Application Example  04/2016

House Control with LOGO! 8 and Weather Sensors LOGO! 8, KTP400 Set 11

https://support.industry.siemens.com/cs/ww/en/view/68585346

Warranty and liability

Warranty and liability Note

The Application Examples are not binding and do not claim to be complete regarding the circuits shown, equipping and any eventuality. The Application Examples do not represent customer-specific solutions. They are only intended to provide support for typical applications. You are responsible for ensuring that the described products are used correctly. These Application Examples do not relieve you of the responsibility to use safe practices in application, installation, operation and maintenance. When using these Application Examples, you recognize that we cannot be made liable for any damage/claims beyond the liability clause described. We reserve the right to make changes to these Application Examples at any time without prior notice. If there are any deviations between the recommendations provided in these Application Examples and other Siemens publications – e.g. Catalogs – the contents of the other documents have priority.

 Siemens AG 2016 All rights reserved

We do not accept any liability for the information contained in this document. Any claims against us – based on whatever legal reason – resulting from the use of the examples, information, programs, engineering and performance data etc., described in this Application Example shall be excluded. Such an exclusion shall not apply in the case of mandatory liability, e.g. under the German Product Liability Act (“Produkthaftungsgesetz”), in case of intent, gross negligence, or injury of life, body or health, guarantee for the quality of a product, fraudulent concealment of a deficiency or breach of a condition which goes to the root of the contract (“wesentliche Vertragspflichten”). The damages for a breach of a substantial contractual obligation are, however, limited to the foreseeable damage, typical for the type of contract, except in the event of intent or gross negligence or injury to life, body or health. The above provisions do not imply a change of the burden of proof to your detriment. Any form of duplication or distribution of these Application Examples or excerpts hereof is prohibited without the expressed consent of the Siemens AG. Security information

Siemens provides products and solutions with industrial security functions that support the secure operation of plants, systems, machines and networks. In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept. Siemens’ products and solutions only form one element of such a concept. Customer is responsible to prevent unauthorized access to its plants, systems, machines and networks. Systems, machines and components should only be connected to the enterprise network or the internet if and to the extent necessary and with appropriate security measures (e.g. use of firewalls and network segmentation) in place. Additionally, Siemens’ guidance on appropriate security measures should be taken into account. For more information about industrial security, please visit http://www.siemens.com/industrialsecurity. Siemens’ products and solutions undergo continuous development to make them more secure. Siemens strongly recommends to apply product updates as soon as available and to always use the latest product versions. Use of product versions that are no longer supported, and failure to apply latest updates may increase customer’s exposure to cyber threats. To stay informed about product updates, subscribe to the Siemens Industrial Security RSS Feed under http://www.siemens.com/industrialsecurity.

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

2

Table of Contents

Table of Contents Warranty and liability ................................................................................................... 2 1

Task ..................................................................................................................... 4

2

Solution............................................................................................................... 6 2.1 2.2 2.2.1

3

Mode of Operation ........................................................................................... 10 3.1 3.1.1 3.1.2 3.1.3 3.1.4 3.1.5 3.2 3.2.1

4

Monitoring with the KTP400 ............................................................... 28 KTP400 screens ................................................................................. 28 Start screen ........................................................................................ 28 Overview of weather data................................................................... 29 System functions ................................................................................ 30 Online Support information................................................................. 31 Operator Control and Monitoring with KTP700 and KTP400 ............. 32 Operation via PC ................................................................................ 35

Links & Literature ............................................................................................ 36

 Siemens AG 2016 All rights reserved

6.1 6.2 7

Installing the hardware ....................................................................... 15 KTP400............................................................................................... 15 LOGO! 8 ............................................................................................. 15 Assigning IP addresses to LOGO and setting the master mode ....... 16 Software installation (download) ........................................................ 16 Commissioning ................................................................................... 17 Basic settings for the KTP400 ............................................................ 17 Settings in the operating system ........................................................ 20 Assigning devices and programs ....................................................... 21 Loading the programs into the KTP400 and KTP700 ........................ 21 Configuring dynamic warning messages for wind in the KTP700 WinCC project .................................................................................... 24

Operation .......................................................................................................... 28 5.1 5.1.1 5.1.2 5.1.3 5.1.4 5.1.5 5.2 5.3

6

Weather sensors ................................................................................ 10 Wind sensor ....................................................................................... 10 Light sensor ........................................................................................ 10 Twilight sensor ................................................................................... 11 Rain sensor ........................................................................................ 11 Temperature sensor ........................................................................... 11 Configuration in network mode .......................................................... 11 Creating a project in network view and two-way programming.......... 12

Installation and Commissioning .................................................................... 15 4.1 4.1.1 4.1.2 4.1.3 4.2 4.3 4.3.1 4.3.2 4.3.3 4.3.4 4.3.5

5

Overview............................................................................................... 6 Hardware and software components ................................................... 7 Components used ................................................................................ 7

Bibliographic references ..................................................................... 36 Internet link specifications .................................................................. 36

History............................................................................................................... 36

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

3

1 Task

Task

1

This LOGO! set expands the house control of LOGO! Set 9 “House Control with Master-Slave Communication” or LOGO! Set 10 “House Control with Touch Panel” by a weather station with a LOGO! 8 and a Basic Panel.

Note

Further information on the functionalities of LOGO! Set 9 and LOGO! Set 10, and the respective documentation for download is available in entry IDs 64143308 and 68585344.

Risk of property damage or personal injury LOGO! Set 10 is based on LOGO! Set 9/10. In order to avoid property damage and personal injury it is absolutely necessary to observe the precautions and warnings from LOGO! Set 9 and 10 for the hardware installation, the handling of the blinds and how to operate the application.

WARNING

 Siemens AG 2016 All rights reserved

Introduction In a residential home, the following functions shall be controlled automatically using weather sensors and the measuring values displayed on a Basic Panel: 

Blinds



Roof hatch



Interior and exterior lighting



Heating



Garden watering

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

4

1 Task

Figure 1-1

Blinds Rolloup/down auf/ab

Roof hatch up/down Dachluke auf/ab

Interior light Licht innen on/off ein/aus

Blinds up/down Rollo auf/ab

Heating Heizung

 Siemens AG 2016 All rights reserved

PT 100 Exterior light Licht außen on/off ein/aus

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

Central light Licht zentral on/off ein/aus

5

2 Solution 2.1 Overview

2

Solution

2.1

Overview

Schematic layout The figure below shows a schematic overview of the most important components of the solution: Figure 2-1

1

2

4

 Siemens AG 2016 All rights reserved

3

PROFINET IE

Set 9/10

Set 11

In the automation solution, a weather station is connected to the LOGO! Set 9 / Set 10 hardware setup. The weather station consists of a LOGO! 8 (1), a LOGO! power supply (3), a Compact Switch module (2) and a SIMATIC HMI KTP400 Basic Panel (4). The SIMATIC HMI KTP400 Basic Panel will be called “KTP400”.

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

6

2 Solution 2.2 Hardware and software components Advantages/benefits

2.2



Weather dependent controlling and monitoring of a house control with LOGO! 8, weather sensors and Touch Panel



Individually setting each of the blinds also possible in automatic mode



Minimizing wind damage at the blinds



Cost reduction through efficient room temperature with internal and external temperature comparison



Additional option to control the functionalities of the application on the PC via the WinCC Basic Panel simulation function

Hardware and software components

Note

Please note that in this LOGO! Set, the LOGO! Set 9 and LOGO! Set 10 hardware setup is expanded by a weather station with a LOGO! 8 and a Basic Panel.

 Siemens AG 2016 All rights reserved

Detailed information on the LOGO! Set 9 / Set 10 hardware setup can be found in the LOGO! Set 9 documentation under entry ID 64143308 and in the LOGO! Set 10 documentation under entry ID 68585344.

2.2.1

Components used The application example was created with the following components:

Hardware components Table 2-1 No.

Component

Qty

Article number

1.

LOGO! 12/24RCE

1

6ED1052-1MD000BA8

2.

LOGO! CSM 12/24 COMPACT SWITCH MODULE

1

6GK7177-1MA200AA0

3.

LOGO!POWER 24 V/4 A

1

6EP1332-1SH52

4.

SIMATIC HMI KTP400 BASIC

1

5.

Rain sensor  „1V output voltage -> no rain  9V output voltage -> rain  Output voltage: 0-10V DC  Operating voltage: 12-24 V DC

1

6AV2123-2DB030AX0 Available from specialist retailers

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

Note

For the connection of the application example to LOGO! Set 9 or LOGO! Set 10.

e.g. Stengler rain sensor RS-600

7

2 Solution 2.2 Hardware and software components

 Siemens AG 2016 All rights reserved

No.

Component

Qty

Article number

Note

6.

Temperature sensor  Measuring range: -20°C…+40°C  Output voltage: 0-10V DC  Operating voltage: 12-24 V DC

1

Available from specialist retailers

e.g. Stengler temperature sensor TS-S

7.

Twilight sensor  Measuring range: 0…255 Lux (linear)  Output voltage: 0-10V DC  Operating voltage: 12-24 V DC

1

Available from specialist retailers

e.g. Stengler twilight sensor DS-S

8.

Light sensor  Measuring range: 0…40 kLux (linear)  Output voltage: 0-10V DC  Operating voltage: 12-24 V DC

1

Available from specialist retailers

e.g.: Stengler light sensor LE-S

9.

Wind sensor  Measuring range: 0.8…40 m/s  Output signal: Frequency, max. 24 V DC, 100Hz = 40m/s  Supply Voltage: max 24V DC

1

Available from specialist retailers

e.g.: Ventus Mini wind gage: Art. 200 430

Software components Table 2-2 Component

Qty

Article number

LOGO!Soft Comfort V8

1

6ED1058-0BA08-0YA1

SIMATIC WINCC BASIC V13 SP1

1

6AV2100-0AA03-0AA5

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

Note

8

2 Solution 2.2 Hardware and software components Example files and projects The following list includes all files and projects that are used in this example. Table 2-3 Component

 Siemens AG 2016 All rights reserved

68585346_LOGO_Set11_CODE_v20.zip

Note This zip-file contains  The enhanced LOGO! Soft Comfort project for the master LOGO! from LOGO! Set 9/ LOGO! Set 10  the LOGO!Soft Comfort project for the LOGO! 8 from the weather station from LOGO! Set 11  a revised WinCC V13 project for the KTP700 from LOGO! Set 10  a WinCC V13 SP1 project for the KTP400 of the weather station from LOGO! Set 11 Note: Please note that the LOGO! program and the WinCC project from LOGO! Set 10 have been expanded here by the following functions:  Weather sensor data processing  Weather-dependent panel alarm messages  Automatic mode for lighting

The LOGO! and the WinCC program from Set 10 are replaced by the programs from Set 11. Unzip and load all contained programs from Set 11 to the relevant LOGO!s and/or panels (see Table 4-2). 68585346_LOGO_Set11_DOKU_v20_en.pdf

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

This document.

9

3 Mode of Operation 3.1 Weather sensors

Mode of Operation

3 Note

Detailed information on the house functions controlled in this application example can be found in the LOGO! Set 9 documentation under entry ID 64143308. It is also possible to use the LOGO! Set 11 individually as a mere weather station or to control other devices.

3.1

Weather sensors

3.1.1

Wind sensor The measured values from the wind sensor are processed in the LOGO! program “68585346_LOGO!_Set11_LOGO!_8.lsc” in the “Blinds” program part. In automatic mode, all blinds are raised in the event of “strong” wind via function block “wind” (B183/analog threshold trigger).

 Siemens AG 2016 All rights reserved

For protecting the blinds, “strong wind” (here, 20 km/h) is given functional priority over high solar irradiation (here, 20 kLux) and lowering via weekly timers. The function block “wind” can be called up in parameter assignment mode with the respective block name using the LOGO! display or LOGO! TDE. This makes it possible to adjust the threshold values for the wind speed for opening the blinds. When wind speeds fall below 18 km/h, the LOGO! program signals that the wind has died down and the blinds can be moved down again.

Note

3.1.2

For wind velocities below the limit value (here, 18 km/h), the blinds will be raised in the morning and lowered in the evening automatically according to the set times of the weekly timers.

Light sensor The light sensor is processed in the LOGO! program in the blinds control. In automatic mode, all blinds are lowered in the event of high solar irradiation (here, 20 kLux) via function block “sun” (B184/analog threshold trigger). High solar irradiation takes priority over raising via weekly timers. Manual switching of blinds takes highest priority, even if the automatic mode is activated and high solar irradiation occurs. The function block “sun” can be called up in parameter assignment mode with the respective block name using the LOGO! display or LOGO! TDE. This makes it possible to adjust the threshold values for sun irradiation for closing the blinds.

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

10

3 Mode of Operation 3.2 Configuration in network mode

3.1.3

Twilight sensor The twilight sensor is processed in the LOGO! program in the lighting control. In automatic mode, all exterior lights are automatically switched off at sunrise (> 10 lux) and switched on at dusk (< 10 lux) via function block “twilight” (B187/analog threshold trigger). Manual switching of lights takes highest priority, even if the automatic mode is activated. The function block “twilight” can be called up in parameter assignment mode with the respective block name using the LOGO! display or LOGO! TDE. This makes it possible to individually adjust the threshold value for automatic switching off and on of the lighting.

3.1.4

Rain sensor The rain sensor is processed in the LOGO! program in the program parts garden watering and roof hatch.

 Siemens AG 2016 All rights reserved

In automatic mode, if it does not rain, the garden watering is switched on automatically in the morning at 09:00 a.m. and in the evening at 08:00 p.m. for 10 minutes via the function block “watering” (B104/Weekly Timer). If automatic mode for the roof hatch has been activated, it will automatically close when it rains. If it does not rain and the temperature is high, the roof hatch will open. The function block “watering” can be called up in parameter assignment mode with the respective block name using the LOGO! display or LOGO! TDE. This makes it possible to adjust days and times in the weekly timer for automatic garden watering.

3.1.5

Temperature sensor The temperature sensor is processed in the LOGO! program in the program part roof hatch. In automatic mode, the roof hatch is opened via function block “auto roof” (B105) at high temperature (here, >28 °C) and closed at low temperature (here, 22 °C outside temperature. The function block “temp out” can be called up in parameter assignment mode with the respective block name using the LOGO! display or LOGO! TDE. This makes it possible to individually adjust the threshold value for automatic switching off of the heating.

3.2

Configuration in network mode From LOGO! Soft Comfort V8 onwards, you are now able to interconnect several LOGO! base modules with each other and with other devices (WinCC and S7CPUs) in the new network view. Communication between the devices will be configured automatically. In addition, it is possible to display three programs at once and to drag&drop signals from one program to the other.

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

11

3 Mode of Operation 3.2 Configuration in network mode

3.2.1

Creating a project in network view and two-way programming

Adding a device in network view Table 3-1 No.

Action/response Start LOGO!Soft Comfort V8.

2.

Click on “Network project” tab to open the network project view.

3.

Click on “Add new device”. The subsequent window enables you to add devices you want to use to the network.

4.

The network view gives you an overview of the devices used in your network.

 Siemens AG 2016 All rights reserved

1.

LOGO!Soft Comfort V8

Two-way programming If more than one LOGO! device is added to the network view, you can connect individual function blocks with drag&drop and can exchange data between the individual LOGO! devices. Note

Please note that two-way programming is only possible between LOGO! 0BA8 devices

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

12

3 Mode of Operation 3.2 Configuration in network mode

Table 3-2 No.

Action/response A double-click on one of the LOGO! base modules in the network view automatically opens the switching program in the diagram editor of the network project.

2.

To exchange data between two LOGO! devices, open the switching programs of two LOGO! devices.

3.

Now click on the symbol for dividing the diagram editor in two windows in order that an additional window in the diagram editor opens.

4.

Then, click on the bar with the name of one of the two switching programs and drag the diagram into the second window that has opened in the diagram editor.

5.

Move the mouse pointer to the output connection of one of the function blocks you want to connect and keep holding the mouse button down.

 Siemens AG 2016 All rights reserved

1.

LOGO!Soft Comfort V8

Then, move the mouse pointer to the function block you want to connect the first function block with. When you release the mouse button, LOGO!Soft Comfort V8 will connect both function blocks.

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

13

3 Mode of Operation 3.2 Configuration in network mode No. 6.

Action/response

LOGO!Soft Comfort V8

Once both function blocks are connected, LOGO!Soft Comfort V8 will create a function block pair and an Ethernet connection and a data transfer mechanism. When the function blocks are displayed in green, configuration of the communication between the two LOGO! devices is complete.

 Siemens AG 2016 All rights reserved

Note: If one of the two function blocks is displayed in red, configuration of the communication between the two LOGO! devices is not yet complete.

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

14

4 Installation and Commissioning 4.1 Installing the hardware

Installation and Commissioning

4 Note

4.1

Please also observe the information on installation and commissioning in the Set_9 and Set 10 documentation, unless you would like to operate Set 11 separately.

Installing the hardware

Table 4-1 Action 1.

Create Sets 9, 10 and 11 as shown in Figure 2-1.

Comment  

2.

Connect the sets with LAN cables

4.1.1  Siemens AG 2016 All rights reserved

Set 11 can be used separately, without connecting other sets. Set 11 can also be used only with Set 9. For this, the LOGO! software from Set 11 must be used for house control

KTP400

Note

Observe the setup guidelines for the KTP400. Further information can be found in the KTP400 Basic Panel Manual.

IP addresses and subnet masks Make sure that the KTP400, your PC and the hardware setup from LOGO! Set 9 and LOGO! Set 10 are in the same IP address range, as shown in the following table.

Table 4-2 No.

Device

IP address

Subnet mask

1.

KTP400 weather station (Set 11)

192.168.1.80

255.255.255.0

2.

KTP700 (Set 10)

192.168.1.20

255.255.255.0

3.

LOGO! weather station (Set 11)

192.168.1.13

255.255.255.0

4.

Master LOGO! (Set 9)

192.168.1.10

255.255.255.0

5.

Slave LOGO! (Set 9)

192.168.1.11

255.255.255.0

6.

LOGO! TDE (Set 9)

192.168.1.14

255.255.255.0

7.

Network card or USB Ethernet Adapter for network connection to PC

192.168.1.12

255.255.255.0

4.1.2 Note

LOGO! 8 Changes of the IP address or the master-slave mode are only possible in “STOP” mode.

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

15

4 Installation and Commissioning 4.2 Software installation (download)

4.1.3

Assigning IP addresses to LOGO and setting the master mode

Table 4-3

 Siemens AG 2016 All rights reserved

No.

Action/response

1.

Go to the “Network” item via the LOGO! display using the arrow keys C1▲ or C2▼ of the LOGO! 8 and press OK.

2.

Select the “IP address” item.

3.

Press the OK button of the LOGO! controller and use the arrow keys C1▲, C2▼, C3 ◄ and C4 ► to enter your LOGO!’s IP address (here: 192.168.1.13). Confirm with the OK button.

4.

Press the ESC key to return to the previous menu item and select “Set M/S mode”.

5.

For configuring the master LOGO!, select “Master”.

6.

The configuration of the IP address and the mode for the LOGO! is now complete. Press ESC to return to the main menu

4.2 Note

LOGO! Display

Software installation (download) It is assumed that the required software LOGO!Soft Comfort V8 and WinCC have been installed on your PC. No previous experience with the software is required.

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

16

4 Installation and Commissioning 4.3 Commissioning

4.3

Commissioning

Note

For the following points you find information in LOGO! Set 9: 

Download LOGO! program in LOGO! controller



Settings for web server access

For LOGO! Set 9 refer to the following entry: Building Automation Systems: House control with LOGO! and Master-Slave communication (LOGO! Set 9) https://support.industry.siemens.com/cs/ww/en/view/64143308

4.3.1

Basic settings for the KTP400

Note

The IP address of the HMI panel can only be changed if Runtime has been “stopped”.

 Siemens AG 2016 All rights reserved

Table 4-4 No.

Action/response

7.

Switch on the KTP400.

8.

Press “Settings” to open the panel settings.

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

KTP400 display

17

4 Installation and Commissioning 4.3 Commissioning No. 9.

Action/response 1. 2.

3.

  4.

 Siemens AG 2016 All rights reserved

5.

6.





KTP400 display

Press “Network interface” to open the dialog for changing the network settings. Make your choice between automatic IP address assignment via “DHCP” and manual IP address assignment. Touch the respective input fields and enter the IP address and the subnet mask with the screen keyboard, here: IP address: 192.168.1.80 Subnet mask: 255.255.255.0 Under “Ethernet parameters” in the “Mode and speed” selection field, tick “Auto Negotiation”; this automatically detects and sets the connection type and the transmission rate in the PROFINET network. Activate the “LLDP” switch to enable the operator panel to exchange information with other operator panels. In this example, “LLDP” can be activated or deactivated. Under “PROFINET” in the “Device name” field, enter a network name for your operator panel. The name must meet the following requirements: Max. four blocks with max. 63 characters each. Example: “Press1.Fender. Bodywork.Hall3” Characters from “a” to “z”, numbers “0” to “9”; special characters: “-” and ".

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

18

4 Installation and Commissioning 4.3 Commissioning No.

Action/response

4.

Press “Settings” on the left side of the dialog window for changing the network settings to return to the panel settings window.

5.

To load a project onto the HMI panel, a data channel must be enabled: 1.

 Siemens AG 2016 All rights reserved

2. 3.

KTP400 display

Click the “Transfer settings” button to open the “Transfer Settings” dialog box. Activate “Enable transfer”. Activate “Automatic” to enable automatic transfer. When automatic transfer is enabled, a transfer from the configuration PC can be started while the project is running. In this case, the current project is stopped and the transfer of the new project is carried out. After the transfer, the new project is started.

6.

To return to the start center, press on the symbol for minimizing the window on the right side of the “Transfer Settings” dialog.

7.

In the start center, you can start your project any time by pressing “Start”.

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

19

4 Installation and Commissioning 4.3 Commissioning

4.3.2

Settings in the operating system

Table 4-5 No. 1.

 Siemens AG 2016 All rights reserved

2.

Action/response

PC screen

In the operating system, navigate to: “Start > Settings > Control Panel > Set PG/PC Interface”. In “Interface Parameter Assignment Used”, select “TCP/IP(Auto) -> Name of your network card or your USB Ethernet adapter” (without the yellow warning sign) for the Ethernet communication with LOGO!.  In this example: TCP/IP(Auto)->Intel(R) 82577LM Gigab. network card) Make sure that in the dropdown menu “Access Point of the Application” “S7ONLINE (STEP7) -> TCP/IP(Auto) -> Name of your network card or your USB Ethernet adapter” has been selected. Click on OK to confirm the selection.

3.

Alternatively the “Interface Parameter Assignment Used” is displayed at “Control Panel -> Set PG/PC Interface” for certain operating systems. As in the previous step 2, also select the interface here and make sure that “Access Point of the Application” “S7ONLINE (STEP7) -> TCP/IP(Auto) -> Name of your network card or your USB Ethernet adapter” has been selected in the drop-down list. Click on OK to confirm the selection.

4.

Acknowledge the warning prompt that appears in certain operating systems with OK to complete the selection.

5.

The settings in the operating system required for controlling the application example with the Basic Panel or with the PC screen are now complete.

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

20

4 Installation and Commissioning 4.3 Commissioning

4.3.3

Assigning devices and programs

Table 4-6 No.

Device

Program for the device in the zip file

1.

KTP400 weather station (Set 11)

68585344_LOGO!_Set11_weather_station_V20.ap13

2.

KTP700 (Set 10)

68585344_LOGO!_Set11_HMI_WinCC_V20.ap13

3.

LOGO! weather station (Set 11)

68585346_LOGO!_Set11_LOGO!8_weather_station.lsc contained in the network project 68585346_LOGO!_Set11_LOGO!_8.lnp

4.

Master LOGO! (Set 9)

5.

Slave LOGO! (Set 9)

68585346_LOGO!_Set11_LOGO!_8.lsc contained in the network project 68585346_LOGO!_Set11_LOGO!_v20.lnp

6.

LOGO! TDE (Set 9)

4.3.4

Loading the programs into the KTP400 and KTP700

Table 4-7 No. 1.

Action/response

WinCC

Start WinCC and with “Browse”, open the project “68585344_LOGO!_

 Siemens AG 2016 All rights reserved

Set11 _weather_station_V20”. Then click “Open”.

Note: Repeat the steps of this table for the project “68585344_LOGO!_Set11_

HMI_WinCC_V20“ of the KTP700, unless you would like to operate Set 11 separately.

2.

Click on “Open the project view” to open it.

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

21

4 Installation and Commissioning 4.3 Commissioning

 Siemens AG 2016 All rights reserved

No.

Action/response

3.

In the project tree under „KTP400 [KTP400 Basic PN]“ go to “Connections” and select it with a double click.

4.

In “HMI device”, enter the IP address of your Basic Panel (here: 192.168.1.80) and press Enter to confirm.

5.

6.

WinCC

Make sure that  “S7ONLINE” is specified under “Access point”.  the master LOGO! IP address is specified under “PLC” (here: 192.168.1.13).  the check box “Cyclic operation” is ticked. In the project tree, go to “Devices & networks” and select it with a double click.

Make sure a subnet has been added to the network. To create a subnet in the network, open the context menu with a right click on the Ethernet interface and click on “Add subnet”. Note: In this application example, the subnet has already been added in the WinCC project.

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

22

4 Installation and Commissioning 4.3 Commissioning No.

Action/response Click on the Ethernet interface and go to the “Properties” tab. Enter IP address and subnet mask of your Basic Panel, here: • IP address: 192.168.1.80 • Subnet mask: 255.255.255.0

8.

In the project tree, select the folder “KTP400 Basic PN” and click on “Load” in the toolbar.

9.

Select the Ethernet interface of your network card or your USB-Ethernet adapter with which you will connect your PC to the Basic Panel. Then click on "Load".

10.

Then confirm the dialog and then click on "Load".

11.

As soon as the project download has been completed, the project will automatically start on the Basic Panel and you can now operate the application.

 Siemens AG 2016 All rights reserved

7.

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

WinCC

23

4 Installation and Commissioning 4.3 Commissioning

4.3.5

Configuring dynamic warning messages for wind in the KTP700 WinCC project In the WinCC project for the KTP700, 4 different dynamic warning messages for wind have been configured. One of the 4 warning messages is displayed depending on the wind speed:

Overview of warning messages Table 4-8

 Siemens AG 2016 All rights reserved

No.

Wind level

Speed

Warning message text

1.

Weak wind

>= 1 km/h

Weak wind: (Wind speed) km/h Blinds can still be operated!

2.

Moderate wind

>= 20 km/h

Moderate wind: (Wind speed) km/h! Blinds will remain closed!

3.

Fresh wind

>= 30 km/h

Fresh wind: (Wind speed) km/h! Blinds will remain closed!

4.

Strong wind

>= 40 km/h

Strong wind: (Wind speed) km/h! Blinds will remain closed!

Warning message color

Individually adjust and modify warning messages Warning message texts, thresholds and colors can be modified and adjusted to the requirements of the application at any time. The table below shows which parameters to set in WinCC to change the warning messages. Table 4-9 No. 1.

Action/response 1. 2.

3.

WinCC Basic

Start WinCC Basic V13 Select your unzipped project „68585344_ LOGO!_Set11_HMI_ WinCC_V20“ with “Browse”. Then click “Open”.

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

24

4 Installation and Commissioning 4.3 Commissioning No.

Action/response Click on “Open the project view” to open it.

3.

In the project tree under „KTP700 [KTP700 Basic PN]“, go to “HMI alarms” and select it with a double click.

4.

Navigate to the “Analog alarms” tab. The following options are provided: 1. “Trigger tag” allows you to specify which tag to use for monitoring the threshold (here for wind). 2. Enter the limit value in “Limit” to define when a specific warning message is displayed.

 Siemens AG 2016 All rights reserved

2.

WinCC Basic

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

1

2

25

4 Installation and Commissioning 4.3 Commissioning

 Siemens AG 2016 All rights reserved

No.

Action/response

5.

You can display a value in the warning message text (here, e.g., the wind speed): 1. Double-click on one of the warning messages to open the text editing mode. 2. Now go to the place in the text where you would like to display a value. 3. Open the context menu with a right click and select the menu item “Insert tag field”.

6.

Now select the tag you would like to display in the text and specify the number of digits to be displayed in the message.

WinCC Basic

Then click on the green checkmark to close the window.

7.

Now, go to the “Alarm classes” tab. Here you can assign userdefined names to the individual warning messages. In addition, you can define the background color of the warning message.

8.

Under “Screen management”, go to “Global screen” and open it with a double click.

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

26

4 Installation and Commissioning 4.3 Commissioning No. 9.

Action/response Proceed as follows: 1.

2.

 Siemens AG 2016 All rights reserved

10.

WinCC Basic

Click on the “Alarm window” to open its properties. Go to the “Properties" tab and make sure that the warning messages (here for wind) which you have configured, are enabled under “Current alarm states” and “Unacknowledged alarms”.

Once you have completed all changes and modifications of the warning messages, click “Load” in the toolbar to load the project to the KTP700.

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

27

5 Operation 5.1 Monitoring with the KTP400

Operation

5 Hinweis

Operating via integrated webserver, the LOGO! display and LOGO! TDE is described in LOGO! Set 9. For LOGO! Set 9 refer to the following entry: Building Automation Systems: House control with LOGO! and Master-Slave communication (LOGO! Set 9) https://support.industry.siemens.com/cs/ww/en/view/64143308

5.1

Monitoring with the KTP400

5.1.1

KTP400 screens All KTP screens have a uniform toolbar on the right:

 Siemens AG 2016 All rights reserved

Press one of the buttons to go to the following screens:

Note

5.1.2



Start



Weather



System



Support



Language switching

Synchronized language change from Basic Panel to LOGO! 8: If the KTP400 is used to change the language with the button, the display language on the LOGO! display and LOGO! TDE will also change.

Start screen Figure 5-1

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

28

5 Operation 5.1 Monitoring with the KTP400

This screen is displayed right after system start.

5.1.3

Overview of weather data

 Siemens AG 2016 All rights reserved

Figure 5-2

This figure displays the current measured values from the weather sensors.

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

29

5 Operation 5.1 Monitoring with the KTP400

5.1.4

System functions

 Siemens AG 2016 All rights reserved

Figure 5-3

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

30

5 Operation 5.1 Monitoring with the KTP400 This screen provides system functions: 

Clean screen



Calibrate



(Data) transfer



Runtime Stop

More information on the system functions can be found in the Basic Panel manual \4\.

5.1.5

Online Support information

 Siemens AG 2016 All rights reserved

Figure 5-4

Information on the Online Support can be found here. The Home button (1) brings you back to the main menu.

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

31

5 Operation 5.2 Operator Control and Monitoring with KTP700 and KTP400

5.2

Operator Control and Monitoring with KTP700 and KTP400

Table 5-1

 Siemens AG 2016 All rights reserved

No.

Action/response

KTP700 and KTP400

1.

Verify on the KTP700 (LOGO! Set 10) that “Automatic mode” for the blinds is activated.

KTP700

2.

The wind speed exceeds 20 km/h.

KTP400

3.

All blinds move up and stay in this final position for as long as the wind is strong (>20 km/h).

KTP700

4.

The KTP700 displays a warning message that the wind speed has increased.

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

32

5 Operation 5.2 Operator Control and Monitoring with KTP700 and KTP400 No.

Action/response

KTP700 and KTP400

5.

Press the “Alarm indicator” to open the “Alarm window” with the wind speed warning messages.

KTP700

6.

A warning message is displayed in the “Alarm window” that the wind has reached a moderate speed.

KTP700

 Siemens AG 2016 All rights reserved

Note: A total of 4 different warning messages have been configured for different wind speed levels in the WinCC project in this application example. Older warning messages which have not been acknowledged remain on display in the alarm window, even if the wind speed has changed or other warning messages have been activated. 7.

Press the button for acknowledging warning messages until the current warning message is hidden. If required, press the acknowledgment button several times to acknowledge older messages that may still be listed.

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

KTP700

33

5 Operation 5.2 Operator Control and Monitoring with KTP700 and KTP400 No.

Action/response

KTP700 and KTP400

Close the message window after you have cleared all warning messages.

KTP700

9.

If the wind speed drops below 18 km/h and at the same time there is high irradiation (>20 kLUX), all blinds will automatically close.

KTP400

 Siemens AG 2016 All rights reserved

8.

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

34

5 Operation 5.3 Operation via PC

5.3

Operation via PC

Note

When using the application example with your PC, please make sure the KTP400 or KTP700 is not connected with the other modules of the application example (LOGO! modules, PC, etc.). It is recommended not to connect the Basic Panel, if you already use your PC as a Basic Panel with the WinCC simulation.

For operating the application example with the PC, the same basic settings (chapter 4.3.1) in the WinCC project apply as for direct operation with the Basic Panel. The only difference is that you do not press the “Load” button, but the “Start simulation” button. Table 5-2

 Siemens AG 2016 All rights reserved

No.

Action/response

1.

In the project tree, select the folder „KTP400[KTP400 Basic PN]“ and click on “Start simulation” in the toolbar.

2.

Press “OK” in the displayed message to start the runtime simulator.

3.

Then, the runtime simulator starts with the project.

4.

You can now operate the application example via your PC with your mouse.

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016

WinCC

35

6 Links & Literature

6

Links & Literature

6.1

Bibliographic references

Table 6-1 Topic

Title

\1\

LOGO! 8

LOGO! 8 A Practical Introduction, with Circuit Solutions and Example Programs Author: Stefan Kruse Published by: Publicis ISBN: 9783895789267

\2\

LOGO! 8

LOGO!8 - MiniTrainerSchool Author: Klaus Machalek Product No.: LOGO! MTS

6.2

Internet link specifications

Table 6-2

 Siemens AG 2016 All rights reserved

Topic

Link

\1\

Siemens Industry Online Support

http://support.industry.siemens.com

\2\

Download page of the entry

https://support.industry.siemens.com/cs/ww/en/view/68585346

\3\

LOGO! 8 Manual

https://support.industry.siemens.com/cs/ww/en/view/100761780/6 7518106635

\4\

HMI KTP400 Manual

https://support.industry.siemens.com/cs/ww/en/view/90114350

\5\

LOGO! Software updates

http://w3.siemens.com/mcms/programmable-logiccontroller/en/logic-module-logo/demosoftware/Pages/Default.aspx

\6\

LOGO! Application Examples

http://w3.siemens.com/mcms/programmable-logiccontroller/en/logic-module-logo/applicationexamples/Pages/Default.aspx

History

7 Table 7-1 Version

Date

Modifications

V1.0

04/2013

First version

V1.1

03/2014

Layout modified and security note amended

V2.0

04/2016

Software and documentation revision with LOGO! 8

House Control and Weather Sensors - LOGO! Set 11 Entry ID: 68585346, V2.0, 04/2016