December 15, 2022 | Author: Anonymous | Category: N/A
Download PR-1948 - Electrical Safety Operating Procedures...
Petroleum Development Oman L.L.C.
UNRESTRICTED Oct. 2010
Document ID: PR-1948 Filing key: A-71
Electrical Safety Operating Procedures
User Note: The requirements of this document are mandatory. Non-compliance shall only be authorised by the Document Owner or his Delegate through STEP-OUT approval. approval. A controlled copy of the current version of this document is on PDO's EDMS. Before making reference to this document, it is the user's responsibility to ensure that any hard copy, or electronic copy, is current. For assistance, contact the Document Custodian or Custodian or the Document Controller . Users are encouraged to participate in the ongoing improvement of this document by providing constructive feedback constructive feedback .
Please familiarise yourself with the
Document Security Classification Definitions They also apply to this Document!
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
This page was intentionally left blank
Page 2
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
i
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
Document Authorisation
Authorised for Issue Oct. 2010
Page 3
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
ii Revision History The following is a brief summary of the 4 most recent revisions to this document. Details of all revisions prior to these are held on file by the issuing department. Note that changes made as part of Document Maintenance (correction of broken hyperlinks) will not be recorded in this Revision Table.
Revision No.
Date
Version 10.0
Oct. 2010
Version 9.0
May.10
Version 8.0
Oct. 04
Version 7.0
Feb. 00
Author/ Editor
UIE/3S
UIE/3
TTE/3 TTE/3
Changes/ Remarks
Minor corrections made in ESOPs-4,6,7, 15,18&22 in line with comments received from field and cosmetic changes made in all ESOPs Converted SP1108-1/25 to PR1948 and reformatted, ref. indicators changed & combined all ESOPs into ONE document Minor changes Converted to Specification as per PDO policy Cascade, ESOP ESOP – 13 deleted
iii Related Business Processes Code
Business Process (EPBM V.4.0)
EP-72
Maintenance and Assure Facilities Integrity
iv Related Corporate Management Frame Work (CMF) Document Documents s CP-14
Maintenance
GU-323
Key Business Control Document
GU-290
Power System Asset Management
PR-1947
Electrical safety Rules
PR-1259
Infrastructure Management Procedures
PR-1344
Asset Activity Registration and Deletion in SAP
The related CMF Documents can be retrieved from the the CMF Business Control Portal at PDO Website.
Page 4
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
Contents i
Document Authorisatio Authorisation n .................... .......................................... ............................................. ............................... ........ 3
ii
Revision History .................... ........................................... ............................................. ............................................ ........................ 4
iii
Related Business Proces Processes ses .................... .......................................... ............................................. ........................... .... 4
iv
Related Corporate Management Frame Work (CMF) Documents .... 4
1.
Introductio Introduction n................... ......................................... ............................................ ............................................ ............................. ....... 11 1.1 Purpose ........................................................................ .............................................................................................................. ...................................... 11 .............................................................................................. ................................. 11 1.1.1 Specific Precautions............................................................. 1.1.2 Distribution of Procedures .................................................................................... 11
2.
APPLICAB APPLICABLE LE STANDARDS, SPECIFICATION AND CODES ....12
3.
ESOP Index ................... ......................................... ............................................ ............................................ ............................. ....... 13
4.
ESOP-1...................... ............................................. .............................................. ............................................. ................................ .......... 15 1.
.............................................................................................................. ................ 15 General ..............................................................................................
2.
Custodian ................................... ......................................................................................................... ........................................................................ .. 15
3. 4.
Scale of Issue of the ESR .................................................................................. .................................................................................. 15 .............................................................................. 15 Scale of Issue of the ESOPs ..............................................................................
5.
Identification of the ESR and ESOPs ........................................................... ................................................................ ..... 15
6.
............................................................................. 15 Issue of the ESR and ESOPs .............................................................................
7.
................................................................................ ............. 16 LOSS OF ESR OR ESOPs ...................................................................
5.
ESOP – 2 ............................................................. ................................................................................... .................................... .............. 17 1.
Objectives ............................................. .......................................................................................................... ............................................................. 17
2.
.................................................................................. ................ 17 Standard Electrical Locks..................................................................
2.1 Details of Approved Electrical Locks ............................................................... ............................................................... 17 3.
...................................................... 19 Locking of Substations and Power Stations ......................................................
4. 5.
Locking of Switchgear ...................................................................................... ...................................................................................... 19 Safety Padlocks .......................................................... ................................................................................................. ....................................... 19
6.
...................................................................................... 19 Provision of Key Safes ......................................................................................
7.
............................................................................ 20 Design and Use of Key Safes ............................................................................
8.
Issue of Keys ..................................................................................................... ..................................................................................................... 21
9.
Securing of Safety Padlock Keys when Key Safes are not available ................ 21
6.
ESOP – 3 ............................................................. ................................................................................... .................................... .............. 22 1.
General .............................................................................................. .............................................................................................................. ................ 22
2.
Selection of Electrical Persons and Appointed Persons.................................... 22
Page 5
2.1 2.2 2.3
General............................................................ .................................................................................................................. ...................................................... 22 Competent Electrical Person (CEP) ...................................................................... 23 Competent Electrical Switching Person (CESP) ................................................... 23
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
2.4 2.5 2.6 2.7
Vers ion 10.0 10.0 Effective:Oct-10
Authorised Electrical Person (AEP) ( AEP) ..................................................................... .................................... ................................. 23 Senior Authorised Electrical Person (SAEP) ........................................................ 23 Control Person (CP) ............................................................. .............................................................................................. ................................. 24 Appointed Person (AP) ....................................................... ........................................................................................ ................................. 24
3.
Training of Electrical Persons and Appointed Persons ..................................... 25
4.
Assessme Assessment nt of Candidates for EP and AP Status .............................................. .............................................. 27
3.1 3.2 4.1 4.2 4.3 4.4 4.5 4.6
General............................................................ .................................................................................................................. ...................................................... 25 Training for Electrical Persons ............................................................................. ....................................................... ...................... 25 Competent Electrical Person (CEP) ...................................................................... 27 Competent Electrical Switching Person (CESP) ................................................... 27 Authorised Electrical Person (AEP) .................................... ................................. 28 ( AEP) ..................................................................... Senior Authorised Person (SAEP) ........................................................................ 28 Control Person (CP) ............................................................. .............................................................................................. ................................. 28 Appointed Person (AP) ........................................................ ......................................................................................... ................................. 29
5.
Appointment of Electrical Persons and Appointed Persons.............................. 29
6.
Periodic Re-Assessment of Electrical Persons and Appointed Persons ............ 29
7.
Recording of Training, Assessme Assessment nt and Registration of Appointments ........... 30
7.
7.1 7.2 7.3
General............................................................ .................................................................................................................. ...................................................... 30 Recording of Training & Assessment ................................................................... 30 Registration of Appointments ............................................................................... 30
ESOP – 4 ............................................................. ................................................................................... .................................... .............. 33 1.
....................................................................................................... ................ 33 Introduction .......................................................................................
2.
Objective ........................................................................................................... 33
3.
Preparation of Switching Programmes ......................................................... .............................................................. ..... 33
4.
Implem Implementation entation of Switching Programmes ....................................................... ....................................................... 33
5.
Emerge Emergency ncy Switching Programm Programmes es.............................................................. ................................................................... ..... 34
6.
Emerge Emergency ncy Switching Without Switching Programm Programmes es ................................... 34
8.
ESOP – 5 ............................................................. ................................................................................... .................................... .............. 39 1.
.............................................................................................................. ................ 39 General ..............................................................................................
2.
Approved Devices ........................................................................................ ............................................................................................. ..... 39
3.
Use of Devices............................................................ ................................................................................................... ....................................... 39
4.
............................................................................................. 39 Method of Testing .............................................................................................
5.
Storage and Inspection ...................................................................................... ...................................................................................... 39
6.
Inspection and Maintenance .............................................................. .............................................................................. ................ 40
9.
ESOP – 6 ............................................................. ................................................................................... .................................... .............. 42 1.
General .............................................................................................. .............................................................................................................. ................ 42
2.
Switchgear with Adequately Rated Earthing Capacity ..................................... ..................................... 42
3.
................. 42 Approved Portable Earthing Leads for Use as Circuit Main Earths .................
4.
Approved Portable Earthing Leads for Use as Additional Earths ..................... 43
5.
Identification of Portable Earthing Leads ......................................................... ......................................................... 43
6. Page 6
Maintenance of Portable Earthing Leads .......................................................... .......................................................... 43
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
7.
Operating Rods for Applying Portable Earthing Leads .................................... 43
8.
Application of Portable Earthing Leads ............................................................ 44
10.
ESOP – 7 ............................................................. ................................................................................... .................................... .............. 46
1.
General .............................................................................................. .............................................................................................................. ................ 46
2.
................................................................................. 46 Initial Construction Phase .................................................................................
3.
Final Construction Phase................................................................... ................................................................................... ................ 46
4.
Scope of ESR.............................................................. ..................................................................................................... ....................................... 46
5.
Commissioning issioning Procedure................................................................. Procedure................................................................. 46 Notice of Comm
6.
Notice of Comm Commissioning issioning Forms..................................................................... ....................................................................... .. 47
11.
ESOP – 8 ............................................................. ................................................................................... .................................... .............. 49
1.
.............................................................................................................. ................ 49 General ..............................................................................................
2.
........................................................................................................ .. 49 Basic Rules ......................................................................................................
3.
Removing or Replacing LV Fuses on Switchboards ......................................... 49
4.
Procedures............................................................. ........................... 50 Additional Precautions and Procedures..................................
5.
Energising LV Circuits ........................................................... ...................................................................................... ........................... 50
6.
Fuse Replaceme Replacement nt................................................................... .............................................................................................. ........................... 50
1.
Introduction ....................................................................................... ....................................................................................................... ................ 52
2.
Scope ...................................................................................... ................................................................................................................. ........................... 52
3.
..................................................................... .. 52 Boundaries / Responsible Persons ...................................................................
4.
Procedures .............................................................................. ......................................................................................................... ........................... 52
5.
Method of Supply Connection .......................................................................... .......................................................................... 53
6.
..................................................................... .. 53 Isolation / De-Isolation Procedure ...................................................................
7.
Maintenance / Repair Activities ........................................................................ ........................................................................ 53
8.
Isolation / De-Isolation in Emerge Emergencies ncies ............................................................ ............................................................ 54
9.
Work Near or Under the Overhead Line ........................................................... ........................................................... 54
1.
Objectives ............................................. .......................................................................................................... ............................................................. 57
2.
.................................................................................................... ....................................... 57 Cable Records.............................................................
3.
Visual and Physical Identification................................................................... ..................................................................... .. 57
4.
.................................................................. ..... 57 Electrical Methods of Identification.............................................................
5.
Use of Electrical Testing Equipment to Identify Cables ................................... 57
6.
Use of Approved Cable Spiking Guns .............................................................. 58
7.
High Voltage Cables that need not to be Spiked .............................................. 58
12.
13.
14. 1. Page 7
ESOP – 9 ............................................................. ................................................................................... .................................... .............. 52
ESOP – 10 ........................................................... ................................................................................. .................................... .............. 57
ESOP – 11 ........................................................... ................................................................................. .................................... .............. 60 General .............................................................................................. .............................................................................................................. ................ 60
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
2.
Generating or Rotating Plant ............................................................................. ............................................................................. 60
3.
Installations............................................................. ............................................................. 60 Automatic Fire Protection Installations
4.
Imm Immobilisation/Mobilisation obilisation/Mobilisation Procedure by AP- Specific LV Motors .............. 60
15.
ESOP – 12 ........................................................... ................................................................................. .................................... .............. 64
1.
.............................................................................................................. ................ 64 General ..............................................................................................
2.
Notices ............................................................. ............................................................................................................... .................................................. 64
3.
Equipment to be Provided ................................................................................. ................................................................................. 64
4.
........................................................................................................ ............................................................. 65 Information ...........................................
5.
Technical Data............................................................ ................................................................................................... ....................................... 65
6.
Storage of Information ...................................................................................... ...................................................................................... 65
16.
ESOP – 14 ........................................................... ................................................................................. .................................... .............. 66
1.
.......................................................................................................... ............................................................. 66 Objectives .............................................
2.
Loss of an Electrical Safety Document ............................................................. 66
17.
ESOP – 15 ........................................................... ................................................................................. .................................... .............. 67
1.
General .............................................................................................. .............................................................................................................. ................ 67
2. 3.
IDENTI IDENTIFICATIO FICATION N of ELECTRI ELECTRICAL CAL PERSONN PERSONNEL EL ...................................... 67 Boundaries........................................................... ................ 67 Selection of System Control Boundaries...........................................
4.
Operation of Apparatus ..................................................................................... ..................................................................................... 68
5.
Schedule of System Control .............................................................................. .............................................................................. 68
18.
ESOP – 16 ........................................................... ................................................................................. .................................... .............. 71
1.
Objectives ............................................. .......................................................................................................... ............................................................. 71
2.
Preparation of Switchgear Operating Procedures ............................................. 71
3.
Switchgear Operating Procedures ..................................................................... 71
4.
Approval of Switchgear Operating Procedures ................................................. 72
5.
Preparation of Procedures for Appointed Persons ............................................ ............................................ 72
6. 7.
.................................................................... 72 Procedures for Appointed Persons .................................................................... Approval of Procedures for Appointed Persons ................................................ 73
19.
ESOP – 17 ........................................................... ................................................................................. .................................... .............. 74
1.
General .............................................................................................. .............................................................................................................. ................ 74
2.
Identification of MEDC/ORPC/PD MEDC/ORPC/PDO O Groups of Personnel .............................. 74
3.
Main Division of Control Responsibilities ....................................................... 74
4.
Selection of System Control Boundaries........................................... Boundaries........................................................... ................ 75
5.
..................................................................................... 75 Operation of Apparatus .....................................................................................
6.
Identification of Apparatus................................................................... ................................................................................ ............. 75
7.
Schedule of System Control and Operation ...................................................... 75
20. Page 8
ESOP – 18 ........................................................... ................................................................................. .................................... .............. 77 PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
1.
General .............................................................................................. .............................................................................................................. ................ 77
2.
.......................................................................................... ...................................................................................... ................ 77 Objections ....................
3.
Accidents and Incidents.......................................................... ..................................................................................... ........................... 77
4.
Failure of Supply / Electrical Fault ................................................................... 77
5.
Emergency ncy Switching ............................................................. ........................................................................................ ........................... 78 Emerge
6.
Control Person Reports ..................................................................................... ..................................................................................... 78
7.
Guidelines for Preparing Fault / Failure Reports .............................................. 78
21.
ESOP – 21 ........................................................... ................................................................................. .................................... .............. 83
1.
General .............................................................................................. .............................................................................................................. ................ 83
2.
The Need for Approved Portable LV Earthing Equipment ............................... 83
3.
Approved Equipment for Use as LV Earths ...................................................... 83
4.
Maintenance of LV Earthing Equipment .......................................................... .......................................................... 84
5.
Application of LV Earthing Devices............................................................ ................................................................. ..... 84
6.
Applying LV Earths to Low Voltage Switchboards ......................................... 84
22.
ESOP – 22 ........................................................... ................................................................................. .................................... .............. 86
1. 2.
.............................................................................................................. ................ 86 General .............................................................................................. Objectives ............................................. .......................................................................................................... ............................................................. 86
3.
Live Line Working Practices ............................................................. ............................................................................. ................ 86
4.
............................................................................. ................ 90 Live Line Washing Practices .............................................................
5.
Contractor's LLW Procedures ........................................................................... ........................................................................... 91
6.
Contractor's Live Line Washing Procedures ..................................................... 93
7.
PDO ESR and Live Line Working Procedures ................................................. 94
8.
PDO ESR and Live Line Washing Procedures ................................................. 97
Page 9
3.1 3.2 3.3 3.4 3.5 3.6
General Precautions to be Observed for LLW ...................................................... 86 Routine Care, Inspection and Electrical Testing of LLW Tools ........................... 88 Provision of Sufficient LLW Tools T ools for LLW Procedures ..................................... 89 LLW Team Numbers Required for Specific Procedures ...................................... 89 Safe Working Clearances or Distances ................................................................. 89 Illustration of LLW Procedures ............................................................................ ................................................................ ............ 89
4.1 General............................................................ .................................................................................................................. ...................................................... 90 ......................................................................................... ................................. 90 4.2 Nozzle Design and Use........................................................ 4.3 Water Pressure at the Nozzle .......................................................... ................................................................................ ...................... 90 4.4 Conductivity of Water Used for LL Washing ....................................................... 90 5.1 5.2 5.3 6.1 6.2 6.3 7.1 7.2 7.3
What to Look for In Contractor's LLW Procedures .............................................. 91 English Translation of LLW Procedures............................................................... 92 Stress Conditions of Conductors and Supports during LLW ................................ 92 What to Look for in Contractor's LL Washing Procedures ...................................93 Portable LL Washing W ashing Equipment ............................................................... .......................................................................... ........... 93 Conductivity of the Water Used for LL Washing ................................................. ................................... .............. 94 LLW Procedures - Initiation, Progress and Completion ....................................... 94 Interpretation of the ESR for LLW Procedures .................................................... .............................. ...................... 95 PDO AEPs Duties for LLW Procedures P rocedures ............................................................... 96
8.1
LLW Procedures Initiation, Progress and Completion ........................................97
8.2
Application of the ESR for LL Washing Procedures Pr ocedures ............................................ 97
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
ESOP – 23 .................... ........................................... .............................................. ............................................. ......................................... ................... 101 1.
........................................................................................................ ........................................................... 101 Objectives .............................................
2.
...................................................................................................... ......................... 101 PDO Policy .............................................................................
3.
Action Required on PDO Sites .......................................................... ........................................................................ .............. 101
4.
Operation of Units Subject to an Operational Restriction .............................. 101
5.
Remova Removall Of A PDO Operational Restriction .................................................. .................................................. 102
23.
ESOP – 23/S1................................... ......................................................... ............................................. ............................... ........104
1.
Background to Restriction ................................................................. ............................................................................... .............. 104
2.
Operational Restriction .......................................................... ................................................................................... ......................... 104
3.
Requirements Of ESOP 23 .............................................................................. .............................................................................. 105
24.
ESOP – 24 ........................................................... ................................................................................. .................................. ............ 106
1.
........................................................................................................ ........................................................... 106 Objectives .............................................
2.
Purpose of the ESOP ....................................................................................... ....................................................................................... 106
3.
................................................................. 106 Relevant Requirements of the ESR .................................................................
4.
Provision of Safety Equipment Called for by other ESOP ............................. 106
5. 6.
Tool s .................................. .................................. 106 Provision and Inspection of Approved Insulated Tools Provision, Storage and Testing of Approved Electrical Rubber Gloves ......... 107
7.
Provision of Eye Protection for Use When Switching .................................... .................................... 107
8.
Flexible Leads for Use with Portable Voltage Operated Instruments ............. 107
25.
8.1 8.2 8.3
Permanently Attached Leads........................................................... ............................................................................... .................... 107 Temporarily Attached Leads ............................................................................... 108 Fuses for Flexible Leads ..................................................................................... ............................................................................ ......... 108
ESOP – 25 ........................................................... ................................................................................. .................................. ............ 110
1.
............................................................................................................ .............. 110 General ..............................................................................................
2.
................................................................ ... 110 Use of Electrical Safety Documents.............................................................
3.
Preparation of Electrical Safety Documents ................................................... 111
4.
.............................................................. ... 112 Issue of Electrical Safety Documents...........................................................
5.
Cancellation of Electrical Safety Documents.................................................. 112
6.
Retention of Electrical Safety Documents ...................................................... ...................................................... 113
4.1 4.2 4.3 5.1 5.2 5.3
Electrical Permits-to-Work ................................................................................. ............................. .................................................... 112 Sanctions-for-Test ............................................................................................... 112 Limitations-of-Access .................................... ..................................................... 112 Limitations-of-Access ......................................................................................... Electrical Permits-to-Work ................................................................................. ............................. .................................................... 112 Sanctions-for-Test ............................................................................................... 113 Limitations-of-Access .................................... ..................................................... 113 Limitations-of-Access .........................................................................................
APPENDICES APPENDIX A - GLOSSARY OF DEFINITIONS, TERMS AND ABBREVIATIONS................................. 128 ....................................................................................................................... .......................................................... 117 SP USER-COMMENT FORM ............................................................. Page 10
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
1.
Introduction
1.1
Purpose
Vers ion 10.0 10.0 Effective:Oct-10
These ELECTRICAL SAFETY OPERATIONAL PROCEDURES are issued by the Corporate Functional Discipline Head Electrical to supplement the PDO ELECTRICAL SAFETY RULES and define policies that assist in their implementation. The policies defined in these PROCEDURES cover a wide range of subjects that affect the safe operation work on the PDO HIGH and associated LOW VOLTAGE electrical systems and include the detail of the APPROVED method and devices called for in the ELECTRICAL SAFETY RULES.
1.1.1
Specific Precautions Certain PROCEDURES call for specific precautions or methods to be adopted in particular operations, individual individual locations or sites. These PROCEDURES shall be given a suffix 'S' after the ESOP number.
1.1.2
Distribution of Procedures The distribution of these PROCEDURES shall be in accordance with ESOP 1.
Page 11
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
2. APPLICABLE STANDARDS, STANDARDS, SPECIFICATION AND CODES The following documents shall be referred when applying the requirement of this standard . DOCUMENT TITLE
Page 12
REF.
ESOP
CUST.
1. Electrical Safety Rules
PR-1947
all
UIE/3
2. PTW Manual 3. HSES Manual Manual
SP - 1172 HSEM
all all
CSM CSM
4. Incident Investigation, Reporting and Followup Procedures & Guidelines (version 2.0)
SRD/P/01
18
CSM
5. Fire Extinguishers
SRD/S/02
12
CSM
6. Emergency Response Procedure Part III Volume 7: Electrical Utilities (Interior)
PR -1168
18
UIE / 3
7. Emergency Response Procedure Part III Volume 10: MAF Offices
PR-1168
18
UIB/12
8. Insulating poles (insulating sticks) and universal tool attachment (fittings) for live working
IEC 60832
24
UIE / 4
9. Hand tools for live working up to 1000Vac tools and 1500Vdc
IEC 60900
24
UIE / 4
10. Specification for rubber gloves for electrical purposes
BS 697
24
UIE / 4
11. Specification for eye-protectors for (non-) industrial uses
BS 2092
24
UIE / 4
12. Electrical test equipment for use by Electricians HSE guidance note GS 38
UK HSE
24
UIE / 4
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
3.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
ESOP Index ESOP NO
ISSUE DATE
ESOP TITLE
1
10 / 2010
ISSUE OF ELECTRICAL SAFETY RULES AND ELECTRICAL SAFETY OPERATIONAL PROCEDURES
2
10 / 2010
LOCKING PROCEDURES AND PROVISION AND USE OF KEY SAFES
3
10 / 2010
SELECTION, TRAINING, ASSESSMENT AND APPOINTMENT OF ELECTRICAL PERSONS (EPs) AND APPOINTED PERSONS (APs)
4
10 / 2010
PREPARATION AND USE OF SWIT SWITCHING CHING PROGRAMMES FOR HIGH VOLTAGE SYSTEMS
5
10 / 2010
VOLTAGE TESTING AND PHASING OUT DEVICES
6
10 / 2010
EARTHING EQUIPMENT FOR USE ON HIGH VOLTAGE APPARATUS
7
10 / 2010
NOTICE OF COMMISSIONING OF HIGH VOLTAGE APPARATUS
8
10 / 2010
BASIC RULES FOR PLANT OPERATION
9
10 / 2010
INTERFACE PROCEDURES BETWEEN PDO OPERATIONAL AREAS AND THIRD PARTY DISTRIBUTION SYSTEMS.
10
10 / 2010
ELECTRICAL IDENTIFICATION OF UNDERGROUND CABLES
11
10 / 2010
MECHANICAL RULES FOR GENERATING MACHINES AND OTHER PLANT
12
10 / 2010
PROVISION OF SUBSTATION EQUIPMENT AND INFORMATION DELETED
13 10 / 2010
LOSS OF ELECTRICAL SAFETY DOCUMENTS AND ELECTRICAL KEYS
ISSUE DATE
ESOP TITLE
15
10 / 2010
BOUNDARY PROCEDURE FOR THE INTERIOR HIGH VOLTAGE ELECTRICAL SYSTEM
16
10 / 2010
PROVISION OF SWITCHGEAR OPERATING PROCEDURES & PROCEDURES FOR APPOINTED PERSONS
17
10 / 2010
BOUNDARY PROCEDURE FOR COASTAL AREA OETC/ORC/PDO ELECTRICAL SYSTEM
14
ESOP NO
Page 13
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
18
10 / 2010
REPORTING OF ACCIDENTS AND INCIDENTS AND EMERGENCY SWITCHING
19
Reserved for future use
20
Reserved for future use
21
10 / 2010
Vers ion 10.0 10.0 Effective:Oct-10
APPLICATION OF LV EARTHING DEVICES TO LOW VOLTAGE SWITCHBOARDS
22
10 / 2010
LIVE LINE WORKING AND LIVE LINE WASHING PRACTICES
23
10 / 2010
IDENTIFICATION OF HIGH OR LOW VOLTAGE SWITCHGEAR SUBJECT TO AN OPERATIONAL RESTRICTION
23/S1
10 / 2010
OPERATIONAL RESTRICTION ON HOLEC CAPITOLE 3 AND 3N LOW VOLTAGE SWITCHBOARDS
24
10 / 2010
PROVISION OF MISCELLANEOUS SAFETY EQUIPMENT FOR OPERATIONAL PURPOSES
25
10 / 2010
PREPARATION, ISSUE, CLEARANCE, CANCELLATION AND RETENTION OF ELECTRICAL SAFETY DOCUMENTS
Page 14
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
4.
Vers ion 10.0 10.0 Effective:Oct-10
ESOP-1 ESOP-1- ISSUE OF ELECTRICAL SAFETY RULES AND ELECTRICAL SAFETY OPERATIONAL PROCEDURES PROCEDURES
1.
2.
3.
4.
5.
General 1.1
All persons who have to operate work work or supervise activities on the PDO HV or associated LV electrical systems require a copy of the ESR.
1.2
All EPs and those who are involved involved in managing these systems require a copy of the ESOPs.
1.3
This PROCEDURE is issued to ensure that all such persons who require ESR or ESOPs either have personal copies or have ready access to them.
Custodian 2.1
The Custodian for both the ESR and ESOPs is the CFDH-E.
2.2
All new issues, revisions, amendments or additions to both ESR and ESOPs shall shall be prepared, approved and issued under the direction of the CFDH-E.
2.3
The scale of issue issue of both ESR and ESOPs shall be the the responsibility responsibility of the CFDH-E.
Scale of Issue of the ESR 3.1
All PDO and Contractor's Contractor's personnel who hold a CofA as SAEP, AEP, CESP, CEP, CP and AP shall be issued with a personal copy of the ESR.
3.2
All other issues of the ESR for PDO management, information or training purposes shall be at the discretion of the CFDH-E.
Scale of Issue of the ESOPs 4.1
All PDO and Contractor's Contractor's personnel who hold a CofA as SAEP, AEP, CESP, CEP and CP shall be issued with a personal copy of the ESOPs.
4.2
All other issues of the ESOPs for PDO management, information or training purposes shall be at the discretion of the CFDH-E.
Identification of the ESR and ESOPs 5.1
All copies of the ESR and ESOPs shall be identified identified by an individual number. The individual number shall be the ESR number, as indicated on the CofA.
6.
5.2
Head of Power system operation and and maintenance shall keep a record so that all all copies of both the ESR and ESOPs can be located in the possession of the person or department issued with them.
5.3
Personal copies of ESR and ESOPs shall shall not be transferred when an individual either leaves or no longer requires them; his copies of both the ESR and ESOPs shall be returned to the Head of Power system operation and maintenance.
Issue of the ESR and ESOPs 6.1
Page 15
Head of Power Power system system operation operation and maintenance shall shall ensure that that a record is kept of individual copy numbers of all ESR and ESOPs issued to PDO and Contractor's personnel.
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
7.
Page 16
Vers ion 10.0 10.0 Effective:Oct-10
6.2
Recipients shall be instructed to maintain maintain their their personal personal copies of ESR and ESOPs in good order and be responsible for updating them when revisions, amendments and additions are issued.
6.3
When copies of ESR and ESOPs are issued issued for information to a Contractor, Contractor, Consultant or PDO Department, then a named representative shall sign a receipt and be made responsible for maintaining them in good order, and updating them when revisions, amendments or additions are issued.
LOSS OF ESR OR ESOPs 7.1 Loss of any any copy of ESR ESR or ESOPs shall be reported reported to the appropriate appropriate Head Head of Power system operation and maintenance
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
5.
Vers ion 10.0 10.0 Effective:Oct-10
ESOP – 2 ESOP 2 LOCKING PROCEDURES, PROVISION OF KEY SAFES AND ISSUE OF KEYS
1.
2.
Objectives 1.1
To specify standards for the secure locking locking arrangements for all power stations and substations to prevent unauthorised access.
1.2
To specify standards for the secure locking of HV and associated LV APPARATUS, both in the service position and when it has been ISOLATED, to allow safe working under ELECTRICAL SAFETY DOCUMENTS. i.e. ELECTRICAL PERMITS-TOWORK, SANCTIONS-FOR-TEST, LIMITATIONS-OF-ACCESS or ELECTRICAL ISOLATION/DE-ISOLATION CERTIFICATES.
1.3
To monitor the issue of keys for STANDARD ELECTRICAL PADLOCKS, SAFETY PADLOCKS and KEY SAFES to persons authorised to receive them.
Standard Electrical Locks 2.1
A master slave system or similar double key system shall be adopted in all PDO Area.
2.2
The system system adopted shall allow for at least two levels of STANDARD ELECTRICAL PADLOCKS/LOCKS to be available for use so that access can be limited to persons appointed under the ESR.
2.3
Details of the STANDARD ELECTRICAL PADLOCKS/LOCKS used at present by Electrical Infrastructure Department are given in the following sections.
2.4
All locks shall be UNION make and engraved as detailed in the following sections.
2.5
All locks shall be procured by Electrical Infrastructure Operation & Maintenance Department. These locks shall be kept in safe custody of the Power System Control Person
2.6
The Electrical Control Person shall issue required electrical locks to the Company Project departments as and when required for free issue to the Contractors for use in Company Project works.
2.6
The locks shall be issued to the responsible person of the contractor. The Project department shall maintain proper record of all issue of locks to the contractors and ensure that they are not misplaced / misused and are traceable. The project department and the contractor shall be accountable for all the locks issued.
2.1
Details of Approv Approved ed Electrical Locks Manufacturer UNION LOCKS-JOSIAH PARKES & SONS LTD UNION WORKS – WORKS – WILLEN WILLEN HALL- ENGLAND Local Dealer DHIYA AL-HILAL TRADING EST VENDOR CODE NUMBER: 100847 Vendor e-mail: e-mail:
[email protected] [email protected]
Types of Locks Page 17
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
For LV Isolation /Panels SAP No.
1000798910
Series :
LT LT
Size:
31mm.
Type:
J3104
Description: Cylinder Description: Cylinder type, brass automatic locking with nickel plated hardened steel spring shackle to be master keyed to the existing BFFW / LT engraved locks, supplied with 2 keys. Locks and keys are to be engraved with serial numbers from LT2101 to LT2300. NOTE: Required serial numbers for use are to be obtained from the Power System Control Person,
For HV Isolation /Panels SAP No.: 1000798910 Series :
HT HT
Size:
31mm.
Type:
J3104
Description: Cylinder type, brass automatic locking with nickel plated hardened steel spring Description: Cylinder shackle to be master keyed to the existing BFFW / HT engraved locks, supplied with 2 keys. Locks and keys are to be engraved with serial numbers from LT2101 to LT2300. NOTE: Required serial numbers for use are to be obtained from the Power System Control Person,
For Substation and power station Gates and Doors with Tower Tow er Bolts SAP No.: 1090002027 Type:
HMKN
Series:
EB EB
Size:
50 mm.
Description : “Pin tumbler padlock,50mm,type: padlock,50mm,type : Cylinder brass automatic locking with Nickel plated hardened steel spring shackle to be master keyed to existing HMKN/EB locks, complete with 2 keys. Locks and Keys are to be engraved as “HMKN/ “HMKN/EB” EB” NOTE: Person,Required serial numbers for use are to be obtained from the Power System Control
For Substation and power station Doors SAP No.: 1090002029 Type:
HMKN
Series :
EB
Size:
25x25 mm.
Description: Barrel type Satin Chrome Rim Cylinder, 25x25mm, locks to be master keyed to existing HMKN/EB locks, complete with 2 keys. Lock and keys are to be engraved with serial nos. Note: Required serial numbers are to be obtained from the Control Person, Yibal Power station.
For HV switchyards and HV Isolators Page 18
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
SAP No.:1090002028 Type:
CCRK
Series :
OHL
Size:
50 mm.
Description: “Pin tumbler padlock, padlock , 50mm, brass automatic locking with Nickel plated hardened steel spring shackle to be master keyed to existing CCRK/OHL locks, complete with 2 keys. Lock and keys engraved with serial nos. Note: Required serial numbers are to be obtained from the Control Person, Yibal Power station
3.
4.
5.
Locking of Substations and Power Stations 3.1
STANDARD ELECTRICAL PADLOCKS/LOCKS level 2 (HMKN/EB) shall be fitted to the access doors or gates for all indoor and outdoor substations and those of power stations.
3.2
In those substations and power power stations where there are compounds or enclosures containing exposed LIVE HV conductors, the higher level-1 CCRK/OHL of STANDARD ELECTRICAL PADLOCK/LOCK shall be used to secure the gates leading to that compound or enclosure.
Locking of Switchgear 4.1
HV switchgear switchgear in in indoor indoor substations substations shall not normally have its lockable parts (i.e. racking handles, panel doors, control handles etc.) locked when in the service position, as only persons appointed under the ESR will have access to the switchgear.
4.2
If persons not appointed appointed under under the ESR are to have access to the HV switchgear, switchgear, then the SAEP shall decide if it is prudent to fit STANDARD ELECTRICAL PADLOCKS to the switchgear's lockable parts.
4.3
Emergency trip buttons or switches shall be left unlocked, unlocked, unless unless the AEP responsible for operation of the switchgear in that indoor substation requires them to be secured.
4.4
Each lockable part of HV switchgear switchgear in outdoor outdoor substations substations shall be locked with a STANDARD ELECTRICAL PADLOCK when in the service position.
4.5
Each mechanism of all manually operated HV disconnector disconnector or circuits breakers, mounted on poles or structures outside substations, etc., shall be locked with a STANDARD ELECTRICAL PADLOCK when in the service position.
Safety Padlocks 5.1
SAFETY PADLOCKS PADLOCKS shall be of a non non standard or unique unique type type and be supplied with only one key for each lock (i.e. no master key shall be supplied or be available). Each such lock shall be marked with a clearly readable individual number.
6.
5.2
SAFETY PADLOCKS shall be kept available for issue to SAEPs, AEPs, CESPs and CEPs for their use when carrying out SWITCHING, prior to work being carried out on either HV or LV APPARATUS.
5.3
These SAFETY PADLOCKS shall shall be used in accordance with the ESR, on points of ISOLATION for APPARATUS that is subject to an ELECTRICAL SAFETY DOCUMENT.
Provision of Key Safes 6.1
Page 19
KEY SAFES with union padlocks shall be provided provided at all power stations and and Area Offices.
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
KEY SAFES shall be provided at all substations unless they are within a convenient distance of KEY SAFES fitted in higher voltage substations (e.g. 132kV), power stations or Area Offices. 6.2
7.
Area Offices may also provide portable KEY SAFES which which may be taken and and used at remote sites (e.g., for use on HV motor circuits).
Design and Use of Key Safes 7.1
All KEY SAFES shall be used in accordance with with the ESR for the secure retention retention of all SAFETY PADLOCK keys used to lock means of ISOLATION, EARTHING or other safety devices.
7.2
KEY SAFES shall be fitted, or be capable of being fitted, with at least least two two unique unique locks locks with keys.
7.3
A unique lock shall be 'locked' and the key given given to a person issued with with an ELECTRICAL SAFETY DOCUMENT. A unique lock shall be 'locked' and a key retained by the SAEP or AEP issuing the SAFETY DOCUMENT. No KEY SAFE shall be capable of being opened, until all the keys to the unique locks securing it have been returned, to the SAEP or AEP who is to cancel the ELECTRICAL SAFETY DOCUMENT.
Page 20
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
8.
Vers ion 10.0 10.0 Effective:Oct-10
Issue of Keys 8.1
The level level of STANDARD ELECTRICAL PADLOCK/LOCK keys shall be issued to SAEPs, AEPs, CESPs and CEPs according to their duties.
8.2
Some APs may need to to be issued with the lower level of STANDARD ELECTRICAL PADLOCK/LOCK keys depending on the specific duties they have been appointed to carry out.
8.3
All persons issued with STANDARD ELECTRICAL PADLOCK/LOCK keys shall sign a key Receipt form. Such keys shall be returned when the recipient leaves the PDO Area or when his authorisation is withdrawn.
8.4
9.
The Area Operations Electrical Supervisor shall maintain a record of all such keys that he is responsible for issuing.
Securing of Safety Padlock Keys when Key Safes are not available 9.1
ESR Rule 5.3(b) requires that keys of SAFETY PADLOCKS used for locking locking points of ISOLATION shall be placed in a KEY SAFE or secured by another APPROVED security method. i.e., for long transmission lines the key for the far end can be placed in a far end key box and the box key retained by an AEP. If KEY SAFES are not readily available, or the work is to be only of short duration, either of the methods detailed in 9.2 and 9.3 are APPROVED for use.
9.2
The SAEP or AEP issuing an ELECTRICAL ELECTRICAL SAFETY DOCUMENT DOCUMENT shall retain on his person the SAFETY PADLOCK keys used to lock the points of ISOLATION, etc., for the APPARATUS to be worked on, until the ELECTRICAL SAFETY DOCUMENT is cleared and cancelled by the same SAEP or AEP.
9.3
The SAEP or AEP issuing issuing an ELECTRICAL SAFETY DOCUMENT shall apply two SAFETY PADLOCKS to each point of ISOLATION. One of the two SAFETY PADLOCK keys shall be issued to and retained by the recipient of the ELECTRICAL SAFETY DOCUMENT, the other shall be retained by the SAEP or AEP until the ELECTRICAL SAFETY DOCUMENT is cleared and cancelled by the same SAEP or AEP.
Page 21
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
6.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
ESOP – 3 ESOP 3 3 SELECTION, TRAINING, ASSESSMENT AND APPOINTMENT OF ELECTRICAL PERSONS (EPs) AND APPOINTED PERSONS (APs)
1.
General 1.1
This PROCEDURE is issued to provide guidelines for the selection, training, assessment and appointment of individuals who are to be appointed under the ESR as EPs or APs.
1.2
The method of applying to the CFDH-E for candidates to be appointed is detailed. Appendix A shows a specimen of the types types of CofA in use.
1.3
A periodic re-assessment of EPs and APs operational competence and discipline is called for on a three yearly basis.
1.4
A proper registration system shall shall be kept of all all matters pertaining pertaining to the training, assessment and appointment of persons.
1.5
Before applying applying for assessment for each level of authorization, the followings shall be ensured; a) An Electrical Engineer, authorised as as a CEP can move from CEP to AEP AEP within one year period period of experience as CEP and should have carried out a minimum of 10 switching program. program . b) Electrical technician should have at least 6 months period months period of experience as CEP for assessment to move to CESP c)
A CESP should have at least one year experience experience as CESP and should have carried out a minimum of 10 switching programme programme before he is qualified for assessment to move to AEP position
d) An AEP should should have worked a minimum one year as as AEP before applying for assessment for the level of SAEP. e) The candidate shall shall have attended the appropriate appropriate course for the level of authorisation he is applying for f)
Electrical authoris authorisation ation applications for contractors’ personnel shall be evaluated by the CFDH-E and CDFP-E maintenance. The required level of experience shall be dependent on the nature and the type of activity the contractors’ personnel is being appointed for. for.
2.
Selection of Electrical Persons and Appointe Appointed d Persons
2.1
General As stipulated in ESR, Rule 2.1.4, it is possible for non-PDO staff staf f to be appointed as EPs or APs, if so required for business reasons. Most often this is the case for contractor or vendor staff involved in the commissioning and/or maintenance of new facilities or equipment. The requirements to obtain authorisation for a specific category are defined in Sections 2.2 u/i 2.7, and shall be equally valid for PDO and non-PDO staff, except that in case of non-PDO staff, the CofA shall clearly state that the scope of authority is limited to commissioning and/or maintenance/contracted out system operation within prescribed boundaries (e.g., equipment of an EPC contractor's site). site). In case of the appointment of non-PDO staff, it is the vendor's or contractor's responsibility to provide a suitably electrically qualified candidate to undertake this role and to provide
Page 22
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
evidence to show that the candidate has sufficient operational experience to carry out the duties and responsibilities responsibilities commensurate with the level of appointment appointment sought. This shall include the ability to be able to understand and work to the ESR and any relevant ESOPs. Irrespective of a candidate's qualifications it is required that he follows the ESR courses and be assessed to the same degree as would apply for a PDO staff seeking a similar level of appointment.
2.2
Competent Electrical Person (CEP) A person being considered for training shall prove himself is able to acquire sufficient electrical technical knowledge and experience to avoid DANGER to himself and others when working on or near HV or LV electrical systems. An electrical engineering engineering background or qualification would be an advantage. advantage. Some knowledge of types of HV HV and LV APPARATUS would be useful. A person being considered for appointment shall demonstrate sufficient electrical technical knowledge and experience to avoid DANGER to himself and others when working on or near HV or LV electrical systems. A methodical approach when working to instructions or on his own initiative is a requirement, as it is difficult to instil good operational discipline into a person with a carefree approach to the potential dangers inherent in all electrical installations. Ability to be able to read and understand the intention of the ESR and the precautions it calls for is necessary.
2.3
Competent Electrical Switching Person (CESP) The person being considered for training and/or appointment shall as a minimum, satisfy the requirements specified in Section 1 & 2.2. The following shall be taken into account when selecting a person for this role:-
2.4
(a)
Ability to follow instructions for both LV SWIT SWITCHING CHING and work.
(b)
Ability to give clear verbal and written instructions to CEPs.
(c)
Be able to appreciate appreciate the the details details of the Sections of the ESR and and those those ESOPs affecting the LV SWITCHING and work he is to undertake.
Authorised Electrical Person (AEP) The person being considered for training and/or appointment shall, as a minimum, satisfy the requirements in Section 1 & 2.2 and should have acceptable qualification and formal training in electrical engineering practice. The following shall be taken into account when selecting a person for this role:(a)
Ability to follow instructions for both HV and LV SWIT SWITCHING CHING and work.
(b)
Ability to give clear verbal and written instructions to CEPs.
(c)
Be able to appreciate appreciate the the details details of the Sections of the ESR and and those those ESOPs affecting all the SWITCHING and work he is to undertake.
2.5
Senior Authorised Electrical Person (SAEP)
2.5.1
The person being considered for training or appointment shall, as a minimum meet the requirements of Section 1 & 2.4. He must have the required experience, electrical qualifications and knowledge of electrical systems to undertake all the duties and responsibilities of a SAEP, as detailed in both ESR and ESOPs. He shall be able to appreciate the electrical electrical system on which he is to operate, direct work to be carried out in a safe manner, and be able to make himself familiar with the APPARATUS it contains. Additionally Additionally,, he shall have a clear understanding under standing of the ESR and ESOPs so that he can train EPs having a lower or no electrical authority level.
Page 23
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
2.5.2
Electrical engineering personnel, with operational experience, arriving from another Operating Company or similar organisation, shall first be assessed and if found suitable, appointed as AEPs. When they have been made familiar with the ESR, ESR, the ESOPs and PDO operational practices, and have been given opportunities to discover the details of the electrical systems and HV and LV APPARATUS they are to operate, then is the time to consider them for SAEP status.
2.6
Control Person (CP) The person being considered for training or appointment shall, as a minimum, meet the requirements of Section 2.5. In addition the CP shall fully understand the electrical system within the defined boundaries for which he is to be appointed, and an appreciation of any other electrical systems that are connected to it across defined control boundary points. He will have to be able to absorb the details and characteristics of generation, transmission and distribution equipment in the specified electrical system, be capable of making decisions regarding suspect APPARATUS and associated protection settings and be able to give guidance where necessary to field operators.
2.7
Appointed Person (AP)
2.7.1
For use in certain situations, or at specific locations, there is the need of a person who can carry out tasks that would normally be done by EPs as a small part of their operational duties. [See ESR Section 10.0]
2.7.2
If a PDO production unit or facility needs selected members of their staff to carry out duties that requires them to be of AP status, then they shall approach the Area Operations Electrical Supervisor to check if they will agree to the such appointments for any of the following activities:(a)
Carry out a specific specific limited limited HV SWITCHING from a position remote from the circuit breaker, or limited LV SWIT SWITCHING. CHING. This SWITCHING shall be limited to the closing closing and opening of a circuit breaker or contractor controlling a generator, motor etc.
(b)
Enter substations under the control of an Area Operations Electrical Supervisor.
(c)
Carry out any any other specified activity that is normally normally carried out by Area Operations Electrical personnel.
2.7.3
It is essential that persons who who are selected to carry out these types of tasks receive receive sufficient training, and clear instructions in writing, so they are warned of any potential hazards that may arise when they are carrying out them out.
2.7.4
The role of the AP is generally defined in the ESR Rule 2.1.4.8
Page 24
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
3.
Training of Electrical Persons and Appointed Persons
3.1
General
3.1.1
If the selection process laid down in Section 2.0 is followed, the training required by all EPs and APs can follow f ollow a similar pattern depending only on the level of authorisation required.
3.1.2
A copy of the ESR shall shall be made available available to all candidates at least least four weeks weeks prior to assessment with a note setting out the Sections that apply to this particular authorisation. This so the personthe can make himself familiar with the intention and detail of the Sections of theisESR affecting operations and work he is to undertake.
3.1.3
A copy of the ESOPs shall be made available at least four weeks prior to assessment to candidates to be authorised. This is so the person can make himself familiar with the specific ESOPs that affect the operations or work he is to undertake.
3.1.4
All candidates shall attend and pass with a minimum mark of 70% the formal operational training course to become familiar with the ESR and any ESOPs relevant to their intended 'authorisation'. This course shall be attended attended prior to authorisation. authorisation. In addition addition candidates for level AEP and up shall attend and pass with a minimum mark of 70% the high voltage ESR familiarisation course.
3.2
Training for Electrical Persons
3.2.1
The main training need for EPs is for them to be made familiar with the APPARATUS and electrical systems on which they will will have to operate or work. This training can only be given on site by an experienced SAEP or AEP, as per the approved assessor list. It is not necessary for a candidate to be made familiar with every particular type of switchgear or transformer on the system, but his practical training should be sufficient that he will behave in a prudent manner when he has to operate or work on unfamiliar APPARATUS.
3.2.2
When candidates are being trained to operate on the HV or LV systems, they shall carry out operations whilst accompanied by an experienced SAEP or AEP. The CP shall be told that the candidate is carrying out HV SWITCHING under the direct supervision of an AEP who is to be responsible for his actions.
3.2.3
On-site training shall include, depending on the level of the authorisation required, the following: Correct operation of APPARATUS. Locking-off at points of ISOLATION with with SAFETY PADLOCKS or using some other APPROVED method. Use of KEY SAFES.
Attaching of NOTICES called for in the ESR. Use of voltage testing devices. Application of CMEs, AEs and LV EARTHS.
3.2.4
For AEPs the writing of SWITCHING PROGRAMMES and ELECTRICAL SAFETY DOCUMENTS shall be included in the training. Persons shall be instructed to print all details details and not to use normal handwriting. The responsibility of taking and checking all the necessary precautions before issuing an ELECTRICAL PERMIT-TO-WORK is very much more onerous than receiving such document. Persons in training shall, under supervision, be made to write the SWITCHING PROGRAMME, carry out all precautions including the SWITCHING operations, secure
Page 25
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
SAFETY PADLOCK keys, use voltage testing devices, apply CMEs and prepare and issue the ELECTRICAL SAFETY DOCUMENT. The person under training shall discuss the reasons for the items he has entered on his SWITCHING PROGRAMME with the 'supervisor', explaining the reasons why he is taking the precautions he has listed, prior to issuing the ELECTRICAL SAFETY DOCUMENT. An essential part of the training is that the person issuing the ELECTRICAL SAFETY DOCUMENT explains its purpose to the recipient and makes sure that he is aware of the work the document covers. This is a particularly particularly important aspect of a person's training, for when issuing such documents, some recipients of ELECTRICAL PERMITS-TO-WORK may not be familiar with the ESR and its requirements (e.g., contractors staff), while others may be very experienced PDO personnel and 'think' they know what is to be done! 3.2.5
The above paragraphs in Section 3.0 are not exhaustive but shall be used as a basic guide to the type of training necessary before assessing persons for appointment as EPs.
3.2.6
TRAINING FOR APPOINTED PERSONS The training of APs to carry out selected tasks shall be carried out under the supervision of the Area Operations Electrical Supervisor or his delegate. The person in charge of AP training shall have AEP status as a minimum requirement. The importance of specifying the limits of clearly defined activities that such APs shall be allowed to carry out is the prime object of training.
Page 26
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
4.
Assessment of Candidates for EP and AP Status
4.1
Competent Electrical Person (CEP)
4.1.1
To meet the general requirements of Section 2.1 the following procedure shall be adopted when assessing the candidate for appointment as a CEP.
4.1.2
Check knowledge of, and and familiarity, with the types of electrical APPARATUS he is to operate and/or work.
4.1.3
Check understanding of simple electrical terms and, if possible, circuitry.
4.1.4
Check knowledge and intention of the ESR, such as:is an ELECTRICAL PERMIT-TO-W PERMIT-TO-WORK ORK necessary? When is general terms, are taken to avoid avoid DANGER to the recipient of an What precautions, in general ELECTRICAL PERMIT-TO-WORK? What precautions are taken to avoid DANGER to a person working on LV APPARATUS?
4.1.5
Check knowledge in general terms of some of the following ESR Sections and specific Rules: Section 1.0:
All
Section 2.0:
All
Section 3.0:
3.1, 3.2, 3.4 and 3.5
Section 4.0:
Does he understand what he is allowed to do under the 'authorisation' he is being assessed to undertake?
Section 5.0:
5.1.1, 5.1.2, 5.1.3, 5.1.4, 5.4, 5.5.3 and 5.6
Section 6.0:
Paragraphs on ELECTRICAL ISOLATION / DE-ISOLATION CERTIFICATES and those affecting the recipient of ELECTRICAL PERMITS-TO-WORK and LIMITATIONS-OF-ACCESS.
Section 7.0:
7.1.2, 7.1.3, 7.1.4, 7.1.6.2, 7.1.7.3, 7.2.2 and 7.8.
The assessment shall include a written test and a subsequent interview with a discussion on the results of the written test to assess the candidate’s candidate ’s knowledge of the ESR sections involved. 4.1.6
As the authorisation includes the SWITCHING and work on LV APPARATUS, a simple programme of SWITCHING shall be drawn up to include the operation of LV switchgear units, withdrawal of fuses, use of SAFETY PADLOCKS and attaching of CAUTION and DANGER NOTICES. The candidate shall be instructed to carry out this simple SWITCHING and then explain to the person who is to carry out the work what precautions he must observe when working. Check he is SWITCHING and operating in accordance with ESOP 8.
4.1.7
It is doubtful if the candidate will be word perfect on some of these assessment exercises, but his attitude and general approach are more important to look for rather than a 'parrot' type recitation of Rules and Procedures. Note: Note:
4.2
Regarding the ESOPs, the CEP candidate needs only to be assessed against ESOP 5, 8, 23, 23S1 and 24.
Competent Electrical Switching Person (CESP) The samesystems, assessment 4.1, but shall as he be should a greater experience on the LV electrical the as candidate givenhave a more complex LV SWITCHING
Page 27
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
programme to carry out, including operations on switchboards switchboards with back feeds. Check that his knowledge of the relevant Sections of the ESR is adequate.
4.3
Authorised Electrical Person (AEP)
4.3.1
To meet the requirements of paragraph 2.4, the following procedure shall be adopted when assessing the candidate for appointment as an AEP.
4.3.2
Check his his knowledge knowledge of types types of HV HV and LV APPARATUS on which he is to operate and issue ELECTRICAL SAFETY DOCUMENTS.
4.3.3
Depending on the authorisation for which he is being assessed, check that he is familiar with both the intention and the detail of the ESR. The candidate shall be checked on the ESR regarding the issue and cancellation of ELECTRICAL SAFETY DOCUMENTS, excluding only SANCTIONS-FOR-TEST, by a written test and subsequent interview to discuss the results of the written test.
4.3.4
He shall be required to prepare a SWIT SWITCHING CHING PROGRAMME which includes the issue of an ELECTRICAL SAFETY DOCUMENT.
4.3.5
The candidate shall then carry out the SWITCHING PROGRAMME PROGRAMME on the circuit chosen, including the opening and making DEAD, ISOLATING, locking off with SAFETY PADLOCKS, testing with with a voltage testing device and application of CMEs. He should attach the appropriate CAUTION, DANGER and and EARTHED NOTICES. Check he is operating in accordance with ESOP 8.
4.3.6
He shall be familiar with requirement of ELECTRICAL PERMITS-TO-W PERMITS-TO-WORK ORK and shall issue and explain the document to the recipient. The ELECTRICAL PERMIT-TO-WORK shall be cleared by the recipient and cancelled by the candidate and the circuit be restored to service.
4.3.7
Candidates shall be asked to explain the conditions under which SANCTIONS-FOR-TEST are issued and received.
4.3.8
The candidate's methodical approach to operations and work is an important measure of his operational discipline for which he is being assessed.
4.4
Senior Authorised Person (SAEP)
4.4.1
To meet the requirements of Section 2.5, the following procedure shall be adopted when a candidate is assessed for appointment as a SAEP.
4.4.2
The candidate shall already have the experience level of an AEP as per section 4.3.
4.4.3
The issue and cancellation of a SANCTION-FOR-TEST shall be included.
4.4.4
The most important part of this assessment is to gauge the candidate's attitude to operational situations, and his approach to operating and working safely on both HV and LV electrical systems. An experienced operational engineer engineer shall operate and behave in a manner that he expects his AEPs and CEPs to follow, and his calm and studied approach to plant failures, emergencies and loss of supply situations is most important. The assessment shall include a written test and subsequent interview to review the results of the written test.
4.5
Control Person (CP)
4.5.1
An appointed Control Person (CP) must have been assessed and appointed on SAEP authorisation level. His skills on SAEP level must have been demonstrated over a reasonable period of time, also depending on his time in the job. CP candidate profile:
Page 28
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
- For operational areas and the coastal utilities area he is the most senior electrical supervisor. - For a utilities area the CP will will be nominated for assessment and appointment by the Head of Utility. 4.5.2
It is is not necessary that the the CP should be familiar with with the specific operation of all all APPARATUS on the system for which he is to be responsible, but he should have a good appreciation of its capabilities and technical limitations. All nominated Control Persons must be interviewed by the CFDH-E as part of the assessment procedure.
4.5.3
All operational and utilities areas with permanent electrical installations must have a CP in the area at all times.
4.6
Appointed Person (AP)
4.6.1
Any application from a PDO production unit or facility f acility for a candidate to become an AP shall, following the necessary training, be sent to the Area Operations Electrical Supervisor.
4.6.2
The Area Operations Electrical Supervisor shall ensure that he is satisfied with the person's training and check that he is competent to carry out the specified activities detailed on the application form. In particular, it is important that such candidates are aware of the limits of the operational duties they may be allowed to undertake on the electrical systems.
4.6.3
If the candidate is to be required to carry out limited SWIT SWITCHING CHING duties, the Area Operations Electrical Supervisor shall produce a written procedure detailing the agreed items of SWITCHING and procedures he will will carry out. This procedure shall be submitted to the appropriate Head of Utility for approval before applying for the candidate's appointment.
5.
Appointmentt of Electrical Persons and Appointed Persons Appointmen
5.1
The assessment for appointment to EP or AP status shall be carried out by a selected SAEP, nominated by the Head of Utility. Utility. In addition the CFDH-E shall interview all all candidates assessed for AEP, SAEP and CP status.
5.2
All appointments of AEP level and above shall be approved by the CFDH-E, CofA below AEP level can be approved by the nominated assessing SAEP.
5.3
For appointments of AEP level and above only after a successful assessment, shall the Head of Utility arrange to forward a completed CofA to the CFDH-E for his final approval and signature. The CFDH-E shall return the CofA to the Head of Utility, Utility, who shall ensure that the relevant person receives the CofA.
5.4
Specimen CofA are shown in Appendix A of this ESOP.
5.5
The CofA shall be returned to the appropriate Head of Utility when the person leaves or has his authorisation withdrawn for any reason.
5.6
The area/ region of validity shall be clearly marked on the CofA.
6.
Periodic Re-Assessment of Electrical Persons and Appointe Appointed d Persons
6.1
The validity of the certification period is a maximum of three years. years. Well before the expiry date the appropriate Head of Utility, or a person nominated by him, shall carry out a reassessment of the person concerned. This re-assessment is to check the operational competence and discipline of such persons and to ensure that they can perform their functions safely and efficiently.
6.2
The Head of Utility or his nominee shall attend a site where the EP or AP is carrying out SWITCHING, or operational duties, and implement random checks, as detailed in Sections 6.3, 6.4 and 6.5.
Page 29
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
6.3
If a SWIT SWITCHING CHING PROGRAMME is being used, it shall be checked for accuracy and legibility.. Times of the operation legibility operation of individual individual items of SWITCHING shall have been recorded.
6.4
If SWIT SWITCHING CHING is in progress, items that can be checked are:SWITCHING CHING PROGRAMME entries? Correct log book or SWIT points of ISOLATION? SAFETY LOCKS correctly applied at points Have CMEs been correctly applied, and if consisting of portable EARTHING leads, labelled 'CME'?
6.5
If a SAFETY DOCUMENT has been issued, items that can be checked are:copy legible and 'printed'? Is the document and its copy Does the recipient understand the work he is to undertake? Is the information, e.g., CMEs, accurate? Have any AEs been issued, and recorded, on the ELECTRICAL ELECTRICAL SAFETY DOCUMENT? Is the CP's name recorded? Are both Issue and and Receipt Receipt sections properly signed?
6.6
If the Head of Utility or his nominee is satisfied with the results of the re-assessment, then a new CofA shall be issued for the next three years, duly approved by the assessing SAEP (for levels up to including AEP) or the CFDH-E. The old CofA shall be destroyed.
7.
Recording of Training, Assessment and Registration of Appointments
7.1
General Each Head of Utility shall maintain an up-to-date up-to-date recording and registration system for all EPs and APs assessed.
7.2
Recording of Training & Asses Assessment sment The record system shall include in an auditable format:individual's attendance attendance at PDO Operational Training Courses; run to Full details of an individual's make persons familiar with the ESR and ESOPs. Full of anprocedures. individual's practical training, received in a PDO Area in SWITCHING individual's and details operational Results of the assessment.
7.3
Registration of Appointments The register of appointments shall include in an auditable format the following details of the persons appointed under the ESR: Name of the person (surname & first name) Reference indicator (for PDO staff only) Company number (PDO staff) or employing Contractor's name ESR Number (see NOTE 1) Region/Area Authorisation level
Page 30
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
Date of appointment Dates of LV/HV courses followed Focal point Acknowledgment of ESR received Issue & expiry data of certificate Re-assessment date Remarks
Note: Note:
1. The ESR number is a unique number. Care shall be taken to avoid duplication, i.e. by assigning blocks of numbers to each Head of Utility. 2. In case of cancellation of the certificate (disciplinary (disciplinary measure, resignation), the person's record shall be deleted from the register, and the certificate shall be destroyed. 3. In case of transfer of a person, the person's details details shall transfer with with him. 4. The registration shall preferably be kept in a database or spreadsheet format. format.
Page 31
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
APPENDIX- A A - CERTIFICATES OF APPOINTMENT APPOINTMENT
CERTIFICATE FOR AUTHORISED STAFF To be used for SAEP, AEP, CESP, CEP, CP and EP FRONT OF CERTIFICA CERTIFICATE TE
Page 32
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
7.
ESOP – 4 ESOP 4 4
1.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
PREPARATION AND USE OF SWITCHING PROGRAMMES FOR HIGH VOLTAGE SYSTEMS
Introduction 1.1
The ESR call for a SWIT SWITCHING CHING PROGRAMME to be written and APPROVED for all all HV SWITCHING carried out, unless it is confined to HV motor circuits and has the prior agreement of the CP. [see ESR Rule Rule 5.2.1.2]
1.2
This PROCEDURE PROCEDURE briefly details the manner in in which such SWITCHING PROGRAMMES shall be prepared, checked and implemented.
1.3
Appendix A of A of this PROCEDURE contains:Standard terms that shall be used when writing such PROGRAMMES. Appendix B of B of this PROCEDURE contains:A specimen SWITCHING PROGRAMME form. Appendix C of C of this PROCEDURE contains:Abbreviations for standard terms and equipment discussed in Appendix A.
2.
Objective
2.1
To produce SWITCHING PROGRAMMES that shall act as a check list and record all the operations required to safely carry out a particular purpose on the system.
2.2
To achieve uniformity in PDO and prevent misunderstandings, standard terms for items of APPARATUS and instructions for SWITCHING operations shall be used.
3.
Preparation of Switching Programmes
3.1
A numbered SWITCHING PROGRAMME together with a clear copy shall be prepared by a SAEP or AEP stating the objective of the SWITCHING and detailing all items necessary such as opening and closing of circuit breakers, ISOLATION, application of CMEs, application of SAFETY PADLOCKS and CAUTION NOTICES, etc. It shall be specifically stated where each SAFETY PADLOCK is to be applied. In case a WORK PERMIT has been issued, it shall cross reference to the associated SWITCHING PROGRAMME.
3.2
The SWITCHING PROGRAMME and copy shall be:
Signed by the EP in charge of the SWIT SWITCHING CHING Checked for correctness and signed by another EP on at least AEP level
Finally approved and signed by the CP
- all in accordance with the electrical boundary procedure.
4.
Implementation of Switching Programmes
4.1
The AEP holding the APPROVED SWITCHING PROGRAMME shall before commencing any item of SWITCHING first check with the CP that the system is in the state assumed by the PROGRAMME, i.e., no outages or open points have been altered that would affect the security or safety of the system if the SWITCHING PROGRAMME is commenced. A copy of the SWITCHING PROGRAMME shall be held by the CP.
4.2
Agreement to proceed shall be given by the CP to undertake SWIT SWITCHING CHING items in order through to completion, he requires confirmation of certain SWITCHING before another batch of items is unless commenced.
Page 33
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
The time of each item of SWITCHING completed shall be recorded by the person performing the operations on his SWITCHING PROGRAMME. 4.3
At the completion of the SWIT SWITCHING CHING PROGRAMME the completed form shall be signed and returned to the CP.
5.
Emergency Switching Programmes
5.1
If an unplanned outage or system emergency occurs, the AEP or AEPs may agree with the CP a SWITCHING PROGRAMME over telephone or radio, each person writing his own copy. The CP shall check over telephone or radio that all PERSONS have recorded the same items of SWITCHING on their copies of the SWITCHING PROGRAMMES before giving permission to precede with the SWITCHING.
6.
Emergency Switching Without Switching Programmes
6.1
If in the view of the CP it is not practicable or desirable to produce an emergency SWITCHING PROGRAMME as detailed in Section 5.1, then the following procedure shall be adopted.
6.2
The CP shall discuss and agree the remedial SWIT SWITCHING CHING necessary with the AEP. The CP shall then instruct the SWITCHING, item by item.
Page 34
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
APPENDIX - A A - DEFINITIONS OF STANDARD TERMS FOR SWITCHING OPERATIONS The following terms shall be used to describe operational APPARATUS. Refer to Appendix C for a list of abbreviations for equipment types.
1.0
GROUND MOUNTED EQUIPMENT
Circuit-Breaker
A device suitable for making or breaking faultmay current in accordance with its agreed rating. Such circuit breakers be fitted with autoautoreclose facilities.
Oil Switch
This is a switch in accordance with IEC 60265. It is a fault making switch and can be used to interrupt full load current.
Oil Isolator
This is a switch not in accordance with IEC 60265. It is NOT fault making. Nor does it have have load making or breaking rating.
Oil Switch Fuse
An automatic device incorporating HV fuses normally used for control of transformers up to 1,000 kVA at 11 kV.
Disconnector
An indoor air break isolator either pole operated or ganged. Neither type has a fault/load making or breaking rating.
Selector
An indoor ganged type air break isolator with no fault/load making or breaking rating.
EARTH Switch
A specially provided switch to enable an EARTH connection to be made.
2.0
OVERHEAD EQUIPMENT
Auto-Recloser
An automatic reclosing circuit breaker. These may be electrically or mechanically operated and their sequences can be programmed.
Auto-
An automatic load breaking fault making switch which normally operates in dead time used in conjunction with an auto-recloser.
Sectionaliser Air Break Disconnector
An air break ganged isolator which may be fitted with arcing arc ing horns or interrupter heads.
Local Fuses
HV fuses controlling a single transformer.
Spur Fuses
HV fuses controlling more than one transformer.
EARTH Switch
A specially provided switch to enable an EARTH connection to be made.
Fault Throwing Switch
An automatic device forming part of circuit protection to apply either EARTH or phase faults to a circuit.
Page 35
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
3.0
SAFETY EQUIPMENT EQUIPMENT
3.1
SAFETY PADLOCKS, CAUTION NOTICES, DANGER NOTICES, EARTHED NOTICES, CIRCUIT MAIN EARTHS and ADDITIONAL EARTHS are defined in the ESR .
3.2
Busbar Shutters and Feeder Shutters.
4.0
STANDARD TERMS TERMS
4.1
Where the CP is required to carry out an operation by remote control (SCADA) the suffix 'CP' is to be included in the operator column of the SWITCHING PROGRAMME.
4.2
A combination of terms is permissible to complete an operation e.g. 'Rack out (...) oil switch, SAFETY PADLOCK feeDer and busBar shutters, apply CAUTION and DANGER NOTICES'. This can be taken as one item on a SWITCHING PROGRAMME, but separate items must always be used for SWITCHING, ISOLATING and EARTHING operations and the application of SAFETY PADLOCKS.
4.3
Abbreviation of terms is also permissible when writing out SWIT SWITCHING CHING PROGRAMMES, using the abbreviations as listed in appendix C. C. For example, 'Open (...) oil switch, SAFETY PADLOCK (busbar and feeder shutters) and apply CAUTION NOTICE' may be written as follows: 'Open (.....) OS - SP (BBS & FDS) & CN'
Page 36
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
APPENDIX -B - SWITCHING PROGRAMME FORM
AREA
: _________ START DATE
: ___________ PROG.NO.
: _______
VOLTAGE
: _________ TIME
: ___________ SHEET NO
: _______
LOCATION
: _________ EST.COMP.DATE
: ___________ No. of SHEETS : _______
PURPOSE
: _________ TIME
: ___________ REFERENCE
ACTION PARTY
NAME
SIGNATURE
: _______
STATUS
EP IN CHARGE:
SAEP/AEP
CHECKED BY:
SAEP/AEP
PERMISSION TO PROCEED BY:
RETURN BY
ITEM
Page 37
: _____________
SUBSTATION
CP
WHEN COMPLETE: __________ COMPLETE: __________
CIRCUIT or UNIT
OPERATION
OPER
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
TIME
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
APPENDIX-C - ABBREVIATIONS ABBREVIATIONS FOR ELECTRICAL EQUIPMENT The following abbreviations may be used when preparing a switching programme. The list is not exhaustive. Other abbreviations may be used, provided clear understanding exists what these abbreviations mean! ELECTRICAL EQUIPMENT & SAFETY EQUIPMENT EQUIPMENT Circuit-breaker
CB
Safety Padlocks
SP
Switch
S
Caution Notices
CN
ISOLator
ISOL
Danger Notices
DN
Switch-Fuse
SF
Earthed Notices
EN
DISConnector
DISC
BusBar Shutters
BBS
Earth Switch
ES
FeeDer Shutters
FDS
Fault Throwing Switch
FTS
Circuit Main Earth
CME
Additional Earth
AE
SWITCHGEAR INTERRUPTING MEDIUM
Note: Note:
Vacuum
V
Air
A
Oil
O
SF6
SF6
Switchgear interrupting medium to be used in combination with switching element. e.g., VCB is a Vacuum Circuit Breaker
Page 38
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
ESOP – 5
8.
ESOP 5 5 VOLTAGE TESTING AND PHASING-OUT DEVICES 1.
General
1.1
This PROCEDURE lists the APPROVED voltage testing and phasing out devices that are to be used on PDO electrical HV and LV systems to meet the requirements of the ESR.
1.2
Also included are methods detailing the manner in which the devices should be used and maintained.
2.
Approved Devices The list shown in Appendix- A of this ESOP is the devices that have been APPROVED by the CFDH-E for use in PDO. This list may be added to when further APPROVALS of the devices are made.
3.
Use of Devices
3.1
No person shall use a voltage testing or phasing out device until he has been adequately trained in its use.
3.2
Before use, the operator shall check the device is APPROVED for the purpose and system voltage he is testing. testing. Additionally Additionally,, the device should be examined for visible defects and and withdrawn from service if any are found.
3.3
The insulation of the device shall be wiped with a dry cloth before and after use.
3.4
The device shall be tested for correct indication before and after use. A proving unit is the recommended method of testing the device, but if one is not available a LIVE conductor may be used.
3.5
Operators shall hold the device by the handle provided and shall not touch any other part of the device when it is being used.
3.6
If the design of the switchgear allows easy access for a HV testing device, then it is good operational practice to test prior to applying a CME via a circuit breaker (i.e., feeder spouts on horizontal and vertical isolatable units).
4. 4.1
Method of Testing
In all situations each phase or conductor shall be tested in succession. 4.2 Most APPROVED devices are not designed for use on unearthed systems. If there is a DANGER of the ISOLATED HV APPARATUS being made LIVE by inversion from a LV source, then to ensure that misleading indications are not obtained when using these devices, the following practice shall be followed. Test all three phases, and then apply an APPROVED EARTH to one phase and then test the other two phases. This will ensure that there is an earthed reference for the device. device.
5.
Storage and Inspection
5.1
Voltage testing devices shall be stored in a secure, warm and dry atmosphere. (e.g. substations, switch rooms, electrical workshops or offices).
5.2
Page 39
Care should be taken when transporting devices to site. A carrying case shall be used to protect the instrument.
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
6.
Inspection and Maintenance
6.1
In addition to the inspection requirements as specified in clauses 3.2, 3.3 and 3.4 of this ESOP, the following shall be carried out.
6.2
All HV testing devices and phasing out devices shall at least be inspected and tested at quarterly intervals. intervals. Associated hot sticks shall be pressure tested annually, to verify the insulation integrity.
6.3
A number shall be used to identify each device and a record of its inspection/testing shall be maintained at the PDO Area where the device is in use. The most recent inspection date shall be clearly indicated on each device.
Page 40
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
APPENDIX A A - APPROVED APPROVED VOLTAGE TESTING AND AND PHASING OUT DEVICES NAME & TYPE OF SERVICE HV DETECTOR TYPE KP TEST III REF. KPT 3.5 BY K. PFISTERER GERMANY FROM ROTEL ELECTRICAL UK LIVE LINE TESTER & ACCESSORIES FOR USE UP TO: MODEL 257a EDGCOMBE INSTRUMENTS UK AGENT: AL-MAAMARY HV DETECTOR TYPE KP TEST IIE BY K. PFISTERER GERMANY FROM ROTEL ELECTRICAL UK HV DETECTOR TYPE 1990/ST BY CHANCE USA. See note 2 CATU HV Detector type: CC245-66/132kV
VOLT RANGE 132 kV
COMMENTS & USE Overhead line and exposed conductors Metal clad switchgear
33 kV
11 kV
1-100 kV & 100-800 kV 66 – 66 – 132kV 132kV
Overhead conductorsline and exposed phasing and potential For phasing detection Metal clad switchgear
Overhead line and exposed conductors
SOFAMEL HV Detectors MULTIMETERS: BECKMANN HD 110 FLUKE AVO
Note:
415 V
Use with stick CM-4000 series. Refer to CATU catalogue for details Refer to Sofamel catalogue
Metal clad switchgear and conductors Note: AVO shall only be used with fused leads
1. Additionally, devices supplied by the equipment manufacturer for that equipment can also be used, provided they have been APPROVED by CFDH –E (Electrical). e.g., COQ, SIEMENS, HOLEC, etc. 2. There are two types on the market, a type with one 9 V battery and a type with two 1½ V 2. batteries. Only the type type with 9 V bat batteries teries s hal halll be us ed.
Page 41
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
9.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
ESOP – 6 ESOP 6 6
EARTHING EQUIPMENT FOR USE ON HIGH VOLTAGE APPARATUS
1.
General
1.1
The ESR requires that the DEAD conductors of HV APPARATUS shall be effectively EARTHED before an ELECTRICAL SAFETY DOCUMENT can be issued to allow work or testing.
1.2
ESR Rule 2.7.1 calls for such EARTHING to be applied either through switchgear with adequately rated EARTHING capacity, by APPROVED portable EARTHING leads or APPROVED devices. ESR Rule 5.5 details how these different EARTHING methods shall be applied on the PDO electrical systems.
1.3
This PROCEDURE specifies the APPROVED equipment that shall be used to carry out such EARTHING operations on PDO HV APPARATUS.
2.
Switchgear with Adequately Rated Earthing Capacity
2.1
EARTHING SWITCHES SWITCHES EARTHING switches installed on PDO HV electrical systems shall be capable of carrying the full rated short circuit earth current that could occur if closed onto a LIVE circuit in error.
2.2
CIRCUIT BREAKER WITH EARTHING FACILITIES FACILITIES Circuit breakers, and their associated EARTHING equipment installed on the PDO HV electrical systems, shall be capable of carrying the full rated short circuit fault current that could occur, if a circuit breaker being used to EARTH APPARATUS, was closed onto a LIVE circuit in error .
2.3
INADEQUATELY RATED EARTHING SWITCHE SWITCHES S BREAKERS WITH EARTHING FACILITIES FACILITIES
OR
CIRCUIT
Any installed EARTHING switch or circuit breaker EARTHING equipment not meeting the requirements of Sections 2.1 or 2.2, shall be clearly identified with a warning label at their operating position. This warning label is a necessary precaution to ensure that AEPs are aware of the technical limitations when using such APPARATUS to apply EARTHS to a circuit, and requires them to take additional precautions, (e.g., first using an APPROVED voltage testing device) or to use alternative methods of EARTHING the circuit .
3.
Approved Approv ed Portable Earthing Leads for Use as Circuit Main Earths
3.1
The portable EARTHING leads, that are to be used as CMEs, shall be of such a size and design, so as to be capable in use of carrying the full rated short circuit earth current if a LIVE circuit, was in error, closed onto them at the position where they had been applied.
3.2
The choice choice of of the cross sectional sectional size of such leads will depend on the short circuit levels of the PDO electrical system system on which they are to be used. For safety and standardisation reasons, the minimum cross-sectional area of the EARTHING leads shall be 70 mm 2. This is adequate for all HV and LV systems. Each phase shall have its individual lead to EARTH, it is not not allowed allowed to use so-called trident leads. The EARTHING leads shall be INSULATED. Appendix B gives details.
Page 42
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
3.3
The choice of fittings fittings for line, line, earth earth end clamps and the length of the leads will depend on the APPARATUS on which the portable EARTHING leads are are to be applied.
3.4
Leads for use in substations with exposed HV conductors shall be of a length suitable to reach from the DEAD conductors to the nearest substation EARTH bar. bar. The line and earth end end clamps shall be of a design suitable to enable an effective connection to be made at both ends.
3.5
Leads for use on wood pole overhead lines conductors, shall shall be of a design suitable for applying a line end clamp to each conductor and have sufficient length and size to connect to EARTHING rods which can be driven into the ground.
3.6
If portable EARTHING leads are required as CMEs on steel tower overhead lines, then those specified for use in substations with exposed HV conductors can be used providing that the line end clamps are suitable for applying to the overhead conductors and the earth end clamps are suitable for connecting to the steelwork of the tower.
3.7
When portable EARTHING leads are applied in position as CMEs they shall have an APPROVED label attached with with the letters C.M.E. Appendix A gives details. details.
4. 4.1
Approved Approv ed Portable Earthing Leads for Use as Additional Earths An overhead line circuit which has been DEAD, ISOLATED and EARTHED at each end, can have dangerously high voltages induced onto its conductors from adjacent LIVE overhead lines or from the adjacent circuit on a double circuit overhead line or by natural phenomena. The effects of this induced voltage can be completely removed when AEs are correctly fitted at, or near, the point of work on the conductors. If a break is to be made in the conductors of an overhead line circuit, then AEs shall first be applied, as a dangerously high voltage can occur across the break.
4.2
The portable portable EARTHING leads, that are to be used as AEs, shall be of such a size and design so as to be capable in use of preventing an induced voltage, at the point of work, on an already EARTHED conductor. It is permitted to use as AEs the same type of portable EARTHING leads, as specified for CMEs. [see Section 3.1]
4.3
5.
When portable EARTHING leads are applied in position as AEs, they shall have an APPROVED label attached with with the letters A.E. APPENDIX A gives details.
Identification of Portable Earthing Leads
5.1
Each set of portable EARTHING leads issued in PDO shall have an unique number permanently attached so that they can be readily identified in position as CMEs or AEs.
5.2
This unique number is also applied to assist in ensuring that portable EARTHING leads are readily identified both before use and when maintenance inspections of such equipment is carried out and properly recorded.
6.
Maintenance of Portable Earthing Leads
6.1
All portable portable EARTHING leads shall shall be examined immediately prior to use to ensure they are in good conditions. [see ESR Rule 5.5.2.1 (b) (iii)]
6.2
At three monthly intervals all portable EARTHING leads shall be maintained in accordance with the relevant SAP maintenance routines.
7. 7.1
Page 43
Operating Rods for Apply Applying ing Portable Earthing Leads The insulated insulated operating operating rods used for applying portable EARTHING leads leads shall be of the glass glass fibre hollow tube type. type. The operating rods shall be made in sections sections that can be assembled to provide a 2.4 m operating length.
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
7.2
The operating rods shall be examined immediately prior prior to use to ensure they are in good condition.
7.3
At three monthly intervals intervals all all such operating rods shall be maintained in accordance with with the relevant SAP maintenance routines .
8.
Application of Portable Earthing Leads
8.1
ESR Rule 5.5.2.1 (b) (iii) gives the procedures for applying APPROVED portable EARTHING
8.2
leads. ESOP 5 gives guidance on using APPROVED voltage testing devices when applying APPROVED portable EARTHING leads.
Page 44
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
APPENDIX A A - APPROVED APPROVED LABELS FOR CIRCUIT MAIN EARTH, ADDITIONAL ADDITIONAL EARTH AND AND EARTHED NOTICE See PDO Electrical Standard Drawings :
STD 4 0004 01 STD 4 0005 01 and STD 4 0003 01
APPENDIX B - APPROVED APPROVED PORTABLE EARTHING LEADS Portable EARTHING leads and relevant accessories as manufactured by Pfisterer have been APPROVED for use in PDO, but note the following with regards to EARTHING leads:
Only the single pole version is APPROVED (Pfisterer catalogue page 63/14)
The three pole version (Pfisterer catalogue page 63/23) is not APPROVED
Portable EARTHING leads and relevant accessories of other manufacturers shall not not be used unless they have been APPROVED by the CFDH-E (ELECTRICAL).
Page 45
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
10.
ESOP – 7 ESOP 7
1.
Vers ion 10.0 10.0 Effective:Oct-10
NOTICE OF COMMISSION COMMISSIONING ING OF HIGH VOLTAGE APPARATUS
General The PROCEDURE is issued to detail the method for sending a Notice of Commissioning form to all involved parties prior to the making of the first electrical connection between new APPARATUS and the existing PDO HV system system.
2.
Initial Construction Phase During the initial stage of construction of new substations when no electrical connection exists between the new APPARATUS and the existing HV system, work can be done outside the provisions of the ESR. Work during this phase is carried out solely under the PDO HSE Regulations.
3. 3.1
3.2
4.
Final Construction Phase It is at the commissioning stage that a potentially dangerous situation can arise. As soon as the first connection is made between the new APPARATUS and PDO's HV system (or even LV if a transformer is connected to a LV switchboard) what has been up to that time a construction site or enclosure, becomes an operational substation and shall come within the scope of the ESR. If an HV circuit connected to a LIVE existing substation is terminated onto a disconnector or into a circuit breaker cable box in a substation under construction, it shall be considered as a potential DANGER to persons performing construction work and ELECTRICAL SAFETY DOCUMENTS shall safely limit their access and work.
Scope of ESR
4.1
From the time, that the first connection is about to be made, it is essential that standard PDO un-climbable fences and gates are erected and complete com plete for outdoor type substations and that doors in the case of indoor substations are ready for locking with STANDARD ELECTRICAL LOCKS or PADLOCKS. The ESR shall then be applied applied and an SAEP shall ensure that all its provisions can be met.
4.2
Work in in that substation shall now be under an ELECTRICAL PERMIT-TO-W ORK, SANCTION FOR TEST or LIMITATION-OF-ACCESS (i.e. an ELECTRICAL SAFETY DOCUMENT). It is important at this time to remember that building and civil engineering contractor’s staffs are not as conversant with electrical safety requirements as PDO electrical personnel and electrical contractors, so clear instructions, to ensure the use, movement and storage of their equipment, materials and especially ladders and scaffolding, shall be given to comply with the ESR.
5. 5.1
Notice of Commissioning Procedure Before any electrical connection is made between newly constructed APPARATUS and the PDO HV system, a Notice of Commissioning form shall be issued to all parties by the PDO Project Engineer responsible for the construction work. These forms shall be sent to all contractors, manufacturers, consultants and other PDO Departments who have been involved in the on site construction of the substation and associated overhead lines and cables terminating in it.
Page 46
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
5.2
The first electrical connection shall not be made until until the receipt of the Notice of Commissioning form has been acknowledged by all parties, and such connection shall not be made prior to the date indicated on the form.
5.3
The PDO Project Engineer shall be responsible for confirming in writing to the SAEP, who is to supervise or witness the electrical commissioning of the substation that all parties have been informed and have returned the receipt part of the Notice of Commissioning form.
5.4
The SAEP shall inform the CP that this PROCEDURE has been completed before commencing the issue of ELECTRICAL PERMIT-TO-WORK, SANCTION-FOR-TEST or LIMITATION-OF-ACCESS for the APPARATUS or associated work.
6.
Notice of Commissioning Forms
6.1
A specimen Notice of Commissioning form is shown as an Appendix to this ESOP.
6.2
The forms shall be numbered in sequence and each one sent to a contractor, etc., shall be individually numbered.
Page 47
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
APPENDIX- A A
NOTICE OF COMMISSIONING OF HIGH VOLTAGE APPARATUS NUMBER:
ISSUING LOCATION:
ISSUED TO: __________________________________ ________________________________________________________________ ______________________________ LOCATION/ROUTE: _________________________________________________________ ____________________________________________________________________ _______________________________ ___________________________________________ ______ CONTRACT/JOB NO: _______________________________ ________________________________________________________ _________________________ WITH WIT H EFFECT FROM: TIME: __________ HRS
DATE: ____________
I hereby give notice that the section of the works described below at the above Location/Route is being made LIVE or by reasons of its proximity or relation to other APPARATUS must be regarded as being LIVE and from the time and date stated above will come under the jurisdiction of the PDO ELECTRICAL SAFETY RULES. From that time no further work shall be done on or near this section of works unless the person in charge of such work is in possession of an ELECTRICAL PERMIT-TOWORK, SANCTION-FOR-TEST, OR LIMITATION-OF-ACCESS issued in accordance with the PDO ELECTRICAL SAFETY RULES (PR-1947). DESCRIPTION OF SECTION OF WORKS:
_____________________________________________________________ ____________________________________________________________ _ _____________________________________________________________ ____________________________________________________________ _ ____________________________________________________________________ _______________________________ ___________________________________________ ______ The SENIOR AUTHORISED ELECTRICAL PERSON responsible, who can explain the requirements, is: ________________________________________________________________________ who may be contacted on site or at: _________________________________ ______________________________________________ _____________ ____________________________________________________________________ _______________________________ ___________________________________________ ______ DATE: ______________ SIGNED: ______________________________ __________________________________________________________________ _____________________________________ _ DESIGNATION: PDO PROJECT ENGINEER
To be issued in accordance with ESOP 7. ACKNOWLEDGEMENT OF CONTRACTOR I acknowledge receipt of this Notice and confirm that all staff in my charge including subcontractors have been warned and understand that this procedure is to ensure safe working conditions. TIME: ______________DATE: ______________ NAME: __________________
SIGNED: ______________
BEING A REPRESENTATIVE OF: _________________________________ ______________________________________________ _____________ ADDRESS: _______________________________________________________________________
Page 48
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
11.
ESOP – 8 ESOP 8
1.
Vers ion 10.0 10.0 Effective:Oct-10
BASIC RULES FOR PLANT OPERATION
General
1.1
The ESR lay down mandatory instructions that shall be obeyed when persons are operating or working on HV or LV systems.
1.2
This PROCEDURE lists good operational practices that if followed can help the operator to switch safety and avoid SWITCHING errors that lead to unnecessary loss of supplies.
2.
Basic Rules Before carrying out any SWITCHING operations on a unit of HV or LV switchgear, check if it has a 'Plant Restriction' marker label fixed to it [see ESOP 23] and check its general condition by a visual inspection. The latter is of particular importance for outdoor switchgear exposed to ambient conditions.
2.1
Do not trust your memory; consult your SWIT SWITCHING CHING PROGRAMME or written instructions before carrying out any operation.
2.2
When instructed to carry out SWIT SWITCHING CHING by telephone or radio, write down the instruction and read it back to the person who has given it to you.
2.3
Make sure you understand how the APPARATUS you are going to operate works. If in doubt, ask for assistance or check if information that would help is available. Do not experiment with LIVE APPARATUS.
2.4
Check the position of any switch you are to operate. Is it in the position you expected (i.e., closed, open or EARTHED)? EARTHED)? If not, find out why your SWITCHING PROGRAMME is not correct or why you have been told to operate it.
2.5
Check the title of any circuit twice before operating. operating. If the title is not the same as your SWITCHING PROGRAMME or instruction, find out why.
2.6
When SWIT SWITCHING CHING remove one padlock at a time to allow the operation. Lock again with a padlock when the operation operation is complete. Do NOT remove all the STANDARD ELECTRICAL PADLOCKS from another unit of switchgear that you are next going to operate before you are ready to carry out that SWITCHING operation.
2.7
Close and open all hand-operated circuit breakers, disconnectors and EARTH switches with a smart quick movement. If the circuit breaker trips immediately on closing, check the
2.8
reason before attempting to close again. After completing an operation, check immediately that you have performed what you intended to do. Is the circuit breaker closed or open? Are all three disconnector blades in the same position? Check the visual indications, ammeters, voltmeters, etc. If you make a mistake, operate the wrong switch or carry out an incorrect operation, check first what has happened and if practicable confirm with the CP what operations you should then carry out to rectify the error.
2.10
All protection relay indications shall be recorded in the log book before resetting any relay.
2.11
Remember to pause and think before you act in an operational substation or situation. All your actions should be deliberate and not impulsive. im pulsive.
2.12
When leaving a substation or disconnector switch, make sure everything is correctly locked and the substation door secure.
3.
Removing or Replacing LV Fuses on Switchboards
3.1
When inserting a fuse or link into any fuse-board it is good operational practise to:-
.
Page 49
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
a)
Ensure that there is an adequate adequate clear working space in front of the fuse-board.
b)
Ensure when operating on LV switchboards from above, that you remove all loose objects (e.g. pens, combs, sunglasses etc.) which could fall from your pockets into the switchboard.
3.2
Ensure that phase barriers in LV switchboards are in position and are in good condition.
3.3
Wear APPROVED LV rubber gloves. [See ESOP 24]
3.4
Confirm the electrical conditions with an APPROVED voltage testing device. [see ESOP 5]
3.5
Check that the fuse-carrier is in good mechanical condition and free of dust and grease.
3.6
Use a suitable fuse extractor.
4.
Additional Precautions and Procedures Following additional precautions and procedures shall be followed when carrying out removal and replacement of fuses on switchboards with exposed live parts
4.1
If it is practicable to make the switchboard of this type DEAD before carrying out the SWITCHING operations of removing or replacing fuses this shall be done.
4.2
When it is not practicable to make switchboards of this type DEAD, the following precautions and procedures shall be followed in addition to those called for in Section 3.0 of this ESOP :a)
The operations shall be carried out by a CESP who shall be accompanied by a SWITCHING CEP.
b) The CESP shall wear an ultraviolet protection face shield and infra-red protecting glasses. [see ESOP 24]
5.
Energising LV Circuits When commissioning and re-commissioning of new LV cables, insulation resistance tests will provide a reasonable assurance assurance that the cable is healthy. healthy. If the time between testing and energising is kept to a minimum the risks are small.
5.1
Check that the incoming supply is normal between all phases and neutral and between phases.
5.2
Carefully check that the correct fuse rating has been selected.
5.3
Insert the first fuse or link. Using an APPROVED voltage testing device, check for the presence of any back-feed on the other phases which, in the light of local knowledge, may determine if a phase-to-phase fault exists.
5.4
Insert the second fuse or link and check (as in Section 5.3) that there is no back-f back-feed eed on the remaining phase.
5.5
Insert the remaining fuse or link. Check on the circuit contacts that all supplies are healthy.
6.
Fuse Replacement When a fuse has blown and the cause is uncertain, particular care is required with its replacement.
6.1
Check the substation log book to see if there is a fault history for the cable circuit. If it appears that a transitory fault may be the cause of the fuse operation, careful checking of the cable insulation value should be carried out.
6.2
Where reasonably practicable, check the cable route for damage (e.g. open excavations).
6.3
Check the fuse cabinet and visible length of cable for signs of damage.
Page 50
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
6.4
Carefully check that the correct fuse rating has been selected.
6.5
If there is concern that there may be a high possible fault current, consideration should be given to de-energising the supply transformer to allow the fuse to be replaced dead.
Page 51
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
ESOP – 9
12.
ESOP 9 1.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
PROCEDURE FOR THIRD PARTY INTERFACES
Introduction
1.1
This procedure is issued to provide guidelines to be followed by PDO and third parties when electrical interfaces with PDO and third parties are involved.
1.2
This PROCEDURE briefly clarifies
1.3
the roles and responsibilities of all parties concerned.
communication method between PDO and third parties.
method of electrical supply connection from PDO to third parties and vice versa.
procedure for isolation / de-isolation of electrical supply for maintenance / repair works.
For a safe and efficient operation of the power supply system, both PDO and the concerned third party shall follow these procedures. Any deviation from this procedure proc edure shall be mutually agreed and approved in writing by PDO CFDH-E and the responsible person of the third party.
2. 2.1 3. 3.1
3.2
Scope This procedure is applicable to PDO and third parties with whom PDO has an agreement or intends to make an agreement for supplying or receiving electric power .
Boundaries / Responsible Persons Boundaries within PDO for the power generation, transmission and distribution are defined in the following ESOPs:
ESOP-15: Boundary Procedure for PDO Power system in the interior.
ESOP-17: Boundary Procedure for coastal area (Mina Al Fahal area)
Further to the above electrical boundaries, the head of area operations (Area Coordinators) are asset owners of electrical system in their respective area. 3.3
3.4 3.5
The head of Power Power system system operations and maintenance is the asset owner for power generation and transmission in the interior areas as defined in Asset Holder Drawings (AHD). The head of Estate Services is is the asset owner of electrical electrical system in the coastal area. The Corporate Functional Discipline Head, Electrical (CFDH-E) is is responsible for all Electrical discipline matters and is the custodian of electrical standards, procedures and electrical safety rules. He is the final authority on all electrical discipline matters.
4.
Procedures
4.1
Initiation
4.1.1
Before entering into any agreement / contract to supply electric power or to receive electric power, both concerned parties shall ensure that they fully understand the boundaries, the roles of the responsible persons and the procedures as laid down in this ESOP for the interface.
Page 52
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
4.1.2
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
Corporate Function Discipline Head, Electrical (CFDH-E) is the focal point in PDO for interfacing with third parties. CFDH-E or his appointed nominee(s) is responsible for negotiations with third parties. All communication comm unication shall be between CFDH-E or his appointed nominee and the responsible person of the third party until the interface project is finalised. After the interface project is finalised and until the project pro ject work is completed, commissioned and handed over to PDO operations the focal point shall be the PDO nominated person and all communication shall be between the nominated person and the third party nominee. Boundary demarcation of the new interface section shall be made m ade in writing and approved by CFDH-E and shall be incorporated in the respective ESOPs (ESOP.15 or 17) and asset holder ’s drawings, ’s drawings, if applicable. Once the interface connection is completed the Operations Area Coordinator responsible for the area shall be the PDO focal point and all correspondence shall be between the area coordinator or his nominated person. Refer to appendix-1 for details of contact numbers for each area.
5.
Method of Supply Connection
5.1
Over head lines shall be designed and constructed in accordance with PDO standards. SP1101,SP-1102,SP-1106 and SP-1107 shall be the basis for design and installation.
5.2
At the point of connection provision shall be made for isolation. For this a pole mounted isolator/fuse switch unit or circuit breaker with auto-recloser facility shall be used. If the supply point is from an indoor substation a dedicated circuit breaker shall be used. Custodian of this isolator / CB shall be the asset owner of power supply; i.e. if the supply is from PDO to third party, then PDO is the custodian; and if the third party is supplying power to PDO then the third party is the custodian. This shall be clearly identified in the concerned boundary procedure and Asset Holder Drawings (if applicable).
5.3
An isolation facility shall be provided at the receiving end also. This is required to safeguard from back feeding if a temporary generator is connected, when the line is isolated for maintenance or repair works. This isolation facility can be used for carrying out any repair / maintenance work at the consumer end. Custodian of this isolator / circuit breaker shall be the power supply receiving party.
6.
Isolation / De-Isolation Procedure
6.1
For any work on the line fed from PDO power supply system, the PDO permit system shall be followed before commencing any work. The isolation procedure in accordance with clause 7, 8 and appendix-2 shall be strictly followed.
6.2
For any work on the section of a line fed from a third party to PDO, the third party's perm permit it system shall be followed. (e.g. MEW power supply to PDO Mina Al Fahal Main Intake Substation)
7.
Maintenance / Repair Activities
7.1
For carrying out any maintenance or repair works on the boundary section of the third party, the responsible / appointed third party person shall give 14 days notice to the concerned PDO Area Coordinator in writing.
7.2
Upon receipt of notice from the third party, the Area Coordinator will arrange for Isolation of the section(s) concerned and instruct area electrical staff accordingly.
7.3
The authorised PDO electrical person shall carry out the isolation / de-isolation using the isolation / de-isolation certificate (Appendix-2)
Page 53
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
8.
Isolation / De-Isolation in Emergencies
8.1
Isolation / De-Isolation during Normal Working Hours
8.1.1
For isolation during normal working hours the third party responsible person shall contact the Area Coordinator and make the request
8.1.2
Upon receipt of such request the Area Coordinator of the area concerned shall authorise the area electrical staff.
8.1.3
The authorised area electrical staff shall carryout the isolation / de-isolation using the Isolation De-isolation Certificate. (Appendix-2)
8.2
Isolation / De-Isolation outside the Normal Working Hours
8.2.1
When the isolation / de-isolation is required outside the normal working hours, the responsible third party person should evaluate the seriousness of the situation and if he is satisfied that the situation is as such that the activities cannot be delayed until the following day, then he can activate PDO Utilities Emergency Response System by contacting the Electrical Emergency Response Person (EERP) on duty. Refer appendix-1 for the contact pager number.
8.2.2
The Electrical Emergency Response Person shall take appropriate steps for the isolation / de-isolation as per the procedure.
9.
Work Near or Under the Overhead Line
9.1
To work near orChapter-11, under the live line, is under PDO control, procedure detailed in PDO HSES Manual, shall bewhich followed. A clearance certificate shall be obtained prior to starting any work or passing of vehicles higher that 5 meter, under a line. Refer HSESM, Chapter-11, for details and certificate.
APPENDIX –1 –1
PDO AREA
PDO.TEL.NO.
PDO FAX.NO.
FAHUD
38 4790
384915
LEKHWAIR
38 1928
381728
QARN ALAM YIBAL
385540 381117
385551 381153
BAHJA
386702
388730
MARMUL
386269
386084
NIMR
382552
382356
RIMA
382231
382114
MINA AL FAHAL
677599
678579
677188/9
677511
UTILITY EMERGENCY RESPONSE PERSON
3RD PARTY TEL.NO. *
3RD PARTY FAX.NO. *
386345-6616 PAGER:
* To be completed after a third party agreement is finalised Page 54
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
Petroleum Development Oman LLC No.
ELECTRICAL ISOLATION /DEISOLATION CERTIFICATE FOR THE INTERFACE BETWEEN PDO & THIRD PARTY THIRD PARTY ISOLATION REQUEST
NAME OF THIRD PARTY:
1.
Isolation requested by: ………………………………………………………………. ………………………………………………………………..(Name .(Name ) I here by authorise our contractor M/s………….........………...(Contractor) at…….………….…… represented by Mr.............................................to Mr.............................................to carry out work on ….............................O/H line on…………….............. I request PDO Electrical Department...…….............(Ref.Ind) to coordinate with my above named person to isolate and give give permission to work on the above O/H line. line. Signed..............................Designation....................Time..........…......Date............………..... (Third party responsible person) PDO ACTION 2.
The above O/H line is Isolated From:................................................................................... Safety Padlock Nos.....................and caution notices have been applied at..........................
Key Safe No. (if applicable)............................. Signed............……................Name Signed............……................N ame ...........…..............Time..................Date.....…........ ...........…..............Time..................Date.....…........ (PDO Authorised Electrical Person) ________________________________________________________________ ____________________________________________________________________ _____ ACCEPTANCE ACCEPTA NCE BY THIRD PARTY PARTY WORK INCHARGE INCHARGE 3.
I accept responsibility for carrying out the work on the overhead line described in section.1 and no attempt will be made by me or persons under my charge to work on any other line or apparatus. Signed..........................…......Name...........................Company..........………............. Time.......................….Date.................………............. (Third party work in charge) __________________________________________________________________ _________________________________ _______________________________________ ______ THIRD PARTY DE-ISOLATION REQUEST
4. I hereby confirm that I have completed the work described in section.1, and that all men and materials under my control used on the above O/H line have been withdrawn, additional earth removed and the line is made safe to de-isolate and energise. The job is * COMPLETED COMPLETED / INCOMPLETE. INCOMPLETE. (List outstanding work) Signed...........……Name...............…….....Company……...…...Date……............ (Third party work in charge)
PERMISSION IS GIVEN TO DE-ISOLATE THE LINE DESCRIBED IN SECTION.1.
Signature.............…Name................….............Time::........…….......Date (Responsible third party person-the originator)
_______________________________________________________________ ______________________________________________________________ PDO ACTION
5. I CONFIRM THAT THIS ELECTRICAL ISOLATION/DE-ISOLATION CERTIFICATE IS CANCELED AND DE-ISOLATION HAS BEEN COMPLETED. ALL EQUIPMENT ARE CONSIDERED LIVE AND ENERGISED. Name:............................. Ref.Ind.:.............Signature..................Time:..............Date:................. White copy: 3rd party work in charge After completion: White copy: Third party file Blue copy: Third Party Blue copy: PDO file after completion of work Pink copy: PDO file
Page 55
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
*Delete as applicable
Page 56
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
13.
Vers ion 10.0 10.0 Effective:Oct-10
ESOP – 10 ESOP 10 10 IDENTIFICATION OF HIGH VOLTAGE UNDERGROUND CABLES
1.
Objectives
1.1
To ensure that any work or testing undertaken on a PDO HV cable shall be carried out in accordance with the ESR. These Rules call for the cable to be made DEAD, DEAD, ISOLATED and EARTHED, to be identified at the point of work, and proved DEAD by APPROVED spiking equipment or other APPROVED means.
1.2
This PROCEDURE shall be adopted, and these APPROVED methods used, when it is necessary to positively identify a PDO HV cable, particularly when it is laid, or runs, in the proximity of one or more other cables.
2.
Cable Records
2.1
Cable records are of help to locate the position of cables in the ground, or in runs, and assist in identifying the actual cable cable on which work or testing is to be carried out. The use of such records is an obvious help in looking for and finding such cables but, by itself, is not normally a sufficient positive methods to identify a cable before using APPROVED spiking equipment.
3.
Visual and Physical Identification
3.1
If practicable, the cable shall be visually traced throughout its length from its termination
3.2
point, at which it has been proved DEAD, to the point of work. A rope noose around the cable can sometimes be used to trace its route throughout its length, from its termination which has been proved DEAD, to the point of work.
3.3
Where the actions in Sections 3.1 or 3.2 have been carried out, mark the cable that has been identified by wrapping coloured tape on each side of the point of work.
4.
Electrical Methods of Identification
4.1
When positive identification cannot be carried out by visual means, electrical testing shall be carried out by using APPROVED cable identification equipment. [see Appendix A]
4.2
The majority of manufacturers' devices that employ electrical methods to identify DEAD cables rely on the detection of an external field, produced when an injected signal current flows around a loop formed by two of the cores inside the cable under test. The injected current is usually at audio frequency and pulsed to aid differentiation of the signal from other interference. Detection of the signal is by means of a search coil applied directly to the serving of the cable. The search coil needs to have extremely good directional properties so that it will ensure correct discrimination between two cables running close together.
5.
Use of Electrical Testing Equipment to Identify Cables
5.1
Following the necessary ISOLATION, EARTHING and all other safety precautions, a SANCTION-FOR-TEST for testing the cable circuit shall be issued in accordance with the ESR. The APPROVED cable identification equipment shall be used in accordance with the manufacturer's instructions and the guidelines in Sections 5.2 to 5.5.
5.2
Page 57
The APPROVED cable identification signal transmitter equipment shall be connected between two phases of the cable c able via suitable test connections.
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
5.3
The test signal can now be injected after removing the cable EARTHING connection at the point of signal injection. injection. The cable under test can normally remain EARTHED at its remote end during such testing. testing. The cable cores remaining EARTHED at the remote end should not affect the method of testing, providing that the output of the transmitter is correctly applied between two cores and not from one core to EARTH.
5.4
The search coil shall be applied to every cable in the trench, or near the point of work, and shall be moved completely round the circumference of every cable emitting a signal. 5.5 When the cable under test has been identified using this method, mark the cable by wrapping coloured tape on each side of the point of work.
6.
Use of Appro Approved ved Cable Spiking Guns
6.1
After positive identification, cable spiking shall be carried out under a SANCTION-FORTEST using an APPROVED cable spiking gun [see Appendix A] in accordance with the following procedure:a)
Fit the spiking gun equipment, between the coloured tapes, [see Sections 3.3 and 5.5] securely onto the cable in accordance with the manufacturer's instructions.
b)
Spike the identified cable using the long lanyard provided. Before removing the spike from the cable, check that no circuit breaker has tripped on fault at substations connected to any cables running in the vicinity of the site where the spiking has taken place.
c)
When removing the spiking gun, gun, check that the spike has cut through into one one phase core and the EARTHED sheath, or through two phase cores.
Note: Note:
If a LIVE cable has been spiked in error, there will not necessarily be an explosion at the point of spiking. The clearance speed of some types of circuit circuit protection could reduce the effects of the short-circuit fault current, so that in consequence, there could only be a minimal disturbance at the site of the spiking.
7.
High Voltage Cables that need not to be Spiked
7.1
In some circumstances it is not desirable to use an APPROVED cable spiking gun to prove an HV cable is DEAD, because because of the damage its operation inflicts on the cable. Three main examples are when:-
7.2
Page 58
a)
A repair repair is necessary on an oil-filled oil-filled or gas-filled gas-filled pressure cable.
b)
A superficial repair only only is necessary on the cable sheath or armouring.
c)
Carrying out an internal examination of a cable box.
In these circumstances it is the duty of the SAEP to ensure that identification of the cable to be worked on, or inspected, is positive, and that the CEP who is to receive the ELECTRICAL PERMIT-TO-WORK for that work, is fully satisfied with the precautions taken to ensure his safety.
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
APPENDIX A A
APPROVED CABLE ELECTRICAL IDENTIFICATION EQUIPMENT EQUIPMENT NAME & TYPE OF EQUIPMENT EQUIPMENT MANUFACTURER: MANUFACTURER:
DYNATRON
MODEL TYPE: TYPE:
METROMECH
MODEL NO.: NO.:
810
COMMENTS & USE USE
APPROVED TYPES OF CABLE SPIKING GUNS NAME & TYPE OF EQUIPMENT EQUIPMENT MANUFACTURER: MANUFACTURER:
BOWTHORPE EMP
MODEL TYPE: TYPE:
HYDRAULIC
COMMENTS & USE USE Complete with 10m of hose
MODEL NO.: NO.:
Page 59
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
14.
ESOP – 11 ESOP 11
1.
Vers ion 10.0 10.0 Effective:Oct-10
MECHANICAL RULES FOR OPERATING MACHINES AND OTHER PLANT
General
1.1
The ESR call for specific precautions to be taken before persons commence work on or near electrical APPARATUS. The majority of these precautions precautions are adopted to prevent DANGER to those persons for LIVE HV and LV electrical systems.
1.2
When work is to take place on generating plant and similar rotating machines, it is also necessary to prevent DANGER from mechanical or other types of hazards.
1.3
This PROCEDURE calls for MECHANICAL Rules to be applied in such instances, in addition to the requirements of the ESR.
1.4
Precautions to be taken when work is to take place in a building or enclosure protected by automatic Halon, CO 2 or similar installation is also included.
2.
Generating or Rotating Plant
2.1
All electrical connections must be ISOLATED and a SAFETY PADLOCK and CAUTION NOTICE attached.
2.2
The rotating parts shall be at rest and cooled sufficiently to allow work without DANGER.
2.3
The fuel supply control valve should be closed and a SAFETY PADLOCK and CAUTION NOTICE attached.
2.4
Any ignition devices and field switches shall be made inoperative and a SAFETY PADLOCK and CAUTION NOTICE attached.
2.5
If the rotating parts can easily rotate without motive power, then the lockable feature shall be operated and a SAFETY PADLOCK and CAUTION NOTICE attached.
2.6
The AEP shall issue an ELECTRICAL ISOLATION/ DE-ISOLATION CERTIFICATE to the person in charge of the work.
2.7
The person in charge of the work shall obtain a WORK PERMIT.
2.8
If any work is is to take place place on the the HV windings, connections, or any other work involving dismantling of the HV rotating equipment an ELECTRICAL PERMIT-TO-WORK will also be issued to the person in charge.
3.
Automatic Fire Protection Installations
3.1
Before entering any enclosure protected by Halon or CO2, the automatic control shall be made inoperative and the installation placed on manual m anual control.
3.2
An APPROVED notice shall be attached to the operating control stating that the installation is on manual control.
3.3
Any ELECTRICAL SAFETY DOCUMENT, or WORK PERMIT issued for work in such enclosures, shall state that the automatic feature is to be left inoperative when persons are inside.
3.4
The automatic control is to be restored immediately when persons withdraw from the enclosure.
4.
Immobilisation/Mobilisation Procedure by AP- Specific LV Motors
4.1
This procedure is only to be used in areas where LOW VOLTAGE motors are operated from Motor Control centres (MCCs) with main isolator devices equipped with padlocks, of which the suitability must be checked by the area CP.
Page 60
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
Reference shall be made to PR-1947 (Electrical Safety Rules), section-6 4.2
Method of Immobilisation PROCEDURE TO IMMOBILISE A SPECIFIC LV MOTOR, FOR USE BY APPOINTED PERSONS ONLY. PERMIT REQUIREMENTS: - Electrical Immobilisation / Mobilisation Certificate (ESR Appendix-E3)
1.
- Operations Work Permit Permit Procedure Ensure motor is stopped from process.
2.
Motor Remote Control Unit:
3.
4.
a)
Check identification number is as given on work permit.
b)
Padlock in "OFF" position using SAFETY PADLOCK.
Motor Control panel. a)
Identify correct cubicle as per work permit equipment tag number
b)
Move the Isolator to the "OFF" position.
c)
Fit SAFETY PADLOCK to lock isolator in position.
d)
Tie on CAUTION NOTICE.
e)
Fill up label and tag.
f)
Enter in the switch room/substation log book.
Motor Remote control unit: a)
Unlock and switch to "ON" position to check motor will not start.
b)
Padlock in "OFF" position and fix caution notice on the RCU.
c)
Put both the SAFETY PADLOCK keys in one of the KEY SAFE in the switch room and collect two keys.
5.
Write" IMMOBILISED" and sign in section 2.a of the work permit.
6.
Hand over one key safe key and work permit to the work party.
7.
The green copy of the work permit and the other key should be given to the operator.
Notes: 1)
All locks used shall be SAFETY PADLOCK i.e. unique key type.
2)
The Tag/Label shall have date, time, work permit number, reason and by whom the motor was made dead. (use pre-printed paper label with appropriate wording)
3)
Procedure must be followed in stated order of activities.
4)
There are different types of isolators /safety switches, ask if you are not certain how they operate.
PROCEDURE TO RETURN LV MOTOR TO SERVICE, FOR USE BY APPOINTED PERSONS ONLY. PROCEDURE: 1.
Page 61
Permit holder completes and signs section 11 of work permit, section 4 of immobilisation / mobilisation certificate and hand over the key.
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
2.
Ensure work party has completed the job, tools and lifting equipment removed guards, covers etc. has been reinstated.
3.
Motor control panel: a)
Open KEY SAFE and collect SAFETY PADLOCK keys.
b)
Remove CAUTION NOTICE, SAFETY PADLOCK and Tag/label.
c)
Move the isolator to the "ON" position.
d) 4.
Enter in the logbook. Motor Remote Control unit.
a)
Remove CAUTION NOTICE, Padlock and Tag/Label.
Page 62
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
4.3Training Procedure: Sr. No 1
02
ACTIVITIES
PERIOD
Selecting personnel for appointment of "APPOINTED PERSON"
1 week
Selected personnel should
10 days
ACTION BY
MONITORED BY
Area Electrical Area Coordinator Supervisor, Area Coordinator UIE/3E
Area Coordinator
2 months
Area Electrical Supervisor
Area Coordinator
6 months
Area Electrical Area Coordinator Supervisor
2 months
Area Electrical Area Coordinator Supervisor
1 week
Area electrical Area Coordinator Supervisor
every 6 months
Area Electrical Area Coordinator Supervisor
every 3 months
Head-Power Area Coordinator system operation
undergo f ollowing technical courses- the following * ELECTRICAL SAFETY (LEL 040) * ESR LOW VOLTAGE COURSE ( LEL 060) 03
04
Selected personnel should familiarise the area under his preview and acquire good knowledge in the following areas* Various types of switchgear and their operation in MCC room for which this procedure is applicable * RCU and their operations. * Identification of cables * Identification of equipment * Log book keeping etc. On the job training to the selected personnel as per the standard procedures
05
Observe the selected personnel performing the procedures independently
06
Examination/Testing of selected personnel for giving "APPOINTED PERSON" authority Review of "PROCEDURES" to the "APPOINTED PERSONS"
07 08
Review the activities stated above
and maintenance. Note: The period mentioned against Sl no 4 and 5 may be varied from person to person. The period can be increased or decreased till the Area Electrical Supervisor fully satisfies the Appointed Persons performance.
Page 63
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
15.
Vers ion 10.0 10.0 Effective:Oct-10
ESOP – 12 ESOP 12
PROVISION OF SUBSTATION SAFETY OPERATIONAL EQUIPMENT AND INFORMATION
1.
General
1.1
This PROCEDURE calls for specific notices and equipment to be provided at all specified PDO HV substations.
1.2
In addition it lists the technical information, concerning the APPARATUS installed in the substation that should, as a minimum requirement, be made available on site to those EPs responsible for its operation.
1.3
The term 'major' substation is used to exclude 11kV and 6.6kV substations supplying LV systems feeding domestic and commercial consumers.
2.
Notices
2.1
All designated entrances to all substations shall show an APPROVED WARNING sign in both English and Arabic.
2.2
All designated entrances to substation enclosures protected by fixed CO 2 fire fighting installations, shall have a notice calling attention to the installation and the need to make the automatic control feature inoperative before entering. An indication lamp shall be provided to call attention that the automatic control feature has been made inoperative.
2.3
A notice shall be posted in all substations, in both English and Arabic, containing directions on the resuscitation of persons suffering from the effects of electric shock.
2.4
A number of DANGER, CAUTION and EARTHING NOTICES shall be provided at all substations.
2.5
Each substation shall have labels mounted on the outside clearly identifying it from all other substations.
2.6
A notice shall be posted identifying the CP responsible for the substation and his contact telephone number.
3.
Equipment to be Provided
3.1
Where CO2 fire fighting installations are installed a switch shall be provided to remove the
3.2
automatic control feature and put it on manual control. Company approved portable fire extinguishers shall be provided in all substations, close to the entrance and access doors. For Company approved fire extinguishers extinguishers refer to HSE procedure SRD/S/02.
3.3
When adjacent to an outside switchyard, the substation shall be provided with APPROVED portable EARTHING leads that can be used as CMEs in that switchyard. switchyard. APPROVED labels inscribed 'CME' shall be made available to to be attached to such leads. [see ESOP 6]
3.4
First aid kits shall be provided at all substations.
3.5
A telephone shall be provided at all substations with a list of telephone numbers of all emergency services, Control Rooms, other substations and associated power stations.
3.6
All substations shall be provided with a log book that can be used to record SWIT SWITCHING, CHING, visits, inspections and protection relay trip indications prior to relay reset.
3.7
All major substations shall be provided with a single line diagram to indicate the position of all circuit breakers and disconnectors.
Page 64
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
3.8
All major substations containing oil filled equipment shall be provided with a fire proof blanket.
3.9
Ladders provided on site for use in switchyards shall be of a non-conductive type and be secured, when not in use, with a STANDARD ELECTRICAL PADLOCK.
4.
Information
4.1
All major substations shall be provided with the following information on site.
4.1.1
A SOP for the types of switchgear installed in the substation. [see ESOP 16]
4.1.2
Drawings for types of switchgear installed.
4.1.3
Drawings for the transformers and tap changers installed.
4.1.4
Drawings for the batteries and battery chargers.
5.
Technical Data
5.1
All major substations shall be provided with the following technical data on site.
5.1.1
Schematics for protection systems installed
5.1.2
Wiring diagrams for switchgear and associated control panels.
5.1.3
Schematics for transformer tap changer and automatic voltage control system installed.
5.1.4
Wiring diagrams for tap changer and automatic voltage control system.
5.1.5
Setting figures for all protection relays including any winding or oil temperature alarms or trips. 'Cutting in' temperature figures for fans and/or and/or pumps from transformer instruments (if this is not available at the Area Control Room).
5.1.6
Any other technical data that would assist maintenance or post-fault investigations on site.
6.
Storage of Information
6.1
Each major substation shall be provided with a suitable storage cabinet to accommodate the information, drawings and technical data called for in Sections 4.0 and 5.0.
Page 65
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
16.
ESOP – 14 ESOP 14
1. 1.1
Vers ion 10.0 10.0 Effective:Oct-10
LOSSES OF ELECTRICAL SAFETY DOCUMENTS AND ELECTRICAL KEYS
Objectives This PROCEDURE is issued to provide guidelines that shall be followed to ensure the safety of personnel when any of the following operational situations occur in PDO. a) ELECTRICAL SAFETY DOCUMENTS issued to allow allow work work or testing, on or near PDO electrical APPARATUS are missing or lost and the work or testing is not complete. b)
ELECTRICAL SAFETY DOCUMENTS issued to allow allow work work or testing, on or near PDO electrical APPARATUS are missing or lost and the APPARATUS is urgently required back in service.
c)
The recipient of an ELECTRICAL SAFETY DOCUMENT issued issued to allow work or testing, on or near PDO electrical APPARATUS is away from the site and cannot be traced to sign the Clearance Section of the document, or to agree to its cancellation, when the APPARATUS is urgently required back in service.
d)
The loss of or missing keys to: STANDARD ELECTRICAL LOCKS or PADLOCKS, SAFETY PADLOCKS and KEY SAFES as defined in ESOP 2.
1.2
The ESR state that ELECTRICAL PERMITS-TO-W ORK, SANCTIONS-TO-TEST, LIMITATIONS-OF-ACCESS and ELECTRICAL ISOLATION/DE-ISOLATION CERTIFICATES are all ELECTRICAL SAFETY DOCUMENTS.
2.
Loss of an Electrical Safety Document Following procedures shall be followed if a safety document is Missing or Lost and the Work, or Testing Is Incomplete.
2.1
Page 66
Work or testing shall not proceed until the following procedures have been carried out:a) All members of the WORKING PARTY are withdrawn from the work or testing. b)
A thorough search has has been made for the missing document.
c)
The recipient of the document shall sign the copy in the book from which which the document was issued, confirming that he has cleared the document; docum ent; an SAEP shall then cancel it.
d)
A new ELECTRICAL SAFETY DOCUMENT DOCUMENT shall be issued to allow the completion of
e)
the work or testing. The CP shall be informed if the missing, or lost document is cancelled in these circumstances, and the details of the new one issued.
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
17.
ESOP – 15 ESOP 15 15
1.
Vers ion 10.0 10.0 Effective:Oct-10
BOUNDARY PROCEDURES FOR THE INTERIOR HIGH VOLTAGE ELECTRICAL SYSTEM-INTERIOR
General
1.1
The Infrastructure Power system generation, transmission and distribution, with its associated substations and electrical plant, requires clearly defined boundaries of responsibility to be established for the Control personnel, who are involved in the system control and operation of these interconnected HV electrical systems.
1.2
The ESR require a CP to be appointed in writing for each section of a HV system, within defined electrical boundaries, and this PROCEDURE identifies where such boundaries exist in the Infrastructure Power system generation, transmission and distribution system.
1.3
Attached to this PROCEDURE, are a SCHEDULE and a set of single line diagrams, which clearly define system boundaries and identify each PDO operations Electrical group, including OETC responsible for a system's control and operation. Refer Appendix- A (SCHEDULE) and Appendix- B (list of single line diagrams).
2.
IDENTIFICATION of ELECTRICA ELECTRICAL L PERSONNEL Following procedures shall be followed for Identification of PDO & 3rd PARTY Operations Electrical Groups of Personnel.
2.1
Solely for the purpose of this PROCEDURE it is necessary to choose terms that clearly identify personnel who are to control and operate circuits and APPARATUS that make up the total interconnected electrical system.
2.2
The Area Operations (PFAT : Production Flow Asset Team) Electrical Supervisor and personnel responsible to this post have been referred to collectively as 'Distribution Staff' and shall be identified as 'DIST 'DIST'' in this PROCEDURE.
2.3
The Head of Power System Operations & Maintenance personnel responsible to this post have been referred to collectively as 'Transmission staff' and shall be identified as ' TRANS TRANS'' in this PROCEDURE.
2.4
The Area Estate Services Electrical Supervisors and the personnel responsible to this post have been referred to collectively as 'Estate Services Staff' and shall be identified as 'EST ' EST'' in this PROCEDURE.
2.5
Staff employed by Third parties have been referred to collectively as ’Third ’Third Party’ Party’ Staff' Staff' and shall be identified as 'THIRD 'THIRD PARTY' PARTY' in this PROCEDURE.
Note:
Exactly who the above identified groups of PDO staff are in terms of reference indicators depends on the organisational structure in place place at the time. ESOP 0 defines for the current organisational structure the reference indicators for each group of PDO staff .
3.
Selection of System Control Boundaries
3.1
Within any defined boundary, one CP shall be responsible for agreeing to all operations, allowing circuits or busbars to be SWITCHED, ISOLATED, EARTHED and ELECTRICAL SAFETY DOCUMENTS issued.
3.2
The CP shall consult with other CPs when the SWIT SWITCHING CHING PROGRAMME he is agreeing to will affect the electrical systems for which they are responsible. [see SP-1947 (ESR) Rule 5.2.2]
Page 67
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Example: Example:
3.3
Vers ion 10.0 10.0 Effective:Oct-10
If a switchboard controlled by 'TRANS TRANS'' requires to be isolated, then the 'TRANS TRANS'' CP shall consult with the 'DIST ' DIST'' CP, in case the isolation will affect any radial feeders which are normally controlled by 'DIST ' DIST'.'.
The control boundaries of the HV electrical systems interconnected by the 132kV overhead line shall be at the following f ollowing points:a)
The busbar spouts of isolatable isolatable metal clad circuit breakers feeding single line radial feeders.
b)
The tee-off points of the radial feeders on the 33kV overhead line rings supplying supplying the production facilities.
4.
Operation of Appar Apparatus atus
4.1
SWITCHING or the application and removal of CMEs shall be with the agreement or at the direction of the CP responsible responsible for that circuit or busbar. busbar. Actual SWITCHING operations shall be performed in accordance with a SWITCHING PROGRAMME. For apparatus which has the facility of remote SWITCHING by Scada, for which 'DIST ' DIST'' is responsible for control, then the 'TRANS 'TRANS'' authorized person in the Yibal or Marmul Control Room using the SCADA equipment may act as an operator.
4.2
'TRANS TRANS'' and 'DIST 'DIST'' personnel may operate any apparatus and apply and remove CMEs on circuits for which they are not operationally responsible, but only after request and agreement of the CP responsible for that circuit or busbar.
5.
Schedule of System Control A Schedule of System Control Responsibilities has been produced for the Infrastructure Power system generation, transmission and distribution systems, to assist personnel in identifying which CP is responsible for controlling a specific circuit within the overall system, in accordance with the requirements laid down by the ESR.
Page 68
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
APPENDIX A A
SCHEDULE OF SYSTEM CONTROL RESPONSIBILITIES RESPONSIBILITIES Note: Note: a)
This schedule shall be used in conjunction with the relevant single line diagram(s), listed in appendix B. B. TRANSMISSION & GENERATION ‘TRANS’ for: within the boundaries boundaries of the 132kV substations. substations. All equipment within equipment within within the boundaries of the power stations. stations. All equipment All 66kV and 132kV transmission lines. All 33kV ring feeder and associated line line isolators isolators originating from 132kV substations substations and power stations.
facilities originating from 132kV Incomers and bus sections of switchgear at production facilities substations and power stations. Incomers and bus sections of switchgear in the camp/industrial substations originating from 132kV substations and power stations.
b)
DISTRIBUTION 'DIST' for: for: 33kV overhead line high voltage voltage feeders, feeders, except as described above. All 33kV All distribution and electrical electrical equipment at production facilities. All distribution equipment in the camp/industrial facilities.
c)
ESTATE SERVICES 'EST' for: for: All electrical equipment within the boundaries of the R.O plants, except for the main incomer feeders which are controlled by 'DIST 'DIST'.'. All building building services at PDO camp and industrial industrial facilities. facilities.
d)
THIRD PARTIES 'THIRD PARTY' for: Third parties, at present, include following Companies:
Majis Industrial Services Company SAOC (MISG)
Mazoon Electricity Company SAOC (MZEC)
Middle East Development Company LLC (MEDCO)
Oman Electricity Transmission Company SAOC (OETC)
Oman Gas Company (OGC)
Oman Power and Water Procurement Company SAOC ( OPWP)
Petro Gas
Rural Areas Electricity Company SAOC (RAEC)
distribution network within within those places, places, All electrical distribution equipment and the distribution including the 33kV disconnectors will be controlled by the respective ‘Third party’. party’.
Page 69
The 33kV auto reclosers / fuses installed in the terminal pole of the 33kV overhead line line rd at the tee-off to the 3 party facilities and the 33kV ring main are controlled by ‘DIST ‘DIST”” . In case the third party facility supply is originating from a switch gear/panel, the same also will be controlled by ‘DIST ‘DIST’’
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
APPENDIX B
LIST OF SINGLE LINE DIAGRA DIAGRAMS MS BOUNDARY DETAILS Note: The following single line diagrams, form part of this ESOP Note: DRAW. NO. EFD 4 ....
AREA
DESCRIPTION/SUB DESCRIPT ION/SUB AREA
ISSUED ATE
REV.
0252 001
North Oman
Lekhwair & Yibal,
07/2009
G
0252 002
North Oman
Yibal-2, Fahud, Nahada 1&2, Kauther & Burhaan
07/2009
F
0252 003
North Oman
Qarn Alam, Saih Nihayda, Burhaan, Ghaba North, Saih Rawl & Mabrouk
07/2009
E
0252.007
North Oman
Saih Rawl 132kV GIS Substation
07/2009
O
0252 004
South Oman
07/2009
E
0252.005
South Oman
Anzauz, Suwaihat, Zauliyah, Bahja, Sayyala Sayyal a & Barik Hubara, Rima, Runib, Mukhaizna, NimrE, Nimr West, NGS &NRPS
07/2009
B
0252.006
South Oman
Amin, Amal, Haima West, Birba, Thuleilat & Harweel
07/2009
A
Page 70
Marmul,
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
18. ESOP – 16 ESOP-16 PROVISION OF SWITCHGEAR OPERATING PROCEDURES ESOP-16 & PROCEDURES FOR APPOINTED PERSONS 1.
Objectives 1.1
This PROCEDURE is issued to ensure that:
(a) When a new new type type of switchgear is installed at a power station, or substation, a complete SOP is available on site for the Custodian who is to operate the units. (b) When activities have been identified, identified, which can be carried out by APs, a complete PAP is available on site for the respective AP(s). 1.2
A dedicated SOP shall be prepared and be available on site, prior to the commissioning for each new type of switchgear that is being handed over to the Custodian to operate. Note: Note:
There is no need to prepare an SOP for a type of switchgear, which is provided under a project, but is existing in PDO somewhere else. else.
1.3
A dedicated PAP shall be prepared and be available on site, prior to the start of tasks or activities to be carried out by the respective APs. Prior to applying applying the PAP the respective respective APs shall be fully familiar with with the PAP for which they are authorised.
1.4
SOPs and PAPs resort under the 'Operations Standards & Practices'.
2.
Preparation of Switchgear Operating Procedures
2.1
It is the Project Engineer's responsibility to establish whether an SOP is required for the switchgear types types installed as part of his project. [see Note of section 1].
2.2
The Project Engineer responsible for the installation of the switchgear shall obtain from the manufacturer, full operating instructions for all new types of switchgear being installed.
2.3
The Project Engineer shall ensure that the SOP is prepared in the format approved by the CFDH-E.
2.4
All operations, using the SOP, shall be able to be carried out in strict accordance with the ESR and ESOPs.
2.5
Full instructions shall be prepared for each of the operations listed in Section 3.0.
2.6
For LOW VOLTAGE switchgear a generic operating procedure must be clearly posted in the switch room where the equipment is located with generic instructions for each of the operations in section 3.0.
3.
Switchgear Operating Procedures
3.1
The SOP shall include full f ull instructions on how to carry out the following operations:a)
Close and open all the switchgear units. To include the use of any synchronising devices.
b)
ISOLATION of the circuit breakers. Application of SAFETY PADLOCKS to shutters or disconnector handles.
c)
ISOLATION of any circuit voltage transformer. Application of SAFETY PADLOCKS to any shutters.
d) Page 71
ISOLATION of any busbar voltage transformer. Application of SAFETY PADLOCKS to any shutters.
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
e)
EARTHING of a feeder circuit. To include the use of an APPROVED voltage testing device into any feeder spouts. Use of the circuit breaker or fully rated EARTHING switch to apply a CME. Application of SAFETY PADLOCKS or device to prevent inadvertent tripping of circuit breaker, or the opening of the EARTHING switch in error.
f)
EARTHING of a section of busbar. To include the use of an APPROVED voltage testing device into any busbar spouts. Use of a circuit breaker, or fully rated EARTHING switch, to apply a CME to the busbar.
g)
Full instructions on the correct operation of any interlocking arrangements, arrangements, such as Castell locks or similar devices.
h)
Fitting, or or insertion, of any test plugs provided with the units.
j)
Any other operations that are called called for by PDO in their switchgear switchgear specification.
4.
Approval Approv al of Switchgear Operating Procedures
4.1
When the SOP has been prepared, the Project Engineer shall submit it to the Custodian to check it is complete, and that it covers all the associated activities they are to carry out.
4.2
Having obtained the agreement of the Custodian, the Project Engineer shall submit it to the CFDH-E for approval.
4.3
The Operations Electrical Support Engineer shall keep an up-to-date record of SOPs issued, obtain an unique reference number to every SOP received, and ensure that the SOP is included in the 'Operations Standards & Practices'.
4.4
The Project Engineer shall ensure that a copy of the SOP is on site prior to the commissioning of the switchgear.
5.
Preparation of Procedures for Appointe Appointed d Persons
5.1
It is the Custodian's responsibility to identify such activities, which can be carried out in a safe and responsible manner by persons having AP status, in the interest of using available resources more economically. economically. [see ESR section section 10] Note: Note:
1) The Custodian in this instance is almost always Operations. 2) It shall be recognised that APs do not generally generally have an electrical background. background.
5.2
Once such activities have been identified, it is the Custodian's responsibility to prepare a dedicated PAP for those activities, in the format approved by the CFDH-E. In most instances this task should be performed by the Area Operations Electrical Supervisor.
5.3
All activities specified in the PAP, shall be able to be carried out in strict accordance with the ESR and ESOPs.
5.4
Full instructions shall be prepared for each of the activities listed in Section 6.0.
6.
Procedures for Appointed Persons When writing a PAP it should be realised that the users are APs, who do in general not have an electrical background or have received received any prior electrical electrical training. The PAP shall be short and concise (ideally not more than one page) and be precise in its instructions and not be ambiguous or open to different interpretations. The use of electrical jargon shall be avoided. The PAP is is typically meant for small and uncomplicated tasks, for which little or no electrical knowledge required. required. It shall at least cover the following:following:-
Page 72
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
a)
A clear title stating the objective of the the PAP.
b)
A list of permits required to carry out the tasks specified in the PAP.
c)
Precise and concise step by step instructions in chronological order
d)
Instructions which safety precautions shall be taken. E.g., the application of SAFETY PADLOCKS, CAUTION and/or DANGER NOTICES etc.
e) Potentially hazardous situations shall be highlighted and instructions given to avoid or manage these hazards.
7.
Approval Approv al of Procedures for Appointed Persons
7.1
When the PAP has been prepared, the originator shall submit it to the relevant Head of Utility, who after checking and verification, shall forward the PAP to the CFDH-E for approval prior to its implementation.
7.2
The Operations Electrical Support Engineer shall keep an up-to-date record of PAPs issued, assign a unique reference number to every PAP received, and ensure that the PAP is included in the 'Operations Standards & Practices'.
7.3
The Custodian shall ensure that a copy of the PAP is on site and available for use by the APs and that APs receive proper training prior to applying applying the PROCEDURE. PROCEDURE.
Page 73
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
19. ESOP – 17 ESOP-17 BOUNDARY PROCEDURE FOR COASTAL AREA MEDC / ESOP-17 ORPC / PDO ELECTRICAL SYSTEM 1.
General
1.1
The MAF area electrical generation and distribution system, with its associated substations requires clearly defined boundaries of responsibility to be established between PDO Electrical Supervisors, ORPC Operations personnel and MEDC Control personnel who are involved in the system control and operation of these interconnected HV electrical systems.
1.2
The ESR require a CP to be appointed in writing for each section of HV system within defined electrical boundaries and this PROCEDURE identifies where such boundaries exist at the PDO Main Intake Substation.
1.3
A SCHEDULE detailing major items of electrical APPARATUS and identifying the MEDC, ORPC and PDO responsibilities for their control and operation are attached to this PROCEDURE.
2.
Identification of MEDC/ORPC/PDO Groups of Personnel
2.1
Solely for the purpose of this PROCEDURE it is necessary to choose terms that clearly identify personnel who are to control and operate circuits and APPARATUS that constitute the boundaries of the interconnected electrical system.
2.2
The MEDC Area Control Engineer and personnel responsible to this post have been referred to collectively as MEDC Staff and shall be identified as 'MEDC 'MEDC'' in this PROCEDURE and its attached SCHEDULE.
2.3
The ORPC Operations Engineer and personnel responsible to this post have been referred to collectively as ORPC Staff and shall be identified as 'ORPC ' ORPC'' in this PROCEDURE and its attached SCHEDULE.
2.4
The Head of Utility and personnel responsible to this post have been referred to collectively as 'PDO 'PDO'' in this PROCEDURE and its attached SCHEDULE.
3.
Main Division of Control Responsibilities
3.1
The division of responsibilities centres upon the 33kV switchboard at the PDO Main Intake Substation. The CP for this switchboard switchboard will be 'PDO 'PDO'.'.
3.2
''MEDC MEDC'' shall control the 33kV feeder circuits from their Al Falaj Substation to the PDO Main Intake Substation.
3.3
''ORPC ORPC'' shall control the radial 33kV feeders to their 33/11kV and 33/6.6kV transformers together with their associated 11kV and 6.6kV circuits.
3.4
'PDO'' shall control:'PDO (a) The 33 kV bus bars and circuit breakers along with all the associated substation auxiliary equipment and (b) The radial 33kV feeders to their 33/11kV transformers and 11kV distribution distribution circuit at Mina al Fahal and Ras al Hamra.
Page 74
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
4.
Selection of System Control Boundaries
4.1
Defined boundaries shall be at points so that any specific circuit or busbar requires only one CP to be responsible for agreeing all operations allowing that circuit or busbar to be SWITCHED, ISOLATED, EARTHED and ELECTRICAL SAFETY DOCUMENTS issued.
4.2
That CP shall consult with other CPs when the SWITCHING he is agreeing to will affect electrical systems for which they are responsible. [see ESR Rule 5.2.2.] Example: Example:
4.3
If one of the 33 kV incoming circuits has to be switched switched out then the MEDC MEDC CP shall first consult with PDO CP before the circuit switching commences.
Control boundaries of the HV interconnected MEDC/PDO electrical system shall be at the 33kV incoming cable spouts of the isolatable metal-clad 33kV switchgear in the PDO Main Intake Substation: Incoming cable spouts Al Falaj No.1, 2 3 & 4
4.4
Control boundaries of the HV interconnected ORPC/PDO electrical systems shall be at the outgoing 33kV cable spouts of the isolatable metal-clad 33kV switchgear in the PDO Main Intake Station: Outgoing cable spouts ORPC-1 & ORPC-2 Outgoing cable spouts ORPC-PP-1 & ORPC-PP-2
5.
Operation of Appar Apparatus atus
5.1
SWITCHING or the application and removal of CMEs shall be with the agreement or at the direction of the CP responsible responsible for that circuit or busbar. busbar. Actual SWITCHING operations shall be performed in accordance with a SWITCHING PROGRAMME.
6.
Identification of Apparatu Apparatus s The circuit breaker, transformer and associated plant numbering used in this PROCEDURE have been taken from the following drawing: MEDC/ORPC/PDO Electrical Boundaries - Drawing No: EFD-4-0252-010 Rev.B
7.
Schedule of System Control and Operation
7.1
The SCHEDULE of System Control, Operation and Maintenance, - Appendix A - has been produced to define for personnel the electrical boundaries and responsibilities, in accordance with the requirements of the ESR.
APPENDIX A - SYSTEM CONTROL, OPERATION & MAINTENANCE Page 75
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
APPARATUS AND VOLTAGE
33kV OVERHEAD LINE/CABLE
33kV SWITCHGEAR
33kV CABLES ALL OTHER SUBSTATION EQUIPMENT
Page 76
Petroleum Development Oman LLC
CIRCUITS OR ITEMS
Al Falaj No.1, 2, 3 & 4 INCOMERS: Al Falaj-1, 2, 3, 4 Bus bars Bus Section Outgoing:PDO-1, 2, 3 outgoing:ORPC-1, 2 Outgoing:ORPC-PP-1, 2 PDO-1, 2, 3 ORPC-1, 2 ORPC-PP-1, 2
Vers ion 10.0 10.0 Effective:Oct-10
CONTROL PERSON RESPONSIBLE
OPERATIONS CLOSING TRIPPING
ISOLATION EARTHING ELECTRICAL SAFETY DOCUMENTS
MEDC
--
MEDC/PDO
MEDC
PDO
PDO
PDO
PDO
PDO PDO
-PDO
PDO PDO
PDO PDO
PDO
PDO
PDO
PDO
ORPC
PDO/ORPC
PDO
PDO
ORPC
PDO/ORPC
PDO
PDO
PDO
PDO
PDO
PDO
ORPC
--
PDO/ORPC
ORPC
PDO
PDO
PDO
PDO
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
MAINTEN ANCE
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
20. ESOP – 18 ESOP-18 ESOP-18
REPORTING OF ACCIDENTS AND INCIDENTS AND EMERGENCY SWITCHING
1.
General
1.1
The ESR (Sections 3.4, 3.5) requires reports to be made in accordance with APPROVED PROCEDURES in the event of abnormal incidents, accidents or loss of supply. The following guidelines are the APPROVED PROCEDURES to be followed in the event of such circumstances.
2.
Objections
2.1
ESR Rules 3.2 directs that any person who objects to performing operations or work on HV APPARATUS shall make their reasons known to the person issuing the instructions. It is expected that they will endeavour to reach an agreement and come to a decision whether the instructions should be amended or cancelled.
2.2
When an agreement cannot be reached, the person issuing the instructions will refer the matter to a higher Electrical Authority for a decision or advice before issuing further instructions. Example: An AEP may refer to a SAEP and a SAEP to CFDH-E.
2.3
The higher Electrical Authority will decide if a report on the objections, and the reasons, should be submitted to the: Area Coordinator The CFDH-E
3.
Accidents and Incidents
3.1
The reporting procedure for accidents and incidents is laid down in the HSE procedure SRD/P/01.
3.2
In addition to the above procedure for all accidents or incidents, which have an electrical aspect, a copy of all reports shall be sent to the CFDH-E.
3.3
ESR Rule 3.4 calls for all dangerous occurrences and electrical accidents to be reported immediately to the CP who shall report in accordance with with an APPROVED procedure. The CP is not required to duplicate the above procedure in Section 3.1 but should ensure that appropriate reports are made.
4.
Failure of Supply / Electrical Fault
4.1
ESR Rule 3.5 requires that any failure of supply on the HV system shall be reported to the CP. Loss of supply to important associated LV installations installations and consumers also should should be included under this heading.
4.2
When the CP becomes aware of such supply interruptions (or severe voltage fluctuations) he shall act in accordance with the Emergency Response Procedures Part III Volume 7 (for the Interior) and Volume 10 (for the Coast). [see PR-1168]
4.3
The Originator shall prepare a fault report addressed to the CP and the Head of Power System Operation and Maintenance with a copy to the relevant Operation Electrical Support Engineers, Head of Integrity, CFDH-E and the Power System Control Engineer at Yibal Power station. [see Appendix A for a specimen of a fault report]
Page 77
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
4.4
The CP will coordinate the preparation of any further reports required by Operations or the CFDH-E.
5.
Emergency Switching
5.1
ESR Rule 5.2.1.7 and ESR Rule 5.2.3 both may require EPs and suitable authorised operators to implement emergency SWITCHING to avoid DANGER to persons or APPARATUS.
5.2
When the CP becomes aware that such SWIT SWITCHING CHING has taken place, first he shall consider what further action needs to be taken to safeguard persons, APPARATUS, or to restore power supplies to PDO facilities and consumers.
5.3
The CP then shall decide if the seriousness of the incident and possible subsequent loss of power supplies requires him immediately to make a verbal report to the Area Head of Operations or wait until normal office hours.
5.4
The CP then shall confirm this verbal report in writing by e mail or fax to head of Operations and maintenance, with a copy telex to the CFDH-E.
6.
Control Person Reports
6.1
Urgent verbal reports made by the CP in accordance with this PROCEDURE are mainly for management information and should be treated as such.
6.2
Written reports made by the Originator to Operations shall contain factual information, but should not be considered as full reports on on-site occurrences.
7.
Guidelines for Preparing Fault / Failure Reports Fault reports serve a useful purpose, as they are used to analyse the reported fault. The result of such an analysis can be that (i) a protection setting has to be changed, or (ii) that equipment which breaks down often, will no longer be purchased, or (iii) an electrical system has to be upgraded etc. Appendix A and B shows specimen electrical fault report form and specimen electrical failure action form. These shall be used to report electrical faults of whatever nature (e.g. equipment failure or power outage). To facilitate analysis, the report should be concise and factual, for instance when discussing the cause of failure, be sure not to mix facts with opinion. Adequate detail shall be provided; provided; the entries in the report serve as a guide guide for this. When reporting on an equipment failure, state the following: Name plate details (e.g., of a faulty motor)
type of equipment involved, including location location (e.g. LV switchgear Capitole Capitole Make and type 3N in substation xx). Sub system of equipment (e.g. starter drawer, panel number).
detail you you deem to be relevant. Any other detail Sometimes it can be helpful to submit with the fault report a single line diagram, showing the location of the fault. fault. Very useful are pictures of the faulty equipment.
In c ase of an equipment equipment failure it is i s very important to to keep k eep the the equipment ava availabl ilable e for ins pection at a la later ter date. date. Do not throw away away anything anything !
Page 78
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
APPENDIX A
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
ELECTRICAL F AULT REPORT FORM
Electrical F Fault R R eport F Form
Fault number:
Type of Fault
Date of Fault:
Time of Fault: Date Power Restored:
Time Power Restored:
Area
Weather Conditions:
System Interruption System Configuration Prior to Fault: Station Affected
Page 79
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
Generator Alarms:
Protection Relay Indication:
Action Taken:
Net Oil Deferment m3
Supplies Restored:
Cause of Fault:
Remarks:
Report made by:
Reference Ind.:
Department:
Page 80
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
APPENDIX B - ELECTRICAL F AILURE ACTION FORM
Electrical F Failure Action F Form EFR No. Area Voltage Type of Fault Effect Deferment Maintenance History Compliance Status Priority Action Ref No. Action
Action Party
Close Out Date
Action Follow up
Completion Confirmation Statement
EFR No. Area Voltage Type of Fault Effect Deferment Maintenance Page 81
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
History Compliance Status Priority Action Ref No. Action
Action
Close
Party
Out Date
Action Follow up
Page 82
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
21. ESOP – 21 ESOP-21 APPLICATION OF LV EARTHING DEVICES TO LOW ESOP-21 VOLTAGE SWITCHBOARDS
1.
General
1.1
The ESR (Rule 5.4) require that before work can take place on LV APPARATUS, or conductors, they shall be made DEAD, ISOLATED and where practicable locked off with SAFETY PADLOCKS. Additionally the Rules require that when it is necessary, because of the design of the LV system or switchboard, or because of the nature of the work to be done, LV EARTHS shall be applied.
1.2
ESR Rule 5.5.3.2 requires that an LV EARTH shall be of an APPROVED design and ESR Rule 5.5.3 details the procedures that shall be followed when such LV EARTHS are applied to LV APPARATUS.
1.3
ESR Rule 7.8 details the precautions, including the application of any LV EARTH, before work takes place on LV switchboards.
1.4
This PROCEDURE proposes guidelines to follow when it is necessary to apply LV EARTHS to PDO LV APPARATUS and specifies the APPROVED equipment that shall be used.
2.
The Need for Approv Approved ed Portable LV Earthing Equipment
2.1
The majority of LV APPARATUS, purchased and installed by PDO, does not include any designed facility for EARTHING any of its internal connections or conductors terminating onto it. The design philosophy of manufacturers of LV ELECTRICAL EQUIPMENT has been, that by providing suitable ISOLATING, locking-off facilities and adequate busbar interlocking features, safe working conditions can always be provided for persons working on or testing LV APPARATUS without the need for EARTHING.
2.2
In many instances SAFETY PADLOCKS (as defined in ESR Rule 2.13) cannot be fitted onto many LV switchboard units or busbar interlocking arrangements. It is difficult in some situations, in particular on remote sites, always to ensure that fuses or links, removed for ISOLATION purposes, will not be replaced in error by unauthorised persons. In these circumstances EPs responsible for the work sometimes decided to apply EARTHING as an additional precaution. PDO personnel and contractor's staff instructed to work on LV APPARATUS, in some instances, wish to see that the conductors are EARTHED, in addition to being made DEAD, particularly when the APPARATUS is connected onto the LV side of a HV/LV transformer.
2.3
If it is necessary, or operationally desirable, to EARTH LV APPARATUS then it should be done as a properly recorded SWITCHING operation, using suitable equipment APPROVED for the job. It is important to avoid avoid PDO personnel, or contractors applying applying their own EARTHING by using pieces of wire etc. that are inadequate to prevent DANGER and could cause serious damage if left on in error.
3.
Approved Approv ed Equipment for Use as LV Earths
3.1
Portable EARTHING devices or EARTHING leads that are to be used as LV EARTHS shall be of such a size and design, so as to be capable in use of carrying the full rated short circuit current if a LIVE circuit, was in error, closed onto them at the position where they had been applied.
Page 83
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
3.2
The choice of the cross sectional size of the leads or conductors used in the construction of such portable EARTHING devices, will depend on the short circuit levels of the PDO electrical system on which they are to be used.
3.3
The portable EARTHING devices shall have leads and end clamps that can be connected to all phase conductors and the EARTH bar, and for preference shall have a lead that can, where necessary, be connected to the neutral conductor. The selection of fittings, leads and end clamping arrangements will depend on the LV APPARATUS on which the devices are to be used. Appendix A gives details. details.
4.
Maintenance of LV Earthing Equipment
4.1
All portable EARTHING devices and EARTHING leads shall be examined immediately prior to use to ensure they are in good condition. [see ESR Rule 5.5.3.3 and Rule 5.5.2.1 (b) (iii)]
4.2
At three monthly intervals all portable LV EARTHING devices and leads shall be maintained in accordance with the relevant SAP maintenance routines.
5.
Application of LV Earthing Devices
5.1
ESR Rule 5.5.3 gives the procedures for applying LV EARTHS after the use of an APPROVED LV testing device.
5.2
Any LV EARTH applied shall be recorded in the 'Other Precautions Section' of the relevant ELECTRICAL PERMIT-TO-WORK.
6.
Applying Apply ing LV Earths to Low Voltage Switchboards
6.1
ESR Rule 7.8.2 (f) and Rule 7.8.3 refer to LV EARTHS being applied on the DEAD conductors of LV APPARATUS. It is important to note that the application of all LV EARTHS shall be recorded on ELECTRICAL PERMITS-TO-WORK in the 'Other Precautions Section', but that the Rules do allow these LV EARTHS to be applied after the ELECTRICAL SAFETY DOCUMENT has been issued. The Rules allow for an LV switchboard unit, or busbar section to be made DEAD, ISOLATED and SAFETY PADLOCKS attached and an ELECTRICAL PERMIT-TO-WORK issued to allow work before any LV EARTHS are applied. However if it has been decided to apply LV EARTHS, then these shall be entered in the 'Other Precautions Section' of the ELECTRICAL PERMIT-TO-WORK when the document is issued.
6.2
To apply LV EARTHS to many types of LV switchboards installed in PDO, it is first necessary to carry out the work of taking off metal covers to expose the conductors that are to be EARTHED. This work shall be carried out under the ELECTRICAL PERMIT-TO-WORK prior to the use of an APPROVED voltage testing device and the application of the LV EARTH. Only CESPs with sufficient training and experience shall be allowed to undertake the careful removal of such covers, and the application of these LV EARTHS, under the direct supervision of an AEP.
6.3
It is the duty of the AEP to check that these LV EARTHS are removed and all covers replaced before accepting the signed 'Clearance Section' of the ELECTRICAL PERMIT-TOWORK from the CESP.
6.4
CMEs shall be applied on HV APPARATUS before an ELECTRICAL PERMIT-TO-W ORK is issued and removed only when that document is cancelled.
Page 84
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
APPENDIX -A
APPROVED LV EARTHING DEVICES DEVICES The contents of this Appendix will depend on the LV EARTHING equipment already in use and the future purchasing policies that PDO wish to adopt for such equipment .
NAME & TYPE OF EQUIPMENT EQUIPMENT
COMMENTS & USE USE
MANUFACTURER: MANUFACTURER:
PFISTERER
MODEL TYPE: TYPE:
3-POLE EARTHING & SHORT-CIRCUITING DEVICE
MODEL NO.: NO.: MANUFACTURER:
360 481 481 PFISTERER
MODEL TYPE:
3-POLE EARTHING SHORT-CIRCUITING CABLES
MODEL NO.:
364 641 016
Page 85
&
FOR USE WITH DIN TYPE FUSE BASES e.g. * HOLEC CAPITOLE 3/5 * FEEDER PILLARS FOR DIRECT BOLTING TO EXISTING CONNECTIONS e.g. * HOLEC CAPITOLE 10/E
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
22. ESOP – 22 ESOP-22 LIVE LINE WORKING AND LIVE LINE WASHING PRACTICES ESOP-22 PRACTICES 1. 1.1
General This PROCEDURE has been issued to provide guidelines for PDO personnel who are required to become involved with LIVE LINE WORKING (LLW) activities, or those of LIVE LINE WASHING (LL WASHING), in the course of their duties.
1.2
The CFDH-E has a responsibility to check that any Contractor approved by PDO for either LLW or LL WASHING, W ASHING, has the necessary proven Procedures, the special equipment and the trained staff to be able to carry out such work safely on PDO HV APPARATUS.
1.3
The ESR call for AEPs to ensure that Contractors who are employed to carry out either LLW or LL WASHING, do it in accordance with the requirements of Sections 8.0 or 9.0 of those Rules. These Sections of Rules require the AEP, initiating the work, to carry out specific operations and checks before allowing the Contractor to start, and to monitor the progress of the LIVE LINE activities on site.
1.4
This ESOP contains Sections that outline internationally accepted LLW and LL WASHING practices, while others give guidance on the precautions and details of equipment that shall be contained in a Contractor's Procedures. In addition, Sections are included that explain what to look for when such activities are being carried out on site, and when Rules, other than those in ESR Sections 8.0 and 9.0, apply to Contractor's personnel following their disconnection of HV APPARATUS using LLW methods.
2.
Objectives
2.1
To provide information for personnel assessing a Contractor's submitted LLW and LL WASHING Procedures for PDO approval.
2.2
To provide guidance to AEPs initiating and observing Contractor's LLW and LL WASHING Procedures on site.
2.3
To provide guidelines on the application of the ESR when LLW Procedures are carried out on overhead lines, or in substations.
3.
Live Line Working Practices This Section contains both general and specific precautions that are internationally accepted as desirable when when LLW is undertaken on HV overhead lines. lines. Contractors undertaking LLW shall have a Section in their Procedures that contain most of these precautions that shall be taken before, and during, the LIVE LINE WORKING. These general items shall normally include the following:-
3.1
General Precautions to be observed for LLW
3.1.1
General
(i) (ii)
No LLW shall be carried out except in accordance with proven Procedures. Safety belts shall be worn worn by members of the Team working from an overhead line support or structure.
(iii) Safety hats shall shall be worn at all times by members of the the Team and any persons working with them. Page 86
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
(iv) Tinted safety spectacles shall be worn by all members of the Team unless it is considered by the person in charge that vision would be restricted by these, due to poor light. [See ESOP 24]
3.1.2
(v)
LLW shall not be used if the line conductors have been jointed with mid-span joints, other than approved compression joints (provided this does not exclude any Procedure designed to replace such non-compression type joints).
(vi)
LLW Procedures shall not be used which which involve conductor displacement on wood
(vii)
pole lines with an over-slung earth wire. Wood poles erected beneath and into LIVE lines shall be shrouded at the top with a suitable insulating shroud.
(viii)
No equipment shall be fixed to a pole pole which is is being erected into a LIVE line other than the insulating shroud and the lifting equipment.
(ix)
Where transformers are to be disconnected using LLW Procedures, prior ISOLATION of the LV system shall take place to prevent any possibility of a back-feed, energising the transformer during the LLW operation.
(x)
Ensure that where under-slung aerial earth wires are installed, these are detached from their fixing and lowered beneath the operating area and either secured to the wood pole or pulled to one side.
(xi)
Before climbing a wood wood pole, and after it has been sounded, sounded, test the pole-top pole-top steelwork for leakage current. Should the pole pole steelwork be found to be LIVE, the pole shall not be climbed.
(xii)
LLW shall normally be restricted to dry weather conditions and and shall not be permitted in misty, foggy or thunder conditions. conditions. Work may m ay continue in in light rain at the discretion discretion of the person in charge, except in those Procedures in which insulating ropes are used in close proximity to LIVE conductors. Where unfavourable weather conditions occur during LLW, the work shall be suspended leaving the structure, conductor and LLW Tools in a secure situation.
Precautions to Be Observed Before Work Starts (i)
Examine structures, fittings and conductors on either side of the point of work to ensure that there is no damage or weakness.
(ii)
Where it is applicable, ensure that auto-reclose features are locked off before work commences.
(iii)
Where practicable, remove the installed EARTH from a wood pole structure using using LLW Tools. The EARTH shall be removed from the full length of the pole. The under slung earth wire shall be detached from its fixing on the pole, lowered beneath the operating area and either secured to the wood pole, or moved to one side.
3.1.3
Precautions to be observed during Work There shall be an OBSERVER on the site during the whole of the LLW Procedure who Procedure who shall ensure that Safe Working Clearances are maintained at all times and that the proven Procedure is followed. (i)
All line supports climbed and worked from during an LLW Procedure shall be marked, e.g. with a 'DANGER - LIVE CONDUCTORS' band, or suitable flag pennants in the case of steel towers or structures.
(ii)
No person shall allow any part of his body to pass beyond these Safe Work Working ing Distance Markers, except when all conductors are securely held by LLW equipment, at a safe distance from the support. When dealing with wood pole constructions where the phase conductors are at different levels, it is permissible to reposition the Safety Distance Markers when the
Page 87
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
lowest conductor(s) have been removed, provided that any bonding between the steelwork at different levels is cut and removed. (iii)
Ensure adequate adequate shrouding shrouding is is used to prevent contact of conductors conductors or wire binding with the supporting steelwork.
(iv)
For system voltages of 33kV and higher, higher, a leakage monitoring device shall be installed.
(v)
When an LLW LLW Tool is in contact with a LIVE conductor, it shall only be handled handled below the appropriate Safe Handling Mark on the Tool.
(vi)
Where conductors are displaced from their normal positions, positions, Safe Working Work ing Clearances between the conductors and the ground or other object(s) shall be maintained.
(vii)
Whilst moving conductors supported by LLW Tools, the operators shall at all times be prepared to lock the Wire Tongs in their saddles should a dangerous situation develop or arise.
(viii)
When working after conductors have been removed to a safe distance, operators shall take care to position themselves and the equipment to give maximum clearance from the conductors.
(ix)
No vehicle, or person, other than a member of the Team, shall be allowed allowed in the near vicinity of the point of work without the permission of the person in charge of the Team.
(x)
In the event of adverse adverse weather weather conditions arising the work shall shall be made safe as quickly as possible with the conductors either in their normal norm al positions or securely held by the LLW Tools. Work shall be suspended until the adverse weather conditions have passed. Before recommencing the LLW, the Tools shall be dried as necessary using clean chamois leather. Electrical rubber gloves gloves shall be worn for this operation.
3.2
Routine Care, Inspection and Electrical Testing of LLW Tools
3.2.1
General Approved epoxy glass Tools for LLW shall be resistant to moisture absorption and have a smooth, highly polished polished finish to prevent prevent contamination. It is essential to keep the LLW Tools in a clean and dry condition. LLW Tools shall not be laid directly on the ground. They shall be kept in their carrying bags or transport until they are required: alternatively they may be laid on a waterproof sheet or on temporary supports above the ground. LLW Tools shall be wiped clean before being passed up the structure for use, and again before being stored. When the Tools are exposed to rain or any contamination contamination they shall be wiped dry and cleaned at the earliest opportunity.
3.2.2
Storage and Transport LLW Tools shall not be stored in a dirty or damp condition and care shall be taken to guard them against abrasion of the insulating surfaces. Storage areas shall be dry and well ventilated. ventilated. LLW Tools shall be transported in specially specially designed vehicles and trailers in which the Tools are properly located and held firmly in position. The Tool compartment shall be ventilated.
3.2.3
Inspection of LLW Tools on Site All LLW Tools shall be inspected before and after af ter use for any signs of damage to the Tool or insulation. If there is any shall doubtinclude:about be used. The inspection incl ude:-the condition of any Tool or part of any Tool it shall not
Page 88
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
(i)
A check that the Tool is complete and working correctly.
(ii)
An examination for signs signs of mechanical over-stressing indicated indicated by the bending or cracking of any part or parts, bent rivets or bolts and movement of ferrules.
(iii)
Checking the metalwork for loose bolts, rivets and damaged or worn parts.
Each Tool shall be stamped with a reference number and a safe working load, where this applies. The Tools shall be subject to at least a six-monthly detailed detailed examination. 3.2.4
Electrical Testing of LLW Tools New epoxy glass LLW Tools shall withstand an electrical pressure test of 100kVDC per 300mm for a time of 1 minute. Any Tool with a measured leakage current greater than 0.03mA shall not be used for LLW. For LLW Tools in service, this test shall be repeated at regular intervals, depending on the frequency of use of the Tools. In addition to the above tests, regular checks on the surface condition of the Tools shall be carried out using a portable LIVE LINE TESTER.
3.3
Provision of Sufficient LLW Tools for LLW Procedures Each LLW Procedure shall state the list of equipment and LLW Tools that are required for that particular job. It is most important that that the recommended numbers of each type of LLW Tool required shall be clearly established. For example, when moving a LIVE, non-tension conductor, there shall always be two Wire Holding Sticks employed for controlling this operation and the Procedure shall state that two are required.
3.4
LLW Team Numbers Required for Specific Procedures In principle there shall be sufficient operators in a Team to carry out the LLW Procedure above ground, a ground-crew member responsible for providing them with the equipment as they require it, and an OBSERVER (who ( who does not take part directly in the activity). The OBSERVER's role being to ensure that the correct Procedure is followed, Safe Working Clearances are maintained at all times, and in the event of an accident, be available to give calm impartial advice to the LLW Team for the safe restoration of the conductors on site.
3.5
Safe Working Clearances or Distances The terms 'Safe Working Clearance', 'Safe Working Distance' Handling Distance' are all to be found in many companies Procedures. Althoughand they'Safe are used in this ESOP, none of them are defined in the GLOSSARY Section 0.0 of the ESR. In some instances the terms are used to refer to the distance that a mark shall be placed (depending on the system voltage) on an LLW Tool to indicate the Safe Handling Distance. Alternatively it is used to define the distance from a LIVE conductor in which no member of an LLW Team shall bring any part of his body, clothing or Tool, except for an LLW Tool.
3.6
Illustration of LLW Procedures A main feature of LLW Manuals is that the written Procedures are illustrated by comprehensive step-by-step drawings. drawings. To ensure full understanding by all members of an LLW Team, it is essential that written LLW Procedures are supported by such drawings. In addition it is extremely difficult to properly assess LLW Procedures which are not supported by detailed drawings.
Page 89
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
4.
Vers ion 10.0 10.0 Effective:Oct-10
Live Line Washing Practices These are the simple, internationally accepted, principles and techniques of using portable LL WASHING equipment to clean insulators on overhead line circuits and in substation compounds.
4.1
General Portable washing equipment used for cleaning polluted insulators supporting LIVE HV conductors, are dependent on three main factors that determine if the LL WASHING Procedure can be used safely. These are:(i)
Nozzle design, size and type.
(ii)
Water pressure available at the nozzle.
(iii)
The conductivity of the water to be used for the washing.
When considering these three factors it is important to be aware that the safety of the person operating the portable washing equipment depends on:-
4.2
(iv)
Avoiding large leakage currents in the water water jet between the LIVE HV conductors conductors and the nozzle the operator is holding.
(v)
Avoiding large leakage currents down the LIVE conductor's insulator stack which could lead to an electrical flashover near to the operator .
Nozzle Design and Use
The nozzle used can be of several different designs, or size, but it shall be capable of breaking up the water into droplets before the water jet comes into contact with an insulator carrying a LIVE conductor. Whatever type of nozzle is used for portable LL WASHING equipment, it shall be effectively connected to EARTH to protect the operator.
4.3
Water Pressure at the Nozzle This pressure obviously depends on the length of the jet of water required to effectively wash a polluted insulator, whilst still allowing the operator to remain at a safe distance from any LIVE HV conductor. This safe distance depends on the clearance required from the LIVE conductors at a particular system voltage, and the need to keep any leakage current, down the water jet to the nozzle, under 1mA (the 'threshold of perception'). The design of the portable washing equipment shall allow for the maximum water pressure that can be produced by its pump when fitted with a particular design, and size of nozzle, and of course, the conductivity of the water being used.
4.4
Conductivity of Water Used for LL Washing The mineral content of any water used for LL WASHING has a direct relationship to its resistance, and therefore its properties for permitting leakage currents down the water jet. Obviously the higher the water conductivity, the lower its resistance, which enables higher leakage currents to flow, creating potential hazards for the operator of the portable LL WASHING equipment. A rise in the water's temperature increases its conductivity, so a close check is required during the LL WASHING to ensure that it remains under the permitted perm itted level. In sophisticated LL WASHING portable equipment, an automatic tripping of the water pump occurs if the conductivity increases above a pre-determined level.
Page 90
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
5.
Contractor's LLW Procedures
5.1
What to Look for In Contractor's LLW Procedures
5.1.1
General
Vers ion 10.0 10.0 Effective:Oct-10
The ESR Section 8.0 (LLW) calls for selected Contractors to use only proven Procedures; have adequately trained experienced staff and well maintained LLW Tools and equipment. Establishing all this before aactually employing Contractor toshould carry give out aaparticular LLW can be difficult. However study of his written writtena Procedures reasonable guijob guide de to the methods he intends to use, and can indicate whether he has a professional, and safe approach to such work. The following guidelines are not exhaustive; however this Section does suggest the information and technical detail which should be looked for in a Contractor's Procedures. This study of his Procedures shall be followed by PDO personnel witnessing the LLW Team in action, confirming the Team's operational discipline is good, and that the LLW Tools and equipment they are using are suitable and well maintained. 5.1.2
General Precautions for LLW Section 3.1 of this ESOP lists many of the accepted LLW practices normally found in LLW Codes of Practice adopted by Power Power Utilities all over over the world. It is unlikely that any Contractor has all these practices listed in the Procedures that he gives to potential customers, but it is a valuable guide to evaluating his written approach to LLW and for subsequently assessing the performance of his Team in action.
5.1.3
Care and Inspection of LLW Tools Section 3.2 of this ESOP gives a summary of the preferred methods that shall be adopted by LLW Contractors to ensure that the Tools they use are kept in in good condition. Check if the Contractor has such written instructions on the transporting, care, inspection and electrical testing of his LLW Tools. Do his LLW Teams have such instructions, as their safety depends on their careful handling and use of insulated LLW Tools? Each LLW Procedure shall state the list of equipment and Tools that are required for that particular job. It is most important that the recommended numbers of each type of LLW LLW Tool required shall be clearly established prior to 'approving' a Procedure. For example, when moving a LIVE, non-tension conductor, there shall always be two Wire Holding Sticks employed for controlling this operation and the Procedure shall state that two are required.
5.1.4
LLW Team Numbers Required for Specific Procedures It is imperative that there are sufficient LLW operators available for any given Procedure to ensure the safety of the operators, plant and equipment. Each Contractor's Procedure shall shall state the minimum number of staff required in the LLW Team. In general, it is good practice to assign one operator for each Wire Tong of a pair i.e. generally two operators. A 'groundman' will be required to pass equipment to these two operators and secure equipment as necessary. In addition to these three operators an OBSERVER shall be on site to ensure Safe Working Distances are maintained and the Procedure is carried out correctly. The majority of Procedures for LLW on wood pole overhead HV lines require a minimum of four Team members.
Page 91
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
LLW Procedures for double circuit steel tower lines, usually require an additional Team member on the ground, plus a further operator in the body of the tower. As a guide itit is probable that a minimum of six Team members would be needed for this type of Procedure. 5.1.5
Safe Work Working ing Clearances or Distances Check the Contractor's Procedures to see if he calls for marks to be placed on the LLW Tools indicating the Safe Handling Distance for the system voltage being worked on by the Team. These marks shall be maintained on the Tools throughout the Procedure and shall be placed at a distance not less than that called for in ESR Rule 8.2.2. Additionally the Procedure shall give instructions to the Team to place 'safety markers' indicating the Safe Working Distance into which no person shall bring any part of his body etc. other than the LLW Tool T ool he is using. This Distance shall be no less less then that called for in ESR Rule 8.3.10. When Procedures are to take place in substations, it is most important that directions are given to the Team to place 'safety markers' markers ' not only on the structure they are working on, but also on those structures, supporting LIVE APPARATUS, in the near vicinity of the LLW activity.
5.2
English Translation of LLW Procedures PDO at present require all Contractors to submit their documents written in English. This presents some LLW Contractors with certain problems, as a literal translation of some of their instructions, terms and LLW jargon, contained in Procedures, are not always clear to PDO personnel. The ESR requires a Contractor's Supervisor to be both responsible for the safety of his LLW Team and to ensure that any LLW they undertake is done in accordance with ESR Section 8.0. However when when checking such a Contractor's Procedure it is important to establish exactly what his Supervisor is given to understand by some of directions in the Procedure that could call, for example, for him to carry out certain SWITCHING, or remove system protection prior to certain work. Additionally does the Contractor's Supervisor have a sufficient command of English to understand Section 8.0 of the ESR and the instructions, and possibly queries that may be presented to him by an AEP? If the English translation is in places difficult to follow in a Procedure, it is important to clarify the meaning of those sections of text before allowing the Procedure to be used in PDO.
5.3
Stress Conditions of Conductors and Supports during LLW
5.3.1
General Typical calculations are given in Appendix A so that it can be seen that LLW imposes additional stresses on overhead line conductors and their supports, which in some situations create hazards not always always generally appreciated by engineers. It is not necessary for PDO personnel to carry out such calculations for all Procedures submitted by a Contractor, but only that they shall have sufficient technical appreciation and background knowledge to query any specific Procedure that appears to impose unusual loads on overhead line or substation APPARATUS.
5.3.2
Use of Wire Holding Tongs It is accepted good practice to hold a LIVE conductor by using two Wire W ire Holding Tongs so as to ensure a firm grip. In some circumstances, however, however, conductors that are in suspension may be supported with one Wire Holding Tong per conductor. The maximum load that any LLW Tool will support depends largely on the geometry of the structure, the type of LLW Tool and the conductor to be moved.
Page 92
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
5.3.3
Vers ion 10.0 10.0 Effective:Oct-10
Apparent Weight of Conductors It is most important to examine the conditions at each structure, where a conductor is to be displaced, in order to ensure that the apparent conductor weight is within the safe working load of the proposed LLW Tool arrangement. Appendix A refers.
5.3.4
Safe Work Working ing Loads for LLW Tools Some typical safe working loads of LLW Tools and combinations are given in Appendix A.
6.
Contractor's Live Line Washing Procedures
6.1
What to Look for in Contractor's LL Washing Procedures
6.1.1
General ESR Section 9.0 (LL WASHING) calls for selected Contractors to use only proven Procedures, have adequately trained experienced staff and use well maintained portable washing equipment. The Contractor's written Procedures shall shall give a reasonable guide to the methods and equipment he intends to use, and indicates whether he has a professional and safe approach to such work. The following guidelines cannot cover all aspects of LL WASHING but this Section does suggest what to look for in the technical detail of the portable washing equipment offered, and the precautions that the Contractor states he will take while carrying out such washing of HV insulators. This study of the Contractor's Procedures shall be followed by PDO personnel witnessing LL WASHING taking place so as to ensure the Contractor's personnel are using the equipment in a safe manner, and are also not subjecting APPARATUS to unnecessary hazards during the LL WASHING.
6.1.2
General Precautions for LL Washing Section 4.1 of this ESOP lists the LL WASHING simple principles, and acceptable techniques, for using portable LL WASHING equipment to clean both insulators on overhead line circuits and those in substation compounds. ESR Section 9.0 calls for specific precautions to be taken by the Contractor's Supervisor, when carrying out such work, and for the AEP to ensure that he does so. Check the Contractor's Procedures include directions that cover the requirements of the following ESR Rule numbers:(i)
Rule 9.3.3
Conductivity of water to be used and the installation of satisfactory
(ii)
Rule 9.3.4
temporary EARTH electrodes. Safe clearance distances for operator.
(iii)
Rule 9.3.5
Warning of DANGER of high winds.
(iv)
Rule 9.3.6
Only one phase to be washed at any time.
(v)
Rule 9.3.7
Avoiding accidental washing of a conductor.
(vi)
Rule 9.3.8
DANGER of lightning when LL WASHING.
(vii)
Rule 9.3.9
Protective clothing required.
6.2
Portable LL Washing Equipment
6.2.1
Hose Nozzle The nozzle for such equipment has to be such that it breaks up the jet of water into a spray, or droplets, before it hits hits the insulator supporting supporting the LIVE conductor. It is common practice to change the size of nozzle on a portable washing equipment to suit the system voltage of the conductors. The 'safety clearance distance' for the operator obviously needs to be
Page 93
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
greater for higher voltages, so the jet of water has to be 'thrown' a greater distance, but still has to provide a satisfactory 'break-up' of the jet. Check that the Contractor's Procedures identifies both the 'safety clearance distance' for the voltage of the system on which the LL WASHING is to be carried out, and also specifies the nozzle size to be used for particular equipment. It is essential that the hose nozzle is EARTHED to protect the operator if by accident leakage current of any magnitude is carried down the jet of water to EARTH. ESR Rule 9.2.3 calls for the nozzle to be bonded to EARTH by a lead of not less than 70mm 2 copper equivalents. Possibly more important, ESR Rule 9.3.3 (second paragraph) calls for the Contractor's Supervisor to install a temporary EARTH electrode when no fixed EARTH plate is available for use (e.g. LL WASHING on wood pole overhead lines). Check the Contractor's Procedures to see if there are directions for both installing an adequate temporary electrode and for making a proper connection from it onto the hose nozzle. NB:
Soil conditions often prevent the provision of low resistance earthing. In such cases it is the Contractor's responsibility to ensure that the lowest possible resistance-to-earth is achieved, so as to ensure safe working conditions for the crew. crew.
6.3
Conductivity of the Water Used for LL Washing Section 4.4 of this ESOP explains that rise in the water's temperature increases its conductivity, so close checks are necessary, both before starting the LL WASHING, and during the washing, as the day becomes hotter and the temperature of the water rises. The Contractor's Procedures shall call for these checks to be carried out and for LL WASHING to cease if the conductivity of the water increases to that stated in ESR Rule 9.3.3 or a lesser figure determined by the Contractor.
7.
PDO ESR and Live Line Working Procedures
7.1
LLW Procedures - Initiation, Progress and Completion
7.1.1
General ESR Section 8.0 - LIVE LINE WORKING contains Rules that call for LLW to be carried out by selected Contractors using proven Procedures etc. Also included in ESR Section 8.0, to assist PDO personnel who have to initiate and monitor the progress of the LLW, are Rules which are based on accepted safety standards enabling them to keep a 'watching brief' on the Contractor's LLW activities on HV APPARATUS. These Rules, for example, give dimensions for 'Safe Handling Distance Markers' to be maintained on LLW Tools, and the 'Safe Working Distances', to be observed by the LLW Team members. ESR Rule 8.3 calls for an AEP to initiate the LLW, to keep a watching brief on site during the LLW activities, and finally, finally, to inform the CP when when the work is complete. It is important to appreciate that this Rule assumes that all the work will be carried out in a continuous operation, using LLW methods and LLW Tools, only by persons in a Contractor's LLW Team.
7.1.2
ESR Considerations for a Specific Type of LLW Procedure Some Contractors' LLW Procedures call for the 'disconnection' of LIVE APPARATUS, such as overhead line conductors, disconnectors (isolators) or pole mounted transformers, by LLW methods, then to be followed by 'bare hand hand working'. This 'bare hand working' is to be done when all exposed LIVE conductors are considered, by the Contractor, to be at a 'safe distance' from the disconnected APPARATUS on which such work is to take place.
Page 94
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
This type of Procedure is not effectively covered by ESR Section 8.0, as only the 'disconnection' of the APPARATUS by the LLW Team using LLW methods and LLW Tools is catered for in those Rules. Other Sections of the ESR have also to be considered when the 'LLW part' of such a Procedure is followed by 'bare hand working'. ESR Rule 5.3 calls for all work on HV APPARATUS to be carried carr ied out under an ELECTRICAL PERMIT-TO-WORK PERMIT-TO-W ORK only after all the precautions in that Rule have been taken. The final paragraph of ESR Rule 5.3 however "any work on LIVE HV conductors or insulators shall be carried outdoes under the LIVEstate LINEthat WORKING Rules in Section 8.0". The intention of the ESR is that all work shall be carried out safely, and in particular, when work or access is necessary either on, or in the close vicinity of, LIVE HV conductors. It is then necessary to decide where work under the LLW Rules ends and which Rules shall apply for the 'bare hand working' that may follow.
7.2
Interpretation of the ESR for LLW Procedures To assist AEPs in reaching a reasonable interpretation of the ESR for LLW Procedures that may include, or may be followed, by 'bare hand working' the following guidelines shall be used:-
7.2.1
LLW Procedures with No 'Bare Hand Working' The Rules in ESR Section 8.0 shall apply if a Contractor's LLW Team carries out work on HV APPARATUS using a proven LLW Procedure in a continuous operation using LLW Tools. i.e. no 'bare hand working'.
7.2.2
LLW Procedures for Wood Pole Overhead Line Circuits The Rules in ESR Section 8.0 and ESR Rule 5.6 shall apply if a Contractor's LLW Team carries out work on a HV wood pole overhead line circuit using a proven LLW Procedure and LLW Tools to displace LIVE conductors to a position where the requirements of ESR Rule 5.6 can then be met. i.e. the SAFETY DISTANCE [ESR Rule 2.1.1] from any LIVE conductor will allow safe 'bare hand working' of the disconnected APPARATUS on the pole by the Contractor's LLW Team. If PDO personnel are then then to be used to move, or work, on the 'disconnected' piece of HV APPARATUS on the pole, then ESR Rule 7.5 shall apply and a LIMITATION-OF-ACCESS shall be issued to the CEP in charge of the work.
7.2.3
LLW Procedures for Steel Tower Overhead Line Circuits The Rules in ESR Section 8.0 and ESR Rule 5.6 shall apply if a Contractor's LLW Team carries out work on one HV circuit on a steel tower double circuit overhead line using a proven LLW Procedure and LLW Tools to displace LIVE conductors to a position where the requirements of ESR Rule 5.6 can then be met. Ie., the SAFETY DISTANCE [ESR Rule 2.1.1] from any LIVE conductor will allow safe 'bare hand working' of the disconnected APPARATUS on the tower by the Contractor's LLW Team.
7.2.4
LLW Procedures for Substations The Rules in ESR Section 8.0 and ESR Rule 5.6 shall apply if a Contractor's LLW Team carries out work in a HV substation using a proven LLW Procedure and LLW Tools to displace LIVE conductors to a position where the requirements of ESR Rule 5.6 can then be met. I.e. the SAFETY DISTANCE [ESR Rule 2.1.1] from any LIVE conductor will allow safe 'bare hand working' of the disconnected APPARATUS, in the substation, by members of the LLW Team.
Page 95
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
If PDO personnel are then to be used to move, or work, on the 'disconnected' piece of HV APPARATUS in the substation, then ESR Rule 7.5 shall apply and a LIMITATION-OF ACCESS shall be issued to the CEP CEP in charge of the work.
7.3
PDO AEPs Duties for LLW Procedures
7.3.1
Responsibility of the LLW Contractor's Supervisor The Rules in ESR Section 8.0 are written so that the responsibility for a LLW Procedure is placed on the Contractor's Supervisor. Supervisor. ESR Rule 8.1.4 states that he is responsible responsible for the safety of his LLW Team and for ensuring that the Procedure is carried out correctly and in accordance with the Rules in ESR Section 8.0.
7.3.2
Authorised Electrical Person's Role for LLW Procedures Wood Pole Overhead Line Circuits ESR Rule 8.3.3 requires the AEP to issue a LIMITATION-OF-ACCESS to the Contractor's Supervisor who is in charge of the LLW. ESR Rule 8.3.4 does allow the AEP to leave the site of the LLW taking place on wood pole overhead lines, if he appoints a CEP to represent him, with full authority to stop the work if he considers the Contractors are not working safely, i.e. to the requirements of the proven Procedure and ESR Section 8.0
7.3.3
Authorised Electrical Person's Role for LLW Procedures Steel Tower Double Circuit Overhead Lines and Substations The third paragraph of ESR Rule 8.3.4 directs the AEP to remain on site if the LLW is to take place in substations or on a circuit of a double circuit circuit overhead tower line. line. This is because these operational situations are very different to an LLW Procedure taking place on a wood pole overhead line circuit, where the dangers from the circuit's LIVE conductors are obvious, and where normally the pole to be climbed is well away from other LIVE circuits. Additionally LLW on a wood pole overhead line circuit is normally carried out in a situation that has been created virtually 'earth-free', by the LLW Contractor who shall fit suitable shrouding on the cross arm etc., whereas it is difficult to shroud all adjacent EARTHED steelwork in a 132kV substation or on a steel tower overhead line. ESR Rule 7.5 puts the responsibility on the AEP to carry out the requirements of that Rule. E.g. identify the area in the substation where the work may be carried out safely and specify how the SAFETY DISTANCES shall be maintained, etc. The intention of that Rule is that it requires an AEP with the full knowledge of the substation's exposed LIVE HV conductor layout etc.; and the full details of the work to be done, to decide how it can be carried out safely to meet the full requirements of all relevant Rules. When an LLW Procedure is to be carried out in a substation compound (or on a double circuit overhead line), the AEP shall first discuss and agree with the Contractor's Supervisor how the LLW Procedure will be carried out by the LLW Team, then issue him with a LIMITATION-OF-ACCESS. The AEP shall then remain on the site of the work and keep a 'watching brief' on the LLW. If the LLW Procedure takes place in substation compounds, it is necessary to take into account the requirements of ESR Rules Rules 5.6 and 7.5. Any LLW Procedure to be used shall at the least meet the intention of those requirements. ESR Rule 8.2.2 requires that a Safe Handling Distance Marker of 1.7m shall be maintained on all LLW LLW tools and equipment to be used for 132kV LLW. However the practical problem in substation compounds is in determining how any LLW Procedure ensures that the LLW Safe Working Distance from all LIVE conductors (not just those the LLW Team are working on) is established and maintained. In brief, the AEP shall establish from the Contractor's Supervisor how the 'safe working area' for the LLW Team members and the equipment they are using, is to be identified and defined whilst the LLW is carried out.
Page 96
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
7.3.4
Vers ion 10.0 10.0 Effective:Oct-10
Discharging Disconnected Apparatus to Earth In Substations Following LLW Procedures When HV APPARATUS has been disconnected, in a substation, using a proven LLW Procedure with LLW Tools it is prudent for the AEP to apply a portable EARTHING lead to the disconnected piece of APPARATUS before allowing the 'bare hand working' to commence. This portable EARTHING lead shall be used to discharge the completely disconnected APPARATUS to EARTH, but it does not need to remain connected to EARTH.
8.
PDO ESR and Live Line Washing Procedures
8.1
LLW Procedures Initiation, Progress and Completion
8.1.1
General ESR Section 9.0 - LIVE LINE WASHING contains Rules that call for LL WASHING to be carried out by selected Contractors using proven Procedures etc. Also included in ESR Section 9.0, to assist PDO personnel who have to initiate and monitor the progress of the work, are Rules based on accepted LL WASHING practices to enable them to keep a 'watching brief' on the Contractor's LL WASHING activities on HV APPARATUS. These Rules, for example, call for a close check to be kept on the conductivity of the water being used for the LL WASHING, the necessity for the hose nozzle to be effectively EARTHED and for the water jet to be broken up into a spray, or droplets, before it hits the insulator carrying an exposed LIVE conductor. ESR Rule 9.3 calls for an AEP to initiate the LL WASHING, to keep a watching brief on site during the LL WASHING activities, and finally, to inform the CP when the work is complete.
8.1.2
ESR Considerations for LL Washing Procedures The Rules in ESR Section 9.0 are as comprehensive as is practicable, but no 'safety clearance distances' are included and ESR Rule 9.3.4 lists the variables that have to be taken into account when 'positioning' the LL WASHING operator. The intention of the ESR is that all work shall be carried out safely when access is required to carry out LL WASHING in the close vicinity vicinity of exposed LIVE HV HV conductors. However if the Rules in ESR Section 9.0 are followed by the Contractor's Supervisor, in agreement with the AEP it should not be necessary to consult other Sections of the Rules.
8.2
Application of the ESR for LL Washing Procedures To assist AEPs who has to monitor LL WASHING Procedures the following guidelines may be of some help.
8.2.1
LL Washing Team's Equipment When looking at the Rules in ESR Section 9.0, in relation to the internationally accepted principles for LL WASHING equipment [see Section 4.0 of this ESOP], it is clear that the relevant points are covered. ESR Rule 9.2.2 covers the selection of nozzle size and design of the equipment to be provided, and ESR Rules 9.2.3 and 9.3.3 call for the nozzle nozzle to be effectively EARTHED. EARTHED. The second paragraph of ESR Rule 9.3.3 calls for the Contractor's Supervisor to provide a temporary EARTH electrode, where necessary, and to check it is installed so that its resistance to EARTH provides adequate protection for the hose operator. The water pressure at the nozzle cannot be specified in the Rules as it will depend on the portable equipment to be used. ESR Rule 9.2.2 calls for the water to be in 'a spray' before reaching the insulator, which effectively means that the water shall be at no greater pressure than to meet that requirement. Finally the ESR Rule 9.3.3 calls for the water conductivity to
Page 97
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
be less than 400S/cm and calls attention to the DANGER of a rise in temperature affecting the conductivity of the water. ESR Rule 9.2.1 calls for monitoring devices to be on site to enable the water conductivity to be checked, before and during the LL WASHING. If the Contractor's Supervisor can satisfy the AEP that his portable washing equipment can meet all these requirements, then the Team should be able to carry out LL WASHING in a satisfactory manner working to their proven Procedure and the Rules in ESR Section 9.0. 8.2.2
LL Washing Procedures for Overhead Lines The Rules in ESR Section 9.0 apply if a Contractor's LL WASHING Team carries out insulator washing on an HV wood pole overhead line circuit using a proven LL WASHING Procedure and LL WASHING equipment. The operator shall be told told to position himself at a safe distance from LIVE conductors and particularly to observe ESR Rules 9.3.4, 9.3.5, 9.3.6 and 9.3.7. The Rules in ESR Section 9.0 equally apply if a Contractor's LL WASHING Team carries out insulator washing on an HV circuit on a steel tower double circuit overhead line using a proven LL WASHING Procedure and taking care when positioning himself to allow for the LIVE conductors of the other circuit and the the direction of the wind. The operator shall be told to take extra care to position himself at a safe distance from all LIVE conductors on the tower and particularly to observe ESR Rules 9.3.4, 9.3.5, 9.3.6 and 9.3.7.
8.2.3
LL Washing Procedures for Substations The Rules in ESR Section 9.0 apply if a Contractor's LL WASHING Team carries out insulator washing in in a HV substation substation using a proven proven LL WASHING Procedure. The operator shall be told to take extra care to position himself at a safe distance from all LIVE conductors in the substation and particularly to observe ESR Rules 9.3.4, 9.3.5, 9.3.6 and 9.3.7. In addition ESR Rule 7.5 shall be taken into account by the AEP if the LL WASHING equipment has to be stationed inside the substation compound while the insulator washing is carried out. The operator shall be told if there is specific APPARATUS in the substation, on the overhead line terminal poles or structures that shall not have water sprayed upon it.
8.2.4
PDO Authorised Electrical Persons Duties Prior and During LL Washing Procedures The Rules in ESR Section 9.0 are written so that the responsibility for an LL WASHING Procedure is placed placed on the Contractor's Supervisor. ESR Rule 9.1.4 states that he is responsible for the safety of his LL WASHING Team and for ensuring that the Procedure is carried out correctly and in accordance with the Rules in ESR Section 9.0. ESR Rule 9.3.2 requires the AEP to issue a LIMITATION-OF-ACCESS to the Contractor's Supervisor who is is in charge of the LL WASHING. ESR Rule 9.3.2 does allow the AEP to leave the site of the LL WASHING taking place on wood pole overhead lines, if he appoints a CEP (this (this person can be the LLWashing crew leader ) leader ) to represent him, with full authority to stop the work if he considers the Contractors are not working safely. i.e. to the requirements of the proven Procedure and ESR Section 9.0. The AEP shall satisfy himself before leaving the site that the guidelines in Sections 8.1 and 8.2 of this ESOP are being followed by the Contractor's LL WASHING W ASHING Team. The fourth paragraph of ESR Rule 9.3.2 directs the AEP to remain on site if the LL WASHING is to take place in substations or on one circuit of a double circuit overhead tower line. This is because these operational situations are very different to an LL W ASHING Procedure taking place on a wood pole overhead line circuit, where the dangers from the circuit's LIVE conductors obvious. shall remain on thebeing site ofsatisfied the insulator and keep a 'watchingare brief' on theThe LL AEP WASHING Procedure that washing the guidelines in Sections 8.1 and 8.2 of this ESOP are being followed.
Page 98
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
APPENDIX A A
APPARENT APPA RENT WEIGHT OF CONDUCTORS i) At an intermediate position, position, providing the conductors have no declination on the working structure, the apparent weight of the conductor is a function of the unit weight of the conductors and half the sum of the span lengths of either side of the pole. W ½*m*(S1 + S2) [kg], where W is the apparent conductor weight in [kg] m is the specific conductor weight in [kg/m] S1 & S2 are the span lengths on either side in [m] ii) When moving the conductor conductor upwards during LLW the apparent conductor weight is increased. In order to introduce a safety factor to cover this, the total weight of the sum of the two spans either side of the structure is normally allowed. Therefore various conductor weights can be derived from the expression:W = m*(S1 + S2) [kg] iii)If there is a declination of the line at the working structure the apparent conductor weight can be considerably increased by the tension in the conductors at this position. W m*(S1 +S2) + T*[sin( ) + sin( )] [kg], where T is the conductor tension in [kg] and are the angles of declination on each side of the structure
(negative values are valid for positions of positive inclination. i.e. uplift)
SAFE WORKING LOADS FOR LLW TOOLS Typical safe working loads of LLW Tools and combinations currently in use are as follows:i)
Safe Work Working ing Loads for Wire Holding Tongs 39mm dia. Tong:
550Nm (55kgm) in Cantilever; 770kg in Tension.
64mm dia. Tong:
2050Nm (205kgm) in Cantilever; 1150kg in Tension.
Typical safe operating conditions for these Tools (normally used in pairs) are that a 64mm * 3m Wire Tong used as a lifting tong with a 39mm * 2.4m Wire Tong used as a holding tong, both attached with saddles, will move a vertical load of 100kg. If the rig is strengthened with a rope block attached to a Wire Tong band 750mm down the 64mm Tong, the permissible load will be increased to 2l5kg. If the saddles are replaced with Lever Lifts the permissible load with the rope blocks will be increased to 270kg.
Page 99
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
ii)
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
Safe Working Loads (SWF) for Other LLW Tools TOOL
SWF [kg]
TOOL TOOL
SWF [kg]
Wire Tong Saddle
250
Lever lift on Wire Tong
450
Link stick 32mm dia. (strain)
1200
Link stick 39mm dia. (strain)
2150
Link stick 32mm dia. (roller)
380
Wire Tong Saddle with extensions Rope snubbing bracket Lever lift two Wire Tongs
iii) Rope Blocks When using rope blocks attached to a Wire Tong pole saddle shackle, the load to be applied to the saddle shall include the loading in the fall rope.
Page 100
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
ESOP – 23 ESOP-23 IDENTIFICATION OF HIGH OR LOW VOLTAGE ESOP-23 SWITCHGEAR SUBJECT TO AN OPERATIONAL RESTRICTION 1.
Objectives
1.1
This ESOP has been issued to ensure that any unit of HV or LV switchgear (or any other electrical APPARATUS), which may be subject to a PDO operational restriction, is readily identifiable to any person before he attempts to carry out any operations on such units.
1.2
Any units subject to an operational restriction are only operated in such a way that does not place personnel in DANGER or present a hazard to APPARATUS.
2.
PDO Policy
2.1
The CFDH-E shall issue a specific ELECTRICAL SAFETY OPERATIONAL PROCEDURE (ESOP 'S' category) for any type of HV or LV switchgear (or any other electrical APPARATUS) when it is known from PDO operating experience, information inform ation received from SIPM, other Shell Operating Companies, Consultants or manufacturers that such units may place in DANGER personnel carrying out operations on them.
2.2
The ESOP shall state the operational restriction that shall apply to the units affected and may call for certain operations on them to be conducted in a specific manner (eg., closing of a circuit breaker from a remote position only).
2.3
A Plant Restriction marker label shall be fitted to all units of switchgear which are subject to any type of PDO operational restriction imposed by the CFDH-E. This marker label used to identify a switch (or any other APPARATUS) subject to an operational restriction shall be a yellow square, self adhesive and have the words "PLANT RESTRICTION" printed on on it. [see Appendix A]
2.4
The Plant Restriction marker label shall only be used in accordance with this ESOP.
3.
Action Required on PDO Sites
3.1
Following the issue of an ESOP imposing an operational restriction on specified units of switchgear (or any other electrical APPARATUS), the Plant Restriction marker label shall be fixed in a prominent position on all the units of that type. It shall be clearly visible to anyone anyone intending to operate the switchgear unit.
3.2
The Plant Restriction marker label shall be used only on switchgear (or other electrical APPARATUS) which is the subject of an operational restriction imposed by an ESOP, or preliminary warning instruction, such as a telex or an ESB originating only from the CFDH-E. The Plant Restriction marker label shall not be used for any other purpose.
3.3
Care must be taken when fitting the marker label to ensure that the surface, upon which the label will be fixed, is clean and free from oily substances. To ensure a good fixing, the surface should first be wiped over with a de-greasing agent, e.g. methylated spirits.
4.
Operation of Units Subject to an Operational Restriction
4.1
Prior to operating any PDO HV or LV switchgear unit the person who is to carry out operations on it shall check if a Plant Restriction marker label is fixed to the unit. If such a marker label is fitted, no operations shall take place until that person has read the ESOP imposing the operational restriction and checked that he can operate the unit in accordance with the precautions, or additional operating procedures, called for in that ESOP.
Page 101
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
5.
Removal Of A PDO Operational Restriction
5.1
Plant Restriction marker labels shall only be removed from APPARATUS when the CFDH-E revises and reissues the relevant ESOP ('S' category) that called for the operational restriction to be imposed. The revised ESOP shall state what modifications to the APPARATUS, special checks, or other course of action is necessary before the operational restriction can be lifted and the marker label removed.
Page 102
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
APPENDIX- A A
PLANT RESTRICTION MARKER LABEL LABEL
PLANT RESTRICTION Refer to ESOP _____________
Black letters on a Yellow background
Page 103
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
23. ESOP – 23/S1 ESOP-23/S1 OPERATIONAL RESTRICTION ON HOLEC CAPITOLE 3 ESOP-23/S1 OPERATIONAL AND 3N LOW VOLTAGE SWITCHBOARDS SW ITCHBOARDS
1.
Background to Restriction An Electrical Technician suffered an accident while he was replacing a fuse on a 415V switchboard of this type. type. While he was inserting the fuse, back into the switchboard, switchboard, one end of it accidentally touched a second LIVE phase or EARTH, resulting in a flashover which caused the injuries. Fuses on this type type of switchboard are fitted on the LIVE side of the isolator. In the design followed for Starter feeders, the draw out type starter feeders rated 5.5kW & less; do not have an isolator in the individual feeders. Isolation of power is presently done by withdrawing the modules. This type of switchboards is presently in operation in Qaharir and other Marmul area Gathering Stations. There may be some isolated cases where the contacts of the contactor are welded and the module is attempted to be withdrawn under these circumstances. This may cause a safety hazard and accident. The following operational restriction shall apply until this ESOP is replaced or cancelled by the CFDH-E.
2.
Operational Restriction WHEN FUSES ARE REMOVED OR REPLACED ON HOLEC CAPITOLE 3 & 3N LV SWITCHBOARDS THE ADDITIONAL PROCEDURES AND PRECAUTIONS DETAILED BELOW SHALL BE FOLLOWED:- FOLLOWED:-
2.1
THE SWITCHING OPERATIONS SHALL BE CARRIED OUT BY A CESP WHO SHALL BE ACCOMPANIED BY A CEP. CEP.
2.2
THE CESP SHALL WEAR APPROVED ELECTRICAL RUBBER GLOVES. [see ESOP 24] 24]
2.4
THE CEP SHALL WEAR AN ULTRAVIOLET PROTECTION FACE SHIELD AND INFRARED PROTECTING GLASSES. [see ESOP 24] 24]
2.5
THE CESP SHALL USE A SUITABLE FUSE EXTRACTOR FOR THESE SWITCHING OPERATIONS. OPERATIONS. Note: Note:
2.6
This restriction applies unless the SWITCHING operations are to be carried out on a Holec Capitole 3 or 3N switchboard unit that has been made DEAD, or the fuses to be removed or replaced have been made DEAD and there are no exposed LIVE conductors adjacent to the fuse bases.
For proper & safe isolation of STARTER modules (RATED BELOW 5.5KW), the following steps shall have to be adhered to. All other applicable
PERSONNEL PROTECTION RESTRICTIONS, PRESCRIBED IN OTHER SOPS, SHALL ALSO BE FOLLOWED.
OPEN THE CONTACTOR BY PRESSING MCC DOOR MOUNTED STOP/OPEN PUSH BUTTONS.
Page 104
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
CHECK PHYSICALLY IF THE MOTOR HAS STOPPED. THIS ENSURES THAT THE CONTACTOR HAS OPENED IT’S CONTACTS.
OPEN THE SWITCH FOR CONTROL CIRCUIT ISOLATION.
OPEN THE MODULE DOORS.
AS PER THE DESIGN, AS SOON AS THE MODULE DOOR IS OPENED, THE MODULE GETS ISOLATED AND THE POWER CONTACTS GET
DISCONNECTED. THEN REMOVE THE FUSES. FUSES.
3.
Requirements Of ESOP 23
3.1
ESOP 23 paragraph 3.0 calls for a 'Plant Restriction' marker label to be fixed in a prominent position on all Holec Capitole 3 & 3N switchboards of this type.
3.2
ESOP 23 paragraph 4.0 requires all 'electrical personnel', before undertaking any SWITCHING operations on a unit of plant that has a 'Plant Restriction' marker label fixed to it, to first read the relevant category 'S' ESOP, detailing the operational restriction that applies, and check that they can operate the unit in accordance with the precautions called for in that special ESOP.
Page 105
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
24. ESOP – 24 ESOP-24
PROVISION OF MISCELLANEOUS SAFETY EQUIPMENT FOR OPERATIONAL PURPOSES
1.
Objectives
1.1
To ensure that suitable and APPROVED safety equipment is available for use when SWITCHING, work or testing is carried out on HV and LV APPARATUS on PDO sites.
1.2
To ensure that reasonable inspections are carried out on such miscellaneous safety equipment to meet the requirements of Petroleum Development Oman LLC, Shell Safety Recommendations and any statutory legislation applicable in the Sultanate of Oman. Om an.
2.
Purpose of the ESOP
2.1
To detail the miscellaneous safety equipment that PDO will provide for use in both HV and LV substations.
3.
Relevant Requirements of the ESR
3.1
ESR Rule 5.4.3 calls for the use of APPROVED equipment to be used when carrying out testing or adjustments on LIVE LV APPARATUS.
3.2
ESR Appendices B, PDO. C, D & E give details of the ELECTRICAL SAFETY DOCUMENTS that shall be provided by
4.
Provision of Safety Equipment Called for by other ESOP
4.1
ESOP 2 gives details of SAFETY PADLOCKS and the KEY SAFES that shall be provided at PDO sites.
4.2
ESOP 5 gives details of the APPROVED voltage testing devices that shall be used.
4.3
ESOP 6 gives details of portable EARTHING leads and operating rods for applying them.
4.4
ESOP 10 gives details of cable identification and spiking equipment that shall be used.
4.5
ESOP 12 calls for CAUTION, DANGER and EARTHED NOTICES to be provided in substations in accordance with ESR Appendix A. ESOP 12 calls for all major substations containing oil filled switchgear to be provided with a fire proof blanket.
4.6
ESOP 23 gives details of Plant Restriction marker labels that shall be fixed to switchgear that is subject to a PDO operational restriction.
5.
Provision and Inspection of Approv Approved ed Insulated Tools
5.1
Insulated tools for live line working shall conform to the following standards:
5.2
IEC 6832 Insulating poles (insulating sticks) and universal tool attachments (fittings) for live working
IEC 6900 Hand tools for live working up to 1000Vac and 1500Vdc
Insulated tools shall be inspected conform the above standards, but at least on a yearly basis to ensure that they have not been damaged or misused.
Unless a tool is badly damaged, or the insulation has been deliberately 'cut back', there should be no need to subject these insulated tools to further electrical tests during their lifetime. Page 106
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
6.
Provision, Storage and Testing of Appro Approved ved Electrical Rubber Gloves
6.1
Electrical rubber gloves shall conform to and be maintained and re-tested to:
BS 697 Specification for Rubber Gloves for Electrical Purposes. Each pair of gloves shall be supplied with a Test Certificate.
6.2
LV gloves for use up to 1000V shall be provided for testing or adjustment purposes on, or in the near vicinity, vicinity, of LIVE LV conductors. [see ESR Appendix A] HV gloves for use when operating in accordance with ESR Rule 5.2.1.5 shall be provided. [see ESR Appendix A]
6.3
Each pair of gloves shall be kept unfolded in a plastic bag containing talc. The plastic bag may in turn be kept in a suitable box or container to ensure that the gloves are not exposed to mechanical or chemical damage. Gloves shall be kept dry, free of grease, oil and shall not be exposed to unnecessary heat or o o light. Storage temperatures for preference shall be from 10 C to 21 C.
6.4
Gloves which become soiled shall be thoroughly washed with soap and water, dried and then dusted with talc. Do not use petroleum based solvents for cleaning dirty dirty gloves.
6.5
Immediately before use, each pair of gloves shall be examined for flaws or defects. If either of the gloves appears to be unduly worn or damaged in any way, the pair shall be immediately withdrawn from service.
6.6
Gloves regularly used shall be taken out of service six clear calendar months after their last certification date. The gloves shall then be sent for re-testing. Gloves used infrequently, or stored for emergency use only, shall be sent for re-testing twelve clear calendar months after their last certification date.
6.7
A register recording the issue and re-testing shall be kept at all PDO sites or at a PDO Area Office.
7.
Provision of Eye Protection for Use When Switching
7.1
Where operating instructions have been issued calling for eye protection to be worn when carrying out specific SWITCHING on LV switchboards, the following equipment shall be provided: Safety Spectacles for Infra Red Protection Visors and Brow guards for Ultra Violet Light Protection
Both items shall comply com ply with the following standard: BS 2092
8.
Specification for eye-protectors for industrial and non-industrial uses
Flexible Leads for Use with Portable Voltage Operated Instruments Paragraphs 8.1 & 8.2 of this ESOP take into account the UK HSE Guidance Note GS 38 'Electrical Test Equipment for use by Electricians'.
8.1
Permanently Attached Leads These guidelines shall be used when purchasing instruments fitted with permanently attached leads.
8.1.1
This type of lead is permanently attached to instruments such as clip-on wattmeter, phase rotation indicators and test lamps [i.e. voltage testing devices] where the fused leads are terminated inside the instrument.
8.1.2
These leads shall be fitted with an insulated fused holder having an attached insulated test prod or insulated terminal clip. The holder shall have a finger shield fitted to safeguard the
Page 107
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
user from making accidental contact with LIVE metal. The test prod must be insulated and have a minimum of exposed metal at the tip. 8.1.3
Where not more than two fused leads are required for any one instrument the insulated holders shall be fitted with insulated test prods. Where three leads are required, e.g. phase rotation indicators, two fused leads shall be provided with insulated test prods and the third with an insulated crocodile crocodile clip. The crocodile clip shall be enclosed within a silicone rubber or similar suitable sheath so as to expose a minimum of metal. For normal single or twin fuse lead connections, crocodile clip terminations shall not be used.
8.2
Temporarily Attache Attached d Leads Existing instruments using 'temporarily attached leads' shall be fitted with leads conforming to those specified below.
8.2.1
This type of flexible lead is temporarily connected to instruments such as voltmeters where the fused leads are fitted to terminals mounted on the instrument case.
8.2.2
The instrument termination for this type of lead shall be a hook-type spade terminal with brass cable grip extensions, or insulated insulated push-in connectors. The cable grip extensions will be fully insulated and adequately clamped to the flexible cables.
8.2.3
The leads shall be fitted with an insulated fused holder similar to that for permanently attached leads. The holder shall be fitted fitted with an insulated test prod. Note:
8.3
The attached sketch in Appendix-A gives illustrations of some types of 'temporarily attached leads'.
Fuses for Flexible Leads These design specifications for fuses in flexible leads are based on an Electricity Council Chief Engineers Conference Conference Recommendation. UK manufacturers of such leads are normally well aware of these requirements.
8.3.1
Page 108
Each fuse fitted in a flexible lead shall have a current rating not exceeding 1.0A and an internal resistance of less than 5 and a breaking capacity adequate for a prospective fault current of 46kA at 600V ac and 33kA at 600V dc. When a fused test prod is carrying carrying a continuous current of 0.5A, the maximum temperature rise of any component part shall not o exceed 40 C.
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
APPENDIX A A – – FUSED FLEXIBLE TEST LEADS FOR PORTABLE INSTRUMENT
Page 109
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
PR 194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
25. ESOP – 25 ESOP-25
PREPARATION, ISSUE, CLEARANCE, CANCELLATION AND RETENTION OF ELECTRICAL SAFETY DOCUMENTS
1.
General
1.1
This ESOP is issued to provide simple basic guidelines for SAEPs and AEPs who have to prepare, issue and cancel ELECTRICAL SAFETY DOCUMENTS as part of their operational duties.
1.2
The ESR defines ELECTRICAL PERMITS-TO-W PERMITS-TO-WORK, ORK, SANCTIONS-FOR-TEST, LIMITATIONS-OF-ACCESS and ELECTRICAL ISOLATION/DE-ISOLATION CERTIFICATES as ELECTRICAL SAFETY DOCUMENTS. [see ESR Rule 2.1.2]
1.3
ELECTRICAL PERMITS-TO-W PERMITS-TO-WORK ORK are normally only for use on HV APPARATUS and shall be prepared, issued and cancelled by SAEPs or AEPs.
1.4
SANCTIONS-FOR-TEST are for use on HV APPARATUS and shall be prepared, issued and cancelled only by SAEPs.
1.5
LIMITATIONS-OF-ACCESS are for use when access is required to carry out work or inspections in the vicinity of LIVE HV APPARATUS and shall be prepared, issued and cancelled by SAEPs or AEPs. A LIMITATION-OF-ACCESS is issued for this purpose when verbal instructions are not considered sufficient, or when a specific Rule calls for one to be issued (e.g. LLW activities).
1.6
LIMITATIONS-OF-ACCESS are also issued when access is required to carry out work or inspections in the vicinity of LIVE LV and shall be prepared, issued and cancelled by SAEPs or AEPs. A LIMITATION-OF-ACCESS is issued for this purpose when verbal instructions are not considered sufficient.
1.7
LIMITATIONS-OF-ACCESS are also issued to allow work on ISOLATED LV APPARATUS when verbal instructions are not considered sufficient. Note: Note:
ELECTRICAL ISOLATION/DE-ISOLATION CERTIFICATES are not included in this ESOP as other documents call for their issue, etc., by the Custodian for his equipment. equipment.
2.
Use of Electrical Safety Documents
2.1
PDO ELECTRICAL SAFETY DOCUMENTS are prepared in a book form, pre-numbered, with a top sheet [white] [white] and two copies copies [blue and pink] immediately underneath. Special paper has been used so that details entered on the top sheet will be reproduced on both the copies beneath without without the use of carbon paper. paper. Provision has been been made so that both both white and blue copies can be easily 'removed' from the books.
2.2
When the SAEP or AEP has completed the Issue Section of the ELECTRICAL SAFETY DOCUMENT and is satisfied that the recipient has afterwards correctly completed the Receipt Section, the top sheet shall be removed and given to the recipient, r ecipient, who shall retain it until he has completed the work, or testing, and is ready to sign the Clearance Section.
2.3
The SAEP or AEP) issuing the ELECTRICAL SAFETY DOCUMENT shall record the time and date of its issue on the relevant SWITCHING PROGRAMME.
2.4
The blue copy of the ELECTRICAL SAFETY DOCUMENT shall be left in the book unless the SAEP or AEP requires the copy for putting in the local Control Room for information
2.5 Page 110
purposes. The pink copy of the ELECTRICAL SAFETY DOCUMENT shall be left in the book. Printed 17/09/13
PR 194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
2.6
When the recipient is ready to sign the Clearance Section of the ELECTRICAL SAFETY DOCUMENT, the SAEP or AEP shall place the top white copy on top of the copies still retained in the book. The recipient shall then complete the Clearance Clearance Section and the SAEP or AEP shall then complete the Cancellation Section of the document.
2.7
The SAEP or AEP cancelling the ELECTRICAL SAFETY DOCUMENT shall record the date and time of its cancellation in the site electrical log book or on the relevant SWITCHING PROGRAMME.
2.8
The SAEP or AEP cancelling the ELECTRICAL SAFETY DOCUMENT shall then remove all the copies of that ELECTRICAL SAFETY DOCUMENT from the book, staple them both together and place them in the appropriate file [see note] in the PDO site storage system. Note: Note:
Each type of cancelled ELECTRICAL SAFETY DOCUMENT i.e. ELECTRICAL PERMITS-TO-WORK, SANCTIONS-FOR-TEST and LIMITATIONS-OF-ACCESS shall each have a separate storage file provided for their secure retention on site. site.
3.
Preparation of Electrical Safety Documents
3.1
All entries on an ELECTRICAL SAFETY DOCUMENT shall be clearly hand 'printed' in ink. Some handwriting is difficult to read and could be misread by the recipient, or one of his WORKING PARTIES.
3.2
Full entries shall be made against all statements on an ELECTRICAL SAFETY DOCUMENT. For example, when an ELECTRICAL PERMIT-TO-W ORK is issued on a 132/33kV Transformer:POINTS AT WHICH THE APPARATUS HAS BEEN ISOLATED AND WHERE CAUTION NOTICES HAVE BEEN POSTED: POSTED: ISOLATOR A114 33kV C.B. C180 WITHDRAWN FROM SERVICE POSITION SPOUT SHUTTERS OF RACKED-OUT VOLTAGE TRANSFORMER DANGER NOTICES ATTACHED AT: AT: BUSBAR SPOUT SHUTTERS OF 33kV C.B. C180 STRUCTURE ADJACENT TO LIVE SIDE OF ISOLATOR A114 CMEs APPLIED AT: AT: CONDUCTORS ON TRANSFORMER SIDE OF ISOLATOR A114 33kV C.B. C180 CLOSED TO EARTH IN FEEDER SPOUTS
3.3
If a statement on the ELECTRICAL SAFETY DOCUMENT does not apply, print 'NONE'.
3.4
Where the ELECTRICAL SAFETY DOCUMENT calls for one statement to be deleted, always cross out the one that does not apply.
3.5
'Ditto' signs, denoting the text is the same as the line above, shall not be used on ELECTRICAL SAFETY DOCUMENTS.
3.6
Always record the number of sets of AEs issued to the recipient of an ELECTRICAL PERMIT-TO-WORK or SANCTION-FOR-TEST.
3.7
Be careful to record on an ELECTRICAL PERMIT-TO-W ORK or SANCTION-FOR-TEST the name of the CP who is agreeing to the issue or cancellation of the document.
3.8
Always check that the entry details on the top sheet of the ELECTRICAL SAFETY DOCUMENT are clearly reproduced on the two copies beneath.
3.9
The LIMITATION-OF-ACCESS can be issued for a variety of work purposes, or access requirements [see 1.5, 1.6 & 1.7 of this ESOP], within the scope of the PDO ESR. It is important that the SAEP or AEP, when hand printing the entries, makes very clear the purpose, and limits, of the work or access that is allowed under the LIMITATION-OF ACCESS they are issuing. issuing.
Page 111
Printed 17/09/13
PR 194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
4.
Issue of Electrical Safety Documents
4.1
Electrical Permits-to-Work
4.1.1
After the recipient has read the ELECTRICAL PERMIT-TO-W ORK to the SAEP or AEP, it is important to check that he clearly understands the written entries and what work he is to carry out.
4.1.2
The SAEP or AEP shall impress on the recipient that he shall tell all persons working with him, under this ELECTRICAL PERMIT-TO-WORK, exactly what work is to be carried out and the limits and extent of that work.
4.1.3
Make sure the recipient checks and and counts the number of AEs he is issued with, for work on overhead lines, under the ELECTRICAL PERMIT-TO-WORK.
4.1.4
Finally before the recipient signs the ELECTRICAL PERMIT-TO-W ORK it is good operational practice for the SAEP or AEP to demonstrate to the CEP that 'safe working conditions exist'. The recipient shall at the site of the work, be shown the precautions that have been taken including the 'locked off' ISOLATION points with SAFETY PADLOCKS, KEY SAFES, CAUTION, DANGER & EARTHED NOTICES and the position of the CMEs and any LV EARTHS. Where it is practicable the SAEP or AEP shall shall touch the EARTHED conductors of the APPARATUS to show it is safe to work on under this ELECTRICAL PERMIT-TO-WORK.
4.2
Sanctions-for-Test
4.2.1
After the recipient has read the SANCTION-FOR-TEST to the SAEP it is important to check that he clearly understands the written entries. Check he knows which which CMEs he may remove when carrying out the testing required by the SANCTION-FOR-TEST and that he understands that under no circumstances shall he reconnect the ISOLATED APPARATUS to the electrical system under the SANCTION-FOR-TEST.
4.2.2
Make sure the recipient checks and counts the number of AEs he is issued with, if he requires any under the SANCTION-FOR-TEST.
4.2.3
The SAEP shall impress on on the recipient that he shall tell all persons testing with him, under this SANCTION-FOR-TEST, exactly the testing which is to be carried out and the limits and extent of the testing.
4.2.4
Finally before the recipient signs the SANCTION-FOR-TEST it is good operational practice for the SAEP to demonstrate to the recipient (the AEP) that 'safe testing conditions exist'.
4.2.5
The recipient recipient shall at the site of the work be shown the precautions that have been taken including the 'locked off' ISOLATION points with SAFETY PADLOCKS, KEY SAFES, CAUTION, DANGER & EARTHED NOTICES and the position of the CMEs. Where it is practicable the SAEP shall touch the EARTHED conductors of the APPARATUS to show it is safe to test under this SANCTION-FOR-TEST.
4.3
Limitations-of-Access
4.3.1
After the recipient has read the LIMITATION-OF-ACCESS to the SAEP or AEP, it is important to check that he clearly understands what work or access is allowed.
4.3.2
The SAEP or AEP shall impress on the recipient that he shall tell all persons working with him, under this LIMITATION-OF-ACCESS, exactly what work is to be carried out and the limits and extent of the work, or access allowed.
5.
Cancellation of Electrical Safety Documents
5.1
Electrical Permits-to-Work
5.1.1
It is important that when cancelling ELECTRICAL PERMITS-TO-W ORK that the SAEP or AEP checks the 'Clearance Section' has been completed by the recipient, to establish if the work is complete and the APPARATUS is in the condition he expects it to be.
Page 112
Printed 17/09/13
PR 194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
5.1.2
The SAEP or AEP shall always check that all AEs have been 'taken off' and the number of sets returned by the recipient agrees with the number shown as having being issued on the ELECTRICAL PERMIT-TO-WORK.
5.1.3
The SAEP or AEP shall make a visual check to see if the work has been completed on the APPARATUS and that it is in a satisfactory condition to be restored to service.
5.2
Sanctions-for-Test
5.2.1
It is most important that when cancelling SANCTIONS-FOR-TEST that the SAEP checks the 'Clearance Section' has been completed by the recipient, to establish if the testing is complete and the APPARATUS is in the operational condition he expects it to be. In particular, have all the CMEs been re-applied following the testing?
5.2.2
The SAEP shall always check that that all AEs have been 'taken off' and the number of sets returned by the recipient agrees with the number shown as having being issued on the SANCTION-FOR TEST.
5.2.3
The SAEP shall make a visual check to see if the testing has been completed on the APPARATUS and that it is in a satisfactory condition to be restored to service.
5.3
Limitations-of-Access
5.3.1
It is important that when cancelling LIMITATIONS-OF-ACCESS that that the SAEP or AEP checks the 'Clearance Section' has been completed by the recipient, to establish if the work is complete and any APPARATUS involved is in the condition he expects it to be.
5.3.2
The SAEP or involved AEP shalland make to seecondition. if the work has been completed on any APPARATUS thataitvisual is in acheck is satisfactory
5.3.3
If the LIMITATION-OF-ACCESS was was issued only to allow access, a check shall be made to ensure that all the gates or doors been locked etc.
6.
Retention of Electrical Safety Documents
6.1
Cancelled ELECTRICAL SAFETY DOCUMENTS shall be retained in their site storage file for a minimum period of two years after the date of their cancellation. This system shall ensure that when ELECTRICAL SAFETY DOCUMENTS are issued and cancelled they can be easily and regularly monitored, by SAEPs or AEPs and if necessary can be produced for inspection by internal management or external Audit Teams.
6.2
Page 113
Printed 17/09/13
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Petroleum Development Oman LLC
Vers ion 10.0 10.0 Effective:Oct-10
APPENDIX A A – – DEFINITIONS, ABBREVIATIONS ABBREVIATIONS & REFERENCE INDICATORS A-1
General Terminology
For the purposes of this document the following definitions shall be used. (The) Company
-
Petroleum Development Oman LLC of Muscat, Sultanate of Oman
Consultant
-
A party to a Contract with The Company who is responsible for providing design, engineering, and other related consultancy services under a Contract.
Contractor
-
A party to a Contract with The Company responsible for maintenance, construction and other related works specified in a Contract. On occasion, for example in 'turnkey or EPC contracts', a contractor may be responsible for the duties of both Consultant and Contractor.
Direct Supervision -
Supervision by a person suitably authorised for that function, which is continuously present at the work site to personally supervise the work without intermediaries.
Manufacturer
-
A party responsible for the manufacture of equipment or material to perform duties specified by a Consultant or the Company
May
-
The word 'may' is to be understood as indicating a possible course of action.
Operations
-
A generic term indicating the party to which electrical maintenance and utility staff report to.
Shall
-
The word 'shall' is to be understood as mandatory.
Should
-
The word 'should' is to be understood as strongly recommended.
User
-
A specified engineer or Consultant who applies these standards in the execution of a PDO project.
Vendor/Supplier
-
A party responsible for supply of equipment, materials or productrelated services in accordance with a Purchasing Office.
Page 114
Printed 17/09/13
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
A-2
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
Abbreviation
AE
-
Additional Earth
AEP
-
Authorised Electrical Person
AP
-
Appointed Person
BS CEP
-
British Standard Competent Electrical Person
CESP
-
Competent Electrical Switching Person
CFDH-E
-
Corporate Functional Discipline Head Electrical
CME
-
Circuit Main Earth
CofA
-
Certificate of Appointment
CP
-
Control Person
ELV
-
Extra Low Voltage
EMC
-
Engineering Maintenance Contract
EP
-
Electrical Person
EPC
-
Engineer, Procure & Construct contract
ESB
-
Electrical Safety Bulletin
ESOP
-
Electrical Safety Operational Procedure
ESR
-
Electrical Safety Rule
HSESM HSESM
-
Health Safety Health Safety Environmental Environmental Protection Protection Standards Standards Manual
HV
-
High Voltage
IEC
-
International Electrical Committee
LLW
Live Line Work
LL Washing
-
Live Line Washing
LV
-
Low Voltage
MEDC
Muscat Electricity Distribution Company SAOG
MJEC MZEC
-
Majan Electricity Company SAOG Mazoon Electricity Company SAOG
OETC
-
Oman Electricity Transmission Company SAOC
OPWP
-
Oman Power and Water Procurement Company SAOC
ORPC
-
Oman Refinery and Petrochemicals Company LLC
PAP
-
Procedure for Appointed Person
PDO
-
Petroleum Development Oman LLC
SAEP
-
Senior Authorised Electrical Person
SAP
-
Systems, Applications and Products
SOP
-
Switchgear Operating Procedures
SRD
-
Safety Reference Document
Page 115
Printed 17/09/13
Page 115
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
Printed 17/09/13
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
A-3
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
PDO GENERIC JOB TITLES & REFERENCE INDICATORS
For the purposes of this document the following generic job titles are defined, along with the current reference indicator(s) PDO GENERIC JOB TITLE
REF. INDICATOR
Corporate Functional Discipline Head Electrical Head Integrity & Standards, Power Systems
UIE UIE / 4
Operations Electrical Support Engineer
UIE / 3S
Head of Power System Operations
UIE / 3 , UIB/1
Head of Operations
ONO, OSO, UIB
Area Operations Electrical Supervisor
ONO/42L, ONO /42Q, ONO /42F, ONO/42Y, OSO / 42N, OSO /42M, OSO / 12B UIB/12 UIB/121/122 UIB/121/122
Area Operations Electrical
Staff reporting to an Area Operations Electrical Supervisor
Area Operations Support (Electrical)
North: ONO/62 South: OSO/62
Head of Area Estate Services
Operations Area Coordinators
Page 116
Printed 17/09/13
PR-1 PR -194 948 8 Ele Elect ctri rica call Saf Safet et O er erat atin in Pr Proc oced edur ures es
The controlled version of this CMF Document resides online in Livelink®. Printed copies are UNCONTROLLED. UNCONTROLLED.
Vers ion 10.0 10.0 Effective:Oct-10
Petroleum Development Oman LLC
PR USER-COMMENT FORM PR User-Comment Form If you find something that is incorrect, ambiguous or could be better in a PR, write your comments and suggestions on this this form. Send the form to the Document Control Section (DCS). They make a record of your your comment and send the form to the correct CFDH. The form has spaces for your personal details. This lets DCS or the CFDH ask you you about your your comments and tell you about the decision. PR Details Details Number:
Title
Issue Date:
Page number:
Heading Number:
Figure Number:
Comments:
Suggestions:
User’s personal details
Name:
Ref. Ind: Ind:
Signature:
Date: Phone:
Document Control Section Actions Actions Comment Number: Number:
CFDH
Dates Dates Recd:
To CFDH:
Ref. Ind: Ind:
CFDH Actions CFDH Actions Recd Date:
Inits:
Decision: Reject: Accept, revise at next issue:
Ref.
Date:
Ind:
Accept, issue temporary amendment Comments:
Originator Advised:
Date:
Inits:
Document Control Section Advised:
Date:
Inits: