Sistema Rectificador Flatpack 2

April 12, 2022 | Author: Anonymous | Category: N/A
Share Embed Donate


Short Description

Download Sistema Rectificador Flatpack 2...

Description

SISTEMA FLATPACK 2 >

José Rodas Utani Jefe de Servicios & Soporte Técnico Perú, Ecuador y Bolivia

Slide 2 of 23 29.04.2013

Generation 4

Slide 3 of 23 29.04.2013

1. Highest Power Density 33W/in3

FP2 3000

Generation 4

25W/in3

FP2 2000 FP2 1800

20W/in3

Generation 3

15W/in3

Flatpack 1800 Flatpack 1500

10W/in3

SMPS 1000

5W/in3 SMPS 60/20 Generation Saves the customer money by :

-

Slide 4 of 23 29.04.2013

1

More space for customer equipment and/or batteries Thus less cabinets and less footprint in the location

1. Highest Power Density – FP2 2KW SHELF

Dimensions

Slide 5 of 23 29.04.2013

Modular Configuration 48 VDC

17.5” Wide –

167A Maximum Per Shelf

brackets mount 19”, 21” or 23”

125A Redundant

14.5” Deep

With four rectifiers installed

1U – 1.75” Height

1. Highest Power Density – FP2 3KW SHELF

Dimensions

Slide 6 of 23 29.04.2013

Modular Configuration 48 VDC

17.5” Wide –

250A Maximum Per Shelf

brackets mount 19”, 21” or 23”

187,5A Redundant

17” Deep

With four rectifiers installed

1U – 1.75” Height

2. Pequeño y ligero

< 1.9 Kg 41.5mm 327 mm 109 mm

Más fácil para dirigir : -

Slide 7 of 23 29.04.2013

Personal de mantenimiento - especialmente como repuestos Logística - un peso más ligero, significa menos costos de envío

3. Operación de los ventiladores 2 Fans – Front to back airflow - will work with only one (Back to front version in design stage)

Ahorros por costos de mantenimiento y operación por : • -

Slide 8 of 23 29.04.2013

Evitar las salidas de llamadas de prioridad (fuera de horas normales) Da una alta eficacia del rectificador

4. Controles digitales 2 controlador digital : Dan mas supervisión y control.

Ahorro de tiempo y dinero por : -

Slide 9 of 23 29.04.2013

Dando al operadores una información más en tiempo real del sistema El personal de mantenimiento sabe exactamente qué necesita hacer con las ayudas.

5. Edge connectors Communications AC Input DC Output

Edge-connector technology

Ahorra tiempo (y dinero) : -

Slide 10 of 23 29.04.2013

Módulos intercambiables en caliente. Reduce fallas de interconexión.

6. Amplio Rango de entrada CA

Output Power vs. Input voltage 2000W 1800W

Nominal Input

850W 650W

0W 185

85V Red LED

Slide 11 of 23 29.04.2013

Yellow LED

290 300 Green LED

Red LED

6. Large AC input range

Mains derating

Output Power (%)

120

> Derating below 176Vac (185Vac on 2kW module)

100 80 60

> 1382W (46%) at 85Vac

40 20 0 0

50

100

150

200

250

Voltage (Vac) FP2 48/2000

Slide 12 of 23 29.04.2013

FP2 48/3000

300

350

7. Temperatura De-rating

Temperatura ambiente (max full carga de salida)

2000W 1800W 1400W

Linear De-rating Zone

o

o

+75

+45 Green LED

Slide 13 of 23 29.04.2013

1200W

Yellow LED

0W

Red LED

7. Temperature De-rating

Temperature derating

Output Power (%)

120

> Derating above 45 oC

100 80

> 2100W (67%) at 75 oC

60 40

> Delivers 50A at 65 oC

20

> Operating down to -40 oC

0 0

10

20

30

40

50

60

Ambient temperature FP2 48/2000

Slide 14 of 23 29.04.2013

FP248/3000

70

80

8. Excelente protección en AC/DC

Mains fuse: 2x15 A (fast) in Live and Neutral

Varistor across the lines for transient protection Hi -ohmic disconnect above 290V / 300V AC (with auto reconnect when in range)

DC Output

DC output : Blocking Diode Slide 15 of 23 29.04.2013

· Short circuit proof (constant current) · Single or double fan blockage/failure

9. Highly Efficient – 2 KW 2000W rectifier : Efficiency at 230Vac input 93

92,5

Eff.(%)

92

Max Efficiency Zone

91,5

91

90,5

90 0

200

400

600

800

1000 Pout(W)

Slide 16 of 23 29.04.2013

1200

1400

1600

1800

2000

9. Highly Efficient – 3 KW > Efficiency above 93% at 40-80% load, 92.4% at 100% load

94

93

> 10% loss reduction on system level Efficiency (%)

> Low load efficiency also improved

92

91

90

89

88

87 3000W 2000W

86 0

10

20

30

40

50

60

Load (% )

Slide 17 of 23 29.04.2013

70

80

90 100

9. Highly Efficient – 2 KW HE

Slide 18 of 23 29.04.2013

Technical Data – 24V 2000 W

Slide 19 of 23 29.04.2013

Technical Data – 48 V 1800 W

Slide 20 of 23 29.04.2013

Technical Data – 48 V 2000 W

Slide 21 of 23 29.04.2013

Technical Data – 48 V 3000 W

Slide 22 of 23 29.04.2013

Technical Data – 48 V 2000 W HE

Slide 23 of 23 29.04.2013

Procedimiento de instalación

Handle in locked position

Hole to release the handle’s spring mechanism

Handle in unlocked position

Slide 24 of 23 29.04.2013

Panel Frontal

Dual Fan Cooling

GREEN Power LED

Slide 25 of 23 29.04.2013

RED Alarm LED

YELLOW Warning LED

Panel Frontal

Power (green)

Slide 26 of 23 29.04.2013

ON

Rectifier is powered

Flashing

Smartpack controller accessing information on the rectifier

OFF

Mains are unavailable

Panel Frontal

Warning (yellow) ON

Slide 27 of 23 29.04.2013

Rectifier is in Derating Mode (reduced output power) high internal temperature (+65 to 70 C) or low input voltage (lower than 176VAC) or single fan failure The remote Battery Current Limit is activated AC input voltage is out of range Rectifier in stand-alone mode (or loss of communication with the Smartpack controller

Flashing

Rectifier is in Over-voltage Protection Mode

OFF

No abnormal situation is present

Panel Frontal

Alarm (red) ON

OFF

Slide 28 of 23 29.04.2013

Rectifier is in Shut-down Mode due to low mains (0 – 85VAC) or high internal temperature (+75 C or higher) or high output voltage (higher than 59.5 VDC) Internal rectifier failure (malfunction) Fan failure (double fan malfunction) Low output voltage (0 to 43.5VDC) CAN bus failure No alarm situation is present

Unidad de Control

> Scaleable y modular, control flexible para la gama entera de productos Eltek

Slide 29 of 23 29.04.2013

Unidad de Control

Slide 30 of 23 29.04.2013

>

Front panel backlit LCD (2x16) and key pad

>

USB for PC connection and easy FW uploading

>

CAN bus para comunicacion con modulos Eltek

>

6 entradas digitales programables

>

6 relay de salidas configurables

>

Latched contactor control

>

Monitoreo y test de baterias

>

Compensacion de carga por temperatura

>

8 symmetry measurements

>

log de eventos(10000) con hora y fecha.

>

Windows-based PC communication software

Pequeño pero de gran alcance

< 300g

44mm 144 mm

109 mm Slide 31 of 23 29.04.2013

Smartpack Vista Frontal

>

”Top-level alarms” scrolls on display when active •

Slide 32 of 23 29.04.2013

Battery, Load, Rectifier, Control System & Mains

>

Alarm LED (red) = Major Alarm active

>

Warning LED (yellow) = Minor Alarm active

>

Power LED (green) = Normal status active

Panel Trasero CAN Bus CAN bus

ID based serial bus communications •

Part No : 242100.110 (RoHS compliant)

Slide 33 of 23 29.04.2013



Max 8 Smartpack



Max 50 Rectifiers

Panel Trasero Monitoreo de Baterías Monitoreo de Baterías Con 4 : Standard Con 3 : Extended •

Symmetry measurement



8 strings mid point or 2 strings 12V block



Sensor de Temp.

Part No : 242100.110 (RoHS compliant)

Slide 34 of 23 29.04.2013

Conectividad Batería

> CON3 & CON4 – Conexiones de baterías

Cable Sensor de Temperatura

Pin

Function

1

Symmetry I/P 1

2

Symmetry I/P 2

3

Symmetry I/P 3

4

Symmetry I/P 4

5

Symmetry I/P 5

6

Symmetry I/P 6

7

Symmetry I/P 7

8

Symmetry I/P 8

9-10

Con 3 : Temp sense 2 Con 4 : Temp sense 1

11 - 14

Con 3 – 2nd batt current, batt fuse Con 4 : Not used

Slide 35 of 23 29.04.2013

Conectividad - Batería > CON3 & CON4 – Conexión de batería

Slide 36 of 23 29.04.2013

Conectividad Symmetry

> Symmetry measurement options

Slide 37 of 23 29.04.2013

Panel Trasero Sistema interno Sistema Interno System measurements Unit Power 2xLVD control (Latched)

Part No : 242100.110 (RoHS compliant)

Slide 38 of 23 29.04.2013

Battery fuse fail

Conectividad Sistema > CON5 – Conexión del sistema

System Connection Card. Art 200625 Slide 39 of 23 29.04.2013

Pin

Function

1

Positive Input

2

Negative Input

3

Batt Current +ve

4

Batt Current -ve

5

Batt Fuse +ve

6

Batt Fuse -ve

7

Load Fuse Fail

8

LVD1 Active

9

LVD1 Common

10

LVD2 Active

11

LVD2 Common

Conectividad Sistema

> Sistema de Configuración de la tarjeta

JP1 -48v system = 1-2 +24v system = 2-3 JP2 -48v system = „Neg‟ +24v system = „Pos‟

Slide 40 of 23 29.04.2013

Panel Trasero Alarmas I/O

Alarma I/O Con 1 (standard):2 + 2 relay input / output

Part No : 242100.110 (RoHS compliant)

Slide 41 of 23 29.04.2013

Con 2 (extended):4 + 4 relay input / output

Conectividad Externa y Alarm I/O

> CON1 & CON2 – I/O Conexiones

Alarm Output & Input Card Art 105954 Slide 42 of 23 29.04.2013

Pin

Function

1-2

Alarm input 1 ( + / -)

3–4

Alarm input 2 ( + / -)

5-7

Alarm output 1 ( NO /C / NC)

8 - 10

Alarm output 2 ( NO /C / NC)

1-2

Alarm input 3 ( + / -)

3-4

Alarm input 4 ( + / -)

5-6

Alarm input 5 ( + / -)

7-8

Alarm input 6 ( + / -)

9 - 11

Alarm output 3 ( NO /C / NC)

12 - 14

Alarm output 4 ( NO /C / NC)

15 - 17

Alarm output 5 ( NO /C / NC)

18 - 20

Alarm output 6 ( NO /C / NC)

RS-232 Opciones

RS-232 mounted Enables connection of Standalone Webpower or modem • Part No : 242100.112 (RoHS compliant)

Rear position : Replaces extended Battery symmetry card •

Slide 43 of 23 29.04.2013

Part No : 242100.111 (RoHS compliant)

Smartpack

Smartpack Extended RS232

Slide 44 of 23 29.04.2013

Panel Trasero Webpower incluido Embedded WebPower

Part No : 242100.113 (RoHS compliant)

Slide 45 of 23 29.04.2013

Ethernet interface of remote monitoring of Smartpack Is possible to “tunnel” Powersuite remotely also.

Smartpack Smartpack SNMP/Webpower

Slide 46 of 23 29.04.2013

Escalabilidad CAN/Power bus

Smartpack Master

Smartpack Slave n

Smartpack Slave 1

System functionality

System functionality

System functionality with 8 modules

Voltage input

1

Voltage inputs

2

Voltage inputs

8

Symmetry inputs

8 (2x4x12V)

Symmetry inputs

16 (4x4x12V)

Symmetry inputs

64 (16x4x12V)

Current inputs

2

Current inputs

4

Current inputs

2x8

Temperature inputs

2

Temperature inputs

4

Temperature inputs

2x8

General purpose inputs 6

General purpose inputs 12

General purpose inputs 6x8

Load fuse input

1

Load fuse input

2

Load fuse input

1x8

Batt fuse input

2

Batt fuse input

4

Batt fuse input

2x8

Relay outputs

6

Relay outputs

12

Relay outputs

6x8

Contactor control

2+

Contactor control

4+

Contactor control

2+x8

Slide 47 of 23 29.04.2013

Conectividad Latched Contactors

A latching contactor changes state only when a reversed pulse voltage is applied to the coil.

Slide 48 of 23 29.04.2013

Protection Diode

PowerSuite

> Explorer oriented easy to use PC SW

> USB gives simple access.

> Wide functionality with clear graphic presentation.

Slide 49 of 23 29.04.2013

Smartpack Front / Power Suite Content >

Front menu

>

Password levels

>

Alarm ”monitor”

>

AlarmGroups and output (relay) mapping

>

”Programmable” inputs

>

Event log

>

Operational mode and ”Critical” conditions

>

Low Voltage Disconnect (LVD)

>

Battery functions • Battery discharge test • Test results • Battery tables • Temp. comp & Charge curr. limitation • Test results • Special monitors • Boost • Symmetry

>

Calibration & shunt Scaling

>

Rectifier ID’s

>

Mains measurement

>

PowerSuite installation and basic introduction

Slide 50 of 23 29.04.2013

Niveles de acceso > Smartpack/PowerSuite password •

4 digit pin-code

> Nivel de usuario •

No password

> Novel de Servicio •

Password: ”0003” (default)

> Nivel de Fabrica •

Password:

> Si perdió la contraseña de servicio, envíe el numero de serie a fabrica, para poder enviar ”PUK-code” de retorno.

Slide 51 of 23 29.04.2013

Smartpack menu frontal

> VoltageInfo - details

Slide 52 of 23 29.04.2013

Option

Description

NomVolt

Nominal output voltage

BoostVolt

Battery boost-charging voltage

LowBatt1

Voltage limit for MinorLow Battery Alarm

LowBatt2

Voltage limit for MajorLow Battery Alarm

HighBatt1

Voltage limit for MinorHigh Battery Alarm

HighBatt2

Voltage limit for MajorHigh Battery Alarm

LVBD

Voltage limit for Low Voltage Battery Disconnect (LVBD)

LVLD 1.1

Voltage limit for Low Voltage Load Disconnect (LVLD)

Smartpack menu frontal > RectifierInfo - details

Slide 53 of 23 29.04.2013

Option

Description

NoOfRects.

Number of rectifiers installed in the system.

RectCurrent

Rectifier current

RectSerialNumber

Rectifier ID and serial number

Rect.PrimaryVolt

Rectifier input mains voltage

Rectifier Status

Rectifier status

Rectifier Temp

Rectifier temperature

Alarm ”monitor” cont’

Slide 54 of 23 29.04.2013

Entradas programables > 6 entradas digitales programables.

Slide 55 of 23 29.04.2013

Entradas programables > Input ”Monitor” •

Event is selectable in ”drop-down-list” - Not all activates a function (yet...)



Description may be changed

> Description and Event text listed in Event log

Slide 56 of 23 29.04.2013

Log de Eventos > Smartpack front: ”DisplayMessages” > PowerSuite: “Event Log”

> El Smartpack controlador puede almacenar hasta 1000 eventos cronológicos. Cuando el registro esta lleno, se sobre escribe el más viejo evento. > El registro se almacena en EEPROME Ejemplo

Slide 57 of 23 29.04.2013



27-09-2005 (Date ”dd-mm-yyyy”)



17:15 (Time ”hh:mm”)



Battery Voltage (Monitor name/Description)



MinorLow: ON (Event status in monitor)

Desconexión por bajo voltaje (LVD) > Se toma la acción de desconexión cuando el sistema está en “crítico” y: - El voltaje de la batería esta debajo del limite. - Delay time ha expirado, si es activo.

> Volver a conectar se toma cuando el sistema “NO es crítico” y: - El voltaje de la batería está sobre límite.

> Default hysteresis entre reconexión y desconexión es de 4V

Slide 58 of 23 29.04.2013

Funciones de Batería Test de Descarga > Smartpack Tiene dos tipos de test batería. •

Normal – usa la tabla de batería



Simplificado – usa el voltaje final y el tiempo a criterio - Si se alcanza el tiempo de la prueba las baterías son buenas - Si se alcanza el voltaje final de las baterías primero son malas

> Tres diferentes modos de test son posibles (para ambos tipos)

Slide 59 of 23 29.04.2013



Manual: Empiezo y parada por una entrada manual



Periódico/Intervalo: Programado por tiempo, fecha y el intervalo de periodos.

Funciones de Batería Resultado del Test >

Hasta 10 diferentes resultados de la prueba de descarga almacenados en la EEPROM • Empiezo Fecha [mm/dd/yyyy] • Tiempo Final [hh:mm] • Tipo de Test [Manual/Periodic/Automatic] • Tabla de batería • Duración del Test [m] • Corriente de descarga [Ah] • Voltaje final [V] • Calidad Calculada [%] • Resultado del Test

>

Datos Registardos • Corriente de bateria(1 & 2) • Voltaje de bateria • Temperatura(1 & 2) • Voltaje de simetria (8)

>

Los Resulatados pueden ser vistos haciendo click en el icono de batería en la columna del resultado de la prueba • First 10 min and last 10 min logging are done every minute • In between every - 10 min (test duration < 300 min) - 20 min (300 min < test duration < 600 min) - 40 min (600 min < test duration < 1200 min)

Slide 60 of 23 29.04.2013

Funciones de Batería Tabla de Batería > Smartpack puede almacenar dos tablas de batería definida por el usuario con: •

Tiempo [min] • Corriente de Bateria 1.9V/cell Voltaje final alto [A] • Corriente de Bateria 1.75V/cell Voltaje final bajo [A]

> NOTE. Muchas tablas de batería pueden ser almacenadas en la PC y facil de uploaded al Smartpack con PowerSuite > What is Eltek Std? •

Slide 61 of 23 29.04.2013

Es el promedio de valores no cambiables de los diferentes tipos de fabricantes de baterías.

Funciones de Batería Tabla de Batería > Configuración de la tabla de baterías por Powersuite

Slide 62 of 23 29.04.2013

Funciones de Batería Tabla de Batería

Slide 63 of 23 29.04.2013

Funciones de Batería Temp. Comp. & Curr. Lim. > Compensacion por temperatura •

Slope



Ref. temp



Min comp. volt



Max comp. volt

> Limitación corriente de batería

Slide 64 of 23 29.04.2013



Dos limitación configurables (v1.02)



Planta generadora, indicando con una entrada digital.

Funciones de Batería Temp. Comp. & Curr. Lim.

Output Voltage [Vdc]

55,5 55 54,5 54

Slope 53,5 53 52,5 Min Comp, volt

Slide 65 of 23 29.04.2013

o

Temperature T [ C]

Max Comp, Volt

Battery Current (A)

Funciones de Batería Temp. Comp. & Curr. Lim.

Battery current limit [A] = 0.3*C10 Float current Mains OK

Mains failure

Mains OK, Recharge

Load current Mains

Slide 66 of 23 29.04.2013

Mains OK

Rectifier ID’s cont’ > Reset number of rectifiers

Slide 68 of 23 29.04.2013

Soluciones de Sistemas Cuanta potencia usted necesita ?

>

Mas densidad de potencia

Up to 8000W per 1PR shelf

1U

Slide 70 of 23 29.04.2013

Montaje Flexible

Smartpack mounting options

Smartpack in PR

Slide 71 of 23 29.04.2013

Smartpack in Distribtuion

Soluciones Integradas

Soluciones Integradas 2U

Incluye (up to) :

5 kg

Slide 72 of 23 29.04.2013

(exc rectifiers)

 1U Distribucion + 1 PR  8000W (166A@48V)  Smartpack  2 x 100A Breakers de Bateria  6 x 2–32A Breakers de Carga  2 x LVD (150A)

Soluciones Integradas

Solucion Integrada 5 - 8U Incluye (up to) :

8 kg

Slide 73 of 23 29.04.2013

(exc rectifiers)

 4U Distribucion + 1-4 PR  32000W (660A@48V)  Smartpack  6 x 100A Breakers de Bateria*  18 x 2–63A Breakers de carga*  2 x LVD (up to 600A) * Verficar en datasheet por otra for otra configuracion disponible

Soluciones Integradas

23” EIA Seismic Equipment Rack

FP2NX-48-9U power system block

7U available equipment space Battery Disconnect #4 Battery Tray #4 Battery Disconnect #3

Slide 74 of 23 29.04.2013

Battery Tray #3

Battery Disconnect #2

Battery Tray #2

Battery Disconnect #1

Battery Tray #1

Gabinetes

> 8 - 96 kW en un solo Gabinete

> Max 2000A@48V = 96kW

(CAN bus limitation)

> Típicamente hasta 4PR por sistema con baterías. Example 32 kW Slide 75 of 23 29.04.2013

> Variedad de gabientes disponibles

Solución Gabinete 96kW

Slide 76 of 23 29.04.2013



Input 230V/400V 3-phase



FP2 2kW rectifiers



Max Output 48V 2000A



Cabinet dimensions: 600x2000x600mm



2 SmartPacks (Master-Slave)

Gracias!!

Slide 77 of 23 29.04.2013

View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF