SERVICE Luna Platinum Ed 8
Short Description
service manual for BAXI Nuvola Platinum...
Description
PCB PARAMETRIZATION
Instr ns truc ucti tion ons s for fo r SERVICE UPDATES: 20/08/ 20/08/201 2012 2 2°edi 2°editi tion on
PCB sof tw are versio vers ion n V3.5.0 V3.5.0-89 -89 or hig her
CONTENTS
1
CONTROL PANEL MENU .................................................................................................................................... 3 1.1
ENGINEER MENU .......................................................... ........................................................... ....................... 3
2
PARAMETER LIST ................................................................................................................................................ 4
3
ERROR LIST ......................................................................................................................................................... 28
4
GAS ADAPTIVE SYSTEM .................................................. ........................................................... ..................... 33
5
FAULT FINDING ......................................................... ........................................................... ............................... 34
6
BURNER PHASE (FAULT HISTORY) ............................................................................................................. . 54
1
CONTROL CONTROL PANEL MENU
The following procedure is used to access the four boiler pro- gramming menus: • from the main menu C; • A e C for approx. 6 seconds; • B to see menus 1 - 2 - 3 - 4; • B to confirm the selected menu; • C to go back one menu at a time to the main menu.
The four menus are: 1 ENDUSER 2 COMMISSIONING 3 ENGINEER 4 OEM
1.1
(visible pressing the button C) (visible with a buttons combination) (visible only with PASSWORD 10101) 10101) (visible only with PASSWORD)
ENGINEER ENGINEER menu men u
Access Engineer menu menu as described in section 1. This level includes all parameters present on Enduser and Commissioning menus. The details of this menu are given in next section. Some menus are avaible only if the system is correctly configured (e.g. solar menu). The parameters with grey underlight are different default values depending on boiler model.
2
PARAMETER LIST Parameter
Level 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Parameter
INFORMATION Room temperature Room temperature min Room temperature max Boiler temperature Outside temp Outside temp min Outside temp max Instant HW heater temp State central heating CH1 State central heating CH2 State central heating CH3 State hot water State boiler State SithermPro Telephone customer service
Displayed if the heating circuit is activated Displayed if the heating circuit is activated
Only with LMS15 pcb
Level
1 2 3 5 6
1 1 1 3 3
Parameter
SET TIME AND DA TE
Def au l t
OPERATOR SECTION
Def au l t
Hours / minutes Day / month Year Start of summertime End of summertime
Level
20
1
Change Language
24
2
Lighting
26
3
Operation lock
27
1
Programming lock
29
2
Units
40
2
Used as
42
2
Assignment device 1
43
2
Action operation
54 70
2 2
Readjustment room sensor Software version
Parameter
Off Temporarily Permanently On Off On Off 1 °C , bar 2 °F , PSI Operator unit 1 Room unit 1 Room unit 2 Room unit 3 Temps / mode CH1 Central heating 1 and 2 Central Heating 1 and 3 All central heatings 0 Locally 1 Centrally -3°C…+3°C
Block of the control panel buttons A e B The parameters can be displayed but not changed
The control panel is installed in the boiler The control panel is configured as room unit of heating circuit 1 The control panel is configured as room unit of heating circuit 2 The control panel is configured as room unit of heating circuit 3 As room unit 1, the action of the respective control panel can be assigned to heating circuit 1 or to 2 heating circuits. The room unit controls only the respective heating circuit. Only room unit 1 can be Centrally. It also controls dhw mode and standby.
Level
WIRELESS
120 121 130
2 2 2
Binding Test mode Room unit 1
Activation of wireless link with basic unit Test mode is used for checking the wireless communication Check of link
131 132 133 134 135 140
2 2 2 2 2 2
Room unit 2 Room unit 3 Outside sensor Repeater Operator unit Delete all devices
Check of link Check of link Check of link Check of link Check of link
Parameter
Level
TIME CENTRA L HEATING 1 – 2 – 3
1 500 514 501 502 503 504 505 506
2 520 534 521 522 523 524 525 526
3 540 554 541 542 543 544 545 546
1
Select days
Selection of days or groups of days for time program
1 1 1 1 1 1 1
Select default timings? 1st Time ON 1st Time OFF 2nd Time ON 2nd Time OFF 3rd Time ON 3rd Time OFF
Is it possibile to select up to 3 preselect time programs
516
536
556
1
Default values
Parameter
TIME HOT WATER
1 1 1 1 1 1 1 1
Select days Select default timings? 1st Time ON 1st Time OFF 2nd Time ON 2nd Time OFF 3rd Time ON 3rd Time OFF
576
1
Default values
Default Defau lt
Yes No
Level
TIME AUXILIARY
1 1 1 1 1 1 1 1
Select days Select default timings? 1st Time ON 1st Time OFF 2nd Time ON 2nd Time OFF 3rd Time ON 3rd Time OFF
616
1
Default values
Yes No
Level
Def au l t
Selection of days or groups of days for time program Is it possibile to select up to 3 preselect time programs
600 614 601 602 603 604 605 606
Parameter
Default
Yes No
Level
560 574 561 562 563 564 565 566
Parameter
Default
Displayed if the control panel is configured as room unit Displayed if the control panel is configured as room unit Displayed if the control panel is configured as room unit
Default
Selection of days or groups of days for time program Is it possibile to select up to 3 preselect time programs
HOL IDA Y HEA TING 1 – 2 – 3
1 641 642 643
2 651 652 653
3 661 662 663
1
Select
Is it possibile to select up to 8 holiday periods
1 1
Start End
648
658
668
1
Operating level
Day and month of holiday start Day and month of holiday end Off Reduced
Def au l t
131 132 133 134 135 140
2 2 2 2 2 2
Parameter
Room unit 2 Room unit 3 Outside sensor Repeater Operator unit Delete all devices
Check of link Check of link Check of link Check of link Check of link
Level
TIME CENTRA L HEATING 1 – 2 – 3
1 500 514 501 502 503 504 505 506
2 520 534 521 522 523 524 525 526
3 540 554 541 542 543 544 545 546
1
Select days
Selection of days or groups of days for time program
1 1 1 1 1 1 1
Select default timings? 1st Time ON 1st Time OFF 2nd Time ON 2nd Time OFF 3rd Time ON 3rd Time OFF
Is it possibile to select up to 3 preselect time programs
516
536
556
1
Default values
Parameter
Yes No
Level
TIME HOT WATER
560 574 561 562 563 564 565 566
1 1 1 1 1 1 1 1
Select days Select default timings? 1st Time ON 1st Time OFF 2nd Time ON 2nd Time OFF 3rd Time ON 3rd Time OFF
576
1
Default values
Parameter
Yes No
Level
TIME AUXILIARY
1 1 1 1 1 1 1 1
Select days Select default timings? 1st Time ON 1st Time OFF 2nd Time ON 2nd Time OFF 3rd Time ON 3rd Time OFF
616
1
Default values
Yes No
Level
Default Defau lt
Selection of days or groups of days for time program Is it possibile to select up to 3 preselect time programs
600 614 601 602 603 604 605 606
Parameter
Def au l t
Default
Selection of days or groups of days for time program Is it possibile to select up to 3 preselect time programs
HOL IDA Y HEA TING 1 – 2 – 3
1 641 642 643
2 651 652 653
3 661 662 663
1
Select
Is it possibile to select up to 8 holiday periods
1 1
Start End
648
658
668
1
Operating level
Day and month of holiday start Day and month of holiday end Off Reduced
Def au l t
2463
3
Settling time HW
2670
3
Parameter
2672 2675 2681 2682
3 3 3 3
Parameter Parameter Parameter Parameter
Parameter
3 3 3 3
Ion current filtered Position stepper motor Learning value gas quality Operating phase
2720
2
Release sel type of gas
2721
2
Type of gas
2725
3
Sel individual boiler setting
2726 2729
3 3
Ind boil setting ion curr LF Ind boil setting ion curr HF
2740
3
Triggering drift test
2741 2742 2743 2744 2745 2746 2747 2748 2749
3 3 3 3 3 3 3 3 3
Parameter Parameter Parameter Parameter Parameter Parameter Parameter Parameter Reset drift test
3510
SITHERM PRO
Default
Ionization current actual value Gas valve stepper motor position Gas calorific power measurement Release of ga type selection: 0 Off 1 On Type of gas: 1 Natural gas 2 Liquefied gas Activation of combustion adjustment: Off Set low-fire ion current Activation of correction at low power Save low-fire ion current Stored of correction at low power Set high-fire ion current Activation of correction at high power Save high-fire ion current Stored of correction at high power Setting of correction at low power Setting of correction at high power Manual test of combustion adjustment: 0 Disabled 1 Test done at high and low power 2 Test done only at high power 3 Test done only at low power 4 Test done at high and low power alternatively for 3 times Last test result at low power Last test filtred result at low power Correction at low power Threshold of correction at low power Last test result at high power Last test filtred result at high power Correction at high power Threshold of correction at high power Reset of correction results
CASCADE Lead strategy
On
Precirculation time on DHW way (3WV position) during precirculation function Precirculation time on CH way (3WV position) during precirculation function
Level 3
1min
30°C Table1 Table1 Table1
L e v el
2700 2702 2703 2706
Parameter
Validity time of parameter 2462 Activation of Super Over Temperature Function (SOT): On Off Increase of boiler setpoint for the control of SOT
Lead strategy:
Off Natural gas
Off
0uA 0uA
0
No Default Late on, late off
2463
3
Settling time HW
2670
3
Parameter
2672 2675 2681 2682
3 3 3 3
Parameter Parameter Parameter Parameter
Parameter
3 3 3 3
Ion current filtered Position stepper motor Learning value gas quality Operating phase
2720
2
Release sel type of gas
2721
2
Type of gas
2725
3
Sel individual boiler setting
2726 2729
3 3
Ind boil setting ion curr LF Ind boil setting ion curr HF
2740
3
Triggering drift test
2741 2742 2743 2744 2745 2746 2747 2748 2749
3 3 3 3 3 3 3 3 3
Parameter Parameter Parameter Parameter Parameter Parameter Parameter Parameter Reset drift test
3510
SITHERM PRO
Default
Ionization current actual value Gas valve stepper motor position Gas calorific power measurement Release of ga type selection: 0 Off 1 On Type of gas: 1 Natural gas 2 Liquefied gas Activation of combustion adjustment: Off Set low-fire ion current Activation of correction at low power Save low-fire ion current Stored of correction at low power Set high-fire ion current Activation of correction at high power Save high-fire ion current Stored of correction at high power Setting of correction at low power Setting of correction at high power Manual test of combustion adjustment: 0 Disabled 1 Test done at high and low power 2 Test done only at high power 3 Test done only at low power 4 Test done at high and low power alternatively for 3 times Last test result at low power Last test filtred result at low power Correction at low power Threshold of correction at low power Last test result at high power Last test filtred result at high power Correction at high power Threshold of correction at high power Reset of correction results
CASCADE Lead strategy
On
Precirculation time on DHW way (3WV position) during precirculation function Precirculation time on CH way (3WV position) during precirculation function
Level 3
1min
30°C Table1 Table1 Table1
L e v el
2700 2702 2703 2706
Parameter
Validity time of parameter 2462 Activation of Super Over Temperature Function (SOT): On Off Increase of boiler setpoint for the control of SOT
Lead strategy:
Off Natural gas
Off
0uA 0uA
0
No Default Late on, late off
5040
3
Discharging protection
5050 5051 5055
3 3 3
Charging temp max Storage tank temp max Recooling temp
5056
3
Recooling heat gen/CHs
5057
3
Recooling collector
5060
3
El imm heater optg mode
5061
3
El immersion heater release
5062
3
El immersion heater control
5070
3
Hot water boost
5071
3
Charging prio time push
5085
3
Excess heat draw
5090
3
With buffer
5092
3
With prim contr/system pump
5093
3
With solar integration
Parameter
Level
Attivazione della pompa Q3 in caso di temperatura di mandata troppo alta This function ensures ensures that the DHW charging pump (Q3) is activated only when the heat source temperature is high enough: Off Disabled Always Enabled Timed Active only if the heat source is not able to supply heat or if it is not available Maximum charging temperature from solar collector Maximum hot water tank temperature Recooling hot water tank temperature Tank recooling through heating circuit: On Off Tank recooling through solar collector: Off Summer Always Electric immersion heater used for DHW tank: Substitute The electric immersion heater is only used if the boiler delivers a fault status message or has been shut down via boiler l ock. Summer The electric immersion heater is used when all connected heating circuits have switched to summer operation. The DHW is again heated by the boiler as soon as at least one of the heating circuits has switched back to Heating mode. But the electric immersion heater is also used if the boiler delivers a fault status message or has been shut down via boiler lock. Always DHW is always heated with the electric immersion heater Electric immersion heater release: 24h/day Hot water release Time hot water Electric immersion heater control mode: External thermostat Hot water sensor If the DHW temperature drops by more than 2 switching differentials (l5024) below the Reduced setpoint: On Off The DHW storage tank is charged with absolute priority during the set period of time Surplus heat can be fed to the DHW storage tank: On Off DHW storage tank receives its heat via buffer storage tank: Yes No DHW storage tank receives its heat via the primary controller or with the help of the system pump: Yes No DHW storage tank receives its heat from the solar collectors: Yes No
INSTANTANEOUS HW HEATER
Timed
65°C 90°C 80°C Off
Off
Substitute
Hot water release
Hot water sensor
On 0min On
No
No
Yes
Default Defau lt
5040
3
Discharging protection
5050 5051 5055
3 3 3
Charging temp max Storage tank temp max Recooling temp
5056
3
Recooling heat gen/CHs
5057
3
Recooling collector
5060
3
El imm heater optg mode
5061
3
El immersion heater release
5062
3
El immersion heater control
5070
3
Hot water boost
5071
3
Charging prio time push
5085
3
Excess heat draw
5090
3
With buffer
5092
3
With prim contr/system pump
5093
3
With solar integration
Parameter
Level
Attivazione della pompa Q3 in caso di temperatura di mandata troppo alta This function ensures ensures that the DHW charging pump (Q3) is activated only when the heat source temperature is high enough: Off Disabled Always Enabled Timed Active only if the heat source is not able to supply heat or if it is not available Maximum charging temperature from solar collector Maximum hot water tank temperature Recooling hot water tank temperature Tank recooling through heating circuit: On Off Tank recooling through solar collector: Off Summer Always Electric immersion heater used for DHW tank: Substitute The electric immersion heater is only used if the boiler delivers a fault status message or has been shut down via boiler l ock. Summer The electric immersion heater is used when all connected heating circuits have switched to summer operation. The DHW is again heated by the boiler as soon as at least one of the heating circuits has switched back to Heating mode. But the electric immersion heater is also used if the boiler delivers a fault status message or has been shut down via boiler lock. Always DHW is always heated with the electric immersion heater Electric immersion heater release: 24h/day Hot water release Time hot water Electric immersion heater control mode: External thermostat Hot water sensor If the DHW temperature drops by more than 2 switching differentials (l5024) below the Reduced setpoint: On Off The DHW storage tank is charged with absolute priority during the set period of time Surplus heat can be fed to the DHW storage tank: On Off DHW storage tank receives its heat via buffer storage tank: Yes No DHW storage tank receives its heat via the primary controller or with the help of the system pump: Yes No DHW storage tank receives its heat from the solar collectors: Yes No
INSTANTANEOUS HW HEATER
5464
2
Hot water preheat release
5470 5476 5482 5490 5491
1 3 3 3 3
HW preheat time when no CH Keep hot periodically Flow switch time cons Parameter Parameter
Parameter
Level
5710
2
Temps / mode CH1
5711
3
Cooling circuit 1
5715
2
Temps / mode CH2
5721
2
Temps / mode CH3
5730
2
Hot water sensor
5731
2
HW controlling element
5732 5733
3 3
Pump off change div valve Delay pump off
5734
3
Basic pos HW div valve
5736
3
Hot water separate circuit
5737
3
Optg action HW div valve
5738
3
Midposition DHW div valve
5774
3
Ctrl boiler pump/HW valve
Preheat mode: 24h/day Hot water release Time central heating CH3 Time hot water Time auxiliary Preheat time Duration time of preheat function Minimum response time of the flow switch for detecting consumption
CONFIGURATION Heating circuit 1 activation: 0 Off 1 On Cooling circuit 1 activation: Off 4-pipe system cooling Heating circuit 2 activation: 0 Off 1 On Heating circuit 3 activation: Off On DHW sensor selection: 1 Hot water sensor B3 DHW storage tank sensor 2 Thermostat Sensor used as DHW thermostat 3 HW outlet sensor B38 Instantaneous water heater outlet sensor Actuator type for DHW request control: No charging request No function Charging pump Actuator used as charging pump Diverting valve Actuator used as diverting valve Set the time the pumps are deactivated when the diverti ng valve switches over Set the delay time for the pumps to be deactivated after the diverting valve has switched over Default DHW diverting valve position: Last request Central heating Default for boiler with DHW tank Hot water Default for instantaneous water heater boiler The DHW separate circuit can only be employed in a cascaded system: On Off The diverting valve position selected here is the position used when the output is active: Position on HW Position on CH DHW diverting valve can be driven to the mid-position: On Off Activation mode of boiler pump and DHW diverting valve: All requests Request CH1/HW only
Timed
65°C 90°C 80°C Off
Off
Substitute
Hot water release
Hot water sensor
On 0min On
No
No
Yes
Default Defau lt
Time hot water
Table1 Table1 1s Table1 Off
Default On
Off
Off
Off
Table1
Diverting valve 0s 0s Table1
Off
Position on HW
Off
All requests
5464
2
Hot water preheat release
5470 5476 5482 5490 5491
1 3 3 3 3
HW preheat time when no CH Keep hot periodically Flow switch time cons Parameter Parameter
Parameter
Level
Preheat mode: 24h/day Hot water release Time central heating CH3 Time hot water Time auxiliary Preheat time Duration time of preheat function Minimum response time of the flow switch for detecting consumption
CONFIGURATION Heating circuit 1 activation: 0 Off 1 On Cooling circuit 1 activation: Off 4-pipe system cooling Heating circuit 2 activation: 0 Off 1 On Heating circuit 3 activation: Off On DHW sensor selection: 1 Hot water sensor B3 DHW storage tank sensor 2 Thermostat Sensor used as DHW thermostat 3 HW outlet sensor B38 Instantaneous water heater outlet sensor Actuator type for DHW request control: No charging request No function Charging pump Actuator used as charging pump Diverting valve Actuator used as diverting valve Set the time the pumps are deactivated when the diverti ng valve switches over Set the delay time for the pumps to be deactivated after the diverting valve has switched over Default DHW diverting valve position: Last request Central heating Default for boiler with DHW tank Hot water Default for instantaneous water heater boiler The DHW separate circuit can only be employed in a cascaded system: On Off The diverting valve position selected here is the position used when the output is active: Position on HW Position on CH DHW diverting valve can be driven to the mid-position: On Off Activation mode of boiler pump and DHW diverting valve: All requests Request CH1/HW only
5710
2
Temps / mode CH1
5711
3
Cooling circuit 1
5715
2
Temps / mode CH2
5721
2
Temps / mode CH3
5730
2
Hot water sensor
5731
2
HW controlling element
5732 5733
3 3
Pump off change div valve Delay pump off
5734
3
Basic pos HW div valve
5736
3
Hot water separate circuit
5737
3
Optg action HW div valve
5738
3
Midposition DHW div valve
5774
3
Ctrl boiler pump/HW valve
5840
3
Solar controlling element
5841
3
External solar exchanger
5870
3
Combi storage tank
5890
2
Relay output QX1
5891
3
Relay output QX2
See relay output QX1
5892
3
Relay output QX3
See relay output QX1
Actuator configuration in case of solar storage tanks: Charging pump Used as charging pump Diverting valve Used as diverting valve In the case of solar plant diagrams with 2 storage tanks, it must be selected whether there is an external heat exchanger for both the DHW and the buffer storage tank or for only one of them.: Commonly Hot water storage tank Buffer storage tank Functions specific to combi storage tanks are activated via this setting (for example, the electric immersion heater installed in the buffer storage tank can be used for both space heating and DHW heating): Yes No 0 None 1 Circulating pump Q4 DHW circulating pump 2 El imm heater HW K6 3 Collector pump Q5 Solar collector pump 4 Cons circuit pump VK1 Q15 Consumer circuit 1 pump 5 Boiler pump Q1 Boiler pump 6 Bypass pump Q12 7 Alarm output K10 Alarm relay signals faults 8 2nd pump speed CH1 Q21 9 2nd pump speed CH2 Q22 10 2nd pump speed CH3 Q23 11 heating pump CH3 Q20 Pump/zone valve for heating circuit 3 12 Cons circuit pump VK2 Q18 13 System pump Q14 Pump activated at every heat request from consumer circuits 14 Heat gen shutoff valve Y4 15 Solid fuel boiler pump Q10 Solid flue boiler pump 16 Time setting 5 K13 The relay is controlled according to setting made in “time auxiliary program” 17 Buffer return valve Y15 18 Solar pump ext exch K9 19 Solar ctrl elem buffer K8 20 Solar ctrl elem swi pool K18 Contact to heat swimming pool by solar (in case of several heat exchangers) 22 Swimming pool pump Q19 25 Cascade pump Q25 Common cascade pump 26 St tank transfer pump Q11 27 Hot water mixing pump Q35 28 HW interm circ pump Q33 29 Heat request K27 30 Refrigeration request K28 Cooling request from cooling circuit 1 33 Heating pump CH1 Q2 Pump/zone valve for heating circuit 1 34 Heating pump CH2 Q6 Pump/zone valve for heating circuit 2 35 Hot water ctrl elem Q3 Pump/diverting valve for DHW tank 36 Instant WH ctrl elem Q34 Pump/diverting valve for instantaneous DHW production 38 Water refill K34 Water refill electrovalve 39 2nd boiler pump speed Q27 2nd boiler pump speed 40 Status output K35 41 Status information K36 42 Flue gas damper K37 43 Fan shutdown K38 External fan control
Time hot water
Table1 Table1 1s Table1 Off
Default On
Off
Off
Off
Table1
Diverting valve 0s 0s Table1
Off
Position on HW
Off
All requests
Charging pump
Commonly
No
heating pump CH1 Q2
Boiler pump Q1 Table1
Actuator configuration in case of solar storage tanks: Charging pump Used as charging pump Diverting valve Used as diverting valve In the case of solar plant diagrams with 2 storage tanks, it must be selected whether there is an external heat exchanger for both the DHW and the buffer storage tank or for only one of them.: Commonly Hot water storage tank Buffer storage tank Functions specific to combi storage tanks are activated via this setting (for example, the electric immersion heater installed in the buffer storage tank can be used for both space heating and DHW heating): Yes No 0 None 1 Circulating pump Q4 DHW circulating pump 2 El imm heater HW K6 3 Collector pump Q5 Solar collector pump 4 Cons circuit pump VK1 Q15 Consumer circuit 1 pump 5 Boiler pump Q1 Boiler pump 6 Bypass pump Q12 7 Alarm output K10 Alarm relay signals faults 8 2nd pump speed CH1 Q21 9 2nd pump speed CH2 Q22 10 2nd pump speed CH3 Q23 11 heating pump CH3 Q20 Pump/zone valve for heating circuit 3 12 Cons circuit pump VK2 Q18 13 System pump Q14 Pump activated at every heat request from consumer circuits 14 Heat gen shutoff valve Y4 15 Solid fuel boiler pump Q10 Solid flue boiler pump 16 Time setting 5 K13 The relay is controlled according to setting made in “time auxiliary program” 17 Buffer return valve Y15 18 Solar pump ext exch K9 19 Solar ctrl elem buffer K8 20 Solar ctrl elem swi pool K18 Contact to heat swimming pool by solar (in case of several heat exchangers) 22 Swimming pool pump Q19 25 Cascade pump Q25 Common cascade pump 26 St tank transfer pump Q11 27 Hot water mixing pump Q35 28 HW interm circ pump Q33 29 Heat request K27 30 Refrigeration request K28 Cooling request from cooling circuit 1 33 Heating pump CH1 Q2 Pump/zone valve for heating circuit 1 34 Heating pump CH2 Q6 Pump/zone valve for heating circuit 2 35 Hot water ctrl elem Q3 Pump/diverting valve for DHW tank 36 Instant WH ctrl elem Q34 Pump/diverting valve for instantaneous DHW production 38 Water refill K34 Water refill electrovalve 39 2nd boiler pump speed Q27 2nd boiler pump speed 40 Status output K35 41 Status information K36 42 Flue gas damper K37 43 Fan shutdown K38 External fan control
5840
3
Solar controlling element
5841
3
External solar exchanger
5870
3
Combi storage tank
5890
2
Relay output QX1
5891
3
Relay output QX2
See relay output QX1
5892
3
Relay output QX3
See relay output QX1
Charging pump
Commonly
No
heating pump CH1 Q2
Boiler pump Q1 Table1
6051 6052 6054
2 2 2
Voltage value 2 H2 module 1 Funct value 2 H2 module 1 Function input H2 module 2
6055
2
Contact type H2 module 2
6057 6058 6059 6060 6062
2 2 2 2 2
Voltage value 1 H2 module 2 Funct value 1 H2 module 2 Voltage value 2 H2 module 2 Funct value 2 H2 module 2 Function input H2 module 3
6063
2
Contact type H2 module 3
6065 6066 6067 6068
2 2 2 2
Voltage value 1 H2 module 3 Funct value 1 H2 module 3 Voltage value 2 H2 module 3 Funct value 2 H2 module 3
6097
2
Sensor type collector
6098 6100 6110
3 2 3
Readjustm collector sensor Readjustm outside sensor Time constant building
6120
3
System frost protection
6200 6205 6212 6213 6215 6217 6220 6230 6231
2 3 2 2 2 2 3 2 2
Save sensors Reset to default parameters Check no. heat source 1 Check no. heat source 2 Check no. storage tank Check no. heating circuits Software version Info 1 OEM Info 2 OEM
Parameter
Level
Parameter for characteristic definition of sensor Parameter for characteristic definition of sensor See function input H1 NO NC Parameter for characteristic definition of sensor Parameter for characteristic definition of sensor Parameter for characteristic definition of sensor Parameter for characteristic definition of sensor See function input H1 NO NC Parameter for characteristic definition of sensor Parameter for characteristic definition of sensor Parameter for characteristic definition of sensor Parameter for characteristic definition of sensor Solar collector sensor type: 1 NTC 2 PT1000 Correction of readed collector sensor value Correction of readed outside sensor value Time thermic constant building Plant frost protection (only with outside sensor): On Off Stored of sensor used in plant Not used Manufactoring information Manufactoring information Manufactoring information Manufactoring information Manufactoring information Manufactoring information Manufactoring information
LPB SYST SYSTEM EM
6600 6601
3 3
Device address Segment address
6604
3
Bus power supply function
6605
3
Bus power supply state
6610
3
Display system messages
6612
3
Alarm delay
6620
3
Action changeover functions
Choice of cascade device address from 1 to 16 (1 = master) Choice of cascade segment from 0 to 14 Bus power supply type: Off Timed Bus power supply state: On Off Visualization of system messages: Yes No Alarm time delay Action function changeover: System Segment
0V 0 None NO 0V 0 0V 0 None NO 0V 0 0V 0 PT1000 0°C 0°C 15h Off No No
Table1
Default 1 0 Timed
No --System
6051 6052 6054
2 2 2
Voltage value 2 H2 module 1 Funct value 2 H2 module 1 Function input H2 module 2
6055
2
Contact type H2 module 2
6057 6058 6059 6060 6062
2 2 2 2 2
Voltage value 1 H2 module 2 Funct value 1 H2 module 2 Voltage value 2 H2 module 2 Funct value 2 H2 module 2 Function input H2 module 3
6063
2
Contact type H2 module 3
6065 6066 6067 6068
2 2 2 2
Voltage value 1 H2 module 3 Funct value 1 H2 module 3 Voltage value 2 H2 module 3 Funct value 2 H2 module 3
6097
2
Sensor type collector
6098 6100 6110
3 2 3
Readjustm collector sensor Readjustm outside sensor Time constant building
6120
3
System frost protection
6200 6205 6212 6213 6215 6217 6220 6230 6231
2 3 2 2 2 2 3 2 2
Save sensors Reset to default parameters Check no. heat source 1 Check no. heat source 2 Check no. storage tank Check no. heating circuits Software version Info 1 OEM Info 2 OEM
Parameter
Level
Parameter for characteristic definition of sensor Parameter for characteristic definition of sensor See function input H1 NO NC Parameter for characteristic definition of sensor Parameter for characteristic definition of sensor Parameter for characteristic definition of sensor Parameter for characteristic definition of sensor See function input H1 NO NC Parameter for characteristic definition of sensor Parameter for characteristic definition of sensor Parameter for characteristic definition of sensor Parameter for characteristic definition of sensor Solar collector sensor type: 1 NTC 2 PT1000 Correction of readed collector sensor value Correction of readed outside sensor value Time thermic constant building Plant frost protection (only with outside sensor): On Off Stored of sensor used in plant Not used Manufactoring information Manufactoring information Manufactoring information Manufactoring information Manufactoring information Manufactoring information Manufactoring information
LPB SYST SYSTEM EM
6600 6601
3 3
Device address Segment address
6604
3
Bus power supply function
6605
3
Bus power supply state
6610
3
Display system messages
6612
3
Alarm delay
6620
3
Action changeover functions
6621
3
Summer changeover
6623
3
Optg mode changeover
6624
3
Manual source lock
6625
3
Hot water assignment
6630
3
Cascade master
6631
3
Ext source with eco mode
6632
3
Note OT limit ext source
6640
3
Clock mode
6650
3
Outside temp source
Parameter
Level
6704
2
Display SW diagnostic code
6705 6706 6710 6740 6741 6742 6743 6745 6800 6805 6806 6810 - 6996
1 1 2 3 3 3 3 3 2 2 2 2
SW diagnostic code Burn ctrl phase lockout pos Reset alarm relay Flow temp 1 alarm Flow temp 2 alarm Flow temp 3 alarm Boiler temp alarm Hot water charging alarm History 1 SW diagnostic code 1 Burner control phase 1 History from 2 to 20
Parameter
Level
7040
3
Choice of cascade device address from 1 to 16 (1 = master) Choice of cascade segment from 0 to 14 Bus power supply type: Off Timed Bus power supply state: On Off Visualization of system messages: Yes No Alarm time delay Action function changeover: System Segment
Summer changeover: Locally Centrally Option mode changeover: Locally Centrally Lock mode: Locally Segment DHW assignment: Local CHs DHW used the setting of boiler All CHs in segment DHW used the setting of boiler in same cascade segment All CHs in system DHW used the setting of boiler in cascade system Cascade master: Always Cascade master is the boiler also if address is not 1 Automatically Cascade master is the boiler with address 1 In ECO mode, external heat sources on the LPB are operated as follows: Off On hot water On External heat sources can be locked or released according to their own parameters, based on the outside temperature: Yes No Clock mode: Autonomously Every boiler has own time program Slave without remote setting Slave boilers not use the master time program Slave with remote setting Slave boilers use the master time program Master The master time program is used Boiler address where is connected outside sensor: - - . - - no outside sensor connected The first 2 numbers are hte segment number, the second part is the boiler number
FAULT Visualization of diagnostic code: 0 No 1 Yes Diagnostic code currently pending Lockout phase indicating where the fault occured Reset of alarm relay value displayed value displayed value displayed value displayed value displayed Last fault occured Diagnostic code of last fault occured Lockout phase indicating where the last fault occured Previous fault history
SERVICE/SPECIAL SERVICE/SPEC IAL OPERATION Burner hours interval
Burner hours before boiler maintenance
0V 0 None NO 0V 0 0V 0 None NO 0V 0 0V 0 PT1000 0°C 0°C 15h Off No No
Table1
Default 1 0 Timed
No --System
Locally
Centrally
Segment
All CHs in system
Automatically
Off
No
Autonomously
Default Yes
No -----------
Default Defau lt ---
Summer changeover: Locally Centrally Option mode changeover: Locally Centrally Lock mode: Locally Segment DHW assignment: Local CHs DHW used the setting of boiler All CHs in segment DHW used the setting of boiler in same cascade segment All CHs in system DHW used the setting of boiler in cascade system Cascade master: Always Cascade master is the boiler also if address is not 1 Automatically Cascade master is the boiler with address 1 In ECO mode, external heat sources on the LPB are operated as follows: Off On hot water On External heat sources can be locked or released according to their own parameters, based on the outside temperature: Yes No Clock mode: Autonomously Every boiler has own time program Slave without remote setting Slave boilers not use the master time program Slave with remote setting Slave boilers use the master time program Master The master time program is used Boiler address where is connected outside sensor: - - . - - no outside sensor connected The first 2 numbers are hte segment number, the second part is the boiler number
6621
3
Summer changeover
6623
3
Optg mode changeover
6624
3
Manual source lock
6625
3
Hot water assignment
6630
3
Cascade master
6631
3
Ext source with eco mode
6632
3
Note OT limit ext source
6640
3
Clock mode
6650
3
Outside temp source
Parameter
Level
6704
2
Display SW diagnostic code
6705 6706 6710 6740 6741 6742 6743 6745 6800 6805 6806 6810 - 6996
1 1 2 3 3 3 3 3 2 2 2 2
SW diagnostic code Burn ctrl phase lockout pos Reset alarm relay Flow temp 1 alarm Flow temp 2 alarm Flow temp 3 alarm Boiler temp alarm Hot water charging alarm History 1 SW diagnostic code 1 Burner control phase 1 History from 2 to 20
Visualization of diagnostic code: 0 No 1 Yes Diagnostic code currently pending Lockout phase indicating where the fault occured Reset of alarm relay value displayed value displayed value displayed value displayed value displayed Last fault occured Diagnostic code of last fault occured Lockout phase indicating where the last fault occured Previous fault history
Parameter
Level
7040
3
Burner hours interval
Burner hours before boiler maintenance
7041 7042 7043 7044 7045 7051
3 3 3 3 2 3
Burn hrs since maintenance Burner start interval Burn starts since maint Maintenance interval Time since maintenance Message ionization current
7130
2
Chimney sweep function
7131
2
Burner output
7140
2
Manual control
7143
2
Controller stop function
7145
2
Controller stop setpoint
7146
2
Deaeration function
7147
2
Type of venting
Burner hours reset after boiler maintenance Burner ignition number before boiler maintenance Burner ignition number reset after boiler maintenance Operation boiler time before boiler maintenance Operation boiler time reset after boiler maintenance Ionization current value Chimney swwp function: On Off Burner output power during chimney sweep function: Partial load Full load Max heating load Manual control function: On Off Controller stop function: On Off Power setpoint during controller stop function Deaeration function: On Off Deaeration function mode: None Heating circuit continuous Heating circuit cycled Hot water continuous Hot water cycled
7170 7231 7232 7233
2 2 2 2
Telephone customer service Refilll time current week Refill time to date Number of refills to date
7244
3
Press superv water refill
7250 7251
3 3
PStick storage pos Parameter
7252
3
PStick command
7253
3
PStick progress
7254
3
Parameter
FAULT
SERVICE/SPECIAL SERVICE/SPEC IAL OPERATION
Locally
Centrally
Segment
All CHs in system
Automatically
Off
No
Autonomously
Default Yes
No -----------
Default Defau lt ---
0h --O --0Month No Off
Max heating load
Off
Off 100% Off
None
0 value displayed value displayed value displayed Used sensor for water pressure supervision for refill function: None With input H1 With input H2 module 1 With input H2 module 2 With input H2 module 3 With input H3 Selection of the dataset number to write/read Description of dataset selected Actions with Pstick: No operation Reading from stick Writing on stick The progress made appears as a percentage which, when stick operation is active (reading or writing) shows the percentage already completed. Status of Pstick: No stick No operation Writing on stick
None
7041 7042 7043 7044 7045 7051
3 3 3 3 2 3
Burn hrs since maintenance Burner start interval Burn starts since maint Maintenance interval Time since maintenance Message ionization current
7130
2
Chimney sweep function
7131
2
Burner output
7140
2
Manual control
7143
2
Controller stop function
7145
2
Controller stop setpoint
7146
2
Deaeration function
7147
2
Type of venting
7170 7231 7232 7233
2 2 2 2
Telephone customer service Refilll time current week Refill time to date Number of refills to date
7244
3
Press superv water refill
7250 7251
3 3
PStick storage pos Parameter
7252
3
PStick command
7253
3
PStick progress
7254
3
Parameter
Burner hours reset after boiler maintenance Burner ignition number before boiler maintenance Burner ignition number reset after boiler maintenance Operation boiler time before boiler maintenance Operation boiler time reset after boiler maintenance Ionization current value Chimney swwp function: On Off Burner output power during chimney sweep function: Partial load Full load Max heating load Manual control function: On Off Controller stop function: On Off Power setpoint during controller stop function Deaeration function: On Off Deaeration function mode: None Heating circuit continuous Heating circuit cycled Hot water continuous Hot water cycled
0h --O --0Month No Off
Max heating load
Off
Off 100% Off
None
0 value displayed value displayed value displayed Used sensor for water pressure supervision for refill function: None With input H1 With input H2 module 1 With input H2 module 2 With input H2 module 3 With input H3 Selection of the dataset number to write/read Description of dataset selected Actions with Pstick: No operation Reading from stick Writing on stick The progress made appears as a percentage which, when stick operation is active (reading or writing) shows the percentage already completed. Status of Pstick: No stick No operation Writing on stick
None
Reading from stick EMC test active Writing error Reading error Incompatible data set Wrong stick type Stick format error Check data set Data set disabled Reading disabled
Parameter
Level
INPUT/OUTPUT TEST
7700
3
Relay test
7730 7750 7760 7820 7821 7822 7830 7831 7832 7833 7834 7835 7840 7841 7845 7846 7848 7849 7851 7852 7862 7860 7865
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
Outside temp B9 Hot waterr temp B3 Boiler temp B2 Sensor temp BX1 Sensor temp BX2 Sensor temp BX3 Sensor temp BX21 module 1 Sensor temp BX22 module 1 Sensor temp BX21 module 2 Sensor temp BX22 module 2 Sensor temp BX21 module 3 Sensor temp BX22 module 3 Voltage signal H1 Contact state H1 Voltage signal H2 Contact state H2 Voltage signal H2 module 2 Contact state H2 module 2 Voltage signal H2 module 3 Contact state H2 module 3 Frequency H4 Contact state H4 Contact state H5
Operatin relays test: No test Everything off Relay output QX1 Relay output QX2 Relay output QX3 Relay output QX4 Relay output QX21 module 1 Relay output QX21 module 2 Relay output QX21 module 3 Relay output QX22 module 1 Relay output QX22 module 2 Relay output QX22 module 3 Relay output QX23 module 1 Relay output QX23 module 2 Relay output QX23 module 3 value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed
Default Defau lt
No test
Reading from stick EMC test active Writing error Reading error Incompatible data set Wrong stick type Stick format error Check data set Data set disabled Reading disabled
Parameter
Level
INPUT/OUTPUT TEST
7700
3
Relay test
7730 7750 7760 7820 7821 7822 7830 7831 7832 7833 7834 7835 7840 7841 7845 7846 7848 7849 7851 7852 7862 7860 7865
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
Outside temp B9 Hot waterr temp B3 Boiler temp B2 Sensor temp BX1 Sensor temp BX2 Sensor temp BX3 Sensor temp BX21 module 1 Sensor temp BX22 module 1 Sensor temp BX21 module 2 Sensor temp BX22 module 2 Sensor temp BX21 module 3 Sensor temp BX22 module 3 Voltage signal H1 Contact state H1 Voltage signal H2 Contact state H2 Voltage signal H2 module 2 Contact state H2 module 2 Voltage signal H2 module 3 Contact state H2 module 3 Frequency H4 Contact state H4 Contact state H5
Operatin relays test: No test Everything off Relay output QX1 Relay output QX2 Relay output QX3 Relay output QX4 Relay output QX21 module 1 Relay output QX21 module 2 Relay output QX21 module 3 Relay output QX22 module 1 Relay output QX22 module 2 Relay output QX22 module 3 Relay output QX23 module 1 Relay output QX23 module 2 Relay output QX23 module 3 value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed
7950 7951 7952
3 3 3
Input EX21 module 1 Input EX21 module 2 Input EX21 module 3
value displayed value displayed value displayed
Parameter 8000 8001 8002 8003 8005 8007 8008 8009 8010 8011 8023
Parameter 8100 8101 8102 8103 8104 8105 8106 8107 8108 8109 8110 8111 8112 8113 8114 8115 8116 8117 8118 8119 8120 8121 8122 8123 8124 8125 8126 8127 8128 8129 8130
Level 2 2 2 2 2 2 2 2 2 2 2
No test
STATE
Default
DIAGNOSTIC CASCADE
Default Defau lt
State central heating CH1 State central heating CH2 State central heating CH3 State hot water State boiler State solar State solid fuel boiler State burner State buffer State swimming pool State SithermPro
Level 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
Default Defau lt
Priority/state source 1 Priority/state source 2 Priority/state source 3 Priority/state source 4 Priority/state source 5 Priority/state source 6 Priority/state source 7 Priority/state source 8 Priority/state source 9 Priority/state source 10 Priority/state source 11 Priority/state source 12 Priority/state source 13 Priority/state source 14 Priority/state source 15 Priority/state source 16
value displayed state displayed value displayed state displayed value displayed state displayed value displayed state displayed value displayed state displayed value displayed state displayed value displayed state displayed value displayed state displayed value displayed state displayed value displayed state displayed value displayed state displayed value displayed state displayed value displayed state displayed value displayed state displayed value displayed state displayed value displayed
7950 7951 7952
Parameter 8000 8001 8002 8003 8005 8007 8008 8009 8010 8011 8023
Parameter
3 3 3
2 2 2 2 2 2 2 2 2 2 2
8131 8138 8139 8140 8141 8150
3 3 3 3 3 3
Parameter
Priority/state source 1
Priority/state source 16
value displayed state displayed value displayed state displayed value displayed state displayed value displayed state displayed value displayed state displayed value displayed state displayed value displayed state displayed value displayed state displayed value displayed state displayed value displayed state displayed value displayed state displayed value displayed state displayed value displayed state displayed value displayed state displayed value displayed state displayed value displayed
Cascade flow temp Cascade flow temp setp Cascade return temp Cascade return temp setp Source seq ch'over current
state displayed value displayed value displayed value displayed value displayed value displayed
Priority/state source 2 Priority/state source 3 Priority/state source 4 Priority/state source 5 Priority/state source 6 Priority/state source 7 Priority/state source 8 Priority/state source 9 Priority/state source 10 Priority/state source 11 Priority/state source 12 Priority/state source 13 Priority/state source 14 Priority/state source 15
Level 3 3 2 2 3 3 2 2 2 3 2 2 3 3 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 1 1 3 3
Level
STATE
Default
DIAGNOSTIC CASCADE
Default Defau lt
DIAGNOSTICS HEAT GENERATION
Default Defau lt
DIAGNOSTICS CONSUMER CONSUMERS S
Default Defau lt
State central heating CH1 State central heating CH2 State central heating CH3 State hot water State boiler State solar State solid fuel boiler State burner State buffer State swimming pool State SithermPro
Level 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
8304 8308 8310 8311 8312 8313 8314 8315 8316 8318 8321 8323 8324 8325 8326 8327 8329 8330 8331 8338 8339 8390 8499 8501 8502 8510 8511 8512 8513 8513 8514 8515 8519 8520 8527 8530 8531 8532 8560 8570
value displayed value displayed value displayed
Level
8100 8101 8102 8103 8104 8105 8106 8107 8108 8109 8110 8111 8112 8113 8114 8115 8116 8117 8118 8119 8120 8121 8122 8123 8124 8125 8126 8127 8128 8129 8130
Parameter
Input EX21 module 1 Input EX21 module 2 Input EX21 module 3
Boiler pump Q1 Boiler pump speed Boiler temperature Boiler setpoint Boiler switching point Parameter Boiler return temp Boiler return temp setpoint Flue gas temp Flue gas temp max Primary exchanger temp Fan speed Set point fan Current fan control Burner modulation Water pressure Ionization current Hours run 1st stage Start counter 1st stage Hours run heating mode Hours run HW Current phase number Collector pump 1 Solar ctrl elem buffer Solar ctrl elem swi pool Collector temp 1 Collector temp 1 max Collector temp 1 min dt collector 1/exchanger 1 dt collector 1/HW dt collector 1/buffer dt collector 1/swimming pool Solar flow temp Solar return temp Total Solar Gain Hours run solar Hours run collect overtemp Hours run collector pump Solid fuel boiler temp Hours run solid fuel boiler
value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value reset value displayed value displayed value displayed value displayed value displayed value displayed value displayed value reset value reset value reset value reset value displayed value displayed value displayed value displayed value displayed value reset value reset value displayed value displayed value displayed value displayed value displayed value displayed value reset value reset value reset value reset value displayed value reset
8131 8138 8139 8140 8141 8150
Parameter 8304 8308 8310 8311 8312 8313 8314 8315 8316 8318 8321 8323 8324 8325 8326 8327 8329 8330 8331 8338 8339 8390 8499 8501 8502 8510 8511 8512 8513 8513 8514 8515 8519 8520 8527 8530 8531 8532 8560 8570
Parameter
8700 8701 8702 8703 8704 8730 8731 8732 8740 8741 8743 8744 8749 8760 8761 8762 8770 8771 8773 8774 8779 8790 8791 8792 8800 8801 8804 8803 8809 8820 8830 8831 8832 8835 8836 8852 8853 8860 8875 8885 8895 8900 8901 8930 8931 8950 8951 8952 8962
3 3 3 3 3 3
Cascade flow temp Cascade flow temp setp Cascade return temp Cascade return temp setp Source seq ch'over current
state displayed value displayed value displayed value displayed value displayed value displayed
Level 3 3 2 2 3 3 2 2 2 3 2 2 3 3 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 1 1 1 1 3 3
Boiler pump Q1 Boiler pump speed Boiler temperature Boiler setpoint Boiler switching point Parameter Boiler return temp Boiler return temp setpoint Flue gas temp Flue gas temp max Primary exchanger temp Fan speed Set point fan Current fan control Burner modulation Water pressure Ionization current Hours run 1st stage Start counter 1st stage Hours run heating mode Hours run HW Current phase number Collector pump 1 Solar ctrl elem buffer Solar ctrl elem swi pool Collector temp 1 Collector temp 1 max Collector temp 1 min dt collector 1/exchanger 1 dt collector 1/HW dt collector 1/buffer dt collector 1/swimming pool Solar flow temp Solar return temp Total Solar Gain Hours run solar Hours run collect overtemp Hours run collector pump Solid fuel boiler temp Hours run solid fuel boiler
Outside temp Outside temp min. Outside temp max. Outside temp attenuated Outside temp composite Central heating pump 1 Heat circ mix valve 1 open Heat circ mix valve 1 close Room temp 1 Room setpoint 1 Flow temp 1 Flow temp setpoint 1 Room thermostat 1 Central heating pump 2 Heat circ mix valve 2 open Heat circ mix valve 2 close Room temp 2 Room setpoint 2 Flow temp 2 Flow temp setpoint 2 Room thermostat 2 Central heating pump 3 Heat circ mix valve 3 open Heat circ mix valve 3 close Room temp 3 Room setpoint 3 Flow temp 3 Flow temp setpoint 3 Room thermostat 3 Hot water pump Hot water temp 1 Hot water temp setpoint Hot water temp 2 Hot water circulation temp HW charging temp Instant HW heater temp Instant HW heater setpoint Hot water flow Flow temp setp VK1 Flow temp setp VK2 Flow temp setp VK3 Swimming pool temp Swimming pool setpoint Primary controller temp Primary controller setpoint Common flow temp Common flow temp setpoint Common return temp Common output setpoint
Default Defau lt
DIAGNOSTICS CONSUMER CONSUMERS S
Default Defau lt
value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value reset value displayed value displayed value displayed value displayed value displayed value displayed value displayed value reset value reset value reset value reset value displayed value displayed value displayed value displayed value displayed value reset value reset value displayed value displayed value displayed value displayed value displayed value displayed value reset value reset value reset value reset value displayed value reset
Level
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
DIAGNOSTICS HEAT GENERATION
value displayed value reset value reset value reset value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed
8700 8701 8702 8703 8704 8730 8731 8732 8740 8741 8743 8744 8749 8760 8761 8762 8770 8771 8773 8774 8779 8790 8791 8792 8800 8801 8804 8803 8809 8820 8830 8831 8832 8835 8836 8852 8853 8860 8875 8885 8895 8900 8901 8930 8931 8950 8951 8952 8962
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
Outside temp Outside temp min. Outside temp max. Outside temp attenuated Outside temp composite Central heating pump 1 Heat circ mix valve 1 open Heat circ mix valve 1 close Room temp 1 Room setpoint 1 Flow temp 1 Flow temp setpoint 1 Room thermostat 1 Central heating pump 2 Heat circ mix valve 2 open Heat circ mix valve 2 close Room temp 2 Room setpoint 2 Flow temp 2 Flow temp setpoint 2 Room thermostat 2 Central heating pump 3 Heat circ mix valve 3 open Heat circ mix valve 3 close Room temp 3 Room setpoint 3 Flow temp 3 Flow temp setpoint 3 Room thermostat 3 Hot water pump Hot water temp 1 Hot water temp setpoint Hot water temp 2 Hot water circulation temp HW charging temp Instant HW heater temp Instant HW heater setpoint Hot water flow Flow temp setp VK1 Flow temp setp VK2 Flow temp setp VK3 Swimming pool temp Swimming pool setpoint Primary controller temp Primary controller setpoint Common flow temp Common flow temp setpoint Common return temp Common output setpoint
value displayed value reset value reset value reset value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed
8980 8981 8982 8983 9005 9006 9009 9031 9032 9033 9050 9051 9052 9053 9054 9055 9056 9057 9058
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
Buffer temp 1 Buffer setpoint Buffer temp 2 Buffer temp 3 Water pressure H1 Water pressure H2 Water pressure H3 Relay output QX1 Relay output QX2 Relay output QX3 Relay output QX21 module 1 Relay output QX22 module 1 Relay output QX23 module 1 Relay output QX21 module 2 Relay output QX22 module 2 Relay output QX23 module 2 Relay output QX21 module 3 Relay output QX22 module 3 Relay output QX23 module 3
value displayed value reset value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed
Parameter
Level
BURNER CONTROL
9500 9504 9512 9524 9529 9540
3 3 2 2 2 3
Prepurge time Required speed prepurging Required speed ignition Required speed LF Required speed HF Postpurge time
9650
3
Chimney drying
9651 9652
3 3
Req speed chimney drying Duration chimney drying
Fan running time of prepurge Prepurging fan speed Ignition fan speed Minimum power fan speed Maximum power fan speed Fan running time of postpurge Mode: Off Temporarily Permanently Fan speed during the function Operation time of function
Default Defau lt 1s Table1 Table1 Table1 Table1 5s Off 500rpm 10min
8980 8981 8982 8983 9005 9006 9009 9031 9032 9033 9050 9051 9052 9053 9054 9055 9056 9057 9058
Parameter
3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
Buffer temp 1 Buffer setpoint Buffer temp 2 Buffer temp 3 Water pressure H1 Water pressure H2 Water pressure H3 Relay output QX1 Relay output QX2 Relay output QX3 Relay output QX21 module 1 Relay output QX22 module 1 Relay output QX23 module 1 Relay output QX21 module 2 Relay output QX22 module 2 Relay output QX23 module 2 Relay output QX21 module 3 Relay output QX22 module 3 Relay output QX23 module 3
Level
value displayed value reset value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed value displayed
BURNER CONTROL
9500 9504 9512 9524 9529 9540
3 3 2 2 2 3
Prepurge time Required speed prepurging Required speed ignition Required speed LF Required speed HF Postpurge time
9650
3
Chimney drying
9651 9652
3 3
Req speed chimney drying Duration chimney drying
Fan running time of prepurge Prepurging fan speed Ignition fan speed Minimum power fan speed Maximum power fan speed Fan running time of postpurge Mode: Off Temporarily Permanently Fan speed during the function Operation time of function
Default Defau lt 1s Table1 Table1 Table1 Table1 5s Off 500rpm 10min
3
ERROR LIST
Error
Internal Code
Description
28
Flue gas temp sensor
30 31
Flow sensor 1 Flow sensor cooling 1
Central heating enabled without any control (room thermostat, room unit o outside sensor) or outside sensor fault Short circuit Open circuit Solid fuel boiler sensor not found or in short circuit Common flow sensor not found or in short circuit Short circuit (lockout) Open circuit (lockout) Short circuit (temporary error) Open circuit (temporary error) Flow sensor mixing zone 1 not found or in short circuit Flow sensor cooling circuit not found or in short circuit
32
Flow sensor 2
Flow sensor mixing zone 2 not found or in short circuit
38
Flow sensor prim contr
40
Return sensor 1
46 47
Return sensor cascade Common return sensor HW sensor 1 (boiler with tank)
Flow sensor primary controller not found or in short circuit Short circuit Open circuit Return sensor cascade not found or in short circuit Common return sensor not found or in short circuit Short circuit Open circuit
10
Outside sensor
20
Boiler sensor 1
25 26
Boiler sensor solid fuel Common flow sensor
50
1 2
539 540 543 544
1 2
1 2
3
ERROR LIST
Error
Internal Code
Description
28
Flue gas temp sensor
30 31
Flow sensor 1 Flow sensor cooling 1
Central heating enabled without any control (room thermostat, room unit o outside sensor) or outside sensor fault Short circuit Open circuit Solid fuel boiler sensor not found or in short circuit Common flow sensor not found or in short circuit Short circuit (lockout) Open circuit (lockout) Short circuit (temporary error) Open circuit (temporary error) Flow sensor mixing zone 1 not found or in short circuit Flow sensor cooling circuit not found or in short circuit
32
Flow sensor 2
Flow sensor mixing zone 2 not found or in short circuit
38
Flow sensor prim contr
40
Return sensor 1
46 47
Return sensor cascade Common return sensor HW sensor 1 (boiler with tank) HW sensor 2 HW flow sensor HW circulation sensor Room sensor 1 Room sensor 2 Room sensor 3 Storage tank sensor 1 Storage tank sensor 2 Storage tank sensor 3 Collector sensor 1 Collector sensor 2
Flow sensor primary controller not found or in short circuit Short circuit Open circuit Return sensor cascade not found or in short circuit Common return sensor not found or in short circuit Short circuit Open circuit Solar DHW sensor not found or in short circuit DHW flow sensor not found or in short circuit DHW circulation sensor not found or in short circuit Room sensor circuit 1 not found or in short circuit Room sensor circuit 2 not found or in short circuit Room sensor circuit 3 not found or in short circuit Storage tank sensor 1 not found or in short circuit Storage tank sensor 2 not found or in short circuit Storage tank sensor 3 not found or in short circuit Solar collector sensor 1 not found or in short circuit Solar collector sensor 2 not found or in short circuit Short circuit (lockout) Short circuit (temporary error) Automatic filling loop loop error (lockout) (lockout) Automatic filling loop error (temporary (temporary error) LPB bus error More than 1 boiler using in the same address No comunication comunication / comunication error More than 1 room unit using in the same Central heating No radio comunication Internal counter out of range External modul 1 not found External modul 2 not found
10
Outside sensor
20
Boiler sensor 1
25 26
Boiler sensor solid fuel Common flow sensor
50 52 54 57 60 65 68 70 71 72 73 74 78
Water pressure sensor
81 82 83 84 85 91 98 99
LPB short-circuit/comm LPB address collision BSB short-circuit BSB address collision BSB Radio communication communicati on Data loss in EEPROM Extension module 1 Extension module 2
100
2 clock time masters
105
Maintenance message
109
Boiler temp supervision
1 2
539 540 543 544
1 2
1 2
506 560 793 797
499
Not correct configuration of clock time 503 504
Flatness 2 test on flow sensor Flatness 2 test on r eturn sensor
419 420 421
110
Lockout SLT
426 427 428 429 431 436 437 438
111
Shutdown limit thermost
117
Water pressure too high
118
Water pressure too low
119
Shutd water press swi
121 122
Flow temp CH1 Flow temp CH2
Maximum temperature of Electronic Safe Limit temperature Return temperature higher than flow temperature temperature more than 10K (temporary error) Return temperature egual or higher than flow temperature more than 10K-2 Temperature slope Unlock limit of temperature slope not reached Flow – return temperature higher than 56K (temporary error) Unlock limit of Flow – return temperature higher than 56K Accepted times return temperature temperature higher than than flow temperature more than 10K reached (lockout error) Electronic Safe Limit temperature on return temperature Accepted times Temperature Temperature slope slope reached Accepted times Flow – return temperature temperature higher higher than 56K reached (lockout error) Maximum limit of flow temperature
565
Static water pressure limit (lockout error) > 2.8 bar
566
Static water pressure limit (temporary error) > 2.8 bar
125
Boiler temp too high
126
HW charg temp
Static pressure limit (lockout error) < 0.5 bar Water pressure limit (lockout error) Water pressure limit (temporary error) Flow temperature Central heating 1 not reached Flow temperature Central heating 2 not reached Reached limit of flow temperature of flow setpoint plus 30K for 2 times in 10 minutes No flow temperature variation for 20 seconds No return temperature variation for 20 seconds Maximum temperature of DHW charging not reached
127
Legionella temp
Legionella limit temperature temperatur e not reached
128
Loss of flame in op
Loss of flame during operation
130
Flue gas temp too high
Flue temperature limit reached
132
Safety shutdown
Lock on GP contact
133
Safety time exceeded
Loss of flame during ignition phase
563 564
500
151
BMU internal
152
Parameterization
501 502
325 326 327 328 329 330 331 332 333 334 335 336 337 338 339 345 346
Software error Software error Software error Software error Software error Ingniter relay closing error Ingniter relay opening error Gas valve relay closing error Gas valve relay opening error Ingnition error of canal 2 Swithing off error of canal 2 Safety relay closing error Safety relay opening error Ingnition error of canal 1 Swithing off error of canal 1 Software error on micro 1 Gas type change error
347 348 349 350 572 573 574 575 576 577 578 579 580 581 153 160
Unit locked Fan speed threshold
164
Flow press switch CH
active 171 Alarm contact 1 active
active 172 Alarm contact 2 active active 173 Alarm contact 3 active active 174 Alarm contact 4 active
561 562 800 805 801 802 803 806 807 804 808 565 565
Max fan speed = Postpurge fan speed accepted Input HX parameterization: limit thermostat Input HX parameterization parameterization Input HX parameterization: air presure switch 10V signal input parameterization Input H6 with 2 different funtions associated Input H7 with 2 different funtions associated Input B4 with 2 different funtions associated Bypass pump Q12 parameterization Cooling request K28 parameterization parameterization Water filling K34 parameterization Hardware reset button pressed more than 10 seconds Fan speed threshold not reached Flow pressure switch Central heating (lockout error) Flow pressure switch Central heating (temporary error) Alarm contact input input H1 Alarm contact input input H4 Alarm contact input input H2 of extension extension module module 1 Alarm contact input input H2 of extension extension module module 2 Alarm contact input input H2 of extension extension module module 3 Alarm contact input input H5 Alarm contact input input H6 Alarm contact input input H3 Alarm contact input input H7 Static water pressure limit (lockout error) Static water pressure limit (lockout error)
176 177
Water press 2 too high Water press 2 too low
178
Limit thermostat CH1
Limit thermostat Central heating 1 (mix zone)
179
Limit thermostat CH2
Limit thermostat Central heating 2 (mix zone)
195
Water refill time
196
Water refill time/week
241 242 243 260
Flow sensor yield Return sensor yield Swimming pool sensor Flow sensor 3
270
Exc temp diff h' exch
320
HW charging sensor
321
HW outlet sensor
322 323
Water press 3 too high Water press 3 too low
324
BX same sensors
325
BX/e'module same sens
326
BX/m'grp same sens
327
E'module same funct
791 795 792 796
507 1 2 565 565
Water refill time for sigle refilling elapsed (lockout error) Water refill time elapsed (temporary error) Water refill time weekly elapsed (lockout error) Water refill time weekly elapsed (temporary (temporary error) Flow sensor yield not found or in short circuit Return sensor yield not found or in short circuit Swimming sensor not found or in short circuit Flow sensor mixing zone 1 not found or in short circuit Temperature differential between flow temperature and exchanger exchanger temperature - Dry fire (lockout error) Charging DHW sensor not found or in short circuit Short circuit Open circuit Static water pressure limit (lockout error) Static water pressure limit (lockout error) More than one sensor with the same function associated More than one sensor (also on external module) with the same function associated More than one sensor (also on mixing zone) with the same function associated More than one sensor on external module with the same
328
Mix group same funct
329
E'mod/m'grp same funct
330 331 332 333 334 335 336 337
BX1 no function BX2 no function BX3 no function BX4 no function BX5 no function BX21 no function BX22 no function B1 no function
function associated More than one sensor on mixing zone with the same function associated More than one sensor (external module and mixing zone) with the same function associated No function associated to input BX1 No function associated to input BX2 No function associated to input BX3 No function associated to input BX4 No function associated to input BX5 No function associated to input BX21 No function associated to input BX22 No function associated to input B1
338
B12 no function
No function associated to input B12
339 340 343
Coll pump Q5 missing Coll pump Q16 missing Solar integration missing
Collector pump Q5 not found or not configurated configurat ed Collector pump Q16 not found or not configurated configurat ed Solar integrated not found or not configurated
344
Solar buffer K8 missing
Solar buffer not found or not configurated
345 346
Sol swi pool K18 missing Boiler pump Q10 missing
347
Solid fuel boil comp sens
348 349
Solid fuel boil addr err Buff valve Y15 missing
Swimming pool from solar not found or not configurated configurated Collector pump Q16 not found or not configurated configurat ed Solid fuel boiler comparative sensor not found or not configurated Solid fuel boiler address error Buffer valve not found or not configurated
350
Buffer address error
Buffer address error
351 353 371 372 373
Prim/sys pump addr err Casc sens B10 missing Flow temp CH3 Limit thermostat CH3 Extension module 3 359
System pump address error Cascade sensor not found or not configurated Flow temperature temperatur e Central heating 3 not reached Limit thermostat Central heating 3 (mix zone) External modul 3 not found Control value out of range
360
Calculated value over the threshold
361
Calculated value under the threshold
362
Gas valve stepper position over the threshold
363 364
Gas valve stepper position under the threshold Ionization current out of range
365
R value out of range
366 367 368 369 370 221 357
Open contact on stepper motor Short circuit on stepper motor Low supply voltage on stepper st epper motor High supply voltage on stepper motor Prevention of startup for a stepper motor is interrupted Fan speed out of range Fan speed out of range Ionization or fan speed with electrode drift test not in the defined area. Problem: Power supply, blower-PWM setting Too much corrrection of drift test Too much corrrection of drift test Drift test performed 4 times consecutive (temporary error) Control value limit reached during the test drift Ionization drift crash during testing
374
375
Sitherm Pro calculation
BV stepper motor
358 376
Drift test limit value
371 372 373 768 769
377 384 385 386
Drift test prevented Extraneous ligth Mains undervoltage Fan speed tolerance
429
Dyn water pres too high
430
Dyn water water pres too low low
431
Primary exch sensor (aluminium exchanger)
432
Function ground missing
433
Heat exch temp
418
558 559 557 1 2 547 548 746 747 508 509
Drift test counter c ounter monitor has excedded Flame present with gas valve closed Low supply voltage Fan speed out of range Dynamic water pressure too high (lockout error) Dynamic test times excedded (lockout error) Dynamic pressure test failed (lockout error) Short circuit (temporary error) Open circuit (temporary error) Short circuit (lockout error) Open circuit (lockout error) Feedback error from PCB (SR) Feedback erro from gas valve realy (BV1) Exchanger temperature > 95°C (lockout error) Exchanger temperature > 95°C (temporary error)
4
GAS ADA PTIVE SYSTEM
LUNA4 is provided with a brand new system GAC (Gas Adaptive Control): the electronic control together with the gas valve grant an automatic control of the combustion and ensure the following advantages during the installation as well as for the end user: • Reduction of the time for the installation, as any manual intervention has been deleted (adjustment or nozzles change); • The boiler is able to adapt to the quality of the gas and to the length of t he flue tubes maintaining a constant efficiency helping a reduction of the gas consumption and generating less pollution. The Gas Adaptive System maintains correct combustion by comparing the measured Flame Signal and the Reference Flame Signal. The Reference Signal follows a set curve depending on fan speed and it is part of the software. The system measures constantly the signal during the operation of the boiler and adjusts the gas flow rate in order to maintain the correct signal and the correct CO level. In this way is also considered the oxidation of the component (flame electrode and burner). The electronic gas valve has a modulator used to set the properly flame signal and so the correct air / gas ratio (LAMBDA). If the system is not able to assure the correct flame signal the boiler goes in lockout. The flame signal detected by the burner control is independent from: - value and type of supply voltage; - quality of the ground in the installation.
5
FAULT FAUL T FINDING 1 Initial Fault Finding Checks 1. Check that gas, water and electrical supplies are available at the boiler. NOTE: When instructed press and hold the ‘Reset’ for between 1-3 seconds to reset the boiler.
2. Electrical supply = 230V ~ 50 Hz. 4. The preferred minimum gas pressure is 10 mbar. 5. Carry out electrical system checks, i.e. Earth Continuity, Resistance to Earth, Short Circuit and Polarity with a suitable meter. NOTE: These checks must be repeated after any servicing or fault finding. 6. Ensure all external controls are calling for heat and check all external and internal fuses. Before any servicing or replacement of parts, ensure the gas and electrical supplies are isolated.
Table Of Error Codes
18.2 Error Codes 1. If a fault occurs on the boiler an error code may be shown by the facia display.
E20
Central Heating Flow NTC Fault
2. The codes are either a flashing two or three digit, number preceded by the symbol 'E '.
E28
Flue NTC Fault
E40
Central Heating Return NTC Fault
E50
Hot Water NTC Fault
E83
Communications error
E109
Pre-Circulation Fault
E110
Safety Thermostat Operated
E111
Maximum flow temperature exceeded
E117
System Water Pressure Too High
E118
System Water Pressure Too Low
E125
Circulation Fault (Primary Circuit)
E128
Flame Failure
E130
Flue NTC Operated
E133
Interruption Of Gas Supply or Flame Failure
E151
PCB Fault
E160
Fan or Fan Wiring Fault
E384
False flame
E20, E28, E40, E50, E83, E151, E160 and E384 indicate possible faulty components. E110
and E111 shows overheat of the primary.
E117 is displayed when the primary water pressure is more than 2.7 bar. E118 is displayed when the primary water pressure is less than 0.5 bar. E133
indicates that the gas supply has been interrupted, ignition has failed or the flame has not been detected. E125 is displayed in either of two situations:i) If within 15 seconds of the burner lighting the boiler temperature has not changed by 1°. ii) If within 10 minutes of the burner lighting the boiler temperature twice exceeds the selected temperature by 30°. In these instances poor primary circulation is indicated. E128 is displayed if there has been a flame failure during normal burner operation.
3. By pressing the 'Reset' button for between 1-3 seconds when E 110, E125 & E133 are displayed it is possible to relight the boiler.
4. If this does not have any effect, or error codes are displayed regularly further investigation is required. .
.
Refer to Annex 1 “Illustrated Wiring Diagram” for position of terminals and components Central Heating - Follow operational sequence NO * Turn on mains power. Go to section ‘A’ If Error 83, 151 or 384 is flashing or re-occurs regularly The display illuminates check all PCB and communication connections, if this has no effe effect ct chan chan e PCB. PCB. YES * Error 110 flashing Error 111 flashing Error 133 flashing Error 125 flashing
YES
NO
Press the ‘Reset’ button for between 1-3 seconds
NO
If the E110 or E111 is still flashing. Go to section ‘H’
YES
Error 20, 28, 40 or 50 flashing
Go to section ‘D’
NO YES
Go to section ‘I’
Error 117 or 118 flashing NO
Ensure controls are set to demand and verify the contacts are closed
CH Rad. Symbol flashes
NO NO
Set the Central Heating temperature to Maximum. Pump runs.
YES
Ensure all controls and Programmers are calling for heat
Go to section ‘B’
YES
Fan runs after up to 3 minutes
NO
Error 160 flashing Go to section ‘C’
NO
Error 160 flashing Go to section ‘C’
YES
Fan runs at correct speed YES
Spark at ignition electrodes for up to 5 seconds and for 4 attempts. YES
NO
YES
Error 133 flashing
Go to section ‘F’ Press the ‘Reset’ button for between 1-3 seconds
Go to section ‘E’
NO
YES YES
Burner does not stay alight after 5 seconds
Burner lights
NO
Error 128 or Error 374 flashing. Go to section ‘N’
YES YES
YES
Error E125 flashing after 1 minute
Error E109 flashing
Error 133 flashing. Go to section ‘G’
Go to section ‘J’
NO YES
Error E110 or E111 flashing
Go to section ‘H’
NO NO
3 way valve open to central heating circuit
Go to section ‘K’
YES
Burner output modulates to maintain the temperature set YES
Burner goes out
Check the Central Heating NTC sensor Go to section ‘D’
YES
Go to section ‘M’
Error E130 flashing NO
NO
YES
YES
Fan stops after 10 seconds
Operation sequence successful
Fault Finding Solutions Sections
A
Is there 230V at: NO
1.
Main terminals L and N
Check electrical supply
YES
NO
2.
Main terminal fuse
Replace fuse
YES
Display illuminated
NO
3.
B
PCB – X10 connector Mains terminals L & N
Connection OK at connector x40
Check wiring
Main or Display PCB fault
NO
Switch to DHW mode maximum flow rate and press reset. During the next three minutes is there:-
230V at PCB –connector x13 pump terminals Blue to Brown (See Wi ring Diagram)
YES
230V between PCB –connector x13 pump terminal Blue and PCB –connector x11 pump terminal Black. (See Wiring Diagram)
NO
Replace PCB
YES
YES
230V at Pump
NO NO
Replace Pump
Replace PCB
Check wiring
C
NO
1.
Fan connections correct at fan and PCB Connectors X11 & X23 See Wiring Diagram Diagram
Make connections
YES
YES
Is there 230V AC at fan terminals connector X11 blue to brown. See Wiring Diagram NO
Replace PCB
YES
Fan jammed of faulty winding
Replace fan
Temperature sensor faulty. Check correct location and wiring
D
YES
Cold resistance approximately 10kΩ @ 25° C (DHW and CH sensors) (resistance reduces with increase in temp.)
Gas at burner
E
NO
NO
Replace sensor
Ensure gas is on and purged
YES
Check wiring & PCB – X15 connector, is there 24 V DC across Gas valve terminals black to green. See Wiring Diagram.
Replace gas valve
NO
Replace PCB
F
NO
Check and correct if necessary 1. Ignition electrode and lead 2. Electrode connection 3. Spark gap and position
G
YES
Check wiring. Voltage at PCB – X15 connector is 24V DC across the igniter unit terminals Blue to Brown for 5 seconds during ignition phase . See Wiring Diagram
1.
Check the gas supply pressure: For Natural Gas greater than 10 - 11 mbar
2.
Check and correct if necessary 1.CO2 values - see instruction 2. Flame sensing electrode and lead connections 3. Flame sensing electrode position
YES
Replace PCB YES
Replace PCB
Flame current should be more than 1,7 μ A NO
Replace flame sensing electrode
Replace igniter unit
H
Overheat thermostat operated or faulty.
NO
Check for and correct any system faults. NO
Allow to cool. Continuity across thermostat terminals more than 1.5 ohm
YES
Replace safety thermostat YES
NO
YES
Is E110 or E111 still flashing
Check Flow, Return, sensors. See section ‘D’
I
CH system pressure less than 0.5 bar or more than 2.7 bar. NO
J
Ensure that the system and boiler are fully vented.
YES
Restore System Pressure YES
Check wiring and pcb connection at connector x22 is there approx. 5 V DC between the green and black terminals
Replace pressure sensor NO
Replace PCB
NO
System fault, correct.
Check flow temperature sensor connections and position. Cold resistance approximately. 10kΩ @ 25° C (CH sensors) (resistance reduces with increase in temp.)
YES
NO
YES
Go to section ‘B’
K
Is there 230V at:
1
PCB connector x13 3 way valve terminals Blue to Black central heating mode Blue to Brown domestic hot water mode See Wiring Diagram
NO
Replace PCB
YES
Check 3 way valve cable.
YES
2
Motor, 3 way valve
Replace motor 3 way valve
Replace sensor
Replace PCB
L
Is mains water filter and assembly clean and the rotor free to move.
YES
PCB connector x22 Hall effect sensor terminals. Check that the voltage is approximately 5 V DC between Red and Blue See Wiring Diagram
YES
Replace Hall Effect Sensor
NO NO
Clean or replace
Replace PCB
M 1.
Temperature sensors faulty. Cold resistance approximately 10kΩ @ 25° C (CH sensor) 20kΩ @ 25° C (Flue sensor) (resistance reduces with increase in temp.)
NO
Replace sensor
YES
2.
If pump is running the heat exchanger could be obstructed
Replace heat exchanger
N E128 flashing E374 flashing
Check if there is recirculation of flue gas in the sealed chamber
YES
NO
1.
NO
2.
E376 flashing
YES
1.
Check and correct if necessary: 1. Selection of gas type 2. Flame sensing electrode position
Check supply pressure at the gas valve Check and correct if necessary: 1. Selection of gas type 2. Flame sensing electrode and lead connections 3. Flame sensing electrode position
Check wiring and PCB X25 connector (stepper motor gas valve) and X15 (EV gas valve)
Reset Drift Test results: -press both buttons for 6 seconds -enter at “specialist” level -go to Sitherm Pro menu -go to parameter 2749 -select yes
YES
NO
Replace PCB Replace flame sensing electrode
YES
Replace gas valve
NO
Replace PCB
WIRING DIAGRAM
6
BURNER BURNER PHASE (fault hist hi stor ory) y)
Phase 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Description Permitted afterburn time Permitted time with air pressure switch closed or fan speed Permitted time with fan speed Standby Start prevention Maximum fan ramp-up time to prepurge speed Maximum fan ramp-up time to ignition speed Preventilation Maximum time to reach ignition speed after prepurging Maximum waiting time 1 Maximum waiting time 2 Preignition time 1st safety time (gas valve open) 2nd safety time (gas valve close) Interval (flame stabilization) Control mode Change to postpurging at last operating speed Change to postpurging at prepurge speed Postpurging at last operating speed Temporary error Lock-out error Postpurging at prepurge speed Chimney drying