Technical Paper Marco di Prisco* Matteo Colombo Daniele Dozio

DOI: 10.1002/suco.201300021

Fibre-reinforced concrete in fib Model Code 2010: principles, models and test validation In the fib Model Code for Concrete Structures 2010, fibre-reinforced concrete (FRC) is recognized as a new material for structures. This introduction will favour forthcoming structural applications because the need of adopting new design concepts and the lack of international building codes have significantly limited its use up to now. In the code, considerable effort has been devoted to introducing a material classification to standardize performance-based production and stimulate an open market for every kind of fibre, favouring the rise of a new technological player: the composite producer. Starting from standard classification, the simple constitutive models introduced allow the designer to identify effective constitutive laws for design, trying to take into account the major contribution in terms of performance and providing good orientation for structural uses. Basic new concepts such as structural characteristic length and new factors related to fibre distribution and structural redistribution benefits are taken into account. A few examples of structural design starting from the constitutive laws identified are briefly shown. FRC can be regarded as a special concrete characterized by a certain toughness after cracking. For this reason, the most important constitutive law introduced is the stress-crack opening response in uniaxial tension. A wide discussion of the constitutive models introduced to describe this behaviour, which controls all the main contributions of fibres for a prevailing mode I crack propagation, is proposed. The validity of the models is discussed with reference to ordinary cross-sections as well as thin-walled elements by adopting plane section or finite element models. Keywords: fibre-reinforced concrete, constitutive equations, identification, modelling, structural characteristic length, structural behaviour, redundancy, structural design

1

Introduction

Fibre-reinforced concrete (FRC) is a composite material that is characterized by an enhanced post-cracking residual tensile strength due to the capacity of the fibres to bridge the crack faces. During the last two decades, a wide range of research has been performed on FRC material properties, in both the fresh and hardened states [1–9]. The investigations

* Corresponding author: [email protected] Submitted for review: 8 April 2013 Revised: 3 August 2013 Accepted for publication: 8 September 2013

342

started in the USA, driven by research into closely spaced wires and random metallic fibres [10–18]. This research was the basis for a patent on steel fibre-reinforced concrete (SFRC) based on fibre spacing in 1969 and in 1970 [19]. The Portland Cement Association (PCA) started investigating fibre reinforcement in the late 1950s. The principles of composite materials were applied to analyse FRC. The addition of fibres was shown to significantly increase toughness after the onset of the first cracking. Another patent based on bond and the aspect ratio of the fibres was granted in 1972 [19]. Since the time of these original fibres, many new steel fibres have been produced. The usefulness of SFRC was aided by other new developments in the concrete field. High-range water-reducing admixtures able to improve the workability of some harsh SFRC mixtures were formulated and break through the suppliers’ and contractors’ reservations regarding the use of SFRC. Although many experimental campaigns have been developed since the 1960s, research on the structural response of FRC elements mainly developed over the last 15 years. As a consequence, there is still a lack of international building codes for the structural design of FRC elements, even though a number of design guidelines were recently drawn up. This may explain the limited use of FRC among practitioners, who hardly accept the adoption of voluntary guidelines or, even worse, research results available in scientific papers. FRC now appears in the fib Model Code 2010 after a huge amount of research and a historical development spanning more than 50 years. Two main reasons justify the long time needed: a theoretical aspect that forces designers to consider fracture mechanics concepts to describe the post-cracking residual strength in tension due to fibre bridging, and the technological aspects mainly related to workability and fibre alignment, which has asked concrete chemistry for new products to favour the introduction of increasingly large fibre contents in cementbased composites. Early design considerations were produced by ACI 544 [20], and even in ACI 318 [21] some new rules were just introduced with reference to minimum shear reinforcement, while RILEM TC162-TDF produced design guidelines for typical structural elements [22, 23]. Afterwards, recommendations were produced by other countries, e.g. France [24], Sweden [25], Germany [26], Austria [27], Italy [28], Japan [29] and Spain [30].

© 2013 Ernst & Sohn Verlag für Architektur und technische Wissenschaften GmbH & Co. KG, Berlin · Structural Concrete 14 (2013), No. 4

M. di Prisco/M. Colombo/D. Dozio · Fibre-reinforced concrete in fib Model Code 2010: principles, models and test validation

P

P P Pcr

crack formation

P Pcr δ

a)

crack formation crack localization

b)

δ

Fig. 1. Typical load P vs. deformation δ curve for FRC: softening (a) and hardening (b) [fib MC2010, Fig. 5.6.2].

Owing to better knowledge of FRC and the recent worldwide developments in guidelines for structural design, fib Special Activity Group 5 (SAG 5), which prepared the new fib Model Code, decided to introduce some sections on new materials [31] and in particular on FRC structure design [32]. The fib Working Groups TG 8.3 (“Fibre-reinforced concrete”) and TG 8.6 (“Ultra-high-performance fibre-reinforced concrete”) prepared these sections of the fib Model Code 2010 concerning FRC design rules to provide guidance to engineers for the proper and safe design of FRC structural elements at both serviceability and ultimate limit states, based on state-of-the-art knowledge. In fib Model Code 2010, FRC is introduced in two sections: 5.6 and 7.7 – the former focusing on material behaviour, the latter on structural behaviour. The basic principles introduced in these two sections are mainly obtained from research on SFRC, but fib Model Code 2010 is open to every kind of fibre, following a performance-based design approach [33]. Nevertheless, several warnings are introduced regarding the long-term behaviour of some fibres, especially those characterized by a low Young’s modulus value. This paper aims to present some basic principles governing the structural design of FRC elements made of regular concrete which were mainly introduced by fib TG 8.3. The main concepts were derived from some national guidelines for FRC structural design [24, 28] and from the guidelines proposed by RILEM TC162-TDF [22, 23]. The principles discussed here are mainly related to SFRC having a softening post-cracking behaviour in uniaxial tension (Fig. 1a), even though they can be extended to hardening materials (Fig. 1b). Since hardening behaviour in one direction is sometimes related to a softening behaviour in the orthogonal direction [34] for the known materials with aligned fibres, the two fib committees active on softening FRC materials (TG 8.3) and hardening UHPFRC materials (TG 8.6) are cooperating in the writing of two bulletins in relation to the design rules in order to favour a unified approach.

2

FRC classification

Classification is an important requirement for structural materials. When referring to ordinary concrete, designers choose the compressive strength, workability or exposition classes that have to be provided by the concrete producer.

Fig. 2. Different response of structures made of FRC having a softening or hardening behaviour under uniaxial tension or bending loads [fib MC2010, Fig. 5.6.1]

It is well known that fibres reduce the workability of fresh concrete, but workability classes for plain concrete can be adopted for FRC as well [35]. Some studies are still needed for exposition classes since fibres may reduce the crack opening [36–38]. Therefore, for the exposition classes described in EN 206 (2006), different rules may be adopted for FRC structures (i.e. smaller concrete covers, etc.). When using FRC, compressive strength is not particularly influenced by the presence of fibres up to a content of 1 % by vol., so the classification for plain concrete can be used. As fibre content grows, the post-peak progressively increases its toughness, becoming ductile for very high fibre contents [39–41]. The mechanical property that is mainly influenced by fibres is the residual post-cracking tensile strength, and that represents an important design parameter for FRC structures. Owing to the well-known difficulties in performing uniaxial tensile tests, standard methods are generally based on bending tests on small notched beams. Since bending behaviour is markedly different from uniaxial tension behaviour, it may happen that softening materials in tension exhibit a hardening behaviour in bending ([42], Fig. 2). In fact, in bending tests, cracks arise before the peak load is reached and it may happen that softening materials in uniaxial tension exhibit stable crack propagation with increasing load (hardening behaviour in bending or flexure hardening). The large number of parameters affecting the fibre pull-out mechanism, and consequently residual strengths, does not allow reliable prediction of FRC response in uniaxial tension based on matrix, fibre mechanical characteristics and fibre content. Experimental evidence suggests treating this cement-based material as a unique composite whose characteristics depend on fibre dispersion. The unknown fibre location and post-cracking residual strength represent the most interesting concepts for this material. If its constitutive relationships are examined assuming a simple homogeneous material, some links between the material and the related structure arise and cannot be ignored if we require reliable design predictions.

Structural Concrete 14 (2013), No. 4

343

M. di Prisco/M. Colombo/D. Dozio · Fibre-reinforced concrete in fib Model Code 2010: principles, models and test validation

Material classification for FRC is based on the nominal properties of the composite material, referring to postcracking tensile strength, determined from bending tests on notched prisms according to EN  14651 (2004 [43], Fig. 3); the diagram of the applied load F vs. the deformation should be produced (Fig. 4). Deformation is expressed in terms of crack mouth opening displacement (CMOD) or mid-span deflection. In order to normalize the load F, the nominal tensile stress σN in bending is considered, i.e. the bending moment F * L/4 divided by the elas-

tic modulus in bending, corresponding to that of the critical notched section (Wel = bhsp2/6 and L = 500 mm). The classification is based on two post-cracking residual strengths at certain CMODs, which characterize the material behaviour at the serviceability limit state (SLS; CMOD1 = 0.5  mm; fR1k) and at the ultimate limit state (ULS; CMOD3 = 2.5 mm; fR3k). The latter is not introduced directly, but the fR3k/fR1k ratio is explicitly indicated (Fig. 5). With these assumptions, an FRC material can be classified by using a couple of parameters: the first one is a number denoting the fR1k class, the second is a letter denoting the ratio fR3k/fR1k. The fR1k strength values indicating the classes are as follows: 1.0, 1.5, 2.0, 2.5, 3.0, 4.0, 5.0, 6.0, 7.0, 8.0 [MPa] whereas the fR3k/fR1k ratio is denoted by the letters a, b, c, d, e corresponding to a if 0.5 < fR3k/fR1k ≤ 0.7 b if 0.7 < fR3k/fR1k ≤ 0.9 c if 0.9 < fR3k/fR1k ≤ 1.1 d if 1.1 < fR3k/fR1k ≤ 1.3 e if 1.3 < fR3k/fR1k The residual flexural tensile strength fRj is defined as

Fig. 3. Setup for a three-point bending test [EN 14651, 2004]

fR, j 

Fig. 4. Typical load F vs. CMOD curve for plain concrete and FRC [fib MC2010, Fig. 5.6-6]

Fig. 5. Example of σN-CMOD curve with proposed classification rules

344

Structural Concrete 14 (2013), No. 4

3 Fj l 2 2 b hsp

(1)

M. di Prisco/M. Colombo/D. Dozio · Fibre-reinforced concrete in fib Model Code 2010: principles, models and test validation

Since brittleness must be prevented in structural members, fibre reinforcement can only substitute (even partially) rebars or welded mesh at ULS if the following relationships are fulfilled: fR1k/fLk ≥ 0.4

(2)

fR3k/fR1k ≥ 0.5

(3)

where fLk is the characteristic value of the nominal strength, corresponding to the peak strength in bending (or the highest nominal stress value in the interval 0–0.05 mm of CMOD), determined in a notched beam test (Figs. 3 and 4). Long-term behaviour of cracked FRC under tension has to be properly taken into account for those materials whose long-term performance is affected by creep and/or creep failure. The creep effects have not been studied enough up to now, even though some research is now in progress at several universities.

3

Constitutive laws in uniaxial tension

3.1

Kinematic model, structural characteristic length and ultimate crack opening

When considering softening materials, the definition of a stress-strain law in uniaxial tension requires the introduction of a structural characteristic length lcs for the structural element. This basic concept represents a “bridge” (Fig. 7) to connect continuous mechanics, governed by stress-strain (σ-ε) constitutive relationships, and fracture mechanics, governed by a stress-crack opening (σ-w) law, initially proposed by Hillerborg (1976, [44]). The structural characteristic length is equal to the crack spacing when multiple cracking takes place and can be considered as equal to the beam depth when a plane section approach is used in the analysis. When a finite element (FE) model is used, several approaches related to an internal length defined in relation to physical parameters, such as maximum aggregate size for non-local approaches, or element size for local approaches, can be used in order to prevent a mesh dependency of the results [45–47]. The introduction of the characteristic length allows the designer to define the strain as

The stress-crack opening relationship in uniaxial tension can be regarded as the main reference material property in the post-cracking range. Two simplified stress-crack opening constitutive laws may be deduced from the bending test results: a rigid-plastic model or a linear post-cracking model (hardening or softening), as shown schematically in Fig. 6, where: wu crack opening corresponding to ULS fFts serviceability residual strength, defined as the postcracking strength for a crack opening significant for SLS fFtu residual strength significant for ULS Both fFts and fFtu are calculated using the residual flexural strengths fR1 and fR3 identified in bending.

Fig. 6. Simplified constitutive laws: stress-crack opening (solid and dashed lines refer to softening and hardening materials respectively) [fib MC2010, Fig. 5.6-7]

Fig. 7. Examples of characteristic lengths

Structural Concrete 14 (2013), No. 4

345

M. di Prisco/M. Colombo/D. Dozio · Fibre-reinforced concrete in fib Model Code 2010: principles, models and test validation

ε = w/lcs

(4)

It is interesting to note that Eq. (4) implies that when a plane section model is taken into account and the crack distribution is not homogeneous in the cross-section (owing to an inhomogeneous distribution of the reinforcement in the cross-section), the same FRC material (defined by a unique σ-w response in uniaxial tension) has to be described in the different portions of the cross-section according to different σ-ε values because of the different crack spacings, which correspond to different lcs values (see examples in Fig. 7). The ultimate crack width wu can be defined on the basis of a ductility requirement and therefore as wu = lcs · εFu

(5)

by assuming εFu equal to 2 % for a neutral axis crossing the cross-section and 1 % for a neutral axis external to the cross-section. Moreover, a limited value strictly correlated to the fibre length should also be considered. In relation to the actual market availability and practical considerations regarding RC crack opening observed at ULS, a value of 2.5 mm is assumed. Eq. (5) can be rewritten as wu = min (lcsεFu; 2.5 mm)

(6)

Multiple cracking occurs in hardening materials. Therefore, the identification of crack openings is not necessary because a conventional stress-strain law may be directly determined by a uniaxial tension test, typically unnotched (like a dog-bone specimen), by dividing the relative displacement by the gauge length. It is interesting to note that sometimes the same self-compacting concrete can exhibit a softening and a hardening behaviour depending on the stretching direction with reference to fibre alignment [34]. This is one of the main reasons why standards have to model FRC material behaviour following a similar approach for both hardening and softening materials. Moreover, every time fibres are aligned, the material cannot be considered isotropic, and suitable anisotropic constitutive laws should be introduced.

3.2

The σ-w curve identified from bending tests

Accepting the Hillerborg idea of a cohesive approach to describe the uniaxial tension behaviour of FRC [44, 48], two possible simplified models can be introduced to describe FRC response after cracking. This is done by emphasizing that the most significant effect induced by fibres is related to the pull-out mechanism: the rigid-plastic and the linear elastic-softening models. The rigid-plastic model requires the identification of only one parameter: fFtu. It can be easily identified by rotational equilibrium at ULS by assuming that the compressive stress distribution is concentrated at the top fibre, whereas a tensile post-cracking residual stress distribution is uniformly applied to the overall critical cross-section (Fig. 8). By equating the internal moment of resistance Mu,int to the external applied moment Mu,ext, it is possible to write the following equation, which corresponds to the rotational equilibrium of the cross-section:

346

Structural Concrete 14 (2013), No. 4

Fig. 8. Simplified model adopted to compute the ultimate residual tensile strength in uniaxial tension fFtu by means of the residual nominal bending strength fR3 [fib MC2010, Fig. 5.6-8]

Mu, ext 

2 fR3bhsp

6



2 fFtubhsp

2

 Mu,int

(7)

fFtu = fR3/3

(8)

The linear model identifies two reference values: fFts and fFtu. They can be defined by residual values of flexural strengths by using the following equations: fFts = 0.45fR1 fFtu  fFts 

(9)

wu ( f  0.5fR3  0.2fR1)  0 CMOD3 Fts

(10)

where wu is the maximum crack opening accepted in structural design. The two equations are introduced according to different assumptions valid at SLS and ULS respectively and briefly summarized in Fig. 9. At SLS the constitutive relationship for FRC is assumed to be elastoplastic in uniaxial tension and elastic in uniaxial compression. Two equations can be written to impose longitudinal and rotational equilibrium. According to the notation used in Fig. 9, and assuming

 E

ws x; ws  0.5 mm; y  hsp  x; lcs  hsp ylcs

(a)

(b)

(c)

Fig. 9. Stress distributions assumed for determining the residual tensile strength fFts (b) and fFtu (c) for the linear model [fib MC2010, Fig. 5.6-9]

M. di Prisco/M. Colombo/D. Dozio · Fibre-reinforced concrete in fib Model Code 2010: principles, models and test validation

then the result is   bx f 2 bx   f   Fts  fFtsb  y  Fts x  0 2 2       2   f by   2 x  y   fFtsbx 2 x  1 fFts  Fts  3 2  2  3 3  

(11) 2  fR1bhsp x  6 

(12)

The resolution of the non-linear system of Eqs. (11) and (12) gives a correlation between fFts and fR1 that depends on Young’s modulus E and on the choice of the structural characteristic length lcs: fFts = ka (E, lcs)fR1

2 bhsp

2

 (kb fR1  fFt,2.5)

2 bhsp

3

 fR3

2 bhsp

6

(14)

By solving Eq. (14), it is possible to compute the unknown fFt,2.5 as fFt,2.5  0.5fR3 

kb f 2 R1

(15)

Now, taking into account that the linear model also has to fit for the point (wi1 = 0.5 mm, σ = 0.37fR1), it is possible to express kb as follows:

(13)

By assuming a structural characteristic length lcs equal to the critical cross-section hsp, the factor ka changes with Young’s modulus E, as shown in Fig. 10. The ka value ranges between 0.362 and 0.378 and therefore an average value of 0.37 could be considered. Let us consider the ULS. In this case the compressive stress distribution is concentrated on a very small portion of the cross-section and therefore, once again, it is assumed that a concentrated compressive force acts at the upper fibre. If at the underside a crack opening of 2.5 mm is considered, a linear softening model involves a linear distribution of stresses that is characterized by a value kbfR1 for w = 0, kafR1 for wi1 = 0.5  mm and fFt,2.5 for wi2 = 2.5 mm. The rotational equilibrium becomes

a)

fFt,2.5

kb  0.529  0.143

fR3 fR1

(16)

If fR3 is considered to be equal to 0.5fR1, then that represents the constraint introduced to define the composite FRC as a structural composite; kb becomes equal to 0.45 and Eq. (15) can be rewritten as fFt,2.5 = 0.5fR3 – 0.225fR1 ≅ 0.5fR3 – 0.2fR1

(17)

Taking into account the definition of the ultimate crack opening wu previously introduced, and in particular that introduced for thin-walled elements, a reduced crack opening value can be considered and Eqs. (9) and (10) deduced. It is important to note that the shifting of the fFts

b)

Fig. 10. a) Definition of ka and kb coefficients, b) ka values vs. E values for the linear–softening model and lcs = h

a)

b)

Fig. 11. Spurious results obtained with fFts associated with a crack opening of w = 0.5 mm and not w = 0

Structural Concrete 14 (2013), No. 4

347

M. di Prisco/M. Colombo/D. Dozio · Fibre-reinforced concrete in fib Model Code 2010: principles, models and test validation

value at w = 0 prevents some spurious situations where a class reduction (i.e. FRC composite changes from class b to a, or c to b) could involve a better performance in bending (see Fig. 11) for thin-walled elements where wu is close to 0.5 mm. Finally, it is worth noting that a CMOD value of 2.5 mm does not correspond to a CTOD value of 2.5 mm (see Eq. (18)), but rather to a CTOD close to 2.1 mm according to a rigid-body assumption. Nevertheless, the idea to arrest the cohesive stress at wu is in this way partially compensated by the crack opening translation.

3.3

(COD), whose behaviour is dominated by matrix response. A three-point bending test exhibits a weak higher peak strength and a more brittle first post-peak slope. Of course, there is also a significant difference in the queue value for a large COD, but this is due to the confinement in compression obtained in three-point bending tests just below the central load knife. However, this significant effect becomes negligible when a fibre pull-out mechanism takes place. Several SFRC materials denoted according to a unified system (Tables 1 and 2) have been compared by investigating their bending behaviour according to UNI 11039 [52] and EN 14651 [43]. The designation is expressed by Mn-Fn-Vf, where Mn indicates a certain matrix (n ranges between 1 and 8, Table 1), Fn indicates a certain steel fibre (n ranges between 1 and 8, Table 2) and Vf indicates the fibre volume percentage used in the composite. The experimental comparison highlights what was already predicted in [51], showing very similar pull-out strengths, with the tendency to have something more in three-point bending test (Fig. 12). It is important to emphasize that the measurement of the crack opening is not the same for the two tests. In fact, whereas for a three-point bending test the measured parameter is CMOD, for the four-point bending test the measured parameter is CTOD. If a linear

Three- vs. four-point bending test

In the literature, the three-point bending test is not the only notched test proposed. The debate on the best test for identifying the uniaxial tension constitutive law σ-w has involved many researchers and is still in progress [49, 50]. It is interesting to observe that the difference between the two tests is not so large when a careful non-linear computation is carried out. According to Ferrara and di Prisco [51], for plain concrete, the main differences between the two tests are related to the peak strength and the first postpeak slope of the load vs. crack opening displacement

Table 1. Mix designs of the different materials considered

M1

M2

M3

M4

M5

M6

M7

M8

Fck [MPa]

50

60

75

65

40

30

55

75

Cement [kg/m3]

400 CEM I 52.5R

400 CEM I 52.5R

450 CEM I 52.5R

350 CEM I 52.5R

300 CEM II 42.5R

340 CEM II 42.5R

480 CEM I 52.5R

380 CEM I 52.5R

Agg. 1 [kg/m3]

511 < 20mm

569 < 12mm

620 0–3mm

120 0–3mm

1450 < 12mm

559 11–22mm

620 0–3mm

120 0–3mm

Agg. 2 [kg/m3]

789 < 10mm

403 < 8mm

440 0–12mm

970 0–12mm

420 3–6mm

93 4–10mm

440 0–12mm

970 0–12mm

Agg. 3 [kg/m3]

375 < 4mm

676 < 4mm

710 8–15mm

815 8–15mm



1201 < 5mm

710 8–15mm

815 8–15mm

Filler [kg/m3]

98 (calc.)

96 (calc.)

30 (calc.)

60 (fly-ash)

80 (fly-ash)





60 (fly-ash)

Plasticizer/cement

0.8 %

2.2 %

1.2 %

0.9 %

2.0 %

0.8 %

0.8 %

0.9 %

Water /binder

0.40

0.39

0.41

0.34

0.46

0.50

0.4

0.34

Table 2. Properties of the different steel fibres considered

F1

F2

F3

F4

F5

F6

F7

F8

Df [mm]

0.375

0.62

0.6

0.8

0.6

0.73

1.2

1.0

Lf [mm]

30

30

30

60

30

30

44

60

Aspect ratio

80

48

50

75

50

41

36

60

Tensile strength [MPa]

2300

1250

1192

1192

1100

390

390

390

Type

h.e.

h.e.

h.e.

h.e.

h.e.

c.

c.

c.

h.e. = hooked end; c. = crimped

348

Structural Concrete 14 (2013), No. 4

M. di Prisco/M. Colombo/D. Dozio · Fibre-reinforced concrete in fib Model Code 2010: principles, models and test validation

Fig. 12. Three- vs. four-point bending tests: experimental responses for several materials

Structural Concrete 14 (2013), No. 4

349

M. di Prisco/M. Colombo/D. Dozio · Fibre-reinforced concrete in fib Model Code 2010: principles, models and test validation

Fig. 13. Simplified relationship suggested for SLS analysis taking matrix peak strength contribution into account [fib MC2010, Fig. 5.6-10]

opening of the crack edges is assumed, then that is usually accepted for large crack openings, a rough upper-bound linear relation between the two COD measures can be introduced as CMOD 

3.4

150 CTOD  1.2  CTOD 125

(18)

Refined constitutive relationships

Once the linear stress-crack opening relationship has been identified, the stress-strain relationship can be deduced by introducing the suitable structural characteristic length lcs with reference to softening materials (Fig. 7, [53]). At SLS, a more refined curve able to fit the peak strength of the matrix can be proposed and it is particularly suggested for FE analyses. The same constitutive relationship adopted for plain concrete in uniaxial tension can be used up to peak strength fct, while in the post-cracking stage, a bilinear relation applies (Fig. 13). The residual strength due to the pull-out mechanism (final branch), which represents the main fibre contribution, is defined by two points corresponding to (εSLS, fFts = kafR1) and (εULS, fFtU). This simplification, which is easily understood because it takes into account only the most significant fibre contribution, the pull-out effect, may cause the same problem previously discussed in Fig. 11. For this reason, espe-

cially when the mechanical behaviour is strongly affected by small crack openings as for statically redundant structures, the first point, corresponding to SLS, can be shifted on the first softening branch conserving a value equal to kafR1. When the identification procedure is carried out starting from a four-point bending notched test, coefficient ka (Eq. (13)) can be set equal to a different value depending on the specific crack opening range adopted in the standard. If UNI 11039 is considered, a value of 0.39 can be adopted to take into account that the SLS value covers a range between 0 and 0.6 mm of crack tip opening displacement (CTOD), which corresponds to an average value of 0.3 mm instead of roughly 0.41 mm as occurs in EN 14651, where the CMOD value is 0.5 mm. In this case, in Eqs. (9) and (10) the residual strengths fRi are substituted by feqi because they are computed as average values in certain CTOD ranges: 0–0.6 mm for SLS and 0.6–3.0 mm for SLU. In fib Model Code 2010, the constitutive relationships for softening materials (Fig. 13) are presented together with those suggested for hardening materials, where, progressively, the matrix contribution cannot be distinguished from the fibre one. Only the softening case is discussed in the following. Further details on hardening material responses will be discussed in an fib bulletin currently in preparation. Note that by introducing the peak strength of the matrix it is possible to better induce localization when an FE model is adopted, thus preventing spurious dissipation due to uncontrolled growths of the cracked band [54]. Finally, the introduction of the fracture energy corresponding to the matrix peak strength contribution is not considered in the equilibrium equations used to identify Eqs. (9) and (10), but its addition is not generally significant for typical structures.

3.5

The σ-w curve identification: theoretical vs. experimental results

A broad experimental campaign was planned in order to ascertain whether the constitutive model σ-w identified from notched bending tests is reliable. A comparison was

b)

a)

Fig. 14. σ-w curves in uniaxial tension; comparison of constitutive law deduced according to linear–softening model (Eqs.(9) and (10)) and fixed-end direct tensile test carried out on cylindrical specimens (b) directly core-drilled by the notched beam used to characterize the FRC composite (a) [43]

350

Structural Concrete 14 (2013), No. 4

M. di Prisco/M. Colombo/D. Dozio · Fibre-reinforced concrete in fib Model Code 2010: principles, models and test validation

Fig. 15. Uniaxial tensile constitutive law identified from bending tests: bilinear hardening (bh); bilinear softening (bs) [51]

Fig. 16. FE meshes adopted for simulating the uniaxial tensile test

first carried out by casting three specimens made with the same FRC, belonging to the same batch, and carrying out three four-point bending tests according to Italian standard UNI 11039 [52]. Three cylindrical specimens were then core-drilled from one undamaged end (Fig. 14a) and tested in uniaxial tension by means of a closed-loop press able to impose a fixed-end condition [55]. The comparison is shown in Fig. 14, and is really encouraging. In fact, the

a)

scattering of the results was very much reduced, not only between the LVDTs at 120° in the same test [55], but also in the three different tests (see small shadow in Fig. 14b). The dashed line shown is computed as the average between the three average responses, computed as the mean curve of the three transducers in each test. Other tests were performed after thermal cycles at different temperatures (T = 200, 400 and 600 °C). Similar comparisons were also carried out on prismatic specimens in order to compare bending tests on notched and unnotched specimens with uniaxial tension tests with fixed and rotating ends made from the same materials [61]. The uniaxial tension test was also simulated by means of Diana Finite Element code, introducing as the constitutive relationship the σ-w response identified from bending (Fig. 15) using Eqs. (9) and (10). The axisymmetric mesh (Fig. 16) adopts regular triangular elements [54] and the COD was computed, as in the experimental tests, as the relative displacement between two points at a distance of 50 mm astride the notch. The structural characteristic length in this case is a localization limiter with lcs = 兹苵苵 2A [56]. The results (Fig. 17) are obtained by changing the size of the elements (lcs = 1.163, 2.327 mm). The higher curve is the constitutive response identified and used as an input for FE modelling, whereas the two FE structural responses of the modelled specimens are practically coincident and a little closer to the average experimental curve measured with the LVDTs at 120°. The main difference is shown in the post-peak response, where a smaller dissipation should be related to the modelling as-

b)

Fig. 17. FE simulation of uniaxial tension tests in fixed-end condition: a) global response, b) zoom at small COD

Structural Concrete 14 (2013), No. 4

351

M. di Prisco/M. Colombo/D. Dozio · Fibre-reinforced concrete in fib Model Code 2010: principles, models and test validation

Fig. 18. FE meshes adopted for simulating four bending tests on notched beams

Fig. 19. FE simulation results for notched four-point bending tests

sumption of neglecting defects, which characterize the real specimen. Using the same constitutive relationship, it is also possible to model the original notched beam specimen tested in a four-point bending setup. Two meshes were introduced: they consider a plane stress approach and quadrilateral elements (mesh 1, Fig. 18, [54]) or triangular elements (mesh 2; Fig. 18, [54]). Even if the same constitutive relationship σ-w considered in the uniaxial tension tests was assumed and a proper localization limiter was applied as suggested by Rots [56] for both meshes, different post-cracking responses were obtained. In Fig. 19 the FE results are compared in terms of nominal strength σN vs. CTOD with experimental values from the four-point bending tests. It should be noted that triangular elements introduce a non-negligible increase in toughness.

b)

a)

Fig. 20. FE simulation of bending test: a) trilinear constitutive law adopted, b) model reliability with reference to a notched four-point bending test

a)

b)

Fig. 21. Notched four-point bending test simulation: multi-linear constitutive law adopted (a) and numerical results (b)

352

Structural Concrete 14 (2013), No. 4

M. di Prisco/M. Colombo/D. Dozio · Fibre-reinforced concrete in fib Model Code 2010: principles, models and test validation

Fig. 22. Plane section and FE validation of the linear model proposed in fib MC2010 for several materials defined in Table 1

Fig. 23. Influence of kinematic and constitutive model

The simplified models introduced can sometimes be substituted by more complex models identified by means of back-analysis [57]. With reference to mesh 1 (Fig. 18, [54]), a trilateral softening curve can be introduced as shown in Fig. 20a to reproduce the uniaxial tension test better. The improvement involves a more careful fitting of the bending response (Fig. 20b). Incidentally, a progressive improvement in the identification process is not always associated with the best response if the back-analysis is carried out with reference to a different kinematic mod-

el. In Fig. 21a, a multi-linear σ-w curve identified by means of a plane section model can allow the designer to fit perfectly the response with a plane section approach (Fig. 21b), but the result of the FE analysis with the same constitutive law could be far from the ideal fitting (Fig. 21b). Moving to the use of a plane section model, which is much more efficient for the structural design of bent elements, a series of beam specimens made of different materials as defined in Tables 1 and 2 was made to check the reliability of the proposed linear model (le/ls: linear elastic pre-peak/linear softening). The same constitutive models were adopted in the FE analysis with the proper structural characteristic length by using the two meshes shown in Fig. 18. The results (Fig. 22) confirm good reliability for a plane section model and FE mesh 1, whereas FE mesh 2 always gives an over-resistant response. Of course, the fitting is reasonable, it often overestimates the peak strength and the stiffness before the peak. A comparison between linear and bilinear relationships at preand post-peak is also shown (Fig. 23) with reference to the plane section and FE models. The main difference for both the kinematic models appears in the peak region as expected: linear relationships exhibit lower peak strengths due to the lack of matrix contribution and the same pull-out strength. A final investigation in terms of good fitting can be performed by considering the choice of the structural

Structural Concrete 14 (2013), No. 4

353

M. di Prisco/M. Colombo/D. Dozio · Fibre-reinforced concrete in fib Model Code 2010: principles, models and test validation

a)

b)

c)

d)

Fig. 24. Plane section model: the role of the structural characteristic length for two different materials with bilinear softening model: a), c) structural characteristic length influence for M2-F4-0.62 and M3-F2-0.62 materials respectively; b), d) related zooms

b)

a)

Fig. 25. Notched standard tests and unnotched structural specimen tests (h = 60 mm; average curves of at least 3 specimens); bending response with the same materials: tests according to UNI 11039 [49] and UNI 11188 [58]; A and B in (b) refer to specimens tested as cast (A) or turning the specimens upside down (B) [56]

characteristic length. In fact, this variable is not only related to the ideal condition of the plane section kinematic constraint, but also plays a role in predicting pre-peak behaviour and peak strength. By examining different choices of lcs and two different materials with a linear elastic model in pre-peak and a bilinear softening model (le/bs) in post-peak, it is possible to highlight the role played by the structural characteristic length. Fig. 24 clearly highlights the value of lcs = h suggested in fib Model Code 2010 as a reasonable choice.

354

Structural Concrete 14 (2013), No. 4

4

The “structural” specimen

The identification of the uniaxial tension constitutive law in the post-cracking regime is severely affected by fibre distribution and other parameters as observed by many researchers [58]. FRC is a cementitious composite and therefore, to be regarded as a homogeneous material, the specimens used to characterize its behaviour should have a volume that can be representative of the FRC heterogeneity grade. Changing casting and handling procedures

M. di Prisco/M. Colombo/D. Dozio · Fibre-reinforced concrete in fib Model Code 2010: principles, models and test validation

as well as the mixer, as necessitated by larger cast volumes, can drastically change mechanical characteristics in bending [58]. In thin-walled elements the use of fibre reinforcement is quite appropriate but, in general, FRC should present a hardening response in bending. The representativeness of standard notched beam specimens, with a cross-section of 150 × 150 mm, for characterizing the behaviour of this type of element is questionable. At the same time, fibre dispersion and orientation are seriously affected by a casting procedure that, in thin elements, is different from that adopted in standard specimens. Furthermore, standard specimens are notched and it is difficult to guarantee the hardening behaviour of the material (in statistical terms) by their response. In fact, the notch favours stable crack propagation and significantly modifies the first cracking process, especially if the fibre content is not high enough to change the mechanical behaviour at peak [59–61]. For all these reasons, an unnotched prismatic specimen cast using the same procedure as for the structure and with the same thickness is preferred. The specimen can be tested by means of a four-point bending setup that favours a crack propagation starting from the weakest cross-section between the load points. A transducer attached between two points on the underside of the specimen measures the relative displacement between these points (COD). This type of thin specimen can be very representative of the behaviour of thin FRC structures; therefore, it can be named “structural” specimen as first suggested in the French guidelines on ultra-high-performance fibre-reinforced concrete AFGC-SETRA [24] and in the Italian guidelines on SFRC [62]. In Fig. 25 a set of five different material tests highlights as the structural specimen usually gives a weaker response in relation to the standard notched tests used for classifying the material, even if a higher performance could be expected for the most favourable fibre distribution. For this reason, when thin-walled elements have to be designed safely, a careful identification of the mechanical response by means of structural specimens is strongly suggested. This choice could allow a partial reduction in the safety factors as suggested in [28, 58].

a)

Fig. 26. Geometry and test setup for full-scale beam test

5

Reliability of structural behaviour prediction

The constitutive models introduced to describe uniaxial tension can also be used to check the behaviour of beams with a conventional cross-section. To this end, three beams 3 m long with a 300 × 300 mm square cross-section were tested in a four-point bending test setup to check the reliability of the approach proposed in fib Model Code 2010. No conventional reinforcement was introduced [63, 64, 54]. The beam geometry and the setup adopted are shown in Fig. 26. The material is M2-F4-0.62, as specified in Tables 1 and 2. According to the measurements indicated in the setup (Fig. 29), both the load vs. vertical displacement and the bending moment vs. measured central curvature are proposed in Figs. 27a,b. Careful measurement of the fibre numbers in the critical cross-sections was also carried out and is indicated in Fig. 28. Fig. 29 also shows the final crack patterns. The numerical prediction carried out using the plane section approach fits quite well with the mechanical response measured experimentally. It is important to emphasize that the comparison is performed by considering the av-

b)

Fig. 27. Full-scale bending test, numerical and experimental results: a) bending moment vs. curvature diagram, b) load vs. displacement curve

Structural Concrete 14 (2013), No. 4

355

M. di Prisco/M. Colombo/D. Dozio · Fibre-reinforced concrete in fib Model Code 2010: principles, models and test validation

Fig. 28. Fibre distribution in the critical cross-section of the full-scale beams tested

Fig. 29. Crack patterns at failure for the full-scale beams tested

a)

b)

Fig. 30. Size effect introduced with the structural characteristic length: a) bilinear softening model, b) linear softening model

erage curves in the identification process of the uniaxial tension law and not the characteristic ones. The smaller stiffness of the global curve (Fig. 27b) is due to the lack of localization and to a softening zone assumed to be spread homogeneously over the overall zone with the same maximum bending moment. FE analyses were also performed using the same constitutive relationship and quadrilateral elements. In this case average and characteristic curves fit the structural behaviour quite well, even if the pre-peak response simulated by the FE analysis is not able to take into account the defect distributions adequately as well as inhomogeneous shrinkage effects in the cross section, thus exhibiting a stiffer behaviour. In order to favour the localization in the critical section detected experimentally, an initial geometric defect was introduced by assigning a local width reduction < 10 % in the proximity of the main crack propagation. To conclude the modelling of unreinforced concrete structures, an example of the role played by the structural

356

Structural Concrete 14 (2013), No. 4

characteristic length is shown in Fig. 30, where the same uniaxial tension constitutive law is assumed and different depths are considered [50]. The structural characteristic length is therefore able to reproduce a significant size effect without the need for any special coefficient as proposed by Rilem TC 162 TDF [23]. The same constitutive relationships were also used to model the bending behaviour of prefabricated FRC roof elements, where only prestressed longitudinal reinforcement remained – all the transverse reinforcement was substituted by different types of steel fibre. Further details for these cases can be found in [65, 66]. Several research projects are in progress to check the global behaviour of R/C structures where an FRC composite is adopted. In section 7.7, the models discussed to reproduce the uniaxial tension behaviour are used coupled with conventional reinforcement. The bending moment resistance at ULS with longitudinal reinforcement, which

M. di Prisco/M. Colombo/D. Dozio · Fibre-reinforced concrete in fib Model Code 2010: principles, models and test validation

Fig. 31. ULS for bending moment and axial force: use of simplified stress-strain relationship [fib MC2010, Fig. 7.7-3]

represents the usual case, can be investigated by means of the addition of a fibre contribution as clearly shown in Fig. 31. The bending failure stage is supposed to be reached when one of the following conditions applies: – attainment of the ultimate compressive strain in the FRC, εcu – attainment of the ultimate tensile strain in the steel (if present), εsu – attainment of the ultimate tensile strain in the FRC, εFu It is important to emphasize that in this case the structural characteristic length usually depends on the crack distance and therefore on the reinforcement ratio and bar diameters used. Furthermore, fibres help to increase the ductility of the plastic hinge by increasing the passive confinement in the compression zone, but this effect is not taken into account. Several investigations are in progress to check the effectiveness of fibres in reducing crack distance and openings as suggested in fib Model Code 2010, with suitable relationships in agreement with conventional reinforced concrete [36, 37, 38].

6

Partial safety factors and redundancy coefficients

For ultimate limit states, recommended values of partial safety factors γF are shown in Table 3. For serviceability limit states, the partial factors should be taken as 1.0. However, some special observations have to be made. FRC is scantly homogeneous and isotropic because fibres location is random and mainly depends on casting procedure, formwork geometry and mix consistency affected by flowability, viscosity and filling ability. Therefore, the scattering of its response mainly depends on numbers of fibres in the cracked section, their location and their orientation. On the basis of the previous considerations, the choice of the safety factors should take into account the following: Table 3. Partial safety factors for FRC

Material

γF

FRC in compression FRC in tension (limit of linearity) FRC in tension (residual strength)

as for plain concrete as for plain concrete 1.5

– the representativeness of the specimens used to characterize the mechanical response of the material, in relation to the structure considered – the number of specimens for mechanical characterization – the stress redistribution capacity of the structure under consideration – the fracture volume involved in the failure mechanism Besides the safety factor indicated in Table 3, suitable coefficients K, which take into account the representativeness of the specimen used for the identification in relation to the structure and the casting procedure adopted, are also introduced. In general, an isotropic fibre distribution is assumed so that the fibre orientation factor K is equal to 1. For favourable effects, an orientation factor K < 1.0 may be applied if verified experimentally. For unfavourable effects, an orientation factor K > 1.0 must be verified experimentally and applied. The values fFtsd and fFtud should then be modified to fFtsd,mod = fFtsd/K

(19)

fFtud,mod = fFtud/K

(20)

A careful analysis of the role played by the safety factor when a non-linear mechanical analysis is carried out according to fib Model Code 2010 is described by Cervenka et al. [67].

7

Basic aspects for design

Fibre reinforcement is suitable for structures where diffused stresses are present. In structures with both localized and diffused stresses, which is the usual case, it is better to base the reinforcement on a combination of rebars and fibre reinforcement. In structural elements where fibres aim to replace conventional reinforcement (even partially), some restrictions on the minimum residual strength are applied (Eqs. (2) and (3)). This residual strength becomes significant in structures characterized by a high degree of redundancy, where a remarkable stress redistribution occurs. For this reason, in structures without rebars, where fibres completely replace conventional reinforcement, a minimum redundancy level is required for the structural member.

Structural Concrete 14 (2013), No. 4

357

M. di Prisco/M. Colombo/D. Dozio · Fibre-reinforced concrete in fib Model Code 2010: principles, models and test validation

Table 4. Experimental results of four-point bending tests

Material

Specimen No.

fIf,av (std %) [MPa]

feq1,av (std %) [MPa]

feq2,av (std %) [MPa]

M1-F1-0.62

3

4.9 (12.1 %)

7.43 (19.6 %)

8.11 (23.7 %)

M1-F2-0.62

3

5.15 (4.9 %)

7.02 (19.6 %)

6.16 (5.2 %)

M1-F3-0.32-F4-0.32

3

5.15 (3.6 %)

6.92 (4.68 %)

5.89 (16.5 %)

M2-F4-0.62

9

5.94 (10.1 %)

8.39 (6.3 %)

4.87 (15.6 %)

M3-F2-0.62

3

5.79 (1.1 %)

5.34 (8.5 %)

3.91 (15.8 %)

M4-F2-0.62

7

5.02 (7.9 %)

6.44 (18.0 %)

6.27 (17.0 %)

M5-F5-0.45

8

3.54 (10.7 %)

2.91 (20.6 %)

2.69 (36.6 %)

M6-F6-0.45

6

3.13 (11.4 %)

1.47 (31.2 %)

0.73 (54.5 %)

M6-F6-0.83

6

3.36 (11.6 %)

2.10 (10.1 %)

1.33 (13.2 %)

M6-F7-0.45

6

2.84 (10.8 %)

1.88 (21.4 %)

1.26 (37.6 %)

M6-F7-0.83

6

3.70 (11.0 %)

3.52 (27.1 %)

3.18 (39.0 %)

M6-F8-0.45

6

2.49 (19.8 %)

1.81 (42.0 %)

1.53 (63.9 %)

M6-F8-0.83

6

2.90 (19.8 %)

2.46 (18.0 %)

2.51 (18.8 %)

M7-F2-0.62

8

4.01 (10.3 %)

3.19 (22.2 %)

2.03 (32.5 %)

M8-F2-0.62

6

6.84 (5.8 %)

8.45 (19.5 %)

3.87 (28.4 %)

M8-F1-0.62

6

6.76 (7.1 %)

9.80 (12.2 %)

9.22 (14.8 %)

Table 5. Experimental results of three-point bending tests

Material

Specimen No.

fctfl,av (std %) [MPa]

fR1,av (std %) [MPa]

fR3,av (std %) [MPa]

M6-F6-0.45

6

3.54 (9.6 %)

1.30 (23.0 %)

0.68 (42.6 %)

M6-F6-0.83

6

4.12 (4.35 %)

2.07 (16.8 %)

1.41 (20.8 %)

M6-F7-0.45

6

3.41 (14.3 %)

1.42 (15.5 %)

1.21 (11.4 %)

M6-F7-0.83

6

3.95 (20.7 %)

2.54 (38.5 %)

2.31 (40.9 %)

M6-F8-0.45

6

3.20 (7.5 %)

1.92 (27.1 %)

1.97 (38.9 %)

M6-F8-0.83

6

4.15 (10.2 %)

2.90 (28.5 %)

3.21 (30.2 %)

M7-F2-0.62

9

5.06 (13.8 %)

2.53 (30.6 %)

1.86 (35.1 %)

On the contrary, in structures with rebars, where fibres constitute additional reinforcement, ductility is generally provided by conventional reinforcement that makes a major contribution to the tensile strength. For hardening FRCs (in uniaxial tension), fibres can be used as the only reinforcement (without rebars), also in statically determinate structural elements. The heterogeneity of the mechanical behaviour in the post-cracking regime is often significantly penalized due to the high scattering mainly related to fibre distribution and orientation. When a significant redundancy is guaranteed for the structure by its geometry and its boundary conditions, and a large volume of the structure is involved in the failure process, the experimental investigation has highlighted that the average mechanical behaviour – rather than the characteristic one – takes place. For this reason, a suitable coefficient KRd,

358

Structural Concrete 14 (2013), No. 4

aimed at increasing the load bearing capacity of the structure, is introduced [54]. Section 7.7, after a rough classification, also introduces semi-empirical equations for designing FRC structural elements when subjected to shear according to the multi-level approach [68], punching [69] and torsion. There are even suitable equations for slabs and walls as well as specific equations to compute crack distance and crack opening taking into account fibre contribution, which thus allows us to design new FRC structures according to these principles.

8

Concluding remarks

The implementation of fibre reinforced concrete (FRC) in the fib Model Code 2010 is a very important milestone. In

M. di Prisco/M. Colombo/D. Dozio · Fibre-reinforced concrete in fib Model Code 2010: principles, models and test validation

the near future it will probably lead to the development of structural rules for FRC elements in Eurocodes and national codes. This paper has carefully discussed the simplified models suggested for the composite and presented them in the material section to evaluate the uniaxial tension residual strength, mainly given by fibre pull-out. Their reliability as well as their limitations are indicated with reference to several FRC materials, characterized by different matrixes, different steel fibres and different fibre contents. The design rules are derived from a unified classification of FRC composite based on a three-point bending test, already accepted as a European standard. The identification of the constitutive law is also discussed with reference to the structural characteristic length concept and two different kinematic models that can be adopted: plane section and finite element approaches. In all the cases discussed, the procedure fits the experimental tests reasonably well, thus showing an appreciable robustness of the whole design approach. For thin-walled elements, the need for a “structural” specimen to identify the material properties better, taking into account the real casting procedure, is also highlighted with reference to various FRC composites. This requirement becomes essential in the case of self-compacting materials too. Suitable coefficients to take into account inhomogeneous fibre alignments are also introduced. Due to the high scatter of FRC responses, a new coefficient able to consider the beneficial effect of redundancy is also introduced. It is worth noting that although the level of knowledge of FRC has increased tremendously over the last 15 years, further research is needed to verify and optimize the proposed design rules, to investigate the long-term behaviour of different FRCs and other open issues such as the anisotropic behaviour of FRC, fatigue and multi-axial mechanical behaviour. A new generation of FRCs will soon enter the market. They are based on a “cocktail” of different fibre types (material and/or geometry) to enhance different structural performance aspects and fib Model Code 2010 should be ready to open up the way for their usage.

Acknowledgements A special vote of thanks goes to professors L. Vandewalle and G. Plizzari for the excellent cooperation to Prof. J. Walraven for the fruitful discussions and to Prof. H. Falkner, who shared with us his considerable design experience. The authors are also indebted to all the members of fib Task Groups TG 8.3 and TG 8.6 for the constructive discussions during the several meetings, where many ideas presented in this paper took a definitive shape. References 1. Reinhardt, H. W., Naaman, A. E. (eds.): High Performance Fiber Reinforced Cement Composites – HPFRCC 3. RILEM Proc. PRO6. RILEM Publications S.A.R.L., Cachan, France, 1999.

2. Naaman, A. E., Reinhardt, H. W. (eds.): High performance Fiber Reinforced Cement Composites – HPFRCC4, RILEM Proc. PRO30, RILEM Publications S.A.R.L., Bagneaux, France, 2003. 3. Reinhardt, H. W., Naaman, A. E. (eds.): High Performance Fiber Cement Composites – HPFRCC5, PRO53, RILEM Publications S.A.R.L., 2007. 4. Parra-Montesinos, G. J., Reinhardt, H. W., Naaman, A. E.: High Performance Fiber Reinforced Cement Composites 6, RILEM book series, vol. 2, 2012. 5. Rossi, P., Chanvillard, G. (eds.): 5th RILEM Symp. on Fiber Reinforced Concretes. BEFIB 2000, RILEM Proc. PRO15, RILEM Publications S.A.R.L., Cachan, France, 2000. 6. di Prisco, M., Felicetti, R., Plizzari, G. (eds.): Fiber-Reinforced Concrete. BEFIB RILEM Proc. PRO39, RILEM Publications S.A.R.L.. Bagneux, France, 2004. 7. Gettu, R. (ed.): Fibre Reinforced Concrete: Design and Applications. BEFIB 2008, RILEM Proc. PRO60, RILEM Publications S.A.R.L., Bagneux, France, 2008. 8. Barros, J. A. O.: Fibre Reinforced Concrete – Challenges and Opportunities. BEFIB 2012, RILEM International Symp., Proc., Guimarães, Portugal, 2012. 9. di Prisco, M. (ed.): FRC structural applications and standards. Materials and Structures, special issue, 42(9), 2009, pp. 1169–1311. 10. Romualdi, J. P., Batson, G. B.: Mechanics of Crack Arrest in Concrete. Proc., ASCE, vol. 89, EM3, 1963, pp. 147–168. 11. Romualdi, J. P., Mandel, J. A.: Tensile Strength of Concrete Affected by Uniformly Distributed Closely Spaced Short Lengths of Wire Reinforcement. ACI Journal, Proc., 61(6), 1964, pp. 657–671. 12. Shah, S. P., Rangan, B. V.: Effects of reinforcements on ductility of concrete. ASCE Journal of the Structural Division, 96 ST6, 1970, pp. 1167–1184. 13. Shah, S. P., Rangan, B. V.: Ductility of Concrete Reinforced with Stirrups, Fibers and Compression Reinforcement. Journal, Structural Division, ASCE, vol. 96, No. ST6, 1970, pp. 1167–1184. 14. Shah, S. P., Rangan, B. V.: Fiber Reinforced Concrete Properties. ACI Journal, Proc., 68(2), 1971, pp. 126–135. 15. Johnston, C. D.: Steel Fibre Reinforced Mortar and Concrete – A Review of Mechanical Properties. Fiber Reinforced Concrete, SP-44, ACI, Detroit, 1974, pp. 127–142. 16. Naaman, A. E., Shah, S. P.: Bond Studies of Oriented and Aligned Fibers. Proc., RILEM Symposium on Fiber Reinforced Concrete, London, 1975, pp. 171–178. 17. Naaman, A. E., Shah, S. P.: Pullout Mechanism in Steel Fiber Reinforced Concrete. ASCE Journal, Structural Division, vol. 102, No. ST8, 1976, pp. 1537–1548. 18. Shah, S. P., Naaman, A. E.: Mechanical Properties of Steel and Glass Fiber Reinforced Concrete. ACI Journal, Proc., vol. 73, No. 1, 1976, pp. 50–53. 19. Patent Nos. 3,429,094 (1969) & 3,500,728 (1970), Battelle Memorial Institute, Columbus, Ohio; Patent No. 3,650,785 (1972), U.S. Steel Corporation, Pittsburgh, Pennsylvania, United States Patent Office, Washington, D.C. 20. ACI Committee 544: Design considerations for steel Fiber Reinforced Concrete, ACI 544.4R-88. American Concrete Institute, ACI Farmington Hills, MI, 1996. 21. ACI Committee 318: Building code and commentary, Report ACI 318-08/318R-08. American Concrete Institute, Farmington Hills, MI, 2008. 22. Vandewalle, L. et al.: Recommendation of Rilem TC162TDF, 2002. Test and design methods for steel fibre reinforced concrete: Design of steel fibre reinforced concrete using the s-w method: principles and applications. Materials and Structures, vol. 35, pp. 262–278.

Structural Concrete 14 (2013), No. 4

359

M. di Prisco/M. Colombo/D. Dozio · Fibre-reinforced concrete in fib Model Code 2010: principles, models and test validation

23. Vandewalle, L. et al.: Recommendation of Rilem TC162TDF, 2003. Test and design methods for steel fibre reinforced concrete: s-e-design method (final recommendation). Materials and Structures, vol. 36, pp. 560–567. 24. AFGC-SETRA: Ultra High Performance Fibre-Reinforced Concretes, Interim Recommendations, AFGC Publication, France, 2002. 25. Stälfiberbetong, rekommendationer för konstruction, utförande och provning Betongrapport n. 4 – Svenska Betongföreningen, 1995. 26. Deutscher Ausschuss für Stahlbeton (DAfStb): Guidelines for steel fiber reinforced concrete – 23rd draft – richtlinie Stahlfaserbeton – DIN 1045 annex, parts 1–4, 2007. 27. Richtlinie Faserbeton, Osterreichische Vereinigung für Beton- und Bautechnik, 2002. 28. CNR-DT 204, Guidelines for design, construction and production control of fiber reinforced concrete structures. National Research Council of Italy, 2006. 29. JSCE: Recommendations for Design and Construction of High Performance Fiber Reinforced Cement Composites with Multiple Fine Cracks (HPFRCC), Rokugo, K. (ed.), Concrete Engng. Series, 82, 2008. 30. AENOR. UNE 83515. Hormigones con fibras. Determinción de la resistencia a fisuración, tenacidad y resistencia residual a tracción. Metodo Barcelona. Asociación Española de Normalización y Certificación, Madrid, 2010. 31. Triantafillou, T., Matthys, S.: Fibre Reinforced Polymer Reinforcement Enters fib Model Code 2010. Structural Concrete, 14, 2013, doi: 10.1002/suco.201300016. 32. Walraven, J.: fib Model Code for Concrete Structures 2010: mastering challenges and encountering new ones. Structural Concrete, 14, 2013, pp. 3–9, doi: 10.1002/suco.201200062. 33. Bigaj, A., Vrouwenvelder, T.: Reliability in the performancebased concept of the fib Model Code 2010, Structural Concrete, 14, 2013, doi: suco.201300053. 34. Ferrara, L., Ozyurt, N., di Prisco, M.: High mechanical performance of fibre reinforced cementitious composites: the role of “casting flow-induced” fibre orientation. Materials and Structures, 44(1), 2011, pp. 109–128. 35. UNI EN 206-1, 2006. Concrete – Part 1: Specification, performance, production and conformity. 36. Vandewalle, L.: Cracking behaviour of concrete beams reinforced with a combination of ordinary reinforcement and steel fibers. Materials and Structures, 33 (227), 2000, pp. 164–170. 37. Minelli, F., Tiberti, G., Plizzari, G.: Crack control in RC elements with fiber reinforcement. American Concrete Institute, ACI, 280 SP, 2011, pp. 76–93. 38. Leutbecher, T., Fehling, E.: Design for serviceability of ultra high performance concrete structures, RILEM book series, vol. 2, 2012, pp. 445–452. 39. Taerwe, L., Van Gysel, A.: Influence of steel fibers on design stress-strain curve for high-strength concrete. Journal of Engineering Mechanics, 122(8), 1996, pp. 695–704. 40. Campione, G., Fossetti, M., Papia, M.: Behavior of fiber-reinforced concrete columns under axially and eccentrically compressive loads. ACI Structural Journal, vol. 107, No. 3, 2010, pp. 272–281. 41. Bencardino, F., Rizzuti, L., Spadea, G., Swamy, R. N.: Stressstrain behavior of steel fiber-reinforced concrete in compression. Journal of Materials in Civil Engineering, vol. 20, No. 3, 2008, pp. 255–263. 42. di Prisco, M., Colombo, M.: FRC thin-walled structures: opportunities and threats, Fibre Reinforced Concrete – Challenges and Opportunities. BEFIB 2012, RILEM International Symp., Proc., Guimarães, Portugal, 2012.

360

Structural Concrete 14 (2013), No. 4

43. EN 14651, 2004: Test method for metallic fiber concrete – Measuring the flexural tensile strength (limit of proportionality, residual). 44. Hillerborg, A., Modeer, M., Peterson, P. E.: Analysis of crack formation and crack growth by means of fracture mechanics and finite elements. Cement and Concrete Research, 6, 1976, pp. 773–782. 45. Bazant, Z. P., Cedolin, L.: Finite element modeling of crack band propagation. Journal of Structural Engineering 109(1), 1983, pp. 69–92. 46. Ferrara, L., di Prisco, M.: Mode I fracture behavior in concrete: non-local damage modelling. ASCE, Journal of Engineering Mechanics, 127(7), 2001, pp. 678–692. 47. di Prisco, M., Felicetti, R., Gambarova, P. G.: On the evaluation of the characteristic length in high strength concrete. High Strength Concrete, Azizinamini, A., Darwin, D., French, C. (eds.), ASCE, 1999, pp. 377–390. 48. Hillerborg, A.: Analysis of fracture by means of the fictitious crack model, particularly for fibre reinforced concrete. Int. J. Cem. Comp. 2(4), 1980, pp. 177–184. 49. Barr, B. I. G., Lee, M. K., De Place Hansen, E. J., Dupont, D., Erdem, E., Schaerlaekens, S., Schnütgen, B., Stang, H., Vandewalle, L.: Round-robin analysis of the RILEM TC 162-TDF beam-bending test: Part 1 – Test method evaluation, 2003. 50. Taylor, M., Lydon, F. D., Barr, B. I. G.: Toughness measurements on steel fibre-reinforced high strength concrete. Cement and Concrete Composites, vol. 19(4), 1997, pp. 329–340. 51. Ferrara, L., di Prisco, M.: Three- vs. four-point bending test for the characterization of plain concrete: a numerical investigation, studies and research. Graduate School in Concrete Structures, Politecnico di Milano, Italy, 22, 2001, pp. 73–119. 52. UNI 11039, 2003. Concrete reinforced with steel fibres. Part II: test method for the determination of first cracking strength and ductility indexes. 53. di Prisco, M., Felicetti, R., Iorio, F., Gettu, R.: On the identification of SFRC tensile constitutive behaviour; in: Fracture mechanics of Concrete structures, de Borst, R., Mazars, J., Pijaudier-Cabot, G., van Mier, J. G. M. (eds.), vol.1, A. A. Balkema Publishers, 2001, pp. 541–548. 54. Dozio, D.: SFRC structures: identification of the uniaxial tension characteristic constitutive law. PhD thesis, Dept. of Structural Engineering, Politecnico di Milano, Starrylink (ed.), 2008, ISBN 978-88-96225-14-1. 55. Colombo, M., di Prisco, M., Felicetti, R.: Mechanical properties of Steel Fibre Reinforced Concrete exposed at high temperatures. Materials and Structures, 43(4), 2010, pp. 475–491. 56. Rots, J. G.: Computational modelling of concrete fracture. PhD thesis, Delft University of Technology, 1988. 57. Löfgren, I. , Stang, H., Olesen, J. F.: Fracture properties of FRC determined through inverse analysis of wedge splitting and three-point bending tests. Journal of Advanced Concrete Technology, 3(3), 2005, pp. 423–434. 58. di Prisco, M., Plizzari, G., Vandewalle, L.: Fibre reinforced concrete: new design perspectives. Materials and Structures, 42(9), 2009, pp. 1261–1281. 59. di Prisco, M., Felicetti, R., Iorio, F.: Il comportamento flessionale di elementi sottili in HPC; in: La meccanica della frattura nel calcestruzzo ad alte prestazioni, di Prisco, M., Plizzari, G. (eds.), Starrylink, Brescia, 2003,pp. 157–182. 60. di Prisco, M., Ferrara, L., Colombo, M., Mauri, M.: On the identification of SFRC constitutive law in uniaxial tension – in Fiber reinforced concrete, di Prisco, M. et al. (eds.), Proc. of 6th Rilem Symp. BEFIB 04, Varenna (Italy), PRO 39, Rilem Publications S.A.R.L., Bagneaux, France, 2004, pp. 827–836.

M. di Prisco/M. Colombo/D. Dozio · Fibre-reinforced concrete in fib Model Code 2010: principles, models and test validation

61. di Prisco, M., Felicetti, R., Lamperti M., Menotti, G.: On size effect in tension of SFRC thin plates; in: Fracture Mechanics of Concrete Structures, Li, V. C., Leung, C. K. Y., Willam, K. J., Billington, S. L. (eds.), 2, Schmick B. L., Pollington, A. D., USA, 2004, pp. 1075–1082. 62. UNI 11188, 2004. Design, Production and Control of Steel Fibre Reinforced Structural Elements. Italian Board of Standardization. 63. di Prisco, M., Dozio, D.: Post-tensioned SFRC beams in Fibre Reinforced Concrete: design and applications, Proc. of 7th Rilem Int. Conf. BEFIB 08, ISBN 978-2-35158-064-6, Rilem Publications S.A.R.L., Bagneux, France, PRO 60, 2008, pp. 899–910. 64. di Prisco M., Dozio D., Galli A., Lapolla, S.: Assessment and control of a SFRC retaining structure: Mechanical issues. European Journal of Environmental and Civil Engineering, 14 (10), 2010, pp. 1259–1296. 65. di Prisco, M., Iorio, F., Plizzari, G.: HPSFRC prestressed roof elements; in: Test and design methods for steel fibre reinforced concrete – Background and experiences, Schnütgen, B., Vandewalle, L. (eds.), PRO 31, RILEM, 2003, pp. 161–188. 66. di Prisco, M., Dozio, D., Belletti, B.: On the fracture behaviour of thin-walled SFRC roof elements. Materials and Structures, 46(5), 2013, pp. 803–829. 67. Cervenka, V.: Reliability-based non-linear analysis according to fib Model Code 2010. Structural Concrete, 14, 2013, pp. 19–28, doi: 10.1002/suco.201200022. 68. Sigrist, V., Bentz, E., Fernández Ruiz, M., Foster, S., Muttoni, A.: Background to the fib Model Code 2010 Shear Provisions – Part I: Beams and Slabs. Structural Concrete, 14, 2013, doi: 10.1002/suco.201200066.

69. Muttoni, A., Fernández Ruiz, M., Bentz, E., Foster, S., Sigrist, V.: Background to the fib Model Code 2010 Shear Provisions – Part II Punching Shear. Structural Concrete, 14, 2013, doi: 10.1002/suco.201200064. Marco di Prisco, Ph.D. Full Professor Politecnico di Milano Department of Civil and Environmental Engineering Piazza Leonardo da Vinci, 32 20133 Milan, Italy [email protected] Tel: +390223998794, Fax: +390223998377 Matteo Colombo, Ph. D. Assistant Professor Politecnico di Milano Department of Civil and Environmental Engineering Piazza Leonardo da Vinci, 32 20133 Milan, Italy [email protected] Tel: +390223998789, Fax: +390223998377

Daniele Dozio, Ph.D. Senior Structural Engineer Arup Corso Italia, 13 20122 Milan, Italy [email protected] Tel: +390285979381, Fax: +39028053984