PROJECT: Construction of Expansion of Yashoda Hospital- Phase-1 GRAND SUMMARY S No

Item

1

SANITARY FIXTURES

2

WATER SUPPLY SYSTEM

3

PUMPS & MOTORS

4

INTERNAL & EXTERNAL SANITARY PIPING SYSTEM

5

RAIN WATER DISPOSAL SYSTEM

6

WATER TREATMENT PLANT WORKS

7

HOT WATER SYSTEM

Supply

Installation

Total

Remarks

TOTAL AMOUNT In Words:

For Employer

Page 1 of 31

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad S.No

Date: 28-Aug-2013 DESCRIPTION

UNIT

Supply A

SANITARY FIXTURES

1

Supply, Fixing in position of Wall mounted European Water Closet suite of approved make & colour, comprising of :

Rev: R0

RATE

QTY

No's

100.00

No's

8.00

AMOUNT Installation

Supply

Installation

Glazed vitreous chin aware Wall mounted European water closet of approved make and co lour with wash down pattern fixed to wall with necessary CI / MS chair bracket, GI bolts & nuts, WC connector with rubber gaskets as per manufacturer's specifications, including cutting and making good the walls & flooring etc. complete. Providing and fixing matching colour solid plastic seat & cover of approved make conforming to IS: 2548 specifications and bearing ISI mark. 25mm Concealed flush valve immediate releasing spring type having all parts made of corrosion resistant materials and of approved make with necessary piping from flush valve to the water closet as per water closet manufacturer's specification for satisfactory operation of system. The top cover plate shall be made of engineering plastic with CP finish / brass with CP finish / polished SS and the flush actuation plate preferably be of square / circular shape with central push button, with necessary 25mm diameter GI/ Threaded PVC piping not exceeding 1m in length from flush valve to water closet for satisfactory operation of system.

2

Providing and fixing of Floor Mounted European water closet comprising the following including cutting and making good the walls /floor wherever required all complete.(For Disabled Toilets) White vitreous China Floor mounted pan with `P' or `S' trap of Make, model, size as specified in the enclosed list. Matching color polypropylene seat cover with necessary C.P. brass hinges, rubber bushes etc. of Make as specified in the enclosed list

For Employer

Page 2 of 31

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad

Date: 28-Aug-2013 RATE

Rev: R0 AMOUNT

25mm Concealed flush valve immediate releasing spring type having all parts made of corrosion resistant materials and of approved make with necessary piping from flush valve to the water closet as per water closet manufacturer's specification for satisfactory operation of system. The top cover plate shall be made of engineering plastic with CP finish / brass with CP finish / polished SS and the flush actuation plate preferably be of square / circular shape with central push button, with necessary 25mm diameter GI/ Threaded PVC piping not exceeding 1m in length from flush valve to water closet for satisfactory operation of system.

3

Supply, Fixing of CP brass Health faucet of approved make comprising of: heavy casted CP brass wall flange and one CP brass Health faucet of approved make with 1m long PVC tube of 8mm dia.Complete all as specified and directed with approved fittings.

No's

108.00

4

Supply, Fixing of oval under counter wash basin with CP bottle trap of approved colour, comprising of : (Common toilets for Ground Floor to 3rd Floor)

No's

24.00

Glazed vitreous china ware oval counter top wash hand basin of approved make of size 650x410mm .The gap between the counter and the top of the basin shall in no case exceed 5mm, silicone sealant shall be applied to the top of the basin before fixing in position so as to completely seal the gap. The excess sealant shall be wiped out using a clean blade flush with the basin inner profile.

For Employer

Page 3 of 31

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad

Date: 28-Aug-2013 RATE

One 15mm CP brass quarter turn type pillar cock wth one no of 15mm CP brass quarter turn type angle stop cock with ceramic disc cartridge of approved make with necessary wall flanges and two 15mm PVC flexible inlet connection pipe 600mm long with CP brass nuts at both ends and necessary rubber washers complete. One 32mm heavy quality CP brass waste coupling & CP brass bottle trap with extension piece & wall flange of approved make and conforming to IS specifications. 40mm dia.UPVC pipe with specials from extension piece of bottle trap to the ceiling suspended trap.The scope includes necessary UPVC pipe ,fitting & necessary sealent to connect Floor Trap etc,complete. 5

Supply ,Fixing of wash basin comprising the following including cutting and making good the walls/ floors wherever necesssary all complete as per specifications .(For all Guest rooms & Consultant rooms)

No's

112.00

No's

108.00

No's

65.00

Rev: R0 AMOUNT

Wall hung wash basin (without pedestal) from approved make white/Colour Wash basin including cutting and making good the walls/ floors wherever necesssary all complete as per specifications

6

7

Fixing of 15mm n.b C.P pillar cock,32mm heavy quality CP brass waste coupling & CP brass bottle trap with extension piece & wall flange of approved make and conforming to IS specifications. 40mm PVC waste pipe with specials from extension piece of bottle trap to the floor trap, length not exceeding 1m concealed in the wall, including cutting and making good the floors and walls. Supply, Fixing of approved make Coat Hook fixed to wall with cp screws and required all accessories etc,complete. Supply, Fixing of approved make Soap Dispenser fixed to wall with cp screws and required all accessories etc,complete.(For all common toilets & OP Rooms)

For Employer

Page 4 of 31

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad

Date: 28-Aug-2013 RATE

8

Supply, Fixing of CP brass Towel Ring of 150mm dia.fixed to wall,with CP screws.(For all common toilets & OP Rooms)

No's

65.00

9

Supply, Fixing of approved make Toilet Paper Holder fixed to wall with cp screws and required all accessories etc,complete.

No's

108.00

10

Supply, Fixing of approved make automatic hand drier operated with sensors,air flow up to 15cms, fixed to wall with cp screws and required all accessories etc,complete.

No's

8.00

11

Supply, Fixing of approved make CP Brass Towel Rail of 20mm dia.600mm long fixed to wall with CP brass screws etc., complete

No's

49.00

12

Supply, Fixing of CP brass Tumbler Holder fixed to wall,with CP screws.

No's

49.00

13

Supply&Fixing of Flat back Half White Large URINAL fixed with screws to wall with waste coupling,bottle trap,waste pipe drop to lower floor&connected to P-Trap with 50mm dia.Galvanized Iron pipe .The scope includes necessary GI fittings(T-Joint) & necessary sealent to connect P- Trap etc,complete.. Concealed Sensor for URINALS with installation box &control cock,CP Dome and all accessories completed provision for manual operation to be made with concealed stop cock.

No's

32.00

14

Supply&Fixing of Granite Urinal Division Plates of 1200mmx600mm size with wall cutting and making good completed

No's

28.00

15

Supply, Fixing of CP brass Shower assembly comprising of the following :

No's

49.00

Rev: R0 AMOUNT

15 mm CP brass overhead shower with hand shower and heavy casted shower arm with wall flange of approved make.

For Employer

Page 5 of 31

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad

Date: 28-Aug-2013 RATE

One quarter turn type with ceramic disc cartridge, CP brass Single Lever Diverter with built in spout & CP bend for overhead shower of approved make. Complete all as specified & directed with approved fittings. 16

Supply ,Fixing of CP brass Shower assembly comprising of the following :

No's

URO

No's

10.00

No's

6.00

No's

49.00

Rev: R0 AMOUNT

15 mm CP brass overhead shower with hand shower and heavy casted shower arm with wall flange of approved make. Fixing of wall mixer with bend provision for overhead shower of approved make. Complete all as specified & directed with approved fittings. The scope includes supply of necessary accessories etc,complete. 17

18 19

Supply, Fixing of Stainless steel sink & drain board of approved make of size 61cmx25cmx45cm supported on suitable RC or Granite platform. Two No's 15mm sink cocks with swivel casted spout conforming to IS specifications. One 40mm heavy quality CP brass waste coupling of approved make with removable crumb cup strainer. 40mm dia. UPVC pipe with specials from extension piece of bottle trap to the ceiling suspended trap.The scope includes necessary UPVC fittings & necessary sealent to connect Floor Trap etc,complete. Fixing of CP long body bib cock for wash area water supply conforming to IS specifications.The scope includes supply of necessary accessories etc,complete. Supply & fixing of approved make soap dish fixed to wall with CP screws etc.complete.(Near Shower )

For Employer

Page 6 of 31

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad

Date: 28-Aug-2013 RATE

20

Supply, Installation, testing and commissioning of commercial water purifier of water flow rate 15.0 Ltr/Hr,Including all components as per manufacture specifications,including connections from water supply line and final connection to water cooler electric wiring & plug top etc.with all accessories complete.

No's

20.00

21

Grab bar -Supplying & fixing floor - wall mounted safety armrest for handicapped,made of stainless steel profiled tube with multi-functional, ergonomic grip area, antislip profile, diameter 32 mm with one 90 deg. & one 180 deg.and two extruded fastening flanges with two holes each,made of stainless steel 8 mm diameter, 3 mm thick, with plastic collar, including fastening set. Execution selectable right-hand or lefthand.

No's

8.00

22

Providing & fixing of Glazed vitreous china ware Lab sink with drain board (SD) comprising of :drain board of approved make size 450x370mm supported on suitable RC or granite platform .One 15mm CP brass quarter turn type sink mixer and two no's of 15mm CP brass quarter turn type angle stop cock with ceramic disc cartridge of approved make with necessary wall flanges conforming to IS specifications. One 40mm heavy quality CP brass waste coupling of approved make with removable crumb cup strainer. 40mm dia. UPVC pipe with specials from extension piece of bottle trap to the ceiling suspended trap.The scope includes necessary UPVC & fittings & necessary sealent to connect Floor Trap etc,complete.(For Scrub Area)

No's

6.00

No's

110.00

No's

20.00

23 24

Supply ,installation of hand sanitizer with require accessories etc,complete. Fixing of CP angular stop cock for water cooler and , RO plant water supply conforming to IS specifications.The scope includes supply of necessary accessories etc,complete.

For Employer

Page 7 of 31

Rev: R0 AMOUNT

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad

Date: 28-Aug-2013 RATE

25

Fixing of CP long body pillar tap for lab sinks conforming to IS specifications.The scope includes supply of necessary accessories etc,complete.

No's

12.00

26

Supply and fixing of electric storage type verticle/horizontal Instant water heater of approved make & colour,storage tank manufactured from 99% pure Copper which is suitable for both hard & soft water with all other internal fittings,internal insulation, inside non-return valve as per IS 2083-1978 with three core heavy duty copper cable 1m long ,15Amps 3 pin plug,CP brass angle valves, fusible plug automatic pressure releaf valve, 600mm CP copper connecting pipe with end nuts for hot & cold water connections etc. complete. Capacity : 25 Ltrs(Each) (For Delux Rooms)

No's

10.00

Rmt

1100.00

B

1

Rev: R0 AMOUNT

TOTAL FOR SANITARY FIXTURES WATER SUPPLY SYSTEM Providing, laying, jointing, fixing, testing, commissioning of Composite PL pipes with Brass & crimp fittings conforming to IS 15450:2004. The scope includes providing threaded fittings having brass threaded ring for outlets for connecting metallic pipes and fittings, including chasing the walls / floors, making holes, clamping to walls and restoring the same to original conditions etc., complete all as specified and directed and as per manufacturer's specification.The scope includes ceiling suspended 8mm dia.GI Hitech clamps/anchor rods (Spacing between two supports as per specifications )for suspended pipes wherever it necessary. Note: Brass fittings are used for utility connections & crimp fittings for all vertical & external pipes. The entire piping system in part or as a whole has to be tested to a hydraulic test pressure of 7 kg/sq.cm for a period of not less than 24 hours. the piping shall be concealed / commissioned only after satisfactory testing of the system. a) 20MM (Internal Dia)

For Employer

Page 8 of 31

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad b) 25MM (Internal Dia) c) 32MM (Internal Dia)

2

Date: 28-Aug-2013 Rmt Rmt

600.00 250.00

Rmt Rmt Rmt Rmt Rmt Rmt

610.00 140.00 300.00 100.00 265.00 550.00

RATE

Rev: R0 AMOUNT

Providing, laying, jointing, fixing, testing, painting, commissioning GI medium quality type pipe of approved make conforming to IS:1239, including cost of GI specials, cutting the pipes to the required lengths, threading, jointing the pipes, chasing,making holes necessary in walls & floors, clamping to walls / supports using fabricated MS brackets(40x40x5mm Angle or 40 x6mm Flat) of approved design, GI threaded U clamps on the bracket, HITECH pipe supports & restoring the walls & floors to the original conditions etc., complete all as specified and directed. The exposed pipes shall be painted with 2 coats of approved synthetic enamel paint over a coat of metal primer, including making the necessary colour bands as specified in the tech.spects. The entire piping system in part or as a whole has to be tested to a hydraulic test pressure of 7 kg/sq.cm for a period of not less than 24 hours. the piping shall be concealed / commissioned only after satisfactory testing of the system. a) 20MM Dia. b) 25MM Dia. c) 32MM Dia. d) 40MM Dia. e) 50MM Dia. f) 65MM Dia.

For Employer

Page 9 of 31

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad

3

RATE

Supply & fixing of heavy quality Ball valves shall have body of carbon steel. The ball and the shaft shall be of stainless steel. The seat shall be of PTFE. The valve shall be complete with socket weld ends and the float of copper sheet. The minimum thickness of copper sheet used for making the float shall be 0.45mm for a float exceeding 115mm dia. The body of the high pressure ball valve when assembled in working condition with the float immersed to not more than half of its diameter shall remain closed against a test pressure of 3.5kg/sqcm.of following sizes, conforming to IS:1703: 1977,PN 1.0 and bearing ISI mark, including testing, making good the leakages etc., complete. a) 20 mm Dia b) 25 mm Dia c) 32 mm Dia d) 40 mm Dia e) 50 mm Dia

4

Date: 28-Aug-2013

No’s No’s No’s No’s No’s

80.00 80.00 12.00 10.00 28.00

No’s No’s No’s

19.00 1.00 1.00

Rev: R0 AMOUNT

Providing & fixing butterfly valve (Body : Grey Cast Iron, Shaft: SS, Disc : SG Iron (Rilson coated), Liner: HT - EPDM) (upto 150mm dia with hand lever operation & above with gear box operation). Tested to a pressure not less than 10Kg/Sq.cm. Including rubber gasket, flanges, nuts, bolts, washers & painting complete as required. a) 65 mm Dia b) 80 mm Dia c) 100 mm Dia

For Employer

Page 10 of 31

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad

Date: 28-Aug-2013 RATE

5

Supply, delivery, installation, testing, commissioning of digital water level controller , digital display of water level in the tank, trigger for automatic operation of pump set when the water level reaches low level, including fixing necessary stainless steel sensors, float level switch, probes, etc. The control cabling from panel to sump, making connections from the level controller to the pump starter, necessary conduiting shall have to be done by qualified electrical contractor only.

Each

6.00

6

Supplying and fixing of digital percentage level indicator for water storage tanks consisting of display unit and level sensor. The display unit should have 2-1/2 digit seven segment LED to display the levels as 0%, 10% --- 100%. The unit should be weather proof and wall / panel mounted input to the unit should be 230V AC. The level sensor should consists of float operated magnetic float switch with one PUF float suitable mounting flange and flame proof enclosure.

Each

6.00

7

Providing and fixing in position 65mm dia flanged Cast Iron dirt box YType Strainer having body fabricated in Cast Iron and strainer made of SS perforated sheet having perforations of suitable size.

Each

2.00

8

Constructing water meter chamber or valve chamber of sizes as mentioned below over 100mm thick CC 1:4:8 leveling course, 100mm thick CC 1:3:6 for foundation with 150mm offset around, 230mm thick brick masonry in CM 1:3 using table mold bricks, 12mm thick plaster on outside, inside surfaces in CM 1:3, providing, fixing frame & cover in 100mm thick RCC 1:2:4 using 20mm metal, finishing top surface with CM 1:3 plaster and finished smooth. Each

1.00

1200x1200mm internal clear dimension with 900x900mm SFRC frame & cover of medium duty (MD-10 grade)(For Municipal Water Incoming Line)

For Employer

Page 11 of 31

Rev: R0 AMOUNT

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad 9

10

11

12

13

14 15

Date: 28-Aug-2013 RATE

Supply and fixing of following mentioned dia. Water meter inclusive of 2 isolating ball valves, GI union and strainer inside the valve chamber. a) 50mm dia. Supply,Laying of 50mm(28 Gauge) thick Rock Wool insulation with mechanical protection, GI wire mesh( 14 Gx3/4”) and Al(28 Gauge) cladding.(All Terrace ,Vertical Down Takes & internal toilet Hot Water Pipes) . a) 20MM Dia. b) 25MM Dia. c) 32MM Dia. Supply, fixing in position auto air release valve (ARV)of 25mm n.b. of approved make with body made of Cast Iron and Rubber Coated Wooden Brass with Brass Plug and other moving parts of stainless steel & Screwed Ends as per IS 14845,PN 1.0.The scope includes provision of ball valve (between ring main & ARV ) for any maintenance shall be made. Supplying & fixing Flanged CI non return valve with necessary nuts, bolts, rubber gaskets etc. complete. of approved make. (To be placed at pump room ) a) 40mm dia. b) 65mm dia. Providing and fixing of following mentioned dia dial pressure gauge to read up to 15kg/sq.cm, to be fixed on delivery main of pump sets with isolation cock. a) 25mm dia. Construction of P.C.C/ Brick Masonry pedestals 600mmx300mmx150mm with MS brackets & GI clamps for laying pipes on terrace Supplying & fixing of 20 mm dia. hose bib with valve of 20 mm dia. (For external gardening) .

For Employer

Each

1.00

Each Each Each

530.00 URO 180.00

No’s

8.00

No’s No’s

2.00 4.00

No’s

4.00

No’s

250.00

No’s

10.00

Page 12 of 31

Rev: R0 AMOUNT

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad 16

17 18

19

20

Supply, installation, testing & commissioning of Ductile iron(DI ) medium duty rectangular manhole cover with frame for the feasibility of access in the tank Size : 600 x 600 (65 kg) Providing and fixing in position G.I. vent with brass mosquito proof coupling and air filter including return bend, complete as required. The entire fitting shall be hot dip galvanised. Providing and fixing PPP Water hammer arrestors complete with necessary fittings for inlet dia of 20mm. Providing & fixing manhole foot rests; poly propylene, steel reinforcement The polypropylene shall confirm to ASTM D-410 and shall be injection molded around 12mm dia Fe-415 Steel reinforcing bar. The foot rest shall be provided in RCC walls / brick walls as per requirement of design / project manager. The external water piping system in part or as a whole has to be filled with water mixed with filtered bleaching powder solution of 50ppm chlorine and kept for a contact shower rose, pillar cocks, flushing cistern etc., shall be operated with this water for effective disinfection Care shall be taken to see that this water is not used for drinking and other purposes. The system shall be flushed with potable water before commissioning.

21

Liaison charges for Making water supply connection to municipal Water supply main with all the necessary works which shall be paid as per actual including cutting the corporation road and making good the road after the connection. the contractors responsibility shall include submitting the papers to the corporation follow-up and get the approval etc.,complete (only statutory charges to be paid by the client)

22

Supply & Fixing of G.I Puddle Flanges of various dia and size made out of G.I. with screwed ends, cap and plain for embedment n concrete as necessary with suitable accessories, consumables welding accessories including placing in position, complete for Under Ground Sumps & Overhead Tanks.

For Employer

Date: 28-Aug-2013 RATE No’s

12.00

No’s

24.00

No’s

8.00

No’s

80.00

LS

1.00

LS

1.00

Page 13 of 31

Rev: R0 AMOUNT

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad

23

24

25

26

Date: 28-Aug-2013 No’s No’s No’s No’s No’s No’s No’s

6.00 10.00 2.00 2.00 2.00 11.00 14.00

No’s No’s No’s No’s

3.00 6.00 6.00 URO

No’s

URO

a) 65mm dia. b) 50mm dia.

No’s No’s

2.00 2.00

Supply , fixing of approved make manually operated 25mm dia .drain valve on terrace ring mains (Ball Valve) made of cast iron TFE coated, hand wheel operated with Screwed ends for two sides & one end threaded outlet for Drain Water as per ASTM 150 standards(PN 1.0)

No’s

4.00

a) 20mm dia. b) 80mm dia. c) 100mm dia. d) 160mm dia. e) 250mm dia. f) 50mm dia. g) 40mm dia. Supplying, installing, testing and Commissioning approved make GM/Brass pressure reducing station(PRS) with union, ball valve / butterfly valve 3 nos of required dia, pressure gauge 2 nos with all necessary accessories etc. complete all conforming to IS. a) 40mm dia. b) 32mm dia. c) 25mm dia. d) 20mm dia. Supply ,installation of Electrically operated Solenoid valve to be mounted on the over head tank incoming line, 220V/24V/50 Hz, deenergized closing following mentioned dia.with necessary cabling from Over Head Tank to Under Ground Sump & required accessories complete. a) 25mm Dia.

RATE

Rev: R0 AMOUNT

Supplying, fixing in position approved make following mentioned diameter Foot Valve conforming to IS 778 with unions etc., complete.

TOTAL FOR WATER SUPPLY SYSTEM

For Employer

Page 14 of 31

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad C

1

2

PUMPS & MOTORS Supply of Vertical Multi stage Centrifugal Pump with suitable capacity 415V, 3-phase,50Hz motor and coupling with base frame having discharge capacity of 10 Cum/Hr against total head of 65m from all causes, with starter consists of suitable MPCB, Cont actor, Overload relay, Single Phase Prevent or, Push buttons, LED on indicators, all in comings in Weather Proof box and necessary suitable copper cables from starter panel to pump etc., complete as required.(Domestic Water Lifting Pump) Each Pump capacity : 10.0 cu.m/Hr No of Pumps : 1 working + 1 standby Delivery head : 65 m Suction : Negative of 3.0 meters Supply of Vertical Multi stage Centrifugal Pump with suitable capacity 415V, 3-phase,50Hz motor and coupling with base frame having discharge capacity of 5 Cum/Hr against total head of 65m from all causes, with starter consists of suitable MPCB, Cont actor, Overload relay, Single Phase Prevent or, Push buttons, LED on indicators, all in comings in Weather Proof box and necessary suitable copper cables from starter panel to pump etc., complete as required.(Flush Water Lifting Pump) Each Pump capacity : 5.0 cu.m/Hr No of Pumps : 1 working + 1 standby Delivery head : 65 m Suction : Negative of 3.0 meters

For Employer

Date: 28-Aug-2013 RATE

Set

1.00

Set

1.00

Page 15 of 31

Rev: R0 AMOUNT

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad

3

4

5

Supply, delivery, testing, commissioning of De-watering submersible pump made of Cast Iron Construction .Impeller shaft shall be S.S construction with mechanical seal suitable for building application..The unit shall include TEFC motor suitable for 415V,3Phase,50Hz & Insulation -Class F,IP 68 Protection and Automatic ON/OFF Level Switch, Base plates,Coupling,Nylon ropes for lifting pumps with necessary control cables etc,complete.(De water Pumps for Lower Basement floor Drain) Each Pump capacity : 50.0 cu.m/Hr No of Pumps : 1 working + 1 standby Delivery head : 20 m Supply, delivery, testing, commissioning of In line Booster pump with suitable capacity 230V, 1-phase,50Hz motor and coupling with base frame having discharge capacity of 5 Cum/Hr against total head of 20m from all causes , without starter, complete as required .The scope includes necessary pressure vessel & switch for the auto on/off of the pump. Each Pump capacity : 5.0 cu.m/Hr No of Pumps : 1 working + 1 standby Delivery head : 20 m Pressure Vessel for Auto ON/OFF : 25 Ltrs Capacity Supply, delivery, testing, commissioning of De-watering submersible pump made of Cast Iron Construction .Impeller shaft shall be S.S construction with mechanical seal suitable for building application..The unit shall include TEFC motor suitable for 415V,3Phase,50Hz & Insulation -Class F,IP 68 Protection and Automatic ON/OFF Level Switch, ,Base plates,Coupling,Nylon ropes for lifting pumps with necessary control cables etc,complete.(Drain water lifting pump at pump room) Each Pump capacity No of Pumps Delivery head

For Employer

Date: 28-Aug-2013 RATE

Set

2.00

Set

1.00

Set

1.00

Rev: R0 AMOUNT

: 5.0 cu.m/Hr : 1 working + 1 standby : 20 m

Page 16 of 31

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad D

1

RATE

TOTAL FOR PUMPS & MOTORS INTERNAL & EXTERNAL SANITARY PIPING SYSTEM

Rev: R0 AMOUNT

Supply,fixing of 150mm deep Multi floor traps of self cleansing design with following mentioned outlet diameter of approved make, including making connection with PVC soil/waste pipes using rubber gaskets and top shall be covered with removable CP strainer & cockroach jolly etc., complete all as specified & directed. a) 110mm dia. b) 75mm dia.

2

Date: 28-Aug-2013

NO's NO's

16.00 180.00

RMT RMT RMT

250.00 550.00 310.00

Supply,laying of under floor UPVC drainage pipes, specials of approved make conforming to to IS:13592 Type 'B' (6 kg/sq.cm.) using lubricant as per manufacturer's specification, including cutting the pipes square to the required lengths, necessary wall cutting, chasing & restoring to the original condition, testing for water tightness etc. (Specials at junctions of lateral pipe must have access doors for inspection).The formation of pipe sockets by heating the pipe shall not be permitted the joints for plain ended pipes shall be made using couplers if necessary. Rate shall also include the cost of GI 'U' clamps of 12/16mm thick to be provided at not more than 1.5m c/c for horizontal ceiling suspended pipes. (Concealed & Ceiling Suspended Piping) .The scope includes FRP sealant for all UPVC pipe joints for ceiling susspended pipes where ever it is necessary. a) 40mm Dia. b) 75mm Dia. c) 110mm Dia.

For Employer

Page 17 of 31

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad

Date: 28-Aug-2013 RATE

3

Rev: R0 AMOUNT

Supply,laying of under floor UPVC drainage pipes, specials & rubber rings of approved make conforming to to IS:13592 Type 'B' (6 kg/sq.cm.) and as per manufacturer's specification, including cutting the pipes square to the required lengths, necessary wall cutting, chasing & restoring to the original condition, testing for water tightness etc., (Specials at junctions of lateral pipe & vertical stack must have access doors for inspection and vent cowls for soil,waster water & anti siphonage pipes). The formation of pipe sockets by heating the pipe shall not be permitted the joints for plain ended pipes shall be made using couplers if necessary. Rate shall also includes the cost of GI 'U' clamps to be provided at not more than 2.0m c/c for vertical pipes . The GI 'U' clamps shall be made of hot dip galvanized 10mm dia MS rod threaded at both ends and of length to suit the secure fixing of the pipe on the bracket of the clamping system with necessary nuts, plate washers and rubber insertions etc., complete (Vertical Down Take Pipes). a) 75mm Dia. b) 110mm Dia. c) 160mm Dia.

For Employer

RMT RMT RMT

750.00 400.00 URO

Page 18 of 31

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad

Date: 28-Aug-2013 RATE

4

Rev: R0 AMOUNT

Providing, laying, jointing MDPE pipes and specials PE-80 grade (PN 6 Class )conforming to As per ISO4427-1996 Suitable for Max allowable design stress of 6.3MPA (SDR11) by electrofusion jointing as per manufacturers specifications, providing flanges for fixing of valves as required, including hydrostaitc pressure testing the pipe system to a hydraulic pressure of 7kg/sq.cm or 3 times the working pressure whichever is higher, the pipe system shall be observed for a period of not less than 6 hours, making good leaks if any etc., complete.The scope includes necessary Electrofusion Couplers,Tees ,bends and,necessary tapping saddles etc.complete.Rate shall also includes the cost of GI 'U' clamps to be provided at not more than 1.0m c/c for horizontal pipes . The GI 'U' clamps shall be made of hot dip galvanized 10mm dia MS rod threaded at both ends and of length to suit the secure fixing of the pipe on the bracket of the clamping system with necessary nuts, plate washers and rubber insertions etc., complete(7th & 6th Floor ceiling suspended & basement header pipes) i) 160MM DIA. ii) 110MM DIA. iii) 75MM DIA. iv) 200MM DIA.

For Employer

RMT RMT RMT RMT

80.00 20.00 40.00 200.00

Page 19 of 31

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad

5

6

7

Date: 28-Aug-2013 RATE

Supply ,fixing of pipe support system for pipes using brackets of length as per details fabricated from 50x50x6mm or suitable MS angles etc., as per approved design and drawings. The brackets shall be fixed to the wall at all levels at a distance not less than 2.0m c/c at all heights up to 80m above ground level with necessary scaffolding as necessary with 4 Nos of 10mm dia.expansion fasteners having a safe working load of 150 kg each with necessary nuts, washers etc.,complete. The brackets shall be installed true to plumb vertically with necessary insertions, spacer blocks etc as required etc., complete. The clamps shall be painted with 2 coats of approved synthetic enamel paint over a coat approved metal primer. Note: The length of the bracket shall be equal to the sum of the outer diameters of all pipe and 50mm for working space per pipe of size 15 to 75mm and 100mm for working space per pipe for pipes of size 75mm and above diameters. Supplying, installing, testing and commissioning of R.C.C Socket and Spigot Pipes(NP2 CLASS) conforming to BIS 458/1988, laid to the required level and grade with rubber rings / joining in CM 1:3 and filling the excavated trench with approved quality saturated sand on sides, bottom and top surface of pipe with all leads and lifts, making necessary connections as required etc., complete. a) 225mm Dia b) 300mm Dia Providing weep hole for raised floor toilet area with 40mm pipe for draining moisture, including making necessary holes in the sunk slab, placing pipe sleeve in position, grouting the opening in CM 1:2 etc., complete.

For Employer

Kg

Rev: R0 AMOUNT

1678.00

RMT RMT

URO URO

No's

40.00

Page 20 of 31

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad

8

9

10

11

Date: 28-Aug-2013 RATE

Supplying and fixing cast brass clean out plug with suitable insert keys for opening male threaded plug jointed to GI socket caulked to soil & waste pipe as required & completed… No's No's No's No's

10.00 35.00 15.00 6.00

No's

12.00

a) 110mm dia. b) 160mm dia. c) 65mm dia.

No's No's No's

140.00 110.00 50.00

Supplying, installing and commissioning of the ACO make grease separators model no ECO-FPI NS-2 with necessary Extension RCC rings, with direct suction with concrete cover and cover and cover plate of load class D 400 with 120 lites and sludge storage of 400 liters.

Each

1.00

a) 75 mm dia b) 110 mm dia c) 160 mm dia d) 200 mm dia Supply of vent pipes mosquito proof grating suitable for the ventilation purpose of the various tanks

Rev: R0 AMOUNT

Drilling with core cutting machine in RCC floor slab etc., for laying pipes and rendering the same in RCC 1:2:4, finishing the same to the satisfaction of the owner or his authorized representative etc., including nominal reinforcement wherever required, . The quoted rate shall also include for providing EPOXY based water proofing compound for sealing the joints around the pipes as approved by site incharge.

For Employer

Page 21 of 31

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad

Date: 28-Aug-2013 RATE

12

Construction of Inspection Chamber with best quality, approved fly ash bricks in CM 1:6, 600x600x1000mm depth over a bed of 150mm thick PCC 1:4:8, walls plastered smooth inside in CM 1:3 and outside with CM 1:3 with sponge finish benching and channeling in PCC 1:2:4. The Inspection Chamber shall be provided with 600x600mm rectangular medium duty approved make frame and cover etc., complete. The quoted rate shall also include for necessary excavation, refilling, disposing off surplus earth with in a lead of 300M etc., complete.

Each

3.00

13

Providing & laying best quality Salt glazed stoneware gully trap of size 100mm square with 100mm outlet embedded in plain cement concrete 1:4:8 (20mm metal), providing & fixing 100mm square CI grating on top of the trap, all the above encased in a chamber of 300x300mm built with 115mm thick brick masonry using first class country bricks in CM 1:3 over a bed of CC 1:4:8 using 40mm down size metal 100mm thick, plastering with CM 1:3,13mm thick inside,exposed to surface, finished smooth with a floating coat of neat cement, providing & fixing SFRC frame & cover of size 300x300mm etc., complete all as specified & directed.

Each

5.00

E

Rev: R0 AMOUNT

TOTAL FOR INTERNAL & EXTERNAL SANITARY PIPING SYSTEM RAIN WATER DISPOSAL SYSTEM

For Employer

Page 22 of 31

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad

Date: 28-Aug-2013 RATE

1

Supply,laying of under floor UPVC drainage pipes, specials & rubber rings of approved make conforming to to IS:13592 Type 'B' (6 kg/sq.cm.) and as per manufacturer's specification, including cutting the pipes square to the required lengths, necessary wall cutting, chasing & restoring to the original condition, testing for water tightness etc., (Specials at junctions of lateral pipe & vertical stack must have access doors for inspection and vent cowls for soil,waster water & anti siphonage pipes). The formation of pipe sockets by heating the pipe shall not be permitted the joints for plain ended pipes shall be made using couplers if necessary. Rate shall also includes the cost of GI 'U' clamps to be provided at not more than 2.0m c/c for vertical pipes . The GI 'U' clamps shall be made of hot dip galvanized 10mm dia MS rod threaded at both ends and of length to suit the secure fixing of the pipe on the bracket of the clamping system with necessary nuts, plate washers and rubber insertions etc., complete (Vertical Down Take Pipes). a) 160mm diameter b) 110mm diameter

2

Rev: R0 AMOUNT

RMT RMT

250.00 50.00

No's No's

6.00 2.00

Supply,fixing of PVC grating for inlet of rain water pipes at terrace level in CM 1:2, including making bores in the roof, setting in position and forming smooth rain water inlet gutter to direct rain water into the rain water pipe etc., complete all as specified and directed. a) 160x160mm b) 110x110mm

For Employer

Page 23 of 31

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad

3

4

F

1

2

Rain water recharge pit of size 2mx1.5m x3m clear size , two layers are top & bottom filled with 60mm metals up to depth of 600mm each , middle layer is filled with 40mm thick metal up to depth of 600mm thick, 1-2mm coarse sand of 200mm depth layers on the top of filter media, including with boring & laying of 150mm slotted G I epoxy coated pipes up to a depth of 6mtr long as directed includes with full size slotted RCC reinforced cover of 600x600x50mm on top and with necessary excavation, refilling etc. complete as directed & including all taxes , duties finish to complete item. Supply & installion of Heavy moulded(with stand up to 25.0 tons of vehicle load) 150mm wide x 150mm Depth x 1000 Length PVC ramp drain grating at entrance of the ramps(Each Ramp two No's) . Make : ECO TOTAL RAIN WATER DISPOSAL SYSTEM WATER TREATMENT PLANT WORKS Supply, installation, Testing & commissioning of Reverse Osmosis Plant(RO) , the features of the plant is , Plant skid made from MS (Powder coated) Pre filtration in FRP/ SS vessel. Pre filter with sediment and housing. High pressure pumps (Rotary vane type/ vertical) Anti scalene dosing pump. Membrane housing (FRP)/ Stainless Steel) High pressure & Low pressure control switch. Full electronic/ MCB panel with Auto water level sensor. High quality Astral PVC/ SS Piping. Membrane cleaning system. Fully automatic with TDS meter, flow meter & pressure gauge . (For Drinking Water Purpose only) Capacity : 500 Ltrs/Hour Supply ,installation of 500 Ltrs Food Grade HDPE/PVC water storage tank with required necessary accessories etc,complete.

For Employer

Date: 28-Aug-2013 RATE

No's

10.00

No's

12.00

Set

1.00

No's

1.00

Page 24 of 31

Rev: R0 AMOUNT

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad

3

Supply, installation, Testing & commissioning of Water Softener with strongly acidic cation exchanger in sodium ions and thus produce soft water of less than 50ppm ( Raw Water Hardness - 450 ppm).the plant for soft water in a period of 10 hours operation for following OBR with necessary accessories complete with frontal piping,valves,suitable supports for mounting pressure gauges,orifice plates. The filter shall be made of FRP with necessary accessories. The cost of filter shall also include initial charge of media to suit the requirement etc.complete as per standards.

Date: 28-Aug-2013 RATE

Set

1.00

Set

1.00

Rev: R0 AMOUNT

Capacity :7.5 Cum/Hour @ 75 Cum OBR(Output Between Regenaration) One vertical cylindrical pressure filter with dished ends made of Fibre with suitable nozzles and manhole. Design Pressure: 3 Kg per Cm2 Filter Media: acidic cation exchanger , One Charge Pressure guages to indicate loss of head (Which indicates when back wash is necessary) Floating message for operation and regeneration as Multiport valve with necessary accessories etc,complete and the scope includes Brine solution tank with necessary connections. Size of the Vessel : As per Manufacture Standard sizes

4

Supply, installation, Testing & commissioning of Pressure Sand Filter with necessary accessories complete with frontal piping,valves,suitable supports for mounting pressure gauges,orifice plates. The filter shall be made of FRP with necessary accessories. The cost of filter shall also include initial charge of under bed with pebbles & Coarse Sand media to suit the requirement etc.complete as per standards. Capacity :7.5 Cum/Hour @ 75 Cum OBR(Output Between Regenaration)

For Employer

Page 25 of 31

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad

Date: 28-Aug-2013 RATE

One vertical cylindrical pressure filter with dished ends made of Fibre with suitable nozzles and manhole. Design Pressure: 3 Kg per Cm2 Filter Media: Coarse Sand , Capacity : One Charge Pressure guages to indicate loss of head (Which indicates when back wash is necessary) Floating message for operation and regeneration as Multiport valve with necessary accessories etc,complete . Size of the Vessel : As per Manufacture Standard sizes

5

Supply, installation, Testing & commissioning of Activated Carbon Filter with necessary accessories complete with frontal piping,valves,suitable supports for mounting pressure gauges,orifice plates. The filter shall be made of FRP with necessary accessories. The cost of filter shall also include initial charge of under bed with pebbles & Activated carbon filter media to suit the requirement etc.complete as per standards.

Set

Rev: R0 AMOUNT

1.00

Capacity :7.5 Cum/Hour @ 75 Cum OBR(Output Between Regenaration) One vertical cylindrical pressure filter with dished ends made of Fibre with suitable nozzles and manhole. Design Pressure: 3 Kg per Cm2 Filter Media: Activated Carbon Capacity : One Charge Pressure guages to indicate loss of head (Which indicates when back wash is necessary) Floating message for operation and regeneration as Multiport valve with necessary accessories etc,complete . Size of the Vessel : As per Manufacture Standard sizes

For Employer

Page 26 of 31

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad

6

Supply of Vertical Multi stage Centrifugal Pump with suitable capacity 415V, 3-phase,50Hz motor and coupling with base frame having discharge capacity of 7.5 Cum/Hr against total head of 35m from all causes, with starter consists of suitable MPCB, Cont actor, Overload relay, Single Phase Prevent or, Push buttons, LED on indicators, all in comings in Weather Proof box and necessary suitable copper cables from starter panel to pump etc., complete as required.

Date: 28-Aug-2013 RATE

Set

Rev: R0 AMOUNT

1.00

Pump Capacity : 7.5 Cum/Hour @ 35 meter Head No of pumps : 1Working + 1 Stand by Suction : Negative (3.0 meter) 7

8

Supply, installation, Testing & commissioning of UV - sterilization plant .The plant consists of Rinsing set for UV-disinfection plants for cleaning of deposits on quartz and internal surface of protective tube. Flow Capacity : 7.5 Cum/Hour Supply,Installation ,Testing & Commissioning approved make Electronic dosing system for dosing Hypo chlorite solution or any other equivalent to the bio medical waste with pre-set dosage based on the quantity of water.The dosing system shall consist of Electronic dosing pump with positive displacement type with adjustable stroke length and frequency.The quoted rate shall also include FRP chemical solution tank,necessary electricals etc.complete to make the operation automatic. Max.Working Pressure = 3.0 Kg/SqCm Max.Flow Rate = 1 Litre/Hr @ 20 Hr Cycle

For Employer

URO

Set

1.00

Page 27 of 31

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad

9

10

G

Supply,Installation ,Testing & Commissioning approved make Electronic dosing system for dosing residual chlorine to the stp treated water at terrace over head tank with pre-set dosage based on the quantity of water.The dosing system shall consist of Electronic dosing pump with positive displacement type with adjustable stroke length and frequency.The quoted rate shall also include FRP chemical solution tank,necessary electricals etc.complete to make the operation automatic. Max.Working Pressure = 3.0 Kg/SqCm Max.Flow Rate = 1 Litre/Hr @ 20 Hr Cycle Providing, laying, jointing, fixing, testing & commissioning of piping sytem with UPVC SCH-40 pipes fittings,required valves and instruments for processing in treatment plant. The scope includes cutting the pipes to required lengths, jointing the pipes using solvent joint type. And necessary chasing the walls / floors, making holes, clamping to walls and restoring the same to original conditions etc., complete all as specified and directed and as per manufacturer's specification.

Date: 28-Aug-2013 RATE

Set

1.00

Lot

1.00

Rev: R0 AMOUNT

TOTAL FOR WATER TREATMENT PLANT WORKS HOT WATER SYSTEM

For Employer

Page 28 of 31

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad

Date: 28-Aug-2013 RATE

1

2

3

Rev: R0 AMOUNT

Supply ,Installation, testing and commissioning of Solar water heater comprising of solar collectors, storage tank, associated piping and controls. The collectors shall consists of 1.4mm thick Aluminum collector frame, toughened clear glass for covering, 50mm Rock wool Insulation for bottom & 25mm insulation for sides. The absorber plate shall be of 36 SWG copper & NaLSUN coating. Reflective foil of 0.05mm thick & Grommet is of EPDM, riser & inlet shall be of copper. The collector size shall be 2080mm x 1070mm x 100mm. & the absorber area is 2 Sq.Mt. 9 No. of riser tubes & absorber plate per collector with 88% glazing transmitivity. The coating absorptivity is 0.95 & coating emissivity is 0.16. The absorber riser bonding shall be continuous bonding. The storage tank shall be SS 304 grade(Wall Thickness of the tank shall be 3.0mm) with built in thermostat ,auto air vent & drain valves to be provided for the system, insulation of the tank shall be of Rock wool with Aluminum cladding material. Necessary valves & internal piping shall be made, with ISI fittings or equivalent as directed by the Engineer-in -charge. Capacity : 2000 Ltr Supplying,installing,testing and commissioning approved make cast brass body Digital water meter with necessary unions,valves for fixing on the cold water main ,etc., complete a) 32 mm nominal dia Supplying,installing,testing and commissioning approved make cast brass body Digital water meter with necessary unions,valves for fixing on the Hot water main ,etc., complete . a) 25 mm nominal dia

For Employer

Set

2.00

No

1.00

No

1.00

Page 29 of 31

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad

4

5

Supply ,intallation,testing & commissioining of of Air Source Water Heating System including the necessary accessories and safeties and capable of delivering hot water at 60 Deg.C.The scope includes automatic control panel microprocessor controller along with necessary accessories. Please refer specifcations for rated input & output capacities. Heat Pump Capacity:750 Ltrs / Hour

Date: 28-Aug-2013 RATE

No

2.00

Set

1.00

Rev: R0 AMOUNT

Supply ,installation & testing of MS fabricated floor supported Horizontal type/ Vertical type storage tank ,internally lined with SS with an adequate wall thickness, fabrication with dish ends and 500mm of top manhole with pad plates .It consists of Solar water Input & Output,Incoming connections for Re Circulation Water , thermostat ,auto air vent & drain valves to be provided for the system.Tank shall be insulated with 100 mm thick rock wool insulation of 48 kg/cu.m. density having approx. k value_0.03 W/mk and R value 3.34 sq.m deg.C/W to withstand a temp. of 250deg.c.Thin polythene sheet shall be used as covering between the glass wool and the cladding sheet besides the retaining material such as chicken mesh etc. Aluminum sheet of thickness 24 SWG shall be used for cladding the tank insulation. The storage tank shall be properly installed at site using enameled coated appropriate size angle iron stands, girder, cement concrete pedestals of 1:2:3 ratio or any other specific provision suitable to site.To ensure the stability against heavy storm etc. but not less than 1’x1’x6” dimensions. External of the tank should be properly insulated so that hot water temperature does not decrease by more than 5 deg.C in about 16 hrs. Times. Necessary valves & internal piping shall be made, with ISI fittings or equivalent as directed by the Engineer-in -charge. Capacity : 4,000 Ltrs

For Employer

Page 30 of 31

For Contractor

Project : Expansion of Yashoda Hospital- Phase-1 Client:Yashoda Hospitals

Package: Supply,Installation,Testing and Commissioning of Internal and External Plumbing Works

Architect: SMJ Design Inc PMC: KP Management Associates MEP Consultant: Synergy Infra Consultant Pvt Ltd

BOQ

Interior Consultant: M/s. Prasad Badle Architects Location: Somajiguda-Hyderabad

6

7

Supply, delivery, testing, commissioning of Hot Water distribution pump with suitable capacity 230V, 1-phase,50Hz motor and coupling with base frame having discharge capacity of 5 Cum/Hr against total head of 20m from all causes, without starter, complete as required. The scope includes necessary pressure vessel & switch for auto on/off for the pumps. Each Pump capacity : 5.0 cu.m/Hr No of Pumps : 1 working + 1 standby Delivery head : 20 m Pressure Vessel for Auto ON/OFF : 25 Ltrs Capacity Supply, delivery, testing, commissioning of two stage centrifugal pump with suitable capacity 230V, 1-phase,50Hz motor and coupling with base frame having discharge capacity of 2.0 Cum/Hr against total head of 15m from all causes, without starter, complete as required.(Hot Water recirculation pump). Each Pump capacity : 2.0 cu.m/Hr No of Pumps : 1 working + 1 standby Delivery head : 15 m Timer controller : 24Hours Operated TOTAL FOR HOT WATER SYTEM GRAND TOTAL

For Employer

Date: 28-Aug-2013 RATE Set

1.00

Set

1.00

Page 31 of 31