SMU02B V500R002C20 Site Monitoring Unit User Manual

April 20, 2024 | Author: Anonymous | Category: N/A
Share Embed Donate


Short Description

Download SMU02B V500R002C20 Site Monitoring Unit User Manual...

Description

SMU02B Site Monitoring Unit V500R002C20

User Manual

Issue

04

Date

2019-08-30

HUAWEI TECHNOLOGIES CO., LTD.

Copyright © Huawei Technologies Co., Ltd. 2019. All rights reserved. No part of this document may be reproduced or transmitted in any form or by any means without prior written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd. All other trademarks and trade names mentioned in this document are the property of their respective holders.

Notice The purchased products, services and features are stipulated by the contract made between Huawei and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS" without warranties, guarantees or representations of any kind, either express or implied. The information in this document is subject to change without notice. Every effort has been made in the preparation of this document to ensure accuracy of the contents, but all statements, information, and recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd. Address:

Huawei Industrial Base Bantian, Longgang Shenzhen 518129 People's Republic of China

Website:

https://www.huawei.com

Email:

[email protected]

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

i

SMU02B Site Monitoring Unit User Manual

Preface

Preface Purpose This document describes the site monitoring unit SMU in terms of its hardware, liquid crystal display (LCD), web user interface (WebUI), common operations, remote management, and features. This document describes all the functions of the SMU. Some functions are implemented by hardware (such as the DC meter and battery cell detector). If the corresponding hardware is not connected to the SMU, the function is not available. Figures in this manual are for reference only.

Intended Audience This document is intended for: 

Sales engineers



Technical support personnel



Maintenance personnel

Symbol Conventions The symbols that may be found in this document are defined as follows. Symbol

Description Indicates a hazard with a high level of risk which, if not avoided, will result in death or serious injury. Indicates a hazard with a medium level of risk which, if not avoided, could result in death or serious injury. Indicates a hazard with a low level of risk which, if not avoided, could result in minor or moderate injury. Indicates a potentially hazardous situation which, if not avoided, could result in equipment damage, data loss, performance deterioration, or unanticipated results. NOTICE is used to address practices not related to personal injury.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

ii

SMU02B Site Monitoring Unit User Manual

Symbol

Preface

Description Supplements the important information in the main text. NOTE is used to address information not related to personal injury, equipment damage, and environment deterioration.

Change History Changes between document issues are cumulative. The latest document issue contains all the changes made in earlier issues.

Issue 04 (2019-08-30) Deleted contents about the app and WiFi. Added the content to modify the WiFi password.

Issue 03 (2019-02-22) Updated parameter lists.

Issue 02 (2018-05-25) Optimized the SMU replacement procedure. Updated parameter lists.

Issue 01 (2018-01-20) This issue is the first official release. The corresponding software version is V500R002C20.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

iii

SMU02B Site Monitoring Unit User Manual

Contents

Contents Preface ............................................................................................................................................... ii 1 Product Overview ......................................................................................................................... 1 2 Component Description............................................................................................................... 2 2.1 SMU02B ....................................................................................................................................................................... 2 2.2 SMU02B1 ..................................................................................................................................................................... 5 2.3 UIM02C ........................................................................................................................................................................ 9 2.4 NIM02D...................................................................................................................................................................... 12 2.5 NIM01C ...................................................................................................................................................................... 14 2.6 CIM02C ...................................................................................................................................................................... 17

3 User Interfaces ............................................................................................................................. 20 3.1 LCD ............................................................................................................................................................................ 20 3.1.1 Setup Wizard............................................................................................................................................................ 20 3.1.2 Modifying the display language............................................................................................................................... 21 3.1.3 Restart Button .......................................................................................................................................................... 22 3.1.4 Password .................................................................................................................................................................. 22 3.1.5 Standby Screen ........................................................................................................................................................ 22 3.2 WebUI ......................................................................................................................................................................... 23 3.2.1 Connecting a Communications Cable ...................................................................................................................... 23 3.2.2 Setting Parameters ................................................................................................................................................... 24 3.2.3 Logging In to the WebUI ......................................................................................................................................... 24

4 NMS Management ...................................................................................................................... 26 4.1 U2000-SPM Management .......................................................................................................................................... 26 4.1.1 Connecting a communications cable ....................................................................................................................... 26 4.1.2 Setting Parameters ................................................................................................................................................... 27 4.2 NetEco Management .................................................................................................................................................. 27 4.2.1 IP Networking .......................................................................................................................................................... 27 4.2.2 Wireless Networking................................................................................................................................................ 29 4.2.3 BBU In-band Networking ........................................................................................................................................ 32 4.2.4 Logging In to the NetEco......................................................................................................................................... 33 4.3 NMS Management over SNMP .................................................................................................................................. 34 4.3.1 Site Configuration .................................................................................................................................................... 34

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

iv

SMU02B Site Monitoring Unit User Manual

Contents

4.3.1.1 Connecting a Communications Cable ................................................................................................................... 34 4.3.1.2 Setting Parameters ................................................................................................................................................ 34 4.3.2 Setting SNMP Parameters........................................................................................................................................ 35 4.3.3 NMS Commissioning .............................................................................................................................................. 36 4.4 NMS Management over YDN1363 Protocol .............................................................................................................. 36 4.4.1 Connecting a Communications Cable ...................................................................................................................... 36 4.4.2 Setting Parameters ................................................................................................................................................... 37 4.5 NMS Management over Modbus ................................................................................................................................ 38 4.5.1 Connecting a Communications Cable ...................................................................................................................... 38 4.5.2 Setting Parameters ................................................................................................................................................... 38 4.6 NMS Management over TCP-Modbus ....................................................................................................................... 39 4.6.1 Connecting a Communications Cable ...................................................................................................................... 39 4.6.2 Setting Parameters ................................................................................................................................................... 39

5 Common Tasks ............................................................................................................................ 41 5.1 Common Installation Tasks......................................................................................................................................... 41 5.1.1 Using a USB Flash Drive for Site Deployment ....................................................................................................... 41 5.1.2 Setting the Time Zone and Time .............................................................................................................................. 42 5.1.3 Setting Basic Battery Parameters ............................................................................................................................. 42 5.1.4 Setting the Alarm Enable Option, Alarm Severity, and Associated Relays.............................................................. 44 5.1.5 Setting Alarm Parameters for Dry Contacts ............................................................................................................. 44 5.1.6 Setting Rectifier Addresses ...................................................................................................................................... 45 5.2 Common Maintenance Tasks ...................................................................................................................................... 47 5.2.1 Backing Up the Current Settings ............................................................................................................................. 47 5.2.2 Restoring Factory Defaults ...................................................................................................................................... 47 5.2.3 Upgrading Software ................................................................................................................................................. 48 5.2.4 Changing a User Password ...................................................................................................................................... 49 5.2.5 Viewing Dry Contact Association Information ........................................................................................................ 51 5.2.6 Viewing Active Alarms ............................................................................................................................................ 52 5.2.7 Viewing Historical Alarms ....................................................................................................................................... 53 5.2.8 Deleting Devices Failing in Communication ........................................................................................................... 54 5.2.9 Viewing Version Information ................................................................................................................................... 54 5.2.10 Exporting Maintenance Information ...................................................................................................................... 55

6 Hardware Replacement .............................................................................................................. 57 6.1 Replacing an SMU02B ............................................................................................................................................... 57 6.2 Replacing an SMU02B1 ............................................................................................................................................. 58 6.3 Replacing a UIM02C Board ....................................................................................................................................... 60 6.4 Replacing an NIM02D Board ..................................................................................................................................... 62 6.5 Replacing an NIM01C ................................................................................................................................................ 63 6.6 Replacing a CIM02C .................................................................................................................................................. 65

A Parameter Lists ........................................................................................................................... 67 A.1 LCD Menu Hierarchy ................................................................................................................................................ 67 Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

v

SMU02B Site Monitoring Unit User Manual

Contents

A.2 Running Information .................................................................................................................................................. 68 A.3 Setting Wizard............................................................................................................................................................ 86 A.4 Parameters Settings .................................................................................................................................................... 88 A.5 Running Control ...................................................................................................................................................... 148 A.6 Site Maintain ............................................................................................................................................................ 159 A.7 User Management .................................................................................................................................................... 159

B Technical Specifications ......................................................................................................... 160 C FAQ ............................................................................................................................................. 161 C.1 How Do I Prepare the WebUI Operating Environment? .......................................................................................... 161 C.2 What Should I Do If I Forgot the Password? ........................................................................................................... 166

D Acronyms and Abbreviations................................................................................................ 167

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

vi

SMU02B Site Monitoring Unit User Manual

1 Product Overview

1

Product Overview

Figure 1-1 Monitoring unit panel

(1) The communications expansion module

(2) SMU02B/SMU02B1

(3) UIM02C (compatible with the NIM02D)/UIM02D

Table 1-1 Monitoring unit configure Monitoring Unit

Function Introduction

SMU02B/SMU02B1

The SMU02B/SMU02B1 (SMU for short) is a compact high-end monitoring module that monitors and manages Huawei's box-type and cabinet-type power systems. The SMU can manage a site power system through the liquid crystal display (LCD), web user interface (WebUI), and Huawei NetEco.

UIM02C/UIM02D

It provides sensor ports, RS485 ports, and dry contact input and output ports to manage the interior environment of the power system and to report alarms.

NIM02D

It provides sensor ports, and FE ports to connect the NMS or smart device such as an IP camera.

NIM01C

It provides a wireless antenna port and 12 V COM port to manage intelligent electronic locks and cameras and to report alarms.

CIM02C

It provides 12 V COM ports to connect smart devices.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

1

SMU02B Site Monitoring Unit User Manual

2 Component Description

2

Component Description

2.1 SMU02B Panel Figure 2-1 SMU02B panel

(1) Run indicator

(2) Minor alarm indicator

(3) Major alarm indicator

(4) Buttons

(5) USB port (protected by a security mechanism)

(6) RS485/RS232 port

(7) Handle

(8) Locking latch

(9) Fast Ethernet (FE) port

(10) LCD

Indicators Table 2-1 Indicator description Name

Color

Status

Description

Run indicator

Green

Off

The SMU is faulty or has no DC input.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

2

SMU02B Site Monitoring Unit User Manual

Name

2 Component Description

Color

Minor alarm indicator

Yellow

Major alarm indicator

Red

Status

Description

Blinking slowly (0.5 Hz)

The SMU is running properly and communicating with the host properly.

Blinking fast (4 Hz)

The SMU is running properly but fails to communicate with the host properly.

Off

No minor or warning alarm is generated.

Steady on

A minor or warning alarm is generated.

Off

No critical or major alarm is generated.

Steady on

A critical or major alarm is generated.

Buttons Table 2-2 Button description Button

Name

Description

Up

Press Up and Down to scroll through the menus or to change the value of a parameter.

Down Cancel

Returns to the previous menu without saving the settings.

Enter



Enters the main menu from the standby screen.



Enters a submenu from the main menu.



Saves menu settings on a submenu.

NOTE  The LCD screen becomes dark if no button is pressed within 30 seconds. 

You need to log in again if no button is pressed within 1 minute.



To increase or decrease a parameter value quickly, hold down



To restart the SMU, hold down



To increase (or decrease) the LCD contrast ratio, hold down seconds.

and

or

.

for 10 seconds. and

(or

) for 2

USB Ports You can quickly deploy a site, import and export configuration files, export running logs, and upgrade software by inserting the USB flash drive that is specially used for site deployment into the USB port.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

3

SMU02B Site Monitoring Unit User Manual

2 Component Description

After installing the specific WiFi module using the USB port, you can access the WebUI locally, which facilitates operations.

Using WiFi modules provided by another vendor may cause data loss or function exception. Consequences arising from this will not be borne by Huawei.

Communications Ports Table 2-3 Communication port description Communications Port

Communications Parameter

Communications Protocol

FE

10/100M autonegotiation

HTTPS, NetEco protocol, SNMP and TCP-Modbus protocol

RS485/RS232

Baud rate: 1200bit/s, 2400bit/s, 4800bit/s, 9600bit/s, 14400bit/s, 19200bit/s, 115200bit/s

Master/slave protocol, YDN protocol, and Modbus protocol

NOTE All these ports are protected by a security mechanism.

Figure 2-2 FE/RS485/RS232 port pins

Table 2-4 Pin definitions for the FE port Pin

Signal

Description

1

TX+

Transmits data over FE.

2

TX-

3

RX+

6

RX-

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

Receives data over FE.

4

SMU02B Site Monitoring Unit User Manual

2 Component Description

Pin

Signal

Description

4, 5, 7, 8

NA

-

Table 2-5 Pin definitions for the RS485/RS232 port Pin

Signal

Description

1

TX+

Transmits data over RS485.

2

TX-

4

RX+

5

RX-

3

RX232

Receives data over RS232.

7

TX232

Transmits data over RS232.

6

PGND

Connects to the ground.

8

NA



Receives data over RS485.

2.2 SMU02B1 Panel Figure 2-3 SMU02B1 panel

(1) SD card slot

(2) Run indicator

(3) Minor alarm indicator

(4) Major alarm indicator

(5) Buttons

(6) USB port (protected by a security mechanism)

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

5

SMU02B Site Monitoring Unit User Manual

2 Component Description

(7) RS485/RS232 port

(8) Fast Ethernet (FE) port

(9) LCD

Indicators Table 2-6 Indicator description Name

Color

Status

Description

Run indicator

Green

Off

The SMU is faulty or has no DC input.

Blinking slowly (0.5 Hz)

The SMU is running properly and communicating with the host properly.

Blinking fast (4 Hz)

The SMU is running properly but fails to communicate with the host properly.

Off

No minor or warning alarm is generated.

Steady on

A minor or warning alarm is generated.

Off

No critical or major alarm is generated.

Steady on

A critical or major alarm is generated.

Minor alarm indicator

Yellow

Major alarm indicator

Red

Buttons Table 2-7 Button description Button

Name

Description

Up

Press Up and Down to scroll through the menus or to change the value of a parameter.

Down

Issue 04 (2019-08-30)

Cancel

Returns to the previous menu without saving the settings.

Enter



Enters the main menu from the standby screen.



Enters a submenu from the main menu.



Saves menu settings on a submenu.

Copyright © Huawei Technologies Co., Ltd.

6

SMU02B Site Monitoring Unit User Manual

Button

2 Component Description

Name

Description

NOTE  The LCD screen becomes dark if no button is pressed within 30 seconds. 

You need to log in again if no button is pressed within 1 minute.



To increase or decrease a parameter value quickly, hold down



To restart the SMU, hold down



To increase (or decrease) the LCD contrast ratio, hold down seconds.

and

or

.

for 10 seconds. and

(or

) for 2

SD Card Slot SD card is used for storing the camera capture images, maximum support 32G capacity.

USB Ports You can quickly deploy a site, import and export configuration files, export running logs, and upgrade software by inserting the USB flash drive that is specially used for site deployment into the USB port. After installing the specific WiFi module using the USB port, you can access the WebUI locally, which facilitates operations.

Using WiFi modules provided by another vendor may cause data loss or function exception. Consequences arising from this will not be borne by Huawei. After a wireless module is connected to the USB port, the SMU can communicate with the NMS in wireless mode.

Communications Ports Table 2-8 Communications port description Communications Port

Communications Parameter

Communications Protocol

FE

10/100M autonegotiation

HTTPS, NetEco protocol, SNMP and TCP-Modbus protocol

RS485/RS232

Baud rate: 1200bit/s, 2400bit/s, 4800bit/s, 9600bit/s, 14400bit/s, 19200bit/s, 115200bit/s

Master/slave protocol, YDN protocol, and Modbus protocol

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

7

SMU02B Site Monitoring Unit User Manual

2 Component Description

Communications Port

Communications Parameter

Communications Protocol

NOTE All these ports are protected by a security mechanism.

Figure 2-4 FE/RS485/RS232 port pins

Table 2-9 Pin definitions for the FE port Pin

Signal

Description

1

TX+

Transmits data over FE.

2

TX-

3

RX+

6

RX-

4, 5, 7, 8

NA

Receives data over FE.

-

Table 2-10 Pin definitions for the RS485/RS232 port Pin

Signal

Description

1

TX+

Transmits data over RS485.

2

TX-

4

RX+

5

RX-

3

RX232

Receives data over RS232.

7

TX232

Transmits data over RS232.

6

PGND

Connects to the ground.

8

NA



Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

Receives data over RS485.

8

SMU02B Site Monitoring Unit User Manual

2 Component Description

2.3 UIM02C Panel Figure 2-5 Panel

(1) Communications port

(2) Dry contact output ports

(3) Dry contact input ports

(4) Sensor ports

Port Description Table 2-11 Port description Port Type

Silk Screen

Remarks

Sensor ports

TEM-HUM

Ambient temperature and humidity sensor

WATER

Water sensor

TEMP1

Temperature sensor 1

TEMP2

Temperature sensor 2

GATE

Door status sensor

SMOKE

Smoke sensor

BTEMP

Battery temperature sensor

DIN1

Dry contact input 1

DIN2

Dry contact input 2

DIN3

Dry contact input 3

DIN4

Dry contact input 4

DIN5

Dry contact input 5

DIN6

Dry contact input 6

ALM1

Dry contact output 1

ALM2

Dry contact output 2

ALM3

Dry contact output 3

Dry contact input ports

Dry contact output ports

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

9

SMU02B Site Monitoring Unit User Manual

2 Component Description

Port Type

Communications port

Silk Screen

Remarks

ALM4

Dry contact output 4

ALM5

Dry contact output 5

ALM6

Dry contact output 6

ALM7

Dry contact output 7

ALM8

Dry contact output 8

COM

RS485

Communications Port Table 2-12 COM port description Communications Port

Communications Parameter

Communications Protocol

Purpose

COM

Baud rate: 1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s, 14400 bit/s, 19200 bit/s, 115200 bit/s

Master/slave, Modbus and YDN1363 protocols

Connects to a downstream device, such as the intelligent battery detector or intelligent air conditioner.

NOTE The COM port is protected by a security mechanism.

Figure 2-6 Pins in the COM port

Table 2-13 COM port pin definitions Pin

Signal

Remarks

1

RX+

Receives data over RS485.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

10

SMU02B Site Monitoring Unit User Manual

2 Component Description

Pin

Signal

Remarks

2

RX-

4

TX+

5

TX-

6

PGND

Protective ground

3, 7, 8

NA

-

Transmits data over RS485.

Sensor Ports Figure 2-7 Pins in sensor ports

Table 2-14 UIM02C pin definitions Silk Screen

No.

Pins

TEM-HUM

1

12 V

2

ENV_TEMP

3

12 V

4

ENV_HUM

1

12 V

2

WATER

3

GND

4

-

1

GND

2

TEMP1

WATER

TEMP1

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

11

SMU02B Site Monitoring Unit User Manual

2 Component Description

Silk Screen

No.

Pins

TEMP2

1

GND

2

TEMP2

1

GATE+

2

GATE-

1

SMOKE

2

12 V

1

GND

2

BTEMP

GATE

SMOKE

BTEMP

2.4 NIM02D Panel Figure 2-8 Panel

(1) FE cascade port

(2) Signal Input ports/12 V power port

(3) FE ports

Ports Table 2-15 Port Description Port

Function

Communications Parameter

FE_CASCADE

Connects to the FE port on the SMU.

10/100M autonegotiation

FE1/2/3/4

Connects to an NMS or a smart device such as an IP camera.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

12

SMU02B Site Monitoring Unit User Manual

2 Component Description

Port

Function

Communications Parameter

CH1/2/3/4/5/6

Signal Input ports.

-

12 V

12 V power output.

-

Remarks: 

The FE ports are protected by a security mechanism.



CH1/2/3/4 supports AI (4–20 mA), AI (0–10 V DC), or DI detection. The function can be used by hardware jumper or software parameter configuration.



CH5/6 supports only AI (4–20 mA) detection by default.

Figure 2-9 Pins in an FE communications port

Table 2-16 Pin definitions for FE communications ports Pin

Signal

Description

1

TX+

Transmits data over FE.

2

TX-

3

RX+

6

RX-

4, 5, 7 and 8

NA

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

Receives data over FE.

-

13

SMU02B Site Monitoring Unit User Manual

2 Component Description

2.5 NIM01C Panel Figure 2-10 NIM01C panel

(1) SIM card slots (2 PCS)

(2) 3G indicator (unavailable if the module does not provide 3G functions)

(3) Alarm indicator

(4) Run indicator

(5) ANT communications port (unavailable if the module does not provide 3G functions)

(6) COM1 port

(7) COM2 port

(8) COM3/CAN port

(9) COM4 port

(10) Handle

-

-

Indicators Table 2-17 Indicator description Indicator

Color

Status

Description

3G indicator

Green

Steady on

The dial-up connection is in the data service state.

Blinking at a period of 2s (on for 0.1s and then off for 1.9s)

The network has been registered.

Blinking at a period of 2s (on for 0.1s, off for 0.1s, on for 0.1s and then off for 1.7s)

A network is in search, or no network is connected.

Off

No alarm is generated.

Steady on

An alarm is generated.

Alarm indicator

Issue 04 (2019-08-30)

Red

Copyright © Huawei Technologies Co., Ltd.

14

SMU02B Site Monitoring Unit User Manual

2 Component Description

Indicator

Color

Status

Description

Run indicator

Green

Off

The NIM01C is not running because it is faulty or has no DC input.

Blinking at 0.5 Hz

The NIM01C is running and communicating with the host properly.

Blinking at 4 Hz

The NIM01C is running properly, but fails to communicate with the host.

Communications Ports Table 2-18 Communications port description Communications Port

Communications Parameter

Description

COM1 port

Baud rate: 1200bit/s, 2400bit/s, 4800bit/s, 9600bit/s, 14400bit/s, 19200bit/s, 115200bit/s

Supports master/slave protocols and Modbus.

Baud rate: 1200bit/s, 2400bit/s, 4800bit/s, 9600bit/s, 14400bit/s, 19200bit/s, 115200bit/s

Supports master/slave protocols and Modbus.

Baud rate: 1200bit/s, 2400bit/s, 4800bit/s, 9600bit/s, 14400bit/s, 19200bit/s, 115200bit/s

COM3: Supports master/slave protocols and Modbus.

COM2 port

COM3/CAN port

Supplies 12 V power.

Supplies 12 V power.

CAN: Supports CAN protocol. COM4 port

Baud rate: 1200bit/s, 2400bit/s, 4800bit/s, 9600bit/s, 14400bit/s, 19200bit/s, 115200bit/s

Supports Modbus.

Figure 2-11 Pins in the COM1, COM2, and COM3 ports

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

15

SMU02B Site Monitoring Unit User Manual

2 Component Description

Table 2-19 Description for the pins in the COM1 and COM2 ports Pin

Signal

Description

1

RS485+

RS485 data +

2

RS485-

RS485 data -

3

12 V

Supply power

4

RS485+

RS485 data +

5

RS485-

RS485 data -

6

NA

-

7

NA

-

8

GND

Grounded

Table 2-20 Description for the COM3/CAN port pins Pin

Signal

Description

1

RX+

Receives data over RS485.

2

RX-

3

NA



4

TX+

Sends data over RS485.

5

TX-

6

NA



7

CANH

CAN high level signal.

8

CANL

CAN low level signal.

Table 2-21 Description for the COM4 port pins Silk Screen

Signal

Description

R+

RS485+

RS485 data +

R-

RS485-

RS485 data -

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

16

SMU02B Site Monitoring Unit User Manual

2 Component Description

2.6 CIM02C Panel Figure 2-12 CIM02C panel

(1) COM1 port

(2) COM2 port

(3) COM3/COM4 port

(4) 12 V power port

(5) COM5 port

(6) Handle

Communications Ports Table 2-22 Communications port description Communications Port

Description

Communications Parameter

COM1 port

Supports RS485.

Baud rate

12 V power supply, maximum output 1.5 A.

Default value: 9600 bit/s

Connects to a smart device. COM2 port

Supports RS485.

Options: 1200 bit/s, 2400 bit/s, 4800 bit/s, 9600 bit/s, 14400 bit/s, 19200 bit/s, 115200 bit/s

12 V power supply, maximum output 1.5 A. Connects to a smart device. COM3/COM4 port

COM3 supports RS485. COM4 supports RS232 and CAN. RS232 is used by default, which can be changed to CAN by using a jumper. Connects to a third-party power supply.

COM5 port

Supports RS232 and RS485. RS485 is used by default, which can be changed to RS232 by using a jumper. Connects to an air conditioner.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

17

SMU02B Site Monitoring Unit User Manual

2 Component Description

Figure 2-13 Pins in the COM1, COM2, or COM3/COM4 port

Table 2-23 Pin definitions for the COM1 and COM2 ports Pin

Single

Description

1

RS485+

RS485 data +

2

RS485-

RS485 data -

3

12 V

Power supply

4

RS485+

RS485 data +

5

RS485-

RS485 data -

6

NA



7

NA



8

GND

Ground

Table 2-24 Pin definitions for the COM3/4 port Pin

Single

Description

1

RS485_RX+

Receives data over RS485.

2

RS485_RX-

3

RS232_RXD

Receives data over RS232.

4

RS485_TX+

Transmits data over RS485.

5

RS485_TX-

6

NA

-

7

CANH/RS232_TXD

CAN high level signal/Transmits data over RS232.

8

CANL

CAN low level signal.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

18

SMU02B Site Monitoring Unit User Manual

2 Component Description

Table 2-25 Pin definitions for the COM5 port Silk Screen

Signal

Description

R+/TX

RS485+/RS232_TXD

RS485 data + or transmits data over RS232.

R-/RX

RS485-/RS232_RXD

RS485 data - or receives data over RS232.

GND

GND

Ground.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

19

SMU02B Site Monitoring Unit User Manual

3 User Interfaces

3

User Interfaces

3.1 LCD 3.1.1 Setup Wizard After the SMU is powered on for the first time, the Setup Wizard page is displayed, as shown in the following figure.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

20

SMU02B Site Monitoring Unit User Manual

3 User Interfaces

Figure 3-1 Setup wizard

3.1.2 Modifying the display language The monitoring unit supports English, Chinese, French, Spanish, Portuguese, Russian, Italian, German, Turkish, and Japanese.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

21

SMU02B Site Monitoring Unit User Manual

3 User Interfaces

When the monitoring unit is running properly, choose the following menus to select a language. Table 3-1 Modifying the display language Main Menu

Second-Level Menu

Third-Level Menu

Setting

Parameters Settings

Local Parameters

Language

Select a desired language.

3.1.3 Restart Button To restart the monitoring unit, hold down

and

for 10s.

3.1.4 Password Two-level password management supported by the LCD, two user levels are available. Table 3-2 Two-level password management Level

Operation Permission

Password

engineer

All permissions except for changing the administrator password and resetting the web password.

000001

admin

Has all operation permissions.

012589 NOTE The admin password can only be used by the administrator. It must not be provided for third-party maintenance personnel.

3.1.5 Standby Screen The following figure shows the monitoring unit standby screen, which displays basic power system information, including the bus bar voltage, total load current, and total battery current.

The parameter values in the figures are for reference only.

Figure 3-2 Standby screen

The standby screen is displayed if no button is pressed within 1 minute on any screen.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

22

SMU02B Site Monitoring Unit User Manual

3 User Interfaces

On the standby screen, you can press , , and to enter the version information screen, basic information screen, and main menu screen respectively, as shown in the following figure. Figure 3-3 Standby screen operations

Main menu include active alarm, running information, setting wizard, parameters settings, running control, site maintain and user management.

3.2 WebUI 3.2.1 Connecting a Communications Cable Procedure Step 1 Preparing the Operating Environment, see C FAQ. Step 2 Connect the FE port on the SMU by using a network cable, as shown in Figure 3-4. Figure 3-4 Connecting a Communications Cable

(1) FE port

----End

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

23

SMU02B Site Monitoring Unit User Manual

3 User Interfaces

3.2.2 Setting Parameters Procedure Step 1 Apply to the site or equipment room network administrator for a fixed IP address. Step 2 Set the IP address, subnet mask, and gateway address on the LCD. Table 3-3 IP parameters Main Menu

Second-Level Menu

Third-Level Menu

Default Value

Setting Value

Setting Wizard

Network Parameters

IP Address

192.168.0.10

Set this parameter according to the address provided by the network administrator.

Subnet Mask

255.255.255.0

Set this parameter according to the subnet mask provided by the network administrator.

Default Gateway

192.168.0.1

Set this parameter according to the gateway address provided by the network administrator.

----End

3.2.3 Logging In to the WebUI Procedure Step 1 Set the PC IP address in the same network segment as the SMU IP address. For example, if the SMU has an IP address of 192.168.0.10, a subnet mask of 255.255.255.0, and a default gateway of 192.168.0.1, set the IP address to 192.168.0.11, subnet mask to 255.255.255.0, and default gateway to 192.168.0.1 on the PC. Step 2 Enter https://monitoring unit local IP address (for example, https://192.168.0.10) in the address box of the browser, and then press Enter to access the WebUI login page.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

24

SMU02B Site Monitoring Unit User Manual

3 User Interfaces

Figure 3-5 WebUI login page

The preset user names include admin, engineer, and operator, and the preset password is Changeme. The user names are intended for administrators, engineers, and operators respectively. Change the preset password when you first log in to ensure system security. The method about how to change the password, see 5.2.4 Changing a User Password.

----End

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

25

SMU02B Site Monitoring Unit User Manual

4 NMS Management

4

NMS Management

4.1 U2000-SPM Management 4.1.1 Connecting a communications cable Procedure Step 1 Connect one end of a network cable to the RS485/RS232 port on the SMU. Step 2 Connect the other end to the MON0 or MON1 port on the BBU. Figure 4-1 Connecting a communications cable

(1) RS485/RS232 port

(2) MON1 port

----End

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

26

SMU02B Site Monitoring Unit User Manual

4 NMS Management

4.1.2 Setting Parameters Step 1 On the LCD, check that the port mode, protocol type, baud rate and communication address are the same as the default values in the following table. Table 4-1 Communications parameters Main Menu

Second-Level Menu

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu

Setting Value

Parameters Settings

Comm. Parameters

Serial Port

Northbound

Port Mode

Manual

Protocol Type

M/S Protocol

Baud Rate

-

9600

Comm. Address

-

3

M/S Protocol

----End

4.2 NetEco Management 4.2.1 IP Networking Step 1 Connect a network cable to the FE port on the SMU. Figure 4-2 Connecting a communications cable

(1) FE Port

Step 2 Apply to the site or equipment room network administrator for a fixed IP address. Step 3 Set the IP address, subnet mask, and gateway address on the LCD.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

27

SMU02B Site Monitoring Unit User Manual

4 NMS Management

Table 4-2 IP parameters Main Menu

Second-Level Menu

Third-Level Menu

Default Value

Setting

Setting Wizard

Network Parameters

IP Address

192.168.0.10

Set this parameter based on the address assigned by the network administrator.

Subnet Mask

255.255.255.0

Set this parameter based on the address assigned by the network administrator.

Default Gateway

192.168.0.1

Set this parameter based on the address assigned by the network administrator.

Step 4 Set IP addresses and port numbers for the active and standby NetEco servers on the LCD. Table 4-3 NetEco parameters Main Menu

Second-Level Menu

Third-Level Menu

Fourth-Level Menu

Default Value

Setting

Parameters Settings

Comm. Parameters

Network Parameters

NetEco Primary IP

192.168.0.10

Set this parameter to the IP address of the active NetEco server.

NetEco Backup IP

192.168.0.10

Set this parameter to the IP address of the standby NetEco server.

NetEco Port Number

31220

31220 NOTE Please contact Huawei technical support if you need change the port number.

----End

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

28

SMU02B Site Monitoring Unit User Manual

4 NMS Management

4.2.2 Wireless Networking Installing a Wireless Antenna Step 1 Insert the SIM card into the SIM card slot in the communications expansion board. The SIM card should support GSM and WCDMA standards and enable the PS (data service) functions. Step 2 Connect the GPRS antenna to the ANT port on the NIM01C. Figure 4-3 Connection between a GPRS antenna and an NIM01C

----End

Setting Communications Parameters Step 1 Check whether the default wireless communications parameters on the LCD are consistent with the communication configurations of the carrier network that the SIM card belongs to. If they are inconsistent, modify the parameters according to the actual configurations of the carrier network. Table 4-4 Checking wireless communication parameters Main Menu

Second-Level Menu

Third-Level Menu

Fourth-Level Menu

Default Value

Value Range

Parameters Settings

Comm. Parameters

Mobile Data

Carrier Operator

Automatic

Automatic, Others

SIMn Acc Point Name

3GNET

A maximum of 28 characters, including lowercase English letters (a-z),

NOTE This parameter is displayed only when Carrier Operator is

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

29

SMU02B Site Monitoring Unit User Manual

Main Menu

4 NMS Management

Second-Level Menu

Third-Level Menu

Fourth-Level Menu

Default Value

set to Others.

SIMn Access Point No

*99#

NOTE This parameter is displayed only when Carrier Operator is set to Others.

SIMn User Name

Value Range uppercase English letters (A-Z), digits (0-9), and special characters (@_#*-.).

3GNET

NOTE This parameter is displayed only when Carrier Operator is set to Others.

SIMn User Password NOTE This parameter is displayed only when Carrier Operator is set to Others.

-

A maximum of 27 characters, including lowercase English letters (a-z), uppercase English letters (A-Z), digits (0-9), and special characters (@_#-.). It is recommended that the password contain at least two types of characters and the length exceed six characters.

Step 2 Set IP addresses and port numbers for the active and standby NetEco servers on the LCD.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

30

SMU02B Site Monitoring Unit User Manual

4 NMS Management

Table 4-5 Setting NetEco parameters Main Menu

Second-Level Menu

Third-Level Menu

Fourth-Level Menu

Default Value

Setting

Parameters Settings

Comm. Parameters

Network Parameters

NetEco Primary IP

192.168.0.10

Set this parameter to the IP address of the active NetEco server.

NetEco Backup IP

192.168.0.10

Set this parameter to the IP address of the standby NetEco server.

NetEco Port Number

31220

31220 NOTE Please contact Huawei technical support if you need change the port number.

----End

Verifying Network Connection Status After the SIM card and wireless antenna are installed, the SIM card automatically accesses the wireless network in dial-up mode. You can view the network connection status on the LCD. Table 4-6 Verifying the network connection status Main Menu

Second-Level Menu

Third-Level Menu

Remarks

Running Information

Mobile Data Info

Connection Status

Connected indicates successful dial-up and normal network connection.

The following table shows general requirements of GPRS Network performance. If the network performance is worse than the requirements, communication interruption may happen.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

31

SMU02B Site Monitoring Unit User Manual

4 NMS Management

Table 4-7 GPRS main performance index Index

Description

Reference

Received signal strength indicator (RSSI)

If the probability of received signal code power (RSCP) greater than –89 dBm is less than 95%, the cell coverage of wireless signals is poor.

P (RSCP > –89 dBm) 95%

Packet Data Protocol (PDP) activation success rate

PDP activation success rate = Successful number of PDP activation/Total number of PDP activation

95%

Attach attachment success rate

Attach attachment success rate = Successful number of PDP attachment/Total number of PDP attachment

95%

Handover success rate

Handover success rate = Successful number of GPRS handover/Total number of GPRS handover

98%

4.2.3 BBU In-band Networking Step 1 Connect one end of a network cable to the RS485/RS232 port on the SMU. Step 2 Connect the other end to the MON0 or MON1 port on the BBU. Figure 4-4 Connecting a communications cable

(1) RS485/RS232 Port

Issue 04 (2019-08-30)

(2) MON1 Port

Copyright © Huawei Technologies Co., Ltd.

32

SMU02B Site Monitoring Unit User Manual

4 NMS Management

Step 3 Set the port mode, communications protocol type, baud rate, and communications address on the LCD. Table 4-8 Setting communications parameters Main Menu

Second-Level Menu

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu

Setting

Parameters Settings

Comm. Parameters

Serial Port

Northbound

Port Mode

Manual

Protocol Type

M/S Protocol

Baud Rate

-

9600

Comm. Address

-

3

M/S Protocol

----End

4.2.4 Logging In to the NetEco Procedure Step 1 Enter https: //NetEco IP address: port number for NetEco login (for example, https://10.10.10.1:31943) in the address box of the browser and press Enter. The NetEco login page is displayed. Figure 4-5 NetEco login page

Step 2 Enter the correct user name and password and click Log In.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

33

SMU02B Site Monitoring Unit User Manual

4 NMS Management

To obtain the NetEco user name and password, contact the site or equipment room network administrator.

4.3 NMS Management over SNMP 4.3.1 Site Configuration 4.3.1.1 Connecting a Communications Cable Step 1 Connect the FE port on the SMU by using a network cable, as shown in Figure 4-6. Figure 4-6 Connecting a Communications Cable

(1) FE port

----End

4.3.1.2 Setting Parameters Procedure Step 1 Apply to the site or equipment room network administrator for a fixed IP address. Step 2 Set the IP address, subnet mask, and gateway on the LCD, as shown in Table 4-9. Table 4-9 IP parameters Main Menu

Second-Level Menu

Third-Level Menu

Default Value

Setting Value

Setting Wizard

Network Parameters

IP Address

192.168.0.10

Set this parameter according to the address provided by the network administrator.

Subnet Mask

255.255.255. 0

Set this parameter according to the

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

34

SMU02B Site Monitoring Unit User Manual

4 NMS Management

Second-Level Menu

Main Menu

Third-Level Menu

Default Value

Setting Value subnet mask provided by the network administrator.

Default Gateway

192.168.0.1

Set this parameter according to the gateway address provided by the network administrator.

----End

4.3.2 Setting SNMP Parameters Prerequisites You can set SNMP parameters remotely or locally on the WebUI.

Before setting SNMP parameters, obtain the information listed in Table 4-10 from the SNMP NMS. Table 4-10 Information obtained from the NMS Item

Description

SNMP version

SNMP version and port number used for communication between the SMU and NMS. The SNMP version can be SNMPv1, SNMPv2c, SNMPv3.

SNMP Port Number Read Community Name Write Community Name User Name MD5/SHA Password

If you use SNMPv1 or SNMPv2c, enter the read and write community names that comply with the NMS. Otherwise, the SMU will not connect to the NMS. The read community name must be different from the write community name. To enhance the security, you need a user name and password for authentication if you use SNMPv3. After the authentication succeeds, the SMU can communicate with the NMS.

DES/AES Password Trap Target Address

IP address and port number used for reporting alarm trap packets.

Trap Port Trap Community

Issue 04 (2019-08-30)

If you use SNMPv1 or SNMPv2c, community name used for reporting alarm trap packets.

Copyright © Huawei Technologies Co., Ltd.

35

SMU02B Site Monitoring Unit User Manual

4 NMS Management

Procedure Step 1 Log in to the WebUI.

The preset user name is admin, and the preset password is Changeme.

Step 2 Access the System Settings page and set SNMP. 

There are two or more NMSs and the SNMP versions have both SNMPv1 or SNMPv2c and SNMPv3: Set SNMP Version to ALL in SNMP, and set SNMP Port Number, Read Community Name, and Write Community Name. Then click Add in SNMPv3, and set User Name, MD5/SHA Password, and DES/AES Password. Then click Confirm.



SNMPv1 or SNMPv2c: Set SNMP Version to SNMPv1&SNMPv2c in SNMP,and set SNMP Port Number, Read Community Name, and Write Community Name. Then click Confirm.



SNMPv3: Set SNMP Version to SNMPv3 in SNMP, click Add in SNMPv3, and set User Name, MD5/SHA Password, and DES/AES Password. Then click Confirm.

Step 3 In SNMP Trap, click Add. 

If the SNMP Version is SNMPv1 or SNMPv2c, set Trap Target Address and Trap Port and set Trap community.



If the SNMP Version is SNMPv3, set Trap Target Address and Trap Port and SNMPv3 User Name.

SNMP Version in this place can be different from the version in Step 2.

Step 4 In Mib files, click Export to export the Mib file and then import it into the NMS.

If there is only one NMS, perform Step 4 once only.

----End

4.3.3 NMS Commissioning You can query the power system operating status, active alarms, and the names of user-defined dry contact inputs, and configure dry contact outputs on the network management system (NMS) that is connected over the Simple Network Management Protocol (SNMP).

4.4 NMS Management over YDN1363 Protocol 4.4.1 Connecting a Communications Cable Step 1 Connect one end of a network cable to the RS485/RS232 port on the SMU. Step 2 Connect the other end to the corresponding port on the power and environment monitoring device, as shown in Figure 4-7.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

36

SMU02B Site Monitoring Unit User Manual

4 NMS Management

Figure 4-7 Connecting a communications cable

(1) Power and environment network management system (NMS)

(2) Power and environment monitoring device

(3) RS485/RS232 port on the SMU

----End

4.4.2 Setting Parameters Step 1 On the LCD, check that the port mode, protocol type, baud rate and communication address are the same as the default values in Table 4-11. Table 4-11 Communications parameters Main Menu

Second-Level Menu

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu

Default Value

Parameters Settings

Comm. Parameters

Serial Port

North485bound

Port Mode

Manual

Protocol Type

YDN1363 Protocol

Baud Rate

-

9600

Comm. Address

-

1

YDN1363 Protocol

----End

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

37

SMU02B Site Monitoring Unit User Manual

4 NMS Management

4.5 NMS Management over Modbus 4.5.1 Connecting a Communications Cable Step 1 Connect one end of a network cable to the RS485/RS232 port on the SMU. Step 2 Connect the other end to the corresponding port on the third-party device, as shown in Figure 4-8. Figure 4-8 Connecting a communications cable

(1) Network management device

(2) Third-party device

(3) RS485/RS232 port on the SMU

4.5.2 Setting Parameters Step 1 On the LCD, check that the port mode, protocol type, baud rate and communication address are the same as the default values in Table 4-12. Table 4-12 Communications parameters Main Menu

Second-Level Menu

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu

Default Value

Parameters Settings

Comm. Parameters

Serial Port

Northbound

Port Mode

Manual

Protocol Type

Modbus Protocol

Baud Rate

-

9600

Comm. Address

-

33

Modbus Protocol

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

38

SMU02B Site Monitoring Unit User Manual

4 NMS Management

4.6 NMS Management over TCP-Modbus 4.6.1 Connecting a Communications Cable Step 1 Connect the FE port on the SMU by using a network cable, as shown in Figure 4-9. Figure 4-9 Connecting a Communications Cable

(1) FE port

----End

4.6.2 Setting Parameters Procedure Step 1 Log in to the WebUI.

The preset user name is admin, and the preset password is Changeme.

Step 2 Choose System Settings > TCP-Modbus Config and set parameters. For details, see Table 4-13. Table 4-13 Communications parameters Parameter

Value

Setting Method

TCP-Modbus link Mode

Sever, Client, Sever+Client



Server: The SMU works as the server and can connect to one client for communication.



Client: The SMU works as a client and can connect to the remote server for communication.



Server+Client: The SMU works as the server and can connect to one client for communication. At the same time, the SMU works as a client and can connect to the remote server for communication.

TCP-Modbus SSL server

Issue 04 (2019-08-30)

Enable, Disable

The default value is Enable. NOTE

Copyright © Huawei Technologies Co., Ltd.

39

SMU02B Site Monitoring Unit User Manual

4 NMS Management

Parameter

Value

Setting Method This parameter is displayed only when TCP-Modbus link Mode is set to Server and Server+Client.

enable TCP-Modbus SSL client enable

Enable, Disable

TCP-Modbus client IP address

-

The default value is Enable. NOTE This parameter is displayed only when TCP-Modbus link Mode is set to Client and Server+Client.

The default value is 192.168.0.10. Set the NMS IP address based on the actual situation. NOTE This parameter is displayed only when TCP-Modbus link Mode is set to Client and Server+Client.

TCP-Modbus client IP port

-

The default value is 16100. It is recommended that you not change the value. If necessary, set this parameter based on the actual situation. NOTE This parameter is displayed only when TCP-Modbus link Mode is set to Client and Server+Client.

Step 3 Upload CA certificate file, local certificate file and key file. ----End

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

40

SMU02B Site Monitoring Unit User Manual

5 Common Tasks

5

Common Tasks

5.1 Common Installation Tasks 5.1.1 Using a USB Flash Drive for Site Deployment Prerequisites 

The USB flash drive stores the upgrade and configuration files required for site deployment.



The upgrade and configuration files must be stored in the root directory of the USB flash drive. Otherwise, the SMU cannot read the configuration file.



The configuration file name starts with Config and ends with .tar.gz or .zip.

The file name should have less than 80 characters, cannot start with fault, and cannot contain single or double quotation marks, spaces, or the following special characters:< \ > | ; $ & ` ( ) % 

The USB flash drive and file have been scanned to ensure that they are not infected with viruses.

Context You can copy site configuration parameters from the LCD or WebUI to a USB flash drive to rapidly set up other sites.



Export configuration parameters from the LCD to a USB flash drive: On the LCD, choose Site Maintain > Export File to USB to export the configurations of the current operating system into a configuration file and save the file in a USB flash drive.



For details about how to export configuration parameters from the WebUI to a USB flash drive, see 5.2.1 Backing Up the Current Settings.

Procedure Step 1 Insert the USB flash drive into the SMU USB port. The LCD displays the Site Maintain screen.

When visiting Site Maintain on the LCD, enter the preset password 000001.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

41

SMU02B Site Monitoring Unit User Manual

5 Common Tasks

Step 2 Choose Site Maintain > U Disk Upgrade/Cfg. Step 3 Select the upgrade or configuration file stored in the root directory of the USB flash drive, and tap

. Back up first. Go on? is displayed.

Step 4 Select YES and tap , Package Classifying is displayed and Config Processing is displayed, indicating that upgrade or data configuration is in progress.

The configuration or upgrade process will take about 5 minutes.

Step 5 After the upgrade or configuration is complete, Config Successful Rebooting in 15s. The SMU will restart 15 seconds later. Step 6 After the restart is complete, remove the USB flash drive. ----End

5.1.2 Setting the Time Zone and Time Set the date and time based on the local time and time zone. Table 5-1 Setting the time zone and time Main Menu

Second-Level Menu

Third-Level Menu

Setting

Setting Wizard

Date and Time

Time Zone

Set to the local time zone.

Date and Time

Set to the local date and time.

5.1.3 Setting Basic Battery Parameters Context Basic battery parameters are fundamental for the monitoring unit to manage batteries and should be set based on the number and capacity of battery strings connected.

Incorrectly setting basic battery parameters affects the battery charge and discharge management and reduces the battery lifespan.

Procedure Step 1 Set the battery type.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

42

SMU02B Site Monitoring Unit User Manual

5 Common Tasks

Table 5-2 Setting the battery type Main Menu

Second-Level Menu

Third-Level Menu

Fourth-Level Menu

Setting

Parameters Settings

Setup Parameter

Basic Parameters

Battery Type Number

1–4

Battery Factory

Set based on site requirements.

Battery Model

Step 2 Set lead-acid battery parameters. Table 5-3 Setting lead-acid battery parameters Main Menu

Second-Level Menu

Third-Level Menu

Setting

Setting Wizard

Battery Parameters

Battery N Connected

Yes/No

Single-String Cap.

Rated capacity of the batteries in a battery string.

NOTE If N battery strings are connected, set Battery 1 Connected to Battery N Connected to Yes, and set the other parameters to No.

NOTE The batteries controlled by one circuit breaker or fuse are called a battery string.

Battery Cable Length Batt Cable CS Area

Set based on site requirements. NOTE  When each battery string is connected to the RTN+ busbar over one cable, set Cable Length to half of the total length of cables between both ends of a battery string and the positive and negative busbars, and set Cable CSA to the cross-sectional area of the cable. 

When each battery string is connected to the RTN+ busbar over two cables, set Cable Length to half of the total length of a suite of cables between both ends of a battery string and the positive and negative busbars, and set Cable CSA to the sum of the cross-sectional areas of the two cables.

For example: 

If battery routes 1 and 2 are respectively connected to a battery string (each battery string consists of four 12 V, 150 Ah batteries in series), set Battery 1 Connected and Battery 2 Connected to Yes and others to No, and set Single-String Cap. to 150 Ah.



If battery route 1 is connected to two battery strings in parallel (each battery string consists of four 12 V, 150 Ah batteries in series), set Battery 1 Connected to Yes and others to No, and set Single-String Cap. to 300 Ah.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

43

SMU02B Site Monitoring Unit User Manual

5 Common Tasks

5.1.4 Setting the Alarm Enable Option, Alarm Severity, and Associated Relays 

You can enable or disable each alarm based on site requirements. If an alarm is enabled, the monitoring unit generates the alarm when the alarm condition is met. If an alarm is disabled, the monitoring unit does not generate the alarm.



You can set the severity of an alarm to critical, major, minor, or warning.



You can associate an alarm with a specific dry contact output relay.

The following describes how to set alarm parameters for an AC Surge Protector Fault. Table 5-4 Setting the alarm enable option, alarm severity, and associated relays Main Menu

Second-Level ThirdMenu Level Menu

FourthFifth-Level Level Menu Menu

Sixth-Level Menu

Parameters Settings

Alarm Parameters

Power System AC Surge Protector Fault

Alarm Enable Enable

Alarm Config

Setting

Alarm Severity

Major

Output Relay

ALM1 Yes

5.1.5 Setting Alarm Parameters for Dry Contacts Context 

You can set associations between dry contact output status and alarm status.



You can clear the associations between all alarms and the selected dry contact inputs or outputs in one click.



You can set associations between dry contact input status and alarm status. Use DIN1 as an example. If you set DIN1 Alarm Condition to Close, the SMU generates a DIN1 Alarm when the DIN1 is closed.

Procedure Step 1 Set alarm actions for dry contact outputs. Use ALM1 as an example. Table 5-5 Setting alarm actions for dry contact outputs Main Menu

Second-Level Menu

Third-Level Menu

Fourth-Level Menu

Setting

Parameters Settings

Alarm Parameters

DO Dry Contact Para.

ALM1 Alarm Action

Close, Open

Step 2 Clear associations between alarms and dry contact outputs. Use ALM1 as an example.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

44

SMU02B Site Monitoring Unit User Manual

5 Common Tasks

Table 5-6 Clearing associations between alarms and dry contact outputs Main Menu

Second-Level Menu

Third-Level Menu

Fourth-Level Menu

Setting

Parameters Settings

Alarm Parameters

Clear ALM Asso.

Clear ALM1 Asso.

Yes

Step 3 Set alarm conditions for dry contact inputs. Use DIN1 as an example. Table 5-7 Setting alarm conditions for dry contact inputs Main Menu

Second-Level Menu

Third-Level Menu

Fourth-Level Menu

Setting

Parameters Settings

Alarm Parameters

DI Dry Contact Para.

DIN1 Alm. Cond.

Close, Open

Step 4 Clear associations between alarms and dry contact inputs. Use DIN1 as an example. Table 5-8 Clearing associations between alarms and dry contact inputs Main Menu

Second-Level Menu

Third-Level Menu

Fourth-Level Menu

Setting

Parameters Settings

Alarm Parameters

Clear DI Asso.

Clear DIN1 Asso.

Yes

----End

5.1.6 Setting Rectifier Addresses Context You can set rectifier addresses only on the LCD and only to the power system that does not have a hardware address.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

45

SMU02B Site Monitoring Unit User Manual

5 Common Tasks

Figure 5-1 Rectifier addresses (twenty 100 A rectifiers are used in the example)

Parameters Table 5-9 Rectifier address parameter description Parameter

Description

Default Value

Value Range

Rect. Address Settings

Select Yes when you need to manually set rectifier addresses.

No



Yes



No

Set each rectifier address manually.



N. Rectifier Address

1~60

LCD Operations Step 1 Set Rect. Address Settings to Yes. Path: Main Menu > Setting Wizard > Rect. Address Settings Step 2 Press

to choose 1. Rectifier Address.

Step 3 Observe the indicators on rectifiers. If the power indicator (green) on a rectifier blinks at 0.5 Hz, the rectifier is selected. Set the rectifier address to the value shown in Figure 5-1 based on the rectifier position. Step 4 Refer to Step 2 and Step 3 to set addresses for the other rectifiers in the cabinet. Step 5 Press

to choose Save Settings. Press

to save the settings.

----End

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

46

SMU02B Site Monitoring Unit User Manual

5 Common Tasks

5.2 Common Maintenance Tasks 5.2.1 Backing Up the Current Settings The configuration file contains all user configuration information (such as parameter values and alarm configurations) about the current system. You can back up the configuration file to a local computer over the WebUI.

When importing the backup configuration file, ensure that the system types of the exported and imported configuration files are consistent. Figure 5-2 Backing up the current configuration

5.2.2 Restoring Factory Defaults

After factory defaults are restored, the monitoring unit restarts. After factory defaults are restored, all parameter values change to their default factory values. You are advised to back up the current settings before restoring factory defaults.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

47

SMU02B Site Monitoring Unit User Manual

5 Common Tasks

Figure 5-3 Restoring factory defaults

5.2.3 Upgrading Software You can use the WebUI and LCD to upgrade software for the SMU BSP, SMU, intelligent device SO library package, and southbound devices.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

48

SMU02B Site Monitoring Unit User Manual

5 Common Tasks



To retain pre-upgrade parameters, back up the data before upgrading software.



The SMU will restart automatically after the software for the BSP, SMU, and intelligent device SO library package is upgraded.



Exercise caution to choose the version rollback function during software upgrade. After version rollback, the user accounts created are deleted, and the initial user name and password are required for login.

Figure 5-4 Upgrading software

5.2.4 Changing a User Password Context For security purposes, change your password periodically. Only the system administrator can change user passwords.

Procedure Step 1 Log in to the WebUI and choose Maintenance > User Management. The user management page is displayed.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

49

SMU02B Site Monitoring Unit User Manual

5 Common Tasks

Figure 5-5 User management page

Step 2 Select the user whose password needs to be changed and click Modify. The dialog box for modifying user information is displayed. Figure 5-6 Changing the password

Step 3 Select Change Password, set New Password and Confirm Password, and click Confirm. The Recertification dialog box is displayed.

The administrator needs to set Old Password only when changing the administrator's own password.

Change the password in compliance with the following rules: 

The password must contain 6 to 20 characters.



The password must consist of at least two of the following types: digits, uppercase letters, lowercase letters, and special characters (! @ * - _ ? { } = /).

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

50

SMU02B Site Monitoring Unit User Manual

5 Common Tasks



The password must be different from the previous two passwords.



The password must be different from the user name or its reverse.

Step 4 Set Password of Current Login User and click Submit. ----End

Changing WiFi password



You are advised to periodically change the WiFi password to improve account security and prevent unauthorized network attacks, such as data tampering.



Huawei will not be liable for any loss caused by your failure to change the password in time or to keep the new password properly.

Change the WiFi account password: choose System Settings > Network Config > WIFI.

5.2.5 Viewing Dry Contact Association Information Context 

You can view the information about association between dry contact outputs and alarms.



You can also view the information about association between dry contact inputs and devices.

Procedure Step 1 View the information about association between dry contact outputs and alarms.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

51

SMU02B Site Monitoring Unit User Manual

5 Common Tasks

Figure 5-7 Viewing the information about association between dry contact outputs and alarms

Step 2 View the information about association between dry contact inputs and devices. Figure 5-8 View the information about association between dry contact inputs and devices

----End

5.2.6 Viewing Active Alarms Active alarms are the alarms that are not cleared.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

52

SMU02B Site Monitoring Unit User Manual

5 Common Tasks

Figure 5-9 Viewing active alarms

5.2.7 Viewing Historical Alarms Prerequisites Historical alarms refer to the alarms that have been cleared.

Procedure Step 1 To filter out historical alarms. Figure 5-10 Filtering out historical alarms

Step 2 View historical alarms.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

53

SMU02B Site Monitoring Unit User Manual

5 Common Tasks

Figure 5-11 Viewing historical alarms

----End

5.2.8 Deleting Devices Failing in Communication If there is no need to troubleshoot when a communication failure alarm is generated, you can manually delete the device failing in communication. The following describes how to delete a rectifier failing in communication. Figure 5-12 Deleting devices failing in communication

5.2.9 Viewing Version Information View the monitoring version number to facilitate fault diagnosis and check whether the upgrade is successful. Figure 5-13 Viewing version information

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

54

SMU02B Site Monitoring Unit User Manual

5 Common Tasks

5.2.10 Exporting Maintenance Information Context 

You can export historical alarms, active alarms, performance data, operation logs, and battery test records on the WebUI.



You can view and export e-label information about the power subrack, monitoring unit, and rectifiers on the WebUI.



You can export version information and system operating information in one-click mode on the WebUI to quickly collect information and identify system faults.

Procedure Step 1 To export historical data. Figure 5-14 Exporting historical data

Step 2 To export e-label information.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

55

SMU02B Site Monitoring Unit User Manual

5 Common Tasks

Figure 5-15 Exporting e-label information

Step 3 To export fault information. Figure 5-16 Exporting fault information

If information export fails due to a browser error, wait for a certain period (30 minutes at most), log in, and try again.

----End

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

56

SMU02B Site Monitoring Unit User Manual

6 Hardware Replacement

6

Hardware Replacement

6.1 Replacing an SMU02B Context The SMU is hot-swappable.

Record the software version of the old SMU. If the old SMU is damaged and cannot be viewed, send the barcodes of the old SMU and the cabinet to Huawei service personnel for query.

Procedure Step 1 Push the locking latch on the SMU to the left and pull out the handle. Step 2 Take the SMU out of the slot, as shown in Figure 6-1. Figure 6-1 Removing the SMU

Step 3 Place the new SMU at the entry to the appropriate slot in the monitoring unit subrack, and push the SMU until its front panel aligns with the front panel of the monitoring unit subrack. Step 4 Push the handle in position and push the locking latch to the right to lock the handle, as shown in Figure 6-2.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

57

SMU02B Site Monitoring Unit User Manual

6 Hardware Replacement

Figure 6-2 Installing the SMU

----End

Follow-up Procedure After replacing the SMU, the parameters are restored to factory defaults. You need to reset the parameters based on site requirements.

After replacing the old SMU with a new spare part, power on the new SMU and check its software version. If the software version of the new SMU is earlier than that of the old SMU, upgrade the new SMU software.

6.2 Replacing an SMU02B1 Prerequisites 

You have obtained the cabinet door key.



The new SMU02B1 is intact.

Procedure Step 1 Connect the ground cable for the ESD wrist strap, and put on the ESD wrist strap and ESD gloves.

Record the software version of the old SMU. If the old SMU is damaged and cannot be viewed, send the barcodes of the old SMU and the cabinet to Huawei service personnel for query.

Step 2 Disconnect the communications cable from the SMU02B1 panel. Step 3 Push the locking latch leftwards. Step 4 Pull the handle outwards and remove the SMU02B1, as shown in Figure 6-3.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

58

SMU02B Site Monitoring Unit User Manual

6 Hardware Replacement

Figure 6-3 Removing the SMU02B1

Step 5 Take off the SD card from the side of the SMU02B1.

If no SD is installed, go to Step 7.

Step 6 Insert the SD card into the new SMU02B1. Step 7 Place the new SMU02B1 in the slot, push the locking latch leftwards, and pull out the handle. Step 8 Gently push the SMU02B1 along guide rails until it is engaged. Close the handle, and push the locking latch rightwards. Figure 6-4 Installing the SMU02B1

Step 9 Reset SMU02B1 parameters.

After replacing the old SMU with a new spare part, power on the new SMU and check its software version. If the software version of the new SMU is earlier than that of the old SMU, upgrade the new SMU software.

Step 10 Reconnect the communications cable to the SMU02B1 panel. ----End

Follow-up Procedure After replacing the SMU02B1, the parameters are restored to factory defaults. You need to reset the parameters based on site requirements.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

59

SMU02B Site Monitoring Unit User Manual

6 Hardware Replacement

6.3 Replacing a UIM02C Board Prerequisites 

An ESD wrist strap, ESD gloves, ESD box or bag, cabinet door key, and required tools are available.



The new UIM02C board is intact.

Procedure Step 1 Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap and ESD gloves. Step 2 Record the position of signal cables connected to the UIM02C panel, and then disconnect the signal cables. Step 3 Unscrew and take out the UIM02C. Figure 6-5 Taking out the UIM02C

Step 4 Disconnect the –48 V power cable from the UIM02C board.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

60

SMU02B Site Monitoring Unit User Manual

6 Hardware Replacement

Figure 6-6 Disconnecting the –48 V power cable

(1) -48 V power port

Step 5 Record the connection positions of all cables including cables for internal and external circulation fans and flat cables on the UIM02C board, and then disconnect the cables. Step 6 Remove the UIM02C board. Figure 6-7 Removing the UIM02C board

Step 7 Take out and install the new UIM02C board. Step 8 Connect all the cables on the UIM02C board to the new UIM02C based on the recorded information. Step 9 Reconnect the –48 V power cable to the UIM02C board. Step 10 Push the UIM02C in place and tighten the screws. Step 11 Reconnect signal cables to the new UIM02C panel based on the recorded information. Step 12 Disconnect the ground cable from the ESD wrist strap, and remove the ESD wrist strap and ESD gloves. ----End

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

61

SMU02B Site Monitoring Unit User Manual

6 Hardware Replacement

Follow-up Procedure Pack the removed component and have it sent to the local Huawei warehouse.

6.4 Replacing an NIM02D Board Prerequisites 

An ESD wrist strap, ESD gloves, ESD box or bag, cabinet door key, and required tools are available.



The new NIM02D board is intact.

Procedure Step 1 Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap and ESD gloves. Step 2 Record the connection positions of cables on the NIM02D panel and disconnect the cables. Step 3 Loosen the screws on both sides of the UIM02C panel and pull out the UIM02C. Step 4 Disconnect the power cables between the NIM02D board and the J1 port on the UIM02C. Step 5 Unscrew the NIM02D from the UIM02C board and take out the NIM02D board. Figure 6-8 Removing the NIM02D board

Step 6 Push the new NIM02D board in place and secure it with holes aligned. Step 7 Connect power cables between the power port on the NIM02D board and the J1 port on the UIM02C.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

62

SMU02B Site Monitoring Unit User Manual

6 Hardware Replacement

Figure 6-9 Connecting power cables

Step 8 Push the UIM02C into the subrack until its front panel is flush with that of the monitoring unit subrack, and then tighten the screws. Step 9 Reconnect the cables to the new NIM02D panel based on the recorded information. Step 10 Disconnect the ground cable from the ESD wrist strap, and remove the ESD wrist strap and ESD gloves. ----End

Follow-up Procedure Pack the removed component and have it sent to the local Huawei warehouse.

6.5 Replacing an NIM01C Prerequisites 

You have obtained an ESD wrist strap, a pair of ESD gloves, an ESD box or bag, the cabinet door key, and tools.



The new NIM01C is intact.

Procedure Step 1 Connect the ground cable for the ESD wrist strap, and put on the ESD wrist strap and ESD gloves.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

63

SMU02B Site Monitoring Unit User Manual

6 Hardware Replacement

Step 2 Record the positions where signal cables connect to the NIM01C panel, and then disconnect the signal cables. Step 3 Loosen the screws on both sides of the NIM01C panel. Step 4 Pull the handle rightwards to remove the NIM01C, as shown in Figure 6-10. Figure 6-10 Removing an NIM01C

Step 5 Remove the SIM card from the SIM card slot, and insert a new NIM01C. Skip this step if no SIM card is installed. Step 6 Place the new NIM01C at the entry to the appropriate slot in the monitoring unit subrack, and push the NIM01C until its front panel is in the same plane the front panel of the monitoring unit subrack. Step 7 Push the handle inwards until it is engaged, and then tighten the screws, as shown in Figure 6-11. Figure 6-11 Installing an NIM01C

Step 8 Connect the signal cables to the original positions on the NIM01C panel. Step 9 Disconnect the ground cable for the ESD wrist strap, and take off the ESD wrist strap and ESD gloves. ----End

Follow-up Procedure Pack the removed component, and return it to Huawei local warehouse.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

64

SMU02B Site Monitoring Unit User Manual

6 Hardware Replacement

6.6 Replacing a CIM02C Prerequisites 

An ESD wrist strap, ESD gloves, ESD box or bag, cabinet door key, and required tools are available.



The new CIM02C is intact.

Procedure Step 1 Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap and ESD gloves. Step 2 Record the connection positions of cables on the CIM02C panel and disconnect the cables. Step 3 Loosen the screws on both sides of the CIM02C panel. Step 4 Pull the handle rightwards and take out the CIM02C. Figure 6-12 Removing a CIM02C

Step 5 Place the new CIM02C at the entry to the appropriate slot in the monitoring unit subrack, and push the CIM02C until its front panel is flush with the front panel of the monitoring unit subrack. Step 6 Push the handle inwards until it is engaged, and then tighten the screws. Figure 6-13 Installing a CIM02C

Step 7 Reconnect the cables to the new CIM02C panel based on the recorded information.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

65

SMU02B Site Monitoring Unit User Manual

6 Hardware Replacement

Step 8 Disconnect the ground cable from the ESD wrist strap, and remove the ESD wrist strap and ESD gloves. ----End

Follow-up Procedure Pack the removed component and have it sent to the local Huawei warehouse.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

66

SMU02B Site Monitoring Unit User Manual

A Parameter Lists

A

Parameter Lists

A.1 LCD Menu Hierarchy Figure A-1 LCD menu hierarchy

Table A-1 LCD menu description Menu Item

Description

Active Alarm

Views active alarms in the power system.

Running Information

Views the operating status of the power system, rectifiers, batteries, and other modules in the system.

Setting Wizard

Quickly sets common parameters, such as the number of battery strings, rated battery capacity, date, time, and network parameters.

Parameters Settings

Sets parameters for the power system, rectifiers, batteries, and other modules in the system.

Running Control

Manually controls the power system, rectifiers, batteries, and other modules in the system, such as switching between equalized charging and float charging, starting or shutting down rectifiers, clearing historical alarms, and restarting the SMU.

Site Maintain

Performs USB-based operations such as upgrade, export, and site setup.

User Management

Change LCD login password, user logout.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

67

SMU02B Site Monitoring Unit User Manual

A Parameter Lists

A.2 Running Information Table A-2 Running Information menu hierarchy SecondLevel Menu

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu

Power System

Basic Information

Bus Bar Voltage

-

Total Load Current

-

Total Load Power

-

Phase L1 Voltage

-

Phase L2 Voltage

-

Phase L3 Voltage

-

Phase L1 Current

-

Phase L2 Current

-

Phase L3 Current

-

AC Frequency

-

System Efficiency

-

NOTE This parameter varies with the system type.

Power Sys. Efficency

-

NOTE This parameter varies with the system type.

DC Load Shared Equip

Issue 04 (2019-08-30)

Site Efficency

-

System Load Ratio

-

SPUE

-

Power Supply Mode

-

Active Power Modules

-

Hibernating Modules

-

Magnetic Latch 1-2 State

-

ATS 1-2 Mains Status

-

Load Shared Cons

-

Load Shared Curr.

-

Load Shared Power

-

Copyright © Huawei Technologies Co., Ltd.

68

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

A Parameter Lists

Third-Level Menu

DC Load n Equip

Fourth-Level Menu

Fifth-Level Menu

Last Mnth Share Cons.

-

DC Load n Pwr. Cons.

-

DC Load n Current

-

DC Load n Power

-

Load n Last Mnth Elec

-

Load n Real-time Cur

-

Load n Last Mnth Cons.

-

UIM

DO Control Status

ALMn Control Status

-

Controller

NetEco Link State

-

-

Rectifier

Rectifier Group

Total DC Output Current

-

Total DC out Power

-

Total AC Input Power

-

Load Usage #

-

Total DC Inp Power #

-

Rect. Missing Num

-

NOTE This parameter is displayed only when rectifier missing.

Rectifier Info

Rectifier n

Slot No. DC Outp. Term. Volt. DC Output Current DC Output Power AC Voltage Rated Efficiency Real-time Efficiency Rectifier Temp. Cur. Limiting Status Run Status

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

69

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

A Parameter Lists

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu Hardware Version Software Version Bar Code

Mains #

Mains Status

-

-

Phase L1 Voltage

-

-

-

-

-

-

-

-

-

-

-

-

Total Active Power

-

-

AC Frequency

-

-

NOTE This parameter is displayed only when AC Model is set to 3 Phase 4 Line.

Phase L2 Voltage NOTE This parameter is displayed only when AC Model is set to 3 Phase 4 Line.

Phase L3 Voltage NOTE This parameter is displayed only when AC Model is set to 3 Phase 4 Line.

Phase L1 Current NOTE This parameter is displayed only when AC Model is set to 3 Phase 4 Line.

Phase L2 Current NOTE This parameter is displayed only when AC Model is set to 3 Phase 4 Line.

Phase L3 Current NOTE This parameter is displayed only when AC Model is set to 3 Phase 4 Line.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

70

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

A Parameter Lists

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu

Mains Power Factor

-

-

Phase L1 Factor #

-

-

Phase L2 Factor #

-

-

Phase L3 Factor #

-

-

Mains Electricity

-

-

Total Runtime

-

-

AC Voltage

-

-

-

-

-

-

-

-

-

-

Battery Status

-

Total Batt. Current

-

Total Rated Cap.

-

NOTE This parameter is displayed only when AC Model is set to 2 Phase 2 Line or 1 Phase 2 Line.

AC Current NOTE This parameter is displayed only when AC Model is set to 2 Phase 2 Line or 1 Phase 2 Line.

L1-L2 Line Voltage NOTE This parameter is displayed only when AC Model is set to 3 Phase 3 Line.

L2-L3 Line Voltage NOTE This parameter is displayed only when AC Model is set to 3 Phase 3 Line.

L3-L1 Line Voltage NOTE This parameter is displayed only when AC Model is set to 3 Phase 3 Line.

Acid Battery

Issue 04 (2019-08-30)

Acid Battery Group

Copyright © Huawei Technologies Co., Ltd.

71

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

A Parameter Lists

Third-Level Menu

Battery String

Fourth-Level Menu

Fifth-Level Menu

Remaining Cap.

-

Remain Cap. Percent

-

Cur. Limiting Status

-

Test Status

-

Total Dis Cap

-

Total Recycle Times

-

Battery Type

-

Battery String n

Current Remaining Cap. Remain Cap. Percent Rated Capacity Batt. SOH # Middle Voltage

Batt. Cell Detector #

BackBatt n #

Issue 04 (2019-08-30)

Batt. Detector Addr.

-

Batt.1 cell1-24 volt.

-

Batt.2 cell1-8 volt.

-

Batt.3 cell1-4 volt.

-

Batt.4 cell1-4 volt.

-

Battery Test Records

-

-

Backup Power Info

-

-

BackBatt n Group

Battery Status

-

Total Batt. Current

-

Total Rated Cap.

-

Remaining Cap.

-

Remain Cap. Percent

-

Backup Time #

-

Cur. Limiting Status

-

Test Status

-

Battery Temp. n #

-

Copyright © Huawei Technologies Co., Ltd.

72

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

TCB E-label

-

Battery Temp.

-

Total Dis Cap.

-

Total Recycle Times

-

BLVD Discon. Reason #

-

Batt. Residual Life #

-

TCB Barcode

-

Battery Type

-

Main/Backup State

-

Rated Capacity

-

Current

-

Remaining Cap.

-

Remain Cap. Percent

-

Batt. SOH

-

Longitude

-

-

Latitude

-

-

Altitude

-

-

Camera #

Camera Group

Camera n

-

NOTE Applies when the serial port camera is connected.

Camera n

Software Version

-

Vendor Type

-

Port number

-

Camera #

Camera Group

Camera n

-

NOTE Applies when the IP camera is connected.

Camera n

Software Version

-

Vendor Type

-

IP Address

-

DTS #

DTS Group

-

-

DTSn

Comm Status

-

Running Mode

-

Main Battery Voltage

-

Third-Level Menu

BackBatt n String n

GPS

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

73

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

DCDB #

A Parameter Lists

Third-Level Menu

DCDB Group

DCDBn

Fourth-Level Menu

Fifth-Level Menu

Back Battery Voltage

-

Combined Voltage

-

Power Supply Mode

-

DTS E-label

-

DTS Board E-label

-

DTS Frame E-label

-

DTS Board Barcode

-

DTS Frame Barcode

-

DTS Barcode

-

Hardware Version

-

Software Version

-

DCDB Number

-

Total Load Number

-

Unused Load Number

-

Basic Information

Comm Status Input Voltage Total Load Number Unused Load Number Total Output Current Total Output Power DCDB Slot No. Barcode Info

Load n

Load n Used Load n Current Load n Power

Asset Information

Software Version Hardware Version

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

74

SMU02B Site Monitoring Unit User Manual

A Parameter Lists

SecondLevel Menu

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu

Elock #

Elock n

Software Version

-

Hardware Version

-

Lock Status

-

Lock Name

-

Com. Port Number

-

Device Address

-

Comm State

-

Hardware Version

-

Software Version

-

COM1 Power Volt

-

COM2 Power Volt

-

Comm State

-

Hardware Version

-

Software Version

-

COM1 Power Volt

-

COM2 Power Volt

-

Comm State

-

Hardware Version

-

Software Version

-

COM1 Power Volt

-

COM2 Power Volt

-

Dial Address

-

Hardware Version

-

Software Version

-

Communication Status

-

RF Software Version

-

BIM Index

-

Software Version

-

Hardware Version

-

Comm. Ex. Board #

NIM01C n

NIM01C3 n

CIM02C n

CIM #

CIM Equip n

CIMn-BIMn

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

75

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Low Cap Li-ion Batt #

A Parameter Lists

Third-Level Menu

Li-ion Battery Group

NOTE This parameter is displayed only when Battery Model is set to BBS 4840Z.

Li Battery # NOTE This parameter is displayed only when Battery Model is set to ESM-A, ESU-A or ESM-BX.

Li Battery Group

Fourth-Level Menu

Fifth-Level Menu

BIM Temp.

-

BIM Voltage

-

BIM Resistance

-

Int Resist Measures

-

Data Report Period

-

BIM SOH

-

Communicate Status

-

Battery Sub-String

-

BIM Num.in Batt.Str

-

Total Batt. Current

-

Battery Status

-

Battery Temp. n

-

Battery Status

-

Batt Cell Pack Volt.

-

Batt Cell Pack Curr.

-

Batt Voltage

-

Batt Current

-

Temperature

-

Normal Comm. BMUs

-

Total Capacity

-

Remain Cap. Percent

-

Total Recycle Times

-

SOH

-

NOTE This parameter is displayed only when Battery Model is set to ESM-A or ESM-BX.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

76

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

A Parameter Lists

Third-Level Menu

Li Battery n

DCDU #

DCDU n

Fourth-Level Menu

Fifth-Level Menu

Total Dis Cap

-

Battery Type

-

BMU Address

-

Status

-

Capacity

-

Battery Voltage

-

Battery Current

-

Cell Pack Volt.

-

Cell Pack Curr.

-

Output Power

-

Battery String SOH

-

Remain Cap. Percent

-

Work Status

-

Software Ver

-

Hardware Ver

-

Basic Information

Major Current Minor Current Ambient Temperature Ambient Humidity Outdoor Amb. Temp. Indoor Vent Temp. TC Mode Temp1 Temp2

Fan Info

Fan 1 Speed Fan 2 Speed Fan 3 Speed

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

77

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

A Parameter Lists

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu Fan 4 Speed

A/C Information

A/C Status A/C Compressor Stat. A/C Indoor Vent Temp A/C External Temp. A/C Inter. Fan Speed A/C Exter. Fan Speed A/C Runtime A/C Compress Runtime

Asset Info

Software Version Hardware Version

EFUSE Group #

EFUSEn

Basic Information

Input Voltage

Load n

Load n Used Load n Current Load n Status Load n Power Load n Consumption

Asset Info

Software Version Hardware Version EFUSE Name

Temp. Control Info. # NOTE This parameter varies with the system

Issue 04 (2019-08-30)

Temp. Control Group

Fan Group

Indoor Vent Temp.

-

Outdoor Amb. Temp.

-

TC Mode

-

System Noise

-

Fan n Speed

-

Copyright © Huawei Technologies Co., Ltd.

78

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu type.

A Parameter Lists

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu

Batt Int AC. n

A/C Status

-

Compressor Status

-

Indoor Vent Temp.

-

External Temp.

-

Internal Fan Speed

-

External Fan Speed

-

A/C Runtime

-

Compressor Runtime

-

DC Power

-

Device Model

-

Input Power

-

Running Current

-

A/C Software Version

-

Comm. Address

-

Address

-

In Circ Fan Speed

-

Ext Circ Fan Speed

-

Ret. Air Temp

-

Software Version

-

Ret. Air Temp

-

Air Inlet Temp.

-

EXTFAN n Speed

-

INFAN n Speed

-

Battery Type

-

Software Version

-

Hardware Version

-

System ID

-

Comm. Address

-

-

-

TCU

Batt TCUC n

AIM n #

Issue 04 (2019-08-30)

AC Frequency

Copyright © Huawei Technologies Co., Ltd.

79

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Sensor

Issue 04 (2019-08-30)

A Parameter Lists

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu

L1-L2 Line Voltage #

-

-

L2-L3 Line Voltage #

-

-

L3-L1 Line Voltage #

-

-

Phase L1 Voltage

-

-

Phase L2 Voltage

-

-

Phase L3 Voltage

-

-

Active Power

-

-

Total Power Factor

-

-

Phase L1 Power

-

-

Phase L2 Power

-

-

Phase L3 Power

-

-

Phase L1 Pwr. Factor

-

-

Phase L2 Pwr. Factor

-

-

Phase L3 Pwr. Factor

-

-

Active Electricity

-

-

SoftWare Version

-

-

Phase L1 Current

-

-

Phase L2 Current

-

-

Phase L3 Current

-

-

Hardware Version

-

-

AC Ammeter Elabel

-

-

BootLoader Version

-

-

AC Voltage

-

-

AC Current

-

-

Phase L1 Reactive Power

-

-

Phase L2 Reactive Power

-

-

Phase L3 Reactive Power

-

-

Door Sensor #

Door Status

-

Copyright © Huawei Technologies Co., Ltd.

80

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Virtual PSC #

DC Energy Meter n #

Issue 04 (2019-08-30)

A Parameter Lists

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu

Water Sensor #

Water Status

-

Smoke Sensor #

Smoke Sensor Status

-

IR Sensor #

IR Sensor Status

-

Humiture Sensor #

Ambient Temperature

-

Ambient Humidity

-

AC1 L1 Phase Volt

-

-

AC1 L2 Phase Volt

-

-

AC1 L3 Phase Volt

-

-

AC1 L1-L2 Line Volt

-

-

AC1 L2-L3 Line Volt

-

-

AC1 L3-L1 Line Volt

-

-

AC1 L1 Phase Cur

-

-

AC1 L2 Phase Cur

-

-

AC1 L3 Phase Cur

-

-

AC1 Frequency

-

-

System Voltage

-

-

Total Load Current

-

-

Qty. of Rect.

-

-

Rectifier n Outp Cur

-

-

Rectifier n Temp

-

-

Batt n Current

-

-

Batt n Temp

-

-

Batt n Capacity

-

-

Device System Time

-

-

Batt Remain Cap %

-

-

Channel n Voltage

-

-

Channel n Current

-

-

Channel n Power

-

-

Chan n Consumption

-

-

Copyright © Huawei Technologies Co., Ltd.

81

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

ATS 1

FSU

24V Module

A Parameter Lists

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu

Protocol Version

-

-

Software Version

-

-

Hardware Version

-

-

DC Ammeter E-label

-

-

Barcode Info

-

-

Running Mode

-

-

Power Supply Mode

-

-

Work Scenario

-

-

Software Version

-

-

Hardware Version

-

-

Wireless Public IP

-

-

Virtual Network IP

-

-

Barcode Info

-

-

Module Group

Output Voltage

-

Total Output Current

-

Total Output Power

-

Serial No.

-

Total Runtime

-

Output Voltage

-

Output Current

-

Output Power

-

Turn On/Off Status

-

Hardware Version

-

Software Version

-

E-Label

-

Barcode Info

-

12DC Output Voltage

-

12DC Output Current

-

24AC Output Voltage

-

Module n

MIMO Module

Issue 04 (2019-08-30)

MIMO 1

Copyright © Huawei Technologies Co., Ltd.

82

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

SSU #

A Parameter Lists

Third-Level Menu

SSU Group

SSU n

Fourth-Level Menu

Fifth-Level Menu

24AC Output Current

-

Software Version

-

Hardware Version

-

E-Label

-

Barcode Info

-

Power Supply

-

Total Current

-

SSU Address

-

Output Voltage

-

Output Current

-

Input Voltage

-

SSU Status

-

Software Version

-

Hardware Version

-

Historical Alarm

-

-

-

Performance

Mains Pwr Cons

-

-

DC Load Pwr Cons

-

-

Acid Batt Dis. Cap.

-

-

BackBatt n Dis. Cap.

-

-

Li Batt Dis. Cap.

-

-

Total AC Input Elec.

-

-

Solar Power Supply

-

-

Power System

Monitor Brd Barcode

-

PowerSubrack Barcode

-

Cabinet Barcode

-

Ext. Board Barcode

-

GMU n

GMU Barcode

-

HVDC #

Bar Code

-

Battery Group #

TCB Barcode

-

Barcode Info NOTE Only the information about connected components is displayed.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

83

SMU02B Site Monitoring Unit User Manual

A Parameter Lists

SecondLevel Menu

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu

Mobile Data Info

Connection Status

-

-

Signal Strength

-

-

Data Mode

-

-

IP Address

-

-

Current SIM Card

-

-

SIM Card 1 Status

-

-

SIM Card 1 IMSI

-

-

SIM Card 1 Number

-

-

SIM 1 On-day Traffic

-

-

SIM Card 2 Status

-

-

SIM Card 2 IMSI

-

-

SIM Card 2 Number

-

-

SIM 2 On-day Traffic

-

-

NIM02D #

-

-

EPACn #

Software Version

-

Indoor Temp

-

Indoor Humidity

-

Outdoor Temp

-

Air Con n Status

-

Fan Status

-

System Time

-

Equip Address

-

Connected Port

-

Loop 1 Control Stat

-

Loop 2 Control Stat

-

ACM Environment Temp

-

Loop 1 A/C Runtime

-

Loop 2 A/C Runtime

-

Software Ver

-

Other Device Info

ACM-2 n #

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

84

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

A Parameter Lists

Third-Level Menu

AC Energy Meter #

HVDC #

HVDC Group

HVDC

Issue 04 (2019-08-30)

Fourth-Level Menu

Fifth-Level Menu

Hardware Ver

-

AC Frequency

-

Phase L1 Voltage

-

Phase L2 Voltage

-

Phase L3 Voltage

-

Chan n Phase L1 Cur

-

Chan n Phase L2 Cur

-

Chan n Phase L3 Cur

-

Chan n Active Power

-

Chan n Power Factor

-

Chan n Consumption

-

Device Model

-

Version

-

Input Voltage

-

Out Voltage

-

Total Output Current

-

Total DC Power

-

Running Status

-

DC Output Voltage

-

DC Output Current

-

Hardware Ver

-

Software Ver

-

Slot No.

-

Rated Efficiency

-

DC Output Power

-

E-Label

-

Barcode Info

-

Work Mode

-

Copyright © Huawei Technologies Co., Ltd.

85

SMU02B Site Monitoring Unit User Manual

A Parameter Lists

A.3 Setting Wizard Table A-3 Setting Wizard menu hierarchy Second-Level Menu

Third-Level Menu

Default Value

Value Range

Site Summary

Battery Factory

Other

AGISSON, Coslight, Dengta, Eltek, EnerSys, Exide, LEOCH, Narada, NorthStar, Shoto, Other

Battery Model

12V VRLA

DCB-A, DCB-A1, DCB-B, DCB-Y, ESU-A, ESM-A, ESM-BX, FCB-A, FCB-B, SCB-A, SCB-A1, TCB-A, TCB-B, TCB-C, 12V VRLA, 2V VRLA, FLOOD, 6-GFM-X, 6-GFMF, Rebak-F4899T, 12TD-F, SBS-F, M12V-FT, LPF12-H, 6-GFM-F, 12NDF, Blue, Red, 6-FMX, 6-XFMJ, GFM, BBS 4840Z

Battery n Connected

Yes

Yes, No

Single-String Cap.

150 Ah

5-10000

Battery Cable Length

1m

0-100

Batt Cable CS Area

35 mm2

1-1000

Battery n Connected

Yes

Yes, No

Single-String Cap.

150 Ah

5-10000

Battery Cable Length

1m

0-100

Batt Cable CS Area

35 mm2

1-1000

Time Zone

UTC +08:00 Beijing

-

Date and Time

-

-

NTP Enable

No

Yes, No

NetEco Primary IP

192.168.0.10

-

NetEco Backup IP

192.168.0.10

-

Site ID

-

-

Battery Parameters

BackBatt #

Date and Time

Neteco Parameters

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

86

SMU02B Site Monitoring Unit User Manual

A Parameter Lists

Second-Level Menu

Third-Level Menu

Default Value

Value Range

Network Parameters

IP Address

192.168.0.10

-

Subnet Mask

255.255.255.0

-

Default Gateway

192.168.0.1

-

IPv4 DSCP

46

0-63

VLAN Enable

No

Yes, No

VLAN ID

0

0-4094

VLAN Priority

5

0-7

Rect. Address Setting

No

Yes, No

n.Rectifier Address

-

1-60

Save Settings

Yes

Yes

Carrier Operator

Automatic

Automatic, Others

SIMn Acc Point Name

3GNET

A maximum of 28 characters, including lowercase English letters (a-z), uppercase English letters (A-Z), digits (0-9), and special characters (@_#*-.).

Rect Addr Setting

Dial Parameters

NOTE This parameter is displayed only when Carrier Operator is set to Others.

SIMn Access Point No

*99#

NOTE This parameter is displayed only when Carrier Operator is set to Others.

SIMn User Name

3GNET

NOTE This parameter is displayed only when Carrier Operator is set to Others.

SIMn User Password

-

NOTE This parameter is displayed only when Carrier Operator is set to Others.

A maximum of 27 characters, including lowercase English letters (a-z), uppercase English letters (A-Z), digits (0-9), and special characters (@_#*-.). It is recommended that the password contain at least two types of characters and the length

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

87

SMU02B Site Monitoring Unit User Manual

A Parameter Lists

Second-Level Menu

Third-Level Menu

Default Value

Value Range exceed six characters.

A.4 Parameters Settings Table A-4 Parameters settings menu hierarchy SecondLevel Menu

Third-Level Menu

Fourth-Level Menu

Power System

Basic Parameters

Fifth-Level Menu

Default Value

Value Range

LLVDn General Discon.

Enable

Enable, Disable

AC Type

Three Phases

D-Live Lines, Single Phase, Three Phases, Three Live Lines

-

NOTE This parameter is not displayed when mains exists. The AC type display of the power system should be consistent with the mains.

Sys On Power Limit

-

No

Yes, No

AC Breaker Rated Cap

-

1000 A

1 to 10000

AC Derating Coef

-

0.8

0.0 to 1.0

Load Shunts

-

0

0 to 4

Other Power Type

-

Other Energy

Other Energy, Solar Power

Stage Elec En

-

Disable

Enable, Disable

Battery Disc Mode

-

Battery Life Priority

Battery Life Priority, Staggering Priority

-

2

1 to 10

NOTE This parameter is displayed only when Stag Elec En. is set to Enable.

Max. Disc Times Per NOTE This parameter is

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

88

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

-

10%

5 to 50

Schedule Mode

-

Automatic Mode

Automatic Mode, Manual Mode

Star Time

-

2000-01-01 00:00:00

-

-

2000-01-01 00:00:00

-

Batt Abn Disable Sta

-

Disable

Enable, Disable

End Volt Of Stag Ele

-

48.0 V

45.0 to 53.0

60%

0 to 90

3

1 to 20

displayed only when Stag Elec En. is set to Enable.

Max. Disc Cap. Per D NOTE This parameter is displayed only when Stag Elec En. is set to Enable.

NOTE This parameter is displayed only when Schedule Mode is set to Manual Mode.

End Time NOTE This parameter is displayed only when Schedule Mode is set to Manual Mode.

NOTE This parameter is displayed only when Batt Abn Disable Sta is set to Enable.

End Soh Of Stag Elec NOTE This parameter is displayed only when Batt Abn Disable Sta is set to Enable.

Time of Disable

Issue 04 (2019-08-30)

-

Copyright © Huawei Technologies Co., Ltd.

89

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

-

15 Min

1 to 600

-

Voltage Mode

Voltage Mode, Capacity Mode, Time Mode

44.0 V

35.0 to 56.0

Sta NOTE This parameter is displayed only when Batt Abn Disable Sta is set to Enable.

Duration of Disable NOTE This parameter is displayed only when Batt Abn Disable Sta is set to Enable.

LLVD Parameters

LLVDn Mode NOTE The parameter cannot be set to Capacity Mode for the ESU-A and ESM-BX.

LLVDn Voltage -

NOTE  If the battery voltage is below the value of this parameter, the LLVD route is disconnected. 

LLVDn Con. Volt.

-

51.5 V

37.0 to 58.0 NOTE  If the system voltage exceeds the value of this parameter, the LLVD route is connected. 

LLVDn Capacity

-

15%

NOTE This parameter is displayed only when LLVD Mode is set to

Issue 04 (2019-08-30)

The value of LLVD Voltage must be lower than the value of LLVD Connection Voltage.

Copyright © Huawei Technologies Co., Ltd.

The value of LLVD Connection Voltage must be higher than the value of LLVD Voltage.

0 to 99 NOTE When the remaining battery capacity is less than the preset value and the battery discharge current is less than 0.05C, the LLVD route is disconnected.

90

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

-

360 Min

5 to 1000

Capacity Mode.

LLVDn Time NOTE This parameter is displayed only when LLVD Mode is set to Time Mode.



If the battery discharge duration exceeds this value, the LLVD route is disconnected.

LLVDn HTD Enable

-

Disable

Enable, Disable

LLVDn HTD Temp

-

65 degC

25 to 80

LLVDn TD Enable

-

Disable

Enable, Disable

LLVDn TD Time

-

-

-

LLVDn TD Duration

-

480 Min

1 to 1439

LLVD Delay Time

-

60s

5 to 90

-

Voltage Mode

Voltage Mode, Percentage Mode

AC Phase OV Thres.

-

280 V

60 to 300

AC Phase UV Thres.

-

180 V

60 to 300

Bus Bar OV Thres.

-

58.0 V

53.0 to 60.0

Bus Bar UV Thres.

-

45.0 V

35.0 to 57.0

Bus Ultra OV Thres.

-

59.0 V

53.0 to 60.0

Bus Ultra UV Thres.

-

44.0 V

35.0 to 57.0

AC Abnormal Record

-

280 V

60 to 300

AC Line OV

-

280 V

60 to 600

AC&DC Volt. AC Voltage Para. Mode

Issue 04 (2019-08-30)

NOTE  The power-off time is started when AC power fails (such as a power outage).

Copyright © Huawei Technologies Co., Ltd.

91

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

AC Line UV Thres. #

-

180 V

60 to 600

AC Line Rated Volt. #

-

220 V

60 to 600

AC Phase Rated Volt.

220 V

60 to 300

DC Input OV Thres

-

433 V

86 to 600

DC Input UV Thres

-

74 V

0 to 432

Thres. #

UIM #

ATS DI Cond. ATS DI Cond. For Mains For Mains Fail Fail

-

Close

Open, Close

Controller

Buzzer Enable -

-

No

Yes, No

Buzzer Alm. Duration

-

-

10 Min

1 to 100

IP Net. Priority

-

-

High

High, Medium, Low

Inband Net. Priority

-

-

Medium

High, Medium, Low

Wire. Net. Priority

-

-

Low

High, Medium, Low

Run. Time Sw. Net.

-

-

60 Min

1 to 1440

Traffic Fluct Thres.

-

-

50 MB/Day

0 to 10000

Heartbeat Duration

-

-

120s

10 to 180

IP Net. Timeout

-

-

5 Min

5 to 1440

Inband Net. Timeout

-

-

5 Min

5 to 1440

NOTE This parameter is displayed only when Buzzer Enable is set to Yes.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

92

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Rectifier Group

A Parameter Lists

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Wire. Net. Timeout

-

-

30 Min

30 to 1440

Default Output Volt

-

-

53.5 V

48.0 to 58.0

Lost Phase Enable

-

-

No

Yes, No

OV Prot.Thres.

-

-

59.5 V

56.0 to 60.5

Sequential St. Int

-

-

0s

0 to 20

High Rect. Capacity

-

-

5%

0 to 150

Low Rect. Capacity

-

-

75%

0 to 150

Max. Limited Current

-

-

121%

10 to 121

NOTE The default output voltage of rectifiers after the communication with the monitoring unit fails.

NOTE Interval for starting the rectifiers sequentially.

NOTE Percentage of the expected maximum rectifier output current to the rated rectifier output current. For example, if a power system is configured with three 50 A rectifiers, and you need an output current of 120 A, then set this parameter to 80%, which is obtained from 120 A/(50 A x 3).

WALK-IN Enable

-

-

No

Yes, No

WALK-IN Time

-

-

8s

8 to 200

NOTE This parameter is displayed only when WALK-IN Enable is set to Yes.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

93

SMU02B Site Monitoring Unit User Manual

A Parameter Lists

SecondLevel Menu

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Energy Saving

Hibernation Enable

-

-

No

Yes, No NOTE  No: Hibernation is disabled. 

Hibernation Mode

-

-

Intelligent Mode

NOTE This parameter is displayed only when Hibernation Enable is set to Yes.

Hiber. Without Batt.

-

-

No



High Efficiency Mode: Rectifiers with higher real-time efficiency take precedence for work.



Intelligent Mode: The monitoring unit instructs rectifiers to hibernate based on the rectifier runtime and real-time efficiency.

Yes, No NOTE Indicates whether hibernation is enabled when batteries are not connected. NOTE If you enable hibernation when batteries are not connected to the power system, the loads may experience power failures. Exercise caution when using this function.

-

-

0.2

Min. Working -

0.05 to 1.00 NOTE Ratio of the minimum redundant current to the rated rectifier current.

NOTE This parameter is displayed only when Hibernation Enable is set to Yes.

Issue 04 (2019-08-30)

Intelligent Mode, High Efficiency Mode, Time Mode NOTE  Time Mode: Rectifiers with shorter runtime take precedence for work.

NOTE This parameter is displayed only when Hibernation Enable is set to Yes.

Min. Rdnt. Coef.

Yes: The monitoring unit hibernates rectifiers when the hibernation condition is met.

For example, if the rated rectifier current is 50 A and a redundant current of 10 A is required, set Min. Redundant Coefficient to 0.2 (10 A/50 A = 0.2).

-

2

Copyright © Huawei Technologies Co., Ltd.

1 to 100

94

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Rects.

NOTE Minimum number of working rectifiers allowed after hibernation is enabled.

NOTE This parameter is displayed only when Hibernation Enable is set to Yes.

Best Efficiency Pt.

-

-

55%

-

-

72.0 h

-

-

7 Day

Phase Balance -

1 to 365 NOTE Period for alternating hibernating rectifiers with working rectifiers. When the period expires, the monitoring unit starts all rectifiers. When the rectifiers have worked for 2 hours, the monitoring unit instructs some of them to hibernate again.

NOTE This parameter is displayed only when Hibernation Enable is set to Yes.

-

Disable

NOTE This parameter is displayed only when Hibernation Enable is set to Yes.

Issue 04 (2019-08-30)

0.5 to 168.0 NOTE All rectifiers stop hibernation if the power system experiences an exception. After the power system recovers, rectifiers attempt to hibernate again when the time specified by Hibernation Stop Duration has elapsed.

NOTE This parameter is displayed only when Hibernation Enable is set to Yes.

Circulation Period

10 to 100 NOTE Percentage of the rectifier loading capacity to the rated capacity, at which the rectifier reaches maximum efficiency.

NOTE This parameter is displayed only when Hibernation Enable is set to Yes.

Hiber. Stop Duration

Value Range

Relative Balance, Absolute Balance, Disable NOTE If the configuration of rectifiers meets the three-phase balance requirement and intelligent rectifier hibernation is enabled in a three-phase power system, the rectifiers corresponding to the three phases try to hibernate.

Copyright © Huawei Technologies Co., Ltd.

95

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Mains #

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range



Absolute Balance: The same quantity of rectifiers must correspond to any two phases.



Relative Balance: The difference in quantity between the working rectifiers corresponding to any two phases must be less than or equal to 1.

AC Voltage Mode

-

-

Voltage Mode

Voltage Mode, Percentage Mode

Rated AC Line Volt

-

-

220 V

104 to 520

-

-

220 V

60 to 300

Max Power Ratio

-

-

100%

0 to 100

AC Model

-

-

Single Phase

2 Phase 2 Line, 1 Phase 2 Line, 3 Phase 4 Line, 3 Phase 3 Line

Schedule Enable

-

-

Disable

Enable, Disable

Main Phase OV Thres.

-

-

286 V

242 to 440

NOTE This parameter is available only when AC Voltage Mode is Percentage Mode and AC Model is 3 Phase 3 Line.

Rated AC Volt NOTE This parameter is displayed only when AC Voltage Mode is Percentage Mode and AC Model is 1 Phase 2 Line, 2 Phase 2 Line or 3 Phase 4 Line.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

96

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

A Parameter Lists

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Main Phase UV Thres.

-

-

176 V

2 to 198

Main Phase OV Thres.

-

-

130%

110 to 200

-

-

80%

1 to 90

Main Line OV Thres.

-

286 V

242 to 760

-

176 V

2 to 342

-

130%

110 to 200

NOTE This parameter is displayed only when AC Voltage Mode is Percentage Mode.

Main Phase UV Thres. NOTE This parameter is displayed only when AC Voltage Mode is Percentage Mode.

NOTE This parameter is available only when AC Model is Three Live Lines.

Main Line UV Thres. NOTE This parameter is available only when AC Model is Three Live Lines.

Main Line OV Thres. NOTE This parameter is available only when AC

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

97

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

-

80%

1 to 90

Voltage Mode is Percentage Mode and AC Model is Three Live Lines.

Main Line UV Thres. NOTE This parameter is available only when AC Voltage Mode is Percentage Mode and AC Model is Three Live Lines.

AC High Fre. Thres.

-

-

66 Hz

40 to 70

AC Low Fre. Thres.

-

-

45 Hz

40 to 70

Mains Curr Limit En

-

-

Disable

Disable, Enable

Mains Rated Power

-

-

5000 kW

2 to 5000

-

-

100%

10 to 150

PSU Conv Eff -

-

95%

90 to 98

Schedule Enable

-

-

Disable

Disable, Enable

-

-

60%

0 to 90

NOTE This parameter is displayed only when Mains Curr Limit En is set to Enable.

Imbalance Ratio

NOTE This parameter is displayed only when the SSU is connected.

DOD for

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

98

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

-

-

1h

0 to 24

-

-

8h

1 to 48

-

-

Disable

Disable, Enable

-

-

45 degC

30 to 65

-

-

29 degC

25 to 65

Mains On NOTE This parameter is displayed only when Schedule Enable is set to Enable.

Min Charge Time NOTE This parameter is displayed only when Schedule Enable is set to Enable.

Max Charge Time NOTE This parameter is displayed only when Schedule Enable is set to Enable.

HT Mains On NOTE This parameter is displayed only when Schedule Enable is set to Enable.

HT On Temp NOTE This parameter is displayed only when HT Mains On is set to Enable.

HT Off Temp NOTE This parameter is

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

99

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

-

-

8h

1 to 24

-

-

Disable

Disable, Enable

-

-

5 degC

-10 to +15

-

-

20 degC

0 to 25

-

-

8h

1 to 24

-

-

Disable

Disable, Enable

displayed only when HT Mains On is set to Enable.

HT Mains Runtime NOTE This parameter is displayed only when HT Mains On is set to Enable.

LT Mains On NOTE This parameter is displayed only when Schedule Enable is set to Enable.

LT On Temp NOTE This parameter is displayed only when LT Mains On is set to Enable.

LT Off Temp NOTE This parameter is displayed only when LT Mains On is set to Enable.

LT Mains Runtime NOTE This parameter is displayed only when LT Mains On is set to Enable.

Timed Mains Off

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

100

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

-

-

22:00:00

0:00:00 to 23:59:59

-

-

6h

1 to 12

-

-

Disable

Disable, Enable

-

-

24 h

1 to 24

Longitude

-

-

-

-

Latitude

-

-

-

-

NOTE This parameter is displayed only when Schedule Enable is set to Enable.

Time for Mains Off NOTE This parameter is displayed only when Timed Mains Off is set to Enable.

Runtime to Mains Off NOTE This parameter is displayed only when Timed Mains Off is set to Enable.

Dischg Time Protect NOTE This parameter is displayed only when Schedule Enable is set to Enable.

Max Dischg Time NOTE This parameter is displayed only when Dischg Time Protect is set to Enable.

GPS

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

101

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Acid Battery

A Parameter Lists

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Altitude

-

-

0m

-500 to +10000

Basic Parameters

Battery n Connected

-

Yes

Yes, No

Single-String Cap.

-

150 Ah

5 to 10000

Float Charge Voltage

-

53.5 V

42.0 to 58.0

Boost Charge Voltage

-

Charge Limit Coef.

-

NOTE When temperature compensation is effective, the valid voltage range is 51.5–55.5 V.

56.4 V

NOTE Charge voltage at which lead-acid batteries are being charged in equalized mode.

0.15 C10

0.05 to 0.50 NOTE Battery charge current limit. The charge current limit setting range varies with battery types and is subject to the battery specifications.

NOTE This parameter is not displayed for the fast charge battery (FCB). The monitoring unit automatically adjusts the parameter based on the battery charging status and the ambient temperature.

Issue 04 (2019-08-30)

42.0 to 58.0

BLVD General Discon.

-

Hibernation Enable

-

Battery Cable Length

-

1m

0 to 100

Batt Cable CS

-

35 mm2

1 to 1000

Enable

Disable, Enable NOTE Enable or disable the monitoring unit to control BLVD.

Disable

Disable, Enable NOTE Indicates whether to enable intelligent battery hibernation management.

Copyright © Huawei Technologies Co., Ltd.

102

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

SOC/SOH Calcu Scene

Backup Scene

Backup Scene, Cyclic Scene

Attenuation Coef

-

0.80

0.00 to 1.00

Block Voltage

-

2V

2 V, 12 V

TC Coefficient

-

80 mV/degC

0 to 500

Area

Temp. Comp. Para.

NOTE This parameter is: For 48 V battery string, the amplitude of the battery float charge voltage that needs to be adjusted for each change of 1°C. Set this parameter based on the actual specifications of the battery. For example, if the temperature compensation coefficient of each 2 V battery is 3.33 mV/degC and each 48 V battery string comprises 24 2 V batteries, then set this parameter to 80 mV/degC, which is calculated as follows: 3.33 x 24 = 80.

Nominal Temperature

BLVD Parameters

-

25 degC

5 to 45

TC Upper Thres. -

45 degC

40 to 45

TC Lower Thres.

-

5 degC

0 to 25

BLVD Disconnect Mode

-

Voltage Mode

Voltage Mode, Capacity Mode, Time Mode

BLVD LVD Voltage

-

43.2 V

35.0 to 56.0 NOTE If the battery voltage is below the value of this parameter, the BLVD route is disconnected. The value of BLVD Voltage must be lower than the value of BLVD Connection Voltage.

BLVD Con. Volt.

Issue 04 (2019-08-30)

-

51.5 V

Copyright © Huawei Technologies Co., Ltd.

37.0 to 58.0 NOTE If the system voltage exceeds the value of this parameter, the BLVD route is connected.

103

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

The value of BLVD Connection Voltage must be higher than the value of BLVD Voltage.

BLVD Time

-

480 Min

NOTE This parameter is displayed only when BLVD Disconnect Mode is set to Time Mode.

BLVD Low Capacity

NOTE  The power-off time is started when AC power fails (such as a power outage). 

-

5%

Issue 04 (2019-08-30)

If the battery discharge duration exceeds this value, the BLVD route is disconnected.

0 to 99 NOTE When the remaining battery capacity is less than the preset value and the battery discharge current is less than 0.05C, the BLVD route is disconnected.

NOTE This parameter is displayed only when BLVD Disconnect Mode is set to Capacity Mode.

Temp. Prot. Para.

5 to 1000

BLVD Delay Time

-

60s

5 to 90

Very HT Prot. Mode

-

Reduce DC Voltage

Reduce DC Voltage, Disable, Disconnect Battery

Very HT Prot. Volt.

-

51.5 V

42.0 to 53.0

HT Alarm Thres.

-

50 degC

25 to 80

Very HT Alarm Thres.

-

NOTE This default value varies in accordance with the battery performance. 55 degC is set by default for the TCB.

53 degC

25 to 80

NOTE This default value varies in accordance with the battery performance. 58degC is set by default for the

Copyright © Huawei Technologies Co., Ltd.

104

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

TCB.

Charge Parameters

Issue 04 (2019-08-30)

LT Alarm Thres. -

-10 degC

-20 to +20

Very LT Alarm Thres.

-20 degC

-20 to +20

Enable

Enable, Disable

-

Auto. EC Enable -

NOTE Indicates whether to enable automatic equalized charging.

FC-EC Cur. Coef.

-

FC-EC Cur. Duration

-

30 Min

2 to 1440

FC-EC Cap. Percent

-

70%

50 to 100

Timed EC Enable

-

Timed EC Interval

-

Timed EC Duration

-

EC-FC Cur. Coef.

-

0.05 C10

0.01 to 0.25 NOTE If the duration within which the battery charge current is higher than Float to Equalized Charge Current Coefficient exceeds the value of Float to Equalized Charge Current Duration, batteries automatically enter equalized charging.

NOTE If the battery charge capacity is lower than Float to Equalized Charge Capacity Percent, batteries automatically enter equalized charging.

Enable

Enable, Disable NOTE Indicates whether to enable scheduled equalized charging.

30 Day

1 to 365 NOTE Period for scheduled equalized charging.

9h

1 to 24 NOTE Duration for each scheduled equalized charging period.

0.01 C10

Copyright © Huawei Technologies Co., Ltd.

0.01 to 0.25 NOTE If the duration within which the battery charge current is

105

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

lower than Equalized to Float Charge Current Coefficient exceeds the value of Equalized to Float Charge Current Duration, batteries automatically enter float charging.

EC-FC Cur. Duration

-

30 Min

2 to 540

EC Max Duration

-

18 h

5 to 48 NOTE If the equalized charging duration exceeds the value of this parameter, batteries automatically enter float charging.

Mains Recovery EC En

Disable

AC Fail EC Duration

10 Min

-

NOTE Indicates whether to perform equalized charging after the AC power is restored.

0 to 30 NOTE If the AC power failure duration exceeds the value of this parameter, batteries automatically enter equalized charging after the AC power is restored.

NOTE This parameter is displayed only when Mains Recovery EC En is set to Yes.

Issue 04 (2019-08-30)

Disable, Enable

Charge Efficiency

-

0.98

0.80 to 1.00

Fast Charge Coef.

-

0.4 C10

0.25 to 0.5

Load Temp.Limit En.

-

Disable

Enable, Disable

Batt. Temp.Limit En.

-

Disable

Enable, Disable

Fast Charge Enable

-

Enable

Enable, Disable

NOTE Current limit coefficient for fast charging. The charge current limit setting range varies with battery types and is subject to the battery specifications.

Copyright © Huawei Technologies Co., Ltd.

106

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

Standard Test Para.

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Batt. Life Opt. En.

-

Disable

Enable, Disable

AC Fail Test Enable

-

Disable

Disable, Enable NOTE Indicates whether the standard battery test is allowed if an AC power outage occurs.

Time Test Mode -

Disable

Disable, Scheduled Test, Planned Test NOTE The mode in which the monitoring unit starts an automatic test on schedule or as planned.

Sche. Test St. Time

-

21:00:00

NOTE Time when a scheduled test starts.

NOTE This parameter is displayed only when Time Test Mode is set to Scheduled Test.

Sche. Test St. Period

-

90 Day

-

0

0 to 6 NOTE Number of planned tests within a year.

NOTE This parameter is displayed only when Time Test Mode is set to Planned Test.

Pre-EC Enable

2 to 999 NOTE Interval for starting a scheduled test.

NOTE This parameter is displayed only when Time Test Mode is set to Scheduled Test.

Annual Battery Tests

HH:MM:SS

-

Enable

Disable, Enable NOTE Indicates whether the monitoring unit allows charging batteries in equalized mode before a standard battery test starts.

Constant Cur.

Issue 04 (2019-08-30)

-

Disable

Copyright © Huawei Technologies Co., Ltd.

Disable, Enable

107

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Test

Value Range

NOTE Indicates whether batteries are allowed to discharge at a constant current in a standard battery test.

Constant Test Cur.

-

9999 A

1 to 9999 NOTE Batteries discharge at this current in a standard battery test.

NOTE This parameter is displayed only when Constant Cur. Test is set to Yes.

Test End Voltage

-

Test End Capacity

-

Planned Test Time n

-

MM-DD HH:MM MM-DD HH:MM

Test End Time

-

480 Min

46.0 V

44.2 to 53.0 NOTE If the battery voltage is below the value of this parameter, the battery test ends.

20%

0 to 99 NOTE If the battery capacity is below the value of this parameter, the battery test ends.

1 to 6000 NOTE If the standard battery test duration reaches the value of this parameter, the battery test ends.

Test End Temperature

-

5 degC

-5 to +15 NOTE If the battery temperature is lower than Test End Temperature, the battery test ends.

SOH Estimation Times

3

1 to 30

1

0.5 to 1.5

NOTE This parameter is displayed only when License is set to enable.

SOH Batch Factor

Issue 04 (2019-08-30)

-

Copyright © Huawei Technologies Co., Ltd.

108

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Short Test Enable

-

Disable

Disable, Enable

Short Test Period

-

Short Test Time

-

NOTE This parameter is displayed only when License is set to enable.

Short Test Para.

NOTE Indicates whether to allow the monitoring unit to perform short tests automatically.

30 Day

1 to 360 NOTE Period for an automatic short test.

5 Min

1 to 240 NOTE If the test duration exceeds the value of this parameter, the monitoring unit exits from the short test.

Alarm Parameters

Issue 04 (2019-08-30)

Short Test End Volt.

-

Overcur. Alm. Thres.

-

0.25 C10

0.05 to 1.00

Low Cap. Alm. Thres.

-

30%

0 to 90

Volt Unbalance Mode

-

Percentage Mode

Percentage Mode, Voltage Mode

Volt Imb Thres

-

10%

5 to 30

Batt Incorrect Curr

-

5.0 A

1 to 100

Batt Incorrect Time

-

5 min

1 to 60

Cur. Imb. Thres. -

0.05 C10

0.00 to 1.00

Cell Imb. Thres.

-

20%

5 to 30

Bat Disch Alm Thres

-

49.7 V

40.0 to 56.0

45.0 V

44.2 to 53.0 NOTE If the battery voltage is below the value of this parameter, the monitoring unit exits from the short test.

Copyright © Huawei Technologies Co., Ltd.

109

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Bat Disch Delay Time

0 Min

0 to 600

SOH Subhealth Val

-

70%

1 to 100

-

50%

1 to 100

-

45.0 V

37.0 to 57.0

-

59.0 V

48.0 to 60.0

Battery Install Time

-

-

-

Volt. Detect Mode

-

Middle Point Volt.

Middle Point Volt., Cell Volt.

NOTE This parameter is displayed only when License is set to enable.

SOH Aging Value NOTE This parameter is displayed only when License is set to enable.

Batt Under Vol Thres NOTE This parameter is displayed only when FSU & Power Supply is set to Only FSU or Power and FSU.

Batt Over Vol Thres NOTE This parameter is displayed only when FSU & Power Supply is set to Only FSU or Power and FSU.

Other Parameters

NOTE When connecting a signal cable for monitoring middle point voltages, select Middle Point Volt.. When connecting a signal cable for monitoring battery voltages, select Cell Volt..

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

110

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Shunt Max. Volt.

-

25 mV

5 to 150

Shunt Max. Cur. -

300 A

5 to 3000

Power Backup Mode

Time Mode

Time Mode, Capacity Mode

LLVD Backup Time

-

NOTE Specifies a mode for detecting power backup capability.

-

180 Min



Time Mode: based on backup time.



Capacity Mode: based on backup capacity.

0 to 9999 NOTE This parameter is displayed if Backup Mode is set to Time Mode. Sets the expected duration from when batteries start to supply power to when loads are disconnected. For example, if you require that loads be powered for 200 minutes since batteries start to supply power, set this parameter to 200Min. If the actual power supply duration is shorter than the expected duration, the monitoring unit generates a Backup Warning alarm.

BLVD Backup Time

-

480 Min

0 to 9999 NOTE This parameter is displayed if Backup Mode is set to Time Mode. Sets the expected duration from when batteries start to supply power to when batteries are disconnected. If the actual power supply duration is shorter than the expected duration, the monitoring unit generates a Backup Warning alarm.

LLVD Backup Capacity

-

75%

NOTE This parameter is

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

5 to 100 NOTE This parameter is displayed if Backup Mode is set to

111

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

displayed only when Power Backup Mode is set to Capacity Mode.

Value Range

Capacity Mode. Sets the expected discharged battery capacity within the duration from when batteries start to supply power to when loads are disconnected. If the actual discharged battery capacity is less than the expected value, the monitoring unit generates a Backup Warning alarm.

BLVD Backup Capacity

-

95%

5 to 100 NOTE This parameter is displayed if Backup Mode is set to Capacity Mode.

NOTE This parameter is displayed only when Power Backup Mode is set to Capacity Mode.

Sets the expected discharged battery capacity within the duration from when batteries start to supply power to when batteries are disconnected. If the actual discharged battery capacity is less than the expected value, the monitoring unit generates a Backup Warning alarm.

BackBatt # Basic Parameters

Issue 04 (2019-08-30)

Battery n Connected

-

Yes

Yes, No

Single-String Cap.

-

150 Ah

5 to 10000

Float Charge Voltage

-

53.5 V

42.0 to 58.0

Boost Charge Voltage

-

56.4 V

42.0 to 58.0

Charge Limit Coef.

-

0.15 C10

0.05 to 0.50

Intelligent Dormancy

-

Disable

Disable, Enable

SOC/SOH Calcu Scene

Backup Scene

Backup Scene, Cyclic Scene

Attenuation Coef

-

0.80

0.00 to 1.00

Block Voltage

-

2V

2 V, 12 V

Battery Cable

-

1m

0 to 100

Copyright © Huawei Technologies Co., Ltd.

112

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Batt Cable CS Area

-

35 mm2

1 to 1000

TC Coefficient

-

80 mV/degC

0 to 500

Length

Temp. Comp. Para.

NOTE Amplitude of the battery float charge voltage that needs to be adjusted for each change of 1°C. Set this parameter based on the temperature compensation coefficient for a 48 V battery string and battery specifications. For example, if each battery is 3.33 mV and each 48 V battery string comprises 24 batteries, then set this parameter to 80 mV, which is calculated as follows: 3.33 x 24 = 80.

Nominal Temperature

-

25 degC

5 to 45 NOTE Temperature at the middle point for temperature compensation. Set this parameter based on battery specifications.

TC Upper Thres. -

45 degC

40 to 45 NOTE Highest temperature for temperature compensation.

BLVD Parameters

Temp. Prot. Para.

TC Lower Thres.

-

BLVD Low Voltage

-

43.2 V

35.0 to 56.0

BLVD Con. Volt.

-

51.5 V

37.0 to 58.0

BLVD Low Capacity

-

5%

5 to 99

Very HT Prot. Mode

-

Reduce DC Voltage

Disable, Reduce DC Voltage, Disconnect Battery

5 degC

0 to 10 NOTE Lowest temperature for temperature compensation.

NOTE If the battery temperature

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

113

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

exceeds the value of Very High Temperature Alarm Threshold, the monitoring unit takes a protective measure that you selected.

Very HT Prot. Volt.

-

HT Alarm Thres.

-

Very HT Alarm Thres.

-

51.5 V

42.0 to 53.0 NOTE Under Reduce DC voltage protection mode, if the battery temperature exceeds the Very High Temperature Alarm Threshold, the monitoring unit adjusts the battery charging voltage to Very High Temperature Protection Voltage.

50 degC

25 to 80 NOTE If the battery temperature exceeds the value of High Temperature Alarm Threshold, the monitoring unit will generate a Battery High Temperature alarm.

53 degC

25 to 80 NOTE If the battery temperature exceeds the value of Very High Temperature Alarm Threshold, the monitoring unit will generate a Battery Very High Temperature alarm.

LT Alarm Thres. -

-10 degC

-20 to +20 NOTE If the battery temperature is below the value of Low Temperature Alarm Threshold, the monitoring unit will generate a Battery Low Temperature alarm.

Charge

Issue 04 (2019-08-30)

Very LT Alarm Thres.

-

Timed EC

-

-20 degC

-20 to +20 NOTE If the battery temperature is below the value of Very Low Temperature Alarm Threshold, the monitoring unit will generate a Battery Very Low Temperature alarm.

Enable

Copyright © Huawei Technologies Co., Ltd.

Enable, Disable

114

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

A Parameter Lists

Third-Level Menu

Fourth-Level Menu

Parameters

Enabled

Standard Test Para.

Issue 04 (2019-08-30)

Fifth-Level Menu

Default Value

Value Range

Timed EC Interval

-

30 Day

1 to 365

Max Timed EC Duration

-

9h

1 to 24

Charge Efficiency

-

0.98

0.80 to 1.00

FC-EC Cur. Coef.

-

0.05 C10

0.01 to 0.25

FC-EC Cap. Percent

-

70%

50 to 100

EC-FC Cur. Coef.

-

0.01 C10

0.01 to 0.25

EC-FC Cur. Duration

-

30 Min

2 to 540

EC Max Duration

-

18 h

5 to 48

FC-EC Cur. Duration

-

30 Min

2 to 1440

Auto. EC Enable -

Enable

Enable, Disable

Mains Recovery EC En

Disable

Enable, Disable

AC Fail EC Duration

-

10 Min

0 to 30

Fast Charge Coef.

-

0.40 C10

0.25 to 0.5

Load Temp.Limit En.

-

Disable

Enable, Disable

Batt. Temp.Limit En.

-

Disable

Enable, Disable

Fast Charge Enable

-

Enable

Enable, Disable

Batt. Life Opt. En.

-

Disable

Enable, Disable

Time Test Mode -

Disable

Disable, Planned Test, Scheduled Test

Pre-EC Enable

Enable

Enable, Disable

-

Copyright © Huawei Technologies Co., Ltd.

115

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Constant Cur. Test

-

Disable

Enable, Disable

Constant Test Cur.

-

9999 A

1 to 9999

-

HH:MM:SS

HH:MM:SS

-

90 Day

2 to 999

NOTE This parameter is displayed only when Constant Cur. Test is set to Enable.

Sche. Test St. Time NOTE This parameter is displayed only when Time Test Mode is set to Planned Test.

Sche. Test St. Period

NOTE Interval for starting a scheduled test.

NOTE This parameter is displayed only when Time Test Mode is set to Scheduled Test.

Annual Battery Tests

-

0

0 to 6

Planned Test Time n

-

MM-DD HH:MM MM-DD HH:MM

AC Fail Test Enable

-

Disable

Enable, Disable

Test End Voltage

-

46.0 V

44.2 to 53.0

Test End Capacity

-

20%

0 to 99

Test End Time

-

480 Min

1 to 6000

Test End

-

5 degC

-5 to +15

NOTE This parameter is displayed only when Time Test Mode is set to Planned Test.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

116

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

3

1 to 30

-

1

0.5 to 1.5

Short Test Enable

-

Disable

Enable, Disable

Short Test Period

-

30 Day

1 to 360

Short Test Time

-

5 Min

1 to 240

Short Test End Volt.

-

45.0 V

44.2 to 53.0

Overcur. Alm. Thres.

-

0.25 C10

0.05 to 1.00

Low Cap. Alm. Thres.

-

30%

0 to 90

80

1 to 99

-

60

1 to 99

-

49.7 V

40 to 56

Temperature SOH Estimation Times NOTE This parameter is displayed only when License is set to enable.

SOH Batch Factor NOTE This parameter is displayed only when License is set to enable.

Short Test Para.

Alarm Parameters

SOH Sub-health Thres NOTE This parameter is displayed only when License is set to enable.

SOH Deterio Thres NOTE This parameter is displayed only when License is set to enable.

Bat Disch Alm Thres

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

117

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Setup Parameter

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Bat Disch Delay Time

0 Min

0 to 600

Other Parameters

Battery Install Time

-

-

-

Basic Parameters

Battery Type Number

-

1

1 to 4

Battery Factory

-

Other

AGISSON, Coslight, Dengta, Eltek, EnerSys, Exide, LEOCH, Narada, NorthStar, Shoto, Other

Battery Model

-

12V VRLA

DCB-A, DCB-A1, DCB-B, DCB-Y, ESU-A, ESM-A, ESM-BX, FCB-A, FCB-B, SCB-A, SCB-A1, TCB-A, TCB-B, TCB-C, 12V VRLA, 2V VRLA, FLOOD, 6-GFM-X, 6-GFMF, Rebak-F4899T, 12TD-F, SBS-F, M12V-FT, LPF12-H, 6-GFM-F, 12NDF, Blue, Red, 6-FMX, 6-XFMJ, GFM, BBS 4840Z

Load Elec Stat Src

-

No

No, Shunt, EFUSE, DC Ammeter, DCDB

Enable Sign Verify

-

Disable

Enable, Disable

TLS 1.0

-

Disable

Enable, Disable

TCB auto-sensing

-

Yes

Yes, No

Include Public Load

-

No

Yes, No

Load Elec Stat Start

-

1

1 to 28

Hybrid Scenario -

No

Yes, No

ATS Number

-

0

0 to 2

Sensor Config AC SPD

-

Yes

Yes, No

DC SPD

-

Yes

Yes, No

Door Sensor

-

No

Yes, No

Water Sensor

-

Yes

Yes, No

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

118

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Smoke Sensor

-

Yes

Yes, No

Ambient Temp. Sensor

-

Yes

Yes, No

Ambient Humi. Sensor

-

Yes

Yes, No

Temp1 Sensor

-

No

Yes, No

Temp2 Sensor

-

Yes

Yes, No

Batt. Temp. Sensor 1

-

No

Yes, No

Batt. Temp. Sensor 2

-

No

Yes, No

Batt. Temp. Sensor 3

-

No

Yes, No

Vibration Sensor -

No

DIN1-6, No

Audible Visual Alarm

-

No

ALM1-7, No

IR sensor connected

-

No

DIN1-6, No

IR Sensor Connected 2

-

No

DIN1-6, No, GATE

IR Sensor Connected 3

-

No

DIN1-6, No, GATE

Glass Brk Snsr Cnnct

-

No

DIN1-6, No

Water Sensor connect

-

No

DIN1-6, No

Smoke Sensor connect

-

No

DIN1-6, No

Nonintelligent Lock

-

No

Yes, No

Door Lock State -

No

DIN1-6, No

NOTE This parameter is displayed only when FSU & Power Supply is set to Only FSU or Power and FSU.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

119

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

-

No

ALM1, ALM2, ALM3, ALM8, No

-

Open

Open, Close

-

Excellent

Average, Fair, Good, Excellent

NOTE This parameter is displayed only when Nonintelligent Lock is set to Yes.

Nonintel. Lock ALM NOTE This parameter is displayed only when Nonintelligent Lock is set to Yes.

ALMn Default State NOTE This parameter is displayed only when Nonintelligent Lock is set to Yes and ALM For Lock is not set to No.

Camera #

Camera n

NOTE Applies when the serial port camera is connected.

Image Quality

NOTE Image definition.

Image Format

-

640 x 480

160 x 120, 320 x 240, 640 x 480

Capture Interval

-

40s

20 to 600 NOTE Interval for taking pictures.

Issue 04 (2019-08-30)

Number Before Alarm

-

Number After Alarm

-

5 Pcs

1 to 10 NOTE Sets how many pictures taken before alarm generation will be saved.

5 Pcs

Copyright © Huawei Technologies Co., Ltd.

1 to 10 NOTE Sets how many pictures taken after alarm generation will be saved.

120

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Camera #

Third-Level Menu

Camera n

NOTE Applies when the IP camera is connected.

DTS #

DTS Group

DTSn

DCDB #

DCDB n

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Hist. Photos Uploaded

-

0 Pcs

0 to 10

Forbid Camera

-

No

Yes, No

Capture Interval

-

40s

20 to 60

Forbid Camera

-

No

Yes, No

Backup Batt Enable

-

Yes

Yes, No

DTS Transfers Limit

-

20

1 to 100

MainBatt Swit. Volt

-

43.2 V

35.0 to 56.0

BackBatt n Swit. Volt

43.2 V

35.0 to 56.0

LeBatt Transfer Mode

-

Discharge apart

Discharge apart, Discharge together

LiBatt Transfer Mode

-

Active/Standby

Active/Standby, Mutual backup

MainBatt UV Thres

-

46.0 V

46.0 to 57.0

MainBatt UV HY

-

1.0

1.0 to 5.0

BackBatt UV Thres

-

46.0 V

46.0 to 57.0

BackBatt UV HY

-

1.0

1.0 to 5.0

Basic Parameters

Load Setting Mode

All Branch

All Branch, Single Branch

Load Off Mode

Voltage Mode

Voltage Mode, Time Mode

Yes

Yes, No

Load Off Enable Load Off Enable NOTE This parameter is available

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

121

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Yes

Yes, No

No

Yes, No

No

Yes, No

51.5 V

37.0 to 58.0

only when Load Setting Mode is All Branch.

Load n Off Enable NOTE This parameter is available only when Load Setting Mode is Single Branch.

Load TD Enable NOTE This parameter is available only when Load Setting Mode is All Branch.

Load n TD Enable NOTE This parameter is available only when Load Setting Mode is Single Branch.

Load On/Off Para.

Load On Voltage NOTE This parameter is available only when Load Setting Mode is All Branch.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

122

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Load n On Volt

51.5 V

37.0 to 58.0

43.2 V

35.0 to 56.0

43.2 V

35.0 to 56.0

6000 Min

0 to 6000

6000 Min

0 to 6000

NOTE This parameter is available only when Load Setting Mode is Single Branch.

Load Off Voltage NOTE This parameter is available only when Load Setting Mode is All Branch.

Load n Off Enable NOTE This parameter is available only when Load Setting Mode is Single Branch.

Load Off Time NOTE This parameter is available only when Load Setting Mode is All Branch and Load Off Mode is Time Mode.

Load n Off Time

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

123

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

HH:MM:SS

HH:MM:SS

HH:MM:SS

HH:MM:SS

480 Min

1 to 1439

480 Min

1 to 1439

This parameter is available only when Load Setting Mode is Single Branch and Load Off Mode is Time Mode. Load TD Time NOTE This parameter is available only when Load Setting Mode is All Branch.

Load n TD Time NOTE This parameter is available only when Load Setting Mode is Single Branch.

Load TD Duration NOTE This parameter is available only when Load Setting Mode is All Branch.

Load n TD Duration NOTE This parameter is

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

124

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Yes

Yes, No

Yes

Yes, No

30 A

3 to 30

30 A

3 to 30

available only when Load Setting Mode is Single Branch.

Load Overcur Thres

Load OvCur Prot En NOTE This parameter is available only when Load Setting Mode is All Branch.

Load n OvCur Prot En NOTE This parameter is available only when Load Setting Mode is Single Branch.

Load Br OC Thres. NOTE This parameter is available only when Load Setting Mode is All Branch.

Load n OC Thres. NOTE This parameter is available only when Load Setting Mode is

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

125

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Single Branch.

Load OvTmp Para.

Load OvTmp Yes Proc En

Yes, No

NOTE This parameter is available only when Load Setting Mode is All Branch.

Load n Yes OvTmp Proc En

Yes, No

NOTE This parameter is available only when Load Setting Mode is Single Branch.

Consumption Config

Load User Config

0

0 to 6

0

0 to 6

0

0 to 10

NOTE This parameter is available only when Load Setting Mode is All Branch.

Load n to User NOTE This parameter is available only when Load Setting Mode is Single Branch.

Load n to

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

126

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

No

Yes, No

Branch NOTE This parameter is available only when Load Setting Mode is Single Branch.

Electronic Lock

E-Lock Group Access Card Aut Lock Close Delay

-

10s

3 to 240

Cabinet Name

-

-

-

Mech Key Enable

-

Yes

Yes, No

Mech Key Delay -

3 min

1 to 30

Number of Batteries

-

0

0 to 96

BIM Volt. Rec. En.

-

No

No, Yes

BIM Res. Rec. En.

-

No

No, Yes

BIM Temp. Rec. En.

No

No, Yes

BIM SOH Rec. En.

-

No

No, Yes

AC Rated Frequency

-

-

50 Hz

50, 60

Detected Object

-

-

AC Total Input

None, AC Total Input, AC Main Equipment, AC TC Equipment, AC Other Equipment

AC OV Thres. -

-

280 V

60-300

AC UV Thres. -

-

180 V

60-300

Channel n Setting

-

-

Disable

Disable, AI (4-20mA), AI (0-10VDC), DI

CH n Unit

-

-

degC

degC, %RH, DCV, ACV, A

Electronic Lock n

CIM

AIM

NIM02D

CIM Equip n

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

127

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

A Parameter Lists

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

CH n Alarm Condition

-

-

Close

Open, Close

CH n Up Measure Value

-

-

80

-1000 to +1000

CH n Lo Measure Value

-

-

-40

-1000 to +1000

CH n Upper Limit

-

-

20

-

CH n Lower Limit

-

-

4

-

CH n High Alarm On

-

-

Disable

Enable, Disable

CH n High Alarm Thres

-

-

40

-

CH n SuperHi Alm On

-

Disable

Enable, Disable

CH n SuperHi Alm Thre

-

60

-

CH n Low Alarm On

-

-

Disable

Enable, Disable

CH n Low Alarm Thres

-

-

-10

-

CH n SuperLo Alm On

-

Disable

Enable, Disable

CH n SuperLo Alm Thre

-

-20

-

FE n Net Mode Set

-

-

WAN

WAN, LAN

Rated Capacity

-

40 Ah

1 to 300

Charging Voltage

-

54.0 V

53.5 to 56.5

BLVD Enable

-

Yes

Yes, No

Battery n Connected

-

Yes

Yes, No

BLVD Mode

-

Voltage Mode

Voltage Mode, Time Mode

Low Cap Basic Li-ion Batt Parameters # NOTE This parameter is displayed only when Battery BLVD

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

128

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

Model is Parameters set to BBS 4840Z.

Alarm Parameters

Other Parameters

Li Battery #

Basic Parameters

NOTE  This param eter is displa yed only when Batter y Model is set to ESMA, ESUA or ESMBX. 

There are differe nces in the defaul t param eters of the batter y when the Batter

Issue 04 (2019-08-30)

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

BLVD Time

-

480 Min

5 to 1000

BLVD Capacity

-

5%

0 to 100

BLVD Voltage

-

43.2 V

35.0 to 47.8

BLVD Con. Volt.

-

51.5 V

37.0 to 53.0

HT Alarm Thres.

-

50 degC

25 to 80

LT Alarm Thres. -

-10 degC

-35 to +20

Shunt Max. Volt.

-

25 mV

5 to 150

Shunt Max. Cur. -

300 A

5 to 3000

Installation Time -

-

-

Batt Atten Coef

-

0.80

0.00 to 1.00

Battery n Connected

-

No

Yes, No

Discharge Mode -

Auto

Auto, Constant Volt Dischg

Priority Charger

-

Disable

Enable, Disabale

iLock Enable

-

Lock Enable

Lock Enable, Lock Disable

-

Host Manage

Host Manage, Auto Manage

-

72

8 to 720

NOTE This parameter is displayed only when the battery anti-theft function is supported.

BMU Manage Model NOTE This parameter is displayed only when the battery anti-theft function is supported.

iLock Verify Timeout NOTE This parameter is displayed only when the battery anti-theft

Copyright © Huawei Technologies Co., Ltd.

129

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

y Model or Batter y Capac ity is differe nt.

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Battery Group Vendor

-

-

-

BMU Quantity

-

0

0 to 32

Cycle Mode

-

Li-Ion primary

Li-Ion primary, Li-Ion And Acid cycle, Li-Ion standby

Charge Efficiency

-

1.00

0.80 to 1.00

-

56.4 V

42.0 to 58.0

-

54.5 V

42.0 to 58.0

Chg Curr Limit Coef

-

0.4 C10

0.05 to 1.00

Chg Over Curr THR

-

0.75 C10

0.15 to 1.00

Load Temp.Limit En.

-

Disable

Disable, Enable

Batt. Temp.Limit En.

-

Disable

Disable, Enable

Batt. Life Opt. En.

-

Disable

Disable, Enable

HT Alarm Thres.

-

50 degC

35 to 70

0

-50 to 0

function is supported.

Charge Parameters

NOTE This parameter only displayed when Hybrid Scenario is set to No.

EC Voltage NOTE This parameter only displayed when Hybrid Scenario is set to No.

FC Voltage NOTE This parameter only displayed when Hybrid Scenario is set to No.

Alarm Parameters

LT Alarm Thres. -

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

130

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

DCDU #

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

DO1 Alarm Action

-

Close

Close, Open

DO2 Alarm Action

-

Close

Close, Open

-

Standard mode

Standard mode, Energy saving mode, Mute mode

LVD Mode

-

Voltage Mode

Voltage Mode, Time Mode

Backup Mode enable

-

Disable

Disable, Enable

Basic Information

User Config

None

None, User1-6

Amb. HT Thres.

55 degC

25 to 80

Amb. LT Thres.

-20 degC

-20 to +20

Amb. HH Thres.

95%

0 to 100

Amb. LH Thres.

5%

0 to 100

Heater Alm DI Conf

None

DIN1-6, None

LLVD Enable

Yes

Yes, No

LLVD Voltage

45.0 V

35.0 to 56.0

LLVD Time

180 Min

-

LLVD Con. Volt.

51.5 V

37.0 to 58.0

BLVD Enable

Yes

Yes, No

BLVD Time

480 Min

-

BLVD Volt.

43.2 V

35.0 to 56.0

BLVD Con. Volt.

51.5 V

37.0 to 58.0

Door Sensor

None

Yes, None

Smoke Sensor

Yes

Yes, None

DCDU Group TC Mode

DCDU n

LLVD Parameters

Sensor Config

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

131

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

A/C Config

EFUSE Group #

EFUSE n

Basic Parameters

Fifth-Level Menu

Default Value

Value Range

Water Sensor Yes

Yes, None

Ambient Temp. Sensor

Yes

Yes, None

Ambient Humi. Sensor

Yes

Yes, None

Indoor Vent TS

Yes

Yes, None

Outdoor Amb. TS

Yes

Yes, None

Temp1 Sensor

None

Yes, None

Temp2 Sensor

None

Yes, None

Comp. Start Temp.

28 degC

20 to 50

HT Alarm Thres.

50 degC

25 to 80

Load Off Mode

Voltage Mode

Time Mode, Voltage Mode

On/Off Setting

Single

All, Single

Load Overcur Setting

Single

All, Single

Load n Off Enable

Yes

Yes, No

No

Yes, No

NOTE This parameter is displayed only when On/Off Setting is Single.

Load Off Enable NOTE This parameter is displayed

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

132

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

No

Yes, No

No

Yes, No

43.2 V

35.0 to 56.0

43.2 V

35.0 to 56.0

51.5 V

37.0 to 58.0

only when On/Off Setting is ALL.

Load n TD Enable NOTE This parameter is displayed only when On/Off Setting is Single.

Load TD Enable NOTE This parameter is displayed only when On/Off Setting is ALL.

Load Off Voltage

Load n Off Volt NOTE This parameter is displayed only when On/Off Setting is Single.

Load Off Voltage NOTE This parameter is displayed only when On/Off Setting is All.

Load On Voltage

Load n On Volt NOTE This parameter is displayed

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

133

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

51.5 V

37.0 to 58.0

Load n Off Time

6000 Min

0 to 6000

Load Off Time

6000 Min

0 to 6000

-

-

480 Min

1 to 1439

only when On/Off Setting is Single.

Load On Voltage NOTE This parameter is displayed only when On/Off Setting is All.

Load Off Time

NOTE This parameter is NOTE displayed only This when Load Off parameter is Mode is Time displayed Mode. only when On/Off Setting is Single.

NOTE This parameter is displayed only when On/Off Setting is All.

Load Time Down

Load TD Time

NOTE NOTE This parameter is This displayed only parameter is when Load TD displayed Enable is Yes. only when On/Off Setting is All.

Load TD Duration NOTE This parameter is displayed

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

134

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

-

-

480 Min

1 to 1439

15.0 A

0.5 to 20.0

15.0 A

0.5 to 20.0

only when On/Off Setting is All.

Load n TD Time NOTE This parameter is displayed only when On/Off Setting is Single.

Load n TD Duration NOTE This parameter is displayed only when On/Off Setting is Single.

Load Overcur. Thres.

Load n Overcur Thres NOTE This parameter is displayed only when Load Overcur. Setting is Single.

Load Overcur. Thres. NOTE  This paramete r is displayed only when Load Overcur. Setting is All. 

Issue 04 (2019-08-30)

When the

Copyright © Huawei Technologies Co., Ltd.

135

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

All Loads to User

None

None, User 1-6

Load n to User

None

actual current exceeds the 1.2 times of the load overcurre nt threshold , the EFUSE automati cally enables or disables the output. The appropria te current can be manually resumed only after the overcurre nt fault is rectified.

Consumption Config

NOTE User SNs must be consecutive; In a multi-LLVD scenario, use SNs must map to LLVD SNs.

NOTE User SNs must be consecutive.

NOTE This parameter is displayed only when Load Elec Stat Src is EFUSE.

Load n to Branch

None, User 1-6

None

None, Branch1-10

NOTE This parameter is displayed only when Load Elec Stat Src is No EFUSE.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

136

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Temp. Control #

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Other Parameters

Input OV Thres

58.0 V

58.0 to 60.0

Input UV Thres

42.0 V

38.0 to 45.0

Set Cabinet Name

-

-

-

-

-

-

-

-

A/C Stop Temp. -

-

-

Indoor Vent TS

-

Yes

Yes, No

Outdoor Amb. TS

-

Yes

Yes, No

Backup Mode enable

-

Disable

Enable, Disable

A/C On HighTemp

-

40 degC

20 to 50

A/C On Higher Temp

-

45 degC

25 to 55

A/C Rotation Runtime

-

12 h

2 to 168

A/C Control Mode

-

-

-

A/C Config. Mode En

-

Disable

Enable, Disable

System HN Thres.

-

68 dB

40 to 80

Btemp for A/C On

-

30 degC

10 to 55

Low-Temp Mode Enable

-

Disable

Enable, Disable

Low-Temp Start Temp

-

-

Fan Qty

4 Pcs

0 to 4

50%

0 to 100

Temp. Control Temp. Control Group Mode A/C Work Temp.

Fan Group

-

Fan Speed Ratio -

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

137

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Work Temperature

-

35 degC

-20 to +50

Stop Temperature

-

30 degC

-20 to +50

Dr. Alm. Fan Stp. En

-

Disable

Enable, Disable

55 degC

25 to 80

25 degC

20 to 50

Batt Hibernation -

Disable

Enable, Disable

Backup Mode enable

Enable

Enable, Disable

HT Alarm Thres -

68 degC

25 to 80

LT Alarm Thres

-20 degC

-20 to +20

Batt String Num -

0

0 to 4

Volt. Detect Mode

-

Batt Mid. Volt

Batt Mid. Volt, Block Voltage

Mid-Point Imb Thres

-

20%

5 to 30

-

20%

5 to 30

Batt Hibernation -

Disable

Enable, Disable

Temp Comp Coef

-

-

80 mV/degC

0 to 500

Float Charge Volt

-

-

53.5 V

42.0 to 58.0

Eql. Charge

-

-

56.4 V

42.0 to 58.0

Batt Int AC. n HT Alarm Thres Comp. Start Temp

TCU

Batt TCUC n

-

-

-

NOTE This parameter is displayed only when Volt. Detect Mode is Batt Mid. Volt.

Cell Imb. Alm. Thres. NOTE This parameter is displayed only when Volt. Detect Mode is Block Voltage.

PSC #

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

138

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Auto. Eql Charge

-

-

Yes

Yes, No

Sched Eql Chrg Time

-

-

9h

1 to 24

DC UV Thres. -

-

48.0 V

35.0 to 57.0

DC OV Thres. -

-

58.0 V

53.0 to 60.0

Batt HT Alarm Thres

-

-

50 degC

25 to 80

AC Overfreq Limit

-

-

55 Hz

0 to 65535

AC Underfreq Limit

-

55 Hz

0 to 65535

AC UV Thres. -

-

180 V

60 to 300

AC OV Thres. -

-

280 V

60 to 300

-

-

80

80 to 82

-

-

4

1 to 4

Chan n Detect Object

-

DC Main Equipment

DC Main Equipment, None, DC Other Equipment, Battery, DC TC Equipment

EPACn #

Working Mode

-

Urgent A/C

Urgent A/C, Switch + Urgent, Switch + Intel, add + Urgent, add + Intel, A/C + Urgent, A/C + Intel, Direct Vent

T0:Fan On Out Temp

-

25 degC

0 to 35

T1:All A/C Off Temp

-

22 degC

12 to 32

T2:1 A/C On Temp

-

25 degC

20 to 35

T3:2 A/C On Temp

-

30 degC

25 to 45

T4:Emerg Fan On Temp

-

42 degC

30 to 50

TA:Outdoor Temp

-

34 degC

0 to 40

Volt

DC Energy Comm. Addr. Meter n # Channels

Other Device Config

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

139

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

ACM-2 n #

Issue 04 (2019-08-30)

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

TB:Fan Off In Temp

-

-5 degC

-10 to +32

TC:Fan On In Temp

-

35 degC

20 to 35

TD:A/C Fail Clr Temp

38 degC

23 to 45

TE:A/C On In Temp

-

45 degC

28 to 50

H1:Fan On Humi

-

85%

60 to 85

H2:Fan Off Humi

-

90%

80 to 100

A/C Delay Start

-

Nodelay

Nodelay, Delay

A/C Quantity

-

2

1 to 2

DT:Fan Fail Temp Dif

-

12 degC

10 to 15

FWTF:Fan Fail Time

-

30 Min

20 to 60

ATF:A/C Fail Temp

-

40 degC

38 to 45

WTF:A/C Fail Time

-

30 Min

20 to 60

WTL:A/C Switch Time

-

12 h

2 to 12

EPAC Reset

-

Yes

Yes

System Time Syn

-

Yes

Yes

Loop1 on/off

-

On

On, Off

Loop2 on/off

-

On

On, Off

Loop1 Start Temp

-

25 degC

20 to 60

Loop2 Start Temp

-

28 degC

20 to 60

Stop Temp Hysteresis

-

2 degC

1 to 10

Rotation

-

480 min

360 to 720

Copyright © Huawei Technologies Co., Ltd.

140

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Mini RunTime

-

35 min

4 to 60

Min. Power-off Time

-

3 min

2 to 10

High Temp Threshold

-

42 degC

20 to 80

High Tem Hystere

-

2 degC

1 to 5

Time Control Enable

-

No

Yes, No

Stop Time

-

00:00:00

-

Start Time

-

08:00:00

-

Work Mode

-

Auto

Auto, Manual

Mains UVT

-

-

39%

39 to 100

Mains OVT

-

-

140%

100 to 159

-

280 V

225 to 400

-

45 V

35 to 56

Module On Volt Thres

51.5 V

37.0 to 58.0

Safe Mode Action

-

Off

Off, Output 55 V

Outp Overvolt Thres

-

410.0 V

400.0 to 450.0

Outp Undervolt Thres

-

230.0 V

220.0 to 240.0

Outp Open Cir Prot

-

Enable

Enable, Disable

-

-

-

-

FSU_PARAM Set FSU Restart

-

Enable

Enable, Disable

FSU Restart Intvl (h)

-

8

4 to 24

FSU ID

-

-

-

FSU Code

-

-

-

Runtime

ATS 1

HVDC #

HVDC Group Default Output Volt ModuleOff Volt Thres

HVDC FSU

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

141

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

-

-

-

SC User Name

-

-

-

SC Password

-

-

-

SC Server Port

-

-

-

Mobile VPN Parm

CM VPN IP

-

-

CM Backup VPN IP

-

-

Unicom VPN Parm

CU VPN IP

-

-

CU Backup VPN IP

-

-

Telecom VPN Parm

CT VPN IP

-

-

CT Backup VPN IP

-

-

Output Voltage

-

-

27.0 V

24.0 to 30.0

OV Prot. Thres.

-

-

32.0 V

31.3 to 33

MIMO Module

MIMO Group 12DC Out. Volt

-

12.0 V

12.0 to 13.2

24AC Out. Volt

-

24.0 V

24.0 to 26.3

SSU Group #

Solar EC En

-

-

Enable

Enable, Disable

SC Parameters SC Server IP

VPN Parameters

24 V Module

NOTE Indicates whether the equalized charge function is enabled in the case of solar power supply.

Solar EC Time

-

-

12 h

NOTE Indicates the maximum duration of equalized charge in the case of solar power supply. If the equalized charge duration exceeds the value of this parameter, batteries automatically enter float charging for protection.

NOTE This parameter is displayed only when Solar EC En is set to Enable.

SSU Increment Volt

Issue 04 (2019-08-30)

1 to 24

-

-

0.5 V

0.2 to 1.0 NOTE Difference between the SSU output voltage and the rectifier output voltage.

Copyright © Huawei Technologies Co., Ltd.

142

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Photovolta PV Module ic Quantity

-

-

24 Pcs

1 to 1000

PV Module Alm Relate

-

-

DIN1

No, DIN1-6

PV Module Power

-

-

180 W

50 to 400

Humiture Sensor #

Amb. HT Thres

-

55 degC

25 to 80

Amb. LT Thres

-

-20 degC

-20 to +20

Amb. Ultra HT Thres.

-

70 degC

25 to 80

Amb. HH Thres. -

95%

0 to 100

Amb. LH Thres. -

5%

0 to 100

Env HT Count Point

-

55 degC

25 to 80

Env LT Count Point

-

-20 degC

-20 to +20

Water Alarm Cond

-

Close

Close, Open

Door Sensor # Door Alarm Cond

-

Open

Close, Open

Smoke Sensor Smoke Alarm # Cond

-

Close

Close, Open

DIN n Alm. Cond.

-

Close

Close, Open

DIN5 Reuse

-

None

None, Heater Fault

DIN6 Reuse

-

None

None, LLVD Forcibly Connection, TCUA Alarm, TEC Alarm

DO Dry Contact Para.

ALMn Alarm Action

-

Close

Close, Open

Alarm Config

Power System

-

-

-

UIM

-

-

-

Controller

-

-

-

Rectifier

-

-

-

Rectifier Group

-

-

-

Sensor

Third-Level Menu

A Parameter Lists

Water Sensor #

Alarm DI Dry Parameters Contact Para.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

143

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

Alarm Level DO Para.

Issue 04 (2019-08-30)

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Acid Battery Group

-

-

-

Battery String

-

-

-

Fan Group

-

-

-

Temp. Control Group

-

-

-

Camera Group # -

-

-

CIM #

-

-

-

HVDC #

-

-

-

AIM #

-

-

-

PSC #

-

-

-

FSU #

-

-

-

Door Sensor #

-

-

-

Water Sensor #

-

-

-

Smoke Sensor #

-

-

-

Humiture Sensor #

-

-

ATS

-

-

-

SSU

-

-

-

SSU Group

-

-

-

PV Moudle

-

-

-

EFUSE #

-

-

-

EFUSE Group#

-

-

-

Mains#

-

-

-

NIM02D #

-

-

-

GPS #

-

-

-

EPAC #

-

-

-

ACM-2 #

-

-

-

Cri. Alm. Asso. DO

-

No

No, ALM1-ALM8

Major Alm. Asso. DO

-

No

No, ALM1-ALM8

Copyright © Huawei Technologies Co., Ltd.

144

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Minor Alm. Asso. DO

-

No

No, ALM1-ALM8

Warn. Alm. Asso. DO

-

No

No, ALM1-ALM8

Clear ALM Asso.

Clear ALMn Asso.

-

Yes

Yes

Clear DI Asso.

Clear DIN n Asso.

-

Yes

Yes

IP Address

-

192.168.0.10

-

Subnet Mask

-

255.255.255.0

-

Default Gateway -

192.168.0.1

-

IPv4 DSCP

-

46

0 to 63

VLAN Enable

-

No

Yes, No

VLAN ID

-

0

0 to 4094

VLAN Priority

-

5

0 to 7

NetEco Primary IP

-

192.168.0.10

-

NetEco Backup IP

-

192.168.0.10

-

NetEco Port Number

-

31220

1 to 65535

FAE Tel Number 1

-

-

+, 0 to 9

FAE Tel Number 2

-

-

+, 0 to 9

FAE Tel Number 3

-

-

+, 0 to 9

FAE Tel Number 4

-

-

+, 0 to 9

FAE Tel Number 5

-

-

+, 0 to 9

Northbound

Port Mode

Automatic

Manual, Automatic

Protocol Type

M/S Protocol

M/S Protocol, YDN1363 Protocol, Modbus Protocol

-

9600

1200, 2400, 4800, 14400,

Comm. Network Parameters Parameters

Serial Port

YDN1363

Issue 04 (2019-08-30)

Baud Rate

Copyright © Huawei Technologies Co., Ltd.

145

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Protocol

Modbus Protocol

M/S Protocol

Mobile Data

Value Range

115200, 9600, 19200 Comm. Address

-

1

1 to 254

Baud Rate

-

9600

1200, 2400, 4800, 14400, 115200, 9600, 19200

Comm. Address

-

33

0-247

Baud Rate

-

9600

1200, 2400, 4800, 14400,115200,9600,19200

Comm. Address

-

3

0 to 31

Carrier Operator -

Automatic

Automatic, Others

SIMn Acc Point Name

-

3GNET

A maximum of 28 characters, including lowercase English letters (a to z), uppercase English letters (A to Z), digits (0 to 9), and special characters (@_#*-.).

-

*99#

-

3GNET

-

-

NOTE This parameter is displayed only when Carrier Operator is set to Others.

SIMn Access Point No NOTE This parameter is displayed only when Carrier Operator is set to Others.

SIMn User Name NOTE This parameter is displayed only when Carrier Operator is set to Others.

SIMn User Password NOTE This parameter is displayed only when Carrier Operator is set to Others.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

A maximum of 27 characters, including lowercase English letters (a to z), uppercase English letters (A to Z), digits (0 to 9), and special characters (@_#-.). It is recommended that the password contain at least two types of characters and the length exceed six

146

SMU02B Site Monitoring Unit User Manual

SecondLevel Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

characters. Wifi Setting

Wifi SSID

-

-

HUAWEI_SITE

A maximum of 31 characters, including lowercase English letters (a to z), uppercase English letters (A to Z), digits (0 to 9), and special characters (@_#-.).

Password

-

-

Changeme

A maximum of 31 characters, including lowercase English letters (a to z), uppercase English letters (A to Z), digits (0 to 9), and special characters (@_#-.). It is recommended that the password contain at least two types of characters and the length exceed eight characters.

Local Language Parameters

-

-

English

English, Chinese, Russian, Spanish, Portuguese, French, Italian, German, Turkish, Japanese.

Site ID

Site ID

-

-

-

System Type

-

-

-

-

-

UTC +08:00 Beijing

Time zones of all the major cities in the world. For details, see the WebUI.

Date and Time

-

-

-

NTP Enable

-

No

Yes, No

LCD Contrast Contrast

-

5

0 to 10

Reset Web Password

-

-

-

-

-

-

Yes

Yes

Date and Time Time Zone

NOTE Only displayed when logged in as an administrator.

Restore Settings

Restore Factory Set

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

147

SMU02B Site Monitoring Unit User Manual

A Parameter Lists

A.5 Running Control Table A-5 Running control menu hierarchy Second-Level Menu

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Power System

System Control Mode

-

-

Automatic

Automatic, Manual, Maintenance NOTE When switching the mode between Manual and Maintenance, first switch to Automatic.

LLVDn Control

-

-

On

On, Off

PUE Calc. Reset

-

-

Yes

Yes

Block Alarm

-

-

No

Yes, No

Reset SMU

-

-

Yes

Yes

Sw. to Wire. Net.

-

-

Yes

Yes

Switch to IP Net.

-

-

Yes

Yes

Sw. to Inband Net.

-

-

Yes

Yes

Delete Fail Dev

-

-

Yes

Yes

ACM Reboot

-

-

Yes

Yes

Factory Reset

-

-

Yes

Yes

Loop n on/off

-

-

On

On, Off

Work Mode

-

-

Auto

Auto, Manual

Rectifier Group

Turn on All Rects.

-

Yes

Yes

OV Lock Reset -

Yes

Yes

NOTE This parameter is displayed only when System Control Mode is set to Manual.

Controller

ACM-2

Rectifier

NOTE This parameter is displayed only when System Control Mode is set to Manual.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

148

SMU02B Site Monitoring Unit User Manual

Second-Level Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

-

42.0-58.0

121%

1-121

Yes

Yes

-

Yes

Yes

Addr Abnormal Start

Yes

Yes

Turn on/off

-

On

On, Off

-

Yes

Yes

NOTE This parameter is displayed only when the rectifier type is a CAN communications module.

Manual Control Volt. NOTE This parameter is displayed only when System Control Mode is set to Manual.

Cur. Limiting Coef.

-

NOTE This parameter is displayed only when System Control Mode is set to Manual.

Clear Rect Loss Alm NOTE This parameter appears only if a communications failure alarm is generated.

Collect Fault Info

Rectifier n

NOTE This parameter is displayed only when System Control Mode is set to Manual.

Mains

Delete Mains Equip -

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

149

SMU02B Site Monitoring Unit User Manual

A Parameter Lists

Second-Level Menu

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Battery

BLVD Control

-

-

On

On, Off

-

-

Float Charging

Float Charging, Equalized Charging

Reset Batt. Capacity -

-

Yes

Yes

Battery Standard Test

-

-

Stop

Stop, Start

Short Test Control

-

-

Stop

Stop, Start

Clear Battery Alarm -

-

All

All, Imbalance, BC Protection, Lost, Test Cancelled, Current Imb.

Clear Test Log

-

-

Yes

Yes

Fast Charge Control -

-

Stop

Stop, Start

Clear Backup Log

-

-

Yes

Yes

Charge Control

-

-

Float Charging

Float Charging, Equalized Charging

Reset Batt Capacity -

-

Yes

Yes

Battery Standard Tes

-

-

Stop

Stop, Start

Short Test Control

-

-

Stop

Stop, Start

BLVD Control

-

-

On

On, Off

NOTE This parameter is displayed only when System Control Mode is set to Manual or Maintenance.

Charge Control NOTE This parameter is displayed only when System Control Mode is set to Manual.

BackBatt #

NOTE This parameter is displayed only when System Control Mode is set to Manual.

NOTE This parameter is displayed only when System Control

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

150

SMU02B Site Monitoring Unit User Manual

Second-Level Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Fast Charge Control -

-

Stop

Stop, Start

Del. Comm. Fail Device

-

-

Yes

Yes

CIM02C #

Module Reset

-

Yes

Yes

NIM01C #

Module Reset

-

Yes

Yes

NIM01C3 #

Module Reset

-

Yes

Yes

CIM Equip n

Reset CIM

-

Yes

Yes

Del. Com. Fail CIM

-

Yes

Yes

Intern R Measurement

-

Yes

Yes

Data Report

-

Yes

Yes

BIM Blink Start

-

Yes

Yes

BIM Blink Stop -

Yes

Yes

Reset BIM

-

Yes

Yes

-

Yes

Yes

Mode is set to Manual.

Comm Exp Board Group

NOTE This parameter appears only if a communications failure alarm is generated.

Comm Exp Board

CIM #

NOTE This parameter appears only if a communications failure CIM alarm is generated.

CIMn-BIMn

GPS Information Del COm. Fail GPS Camera #

Camera Group

Del Com. Fail Camera

-

Yes

Yes

DTS #

DTS Group

DTS Control

-

Auto

Auto, To Main BattGro, To Back BattGro1-3

NOTE This parameter is displayed only when Batt Transfer Mode is set to Discharge

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

151

SMU02B Site Monitoring Unit User Manual

Second-Level Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

-

Yes

Yes

Apart or Discharge together .

Del Com. Fail DTS NOTE This parameter appears only if a communications failure alarm is generated.

DCDB #

DTSn

Reset

-

Yes

Yes

DCDB Group

DCDB Reset

-

Yes

Yes

Delete Com Fail DCDB

-

Yes

Yes

-

Yes

Yes

Reset

Yes

Yes

Clr Load OvCur Alm

Yes

Yes

Clr Load n OvCur Alm

Yes

Yes

All Load Control

On

On, Off

Load n Control

On

On, Off

All Load Consum Clr

Yes

Yes

Load n

Yes

Yes

NOTE This parameter appears only if a communications failure alarm is generated.

Clear DCDB Loss Alm. NOTE This parameter appears only if a DCDB loss alarm is generated.

DCDBn

Basic Control

Load On/Off Control

Load Consum Clr Ctl

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

152

SMU02B Site Monitoring Unit User Manual

Second-Level Menu

A Parameter Lists

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Open All Locks -

Yes

Yes

Del. Com. Fail Lock

-

Yes

Yes

Consum Clear Elock #

E-lock Group

NOTE This parameter appears only if an electronic lock communications failure alarm is generated.

Low Cap Li-ion Batt NOTE This parameter is displayed only when Battery Model is set to BBS 4840Z.

Li Battery #

Elock n

Open Lock

-

Yes

Yes

Clear Battery

-

-

Yes

Yes

BLVD Control

-

-

On

On, Off

Li Battery Group

On/Off Control -

On

On, Off

-

Yes

Yes

-

Yes

Yes

-

Yes

Yes

NOTE This parameter is displayed only when Battery Model is set to ESM-A, ESU-A or ESM-BX.

NOTE This parameter is displayed only when System Control Mode of the power system is set to Manual.

Delete BMU NOTE This parameter appears only if a communications failure alarm is generated.

Clear BMU Loss Alm. NOTE This parameter appears only if an ESMU loss alarm is generated.

Li Battery n

Issue 04 (2019-08-30)

Reset BMU

Copyright © Huawei Technologies Co., Ltd.

153

SMU02B Site Monitoring Unit User Manual

A Parameter Lists

Second-Level Menu

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

DCDU #

DCDU Group

Delete DCDU

-

Yes

Yes

DCDU n

LLVD Control

-

On

On, Off

BLVD Control -

On

On, Off

Reset Smoke Sensor

-

Yes

Yes

Clear EFUSE # -

Yes

Yes

-

On

On, Off

Load n Control -

On

On, Off

EFUSE #

EFUSE Group

NOTE This parameter is displayed only when the EFUSE fails to communicate.

EFUSE n

All Load Control NOTE This parameter is displayed only when Control Mode is set to Manual.

NOTE This parameter is displayed only when Control Mode is set to Manual.

Temp. Control # Fan Group Batt Int AC. n

Fan Control Mode

-

Auto

Automatic, Manual

A/C Control Mode

-

Auto

Automatic, Manual

A/C Power-on/off

-

On

On, Off

Fan Control Mode

-

Auto

Automatic, Manual

Fan Speed

-

On

On, Off

NOTE This parameter is displayed only when A/C Control Mode is set to Manual.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

154

SMU02B Site Monitoring Unit User Manual

Second-Level Menu

A Parameter Lists

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

-

Auto

Automatic, Manual

Yes

Yes

Ratio Reset Batt Cabinet

Del Comm Fail Cab This parameter is displayed only when the battery cabinet fails to communicate. TCU

Reset

-

Yes

Yes

Delete TCU

-

Yes

Yes

Reset TCUC

-

Yes

Yes

Smoke Reset

-

Yes

Yes

Delete TCUC

-

Yes

Yes

-

-

Float Charging

Float Charging, Equalized Charging

Turn On/Off Rect n -

-

On

On, Off

System Control Mode

-

-

Automatic

Automatic, Manual

Smoke Sensor # Reset Smoke Sensor -

-

Yes

Yes

Clr Comm. Fail Equip

Yes

Yes

NOTE This parameter is displayed only when the TCU fails to communicate.

This parameter is displayed only when the TCU fails to communicate. Batt TCUC n

NOTE This parameter is displayed only when the TCUC fails to communicate.

Virtual PSC #

ATS

Eql/Float Chrg Ctrl

ATS Group

NOTE

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

155

SMU02B Site Monitoring Unit User Manual

Second-Level Menu

Third-Level Menu

A Parameter Lists

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

Fault Reset

-

Reset

Reset

Control Reset

-

Reset

Reset

Clr Com Fail 24 V Mod

-

Yes

Yes

-

Yes

Yes

Turn On/Off

-

All Module On

All Module On, All Module Off

Module

Turn On/Off

-

On

On, Off

MIMO Group

Turn On/Off

-

Turn On

Turn On, Turn Off

Yes

Yes

Yes

Yes

This parameter is displayed only when the ATS fails to communicate.

ATS n

24 V Module

Module Group

NOTE This parameter is displayed only when the 24 V Module fails to communicate.

Clear 24 V Mod Lost Alarm NOTE This parameter is displayed only when there is an 24 V Module Lost alarm.

MIMO Module

Clear Mod Loss Alarm NOTE This parameter is displayed only when there is an MIMO Lost alarm.

Clr Comm. Fail Equip NOTE This parameter is displayed only when the MIMO fails to communicate.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

156

SMU02B Site Monitoring Unit User Manual

Second-Level Menu

SSU #

A Parameter Lists

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

MIMO n

Turn On/Off

-

On

On, Off

24 V AC Output Control

On

On, Off

12 V DC Output Control

On

On, Off

ON/OFF

-

On

On, Off

-

Yes

Yes

Clear Lost Alm -

Yes

Yes

Yes

Yes

-

On

On, Off

Reset

-

Yes

Yes

Module Off Enable

-

Disable

Disable, Enable

Open Cir Prot Reset

-

Reset

Reset

Module Group On/Off

-

On

On, Off

SSU Group

NOTE This parameter is displayed only when System Control Mode is set to Manual.

Reset

NOTE This parameter is displayed only when there is an SSU Lost alarm.

Clear Com. Fail SSU NOTE This parameter is displayed only when there is an All SSU Comm Fail alarm.

SSU n

ON/OFF NOTE This parameter is displayed only when System Control Mode is set to Manual.

HVDC #

HVDC Group

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

157

SMU02B Site Monitoring Unit User Manual

Second-Level Menu

A Parameter Lists

Third-Level Menu

Fourth-Level Menu

Fifth-Level Menu

Default Value

Value Range

-

Yes

Yes

-

On

On, Off

NOTE This parameter is displayed only when System Control Mode is set to Manual.

Del. Comm. Fail Eq NOTE This parameter appears only if a communications failure alarm is generated.

HVDC

Module CTL NOTE This parameter is displayed only when System Control Mode is set to Manual.

Historical Alarm

Delete His. Alarms

-

Yes

Yes

Active Alarm

-

-

Clear Alarm

Clear Alarm

Clear Batt. Test Log

Clear Test Log

-

-

Yes

Yes

Output Relay Test

Test Enable

-

-

No

No, Yes

Test Duration

-

-

1 Min

1 to 15

-

-

Open

Open, Close

-

-

-

-

Clear Alarm

NOTE This parameter is displayed only when Test Enable is set to Yes.

ALMn NOTE This parameter is displayed only when Test Enable is set to Yes.

Hiber. Test Para. Rect. Hiber. Speedup

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

158

SMU02B Site Monitoring Unit User Manual

A Parameter Lists

A.6 Site Maintain Table A-6 Site maintain menu hierarchy Second-Level Menu

Third-Level Menu

Fourth-Level Menu

Default Value

Value Range

U Disk Hist Record

Upgrade/Cfg Result

-

-

-

Last Export Result

-

-

-

U Disk Upgrade/Cfg

-

-

-

-

Export File to USB

-

-

-

-

Module Check

Check Result

Comm OK Equip Num

-

-

Comm Fail Equip Num

-

-

Normal Equip List

-

-

-

Abnormal Equip List

-

-

-

A.7 User Management Table A-7 User Management menu hierarchy Second-Level Menu

Default Value

Range

Change Password

-

-

User Logout

Yes

Yes

NOTE  Log out the current user. 

Issue 04 (2019-08-30)

This parameter is displayed only when you log in as an administrator or engineer.

Copyright © Huawei Technologies Co., Ltd.

159

SMU02B Site Monitoring Unit User Manual

B Technical Specifications

B

Technical Specifications

Table B-1 Technical Specifications Category

Item

Specifications

Environmental conditions

Operating temperature

–40°C to +70°C

Transportation temperature

–40°C to +70°C

Storage temperature

–40°C to +70°C

Operating humidity

5%–95% RH (non-condensing)

Storage humidity

5%–95% RH (non-condensing)

Altitude

0–4000 m When the altitude ranges from 3000 m to 4000 m, the operating temperature decreases by 1ºC for each additional 200 m.

Power supply

Structure

Input voltage range

36–72 V DC

Maximum current

0.5 A

Dimensions (H x W x D)

41.5 mm x 106.5 mm x 209 mm

Weight

≤ 1.5 kg

Mean time between failures (MTBF)

Issue 04 (2019-08-30)

≥ 250,000 hours

Copyright © Huawei Technologies Co., Ltd.

160

SMU02B Site Monitoring Unit User Manual

C FAQ

C

FAQ

C.1 How Do I Prepare the WebUI Operating Environment? Before logging in to the WebUI, you need to prepare the WebUI operating environment to connect to the monitoring unit.

Operating Environment Operating system: Windows XP or later Browser: Internet Explorer 8.0 or later, FireFox 13 or later, and Chrome 20

Internet Explorer is used as an example to illustrate all WebUI operations mentioned in this document.

Setting a LAN

If the monitoring unit is connected to a LAN and a proxy server has been selected, cancel the proxy server settings. If the monitoring unit is connected to the Internet but your computer is connected to a LAN, do not cancel the proxy server settings. Otherwise, you cannot access the SMU. To cancel proxy server settings, perform the following steps: 1.

Open Internet Explorer.

2.

Choose Tools > Internet Options.

3.

Choose Connections tab, click LAN Settings.

4.

Clear Use a proxy server for your LAN.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

161

SMU02B Site Monitoring Unit User Manual

C FAQ

Figure C-1 Canceling proxy server settings

5.

Click OK.

Setting Internet Explorer Security

Set Internet Explorer security before you perform the following operations:

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

162

SMU02B Site Monitoring Unit User Manual

C FAQ



Export historical logs, historical data, statistics, and battery test records.



Upload system configuration files.



Download system configuration files.



Upgrade software.

To set Internet Explorer security, perform the following steps: 1.

Open Internet Explorer.

2.

Choose Tools > Internet Options.

3.

Choose Security Tab.

4.

Click Internet and click Custom level, as shown in Figure C-2. After you specify Internet security settings, click Local intranet and click Custom level. Figure C-2 Internet Explorer security

5.

Specify the security settings. Enable the following:

Issue 04 (2019-08-30)



Initialize and script ActiveX controls not marked as safe for scripting



Allow previously unused ActiveX controls to run without prompt



Include local directory path when uploading files to a server



Automatic prompting for file downloads

Copyright © Huawei Technologies Co., Ltd.

163

SMU02B Site Monitoring Unit User Manual

C FAQ

Figure C-3 Internet Explorer security setting 1

Figure C-4 Internet Explorer security setting 2

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

164

SMU02B Site Monitoring Unit User Manual

C FAQ

Figure C-5 Internet Explorer security setting 3

Figure C-6 Internet Explorer security setting 4

6.

Click OK.

7.

Click the Advanced tab, and select Use SSL 3.0, Use TLS 1.0, Use TLS 1.1, and Use TLS 1.2.

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

165

SMU02B Site Monitoring Unit User Manual

C FAQ

Figure C-7 Internet Explorer security setting 5

8.

Click OK.

C.2 What Should I Do If I Forgot the Password? The monitoring unit allows users to change passwords mutually on the WebUI and LCD. For example, if you forgot the WebUI login password, you can change the WebUI password on the LCD. Table C-1 Resetting the WebUI password on the LCD Main Menu

Second-Level Menu

Third-Level Menu

Setting

Parameters Settings

Local Parameters

Reset Web Password

Set based on site requirements.

For details about how to change the LCD password on the WebUI, see 5.2.4 Changing a User Password. Select the user whose login source is LCD for changing.

Issue 04 (2019-08-30)



There are 2 LCD account, see 3.1.4 Password



The WebUI account is admin and the password is Changeme by default.

Copyright © Huawei Technologies Co., Ltd.

166

SMU02B Site Monitoring Unit User Manual

D Acronyms and Abbreviations

D

Acronyms and Abbreviations

A

-

AC

Alternating current

B

-

BLVD

Battery low voltage disconnected

C

-

CAN

Control area network

D

-

DC

Direct current

DCB

Deep cycle battery

DIN

Dry contact input

DOD

Depth of discharge

DTS

DC transfer switch

E

-

ESD

Electrostatic discharge

ESM

Energy storage module

ESU

Energy storage unit

F

-

FCB

Fast charge battery

FE

Fast Ethernet

H

-

HTTPS

Hypertext Transfer Protocol Secure

I

-

IMEI

international mobile equipment identity

IP

Internet Protocol

Issue 04 (2019-08-30)

Copyright © Huawei Technologies Co., Ltd.

167

SMU02B Site Monitoring Unit User Manual

D Acronyms and Abbreviations

L

-

LCD

Liquid crystal display

LLVD

Load low voltage disconnected

N

-

NMS

Network management system

S

-

SCB

Solar cycle battery

SMU

Site monitoring unit

SNMP

Simple Network Management Protocol

SOH

State of health

SPM

Site Power Management

U

-

UI

User interface

UIM

User interface module

USB

Universal Serial Bus

Issue 04 (2019-08-30)