Raj Emtp Model

Share Embed Donate


Short Description

Download Raj Emtp Model...

Description

ii

INSULATION COORDINATION OF QUADRUPLE CIRCUIT HIGH VOLTAGE TRANSMISSION LINES USING ATP-EMTP

SITI RUGAYAH BTE DUGEL

A thesis submitted in partial fulfillment of the requirements for the award of the degree of Master of Engineering (Electrical-Power)

Faculty of Electrical Engineering Universiti Teknologi Malaysia

MEI 2007

iv

To my beloved husband and dear children, who are always giving their support and understanding. They are always with me when I need support and advice and without their understanding, I will not be able to complete my master study

v

ACKNOWLEDGEMENT

I would like to express my sincere appreciation and special thanks to my project supervisor, Prof. Dr. Zulkurnain Abdul Malek, for his support, advices, encouragement, guidance and friendship. I wish to thank the grateful individuals from TNB research and TNB Generation. I am grateful for their cooperation and willingness to assist me in this matter. I am also would like to thank all my friends especially Adzhar Bin Khalid for their assistance towards the successful completion of this project. I am also indebted to Universiti Teknologi Malaysia (UTM) for their assistance in supplying the relevant literatures. Last but not least, I wish to thank my beloved husband, Surmazalan B. Ngarif who give me his undivided attention and support throughout this research.

vi

ABSTRACT

A significant number of faults in overhead transmission lines are due to lightning strikes which cause back flashovers and hence single or double circuit outages. The continuity and quality of the power supply is therefore can be severely affected by the outages, especially in Malaysia where the isokeraunic level is rather high. The lightning performance of transmission lines is also influenced by the transmission line configuration itself. In Malaysia, the TNB's transmission lines consist of 500 kV or 275 kV double circuits, and 275/132 kV quadruple circuits. It is known that the lower portion of the 132 kV line apparently has the lowest lightning performance.

The application of transmission line arresters is also known to be the best method in improving the lightning performance of transmission lines in service. However, its usage requires proper coordination and placement strategy to ensure optimum improvement in lightning performance.

In this work, the ATP-EMTP simulation program was used to study the lightning performance of the quadruple circuit transmission line behaviour towards lightning activities. The models used include those for the surge arresters, overhead lines, towers and insulators. All models were based on the data supplied by the utility. Initial results show that the configuration 6 gives the best protection or lowest flashover rate.

vii

ABSTRAK

Kebanyakkan gangguan bekalan pada talian atas penghantaraan adalah disebabkan oleh panahan petir yang mana telah mengakibatkan kerosakkan dan gangguan bekalan pada litar sediada dan litar berkembar. Gangguan bekalan ini telah mengakibatkan keterusan dan kualiti bekalan elektrik terganggu teruk. Tahap panahan petir di talian atas penghantaran adalah juga dipengaruhi oleh configurasi talian atas itu sendiri. Di Malaysia, talian penghantaran TNB adalah terdiri dari 500kV atau 275kV litar berkembar dan 275/132kV litar berkembar empat(quadruple circuits). Telah dikenalpasti bahawa pada bahagian bawah talian 132kV adalah merupakan tahap panahan petir yang terendah.

Penggunaan penangkap kilat untuk talian atas adalah merupakan cara terbaik dalam memperbaiki tahap panahan petir di talian atas yang sedang beroperasi. Walau bagaimanapun, penggunaanya memerlukan koordinasi yang tepat dan lokasi yang strategik bagi mendapatkan kesan yang optimum.

Untuk kajian ini, aturcara simulasi ATP-EMTP telah digunakan bagi mengkaji tahap dan aktiviti panahan petir terhadap litar berkembar empat. Model yang digunakan adalah termasuk penangkap kilat, talian atas penghantaraan, menara dan penebat. Semua data yang digunakan untuk dimodelkan adalah diperolehi dari pembekal elektrik

Keputusan dari simulasi yang dibuat menunjukkan configurasi 6 telah

menghasilkan perlindungan yang terbaik dan kadar gangguan bekalan yang terendah

viii

UTM(PS)-1/02

School of Graduate Studies Universiti Teknologi Malaysia

VALIDATION OF E-THESIS PREPARATION

Title of the thesis:

INSULATION COORDINATION OF QUADRUPLE CIRCUIT HIGH VOLTAGE TRANSMISSION LINES USING ATP-EMTP

Degree:

MASTER OF ENGINEERING (ELECTRICAL POWER)

Faculty:

KEJURUTERAAN ELEKTRIK

Year:

2007

I SITI RUGAYAH BINTI DUGEL hereby declare and verify that the copy of e-thesis submitted is in accordance to the Electronic Thesis and Dissertation’s Manual, School of Graduate Studies, UTM

_____________________

______________________

(Signature of the student)

(Signature of supervisor as a witness)

Permanent address:

Name of Supervisor: Prof Madya Dr Zulkurnain

No 17, Lorong Gurney off Jalan Semarak, 54100 Kuala Lumpur, Wilayah Persekutuan.

Bin Abdul Malek Faculty: KEJURUTERAAN ELEKTRIK

TABLE OF CONTENTS

CHAPTER

TITLE TITLE PAGE

i

DECLARATION

ii

DEDICATION

iii

ACKNOWLEDGEMENT

iv

ABSTRACT

v

ABSTRAK

vi

TABLE OF CONTENTS

vii

LIST OF TABLES

xiii

LIST OF FIGURES

xv

LIST OF ABBREVIATIONS

1

2

CHAPTER

PAGE

xviii

LIST OF SYMBOLS

xix

INTRODUCTION

1

1.1 Background

1

1.2 The Objectives of the Research

2

1.3 Scope of Study

3

LITERATURE REVIEW

3

2.1 Case Study by Kerk Lee Yen(TNBT Network SB)

3

2.1.1 Objective

3

2.1.2 Methodology

4

2.1.2.1 Line Section

4

2.1.2.2 Basic input data

4

TITLE

PAGE

10

2.1.3 Configuration of TLA installation

5

2.1.4 Result

5

2.1.5 Various installation of TLA

6

2.1.6 Simulation Result

7

2.1.6.1 Application of 3 TLA per tower

7

2.1.6.2 Application of 2 TLA per tower

7

2.2 Case Study by S.J Shelemy and D.R.Swatek 2.2.1 Objective

7

2.2.2 Introduction

8

2.2.3 Model Overview

8

2.2.4 Methodology

9

2.2.4.1 Tower Model

9

2.2.4.2 Line Termination

10

2.2.4.3 Insulator String

10

2.2.4.4 Tower Ground Resistance

10

2.2.4.5 Point of Contact

11

2.2.4.6 Lightning stroke

12

2.2.5 Results

12

2.2.6 Conclusion

13

2.3 Case Study by Y.A.Wahab, Z.Z.Abidin and S.Sadovic

CHAPTER

7

13

2.3.1 Objective

13

2.3.2 Introduction

14

2.3.3 Model Overview

14

2.3.4 Methodology

14

2.3.4.1 Electromagnetic model

15

2.3.4.2 Tower footing resistance model

16

2.3.4.3 Line insulation flashover model

16

2.3.4.4 Tower Model

17

2.3.4.5 Transmission Line Surge Arrester

17

TITLE

PAGE

11

2.3.4.6 Corona model

3

18

2.3.5 Result of Lightning Performance

18

2.3.6 Conclusions

20

TRANSMISSION SYSTEM

21

3.1 Transmission Line and Ground Wire

21

3.2 Insulator

22

3.3 Insulation Coordination

23

3.1.1 Definitions of Insulation Coordination

23

3.3.2 Insulation Coordination

24

3.3.3 Insulation Coordination Involves

24

3.3.4 Selection of Insulation Levels

24

3.3.5 Basic Principles of Insulation Coordination

25

3.3.6 Insulation Withstand Characteristics

26

3.3.7 Standard Basic Insulation Levels

26

3.4 Arching Horn

27

3.5 Earthing

28

3.6 Tower Types

28

3.6.1 Tower with wooden cross arm

29

3.7 Design Span

30

3.8 System Over voltages

30

3.9 Fast Front Over voltages

31

3.10 Fast Front Over voltages

31

3.11 Metal-Oxide Arresters

33

3.12 Gapped TLA and Gapless TLA

33

3.13 Surge Lightning Arrester placement (TLA)

34

3.14 Comparison of Available Surge Arresters (Gapless Type)

35

12 CHAPTER 4

TITLE

TRANSMISSION SYSTEM

5

PAGE 37

4.1

System Modelling

37

4.2

EMTP Simulation

37

4.3

Selected model and Validation

38

4.4

Transmission Line

38

4.5 Line exposure to lightning

39

4.6

Shielding Failure

40

4.7

Overhead Transmission Lines

41

4.8

Line length and Termination

41

4.9 Tower Model

42

4.10 Tower footing resistance model

45

4.11 Insulators

46

4.12 Backflashover

46

4.13 Corona

47

4.14 Line surge arrester

47

4.15 Selection of Lightning Configuration

51

AVAILABLE METHOD FOR LIGHTNING

52

PERFORMANCE IMPOVEMENT 5.1

Additional Shielding Wire

53

5.2 Tower Footing Resistance

53

5.3 Increase the Tower Insulation

54

5.4

Unbalance Insulation

54

5.5 Transmission Line Arrester

55

5.6

Installation of TLA based on TFR

55

5.6.1

57

Additional of TLA at low TFR Section

5.6.2 Installation of TLA on one circuit

58

5.6.3

59

Coordination of Gap Spacing fot Transmission

13 CHAPTER

6

TITLE

PAGE

5.6 Extended Station Protection

61

SIMULATION METHOD

61

6.1 ATP-EMTP Simulation

61

6.2

Selected Model and Validation

62

6.2.1

62

Tower Model

6.3 Model And Parameters Used In The Simulation

7

66

6.3.1

Tower Model

66

6.3.2

Transmission Line model

67

6.4 Selection of Lightning Parameter

70

6.5

Lightning Amplitude

70

6.6

Time of Rising

71

6.7

Time of Falling

71

6.8

Limitation of Simulation

74

6.9

Statistical Approach

74

SIMULATION: 275 kV DOUBLE CIRCUIT

75

AND 275/132kV QUADRUPLE CIRCUIT LINE 7.1

275/132kV Quadruple Circuit and

75

Specification used in this Simulation 7.1.1

Model Used In The Simulation

78

7.2 Lightning Surge Arrester Configuration

79

7.3 Results Of Simulation For Lightning

80

Current of 17kA And Strike at Tower 2 7.3.1

Response without transmission line arrester

80

7.3.2

Response with transmission line arrester

81

7.3.2.1 TLA with configuration 1

82

7.3.2.2 TLA with configuration 2

83

14 7.3.2.3 TLA with configuration 3

83

7.3.2.4 TLA with configuration 4

84

7.3.2.5 TLA with configuration 5

85

7.3.2.6 TLA with configuration 6

85

7.3.2.7 TLA with configuration 7

86

7.3.2.8 TLA with configuration 8

87

7.4 Results Of Simulation For Lightning

88

Current of 120kA And Strike at Tower 2

8

7.4.1

Response without transmission line arrester

88

7.4.2

Response with transmission line arrester

89

7.4.2.1 TLA with configuration 1

89

7.4.2.2 TLA with configuration 2

90

7.4.2.3 TLA with configuration 3

90

7.4.2.4 TLA with configuration 4

91

7.4.2.5 TLA with configuration 5

92

7.4.2.6 TLA with configuration 6

92

7.4.2.7 TLA with configuration 7

93

7.4.2.8 TLA with configuration 8

94

7.4.2.9 TLA with configuration 9

94

7.5 Summary of the Simulation

95

7.4

98

Limitation of simulation

RECOMMENDATION AND CONCLUSION

REFERENCES

99 101

15

LIST OF TABLES

TABLE NO.

TITLE

PAGE

2.1

Section of BBTG-RSID 132 kV

4

2.2

Flashover rate for individual section of line

5

2.3

Various installation of TLA

6

2.4

Strike distances for the Nelson River HVDC

11

transmission line 2.5

Critical peak lightning current amplitudes for

11

the Nelson River HVDC transmission line towers 2.6

Back flashover rates and shielding failure rates

12

per 10,000 lightning strikes 2.7

Two-line stroke distribution to flat ground

15

2.8

Flashover rate for different circuits without line

18

surge arresters( flashover rate/100km/year) 2.9

Line total and multi circuit flashover rate without

19

line surge arresters( flashover rate/100km/year) 2.10

Line Total Flashover Rate Different Arrester

19

Installation Configurations( flashover rate/100km/year) 2.11

Line Double Total Flashover Rate Different Arrester

20

Installation Configurations( flashover rate/100km/year) 3.1

Conductors Type and Their Specification

22

3.2

Number of insulator set required based on voltage

23

and type of insulator set

16 TABLE NO.

TITLE

PAGE

3.3

Standard Basic Insulation Levels(BIL)

27

3.4

Arching distance and BIL for various circuit

27

and towers 3.5

Tower types and deviation angle

29

3.6

The major differences between gapped SLA

32

and gapless SLA 3.7

SLA placement and energy consideration

34

3.8

TLA Placement and Energy Consideration

35

3.9

Data on Gapless Transmission line arrester

36

manufactured by several company 4.1

Balakong to Serdang 132kV line information

39

4.2

Value for A0 and A1 based on 8/20 us residual

48

voltage supplied by manufacturer for the application of Pinceti’s arrester model. 5.1

Arrester installation strategy to eliminate double

56

circuit flashover 7.1

Parameter of the 275kV double circuit tower model

77

7.2

Value for A0 and A1 based on 8/20 us residual voltage

75

supplied for the application of Pinceti’s arrester model with 120kV rated Siemens 3EQ4-2/LD3 7.3

Line Performance For Different TLA Configuration

95

For Lightning Current of 17kA 7.4

Line Performance For Different TLA Configuration For Lightning Current of 120kA

97

17

LIST OF FIGURES

FIGURE NO.

TITLE

PAGE

4.1

Model of Transimission Line

40

4.2

Overhead Transmission Line, Tower and Insulator

42

model 4.3

Tower Representation for Quadruple Circuit

43

Transmission Line 4.4

M. Ishii’s tower model for a double circuit line tower

44

4.5

Pinceti’s arrester model used for representing

49

surge arrester 4.6

Relative error of residual voltage for representing

49

Siemens 120kV rated 3EQ4-2/LD3 SA with Picenti’s model compared to manufacturer performance data 4.7

Example of Gapless-type Surge Arrester installed

50

at 132kV BLKG-SRDG 4.8

Different arrester Installation Configurations

51

5.1

Available Method for Lightning Improvement

52

5.2

Unbalance tower insulation for double circuit line

55

5.3

Circuit location and TLA placement for a double

56

circuit line 5.4

Additional TLA at Low TFR section along the high

57

TFR section 5.5

TLA added only at one circuit of a double circuit line tower

58

18 FIGURE NO.

TITLE

PAGE

5.6

Extended station protection

60

6.1

M.Ishii’s tower model for a double circuit line tower

64

6.2

Tower equivalent radius

64

6.3

Modified M.Ishii’s tower model for a quadruple

66

circuit line tower modeling 6.4

Voltage Amplitude for Time of Falling 20µs

72

6.5

Voltage Amplitude for Time of Falling 50µs

72

6.6

Voltage Amplitude for Time of Falling 100µs

73

6.7

Voltage Amplitude for Time of Falling 200µs

73

6.8

Voltage Amplitude for Time of Falling 500µs

73

7.1

Simulated 275/132kV quadruple circuit line

76

7.2

Conductor identification for 275/132kV double

76

circuit line used in simulation 7.3

Modified M.Ishii’s tower model for a quadruple

78

circuit line tower modeling 7.4

Current injected at top tower 2

80

7.5

Lightning strike has caused voltage rise at top tower 2

80

7.6

Voltage measured at tower 2 which are connected to

81

275kV Line 7.7

Flashover Voltages when TLA are equipped at

82

conductor RBT and RBT1 7.8

Flashover Voltages when TLA are equipped at

83

conductor RBT132, RBT131 and BBT131 7.9

Flashover Voltages when TLA are equipped at

83

conductor RBT131, YBT 131 and BBT131 7.10

Flashover Voltages when TLA are equipped at

84

conductor RBT, RBT1 and RBT131 7.11

Flashover Voltages when TLA are equipped at conductor RBT132, RBT131, YBT132 and YBT131

85

19 FIGURE NO. 7.12

TITLE Flashover Voltages when TLA are equipped at

PAGE 85

conductor RBT, RBT1, RBT132 and RBT131 7.13

Flashover Voltages when TLA are equipped at

86

conductor RBT, RBT1, BBT, RBT132 and RBT131 7.14

Flashover Voltage when TLA are equipped at

87

conductor RBT, RBT1, YBT, RBT132 and RBT131 7.15

Current injected at top tower 2

88

7.16

Lightning strike has caused voltage rise at top tower 2

88

7.17

Flashover Voltage across insulators when TLA are

89

equipped at conductor RBT and RBT1 7.18

Flashover Voltage across insulators when TLA are

90

equipped at conductor RBT132, RBT131 and BBT1 7.19

Flashover Voltage across insulators when TLA are

90

equipped at conductor RBT132, RBT131 and BBT1 7.20

Flashover Voltage across insulators when TLA are

91

equipped at conductor RBT, RBT1 and RBT131 7.21

Flashover Voltage across insulators when TLA are

92

equipped at conductor RBT132, RBT131, YBT132 and YBT131 7.22

Flashover Voltage across insulators when TLA are

92

equipped at conductor RBT, RBT1, RBT132 and RBT131 7.23

Flashover Voltage across insulators when TLA are

93

equipped at conductor RBT, RBT1, BBT, RBT132 and RBT131 7.24

Flashover Voltage across insulators when TLA are

94

equipped at conductor RBT, RBT1, BBT, RBT132 and RBT131 7.25

Flashover Voltage across insulators when TLA are equipped at all conductors of 275kV and 132kV lines

94

20

LIST OF ABBREVIATIONS

ac

-

Alternating Current

ACSR

-

Aluminium Conductor Steel Reinforced

AIS

-

Air Insulated Substation

ATP

-

Alternative Transient Program

BFR

-

Back Flashover Rate

BIL

-

Basic Lightning Insulation Level

CB

-

Circuit Breaker

CBPS

-

Connaught Bridge Power Station

CFO

-

Critical Flashover

EMTP

-

Electro Magnetic Transient Program

FDQ

-

Frequency Dependent Q Matrix

GIS

-

Gas Insulated Substation

GPS

-

Global Positioning System

IEE

-

The Institution of Electrical Engineers

IEEE

-

Institute of Electrical and Electronic Engineers

IVAT

-

High Voltage and Current Institute

LOC

-

Leader Onset Conditions

MO

-

Metal Oxide

MOV

-

Metal Oxide Varistor

OPGW

-

Optical Fibre Composite Ground Wire

SA

-

Surge Arresters

SiC

-

Silicon Carbide

S/S

-

Substation

21 TFR

-

Tower Footing Resistance

TLA

-

Transmission Line Arresters

TNB

-

Tenaga Nasional Berhad

ZnO

-

Zinc Oxide

22

LIST OF PRINCIPLE SYMBOLS

µF

-

micro-Farad

µH

-

micro-Hendry

µs

-

nicro-second

A

-

Ampere

C

-

Capacitive

Ng

-

Ground Flash Density per Kilometer2 per year

kA

-

kilo-Ampere

kJ

-

kilo-Joule

kV

-

kilo-Volt

L

-

Inductive

MV

-

Mega-Volt

R

-

Resistance

Uc

-

Maximum Continuous Operating Voltage

Ur

-

Rated Surge Arrester Voltage

Km

-

kilometer

V

-

Volt

Z

-

Impedance

Zt

-

Surge Impedance

CHAPTER 1

INTRODUCTION

1.1

Background

Transmission system in services can be divided into two which are overhead transmission system and cable type transmission system. The main focus here is the overhead transmission systems, which are directly subjected to lightning over voltage. A significant number of the faults on overhead transmission lines are due to lightning. Lightning Faults may be single or multiple, and their elimination causes voltage dips and outages. Therefore, the outage rate of a line and the quality of the delivered voltage depend on the lightning performance of the line.

Many procedures have been presented over the years with the aim of predicting the lightning performance of transmission lines. Modern understanding about lightning phenomena and lightning attraction mechanisms allowed developing methods for estimating the lightning performance of overhead lines which avoid such empiricism.

2 For this purpose, the performance of transmission lines is estimated using ATP-EMTP simulation programs

1.2

The Objectives of the Research

The main objective of the project is to improve the lightning performance of transmission lines by the application of line surge arresters on the quadruple circuit transmission line and to analyze different line surge arresters application configurations in order to optimize application of this technology to the existing and to the future quadruple transmission lines.

1.3

Scope of Study

The main scope of this project is to study the applications of surge arresters on transmission line to improve the lightning and transient performance of the transmission line which is includes: ■

Arrangement of line arresters for optimum technical and economic



Performance which include where or which tower along the line arresters to be installed



The rating and withstand energy of the surge arresters



The arresters configurations

3

CHAPTER 2

LITERATURE REVIEW

The purposes of these Studies are to measure the performance to eliminate circuit trippings on Overhead Transmission Line Protection for double and quadruple circuit transmission line. The performance of the system are justified by installation of transmission line arrester (TLA) and analyzing different line surge arresters application configurations also to determine best location and configuration of TLA installation.

2.1

Case Study by Kerk Lee Yen(TNB Transmission Network SB): Studies on Optimum Installation of TLA for BBTG-RSID 132kV

2.1.1

Objective

The prime focus of this study is on elimination double circuit tripping by installation of transmission line arrester (TLA) and also to determine best location and configuration of TLA installation.

4 2.1.2

Methodology

The study using Sigma SLP software developed by Sodovic Consultant. Simulations are performed assuming no shielding failure as the software could generate only vertical stokes.

2.1.2.1 Line Sectioning

Based on tower footing resistance (TFR) and soil resistivity measurement collected, BBTG-RSID is sectionalized to 3 sections as follow to simply the analysis:

Table 2.1: Section of BBTG-RSID 132 kV Section Tower

Average TFR Soil Resistivity Land Profile Average

No.

(ohm)

1

1-5

8.86

(ohm-meter) 200

Length(km) Bushes/Flat

1.5

Land 2

6 – 29

56

1000

Hilly

7.2

3

30 - 39

5.04

30

Flat land

3.0

2.1.2.2 Basic input data

i ) Tower structure – standard drawings ii ) Total Thunderstorm day –200 thunderstorm days (Worst case scenario) iii) Type of lightning arrester – NGK gapless

5 2.1.3

Configuration of TLA installation 1) 1-3 arrangement 2) Double bottom 3) L-arrangement 4) I – arrangement

2.1.4 RESULT

1.

Without TLA installation

Result of flashover rate for the transmission line without TLA installation as table below:

Table 2.2: Flashover rate for individual section of line Section

Total Flashover

Single

Double Circuit

(Flash/km-year)

Circuit

Flashover

Flashover 1 (T1 – T5)

0

0

0

2 (T6 – T29)

55.71

35.05

20.65

0

0

0

3 (T30 – T39)

6 Above result shows that total flashover rate for both sections 1 and 3 are essentially zero. Hence, no installation of SLA is required for these two sections. The main factor that minimizes the flashover rate is their good tower footing resistance (TFR) values. TFR of these two sections are reasonably well maintained with values below requirement – 10 ohm

However, section 2 records high total flashover rate from simulation performed. Double circuit flashover constitutes about 37% of total flashover. As section 2 is hilly area, TFR readings are excessively high with an average of 56 ohms. High TFR hence contributes to higher back flashover.

2.1.5

Various installation of TLA

Table 2.3: Various installation of TSLA No

Scenario

Total Flashover

Single Circuit Double Circuit

(flashover/km/year)

Flashover

Flashover

1

1-3 arrangement

24.97

24.49

0.48

2

Double bottom

9.6

8.64

0.96

3

L-arrangement

3.36

3.36

0

4

I – arrangement

19.21

19.21

0

7 2.1.6

Simulation Result

2.1.6.1 Application of 3 TLA per tower

Configuration 3 and 4 are capable of eliminating double circuit flashover. However configuration “L” is the most effective solution as it helps to reduce single circuit flashover to the lowest compared to configuration “I”

2.1.6.2 Application of 2 TLA per tower

Configuration 2 “Double Bottom” records lowest total flashover rate. However, configuration 1 “1-3 arrangement” is more effective in reducing double circuit tripping

2.2

Case Study by S.J Shelemy and D. R. Swatek from System Planning Department, Manitobe Hydro, Manitoba, Canada

2.2.1

Objective

Study on Lightning Performance of Manitoba Hydro’s Nelson River HVDC Transmission Lines using Monte Carlo Model

8 2.2.2

Introduction

A Monte Carlo model of the lightning performance of Manitoba Hydro’s Nelson River HVDC Transmission Lines has been constructed in PSCAD/EMTDC Version 3. The value of key parameters is randomly drawn from user specified probability density functions (pdf’s). Most significant of these are the pdf’s of the positive and negative lightning stroke amplitudes which have been derived from actual data measured within 1km radius buffer of the lines. Estimates of the back flashover rate and shielding failure rate were calculated using various “zone-of-attraction” models.

2.2.3

Model Overview

A hierarchical multi-layered graphical representation of the conductor-towerinsulator-ground system was implemented in PSCAD/EMTDC Version 3. For each run(1 run = 1 lightning stroke), random number generators select values for the preionization tower footing resistance and for the amplitude and rise time of the lightning current pulse based on user defined probability density functions(pdf’s). Transmission tower geometry, stroke amplitude, and initial location are fed into zone-of-attraction model in order to determine the most likely point of contact between the stroke and the conductor-ground system

Each tower is represented by the detail traveling wave model. False reflections from the artificial truncation are eliminated by a multi conductor surge impedance termination. The non-linear time dependent characteristics of the insulator strings are

9 represented by the “Leader Progression Model” (LPM). The outcome of each run stored in a “Monte Carlo Accumulator”. Which compare the number and nature of insulator flashover to the total number of lightning strokes in order to obtain the rates of back flashover and shielding failure.

2.2.4

Methodology

Lightning outage statistics are estimated by way of a monte carlo simulation, by which we mean a multi-run case in which the key model parameters (pre-ionization footing resistance, lightning stroke rise time, lightning stroke peak current amplitude, and lateral position of stroke), for each separate run, are randomly drawn from a predefined pool of values. The Monte Carlo simulation was run for a total of 20,000 lightning strokes (10,000 strokes for both positive and negative lightning)

2.2.4.1 Tower Model

The tower was divided into five equivalent transmission line sections including the upper member, two cross arms, tower base, and a single equivalent of four parallel guy wires. The propagation time along the tower member is taken to be 3.92 x 10-9 sec/m. A 5 nsec simulation time step is used.

10

2.2.4.2 Line termination

To prevent false reflections from the truncations, the line model is terminated into its multi-conductor surge impedance.

2.2.4.3 Insulator String

The insulator string was modeled as a stray capacitance (0.476pF) in parallel with a volt-time controlled circuit breaker. The recursive equations selected by CIGRE for leader velocity v (t) and unabridged gap length are used. V(t) = kLe(t)( e(t) - E50 ) m/sec x

2.2.4.4 Tower Ground Resistance

High Magnitudes of lightning current flowing through ground decrease the ground resistance significantly below the measured low current values. Rt =

Ro/ √( 1 + Ir ) Ig

Ig =

1

ρEo



Ro ²

11 A PSCAD/EMTDC Version 3 component was developed to calculate each individual tower grounding resistance.

2.2.4.5 Point of Contact

Electromagnetic models that treat the zone-of-attraction as a strike distance include the strike distance to ground Rg, The strike distance to the shield wire, Rs and the strike distance to the pole conductor, Rc. Five electromagnetic models were studied as table below: Table 2.4: Strike distances for the Nelson River HVDC transmission line Model

rg

rs

rc

Young

27 Im0.32

1.07I rg

1.046 rg

Love

10 Im0.65

rg

rg

IEEE 1992 T&D

9 Im0.65

1.256 rg

1.256 rg

1.274 rg

1.180 rg

6.8 Im0.74

5.9 Im0.74

Brown & Whitehead Eriksson

6.4

Im0.75

N.A

List of the critical peak current amplitudes predicted for the Nelson River HVDC transmission line tower as table below

Table 2.5: Critical peak lightning current amplitudes for the Nelson River HVDC transmission line towers Model Young Love IEEE 1992 T&D Brown & Whitehead Eriksson

Critical Current(kA) 25 30 70 20 15

12

2.2.4.6 Lightning Stroke

The lightning stroke was modeled as a current impulse, idealized as a triangular wave. Because insulation occurs shortly after the lightning strike, the fall time was fixed at 100 micro-sec.

2.2.5

Results

Using fault data for the Nelson River HVDC transmission lines collected between 1998 to 2000, faults were correlated to lightning strikes occurring at the same time and location. Over this period of time the FALLS program found 5066 negative lightning strokes and 530 positive lightning strokes within 1 km radius buffer of the transmission line. Out of these lightning strikes, only 6 are found to have caused lightning failure and due to shielding failures and back flashovers. The result of the simulation of lightning strike to the Nelson River HVDC transmission line as listed in table below:

Table 2.6: Back flashover rates and shielding failure rates per 10,000 lightning strikes Model Young Love IEEE 1992 T&D Brown & Whitehead Eriksson Measured

Back Flashover 2 3.3 6 7.5 2.1 3.6

Shielding Failure 11.2 58.5 75.5 3 6.2 7.1

13 From the result above, model of Young’s, Love’s and the IEEE 1992 T&D greatly over predicted the number of shielding failures. On the other hand the two remaining models, Brown & Whitehead and Eriksson’s model predicted failure rates closer to those actually observed, however the Brown & Whitehead model predicted a disproportionately high ratio of back flashovers to shielding failures. Of the models tested, Eriksson’s model yielded failure rates most consistent with the recorded data.

2.2.6 Conclusion

Through this analysis, the estimation of the back flashover rate and shielding failure rate were calculated using various zone-of-attraction models and Eriksson’s model yielded failure rate most consistent with lightning correlated fault data measured.

2.3

Line Surge Arrester Application on Quadruple Circuit Transmission Line by Y. A. Wahab, Z. Z. Abidin and S.Sadovic

2.3.1

Objective This paper is dealing with the application of line surge arresters on the

quadruple circuit transmission line and to analyze different line surge arresters application configurations in order to optimize application of this technology to the existing and to the future quadruple transmission lines.

14

2.3.2

Introduction

Line surge arresters are normally installed on all phase conductors of one circuit of the double circuit line. Arresters are installed on all towers of the considered 132kV line. With this arrester configuration, double circuit outages are eliminated but there exists possibility to have flashovers on the circuit without arresters.

Based on the positive experience with the surge line arresters on 132kV double circuit lines, it was decided to extend line surge arrester application to the quadruple circuit lines: 2 x 275kV and 2 x 132kV. By the application of the line arresters on 132kV circuits only, line overall lightning performance is improved since the majority of the flashovers will happen to 132kV circuit.

2.3.3

Model Overview

The circuit needs to be modeled is a quadruple circuit transmission line Balakong-Bandar Tun Razak, being commissioned in 1992, consists of two 275kV circuit and two 132kV circuit. Route length is 10.6km and number of towers is 37. Average line span is 300m. Line is operating with an average ground flash density of 10-20 strokes/km squared/year

2.3.4

Methodology

15 All computer simulations are performed using sigma slp simulation software tool. 2.3.4.1 Electromagnetic model

Line span is divided into short sections (10-15m each), in order to accept lightning stroke to the ground wires or to the phase conduction along the span. A total number of 20 to 30 thousand strokes are used in the electromagnetic simulations. Following striking distances are used: The Striking Distance to the conductor (CIGRE) rc = 10I 0.65 The striking distance to earth (IEEE) re = 5.5I 0.65 The striking distance to tower top rT = 1.05 rc I(kA) – lightning stroke current Two line CIGRE stroke distributions are modified to represent stroke distribution to flat ground as table below:

Table 2.7: Two-line stroke distribution to flat ground Parameter

Shielding

Failure Backflashover

range ( I < 15.9 kA)

Range( I > 15.9 kA)

Im (kA)

48.4

26.4

σ

1.33

0.605

16

2.3.4.2 Tower footing resistance model

The tower footing impulse resistance by the following equation: Ri =

Rt / √ ( 1 + I ) Ig

Ig =

1

ρEg



Rlc²

where: Rt - Tower footing resistance at low current and low frequency, (ohm) (Rt = 10 – 40 ohm) Ri - Tower footing resistance, (ohm) Ig

- The limiting current to initiate sufficient soil ionization,(A)

I

- The lightning current through the footing impedance, (kA)

ρ

- Soil resistivity ( 100 ohm-m)

Eg - soil ionization critical electric field (kV/m), (Eg = 400 kV/m) Rlc - tower low current resistance ρ

- 50

Rlc

2.3.4.3 Line insulation flashover model

The leader propagation model is used to represent line insulation flashovers: Vl

=

17 0d {(u(t) ) - Eo }e0.0015{u(t)/d }

17 D–lL Where : V1

=

Leader velocity, m/s

d

=

Gap distance, m

lL

=

Leader length, m

u(t)

=

Applied Voltage, kV

E0

=

520, kV/m

2.3.4.4 Tower Model

Section of the tower from the bottom cross arm to the ground is represented as propagation element, which is defined by the surge impedance Zt and the propagation length Iprop. Wave propagation speed on the tower was taken to be equal to the velocity of light. Section on the tower top(between tower top and top cross arm) are modeled as inductance branches parallel with damping resistors

2.3.4.5 Transmission Line Surge Arrester

Polymer housed line surge arrester with an external gap is used with the following characteristic: Rated Voltage:

120kV

Series gap spacing:

650mm

IEC Line discharge class:

II

Critical flashover voltage:

620kV

18

2.3.4.6 Corona model

The influence of the corona is modeled by the capacitance branches which are connected between conductors and ground

2.3.5

Result of Lightning Performance

Line lightning performance is first determined for the line without arresters and then several arrester installation configurations are studied. Lightning performance of a line without line surge arresters is presented in table below:

Table 2.8: Flashover rate for different circuits without line surge arresters ( flashover rate/100km/year) Rt(Ω) 10 15 20 25 30 35 40

C1(275) 0 0 0 0 0.19 0.19 0.19

C2(275) 0 0 0 0.19 0.39 0.58 0.19

C3(132) 0 0.78 5.66 12.69 20.69 29.67 42.55

C4(132) 0 2.14 4.88 10.92 20.69 33.58 46.85

From the above table has shown the majority of the flashover happened on 132kV circuits. For the tower footing resistance less than 10Ω, zero flashover rates is obtained. Table below is line total, single, double and triple line flashover rates presented.

19

Table 2.9: Line total and multi circuit flashover rate without line surge arresters ( flashover rate/100km/year) Rt(Ω) 10 15 20 25 30 35 40

Total 0 2.93 8.39 18.35 32.6 49.26 65.64

Single 0 2.93 6.24 13.08 23.81 32.41 41.98

Double 0 0 2.14 5.07 8.19 14.64 22.84

Triple 0 0 0 0.19 0.58 0.78 0.78

Number of double circuit flashovers depends on the tower footing resistance, and may reach value of 35% of the line total flashover rate, for the tower footing resistance of 40 Ω. Results of the simulation for the different line arrester installation configuration are presented in tables below: Table 2.10: Line Total Flashover Rate Different Arrester Installation Configurations ( flashover rate/100km/year) o : o o : o o : o o : o o : o Rt(Ω) o : o o : o o : o o : o o : o 10 0 0 15 2.93 0 20 8.39 0.78 25 18.35 2.53 30 32.6 5.66 35 49.26 8.78 40 65.64 13.08 o - Without Lightning Surge Arrester

o : o o : o o : o o : o o : o 0 0.19 2.14 6.24 9.37 15.62 23.62

o : o o : o o : o o : o o : o 0 0 0 0.58 0.97 3.12 3.89

o - With Lightning Surge Arrester The substantial improvement in the line total flashover rate is obtained by the installation of line arresters on the two bottom conductors of 132kV circuits than the

20 three arresters installed on the all phase conductors of one 132kV circuit. The best improvement in the line total flashover rate is obtained by the installation of the arrester on the bottom conductor of one 132kV circuit and on the one top conductor of one 132kV circuit.

Table 2.11: Line Double Total Flashover Rate Different Arrester Installation Configurations ( flashover rate/100km/year)

Rt(Ω) 10 15 20 25 30 35 40

o o o o o

: o : o : o : o : o 0 0 2.14 5.07 8.19 14.64 22.84

o o o o o

: o : o : o : o : o 0 0 0 0.19 0 0.58 1.17

o o o o o

: : : : : 0 0 0 0 0 0 0

o o o o o

o o o o o

: o : o : o : o : o 0 0 0 0 0 0.19 0.39

When line surge arresters are installed on all phases conductors of one 132kV circuit, double circuit flashover are completely eliminated. But it is to note that with this arrester installation configuration line total flashover rate remains high. Arrester installation configuration with the arresters on the bottom conductors of both 132kV circuits and on the one top conductor of one 132kV be able to reduce line total flashover rate and at the same time reducing double circuit flashover rate.

2.3.6

Conclusions

21 Lightning Performance with different voltage levels can be improved by the installation of the LSA on the lower voltage level circuits only and the ‘L’ arrester configuration will give the best improvement in the line total flashover rate

CHAPTER 3

TRANSMISSION SYSTEM

3.1

Transmission Line and Ground Wire

Three type of transmission tower are being used in the transmission system, whish sre the old single circuit, double circuit and the quadruple circuit. The current practiced is to build double circuit or quadruple circuit due to the needs to transfer large quantity of power. The double circuit transmission lines are used for voltage from 132kV, 275kV to 500kV. The quadruple circuits are used either for 132kV/132kV circuit or for 275kV/132kV circuit.

The conductor used in transmission lines is called ACSR (Aluminium Conductor Steel Reinforced). The ACSR conductor consists of aluminium and steel stranding. Two conductors are used per phase and are kept apart at a distance of

22 400mm by the use of spacers. For quadruple circuit line design the 275kV lines used a configuration of 2x400mm squared bundle namely zebra and 132kV lines uses a configuration of 2x300mm squared bundle namely batang. The earth wire used is ACSR 60mm squared namely skunk. Two earth wires are used per tower, one on each side Table 3.1: Conductors Type and Their Specification Conductor Code Name ACSR Curlew ACSR Zebra ACSR Curlew ACSR Curlew

3.2

Nominal Cross Sectional Area (mmⁿ) 500

Actual Cross Sectional Area (mmⁿ) n/a

Maximum Resistance At 20C (Ω) n/a

Diameter (mm)

Voltage (kV)

n/a

500

400

428.9

0.0674

28.62

275

300

338.5

0.0892

24.16

275 & 132

150

n/a

n/a

n/a

132

Insulator

Insulators are defined as non-conductive materials that cover separate or support a conductive material to prevent a passage of electricity to ground. From the point of transmission system, the insulator are being used to separate the conductors that carries large amount of current and the tower body that are directly connected to ground. The insulators are very important to the operating performance of the transmission system itself. The insulator provide mechanical support to the conductors and all the current carrying parts and subjected to normal operating and transient voltage

23

Standard materials used on transmission tower insulator are usually glass and porcelain because it has high dielectric strength and easily spotted if break. The type used are pin and cap types. Table 3.2: Number of insulator set required based on voltage and type of insulator set Type of Insulator set

Installation location

Upright Light Duty Tension Set Inverted Light Duty Tension Set Jumper suspension Set

Upper end of the slack spans between terminal tower Lower end of Slack end with line end and earth end arching horns Heavy angle towers to maintain the electrical clearances between the jumper loops to the tower body

3.3

132kV insulator units 10

275kV insulator units 20

10

16

13

20

Insulation Coordination

3.3.1 Definitions of Insulation Coordination

ƒ

IEC: The selection of the dielectric strength of equipment in relation to the voltages which can appear on the system for which the equipment is intended and taking into account the service environment and characteristics of the available protective devices

ƒ

IEEE: The selection of insulation strength consistent with expected over voltages to obtain an acceptable risk of failure

ƒ

General: The protection of electrical systems and apparatus from harmful overvoltages by the correlation of the characteristics of protective devices and the equipment being protected

24

3.3.2. Insulation Coordination

ƒ

Insulation coordination is an optimization process where the attempt is made to keep the overall cost of insulation, protection devices and service interruption to a minimum.

ƒ

For self-restoring insulation some failures have to be tolerated. However, insulation failures should be confined to areas where they cause minimum damage and least interruption of supply; and they should not compromise the safety of operating personnel.

3.3.3. Insulation Coordination Involves

ƒ

Estimating of credible over voltages that may appear in the network, their peak values, wave shapes and frequency of occurrence.

ƒ

Exploring means of reducing and/or diverting the over voltages.

ƒ

Selection of insulation levels to achieve the performance criteria.

3.3.4. Selection of Insulation Levels

25

™ For Voltages up to 300 kV ♦ Insulation is designed to withstand lightning and power frequency overvoltages. ♦ Sufficient margin is kept between the maximum overvoltage and the minimum withstand strength. ™ For Voltages Higher than 300 kV ♦ Choice of insulation and tower dimensions to withstand switching overvoltages. ♦ Check the number of failures due to atmospheric overvoltages. ♦ Check the ability of the design to withstand power frequency overvoltages under different operating conditions.

3.3.5. Basic Principles of Insulation Coordination

The process of correlating the insulation strengths of electric equipment with expected overvoltages and with the characteristics of surge protective devices. ™ Main Issues: ♦ System overvoltages, their wave shapes, peak values and probabilities of occurrence. ♦ Withstand characteristics of different types of insulation to different types of overvoltages. ♦ Measures used to reduce system overvoltages and protective devices to divert them

26

3.3.6. Insulation Withstand Characteristics

™ Voltage/Clearance Characteristics ♦ Withstand voltage as a function of gap spacing for lightning and switching surges. ™ Voltage/Time Characteristics ♦ Withstand voltage as a function of time to crest of the voltage surge. ™ Observations ♦ Lightning overvoltage is important for high voltage systems. ♦ Switching overvoltages are more important in extra- and ultra-high voltage systems.

3.3.7. Standard Basic Insulation Levels

™ Standard BILS developed for various system voltages based on experience. ™ Test voltage levels for other types of surges and tests are usually associated with the equipment BIL. ™ Standard BILS originally intended irrespective of how system was grounded.

27 ™ It became recognized that lower voltage arresters could be used on solidly grounded systems thus providing lower protective levels (better protection) for equipment insulation. ™ Resulted in reduced insulation levels (one or more steps lower). ™ At EHV, much greater economic incentive to use lower insulation levels through better arrester protection. Table 3.3: Standard Basic Insulation Levels(BIL) System Voltage

Standard BIL

Class (kV)

Reduced BIL (kV)

115

550

450

138

650

550

161

750

650

198

900

230

1050

287

1300

345

1550

900

*For effectively grounded system using 80% arrester

3.4

Arching Horn Arching horn put at the live end of the conductor string to create a preferred

path for lightning impulse to prevent flashing over at the conductors and insulators, which might damage it. Table 3.3 shows at arching distance and BIL at various circuit and tower design Table 3.4: Arching distance and BIL for various circuit and towers Circuit & Towers 275kV High Insulation Suspension

No.of Insulator Disc 16

Arching Distance (m) 2.16

BIL (kV) 1819

28 275kV Low Insulation Suspension 275kV High Insulation Tension 275kV Low Insulation Tension 132kV Suspension 132kV Tension 3.5

16

1.78

1411

2x20

2.62

1440

2x20

1.83

1100

10 2x14

1.40 1.87

1160 1000

Earthing

The basic lightning protection consists of atroke interceptor (earth wire), a down lead (tower) and an earth connection, whose primary function is to dissipate the lightning current safely into the ground. When the lightning struck the earth wire, a large amount of current flows through the tower and into the ground through the grounding system. The potential of the tower will be raised above the earth potential by an amount equal to or at least to the product of current and impedance of the earth path. If the potential rise minus and conductor voltage are much higher than the withstand voltage of the arching horn, a back flashover would occur from the tower to the conductor.

It is found that the BFR of a shielded line are very sensitive to tower footing resistance of the tower and that the BFR decrease with the decrease of the tower footing resistance. In addition, the discharge of the lightning currents into the ground will raised the potential around the earth point and those potential are related to the earth resistance and soil resistivity. Good earthing will reduce the BFR as well as the spread of dangerous voltages around the earth point.

3.6

Tower Types

29

The tower family are usually selected based on their distribution of line angle. Line angle could be grouped such that angle would follow a pattern of light medium and heavy suspension and medium and heavy tension types. Tower types are divided into four categories: 1. 23 Series tower : 2x132kV – twin(duplex) 2x300mm sq. “Batang” 2. 24 Series tower : 2x275kV – twin(duplex) 2x400mm sq. “Zebra” 3. 2423 Series tower : 2x275kV + 2x132kV – twin(duplex) 2x400mm sq. “Zebra” + twin(duplex) 2x400mm sq. “Zebra” 3. 2323 Series tower : 2x132kV – twin(duplex) 2x300mm sq. “Batang” + 2x132kV – twin(duplex) 2x300mm sq. “Batang”

Table 3.5: Tower types and deviation angle Tower Type

Angle of Dviation

Suspension Tower (Line-tower)

0-2

Tension Tower (Section Tower)

2-10

Tension Tower (Medium Tower)

10-30

Tension Tower (Heavy Tower)

30-60

Tension Tower (Right Tower)

60-90

Tension Tower (Terminal Tower)

0-10

3.6.1 Tower with wooden cross arm

The advantages of wooden cross arm is its higher impulse level and its good arch quenching properties, which result in a better lightning performance of the line. The

30 275kV cross arm is made from 4 pieces of chengal timber , 2 strut and 2 tie members and the 132kV design is made from 3 pieces of chengal timber, 2 strut and 1 tie. Due to its structursl strength limitation, wooden cross arm are used only in light suspension tower while the heavy suspension and tension towers are fitted with steel cross arm and longer tension strings. 3.7

Design Span

Span is defined as a distance between a tower top to the next adjacent tower with both tower are in the same tower family. The three terms used for span are:

1.

Basic Span defined as horizontal distance between centres of adjacent supports on level ground from which the height of standard supports is derived with the specified conductor’s clearances to ground in still air at maximum temperature

2.

Wind Span defined as half the sum of adjacent horizontal span length supported on any on tower

3.

Weight Span defined as equivalent length of the weight of conductor supported at any one tower at minimum temperature in still air

3.8 System Over voltages

™ Characteristic: ♦ They appear during abnormal operating conditions or during transitions between steady states.

31 ♦ They can have values much higher than system operating voltage. ♦ They form a threat to the integrity of the system and the safety of personnel. ™ Classification: ♦ By origin: ƒ

internal overvoltages

ƒ

external overvoltages

♦ By waveshape:

3.9

ƒ

temporary overvoltages

ƒ

slow front overvoltages

ƒ

fast front overvoltages

Fast Front Over voltages

™ Due to lightning strokes hitting towers, ground wires, or phase conductors. ™ Can also be induced by coupling with structures hit by lightning. ™ Frequency of occurrence depends on the thunderstorm activity in the area which is measured by the number of thunderstorm days per year. ™ The amplitude of the overvoltage surge generated by atmospheric discharge depends on the discharge current, line surge impedance and tower footing resistance.

3.10

Surge Arresters

32

The application of surge arresters on distribution lines started around 1975 in Japan. Field trial of surge arresters 66kV, 77kV and 138kV lines were carried out in and around 1980 in Japan and the United States. An external air gap in series with the surge arrester was introduced in 1985 to electrically isolate the surge arrester from the system. No international Standards specific on TLA available. Table below summarizes the basic requirements of TLA

Table 3.6: Fundamental requirements for surge arresters on line(TLA) Functional

Practical

Suppress over voltages and prevent flashover Light and compact at the instant of lightning Is able to cut off follow current before Easy to install on towers operation of the circuit breaker Not operate under the switching over voltages

Minimum maintenance and easy to inspect

Not cause permanent fault and impedance Long life and adverse weather proof circuit re closing in the event the arrester fails

Safe and explosion-proof

The idea of using metal oxide-surge arresters to prevent lightning fault on lines has existed quite a long time. However, there was a practical concern on “stresses” that these surge arresters may be subjected when installed on towers and the line tripping that the disconnecting device fail to operate to isolate the faulty arresters. ™ Four general classes of devices that have been used to limit over voltages and permit lower (more economical) insulation levels of equipment: ♦ spark gaps ♦ expulsion-type arresters ♦ gapped valve-type arresters

33 ♦ (gapless) metal-oxide arresters ™ Devices do not provide the same degree of protection ™ Spark gaps have been used up to 245 kV in locations with modern lightning activity. 3.11

Metal-Oxide Arresters

Advantages using Metal-Oxide arresters as below:

™ Use metal-oxide (zinc oxide) for non-linear resistor element. ™ Metal-oxide has a much more non-linear characteristic than silicon carbide. ™ Characteristic is so flat that current at normal (1 per unit) voltage is in milliamps range that element can conduct continuously without overheating. No series gap required ™ Some early versions used a shunt gap across some of the elements to reduce discharge voltage at high currents. No longer used in current designs. ™ Present metal-oxide arresters have better protective characteristics than gapped silicon-carbide arresters and also other advantages. ™ Metal-oxide arresters are very suitable for HVDC applications due to possibility of using parallel columns to share duty.

3.12 Gapped TLA and Gapless TLA

34 Both type of TLA are being used in many utilities worldwide to prevent lightning faults on transmission lines. However some utilities may prefer one to the other. Both types have advantages and disadvantages owing primary to the fact that the gapless TLA is connected directly to the system while gapped TLA is only connected directly to the system temporarily during the gap (spark over) operation. Table below shows the major differences between gapped TLA and gapless TLA. This table is used as basis for selecting of gapless TLA in this modeling Table 3.7: The major differences between gapped TLA and gapless TLA Subject Basic Construction Operation Principle

TLA Reliability

Faulty arrester isolation

Electrical Stresses

Gapped TLA Metal-oxide surge arrester unit in series with external air gap connected between live phase conductor and earth When lightning strikes the tower or shield wire, there will be a rise of voltage on the tower. The voltage across the insulator may reach sufficiently high value and cause the gap to spark over. A large lightning surge arrester is discharged through surge arrester and overvoltages are suppressed. As lightning surge current is discharged, resistance of ZnO block increases and current becomes small. Faulty arresters may reduce the breakdown strength of the SLA and upset the overall insulation coordination. Gap distance critical. Air gap operation can be affected by conditions during service.

Provided by external series air gap

Not subjected to temporary over voltages. Lower arrester rating and smaller arrester feasible

Gapless TLA Metal-oxide surge arrester directly connected live conductor and earth Metal oxide surge arrester to suppress the overvoltages across the insulator. Disconnecting device will operate to isolate the arrester in case the arrester fails during service Very critical because faulty arrester would cause the line to trip Arrester is usually equipped with a disconnecting device to isolate faulty arrester. The disconnecting devices operation must not affect line clearance or impedance line reclosing subjected to temporary over voltages on the system. Higher electrical stresses on the arresters

35

Installation

Maintenance Subject Arrester size and weight

More hardware needed (external spark gap rods). Gap distance critical

Periodic inspection and maintenance of surge arresters and spark gap rods recommended Gapped TLA Smaller arrester unit possible

Energy sharing Energy less assured and can be affected by the “non-ideal” air gap spark-over Operational Failure of air gap to operate correctly and Risk consistently. Gap operation may be affected by conditions in service

Strokes

TLA Placement

MOV block and polymeric housing Less hardware needed. Spaces on the strength of (existing) towers may be the limiting factors for large and heavy SLA Periodic inspection and maintenance of surge arresters recommended Gapless TLA Connected continuously to the system and subjected to over voltages in the system. Bigger and larger arrester may be required Better energy sharing between arresters Failure of the disconnecting device to operate to isolate faulty arresters

Energy Consideration

3.13 Surge Lightning Arrester placement (TLA) The placement of arrester for black-flashover, direct stroke and induced surges are summarized below :

Table 3.8: TLA placement and energy consideration High energy direct strokes Fir arresters on the other phases and Arrester must withstand to line without shield wire adjacent structures if high TFR discharge energy and causes back flashover from struck high current amplitude phase and structure to another phase in lightning impulse. Low energy direct strokes Fit arresters to phases for which Shielding angle arising from shielding shielding failure is expected failure also occurring on unshielded lines Backflashover – low Fix arresters on exposed structures on Low energy rating energy injected into the those phases most likely to suffer adequate because most

36 phase conductor from the structure Induced surges greater than line insulation

back flashover

energy is discharged into the shield wire earthing Low energy rating adequate because discharge is shared by many arresters and structures

Install arresterson all phases on all structures exposed to high induced surges

3.14 Comparison of Available Surge Arresters (Gapless Type)

There are number of high voltage surge arrester manufactured by several company which can be discussed here as mean of reference in designing the transmission line arrester. Below is the data for SLA which is PROTECTA*LITE by Ohio Brass, PEXLIM R120-YH145H by ABB and SLA.2.120.030 by Sediver

Table 3.9: Data on Gapless Transmission line arrester manufactured by several company PROTECTA*LITE Manufacturer Rated Voltage (kV) Uc (kV) MCOV (kV) Nominal discharge current (kA) Line discharge class Energy capability (kJ/KVur) Insulation material Creepage distance (mm) Weight (kg) Length (mm)

98 10

PEXLIM R120YH145H ABB 120 92 98 10

96 10

2

2

2

5.1

5.2

5

ESP 4,694

Silicon 3,726

Silicon 3,736

18 2,140

25 1,216

32 1,470

Ohio Brass 120

SLA.2.120.030 Sediver 120

37

CHAPTER 4

METHODOLOGY

4.1

System Modelling

The main emphasis is to identify the models of power system components to be used in the lightning studies. For each component, the important model parameters will be described and typical values will be provided.

38 4.2

EMTP Simulation

EMTP is a computer simulation program specially designed to study a transient pheno mena in the power system It contains a large variety of detailed power equipment models or builds in setups that simplify the tedious work of creating a system representation. Generally, this simulation software can be used in design of an electrical system or in detecting or predicting an operating problem of a power system. ATP-EMTP is used in this simulation process of observing the electrical response of the transmission system. To represent the electrical response of the transmission system, electrical model of the transmission system apparatus have to be selected and validated to gain high accuracy result.

4.3

Selected model and Validation

Models are circuit or mathematical or electrical representation of a physical apparatus so that its characteristic by the means of an output when applied with certain input. In EMTP simulation, the input and output that are usually observed are current, voltage, power and energy. A complete set of representation of a transmission system are combination of every model of the transmission line apparatus itself.

4.4

Transmission Line

39 The line which is Quadruple circuit 2 x 275kV and 2 x 132kV from Balakong to Bandar Tun Razak was commissioned in January 1995. The 12.07 km long line span across the urban areas of Balakong, Seri kembangan and Serdang with a number of spans cut across plantation, jungle and hills. The line comprises of 37nos. of 2423 series towers with steel cross-arms. The detail of the overhead transmission line system as below:

Table 4.1: Balakong to Serdang 132kV line information Line length (km)

12.07

Number of Tower

37 (No. T49A – No. T85A) Suspension: 11

Tower

2423 series

Cross arms

Steel

Span Length (m)

Min; 173

Max: 530

Avg: 335

TFR (Ohm)

Min: 1.1

Max: 11.0

Avg: 3.7

Altitude from sea level(m)

Min: 37

Max: 142

Avg: 77

Terrain

4.5

Tension: 16

16 towers on flat land and 21 towers on hills

Line exposure to lightning

How often an overhead transmission line is likely to be struck by lightning must be known to assess its lightning performance. For this purpose, the first step is to characterize the lightning activity in the region crossed by the line. Number of lightning activity can be calculated as :

N

g

= 0 . 04 T D

1 . 25

40

N

=

s

N

g

10

(4 h

1 . 09

+ b

)

Ng

=

Number of flashes to ground per square kilometer per year

h

=

Average height of the line

b

=

Width of the line

Ns

=

Total hit to line

The Lightning performance of an overhead line depends on the ground flash density of the region and on the incidence of lightning strikes to a line.

Lightning

Transition

Transition OHLine 1000 MVA

PMU Bdr Tun

PMU Balakong

Razak S/S Switching

Switching

Underground Cable 1000 MVA

Underground Cable 1000 MVA

Fig. 4.1: Model of Transimission Line

4.6

Shielding Failure

41 The phase conductor exposure to lightning is evaluated using an electrogeometric model. Line span is divided into short sections (10m to 15m), in order to accept lightning stroke to the ground wires or to the phase conductors along the span.By using IEEE 1992, the following striking distances are used : The striking distance to a conductor : rc = 1.256 rg The striking distance to earth : rg = 9Im 0.65 The striking distance to top tower : rt = 1.05 rc Im(kA) = 70kA (Lightning Stroke Current)

4.7

Overhead Transmission Lines

The overhead lines are represented by multi-phase models considering the distributed nature of the line parameters due to the range of frequencies involved Phase conductors and shield wires are explicitly modeled between towers and only a few spans are considered. The line parameters can be determined by a line constants, using the tower structure geometry and conductor data as input.

4.8

Line length and Termination

42

Since peak voltage at the struck tower is influnced by reflections from the adjacent tower sufficient number of adjacent towers at both sides of the struck tower should be modeled to determine the overvoltages accurately. Number of line span need to modeled in such that the travel time between the struck tower and the fartest tower is more than one-half of the lightning surge front time. Fig 2, shows the model of transimmision line and tower used for lightning studies

Phase Conductors and Shield Wires

Insulators

Towers

Fig. 4.2: Overhead Transmission Line, Tower and Insulator model

4.9

Tower Model

Transmission line tower model used in all simulation is represented as in Fig 3. Section of the top tower (between tower top ad top cross arm and between cross arm) are modeled as inductance branches which is determined according to section length, tower surge impedance and the propagation velocity.

43

Section of the tower from the bottom cross arm to a ground is represented by the surge impedance Zt and the propagation length Iprop as in Fig 4 . Wave propagation speed on the tower was taken to be equal to the velocity of light. Detail parameters as shown in Fig.4 This tower model is based on the work of M.Ishii, which is recognized as a detail tower model widely used in Japan for EMTP simulation purpose. This tower model does not consider the tower wrm, which is available with new tower model develop by other author. There is six-tower model parameter, which is important in selecting its parameter ♦ Zt = Tower Surge Impedance ♦ VL = Surge Propagation Velocity ♦

γ = Attenuation coefficient



α

= Damping coefficient

♦ R

= Damping resistance

♦ L

= Damping Inductance

44

275 kV circuit U50% = 1120 kV

Parallel ResistanceInductance branch

132 kV circuit U50% = 880 kV

Propagation element Zt, Iprop

Fig 4.3: Tower Representation for Quadruple Circuit Transmission Line

Fig 4.4: M. Ishii’s tower model for a double circuit line tower

45 This double circuit tower model could be extended into quadruple circuit tower model with little modification. To produce high accuracy result, current impulse test should be conducted to the quadruple tower to validate its voltage and current response so that the selected parameter of Zt, R and L could be modified to increase the accuracy of the simulation. Formula used for double circuit tower could be modified to be used as quadruple tower model as follows: H

= h1 + h2 + h3 + h4 + h5 + h6 + h7

Ri =

-2Zt1 x ln√γ

x h1

h1 + h2 + h3 + h4 + h5 + h6 R7 = -2Zt2 x ln√γ Li

= α x Ri x 2H Vt

4.10

Tower footing resistance model

Steel towers are represented as a single conductor distributed parameter line terminated by resistance representing the tower footing impedance. By using a soil ionization model, the tower footing impulse resistance is described by the following equations : Rt =

Ro √(1 + I/Ig)

Ig =

ρEg 2π Rlc ²

46 where: Ro - Tower footing resistance at low current and low frequency, (ohm) (Ro = 10 – 40 ohm) Rt - Tower footing resistance, (ohm) Ig

- The limiting current to initiate sufficient soil ionization,(A)

I

- The lightning current through the footing impedance, (kA) - Soil resistivity ( 100 ohm-m)

Eg - soil ionization critical electric field (kV/m), (Eg = 400 kV/m) Rlc - tower low current resistance

The tower footing low current resistance was varied between 10 – 40 ohm and the ratio between the soil resitivity and the tower low current resistence was kept constant at 50 and typical tower grounding resistance is between 10 – 100 ohms. 4.11

Insulators

The insulators are represented by voltage-dependent flashover switches in parallel with capacitors connected between the respective phases and the tower. Refer to Fig.4.2 Typical capacitance = 80pF/unit

4.12

Back flashover

47 The back flashover of the insulators can be represented by volt-time curves. CIGRE suggested that the leader propagation model is used to represent line insulation flashovers and can be calculated using the equation as below :

V1 = 170d

u(t)

- Eo

e0.0015(u(t)/d)

d – l1 Where : V1

=

Leader velocity, m/s

d

=

Gap distance, m

l1

=

Leader length, m

u(t)

=

Applied Voltage, kV

Eo

=

520 ( kV/m )

Critical flashover voltage ( U50%) of 275 kV circuits was 1120kV and value for 132kV was 880kV.

4.13

Corona

The influence of the corona is modeled by the capacitance branches, which are connected between conductors and ground. Although corona effects may reduce the peak of lightning related over voltages by 5 – 20%, in this study corona is neglected in order to be on the pessimistic side and take the worst condition of the lightning struck. From the evaluation procedures implemented in PLASH and DESCARGA, the corona effect does not significantly affect the computation result

48

4.14

Line surge arrester

For representing the non-linear characteristic of ZnO surge arrester, Pinceti’s model has been planned to be used in simulation. Pinceti’s model was introduced in year 1999 and are the easiest model to be used. The model is from the IEEE working group with some minor difference. The model can be realized directly rom performance data rom residual voltage with various current impulses supplied by the manufacturer

The inductance value can be obtained directly from residual voltage in kV of ½, ¼ or 1/20 us impulse and 8/20 us impulse of the same current impulse. The formula used to obtained the inductances is as below. All value obtained are in Uh

L0 =

1 (V 1 / 20 − V 8 / 20) (Ur) V 8 / 20 12

L1 =

1 (V 1 / 20 − V 8 / 20) (Ur) V 8 / 20 4

For the non-linear element A0 and A1, the value can be obtained from 8/20 us impulse data as supplied by the manufacturer. The table bellows shows the value of A0 and A1 based on the recommendation from the author

49 Table 4.2: Value for A0 and A1 based on 8/20 us residual voltage supplied by

manufacturer for the application of Pinceti’s arrester model. I [kA]

A0[p.u]

A0[V]

A1[p.u]

A1[V]

2x10-6

0.810

-

0.623

-

0.1

0.974

-

0.788

-

1

1.052

109829

0.866

90410

2.5

1.096

121875

0.910

101192

3

1.108

-

0.922

-

5

1.147

134199

0.961

124437

10

1.195

153797

1.009

129858

20

1.277

-

1.091

-

Fig. 4.5: Pinceti’s arrester model used for representing surge arrester

Polymer housed line surge arrester with gapless type is choosen to be used for the lightning performance improvement. The example of SLA installation as in Fig 6.

50

14.00 5 kA 1/10 us 1 kA 8/20 us 2.5 kA 8/20 us 5 kA 8/20 us 10 kA 8/20 us 100 A 30/60 us 250 A 30/60 us 500 A 30/60 us 1 kA 30/60 us

12.00

Relative Error [%]

10.00 8.00 6.00 4.00 2.00 0.00 1

-2.00 -4.00 -6.00

Figure 4.6: Relative error of residual voltage for representing Siemens 120kV rated

3EQ4-2/LD3 SA with Picenti’s model compared to manufacturer performance data

The selection of gapless type compare to gapped type is as per appendix 1. Both types have advantages and disadvantages owing primarily to the fact that the gapless type is connected directly to the system (and continuously exposed to the system voltage and to any over voltages that may appear on the system) while gapped type is only “connected” directly to the system temporarily during the gap (spark over) operation. Proposed Surge arrester (manufactured by ABB) has the following characteristics: Rated Voltage

120 kV

Uc(kV)

92kV

MCOV(kV)

96kV

Nominal discharge current

10kA

IEC Line discharge class

2

Energy capability(kJ/KVur) 5.2 (kJ/kVmcov) Insulation Material

Silicon

Critical Flashover voltage

620 kV

Creepage distance(mm)

3,736mm

Weight(kg)

25kg

Length(mm)

1,216mm

51

Fig 4.7: Example of Gapless-type Surge Arrester installed at 132kV BLKG-SRDG

The arresters can be modeled as nonlinear resistors with 8 x 20us maximum voltage-current characteristics. SiC surge arresters will be installed at 132kV circuits only because the lower voltage (132kV) circuits of the quadruple line have lower line insulation critical flashover voltages, which means that the majority of the backflashover will happen on the 132kV circuits

4.15

Selection of Lightning Configuration

Several arrester installation configuration will be studied with maximum number of the arrester to be used is less or equal to three. The example installation configuration are as Fig 7.

52

1) 1-3 arrangement

3) L-arrangement

2) Double bottom

4) I - arrangement

Fig 4.8: Different arrester Installation Configurations

- With `Line Surge Arrester Installed -

Without Line Surge Arrester Installed

CHAPTER 5

AVAILABLE METHOD FOR LIGHTNING PERFORMANCE IMPOVEMENT

53

There are several methods available for improving the lightning performance of a transmission line in services. This method can be applied for improving the lightning performance of a transmission line already in services.

Additional Shiels Increasing

Under built Ground

Line Surge

Foot resistance

Fig. 5.1: Available Method for Lightning Improvement 5.1 Additional Shielding Wire

Shield wire could be added or modified to a tower design. The shielding angle could be decrease or in the case of quadruple circuit, additional of an under running and over running ground wire to the 132kV circuit could be done. Improvement in the performance of the 132kV circuit are expected due to coupling of the lower phases and upper phases with over running ground wire are comparable with the normal double circuit line. However, this solution would translate into high cost especially if the provisions are not in the original tower design. It would eliminate a large number of interruptions but not enough to obtain a new demanded degree reliability.

54

5.2 Tower Footing Resistance

Resistance value for transmission line with high Footing Resistance can be improved by method of counterpoise that could lead to improve the performance of the line. However this method is often difficult and expensive especially in hilly terrain. In the case of quadruple circuit line with good grounding and low lightning performance, this method ie useless because the low performance of the lower portion of the quadruple circuit line are caused low coupling with the ground wire, lower insulation and sacrificial nature of lower circuit due to the tower height.

5.3 Increase the Tower Insulation

This method can be used to increase the lightning performance of the line but also would require a large modification of the clearance and mechanical strength of the tower structure, which would lead to high cost. The insulation of the station equipment would also have to be increased to cope up with the modification, which is not a very good choice for a line in services.

5.4 Unbalance Insulation

55

This method is only applicable to double and quadruple circuit line. Double circuit outages could also be reduced by use of unbalanced insulation, which the basic principle of unbalanced insulation is to install one circuit at a higher insulation level than the other circuit. The decrease in double circuit outage rate depends on the insulation differential and on the tower footing resistance. Unbalanced insulation does not reduce total line outage rate.

Double circuit flashovers and flashovers on the higher insulation circuit are reduced, but with an inceased number of flashovers on the lower insulation circuit which is not a very reliable and good solutions for improving the lightning performance of a line. Rhis method maybe cheap considering the fact that the only thing that should be done is to decrease the arching distance of one circuit and to maintain the next circuit arching distance but this method will affect realibility and quality of power.

5.5 Transmission Line Arrester

Double circuit outages can be eliminated by installation of line surge arresters on all conductors of all circuit, which is uneconomical considering the total amount of money compared to the improvement gain. Lower TLA configuration could result in performance improvement. There are several methods available for optimizing the application of TLA for improving the lightning performance of a transmission line in services.

56

Circuit with lower Insulation level

Circuit with higher Insulation level

Fig 5.2: Unbalance tower insulation for double circuit line 5.6 Installation of TLA based on Tower Footing Resistance(TFR)

This method is used for improving a lightning performance of a double circuit line with high TFR on certain section of a line. This method is based on a strategy of arrester installment as in Figure 5.1. This strategy is based on an assumption that the higher TFR the higher the current have to be diverted by the surge arrester. Table 5.1: Arrester installation strategy to eliminate double circuit flashover

No

TFR(Ω)

TLA location

1

TFR < 10

No TLA

2

10 < TFR < 20

3

3

20 < TFR < 40

2&3

4

40 < TFR

1,2 and 3

57

1

2 3

1 2

3

Fig. 5.3: Circuit location and TLA placement for a double circuit line

Base on the strategy as in Table 5.1, an improvement of a lightning performance can be conducted based in this procedure: ♦ Divide the line into several sections and apply arrester installation configuration related to the section’s tower footing resistance. ♦ Apply same arrester installation configuration throughout the particular line section. ♦ Perform statistical study in determining the arrester energy duties ♦ The most energy sensitive installation is a configuration with arrester installed on all conductors. Lightning current have to be shared by TFR, ground wire and surge arresters.

5.6.1 Additional of TLA at low TFR Section

58

These methods are proposed by ABB for increasing the availability of the line. This procedure specially designs for protecting the line against the abnormal lightning surges (frequent or high amplitude) and reduce the outages caused by such lightning surges. Two steps needed to perform this procedur are: ♦ Place TLA at all tower section with high TFR ♦ Add additional TLA at one tower at both of the low TFR section along the section of high TFR that have been equipped with TLA

4 3

5 6

7

2

1

Fig. 5.4: Additional TLA at Low TFR section along the high TFR section

5.6.2

Installation of TLA on one circuit

Double circuit flashover can be reduced using arrester installation configuration, which are three and more arresters on one circuit installation scheme. An important difference between the application of line surge arresters on one circuit and unbalanced insulation is in the fact that line surge arresters substantially reduce the number of flashovers on the other circuit, hence improving total line lightning performance

59

TLA added only at one circuit

Fig. 5.5: TLA added only at one circuit of a double circuit line tower

5.6.3

Coordination of Gap Spacing fot Transmission Line Arrester with External Gap

The purpose of adding an external gap to the TLA are to protect the TLA from acceleration aging due to leakage current and to protect the TLA from being stressed from switching over voltage that could be in duration of 2 second which could also caused accelerated ageing of TLA. Gap distance of TLA external gap are coordinated based on two main references, the maximum switching over voltage predicted to the

60 system and the lightning impulse withstand voltage of the system insulation with TLA added. This is based on the gap distance that wide enough for not permitting operation of TLA when switching over voltage occurs but low enough to ensure operation of TLA when lightning over voltage occur.

5.7 Extended Station Protection

By locating TLA on towers near a substation, the risk of back flashover near the station is eliminated.

This result in reduction of steepness and amplitude of coming

travelling wave, thus improving the protection performance of station arresters and eliminating the need for additional expensive metal-enclosed arresters even for large GIS.

Usually a gapped TLA with higher rating are applicable to cope with the probability of being stressed by switching over voltage however higher rated compare to the substation surge arrester are advisable so that the TLA are less stressed by the switching over voltage. TLA with external gap are also applicable but the gap distance must be kept as minimum as possible so that the surge can be reduce effectively

61

Substation

Fig. 5.6: Extended station protection

CHAPTER 6

62

SIMULATION METHOD

6.1

ATP-EMTP Simulation

The study is performed with the aid of ATP-EMTP software. This software program is a computer simulation program specially design to study a transient phenomena in the power system. It contains a large variety of detailed power equipment models or builds in setups that simplify the tedious work of creating a system representation.

Generally this simulation software can be used in design of an electrical system or in detecting or predicting an operating problem of a power system. To represent the electrical response of the transmission system, electrical model of transmission system apparatus have to be selected and validated to gain high accuracy result

6.2

Selected Model and Validation

In this simulation, the parameters as input and output and need to be observed are current, voltage, power and energy. The models are circuit or electrical

63 representation of a physical apparatus and the characteristic can be observed through the output when the input applied. A complete set of representation of a transmission system are combination of every model of the transmission line apparatus itself

6.2.1

Tower Model

M.Ishii multi-storey tower model is selected as tower model for EMTP simulation purpose. This tower model does not consider the tower arm, which is available in other model. The parameters need to be modeled using M.Ishii model are : Zt = Tower Surge Impedance VL = Surge Propagation Velocity R = Damping Resistance L = Damping Inductance Hi = Height of Tower

Where: H = h1 + h2 + h3 + h4 + h5 + h6 + h7 The value of surge impedance for each level of the tower can be based on IEEE and CIGRE formula for inverted cone Z = 60 x Loge cos{0.5x tan (R/H)}

64 If R
View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF