Download Power Factor Dry Type Transformer Testing...
Description
12/25/2018
Performing power factor test on dry-type transformer during commissioning | EEP
Maintenance / Testing and Commissioning / Transformers
Performing power factor test on dry-type transformer during commissioning Power factor test The power factor test is a maintenance test used to determine the insulation system dielectric power loss by by measuring measuring the the power power angle between an applied AC voltage and the resultant current.
Performing Performing power power factor factor test test on on dry-type dry-type transformer transformer during during commissioning commissioning (photo (photo photo credit: credit: sgb-smit.com) sgb-smit.com)
Performing power factor test on dry-type transformer during commissioning | EEP
Power factor is defined as the ratio of the power dissipated divided by the input volt-ampere multiplied by 100% .
This test may be required required to to be be performed performed during during the the acceptance testing stage to establish a baseline reading for future test comparison.
Figure Figure 11 –– Insulation Insulation System System Equivalent Equivalent Circuit Circuit and and Power Power Factor Factor Factor Vector Vector Diagram Diagram
Dielectric Dielectric losses losses in in and and power power factor factor can can be calculated by:
Watts = = E × IT × × Cosine Ө Power factor = = Cosine Ө = Watts / (E × IT) Power factor test is performed performed for for detecting insulation deterioration or degradation usually usually caused caused by moisture , carbonization or other forms of contaminants of the winding and bushing. Winding distortions results in a change in winding capacitance and short-circuited and partially short-circuited turns result in abnormally high excitation current. Types of transformers that are normally subjected to the power factor test are: https://electrical-engineering-portal.com/dry-type-transformer-power-factor-test
2/12
12/25/2018
Performing power factor test on dry-type transformer during commissioning | EEP
1. Two winding transformers 2. Three winding transformer Auto-transformers rmers 3. Auto-transfo Auto-transforme rs 4. Instrument transformers
Other test names names synonymous synonymous with the power factor test are dielectric loss angle, dissipation factor test, tan delta or doble test.
General conditions required for testing transformers are: 1. The unit must be de-energized and isolated from the power system including the neutral connection from ground. 2. Transformer enclosure must be properly grounded and and applicable applicable to to when when testing spare units. 3. All terminal of each winding are short-circuit short-circuited ed together including the neutral terminals. This will minimize the effect of winding inductance during testing. 4. Load tap changer (LTC) should should be be set of neutral if it has arrester-type elements that are not effectively short circuited in the neutral position. The power factor factor test test typically typically applies a test test voltage voltage less than the stress working levels of the equipment. Refer to Table 1. Table 1 – Recommended power factor test voltage for dry-type power transformer connected in delta and ungrounded-wye
Performing power factor test on dry-type transformer during commissioning | EEP
Winding
Test Voltage Voltage
rating
Line-to-ground, kV
Line-to-line, kV Above 14.4
2 and 10
12 to 14.4
2, 10 and at operating line-to-ground voltage
5.04 to 8.72
2 and 5
2.4 to 4.8
2
Below 2.4
1
Note //
Transformer windings Transformer windings provided with neutral insulation rating which is less than the line insulation rating should be tested below the neutral insulation rating level. The required tests are noted in Table 2 and its connection is shown in Figure Figure 22 and and Figure Figure 3. 3. The The difference between the high voltage winding tests and the low voltage winding tests are are the the placement of the test leads and the test voltage levels. Test 3 and test 8 of Table 2 should generate the same value as they both measure the same capacitance capacitance between between the the windings. Table 2 – Power Factor test connection for two winding dry-type transformer
Performing power factor test on dry-type transformer during commissioning | EEP
Test
Test Energized Ground Grou Gr ound nd G Guar Gu ua ard rd US UST T Measur Measu sur r
number mode
winding
1
GST
High
Low
–
–
CH+CH
2
GST
High
–
Low
–
CH
3
UST
High
–
–
Low
CHL
4
Calculate Test 1 minus Test 2
CHL
5
GST
Low
High
–
–
CL+CH
6
GST
Low
–
High
–
CL
7
UST
Low
–
–
High
CHL
8
Calculate Test 5 minus Test 6
CHL
HV winding power factor test 1. Isolate transformer 2. Isolate Neutral Connection 3. Install shorting jumpers on H1, H2 and H3 4. Install shorting jumpers on X1, X2, X3 and X0 5. Apply Specified test voltage at ramp rate in 15 seconds 6. Test at specified voltage for 1 minute 7. Reduce test voltage to zero at ramp rate in 5 seconds
Performing power factor test on dry-type transformer during commissioning | EEP
Figure Figure 22 –– Power Power Factor Factor High High Voltage Voltage Winding Winding Test Test Connection Connection
LVV winding power factor test 1. Isolate transformer 2. Isolate Neutral Connection 3. Install shorting jumpers on H1, H2 and H3 4. Install shorting jumpers on X1, X2, X3 and X0 5. Perform a GST test 6. Perform a Guard test test 7. Perform an UST test 8. Confirm capacitance value from GST test minus Guard test equal UST test
Performing power factor test on dry-type transformer during commissioning | EEP
Figure Figure 33 –– Power Power Factor Factor Low Low Voltage Voltage Winding Winding Test Test Connection Connection
Caution //
Always ground to the previously energized terminal with a grounding stick before making any connection changes to bleed off any electrical charge that may be present. Leave the grounding connected until connection changes is completed and before the start of the next test.
Power factor test procedure (Two winding dry-type transformer) 1. Isolate the equipment, apply working grounds to all incoming and outgoing cables and disconnect all incoming and outgoing cables from the transformer bushing terminals. Disconnected cables should have sufficient clearance from the https://electrical-engineering-portal.com/dry-type-transformer-power-factor-test
7/12
12/25/2018
Performing power factor test on dry-type transformer during commissioning | EEP
switchgear terminals greater that the phase spacing distance.
Use nylon rope to to hold cable away from incoming and outgoing terminals as required.
2. Isolate the neutral bushing connection if applicable from the transformer grounding bar. 3. Short-circuit all high voltage bushing terminals together. 4. Short-circuit all low voltage bushing terminals and the neutral bushing terminal together. 5. Connect the power factor test set. Refer to Table 2 for the test measuring mode and associated test number. 6. Apply the specified test voltage levels as noted in Table 2. 7. Record power factor and watts watts loss loss values. values. 8. Repeat step 5 to 7 until all tests are completed Table 2 -Standard kVA Ratings Ratings for for Dry-Type Dry-Type Transformers
Performing power factor test on dry-type transformer during commissioning | EEP
Single
Three Thre e phase phase Sing Single le phase phase Three Three phase phase
phase 2
6
333
1000
3
9
500
1500
5
15
667
2000
10
30
833
2500
15
45
1000
3000
25
75
1250
3750
37
112
1667
5000
50
150
2500
7500
75
225
3333
open-ended
100
300
5000
—
450
open-ended
167
500
–
250
750
–
Measuring capacitance and power factor or dissipation factor The condition of the bushings and the overall insulation of power transformers can be investigated by measuring the capacitance and dissipation factor, also known as the tangent delta, or power factor. Aging and decomposition of the insulation, or the ingress of water , increases the losses and thus more energy is turned into heat in the insulation. The level of this this dissipation dissipation is expressed expressed by the the dissipation dissipation factor or power factor.
Performing power factor test on dry-type transformer during commissioning | EEP
Power factor testing In this video you will learn about means to measure the quality of the insulation of power transformers and bushings, such as power factor or dissipation factor measurement, and measuring capacitance. Possible causes for a reduction in insulation Possible causes for a reduction in insulation quality are also explained.
Thank you for interesting in our services. We are a non-profit group that run this website to share documents. We need your help to maintenance this website.