PMG-EnG-O-DSH-U00-001-W Rev 3 Fire Fighting & Safety Equipment Datasheet_Part8

February 8, 2018 | Author: Aditya Pranoto | Category: Firefighting, Valve, Building Engineering, Nature
Share Embed Donate


Short Description

Yo...

Description

PROYEK PEMBANGUNAN PABRIK MINYAK GORENG KAP. 600.000 TON CPO/TH Document No. PMG-ENG-O-DSH-U00-001-W

Rev. 3

FIRE FIGHTING & SAFETY EQUIPMENT DATASHEET

Page 8

GENERAL INFORMATION Equipment Location Manufacturer Model

: Pillar Hydrant : Note 3 : (*) : (*)

Tag Quantity Dimension

: PH-001~017 : 17 : (*)

Onshore Tropical Humidity :

Other Other 59-92

TECHNICAL DATA Environmental Data

Equipment Data

Location : Atmosphere : Ambient Temperature: Wind Speed : Type

:

Inlet size Outlet connection Flowrate

Valve

: : : : : : : : : : :

Cap & chain

:

Range of Throw Dimension Weight Working pressure Max pressure Material Color

Offshore Salt Laden 24-32 120

o

C km/hour

%

Pillar hydrant, 4" with a single hydrant valve, and 2 x 2-1/2" outlets with chained caps 4" 150# FF 2-1/2" Instantaneous 2 x 946 lpm 30 m mm Note 1 kg Note 1 7 barg 16

barg

Cast Iron Red Two units 2-1/2" hydrant valves & pressure control valve Two 2-1/2" caps (bronze/brass) & chains (Stainless Steel)

Hand-wheel direction :

Clockwise to close

: Applicable Standards :

"OPEN" & "CLOSED" on the wheel

Description

:

Fire hydrant cabinet consists of two 30 meters (100 ft) of 2-1/2" fire

Material

:

U/V resistant glass fiber or epoxy coated steel construction

Door

:

Double swing fitted with a quick release non-lockable handle

Quantity

:

17 (one (1) for each pillar hydrant)

Color Standard

:

Red

:

NFPA 24

Hose Material

:

Collapsible rubber coated, heat and oil resistant

Marking

Hose Cabinet

NFPA 14; NFPA 24; NFPA 1963

hoses and two nos jet nozzles with 2-1/2" french symetric coupling

Hose, Nozzle & Adapter

Marking

Max hose opt press. :

20 barg (*)

Hose Length

:

30 m

Hose Quantity

:

2 each per cabinet

Nozzle Material

:

Pyrolite (*)

Nozzle inlet pressure :

3.5 bar

Nozzle Quantity

:

2 each per cabinet

Adapter

:

2-1/2" adapter to connect 2 hoses

Adapter Material

:

Note 1

Adapter Quantity

:

1 each per cabinet

"FIRE HOSE" (in white letter)

NOTE * Vendor to specify and verify data. 1. Vendor to advise as per manufacture standard 2. Instruction for use to be included 3. The location of hydrant pillar shall refer to Fire Fighting & Safety Equipment Layout (PMG-ENG-O-GEN-U00-001-W)

View more...