CG Lucy Switchgear Ltd is a joint venture company of Crompton Greaves Ltd., India and W.Lucy & Co. Ltd., U.K. Established in 1994, the factory is situated at Nasik, India. With 30000 sq.feet of area, the facility has modern automated equipments with all major testing facilities, to guarantee quality products. CG Lucy is a ISO 9001:2000 Certified company. Division : S2 – MV Switchgear
Category : General
2
New Factory
CG Lucy is the largest manufacturer of SF6 gas insulated Vacuum RMU in India. With near total population in many metro’s, our RMU’s make the metro’s of India to glow with reliable power. Oil RMU’s is another most sought product not only in India, but also in the South Asian countries, especially in Malaysia. This is an economical & highly reliable product which uses HT Fuse links immersed in the Oil chamber. Division : S2 – MV Switchgear
Category : General
3
Ring Network
Division : S2 – MV Switchgear
Category : General
4
Distribution Network MAIN SUBSTATION
RMU
RMU
RMU
COMPACT SUBSTATION FEEDER PILLAR
Division : S2 – MV Switchgear
Category : General
5
‘SABRE’ RING MAIN UNITS (RMU) - SF6 Encapsulated Vacuum RMU
Division : S2 – MV Switchgear
Category : General
6
‘SABRE’ Designation Code
Product Description
VRN VRE VCE
Vacuum Ring Main Unit - Non Extensible Vacuum Ring Main Unit – Extensible Vacuum Circuit Breaker - Extensible
SSE DSE
Single Switch – Extensible Double Switch – Extensible
Multi Circuit Range (MCR) RMU - SF6 Encapsulated Vacuum RMU
Division : S2 – MV Switchgear
Category : General
16
MULTI CIRCUIT RANGE (MCR) MCR is a versatile SF6 insulated Vacuum Ring Main Unit – a combination of vacuum circuit breaker unit and fault-make load break switches (Ring switch / Isolators). With front cable terminations, the system is highly compact and well protected with Padlock, interlock & earthing facilities.
Division : S2 – MV Switchgear
Category : General
17
MCR – 5 Way Under Assembly
Division : S2 – MV Switchgear
Category : General
18
MCR – Range & Extensibility
Division : S2 – MV Switchgear
Category : General
19
Technical Data – SABRE & MCR Variants Rated Voltage kV Rated Current A
Symmetrical Breaking Capacity kA / sec Making Current kAp Impulse Withstand kVp
SABRE - VRE VRE - 6A 12 / 15.5
SABRE 24
MCR 12
630
630 for Ring Switch & 400 for CB
630
21 / 3
16 / 3
21 / 3
52.5
40
52.5
75 / 110 (optional)
125
Min Gas Pressure Bar Filling Pressure Bar Index of protection Cable termination Incoming Tee off Cable Tests Dimensions Width Depth Height Weight kg
0 0.4
0.5
0 0.4 IP 54
Side Bottom Rear Bottom Bottom
Front Bottom Front Bottom Top
935 1078 1470 450
1300 900 1400 540 (3way)
IP 54 Side Bottom Rear Bottom Bottom Bottom 935 1030 1333 410
Division : S2 – MV Switchgear
948 1085 1750 350
75 / 95 (optional)
Category : General
20
Applicable Standards RMU’s has been fully certified in accordance with IEC standards: - IEC 60129 - IEC 60056 - IEC 60265-1 - IEC 60298 - IEC 60694 - IEC 60526 & IEC 60529
Division : S2 – MV Switchgear
Category : General
21
Features
Low gas operating pressure - 0.5 Bar
Pressure indicator and SF6 recharging facility.
Gas pressure relief diaphragm for internal arcing.
Low Temperature rise of Busbars , hence no derating of switches at ambient of 45 to 50 Deg C.
CB Earthing through Vacuum Interrupters hence full rating for earthing circuit.
Operational Safety - We have tested our RMU with ZERO gas pressure for satisfactory electrical performance.
Division : S2 – MV Switchgear
Category : General
22
Features
Stainless Steel Tank: SS is the most preferred material for Gas Insulated System because of its high resistance to corrosive and humid atmosphere.
Extensibility: RMU is extensible on both sides. This feature give greater flexibility to Utility’s planning department to plan future extensions.
Outdoor Application: RMU is suitable for outdoor application. It is IP54 tested. This prevents construction of extra room to house the switchgear.
Gas leakage - For a SF6 Insulated VCB type RMU, the chances of Vacuum bottle leaking and SF6 gas leakage from chamber, simultaneously are very rare. Hence in VCB type RMU provides a double protection scheme.
Division : S2 – MV Switchgear
Category : General
23
Features – Vacuum Dielectric Medium
Ionization of Gas: Since fault is broken in Vacuum Interrupter, the SF6 gas is not polluted.
Constant dielectric: There is no gas decomposition products in vacuum and hermetically sealed vacuum interrupter keep out all environmental effects.
High total current switched: Since the contact piece erosion is small, rated normal current can be interrupted more than 20000 times and rated shortcircuit breaking current on average a hundred times.
Division : S2 – MV Switchgear
Category : General
24
Features - SF6 Leak Prevention Stainless Tank – Robotic Welding Tank Helium Leak Tested SF6 Filling at 0.1 torr Quarantine for 10 days Low SF6 Pressure Pressure Indication Facility for SF6 Recharging on site
Division : S2 – MV Switchgear
Category : General
25
Transformer Protection
Division : S2 – MV Switchgear
Time limit fuses
Electronic Over current and earth fault relays
Auxiliary powered or self powered Relays
Category : General
26
Transformer Protection
Division : S2 – MV Switchgear
Category : General
Current Transformers with Relay for transformer protection
27
Cable Testing Step-1 Step-2
Step-3 Test Bushing
Division : S2 – MV Switchgear
Category : General
28
SABRE Cable Boxes
Bottom or Top Entry Side & Rear Termination for operator Safety Full terminal access Interlocked cable test facility
Division : S2 – MV Switchgear
Category : General
29
Facia Details
Division : S2 – MV Switchgear
All Live parts fully covered All positions visible from front Padlocking in all position – ON / OFF / EARTH
Category : General
30
GA - Overview Bursting Disk Circuit Breaker operating Mechanism
Ring Bushing
Gas Pressure Gauge
Division : S2 – MV Switchgear
Category : General
31
Ring Switch Mechanism
Positively driven Indicators (3 positions)
Indication Operating Lever
Earth/Service operation interlock
Division : S2 – MV Switchgear
Category : General
32
Features: Mechanism
Highly reliable time proven mechanism.
Common frame for both switches ensure accurate center alignment.
Use of stainless steel and brass bushings eliminates effects of corrosion.
5mm thick stainless steel for Service/Earth selectors and interlocks to avoid possible damage due to mis-operations.
Division : S2 – MV Switchgear
Category : General
33
Ring Switch
Interswitch barrier
Insulated Drive Disc Support Disc
Key Advantages:
Reduced number of parts
Self aligning contacts
Compact design
Rear Support Disc allowing automatic self alignment of rear bearing Division : S2 – MV Switchgear
Category : General
34
Ring Switch & Circuit Breaker Module
Fixed contacts for Circuit Breaker selector
Division : S2 – MV Switchgear
CG make Vacuum interrupters
High Fault switching capability
Category : General
35
Contact Arrangements
Hot Brass Stampings
A
B
C
A - Earth Contact B - Switch Blade Pivot C - Line Contact
Benefits over casting:
Better durability Better electrical and mechanical properties
Division : S2 – MV Switchgear
Category : General
36
Optional Accessories
Division : S2 – MV Switchgear
Live line indication
Earth Fault Indicators
Emergency push button
Key interlocks
Motorization
Remote control & monitoring
Category : General
37
SAFETY – Never Compromised
Insulated Drive Plate
FE Stress Analysis We are committed towards providing the best safety features & our products undergo rigorous testing for its reliability. Division : S2 – MV Switchgear
Category : General
38
Robotic Welding
Division : S2 – MV Switchgear
Category : General
39
Module Building
Assembled in Pressurized Clean Room
Controlled entry for personnel and material
Only trained operators are used as per training matrix
Division : S2 – MV Switchgear
Category : General
40
Leak Monitoring
Chamber test Division : S2 – MV Switchgear
Category : General
41
Leak Monitoring – Sniff test
•
Division : S2 – MV Switchgear
Category : General
42
Electrical Testing
High Voltage Test Division : S2 – MV Switchgear
Category : General
43
TRIDENT OIL RING MAIN UNIT
Division : S2 – MV Switchgear
Category : General
44
‘TRIDENT’ Designation Code
Product Description
FRMU
Fused Ring Main Unit - Non Extensible
FRMUE
Fused Ring Main Unit – Extensible
EFS
Extensible Fuse Switch
NEFS
Non Extensible Fuse Switch
EOS
Extensible Oil Switch
Division : S2 – MV Switchgear
Category : General
45
‘TRIDENT’ Range TRIDENT FRMUE/ FRMU:
- 2 Ring Switches + 1 Fuse Switch unit TRIDENT EFS / NEFS - 1 Fuse Switch unit TRIDENT EOS - 1 Switch unit
Division : S2 – MV Switchgear
Category : General
46
FRMU Oil Ring Main Unit Fused tee-off oil switch, with 2 ring oil switches in a separate chamber Transformer mounting or free standing Tripping facility manually, fuse striker pin or remote electrical signal
Division : S2 – MV Switchgear
Category : General
47
Technical Parameters
TRIDENT Variants Rated Voltage kV Rated Current A Breaking Capacity Main / Earth kA Making Capacity Main / Earth kAp Impulse Withstand kVp Index of protection
Division : S2 – MV Switchgear
FRMU / NEFS / EFS / EOS / DEOS Ring Switch Fuse Switch 12 / 15.5 630 400 0.63 20 55 / 55 50 / 7.8 110 110 IP 54