6.
DOC №. : 60-0000-L-SPE-0002 Rev. 4
±100mm for 300mm long shoes ±200mm for 500mm long shoes Adjustable hangers shall only be used in preference to non-adjustable hangers where the support is: (a) Local to a rotating equipment nozzle, (one of the first two supports) (b) The first support local to a column or vessel. The first support local to either pump nozzle shall be adjustable. Vertical stainless steel pipes, which require guides, shall have a cradle (C101 or C102) and a welded shoe if the line is insulated. Clamped shoes shall not be used. Anchor clamps can be used for galvanised piping. Completed pipe supports to be primed and finished coated in accordance with Specification 60-0000-L-SPE-0007.
MAXIMUM PIPE SPANS
From BS 3974 Part 1 (1974) for continuous piping spans, The Maximum Stress in the pipe (σ) is given by the formulae: -
wDL2 σ= 240 I The Maximum Deflection in the pipe (δ) is given by the formulae: -
100000wL4 δ= 384 EI Where: σ = Stress (N/mm2) δ = Pipe deflection (mm) w = Pipe weight (N/m) D = Pipe Diameter (mm) L = Pipe Span for continuous spans (m) I = Second moment of area (cm4) E =Young's Modulus of elasticity (N/mm2) Limiting the Stress to 35 N/mm2 and the deflection to 12.7mm the maximum pipe span for continuous piping is calculated from the lesser of the following formulae: -
L=
240 Iσ wD
L=4
384 EIδ 100000 w
Notes: 1- Pipes are assumed to be full of water s.g. = 1.0 2- Insulation density is assumed to be 150 kg/m3 3- Insulation thickness is based upon Spec No 60-0000-L-0010 Rev D (Temp 201 - 250ºC)
Pagee 6 of 22
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
PFD PROJECT №. 571500 DOC №. : 60-0000-L-SPE-0002 Rev. 4
4- The maximum spans for piping arrangements other than continuous spans are shown below.
Max Span = 0.8 x L Max Span = 0.75 x L
Max Span = 0.65 x L
Pagee 7 of 22
PFD PROJECT №. 571500
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
DOC №. : 60-0000-L-SPE-0002 Rev. 4
PIPE SPAN TABLES FOR CONTINUOUS PIPE SPANS
Pipes Full (SG=1), Insulated (Temp 250oC) Pipe Size ¾ 1 1½ 2 3 4 6 8 10 12 14 16 18 20 22 24
10
10.1 10.3 10.4 10.6 10.8 11.0
20
9.0 9.6 9.9 11.2 10.9 10.9 12.5 12.7 12.9
30
9.4 10.5 11.2 12.1 12.5 13.5 14.6 14.9 15.9
STD 2.6 3.3 4.0 4.4 5.9 7.0 8.5 10.0 11.2 11.7 12.0 12.2 12.3 12.5 12.7 12.9
Schedule 40 2.6 3.3 4.0 4.4 5.9 7.0 8.5 10.0 11.2 12.2 12.8 13.9 14.8 15.5 16.2 17.1
XS 2.3 3.6 4.5 5.1 7.0 8.0 10.0 11.5 12.4 13.0 13.4 13.9 14.2 14.6 14.9 15.1
80 2.3 3.6 4.5 5.1 7.0 8.0 10.0 11.5 13.0 14.2 14.9 16.0 17.0 18.0 18.9 19.9
120
160 3.6 4.2 5.1 5.9 7.5
8.5 10.5 12.3 13.9 15.2 16.0 17.1 18.2 19.2 20.2 21.2
Pipes Full (SG=1), Not Insulated Pipe Size ¾ 1 1½ 2 3 4 6 8 10 12 14 16 18 20 22 24
10
10.6 10.9 11.1 11.3 11.4 11.5
20
9.6 10.1 10.5 11.8 11.6 11.7 13.3 13.4 13.5
30
10.1 11.0 11.8 12.7 13.1 14.2 15.3 15.6 16.6
STD 3.3 4.0 4.8 5.3 7.0 7.9 9.4 10.6 11.8 12.4 12.7 12.9 13.1 13.3 13.4 13.5
Schedule 40 3.3 4.0 4.8 5.3 7.0 7.9 9.4 10.6 11.8 12.8 13.4 14.5 15.5 16.2 16.8 17.7
XS 3.9 4.5 5.4 6.1 7.7 8.7 10.6 12.0 12.9 13.6 14.0 14.5 14.9 15.3 15.6 15.8
80 3.9 4.5 5.4 6.1 7.7 8.7 10.6 12.0 13.5 14.7 15.5 16.6 17.6 18.6 19.5 20.4
120
160 4.2 4.8 5.8 6.6 8.2
9.1 11.1 12.8 14.3 15.7 16.4 17.6 18.7 19.7 20.7 21.7
Pagee 8 of 22
PFD PROJECT №. 571500
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
DOC №. : 60-0000-L-SPE-0002 Rev. 4
PIPE SPAN TABLES FOR CONTINUOUS PIPE SPANS
Pipes Empty, Insulated (Temp 250oC) Pipe Size ¾ 1 1½ 2 3 4 6 8 10 12 14 16 18 20 22 24
10
15.3 16.2 16.7 17.6 18.5 19.4
20
12.0 13.5 14.6 16.2 17.1 17.7 19.5 20.6 21.5
30
12.3 14.2 15.6 16.8 17.8 19.0 20.5 21.6 23.0
STD 2.7 3.5 4.4 4.9 7.1 8.4 10.7 12.7 14.7 15.9 16.8 17.8 18.5 19.5 20.6 21.5
Schedule 40 2.7 3.5 4.4 4.9 7.1 8.4 10.7 12.7 14.7 16.1 17.2 18.6 19.7 21.0 22.2 23.5
XS 2.5 3.9 5.0 5.6 7.7 9.1 11.5 13.5 15.3 16.6 17.4 18.6 19.4 20.5 21.6 22.6
80 2.5 3.9 5.0 5.6 7.7 9.1 11.5 13.5 15.5 17.0 18.0 19.4 20.5 21.8 23.1 24.2
120
160 3.6 4.3 5.4 6.2 8.0
9.4 11.8 13.8 15.7 17.3 18.2 19.5 20.7 22.0 23.2 24.3
Pipes Empty, Not Insulated Pipe Size ¾ 1 1½ 2 3 4 6 8 10 12 14 16 18 20 22 24
10
17.5 18.7 19.8 20.9 21.9 22.9
20
13.6 15.3 16.6 18.0 19.3 20.5 22.1 23.2 24.2
30
13.8 15.7 17.3 18.4 19.7 21.2 22.5 23.7 24.9
STD 3.6 4.4 5.5 6.3 8.3 9.7 12.1 14.1 16.0 17.5 18.4 19.7 20.9 22.1 23.2 24.2
Schedule 40 3.6 4.4 5.5 6.3 8.3 9.7 12.1 14.1 16.0 17.6 18.6 20.1 21.5 22.7 23.9 25.1
XS 4.1 4.8 6.0 6.8 8.7 10.0 12.5 14.5 16.3 17.8 18.7 20.1 21.3 22.5 23.7 24.8
80 4.1 4.8 6.0 6.8 8.7 10.0 12.5 14.5 16.4 18.0 18.9 20.4 21.7 22.9 24.1 25.2
120
160 4.4 5.0 6.2 7.0 8.8
10.1 12.6 14.5 16.4 17.9 18.9 20.2 21.5 22.7 23.9 25.0
Pagee 9 of 22
PFD PROJECT №. 571500
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
7.
DOC №. : 60-0000-L-SPE-0002 Rev. 4
MAXIMUM GUIDE SPACING Pipe Size ¾ 1 1½ 2 3 4 6 8 10 12 14 16 18 20 22 24
Maximum Span between guides (m) Horizontal Pipes Vertical Pipes 8.0 7.0 8.0 7.0 8.0 7.0 8.0 7.0 16.0 8.0 16.0 8.0 16.0 10.0 24.0 12.0 24.0 12.0 24.0 14.0 24.0 14.0 24.0 16.0 24.0 16.0 32.0 18.0 32.0 18.0 32.0 18.0
Pagee 10 of 22
PFD PROJECT №. 571500
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
8.
DOC №. : 60-0000-L-SPE-0002 Rev. 4
PIPE SHOE HEIGHTS Non-insulated and personnel protection insulated pipes shall rest directly upon the support steelwork. Pipes with heat or cold conservation insulation shall be supported on shoes. The shoe height is determined from the tables below: -
HEAT CONSERVATION THICKNESS TABLE (Ref Doc No60-0000-L-SPE-0010 Section 5.17.1) PIPE SIZE DN
NPS
15 ½ 20 ¾ 25 1 40 1½ 50 2 80 3 100 4 150 6 200 8 250 10 300 12 350 14 400 16 450 18 500 20 600 24 600 - 1000 24 - 40 ≥ 1050 ≥ 42
INSULATION THICKNESS FOR OPERATING TEMPS (Deg.C.) AMB to 101 to 151 to 201 to 251 to 51 to 100 50 150 200 250 350 40 40 40 40 40 50 40 40 40 40 40 50 40 40 40 40 40 50 40 40 40 40 50 60 40 40 40 40 60 80 40 40 50 60 60 80 40 40 60 60 60 80 40 50 60 60 70 90 50 50 60 60 70 90 50 50 70 70 70 90 60 60 70 80 80 100 60 60 70 80 80 100 60 60 70 90 90 110 60 70 70 90 110 110 60 70 90 100 110 120 70 70 90 100 110 120 70 70 90 100 110 120 70 70 90 100 110 120
Notes: •
The pipe shoe height in the non-shaded area of the above table shall be 100mm
•
The pipe shoe height in the shaded area of the above table shalll be 150mm
•
The intermediate beam of the main SGP piperack is set 50 mm lower than the main beams. Pipe Sizes 2", 3" & 4" only will be supported on this beam, therefore shoe heights will be 150mm for insulated lines and 50mm for non-insulated lines.
Pagee 11 of 22
PFD PROJECT №. 571500
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
DOC №. : 60-0000-L-SPE-0002 Rev. 4
COLD CONSERVATION OR PERSONNEL PROTECTION COLD TABLE Ref Doc No 60-0000-L-SPE-0010 Section 6.12 & 6.13 INSULATION THICKNESS PERSONNEL NPS COLD CONSERVATION (CI) PROTECTION COLD (PPC) ¾ 30 40 50 60 1 30 40 60 60 1½ 30 40 50 60 70 2 30 40 50 60 70 3 30 40 50 60 70 80 4 30 40 50 60 70 80 6 30 40 50 60 80 90 8 30 40 50 70 80 100 10 30 40 50 70 80 100 12 30 40 50 60 70 90 100 14 30 40 50 60 70 90 100 16 30 40 50 60 70 90 100 18 30 40 50 60 70 90 110 20 30 40 50 60 70 90 110 24 30 40 50 60 70 90 110 26 30 40 50 60 70 90 110 28 30 40 50 60 70 90 110 30 30 40 50 60 70 90 110 32 30 40 50 60 70 90 110 34 30 40 50 60 80 100 110 36 30 40 50 60 80 100 110 >36 30 40 50 60 80 100 120
PIPE SIZE DN 20 25 40 50 80 100 150 200 250 300 350 400 450 500 600 650 700 750 800 850 900 >900
100 High Shoe
150 High Shoe
200 High Shoe
Notes: •
The pipe shoe height in the non-shaded area of the above table shall be 100mm
•
The pipe shoe height in the lightly shaded area of the above table shalll be 150mm
•
The pipe shoe height in the heavy shaded area of the above table shalll be 200mm
The intermediate beam of the main SGP piperack is set 50 mm lower than the main beams. Pipe Sizes 2", 3" & 4" only will be supported on this beam, therefore shoe heights will be 50mm greater than indicated above.
Pagee 12 of 22
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
DOC №. : 60-0000-L-SPE-0002 Rev. 4
ALLOWABLE LOADS FOR NON-INSULATED PIPES, PIPE SHOES, PIPE ANCHORS & TRUNNIONS The allowable loads for pipe shoes, pipe anchors and trunnions are listed in the pipe support attachments. The allowable loads for non-insulated pipes with a design temperature up to 50°C are shown below: Allowable loads for Non-Insulated pipes resting on support steel Max Allowable Load (KN) Pipes without a re-pad Pipes with a re-pad Pipe Size Stain. Carbon Stain. Carbon Steel (") Steel Steel Steel c.a. = 1.5 c.a. = 3.0 c.a. = 1.0 All pipes c.a. = 1.0 2 8.0 6.0 10.0 25.0 25.0 3-4 12.0 5.0 15.0 40.0 40.0 6-8 15.0 9.0 12.0 45.0 50.0 10 - 12 20.0 14.0 10.0 50.0 55.0 14 - 18 12.0 7.0 9.0 40.0 30.0 20 - 24 15.0 10.0 8.0 40.0 27.0 26 - 40 32.0 32.0 For lines that have higher design temperatures the tabulated loads shall be multiplied by the temperature correction factor shown below: Temperature Correction Factor Material Carbon Steel Stain. Steel Grade A333 Gr 8 A671 CC 60 A312 TP316/L Pipe Size 2" - 16" 18" - 36" 2" - 36" 50 1.00 1.00 1.00 100 1.00 0.97 1.00 150 1.00 0.94 1.00 200 1.00 0.92 0.96 250 0.95 0.88 0.91 300 0.89 0.81 0.86 350 0.83 0.76 0.83 400 0.65 0.65 0.81 Temperature °C
9.
PFD PROJECT №. 571500
Unless noted otherwise, the maximum loads for non-insulated pipes, pipe shoes, pipe anchors and trunnions are based upon pipes with a 12.5% tolerance, a corrosion allowance of 3.0mm and pipe schedules of: 2” Sch XS 3” – 12” Sch 40 14” – 36” Sch 20 40” Sch Std Note- these pipe schedules represent the smallest wall thickness in the piping specification. For pipes without re-pads, the following equation can be used to increase the actual allowable load: -
Pagee 13 of 22
PFD PROJECT №. 571500
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
Allowable load = tabulated load *
DOC №. : 60-0000-L-SPE-0002 Rev. 4
tp tt
1 .5
1 .5
* temp correction factor
Where: - tp is the pipe thickness (less c.a. and tolerances) of the pipe in question tt is the pipe thickness (less c.a. and tolerances) of the pipe used to calculate the tables Example What is the maximum load that can be applied to an non-insulated 18” Sch 40 pipe corrosion allowance = 3.0mm, design temp = 150°C with out a re-pad. 18” Sch 40 pipe 18” Sch 20 pipe
tp = (14.27 x 0.875) – 3 = 9.49mm tt = (7.92 x 0.875) – 3 = 3.93mm
9 . 49 1 .5 Allowable load = 10 * * 0 . 94 = 35 . 3 KN 3 . 93 1 .5 10.
PROCEDURE FOR INSTALLATION OF ANCHOR BOLTS AND GROUTING OF BASE PLATES The procedure for the installation of Anchor bolts and grouting of Base plates is included in the following Guidelines that are issued into ProArc: 60-0000-S-RLY-0006-01 60-0000-S-RLY-0006-02 60-0000-S-RLY-0006-03 60-0000-S-RLY-0006-04
SGP roads and paving layout settlement monitoring guidelines SGP roads and paving layout 0200 Area settlement monitoring guidelines SGP roads and paving layout 0400 Area settlement monitoring guidelines SGP roads and paving layout 0700 Area settlement monitoring guidelines
Pagee 14 of 22
PFD PROJECT №. 571500
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
ATTACHMENT A
DOC №. : 60-0000-L-SPE-0002 Rev. 4
SHOES
SUPPORT TYPE Standard Length Welded Shoe Long Welded Shoe Long Welded Shoe Standard Clamped Shoe, pipe sizes ½”- 6” Standard Clamped Shoe, pipe sizes 8”- 24” Long Clamped Shoe PTFE for Pipe Shoes Standard Clamped Shoe for Stainless Steel Pipes Sizes ½”- 6” Standard Clamped Shoe for Stainless Steel Pipes Sizes 8”- 32” Long Clamped Shoe for Stainless Steel Pipes, pipe sizes ½”- 6” Long Clamped Shoe for Stainless Steel Pipes, pipe sizes 8”- 24” Isolator Pad for Stainless Steel Pipes Pick-Up Support for 3” and below Insulated Pipes Pick-Up Support for 3” and below Uninsulated Pipes Packing Plates for gaps up to 20mm Packing Support for gaps 21 to 60mm for pipes with guides Packing Support for gaps 21 to 60mm without guides. Pipe sizes 42” and below Packing Support for gaps 61 to 80mm
SUPPORT NO S1, S5, S9 S2, S6, S10 S2, S6 S3, S7, S11 S3, S7, S11 S4, S8, S12 S19 S103, S107, S111 S103, S107, S111 S104, S108, S112 S104, S108, S112 S113 S114 S115 PK1
SHEET NO A1, A2, A3 A4, A5 A6, A7 A8 A9 A10, A11 A12, A13
REV 2 2 4 3 2 2 2
A14
2
A15
3
A16
2
A17
3
A18 A19 A20 A21, A22
3 2 2 3
PK2
A23
2
PK3
A24
3
PK4, PK5
A25, A26
2
PTFE for Long Pipe Shoes
S20
A27, A28
2
Pipe Shoe for SECT Traced piping Long welded shoes for Pipe Specs 150H26 & 150K26. Pipe sizes 36” – 40” Packing Support for gaps 21 to 60mm for 44” to 92” pipes Stiffening Rings Double Pipe Shoe for SECT Traced piping Puddle Flanges for Sump Covers Shoe for Contra-Traced Piping
S21
A29
0
S13, S14
A30, A31
0
PK3
A32
1
SR1, SR101 S22 PF1, PF101 S15
A33 A34 A35 A36
0 0 0 0
ATTACHMENT B
ANCHORS, GUIDES & VERTICAL PIPE SUPPORTS
SUPPORT TYPE Directional Anchor for Bare pipes Directional Anchor for Insulated pipes sizes ½”- 4” Directional Anchor for Insulated pipes sizes 6”- 24” Directional Anchor for Insulated pipes sizes 26”- 92” Directional Anchor for Insulated pipes sizes 26”- 92” Dimensions Guides for Insulated Horizontal pipes Guides for Bare Horizontal pipes Hold-down Guide Guide for Bare Pipes 2” and smaller (1 Pipe)
SUPPORT NO DA1 DA2, DA3 DA2, DA3 DA2, DA3
SHEET NO B1, B2, B3 B4 B4, B5, B6,
REV 2 4 3 4
DA2, DA3
B7
5
HG1 HG2 HG3 VG1
B8 B9, B10 B11 B12
2 2 2 2
Pagee 15 of 22
PFD PROJECT №. 571500
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
DOC №. : 60-0000-L-SPE-0002 Rev. 4
Guide for Pipes 2” and smaller (2 or more Pipes) Guide for 3”- 6” Bare Pipes and ½”- 6” Insulated Pipes 4-Way Guide for 8”- 24” Bare Pipes 4-Way Guide for 8”- 24” Insulated Pipes 2-Way Guide for 4”- 24” Bare Pipes 2-Way Guide for 4”- 24” Insulated Pipes Vertical Pipe Support, Cantilever Vertical Pipe Support, Braced Cantilever Vertical Pipe Support and Guide, Horizontal Frame Vertical Pipe Support, Braced Horizontal Frame Vertical Pipe Support from Vessels for pipe sizes 2”10” Vertical Pipe Support from Vessels for pipe sizes 4”24” Rigid Strut with Trunnion and Clamp Rigid Strut with Shoe Line stop for non-insulated Stainless Steel lines 300mm
A
Plan
Pipe Support No VG104 4-Directional Guide for Non-Insulated Pipes 4" - 24" A
B 75 (typ)
75 (typ)
Note Bracing omitted for clarity
A B 3 Gap (typ) Pipe Support No VG107 2-Directional Guide for Non-Insulated Pipes 4" - 24"
Existing Cradle C101 Refer to Iso for orientation
3 Gap (typ)
Pipe Support No VG108 2-Directional Guide for Non-Insulated Pipes 4" - 24"
Assembly Tag No: - VG104 or VG107 or VG108 - X SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size Detail No VG104, VG107, VG108 Vertical Guides for Non-Insulated Stainless Steel Pipes 4" - 24"
Sheet B32
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Pipe Size 4 6 8 10 12 14 16 18 20 22 24
Pipe O.D. 114 168 219 273 324 356 406 457 508 559 610
Pipe Size 4 6 8 10 12 14 16 18 20 22 24
SUPPORT No SUPPORT TYPE PIPE SIZE
Mark No 1 UPN 100
UPN 160
UPN 200
Pipe O.D. 114 168 219 273 324 356 406 457 508 559 610
Length 2000 2000 2500 2500 3000 3000 3300 3300 3800 3800 3800
A 140 194 245 299 350 382 432 483 534 585 636
Mark No 2
UPN 100
Length 1200 1500 1700 1900 2100 2200 2400 2600 2800 3000 3200
Dimensions B K 264 1000 318 1000 369 1250 423 1250 474 1500 506 1500 556 1650 607 1650 658 1900 709 1900 760 1900
Maximum Horizontal Loads (KN)
5.0
8.0
10.0
L (Max) 700 700 900 900 1100 1100 1200 1200 1400 1400 1400
VG104, VG107, VG108 Vertical Guides for Non-Insul. Stainless Steel Pipes (dims)
4" - 24"
Sheet B33
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
Cradle for Stainless lines only See Note 1
1 250
100
Pipe Size ½-4
Notes
Supporting sleeper by others. NOTE- The maximum sleeper width is 600.
2 Gap (typ)
Mark No 1 12 Thk Plate
Area (cm²) 500
Maximum Anchor Load (KN) 5.0
1- Cradle is mandatory for stainless steel lines 2" - 4". Refer to Support No C107 2- Cradles shall not be used for Carbon Steel lines
Assembly Tag No: - DA4 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size DA4 Directional Anchor for Non-Insul. pipes on sleepers≤ 600mm
½" - 4"
Sheet B34
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS Cradle if required Ref. Support No C7 or C107 See Note 1
1
175
H
Supporting sleeper by others. NOTE- The maximum sleeper width is 600.
2 Gap (typ)
L
4 gap
Pipe Size 6 - 14
10
250
Maximum Anchor Load (KN) With Cradle No Cradle 15.0 40.0
10
2
=
= A
Pipe Size Mark No 1 6 8 10 12 14 Notes
150 x 10 Plate
Total Length 1112 1136 1152 1192 1224
Mark No 2
10 Thk Plate
Area (cm²) 825 1000 1150 1350 1500
A 165 200 230 270 300
Dimensions L 160 160 160 160 160
H 278 284 288 298 306
1- Cradle is mandatory for stainless steel lines. Refer to Support No C107
Assembly Tag No: - DA4 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size DA4 Directional Anchor for Non-Insul. pipes on sleepers≤ 600mm
6" - 14"
Sheet B35
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS
Cradle if required Ref. Support No C7 or C107 See Note 1 2 175
H
Supporting sleeper by others. NOTE- The maximum sleeper width is 600.
2 Gap (typ)
4 gap
L
1
10
250
Pipe Size 16 - 24 26 - 40
Maximum Anchor Load (KN) 50.0 100.0
A 250
Dimensions L T 200 10
10 =
= A
Pipe Size Mark No 1
Area (cm²) 2125
Mark No 2
Area (cm²) 2002
16 18 10 Thk 20 Plate 22 2550 2023 300 200 10 24 26 10 Thk 28 2975 Plate 2613 350 250 12 30 32 12 Thk 34 Plate 36 3400 2631 400 250 12 38 40 Notes 1- Cradle is mandatory for stainless steel lines. Refer to Support No C107 Assembly Tag No: - DA4 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
H 278 274 284 281 278 287 284 282 291 288 286 284 282
Pipe Size DA4 Directional Anchor for Non-Insul. pipes on sleepers≤ 600mm
16" - 40"
Sheet B36
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS
25
Cradle for Stainless lines only See Note 1
50 (typ)
80
1
H
250 Supporting sleeper by others. NOTE- The maximum sleeper width is 600.
3 2 Gap (typ) 900 NOTE - Lugs shall be tack welded to the shoe in the shop. The final weld shall be made in the field.
Gusset plates required on 3" and 4" pipes only
15 (typ)
H = 100 for Support No DA5 H = 150 for Support No DA6
Pipe Size ½-4
Maximum Anchor Load (KN) 12.0
2
100 Pipe Size ½-2 3-4 Notes
Mark No 1 IPE 200 IPE 200
Length DA6 900 900
DA5 450 450
Mark No 2
Area (cm²)
10 Thk Plate
100
Mark No 3 HEA100 HEA100
Area (cm²) 500 500
1- Cradle is mandatory for stainless steel lines 2" - 4". Refer to Support No C107 2- Cradles shall not be used for Carbon Steel lines
Assembly Tag No: - DA5, DA6 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size DA5, DA6 Directional Anchor for Insul. pipes on sleepers≤ 600mm
½" - 4"
Sheet B37
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS Cradle if required Ref. Support No C7 or C107. Cradle is mandatory for SS pipes 1
35 (typ)
=
=
=
Cut Notches into Anchor
=
25
W
H
T 20 250
3
Supporting sleeper by others. NOTE- The maximum sleeper width is 600.
2 Gap (typ) L
H = 100 for Support No DA5 H = 150 for Support No DA6
NOTE - Lugs shall be tack welded to the shoe in the shop. The final weld shall be made in the field. Pipe Size 6-8 10 - 24 Pipe Size 6-8 10 12 14 16 18 20 - 22 24
2
30 (typ) Pipe Size 6 8 10 12 14 16 18 20 22 24
A
Maximum Anchor Load (KN) No Cradle With Cradle 25.0 100.0 50.0 200.0
A 150 200 250 250 300 300 350 400
Dimension Mark No 1 DA5 DA6 Mark No 2 H Area (cm²) Area (cm²) 1161 1611 1161 1611 1356 1806 10 Thk 1641 2141 Plate (See 10 Thk 1641 2141 Note 1) Plate 1836 2336 1926 2476 2121 2671 12 Thk 2121 2671 Plate 2316 2866
Dimension L T 900 900 1000 10 1000 1000 1100 1100 12 1100 Area (cm²) 1350 1350 1800 2500 2500 3000 3300 3850 3850 4400
W
10
Mark No 3
Total Length
HEA 100
500
HEA 160
500
HEA 200
500
Assembly Tag No: - DA5, DA6 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size DA5, DA6 Directional Anchor for Insul. pipes on sleepers≤ 600mm
6" - 24"
Sheet B38
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
Cradle for Stainless lines only See Note 1
1 250
100
Pipe Size ½-4
Notes
Supporting sleeper by others. NOTE- The maximum sleeper width is 1000.
2 Gap (typ)
Mark No 1 12 Thk Plate
Area (cm²) 500
Maximum Anchor Load (KN) 5.0
108 1- Cradle is mandatory for stainless steel lines 2" - 4". Refer to Support No C 2- Cradles shall not be used for Carbon Steel lines
Assembly Tag No: - DA7 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size DA7 Directional Anchor for Non-Insul. pipes on sleepers > 600mm
½" - 4"
Sheet B39
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS Cradle if required Ref. Support No C8 or C108 See Note 1
1
175
H
Supporting sleeper by others. NOTE- The maximum sleeper width is 1000.
2 Gap (typ)
L
4 gap
Pipe Size 6 - 14
10
250
Maximum Anchor Load (KN) With Cradle No Cradle 15.0 40.0
10
2
=
= A
Pipe Size Mark No 1 6 8 10 12 14 Notes
150 x 10 Plate
Total Length 1112 1136 1152 1192 1224
Mark No 2
10 Thk Plate
Area (cm²) 825 1000 1150 1350 1500
A 165 200 230 270 300
Dimensions L 160 160 160 160 160
H 278 284 288 298 306
1- Cradle is mandatory for stainless steel lines. Refer to Support No C108
Assembly Tag No: - DA7 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size DA7 Directional Anchor for Non-Insul. pipes on sleepers > 600mm
6" - 14"
Sheet B40
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS
Cradle if required Ref. Support No C8 or C108 See Note 1 2 175
H
Supporting sleeper by others. NOTE- The maximum sleeper width is 1000.
2 Gap (typ)
4 gap
L
1
10
250
Pipe Size 16 - 24 26 - 40
Maximum Anchor Load (KN) 50.0 100.0
A 250
Dimensions L T 200 10
10 =
= A
Pipe Size Mark No 1
Area (cm²) 2125
Mark No 2
Area (cm²) 2002
16 18 10 Thk 20 Plate 22 2550 2023 300 200 10 24 26 10 Thk 28 2975 Plate 2613 350 250 12 30 32 12 Thk 34 Plate 36 3400 2631 400 250 12 38 40 Notes 1- Cradle is mandatory for stainless steel lines. Refer to Support No C108 Assembly Tag No: - DA7 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
H 278 274 284 281 278 287 284 282 291 288 286 284 282
Pipe Size DA7 Directional Anchor for Non-Insul. pipes on sleepers > 600mm
16" - 40"
Sheet B41
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS Monolux Isolation Block or equivalent.
Pipe Insulation
60 Thk
150
150 Supporting steelwork by others
2 Gap (typ) =
=
1
L SECT Heat tubes
45o
250 Max Pipe Size 6
Dimension Mark No 1 L 800 HEA 100
Length
300 NOTE 1, For details of the SECT Traced Pipe Shoes refer to Specification No. 60-0000-L-SPE-1003. Assembly Tag No: - DA8 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size DA8 Directional Anchor for SECT Traced piping on steelwork 6"
Sheet B42
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS Monolux Isolation Block or equivalent.
Pipe Insulation 60 Thk
150
250 Supporting sleeper by others. NOTE- The maximum sleeper width is 500.
2 Gap (typ)
1
=
= L
45o
SECT Heat tubes
250 Max Pipe Size 6
Dimension Mark No 1 L 800 HEA 100
Length
500 NOTE 1, For details of the SECT Traced Pipe Shoes refer to Specification No. 60-0000-L-SPE-1003. Assembly Tag No: - DA9 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size DA9 Directional Anchor for SECT Traced piping on sleepers 6"
Sheet B43
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS
25
Cradle for Stainless lines only See Note 1
50 (typ)
80
1
100
250 Supporting sleeper by others. NOTE- The maximum sleeper width is 1000.
3 2 Gap (typ) 1300 NOTE - Lugs shall be tack welded to the shoe in the shop. The final weld shall be made in the field.
Gusset plates required on 3" and 4" pipes only
15 (typ)
Pipe Size ½-4
Maximum Anchor Load (KN) 12.0
2
100 Pipe Size Mark No 1 ½-2 IPE 200 3-4 IPE 200 Notes
Length 650 650
Mark No 2 10 Thk Plate
Area (cm²) Mark No 3 Area (cm²) HEA100 500 100 HEA100 500
1- Cradle is mandatory for stainless steel lines 2" - 4". Refer to Support No C108 2- Cradles shall not be used for Carbon Steel lines
Assembly Tag No: - DA10 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size DA10 Directional Anchor for Insul. pipes on sleepers > 600mm
½" - 4"
Sheet B44
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS Cradle if required Ref. Support No C8 or C108. Cradle is mandatory for SS pipes 1
35 (typ)
=
=
=
Cut Notches into Anchor
=
25
W
100
T 20 250
3
Supporting sleeper by others. NOTE- The maximum sleeper width is 1000.
2 Gap (typ) L
NOTE - Lugs shall be tack welded to the shoe in the shop. The final weld shall be made in the field. Pipe Size 6-8 10 - 16 2
30 (typ) Pipe Size 6 8 10 12 14 16
Pipe Size 6-8 10 12 14 16
Maximum Anchor Load (KN) No Cradle With Cradle 25.0 100.0 50.0 200.0
Dimension L T 1300 1300 1400 10 1400 1400
A 150 200 250 250 300
W
10
A Dimension Mark No 1 DA10 Mark No 2 H Area (cm²) 1521 1521 (See 10 Thk 1716 10 Thk Note 1) Plate 2001 Plate 2001 2196
Area (cm²) 1950 1950 2600 3500 3500 4200
Mark No 3
Total Length
HEA 100
500
HEA 160
500
Assembly Tag No: - DA10 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size DA10 Directional Anchor for Insul. pipes on sleepers≤ 600mm
6" - 16"
Sheet B45
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS X =
=
Stiffening Ring, where required
Y = 25 (typ)
Cut Notches into Anchor 80
W
H 75
T
75 C (typ)
Cradle is Mandatory Ref Support No C3
2 gap (typ) L
B
NOTE - Lugs shall be tack welded to the shoe in the shop. The final weld shall be made in the field.
Stiffening Ring
θ
6 Profile to Suit
1
6
2 3 N = No of Gusset Plates. Gusset Plates are to be evenly spaced
4 20 D
30 (typ)
=
Assembly Tag No: -DA11 or DA12 - X
5 Pipe Size 36 - 40
W (typ) = A
SUPPORT No SUPPORT TYPE PIPE SIZE
W (typ)
Maximum Anchor Load (KN) 400.0
Stiffening Ring Required for Pipe 36" and Above For Pipe Specs 150H26 & 150K26 For other Pipe Specs refer to Support Nos DA2 & DA3
Detail No Pipe Size DA11, DA12 Directional Anchor for Spec Nos. 150H26 & 150K26 for In 36" - 40"
Sheet B46
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 1
SPECIFICATION FOR PIPE SUPPORTS
W 10 10
Dimension C 10 10
Angle θ (Deg) 30
No of Gussets N 0
Area (cm²) 5735 6192 6635 7092
Mark No 2
Area (cm²) 1800 1800
Mark No 5
Support Type DA11 DA12
Pipe Size 36, 40 36, 40
H 100 150
Support Type DA11,DA12
Pipe Size 36, 40
Dimensions X Y 12 80
Support Type DA11
Pipe Size 36 40 36 40
Mark No 1
Pipe Size 36 40
Mark No 4
DA12
Support Type DA11,DA12 DA11,DA12
SUPPORT No SUPPORT TYPE PIPE SIZE
10 Thk Plate 10 Thk Plate
10 Thk Plate
T 12 12
10 Thk Plate 10 Thk Plate
10 Thk Plate
B 250 250
L 900 900
D 400 400
Area (cm²) 2514 3017 2909 3456
Mark No 3
Area (cm²) 7823 8615 7823 8615
Dimension A 869 957 869 957
Area (cm²) 1035 1035
Mark No 6
12 Thk Plate 12 Thk Plate
12 Thk Plate
DA11, DA12 Directional Anchor for Spec Nos. 150H26 & 150K26 (Dim 36" - 40"
Area (cm²) 2298 2554
Sheet B47
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS
=
=
=
W
25 (typ)
Cut Notches into Anchor 80
H 125
T
125 C (typ)
Cradle is Mandatory Ref Support No C7
2 gap (typ)
B L
θ
NOTE - Lugs shall be tack welded to the shoe in the shop. The final weld shall be made in the field.
1 6 2 3
N = No of Gusset Plates. Gusset Plates are to be evenly spaced
4 20 D
30 (typ)
W (typ)
5
W (typ) =
= A
Pipe Size 26 - 40
Maximum Anchor Load (KN) 400.0
Assembly Tag No: -DA5 or DA6 - X SUPPORT No SUPPORT TYPE PIPE SIZE
Detail No Pipe Size DA5, DA6 Directional Anchor for Insulated Pipes on Sleepers ≤600 26" - 40"
Sheet B48
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS
Support Type DA5 DA6
Pipe Size 26 - 40 26 - 40
H 100 150
T 12 12
Support Type DA5,DA6
Pipe Size 26 - 40
Angle θ (Deg) 30
No of Gussets N 0
Support Type
Pipe Size 26 28 30 32 34 36 38 40 26 28 30 32 34 36 38 40
Mark No 1
Area (cm²) 6122 6427 6732 7037 7342 7646 7951 8256 5492 5720 5949 6178 6406 6635 6863 7092
Mark No 2
Pipe Size 26 - 40
Mark No 4 (Plate) 10 Thk
Area (cm²) 3000
Mark No 5 (Plate) 10 Thk
DA5
DA6
Support Type DA5,DA6
SUPPORT No SUPPORT TYPE PIPE SIZE
10 Thk Plate
10 Thk Plate
W 10 10
10 Thk Plate
10 Thk Plate
Dimension C 10 10
Area (cm²) 1452 1642 1843 2056 2280 2514 2760 3017 1737 1949 2172 2407 2652 2909 3177 3456
B 250 250
L 1200 1200
D 400 400
Mark No 3
Area (cm²) 7791 8319 8847 9374 9902 10430 10958 11486 7791 8319 8847 9374 9902 10430 10958 11486
Dimension A 649 693 737 781 825 869 913 957 649 693 737 781 825 869 913 957
12 Thk Plate
12 Thk Plate
Area (cm²) 1725
DA5, DA6 Directional Anchor for Insulated Pipes on Sleepers (Dims 26" - 40"
Sheet B49
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS
Gusset plates required on 3" and 4" pipes only
25
60
1
90
2
15 (typ)
100
100
3 150 50 (typ)
2 Gap (typ) =
Do not weld this side of Shear lug
100 =
80 100
600 NOTE - Lugs shall be tack welded to the shoe in the shop. The final weld shall be made in the field.
Pipe Size ½-4 Pipe Size Mark No 1 ½-2 IPE 200 3-4 IPE 200
SUPPORT No SUPPORT TYPE PIPE SIZE
4 Isolation Pad. Site trim pad if it overlaps the steelwork
Maximum Anchor Load (KN) 12.0
Length 300 300
Mark No 2 Area (cm²) Mark No 3 Area (cm²) 10 Thk 200 10 Thk Plt 200 Plate 200
Mark No 4 Fabreeka Nitrile 21 Ply Pad 150 x 80 or equivalent
Dimensions Required: - None
Assembly Tag No: -DA13 - X Detail No
10
Pipe Size DA13 Directional Anchor for Acoustically Insulated Pipes ½" - 4"
Sheet B50
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS Cradle if required Ref. Support No C3 or C103. Cradle is mandatory for SS pipes 1
35 (typ)
=
=
=
Cut Notches into Anchor
=
25
10
90
T 20
3 150
Do not weld this side of Shear lug (typ)
L
Isolation Pad. Site trim pad if it overlaps the steelwork
B A Pipe Size 6 8 10 12 14 16 18 20 22 24
Mark No 1
10 Thk Plate
Area (cm²) 891 891 1086 1371 1371 1566 1656 1851 1851 2046
Mark No 2
10 Thk Plate
12 Thk Plate
2 Gap (typ)
6-8 10 - 24 Pipe Size 6-8 10 12 14 16 18 20 - 22 24
A 150 200 250 250 300 300 350 400
Pipe Size
30 (typ)
150
NOTE - Lugs shall be tack welded to the shoe in the shop. The final weld shall be made in the field. Maximum Anchor Load (KN) No Cradle With Cradle 25.0 100.0 50.0 200.0
4
2
100
Area (cm²) 900 900 1200 1750 1750 2100 2400 2800 2800 3200
Dimension L T 600 600 700 10 700 700 800 800 12 800
Mark No 3
Total Length
HEA 100
300
HEA 160
300
HEA 200
300
Mark No 4
Fabreeka Nitrile 21 Ply Pad or equivalent
B 100 150 200 200 250 250 300 350 Size 150 x 100 150 x 100 150 x 150 200 x 150 200 x 150 250 x 150 250 x 150 300 x 150 300 x 150 350 x 150
Assembly Tag No: -DA13 - X Detail No Pipe Size SUPPORT No DA13 SUPPORT TYPE Directional Anchor for Acoustically Insulated Pipes PIPE SIZE 6" - 24"
Sheet B51
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS
=
=
= 25 (typ)
Cut Notches into Anchor 70
W
100 75
T
75
150
C (typ)
Cradle is Mandatory Ref Support No C3
θ
90
2 gap (typ) L
B
NOTE - Lugs shall be tack welded to the shoe in the shop. The final weld shall be made in the field.
1 6
6 Isolation Pad. Site trim pad if it overlaps the steelwork
2 E 3 4 20 D
30 (typ)
W (typ)
5
W (typ) =
= A
Assembly Tag No: -DA13 - X Detail No Pipe Size SUPPORT No DA13 SUPPORT TYPE Directional Anchor for Acoustically Insulated Pipes PIPE SIZE 26" - 40"
Sheet B52
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS
Support Type DA13
Pipe Size 26 - 40
H 100
Support Type DA13
Pipe Size 26 - 40
Angle θ (Deg) 30
Support Type
Pipe Size 26 28 30 32 34 36 38 40
Mark No 1
Pipe Size 26 28 30 32 34 36 38 40
Mark No 3
Pipe Size 26 - 40
Mark No 4
DA13
Support Type
DA13
Support Type DA13
SUPPORT No SUPPORT TYPE PIPE SIZE
10 Thk Plate
12 Thk Plate
10 Thk Plate
Dimension C 10
T 12
W 10
Area (cm²) 4592 4820 5049 5278 5506 5735 5963 6192
Mark No 2
Area (cm²) 5843 6239 6635 7031 7427 7823 8219 8615
Dimension A 649 693 737 781 825 869 913 957
Mark No 6
Area (cm²) 1800
Mark No 5
Area (cm²) 1035
10 Thk Plate
10 Thk Plate
B 250
L 900
Size
Dimension E 500 500 550 600 650 700 750 800
D 400
Area (cm²) 1452 1642 1843 2056 2280 2514 2760 3017
Fabreeka Nitrile 21 Ply Pad or equivalent
500 x 150 500 x 150 550 x 150 600 x 150 650 x 150 700 x 150 750 x 150 800 x 150
DA13 Directional Anchor for Acoustically Insulated Pipes (Dims 26" - 40"
Sheet B53
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS
Ref Cradle, Support No C-101, C-102 or C-103
75
H
4 gap
1
150
10 L
2 gap (typ)
2
10 =
= A
Pipe Size 8 - 14
Pipe Size 8 10 12 14
Mark No 1 150 x 10 Stainless Steel Plate ASTM-A-240 Type 316
Maximum Anchor Load (KN) 40.0
Total Length 736 752 792 824
Mark No 2 10 Thk Stainless Steel Plate ASTM-A-240 Type 316
Area (cm²) 600 690 810 900
A 200 230 270 300
Dimensions L 160 160 160 160
H 184 188 198 206
Assembly Tag No: - DA103 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size DA103 Directional Anchor for Non-Insulated or PPC piping with a design temp of -60°C or below 8" - 14"
Sheet B54
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS
Ref Cradle, Support No C-101, C-102 or C-103
1 2
T
T
150
H
4 gap
75
10
2 gap (typ)
1
=
L
16 18 20 22 24
Mark No 1 10 Thk Stainless Steel Plate ASTM-A-240 Type 316
= A
Pipe Size 16 - 24
Pipe Size
10
Area (cm²) 1125
1350
Maximum Anchor Load (KN) 50.0
Mark No 2 10 Thk Stainless Steel Plate ASTM-A-240 Type 316
Area (cm²) 1200
A 250
Dimensions L T 200 10
1200
300
200
10
H 178 174 184 181 178
Assembly Tag No: - DA103 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size DA103 Directional Anchor for Non-Insulated or PPC piping with a design temp of -60°C or below 16" - 24"
Sheet B55
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS
Monolux Isolation Block or equivalent.
Pipe Insulation
60 Thk
150
SECT Heat tubes
45o
NOTE 1, For details of the SECT Traced Pipe Shoes refer to Specification No. 60-0000-L-SPE-1003. 2, Support shall be used with Anchor Lugs DA8
Assembly Tag No: - SAS1 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size SAS1 Anchor Shoe for SECT Traced piping on steelwork All Sizes
Sheet B56
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS
Monolux Isolation Block or equivalent.
Pipe Insulation 60 Thk
150
Supporting sleeper by others. NOTE- The maximum sleeper width is 500.
45o
SECT Heat tubes
NOTE 1, For details of the SECT Traced Pipe Shoes refer to Specification No. 60-0000-L-SPE-1003. 2, Support shall be used with Anchor Lugs DA9
Assembly Tag No: - SAS2 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size SAS2 Anchor Shoe for SECT Traced piping on Sleepers All Sizes
Sheet B57
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS 6mm Weep Hole seal with mastic after welding
For Trunnion Details Refer to Iso.
X 1
A
The Elevation of the trunnion shall allow for 12mm Field Shim.
X
750 (Max)
250
View X-X Round Plate
NOTES 1- Unless otherwise advised by Piping Stress the Trunnion sizes that shall be used are listed below Pipe Size Trunnion Size
2", 3" 2"
4" 3"
6" 4"
8" 6"
10" 8"
Pipe Size Trunnion Size
12", 14" 10"
16", 18" 12"
20" - 24" 16"
26" - 30" 20"
32" - 36" 24"
Trunnion Dimension Mark No 1 2 Size Description Area (cm ) A 2 100 100 3 144 120 4 6 Thk 225 150 6 Round 400 200 8 Plate 625 250 10 961 310 12 1296 360 16 10 Thk 2025 450 20 Round 3025 550 24 Plate 4225 650 26 4900 700 Assembly Tag No: - T1 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Dimensions Required: - None
Trunnion Size T1 Horizontal Trunnion Support from Pipe (1 Off) 2" - 36"
Sheet C1
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
For Trunnion Details Refer to Iso. 1
View X-X
Round Plate
X
A
A
1
X 6mm Weep Hole seal with mastic after welding (Typ)
750 (Max)
The Elevation of the trunnion shall allow for 12mm Field Shim.
250
NOTES 1- Unless otherwise advised by Piping Stress the Trunnion sizes that shall be used are listed below Pipe Size Trunnion Size
2", 3" 2"
4" 3"
6" 4"
8" 6"
10" 8"
Pipe Size Trunnion Size
12", 14" 10"
16", 18" 12"
20" - 24" 16"
26" - 30" 20"
32" - 36" 24"
Trunnion Dimension Mark No 1 2 ) Area (cm A Size Description 2 200 100 3 288 120 4 6 Thk 450 150 6 Round 800 200 8 Plate 1250 250 10 1922 310 12 2592 360 16 10 Thk 4050 450 20 Round 6050 550 24 Plate 8450 650 Assembly Tag No: - T2 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Dimensions Required: - None Trunnion Size
T2 Horizontal Trunnion Support from Pipe (2 Off) 2" - 36"
Sheet C2
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
Material Grade Pipe Size 50 100 150 200 250 300 350 400
Temperature °C
Pad if required. Ref Spec No 60-0000-L-SPE-0014
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2 Temperature Correction Factor Carbon Steel Stain. Steel A333 Gr 8 A671 CC 60 A312 TP316/L 2" - 16" 18" - 36" 2" - 36" 1.00 1.00 1.00 1.00 0.97 1.00 1.00 0.94 1.00 1.00 0.96 0.92 0.91 0.95 0.88 0.89 0.81 0.86 0.83 0.76 0.83 0.65 0.65 0.81
D (m) Load (N)
Pipe Size (") 2 3 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
Bending Moment = D x Load
Allowable Bending Moment (Nm) Trun Corrosion Allowance = 1.5mm Corrosion Allowance = 3.0mm Size Sch 80 Sch 20 Sch 40 Sch 80 Sch 20 Sch 40 (") No Pad Pad No Pad Pad No Pad Pad No Pad Pad No Pad Pad No Pad Pad 2 163 375 13 119 2 303 1317 593 2309 93 760 271 1462 3 708 2963 1419 5371 248 1732 691 3422 4 1352 5365 3039 10978 566 3253 1661 7214 6 3371 12895 7466 26404 1559 7971 4250 17465 8 6466 24073 15229 52753 3222 15207 9088 35470 10 11183 40821 27751 94737 5839 26081 17019 64145 10 12236 44105 30568 103570 6400 27635 18489 68473 12 8621 33232 20305 71806 48854 164023 3753 19652 11132 45742 30141 109305 12 8128 31332 23390 81530 54643 182147 3539 18528 13271 52591 34232 122142 16 17124 63423 38411 133052 95079 315113 8347 38819 22110 86293 60293 212371 16 16327 60471 40000 137797 104368 344225 7959 37012 23316 89798 66855 232973 16 15632 57897 44871 153170 113366 372416 7620 35437 26697 100610 73218 252930 20 39181 138561 21480 88265 20 37756 133521 20699 85054 20 36475 128993 19997 82170 24 50857 179852 87433 298461 27881 114568 52020 196045 24 49338 174482 84822 289550 27049 111147 50467 190191 24 47948 169566 95048 322042 26287 108016 57490 212910
Notes 1- The loads shown are for one trunnion. When two trunnions are used the actual piping load shall be divided by two. 2- The table is for carbon steel & stainless steel pipes up to 50°C. For higher temperatures the allowable loads shall be multiplied by the temperature correction factor (see above table). 3- For pipe schedules not listed the allowable load = tabulated load xp1.5 t /tt1.5 Where tp is the thickness of the pipe in question less mill tolerance and corrosion allowance and, tt is the thickness of the tabulated pipe less mill tolerance and corrosion allowance SUPPORT No SUPPORT TYPE PIPE SIZE
T1, T2 Horizontal Trunnion Allowable Loads 2" - 36"
Sheet C3
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
For Trunnion Details Refer to Iso.
1
View X-X
Round Plate
X
A
X 6mm Weep Hole seal with mastic after welding
250
1000 (Max)
NOTES 1- For allowable loads see Sheet C17 2- Unless otherwise advised by Piping Stress the Trunnion sizes that shall be used are listed below 2", 3" 4" 6" 8" 10" Pipe Size 2" 3" 4" 6" 8" Trunnion Size Pipe Size Trunnion Size
12", 14" 10"
Trunnion Dimension Mark No 1 2 Size Description Area (cm ) A 2 100 100 3 6 Thk 144 120 4 Round 225 150 6 Plate 400 200 8 625 250 Assembly Tag No: - T3 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
16", 18" 12"
20" - 24" 16"
26" - 30" 20"
32" - 36" 24"
Trunnion Dimension Mark No 1 2 Size Description Area (cm ) A 10 6 Thk 961 310 12 Rnd. Plate 1296 360 16 10 Thk 2025 450 20 Round 3025 550 24 Plate 4225 650
Dimensions Required: - None Trunnion Size
T3 Horizontal Trunnion Support from Elbow 2" - 36"
Sheet C4
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 4
SPECIFICATION FOR PIPE SUPPORTS
NOTE: - This support shall not be used from grade in un-paved areas.
For Trunnion Details Refer to Iso.
Ref Support No BS4 Field Weld Detail A Trunnion Size 2" - 16" Minimum Gap
2
Field Weld A
For bottom of Trunnion EL see Table below
1.6 ± 350 0.8mm Site Trim to suit
350
10
1 A
2
20 weep hole
2
Detail B Trunnion Size 18" to 24"
1
Unless advised by Piping Stress the Trunnion sizes that shall be used are listed below: Pipe Size Trunnion Size Pipe Size Trunnion Size
2", 3" 2" 16", 18" 10"
Trunnion Size (") Pipe Support Foundation or Baseplate Bottom of Trunnion elevation Trunnion Dimension Size A 2 150 3 180 4 230 6 290 8 320 10 350 12 380 16 500 18 530 20 560 24 650
Mark No 1 3" Sch XS Pipe 4" Sch XS Pipe 6" Sch 40 Pipe 8" Sch 40 Pipe 10" Sch 40 Pipe 12" Std Pipe 14" Std Pipe 18" Sch 40 Pipe 18" Sch 40 Pipe 20" Sch Std Pipe 24" Sch Std Pipe
4" 3" 20", 22" 12"
6" 4" 24" - 26" 16"
8", 10" 6" 30" - 34" 20"
12", 14" 8" 36" - 40" 24"
Support at Grade Support on Steelwork All 2 - 12 16 - 24 BPS Where req'd BP1 F8 or F9 TOS + 150 100150 100350 Total Length
Mark No 2
330
10 Thk Square Plate
326
12 Thk Square Plate
335
15 Thk Sqr Plate
Area (cm2) 450 648 1058 1682 2048 2450 2888 5000 2809 3136 4225
Assembly Tag No: - BS1 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Trunnion Size BS1 Non-Adjustable Base Support 2" - 40"
55°
Sheet C5
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
For Trunnion Details Refer to Iso. View X-X X
1
X
3 Installation H Height
2
Hole Dia D
10
B (typ)
3
=
= A
Grind smooth after welding NOTE: -This support, when located at grade, shall be used in conjunction with Pipe Support foundations F8 or F9, to ensure a consistent elevation. Unless otherwise advised by Piping Stress the Trunnion sizes that shall be used are listed below Pipe Size Trunnion Size
2", 3" 2"
4" 3"
6" 4"
8", 10" 6"
12", 14" 8"
Pipe Size Trunnion Size
16", 18" 10"
20", 22" 12"
24" - 26" 16"
30" - 34" 20"
36" - 40" 24"
Assembly Tag No: - BS2 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Trunnion Size BS2 Adjustable Base Support 2" - 40"
Sheet C6
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Trunnion Size 2 3 4 6 8 10 12 16 20 24
Mark No 1 (8 Off) M20 Hex Nut Heavy Type M24 Hex Nut Heavy Type
Mark No 2 (4 Off) M20 Stud Bolt 150 Long M24 Stud Bolt 150 Long
M30 Hex Nut Heavy Type
M30 Stud Bolt 200 Long
15 Thk Plate
M36 Hex Nut Heavy Type
M36 Stud Bolt 200 Long
20 Thk Plate
Trunnion Size 2 3 4 6 8 10 12 16 20 24
SUPPORT No SUPPORT TYPE PIPE SIZE
A 200 200 260 290 320 350 380 500 560 650
Mark No 3
12 Thk Plate
Dimensions B D 30
Area (cm2) 800 800 1352 1682 2048 2450 2888 5000 6272 8450
H
22 100 26
45 32 130 55
BS2 Adjustable Base Support (Dimensions) 2" - 40"
38
Sheet C7
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
For Trunnion Details Refer to Iso.
Existing Trunnion Support (BS1) or Adjustable Trunnion Support (BS2).
17
1 2 5
=
Symmetrically weld 5mm Thick square S.S. Plate to underside of Trunnion Support.
= A
Note: -
For PTFE details and installation instructions refer to Spec No 60-0000-L-SPE-1003
Trunnion Mark No 1 Size 2-4 5 Thk Polished Stainless Steel 6-8 Plate ASTM-A-240 Type 316 10 - 12 or Equivalent.
Area (cm²) 169 400 900
Mark No 2 PTFE pad Type A PTFE pad Type B PTFE pad Type D
No Off 1 1 1
Dimension A 130 200 300
Assembly Tag No: - BS3 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Trunnion Size BS3 PTFE for Existing Base Support 2" - 22"
Sheet C8
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
For Trunnion Details Refer to Iso.
View X-X
2 Existing Trunnion Support (BS1) or Adjustable Trunnion Support (BS2).
1
B B
17
5
X
=
=
X
B
B
A Note: -
For PTFE details and installation instructions refer to Spec No 60-0000-L-SPE-1003
Trunnion Mark No 1 Size 16 5 Thk Polished Stainless Steel 20 Square Plate ASTM-A-240 24 Type 316 or Equivalent.
Area (cm²) 1600 2025 2500
Mark No 2
No Off
PTFE pad Type B
4 4 4
Dimension A B 400 100 450 125 500 150
Assembly Tag No: - BS3 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Trunnion Size BS3 PTFE for Existing Base Support 24" - 40"
Sheet C9
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Ref BS1
X
1
X
100 Weld Angles to Existing BasePlate
2 Gap (Typ)
Do not weld this face of the guide
=
=
Trunnion Size 2-6 8 - 12 16,20,24
Mark No1 (4 Off) 60 x 6 Angle 100 x 10 Angle HEA 100
View X-X
Total Length 400 400 400
Assembly Tag No: - BA1 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Trunnion Size BA1 Base Anchor for Non-Adjustable Support 2" - 40"
Sheet C10
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
For Trunnion Details Refer to Iso.
1
Ref BS2
X
X
H 2 Gap (Typ)
Do not weld this face of the guide
= View X-X =
Trunnion Dimension Size H 2-6 150 8 - 12 180 16,20,24 180
Mark No1 (4 Off) 60 x 6 Angle 100 x 10 Angle HEA 100
Total Length 600 720 720
Assembly Tag No: - BA2 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Trunnion Size BA2 Base Anchor for Adjustable Support 2" - 40"
Sheet C11
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS
Ref BS1
X
1
X
100 Weld Angles to Existing BasePlate
Do not weld this face of the guide
2 Gap (Typ)
=
For Correct Orientation of Guides Refer to the Isometric
=
Trunnion Size 2-6 8 - 12 16,20,24
Mark No1 (2 Off) 60 x 6 Angle 100 x 10 Angle HEA 100
View X-X
Total Length 200 200 200
Assembly Tag No: - BG1 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Trunnion Size BG1 Base Guide for Non-Adjustable Support 2" - 40"
Sheet C12
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS
For Trunnion Details Refer to Iso.
Ref BS2
X
X
1
H 2 Gap (Typ) For Correct Orientation of Guides Refer to the Isometric
Do not weld this face of the guide
= View X-X =
Trunnion Size 2-6 8 - 12 16,20,24
Mark No1 (2 Off) 60 x 6 Angle 100 x 10 Angle HEA 100
Total Length 300 360 360
Dimension H 150 180 180
Assembly Tag No: - BG2 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Trunnion Size BG2 Base Guide for Adjustable Support 2" - 40"
Sheet C13
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS
For Details of Trunnion Refer to Iso NOTE 1
Existing Trunnion Support 3
1
X
X 6 25 (Min) Grout Type G1
150 2
100 Bolt Penetration
200
Existing Paving
NOTE 1 4
= A = 50 (Typ) A View X-X
Hole Dia = D
NOTES 1- Refer to Section 10 of this Spec for a procedure for the installation of bolts, grouting and monitoring the settlement of the paving 2- For General Notes refer to Drawing Nos. 60-0000-Q-STD-0010-01 and 02 3- Hilti HIT-ICE resin to be used if the installation temperature is below -5°C) Trunnion Size 2-3 4-6
Trunnion Size 2-3 4-6
Mark No 1 (Note 3) (4 Off)
Mark No 2 Area (cm²) Mark No 3 (8 Off) M20 threaded rod with Hilti HY150 20 Thk 1764 M20 Nuts resin capsule adhesive 280 Long Plate M30 threaded rod with Hilti HY150 20 Thk 3025 M30 Nuts resin capsule adhesive 280 Long Plate Mark No 5 Cementitious Grout (G1) 0.01m3
Mark No 6 (8 Off) M20 Washers M30 Washers
Dimension A D 420 22 550
33
Max Loads (KN) Trunnion 200 Thick Paving Size Vertical Shear 2-3 20.0 6.0 4-6 25.0 12.0
Assembly Tag No: - BP - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Trunnion Size BP Base Plate from grade 2" - 10"
Sheet C14
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 4
SPECIFICATION FOR PIPE SUPPORTS
NOTE: - This support shall only be used from grade in un-paved areas. For other locations refer to BS1
For Trunnion Details Refer to Iso.
Field Weld Detail A Trunnion Size 2" - 16" Minimum Gap
2 A 1
For bottom of Trunnion EL 100275
Field Weld
weep hole 150
2
U/S baseplate EL 100200
1.6 ± 0.8mm
20
350 Site Trim to suit
10 A
20
55°
3 2
1
Detail B Trunnion Size 18" to 24"
Unless advised by Piping Stress the Trunnion sizes that shall be used are listed below: Pipe Size 2", 3" 4" 6" 8", 10" 12", 14" Trunnion Size 2" 3" 4" 6" 8" Pipe Size 16", 18" 20", 22" 24" - 26" 30" - 34" 36" - 40" Trunnion Size 10" 12" 16" 20" 24" Trunnion Dimension Size A 2 150 3 180 4 230 6 290 8 320 10 350 12 380 16 500 18 530 20 560 24 650
Mark No 1 3" Sch XS Pipe 4" Sch XS Pipe 6" Sch 40 Pipe 8" Sch 40 Pipe 10" Sch 40 Pipe 12" Std Pipe 14" Std Pipe 18" Sch 40 Pipe 18" Sch 40 Pipe 20" Sch Std Pipe 24" Sch Std Pipe
Total Length
Area 2 (cm )
Mark No 2
130
10 Thk Square Plate
126
12 Thk Square Plate 2000 2400 2900
15 Thk Sqr Plate
Area 2 (cm ) 450 648 1058 1682 2048 2450 2888 5000 2809 3136 4225
Mark No 3 Pipe Support Foundat'n F9-4 Pipe Support Foundat'n F9-4
Assembly Tag No: - BS4 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Trunnion Size BS4 Non-Adjustable Base Support for un-paved areas 2" - 40"
Sheet C15
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
For Details of Trunnion Refer to Iso
Existing Trunnion Support
X
X
1
Field weld plate to existing steelwork
= A =
A View X-X
Trunnion Mark No 1 Area (cm²) Dimension A Size 2-3 10 Thk 1764 420 4-6 Plate 3025 550 8 - 12 12 Thk 4900 700 Plate NOTE: - The allowable loads are limited by the supporting steelwork Assembly Tag No: - BPS - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Trunnion Size BPS Base Plate from Steelwork 2" - 22"
Sheet C16
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Temperature °C
Load (N)
D (m)
Temperature Correction Factor St. Steel Carbon Steel Material Grade A333 A671 A312 Gr 8 CC 60 TP316/L 2" - 16" 18" - 36" 2" - 36" Pipe Size 50 1.00 1.00 1.00 100 1.00 0.97 1.00 150 1.00 0.94 1.00 200 1.00 0.92 0.96 250 0.95 0.88 0.91 300 0.89 0.81 0.86 350 0.83 0.76 0.83 400 0.65 0.65 0.81
Bending Moment = D x Load Pipe Size (") 2 3 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
Trun Size (") 2 2 3 4 6 8 10 10 12 12 16 16 16 20 20 20 24 24 24
Allowable Bending Moment (Nm) c.a. = 1.5mm c.a. = 3.0mm Sch 20 Sch 40 Sch 80 Sch 20 Sch 40 Sch 80
8621
163
375
13
303
593
93
119 271
708
1419
248
691
1352
3039
566
1661
3371
7466
1559
4250
6466
15229
3222
9088
11183
27751
5839
17019
12236
30568
20305
48854
3753
6400
18489
11132
30141
8128
23390
54643
3539
13271
34232
17124
38411
95079
8347
22110
60293
16327
40000
104368
7959
23316
66855
15632
44871
113366
7620
26697
73218
39181
21480
37756
20699
36475
19997
50857
87433
27881
52020
49338
84822
27049
50467
47948
95048
26287
57490
Notes 1- The table is for carbon steel & stainless steel pipes up to 50°C. For higher temperatures the allowable loads shall be multiplied by the temperature correction factor (see above table). 2- For pipe schedules not listed the allowable load = tabulated load xp1.5 t /tt1.5 Where tp is the thickness of the pipe in question less mill tolerance and corrosion allowance and, tt is the thickness of the tabulated pipe less mill tolerance and corrosion allowance SUPPORT No SUPPORT TYPE PIPE SIZE
T3 Allowable Loads for Horizontal Trunnion from Elbows 2" - 36"
Sheet C17
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 4
SPECIFICATION FOR PIPE SUPPORTS
NOTE: - This support shall be used in paved areas from plinths & in non-paved areas from spread-footing foundations Nos F9-6 to F9-10 Field Weld Detail A Trunnion Size 2" - 16"
For Trunnion Details Refer to Iso.
Minimum Gap A
2
Field Weld
For bottom of Trunnion EL 100275
weep hole
150
1 2
1.6 ± 0.8mm
20
U/S baseplate EL 100200 20
350 Site Trim to suit
10 A
Paving or grade
55°
2
1
Detail B Trunnion Size 18" to 24"
Pipe Support Foundation 3 F8N3-XX.Where XX is trunnion size
Ref. Foundation F9-6 to F9-10 or Civil designed foundation
Unless advised by Piping Stress the Trunnion sizes that shall be used are listed below: 2", 3" 4" 6" 8", 10" 12", 14" Pipe Size 2" 3" 4" 6" 8" Trunnion Size 16", 18" 20", 22" 24" - 26" 30" - 34" 36" - 40" Pipe Size 10" 12" 16" 20" 24" Trunnion Size Trunnion Dimension Size A 2 150 3 180 4 230 6 290 8 320 10 350 12 380 16 500 20 560 24 650
Mark No 1 3" Sch XS Pipe 4" Sch XS Pipe 6" Sch 40 Pipe 8" Sch 40 Pipe 10" Sch 40 Pipe 12" Sch Std Pipe 14" Std Pipe 18" Std Pipe 20" Sch Std Pipe 24" Sch Std Pipe
Total Length
Area (cm 2)
Mark No 2
130
10 Thk Square Plate
126
12 Thk Square Plate 15 Thk Sqr Plate
2400 2900
Area (cm 2) 450 648 1058 1682 2048 2450 2888 5000 3136 4225
Mark No 3 F8N3-2 F8N3-3 F8N3-4 F8N3-6 F8N3-8 F8N3-10 F8N3-12 F8N3-16 F8N3-20 F8N3-24
Assembly Tag No: - BS5 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Trunnion Size BS5 Non-Adjustable Base Support for paved areas and non-paved areas from spread-footing type foundations 2" - 40"
Sheet C18
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 4
SPECIFICATION FOR PIPE SUPPORTS
Detail A Trunnion Size 2" - 16" Field Weld
For Trunnion Details Refer to Iso.
Minimum Gap 2
A Field Weld
Trunnion EL TOS + 75
weep hole 150
1.6 ± 0.8mm
10
1
350 Site Trim to suit
20
A
2
2
1
Detail B Trunnion Size 18" to 24"
Unless advised by Piping Stress the Trunnion sizes that shall be used are listed below: 2", 3" 2" 16", 18" 10"
Pipe Size Trunnion Size Pipe Size Trunnion Size Trunnion Dimension Size A 2 150 3 180 4 230 6 290 8 320 10 350 12 380 16 500 18 530 20 560 24 650
Mark No 1 3" Sch XS Pipe 4" Sch XS Pipe 6" Sch 40 Pipe 8" Sch 40 Pipe 10" Sch 40 Pipe 12" Std Pipe 14" Std Pipe 18" Sch 40 Pipe 18" Sch 40 Pipe 20" Sch Std Pipe 24" Sch Std Pipe
4" 3" 20", 22" 12"
6" 4" 24" - 26" 16"
8", 10" 6" 30" - 34" 20"
12", 14" 8" 36" - 40" 24"
Total Length
Area (cm 2)
Mark No 2
Area (cm 2) 450 648 1058 1682 2048 2450 2888 5000 2809 3136 4225
130
10 Thk Square Plate
126
12 Thk Square Plate 1950 2400 2900
15 Thk Sqr Plate
Assembly Tag No: - BS6 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Trunnion Size BS6 Small Non-Adjustable Base Support from existing steel 2" - 40"
55°
Sheet C19
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 1
SPECIFICATION FOR PIPE SUPPORTS
Full encirclement pad, shall be supplied to site in at least 2 pieces
Trunnion. Spec shall be the same as the pipe
2
1
View X-X
Round Plate
X
B A
A
1
X 6mm Weep Hole seal with mastic after welding (Typ). 1 weephole is required per section of encirclement pad
250 L
The Elevation of the trunnion shall allow for 12mm Field Shim.
NOTE - 1- For welding details of the trunnion refer to Standard Piping Detail No 19 in Spec No 60-0000-L-SPE-0014 2- The trunnion shall be welded to the pipe before welding the reinforcing cradle 3- Both welds shall be completed in the field
Pipe Size 48 54 60 66 70 Pipe Size 48 54 60 66 70
Pipe Spec 150K26 150H26 150K26 150H26 150K26
Trunnion Size 30 30 30 36 36
Mark No 1
2
Pipe Trunnion Size Size 48",54",60" 30" 66",70" 36"
Mark No 2
2
Dimension A B 790 1525 940 1830
Dimension
Description Area (cm ) Description Area (cm )
10 Thk Round Plate
12482 12482 12482 17672 17672
Assembly Tag No: - T2 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
10 Thk Plate
59377 66679 73982 97541 103382
1525 1525 1525 1830 1830
Dimensions Required: - None Trunnion Size
T2 Horizontal Trunnion Support from Pipe (2 Off) 48" - 70"
Sheet C20
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
1
2 6 3
H
2
4 5
1
Supt. No HR1 (Light Loads) Supt. No HR2 (Heavy Loads)
Pipe Size ½ - 1½ 2 3 4 6-8 10 12 14 - 18 20 - 24 26 - 30
Supt. No HR3 (Light Loads)
HR1 HR2 HR3 Max Max Max Dimension H Load (KN) Load (KN) Load (KN) Maximum Minimum 400 4.0 4.0 12.0 2000 500 7.0 7.0
20.0
12.0
35.0
600 800 2200 2400
50.0
900 1000 1100
Assembly Tag No: - HR1 or HR2 or HR3 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
HR1, HR2, HR3 Non-Adjustable Hangers for Bare Pipes ½" - 30"
Sheet D1
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Pipe Support No HR1, Hanger with 2-Bolt Clamp for Light Loads Pipe Size ½ - 1½ 2-4 6 - 12 14 - 18 20 - 24
Mark No 1 (1 Off)
Pipe Size ½ - 1½ 2-4 6 - 12 14 - 18 20 - 24
Mark No 4 (1 Off)
Lug
Size L-12 L-16 L-20 L-24 L-30 Size
Mark No 2 (1 Off)
Clevis
Mark No 5 (1 Off)
WENR-12 Weldless WENR-16 Eye Nut WENR-20 Pipe Clip WENR-24 WENR-30
Size CLR-12 CLR-16 CLR-20 CLR-24 CLR-30 Size
Mark No 3 (1 Off)
Size R-12A R-16A R-20A R-24A R-30A
Threaded Sling Rod
Mark No 6 (1 Off)
PC1 Size as Pipe
Size M12 M16 M20 M24 M30
Nut
Pipe Support No HR2, Hanger with 2- Bolt Clamp for Heavy Loads Pipe Size 3 4-8 10 - 12 14 - 24 26 - 30
Mark No 1 (1 Off)
Pipe Size 3 4-8 10 - 12 14 - 24 26 - 30
Mark No 4 (1 Off)
Lug
Size L-20 L-24 L-30 L-36 L-42
Size
Mark No 2 (1 Off)
Clevis
Mark No 5 (1 Off)
WENR-20 Weldless WENR-24 Eye Nut WENR-30 Pipe Clip WENR-36 WENR-42
Size CLR-20 CLR-24 CLR-30 CLR-36 CLR-42
Size
Mark No 3 (1 Off) Threaded Sling Rod
Mark No 6 (1 Off)
PC2 Size as Pipe
Nut
Size R-20A R-24A R-30A R-36A R-42A
Size M20 M24 M30 M36 M42
Pipe Support No HR3, Hanger with Lug for Light Loads Pipe Size ½ - 1½ 2-4 6 - 10
Mark No 1 (2 Off) Welding Lug
SUPPORT No SUPPORT TYPE PIPE SIZE
Size L-12 L-16 L-20
Mark No 2 (2 Off) Clevis
Size CLR-12 CLR-16 CLR-20
Mark No 3 (1 Off) Threaded Sling Rod
Size R-12A R-16A R-20A
HR1, HR2, HR3 Non-Adjustable Hangers for Bare Pipes (Dimensions) ½" - 30"
Mark No 6 (1 Off) Nut
Size M12 M16 M20
Sheet D2
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
1
2
6
H 3
4
5
Supt. No HR4 (Light Loads) Supt. No HR5 (Heavy Loads)
Pipe Size ½-1 1½ - 2 3-4 6-8 10 - 12 14 16 - 20 22 - 24
HR4 HR5 Maximum Maximum Dimension H Load (KN) Load (KN) Maximum Minimum 5.0 500 5.0 2000 10.0 600 10.0 30.0 700 15.0 40.0 2200 900 18.0 40.0 1000 23.0 45.0 2400 1100 23.0 50.0 1200
Assembly Tag No: - HR4 or HR5 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
HR4, HR5 Non-Adjustable Hanger for Insulated Pipes ½" - 24"
Sheet D3
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Pipe Support No HR4, Hanger with 3-Bolt Clamp for Light Loads Pipe Size ½-1 1½ - 4 6 - 12 14 - 20 22 - 24
Mark No 1 (1 Off)
Pipe Size ½-1 1½ - 4 6 - 12 14 - 20 22 - 24
Mark No 4 (1 Off)
Lug
Size L-12 L-16 L-20 L-24 L-30 Size
Mark No 2 (1 Off)
Clevis
Mark No 5 (1 Off)
WENR-12 Weldless WENR-16 Eye Nut WENR-20 Pipe Clip WENR-24 WENR-30
Size CLR-12 CLR-16 CLR-20 CLR-24 CLR-30 Size
PC3 Size as Pipe
Mark No 3 (1 Off) Threaded Sling Rod
Mark No 6 (1 Off)
Nut
Size R-12A R-16A R-20A R-24A R-30 Size M12 M16 M20 M24 M30
Pipe Support No HR5, Hanger with 3- Bolt Clamp for Heavy Loads Pipe Size 6-8 10 - 14 16 - 24
Mark No 1 (1 Off) Welding Lug
Pipe Size 6-8 10 - 14 16 - 24
Mark No 4 Size Mark No 5 (1 Off) (1 Off) Weldless WENR-30 Eye Nut WENR-36 Pipe Clip WENR-42
SUPPORT No SUPPORT TYPE PIPE SIZE
Size L-30 L-36 L-42
Mark No 2 (1 Off) Clevis
Size CLR-30 CLR-36 CLR-42 Size PC4 Size as Pipe
Mark No 3 (1 Off) Threaded Sling Rod
Mark No 6 (1 Off) Nut
HR4, HR5 Non-Adjustable Hanger for Insulated Pipes (Dim'ns) ½" - 24"
Size R-30A R-36A R-42A Size M30 M36 M42
Sheet D4
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
1 2 7 3 4
H
5
L.H. Thread Rod, Nut & Clevis (Typ)
8
6 1
Supt. No HR6 (Light Loads) Supt. No HR7 (Heavy Loads) Pipe Size ½ - 1½ 2 3 4 6-8 10 12 14 - 18 20 - 24 26 - 30
Supt. No HR8 (Light Loads)
HR6 HR7 HR8 Max Max Max Dimension H Load (KN) Load (KN) Load (KN) Maximum Minimum 600 4.0 4.0 12.0 2000 700 7.0 7.0
20.0
12.0
35.0
800 1050 2200 2400
50.0
1150 1250 1350
Assembly Tag No: - HR6 or HR7 or HR8 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
HR6, HR7, HR8 Adjustable Hangers for Bare Pipes ½" - 30"
Sheet D5
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Pipe Support No HR6, Hanger with 2-Bolt Clamp for Light Loads
Pipe Size ½ - 1½ 2-4 6 - 12 14 - 18 20 - 24
Pipe Size ½ - 1½ 2-4 6 - 12 14 - 18 20 - 24
Mark No 1 (1 Off)
Mark No 4 (1 Off)
Size
Mark No 5 (1 Off)
T-12 T-16 T-20 T-24 T-30
WENL-12 Weldless WENL-16 Eye Nut WENL-20 Pipe Clip WENL-24 WENL-30
Turnbuckle
Welding Lug
Size L-12 L-16 L-20 L-24 L-30
Mark No 2 (1 Off)
Clevis
Size
Size CLR-12 CLR-16 CLR-20 CLR-24 CLR-30
Mark No 3 (1 Off)
Size R-12B R-16B R-20B R-24B R-30B
Threaded Sling Rod
Mark No 6 (1 Off)
Size
Mark No 7 (1 Off)
PC1 Size as Pipe
Nut
Size M12 M16 M20 M24 M30
Pipe Support No HR7, Hanger with 2- Bolt Clamp for Heavy Loads
Pipe Size 3 4-8 10 - 12 14 - 24 26 - 30
Pipe Size 3 4-8 10 - 12 14 - 24 26 - 30
Mark No 1 (1 Off)
Mark No 4 (1 Off)
Size
Mark No 5 (1 Off)
T-20 T-24 T-30 T-36 T-42
WENL-20 Weldless WENL-24 Eye Nut WENL-30 Pipe Clip WENL-36 WENL-42
Turnbuckle
Welding Lug
Size L-20 L-24 L-30 L-36 L-42
Mark No 2 (1 Off)
Clevis
Size
Size CLR-20 CLR-24 CLR-30 CLR-36 CLR-42
Mark No 3 (1 Off) Threaded Sling Rod
Mark No 6 (1 Off)
Size
PC2 Size as Pipe
Size R-20B R-24B R-30B R-36B R-42B Mark No 7 (1 Off)
Nut
Size M20 M24 M30 M36 M42
Pipe Support No HR8, Hanger with Lug for Light Loads Pipe Size ½ - 1½ 2-4 6 - 10
Mark No 1 (2 Off) Welding Lug
Pipe Size ½ - 1½ 2-4 6 - 10
Mark No 3 (1 Off) Threaded Sling Rod
SUPPORT No SUPPORT TYPE PIPE SIZE
Size L-12 L-16 L-20 Size R-12B R-16B R-20B
Mark No 2 (1 Off) Clevis
Mark No 4 (1 Off) Turnbuckle
Size CLR-12 CLR-16 CLR-20 Size
Mark No 8 (1 Off) Clevis
Mark No 7 (1 Off)
T-12 T-16 T-20
HR6, HR7, HR8 Adjustable Hangers for Bare Pipes (Dimensions) ½" - 30"
Nut
Size CLL-12 CLL-16 CLL-20 Size M12 M16 M20
Sheet D6
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
1 2
3 4
L.H. Thread Rod, Nut & Weldless Eye Nut
H
5
6
Supt. No HR9 (Light Loads) Supt. No HR10 (Heavy Loads)
Pipe Size ½-1 1½ - 2 3-4 6-8 10 - 12 14 16 - 20 22 - 24
HR9 HR10 Maximum Maximum Dimension H Load (KN) Load (KN) Maximum Minimum 5.0 700 5.0 2000 10.0 800 10.0 30.0 900 15.0 40.0 2200 1150 18.0 40.0 1250 23.0 45.0 2400 1350 23.0 50.0 1450
Assembly Tag No: - HR9 or HR10 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
HR9, HR10 Adjustable Hanger for Insulated Pipes ½" - 24"
Sheet D7
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Pipe Support No HR9, Hanger with 3-Bolt Clamp for Light Loads Pipe Size ½-1 1½ - 4 6 - 12 14 - 20 22 - 24
Mark No 1 (1 Off)
Pipe Size ½-1 1½ - 4 6 - 12 14 - 20 22 - 24
Mark No 4 (1 Off)
Welding Lug
Turnbuckle
Size L-12 L-16 L-20 L-24 L-30
Mark No 2 (1 Off)
Clevis
Size CLR-12 CLR-16 CLR-20 CLR-24 CLR-30
Size
Mark No 3 (1 Off) Threaded Sling Rod
Size
Mark No 5 (1 Off)
Mark No 6 (1 Off)
T-12 T-16 T-20 T-24 T-30
WENL-12 Weldless WENL-16 Eye Nut WENL-20 Pipe Clip WENL-24 WENL-30
Size R-12B R-16B R-20B R-24B R-30B
Size
PC3 Size as Pipe
Pipe Support No HR10, Hanger with 3- Bolt Clamp for Heavy Loads Pipe Size 6-8 10 - 14 16 - 24
Mark No 1 (1 Off) Welding Lug
Pipe Size 6-8 10 - 14 16 - 24
Mark No 4 (1 Off)
SUPPORT No SUPPORT TYPE PIPE SIZE
Turnbuckle
Size L-30 L-36 L-42
Size T-30 T-36 T-42
Mark No 2 (1 Off) Clevis
Size CLR-30 CLR-36 CLR-42
Mark No 3 (1 Off) Threaded Sling Rod
Mark No 5 Size Mark No 6 (1 Off) (1 Off) Weldless WENL-30 Eye Nut WENL-36 Pipe Clip WENL-42
HR9, HR10 Adjustable Hanger for Insulated Pipes (Dimensions) ½" - 24"
Size R-30B R-36B R-42B
Size PC4 Size as Pipe
Sheet D8
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
1
2 6 3
H
4 5
Isolation Strip
Supt. No HR101 (Light Loads) Supt. No HR102 (Heavy Loads)
Pipe Size ½ - 1½ 2 3 4 6-8 10 12 14 - 18 20 - 24 26 - 30
HR101 HR102 Max Max Dimension H Load (KN) Load (KN) Maximum Minimum 400 4.0 12.0 2000 500
7.0
20.0
12.0
40.0
600 800 2200 2400
50.0
900 1000 1100
Assembly Tag No: - HR101 or HR102 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
HR101, HR102 Non-Adjustable Hanger for Bare Stainless Steel Pipes ½" - 30"
Sheet D9
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Pipe Support No HR101, Hanger with 2-Bolt Clamp for Light Loads Pipe Size ½ - 1½ 2-4 6 - 12 14 - 18 20 - 24
Mark No 1 (1 Off)
Pipe Size ½ - 1½ 2-4 6 - 12 14 - 18 20 - 24
Mark No 4 (1 Off)
Welding Lug
Size L-12 L-16 L-20 L-24 L-30 Size
Mark No 2 (1 Off)
Clevis
Mark No 5 (1 Off)
WENR-12 Weldless WENR-16 Eye Nut WENR-20 Pipe Clip WENR-24 WENR-30
Size CLR-12 CLR-16 CLR-20 CLR-24 CLR-30 Size
PC101 Size as Pipe
Mark No 3 (1 Off) Threaded Sling Rod
Mark No 6 (1 Off)
Nut
Size R-12A R-16A R-20A R-24A R-30A Size M12 M16 M20 M24 M30
Pipe Support No HR102, Hanger with 2- Bolt Clamp for Heavy Loads Pipe Size 3 4-8 10 - 12 14 - 24 26 - 30
Mark No 1 (1 Off)
Pipe Size 3 4-8 10 - 12 14 - 24 26 - 30
Mark No 4 (1 Off)
SUPPORT No SUPPORT TYPE PIPE SIZE
Welding Lug
Size L-20 L-24 L-30 L-36 L-42
Size
Mark No 2 (1 Off)
Clevis
Mark No 5 (1 Off)
WENR-20 Weldless WENR-24 Eye Nut WENR-30 Pipe Clip WENR-36 WENR-42
Size CLR-20 CLR-24 CLR-30 CLR-36 CLR-42
Size
PC102 Size as Pipe
Mark No 3 (1 Off) Threaded Sling Rod
Mark No 6 (1 Off)
Nut
HR101, HR102 Non-Adjustable Hanger for Bare Stainless Steel Pipes ½" - 30"
Size R-20A R-24A R-30A R-36A R-42A
Size M20 M24 M30 M36 M42
Sheet D10
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
1
2
6
H 3
4
5
Isolation Strip
Pipe Size ½-1 1½ - 2 3-4 6-8 10 - 12 14 16 - 20 22 - 24
Supt. No HR104 (Light Loads) Supt. No HR105 (Heavy Loads)
HR104 HR105 Maximum Maximum Dimension H Load (KN) Load (KN) Maximum Minimum 5.0 500 5.0 2000 10.0 600 10.0 30.0 700 15.0 40.0 2200 900 18.0 40.0 1000 23.0 45.0 2400 1100 23.0 50.0 1200
Assembly Tag No: - HR104 or HR105 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
HR104, HR105 Non-Adjustable Hanger for Insulated SS Pipes ½" - 24"
Sheet D11
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Pipe Support No HR104, Hanger with 3-Bolt Clamp for Light Loads Pipe Size ½-1 1½ - 4 6 - 12 14 - 20 22 - 24
Mark No 1 (1 Off)
Pipe Size ½-1 1½ - 4 6 - 12 14 - 20 22 - 24
Mark No 4 (1 Off)
Welding Lug
Size L-12 L-16 L-20 L-24 L-30 Size
Mark No 2 (1 Off)
Clevis
Mark No 5 (1 Off)
WENR-12 Weldless WENR-16 Eye Nut WENR-20 Pipe Clip WENR-24 WENR-30
Size CLR-12 CLR-16 CLR-20 CLR-24 CLR-30 Size
Mark No 3 (1 Off) Threaded Sling Rod
Mark No 6 (1 Off)
PC103 Size as Pipe
Nut
Size R-12A R-16A R-20A R-24A R-30 Size M12 M16 M20 M24 M30
Pipe Support No HR105, Hanger with 3- Bolt Clamp for Heavy Loads Pipe Size 6-8 10 - 14 16 - 24
Mark No 1 (1 Off) Welding Lug
Pipe Size 6-8 10 - 14 16 - 24
Mark No 4 Size Mark No 5 (1 Off) (1 Off) Weldless WENR-30 Eye Nut WENR-36 Pipe Clip WENR-42
SUPPORT No SUPPORT TYPE PIPE SIZE
Size L-30 L-36 L-42
Mark No 2 (1 Off) Clevis
Size CLR-30 CLR-36 CLR-42 Size
Mark No 3 (1 Off) Threaded Sling Rod
Mark No 6 (1 Off)
PC104 Size as Pipe
HR104, HR105 Non-Adjustable Hanger for Insulated SS Pipes ½" - 24"
Nut
Size R-30A R-36A R-42A Size M30 M36 M42
Sheet D12
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
1 2 7 3 4
H
L.H. Thread Rod, Nut & Weldless Eye Nut
5 6
Isolation Strip
Supt. No HR106 (Light Loads) Supt. No HR107 (Heavy Loads) Pipe Size ½ - 1½ 2 3 4 6-8 10 12 14 - 18 20 - 24 26 - 30
HR106 HR107 Max Max Dimension H Load (KN) Load (KN) Maximum Minimum 600 4.0 12.0 2000 700
7.0
20.0
12.0
35.0
800 1050 2200 2400
50.0
1150 1250 1350
Assembly Tag No: - HR106 or HR107 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
HR106, HR107 Adjustable Hangers for Bare Stainless Steel Pipes ½" - 30"
Sheet D13
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Pipe Support No HR106, Hanger with 2-Bolt Clamp for Light Loads
Pipe Size ½ - 1½ 2-4 6 - 12 14 - 18 20 - 24
Pipe Size ½ - 1½ 2-4 6 - 12 14 - 18 20 - 24
Mark No 1 (1 Off)
Mark No 4 (1 Off)
Size
Mark No 5 (1 Off)
T-12 T-16 T-20 T-24 T-30
WENL-12 Weldless WENL-16 Eye Nut WENL-20 Pipe Clip WENL-24 WENL-30
Turnbuckle
Welding Lug
Size L-12 L-16 L-20 L-24 L-30
Mark No 2 (1 Off)
Clevis
Size
Size CLR-12 CLR-16 CLR-20 CLR-24 CLR-30 Mark No 6 (1 Off)
Mark No 3 (1 Off) Threaded Sling Rod
Size
PC101 Size as Pipe
Size R-12B R-16B R-20B R-24B R-30B Mark No 7 (1 Off)
Nut
Size M12 M16 M20 M24 M30
Pipe Support No HR107, Hanger with 2- Bolt Clamp for Heavy Loads
Pipe Size 3 4-8 10 - 12 14 - 24 26 - 30
Pipe Size 3 4-8 10 - 12 14 - 24 26 - 30
Mark No 1 (1 Off)
Mark No 4 (1 Off)
Size
Mark No 5 (1 Off)
T-20 T-24 T-30 T-36 T-42
WENL-20 Weldless WENL-24 Eye Nut WENL-30 Pipe Clip WENL-36 WENL-42
Turnbuckle
SUPPORT No SUPPORT TYPE PIPE SIZE
Welding Lug
Size L-20 L-24 L-30 L-36 L-42
Mark No 2 (1 Off)
Clevis
Size
Size CLR-20 CLR-24 CLR-30 CLR-36 CLR-42 Mark No 6 (1 Off)
Mark No 3 (1 Off) Threaded Sling Rod
Size
PC102 Size as Pipe
HR106, HR107 Adjustable Hangers for Bare SS Pipes (Dimensions) ½" - 30"
Size R-20B R-24B R-30B R-36B R-42B Mark No 7 (1 Off)
Nut
Size M20 M24 M30 M36 M42
Sheet D14
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
1 2
3 4
L.H. Thread Rod, Nut & Weldless Eye Nut
H
5
6
Isolation Strip.
Pipe Size ½-1 1½ - 2 3-4 6-8 10 - 12 14 16 - 20 22 - 24
Supt. No HR109 (Light Loads) Supt. No HR110 (Heavy Loads)
HR109 HR110 Maximum Maximum Dimension H Load (KN) Load (KN) Maximum Minimum 5.0 700 5.0 2000 10.0 800 10.0 30.0 900 15.0 40.0 2200 1150 18.0 40.0 1250 23.0 45.0 2400 1350 23.0 50.0 1450
Assembly Tag No: - HR109 or HR110 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
HR109, HR110 Adjustable Hanger for Insulated Stainless Steel Pipes ½" - 24"
Sheet D15
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Pipe Support No HR109, Hanger with 3-Bolt Clamp for Light Loads Pipe Size ½-1 1½ - 4 6 - 12 14 - 20 22 - 24
Mark No 1 (1 Off)
Pipe Size ½-1 1½ - 4 6 - 12 14 - 20 22 - 24
Mark No 4 (1 Off)
Welding Lug
Turnbuckle
Size L-12 L-16 L-20 L-24 L-30
Mark No 2 (1 Off)
Clevis
Size CLR-12 CLR-16 CLR-20 CLR-24 CLR-30
Size
Mark No 3 (1 Off) Threaded Sling Rod
Size
Mark No 5 (1 Off)
Mark No 6 (1 Off)
T-12 T-16 T-20 T-24 T-??
WENL-12 Weldless WENL-16 Eye Nut WENL-20 Pipe Clip WENL-24 WENL-30
Size R-12B R-16B R-20B R-24B R-30B
Size
PC103 Size as Pipe
Pipe Support No HR110, Hanger with 3- Bolt Clamp for Heavy Loads Pipe Size 6-8 10 - 14 16 - 24
Mark No 1 (1 Off) Welding Lug
Pipe Size 6-8 10 - 14 16 - 24
Mark No 4 (1 Off)
SUPPORT No SUPPORT TYPE PIPE SIZE
Turnbuckle
Size L-30 L-36 L-42
Size T-30 T-36 T-42
Mark No 2 (1 Off) Clevis
Size CLR-30 CLR-36 CLR-42
Mark No 3 (1 Off) Threaded Sling Rod
Mark No 5 Size Mark No 6 (1 Off) (1 Off) Weldless WENL-30 Eye Nut WENL-36 Pipe Clip WENL-42
HR109, HR110 Adjustable Hanger for Insulated Stainless Steel Pipes ½" - 24"
Size R-30B R-36B R-42B
Size PC104 Size as Pipe
Sheet D16
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
1
2 3 H 2 1 Max Load (KN) 4
50
=
50
= L
Size Code A1 A2 A3 B1 B2 B3 B4 C1 C2 C3 C4 Size Code A B C
L 500 700 900 900 1100 1300 1500 1500 1700 1900 2100 Mark No 1 (4 Off) Welding Lug
Dimensions H (Max) H (Min)
Max Load Mark No 4 (KN) (1 Off)
2000
400
4.0
IPE 100
3000
500
20.0
IPE 200
3000
800
40.0
IPE 300
Size
Mark No 2 (4 Off)
Size
Mark No 3 (2 Off) Threaded Sling Rod
L-12 L-24 L-36
Clevis
CL-12 CL-24 CL-36
M.T.O. Length 500 700 900 900 1100 1300 1500 1500 1700 1900 2100 Size R-12A R-24C R-36C
Assembly Tag No: - TH - XX Detail No Size Code SUPPORT No TH SUPPORT TYPE Trapeze Hanger All Sizes PIPE SIZE
Sheet D17
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
H
For Details of Spring Hangers Refer to Spring Spec No 60-0000-L-SPE-1003
SH1 Spring Hanger For Bare Pipes
Assembly Tag No: - SH1 or SH2 Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
SH2 Spring Hanger For Insulated Pipes
Dimensions Required: - H Item No (Ref Spring Spec) is also required
SH1, SH2 Spring Hangers from Underside of Steel 2"- 36"
Sheet D18
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
For Details of Spring Hangers Refer to Spring Spec No 60-0000-L-SPE-1003
H
SH3 Spring Hanger For Bare Pipes
SH4 Spring Hanger For Insulated Pipes
Assembly Tag No: - SH3 or SH4 Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
SH3, SH4 Spring Hangers from Top of Steel 2"- 36"
Dimensions Required: - H Item No (Ref Spring Spec) is also required Sheet D19
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
For Details of Spring Hangers Refer to Spring Spec No 60-0000-L-SPE-1003
H
L
H
L
Assembly Tag No: - SH5 Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Detail for Pipes with Shoes
Where required shoe to be called up separately by piping designer
Dimensions Required: - H, L Item No (Ref Spring Spec) is also required
SH5 Trapeze Spring Hanger from Underside of Steel All Sizes
Sheet D20
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
For Details of Spring Hangers Refer to Spring Spec No 60-0000-L-SPE-1003
H
L
Detail for Pipes with Shoes
H
L Assembly Tag No: - SH6 Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Where required shoe to be called up separately by piping designer Dimensions Required: - H, L Item No (Ref Spring Spec) is also required
SH6 Trapeze Spring Hanger from Top of Steel All Sizes
Sheet D21
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
H
For Details of Spring Hangers Refer to Spring Spec No 60-0000-L-SPE-1003 L
H
Detail for Pipes with Shoes
Where required shoe to be called up separately by piping designer L Assembly Tag No: - SH7 Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Dimensions Required: - H, L Item No (Ref Spring Spec) is also required
SH7 Trapeze Spring Hanger, Springs underneath pipe All Sizes
Sheet D22
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
Shoe (ref. By PFD) For Details of Spring Hangers Refer to Spring Spec No 60-0000-L-SPE-1003
H
Stitch weld spring to supporting steelwork
Base Support (ref. BS1 or BS6 by PFD)
For Details of Spring Hangers Refer to Spring Spec No 60-0000-L-SPE-1003
H
Stitch weld spring to supporting steelwork Assembly Tag No: - SH8 Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
SH8 Pedestal Spring All Sizes
Dimensions Required: - H Item No (Ref Spring Spec) is also required Sheet D23
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
For Details of Spring Hangers Refer to Spring Spec No 60-0000-L-SPE-1003
H
SH11 Constant Spring Hanger Trapeze
Assembly Tag No: - SH11 or SH12 Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
SH12 Constant Spring Hanger Trapeze
Dimensions Required: - H Item No (Ref Spring Spec) is also required
SH11, SH12 Constant Spring Hangers from Underside of Steel 2"- 36"
Sheet D24
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
For Details of Spring Hangers Refer to Spring Spec No 60-0000-L-SPE-1003
H
SH14 Constant Spring Hanger
SH13 Constant Spring Hanger
Assembly Tag No: - SH13 or SH14 Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Dimensions Required: - H Item No (Ref Spring Spec) is also required
SH13, SH14 Constant Spring Hangers from Top of Steel 2"- 36"
Sheet D25
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
For Details of Spring Hangers Refer to Spring Spec No 60-0000-L-SPE-1003
H
SH15 Constant Spring Hanger Trapeze
L
Detail for Pipes with Shoes Where required shoe to be called up separately by piping designer
L
For Details of Spring Hangers Refer to Spring Spec No 60-0000-L-SPE-1003
H
SH16 Constant Spring Hanger Trapeze L Assembly Tag No: - SH15 or SH16 Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Dimensions Required: - H,L Item No (Ref Spring Spec) is also required
SH15, SH16 Constant Spring Hangers from Underside of Steel All Sizes
Sheet D26
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
For Details of Spring Hangers Refer to Spring Spec No 60-0000-L-SPE-1003 H
SH17 Constant Spring Hanger Trapeze
L H
Detail for Pipes with Shoes Where required shoe to be called up separately by piping designer
L
For Details of Spring Hangers Refer to Spring Spec No 60-0000-L-SPE-1003 H SH18 Constant Spring Hanger Trapeze
L Assembly Tag No: - SH17 or SH18 Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Dimensions Required: - H,L Item No (Ref Spring Spec) is also required
SH17, SH18 Constant Spring Hangers from Top of Steel All Sizes
Sheet D27
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2 SH19 Constant Pedestal Spring
For Details of Spring Hangers Refer to Spring Spec No 60-0000-L-SPE-1003
H
SH20 Constant Pedestal Spring
For Details of Spring Hangers Refer to Spring Spec No 60-0000-L-SPE-1003
Assembly Tag No: - SH19 or SH20 Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
SH19, SH20 Constant Pedesal Springs All Sizes
H
Dimensions Required: - H Item No (Ref Spring Spec) is also required Sheet D28
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2 For Details of Spring Hangers Refer to Spring Spec No 60-0000-L-SPE-1003
H
A
A
View A-A
Assembly Tag No: - SH9 Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Dimensions Required: - H Item No (Ref Spring Spec) is also required
SH9 Spring Hangers from Top of Steel to Elbow hanger All Sizes
Sheet D29
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS
For Details of Spring Hangers Refer to Spring Spec No 60-0000-L-SPE-1003
H H X
X
X
X
SH22
SH21
View X-X Assembly Tag No: - SH21 or SH22 Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Dimensions Required: - H Item No (Ref Spring Spec) is also required
SH21, SH22 Spring Hangers for Cold Insulated Pipes 2"- 36"
Sheet D30
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
For Details of Spring Hangers Refer to Spring Spec No 60-0000-L-SPE-1003
H
A
A
View A-A
Assembly Tag No: - SH10 Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Dimensions Required: - H Item No (Ref Spring Spec) is also required
SH10 Spring Hangers from Underside of Steel to Pipe Elbow.
All Sizes
Sheet D31
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
For Details of Spring Hangers Refer to Spring Spec No 60-0000-L-SPE-1003
H
A
A
View A-A
Assembly Tag No: - SH23 Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Dimensions Required: - H Item No (Ref Spring Spec) is also required
SH23 Spring Hangers from Underside of Steel to Pipe Lug. All Sizes
Sheet D32
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
For Details of Spring Hangers Refer to Spring Spec No 60-0000-L-SPE-1003
H
A
A
View A-A
Assembly Tag No: - SH24 Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Dimensions Required: - H Item No (Ref Spring Spec) is also required
SH24 Spring Hangers from Top of Steel to Pipe Lug All Sizes
Sheet D33
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS
1 2 3 2400
2
4
Site Drill 22dia holes through the centreline of the top flange of the beam
50
50 1800
Support PS15
Mark No 1 M10 Alphawedge Deck Fixing
No Off 2
Mark No 2 M10 Nuts
No Off 6
Support PS15
Mark No 3 M10 Threaded Rod
Length 5000
Mark No 4 UPN 100
Length 1800
NOTES 1- This support shall be used for HVAC piping only 2- Threaded rods and beam shall be trimed to suit
Assembly Tag No: - PS15 Detail No SUPPORT No PS15 SUPPORT TYPE Horizontal Pipe Support - Single Bank All Sizes PIPE SIZE
Sheet D34
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS L Reference Pipe
=
=
Note - View Looking North or East
Y
Support No P1-A
T.O.S. EL L =
Support No P1-B/C/D/E/F
1
=
20
H
1 Site trim and field weld to existing structure
H
For alternative welding arrangements refer to Support No P2 Dimension Size Code
Mark No1 H
A1 A2 A3 B1 B2 B3 B4 C1 C2 C3 C4 D1 D2 D3 D4 E1 E2 E3 E4 F1 F2 F3 F4
1000
1000
2000
2000
3000
3000
L 300 500 750 300 500 750 1000 300 500 750 1000 300 500 750 1000 300 500 750 1000 300 500 750 1000
Assembly Tag No: - P1 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Total Length
70 X 8 Angle
HEA 100
HEA 100
HEA 160
HEA 160
HEA 200
Dimension "Y",
1300 1500 1800 1200 1400 1650 1900 2200 2400 2650 2900 2140 2340 2600 2840 3140 3340 3600 3840 3100 3300 3550 3800
Allowable Bending Moment (KNm) 0.5
Notes For use only on Pipe Sizes ≤ 2"
4.0
4.0
For use only on Pipe Sizes ≤ 4"
8.0
8.0
For use only on Pipe Sizes ≤ 4"
12.0
T.O.S. EL
Size Code P1 T-Post from existing structure All Sizes
Sheet E1
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Preferred Arrangement
Alternative Welding Arrangements for Pipe Support Nos P1 - P9.
L (typ)
2 =
=
T.O.S. EL
HEA 160 or HEA 100 or 70 x 8 Angle
1
200 min 20
H 200 min
Site trim and field weld to existing structure HEA 100 or 70 x 8 Angle
20 10
200 min
Flange toes cut back 10mm to ensure a good weld
20
Notes: - 1- Size Codes "B" and "D" shall only be used for Pipe Sizes ≤ 4" Size Code A1 A2 B1 B2 C1 C2 D1 D2 E1 E2
Dimension H
L
1000
200 300 200 300 300 450 300 450 400 550
2000 2000 3000 3000
Assembly Tag No: - P2 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Mark No 1
Total Length
Mark No 2
Area (cm²)
HEA 100
1000 1000 2000 2000 2000 2000 3000 3000 3000 3000
12 Thk square plate
400 900 400 900 900 2025 900 2025 1600 3025
HEA 100 HEA 160 HEA 160 HEA 200
15 Thk square plate
Allowable Bending Moment (KNm) 4.0 4.0 Note 1 8.0 8.0 Note 1 12.0
T.O.S. EL
Size Code P2 Post with Square Plate from exisiting structure All Sizes
Sheet E2
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
20
L
Note - View Looking ????
Y
Reference Pipe
Reference Pipe T.O.S. EL
20
L Y
T.O.S. EL 1
20
H 1
Site trim and field weld to existing structure
H
For alternative welding arrangements refer to Support No P2 Support No P3-A
Support No P3-B/C/D/E/F
Note: -
Size Code A1 A2 B1 B2 C1 C2 D1 D2 E1 E2 F1 F2
1- This support is not to be used for anchoring pipes 2- The support can not be used on lines 6" and above without consultation with the stress engineer. Dimension H
L
1000
250 500 250 500 250 500 250 500 250 500 250 500
1000 2000 2000 3000 3000
Assembly Tag No: - P3 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Mark No 1
Total Length
70 X 8 Angle HEA 100
1350 1550 1220 1470 2220 2470 2190 2440 3190 3440 3170 3420
HEA 100 HEA 160 HEA 160 HEA 200
Dimension "Y",
Allowable Bending Notes Moment (KNm) 0.5 For use only on Pipe Sizes ≤ 2" 4.0 4.0
For use only on Pipe Sizes ≤ 4"
8.0 8.0
For use only on Pipe Sizes ≤ 4"
12.0
T.O.S. EL, View looking ????
Size Code P3 Cantilevered-Post from existing structure All Sizes
Sheet E3
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
L K Reference Pipe
K
M Y
20
T.O.S. EL
1 H
Note - View Looking North or East
Site trim and field weld to existing structure
For alternative welding arrangements refer to Support No P2 Note: -
1- The support shall be used for pipes ≤ 2" Size Code A1 A2
H 1000
Size Code A1 A2
Mark No 1 70 x 8 Angle
Assembly Tag No: - P4 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Dimension L M 1100 1000 1500
Total Length 3100 3500
Dimension "Y",
K 50 250
Max Bending Moment (KNm) 0.5
T.O.S. EL
Size Code P4 Goal Post from Structure ½" - 2"
Sheet E4
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS L K Reference Pipe
K
M Y
T.O.S. EL
1
Note - View Looking North or East
H
Site trim and weld to existing structure For alternative welding arrangements refer to Support No P2
Size Code B1 B2 B3 C1 C2 C3 C4 C5 C6 C7 C8 D1 D2 D3 D4 D5 D6 D7 D8 D9
Dimension H 1000
1000
2000
1000
2000
3000
L
K
1300 1600 2000 1400 1700 2000 2500 1400 1700 2000 2500 2000 2500 3000 2000 2500 3000 2000 2500 3000
150 300 500 100 250 250 500 100 250 250 500 150 250 500 150 250 500 150 250 500
Assembly Tag No: - P4 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
M 1000
Mark No 1
HEA 100
1200 1500 HEA 160 1200 1500 1700 2000 1700 2000
HEA 200
1700 2000
Dimension "Y",
Total Length 3110 3410 3810 3100 3400 3700 4200 5100 5400 5700 6200 3620 4120 4620 5620 6120 6620 7620 8120 8620
Allowable Bending Moment (KNm) 4.0
8.0
12.0
T.O.S. EL
Size Code P4 Goal Post from Grade or Structure All Sizes
Sheet E5
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
T.O.S. EL
1
H Site trim and field weld to existing structure
For alternative welding arrangements refer to Support No P2 Note: -
1- For dimension "H" see Table below
Size Code
Dim'n H
Mark No 1
Total Length
A B C D
1000 2000 2000 3000
HEA 100 HEA 100 HEA 160 HEA 160
1000 2000 2000 3000
Allowable Bending Moment (KNm) 4.0 4.0 8.0 8.0
Assembly Tag No: - P5 - X, T.O.S. EL Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Size Code P5 Post from existing structure All Sizes
Sheet E6
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS L K
Reference Pipe
M Y
T.O.S. EL
1 H Site trim and Field weld to existing structure
Note - View Looking ????
Size Code A1 A2 A3 A4 B1 B2 B3 B4 B5 B6
Dimension H
L
K
1000
1600 2000 1600 2000 2120 2500 2120 2500 2120 2500
100 500 100 500 120 500 120 500 120 500
2000 1000 2000 3000
Assembly Tag No: - P6 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Dimension "Y",
M
Mark No 1
1500
HEA 160
2000
HEA 200
Total Length
Allowable Bending Moment (KNm)
2500 2900 3500 3900 3020 3400 4020 4400 5020 5400
8.0
12.0
T.O.S. EL, View looking ????
Size Code P6 Welded Cantilevered Post from existing structure All Sizes
Sheet E7
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS For alternative welding arrangements refer to Support No P2
Site trim and weld to existing beam
Reference Pipe H
1
H Reference Pipe
T.O.S. EL
1
Y
20
=
=
T.O.S. EL
L
Y
Note - View Looking North or East
=
= L Dimension Size Code A1 A2 B1 B2 C1 C2 D1 D2 E1 E2 F1 F2
Mark No1 H
L
1000
500 750 750 1000 750 1000 750 1000 750 1000 750 1000
1000 2000 2000 3000 3000
70 X 8 Angle HEA 100 HEA 100 HEA 160 HEA 160 HEA 200
M.T.O. Length 1550 1800 1750 2000 2750 3000 2750 3000 3750 4000 3750 4000
Allowable Bending Notes Moment (KNm) 0.5 For use only on Pipe Sizes ≤ 2" 4.0 4.0
See Note 1
8.0 8.0
See Note 1
12.0
NOTE 1- The support can not be used on lines 6" and above without consultation with the stress engineer. Assembly Tag No: - P7 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Dimension "Y",
T.O.S. EL
Size Code P7 Inverted T-Post All Sizes
Sheet E8
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS For alternative welding arrangements refer to Support No P2
Site trim and weld to existing beam Reference Pipe
H
Reference Pipe
1
T.O.S. EL
1 20 T.O.S. EL
Y
20
Y L
20
Note - View Looking ????
L
Note: -
Size Code A1 A2 B1 C1 C2
1- This support is not to be used for anchoring pipes 2- The support can not be used on lines 6" and above without consultation with the stress engineer.
Dimension H L 1000 300 500 1000 500 2000 500 750
Assembly Tag No: - P8 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Mark No 1 70 X 8 Angle HEA 100 HEA 160
M.T.O. Length 1420 1620 1570 2600 2850
Dimension "Y",
Max Bending Moment (KNm) 0.5
Notes For use only on Pipe Sizes ≤ 2"
4.0 8.0
T.O.S. EL, View looking ????
Size Code P8 Inverted Cantilevered Post All Sizes
Sheet E9
H
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS For alternative welding arrangements refer to Support No P2
Site trim and weld to existing beam
1
Reference Pipe
H
1
T.O.S. EL
20
Y 50
50
L
Note - View Looking North or East
Note: -
Size Code A1 A2 A3
1- The support shall be used for pipes ≤ 2"
Dimension H L 750 1000 1000 1250
Assembly Tag No: - P9 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Mark No 1 70 X 8 Angle
Dimension "Y",
M.T.O. Length 2950 3200 3500
Max Bending Moment (KNm) 0.5
T.O.S. EL
Size Code P9 Inverted Goal Post ½" - 2"
Sheet E10
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS For alternative welding arrangements refer to Support No P2
Site trim and weld to existing beam Reference Pipe
1
1
H
T.O.S. EL
20
Y
Note - View Looking North or East
L Size Code B1 B2 B3 C1 C2 C3 C4 C5 C6 C7 C8 D1 D2 D3 D4 D5 D6 D7 D8 D9
Dimension H L 800 1000 1200 1600 800 1000 1200 1600 2000 800 2000 1200 1600 2000 1000 2500 3000 2000 2500 3000 1200 1600 3000 2000 2500 3000
Assembly Tag No: - P9 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Mark No 1 HEA 100
HEA 160
HEA 200
Dimension "Y",
M.T.O. Length 2940 3340 3740 3000 3400 3800 4200 5000 5400 5800 6200 4740 5240 6740 7240 7440 7840 8240 8740 9240
Max Bending Moment (KNm) 4.0
8.0
12.0
T.O.S. EL
Size Code P9 Inverted Goal Post All Sizes
Sheet E11
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS
Site trim and weld to existing beam
Note - View Looking ????
1 H 1
Reference Pipe
Site trim and weld to existing column
T.O.S. EL
20
Y L
Size Code A1 B1 B2 B3 B4 C1 C2 C3 C4 C5 C6
Dimension H L 1000 1000 1000 1000 1500 2000 1000 1500 1000 1500 2000 2000 1500 2000 3000 1500 2000
Assembly Tag No: - P10 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Mark No 1 HEA 100 HEA 160
HEA 200
Dimension "Y",
M.T.O. Length 2070 2100 2600 3100 3600 2620 3120 3620 4120 4620 5120
Max Bending Moment (KNm) 4.0 8.0
12.0
T.O.S. EL, View Looking
Size Code P10 Inverted Welded Cantilevered-Post All Sizes
Sheet E12
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS Main Transverse Beam HEA 500
Intermediate Beam HEA 240/400
Locally remove fire proofing, weld support to existing beams.
H
K
1 TOS EL
20
4000
Note: - 1- This support shall only be used in the main N-S SGP piperacks for pipes ≤ 6" to keep the pipe spans within acceptable limits. (See Sketch below)
N
Main Beam
Intermediate Beam Support Point (typ)
Size Code A1 A2 A3
Dimension H K 1010 1220 510 720 1310 1410
Mark No 1 HEA 100
M.T.O. Length 6370 5370 6860
Max Load (KN) 5.0
TOS EL 4500 or 7500 10500 114200
Assembly Tag No: - P11 - XX Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Size Code P11 Inverted Goal Post (for piperacks only) 2" - 6"
Sheet E13
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Reference Pipe
Note - View Looking ????
T.O.S. EL
1 Y K
M L Max Load (typ)
Notes: -
Size Code A1 A2 B1 B2 B3 C1 C2 C3 C4 C5
K (Max) 200 400 200 400 600 200 400 600 800 1000
1- Size Code "A" shall only be used for small bore lines ≤ 1½" where the max loads are nominal Dimensions M (Min) 100
150
200
Assembly Tag No: - P21 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
L 300 500 350 550 750 400 600 800 1000 1200
Mark No 1 70 x 8 Angle HEA 100
HEA 160
Dimension "Y",
M.T.O. Length 300 500 350 550 750 400 600 800 1000 1200
Max Loads (KN) Vertical Horizontal (Note 1) (Note 1) (Note 1) (Note 1) 9.0 3.0 9.0 3.0 6.0 2.0 15.0 5.0 15.0 5.0 15.0 5.0 12.0 4.0 10.0 3.0
T.O.S. EL, View looking ????
Size Code P21 Cantilevers All Sizes
Sheet E14
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS Reference Pipe
Note - View Looking ????
T.O.S. EL Support No P22
1 20
Y (200 min)
K
M
L Max Load (typ)
Reference Pipe Note - View Looking ???? T.O.S. EL Support No P23
1 Y K
M
20 (200 min)
L Notes: Size Code A1 A2 A3 A4 A5 B1 B2 B3 B4 B5 C1 C2 C3 C4 C5 C6 C7
1- Size Code "A" shall only be used for small bore lines (≤ 1½") Mark M.T.O. Dimensions Max Loads (KN) L K (Max) M (Min) No 1 Length Vertical Horizontal 400 400 600 70 x 8 600 0.5 0.5 800 400 100 Angle 800 (Note 1) (Note 1) 1000 1000 1200 1200 600 600 4.0 1.0 800 800 2.0 0.5 1000 600 150 UPN 100 1000 2.0 0.5 1200 1200 2.0 0.5 1400 1400 2.0 0.5 600 600 10.0 3.0 800 800 7.5 2.5 1000 1000 5.0 2.0 1200 1000 200 UPN 160 1200 3.0 1.0 1400 1400 3.0 1.0 1600 1600 3.0 1.0 1800 1800 3.0 1.0
Assembly Tag No: - P22 or P23 - XX, Dimension "Y", Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
P22, P23 Cantilevers All Sizes
T.O.S. EL, View looking ????
Size Code Sheet E15
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Reference Pipe
Note - View Looking ????
T.O.S. EL Support No P24 1 Y (200 min)
20
K
M
L Max Load (typ) Reference Pipe
Note - View Looking ????
T.O.S. EL Support No P25
1 Y M
(200 min)
K
20
L Notes: Size Code A1 A2 A3 A4 A5 B1 B2 B3 B4 B5 C1 C2 C3 C4 C5 C6 C7
1- Size Code "A" shall only be used for small bore lines (≤ 1½") Mark M.T.O. Dimensions Max Loads (KN) L K (Max) M (Min) No 1 Length Vertical Horizontal 400 400 600 70 x 8 600 0.5 0.5 800 400 100 Angle 800 (Note 1) (Note 1) 1000 1000 1200 1200 600 600 4.0 1.0 800 800 2.0 0.5 1000 600 150 UPN 100 1000 2.0 0.5 1200 1200 2.0 0.5 1400 1400 2.0 0.5 600 600 10.0 3.0 800 800 7.5 2.5 1000 1000 5.0 2.0 1200 1000 200 UPN 160 1200 3.0 1.0 1400 1400 3.0 1.0 1600 1600 3.0 1.0 1800 1800 3.0 1.0
Assembly Tag No: - P24 or P25 - XX, Dimension "Y", Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
P24, P25 Cantilevers All Sizes
T.O.S. EL, View looking ????
Size Code Sheet E16
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Note - View Looking ???? L Reference Pipe
Y
M
T.O.S. EL
1
45º K
200
Max Load
1
Size Code A1 B1 B2 B3
K (Max) 600 600 800 1000
Dimensions M (Min) 150 200
Assembly Tag No: - P26 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
L 750 800 1000 1200
Mark No 1 HEA 100 HEA 160
Dimension "Y",
M.T.O. Length 1599 1649 2132 2615
Max Loads (KN) Vertical Horizontal 12.0 3.5 30.0 10.0 25.0 8.0 20.0 6.0
T.O.S. EL, View looking ????
Size Code P26 Braced Cantilevers All Sizes
Sheet E17
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
L M
K Y
Reference Pipe
Note - View Looking ????
T.O.S. EL
1
45º
200
Support No P27
Max Load 1
1 Support No P28
20 (typ)
Support is Identical to P27 except it is Opposite hand
200 min
1
Size Code A1 A2 A3 A4 A5 A6
K (Max)
Dimensions M (Min)
1000
200
L 800 1000 1200 1400 1600 1800
Assembly Tag No: - P27 or P28 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Mark No 1
UPN 160
Dimension "Y",
M.T.O. Length 1649 2132 2615 3098 3581 4064
Max Loads (KN) Vertical Horizontal 15.0 5.0 12.0 4.0 10.0 3.0 8.0 2.5 8.0 2.5 8.0 2.5
T.O.S. EL, View looking ????
Size Code
P27, P28 Braced Cantilevers All Sizes
Sheet E18
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
L K Reference Pipe
M
Y
Note - View Looking ????
20 (typ) T.O.S. EL
45º
1
Support No P29
200 Max Load 1
1 Support No P30 Support is Identical to P29 except it is Opposite hand
(200 Min)
1
Size Code A1 A2 A3 A4 A5
K (Max)
Dimensions M (Min)
1000
200
L 800 1000 1200 1400 1600
Assembly Tag No: - P29 or P30 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Mark No 1
UPN 160
Dimension "Y",
M.T.O. Length 1649 2132 2615 3098 3581
Max Loads (KN) Vertical Horizontal 10.0 3.0 7.5 2.5 5.0 1.5 5.0 1.5 5.0 1.5
T.O.S. EL, View looking ????
Size Code
P29, P30 Braced Cantilevers All Sizes
Sheet E19
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS Y
Reference Pipe
Note - View Looking ????
T.O.S. EL
1 = Support No P31
= Max Load (typ) 4000 (Max) L
Y
Reference Pipe
Note - View Looking ???? T.O.S. EL 1 Support No P32
20 (Min)
200 min
4000 (Max) L
200 min
Y
Reference Pipe
Note - View Looking ???? T.O.S. EL 1 Support No P33
4000 (Max)
20 (Min)
L
Assembly Tag No: - P31 or P32 or P33 - XX, Dimension "Y", Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
T.O.S. EL, View looking ????
Size Code
P31, P32, P33 Beams Welded to Columns All Sizes
Sheet E20
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Support No
P31
P32/P33
SUPPORT No SUPPORT TYPE PIPE SIZE
Size Code A1 B1 B2 B3 C1 C2 C3 A1 A2 A3 A4 A5 A6 A7 A8
Dim'n L 2000 2000 3000 4000 2000 3000 4000 2000 2400 2800 3200 3600 4000 4400 4800
Mark No 1 HEA 100 HEA 160
HEA 200
UPN 200
M.T.O. Length 2000 2000 3000 4000 2000 3000 4000 2000 2400 2800 3200 3600 4000 4400 4800
P31, P32, P33 Beams Welded to Columns (Dimensions) All Sizes
Max Loads (KN) Vertical Horizontal 8.0 4.0 20.0 10.0 15.0 7.0 10.0 5.0 30.0 20.0 25.0 15.0 20.0 10.0 15.0 4.0 12.0 3.0 10.0 2.5 8.0 2.5 6.0 2.0 6.0 2.0 4.0 1.5 4.0 1.5
Sheet E21
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
L (4000 Max) Y
Note - View Looking North or East
Reference Pipe
T.O.S. EL
1 Max Load (typ)
Support No P34
=
=
Y
Reference Pipe
Note - View Looking North or East T.O.S. EL 1 Support No P35
100
100
4000 (Max) L
Y
Reference Pipe
Note - View Looking North or East
Site Trim to suit
2
300 Max
T.O.S. EL
520 1 Support No P36
100
4000 (Max)
20
L
Assembly Tag No: - P34 or P35 or P36 - XX, Dimension "Y", Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
100
T.O.S. EL
Size Code
P34, P35, P36 Beams Welded to Beams All Sizes
Sheet E22
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Support No
P34/35
P36
Size Code A1 B1 B2 B3 C1 C2 C3 A1 A2 A3 A4 A5 A6
SUPPORT No SUPPORT TYPE PIPE SIZE
Dim'n L 2000 2000 3000 4000 2000 3000 4000 2000 2400 2800 3200 3600 4200
Mark No 1 HEA 100 HEA 160
HEA 200
UPN 200
M.T.O. Length 2000 2000 3000 4000 2000 3000 4000 2000 2400 2800 3200 3600 4200
Mark No 2
M.T.O. Length
100 x 10 Angle
520
P34, P35, P36 Beams Welded to Beams (Dimensions) All Sizes
Max Loads (KN) Vertical Horizontal 8.0 4.0 20.0 10.0 15.0 7.0 10.0 5.0 30.0 20.0 25.0 15.0 20.0 10.0 15.0 4.0 12.0 3.0 10.0 2.5 8.0 2.5 6.0 2.0 6.0 2.0
Sheet E23
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Reference Pipe
200 (Min)
Y 500 (Max)
Note - View Looking ???? 1
T.O.S. EL
Support No P37
100
4000 (Max)
Max Load L
Reference Pipe
200 (Min)
Y 500 (Max)
Site trim to suit
Note - View Looking ????
2 1
300 (Max)
T.O.S. EL
Support No P38
4000 (Max)
Max Load
100
20
L
Reference Pipe
Y
200 (Min)
2 1
300 (Max)
T.O.S. EL
Support No P39
Note - View Looking ????
Site trim to suit
Max Load
20 4000 (Max)
100
L
Assembly Tag No: - P37 or P38 or P39 - XX, Dimension "Y", Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
P37, P38, P39 Cantilevered Beams All Sizes
T.O.S. EL, View looking ????
Size Code Sheet E24
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Support No
P37
P38/39
Size Code A1 A2 A3 B1 B2 B3 B4 C1 C2 C3 A1 A2 A3 A4 A5 B1 B2 B3
SUPPORT No SUPPORT TYPE PIPE SIZE
Dim'n L 2000 2400 2800 2400 2800 3200 3600 4000 4400 4800 2000 2400 2800 3200 3600 4000 4400 4800
Mark No 1 HEA 100
HEA 160
HEA 200
UPN 160
UPN 200
M.T.O. Length 2000 2400 2800 2400 2800 3200 3600 4000 4400 4800 2000 2400 2800 3200 3600 4000 4400 4800
P37, P38, P39 Cantilevered Beams (Dimensions) All Sizes
Mark No 2
M.T.O. Length
100 x 10 Angle
520
Max Loads (KN) Vertical Horizontal 8.0 2.5 8.0 2.5 6.0 2.0 20.0 8.0 20.0 8.0 15.0 6.0 15.0 6.0 25.0 10.0 20.0 10.0 20.0 10.0 7.0 2.0 7.0 2.0 7.0 2.0 7.0 1.5 7.0 1.5 12.0 3.0 12.0 2.0 12.0 2.0
Sheet E25
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3 L
SPECIFICATION FOR PIPE SUPPORTS L =
Reference Pipe
=
=
Y
=
20
T.O.S. EL
1
T.O.S. EL
2
150
1
H
6
Site trim and field weld
15
3 4
20
100mm Bolt Penetration into paving
5
2
U/S Baseplate EL 100200
= 250 =
Paving Support No P41-B/C/D/E/F Size Code A1 A2 A3
B1 B2 B3 B4 C1 C2 C3 C4 D1 D2 D3 D4 E1 E2 E3 E4 F1 F2 F3 F4
35 (Typ)
Note - View Looking North or East
Dimension H L 300 500 1000 750
Size Code Mark No1 A1 70 x 8 A2 Angle A3 Size Code
H
X
X
Length 1300 1500 1800
Dimension H L 300 1000 500 750 1000 300 2000 500 750 1000 300 2000 500 750 1000 300 3000 500 750 1000 300 3000 500 750 1000
Allowable Bending Moment (KNm) 0.5
Notes
Hole Dia = 22
250 View X-X
Support No P41-A Max Pipe Size = 2"
Mark No5 (4 Off) Mark No2 Mark No3 Mark No4 Mark No6 M20 250 x 250 Cementitious M20 Nuts M20 threaded rod with 15 Thk Grout (G1) (8 Off) Hilti HY150 resin capsule Washers 3 0.01m adhesive 280 Long (8 Off) Plate Mark No1
HEA 100
HEA 100
HEA 160
HEA 160
HEA 200
Total Length 1200 1400 1650 1900 2200 2400 2650 2900 2140 2340 2600 2840 3140 3340 3600 3840 3100 3300 3550 3800
Assembly Tag No: - P41 - XX, Dimension "Y", Detail No Size Code SUPPORT No P41 SUPPORT TYPE T-Post from new paving PIPE SIZE All Sizes
Mark No2 Pipe Support Foundat'n F8N-1 Pipe Support Foundat'n F8N-1 Pipe Support Foundat'n F8N-2 Pipe Support Foundat'n F8N-2 Pipe Support Foundat'n F8N-2
Allowable Bending Moment (KNm)
Notes
4.0
4.0
Max Pipe Size = 4"
8.0
8.0
Max Pipe Size = 4"
12.0
T.O.S. EL
Sheet E26
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
L (typ) =
=
T.O.S. EL
2
1
H
Site trim and field weld 3
20 U/S Baseplate EL 100200 Paving
Notes: - 1- Size Codes "B" and "D" shall only be used for Pipe Sizes ≤ 4"
Size Code A1 A2 B1 B2 C1 C2 D1 D2 E1 E2
Dimension H
L
1000
200 300 200 300 300 450 300 450 400 550
2000 2000 3000 3000
Assembly Tag No: - P42 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Mark No 1
Total Length
Mark No 2
Area (cm²)
HEA 100
1000 1000 2000 2000 2000 2000 3000 3000 3000 3000
12 Thk square plate
400 900 400 900 900 2025 900 2025 1600 3025
HEA 100 HEA 160 HEA 160 HEA 200
15 Thk square plate
Mark No 3
Allowable Bending Moment (KNm) 4.0
Pipe Support Foundat'n 4.0 Note 1 F8N-1 Pipe 8.0 Support Foundat'n 8.0 Note 1 F8N-2 Foundat'n 12.0 F8N-2
T.O.S. EL
Size Code P42 Post with Square Plate from new paving All Sizes
Sheet E27
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS
20
Note - View Looking ????
L
20
L Y
Y T.O.S. EL T.O.S. EL
1 H 1 Site trim and field weld
H
X
X
2
150 6
2
15
3 4 20
U/S Baseplate EL 100200
5
100mm Bolt Penetration into paving = 250
Paving
= 35 (Typ)
Support No P43-B/C/D/E/F Note: -
Size Code A1 A2
1- This support is not to be used for anchoring pipes 2- The support can not be used on lines 6" and above without consultation with the stress engineer. Dimension H L 1000 250 500
Size Code Mark No1 70 x 8 A1 Angle A2 Size Code B1 B2 C1 C2 D1 D2 E1 E2 F1 F2
Length 1350 1550 1800
Dimension H L 1000 250 500 2000 250 500 2000 250 500 3000 250 500 3000 250 500
Assembly Tag No: - P43 - XX,
Hole Dia = 22
250 View X-X
Support No P43-A
Allowable Bending Moment (KNm)
Notes Max Pipe Size = 2"
0.5
Mark No5 (4 Off) Mark No2 Mark No3 Mark No4 Mark No6 M20 250 x 250 Cementitious M20 Nuts M20 threaded rod with 15 Thk Grout (G1) (8 Off) Hilti HY150 resin capsule Washers 0.01m3 adhesive 280 Long (8 Off) Plate Mark No1 HEA 100 HEA 100 HEA 160 HEA 160 HEA 200
Total Length 1240 1480 2230 2480 2200 2450 3200 3450 3180 3430
Dimension "Y",
Mark No2 Pipe Support Foundat'n F8N-1 Pipe Support Foundat'n F8N-2 Foundat'n F8N-2
Allowable Bending Moment (KNm) 4.0 4.0
Notes
Max Pipe Size = 4"
8.0 8.0
Max Pipe Size = 4"
12.0
T.O.S. EL, View looking ????
Size Code Detail No SUPPORT No P43 SUPPORT TYPE Cantilevered-Post from new paving All Sizes PIPE SIZE
Sheet E28
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS L K Reference Pipe
K
M Y
20
T.O.S. EL
Site trim and field weld 1
Note - View Looking North or East
H X
X
2
150 6
15
3 4
5
100mm Bolt Penetration into paving
= 250 = 35 (Typ)
Hole Dia = 22
250 View X-X
Note: -
Support No P44-A
Size Code A1 A2
H 1000 1000
Size Code Mark No1 A1 A2
70 x 8 Angle
Dimension M L 1100 1000 1500 1000 Length 3100 3500
Assembly Tag No: - P44 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
K 50 250
1- The support shall be used for pipes ≤ 2"
Allowable Bending Moment (KNm) 0.5
Notes Max Pipe Size = 2"
Mark No5 Mark No2 Mark No3 Mark No4 Mark No6 (8 Off) (2 Off) (16 Off) (16 Off) M20 threaded rod with M20 250 x 250 Cementitious 15 Thk Grout (G1) M20 Nuts Hilti HY150 resin capsule Washers 0.02m3 adhesive 280 Long Plate Dimension "Y",
T.O.S. EL
Size Code P44 Goal Post from new paving ½" - 2"
Sheet E29
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS L K Reference Pipe
K
M Y
T.O.S. EL
1
Note - View Looking North or East
H Site trim and field weld 2
U/S Baseplate EL 100200
Size Code B1 B2 B3 C1 C2 C3 C4 C5 C6 C7 C8 D1 D2 D3 D4 D5 D6 D7 D8 D9
20
Paving
Dimension H 1000
1000
2000
1000
2000
3000
L
K
1300 1600 2000 1400 1700 2000 2500 1400 1700 2000 2500 2000 2500 3000 2000 2500 3000 2000 2500 3000
150 300 500 100 250 250 500 100 250 250 500 150 250 500 150 250 500 150 250 500
Assembly Tag No: - P44 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Mark No 1
M 1000
HEA 100
1200 1500 HEA 160 1200 1500 1700 2000 1700 2000
HEA 200
1700 2000
Dimension "Y",
Total Length 3110 3410 3810 3100 3400 3700 4200 5100 5400 5700 6200 3620 4120 4620 5620 6120 6620 7620 8120 8620
Allowable Mark Bending No 2 Moment (2 Off) (KNm) Support Foundat'n 4.0 F8N-1
Pipe Support Foundat'n F8N-2
Pipe Support Foundat'n F8N-2
8.0
12.0
T.O.S. EL
Size Code P44 Goal Post from new paving All Sizes
Sheet E30
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
T.O.S. EL
1
H Site trim and field weld
20
2
U/S Baseplate EL 100200
Paving
For dimension "H" see Table below Note: Size Code
Dim'n H
Mark No 1
Total Length
Mark No 2
A B C D
1000 2000 2000 3000
HEA 100 HEA 100 HEA 160 HEA 160
1000 2000 2000 3000
Pipe Support Foundation F8N-1 Pipe Support Foundation F8N-2
Allowable Bending Moment (KNm) 4.0 4.0 8.0 8.0
Assembly Tag No: - P45 - X, T.O.S. EL Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Size Code P45 Post from new paving All Sizes
Sheet E31
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS L K
Reference Pipe
M Y
T.O.S. EL
1 H Site trim and field weld
2
20
Note - View Looking ????
U/S Baseplate EL 100200 Paving
Size Code A1 A2 A3 A4 B1 B2 B3 B4 B5 B6
Dimension H
L
K
1000
1600 2000 1600 2000 2120 2500 2120 2500 2120 2500
100 500 100 500 120 500 120 500 120 500
2000 1000 2000 3000
Assembly Tag No: - P46 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Mark No 1
M 1500
HEA 160
2000
HEA 200
Dimension "Y",
Total Length
Mark No 2
2500 2900 3500 3900 3020 3400 4020 4400 5020 5400
Pipe Support Foundat'n F8N-2 Pipe Support Found'n F8N-2
Allowable Bending Moment (KNm) 8.0
12.0
T.O.S. EL, View looking ????
Size Code P46 Welded Cantilevered Post from new paving All Sizes
Sheet E32
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS L =
=
Reference Pipe
Note - View Looking North or East
Y
T.O.S. EL
L = Support No P1-B/C/D/E/F
1
H
Support No P1-A =
20
1 H 2
Site trim and field weld
20 U/S Baseplate EL 100200 (typ)
Existing Grade
Dimension Size Code
Mark No1 H
A1 A2 A3 B1 B2 B3 B4 C1 C2 C3 C4 D1 D2 D3 D4 E1 E2 E3 E4 F1 F2 F3 F4
1000
1000
2000
2000
3000
3000
L 300 500 750 300 500 750 1000 300 500 750 1000 300 500 750 1000 300 500 750 1000 300 500 750 1000
Assembly Tag No: - P51 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
2
70 x 8 Angle
HEA 100
HEA 100
HEA 160
HEA 160
HEA 200
Total Length 1300 1500 1800 1200 1400 1650 1900 2200 2400 2650 2900 2140 2340 2600 2840 3140 3340 3600 3840 3100 3300 3550 3800
Dimension "Y",
Allowable Bending Mark No2 Moment (KNm) Support Foundat'n 0.5 F9-1 Pipe Support 4.0 Foundat'n F9-1 Pipe Support 4.0 Foundat'n F9-1 Pipe Support 8.0 Foundat'n F9-2 Pipe Support 8.0 Foundat'n F9-2 Pipe Support 8.0 Foundat'n F9-2
Notes For use only on Pipe Sizes ≤ 2"
For use only on Pipe Sizes ≤ 4"
For use only on Pipe Sizes ≤ 4"
T.O.S. EL
Size Code P51 T-Post for un-paved areas All Sizes
Sheet E33
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
L (typ) =
=
T.O.S. EL
2
1
H
Site trim and field weld 3
20 U/S Baseplate EL 100200
Existing Grade
Notes: - 1- Size Codes "B" and "D" shall only be used for Pipe Sizes ≤ 4" Size Code A1 A2 B1 B2 C1 C2 D1 D2 E1 E2
Dimension H
L
1000
200 300 200 300 300 450 300 450 400 550
2000 2000 3000 3000
Assembly Tag No: - P52 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Mark No 1
Total Length
Mark No 2
Area (cm²)
HEA 100
1000 1000 2000 2000 2000 2000 3000 3000 3000 3000
12 Thk square plate
400 900 400 900 900 2025 900 2025 1600 3025
HEA 100 HEA 160 HEA 160 HEA 200
15 Thk square plate
Mark No 3
Allowable Bending Moment (KNm) 4.0
Pipe Support Foundat'n 4.0 Note 1 F9-1 Pipe 8.0 Support Foundat'n 8.0 Note 1 F9-2 Foundat'n 8.0 F9-2
T.O.S. EL
Size Code P52 Post with Square Plate for un-paved areas All Sizes
Sheet E34
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS 20
L Y Note - View Looking ????
T.O.S. EL
20
L Y
T.O.S. EL 1 H
20
Site trim and field weld to existing structure
1 H
2 20 U/S Baseplate EL 100200 (typ)
2
Existing Grade
Support No P3-B/C/D/E/F Support No P3-A Note: 1- This support is not to be used for anchoring pipes 2- The support can not be used on lines 6" and above without consultation with the stress engineer. Allowable Dimension Size Mark Total Mark Bending Notes Code No 1 Length No 2 Moment H L (KNm) A1 1000 250 70 X 8 1350 0.5 For use only on A2 500 Angle 1550 Pipe Pipe Sizes ≤ 2" B1 1000 250 HEA 100 1220 Support 4.0 B2 500 1470 Foundat'n C1 2000 250 HEA 100 2220 F9-1 4.0 For use only on C2 500 2470 Pipe Sizes ≤ 4" D1 2000 250 HEA 160 2190 Pipe 8.0 D2 500 2440 Support E1 3000 250 HEA 160 3190 Foundat'n 8.0 For use only on E2 500 3440 F9-2 Pipe Sizes ≤ 4" F1 3000 250 HEA 200 3170 Foundat'n 8.0 F2 500 3420 F9-2 Assembly Tag No: - P53 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Dimension "Y",
T.O.S. EL, View looking ????
Size Code P53 Cantilevered-Post for un-paved areas All Sizes
Sheet E35
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
SUPPORT DELETED L K Reference Pipe
K
M Y
20
T.O.S. EL
1
Note - View Looking North or East
H Site trim and field weld
200 (Ref)
200 (Ref)
Existing Grade
2
Note: -
Size Code A1 A2
1- The support shall be used for pipes ≤ 2"
H
Dimension L M
Mark No 1
K
Total Length
Mark No 2 (2 Off)
SUPPORT DELETED
Assembly Tag No: - P54 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Dimension "Y",
T.O.S. EL
Size Code P54 SUPPORT Goal Post for un-paved areas ½" - 2"
DELETED
Sheet E36
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS
L K Reference Pipe
K
M Y
T.O.S. EL
1
Note - View Looking North or East
H Site trim and field weld 2
U/S Baseplate EL 100200 (typ)
20 Existing Grade
Size Code
B2 B3 C3 C4 C7 C8 D3 D6 D7 D8 D9
Dimension H
L
K
M
1000
1620 2000 2000 2500 2000 2500 3000 3000 2100 2500 3000
60 250 100 350 100 350 500 500 150 250 500
1500
1000 2000 1000 2000 3000
Assembly Tag No: - P54 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Mark No 1
Total Length
HEA 100
3430 3810 3700 4200 5700 6200 4620 6620 7720 8120 8620
1800 HEA 160 1800 2000 2000 1800 2000
Dimension "Y",
HEA 200
Allowable Mark Bending No 2 Moment (2 Off) (KNm) Support Foundat'n 4.0 F9-1 Pipe Support 8.0 Foundat'n F9-2 Pipe Support 8.0 Foundat'n F9-2
T.O.S. EL
Size Code P54 Goal Post for un-paved areas All Sizes
Sheet E37
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
T.O.S. EL
1
H Site trim and field weld
2 20 U/S Baseplate EL 100200 Existing Grade
Note: -
For dimension "H" see Table below
Size Code
Dim'n H
Mark No 1
Total Length
Mark No 2
A B C D
1000 2000 2000 3000
HEA 100 HEA 100 HEA 160 HEA 160
1000 2000 2000 3000
Pipe Support Foundation F9-1 Pipe Support Foundation F9-2
Allowable Bending Moment (KNm) 4.0 4.0 8.0 8.0
Assembly Tag No: - P55 - X, T.O.S. EL Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Size Code P55 Post for un-paved areas All Sizes
Sheet E38
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS
L K
Reference Pipe
M Y
T.O.S. EL
1 H Site trim and field weld
20 U/S Baseplate EL 100200
Size Code B1 B2 B3 B4 B5 B6
Existing Grade
Dimension H
L
K
1000
2120 2500 2120 2500 2120 2500
120 500 120 500 120 500
2000 3000
Assembly Tag No: - P56 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Note - View Looking ????
2
Mark No 1
M
2000
Dimension "Y",
HEA 200
Total Length
Mark No 2
3020 3400 4020 4400 5020 5400
Pipe Support Foundat'n F9-2
Allowable Bending Moment (KNm)
8.0
T.O.S. EL, View looking ????
Size Code P56 Welded Cantilevered Post for un-paved areas All Sizes
Sheet E39
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS
NOTE - TYPICAL SUPPORT FOR UTILITY STATIONS OR SIMILAR PIPING L Reference Pipe
=
X
=
Y
A
T.O.S. EL 10
1
H
Support No P60-A
Site trim and field weld to existing structure
A
For alternative welding arrangements refer to Support No P2
Support from grade. Steelwork sizes and dimensions as 60-A, but the support includes a baseplate BP-2"
A1 A2 A3 A4 B1 B2 B3 B4
Dimension H L 500 2000 750 1000 1300 500 2000 750 1000 1300
Assembly Tag No: - P60 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Mark No1
HEA 100
HEA 100
View A-A
1
Support No P60-B
Size Code
Site Trim shear lug if it clashes with vertical steel section
Support from Existing Steelwork
Total Length 2510 2760 3010 3310 2510 2760 3010 3310
2
Mark No2
Allowable Bending Moment (KNm)
Notes
1.0
Max pipe size 2"
1.0
Max pipe size 2"
Base Plate BP-2"
Dimension "X", Dimension "Y", T.O.S. EL,
Size Code P60 T-Post from structure or grade for Utility Stations ½" - 2"
Sheet E40
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS L =
=
Utility Pipe
20 Field Weld
SB-9 (ref only) U-Bolt shall be bolted tight so that it grips the pipe
1 Handrailing 1300 (typ)
1 2000
Site trim vertical section to suit, and field weld
Platform grating
1
Platform Support steel
20
100
20
400 Weld Angle to beam/channel face or underside of section dependant on platform design.
Size Code A1 A2 A3 A4
No of Pipes 1 2 3 4
Dimension Mark No1 L 300 500 70 x 8 700 Angle 900
Total Length 2700 2900 3100 3300
200 min
Assembly Tag No: - P61 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Size Code P61 Support for Utility Stations from platforms ½" - 2"
Sheet E41
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
NOTE - THESE SUPPORTS SHALL BE USED FOR UTILITY STATIONS ONLY Existing Column
Plan View
A Field weld
T 1
A
Reference Pipe
Y
L Field Trim Length as required
Site Trim shear lug if it clashes with vertical steel section
SB7 (Ref) T.O.S. EL
View A-A
Size Code Dimension Mark No1 L A1 600 A2 800 HEA 100 A3 1000 A4 1200
Assembly Tag No: P62 - XX Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Total Length 600 800 1000 1200
Dimension "Y"
Size Code P62 Cantilever support for utility stations ½" - 2"
Sheet E42
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Existing Column
Plan View
A Field weld
1
T A
Reference Pipe
Y L Field Trim Length as required
SB8 (Ref) UG (Ref) T.O.S. EL
View A-A
Size Code Dimension Mark No1 L A1 800 A2 1000 UPN100 A3 1200 A4 1500
Assembly Tag No: P63 - XX Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Total Length 800 1000 1200 1500
Dimension "Y"
Size Code P63 Support for steam trap manifolds ½" - 2"
Sheet E43
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS
10 2
3
1 4
250
30 Typ
30 Typ
Field Weld
175
30
Size Code A
A
24 dia Holes (4 off)
Ref Cantilever Support No P21,P22,P23 Size Codes A or B only (70 x 8 Angle, HEA 100, UPN 100)
Hole Depth = 175. Insert HVU Resin Capsule suitable for M20 threaded bar
Size Code
250
Mark No.1 10 Thk. Square Plate
Area cm2 625
Allowable Load (KNm) 4.0
Mark No.4 Mark No.2 Mark No.3 (4 Off) (4 Off) (4 Off) M20 Threaded Bar & M20 M20 HVU Resin Capsule Washer Nuts
Length
220
Assembly Tag No: - P20 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Size Code P20 Base Plate for Cantilever to Concrete 2" - 6"
Sheet E44
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS L =
=
Reference Pipe
Note - View Looking North or East
Y
T.O.S. EL
L = Support No P71-B/C/D/E/F
1
H
Support No P71-A =
20
1 H
Site trim and field weld 20
3
U/S Baseplate EL 200 above Local Grade (typ)
Local Grade 2
Dimension Size Code
Mark No1 H
A1 A2 A3 B1 B2 B3 B4 C1 C2 C3 C4 D1 D2 D3 D4 E1 E2 E3 E4 F1 F2 F3 F4
1000
1000
2000
2000
3000
3000
L 300 500 750 300 500 750 1000 300 500 750 1000 300 500 750 1000 300 500 750 1000 300 500 750 1000
Assembly Tag No: - P71 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
70 x 8 Angle
HEA 100
HEA 100
HEA 160
HEA 160
HEA 200
Total Length 1300 1500 1800 1200 1400 1650 1900 2200 2400 2650 2900 2140 2340 2600 2840 3140 3340 3600 3840 3100 3300 3550 3800
Dimension "Y",
Allowable Bending Mark No2 Mark No3 Notes Moment (KNm) Support F8N-4 For use Foundat'n Size Negligible on Pipes F9-10 Code A Sizes ≤ 2" Pipe Support Pipe 4.0 Foundat'n Support F9-6 Foundat'n Pipe F8N4 For use Support Size 4.0 on Pipes Foundat'n Code B Sizes ≤ 4" F9-6 Pipe Support 8.0 Foundat'n F9-9 Pipe Pipe Support For use Support Foundat'n 8.0 on Pipes Foundat'n F8N4 Sizes ≤ 4" F9-9 Size Pipe Code C Support 8.0 Foundat'n F9-9
T.O.S. EL
Size Code P71 T-Post for un-paved areas All Sizes
Sheet E45
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS L (typ) =
=
T.O.S. EL
2
1
H
Site trim and field weld 4 20
3
U/S Baseplate EL 200 above Local Grade (typ)
Local Grade
Notes: - 1- Size Codes "B" and "D" shall only be used for Pipe Sizes ≤ 4" Size Code A1 A2 B1 B2 C1 C2 D1 D2 E1 E2
Dimension H L 1000 200 300 2000 200 300 2000 300 450 3000 300 450 3000 400 550 Size Code A, B C,D,E
SUPPORT No SUPPORT TYPE PIPE SIZE
HEA 100 HEA 160 HEA 160 HEA 200
Total Length 1000 1000 2000 2000 2000 2000 3000 3000 3000 3000
Mark No 2 12 Thk square plate
15 Thk square plate
Area (cm²) 400 900 400 900 900 2025 900 2025 1600 3025
Mark Mark No 3 No 4 Pipe Foundat'n Support F8N4 Foundat'n Size F9-6 Code B Pipe Pipe Support Support Foundat'n Foundat'n F9-9 F8N4 Foundat'n Size F9-9 Code C
Allowable Bending Moment (KNm) 4.0 8.0
Assembly Tag No: - P72 - XX, Detail No
Mark No 1 HEA 100
T.O.S. EL
Size Code P72 Post with Square Plate for un-paved areas All Sizes
Sheet E46
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS 20
L Y Note - View Looking ????
T.O.S. EL
20
L Y
T.O.S. EL 1 H
20
Site trim and field weld to existing structure
1 H
3
3 20 U/S Baseplate EL 200 above Local Grade (typ)
Local Grade
2 Support No P73-B/C/D/E/F Support No P73-A Note: 1- This support is not to be used for anchoring pipes 2- The support can not be used on lines 6" and above without consultation with the stress engineer. Allowable Dimension Size Mark Total Mark Mark Bending Code No 1 Length No 2 No 3 Moment H L (KNm) A1 1000 250 70 x 8 1350 Pipe Fnd. F8N4 Negligible A2 500 Angle 1550 F9-10 Code A B1 1000 250 HEA 100 1220 Pipe Foundat'n 4.0 B2 500 1470 Support F8N4 C1 2000 250 HEA 100 2220 Foundat'n Size 4.0 C2 500 2470 F9-6 Code B D1 2000 250 HEA 160 2190 Pipe Pipe 8.0 D2 500 2440 Support Support E1 3000 250 HEA 160 3190 Foundat'n Foundat'n 8.0 E2 500 3440 F9-9 F8N4 F1 3000 250 HEA 200 3170 Foundat'n Size 8.0 F2 500 3420 F9-9 Code C Assembly Tag No: - P73 - XX, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Dimension "Y",
Notes
For Pipes Sizes ≤ 2"
For Pipes Sizes ≤ 4"
For Pipes Sizes ≤ 4"
T.O.S. EL, View looking ????
Size Code P73 Cantilevered-Post for un-paved areas All Sizes
Sheet E47
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS L K Reference Pipe
K
M Y
T.O.S. EL
1
Note - View Looking North or East
H Site trim and field weld 3
U/S Baseplate EL 200 above Local Grade (typ)
20 Local Grade
2
Size Code B2 B3 C3 C4 C7 C8 D3 D6 D7 D8 D9
H 1000 1000 2000 1000 2000 3000
Size Code B C,D
Dimension L K 1620 2000 2000 2500 2000 2500 3000 3000 2100 2500 3000
60 250 100 350 100 350 500 500 150 250 500
Detail No
Mark No 1
Total Length
1500
HEA 100
3420 3800 3680 4180 5680 6180 4600 6600 7700 8100 8600
1800 HEA 160 1800 2000 2000 1800 2000
HEA 200
Mark No 2 Mark No 3 (2 Off) (2 Off) Support F8N4 Foundat'n Size F9-6 Code B Pipe Support Pipe Foundat'n Support F9-9 Foundat'n Pipe F8N4 Support Size Foundat'n Code C F9-9
Allowable Bending Moment (KNm) 4.0 8.0
Assembly Tag No: - P74 - XX, SUPPORT No SUPPORT TYPE PIPE SIZE
M
Dimension "Y",
T.O.S. EL
Size Code P74 Goal Post for un-paved areas All Sizes
Sheet E48
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS
T.O.S. EL
1
H Site trim and field weld
3 20 U/S Baseplate EL 200 above Local Grade (typ)
Local Grade
2
Note: -
For dimension "H" see Table below
Size Code
Dim'n H
Mark No 1
Total Length
Mark No 2
A B C D
1000 2000 2000 3000
HEA 100 HEA 100 HEA 160 HEA 160
1000 2000 2000 3000
Pipe Support Foundation F9-6 Pipe Support Foundation F9-9
Allowable Bending Moment (KNm) Support Foundation 4.0 F8N4 Size Code B 4.0 Support Foundation 8.0 F8N4 Size Code C 8.0 Mark No 3
Assembly Tag No: - P75 - X, T.O.S. EL Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Size Code P75 Post for un-paved areas All Sizes
Sheet E49
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS L K
Reference Pipe
M Y
T.O.S. EL
1 H Site trim and field weld Note - View Looking ????
3
20 U/S Baseplate EL 200 above Local Grade (typ)
Local Grade 2
Size Code B1 B2 B3 B4 B5 B6
H 1000 2000 3000
Size Code B
Dimension L K 2120 120 2500 500 2120 120 2500 500 2120 120 2500 500
SUPPORT No SUPPORT TYPE PIPE SIZE
Mark No 1
2000
HEA 200
Total Length 3020 3400 4020 4400 5020 5400
Mark No 2
Mark No 3 Pipe Pipe Support Support Foundat'n Foundat'n F8N4 F9-9 Size Code C
Allowable Bending Moment (KNm) 8.0
Assembly Tag No: - P76 - XX, Detail No
M
Dimension "Y",
T.O.S. EL, View looking ????
Size Code P76 Welded Cantilevered Post for un-paved areas All Sizes
Sheet E50
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS 1000
Site drill angle and Guide Pipes with U-Bolt Guide No UG301 (ref)
=
= Y
Reference Pipe
20
1 800 Baseplate shall rest on floor of Caustic Sump
Site Trim and field weld to suit slope in sump
2
300
= 500 =
=
= 800
Size Code A1
Mark No 1 70 x 8 Angle
Total Length 2200
Assembly Tag No: - P64 - A1, Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Mark No 2 15 Thk Plate
Area (cm²) 4000
Dimension "Y",
NOTEMark Nos 1 & 2 (base plate and angle) shall be painted with an epoxy paint System AD. The painting shall be made good after welding and drilling of the pipe support
Size Code P64 T-Post for use in Caustic Sump All Sizes
Sheet E51
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 2
SPECIFICATION FOR PIPE SUPPORTS
Pipe Support No SB2 Anchor
Pipe Support No SB1 Guide X
X
1
1
2
2
60
X
X 1200
=
Site Trim to suit
A =
10 Dia Hole (Typ) View X-X
35
Pipe Sup't No
Pipe Size ½ ¾ 1 1½ 2 ½ ¾ 1 1½ 2
SB1
SB2
Mark No 1
Length
Mark No 2
60 x 6 Angle
1260
U-Bolt Guide
60 x 6 Angle
1260
U-Bolt Anchor
Size UG-½ UG-¾ UG-1 UG-1½ UG-2 UA-½ UA-¾ UA-1 UA-1½ UG-2
Dimension A 31 37 44 58 74 29 35 42 56 72
Assembly Tag No: - SB1 or SB2 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
SB1, SB2 Base Guide/Support from Steel for Horizontal Pipes ½" - 2"
Sheet F1
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 4
SPECIFICATION FOR PIPE SUPPORTS Pipe Support No SB3 - Guide X
Pipe Support No SB4 - Anchor X
U-Bolt to be raised if paving settles to ensure pipe remains horizontal
1
1
200
2
2
1200
X
Slotted Holes (4 Off)
X Site Trim to suit and Field Weld
60
3
35 5
Pipe
4
CL
25
10 (typ)
= =
A 25
20 (Typ)
= =
Pipe Sup't No
22 Dia Hole =
= 120
SB3
NOTES 1- For General Notes refer to Drawing Nos. 60-0000-Q-STD-0010-01 and 02
Pipe Sup't No
SB3
SB4
View X-X
35
120
Pipe Size (") ½ ¾ 1 1½ 2 ½ ¾ 1 1½ 2
Mark No 2 (1 Off) U-Bolt Guide
U-Bolt Anchor
Size
Mark No 3
UG-½ UG-¾ UG-1 UG-1½ UG-2 UA-½ UA-¾ UA-1 UA-1½ UA-2
Assembly Tag No: - SB3 or SB4 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
SB4
Area (cm²)
10 Thk Plate
144
10 Thk Plate
144
Pipe Size ½ ¾ 1 1½ 2 ½ ¾ 1 1½ 2
Mark No 1
Length
60 x 6 Angle
1400
60 x 6 Angle
1400
Dimension A 31 37 M 20 threaded rod 44 with Hilti HY 150 resin 58 capsule adhesive 74 170 Long. (Hilti 29 HIT-ICE resin to be 35 used if the installation temperature 42 is below -5°C) 56 72 Mark No 5 Cementitious Grout (G1) 0.005m3 Mark No 4 (1 Off)
SB3, SB4 Base Guide/Support from Grade for Horizontal Pipes ½" -2"
Sheet F2
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 2
SPECIFICATION FOR PIPE SUPPORTS
240
60
A
Y
10
= X
=
X
45
35
Y
10 Dia Hole in Angle (Typ)
2 1200
View X-X 150
1
Site Trim to suit and Field Weld
50 3
View Y-Y
Pipe Size ½ ¾ 1 1½ 2
Mark No 1
60 x 6 Angle
Length
1545
Mark No 2 (1 Off) U-Bolt Anchor
Size UA-½ UA-¾ UA-1 UA-1½ UA-2
Mark No 3
Area (cm²)
6 Thk Plate
75
Dimension A 29 35 42 56 72
Assembly Tag No: - SB5 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size SB5 Base Support from Steel for Vertical Pipes ½" - 2"
Sheet F3
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 4
SPECIFICATION FOR PIPE SUPPORTS 240
60
A
Y
10
= X
=
X
45
35
10 Dia Hole in Angle (Typ)
Y 2
1
1200
Z
View X-X 150
Site Trim to suit and Field Weld
Z
50
3
5
25 Grout (Min)
View Y-Y Shim pipe support if paving settles
6 4
20 (Typ)
=
Existing Paving
120 =
NOTES 1- For General Notes refer to Drawing Nos. 60-0000-Q-STD-0010-01 and 02 Pipe Mark No 1 Mark No 2 Size Size (1 Off) ½ 60 x 6 UA-½ ¾ Angle U-Bolt UA-¾ 1 Anchor UA-1 1½ Length UA-1½ 2 =1545 UA-2 Assembly Tag No: - SB6 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
22 Dia Hole =
=
View Z-Z
120 Mark No 4 Mark No 5 Dimension A (1 Off) 10 Thk 6 Thk 29 M 20 threaded rod Plate Plate 35 with Hilti HY 150 resin 42 capsule adhesive Area = Area = 56 170 Long. (Hilti 75 cm² 72 144 cm² HIT-ICE resin to be Mark No 6 used if the installation Cementitious Grout temperature 3 is below -5°C) (G1) 0.01m
Mark No 3
SB6 Base Support from Grade for Vertical Pipes ½" - 2"
Sheet F4
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 2
SPECIFICATION FOR PIPE SUPPORTS
150
50 Elevation 1 Existing Steel
3
2 X
X 10 Dia Hole (Typ) =
Plan
A
B
= View X-X
Pipe Size ½ ¾ 1 1½ 2
Mark No 1 6 Thk Plate
Area (cm²)
Mark No 2
75
60 x 6 Angle
Length 70 75 85 100 120
Mark No 3 (1 Off) U-Bolt Guide
Size UG-½ UG-¾ UG-1 UG-1½ UG-2
Dimension A B 31 70 37 75 44 85 58 100 74 120
Assembly Tag No: - SB7 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size SB7 Support and Guide for Vertical Pipes ½" - 2"
Sheet F5
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 2
SPECIFICATION FOR PIPE SUPPORTS
150
50
1
Pipe Size ½ ¾ 1 1½ 2
Mark No 1
Area (cm²)
6 Thk Plate
75
Assembly Tag No: - SB8 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size SB8 Support for Vertical Pipes ½" - 2"
Sheet F6
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 2
SPECIFICATION FOR PIPE SUPPORTS
X
X
Elevation
Existing Steel
10 Dia Hole (Typ)
1
2 = Plan
A
B
= View X-X
Pipe Size ½ ¾ 1 1½ 2
Mark No 1
60 x 6 Angle
Length
Mark No 2 (1 Off)
70 75 85 100 120
U-Bolt Guide
Size UG-½ UG-¾ UG-1 UG-1½ UG-2
Dimension A B 31 70 37 75 44 85 58 100 74 120
Assembly Tag No: - SB9 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size SB9 Guide for Vertical Pipes ½" - 2"
Sheet F7
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 2
SPECIFICATION FOR PIPE SUPPORTS
Pipe Support No SB102 Anchor
Pipe Support No SB101 Guide X
X
1
1
2
2
80
X
X 1200
=
Site Trim to suit
A =
Hole Dia = D 35
Pipe Sup't No
SB101
SB102
Pipe Size ½ ¾ 1 1½ 2 ½ ¾ 1 1½ 2
Mark No 1
60 x 6 Angle
60 x 6 Angle
Length
Mark No 2
1280
Insulated U-Bolt Guide for Stainless Steel Pipes.
1280
Insulated U-Bolt Anchor for Stainless Steel Pipes.
View X-X Size ½ ¾ 1 1½ 2 ½ ¾ 1 1½ 2
Dimension Hole Dia A D 37 43 8 50 75 12 87 37 43 8 50 75 12 87
Assembly Tag No: - SB101 or SB102 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
SB101, SB102 Base Guide/Support from Steel for Horizontal SS Pipes ½" - 2"
Sheet F8
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 4
SPECIFICATION FOR PIPE SUPPORTS
Pipe Support No SB104 - Anchor
Pipe Support No SB103 - Guide X
X
U-Bolt to be raised if paving settles to ensure pipe remains horizontal
1
1
200
2
2
1200
X
Site Trim to suit and Field Weld
4
Slotted Holes (4 Off)
X
3 25 Grout (Min)
150
60
Existing Paving 5
35
Pipe
25
10 (typ)
= =
C L
20 (Typ)
=
25
120 35
=
22 Dia Hole =
= 120
NOTES 1- For General Notes refer to Drawing Nos. 60-0000-Q-STD-0010-01 and 02 Pipe Sup't No
Pipe Size (") ½ ¾ 1 1½ 2 ½ ¾ 1 1½ 2
Mark No 2
Size
A
Mark No 3
Pipe Sup't No SB103
Pipe Size ½-2
SB104
½-2
Mark No 4 (1 Off)
View X-X Mark No 1
Length
60 x 6 Angle 60 x 6 Angle
1400 1400
Dimension Hole Dia A D Insulated ½ 10 Thk 37 M 20 threaded rod U-Bolt ¾ Plate 43 8 with Hilti HY 150 resin SB103 guide for 1 50 capsule adhesive Stain. Stl 1½ Area = 75 12 170 Long. (Hilti Pipes 2 144 cm² 87 HIT-ICE resin to be Insulated ½ 10 Thk 37 used if the installation U-Bolt ¾ Plate 43 8 temperature SB104 Anchor for 1 50 is below -5°C) Stain. Stl 1½ Area = 75 12 Pipes 2 144 cm² 87 Mark No 5 Assembly Tag No: - SB103 or SB104 - X Cementitious Grout Pipe Size Detail No (G1) 0.005m3 SUPPORT No SB103, SB104 Sheet F9 SUPPORT TYPE Base Guide/Anchor from Grade for Horizontal SS Pipes PIPE SIZE ½" -2"
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 2
SPECIFICATION FOR PIPE SUPPORTS
240
60
Hole Dia = D
Y
A
10
= X
=
X
45
35
Y 2 1200
View X-X
1 150 Site Trim to suit and Field Weld 50 3 Stainless Steel plate ASTM-A-240 Type 316 or equivalent View Y-Y
Pipe Size ½ ¾ 1 1½ 2
Mark No 1
Length
60 x 6 Angle
Mark No 2 Insulated U-Bolt Guide for Stainless Steel Pipes.
1545
Size ½ ¾ 1 1½ 2
Mark Dimension Hole Dia A D No 3 5 Thk 37 SS Plate 43 8 50 Area = 75 12 87 75 cm²
Assembly Tag No: - SB105 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
SB105 Base Support from Steel for SS Vertical Pipes ½" - 2"
Sheet F10
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 4
SPECIFICATION FOR PIPE SUPPORTS 240
60
Hole Dia = D
Y
10
A =
X
=
X
45
35
Y View X-X 2 1200
1 150 Z
Z
Site Trim to suit and Field Weld
5
4
Shim pipe support if paving settles 50
25 Grout (Min)
View Y-Y 150 Existing Paving
3 Stainless Steel plate ASTM-A-240 Type 316 or equivalent
6
20 (Typ)
=
Pipe Size ½ ¾ 1 1½ 2
120 =
22 Dia Hole
View Z-Z
=
=
NOTES 1- For General Notes refer to Drawing Nos. 60-0000-Q-STD-0010-01 and 02
120 Pipe Size ½ ¾ 1 1½ 2
Mark No 2
Mark No 1 60 x 6 Angle
Insulated U-Bolt Guide for Stainless Steel Pipes.
Length =1545
Assembly Tag No: - SB106 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Dimension Hole Dia A D 37 43 8 50 75 12 87
Pipe Size
Size ½ ¾ 1 1½ 2
Mark No 5 (1 Off) M 20 threaded rod 5 Thk 10 Thk with Hilti HY 150 resin SS Plate Plate capsule adhesive 170 Long. (Hilti Area = Area = 75 cm² 144 cm² HIT-ICE resin to be Mark No 6 used if the installation temperature Cementitious Grout 3 is below -5°C) (G1) 0.01m
Mark No 3 Mark No 4
SB106 Base Support from Grade for Vertical SS Pipes ½" - 2"
Sheet F11
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 3
SPECIFICATION FOR PIPE SUPPORTS 150
Stainless Steel plate ASTM-A-240 Type 316 or equivalent
50 Elevation 1 Existing Steel
3
2 X
X
Hole Dia = D
= B
A = View X-X Pipe Size ½ ¾ 1 1½ 2
Mark No 1 5 Thk SS Plate
Area (cm²)
Mark No 2
75
60 x 6 Angle
Length 80 90 100 120 140
Dimension A B 37 80 43 90 50 100 75 120 87 140
Pipe Size ½ ¾ 1 1½ 2
Mark No 3 Insulated U-Bolt Guide for Stainless Steel Pipes.
Size ½ ¾ 1 1½ 2
Hole Dia D 8 12
Assembly Tag No: - SB107 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
SB107 Support and Guide for Vertical SS Pipes ½" - 2"
Sheet F12
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 3
SPECIFICATION FOR PIPE SUPPORTS
Stainless Steel plate ASTM-A-240 Type 316 or equivalent
150
50
1
Pipe Size ½ ¾ 1 1½ 2
Mark No 1
Area (cm²)
5 Thk SS Plate
75
Assembly Tag No: - SB108 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
SB108 Support for Vertical Stainless Steel Pipes ½" - 2"
Sheet F13
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 2
SPECIFICATION FOR PIPE SUPPORTS
X
X
Elevation
Existing Steel
Hole Dia = D
2 = A
B
=
View X-X 1 Pipe Size ½ ¾ 1 1½ 2
Mark No 1
Length
Mark No 2
80 90 100 120 140
60 x 6 Angle
Insulated U-Bolt Guide for Stainless Steel Pipes.
Size ½ ¾ 1 1½ 2
Dimension A B 37 80 43 90 50 100 75 120 87 140
Hole Dia D 8 12
Assembly Tag No: - SB109 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
SB109 Guide for Vertical Pipes ½" - 2"
Sheet F14
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 2
SPECIFICATION FOR PIPE SUPPORTS
C T
R = 1.5 x T (typ) 1
A
B
D
A
B 2
Bolts shall be provided with a nut and a locking nut
SUPPORT No SUPPORT TYPE PIPE SIZE
PC1, PC2 2-Bolt Pipe Clip ½" - 30"
Hole Dia = Bolt Dia + 2
Sheet F15
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 3
SPECIFICATION FOR PIPE SUPPORTS
2 Bolt Pipe Clip - Light Load. Pipe Support No PC1 Pipe Size ½ ¾ 1 1½ 2 3 4 5½ 6 8 10 12 14 16 18 20 22 24 26 28 30
Mark No 1 (2 Off)
40 x 6 Plate
50 x 10 Plate
80 x 15 Plate
100 x 20 Plate
Total Length 228 235 266 335 372 485 606 732 820 1006 1215 1377 1489 1647 1857 2019 2245 2423 2729 2891 3053
Mark No 2 (2 Off) M12 x 50 Bolts
M16 x 60 Bolts
M20 x 80 Bolts M24 x 100 Bolts M30 x 120 Bolts M36 x 140 Bolts
A 32 32 38 51 57 76 95 113 127 159 190 216 235 260 298 324 357 387 440 466 492
B 51 51 57 70 76 96 119 143 157 189 226 252 271 296 334 360 402 432 494 520 546
Dimensions C 12
16 20 24
27
34 40
D 21 27 33 48 60 89 114 140 168 219 273 324 356 406 457 508 559 610 660 711 762
T
6
10
15
20
2 Bolt Pipe Clip - Heavy Load. Pipe Support No PC2 Pipe Size
Mark No 1 (2 Off)
Total Length
3 4 6 8 10 12 14 16 18 20 22 24 26 28 30
50 x 10 Plate
561 658 876 1034 1291 1489 1641 1799 1957 2115 2333 2491 2729 2891 3053
80 x 15 Plate
100 x 20 Plate
220 x 20 Plate
SUPPORT No SUPPORT TYPE PIPE SIZE
Mark No 2 (2 Off) M20 x 80 Bolts M24 x 100 Bolts M30 x 120 Bolts
M36 x 140 Bolts
A
B
85 96 135 160 200 235 255 280 305 330 370 395 440 466 492
115 132 171 196 245 280 309 334 359 384 424 449 494 520 546
PC1, PC2 2-Bolt Pipe Clip (dimensions) ½" - 30"
Dimensions C 24 27
34
40
D
T
89 114 168 219 273 324 356 406 457 508 559 610 660 711 762
10
15
20
Sheet F16
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 2
SPECIFICATION FOR PIPE SUPPORTS
C T 3
Spacer
E
R = 1.5 x T (Typ)
B A
1 D
A
F 2
3 Spacer
SUPPORT No SUPPORT TYPE PIPE SIZE
PC3, PC4 3-Bolt Pipe Clip ½" - 24"
Bolts shall be provided with a nut and a locking nut
Hole Dia = Bolt Dia + 2
Sheet F17
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 2
SPECIFICATION FOR PIPE SUPPORTS
3 Bolt Pipe Clip - Light Load. Pipe Support No PC3
Pipe Size ½ ¾ 1 1½ 2 3 4 6 8 10 12 14 16 18 20 22 24
Pipe Size ½ ¾ 1 1½ 2 3 4 6 8 10 12 14 16 18 20 22 24
Mark No 1 (2 Off)
A 32 38 44 51 54 76 100 135 163 192 220 243 273 300 329 365 390
B 92 95 97 102 127 152 165 216 241 279 305 330 356 381 406 432 457
SUPPORT No SUPPORT TYPE PIPE SIZE
40 x 6 Plate
50 x 10 Plate 80 x 15 Plate
100 x 20 Plate
Total Length 332 357 400 439 518 649 776 1046 1210 1405 1571 1743 1909 2075 2253 2459 2617
C 12 16 25
38
51
Mark No 2 Mark No 3 (3 Off) (2 Off) M12 x 50 Bolts
Total Length 24 32
1" Sch 80 M16 x 80 Pipe Bolts M20 x 100 Bolts M24 x 130 Bolts M30 x 150 Bolts
Dimensions D 21 27 33 48 60 89 114 168 219 273 324 356 406 457 508 559 610
50
76
1½" Sch 80 Pipe
102
E 107 110 117 124 149 175 194 254 279 317 343 378 403 429 457 489 514
F 47 53 64 68 76 99 129 173 201 230 258 291 320 348 380 422 447
PC3 3-Bolt Pipe Clip, Light Load (Dimensions) ½" - 24"
T
6
10
15
20
Sheet F18
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 2
SPECIFICATION FOR PIPE SUPPORTS
Pipe Size 6 8 10 12 14 16 18 20 22 24
Pipe Size 6 8 10 12 14 16 18 20 22 24
Mark No 1 (2 Off) 80 x 15 Plate 100 x 20 Plate
A 143 172 214 240 262 292 317 353 393 418
B 229 254 305 330 356 381 406 457 483 508
SUPPORT No SUPPORT TYPE PIPE SIZE
130 x 20 Plate 220 x 20 Plate
Total Length 1136 1306 1553 1713 1869 2037 2199 2455 2693 2851
C 44
51
57
Mark No 2 Mark No 3 (3 Off) (2 Off) M30 x 120 Bolts 1½" Pipe M36 x 160 Sch 80 Bolts
Total Length 88
102
M42 x 180 2" Sch 80 Bolts Pipe
114
Dimensions D 168 219 273 324 356 406 457 508 559 610
F 193 223 265 291 319 349 375 417 469 494
E 279 305 356 381 413 438 464 521 559 584
PC4 3-Bolt Pipe Clip, Heavy Load (Dimensions) 6" - 24"
T 15
20
Sheet F19
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 3
SPECIFICATION FOR PIPE SUPPORTS
C T
R = 1.5 x T (typ) A
1 D
B
D
3 A
B 2
Bolts shall be provided with a nut and a locking nut
SUPPORT No SUPPORT TYPE PIPE SIZE
PC101, PC102 2-Bolt Pipe Clip for Stainless Steel pipes ½" - 32"
Hole Dia = Bolt Dia + 2
Sheet F20
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 3
SPECIFICATION FOR PIPE SUPPORTS
2 Bolt Pipe Clip - Light Load. Pipe Support No PC101 Pipe Size ½ ¾ 1 1½ 2 3 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32
Mark No 1 (2 Off)
40 x 6 Plate
50 x 10 Plate
80 x 15 Plate
100 x 20 Plate
Total Length 266 272 303 372 410 523 644 857 1043 1253 1415 1527 1685 1895 2057 2283 2461 2753 2915 3077 3135
Mark No 2 Mark No 3 (2 Off) (1 Off) M12 x 50 Bolts
M16 x 60 Bolts M20 x 80 Bolts
Isolation Strip
M24 x 100 Bolts M30 x 120 Bolts
M36 x 140 Bolts
A 38 38 44 57 63 82 101 133 165 196 222 241 266 304 330 363 393 446 472 498 498
B 57 57 63 76 82 102 125 163 195 232 258 277 302 340 366 408 438 500 526 552 552
Dimensions C 12
16 20 24
27
34 40
D 33 39 45 60 72 101 126 180 231 285 336 368 418 469 520 571 622 660 711 762 813
T
6
10
15
20
2 Bolt Pipe Clip - Heavy Load. Pipe Support No PC102 Pipe Size
Mark No 1 (2 Off)
Total Length
3 4 6 8 10 12 14 16 18 20 22 24
50 x 10 Plate
599 696 913 1071 1329 1527 1679 1837 1995 2153 2371 2529
80 x 15 Plate
100 x 20 Plate
SUPPORT No SUPPORT TYPE PIPE SIZE
Mark No 2 Mark No 3 (2 Off) (1 Off) M20 x 80 Bolts M24 x 100 Bolts M30 x 120 Isolation Bolts Strip
M36 x 140 Bolts
A
B
91 102 141 166 206 241 261 286 311 336 376 401
121 138 177 202 251 286 315 340 365 390 430 455
PC101, PC102 2-Bolt Pipe Clip for Stainless Steel pipes (dimensions) ½" - 32"
Dimensions C 24 27
34
40
D
T
101 126 180 231 285 336 368 418 469 520 571 622
10
15
20
Sheet F21
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 2
SPECIFICATION FOR PIPE SUPPORTS
C T 3
Spacer
E
R = 1.5 x T (Typ)
B A
1 D
D D
A
F 2
3 Spacer
SUPPORT No SUPPORT TYPE PIPE SIZE
Bolts shall be provided with a nut and a locking nut
PC103, PC104 3-Bolt Pipe Clip for Stainless Steel pipes ½" - 24"
Hole Dia = Bolt Dia + 2
Sheet F22
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 2
SPECIFICATION FOR PIPE SUPPORTS
3 Bolt Pipe Clip - Light Load. Pipe Support No PC103
Pipe Size ½ ¾ 1 1½ 2 3 4 6 8 10 12 14 16 18 20 22 24
Pipe Size ½ ¾ 1 1½ 2 3 4 6 8 10 12 14 16 18 20 22 24
Mark No 1 (2 Off)
A 38 44 50 57 60 82 106 141 169 198 226 249 279 306 335 374 399
B 98 101 103 108 133 158 171 222 247 285 311 336 362 387 412 441 466
SUPPORT No SUPPORT TYPE PIPE SIZE
40 x 6 Plate
50 x 10 Plate 80 x 15 Plate 100 x 20 Plate HOLD
Total Length 370 394 437 476 556 687 814 1083 1247 1443 1609 1781 1947 2113 2291 2516 2673
C 12 16 25
38
51
Mark No 2 Mark No 3 (3 Off) (2 Off) M12 x 50 Bolts
Total Length 24 32
1" Sch 80 M16 x 80 Pipe Bolts M20 x 100 Bolts M24 x 130 Bolts M30 x 150 Bolts
Dimensions D 33 39 45 60 72 101 126 180 231 285 336 368 418 469 520 577 628
50
76
1½" Sch 80 Pipe
102
E 113 116 123 130 155 181 200 260 285 323 349 384 409 435 463 498 523
F 53 59 70 74 82 105 135 179 207 236 264 297 326 354 386 431 456
PC103 3-Bolt Pipe Clip for Stainless Steel pipes, Light Load ½" - 24"
T
6
10
15
20
Sheet F23
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 2
SPECIFICATION FOR PIPE SUPPORTS
Pipe Size 6 8 10 12 14 16 18 20 22 24
Pipe Size 6 8 10 12 14 16 18 20 22 24
Mark No 1 (2 Off) 80 x 15 Plate 100 x 20 Plate
A 149 178 223 249 271 304 329 365 405 430
B 235 260 314 339 365 393 418 469 495 520
SUPPORT No SUPPORT TYPE PIPE SIZE
HOLD
HOLD
Total Length 1173 1343 1610 1770 1926 2113 2275 2530 2768 2926
C 44 51
57
Mark No 2 Mark No 3 (3 Off) (2 Off) M30 x 120 Bolts 1½" Pipe M36 x 160 Sch 80 Bolts
Total Length 88
M42 x 180 2" Sch 80 Bolts Pipe
114
Dimensions D 180 231 291 342 374 430 481 532 583 634
E 285 311 365 390 422 450 476 533 571 596
102
F 199 229 274 300 328 361 387 429 481 506
PC104 3-Bolt Pipe Clip for Stainless Steel pipes, Heavy Load 6" - 24"
T 15
20
Sheet F24
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 2
SPECIFICATION FOR PIPE SUPPORTS
2 Gap (typ)
1
2 10 Max
L T
10 Dia Hole in Existing Steel
D C
Pipe Size ½ ¾ 1 1½ 2 2½
Pipe O.D. 21 27 34 48 60 73
Mark No 1 Developed Mark No 2 Length (4 Off) 8 dia 126 Round 141 Bar 159 M 8 Nut 195 226 259
C 31 37 44 58 70 83
Dimension D L 39 42 8 45 52 58 65
T
38
Assembly Tag No: - UG - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size UG U-Bolt Guide ½" - 2½"
Sheet F25
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 2
SPECIFICATION FOR PIPE SUPPORTS
1
10 Max
L T
10 Dia Hole in Existing Steel D
2
C
Pipe Size ½ ¾ 1 1½ 2 2½
Pipe O.D. 21 27 34 48 60 73
Mark No 1 Developed Mark No 2 Length (4 Off) 133 8 dia 148 Round 166 M 8 Nut Bar 202 233 266
C 29 35 42 56 68 81
Dimension D L 44 47 8 50 57 63 70
T
30
Assembly Tag No: - UA - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
UA U-Bolt Anchor ½" - 2½"
Sheet F26
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 2
SPECIFICATION FOR PIPE SUPPORTS D
F
Clevis pin with split pins
E
G B C
H
(Typ)
A
J L
Note: -
CLR - Right hand thread clevis CLL - Left hand thread clevis
Pipe Sup't Sling Rod No Dia D CL-12 12 CL-16 16 CL-20 20 CL-24 24 CL-30 30 CL-36 36 CL-42 42 Pipe Sup't Sling Rod No Dia D CL-12 12 CL-16 16 CL-20 20 CL-24 24 CL-30 30 CL-36 36 CL-42 42 SUPPORT No SUPPORT TYPE PIPE SIZE
CLL, CLR Clevis All Sizes
A
B
C
E
F
30 45 45 65 65 70 90
19 33 33 38 38 45 51
10 10 10 12 12 12 12
82 68 68 63 63 152 152
32 32 32 32 32 41 44
G
H
J
L
12 16 20 24 30 36 42
14 18 22 26 32 39 45
38 50 50 58 58 80 85
55 65 65 80 80 100 105
Max Load (KN) 5.0 10.0 15.0 23.0 35.0 53.0 73.0
Sheet F27
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 2
SPECIFICATION FOR PIPE SUPPORTS
C
R.H. Thread Locknut
B
L
150
L.H. Thread Locknut
Pipe Sup't Sling Rod No Dia D TB-12 12 TB-16 16 TB-20 20 TB-24 24 TB-30 30 TB-36 36 TB-42 42
SUPPORT No SUPPORT TYPE PIPE SIZE
TB Turnbuckle All Sizes
D
B
C
L
20 26 32 39 53 58 68
31 41 49 59 67 78 92
190 202 214 228 256 266 286
Max Load (KN) 5.0 10.0 15.0 23.0 35.0 53.0 73.0
Sheet F28
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 2
SPECIFICATION FOR PIPE SUPPORTS
OC OA NOTE WENL- Left hand thread WENR- Right hand thread
K
F
B M
D
Note: -
1- WENL - Left hand thread Weldless Eye Nut WENR - Right hand thread Weldless Eye Nut 2- Minimum Length of Thread Engagement equals Diameter of Sling Rod. 3- Variations on dimensions are acceptable provided the load bearing requirements are met.
Pipe Sup't Sling Rod No Dia A WEN-12 12 WEN-16 16 WEN-20 20 WEN-24 24 WEN-30 30 WEN-36 36 WEN-42 42
SUPPORT No SUPPORT TYPE PIPE SIZE
B
C
K
M
F
D
9 13 16 19 29 29 30
38 38 45 50 70 70 80
18 18 25 28 40 40 45
73 73 102 124 149 149 180
16 20 25 26 44 44 46
30 30 44 50 70 70 100
WENL, WENR Weldless Eye Nut All Sizes
Max Load (KN) 5.0 10.0 15.0 23.0 35.0 53.0 73.0
Sheet F29
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 2
SPECIFICATION FOR PIPE SUPPORTS
Support No R-A Rod for Non-Adjustable Hangers
Support No R-B Rod for Adjustable Hangers
Support No R-C Rod for Trapeze Hangers
1
1 1 1700 3000
2000 R.H. Thread
R.H. Thread
R.H. Thread
L.H. Thread 300
D
2 D
D Pipe Sup't Sling Rod Mark No Dia D No 1 R-12A 12 R-16A 16 R.H. R-20A 20 Threaded R-24A 24 Rod R-30A 30 Dia = D R-36A 36 42 R-42A
Pipe Sup't Sling Rod Mark No Dia D No 1 R-12B 12 R-16B 16 R.H. R-20B 20 Threaded R-24B 24 Rod R-30B 30 Dia = D R-36B 36 R-42B 42
Length 1700 1700 1700 1700 1700 1700 1700
Length 2000 2000 2000 2000 2000 2000 2000 Mark No 2 L.H. Threaded Rod Dia = D
Mark No 1 Pipe Sup't Sling Rod No Dia D R-24C 24 R.H.Threaded Rod R-36C 36 Dia = D
SUPPORT No SUPPORT TYPE PIPE SIZE
RA, RB, RC Sling Rod All Sizes
Max Load (KN) 5.0 10.0 15.0 23.0 35.0 53.0 73.0 Length 300 300 300 300 300 300 300
Max Load (KN) 5.0 10.0 15.0 23.0 35.0 53.0 73.0
Length 3000 3000
Sheet F30
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 2
SPECIFICATION FOR PIPE SUPPORTS
E A D
H
=
= B
Pipe Sup't No L-12 L-16 L-20 L-24 L-30 L-36 L-42
C
Dia D
A
B
C
E
H
12 16 20 24 30 36 42
65 75 90 115 135 175 200
50 50 80 80 100 130 130
6 6 10 10 12 15 15
40 50 60 80 90 110 130
14 18 22 26 32 39 45
SUPPORT No SUPPORT TYPE PIPE SIZE
L Welding Lug All Sizes
Max Load (KN) 5.0 10.0 15.0 23.0 35.0 53.0 73.0
Sheet F31
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 4
SPECIFICATION FOR PIPE SUPPORTS
D R = 25 A
L
6mm weephole seal with mastic after welding
1
Carbon Steel Pipes Cradle for Standard shoes Long shoes Anchors
Pipe Supt No C1 C2 C3
Mark No 1 (Note 1) 10 thk Carbon Steel plate
Stainless Steel Pipes Cradle for Standard shoes Long shoes Anchors
Pipe Supt No C101 C102 C103
Mark No 1 (Note 1) 10 thk Stainless Steel plate ASTM-A-240 Type 316
Note 1 - For plate MTO see Table 2 Sheet F33 Table 1- Cradle dimensions Pipe size 2" - 10" 12" - 16" 18" - 24" 26" - 40" 42",46"-58",62"-66" 44" 60" 68" 70" 72" - 92"
C1 or C101 L A
C2 or C102 L A
132°
132° 600
400
162° 166°
162° 166° 650
162°
162° 600
C3 or C103 L A 700 800 132° 900 1000 1100 162° 1100 166° 1150 1100 1150 162° 1200
Assembly Tag No: - C1 or C2 or C3 or C101 or C102 or C103 - X Detail No
Pipe Size Dimensions Required: - None
SUPPORT No SUPPORT TYPE PIPE SIZE
C1, C2, C3, C101, C102, C103 Cradle 2" - 92"
Sheet F32
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 4
Table 2- MTO for cradles C1, C2, C3, C101, C102, C103 Pipe Size (") 2 3 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 64 66 68 70 72 76 80 84 88 92
SUPPORT No SUPPORT TYPE PIPE SIZE
D 60 89 114 168 219 273 324 356 406 457 508 559 610 660 711 762 813 864 914 965 1016 1067 1118 1168 1219 1270 1321 1372 1422 1473 1524 1626 1676 1727 1778 1829 1930 2032 2134 2235 2337
Area of plate required (cm²) C1, C101 C2, C102 C3, C103 322 484 564 456 684 798 571 857 1000 820 1230 1435 1055 1582 1846 1304 1956 2282 1539 2308 3077 1684 2526 3368 1918 2877 3837 2152 3228 4843 2386 3579 5369 2620 3931 5896 2854 4282 6422 3088 4633 7721 3322 4984 8306 3556 5335 8891 3790 5686 9476 4025 6037 10061 4259 6388 10646 4493 6739 11231 4727 7090 11816 6088 9132 16742 6375 10360 17532 6662 9994 18322 6950 10424 19112 7237 10855 19901 7524 11286 20691 7811 11717 21481 8099 12148 22271 8386 12579 23061 8673 14094 24935 9247 13871 25430 9535 14302 26220 9822 15960 27010 10109 16427 29063 10396 15594 31189 10971 16456 32912 11545 17318 34635 12119 18179 36358 12694 19041 38082 13268 19903 39805
C1, C2, C3, C101, C102, C103 Cradle (Dimensions) 2" - 92"
Sheet F33
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 2
SPECIFICATION FOR PIPE SUPPORTS
Longitudinal Weld D θ
L 1
6mm weephole (per plate section) seal with mastic after welding
θ is the minimum angle between longitudinal welds at the bottom of the cradle
Carbon Steel Pipes Cradle for Standard shoes Long shoes Anchors
Pipe Supt No C4 C5 C6
Mark No 1 (Note 1) 10 thk Carbon Steel plate
Stainless Steel Pipes Cradle for Standard shoes Long shoes Anchors
Pipe Supt No C104 C105 C106
Mark No 1 (Note 1) 10 thk Stainless Steel plate ASTM-A-240 Type 316
Note 1 - For plate MTO see Table 2 Sheet F35
Table 1- Cradle dimensions Pipe size 2" - 10" 12" - 16" 18" - 24" 26" - 40" 42" - 70" 72" - 92"
C4/C104 L
C5/C105 L
400
600
C6/C106 L 700 800 900 1000 1100 1200
Angle θ (Min)
150º
Assembly Tag No: - C4 or C5 or C6 or C104 or C105 or C106 - X Detail No
Pipe Size Dimensions Required: - None
SUPPORT No SUPPORT TYPE PIPE SIZE
C4, C5, C6, C104, C105, C106 Full encirclement cradle 2" - 92"
Sheet F34
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 2
Table 2- MTO for cradles C4, C5, C6, C104, C105, C106 Pipe Size (") 2 3 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60 64 68 70 72 76 80 84 88 92
SUPPORT No SUPPORT TYPE PIPE SIZE
D 60 89 114 168 219 273 324 356 406 457 508 559 610 660 711 762 813 864 914 965 1016 1067 1118 1168 1219 1270 1321 1372 1422 1473 1524 1626 1727 1778 1829 1930 2032 2134 2235 2337
Area of plate required (cm²) C4, C104 C5, C105 C6, C106 879 1319 1539 1244 1866 2177 1558 2337 2726 2236 3355 3914 2877 4316 5035 3556 5333 7111 4196 6295 8393 4593 6890 9187 5232 7847 10463 5870 8805 13207 6508 9762 14643 7146 10720 16079 7785 11677 17515 8423 12634 21057 9061 13592 22653 9699 14549 24249 10338 15506 25844 10976 16464 27440 11614 17421 29035 12252 18379 30631 12891 19336 32227 13529 20293 37205 14167 21251 38960 14805 22208 40715 15444 23166 42470 16082 24123 44225 16720 25080 45980 17358 26038 47736 17997 26995 49491 18635 27952 51246 19273 28910 53001 20550 30825 56512 21826 32739 60022 22464 33697 61777 23103 34654 69308 24379 36569 73138 25656 38484 76967 26932 40398 80797 28209 42313 84626 29485 44228 88456
C4, C5, C6, C104, C105, C106 Full encirclement cradle (Dimensions) 2" - 92"
Sheet F35
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
L
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 3
10 Max T
D A
Pipe Sup't No
UA101
Pipe Size ½ ¾ 1 1½ 2 3 4
Mark No 1
Insulated U-Bolt Anchor for Stainless Steel Pipes.
A 37 43 50 75 87 115 166
Dimension D L 60 65 8 65 80 80 12 100 110
T 60 60 60 70 70 70 70
Assembly Tag No: - UA101 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
UA101 Insulated U-Bolt Anchor for Stainless Steel pipes ½" - 4"
Sheet F36
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 3
SPECIFICATION FOR PIPE SUPPORTS
L
T
D A
Pipe Sup't No
UG101
Pipe Size ½ ¾ 1 1½ 2 3 4
Mark No 1
Insulated U-Bolt Guide for Stainless Steel Pipes.
A 37 43 50 75 87 115 166
Dimension D L 60 65 8 65 80 80 12 100 110
T 60 60 60 70 70 70 70
Assembly Tag No: - UG101 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
UG101 Insulated U-Bolt Guide for Stainless Steel pipes ½" - 4"
Sheet F37
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 4
SPECIFICATION FOR PIPE SUPPORTS
Plate Thickness = T A
Hole Dia D
H
Dimensions and Shape of Lug to be confirmed by vendor
L
Min Pipe Dimensions (mm) Pipe Wall Thk Maximum A Size (mm) Load (KN) L H Hole dia D 2 1.8 0.5 50 180 22 35 3 1.8 1.0 80 180 22 35 4 2.3 2.0 100 180 22 35 6 3.2 3.0 100 180 22 35 8 4.1 4.0 120 180 22 35 10 4.1 5.0 120 180 22 35 12 4.1 6.0 150 210 26 40 14 4.1 8.0 150 210 33 50 16 3.9 10.0 200 210 33 50 18 3.9 12.0 200 210 39 60 20 4.1 12.0 250 210 39 60 22 - 24 4.1 12.0 250 210 45 70 26 - 30 5.4 20.0 300 210 45 70 32 - 36 5.4 20.0 300 210 45 70 NOTES 1- The lugs shall not be used as permanent pipe supports 2- These loads are based upon the tabulated wall thicknesses. The following equation can be used to increase the actual allowable load: -
Allowable Where: -
load = tabulated
load *
tp tt
T 10 10 10 10 10 10 12 15 15 20 20 20 20 20
1 .5
1 .5
t p is the pipe thickness (less c.a. and tolerances) of the pipe in question t t is the tabulated pipe thickness
Assembly Tag No: - LL1 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
LL1 Lifting Lugs for Piping Break-Out Spools from an elbow 2" - 36"
Sheet F38
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 4
SPECIFICATION FOR PIPE SUPPORTS L
T A
Hole Dia D
B
H
θ R = 25
6mm weephole. Seal with mastic after welding
10 Thk Re-Pad where required Min Pipe Re-pad Pipe Wall Thk Maximum Required Size (mm) Load (KN) (Y/N) 2 1.8 0.5 N 3 1.8 1.0 N 4 2.3 2.0 N 6 3.2 3.0 N 8 4.1 4.0 N 10 4.1 5.0 N 12 4.1 6.0 N 14 4.1 8.0 Y 16 3.9 10.0 Y 18 3.9 12.0 Y 20 4.1 12.0 Y 22 - 24 4.1 15.0 Y 26 - 30 5.4 20.0 Y 32 - 36 5.4 25.0 Y Y 54 10 40.0
Dimensions (mm) L 100 100 100 100 120 120 120 120 120 120 120 120 150 150 200
H 120 120 120 150 150 150 150 150 180 180 180 180 180 180 210
Hole dia D 22 22 22 22 22 22 26 33 33 39 39 45 45 45 63
A 35 35 35 35 35 35 40 50 50 60 60 70 70 70 100
B
250 250 250 250 250 300 300 400
T 10 10 10 10 10 10 12 15 15 20 20 20 20 20 20
θ
90 90 90 90 75 60 60 45
NOTES 1- The lugs shall not be used as permanent pipe supports 2- These loads are based upon the tabulated wall thicknesses. The following equation can be used to increase the actual allowable load: -
Allowable Where: - t
p
load = tabulated
load *
tp tt
1 .5
1 .5
is the pipe thickness (less c.a. and tolerances) of the pipe in question
t t is the tabulated pipe thickness Assembly Tag No: - LL2 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
LL2 Lifting Lugs for Piping Break-Out Spools from pipe All Sizes
Sheet F39
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 1
SPECIFICATION FOR PIPE SUPPORTS
o
45 1
1
50 (min) 45o
50 min
A
The gusset shall not be in the same plane as the pipe nipple and shall be typically welded to the bottom or the side of the pipe
1 Angle between gusset supports One gusset and pipe axis shown shall be View A-A A for clarity approx 45° NOTE- A gusset support for orifice flanges is only required where a pipe nipple has been introduced between the flange and the modular valve
For Stainless Steel Piping, the Gusset shall be formed by 2 flat plates welded together (typ). See below: -
1
40
5 50 (min)
40
450 (max)
NOTES 1- Gusset supports shall be installed in the shop where the branch and header are on the same isometric, otherwise they shall be installed in the field. 2- The gusset length shall be cut and profiled as required to match the o.d. of pipe. Support Mark No 1 Length Support Mark No 1 GSW1 40 x 6 1000 5 Thk Stainless Steel Plate, Grade ASTM-A-240 Angle GSW101 Type 316 or equivalent Assembly Tag No: - GSW1,GSW101
Size 1000 x 40 (2 Off)
Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
GSW1,GSW101 Welded Gusset Support, Carbon & Stainless Steel pipes All Sizes
Sheet F40
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS
2
Do not use on Nipo-flanges. Use welded Gusset type GSW 1
Min
Orientation of the angle to be determined on site Pipe Clip PC1 or PC101 (Ref only) 45o
45o
Pipe Clip PC1 or PC101 (Ref only)
1
Min
2
Orientation of the angle to be determined on site Pipe Clip PC1 or PC101 (Ref only)
1 2
Min
NOTES 1- All gusset supports shall be installed in the field 2- Field to cut length as required and profile gusset to match o.d. of pipe clamp Assembly Tag No: - GSB1,GSB101 - X
Pipe Sup't No GSB1
450 (max) Branch Pipe Size Mark No 1 ¾ 1 40 x 6 1½ Angle ¾ 1 Length 1½ = 1000
GSB101 Size Code Detail No SUPPORT No GSB1,GSB101 SUPPORT TYPE Bolted Gusset Support, Carbon & Stainless Steel pipes All Sizes PIPE SIZE
Mark No 2 UA-¾ UA-1 UA-1½ UA101-¾ UA101-1 UA101-1½
Sheet F41
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 0
SPECIFICATION FOR PIPE SUPPORTS
D R = 25 A
L
6mm weephole seal with mastic after welding
1
Carbon Steel Pipes Cradle for Anchors on sleepers ≤ 600mm Anchors on sleepers > 600mm
Pipe Supt No C7 C8
Mark No 1 (Note 1) 10 thk Carbon Steel plate
Stainless Steel Pipes Cradle for Anchors on sleepers ≤ 600mm Anchors on sleepers > 600mm
Pipe size 2" - 4" 6" - 16" 18" - 24" 26" - 40"
Pipe size 2" - 4" 6" - 16"
Pipe Supt No C107 C108
Mark No 1 (Note 1) 10 thk Stainless Steel Plate ASTM-A-240 Type 316
Pipe Size (")
D
2 3 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40
60 89 114 168 219 273 324 356 406 457 508 559 610 660 711 762 813 864 914 965 1016
C7or C107 L A 1000 1100 132° 1200 1300
C8 or C108 L A 1400 132° 1500
Area of plate required (cm²) C7, C107 C8, C108 806 1129 1140 1596 1428 1999 2255 3075 2901 3956 3585 4889 4231 5770 4632 6316 5275 7194 6457 7159 7861 8563 10037 10798 11558 12319 13080 13840 14601 15361
Assembly Tag No: - C7 or C8 or C107 or C108 - X Detail No
Pipe Size Dimensions Required: - None
SUPPORT No SUPPORT TYPE PIPE SIZE
C7, C8, C107, C108 Cradle for Anchors on Concrete Sleepers 2" - 40"
Sheet F42
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS
E
Thickness T D
X
= =
2 lugs required for rods 80mm and larger
C
Hole Dia H
Pipe
X
CL
Radius R A
View X-X
1 10mm Continuous Fillet Weld
Thickness T
Pipe
CL
Notch around weld. Radius = 25mm
View X-X
Pipe Size No of Lugs Thickness T 48" 1 25 60" 1 25
Pipe Size 48" 60"
Mark No 1 25 Thk Plate 25 Thk Plate
Radius R 110 95
Hole Dia H 68 50
A 520 463
Dimensions C D 220 410 178 300
E N/A N/A
Dims 520 x 410 465 x 300
Assembly Tag No: - LL1 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
LL1 Lifting Lugs for Piping Break-Out Spools from an elbow 48" - 92"
Sheet F43
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS L
T
1
Hole Dia D
A B
2
H
θ R = 25
6mm weephole. Seal with mastic after welding
10 Thk Re-Pad where required Pipe Size 2 3 4 6 8 10 12 14 16 18 20 22 - 24 26 - 30 32 - 36
Min Pipe Re-pad Wall Thk Maximum Required (mm) Load (KN) (Y/N) 1.8 0.5 N 1.8 1.0 N 2.3 2.0 N 3.2 3.0 N 4.1 4.0 N 4.1 5.0 N 4.1 6.0 Y 4.1 8.0 Y 3.9 10.0 Y 3.9 12.0 Y 4.1 12.0 Y 4.1 15.0 Y 5.4 20.0 Y 5.4 25.0 Y
Dimensions (mm) L 100 100 100 100 120 120 120 120 120 120 120 120 150 150
H 120 120 120 150 150 150 150 150 180 180 180 180 180 180
Hole dia D 22 22 22 22 22 22 26 33 33 39 39 45 45 45
A 35 35 35 35 35 35 40 50 50 60 60 70 70 70
B
250 250 250 250 250 250 300 300
T 10 10 10 10 10 10 12 15 15 20 20 20 20 20
θ
90 90 90 90 90 75 60 60
Mark No 1 Dimension Mark No 2 Dimension Pipe Size 10 Thk Stainless Steel Plate 100 x 120 2-4 ASTM-A-240 Type 316 100 x 150 6 or equivalent 120 x 150 8 - 10 12 Thk Carbon Steel Plate 120 x 150 250 x 250 12 15 Thk Carbon Steel Plate 120 x 150 250 x 280 14 15 Thk Carbon Steel Plate 250 x 320 16 250 x 360 18 120 x 180 10 Thk Stainless 250 x 400 20 Steel Plate 250 x 370 22 ASTM-A-240 250 x 400 24 20 Thk Carbon Steel Plate Type 316 300 x 350 26 or equivalent 300 x 370 28 150 x 180 300 x 400 30 300 x 425 32 300 x 450 34 300 x 480 36 NOTES - 1- The lugs shall not be used as permanent pipe supports 2- These loads are based upon the tabulated wall thicknesses. The following equation can be used to increase the actual allowable load: -
Allowable load = tabulated load *
tp tt
1 .5
1 .5
Where: - t p is the pipe thickness (less c.a. and tolerances) of the pipe in question t t is the tabulated pipe thickness Assembly Tag No: - LL102 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
LL102 Lifting Lugs for Piping Break-Out Spools from Stainless Steel pipe All Sizes
Sheet F44
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 0 1
X
X
5
L T
10 Max
3
D
10 Dia Hole in Existing Steel
C 2
Monel Backing Plate
= 40 =
View X-X 20
Pipe Size ½ ¾ 1 1½ 2
75
Dimension D L 44 47 8 50 57 63
C 31 37 44 58 70
T
43
Pipe Pipe Mark No 1 Developed Mark No 2 Mark No 3 Size O.D. Length (4 Off) ½ 21 8 dia 137 ¾ 27 Round 152 5 Thk 1 34 Monel 169 M 8 Nut Monel 1½ 48 Bar 205 plate 2 60 236 Assembly Tag No: - UG301 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Area 2 (cm )
30
Pipe Size
UG301 U-Bolt Guide for pipes in the Caustic Sump ½" - 2"
Sheet F45
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev 0 1
X
X 5
L
10 Max
T 3 10 Dia Hole in Existing Steel
D C
2
Monel Backing Plate
= 40 =
View X-X 20
Pipe Size ½ ¾ 1 1½ 2
75
Dimension D L 49 52 8 55 62 68
C 29 35 42 56 68
T
35
Pipe Pipe Mark No 1 Developed Mark No 2 Mark No 3 Size O.D. Length (4 Off) ½ 21 8 dia 144 ¾ 27 Round 159 5 Thk 1 34 Monel 176 M 8 Nut Monel 1½ 48 Bar 212 plate 2 60 243 Assembly Tag No: - UA301 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Area 2 (cm )
30
Pipe Size
UA301 U-Bolt Anchor for pipes in the Caustic Sump ½" - 2"
Sheet F46
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS Pipe Support No SB301 - Guide
Pipe Support No SB302 - Anchor
X
X 1
1
3
3
500
X Baseplate shall rest on floor of Caustic Sump
2
X 30 30
10mm Wide Slotted Hole = 30
400 View X-X
=
=
NOTEMark Nos 1 & 2 (base plate and angle) shall be painted with an epoxy paint System AD
= 400
Pipe Sup't No SB301
Pipe Size (") ¾
SB302
¾
Mark No 1
Length
Mark No 2
50 x 6 Angle 50 x 6 Angle
500
12 Thk Plate 12 Thk Plate
500
Area (cm²) 1600 1600
Mark No 3
Size
Monel U-Bolt UG301-¾ Guide Monel U-Bolt UA301-¾ Anchor
Assembly Tag No: - SB301 or SB302 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
SB301, SB302 Base Guide/Anchor Pipes in Caustic Sump ¾"
Sheet F47
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS X
1
3
500 Baseplate shall rest on floor of Caustic Sump
X 2
30 30
10mm Wide Slotted Hole
Field Weld
= 30
400 View X-X
=
113
=
NOTEMark Nos 1 & 2 (base plate and angle) shall be painted with an epoxy paint System AD
=
500
Pipe Sup't No SB303
Pipe Size (") ¾
Mark No 1
Length
Mark No 2
50 x 6 Angle
1000
12 Thk Plate
Area (cm²) 2000
Mark No 3 Size (2 Off) Monel U-Bolt UG301-¾ Guide
Assembly Tag No: - SB303 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
SB303 Base Guide for 2 pipes in Caustic Sump ¾"
Sheet F48
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS
50 min A
Bolt Angle into one of the four existing holes in the flange body. A washer is required either side of the angle
Angle between gusset supports and pipe axis shall be approx 45°
2 3
1 A
SP-1914 or SP-1916
View A-A
One gusset shown for clarity
Field Welds
NOTES 1- The gusset length shall be cut and profiled as required to match the o.d. of pipe.
Support GSW2
Mark No 1 40 x 6 Angle
Length 1000
Mark No 2 M10 Bolt
Length 30
Mark No 3 M10 Washers
No Off 2
Assembly Tag No: - GSW2 Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
GSW2 Gusset Support for SP Item Nos. SP-1914 & SP-1916 All Sizes
Sheet F49
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS
4-M20 threaded rod with Hilti HY150 resin capsule adhesive. (Hilti HIT-ICE resin to be used if the 2 installation temperature is below -5°C) Max length = 620, Dimension to be confirmed at site. Varies due to paving sloping. NOTE 1
Pipe Support Section HEA 100 field welded to 20 thk. Plate. 30 Grout (Type G1)
Plinth cast on paving by piping contractor. 5
3 M20 Nuts
150
50
U/S of Plate EL. 100,200
100 140
2 layers of A393 Structural mesh
200 Slab. C25 Paving
PVC Sheet 6 NOTE 1
60 (Typ)
Controlled frost free graded granular fill (type 1) compacted in 200mm layers to spec. (90% max.dry density) 60 (Typ)
ELEVATION
7
1
100 100
20 Thick Plate
B
A
100 4
100
24 Dia holes in each corner of the plate (4 off)
A PLAN
2 - 8 dia. stirrups
B
NOTES 1- Refer to Section 10 of this Spec for a procedure for the installation of bolts, grouting and monitoring the settlement of the paving 2- For General Notes refer to Drawing Nos. 60-0000-Q-STD-0010-01 and 02
Support F8N-1 Mark No 1 20 Thk Plate
Dimensions (mm) A B 320 400 Area (cm2) 1025
Mark No 2 20 Dia Bar Threaded
Assembly Tag No: - F8N-1 SUPPORT No SUPPORT TYPE PIPE SIZE
Vertical (KN) 20.0 Total Length 2500
Allowable Loads Bending Moment (KNm) 4.0
Mark No 3 Mark No 4 (8 Off) M20 Nut 8 Dia Bar Mark No 6 Cementitious Grout (G1) 0.01m3
F8N-1 Pipe Support foundation for New Paving All Sizes
Total Length 2000
Mark No 5 (8 Off) M20 Washers
Mark No 7 Structural Concrete Grade (K25AE) 0.05m3 Sheet G1
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS Pipe Support Section HEA 160 or HEA 200 field welded to 20 thk. Plate. 30 Grout (Type G1)
Plinth cast on paving by piping contractor.
2
3
150
30
6
4-M20 threaded rod with Hilti HY150 resin capsule adhesive. (Hilti HIT-ICE resin to be used if the installation temperature is below -5°C) (Max length = 620, Dimension to be confirmed at site. Varies due to paving sloping).NOTE 1 M20 Nuts 50
U/S of Plate EL. 100,200
100 140
2 layers of A393 Structural mesh PVC Sheet
ELEVATION
60 (Typ) =
7 NOTE 1 8 4 4-16 dia. threaded rod x 140 projection with Hilti HY150 capsule adhesive. (Max length = 400, Dimension to be confirmed at site. Varies due to paving sloping).
=
=
A
B
1
20 Thick Plate
5
2 - 8 dia. stirrups
24 Dia holes in each corner of the plate (4 off)
=
60 (Typ)
Controlled frost free graded granular fill (type 1) compacted in 200mm layers to spec. (90% max.dry density)
200 Slab. C25 Paving
A
PLAN
B
NOTES 1- Refer to Section 10 of this Spec for a procedure for the installation of bolts, grouting and monitoring the settlement of the paving 2- For General Notes refer to Drawing Nos. 60-0000-Q-STD-0010-01 and 02 Support F8N-2 Mark No 1 20 Thk Plate
Dimensions (mm) A B 500 600 Area (cm2) 2500
Mark No 2 20 Dia Bar Threaded
Assembly Tag No: - F8N-2 SUPPORT No SUPPORT TYPE PIPE SIZE
Vertical (KN) 25.0 Total Length 2500
Allowable Loads Bending Moment (KNm) 8.0
Mark No 3 Mark No 4 Total (8 Off) Length M20 Nut 16 Dia Bar 1600 Threaded Mark No 7 Mark No 6 M20 Cementitious Grout Washers (G1) 0.01m3 (8 Off)
F8N-2 Pipe Support foundation for New Paving All Sizes
Mark No 5 8 Dia Bar
Total Length 6000
Mark No 8 Structural Concrete Grade (K25AE) 0.12m3 Sheet G2
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
Maximum Applied Vertical Load 'P' (KN)
SPECIFICATION FOR PIPE SUPPORTS 30 25
20
10
0 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Maximum Applied Moment 'M' (KNm) F8N-1 (200 thk. paving x 400 sq. pier) F8N-2 (200 thk. paving x 600 sq. pier)
F8N-1 x 400 sq. F8N-2 x 600 sq.
F8N-2 x 200 thk.
'M'
F8N-1 x 200 thk.
'P'
Effective paving length = 2.0m 2
Effective paving area = 4.0m
CRITERIA ASSUMED 2 1- The allowable vertical loads are based upon an effective paving area of 4.0m , which equates to a distance between the piers of 2.0m. If the distance between the piers is less than 2.0m the allowable loads shall be reduced in proportion to the effective pier area. Example- Distance between piers = 1.5m 2 2 Allowable load shall be 1.5 /2.0 = 0.56 x load in graph 2 2- Allowable ground bearing pressure of 50KN/m 3- The face of the pier shall be 1.0m minimum away from the edge of the slab. 4- The concrete grade shall be at least 25N/mm2 5- There are 2 layers of mesh fabric grade A393 in the paving 6- All slab joints are dowelled SUPPORT No F8N-1, F8N-2 SUPPORT TYPE Pipe Support Foundation Loading Graph for F8N-1, F8N-2 Sheet G3 PIPE SIZE All Sizes
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS 100 (typ)
400 140
SUPPORT SHALL BE USED FOR THE SGI PROJECT ONLY
140
1
140 400
24dia holes (4 off)
140
PLAN
Pipe Support Section Size HEA 100 or smaller 3
Trim post and site weld to plate
2
30
U/S EL 100,200
75
25
4 Grade EL 100,000 50
75 cover
100 300 bar embedment
50 5
75 cover
Concrete Infill
6 dia helix @ 200 pitch
6 A
7
A
ELEVATION
450 dia Augered Pile 25 Grade Concrete
75 cover
NOTES: 1- When the auger is located on a piling mat or pile cap it shall not penetrate the surface of them. The approximate depth of the auger will be 2000mm where there is a piling mat and 1200mm where there is a pile cap.
Assembly Tag No: - F9-1 SUPPORT No SUPPORT TYPE PIPE SIZE
3000 (Note 1)
450 Dia
75 cover
F9-1 Augered Pile, Pipe Support Foundation for welded posts in non-paved areas (HEA 100) All
SECTION A-A Sheet G4
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS
SUPPORT SHALL BE USED FOR THE SGI PROJECT ONLY Allowable loads Bending Vertical Moment (KN) (KNm) 25.0 4.0
Mark No 1 20 Thk Plate
Area (cm2) 1600
Mark No 6 (Note 1) 20 dia rebar
Mark No 2
Minimum allowable distance between augers Auger diameters Distance (mm) (mm) 450 - 450 1500
Length (4 Off)
20 dia threaded rod
400
Length (6 Off) 3200
Total Length 19200
Mark No 3 Mark No 4 Mark No 5 (4 Off) (12 Off) 20 dia 20 dia 12 dia Washers Nuts rebar
Mark No 7 (Note 1) 6 dia helix
Total Length 10500
Total Length 15000
NOTES: 1- MTO is based upon a auger length of 3000mm
Assembly Tag No: - F9-1 SUPPORT No SUPPORT TYPE PIPE SIZE
F9-1 Augered Pile, Pipe Support Foundation for welded posts in non-paved areas (HEA 100)(dim'ns) All
Sheet G5
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS 100 (typ)
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
500 190
SUPPORT SHALL BE USED FOR THE SGI PROJECT ONLY
190
190
1
190
24dia holes (4 off)
500
PLAN
Pipe Support Section Size HEA 160 or HEA 200 3
Trim post and site weld to plate
2
30
U/S EL 100,200 25
4 Grade EL 100,000
75 cover
75
100 300 bar embedment
50
5
75 cover
Concrete Infill
6 dia helix @ 200 pitch
6 A
7
A
3000 (Note 1)
ELEVATION
450 dia Augered Pile 25 Grade Concrete
75 cover NOTES: 1- When the auger is located on a piling mat or pile cap it shall not penetrate the surface of them. The approximate depth of the auger will be 2000mm where there is a piling mat and 1200mm where there is a pile cap.
Assembly Tag No: - F9-2 SUPPORT No SUPPORT TYPE PIPE SIZE
450 Dia
75 cover
F9-2 Augered Pile, Pipe Support Foundation for welded posts in non-paved areas (HEA160 or HEA200) All
SECTION A-A Sheet G6
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS
SUPPORT SHALL BE USED FOR THE SGI PROJECT ONLY Allowable loads Bending Vertical Moment (KN) (KNm) 25.0 4.0
Mark No 1 20 Thk Plate
Area (cm2) 2500
Mark No 2 20 dia threaded rod Mark No 6 (Note 1) 20 dia rebar
Minimum allowable distance between augers Auger diameters Distance (mm) (mm) 450 - 450 1500
Length (4 Off) 400
Length (6 Off) 3200
Mark No 3 Mark No 4 Mark No 5 (4 Off) (12 Off) 20 dia 20 dia 12 dia Washers Nuts rebar
Total Length 19200
Mark No 7 (Note 1) 6 dia helix
Total Length 12500
Total Length 15000
NOTES: 1- MTO is based upon a auger length of 3000mm
Assembly Tag No: - F9-2 SUPPORT No SUPPORT TYPE PIPE SIZE
F9-2 Augered Pile, Pipe Support Foundation for welded posts in non-paved areas (HEA160 or HEA200)(dim'ns) All
Sheet G7
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS 100 (typ)
500 190
SUPPORT SHALL BE USED FOR THE SGI PROJECT ONLY
190
190
1
500
24dia holes (4 off)
190
PLAN Existing BS2 or BS4
U/S EL 100,200 75
25
2 Grade EL 100,000
300 bar embedment
75 cover
3
100
50
4
75 cover
Concrete Infill
6 dia helix @ 200 pitch
5
A
A
6
3000 (Note 1)
ELEVATION 450 dia Augered Pile 25 Grade Concrete 75 cover NOTES: 1- When the auger is located on a piling mat or pile cap it shall not penetrate the surface of them. The approximate depth of the auger will be 2000mm where there is a piling mat and 1200mm where there is a pile cap.
450 Dia
75 Assembly Tag No: - F9-4 SUPPORT No SUPPORT TYPE PIPE SIZE
cover
F9-4 Augered Pile, Pipe Support Foundation for base supports in non-paved areas (Trunnion ≤ 6") All
SECTION A-A Sheet G8
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS
SUPPORT SHALL BE USED FOR THE SGI PROJECT ONLY Minimum allowable distance between augers Auger diameters Distance (mm) (mm) 450 - 450 1500
Allowable loads Vertical Shear (KN) (KN) 25.0 5.0
Mark No 1 20 Thk Plate
Area (cm2) 2500
Mark No 4 Mark No 5 (4 Off) (Note 1) 20 dia 20 dia Nuts rebar
Mark No 2
Length (4 Off)
20 dia threaded rod
350
Length (6 Off) 3200
Total Length 19200
Mark No 3 12 dia rebar
Mark No 6 (Note 1) 6 dia helix
Total Length 12500
Total Length 15000
NOTES: 1- MTO is based upon a auger length of 3000mm
Assembly Tag No: - F9-4 SUPPORT No SUPPORT TYPE PIPE SIZE
F9-4 Augered Pile, Pipe Support Foundation for base supports in non-paved areas (Trunnion ≤ 6")(dim'ns) All
Sheet G9
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS 100 (typ)
700 140
GENERAL REVISION
140
1 140 700 140
PLAN Existing BS2 or BS4
U/S EL 100,200 25
2 Grade EL 100,000
75 cover
3
75
100 300 bar embedment
50
4
75 cover
Concrete Infill
6 dia helix @ 200 pitch
5 A
6
3000 (Note 1)
A
ELEVATION
450 dia Augered Pile 25 Grade Concrete
75 cover NOTES: 1- When the auger is located on a piling mat or pile cap it shall not penetrate the surface of them. The approximate depth of the auger will be 2000mm where there is a piling mat and 1200mm where there is a pile cap.
450 Dia
75 Assembly Tag No: - F9-5 SUPPORT No SUPPORT TYPE PIPE SIZE
cover
F9-5 Augered Pile, Pipe Support Foundation for base supports in non-paved areas (Trunnion ≥8") All
SECTION A-A Sheet G10
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
GENERAL REVISION Minimum allowable distance between augers Auger diameters Distance (mm) (mm) 450 - 450 1500
Allowable loads Vertical Shear (KN) (KN) 25.0 5.0
Mark No 1 20 Thk Plate
Area (cm2) 4900
Mark No 4 Mark No 5 (4 Off) (Note 1) 20 dia 20 dia Nuts rebar
Mark No 2
Length (4 Off)
20 dia threaded rod
350
Length (6 Off) 3200
Total Length 19200
Mark No 3
Total Length
12 dia rebar
Mark No 6 (Note 1) 6 dia helix
16000
Total Length 15000
NOTES: 1- MTO is based upon a auger length of 3000mm
Assembly Tag No: - F9-5 SUPPORT No SUPPORT TYPE PIPE SIZE
F9-5 Augered Pile, Pipe Support Foundation for base supports in non-paved areas (Trunnion ≥8") All
Sheet G11
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 4
SPECIFICATION FOR PIPE SUPPORTS
Existing piled foundation by civil contractor or pipe support foundation.
2
Levelling nut
Grout (Note 1) (Type G1)
Existing Trunnion Support No BS5 or BS2
4 threaded rods with Hilti HY150 resin capsule adhesive. (Hilti HIT-ICE resin to be used if the installation temperature is below -5°C) NOTE 1 3 Nuts (8 Off) Washers (8 Off)
4
U/S of Plate EL. 100,200 5
Paving or Grade Use 24dia drill bit for 20dia bolts. Use 35dia drill bit for 30dia bolts.
L C
ELEVATION
20 dia grout holes (2 off) NOTE - Only required for base plates 800 x 800 or larger
A
B
60 (Typ)
Note 1- Grout thickness = 25mm for baseplates smaller than 500 x 500. Grout thickness = 40mm for baseplates 500 x 500 and larger. 60 (Typ) 1
125 Bolt Holes in each corner of the plate dia = D (4 off) A
PLAN
B NOTE 1- Refer to Section 10 of this Spec for a procedure for the installation of bolts, grouting and monitoring the settlement of the paving 2- For General Notes refer to Drawing Nos. 60-0000-Q-STD-0010-01 and 02 Dimensions (mm) Trunnion Max Axial Foundation reference Size C L dia D Load (KN) (if required) A B F9-6 2, 3 310 25.0 420 600 F9-7 4, 6 175 325 24 550 750 F9-8 8, 10, 12 50.0 700 900 Foundation to be 16, 18, 20 850 1050 280 460 34 100.0 24 designed by Civils 950 1150 Trunnion Mark No 1 Area Mark No 2 Length Mark No 3 Size (cm2) 2, 3 20 Thk 1764 20 Dia Bar 310(4 Off) M20 Nut Plate 3025 Threaded 325(4 Off) (8 Off) 4, 6 8, 10, 12 4900 16, 18, 20 25 Thk 7225 30 Dia Bar 460(4 Off) M30 Nut 24 Plate 9025 Threaded (8 Off) Assembly Tag No: -F8N3 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Mark No 4
Mark No 5
(8Off) M20 Washers
Cementitious Grout (G1) 0.02m3
(8Off) M30 Washers
Cementitious Grout (G1) 0.03m3
Trunnion Size
F8N3 Pipe Support baseplate on a civil foundation or pipe support foundation No F9-6, F9-7 or F9-8 All Sizes
Sheet G12
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
Existing piled foundation by civil contractor.
2
Levelling nut
25 Thk Grout (Type G1)
Existing Post
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3 4 threaded rods with Hilti HY150 resin capsule adhesive. (Hilti HIT-ICE resin to be used if the installation temperature is below -5°C) NOTE 1 3 Nuts (8 Off) Washers (4 Off)
4
U/S of Plate EL. 200 above Local Grade 5
Local Grade Use 24dia drill bit for 20dia bolts.
ELEVATION
60 (Typ)
60 (Typ)
L C 1
A
B
NOTE 1
Bolt Holes in each corner of the plate dia = D (4 off) A
PLAN
B
NOTE 1- Refer to Section 10 of this Spec for a procedure for the installation of bolts, grouting and monitoring the settlement of the paving 2- For General Notes refer to Drawing Nos. 60-0000-Q-STD-0010-01 and 02 Pipe support Dimensions (mm) Size Section Code C L dia D A B 70 Angle A 175 300 24 250 450 HEA 100 B 175 300 24 320 500 175 300 34 C HEA 160 or HEA 200 400 600 Size Code A B C
Pipe support Section 70 Angle 70 Angle or HEA 100 HEA 160 or HEA 200
Vertical (KN) 5.0 25.0 50.0
Allowable Loads Bending Moment (KNm) Negligible 4.0 8.0
Shear Foundation reference (KN) (if required) Negligible F9-10 2.0 F9-6 4.0 F9-9
Size Mark No 1 Area Mark No 2 Length Mark No 3 Mark No 4 (4 Off) Code (cm2) A 625 M20 20 Thk 20 Dia Bar 300(4 Off) M20 Nut Plate Threaded 300(4 Off) (8 Off) B 1024 Washers C 1600 300(4 Off) Assembly Tag No: -F8N4 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Mark No 5 Cementitious Grout (G1) 0.01m3
Size Code
F8N4 Pipe Support baseplate on a civil foundation or pipe support foundation No F9-6, F9-9 or F9-10 All Sizes
Sheet G13
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Ref Trunnion 2" or 3" or Post size HEA100 40 Grout
Ref F8-N3 or F8-N4 Size Code B
160
EL Local Grade 450 X
900
4
X
Bitumen Coating (Typical)
100
2 1
3 300
5
300
K25AE Mass Concrete
200
1400 Square
200
4
1000g 0.25mm Thk Polythene Sheeting
2 Pipe CL Support
3
75 Cover (Typ) Pipe Support on Foundation F9-6
600 Square
Section X-X CL Pipe Support Allowable Loads Bending Moment (KNm) 4.0 2.0 7.5
Axial (KN) Shear (KN)
25.0 25.0
Welded Post HEA100
Trunnion 2" or 3" Mark No
Material
1 2 3 4 (Note 2)
16 dia Rebar Type AIII 16 dia Rebar Type AIII 10 dia Rebar Type AIII 12 dia Rebar Type AIII
No of Bars Length of Each Bar 12 (6 E-W) 1225 8 1600 6 1900 4 1250
Shape Code 20 37 61 39
Dimensions A B 1225 1185 440 440 600 100
Material Take Off - Reinforcement Only AIII - 16 AIII - 12 AIII - 10 Bar Type - Size 28 5 12 Total Length (m) 45 5 8 Weight (kg) Mark No
Material
Quantity Matman Code 2.0 m3 1011651 4.4 m2 1060510 1070510 9 Litres NOTES: 1- For General Notes refer to Drawing Nos. 600000-Q-STD-0010-01 and 02 2- Optional lifting lugs for Precast Base
Structural Concrete Grade (K25AE)
5 Polythene Sheeting Bitumen Emulsion Found'n Assembly Tag No: -F9-6 Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
F9-6 Pipe Support foundation for non paved areas for 2" & 3" trunnions and welded posts HEA 100 All Sizes
Sheet G14
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Ref Trunnion 4" or 6" 40 Grout
Ref F8-N3
160
EL Local Grade 450 X
900
X
4
Bitumen Coating (Typical)
100
2
1
3 300
300
5
K25AE Mass Concrete
200
1400 Square
200 1000g 0.25mm Thk Polythene Sheeting
4 2 Pipe CL Support
3
75 Cover (Typ) Pipe Support on Foundation F9-7 Trunnion 4" or 6"
750 Square
Section X-X CL Pipe Support Allowable Loads Bending Moment (KNm) 7.5
Axial (KN) Shear (KN)
25.0
Mark No
Material
1 2 3 4
16 dia Rebar Type AIII 16 dia Rebar Type AIII 10 dia Rebar Type AIII 16 dia Rebar Type AIII
No of Bars Length of Each Bar 16 (8 E-W) 1225 12 1600 6 2500 4 1575
Shape Code 20 37 61 39
Dimensions A B 1225 1185 590 590 750 130
Material Take Off - Reinforcement Only AIII - 16 AIII - 10 Bar Type - Size 46 15 Total Length (m) 73 10 Weight (kg) Mark No
Quantity Matman Code 2.8 m3 1011651 5.3 m2 1060510 5 Polythene Sheeting Bitumen Emulsion 1070510 Found'n 11 Litres NOTES: 1- For General Notes refer to Drawing Nos. 60Assembly Tag No: -F9-7 0000-Q-STD-0010-01 and 02 Detail No 2- Optional lifting lugs for Precast Base SUPPORT No F9-7 Pipe Support foundation for non paved areas for SUPPORT TYPE Sheet G15 4" & 6" trunnions PIPE SIZE All Sizes Material
Structural Concrete Grade (K25AE)
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Ref Trunnion 8",10" or 12" 40 Grout
Ref F8-N3
160
EL Local Grade 450 X
900
4
X Bitumen Coating (Typical)
100
2
1
3 300
300
5
K25AE Mass Concrete
1600 Square
200
200
4
1000g 0.25mm Thk Polythene Sheeting
2 Pipe CL Support
3
75 Cover (Typ)
900 Square
Section X-X CL Pipe Support
Pipe Support on Allowable Loads Axial (KN) Shear (KN) Bending Moment (KNm) Foundation F9-8 Trunnion 8",10" or 12" 50.0 15.0 Mark No
Material
1 2 3 4
16 dia Rebar Type AIII 16 dia Rebar Type AIII 10 dia Rebar Type AIII 16 dia Rebar Type AIII
No of Bars Length of Each Bar 16 (8 E-W) 1425 12 1600 6 3100 4 1575
Shape Code 20 37 61 39
Dimensions A B 1425 1185 740 740 750 130
Material Take Off - Reinforcement Only AIII - 16 AIII - 10 Bar Type - Size 49 19 Total Length (m) 75 12 Weight (kg) Mark No
Material
Quantity Matman Code 2.8 m3 1011651 5.3 m2 1060510 1070510 16 Litres NOTES: 1- For General Notes refer to Drawing Nos. 600000-Q-STD-0010-01 and 02 2- Optional lifting lugs for Precast Base
Structural Concrete Grade (K25AE)
5 Polythene Sheeting Bitumen Emulsion Found'n Assembly Tag No: -F9-8 Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
F9-8 Pipe Support foundation for non paved areas for 8",10" & 12" trunnions All Sizes
Sheet G16
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Ref Post size HEA160 or HEA200 40 Grout
Ref F8-N4 Size Code C
160
EL Local Grade 450 X
900
4
X
Bitumen Coating (Typical)
100
2
1
3 300
5 300 K25AE Mass Concrete
1600 Square
200
200
4
1000g 0.25mm Thk Polythene Sheeting
2 Pipe CL Support
3
75 Cover (Typ) Pipe Support on Foundation F9-9
600 Square
Section X-X CL Pipe Support Allowable Loads Bending Moment (KNm)
Axial (KN) Shear (KN)
Welded Post HEA160
50.0
or HEA 200 Mark No
Material
1 2 3 4
16 dia Rebar Type AIII 16 dia Rebar Type AIII 10 dia Rebar Type AIII 12 dia Rebar Type AIII
4.0
8.0
No of Bars Length of Each Bar 16 (8 E-W) 1425 8 1600 6 1900 4 1250
Shape Code 20 37 61 39
Dimensions A B 1425 1185 440 440 600 100
Material Take Off - Reinforcement Only AIII - 16 AIII - 12 AIII - 10 Bar Type - Size 36 5 12 Total Length (m) 57 5 8 Weight (kg) Mark No
Material
Quantity Matman Code 2.5 m3 1011651 5.3 m2 1060510 1070510 11 Litres NOTES: 1- For General Notes refer to Drawing Nos. 600000-Q-STD-0010-01 and 02 2- Optional lifting lugs for Precast Base
Structural Concrete Grade (K25AE)
5 Polythene Sheeting Bitumen Emulsion (Found'n) Assembly Tag No: -F9-9 Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
F9-9 Pipe Support foundation for non paved areas for welded posts HEA 160 & HEA 200 All Sizes
Sheet G17
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Ref Small Bore Pipe Support or Post size 70 x 8 Angle 40 Grout
Ref F8-N4 Size Code A
160
EL Local Grade 450 X
1200
X
3
100
1
Bitumen Coating (Typical)
2
300
4
K25AE Mass Concrete
800 Square 1000g 0.25mm Thk Polythene Sheeting
2 3 Pipe CL Support
1
75 Cover (Typ) Pipe Support on Foundation F9-10
Section X-X CL Pipe Support
1 2 3
Allowable Loads Bending Moment (KNm) -
Axial (KN) Shear (KN)
5.0
Post 70 x 8 Angle
Mark No
450 Square
-
Material
No of Bars Length of Each Bar 8 1175 16 dia Rebar Type AIII 7 1300 10 dia Rebar Type AIII 4 1250 12 dia Rebar Type AIII
Shape Code 20 61 39
Dimensions A B 1175 290 290 600 100
Material Take Off - Reinforcement Only AIII - 16 AIII - 12 AIII - 10 Bar Type - Size 10 5 10 Total Length (m) 16 5 7 Weight (kg) Mark No
Material
Quantity Matman Code 0.5 m3 1011651 1.2 m2 1060510 1070510 7.7 Litres NOTES: 1- For General Notes refer to Drawing Nos. 600000-Q-STD-0010-01 and 02 2- Optional lifting lugs for Precast Base
Structural Concrete Grade (K25AE)
4 Polythene Sheeting Found'n Bitumen Emulsion Assembly Tag No: -F9-10 Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
F9-10 Pipe Support foundation for non paved areas for Small Bore Pipe Supports and 70 x 8 Angle Posts ½" - 2"
Sheet G18
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
B.O.P.
See Note 2
See Note 2
B.O.P.
Pipe Size 3/4" - 3"
Pipe Size 4" - 24"
300 = Support Type CS1-A CS1-B CS1-C CS1-D CS1-E CS1-F CS1-G CS1-H CS1-J
Pipe Size 3/4" - 24" =
Insulation Thickness (mm) 30 40 50 60 70 80 90 100 110
NOTE 1, For details of Cold Shoes see Specification No. 60-0000-L-SPE-1003. 2, For shoe height see Document No. 60-0000-L-SPE-0002.
Assembly Tag No: - CS1 - X - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
CS1 Cold Shoe, Standard Length 3/4" - 24"
Sheet H1
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
B.O.P.
See Note 2
See Note 2
B.O.P.
Pipe Size 3/4" - 3"
Pipe Size 4" - 24"
500 = Support Type CS2-A CS2-B CS2-C CS2-D CS2-E CS2-F CS2-G CS2-H CS2-J
Pipe Size 3/4" - 24" =
Insulation Thickness (mm) 30 40 50 60 70 80 90 100 110
NOTE 1, For details of Cold Shoes see Specification No. 60-0000-L-SPE-1003. 2, For shoe height see Document No. 60-0000-L-SPE-0002.
Assembly Tag No: - CS2 - X - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
CS2 Cold Shoe, Long 3/4" - 24"
Sheet H2
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
See Note 2 (Typ.)
B.O.P.
Pipe Size 8" - 24"
Support Type CS3-A CS3-B CS3-C CS3-D CS3-E CS3-F CS3-G CS3-H CS3-J
Insulation Thickness (mm) 30 40 50 60 70 80 90 100 110
300 =
=
Pipe Size 8" - 24"
NOTE 1, For details of Cold Shoes see Specification No. 60-0000-L-SPE-1003. 2, For shoe height see Document No. 60-0000-L-SPE-0002.
Assembly Tag No: - CS3 - X - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
CS3 Cold Double Shoe, Standard Length 8" - 24"
Sheet H3
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
B.O.P.
See Note 2
See Note 2
B.O.P.
Pipe Size 3/4" - 3"
Pipe Size 4" - 24"
Pipe Size 3/4" - 24" = Support Type CAS1-A CAS1-B CAS1-C CAS1-D CAS1-E CAS1-F CAS1-G CAS1-H CAS1-J
Insulation Thickness (mm) 30 40 50 60 70 80 90 100 110
L
= Pipe Dimension Size L 3/4" - 10" 600 12" - 24" 800
NOTE 1, For details of Cold Anchor Shoes see Specification No. 60-0000-L-SPE-1003. 2, For shoe height see Document No. 60-0000-L-SPE-0002.
Assembly Tag No: - CAS1 - X - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
CAS1 Anchor Shoe - Cold Insulated Lines 3/4" - 24"
Sheet H4
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
See Note 1
See Note 1
Pipe Size 3/4" - 3"
Do not weld along this face
Pipe Size 4" - 24"
150
100
Do not weld along this face
100
2 Gap (typ)
=
Mark Pipe No. 1 Size 3/4" - 3" 10 Thk.Plt. 4" - 10" 12" - 16" 18" - 24"
1
=
Area (cm²) 200
2 Gap (typ) =
Mark No. 2
Total Length
HEA100 HEA160 HEA200
300 300 300
=
Maximum Anchor Load (KN) HOLD HOLD HOLD HOLD
Note 1. For details of Cold Anchor Shoe see CAS1. Assembly Tag No: - CDA1 - X Detail No.
SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
CDA1 Anchor Shoe - Cold Insulated Lines 3/4" - 24"
Sheet H5
2
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
1
2 3
H
4 3
5
See Note 1
Support Type CH1-A CH1-B CH1-C CH1-D CH1-E CH1-F CH1-G CH1-H CH1-J
Pipe Size 3/4" - 24" Pipe Maximum Dimension 'H' Size Maximum Minimum Load (KN) 3/4" - 1" 500 2.0 1½ - 2" 500 3.0 2000 3" - 6" 600 5.0 8" 700 8.0 10" - 14" 800 12.3 2200 16" - 18" 900 20.0 20" - 24" 2400 1100 27.0
Insulation Thickness (mm) 30 40 50 60 70 80 90 100 110
Note 1. For details of Hanger Clamp see Specification No. 60-0000-L-SPE-1003. Assembly Tag No: - CH1 - X - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size CH1 Non-Adjustable Hanger for Cold Insulated Pipe 3/4" - 24"
Sheet H6
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Pipe Mark No.1 Size (1 Off) 3/4" - 2" 3" - 6" 8" Welding 10" - 14" Lug 16" - 18" 20" - 24"
Pipe Mark No.4 Size (1 Off) 3/4" - 2" 3" - 6" 8" Threaded 10" - 14" Sling Rod 16" - 18" 20" - 24"
SUPPORT No SUPPORT TYPE PIPE SIZE
Size L-12 L-16 L-20 L-24 L-30 L-36
Size R-12A R-16A R-20A R-24A R-30A R-36A
Mark No.2 (1 Off)
Clevis
Mark No.5 (1 Off)
Size
Mark No.3 (2 Off)
CL-12 CL-16 CL-20 CL-24 CL-30 CL-36
Nut
Size M12 M16 M20 M24 M30 M36
Size
WENR-12 WENR-16 Weldless WENR-20 Eye Nut WENR-24 WENR-30 WENR-36
CH1 Non-Adjustable Hanger for Cold Insulated Pipe 3/4" - 24"
Sheet H7
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
5T See Note 1
SPECIFICATION FOR PIPE SUPPORTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
100
Cold Insulate Trunnion to depth shown A Hole in centre of plate = Trunnion dia. + 2mm
1
BS1 or BS2 (Ref.)
For Trunnion details refer to Isometric
Existing Steel or Base Plate NOTE 1. 'T' = Cold Insulation Thickness. Trunnion 2" 3" 4" 6" 8" 10" 12" 16" Size Mark 6 Thk. Sq. 6 Thk. Sq. 6 Thk. Sq. 6 Thk. Sq. 6 Thk. Sq. 6 Thk. Sq. 6 Thk. Sq. 6 Thk. Sq. No. 1 Plate Plate Plate Plate Plate Plate Plate Plate Area 400 625 755 1225 1765 2255 2755 3660 (cm²) Dimension 200 250 275 350 420 475 525 605 A'
Assembly Tag No: - CBS1 - X Detail No SUPPORT No SUPPORT TYPE TRUNNION SIZE
Trunnion Size
CBS1 Base Support for Cold Insulated Lines 2" - 16"
Sheet H8
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
Extend Cold Insulation to end of Trunnion For Trunnion details refer to Isometric
1
A
CS1 (Ref.)
6mm Dia. Weep Hole. Seal with Mastic after Welding Existing Steel 250
1000 (Max.)
NOTE 1. Unless otherwise advised by Piping Stress, the trunnion sizes that shall be used are those listed below. Pipe 2",3" 4" 6" 8" 10" 12",14" 16", 18" 20", 24" Size Trunnion 2" 3" 4" 6" 8" 10" 12" 16" Size Mark 6 Thk. Sq. 6 Thk. Sq. 6 Thk. Sq. 6 Thk. Sq. 6 Thk. Sq. 6 Thk. Sq. 6 Thk. Sq. 6 Thk. Sq. No. 1 Plate Plate Plate Plate Plate Plate Plate Plate Area 400 625 755 1225 1765 2255 2755 3660 (cm²) Dimension 200 250 275 350 420 475 525 605 A'
Assembly Tag No: - CTS1 - X Detail No SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size
CTS1 Trunnion Support for Cold Insulated Lines 2" - 24"
Sheet H9
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
2
Trim to suit and weld to existing steel or vessel clip
2
130 1 Elevation L K Guides shall be welded 20mm below top face of angle. 3
See Note 1
10 (typ)
3 Gap (typ)
Alternative connection to steel (Elevation)
L
20
0°
3 Gap (typ)
A
Field weld bracing where req'd 30° 0 60°
30
30 Plan
A
Bracing req'd when this dimension > 300mm
NOTE 1. For details of Cold Double Shoe see CS3. 2. For Pipes with an Insulation Thickness of 50mm and below use pipe support CVG1. For Pipes with an Insulation Thickness of between 60mm and 100mm use pipe support CVG2. For Pipes with an Insulation Thickness of 110mm and above use pipe support CVG3.
Assembly Tag No: - CVG1 - X Detail No. SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size CVG1, CVG2, CVG3 4- Directional Vertical Guide for Cold Insulated Lines 8" - 24"
Sheet H10
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Pipe Size 8" 10" 12" 14" 16" 18" 20" 22" 24"
Pipe Size 8" 10" 12" 14" 16" 18" 20" 22" 24"
Pipe O.D. 219 273 324 356 406 457 508 559 610
CVG1 Dimn. 'A' 425 479 -
Mark No. 1 UPN 160
UPN 200
CVG2 Dimn. 'A' 525 579 630 662 712 763 814 865 916
Length 2500 2500 3080 3080 3500 3500 4040 4040 4040
Dimensions CVG3 Dimn. 'A' 863 914 965 1016
Mark No. 2
UPN 100
Length 2300 2470 2630 2625 2890 3260 3500 3680 3850
Mark No.3
Maximum Horizontal Loads (KN) 5
10 Thk Plate 8 Area = 36 cm2 10
All Pipe Supports 'K' 'L' Max. 1250 900 1250 900 1540 1100 1540 1100 1750 1200 1750 1200 2020 1400 2020 1400 2020 1400
Assembly Tag No: - CVG1 - X Detail No. SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size CVG1 4- Directional Vertical Guide for Cold Insulated Lines 8" - 24"
Sheet H11
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
2
Trim to suit and weld to existing steel or vessel clip
2
130 1 Elevation L K For shoe orientation refer to isometric See Note 1
10 (typ)
Alternative connection to steel (Elevation)
L
20
0°
3 Gap (typ)
A
Field weld bracing where req'd 30° 0 60°
Plan
A
Bracing req'd when this dimension > 300mm
NOTE 1. For details of Cold Double Shoe see CS3. 2. For Pipes with an Insulation Thickness of 50mm and below use pipe support CVG4. For Pipes with an Insulation Thickness of between 60mm and 100mm use pipe support CVG5. For Pipes with an Insulation Thickness of 110mm and above use pipe support CVG6.
Assembly Tag No: - CVG4 - X Detail No. SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size CVG4, CVG5, CVG6 2- Directional Vertical Guide for Cold Insulated Lines 8" - 24"
Sheet H12
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Pipe Size 8" 10" 12" 14" 16" 18" 20" 22" 24"
Pipe Size 8" 10" 12" 14" 16" 18" 20" 22" 24"
Pipe O.D. 219 273 324 356 406 457 508 559 610
CVG4 Dimn. 'A' 425 479 -
Mark No. 1 UPN 160
UPN 200
CVG5 Dimn. 'A' 525 579 630 662 712 763 814 865 916
Length 2500 2500 3080 3080 3500 3500 4040 4040 4040
Dimensions CVG6 Dimn. 'A' 863 914 965 1016
Mark No. 2
UPN 100
Length 2300 2470 2630 2625 2890 3260 3500 3680 3850
Maximum Horizontal Loads (KN) 5
8
10
All Pipe Supports 'K' 'L' Max. 1250 900 1250 900 1540 1100 1540 1100 1750 1200 1750 1200 2020 1400 2020 1400 2020 1400
Assembly Tag No: - CVG4 - X Detail No. SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size CVG4, CVG5, CVG6 2- Directional Vertical Guide for Cold Insulated Lines 8" - 24"
Sheet H13
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
20 4
70
Stack as Shown
20
X
5
55
6
1
3
25 Typ.
'A'
7
1 X
2 65
Section X-X 130
Pipe Size ¾" 1" 1½"
Mark No.1
Pipe Size ¾" 1" 1½"
Mark No.5
No. Off
Mark No.6
No. Off
Mark No.7
No. Off
M10 Plain Washer
4 4 4
M10 Compression Washer or Similar
6 6 6
Fabreeka Nitrile 21 Ply Pad 70 x 90 or equivalent
2 2 2
Pipe Size ¾" 1" 1½"
Dimension A 115 130 145
100x100 x10L
Total Length 260 260 260
Mark No.2 6Thk. Plate
M.T.O. Mark No.3 Area (cm²) 81 M10 Stud 81 Bolt 81
Total Length 230 260 290
Mark No.4
No. Off
M10 Anco Self Lock Nut
4 4 4
NOTES: 1- Field procedure for tightening bolts: -Tighten all nuts by hand (finger Tight) -Turn nuts an additional 1/2 turn for pipes 2" - 4" -Turn nuts an additional 1/4 turn for pipes 6" - 12" 2- Bond Nitrile Pad to Steel using Epoxy Adhesive TX528 or equivalent
Assembly Tag No: - HD1 - X Detail No. SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size HD1 Hold Down for Uninsulated Pipes ¾" - 1½"
Sheet H14
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2 C L
SPECIFICATION FOR PIPE SUPPORTS C L
10
'T'
1 'F'
'F'
1 Hole 'H' Dia. Note For Use With 6" to 12".
1 Hole 'H' Dia.
'A'
1
Bond to Mark No.1
Min Bend radius = 1.5T
'C'
'B'
'C'
8
9 7 21
'T'
'R'
'D'
10
13
'A' Note No Gusset Required For 2" to 4".
13
'E'
'E'
2
Existing Steel 4
3
6
5 Bond to Mark No.4
Pipe Size 2" 3" 4" 6" 8" 10" 12"
A 97 111 124 162 187 211 257
Pipe Size 2" 3" 4" 6" 8" 10" 12"
Dimensions R T 32 6 46 6 59 6 86 10 111 10 138 10 164 12
B 76 105 130 191 241 295 352
C 90 90 90 98 98 98 113
Drill 18 dia hole in existing steel Dimensions D 17 32 44 71 97 124 149
E 60 60 60 90 90 90 90
F 30 30 30 30 30 30 30
H 18 18 18 18 18 18 18
NOTES: 1- Field procedure for tightening bolts: -Tighten all nuts by hand (finger Tight) -Turn nuts an additional 1/2 turn for pipes 2" - 4" -Turn nuts an additional 1/4 turn for pipes 6" - 12"
Assembly Tag No: - HD1 - X Detail No. SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size HD1 Hold Down Support for Uninsulated Pipes 2" - 12"
Sheet H15
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Pipe Size 2" 3" 4" 6" 8" 10" 12"
Pipe Size 2" 3" 4" 6" 8" 10" 12"
Pipe Size 2" 3" 4" 6" 8" 10" 12"
Mark No. 1 60 x 6 Thk. Plate 90 x 10 Thk. Plate 90 x 12 Thk. Plate
Total Length 330 410 470 630 760 900 1060
Mark M.T.O. Area(cm²) No. 5 12Thk. 165 Kinetics 185 Molded 200 Fibreglass 345 Pad Type 390 S-40 440 515 Density
Mark No. 8
M16 Nut
No. Off 2 2 2 2 2 2 2
Mark No. 2
10Thk. Plate 12 Thk. Plate
Mark No. 6
1.5mm Thick PTFE
Mark No. 9
M16 Self Lock Nut
M.T.O. Area(cm²)
70 95 120 170
M.T.O. Area(cm²) 165 185 200 345 390 440 515
No. Off 2 2 2 2 2 2 2
Mark No. 3
M16 x 120Lg. Bolt
Mark No. 7
See Note 1
Mark No. 10
1.5mm Thick PTFE
No. Off 2 2 2 2 2 2 2
Mark No. 4
M.T.O. Area(cm²) 165 185 6Thk. 200 Galvanised 345 Plate 390 440 515
No. Off 2 2 2 2 2 2 2
M.T.O. Area(cm²) 65 95 120 240 310 385 460
Note 1. 6Thk. Galvanized Steel Plate, Bonded to 12Thk. Flexoply Isolation Washer Impregnated in Neoprene and Hot Dipped in Plastisol or Equal.
SUPPORT No SUPPORT TYPE PIPE SIZE
HD1 Hold Down Guide for Uninsulated Pipes 2" - 12"
Sheet H16
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2 C L
SPECIFICATION FOR PIPE SUPPORTS 'T'
10
C L
'F'
'E'
2
'F'
1 Hole 'H' Dia.
'A'
Min Bend radius = 1.5T
'C'
'B'
'C'
9
10 11
'R'
55 21
'T'
13
2
Note No Gusset Required For 2" to 4".
Bond to Mark No.2
12
'A'
'D'
1 Hole 'H' Dia. Note For Use With 6" to 12".
13
'E'
4
5 1 8 'I' 6
7
'I'
3
10 (typ)
Bond to Mark No.6
Pipe Size 2" 3" 4" 6" 8" 10" 12"
A 97 111 124 162 187 211 257
B 76 105 130 191 241 295 352
C 90 90 90 98 98 98 113
Pipe Size 2" 3" 4" 6" 8" 10" 12"
I 140 150 165 205 230 255 300
Dimensions R 32 46 59 86 111 138 164
T 6 6 6 10 10 10 12
Dimensions D 17 32 44 71 97 124 149
E 60 60 60 90 90 90 90
1 Gusset Req'd. Pipe Size 2" to 4". 3 Gussets Req'd. Pipe Size 6" to 12"
F 30 30 30 30 30 30 30
H 18 18 18 18 18 18 18
NOTES: 1- Field procedure for tightening bolts: -Tighten all nuts by hand (finger Tight) -Turn nuts an additional 1/2 turn for pipes 2" - 4" -Turn nuts an additional 1/4 turn for pipes 6" - 12"
Assembly Tag No: - HD2 - X Detail No. SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size HD2 Hold Down Guide for Uninsulated Pipes 2" - 12"
Sheet H17
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Pipe Size 2" 3" 4" 6" 8" 10" 12"
Pipe Size 2" 3" 4" 6" 8" 10" 12"
Pipe Size 2" 3" 4" 6" 8" 10" 12"
Mark No. 1
100x100x 10L
Mark No. 5
1.5mm Thick PTFE
Mark No. 9
M16 Nut
Total Length 280 300 330 410 460 510 600
Mark No. 2 60 x 6 Thk. Plate 90 x 10 Thk. Plate 90 x 12 Thk. Plate
Total Length 330 410 470 630 760 900 1060
Mark No. 3
6Thk. Plate
M.T.O. Area(cm²) 81 81 81 162 162 162 162
M.T.O. Mark M.T.O. Mark M.T.O. Area(cm²) No. 6 Area(cm²) No. 7 Area(cm²) 165 165 12Thk. 165 185 185 Kinetics 185 200 6Thk. 200 Molded 200 345 Galvanised 345 Fibreglass 345 390 Plate 390 Pad Type 390 440 440 S-40 440 515 515 515 Density
No. Off 2 2 2 2 2 2 2
Mark No. 10
M16 Self Lock Nut
No. Off 2 2 2 2 2 2 2
Mark No. 11
See Note 1
No. Off 2 2 2 2 2 2 2
Mark No. 4
M.T.O. Area(cm²)
10Thk. Plate
70 95 120 170
12 Thk. Plate
Mark No. 8
M16 x 120Lg. Bolt
Mark No. 12
1.5mm Thick PTFE
No. Off 2 2 2 2 2 2 2
M.T.O. Area(cm²) 65 95 120 240 310 385 460
Note 1. 6Thk. Galvanized Steel Plate, Bonded to 12Thk. Flexoply Isolation Washer Impregnated in Neoprene and Hot Dipped in Plastisol or Equal.
SUPPORT No SUPPORT TYPE PIPE SIZE
HD2 Hold Down Guide for Uninsulated Pipes 2" - 12"
Sheet H18
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
'H'
3
'H'
4
'B' Typ.
20 Typ.
'A'
300
'C' 7
40
A
5
6
10 (typ)
55
1
40
2
9
'E'
8
2 10 Typ.
A
NOTES:
'D'
Section A-A
6
5 Pipe Size 1" 1½" 2" 3" 4" 6" 8" 10" 12"
1
A 100 100 100 100 100 100 200 200 250
B 35 30 25 20 20 20 30 30 30
Dimension C D 360 110 380 110 390 110 440 110 480 110 540 110 590 110 660 110 710 110
E 270 290 300 330 355 410 460 515 565
H 100 100 100 100 100 100 100 100 100
1- Bond Nitrile Pad to Steel using Epoxy Adhesive TX528 or equivalent 2- Field procedure for tightening bolts: -Tighten all nuts by hand (finger Tight) -Turn nuts an additional 1/2 turn for pipes 2" - 4" -Turn nuts an additional 1/4 turn for pipes 6" - 12"
Assembly Tag No: - HD3 - X Detail No. SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size HD3 Hold Down for Insulated Pipes 1" - 12"
Sheet H19
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Pipe Size 1" 1½" 2" 3" 4" 6" 8" 10" 12"
Pipe Size 1" 1½" 2" 3" 4" 6" 8" 10" 12"
Pipe Size 1" 1½" 2" 3" 4" 6" 8" 10" 12"
Mark No. 1
100x100x 10L
Mark No. 5
10 Thk. Plate
Mark No. 8
M16 Plain Washer
SUPPORT No SUPPORT TYPE PIPE SIZE
Total Length 580 600 610 660 700 760 810 880 930
Mark No. 2
M16 Stud Bolt
Total Length 515 555 575 635 685 795 895 1005 1105
M.T.O. Area(cm²) 325 325 325 325 325 325 325 325 325
Mark No. 6 Fabreeka Nitrile 21 Ply Pad 150x90 or equiv. Fabreeka Nitrile 21 Ply Pad 300x90 or equiv.
No. Off
No. Off
Mark No. 9
No. Off
4 4 4 4 4 4 4 4 4
M16 Compr'sn Washer or Similar
2 2 2 2 2 2 2 2 2
Mark No. 3
10 Thk. Plate
Mark No. 7
M16 Self Lock Nut or equivalent
M.T.O. Area(cm²) 1140 1140 1140 1140 1140 1140 1740 1740 2040
Mark No. 4
10 Thk. Plate
M.T.O. Area(cm²) 120 160 210 245 240 230 645 610 920
No. Off 4 4 4 4 4 4 4 4 4
6 6 6 6 6 6 6 6 6
HD3 Hold Down for Insulated Pipes 1" - 12"
Sheet H20
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
C L
C L 'E'
1
'A'
Min Bend radius = 1.5T
'C'
'B'
'C'
8
1
'A'
9 7 21
'T'
'R' 13
=
Note No Gusset Required For 2" to 4".
Bond to Mark No.1
10
25 =
'D'
=
13
Note For Use With 6" to 12".
25 =
'H'
'F'
'F' 'H'
'E'
2
10
'T'
SPECIFICATION FOR PIPE SUPPORTS
Existing Steel 4
3
6
5 Bond to Mark No.4
Pipe Size 2" 3" 4" 6" 8" 10" 12"
A 110 124 137 168 194 224 270
Pipe Size 2" 3" 4" 6" 8" 10" 12"
Dimensions R T 32 6 46 6 59 6 86 10 111 10 138 10 164 12
B 76 105 130 191 241 295 352
C 118 120 120 125 125 125 137
Drill 18 dia hole in existing steel Dimensions D 17 32 44 71 97 124 149
E 60 60 60 90 90 90 90
F 30 30 30 30 30 30 30
H 18 18 18 18 18 18 18
NOTES: 1- Field procedure for tightening bolts: -Tighten all nuts by hand (finger Tight) -Turn nuts an additional 1/2 turn for pipes 2" - 4" -Turn nuts an additional 1/4 turn for pipes 6" - 12"
Assembly Tag No: - HDS1 - X Detail No. SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size HDS1 Slotted Hold Down Support for Uninsulated Pipes 2" - 12"
Sheet H21
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Pipe Size 2" 3" 4" 6" 8" 10" 12"
Pipe Size 2" 3" 4" 6" 8" 10" 12"
Pipe Size 2" 3" 4" 6" 8" 10" 12"
Mark No. 1 60 x 6 Thk. Plate 90 x 10 Thk. Plate 90 x 12 Thk. Plate
Total Length 340 370 390 460 510 590 650
Mark M.T.O. Area(cm²) No. 5 12Thk. 190 Kinetics 210 Molded 225 Fibreglass 400 Pad Type 440 S-40 490 565 Density
Mark No. 8
M16 Nut
No. Off 2 2 2 2 2 2 2
Mark No. 2
10Thk. Plate 12 Thk. Plate
Mark No. 6
1.5mm Thick PTFE
Mark No. 9
M16 Self Lock Nut
M.T.O. Area(cm²)
70 95 120 170
M.T.O. Area(cm²) 190 210 225 400 440 490 565
No. Off 2 2 2 2 2 2 2
Mark No. 3
No. Off 2 2 2 2 2 2 2
M16 x 120Lg. Bolt
Mark No. 7
See Note 1
Mark No. 10
1.5mm Thick PTFE
Mark No. 4
M.T.O. Area(cm²) 190 210 6Thk. 225 Galvanised 400 Plate 440 490 565
No. Off 2 2 2 2 2 2 2
M.T.O. Area(cm²) 65 95 120 240 310 385 460
Note 1. 6Thk. Galvanized Steel Plate, Bonded to 12Thk. Flexoply Isolation Washer Impregnated in Neoprene and Hot Dipped in Plastisol or Equal.
SUPPORT No SUPPORT TYPE PIPE SIZE
HDS1 Slotted Hold Down Support for Uninsulated Pipes 2" - 12"
Sheet H22
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3 CL
SPECIFICATION FOR PIPE SUPPORTS C L
10
'T'
2
Note For Use With 6" to 12".
'A'
Min Bend radius = 1.5T
'C'
'B'
'C'
9
2
'A'
10 11
'R'
55 21
'T'
13
=
Note No Gusset Required For 2" to 4".
Bond to Mark No.2
12
25 =
'D'
=
13
'H'
25 =
'H'
'F'
'F'
'E'
'E'
4
5 1 8 'I' 6
7
'I'
3
10 (typ)
Bond to Mark No.6
Pipe Size 2" 3" 4" 6" 8" 10" 12"
A 110 124 137 168 194 224 270
B 76 105 130 191 241 295 352
C 118 120 120 125 125 125 137
Pipe Size 2" 3" 4" 6" 8" 10" 12"
I 170 185 195 230 255 285 325
Dimensions R 32 46 59 86 111 138 164
T 6 6 6 10 10 10 12
Dimensions D 17 32 44 71 97 124 149
E 60 60 60 90 90 90 90
1 Gusset Req'd. Pipe Size 2" to 4". 3 Gussets Req'd. Pipe Size 6" to 12"
F 30 30 30 30 30 30 30
H 18 18 18 18 18 18 18
NOTES: 1- Field procedure for tightening bolts: -Tighten all nuts by hand (finger Tight) -Turn nuts an additional 1/2 turn for pipes 2" - 4" -Turn nuts an additional 1/4 turn for pipes 6" - 12"
Assembly Tag No: - HDS2 - X Detail No. SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size HDS2 Slotted Hold Down Support for Uninsulated Pipes 2" - 12"
Sheet H23
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 3
SPECIFICATION FOR PIPE SUPPORTS
Pipe Size 2" 3" 4" 6" 8" 10" 12"
Pipe Size 2" 3" 4" 6" 8" 10" 12"
Pipe Size 2" 3" 4" 6" 8" 10" 12"
Mark No. 1
100x100x 10L
Mark No. 5
1.5mm Thick PTFE
Mark No. 9
M16 Nut
Total Length 340 370 390 460 510 570 650
Mark No. 2 60 x 6 Thk. Plate 90 x 10 Thk. Plate 90 x 12 Thk. Plate
Total Length 390 470 535 695 825 965 1125
Mark No. 3
6Thk. Plate
M.T.O. Area(cm²) 81 81 81 162 162 162 162
M.T.O. Mark M.T.O. Mark M.T.O. Area(cm²) No. 6 Area(cm²) No. 7 Area(cm²) 190 190 12Thk. 190 210 210 Kinetics 210 225 6Thk. 225 Molded 225 400 Galvanised 400 Fibreglass 400 440 Plate 440 Pad Type 440 490 490 S-40 490 565 565 565 Density
No. Off 2 2 2 2 2 2 2
Mark No. 10
M16 Self Lock Nut
No. Off 2 2 2 2 2 2 2
Mark No. 11
See Note 1
No. Off 2 2 2 2 2 2 2
Mark No. 4
M.T.O. Area(cm²)
10Thk. Plate
70 95 120 170
12 Thk. Plate
Mark No. 8
M16 x 120Lg. Bolt
Mark No. 12
1.5mm Thick PTFE
No. Off 2 2 2 2 2 2 2
M.T.O. Area(cm²) 65 95 120 240 310 385 460
Note 1. 6Thk. Galvanized Steel Plate, Bonded to 12Thk. Flexoply Isolation Washer Impregnated in Neoprene and Hot Dipped in Plastisol or Equal.
SUPPORT No SUPPORT TYPE PIPE SIZE
HDS2 Slotted Hold Down Support for Uninsulated Pipes 2" - 12"
Sheet H24
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0 C L
C L
1 'F'
'F'
'E'
'E'
2
10
'T'
SPECIFICATION FOR PIPE SUPPORTS
1 Hole 'H' Dia.
1 Hole 'H' Dia.
'A'
Note For Use With 6" & 8".
'A'
1
Note No Gusset Required For 1½" to 4".
Min Bend radius = 1.5T
'B'
'B'
'D'
'C'
'T'
'R'
5 4
1 Hole 'H' dia. in Existing Steel Typ.
3
Pipe Size 1½" 2" 3" 4" 6" 8"
A 60 70 99 108 155 180
Pipe Size 1½" 2" 3" 4" 6" 8"
Dimensions R T 25 6 31 6 46 6 58 10 85 10 111 10
B 80 100 137 146 200 230
C 22 28 41 54 81 105
Dimensions D 2 2 3 3 3 4
Existing Steel
E 60 60 60 60 90 90
F 30 30 30 30 30 30
H 14 14 18 18 26 26
Assembly Tag No: - AS1 - X Detail No. SUPPORT No SUPPORT TYPE PIPE SIZE
Pipe Size AS1 Anchor Strap for Uninsulated Galvanised Pipe 1½" - 8"
Sheet H25
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
Pipe Size 1½" 2" 3" 4" 6" 8"
Mark No. 1 60 x 6 Thk. Plate
Pipe Size 1½" 2" 3" 4" 6" 8"
Mark No. 5 M24 x 100Lg. Bolt C/W Nut & Washer
90 x 10 Thk. Plate
SUPPORT No SUPPORT TYPE PIPE SIZE
Total Length 200 300 420 480 670 810
Mark No. 2
10Thk. Plate
M.T.O. Area(cm²)
160 210
Mark No. 3 M12 x 70Lg. Bolt C/W Nut & Washer
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
No. Off 2 2
Mark No. 4 M16 x 80Lg. Bolt C/W Nut & Washer
No. Off
2 2
No. Off
2 2
AS1 Anchor Strap for Uninsulated Galvanised Pipe 1½" - 8"
Sheet H26
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Welded Shoe S1, S5 Standard Length. Pipe Size 26"-40" Sheet A3
Welded Shoe S1, S5, S9 Standard Length. Pipe Size ½"-6" Sheet A1
Welded Shoe S1, S5, S9 Standard Length. Pipe Size 8"-24" Sheet A2
Clamped Shoe S3, S7, S11 Standard Length. Pipe Size ½"-6" Sheet A8
Clamped Shoe S3, S7, S11 Standard Length. Pipe Size 8"-24" Sheet A9
Clamped Shoe S4, S8, S12 Long. Pipe Size ½"-6" Sheet A10
Clamped Shoe S4, S8, S12 Long. Pipe Size 8"-24" Sheet A11
Clamped Shoe S104, S108, S112 Long. For St. Stl. Pipe. Pipe Size 8"-30". Sheet A17
PTFE Isolator Pad for Stainless Steel Pipe. S113. Pipe Size ½"-12" Sheet A18
Pick-Up for Insulated Pipe S114. Pipe Size 3" Max (Supported Pipe). Sheet A19
PTFE for Pipe Shoe S19. Pipe Size 26"-88" Sheet A13
Packing Plate types for gaps 21mm to 60mm. Pipe Size ½"-42" Sheet A23 & A24
Packing Plate types for gaps 61mm to 80mm. Pipe Size ½"-42" Sheet A25 & A26
Clamped Shoe S104, S108, S112 Long. For St. Stl. Pipe. Pipe Size ½"-6". Sheet A16
PTFE for Pipe Shoe S19. Pipe Size ½"-24" Sheet A12
Welded Shoe S2, S6, S10 Long. Pipe Size ½"-6" Sheet A4
Welded Shoe S2, S6, S10 Long. Pipe Size 8"-24" Sheet A5
Welded Shoe S2, S6 Long. Pipe Size 26"-92" Sheet A6 & A7
Clamped Shoe S103, S107, S111 For St. Stl. Pipe. Pipe Size ½"-6" Sheet A14
Clamped Shoe S103, S107, S111 For St. Stl. Pipe. Pipe Size 8"-30" Sheet A15
Pick-Up for Uninsulated Pipe S115. Pipe Size 3" Max. (Supported Pipe). Sheet A20
Packing Plate types for gaps up to 20mm. Pipe Size ½"-42" Sheet A21 & A22
PTFE for Long Pipe Shoe S20. Pipe Size ½"-24" Sheet A27
ATTACHMENT A - PIPE SUPPORT SELECTION CHART (SHOES, PTFE, PICK-UP, PACKING)
PTFE for Long Pipe Shoe S20. Pipe Size 26"-88" Sheet A28 SHEET No. J1A
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS
Pipe Shoe for SECT Traced Piping S21. All Sizes Sheet A29
Long Welded Shoe. S13, S14 For Pipe Spec. 150H26, 150K26 Pipe Size 36"- 40" Sheet A30 & A31
Packing Support for gaps from 21mm to 60mm. PK3 Pipe Size 44" - 92". Sheet A32
Stiffening Ring SR1, SR101. Pipe Size 36" - 92" Sheet A33
Double Pipe Shoe for SECT Traced Piping. S22. All Sizes Sheet A34
Puddle Flange for Sump Covers PF1, PF101. Pipe Size ¾" - 12" Sheet A35
Welded Shoe for Contra Traced Pipes S15. Pipe Size 28". Sheet A36
ATTACHMENT A - PIPE SUPPORT SELECTION CHART (SHOES, PTFE, PICK-UP, PACKING)
SHEET No. J1B
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Line Stop for Uninsulated Pipe DA1. Pipe Size ½"-4" Sheet B1
Line Stop for Uninsulated Pipe DA1. Pipe Size 6"-14" Sheet B2
Guide for Insulated Pipe HG1. Pipe Size ½"-92" Sheet B8
Guide for Uninsulated Pipe HG2. Pipe Size ½"-14" Sheet B9
PLAN Guide for Uninsulated Vertical Pipe VG1. Pipe Size ½"-2" Sheet B12
PLAN Guide for Uninsulated Vertical Pipe 2 Way. VG7. Pipe Size 4"-24" Sheet B17 & B18
PLAN Guide for 2 or more Vertical Pipes VG2. Pipe Size ½"-2" Sheet B13
PLAN Guide for Uninsulated Vertical Pipe 2 Way. VG8. Pipe Size 4"-24" Sheet B17 & B18
Line Stop for Uninsulated Pipe DA1. Pipe Size 16"-40" Sheet B3
Line Stop for Insulated Pipe DA2, DA3. Pipe Size ½"-4" Sheet B4
Line Stop for Insulated Pipe DA2, DA3. Pipe Size 6"-24" Sheet B5
Line Stop for Insulated Pipe DA2. Pipe Size 26"-92" Sheet B6 & B7
Guide for Uninsulated Pipe HG2. PipeSze 16" - 40" Sheet B10
Guide (Hold-down) for Insulated Pipe. HG3. Pipe Size ½"-6" Sheet B11
Guide for Uninsulated Vertical Pipe 4 Way. St.Stl. VG104. Pipe Size 4"-24". Sheet B32 & B33
Guide for Uninsulated Vertical Pipe 2 Way. St.Stl. VG107 & VG108 Pipe Size 4"-24". Sheet B32 & B33
PLAN
PLAN
PLAN Guide for all Vertical Pipes VG3. Pipe Size ½"-6" Sheet B14
PLAN Guide for Vertical Pipe - 2 Way Insulation ≤ 75mm Thk. VG9 Pipe Size 4"-24". Sheet B17 & B18
Guide for Uninsulated Vertical Pipe 4 Guide for Vertical Pipe - 4 Way Way. VG4. Pipe Size 8"-24" Insulation ≤ 75mm Thk. VG5 Sheet B15 & B16 Pipe Size 8"-24". Sheet B15 & B16
PLAN Guide for Vertical Pipe - 4 Way Insulation ≥ 75mm Thk. VG6 Pipe Size 8"-24". Sheet B15 & B16
PLAN Guide for Vertical Pipe - 2 Way Insulation ≥ 75mm Thk. VG10 Pipe Size 4"-24". Sheet B17 & B18
Rigid Strut with Trunnion and Clamp RS1. Pipe Size All Sizes. Sheet B26
ATTACHMENT B - PIPE SUPPORT SELECTION CHART (LINE STOPS, GUIDES, RIGID STRUTS)
Rigid Strut with Shoe RS2. Pipe Size All Sizes. Sheet B27 SHEET No. J2
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Plan Cantilever Support for Vertical Pipe VS1. Pipe Size ½"-8" Sheet B19
Braced Cantilever Support for Vertical Pipe. VS2. Pipe Size 2"-24" Sheet B20
Line Stop for Non-Insulated St.Stl. Pipes. DA101. Pipe Size ¾" - 1½" Sheet B28
Line Stop for Insulated St.Stl. Pipes. DA102. Pipe Size ½" - 1½" Sheet B29
Horizontal Frame Support and Guide for Vertical Pipe. VS3. Pipe Size ½"-24". Sheet B21
Braced Horizontal Frame Support for Vertical Pipe. VS4. Pipe Size ½"-24" Sheet B22
Support from Vessel for Vertical Pipe VS5. Pipe Size 2" - 10" Sheet B23
Braced Support from Vessel for Vertical Pipe. VS6. Pipe Size 4" - 24" Sheet B24 & B25
Line Stop, Non-Insul Galvanised pipes DA201. Pipe Size ½" - 3" Sheet B30
Line Stop, Insulated Galvanised pipes DA202. Pipe Size ½" - 3" Sheet B31
Guide for Uninsulated St. Stl. Pipe 4 Way. VG104. Pipe Size 4" - 24" Sheet B32 & B33
Guide for Uninsulated St. Stl. Pipe 2 Way. VG107. Pipe Size 4" - 24" Sheet B32 & B33
Guide for Uninsulated St. Stl. Pipe 2 Way. VG108. Pipe Size 4" - 24" Sheet B32 & B33
Line Stop for Uninsulated Pipes on Sleepers < 600mm . DA4 Pipe Size ½" - 4" Sheet B34
Line Stop for Uninsulated Pipes on Sleepers < 600mm . DA4 Pipe Size 6" - 14" Sheet B35
Line Stop for Uninsulated Pipes on Sleepers < 600mm . DA4 Pipe Size 16" - 40" Sheet B36
Line Stop for Insulated Pipes on Sleepers < 600mm . DA5, DA6 Pipe Size 26"-40" Sheet B48 & B49
Line Stop for Uninsulated Pipes on Sleepers > 600mm . DA7 Pipe Size ½" - 4" Sheet B39
Line Stop for Uninsulated Pipes on Sleepers > 600mm . DA7 Pipe Size 6" - 14" Sheet B40
Line Stop for Uninsulated Pipes on Sleepers > 600mm . DA7 Pipe Size 16" - 40" Sheet B41
Line Stop for Insulated Pipes on Sleepers < 600mm . DA5, DA6 Pipe Size ½" - 4" Sheet B37
Line Stop for Insulated Pipes on Sleepers > 600mm . DA10 Pipe Size ½" - 4" Sheet B44
Line Stop for Insulated Pipes on Sleepers < 600mm . DA5, DA6 Pipe Size 6" - 24" Sheet B38
Line Stop for Insulated Pipes on Sleepers > 600mm . DA10 Pipe Size 6" - 16" Sheet B45
ATTACHMENT B - PIPE SUPPORT SELECTION CHART (BRACKETS WITH TRUNNIONS; STEEL, STAIN. STEEL AND GALVANISED LINE STOPS ON STEEL/SLEEPERS)
SHEET No. J3A
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS
Line Stop for SECT Traced Piping on Steel. DA8 Pipe Size 6" Sheet B42
Line Stop for SECT Traced Piping on Sleepers. DA9 Pipe Size 6" Sheet B43
Line Stop for Acoustic Insulated Pipe. DA13 Pipe Size 6"- 24" Sheet B51
Line Stop for Acoustic Insulated Pipe. DA13 Pipe Size 26"- 40" Sheet B52 & B53
Anchor Shoe for SECT Traced Piping on Steel. SAS1 Pipe Size All Sizes Sheet B56
Anchor Shoe for SECT Traced Piping on Sleepers. SAS2 Pipe Size All Sizes Sheet B57
Line Stop for Pipe Spec. 150H26, 150K26. DA11, DA12 Pipe Size 36"- 40" Sheet B46 & B47
Line Stop for Acoustic Insulated Pipe. DA13 Pipe Size ½"- 4" Sheet B50
Line Stop for Uninsulated or PPC Pipe, Line Stop for Uninsulated or PPC Pipe Des. Temp. -60°C or below. Des. Temp. -60°C or below. DA103 Pipe Size 8"-14" Sheet B54 DA103 Pipe Size 16"-24" Sheet B55
ATTACHMENT B - PIPE SUPPORT SELECTION CHART (BRACKETS WITH TRUNNIONS; STEEL, STAIN. STEEL AND GALVANISED LINE STOPS ON STEEL/SLEEPERS)
SHEET No. J3B
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Base Anchor for Non-Adjustable Support. BA1. Pipe Size 2"-40" Sheet C10
Base Plate from Grade BP. Pipe Size 2"-22" Sheet C14
Base Anchor for Adjustable Support BA2. Pipe Size 2"-40" Sheet C11
Base Plate from Steelwork BPS. Pipe Size 2"-22" Sheet C16
PTFE for Existing Base Support BS3. Pipe Size 2"-22" Sheet C8
PTFE for Existing Base Support BS3. Pipe Size 24"-40" Sheet C9
Horizontal Trunnion Support from Pipe (1 Off). T1. Pipe Size 2"-36" Sheet C1 & C3
Horizontal Trunnion Support from Pipe (2 Off). T2. Pipe Size 2"-36" Sheet C2 & C3
Non-Adjustable Base Support for Un-Paved areas. BS4 Pipe Size 2"-40". Sheet C15
Base Guide for Non-Adjustable Support. BG1. Pipe Size 2"-40" Sheet C12
Base Guide for Adjustable Support BG2. Pipe Size 2"-40" Sheet C13
Non-Adjustable Base Support for Paved and non-paved areas. BS5 Pipe Size 2"-40". Sheet C18
Non-Adjustable Base Support BS1. Pipe Size 2"-40" Sheet C5
Adjustable Base Support BS2. Pipe Size 2"-40" Sheet C6 & C7
Small non-adjustable Base Support BS6. Pipe Size 2" - 40" Sheet C19
Horizontal Trunnion Support from Elbow. T3. Pipe Size 2"-36" Sheet C4 & C17
Horizontal Trunnion Support from Pipe (2 Off) with RePad. T2. Pipe Size 48"-70" Sheet C20
ATTACHMENT C - PIPE SUPPORT SELECTION CHART (BASE SUPPORTS, BASE SUPPORTS WITH PTFE, TRUNNIONS)
SHEET No. J4
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 1
SPECIFICATION FOR PIPE SUPPORTS
Non-Adjustable Hanger for Uninsulated Pipe . HR1 (LightLoads) Pipe Size 1/2"-30". Sheet D1 & D2
Non-Adjustable Hanger for Uninsulated Non-Adjustable Hanger for Uninsulated Non-Adjustable Hanger for Insulated Pipe. HR4 (Light Loads) Pipe. HR2 (Heavy Loads) Pipe. HR3 (Light Loads) Pipe Size 1/2"-24". Sheet D3 & D4 Pipe Size 1/2"-30". Sheet D1 & D2 Pipe Size 1/2"-30". Sheet D1 & D2
Adjustable Hanger for Uninsulated Pipe. Adjustable Hanger for Uninsulated Pipe.Adjustable Hanger for Insulated Pipe. HR9 (Light Loads) HR7 (Heavy Loads) HR8 (Light Loads) Pipe Size 1/2"-24". Sheet D7 & D8 Pipe Size 1/2"-30". Sheet D5 & D6 Pipe Size 1/2"-30". Sheet D5 & D6
Non-Adjustable Hanger for Insulated St. Steel Pipe. HR104 (Light Loads) Pipe Size 1/2"-24". Sheet D11 & D12
Non-Adjustable Hanger for Insulated St. Steel Pipe. HR105 (Heavy Loads) Pipe Size 1/2"-24". Sheet D11 & D12
Adjustable Hanger for Uninsulated St. Steel Pipe. HR106 (Light Loads) Pipe Size 1/2"-30". Sheet D13 & D14
Non-Adjustable Hanger for Insulated Pipe. HR5 (Heavy Loads) Pipe Size 1/2"-24". Sheet D3 & D4
Adjustable Hanger for Uninsulated Pipe. HR6 (Light Loads) Pipe Size 1/2"-30". Sheet D5 & D6
Adjustable Hanger for Insulated Pipe. HR10 (Heavy Loads) Pipe Size 1/2"-24". Sheet D7 & D8
Non-Adjustable Hanger for Uninsulated Non-Adjustable Hanger for Uninsulated St. Steel Pipe. HR102 (Heavy Loads) St. Steel Pipe. HR101 (Light Loads) Pipe Size 1/2"-30". Sheet D9 & D10 Pipe Size 1/2"-30". Sheet D9 & D10
Adjustable Hanger for Uninsulated St. Steel Pipe. HR107 (Heavy Loads) Pipe Size 1/2"-30". Sheet D13 & D14
Adjustable Hanger for Insulated St. Steel Pipe. HR109 (Light Loads) Pipe Size 1/2"-24". Sheet D15 & D16
Adjustable Hanger for Insulated St. Steel Pipe. HR110 (Heavy Loads) Pipe Size 1/2"-24". Sheet D15 & D16
Trapeze Hanger TH Pipe Size All Sizes. Sheet D17
ATTACHMENT D - PIPE SUPPORT SELECTION CHART (HANGERS)
SHEET No. J5
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Spring Hanger for Uninsulated Pipe SH1 Pipe Size 2"-30". Sheet D18
Spring Hanger for Insulated Pipe SH2 Pipe Size 2"-30". Sheet D18
Spring Hanger for Uninsulated Pipe SH3 Pipe Size 2"-30". Sheet D19
Spring Hanger for Insulated Pipe SH4 Pipe Size 2"-30". Sheet D19
Trapeze Spring Hanger from under side of steel. SH5 Pipe Size All Sizes. Sheet D20
Trapeze Spring Hanger from top of steel. SH6 Pipe Size All Sizes. Sheet D21
Spring Hanger for Cold Insulated Pipe. SH22 Pipe Size 2"-36" Sheet D30
Spring Hanger from U/Side of Steel to Elbow Lug. SH10 Pipe Size All Sizes. Sheet D31
Trapeze Spring Hanger from under side of steel. SH7 Pipe Size All Sizes. Sheet D22
Pedestal Spring SH8 Pipe Size All Sizes. Sheet D23
Spring Hanger from U/Side of Steel to Pipe Lug. SH23 Pipe Size All Sizes. Sheet D32
Spring Hanger from Top of Steel to Pipe Lug. SH24 Pipe Size All Sizes. Sheet D33
Constant Spring Hanger from under side of steel. SH11 Pipe Size 2"-30". Sheet D24
Constant Spring Hanger from under side of steel. SH12 Pipe Size 2"-30". Sheet D24
Constant Spring Hanger from top of steel. SH13 Pipe Size 2"-30". Sheet D25
Constant Spring Hanger from top of steel. SH14 Pipe Size 2"-30". Sheet D25
Constant Spring Hanger from under side of steel. SH15 Pipe Size 2"-30". Sheet D26
Constant Spring Hanger from under side of steel. SH16 Pipe Size 2"-30". Sheet D26
Constant Spring Hanger from top of steel. SH17 Pipe Size 2"-30". Sheet D27
Constant Spring Hanger from top of steel. SH18 Pipe Size 2"-30". Sheet D27
Constant Pedestal Spring SH19 Pipe Size All Sizes. Sheet D28
Constant Pedestal Spring SH20 Pipe Size All Sizes. Sheet D28
Spring Hanger from Top of Steel to Elbow Lug. SH9 Pipe Size All Sizes. Sheet D29
Spring Hanger for Cold Insulated Pipe. SH21 Pipe Size 2"-36" Sheet D30
ATTACHMENT D - PIPE SUPPORT SELECTION CHART (SPRING HANGERS)
SHEET No. J6A
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS SPECIFICATION FOR PIPE SUPPORTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
Horizontal Pipe Support for HVAC Piping-Single Bank. PS15 Pipe Size All Sizes Sht. D34
ATTACHMENT D - PIPE SUPPORT SELECTION CHART (HORIZONTAL PIPE SUPPORT FOR HVAC PIPING-SINGLE BANK)
SHEET No. J6B
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 1
SPECIFICATION FOR PIPE SUPPORTS
Cantilevered Post from Existing Structure. P3 (HEA) Pipe Size All Sizes. Sheet E3
Goal Post from Existing Structure P4 (Angle) Pipe Sizes 1/2" - 2". Sheet E4
Inverted Tee Post P7 (HEA) Pipe Size 4" & below. Sheet E8
Inverted Cantilevered Support P8 (Angle) Pipe Size 2" & below. Sheet E9
Inverted Cantilevered Post P10 Pipe Size All Sizes. Sheet E12
Inverted Goal Post (Piperacks only) P11 Pipe Size All Sizes. Sheet E13
Cantilever Support P21 Pipe Size All Sizes. Sheet E14
Cantilever Support P25 Pipe Size All Sizes. Sheet E16
Braced Cantilever Support P26 Pipe Size All Sizes. Sheet E17
Tee Post from Existing Structure P1 (Angle) Pipe Size 1/2" - 2". Sheet E1
Tee Post from Existing Structure P1 (HEA) Pipe Size All Sizes. Sheet E1
Pedestal from Existing Structure P2 Pipe Size All Sizes. Sheet E2
Cantilevered Post from Existing Structure. P3 (Angle) Pipe Size 1/2" - 2". Sheet E3
Goal Post from Existing Structure P4 (HEA) Pipe Sizes All Sizes. Sheet E5
Post from Existing Structure P5 Pipe Size All Sizes. Sheet E6
Cantilevered Post from Existing Structure. P6 Pipe Size All Sizes. Sheet E7
Inverted Tee Post P7 (Angle) Pipe Size 1/2" - 2". Sheet E8
Inverted Cantilevered Support P8 (HEA) Pipe Size All Sizes. Sheet E9
Inverted Goal Post P9 (Angle) Pipe Size 1/2" - 2". Sheet E10
Inverted Goal Post P9 (HEA) Pipe Size All Sizes. Sheet E11
Cantilever Support P22 Pipe Size All Sizes. Sheet E15
Cantilever Support P23 Pipe Size All Sizes. Sheet E15
Cantilever Support P24 Pipe Size All Sizes. Sheet E16
Braced Cantilever Support P27 Pipe Size All Sizes. Sheet E18
ATTACHMENT E - PIPE SUPPORT SELECTION CHART (TEE POSTS, PEDESTAL, GOAL POSTS, CANTILEVERS, BRACKETS WELDED TO EXIST. STRUCTURE)
SHEET No. J7
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 1
SPECIFICATION FOR PIPE SUPPORTS
Braced Cantilever Support P28 Pipe Size All Sizes. Sheet E18
Braced Cantilever Support P29 Pipe Size All Sizes. Sheet E19
Braced Cantilever Support P30 Pipe Size All Sizes. Sheet E19
Beam Welded to Column P31 Pipe Size All Sizes Sheet E20 & E21
Beam welded to Beam P34 Pipe Size All Sizes Sheet E22 & E23
Beam welded to Beam P35 Pipe Size All Sizes Sheet E22 & E23
Beam welded to Beam P36 Pipe Size All Sizes Sheet E22 & E23
Cantilevered Welded Beam P37 Pipe Size All Sizes Sheet E24 & E25
Beam Welded to Column P32 Pipe Size All Sizes Sheet E20 & E21
Cantilevered Welded Beam P38 Pipe Size All Sizes Sheet E24 & E25
Beam Welded to Column P33 Pipe Size All Sizes Sheet E20 & E21
Cantilevered Welded Beam P39 Pipe Size All Sizes Sheet E24 & E25
Base Plate for Cantilever to concrete P20 Pipe Size All Sizes Sheet E44
ATTACHMENT E - PIPE SUPPORT SELECTION CHART (BRACKETS, WELDED BEAMS TO EXISTING STRUCTURE)
SHEET No. J8
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 1
SPECIFICATION FOR PIPE SUPPORTS
Tee Post from New Paving P41 (Angle) Pipe Size All Sizes. Sheet E26
Tee Post from New Paving P41 (HEA) Pipe Size All Sizes. Sheet E26
Goal Post from New Paving P44 (HEA) Pipe Size 3" & above. Sheet E30
Post from New Paving P45 Pipe Size All Sizes. Sheet E31
Pedestal from New Paving P42 Pipe Size All Sizes. Sheet E27
Welded Cantilevered Post from New Paving. P46 Pipe Size All Sizes. Sheet E32
Cantilevered Post from New Paving P43 (Angle) Pipe Size All Sizes. Sheet E28
Tee Post for Un-Paved Areas P51 (Angle) Pipe Size All Sizes. Sheet E33
Cantilevered Post from New Paving P43 (HEA) Pipe Size All Sizes. Sheet E28
Goal Post from New Paving P44 (Angle) Pipe Size 1/2" - 2". Sheet E29
Tee Post for Un-Paved Areas P51 (HEA) Pipe Size All Sizes. Sheet E33
Pedestal for Un-Paved Areas P52 Pipe Size All Sizes. Sheet E34
SUPPORT DELETED
Cantilevered Post for Un-Paved Areas Cantilevered Post for Un-Paved Areas P53 (Angle) (Augered Pile SGI) P53 (HEA) (Augered Pile SGI) Pipe Size All Sizes. Sheet E35 Pipe Size All Sizes. Sheet E35
Goal Post for Un-Paved Areas P54 (Angle) Pipe Size 1/2" - 2". Sheet E36
Goal Post for Un-Paved Areas P54 (HEA) (Augered Pile SGI) Pipe Size All Sizes. Sheet E37
Post for Un-Paved Areas P55 (Augered Pile SGI) Pipe Size All Sizes. Sheet E38
Welded Cantilevered Post for UnPaved Areas. P56(Augered Pile SGI) Pipe Size All Sizes. Sheet E39
T
T T-Post for Utility Stations, all areas P60 Pipe Size 1/2" - 2" Sheet E40
Pipe Support for Utility Stations from Platforms. P61 Pipe Size 1/2"-2" Sheet E41
Cantilever support for utility stations P62 Pipe Size 1/2" - 2" Sheet E42
Support for steam trap manifolds P63 Pipe Size 1/2" - 2" Sheet E43
ATTACHMENT E - PIPE SUPPORT SELECTION CHART (TEE POSTS, GOAL POSTS, CANTILEVERED POSTS FROM GRADE (SGI) AND UTILITY STATION SUPPORTS )
SHEET NO. J9
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 1
SPECIFICATION FOR PIPE SUPPORTS
T-Post for un-paved areas P71 Pipe Size-All Sizes Sheet E45
Post with plate for un-paved areas P72 Pipe Size-All Sizes Sheet E46
Cantilevered-Post for un-paved areas P73 Pipe Size-All Sizes Sheet E47
Goal-Post for un-paved areas P74 Pipe Size-All Sizes Sheet E48
Post for un-paved areas P75 Pipe Size-All Sizes Sheet E49
ATTACHMENT E - PIPE SUPPORT SELECTION CHART (TEE POSTS, GOAL POSTS, CANTILEVERED POSTS FROM GRADE - SGP )
Welded Cantilevered Post for un-paved areas P76 Pipe size-All Sizes Sheet E50
SHEET NO. J10
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 2
SPECIFICATION FOR PIPE SUPPORTS
Anchor Support from Steel for Vertical Pipe. SB5 Pipe Size ½" - 2". Sheet F3
Anchor Support from Grade for Vertical Pipe. SB6 Pipe Size ½" - 2". Sheet F4
Guide/Support from Steel for Stainless Steel Pipe. SB101 Pipe Size ½" - 2". Sheet F8
Anchor/Support from Steel for Stainless Steel Pipe. SB102 Pipe Size ½" - 2". Sheet F8
Guide/Support from Grade for Stainless Steel Pipe. SB103 Pipe Size ½" - 2". Sheet F9
Guide/Support from Grade for Stainless Steel Pipe. SB106 Pipe Size ½" - 2". Sheet F11
Support and Guide for Vertical Stainless Steel Pipe. SB107 Pipe Size ½" - 2". Sheet F12
Support for Vertical Stainless Steel Pipe. SB108 Pipe Size ½" - 2". Sheet F13
Insulated 'U' Bolt Anchor for Stainless Steel Pipe. UA101 Pipe Size ½" - 2". Sheet F36
Insulated 'U' Bolt Guide for Stainless Steel Pipe. UG101 Pipe Size ½" - 2". Sheet F37
Guide/Support from Exist.Steel SB1 Pipe Size 1/2" - 2". Sheet F1
Anchor/Support from Exist.Steel SB2 Pipe Size ½" - 2". Sheet F1
Support and Guide for Vertical Pipe SB7 Pipe Size ½" - 2". Sheet F5
Support for Vertical Pipe SB8 Pipe Size ½" - 2". Sheet F6
Guide for Vertical Pipe SB9 Pipe Size ½" - 2". Sheet F7
Anchor/Support from Grade for Stainless Steel Pipe. SB104 Pipe Size ½" - 2". Sheet F9
Guide/Support from Steel for Stainless Steel Pipe. SB105 Pipe Size ½" - 2". Sheet F10
Cradle C1,C2,C3,C7,C8,C101, C102,C103,C107,C108 Pipe Size 2"-92". Sheet F32,F33,F42
Cradle C4, C5, C6, C104, 105, C106 Pipe Size 2"-92". Sheet F34 & F35
Guide/Support from Grade SB3 Pipe Size ½" - 2". Sheet F2
Anchor/Support from Grade SB4 Pipe Size ½" - 2". Sheet F2
Lifting Lugs for Piping Break-Out Spools from an elbow LL1. Pipe Size-All Sizes. Sheet F38
ATTACHMENT F - PIPE SUPPORT SELECTION CHART ('U' BOLT GUIDE/ANCHOR, SHEAR LUG)
Guide for Vertical Stainless Steel Pipe. SB109 Pipe Size ½" - 2". Sheet F14
Lifting Lugs for Piping Break-Out Spools from pipe LL2. Pipe Size-All Sizes. Sheet F39 SHEET No. J11A
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 0
SPECIFICATION FOR PIPE SUPPORTS
U-Bolt Anchor UA Pipe Size ½" - 2½" Sheet F26
Welded Gusset Support for Carbon Steel and Stain. Stl. GSW1, GSW101 Pipe Size All Sizes Sheet F40
Welded Gusset Support for Carbon Steel and Stain. Stl. GSW1, GSW101 Pipe Size All Sizes Sheet F40
Welded Gusset Support for Carbon Steel and Stain. Stl. GSW1, GSW101 Pipe Size All Sizes Sheet F40
Welded Gusset Support for Carbon Steel and Stain. Stl. GSW1, GSW101 Pipe Size All Sizes Sheet F40
Bolted Gusset Support for Carbon Steel and Stain. Stl. GSB1, GSB101 Pipe Size All Sizes Sheet F41
Bolted Gusset Support for Carbon Steel and Stain. Stl. GSB1, GSB101 Pipe Size All Sizes Sheet F41
Bolted Gusset Support for Carbon Steel and Stain. Stl. GSB1, GSB101 Pipe Size All Sizes Sheet F41
Bolted Gusset Support for Carbon Steel and Stain. Stl. GSB1, GSB101 Pipe Size All Sizes Sheet F41
Bolted Gusset Support for Carbon Steel and Stain. Stl. GSB1, GSB101 Pipe Size All Sizes Sheet F41
Gusset Support for SP Item No.'s SP-1914 & SP1916. GSW2 Pipe Size All Sizes Sheet F49
Lifting Lugs for Piping Break-Out Spools from an Elbow. LL102 Pipe Sizes All Sizes. Sheet F44
Lifting Lugs for Piping Break-Out Spools from Stain. Stl. Pipe. LL102 Pipe Sizes All Sizes. Sheet F44
U-Bolt Guide for Pipes in the Caustic Sump. UG301 Pipe Size ½ - 2" Sheet F45
U-Bolt Anchor for Pipes in the Caustic Sump. UA301 Pipe Size ½ - 2" Sheet F46
Base Guide for Pipes in Caustic Sump. SB301 Pipe Size ¾" Sheet F47
Base Anchor for Pipes in Caustic Sump. SB302 Pipe Size ¾" Sheet F47
U-Bolt Guide UG Pipe Size ½" - 2½" Sheet F25
ATTACHMENT F - PIPE SUPPORT SELECTION CHART ('U' BOLT GUIDE/ANCHOR, SHEAR LUG)
SHEET No. J11B
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 1
SPECIFICATION FOR PIPE SUPPORTS
Pipe Support Foundation for New Paving. F8N-1 Pipe Size-All Sizes. Sheet G1 & G3
Pipe Support Foundation for New Paving. F8N-2 Pipe Size-All Sizes. Sheet G2 & G3
Pipe Support Foundation from Existing Civil Plinth (Trunnion). F8N-3 Pipe Size-All Sizes. Sheet G12
Pipe Support Foundation from Existing Civil Plinth (post). F8N-4 Pipe Size-All Sizes. Sheet G13
Pipe Support Foundation for posts Unpaved Areas, Light Loads. F9-1 Pipe Size-All Sizes. Sheet G4,G5
Pipe Support Foundation for posts Unpaved Areas, Heavy Loads. F9-2 Pipe Size-All Sizes. Sheet G6,G7
Pipe Support Foundation for trunnions Unpaved Areas, Light Loads. F9-4 Pipe Size-All Sizes. Sheet G8,G9
Pipe Support Foundation for trunnions Unpaved Areas, Light Loads. F9-4 Pipe Size-All Sizes. Sheet G10,G11
Pipe Support foundation for non paved areas for 2" & 3" trunnions and welded posts HEA 100 F9-6 Pipe Size-All Sizes. Sheet G14
Pipe Support foundation for non paved areas for 4" & 6" trunnions F9-7 Pipe Size-All Sizes. Sheet G15
Pipe Support foundation for non paved areas for 8",10' & 12" trunnions F9-8 Pipe Size-All Sizes. Sheet G16
Pipe Support foundation for non paved areas for welded posts HEA160 & HEA200 F9-9 Pipe Size-All Sizes. Sheet G17
ATTACHMENT G - PIPE SUPPORT SELECTION CHART (FOUNDATION TYPES)
Pipe Support foundation for non paved areas for Small Bore Pipe Supports and 70 x 8 Angle Posts F9-10 Pipe Size-1/2" -2". Sheet G18
SHEET No. J12
TENGIZCHEVROIL ASSET DEVELOPMENT PROJECTS
PFD CONTRACT No 571500 DOC No 60-0000-L-SPE-0002 Rev. 1
SPECIFICATION FOR PIPE SUPPORTS
Cold Shoe - Standard Length CS1. Pipe Size ¾"-24". Sheet H1
Directional Anchor for Cold Insulated Pipe. CDA1 Pipe Size 4" - 24". Sheet H5
Hold Down for Uninsulated Pipe. HD1. Pipe Size ¾" - 11/2". Sheet H14
Cold Shoe - Long. CS2. Pipe Size 4"-24". Sheet H2
Cold Double Shoe - Std. Length CS3 Pipe Size 8" 24". Sheet H3
Cold Anchor Shoe - 600 Lg. CAS1. Pipe Size ¾" - 10". Sheet H4
Cold Anchor Shoe - 800 Lg. CAS1. Pipe Size 12" - 24". Sheet H4
Directional Anchor for Cold Insulated Pipe. CDA1 Pipe Size ¾" - 3". Sheet H5
Non-Adjustable Hanger for Cold Insulated Pipe. CH2 Pipe Size ¾" - 24". Sheet H6 & H7
Base Support for Cold Insulated Pipe. CBS1 Trunnion Size 2" - 16". Sheet H8
Trunnion Support for Cold Insulated Pipe. CTS1 Pipe Size 2" - 24". Sheet H9
4-Directional Vertical Guide for Cold Insulated Pipes. CVG1,CVG2,CVG3. Pipe Size 8" - 24". Sheet H10 & H11
2-Directional Vertical Guide for Cold Insulated Pipes. CVG4,CVG5,CVG6. Pipe Size 8" - 24". Sheet H12 & H13
Hold Down for Uninsulated Pipe. HD1. Pipe Size 2" - 12". Sheet H15 & H16
Hold Down Guide for Uninsulated Pipe. HD2. Pipe Size 2" - 12" Sheet H17 & H18
Hold Down for Insulated Pipe Slotted Hold Down for Uninsulated HD3. Pipe. HDS1. Pipe Size 1" - 12" Sheet H19 & H20 Pipe Size 2" - 12". Sheet H21 & H22
Slotted Hold Down for Uninsulated Pipe. HDS2. Pipe Size 2" - 12" Sheet H23 & H24
Anchor Strap for Uninsulated Galvanised Pipe. AS1. Pipe Size 1½" - 8" Sheet H25 & H26
ATTACHMENT H - PIPE SUPPORT SELECTION CHART (COLD SHOES, GUIDES, LINE STOPS, HANGERS, TRUNNIONS)
SHEET No. J13
View more...
Comments