Shelter Alarms

October 23, 2017 | Author: Eric Gruschow | Category: N/A
Share Embed Donate


Short Description

Alarm configuration...

Description

6201 OVP Alarm #

Ericsson Alarm Script

Alarm Means

1 2 3 4

RBS DC MJ) RBS DC MN RBS COMMERCIAL POWER FAIL RBS DC DIST BREAKER FUSE FAIL

Power Plant Major Fault Power Plant Minor Fault AC Power Failure Fuse, Circuit Breaker or Battery Disc

5 6 7 8

RBS BATT ON DISCHARGE RBS SMOKE RBS INTRUSION RBS HVAC #1 FAIL

Site is Running on Batteries Fire or smoke in building Buiding Door Open Heating or Cooling system Failure

9 10 11 12

RBS HVAC #2 FAIL RBS HYDROGEN GAS RBS HIGH TEMPERATURE RBS LOW TEMPERATURE

Heating or Cooling system Failure Hydrogen Gas Leak High Temperature Low Temperature

13 14 15 16

For Future Growth For Future Growth For Future Growth For Future Growth

17 18 19 20

For Future Growth For Future Growth For Future Growth For Future Growth

21 22 23 24

For Future Growth For Future Growth For Future Growth For Future Growth

25 26 27 28

For Future Growth For Future Growth For Future Growth For Future Growth

29 30 31 32

For Future Growth For Future Growth For Future Growth For Future Growth

*ERICSSON RJ45 ALARM PIN CONNECTIONS Use installed 1st Alarm 2nd Alarm 3rd Alarm 4th Alarm

66 block pair 1 66 block pair 2 66 block pair 3 66 block pair 4

CRITICAL CRITICAL MINOR MAJOR

NC NC NC NC

OVP1 A5 OVP1 A6 OVP1 A7 OVP1 A8

Building Alarm Building Alarm Building Alarm Building Alarm

66 block pair 5 66 block pair 6 66 block pair 7 66 block pair 8

MAJOR CRITICAL CRITICAL MAJOR

NC NC NC NC

OVP2 A1 OVP2 A2 OVP2 A3 OVP2 A4

Building Alarm Building Alarm Building Alarm Building Alarm

66 block pair 9 66 block pair 10 66 block pair 11 66 block pair 12

NC NC NC NC

OVP2 A5 OVP2 A6 OVP2 A7 OVP2 A8

Building Alarm Building Alarm Building Alarm Building Alarm

66 block pair 13 66 block pair 14 66 block pair 15 66 block pair 16

NC NC

OVP3 A1 Building Alarm 66 block pair 17 OVP3 A2 Building Alarm 66 block pair 18 OVP3 A3 OVP3 A4

OVP4 A1 OVP4 A2 OVP4 A3 OVP4 A4

Alarm Inputs 25-28

OVP4 A5 OVP4 A6 OVP4 A7 OVP4 A8

Alarm Inputs 29-32

OVP3 A5 OVP3 A6 OVP3 A7 OVP3 A8

M PIN CONNECTIONS Use these if no OVP installed PIN PIN (-) (Common/Return) 5 4 2

1

6

3

8

7

Alarm Inputs 5- Alarm Inputs 18 4

Building Alarm Building Alarm Building Alarm Building Alarm

Alarm Inputs 9-12

OVP1 A1 OVP1 A2 OVP1 A3 OVP1 A4

Alarm Inputs 13-16

NC NC NC NC

RBS SAU RJ48 Alarm Jack

Alarm Inputs 17-20

MAJOR MAJOR CRITICAL MAJOR

Connects to LEFT SIDE of Building Alarm 66 Block

Alarm Inputs 21-24

Severity

Alarm Type NO/NC

Connects To RBS alarm Terminals , if Installed*

6601 OVP Alarm #

Ericsson Alarm Script

Alarm Means

Severity

1 2 3 4

RBS INTRUSION RBS TEMP OUT OF RANGE RBS HVAC FAIL RBS DC MN

Buiding Door Open Building HighTemp (Low not connected) Heating or Cooling system Failure Power Plant Minor Fault

MINOR CRITICAL MAJOR MAJOR

5 6 7 8

RBS DC MJ RBS SMOKE RBS PWR AC SPD RBS COMMERCIAL POWER FAIL

Power Plant Major Fault Fire or smoke in building Surge Protector Failure-AC AC Power Failure

MAJOR CRITICAL MAJOR CRITICAL

9 10 11 12

RBS LNA FAIL RBS GENERATOR RUNNING RBS GENERATOR FAIL RBS TOWER LIGHT FAIL

RXAIT or TMA Failure (SCPA GSM*) Generator Running Generator Fault and or Low Fuel Tower Light Beacon Failure

MAJOR MAJOR MAJOR MAJOR

13 14 15 16

RBS SIDE LIGHT FAIL RBS CCIC TWR LIGHT SUMM RBS LTE RRU AT DC SYS SPD RBS MW FAIL

Tower Sidelamps Failure Crown Site Tower Light Failure Raycap surge arrestor alarm Microwave or Misc System Failure

MAJOR MAJOR MAJOR MAJOR

17 18 19 20

RBS HYDROGEN DETECTED RBS SMOKE RBS HUMIDITY HIGH RBS BATT ON DISCHARGE

Hi Levels of Hydrogen Gas detected Fire or smoke in building Building High Humdity Site is Running on Batteries

21 22 23 24

For Future Growth For Future Growth For Future Growth For Future Growth

25 26 27 28

For Future Growth For Future Growth For Future Growth For Future Growth

29 30 31 32

For Future Growth For Future Growth For Future Growth For Future Growth

CRITICAL CRITICAL MAJOR CRITICAL

*ERICSSON RJ45 ALARM PIN CONNECTIONS Use these if no OVP installed PIN (-) 1st Alarm

5

nd

Alarm

2

3

rd

Alarm

6

4

th

Alarm

8

2

NC NC NC NC

OVP1 A5 OVP1 A6 OVP1 A7 OVP1 A8

Building Alarm Building Alarm Building Alarm Building Alarm

66 block pair 5 66 block pair 6 66 block pair 7 66 block pair 8

NC NC NC NC

OVP2 A1 OVP2 A2 OVP2 A3 OVP2 A4

Building Alarm Building Alarm Building Alarm Building Alarm

66 block pair 9 66 block pair 10 66 block pair 11 66 block pair 12

NC NC NC NC

OVP2 A5 OVP2 A6 OVP2 A7 OVP2 A8

Building Alarm Building Alarm Building Alarm Building Alarm

66 block pair 13 66 block pair 14 66 block pair 15 66 block pair 16

NC NC NC NC

OVP3 A1 OVP3 A2 OVP3 A3 OVP3 A4

Building Alarm Building Alarm Building Alarm Building Alarm

66 block pair 17 66 block pair 18 66 block pair 19 66 block pair 20

OVP3 A5 OVP3 A6 OVP3 A7 OVP3 A8

Building Alarm Building Alarm Building Alarm Building Alarm

66 block pair 21 66 block pair 22 66 block pair 23 66 block pair 24

OVP4 A1 OVP4 A2 OVP4 A3 OVP4 A4

Alarm Inputs 25-28

OVP4 A5 OVP4 A6 OVP4 A7 OVP4 A8

Alarm Inputs 29-32

NECTIONS Use these if no OVP d PIN (Common/Return) 4 1 3 7

Alarm Inputs 5- Alarm Inputs 18 4

66 block pair 1 66 block pair 2 66 block pair 3 66 block pair 4

Alarm Inputs 9-12

Building Alarm Building Alarm Building Alarm Building Alarm

Alarm Inputs 13-16

OVP1 A1 OVP1 A2 OVP1 A3 OVP1 A4

RBS SAU RJ48 Alarm Jack

Alarm Inputs 17-20

NC NC NC NC

Connects to LEFT SIDE of Building Alarm 66 Block

Alarm Inputs 21-24

Alarm Type NO/NC

Connects To RBS alarm Terminals , if Installed*

Building End Device Wire Points and connects to RIGHT SIDE of Alarm 66 Block Door Switch Hi Temp Thermostat HVAC system Power Plant Alarms Power Plant Alarms Smoke Alarm AC Panel Surge Protector AC Fail Relay CCI RXAIT's & TMA PDU's in Series* Generator Generator, wire low fuel in series if not annuciated with common fault Tower Light Controller Tower Light Controller Crown Castle Tower Alarm Box Raycap Surge Arrestor Rear TB NC & COM Microwave System Hydrogen Gas Detector Smoke Alarm Humidistat Power Plant Alarms

View more...