MiCO Mi COM M P1 P139 39 Time Overcurrent P&C Unit
MiCOM P139 Time Overcurrent Protection and Control Unit
T&D Protection & Control
MiCO MiCOM M P13 P139 Time Overcurrent Protection and Control Unit Application and scope The MiCOM P139 is a cost effective one box solution for integrated numerical distance protection and control. The protection functions provide selective short-circuit protection, ground fault protection (UK: earth fault) and overload protection in medium, high and extra high voltage systems. The systems can be operated as solidly grounded, low impedance grounded (UK: solidly earthed/resistance earthed), resonant grounded (UK: Petersen Coil) or insulated neutral systems. The multitude of protection functions incorporated into the device enable the user to cover a wide range of applications in the protection of cable and line sections, transformers and motors. The control functions are designed for the control of up to six electrically operated switchgear units equipped with electrical check back signalling located in the bay of a medium voltage substation or a non-complex high voltage station. External auxiliary devices are largely obviated through the integration of binary inputs and power outputs that are independent of auxiliary voltages, by the direct connection option for current and voltage transformers and by the comprehensive interlocking capability. This simplifies handling of the protection and control technology for a switchbay from planning to commissioning.
During operation, the user friendly interface facilitates setting of the device and promotes safe operation of the substation by preventing nonpermissible switching operations. The P139 has the following main functions:
Control functions • Control and monitoring of up to 6 switchgear units • Selection from over 200 predefined bay types or download of customised bay type • Thermal overload protection (with true rms value measurement)
• Bay interlock • Local control and LCD display with a selection between the diagrams and lists of the bay panel, measured value panel and signal panel.
Protection functions • Four pole measurement (A, B, C, N) • Definite time overcurrent protection, 3 stages, phase selective • Inverse time overcurrent protection, 1 stage, phase selective • Short circuit direction determination • Protective signalling • Autoreclosing control • Over/underfrequency protection • Directional power protection • Motor protection (with true rms value measurement)
2
• Unbalance protection • Over/undervoltage protection • Switch-on-to-fault protection • Circuit breaker failure protection • Ground fault direction determination using steady state values • Transient ground fault direction determination (optional) • Measuring circuit monitoring • Limit value monitoring • Programmable scheme logic. All main functions are individually configurable and can be disabled or enabled by the user as desired. By means of a straight forward configuration procedure, the user can adapt the device flexibly to the scope of protection required in each particular application. Due to the powerful, freely configurable logic of the device, special applications can be accommodated.
In addition to the features listed above, as well as comprehensive self monitoring, the following global functions are available in the P139:
The maximum configuration of binary inputs and outputs provide the signalling of 10 switchgears whereas 6 of them are controllable.
• Parameter subset selection (4 alternative setting groups)
The nominal voltage range of the optical coupler inputs is 24 to 250V dc without internal switching.
• Operating data recording (time tagged signal logging) • Overload data acquisition • Overload recording (time tagged signal logging) • Ground fault data acquisition • Ground fault recording (time tagged signal logging) • Measured fault data
The auxiliary voltage input for the power supply is a wide range design with a nominal voltage range of 48 to 250V dc and 100 to 230V ac. An additional version is available for the lower nominal voltage range of 24V dc. All output relays are suitable for both signals and trip duties.
• Fault recording (time tagged signal logging together with disturbance recording of the three phase currents, residual current, three phase-ground voltages and the neutral displacement voltage).
Control and display
The P139 is of modular design. The pluggable modules are housed in a robust aluminium case and electrically connected via an analogue and a digital bus printed circuit board.
• Communication interface (optional).
The P139 has the following inputs and outputs: • 4 current measuring inputs • 4 voltage measuring inputs • 8 or 14 additional output relays with freely configurable function assignment for individual control or protection applications
• Local control panel • 17 LED indicators, 12 of which allow freely configurable function assignment • PC interface
Information exchange is via the local control panel, PC interface and the optional communication interface. The communication interface conforms alternatively to IEC 60870-5-103, IEC 60870-5101, DNP3.0 or MODBUS. Using this information interface, the P139 can be integrated into a substation control system.
Main functions Main functions are autonomous function groups and can be individually configured or disabled to suit a particular application. Function groups that are not required and have been disabled by the user are masked completely (except for the configuration parameter) and functional support is withdrawn from such groups. This concept permits an extensive scope of functions and universal application of the device in a single design version, while at the same time providing for a clear and straight forward setting procedure and adaptation to the protection and control task under consideration. Control functions For the acquisition of switchgear positions, the P139 uses up to 20 binary inputs for the signalling of up to ten two-pole switching positions and up to twelve binary outputs for controlling of up to six switchgear. The acquisition of further binary inputs is in the form of single-pole operating signals; they are processed in accordance with their significance for the substation (circuit breaker readiness, for example). For each switchgear input and each free input a separate debounce and chatter time may be set. For the acquisition of a binary count, a binary input may be configured. In the event of loss of operating voltage, the count is stored. Upon the following start-up of the unit, counting is continued with the stored value as initial value.
• 6 binary signal inputs (optical couplers) and 6 output relays for the control for 3 switching devices or • 12 binary signal inputs (optical couplers) and 12 output relays for the control of 6 switching devices
The P139 issues switching command outputs with the integration of switching readiness and permissibility tests; subsequently the P139 monitors the intermediate position times of the switchgear units. If a switchgear malfunction is detected, this fact will be indicated (eg. By an appropiately configured LED indicator).
• 4, 8 or 28 additional binary signal inputs (optical couplers) with freely configurable function assignment for individual control or protection signals
3
Before a switching command output is executed, the interlocking logic of the P139 will check whether the new switchgear unit state corresponds to a permissible bay or substation topology. The interlock logic is set out for each bay in the default setting as bay interlock with and without station interlock. By means of a straight forward parameter setting procedure, the interlocking equations can be adapted to the prevailing bay and substation topology. The presentation and functioning of the interlocking system correspond to those of the programmable logic. For integration of the P139 into an integrated control system, the equations for the bay interlock with station interlock form the basis of interlock checking. Without integration into the substation control system, the bay interlock without station interlock is used in interlock checking; external ring feeders may be included in the interlocking logic. If the bay or station topology (as applicable) is permissible then the switching command is issued. If a nonpermissible state would result from the switching operation then the switching command is rejected and a signal to this effect is issued. If the bay type does not require all binary outputs then the remaining outputs are available for free configuration. In addition to the switching command output, a triggering of binary outputs by continuous commands is possible.
Tripping time characteristics No. Tripping time characteristic (k = 0.01 to 10.00) 0
Definite time
1 2 2 4
Per IEC 60255-3 Normally inverse Very inverse Extremely inverse Long time inverse
5 6 7
Per ANSI/IEEE C37.112 Moderately inverse Very inverse Extremely inverse
a
Constants and formulae (t in s) b c R
0.14 13.5 80 120
0.02 1.00 2.00 1.00
Trip 0.0515 19.6100 28.2000
Per ANSI 8 Normally inverse 9 Short time inverse 10 Long time inverse
Trip 8.9341 0.2663 5.6143 t
= k
a I I ref
Not per standard 11 RI type inverse
t
= k
t
= k
t
= k
a b –1
I I ref
Release 4.85 21.60 29.10
0.0200 2.0000 2.0000
0.1140 0.4910 0.1217
2.0938 1.2969 1.0000
Release 0.17966 9.00 0.03393 0.50 2.18592 15.75
+c b –1
t r
= k
R I I ref
2
–1
1
0.339 –
0.236 I I ref
Not per standard 11 RXIDG type inverse
Definite time overcurrent protection The definite time overcurrent protection (DTOC) operates on the basis of a four-pole measurement (A,B,C,N) with separate evaluation of the three phase currents and the residual current. Three stages each are provided for the two measuring systems. Each of the stages operates with phase selective starting. The timer stages measuring in the residual path affect the general starting signal. This effect can be suppressed if desired. Starting of the phase current stage I> can be stabilised under inrush conditions if desired. The ratio of the second harmonic component of the phase currents to the fundamental wave serves as the criterion. This stabilisation is either phase selective or effective across
4
t
= k 5.8 – 1.35 ln
I I ref
all three phases depending on the chosen setting. The phase current stages I>> and I>>> are never affected by this stabilisation procedure. Intermittent startings of the residual current stage IN> can be accumulated over time by means of a settable hold time. If the accumulated starting times reach the trip limit value (which is also adjustable by setting) then a trip with selective signaling ensues. Additionally, the operate values of all overcurrent stages can be set as dynamic parameters. For a settable hold time, switching to the dynamic operate values can be done via an external signal. Once the hold time has elapsed, the static operate values are reinstated.
Inverse time overcurrent protection The inverse time overcurrent protection operates on the basis of a four-pole measurement (A,B,C,N) just as the DTOC protection does. Additionally, however, the negative sequence current is determined from the filtered fundamental wave of the three phase currents. The three phase currents, the negative sequence and residual current are evaluated in separate, single stage measuring systems. The effect on the general starting signal of the stages measuring in the residual path and in the negative sequence system, respectively, can be suppressed if desired. For the individual measuring systems, the user can select from a multitude of tripping characteristics (see the table below). Starting of the phase current stage and the negative sequence current stage can be stabilised under inrush conditions if desired. The ratio of the second harmonic component of the phase currents to the fundamental wave serves as the criterion. This stabilisation is either phase selective or effective across all three phases depending on the chosen setting. The negative sequence current stage is subject to all phase current stabilisations. Intermittent startings of the phase, negative sequence or residual current stage can be accumulated
on the basis of the set tripping characteristic by means of a settable hold time. Tripping is also performed in accordance with the relevant tripping characteristic. Additionally, the operate values of all overcurrent stages can be set as dynamic parameters. For a settable hold time, switching to the dynamic operate values can be done via an external signal. Once the hold time has elapsed, the static operate values are reinstated. Short circuit direction determination Due to the short circuit direction determination function, the P139 can be used as a directional time overcurrent protection device. For each overcurrent timer stage the user may select whether the stage shall be forward directional, backward directional or nondirectional. Direction determination is performed in separate measuring systems for the phase current and residual current timer stages, respectively. In the direction-measuring system for the phase current timer stages, the phase-to-phase voltage opposite to the selected phase current is used for direction determination as a function of the type of fault, and an optimum characteristic angle is employed (as shown in the table below).
In the direction measuring system for the residual current timer stages, direction is determined using the internally computed neutral displacement voltage; the characteristic angle is adjustable taking account of the various neutral point treatments in the system. The direction measuring system for the residual current timer stages is not enabled until a set value for neutral displacement voltage is exceeded. The user may select whether the triggering preorientation for a non-enabled direction measuring system for residual current timer stages shall be blocked in the event of phase current starting. Protective signaling Protective signaling can be used in conjunction with short circuit direction determination. For this purpose the protection devices must be suitably connected by pilot wires on both ends of the line section to be protected. The user may select whether teleprotection will be controlled by the direction measuring system of the phase current timer stages only, by the direction measuring system of the residual current timer stages only, or by the direction measuring systems of the phase current and residual current timer stages. For protection devices on the infeed side of radial networks, teleprotection can also be controlled without the short-circuit direction determination function.
Directional characteristics in short circuit direction determiniation
Meas. system P
G
Starting
Variables selected for measurement
Characteristic Forward decision Angle αP or αN
Imeas
Vmeas
A
IA IB
C
IC
VBN - VCN VCN - VAN VAN - VBN
+45º
B
VBC = VCA = VAB =
A-B
IA
VCB = VAB =
VBN - VCN VAN - VBN
+60º
B-C
IC
C-A
IC
A-B-C
IC
GF
IN
Imeas
+45º +45º +30º
VAB = VAB =
VAN - VBN +60º VAN - VBN +45º VNG = -1/3 . (VAN + VBN + VCN) +80º to +90º
5
Vmeas
(reference variable)
Backward decision
Figure 1: Overload memory and startup counter
Overload memory 100 min % 80 60 40
20 0
t Permissible number of startups
Reclosure blocking
• Separate cooling periods for rotating and stopped motors
3 2 1 t
3 successive startups
• Inclusion of heat dispersion processes in the rotor after several startups
• Startup repetition monitoring with reclosure blocking (see Figure 1) • Control logic for heavy starting and protection of locked rotor
Auto reclosure control The auto reclosing control (ARC) operates in three phase mode. ARC cycles with a high-speed reclosure (HSR) and multiple (up to nine) subsequent time delay reclosures (TDR) are possible. Reclosuring cycles without prior HSR is possible. For special applications, tripping prior to an HSR or TDR can be delayed. HSR and TDR reclosures are counted and signaled separately. A test HSR can be triggered via any of the unit’s interfaces. Over/underfrequency protection Over/underfrequency protection has four stages. Each of these can be operated in one of the following modes: • Over/underfrequency monitoring • Over/underfrequency monitoring combined with differential frequency gradient monitoring (df/dt) for system decoupling applications
• Over/underfrequency monitoring combined with medium frequency gradient monitoring • (∆f/∆t) for load shedding applications Directional power protection The directional power protection monitors exceeding the active and reactive power limt, a power drop and the reversal of direction at unsymmetrically operated lines. Evaluation of the power is performed using the fundamental wave of the phase voltages and of the neutral displacement voltage. Motor protection For the protection of directly switched h.v. induction motors with thermally critical rotor, the following specially matched protection functions are provided: • Recognition of operating mode • Rotor overload protection using a thermal motor replica • Choice of reciprocally quadratic or logarithmic tripping characteristic
6
Thermal overload protection Using this function, thermal overload protection for lines, transformers and stator windings of HV motors can be realised. The highest of the three phase currents serves to track a first order thermal replica according to IEC 60255-8. The tripping time is determined by the set thermal time constant τ of the protected object and the set tripping level Θtrip depending on the accumulated thermal load Θp: I 2
t = τ.ln
I B I 2 I B
– Θp – Θtrip
A warning signal can be issued in accordance with the set warning level Θwarning.
Unbalance protection
Switch-on-to-fault protection
The negative sequence current is determined from the filtered fundamental wave of the three phase currents. The evaluation of the negative sequence current is performed in two time overcurrent stages with definite time delay.
Closing of a circuit breaker might inadvertently lead to a short circuit fault due to a maintenance ground clamp not yet removed, for example.
Over/undervoltage protection The over/undervoltage time protection function evaluates the fundamental wave of the phase voltages and neutral displacement voltage, as well as the positive sequence voltage and negative sequence voltage obtained from the fundamental wave of the three phase-ground voltages. Two definite time delay overvoltage stages each are provided for evaluation of the neutral displacement voltage and negative sequence voltage. Two additional definite time delay undervoltage stages each are provided for evaluation of the phase voltages and positive sequence voltage. Phase voltage evaluation can be performed using either the phase-phase voltages or the phase-ground voltages as desired. For evaluating the neutral displacement voltage, the user may choose between the neutral displacement voltage formed internally from the three phase-ground voltages and the neutral displacement voltage formed externally (from the open delta winding of the voltage transformer, for example) via the fourth voltage measuring input.
The function ‘switch-on-to-fault protection’ provides for an undelayed protective tripping during a settable time after a manual close command has been issued. Depending on the operating mode, a trip command with initialisation of the fault detection logic results. Circuit breaker failure protection With the trip command, a timer stage is started for the monitoring of the circuit breaker action. If the timer elapses due to the persistence of the general starting, a ‘circuit breaker failure’ signal is issued. This serves to issue a second trip command (retrip) or, according to the users choice, to trip neighbouring protection device (upstream breaker). The input of a ‘circuit breaker failure’ signal via an appropriately configured binary input while the general starting persists, effects an undelayed trip command. Ground fault direction determination using steady state values The ground fault direction is determined by evaluating the neutral displacement voltage (eg. from the open delta winding of the voltage transformer) and the residual current (eg. from a core balance or window type current transformer). The directional characteristic can be set to suit the method of system grounding (cos ϕ measured for Petersen Coil and sin ϕ circuit for insulated neutral).
7
In the cos ϕ circuit, the adjustable sector angle also has an effect so that faulty direction decisions (resulting, for instance, from the phase angle error of the current and voltage transformers) can be suppressed effectively. Operate sensitivity and sector angle can be set separately for the forward and backward direction, respectively. Alternatively, an evaluation based on current only can be performed. In this case, only the magnitude of the filtered residual current is used as ground fault criterion. Both procedures operate with either the filtered fundamental or the fifth harmonic component in accordance with the chosen setting. Transient ground fault direction determination (optional) The ground fault direction is determined by evaluating the neutral displacement voltage, calculated from the three phaseground voltages and the neutral current on the basis of the transient ground fault measuring procedure. The direction decision is latched. The user may select either manual or automatic resetting after a set time delay. Measured data output The protection device provides the options of operating data output and fault data output. The user can select an output in BCD-coded form through relay contacts or an output in analogue form as load independent current (0 to 20 mA). For an output in BCD-coded form, an appropriate number of free output relays need to be available. For the current output, a special analogue I/O module is required.
Measuring circuit monitoring
Programmable logic
Clock synchronisation
Measuring circuit monitoring includes the monitoring of the phase currents and phase-phase voltages.
User configurable logic enables the user to set-up logic operations on binary signals within a framework of Boolean equations. By means of a straightforward configuration procedure, any of the protection device signals can be linked by logic ‘OR’ or ‘AND’ operations with the possibility of additional negation operations.
The devices incorporate an internal clock with a resolution of 1ms.
Phase current monitoring is based on the principle of maximum allowable magnitude unbalance, whereby the arithmetic difference between the maximum and minimum phase currents, as referred to the maximum phase current, is compared to the set operate value. Even with an economy type CT connection (CTs in only two phases) it is possible to monitor the phase currents given appropriate settings. Phase-phase voltage monitoring is based on a plausibility check involving the phase currents. If a low current threshold setting is exceeded by at least one phase current, the three phase-phase voltages are monitored for a set minimum level. In addition to magnitude monitoring, phase sequence monitoring of the phasephase voltages may be activated. Limit monitoring A multitude of currents, voltages and the measured temperature are monitored to aid operation of the protected line. This function is not intended to be used for protection purposes, as it has an inherent one second delay. For example, for the 3-phase currents, the phase-ground voltages and the phase-phase voltages the highest and lowest value is determined. These are evaluated using an operate value and time delay set by the user. Thereby, these currents and voltages can be monitored for exceeding an upper limit or falling below a lower limit.
The output signal of an equation can be fed into a further, higher order equation as an input signal, thus leading to a set of interlinked Boolean equations. The output signal of each equation is fed to a separate timer stage with two timer elements each and a choice of operating modes. Thus the output signal of each equation can be assigned a freely configurable time characteristic. The two output signals of each equation can be configured to each available input signal after logic OR linking. The user configurable logic function is then able to influence the individual functions without external wiring (block, reset, trigger, for example). Via non-storable continuous signals, monostable trigger signals and bistable stored setting/resetting signals, the Boolean equations can be controlled externally via any of the device’s interfaces.
Global functions Functions operating globally allow the adaptation of the device’s interfaces to the protected power system, offer support during commissioning and testing, providing continuously updated information on the operation, as well as valuable analysis results following events in the protected system.
8
All events are time tagged based on this clock, entered in the recording memory appropriate to their significance and signalled via the communication interface. Alternatively, two external synchronisation signals can be used according to the selected communication protocol: using one of the protocols MODBUS, DNP3.0, IEC 60870-5-103 or IEC 60870-5-101 the device will be synchronised by a time telegram from a higher level substation control system or in any other case, it will be synchronised using the IRIG-B signal input. The internal clock will then be adjusted accordingly and operate with an accuracy of ±10ms if synchronised via protocol and ±1ms if synchronised via IRIG-B signal. Parameter subset selection The function parameters for setting the protection functions are, to a large extent, stored in four independent parameter subsets. Switching between these alternative setting groups is readily achieved via any of the device´s interfaces. Operating data recording For the continuous recording of processes in system operation or of events, non-volatile ring memory entries are provided. The relevant signals, each fully tagged with date and time at signal start and signal end, are entered in chronological sequence. Included are control actions such as enabling or disabling of functions as well as local control triggering for testing and resetting. The onset and end of events in the network, as far as these represent a deviation from normal operation (overload, ground fault or short circuit, for example) are recorded.
Overload data acquisition
Ground fault recording
Fault recording
Overload situations in the network represent a deviation from normal system operation and can be permitted for a brief period only. The overload protection functions enabled in the protection and control units recognise overload situations in the system and provide for acquisition of overload data such as the magnitude of the overload current, the relative heating during the overload situation and its duration.
While a ground fault condition persists in the power system, the relevant signals, each fully tagged with date and time at signal start and signal end, are entered into a non-volatile memory in chronological sequence.
Fault recording comprises event and disturbance recording along with the stored fault measurands. While a fault condition persists in the power system, the relevant signals, each fully tagged with date and time at signal start and signal end, are entered into a non-volatile memory in chronological sequence.
Overload recording While an overload condition persists in the network, the relevant signals, each fully tagged with date and time at signal start and signal end, are entered into a non-volatile memory in chronological sequence. The measured overload data, fully tagged with the date and time of acquisition, are also entered. Up to eight overload situations can be recorded. If more than eight overload situations occur without interim memory clearance then the oldest overload recording is overwritten. Ground fault data acquisition While a ground fault in a network with isolated neutral or resonant grounding represents a system fault, it is usually nevertheless possible, in the first instance, to continue system operation without restrictions. The ground fault determination functions enabled in the protection device recognise ground faults in the system and provide for the acquisition of the associated ground fault data such as, the magnitude of the neutral displacement voltage and the ground fault duration.
The measured ground fault data, fully tagged with the date and time of acquisition, are also entered. Up to eight ground faults can be recorded. If more than eight ground faults occur without interim memory clearance then the oldest ground fault recording is overwritten. Fault data acquisition A short circuit within the network is described as a fault. The short circuit protection functions enabled in the devices recognise short circuits within the system and trigger acquisition of the associated measured fault data such as, the magnitude of the short circuit current and the fault duration. As acquisition time, either the end of the fault or the start of the trip command can be specified by the user. Triggering via an external signal is also possible. The acquisition of the measured fault data is performed in the measuring loop selected by the protective device and provides impedances and reactances as well as current, voltage and angle values. The fault distance is determined from the measured short circuit reactance and is read out with reference to the set 100% value of the protected line section. The fault location is output either with each general starting or only with a general starting accompanied by a trip (according to the user’s choice).
9
The measured fault data, fully tagged with the date and time of acquisition, are also entered. Furthermore, the sampled values of all analogue input variables such as phase currents, neutral current, phase-ground voltages and neutral displacement voltage are recorded during a fault. Up to eight faults can be recorded. If more than eight faults occur without interim memory clearance then the oldest fault recording is overwritten. Self monitoring Comprehensive self monitoring procedures within the devices ensure that internal hardware or software errors are detected and do not cause malfunctions of the protective devices. As the auxiliary voltage is turned on, a functional test is carried out. Cyclic self monitoring tests are run during operation. If test results deviate from the default value then the corresponding signal is entered into the non-volatile monitoring signal memory. The result of the fault diagnosis determines whether a blocking of the protection device will occur or whether a warning only is issued.
Control All data required for operation of the protection and control unit are entered from the integrated local control panel. Data important for system management is also read out from here. The following tasks can be handled via the local control panel: • Control of switchgear units • Readout and modification of settings • Readout of cyclically updated measured operating data and state signals
6
1
2 4 3 5 7
• Readout of operating data logs and of monitoring signal logs • Readout of event logs (after overload situations, ground faults or short circuits in the power system) • Resetting of the unit and triggering of further control functions designed to support testing and commissioning tasks The local control panel shown in Figure 2 comprises the local control elements and functions described below. Display (1) The integrated local control panel has an LCD display with 16 x 21 alphanumeric characters (128 x 128 pixels). 17 LED indicators are provided for signal display. (2) 5 LED indicators are permanently assigned to signals. (3) The remaining 12 LED indicators are available for free assignment by the user. A separate adhesive label is provided for user defined labeling of these LED indicators according to the chosen configuration.
8
Figure 2: Local control panel
Menu tree (4) By pressing the cursor keys and guided by the LCD display, the user moves within a plain text menu. All setting parameters and measured variables as well as all local control functions are arranged in this menu which is standardised for all system devices. Changes to the settings can be prepared and confirmed by means of the ENTER key which also serves to trigger local control functions. In the event of erroneous entries, exit from the EDIT MODE with rejection of the entries is possible at any time by means of the CLEAR key . When the EDIT MODE is not activated, pressing the CLEAR key has the effect of resetting the indications. Pressing the READ key provides direct access to a preselected point in the menu. Switchgear control (5) The control of switching devices from the local control panel can only be done via the bay panel. Switchgear units can be controlled from the local control panel provided that the device has been set to ‘local control’.
10
This setting may be selected either via the password protected local/remote key or via an external key switch. Once the intended switching device has been selected with the help of the selection key , the switching device may then be controlled via the close key or open key . Pressing the page key results in leaving the display of the bay or the menu tree and switching to the panel display mode. The panel type being displayed may be switched by pressing the page key consecutively. From the panel display, the user can return to the menu tree display at any time by pressing the enter key. Device identification, ports (6) The upper covering flap is labelled with the device type designation. Located under the flap is the type identification label with information on the order number, serial number and the nominal electrical values.
Password protection Access barriers protect the enter mode in order to guard against inadvertent or unauthorised changing of parameters or triggering of control functions
(7) Located under the lower covering flap is the serial interface for connecting a PC. (8) To prevent unauthorized opening of the lower flap, it can be sealed using the attached eyelets. Display panels With the help of the display panels, the user is able to carry out a quick and up to date check of the state of the bay. The device provides the following display panels:
On the bay panel the selected bay is displayed as a single pole equivalent network (single line diagram) with the updated switchgear states. This panel is always displayed following startup or after a defined period of time after the most recent local control action. Moreover, ancillary information such as the position of the remote/local switch, the operating state of the interlock functions and (optionally) a measured value are displayed as text and bar displays.
Selected measured values are displayed on the measured value panels. The type of measured values shown (such as measured operating data or measured fault values) will depend on the prevailing conditions in the substation. Priority increases from normal operation to operation under overload conditions, operation during a ground fault and finally to operation following a short circuit in the system. The measured value sequence in the measured value panel is user configurable. The signal panel displays the most recent events such as the opening of a witchgear unit. A list presentation of the operating data recording complete with time tagging is displayed.
• Bay panel • Measured value panels (operation panel, overload panel, ground fault panel, fault panel) • Signal panel
Bay Panel P139
Measured Value Panels
17:58:34
Meas. values 17:58:44 Voltage A - B prim. 20.7 kV Voltage B - C prim. 20.6 kV Voltage C - A prim. 20.8 kV Current A prim. 415 A Current B prim. 416 A Current C prim. 417 A
BB1 BB2 Q1
Events
Q2
Q0 Q8
Locked Remote 1088 A Curr. IP, max prim.
Events
17:58:54
20.04.98 05:21:32.331 Enabled Start
ARC
23:58:17.501 Enabled End 21.04.98 00:03:57.677 Enabled Start
ARC
ARC
Control and Display Panels
Device Type
Parameters
Operation
Device ID
Cyclic measurements
Configuration parameters Function parameters
Global Main functions
Control and testing Operating data recordings
Events
Event counters Measured fault data Event recordings
Measured operating data Physical state signals
Parameter subset 1
Logic state signals
Parameter subset ... Control
Menu tree
Figure 3: Local control
11
Mechanical design
Processor module P
Bus modules B
The device is supplied in two case designs.
The processor module performs the analogue/digital conversion of the measured variables as well as all digital processing tasks.
Bus modules are printed circuit boards (PCBs) without any active components. They provide the electrical connection between the other modules. Two types of bus modules are used, namely the analogue and the digital bus PCB.
• Surface mounting case • Flush mounting case With both case designs, connection is via threaded terminal ends. Flush mounting cases - taking into account the differing case widths can be combined to form a complete 19” mounting rack. Figure 4 shows the modular hardware structure of the device. The plug-in modules can be combined to suit individual requirements. During each startup the number and type of fitted modules are identified and checked for compliance with the permissible configurations. As a function of the components actually fitted, the corresponding configuration parameters are then enabled for application. Transformer module T The transformer module converts the measured currents and voltages to the internal processing levels and provides for electrical isolation.
Transient ground fault evaluation module N The optional transient ground fault module evaluates the measured variables according to the transient ground fault evaluation scheme.
Binary I/O modules X The binary I/O modules are equipped with optical couplers for binary signal input as well as output relays for the output of signals and commands or combinations of these.
Local control module L The local control module encompasses all control and display elements as well as a PC interface for running the operating program. The local control module is located behind the front panel and connected to the processor module via a ribbon cable.
Analogue module Y The analogue module is fitted with a PT 100 input, a 20mA input and two 20mA outputs. One output relay each is assigned to two 20mA outputs. Additionally, four optical coupler inputs are available.
Communication module A The optional communication module provides a serial information interface for the integration of the protection and control unit into a substation control system. The communication module is plugged into the processor module.
Operating (PC) Port
Power supply module V The power supply module ensures the electrical isolation of the device as well as providing the power supply. Depending on the chosen design version, optical coupler inputs and output relays are provided in addition.
Communication Port A
MiCOM
L
TRIP
G C
ALARM
HEALTHY
G
EDITMODE
G
µC
G
G
G
O
N
G
OUTOFSERVICE
I
L/R
P
µP
B T
X
Currents / Voltages
Y
Control
/ Signals
V
/ Analogue Signals
Figure 4: Hardware structure
12
/ Commands Aux. Voltage
Technical data General data Design Surface mounting case suitable for wall installation or flush mounting case for 19” cabinets and for control panels
Installation position Vertical ±30°
Degree of protection Per DIN VDE 0470 and EN 60529 or IEC 60529. IP 52; IP 20 for the rear connection area of the flush mounting case.
Weight Case 40T: max. 7 kg Case 84T: max. 11 kg
Dimensions See dimensions
Terminal connection diagrams See Location and connections
Terminals PC interface DIN 41652 connector (X6), type D-Sub, 9 pin. Communication interface Optical plastic fibres (X7 and X8): F-SMA interface per DIN 47258 or IEC 60874-2 per plastic fibres or BFOC-(ST®) interface 2.5 per DIN 47254-1 or IEC 60874-10 per glass fibre or Leads (X9, X10): Threaded terminal ends M2 for wire cross sections up to 1.5mm 2 IRIG-B interface (X11) BNC plug Current measuring inputs Threaded terminals for pin terminal connection: Threaded terminal ends M5, self centering with wire protection for conductor cross sections of ≤ 4mm2 or Threaded terminals for ring terminal connection: In preparation Other inputs and outputs Threaded terminals for pin terminal connection: Threaded terminal ends M3, self centering with wire protection for conductor cross sections of 0.2 to 2.5mm2 or Threaded terminals for ring terminal connection: In preparation
Immunity to electrostatic discharge Per EN 60255-22-2 or IEC 60255-22-2, Level 3 Contact discharge, single discharges: > 10 Holding time: > 5s, Test voltage: 6kV Test generator: 50 to 100MΩ, 150pF/330Ω Immunity to radiated electromagnetic energy Per EN 61000-4-3 and ENV 50204, Level 3 Antenna distance to tested device: > 1m on all sides Test field strength, freq. band 80 to 1000MHz: 10V/m Test using AM: 1kHz /80% Single test at 900 MHz: AM 200Hz/100% Electrical fast transient or burst requirements Per IEC 60255-22-4 Test severity level 4 Rise time of one pulse: 5ns Impulse duration (50% value): 50ns Amplitude: 4kV/2kV, resp. Burst duration: 15ms, Burst period: 300ms Burst frequency: 2.5kHz Source impedance: 50Ω Surge immunity test Per EN 61000-4-5 or IEC 61000-4-5, Level 4 Testing of power supply circuits unsymmetrically/symmetrically operated lines Open circuit voltage front time/time to half value: 1.2/50µs, Short circuit current front time/time to half value: 8/20µs, Amplitude: 4/2kV, Pulse frequency: > 5/min Source impedance: 12/42Ω Immunity to conducted disturbances induced by radio frequency fields Per EN 61000-4-6 or IEC 61000-4-6, Level 3 Disturbing test voltage: 10V Power frequency magnetic field immunity Per EN 61000-4-8 or IEC 61000-4-8, Level 4 Frequency: 50Hz, Test field strength: 30A/m Alternating component (ripple) in dc auxiliary energizing quantity Per IEC 60255-11 12%
Insulation Voltage test Per IEC 60255-5 or EN 61010 2kV ac, 60s For the voltage test of the power supply inputs, direct voltage (2.8kV dc) must be used. The PC interface must not be subjected to the voltage test. Impulse voltage withstand test Per IEC 60255-5 Front time: 1.2µs, Time to half value: 50µs Peak value: 5kV, Source impedance: 500Ω
Creepage distances and clearances
Mechanical robustness
Per EN 61010-1 and IEC 60664-1 Pollution degree 3 working voltage 250V overvoltage category III, impulse test voltage 5kV
Vibration test Per EN 60255-21-1 or IEC 60255-21-1 Test severity class 1 Frequency range in operation: 10 to 60Hz, 0.035mm, 60 to 150Hz, 0.5g Frequency range during transport: 10 to 150Hz, 1 g
Tests Type test Tests according to EN 60255-6 or IEC 60255-6
EMC Interference suppression Per EN 55022 or IEC CISPR 22, Class A 1 MHz burst disturbance test Per EN 60255-22-1 or IEC 60255-22-1, Class III Common mode test voltage: 2.5kV Differential test voltage: 1.0kV Test duration: > 2s, Source impedance: 200Ω
Shock response and withstand test, bump test Per EN 60255-21-2 or IEC 60255-21-2 Test severity class 1 Acceleration: 5g/15g, Pulse duration: 11ms Seismic test Per EN 60255-21-3 or IEC 60255-21-3 Test procedure A, Class 1 Frequency range: 5 to 8Hz, 3.5mm/1.5mm 8 to 35Hz, 10/5m/s2, 3 x 1 cycle
13
Routine test Tests per EN 60255-6 or IEC 60255-6 Voltage test Per IEC 60255-5 2.2kV ac, 1s For the voltage test of the power supply inputs, direct voltage (2.8kV dc) must be used. The PC interface must not be subjected to the voltage test. Additional thermal test 100% controlled thermal endurance test, inputs loaded
Environmental conditions Ambient temperature range Recommended temperature range: –5°C to +55°C or +23°F to +131°F Limit temperature range: 25°C to +70°C or –13°F to +158°F Ambient humidity range ≤ 75% relative humidity (annual mean), up to 56 days at ≤ 95% relative humidity and 40°C, condensation not permissible Solar radiation Avoid exposure of the front panel to direct solar radiation.
Ratings Measurement inputs Nominal frequency f nom: 50 and 60Hz (settable) Operating range: 0.95 to 1.05f nom Over/Underfrequency protection: 40...70Hz Current Nominal current I nom: 1 and 5A (settable) Nominal consumption per phase: < 0.1 VA at I nom Load rating: continuous: 4 I nom for 10s: 30 I nom for 1s: 100 I nom Nominal surge current: 250 I nom Voltage Nominal voltage Vnom: 50 to 130V ac (settable) Nominal consumption per phase: < 0.3VA at V nom = 130V ac Load rating: continuous 150V ac
Binary signal inputs Nominal auxiliary voltage Vin,nom : 24 to 250V dc Operating range: 0.8 to 1.1Vin,nom with a residual ripple of up to 12% of Vin,nom Power consumption per input: Vin = 19 to 110V dc: 0.5W ±30% Vin > 110V dc: Vin x 5mA ±30%
Binary count input Maximum frequency of 20Hz with a pulse/interpulse ratio of 1:1
Analogue inputs and outputs Direct current input Input current: 0 to 26mA Value range: 0.00 to 1.20 Idc,nom (Idc,nom = 20mA) Maximum permissible continuous current: 50mA Maximum permissible input voltage: 17V Input load: 100Ω Open circuit monitoring: 0 to 10mA (adjustable) Overload monitoring: > 24.8mA Zero suppression: 0.000 to 0.200 Idc,nom (adjustable) Resistance thermometer: Only PT 100 permitted, mapping curve per IEC 60751 Value range: –40 to +215°C (equivalent to –40 to +419°F) 3 wire configuration: max. 20Ω per conductor. Open and short circuited input permitted. Open circuit monitoring: Θ > +215°C (or Θ > +419°F) and Θ < –40°C (or Θ < –40°F)
Output relays
Typical characteristic data
Rated voltage: 250V dc, 250V ac Continuous current: 5A Short duration current: 30A for 0.5s Making capacity: 1000W (VA) at L/R = 40ms Breaking capacity: 0.2A at 220V dc and L/R = 40ms 4A at 230V ac and cos ϕ = 0.4
Main function Minimum output pulse for a trip command: 0.1 to 10s (settable) Output pulse for a close command: 0.1 to 10s (settable)
Power supply Nominal auxiliary voltage VA,nom: 48 to 250V dc and 100 to 230V ac or V A,nom: 24V dc (depends on ordering) Operating range for direct voltage: 0.8 to 1.1 VA,nom with a residual ripple of up to 12% of VA,nom for alternating voltage: 0.9 to 1.1 VA,nom Nominal consumption at V A = 220V dc/ maximum number of modules fitted: In case 40TE: Initial position approx.: 12.6W Active position approx.: 34.1W In case 84TE: Initial position approx.: 14.5W Active position approx.: 42.3W Start-up peak current < 3A, duration 0.25ms Stored energy time ≥ 50ms for interruption of VA ≥ 220 dc
PC interface Transmission rate: 300 to 115,200 baud (settable)
Communication interface Protocol can be switched between: IEC 60870-5-103, IEC 60870-5-101, MODBUS, DNP 3.0 Transmission rate: 300 to 38400 baud (settable) Wire leads Per RS 485 or RS 422, 2kV isolation Distance to be bridged: peer-to-peer link: max. 1200m multi-endpoint link: max. 100m Plastic fibre connection Optical wavelength: typ. 660 nm Optical output: min. –7.5 dBm Optical sensitivity: min. –20 dBm Optical input: max. –5 dBm Distance to be bridged: max. 45m1) Glass fibre connection G 50/125 Optical wavelength: typ. 820 nm Optical output: min. –19.8 dBm Optical sensitivity: min. –24 dBm Optical input: max. –10 dBm Distance to be bridged: max. 400m1) Glass fibre connection G 62,5/125 Optical wavelength: typ. 820 nm Optical output: min. –16 dBm Optical sensitivity: min. –24 dBm Optical input: max. –10 dBm Distance to be bridged: max. 1400m1)
IRIG-B interface Format B122 Amplitude modulated, 1kHz carrier signal BCD time of year code
Definite time and inverse time overcurrent protection Operate time inclusive of output relay (measured variable from 0 to 2 fold operate value): ≤ 40 ms, approx, 30 ms Reset time (measured variable from 2 fold operate value to 0): ≤ 40 ms, approx, 30 ms Starting resetting ratio: ca. 0.95 Short circuit direction determination Nominal acceptance angle for forward decision: ±90° Resetting ratio forward/backward recognition: ≤ 7° Base point release for phase currents: 0.1 I nom Base point release for phase-phase voltages: 0.002 Vnom at V nom = 100V Base point release for residual current: 0.01 I nom Base point release for neutral displacement voltage: 0.015 to 0.6Vnom / √ 3 (adjustable) Over/undervoltage protection Operate time inclusive of output relay (measured variable from nominal value to 1.2 fold operate value or measured variable from nominal value to 0.8 fold operate value): ≤ 40 ms, approx, 30 ms Reset time (measured variable from 1.2 fold operate value to nominal value or measured variable for 0.8 fold operate value to nominal value): ≤ 45 ms, approx, 30 ms Starting resetting ratio: for operate values >0.6 Vnom or V nom / √ 3: ca. 0.95 for operate values >0.6 Vnom or V nom / √ 3: ca. 1.05
Deviations of the operate values Reference conditions
Sinusoidal signals with nominal frequency f nom, total harmonic distortion ≤ 2%, ambient temperature 20°C and nominal auxiliary voltage VA,nom Deviation
Deviation relative to the set value under reference conditions Measuring circuit monitoring Operate values I neg, V: ±3% Overcurrent time protection Operate values: ±5% Short circuit direction determination Operate values: ±10° Motor and thermal overload protection Reaction time: ±7.5% at I /I ref = 6 Over/underfrequency protection Operate values: ±3% Over/undervoltage protection Operate values: ±5% Unbalance protection Operate values: ±5% Ground fault direction determination Operate values VNG> , IN.act , IN.reac , IN>: ±3% Sector angle: 1°
Deviations of the timer stages Reference conditions
Sinusoidal signals with nominal frequency f nom, total harmonic distortion ≤ 2%, ambient temperature 20°C and nominal auxiliary voltage VA,nom Deviation
Deviation relative to the setting under reference conditions 1) Distance to be bridged for optical outputs and inputs that are equal on both ends, taking into account a system reserve of 3dB and typical fibre attenuation.
Definite time stages ±1% +20...40ms
14
Inverse time stages ±5% +10 to 25ms (measured variable greater than 2 I ref ) for IEC characteristic extremely inverse and for thermal overload protection: ±7.5% + 10 to 20ms
Deviations in measured data acquisition Reference conditions
Sinusoidal signals with nominal frequency f nom, total harmonic distortion ≤ 2%, ambient temperature 20°C and nominal auxiliary voltage VA,nom Deviation
Deviation relative to the relevant nominal value under reference conditions Operating data Currents/measuring inputs: ±1% Voltages/measuring input: ±0.5% Currents/internally calculated: ±2% Voltages/internally calculated: ±2% Active and reactive power: ±2% Load angle: ±1° Frequency: ±10mHz Fault data Short circuit current and voltage: ±3% Short circuit impedance, reactive: ±5% Fault location: ±5% Internal clock With free running internal clock: < 1 min./month With external synchronisation, via protocol, synch. interval ≤ 1 min: ±10 ms via IRIG-B signal input : ±1 ms
Resolution in fault data acquisition Time resolution 20 sampled values per period Phase currents and residual currents or neutral point currents resp. Dynamic range: 100 Inom or 25 Inom (settable) Amplitude resolution at Inom = 1A: 6.1mA rms. or 1.5mA rms. at Inom = 5A: 30,5mA rms. or 7.6mA rms. Voltages Dynamic range: 150V Amplitude resolution: 9,2 mV rms
Address list Function parameters Global functions PC link (PC): Command blocking: No/Yes Sig./meas.val.block.: No/Yes Communication link (COMM1): Command block. USER: No/Yes Sig./meas.block.USER: No/Yes Binary and analogue output (OUTP): Outp.rel.block USER: No/Yes Main function (MAIN): Device on-line: No (= off) /Yes (= on) Test mode USER: No/Yes Nominal frequ. fnom: 50Hz/60Hz Rotary field: Clockwise rotation/Anti-clockwise rot. Inom CT prim.: 1..10000A IN,nom CT prim.: 1....10000A Vnom VT prim.: 0.1....1000.0kV VNG,nom V.T. prim.: 0.1....1000.0kV Inom device: 1.0A/5.0A IN,nom device: 1.0A/5.0A Vnom VT sec.: 50...130V VNG,nom VT sec.: 50...130V Conn. meas. circ. IP: Standard/Opposite Conn. meas. circ. IN: Standard/Opposite Meas. value rel. IP: 0.000...0.200 Inom Meas. value rel. IN: 0.000...0.200 IEnom Meas. value rel. V: 0.000...0.200Vnom Meas. val. rel. VNG: 0.000...0.200 Vne,nom Settl. t. IP,max,del: 0.1... 15.0...60.0 min Fct.assign. block. 1: see selection table Fct.assign. block. 2: see selection table Trip cmd.block. USER: No/Yes Fct.assig.trip cmd.1: see selection table Fct.assig.trip cmd.2: see selection table Min.dur. trip cmd. 1: 0.10...10.00s Min.dur. trip cmd. 2: 0.10...10.00s Latching trip cmd. 1: No/Yes Latching trip cmd. 2: No/Yes Close cmd.pulse time 0.10 ... 10.00s Inp.asg. ctrl.enable. Without function valid for y = ,1’ ... ,8’ Debounce time gr. y: 0.00...2.54s Chatt.mon. time gr. y: 0.0...25.4s Change of state gr. y: 0...254 Cmd. dur.long cmd.: 1...254s Cmd. dur.short cmd.: 1...254s Inp.asg. ctrl.enable.: see selection table Inp.asg.interl.deact: see selection table Auto-assignment I/O: No/Yes Electrical control: Remote/Local W. ext. cmd. termin.: No/Yes Inp.assign. tripping: see selection table Prot.trip>CB tripped: Without function Gen. trip command 1 Gen. trip command 2 Gen. trip command 1/2 Inp. asg. CB trip: see selection table Sig. asg. CB closed: see selection table Inp.asg.CB tr.en.ext: see selection table Inp.asg. CB trip ext: see selection table Inp.asg. mult.sig. 1: see selection table Inp.asg. multi.sig. 2: see selection table Fct. assign. fault: see selection table
Fault data acquisition (FT_DA): Line length: 0.01 ... 500.00km Line reatance: 0.10 ... 200.00 -- bei Inom = 1.0A 0.01 ... 40.00 -- bei Inom = 5.0A Angle kG: -180 ... 180° Abs. value kG: 0.00 ... 8.00 Start data acquisit.: End of fault/Trigg., trip, GS end Output fault locat.: On general starting On gen.start.w.trip Fault recording (FT_RC): Fct. assig. trigger: see selection table I>: 0.01 ... 40.00 Inom Pre fault time: 1...50 periods Post fault time: 1...50 periods Max. recording time: 5...750 periods
Main functions Main function (MAIN): Syst.IN enabled USER: No./Yes Hold time dyn.param.: 0.00 ... 100.00s Block tim.st.IN, neg: Without For single-ph. start For multi-ph. start. Gen. starting mode: W/o start. IN, Ineg/With start. IN, Ineg Op. mode rush restr.: Without Not phase selective Phase selective Rush I(2*fn)/I(fn): 10...35% I> lift rush restr.: 5.0...20.0 Inom Suppress start. sig.: 0.0 ... 100.0s tGS: 0.00 ... 100.00s Definite time overcurrent protection (DTOC): General enable USER: No/Yes Inverse time overcurrent protection (IDMT): General enable USER: No/Yes Short circuit direction determination (SCDD): General enable USER: No/Yes Protective signalling (PSIG): General enable USER: No/Yes Autoreclosing control (ARC): General enable USER: No/Yes Motor protection (MP): General enable USER: No/Yes Thermal overload protection (THERM): General enable USER: No/Yes Unbalance protection (I2>): General enable USER: No/Yes Over/undervoltage proection (V ): General enable USER: No/Yes Directional power protection (P): General enable USER: No/Yes Over/underfrequency protection (f): General enable USER: No/Yes Selection meas. volt: Voltage A-G Voltage B-G Voltage C-G Voltage A-B Voltage B-C Voltage C-A Evaluation time: 3 ... 6 periods Undervolt. block. V Trip by I>> Trip by I>>> Trip by gen. start. Manual close timer: 0.00 ... 10.00s
Selfmonitoring (SFMON): Fct. assign. warning: see selection table
Circuit breaker failure protection (CBF): General enable USER: No/Yes tCBF: 0.00 ... 10.00s
15
Ground fault direction determination using steady state values (GFDSS): General enable USER: No/Yes Operating mode: Steady state power/Steady state current Oper. mode GF (pow.): cos phi circuit/sin phi circuit Evaluation VNG: Calculated/Measured Measuring direction: Standard/Opposite VNG>: 0.02...1.00Vnom(/ √ 3) tVNG>: 0.02...10.00s f/fnom (pow.meas.): 1/5 f/fnom (curr.meas.): 1/5 IN,act>/IN,reac> LS: 0.003...1.000 IN,nom Sector angle LS: 80...89° Operate delay LS: 0.00...100.00s Release delay LS: 0.00...10.00s IN,act>/IN,reac> BS: 0.003...1.000 IN,nom Sector angle BS: 80...89° Operate delay BS: 0.00...100.00s Release delay BS: 0.00...10.00s IN>: 0.003...1.000 IN,nom Operate delay IN: 0.00...100.00s Release delay IN: 0.00...10.00s Transient ground fault direction determination (TGFD): General enable USER: No/Yes Evaluation VNG: Sum (VA-B-C-G) /Measured Measurem. direction: Standard/Opposite VNG>: 0.15...0.50Vnom(/ √ 3) Operate delay: 0.05...1.60s IN,p>: 0.10...0.50 Inom Buffer time: 0...1200s Limit value monitoring (LIMIT): General enable USER: No/Yes I>: 0.10...2.40 Inom I>>: 0.10...2.40 Inom tI>: 1...1000 s tI>>: 1...1000 s I: 1...1000 s VPG: 1...1000 s VPP: 1...1000 s IDC,lin>: 0.100...1.100 IDC,nom IDC,lin>>: 0.100...1.100 IDC,nom tIDC,lin>: 0.00...20.00 s tIDC,lin>>: 0.00...20.00 s IDC,lin: 0...1000 s T> dynamic: 0.1...40.0 Inom I>>>: 0.1...40.0 Inom I>>> dynamic: 0.1...40.0 Inom tI>: 0.00...100.00 s tI>>: 0.00...100.00 s tI>>>: 0.00...100.00 s Evaluation IN PSx: Calculated/Measured IN>: 0.002...8.000 Inom IN> dynamic: 0.020...8.000 Inom IN>>: 0.002...8.000 Inom IN>> dynamic: 0.020...8.000 Inom IN>>>: 0.002...8.000 Inom IN>>> dynamic: 0.020...8.000 Inom tIN>: 0.00...100.00 s tIN>>: 0.00...100.00 s tIN>>>: 0.00...100.00 s Puls.prol. IN>,interm: 0.00...10.00 s tIN>,interm.: 0.00...100.00 s Hold-time tIN>,intm.: 0.0...600.0 s Shortcircuit direction determination (SCDD): Enable PSx: No/Yes Trip bias: No/Yes valid values for x: Direction tI> PSx: Direction tI>> PSx: Direction tIref,P> PSx: Direction tIN> PSx: Direction tIN>> PSx: Direction tIref,N> PSx: Forward directional Backward directional Non-directional Charact. angle G: -90... -45...90° VNG>: 0.015... 0.100...0.600 Vnom/ √ 3 Block. bias G: No/Yes Protective signaling (PSIG): Enable PSx: No/Yes Tripping time: 0.00...10.00 s Release time send: 0.00...10.00 s DC loop op. mode: Transm.rel.break con/Transm.rel.make con. Direction dependence: Without Phase curr. system Residual curr.system Phase/resid.c.system Autoreclosing control (ARC): Enable PSx: No/Yes Motor protection (MP): Enable PSx: No/Yes Iref: 0.10...4.00 Inom Factor kP: 1.05...1.50 Istup>: 1.8...3.0 Iref tIstup>: 0.1...1.9 s Character. type P: Reciprocal squared/logarithmic t6Iref: 1.0...100.0 s Tau after start-up: 1...60 s Tau machine running: 1...1000 min Tau machine stopped: 1...1000 min
16
Permiss.No.start-ups: 2/1 cold/warm/3/2 cold/warm RC permitted, o: 0.10...0.80 Inom Ineg>>: 0.10...0.80 Inom tIneg>: 0.00...100.00 s tIneg>>: 0.00...100.00 s Over/undervoltage protection (V): Enable PSx: No/Yes Operating mode PSx: Delta/Star Evaluation VNG PSx: Calculated/Measured V> PSx: 0.20...1.50 Vnom(/ √ 3) V>> PSx: 0.20...1.50 Vnom(/ √ 3) tV> PSx: 0.00...100.00 s tV> 3-pole PSx: 0.00...100.00 s tV>> PSx: 0.00...100.00 s V< PSx: 0.20...1.50 Vnom(/ √ 3) V> PSx: 0.20...1.50 Vnom/ √ 3 tVpos> PSx: 0.00...100.00 s tVpos>> PSx: 0.00...100.00 s Vpos< PSx: 0.20...1.50 Vnom/ √ 3 Vpos> PSx: 0.20...1.50 Vnom/ √ 3 tVneg> PSx: 0.00...100.00 s tVneg>> PSx: 0.00...100.00 s VNG> PSx: 0.02...1.00 Vnom(/ √ 3) VNG>> PSx: 0.02...1.00 Vnom(/ √ 3) tVNG> PSx: 0.00...100.00 s tVNG>> PSx: 0.00...100.00 s tTransient PSx: 0.00...100.00 s Hyst. V meas. PSx: 1...10 % Hyst. V deduc. PSx: 1...10 % Directional power protection (P): Enabled PSx: No/Yes P> high range PSx: 0.100...2.000 Snom P> sens. range PSx: 0.010 Snom Operate delay P> PSx: 0.00...100.00 s Release delay P> PSx: 0.00...100.00 s Direction P> PSx: Forward directional Backward directional Non-directional Diseng. ratio P> PSx: 0.05 P>> high range PSx: 0.100...2.000 Snom . P>>sens. range PSx: 0.010 Snom Operate delay P>>PSx: 0.00...100.00 s Release delay P>>PSx: 0.00...100.00 s Direction P>> PSx:
Forward directional Backward directional Non-directional Diseng. ratio P>>PSx: 0.05 Q> high range PSx: 0.100...2.000 Snom Q> sens. range PSx: 0.010 Snom Operate delay Q> PSx: 0.00...100.00 s Release delay Q> PSx: 0.00...10.00 s Direction Q> PSx: Forward directional Backward directional Non-directional Diseng. ratio Q> PSx: 0.05 Q>> high range PSx: 0.100...2.000 Snom Q>> sens. range PSx: 0.010 Snom Operate delay Q>>PSx: 0.00...100.00 s Release delay Q>>PSx: 0.00...100.00 s Direction Q>> PSx: Forward directional Backward directional Non-directional Diseng. ratio Q>>PSx: 0.05 Over/underfrequency protection (f): Enable PSx: No/Yes valid for y = ‚1‘ ... ‚4‘ Oper. mode fy PSx: f f with df/dt f w. Delta f/Delta t fy PSx: 40.00...70.00 Hz tfy PSx: 0.00...10.00 s dfy/dt PSx: 0.1...10.0 Hz/s Delta fy PSx: 0.01...5.00 Hz Delta ty PSx: 0.04...3.00 s
Control Main function (MAIN): BI active USER: No/Yes SI active USER: No/Yes Inp.asg fct.block.1: see selection table Inp.asg. fct.block.2: see selection table Op. delay fct. block: 0...60s Perm.No.mot.drive op: 1...20 Mon.time mot.drives: 1...20 min Cool.time mot.drives: 0...10 min Mon.time motor relay: 0.01...2.00s External device (DEV01 to DEV10): Designat.ext.dev.: see selection table Op.time switch. dev.: 0...254s Latching time: 0.00...25.4s GR. assign.debounce: Group 1... Group 8 Interm.pos. suppr.: No/Yes Stat.ind.interm.pos.: No/Yes Oper.mode cmd: Long command/Short commnad/Time control Inp.asg.sw.tr.plug: see selection table Inp.asg.el.ctrl.open: see selection table Inp.asg.el.clr.close: see selection table Inp.asg. end open: see selection table Inp.asg. end close: see selection table Open w/o stat.interl: No/Yes Close w/o stat. int.: No/Yes Fct.assig.BlwSI open: see selection table Fct.assig.BlwSI clos: see selection table Fct.asg.BI w/o SI op: see selection table Fct.asg.BI w/o SI cl: see selection table Interlocking logic (ILOCK): valid for y = ,1’...,32’ Fct.assignm.outp. y: see selection table
Operation Measured operating data Device (DVICE) Processor frequency: 25 ... 100MHz Measured data input (MEASI): Current IDC: 0.00...24.00mA Current IDC p.u.: 0.00...1.20 IDC,nom Curr. IDC, lin. p.u.: 0.00...1.20 IDC,nom Scaled value IDC,lin: -32000 ... 32000 Temperature: –40.0...215.0°C Measured data output (MEASO): Current A-1: 0.00...20.00mA Current A-2: 0.00...20.00mA Main function (MAIN): Date: dd.mm.yy Time: hh:mm:ss Time switching: Standard time/Daylight saving time Frequency f: 40.00...70.00Hz Curr. IP,max prim.: 0...25000A IP,max prim.,delay: 0...25000A IP,max prim.,stored: 0...25000A Curr. IP,min prim.: 0...25000A Current A prim.: 0...25000A Current B prim.: 0...25000A Current C prim.: 0...25000A Current ∑(IP) prim.: 0...25000A Current IN prim.: 0...25000A Volt. VPG,max prim.: 0.0...2500.0kV Volt. VPG,min prim.: 0.0...2500.0kV Voltage A-G prim.: 0.0...2500.0kV Voltage B-G prim.: 0.0...2500.0kV Voltage C-G prim.: 0.0...2500.0kV Volt. ∑(VPG)/3 prim.: 0.0...2500.0kV Voltage VNG prim.: 0.0...2500.0kV Volt. VPP,max prim.: 0.0...2500.0kV Voltage VPP,min prim: 0.0...2500.0kV Voltage A-B prim.: 0.0...2500.0kV Voltage B-C prim.: 0.0...2500.0kV Voltage C-A prim.: 0.0...2500.0kV Active power P prim.: –999.9...1000.0 MW Reac. power Q prim.: –999.9...1000.0 Mvar Act.energy outp.prim: 0.00...655.35 MWh Act.energy inp. prim: 0.00...655.35 MWh React.en. outp. prim: 0.00...655.35 Mvar h React. en. inp. prim: 0.00...655.35 Mvar h Current IP,max p.u.: 0.000...25.000 Inom IP,max p.u.,delay: 0.000...25.000 Inom IP,max p.u.,stored: 0.000...25.000 Inom Current A p.u.: 0.000...25.000 Inom Current B p.u.: 0.000...25.000 Inom Current C p.u.: 0.000...25.000 Inom Current ∑(IP) p.u.: 0.000...25.000 Inom Current IN unfilt.: 0.000...16.000 IN,nom Current IN p.u.: 0.000...25.000 V nom Voltage VPG,max p.u.: 0.000...25.000 Vnom Voltage VPG,min p.u.: 0.000...25.000 Vnom Voltage A-G p.u.: 0.000...25.000 Vnom Voltage B-G p.u.: 0.000...25.000 Vnom Voltage C-G p.u.: 0.000...25.000 Vnom Volt. ∑(VPG)/ √ 3 p.u.: 0.000...12.000 Vnom Voltage VNG p.u.: 0.000...25.000 VNG,nom Voltage VPP,max p.u.: 0.000...25.000 Vnom Voltage VPP,min p.u.: 0.000...25.000 Vnom Voltage A-B p.u.: 0.000...25.000 Vnom Voltage B-C p.u.: 0.000...25.000 Vnom Voltage C-A p.u.: 0.000...25.000 Vnom Active power P p.u.: –7.500...7.500 Snom Reac. power Q p.u.: –7.500...7.500 Snom Active power factor: –1.000...1.000 Load angle phi A: –180...180° Load angle phi B: –180...180° Load angle phi C: –180...180° Angle phi N: –180...180° Phase rel. IN vs ∑IP: Equal phase/Reverse phase
17
Ground fault direction determination using steady-state values (GFDSS): Current IN,act p.u.: 0.000...30.000 IN,nom Curr. IN,reac p.u.: 0.000...30.000 IN,nom Curr. IN filt. p.u.: 0.000...30.000 IN,nom Motor protection (MP): Therm.repl.buffer MP: 0...100 % St-ups still permitt: 0...3 Thermal overload protection (THERM): Therm. replica vers.: 0...250% Counters COUNT Count 1: 0...65535
Case dimensions
Surface mounted case 40 TE
P139
5 . 7 4 1
5 . 7 7 1
5 . 4 8 1
213.4
257.1
242.6 260.2
Flush mounted case 40 TE with panel cutout
P139
5 . 7 7 1
227.9
213.4
253.6 203 155.4
9 5 1
5.0 181.3
Figure 5: Dimensional drawings for case 40 TE
18
8 6 1
Surface mounted case 84 TE
P139
5 . 7 4 1
5 . 7 7 1
5 . 4 8 1
434.8
257.1
464 481.6
Flush mounted case 84 TE with panel cutout
P139
5 . 7 7 1
227.9
434.8
253.6 284.9 259.0
25.9
9 8 5 6 1 1
5.0
5.0 410.0
Figure 6: Dimensional drawings for case 84 TE
19
Location and connections
P139 in case 84TE for ring terminal connection 01
02
03
04
P A N
01
02
03
05
06
07
08
09
10
11
12
13
14
P139 in case 40TE for pin terminal connection 15
16
T
X
X
X
4J 4U
6I 6O
6I 6O
24I
04
05
06
07
08
09
10
11
12
13
14
15
17
18
19
20
X
V
6O
4I 8O
21
01
02
03
04
P A N
05
T
06
07
08
4J 4U
6I 6I 24I 4I 6O 6O 8O 6O
alt.
Y
Y
4I
4I 17
18
19
Figure 7: Location diagram
20
20
21
01
02
03
04
10
X X X V X
alt.
16
09
05
06
07
08
09
10
Terminal connections
Type T
Transformer module Ring
Pin
X041 X041 1 2 3 4 5 6
4J 4V
Voltage measuring inputs Fitted module combin. U T5 V T6 W T7 N e T90 n
Type X
Binary module Ring
6I 6O
Pin
Power supply module Ring
X_1
X_1
1
Output relays
X_1
1
1
1
2
2
2
2
3
3
3
3
4
4
4
4
5
5
5
5
6
6
6
6
7
7
7
7
8
8
8
8
9
9
9
9
K_2
K_3
1 2 3 4 5 6 7 8
Current measuring inputs A1 T1 A2 B1 T2 B2 C1 T3 C2 T4 N1 N2
Type TypeAA
Communication module Per order
10
1
11
2
3
12
3
13
4
13
4
14
5
14
5
15
6
15
6
16
7
15
7
17
8
17
8
18
9 18
9
10
1
11
2
12
X_3
VI
22
4
23
5
24
6
25
7
26
8
27
9
U_1 U_2
U_4
VI
U_5
VI
U_6
24I
2
2
1
3
3
4
4
X8
5
5
1
6
6
7
7
8
8
9
9
K_3
K_4 K_5 K_6 K_7 K_8
Vin
19
1
20
2
21
3
22
4
Vin
23
5
24
6
Vin
25
7
26
8
27
9
U_3
VI
Type Type X X
X7
K_2
U_1
X_3
VI
Binary module
1
or wire link
Signal inputs VI
1
K_1
Signal inputs
2 3
X_1
X9
K_6
20 21
Stiff
X//Y U18 U18
K_5
1
X_1
X//Y U17 U17
K_4
19
Ring
COMM1 optical fibre link
Output relays
X_2
X_2
X042
Pin
X_1
K_1
Type TypeV V
Signal inputs Vin
U_1 U_1 U_2 U_2 U_3 U_3 U_4 U_4 U_5 U_5 U_6 U_6 U_7 U_7 U_8 U_8
U_2 U_3 U_4
Power supply VAux U100
Type TypeX X
Binary module Ring
Vin
6O
Pin
Ring
Pin
X_1
X_1
1
1
2
2
3
3
5
4
4
6
5
5
6
6
X_1
X_1
1
1
2
2
3
3
4
4
5 6 7
7
8
8
9
9
Output relays K_1
K_2
X//Y
1
X_1
D2[R ]
2 3
U19 U19
4
D1[T ]
5
RS 485 COMM2 wire link only
10
1
11
2
12
3
13
4
14
5
15
6
16
7
17
8
18
9
Vin
3
X_1
U20
4
D1[T ]
5
RS 485
X11 1
19
1
20
2
21
3
22
4
23
5
24
6
IRIG-B
25
7
time synchronisation
26
8
27
9
#
#
Vin
7
7
8
8
9
9
1
11
2
10
K_1 valid
U
# U_8 K_2 valid
X_2 1
12
3
11
2
13
4
12
3
14
5
15
6
15
7
17
8
18
9
K_3
U_17 U_17 U_18 U_18 U_19 U_19 U_20 U_20 U_21 U_21 U_22 U_22 U_23 U_23 U_24 U_24
19
1
20
2
21
3
22
4
23
5
24
6
25
7
26
8
27
9
U21 U21
Figure 8: Terminal connection diagrams of the modules
21
# U_9
0..20 mA
K_4
13
4
14
5
15
6
15
7
17
8
18
9
K_5
Vin
U_1
Vin
U_2
Vin
U_3
Vin
U_4
X_3
K_6
19
1
20
2
21
3
22
4
23
5
24
‘-’ is used as a wildcard for the location according to figure 7
U
Signal and meas. inputs
X_3
D2[R ]
2
Meas. outputs
0..20 mA
10
X//Y
1
4I
X_2
U_9 U_9 U_10 U_10 U_11 U_11 U_12 U_12 U_13 U_13 U_14 U_14 U_15 U_15 U_16 U_16
(in preparation) X10
Type Y
Analogue module
6
U 0..20 mA
#
U PT100
#
U_5 U_6
Connection examples
Power supply
K200.1
Motor relay monitoring
K200 A1
M
Drive Q3
A2 E3
E1
X072: 8
4
X072: 9
5
X071: 3 X071: 6 X071: 5 X071: 4 X071: 2
1 2
6 9 8 7 5
4
E4 A1
M
Drive Q2
X062: X 06 2: X062: X062: X062:
A2 E3
E1
VE
E4 Drive Q1
A2
E4
Circuit breaker Q0
A1
M
E3
OPEN
5
E1 K200.3 K200.2 CLOSE
7
X061: X062: X 06 2: X062: X061:
9 3 2 1 8
X072: X073: X073: X072:
7 9 8 6
5
X061: X061: X 06 1: X061:
5 6 3 4
1 2
X091: 2 X091: 4
1 3
8
4
A B C
Gen. trip command 1
N2
X042: 1 2 3 4 5 6 7 8
U V W N e n
X041: 1 2 3 4 5 6
A1 A2 B1 B2 C1 C2 N1
I>
I>
I>
P139 (Detail)
I>
Dashed lines: recommended for GFDSS only (GFDSS: ground fault direction determination using steady-state values)
Figure 9: Connection example for P139 in case 40 TE with pin terminal connection
22
Ordering information Variants Time Overcurrent Protection and Control P139
Order No. P139-
Basic device 40TE, pin terminal connection Basic complement 4 binary inputs and 8 output relays 6 binary inputs and 6 output relays to control 3 switchgear Basic device 84TE, ring terminal connection Basic complement 4 binary inputs and 8 output relays 6 binary inputs and 6 output relays to control 3 switchgear
9
- 301
- 601
3
- 401
8
- 402
Case design: Surface mounted, local control panel with graphic display Flush mounted, local control panel with graphic display
Nominal current Inom = 1.0A/5.0A (T1..4)
0
9
5 6 9
1)
Without voltage input Nominal volage Vnom = 50V ... 130V (4 pole)
0 4
Additional options: Without 6 binary inputs/6 output relays to control 3 additional switchgear
0 5
Power supply and additional option: VA,nom = 24V dc VA,nom = 48 to 250V dc/100 to 230V ac VA,nom = 24V dc and binary module (6 output relays) VA,nom = 48 to 250V dc/100 to 230V ac and binary module (6 output relays)
3 4 8 9
Additional options: Without With transient ground fault direction determinatio n With analogue module With transient ground fault direction determination and analogue module With binary module (24 binary inputs) With binary module (24 binary inputs) and transient ground fault direction determination
0 1 2 3 4 5
Interfaces:
IRIG-B input for clock synchronisation
-456
0
0
2 2 2
1 2 4
With communication interface: IRIG-B input for clock synchronisation and switchable protocol between IEC 60870-5-101/103, MODBUS, DNP 3.0 and for connection to wire, RS485, isolated for connection to plastic fibre, FSMA connector for connection to glass fibre, ST connector Language: English (German) German (English) French (English) Spanish (English) 1)
User sele cted (factory settin g underl ined)
2)
Must be ordered before assebling
(without order ext. no.) 2) 2) 2)
Your contact:
23
-801 -802 -803
t n e m é l C e i r e m i r p m I e c n a r F n i d e t n i r P 1 0 1 0 5 0
a A / R B
TRANSMISSION & DISTRIBUTION Protection & Control, 60 Route de Sartrouville, BP58, 78230 Le Pecq Cedex, France Tel: +33 (0) 134 80 79 00 Fax: +33 (0) 134 80 79 13 Email:
[email protected] Internet: www.tde.alstom.com ©2001 ALSTOM. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM. MiCOM is a registered trademark of ALSTOM. Other names mentioned, registered or not, are the property of their respective companies. Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it. We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.
N E / 9 3 1 P n o i t a c i l b u P