SiemensFlexCable Handbook
Short Description
Siemens Cable Handbook...
Description
INDEX: FLEXIBLE CABLES
For power and control with or without fibre optic's, Siemens cables have been developed to provide optimum performance, maximum safety and extended life
SECTION 1 General Flexible Elastomer Cables ➔ SINGLE CORE 3.3kV FLEX ➔ OZOFLEX ➔ OZOFLEX (PLUS) ➔ OZOFLEX (PLUS) SCREENED (FC+) ➔ HYDROFIRM (T) ➔ HYDROFIRM (T) SCREENED ➔ PROTOMONT HD ➔ PROTOMONT Screened
5DF2 5DH2 5DH1 5DH5 5DH1 5DH1 5DL1 5DL2
SECTION 2 High Temperature Cables ➔ SINOTHERM ➔ EVA 125 FLEX
5DR3/5 5DR7
Page 30 34 42 48 52 60 64 70 74 80
SECTION 3 PVC Data and Control Cables ➔ PROTOFLEX Ö500 uncscreened 5DE7 ➔ PROTOFLEX Ö500 screened 5DE7 ➔ PROTOFLEX-EMV-FC 5DE6 ➔ EMC CABLE GLANDS ➔ BLUEGLOBE CABLE GLANDS
86 96 100 104 108
SECTION 4 Crane, Reeling and Hoist Cables ➔ CORDAFLEX (SMK) ➔ RONDOFLEX ➔ PLANOFLEX ➔ OPTOFLEX ➔ SPREADERFLEX ➔ PENDANTFLEX
5DH3 5DG6 5DG5 5DG8 5DE5 5DE5
112 126 148 154 162 166
SECTION 5 Mining Cables and High Voltage Reeling Cables ➔ PROTOMONT XHD 5DL4 ➔ MINING MSR 5DM4 ➔ PROTOLON 5DK8
170 176 180
SECTION 6 Technical Tables and Formulae
188
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
1
APPLICATION SELECTION GUIDE
Construction
1. 2. 3.
1. 2. 3. 4.
1. 2. 3. 4.
2
Designation
Rated Voltage
Application & Design
3.3kV 1100 Flex 5DF2
0.6/1kV to 1.9/3.3kV
Single core highly flexible cable for switchboard cabling; submains, machine and equipment cabling. Suitable for high and sub-zero temperatures with a high short circuit strength.
30
OZOFLEX 5DH2
0.6/1kV
Heavy duty EPR/CSP flexible for power and control supply. Suitable as flexible leads in mining, industry and agriculture.
34
OZOFLEX (PLUS) 5DH10
0.6/1kV
Especially suitable for submersion in sewage and effluent, waste water, polluted liquids containing oils, fats, solvents and chemicals etc. For pumps and aerators.
42
PCP elastomer Sheath Protolon R-EP-110 insulation Tinned copper conductor, highly flexible
CSP elastomer sheath Elastomer inner sheath EPR insulation Copper conductors, flexible
Page
Special CSP elastomer sheath Elastomer inner sheath EPR insulation Copper conductors, flexible
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
3
APPLICATION SELECTION GUIDE
Construction
1. 2. 3. 4. 5.
1. 2. 3. 4.
1. 2. 3. 4. 5. 4
CSP elastomer outer sheath Copper braid screen Elastomer inner sheath EPR insulation Copper conductor, flexible
Designation
Rated Voltage
OZOFLEX (PLUS) SCREENED 5DH5
0.6/1kV
Screened cable suitable for VSD's submersion in sewage and effluent, waste water, polluted liquids containing oils, fats, solvents and chemicals etc. For pumps and aerators requiring control cores.
48
HYDROFIRM (T) 5DH1
0.6/1kV
Circular and flat flexible cable especially developed for continuous submersion in fresh, salt and bore water as a power supply to pumps and underwater electrical equipment.
52
HYDROFIRM (T) SCREENED 5DH1
0.6/1kV
Screened flexible cable especially developed for continuous submersion in fresh, salt and bore water as a power supply with control cores to pumps and underwater electrical equipment.
60
Special EPR sheath Watertight bond between insulation and sheath EPR insulation Copper conductors, flexible
EPR outer elastomer sheath Copper braid screen Elastomer inner sheath EPR insulation Copper conductor, flexible
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Application & Design
Sales & Order Processing
Phone 131 773
Page
Fax 1800 060 773
5
APPLICATION SELECTION GUIDE
Construction
1. 2. 3. 4.
1. 2. 3. 4. 5.
1. 2.
1. 2. 6
Designation
Rated Voltage
Application & Design
PROTOMONT HD 5DL1
0.6/1kV
Extra heavy duty flexible cable for mining, construction, industry and harsh environments. Designs suitable for submersion in aggressive liquids. Single core cables suitable for mobile festoon systems.
64
PROTOMONT SCREENED 5DL2
0.6/1kV
Heavy duty overall screened EPR/PCP flexible in 4 and 5 core constructions. Submersible pumps, mining where earth screen protection in required.
70
SINOTHERM 5DR3 5DR4 5DR5
380/660V 0.6/1kV
High temperature silicone cables up to 180°C. Suitable for motor rewinds, heating appliances, steelwork, floodlights etc. Available with glass braid and in flexible multicore constructions.
74
EVA 125 FLEX 5DR7
0.6/1kV
High temperature EVA flexible cables for 125°C application. Increased mechanical strength with low smoke, and a non toxic gas emission and halogen free sheath in the event of fire. For switchboard wiring and coils.
80
PCP elastomer sheath Elastomer inner sheath PROTOLON EPR insulation Copper conductors, flexible
PCP elastomer sheath Copper braid screen Elastomer inner sheath EPR insulation Copper conductor, flexible
Silicone rubber insulation Copper conductors, flexible
EVA elastomer insulation Copper conductors, flexible
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Page
Fax 1800 060 773
7
APPLICATION SELECTION GUIDE
Construction
Designation
PROTOFLEX Ö500 5DE7
1. 2.
1. 2. 3.
PVC sheath Copper conductors, flexible
UV-stabilised PVC orange outer sheath. Tinned copper braid screen. Cross linked poly ethylene (XLPE) insulation.
3. 8
300/500V
PROTOFLEX Ö500 SCREENED 5DE7
PROTOFLEX EMV-FC UV stabilized 5DE6
EMC Cable Glands 1. 2.
Rated Voltage
0.6/1 kV
Application & Design
Page
Light duty flexible PVC control cable for machine tools, process automation and control devices.
86
Flexible overall screened PVC control cable for EMI and RFI interference suppression in industrial electronics, switchboards, PLC connections, etc.
96
Flexible tinned copper braid screened XLPE power cable for variable speed drive to motor connections.
100
EMC metric glands are IP68, brass, galv nichel plated. Designed for EMC environments, ensuring positive contact with the cable.
104
Highest protection IP68 & 15 bar. One gland body for several cable O.D’s. Highest strain relief.
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
9
APPLICATION SELECTION GUIDE
Construction
Designation
1. Highest protection IP68 up to 15 bar. 2. One gland for several cable O.D's. 3. Highest strain relief.
1. 2. 3. 4. 5.
1. 2. 3. 4. 10
Rated Voltage
blueglobe®
Cable Glands
Blueglobe cable glands are available in brass, plastic and stainless steel. Widest sealing range in one gland body. Highest strain relief and IP68 up tp 15 bar.
108
0.6/1kV
Crane, reeling and festoons cable designed to withstand tensile and torsional stresses. Suitable for all types of mobile equipment eg., stackers, reclaimers, hoists, cranes, ship loaders, trippers etc. Screened data cores for PLC and communications are standard. Integrated fibre optics available.
112
RONDOFLEX 5DG6
0.6/1kV
Flexible power and control cable, for use on festoon systems and for connecting moving parts of machine tools, material handling equipment, etc, associated with high mechanical stresses and frequent bending operation. Suitable for simple reeling.
126
PCP elastomer sheath Protolon insulation Tinned finely stranded conductors Braid screen available Phone 131 773
Page
CORDAFLEX (SMK) 5DH3
PCP elastomer sheath Anti torsion textile braid Elastomer inner sheath Protolon EPR insulation Copper conductors, highly flexible
Sales & Order Processing
Application & Design
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
11
APPLICATION SELECTION GUIDE
Construction
1. 2. 3. 4.
1. 2. 3. 4.
12
Designation
Rated Voltage
0.6/1kV
Shielded EMC festoon power cable used for applications where there is a danger of interference to data transmission systems from power cables. This cable is suitable for festoon systems.
132
RONDOFLEX (CHAIN) 5DG5
0.6/1kV
Specially designed for outdoor applications with long travel distances at high speeds. Including drag cabin systems on container stacking cranes. Key benefits are reliability, abrasion resistance and long life time.
136
PCP elastomer sheath Protolon EPR insulation Tinned copper conductors, extremely flexible Individual copper braid screens
Phone 131 773
Page
RONDOFLEX (C)-FC 5DG6
PCP elastomer sheath Protolon insulation Tinned finely stranded conductors Overall braid screen shield
Sales & Order Processing
Application & Design
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
13
APPLICATION SELECTION GUIDE
Construction
Designation
PLANOFLEX 5DG5
1. 2. 3. 4.
1. 2. 3.
1. 2 3.
14
Rated Voltage
380/660V 0.6/1kV
Application & Design
Page
Flat form elastomer cable for gantry and festoon installations in mining, marine and sub zero environments. Screened cores, pairs and integrated fibre optics available for data transmission.
148
OPTOFLEX (M) 5DG8
Optical signal and data transmission cable for fixed installations for material handling and mining equipment and in open pits on conveyors.
154
OPTOFLEX (F.O) 5DG8
Flexible fibre optic cable suitable for cable handling systems, cable tenders on cranes and material handling systems. Key benefits are high data rates, large bandwith and absolute immunity to EMI.
158
PCP elastomer sheath PROTOLON EPR insulation Copper conductors, extremely flexible Individual copper braid screens
Orange PCP outer sheath. Kevlar braided coverage of core assembly. 50/125; 62.5/125 micron graded index and E9 mono mode fibres.
Black PCP outer sheath. Kevlar braided coverage of core assembly. 50/125; 62.5/125 micron graded index and E9 mono mode fibres.
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
15
APPLICATION SELECTION GUIDE
Construction
1. 2. 3. 4. 5.
1. 2. 3. 4.
16
Designation
Rated Voltage
300/500V
Dedicated flexible cable for free fall coiling in spreader crane applications. Kevlar reinforced with lead bead weights to improve performance in high speed, high wind environments.
162
PENDANTFLEX 5DE5
300/500V
Lift control and pendant cable with central support element. Extremely flexible and lightweight for elevators, hoists, cranes and for increased suspension distances.
166
PVC sheath PROTODUR PVC insulation Copper conductors, flexible Central support element
Phone 131 773
Page
SPREADERFLEX 5DE5 Polyurethane sheath Lead beaded core elements Kevlar rope strength support PROTODUR PVC insulation Copper conductors, highly flexible
Sales & Order Processing
Application & Design
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
17
APPLICATION SELECTION GUIDE
Construction
1. 2. 3. 4. 5.
1. 2. 3. 4. 5.
18
Designation
Rated Voltage
0.6/1kV
Extra heavy duty mining cable with screened power cores and separate control cores. Abrasion and tear resistant, suitable for all above ground mining installations and industry eg., drills, pumps, conveyors and 400 Hz installations.
170
MINING MSR 5DM4
250/250V
Twisted pair screened elastomer cable for mining installations. Heavy duty and flexible, resistant to UV with excellent transmission characteristics for PLC’s, instrumentation and control signals.
176
CPE sheath Overall copper braid screen Elastomer inner sheath Polyethylene insulation Copper conductors, flexible, screened pairs
Phone 131 773
Page
PROTOMONT XHD 5DL/5DM PCP heavy duty sheath Elastomer inner sheath Individual copper core screens PROTOLON EPR insulation Copper conductors, flexible
Sales & Order Processing
Application & Design
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
19
APPLICATION SELECTION GUIDE
Construction
1. 2. 3. 4. 5.
1. 2. 3. 4. 5. 6.
20
Designation
Rated Voltage
0.6/1kV to 33/33kV
High voltage flexible reeling cable specifically designed to withstand torsional and tensile forces of medium duty reeling. Suitable for all mobile equipment in mining, marine and materials handling facilities.
182
PROTOLON (SM) 5DK8
0.6/1kV to 33/33kV
High voltage, heavy duty reeling cable specifically designed for extreme dynamic applications eg., high mount reelers, high speed cranes, multiple deflection guidance systems.
182
Protofirm PCP HD Anti torsion textile braid Elastomer inner sheath Protolon EPR insulation Semiconductive core screens Copper conductors, highly flexible
Phone 131 773
Page
PROTOLON (N) 5DK8 Protofirm PCP sheath Elastomer inner sheath Protolon EPR insulation Semiconductive core screens Copper conductors, flexible
Sales & Order Processing
Application & Design
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
21
APPLICATION SELECTION GUIDE
Construction
1. 2. 3. 4. 5. 6. 7.
1. 2. 3. 4. 5. 6.
1. 2. 3. 4. 5. 22
Designation
Protofirm PCP HD outer sheath Anti torsion textile braid Elastomer inner sheath Protolon EPR insulation Semiconductive core screens Highly flexible copper conductors Mono mode & multi mode fibres
Rated Voltage
0.6/1kV to 33/33kV
High voltage reeling cable with integrated fibre optics for transmission of voice, video and data signals thereby eliminating the need for a separate control reeler.
182
PROTOLON (SB) 5DK8
3.6/66kV to 33/33kV
Designed as a power supply or connection cable for large material handling machines in open cut mines where they are subject to extremely high mechanical stresses due to abrasion and trailing. Also available with screened power cores.
182
PROTOLON (Single Core) 5DK8
3.6/6.6kV to 22/22kV
Designed for voltages up to 22kV for power supply interconnections, transformer drop cable, mobile sustations, over head service line connections and H.V switchboards.
184
Protofirm PCP sheath Elastomer inner sheath Protolon EPR insulation Semiconductive core screens Copper conductors, flexible Phone 131 773
Page
PROTOLON (SM-R) FO FIBRE OPTICS
Protofirm PCP heavy duty sheath Anti torsion textile braid Elastomer inner sheath Protolon EPR insulation Semiconductive core screens Copper conductors, highly flexible
Sales & Order Processing
Application & Design
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
23
FLEXIBLE CABLE DESIGN AND ELECTRICAL CRITERIA
SHEATH MATERIALS
The design and proper selection of a cable should take into account environmental conditions, electrical, thermal and mechanical stresses that can be expected as these all have a bearing on its operating life. All Siemens flexible cables are designed to suit their application perfectly, thereby ensuring a long trouble free service life even under the harshest conditions.
CONDUCTORS Siemens flexible cables utilise high conductivity copper in accordance with the Australian Standard AS 1125 either fi nely or extra fi nely stranded, depending on its intended application, and these are bunched or rope laid to provide a flexible conductor assembly with increased mechanical strength. All values for strandings are given as approximate due to final conductance values of the copper used in production. The Australian Standard AS1125 now nominates for flexible cables a maximum DC resistance value for a given conductor cross section. In this way the cross- sectional area of the conductor is stated not as the geometrical, but as the electrically effective cross-sectional area determined by the resistance measurement. Thereby, all cables will have equivalent electrical characteristics irrespective of the manufacturer or the origin of the base copper used. Conductor resistance values are given on page 174, table 6.10 and comply with AS 1125.
Likewise sheath materials are either thermoplastic or elastomeric compounds such as Chlorosulphonated Polyethylene (CSP), Polychloroprene (PCP), Chlorinated Polyethylene (CPE), Silicone (SR), Ethylene Propylene Rubber (EPR), or Polyurethane (PU). CSP is often known by the DuPont trade name Hypalon and PCP as Neoprene. Each particular sheath material is selected or specially compounded for its specific characteristics. eg EPR (HYDROFIRM) compounded with additives to achieve total water resistance. PCP (CORDFLEX) for a high mechanical strength and abrasion resistance. Although the base polymer name is used eg. CSP, up to 14 additives may be compounded to achieve the desired characteristics based on years of research, field service and customer’s requirements.
INSULATION AND SHEATH THICKNESSES All Siemens elastomer (synthetic rubber) cables meet or exceed the values laid down in AS 3116 and AS 3191 (flexible cords). Voltage ratings based on the insulation electrical, thermal and mechanical characteristics for each cable are given. SINOTHERM silicone insulated 0.6/1kV cables are in accordance with and approved to AS 3178.
INSULATION Insulation materials covered within this catalogue are of basically two types. Thermoplastic polyvinyl chloride (PVC) and cross linked compounded elastomers such as Ethylene Propylene Rubber (EPR), Ethyl Vinyl Acetate (EVA) and Silicone rubber. The Silicone and EVA compounds permit higher operating temperatures, and accordingly higher current capacities, whilst EPR exhibits excellent dielectric properties, low temperature flexibility and resistance to ozone, ionization and weather. To attain resistance against elevated water temperatures Cross Linked Polyethylene (XLPE) is used in single core and flat form HYDROFIRM and Protoflex EMV-FC.
24
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
25
GRAPH RANGE/TEMPERATURE
AMBIENT AND CONDUCTOR OPERATING TEMPERATURE Ambient temperature is that surrounding the cable. All values stated in this catalogue are based on an ambient of +30.5°C which is generally considered the norm for Australian conditions when averaged annually. Surface temperature is the maximum permissible temperature onto which the cable can be laid upon without damage to the sheath. Conductor temperature is the temperature the conductor will maintain when loaded fully in accordance with its rated current carrying capacity. The maximum permissible conductor temperature is also the temperature rating of the insulation which it can withstand indefinitely without effect on its properties. The difference between the ambient temperature and the maximum conductor temperature is the window of thermal heat rise generated when current is passed. Basically the heat generated by current flow must be equalised by convection and thermal radiation so that an equilibrium is maintained at the maximum insulation temperature. For this reason the derating factors are applicable when higher or lower ambients are present.
HIGH AND LOW TEMPERATURES Siemens elastomer cables utilise insulation and sheathing compounds which provide excellent performance in extremes in ambient temperatures. In sub zero environments the catalogue lists the absolute minimum that the cable can withstand and additionally the minimum for fully flexible operation in its intended application. Elastomer insulated conductors operate continuously at 90.5°C with an emergency overload up to 130°C and short circuit temperature withstand of up to 250.5°C. Experience has shown that flexible reeling cables with tinned conductors should be limited to a short circuit temperature of 200.5°C. Exposure to higher temperatures than the cables are rated will lead to degredation over a period of time of the compounds based on the rate of exposure and intensity. Fig. 1 shows the service life characteristic for EPR insulation. The temperature index criteria was 113.5°C, ie., the compound will remain serviceable for 20,000hrs at 113.5°C in accordance with IEC 216. This table is purely indicative as many variables can effect the result.
26
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Fig. 1
VOLTAGE RATINGS Voltage values are usually expressed in the form Uo/U and Um. Uo is the rms power frequency voltage between phase and earth. U is the rms power frequency voltage between phases. Um is the maximum continuous rms power frequency voltage between any two phases and excludes fault conditions or sudden disconnection of large loads. Sales & Order Processing
Phone 131 773
Fax 1800 060 773
27
CURRENT CARRYING CAPACITY Current ratings are dependant on the method of installation, the insulation material affecting the maximum conductor temperature, internal thermal resistance and external ambient conditions. Unless otherwise indicated the ratings stated within are for cables touching a surface and unenclosed, based on a 50Hz system either single phase or balanced three phase. For all intents and purposes current ratings for DC are equivalent to AC values.
VOLTAGE DROP Volt drop is dependant on the impedance of the conductor, the load current, power factor and route length. In accordance with AS/NZS 3008.1.1:1998 the milli-volts per ampere meter (mV/A.m) are listed on Page 81/ 81, Table 41/42 together with the formula to satisfy the voltage drop limitations. AS 3000 generally limits the allowable voltage drop to 5% of the system Voltage, however some mining installations may nominate a lower value. It is important where practicable in the case of single core cables they are run in trefoil arrangement to minimise impedance.
SHORT CIRCUIT Symetrical short circuit calculations are given on page 160, table 6.2 and are based on the maximum operating temperature of the insulation and the maximum final safe short circuit temperature of the insulated conductor.
AUSTRALIAN STANDARDS The following Australian Standards relate to cables, their design and application. AS 1125 AS 3116 AS 3191 AS 3178 AS 3147 AS 3008 AS 1802
28
Conductors in Flexible Cables and Cords Elastomer Insulated Cables 0.6/1kV Electric Flexible Cords 250V, 440V and 0.6/1kV Silicone Rubber Insulated Wires and Cables Thermoplastic (PVC) Insulated Cables 0.6/1kV Cable Selection 0.6/1kV Cables for Underground Mining (Reeling)
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
AS 2802 Cables for Above Ground (open cut) Mining AS 1979 Flexible Cables for Lifts AS 1660 Test Methods for Cables AS 1429 XLPE High Voltage Cables 3.3 - 33kV Generally all Australian Standards are aligned with the relevant IEC Standards to enable them to conform internationally. IEC 227 Flexible PVC Cables and Cords IEC 245 Flexible Elastomer Cables and Cords VDE 0250 Cables, Wires and Flexible Cords for Power Installations VDE 0282 Elastomer Cables and Flexible Cords for Power Installations
CABLE REPAIR In the event of damage to either the insulation or sheath or where two cables must be spliced together, the use of commercially available repair materials are suitable for use with Siemens flexible cable compounds. Various methods and types are available from cast kits which offer a simple, effective, however non-flexible joint to electrical repair and selffusing tapes which when applied build up the insulation and sheath to their specified dimensions and provide a flexible, weatherproof repair equal to the original cable. It is most important that the repair tapes and kit compounds match those of the cables and this should be confirmed with the supplier prior to use. R-EP-90 (EPR) tape must be used on all Siemens elastomer insulated cables and HD-85-PCP and HD-90-CSP tapes should be used on their appropriate sheath types. Other repair materials from Calico and polyester tapes, semi conductive screen tape, silicone, vinyl/mastic and glass cloth tapes to tinned copper wire braid screen tapes are available from various manufacturers and include all instructions on preparation and installation.
QUALITY ASSURANCE We, at Siemens, have a deep commitment to quality assurance at all levels of our organisation. In fact, this catalogue represents one step in the quality effort by presenting complete product and applications information in such a way that leads to optimum product selection to satisfy the customer’s needs.Our internal quality assurance programme includes quality audits, the maintenance of a quality assurance manual and many other procedures designed to optimise quality. Sales & Order Processing
Phone 131 773
Fax 1800 060 773
29
SINGLE CORE 3.3KV 1100 FLEX
SINGLE CORE 3.3KV 1100 FLEX
Highly Flexible, Single Core Rubber Cables
OPERATING TEMPERATURE -
APPLICATION • • • • • • • • • •
Internal Switchboard Cabling Sub-mains Electrical Traction Vehicles Battery Bank Connections Machine & Equipment Cabling Steelworks, cranes & hoists Stacker & Reclaimer cabling DC wiring 415/ 1000V installations Submersible to 100 metres
Minimum permissible ambient temperature Maximum permissible conductor temperature Maximum permissible short circuit temperature Minimum ambient temperature for optimum fully flexible operation
The following minimum bending radii should be observed to ensure operating reliability. For fixed installation 6 x cable diameter When freely flexing 8 x cable diameter
CURRENT CARRYING CAPACITY Current ratings are based on continuous operation at an ambient temperature of 40°C. At other temperatures these values must be converted using the following table.
Single core 3.3kV flex cables consist of extra finely stranded tinned copper conductors laid up to provide an extremely flexible design. The Protolon R-EP-110 elastomer insulation is rated at 3.3kV with an oil resistant, flame retardant PCP sheath completing the construction.
°C 15 20 25 30 35 40 45 50 55 60 65 70 75 80 Factor 1.26 1.20 1.15 1.10 1.05 1.00 0.94 0.88 0.81 0.73 0.65 0.57 0.47 0.34
Current ratings are based on AS/NZS 3008.1.1:1998. Table 8 CurrentCarrying Capacities of Three Single-Core 0.6/1kV Sheathed and Unsheathed non-armoured cables R-E-110
The cable is in accordance with AS1125, AS3116 and VDE0250 part 602. for NSGAFoeu.
TENSILE STRENGTH
Permissable thermal short-circuit currents for 1 s duration (conductor temperature at start of short-circuit: 110°C):
The maximum allowable tensile stress is 15N/mm2. This ensures no conductor damage will occur in operation.
[mm2]
VOLTAGE RATING
4 0.488
6
10
0.732 1.22
16
2
35
-25°C
MINIMUM BENDING RADII
DESIGN
[kA]
-40°C 110°C 250°C
50
70
1.95 3.05 4.27 6.10 8.54
95
120
185
240
11.6
14.6 18.3 22.6
150
29.3
Permissible short-circuit currents for other durations are given on Page 190. The thermal as well as the dynamic short-circuit strength must be taken into account. The cables must in particular be firmly fixed to protect them from the effects of peak short-circuit currents.
-
Rated Voltage: 0.6/1kV to 3.3kV AC Maximum operating voltages in: 3 phase AC operation Uo/U = 2.1/3.6kV DC operation Uo/U = 2.7/5.4kV AC test voltage = 6kV
CORE COLOUR IDENTIFICATION The core insulation is white.
30
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
31
SINGLE CORE 3.3KV 1100 FLEX
SINGLE CORE 3.3KV 1100 FLEX
Selection and Ordering Data No. of cores x conductor size
Part No.
Approx No. of Strands x Max.
Diameter of Bare Conductor Strand
mm
mm
Min mm
Max mm
mm2
Cable Overall Diameter
Cable Weight
kg/km
Current Carrying Capacity when installed Unenclosed Spaced
Unenclosed Spaced from surface
Unenclosed Touching
Enclosed
A
A
A
A
1 x 1.5
5DF2 043
28 x 0.26
1.5
5.0
6.5
50
31
27
25
22
1 x 2.5
5DF2 053
45 x 0.26
1.9
5.5
7.0
65
43
38
36
32
1x4
5DF2 063
51 x 0.31
2.5
6.0
7.5
85
57
50
47
41
1x6
5DF2 073
75 x 0.31
3.2
6.5
8.0
105
73
63
59
51
1 x 10
5DF2 103
77 x 0.41
4.1
8.0
9.5
160
99
86
81
71
1 x 16
5DF2 123
123 x .041
6.5
9.5
11.5
235
130
115
105
93
1 x 25
5DF2 133
190 x 0.41
6.8
11.5
13.5
360
175
155
145
125
1 x 35
5DF2 143
268 x 0.41
8.1
13.0
15.0
460
220
190
175
150
1 x 50
5DF2 153
384 x 0.41
9.6
14.5
16.5
620
265
230
215
180
1 x 70
5DF2 163
545 x 0.41
11.2
16.0
18.0
820
340
290
270
235
1 x 95
5DF2 173
724 x 0.41
13.2
18.5
20.5
1070
420
365
340
285
1 x 120
5DF2 183
926 x 0.41
14.9
20.5
22.5
1320
490
420
395
335
1 x 150
5DF2 203
1154 x 0.41
16.6
22.5
24.5
1620
570
485
455
380
1 x 185
5DF2 213
1407 x 0.41
18.0
24.0
26.0
1950
660
560
530
450
1 x 240
5DF2 223
1866 x 0.41
21.2
27.5
30.5
2540
790
670
630
550
1 x 300
5DF2 233
1551 x 0.51
23.6
29.3
36.9
3460
910
780
730
630
1 x 400
5DF2 243
1995 x 0.51
27.2
32.5
39.5
4332
1070
910
850
720
Current ratings are based on AS/NZS 3008.1.1:1998. Table 8 Current-Carrying Capacities of Three Single-Core 0.6/1kV Sheathed and Unsheathed non-armoured cables R-E-110
32
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
33
OZOFLEX
OZOFLEX
Heavy Duty EPR/CSP Rubber Flexible Cables
OZOFLEX cables, covered by the Prescribed Items Act mandatory approval for flexible leads, are accordingly overed by Approval Certificate No. 11551.
OPERATING TEMPERATURE -
APPLICATION • • • • • • • •
Heavy Duty construction site leads for drills, pumps, saws, kangos Cranes, hoists & festoon systems Steelworks and rolling mills Stage & Theatre power & lighting Hand held drills, grinders & welders Agricultural equipment Portable motors, generators & power supplies Submersible to 100 metres plus
DESIGN OZOFLEX is designed as a heavy duty flexible for dry, damp and wet environments, areas of stress caused by vibration or impact and is resistant to abrasion, exposure to radiated heat and chemical contamination. Because of the black, flame retardant CSP sheath OZOFLEX is suitable for areas subject to fire hazard and hazardous locations. OZOFLEX cables consist of finely stranded copper conductors laid up to provide a flexible design. R-EP-90 elastomer insulation provides improved current capacities. Cables above 16mm2 and all control cables have an elastomer inner sheath. The CSP elastomer sheath (Hypalon) is oil resistant and flame retardant in accordance with VDE 0472.
Minimum permissible ambient temperature Maximum permissible short circuit temperature Minimum ambient temperature for optimum fully flexible operation
-40°C 250°C -25°C
MINIMUM BENDING RADII The following minimum bending radii should be observed to ensure operating reliability. -
For fixed installation 4 x cable diameter
-
When freely flexing 5 x cable diameter
CURRENT CARRYING CAPACITY Current ratings are based on continuous operation at an ambient temperature of 40°C. At other temperatures these values must be converted using the following table. °C 15 20 25 30 35 40 45 50 55 60 65 70 75 80 Factor 1.26 1.20 1.15 1.10 1.05 1.00 0.94 0.88 0.81 0.73 0.65 0.57 0.47 0.34
When installed on spring operated reelers the following de-rating factors are to be applied: 1 2 3
layer on real layers layers
0.80 0.61 0.49
The construction is in accordance with the Australian Standards AS 1125, AS 3191, AS 3116 and DIN/VDE 0282 IEC332-1 and CENELEC standards for O7RN. 34
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
35
OZOFLEX
OZOFLEX
VOLTAGE RATING -
Rated Voltage: Uo/U Maximum operating voltages in: 3 phase AC operation Uo/U DC operation Uo/U AC test voltage
-
CORE COLOUR IDENTIFICATION
= 0.6/1kV = 0.7/1.15kV = 0.9/1.73kV = 2.5kV
Single Core 3 Core 4 Core 5 Core Multi core
black blue, brown, green/yellow brown, black, green/yellow, grey blue, brown, black, green/yellow, grey black insulation sequentially numbered including a green/yellow earth core.
*The cable is designated 450/750V with EI1 insulation compound in accordance with VDE/IEC and meets or exceeds the Australian Standard AS 3116 for the voltage rating of 0.6/1kV, R-EP-90.
TENSILE STRENGTH
Selection and Ordering Data
The maximum allowable tensile stress is 15N/mm2. This ensures no conductor damage will occur in operation.
No. of Cores x Conductor Size
OZOFLEX with black insulation and sheath
without a green/yellow earth
36
mm2 1 x 10 1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 2 x 1.5 2 x 2.5 2x4
Sales & Order Processing
Part No.
5DH2 110-5 5DH2 112-5 5DH2 113-5 5DH2 114-5 5DH2 115-5 5DH2 116-5 5DH2 117-5 5DH2 118-5 5DH2 120-5 5DH2 121-5 5DH2 122-5 5DH2 123-5 5DH2 204-5 5DH2 205-5 5DH2 206-5
Phone 131 773
Approx. No. of Strands x Max Strand Diameter
Diameter of Bare Conductor
mm 80 x 0.41 126 x 0.41 196 x 0.41 276 x 0.41 396 x 0.41 546 x 0.41 725 x 0.41 927 x 0.41 1157 x 0.41 1409 x 0.41 1869 x 0.41 2338 x 0.41 30 x 0.26 50 x 0.26 56 x 0.31
mm 4.1 5.7 6.8 8.1 9.7 11.2 13.2 14.9 16.6 18.0 21.2 23.6 1.5 1.9 2.5
Fax 1800 060 773
Cable Overall Diameter
Min mm 9.8 11.0 12.5 14.0 16.5 18.5 21.0 23.5 26.0 28.0 31.5 33.5 9.0 10.5 12.0
Max mm 12.5 14.5 15.0 16.5 19.5 21.0 24.0 26.5 28.5 30.0 35.0 38.0 11.5 13.5 15.0
Sales & Order Processing
Cable Weight
Unenclosed Touching
kg/km 230 320 450 605 825 1090 1405 1745 2130 2300 3100 3810 135 195 270
A 65 86 115 145 175 225 280 325 375 435 520 610 20 28 37
Phone 131 773
Fax 1800 060 773
37
OZOFLEX
OZOFLEX
Selection and Ordering Data No. of Cores x Conductor Size
OZOFLEX including a green/yellow earth core
38
mm2 3G1 3G1.5 3G2.5 3G4 3G6 3G10 3G16 4G1 4G1.5 4G2.5 4G4 4G6 4G10 4G16 4G25 4G35 4G50 4G70 4G95 4G120 5G1 5G1.5 5G2.5 5G4 5G6 5G10 5G16 5G25 5G35
Sales & Order Processing
Part No.
Approx. No. of Strands x Max Strand Diameter
5DH2 303-5 5DH2 304-5 5DH2 305-5 5DH2 306-5 5DH2 307-5 5DH2 310-5 5DH2 312-5 5DH2 403-5 5DH2 404-5 5DH2 405-5 5DH2 406-5 5DH2 407-5 5DH2 410-5 5DH2 412-5 5DH2 413-5 5DH2 414-5 5DH2 415-5 5DH2 416-5 5DH2 417-5 5DH2 418-5 5DH2 503-5 5DH2 504-5 5DH2 505-5 5DH2 506-5 5DH2 907 5DH2 510-5 5DH2 939 5DH2 513-5 5DH2 514-4 Phone 131 773
mm 32 x 0.21 30 x 0.26 50 x 0.26 56 x 0.31 84 x 0.31 80 x 0.41 126 x 0.41 32 x 0.21 30 x 0.26 50 x 0.26 56 x 0.31 84 x 0.31 80 x 0.41 126 x 0.41 196 x 0.41 296 x 0.41 396 x 0.41 551 x 0.41 733 x 0.41 938 x 0.41 32 x .0.21 30 x 0.26 50 x 0.26 56 x 0.31 84 x 0.31 80 x 0.41 126 x 0.41 196 x 0.41 296 x 0.41
Fax 1800 060 773
Diameter of Bare Conductor
Cable Overall Diameter
mm 1.2 1.5 1.9 2.5 3.2 4.1 5.7 1.2 1.5 1.9 2.5 3.2 4.1 5.7 6.9 8.1 9.7 11.3 13.2 15.0 1.2 1.5 1.9 2.5 3.2 4.1 5.7 6.9 8.1
Min Max mm mm 8.6 10.5 9.6 11.0 11.5 13.0 13.0 15.0 14.5 16.5 20.0 22.5 22.5 26.5 9.8 10.2 10.5 12.5 12.5 14.0 14.5 16.5 16.5 18.0 21.5 25.0 24.5 28.9 29.5 35.0 33.0 37.5 33.0 43.5 43.0 48.5 49.0 55.0 53.0 60.0 10.5 12.5 11.5 13.5 13.5 15.8 16.0 18.8 18.0 22.0 24.0 27.0 27.0 32.5 32.5 37.0 37.5 41.5
Sales & Order Processing
Cable Weight
kg/km 130 165 235 320 495 880 1090 140 192 290 395 530 930 1300 1880 2450 3380 4450 5830 7140 180 240 345 485 760 1300 1680 2470 3306
Phone 131 773
Unenclosed Touching
A 14 19 26 35 45 62 83 14 19 26 35 45 62 83 110 135 170 215 265 305 14 19 26 35 45 62 83 110 135 Fax 1800 060 773
39
OZOFLEX
OZOFLEX Selection and Ordering Data No. of Cores x Part No. Conductor Size
Approx. No. of Strands x Max Strand Diameter
mm2 OZOFLEX Aust. Core Colours R,W,B,B,G/Y
OZOFLEX including a green/yellow earth core
40
5G2.5 5G4 5G6 5G10 5G16 5G25 5G35 7G1.5 10G1.5 12G1.5 7G2.5 8G2.5 12G2.5 18G2.5 24G2.5
Sales & Order Processing
5DH2 505-6 5DH2 506-6 5DH2 907-6 5DH2 510-6 5DH2 512-6 5DH2 513-6 5DH2 514-6 5DH2 580-5 5DH2 938-4 5DH2 583-5 5DH2 590-5 5DH2 591-5 5DH2 593-5 5DH2 595-5 5DH2 596-5
Phone 131 773
Diameter of Bare Conductor
mm
mm
50 x 0.26 56 x 0.31 84 x 0.31 80 x 0.41 126 x 0.41 196 x 0.41 296 x 0.41 30 x 0.26 30 x 0.26 30 x 0.26 50 x 0.26 50 x 0.26 50 x 0.26 50 x 0.26 50 x 0.26
1.9 2.5 3.2 4.1 5.7 6.9 8.1 1.5 1.5 1.5 1.9 1.9 1.9 1.9 1.9
Fax 1800 060 773
Cable Overall Diameter Min mm 13.5 16.0 18.0 24.0 27.0 32.5 37.5 14.0 18.5 19.2 16.5 18.0 18.5 25.0 28.5
Cable Weight
Unenclosed
Touching
Max mm
kg/km
A
15.8 18.8 22.0 27.0 32.5 37.0 41.5 17.5 20.5 20.2 20.0 21.5 26.5 31.5 35.0
345 485 760 1300 1680 2470 3306 355 610 520 505 570 755 1100 1380
26 35 45 62 83 110 135 19 19 19 19 26 26 26 26
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
41
OZOFLEX (PLUS)
OZOFLEX (PLUS)
Flexible Cables for Submersion in Polluted Liquids
MINIMUM BENDING RADII The following minimum bending radii should be observed to ensure operating reliability.
APPLICATION
-
For fixed installation 4 x cable diameter
• • • • • • • •
-
When freely flexing 5 x cable diameter
Sewage Treatment Plants Waste water pumps - effluent aerators Abattoirs (high temp chemical cleaning) Dairy industry Mining - de-watering Chemical plants & steelworks Hygenic cleaning in breweries, food processing plants etc. Water depth approx. 10m in waste water, up to 500m in all other types
DESIGN OZOFLEX (PLUS) cables consist of finely stranded copper conductors laid up to provide a flexible design. R-EP-90 elastomer insulation provides improved current capacities. Cables above 16mm2 and all control cables include an additional elastomer inner sheath and all cables up to 6mm2 have tinned conductors. The specially compounded heavy duty CSP Elastomer sheath (Hypalon) is oil resistant and flame retardant and resists the effects of water absorption. The construction is in accordance with the Australian Standards AS 1125, AS 3191, AS 3116 and DIN/VDE 282 and CENELEC STANDARDS for 07RN, IEC 60332-1.
OPERATING TEMPERATURE -
Minimum permissible ambient temperature Maximum permissible short circuit temperature Minimum ambient temperature for optimum fully flexible operation
-40°C 250°C -25°C
CURRENT CARRYING CAPACITY Current ratings are based on continuous operation at an ambient temperature of 40°C. At other temperatures these values must be converted using the following table. °C
15
20
25
30
35
40
45
50
55
60
65
70
75
80
Factor 1.26 1.20 1.15 1.10 1.05 1.00 0.94 0.88 0.81 0.73 0.65 0.57 0.47 0.34
VOLTAGE RATING -
Rated Voltage: Uo/U = 0.6/1kV Maximum operating voltages in: 3 phase AC operation Uo/U = 0.7/1.15kV DC operation Uo/U = 0.9/1.73kV - AC test voltage = 2.5kV * The cable is designated 450/750V with EI1 insulation compound in accordance with VDE/IEC and meets or exceeds the Australian Standard AS 3116 for the voltage rating of 0.6/1kV, R-EP-90.
CORE COLOUR IDENTIFICATION Single Core 3 Core 4 Core 5 Core Multi core
black blue, brown, green/yellow brown, black, green/yellow, grey blue, brown, black, green/yellow, grey black insulation sequentially numbered including a green/yellow earth core.
TENSILE STRENGTH The maximum allowable tensile stress is 15N/mm2. This ensures no conductor damage will occur in operation.
42
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
43
OZOFLEX (PLUS)
OZOFLEX (PLUS)
Selection and Ordering Data Number of Cores x Conductor Size
OZOFLEX (PLUS) Black insulation and sheath
OZOFLEX (PLUS) including a green/yellow earth
44
mm2 1 x 10 1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 3G1 3G1.5 3G2.5 3G4 3G6 3G10
Sales & Order Processing
Part No.
Approx. No. of Strands x Max. Strand Diameter
5DH1 005 5DH1 006 5DH1 007 5DH1 008 5DH1 010 5DH1 011 5DH1 012 5DH1 014 5DH1 015 5DH1 016 5DH1 017 5DH1 018 5DH1 020
Phone 131 773
mm 80 x 0.41 126 x 0.41 196 x 0.41 276 x 0.41 396 x 0.41 360 x 0.51 475 x 0.51 29 x 0.21 27 x 0.26 45 x 0.26 50 x 0.31 75 x 0.31 78 x 0.31
Fax 1800 060 773
Diameter of Bare Conductor
mm 5.0 6.3 8.0 9.7 11.0 13.0 15.2 1.5 1.8 2.6 3.2 3.9 5.1
Cable Overall Diameter
Cable Weight
Min mm 9.8 11.0 12.5 14.0 16.5 18.5 21.0 8.6 9.6 11.5 13.2 14.5 20.4
kg/km 230 320 450 605 825 1090 1405 122 154 229 319 420 780
Sales & Order Processing
Max mm 12.5 14.5 16.5 18.5 21.0 23.5 26.0 9.6 10.6 12.8 14.8 16.9 22.4
Phone 131 773
Unenclosed Touching
A 65 86 115 145 175 225 280 14 19 26 35 45 62
Fax 1800 060 773
45
OZOFLEX (PLUS)
OZOFLEX (PLUS)
Selection and Ordering Data Number of Cores x Conductor Size
OZOFLEX (PLUS) including a green/yellow earth
OZOFLEX (PLUS) with pilots
46
mm2 7G1.5 4G1.5 4G2.5 4G4 4G6 4G10 4G16 4G25 4G35 4G50 4G70 4G95 4G120 4G1.5 + 2 x 1.5 4G2.5 + 2 x 1.5 4G4 + 2 x 1.5 4G6 + 2 x 1.5 4G10 + 2 x 1.5 4G16 + 2 x 1.5 4G25 + 2 x 1.5 4G35 + 2 x 1.5
Sales & Order Processing
Part No.
Approx. No. of Strands x Max. Strand Diameter
5DH1 241 5DH1 021 5DH1 022 5DH1 023 5DH1 901-5 5DH1 025 5DH1 026 5DH1 027 5DH1 028 5DH1 030 5DH1 031 5DH1 032 5DH1 033 5DH1 069 5DH1 070 5DH1 071 5DH1 072 5DH1 073 5DH1 275 5DH1 075 5DH1 076
Phone 131 773
mm 30 x 0.26 27 x 0.26 45 x 0.26 50 x 0.31 75 x 0.31 78 x 0.41 124 x 0.41 192 x 0.41 271 x 0.41 388 x 0.41 551 x 0.41 733 x 0.41 938 x 0.41 28 x 0.26 45 x 0.26 51 x 0.31 75 x 0.31 77 x 0.26 123 x 0.41 190 x 0.41 268 x 0.41
Fax 1800 060 773
Diameter of Bare Conductor
mm 1.5 1.8 2.6 3.2 3.9 5.1 6.3 7.8 9.2 11.0 11.3 13.2 15.0 1.5 1.9 2.5 3.2 4.1 5.6 6.8 8.1
Cable Overall Diameter
Min mm 14.0 10.5 12.5 14.5 16.5 22.2 26.1 29.8 34.6 40.3 43.0 49.0 53.0 14.0 16.0 19.0 21.0 26.5 26.5 31.5 35.0
Sales & Order Processing
Max mm 17.5 12.0 14.0 16.1 18.6 24.2 29.1 33.8 37.6 43.3 48.5 55.0 60.0 16.0 18.5 21.5 23.5 30.0 30.0 35.0 38.5
Cable Weight
kg/km 355 192 279 388 530 940 1310 1890 2460 3390 4450 5830 7140 310 420 570 720 1170 1310 1910 2460
Phone 131 773
Unenclosed Touching
A 19 19 26 35 45 62 83 110 135 170 215 265 305 19 26 35 45 62 83 110 135
Fax 1800 060 773
47
OZOFLEX (PLUS) SCREENED (FC+)
OZOFLEX (PLUS) SCREENED (FC+)
Submersible Overall Screened Cable (EMC Compliant)
The construction is in accordance with the Australian Standards AS 1125, AS 3191, AS 3116 and DIN/VDE 0282 and CENELEC standards for 07RN, IEC 60 332-1.
OPERATING TEMPERATURE APPLICATION Specifically designed for pumps in water waste-water under medium mechanical stress. • • • • • • • • • •
Sewage Treatment Plants Waste water pumps, effluent aerators For pumps requiring control cores Electromagnetic compatibility (EMC) Abattoirs (high temp chemical cleaning) Dairy industry Mining - de-watering Chemical plants & steelworks Hygenic cleaning in breweries, food processing plants etc. Water depth approx. 10m in waste water, up to 500m in all other types
DESIGN OZOFLEX (PLUS) SCREENED cables consist of finely stranded copper conductors laid up to provide a flexible design. R-EP-90 elastomer insulation provides improved current capacities. All cables up to 6mm2 have tinned conductors. Between the elastomer inner and outer sheaths there is an overall tinned copper screen. The specially compounded heavy duty CSP Elastomer sheath (Hypalon) is oil resistant and flame retardant and resists the effects of water absorption.
48
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
-
Minimum permissible ambient temperature Maximum permissible short circuit temperature Minimum ambient temperature for optimum fully flexible operation
-40°C 250°C -25°C
CURRENT CARRYING CAPACITY Current ratings are based on continuous operation at an ambient temperature of 40°C. At other temperatures these values must be converted using the following table. °C 15 20 25 30 35 40 45 50 55 60 65 70 75 80 Factor 1.26 1.20 1.15 1.10 1.05 1.00 0.94 0.88 0.81 0.73 0.65 0.57 0.47 0.34
VOLTAGE RATING -
Rated Voltage: Uo/U = 0.6/1kV Maximum operating voltages in: 3 phase AC operation Uo/U = 0.7/1.15kV DC operation Uo/U = 0.9/1.73kV - AC test voltage = 2.5kV *The cable is designated 450/750V with EI1 insulation compound in accordance with VDE/IEC and meets or exceeds the Australian Standard AS 3116 for the voltage rating of 0.6/1kV, R-EP-90.
CORE COLOUR IDENTIFICATION Single Core 3 Core 4 Core Multi core
black blue, brown, green/yellow brown, black, green/yellow, grey black insulation sequentially numbered including a green/yellow earth core.
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
49
OZOFLEX (PLUS) SCREENED (FC+)
OZOFLEX (PLUS) SCREENED (FC+)
Selection and Ordering Data Number of Cores and Conductor Size strand diameter mm2 4 G 1.5 4 G 2.5 4G4 4G6 4 G 10 4 G 16 4 G 25 4 G 35 4 G 50 4 G 70 4 G 95 4 G 120
Part No.
Power conductor Approx. number of strands x max. mm 28 x 0.26 45 x 0.26 51 x 0.31 75 x 0.31 77 x 0.41 123 x 0.41 190 x 0.41 268 x 0.41 384 x 0.41 545 x 0.41 724 x 0.41 926 x 0.41
5DH5 312 5DH5 313 5DH5 314 5DH5 315 5DH5 316 5DH5 317 5DH5 318 5DH5 320 5DH5 321 5DH5 322 5DH5 323 5DH5 324
Overall diameter of cable
Net weight
Unenclosed Touching
Min
Max
1000 m approx.
mm 13.0 15.5 17.5 19.5 23.5 27.5 32.5 36.0 42.0 46.5 53.5 57.5
mm 15.0 18.0 20.0 22.0 26.0 31.0 36.0 39.5 45.5 50.0 58.0 62.0
kg 280 415 545 700 1010 1460 2100 2730 3680 4800 6280 7520
A 19 26 35 45 62 83 110 135 170 215 265 305
Ozoflex (plus) screened with pilots Number of Cores and Conductor Size strand diameter mm2 4 G 2.5 + 4 x 1.5 4 G 4 + 4 x 1.5 4 G 6 + 4 x 1.5 4 G 10 + 4 x 1.5 4 G 16 + 4 x 1.5 4 G 25 + 4 x 2.5 4 G 35 + 4 x 2.5 4 G 50 + 4 x 2.5 4 G 70 + 4 x 2.5 4 G 95 + 4 x 2.5 4 G 120 + 4 x 2.5 50
Part No.
Power conductor Approx. number of strands
Overall diameter of cable
mm 45 x 0.26 51 x 0.31 75 x 0.31 77 x 0.41 123 x 0.41 190 x 0.41 268 x 0.41 384 x 0.41 545 x 0.41 724 x 0.41 926 x 0.41
mm 21.70 24.00 26.00 26.70 28.40 34.00 36.40 42.50 48.20 56.20 61.00
5DH5 146 5DH5 147 5DH5 148 5DH5 149 5DH5 150 5DH5 152 5DH5 151 5DH5 154 5DH5 153 5DH5 155 5DH5 156
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Net weight
kg 630 905 930 1133 1363 2022 2550 3600 4800 6110 6900 Phone 131 773
Unenclosed Touching
A 26 35 45 62 83 110 135 170 215 265 305 Fax 1800 060 773
51
HYDROFIRM (T)
HYDROFIRM (T)
Flexible Cables for use Underwater and for Submersible Pumps
DESIGN HYDROFIRM (T) cables consist of finely stranded copper conductors laid up to provide a flexible design. R-EP-90 elastomer insulation enables improved current capacities and a specially compounded EPR sheath inhibits water absorption. A hand stripable bond between insulation and sheath stops any moisture migration along the insulated conductors should the sheath be damaged. HYDROFIRM (T) is suitable for water temperatures up to 60°C and is designed and approved for use in drinking water eg., mineral spring and spa pumps. For particularly aggressive liquids refer to OZOFLEX (PLUS) and PROTOMONT HD. The sheath colour is blue for identification. The cable is in accordance with the Australian Standard AS 1125, AS 3116, AS 3191 and DIN VDE 0282 pt 810.
OPERATING TEMPERATURE APPLICATION • • • • • • • • • •
Submersible pumps in boreholes, mining, irrigation dams, reticulation systems Ponds and fountains For fresh, salt & lightly polluted water (60°C) Underwater and marine installations Sub zero installations (-40°C) De-watering & drainage systems For pumps with thermistors Water Authorities Flexible marina power supplies Round version suitable for depths up to 2000mts
-
Minimum permissible ambient temperature Maximum permissible conductor temperature Maximum permissible short circuit temperature Minimum ambient temperature for optimum fully flexible operation
-40°C 90°C 250°C -25°C
MINIMUM BENDING RADII The following minimum bending radii should be observed to ensure operating reliability. For fixed installation 4 x cable diameter When freely flexing 5 x cable diameter
CURRENT CARRYING CAPACITY Current ratings are based on continuous operation at an ambient temperature of 40°C. At other temperatures these values must be converted using the following factors. For HYDROFIRM (T) the water temperature should be considered as the ambient depending on the % of cable submerged. °C 15 20 25 30 35 40 45 50 55 60 65 70 75 80 Factor 1.26 1.20 1.15 1.10 1.05 1.00 0.94 0.88 0.81 0.73 0.65 0.57 0.47 0.34
52
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
53
HYDROFIRM (T)
HYDROFIRM (T)
TENSILE STRENGTH
CORE COLOUR IDENTIFICATION
The maximum allowable tensile stress is 15N/mm2. This ensures no conductor damage will occur in operation.
Single core 3 Core 4 Core 5 Core Multi Core
VOLTAGE RATING -
Rated Voltage: Uo/U = 0.6/1kV Maximum operating voltages in: 3 phase AC operation Uo/U = 0.7/1.15kV DC operation Uo/U = 0.9/1.73kV - AC test voltage = 2.5kV *The cable is designated 450/750V in accordance with VDE/IEC and meets or exceeds the Australian Standard AS 3116 for the voltage rating 0.6/1kV
-
black blue, brown and green/yellow grey grey b l a c k i n s u l a t i o n , s e q u e n t i a l l y n u m b e re d , including a green/yellow earth core
Selection and Ordering Data No. of Cores x Conductor Size
HYDROFIRM (T) with black core insulation
54
mm2 1 x 1.5 1 x 2.5* 1 x 4* 1x6 1 x 10 1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120*
Sales & Order Processing
Part No.
5DH1 302 5DH1 602 5DH1 603 5DH1 305 5DH1 306 5DH1 307 5DH1 308 5DH1 310 5DH1 311 5DH1 312 5DH1 313 5DH1 314
Phone 131 773
Approx. No. of Strands x Max. Strand Diameter
Diameter of Bare Conductor
mm 28 x 0.26 46 x 0.26 52 x 0.31 80 x .031 77 x .041 123 x 0.41 190 x 0.41 268 x 0.41 384 x 0.41 545 x 0.41 724 x 0.41 926 x 0.41
mm 1.5 2.2 3.1 3.8 4.1 5.7 6.8 8.1 9.6 11.2 13.2 14.9
Fax 1800 060 773
Cable Overall Diameter
Min mm 5.5 6.3 7.3 7.8 9.5 11.5 13.5 15.0 17.5 20.0 22.5 24.0
Max mm 7.0 7.4 8.4 8.8 11.0 13.5 15.5 17.5 20.0 22.5 25.0 26.5
Sales & Order Processing
Cable Weight
Unenclosed
Unenclosed
Spaced
Touching
A 26 36 48 61 84 110 150 185 230 290 360 420
A 20 28 37 47 65 86 115 145 175 225 280 325
kg/km 50 62 86 120 180 265 380 500 690 920 1180 1470
Phone 131 773
Fax 1800 060 773
55
HYDROFIRM (T)
HYDROFIRM (T)
Selection and Ordering Data No. of Cores x Conductor Size
HYDROFIRM (T) including a green/yellow earth core
56
mm2 3G1.5 3G2.5 3G4 3G6 3G10 4G1.5 4G2.5 4G4 4G6 4G10 4G16 4G25 4G35 4G50 4G70 5G1.5* 5G2.5*
Sales & Order Processing
Part No.
5DH1 352 5DH1 353 5DH1 354 5DH1 644 5DH1 645 5DH1 362 5DH1 363 5DH1 364 5DH1 365 5DH1 366 5DH1 367 5DH1 368 5DH1 370 5DH1 371 5DH1 372 5DH1 731 5DH1 732
Phone 131 773
Approx. No. of Strands x Max. Strand Diameter
Diameter of Bare Conductor
mm 28 x 0.26 46 x 0.26 52 x 0.31 80 x 0.31 80 x 0.41 28 x 0.26 45 x 0.26 51 x 0.31 75 x 0.31 77 x 0.41 123 x 0.41 190 x 0.41 268 x 0.41 384 x 0.41 545 x 0.41 28 x 0.26 46 x 0.26
mm 1.7 2.2 3.1 3.8 5.0 1.5 1.9 2.5 3.2 4.1 5.6 6.8 8.1 9.6 11.2 1.7 2.2
Fax 1800 060 773
Cable Overall Diameter
Min mm 9.6 11.2 13.1 14.5 19.4 10.0 12.0 14.0 15.5 21.0 25.5 31.0 35.0 41.0 46.5 11.5 13.6
Cable Weight
Max mm 10.6 12.8 14.7 16.0 21.4 12.0 14.0 16.0 18.0 23.5 29.0 34.0 39.0 45.0 50.0 13.1 15.2
Sales & Order Processing
kg/km 140 200 285 370 655 175 250 355 475 825 1250 1800 2360 3250 4300 215 310
Phone 131 773
Unenclosed
Unenclosed
Spaced
Touching
A 20 28 38 48 66 20 28 38 48 66 88 120 145 180 230 20 28
A 19 26 35 45 62 19 26 35 45 62 83 110 135 170 215 19 26
Fax 1800 060 773
57
HYDROFIRM (T)
HYDROFIRM (T)
Selection and Ordering Data No. of Cores x Conductor Size
HYDROFIRM (T) without green/yellow earth core
mm2 3 x 1.5 3 x 2.5 3x4 3x6 3 x 10 3 x 16
Part No.
5DH1 332 5DH1 333 5DH1 334 5DH1 335 5DH1 336 5DH1 337
Approx. No. of Strands x Max. Strand Diameter
Diameter of Bare Conductor
mm 28 x 0.26 45 x 0.26 51 x 0.31 75 x 0.31 77 x 0.41 123 x 0.41
mm 1.5 1.9 2.5 3.2 4.1 5.6
Approx. No. of Strands x Max. Strand Diameter
Diameter of Bare Conductor
mm 28 x 0.26 45 x 0.26 51 x 0.31 75 x 0.31 77 x 0.41 123 x 0.41 190 x 0.41 268 x 0.41 384 x 0.41
mm 1.5 1.9 2.5 3.2 4.1 5.6 6.8 8.1 9.6
Cable Unenclosed Unenclosed Weight Spaced Touching
Cable Overall Dimensions
Min mm 9.5 11.0 13.0 14.5 19.0 23.5
Max mm 11.0 13.0 15.0 16.0 21.5 26.0
kg/km 137 197 280 370 665 1000
Selection and Ordering Data No. of Cores x Conductor Size
HYDROFIRM (T) FLAT including a green/yellow earth core
58
mm2 4 G 1.5 4 G 2.5 4G4 4G6 4 G 10 4 G 16 4 G 25 4 G 35 4 G 50
Sales & Order Processing
A 20 28 38 48 66 88
A 19 26 35 45 62 83
HYDROFIRM (T) FLAT Part No.
5DH1 522 5DH1 523 5DH1 524 5DH1 525 5DH1 526 5DH1 527 5DH1 528 5DH1 530 5DH1 531
Phone 131 773
Fax 1800 060 773
Cable Overall Width Dimensions
Cable Unenclosed Unenclosed Weight Spaced Touching
Min mm 16.0 19.0 22.5 25.5 33.0 41.0 49.0 56.5 66.5
kg/km 175 255 360 485 955 1220 1800 2400 3270
Sales & Order Processing
Max mm 18.5 21.5 25.5 29.0 36.5 44.5 53.5 60.5 69.5
Phone 131 773
A 20 28 38 48 66 88 120 145 180
A 19 26 35 45 62 83 110 135 170
Fax 1800 060 773
59
HYDROFIRM (T) SCREENED
HYDROFIRM (T) SCREENED
Flexible Cables for use Underwater and for Submersible Pumps
OPERATING TEMPERATURE -
APPLICATION • • • • • • • • •
Submersible pumps in boreholes, mining, irrigation dams, reticulation systems Ponds and fountains For fresh, salt & lightly polluted water (60°C) Underwater and marine installations Sub zero installations (-40°C) De-watering & drainage systems Pumps with thermistors Flexible marina power supplies Suitable for depths up to 500 mts
DESIGN HYDROFIRM (T) screened cables consist of finely stranded copper conductors laid up to provide a flexible design. R-EP-90 elastomer insulation enables improved current capacities and a specially compounded EPR sheath inhibits water absorption. A hand stripable bond between insulation and inner sheath stops any moisture migration along the insulated conductors should the sheath be damaged. Between the inner and outer EPR sheaths there is an overall copper screen. HYDROFIRM (T) is suitable for water temperatures up to 60°C and is designed and approved for use in drinking water eg., mineral spring and spa pumps. For particularly aggressive liquids refer to OZOFLEX (PLUS) and PROTOMONT HD. The sheath colour is blue for identification. The cable is in accordance with the Australian Standard AS 1125, AS 3116, AS 3191 and DIN VDE 0282 pt 810.
Minimum permissible ambient temperature Maximum permissible conductor temperature Maximum permissible short circuit temperature Minimum ambient temperature for optimum fully flexible operation
-40°C 90°C 250°C -25°C
MINIMUM BENDING RADII The following minimum bending radii should be observed to ensure operating reliability. For fixed installation 4 x cable diameter When freely flexing 5 x cable diameter
CURRENT CARRYING CAPACITY Current ratings are based on continuous operation at an ambient temperature of 40°C. At other temperatures these values must be converted using the following factors. For HYDROFIRM (T) the water temperature should be considered as the ambient depending on the % of cable submerged. °C 15 20 25 30 35 40 45 50 55 60 65 70 75 80 Factor 1.26 1.20 1.15 1.10 1.05 1.00 0.94 0.88 0.81 0.73 0.65 0.57 0.47 0.34
TENSILE STRENGTH The maximum allowable tensile stress is 15 N/mm2. This ensures no conductor damage will occur in operation.
VOLTAGE RATING -
-
Rated Voltage: Maximum operating voltages in: 3 phase AC operation DC operation AC test voltage
Uo/U = 0.6/1kV Uo/U = 0.7/1.2kV Uo/U = 0.9/1.8kV = 3kV
CORE COLOUR IDENTIFICATION 4 Core Pilot Core 60
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
-
brown, black, grey and green/yellow black
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
61
HYDROFIRM (T) SCREENED Selection and Ordering Data Part No.
5DH1 401 5DH1 751 5DH1 752 5DH5 634 5DH1 754 5DH1 755 5DH1 407 5DH1 408 5DH1 409 5DH1 410 5DH1 411 5DH1 412
62
Number of Power conductor Cores and Approx. Conductor Size number of strands x max. strand diameter mm2 4G1.5 4G2.5 4G4 4G6 4G10 4G16 4G25 4G35 4G50 4G70 4G95 4G120
Sales & Order Processing
mm 28 x 0.26 45 x 0.26 51 x 0.31 75 x 0.31 77 x 0.41 123 x 0.41 190 x 0.41 268 x 0.41 384 x 0.41 545 x 0.41 724 x 0.41 926 x 0.41
Phone 131 773
Diameter of Bare Conductor
Overall diameter of cable
Net weight
Unenclosed Unenclosed Spaced Touching
1000 m approx mm 1.5 1.9 2.5 3.2 4.1 5.6 6.8 8.1 9.6 11.2 13.2 14.9
Fax 1800 060 773
Min mm 13.0 15.5 17.5 19.5 23.5 27.5 32.5 36.0 42.0 46.5 53.5 57.5
Max mm 15.0 18.0 20.0 22.0 26.0 31.0 36.0 39.5 45.5 50.0 58.0 62.0
Sales & Order Processing
kg 260 396 525 665 970 1400 2030 2610 3610 4710 6340 7470
Phone 131 773
A 20 28 38 48 66 88 120 145 180 230 285 330
A 19 26 35 45 62 83 110 135 170 215 265 305
Fax 1800 060 773
63
PROTOMONT HD
PROTOMONT HD
Heavy Duty Flexible for Aggressive Environments
OPERATING TEMPERATURE -
Minimum permissible ambient temperature Maximum permissible conductor temperature Maximum permissible short circuit temperature Minimum ambient temperature for optimum fully flexible operation
-40°C 90°C 250°C -25°C
MINIMUM BENDING RADII The following minimum bending radii should be observed to ensure operating reliability. For fixed installation 4 x cable diameter When freely flexing 5 x cable diameter
APPPLICATION • • • • • • • •
Extra Heavy Duty flexible Stackers & reclaimer cabling Draglines, shovels & hoists Conveyors Open cut mine trailing cable Heavy industry & construction sites Submersion in polluted liquids Single core for festoon cranes
CURRENT CARRYING CAPACITY Current ratings are based on a continuous operating ambient temperature of 40°C. At other temperatures, these values must be converted using the following table °C 15 20 25 30 35 40 45 50 55 60 65 70 75 80 Factor 1.26 1.20 1.15 1.10 1.05 1.00 0.94 0.88 0.81 0.73 0.65 0.57 0.47 0.34
TENSILE STRENGTH
DESIGN PROTOMONT HD heavy duty elastomer flexible cables are designed for aggressive environments in open cut mining and quarries, industry and construction sites as well as agricultural use where heavy mechanical stresses occur.
The maximum allowable tensile stress is 15 N/mm2. This ensures no conductor damage will occur in operation.
PROTOMONT HD cables consist of finely stranded tinned copper conductors laid up to provide a flexible design. R-EP-90 elastomer insulation enables improved current capacities and a specially compounded XHD-PCP-90 outer sheath resists hard and abrasive surfaces. The cable is in accordance with the Australian Standard AS 1125, AS 3116, AS 3191 and DIN VDE 0250 pt 812 for NSSHoeu. Flame retardant to VDE and MSHA.
64
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
65
PROTOMONT HD
PROTOMONT HD
VOLTAGE RATING -
-
CORE COLOUR IDENTIFICATION
Rated Voltage: Uo/U Maximum operating voltages in: 3 phase AC operation Uo/U DC operation Uo/U AC test voltage
= 0.6/1kV = 0.7/1.2kV = 0.9/1.8kV = 3kV
Single core: 3 Core 4 Core 5 Core Multicore: -
black blue, brown and green/yellow blue, brown, black and green/yellow blue, brown, black, green/yellow and black black insulation sequentially numbered including a green/yellow earth core
Selection and Ordering Data No. of Cores x Conductor Size
PROTOMONT with black core insulation
PROTOMONT including green/ yellow earth core
66
mm2 1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 1 x 240 1 x 300 3 x 1.5* 3 x 2.5* 3 x 4* 3 x 6*
Sales & Order Processing
Part No.
5DL1 112 5DL1 113 5DL1 114 5DL1 115 5DL1 116 5DL1 117 5DL1 118 5DL1 120 5DL1 121 5DL1 122 5DL1 123 5DL1 304 5DL1 305 5DL1 306 5DL1 307
Phone 131 773
Approx. No. of Strands x Max. Strand
Diameter of Bare Conductor
Cable Overall Diameter
mm 122 x 0.41 188 x 0.41 265 x 0.41 379 x 0.41 539 x 0.41 716 x 0.41 915 x 0.41 1138 x 0.41 1390 x 0.41 1844 x 0.41 2301 x 0.41 28 x 0.26 45 x 0.26 50 x 0.31 75 x 0.31
mm 6.3 7.8 9.2 11.0 13.0 15.1 17.0 19.0 21.0 24.0 27.0 1.8 2.6 3.2 3.9
Min Max mm mm 10.5 12.5 13.0 15.0 14.5 16.5 16.0 18.5 18.0 20.5 21.0 23.5 22.5 25.5 24.5 27.5 27.5 31.0 31.0 34.5 34.5 38.0 11.5 13.5 12.5 15.0 15.5 18.0 17.0 19.5
Fax 1800 060 773
Sales & Order Processing
Cable Weight
kg/km 255 283 493 670 900 1140 1430 1740 2150 2760 3480 210 273 408 510
Phone 131 773
Unenclosed Spaced Touching
A 110 150 185 230 290 360 420 485 570 680 790 20 28 38 48
A 86 115 145 175 225 280 325 375 435 520 610 19 26 35 45
Fax 1800 060 773
67
PROTOMONT HD
PROTOMONT HD
Selection and Ordering Data No. of Cores x Conductor Size
PROTOMONT including green/ yellow earth core
mm2 4 x 1.5* 4 x 2.5* 4 x 4* 4 x 6* 4 x 10* 4 x 16* 4 x 25* 4 x 35* 4 x 50* 3 x 70/35* 3 x 95/50* 3 x 120/95* 5 x 1.5 5 x 2.5 5x4 5x6 5 x 10 5 x 16 5 x 25 6 x 1.5* 7 x 1.5* 8 x 1.5* 10 x 1.5* 11 x 1.5* 7 x 2.5 10 x 2.5* 12 x 2.5 12 x 2.5* 18 x 2.5
Part No.
5DL1 404 5DL1 405 5DL1 406 5DL1 407 5DL1 410 5DL1 412 5DL1 413 5DL1 414 5DL1 415 5DL1 716 5DL1 717 5DL1 718 5DL1 504 5DL1 505 5DL1 506 5DL1 507 5DL1 510 5DL1 512 5DL1 513 5DL1 945 5DL1 933 5DL1 931 5DL1 878 5DL1 903 5DL1 911 5DL1 748 5DL1 755 5DL1 923 5DL1 937
Approx. No. of Strands x Max. Strand Diameter
Diameter of Bare Conductor
mm 28 x 0.26 45 x 0.26 50 x 0.31 75 x 0.31 77 x 0.41 122 x 0.41 190 x 0.41 267 x 0.41 383 x 0.41 544 x 0.41 722 x 0.41 925 x 0.41 28 x 0.26 45 x 0.26 50 x 0.31 75 x 0.31 77 x 0.41 122 x 0.41 190 x 0.41 28 x 0.26 28 x 0.26 28 x 0.26 28 x 0.26 28 x 0.26 45 x 0.26 45 x 0.26 45 x 0.26 45 x 0.26 45 x 0.26
mm 1.8 2.6 3.2 3.9 5.1 6.3 7.8 9.2 11.0 13.1 15.1 17.0 1.8 2.6 3.2 3.9 5.1 6.3 7.8 1.8 1.8 1.8 1.8 1.8 2.6 2.6 2.6 2.6 2.6
Cable Overall Diameter
Cable Weight
Current Carrying free in air
Min mm 12.0 14.5 16.5 18.0 22.0 26.5 31.5 34.5 40.5 44.5 51.5 57.5 13.0 16.0 18.0 20.0 24.0 29.0 34.5 14.0 16.0 17.3 18.5 19.3 18.0 21.6 22.5 22.5 26.0
kg/km 239 364 477 600 920 1370 2010 2530 3520 4280 5710 7010 266 403 540 720 1050 1580 2320 315 416 462 540 580 530 760 800 830 1140
A 20 28 38 48 66 88 120 145 180 230 285 330 20 28 38 48 66 88 120 20 20 20 20 20 28 28 28 28 28
Max mm 14.0 17.0 19.0 20.5 25.0 30.0 35.5 38.5 45.0 49.0 57.0 63.5 15.0 18.0 20.5 23.0 27.0 32.5 38.5 15.0 18.5 19.1 21.0 20.7 21.0 23.6 25.0 25.0 30.0
Capacity direct installed
A 19 26 35 45 62 83 110 135 170 215 265 305 19 26 35 45 62 83 110 19 19 19 19 19 26 26 26 26 26
*This construction can be used for submersion in aggressive liquids
68
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
69
PROTOMONT SCREENED
PROTOMONT SCREENED
Heavy Duty/Extra Heavy Duty Flexible Cables
CURRENT CARRYING CAPACITY Current ratings are based on continuous operation at an ambient temperature of 40°C. At other temperatures these values must be converted using the following table. °C 15 20 25 30 35 40 45 50 55 60 65 70 75 80 Factor 1.26 1.20 1.15 1.10 1.05 1.00 0.94 0.88 0.81 0.73 0.65 0.57 0.47 0.34
APPLICATION •
Flexible pump cable
VOLTAGE RATING
• • •
Heavy duty construction site leads Oil rigs Generator supply cables
-
DESIGN PROTOMONT heavy duty elastomer flexible cables are designed for aggressive environments in open cut mining and quarries, industry and construction sites as well as agricultural use where heavy mechanical stresses occur. PROTOMONT cables consist of finely stranded tinned copper conductors laid up to provide a flexible design. Between the elastomer inner and outer sheaths there is an overall tinned copper screen. R-EP-90 elastomer insulation enables improved current carrying capacities and a specially compounded XHD-PCP-90 outer sheath resists hard and abrasive surfaces. The cable is in accordance with the Australian Standard AS 1125, AS 3116, AS 3191 and DIN VDE 0250 pt 812 for NSSHoeu. Flame retardant to VDE and MSHA.
70
Minimum permissible ambient temperature Maximum permissible conductor temperature Maximum permissible short circuit temperature Minimum ambient temperature for optimum fully flexible operation
Sales & Order Processing
Phone 131 773
MINIMUM BENDING RADII The following minimum bending radii should be observed to ensure operating reliability. For fixed installation 4 x cable diameter When freely flexing 5 x cable diameter Note: For force guided and reeling applications please refer to Siemens CORDAFLEX (K) information.
TENSILE STRENGTH
OPERATING TEMPERATURE -
Rated Voltage: Uo/U = 0.6/kV Maximum operating voltages in: 3 phase AC operation Uo/U = 0.7/1.15kV DC operation Uo/U = 0.9/1.73kV - AC test voltage = 2.5kV * The cable is designated 450/750V in accordance with VDE/IEC and meets or exceeds the Australian Standard AS 3116 for the voltage rating of 0.6/1kV.
-40°C 90°C 250°C -25°C
Fax 1800 060 773
The maximum allowable tensile stress is 15N/mm2. This ensures no conductor damage will occur in operation.
CORE COLOUR IDENTIFICATION 4 Core 5 Core
blue, brown, black, green/yellow red, white, blue, black, green/yellow
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
71
PROTOMONT SCREENED
PROTOMONT SCREENED
Selection and Ordering Data 5 CORE OVERALL PROTOMONT SCREENED (F) Number of Cores x Conductor Size
PROTOMONT Screened
mm2 5 x 2.5/2.5 5 x 4/4 5 x 6/6 5 x 10/10 5 x 16/16
Part No.
Approx. No. of Strands x Max. Strand Diameter mm 50 x 0.26 56 x 0.31 84 x 0.31 84 x 0.41 126 x 0.41
5DL2 710 5DL2 711 5DL2 712 5DL2 713 5DL2 714
Diameter of Cable Overall Bare Diameter Conductor Max. mm mm 2.6 15.8 3.2 18.8 3.9 20.4 5.1 24.6 6.3 30.0
Cable Weight
Unenclosed Touching
kg/km 540 680 910 1320 1955
A 26 35 45 62 83
Diameter of Cable Overall Bare Diameter Conductor Max. mm mm 1.8 15.4 2.6 18.4 3.2 20.5 3.9 23.1 5.1 27.2 6.3 32.4 8.0 39.1
Cable Weight
Unenclosed Touching
kg/km 375 540 680 910 1320 1955 2675
A 19 26 35 45 62 83 110
5 CORE OVERALL PROTOMONT SCREENED Number of Cores x Conductor Size
PROTOMONT Screened
72
mm2 5 x 1.5/1.5 5 x 2.5/2.5 5 x 4/4 5 x 6/6 5 x 10/10 5 x 16/16 5 X 25/25
Sales & Order Processing
Part No.
5DL2 808 5DL2 810 5DL2 811 5DL2 812 5DL2 813 5DL2 814 5DL2 815
Phone 131 773
Approx. No. of Strands x Max. Strand Diameter mm 30 x 0.26 50 x 0.26 56 x 0.31 84 x 0.31 80 x 0.41 126 x 0.41 196 x 0.41
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
73
SINOTHERM
SINOTHERM
High Temperature 180°C Silicone Flexible Cables
MINIMUM BENDING RADII The following minimum bending radii must be observed to ensure operating reliability.
APPLICATION
These are applicable for both sub-zero and elevated temperatures.
• • • • • • • • •
-
Fixed Installation 4 x cable diameter
-
When freely flexing 5 x cable diameter
Switchboard & cubical wiring Transformer and Capacitor cabling High output floodlights Chemical & ceramic industry Injection moulding & extruders Steelworks/ hot strip rolling mills Foundries & cooking plants Heating appliances Motor rewinders
CURRENT CARRYING CAPACITY Current ratings are based on continous operation at an ambient temperature of 150°C per the following table when installed unenclosed and touching. Conductor Size Amps
DESIGN SINOTHERM cables consist of fine stranded copper conductors laid up to provide a flexible design. Silicone insulation offers high resistance to increased ambient temperatures, however with a low mechanical resistance to cuts and tearing.
OPERATING TEMPERATURE -
Minimum and maximum permissible ambient temperature Maximum permissible conductor temperature Maximum permissible short circuit temperature Minimum ambient temperature for optimum fully flexible operation
-55°C +180°C 180°C 350°C -40°C
RESISTANCE TO CHEMICALS Occasional slight exposure to oil and grease is permitted but the cables must not lie continually in oil or grease. They must be protected against fuels and solvents by suitable insulation. In accordance with AS 3178 the single core 0.6/1kV SINOTHERM carries the SECV Approval No.89516V. 74
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
0.75 15
1.0 19
1.5 24
2.5 32
4 42
6 54
10 73
16 98
25 35 50 70 95 129 158 198 245 292
At other temperatures these values must be converted using the following table. Ambient temp. up to °C Current capacity as a % of values above
150 155 100 91
160 165 170 82 71 58
175 180 41 23
Current ratings are based on continous operation at an ambient temperature of 40°C per the following table when installed unenclosed and touching. Conductor Size Amps
0.75 18
1.0 21
1.5 27
2.5 38
4 51
6 65
10 92
16 25 35 50 70 95 123 163 202 294 364 433
At other temperatures these values must be converted using the following table. °C Factor
40 1.0
45 50 55 60 65 70 75 0.98 0.95 0.93 0.90 0.88 0.85 0.83
VOLTAGE RATING -
Rated Voltage: Single Core
Uo/U
= 0.6/1kV
-
Multi Core & Glass Braided
Uo/U
= 300/500V
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
75
SINOTHERM
SINGLE CORE INSULATED SINOTHERM 0.6/1kV
CORE COLOUR IDENTIFICATION 2 Core 3 Core 4 Core 5 Core
-
blue, brown blue, brown, green/yellow blue, brown, black, green/yellow blue, brown, black, green/yellow, black
A single core 660V is available in a range of colours for control wiring in black, red, pink, green/yellow, blue, orange, brown, white and grey. Coloured Sinotherm Conductors tinned to AS 1125.
Selection and Ordering Data No. of Cores x Conductor Size
Part No.
mm2
76
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Approx. No. of Strands x Max. Strand Diameter
Diameter of Bare Conductor
Cable Overall Diameter
Cable Weight
mm
mm
Min mm
Max mm
kg/km
1 x 1.5
5DR3 514
30 x 0.26
1.8
2.9
3.9
20
1 x 2.5
5DR3 515
50 x 0.26
2.6
3.5
4.6
30
1x4
5DR3 516
56 x 0.31
3.2
4.2
5.2
50
1x6
5DR3 517
84 x 0.31
3.9
4.8
6.7
65
1 x 10
5DR3 518
80 x 0.41
5.1
6.2
8.0
115
1 x 16
5DR3 520
126 x 0.41
6.3
7.2
9.3
180
1 x 25
5DR3 521
196 x 0.41
7.8
8.7
11.4
275
1 x 35
5DR3 522
276 x 0.41
9.2
10.0
13.4
365
1 x 50
5DR3 523
396 x 0.41
11.0
11.8
15.4
520
1 x 70
5DR3 524
360 x 0.51
13.1
13.5
17.9
710
1 x 95
5DR3 525
475 x 0.51
15.1
15.4
20.0
930
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
77
SINGLE CORE SINOTHERM WITH GLASS FIBRE BRAID (500V)
MULTICORE SINOTHERM FLEXIBLE CABLES (500V)
Selection and Ordering Data No. of Cores x Conductor Size
Part No.
mm2
Selection and Ordering Data
Approx. No. of Strands x Max. Strand Diameter
Diameter of Bare Conductor
Cable Overall Diameter
mm
mm
Min mm
Max mm
Cable Weight
No. of Cores x Conductor Size
kg/km
mm2
Part No.
Approx. No. of Strands x Max. Strand Diameter
Diameter of Bare Conductor
Cable Overall Diameter
mm
mm
Min mm
Max mm
Cable Weight
kg/km
1 x 0.75
5DR4 021-5
24 x 0.21
1.2
2.6
3.6
17
2 x 0.75
5DR5 228-4
24 x 0.21
1.2
6.0
7.2
52
1x1
5DR4 031-5
32 x 0.21
1.4
2.7
3.8
20
2x1
5DR5 238-4
32 x 0.21
1.4
6.4
7.8
59
27
2 x 1.5
5DR5 248-4
30 x 0.26
1.7
7.6
9.0
81
5DR5 258-4
50 x 0.26
2.2
9.0
10.5
125
1 x 1.5
5DR4 041-5
30 x 0.26
1.7
3.2
4.3
1 x 2.5
5DR4 051-5
50 x 0.26
2.2
3.8
5.0
39
2 x 2.5
1x4
5DR4 061-5
56 x 0.31
3.1
4.3
5.6
54
2x4
5DR5 268-4
56 x 0.31
3.1
10.0
12.0
180
1x6
5DR4 071-5
84 x 0.31
3.8
4.8
6.2
75
3 x 0.75
5DR5 328-4
24 x 0.21
1.2
6.6
7.8
62
1 x 10
5DR4 101-5
80 x 0.41
5.0
6.0
8.2
130
3x1
5DR5 338-4
32 x 0.21
1.4
6.8
8.2
77
1 x 16
5DR4 121-5
126 x 0.41
6.3
8.1
9.6
200
3 x 1.5
5DR5 348-4
30 x 0.26
1.7
8.0
9.6
98
1 x 25
5DR4 131-4
196 x 0.41
8.0
9.7 12.0
305
3 x 2.5
5DR5 358-4
50 x 0.26
2.2
9.6
11.5
150
1 x 35
5DR4 141-4
276 x 0.41
9.2
11.6 13.0
420
3 x 4*
5DR5 368-4
56 x 0.31
3.1
11.0
13.0
225
1 x 50
5DR4 151-4
396 x 0.41
11.0
13.5 16.0
595
4 x 0.75
5DR5 428-4
24 x 0.21
1.2
7.2
8.4
80
1 x 70
5DR4 161-4
360 x 0.51
13.9
15.6 18.0
825
4 x 1*
5DR5 438-4
32 x 0.21
1.4
7.6
8.8
94
1 x 95*
5DR4 171-4
475 x 0.51
15.2
17.7
4 x 1.5
5DR5 448-4
30 x 0.26
1.7
9.0
10.5
125
4 x 2.5
5DR5 458-4
50 x 0.26
2.2
10.5
12.5
185
4x4
5DR5 468-4
56 x 0.31
3.1
12.0
14.0
290
5 x 1.5
5DR5 548-4
30 x 0.26
1.7
9.8
11.5
155
7 x 1.5
5DR5 793-4
30 x 0.26
1.7
10.2
12.9
195
12 x 1.5*
5DR5 794-4
30 x 0.26
1.7
13.5
15.5
315
78
Sales & Order Processing
Phone 131 773
21.0
1075
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
79
EVA 125 FLEX
EVA 125 FLEX
High Temperature 125°C Flame Retardant Halogen Free Flexible Cables
MINIMUM BENDING RADII
APPLICATION
-
For fixed installation 4 x cable diameter
-
When freely flexing 5 x cable diameter
• • • • •
The following minimum recommended bending radii should be observed to ensure operating reliability.
Switchboard cabling Coil & transformer wiring High thermal stress resistant Chemical & ceramic industry Steelworks
CURRENT CARRYING CAPACITY Current ratings are based on a continuous operating ambient temperature of 40 °C. At other temperatures these values must be converted using the following table.
DESIGN EVA 125 is a flexible elastomer insulated cable with improved thermal characteristics due to special cross linking together with an excellent resistance to oils, chemicals, abrasion and mechanical damage. EVA 125 Flex cables consist of finely stranded tinned copper conductors laid up to provide a flexible design with a specially compounded R-EVA125 synthetic rubber insulation for operation in elevated ambient temperatures. The cable is in accordance with the Australian Standards AS 1125, AS 3116 and DIN VDE 0282 pt 501 for H07G The special Ethylene Vinyl Acetate compound is halogen free and exhibits low smoke generation in the event of fire and has a high resistance to absorption of oils and grease.
TEMPERATURE -
Minimum and maximum permissible ambient temperature +110 °C Maximum permissible conductor temperature Maximum permissible short circuit temperature
80
Sales & Order Processing
Phone 131 773
-40 °C to 125°C 250 °C
Fax 1800 060 773
°C 15 20 25 30 35 40 45 50 55 60 65 70 75 80 Factor 1.26 1.20 1.15 1.10 1.05 1.00 0.94 0.88 0.81 0.73 0.65 0.57 0.47 0.34
TENSILE STRENGTH The maximum allowable tensile stress on the conductors is 15N/mm2. This ensures no conductor damage will occur in operation.
VOLTAGE RATING -
Rated Voltage: Uo/U = 0.6/1kV Maximum operating voltages in: 3 phase AC operation Uo/U = 0.7/1.15kV DC operation Uo/U = 0.9/1.73kV - AC test voltage = 2.5kV The cable is designated 450/750V in accordance with VDE/IEC and meets or exceeds the Australian Standard AS3116 for the voltage rating 0.6/1kV
CORE COLOUR IDENTIFICATION The cable is available in either black or orange as standard. Variations are available subject to manufacture length.
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
81
EVA 125 FLEX
EVA 125 FLEX
Selection and Ordering Data No. of Cores x Conductor Size
mm2 1 x 0.75 1x1 1 x 1.5 1 x 2.5 1x4 1x6 1 x 10 1 x 16 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95
82
Insulation Colour
black black black black black black black black black black black black black
Sales & Order Processing
Part No.
5DR7 051-5 5DR7 052-5 5DR7 053-5 5DR7 054-5 5DR7 055-5 5DR7 056-5 5DR7 057-5 5DR7 060-5 5DR7 061-5 5DR7 062-5 5DR7 063-5 5DR7 064-5 5DR7 065-5
Phone 131 773
Approx. No. Strands x Max. Strand Diameter
Diameter of Bare Conductor (Max.)
mm 24 x 0.21 32 x 0.21 30 x 0.26 50 x 0.26 56 x 0.31 84 x 0.31 80 x 0.41 126 x 0.41 196 x 0.41 276 x 0.41 396 x 0.41 360 x 13.9 475 x 0.51
mm 1.3 1.5 1.8 2.6 3.2 3.9 5.1 6.3 7.8 9.2 11.0 13.9 15.1
Fax 1800 060 773
Cable Overall Diameter
Min mm 2.5 2.6 2.9 3.5 4.2 4.8 6.0 7.2 8.7 10.0 11.8 15.6 16.5
Sales & Order Processing
Cable Weight
Unenclosed Touching
kg/km 15 20 25 40 60 80 130 210 320 420 595 850 985
A 18 20 25 35 47 59 81 105 145 175 215 271 340
Max mm 3.2 3.4 3.7 4.4 5.5 6.3 7.9 9.0 11.0 12.4 15.4 18.0 19.1
Phone 131 773
Fax 1800 060 773
83
EVA 125 FLEX
EVA 125 FLEX
High Temperature Multicore Flexible Cables
Selection and Ordering Data No. of Cores x Conductor Size
84
Part No.
mm2 3 x 0.75 5 x 0.75 7 x 0.75
5DR7 646 5DR7 648 5DR7 650
3 x 1.5 4 x 1.5 5 x 1.5 7 x 1.5 5 x 2.5
5DR7 644 5DR7 642 5DR7 645 5DR7 643 5DR7 651
Sales & Order Processing
Approx. No. Strands x Max.
Diameter of Bare Conductor Strand Diameter
Cable Overall Diameter
Cable Weight
Current Carrying Capacity
max.
Min
Max
mm 24 x 0.21
mm 1.3
mm 6.9 9.1 9.6
mm 8.6 11.0 12.0
kg/km 80 135 175
A 11 11 11
30 x 0.26
1.8
50 x 0.26
2.6
8.2 9.3 9.9 10.6 11.6
10.0 11.0 12.0 13.5 14.5
120 140 185 220 250
16 16 16 16 24
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
85
PROTOFLEX Ö500
PROTOFLEX Ö500 PVC Control Cables
SPECIAL FEATURES
APPLICATION PROTOFLEX® Ö500/Ö500CY PVC control cables are specially suitable for use as flexible control cables. Applications include machine tools, production and processing machines, machining centres. industrial robots, transfer lines and handling systems in industries manufac turing pumps, fans, conveyors and air- conditioning systems, as well as the fo o d - p ro c e s s in g , tex t il e m a c hi n e, p a p e r s te e l m a k i n g a n d metal-working industries.
Suitable for use Burning behavior in accordance with DIN in hazardous areas VDE 0472 Part 804, Test B (IEC 332-1) Low transfer impedance The cable has a concentric copper braided shield to avoid electromagnetic interference (max 250 Ω /km at 30 MHz). Voltages 300/500 V Rated voltage 318/550 V HIghest permissible operating voltage - 3 phase and single phase operation - in DC operation 2 kV Test voltage Certification VDE Reg. No. 7042 Standards Based on DIN VDE 0281-13
DESIGN PROTOFLEX® Ö500 PVC control cables consist of finely stranded copper conductors with V75 PVC insulation. The high grade PVC sheath is resistant to oil, grease and chemicals. PROTOFLEX® Ö500CY PVC screened control cables have a PVC inner and outer sheath with a copper braided shield between the sheaths which serves to avoid electromagnetic interference (EMC) in building systems and were equipment is in environments where Electromagnetic interference would be unacceptable. Designed for moderate mechanical loading, in dry, damp and wet areas and in hazardous areas. Outdoor use is possible, provided that the cables are protected from direct sunlight and are permanently installed.
86
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
87
PROTOFLEX Ö500
PROTOFLEX Ö500
SHIELD CONNECTION
PERMISSIBLE TEMPERATURE
In order to obtain optimum shielding quality, the shield must be connected around its entire circumference and over an ample surface area at both ends of the cable.
At conductor:
Twisting the shielding strands together into a pigtail or exclusive use of a sheath wire is not sufficient.
d= outer diameter of cable
The current carrying capacities are based on a continuous operating
Cable construction is based on DIN VDE 0281-13
• • • •
+5oC to + 70 oC - 40 oC to + 70 oC 4d 7.5 d
CURRENT CARRYING CAPACITY
TECHNICAL INFORMATION •
Bending radii:
free-flexing fixed fixed free-flexing
Finely-stranded bare copper conductors according to VDE 0295 Class 5 Insulation of special polyvinyl chloride (PVC) PVC inner sheath over laid-up cores in shielded versions Braided shield of tinned copper wires over inner sheath Grey PVC outer sheath, largely resistant to oil and chemicals
Marking stamped or printed onto the outer sheath. PROTOFLEX - Ö500 SYSLY 300/500 V VDE-Reg.-Nr. 7042 PROTOFLEX - Ö500CY SYSLYCY 300/500 V VDE-Reg.-Nr. 7042
CONTINUOUS TENSILE LOAD The maximum allowable tensile stress for operation of cables with mobile equipment is 15 N per mm2.
temperature of 40 °C. At other temperatures these values must be converted using the following factors °C 15 20 25 30 35 40 45 50 55 60 65 70 75 80 Factor 1.26 1.20 1.15 1.10 1.05 1.00 0.94 0.88 0.81 0.73 0.65 0.57 0.47 0.34
VOLTAGE RATINGS - Rated Voltage: Uo/U = 300/500V - AC test voltage = 2kV *The cable is designated 300/500V in accordance with VDE/IEC and meets the Australian standard for the stated voltage rating AS 1125, AS 3147.
CORE COLOUR IDENTIFICATION All control cores are black, sequentially numbered and include a green/ yellow earth core.
The maximum allowable tensile stress is 50 N mm 2 for fixed installations.
88
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
89
PROTOFLEX Ö500
PROTOFLEX Ö500
PVC Control cables, unscreened Selection and Ordering Data No. of Cores x Conductor Cross-section mm2 2 x 0.5 3 x 0.5 4 x 0.5 5 x 0.5 7 x 0.5 12 x 0.5 18 x 0.5 25 x 0.5 32 x 0.5 40 x 0.5 52 x 0.5
90
Part No.
5DE7 026 5DE7 001 5DE7 002 5DE7 003 5DE7 004 5DE7 005 5DE7 010 5DE7 012 5DE7 014 5DE7 016 5DE7 027
Sales & Order Processing
PVC Control cables, unscreened Selection and Ordering Data
Approx. No. of Strands x Max. Strand Diameter
Cable Overall Diameter
Unenclosed Touching
mm 16 x 0.21 16 x 0.21 16 x 0.21 16 x 0.21 16 x 0.21 16 x 0.21 16 x 0.21 16 x 0.21 16 x 0.21 16 x 0.21 16 x 0.21
mm 4.8 5.1 5.6 6.2 6.8 9.2 10.8 13.1 14.2 16.1 17.7
A 8 8 8 8 8 8 8 8 8 8 8
Phone 131 773
Fax 1800 060 773
No. of Cores x Conductor Cross-section mm2 2 x 0.75 3 x 0.75 4 x 0.75 5 x 0.75 7 x 0.75 12 x 0.75 18 x 0.75 25 x 0.75 34 x 0.75 42 x 0.75 50 x 0.75
Part No.
5DE7 040 5DE7 041 5DE7 042 5DE7 043 5DE7 044 5DE7 045 5DE7 050 5DE7 052 5DE7 055 5DE7 057 5DE7 058
Sales & Order Processing
Approx. No. of Strands x Max. Strand Diameter
Cable Overall Diameter
Unenclosed Touching
mm 24 x 0.21 24 x 0.21 24 x 0.21 24 x 0.21 24 x 0.21 24 x 0.21 24 x 0.21 24 x 0.21 24 x 0.21 24 x 0.21 24 x 0.21
mm 5.2 5.6 6.2 6.8 7.5 10.0 12.0 14.5 16.5 17.9 19.6
A 10 10 10 10 10 10 10 10 10 10 10
Phone 131 773
Fax 1800 060 773
91
PROTOFLEX Ö500
PROTOFLEX Ö500
PVC Control cables, unscreened Selection and Ordering Data No. of Cores x Conductor Cross-section mm2 2 x 1.0 3 x 1.0 4 x 1.0 5 x 1.0 7 x 1.0 12 x 1.0 18 x 1.0 25 x 1.0 34 x 1.0 41 x 1.0 50 x 1.0
92
Part No.
5DE7 080 5DE7 081 5DE7 082 5DE7 083 5DE7 084 5DE7 085 5DE7 090 5DE7 093 5DE7 096 5DE7 098 5DE7 102
Sales & Order Processing
PVC Control cables, unscreened Selection and Ordering Data
Approx. No. of Strands x Max. Strand Diameter
Cable Overall Diameter
Unenclosed Touching
mm 32 x 0.21 32 x 0.21 32 x 0.21 32 x 0.21 32 x 0.21 32 x 0.21 32 x 0.21 32 x 0.21 32 x 0.21 32 x 0.21 32 x 0.21
mm 5.7 6.1 6.7 7.4 8.3 10.9 13.1 15.9 18.1 19.6 21.5
A 13 13 13 13 13 13 13 13 13 13 13
Phone 131 773
Fax 1800 060 773
No. of Cores x Conductor Cross-section mm2 2 x 1.5 3 x 1.5 4 x 1.5 5 x 1.5 7 x 1.5 12 x 1.5 18 x 1.5 25 x 1.5 34 x 1.5 42 x 1.5 50 x 1.5
Part No.
5DE7 120 5DE7 121 5DE7 122 5DE7 123 5DE7 124 5DE7 125 5DE7 128 5DE7 133 5DE7 135 5DE7 136 5DE7 137
Sales & Order Processing
Approx. No. of Strands x Max. Strand Diameter
Cable Overall Diameter
Unenclosed Touching
mm 28 x 0.26 28 x 0.26 28 x 0.26 28 x 0.26 28 x 0.26 28 x 0.26 28 x 0.26 28 x 0.26 28 x 0.26 28 x 0.26 28 x 0.26
mm 6.3 6.7 7.4 8.3 9.1 12.1 14.5 17.7 19.9 21.6 23.8
A 16 16 16 16 16 16 16 16 16 16 16
Phone 131 773
Fax 1800 060 773
93
PROTOFLEX Ö500
PROTOFLEX Ö500
PVC Control cables, unscreened Selection and Ordering Data No. of Cores x Conductor Cross-section mm2 2 x 2.5 3 x 2.5
94
Part No.
5DE7 160 5DE7 161
PVC Control cables, screened Selection and Ordering Data
Approx. No. of Strands x Max. Strand Diameter
Cable Overall Diameter
Unenclosed Touching
mm 48 x 0.26 48 x 0.26
mm 7.7 8.3
A 23 23
mm2 2 x 0.5 3 x 0.5
No. of Cores x Conductor Cross-section
Part No.
Approx. No. of Strands x Max. Strand Diameter
Cable Overall Diameter
Unenclosed Touching
5DE7 626 5DE7 601
mm 16 x 0.21 16 x 0.21
mm 6.8 7.0
A 8 8
4 x 2.5
5DE7 162
48 x 0.26
9.2
23
4 x 0.5
5DE7 602
16 x 0.21
7.5
8
5 x 2.5
5DE7 163
48 x 0.26
10.1
23
5 x 0.5
5DE7 603
16 x 0.21
8.2
8
7 x 2.5
5DE7 164
48 x 0.26
11.2
23
7 x 0.5
5DE7 604
16 x 0.21
8.7
8
12 x 2.5
5DE7 165
48 x 0.26
15.2
23
12 x 0.5
5DE7 605
16 x 0.21
10.9
8
18 x 2.5
5DE7 170
48 x 0.26
18.1
23
18 x 0.5
5DE7 610
16 x 0.21
12.8
8
25 x 2.5
5DE7 172
48 x 0.26
22.1
23
25 x 0.5
5DE7 612
16 x 0.21
15.4
8
34 x 2.5
5DE7 175
48 x 0.26
25.0
23
32 x 0.5
5DE7 614
16 x 0.21
16.7
8
50 x 2.5
5DE7 178
48 x 0.26
30.0
23
40 x 0.5
5DE7 616
16 x 0.21
18.3
8
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
95
PROTOFLEX Ö500
PROTOFLEX Ö500
PVC Control cables, screened
PVC Control cables, screened Selection and Ordering Data No. of Cores x Conductor Cross-section mm2 2 x 0.75 3 x 0.75 4 x 0.75 5 x 0.75 7 x 0.75 12 x 0.75 18 x 0.75 25 x 0.75 34 x 0.75 42 x 0.75
96
Part No.
5DE7 640 5DE7 641 5DE7 642 5DE7 643 5DE7 644 5DE7 645 5DE7 650 5DE7 652 5DE7 655 5DE7 657
Sales & Order Processing
Selection and Ordering Data
Approx. No. of Strands x Max. Strand Diameter
Cable Overall Diameter
Unenclosed Touching
mm 24 x 0.21 24 x 0.21 24 x 0.21 24 x 0.21 24 x 0.21 24 x 0.21 24 x 0.21 24 x 0.21 24 x 0.21 24 x 0.21
mm 7.4 7.7 8.2 9.0 9.5 12.0 14.2 17.0 19.0 20.3
A 10 10 10 10 10 10 10 10 10 10
Phone 131 773
Fax 1800 060 773
No. of Cores x Conductor Cross-section mm2 2 x 1.0 3 x 1.0 4 x 1.0 5 x 1.0 7 x 1.0 12 x 1.0 18 x 1.0 25 x 1.0 34 x 1.0 41 x 1.0
Part No.
5DE7 680 5DE7 681 5DE7 682 5DE7 683 5DE7 684 5DE7 685 5DE7 690 5DE7 693 5DE7 696 5DE7 698
Sales & Order Processing
Approx. No. of Strands x Max. Strand Diameter
Cable Overall Diameter
Unenclosed Touching
mm 32 x 0.21 32 x 0.21 32 x 0.21 32 x 0.21 32 x 0.21 32 x 0.21 32 x 0.21 32 x 0.21 32 x 0.21 32 x 0.21
mm 7.8 8.1 8.9 9.5 10.3 13.3 15.6 18.4 20.8 22.3
A 13 13 13 13 13 13 13 13 13 13
Phone 131 773
Fax 1800 060 773
97
PROTOFLEX Ö500
PROTOFLEX Ö500
PVC Control cables, screened Selection and Ordering Data No. of Cores x Conductor Cross-section
98
Part No.
PVC Control cables, screened Selection and Ordering Data
Approx. No. of Strands x Max. Strand Diameter
Cable Overall Diameter
Unenclosed Touching
mm 8. 8.9
A 16 16
mm2 2 x 1.5 3 x 1.5
5DE7 720 5DE7 721
mm 28 x 0.26 28 x 0.26
4 x 1.5
5DE7 722
28 x 0.26
9.5
16
5 x 1.5
5DE7 723
28 x 0.26
10.3
16
7 x 1.5
5DE7 724
28 x 0.26
11.0
16
12 x 1.5
5DE7 725
28 x 0.26
14.7
16
18 x 1.5
5DE7 728
28 x 0.26
17.0
16
25 x 1.5
5DE7 733
28 x 0.26
20.4
16
34 x 1.5
5DE7 735
28 x 0.26
22.6
16
42 x 1.5
5DE7 736
28 x 0.26
24.3
16
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
No. of Cores x Conductor Cross-section mm2 2 x 2.5 3 x 2.5 4 x 2.5 5 x 2.5 7 x 2.5 12 x 2.5 18 x 2.5 25 x 2.5 34 x 2.5
Part No.
5DE7 760 5DE7 761 5DE7 762 5DE7 763 5DE7 764 5DE7 765 5DE7 770 5DE7 772 5DE7 775
Sales & Order Processing
Approx. No. of Strands x Max. Strand Diameter
Cable Overall Diameter
Unenclosed Touching
mm 48 x 0.26 48 x 0.26 48 x 0.26 48 x 0.26 48 x 0.26 48 x 0.26 48 x 0.26 48 x 0.26 48 x 0.26
mm 9.7 10.3 11.1 12.2 13.7 17.8 20.8 25.1 28.2
A 23 23 23 23 23 23 23 23 23
Phone 131 773
Fax 1800 060 773
99
PROTOFLEX-EMV-FC
PROTOFLEX-EMV-FC
UV stabilised
UV stabilised
OPERATING TEMPERATURE -
APPLICATION Specifically designed low capacitance screened cable for connection between AC variable speed drives and motors. Suitable for fixed installation and occasional freely flexing applications in dry damp and wet conditions. U.V stabilised for outdoor use. Not suitable for direct installation into the ground or submersion in water.
DESIGN
Minimum permissible ambient temperature -40°C Maximum permissible conductor temperature 90°C Maximum permissible short circuit temperature 250°C Minimum ambient temperature for optimum fully flexible operation -5°C
CURRENT CARRYING CAPACITY Current ratings are based on continuous operation at an ambient temperature of 40°C. At other temperatures these values must be converted using the following table. °C 15 20 25 30 35 40 45 50 55 60 65 70 75 80 Factor 1.26 1.20 1.15 1.10 1.05 1.00 0.94 0.88 0.81 0.73 0.65 0.57 0.47 0.34
Electromagnetic compatibility (EMC) is the ability of electrical or electronic equipment to function normally in an environment without being effected by (EMI) electromagnetic and (RFI) radio frequency interferences or in turn disturbing the environment by transmitting EMI or RFI.
MINIMUM BENDING RADII
The Siemens PROTOFLEX -EMV screened power cable consists of finely stranded copper conductors with Cross Linked Poly Ethylene (XLPE) insulation covered with a tinned copper braided screen and a PVC orange, transparent sheath.
CORE COLOUR IDENTIFICATION
For cable cross sections greater than 16mm2 the earth conductor is divided evenly into 3 seperate cores and uniformally located in the intersticial gaps around the power cores. This achieves a truly concentric design in accordance with the EMC standards.
For recommended bending radii refer to the selection and ordering data tables.
4 core - Brown, Blue, Black, Green/Yellow
VOLTAGE RATING -
Rated AC Voltage:
Uo/U
= 0.6kV
-
Rated DC Voltage:
Uo/U
= 0.9/1.8kV
-
AC test Voltage:
= 5kV
The overall tinned copper braid screen is specifically designed for optimum Electromagnetic Compatibility (EMC) by taking into account the percentage coverage, braid fan angle, and wire gauge which all results in a very low transfer resistance. The screen offers a low DC resistance affording protection from low frequency interference such as AC harmonics. The cable is in accordance with AS 1125 for the conductors and AS 1347 for the sheath. Fire performance is according to IEC 06332- 1 100
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
101
PROTOFLEX-EMV-FC
PROTOFLEX-EMV-FC
UV stabilised
UV stabilised
Selection and Ordering Data No. of Cores and Conductor Rated Cross-section
Part No.
Conductor Design approx. no. of strands x max. strand diameter
Operating Capacitance
Nominal Diameter over Screen
Max Outer Diameter
Min Bending Radii Fixed
Min Bending Radii Flexing
Net Weight
kg/km 150 205 320 410 600 770 1110 1510 2140 2860 3740 4810 5850 7100 9400
mm2 4 x 1.5 4 x 2.5 4x4 4x6 4 x 10 3 x 16 + 3 x 2.5/3 3 x 25 + 3 x 4/3 3 x 35 + 3 x 16/3 3 x 50 + 3 x 25/3 3 x 70 + 3 x 35/3 3 x 95 + 3 x 50/3 3 x 120 + 3 x 50/3 3 x 150 + 3 x 70/3 3 x 185 + 3 x 95/3 3 x 240 + 3 x 120/3
5DE6 600 5DE6 601 5DE6 602 5DE6 603 5DE6 604 5DE6 605 5DE6 606 5DE6 607 5DE6 608 5DE6 610 5DE6 611 5DE6 612 5DE6 613 5DE6 614 5DE6 615
mm 28 x 0.25 46 x 0.25 5 x 0.30 77 x 0.30 78 x 0.39 26 x 0.39 96 x 0.39 27 x 0.39 388 x 0.39 553 x 0.39 729 x 0.39 932 x 0.39 66 x 0.39 425 x 0.39 887 x 0.39
nF/Km 130 145 145 160 185 235 245 270 270 295 300 312 315 315 320
mm 8.4 9.4 11.6 12.8 15.3 16.2 19.8 22.5 26.7 30.6 35.1 39.6 44.3 48.9 55.8
mm 11.5 13.0 15.5 17.0 19.5 21.0 24.5 28.0 33.0 37.0 42.0 46.5 51.5 57.0 64.5
mm 69 100 124 136 156 168 196 224 264 296 336 372 412 456 516
mm 92 125 155 170 195 210 245 280 330 370 420 465 515 570 645
3 x 300 + 3 x 150/3
5DE6 616
2350 x 0.39
330
62.9
72.0
576
720
102
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
11680
Unenclosed Touching
A 21 27 37 48 67 90 119 147 184 228 274 320 368 420 498 576
Fax 1800 060 773
103
EMC CABLE GLANDS
EMC CABLE GLANDS THE SOLUTION The 6 teeth of the lock nut are for equipotential bonding and scrape into the insulating layers of paint or powder to create a vibration-resistant contact. • • • •
EMC Cable Glands from Siemens are the perfect complement to PROTOFLEX-EMV screen cables providing an efficient shield connection that meets the requirements of both AS/NZS CISPR-11 and EN 55011. Consisting of a few components they are quick and easy to install. Tightening the pressure nut causes the insert to press against two taper rings which, in turn, press on an endless spring washer, making its diameter taper, thus permanently bonding the screen braid of the threaded cable. The result is a low resistance connection between the cable screen and the housing of the electrical equipment via the gland body. In order to conform with the radio inter ference suppression requirements set forth in EN 55011, the shield must be connected around its entire circumference and over an ample surface area at both ends of the cable.
ADVANTAGES • • • • • •
easily assembled 360 o bonding on screen large sealing ranges IP68 high attenuation sheath can still be continued on into the equipment housing
THE EARTHING PROBLEM The paint on cubicles and equipment housings has to be removed so the metal gland body is in direct contact with the bare metal of the equipment to ensure the earth bonding circuit is compliant. 104
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
no surface corrosion very low-ohm transition; gland/housing no need to clean contact surface increases the installed vibration-resistance through frictional connection
Cable Cross Section
Cable Gland
Lock Nut
mm 4 x 1.5 4 x 2.5 4x4 4x6 4 x 10 3 x 16 + 3 x 2.5/3 3 x 25 + 3 x 4/3 3 x 35 + 3 x 16/3 3 x 50 + 3 x 25/3 3 x 70 + 3 x 35/3 3 x 95 + 3 x 50/3 3 x 120 + 3 x 50/3 3 x 150 + 3 x 70/3 3 x 185 + 3 x 95/3 4 x 240 + 3 x 120/3
Part No. 100210368 100210999 100210738 100210708 100206872 100206246 100207312 100208193 100208574 100209510 100209202 100209598 100209276 100210042 100200893
Part No. 100203808 100204211 100204211 100204211 100204211 100206391 100207739 100207739 100209917 100209917 100210718 100210718 100210735 100211073 100200894
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
105
EMC CABLE GLANDS
EMC CABLE GLANDS
Selection and Ordering Data
Gland Part No
No. of Cores x Conductor size mm2
Cable gland drawing and dimensions Cable cross section
Glands Part No
mm Part No. 4 x 1.5 100210368 4 x 2.5 100210999 4x4 100210738 4x6 100210708 4 x 10 100206872 3 x 16 + 3 x 2.5/3 100206246 3 x 25 + 3 x 4/3 100207312 3 x 35 + 3 x 16/3 100208193 3 x 50 + 3 x 25/3 100208574 3 x 70 + 3 x 35/3 100209510 3 x 95 + 3 x 50/3 100209202 3 x 120 + 3 x 50/3 100209598 3 x 185 + 3x 95/3 100210042 3 x 240 + 3 x 120/3 100200893
106
Sales & Order Processing
Lock Nut
Part No. 100203808 100204211 100204211 100204211 100204211 100206391 100207739 100207739 100209917 100209971 100210718 100210718 100211073 100200894
Phone 131 773
A1
M 20 x 1.5 M 25 x 1.5 M 25 x 1.5 M 25 x 1.5 M 25 x 1.5 M 32 x 1.5 M 40 x 1.5 M 40 x 1.5 M 50 x 1.5 M 50 x 1.5 M 63 x 1.5 M 63 x 1.5 M 75 x 1.5 M 80 x 2.0
Overall Thread Height C mm 31 32 32 32 34 39 45 45 50 58 58 58 47 61
Fax 1800 060 773
100210368 100210999 100210738 100210708 100206872 100206246 100207312 100208193 100208574 100209510 100209202 100209598 100209276 100210042 100200893
Protoflex EMV 4 x 1.5mm Protoflex EMV 4 x 2.5mm Protoflex EMV 4 x 4 mm Protoflex EMV 4 x 6 mm Protoflex EMV 4 x 10 mm Protoflex EMV 3 x 16 + 3 x 2.5/3 Protoflex EMV 3 x 25 + 3 x 4/3 Protoflex EMV 3 x 35 + 3 x 16/3 Protoflex EMV 3 x 50 + 3 x 25/3 Protoflex EMV 3 x 70 + 3 x 35/3 Protoflex EMV 3 x 95 + 3 x 50/3 Protoflex EMV 3 x 120 + 3 x 50/3 Protoflex EMV 3 x 150 + 3 x 70/3 Protoflex EMV 3 x 185 + 3 x 95/3 Protoflex EMV 3 x 240 + 3 x 120/3
Sales & Order Processing
Phone 131 773
Cable Diameter Max mm 11.5 13.0 15.5 17.0 19.5 21.0 24.5 28.0 33.0 37.0 42.0 46.5 51.5 57.0 64.5
Sealing Diameter Min mm 7.0 10.0 14.0 14.0 17.0 19.0 25.0 25.0 32.0 37.0 40.0 45.0 51.0 54.0 63.0
Max mm 11.0 14.0 18.0 18.0 20.0 23.0 29.0 29.0 37.0 41.0 45.0 51.0 55.0 58.0 70.0
Fax 1800 060 773
107
blueglobe® CABLE GLANDS
blueglobe® CABLE GLANDS Gland selection data based on cable O.D Thread
M12
M16
M20
Cable O.D range mm
M25
2-8
4 - 11
5 - 14 11 - 20 15 - 25
20 - 32 31 - 42 41 - 54
Max. strain Class B
75N
120N
130N
350N
140N
M32
M40
250N
M50
M63
350N
400N
Part number and gland dimensions
• • •
108
Highest protection rate IP68 up to 15 bar Wide sealing range means one gland body for several cable O.D's Highest strain relief (EN 50262 Class B)
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Brass Nickel Plated Part No bg812 ms bg816 ms bg820 ms bg825 ms bg832 ms bg840 ms bg850 ms bg863 ms
Connection thread/ length mm A D M12x1,5 M16x1,5 M20x1,5 M25x1,5 M32x1,5 M40x1,5 M50x1,5 M63x1,5
15 15 15 15 15 15 15 15
Sales & Order Processing
range max/min. ø mm
Sealing range without insert max/min. ø mm
C
Spanner width SW x E mm
2-8 4 - 11 5 - 14 11 - 20 15 - 25 20 - 32 31 - 42 41 - 54
5-8 7 - 11 9 - 14 16 - 20 20 - 25 26 - 32 35 - 42 46 - 54
21 25 29 29 32 35 35 38
17x18,9 20x22,2 24x26,5 30x33 36x39,5 45x48 57x61 68x74
Phone 131 773
Fax 1800 060 773
109
blueglobe® CABLE GLANDS
blueglobe® CABLE GLANDS
INSTALLATION INSTRUCTIONS
KEY BENEFITS A blueglobe ® Gland body Brass nickel plated & metric thread B Temperature range -40°C up to +130°C Sealing insert Blue elastic TPE High UV-stability Halogen and plasticiser free C Highest IP rating Up to 15 bar and above at IP 68 D Symmetric radial design Patented “globe” sealing system Large surface area with elastic sealing Zero cable damage from notching or strangling No insert folding with small cable O.D’s E Removable insert F Connection thread O-ring groove with O-ring in flange surface Metric connection thread G Strain relief Highest strain relief in accordance with EN 50262 Class B
Small cable diameter
Insert cable with IP 68 Installations globemarker on the outside….or remove the marker.
INSTALLATION INSTRUCTIONS Large cable diameter
For a larger cable diameter remove the insert by inserting a screw driver into the seam… and lift out the insert.
110
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
111
CORDAFLEX (SMK)
CORDAFLEX (SMK)
Flexible Reeling and Crane Cables
APPLICATION CORDAFLEX (SMK) cables are specifically designed to withstand high and very high mechanical stresses associated with cable reelers, festoon systems and force guided applications where high dynamic and static forces are induced into the cable. CORDAFLEX (SMK) is designed for all types of mobile equipment such as ship loaders, gantry cranes, stackers and reclaimers, inclinators, hoists, spreader and magnet cranes, in steelworks, smelters and subzero environments.
112
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
113
CORDAFLEX (SMK)
CORDAFLEX (SMK) - selection table -
Festoon System
Spring reeler without guides
Motor driven reeler without cable guide
Mono-spiral with multiroller guides
Drum reeler force guided
M
M
M
M
Reeler for vertical cable run
CORDAFLEX SMK max = 30 N/mm2
M
M
M = Main field of application
Type
CORDAFLEX (SMK)
Conductor (refer also to DIN VDE 0295
Electrolytic copper tinned, very finely stranded class "F"
Conductor (refer also to DIN VDE 0207, Part 20)
PROTOLON MS Newly developed special compound based on high-quality EPR (at least 3GI3); improved mechanical and electrical characteristics
Shield for individually shielded cores and twisted and shielded
Braid screen made of tinned copper wires. Transfer impedance optimized at 30 MHz Surface covered: at least 60% for shielded cores at least 80% for twisted and shielded pairs
Core identification
Optimal identification as a result of light insulation with numbers printed in black for power and control cables, protective-earth conductor green-yellow
Core arrangement
Laid-up in a maximum of 3 layers, Length of lay 5 x D (core diameter)
Support element
Central aramide support element to increase the loading capability for special designs; the kN value designates the breaking load of the support element.
Sheath System
PROTOFIRM special: First sheath Newly developed special compound based on PCP, colour: yellow Anti-torsion braid Reinforced braid made of polyester threads, in a vulcanized bond between the sheaths. Resulting in a high strength of the sheath system. PROTOFIRM: Third sheath A sheath system with a unique combination of flexibility and robustness has been achieved through the use of a new structure. Abrasion and tear-proof special rubber compound based on PCP, colour: yellow. PROTOFIRM sandwich construction (2 sheaths) for wall thickness 3mm and more. Refer also to PROTOLON (SMK)
Marking
CORDAFLEX (SMK) (N)SHTÖU-J/-O (number of cores) x (cross section)
DESIGN CORDAFLEX (SMK) cables consist of extra finely stranded tinned copper conductors with a short length of lay to provide an extremely flexible conductor assembly with greater mechanical strength. The cable design is in accordance with the Australian Standards AS 1125, AS 3116, AS 3191 and DIN VDE 0250 pt 814 for NSHTOU-J.
114
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
115
CORDAFLEX (SMK)
CORDAFLEX (SMK) Minimum bending radii
THERMAL PARAMETERS
CORDAFLEX, PLANOFLEX, RONDOFLEX, SPREADERFLEX, PROTOLON, Lift control cable
Flexible Cables
Ambient temperature • fully flexible operation • fixed installaton
-35oC to +60 oC -50 oC to +80 oC
Rated voltage Uo/U Up to 0.6/1 kV Up to 8
Above 8 to 12
Above 12 to 20
Above 20
Fixed installation
3xd
3xd
4xd
4xd
Fully flexible operation
3xd
4xd
5xd
5xd
If the bending radii are smaller than those permitted, a reduced service life can be expected depending on the stress conditions. The values given in the following table should be taken as a basis.
For the entry, e.g. at a centre feed point
3xd
4xd
5xd
5xd
The minimum bending radii are shown as the product of the overall diameter of the cable and a factor, which is dependent on the diameter of the cable (e.g. 3x d).
For forced guidance with reeling operation
5xd
5xd
5xd
6xd
The minimum permissible bending radii are valid within the specified ambient temperature range (see thermal parameters subject to the provision that the permissible tensile loads are not exceeded .
For forced guidance with festoon operation
4xd
4xd
5xd
5xd
For forced guidand with power tracks
4xd
4xd
5xd
5xd
For forced guidance with sheaves
7.5 x d
7.5 x d
7.5 x d
7.5 x d
For forced guidance with cable tenders
7.5 x d
7.5 x d
7.5 x d
7.5 x d
Minimum distance with double or S-type directionalchanges
20 x d
20 x d
20 x d
20 x d
Maximum permissible operating temperature of the conductor
90 oC
Short-circuit temperature of the conductor
250 oC
MECHANICAL PARAMETERS
Maximum overall diameter of the cable ormaximium thickness of the flat cable (mm)
Minimum bending radii
In critical cases, the cable manufacturer should be consulted.
CHEMICAL PARAMETERS Resistance to oil Weather resistance Water compatibility
116
Given to DIN VDE 0473, part 811-2-1, para.10 Unrestricted use outdoors and indoors, resistant to zone, UV and mositure Given and verified in long-term tests
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
117
CORDAFLEX (SMK)
CORDAFLEX (SMK)
Selection and Ordering Data
mm2
Cross- Stretched Suspended section laying freely in air mm2 A A Factor 1 1.05 1 1.5 23 24 2.5 30 32 4 6 49 51 10 66 69 16 88 92 25 120 126 35 145 152 50 170 179 70 220 231 95 250 263 120 295 310 150 340 357 185 385 404 240 455 478 300 515 541
118
Sales & Order Processing
mm2
1 layer A 0.8 19 25 41 55 74 101 122 143 185 210 248 286 323 382 433
Reeled in layers 2 layers 3 layers A A 0.61 0.49 12 6 15 8 25 12 34 17 45 22 61 30 74 36 87 43 113 55 128 63 151 74 174 85 197 97 233 114 264 129
Phone 131 773
4 layers A 0.42 2 3 5 7 9 13 15 18 23 26 31 36 41 48 54
Fax 1800 060 773
Cross- Stretched Suspended section laying freely in air mm2 A A Factor 1 1.05 1 1.5 18 19 2.5 23 24 4 6 38 40 10 51 54 16 67 70 25 90 95 35 110 116 50 125 131 70 160 168 95 185 194 120 210 221 150 245 257 185 270 284 240 315 331 300 355 373
Sales & Order Processing
1 layer A 0.8 15 19 32 43 56 76 92 105 134 155 176 206 227 265 298
Phone 131 773
Reeled in layers 2 layers 3 layers A A 0.61 0.49 9 5 12 6 19 10 26 13 34 17 46 23 56 28 64 31 82 40 95 46 108 53 126 62 138 68 161 79 182 89
4 layers A 0.42 2 2 4 5 7 9 12 13 17 20 22 26 28 33 37
Fax 1800 060 773
119
CORDAFLEX (SMK)
CORDAFLEX (SMK)
MECHANICAL PARAMETERS
VOLTAGE RATING
Tensile load: Torsional stresses: Minimum bending radii: Min. distance with S-type directional changes:
-
Up to 30 N/mm2 + 50o/m According to DIN VDE 0298, Part 3 20 x D
-
Rated Voltage: Maximum operating voltages in: 3 phase AC operation DC operation AC test voltage
Uo/U = 0.6/1kV Uo/U = 0.72/1.2kV Uo/U = 0.9/1.8kV = 4kV over 5 min
CURRENT CARRYIING CAPACITY
TRAVEL SPEED
If, after all selection criteria have been taken into account, the type of flexible electric cable to be used for cranes and material handling equipment has been decided on, the necessary cross-section of the conductor can be determined either from the current to be transmitted or from the power. Installation conditions (stretched laying, suspended freely in the air, reeled), variations in ambient temperature, grouping, type of operation (continuous duty, intermittent periodic duty) and the use of multi-core cables are to be taken into account.
At high speeds close attention to other parameters eg bending radii, cable tension and temperature must be adhered to.
De-rating factors for varying ambient temperatures Ambient temperature oC °C 15 20 25 30 35 40 45 50 55 60 65 70 75 80 Factor 1.26 1.20 1.15 1.10 1.05 1.00 0.94 0.88 0.81 0.73 0.65 0.57 0.47 0.34
TENSILE STRENGTH CORDAFLEX has a maximum safe reeling tensile strength of 30N/mm2. This ensures that no conductor deformation will occur in operation. Dynamic tensile stresses such as start-up, braking and centre feed pass-over should be taken into account.
120
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
VERTICAL SUSPENSION When CORDAFLEX cables are vertically suspended care must be taken to terminate the cable at the point of suspension. This can be done by either stress relief drums with 21/2 turns of cable around the drum, cable stockings correctly sized for the diameter and weight or cable clamps. Refer to page 193. CORDAFLEX (SMK) control cables for vertical reeling operations with 20 kN support element. For CORDAFLEX steel core hangers or rope thimbles should be employed to ensure correct tensile load bearing on the steel support rope. If the cable is to pass or be guided over a roller sheave then this shall be specifically dimensioned for the cable and shall have a minimum bending radius of 18 x cable diameter to distribute the tensile stress and compressive forces over as wide a surface area as possible. The support element must be terminated at the reeler.
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
121
CORDAFLEX (SMK)
CORDAFLEX (SMK)
Selection and Ordering Data Part No.
Number of Cores Main Conductor and Nominal Diameter Cross-section mm mm2 (N)SHTÖU-J Power Cables, Four-core Design 5DH3 132 4x4 3.0 5DH3 133 4x6 3.6 5DH3 134 4 x 10 4.6 5DH3 135 4 x 16 5.6 5DH3 136 4 x 25 7.3 (N)SHTÖU-J Power Cables, Five-core Design 5DH3 151 5x4 3.0 5DH3 152 5x6 3.6 5DH3 153 5 x 10 4.6 5DH3 154 5 x 16 5.6 (N)SHTÖU-J Power Cables, Three-core Design with Protective-earth Conductor split into 3 5DH3 121 3 x 35 + 3 x 16/3 8.4/3.5 5DH3 122 3 x 50 + 3 x 25/3 10.3/4.2 5DH3 123 3 x 70 + 3 x 35/3 12.0/5.0 5DH3 124 3 x 95 + 3 x 50/3 14.0/6.0 5DH3 125 3 x 120 + 3 x 70/3 15.8/7.2 5DH3 126 3 x 150 + 3 x 70/3 17.5/7.2 5DH3 127 3 x 185 + 3 x 95/3 19.4/8.1 5DH3 128 3 x 240 + 3 x 120/3 22.5/9.3 (N)SHTÖU-J Control Cables for Vertical Reeling Operation, with 20 kN Support Element 5DH3 291 49 x 1 (20 kN) 1.3 5DH3 295 24 x 2.5 (20 kN) 2.0 5DH3 296 30 x 2.5 (20 kN) 2.0 5DH3 298 44 x 2.5 (20 kN) 2.0 5DH3 290 56 x 2.5 (20 kN) 2.0 122
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Overall Diameter of Cable
Approx. Net Weight for 1000 m kg
Maximum Permissible Tensile Force N
Min mm
Max mm
16.0 17.4 21.6 23.7 28.5
18.0 19.4 23.6 26.7 31.5
455 575 905 1240 1850
480 720 1200 1920 3000
17.4 19.0 23.4 26.1
19.4 21.0 25.4 29.1
430 690 1080 1500
600 900 1500 2400
28.5 34.4 39.7 44.3 51.0 53.9 58.9 67.4
31.5 37.4 42.7 47.3 55.0 57.9 62.9 71.4
2160 2850 3920 5020 6630 7690 9310 12200
3150 4500 6300 8550 10800 13500 16650 21600
26.6 26.2 29.4 34.1 40.1
29.6 29.2 32.4 37.1 43.1
1190 1290 1610 2160 2840
3200 3600 4100 5100 6000
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
123
CORDAFLEX (SMK)
CORDAFLEX (SMK)
Selection and Ordering Data Part No.
Number of Cores and Nominal Cross-section mm2 (N)SHTÖU-J Control Cables 5DH3 130 4 x 1.5 5DH3 140 5 x 1.5 5DH3 142 7 x 1.5 5DH3 161 12 x 1.5 5DH3 162 18 x 1.5 5DH3 163 24 x 1.5 5DH3 164 30 x 1.5 5DH3 165 36 x 1.5 5DH3 166 44 x 1.5 5DH3 167 56 x 1.5 5DH3 111 3 x 2.5 5DH3 131 4 x 2.5 5DH3 141 5 x 2.5 5DH3 143 7 x 2.5 5DH3 171 12 x 2.5 5DH3 172 18 x 2.5 5DH3 173 24 x 2.5 5DH3 174 30 x 2.5 5DH3 175 36 x 2.5 5DH3 176 44 x 2.5 5DH3 177 56 x 2.5 (N)SHTÖU-O Bus Cables 5DH3 186 3 x (2 x 1)C 5DH3 187 6 x (2 x 0.5)C 5DH3 188 6 x (2 x 1)C 5DH3 183 12 x 1(C) (N)SHTÖU-J Combined Control Cables 5DH3 184 12 x 2.5 + 12 x 1 (C) 5DH3 180 19 x 2.5 + 5 x 1 (C) 5DH3 181 25 x 2.5 + 5 x 1 (C) 124
Sales & Order Processing
Phone 131 773
Main Conductor Diameter mm
Min mm
Max mm
Approx. Net Weight for 1000 m kg
1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0
12.2 13.0 15.2 21.4 21.3 23.8 26.6 26.5 29.5 34.9 12.7 13.2 14.2 16.6 23.4 23.3 26.2 29.4 29.3 34.1 40.1
13.8 14.6 17.2 23.4 23.3 26.8 29.6 29.5 32.5 37.9 14.3 14.8 15.8 18.6 25.4 25.3 29.2 32.4 32.3 37.1 43.1
240 280 385 710 760 990 1220 1260 1530 2050 280 305 355 510 920 1005 1320 1660 1720 2230 2940
180 225 315 540 810 1080 1350 1620 1980 2520 300 375 525 900 1350 1800 2250 2700 3300 4200
1.3 0.9 1.3 1.3
22.0 23.1 28.9 22.9
24.0 25.1 31.9 25.9
755 885 1330 865
180 360 360 360
2.0/1.3 2.0/1.3 2.0/1.3
26.2 26.2 29.4
29.2 29.2 32.4
1230 1290 1620
900 1575 2025
Fax 1800 060 773
Overall Diameter of Cable
Sales & Order Processing
Phone 131 773
Maximum Permissible Tensile Force N
Fax 1800 060 773
125
RONDOFLEX
RONDOFLEX
Rubber Sheathed Festoon Cable
ELECTRICAL PARAMETERS Rated voltage Max permissible operating voltage in AC systems Max permissible operating voltage in DC systems AC test voltage
APPLICATION Flexible power and control cable, for use on festoon systems machine tools, material handling equipment, associated with high mechanical stresses and frequent bending during operation, also suitable for light duty reeling applications.
DESIGN RONDOFLEX cables consist of electrolytic copper, tinned finely stranded conductors. The insulation is a PROTOLON MS which is a newly developed special compound based on high quality EPR which provides improved mechanical and electrical characteristics. For individually shielded cores and twisted and shielded pairs the overall braided screen consists of tinned copper wires. The transfer impedance is optimised at 30 MHz and the surface area covered is approx 60% for shielded cores and 80% for twisted and shielded pairs. The inner sheath is EPR, the outer sheath is PCP. RONDOFLEX remains flexible at sub zero temperatures and high ambient temperatures. The construction is in accordance with the Australian Standards AS1125, AS3116, AS3191 and VDE certificate with VDE Reg No. 9809.
CHEMICAL PARAMETERS Resistance to oil Weather resistance
126
Sales & Order Processing
Given to DIN VDE 0473, Part 811-2-1, para.10 Unrestricted use outdoors and indoors, resistant to ozone, UV and moisture
Phone 131 773
Fax 1800 060 773
Uo/U = 0.6/1kV Uo/U = 0.7/1.2kV Uo/U = 0.9/1.8kV 2.5 kV over 5 min
THERMAL PARAMETERS Ambient temperature • Fully flexible operation • Fixed installation Max permissible operating temperature of the conductor Short-circuit temperature of the conductor
-35oC to +60 oC -50 oC to +80 oC 90 oC 200 oC
CURRENT CARRYING CAPACITY Current ratings are based on continuous operation at an ambient temperature of 40°C. At other temperatures these values must be converted using the following table.
MECHANICAL PARAMETERS Tensile load Torsional stresses Minimum bending radii
Up to 15 N/mm2 + 90 o/m According to DIN VDE 0298, Part 3
Minimum distance for S-type directional changes
20 X D
Travel speed • Gantry (reeling operation) 60 m/min • Trolley (festoon system) up to 180 m/min • For speeds above 180m/min consult the manufacturer
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
127
RONDOFLEX
RONDOFLEX
CORE COLOUR INDENTIFICATION
CORE ARRANGEMENT
Control and power conductors are light coloured with numbers printed in black for easy indentifi cation and include a green/yellow earth conductor.
Laid-up in a maximum of 3 layers. Length of lay 10 x D.
Selection and ordering data Number of Cores & Nominal Cross-section mm2 NGRDGÖU–O Power cables Single-core design
NGRDGÖU–J Power cables Four and five-core design
NGRDGÖU–J Power cables Three-core design with protective-earth conductor split into 3 128
Sales & Order Processing
mm2 1 x 25 1 x 35 1 x 50 1 x 70 1 x 95 1 x 120 1 x 150 1 x 185 4x4 4x6 4 x 10 4 x 16 4 x 25 4 x 35 4 x 50 5x4 5x6 5 x 10 5 x 16 5 x 25 3 x 35 + 3 x 16/3 3 x 50 + 3 x 25/3 3 x 70 + 3 x 35/3
Phone 131 773
Part No.
5DG6 610 5DG6 611 5DG6 612 5DG6 613 5DG6 614 5DG6 615 5DG6 616 5DG6 617 5DG6 642 5DG6 643 5DG6 644 5DG6 645 5DG6 646 5DG6 647 5DG6 648 5DG6 652 5DG6 653 5DG6 654 5DG6 655 5DG6 656 5DG6 631 5DG6 632 5DG6 633
Fax 1800 060 773
Conductor diameter
mm 6.8 8.1 9.6 11.2 13.2 14.9 16.6 18.0 3.0 3.2 4.2 5.7 6.8 8.1 9.6 3.0 3.2 4.2 5.7 6.8 8.1 9.7 11.2
Overall Diameter of Cable
Min mm 11.4 12.3 15.0 16.5 18.9 20.8 22.9 24.8 13.9 15.9 18.2 22.9 26.9 30.1 35.7 15.7 17.5 20.8 24.6 29.5 27.7 32.5 39.1
Sales & Order Processing
Max mm 12.6 13.9 16.6 18.5 20.9 22.8 24.9 27.8 15.5 17.9 20.2 24.9 29.9 33.1 38.7 17.7 19.5 22.8 27.6 32.5 30.7 35.5 42.1
Approx. Net Weight for 1000 m
Maximum Permissible tensile force
Unenclosed Spaced
kg 330 430 625 835 1070 1340 1650 2010 350 475 680 1070 1600 2090 2970 450 575 865 1300 1940 1800 2540 3570
N 375 525 750 1050 1425 1800 2250 2775 240 360 600 960 1500 2100 3000 300 450 750 1200 1875 1575 2250 3150
A 150 185 230 290 360 420 485 570 38 48 66 88 120 145 180 38 48 66 88 120 145 180 230
Phone 131 773
Fax 1800 060 773
129
RONDOFLEX
RONDOFLEX
Selection and ordering data Number of Cores & Nominal Cross-section
NGRDGÖU–J Control cables
NGRDGÖU–O Bus cables
130
Sales & Order Processing
mm2 12 x 1.5 18 x 1.5 24 x 1.5 30 x 1.5 36 x 1.5 12 x 2.5 18 x 2.5 24 x 2.5 30 x 2.5 36 x 2.5 6 x (2 x 0.5) 6 x (2 x 1) C 9 x (2 x 0.5) C 9 x (2 x 1) C 12 x 1(C)
Phone 131 773
Part No.
5DG6 662 5DG6 663 5DG6 664 5DG6 665 5DG6 666 5DG6 672 5DG6 673 5DG6 674 5DG6 675 5DG6 676 5DG6 693 5DG6 694 5DG6 691 5DG6 692 5DG6 681
Fax 1800 060 773
Conductor diameter
mm 1.6 1.6 1.6 1.6 1.6 2.0 2.0 2.0 2.0 2.0 0.9 1.3 0.9 1.3 1.3
Overall Diameter of cable Min mm 16.2 18.7 22.1 23.3 24.6 17.9 21.5 24.0 26.4 28.4 22.1 28.1 28.3 35.9 18.0
Max mm 18.2 20.7 24.1 25.3 27.6 19.9 23.5 27.0 29.4 31.4 25.1 31.1 31.3 38.9 20.0
Sales & Order Processing
Approx. Net Weight for 1000 m
kg 440 615 805 930 1090 580 865 1110 1330 1550 850 1250 1340 2010 590
Phone 131 773
Maximum Permissible tensile force N 270 405 540 675 810 450 650 900 1125 1350 180 180 270 270 180
Unenclosed Spaced
A 20 20 20 20 20 28 28 28 28 28
Fax 1800 060 773
131
RONDOFLEX (C) - FC
RONDOFLEX (C) - FC ELECTRICAL PARAMETERS
Shielded EMC Festoon Power Cables
Rated voltage Max permissible operating voltage in AC systems Max permissible operating voltage in DC systems AC test voltage
APPLICATION For use on festoon systems, eg, on gantry cranes, hall gantry cranes, rack material handling equipment, transportation systems or machine tools, in particular for applications where there is a danger of interference to data transmission systems from power cables. The cables are used for high mechanical stresses and frequent bending, also suitable for use as a flexible motor power supply cable.
DESIGN The RONDOFLEX (C) - FC cable consists of electrolytic copper, thinned finely stranded conductors. The insulation is a PROTOLON MS which is a newly developed special compound based on high quality EPR providing improved mechanical and electrical characteristics. The overall braid screen is made of tinned copper wires with a surface coverage of greather than 80%. The inner sheath is SBR, the black outer sheath is PCP allowing it to remain flexible at sub zero temperatures and also withstand extremely high ambients. The construction is in accordance with the Australian Standards AS1125, AS3116, AS3191 and VDE certificate with VDE Reg No. 9809.
CHEMICAL PARAMETERS Resistance to oil Weather resistance
132
Sales & Order Processing
Given to DIN VDE 0473, Part 811-2-1, para. 10 Unrestricted use outdoors and indoors, resistant to ozone, UV and moisture
Phone 131 773
Fax 1800 060 773
Uo/U = 0.6/1kV Uo/U = 0.7/1.2kV Uo/U = 0.9/1.8kV 2.5 kV over 5 min
THERMAL PARAMETERS Ambient temperature • Fully flexible operation • Fixed installation Max permissible operating temperature of the conductor Short-circuit temperature of the conductor
-35oC to +60oC -50oC to +80oC 90oC 200oC
CURRENT CARRYING CAPACITY Current ratings are based on continuous operation at an ambient temperature of 40°C. At other temperatures these values must be converted using the following table.
MECHANICAL PARAMETERS Tensile load Up to 15 N/mm2 Torsional stresses No application Minimum bending radii According to DIN VDE 0298, Part 3 Travel speed • Gantry (reeling operation) 60 m/min • Trolley (festoon system) - up to 180 m/min, the travel speed is determined by a number of factors and can thus not be precisely defined. Influence factors are, eg, space requirement, cable weight, loop sag, number of the festoon systems etc. • For speeds above 180 m/min consult the manufacturer. Additional tests Bending test Sales & Order Processing
Phone 131 773
Fax 1800 060 773
133
RONDOFLEX (C) - FC
RONDOFLEX (C) - FC
CORE COLOUR IDENTIFICATION
CORE ARRANGEMENT
Black, blue, brown with green/yellow earth conductor.
Three main conductors laid-up (10 x D) with protective-earth conductor split into 3 in the outer filler
Selection and ordering data Number of Cores & Nominal Cross-section
Part No.
mm2 4x4 4x6 4x10 3x16+3x2,5 3x25+3x4 3x35+3x6 3x50+3x10 3x70+3x10 3x95+3x16 3x120+3x25 Number of Cores & Nominal Cross-section mm2 4x4 4x6 4x10 3x16+3x2,5 3x25+3x4 3x35+3x6 3x50+3x10 3x70+3x10 3x95+3x16 3X120+3X16 134
5DG6 682 5DG6 683 5DG6 684 5DG6 685 5DG6 686 5DG6 687 5DG6 688 5DG6 690 5DG6 679 5DG6 680 Part No.
5DG6 682 5DG6 683 5DG6 684 5DG6 685 5DG6 686 5DG6 687 5DG6 688 5DG6 690 5DG6 679 5DG6 680
Sales & Order Processing
Conductor resistor
Ω/km 4.95 3.30 1.91 1.21 0.78 0.55 0.39 0.27 0.21 0.16
Phone 131 773
Shield cross-section
Conductor diameter
mm2 8.0 10.7 12.7 13.3 15.9 21.4 24.9 29.8 -
mm 2.45 2.93 3.90 5.72 6.75 8.05 9.60 11.50 14.00 15.80
Overall Diameter of Cable Min mm 14.8 17.2 19.7 22.2 25.3 29.3 35.0 40.9 44.2 48.7
Inductance
Capacitance
(core/core) at 10 kHz iH/km 550 530 510 480 450 430 410 390 250 220
(core/shield) at 1 kHz iF/km 180 190 230 225 275 325 400 475 360 370
Fax 1800 060 773
Approx. Net Weight for 1000 m Max mm 17.8 20.2 22.7 25.2 28.3 32.3 38.0 43.9 47.2 51.7
kg 485 700 925 1150 1610 2160 3090 4100 5040 5900
Maximum Permissible tensile force N 240 300 600 720 1125 1575 2250 3150 4275 5400
Unenclosed Spaced
A 38 48 66 88 120 145 180 230 285 330
Transfer impedance
at 1 MHz mΩ/m 0.4 0.2 0.1 -
Sales & Order Processing
at 10 MHz mΩ/m 1.3 0.6 0.2 -
Phone 131 773
at 30 MHz mΩ/m 3.5 1.5 0.7 -
Fax 1800 060 773
135
RONDOFLEX-CHAIN
RONDOFLEX-CHAIN ELECTRICAL PARAMETERS
Highly Flexible Chain Cable
Rated voltage Max permissible operating voltage in AC systems Max permissible operating voltage in DC systems AC test voltage
APPLICATION All chain systems (e.g. container cranes, stacking cranes, indoor cranes, material-handling equipment). Specifically designed for outdoor energy chain applications with long travel distances at high travel speeds. Key benefits are reliability, abrasion resistance and a long lifetime.
DESIGN The power and control conductors in RONDOFLEX (CHAIN) cables consist of Class 5 finely stranded electrolytic copper. The earth conductors consist of very finely stranded electrolytic copper exceeding Class 5. The insulation compound is Protolon MS (refer also DIN VDE 0207) which is a high grade insulation compound based on EPR (at least. 3GI3) with improved mechanical and electrical performance; alternative for control cables: ETFE. The inner sheath is a black special compound based on EPR GM1b. The overall shield consists of a tinned copper wire braided screen with greater than 80% coverage. The outer sheath is a high grade compound based on EVA with excellent abrasion and aging characteristics. Core identification is a light coloured compound with black number prints, yellow-green earth.
CHEMICAL PARAMETERS Resistance to oil Weather resistance
136
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Uo/U = 0.7/1.2kV Uo/U = 0.9/1.8kV 3.5 kV over 5 min
THERMAL PARAMETERS Ambient temperature • Fully flexible operation • Fixed installation Max permissible operating temperature of the conductor Short-circuit temperature of the conductor
-35oC to +80 oC -50 oC to +80 oC 90 oC 200 oC
MECHANICAL PARAMETERS Tensile load Torsional stresses Minimum bending radii Travel speed • Trolley • Other
According to DIN VDE 0473, Part 811-2-1 Para. 10 Unrestricted use indoors and outdoors, resistant to ozone, UV and moisture.
Uo/U = 0.6/1kV
Up to 15 N/mm2 No application According to DIN VDE 0298, Part 3 As a guide up to 300 m/min as tested on factory test rig As per all other recommended chain application speeds
TRAVEL SPEED Trolley Other
As a guide up to 300 m/min as tested on factory test rig. As per all other recommended chain application speeds.
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
137
RONDOFLEX-CHAIN
RONDOFLEX-CHAIN
CORE COLOUR INDENTIFICATION Control and power conductors are light coloured with numbers printed in black for easy indentification and include a green/yellow earth conductor.
Selection and ordering data Number of Cores & Nominal Cross-section
(N) GRDGÖU Power cable single core design
138
mm2 1x16 1x25 1x35 1x50 1x70 1x95 1x120 1x150 1x185 1x240
Sales & Order Processing
Part No.
5DG4 011 5DG4 012 5DG4 013 5DG4 014 5DG4 015 5DG4 016 5DG4 017 5DG4 018 5DG4 019 5DG4 020
Phone 131 773
Conductor diameter
mm 5.7 7.1 8.3 9.8 11.6 13.8 14.9 17.2 18.0 22.5
Fax 1800 060 773
Overall Diameter of Cable Min mm 7.7 10.6 12.1 13.9 15.9 19.1 20.8 23.0 25.8 29.9
Max mm 9.7 12.6 14.1 15.9 17.9 21.1 22.8 26.0 28.8 32.9
Approx. Net Weight for 1000 m
kg/km 210 325 445 605 830 1120 1390 1740 2130 2830
Sales & Order Processing
Maximum Permissible tensile force N 240 375 525 750 1050 1425 1800 2250 2775 3600
Phone 131 773
Unenclosed Spaced
Unenclosed Touching
A 110 150 185 230 290 360 420 485 570 680
A 86 115 145 175 225 280 325 375 435 520
Fax 1800 060 773
139
RONDOFLEX-CHAIN
RONDOFLEX-CHAIN
Selection and ordering data Number of Cores & Nominal
Part No.
Conductor diameter
Overall Diameter of Cable
Approx. Net Weight
Maximum Permissible for 1000 m
Cross-section
(N)GRDGCGÖU Power cable, single core design, screened
(N)GRDGÖU-J Power cable, 3/4 - core design
140
mm2 1x16C 1x25C 1x35C 1x50C 1x70C 1x95C 1x120C 1x150C 1x185C 1x240C
4x4 4x6 4x10 4x16 4x25 3x50+3x25/3
Sales & Order Processing
Unenclosed Spaced tensile force
Unenclosed Touching
5DG4 211 5DG4 212 5DG4 213 5DG4 214 5DG4 215 5DG4 216 5DG4 217 5DG4 218 5DG4 219 5DG4 220
mm 5.7 7.1 8.3 9.8 11.6 13.8 14.9 17.2 18.0 22.5
Min mm 10.1 12.8 13.9 15.7 18.7 20.8 22.8 25.6 27.8 31.9
Max mm 12.1 14.8 15.9 17.7 20.7 22.8 24.8 28.6 30.8 34.9
kg/km 320 450 555 745 1090 1330 1580 2000 2330 3130
N 240 375 525 750 1050 1425 1800 2250 2775 3600
A 110 150 185 230 290 360 420 485 570 680
A 86 115 145 175 225 280 325 375 435 520
5DG4 111 5DG4 112 5DG4 113 5DG4 114 5DG4 115 5DG4 117
2.9 3.6 4.6 5.9 7.2 10.0
12.7 14.2 16.6 20.0 25.9 31.5
14.7 16.2 18.6 22.0 28.9 34.5
325 435 650 960 1580 2510
240 360 600 960 1500 2250
38 48 66 88 120 180
35 45 62 83 110 170
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
141
RONDOFLEX-CHAIN
RONDOFLEX-CHAIN
Selection and ordering data Number of Cores & Nominal Cross-section
(N)GRDGCGÖU-J Power cable, 3/4 - core design overall screened
(N)GRDGÖU-J Power cable, 5 & 7 - core design
142
mm2 4x2,5C 4x4C 4x6C 4x10C 3x16+3x2,5C 3x25+3x4C 3x35+3x6C 3x50+3x10C
7x4 5x6 5x10 5x16
Sales & Order Processing
Part No.
Conductor diameter
Overall Diameter of Cable
Approx. Net Weight for 1000 m
Maximum Permissible tensile force
Unenclosed Spaced
Unenclosed Touching
5DG4 240 5DG4 241 5DG4 242 5DG4 243 5DG4 254 5DG4 255 5DG4 256 5DG4 257
mm 1.9 2.9 3.6 4.6 5.9 7.2 8.1 10.0
Min mm 11.3 15.7 17.0 19.7 20.4 25.8 28.6 35.0
Max mm 13.3 17.7 19.0 21.7 22.4 28.8 31.6 38.0
kg/km 390 505 650 930 1070 1810 2220 3090
N 150 240 360 600 720 1125 1575 2250
A 28 38 48 66 88 120 145 180
A 26 35 45 62 83 110 135 170
5DG4 171 5DG4 122 5DG4 123 5DG4 124
2.9 3.6 4.6 5.9
16.7 15.8 19.7 22.8
18.7 17.8 21.7 24.8
535 535 850 1220
420 450 750 1200
38 48 66 88
35 45 62 83
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
143
RONDOFLEX-CHAIN
RONDOFLEX-CHAIN
Selection and ordering data Number of Cores & Nominal Cross-section
(N)GRDGÖU-J control cable, overall screened
(N)GRDGÖU-J control cable
144
mm2 12x1.5C 5x2.5C
12x1.5 24x1.5 7x2.5 12x2.5 18x2.5 24x2.5
Sales & Order Processing
Part No.
Conductor diameter
Overall Diameter of Cable
Approx. Net Weight for 1000 m
Maximum Permissible tensile force
Unenclosed Spaced
Unenclosed Touching
5DG4 252 5DG4 260
mm 1.5 1.9
Min mm 14.7 12.7
Max mm 16.7 14.7
kg/km 440 435
N 270 188
A 20 28
A 19 26
5DG4 152 5DG4 154 5DG4 141 5DG4 190 5DG4 191 5DG4 192
1.5 1.5 1.9 1.9 1.9 1.9
11.7 17.1 11.3 13.6 16.9 22.5
13.7 19.1 13.3 15.6 18.9 24.5
305 705 290 485 760 1010
270 540 263 450 675 900
20 20 28 28 28 28
19 19 26 26 26 26
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
145
RONDOFLEX-CHAIN
RONDOFLEX-CHAIN
Selection and ordering data Number of Cores & Nominal Cross-section
Part No.
Conductor Diameter
Fibre optic cable
6xG62,5/125µ 12xG62,5/125µ
5DG4 290 5DG4 291
mm -
(N)GRDGÖU-J Bus cable
1x(2x0.5)C 4x(2x0.5)C (4x2x0.5)C 6x(2x0.5)C 6x(2x1)C
5DG4 --5DG4 280 5DG4 --5DG4 --5DG4 ---
0.9 0.9 0.9 0.9 1.3
146
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Overall Diameter of Cable
Approx. Net Weight for 1000 m
Maximum permissible tensile force
Min mm 14 14
Max mm 16 16
kg/km 260 260
N 500 500
8 19 19.2 20.2 26.3
10 21 21.2 22.2 29.3
135 625 605 730 1120
15 60 60 90 180
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
147
PLANOFLEX
PLANOFLEX
Flat Festoon Crane Cables
OPERATING TEMPERATURE -
Minimum permissible ambient temperature Maximum permissible conductor temperature Maximum permissible short circuit temperature Minimum ambient temperature for optimum fully flexible operation
-55°C 90 °C 250 °C -35°C
MINIMUM BENDING RADII The recommended minimum bending radii is dependent on the cable thickness and should be observed to ensure operating reliability. cables up to 8mm thick = 3 x cable thickness cables up to 12mm thick = 4 x cable thickness cables above 12mm thick = 5 x cable thickness
APPLICATION • • • • • • • •
CURRENT CARRYING CAPACITY
Festoon gantry cranes Wharf & port facilities Mine sites & cold stores Container Cranes Timber & refuse cranes Rubber tyred gantries Trippers Steelworks & ladle cranes
Current ratings are based on a continuous operating ambient temperature of 40 °C. At other temperatures these values must be converted using the following table. °C Factor
TENSILE STRENGTH The maximum allowable tensile stress is 15N/mm2.
DESIGN PLANOFLEX cables consist of extra finely stranded copper conductors with a short length of lay to provide a high degree of flexibility. PROTOLON elastomer R-EP-90 insulation provides improved current carrying capacities and the cable is sheathed overall with HD-PCP-90 Polychloroprene which is oil resistant and flame retardant, remaining flexible at sub-zero temperatures, and withstands high ambient. The construction is in accordance with the Australian Standards AS 1125, AS 3116, AS 3191 and DIN VDE 0250 pt 809. PLANOFLEX is UL approved, Certificate File No. E113313.
148
Sales & Order Processing
15 20 25 30 35 40 45 50 55 60 65 70 75 80 1.26 1.20 1.15 1.10 1.05 1.00 0.94 0.88 0.81 0.73 0.65 0.57 0.47 0.34
Phone 131 773
Fax 1800 060 773
This ensures no conductor damage will occur in operation.
VOLTAGE RATING -
Rated Voltage: (multicore control) Uo/U = 380/660V (power) Uo/U = 0.6/1kV - AC test voltage = 2kV * The cable is designated 300/500V in accordance with VDE/IEC and meets or exceeds the Australian Standard AS 3116 for the stated voltage ratings.
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
149
PLANOFLEX
PLANOFLEX
SCREENED CONTROL/DATA CORES Individually screened and twisted screened pair constructions have been developed to enable interference free data/PLC transmission. Screens consist of tinned copper wire braid with 95% coverage with an extruded polymer skin to bond the screen to the insulation and enable greater internal screen protection. Attenuation data for these screened cores at various transmission rates is listed in tables 6.8 and 6.9 on Page 172/173. Integrated fibre optics are also available.
CORE COLOUR IDENTIFICATION Control cables (up to incl. 2.5mm2)
- black cores sequentially numbered, including a green/yellow earth
4 Core 7 Core
- blue, brown, black and green/yellow - black cores sequentially numbered, including a green/yellow earth core
NOTES The 7 core design permits two three phase supplies to be incorporated within a single cable, each circuit sharing the full size earth. For the system design the length of cable required for a festoon is approximately +10% on the total trolley length. For large or fast moving systems the stronger power cables should have a shorter loop depth than the lighter control cables. These types of festoons must always be fitted with tow ropes to limit whiplash and conductor stress on acceleration and braking.
Selection and ordering data Number of Cores x Conductor Size
Part No.
mm
mm2 PLANOFLEX Control Cable
PLANOFLEX Power Cable
150
4 x 1.5 7 x 1.5 8 x 1.5 10 x 1.5 12 x 1.5 24 x 1.5 4 x 2.5 7 x 2.5 8 x 2.5 12 x 2.5 24 x 2.5 4x4 4x6 4 x 10 4 x 16 4 x 25 4 x 35 4 x 50 4 x 70 4 x 95
Sales & Order Processing
Approx. No. of Strands x Max. Strand Diameter
5DG5 711 5DG5 714 5DG5 715 5DG5 717 5DG5 718 5DG5 720 5DG5 721 5DG5 724 5DG5 725 5DG5 728 5DG5 730 5DG5 731 5DG5 741 5DG5 765 5DG5 766 5DG5 767 5DG5 768 5DG5 770 5DG5 771 5DG5 772
Phone 131 773
85 x 0.16
Diameter of Bare Conductor
Fax 1800 060 773
Unenclosed Spaced
Min mm
Max mm
kg/km
A
1.7
5.2 x 14.5 5.2 x 24.5 5.2 x 27.5 5.8 x 35.0 5.8 x 41.0 11.5 x 50.5 6.6 x 19.0 6.6 x 32.0 6.6 x 35.5 7.2 x 53.5 15.0 x 65.5 8.0 x 23.0 8.8 x 25.5 10.0 x 31.5 12.0 x 37.0 13.5 x 44.5 16.0 x 51.5 18.5 x 60.0 21.0 x 68.5 23.5 x 78.0
6.2 x 17.0 6.2 x 27.0 6.2 x 30.5 7.0 x 39.0 7.0 x 45.0 13.5 x 55.5 7.8 x 21.5 7.8 x 35.5 7.8 x 39.5 8.4 x 58.5 17.0 x 72.0 9.4 x 26.0 10.0 x 28.5 12.0 x 35.0 14.0 x 41.0 16.0 x 49.0 18.0 x 56.5 21.0 x 65.5 23.5 x 75.5 26.5 x 85.5
155 265 295 405 480 1010 255 440 495 790 1690 380 490 750 1080 1590 2110 2950 4020 5210
20 20 20 20 20 20 28 28 28 28 28 38 48 66 88 120 145 180 230 285
2.5 2.5
290 x 0.16 190 x 0.21 320 x 0.21 475 x 0.20 741 x 0.20 269 x 0.39 385 x 0.39 546 x 0.39 725 x 0.39
Cable Weight
Max mm
1.7 140 x 0.16
Cable Overall dimension Thickness x Width
2.8 3.5 4.5 5.7 7.1 8.3 9.8 11.4 13.8
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
151
PLANOFLEX
PLANOFLEX
Selection and Ordering Data
Number of Cores x Conductor Size
PLANOFLEX 7 Core Cable
Individually Screened Data Cores and Pairs
Part No.
mm2 7x4 7x6 7 x 10 7 x 16 7 x 25 7 x 35
4 x 1 (c) 4 x (2x1) (c) 12 x 1 (c) 4 x 1.5 (c) 8 x 1.5 (c) 12 x 1.5 (c) 6 x (2x2.5) (c)
Approx. No. of Strands x Max. Strand Diameter
Diameter of Bare Conductor
Cable Overall dimension Thickness x Width
Cable Weight
Unenclosed Spaced
5DG5 734 5DG5 744 5DG5 865 5DG5 866 5DG5 867 5DG5 868
mm 290 x 0.16 190 x 0.21 320 x 0.21 510 x 0.21 780 x 0.21 280 x 0.41
Max mm 3.2 3.9 5.2 6.3 8.0 9.2
Min mm 8.0 x 38.0 8.8 x 42.5 10.5 x 53.5 12.5 x 65.5 15.0 x 77.0 16.5 x 87.5
Max mm 9.4 x 42.0 10.0 x 47.0 12.5 x 59.0 14.5 x 69.6 17.0 x 84.0 18.5 x 96.0
kg/km 655 840 1350 1940 2870 3770
A 38 48 66 88 120 145
5DG5 673 5DG5 890 5DG5 670 5DG5 880 5DG5 884 5DG5 888 5DG5 898
54 x 0.15 54 x 0.15 54 x 0.15 85 x 0.16 85 x 0.16 85 x 0.16 140 x 0.16
1.25 1.25 1.25 1.7 1.7 1.7 2.5
5.2 x 15.5 10.5 x 33.1 6.6 x 48.2 6.9 x 18.5 6.9 x 35.0 7.5 x 52.0 14.8 x 61.5
6.2 x 18.0 12.0 x 35.1 7.1 x 51.5 7.4 x 19.5 7.4 x 38.0 8.0 x 56.0 15.6 x 65.0
150 665 655 250 510 820 1800
16 16 16 20 20 20 28
(c) indicates individually screened cores or twisted screened pairs
152
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
153
OPTOFLEX (M)
OPTOFLEX (M)
Flexible Rubber Sheathed Fibre Optic Cable
CHEMICAL PARAMETERS Resistance to oil -
Given to DIN VDE 0473, Part 811-2-1, Para.10, EN 60811-2-1, IEC 60811-2-1
Weather resistance - Unrestricted use indoors and outdoors, resistant to ozone, UV and moisture.
ATTENUATION DATA
APPLICATION For optical signal and data transmission in open-pit mining applications, for use on material handling equipment and for fixed installation alongside conveyor belts (including mobile conveyor belts).
DESIGN The fibres are enclosed in buffering tube filled with an EFTE natural coloured compound type: 7YI1. The fibres and buffering tube are colour coded for identification of the fibre type. Core arrangement of the six buffering tubes is one layer, specially laid-up around a GFK supporting element (GFK = Glass fibre reinforced plastic). The core arrangement is covered by a special braid consisting of Kevlar threads in a longitudinal lay to increase tensile-strength covering approx. 80% of the surface. The orange outer sheath consists of a 5GM5 PCP compound.
FIBRE-OPTICS The fibre elements are available in the following constructions 50/125 Micron – Graded index fibre 62.5/125 Micron – Graded index fibre E9/125 Micron – Mono mode fibre The inner core diameter of the fibres: 50µm, 62.5µm or 9µm, Diameter over cladding: 125µm. Diameter over coating: 250µm.
Fibre Transmission data Attenuation at 850 nm Attenuation at 1310 nm Attenuation at 1550 nm Bandwidth at 850 nm Bandwidth at 1300 nm Numerical aperture Dispersion value at 1300 nm Dispersion value 1550 nm
50/125
62,5/125
E9/125 Mono mode
2.8 dB/km
3.3 dB/km
-
0.8dB/km
0.9 dB/km
0.4 dB/km
-
-
0.3 dB km
>=400 MHz
>=400 MHz
-
>1200 MHz
>600 MHz
-
0.200 +/- 0.200
0.275 +/- 0.02
0.14 +/- 0,02
-
-
1200 >1200
100 100 100
2000 2000 2000
>600 >600 >600
100 100 100
2000 2000 2000
-
100 100 100 100
2000 2000 2000 2000
Phone 131 773
Fax 1800 060 773
157
OPTOFLEX (F.O)
OPTOFLEX (F.O) ATTENUATION DATA
Fibre Optic Reeling and Festoon Cable
APPLICATION Flexible fibre optic cable for signal and data transmission on cranes and material handling equipment; suitable for cable handling systems, such as reels, festoon systems, cable tenders, etc. High data rates at a large bandwidth have absolute immunity to electromagnetic interference.
DESIGN The fibres are enclosed in a buffering tube filled with an EFTE natural coloured compound type: 7YI1. For identification the fibres and buffering tube are colour coded for identification of the fibre type The six buffering tubes are specially laid-up in one layer around a GFK supporting element (GFK = Glass fibre reinforced plastic). The core arrangement is covered by a special braid consisting of polyester threads covering approx. 80% of the surface. The black outer sheath consists of a 5GM5 PCP compound with a wall thickness of 2.6 mm.
FIBRE-OPTICS The fibre elements are available in the following constructions 50/125 Micron – Graded index fibre 62.5/125 Micron – Graded index fibre E9/125 Micron – Mono mode fibre The inner core diameter of the fibres: 50µm, 62.5µm or 9µm, Diameter over cladding: 125µm. Diameter over coating: 250µm.
CHEMICAL PARAMETERS Resistance to oil Given to DIN VDE 0473, Part 811-2-1 Para.10 Weather resistance - Unrestricted use indoors and outdoors, resistant to ozone, UV and moisture.
158
Sales & Order Processing
Phone 131 773
Fax 1800 060 773
Fibre Transmission data Attenuation at 850 nm Attenuation at 1310 nm Attenuation at 1550 nm Bandwidth at 850 nm Bandwidth at 1300 nm Numerical aperture Dispersion value at 1300 nm Dispersion value 1550 nm
50/125
62,5/125
E9/125 Mono mode
2.8 dB/km
3.3 dB/km
-
0.8dB/km
0.9 dB/km
0.4 dB/km
-
-
0.3 dB km
>=400 MHz
>=400 MHz
-
>1200 MHz
>600 MHz
-
0.200 +/- 0.200
0.275 +/- 0.02
0.14 +/- 0,02
-
-
View more...
Comments