ZXDU58/ZXDU68 CSU500 Centralized Supervision Unit

Operation Guide Software Version: V1.0

ZTE CORPORATION NO. 55, Hi-tech Road South, ShenZhen, P.R.China Postcode: 518057 Tel: +86-755-26771900 Fax: +86-755-26770801 URL: http://ensupport.zte.com.cn E-mail: [email protected]

Appendix B

Alarm List Refer to the following tables for the alarms and their default levels and output relays.Table B-1Table B-2Table B-3Table B-4 and Table B-5.

Note: A1 to A6 are the six output relays. quick installation and commissioning ZXDU58/ZXDU68 DC power system.

For their corresponding interfaces, refer to the guide or product description manual of the

Table B-1 Battery and System Alarms S/N

Alarm Name

Default Level

1

Common Alarm

Mask

Output Relay Default A1

Description

Modified The CSU detects that an alarm occurs.

2

Batt.Test Fail

Mask

A2

A battery test is terminated when the battery voltage reaches Test Stop Volt. while the battery capacity does not reach Test Stop Cap.

3

LLVD1 Alarm

Critical

A2

WithDisconnect Modeset to Batt.Volt., the battery voltage is lower than LLVD1 Voltage. 

With Disconnect Mode set to Batt.Rem.Cap., the battery voltage is lower than LLVD1 Voltage or the remaining battery capacity is lower than LLVD1 Capacity.



With Disconnect Mode set to PowerOff Time, the battery voltage is lower than LLVD1 Voltage or the

B-1 SJ-20110425090737-001|2011-09-09 (R1.3)

ZTE Proprietary and Confidential

ZXDU58/ZXDU68 CSU500 Operation Guide

S/N

Alarm Name

Default Level

Output Relay Default

Description

Modified power-off time is longer than LLVD1 Duration. WithLLTD Enabledset to Enabled.

4

LLVD2 Alarm

Critical

A2

WithDisconnect Modeset to Batt.Volt., the battery voltage is lower than LLVD2 Voltage. 

With Disconnect Mode set to Batt.Rem.Cap., the battery voltage is lower than LLVD2 Voltage or the remaining battery capacity is lower than LLVD2 Capacity.



With Disconnect Mode set to PowerOff Time, the battery voltage is lower than LLVD2 Voltage or the power-off time is longer than LLVD2 Duration.

WithLLTD Enabledset to Enabled. 5

CAN Bus Abnormal

Mask

A2

The CAN bus cannot send or receive data normally due to some communication exception.

6

Batt.Det.Abnor.

Critical

A2

The battery voltage gets lower than Test Stop Volt. in the process of the battery test.

7

BLVD Alarm

Critical

A2

WithDisconnect Modeset to Batt.Volt., the battery voltage is lower than BLVD Voltage. 

With Disconnect Mode set to Batt.Rem.Cap., the battery voltage is lower than BLVD Voltage or the remaining battery capacity is lower than BLVD Capacity.

B-2 SJ-20110425090737-001|2011-09-09 (R1.3)

ZTE Proprietary and Confidential Appendix B Alarm List

S/N

Alarm Name

Default Level

Output Relay Default

Description

Modified WithDisconnect Mode set to PowerOff Time, the battery voltage is lower than BLVD Voltage or the power-off time is longer than BLVD Dura. WithBHTD Enabledset to Enabled.

8

LLTD Alarm

Critical

A2

When the environment temperature is lower than LLTD Env.Temp., the system disconnects the LLVD1 and LLVD2 loads.

9

BHTD Alarm

Critical

A2

When the battery temperature is higher than BHTD Temp., the system disconnects the batteries.

10

All Alarm Blocked

Critical

A2

The system does not display any other real-time alarms. This can be set through Alm.Ctrl.

Table B-2 AC Alarms S/N

Alarm Name

Default Level

11

AC Power Off

Major

Output Relay Default A3

Description

Modified The mains power fails and there is no standby AC input.

12

AC In.Switch Off

Mask

A3

The main AC input circuit breaker trips.

13

Pha.Volt.High

Major

A3

The detected phase voltage is higher than Pha.Volt.H.Thre.

14

Pha.Volt.Low

Major

A3

The detected phase voltage is lower than Phase Under Volt.

15

AC Phase Lack

Major

A3

The AC input lacks one phase or two.

16

Pha.Volt.Imbala

Major

A3

The difference between phase voltages is greater than Phase Volt.Imbala.

B-3 SJ-20110425090737-001|2011-09-09 (R1.3)

ZTE Proprietary and Confidential

ZXDU58/ZXDU68 CSU500 Operation Guide

S/N

Alarm Name

Default Level

17

Pha.Curr.High

Major

Output Relay Default

Description

Modified

A3

The phase current is higher than AC Curr.High.Thre.

18

AC Out.Switch Off

Mask

A3

The auxiliary AC output circuit breaker trips.

19

AC SPD Abnor

Major

A3

The AC surge protection device (SPD) is damaged or not installed.

Table B-3 Rectifier Alarms S/N

Alarm Name

Default Level

Output Relay Default

Description

Modified

20

SMR Fan Fault

Major

A4

The rectifier fan is faulty.

21

SMR Ra.T.H.O

Major

A4

The temperature of the PFC heat radiator is higher than the maximum radiator temperature (110 ℃).

22

SMR In.V.H.O.

Major

A4

The AC input voltage of the rectifier is higher than the maximum input voltage (300 V).

23

SMR In.V.L.O.

Major

A4

The AC input voltage of the rectifier is lower than the minimum input voltage (80 V).

24

SMR Out.V.H.O.

Major

A4

The output voltage of the rectifier is higher than the maximum output voltage (56.6 V to 62 V, which can be set).

25

SMR Out.C.H.

Major

A4

The output current of the rectifier is higher than the maximum output current (68 A).

26

SMR Inter.T.H.

Major

A4

The temperature at the air inlet of the rectifier is higher than the maximum internal temperature (70 ℃).

27

SMR Out.Fuse

Major

A4

The output fuse of the rectifier blows.

B-4 SJ-20110425090737-001|2011-09-09 (R1.3)

ZTE Proprietary and Confidential Appendix B Alarm List

S/N

Alarm Name

Default Level

28

SMR Curr.Share

Major

Output Relay Default A4

Description

Modified When multiple rectifiers are working in parallel, the output current difference between these rectifiers is greater than the threshold (8 A).

29

SMR Input Off

Major

A4

The power input of the rectifier is interrupted.

30

PFC Out.V.H.

Major

A4

The output voltage of PFC is higher than the threshold (450 V).

31

PFC Out.V.L.

Major

A4

The output voltage of PFC is lower than the threshold (345 V).

32

SMR EEPROM

Major

A4

Errors occur when the rectifier reads and writes the EEPROM.

33

SMR In.Comm F.

Major

A4

Some exception occurs to the communication of the Serial Communication Interface (SCI).

34

SMR Primy.C.H.

Major

A4

The primary current of the transformer is higher than the threshold (28 A).

35

PFC Input C.H.

Major

A4

Reserved alarm

36

SMR Start Abr.

Major

A4

The starting time of the rectifier exceeds 5 minutes.

37

SMR In.Fuse

Major

A4

The input fuse of the rectifier blows.

38

SMR Comm.Fail

Major

A4

The communication between the rectifier and the CSU is interrupted because the rectifier is removed or there is some communication exception.

39

SMR In.Freq.

Major

A4

The input frequency of the rectifier is too high (higher than 73 Hz) or too low (lower than 40 Hz).

40

SMR Out.V.L.

Major

A4

The output voltage of the rectifier is lower than the threshold (36 V).

B-5 SJ-20110425090737-001|2011-09-09 (R1.3)

ZTE Proprietary and Confidential

ZXDU58/ZXDU68 CSU500 Operation Guide

Table B-4 DC Alarms S/N

Alarm Name

Default Level

41

DC Volt.High

Major

Output Relay Default A5

Description

Modified The DC output voltage is higher than DC Volt.High Thre.

42

DC Volt.Low

Major

A5

The DC output voltage is lower than DC Volt.Low Thre.

43

DC SPD Abnor.

Major

A5

The DC SPD is faulty.

44

Batt.Volt.Low

Major

A5

The voltage of a battery pack is lower than Batt.Volt.L.Thre.

45

Batt.Curr.Abr.

Minor

A5

The rate of the detected battery current to the highest detectable current is greater than Batt.Curr.Abn.Rate.

46

Batt.Temp.High

Major

A5

The battery temperature is higher than Batt.Temp.H.Thre.

47

Batt.Temp.Low

Major

A5

The battery temperature is lower than Batt.Temp.L.Thre.

48

Batt.Loop Brk.

Critical

A5

The battery loop is disconnected.

49

Batt.Dischg.

Minor

A5

The battery discharge current is higher than Batt.Dischg Thre.

50

Batt.T.Invalid

Warning

A5

The system is configured with batteries, but the battery temperature detection is ineffective. The battery temperature sensor is not installed or the battery temperature is out of the detection range.

51

LLVD1 Extend Brk.

Minor

A5

The circuit breaker or fuse of the extended LLVD1 loop trips or blows.

52

LLVD1 Loop B.

Minor

A5

The circuit breaker or fuse of the LLVD1 loop trips or blows.

53

LLVD2 Extend Brk.

Minor

A5

The circuit breaker or fuse of the extended LLVD2 loop trips or blows.

B-6 SJ-20110425090737-001|2011-09-09 (R1.3)

ZTE Proprietary and Confidential Appendix B Alarm List

S/N

Alarm Name

Default Level

54

BLVD Extend Brk.

Minor

Output Relay Default

Description

Modified

A5

The fuse of the extended BLVD loop blows.

55

BLVD Loop Brk.

Minor

A5

The fuse of the BLVD loop blows.

Table B-5 Environment Alarms S/N

Alarm Name

Default Level

56

Env.Temp.High

Minor

Output Relay Default A6

Description

Modified The environment temperature is higher than Env.Temp.H.Thre.

57

Env.Temp.Low

Minor

A6

The environment temperature is lower than Env.Temp.L.Thre.

58

Env.Hum.High

Minor

A6

The environment humidity is higher than Env.Hum.H.Thre.

59

Env.Hum.Low

Minor

A6

The environment humidity is lower than Env.Hum.L.Thre.

60

Smog Alarm

Major

A6

The sensor detects smog.

61

Flood Alarm

Major

A6

The sensor detects the flooding danger.

62

Access Ctrl.Alm.

Minor

A6

The sensor detects the intrusion of something.

63

Door Alarm

Minor

A6

The door with the door status switch is opened.

64

Glass Brk.Alm.

Minor

A6

The sensor detects broken glasses.

65

Env.Temp.Invalid

Warning

A6

The environment temperature sensor is damaged or not installed.

66

Env.Hum.Invalid

Warning

A6

The environment humidity sensor is damaged or not installed.

B-7 SJ-20110425090737-001|2011-09-09 (R1.3)