Sl Ref542plus(en)a 1vcp000060

November 17, 2018 | Author: Yigit Sarıkaya | Category: Automation, User Interface, Resonance, Power Supply, Electromagnetism
Share Embed Donate


Short Description

abb ref542...

Description

Power ower Te Technologies Division Medium Voltage

Protect IT Multifunctional Protection switchgear Control unit Model REF542plus REF542plus (Rel. 2.0)

   0    1  .    4    0    0    2   –   n   e  ,    A  .   v   e    R   –    0    6    0    0    0    0    P    C    V    1

REF542plus – presentation contents 

REF542plus REF542plus 

General



Hardware



Features



 Ap  A p p l i c ati at i o n s



Engineering



Tests and Certifica rtificatio tions ns



Custo us tomer mer valu value es

REF542 plus Rel 2.0 present presentati ation on , 2 of 62 EC V2.0 10/10/04

Presentation Contents

REF542plus – presentation contents 

REF542plus REF542plus 

General



Hardware



Features



 Ap  A p p l i c ati at i o n s



Engineering



Tests and Certifica rtificatio tions ns



Custo us tomer mer valu value es

REF542 plus Rel 2.0 present presentati ation on , 2 of 62 EC V2.0 10/10/04

Presentation Contents

 ABB first in Intelligent Switchgear   ABB first introduced in the market integrated numerical combined protection and control in MV switchgear 

Cost effectiveness



Engineering and wiring wiring reduct reduction ion



Hardware Hardware variants variants minimization minimization



High Integration



Fault possibilities possibilities reduction reduction



Easier modifications



Easier expansions

REF542 plus Rel 2.0 present presentati ation on , 3 of 62 EC V2.0 10/10/04

REF542plus General

REF542plus The History

REF542plus General

SCU => REF542 => REF542plus 

From thousands of installations Evolution and enhacements of a proven technology



PTMV-wide product

REF542plus is ABB standard solution for AIS and GIS switchgear 

REF542 plus Rel 2.0 presentation , 4 of 62 EC V2.0 10/10/04

REF542plus – Yearly volumes

REF542plus General

10000    )   s   c   p    (   e   m   u    l   o    V

8000 6000 4000 2000 0    3    9  4    9    5    9    6    9    7    9    8    9    9    0    0    0  1    0    2    0    3    9    9    9    9    9    9    9    9    0    0    0    0   1   1   1   1   1   1   1    2    2    2    2

REF542 plus Rel 2.0 presentation , 5 of 62 EC V2.0 10/10/04

REF542plus REF542

REF542plus - Licensee companies 

WE 



CEE 



TRABB - EGARC

SEA 



CNDMX

MENA 



CZEJF

CN 



DECMS - ITSCB - CHSEC

 AUTIL - MYTAD – KRABB

INDIA 

INABB

REF542 plus Rel 2.0 presentation , 6 of 62 EC V2.0 10/10/04

REF542plus General

REF542plus - Hardware



REF542plus 

General



Hardware



Features



 Applications



Engineering



Tests and Certifications



Customer values

REF542 plus Rel 2.0 presentation , 7 of 62 EC V2.0 10/10/04

REF542plus Hardware

REF542plus – Hardware Structure

REF542plus Hardware

REF542plus is composed of 2 parts: Base Unit and LD HMI  High

flexibility due to separation of HMI and Base Unit

 – Blind Unit (without HMI) possible  – One HMI shared for several Base Units  HMI

easy integration on panel front door 

 Base

Unit easy integration in low voltage cubicle

 Independent

operation of Base Unit and HMI

 – HMI can be disconnected without affecting Base Unit operation

Base Unit REF542 plus Rel 2.0 presentation , 8 of 62 EC V2.0 10/10/04

LD HMI: Local Detached Human Machine Interface

REF542plus Hardware

REF542plus – Hardware, HMI  Al arm LED

Interlocking error LED

Network communication LED 3 LED bars for measurements

Unit Ready LED

Optical Interface

CB fast opening butt on

Electronic k ey for: - remote / local - operational / set Select-, off-, on-buttons

FREE programmable co mmands configurable with the config tool 8 x 4 pages user programmable LEDs

Menu navigation b uttons REF542 plus Rel 2.0 presentation , 9 of 62 EC V2.0 10/10/04

REF542plus Hardware

REF542plus – Hardware, Base Unit  Analog Output 4..20mA Module

 Analog Input 4..20mA Module

Communication Module

RX 0/4...20mA

4...20mA

TX CP

Communication Processor 

 Analog Input Module IL1 IL2 IL3 UL1 UL2 UL3 Io

DSP Protections, Measurements

µC

start L1 start L2 start L3 Release/Trip  Autoreclosure

Control

Vo CAN

Eth.

(exemplary inputs) Main Board Binary inputs

Binary Input Output Module(s) REF542 plus Rel 2.0 presentation , 10 of 62 EC V2.0 10/10/04

Binary outputs

 .    h   c   n   y    S   e   m    i    T

REF542plus – Hardware, Connector plates

REF542plus Hardware

CT, VT connector  Wide housing, mixed analog input Sensor input s

Small housin g

HMI

REF542 plus Rel 2.0 presentation , 11 of 62 EC V2.0 10/10/04

REF542plus – Hardware, Modules Components

 Analog input module Main Board module  Analog output module 1... 3 x binary I/O module

Power supply module

REF542 plus Rel 2.0 presentation , 12 of 62 EC V2.0 10/10/04

REF542plus Hardware

REF542plus – Hardware, Main Board 5 Module

20%

REF542plus Hardware

faster than previous MainBoard 4 (MB4) Motorola ColdFire processor (32 bit s) @ 66MHZ Motorola 56307 DSP (24 bits) @ 150MHZ Backward compatible with MB4

3 Versions: BASE •RS232 Service port, RS485 for HMI, RJ45 Ethernet 10Base T STANDARD

•Like BASE plus CAN and Irig–B optical input port for time synchronization FULL  Like STANDARD plus fast digital I/0 ports (2 inputs - 1 output)

REF542 plus Rel 2.0 presentation , 13 of 62 EC V2.0 10/10/04

REF542plus – Hardware, Analog Input Module

REF542plus Hardware

Conventional VTs and CTS

Sensors analog inputs Mixed modules available (Sensors+conventional CTs and VTs)

8 channels for protection and measurements, (AD 20bits, 16 MSB used) Channels can be supervised against wire cuts REF542 plus Rel 2.0 presentation , 14 of 62 EC V2.0 10/10/04

REF542plus Hardware

REF542plus – Hardware, Analog input modules

REF542plus can have a maximum of 8 analogue input channels. These inputs are divided into three measurement groups: •Measurement Group 1: channel 1, channel 2, channel 3 •Measurement Group 2: channel 4, channel 5, channel 6 •Measurement Group 3: channel 7, channel 8 Group 1 and group 2 have to be homogeneous, that means they can measure 3 currents or 3 voltages. For example, measurement of 1 current and 2 voltages is not allowed. Group 3 can get any type of signals: 2 currents, 2 voltages, 1 current and 1 voltage, etc. The input CT 0.2A is commonly used with a toroidal transformer for sensitive earth fault current measurement. CT means input for current transformer (CT2 is the 0.2A input). The instrument transformer can have ratio /1 or /5 . The ratio and the nominal current (e.g. 100/5) are selected via software in the configuration tool. The input module is the same; a different pin on the connector is wired depending on the ratio /1 or /5. VT means input for voltage transformer. Both Phase-to-ground or phase-to-phase VT can be used. SI means sensor input. The rogowsky coil is used for current sensing. The correct ratio of the rogowsky coil is selected by the configuration tool. The resistive divider is used for voltage sensing. The ratio is selected by the configuration tool. The input is the same both for voltage and current sensing, the selection is done via the configuration tool. So, it is possible to use 6 rogowsky coils, or 6 voltage dividers, or 3 rogowsky coils and 3 voltage dividers.

REF542 plus Rel 2.0 presentation , 15 of 62 EC V2.0 10/10/04

Group 1 CT VT CT CT CT CT CT CT CT CT CT CT CT CT S S S S S S S S

CT VT CT CT CT CT CT CT CT CT CT CT CT CT S S S S S S S S

CT VT CT CT CT CT CT CT CT CT CT CT CT CT S S S S S S S S

Group 2 VT VT CT CT CT VT VT VT VT VT VT VT CT CT S S VT S S S S CT

VT VT CT CT CT VT VT VT VT VT VT VT CT CT S S VT S S S S CT

VT VT CT CT CT VT VT VT VT VT VT VT CT CT S S VT S S S S CT

Group 3 CT2 CT2

VT CT2

CT2 CT VT CT CT CT CT2 VT

VT

CT CT S CT2 CT2 CT CT CT2 VT CT2

CT VT S VT VT

VT CT CT2 VT

VT VT VT

REF542plus – Hardware, Electromech. BIO module

REF542plus Hardware

Up to three binary Input Output modules BIO3 with mechanical contacts in the wide housing (two in the standard housing)

14 Binary Inputs, 24-90 VDC (threshold 14VDC) or 85-220 VDC (threshold 50VDC) 6 Power Outputs, Load current 12A, operate tim e 9ms 2 Signal Outputs, Load current 2A, operate time 5ms 1 Optio nal Static Output instead of mechanical, Load current 0.7A, operate time 1ms

1 coil supervision circuit 1 watchdog contact The module is also available with the minus (‘-’) of the binary inputs interconnected, to semplify wiring REF542 plus Rel 2.0 presentation , 16 of 62 EC V2.0 10/10/04

REF542plus – Hardware, Static BIO module

Up to three Static binary Input Output modules in the wide housing (two in the standard housing)

14 Binary Inpu ts, 48-285 VDC 2 Power Outpu ts, Load current 12A, operate time 1ms 4 Power Outpu ts, Load current 10A, operate time 1ms 2 Static Outputs,Operate voltage max.250V, operate time 1ms 2 coil supervision circuits 1 watchdog contact

REF542 plus Rel 2.0 presentation , 17 of 62 EC V2.0 10/10/04

REF542plus Hardware

REF542plus – Hardware, Power supplies Hardware – Power Supply

Fixed 110 or 220 V DC Tolerance -30% + 15%

Full range 48... 220 V DC Tolerance -15% + 10%

REF542 plus Rel 2.0 presentation , 18 of 62 EC V2.0 10/10/04

REF542plus Hardware

REF542plus – Hardware, Analog Output module Hardware – Analog Output 0..20mA module

4 freely programmable output channels (I, V, Power, cosphi)

REF542 plus Rel 2.0 presentation , 19 of 62 EC V2.0 10/10/04

REF542plus Hardware

REF542plus – Hardware, 4...20mA Analog Input Module Hardware – 4..20mA Analog Input Module

General purpose inputs for 4..20mA sensors, e.g.: •Temperature •SF6 density •... 6 channels available The module can be used in the wide housing only

REF542 plus Rel 2.0 presentation , 20 of 62 EC V2.0 10/10/04

REF542plus Hardware

REF542plus – Hardware, Communication modules

REF542plus Hardware

SPA-Bus Protocol (plastic fiber snap in, glass fiber SMA, glass fiber ST) LON LAG 1.4 (glass fiber, ST)

Dual channel SPA-Bus/MODBus RTU (glass fiber, ST or  RS 485, screw terminals)

IEC 60 870-5-103 (gl ass fiber, ST)

REF542 plus Rel 2.0 presentation , 21 of 62 EC V2.0 10/10/04

REF542plus – Hardware, Summary Binary input and output: at most 3 modules 

14 (28,42) binary inputs



6 (12, 18)

power outputs



2 (4, 6)

signal outputs



1 (2, 3)

watchdog outputs

 Analog Input 

8 analog inputs for current and voltage

4…20mA Analog Input 

6 x 4...20mA channels

 Analog Output 

4 x 4/0...20mA channels

Communication 

SPABUS (optical glass, optical plastic)



LON LAG 1.4 (optical glass)



IEC 103 (optical glass)



MODBUS RTU (two independent channels, optical glass, RS 485)



WEB SERVER

REF542 plus Rel 2.0 presentation , 22 of 62 EC V2.0 10/10/04

REF542plus Hardware

REF542plus – Hardware, Summary   Always 



REF542plus Hardware

required with any housing:

HMI, power supply, MainBoard, Analog Input,1 x binary IO

Standard housing: 

 At most 2 binary IO, alternatively communication or Analog Output board  –  backplane differs in case analog output or communication module is inserted



Wide housing: 

 At most 3 binary IO, communication, Analog Output, Analog Input 0..20nA module instead of Analog Output module or one of the binary IO  –  The Analog Input 0..20mA module can be inserted in the Analog Output slot.  Analog input and analog output are mutually exclusive.

REF542 plus Rel 2.0 presentation , 23 of 62 EC V2.0 10/10/04

REF542plus – Features 

REF542plus 

General



Hardware



Features



 Applications



Engineering



Tests and Certifications



Customer values

REF542 plus Rel 2.0 presentation , 24 of 62 EC V2.0 10/10/04

REF542plus Features

REF542plus Features

REF542plus – Features Protections

Visualization

 – overc ur ren t

 – bay sin gl e lin e diagr am

 – overv olt age / under vol tage  – earthf ault

 – measur emen t  – event s and alar ms

Motor specific protections

 – param eters and settin gs

 – ther mal o verl oad

 – dis tan ce

 – di rec tio nal power 

 – dif ferent ial for tran sf orm ers and motors

 – un bal anc ed load

 –res tri cted diff eren tial

 – in rus h bl oc king

 – lo w lo ad

Control  – cont rol , int erloc king  – alarm hand li ng  – lo cal cont rol and ind ic ation

 Ad itio nal fun ctio ns  – syn chro -chec k  – 5 sho ts auto-rec lo sin g  – fault rec or di ng

Supervision  – self di agn os is  – sw itc hgear f aul ts  –dat a trans mis sion failu re

REF542 plus Rel 2.0 presentation , 25 of 62 EC V2.0 10/10/04

Power Quality  – Pow er fact or con tro ller with resonance protection  – THD pro tection -Frequency protection -High speed transfer 

-communication to SCADA -WEB SERVER - CAN digital bus interface

REF542plus – Feeder Local Control 

REF542plus Features

REF542plus provides an easy and pratical local control with complete interlocking. 

The operator interface carries out the following functions: 

Status of the different primary objects

 Activation of the primary object by means of control push-buttons



REF542 plus Rel 2.0 presentation , 26 of 62 EC V2.0 10/10/04



Events, alarms, measurements visualization



User programmable buttons

REF542plus – Protection Functions (I) 

Current Protection Functions: 

Inrush (68)



Overcurrent istantaneous (50)



Overcurrent definite time and IDMT (51





Voltage Protection Functions: 

Undervoltage istantaneous (27)



Undervoltage definite time (27 High, 27 Low)

High, 51 Low, 51 IDMT)



Overvoltage istantaneous (59)

Directional Overcurrent protection (67



Overvoltage definite time (59 High, 59 Low)



Residual Overvoltage definite time (59N

High, 67 Low) 

Earthfault protection definite time and IDMT (51N High, 51N Low, 51N IDMT)



REF542plus Features

Directional earth fault protection (67N High, 67N Low, 67N sensitive,67N sector)

REF542 plus Rel 2.0 presentation , 27 of 62 EC V2.0 10/10/04

High, 59N Low)

REF542plus  – Protection Functions (II) 

Motor Protection Functions: 

Number of starts (66)



Motor Start (51 MS)



Locked Rotor (51 LR)



Thermal Overload (49)



Unbalanced Load (46)



Directional Power (32)



Low Load (37)

Power



Quality Functions:

Other protection, control and supervision functions: 

Differential (87)



Restricted earth fault (87N)



Distance protection (21)



Synchrocheck (25)



 Autoreclosing (79)



Fault recorder 



Interlocking



PLC-like automation functions



Measurements



Power factor controller (55) with resonance protection



Switch gear monitoring



THD protection



Self-diagnosis



Frequency protection



CAN



High Speed Transfer System (HSTS)

REF542 plus Rel 2.0 presentation , 28 of 62 EC V2.0 10/10/04

REF542plus Features

REF542plus Features

REF542plus – Measurements



Line currents IL1, IL2, IL3, A



Earth-fault current Ilo ,A



Phase to earth voltages U1N, U2N, U3N, V



Phase to phase voltages U12, U23, U31, V



Residual voltage Uo, V



Frequency f, Hz



Power factor cos phi



 Active power P, Watt

  

Reactive power Q, VAR  Active energy, Watth Reactive energy, VARh

REF542 plus Rel 2.0 presentation , 29 of 62 EC V2.0 10/10/04



Circuit-Breaker electrical and mechanical life: 

Operating hours



Operating cycles

 

Interrupted currents sum Mean and peak current in the observation period



Recording of 30 protection events (visible from HMI): 

Involved protection



Faulty phase



Tripping time



Tripping values

REF542plus – Fault Recorder 

 Analogue channels

8

Digital channels

32

 Acquisition rate

1,2 kHz



Pre fault time

100ms..2s



Min Recording time

1sec



Max Recording time

5sec



Max num of records

5

  

Fault records are retrieved and converted into the COMTRADE format

REF542 plus Rel 2.0 presentation , 30 of 62 EC V2.0 10/10/04

REF542plus Features

Programmable electronic key 



Multiple codes for different access authorization levels 

8 characters custom code for authenticated HMI access



Possibility of “Super User” key code

Increased security 



Recording of access operations (log-book)

SW programmer for custom HMI -key programming

REF542 plus Rel 2.0 presentation , 31 of 62 EC V2.0 10/10/04

REF542plus Features

REF542plus – Communication protocols  LON  IEC

according to LAG 1.4

60 870-5-103 protocol with VDEW extension

 MODBUS  SPA

RTU or SPA protocol on dual channels interface

bus protocol

 Embedded

REF542 plus Rel 2.0 presentation , 32 of 62 EC V2.0 10/10/04

WEB server 

REF542plus Features

REF542plus, WEBREF Embedded Web tecnology 

Integrated WEB technology goals:



Flexible, virtual HMI running on a commercial Web Browser. 

Easy adaptation to local languages



System condition acquisition



Low cost replacement of SCADA monitoring functions



 Alarm alert with SMS messaging

REF542 plus Rel 2.0 presentation , 33 of 62 EC V2.0 10/10/04

REF542plus Features

REF542plus, WEBREF Application example 

Working activities cause a short circuit in the medium voltage system



REF542plus trips



Local alarm indication => SMS is sent



REF542 plus Rel 2.0 presentation , 34 of 62 EC V2.0 10/10/04

SMS:  Alarm is delivered directly to the operator’s mobile phone

REF542plus Features

REF542plus, WebREF Application example 



REF542plus Features

Operator connects to REF542plus

Operator finds out what happened

 Advantages: Operator is alerted nearly in real time, he/she could verify and assess the fault type and reason even from home. No need of expensive equipment, no dedicated network, No human surveillance.

REF542 plus Rel 2.0 presentation , 35 of 62 EC V2.0 10/10/04

REF542plus, CAN process bus 

Standard CAN Open network int erface



Up to 1 Mbit/s (40 m)



Goals:

REF542plus Features



Digital I/O system for signalling



Interlocking signals exchange among REFs in the same panel

 –  Horizontal communication of real time information 

Increase automation capabil iti es

 –  Access to the huge market of off-the-shelf CAN automation products (terminal blocks, actuators, PLCs, PCs, ...) 

 Analog objects for RTD or 4-20 mA sensors

REF542 plus Rel 2.0 presentation , 36 of 62 EC V2.0 10/10/04

 A new switchboard concept 

REF542plus Features

Digital bus (CAN) as replacement of hard-wiring for inter panel control applications 

Interlocking, automated transfer switch



Horizontal communication

REF542 plus Rel 2.0 presentation , 37 of 62 EC V2.0 10/10/04

REF542plus – CAN application example



REF542plus’s exchange interlocking information via CAN 



REF542plus Features

Reduced interpanel wiring

 Additional, intelligent CAN I/O modules are placed in empty panels. 

CAN I/O modules used for signalling and data acquisition (e.g. aux contacts multiplication, external devices status acquisition).

REF542 plus Rel 2.0 presentation , 38 of 62 EC V2.0 10/10/04

Time synchronization possibilities with REF542plus 

In case of fault, it is fundamental to understand:



 –  What happened  –  Where the fault started  –  How the fault started 

Fault records and events from several units must be placed in precise chronological order 

Spabus communication: time setting, date and time up to seconds. 



 Accuracy 1ms

Direct GPS input: ti me synchronization 

REF542 plus Rel 2.0 presentation , 39 of 62 EC V2.0 10/10/04

 Accuracy 10ms

LON LAG 1.4 VATS: t ime synchronization 



 Accuracy about 50ms

IEC 103 communication: time synchronization, date and time up to seconds. 



 Accuracy about 50 ms

Modbus communication: time setting, date and time up to seconds. 



REF542plus Features

 Accuracy better than 200us

REF542plus time synchronization with direct input 

Synchronization accuracy better than 1ms



Events absolute time stamp



Fiber optic dedicated input on REF542plus MainBoard 5



IRIG-B protocol (B000, B002,B003)



Star topology signal distribution

REF542 plus Rel 2.0 presentation , 40 of 62 EC V2.0 10/10/04

REF542plus Features

 A compatible GPS: Meinberg GPS167BGT

REF542plus Features



Http://www.meinberg.de



20 REF542plus can be directly synchronized



For more REF, make a connection among several GPS racks

REF542 plus Rel 2.0 presentation , 41 of 62 EC V2.0 10/10/04

Connector 

X74 on the mainboard

Transducer type

HFBR-0400 Series

Wavelength

820 nm

Max. distance

1500m

Connector type

ST

Supported protocol

IRIG, time format B000, B002, B003

Signal type

Digital

Integrated power factor controller  



Turn key solution Shunt capacitor bank integrated in the MV switchgear  

No additional panels



No additional control units

Several technical and economical benefits:    

Reduced electric utility billing and penalties Released system capacity Increased voltage control on the load Decreased I2R losses

REF542 plus Rel 2.0 presentation , 42 of 62 EC V2.0 10/10/04

REF542plus Features

REF542plus Features

REF542plus power factor controller 

One REF542plus controls up to 4 capacitor banks  –  While it is implementing the control and protection functions for the panel



Three different operational modes:  –  Automatic mode on instantaneous Q values  –  Automatic mode on integral Q value  –  Manual mode by the local HMI Feeder  3~

3~ I V

PFC

     x

x

     x

C&P

REF542 plus Rel 2.0 presentation , 43 of 62 EC V2.0 10/10/04

Load 

REF542plus Features

PFC with Resonance Protection 

The problem  –  Network parameters changes may cause resonance behaviour at capacitor or  load switching

 –  Resonance frequencies originates current and voltage distorsion with increase of power losses 

REF542plus resonance protection monitors continuosly the network total harmonic distorsion (THD)  –  Resonance protection detects harmonics caused by PFC operation (switching resonance).

 –  Resonance protection clears the oscillation by de-energizing the capacitor banks (PFC coordination) Case 1 Voltage waveform at BUS9A 1.5

1

Feeder 

0.5

I V

   )   u   p    (

PF C Control

0

   V

-0.5

-1

Load 

REF542 plus Rel 2.0 presentation , 44 of 62 EC V2.0 10/10/04

-1.5 0.1

0.15

0.2

0.25 t (sec)

0.3

0.35

0.4

THD protection

REF542plus Features



THD protection detects frequencies up to 25th harmonics (sample rate 4.8 kHz)



Minimum operating time 50 ms



The protection detects high harmonic content condition based on THD calculation

REF542 plus Rel 2.0 presentation , 45 of 62 EC V2.0 10/10/04

REF542plus Features

High speed transfer system Target 

To ensure continuous power supply to essential electrical equipment by changing over from a main to a stand-by feeder as fast as possible

Feeder A

Prerequisites 

Existence of at least two- usually independent – synchronous feeders



Circuit-breakers with short operating times



Suitability of consumers for network change-over 

Feeder B

U1

U2

U3 S1

S2

M

REF542 plus Rel 2.0 presentation , 46 of 62 EC V2.0 10/10/04

HSTS

M

HSTS based on REF542plus/SUE3000 Feeder 1

Feeder terminals

REF542plus Features Feeder 2

VS/FDI   VS/FDI Init (IRQ)

Fast VM 1

Fast VM 1

Busbar 

•Fast mode total tr ansfer time = 30ms •Based on fast VM1-T Circuit Breaker  •HSTS is int egrated in the MV switchgear: •No need of dedicated panels •No supplementary equipment REF542 plus Rel 2.0 presentation , 47 of 62 EC V2.0 10/10/04

REF542plus Features

HSTS Available Configuration 



3-Circuit breaker-configuration 

2 busbar busbar section sections, s, Busba Busbar  r  coupling breaker 



Transfer between feeder and busbar busbar couplin coupling g breaker  breaker 

REF542 plus Rel 2.0 presen presentat tation ion , 48 of 62 EC V2.0 10/10/04

2-Circuit breaker-configuration 

One busbar 



Transfer takes place between the 2 feeders

REF542plus – Applications 

Ind ndus ustr tria iall IT Ove verv rvie iew w



REF542plus 

General



Hardware



Features



 Ap  A p p l i c ati at i o n s



Engineering



Tests and Certif rtifica ication tions s



Customer Custom er values values

REF542 plus Rel 2.0 presen presentat tation ion , 49 of 62 EC V2.0 10/10/04

REF542plus  Ap  A p p l i c at atii o n s

REF542plus - Appli pplica cati tion ons s 

REF542plus  Ap  A p p l i c at atii o n s

Typical Applications for: 

 Any kind of medium voltage switchgear (Incoming, (Incoming, Trafo, Overhead lines, Motor, Bus Tie, ...)



High voltage switchgear up to 170kV and three pole op. mechanism



Low voltage switchgear with complex automation requirements

  All

the switchgear secondary functions integrated in one single unit:



Control



Protection



Measurements



Monitoring



Communications

REF542 plus Rel 2.0 presen presentat tation ion , 50 of 62 EC V2.0 10/10/04

REF542plus – Feeder Automation 

REF542plus  Applications

REF542plus equipped switchgear are a complete and effective system for distribution networks.

 Among others, the following automation sequences are possible:





 Automatic switching from a double radial to a simple distribution system (ATS).



Performing manual switching by paralleling the feeders with the synchro-chek function (25).



Motors shutdown upon temporary voltage loss/drop.



Prompt re-acceleration on voltage restoring within the pre-set time.



Motors restarting according to the pre-set sequence after voltage loss.

REF542 plus Rel 2.0 presentation , 51 of 62 EC V2.0 10/10/04

REF542plus – Protection sets, example Type

Protection functions Meas.

Basic Non directional overcurrent 50, 51, 51N, 49 protection Non directional overcurrent 50, 51, 51N, 49, 27, 59, 59N protection, voltage protections

I,V, energy, cosphi, power  I,V, energy, cosphi, power 

Directional overcurrent protection Directional overcurrent protection, voltage protection

50, 51, 51N, 49, 67, 67N, 67N sensitive 50, 51,51N, 49, 67, 67N, 67N sensitive, 27, 59, 59N

I,V, energy, power, cosphi I,V, energy, power, cosphi

Undervoltage protection D if fe re nt ia l p ro te c ti on

50, 51,51N, 49, 27, 68 5 0, 51 , 5 1I DM T, 51 N, 49 , 6 8, 87T,87N

I,V I

Basic

50, 51, 51IDMT,51N, 51MS, 51LR, 49, 46, 66 5 0, 5 1, 5 1 ID MT, 5 1N , 4 6, 4 9, 51MS, 51LR, 66, 87M 50, 51, 51IDMT,51N, 51MS, 51LR, 49, 46, 66, 27 50, 51, 51IDM T, 51N, 51M S, 51LR, 49, 46, 66, 27, 37, 32

I

Standard

 App lic atio n specific Transformer 

Motor 

D if fe re nt ia l p ro te c ti on Undervoltage protection, motor restart Full, mot or res tart

I I,V, energy, power, cosphi I,V, energy, power, cosphi

Generator 

Basic Standard Full

50, 51,51N, 49, 46 50, 51,51N, 49, 46, 32

I I,V, energy, power, cosphi 50, 51, 51N, 51IDMT,49, 46, 32, I,V, energy, power, 27, 59, 59N cosphi

Bus tie/rise

Voltage protection Bus tie, voltage protection both sides Bus tie, voltage protection one side, ATS Voltage protection, synchrocheck, ATS Bus tie, voltage protection both sides, ATS Bus tie, voltage protection both sides, synchrocheck,  ATS

27,59,59N,50, 51 I,V 27,59,59N right side; 27,59,59N V,V left side 27, 59, 59N, ATS V

Distance protection

21, 51, 67N, 79

 Autorec losing Fault recorder  Frequency protection Frequency monitoring PFC & resonance protection THD protection

79

27, 59, 59N, 25, ATS

V, V

27,59,59N right side; 27,59,59N V,V left side, ATS 27, 59, 59N right side; 27, 59, V,V 59N left side; 25, ATS

Line

I,V, energy, power, cosphi

Option

81 55

Internet (* )

REF542 plus Rel 2.0 presentation , 52 of 62 EC V2.0 10/10/04

WEBREF (* ) Ev al u at io n /v i su a li z at io n sw pa ck ag e f or c om tr ad e f il e s i s n o t i n cl u de d.

 At most 24 protection functions can be activated

REF542plus  Applications

REF542plus – Integration in SCADA system 

Four different communication protocols are available.



REF542plus can thus be easily integrated in any SCADA systems.



Distributed intelligence architectures result in a high degree of plant automation to: 

Manage different loads and plant configurations



Change and modify the power network distribution

  Acquire   Advanced

measurements and status information

functions are also possible:



Primary parts status verification



Circuit breaker electrical and mechanical life analysis



Preventive maintenance plans

REF542 plus Rel 2.0 presentation , 53 of 62 EC V2.0 10/10/04

REF542plus  Applications

REF542plus – Engineering 

Industrial IT Overview



REF542plus 

General



Hardware



Features



 Applications



Engineering



Tests and Certifications



Customer values

REF542 plus Rel 2.0 presentation , 54 of 62 EC V2.0 10/10/04

REF542plus Engineering

REF542plus – Engineering Environment 



REF542plus Engineering

REF542plus software tools run on a PC, 2 Versions 

Configuration Tool: can manage protection functions



Operating Tool: control functions only

REF542plus software tools have the same version of the REF542plus firmware

REF542plus configuration tool

REF542 plus Rel 2.0 presentation , 55 of 62 EC V2.0 10/10/04

REF542plus - Engineering Environment



Protection functions are function blocks



Circuit breaker etc modeled with switching objects



Wealth of logic functions (And, Or, Flip-flop, ...)



Programming is done linking the objects with wires

REF542 plus Rel 2.0 presentation , 56 of 62 EC V2.0 10/10/04

REF542plus Engineering

REF542plus - Engineering Environment Function block diagram programming

PLC-Style programming REF542 plus Rel 2.0 presentation , 57 of 62 EC V2.0 10/10/04

REF542plus Engineering

REF542plus – Tests and certifications 

Industrial IT Overview



REF542plus 

General



Hardware



Features



 Applications



Engineering



Tests and Certifications



Customer values

REF542 plus Rel 2.0 presentation , 58 of 62 EC V2.0 10/10/04

REF542plus Tests & certif.

REF542plus - Type tests and certifications

  All

relevant tests according to:



IEC 60255 series



EN 61000 (basic EMC standards)



IEC 6094 (common specifications for HV switchgear and control gear standards)



EN 50263 ( New product standard )

     2    0      3    0      6    2    E    7    6    7    6   -

REF542 plus Rel 2.0 presentation , 59 of 62 EC V2.0 10/10/04



REF542plus Tests & certif.

 ATEX (PTB 02 ATEX 3000) 

 According to Directive 94/9/EC for explosive environments



EC Conformity



Panorama Verification Centre 

(ABB Internal compliance for Substation Automation Integration)

REF542plus – Customer Values 

Industrial IT Overview



REF542plus 

General



Hardware



Features



 Applications



Engineering



Tests and Certifications



Customer values

REF542 plus Rel 2.0 presentation , 60 of 62 EC V2.0 10/10/04

REF542plus Tests & certif.

REF542plus – Customer Values 



REF542plus Customer Values

Flexibility and advanced functions: 

Very complex automation sequences possible.



Flexibility also after commissioning: software changes, no new wiring.



Wealth of information in case of primary faults (fault recorder, event time, etc).

Everything in one box, which is always the same: 

Trafo feeder, motor feeder, overhead lines feeder, etc.: the box is always the same.



One kind only of spare part.



One human machine interface only to learn.

REF542 plus Rel 2.0 presentation , 61 of 62 EC V2.0 10/10/04

REF542plus – Customer Values





REF542plus Customer Values

Open connectivity to any automation systems: 

4 different protocols (Modbus RTU, IEC 103, LON Lag 1.4, Spabus).



WEBInterface for intranet/internet applications.



4...20mA analog input and output.

REF542plus General

State of the art technology 

E.G. innovative sensors supported according to new IEC 60044-8.



Wealth of protection and control functions.



User friendliness.

REF542 plus Rel 2.0 presentation , 62 of 62 EC V2.0 10/10/04

View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF