Download Short Circuit Lecture Using EDSA ETAP PSSE Matlab...
Description
Analysis of Faulted Power System (Shunt Fault)
Sequence Model for Transformer
Roel B. Calano
Sequence Model for AC Generator Generator Connection Diagram
Zero Sequence Network Diagram
a Z0 c Z0 Z0
Z0 N0 b
a Z0 c Z0 Z0
3Zn Zn Z0
N0 b
a
Z0
c Z0 Z0
N0
Z0 b
Sequence Networks
One of the most useful concepts about the symmetrical components is the sequence network. A sequence network is an equivalent network for power system under the assumption that only one sequence component of voltages and currents is presented in the system. There will be no interaction between each sequence network and each of them is independent of each other. The positive sequence network is the only one containing voltage source since generators produce only voltages of positive sequence. Negative and zero sequence networks contain only their corresponding impedances and these impedances are obtained based on the location of the fault under investigation. These sequence networks are shown in Figure. The types of fault conditions will determine the connections between the sequence networks. The positive sequence impedance, Z1, is the impedance looking into the positive sequence network from the fault point. Similarly, the negative sequence impedance, Z2, is the impedance looking into the negative sequence network from the fault point, and the zero sequence impedance, Z 0, is the impedance looking into the zero sequence networks from the fault point.
Example: Draw the Zero sequence network of the power system shown ∆
Y grounded - Y grounded
-∆
G
G
Y grounded
Reactance grounded
Y grounded - Y grounded
∆
-∆
Solution:
j0.2
2
3
j0.3
1
j0.06
j0.3
4
j0.25
5
j0.5
j0.06j0.35
6 j0.09
N0 (Neutral or Zero-potential bus)
Example: Draw the Zero sequence network of the power system shown Y ungrounded - Y grounded
Y ungrounded - Y ungrounded
G
G
Reactance grounded
Y ungrounded
Y ungrounded - Y ungrounded
∆
-∆
Solution:
j0.2
j0.06
j0.25
j0.3
j0.3
j0.5
j0.35
j0.06
j0.09
N0 (Neutral or Zero-potential bus)
∆
Y grounded- Y grounded
-∆
G
G
Y ungrounded
Reactance grounded
∆
Y grounded - Y grounded
∆
Y ungrounded - Y grounded
- Y ungrounded
-∆
G Y grounded 2
j0.2
3
j0.3
1
j0.06
j0.3
4
j0.35
j0.25
5
6
j0.5 j0.09
j0.09
j0.09
j0.09
N0 (Neutral or Zero-potential bus) B
B
j0.06
j0.09
∆
Y grounded - Y grounded
- Y ungrounded
Y ungrounded
G
G
∆
- Y grounded
∆
Y ungrounded - Y grounded
∆
- Y grounded
G
2
-∆
Solidly grounded
3
1
4
5
6
N0 (Neutral or Zero-potential bus) B
B
Problem: Draw the Positive, Negative and zero sequence model for the power system shown.
∆
Y grounded - Y grounded
-∆
1
4 3
2
G
G 5
6 Reactance grounded
Y grounded
Y grounded - Y grounded
∆
∆
∆
- Y grounded
-∆
- Y grounded
G
G
∆
- Y grounded
∆
∆
∆
- Y grounded
G
- Y grounded
- Y grounded
Solution:
Reactance Diagram Simplification
2
j0.2
3
j0.15
1
4
j0.2
j0.25
j0.22
5 G
j0.3
j0.2j0.35
6
1.0 angle 0°
G
N1 (Neutral or Zero-potential bus)
2
j0.2
3
j0.15
1
j0.14
j0.3
4
j0.25
j0.22
5
j0.14 j0.35
6
N2 (Neutral or Zero-potential bus)
2
j0.2
3
j0.3
1
j0.06
j0.3
4
j0.25
5
j0.5
j0.06j0.35
6 j0.09
N0 (Neutral or Zero-potential bus) B
B
1.0 angle 0°
Positive Sequence Network j0.35
j0.3
3
1
4
j0.2
G
j0.82
j0.2
1.0 angle 0°
G
1.0 angle 0°
N1
3
3
j0.0.0714
j0.0.0714 4
1 j0.1952
j0.1673 j0.2
j0.2
G
1.0 angle 0°
1.0 angle 0°
j0.3673
j0.3952
G
G
N1
1.0 angle 0°
1.0 angle 0°
G
N1
3
3
3 j0.0.0714
j0.0.0714
j0.0.2618
j0.3952
j0.3952
j0.3673
j0.1904
1.0 angle 0° 1.0 angle 0°
G
1.0 angle 0°
G
G N1
N1 B
N1 B
B
B
Negative Sequence Network j0.35
j0.3
3
1
4
j0.14
j0.82
j0.14
N2
3
3
j0.0.0714
j0.0.0714 4
1 j0.1952
j0.1673
j0.14
j0.3073
j0.3352
j0.14
N2
N2
3
3
3 j0.0.0714
j0.0.0714
j0.0.2317
j0.3352
j0.3952
j0.3073
j0.1603
N2 N2 B
N2 B
B
B
Zero Sequence Network
2 j0.3
j0.2
3 3
j0.06 j0.0.56
N0
N0
Problem:
Draw the connection diagram of Positive, Negative and Zero sequence network of the 4 bus shown.
G
G ∆
- Y grounded
∆
- Y grounded
Short Circuit Current under Transient Condition
G
G
Three Phase Symmetrical Symmetrical Fault
G
Consider a Three phase Fault occurs near the terminal of the generator
e= VS sin (ωt + α) α
Derivation of Short Circuit Current under Transient Condition VR + VL = VS Ldi
From the given equation it can be seen that the short circuit current has two component, the transient current which decays with respect to time ( at time = infinity) and the steady current.
Transient Analysis of Three Phase Short Circuit Three Phase Short Circuit at Phase a
Three Phase Short Circuit at Phase b
Three Phase Short Circuit at Phase c
Three Phase Short Circuit at the Field
Line to Line Short Circuit at Phase b
Line to Line Short Circuit at the field
Line to Ground Short Circuit at Phase a
Line to Ground Short Circuit at the Field
Different Level of Short Circuit Current with respect to time
Difference between Symmetrical and Unsymmetrical Fault
Symmetrical
Unsymmetrical
Short Circuit Current near the Generator
Example: Draw the wave form of short circuit current of different ωL/R and power factor angle Solution: ωL/R program
Important Notes when Conducting Short Circuit Analysis • • • • • •
• •
The Three Sequence are independent The positive-sequence network is the same as the one line diagram used in studying balanced three-phase current and voltages The Positive-sequence network has a voltage source. Therefore, the positivesequence current causes only positive-sequence voltage drops There is no voltage source in the negative or zero sequence networks Negative and Zero sequence currents cause negative and zero sequence voltage drops only The Neutral of the System is the Reference for positive and negative sequence networks, but ground is the reference for the zero sequence networks. Therefore, the zero sequence current can flow only if the circuit from the system neutrals to ground is complete The grounding impedance is reflected in the zero sequence network as 3 Z 0 The threes sequence systems can be solved separately on a per phase basis. The phase currents and voltages can be determined by superposing the symmetrical components of current and the voltages respectively.
Simplifications
When computing short circuits in a power system further simplifications can be made. The following simplifications are also used for the analysis
•
All line capacitances are ignored.
•
All non-motor shunt impedances are ignored; motor loads are treated the same way as generators.
•
The voltage magnitude and phase angle of generators and in feeds are all set to the same value
•
All tap changing transformers are in middle position.
These simplifications are indicated for studies regarding medium- and long-term network planning. In the planning stage, the calculations are based on estimated and hence inaccurate data. Therefore, the demands on the short circuit computation algorithm are lower than for real-time applications in the network operation, where accurate results are desired. Studies have shown that the shunt elements and loads have little influence on the short circuit currents (0.5%. . . 4%) and may compensate each other. However, disregarding the actual generator pole voltages and the actual positions of tap changing transformers may sometimes lead to errors of up to 30%.
Thank you for interesting in our services. We are a non-profit group that run this website to share documents. We need your help to maintenance this website.