Training Area Setup with S7-300 ...................................................................................................... Configuration of the S7-300 Training Unit ......................................................................................... The Simulator ................................................................................................................................... The Conveyor Model ..................................................................................................................... Complete Symbol List (1) ................................................................................................................. Complete Symbol List (2) .................................................................................................................. If You Want to Know More .............................................................................................................. Training Area Setup with S7 - 400 .................................................................................................. Configuration of the S7 - 400 Training Unit .....................................................................................
SITRAIN Training for Automation and Industrial Solutions
Page 1
2 3 4 5 6 7 8 9 10
ST-PRO1 Training Units and Addressing
Training Area Setup with S7 - 300
SIMATIC S7
Date: File:
Siemens AG 2005. All rights reserved.
S7 - 300 Training Area • • • • • • • •
14.10.2005 PRO1_02E.2
SITRAIN Training for Automation and Industrial Solutions
The training area consists of the following components: An S7-300 programmable logic controller with the CPU 315-2 DP Digital input and output modules, analog module Simulator with digital and analog sections Conveyor model ET 200S distributed peripheral MM420 Micromaster with PROFIBUS module TP170B Touchpanel Programming device or PC
SITRAIN Training for Automation and Industrial Solutions
Page 2
ST-PRO1 Training Units and Addressing
Configuration of the S7 - 300 Training Unit
(32-channel I/O modules)
Module Slot No. I/O Address
--> --> -->
PS 1
SIMATIC S7
Date: File:
Siemens AG 2005. All rights reserved.
Configuration
DI 32 4 0
14.10.2005 PRO1_02E.3
DO 32 5 4
DI8/DO8 6 8
AI 2 7 304
SITRAIN Training for Automation and Industrial Solutions
The programmable controller is configured with the following modules: Slot 1: Slot 2: Slot 4: Slot 5: Slot 6: Slot 7:
Addresses
CPU 2
Power Supply 24V/5A CPU 315-2 DP Digital input 32x24V
Inputs from the simulator and thumbwheel buttons Digital output 32x24V/0.5A Outputs from the simulator and digital display Digital input and output Conveyor model module 8X24V/ 8x24V 0.5A Analog input 2 AI Analog section from the simulator
For the training unit with the CPU 315-2DP and for the S7-400 training unit, you can set the starting addresses of the modules by parameter assignment (freely).
SITRAIN Training for Automation and Industrial Solutions
Page 3
ST-PRO1 Training Units and Addressing
The Simulator Potentiometers for setting the analog vales
Digital Display DI
DO
.0
..........
..........
.0
.1
..........
..........
.1
.2
..........
..........
.2
.3
..........
..........
.3
.4
..........
..........
.4
.5
..........
..........
.5
.6
..........
..........
.6
.7
..........
..........
.7
.0
..........
..........
.1
..........
..........
.2
..........
..........
.3
..........
..........
.4
..........
..........
.5
..........
..........
.6
..........
..........
.7
..........
..........
Switches / Pushbuttons
V
-15V...+15V AI1
.0 .1
AI1
AI2
.3 .4 .5
0 8 1 5
AI1
AI2
AO1
AO2
.6 .7
LEDs
Thumbwheel Buttons
Date: File:
Siemens AG 2005. All rights reserved.
Addressing
V
.2
SIMATIC S7 Design
AI2 AO1 -15V...+15V AO2
SITRAIN Training for
14.10.2005 PRO1_02E.4
Automation and Industrial Solutions
Two cables connect the simulator to the S7-300™ or S7-400™ training unit. The simulator is divided into the following three sections: •
Binary section with 16 switches / pushbuttons and 16 LEDs
•
Digital section with 4 thumbwheel buttons and a digital display. The thumbwheel and digital (BCD) display use BCD values,
•
Analog section with a voltmeter for displaying the values at analog channels 0 and 1 or the analog outputs 0 and 1. You use the selector switch to choose the voltage value you want to monitor. There are two separate potentiometers for setting the values for the analog inputs.
You use the following addresses to address the inputs and outputs in your user program :
SITRAIN Training for Automation and Industrial Solutions
Sensor / Actuator
(DI32, DO32)
Switch / Pushb.
IW 0
LEDs
QW 4
Thumb. buttons
IW 2
Digital display
QW 6
Analog channels
PIW 304/306
Page 4
ST-PRO1 Training Units and Addressing
The Conveyor Model
BAY_1 I 8.5
K_RT (Q 8.5) K_LT (Q 8.6)
BAY_2 I 8.6
BAY_3 I 8.7
LB1 I8.0
Horn Q 8.7
T_Bay_1 T_Bay_2 T_Bay_3 T_FinalAssy I 8.1 I 8.2 I 8.3 I 8.4 L_Bay_1 L_Bay_2 L_Bay_3 L_FinalAssy Q 8.1 Q 8.2 Q 8.3 Q 8.4
SIMATIC S7
Date: File:
Siemens AG 2005. All rights reserved.
Design
14.10.2005 PRO1_02E.5
SITRAIN Training for Automation and Industrial Solutions
The slide shows a diagram of the conveyor model with its sensors and actuators.
Addresses
SITRAIN Training for Automation and Industrial Solutions
Page 5
ST-PRO1 Training Units and Addressing
Complete Symbol List (1)
SITRAIN Training for Automation and Industrial Solutions
Page 6
ST-PRO1 Training Units and Addressing
Complete Symbol List (2)
SITRAIN Training for Automation and Industrial Solutions
Page 7
ST-PRO1 Training Units and Addressing
If You Want to Know More
SIMATIC S7
Date: File:
Siemens AG 2005. All rights reserved.
Note
14.10.2005 PRO1_02E.8
SITRAIN Training for Automation and Industrial Solutions
The following pages contain either further information or are for reference to complete a topic.
SITRAIN Training for Automation and Industrial Solutions
Page 8
ST-PRO1 Training Units and Addressing
Training Area Setup with S7- 400
SIMATIC S7
Date: File:
Siemens AG 2005. All rights reserved.
Contents of the Training Area
14.10.2005 PRO1_02E.9
SITRAIN Training for Automation and Industrial Solutions
The training area consists of the following components: • An S7-400 programmable logic controller with a CPU 412 or CPU 413-2 DP) • Digital input and output modules, analog module • Simulator with digital and analog section • Conveyor model • ET 200S distributed peripheral • MM420 Micromaster with PROFIBUS module • TP170B Touchpanel • Programming device or PC
SITRAIN Training for Automation and Industrial Solutions
Page 9
ST-PRO1 Training Units and Addressing
Configuration of the S7-400 Training Unit Slot No.
1
PS
2
3
CPU
Default Address:
SIMATIC S7
4
5
6
7
DI 32
DI 32
28
32
8
10
11
12
13
14
15
16
17
18
DO DO AI 32 32 8 36
Date: File:
Siemens AG 2005. All rights reserved.
9
40
1216
14.10.2005 PRO1_02E.10
SITRAIN Training for Automation and Industrial Solutions
Design
You can see the design of the S7-400 training unit in the slide above.
Configuration
The UR 1 rack is configured with the following modules: Slot 1: Power Supply 24V and 5V/20A Slot 2: -"Slot 3: -"Slot 4: CPU 412 or other Slot 5: vacant (when the CPU only has a single width) Slot 6: vacant Slot 7: vacant Slot 8: Digital input 32x24V (from simulator) Slot 9: Digital input 32x24V (from conveyor model) Slot 10: Digital output 32x24V 0.5A (to simulator) Slot 11: Digital output 32x24V 0.5A (to conveyor model) Slot 12: Analog input 8x13 Bit (from potentiometer on simulator) Slot 13: vacant Slot 14: vacant Slot 15: vacant Slot 16: vacant Slot 17: vacant Slot 18: vacant
Addressing
You have the default addresses, as shown in the slide above, as long as no configuration or parameter settings have been made.
SITRAIN Training for Automation and Industrial Solutions
Thank you for interesting in our services. We are a non-profit group that run this website to share documents. We need your help to maintenance this website.