Relay Coordination
February 14, 2017 | Author: chidambaram32 | Category: N/A
Short Description
Download Relay Coordination...
Description
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
RELAY SETTING STUDY
CONTRACT NO.
: ONS-09-0-CO ONS CO-4127
PROJECT
: X GAS FIELD DEVELOPMENT (PHASES X))-132kV 132kV TEMPORARY POWER FROM MPC
COMPANY
:X
SITE
: X GAS FIELD
0
23/05/08
Issued for Approval
Hir.
S.M.K.
S.M.K.
Rev.
Date
Description
ORIGI
PRPD
CHKD
A.F. APP’ D
CONT. ONT. APPRD. PPRD.
X GAS FIELD DEVELOPMENT – PHASES X,, ONSHORE FACILITIES Project No. : ONS-09-00-CO-4127
Doc. Class :
Scale : NTS
132kV 32kV TEMPORARY POWER FROM MPC RELAY SETTING STUDY(CT2000:5) DOCUMENT No.
X Gas Field Development (Phases X)
NC--6340S-550-1600 1600-0004
Sh. No. :
1 of 158
Rev. 0
Page 1 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
TABULATION OF REVISED PAGES PAGE
REV
PAGE
X Gas Field Development (Phases X)
REV
PAGE
REV
PAGE
REV
PAGE
REV
PAGE
REV
Page 2 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
TABLE OF CONTENTS
1. INTRODUCTION
2. SCOPE
3. SYSTEM DESCRIPTION DESCRIPTION AND INPUT DATA 3.1.Reference Documents 3.2.System System Analysis Software 3.3. Electrical System Representation 3.3.1.Network Topology 3.3.2. Network Parameters and Data 4. CALCULATION CRITERIA 5. LOAD FLOW AND FAULT RESULTS 6. RELAY TYPE AND LOCATIONS LOCAT 7. RELAY SETTINGS 8. RESULTS 9. TRANSIENT ACTIONS 9.1 TRANSIENT ACTION OF THE RELAYS WITH TRANSIENT STABILITY 9.1.1 33KV UNDER VOLTAGE RELAY ACTION IN TRANSIENT STABILITY SIMULATION 9.1.2 Under voltage, Bus Transfer 9.2 TRANSIENTS CHECKS 10.0 OTHER PARAMETERS TO BE SET 10.1 TRANSFORMER AUTOMATIC VOLTAGE REGULATOR 10.2 INRUSH CURRENT SETTINGS 11.. CONCLUSIONS
X Gas Field Development (Phases X)
Page 3 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
APPENDIX I STATIC AND DYNAMIC EQUIVALENT OF GAS PLANT A.I.1 GAS PLANT ELECTRICAL NETWORK REPRESENTATION A.I.2 INPUT DATA A.I.3LOAD FLOW A.I.4SHORT CIRCUIT ANALYSIS A.I.5 DYNAMIC STUDIES A.I.6 STATIC AND DYNAMIC EQUIVALENT OF GAS PLANT ELECTRICAL NETWORK A.I.7 INTENDED STUDY SYSTEM
X Gas Field Development (Phases X)
Page 4 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
-Attachments Attachments NC-6340S 6340S-550-1600-0004 0004-RELAY RELAY SETTING STUDY-AT01(CT2000:5) STUDY (CT2000:5) NC-6340S 6340S-550-1600-0004 0004-RELAY RELAY SETTING STUDY-AT02(CT2000:5) STUDY (CT2000:5)
X Gas Field Development (Phases X)
Page 5 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
1. INTRODUCTION The phases phase X within the X Gas Field Development project are designed to process the incoming hydrocarbon fluid by the sub-marine sub marine pipelines. The refinery is located at X Village, about 270 km South East of X city. The Temporary Electrical Power required for phases X Gas Plant shall be supplied from Power Plan Plant of Mobin Mobin Petrochemical Complex through 132kv 132 v underground cable line and a 132kV/33 132kV/33kV,, 100MVA power transformer. Six generators that are connected to the X National grid are assumed to supply electric power through circuit that contains 132kV cable and 13 132/33kV 2/33kV transformer. The temporary supply relay setting and coordination studies are described in this document.
2. SCOPE The objective of this document is to do relay settings and coordination analysis for temporary supply up to the 33KV outgoing to the Gas plant relays that are coordinated by another vendor and made available to us in document VP 6340S 1600 LG 0001 077. 077 The results of this study provide the exact settings of the concerned relays of the temporary supply which must be tuned before commissioning of the plant.
3. SYSTEM DESCRIPTION AND INPUT DATA 3.1. Reference Documents DW 6340S 120 1633 0001 NC 6340S 120 1634 0001 NC 6340S 999 1630 0020 NC 6340S 999 1630 0021 VP 6340S 1600 LG 0001 077 NC 6340S 550 1600 001 NC 6340S 550 1600 002 NC 6340S 550 1600 003 NC 6340S 550 1600 005 SLD 6340S 550 1600 0002
X Gas Field Development (Phases X)
General Single Line Diagram Electrical Load Summary Short Circuit and Load Flow Study Dynamic Stability Study (Issued with no name) Switching Overvoltage Study made by TOM Load Flow Study made by TOM Short Circuit Study made by T TOM OM Motor Starting Study made by TOM Single Line Diagram
Page 6 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
3.2. System Analysis Software PASHA (Power Apparatus and System Homological Analysis), Version 2008,, was used for performing the studies. The software is product of TOM and serving the electrical utilities and the industries for twenty three years worldwide.
3.3. Electrical System Representation 3.3.1. Network Topology Single line diagram of the involving plants are used to produce the study power system. Figure 1 shows hows a view of the overall electrical network represented in the present studies. Gas plant is analyzed and equalized in Appendix I. For the purpose of the equalization, the Gas Plant, single line diagram as represented in drawing DW 6340S 120 1633 0001 is represented in PASHA software. Documents NC 6340S 999 1630 0020, 0020, NC 6340S 999 1630 002 0021 are used to provide the required data. Here, 11 KV motor loads are represented separately based on their dynamic models. Some of 6 KV motor loads are also represented separately based on their dynamic models models. Other 6KV motors and 400 V induction motor loads are summed and represented as equivalent m motor otor loads on their corresponding bus bars. Static loads are lumped represented on their appropriate locations. Please refer to appendix I for detailed representation of GAS PLANT electrical systems. Figure 2 shows the electrical network representation whe where re the static and dynamic equivalent of the GAS PLANT is represented inside the network, please see also drawing DW 6340S 550 1600 0002, and DW 6340S 550 1600 0001 000 at the end of this report inside appendix I. The dynamic loads of this plant are represented as equivalent induction motor motors and loads loads.. The parameters of the equivalent induction motors are selected such that the static power requirment and the dynamic behaviour of the load matches those comes from the overall loads and induction motors existing iin n the Gas Plant. Equalization, makes documentation and reportings easiear. The Gas plant equivalent valent is shown in GASEQUAL area in Figure 2. In n fault and relay coordination studies we need to consider the maximum planed and in operation fault level levels and their their contributions in device setting studies. The neighboring factories play important rule in this regard. Therefore, they are included in the representation of the electrical networks as it is shown in Figure 2. In this report the neighboring factories are called External xternal plants plants.. The external plants are represented by their lumped loads equivalence. For these lumped loads 80% motor loads is considered. One incoming transformer of these plants is also considered in the studies. This is because the bus bars o on 20KV or 33KV side of the external plants cannot be closed together. Maximum aximum fault current contribution contributionss of these plants are imposed in their respective board when a bus coupler is closed while one incomer is opened. Therefore all the motor fault contributions contributions to short circuit are congregated in the coupled bus. The external plants are shown in EXTERNAL area in Figure 2.
X Gas Field Development (Phases X)
Page 7 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
The existence of the connection of MOBIN MOB power generation plant to X National GRID is also considered. This is shown in Figure 2 in GRID area.. The detailed representation of the X national power grid is already represented in PASHA software elsewhere. The 1990 deck of the 400KV, 230KV, and 132KV of the X network which includes the 63KV of the Esfahan is used to provide the equivalent of th the e power grid as represented in this report. The box RELAY is introduced inside the Gas plant equivalent to consider for the outgoing 33KV relays that feeds the various substations inside the Gas plant. The bahaviour of 33KV relays protecting the 11KV motors motors of the Gas plant is also considered. The selected equivalent motors are intdicated in Figure 2 in 11KV area. As mentioned the equalization is just made to simplify the reporting, the actual 33KV relays behavior is also considered inside the Gas plant but it does not included in the reports.
X Gas Field Development (Phases X)
Page 8 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Figure 1: The overall view of the study system
X Gas Field Development (Phases X)
Page 9 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Figure 2: The study system of this report report;; Gas plant equivalent (Appedix I) is introduced
X Gas Field Development (Phases X)
Page 10 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
3.3.2. Network Parameters and Data The data are provided in two groups. One is from PASHA data bases which contains the fundamental data of equipment, usually based on the equipment ratings. The second one is according to PASHA edit pages which includes the drawn equipment data on system base.This is selected to be 10MVA. Table 1 contains contain the base DATA for equipment parameters of the equivalent study system system.. The equivalent dynamic loads are represented with type types 9000 to 9030 and those lumped loads are represented with type types 8000000 to 8999999. 89 For the detailed data base of the Gas plant equipment please refer to Table I.1 of appenix I. Table 2 shows the system parameters after base conversion. The length of 132KV temporary cable is considered equal to 14.3 km per phase. For GAS PLANT deta detailed iled input data please refer to Table I.2 of Appendix I.
X Gas Field Development (Phases X)
Page 11 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Table 1 Data base for system equipment ZERO SEQUENCE REACTANCEPU/KM
ZERO SEQUENCE RESISTANCEPU/KM
33 6 15
SUSEPTANCE PU/KM
100 5 160
REACTANCE PU/KM
33 6 15
RESISTANCE PU/KM
RATING KV
Type MANUFACT.
RATING MVA
SIZE
PASHA LIB.
CABLES AND LINES DATA BASE CABLE
1(500) 1(400) 1(800)
Used for Tie connections and those not known
FICT FICT FICT
0.0001 0.0001 0.0001
0.0003 0.0003 0.0003
Note : RATING MVA IS OBTAINED FROM CABLE CURRENT CAPACITY, RATINGS ARE THE PU BASES
X Gas Field Development (Phases X)
Page 12 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
(
%& '" /
)
%& '"
/
/ /
*+ "
,-% "'
%& '" % / / / / / /
(
.+
-
%& '" / /
! "" #
%$%& '" /
*400A A grounding resistor considered, **X means Yn and from simulation point of view DY11 is equal to DY5, and DY1 is equal to DY7,
X Gas Field Development (Phases X)
Page 13 of 158
Type or MANUFACT.
RATIO DV
MAX. TAP
MIN. TAP
REACTANCE PU
TAP STEP
ZERO SEQUENCE RESISTANCE PU*
REACTANCE PU
RESISTANCE PU
PASHA LIB.
CONNECTION TYPE **
U1/U2 KV/KV
RATING (BASE) MVA
TRANSFORMERS DATA BASE
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
*0. 1 *0. 1 *0. .1 *0. 1 *0. .1 *0. 1 *0. .1 *0. 1 *0. 1 *0. 1 *0. 1 *0. 1 *0. 1 *0. 1 *0. .1 *0. 1
" " " " " " " " " " " " " " " "
Type or Man ufac turer
*23 *23 *23 *23 *23 *23 *23 *23 *23 *23 *23 *23 *23 *2 *2 *2
H (Sec.) (total) (driven)
REACT.-PU
REAC T.-PU T.
ROTOR RESIST.-PU
MVA
MAGNETIZING
BASE
VOLTAGE KV
STATOR REACT-PU
LIB.
OTHERS
RESIST.-PU
KW
PASHA
RATED
MOTORS DATA BASE
Driven TYPE*
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
*Driven Type: Typ Mechanical Torque Formula=(A+B(1 Formula=(A+B(1-s)+C(1-s)2)Tmo where A+B+C=1, B and C is written and s is slip.
X Gas Field Development (Phases X)
Page 14 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
% STATIC Load
H (Sec.) (total) (driven)
REACT.-PU
REAC T.--PU
ROTOR RESIST.-PU
MVA
MAGNETIZING
BASE
VOLTAGE KV
STATOR REACT-PU
LIB.
OTHERS
RESIST.-PU
MVA
PASHA
RATED
LUMPED LOAD LOADS DATA BASE
Driven TYPE*
4 4 4 4 4 4 4 4 4
*Driven Type: Typ Mechanical nical Torque Formula=(A+B(1 Formula=(A+B(1-s)+C(1-s)2)Tmo where A+B+C=1, B and C is written and s is slip.
X Gas Field Development (Phases X)
Page 15 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
GENERATOR DATA BASE
RATED POWER
TYPE
MVA
RATED VOLTAGE KV
PASHA
RESISTANCE
REACTANCE
LIB.
PU
PU
ZERO SEQUENCE RESISTANCE RESISTANCE- REACTANCEREACTANCE PU PU
% . " . % . "
H (SEC)
5 5 &
PASHA LIB.
X'd
DIRECT AXIS 'd X"d
"d
Xq
X'q
QUADRATURE AXES 'q X"q
"q
*10A A grounding resistor considered
X Gas Field Development (Phases X)
Page 16 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Table 2: List of DATA which ar aree represented in PASHA software
INPUT DATA =========================== SYSTEM TITLE: TEMPORARY SUPPLY TO PHASES 9-10 9 STUDY TITLE: SYSTEM MVA BASE = 10.000
PASHA ACTUAL DYNAMIC FAULT IS ACTIVE
B U S B A R
D A T A
I N P U T
-----------------------------------------------------------------------S Y N C H R O N O U S GENERATION
G E N E R A T O R S GENERATOR IMPEDANCES PU
BUSBAR
P
Q
RES
NAME
(MW)
(MVAR)
R
0 0-C C TIME CONST
SYN-X SYN DA-TR-X X DA-ST-X DA X TDO' XD
XD'
XD"
TDO"
AREA
(MSEC) (MSEC)
GT1
107.04
78.05 0.0001 0.1303 0.0158 0.0102 7550.00
GT2
100.00
74.45 0.0001 0.1303 0.0158 0.0102 7550.00
30.00 MOBIN 30.00 MOBIN
GT3
100.00
7 77.64 7.64 0.0001 0.1303 0.0158 0.0102 7550.00
30.00 MOBIN
GT4
100.00
74.45 0.0001 0.1303 0.0158 0.0102 7550.00
30.00 MOBIN
GT5
100.00
74.45 0.0001 0.1303 0.0158 0.0102 7550.00
30.00 MOBIN
GT6
100.00
77.64 0.0001 0.1303 0.1303 0.0158 0.0102 7550.00
30.00 MOBIN
WARNING - TDO' OF FOLLOWING MACHINE MISSING GRIDG
60.00
40.00 0.0006 0.000 0.0025 0.0025 0.0000
0.00
0.00 GRID
END OF SYNCHRONOUS MACHINE DATA
S T A T I C BUSBAR NAME
L O A D S LOAD
INITIAL VOLTAGES
P(MW) Q(MVAR)
AREA
MAG(PU) ANG(DEG) VNOM.(KV)
MBIN132
0.00
0.00
1.0000
0.000
132.000 MOBIN
GT6
0.00
0.00
1.0000
0.000
15.000 MOBIN
GT5
0.00
0.00
1.0000
0.000
15.000 MOBIN
GT4
0.00
0.00
1.0000
0.000
15.000 MOBIN
GT3
0.00
0.00
1.0000
0.000
15.000 MOBIN
GT2
0.00
0.00
1.0000
0.000
15.000 MOBIN
GT1
0.00
0.00
1.0000
0.000
15.000 MOBIN
GC1
0.00
0.00
1.0000
0.000
15.000 MOBIN
GC2
0.00
0.00
1.0000
0.000
15.000 MOBIN
GC3
0.00
0.00
1.0000
0.000
15.000 MOBIN
GC4
0.00
0.00
1.0000
0.000
15.000 MOBIN
X Gas Field Development (Phases X)
Page 17 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004 GC5
0.00
0.00
1.0000
0.000
GC6
0.00
0.00
1.0000
0.000
INT1
0.00
0.00
1.0000
0.000
132.000 ALL 33.000 ALL
15.000 MOBIN 15.000 MOBIN
1S11A
0.00
0.00
1.0000
0.000
1S11B
0.00
0.00
1.0000
0.000
33.000 ALL
MBF1321
0.00
0.00
1.0000
0.000
132.000 ALL
GRID
0.00
0.00
1.0000
0.000
132.000 ALL2
J1
0.00
0.00
1.0000
0.000
132.000 EXTERNAL
J2
0.00
0.00
1.0000
0.000
132.000 EXTERNAL
J3
0.00
0.00
1.0000
0.000
132.000 EXTERNAL
J4
0.00
0.00
1.0000
0.000
132.000 EXTERNAL
J5
0.00
0.00
1.0000
0.000
132.000 EXTERNAL
J6
0.00
0.00
1.0000
0.000
132.000 EXTERNAL
J7
0.00
0.00
1.0000
0.000
132.000 EXTERNAL
J8
0.00
0.00
1.0000
0.000
132.000 EXTERNAL
J9
0.00
0.00
1.0000
0.000
132.000 EXTERNAL
ACIDA
17.00
10.54
1.0000
0.000
20.000 EXTERNAL
COMMU
10.71
6.64
1.0000
0.000
20.000 EXTERNAL
C2REC
3.40
2.11
1.0000
0.000
20.000 EXTERNAL
UREAA
6.12
3.79
1.0000
0.000
20.000 EXTERNAL
SEAWA
10.71
6.64
1.0000
0.000
20.000 EXTERNAL
4THAR
13.60
8.43
1.0000
0.000
20.000 EXTERNAL
ASU
17.00
10.54
1.0000
0.000
20.000 EXTERNAL
10THO
17.00
10.54
1.0000
0.000
20.000 EXTERNAL
9THOL
20.40
12.64
1.0000
0.000
20.000 EXTERNAL
AU1400
0.09
0.05
1.0000
0.000
0.400 AU1
AU16KV
0.85
0.53
1.0000
0.000
6.000 AU1
AU2400
0.09
0.05
1.0000
0.000
0.400 AU2
AU36KV
0.85
0.53
1.0000
0.000
6.000 AU3
AU3400
0.09
0.05
1.0000
0.000
0.400 AU3
AU4400
0.09
0.05
1.0000
0.000
0.400 AU4
AU5400
0.09 0.09
0.05
1.0000
0.000
0.400 AU5
AU66KV
0.85
0.53
1.0000
0.000
6.000 AU6
AU6400
0.09
0.05
1.0000
0.000
0.400 AU6
GRID132
0.00
0.00
1.0000
0.000
132.000 GRID
GRID230
0.00
0.00
1.0000 1.0000
0.000
230.000 GRID
JGRID
0.00
0.00
1.0000
0.000
20.000 GRID
GRID20
0.00
0.00
1.0000
0.000
20.000 GRID
GRIDG
0.00
0.00
1.0000
0.000
230.000 GRID
OUT1
0.00
0.00
1.0000
0.000 0.000
J0
0.00
0.00
1.0000
0.000
PH678
17.00
10.54
1.0000
0.000
33.000 EXTERNAL
STEQU1
2.75
3.06
1.0000
0.000
33.000 GASEQUAL
DYEQU1
0.00
0.00
1.0000
0.000
33.000 GASEQUAL
STEQU2
2.75
3.06
1.0000
0.000
33.000 GASEQUAL
DYEQU2
0.00
0.00
1.0000
0.000
33.000 GASEQUAL
DEQSM1
0.00
0.00
1.0000
0.000
33.000 GASEQUAL
DEQSM2
0.00
0.00
1.0000
0.000 0.000
33.000 GASEQUAL
09
0.00
0.00
1.0000
0.000
33.000 RELAY
REL1
0.00
0.00
1.0000
0.000
33.000 RELAY
08
0.00
0.00
1.0000
0.000
33.000 RELAY
X Gas Field Development (Phases X)
Rev. No. : 0
33.000 ALL 132.000 EXTERNAL
Page 18 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004 07
0.00
0.00
1.0000
0.000
33.000 RELAY
06
0.00
0.00
1.0000
0.000
33.000 RELAY
05
0.00
0.00
1.0000
0.000
33.000 RELAY
04
0.00
0.00
1.0000
0.000
33.000 RELAY
03
0.00
0.00
1.0000
0.000
33.000 RELAY
02
0.00
0.00
1.0000
0.000
33.000 RELAY
01
0.00
0.00
1.0000
0.000
33.000 RELAY
147
0.00
0.00
1.0000
0.000
33.000 11KV
111
0.00
0.00
1.0000
0.000
33.000 11KV
103
0.00
0.00
1.0000
0.000
33.000 11KV
Rev. No. : 0
END OF STATIC LOAD DATA
I N D U C T I O N
M O T O R S
LOAD BUSBAR NAME
TYPE PASHA
MOTOR IMPEDANCES PU P
Q
(MW)
(MVAR)
STATOR RES
REACT
ROTOR 1 RES
REACT
ROTOR 2 RES
MAGNETISING AREA
REACT
REACT
ACIDA
8010000.
60.50
36.98 0.0000 0.0091 0.0012 0.0091 0.0000 0.0000
COMMU
8006300.
40.35
23.84 0.0000 0.0145 0.0020 0.0145 0.0000 0.0000
0.325 EXTERNAL 0.516 EXTERNAL
C2REC
8002000.
14.14
7.92 0.0001 0.0456 0.0062 0.0456 0.0000 0.0000
1.625 EXTERNAL
UREAA
8003600.
20 20.15 .15
12.94 0.0001 0.0253 0.0035 0.0253 0.0000 0.0000
0.903 EXTERNAL
SEAWA
8006300.
40.35
23.84 0.0000 0.0145 0.0020 0.0145 0.0000 0.0000
0.516 EXTERNAL
4THAR
8008000.
50.44
30.07 0.0000 0.0114 0.0016 0.0114 0.000 0.0000 0 0.0000
0.406 EXTERNAL
ASU
8010000.
60.50
36.98 0.0000 0.0091 0.0012 0.0091 0.0000 0.0000
0.325 EXTERNAL
10THO
8010000.
60.50
36.98 0.0000 0.0091 0.0012 0.0091 0.0000 0.0000
0.325 EXTERNAL
9THOL
8012000.
80.75
46.41 0.0000 0.0076 0.0010 0.0076 0.0000 0.0000
0.271 EXTERNAL
AU16KV
8000500.
4.30
2.58 0.0885 0.2820 0.0362 0.1880 0.0000 0.0000
5.412 AU1
AU1400
8012500.
0.43
0.25 1.0612 2.0529 0.2383 1.3686 0.0000 0.0000
48.825 AU1
AU2400
8012500.
0.43
0.25 1.0612 2.0529 0.2383 1.3686 0.0000 0.0000
48.825 AU2
AU36KV
8000500.
4.30
2.58 0.0885 0.2820 0.0362 0.1880 0.0000 0.0000
5.412 AU3
AU3400
8012500.
0.43
0.25 1.0612 2.0529 0.2383 1.3686 0.0000 0.0000
48.825 AU3
AU4400
8012500.
0.43
0.25 1.0612 2.0529 0.2383 1.3686 0.0000 0.0000
48.825 AU4
AU5400
8012500.
0.43
0.25 1.0612 2.0529 0.2383 1.3686 0.0000 0.0000
48.825 AU5
AU66KV
8000500.
4.30
2.58 0.0885 0.2820 0.0362 0.1880 0.0000 0.0000
5.412 AU6
AU6400
8012500.
0.43
0.25 1.0612 2.0529 0.2383 1.3686 0.0000 0.0000
48.825 AU6
PH678
8010003.
0.00
29.93 0.0000 0.0091 0.0012 0.0091 0.0000 0.0000
0.325 EXTERNAL
DYEQU1
9011.
20.84
10.51 0.0300 0.0405 0.0044 0.0405 0.0000 0.0000
1.250 GASEQUAL
DYEQU2
9013.
18.47
9.80 0.0300 0.0405 0.0044 0.0405 0.00 0.0000 00 0.0000
1.250 GASEQUAL
DEQSM1
9012.
20.30
10.56 0.0001 0.0480 0.0044 0.0480 0.0000 0.0000
1.556 GASEQUAL
DEQSM2
9014.
18.26
9.71 0.0001 0.0480 0.0044 0.0480 0.0000 0.0000
1.556 GASEQUAL
END OF INDUCTION MACHINE DATA END OF BUSBAR DATA
X Gas Field Development (Phases X)
Page 19 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004 B R A N C H
D A T A
Rev. No. : 0
I N P U T
------------------------------------BUSBAR FROM
TO
BRANCH IMPEDANCES (PU) PPS AND NPS R
X
ZPS R
TRANSFORMER AREA AREA-TO-AREA AREA PASHA TYPE SUSC
X
B
TAP WINDING (%)
CODE
GT1
GC1
0.0000 0.0000 0.0000 0.0001 0.0000
MOBIN
MOBIN
15.
GT2
GC2
0.0000 0.0000 0.0000 0.0001 0.0000
MOBIN
MOBIN
15.
GT3
GC3
0.0000 0.0000 0.0000 0.0001 0.0000
MOBIN
MOBIN
15.
GT4
GC4
0.0000 0.0000 0.0000 0.000 0.0001 1 0.0000
MOBIN
MOBIN
15.
GT5
GC5
0.0000 0.0000 0.0000 0.0001 0.0000
MOBIN
MOBIN
15.
GT6
GC6
0.0000 0.0000 0.0000 0.0001 0.0000
MOBIN
MOBIN
1 15.
MBIN132 GC1
0.0002 0.0089 0.0002 0.0072 0.0000 -2.5 2.5
XD11
MOBIN
MOBIN
1.
MBIN132 GC2
0.0002 0.0089 0.0002 0.0072 0.0000 -2.5 2.5
XD11
MOBIN
MOBIN
1.
MBIN132 GC3
0.0002 0.0089 0.0002 0.0072 0.0072 0.0000 -2.5 2.5
XD11
MOBIN
MOBIN
1.
MBIN132 GC4
0.0002 0.0089 0.0002 0.0072 0.0000 -2.5 2.5
XD11
MOBIN
MOBIN
1.
MBIN132 GC5
0.0002 0.0089 0.0002 0.0072 0.0000 -2.5 2.5
XD11
MOBIN
MOBIN
1.
MBIN132 GC6
0.0002 0.0089 0.0002 0.0072 0.0000 -2.5 2.5
XD11
MOBIN
MOBIN
1.
MBIN132 MBF1321
0.0000 0.0000 0.0000 0.0001 0.0197
MOBIN
ALL
32150000.
MBF1321 INT1
0.0004 0.0012 0.0012 0.0037 1.3860
ALL
ALL
32150000.
1S11A
1S11B
0.0000 0.0000 0.0000 0.0000 0.0000
ALL
ALL
GRID
MBIN132
0.0000 0.0000 0.0000 0.0001 0.6842
ALL2
MOBIN
MBIN132 J1
0.0000 0.0000 0.0000 0.0001 0.5701
MOBIN
EXTERNAL 32150000.
MBIN132 J2
0.0000 0.0001 0.0001 0.0002 0.2423
MOBIN
EXTERNAL 32140000.
MBIN132 J3
0.0000 0.0001 0.0001 0.0001 0.0002 0.2423
MOBIN
EXTERNAL 32140000.
MBIN132 J4
0.0000 0.0001 0.0001 0.0002 0.2423
MOBIN
EXTERNAL 32140000.
MBIN132 J5
0.0000 0.0000 0.0000 0.0001 0.4846
MOBIN
EXTERNA EXTERNAL 32140000.
MBIN132 J6
0.0000 0.0001 0.0001 0.0002 0.2423
MOBIN
EXTERNAL 32140000.
MBIN132 J7
0.0000 0.0001 0.0001 0.0002 0.2423
MOBIN
EXTERNAL 32140000.
MBIN132 J8
0.0000 0.0000 0.0000 0.0000 0.0001 0.5701
MOBIN
EXTERNAL 32150000.
MOBIN
EXTERNAL 32180000.
33. 3 32180000.
MBIN132 J9
0.0000 0.0000 0.0000 0.0001 0.6842
J1
ACIDA
0.0002 0.0100 0.6563 0.0100 0.0000
0.0
DX1
EXTERNAL EXTE EXTERNAL RNAL
22.
J2
COMMU
0.0003 0.0159 1.0417 0.0159 0.0000
0.0
DX1
EXTERNAL EXTERNAL
24.
J3
C2REC
0.0009 0.0500 3.2814 0.0500 0.0000
0.0
DX1
EXTERNAL EXTERNAL
26.
J4
UREAA
0.0005 0.0278 1.8230 0.0278 0.0000
0.0
DX1
EXTERNAL EXTERNAL
25.
J5
SEAWA
0.0003 0.0159 1.0417 0.0159 0.0000
0.0
DX1
EXTERNAL EXTERNAL
24.
J6
4THAR
0.0002 0.0125 0.8204 0.012 0.0125 5 0.0000
0.0
DX1
EXTERNAL EXTERNAL
23.
J7
ASU
0.0002 0.0100 0.6563 0.0100 0.0000
0.0
DX1
EXTERNAL EXTERNAL
22.
J8
10THO
0.0002 0.0100 0.6563 0.0100 0.0000
0.0
DX1
EXTERNAL EXTERNAL
2 22.
J9
9THOL
0.0002 0.0083 0.5469 0.0083 0.0000
0.0
DX1
EXTERNAL EXTERNAL
21.
GT1
AU1400
0.0752 0.4741 0.0752 0.4741 0.0000
0.0
DX11
MOBIN
AU1
31.
GC1
AU16KV
0.0143 0.0898 0.0143 0. 0.0898 0898 0.0000
0.0
DX11
MOBIN
AU1
32.
GT2
AU2400
0.0752 0.4741 0.0752 0.4741 0.0000
0.0
DX11
MOBIN
AU2
31.
GT3
AU3400
0.0752 0.4741 0.0752 0.4741 0.0000
0.0
DX11
MOBIN
AU3
31.
GC3
AU36KV
0.0143 0.0898 0.0143 0.0898 0.0000
0.0
DX11
MOBIN
AU3
32.
GT4
AU4400
0.0752 0.4741 0.0752 0.4741 0.0000
0.0
DX11
MOBIN
AU4
31.
GT5
AU5400
0.0752 0.4741 0.0752 0.4741 0.0000
0.0
DX11
MOBIN
AU5
31.
GT6
AU6400
0.0752 0.4741 0.0752 0.4741 0.0000
0.0
DX11
MOBIN
AU6
31.
GC6
AU66KV
0.0143 0.0898 0.0143 0.0898 0.0000
0.0
DX11
MOBIN
AU6
GRID
ALL2
GRID132 GRID
0.0001 0.0002 0.0002 0.0005 1.1796
X Gas Field Development (Phases X)
32. 32180000.
Page 20 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
GRID230 JGRID
0.0008 0.0152 0.0007 0.0133 0.0000
0.0
XX0
GRID
GRID
JGRID
GRID132
0.0000 0.0008 0.0000 0.0000 0.0008 0.0000
0.0
XX0
GRID
GRID
2131252.
JGRID
GRID20
0.0000 0.0240 0.0000 0.0240 0.0000
0.0
XD11
GRID
GRID
2131253.
GRID
GRID
ALL
ALL
3.
ALL
ALL
33.
GRIDG
GRID230
0.0000 0.0001 0.0000 0.0000 0.0000
INT1
OUT1
0.0002 0.0096 1.3124 0.0098 0.0000 -5.0 5.0
OUT1
1S11A
0.0000 0.0000 0.0000 0.0000 0.0000
J0
PH678
0.0002 0.0096 1.3124 1.3124 0.0098 0.0000 -3.3 3.3
DX1 DX1
EXTERNAL EXTERNAL
2131251.
0.
3.
MBIN132 J0
0.0002 0.0005 0.0005 0.0016 0.5996
MOBIN
EXTERNAL 32150000.
1S11A
STEQU1
0.0000 0.0000 0.0000 0.0000 0.0000
ALL
GASEQUAL GASEQUAL
33.
1S11A
DYEQU1
0.0000 0.0000 0.0000 0.0000 0.0000
ALL
GASEQUAL
33.
1S11B
STEQU2
0.0000 0.0000 0.0000 0.0000 0.0000
ALL
GASEQUAL
33.
1S11B
DYEQU2
0.0000 0.0000 0.0000 0.0000 0.0000
ALL
GASEQUAL
33.
1S11A
DEQSM1
0.0000 0.0000 0.0000 0.0000 0.0000
ALL
GASEQUAL
33.
1S11B
DEQSM2
0.0000 0.0000 0.0000 0.0000 0.0000
ALL
GASEQUAL
33.
1S11B
REL1
0.0000 0.0000 0.0000 0.0000 0.0000
ALL
RELAY
33.
REL1
09
0.0000 0.0000 0.0000 0.000 0.0000 0 0.0000
RELAY
RELAY
33.
REL1
08
0.0000 0.0000 0.0000 0.0000 0.0000
RELAY
RELAY
33.
REL1
07
0.0000 0.0000 0.0000 0.0000 0.0000
RELAY
RELAY
3 33.
REL1
06
0.0000 0.0000 0.0000 0.0000 0.0000
RELAY
RELAY
33.
REL1
05
0.0000 0.0000 0.0000 0.0000 0.0000
RELAY
RELAY
33.
REL1
04
0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
RELAY
RELAY
33.
REL1
03
0.0000 0.0000 0.0000 0.0000 0.0000
RELAY
RELAY
33.
REL1
02
0.0000 0.0000 0.0000 0.0000 0.0000
RELAY
RELAY
33.
REL1
01
0.0000 0.0000 0.0000 0.0000 0.0000
RELAY
RELAY
33.
REL1
147
0.0000 0.0000 0.0000 0.0000 0.0000
RELAY
11KV
33.
REL1
111
0.0000 0.0000 0.0000 0.0000 0.0000
RELAY
11KV
33.
REL1
103
0.0000 0.0000 0.0000 0.0000 0.0000
RELAY
11KV
33.
END OF BRANCH DATA
X Gas Field Development (Phases X)
Page 21 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
4. CALCULATION CRITERIA a) PASHA dynamic fault studies and transient stability calculations b) Software PASHA version 2008 c) Calculation procedure for short circuit analysis (i)
Maximum considerable short circuit current is depicted in the analysis
(ii)
Generators saturated reactances are considered in the analysis as the clien clientt request However in dynamic fault studies the actual reactances considering the saturation will be used by PASHA
(iii)
Pre-fault fault voltages are shown in input data table tables and their values depend to load flow results
(iv)
Maximum fault current is attained when six generators connected to the GRID GRID, are supplying the power required for G Gas plant and 33KV Bus Bus-coupler coupler is closed and dual feeding by incomer transformers are not considered (i.e. one incoming circuit is considered) considered).. Since other connected external plants loads and the future reinforcement of the MOBIN generation station are considered, the maximum fault current is obtained when all the external plants are in action.
(v)
Minimum fault current is attained when two generato generators rs are supplying the Gas plant through one temporary circuit that feeds the Gas plant. In this situation a two phase fault in the outgoing 132KV cable can not be cleared by the present relay settings before the trip of MOBIN two generators. The problem can be solved with extra signaling if required required.
(vi)
Therefore, In the above special occasions of L L-L L faults, Minimum is considered with three generators or two generators generators and the GRID in action in the present report.
(vii)
For high set relays and the transformer inrush current consideration the fault is calculated instantaneously. For other relays settings the actual current up to the time of operation of the relays will be considered by software.
X Gas Field Development (Phases X)
Page 22 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
5. LOAD FLOW AND FAULT RESULTS Load flow of the network considered is already reported in document NC 6340S 550 1600 0002. 0002 Short circuit analysis of the plant is reported in document NC 6340S 550 1600 000 0003.. For the sake of simplicity of the reviewing of the results, maximum load flows o off the plant and the maximum fault contribution of the plants are shown in the following figures (Figures (Figure 3,, 4 and 5 show the load flow results and Figure 6 and 7 show the fault results results).. Here since PASHA dynamic short circuit study is used for the relay settings, se the short circuit results shown in Figure Figures 6 and 7 outcome the result of using such a method. In document NC 6340S 550 1600 000 0003 3, IEC909 method has been used. There is however a small difference in the result results, s, but the dynamic fault is more reliable reliable for the purpose of relay coordination coordination. Please lease refer to the pa paper pers published in IEEE Transactions on Industrial ndustrial Application pplication: 1-- “A Comparison of Static and Dynamic Short Circuit Analysis Procedures”,1990 pp463 2--“Simulation “Simulation of Protective Relay Performance Under Short Circuit and Transient Swing Conditions” ,1990, pp1108 Also please note that document NC 6340S 999 1630 0020 short circuit study is based on 1314MVA maximum Short Circuit Capacity (SCC) of the incoming supply. This would not be the ccase ase for 100MVA, 10% transformer used in the temporary incoming supply.
X Gas Field Development (Phases X)
Page 23 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Figure 3: Load flow result shows MW MVAR flows
X Gas Field Development (Phases X)
Page 24 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Figure 4: Load flow result shows current flows
X Gas Field Development (Phases X)
Page 25 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Figure 5: Load flow result shows MVA flows
X Gas Field Development (Phases X)
Page 26 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Figure 6: Maximum Fault Level of each each busbar, and lines contributions
X Gas Field Development (Phases X)
Page 27 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Figure 7: Minimum Fault Level of each busbar, and lines contributions
X Gas Field Development (Phases X)
Page 28 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
6. RELAY TYPE AND LOCATIONS Figure 8, shows a simplified view of the relays types type and locations. locations. For the functions that they are considered to perform please refer to Tables Table 3 and 4 at the result section of the present report report. The relays shown on black lack boxes are those must be set in this report (they are shown in Tables 3 and 4 with blue background).. The color relays of the figure 8 are already sset et by other vendors. For more accurate drawings drawings please refer to (132KV 132KV TEMPORARY POWER FROM MPC METERING AND PROTECTION SINGLE LINE DIAGRAM DIAGRAM) SLD 6340S 550 1600 0002 0002, for those commition commitioning by Hirbodan Hirbodan, document VP 6340S 1600 LG 0001 077 and VP 6340S 1600 LG 0001 003 for Gas plant relays, and drawing MP MBU OOEE 02 EGO 001 001from from MOBIN power plant for MOBIN relays. Note that the core balance CT’s for 11KV motors feeders (111KM101 and 103KM 101) have different ratio specification in document VP 6340S 1600 LG 0001 0001 077 and document VP 6340S 1600 LG 0001 003 003. Those specified in document VP 6340S 1600 LG 0001 003 is selected in the present report.
X Gas Field Development (Phases X)
Page 29 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Figure 8: The relays type types and locations location
147KM10A
111KM101 111KM 01 103KM101
S31A ……………………………………………………………………….
147KM10B
111KM201 01 103KM201
S31B ……………………………………………………………………….
111KM301 01 111KM401 01 111KM501 01 111KM601
X Gas Field Development (Phases X)
Page 30 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
7. RELAY SETTINGS The current practice of relay coordination and settings which are reported in IEC standard standards and other practical text books are adopted in this report to obtain the best possible function of the relays during the operation. Both short circuit studies and transient stability studies have been performed and the relays actions were observed to act iin n desired performance. The manual of the manufacturer are reviewed in order to consider the special function and treatment of the relays. The 33KV outgoing relays including the 33KV bus tie relay coordinated in document VP 6340S 1600 LG 0001 077 are the basis basis of the incoming relay relays settings that are reported in the present document. Note that; that the earth faults fault 51 1G and 50G of the bus tie have some settings setting in the mentioned document, but its core balance CT is not specified. Therefore, with reference to document DWG VP 6340S 1600 LG 0001 077 sheet 12 from 35 35, it is recognized that the earth current obtaines from residual phase currents. currents Therefore, the CT ratio is 2500:1. The setting values (IDMT-SI SI 0.1In , TMS=1 for 51G)) and (I>>1In I>>1In , tI>>0.05 tI for 50G) 50G reported in document VP 6340S 1600 LG 0001 077 for this bus tie can not protect the system againt LG fault; since for LG short circuit current (i.e. 400A 3I0) its operation time is aboutt 14sec which is too high. But this setting settings have not been changed in tthe e present report,, because it is out of the scope of the report. report Note also that;; the phase fault 51 and 50 relays of the bus tie do not have appropriate settings in document VP 6340S 1600 LG 0001 077. 077 The setting values ((IDMT ( IDMT-SI 0.8In In , TMS=1 for 51 51)
and (I>> I>>8In , tI>>0.6 0.6 for
50) 50 can not protect the system even againt three phase fault. Its operatiom time for a three phase fault in even in 33KV busbars is abot 3200msec. which is too high. But this settings settings have not been changed in the th present report, report because use it is out of the scope of the report report. Note also those comments written in section 9 of this report about undervoltage relay settings of document VP 6340S 1600 LG 0001 077. 077 Note also on the comments comment written in section 4, 4, i.e. Minimum fault current in the present document is attained when two generators are supplying the Gas plant through one temporary circuit that feeds the Gas plant. In this situation a two phase fault in the outgoing 132KV cable can not be cleared by the present relay settings before before the trip of MOBIN two generators. The problem can be solved with extra signaling if required.Therefore, required.Therefore, In the above special occasions of L-L L L faults, Minimum is considered with three generators or two generators generators and the GRID in action.
X Gas Field Development (Phases X)
Page 31 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
8. RESULTS Refer to the next pages the calculation results are reported in Four categories. The first one comprises the relay setting results, the second one shows the graph curves of the relays on Log Log-Log Log diagram and the third one indicates the trend of the fault current that the relays senses and the operation of the relays in case of various kind of fault (LG-LL(LG -LLG-LLL) LLL) occurred in different locations of the network. Catogory No.4 are those extracted from the results and just reported to simplify the site setting of the purposed relays.
The following drawings and lists are reported: (1) Relay settings reports (Table 3 and Table 4 4). (2) Graph curves (Table 5). (3) Relay actions in short circuit studies (Table 6,, reported as an attachment). (4) Actual relay settings (Table 7, 7, reported as an attachment). attachment
X Gas Field Development (Phases X)
Page 32 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
9. TRANSIENT ACTIONS The relays set in section 8 and the relays set by other vendors are all put under investigation, in this section section. 10.1 TRANSIENT ACTION OF THE RELAYS WITH TRANSIENT STABILITY In order to accept the relay action during the fault, the entire network is subjected to the following Transient ransient Stability tability TS (or frequency dynamic FD) scenarios: scenarios
(1) Three phase fault are applied in the 33KV busbars and outgoing lines, lines, and cleared by primary prima protection which are already tuned in document VP 6340S 1600 LG 0001 077, 077, in order to investigate the plant recovery. PASHA considers the relay action automatically in its transient stability and frequency dynamic simulation. Some of the results are sho shown wn in the following sections. sections (2) Three phase fault are applied in the 33KV busbars and outgoing lines, and cleared by back up protection, in order to investigate the plant recovery.
and the switching actions are reported in the followings.
9.1.1
33KV UNDER VOLTAGE RELAY ACTION IN TRANSIENT STABILITY SIMULATION
A fault lasting for 300 msec. long (Starts from 100msec) applied in the external factories in its 20KV substation side. side The TS output results shown in Figure 9 and its table, table, indicate that Under voltage voltage relay (P922) set in document VP 6340S 1600 LG 0001 077 ; (The e setting is 0.8P.U. P.U. and 0.2 sec sec) will operate and disconnects all the outgoing lines and black outs the entire Gas as plant. It is obvious that this relay has not been set properly, since the 300msec long duration fault in the neighboring factory is a usual interruption time considering the relay and circuit breaker actions in these factories. In order to investigate other transient transient runs runs,, the setting settings of under voltage relay set in the mentioned document are inhibited. In fact they are set at 0.7 P.U., 1100 msec. sec. which is our suggestions. However, the responsibility of the action of this relay is out of the scope of the present do document cument.
X Gas Field Development (Phases X)
Page 33 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Figure 9: Transient Stability Result Output for a fault in neighbouing factory
Table of figure 9: The switching actions reported in PASHA SHUNT OF IMPEDANCE 0.00000 +J 0.00000 P.U. APPLIED TO BUS PH678
AT TIME 0.1000 SECONDS
----------------------------------------------------------------------------------------------------------------------SHUNT OF IMPEDANCE 0.00000 +J 0.00000 P.U. REMOVED FROM BUS PH678
AT TIME 0.4000 SECONDS
----------------------------------------------------------------------------------------------------------------------LINE OF IMPEDANCE 0.00000 +J 0.00001 P.U. SWITCHED OUT BETWEEN BUSES OUT1 DUE TO UNDE. VOL VOLTAGE TAGE
RELAY OPERATION, STAGE
AND 1S11A
AT TIME 0.4700 SECONDS
1, SCH.NO. 1 (TRIPPING TIME = 0.3700 SEC)
-----------------------------------------------------------------------------------------------------------
X Gas Field Development (Phases X)
Page 34 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004 9.1.2
Rev. No. : 0
Under nder voltage, Bus Transfer
Document VP 6340S 1600 LG 0001 077 has tuned undervoltage/overvoltage undervoltage/overvoltage relay for 6KV busbars at 0.8P.U. 0.2sec. and undervoltage for 400V busbars at 0.8P.U. 0.2 sec. These have the same problem as already mentioned in section 7.2. No bus transfer schemes has been recognized and no automatic rest restart has been defined for system loads. Therefore, in the present document we have assumed that all undervoltage relays are inhibited.
9.2 TRANSIENTS CHECKS
The following figures (Figures 10,11,12,13 10,11,12,13 and 14) 14 show the relays action and time of opening of the circuit (Including Cicuit Breaker Intrruption Intr uption time), for a specified three phase fault. Please note that, these are different from those shown in relays action lists reported in section 8 of the present document. Those lists are using short circuit analysis and these are due to transient stability analysis. The latter is more reliable, since all the transient actions of the induction motors, angle diviation of the supply, AVR and Governor actions and many other factors that do not usually consider in short circuit studies will be considered in transient stability runs. For example if you do apply a three phase fault in 20KV of neighboring factory in short circuit analysis, the voltage in 1S11A would be more than 0.9 P.U. (and it does not show the problem already mentioned in section 9.1) 9.1),, while the reality is that; that the voltage in 1S11A will pass below 0.7 P.U. during the induction motors recovery from fault. In all the following figures, we have assumed that some 400V sma smallll induction motors will be disconnected from the system due to their AC contactor action actions.. As indicated before, the undervoltage relays actions in 6KV and 400V of Gas plant have been ignored, ignored, due to their incorrect settings settings. The induction motors switching actions are shown with L/OUT (Lock out) times in these these figures. Also note that the INTERLOCK between upstream and downstream circuit breakers of the temporary supply has not introduced in simulations. In figure 14, although the fault will be cleared in 23 230msec., 0msec., MOBIN generator relays disconnect the supplying generator in 2.106 106sec. sec. This is because we have not considered the Under Voltage and AC contactors of the external plants that the MOBIN generator plant is supplying them. This might not be happened in the real situation. However the consideration of this phenomena is out of the scope of this report. As far as this report is concern, the three phase fault in the 132KV cable is cleared as fast as possible, i.e. 230 msec.
X Gas Field Development (Phases X)
Page 35 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Figure 10: 10 Transient response of the relays (operating times including CB times are shown in diagram)
X Gas Field Development (Phases X)
Page 36 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Figure 11: Transient response of the relays (operating times including CB times are shown in diagram)
X Gas Field Development (Phases X)
Page 37 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Figure 12: Transient response of the relays (operating times including CB times are shown in diagram)
X Gas Field Development (Phases X)
Page 38 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Figure 13: Transient response of the relays (operating times including CB times are shown in diagram)
X Gas Field Development (Phases X)
Page 39 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Figure 14: Transient response of the relays (operating times including CB times are shown in diagra diagram)
X Gas Field Development (Phases X)
Page 40 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
10. OTHER PARAMETERS TO BE SET This section addresses other controllers and adjustments that must be set before commissioning of the plant. 10.1 TRANSFORMER AUTOMATIC VOLTAGE REGULATOR The followings must be set according to load flow studies reported in document NC 6340S 550 1600 0002: 0002
Note: Do not set on factory settings listed below
MUST BE SET TO: DESIRED V= V=1 100V
(Voltage Transformer secondary rated voltage compensated with voltage transformer ratio introduced)
Band With=1.67% With=1.67% Delay time 1 = 22s (Sets according ccording to maximum start time of the motors reported in NC 6340S 550 1600 0005 0005) Compensation = OFF UNDER VOLTAGE BLOCKING = 70% OVER VOLTAGE BLOCKING = 115% VOLTAGE TRANSFORMER RATIO = =33KV 33KV / 100 1 Current transformer ratio = 2000 / 1
X Gas Field Development (Phases X)
Page 41 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
10.2 INRUSH CURRENT SETTINGS The relays acting on 132KV side must have inrush current blocking enabled enabled,, by the following values. values
7SJ61 Lower function limit=1.25A Upper function limit=8A I2f/I=15% 7UT61 Lower function limit=1.25A Upper function limit=8A I2f/I=15%
X Gas Field Development (Phases X)
Page 42 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
11. CONCLUSIONS All the devices within the scope of this report (blue coloured items in the relay setting tables) are working within their duties, and are coordinated with downstream and upstream relays according to the usual relay coordination practice. practice. In addition to the graph presented, all the points inside the network are subjected to various kinds of faults (LLL-LLG-LL-LG) (LLL LG) in various sections of this report report,, and it is shown that they are working as it is expected.
X Gas Field Development (Phases X)
Page 43 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Table 3: RELAY SETTINGS REPORT
PASHA LINE No. BUSBAR SENDING
The line number in PASHA software program The sending busbar the line is originated in PASHA program
BUSBAR RECEIVING
The receiving busbar the line is ended in PASHA program
COMPONENT (Comp)
The component inside the line (Transformer, Cable…)
RATTING KVA (Comp)
The ratting of the component (comes from DATABASE)
RATTING KVA LOAD FLOW (All loads included) FAULT THROUGH (A) VOLTAGE KV LOCATION SEND SEND-RECEIVE RECEIVE DEVICE FUNCTION PASHA TYPE MANUFACTURER & TYPE RATTINGS CT,VT,FUSE,MCCB PRIMARY SETTINGS (A)
The maximum ratting of the circuit if the peak load is feeding comes from load flow calculation (depended to the case). For over current device this is the maximum fault current. For overload device this shows the maximum through load current. For ground relays it is the maximum 3I0. For Locked rotor it is the starting current. For unbalance device it is the maximum I2 in The voltage base Location of the device in the line S for sending and R for receiving The protective function symbols (51,51N,67,51G,50,…) The protective function A number represents the device type in PASHA data base Manufacturer also shows the curve type. S.I stands for Standard Inverse and so For CT it shows the CT ratio. For fuses it shows the Fuse ratting. For MCCB it is MCCB ratting. If there is VT associated with device, it is the VT ratio. As the name applies it is the primary settings in A. For fuses it is the ratting of fuse
SECONDARY PLUG SETTING
As the name applies
TIME SETTING
As the name applies Recommended Settings of this document Must be set on site, just suggestions Relays set by other vendors vendors; meet the requirement. requirement. This does not mean we have approved the settings. Provided for backup; M Might be disabled SET BY OTHER VENDORS BUTDO BUT NOT MEET THE REQUIRMENT REQUIRMENTS; Has been changed in simulation SET BY OTHER VENDORS BUTDO NOT MEET THE REQUIRMENTS REQUIRMENTS; Has not been changed in simulation GROUP B needed
X Gas Field Development (Phases X)
Page 44 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550 550-1600-0004 0004
MANUFACTUR ER & TYPE
RATTINGS CT,VT,FUSE,M CCB
PRIMARY Settings (A)
SECONDARY Plug Setting
TIME Setting
Over Current
75351
SEPAM 343 V.D S.I
8000.1
7992.2
100
1
1
GT1
GC1
CABLE
160000
124319
42698.7
15
S
51V
Voltage Restra.
75351
SEPAM 343 V.D S.I
15000.1
Kfac=.250
Vs1 =0.8 Vs2=0.6 Tdelay= 1.0
7
MBIN132
GC1
TRANS
160000
96933
26639.2
132
S
51
Over Current
12300
1600.1
768.2
48
0.075
7
MBIN132
GC1
TRANS
160000
96933
26639.2
132
S
50
High Set
12300
1600.1
2800.7
175
0.149
7
MBIN132
GC1
26050.6
132
S
50G
Ground FAULT
123005
1600.1
2800.7
175
0.4
13
MBIN132
MBF1321
CABLE
100000
93870
29533.7
132
S
51
Over Current
12302
1600.1
480.1
30
0.8
13
MBIN132
MBF1321
CABLE
100000
93870
29533.7
132
S
50
High Set
12302
1600.1
4321.1
270
0.1 0.15
13
MBIN132
MBF1321
32884.6
132
S
50G 50
Ground FAULT
123005
1600.1
768.2
48
0.2
13
MBIN132
MBF1321
CABLE
100000
93870
29198.4
132
R
49
OVER LOAD
12304
1600.1
416.1
26
10
14
MBF1321
INT1
CABLE
100000
97272
28964.5
132
S
51
Over Current
54102
1600.1
480.1
30
0.8
14
MBF1321
INT1
CABLE
100000
97272
28964.5
132
S
50
High Set
54102
1600.1
4321.1
270
0.1 0.15
14
MBF1321
INT1
0
0
31730.7
132
S
50G 50
Ground FAULT
541005
1600.1
768.2
48
0.2
14
MBF1321
INT1
CABLE
100000
97272
16015.6
132
R
51
Over Current
54102
1600.1
512.1
32
0.7
14
MBF1321
INT1
CABLE
100000
97272
16015.6
132
R
50
High Set
54102
1600.1
8002
500
0
14
MBF1321
INT1
12975.3
132
R
50G 50
Ground FAULT
541005
1600.1
720.2
45
0.2
320
IS1=20% IS2=2A K1=30% K2=150%
0
1600.1
320
IS1=20% IS2=2A K1=30% K2=150%
0
2500.1
1998
80
1
2500.1
19980.5
800
0.599
2500.1
249.8
10
1
2500.1
2497.6
100
0.05
FUNCTION
51V
DEVICE
S
LOCATION Send-Receive
15
VOLTAGE KV
42698.7
FAULT CURRENT THROUGH (A)
124319
RATTING KVA Load flow (All loads included)
160000
RATTING KVA (Comp)
CABLE
COMPONENT (Comp)
GC1
BUSBAR Receiving
GT1
BUSBAR Sending
1
PASHA LINE No.
PASHA TYPE
Rev. No. : 0
RELAY SETTINGS
14
MBF1321
INT1
CABLE
100000
98326
20192
132
S
87L
DIFFRENTIAL
CABLE
100000
98326
20192
132
S
87L
DIFFRENTIAL
541
15
1S11A
1S11B
CABLE
100000
45627
18084
33
S
51
Over Current
14300
15
1S11A
1S11B
CABLE
100000
45627
18084
33
S
50
High Set
14300
15
1S11A
1S11B
398.3
33
S
51G 1G
Ground FAULT
14300
15
1S11A
1S11B
398.3
33
S
50G 50
High Set
14300
X Gas Field Development (Phases X)
E.INVER MICOM P541 E.INVER MICOM P541 I0 D.T. MICOM P541
MICOM P541
INT1
45627
E.INVER MICOM P541 E.INVER MICOM P541 I0 D.T. MICOM P541
541
MBF1321
100000
E.INVER MICOM P123 E.INVER MICOM P123 I0 D.T. MICOM P123 OV.LOAD MICOM P123
MICOM P541
14
CABLE
INVERSE MICOM P123 INVERSE MICOM P123 I0 D.T. MICOM P123
INVERSE MICOM P143 INVERSE MICOM P143 INVERSE MICOM P143 INVERSE MICOM P143
Page 45 of 158
1600.1
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550 550-1600-0004 0004
Rev. No. : 0
49
INT1
OUT1
TRANS
100000
100921
15481
132
S
51
Over Current
76112
E.INVER 7SJ611
500.1
500
100
0.7
49
INT1
OUT1
TRANS
100000
100921
15481
132
S
50
High Set
76112
E.INVER 7SJ611
500.1
7000
1400
0
49
INT1
OUT1
7106.5
132
S
50N
Ground FAULT
761105
I0 D.T. 7SJ611
500.1
700
140
0.2
49
INT1
OUT1
398.4
33
S
50Ns
Ground FAULT
761105
I0 D.T. 7SJ611
250.1
47.5
19 9
0.7
OUT1
Asym. 6765A A 27KA Sym. 3908A A 15.5KA KA
132 / 33
S R
87T
DIFFRENTIAL
612
53
INT1
TRANS
100000
98326
SIEMENS 7UT612
IDIFF> 30% IDIFF>> 1350% 50%
500.1 2000.1
0
Other settings of diffrential protection: Inrush Blocking 2nd=15% 3Cycle , Crossblock=ON,nthH=30% Cycle Limit=1.5,Slope1=0.25 Limit=1.5,Slope1=0.25 base=0.0 Slope2=0.4 base=1.25, I--RESTRAINT=0. RESTRAINT=0.1 1 Fac. For increase=1.0 Maximum permissible starting time=5.0s, Pick up for add on stablization=4.0 Duration of Add-on Add on stabilization=15Cycle Time for cross cross-block block Add-on Add on Stabiliz.=15Cycle PLEASE TAKE CARE IN APPLYING CORRECT S1 AND S2 AND PHASE SHIFT SHIFT FOR DIFFRENTIAL PROTECTION
132 / 33
S R
87N (64 64)
Restricted Earth Faul
612
SIEMENS 7UT612
98326
132 / 33
S
59
OVER FLUXING
612
SIEMENS 7UT612
100000
98326
132 / 33
S R
49
OVER LOAD
612
SIEMENS 7UT612
CABLE
100000
95875
14738.4
33
S
51
Over Current
12702
CABLE
100000
95875
14738.4
33
S
50
High Set
12702
398.5
33
S
51G 51
Ground FAULT
12702
100000
21443.1
33
S
51
Over Current
12300
100000
100000
21443.1
33
S
50
High Set
12300
0
0
398.5
33
S
50Ns
Ground FAULT
12300
CABLE
100000
100000
398.5
33
S
50
High Set
12300
8
CABLE
100000
100000
21443.1
33
S
51
Over Current
12300
1S11B
8
CABLE
100000
100000
21443.1
33
S
50
High Set
12300
61
1S11B
8
0
0
398.5
33
S
51G 1G
Ground FAULT
12300
61
1S11B
8
CABLE
100000
100000
398.5
33
S
50G 50
High Set
12300
62
1S11B
7
CABLE
100000
100000
21443.1
33
S
51
Over Current
12300
62
1S11B
7
CABLE
100000
100000
21443.1
33
S
50
High Set
12300
62
1S11B B
7
0
0
398.5
33
S
51G 1G
Ground FAULT
12300
62
1S11B
7
CABLE
100000
100000
398.5
33
S
50G 50
High Set
12300
63
1S11B
6
CABLE
100000
100000
21443.1
33
S
51
Over Current
12300
53
INT1
OUT1
TRANS
53
INT1
OUT1
TRANS
100000
53
INT1
OUT1
TRANS
50
OUT1
1S11A
50
OUT1
1S11A
50
OUT1
1S11A
60
1S11B
9
CABLE
100000
60
1S11B
9
CABLE
60
1S11B
9
60
1S11B
9
61
1S11B
61
X Gas Field Development (Phases X)
408A
E.INVER MICOM P127 E.INVER MICOM P127 E.INVER MICOM P127 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123
Page 46 of 158
2000.1 2000.1
132000 / 110
2.32 V/HZ
500.1 2000.1
5%
0
110%
2S
Man.
20 2000.5
2060
103 3
0.65
20 2000.5
5620
281 81
0.75
20 2000.5
200
10
0.0 0.05
500.1
350
70
3.5
500.1
4999.7
1000
0.2
150.1
45
30
0.1
150.1
150
100
0.05
150.1
90
60
0.9
150.1
450
300
0.5
150.1
45
30
0.5
150.1
150
100
0.05
150.1
75
50
0.3
150.1
600
400
0.5
150.1
15
10
0.3
150.1
150
100
0.05
200.1
150
75
0.5
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550 550-1600-0004 0004
63
1S11B S11B
6
63
1S11B
6
63
1S11B
6
64
1S11B
64
CABLE
Rev. No. : 0
100000
100000
21443.1
33
S
50
High Set
12300
0
0
398.5
33
S
51G 1G
Ground FAULT
12300
CABLE
100000
100000
398.5
33
S
50G 50
High Set
12300
5
CABLE
100000
100000
21443.1
33
S
51
Over Current
12300
1S11B
5
CABLE
100000
100000
21443.1
33
S
50
High Set
12300
64
1S11B
5
0
0
398.5
33
S
51G 1G
Ground FAULT
12300
64
1S11B
5
CABLE
100000
100000
398.5
33
S
50G 50
High Set
12300
65
1S11B
4
CABLE
100000
100000
21443.1
33
S
51
Over Current
12300
65
1S11B S11B
4
CABLE
100000
100000
21443.1
33
S
50
High Set
12300
65
1S11B
4
0
0
398.5
33
S
51G 1G
Ground FAULT
12300
65
1S11B
4
CABLE
100000
100000
398.5
33
S
50G 50
High Set
12300
66
1S11B
3
CABLE
100000
100000
21443.1
33
S
51
Over Current
12300
66
1S11B
3
CABLE
100000
100000
21443.1
33
S
50
High Set
12300
66
1S11B
3
0
0
398.5
33
S
51G 1G
Ground FAULT
12300
66
1S11B
3
CABLE
100000
100000
398.5
33
S
50G 50
High Set
12300
67
1S11B
2
CABLE
100000
100000
21443.1
33
S
51
Over Current
12300
67
1S11B 11B
2
CABLE
100000
100000
21443.1
33
S
50
High Set
12300
67
1S11B
2
0
0
398.5
33
S
51G 1G
Ground FAULT
12300
67
1S11B
2
CABLE
100000
100000
398.5
33
S
50G 50
High Set
12300
68
1S11B
1
CABLE
100000
100000
21443.1
33
S
51
Over Current
12300
68
1S11B
1
CABLE
100000
100000
21443.1
33
S
50
High Set
12300
68
1S11B
1
0
0
398.5
33
S
51G 1G
Ground FAULT
12300
68
1S11B
1
CABLE
100000
100000
398.5
33
S
50G 50
High Set
12300
69
1S11B
147
CABLE
100000
100000
21443.1
33
S
49
OVER LOAD
225000
69
1S11B
147
CABLE
100000
100000
21443.1
33
S
50
High Set
225000
69
1S11B
147
0
0
398.5
33
S
50G 50
Ground FAULT
225005
70
1S11B
111
100000
100000
21443.1
33
S
51
Over Current
225000
CABLE
X Gas Field Development (Phases X)
INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 INVERSE MICOM P123 DT TIME MICOM P225 DT TIME MICOM P225 I0 D.T. MICOM P225
DT TIME MICOM P225
Page 47 of 158
200.1
1199.9
600
0.5
150.1
30
20
0.5
150.1
150
100
0.05
150.1
112.5
75
0.6
150.1
899.9
600
0.5
150.1
15
10
0.6
150.1
150
100
0.05
250.1
180
72
0.6
250.1
1999.9
800
0.5
150.1
30
20
0.6
150.1
150
100
0.05
250.1
180
72
0.6
250.1
1999.9
800
0.5
150.1
30
20
0.6
150.1
150
100
0.05
150.1
75
50
0.4
150.1
750
500
0.5
150.1
15
10
0.4
150.1
150
100
0.05
250.1
180
72
0.4
250.1
1499.9
600
0.5
150.1
30
20
0.4
150.1
150
100
0.05
350.1
262.5
75
12
350.1
2099.9
600
0.049
150.1
45
30
0.1
250.1
125
50
8
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550 550-1600-0004 0004
70
1S11B
111
70
1S11B
111
71
1S11B
103
71
1S11B
103
71
1S11B
103
CABLE
Rev. No. : 0
100000
100000
21443.1
33
S
50
High Set
225000
0
0
398.5
33
S
50G 50
Ground FAULT
225005
CABLE
100000
100000
21443.1
33
S
51
Over Current
225000
CABLE
100000
100000
21443.1
33
S
50
High Set
225000
0
0
398.5
33
S
50G 50
Ground FAULT
225005
X Gas Field Development (Phases X)
DT TIME MICOM P225 I0 D.T. MICOM P225 DT TIME MICOM P225 DT TIME MICOM P225 I0 D.T. MICOM P225
Page 48 of 158
250.1
1249.9
500
0.049
150.1
75
50
0.1
150.1
150
100
8
150.1
974.9
650
0.049
150.1
45
30
0.1
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Table 4: Voltage and Frequency relays setting tables
INDEX
PASHA LINE No. BUSBAR SENDING BUSBAR RECEIVING BUSBAR Actuated
The line number in PASHA software program. The sending busbar the line is originated in PASHA program. The receiving busbar the line is ended in PASHA program. The busbar the relay is located hier in PASHA program.
STEP Number
Load sheding step number.
RELAY TYPE
The type of relay
VOLTAGE (P.U.) FREQUENCY (Hz)
The voltage the relay is set. The frequency the relay is set.
df/dt (Hz/Sec)
The frequency rate the relay is set.
DELAY TIME (mSec)
The delay time the relay is set.
EXPECTED P (MW) EXPECTED Q (MVAR)
The expected maximum MW load that shed. N/A The expected maximum MVAR load that shed. N/A
TOTAL P
The expected maximum total MW load that shed. N/A
TOTAL Q
The expected maximum total MVAR load that shed. N/A
X Gas Field Development (Phases X)
Page 49 of 158
RELAY SETTING STUDY (CT2000:5)
RELAY TYPE
Busbar Voltage Rat.
LOGIC DIAGRAM REFERENC E or According
DELAY TIME (mSec)
Rev. No. : 0 df/dt (Hz/Sec)
1 1
FREQUENCY (Hz) or VOLTAGE P.U.
PASHA STEP Number
OUT1 OUT1
RELAY TYPE
BUSBAR Actuated
54 54
CODE
PASHA BUSBAR No.
Doc. No. : NC--6340S-550-1600 1600-0004
Micom P127 Micom P127
33KV/100V 33KV/10 KV/100V
Voltage and Frequency relays 27 UNDER VOLTAGE 0.7 0 12500 59 OVER VOLTAGE 1.1 0 200 Note that : All other voltage relays, used for closing permission must set at 0.9
33KV under voltage set in document VP 6340S 1600 LG 0001 077 must be changed by IOEC approval. Please inform us when you have this approval. Blue values are used for plant simulation in this report report. IOEC Micom 922 33KV/10 33KV/100 11 1S11A 1 27 UNDER VOLTAGE 0.8 0 200 TOM Micom 922 33KV/10 33KV/100 11 1S11A 1 27 UNDER VOLTAGE 0.7 0 1100 00 IOEC Micom 922 33KV/10 33KV/100 12 1S11B 1 27 UNDER VOLTAGE 0.8 0 200 TOM Micom 922 33KV/10 33KV/100 12 1S11B 1 27 UNDER VOLTAGE 0.7 0 1100 00 6KV under voltage set in document VP 6340S 1600 LG 0001 077 seems not correct. However, not refered in the present report. 400V under voltage set in document VP 6340S 1600 LG 0001 077 seems not correct. However, not refered in the present report.
X Gas Field Development (Phases X)
Page 50 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Table 5: Graph curves Figures
X Gas Field Development (Phases X)
Page 51 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
1 –OVER ER LOAD MICOM P123,CT/RATIO=1600.1,P/S =%26.0,T/S= =%26.0,T/S=10.00 10.00 2 -E.INVER E.INVER MICOM P123,CT/RATIO=1600.1,P/S=%30.0,T/S=0.80,HIGHSET =270,TIMESET =0.15 3 -INVERSE INVERSE MICOM P123,CT/RATIO=1600.1,P/S=%48.0,T/S=0.08,HIGHSET =175,TIMESET =0.15 4 -SEPAM SEPAM 343 V.D S.I,CT/RATIO=8000.1,P/S =%100.0,T/S=1.00
X Gas Field Development (Phases X)
Page 52 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
1 -E.INVER E.INVER MICOM P127,CT/RATIO=2000.5,P/S=% P127,CT/RATIO=20 ,P/S=%103.0,T/S=0.65,HIGHSET= .0,T/S=0.65,HIGHSET= 81,TIMESET=0.75 .0,T/S=0.65,HIGHSET=%281 0.75 2 -E.INVER E.INVER 7SJ611,CT/RATIO=500.1,P/S=%100.0,T/S=0.70,HIGHSET=%1400,TIMESET=0 3 -E.INVER E.INVER MICOM P541,CT/RATIO=1600.1,P/S=%32.0,T/S=0.70,HIGHSET=%500,TIMESET=0 4 -E.INVER E.INVER MICOM P541,CT/RATIO=1600.1,P/S=30.0,T/S=0.80,HI P541,CT/RATIO=1600.1,P/S=30.0,T/S=0.80,HIGHSET=%270,TIMESET= GHSET=%270,TIMESET=0.15 GHSET=%270,TIMESET=0.15 *TRANSFORMER TRANSFORMER CAPABILITY CURVE: RAT RAT-MVA MVA =100 =100,Through hrough Fault,Frequent,Inrush=9 Fault,Frequent,Inrush=9,Curve ,Curve TCC/0.1sec *CABLE CABLE CAPABILITY CURVE: RAT-MVA RAT =95.12,Conductor 95.12,Conductor IO T90 (oC),Conductor FF T250 T250 (oC),CrossArea 500 (mm2),Material Material Copper For the abbreviations used in the above capability curves, please refer to IEC standard
X Gas Field Development (Phases X)
Page 53 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
1 -INVERSE INVERSE MICOM P123,CT/RATIO=500.1,P/S =%70.0,T/S =3.50,HIGHSET =%1000,TIMESET= =%1000,TIMESET=0.2 2 -INVERSE INVERSE MICOM P143,CT/RATIO=2500.1,P/S=%80.0,T/S=1.00,HIGHSET =%800,TIMESET= =%800,TIMESET=0.6 0.6 *** 3 -E.INVER E.INVER MICOM P127,CT/RATIO=2000.5,P/S P127,CT/RATIO=2000.5,P/S =%103.0,T/S=0.65,HIGHSET =% .0,T/S=0.65,HIGHSET =%2 =%281 81,TIMESET= =0.75 4 -E.INVER E.INVER 7SJ611,CT/RATIO=500.1,P/S=%100.0,T/S=0.70,HIGHSET =% =%1400,TIMESET 1400,TIMESET=0
*** Note that the P143 has incorrect settings settings as described in the text
X Gas Field Development (Phases X)
Page 54 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
1 -I0 D.T. MICOM P225,CT/RATIO=150.1,P/S = =%30.0,T/S 30.0,T/S =0.10 2 -INVERSE INVERSE MICOM P143,CT/RATIO=2500.1,P/S = =%10.0,T/S 10.0,T/S =1.00,HIGHSET =%100,TIMESET =0.5 *** 3 -E.INVER E.INVER MICOM P127,CT/RATIO=2000.5,P/S P127,CT/RATIO=2 00.5,P/S =%10,T/S = ,T/S =0.0 =0.05 4 -I0 I0 D.T. 7SJ611 50Ns,CT/RATIO=250.1,P/S 50Ns,CT/RATIO=250.1,P/S = =%19.0,T/S 19.0,T/S =0.70 5 -I0 I0 D.T. 7SJ611 50N,CT/RATIO=500.1,P/S= 50N,CT/RATIO=500.1,P/S=% %140.0,T/S 140.0,T/S =0.20 6 -I0 I0 D.T. MICOM P541,CT/RATIO=1600.1,P/S =%45.0,T/S =0.20 7 -I0 I0 D.T. MICOM P541,CT/RATIO=1600.1,P/S =%48.0,T/S = =0.20 8 -I0 I0 D.T. MICOM P123,CT/RATIO= P123,CT/RATIO=1600.1,P/S=% .1,P/S=%48.0,T/S .0,T/S =0.20 9 -I0 I0 D.T. MICOM P123,CT/RATIO= P123,CT/RATIO=1600.1,P/S .1,P/S =%175.0,T/S =% .0,T/S =0. =0.40 *TRANSFORMER CAPABILITY CURVE: RATRAT-MVA MVA =100,Through Fault,Frequent,Inrush=9,Curve TCC/0.1sec *** Note that the P143 has incorrect setting settings s as described in the text
X Gas Field Development (Phases X)
Page 55 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Table 6:: Please find the full report of this table in the the attachment, NC-6340S 6340S-500-1600-0004 0004-RELAY RELAY SETTING STUDY STUDY-AT01(CT2000.5) (CT2000.5)
The following figures (Figures 15, 16, 17,18,19,and 17,18 20)) are snapshots of relay operating times (excluding Circuit Breakers opening times) in PASHA protection checking studies studies.. In this section we have used PASHA short cicuit analysis to find the operating times of the relays. They are shown in the figures and iin the lists. In these figures the symbols PH indicate the phase relay action and symbols Ea indicates the earth relay actions. The unit protections protections are checked against operating for inside fault and not to operate for the fault through the devices (outside fault).. The operation and no operation of them are shown in figure 21.
X Gas Field Development (Phases X)
Page 56 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Figure 155: Short circuit response of the relays (operating times excluding cluding CB times are shown in diagram)
X Gas Field Development (Phases X)
Page 57 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Figure 166:: Short circuit response of the relays (operating times excluding CB times are shown in diagram)
X Gas Field Development (Phases X)
Page 58 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Figure 17(a): 17 : Short circuit response of the relays (operating times excluding CB times are shown in diagram) diagram),maximum ,maximum condition
Figure 17(b): 17 : Short circuit response of the relays (operating times excluding CB ttimes imes are shown in diagram),minimum diagram),minimum condition
X Gas Field Development (Phases X)
Page 59 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Figure 18: Short circuit response of the relays (operating times excluding CB times are shown in diagram)
X Gas Field Development (Phases X)
Page 60 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Figure 199:: Short circuit response of the relays (operating times excluding CB times are shown in diagram)
X Gas Field Development (Phases X)
Page 61 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Figure 20: 20: Short circuit response of the relays (operating times excluding CB times are shown in diagram)
X Gas Field Development (Phases X)
Page 62 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Figure 21: 21: Short circuit response of the unit differential relays.
INTERNAL FAULT IN TRANSFORMER ----------------------------WINDING INDING PERCENT FROM NEUTRAL IN SECONDARY PHASE A: 50.
PHASE B: 50.
PHASE C: 50.
TERMINAL CURRENTS RED PHASE
YELLOW PHASE
BLUE PHASE
MAG(PU) ANG(DEG) MAG(PU) ANG(DEG) MAG(PU) ANG(DEG) PRIMARY SIDE
81.7565 -87.11 87.11 81.7565 152.89 81.7565
0.00
SECONDARY SIDE
38.1282
0.00
60.71 38.1282 -59.29 -59.29 38.1282
UNIT PROTECTION --------------SCH. H.
B R A N C H
NO. ----------------SEND
RECV
S E T T I N G S SET CT-RAT CT RAT (%) PRIMARY
1 MBF1321 INT1
20.0 20.0
1 MBF1321 INT1
20.0
1600.1
OUT1
30.0
1600.1 500.1
OUT1
30.0
81.8 500.1
2 Actual Currents I1,I2 (A), 2 INT1
OUT1
30.0
81.8 500.1
2 Actual Currents I1,I2 (A),
81.8
MAGNITUDE
MAGNITUDE
IDIF(A)
IBAIS(A)
TRIPPING OPERAT. TIME (S) TIME(S)
RED PHASE
0.00
4.44
NO OPERATION
YEL. PHASE
0.00
4.44
NO OPERATION
BLUE PHASE
0.00
4.44
NO OPERATION
RED PHASE
119.87
119.88
0.000
0.100
YEL. PHASE
119.87
119.88
0.000
0.100
BLUE PHASE PHASE
119.87
119.88
0.000
0.100
RED PHASE
0.00
4.84
NO OPERATION
YEL. PHASE
0.00
4.84
NO OPERATION
BLUE PHASE
0.00
4.84
NO OPERATION
RED PHASE
4.46
173.59
NO OPERATION
YEL. PHASE
4.46
173.59
NO OPERATION
BLUE PHASE
4.46
173.59
NO OPERATION
2.2 1600.1 2.2 1600.1
2.2
2 Actual Currents I1,I2 (A), 2 INT1
1600.1
2.2
1 Actual Currents I1,I2 (A), 2 INT1
SECONDARY
2.2
1 Actual Currents I1,I2 (A),
----------------------------------
CT-RAT CT RAT
1600.1
1 Actual Currents I1,I2 (A), 1 MBF1321 INT1
CURRENT SEEN BY RELAY(PRIMARY)
------------------------
2.2 2000.1 38.1 2000.1 38.1 2000.1 38.1
LLL FAULT AT SUBSTATION OUT1 1 MBF1321 INT1
20.0
1600.1
1 Actual Currents Currents I1,I2 (A), 1 MBF1321 INT1
20.0
2.4 1600.1
1 Actual Currents I1,I2 (A), 1 MBF1321 INT1
20.0
2.4 1600.1
1 Actual Currents I1,I2 (A), 2 INT1
OUT1
30.0
2.4 500.1
2 Actual Currents I1,I2 (A), 2 INT1
OUT1
30.0
89.0 500.1
2 Actual Currents I1,I2 (A), 2 INT1
OUT1
30.0
89.0 500.1
2 Actual Currents I1,I2 (A),
X Gas Field Development (Phases X)
89.0
1600.1 2.4 1600.1 2.4 1600.1 2.4 2000.1 84.6 2000.1 84.6 2000.1 84.6
Page 63 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Table 7: Please find the clearer clear report of this table in the attachment, NC NC-6340S-500 500-1600-0004-RELAY RELAY SETTING STUDY STUDY-AT02(CT2000.5) (CT2000.5) RELAY SETTING & COORDINATION STUDY
Switchboard Name: Voltage Level: Relay Brand:
1S11A/1S11B 33KV AREVA
Type: Protections
MICOM P127 Ansi Code
Phase Overcurrent (Over load / Thermal)
Phase Short Circuit
51/49
50
Earth Fault
51G
Earth Fault
50G
Under Voltage
27
Over Voltage
59
Type: Protections
TEMPORARY INCOMING
I>
tI>
IDMTExtra INVERSE
1.03
0.65
I>> 2.81 I>
tI>> 0.75 tI>
0.1
0.05
Curve DT Curve IDMTExtra INVERSE Curve V< 70 V> 110
I>>
Core Balance Ratio:
N.A
Equipment Service:
Check Synchro
tI>>
tV< 1.25 tV> 0.2
-
KAVS100 Ansi Code
25
MAIN INCOMING 1S11A-IN 2000/5A
Settings Curve
Settings Slip Control
Check Synchron
Equipment Service: Item No: CT Ratio:
Live incoming / Dead outgoing
Under Voltage Live Voltage
95V
Dead Voltage
Check Synchronising
Slip Frequency
10V
RELAY SETTING & COORDINATION STUDY Switchboard Name: Voltage Level: Relay Brand: Type: Protections Over load / Thermal
Phase Overcurrent
Phase Short Circuit
BAY No. 20 132KV AREVA MICOM P123 Ansi Code 49
51
50
Earth Fault
51G
Earth Fault
50G
X Gas Field Development (Phases X)
TEMPORARY INCOMING
Equipment Service: Item No: CT Ratio:
OUTGOING MOBIN132 1600/1A
Core Balance Ratio:
N.A
Settings Curve
I
tI
OVER LOAD
0.26
10
Curve
I>
tI>
IDMTExtra INVERSE
0.3
0.8
Curve DT Curve DT Curve DT
I>> 2.7 I> 0.48 I>> -
tI>> 0.15 tI> 0.2 tI>> -
Page 64 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
RELAY SETTING & COORDINATION STUDY Switchboard Name: Voltage Level: Relay Brand:
1TR2 132/33KV SIEMENS
Type: Protections
7UT612 Ansi Code
Equipment Service: Item No: CT Ratio: 100MVA TEMPORARY TRANSFORMER
49
Over Fluxing
59
Type: Protections Numerical high impedance differential
2000:1A
Settings Curve
Over load / Thermal
NEUTRAL CT Ratio:
INCOMING 1S11-INCOMING 500/1A:2000/1A
I
tI
MUST BE VALIDATE BY TRANSFORMER MANUFACTURER
dV>df 110%
dV>dt 2s Equipment Service:
TRANSFORMER Ansi Code
INCOMING
Settings
Idiff>
tdiff>
Idiff>>
tdiff>>
30%
0s
1350%
0s
87T
Crossblock=ON,nthH=30% Cycle Limit=1.5,Slope1 Slope1=0.25 =0.25 base=0.0 Slope2=0.4 =0.4 base=1.25, IOther settings of diffrential protection: Inrush Blocking 2nd=15% 3Cycle , Crossblock=ON,nthH=30% RESTRAINT=0.1 =0.1 Fac. For increase=1.0 increase=1.0 Maximum permissible starting time=5.0s, Pick up for add on stablization=4.0 stablization=4.0 Duration of Add-on stabilization=15Cycle Time for cross-block Add-on Stabiliz.=15Cycle
PLEASE TAKE CARE IN APPLYING CORRECT S1 AND S2 AND PHASE SHIFT FOR DIFFRENTIAL PROTECTION Restricted Earth Fault (Earth Diffrential)
Idiff>
tdiff>
5%
0s
87N (64)
RELAY SETTING & COORDINATION STUDY Switchboard Name: Voltage Level: Relay Brand: Type: Protections
Equipment Service: Item No: CT Ratio:
1TR2 132KV SIEMENS 7SJ611
132KV incoming cable to 100MVA temporary transformer
Ansi Code
Phase Short Circuit
Earth Fault Earth Fault
51/49
50 50N 50Ns
X Gas Field Development (Phases X)
250:1A
Settings
Curve Phase Overcurrent (Over load / Thermal)
NEUTRAL CT Ratio:
INCOMING Receiving end 500/1A
I>
IDMTExtra 1 INVERSE Curve I>> DT 14 Curve I> DT 1.4 Curve I> DT 0.19
tI> 0.7
tI>> 0 tI> 0.2
tI> 0.7
Page 65 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
RELAY SETTING & COORDINATION STUDY Switchboard Name: Voltage Level: Relay Brand:
BAY No. 20 132KV MICOM
Type: Protections
P541 Ansi Code
Equipment Service: Item No: CT Ratio: OUTGOING FROM BAY 20
Phase Short Circuit
51/49
50
Earth Fault
51G
Earth Fault
50G
Type: Protections Numerical high impedance differential
I>
IDMTExtra 0.3 INVERSE Curve I>> DT 2.7 Curve I> DT 0.48 Curve I>> DT -
tI> 0.8 tI>> 0.15 tI> 0.2 tI>> -
CABLE Ansi Code
87
(L)
ABREVIATION
Settings Curve
Phase Overcurrent (Over load / Thermal)
LOCAL OUTGOING 132 1600/1A
Equipment Service:
LOCAL
Equipment Service: Item No: CT Ratio:
REMOTE INCOMING132 1600/1A
Settings
IS1
IS2
K1
K2
TIME
20%
2A
30%
150%
0s
Other settings of diffrential protection:
RELAY SETTING & COORDINATION STUDY Switchboard Name: Voltage Level: Relay Brand: Type: Protections
1TR2 132KV MICOM P541 Ansi Code
INCOMING CABLE
Settings Curve
Phase Overcurrent (Over load / Thermal)
Phase Short Circuit
51/49
50
Earth Fault
51G
Earth Fault
50G
Type: Protections Numerical high impedance differential
I>
IDMT0.32 Extra INVERSE Curve I>> DT 5 Curve I> DT 0.45 Curve I>> DT -
tI> 0.7 tI>> 0 tI> 0.2 tI>> Equipment Service:
CABLE Ansi Code
87
(R)
ABREVIATION
REMOTE
Settings
IS1
IS2
K1
K2
TIME
20%
2A
30%
150%
0s
Other settings of diffrential protection:
X Gas Field Development (Phases X)
Page 66 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
A.I.1 A.I. GAS PLANT ELECTRICAL NETWORK REPRESENTATION
Gas plant single line diagram as represented in drawing DW 6340S 120 1633 0001 is represented in PASHA software. Drawings DW-6340S-550 550-1600-0001 0001,, which is included in the last pages of this appendix, shows the Gas plant electrical network topology as represented in PASHA. Here the type and lengths of cables are also shown. Documents NC 6340S 999 1630 0020 0020, and NC 6340S 999 1630 002 0021 are used to provide the required data. Here, 11 KV moto motorr loads are represented separately based on their dynamic models. Some of 6 KV motor loads are also represented separately based on their dynamic models models. Other 6KV motors and 400 V induction motor loads are summed and represented as equivalent motor loads on their corresponding bus bars. Static loads are lumped represented on their appropriate locations. The tie switched position and the amount of loads are set according to worst condition situation as addressed in document NC 6340S 999 1630 0020 0020.
A.I.2 A. INPUT PUT DATA
Table I.1 shows the input data base and Table I.2 shows the actual input data provided in PASHA edit pages.
X Gas Field Development (Phases X)
Page 67 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Table I.1 Data base for Gas plant equipment
7
6
7
6
7
6
7
1(150)
Used for Tie connections and those not known
ZERO SEQUENCE REACTANCEPU/KM
ZERO SEQUENCE RESISTANCEPU/KM
33 6 400
100 5 2
33 6 0.4
0.0001 0.0001 0.0001
0.0003 0.0003 0.0003
FICT
474
2
0.4
0.0001
0.0003
REACTANCE PU/KM
FICT FICT FICT
83 83 83 83, 83, 83
RESISTANCE PU/KM
RATING KV
7
RATING MVA
6 6
Type MANUFACT.
PASHA LIB.
SIZE
SUSEPTANCE PU/KM
CABLES AND LINES DATA BASE CABLE
6118500
Note : RATING MVA IS OBTAINED FROM CABLE CURRENT CAPACITY, RATINGS ARE THE PU BASES TOO
X Gas Field Development (Phases X)
Page 68 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
DX11 DX11 DX11 DX11 DX11 DX11 DX11 DX11 DX11 DX11 DX11 DX11 DX11 DX11 DX11 DX11 DX11 DX11 DX11 DX11 DX11
/ / / / / / / / / / / / / / / / / / / / /
(*8 (*8 (*8 (*8 (*8 (*8 (*8 (*8 (*8 (*8 (*8 (*8 (*8 (*8 (*8 (*8 (*8 (*8 (*8 (*8 (*8
*30A and 50A grounding resistor considered for all 11.5KV and 6KV side correspondingly, **X X means Yn and from simulation point of view DY11 is equal to DY5, and DY1 is equal to DY7,
X Gas Field Development (Phases X)
Type or MANUFACT.
RATIO DV
MAX. TAP
TAP STEP
MIN. TAP
REACTANCE PU
ZERO SEQUENCE RESISTANCE PU*
REACTANCE PU
RESISTANCE PU
PASHA LIB.
CONNECTION TYPE **
U1/U2 KV/KV
RATING (BASE) MVA
TRANSFORMERS DATA BASE
Page 69 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
Type or Man ufac turer
9 : : : 9 9 ; 9 9 9 9 9 9 9 9
H (Sec.) (total) (driven)
REACT.-PU
ROTOR RESIST.-PU
MVA
MAGNETIZING
BASE
VOLTAGE KV
STATOR REACT-PU
LIB.
REAC T.-PU PU
OTHERS
RESIST.-PU
KW
PASHA
RATED
MOTORS DATA BASE
Driven TYPE*
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
*Driven Type: Type Mechanical Torque Formula=(A+B(1 Formula B(1-s)+C(1-s)2)Tmo where A+B+C=1, B and C is written and s is slip.
X Gas Field Development (Phases X)
Page 70 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
% STATIC Load
H (Sec.) (total) (driven)
REACT.-PU
REAC T.--PU
ROTOR RESIST.-PU
MVA
MAGNETIZING
BASE
VOLTAGE KV
STATOR REACT-PU
LIB.
OTHERS
RESIST.-PU
KVA
PASHA
RATED
LUMPED LOAD LOADS DATA BASE
Driven TYPE*
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 *Driven Type: Type Mechanical Torque Formula=(A+B(1 Formula=(A+B(1-s)+C(1-s)2)Tmo where A+B+C=1, B and C is written and s is slip.
X Gas Field Development (Phases X)
Page 71 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
H (Sec.) (total) (driven)
REACT.-PU
REAC T.--PU
ROTOR RESIST.-PU
MVA
MAGNETIZING
BASE
VOLTAGE KV
STATOR REACT-PU
LIB.
OTHERS
RESIST.-PU
KVA
PASHA
RATED
LUMPED LOADS LOADS DATA BASE (continued 11)
% Load
Driven TYPE*
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 *Driven Type: Type Mechanical Torque Formula=(A+B(1 Formula=(A+B(1-s)+C(1-s)2)Tmo where A+B+C=1, B and C is written and s is slip.
X Gas Field Development (Phases X)
Page 72 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
H (Sec.) (total) (driven)
REACT.-PU
REAC T.--PU
ROTOR RESIST.-PU
MVA
MAGNETIZING
BASE
VOLTAGE KV
STATOR REACT-PU
LIB.
OTHERS
RESIST.-PU
KVA
PASHA
RATED
LUMPED LOADS LOADS DATA BASE (continued 2)
% Load
Driven TYPE*
4 4 4 4 4 4 4 *Driven Type: Type Mechanical Torque Formula=(A+B(1 Formula=(A+B(1-s)+C(1-s)2)Tmo where A+B+C=1, B and C is written and s is slip.
X Gas Field Development (Phases X)
Page 73 of 158
RELAY SETTING STUDY (CT2000:5) Doc. No. : NC--6340S-550-1600 1600-0004
Rev. No. : 0
GENERATOR DATA BASE
RATED POWER MVA 100 2.5 0.150
PASHA LIB. 100 92 150
TYPE
8(
View more...
Comments