A L A R M / T R I P S E T T ISN G Description Fuel Gas Temperature High
Alarm
GT-1/2
GT-3/4
GT-5/8
GT-13/14
NA
NA
NA
N.A
NA
NA
Alarm = NIL
N.A
Trip Fuel Gas Temperature low during running Alarm
TRIP = < 11°C Trip Fuel Gas Temperature Low during start Start inhibit MVAR –ve Maximum +ve Maximum Electronic Over Speed Trip Generator Over Voltage Generator circuit breaker open
Generator Over Frequency (HZ) C/B Open Generator under frequency (HZ )C/B Open
NA
NA
-40
-40
+60 3300 Mech 3170 Elect
+60 3300 Mech 3200 Elect
120%
120%
=12.6 KV
=13.2 KV
51.5Hz
______
47.5Hz
47.5Hz
Could be < 11°C but not specifically -45
N.A
+60
+123
3360 Mech 3300 Elect 13.8KV for 3.6 sec
3233 rpm Elect 12.8KV Alarm
Low voltage 8.28KV for 2.8 sec
13.2KV trip
-75
____________ 47.75 Hz for 6 sec
48.5 Alarm 47.5 HZ
Generator Over Current Circuit breaker open
CT 600/1 30% of generator rated current
CT 800/1 30% of generator rated current
CT 7500/1 112% 8400 Amp
1.4 IN time for 2.8 sec
LSFO Temperature Low during running machine change over on HSD. LSFO Temperature high during running