Power Substation Automation & Communication_IEC 61850

April 29, 2018 | Author: boeingAH64 | Category: Electrical Substation, Electric Power System, Telecommunication, Computer Network, Transformer
Share Embed Donate


Short Description

Download Power Substation Automation & Communication_IEC 61850...

Description

Power Systems Communications

Implementation of IEC61850 in a Substation Environment 26 October 2009 Reference VEE4700-01 Revision 0

Document Control Document ID: DOCUMENT1 Rev No

Date

Revision Details

Typist

Author

0

20/10/2009

Document Created

Team

Team

Verifier

Approver Team

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

Contents Section

1.

2.

3.

4.

Page

Introduction

1

1.1 1.2 1.3 1.4

2 2 2 2

Generator Protection

3

2.1 2.2 2.3

3 3 4

6.

7.

Chosen Relay for Generator Protection Key Benefits and Features of G60 Relay Wiring Diagrams for Generator Protection

Transformer protection

7

3.1 3.2 3.3

7 7 8

Key Features User Benefits Single line diagram of how relay connected to the transformer

Switchgear Protection 4.1 4.2 4.3 4.4 4.5 4.5.1 4.5.2 4.6

5.

IEC 61850 Standard Peer-to-Peer Message (GOOSE) Process Bus Interface True Interoperability

Busbar Protection The important issues of switchgear protection can be summarized The requirements for good protection 330kV Busbars Intelligent Electronic Device (IED) Functional Block Diagram (GE Multilin) Substation Monitoring (Human Machine Interface) Differential Busbar Protection

9 9 9 9 10 10 11 11 12

Line Protection

15

5.1 5.2 5.3

15 16 18

Line Distance Protection IED61850 Application Distance IED Communications Application

Substation Communications Network (IED61850 Network)

19

6.1 6.2

19 19

Implementation of IEC61850 Redundant Network

Conclusion

20

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX  26 OCTOBER 2009  REVISION 1  PAGE i

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

1. Introduction The aim of the project is to design the protection solution for the given system which has to be in compliance with IEC61850 standard. It is also required to work out the infrastructure of the next generation power system communications including the communication and telecommunication protocols.

Figure 1: Given system

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX  26 OCTOBER 2009  REVISION 1  PAGE 1

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

1.1 IEC 61850 Standard IEC 61850 is the global standard for communication in substations. It enables integration of all protection, control, measurement and monitoring functions within a substation, and additionally provides the means for high-speed substation protection applications, interlocking and intertripping. The comprehensive implementation facilitates integration of the relays into IEC 61850-based Substation Automation Systems and at the same time it allows the interface with different vendors' Merging Units over the IEC 61850 Process Bus. It combines the convenience of Ethernet with the performance and security which is essential in substations today. IEC 61850-enabled relays are fitted with an integral Ethernet card providing both copper and fiber Ethernet. No external adaptors or data concentrators are necessary and only standard Ethernet equipment such as switches and substation grade switches etc are required.

1.2 Peer-to-Peer Message (GOOSE) Generic Object-Oriented Substation Event (GOOSE) messages can be used for interlocking, disturbance recording cross-triggering, breaker failure protection tripping, directional comparison bus protection and many other advanced applications, thus eliminating extensive hardwiring in equipment bays and so reducing the cost of implementing advanced distributed protection and control schemes. The implementation of the IEC GOOSE messaging provides faster end-to-end transfer than using hardwiring.

1.3 Process Bus Interface Analog interface units (or Merging Units) located in the substation yard interface with conventional or non-conventional instrument transformers and send the sampled current and voltage values over fiber, thus significantly reducing (actually eliminating) the copper wires between the substation primary equipment and the protection, control and measuring devices.

1.4 True Interoperability One protocol is all that is needed in the substation. Costly gateways and split path communications are thus avoided. Peer-to-peer messages, control commands, disturbance files transfer or event driven reports are interleaved on a single Substation Bus network. Multiple clients can be integrated, allowing authorized operators and engineers to interrogate and control the substation IEDs. The Substation Configuration Language defined in the standard represents a leap in the engineering process related. The self-descriptive nature of IEC 61850-compatible IEDs means that system integration and commissioning are easier. Standardized data classes and services mean IEC 61850-enabled IEDs can operate seamlessly in multi-vendor environments.

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX  26 OCTOBER 2009  REVISION 1  PAGE 2

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

2. Generator Protection Industrial and commercial power systems may include generators as a local source of energy. These generators supply all or part of the total energy required, or they provide emergency power if the normal source of energy fails. The application of generators can be classified as single-isolated generators, multiple-isolated generators, unit-connected generators, cogeneration generators, and induction generators. Generator protective schemes vary depending on the objectives to be achieved. Generator protection requires the consideration of many abnormal conditions that are not present with other system elements. The abnormal conditions that may occur with generators include: • • • • • • • • • • • • • • •

Overheating Stator (due to overload or loss of cooling) Rotor (due to overexcitation, loss of cooling) Winding faults Stator (phase and ground faults) Rotor (ground faults and shorted turns) Overspeed and underspeed Overvoltage Loss of excitation Motoring Unbalanced current operation Out of step Subsynchronous oscillations Inadvertent energization Nonsynchronized connection

2.1 Chosen Relay for Generator Protection The relays selected for generator protection is manufactured by GE Multilin.

Figure2: GE Multilin G60- Comprehensive protection for generators

2.2 Key Benefits and Features of G60 Relay Complete IEC 61850 Process Bus solution providing resource optimization. Secure high-speed protection elements for complete generator protection, compliant with IEEE C37.102. FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX  26 OCTOBER 2009  REVISION 1  PAGE 3

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

Reduced relay to relay wiring and associated installation costs through highhigh-speed inter-relay communications. Redundant architecture for dependability and security security. Networking interfaces – 100Mbit Fiber Optic Ethernet, RS485, RS232, RS422, G.703, and C37.94. Multiple Protocols - IEC61850, DNP 3.0 Level 2, Modbus RTU, Modbus TCP/IP, IEC60870 IEC60870-5104, Ethernet Global Data (EGD). (EGD) 2.3

Wiring Diagrams for Generator Protection

orm the followin followingg ANSI functions if configured using standard scheme as This relay can perform shown below in single line diagram:

Figure 3

For our particular system single line diagram showing VT & CT connections is given below:

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL LOCAL SETTINGS SETTINGS\TEMPORARY INTERNET FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER FILES POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX  26 OCTOBER 2009 

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

Generator Protection 87 81O/81U 67N 59N 50G/51G 27P/27TN 24 GE G60 Multilin IED

CT/VT Connection Circuit Breaker Trip

110V VT Metering

Generator Protection GE G60 – Multilin IED

200MVA Generator

Protection Employed 87 81O/81U 67N 59N 50G/51G 27P/27TN 24

22kV/330kV Transformer

Figure 4

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX  26 OCTOBER 2009 

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

Three CT’s and one VT were used to implement the generator protection and the protection functions employed were:

ANSI Device Number 87 81O 81U 67N 59N 50G 51G 27P 27TN 24

Function Generator Stator Differential Overfrequency Underfrequency Neutral Directional Overcurrent Neutral Overvoltage Ground Instantaneous Overcurrent Ground Time Overcurrent Phase Undervoltage Third Harmonic Neutral Undervoltage Volts Per Hertz

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX  26 OCTOBER 2009  REVISION 1  PAGE 6

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

3. Transformer protection Transformers are high capital cost assets in electrical power systems. Elimination of all electrical and mechanical stresses desirable to preserve transformer life is impractical. Adaptive techniques to measure and alarm in such instances and advise on service duty can help to schedule preventive maintenance. Internal faults are a risk for all transformers. With short circuits dissipating the highest lacalized energy. Unless cleared quickly the possibility to rewind windings reduces and core damages may become irreparable. The MiCOM P642, P643 and P645 from AREVA address all the issues - preserving service life, and offering fast protection for transformer faults. The P642 incorporates differential, REF, thermal, and overfluxing protection, plus backup protection for uncleared external faults. So we decided to use P642 as it is cheap and suitable for our substation design.

3.1 Key Features • • • • • • • •

High-speed transformer differential protection. A proven 2nd harmonic current scheme is used Simple setting – wizard requires only nameplate data Restricted earth fault (REF) boosts trip sensitivity Voltage, frequency, thermal and overfluxing elements CT, VT, trip circuit and self-supervision: Patented CT supervision ensures no trip for CT or wiring failures Integrated backup overcurrent per winding Readily interfaces to multiple automation protocols, including IEC 61850

3.2 User Benefits • • • •

Universal IED for all transformer configurations Simple to specify, set and commission Backup and logging of faults Protection , control , measurements and recording in one device

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX  26 OCTOBER 2009  REVISION 1  PAGE 7

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

3.3 Single line diagram of how relay connected to the transformer CTs on both side of the transformer are for differential protection. Grounding CT is to tell weather the connection is delta/star or star/delta Overcurrent backup protection indicates from dotted red line.

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL LOCAL SETTINGS SETTINGS\TEMPORARY INTERNET FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER FILES POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX  26 OCTOBER 2009 

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX  26 OCTOBER 2009  REVISION 1  PAGE 9

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

4. Switchgear Protection 4.1 Busbar Protection Busbars are one of the most important components in a substation. There can be open busbars in an outdoor switch yard or contained inside a metal clad cubicle restricted within a limited enclosure with minimum phase-to-phase and phase-to ground clearances. Busbars form an electrical node where many circuits come together, feeding in and feeding out power. It is very clear that for any reason the busbars fails, it could lead to shutdown of all distribution loads connected through them, even if the power generation is normal and the feeders are operating normally.

4.2 The important issues of switchgear protection can be summarized • • • • • • • • • •

Loss very serious and sometimes catastrophic Switchgear damaged beyond repair Multi-panel boards not available ‘off-the-shelf’ Numerous joints Air enclosure Dust build-up Insect nesting Ageing of insulation Frequency of stress impulses Long earth fault protection tripping times

4.3 The requirements for good protection The successful protection can be achieved subject to compliance with the following: •

Speed – Limit damage at fault point – Limit effect on fault stability



Selectivity – Trip only the faulted equipment – Important for busbars divided into zones



Stability – Not to operate for faults outside the zone – Most important for busbars – Stability must be guaranteed



Reasons for loss of stability – Interruption of CT circuits – imbalance – Accidental operation during testing



Tripping can be arranged ‘two-out-of-two’ – Zone and check relays FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX  26 OCTOBER 2009  REVISION 1  PAGE 10

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

4.4 330kV Busbars

This is the 330kV busbars that require busbar protection.

4.5 Intelligent Electronic Device (IED) IEDs selected to protect the 330kV busbars.

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX  26 OCTOBER 2009  REVISION 1  PAGE 11

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

4.5.1

Functional Block Diagram (GE Multilin)

4.5.2

Substation Monitoring (Human Machine Interface)

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX  26 OCTOBER 2009  REVISION 1  PAGE 12

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

4.6 Differential Busbar Protection The busbars will be protected by two IEDs; the purpose of the two IEDs is to provide reliability and backup protection. If one IED fails, one busbar will still be protected.

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX  26 OCTOBER 2009  REVISION 1  PAGE 13

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX  26 OCTOBER 2009  REVISION 1  PAGE 14

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX  26 OCTOBER 2009  REVISION 1  PAGE 15

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX  26 OCTOBER 2009  REVISION 1  PAGE 16

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

5. Line Protection This part of the report will be covering the transmission line protection of the substation. The main faults that can occur on the transmission lines are: • Line to Line • Line to ground • Double line to ground • Three phase line to ground These faults can be caused by simply things such as birds, snakes, bushfires, and branches falling on to the line. They can also be caused by lightning and deterioration of insulation. This section will be focusing on the four transmission lines for the 2 buses which have to lines each as shown below.

Figure 5.1 Four transmission lines

5.1 Line Distance Protection In order to protect these four lines two relays from different vendors has been chosen. The first relay chosen is the ABB REL 670 Distance relay (figure 2). The REL 670 relay is fully IEC61850 complaint and features Control, monitoring and protection integrated in to the one IED. This relay is also chosen because of its maximum reliability and performance optimized for Figure 2. ABB relay transmission overhead lines and cables.

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX  26 OCTOBER 2009  REVISION 1  PAGE 17

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

The way in which The ABB REL 760 relay is connected to the transmission line is in the Dual breaker configuration instead of a simply configuration which uses 1 VT and 1 CT. The Dual breaker configuration uses 2 VTs and 2VTs it will cost more but is a lot more reliable. The connection scheme can be seen in figure 3.

The second relay used in the system is the GE D90Plus (figure 4) . The D90Plus is also fully IEC61850 and also features back up protection such as time over current. The D90Plus is also selected because of the fact that it can use fibre optic communication. The D90Plus is connected on the same scheme as the ABB in which it is connected in a Dual breaker scheme with 2 VTs and 2 CTs.(Figure 5) Figure 4. GE D90Plus

Figure 5. D90Plus connection

5.2 IED61850 Application When all the relays have been place in the substation, the relays from the two vendors are connected together by the fibre optic link on the process bus as can be seen in figure 6. One each bus we have 4 CTs and 4VTs with 3 circuit breakers with one of those circuit breakers being used by both relays.

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX  26 OCTOBER 2009  REVISION 1  PAGE 18

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX  26 OCTOBER 2009  REVISION 1  PAGE 19

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

5.3 Distance IED Communications Application This report covers the transmission line protection of a new substation but Figure 7 shows a larger picture of the system with the top half being the new substation and the bottom half being another substation xxx Kilometres away, the top substation uses a ABB relay while the bottom substation uses a GE relay and the two are connected by a fibre optic cable xxx Kilometres away.

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX  26 OCTOBER 2009  REVISION 1  PAGE 20

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX  26 OCTOBER 2009  REVISION 1  PAGE 21

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

6. Substation Communications Network (IED61850 Network) 6.1 Implementation of IEC61850

6.2 Redundant Network • • • • • •

Redundant bay controller has default settings Local servers store all real time data operate substation in the event of network hack, security breach or corrupted data transmitted to control centre can only take instructions from the local HMI Require passwords A SMS message will be sent using a mobile phone or other similar device via a message broker in an emergency

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX  26 OCTOBER 2009  REVISION 1  PAGE 22

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

FILE C:\DOCUMENTS AND SETTINGS\DURA65282\LOCAL SETTINGS\TEMPORARY INTERNET FILES\CONTENT.OUTLOOK\KZ6DO78L\POWER SYSTEM COMMUNICATION REPORT REVISION 0 0.DOCX  26 OCTOBER 2009  REVISION 1  PAGE 23

Power Systems Communications Assignment - VEE4700 Implementation of IEC61850 standard in a Substation Environment

7. Conclusion The IEC61850 standard will become the most widely used standard for substation communications. The main features being interoperability, reliability (easy to replace IED’s with different vendor IED’s), advanced protection, advanced automation and control (smart grid compatibility), advanced metering and easier/simplified human interface with the power system.