PSAT User Manual

PSAT

Powerflow & Short-circuit Analysis Tool

User Manual

A product of

Powertech Labs Inc. Surrey, British Columbia Canada www.powertechlabs.com www.DSATools.com

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

PSAT User Manual

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITIES THIS SOFTWARE AND ITS DOCUMENTATION WERE PREPARED BY POWERTECH LABS, INC. (PLI). NEITHER PLI, ANY COSPONSOR, NOR ANY PERSON ACTING ON BEHALF OF ANY OF THEM: (A) MAKES ANY WARRANTY OR REPRESENTATION WHATSOEVER, EXPRESS OR IMPLIED, (I) WITH RESPECT TO THE USE OF ANY INFORMATION, APPARATUS, METHOD, PROCESS, OR SIMILAR ITEM DISCLOSED IN THIS REPORT, INCLUDING MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, OR (II) THAT SUCH USE DOES NOT INFRINGE ON OR INTERFERE WITH PRIVATELY OWNED RIGHTS, INCLUDING ANY PARTY'S INTELLECTUAL PROPERTY, OR (III) THAT THIS REPORT IS SUITABLE TO ANY PARTICULAR USER'S CIRCUMSTANCE; OR (B) ASSUMES RESPONSIBILITY FOR ANY DAMAGES OR OTHER LIABILITY WHATSOEVER (INCLUDING ANY CONSEQUENTIAL DAMAGES, EVEN IF PLI OR ANY PLI REPRESENTATIVE HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES) RESULTING FROM YOUR SELECTION OR USE OF THIS REPORT OR ANY INFORMATION, APPARATUS, METHOD, PROCESS, OR SIMILAR ITEM DISCLOSED IN THIS REPORT.

PSAT program and its documentation are confidential property of Powertech Labs Inc. This Program is protected under the copyright laws and by application of international treaties. All Rights Reserved under the Copyright Laws. Except as expressly provided by the terms and conditions set forth in the License, the LICENSEE shall not: (A) distribute or disclose the Program, Documentation or Derivative Work thereof to others; or (B) disclose the Proprietary Information associated with or embodied in the Program and Documentation in any form whatsoever; without prior written consent of Powertech Labs Inc. The LICENSEE shall not use the program except as expressly provided by the conditions of LICENSE TYPE in the License. Copyright Powertech Labs Inc. 20022011

Last modified – April 11

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

i

PSAT User Manual

CONTENTS

Page

1

PREFACE

1

2

PROGRAM INSTALLATION AND TESTING

2

2.1 2.2 2.3 2.4

Minimum System Requirements Installing the Program Installing Driver/Server for Security Keys Running the Program

3

OVERVIEW

3.1 Windows Graphical Interface 3.2 Getting Started 3.2.1 PSAT Main Window 3.2.2 Creating new Project and Powerflow 3.2.3 Opening, Viewing and Modifying a Project 3.2.4 Creating a New Diagram 3.2.5 Adding Components Graphically 3.2.6 Solving Powerflow 3.2.7 Viewing Solution Reports 3.2.8 Macros 3.2.9 Python Scripts

2 2 3 3

4 4 5 5 6 7 8 8 9 9 9 10

4

DATA AND REPORT TABLES

11

4.1 4.2 4.3 4.4 4.5

Modifying Powerflow Data in Tables Customizing Data and Report Tables Sorting Data and Report Tables Filtering Data and Report Tables Searching Data and Report Tables

5

BUS VIEW

15

6

SINGLE LINE DIAGRAM

16

6.1 6.2 6.3 6.4 6.4.1 6.4.2 6.4.3 6.4.4 6.4.5 6.4.6 6.4.7 6.4.8 6.4.9 6.5 6.6

Powerflow and Diagram Files Using the SLD Toolbox Using the Bus Tree Drawing Features Zooming Cropping the Diagram Redrawing the Connections Labels Animation of Flows SLD Contours Automatic Drawing Auto Generate One Level Automatic Drawing Bus Split Adding Other Drawing Objects Sub-Diagrams Printing Diagrams

7

MENUS

11 12 12 13 14

16 16 18 19 19 19 19 20 21 21 21 21 22 22 22

23

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

ii

PSAT User Manual

7.1 7.2 7.3 7.4 7.5 7.5.1 7.6 7.7 7.8 7.8.1 7.8.2 7.9 7.10 7.11

File Menu Solution Menu Reports Menu Subsystem Menu Edit Menu for Data Windows Data Manipulation Submenu Edit Menu for Report Windows Edit Menu for Diagram Windows Settings Menu Background Submenu Bus View Label Appearance Submenu Script Menu View Menu Window Menu

8

DIALOGS

8.1 8.2 8.3 8.4 8.5 8.6 8.7 8.8 8.9 8.10 8.11 8.12 8.13 8.14 8.15 8.16 8.17 8.18 8.19 8.20 8.21 8.22 8.23 8.24 8.25 8.26

Open and Save As Dialogs Import Powerflow Dialog Export Powerflow Dialog Page Setup Dialog Print Dialog Preview and Print Dialog Solution Parameters Dialog Bus Mismatch Threshold Dialog Limit Check Options Dialog Simple Subsystems Dialog Composite Subsystems Dialog Table Customization Dialog Diagram Data Matching Dialog Comparison Data Matching Dialog Color Options Dialog Contour Options Dialog Set Label Appearance Dialogs Show / Hide Labels Dialog Customize Dialog Set Bus Dialogs Set Area, Zone, Owner Dialogs Bus Connections Dialog Sectional Branch Dialog Select Branch Dialog Composite Label Dialog Interface Label Dialog

9

MODELS AND PROPERTIES

9.1 9.2 9.3 9.4 9.5 9.6 9.7 9.8 9.9 9.10 9.11

AC Bus Generator Load Load Model Fixed Shunt Switchable Shunt AC Line Fixed Transformer Adjustable Transformer Impedance Correction Table Three Winding Transformer

23 24 25 25 26 27 28 28 28 30 30 30 31 32

33 33 33 34 34 34 34 35 36 36 37 39 41 42 42 43 45 45 46 46 47 48 48 49 49 50 50

51 51 52 54 55 57 57 59 60 61 64 65

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

iii

PSAT User Manual

9.12 9.13 9.14 9.15 9.16 9.17 9.18 9.19 9.20 9.21 9.22 9.23 9.24

Fixed Series Compensator Adjustable Series Compensator Static Tap Changer / Phase Regulator DC Bus DC Line Commutated Converters Voltage Source Converter DC Line DC Breaker Area Zone Owner Sectional Branch Case Description

69 70 72 76 76 78 80 81 82 82 82 83 83

10

DATA MANIPULATION

10.1 10.2 10.3 10.4 10.5 10.6 10.7 10.8

Reassign Zone Reassign Area Scale MW Generation Scale Load Scale MVAr Load Scale Fixed Shunt Convert Load Model Delete Out-of-Service

11

SOLVING POWERFLOW

11.1

Governor Response

12

COMPARING TWO POWERFLOWS

90

13

REDUCTION

91

13.1 13.2

How to Reduce a Network Purging from the Network

14

SHORT CIRCUIT

14.1 14.2

How to Run Short Circuit Analysis Menus of Short Circuit Window

15

PSAT ASCII POWERFLOW FILE FORMAT

15.1 15.2 15.3 15.4 15.5 15.6 15.7 15.8 15.9 15.10 15.11 15.12 15.13 15.14 15.15

Solution History Data Bus Data Generator Data Load Data Load Model Data Fixed Shunt Data Switchable Shunt / SVC / STATCON Data Line Data Fixed Transformer Data ULTC Transformer Data Impedance Correction Tables Fixed Series Capacitor Data Switchable Series Capacitor Data Static Tap Changer / Phase Regulator Data 3-Winding Transformer Data

84 Error! Bookmark not defined. 84 85 85 86 86 87 87

88 89

91 92

93 93 94

95 95 97 97 99 101 101 102 103 104 106 108 108 109 110 113

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

iv

PSAT User Manual

15.16 Area Interchange Data 15.17 Interface Data 15.18 Multi-Terminal DC Data 15.18.1 Line Commutated Converters 15.18.2 DC Lines 15.18.3 DC Breakers 15.18.4 DC Buses 15.18.5 Miscellaneous Data 15.18.6 Voltage-Sourced Converter 15.19 Zone Data 15.20 Node Mapping Data 15.21 File Section Data

116 117 118 118 121 122 122 122 123 125 125 126

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

v

PSAT User Manual

1 Preface The PSAT software is a full-featured graphical powerflow program to create, examine and modify the powerflow data, solve the powerflow, and view the solution reports. The powerflow data and solution are displayed in Tables as well as on Diagrams. The powerflow data contains a complete and advanced set of models of power system components. It can be imported from (and exported to) commonly used powerflow data formats such as the PSS/E Raw data (versions 2632), GE EPC data (version 16), etc. The Single Line Diagram (SLD) is created easily by dragging and dropping the symbols of buses, generators, lines, etc., on the diagram. The Bus View diagram graphically shows all components at a selected bus. Several diagrams can be created from a powerflow data, each representing a different part of the system or different level of details. These diagrams can be saved in individual files and used with another (similar) powerflow data. In addition to its own macro, PSAT supports scripting in Python. A separate user‟s guide described the features and functionalities of this option. This manual describes the overall operation of PSAT. Chapter 2 describes the program installation. Chapter 3 provides an overview of the program features and operation.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

1

PSAT User Manual

2 Program Installation and Testing This chapter describes program installation and testing on Windows XP/Vista/7 systems. In addition to installing the program, you must install the driver and server for the security key.

2.1

Minimum System Requirements

The minimum hardware and software requirements for the Windows version are: 1. 2. 3. 4. 5. 6.

2.2

PC Pentium IV 50 Mb of free hard disk space 2 GB of RAM VGA card Windows 7, Vista, XP or Server2003 (or higher versions of these operating systems) Acrobat Reader1 5 or higher for viewing the User Manual

Installing the Program

Running the installation program provided on a CD creates the necessary folders and files on your computer. To install the software: 1.

Place the CD in your CD drive. After a few seconds, the Powertech Software Installation Guide window will appear on your screen. In this case go to step 3, otherwise go to step 2.

2.

To open the Powertech Software Installation Guide window, from the Start menu of your computer select Run and type: X:\start.exe where X is the drive in which the CD is inserted (e.g. D:\start.exe)

3.

To start the installation of PSAT, click on Install DSA Software. When the DSAToolsTM installer window appears, follow the steps as shown on your screen to complete the installation. The installation steps are: 3.1 Display of program information and welcome message. 3.2 Display of License Agreement: You must accept the terms of license to complete the installation. 3.3 Display of installation information. 3.4 Selection of destination folder: By default, the installation program creates a directory named DSATools_n (n is the version number, e.g., 11) on the destination drive (C) where it puts PSAT folder and its files. You may change this default destination to other directories/drives. 3.5 Selection of setup type: You may select to install some or all of the DSAToolsTM components provided on the CD. The “Typical” setup (default) installs all components. The “Custom” setup allows you to choose

1

Adobe and Acrobat are trademarks of Adobe Systems Incorporated

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

2

PSAT User Manual

which component is to be installed. In the Custom setup window, click on the arrow beside each component to make your selection from the drop-down list. 3.6 After copying the files, the installation creates a folder named DSATools under Start | Programs menu with subfolder PSAT n.m (n.m is the program version number, e.g. 11.0) and places shortcuts to the executables in this folder.

2.3

Installing Driver/Server for Security Keys

You may be provided with stand-alone (single-user) keys or a network key. For these keys to function properly, you must installed:  Driver for stand-alone key on all computers running PSAT. One key must be connected to the parallel port or USB port of each computer running the program.  Driver and Server for network key on a computer on the network where you intend to connect the security key. This server must be running for PSAT to obtain license from the network key and run (on any computer on the network).  Optionally, the Monitoring Tool to track the use of licenses of the network key. Click on Install Sentinel Driver/Server (or run the Sentinel\Sentinel Protection Installer.exe program from the CD) to install the driver and, if needed, the server for the security key. When the Sentinel installer window appears, follow the steps as indicated on the screen. You may choose the “Custom” setup type to select the parallel driver or USB driver (depending on the type of key you have received with the software; install both drivers on Windows XP) and the server to be installed. For more information, refer to the Sentinel\Readme.pdf file on the CD. You may need administrative privileges to install the driver/server. To complete the driver/server installation, the computer must be rebooted.

2.4

Running the Program

Connect the Security key to the parallel or USB port and, in case of the network key, make sure its server is running on the same computer. You may run the Monitoring Tool to check the server and available licenses in the key. If you have installed driver and server as described above, the server will start automatically every time you start the computer. Under the Start | Programs menu, find and click the PSAT shortcut to start the program. You may copy this shortcut to your desktop for easier access.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

3

PSAT User Manual

3 Overview This chapter describes the overall features and operation of PSAT. With PSAT, you can create a new powerflow data (case) and save it, open an existing powerflow data file in the PSAT ASCII (see Appendix I for details) or PSAT binary data (PFB or PSF), or import a powerflow data file in a variety of formats. You can also create Single Line Diagrams (SLD) of the system by drawing some or all buses in the powerflow data and their connections. The data can be viewed and modified through Properties dialogs or data tables. You can then solve the powerflow and view the solution on the diagram or solution tables. PSAT also supports a network reduction facility that can be used to eliminate a portion of the system by computing appropriate equivalents at boundary buses. You can also perform the classical short circuit analysis for the powerflow case with a specified sequence data or default data and view the results in a table or on the diagram. Each diagram can be saved in a file. You may store the powerflow data and any number of diagrams in a PSAT Project (PSP) file. By opening a project file, the powerflow data and all its diagrams will be loaded in and available for display. The diagrams created for a powerflow data (case) can be used for another (similar) case without the need for redrawing them. In this way, you can mix and match saved powerflow and diagram files in several project files. Many aspects of the data/solution tables and diagrams are customizable. The configuration files remember your customizations and appearances of the tables and diagrams. In addition, PSAT supports scripting in Python that allows the users to perform a variety of operations on the power system including data manipulation, obtaining specialized reports, etc.

3.1

Windows Graphical Interface

The PSAT interface and its description in this manual follow the standard Windows convention. The PSAT main window includes several menus, toolbars and sub-windows that function similar to commonly used Windows programs.  “Select” or “Click” in this manual means you move the mouse to position the cursor on an object, e.g., a menu item, button, tool icon, or title bar of a window or dialog box, and press the left mouse key to select that object.  “Right click” means a similar action except that you press the right mouse button instead of the left one.  “Drag” means you select an object and while you keep the left mouse key pressed, move the cursor to another position.  “Drop” means after you drag an object to a new position, you release the mouse button, so the object stays at the new position. On the diagrams, if you press the left mouse button and drag the mouse, a dotted rectangle shows the growing selected area and when you release the mouse button, all objects in that rectangle will be selected together. You can also hold the Shift key while clicking on (selecting) several objects to have them selected together. In PSAT several windows can be open at the same time. One of these is the “active” window and is the focus of mouse click, menu selection and keyboard. To make any window the “active” window, click on the title bar or anywhere else in that window, or select it from the Window menu.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

4

PSAT User Manual

3.2

Getting Started

This section is a brief tutorial to familiarize you with the operation of PSAT, using the samples provided with the program. The next chapters describe the program features and interface in detail. In PSAT, you deal with Powerflow, Single Line Diagram (SLD) and Project files. A PSAT Project is a collection of a powerflow data and one or more associated diagrams. You can create new powerflow, diagram and project files, or open existing (previously created and saved) files.

3.2.1 PSAT Main Window When you start the program (see Section 2.4) the PSAT main window appears with:  The menu bar  The toolbars with icons for commands such as open, save, etc.  The SLD toolbox (bar on the right margin of the PSAT main window) with symbols for AC bus, generator, etc., for drawing diagrams, and Drawing toolbox with symbols for line, rectangle, grouping, etc., for adding and arranging drawing symbols in the diagrams  Three panes for the project, data/report tables and diagrams, and messages (if the message window is hidden, open it by selecting Message in the View menu) The main window is better described by first loading a sample project. From the File menu select Open Project… and choose test1.psp in samples subdirectory of PSAT to open it. The three panes of the PSAT main window show the following: Workspace Window The Workspace window appears on the left and has two tabs (on the bottom). The Project Tab contains the tree structure of:  Single line Diagrams  Powerflow Data  Solution Reports  Data Verifications  Limit Checks The Bus Tree Tab shows the Bus Tree for drawing Single Line Diagrams. By clicking on the + icon beside Single Line Diagrams in the Project tab, it expands to show all diagrams files in the current project. Clicking the + icon beside Powerflow Data expands the tree to shows the list of all tables (categories) of powerflow data, e.g. AC Bus, Generator, etc. Clicking the + icon beside Solution Reports shows the list of all reports, e.g. Bus Mismatches, Bus Flows, etc. Clicking the + icon beside Data Verifications shows the list of all verification categories, e.g., Islands, Isolated Buses, etc. Clicking the + icon beside Limit Checks shows the list of all types of checks, e.g., Bus Under/Over Voltages, Overloaded Lines, etc. In the Bus Tree Tab, by clicking on the + icon beside each bus in the Bus Tree, it expands to show all components at that bus by their symbol and ID. If a component is a line (or transformer, etc.), the tree shows the bus at the other end of the line (or transformer, etc.). See section 6.3 for more information. Right Pane

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

5

PSAT User Manual

The right part of the window contains opened diagrams, data tables and reports. Double clicking on a diagram filename under Single Line Diagrams of the Workspace window, opens that diagram in a window in the right pane. Similarly, double clicking a Powerflow Data table (e.g. AC Bus) or a Solution Report table (e.g. Bus Mismatches) in the Workspace window, opens that data or report table in the right pane. The windows in the right pane can be resized, minimized or rearranged (cascade/tile). The columns of the tables can be customized by adjusting their width, reordering, hiding and freezing (so that they won‟t scroll left). The data in the tables can also be sorted by one or more columns. For drawing a Single Line Diagram (SLD), first an existing or new diagram window is opened in the right pane, then buses (and their connected components) are dragged from the Bus Tree of the Workspace window and dropped in this diagram window. Message Window The bottom pane of the main window shows the message window, which has three tabs: Messages:

This tab shows messages related to opening/importing powerflow files, solving, saving/exporting powerflow files, etc. Right-click in this tab to open the pop-up menu with commands for clearing or saving its contents.

Change Log: This tab shows the log of data modifications in the tables, diagrams and Property dialogs. Right-click in this tab to open the pop-up menu with commands for clearing or saving its contents. Macro:

This tab shows all the recorded Macro activities. Use the Macro menu or right-click in this tab to open the pop-up menu with commands for clearing, modifying (editing) or saving the contents of this tab.

The Workspace and Message windows can be “torn off” by dragging their handle bars (the bar on the top or left margin) away from their docked position and leaving them anywhere in the desktop. You may even close these windows by clicking the x button on their title bar (when they are torn off) or deselecting them in the View menu. To redisplay these windows, select them again in the View menu.

3.2.2 Creating new Project and Powerflow In the PSAT main window, from the File menu select New Project. A new (empty) powerflow case will be created. You can add new buses, generators, lines, and other components to the powerflow data in two ways: 1.

Open a Data table and use the Insert New Row command of the Edit menu as described below.

2.

Open a new or existing Diagram and use the SLD Toolbox as described in sections 3.2.5 and 6.2

For example, double click on AC Bus under Powerflow Data in the Project tab of the Workspace window to open the AC Bus table on the right. Then use the Edit | Insert New Row menu (or press the F2 key) to add a new bus to the table. This command first opens the Property dialog where you can enter/modify data for the added bus. When you add a bus, after closing the Property dialog, the Bus Connections dialog opens where you can add generators, loads, etc., to the new bus. You may choose not to add any component at this time and close this dialog to return to the AC Bus table. You may then open the Generator table, Load table, etc. and use the Edit | Insert New Row menu to add new components. For these components, a dialog first appears to select one of the existing buses for connecting the new component. Then, the Property dialog appears for entering data for the new component.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

6

PSAT User Manual

To delete a powerflow component, open its Data table, click on the row of that component to select it, and use the Delete Row command of the Edit menu. You may modify the powerflow data at any time by entering new values in the cells of Data tables, or Property dialogs. To open the Property dialog of a component, double click on it in the Data table, Bus Tree or Diagram. You save the powerflow data that you have created by selecting File | Save Powerflow as... menu item. This will open the “Save as” window where you can navigate the directories and choose a filename for the powerflow data to be saved in. Similarly, you can save the diagram that you may have created by clicking on its window (or double clicking on its name under Single Line Diagrams in the Project Tab) and then selecting File | Save Diagram as… menu item. You may then save the new project (powerflow and diagram files) by selecting File | Save Project as... menu item.

3.2.3 Opening, Viewing and Modifying a Project From the File menu select Open Project… and in the “Open” window that appears, find a PSAT Project file (PSP) and click open. For example, you may open test1.psp in samples subdirectory of PSAT. As described in Section 3.2.1, the Project tab of the Workspace window in the left shows the diagrams and powerflow data of the opened project. By clicking on a diagram filename under Single Line Diagrams in the Workspace window, that diagram opens in a window in the right pane of the PSAT main window. Also, clicking on each table name (AC Bus, Generator, etc.) under Powerflow Data in the Workspace window, that table appears in a window in the right pane. In the test1 project, clicking the test1-a diagram opens this diagram, which contains some of the buses in this case, and clicking the AC Bus opens the AC bus table, which shows data of all AC buses in this case. Instead of opening a project, you may open an existing PSAT Power Flow Binary (PFB) file without any diagram. For this, select File | Open Powerflow menu item and in the Open window that appears, choose a PSAT powerflow binary file to open. If a PSAT project (PSP) file with the same name is found, the program will ask you whether to open that project or not. If you select No, or if a project file is not found, a new project is created with this powerflow file. If the powerflow file is not in the PFB (or binary PSF) format, you need to select File | Import… menu item. This will open the Import window where you specify the powerflow file and its type and click the Import button to convert it to PFB format. If you have previously created and saved a diagram (in another project), to include it in the current project, select File | Open Diagram menu and choose that diagram file to open. For example, in the test1 project you can open test1-b.pfd in samples subdirectory. If the opened diagram was created for another powerflow data and has some components that do not exist in the current powerflow data, those components are ignored and only the remaining components (which match the current data) appear in the diagram. In this case (and after modifying the diagram), it is better to save the diagram in a new file so that the original diagram won‟t be lost. It is also possible to open/import a powerflow or diagram by simply dragging the file from the windows file manager into the PSAT main window. As described in the previous section, to modify a data item of a component (e.g. MW output of a generator), simply open its Powerflow Data table, click on the item in the table and type a new value, or double click on that component in the table (or in the diagram) to open its Property dialog and enter new values for its data items.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

7

PSAT User Manual

3.2.4 Creating a New Diagram To create a new single line diagram of powerflow components, select File | New Diagram menu. It opens a new (blank) diagram window in the right pane. Click on the Bus Tree tab in the left pane to display the Bus Tree. Drag a bus from the Bus Tree to the diagram window and drop it at a desired location. All generators, loads and shunts connected to this bus will be automatically drawn. Also, after adding other buses, any line, transformer, etc., connecting the added bus to the existing buses on the diagram will be automatically drawn. See section 6.3 for more information. If you cut (erase) any component (select it and press Delete key) from the diagram, you can redraw it by dragging it from the Bus Tree to the diagram window and joining it to its bus(es). The components that are drawn on the diagrams are shown in bold in the Bus Tree. To display bus names/numbers, line IDs, etc., select one or more buses, lines, etc., on the diagram (click on them while holding the Shift key or hold the left mouse key and drag on the diagram), then open the View menu and click on Label (or click the label icon on the toolbar). The Show / Hide Labels Dialog opens. Select Bus Name, ID, etc., by clicking on the box beside each item, then click the Apply button. If you click the Apply All button instead, the selected labels appear on all drawn components. Click the OK button to close the Show / Hide Labels dialog (or click the x button on the top-right corner) and click on the diagram to deselect the selected components. After you modify the diagrams or powerflow data, you can save them in the existing files or in new files by selecting File | Save Diagram (as…) and File | Save Powerflow (as…) menu items. Alternatively, you can save them by selecting Save Project or Save Project as... from the File menu.

3.2.5 Adding Components Graphically You can graphically add components to the opened powerflow case. For this, first open a new or existing diagram as described in sections 3.2.3 and 3.2.4. The window appears on the right pane of the PSAT main window. Then add new components on the diagram as follows: 1.

Click on the bus symbols in the SLD toolbox (short bar with a short line in the middle) to select it.

2.

Bring the mouse in the diagram and click anywhere to position the new bus at that location.

3.

Click on the generator or another symbols in the SLD toolbox to select it.

4.

Bring the mouse in the diagram and click anywhere to position the new component at that location, then click on the bus in the diagram to connect the component to that bus.

5.

Add other buses, lines, etc., in the same way. For lines, transformers, etc., you connect their two ends to two buses by first clicking one bus and then the other bus.

6.

Double click any component in the diagram to open its Property dialog and enter/modify its data.

For example, you first select AC bus in the toolbox and click in the diagram to add one bus. Then select generator in the toolbox and click in the diagram near the bus to add one generator. At this time the cursor changes to indicate you are in the Draw mode and allow you to connect the generator to a bus. Simply move the cursor over the bus and click to complete this connection. Then draw another AC bus and connect a load to it similar to the first bus and generator. Now connect the two buses by a line by selecting the AC line in the toolbox. The cursor changes to Draw mode and by clicking on one bus and then the other, a line will be connected between the two. If you first click on one bus, then on a point between the buses, and then on the second bus, the connected line will have two segments, with a Vertex (or breakpoint) at the clicked position. This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

8

PSAT User Manual

The new components that you draw from the toolbox are added to the powerflow data and appear in the Data tables. Double click on each added component in the diagram or Data tables to open its Properties dialog and enter required data for it.

3.2.6 Solving Powerflow After you open the powerflow data and, if needed, modify (and preferably save) it, you can solve the powerflow by using the Solution menu. First select Solution | Parameters… menu item to open the Solution Parameters Dialog where you can examine and, if needed, modify the solution options. After closing this dialog, select Solution | Solve menu item to start the solution. The Message window pops-up and shows the solution process. If the messages show data/solution errors or indicate that the solution is not found (did not converge), you need to examine and modify the data or solution options and repeat the solution. See section 11 for more details.

3.2.7 Viewing Solution Reports Click on the + button beside Solution Reports in the Project tab of the Workspace to see the list of reports. Double click on a report (e.g., Bus Mismatches, Bus Flows, Losses, etc.) to open it in the right pane. You may store each opened solution report. After you select the report by clicking on its title or double clicking on its name in the Workspace, use the Edit menu and choosing Save to Text File…, Save to Excel File… or Save to Clipboard to save the report in one of these places. The first two choices bring up the Save AS window where you select a file for saving the report. The solution can be viewed on the diagram as well. Select one or more buses, lines, etc., on the diagram (click on them while holding the Shift key or hold the left mouse key and drag on the diagram), then open the View menu and click on Label (or click the label icon on the toolbar). The Show/Hide Labels dialog opens. Select Voltage Magnitude, Power, etc., by clicking on the box beside each item, then click the Apply button. If you click the Apply All button instead, the selected labels appear on all drawn components. Close the Show/Hide Labels dialog by clicking the OK button (or the x button on the top-right corner) and click on the diagram to deselect the selected components. As described in the previous sections, you may save the solved powerflow in the existing or a new PFB file by using the File | Save Powerflow (as…) menu items.

3.2.8 Macros You can record all your activities, such as opening files, changing data, solving powerflow, saving solution reports to files, etc., in Macros which can be played back to repeat similar activities on the same case or a similar case. When you start a macro (using Start Recording of the Macro menu or the Record button of the toolbar), PSAT asks you to specify a file for saving the activities that will follow. When you stop the macro (using Stop Recording of the Macro menu or Record button of the toolbar), the file will be closed. The activities will be reflected in the Macro window (Macro tab of the Message window) as well. You may use this window similar to a text editor to modify its contents and save them to a file, just as you can open a saved macro file in an editor outside PSAT and modify and save it.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

9

PSAT User Manual

You can run saved macro files or the Macro window (using Run commands of the Macro menu) to repeat the recorded activities. For these activities to give similar result as before, PSAT status must be as it was when the recording of the macro had started. For example, the same or similar powerflow case must be open, similar subsystems must be defined and selected for open data and report tables, etc. Obviously, to make sure that you will get similar results, you can start recording of the macro before you open the powerflow file, define subsystems, etc., so these will also be recorded in the macro.

3.2.9 Python Scripts PSAT supports the use of Python programs. Python is a powerful and popular programming language, which can be freely downloaded from http://www.python.org. This site provides valuable information on Python and includes tutorials to help you become familiar with this tool. The specific versions of Python supported by PSAT are described in the PSAT-Python manual. A module named psat_python is provided with PSAT. It includes the functions that you can call from a Python program to obtain powerflow data, change powerflow data, solve powerflow, etc. You write a Python program, using these PSAT functions and any other Python feature, and you run it within PSAT by choosing Run Python File from the Script menu. See the PSAT-Python manual and help which are provided separately from this PSAT manual and help.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

10

PSAT User Manual

4 Data and Report Tables This chapter describes the features and contents of the powerflow data tables and solution report tables. The data tables appear in the right pane of the PSAT Main Window by double clicking a data category (e.g., AC Bus) under the Powerflow Data group in the Project tab of the Workspace. Each data table contains the powerflow data for one type of component, such as AC bus, Generator, Load, etc. Double clicking on a row of a data table, opens the Property dialog for that component which shows the same data items that were in the selected row. When you are viewing or modifying data items of one component, you may find it easier to use the property dialog, but when you are viewing or modifying the same data item for several components (e.g., MVAr output of a group of generators), it is easier to use the column of the tables. To find out the meaning and purpose of powerflow data items (columns of data tables and boxes of property dialogs), refer to chapter 9 which describes the models and attributes of powerflow components. The report tables also appear in the right pane of the PSAT main window by double clicking a report (e.g., Bus Flows under the Solution Reports or Overloaded Lines under Limit Checks) in the Project tab of the Workspace. The data shown in the report tables are not editable. You can customize the appearance and contents of the tables (see section 8.12), print them, save them in text or Excel files, or copy them to the clipboard (see the description of menus for details). The data tables and property dialogs have two types of fields (columns and boxes): External and Internal. The internal fields contain the attributes of the component to which the table or dialog belongs, while the external fields contain the attributes of another component related to this component. For example, generator table and property dialog contain the internal fields Status, MW output, MVAr output, etc., which are attributes of the generator, and external fields Bus Number, Bus Name and Bus Type, which are attributes of the bus to which the generator belongs. The External fields are shaded in the data tables and property dialogs.

4.1 Modifying Powerflow Data in Tables To modify a data item in a table, click on it and specify a new value. For example, in the generator table, you can click on MW output column of one of the rows (generators) and type a new value, or click on Status and select In or Out from its pull-down list. You need to press return or click on another field to complete the change. If you double click on an internal filed or the row number of a generator, the property dialog of that generator opens where you can change the attributes (e.g., MW output or Status) similar to changes in the table. For the external fields, two kinds of changes are possible by single click and double click. In the case of generator table, if you double click on the Bus Number, Name or Type of a generator, the Bus property dialog opens where you can modify the attributes of that bus. For example, you can change the bus type from Load Bus to Gen. Bus. On the other hand, if you single click on Bus Number, Name or Type for generator X, a down-arrow appears. Clicking this arrow opens the Set AC Bus dialog, which shows the list of all buses. If you double click on a bus in this dialog, it becomes the bus of generator X (i.e., the generator is moved from its previous bus to the new bus). Similarly, in other tables, single clicking on an external field of component X and changing it from A to B, connects (or relates) component X to component B instead of A, but double clicking on this field opens the property dialog of component A for viewing and modifying its attributes. Use the Edit menu, described in section 7.5, to add new components (rows) in the tables or delete existing components.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

11

PSAT User Manual

Modified fields and added rows will be highlighted blue. This coloring persists until the powerflow is saved, the solve powerflow command is run, or a solution report is loaded. In the AC Bus table, after you select a bus by clicking on it, the Edit Bus Connections command of Edit menu (or the right click pop-up menu) opens the Bus Connections Dialog where all connected components to the bus are listed and you can modify or delete them and add new components.

4.2 Customizing Data and Report Tables First select a data or report table to be customized by clicking on it in the right pane or on its name in the Workspace. Then select Customize table… in the Settings menu or the menu that pops up after right click on the table header row. The Table Customization dialog pops up where you can customize the columns and sorting orders as described in section 8.12. The following shortcut can also be used to customize the table. Column Width: To adjust the width of a column, click on the column border line in the headings row and drag it to the right or left, or double click on the border line to fit the column width to its contents. Column Position, Hiding and Freezing: To change the position of the columns in the table, hide or show columns, or freeze them from scrolling left, use the Table Customization Dialog (see section 8.12). Fonts: To change the font, size, and style of the text used in data tables, use the options listed under the „Global Settings‟ tab. For more information see section 8.12.

4.3 Sorting Data and Report Tables The rows of tables can be sorted by one or more columns. To sort by one column (e.g. Bus number), simply click on the column header. An “up” arrow appears in the column header, indicating that table is sorted by that column in ascending order (e.g., the row with lowest bus number is first). If you click again on the same column header, the sorting toggles between ascending and descending. The “up” arrow changes to a “down” arrow to indicate the new sorting direction. By clicking on another column header, the table is sorted by that column after canceling any previous sort. To sort by more than one column, after you click on the first sort column header, right click on another column header and select Add to Sort (2) from the pop-up menu. “Up” arrows appear in the column headers with numbers “1” and “2” to indicate the table is sorted first by the column with “1” in the header and then by the column with “2” in the header. If you right click on another column header and select Add to Sort (1), it becomes the first sort column and the previous first and second sort columns become the second and third sort column, respectively. If you right click on, for example, the second sort column header and click on the small arrow in the pop-up menu, the sorting direction for this column toggles between ascending and descending. If you select Reorder Sort (1) from the right click menu, this column becomes the first sort column and the first one becomes the second sort column. If you select Remove from Sort instead, this column is removed from the sort order and the third sort column becomes the second one. You may use the Table Customization Dialog instead to specify the sort orders (see section 8.12).

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

12

PSAT User Manual

4.4

Filtering Data and Report Tables

When working with a very large case, you may not need to view the whole data and reports in very large tables. In that case, you can define portions of the case (powerflow data) as subsystems and limit the contents of each table to one of these subsystems. Subsystems can be defined as:



      



 

Simple Subsystems: Bus number list, e.g., 1011, 1015, …, or range, e.g., 2001:2999 Bus name with wildcards, e.g., *ABC*, meaning all buses with “ABC” in their name Bus kV range, e.g., 138.0:500.0 Area number list or range Area name with wildcards Zone number list or range Zone name with wildcards Composite Subsystems: Including and Excluding bus/area/zone numbers/names and kVs (similar to simple subsystems) Including and Excluding bus types

Several composite subsystems can be defined and each would be identified by a given name. The included and excluded buses, areas, zones and kVs in a subsystem are process in the order they are specified. Therefore, this order has a significant effect on the end results. The following are examples of various subsystems that demonstrate the effect of the specified orders. Subsystem Name A5

Definition

Result

Include Area 5

All components in Area 5 are included (all other areas are excluded)

Sub1

Include Area 3 to 4

All components in Areas 3 to 4 are included,

Exclude Zone 24 to 27

those in Zones 24 to 27 are excluded (whether or not these are in Areas 3 to 4),

Include Bus kV 500. and all 500 kV components in all Areas and Zones (even those in Zones 24 to 27) are also included Sub2

Include Area 3 to 4

All components in Areas 3 to 4 are included,

Include Bus kV 500.

all 500 kV components in the case are included,

Exclude Zone 24 to 27

those in Zones 24 to 27 are excluded (whether or not these are 500 kV or in Areas 3 to 4 )

See section 8.10 and 8.11 on how to define the subsystems. To limit a data or report table to a defined subsystem, select it by clicking on its window in the right pane, or on its name in the Workspace. Then open the Select Subsystem submenu of the Subsystems menu (or the subsystem This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

13

PSAT User Manual

pull-down list in the toolbar) and click on of one of the defined subsystems in the list. The menu (or pull-down list) shows only the subsystems that are relevant to the selected table. The table will be limited to the selected subsystem and the subsystem name will appear beside the table name in the Workspace, as well as on the title bar of its window in the right pane. To include the whole system in the table, select from the Subsystem list. A quick filter option is available to modify and apply simple subsystem filters. By using the shortcut (Ctrl+F) from a data table, the Simple Subsystem dialog will appear. When the dialog is closed, the filter corresponding to the last property edited will be applied to the table (this is not done when the dialog is accessed from the menu / toolbar). For example to filter a table to bus number „123‟, press (Ctrl+F), type „123‟, and press enter. Note that for Solution Reports and Limit Checks, the subsystem list includes which is an empty subsystem and is the default for some tables (e.g., Bus Flows report is initially empty and shows no buses until you select a subsystem for it). Even after you close a table, its selected subsystem will be remembered and the next time you open it, the same subsystem will be applied.

4.5

Searching Data and Report Tables

You can quickly jump to a specific row in the data table by searching for a value within a data column. Simply select a cell within the data table to act as the starting point for your search and type your search term into the dropdown on the search tool bar. Pressing the „Find Next‟ button (F5) will search within the column of the selected cell for the next row to match your search term. Pressing the „Find Previous‟ button (Shift-F5) will search in the opposite direction. Depending of the type of data stored in the column, matching rows are found using slightly different criteria: 

Text: Values that exactly match or contain the search term as a substring. This is a case-insensitive search. For example: searching for the term „Cob‟ will match the Values „COB‟, „COBBLE‟, „JACOB‟, etc.



Integer: Values that exactly match the numeric value of the search term. (Do not include spaces in the number). You can search for a range of values by separating them with a colon. For example: „1:1000‟ will match on any value between (and including) 1 and 1000.



Decimal: Values that will round to the entered search term. The precision of the rounding is controlled by the precision of the number entered. For example: searching for the value „10‟ will match any value between 9.5 and 10.5. Searching for „10.00‟ will match any value between 9.995 and 10.005. You can search for a range of values by separating them with a colon. For example: „1:1000‟ will match on any value between (and including) 1.000 and 1000.000 (note that no rounding occurs when performing a range search).

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

14

PSAT User Manual

5 Bus View This chapter describes the features of Bus View. Bus View graphically shows all connected components at a bus and displays the powerflow data or solution of those components. To open the Bus View, select Bus View with Parameter or Bus View with Solution from the View menu. Note that selecting one of these, deselects the other one (you can toggle between the two). The Bus View shows the last selected bus (the bus selected in a data table or diagram) as a long bar on the left, as well as all its connected components with the labels selected for the view. For lines, transformers, etc., the other terminal bus(es) are shown on the right. If you click on one of these buses on the right, it becomes the “Selected” bus and the view changes to show that bus with all its connections. If you click on any bus in a table, a diagram, or the Bus Tree of the Workspace, it becomes the selected bus and the Bus View changes to show that selected bus. Double clicking the selected bus on the view opens its property dialog where all attributes of the bus can be viewed and modified. The Parameter and Solution views are similar except for the labels shown in each view. You can customize the labels for each view by using the Bus View Label Appearance of the Setting menu as described in section 8.16. You can put any label in any of these two views (even mix parameter and solution labels). The Bus View originally appears on the right side of the PSAT window. But you can grab (click and hold) its handlebars and drag it to any position on your screen. While you are dragging the view, when the cursor touches a border of PSAT window, the view docks to that border and you can leave it there or continue dragging it across the border. To close the view, deselect Bus View with Parameter or Bus View with Solution from the View menu (click on the checked item in the menu to remove the check mark). When it is torn-off from PSAT window, the title bar of the Bus View window has an x button on the top-right corner that will close the window.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

15

PSAT User Manual

6 Single Line Diagram This chapter describes the features of Single Line Diagrams (SLD).

6.1 Powerflow and Diagram Files To create a new powerflow data and diagram from scratch, open a new project using the File menu described in section 7.1 (or click on New Project button on the toolbar), which automatically opens a new powerflow data. Then open a new diagram (click on New Diagram button on the toolbar). This opens a blank diagram window where you can draw and connect components such as buses, generators, lines, etc., using the SLD Toolbox. To create a new diagram for an existing powerflow data, open the powerflow file or its project file, if it exists, using the File menu. Then open a new diagram (as above) to open a blank diagram window where you can draw the buses, with their generators, lines, etc., by dragging them from the Bus Tree and dropping them in the diagram window. To modify an existing diagram, open the related powerflow file and the diagram file, or if these are saved in a project, open the project file, using the File menu. Then double click on the diagram filename under Single Line Diagrams of the Workspace to open the diagram window, showing its contents. If the diagram does not belong to the opened powerflow file, or the file has been changed after the diagram was saved, those components in the diagram that do not match the components in the powerflow data will be ignored. Matching can be based on bus name, bus number or both as described in section 8.13. In this way, you can open a diagram of a powerflow case with a similar but different powerflow case, automatically remove unmatched components, and after adding other components, save it (with a new name so that the original diagram is not lost) in the other project.

6.2 Using the SLD Toolbox The SLD Toolbox, which normally appears on the right margin of PSAT Main Window, is used to simultaneously add new components to the powerflow data and draw them in the diagram. The tools included in the toolbox are the following:

          

AC Bus Generator Load Fixed Shunt Switchable Shunt AC Line Fixed Transformer Adjustable Transformer Three-Winding Transformer Fixed Series Compensator Adjustable Series Compensator

        

Converter Voltage Source Converter DC Line DC Breaker Ground Infinite bus (for converters) Text Contour Legend Composite Label



Interface Label



Case Detail Label

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

16

PSAT User Manual

 

Static Tap Changer / Phase Regulator DC Bus

 

Sectionalize Branch “Wand” Sub-diagram Container

To add a new bus to the diagram, click the bus icon in the toolbox, move the cursor to a desired position in the diagram and click. The new bus will be added at that position. To add a generator, load or shunt to a bus in the diagram, click an icon in the toolbox, move the cursor to a desired position in the diagram and click. The new component will be added at that position and the cursor changes to + to indicate you are in the Draw mode for connecting the new component to a bus. Simply move the cursor over a bus symbol and click to complete this connection. To draw a new AC line between two buses, click the AC line icon in the toolbox. The cursor changes to + for the Draw mode and by clicking on one bus and then the other bus in the diagram, the new line will be connected between the two. If you first click on one bus, then on one or more points between the buses, and finally on the second bus, the line will appear as a zigzag line, connecting the buses through Vertices (the clicked positions). You can add vertices to other connections (e.g., connecting a load to a bus) in a similar way. Transformers, series compensators, DC converters, etc., are drawn by selecting them in the toolbox, clicking in the diagram to position their symbol, and connecting each one of their terminals to one bus. This connection is similar to connection of lines and can go through a series of vertices by clicking at desired positions before reaching the bus. DC buses, converters and DC lines are added from the toolbox to the diagram in a similar way. You can add annotations to the diagram by the text tool. Click on the text icon (T) in the toolbox, then click at a desired position in the diagram to add “text” at that position. Right clicking on this “text” pops-up a menu where you can select Properties to open the Label Properties dialog, or select Edit Text to change the text. In the Label Properties dialog, you can change the text, select its alignment, foreground and background color and font. When you select Edit Text from the pop-up menu, the cursor changes to edit mode where you can type and change the text right in the diagram. In this mode, pressing the Enter key adds a new line of text. At the end of editing, click somewhere outside the text box to return to the normal mode. Contour Legend tool allows you to add a legend to the diagram to describe the values and colors used to generate a contour. Composite Label tool allows you to add a composite label on the diagram as described in section 6.4.4.1 Interface Label tool allows you to add power flows associated with an interface on the diagram as described in section 6.4.4.2 Case Detail Label tool allows you to add a label that lists the properties of the case used to generate the diagram. Properties include: File Name, File Date, Case Description, and Case Summary. Sectionalize Branch Wand of the toolbox allows you to change a regular (single-section) branch to a multisectional branch. Select (click on) this tool, then click on a regular branch. The Select Branch dialog (described in section 8.24) appears for you to select the type of the new section to be added to the selected branch. After you select a branch type from the pull-down list of this dialog and click OK, the Sectional Branch Property dialog (described in section 8.23) appears where you can set the properties of the new section, add and rearrange other sections, etc. The Sub-diagram Container tool is used to create sub-diagrams as described in section 6.5. You can select the default Horizontal or Vertical orientation in Bus Orientation of the Settings menu for adding buses in the diagram. Later, you can Rotate and Flip the bus symbols using the Edit menu or buttons of the toolbar. This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

17

PSAT User Manual

As you add components to the diagram, they are added to the powerflow data tables and the Bus Tree (you need to click on the tables and on each bus in the tree to refresh it for the added components). Double click on components in the Bus Tree or diagram to open their property dialog and enter data, such as name, ID, MW, etc. You can open the tables and enter and modify data in those tables or even add new buses, generators, lines, etc., while you add new components to the diagram from the toolbox.

6.3 Using the Bus Tree After you open existing or new powerflow data and diagrams as described above, you can easily draw the existing components of the powerflow data in the diagram by using the Bus Tree. At the same time, you can add new components to the powerflow data and the diagram by using the SLD Toolbox. You can then reposition and modify the components in the diagram, and display powerflow data and solution in the diagram as described in the following. Click on the Bus Tree tab in the Workspace to display the Bus Tree. This tree shows all the buses in the powerflow data. There is a Subsystem Selection pull-down list above the bus tree (in the Workspace window) similar to the Subsystem Selection list in the toolbar for the tables. If you have defined a simple or composite subsystem (as described in section 8.10 and 8.11), you can select it from this list to limit the Bus Tree and show only the buses of this selected subsystem. AC buses are shown at the top and DC buses are shown at the bottom of the tree. The list of AC buses can be sorted by bus name or bus number (which appears with # after the bus name). To sort by name or number, right click on the Bus Tree to pop-up a menu and select Sort by Name or Sort by Number from that menu. By clicking on the + icon beside each bus in the tree, it expands to show all connected components at that bus with their ID beside their symbol. For the lines, transformers, etc., the bus at the other end is also shown with a + icon which can be further expanded to show connected components at that bus (just as they would be shown in the main branches of the tree). In this way, the tree can be quickly branched out from one bus to show all connections at or near the bus. To draw a bus, grab it (click on its name/number and hold) in the main branch or an expanded branch of the Bus Tree, drag it to the diagram window and drop it at a desired position. The bus symbol appears with all generators, loads and shunts connected to this bus. Also, any line, transformer, etc., connecting this bus to the existing buses in the diagram appear automatically. You can reposition these components and redraw the connection lines as described above for the new cases. You can also select a symbol (click on it) and press the Delete key (or Cut in Edit menu) to remove it from the diagram. If you remove a load, transformer, etc., but leave the bus(es) in the diagram, to redraw them, again drag the bus from the Bus Tree to the diagram. This does not affect the bus and its existing connections in the diagram and only adds the removed symbols. You can select Horizontal or Vertical orientation in Bus Orientation of the Settings menu for buses as they are dragged from the Bus Tree to the diagram. Later, you can Rotate and Flip the bus symbols using the Edit menu or buttons of the toolbar. The buses that are drawn in the diagrams are shown in bold in the Bus Tree. To find a particular bus in a large crowded diagram, right click on it in the Bus Tree to pop-up a menu and select Find Symbol in that menu. The diagram window scrolls to bring that bus in view and shows it as the “selected” bus (as if you click on the symbol).

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

18

PSAT User Manual

6.4 Drawing Features In the normal mode, when the Select tool (pointer) in the toolbar is pressed, the symbols in the diagram are selected by clicking on them. To select a group of symbols, lasso them by clicking at a point in the diagram and dragging the mouse to select a rectangle (from the clicked point to the new mouse position). You can also select several symbols by clicking on them one by one while holding the Ctrl key. The connecting tails (lines) of generators, loads, etc. are selected separately from the symbols themselves for redrawing. To reposition the selected symbols, hold and drag them to a new location in the diagram. When you move a bus, its generators, loads and shunts move with it and the connection of lines and transformers are redrawn automatically. You can Rotate the selected symbols left or right and Flip them vertically or horizontally by using the Edit menu or toolbar buttons. You can also resize a component by clicking on it and dragging its corners to enlarge or reduce its size. The drawing area itself has an initial size. As you add symbols near the edge of drawing area, it expands gradually. To expand it by a large step, first zoom out to see the gray area outside the drawing area in the window. Then drag a symbol (or a bus from the Bus Tree or SLD Toolbox) to a position in the gray area to expand the drawing area to include this position. When you click on a bus in the main branch of the Bus Tree or in the diagram, if the Bus View is open, it shows that bus in the view. Double clicking opens the bus property dialog to view and modify its attributes. Double clicking any other component in the tree or diagram opens its property dialog to view and modify its attributes. Right click, instead, pops-up a menu and selecting Properties from that menu opens the property dialog as well.

6.4.1 Zooming You can Zoom in and out of the diagram by a fixed or specified factor and Zoom to Fit the whole diagram in the window by using the View menu or toolbar buttons. When the magnifying glass tool is selected in the toolbar, each right click zooms out by a factor. In this mode, selecting a part of the diagram by left click, drag and release, zooms in that part. Click the Select tool (pointer) in the toolbar to end this mode and return to the Select mode. Select one or more symbols and use Zoom to Selection menu command or button to zoom in them. Use Zoom Normal menu command to return to normal (100%) zoom factor. Use the Pan (hand) tool and the scroll bars to bring different parts of the diagram in the window.

6.4.2 Cropping the Diagram The size of the diagram automatically grows to accommodate new components. If components are moved or deleted, the diagram will remain at its larger size. To shrink the diagram‟s dimensions to fit the existing components, you can use the crop command by pressing the “C” key while viewing a diagram.

6.4.3 Redrawing the Connections You can change the shape of the AC lines, as well as the lines connecting components to buses, by adding and deleting vertices on the line and grabbing each vertex and dragging it to a new position. To add a vertex, right click on a desired point on the line and in the menu that pops-up, select Insert Vertex. To delete an existing vertex, right click on it and in the menu that pops-up, select Delete Vertex. In this pop-up menu if you select Redraw, the whole line is deleted and redrawn automatically (with vertices if needed).

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

19

PSAT User Manual

AC and DC buses are the only locations where the components are connected together. In a congested diagram, lines and other components may cross each other. These cross points will not be connections. To prevent confusion, add vertices to lines, including the connecting tail of generators, loads, etc., to go around buses to which they are not connected, instead of crossing them.

6.4.4 Labels Add Label command of the menu that pops-up with right click on a symbol in the diagram, opens the Select Label dialog, which shows the list of labels that can be added for that symbol. Those labels that are already shown in the diagram have a check mark beside them. To show the other labels, click to add a check mark beside them, and to hide a shown label, click to remove its check mark. After completing the label selection, close the dialog by clicking its OK button. Another way of adding labels (which is independent of the above Add Label command) is by the Show / Hide Labels dialog described in section 8.18. Apply and Apply All buttons of this dialog adds to the diagram those labels that are selected, and hides the ones that are not selected, in that dialog (not those in the Select Label dialog). In addition the Label Wand of the toolbar toggles show/hide of the labels. Click on the wand to select it, then click on any symbol to show/hide the labels that are selected in the Show / Hide Labels dialog. To end this and return to the Select mode, click the Select tool (pointer) in the toolbar. 6.4.4.1 Composite Labels You may add composite labels to the diagrams by using the Composite Label tool of the SLD Toolbox. This label may contain one or more lines of text, each with a value pointing to the sum of generation, load, etc., in a selected subsystem. When you add a new composite label, or double click on an existing one, the Composite Label Properties dialog (described in section 8.25) appears for setting the contents and appearance of the label. When you right-click on a Composite Label on the diagram, the pop-up menu gives you options to:

   

Open the Properties dialog (also accessed by double click on the label) and change the contents of the label. Edit Text by clicking in the label, typing and/or deleting text, then clicking outside the label to end editing. Link the label position to any symbol on the diagram. For this, first select the Link command, then click on the desired symbol (a bus, a sub-diagram, etc.). The label will move with the linked symbol. Re-link the label position to another symbol, or Un-link it so it won‟t move with the symbol.

6.4.4.2 Interface Labels Similar to Composite Label you may add interface(s) flows by using the Interface Label tool of the SLD Toolbox. This label may contain one or more lines of text, each with a value pointing to the interface name, sum of “From Side” Flow (MW), sum of “From Side” Flow (MVAR), sum of “To Side” Flow (MW), sum of “To Side” Flow (MVAR), etc., for the selected interface. The Properties dialog of the Interface Label has a tab marked as “Definition” which is used to select the interface definition for the label. A VSAT interface definition file is used to describe these interfaces; any changes to this file will be reflected in the corresponding Interface Label. To link to an interface definition file (and populate the interface definition list), use the Load Interfaces From File… command from the Subsytem menu (section 7.4). When you add a new interface label, or double click on an existing one, the Interface Label Properties dialog appears for setting the contents and appearance of the label. This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

20

PSAT User Manual

6.4.4.3 Linked Labels You may also add a Linked Label that shows a data item to which it is linked. For example, you can create a linked label that shows the Base MVA of a generator and place it anywhere in the diagram. For this: 1.

Go to the data table (click on its name in the Workspace or its window) and click on the desired item (e.g., Base MVA of a generator in the Generator table), then choose Copy Linked-Label from the Edit menu.

2.

Go to the diagram window (click on its name in the Workspace or its window) and choose Paste from the Edit menu (or click the Paste button on the toolbar), then click at the desired location on the diagram to place the linked label.

When you double click on a Linked Label, its Properties dialog appears where you can add a text to the label and specify its alignment, line, fill and font. The pop-up menu of right-click on the linked label gives you commands similar to the pop-up menu of the Composite Label described above, including linking the position of the label to a symbol on the diagram. Note that the “value” is linked to a data item and the “position” on the diagram is linked to a symbol, and these are independent of each other.

6.4.5 Animation of Flows To see the direction of flows on the diagram, use the Animate MW Flow and Animate MVAr Flow commands of the View menu (see section 7.10). Moving arrows show the direction of flow of real and reactive power through branches, and from/to generators, loads, etc. The size of the arrows indicates the magnitude of the flow. The speed at which the arrows move can be adjusted under the Animation Speed command of the Settings menu (see section 7.8).

6.4.6 SLD Contours SLD Contours can be used to visualize changes in component values as a color value in the background of the diagram. To display a contour use the „Show Contour‟ command of the Settings menu and use the „Contour Options…‟ Command to adjust the property and colors used to draw the contour (see section 7.8).

6.4.7 Automatic Drawing Auto Generate One Level Just as easily as expanding the Bus Tree from one bus, you can expand the diagram around a bus. Right click on a bus in the diagram and select Auto Generate One Level from the pop-up menu. All buses connected to this bus by lines and transformers are drawn automatically (if they are not already in the diagram). Select each one of these buses and, if necessary, drag it to a new location, and right click on it to expand it as well. By repeating this process, you can quickly draw a large number of buses that are connected together.

6.4.8 Automatic Drawing Bus Split Right click on a bus in the diagram (SLD) or select a row in the bus table and select Split Bus from the pop-up menu. The bus split dialog will appear showing, at the right side of screen, all elements connected to this bus (i.e. lines and transformers, load, etc.) and at left side of the dialog a new bus created based on the selected bus will be shown. You can move any of the elements connected to the old bus to the new bus.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

21

PSAT User Manual

6.4.9 Adding Other Drawing Objects You may add other objects to the diagram, such as rectangles and other shapes, images, etc., by using the Drawing Toolbox as you would in other drawing software. The Drawing Toolbox also has buttons for grouping and arranging the selected objects in the diagram.

6.5 Sub-Diagrams By using the Sub-diagram Container of the SLD Toolbox, you can create several layers of sub-diagrams in any diagram. You can draw any group of the powerflow components in a sub-diagram as you would in a normal diagram. Drawing features described above are the same for diagrams and sub-diagrams. Each sub-diagram appears as a rectangle in the upper diagram. In the upper diagram, the lines connecting the components to those inside the sub-diagram terminate at the boundary of the sub-diagram rectangle. By right click on the sub-diagram symbol (rectangle) in the upper diagram, a menu pops-up with Change Name, Properties and Add Label commands. The Change Name command opens the SubSystem Properties dialog where you can specify a name for the sub-diagram. Add Labels command allows you to show / hide these labels in the upper diagram. The Properties command allows you do change the draw style of the Sub-Diagram symbol. Layers of sub-diagrams appear in a tree structure under the diagram filename in the Workspace and are saved in the same file with the parent diagram. To open a sub-diagram, double click on its name under diagram filename in the Workspace or on its symbol (rectangle) in the upper diagram. You can have several diagram and sub-diagrams open, each in its own window in the right pane of PSAT window, and freely move from one to other to add components and modify them.

6.6 Printing Diagrams Toolbar buttons and Preview and Print command of File menu (described in section 8.6) allow you to print the whole or part of the diagram. To print a part, you either use print Selected Region, which then allows you to select a region of the diagram to be printed, or use print Window after you scroll/pan, zoom and resize the window to fill it with the desired part of the diagram.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

22

PSAT User Manual

7 Menus This chapter describes the menus of PSAT.

7.1 File Menu The File menu contains the following items. New Project

Opens a new (empty) project. If a project is already open, it is closed after asking whether to save the changes or not.

Open Project…

Opens the “Open” window for choosing an existing project file (PSP) to be opened. If a project is already open, it is closed after asking whether to save the changes or not.

Save Project

Saves the current project in its existing project file (PSP). The powerflow data and diagrams are also saved by this command.

Save Project as...

Opens the “Save as” window for choosing a new or existing project file and saving the current project in that file. This command also saves the powerflow data and diagrams in their existing files.

Close Project

Closes the current project after asking whether to save the changes or not. If your choose Yes, the project, powerflow and diagrams are saved, otherwise, they are closed without saving their changes.

Open Powerflow…

Opens the “Open” window for choosing an existing PSAT Power Flow Binary file (PFB) to be opened. If a project file (PSP) with the same name as the PFB file is found, it asks whether to open that project or create a new one. If a project is already open, it is closed (after asking whether to save the changes or not) before opening the PFB file. This command also opens binary powerflow files (PSF) created by previous versions of DSAToolsTM programs.

Save Powerflow

Saves the powerflow data in its existing PFB (or PSF) file.

Save Powerflow as...

Opens the “Save as” window for choosing a new or existing file and saving the powerflow data in that file (in PFB format).

Import…

Opens the “Import” window for specifying an existing powerflow file and its format and converting it to PFB format.

Export…

Opens the “Export” window for specifying a new or existing file and a format and saving the powerflow data in that file in the specified format.

Compare Powerflow Data…

Opens a second powerflow (PFB) file to compare its data (“case 2”) with the current data (“case 1”), and this command changes to Stop Comparing.

Stop Comparing

Stops the powerflow data comparison and returns to the normal PSAT mode.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

23

PSAT User Manual

New Diagram

Opens a new (blank) diagram. A project must already be opened before adding a new diagram to it.

Open Diagram…

Opens the “Open” window for choosing an existing diagram file (PFD) to be opened. A project must already be opened before adding an existing diagram to it.

Save Diagram

Saves the selected diagram in its existing file (PFD). To select a diagram, click on its open window or double click on its name in the Workspace file/data tree.

Save Diagram as...

Opens the “Save as” window for choosing a new or existing file and saving the selected diagram in that file. To select a diagram, click on its open window or double click on its name in the Workspace file/data tree.

Remove Diagram

Removes the selected diagram from the project. To select a diagram, click on its open window or double click on its name in the Workspace file/data tree.

Page Setup

Opens the “Page Setup” dialog to select the paper size, page orientation, margins, etc., for printing.

Print Preview

Displays the print image of selected data or report table in the Preview window, which appears on the right pane of the main window (hiding the open tables, reports and diagrams). To select a table for preview, click on its open window or double click on its name in the Workspace file/data tree.

Print...

Opens the “Print” dialog to select the printer and its properties for printing the selected data or report table. To select a table, click on its open window or double click on its name in the Workspace file/data tree.

Preview and Print

When a diagram is selected by clicking on its open window or double clicking on its name in the Workspace file/data tree, the above Print and Print Preview commands are replaced by this command which opens the “Preview and Print” dialog described in section 8.6.

Recent Files

This is a list of previously opened projects and powerflow files. Selecting one of these items will close the exiting project and open the selected item.

Exit

Exits PSAT. If a project is open, it is closed after asking whether to save the changes or not.

7.2 Solution Menu The Solution menu contains the following items. Solve

Starts the powerflow solution with the specified method and other solution parameters and options.

Parameters…

Opens the “Solution Parameters” dialog where the solution method, parameters and options can be viewed and modified.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

24

PSAT User Manual

Reduction / Purge…

Opens the “Reduction / Purge” window where the network can be reduced by retaining a selected subsystem and replacing the rest of the network by equivalent lines, shunts and loads.

Short Circuit…

Opens the “Short Circuit” window where short circuit computations are performed and results are displayed.

7.3

Reports Menu

The Report menu contains the following items. Bus Mismatch Threshold…

Opens the “Bus Mismatch Threshold” dialog where the threshold for Bus Mismatch report can be viewed and modified.

Limit Check Options…

Opens the “Limit Checks Options” dialog where the parameters for limit check reports can be viewed and modified.

7.4 Subsystem Menu The Subsystem menu contains the following items. Define Simple Subsystems…

Opens the dialog for defining Area, Zone, Bus and kV subsystems. These subsystems will be remembered until they are modified again in this dialog.

Define Composite Subsystems…

Opens the dialog for defining composite subsystems.

Select Subsystem

Opens the following submenu to select a subsystem. The selected subsystem will apply to the selected (“active”) data or report table. The table will be limited to the selected subsystem.



The whole system will be selected. This is the default for data tables.



Nothing will be selected (this is an empty subsystem). This is the default for some of the solution report tables and does not appear for data tables.



The defined Area subsystem becomes the selected subsystem.



The defined Bus subsystem becomes the selected subsystem.



The defined kV subsystem becomes the selected subsystem.



The defined Zone subsystem becomes the selected subsystem.

Composite Subsystems

List of defined composite subsystems, selecting one of these subsystems from this list will make it the selected subsystem.

Save Subsystems to file…

Opens the “Save as” window to select a file for saving the defined subsystems.

Load Subsystems from file…

Opens the “Open” window to select a saved subsystem file and open it to define the subsystems as saved in that file.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

25

PSAT User Manual

7.5

Edit Menu for Data Windows

When the active window is a Powerflow Data table, the Edit menu appears with the following items. Undo

Reverses the last change made in a data table (or property dialog) or a diagram. Repeated selection of this command reverses previous changes in sequence. The menu items toggles between Undo Data Change and Undo SLD Change depending on whether the change was made in a data table or in a diagram.

Redo

Reapplies the last change that was undone by Undo command. Repeated selection of this command reapplies previous Undone commands in sequence. The menu items toggles between Redo Data Change and Redo SLD Change depending on whether the change applies to a data table or a diagram.

Insert New Row

Adds a new component to the powerflow data by adding a new row in the selected table. For example, when the active window is AC Bus table, this command adds a new bus to the data. The Property dialog appears to view and modify the data items of the added component. When adding other components, a dialog appears first to select the bus where the new component will be added.

Duplicate Row

Adds a new component to the powerflow data by copying a selected row (where the cursor is) in the table to a new row. In the case of duplicating AC buses, a new number and name is given to the new bus and the other data items are copied from the selected bus. In the case of other components, first a dialog appears to select the bus where the new component will be added, then other data of the selected row is copied to the new row.

Delete Row

Deletes the selected row (where the cursor is) from the active table and removes the component from the powerflow data.

Property Dialog…

Opens the property dialog, showing data items of the component in the selected row (where the cursor is) of the table. The shortcut for this command is double click on a row in data tables. Double click on the row number or a regular cell (e.g. Generator ID) opens the property dialog of the component in that row. Double click on an external cell (e.g. Generator Bus Number) opens the property dialog of the component corresponding to that cell (the AC bus in this example).

Edit Bus Connections…

When a row (bus) is selected in the AC Bus table, this command opens the “Bus Connections” dialog where components can be added, deleted or modified at a selected bus.

Sectionalize…

When a row of a regular branch is selected in the Line, Transformer or Series Compensator tables, this command first opens the “Select Branch” dialog where you can select a line, transformer or series compensator branch type to be added in series with the selected branch. Then, the “Sectional Branch” dialog appears where you can modify, add and delete sections of this new sectional branch.

Sectional Branch Properties…

When a row of a sectional branch is selected in the Line, Transformer or Series Compensator tables, this command opens the “Sectional Branch” dialog where you can modify, add and delete sections of the selected sectional branch.

Save to Text file…

Opens the “Save as” window to select a file and save the contents of the active table in that file in text (comma separated) format.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

26

PSAT User Manual

Save to Excel file…

Opens the “Save as” window to select a file and save the contents of the active table in that file in Excel format. Depending on the version of Excel installed on your computer, you can select to save as either the older .xls format or the newer .xlsx format using the file type dropdown of the save dialog.

Save to Clipboard

Copies the contents of the active table to the clipboard in text (tab separated) format.

Data Manipulation

Opens Data Manipulation Submenu to manipulate data in the selected table.

7.5.1 Data Manipulation Submenu When the active window is a Powerflow Data table, the Data Manipulation submenu of the Edit menu contains the following items. Refer to section 10 for more details on each item. Reassign Zone…

When the active window is the AC Bus Table, this command opens the “Set Zone” dialog to select an existing zone or create a new zone, and change the zone of all the buses in the AC Bus Table to the selected zone.

Reassign Area…

When the active window is the AC Bus Table, this command opens the “Set Area” dialog to select an existing area or create a new area, and change the area of all the buses in the AC Bus Table to the selected area.

Scale MW Generation …

When the active window is the Generator Table, this command opens the “Scale MW Generation” dialog to scale the MW output of all the generators in the Generator Table by a factor or scale them to a new value.

Scale Load …

When the active window is the Load Table, this command opens the “Scale Load” dialog to scale all the loads in the Load Table by a factor or scale them to a new value.

Scale MVAr Load …

When the active window is the Load Table, this command opens the “Scale MVAr Load” dialog to scale the reactive part of all the loads in the Load Table by a factor or scale them to a new value.

Scale Fixed Shunt …

When the active window is the Fixed Shunt Table, this command opens the “Scale Fixed Shunt” dialog to scale the conductance, capacitance and/or inductance of all the shunts in the Fixed Shunt Table by a factor or scale them to a new value.

Covert Load Model…

When the active window is the Load Table, this command opens the “Convert Load Model” dialog to convert all the loads in the Load Table to a new combination of 1 to 5 components where each component can have one of the existing models (constant power, constant current, etc.).

Delete Out-Of-Service

When the active window is the Generator Table, Switchable Shunt Table, etc., this command deleted all out-of-service components in the table.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

27

PSAT User Manual

7.6

Edit Menu for Report Windows

When the active window is a Solution Report, Data Verification, or other types of report table, the Edit menu contains only the Save to Text File, Save to Excel File and Save to Clipboard, except when the Subsystem Summary report is selected, in which case, Save to Excel File does not apply.

7.7

Edit Menu for Diagram Windows

When the active window is an SLD, the Edit menu contains: Undo

Reverses the last change made in a data table (or property dialog) or a diagram. Repeated selection of this command reverses previous changes in sequence. The menu items toggles between Undo Data Change and Undo SLD Change depending on whether the change was made in a data table or in a diagram.

Redo

Reapplies the last change that was undone by Undo command. Repeated selection of this command reapplies previous Undone commands in sequence. The menu items toggles between Redo Data Change and Redo SLD Change depending on whether the change applies to a data table or a diagram.

Cut

Deletes the selected component(s) from the diagram (not from the project data) and keeps them in the clipboard.

Copy

Copies the selected component(s) from the diagram to the clipboard.

Paste

Copies the contents of the clipboard to the diagram. After a Cut or Copy command on the diagram, Paste command adds new components to the powerflow data (with modified bus number, name and ID) and the diagram as described in section 6.4.

Select All

Selects all symbols in the diagram.

Rotate Left

Rotates the selected symbols in the diagram 90 o to the left.

Rotate Right

Rotates the selected symbols in the diagram 90 o to the right.

Flip Horizontal

Flips the selected symbols in the diagram horizontally.

Flip Vertical

Flips the selected symbols in the diagram vertically.

7.8 Settings Menu When there is no open data table, report or diagram, the Settings menu contains the following items. Load from file…

Opens the “Open” dialog to select a saved settings file and change all the settings to those in the selected file.

Save to file…

Opens the “Save” dialog to select a file to save all the settings.

Revert to default

Changes all the settings back to the default values.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

28

PSAT User Manual

Diagram Data Matching…

Opens the Diagram Data Matching dialog to select the Name, Number or both for matching the components in saved diagram files with the powerflow data when the diagram files are opened. The diagram components that do not match the powerflow data based on the selected option will be ignored.

Comparison Data Matching…

Opens the Comparison Data Matching dialog to select the Name, Number or both for matching the data in two powerflow cases. For example, if you select the Number option, two buses with the same number in both cases are compared to each other and if their names don‟t match, the AC Bus table shows that they have different names. But if you select the Name option, these two buses will not be compared to each other (will be shown as two separate buses, each belonging only to one of the cases).

Bus View Label Appearance…

Opens Bus View Label Appearance Submenu to select the position and appearance of labels, such as bus number, bus name, ID, voltage, MW flow, etc., that appear beside each component in the Bus View.

When a Powerflow Data table, Solution Report or other type of tables is open and active, the Settings menu contains the following item in addition to the above items. Customize table…

Opens the Table Customization dialog to select the order, size and scroll option of the columns of the table and sorting of its rows by one or more columns.

When a diagram is open and active, the Settings menu contains the following items in addition to the above items. Background

Opens Background Submenu to change the background of the diagram.

Show Grid

Shows/hides the grid on the diagram.

Show Contour

Enables/Disables the drawing of background contours for open diagrams (see section 8.16)

Show Page Bounds

Shows/hides the bounds of printed pages on the diagram.

Show Units

Updates component labels to include their respective units in addition to the property values.

Use IEC Diagram Style

Changes the symbols used for various SLD components to more closely resemble the IEC diagram style.

Color by Type

Colors the components based on their type.

Color by kV

Colors the components based on their voltage level.

Color by Solution

Colors the buses based on the range of their per unit voltage magnitude and branches based on their loading.

Color Options…

Opens the Color Options dialog to select the colors and line thickness for component types, kV levels, and solution ranges.

Contour Options…

Opens the Contour Options dialog to adjust the colors and data used to generate the SLD contours. (see section 8.16)

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

29

PSAT User Manual

Default Bus Orientation

Opens a submenu to select 0o, 90o, 180o or 270o for orientation of the bus symbols. If you select 0o, the buses you add to the diagram (from the bus tree or the SLD toolbox) will appear as a vertical bar with label positions as those set in the Set Default Label Appearance dialog. If you select 90o, 180o or 270o, the default orientation of the bus symbol and its labels rotates by 90 o, 180o or 270o clockwise.

Animation Speed

Opens a submenu to select Fast, Normal, Slow, or Very Slow animation speeds for the flow animation on the diagram.

Label Appearance…

Opens the Set Defaults Label Appearance dialog to select the position and appearance of labels, such as bus number, bus name, ID, voltage, MW flow, that appear beside each component in the diagram.

7.8.1 Background Submenu When the active window is a diagram, the Background submenu of the Settings menu contains the following items. Background Color…

Opens the Color dialog to select a color for the background of the diagram.

Insert Image…

Opens the Open dialog to select an image file and insert its image in the diagram as the background.

Load GPS file…

Opens the “Insert GPS file” dialog to select a file with GPS coordinates of the borders of a map (and other coordinates) and draw them in the diagram.

7.8.2 Bus View Label Appearance Submenu The Bus View Label Appearance submenu of the Settings menu contains the following items. Parameter…

Opens the Set Parameter Appearance dialog to select the labels and their positions to appear beside the components in the Bus View with Parameters window.

Solution…

Opens the Set Solution Appearance dialog to select the labels and their positions to appear beside the components in the Bus View with Solutions window.

7.9 Script Menu The Script menu contains the following items. Start / Stop Recording Macro

Start Recording Macro opens the Select File dialog for you to specify a file for the macro to be saved in and after that, all your activities (data changes, etc.) are saved in that file, until you select Stop Recording Macro (this menu item toggles between Start and Stop). The activities saved in the macro file also appear in the Macro window.

Run Macro File

Opens a dialog for you to specify a saved macro file to be run. You may select a file from the pull-down list (it has the list of previously run macro files) or click on the browse button to open the Open File dialog, where you can navigate the folders and select a file. After specifying the macro file, click the Run button to perform all the activities (data changes, etc.) saved in that file.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

30

PSAT User Manual

Run Macro Window

Performs all the activities (data changes, etc.) contained in the Macro Window (same as saving the Macro window to a file and then running that file).

Clear Macro Window

Clears the Macro window by deleting all its contents.

Save Macro Window

Opens the Save As window for you to specify a file and then saves the contents of the Macro window in that file.

By Name

When selected, activities will be recorded in the macro file and window by bus/area/zone name. This de-selects “By Number”.

By Number

When selected, activities will be recorded in the macro file and window by bus/area/zone number. This de-selects “By Name”.

Run Python File

Opens a dialog for you to specify a saved Python script file to be run. You may select a file from the pull-down list (it has the list of previously run Python script files) or click on the browse button to open the Open File dialog, where you can navigate the folders and select a file. The file must be a text (un-compiled) Python script file (.py). After specifying the Python script file, click the Run button to run that script. This command will be disabled if the selected version of Python is not installed.

Python Version

This lets you select the version of Python used when running python scripts.

7.10 View Menu When a diagram is not the active window, the View menu contains the following items. Bus View with Parameters

Shows/hides the Bus View window with display of selected parameters (e.g. impedance, tap ratio, etc.)

Bus View with Solution

Shows/hides the Bus View window with display of selected solution quantities (e.g. MW flows, MVAr flows, etc.)

Toolbars

Opens the submenu to show/hide the Standard, SLD Components, Zoom, etc., toolbars in the PSAT window. Toolbars appear below the Menu bar, on the right border or other locations. By dragging their handle bars, these can be moved to any position.

Workspace

Shows/hides the Workspace (with Project and Bus Tree tabs) in the PSAT window.

Messages

Shows/hides the program messages (with Messages and Change Log tabs) in the PSAT window.

Status Bar

Shows/hides the Status bar on the bottom border of the PSAT window.

Customize…

Opens the Customize dialog to change the contents of the Menu bar and Toolbars.

When a diagram window is selected, the View menu contains the following items in addition to the above items. Label…

Opens the “Show / Hide Labels” dialog to select labels, such as Bus name, Bus Number, ID, etc., to be displayed on the diagram.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

31

PSAT User Manual

Zoom Normal

Sets the magnification factor to 100%.

Zoom Percent

Opens the submenu to set the magnification factor to 50%, 75%, 100%, or 200%.

Zoom Custom…

Opens the Zoom dialog to set the magnification factor to any value.

Zoom to Fit

Sets the magnification factor to show all components and fill the diagram window.

Zoom to Selection

Sets the magnification factor to show only the components that are selected in the diagram window.

Animate MW Flow

Shows/hides moving arrows that show the direction of flow of real power through branches, and from/to generators, loads, etc.

Animate MVAr Flow

Shows/hides moving arrows that show the direction of flow of reactive power through branches, and from/to generators, loads, etc.

7.11 Window Menu When one or more table, report or diagram windows are open, the Window menu appears with the following commands. Cascade

Cascades the table, report and diagram windows in the right pane of PSAT window.

Tile

Tiles the table, report and diagram windows in the right pane of PSAT window.

Arrange Icons

Arranges icons of minimized windows at the bottom of the right pane of PSAT window.

Close All

Closes all windows that are open in the right pane of PSAT window.

Open window list

Shows the list of all open windows and indicates the active window by a check mark. Clicking on another window in this list, makes that window the active one and brings it to the front of other windows.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

32

PSAT User Manual

8 Dialogs This chapter describes the dialogs of PSAT related to file handling, menu commands, customizations, etc. The component property dialogs are described in chapter 9 and data manipulation dialogs are described in chapter 10.



Contour Options … command of the Settings menu opens this dialog for choosing the colors and data used to draw SLD contour backgrounds. PSAT Color Spectrums tab is for choosing the gradient and colors to use when displaying contour data on SLDs. Value to Compare

All component properties that can be displayed in a contour are listed in this dropdown. The selected property will be used to supply values used in generating the contour

Spectrum Type

A list of preset and custom color gradients used to generate contours. The gradient settings can be adjusted using the color list to the right. Custom gradient settings can be saved to this list by using the „Save As’ Button in the Custom Contour box.

Range of Influence

By default, a component will influence the color of the entire SLD. By reducing the range of influence, you will set a maximum range a given component will color. This can be used to increase draw performance for large or complex diagrams and increase contrast in crowded areas.

Bounds

Sets the upper and lower bounds for determining the contour colors. Any value higher than max will use the color for 100% and any value lower than min will use the color for 0%. Setting the Auto Checkbox will automatically determine the Max and Min Bounds for each diagram based on the highest and lowest value of the components shown on the SLD.



Set Label Appearance DialogsOpen

and Save As Dialogs

These dialogs that appear after Open (or Load) and Save As commands are common Windows dialogs where you can navigate among the directories, create new directories, use “File of Type” pull-down list to filter the files being shown, click on a file to select it, right click on a file to get a menu for various command, create a new file, etc.

8.2 Import Powerflow Dialog The Import command of the File menu opens this dialog to select a powerflow data file and convert it to PSAT Power Flow Binary (PFB) format Powerflow Type

Specify the type (format) of the imported data by selecting one item from the type pull-down list.

Powerflow File

Specify the filename of the imported data by clicking the browse (…) button beside it, which opens the Open dialog for searching the directories and selecting the file. Instead, if you had imported the same file before, open the file pull-down list and select the file by clicking on it in the list.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

33

PSAT User Manual

Import button closes the dialog and starts the data conversion. The Message window shows the progress and warning and error messages of the conversion. Cancel button closes the dialog without importing the data.

8.3 Export Powerflow Dialog The Export command of the File menu opens this dialog to convert the PSAT powerflow data and save it in a selected file. Powerflow Type

Specify the type (format) of the exported data by selecting one item from the type pull-down list.

Powerflow File

Specify the filename of the exported data by clicking the browse (…) button beside it, which opens the Save As dialog for searching the directories and selecting an existing or new file.

Export button closes the dialog and starts converting and saving the data. The Message window shows the progress and warning and error messages of the conversion. Cancel button closes the dialog without exporting the data.

8.4 Page Setup Dialog The Page Setup command of the File menu opens this dialog to select the print and print preview options. You can specify: Print Pages

The number of pages for printing the diagrams. For example, if you specify 2 Down and 3 Across, the diagram will be printed on 6 pages. Use the print preview or Show Page Bounds of the Settings menu to see what will appear on each page. The same number of pages applies to View, Full and Selection printing.

Paper

The size and source of paper.

Orientation

Portrait or Landscape orientation of the pages.

Margins

Margins of the pages.

OK button will apply the settings and closes the dialog, Cancel button ignores the new settings (keeps the original settings when the dialog opened) and closes the dialog, and Printer button opens the dialog to select the printer and its properties.

8.5 Print Dialog This dialog that appears after Print commands is a common Windows dialog where you can select a printer, its properties, pages to be printed, number of copies, etc.

8.6 Preview and Print Dialog When a diagram window is selected, the Preview and Print command of the File menu opens this dialog to preview and print the diagram. It gives you the following options:

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

34

PSAT User Manual

Full Diagram

If this option is selected by clicking on its radio button, the whole diagram is previewed and printed.

Window

If this option is selected by clicking on its radio button, the part of the diagram that is visible in the window is previewed and printed

Selected Region

If this option is selected by clicking on its radio button, a selected region of the diagram is previewed and printed.

When the Selected Region is selected, Preview and Print buttons are inactive (grayed out) and “Select a Region” button is active. Otherwise, the first two buttons are active and “Select a Region” button is inactive. The function of these buttons are: Preview

Opens the preview window, which shows the print image (page by page) of the whole diagram or the visible part of the window, depending on the above selection. The Print button in this window will open the Print dialog to print this image. The Close button in this window closes the preview without printing.

Print

Opens the Print dialog to print the whole diagram or the visible part of the diagram window

Select a Region

Closes the dialog and changes the cursor for selecting the region to be printed. Press the mouse key anywhere on the diagram, drag it, and release the key to mark a rectangular region. After the mouse key is released, the preview window appears, showing the print image of the selected region. To print the shown pages, click the Print button of the preview window.

Cancel

Closes this dialog.

8.7 Solution Parameters Dialog The Parameter command of the Solution menu opens this dialog where you can specify: Solution Algorithm

Choose the solution method from the list of:  Auto  Newton-Raphson  Fast Decoupled (XB)  Fast Decoupled (BX) The Auto method starts with the Fast Decoupled solution and switches to NewtonRaphson for convergence to smaller than 1 MVA tolerance. The XB version of Fast Decoupled method is the conventional algorithm while the BX version is a modified algorithm that convergences better when there are AC lines with high R/X ratio.

Solution Parameters

Specify values for each parameter listed.

Control Parameters

Enable (check) or disable (uncheck) each control option. These apply to all control devices whose individual controls (shown in data tables and property dialogs) are enabled.

OK button will apply any change made to the parameters and closes the dialog. Cancel button ignores the changes (keeps the original value of parameters when the dialog opened) and closes the dialog. This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

35

PSAT User Manual

8.8 Bus Mismatch Threshold Dialog The Bus Mismatch Threshold command of the Reports menu opens this dialog where you can specify a threshold for bus mismatches. The Bus Mismatch report will show the buses with a mismatch greater than this threshold. OK button will apply any change made to the threshold and closes the dialog. Cancel button ignores the changes (keeps the original threshold) and closes the dialog.

8.9 Limit Check Options Dialog The Limit Check Options command of the Reports menu opens this dialog where you can specify the following parameters for Limit Checks: Bus Under Voltage Limit

Specify the low voltage limit in pu. Buses with voltage less than this limit will be listed in the Bus Under Voltage report.

Bus Over Voltage Limit

Specify the high voltage limit in pu. Buses with voltage greater than this limit will be listed in the Bus Over Voltage report.

Overloaded Lines Rating Number

Choose between 1 and 6. Loading of lines will be checked against this rating number.

Loading %

Choose any value smaller or larger than 100. Lines with loading greater than this percentage of the above rating number will be listed in the Overloaded Lines report.

Overloading Check Based on MVA

If selected, the overloading will be checked based on the MVA value

Overloaded Transformers Rating Number

Choose between 1 and 6. Loading of transformers will be checked against this rating number.

Loading %

Choose any value smaller or larger than 100. Transformers with loading greater than this percentage of the above rating number will be listed in the Overloaded Transformers report.

Overloading Check Based on MVA

If selected, the overloading will be checked based on the MVA value

Generator Voltage Violations Only report generators with unequal VAr limits

Line Angle Limit

When checked, the Generator Voltage Violations report will include only those generators whose Max.MVAr is greater than Min.MVAr.

Specify the angle threshold in degrees. If the phase angle difference between the two terminals of a line is greater than this threshold, it will be listed in the Line Angle report.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

36

PSAT User Manual

OK button will apply any change made to the parameters and closes the dialog. Cancel button ignores the changes (keeps the original value of parameters when the dialog opened) and closes the dialog.

8.10 Simple Subsystems Dialog The Define Simple Subsystem command of the Subsystem menu opens this dialog where you can define the simple subsystems, which include:

   

Selected Areas Selected Buses Selected kVs Selected Zones

The first three can be specified either by number or by name. To change the selection between “By Number” and “By Name” click on the radio button beside them. The subsystems are specified as follows: Selected Buses By Number

Specify the number of a bus (e.g., 1205), a list of buses (e.g., 15, 17, 23), a range of buses (e.g. 3001: 3200), or a combination of these (e.g., 703, 800:820, 915).

By Name

Specify a full bus name (e.g., ABC 138.) or a partial name with ? and * wildcards (e.g., A?C*138.), where ? indicates any (one) character and * indicates any number of characters. If By Number is selected (by clicking the radio button beside it), the Selected Buses subsystem consists of the buses whose number is included in the number list. If By Name is selected, the Selected Buses subsystem consists of one bus whose full name is specified, or all the buses whose names matches the specified partial name with wildcard. (e.g., ABC 138., AXCDEF 138., …)

Selected Areas By Number

Specify the number of an area, a list of areas, or a range of areas, similar to the bus number list above.

By Name

Specify a full area name or a partial name with ? and * wildcards, similar to the bus name above If By Number is selected, the Selected Areas subsystem consists of the areas whose number is included in the number list. If By Name is selected, the Selected Areas subsystem consists of one area whose full name is specified, or all the areas whose names matches the specified partial name with wildcard.

Selected Zones By Number

Specify the number of a zone, a list of zones, or a range of zones, similar to the bus number list above.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

37

PSAT User Manual

By Name

Specify a full zone name or a partial name with ? and * wildcards, similar to the bus name above If By Number is selected, the Selected Zones subsystem consists of the zones whose number is included in the number list. If By Name is selected, the Selected Zones subsystem consists of one zone whose full name is specified, or all the zones whose names matches the specified partial name with wildcard.

Selected kVs From kV To kV

Specify the range of kV. The Selected kV subsystem consists of all buses whose base kV is within the “From kV”:“To kV” range.

OK button will apply any change made to the subsystems and closes the dialog. Cancel button ignores the changes (keeps the original subsystem definitions) and closes the dialog.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

38

PSAT User Manual

8.11 Composite Subsystems Dialog The Define Composite Subsystem command of the Subsystem menu opens this dialog where you can define the composite subsystems, each consisting of a combination of buses, areas, zones, kVs (simple subsystems) and bus types. Each composite subsystem definition consists of Include and Exclude records of simple subsystems. These records are processed in order from top to bottom. For example if bus 101 and 102 belong to area 5 and zone 44, then subsystem: Include Area: 5 Exclude Bus: 101:102 Include Zone: 33 will consists of all buses in area 5 except bus 101 and bus 102, plus all buses in zone 33. If however, bus 101 belongs to zone 33, it will be included in the above subsystem because Include Zone: 33 appears after Exclude Bus: 101:102. Each composite subsystem is saved by a name, which appears in the Select Subsystem submenu. The Composite Subsystems dialog consists of the following: Subsystem List

Defined (saved) composite subsystem names. To view and modify a subsystem definition, select it from this pull-down list.

Bus tab

Allows you to include or exclude selected buses in the subsystem. It contains:

Bus list

List of all buses. Double click on a bus in the list (or click on a bus, then Include button) to include it in the subsystem definition. Click on a bus, then Exclude button to exclude it in the subsystem definition. Right click on the header row(s) to get the menu for sorting the list and customizing its columns similar to the AC Bus table (see section 8.12).

Bus Number fields

Type in a number in the first box (leave 0 in the second box) and click Include or Exclude button to include or exclude that bus number in the subsystem definition. Type in another number in the second box to include or exclude a range of bus numbers (e.g., 101:130) in the subsystem definition.

Bus Name field

Type in a full name or a partial name with ? and * wildcards and click Include or Exclude button to include or exclude the bus(es) with matching name in the subsystem definition.

Area tab Area list

Allows you to include or exclude selected areas in the subsystem. It contains: List of all areas. Double click on an area in the list (or click on an area, then Include button) to include it in the subsystem definition. Click on an area, then Exclude button to exclude it in the subsystem definition. Right click on the header row(s) to get the menu for sorting the list and customizing its columns similar to the Area table (see section 8.12).

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

39

PSAT User Manual

Area Number fields

Type in a number in the first box and 0 (or another number) in the second box and click Include or Exclude button to include or exclude that area number (or range of numbers) in the subsystem definition.

Area Name field

Type in a full name or a partial name with ? and * wildcards and click Include or Exclude button to include or exclude the area(s) with matching name in the subsystem definition.

Zone tab

Allows you to include or exclude selected zones in the subsystem. It contains:

Zone list

List of all zones. Double click on a zone in the list (or click on a zone, then Include button) to include it in the subsystem definition. Click on a zone, then Exclude button to exclude it in the subsystem definition. Right click on the header row(s) to get the menu for sorting the list and customizing its columns similar to the Zone table (see section 8.12).

Zone Number fields

Type in a number in the first box and 0 (or another number) in the second box and click Include or Exclude button to include or exclude that zone number (or range of numbers) in the subsystem definition.

Zone Name field

Type in a full name or a partial name with ? and * wildcards and click Include or Exclude button to include or exclude the zone(s) with matching name in the subsystem definition.

KV/Type tab

Allows you to include or exclude selected kV levels or bus types in the subsystem. It contains:

From kV and To kV fields

Type in two values and click Include or Exclude button to include or exclude that kV range in the subsystem definition.

Type

Select a bus type from the pull-down list and click Include or Exclude button to include or exclude the buses with that type in the subsystem definition.

Component tab

Subsystem Definition

Allows you to Include or Exclude components from a pick list. A component will match a subsystem if it has all the specified fields of the selected type (Number, Name, or Equipment Name). Fields are ignored if: 

Bus Number is less than or equal to 0.



Bus Name / Equipment Name is Empty



ID is set to *

Shows the Include and Exclude records in the order that they were defined (and would be processed). To remove a record from the definition, click on that record, then Remove button. Click Remove All button to remove all records.

New button will create a new (blank) subsystem. Save button will apply any change made to the subsystem. Save As button will save the subsystem by a new name. It opens a dialog where you type in a name for the new subsystem (keeps the original subsystem definition with the old name). Delete button deletes the subsystem from the list of composite subsystems. Close button closes the dialog.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

40

PSAT User Manual

8.12 Table Customization Dialog The Customize table… command of the Settings menu (or the menu that pops up by right click on a table header row) opens this dialog for customizing the selected table. Load settings from file

If you have saved the settings in initialization files (by the Save to File command of the Setting menu), you can pull-down this list and choose one of the saved files. The table settings will be changed to that saved in the selected file.

Columns tab lists all columns of the table in the order that they appear in the table. Hidden columns appear at the end of the list. To select a column in the list, click on its name. Move Up / Down

To change the position of a column in the table, select it in the list and click Move Up button to move it up in the list (left in the table) or Move Down button to move it down in the list (right in the table).

Show / Hide

The columns with a check mark beside them are shown in the table. Others are hidden. To hide or show a column, click on the □ box beside it to remove or add the check mark. Click Hide All or Show All button to hide or show all columns.

Column Width

The exact width of the selected column in the list is shown in “The width of the selected column . . . pixels” box. To change it, type a new number in this box. You can also resize the columns in the table itself by clicking on the border lines between the columns in the header row and dragging them to the right or left.

Freeze Columns

To freeze the first N columns of the table so that they stay in view when the table is scrolled to the right, choose a number in the “Number of frozen columns” pull-down list. If you choose 0, all columns will scroll left and right.

When you are comparing two powerflow cases, the Customization dialog of the comparison tables includes two more items. Comparison Threshold

The comparison threshold of the selected column in the list is shown in “The comparison threshold for the selected column” box. To change the threshold for a column, click on it in the list to select it and type a new value in this box.

Hide Rows of Similar Data

If you click on the □ box beside “Hide rows with the same data in both cases” to add a check mark, the rows in the table that show no value in the Diff columns are hidden. If you click on this box to remove the check mark, all rows (of the selected subsystem) will appear in the table.

Sort tab allows you to specify the sorting order of the rows of the table by one or more columns. The left list in this tab shows all columns and the right list shows the sort columns. To select a column in each list, click on its name. Add

Add button adds a column selected in the left list to the right list. You can also double click on a column name in the left list to add it to the right list.

Remove

Remove button removes a column selected in the right list. You can also double click on a column in the right list to remove it from the sort list

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

41

PSAT User Manual

Move Up / Down

To change the sort order by a column, select it in the right (sort) list and click Move Up or Move Down button to sort earlier or later by that column. The rows of the table will be sorted first by the first column in the list, then by the second column in the list, and so on.

Ascending / Descending

To sort by a column in ascending or descending order, select it in the right list and click Ascending or Descending button. You can also click on the arrow beside the column name in the right list to toggle its sort direction between ascending and descending.

The Global Settings Tab specifies settings that apply to all Data Tables. User Alternate Font

Change the font used for column headers and values displayed in data tables. Set the check box to adjust the font properties using the font browser to the right.

List fixed width fonts only

Set this checkbox to limit the font browser to only show fonts with characters of equal width. This is useful for aligning results within columns.

OK button will apply any change made to the customization and closes the dialog. Cancel button ignores the changes (keeps the original customization) and closes the dialog.

8.13 Diagram Data Matching Dialog The Diagram Data Matching … command of the Settings menu opens this dialog. In any project, you can open a diagram (by File | Open Diagram command) that was created and saved in a previous project (with a similar powerflow data). When the diagram is opened, those components of the diagram (buses, generators, etc.) that exist in the powerflow data will be kept and those that do not exist in the powerflow data will be ignored. To compare the components of the diagram and powerflow data, you can select one these options: Both Bus Name & Bus Number

If both name and number of a bus in the diagram are the same as those in the powerflow data, it will be kept in the diagram, otherwise it will be ignored.

Bus Name

If the name of a bus in the diagram is the same as the name in the powerflow data, it will be kept in the diagram (its number will be changed to that in the powerflow data), otherwise it will be ignored.

Bus Number

If the number of a bus in the diagram is the same as the number in the powerflow data, it will be kept in the diagram (its name will be changed to that in the powerflow data), otherwise it will be ignored.

OK button will apply any change made to the matching option and closes the dialog. Cancel button ignores the changes (keeps the original option) and closes the dialog.

8.14 Comparison Data Matching Dialog The Comparison Data Matching … command of the Settings menu opens this dialog. When you open a second powerflow data file to compare it with the current powerflow data (by File | Compare Powerflow Data command), the setting in this dialog determines how the two cases are matched. The options are: This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

42

PSAT User Manual

Both Bus Name & Bus Number

If both name and number of a bus in case 2 are the same as those in case 1, these buses match and their data from the two cases will be compared. Otherwise, they will be listed as two separate buses, each belonging to only one of the cases.

Bus Name

If the name of a bus in case 2 is the same as the name of a bus in case 1, these buses match and their data from the two cases will be compared. Otherwise, they will be listed as two separate buses. If the matched buses have different numbers, they are still compared with each other and the difference in their numbers is shown in the tables.

Bus Number

If the number of a bus in case 2 is the same as the number of a bus in case 1, these buses match and their data from the two cases will be compared. Otherwise, they will be listed as two separate buses. If the matched buses have different names, they are still compared with each other and the difference in their names is shown in the tables.

OK button will apply any change made to the matching option and closes the dialog. Cancel button ignores the changes (keeps the original option) and closes the dialog.

8.15 Color Options Dialog The Color Options … command of the Settings menu opens this dialog for choosing the color and line thickness of the symbols on the diagrams. Equipment Colors tab is for choosing the colors and line thickness of symbols as they appear in the diagram when you choose Color by Type option in the Settings menu. Components

All component types are listed in the left box. Click on one component to select it.

Color

Shows the color of the select component. To change the color, click on the browse button (…) beside it to open the color pallet and choose a different color.

Line Thickness

Shows the line thickness of the select component. To change the thickness, choose a value from its pull-down list.

Out of Service

Shows the color and line thickness of the out-of-service components. To change the color, click on the browse button (…) beside it and to change the thickness, choose a value from its pull-down list.

kV Rating Colors tab is for choosing the colors and line thickness of symbols as they appear in the diagram when you choose Color by kV option in the Settings menu. kV Level

Seven kV levels can be specified in the kV Level boxes in ascending order. For example, if you specify, 33.0, 66.0, … 700.0, the AC buses, lines, etc., at kV levels 0 to 33.0kV will have the color and thickness selected in the first row, those at kV levels above 33.0kV and up to 66.0kV will have the color and thickness selected in the second row, … and those at kV levels above 700.0kV will have the color and thickness selected in the seventh row.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

43

PSAT User Manual

Color

Shows the color of the select component. To change the color, click on the browse button (…) beside it to open the color pallet and choose a different color.

Line Thickness

Shows the line thickness of the select component. To change the thickness, choose a value from its pull-down list.

DC Components

Shows the color and line thickness of DC buses, lines, converters, etc., which can be set similar to the color and thickness of AC components above.

Solution Colors tab is for choosing the colors and line thickness of AC buses and branches as they appear in the diagram when you choose Color by Solution option in the Settings menu. For AC bus voltage, three groups of color and line thickness are specified as: Below

Buses with pu voltage below the value specified in the first row will have the color and thickness shown in the first row.

Over

Buses with pu voltage above the value specified in the second row will have the color and thickness shown in the second row.

Otherwise

Buses with pu voltage within the “Below” and “Over” values specified above will have the color and thickness shown in the third row.

Color

Shows the color of the voltage group on the left. To change the color, click on the browse button (…) beside it to open the color pallet and choose a different color.

Line Thickness

Shows the line thickness of the voltage group on the left. To change the thickness, choose a value from its pull-down list.

For AC branch loading, two groups of color and line thickness are specified as: Over / Rating

Branches with loading above the threshold, specified as a percentage value (“Over” box) of one of the ratings (“Rating” box), will have the color and thickness shown in the forth row.

Otherwise

Branches with loading below the above threshold will have the color and thickness shown in the fifth row.

You can specify any value (smaller or larger than 100) for the loading threshold and choose a rating number from its pull-down list. To change the color, click on the browse button (…) beside it and to change the thickness, choose a value from its pull-down list. OK button will apply any change made to the options and closes the dialog. Cancel button ignores the changes (keeps the original options) and closes the dialog.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

44

PSAT User Manual

8.16 Contour Options Dialog The Contour Options … command of the Settings menu opens this dialog for choosing the colors and data used to draw SLD contour backgrounds. PSAT Color Spectrums tab is for choosing the gradient and colors to use when displaying contour data on SLDs. Value to Compare

All component properties that can be displayed in a contour are listed in this dropdown. The selected property will be used to supply values used in generating the contour

Spectrum Type

A list of preset and custom color gradients used to generate contours. The gradient settings can be adjusted using the color list to the right. Custom gradient settings can be saved to this list by using the „Save As’ Button in the Custom Contour box.

Range of Influence

By default, a component will influence the color of the entire SLD. By reducing the range of influence, you will set a maximum range a given component will color. This can be used to increase draw performance for large or complex diagrams and increase contrast in crowded areas.

Bounds

Sets the upper and lower bounds for determining the contour colors. Any value higher than max will use the color for 100% and any value lower than min will use the color for 0%. Setting the Auto Checkbox will automatically determine the Max and Min Bounds for each diagram based on the highest and lowest value of the components shown on the SLD.

8.17 Set Label Appearance Dialogs The Label Appearance… command of the Settings menu opens the Set Default Label Appearance dialog for specifying the initial position and appearance of the labels for each type of component in the diagrams. The Bus View Label Appearance | Parameter… command of the Settings menu opens the Set Parameter Appearance dialog for specifying the position and appearance of the labels for each type of component in the Bus View with Parameter window. The Bus View Label Appearance | Solution… command of the Settings menu opens the Set Solution Appearance dialog for specifying the position and appearance of the labels for each type of component in the Bus View with Solution window. These three dialogs are similar and have the following elements: Component pull-down list, Toolbar and Drawing box. Component

Select one component from this pull-down list to show its symbol and its selected labels in the drawing box below where their position and appearance can be specified.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

45

PSAT User Manual

Select Labels…

This button opens the Select Labels dialog showing all labels (attributes) of the selected component. The check box beside each label indicates whether the label is selected or not (selected labels will appear in the diagram or Bus View). After selecting labels to appear, close the Select Labels dialog by clicking its OK button, or cancel the changed selection by clicking its Cancel button. In the Drawing box, you can click on any label to drag it to a different position relative to the symbol or to select it for specifying its appearance as described below.

Font…

After selecting a label beside the symbol, the Font button opens the common font and color selection dialog for that label. After you change the font close this dialog by its OK or Cancel button.

Alignment

After selecting a label beside the symbol, clicking on one of the three alignment buttons (marked by a “T” inside a text box) aligns the label to the left, right or center of its text box in the diagram or Bus View.

Rotation

After selecting a label beside the symbol, clicking on the rotation buttons (marked by “Abc” in a vertical or horizontal text box) rotates the label by 90o relative to the symbol.

The close (x) button will apply any change made to the label appearances and closes the dialog.

8.18 Show / Hide Labels Dialog The Labels… command of the View menu opens this dialog for selecting common labels of all component types to appear in the diagram. For buses you can select Bus Name, Bus Number, Voltage Magnitude, Voltage Angle and fault levels. For other components you can select ID, Power (MW and MVAr), Current, Tap Ratio and Phase Shift Angle (for transformers). It is also possible to use the “Custom” option where other component properties can be displayed on the SLD. Use the check mark beside “Custom” and then press the “Modify..” button to specify the desired attribute(s)/Properties. The check mark beside each label indicates whether it is selected or not to appear in the diagram. After making the selections, Shows the selected labels, and hides the un-selected ones, for the components Apply that are selected in the diagram. The components must be selected before this dialog is opened, otherwise, this button is grayed out. Apply All

Shows the selected labels, and hides the un-selected ones, for all the components in the diagram.

OK

Keeps the label selections and closes the dialog.

Any new component that is added to the diagram will appear with the selected labels. Note that other labels can be shown for each individual component by using the Add Label command of the pop-up menu that appears when you right click on a symbol in the diagram.

8.19 Customize Dialog The Customize… command of the View menu opens this dialog for customizing the toolbars. The Toolbars tab shows the list of defined toolbars. A check mark beside a toolbar indicates that toolbar is shown in the PSAT window. Click on the check mark box to turn it on and off. This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

46

PSAT User Manual

Show Tooltips

Click on this checkmark box to turn the tooltips on and off. When on, positioning the cursor on any button in the toolbars will show the description of that button.

Cool Look

Click on this checkmark box to toggle the appearance of the buttons in the toolbars.

New…

Adds a new toolbar after you are asked to type in a name for it.

Reset

After you select a toolbar by clicking on it in the list, clicking Reset puts its buttons back to the original setting.

Delete

After you select an added (new) toolbar by clicking on it in the list, Reset button is replaced by Delete button, which deletes that toolbar.

The Commands tab shows the list of toolbars under Categories (on the left) and the buttons of each toolbar under Buttons (on the right). Click on each toolbar on the left to see its buttons on the right. Click on each button on the right to see its description in the lower part of the dialog. To add any button to a toolbar, drag it from this dialog and drop it in the toolbar in PSAT window. To remove a button from a toolbar, while this dialog is open, drag it off that toolbar in PSAT window and drop it anywhere. OK button will closes the dialog.

8.20 Set Bus Dialogs Several commands and dialogs require you to specify an AC or a DC bus in the Set AC Bus, Set Remote Bus or Set DC Bus dialogs, which have similar features. These dialogs give the list of existing buses from which you can select one bus. Double click on a bus in the list, or click on the bus and then OK button, to select it and close the dialog. The list initially shows all the buses in the case. The Subsystem pull-down list allows you to limit the list to the buses in a simple or composite subsystem. All the subsystems that you have defined (as described in section 8.10 and 8.11) appear in the Subsystem pull-down list and you can select one by clicking on it. The columns of the bus list are similar to those in the AC Bus or DC Bus data table and can be customized in the same way. Click on a column heading to sort the table by that column. Click again to switch between ascending and descending sort. Right click on the heading row and select Customize Columns… from the pop-up menu to open the Customization dialog. Rearrange, show, hide and freeze columns in this dialog as described in section 8.12. In the Search box, type in a Number or Name to find a bus in the list. As you type the number or name, the list scrolls and highlights the matching bus for you to select. For example as you type ABC, the first bus that has a name starting with ABC is highlighted (the Number field is grayed out in the Set DC Bus dialog). In some cases, additional boxes and keys appear in this dialog (e.g., Set to Ground or Set to Infinity). These are described along with the related dialogs in chapter 9.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

47

PSAT User Manual

8.21 Set Area, Zone, Owner Dialogs Some commands and dialogs require you to specify an area, a zone or an owner in the Set Area, Set Zone or Set Owner dialog. These dialogs give the list of existing areas, zones or owners from which you can select one. Double click on an area (zone, owner) in the list, or click on the area (zone, owner) and then OK button, to select it and close the dialog. The list initially shows all the areas (zones, owners) in the case. The Subsystem pull-down list allows you to limit the list to the areas (zones, owners) in a simple or composite subsystem. All the subsystems that you have defined (as described in section 8.10 and 8.11) appear in the Subsystem pull-down list and you can select one by clicking on it. The columns of the list are similar to those in the Area (Zone, Owner) data table and can be customized in the same way. Click on a column heading to sort the table by that column. Click again to switch between ascending and descending sort. Right click on the heading row and select Customize Columns… from the pop-up menu to open the Customization dialog. Rearrange, show, hide and freeze columns in this dialog as described in section 8.12. In the Search box, type in a Number or Name to find an area (zone, owner) in the list. As you type the number or name, the list scrolls and highlights the matching area (zone, owner) for you to select. For example as you type ABC, the first area (zone, owner) that has a name starting with ABC is highlighted. The New Area (New Zone, New Owner) button adds a new area (zone, owner) to the case, similar to using the Insert New Row command of the Edit Menu for the Area (Zone, Owner) data table.

8.22 Bus Connections Dialog The Edit Bus Connections… command of the Edit menu opens this dialog, which shows the Number, Name and other attributes of a selected bus and all its connections. The Area, Zone and Owner boxes have a browse button beside them, which open the Set Area/Zone/Owner dialogs to change these attributes of the bus as you would in the AC Bus Property dialog. The list of connected components shows their type, ID, and depending on the type:

   

Bus 1 is the terminal bus, From-bus of 2-terminal branch, Primary-bus of 3-winding transformer or DC Bus 1 Bus 2 is the To-bus of 2-terminal branch, Secondary-bus of 3-winding transformer or DC Bus 2 Bus 3 is the Tertiary-bus of 3-winding transformer, AC Bus of converter or AC Bus 1 of VSC Bus 4 is AC Bus 2 of VSC

Select a component in the list and click Properties button to open its property dialog or click Delete button to delete the selected component from the powerflow data. To connect a new element to the bus, click Add button. This opens the Select Element dialog which has a pulldown list of all component types. After selecting a component (generator, load, etc.) from this list, close this dialog by clicking OK. The new component appears in the list above. You need then to select this component in the list and click Properties button to open its property box and enter the required data for it. Close button closes this dialog.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

48

PSAT User Manual

8.23 Sectional Branch Dialog After you select a sectional branch in the Sectional Branch data table, or one of the sections in the Line, Transformer or other data tables, the Sectional Branch Properties command of the Edit menu opens the Sectional Branch dialog to view and modify the sections of that branch. This dialog shows the following information for the selected sectional branch: From-Bus:

Terminal bus at the “From” end.

To-Bus:

Terminal bus at the “To” end.

ID:

8 character identifier.

Status:

In-service or Out-of-service status.

Sections list:

Section Number (1, 2, …) and type (line, fixes series compensator, etc.) of the sections.

To move the branch to another From (or To) bus, click the browse button beside the From (or To) bus to open the Set AC Bus dialog and select another bus. The other buttons in this dialog are: Up:

Moves a selected section before the previous section and renumbers the sections accordingly. To move a section, first select it in the list by clicking on it, then click the Up (Down) button. Note that this command actually changes the branch combination since sections are connected in the sequence of their Sections Number (starting with Section 1 at the From bus).

Down:

Moves a selected section after the next section and renumbers the sections accordingly.

Add:

Adds a new section to the branch. It first opens the Select Branch dialog (described below) for you to select the type of the section to be added.

Delete:

Deletes a selected section from the branch. To select a section first, click on it in the Sections list.

Properties button:

Opens the property dialog of a selected section. To select a section first, click on it in the Sections list

Close:

Closes the dialog.

8.24 Select Branch Dialog When you select a non-sectional branch in the Line, Transformer or other data tables, the Sectionalize command of the Edit menu opens the Select Branch dialog for adding a section to that branch (making it sectional). The Add button of the Sectional Branch dialog and the Sectionalize wand of SLD Toolbox also open the Select Branch dialog to add another section to the existing sections of the branch.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

49

PSAT User Manual

The Select Branch dialog has a pull-down list of all branch types. After selecting a branch type (line, fixed series compensator, etc.) from this list, close this dialog by clicking OK. This adds the new section and opens the Sectional Branch dialog to view and modify the sections. Select the new section in the Sectional Branch dialog and click Properties button to open its property box and enter the required data for it. You may then rearrange the sections and add new sections as described above.

8.25 Composite Label Dialog When you add a new composite label to a diagram by using the SLD toolbox, or double click on an existing composite label, the Composite Label Properties dialog appears to set the properties of the label. Under the Settings tab, you select the subsystem to which the label applies, and the quantities such as total generation, load, etc., that will appear in the label. Each quantity that you select by clicking on listed items (where a check mark appears) will be included in a separate line in the composite label. Under the Text tab, you can change (type in) the text that appears in the label with each selected quantity and set the alignments. The quantities themselves are shown as #VALUE n# in this Text box. You can also specify the line, fill and font of the composite label under the corresponding tabs in this dialog.

8.26 Interface Label Dialog When you add a new interface label to a diagram by using the SLD toolbox, or double click on an existing interface label, the Interface Label Properties dialog appears to set the properties of the label. Under the Settings tab, you select the interface quantities such as total From Side Flow (MW), etc., that will appear in the label. Each quantity that you select by clicking on listed items (where a check mark appears) will be included in a separate line in the interface label. Under the Text tab, you can change (type in) the text that appears in the label with each selected quantity and set the alignments. The quantities themselves are shown as #VALUE n# in this Text box. Under the Definition tab, you can specify branches that the interface is comprised of or import an interface definition file from VSAT. You can also specify the line, fill and font of the interface label under the corresponding tabs in this dialog.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

50

PSAT User Manual

9 Models and Properties This chapter describes the model and attributes of powerflow components. These attributes are displayed in the Property dialogs under one or more tabs. They are also shown in the Data tables where you can choose to show or hide the column of each attribute by customizing the table. The Property dialog appears when you double click on a component in a Data table or double click on its symbol in a Diagram.



Commutated ConvertersAC

Bus

All AC components, such as generator, load, shunt, line, transformer, etc. are connected together only at AC buses. These components are identified by their bus, along with their ID. AC buses are represented by a thick line (bar) in the Bus Tree and diagrams. The attributes of an AC bus in the powerflow data are the following: Number:

Unique integer (positive) number used to identify the bus.

Name:

Name (up to 16 characters), used to identify the bus (may or may not include kV). The bus names should be unique in order to identify the buses by name rather than by number.

Base kV:

Base (nominal) kV of the bus.

Type:

The bus type can be one of the following: Load bus: all generators at a Load bus are assumed to be out-of-service (even if their status is in-service) and ignored during powerflow solution. Gen. bus: generators at a Generator bus are not ignored during powerflow solution unless their status is out-of-service. Swing bus: is a Generator bus which, during powerflow solution, its voltage angle remains fixed and MW output of its generators are computed and set by powerflow solution to result in zero net generation-load-loss in the system. Note that the voltage magnitude of a swing bus does not remain fixed and its MVAr generation is not unlimited (unless its generators have Open-MVAr-Limits). Therefore, in a solved powerflow case, if a Swing bus is changed to a Generator bus and vice-versa, the case still remains a solved case. Out of service bus: all connected components of an out of service bus are ignored during powerflow solution (they must have out-of-service status). In the Property dialog, you can modify the bus Type by selecting an item from its pull-down list.

Voltage Magnitude:

Magnitude (in pu) of bus voltage. This would be the initial value for powerflow solution. It will be replaced by the final value after a powerflow solution.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

51

PSAT User Manual

Voltage Angle:

Phase angle (in degrees) of bus voltage. This would be the initial value for powerflow solution. It will be replaced by the final value after a powerflow solution.

Area:

Area of the bus. A bus can belong to only one area. In the Property dialog, to modify the Area of the bus, click on the browse button (. . .) beside it. The Set Area dialog appears where you can select an existing area or create a new area.

Zone:

Zone of the bus. The zones may cross the area boundaries (buses of a zone may belong to more than one area and vice-versa). In the Property dialog, to modify the Zone of the bus, click on the browse button (. . .) beside it. The Set Zone dialog appears where you can select an existing zone or create a new zone.

Owner:

Owner of the bus (identified by a 16-character name). In the Property dialog, to modify the Owner of the bus, click on the browse button (. . .) beside it. The Set Owner dialog appears where you can select an existing owner or create a new owner.

9.2 Generator Generators are sources of MW and MVAr power and can control the voltage of the generator terminal bus or a remote bus during powerflow solution. Generators are represented by a circle in the Bus Tree and diagrams. The generator model may include a step-up transformer in addition to the machine‟s impedance. The machine impedance and step-up transformer are ignored in powerflow solution and the MW/MVAr output of the generator are injections at the terminal bus. During powerflow solution, each generator controls a bus voltage as long as its MVAr output remains within limits. Otherwise, the MVAr output will remain fixed at the limit and the bus voltage will not be controlled by this generator. If the “Open MVAr Limit” of a generator is Yes, its MVAr limits are ignored (considered unlimited). Also, if the solution parameter “Generator MVAr Limits” is unchecked, the MVAr limits of all generators are ignored. If a generator controls a remote bus voltage, a scheduled voltage must be specified for that bus. Whether or not a generator controls a remote bus, a voltage range (Vlo:Vhi) must be specified for its local (terminal) bus. Vlo can be set equal to Vhi in order to control the terminal voltage at a fixed value. If, in order to control a remote bus, the local voltage exceeds Vhi (or drops below Vlo), the remote control will be ignored and the local voltage will be controlled at Vhi (or Vlo). All the generators of one bus control the voltage of the same local or remote bus. When generators of more than one bus control the same remote bus, the reactive power generation of each bus (not its individual generators) compared to other buses will be in proportion to the MVAr Share % of its generators, unless the remote control is abandoned by one bus when all of its generators reach their MVAr limit or the local bus voltage reaches its limit. All generators of one bus must have the same desired voltage and MVAr Share %, as well as the same remote bus. The distribution of MVAr output among the generators of each bus is in proportion to their MW output, within their individual MVAr limits (when one generator reaches its limits, its remaining share of total MVAr goes to other generators). If the MW outputs are zero, the distribution of MVAr is in proportion to the generator base MVA. The attributes of a generator, shown under the Main and Impedance tabs of Generator Properties dialog, are the following:

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

52

PSAT User Manual

Bus:

Generator terminal bus. This bus must exist in the powerflow data. To move a generator from one bus to another bus, click on the browse button (. . .) beside the bus number/name to open the Set AC Bus dialog, select the destination bus in that dialog and click the OK button.

ID:

An 8-character identifier, used to distinguish different generators connected to the same bus.

Status:

In-service, Out-of-service, or Not Available status. Generators that are „Not Available‟ cannot be put back in service during transaction analysis. Note that at the Load-type buses, even In-service generators are always considered to be out of service.

Base MVA:

Base MVA of the generator.

MW output:

Real power output of the generator.

Maximum MW:

Maximum real power output.

Minimum MW:

Minimum real power output.

MVAr output:

Reactive power output of the generator. It is computed and set by powerflow solution.

Maximum MVAr:

Maximum reactive power output.

Minimum MVAr:

Minimum reactive power output.

Open MVAr Limits:

When set to Yes, the maximum and minimum MVAr limits are ignored in powerflow solution.

Vt Upper Limit:

Upper limit of terminal bus voltage (in pu).

Vt Lower Limit:

Lower limit of terminal bus voltage (in pu).

Remote Controlled bus:

Remote bus whose voltage is controlled by the generator. It could be any bus in the powerflow data and may be controlled by more than one device. To change the remote bus, click on the browse button (. . .) beside it to open the Set Controlled Bus dialog, select the desired bus in that dialog and click the OK button. To remove the existing remote bus, click on the browse button (. . .) beside it to open the Set Controlled Bus dialog and click the Remove Bus button in that dialog.

Desired Vr:

Desired (scheduled) voltage (in pu) for the remote controlled bus. If there are other generators or switchable shunts controlling the same remote bus, the specified desired voltage should be the same for all of them.

MVAr Share %:

Share (Contribution) of all generators at this bus, compared to other buses, in providing reactive power for control of the same remote bus voltage. The MVAr Share % of all buses with the same remote bus are scaled to 100 during powerflow solution.

Generator Resistance and Reactance:

Generator internal impedance (in pu of generator base MVA).

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

53

PSAT User Manual

Transformer Resistance and Reactance:

Step-up transformer impedance (in pu of generator base MVA).

Transformer Turns Ratio:

Step-up transformer off-nominal turns ratio (in pu).

GWMOD:

Wind machine control mode:

GWPF:

1.

Not a wind machine.

2.

Wind machine whose reactive power limits are specified by MVAr limits.

3.

Wind machine whose reactive power limits are determined from the machine‟s active power output and GWPF; limits are of equal magnitude and opposite sign.

4.

Wind machine with a fixed reactive power setting determined from the machine‟s active power output and GWPF; when GWPF is positive, the machine‟s reactive power has the same sign as its active power; when GWPF is negative, the machine‟s reactive power has the opposite sign of its active power.

Wind machine power factor

The Generator Properties dialog also shows the type and base kV of the generator bus as well as its voltage and the voltage of remote controlled bus (for comparison with the upper/lower limits and desired value).

9.3 Load Loads are consumers of MW and MVAr power (positive MVAr load is an inductive load). They are represented by an arrow in the Bus Tree and diagrams. Each bus may have several loads. Each load consists of 5 components and each component has a model (type) as described below. The nominal load is the sum of the real (MW) and reactive (MVAr) part of the 5 components at nominal voltage (1 pu). The actual load is the sum of these components computed at the current bus voltage. The reference load is a user-specified value (initially set to the nominal load) used for converting loads as described in section 10.7. The attributes of a load, shown under the Main and Load Components tabs of Load Properties dialog, are the following: Bus:

Load terminal bus. This bus must exist in the powerflow data. To move a load from one bus to another bus, click on the browse button (. . .) beside the bus number/name to open the Set AC Bus dialog, select the destination bus in that dialog and click the OK button.

Owner:

Owner of the load. To change the owner of the load, click on the browse button (. . .) beside the owner number/name to open the Set Owner dialog, select the new owner in that dialog and click the OK button.

ID:

An 8-character identifier, used to distinguish different loads connected to the same bus.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

54

PSAT User Manual

MW Reference:

Reference real load, used for Load Conversion.

MVAr Reference:

Reference reactive load, used for Load Conversion.

Status: Scalable: Load Name:

Load status (1- In service; 0- Out of service). Controls if load should be adjusted when performing load scaling (section 10.4) or if load is fixed. (Yes = Scalable; No = Fixed). 16 characters long characteristic name. This name is not required to be unique.

For Component 1 to 5: Real Part:

Real part of the component (P0) in MW at nominal (1 pu) voltage.

Reactive Part:

Reactive part of the component (Q0) in MVAr at nominal (1 pu) voltage (positive for inductive load components).

Model:

Model of the component. To change the model of a component, click on its pull-down list and select one of the following: (P = P0 Q = Q0)  Constant PQ (P = P0V Q = Q0V)  Constant Current (P = Q = Q0V2)  Constant Impedance 2 P0V  Model number "k" represented in the Load Model table  Out (the component is ignored)

The Load Properties dialog also shows the type of load bus and the actual and nominal values of the load (sum of its 5 components). To view and modify the load models or to add a new one, click on the Add/View Load Models button to open the Load Model dialog.

9.4 Load Model The model of load components with a positive “model number” are specified in the load model data. A component with load model k>0 is represented as: P = P0 (A1k VN1k + A2k VN2k + A3k VN3k) Q = Q0 (B1k VM1k + B2k VM2k + B3k VM3k) where P0 and Q0 are specified as part of load data described above and A1 , A2 , A3 , N1 , N2, N3 , B1 , B2 , B3 , M1 , M2 and M3 are parameters of the model number k specified in the load model data. Note that for these components, the “nominal” MW and MVAr load are P 0 (A1k+ A2k+ A3k) and Q0 (B1k+ B2k + B3k) (not P0 and Q0 which are specified in the load data). The attributes of each load model are: Model number:

The positive integer number.

P Coefficients:

Three real numbers specifying A1 , A2 , A3.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

55

PSAT User Manual

P Exponents:

Three real numbers specifying N1 , N2, N3.

Q Coefficients:

Three real numbers specifying B1 , B2 , B3.

Q Exponents:

Three real numbers specifying M1 , M2 , M3.

The Add/View Load Models button in Load Properties dialog and Convert Load Model dialog opens the Load Models Dialog, which shows the parameters of existing load models. To view a load model in this dialog, select its number from the Model Number pull-down list and to modify its parameters, type in new values in the parameter boxes. To add a new load model, after typing a new number in the New Model Number box, click Add button. This creates a new model, which appears with all-zero parameters and you need to type in the value of its parameters in the edit boxes. Click Close button to close this dialog.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

56

PSAT User Manual

9.5 Fixed Shunt Fixed shunts are constant admittances connected to AC buses. They are represented by an inductor or capacitor symbol in the Bus Tree and diagrams. Each bus may have several fixed shunts. The attributes of each fixed shunt are: Bus:

Shunt terminal bus. This bus must exist in the powerflow data. To move a shunt from one bus to another bus, click on the browse button (. . .) beside the bus number/name to open the Set AC Bus dialog, select the destination bus in that dialog and click the OK button.

Owner:

Owner of the shunt. To change the owner, click on the browse button (. . .) beside the owner number/name to open the Set Owner dialog, select the new owner in that dialog and click the OK button.

ID:

8 character identifier to distinguish among multiple shunts at the same bus.

MW Shunt:

Shunt conductance in MW at nominal (1 pu) voltage.

MVAr Shunt:

Shunt susceptance in MVAr at nominal (1 pu) voltage. A positive susceptance represents a capacitor.

Status:

Fixed Shunt status (1- In service; 0- Out of service).

Name:

16 characters long characteristic name. This name is not required to be unique.

The Fixed Shunt Properties dialog also shows the type of shunt bus.

9.6 Switchable Shunt Switchable shunts are variable admittances connected to AC buses. In the Bus Tree and diagrams, they are represented by an inductor or capacitor symbol with an arrow. Each bus may have several switchable shunts. Each switchable shunt may have up to 8 blocks of shunt banks and each block may have up to 99 identical banks (steps). The inductive banks must be specified before the capacitive banks. These are switched in and out in the ordered specified (i.e., banks in block k are switched in before banks in block k+1; banks in block k+1 are switched out before banks in block k). All inductive banks are switched out before capacitive banks are switched in and viceversa. During powerflow solution, each type of switchable shunt can control a bus voltage by varying its admittance (switching the shunt banks in and out). If a shunt controls a remote bus voltage, a scheduled voltage must be specified for that bus. Whether or not a shunt controls a remote bus, a voltage range (Vlo:Vhi) must be specified for its local (terminal) bus. Vlo can be set equal to Vhi in order to control the terminal voltage at a fixed value. If, in order to control a remote bus, the local voltage exceeds Vhi (or drops below Vlo), the remote control will be ignored and the local voltage will be controlled at Vhi (or Vlo). When shunts of several buses control the same remote bus, the admittance of each shunt compared to other shunts will be in proportion to its MVAr Share %, unless the remote control is abandoned by one shunt when it reaches its maximum or minimum admittance, or the local bus voltage reaches its limit. All shunts of one bus must have the same desired voltage and MVAr Share %, as well as the same remote bus. This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

57

PSAT User Manual

Discrete shunts change their admittance by switching one bank at a time. During the solution, the admittance may first change continuously, but then it is fixed at the nearest step (bank size). Continuous shunts change their admittance continuously between Ymin (sum of all inductive banks) and Ymax (sum of all capacitive banks). Similarly, SVCs move continuously while holding the local bus voltage on the droop characteristic (specified by straight line from Ymin-Vhi to Ymax-Vlo). . The attributes of each switchable shunt, shown under the Main and Shunt Blocks tabs of Switchable Shunt Properties dialog, are the following: Bus:

Shunt terminal bus. This bus must exist in the powerflow data. To move a shunt from one bus to another bus, click on the browse button (. . .) beside the bus number/name to open the Set AC Bus dialog, select the destination bus in that dialog and click the OK button.

Owner:

Owner of the shunt. To change the owner, click on the browse button (. . .) beside the owner number/name to open the Set Owner dialog, select the new owner in that dialog and click the OK button.

ID:

8 character identifier to distinguish among multiple switchable shunts at the same bus.

Status:

In-service or Out-of-service status.

Control Mode:

Shunt control mode or type. To change the control mode, click on its pull-down list and select one of the following:  Frozen  Discrete  Continuous  SVC Conductance in MW at unity (1 pu) voltage. The conductance remains fixed when shunt banks are switched in and out.

Nominal MW:

Nominal MVar:

Susceptance of switched-in shunt banks in MVAr at unity (1 pu) voltage. Susceptance is positive for capacitors. For frozen and discrete shunts, this value must agree with the value and order of the shunt banks. For continuous shunts and SVC, this can be any value within Bmin (sum of inductors) and Bmax (sum of capacitors).

Vt Upper Limit:

Upper limit of terminal bus voltage (in pu).

Vt Lower Limit:

Lower limit of terminal bus voltage (in pu).

Remote Controlled bus:

Remote bus whose voltage is controlled by the shunt. It could be any bus in the powerflow data and may be controlled by more than one device. To change the remote bus, click on the browse button (. . .) beside it to open the Set Controlled Bus dialog, select the desired bus in that dialog and click the OK button. To remove the existing remote bus, click on the browse button (. . .) beside it to open the Set Controlled Bus dialog and click the Remove Bus button in that dialog.

Desired Vr:

Desired (scheduled) voltage (in pu) for the remote controlled bus. If there are other generators or switchable shunts controlling the same remote bus, the specified desired voltage should be the same for all of them.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

58

PSAT User Manual

MVAr Share %:

Share (Contribution) of the shunt, compared to other shunts, in providing reactive power for control of the same remote bus voltage. The MVAr Share % of all shunts with the same remote bus are scaled to 100 during powerflow solution.

Name:

16 characters long characteristic name. This name is not required to be unique.

For Block 1 to 8: Number of Steps:

Number of steps (banks) in the block.

MVAr per Step:

Susceptance of each step (bank) in the block in MVAr at unity (1 pu) voltage. All inductive blocks (negative MVar) must be specified first, followed by all capacitive blocks (positive MVAr). All blocks after the first one with “Number of Steps”=0 are ignored.

The Switchable Shunt Properties dialog also shows the type of the shunt bus as well as its voltage and the voltage of remote controlled bus (for comparison with the upper/lower limits and desired value).

9.7 AC Line AC transmission lines are connected between a pair of AC buses, individually or as a section of a sectional branch. They are represented by a simple line in the Bus Tree and diagrams. The attributes of each AC line, shown under Main and MVA Ratings tabs in Line Properties dialog, are the following: From-Bus:

Terminal bus at the “From” end. This bus must exist in the powerflow data.

To-Bus:

Terminal bus at the “To” end. This bus must exist in the powerflow data. To connect the line to a different From or To bus, click on the browse button (. . .) beside the bus number/name to open the Set AC Bus dialog, select the new bus in that dialog and click the OK button.

ID:

8 character identifier to distinguish among parallel lines.

Section:

Section number of the line if it belongs to a sectional branch. It will be 0 (blank in the Line table) if the line is not a section of a sectional branch. Sections of a sectional branch must have the same From-bus, To-bus (in the same order) and ID, and consecutive Section numbers (1, 2, . . .) starting from 1 for the section at the From-bus.

Status:

In-service or Out-of-service status.

Meter end:

Metered end, which can be set to one of the following:  From  To

Resistance:

Series resistance in pu.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

59

PSAT User Manual

Reactance:

Series reactance in pu.

Charging:

Charging (shunt) conductance and susceptance in pu.

From-Shunt:

Conductance and susceptance in pu, representing a shunt at the From-bus.

To-Shunt:

Conductance and susceptance in pu, representing a shunt at the To-bus

MVA Ratings 1 to 6:

Thermal ratings of the line in MVA at nominal (1 pu) voltage.

Rating Group:

An integer number representing the rating group.

Length:

Line length in miles.

The Line Properties dialog also shows the MW, MVAr and current (A) flows at the From and To buses (flows entering the line from each bus) under the Flows tab. For description of Sectional Branches and how to add, remove and modify the sections, see section 9.23.

9.8 Fixed Transformer Fixed-tap transformers and fixed-angle phase shifters are connected between a pair of AC buses, individually or as a section of a sectional branch. They are represented by a two-inductor symbol in the Bus Tree and diagrams. The model of a fixed transformer or phase shifter consists of an ideal transformer on the From side and a series impedance on the To side, as well as magnetizing admittances at the From and To buses and shunt (charging) admittance. The attributes of each fixed transformer, shown under Main and MVA Ratings tabs in Fixed Transformer Properties dialog, are the following: From-Bus:

Terminal bus at the “From” end. This bus must exist in the powerflow data.

To-Bus:

Terminal bus at the “To” end. This bus must exist in the powerflow data. To connect the transformer to a different From or To bus, click on the browse button beside the bus number/name to open the Set AC Bus dialog, select the new bus in that dialog and click the OK button.

ID:

8 character identifier to distinguish among parallel fixed transformers.

Section:

Section number of the transformer if it belongs to a sectional branch. It will be 0 (blank in the Transformer table) if the transformer is not a section of a sectional branch. Sections of a sectional branch must have the same Frombus, To-bus (in the same order) and ID, and consecutive Section numbers (1, 2, . . .) starting from 1 for the section at the From-bus. Note that a sectional branch cannot have more than one fixed or adjustable transformer or static tap changer/phase regulator.

Status:

In-service or Out-of-service status.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

60

PSAT User Manual

Base MVA:

Rated (base) MVA. Note that pu impedance and admittances are in the system MVA base, not the transformer base MVA.

Meter end:

Metered end, which can be set to one of the following:  From  To

Tap Ratio:

Off-nominal turns ratio (From side to To side) in pu.

Phase Shift:

Phase shift angle (phase angle of From side minus To side at no load) in degrees.

Resistance:

Series resistance in pu.

Reactance:

Series reactance in pu.

From-Magnetizing:

Magnetization conductance and susceptance in pu at the From-bus.

To-Magnetizing:

Magnetization conductance and susceptance in pu at the To-bus.

Charging:

Charging (shunt) conductance and susceptance in pu.

MVA Ratings 1 to 6:

Thermal ratings of the transformer in MVA at nominal (1 pu) voltage.

Rating Group:

An integer number representing the rating group.

Name:

16 characters long characteristic name. This name is not required to be unique.

Owner:

16 characters long transformer owner.

The Fixed Transformer Properties dialog also shows the MW, MVAr and current (A) flows at the From and To buses (flows entering the transformer from each bus) under the Flows tab.

9.9 Adjustable Transformer The 2-winding tap-changing transformers and angle-changing phase shifters are connected between a pair of AC buses, individually or as a section of a sectional branch. They are represented by a two-inductor symbol with an arrow in the Bus Tree and diagrams. The model of an adjustable transformer consists of an ideal transformer with variable tap ratio or phase shift on the From side, a fixed-tap ideal transformer on the To side, a series impedance between them, as well as magnetizing admittances at the From and To buses and shunt (charging) admittance. A tap-changer can control the voltage of a bus or its own MVAr flow by adjusting the From-side turns ratio within limits. A phase-shifter can control its own MW flow by adjusting its phase shift angle within limits. The attributes of each adjustable transformer, shown under Main, Impedances, Controls and MVA Ratings tabs in Adjustable Transformer Properties dialog, are the following: From-Bus:

Terminal bus at the “From” end. This bus must exist in the powerflow data.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

61

PSAT User Manual

To-Bus:

Terminal bus at the “To” end. This bus must exist in the powerflow data. To connect the transformer to a different From or To bus, click on the browse button beside the bus number/name to open the Set AC Bus dialog, select the new bus in that dialog and click the OK button.

ID:

8 character identifier transformers.

to

distinguish

among

parallel

adjustable

Section:

Section number of the transformer if it belongs to a sectional branch. It will be 0 (blank in the Transformer table) if the transformer is not a section of a sectional branch. Sections of a sectional branch must have the same From-bus, To-bus (in the same order) and ID, and consecutive Section numbers (1, 2, . . .) starting from 1 for the section at the From-bus. Note that a sectional branch cannot have more than one fixed or adjustable transformer or static tap changer/phase regulator.

Status:

In-service or Out-of-service status.

Base MVA:

Rated (base) MVA. Note that pu impedance and admittances are in the system MVA base, not the transformer base MVA.

Meter end:

Metered end, which can be set to one of the following:  From  To

From-Side Tap Ratio:

Off-nominal turns ratio of the From side in pu.

To-Side Tap Ratio:

Off-nominal turns ratio of the To side in pu.

Maximum Ratio:

Maximum of From side tap ratio in pu.

Minimum Ratio:

Minimum of From side tap ratio in pu.

Ratio Step:

Step size, for From side tap ratio adjustment, in pu.

Phase Shift Angle:

Phase shift angle (phase angle of From side minus To side at no load) in degrees.

Maximum Ph. Sh.:

Maximum of phase shift angle in degrees.

Minimum Ph. Sh.:

Minimum of phase shift angle in degrees.

Resistance:

Series resistance in pu.

Reactance:

Series reactance in pu. For transformers with Impedance Correction Table, resistance and reactance values specify the reference impedance. The actual impedance will depend on the tap ratio or the phase shift angle.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

62

PSAT User Manual

Correction Table:

Number of the Impedance Correction Table. To choose one of the existing correction tables, click on the pull-down list and select a table number. To specify no correction table (remove the specified number), choose the blank (first) item in the pull-down list. To view or modify the correction tables or add a new one, click on the Add/View Correction Tables button to open the Impedance Correction Tables Dialog.

From-Magnetizing:

Magnetization conductance and susceptance in pu at the From-bus.

To-Magnetizing:

Magnetization conductance and susceptance in pu at the To-bus.

Charging:

Charging (shunt) conductance and susceptance in pu.

Control Flag:

Control flag, which can be set to one of the following:  Enabled  Disabled Tap ratio or phase angle of Enabled transformers will be adjusted in powerflow solution if the corresponding solution parameter is set. Tap ratio and phase angle of Disabled transformers will remain fixed.

Control Variable:

Control variable, which can be set to one of the following:  Voltage  Real Power (MW flow)  Reactive Power (MVAr flow)

Control Side:

Control side, which can be set to one of the following:  From  To For voltage control of a remote bus, this indicates whether that bus is on the From side or To side. For MW or MVAr flow control, this indicates whether the flow is measured at the From side or To side, but always in the From-to-To direction.

Controlled Bus:

Controlled bus (for voltage control). It can be the From-bus, To-bus or a remote bus. To change the controlled bus, click on the browse button (. . .) beside it to open the Set Controlled Bus dialog, select the desired bus in that dialog and click the OK button. To remove the existing controlled bus, click on the browse button (. . .) beside it to open the Set Controlled Bus dialog and click the Remove Bus button in that dialog.

Upper Voltage Limit:

Upper limit for controlled bus voltage in pu.

Lower Voltage Limit:

Lower limit for controlled bus voltage in pu.

Upper MVAr Limit:

Upper limit for controlled reactive power in MVAr.

Lower MVAr Limit:

Lower limit for controlled reactive power in MVAr.

Upper MW Limit:

Upper limit for controlled real power in MW.

Lower MW Limit:

Lower limit for controlled real power in MW.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

63

PSAT User Manual

MVA Ratings 1 to 6:

Thermal ratings of the transformer in MVA at nominal (1 pu) voltage.

Rating Group:

An integer number representing the rating group.

Name:

16 characters long characteristic name. This name is not required to be unique.

Owner:

16 characters long transformer ownership name.

The Adjustable Transformer Properties dialog also shows the voltage of the controlled bus and MW/MVAr flows (for comparison with the upper/lower limits), as well as the MW, MVAr and current (A) flows at the From and To buses (flows entering the transformer from each bus) under the Flows tab.

9.10 Impedance Correction Table The impedance correction tables specify the factors for correcting the series impedance of adjustable transformers as a piece-wise linear function of turns ratio or phase shift angle. The actual impedance is determined by multiplying the reference impedance by the corresponding correction factor. Each table is specified by a minimum of two and maximum of eleven points and it will be a function of either turns ratio or phase shift angle (not both). The attributes of each Impedance Correction Table are the following: Table Number:

Number to identify each impedance correction table.

For Points 1 to 11: Ratio or Ph.Sh.:

Turns ratio in pu or phase shift angle in degrees.

Correction Factor:

Correction factor for the corresponding turns ratio or phase shift angle.

If a table is specified by, for example, 8 points, the last three points appear as zero and will be ignored. Turns ratio and phase shift angle of the specified points must be monotonically increasing and their factor must be positive. If the correction factors are for phase shift, the angle of the first point must be less than 0.5 or the angle of the last specified point must be greater than 1.5, otherwise these points are considered to be turns ratios.

Impedance Correction Tables Dialog: The Add/View Correction Tables button in transformer properties dialogs open this dialog, which shows the data of existing correction tables. To view or modify a correction table, select its number from the Table Number pull-down list. The points in the selected table appear in the list below and you can type in new values for each point. In addition, this dialog shows the type of each Impedance Correction table beside its Number. The type is Ratio if correction factors correspond to turns ratio, or Phase Shift: if correction factors correspond to phase shift. To add a new correction table, click Add New Table button. This opens a dialog for you to type in a new number and click OK. The new correction table appears with all-zero data and you need to type in at least two pairs (number 1 and 2) of non-zero Ratio or Phase Shift and Correction Factors for the new table. Click Close button to close this dialog.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

64

PSAT User Manual

9.11 Three Winding Transformer The three winding transformers are connected between three AC buses. They are represented by a three-inductor symbol in the Bus Tree and diagrams. The model of a 3-W transformer consists of three ideal transformers (with off-nominal turns ratio and phase shift angle) at the three terminals, three series impedances in Star connection, as well as three magnetizing admittances at the terminals and three shunt (charging) admittances for the windings. The turns ratio of one of the windings can be variable to control the voltage of a bus. The attributes of each 3-W transformer, shown under Main, Impedances, Controls and MVA Ratings tabs in Three Winding Transformer Properties dialog, are the following: Primary Bus:

Terminal bus of the primary winding. powerflow data.

This bus must exist in the

Secondary Bus:

Terminal bus of the secondary winding. powerflow data.

This bus must exist in the

Tertiary Bus:

Terminal bus of the tertiary winding. powerflow data.

This bus must exist in the

To connect the transformer to a different Primary, Secondary or Tertiary bus, click on the browse button beside the bus number/name to open the Set AC Bus dialog, select the new bus in that dialog and click the OK button. ID:

8 character identifier to distinguish among parallel 3-W transformers.

Status:

In-service or Out-of-service status of windings, which can be set to one of the following:  In : All windings in-service  Out : All windings out-of-service  Pri. out : Primary winding out-of-service  Sec. out : Secondary winding out-of-service  Ter. out : Tertiary winding out-of-service

Base MVA:

Rated (base) MVA. Note that pu impedance and admittances are in the system MVA base, not the transformer base MVA.

Non-meter end:

Non-metered terminal, which can be set to one of the following:  Primary  Secondary  Tertiary The other two terminals are metered.

Primary’s: Tap Ratio:

Off-nominal turns ratio of the primary winding in pu.

Phase Shift:

Phase shift angle of the primary winding in degrees.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

65

PSAT User Manual

Secondary’s: Tap Ratio:

Off-nominal turns ratio of the secondary winding in pu.

Phase Shift:

Phase shift angle of the secondary winding in degrees.

Teriary’s: Tap Ratio:

Off-nominal turns ratio of the tertiary winding in pu.

Phase Shift:

Phase shift angle of the tertiary winding in degrees.

Primary’s: Series Impedance:

Series resistance and reactance of the primary winding in pu.

Magnetization:

Magnetizing conductance and susceptance of the primary winding in pu.

Charging:

Charging conductance and susceptance of the primary winding in pu.

Secondary’s: Series Impedance:

Series resistance and reactance of the secondary winding in pu.

Magnetization:

Magnetizing conductance and susceptance of the secondary winding in pu.

Charging:

Charging conductance and susceptance of the secondary winding in pu.

Tertiary’s: Series Impedance:

Series resistance and reactance of the tertiary winding in pu.

Magnetization:

Magnetizing conductance and susceptance of the tertiary winding in pu.

Charging:

Charging conductance and susceptance of the tertiary winding in pu.

Primary’s: Correction Table:

Number of the Impedance Correction Table (similar to that of adjustable transformers). To choose one of the existing correction tables, click on the pull-down list and select a table number. To specify no correction table (remove the specified number), choose the blank (first) item in the pull-down list. To view the tables or add a new one, click on the “Add/View Correction Tables. . .” button. With an Impedance Correction Table, resistance and reactance values specified for the variable-tap winding are the reference impedance. The actual impedance will depend on the tap ratio or phase shift angle.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

66

PSAT User Manual

Voltage Controlled Bus:

Controlled bus (for voltage control). It can be one of the terminal buses or a remote bus. To change the controlled bus, click on the browse button (. . .) beside it to open the Set Controlled Bus dialog, select the desired bus in that dialog and click the OK button. To remove the existing controlled bus, click on the browse button (. . .) beside it to open the Set Controlled Bus dialog and click the Remove Bus button in that dialog.

Voltage Control Side:

Relative position of the remote controlled bus with respect to the variabletap winding, which can be set to one of the following:  Tap side  Impedance side

Control Variable Upper Limit:

Upper limit for controlled variable.

Control Variable Lower Limit:

Lower limit for controlled variable.

Control Flag:

Control flag, which can be set to one of the following:  Disabled  Voltage  MVAr  MW Tap ratio or phase angle of Enabled windings of 3-W transformers will be adjusted will be adjusted in powerflow solution if the corresponding solution parameter is set. Tap ratio and phase angle of Disabled windings of 3-W transformers will remain fixed.

Maximum:

Maximum tap ratio or phase shift angle.

Minimum:

Minimum tap ratio or phase shift angle.

Ratio Step:

Step size, for adjustment of variable tap, in pu.

Secondary’s: Correction Table:

Number of the Impedance Correction Table (similar to that of adjustable transformers). To choose one of the existing correction tables, click on the pull-down list and select a table number. To specify no correction table (remove the specified number), choose the blank (first) item in the pull-down list. To view the tables or add a new one, click on the “Add/View Correction Tables. . .” button. With an Impedance Correction Table, resistance and reactance values specified for the variable-tap winding are the reference impedance. The actual impedance will depend on the tap ratio or phase shift angle.

Voltage Controlled Bus:

Controlled bus (for voltage control). It can be one of the terminal buses or a remote bus. To change the controlled bus, click on the browse button (. . .) beside it to open the Set Controlled Bus dialog, select the desired bus in that dialog and click the OK button. To remove the existing controlled bus, click on the browse button (. . .) beside it to open the Set Controlled Bus dialog and click the Remove Bus button in that dialog.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

67

PSAT User Manual

Voltage Control Side:

Relative position of the remote controlled bus with respect to the variabletap winding, which can be set to one of the following:  Tap side  Impedance side

Control Variable Upper Limit:

Upper limit for controlled variable.

Control Variable Lower Limit:

Lower limit for controlled variable.

Control Flag:

Control flag, which can be set to one of the following:  Disabled  Voltage  MVAr  MW Tap ratio or phase angle of Enabled windings of 3-W transformers will be adjusted will be adjusted in powerflow solution if the corresponding solution parameter is set. Tap ratio and phase angle of Disabled windings of 3-W transformers will remain fixed.

Maximum:

Maximum tap ratio or phase shift angle.

Minimum:

Minimum tap ratio or phase shift angle.

Ratio Step:

Step size, for adjustment of variable tap, in pu.

Tertiary’s: Correction Table:

Number of the Impedance Correction Table (similar to that of adjustable transformers). To choose one of the existing correction tables, click on the pull-down list and select a table number. To specify no correction table (remove the specified number), choose the blank (first) item in the pull-down list. To view the tables or add a new one, click on the “Add/View Correction Tables. . .” button. With an Impedance Correction Table, resistance and reactance values specified for the variable-tap winding are the reference impedance. The actual impedance will depend on the tap ratio or phase shift angle.

Voltage Controlled Bus:

Controlled bus (for voltage control). It can be one of the terminal buses or a remote bus. To change the controlled bus, click on the browse button (. . .) beside it to open the Set Controlled Bus dialog, select the desired bus in that dialog and click the OK button. To remove the existing controlled bus, click on the browse button (. . .) beside it to open the Set Controlled Bus dialog and click the Remove Bus button in that dialog.

Voltage Control Side:

Relative position of the remote controlled bus with respect to the variabletap winding, which can be set to one of the following:  Tap side  Impedance side

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

68

PSAT User Manual

Control Variable Upper Limit:

Upper limit for controlled variable.

Control Variable Lower Limit:

Lower limit for controlled variable.

Control Flag:

Control flag, which can be set to one of the following:  Disabled  Voltage  MVAr  MW Tap ratio or phase angle of Enabled windings of 3-W transformers will be adjusted will be adjusted in powerflow solution if the corresponding solution parameter is set. Tap ratio and phase angle of Disabled windings of 3-W transformers will remain fixed.

Maximum:

Maximum tap ratio or phase shift angle.

Minimum:

Minimum tap ratio or phase shift angle.

Ratio Step:

Step size, for adjustment of variable tap, in pu.

Primary Ratings:

6 ratings of the primary winding in MVA at nominal voltage.

Secondary Ratings:

6 ratings of the secondary winding in MVA at nominal voltage.

Tertiary Ratings:

6 ratings of the tertiary winding in MVA at nominal voltage.

Rating Group:

An integer number representing the rating group.

Name:

16 characters long characteristic name. This name is not required to be unique.

Owner:

16 characters long transformer ownership name.

The Three Winding Transformer Properties dialog also shows the value of the controlled variable and variable tap ratio/phase shift angle (for comparison with the upper/lower limits), as well as the MW, MVAr and current (A) flows at the terminal buses (flows entering the transformer from each bus) under the Flows tab.

9.12 Fixed Series Compensator Fixed series compensators (capacitors or inductors) are connected between a pair of AC buses, individually or as a section of a sectional branch. They are represented by a capacitor or inductor with two terminals in the Bus Tree and diagrams. The attributes of each fixed series compensator, shown in Fixed Series Compensator Properties dialog, are the following: From-Bus:

Terminal bus at the “From” end. This bus must exist in the powerflow data.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

69

PSAT User Manual

To-Bus:

Terminal bus at the “To” end. This bus must exist in the powerflow data. To connect the series compensator to a different From or To bus, click on the browse button beside the bus number/name to open the Set AC Bus dialog, select the new bus in that dialog and click the OK button.

ID:

8 character identifier to distinguish among parallel fixed series compensators.

Section:

Section number of the series compensator if it belongs to a sectional branch. It will be 0 (blank in the Compensator table) if the series compensator is not a section of a sectional branch. Sections of a sectional branch must have the same From-bus, To-bus (in the same order) and ID, and consecutive Section numbers (1, 2, . . .) starting from 1 for the section at the From-bus.

Status:

In-service or Out-of-service status.

Meter end:

Metered end, which can be set to one of the following:  From  To

Reactance:

Series reactance in pu.

Amp Rating:

Current rating in Amps.

kV Rating:

kV Rating.

Name:

16 characters long characteristic name. This name is not required to be unique.

Owner:

16 characters long ownership name.

The Fixed Series Compensator Properties dialog also shows the MW, MVAr and current (Amp) flows at the From and To buses (flows entering the series compensator from each bus) under the Flows tab.

9.13 Adjustable Series Compensator Adjustable series compensators (capacitors or inductors) are connected between a pair of AC buses, individually or as a section of a sectional branch. They are represented in the Bus Tree and diagrams by a capacitor or inductor with two terminals and an arrow. By adjusting the series impedance, adjustable series compensator can control its own MW flow. The attributes of each adjustable series compensator, shown in Adjustable Series Compensator Properties dialog, are the following: From-Bus:

Terminal bus at the “From” end. This bus must exist in the powerflow data.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

70

PSAT User Manual

To-Bus:

Terminal bus at the “To” end. This bus must exist in the powerflow data. To connect the series compensator to a different From or To bus, click on the browse button beside the bus number/name to open the Set AC Bus dialog, select the new bus in that dialog and click the OK button.

ID:

8 character identifier to distinguish among parallel adjustable series compensators.

Section:

Section number of the series compensator if it belongs to a sectional branch. It will be 0 (blank in the Compensator table) if the series compensator is not a section of a sectional branch. Sections of a sectional branch must have the same From-bus, To-bus (in the same order) and ID, and consecutive Section numbers (1, 2, . . .) starting from 1 for the section at the From-bus.

Status:

In-service or Out-of-service status.

Meter end:

Metered end, which can be set to one of the following:  From  To

Control Flag:

Control flag, which can be set to one of the following:  Enabled  Disabled Impedance of Enabled series compensators will be adjusted in powerflow solution if the corresponding solution parameter is set. Impedance of Disabled compensators will remain fixed.

Reactance:

Series reactance in pu.

Maximum Reactance:

Maximum series reactance in pu.

Minimum Reactance:

Minimum series reactance in pu.

Upper MW Limit:

Upper limit for real power flow, in MW, through the series compensator in the From-to-To direction.

Lower MW Limit:

Lower limit for real power flow, in MW, through the series compensator in the From-to-To direction.

Amp rating:

Current rating in Amps.

kV Rating:

kV Rating.

Name:

16 characters long characteristic name. This name is not required to be unique.

Owner:

16 characters long ownership name.

The Adjustable Series Compensator Properties dialog also shows the MW flow (for comparison with the upper/lower limits), as well as the MW, MVAr and current (Amp) flows at the From and To buses (flows entering the series compensator from each bus) under the Flows tab. This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

71

PSAT User Manual

9.14 Static Tap Changer / Phase Regulator The Static Tap Changers / Phase Regulators (STC/SPR) are connected between a pair of AC buses, individually or as a section of a sectional branch. In the Bus Tree and diagrams, they are represented by two windings and a converter symbol in the middle. The model of a St. TC/PR consists of two ideal transformers, each with a variable turns ratio and phase shift, on the From and To sides, a series impedance between them, as well as magnetizing admittances at the From and To buses and shunt (charging) admittance. The off-nominal turns ratio and phase shift angle of the two transformers are determined from the tap-changer and phase-regulator parameters as: Tf f = 1 + AT ( 1 – XT) RT + j AP ( 1 – XP) RP Tt t = 1 - AT XT RT - j AP XP RP where Tf : Off-nominal turns ratio of From-side transformer f : Phase shift angle of From-side transformer Tt : Off-nominal turns ratio of To-side transformer t : Phase shift angle of To-side transformer AT : Tap-changer range XT : Tap-changer winding position RT : Tap-changer variable ratio AP : Phase-regulator range XP : Phase- regulator winding position RP : Phase- regulator variable ratio Each St. TC/PR can control the voltage of a bus or its own MVAr and/or its own MW flow by adjusting its tapchanger and phase- regulator ratios within limits. The attributes of each St. TC/PR, shown under Main, Impedances, Controls and MVA Ratings tabs in Static Tap Changer / Phase Regulator Properties dialog, are the following: From-Bus:

Terminal bus at the “From” end. This bus must exist in the powerflow data.

To-Bus:

Terminal bus at the “To” end. This bus must exist in the powerflow data. To connect the St. TC/PR to a different From or To bus, click on the browse button beside the bus number/name to open the Set AC Bus dialog, select the new bus in that dialog and click the OK button.

ID:

8 character identifier to distinguish among parallel St. TC/PRs.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

72

PSAT User Manual

Section:

Section number of the St. TC/PR if it belongs to a sectional branch. It will be 0 (blank in the St.TC/PR table) if the St. TC/PR is not a section of a sectional branch. Sections of a sectional branch must have the same From-bus, To-bus (in the same order) and ID, and consecutive Section numbers (1, 2, . . .) starting from 1 for the section at the From-bus. Note that a sectional branch cannot have more than one fixed or adjustable transformer or static tap changer/phase regulator.

Status:

In-service or Out-of-service status.

Base MVA:

Rated (base) MVA. Note that pu impedance and admittances are in the system MVA base, not the St. TC/PR base MVA.

Meter end:

Metered end, which can be set to one of the following:  From  To

TC Range:

Tap changer range (factor) in pu.

TC Winding Position:

Tap changer winding position (split), which is a value between 0.0 and 1.0.

TC Ratio:

Tap changer ratio in pu.

TC Maximum Ratio:

Maximum tap changer ratio in pu.

TC Minimum Ratio:

Minimum tap changer ratio in pu.

PR Range:

Phase regulator range (factor) in pu.

PR Winding Position:

Phase regulator winding position (split), which is a value between 0.0 and 1.0.

PR Ratio:

Phase regulator ratio in pu.

PR Maximum Ratio:

Maximum phase regulator ratio in pu.

PR Minimum Ratio:

Minimum phase regulator ratio in pu.

Resistance:

Series resistance in pu.

Reactance:

Series reactance in pu. For St. TC/PR with TC and/or PR Correction Table, resistance and reactance values specify the reference impedance. The actual impedance will depend on the tap changer and/or phase regulator ratio.

TC Correction Table:

Number of the Impedance Correction Table (similar to that of adjustable transformers).

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

73

PSAT User Manual

PR Correction Table:

Number of the Impedance Correction Table (similar to that of adjustable transformers). The actual impedance is computed by multiplying the reference impedance with two factors. The first factor is determined from the TC correction table for the TC ratio and the second factor is determined from the PR correction table for the PR ratio. To choose one of the existing correction tables for TC or PR, click on its pull-down list and select a table number. To specify no correction table (remove the specified number), choose the blank (first) item in the pulldown list. To view the tables or add a new one, click on the “Add/View Correction Tables. . .” button.

From-Magnetizing:

Magnetization conductance and susceptance in pu at the From-bus.

To-Magnetizing:

Magnetization conductance and susceptance in pu at the To-bus.

Charging:

Charging (shunt) conductance and susceptance in pu.

Control Flag:

Control flag, which can be set to one of the following:  Enabled  Disabled Tap changer and/or phase regulator ratios of Enabled St. TC/PRs will be adjusted in powerflow solution if the corresponding solution parameter is set. Ratios of Disabled St. TC/PRs will remain fixed.

Control Variable:

Control variable, which can be set to one of the following:  Voltage (V)  Real Power (P)  Reactive Power (Q)  V and P  Q and P

Control Side:

Control side, which can be set to one of the following:  From  To For voltage control of a remote bus, this indicates whether that bus is on the From side or To side. For MW or MVAr flow control, this indicates whether the flow is measured at the From side or To side, but always in the From-to-To direction.

Controlled Bus:

Controlled bus (for voltage control). It can be the From-bus, To-bus or a remote bus.

Upper Voltage Limit:

Upper limit for controlled bus voltage in pu.

Lower Voltage Limit:

Lower limit for controlled bus voltage in pu.

Upper MVAr Limit:

Upper limit for controlled reactive power in MVAr.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

74

PSAT User Manual

Lower MVAr Limit:

Lower limit for controlled reactive power in MVAr.

Upper MW Limit:

Upper limit for controlled real power in MW.

Lower MW Limit:

Lower limit for controlled real power in MW.

MVA Ratings 1 to 6:

Thermal ratings of the St. TC/PR in MVA at nominal (1 pu) voltage.

Rating Group:

An integer number representing the rating group.

Name:

16 characters long characteristic name. This name is not required to be unique.

Owner:

16 characters long transformer ownership name.

The Static Tap Changer / Phase Regulator Properties dialog also shows the voltage of the controlled bus and MW/MVAr flows (for comparison with the upper/lower limits), as well as the MW, MVAr and current (A) flows at the From and To buses (flows entering the St. TC/PR from each bus) under the Flows tab.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

75

PSAT User Manual

9.15 DC Bus DC buses are where DC components, such as DC converters and DC lines are connected together. These components are identified by their DC buses, along with their circuit number. DC buses as represented by a short bar in the Bus Tree and diagrams. One DC bus, with the reserved name “GROUND”, represents the ground with zero voltage. This bus does not appear in the list of DC buses. The attributes of a DC bus, shown in the DC Bus Properties dialog, are the following: Name:

Unique name (up to 8 characters), used to identify the bus.

Area:

Area of the bus. In the Properties dialog, to modify the Area of the bus, click on the browse button (. . .) beside it. The Set Area dialog appears where you can select an existing area or create a new area.

Zone:

Zone of the bus. In the Properties dialog, to modify the Zone of the bus, click on the browse button (. . .) beside it. The Set Zone dialog appears where you can select an existing zone or create a new zone.

The DC Bus Properties dialog also shows the voltage of the DC bus computed by the powerflow solution.

9.16 DC Line Commutated Converters A DC converter is connected to two DC buses and one AC bus through a transformer. The first DC bus of a converter has a voltage which is positive with respect to the voltage at the second bus. One of these buses can be “GROUND”. The AC bus is the primary terminal of the converter transformer and the transformer parameters are part of the DC converter data. The AC bus can be set to the Infinity bus, which has 1 pu voltage and provides unlimited real and reactive power. The transformer reactance or its derivative, the commutating reactance can be supplied in two ways. The first option is to specify the commutating reactance in ohms/bridge and set the transformer MVA to zero. The second option is to specify the transformer reactance in pu and specify its rated MVA and the program computes the commutating reactance. These quantities must be consistent with the value specified for the number of bridges in series. For each DC converter, two control variables are specified. The control variables include: VD - DC voltage in kV ID - DC current in Amps (+ve at rectifier and -ve at inverter) PA - Real power in MW (-ve at rectifier and +ve at inverter) QA - Reactive power in MVAr (-ve at rectifier and inverter) AL - Firing angle (alpha) in degrees GA - Extinction angle (gamma) in degrees AT - Transformer tap (off-nominal turns ratio) in pu During the solution, the converter will control the two variables at a given value (set point) as long as other variables do not exceed their limit. Otherwise, the control mode will change to keep the other variable(s) at their limit based on their priority. Note that not all combinations of the two control variables are appropriate or desirable. The This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

76

PSAT User Manual

combinations of VD and ID, VD and PA, and ID and PA result in an invalid converter specification (since one of these variables is determined by the other two). The combination of AL and GA is not recommended but is acceptable. The attributes of each DC converter, shown under Main and Limits tabs of the Converter Properties dialog, are the following: DC Bus 1:

Name of first DC bus (8 character long).

DC Bus 2:

Name of second DC bus (8 character long). It is the negative terminal with respect to the first bus. To move a converter from one DC bus to another bus, click on the browse button (. . .) beside the DC bus name to open the Set DC Bus dialog, select the destination bus in that dialog and click the OK button. To connect the converter to ground, in the Set DC Bus dialog, click the “Set to Ground” button instead of selecting a DC bus.

AC bus:

AC bus (primary terminal) of converter transformer. To change the AC bus of the converter, click on the browse button (. . .) beside the AC bus number/name to open the Set AC Bus dialog, select a bus in that dialog and click the OK button, or click the “Set to Infinity” button.

ID (Circuit no):

Circuit number to distinguish parallel converters.

Type:

converter type which can be set to one of the following:  Rectifier  Inverter

Commut. Reactance:

Commutating reactance (Xc) either in ohms per bridge when transformer MVA is zero, or in pu based on transformer MVA rating.

Compnd. Resistance:

Voltage compounding resistance (Bias R) in Ohms.

Number of bridges:

Number of series bridges in this converter.

Transformer’s: Base MVA:

Transformer MVA rating (zero when Xc is in ohms/bridge).

Base kV:

Base voltage of transformer primary side in kV (if zero it is set to the base kV of AC bus).

Nominal Ratio:

Transformer nominal ratio, which is the ratio of the secondary voltage (DC side) to the primary voltage (AC side).

Maximum Ratio:

Maximum off-nominal turns ratio of the transformer in pu.

Minimum Ratio:

Minimum off-nominal turns ratio of the transformer in pu.

Ratio Step:

Step size in percent for adjustment of transformer turns ratio.

Control Variable1:

First control variable, which can be set to VD, ID, etc., described above.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

77

PSAT User Manual

Set Point 1:

Set point of the first control variable in the units specified above for VD, ID, etc.

Control Variable2:

Second control variable, which can be set to VD, ID, etc., described above.

Set Point 2:

Set point of the second control variable in the units specified above for VD, ID, etc.

Max Alpha:

Maximum alpha in degrees.

Min Alpha:

Minimum alpha in degrees.

Min Gamma:

Minimum gamma in degrees.

Max Power (MW):

Maximum real power in MW.

Min Power (MW):

Minimum real power in MW.

Max Power (MVAr):

Maximum reactive power in MVAr.

Min Power (MVAr):

Minimum reactive power in MVAr.

Max DC Current:

Maximum DC current in Amps.

Note that some of the converter data such as bias resistance, ratio step and minimum/maximum limits for ratio, current and real and reactive power are only used by central schedulers. The Converter Properties dialog also shows the DC voltage and current, alpha, gamma, transformer off-nominal turns ratio and AC power and current computed by the powerflow solution under Solution tab.

9.17 Voltage Source Converter A voltage source converter (VSC) is connected to two DC buses on the DC side (one of them can be “GROUND”) and two AC buses on the AC side. The primary winding of the VSC transformer is connected between the two AC buses. The second AC bus can be set to “GROUND”, which indicates a shunt VSC connection, or to an existing AC bus, which indicates a series VSC connection between the two AC buses. The first AC bus can be set to Infinity. Data for VSC is similar to that of regular DC converter described above, except that VSC has three specified control variables. These include: VD - DC voltage in kV ID - DC current in amps (+ve at rectifier and -ve at inverter) PA - Real power injected into first AC bus in MW QA - Reactive power injected into first AC bus in MVAr AL - Power angle (alpha) in degrees GA - Modulation ratio (gamma), between -1.0 and 1.0 AT - Transformer tap (off-nominal turns ratio) in pu The attributes of each VSC, shown under Main and Limits tabs of the Voltage Source Converter Properties dialog, are the following:

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

78

PSAT User Manual

DC Bus 1:

Name of first DC bus (8 character long).

DC Bus 2:

Name of second DC bus (8 character long). It is the negative terminal with respect to the first bus. To move a converter from one DC bus to another bus, click on the browse button (. . .) beside the DC bus name to open the Set DC Bus dialog, select the destination bus in that dialog and click the OK button. To connect the converter to ground, in the Set DC Bus dialog, click the “Set to Ground” button instead of selecting a DC bus.

AC bus 1:

First AC bus.

AC bus 2:

Second AC bus. To change the AC bus of the converter, click on the browse button (. . .) beside the AC bus number/name to open the Set AC Bus dialog, select a bus in that dialog and click the OK button, or click the “Set to Infinity” (for the first bus) or “Set to Ground” (for the second bus) button.

ID (Circuit no):

Circuit number to distinguish parallel VSCs.

Type:

VSC type which can be set to one of the following:  Rectifier  Inverter

Transf. Reactance:

Transformer reactance (Xt), either in ohms per bridge when transformer MVA is zero, or in pu based on transformer MVA rating.

Line Reactance:

Line reactance (X1), either in ohms if transformer MVA is zero, or in pu based on transformer MVA rating. This is the reactance of line in series with the transformer between the two AC buses.

Number of bridges:

Number of series bridges in this converter.

Gain:

Code for the DC to AC gain (Kc) of the converter (i.e. Vl-1/Vd), which can be set to one of the following: 0 - gain is 1 1 - SQRT(6)/4 for linear sinusoidal PWM 2 - SQRT(6)/ for square-wave pulse switching 3 - 0.727 for 5th and 7th harmonic elimination switching

Transformer’s: Base MVA:

Transformer MVA rating (zero when Xt is in ohms/bridge).

Base kV:

Base voltage of transformer primary side in kV. If zero, it is set to the base kV of first AC bus.

Nominal Ratio:

Transformer nominal ratio, which is the ratio of the secondary voltage (DC side) to the primary voltage (AC side).

Maximum Ratio:

Maximum off-nominal turns ratio of the transformer in pu.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

79

PSAT User Manual

Minimum Ratio:

Minimum off-nominal turns ratio of the transformer in pu.

Ratio Step:

Step size in percent for adjustment of transformer turns ratio.

Control Variable1:

First control variable, which can be set to VD, ID, etc., described above.

Set Point 1:

Set point of the first control variable in the units specified above for VD, ID, etc.

Control Variable2:

Second control variable, which can be set to VD, ID, etc., described above.

Set Point 2:

Set point of the second control variable in the units specified above for VD, ID, etc.

Control Variable3:

Third control variable, which can be set to VD, ID, etc., described above.

Set Point 3:

Set point of the third control variable in the units specified above for VD, ID, etc.

Max Power Angle:

Maximum power angle in degrees (90).

Min Power Angle:

Minimum power angle in degrees (-90).

Max Modul. Ratio:

Maximum modulation ratio (1.0)

Min Modul. Ratio:

Minimum modulation ratio (-1.0)

Max AC Current:

Maximum AC current in Amps (for shunt VS converters only).

Ref. AC Voltage:

Estimated UPFC terminal voltage (the voltage expected to be kept constant by the shunt converter of UPFC) in pu.

Max AC Voltage:

Upper limit of the voltage of first AC bus in pu.

Min AC Voltage:

Lower limit of the voltage of first AC bus in pu. The last three items are specified for the series VSC of a UPFC model.

The Solution tab of the VSC Properties dialog shows the DC voltage and current, power angle, modulation ratio, transformer off-nominal turns ratio, AC power and current entering the first AC bus, and AC power and voltage injected into the AC system (between two AC buses) as computed by the powerflow solution.

9.18 DC Line DC lines are connected between a pair of DC buses (or a DC bus and ground). They are represented by a simple line in the Bus Tree and diagrams. The DC line model consists of a series resistance and inductance and two shunt capacitances at the terminals. The inductance and capacitances have no effect on powerflow solution (are used only in stability studies). The attributes of each DC line, shown in the DC Line Properties dialog, are the following: This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

80

PSAT User Manual

DC Bus 1:

Name of the “From” DC bus (8 character long).

DC Bus 2:

Name of the “To” DC bus (8 character long). To move a DC line from one DC bus to another bus, click on the browse button (. . .) beside the DC bus name to open the Set DC Bus dialog, select the destination bus in that dialog and click the OK button. To connect the line to ground, in the Set DC Bus dialog, click the “Set to Ground” button instead of selecting a DC bus.

ID (Circuit no):

Circuit number to distinguish parallel DC lines.

Metered end:

Metered end, which can be set to one of the following:  DC Bus 1 (From side)  DC Bus 2 (To side)

Resistance:

Resistance (Rdc) in Ohms. It must be nonzero.

Inductance:

Inductance (Ldc) in mH.

Capacitance 1:

Capacitance at From side (Cdc 1) in microF.

Capacitance 2:

Capacitance at To side (Cdc 2) in microF.

Max Current:

Current rating in Amps.

The DC Line Properties dialog also shows the DC power and current entering the line from each bus.

9.19 DC Breaker DC breakers are connected between a pair of DC buses (or a DC bus and ground). They are represented by a switch symbol in the Bus Tree and diagrams. The attributes of each DC breaker, shown in the DC Breaker Properties dialog, are the following: DC Bus 1:

Name of the “From” DC bus (8 character long).

DC Bus 2:

Name of the “To” DC bus (8 character long). To move a DC breaker from one DC bus to another bus, click on the browse button (. . .) beside the DC bus name to open the Set DC Bus dialog, select the destination bus in that dialog and click the OK button. To connect the breaker to ground, in the Set DC Bus dialog, click the “Set to Ground” button instead of selecting a DC bus.

ID (Circuit no):

Circuit number to distinguish parallel DC breakers.

Status:

Breaker status which can be set to one of the following:  Closed  Open

The DC Breaker Properties dialog also shows the DC power and current flowing from DC bus 1 to 2. This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

81

PSAT User Manual

9.20 Area Buses belong to control areas. Each area can have a designated Slack bus. With Area Interchange control, the generation at the slack bus is adjusted by the powerflow solution to keep the power export from the area at the desired value. In this adjustment, the generator MW limits can be respected or ignored. The attributes of each area, shown in the Area Properties dialog, are the following: Number:

Unique integer number used to identify the area.

Name:

Unique name (up to 16 characters), used to identify the area.

Slack bus:

Area slack bus (for area interchange control). This bus must be a generator bus in this area. In the areas containing a swing bus, that swing bus must be specified as the area slack bus. To change the slack bus, click on the browse button (. . .) beside the bus number/name to open the Set Slack Bus dialog, select a bus in that dialog and click the OK button.

Control Area Export:

Control flag, which can be set to one of the following:  Enabled  Disabled Power of Enabled slack generators will be adjusted in powerflow solution if the Area Interchange solution parameter is set. Power of Disabled slack generators will not be adjusted by Area Interchange control.

Limit Slack Gen.:

Flag for adjustment by Area Interchange control, which can be set to one of the following:  Yes (to keep the slack generation within its limit)  No (to ignore the slack generation limits)

Desired MW Export:

Desired (scheduled) real power export, in MW, from the area.

Export Tolerance:

Tolerance, in MW, for control of export at its desired value.

9.21 Zone Buses also belong to zones. Zones can cross area boundaries (buses of one zone may belong to more than one area and vice-versa). The attributes of each zone are: Number:

Unique integer number used to identify the zone.

Name:

Unique name (up to 16 characters), used to identify the zone.

9.22 Owner Buses, generators, loads, etc., belong to owners. The attributes of each Owner are:

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

82

PSAT User Manual

Number:

Unique integer number used to identify the owner.

Name:

Unique name (up to 16 characters), used to identify the owner.

9.23 Sectional Branch A Sectional Branch consists of series connected lines, series compensators, and/or at most one 2-winding transformer or static tap changer/phase regulator. A sectional branch is represented by a line with three sections in the Bus Tree and diagrams. The Sectional Branch data table shows the following information for the sectional branches: From-Bus:

Terminal bus at the “From” end.

To-Bus:

Terminal bus at the “To” end. To connect the branch to a different From or To bus, click on the browse button (. . .) beside the bus number/name to open the Set AC Bus dialog, select the new bus in that dialog and click the OK button.

ID:

8 character identifier.

Status:

In-service or Out-of-service status.

All sections of a sectional branch must have the same From-bus, To-bus (in the same order) and ID, and consecutive Section numbers (1, 2, . . .) starting from 1 for the section at the From-bus. Note that a sectional branch cannot have more than one fixed or adjustable transformer or static tap changer/phase regulator. The sections of sectional branches are included with regular branches in the Line, Transformer and other tables and have properties similar to regular branches. In those tables and property dialogs, sections of sectional branches have a non-zero Section number. Changing the From-bus, To-bus, ID or Status of a section in those tables and property dialogs will apply the same change to all sections. The connection points of sections (mid-buses) are not represented explicitly in the powerflow data, but their voltages are included in some of the reports. After selecting a row of Sectional Branch table (click on the row), Property Dialog of the Edit menu (or double click on the row) opens the Sectional Branch Dialog where you can view, add, remove, modify and rearrange the sections of that branch. See Sectional Branch Dialog on how to add sections to a non-sectional branch.

9.24 Case Description The Case Description dialog which opens by double clicking Case Description under PowerFlow Data in the Workspace, shows the Title as well as the number of elements (buses, generators, etc) in the powerflow data and the date and time of its creation (or modification). The Title has three lines of text, up to 80 characters each. To modify the title, simply click on each line and delete and insert text.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

83

PSAT User Manual

10 Data Manipulation This chapter describes the features and functions of the data manipulation dialogs. These dialogs are opened from the Data Manipulation submenu of the Edit menu when a related data table is selected. The data manipulation (scaling, reassigning, etc.) applies to the data included in the table. Therefore, to apply the action to the whole system, you must select the subsystem for the table before the data manipulation. Otherwise, to apply the action to a part of the system, you must first define a simple or composite subsystem to represent that part, then select that subsystem for the table before the data manipulation.

10.1 Reassign Zone When the active window is the AC Bus table, the Reassign Zone command of the Edit | Data Manipulation submenu opens the Set Zone dialog for changing the zone of all buses in the AC Bus table. The list in this dialog shows the number and name of all zones in the powerflow data, unless you select a previously defined subsystem other than from the pull-down list at the top. Select a zone by clicking on a row in the zone list, then click OK button (or double click on the row). The zone of buses in the AC Bus table changes to this selected zone and the dialog closes. To change the zone of buses to a new zone, you must first define the new zone by clicking New Zone… button. This adds a zone to the powerflow data and opens its property dialog for you to specify a number and name for this new zone. After you close the Zone Property dialog (Click OK button), the new zone appears in the zone list In the Search box, type in a Zone Number or Zone Name to find a zone in the list. As you type the number or name, the list scrolls and highlights the matching zone for you to select. For example as you type ABC, the first zone that has a name starting with ABC is highlighted. To close the dialog without changing the zone of AC buses, click Cancel button.

10.2 Reassign Area When the active window is the AC Bus table, the Reassign Area command of the Edit | Data Manipulation submenu opens the Set Area dialog for changing the area of all buses in the AC Bus table. The list in this dialog shows the number and name of all areas in the powerflow data, unless you select a previously defined subsystem other than from the pull-down list at the top. Select an area by clicking on a row in the area list, then click OK button (or double click on the row). The area of buses in the AC Bus table changes to this selected area and the dialog closes. To change the area of buses to a new area, you must first define the new area by clicking New Area… button. This adds an area to the powerflow data and opens its property dialog for you to specify a number and name for this new area. After you close the Area Property dialog (Click OK button), the new area appears in the area list In the Search box, type in an Area Number or Area Name to find an area in the list. As you type the number or name, the list scrolls and highlights the matching area for you to select. For example as you type ABC, the first area that has a name starting with ABC is highlighted. To close the dialog without changing the area of AC buses, click Cancel button.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

84

PSAT User Manual

10.3 Scale MW Generation When the active window is the Generator table, the Scale MW Generation command of the Edit | Data Manipulation submenu opens this dialog for changing MW output of all generators in the Generator table. If you click in the Exclude negative generation box to select this option (add a check mark), generators with negative MW output will be excluded from scaling. If you click the Respect Pmin & Pmax box to select this option (add a check mark), scaling of generation will respect each generators Pmin and Pmax and will not scale above their Pmax or scale below their Pmin. It is possible that if all scaled generators reach their limit that the desired final total generation may not be met. Click in the Scale To box to select it and type in a MW value. When you click Scale button, the MW output of generators in the Generator table are scaled uniformly so that their sum will be equal to the value you specified in the Scale To box. Click in the Scale By box to select it and type in a percent value. When you click Scale button, the MW output of generators in the Generator table are changed by the percentage you specified in the Scale By box. For example if you specify –10 in this box, MW outputs are reduced by 10% (i.e., 200 MW output becomes 180 MW). Note that as you specify a total MW value in the Scale To box, the Scale By box shows by what percentage generations will change, and vice versa. To close this dialog without changing MW generations, click Cancel button.

10.4 Scale Load When the active window is the Load table, the Scale Load command of the Edit | Data Manipulation submenu opens this dialog for changing the real and reactive parts of all loads in the Load table. If you click in the Exclude negative real load box to select this option (add a check mark), loads with negative real part will be excluded from scaling. Click in the Scale Real Load To box to select it and type in a MW value. When you click Scale button, the real part of loads in the Load table are scaled uniformly so that their sum will be equal to the value you specified in the Scale Real Load To box. Click in the Scale Real Load By box to select it and type in a percent value. When you click Scale button, the real part of loads in the Load table are changed by the percentage you specified in the Scale Real Load By box. For example if you specify –10 in this box, real loads are reduced by 10% (i.e., 200 MW load becomes 180 MW). Note that as you specify a total MW value in the Scale Real Load To box, the Scale Real Load By box shows by what percentage real loads will change, and vice versa. For the reactive load, if you click the Keep Power Factors Constant radio button to select it, as the real loads are scaled, reactive loads are also scaled in proportion to their real part so that the power factor of each load remains constant. If you click the Keep Reactive Load Constant radio button to select it, as the real loads are scaled, reactive loads remain constant.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

85

PSAT User Manual

Click in the Scale Reactive Load To box to select it and type in a MVar value. When you click Scale button, the reactive part of loads in the Load table are scaled uniformly so that their sum will be equal to the value you specified in the Scale Reactive Load To box. Click in the Scale Reactive Load By box to select it and type in a percent value. When you click Scale button, the reactive part of loads in the Load table are changed by the percentage you specified in the Scale Reactive Load By box. Note that as you specify a total MVAr value in the Scale Reactive Load To box, the Scale Reactive Load By box shows by what percentage reactive loads will change, and vice versa. To close this dialog without changing the loads, click Cancel button.

10.5 Scale MVAr Load When the active window is the Load table, the Scale MVAr Load command of the Edit | Data Manipulation submenu opens this dialog for changing the reactive part of all loads in the Load table. The real part of loads remains unchanged. If you click in the Exclude capacitive load box to select this option (add a check mark), loads with negative reactive part will be excluded from scaling. Click in the Scale To box to select it and type in a MVar value. When you click Scale button, the reactive part of loads in the Load table are scaled uniformly so that their sum will be equal to the value you specified in the Scale To box. Click in the Scale By box to select it and type in a percent value. When you click Scale button, the reactive part of loads in the Load table are changed by the percentage you specified in the Scale By box. Note that as you specify a total MVAr value in the Scale To box, the Scale By box shows by what percentage reactive loads will change, and vice versa. To close this dialog without changing the loads, click Cancel button.

10.6 Scale Fixed Shunt When the active window is the Fixed Shunt table, the Scale Fixed Shunt command of the Edit | Data Manipulation submenu opens this dialog for changing all shunt admittances in the Fixed Shunt table. For Conductance, click in the Scale To box to select it and type in a MW value. When you click Scale button, the conductance of shunts in the Fixed Shunt table are scaled uniformly so that their “nominal” sum (sum of their MW loss at nominal voltage) will be equal to the value you specified in the Scale To box. Click in the Scale By box to select it and type in a percent value. When you click Scale button, the conductance of shunts in the table are changed by the percentage you specified in the Scale By box. For example if you specify –10 in this box, conductance of shunts are reduced by 10% (i.e., 20 MW shunt becomes 18 MW). For Capacitance, click in the Scale To box to select it and type in a MVAr value. When you click Scale button, the positive susceptance shunts in the Fixed Shunt table are scaled uniformly so that their “nominal” sum (sum of their MVAr generation at nominal voltage) will be equal to the value you specified in the Scale To box. Click in the Scale By box to select it and type in a percent value. When you click Scale button, the positive susceptance shunts in the table are changed by the percentage you specified in the Scale By box. This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

86

PSAT User Manual

For Inductance, click in the Scale To box to select it and type in a MVAr value. When you click Scale button, the negative susceptance shunts (reactors) in the Fixed Shunt table are scaled uniformly so that their “nominal” sum (sum of their MVAr generation at nominal voltage; which is negative for reactors) will be equal to the value you specified in the Scale To box. Click in the Scale By box to select it and type in a percent value. When you click Scale button, the negative susceptance shunts in the table are changed by the percentage you specified in the Scale By box. Note that as you specify a value in the Scale To box, the Scale By box shows by what percentage conductance, capacitance or inductance will change, and vice versa. To close this dialog without changing the shunts, click Cancel button.

10.7 Convert Load Model When the active window is the Load table, the Convert Load Model command of the Edit | Data Manipulation submenu opens this dialog for changing the model of all loads in the Load table. In the Convert based on box, if you click the Bus Voltage radio button to select it, the Actual MW and MVAr loads remain the same (the Nominal values change) after the model conversion. If you click the Unity Voltage radio button to select it, the Nominal MW and MVAr loads remain the same (the Actual values change). If the Reference Load radio button is selected, after the model conversion the Nominal loads will be equal to the reference loads. Each load (with its existing 5 components) can be converted to up to 5 new components. For each new component, you need to specify its model from the Model pull-down list and its percentage of the Real and Reactive part of the load. This Model list includes the standard model names plus defined exponential load model numbers. The model of an unused (undefined) component will be “Out”. To view the models or define a new model, click the Add / View Models button. This opens the Load Models dialog where you can examine the existing models and add new models as described in section 9.4. Clicking Convert button will convert the existing components of all the loads in the Load table to the new components, based on the conversion option selected above. If the sum of real or reactive part percentages of the components (shown at the button of the component list) is not 100, you will be asked to confirm to change an “Out” component to “Constant Power” and set its percentages so that the total will be 100. If you respond No, or if none of the 5 components is “Out”, you must change the composition of the 5 components to make the percentages add up to 100 and then click Convert button. To close this dialog without changing the load models, click Cancel button.

10.8 Delete Out-of-Service When the active window is the AC Bus table, Generator table, etc., the Delete Out-of-Service command of the Edit | Data Manipulation submenu deletes all out-of-service components in that table.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

87

PSAT User Manual

11 Solving Powerflow To solve the powerflow for the current (opened) case, use the Solution menu or the Solve button on the Toolbar. Before, solution, select Parameters… of the Solution menu to open the Solution Parameters Dialog where you can examine and, if needed, modify the solution options. Choose the Solution Algorithm from the list of: Auto:

Solution starts with the Fast Decoupled method and switches to Newton-Raphson for convergence to smaller than 1 MW/MVAr tolerance.

Newton-Raphson:

Standard Newton-Raphson method.

Fast Decoupled (XB):

Standard Fast Decoupled method.

Fast Decoupled (BX):

Modified Fast Decoupled method that convergences better when there are AC lines with high resistance relative to their reactance.

Specify the Solution Parameters, which include: Maximum Iterations:

Solution process stops if it does not converge in the specified maximum number of iterations.

Blow Up:

Solution is considered “diverged” if voltage changes become larger than the specified blow up value.

Solution Tolerance:

Solution is reached (converged) when the largest MW and MVAr mismatches of all buses becomes less than the specified tolerance, and all enabled control actions are completed.

Voltage Tolerance:

Voltage controls are considered completed when the voltages reach within the specified tolerance of their desired value.

Zero Impedance Threshold:

Lines with impedance smaller than the specified threshold are considered as “Zero Impedance Line” (their terminal buses are joined together). If you set this threshold to smaller than 0.0001, the solution may not converge because of rounding errors caused by very small impedances.

Control Threshold:

During the solution iterations, enabled controls are adjusted when the voltage corrections become smaller than the specified threshold. If you set this threshold too high, solution may diverge quickly. If you set it too low, switchable shunts and other controls may not switch in time to help reaching the solution (e.g., in cases where it is needed to switch in capacitors for the case to have a solution).

Acceleration Factor:

Factor used to correct controlled voltages. You may leave its value at 1.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

88

PSAT User Manual

Flat Start:

If you select Yes, all bus voltages are initialized to 1 pu and zero angle before the solution. If you select No, the solution starts with bus voltages at their current value in the powerflow data.

Specify the Control Parameters by placing a check mark for each type of control device that you want to be enabled (click on each control to toggle its check mark on and off). Enabled control devices (e.g., discrete shunts, Voltage Control transformers, etc.) will be adjusted during the solution to control a variable (voltage, flow, etc.) according to their data in the powerflow. Section 9 describes the data and control functions of these devices. See section 11.1 for description of Governor Response option. After closing this dialog, select Solve from the Solution menu (or click the Solve button in the Toolbar) to start the solution. The Message window pops-up and shows the solution process. You should examine the messages and find out whether the case solved or not. If you see any data/solution error in the messages, you need to examine and modify the data or solution options and repeat the solution. If the solution does not converge, you have a choice of either reverting back to the condition before you started the solution process (restore bus voltages and control variables to their pre-solution value), so you can modify the data or solution options and repeat the solution, or keeping the condition reached at the last solution iteration, so you can examine unsolved buses, uncompleted control actions, etc.

11.1 Governor Response When the Governor Response option in the Solution Parameters Dialog is not enabled, during powerflow solution, the swing generators will balance the MW generation, load and losses in the system. The area slack generators also may be adjusted if the Area Interchange control is enabled. The real power output of all other generators remain fixed. When the Governor Response is enabled, all generators can participate to balance the MW generation, load and losses in the system (Area Interchange will be disabled). In this version of PSAT, it is assumed that all generators participate, their governor droops are the same (usually droops are 4 to 5%) and their regulation range is 15% to 95% of their Base MVA. In this case, solution with governor response will change the MW output of all generators in proportion to their Base MVA, as long as they stay within 0.15*Base_MVA and 0.95*Base_MVA (the change in swing generation may be up to 5*Solution_Tolerance higher or lower than its share).

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

89

PSAT User Manual

12 Comparing Two Powerflows You can compare the powerflow data and branch flows of the current (open) case in PSAT with another saved powerflow data. For this, use the Compare Powerflow Data command of the File menu. The Open File dialog appears where you can choose an existing PFB (or PSF) file to be opened and compared to the current case. The Workspace changes to show only the “Compare case 1 to case 2” group, where “case 1” is the name of powerflow file of the current case and “case 2” is the name of second powerflow file opened for comparison. Click on the + button beside “Compare case 1 to case 2.” To expand its list, which includes AC Bus, Generator, etc., similar to the list under Powerflow Data previously shown in the Workspace. Double click on each item to open its comparison table. You may choose to match the two cases by bus number, name or both. This selection must be made in the Comparison Data Matching Dialog, accessed from the Settings menu, before you open the second powerflow data. For example, when you choose the compare by number option, if the number of a bus in case 2 is the same as the number of a bus in case 1, these buses match and their data from the two cases will be compared (they may have the same name or different names). Otherwise, they will be listed as two separate buses, each belonging to only one of the cases. The columns of the comparison tables are similar to those in the powerflow data tables and show the data in case 1 and case 2 and their differences. For example, if you double click on AC Bus, its comparison table opens, showing three columns for Bus Number, three columns for Bus Name, three columns for Bus Type, etc. The three columns of each data item have headings “1”, “2” and “Diff”, which correspond to the data in case 1, data in case 2 and their difference, respectively. If, for example, the type of a bus in case 1 is the same as that in case 2, the “Bus Type Diff” column remains blank for this bus. For non-numerical items, e.g., Bus Type, Status, etc., the “Diff” column shows “Diff” if the data of columns “1” and “2” are different. For un-matched data, e.g., buses that exist in one case but not in the other, the “1” or “2” column remains blank and the “Diff” column shows “N/A”. You may limit each comparison table to a subsystem by selecting one from the Subsystem menu or the pull-down list, similar to that for Powerflow Data tables. You can also customize the comparison tables similar to other tables. The Customize table command of the Settings menu (or Customize columns command from right click on the table heading row) opens the Table Customization Dialog where you can choose the columns to be shown, their order, etc. Note that each item in the customization dialog corresponds to a set of “1”, “2” and “Diff” columns for that item. You can specify a threshold for comparison of each data item in the customization dialog. For example, if for the Voltage p.u. column of the AC Bus table, you set this threshold to 0.001, then the bus voltage differences (voltages in case 1 minus voltages in case 2) that are smaller than 0.001 p.u. will not be shown in the table and the “Diff” column remains blank for these voltages. Check the comparison thresholds to make sure you don‟t miss the differences that are smaller than the previously specified thresholds. You can reduce the rows of a comparison table by hiding the rows that don‟t show any difference in the “Diff” columns. For example, if you show only the Bus Type and Voltage p.u. columns of the AC Bus table (hide other columns) and set the threshold for voltage comparison to 0.001, only those buses that have a different type or have a voltage difference larger than 0.001 in the two cases will appear in the table. The selection to hide or show the rows with no difference values (the same data in case 1 and case 2) is made in the customization dialog of each table. If you click on a “Diff” header, the rows of the table are sorted based on the absolute value of the differences in that column. This is more convenient than sorting by algebraic values when you want to find the large differences between two cases. Another click on the same header toggles the sorting between ascending and descending, but still based on the absolute values. To stop the comparison and return to the normal PSAT mode, use the Stop Comparing command of the File menu. This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

90

PSAT User Manual

13 Reduction The static network reduction feature of PSAT allows you to reduce the current (opened) powerflow case to a smaller case by keeping a specified part of the network and replacing the rest of it with equivalent branches, shunts and loads at the boundary buses. Boundary bus is a bus in the retained part of the network that was connected to a bus in the rest (reduced part) of the network. The changes that are made to the network by the reduction cannot be undone. Therefore, it is recommended to save the powerflow file before reduction, so you can return to the unreduced case if necessary. For accurate reduction, powerflow must be solved before reducing the network.

13.1 How to Reduce a Network By selecting Reduction / Purge from the Solution menu of PSAT window, the Reduction window appears where you can specify the reduction options and parameters, reduce the network and view the messages and results. The Specify the subnetwork to be retained box tells PSAT which part of the system is to be retained. Select a simple or composite subsystem from the pull-down list of this box. This list includes the subsystems that you had defined previously in PSAT (by default, it specifies the previously selected areas). If you need to define a new subsystem or change the definition of a subsystem, use the buttons beside this box to open the subsystem definition dialogs. See section 8.10 and 8.11 on how to define or modify the subsystems. When reducing the network to a specified subsystem, PSAT can retain a few additional buses in the rest (reduced part) of the network to maintain its sparsity. If you do not want PSAT to retain any additional bus, click the Retain additional buses to maintain sparsity box to remove its check mark. However, if you can accept retaining a few additional buses, it is recommended to select this option (click on the box to put a check mark in it). Some of the equivalent lines generated by the reduction may have very high impedance, amounting almost to an open circuit. By setting the value of Cut-off impedance for equivalent lines you ask PSAT to ignore (reject) the equivalent lines with impedance higher than this value. A smaller impedance cut-off value results in fewer equivalent lines (and a more sparse network), but if this value is set too small, it results in the rejection of too many equivalent lines and inaccurate reduction (mismatches at the boundary buses). Reduction will be different if you set the value of cut-off impedance to zero. In this case, the eliminated part of the network is completely replaced by equivalent loads and shunts at the boundary buses (equivalent lines and phase shifters are replaced with their injections and there will be no mismatch at the boundary buses). After specifying the above parameters/options, to start the reduction click the Reduce button (before clicking the Reduce button, you may click the Close button to return to the main PSAT window without reducing the case). The message box shows the progress of reduction process. Before computing the equivalent network, PSAT checks the powerflow solution at the buses marked for elimination by computing the MW/MVAr mismatch at these buses. If PSAT finds buses with mismatch larger than the solution tolerance, it will list them in the message box and abort the reduction. If there are no mismatches, PSAT will reduce the case and display the following information in the message window:

   

Original number of buses in the network Number of buses marked to be eliminated Number of additional buses retained to maintain sparsity Number of boundary buses

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

91

PSAT User Manual

  

Number of equivalent lines generated by the reduction Number of equivalent phase shifters generated by the reduction Number of rejected equivalent lines (those with impedance higher than the cut-off value)

Before closing the Reduction window, you may click the Examine boundary buses and Examine additional retained buses buttons to view the list of these buses in separate tables. You can customize these tables and save/copy their contents by using their menus, similar to the data and report tables (see section 8.12 and section 7.6 for description of these menus). If the reduction completes successfully, the current case in PSAT will be the reduced network, but if the reduction is aborted because of an error or mismatch, PSAT keeps the original network. When you click the Close button PSAT returns to the main window. You may check the validity of the reduced case by checking its mismatches in the Solution Reports (there might be small mismatches caused by the rejection of high-impedance equivalent lines) and solving the powerflow (it should solve in one or two iterations if some controls do not require more iterations as they would in the un-reduced case). In the reduced case, since equivalent lines, loads and shunts might have replaced the area tie lines of the un-reduced case, the Area Interchange control might not function properly. In this situation, you need to reset the Desired MW Export of the areas to correspond to the reduced case. For example, if Area 1 was exporting 200 MW to Area 5, and now area 5 is replaced by equivalent loads and shunts, the Desired MW Export of Area 1 must be reduced by 200.

13.2 Purging from the Network Instead of performing a reduction, purging can be used to remove unwanted network components and replace them with equivalent loads and (optionally) generators at the boundaries. By selecting Reduction / Purge from the Solution menu of PSAT window, you can specify the purge options and parameters and reduce the network. The Specify the subnetwork to be retained box tells PSAT which part of the system is to be retained. Select a simple or composite subsystem from the pull-down list of this box. This list includes the subsystems that you had defined previously in PSAT (by default, it specifies the previously selected areas). If you need to define a new subsystem or change the definition of a subsystem, use the buttons beside this box to open the subsystem definition dialogs. See section 8.10 and 8.11 on how to define or modify the subsystems. When purging the parts of the network that are not retained, you have the option to either remove the components completely (Delete) or to retain the network data and simply set the components to be offline (Reserve). Select the appropriate setting from the area marked “External System”. Buses on the boundary of the retained system can be converted to generator buses and a fictitious generator added to hold the voltage. If you wish to use this option select Change to Gen Bus option in the “Boundary Bus Type” area; otherwise, leave the Unchanged setting selected and the buses will retain their original type and fictitious loads will be used to represent tie line flows at the bus. When purging the network, it is possible for retained buses to become isolated into islands. Setting the Out of Service option in the “Simple Islands” area will automatically detect and offline any islands containing a single bus; otherwise, the Remain in Service option will leave these islands unaltered. After specifying the above parameters/options, to start the purge click the Purge button (before clicking the Purge button, you may click the Close button to return to the main PSAT window without reducing the case). The message box shows the progress of purge process

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

92

PSAT User Manual

14 Short Circuit This chapter describes the Short Circuit computations in PSAT, which is based on the classical method. PSAT computes the positive, negative and zero sequence Thevenin impedances seen at selected buses as well as the fault levels for all standard fault types. These include:  Three-phase fault (LLL)  Phase-to-phase fault (LL)  Phase-to-phase-to-ground fault (LLG)  Phase-to-ground fault (LG) Classical Short Circuit computation is based on the following assumptions and conditions:  Pre-fault voltages are set to unity  Transformer taps are kept as they are in the powerflow data (not set to unity)  All bus shunts and loads are ignored in positive, negative and zero sequence  Zero sequence mutual coupling of transmission lines is respected as specified in the Sequence data The computation results shown in the Short Circuit window as well as on the diagrams include:  Positive, negative, and zero sequence Thevenin impedances at selected buses, in polar or Cartesian form  Short circuit levels, in pu., kA or MVA, for all four types of faults at selected buses, in polar or Cartesian coordinates

14.1 How to Run Short Circuit Analysis After a powerflow case is loaded in PSAT, the Short Circuit command of the Solution menu opens the Short Circuit window. In this window, you specify the Sequence data for the powerflow case (if this data is not specified, PSAT uses default data), select the buses for which fault levels and Thevenin impedances are to be computed, and the format for the display of results. PSAT then displays the results in the table in the same window. The top part of the window allows you to:  Specify the Sequence data file by clicking the browse button beside the filename. The Open dialog appears where you can specify the file containing the sequence data. Current version of PSAT accepts the sequence data file in PSS/E version 28 or 29 format. If you do not specify this data, or uncheck the Use Sequence File box beside it, PSAT uses default sequence data.



 

Select the buses by using the Subsystem pull-down list. You may use the buttons beside the Subsystem pull-down list to define simple and composite subsystems. These and previously defined subsystems appear in the pull-down list, where you can select one of them. The subsystem pull-down list and its buttons function the same as those in the toolbar of PSAT main window (See section 4.4, 8.10 and 8.11). Specify the appearance of the results in the Layout and Options boxes. If you select User-Defined in the Layout box, the appearance of result table is customizable as described below. If you select Impedances, the result table shows the positive, negative and

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

93

PSAT User Manual



zero sequence Thevenin impedances, and if you select Faults, the result table shows the LLL, LL, LLG and LG fault levels. You may specify p.u., kA or MVA as Units for the display of fault levels in the Options box. You may also specify Polar or Cartesian as Format for the display of fault levels and Thevenin impedances.

You can make the above selections also by using the menus of the Short Circuit window. The table in the middle part of the window shows the results for all buses in the selected subsystem above. If you choose User-Defined for the Layout, you can customize the table by using the Setting menu (or right click on the title row of the table) as described in section 4.2 and 8.12. Otherwise, the table shows either the Thevenin impedances or fault levels as specified for the Layout. You may export the result table to a text file, Excel file, or clipboard by using the Edit menu. The lower part of the window shows the messages for short circuit computations. The Close button or Close command of File menu closes the Short Circuit window and returns to PSAT main window.

14.2 Menus of Short Circuit Window File menu contains: Close

Closes the window and return to PSAT main window.

Edit menu contains: Export to Text File

Exports the result table to a text file.

Export to Excel File

Exports the result table to an Excel file.

Export to Clipboard

Copies the result table to the clipboard.

Subsystem menu contains: Define Simple Subsystem

Opens the Simple Subsystem Selection dialog for defining simple subsystems.

Define Composite Subsystem

Opens the Composite Subsystem Selection dialog for defining composite subsystems.

Setting menu contains: Customize table

Opens the Table Customization dialog for customizing the User-defined layout of the table.

Layout

Selects User-defined, Impedances or Faults layout for the result table.

Unit

Selects p.u., kV or MVA as units of fault levels

Format

Selects Cartesian or Polar for the format of fault levels and Thevenin impedances.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

94

PSAT User Manual

Help menu contains the help commands as those in the Help menu of PSAT main window.

15 PSAT ASCII Powerflow File Format In the PSAT ASCII raw data file, the first line contains the bus identification code and the version number. The bus identification code indicates whether buses are addressed by bus number (1), bus name (2) or both (3). This code is relevant for all data sections with two exceptions. In the Bus Data section the bus name is always present, even with Code 1. In the Multi-terminal DC Data Section only the AC bus numbers are present with Code 3. The version number is 10.0 in this version of PSF. The Power System File consists of the following data sections: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20.

Solution history data Bus data Generator data Load data Load model data Fixed shunt data Switched shunt data Line data Fixed transformer data ULTC transformer data Impedance correction tables Fixed series capacitor data Switchable series capacitor data FACTS device data 3-winding transformer data Area interchange data Interface data Multi terminal DC data Zone data File section data

A header line identifies the beginning of each category of data. The header line has the following format: ** ** The first two characters of the header line must be "**", e.g., "** BUS DATA **". Following the section header line, the data for each item of the section (i.e. each bus of the Bus data section) are specified on one or more data records. Although the number and order of data items on each record are fixed, they are read "free format", separated by a comma or one or more blanks. The character string data must be enclosed in single quotes.

15.1 Solution History Data This section consists of six lines. The first three lines contain the case description (up to 80 characters per line).

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

95

PSAT User Manual

Date, time and the base MVA of the system are specified on the fourth line. Date and time must be entered as character strings. (It is strongly recommended to set the base MVA to 100.0.). The following data items are specified on the fifth line:

 Auto:

Solution algorithm specified as character string (default - Auto). There are four algorithms which can be selected for power flow solution namely: This is an automated solution algorithm where initially the fast decoupled method is used and if convergence tolerance is less than 1.0 (MW or MVAR), it switches to full Newton Raphson method. Furthermore, when this algorithm is selected with the flat start, the generators VAR limits are opened for the first 3 iterations.

FD(XB):

This is the Fast Decoupled method, where the R is neglected in B'.

NR:

This is the Newton Raphson method.

FD(BX):

This is the Fast Decoupled method where the R is neglected in B"

        

Maximum number of iterations (default 20). Convergence tolerance in terms of maximum MW or MVAR mismatch (default 1.0). Blow up limit in terms of maximum pu voltage magnitude deviations in each iteration (default 1.0). Acceleration factor. This factor is used to modify the amount of voltage correction when a bus is switched from PQ to PV (default 1.0). Zero impedance threshold. This is the impedance threshold below which the lines are treated as zero impedance and the buses at the two ends of the line are joined (default 0.00001). NOTE: If a branch is sectionalized, then there must be at least one section between the FROM and the TO buses with a series impedance that is greater than the zero impedance threshold. Voltage tolerance (default 0.0001). This is used to determine whether the voltage controls are satisfied. Control adjustment threshold (default 0.01). This is used to initiate the control adjustment. When the pu MW and MVAR mismatch during the previous iteration fall below this value, the control adjustment is initiated. Hot or flat start specified as character string (i.e. HOT OR FLAT. For flat start voltage for all buses (except the system swing bus) are set to magnitude of 1.0 and angle 0.0.

The solution control flags are specified on the sixth line. These flags are entered as character strings (i.e.) ON or OFF. The control options along with the default values are as follows: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14.

Area interchange control - OFF Switchable shunts voltage control - OFF Transformers voltage control - OFF Phase shifters MW control - OFF Transformers MVAR control - OFF Series Capacitors MW control - OFF Static tap changers voltage control - OFF Static tap changers MVAR control - OFF Static phase shifters MW control - OFF Limit generator MVAR - ON Three winding transformers voltage control - OFF Interfaces MW control - OFF Continuous shunts (SVC) voltage control - ON Generator remote voltage control – ON

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

96

PSAT User Manual

15. Three winding transformers MVAR control - OFF 16. Three winding transformers MW control - OFF 17. Limit swing generator MVAR - ON

15.2 Bus Data The data for each bus is specified on two lines and it consists of the following items: Bus number:

Unique number used to identify the bus (not given when the Bus Identification code is 2).

Bus name:

16 characters long bus name used to identify the bus. This name should be unique

Bus voltage:

Magnitude in pu and angle in degrees.

Bus kV:

Bus base kV.

Bus type:

In PSF, there are four bus types (default 1): 1. Load bus 2. Generator bus 3. System swing bus 4. Isolated bus (0 - Out of service; 1 - In service). If a bus is out of service, then the status of all the components connected to the bus is changed to out of service and the bus type is set to 4

Bus status:

Bus area:

Area number. A bus can belong to only one area.

Bus zone:

Zone number. The zones are not exclusive and a bus can have up to 6 different zone numbers.

Bus owner:

16 characters long bus ownership ID.

The following items are entered on the second line: Equipment name:

32 characters long bus equipment name

Bus latitude:

latitude of bus in degrees. Negative values are south of equator.

Bus longitude:

longitude of bus in degrees. Negative values are west of prime meridian.

15.3 Generator Data The generators in the network are represented in this section. A generator which is connected to a type 1 bus is considered to be out of service.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

97

PSAT User Manual

For local control, the generator bus voltage is maintained between V Hi and V Lo limits, as long as the required reactive power generation is between the specified limits. If the required MVAR generation is beyond the limits, the generator will not be able to regulate the bus voltage and it will be treated as fixed MVAR generation at QMAX or QMIN, unless the VAR limits are opened by setting the USCH Q flag to 1. For remote bus voltage control, the generator can be regulating the bus voltage by itself or be contributing to the control with other generators. The generator contributes MVAR to control the remote bus voltage as long as the generator bus voltage is between the specified limits and the required reactive power generation is also between the specified limits (unless VAR limits are open). The generator data is entered in three lines. The first line consists of the following items: Bus number:

Number of the bus where the generator is connected (not given when bus identification code is 2).

Bus name:

Name of the bus where the generator is connected (not given when bus identification code is 1).

ID:

8 characters long machine identifier which is used to distinguish among multiple machines connected to the same bus.

Status:

Machine status (1 - In service; 0 - Out of service; -1 – Not Available).

MW output:

Generator real power output in MW.

MVAR output:

Generator reactive power output in MVAR.

QMAX:

Maximum generator reactive power output in MVAR.

QMIN:

Minimum generator reactive power output in MVAR. When QMAX and QMIN are equal, the generator will have a fixed reactive power output.

V Hi limit:

Generator bus upper voltage limit in pu (default 1.5).

V Lo limit:

Generator bus lower voltage limit in pu (default 0.5).

Remote bus:

Remote bus number and/or name depending on bus identification code.

RMB voltage:

Remote bus desired voltage in pu. If there is more than one generator controlling a bus, the specified desired voltage should be the same for all the generators.

% Contr:

Percentage reactive power contribution of this generator to regulate the voltage at the remotely controlled bus (0 to 100). It is not necessary that the % contribution of all generators controlling a bus add up to 100. The total reactive power generation required to regulate the remote bus voltage is split between the controlling generators according to the % contribution.

The following items are entered on the second line: USCH Q:

Unscheduled reactive power generation flag (0 or 1). If the flag is set to one, the generator VAR limits are left open.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

98

PSAT User Manual

MVA:

Total MVA base of the units represented by this machine in MVA. When the real power output of the machines at a bus is zero, this value is used to split the required bus reactive power generation between the machines.

PMAX:

Maximum generator real power output in MW. This is the maximum continuous rating.

PMIN:

Minimum generator real power output in MW. This is the minimum machine load.

RS, XS:

Generator internal impedance in pu on generator MVA base. This data is not used in powerflow solutions.

RT, XT:

Step-up transformer impedance in pu on generator MVA base. This data is not used in powerflow solutions.

TAP:

Step-up transformer off-nominal turns ratio (from high tension to low tension) in pu. This data is not used in powerflow solutions.

The following items are entered on the third line: Equipment name

32 characters long generator equipment name.

Owner

16 characters long generator ownership ID. Default Owner is the owner of the generator bus.

GWMOD

Wind machine control mode: 0. Not a wind machine. 1. Wind machine whose reactive power limits are specified by QMAX and QMIN. 2. Wind machine whose reactive power limits are determined from the machine‟s active power output and GWPF; limits are of equal magnitude and opposite sign. 3. Wind machine with a fixed reactive power setting determined from the machine‟s active power output and GWPF; when GWPF is positive, the machine‟s reactive power has the same sign as its active power; when GWPF is negative, the machine‟s reactive power has the opposite sign of its active power. Wind machine power factor.

GWPF GBASLD

Base load flag: 0. Unit is not base-loaded. 1. Unit is base-loaded.

15.4 Load Data A bus can have more than one load connected to it. Each load is composed of 5 components, each component having its own load model. The load data is entered in three lines. The first line consists of the following items:

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

99

PSAT User Manual

Bus number:

Number of the bus where the load is connected (not given when bus identification code is 2).

Bus name:

Name of the bus where the load is connected (not given when bus identification code is 1).

Reference PQ:

Reference Complex PQ load in MW and MVAR obtained from base case.

PQ comp (1:4):

4 pairs of real and reactive parts of load components 1 to 4, in MW and MVAR. For load components with model -1, -2 and -4 (see below), these represent the nominal value of load at rated voltage. For components with model -3, these represent the load admittance (negative reactive part for inductive load) in MW and MVAR at rated voltage. For components with model +k, these represent P0 and Q0 factors (see Load Model Data below).

The following items are specified on the second line: PQ comp (5):

1 pair of real and reactive parts of load component 5, in MW and MVAR.

Load model:

5 load model numbers of load components 1 to 5. The load model number can be: -1 = Constant MVA -2 = Constant current load -3 = Constant impedance load +k = Model number "k" represented in the load model table

Load type:

The following load types are available (default 1): 1 - Industrial 2 - Firm 3 - Non-industrial 16 characters long load ownership ID.

Load owner: Load ID:

8 characters long load identifier used to distinguish among multiple loads at the same bus.

Scalable:

Controls if load should be adjusted when performing load scaling or if load is fixed (1 – Scalable; 2- Fixed) Default is 1.

The following items are specified on the third line: Equipment Name:

32 characters long equipment name.

Area:

Load area number. Default is bus area.

Zone:

Load zone number. Default is bus zone.

Status:

Load status (1 - In service; 0 - Out of service). Default Status is 1.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

100

PSAT User Manual

15.5 Load Model Data The load model table is used in conjunction with the load data to represent voltage dependent loads. A voltage dependent load component with load model k is represented as: P load = P0 (A1k VN1k + A2k VN2k + A3k VN3k) Q load = Q0 (B1k VM1k + B2k VM2k + B3k VM3k) where P0 and Q0 are specified as part of load data (see PQ Comp above) and A1 , A2 , A3 , N1 , N2, N3 , B1 , B2 , B3 , M1 , M2 and M3 are parameters of the model specified in this section. Each line of data in this section consists of: Model number:

The load model number (+k).

A values:

Three real numbers specifying the coefficients for P load.

N values:

Three real numbers specifying the exponents for P load.

B values:

Three real numbers specifying the coefficients for Q load.

M values:

Three real numbers specifying the exponents for Q load.

15.6 Fixed Shunt Data The data for fixed shunts which are connected to a bus are given in this section. A bus can have more than one shunt connected to it. The data for fixed shunts are specified on two lines and it consists of the following items: Bus number:

Number of the bus where the shunt is connected (not given when bus identification code is 2).

Bus name:

Name of the bus where the shunt is connected (not given when bus identification code is 1).

Admittance:

Shunt admittance in MW and MVAR at unity voltage (positive reactive part for capacitance).

Type:

Bus shunt type. The following types are available (default 1): 1 - Actual 2 - Equivalent

Fx Sh Owner:

16 characters long ownership ID.

Fx Sh ID:

8 characters long fixed shunt identifier to distinguish among multiple shunts at the same bus.

The following items are specified on the second line: Equipment Name:

32 characters long equipment name.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

101

PSAT User Manual

Fx Sh Status:

Fixed shunt status (1 - In service; 0 - Out of service). Default Status is 1.

15.7 Switchable Shunt / SVC / STATCON Data The data for switchable shunts is given in this section. The switchable shunt and SVC are represented with up to eight blocks of admittance, each of which can consist of up to 99 steps of the specified block admittance. For local control, the shunt bus voltage is maintained between the V Hi and V Lo limits, as long as the required reactive power can be supplied by the shunt. SVC and STATCON maintain the voltage on the droop characteristic (straight line from V Lo to V Hi). For remote bus voltage control, the switchable shunt can be regulating the bus voltage by itself or by contributing to the control with other shunts. The switchable shunt contributes to the remote bus voltage regulation, as long as the required reactive power can be supplied and the voltage of the bus, the bus to which the switchable shunt is connected, lies between specified limits. The switchable shunt / SVC / STATCON data is entered in three lines, the first line consist of the following items: Bus number:

Number of the bus where the shunt is connected (not given when bus identification code is 2).

Bus name:

Name of the bus where the shunt is connected (not given when bus identification code is 1).

Mode:

Switchable shunt control mode 0 - Frozen 1 - Discrete 2 - Continuous

3 - SVC

4 - STATCON

Status:

Status of switchable shunt (0 - Out of service; 1 - In service).

V Hi limit:

Switchable shunt bus upper voltage limit in pu (default 1.5).

V Lo limit:

Switchable shunt bus lower voltage limit in pu (default 0.5).

Remote bus:

Remote bus number and/or name depending on bus identification code.

RMB voltage:

Remote bus desired voltage in pu. If there is more than one switchable shunt controlling a bus, the specified desired voltage should be the same for all the switchable shunts.

% Contr:

Percent contribution of this shunt to regulate the voltage at the remote bus (0 to 100). It is not necessary that the % contribution of all shunts controlling the same remote bus add up to 100. The reactive power required to regulate the remote bus voltage is split between the controlling shunts according to the % contribution.

Y initial:

Initial switchable shunt admittance in MW and MVAR at unity voltage (positive reactive part for capacitance).

SWS owner:

16 characters long ownership ID.

The second line of the switchable shunt for SVC data consists of the following items: This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

102

PSAT User Manual

SWS ID:

8 characters long identifier to distinguish between multiple switched shunts at the same bus.

Ni:

Number of steps for block i.

Bi:

Susceptance increment for each of Ni steps in block i in MVAR at unity voltage. There must be 8 [Ni; Bi] pairs. After the first Ni with zero value, the rest of Ni and Bi are set to zero. The switchable shunt blocks may be entirely inductive or capacitive. In this case, the shunt blocks are in the order in which they are switched on. If both types exist, inductive blocks must be entered first

The second line of the switchable shunt for STATCON data consists of the following items: SWS ID:

8 characters long identifier to distinguish between multiple shunts at the same bus.

IMAX:

STATCON current limit (in Amps).

The third line of the switchable shunt data (SVC or STATCON) consists of the following items: Equipment Name:

32 characters long equipment name.

Remote High V limit:

Remote bus high voltage limit

Remote High V limit:

Remote bus low voltage limit.

15.8 Line Data The AC transmission line data are supplied in this section. The line data is entered in three lines. The first line consists of the following items: BUS1 number:

Number of the FROM bus (not given when bus identification code is 2).

BUS1 name:

Name of the FROM bus (not given when bus identification code is 1).

BUS2 number:

Number of the TO bus (not given when the bus identification code is 2).

BUS2 name:

Name of the TO bus (not given when bus identification code is 1).

Circuit ID:

8 characters line circuit identifier.

Section #:

Line section number (default 1).

Status:

Branch status (0 - Out of service; l - In service)

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

103

PSAT User Manual

Meter end:

1 character metered end identifier used for area interchange control ('F' or blank - FROM; 'T' - TO).

Impedance:

Complex impedance of the line in pu. If the magnitude of the line impedance is less than the specified zero impedance threshold, the two ends of the lines are joined when solving the power flow.

Charging:

Complex admittance of line charging in pu.

The following items are entered on the second line: FROM shunt:

Complex admittance of the line shunt at the FROM bus in pu.

TO shunt:

Complex admittance of the line shunt at the TO bus in pu.

Rating:

6 branch MVA ratings at nominal voltage.

Rating group:

Line rating group number (default 1).

Zone:

6 zone numbers. A line can belong to up to 6 different zones. Zone numbers should be the same as that of BUS1 or BUS2.

Type:

Line type (default 1). 1 - Normal; 2 - Equivalent line; 3 - Cable

The following items are entered on the third line: Equipment name

32 characters long line equipment name.

Owner

16 characters long line ownership ID. Default Owner is the owner of the line BUS1.

Length

Line length in miles. Default Length is zero miles.

For sectionalized branches, the BUS1 and BUS2 of all sections must be the same (i.e. they can not be in reverse order).

15.9 Fixed Transformer Data The data for fixed transformers and phase shifters is given in this section. BUS1 is the tapped side bus and BUS2 is the impedance side bus. The data is entered in four lines, the items on the first line are as follows: BUS1 number:

Number of the FROM bus (not given when bus identification code is 2).

BUS1 name:

Name of the FROM bus (not given when bus identification code is 1).

BUS2 number:

Number of the TO bus (not given when bus identification code is 2).

BUS2 name:

Name of the TO bus (not given when bus identification code is 1).

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

104

PSAT User Manual

Circuit ID:

8 characters branch circuit identifier.

Section #:

Branch section number (default 1).

Status:

Branch status (0 - Out of service; 1 - In service).

Meter end:

1 character metered end identifier used for area interchange control ('F' or blank - FROM; 'T' - TO).

ONR:

Transformer turns ratio in pu.

Angle:

Transformer phase shift angle in degrees.

Impedance:

Complex impedance of the branch in pu.

Charging:

Complex admittance of branch charging in pu.

The following items are specified on the second line: FROM MAG:

Complex admittance of transformer magnetization to be represented at the FROM bus in pu.

TO MAG:

Complex admittance of transformer magnetization to be represented at the TO bus in pu.

Rating:

6 branch MVA ratings at nominal voltage.

Rating Group:

Branch rating group number (default 1).

MVA:

Transformer rated MVA.

The following items are specified on the third line: Zone:

6 zone numbers. A branch can belong to up to 6 different zones. Zone numbers should be the same as that of BUS1 or BUS2.

The following items are specified on the fourth line: Equipment Name :

32 characters long equipment name.

Name:

16 characters long characteristic name. This name is not required to be unique.

Owner :

16 characters long transformer ownership ID. Default owner is the owner of the transformer BUS1.

For sectionalized branch, the BUS1 and BUS2 of all sections must be the same (i.e. they can not be in reverse order).

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

105

PSAT User Manual

NOTE : If a branch is sectionalized, not more than one section can be a fixed transformer or ULTC transformer or static tap changer/phase shifter.

15.10

ULTC Transformer Data

The 2-winding ULTC transformer and phase shifter data are entered on five lines. The primary winding is on BUS1 side and can have a variable turns ratio. The first line of data consists of the following items: BUS1 number:

Number of the FROM bus (not given when bus identification code is 2).

BUS1 name:

Name of the FROM bus (not given when bus identification code is 1.

BUS2 number:

Number of the TO bus (not given when bus identification code is 2).

BUS2 name:

Name of the TO bus (not given when bus identification code is 1).

Circuit ID:

16 characters branch circuit identifier.

Section #:

Branch section number (default 1).

Status:

Branch status (0 - Out of service; 1 - In service).

Meter end:

1 character metered end identifier used for area interchange control ('F' or blank - FROM; 'T' - TO).

FROM Ratio:

Transformer FROM-side (primary) turns ratio in pu.

TO Ratio:

Transformer TO-side (secondary) turns ratio in pu.

Angle:

Transformer phase shift angle in degrees (when positive, at zero current, BUS1 angle leads BUS2 angle).

Impedance:

Complex impedance of the branch in pu.

Charging:

Complex admittance of branch charging in pu.

The following items are specified on the second line: FROM Mag:

Complex admittance of transformer magnetization to be represented at the FROM bus in pu.

TO Mag:

Complex admittance of transformer magnetization to be represented at the TO bus in pu.

Max. Ratio:

Upper limit for FROM-side turns ratio in pu (default 1.5).

Min. Ratio:

Lower limit for FROM-side turns ratio in pu (default 0.5).

Step Size:

FROM-side turns ratio step size in pu.

Max. Angle:

Upper limit for phase shift angle in degrees.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

106

PSAT User Manual

Min. Angle:

Lower limit for phase shift angle in degrees.

# of Ang. Stp:

Number of phase shift angle steps. Currently the number of angle steps is neglected.

Control type:

1 character control type identifier (set to 'V' if a blank is entered): 'V' - Self or remote bus Voltage control 'Q' - MVAR flow control 'P' - MW flow control

Control side:

1 character that specifies the controlled voltage as being on the FROM side or TO side ('F' or blank - FROM or tap side; 'T' - TO or impedance side).

Control flag:

Control flag (0 - Disable the control; 1 - Enable the control).

Max. MW:

Upper limit for real power flow (in MW) through the transformer.

Min. MW:

Lower limit for real power flow (in MW) through the transformer.

The following items are specified on the third line: Max. MVAR:

Upper limit for reactive power flow (in MVAR) through the transformer.

Min MVAR:

Lower limit for reactive power flow (in MVAR) through the transformer.

V Hi limit:

Upper limit for controlled bus voltage in pu (default 1.5).

V Lo limit:

Lower limit for controlled bus voltage in pu (default 0.5).

CNTRL Bus:

Controlled bus number and/or name depending on bus identification code.

Z Corr. Table:

Number of transformer or phase shifter impedance correction table. If non-zero, the branch impedance will be a function of the turns ratio or the phase shift angle.

Rating:

6 branch MVA ratings at nominal voltage

The following items are specified on the fourth line: Rating group:

Branch rating group number (default 1).

MVA:

Transformer rated MVA.

Zone:

6 zone numbers. A branch can belong to up to 6 different zones. Zone numbers should be the same as that of BUS1 or BUS2.

The following items are specified on the fifth line: Equipment Name:

32 characters long equipment name.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

107

PSAT User Manual

Name:

16 characters long characteristic name. This name is not required to be unique.

Owner :

16 characters long transformer ownership ID. Default Owner is the owner of the transformer BUS1.

For sectionalized branches, the BUS1 and BUS2 of all sections must be the same (i.e. they cannot be in reverse order). NOTE: If a branch is sectionalized, not more than one section can be a fixed transformer or ULTC transformer or static tap changer/phase shifter.

15.11

Impedance Correction Tables

This section provides the data for the transformer or phase shifter impedance correction tables used to model the change in the branch impedance as the turns ratio or the phase shift angle is adjusted. The table consists of the following items: Table #

Impedance correction table number.

Ti:

ONR in pu or phase shift angle in degrees.

Fi:

Correction factor by which the nominal branch impedance is multiplied to obtain the actual impedance for the corresponding Ti.

The first six pairs of Ti and Fi are entered on the first line and the next five pairs are specified on the second line.

15.12

Fixed Series Capacitor Data

The fixed series compensator data are given in this section. The data for each series compensator is entered on two lines and the first line consists of the following items: BUS1 number:

Number of the FROM bus (not given when bus identification code is 2).

BUS2 name:

Name of the FROM bus (not given when bus identification code is 1).

BUS2 number:

Number of the TO bus (not given when bus identification code is 2).

BUS2 name:

Name of the TO bus (not given when bus identification code is 1).

Circuit ID:

8 characters branch circuit identifier.

Section #:

Branch section number (default 1).

Reactance:

Fixed series compensator reactance in pu.

Status:

Branch status (0 – Out of service; 1 – In service).

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

108

PSAT User Manual

Meter end:

1 character metered end identifier („F‟ or blank – FROM; „T‟ – TO).

I Rating:

Series compensator current rating in AMPs.

kV Rating:

Series compensator kV rating.

Zone:

6 zone numbers. A branch can belong to up to 6 different zones. Zone numbers should be the same as that of BUS1 or BUS2.

The following items are specified on the second line: Equipment Name:

32 characters long equipment name.

Owner :

16 characters long transformer ownership ID. Default Owner is the owner of the transformer BUS1.

For sectionalized branches, the BUS1 and BUS2 of all sections must be the same (i.e. they cannot be in reverse order).

15.13

Switchable Series Capacitor Data

The switchable series compensator data are given in this section. The data is entered on three lines. The first line consists of the following items: BUS1 number:

Number of the FROM bus (not given when bus identification code is 2).

BUS1 name:

Name of the FROM bus (not given when bus identification code is 1).

BUS2 number:

Number of the TO bus (not given when bus identification code is 2).

BUS2 name:

Name of the TO bus (not given when bus identification code is 1).

Circuit ID:

16 characters branch circuit identifier.

Section #:

Branch section number (default 1).

Status:

Branch status (0 - Out of service; 1 - In service).

Meter end:

1 character metered end identifier ('F' or blank - FROM; 'T' - TO).

X:

Initial compensator reactance in pu.

X Max.:

Maximum series compensator reactance in pu.

X Min.:

Minimum series compensator reactance in pu.

# of steps:

Number of steps between X Min and X Max.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

109

PSAT User Manual

Control flag:

Control flag (0 - Control is off; 1 - Current control; 2 - MW flow control). Please note that current control is currently not implemented.

Max. MW:

Upper limit for real power flow (in MW) through the series compensator.

Min. MW:

Lower limit for real power flow (in MW) through the series compensator.

The following items are specified on the second line: I Rating:

Series compensator current rating in AMPs.

kV Rating:

Series compensator kV rating.

Zone:

6 zone numbers. A branch can belong to up to 6 different zones. Zone numbers should be the same as that of BUS1 or BUS2.

Owner:

16 characters long transformer ownership ID. Default owner is the owner of the transformer BUS1.

Equipment Name:

32 characters long equipment name

The following items are specified on the third line: Equipment Name:

32 characters long equipment name.

Owner :

16 characters long transformer ownership ID. Default Owner is the owner of the transformer BUS1.

For sectionalized branches, the BUS1 and BUS2 of all sections must be the same (i.e. they cannot be in reverse order).

15.14

Static Tap Changer / Phase Regulator Data

The Static Tap Changer / Phase Regulator data is given in this section. BUS1 is the tapped side bus and BUS2 is the impedance side bus. The data is entered on five lines. The first line consists of the following items: BUS1 number:

Number of the FROM bus (not given when bus identification code is 2).

BUS1 name:

Name of the FROM bus (not given when bus identification code is 1).

BUS2 number:

Number of the TO bus (not given when bus identification code is 2).

BUS2 name:

Name of the TO bus (not given when bus identification code is 1).

Circuit ID:

16 characters branch circuit identifier.

Section #:

Branch section number (default 1).

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

110

PSAT User Manual

Status:

Branch status (0 - Out of service; 1 - In service).

Meter end:

1 character metered end identifier user for area interchange control ('F' or blank - FROM; 'T' - TO).

Impedance:

Complex impedance of the branch in pu.

Charging:

Complex admittance of branch charging in pu.

Name:

16 characters long characteristic name. This name is not required to be unique.

The following items are specified on the second line: FROM MAG:

Complex admittance of magnetization in pu, to be represented at the FROM bus.

TO MAG:

Complex admittance of magnetization in pu, to be represented at the TO bus.

TC range:

Tap changer range (factor) in pu.

PS range:

Phase shifter range (factor) in pu.

TC wdg psn:

Tap changer winding position (split) (between 0.0 and 1.0).

PS wdg psn:

Phase Shifter winding position (split) (between 0.0 and 1.0).

TC ratio:

Tap changer ratio in pu.

Mx TC ratio:

Maximum tap changer ratio in pu.

Mn TC ratio:

Minimum tap changer ratio in pu.

PS ratio:

Phase shifter ratio in pu.

MX PS ratio:

Maximum phase shifter ratio in pu.

Mn PS ratio:

Minimum phase shifter ratio in pu.

Control type:

Two-character control type (set to „V‟ if a blank is entered): „V „ - Voltage control „Q „ - MVAR flow control „P „ - MW flow control „PV‟ - MW flow and voltage control „PQ‟ - MW flow and MVAR flow control

The following items are specified on the third line: Control side:

This variable defines the control side (F – FROM or tap side; T – TO or impedance side) (set to F if a blank is entered).

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

111

PSAT User Manual

Control flag:

Control flag (0 – Disable the control; 1 – Enable the control).

Max. MW:

Upper limit for real power flow (in MW) through STP (default 9999).

Min. MW:

Lower limit for real power flow (in MW) through STP (default -9999).

Max. MVAR:

Upper limit for reactive power flow (in MVAR) through STP (default 9999).

Min. MVAR:

Lower limit for reactive power flow (in MVAR) through STP (default 9999).

V Hi limit:

Upper limit for controlled bus voltage in pu (default 1.5).

V Lo limit:

Lower limit for controlled bus voltage in pu (default 0.5).

CNTRL Bus:

Controlled bus number and/or name depending on bus identification code.

Z Corr. TC:

Number of transformer impedance correction table for tap changer. If nonzero, transformer impedance will be a function of the tap change ratio.

Z Corr. PS:

Number of transformer impedance correction table for phase shifter. If non-zero, transformer impedance will be a function of the phase shift ratio.

MVA:

Rated MVA.

The following items are entered on the fourth line: Rating:

6 branch MVA ratings at nominal voltage

Rating group:

Branch rating group number (default 1).

Zone:

6 zone numbers. A branch can belong to up to 6 different zones. Zone number should be the same as that of BUS1 or BUS2.

Owner :

16 characters long transformer ownership ID. Default Owner is the owner of the transformer BUS1. 32 characters long equipment name.

Equipment name :

The following items are specified on the fifth line: Equipment Name:

32 characters long equipment name.

Name:

16 characters long characteristic name. This name is not required to be unique.

Owner :

16 characters long transformer ownership ID. Default Owner is the owner of the transformer BUS1.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

112

PSAT User Manual

For sectionalized branches, the BUSI and BUS2 of all sections must be the same (i.e. they cannot be in reverse order). NOTE: If a branch is sectionalized, not more than one section can be a fixed transformer or ULTC transformer or static tap changer / phase shifter.

15.15

3-Winding Transformer Data

The three winding transformer data are entered on nine lines. The first line of data consists of the following items: BUS1 number:

Number of primary bus (not given when bus identification code is 2).

BUS1 name:

Name of primary bus (not given when bus identification code is 1).

BUS2 number:

Number of secondary bus (not given when bus identification code is 2).

BUS2 name:

Name of secondary bus (not given when bus identification code is 1).

BUS3 number:

Number of tertiary bus (not given when bus identification code is 2).

BUS3 name:

Name of tertiary bus (not given when bus identification code is 1).

Circuit ID:

16 characters branch circuit identifier.

Status:

Transformer status (0 – Out of service; 1 – In service). In addition one winding may be out of service with the remaining windings in service. 2 – only winding two out of service; 3 – only winding three out of service; 4 – only winding one out of service.

Non-Metered end:

Non-metered end (P – Primary bus; S – Secondary bus; T –Tertiary bus) (Set to P if a blank is entered).

Name:

16 characters long characteristic name. This name is not required to be unique.

Equipment Name:

32 characters long equipment name.

The following items are specified on the second line: Ratio 1:

Turns ratio in pu for the primary winding.

Angle 1:

Phase shift angle in degrees for the primary winding.

Ratio 2:

Turns ratio in pu for the secondary winding.

Angle 2:

Phase shift angle in degrees for the secondary winding.

Ratio 3:

Turns ratio in pu for the tertiary winding.

Angle 3:

Phase shift angle in degrees for the tertiary winding

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

113

PSAT User Manual

The following items are specified on the third line: Impedance 1:

Complex series impedance of primary winding in pu.

Impedance 2:

Complex series impedance of secondary winding in pu.

Impedance 3:

Complex series impedance of tertiary winding in pu.

Magnetization 1:

Complex admittance of magnetization in pu for the primary winding.

Magnetization 2:

Complex admittance of magnetization in pu for the secondary winding.

Magnetization 3:

Complex admittance of magnetization in pu for the tertiary winding.

The primary winding control parameters are specified on the fourth line: Max. Ratio/Phase Shift Angle:

Upper limit for turns ratio or phase shift angle.

Min. Ratio/Phase Shift Angle:

Lower limit for turns ratio or phase shift angle.

Step Size:

Turns ratio step size in pu

Control side:

Location of the controlled bus (T - Tapped side; Z - Impedance side) (Set to T if blank is entered).

Control flag:

Control flag (0 – Disable the control; 1 – Voltage control; 2 – MVar control; 10 – MW control).

V hi:

Upper limit for controlled variable.

V lo:

Lower limit for controlled variable.

CNTRL bus:

Controlled bus number and/or name depending on the bus identification code.

Z Corr. Table:

Number of transformer impedance correction table. If positive, the impedance of the winding will be a function of its turns ratio/phase shift angle.

The secondary winding control parameters are specified on the fifth line: Max. Ratio/Phase Shift Angle:

Upper limit for turns ratio or phase shift angle.

Min. Ratio/Phase Shift Angle:

Lower limit for turns ratio or phase shift angle.

Step Size:

Turns ratio step size in pu

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

114

PSAT User Manual

Control side:

Location of the controlled bus (T - Tapped side; Z - Impedance side) (Set to T if blank is entered).

Control flag:

Control flag (0 – Disable the control; 1 – Voltage control; 2 – MVar control; 10 – MW control).

V hi:

Upper limit for controlled variable.

V lo:

Lower limit for controlled variable.

CNTRL bus:

Controlled bus number and/or name depending on the bus identification code.

Z Corr. Table:

Number of transformer impedance correction table. If positive, the impedance of the winding will be a function of its turns ratio/phase shift angle.

The tertiary winding control parameters are specified on the sixth line: Max. Ratio/Phase Shift Angle:

Upper limit for turns ratio or phase shift angle.

Min. Ratio/Phase Shift Angle:

Lower limit for turns ratio or phase shift angle.

Step Size:

Turns ratio step size in pu

Control side:

Location of the controlled bus (T - Tapped side; Z - Impedance side) (Set to T if blank is entered).

Control flag:

Control flag (0 – Disable the control; 1 – Voltage control; 2 – MVar control; 10 – MW control).

V hi:

Upper limit for controlled variable.

V lo:

Lower limit for controlled variable.

CNTRL bus:

Controlled bus number and/or name depending on the bus identification code.

Z Corr. Table:

Number of transformer impedance correction table. If positive, the impedance of the winding will be a function of its turns ratio/phase shift angle.

The following items are entered in the seventh line: Charging 1:

Complex admittance of charging in pu for the primary winding.

Charging 2:

Complex admittance of charging in pu for the secondary winding.

Charging 3:

Complex admittance of charging in pu for the tertiary winding.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

115

PSAT User Manual

Primary Rating:

6 ratings in MVA for the primary winding.

Rating group:

Transformer rating group (default 1).

MVA:

Transformer rated MVA.

Owner :

16 characters long transformer ownership ID. Default Owner is the owner of the transformer BUS1.

The following items are entered in the eighth line: Secondary Rating:

6 ratings in MVA for the secondary winding.

Tertiary Rating:

6 ratings in MVA for the tertiary winding.

The following items are specified on the ninth line: Equipment Name:

32 characters long equipment name.

Name:

16 characters long characteristic name. This name is not required to be unique.

Owner :

16 characters long transformer ownership ID. Default Owner is the owner of the transformer BUS1.

15.16 Area Interchange Data Area interchange control data are given in this section. The data consist of the following items: Number:

Area interchange number.

Name:

Area interchange name (16 characters).

Desired flow:

Desired real power export in MW.

Tolerance:

Real power interchange tolerance in MW (default 10.0).

Slack bus:

Number or name (depending on bus identification code) of area slack bus for area interchange control. The bus must be a generator in this area. In the areas containing system swing bus, that swing bus must be specified as area slack bus.

Description:

60 character text description of area interchange

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

116

PSAT User Manual

15.17 Interface Data In this section, the first three characters in each line of data must correspond to one of the following codes:

   

INT - Interface data IBG - Controlling bus group data IGU - Generator unit data IBR - Branch data

After each interface record, the interface branch records must be entered. If the interface flow is being controlled, the corresponding controlling bus group records should be entered. Each controlling bus group record should be followed by the records of the generator units that belong to that controlling bus group. Interface Record Code:

INT

Number:

Interface number.

Name:

16 character interface name.

Description:

60 character interface description.

Mode:

Interface control mode (OFF - Control off, PRI - Control by priority; PER - Control by percentage) (Set to OFF if a blank is entered).

Desired flow:

Desired MW flow through the interface.

Flow tolerance:

Flow tolerance in MW (default 10.0).

Controlling Bus Group record Code:

IBG

Number:

Controlling bus group number.

Name:

16 character controlling bus group name.

Location:

Controlling bus group location (F - From side; T - To side) (Set to F if a blank is entered).

Mode:

Group control mode (OFF - Control off; PRI - Control by priority; PER - Control by percentage) (Set to OFF if a blank is entered).

Priority:

Priority in contributing MW for interface control.

Percent share:

Percent of required MW that will be contributed by this controlling bus group for interface control.

Generator Unit Record

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

117

PSAT User Manual

Code:

IGU

Bus number:

Number of the bus where the generator is connected (not given when bus identification code is 2).

Bus name:

Name of the bus where the generator is connected (not given when bus identification code is 1).

Unit ID:

8 character long machine identifier which is used to distinguish among multiple machines connected to the same bus (set to 1 if a blank is entered).

Participat. mode:

Participation mode (YES - Participate in control; NO - Do not participate in control) (Set to NO if a blank is entered).

Priority:

Priority in contributing MW to the controlling bus group for interface control.

Percent share:

Percent of required MW that will be contributed by this generating unit to the controlling bus group for interface control.

Branch Record Code:

IBR

BUS I number:

Number of the FROM bus (not given when bus identification code is 2).

BUS 1 name:

Name of the FROM bus (not given when bus identification code is 1).

BUS2 number:

Number of the TO bus (not given when bus identification code is 2).

BUS2 name:

Name of the TO bus (not given when bus identification code is 1).

Circuit ID:

8 character branch circuit identifier.

Section #:

Branch section number (default 1).

15.18

Multi-Terminal DC Data

The multi-terminal DC data is similar to the format used in EPRI RP1964-4 project with some exceptions (mainly for newly added features). This data is specified in free format in the PSF raw data file except for the Miscellaneous data records which are specified in fixed format exactly the same as in RP1964-4.

15.18.1

Line Commutated Converters

A line commutated converter is connected at two points to the DC network and at one point to the AC system. Parallel converters with the same connections are given different circuit numbers. The first DC terminal of a converter has a voltage which is positive with respect to the voltage at the second terminal.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

118

PSAT User Manual

The converter connects to the AC system at the primary terminal of the converter transformer and the transformer description is part of the DC data. One DC node name is reserved. This name, GROUND, represents the true zero voltage bus and is sometimes referred to as remote ground or remote earth. Two records are required to describe each converter in the DC network. First Converter Record The following are the data items that appear on this record. Note that the transformer reactance or its derivative, the commutating reactance can be supplied in two ways. In one way, the commutating reactance in ohms/bridge is specified and the transformer MVA (on the second converter record) is set to zero. In the other way, the transformer reactance in pu and the transformer MVA rating are both specified to enable the program to calculate the commutating reactance. These quantities must be consistent with the value specified for the number of bridges in series. All items in the first converter record are mandatory. Code:

'BD'

Change:

' ' (Blank) -base case, no changes 'D' - delete data associated with converter 'M' - change the data provided for the converter

DCBUS1:

Name of first DC terminal (8 characters long).

DCBUS2:

Name of second DC terminal (8 characters long).

ACBUS number or name:

AC bus number (for bus identification code equal to 1 or 3) or AC bus name (for bus identification code equal to 2). 8 characters long.

CKT:

Circuit number (one digit).

Group

3 character group identifier which is used for solution reporting purposes.

Zone:

Converter zone number.

No. of bridges:

Number of series bridges.

Xc:

Commutating reactance in ohms per bridge when transformer MVA on the BZ card is zero, otherwise, in pu based on transformer MVA.

Voltage ratio:

Nominal ratio of the secondary voltage (DC side) of converter transformer to the primary voltage (AC side).

Tap step:

Tap step in percent.

Tap min:

Minimum tap setting in pu.

Tap max:

Maximum tap setting in pu.

Alpha min:

Minimum alpha in degrees.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

119

PSAT User Manual

Alpha max:

Maximum alpha in degrees.

Gamma min:

Minimum gamma in degrees.

Imax:

Maximum DC current in amps.

Second Converter Record On this record, it is necessary to specify two setpoints for the converter. These setpoints must be consistent with the desired solution and should not over specify the problem. The two letter set point descriptions (two of them must be entered as CTRL MODE) are: VD - DC voltage in kV (+ve at rectifier and inverter) ID - DC current in amps (+ve at rectifier and -ve at inverter) PA - Real power in MW (-ve at rectifier and +ve at inverter) QA - Reactive power in MVAR (-ve at rectifier and inverter) AL - Firing angle in degrees (+ve at rectifier and inverter) GA - Extinction angle in degrees (+ve at rectifier and inverter) AT - Transformer tap in pu (+ve at rectifier and inverter) Not all combinations of the above variables are appropriate or desirable. The combinations of VD and ID, VD and PA, and ID and PA result in invalid converter specification and a solution is not attempted. The combination of AL and GA is not recommended but is acceptable. Numerical values for the set points must be entered as SP1 and SP2 in the same order as the CTRL MODE description. For example, if the DC voltage and the converter alpha are to be specified, then the CTRL MODE will be VDAL and set point 1 will be the desired voltage and set point 2 will be the desired alpha. Sign conventions as described above must be followed when specifying the converter set points. All items in the second converter record are mandatory. Code:

'BZ'

Change:

' ' (Blank) -base case, no changes 'D' - delete data associated with converter 'M' - change the data provided for the converter

DCBUS1:

Name of the first DC terminal (8 characters long).

DCBUS2:

Name of second DC terminal (8 characters long).

ACBUS number or name:

AC bus number (for bus identification code equal to 1 or 3) or AC bus name (for bus identification code equal to 2). 8 characters long.

CKT:

Circuit number (one digit).

CTRL MODE:

4 character set point description.

SP1:

Converter set point 1.

SP2:

Converter set point 2.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

120

PSAT User Manual

Type:

1 character that identifies the converter as a rectifier or an inverter ('R': Rectifier; 'I': Inverter).

Trans. MVA:

Transformer MVA rating.

Pmin:

Minimum real power in MW.

Pmax:

Maximum real power in MW.

Qmin:

Minimum reactive power in MVAR.

Qmax:

Maximum reactive power in MVAR.

BiasR:

Voltage compounding resistance in Ohms.

Base kV:

Base voltage of transformer primary side in kV (if zero it is set to the base kV of AC bus).

Note that some of the data provided by the converter records such as tap step, minimum and maximum tap, maximum current, minimum and maximum real and reactive powers and bias ohms are only used by central schedulers.

15.18.2

DC Lines

A DC line is specified in one record. Each line has two DC buses and a circuit number to describe its connection with the rest of the network. The line, for power flow purposes, if fully defined once the value is given for its resistance, which must be nonzero. Inductance and capacitance data are used in the stability program. Note that the two capacitance values do not have to be equal and either can be zero. The primary use of this unequal capacitance model will be in situations where the DC filter capacitance or the electrode line surge capacitance is significant. All items in the line record are mandatory. Code:

'LD'

Change:

' ' (Blank) -base case, no changes 'D' - delete data associated with converter 'M' - change the data provided for the converter

DCBUS1:

Name of the first DC terminal (8 characters long).

DCBUS2:

Name of second DC terminal (8 characters long).

CKT:

Circuit number (one digit).

Group:

3 character group identifier which is used for solution reporting purposes.

Zone:

Zone number (one or two digits).

Owner:

3 character ownership ID.

Rdc:

Line resistance in Ohms (must be nonzero).

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

121

PSAT User Manual

Ldc:

Line inductance in mH.

Cdca:

Capacitance at DCBUS1 in microF.

Cdcb:

Capacitance at DCBUS2 in microF.

Imax:

Maximum current in amps.

Mend:

1 character metered end identifier ('F' - DCBUS1; 'T' - DCBUS2).

15.18.3

DC Breakers

A DC breaker is specified by one record. Each breaker has two DC buses and a circuit number to describe its connection with the rest of the network. All items in the breaker record are mandatory. Code:

'LB'

Change:

' ' (Blank) -base case, no changes 'D' - delete data associated with converter 'M' - change the data provided for the converter

DCBUS1:

Name of the first DC terminal (8 characters long).

DCBUS2:

Name of second DC terminal (8 characters long).

CKT:

Circuit number (one digit).

Group:

3 character group identifier which is used for solution reporting purposes.

Zone:

Zone number (one or two digits).

Owner:

3 character ownership ID.

Status:

'CLOSED' or 'OPEN'

15.18.4

DC Buses

Code:

'DA'

Change:

Not used (one character)

DCBUS:

Name of the bus

Area:

Area number of the bus (up to 4 digits).

Zone:

Zone number of the bus (up to 4 digits).

15.18.5

Miscellaneous Data

All other DC data corresponding to control of the DC solution and the central schedulers is provided in a format identical to the one used in EPRI RP 1964-4. This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

122

PSAT User Manual

15.18.6

Voltage-Sourced Converter

The VSC data is represented by FD and FZ records, similar to the BD and BZ records of line commutation converters. Optionally, there can be an additional FV record for the series VSC of UPFC model as described below: "FD" record: Code:

'FD'

Change:

' ' (Blank) - no change 'D' - delete data associated with converter 'M' - change the data provided for the converter

DC bus 1 Name

DC node positive connection (8 characters long)

DC bus 2 Name

DC node negative connection (8 characters long)

AC bus 1 Number or Name

First AC bus number (for bus identification code equal to 1 or 3) or AC bus name (for bus identification code equal to 2). 8 characters long.

Circuit Number

Circuit number (one digit)

Group

3 character group identifier

Zone

Converter zone number

Nb

Number of bridges in series

Xt

Transformer Reactance in ohms per bridge if transformer MVA on the FZ card is zero, otherwise in pu based on transformer MVA.

Nt

Transformer Nominal Voltage Ratio (secondary to primary, i.e. DC side to AC side)

Tap Step

Transformer tap step size in percent.

Tap Min.

Transformer minimum tap in pu

Tap Max.

Transformer maximum tap in pu

Alpha Min.

Minimum alpha setting in degrees (-90)

Alpha Max.

Maximum alpha setting in degrees (90)

Gamma Min.

Minimum modulation ratio (-1.0)

Gamma Max.

Maximum modulation ratio (1.0)

Imax

Maximum AC current in amps (for shunt VS converters only)

"FZ" record:

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

123

PSAT User Manual

Code:

'FZ'

Change:

' ' (Blank) - no change 'D' - delete data associated with converter 'M' - change the data provided for the converter

DC bus 1 Name

DC node positive connection (8 characters long)

DC bus 2 Name

DC node negative connection (8 characters long)

AC bus 1 Number or Name

First AC bus number (for bus identification code equal to 1 or 3) or AC bus name (for bus identification code equal to 2). 8 characters long.

Circuit Number

Circuit number (one digit)

Mode

Three set points description (6 characters). Each set point can be one of the following VD - DC voltage in kV ID - DC current in amps (+ve at rectifier and -ve at inverter) PA - Real power injected into AC bus 1 in MW (equation 3) QA - Reactive power injected into AC bus 1 in MVAR (equation 4) AL - Alpha; Converter power angle in degrees GA - Gamma; Modulation ratio AT - Transformer tap in pu

Numerical values for the set points must be entered as SP1, SP2, SP3, in the same order as the set points description in Mode Converter set point 1 SP1 SP2

Converter set point 2

SP3

Converter set point 3

X1

Line reactance in ohms if transformer MVA is zero, otherwise in pu based on transformer MVA

Kc

Code for the DC to AC gain of the converter (i.e. Vl-1/Vd) 0 : gain is 1 1: SQRT(6)/4 for linear sinusoidal PWM 2: SQRT(6)/ for square-wave pulse switching 3: 0.727 for 5th and 7th harmonic elimination switching

Type

1 character that identifies the converter as a rectifier or inverter ('R' Rectifier; 'I' - Inverter)

Trans MVA

Transformer MVA rating

AC bus 2 Number or Name

Second AC bus number (for bus identification code equal to 1 or 3) or AC bus name (for bus identification code equal to 2). 8 characters long. Zero bus number or blank bus name (' ') indicates ground (for shunt VS converters)

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

124

PSAT User Manual

Base kV

Base voltage of transformer AC side in kV (if zero, it is set to the base kV of AC bus 1)

"FV" record: For an UPFC which is modelled by a shunt and a series VSC, voltage control parameters are specified on the FV card of the series converter (which has non-zero AC bus 2). Code:

'FV'

Change:

' ' (Blank)

DC bus 1 Name

DC node positive connection (8 characters long)

DC bus 2 Name

DC node negative connection (8 characters long)

AC bus 1 Number or Name

First AC bus number (for bus identification code equal to 1 or 3) or AC bus name (for bus identification code equal to 2). 8 characters long.

Circuit Number

Circuit number (one digit)

Vmin

Lower bound for the voltage of AC bus 1

Vmax

Upper bound for the voltage of AC bus 1

Vref

Estimated UPFC terminal voltage (the voltage expected to be kept constant by the shunt converter of UPFC)

If the FV record is missing, the default values of 0.2, 2.0 and 1.0 are assigned to Vmin, Vmax and Vref, respectively.

15.19

Zone Data

Each record of zone data consists of the following items: Number:

Zone number

Name:

16 character zone name

15.20

Node Mapping Data

Each record of node-bus mapping data consists of the following items: Bus number:

Number of the bus which contains the node (not given when bus identification code is 2).

Bus name:

Name of the bus whicj ontains the node (not given when bus identification code is 1).

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.

Powertech Labs Inc.

125

PSAT User Manual

Node Name:

15.21

32 characters long name.

File Section Data

The data for Generator Capability Curves and Induction Motor Loads are stored in two separate ASCII files. The file names of these files (if they are required) are stored in this section of the PSF raw data file. File identifier:

A four character file identifier. The first three characters must be either GCC (for Generator Capability Curves) or IMT (for Induction Motor Loads). The last character corresponds to the bus identification code used in preparing the data in the file.

File name:

File name (maximum of 60 characters).

At present, this section can have a maximum of two records (one for Generator Capability Curves and one for Induction Motor Loads). THIS OPTION IS NOT SUPPORTED IN THE PRESENT VERSION OF PSAT.

This document contains proprietary information and shall not be reproduced in whole or in part without the prior written permission of Powertech.