Di1(Si210) Elevator / TCD 191 Meaning [Meaning ]
Duplicated door open/close command c ommand (ER_DOOR_COMMAND) The open&close signals are inputted to DCD PCB at same time
Part: TCD Code Ctrl No.: SI-TS-02-2 Page: 102/117
Trouble Shooting Shoo ting Detection
○ Operation CPU ○ Speed CPU
Application
Si210
[Countermeasures ] 1. Check the voltage of DOC PCB as below
[Explanation ] If the door close &open command are inputted to DCD PCB, it sends an error signal to CP through car communication
When the command occurs
When the command cut
DO-07(open)
0.7V ±0.1V
24V ±10%
DO-06(Close)
0.7V ±0.1V
24V ±10%
2. Check the signals through ANN (2 row-13 & 14 column) 3. Even if the open and close command are cut the voltage is not 24V ±10%, check the followings 1) Remove the DO connector from DOC-131 PCB and proceed the insulation test between 1&2 and earth. 2) If 1) is norm al, replace DOC-131 PCB. 4. Replace DCD-23X PCB
Di1(Si210) Elevator / TCD TCD 192 192 Meaning [Meaning ]
Door oor pos posit itio ion n trou troubl ble e Door position detector error
Part: TCD Code Ctrl No.: SI-TS-02-2 Page: 103/117
Trouble Shooting Shoo ting Detection
○ Operation CPU ○ Speed CPU
Application
[Countermeasures ] ( SAV1 SAV1 Door applied )
[Explanation ] ( SAV1 Door applied ) In case of the trouble of door thermal, under voltage, over voltage & current, TCD192 occurs.
1. Check the door thermal, voltage, current 2. Check the ROM version of DCD-23X PCB (V1.6 ↑) 2. Replace DCD-23X PCB
Si210
Di1(Si210) Elevator / Door voltage trouble(ER_DOOR_VOLTAGE)
TCD 193 Meaning [Meaning ]
Door input voltage error
[Explanation ] Error detected and transmitted to operation CPU when the input voltage of DCD-23X PCB is over or low voltage. 1) Low voltage : under AC 77V (110V -30%) 2) High voltage : over AC 154V (110V +40%)
Part: TCD Code Ctrl No.: SI-TS-02-2 Page: 104/117
Trouble Shooting Shoo ting Detection
○ Operation CPU ○ Speed CPU
Application
Si210
[Countermeasures ]
1. Check the PJ1 connector of DCD-23X PCB. The voltage between PJ1-17 and PJ1-8 is AC 110V±20%. (normal) 2. Above 1 is normal : DCD-23X PCB is troubled 3. Above 1 is abnormal, check below items: 1) Main power voltage is within AC323V~AC418V. (normal) 2) 1) is normal : Control transformer is troubled.
Di1(Si210) Elevator / TCD 194 Meaning [Meaning ]
Door motor thermal trouble (ER_DOOR_MOTOR_THERMAL) Door motor over_heat error
Part: TCD Code Ctrl No.: SI-TS-02-2 Page: 105/117
Trouble Shooting Shoo ting Detection
○ Operation CPU ○ Speed CPU
Application
Si210
[Countermeasures ] 1. Check if the door motor is real heat .
[Explanation ]
Error detected and transmitted to operation CPU when the motor coil temperature is over 130℃.
* Caution : Motor f rame tempe temperature rature is over 100 motor wer e real heat. heat.
when the
2. In case that the door motor is real heat 1) Remove any obstacles to door open/close on car or landing sill. 2) Refer to the countermeasure 1), 2) of TCD 191. 3. In case that the door motor is not real heat. Check if between PJ2-4 and PJ2-5 pins are shortage after power off and disconnecting PJ2 connector from DCD-23X PCB. 1) Shortage: DCD-23X PCB is troubled 2) Open: Motor is troubled.
Di1(Si210) Elevator / TCD 195 Meaning [Meaning ]
Door motor over current trouble(ER_DOOR_OC) Door motor over_current error
[Explanation ]
Error detected and transmitted to operation CPU when the over current flows flows in inverter part .
Part: TCD Code Ctrl No.: SI-TS-02-2 Page: 106/117
Trouble Shooting Shoo ting Detection
○ Operation CPU ○ Speed CPU
Application
Si210
[Countermeasures ] 1. Check the below items (Motor side) after disconnecting PJ2 connector from DCD-23X PCB. 1) Check the isolation of between PJ2-1,2,3 pin and Earth. 2) Check resistance value between PJ2-1 and PJ-2 pin. Value for 50W Door Motor: 17.6Ω±10% Value for 80W Door Motor: 10Ω ±10% 3) Check the resistance as above PJ2-1,3 and PJ-2,3 pin. 4) In case that the test result were not good, motor is troubled 2. If the result is normal, check check below Items after power power off. 1) Check the isolation of between PJ2-1,2,3 pin and Earth. 2) Check the isolation at PJ2-1,2 , PJ2-1,3 and PJ-2,3 pin. 3. Check shortage between DCD-23X & door box frame. 4. Replace DCD-23X PCB.
Di1(Si210) Elevator / TCD 196 Meaning [Meaning ]
Photo-Shoe input error Reopen count by Photo sensor
Part: TCD Code Ctrl No.: SI-TS-02-2 Page: 107/117
Trouble Shooting Shoo ting Detection
○ Operation CPU ○ Speed CPU
Application
[Countermeasures ] 1. Check the photo condition and connection
[Explanation ] If the door is reopened 5 times continuously by photo shoe, it will be display error
Si210
Di1(Si210) Elevator / TCD 199 Meaning [Meaning ]
ER_PCB_Protect_Fail (Korea domestic only) The security approval for PCB is failed. When a DOC or DCL PCB is replaced, it detects error. Or SPEC data is damaged, it also detects an error
[Explanation ]
Whenever a DOC PCB or DCL PCB is replaced in Korea, the security system in CP request serviceman’s ID and approval number. If this requirement requirement is not satisfied, the PCB protection program will not removed. So, its operation shall be locked.
Part: TCD Code Ctrl No.: SI-TS-02-2 Page: 108/117
Trouble Shooting Shoo ting Detection
○ Operation CPU ○ Speed CPU
Application
Si210
[Countermeasures ] 1. If this error is founded in your field, request new PCB. And the wrong PCB that makes TCD199 must be back to manufacturer with claim letter.
Di1(Si210) Elevator / TCD TCD 200 200 Meaning [Meaning ]
Trouble Shooting Shoo ting Detection
CNET CNET LON LON com commu muni nica cati tion on trou troubl ble e DPRAM communication between Main LON and i186 does not operate
Part: TCD Code Ctrl No.: SI-TS-02-2 Page: 109/117
○ Operation CPU ○ Speed CPU
Application
Si210
[Countermeasures ] 1. If the trouble doesn’t disappear after system reset on DOC -131, Check if ROM(OS ROM) of DOC-131 & ROM of main LON are mounted correctly.
[Explanation ]
2. If the trouble doesn’t disappear after performing 1 item above, Replace ROM(OS ROM) of DOC-131 & ROM of main LON.
I186EC_Port3_Input & 0x20
Coil[VALID_186_TOKEN]
3. Replace DOC-131 even if nothing is improved after performing item 2 above. *SYS_INPUT_PORT & 0x10
Coil[VALID_186_TOKEN]
+1
err_count
0x9300
err_count > 5
*SYS_INPUT_PORT & 0x04
[Condition ] LON LED on DOC-131 will light off.
TCD 200
Di1(Si210) Elevator / TCD TCD 202 202 Meaning [Meaning ]
Car LON communication trouble on main OPB( OPB ID = 1 )
[Explanation ] CND_OPB_Node_State CND_OPB_Node_State & 0x01
TCD 202
* TCD 202 is detected on MAIN LON and write in DPRAM. variable of appropriate data is read and saved is CND_OPB_Node_State.
[Condition ] LON LEDs of DOC-131 and DCL-243 are flickering with 1.2 sec. cycle
Trouble Shooting Shoo ting Detection
Car Car com commu muni nica cati tion on trou troubl ble e
Part: TCD Code Ctrl No.: SI-TS-02-2 Page: 110/117
○ Operation CPU ○ Speed CPU
Application
Si210
[Countermeasures ] 1. Check the ON/OFF state of LON LED in DOC-131 (0.06 sec. cycle when normal). 2. Check the ON/OFF state of DCL -243 LED (0.2 sec. cycle when normal). 3. Verify if the connector(SC) for LON com munication is normally connected. 4. Verify if OPB ID is 1 (DIP 1 ‘ON’). 5. Verify if DCL-243 has a term inal resistor(DIP 8) set. 6. Measure the resistance between pins No. 1, 2 of SC c onnector. If it is is approximately 10 OHM, normal. If there is no resistance, check for disconnection. 7. Replace ROM(OS ROM) of DOC-131 & ROM Main LON. 8. Replace DCL-243. 9. Replace DOC-131.
Di1(Si210) Elevator / TCD 209 Meaning [Meaning ]
Trouble Shooting Shoo ting Detection
ER_NPLEX_MASTER_COM
Part: TCD Code Ctrl No.: SI-TS-02-2 Page: 111/117
○ Operation CPU ○ Speed CPU
Application
Communication Error to N-PLEX Module
1. Check if N-plex system is applied or not. (If the system is applied to SPEC data where N-plex is not configured at elevators, it will detect error)
[Explanation ] In case there is non signal reply from N-PLEX Module about 3 seconds more or signal transmitting failure to N-PLEX module 4 times more, it detects an error (TCD209)
G_Signal_Wait_Counter == 0
Group_Fail_Count > 3
TCD 209
Addr
Label
Contents
1D00
Enable
IN-PLEX application, 0x01
1D02
Car ID ID
Lift ID ID un under NN-PLEX (0 (0x01~0x04)
2. Check the N-PLEX communication line. (SH connector) The communication line should be twisted shield cable. 3. Check the terminal resistor setting (HJP-SH jumper must be connected)
※ See the N-plex manual for terminal resistor setting
[Condition ]
Si210
※ If terminal resistor is not properly set, following
condition may happen - Communication failure is happened frequently and hall call registration is impossible. - Lift goes under back-up operation (ACD=26) (ACD=26)
Di1(Si210) Elevator / TCD TCD 211 211 Meaning [Meaning ]
Othe Otherr ele elev vator ator trou troubl ble e Communication error with other car is detected in duplex operation.
[Explanation ] 1. In duplex, In case there is no transm ission data for 1 sec. from other elevator, the trouble occurs. 2. When G/A transmission from other is f ailed 4 times in series, the trouble occurs.
Part: TCD Code Ctrl No.: SI-TS-02-2 Page: 112/117
Trouble Shooting Shoo ting ○ Operation CPU ○ Speed CPU
Detection
Application
Si210
[Countermeasures ] 1. In case of duplex, No.1 of the SPEC1(DIP S/W ) must be on. In case of simplex, it must be off. 2. Check the condition of communication line between 2 elevators. The communication line must be a shield wire. 3. Check if terminal resistor(HJP-SH Jumper) is is connected.
No.1 SH(HJP) SH
No.1
No.2
SL
SH(HJP) SL
SH
SH(HJP) SH
SL
No.2 SH(HJP) SL
SH
DHG-162
DHG-162
DHG-162
DHG-162
DHG-162
DHG-162
DHG-162
DHG-162
DHG-162
Di1(Si210) Elevator / TCD TCD 217 217 Meaning [Meaning ]
Trouble Shooting Shoo ting Detection
Hall Hall butt button on jam jam det detec ecti tion on When hall button is being pushed continuously, the trouble is detected.
Part: TCD Code Ctrl No.: SI-TS-02-2 Page: 113/117
○ Operation CPU ○ Speed CPU
Application
[Countermeasures ] 1. Check the floor where button jam is detected. The floor can be check ed by ‘A21E’.
[Explanation ]
2. If abnormal, replace the button.
When hall button is being pushed for the time(Default :180 sec.) that is designated by SPEC, TCD 217 will occur. Button_Jam_Detect[0][UP_INDX]
TCD 217
Button_Jam_Detect[0][DN_INDX]
The floor button Jam detected Address
Floor
0x9954
1st floor ~ 8th floor UP Button
0x9955
9th floor ~ 16th floor UP Button
0x9956
17th floor ~ 24th floor UP Button
0x9957
25th floor ~ 32nd floor UP Button
0x9958
1st floor ~ 8th floor DOWN Button
0x9959
9th floor ~ 16th floor DOWN Button
0x995A
17th floor ~ 24th floor DOWN Button
0x995B
25th floor ~ 32nd floor DOWN Button
Each floor is matched with each Bit.
Si210
Di1(Si210) Elevator / TCD 22 223
Trouble Shooting Shoo ting Detection
Hall CP CPU tr trouble
Meaning [Meaning ] 1 or more communication trouble on Hall Station B/D, detected.
Part: TCD Code Ctrl No.: SI-TS-02-2 Page: 114/117
○ Operation CPU ○ Speed CPU
Application
Si210
[Countermeasures ] 1. Check the floor of communication not activated by ANN - A21E and the type type of button to check DHG-162 of the failed floor for failure.
[Explanation ] HND_Fail_Node[ 0 ]
TCD 223
0x8762
* HND_Fail_Node : 4Byte( 32bit 32bit )
[Checking of hall button trouble] Enter as below on annunciator K: A21E ADDR:DAT K : 8762E If 8762=x02(0000 0010) DFG-16X of 2nd floor is failure. If 8762 =x30(0011 0000) DHG-162 of 5th, 6th floors are failure. To see floor 8th or higher is required to enter KEY-PAD KEY-PAD ‘0’ of annunciator.
Address
Floor
0x8762
1st floor ~ 8th floor
0x8763
9th floor ~ 16th floor
0x8764
17th floor ~ 24th floor
0x8765
25th floor ~ 32nd floor
Each floor is matched with each Bit. Ex) ADDR:0x8762 - DATA:0x04 means 3rd floor is out of order. order.
2. Verify if controller DOP PCB XHA MIC is connected, and see if voltage between HA plug pin 3-4 of DHG-162 at failed floor is DC24V. 3. Verify if the ID of DHG-162 at failed floor is set correctly. 4. Resistance between HA connector pin1-2 in DHG-162 at the failed floor must be 2±0.5Ω. 0.5Ω. If not so, the pulse transformer(PT1, position in DHG-162) in DHG-162 is a failure. 5. Check between pin 3-4 of HA connector in DHG-162 at t he failed floor. if it is open circuit, replace DHG -162.
Di1(Si210) Elevator / TCD TCD 224 224
Meaning [Meaning ] Communication error with all floor in hall line is detected
NCD_P_SVC_Fl[ 0 ]
check_floor
○ Operation CPU ○ Speed CPU
Application
Si210
[Countermeasures ]
[Explanation ]
Normal_Floor[ 0 ]
Trouble Shooting Shoo ting Detection
Hall Hall nod nod tro troub uble le (All (All))
Part: TCD Code Ctrl No.: SI-TS-02-2 Page: 115/117
check_floor
TCD 224
H_Data_Receive_Wait_Counter == 0
[Condition ] When TCD224 occurs, operation mode would be ACD26 and perform backup operation.
1. Check if the jumper(HJP-SH) of DOC -131 is set correctly. 2. Check if XHA MIC of DOP PCB is connected. 3. Check if SH connector of DOC-131 is connected. 4. Check if terminal resistor(120) in diverging box at bottom floor is connected. 5. Check if the volt of XHA MIC of DOP PCB is DC24V after removing XHA MIC . 1) 1th ~ 8th floor: XHA 3-4 is to be DC24V. 2) 9th ~ 16th floor: XHA 5-6 is to be DC24V. 3) 17th ~ 24th floor: XHA 7-8 is to be DC24V. 4) 25th ~ 32th floor: TB2 (Terminal Block) 5-6 is to be DC24V.
Di1(Si210) Elevator / TCD TCD 237 237
Meaning [Meaning ] When communication error between CRT & CP occurs
○ Operation CPU ○ Speed CPU
Application
Si210
[Countermeasures ] 1. Check if CRT option is applied. (When SPEC has CRT option even if a project does not apply for CRT, the trouble will occur)
[Explanation ] In case that there is no receive data from CRT for 8 sec., TCD237 would be occurs.
CRT_Comm_Error_Counter CRT_Comm_Error_Counter == 0
Trouble Shooting Shoo ting Detection
CRT CRT com commu muni nica cati tion on trou troubl ble e
Part: TCD Code Ctrl No.: SI-TS-02-2 Page: 116/117
TCD 237
Crt_Id ADDR:0x0002 Crt_Operation ADDR:0x0020 2. Check if the connection between CRT & CP is correct. (SM connector) Communication cable should be twisted & shielded. 3. Check if HJP-SL jumper is connected.
Di1(Si210) Elevator / TCD 240
Meaning [Meaning ] When elevator stops a floor, a landing door at another floor is opened Then, it detects an error (Russia code area only)
[Explanation ] The elevator will be stop immediately under normal operation mode, the error is hold until the main power is turned off. It does not detects t his error under inspection mode.
Normal Mode
VI_OPZX 803C
Trouble Shooting Shoo ting Detection
ER_RUSSIA_OPZX
TCD240
Part: TCD Code Ctrl No.: SI-TS-02-2 Page: 117/117
○ Operation CPU ○ Speed CPU
Application
Si210
[Countermeasures ] 1. Check if the Russia c ode application 1) In case of Si210, The following 2 options effect on this error 2) In case of Si25x and Si23x, Russia code(0042) effects on this error Addr
Label
Contents
0042
Russia
Russia code application, 0x 0x01
07CA
OPZX
Landing do door de detection fu function application, 0x01
2. Check the input buffer ( 0x803C)and voltage level at connector. Normal : Input buffer is is 0x00, Voltage level is 48V(24V-Si25x). 48V(24V-Si25x). Error : Input buffer is 0x01, Voltage level level is 0V In case of Si25X, Check the DOX-100 PCB의 PCB의 connection 3. Check the each landing door condition. 4. This error can be erased by power reset in CP.