Saep 58 PDF

March 30, 2023 | Author: Anonymous | Category: N/A
Share Embed Donate


Short Description

Download Saep 58 PDF...

Description

 

 

Engineering Procedure

 

SAEP-58 29 October 2015 Factory and Site Acceptance Testing Requirements for Large Gas Metering Systems Document Responsibility: Responsibility: Custody Meas Measurement urement Standards C Committee ommittee

Contents   1

Scope............................................................. Scope............................................................... 2 

2

Conflicts and Deviations......................... Deviations................................. ........  2 

3

Applicable Documents............................... Documents.................................... .....  2 

4

Definitions and Acronyms............................... Acronyms............................... 4 

5

Instructions......................................................5  Instructions......................................................

6 7

Factory (Site) Acceptance Test report…….... ...... 5  Responsibilities...............................................  6  Responsibilities...............................................

8

Prerequisites...................................................  6  Prerequisites...................................................

 Appendix 1 - Factory Acceptance Test Procedure and an d Reporting........................ Reporting........................  7   Appendix 2 - Site Acceptance Test Procedure and an d Reporting...................... 23  23 

Next Planned Update: 29 October 2018 Previous Issue:  New   New  Primary contacts: Escobar, Juan David (escobajd ) on +966-13-8801375 dovallx)) on +966-13-8801393 Do Val, Luiz Gustavo (dovallx Copyright©Saudi Aramco 2015. All rights reserved. 

Page 1 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

1

Scope This procedure specifies the requirements to conduct Factory Acceptance Test (FAT) and Site Acceptance Test (SAT) (SAT) for the Large Gas Metering Metering Systems. Conducting these tests is mandatory in  in SAEP-21  SAEP-21 and  SAEP-50 SAEP-50..  The purpose of the FAT is to demonstrate, to the fullest extent possible at the Contractor's facility, that the subject Large Gas Metering System meets all requirements of the Job Specification, particularly the Functional Specification Document before it is shipped to the site. The test shall include the functionality of the Metering Skid (software, hardware AB-036184..  and special application packages) as per  34-SAMSS-154  34-SAMSS-154 and  AB-036184 The purpose of the SAT is to demonstrate that the subject Large Gas Metering S System ystem is ready for commissioning and operation.

2

3

Conflicts and Deviations Deviations 2.1 Any conflicts between this procedure and other applicable Saudi Aramco Engineering Standards (SAES’s), Materials System Specifications S pecifications (SAMSS’s), Saudi Aramco Standard Drawings (SASD’s), or industry standards, codes, and codes,  and forms shall be resolved in writing by the Manager, Process P rocess & Control Systems Department of Saudi Aramco, Dhahran. 2.2

Direct all requests to deviate from this procedure in writing in accordance with SAEP-302  S ystems Department of Saudi SAEP-302 to the Manager, Process & Control Systems Aramco, Dhahran.

2.3

Direct all requests for interpretation of this procedure in writing to the chairman, Custody Measurement Standards Committee for for resolution. The Chairman, Custody Measurement Standards Committee shall be solely responsible for determining whether a proposed request meets the requirements of this  procedure.

Applicable Documents All referenced Procedures, Standards, Specifications, Codes, Forms, Drawings, and similar material or equipment supplied shall be considered part of this Procedure P rocedure to the extent specified herein and shall be of o f the latest issue (including all revisions, addenda, and supplements), unless stated otherwise.

Page 2 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

3.1

Saudi Aramco References Saudi Aramco Engineering Procedures SAEP-21 SAEP-21  

Project Execution Requirements for Saudi Aramco  Royalty/Custody  Royalty /Custody Metering Metering Systems Systems

SAEP-50   SAEP-50

Project Execution Requirements for Third Party  Royalty/Custody  Royalty /Custody Metering Metering Systems Systems

SAEP-302 SAEP-302  

 Instructions  Instructions for Obtaining Obtaining a Waiver Waiver of a Mandatory Mandatory Saudi Aramco Engineering Requirement

Saudi Aramco Engineering Standard SAES-A-112  SAES-A-112 

 Meteorological  Meteorological and Seismic Design Design Data

Saudi Aramco Material System Specifications 34-SAMSS-154 34-SAMSS-154  

 Large Gas Gas Metering System System with Ultrasonic Flow  Meters

34-SAMSS-846  

Flow Computers for Custody Transfer Measurement of Hydrocarbon Gases

Saudi Aramco Standard Drawings  AB-036019  AB-036019  

Thermowell Assembly and Detail

 AC-036045   AC-036045

 Detail Vent, Vent, Drain and and Sample Connections Connections

 AE-036046  46    AE-0360

Standard Sample Tube

 AB-036184  AB-036184  

 Large Metering Metering Skid (Gas) (Gas) –  Ultrasonic  Ultrasonic Flow Meter  Based

Saudi Aramco Library Drawings  DC-950040    DC-950040

Pressure Indicators and Switches

 DC-950042  DC-950042  

 Instrument  Instrument Piping Details Details - Pressure Pressure Instruments Instruments

 DC-950061    DC-950061

Flow Meter Installations - Gas and Vapor Service (Non-Corrosive)

Saudi Aramco Form and Data Sheet SA-7213-ENG   SA-7213-ENG 

3.1

 Mechanical  Mechanical Completion Completion Certificate Certificate

International References  AGA Report Report 8

American American Gas Association Association Page 3 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

4

Definitions Definitions and Acronyms 4.1

Definitions Approve: Review and formal acceptance characterized by the signature of a final authorizing individual or organization. Company: Refers to a Saudi Arabian Oil Company (Saudi Aramco). Custody Transfer Measurement: A specialized form of measurement that  provides quantity and quality information used for the physical and fiscal documentation of a change in ownership and/or responsibility of hydrocarbon commodities. This includes measurement of hydrocarbon liquid movements (deliveries or receipts) between Saudi Aramco and its customers, suppliers, supp liers, joint ventures and transport contractors including VELA ships. Factory Acceptance Test (FAT): Test to demonstrate compliance of the System with the job specification requirements, to the maximum extent possible in the Contractor's factory environment. Functional Specification Document (FSD): Provides the technical requirements for the System. Job Specification: The scope of the work to be performed pursuant to a contract; it describes or references the applicable drawings, standards, specifications, as well as the administrative, procedural, and technical requirements that the Contractor shall satisfy or adhere to in accomplishing the work. Large Gas Metering System: A metering system designed to handle gas flow rate of 200 MMSCFD or higher. Pre-FAT: A comprehensive test, completed prior to FAT, which ensures that the System can be tested according to FAT procedures without unanticipated delays. Site Acceptance Test (SAT): The acceptance test, performed on the installed System that demonstrates compliance with all requirements, except availability. un der the Contract. System: The metering skid system that is procured under Ultrasonic Meter: A fluid flow measuring device that utilizes transit-time ultrasonic signals to measure the flow rate. Vendor: The party that supplies or sells integrated metering systems, metering equipment, or components sometimes called Integrator.  Page 4 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

4.2

5

Abbreviations FAT

Factory Acceptance Test

FSD

Functional Specification Document

MSC

Metering Supervisory Computer

PLC

Programmable Logic Controller

SAEP

Saudi Aramco Engineering Procedure

SAES

Saudi Aramco Engineering Standard

SAMSS

Saudi Aramco Material Specification System

SASD  SASD 

Saudi Aramco Standard Drawing

SAT

Site Acceptance Test

UFM

Multi-Path Ultrasonic Transit-Time Flow Meter

VID

Vendors Inspection Division

Instructions The FAT and SAT Reports shall meet the following minimum specific requirements: a)

Identify System and Contractor

 b)

Include certification statement

c)

FAT and SAT location, start date, completion date

d)

Contractor representative signature

e)

Company representative signature

f)

A FAT and SAT Punch List (exception items).

Appendix 1 1  is the outline of the FAT Procedure and Report. The FAT Procedure shall contain, as a minimum, the information specified and, except for any additions, need to follow the format of the outline. 2  is the outline of the SAT Procedure and Report. The SAT Procedure shall Appendix 2 contain, as a minimum, the information specified and, except for any additions, need to follow the format of the outline.

6

Factor Factor y (S (Site) ite) Accept ance Test Test Repor Repor t Appendices 1 & 2 shall serve as the FAT and SAT reports and when approved by the Appendices  Company representatives shall be used as the certification that the FAT and S SAT AT has  been successfully completed. Page 5 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

 Note that that as a minimum minimum a cover page, a system system acceptance acceptance certifi certificate cate page and and the table table of contents need to be added to Appendixes  Appendixes  1 & 2 to complete the FAT and SAT reports.

7

Responsibilities The responsibilities of all Saudi Aramco organizations participating in the FAT and SAT of metering skids are stated in the  the  SAEP-21 SAEP-21  and  SAEP-50. SAEP-50.  The assigned Saudi Aramco Project Management Team engineer is responsible for ensuring that the concerned organizations fulfill their responsibilities.

8

Prerequisites All items that are a part of the System to be tested during the FAT and SAT shall be verified to be present. present. Specific items include system equipment (hardware, firmware, and software), including part numbers and revisions numbers as necessary for identification and verification. All test equipment needed for all aspects of the FAT and the SAT shall be identified. identified. Calibration reports of test test equipment shall be available  prior to the start of FAT and SAT. 8.1

Pre-FAT and pre-SAT The Vendor shall conduct a Pre-FAT and Pre-SAT. Pre-FAT and Pre-SAT are  basically  basical ly a trial trial run of all FAT FAT and SAT SAT procedures procedures to identify identify and correct correct any deficiencies that could cause delays during FAT and SAT. The pre-FAT and Pre-SAT are carried out without the presence of Company representatives. The purpose of the pre-FAT and pre-SAT are to ensure that all hardware, software, and application program deficiencies have been identified and corrected  before the official official FAT FAT and SAT (for example: example: incorrect incorrect wiring wiring from the test test  panel to to the I/O I/O points, points, incorrect incorrect wiring wiring inside inside the equipment, equipment, bad bad I/O modules). modules). Formal, signed shall be submitted Saudi Aramco before pre-FAT a date forand the pre-SAT FAT and reports SAT can be set, the vendortoshall complete Pre-FAT and Pre-SAT utilizing the approved FAT and SAT  procedure/report.

8.2

Utility Requirements Vendor shall provide all needed utilities to perform tthe he FAT. Some of these utilities are: Control Panel power supply and Instrument Instrument air or nitrogen. nitrogen.

29 October 2015

Revision Summary New Saudi Aramco Engineering Procedure that provides the FAT and SAT procedures for the Large Gas Metering Systems.

Page 6 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

 Ap pen di x 1 - Fact Fa ct or y Ac A c ce cept pt anc e Test Tes t Pr oc edu r e and Repo r ti ng 1.

Introduction This document is the FAT Procedure to inspect i nspect and verify the functionality of the Large Sales Gas Metering Skid and associated control panel pa nel built under (Indicate BI number) to be located in (Indicate (Indicate location). This document contains detailed test procedures with associated lists, tables and a customer comment and sign off area in order to verify and document that each test has been carried out successfully and in accordance with the customer specification (FSD). This procedure has been submitted for for client review and approval. FAT will be  performed against this document in the presence of the client or the client nominated representatives. Any divergence from the agree requirement (FSD) will be formally advised to the client such that revision of the requirement may be agreed and the FSD and this document are altered accordingly. 1.1

Scope All instruments calibration will be verified during FAT and will be wired to the control panel and a functional test is carried out by simulating process conditions at the field instruments and the results are recorded on Test Record Sheets. Metering Tests will be conducted with the field I/O’s I/O ’s connected  connected to the flow computer and reports will be validated against a gainst commercial AGA 8 software. A set of master documentation (Master FAT), drawings and ISS (data sheets) will be made available for the FAT (refer to to Section 1.3). Any discrepancies will be recorded on the Punch List and any document/drawing changes will be marked in the “Master FAT” copy cop y for incorporation to the documents that will  be made available at the SAT.

1.2

Test Overview The FAT will begin with a full review of o f the system and documentation followed by the inspection of the skid, the verification of the calibration of the field instruments and loop checks and finally the configuration of the flow computer. A daily review will be carried out discussing the day’s da y’s test agenda and the  previous day’s test activities and issues. The test will follow a structured plan according to this document. Page 7 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

Any test failures will be fully documented and discussed at the daily review. Failures will be evaluated and prioritized according to impact on both further system testing and test schedule time frame. Test schedule shall be modified tto o continue testing on the unaffected unaffected part of the system. Low priority failures failures which cannot be rectified immediately and do not prevent further testing will be revisited at the end of the scheduled test period. Every effort will be made to rectify high priority failures and retest as soon as they have been resolved. 1.3

Applicable Documents All documents referenced in the FAT Procedure shall be list listed. ed. All documents shall have revision revision numbers and publishing publishing date. Documentation which is part of System and/or is needed during FAT shall be available. Specific items typically include User's Manuals, Maintenance Manuals, configuration drawings, connection drawings, database listings, logic drawings, instrumentation loop drawings (ILD), P&IDs. Title Functional Specification Document Piping and Instrumentation Diagram System Block Diagram Control Panel Termination Details/Loop Diagrams Instrument Specification Sheet Pressure Transmitters Detailed and Complete Technical Information Temperature Transmitter Detailed and Complete Technical Information USM Detailed and Complete Technical Information Gas Chromatograph Detailed and Complete Technical Information Pressure Gauges Detailed and Complete Technical Information Flow Computer Detailed and Complete Technical Information Printer Detailed and Complete Technical Information Sampler (if provided) Detailed and Complete Technical Information Saudi Aramco Detail Vent, Drain and Samplers Saudi Aramco locally mounted pressure indicators and switches

Document Number Revision Date

AC-036045 & AE-036046 DC-950040

Page 8 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

Title

Document Number Revision Date

Instrument Piping Details –  Details –  Pressure  Pressure Instruments –  Instruments  –  Blind   Blind and Indicating type Saudi Aramco Thermowell Assembly and Detail Appendix 1A of  34-SAMSS-846   34-SAMSS-846

DC-950042

Flow Computer instrument specification sheet

SA-8020-846ENG

AB-036019

Meter tube diameters tolerance certificate System As-Built drawings Bill of materials FAT test results

1.4

Test Equipment All test equipment needed for all aspects of FAT has been identified. Calibration/Certification reports of test equipment are available. Description

Manufacturer

Model

S/N

Cal date

Digital Multimeter Hart Communicator Hi pressure tester Decade Box Tape measure

1.5

N/A

N/A

Terms and Abbreviations Definitions of all acronyms, mnemonics, and special terms used in this th is Procedure shall be provided. D

Pipe Nominal Diameter

DB&B

Double Block and Bleed

FAT

Factory Acceptance test

FSD

Functional Specification Design

GC

Gas Chromatograph Page 9 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

2.

HMI

Human Machine Interface

MOV

Motor Operated Valve

MSC

Metering Supervisory Computer

OSPAS PIB

Oil Supply Planning & Scheduling Department Process Interface Building

PLC

Programmable Logic Controller

P&CSD

Process & Control Systems Department

SAEP

Saudi Aramco Engineering Procedure

SAMSS

Saudi Aramco Materials System Specification

SAPMT

Saudi Aramco Project Management Team

SPU

Signal Processing Unit

UPS

Uninterruptible Power Supply

USM

Ultrasonic Meter

System Checks The tests shall demonstrate and document the satisfaction of all requirements of the System as stated in the Job Specification. The test procedure consists of tables with questions to outline a very detail inspection. 2.1

Skid Mechanical Inspection All equipment/instrumentation should be checked for correct mechanical installation as follows:

TEST Is the metering system fabricated in accordance with the approved P&ID? Are instruments tagged in accordance with the latest issue of the P&ID?

Y/N

Punch List Item #

Does the meter have a minimum of four ultrasonic paths? Is the meter equipped with provisions provisions (such as valves) and all necessary additional devices, mounted on the transducer  ports in order to make make it possible to remove remove transducers fo forr inspection or replacement while the meter is under  pressure? Does the meter body have at least one pressure tap for measuring the static pressure? Page 10 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

TEST

Y/N

Punch List Item #

Is the Static Pressure Transmitter impulse line run as indicated in library drawing DC-950042? Is the nipple coming out the USM for the pressure transmitter welded to the USM and to the root valve? Does the UFM have a permanently fixed sunshade with a top and three sides to protect the transducers, the SPU and the cables? Do the gaskets have the inner diameter 10mm larger than the meter tube bore? Are the upstream and downstream meter tube sections constructed out of seamless pipe?  Note: Seamed pipe pipe may be used for 24 inch meter tubes tubes and larger if the internal longitudinal welds are ground flush and smooth. Are the upstream and downstream meter tubes internal diameters stamped on stainless steel data plates  permanently attached to the meter meter tubes? Are the internal welds with the flanges/ fitting are flush ground with the internal diameter of the pipe and free of sharp edges or abrupt changes in surface level or diameter. Is the flow direction indicated on the meter tube close to each side of the flow meter? Does the upstream meter tube consist of two sections with a total minimum clear length of 20D? Is there a flow conditioning plate installed in the middle of the upstream meter tube? Is the upstream meter tube flange-ended and equipped with a spacer ring or jack screw so that the tube sections and the flow conditioner can be easily removed for inspection and cleaning? Does the flow conditioning plate have provisions (such as marking or pin) to ensure that it will be installed in stalled in the same orientation whenever the conditioning conditioning plate is taken out. Does the downstream meter tube have a minimum clear length of 5D? Is there a thermowell installed at least 5D downstream of the USM at each meter tube? Is there another thermowell installed installed downstream of the first one and at a distance between 150 and 300 mm? Are the thermowells installed in 1 inch NPT tap fittings?

Page 11 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

TEST

Y/N

Punch List Item #

Is the following information stamped on the stainless steel tag permanently attached to the meter body? Manufacturer Model Number Serial Number Month and Year of Manufacture Total Weight Tag Number  Nominal Size Size Flange Rating Maximum and minimum actual flow rates at operating conditions Maximum and minimum operating pressure and temperature K-Factor Meter body design code and material Meter flange design code and material Internal diameter @ 68°F Acoustic Path 1 length @ 68°F Acoustic Path 2 length @ 68°F Acoustic Path 3 length @ 68°F Acoustic Path 4 length @ 68°F Axial Distance between Transducer pairs @ 68°F Thermal Expansion Coefficient Does each transducer have a permanently permanently marked serial number? Is the flow direction indicated by an arrow on the meter  body and/or by the words UPSTREAM UPSTREAM and DOWNSTREAM on the piping connections? Is there a check meter meter in “Z” configuration?  configuration?  Are the operational meter(s) and the check meter equally size and calibrated across the entire operational flow range? Does each meter run have inlet DB&B isolation MOV? Is there a 2” flanged inspection inspection fitting at no less les s than 150 mm downstream of the thermowells mounted 45 o  facing the flow?

Page 12 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

TEST

Y/N

Punch List Item #

Is there a DB&B isolation MOV on the connection pipe pipe to the check meter? Does each meter run have outlet DB&B isolation MOV? Is the control system mounted in a process interface  building? Are instruments and valves located at convenient working heights and accessible? Are pipe header stubs provided? Are there two identical Flow Control Valves with upstream and downstream isolation valves installed in  parallel and downstream downstream of the met meter er runs? Is there an Isolation Valve with remote closing capability from OSPAS? Is there a GC and sample probe installed according to SASD-AC-036045? Is there a vent line? Does the vent line extent at least 3 meters above the highest operating platform? Are vents, drains and samplers installed according to AC036045 and AE-036046? Is there a pressure gauge installed on the skid’s inlet header? Is there a pressure gauge installed on the skid’s outlet header? Are pressure gauges installed as per DC-950040? Are all transmitters grouped in a single point facing the same direction? Is there a fix calibration table adjacent adjacent to the instruments? Is there adequate sunshade to protect the transmitters? Are pressure transmitters’ impulse lines with a slope of not less than 1:12 toward the USMs? Is there a sample probe installed on top of the pipe and on the downstream side of the metering skid?

Page 13 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

2.2

Skid Electrical Inspection

TEST

Y/N

Punch List Item #

Are field junction boxes installed in accessible locations at the edge of the meter skid? Do conduit and cable connections enter junction boxes from the bottom? Is conduit sealed with a weather-tight seal at the entrance of the box? Is the flow computer powered by a UPS system?

2.3

Loop testing and Functionality Checks Verify that the basic functionality associated with the System I/O works  properly as evidenced on the Flow Computer display. This willproperly, include checks that the I/O are wired properly, configured prope properly, rly, displayed and documented properly. 2.3.1

Temperature

TEST

Y/N

Punch List Item #

Are thermowells installed in a 1 inch NPT tap fitting? Are RTD(s) of the 4-wire type? Are RTD(s) of the spring loaded type type?? Is temperature transmitter of the SMART type? Is the temperature transmitter range from 0 –  150°F  150°F (4 (4 –   –  20  20 mA)?

Page 14 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

TEST

Y/N

Punch List Item #

Y/N

Punch List Item #

Using the resistance box, apply resistance values to the transmitter as this: Temperature

Resistance

Span

(F)

(Ohms)

(%)

0

93.03

0

37.5

101.19

25

75

109.30

50

112.5

117.36

75

150

125.37

100

Using a certified thermometer compared the thermometer reading to the transmitter reading (Using a HART communicatorr if transmitter has no display). Is the communicato difference between these readings less than 0.5 F? Compare table above to Flow Computer and HMI readings. Are these readings within 0.5°F?

2.3.2

Static Pressure Transmitter

TEST

Is pressure transmitter of the SMART type? Verify calibration of pressure transmitter at 0, 50, 100% increasing and 80, 20, 20, 0% decreasing. decreasing. Using a certified  pressure tester compared compared the tester readin reading g to the transmitter transmitter reading (Using a HART communicator if transmitter has no display). Is the difference between between these reading readingss less than 0.25% of span? Compare transmitter’s pressure reading to Flow Computer and HMI readings. readings. Are these readings readings within 0.25% of span? Is the pressure transmitter fitted with a 3-way manifold valve? Are the impulse lines ½ inch type 316 stainless steel tubing?

Page 15 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

2.3.3

Pressure Gauges

TEST

Y/N

Punch List Item #

Y/N

Punch List Item #

Is the operating pressure within 30% to 70% of the scale range? Are pressure gauges filled with a viscous liquid? Is the diameter of the pressure gauges 4 ½ inches? Is the background of the pressure gauges white with black numbers?

2.4

Flow Computers

TEST

Are there redundant flow computers? Are the flow computers connected in multi-drop network configuration with OSPAS? Are the flow computers tagged according to SA-8020-846ENG? Are the flow computers configured configured to use the USC system of units? Are the reference pressure and temperature configured to be 14.73 psia and 60 F respectively? Are the flow computers configured configured with the correct USM internal diameter (stamped on tag attached to the meter  body)?

Page 16 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

TEST

Y/N

Punch List Item #

Are the flow computers atmospheric atmospheric pressure configured according to following table? Location

Atm. Press. (psia)

Dhahran

14.542

Jubail

14.679

Qasim

13.606

Ras Tanura

14.693

Riyadh

13.667

Shedgum

14.191

Yanbu

14.686

For other areas the following equation shall be utilized: Patm= 14.54*[55096-(elevation[ft]-361)/[55096+(elevation[ft]361)] where “elevation” is obtained from  from SAES-A-112.  Is the low flow cut off set to be 0.020 ft/s? Is the flow computer configured to read a temperature of 0 –  0 –  150°F?  150°F? Is the flow computer configured to read a static pressure according to the transmitter’s calibration?  calibration?  Is the flow computer configured to use fallback values of  pressure and temperature temperature on transmitt transmitter er failure? Open the Temperature Transmitter loop (normally it is easy to open the loop at the fuse). Does the flow computer computer take the temperature fallback value? Open the Static Pressure Transmitter loop (normally it is easy to open the loop loop at the fuse). Does the flow computer computer take the pressure override value? Generate a Delivery Delivery Ticket. Does the ticket ticket follow the form indicated in 34-SAMSS 34-SAMSS-846 -846 Appendix 1A? Is the flow computer configured to use the dual pulse signals as primary? Is flow computer configured to compute as per AGA 5, AGA 8, AGA 9 and AGA 10?

Page 17 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

TEST

Y/N

Punch List Item #

Y/N

Punch List Item #

Force transmitters according to following table: Flow Velocity

12 m/s

Temperature

100°F

Static Press.

375 psig

Methane

85%

Ethane

5%

Propane

1%

CO2 

2%

 N2

7%

Pipe ID

6 in

Is the compensated flow rate calculated within ± 0.1% of 17.09884 MMSCFD? 

2.5

MSC

TEST

Are the flow computers connected to the MSC via serial communication communicat ion link? Is the MSC located in a console suitable for its location inside the PIB? Is there a laser printer connected to the MSC? Are the following software packages installed in the MSC?   HMI designed for gas metering applications   USM package for configuration and diagnosis   GC package for configuration and diagnosis   Flow computer package for configuration. Are copies of the above software packages provided in electronic (CD) format with installation instructions? Does the HMI show data in a graphical format similar to the field arrangement? ar rangement? Does the HMI real time data includes, as a minimum, gross flow rate, net flow rate, temperature, pressure, heating value, gas composition and density? Is there a table including daily totals for volume and energy? 



 

Page 18 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

TEST

Y/N

Punch List Item #

Y/N

Punch List Item #

Is there a table including daily averages for flow rate, temperature, pressure, specific gravity and gas composition? Is there a table for real time and historical alarms? Can the HMI capture reports from the primary flow computer (daily tickets, meter comparison report)? Can the HMI archive reports from the primary flow computer (daily tickets, meter comparison report)? Can the HMI print reports from the primary flow computer (daily tickets, meter comparison report)? Does the HMI print the daily tickets automatically at midnight base on the primary computer? Does the HMI print the daily tickets upon manual request  base on the primary computer? Can the HMI trend critical values including the USMs diagnostic parameters? Can the HMI initiate controlled comparison of the operational meter(s) using the check meter? Can the MSC communicate with the GC to display analysis, archive results and verify the configuration? configuration? Does the MSC have a direct serial link to the USM? Do the inlet and outlet isolation MOVs have limit switches for indication of valve position at the MSC?

2.6

PLC

TEST

Is there a PLC connected to the MSC with dual communication links? Does the PLC provide Open/Stop/Close commands for each MOV? Does the PLC provide Remote/Local status for each MOV? Does the PLC provide reverse travel before completion-ofa-command for each MOV? Does the PLC refuse sequential operation if any of the affected valves is in local position?

Page 19 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

TEST

Y/N

Punch List Item #

Y/N

Punch List Item #

Does the PLC follow the next sequence in response to a “Compare Meters” command from the MSC?  MSC?  1. Ensure the inlet MOV of the check meter is closed 2. Open check meter outlet MOV 3. Open MOV on the connection pipe from the meter to be verified 4. Close the meter run outlet MOV Does the PLC follow the next sequence after completion of the ultrasonic meter comparison? 1. Open the meter run outlet MOV 2. Close the MOV on the connection pipe from the meter to be verified to the check meter 3. Close the check meter outlet MOV Does the PLC follow the next sequence after an “Open Meter Run” command from the MSC?  MSC?   1. Ensure the MOV on the connection pipe from meter run to the check meter is closed. 2. Open the inlet MOV for the meter run. 3. Open the outlet MOV for the meter run. Does the PLC follow the next sequence after a “Close Meter Run” command from the MSC?  MSC?   1. Ensure the MOV on the connection pipe from meter run to the check meter is closed. 2. Close the meter run outlet MOV. 3. Close the meter run inlet MOV. MOV.

2.7

FCVs

TEST

Are there 2 FCVs in parallel installed downstream of the meter? According to the ISS, is each FCV rated to handle 100% of the maximum flow rate? Are there upstream and downstream valves for each FCV? Page 20 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

TEST

Y/N

Punch List Item #

Y/N

Punch List Item #

Y/N

Punch List Item #

With the valves in Manual Mode set it to 25% Open. Are the valve’s local position indicato indicatorr and the MSC indication about 25%? With the valves in Manual Mode set it to 75% Open. Are the valve’s local position indicat indicator or and the MSC indication about 25%? Force the USM to simulate a 50% of Max Flow Rate. With the valve in Automatic Mode set it to 25% Open. Are the valve’s local position indicato indicatorr and the MSC indication at 0%? Force the USM to simulate a 50% of Max Flow Rate. With the valve in Automatic Mode set it to 75% Open. Are the valve’s local position indicato indicatorr and the MSC indication at 100%? Do the valves Fail Open on Air and Electrical Failure? Failure?

2.8

Gas Chromatograph

TEST

Is the sample probe located on top of the pipe? Is the sample probe located in the downstream side of the metering skid?

2.9

Printer

TEST Is the printer an 80 column printer?

Does the Delivery Ticket follow the form indicated in Appendix 1A of 34-SAMSS-846? Does the Comparison Ticket follow the form indicated in Appendix 1c of 34-SAMSS-846?

Page 21 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

3.

Test Discrepancies and Punch List All items marked with N in the previous tables are to become part of the Punch List for further to be takenduring in the the event of to discrepancies shall be defined. Actionsresolution. to be takenActions by the Contractor FAT resolve minor problems shall  be defined.

4.

FAT Suspension / Resumption / Restart In the event a discrepancy is encountered which cannot be resolved during the time allowed for resolution during the FAT, the FAT shall be suspended and the following notices shall be defined to process these discrepancies with a description of the  procedures to be followed for each: 4.1

Notice of FAT suspension [testing is terminated until problem(s) are resolved]

4.2

Notice of FAT restart [begin testing after problem(s) have been resolved and all necessary retesting to be completed]

Page 22 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

 Ap pen di x 2  – Site Acc Acc eptance Test Test Proc edure and Repor Repor ting

1.

Introduction This document is the SAT Procedure to Inspect and verify the functionality of the Large Sales Gas Metering Skid and associated control panel pa nel built under (Indicate BI number) located in (Indicate location). This document contains detailed test procedures with associated lists, tables and a customer comment and sign off area in order to verify and document that each test has been carried out successfully and in accordance with the customer specification (FSD). This procedure has been submitted for for client review and approval. SAT will be  performed against this document in the presence of the client or the client nominated representatives. Any divergence from the agree requirement (FSD) will be formally advised to the client such that revision of the requirement may be agreed and the FSD and this document are altered accordingly. 1.1

Scope All instruments calibrations were verified during FAT and there is no need to repeat verification during SAT unless six or more months have passed since FAT. FAT Test Record Sheets shall be available during SAT. Metering Tests will be conducted with the field I/O connected connect ed to the flow computer and reports will be validated against commercial AGA 8 software. A set of master documentation (Master SAT), drawings and ISS (data sheets) will be made available for the SAT (refer to Section 1.3). Any discrepancies will be recorded on the Punch List and any document/drawing changes will be marked in the “Master SAT” copy  copy to be included in the “As Built” drawings.

1.2

Test Overview The SAT will begin with a full review of o f the system and documentation followed by the inspection of the skid. The goal of the SAT is to check and certify that the system is in compliance with the purchase p urchase order, requisition, specifications and the approved documents. A daily review will be carried out discussing the day’s da y’s test agenda and the  previous day’s test activities and issues. The test will follow a structured plan according to this document. Page 23 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

Any test failures will be fully documented and discussed at the th e daily review. Failures will be evaluated and prioritized according to impact on both further system testing and test schedule time frame. frame. Test schedule shall be modified to to continue testing on the unaffected unaffected part of the system. Low priority failures failures which cannot be rectified immediately and do not prevent further testing will be revisited at the end of the scheduled test period. Every effort will be made to rectify high priority failures and retest as soon as they have hav e been resolved. 1.3

Applicable Documents All documents referenced in the SAT Procedure shall be listed. All documents shall have revision revision numbers and publishing publishing date. Documentation which is part of System and/or is needed during SAT shall be available. Specific items typically include User's Manuals, Maintenance Manuals, configuration drawings, connection drawings, database listings, logic drawings, instrumentation loop drawings (ILD), P&IDs. Document Number

Title

Revision

Date

Master SAT (Full set of documents to be left at facility) Piping and Instrumentation Diagram System Block Diagram Control Panel Termination Details/Loop Diagrams Flow Computer Configuration FAT Records Sheets

1.4

Test Equipment All test equipment needed for all aspects of FAT F AT has been identified. Calibration/Certification reports of test equipment are available. Description

Manufacturer

Model

S/N

Cal date

Digital Multimeter Hart Communicator Communicator Hi pressure tester * Lo pressure tester * Decade Box * Page 24 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

* These instruments are needed if six or more months have passed since FAT. Then, recalibration is required.

1.5

Terms and Abbreviations Definitions of all acronyms, mnemonics, and special terms used in this Procedure shall be provided. D

Pipe Nominal Diameter

DB&B

Double Block and Bleed

FAT

Factory Acceptance test

FSD

Functional Specification Design

GC

Gas Chromatograph

HMI

Human Machine Interface

MOV

Motor Operated Valve

MSC

Metering Supervisory Computer

OSPAS

Oil Supply Planning & Scheduling Department

PIB

Process Interface Building

PLC

Programmable Logic Controller

P&CSD

Process & Control Systems Department

SAEP

Saudi Aramco Engineering Procedure

SAMSS

Saudi Aramco Materials System Specification

SAPMT

Saudi Aramco Project Management Team

SPU

Signal Processing Unit

UPS

Uninterruptible Power Supply

USM

Ultrasonic Meter

Page 25 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

2.

System Checks The tests shall demonstrate and document the satisfaction of all requirements of the System as stated in the Job Specification. The test procedure consists of tables with questions to outline a very detail inspection. 2.1

Skid Mechanical Inspection All equipment/instrumentation should be checked for correct mechanical installation as follows:

TEST

Y/N

Punch List Item #

Is the metering system fabricated in accordance with the approved P&ID? Are instruments tagged in accordance with the latest issue of the P&ID? Does the meter have a minimum of four ultrasonic paths? Is the meter equipped with provisions provisions (such as valves) and all necessary additional devices, mounted on the transducer  ports in order to make make it possible to remove remove transducers fo forr inspection or replacement while the meter is under  pressure? Does the meter body have at least one pressure tap for measuring the static pressure? Is the Static Pressure Transmitter impulse line run as indicated in library drawing DC-950042? Is the nipple coming out the USM for the pressure transmitter welded to the USM and to the root valve? Does thethree UFM havetoaprotect permanently fixed sunshade with a top and sides the transducers, the SPU and the cables? Are the upstream and downstream meter tube sections constructed out of seamless pipe? Note: Seamed pipe may be used for 24 inch meter tubes and larger if the internal longitudinal welds are ground flush and smooth.

Are the upstream and downstream meter tubes internal diameters stamped on stainless steel data plates  permanently attached to the meter meter tubes? Is the flow direction indicated on the meter tube close to each side of the flow meter?

Page 26 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

TEST

Y/N

Punch List Item #

Does the upstream meter tube consist of two sections with a total minimum clear length of 20D? Is there a flow conditioning plate installed in the middle of the upstream meter tube? Is the upstream meter tube flange-ended and equipped with a spacer ring or jack screw so that the tube sections and the flow conditioner can be easily removed for inspection and cleaning? Does the flow conditioning plate have provisions (such as marking or pin) to ensure that it will be installed in the same orientation whenever the conditioning conditioning plate is taken out. Does the downstream meter tube have a minimum clear length of 5D? Is there a thermowell installed at least 5D downstream of the USM at each meter tube? Is there another thermowell installed downstream downstream of the first one and at a distance between 150 and 300 mm? Are the thermowells installed in 1 inch NPT tap fittings?

Page 27 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

TEST

Y/N

Punch List Item #

Is the following information stamped on the stainless steel tag permanently attached to the meter body? Manufacturer Model Number Serial Number Month and Year of Manufacture Total Weight Tag Number  Nominal Size Size Flange Rating Maximum and minimum actual flow rates at operating conditions Maximum and minimum operating pressure and temperature K-Factor Meter body design code and material Meter flange design code and material Internal diameter @ 68°F Acoustic Path 1 length @ 68°F Acoustic Path 2 length @ 68°F Acoustic Path 3 length @ 68°F Acoustic Path 4 length @ 68°F Axial Distance between Transducer pairs @ 68°F Thermal Expansion Coefficient Does each transducer have a permanently permanently marked serial number? Is the flow direction indicated by an arrow on the meter  body and/or by the words UPSTREAM UPSTREAM and DOWNSTREAM on the piping connections? Is there a check meter in “Z” configuration?  configuration?  Are the operational meter(s) and the check meter equally size and calibrated across the entire operational flow range? Does each meter run have an inlet DB&B isolation MOV? Is there a 2” flanged inspection inspection fitting at no less than  than   150 mm downstream of the thermowells mounted 45 o  facing the flow?

Page 28 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

TEST

Y/N

Punch List Item #

Is there a DB&B isolation MOV on the connection pipe to the check meter? Does each meter run have an outlet DB&B isolation MOV? Is the control system mounted in a process interface  building? Are instruments and valves located at convenient working heights and accessible?  Are pipe header stubs provided? Are there two identical Flow Control Valves with upstream and downstream isolation valves installed in  parallel and downstream downstream of the met meter er runs? Is there an Isolation Valve with remote closing capability from OSPAS? Is there a GC and sample probe installed according to SASD-AC-036045? Is there a vent line? Does the vent line extent at least 3 meters above the highest operating platform? Are vents, drains and samplers installed according to AC-036045 and AE-036046? AE-036046? Is there a pressure gauge installed on the skid’s inlet header? Is there a pressure gauge installed on the skid’s outlet header? Are pressure gauges installed as per DC-950040? Are all transmitters grouped in a single point facing the same direction? Is there a fix calibration table adjacent adjacent to the instruments? Is there adequate sunshade to protect the transmitters? Are pressure transmitters’ transmitters’ impulse lines with a slope of not less than 1:12 toward the USMs? Is there a sample probe installed on top of the pipe and on the downstream side of the metering skid?

Page 29 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

2.2

Skid Electrical Inspection

TEST

Y/N

Punch List Item #

Are field junction boxes installed in accessible locations at the edge of the meter skid? Do conduit and cable connections enter junction boxes from the bottom? Is conduit sealed with a weather-tight seal at the entrance of the box? Is the flow computer powered by a UPS system?

2.3

Loop Testing and Functionality Checks Verify that the basic functionality associated with the System I/O works  properly as evidenced on the Flow Computer display. This will include checks that the I/O are wired properly, configured properly, prope rly, displayed properly, and documented properly. 2.3.1

Temperature

TEST

Y/N

Punch List Item #

Are thermowells installed in a 1 inch NPT tap fitting? Are RTD(s) of the 4-wire type? Are RTD(s) of the spring loaded type type?? Is temperature transmitter of the SMART type? Is the temperature transmitter range from 0 –  150°F  150°F (4 (4 –   –  20  20 mA)?

Page 30 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

TEST

Y/N

Punch List Item #

Y/N

Punch List Item #

Using the resistance box, apply resistance values to the transmitter as this: Temperature

Resistance

Span

(F)

(Ohms)

(%)

0

93.03

0

37.5

101.19

25

75

109.30

50

112.5

117.36

75

150

125.37

100

Using a certified thermometer compared the thermometer reading to the transmitter reading (Using a HART communicatorr if transmitter has no display). Is the communicato difference between these readings less than 0.5°F? 0.5 °F? Compare table above to Flow Computer and HMI readings. Are these readings within 0.5°F?

2.3.2

Static Pressure Transmitter

TEST

Is pressure transmitter of the SMART type? Verify calibration of pressure transmitter at 0, 50, 100% increasing and 80, 20, 20, 0% decreasing. decreasing. Using a certified  pressure tester compared compared the tester readin reading g to the transmitter transmitter reading (Using a HART communicator if transmitter has no display). Is the difference between between these reading readingss less than 0.25% of span? Compare transmitter’s pressure reading to Flow Computer and HMI readings. readings. Are these readings readings within 0.25% of span? Is the pressure transmitter fitted with a 3-way manifold valve? Are the impulse lines ½ inch type 316 stainless steel tubing?

Page 31 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

2.3.3

Pressure Gauges

TEST

Y/N

Punch List Item #

Y/N

Punch List Item #

Is the operating pressure within 30% to 70% of the scale range? Are pressure gauges filled with a viscous liquid? Is the diameter of the pressure gauges 4 ½ inches? Is the background of the pressure gauges white with black numbers?

2.4

Flow Computers

TEST

Are there redundant flow computers? Are the flow computers connected in multi-drop network configuration with OSPAS? Are the flow computers tagged according to SA-8020-846ENG? Are the flow computers configured configured to use the USC system of units? Are the reference pressure and temperature configured to be 14.73 psia and 60°F respectively? Are the flow computers configured configured with the correct USM internal diameter (stamped on tag attached to the meter  body)?

Page 32 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

TEST

Y/N

Punch List Item #

Are the flow computers atmospheric atmospheric pressure configured according to following table? Location

Atm. Press. (psia)

Dhahran

14.542

Jubail

14.679

Qasim

13.606

Ras Tanura

14.693

Riyadh

13.667

Shedgum

14.191

Yanbu

14.686

For other areas the following equation shall be utilized: Patm= 14.54*[55096-(elevation[ft]-361)/[55096+(elevation[ft]361)] where “elevation” is obtained from  from SAES-A-112.  Is the low flow cut off set to be 0.020 ft/s? Is the flow computer configured to read a temperature of 0 –  0 –  150°F?  150°F? Is the flow computer configured to read a static pressure according to the transmitter’s calibration?  calibration?  Is the flow computer configured to use fallback values of  pressure and temperature temperature on transmitt transmitter er failure? Open the Temperature Transmitter loop (normally it is easy to open the loop at the fuse). Does the flow computer computer take the temperature fallback value? Open the Static Pressure Transmitter loop (normally it is easy to open the loop loop at the fuse). Does the flow computer computer take the pressure override value? Generate a Delivery Ticket. Does the ticket follow the form indicated in 34-SAMSS 34-SAMSS-846 -846 Appendix 1A? Is the flow computer configured to use the dual pulse signals as primary? Is flow computer configured to compute as per AGA 5, AGA 8, AGA 9 and AGA 10?

Page 33 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

TEST

Y/N

Punch List Item #

Y/N

Punch List Item #

Force transmitters according to following table: Flow Velocity

12 m/s

Temperature

100°F

Static Press.

375 psig

Methane

85%

Ethane

5%

Propane

1%

CO2

2%

 N2

7%

Pipe ID

6 in

Is the compensated flow rate calculated within ± 0.1% of 17.09884 MMSCFD? 

2.5

MSC

TEST

Are the flow computers connected to the MSC via serial communication communicat ion link? Is the MSC located in a console suitable for its location inside the PIB? Is there a laser printer connected to the MSC? Are the following software packages installed in the MSC?   HMI designed for gas metering applications   USM package for configuration and diagnosis   GC package for configuration and diagnosis.   Flow computer package for configuration. Are copies of the above software packages provided in electronic (CD) format with installation instructions? Does the HMI show data in a graphical format similar to the field arrangement? ar rangement? Does the HMI real time data includes, as a minimum, gross flow rate, net flow rate, temperature, pressure, heating value, gas composition and density? 



 

Page 34 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

TEST

Y/N

Punch List Item #

Y/N

Punch List Item #

Is there a table including daily totals for volume and energy? Is there a table including daily averages for flow rate, temperature, pressure, specific gravity and gas composition? Is there a table for real time and historical alarms? Can the HMI capture reports from the primary flow computer (daily tickets, meter comparison report)? Can the HMI archive reports from the primary flow computer (daily tickets, meter comparison report)? Can the HMI print reports from the primary flow computer (daily tickets, meter comparison report)? Does the HMI print the daily tickets automatically at midnight base on the primary computer? Does the HMI print the daily tickets upon manual request  base on the primary computer? Can the HMI trend critical values including the USMs diagnostic parameters? Can the HMI initiate controlled comparison of the operational meter(s) using the check meter? Can the MSC communicate with the GC to display analysis, archive results and verify the configuration? configuration? Does the MSC have a direct serial link to the USM? Do the inlet and outlet isolation MOVs have limit switches for indication of valve position at the MSC?

2.6

PLC

TEST

Is there a PLC connected to the MSC with dual communication links? Does the PLC provide Open/Stop/Close commands for each MOV? Does the PLC provide Remote/Local status for each MOV? Does the PLC provide reverse travel before completion-ofa-command for each MOV? Does the PLC refuse sequential operation if any of the affected valves is in local position?

Page 35 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

TEST

Y/N

Punch List Item #

Y/N

Punch List Item #

Does the PLC follow the next sequence in response to a “Compare Meters” command from the MSC?  MSC?  1. Ensure the inlet MOV of the check meter is closed 2. Open check meter outlet MOV 3. Open MOV on the connection pipe from the meter to be verified 4. Close the meter run outlet MOV Does the PLC follow the next sequence after completion of the ultrasonic meter comparison? 1. Open the meter run outlet MOV 2. Close the MOV on the connection pipe from the meter to be verified to the check meter 3. Close the check meter outlet MOV Does the PLC follow the next sequence after an “Open Meter Run” command from the MSC?  MSC?   1. Ensure the MOV on the connection pipe from meter run to the check meter is closed. 2. Open the inlet MOV for the meter run. 3. Open the outlet MOV for the meter run. Does the PLC follow the next sequence after a “Close Meter Run” command from the MSC?  MSC?   1. Ensure the MOV on the connection pipe from meter run to the check meter is closed. 2. Close the meter run outlet MOV. 3. Close the meter run inlet MOV. MOV.

2.7

FCVs

TEST

Are there 2 FCVs in parallel installed downstream of the meter? According to the ISS, is each FCV rated to handle 100% of the maximum flow rate? Are there upstream and downstream valves for each FCV?

Page 36 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

TEST

Y/N

Punch List Item #

Y/N

Punch List Item #

Y/N

Punch List Item #

With the valves in Manual Mode set it to 25% Open. Are the valve’s local position indicato indicatorr and the MSC indication about 25%? With the valves in Manual Mode set it to 75% Open. Are the valve’s local position indicato indicator  r  and  and the MSC indication about 25%? Force the USM to simulate a 50% of Max Flow Rate. With the valve in Automatic Mode set it to 25% Open. Are the valve’s local position indicato indicatorr and the MSC indication at 0%? Force the USM to simulate a 50% of Max Flow Rate. With the valve in Automatic Mode set it to 75% Open. Are the valve’s local position indicato indicatorr and the MSC indication at 100%? Do the valves Fail Open on Air and Electrical Failure?

2.8

Gas Chromatograph

TEST

Is the sample probe located on top of the pipe? Is the sample probe located in the downstream side of the metering skid? 2.9

Printer

TEST

Is the printer an 80 column printer? Does the Delivery Ticket follow the form indicated in Appendix 1A of 34-SAMSS-846? Does the Comparison Ticket follow the form indicated in Appendix 1c of 34-SAMSS-846?

Page 37 of 38

 

Document Responsibility: Custody Measurement Standards Committee SAEP-58 Issue Date: 29 October 2015 Factory and Site Acceptance Testing  Next Planned Update: 29 October 2018 Requirements for Large Gas Metering Systems

3.

Test Discrepancies and Punch List All items marked with N in the previous tables are to become part of the Punch List for further resolution. Actions to be taken in the event of discrepancies shall be defined. Actions to be taken by the Contractor during the SAT to resolve minor problems shall  be defined.

4.

SAT Suspension / Resumption / Restart In the event a discrepancy is encountered which cannot be resolved during the time allowed for resolution during the SAT, the SAT shall sh all be suspended and the following notices shall be defined to process these discrepancies with a description of the  procedures to be followed for each: 4.1

Notice of SAT suspension [testing is terminated until problem(s) are resolved]

4.2

Notice of SAT restart [begin testing after problem(s) have been resolved and all necessary retesting to be completed].

Page 38 of 38

View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF