PLANOS INTERRUPTOR ALSTOM
October 11, 2017 | Author: dielcord90 | Category: N/A
Short Description
Descripción: alstom...
Description
A
B
CIRCUIT BREAKER INTERRUPTOR
1
CABINET LIGHT LUZ DEL GABINETE
COIL BOBINA CONTACT, NORMALLY CLOSED CONTACTO, NORMALENTE CERRADO CONTACT, NORMALLY OPEN CONTACTO, NORMALENTE ABIERTO CONNECTOR CONNECTOR DENSITY MONITOR INTERRUPTOR DE PRESION
2
DOOR SWITCH INTERRUPTOR DE LA PUERTA FUSE BLOCK FUSIBLE
FUSE PULLOUT, SLUGGED FUSIBLE DESCONECTADO
C
D
STANDARD ANSI DESIGNATIONS (DESCRIPCIONES - NORMAS ANSI)
WIRING KEY CODIGO DEL CABLEADO
01CS BREAKER CONTROL SWITCH ~ INTERRUPTOR DE CONTROL DEL INTERRUPTOR INDICATOR LIGHT LUZ INDICADORA
23 THERMOSTAT ~ TERMOSTATO
28
23X HEATER CONTACTOR ~ CONTACTO DE LA CALEFACCIÓN
ES:14
ES:A1
1
27X LOSS OF POWER RELAY ~ RELÉ DE PERDIDA DE POTENCIA KNIFE SWITCH CUCHILLA
30 ANNUNCIATOR ~ TABLERO INDICADOR
SOURCE PIN NUMBER
37 UNDERCURRENT ALARM ~ ALARMA DE CORRIENTE BAJA 43L/R LOCAL / REMOTE TRANSFER SWITCH ~ SELECTOR LOCAL / REMOTO
CHARGING MOTOR MOTOR DE CARGA
DESTINATION DEVICE DESIGNATION
NÚMERO DE TERMINAL DE ORIGEN
49 MOTOR THERMAL OVERLOAD ~ PROTECCIÓN TÉRMICA DE SOBRE CARGA
DENOMINACIÓN DEL APARATO DE DESTINO
DESTINATION PIN NUMBER NÚMERO DE TERMINAL DE DESTINO
SECOND DESTINATION IF APPLICABLE DESTINO SECUNDARIO (SI APLICA)
52a,b BREAKER AUXILIARY SWITCH ~ INTERRUPTOR AUXILIAR 52C CLOSE PUSHBUTTON ~ BOTÓN DE CIERRE PUSH BUTTON BOTÓN PULSADOR
52CC BREAKER CLOSE COIL ~ BOBINA DE CIERRE
CONTROL STATION TABLERO DE CONTROL
52T TRIP PUSHBUTTON ~ BOTÓN DE DISPARO
TOP VIEW OF CONTROL CABINET VISTA DE ARRIBA DEL GABINETE DE CONTROL
52TC BREAKER TRIP COIL ~ BOBINA DE DISPARO RESISTOR / HEATER RESISTENCIA / CALEFACCIÓN TERMINAL BLOCK TABILLA TERMINAL
52X CLOSING RELAY ~ RELÉ DE CIERRE DROP OUT PANEL PLACA REMOVIBLE
MECHANISM MECANISMO
52Y ANTIPUMP RELAY ~ RELÉ ANTIBOMBEO 52-MON BREAKER CONDITION MONITOR ~ IDENTIFICADOR DE POSICÓN
2
RELAY PANEL PANEL DE RELES
63G SF6 PRESSURE / DENSITY GAUGE ~ DENSÍMETRO 63GX SF6 PRESSURE / DENSITY RELAY ~ RELÉ DEL DENSÍMETRO
TERMINAL BLOCK (AUXILIARY) TABILLA TERMINAL (AUXILIAR)
69 PERMISSIVE CONTROL SWITCH ~ INTERRUPTOR DE CONTROL PERMISIVO 69-KI KEY INTERLOCK ~ ENCLAVAMIENTO
THERMOSTAT TERMOSTATO
74CC CLOSE COIL MONITOR ~ RELÉ DE LA BOBINA DE CIERRE
CONTROL TERMINALS TABLERO DE LAS TABILLAS
74TC TRIP COIL MONITOR ~ RELÉ DE LA BOBINA DISPARO
GROUND BAR BARRA DE PUESTA A TIERRA
79X RECLOSE DELAY RELAY ~ RELÉ DE DEMORA DE RECIERRE FUSE BLOCK, SLUGGED FUSIBLE
THERMAL OVERLOAD SOBRE CARGA TERICA
FUSED DISCONNECT, SLUGGED FUSIBLE SECCIONADOR
3
FUSE PULLOUT FUSIBLE SECCIONADOR
88 MOTOR ~ MOTOR 88F MOTOR FAILURE ALARM ~ ALARMA DE FALLA DEL MOTOR
FUSED DISCONNECT FUSIBLE SECCIONADOR TOGGLE SWITCH CONMUTADOR DE PALANCA
AIL AMBER INDICATOR LIGHT~ LUZ NARANJA
NUMERO DE SERIE DEL INTERRUPTOR BREAKER SERIAL NUMBER
HTR HEATER ~ CALEFACCIÓN
NUMER DE PARTE DE ALSTOM
163783-010-A
RIL RED INDICATOR LIGHT ~ LUZ ROJA
4
CC-DT1-72-145FK- REV6
TABLA 1. TABLA DE REFERENCIA DEL ENCLAVAMIENTO MECANICO TABLE 1. KEY INTERLOCK REFERENCE TABLE
88LS MOTOR LIMIT SWITCH ~ INTERRUPTOR AUXIILAR
GIL GREEN INDICATOR LIGHT ~ LUZ VERDE TRANSFORMER TRANSFORMADOR
BCT TERMINALS TERMINALES DE LOS TC
83X MOTOR TRANSFER CONTACTOR ~ CONTACTO DEL MOTOR
NUMERO DE LLAVE
ALSTOM PART NUMBER
KEY NUMBER
CC410666-034
21472
NUMERO DE ORDEN DE COMPRA ALSTOM ALSTOM PO NUMBER
3485-CC163783
N ALSTOM PEDIDO # REV.
DESCRIPCIÓN
A
DIBUJADO
VERIFICADO
FECHA
W.Holt
A.Izvorean
02/21/14
DIBUJADO
VERIFICADO
FECHA
B
C
3
D
4
A
B
C
CLOSE CIRCUIT (CIRCUITO DE CIERRE) TB1
16A
TB1
3
1
PB1
4
CUSTOMER REMOTE CLOSE
TB2
SCC 7
11
12
INDICACION DE APERTURA REMOTA
REMOTE OPEN INDICATION
7R
GIL
SET RECLOSER AT NO LESS 43L/R THAN 20 CYC.
13
DISPARO DE EMERGENCIA EXTERNO
CONTACTO AUXILIAR REMOTO 5 PARA CIERRE REMOTO
52C
TB1 1 TB9
TB3 7
AJUSTAR EL RECIERRE A NO MENOS DE 20 CICLOS
SCC
TB10
109
13
ER
8
SCC
2
3
S2
16A
3
122
MB1 13 88LS a
1A
CUSTOMER REMOTE TRIP
MB1 1
15
8
9
1 MANUAL RESET
69
2 125 VDC
16A
SCC
RIL
INDICACION CERRAR
3
ER
43L/R
18
TB2
SCC 61
EA1
TB2
9A
EA1
63GX1
62
SCC
12
69-KI
13
ES
52Y
MA1 14
EA1
63GX1 125 VDC
TB3
19
TB3
TB3
20
TB10
ADD JUMPER TO TRIP ON LOW SF6
63GX1
22
ES
21
112
3W 3D
52Y
22
TB10
3
113 1
3
MA1
9 52Y
52-1 b
10
12
MA1 52-1 b
88LS b
10
4
14
AÑADIR UN PUENTE PARA EL DISPARO EN BAJO SF6
MA1 52-1 b
TB9
1 2
MA2 52-2 a
102
9 10
MA2 52-2 b
3
63G 47.9 psig 4 4D
11
MA1 13
TB10
118
EGA
4W A1
1
AT2
2
1
MD
52TC1 35.5 OHM MAX CONT. PWR 4W
2
EA1
63GX1
MB1
9
A2
115
52CC 35.5 OHM MAX CONT. PWR 4W
2
ES
TB10
MC
AT2
101
3
52-1 a
ADD JUMPER TO TRIP ON LOW SF6
TB9
116
AÑADIR UN PUENTE PARA EL DISPARO EN BAJO SF6
63GX1
44
17
EA1
21
2
EA1
43
14
125 VDC
52-1 a
TB10
4
ER
SCC
SCC
K1
TB10
TB1 3
9AR
22
18
2
23
INDICACION CERRAR
19
SCC
A1
21
32
SCC 13
2
TB2
SCC
17
4
TB3
1
4
52T3
16
11
13
EE
1
CLOSED INDICATION
52T2
63GX1
2
111
11A
PB3
9
31
APERTURA REMOTA DEL CLIENTE
TB2
3
2
1
KIRK KEY INTERLOCK
5
9R
17
15
10
ENCLAVAMIENTO
SCC
S3
16
CONTACTOS LIBRES DEL FIN DE CARRERA DEL MOTOR
LA1
CLOSED INDICATION
2
CUSTOMER REMOTE TRIP
43L/R
TB9 SPARE MOTOR LIMIT SWITCH CONTACTS
BLOQUEO OPCIONAL DEL CLIENTE
OPTIONAL CUSTOMER LOCKOUT
TB2
SCC
14
110
7
SCC
TB2
SCC
52T3
2
TB2
1B
11
PB2
4
EE
TB1 1
TB2
RIL
88LS b
14
APERTURA REMOTA DEL CLIENTE
52T1
8
RESETEO MANUAL
(DIAGRAMA ELEMENTAL 125VCD)
EXTERNAL TRIP
1
S1
1
ELEMENTARY DIAGRAM 125VDC
TRIP 2 CIRCUIT (CIRCUITO DE DISPARO 2)
TRIP 1 CIRCUIT (CIRCUITO DE DISPARO 1)
SCC
2
1
D
A2
2A
4
S2
16A
4
SCC
52TC2 35.5 OHM MAX CONT. PWR 4W
TB10
TB10 TB1 3
ME
119
117
TB1 3
TB2
2B
10
4
SCC 6
S3
16A
TB2
10A
TB10
SCC
114
2
S1
TB1
16A
6
NOTAS: 1) TODOS LOS DISPOSITIVOS SON MOSTRADOS EN POSICION DESENERGIZADOS. 2) EL INTERRUPTOR SE ENCUENTRA ABIERTO. 3) LA PRESION DE GAS SF6 EN CERO. 4) CONTACTOS PRINCIPALES CON RESORTE ABIERTO Y RESORTE CERRADO. 5) EL SELECTOR LOCAL/REMOTO ESTA LA POSICION LOCAL NOTES: 1) ALL DEVICES SHOWN IN DE-ENERGIZED POSITION. 2) BREAKER IN OPEN POSITION. 3) SF6 AT ZERO PRESSURE. 4) CLOSING SPRING SHOWN IN CHARGED POSITION 5) LOCAL/REMOTE SWITCH SHOWN IN LOCAL POSITION
NUMERO DE MATERIAL DE ALSTOM
CLIENTE: I No. de PE 4 SUBESTACIÓN: No. de SERIE: 1
4
CCDT1-72.5FK-065
ALSTOM PEDIDO # REV.
DESCRIPCIÓN
DC CONTROL CIRCUIT CABLEADO DE CONTROL DE CC
A
DIBUJADO
VERIFICADO
FECHA
W.Holt
A.Izvorean
02/21/14
DIBUJADO
VERIFICADO
FECHA
B
163783
No. de EQUIPO DEL CLIENTE: ALSTOM GRID Inc. One Power Lane Charleroi, PA 15022
C
NUMERO de DIBUJO:
E163783010
HOJA 2
D
de 14
4
A
B
C
1
SPARE TERMINAL BLOCKS FOR CUSTOMER USE
ELEMENTARY DIAGRAM 125VDC
MOTOR CIRCUIT TB1
D (TERMINALES LIBRES)
(DIAGRAMA ELEMENTAL 125VDC)
(CIRCUITO DEL MOTOR) 125VDC
TB1
TB1
B1
B2
TB2
TB4
B3
28
TB4 TB5 29
62
2
1
S4
3
16A 1
TB7
TB7
85
86
DT1
TB8
TB8
97
98
TB9
TB5
TB6
TB6
61
73
74
1
TB9
99
100
49 10-16A 2 3
DT1
49 10-16A 4
TB9
103
CONTACTOS LIBRES DE FIN DE CARRERA DEL MOTOR
88LS a
2
SPARE MOTOR LIMIT SWITCH CONTACTS
2
TB9
107
MB1
11
88LS b
12
88LS a
6
MB1
MA1 15
8
16
52-1 a
TB5
TB5
TB5
55
MA1 52-1 b
TB5
57
3
MA2 11
4
12
TB5
52
TB6
59
52-2 b
TB6
63
5
MA2 13
6
14
TB6
TB6
65
52-2 b
67
7
MA2 15
8
16
TB6
71
69
52-2 b
1 2
52-3 a
52-3 b
10
2
TB6
72
TB8
91
MA3
9
TB6
TB8
89
MA3
70
68
TB8
87
MA2
TB6
66
TB8
83
52-2 a
TB6
64
TB7
81
MA2
TB6
60
TB7
79
52-2 a
TB5
58
TB7
77
MA2
TB5
56
TB7
75
52-2 a
TB5
54
TB7
TB9
TB8
93
95
104
TB9
TB9
7
88LS a
4
106
108
88 125VDC/AC 1.6 kW
3
MB1
5
TB5
53
M1
T2
105
TB5
51
T1
TB9
(INTERRUPTOR AUXILIAR)
MB1
1
125VDC
SPARE AUXILIARY SWITCHES FOR CUSTOMER USE
5
DT1
49 10-16A
3
MA3 11
4
12
52-3 a
MA3 52-3 b
5
MA3 13
6
14
52-3 a
MA3 52-3 b
7
MA3 15
8
16
52-3 a
MA3 52-3 b
1 2
MA4 52-4 a
9 10
MA4 52-4 b
3
MA4 11
4
12
52-4 a
MA4 52-4 b
6
TB1
4
3
S4
4
16A
76
78
80
82
84
88
90
92
94
96
TB7
TB7
TB7
TB7
TB7
TB8
TB8
TB8
TB8
TB8 TB10
CUSTOMER ALARMS
120
(ALARMAS DEL CLIENTE) TB3
TB3
21
3
5W 5D
AT2
5
23 1W
1
EGA
63G 47.9 psig
6D 6W
63G 52.2 psig
2
AT2
25
27
2D 2W
TB11
123
TB11
127
24
TB3
TB3
52-4 a
6
129
TB10
31
33
ER
53
43L/R
EA1
63GX1
13
DT1 21 DT1
14
22
49
49
NOTAS: 1) TODOS LOS DISPOSITIVOS SON MOSTRADOS EN POSICION DESENERGIZADOS. 2) EL INTERRUPTOR SE ENCUENTRA ABIERTO. 3) LA PRESION DE GAS SF6 EN CERO. 4) CONTACTOS PRINCIPALES CON RESORTE ABIERTO Y RESORTE CERRADO. 5) EL SELECTOR LOCAL/REMOTO ESTA LA POSICION LOCAL
54
32
26
TB3
LOCAL/REMOTE LOW GAS LOCKOUT LOW GAS ALARM SWITCH BLOQUEO GAS BAJO ALARMA GAS BAJO SELECTOR LOCAL/ REMOTO
124
TB11 LOW GAS LOCKOUT BLOQUEO GAS BAJO
NOTES: 1) ALL DEVICES SHOWN IN DE-ENERGIZED POSITION. 2) BREAKER IN OPEN POSITION. 3) SF6 AT ZERO PRESSURE. 4) CLOSING SPRING SHOWN IN CHARGED POSITION 5) LOCAL/REMOTE SWITCH SHOWN IN LOCAL POSITION
128
TB11 MOTOR THERMAL OVERLOAD PROTECCIÓN TÉRMICA DEL MOTOR
NUMERO DE MATERIAL DE ALSTOM
CLIENTE: IN No. de PEDIDO: T SUBESTACIÓN: No. de SERIE: 1
4
CCDT1-72.5FK-065
ALSTOM PEDIDO # REV.
3
121
AT2
22
MA4
5
TB11
AT2
1D
EGA
6
TB3 TB3
DESCRIPCIÓN
MOTOR CIRCUIT & CUSTOMER ALARMS CIRCUITO DEL MOTOR & ALARMAS DEL CLIENTE
A
DIBUJADO
VERIFICADO
FECHA
W.Holt
A.Izvorean
02/21/14
DIBUJADO
VERIFICADO
FECHA
B
163783
No. de EQUIPO DEL CLIENTE: ALSTOM GRID Inc. One Power Lane Charleroi, PA 15022
C
NUMERO de DIBUJO:
E163783010
HOJA 3
D
de 14
4
A
B
C
D
1
1
HEATING (CALEFACCIÓN) 208VAC
TB4
31
2
1
S8
16A 1
2 1W 1D 1
2 208 VAC
2 2D 2W
TH1
23-1 45-90 F (7-32 C)
3W 3D
HT1
HT1
3
H1
4
95 W 600 OHM
H1 95 W 600 OHM
2
HT1
OUTLET & LIGHT (ENCHUFE Y LUZ) 120VAC
4
3
S8
16A
TB4
2
1
32
1
S6
20A
4
2
1 3
120 VAC
5
3
PL1 120 VAC
LS1
2
20 A
L1
1 - LINE 2 - NEUTRAL 3 - GND 4 - LOAD LINE 5 - LOAD NEUTRAL
L2
L1 GND
L1
3 NOTAS: 1) TODOS LOS DISPOSITIVOS SON MOSTRADOS EN POSICION DESENERGIZADOS. 2) EL INTERRUPTOR SE ENCUENTRA ABIERTO. 3) LA PRESION DE GAS SF6 EN CERO. 4) CONTACTOS PRINCIPALES CON RESORTE ABIERTO Y RESORTE CERRADO. 5) EL SELECTOR LOCAL/REMOTO ESTA LA POSICION LOCAL
TB4 33
7D
AT2
7W
EGA
7
GND
TH1 23-1
63G
GND1
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
NOTES: 1) ALL DEVICES SHOWN IN DE-ENERGIZED POSITION. 2) BREAKER IN OPEN POSITION. 3) SF6 AT ZERO PRESSURE. 4) CLOSING SPRING SHOWN IN CHARGED POSITION 5) LOCAL/REMOTE SWITCH SHOWN IN LOCAL POSITION
NUMERO DE MATERIAL DE ALSTOM
CLIENTE: I No. de PEDIDO: T4 SUBESTACIÓN: No. de SERIE: 1A
4
CCDT1-72.5FK-065
ALSTOM PEDIDO # REV.
DESCRIPCIÓN
AC CIRCUIT CABLEADO DE CONTROL DE CA
A
DIBUJADO
VERIFICADO
FECHA
W.Holt
A.Izvorean
02/21/14
DIBUJADO
VERIFICADO
FECHA
B
163783
No. de EQUIPO DEL CLIENTE: ALSTOM GRID Inc. One Power Lane Charleroi, PA 15022
C
NUMERO de DIBUJO:
E163783010
HOJA 4
D
de 14
4
2B B 2
8 2 1
(POTENCIA DEL MOTOR)
S4:1
MOTOR POWER
3
S4:3
4
130
(BARRA (+) PARA EL CIERRE)
CLOSE (+) BUS
SCC:1
5
131
(BARRA (-) PARA EL CIERRE)
CLOSE (-) BUS
TB10:114
6
132
3
9 2 1
4
MOTOR THERMAL OVERLOAD
(PROTECCIÓN TERMICA DEL MOTOR)
(MONITOREO REMOTO DEL DISPARO 2)
(RESORTE CARGADO)
(52a USADO EN EL CIRCUITO)
(CIRCUITO DE CIERRE)
(MONITOREO REMOTO DEL DISPARO 1)
52b
DT1:21
S3:3
52a
129
(LIBRE)
52b
DT1:22
SPARE
52a
128
7 2 1
SPARE (LIBRE)
DT1:13
6 2 1
SPARE (LIBRE)
127
B 1
100
1B
REMOTE TRIP1 MON.
S3:1
5 2 1
101
126
A 2
MA1:13
DC PWR TRIP 2
2A
(BLOQUEO POR GAS BAJO)
MOTOR CIRCUIR (CIRCUITO DEL MOTOR)
(CC PARA EL DISPARO 2)
125
S2:3
A 1
REMOTE TRIP2 MON.
DC PWR TRIP 1
1A
102
(CC PARA EL DISPARO 1)
S2:1
LOW GAS LOCKOUT
1
MA2:9
EA1:54
4 2 1
SPRING DISCHARGED (RESORTE DESCARGADO)
EA1:53
124
SPRING CHARGED
123 3 2 1
2
SPRING STATUS FORM C
2
52a USED IN CIRCUIT
S1:3
TB11
1
TRIP2 CIRCUIT
1
52a
S1:1
CLOSE CIRCUIT
TB1 DC PWR CLOSE
(CC PARA EL EL CIERRE)
(CIRCUITO DE DISPARO 1)
NOTAS: 1) TODO EL CABLEADO DE CA ES DE 12GA SIS VW1 GRIS 2) TODO EL CABLEADO DE CC ES DE 14GA SIS VW1 GRIS 3) TODOS LOS CABLES DE PUESTA A TIERRA SON DE 12GA SIS VW1 VERDE 4) LOS INDICADORES LOS CABLES SON TIPO ENCOGIDO Y TIENE LA MISMA DESIGNACIÓN EN AMBOS LADOS. 5) LAS PUNTAS DE LOS CABLES SON TIPO ANILLO (EXCEPTO PARA LOS APARATOS QUE NO ACEPTAN ESTE TIPO DE TERMINALES) 6) SCC:11 Y SCC:12 SON CONECTADOS CON UNA BARRA CORTO CIRCUITABLE DE DOS PUNTOS
SPRING STATUS FORM C
1
D
(CIRCUITO DE DISPARO 2)
NOTES: 1) ALL AC WIRING TO BE 12GA GRAY SIS VW1 2) ALL DC WIRING TO BE 14GA GRAY SIS VW1 3) ALL GROUND WIRES TO BE 12GA GREEN SIS VW1 4) WIRE MARKERS TO BE SHRINK-TYPE AND TO SHOW SAME-END/OPPOSITE-END DESIGNATION 5) WIRE LUGS ARE TO BE INSULATED RING-TYPE (EXCEPT FOR DEVICES THAT DO NOT ACCEPT RING-TYPE TERMINALS) 6) SCC:11 & SCC:12 ARE CONNECTED BY A 2PT SHORTING BAR
C
52b
B
TRIP2 CIRCUIT
A
0 3 1
5
SPARE
(LIBRE)
0 1
1
7 8
88
87 MA3:15
MA3:16
8
9 8
90
89 MA4:1
MA4:2
0 9
1 9
92
91 MA4:9
MA4:10
2 9
93 MA4:3
3 9
94 MA4:4
4 9
5 9
6 9
7 9
97
8 9
98
99 9
0 1
0 1
2 0 1
4 0 1
5 0 1
106 6 0 1
7 0 1
8 0 1
9 0 1
0 1
1
2 1
3 1
TB1:6,SCC:2 4 1
114
3 0 1
TB5
MA1:15
MA1:8
MA1:7
53
52
51 1 5
MA1:16 54
2 5
MA2:3 55
3 5
MA2:4 56
4 5
MA2:11
5
MA2:12
57
6 5
58
7 5
MA2:5
8 5
MA2:6
9 5
60
59
0 6
61 1 6
MA2:13 63
2 6
MA2:14 64
62
MA2:7 65
3 6
MA2:8 66
4 6
MA2:15
5 6
MA2:16 68
67
6
MA3:1
7 6
MA3:2
69
8 6
70
9 6
MA3:9 71
0 7
MA3:10
1 7
2 7
72
73 3 7
4 7
MA3:3 75
74
MA3:4 76
5 7
MA3:11 77
6 7
MA3:12
7
MA3:5
8 7
85
6 8
5 8
86
9 1
0 2
1 2
3
2
3 2
4 2
ER:31
25
ER:32
26
ER:33
27
5 2
6 2
9 2
52a
52b
52a
52b
52a
52b
52a
52b
52a
52b
52a
52b
52a
52b
(LIBRE) SPARE
8 2
29
(LIBRE) SPARE
28
52a
7 2
TB4 SPARE
78
LOCAL REMOTE SWITCH
79
(SELECTO LOCAL/ REMOTO)
9 7
24
MA3:6
AT2:2W
MA3:13
23
0 8
AT2:1W
80
LOW SF6 GAS ALARM
81
(ALARMA DE GAS SF6 BAJO)
MA3:14
22
MA3:7
AT2:6W
1 8
21
2 8
AT2:5W
82
SPARE DENSITY SWITCH CONTACT
83
20
3 8
SCC:19
8 1
MA3:8
19
7 1
4 8
EA1:44
3 1
84
18
(LIBRE)
TB6
3 B
(LIBRE) SPARE
3
TB7
TB8
B3
SCC:16
(CONTACTO LIBRE DEL DENSÍMETRO)
TB9
A 1
13
TRIP ON LOW SF6
TB10
A 0 1
17
(DISPARO POR SF6 BAJO)
5 1
R A 9
EA1:14
TRIP ON LOW SF6
6 1
A 9
TB10:115
(DISPARO POR SF6 BAJO)
2
ER:23 9AR
TB3 (INDICACIÓN ABIERTA REMOTA) REMOTE OPEN INDICATION
95
SPARE
96
(LIBRE)
MA4:11
11A
MA4:12
11
SCC:5
DT1:4
SCC:3
TRIP 2 (+) BUS
DT1:5
TRIP 1 (+) BUS
(BARRA (+) PARA EL DISPARO 2)
104
(BARRA (+) PARA EL DISPARO 1)
MB1:1 103
10A
MB1:4
SCC:6
105
TRIP 2 (-) BUS
MB1:5
(BARRA (-) PARA EL DISPARO 2)
MB1:6
10
108
SCC:4
MB1:11 107
TRIP 1 (-) BUS
109
(BARRA (-) PARA EL DISPARO 1)
MB1:7
9A
MB1:12
SCC:18
REMOTE TRIP 2
(ENCLAVAMIENTO DEL CIERRE DEL CLIENTE)
R 9
110
REMOTE PROT TRIP 2
(DISPARO 2 REMOTA)
9
MB1:8,MB1:14
(PROTECCIÓN DE DISPARO 2 REMOTA)
9
ES:14
9R
ES:13
ER:17
112
SCC:15
REMOTE TRIP 1
CUST CLOSE INTERLOCK
MA1:1 111
REMOTE PROT TRIP 1
(DISPARO 1 REMOTA)
TB2:7
MA1:2
(PROTECCIÓN DE DISPARO 1 REMOTA)
8
ES:22
8
TB3:13
SCC:9
MA1:11 115
CUST INTERLOCK
MB1:10,MA1:12
(ENCLAVAMIENTO DEL CLIENTE)
TB2:8
R 7
SCC:4
7R
SCC:16
ER:13
116
7
REMOTE CLOSE
117
119 ME:2
7
(CIERRE REMOTO)
0 2 1
120 MA4:5
2
SCC:8
2 1
121 MA4:6
2 1
122 MB1:13
TB2 REMOTE CLOSE (BYPASS 43L/R)
MD:2
(LIBRE)
4 3 1
MA1:3
SCC:6
SPARE
3 1
2 B
7 1
134
1 B
8 1
133
B2
MA2:1 118
B1
9 1
SPARE
(LIBRE)
SCC:19
2 3 1
MC:1 113
3 1
6
30 0 3
(POTENCIA AUXILIAR PARA LA CALEFACCIÓN DEL GABINETE)
CAB HTR AUX PWR
S8:1
31
S6:1,S8:3
32
PL1:2
33
1 3
208VCA
2 3
3
NEUTRAL
NUMERO DE MATERIAL DE ALSTOM
CLIENTE: IN No. de PEDIDO: 14 SUBESTACIÓN: No. de SERIE: 1A
4
CCDT1-72.5FK-065
ALSTOM PEDIDO # REV.
DESCRIPCIÓN
TERMINAL BLOCK WIRING DIAGRAM DIAGRAMA DE CABLEADO DE LOS BLOQUES TERMINALES
A
DIBUJADO
VERIFICADO
FECHA
W.Holt
A.Izvorean
02/21/14
DIBUJADO
VERIFICADO
FECHA
B
163783
No. de EQUIPO DEL CLIENTE: ALSTOM GRID Inc. One Power Lane Charleroi, PA 15022
C
NUMERO de DIBUJO:
E163783010
HOJA 5
D
de 14
4
A
B
LS1 1
L1
1 PL1:4 2 L1:L1
EGA
L2
63G
1 AT2:1D 2 AT2:2D 3 AT2:3D 4 AT2:4D 5 AT2:5D 7 2 4 6 6 AT2:6D 52.2 psig 47.9 psig 47.9 psig 7 AT2:7D (COLORES ESTÁNDARES DE LOS CABLES) STANDARD CABLE COLORS 1 - NEGRO 4 - NARANJA 7 - VERDE 1 - BLK 4 - ORA 7 - GRN 2 - ROJO 5 - BLANCO 2 - RED 5 - WHT 3 AZUL 6 BLANCO/NEGRO O CAFÉ 3 - BLU 6 - WHT/BLK or BRN
L1 LS1:2 L2 PL1:5 GND GND1:1
L1
2
1
GND
WATTAGE - 40 W (POTENCIA - 40 W)
1
C
CONTROL STATION (ESTACIÓN DE CONTROL)
3
D
NOTES: 1) ALL AC WIRING TO BE 12GA GRAY SIS VW1 2) ALL DC WIRING TO BE 14GA GRAY SIS VW1 3) ALL GROUND WIRES TO BE 12GA GREEN SIS VW1 4) WIRE MARKERS TO BE SHRINK-TYPE AND TO SHOW SAME-END/OPPOSITE-END DESIGNATION 5) WIRE LUGS ARE TO BE INSULATED RING-TYPE (EXCEPT FOR DEVICES THAT DO NOT ACCEPT RING-TYPE TERMINALS) 6) SCC:11 & SCC:12 ARE CONNECTED BY A 2PT SHORTING BAR
5
MC 52CC
1
3
a
1
12 16
2
22
2
26 32
3
36
SWITCH POSITION LOCAL
11 13
X
15
X
REMOTE
X X
17 21
X
X
23 25
X
X
27 31
X
13
15
b
b
b
b
10
12
14
16
88 T1
SCC:7 SCC:8 TB2:7R SCC:14 SCC:15 TB2:9R SCC:17 SCC:18 TB2:9AR TB3:25 TB3:26 TB3:27
8
11
T1 MB1:2 T2 MB1:3
9 10 11 12 13 14
23-1 1
MA1:10 TB10:114 TB9:107 TB9:108 TB10:122 TB9:110
COIL VOLTAGE - 125 VDC COIL RESISTANCE - 35.5 OHM
MA1
1 HT1:3W 2 HT1:1W GND GND1:11
GND
1
1
1 MA1:14,MA1:4 2 TB10:117
X
a
3
COIL VOLTAGE - 125 VDC COIL RESISTANCE - 35.5 OHM
COIL VOLTAGE - 125 VDC COIL RESISTANCE - 35.5 OHM
MA3
15
b
b
b
b
8
10
12
14
16
5
7
9
11
13
15
1
a
6
3
a
8
5
a
7
a
4
MA4
SCC:1 SCC:7
1 2 3 4 7 8 9 10
TB10:111 TB10:112 TB10:116 MD:1 TB5:51 TB5:52 MC:2 MB1:9
11 12 13 14 15 16
TB10:115 TB10:114 TB9:101 MD:1 TB5:53 TB5:54
1 2 3 4 5 6 7 8
TB10:118 ME:1 TB5:55 TB5:56 TB5:59 TB5:60 TB6:65 TB6:66
9 10 11 12 13 14 15 16
TB9:102 ME:1 TB5:57 TB5:58 TB6:63 TB6:64 TB6:67 TB6:68
b
b
b
b
10
12
14
16
1 2 3 4 5 6 7 8
TB6:69 TB6:70 TB7:75 TB7:76 TB7:79 TB7:80 TB7:83 TB7:84
9 10 11 12 13 14 15 16
TB6:71 TB6:72 TB7:77 TB7:78 TB7:81 TB7:82 TB8:87 TB8:88
TB8:89 TB8:90 TB8:93 TB8:94 TB10:120 TB10:121 TB8:91 TB8:92
11 TB8:95 12 TB8:96
2
52-3
2
52C 3 4
13
6
a
4
11
9
a
13
15
b
b
b
b
6
8
10
12
14
16
5
7
9
11
13
15
52-4
1
PB1
a
11
2
2
X
37
3
a T2
9
52-2
1
2
MOTOR VOLTAGE - 125VDC/AC WATTAGE - 1.6 kW
7
a
4
MA2
1 MA2:10,MA2:2 2 TB10:119
5
a
2
TEMP SETTING - 45-90 F (7-32 C)
ME 52TC2
3
a
2
MD 52TC1
52-1
1
X
33 35
11 12 13 15 16 17 21 22 23 31 32 33
9
a
6
M1
CONTACTS FRONT END
7
a
4
43L/R
DECK
5
a
2
ER
TH1 TB9:103 M1:T1 M1:T2 TB9:104 TB9:105 TB9:106 TB9:109 TB9:110
1
2
88LS 1 2 3 4 5 6 7 8
1 TB10:113 2 MA1:9
1
MOUNTED ON CB FRAME (MONTADA EN LA ESTRUCTURA DEL INTERRUPTOR) MB1
NOTAS: 1) TODO EL CABLEADO DE CA ES DE 12GA SIS VW1 GRIS 2) TODO EL CABLEADO DE CC ES DE 14GA SIS VW1 GRIS 3) TODOS LOS CABLES DE PUESTA A TIERRA SON DE 12GA SIS VW1 VERDE 4) LOS INDICADORES LOS CABLES SON TIPO ENCOGIDO Y TIENE LA MISMA DESIGNACIÓN EN AMBOS LADOS. 5) LAS PUNTAS DE LOS CABLES SON TIPO ANILLO (EXCEPTO PARA LOS APARATOS QUE NO ACEPTAN ESTE TIPO DE TERMINALES) 6) SCC:11 Y SCC:12 SON CONECTADOS CON UNA BARRA CORTO CIRCUITABLE DE DOS PUNTOS
3
a
a
a
4
2
a
6
8
b
b
b
b
10
12
14
16
1 2 3 4 5 6 9 10
4 COLOR - RED (ROJO)
PB2
3
52T1 3 3 4
GND1 1
SCC:3 SCC:14
K1
2
3
4
5
6
7
8
9
10 11 12
3
69-KI 1
1 SCC:10 2 SCC:11 13 14 15 16 17 18 19 20 21 22 23 24
4
1 PL1:3,L1:GND 4 AT2:7W 11 TH1:GND
2
COLOR - BLK (NEGRO)
PL1
GFI 4
PB3 3
52T2 3 SCC:5 4 SCC:17
HT1 EE
52T3 1
3
4 COLOR - BLK (NEGRO) 2
1 2 3 4
SCC:3 SCC:15 SCC:5 SCC:18
LA1 1
2
4
H1:1 1D
69 3
1 SCC:9 2 SCC:10
4
H1:2,H1:4 2D H1:3 3D
2
H1
1W TH1:2
1
3
2W S8:4 3W TH1:1,S8:2
4D
4W
5D
5W
6D
6W
2
1 2 3 4
HT1:1D HT1:2D HT1:3D HT1:2D
4
WATTAGE - 2X 95 W RESISTANCE - 2X 600 OHM
COLOR - BLK
1
1 2 3 4 5
S6:2 TB4:33 GND1:1 LS1:1 L1:L2
1 - LINE 2 - NEUTRAL 3 - GND 4 - LOAD LINE 5 5 - LOAD NEUTRAL VOLTAGE - 120 VAC AMP RATING - 20 A 3
1 - LÍNEA 2 - NEUTRO 3 - TIERRA 4 - CARGA DE LÍNEA 5 - CARGA DE NEUTRO
NUMERO DE MATERIAL DE ALSTOM
CLIENTE: IN No. de PEDIDO: TC SUBESTACIÓN: No. de SERIE: 1A
4
CCDT1-72.5FK-065
ALSTOM PEDIDO # REV.
DESCRIPCIÓN
MECHANISM AND CONTROL STATION WIRING CABLEADO DEL MECANISMO Y LA ESTACÍON DE CONTROL
A
DIBUJADO
VERIFICADO
FECHA
W.Holt
A.Izvorean
02/21/14
DIBUJADO
VERIFICADO
FECHA
B
163783
No. de EQUIPO DEL CLIENTE: ALSTOM GRID Inc. One Power Lane Charleroi, PA 15022
C
NUMERO de DIBUJO:
E163783010
HOJA 6
D
de 14
4
A
B
C
D
NOTES: 1) ALL AC WIRING TO BE 12GA GRAY SIS VW1 2) ALL DC WIRING TO BE 14GA GRAY SIS VW1 3) ALL GROUND WIRES TO BE 12GA GREEN SIS VW1 4) WIRE MARKERS TO BE SHRINK-TYPE AND TO SHOW SAME-END/OPPOSITE-END DESIGNATION 5) WIRE LUGS ARE TO BE INSULATED RING-TYPE (EXCEPT FOR DEVICES THAT DO NOT ACCEPT RING-TYPE TERMINALS) 6) SCC:11 & SCC:12 ARE CONNECTED BY A 2PT SHORTING BAR
SCC:12,EA1:21
ER:15,PB2:4
ER:16,TB2:9,EE:2,EA1:31
EA1:32,TB3:18,TB10:116
ER:21,PB3:4
TB2:9A,ER:22,EE:4,EA1:61
TB3:20,EA1:62,TB10:118
15
16
17
18
19
SCC:13
14
ES:13,K1:2 11
12
13
TB2:8,LA1:1
K1:1,LA1:2 10
ER:12,TB2:7 8
9
S3:4,TB2:10A,TB10:119
S3:2,TB2:11A,PB3:3,EE:3,EA1:43
ER:11,PB1:4
S2:4,TB10:117,TB2:10
5
7
S2:2,EA1:13,TB2:11,PB2:3,EE:1
4
6
S1:4,TB10:114,EA1:A2,ES:A2
3
S1:2,TB1:5,PB1:3,AT2:3W 1
SCC
2
2
1
52Y
13
43
14
21
44
22
31
32
A1 A1 A2 13 14 21 22 A2
ES:14 SCC:2 TB10:111,SCC:11 TB10:112,ES:A1 EA1:22 TB10:113
63GX1
13
43
21
31
14
44
22
32
53
83
61
71
54
84
62
72
A1 A1 A2 13 14 21 22 A2 31 32 43 44 53 54 61 62
COIL VOLTAGE - 125VDC COIL RESISTANCE - 3729 Ohms
3
COIL VOLTAGE - 125VDC COIL RESISTANCE - 3729 Ohms
S1 1
2
S2 3
1 2 3 4
TB1:1 SCC:1 TB1:2 SCC:2
4
AMP RATING - 16A
1
2
S3 3
1 2 3 4
TB1:1A SCC:3 TB1:2A SCC:4
4
AMP RATING - 16A
1
2
AT2:4W SCC:2 SCC:3 TB3:17 SCC:13 ES:21 SCC:15 SCC:16 SCC:5 TB3:19 TB11:123 TB11:124 SCC:18 SCC:19
DT1
1 2 3 4
TB1:1B SCC:5 TB1:2B SCC:6
4
AMP RATING - 16A
3
5
13
21
2
4
6
14
22
1 2 3 4 5 6 13 14 21 22
AMP RATING - 10-16A
1
2
3
1 2 3 4
1
TB1:3 DT1:1 TB1:4 DT1:6
1 TB4:32 2 PL1:1
1
3
1 2 3 4
TB4:31 HT1:3W TB4:32 HT1:2W
2 AMP RATING - 20A
AMP RATING - 16A
4
3
AT2 TB3:23 1W
4
S4:2 DT1:3 DT1:2 TB9:103 TB9:104 S4:4 TB11:127 DT1:22 TB11:129 DT1:14,TB11:128
S8
S6
S4 3
49
1
2
4
AMP RATING - 16A
1D EGA:1
TB3:24 2W
2D EGA:2
SCC:1 3W
3D EGA:3
EA1:A1 4W
4D EGA:4
TB3:21 5W
5D EGA:5
TB3:22 6W
6D EGA:6
GND1:4 7W
7D EGA:7
NUMERO DE MATERIAL DE ALSTOM
CLIENTE: IE No. de PEDIDO: T SUBESTACIÓN: No. de SERIE: 16
CCDT1-72.5FK-065
ALSTOM PEDIDO # REV.
DESCRIPCIÓN
RELAY PANEL WIRING DIAGRAM DIAGRAMA DE CABLEADO DEL PANEL LOS RELÉS
A
1
2
EA1 ES
NOTAS: 1) TODO EL CABLEADO DE CA ES DE 12GA SIS VW1 GRIS 2) TODO EL CABLEADO DE CC ES DE 14GA SIS VW1 GRIS 3) TODOS LOS CABLES DE PUESTA A TIERRA SON DE 12GA SIS VW1 VERDE 4) LOS INDICADORES LOS CABLES SON TIPO ENCOGIDO Y TIENE LA MISMA DESIGNACIÓN EN AMBOS LADOS. 5) LAS PUNTAS DE LOS CABLES SON TIPO ANILLO (EXCEPTO PARA LOS APARATOS QUE NO ACEPTAN ESTE TIPO DE TERMINALES) 6) SCC:11 Y SCC:12 SON CONECTADOS CON UNA BARRA CORTO CIRCUITABLE DE DOS PUNTOS
DIBUJADO
VERIFICADO
FECHA
W.Holt
A.Izvorean
02/21/14
DIBUJADO
VERIFICADO
FECHA
B
163783
No. de EQUIPO DEL CLIENTE: ALSTOM GRID Inc. One Power Lane Charleroi, PA 15022
C
NUMERO de DIBUJO:
E163783010
HOJA 7
D
de 14
4
A
B
TOP VIEW OF CONTROL CABINET VISTA DE ARRIBA DEL GABINETE DE CONTROL
MANUFACTURING NOTES: 1) DEVICES TO BE MARKED WITH ENGRAVED PLASTIC TAGS. 2) DIN RAIL TO BE PER ALSTOM SPEC 1_415_881. 3) POSITION INDICATOR TAGS ATTACHED w/SCREWS 4) WHERE END CLAMPS OR DEVICES ARE SHOWN DISPLACED FROM LAST COMPONENT SLIDE END CLAMP OR DEVICE OVER TO SECURE ROW OF COMPONENTS 5) SCC:11 & SCC:12 ARE CONNECTED BY A 2PT SHORTING BAR.
BCT TERMINALS TERMINALES DE LOS TC
RELAY PANEL PANEL DE RELES
1
MECHANISM MECHANISMO
D
TABLA 1. TABLA DE REFERENCIA DEL ENCLAVAMIENTO MECANICO TABLE 1.
KEY INTERLOCK REFERENCE TABLE
NUMERO DE SERIE DEL INTERRUPTOR BREAKER SERIAL NUMBER
NUMER DE PARTE DE ALSTOM
NUMERO DE LLAVE KEY NUMBER
ALSTOM PART NUMBER
163783-010-A
DROP OUT PANEL PLACA REMOVIBLE
CC410666-034
21472
NUMERO DE ORDEN DE COMPRA ALSTOM ALSTOM PO NUMBER
1
3485-CC163783
EGA
CONTROL TERMINALS TABLERO DE LAS TABILLAS
CONTROL PANEL TABLERO DE CONTROL
C
GROUND BAR BARRA DE PUESTA A TIERRA
L1
LS1
RELAY PANEL (PANEL DE RELÉS)
MFR WIREWAY 2X2 - MOUNTED TO BACK OF MECH PANEL CUSTOMER WIREWAY 1.5X3
*
1X
TB10 CONTROL STATION ESTACIÓN DE CONTROL
SCC
52Y
ES
MA1
*
DT1 STOP
S2
S3
16A
16A
ME
ME
52TC1
*
5X
MA2
52TC2
MA2 52-2
*
M1 88
MA3
K1
2X
MA4
MA4
69-KI 52-4
START
*
MFR WIREWAY 1X3 S1 16A
MD
MD
M1
52-1
ER
49
EA1
*
MA1 0 0 0 0 0 0 0
3X
52-3
DT1
63GX1
MB1 88LS
K1
TB3
MC 52CC
ER 43L/R
EA1
MC
TH1 23-1
2
MA3
MFR WIREWAY 1X3 ES
TB8
TH1 MFR WIREWAY 1.5X3 MB1 CUSTOMER WIREWAY 1X3
TB2
MFR WIREWAY 1X3
MFR WIREWAY 2X3
MFR WIREWAY 1.5X3
MFR WIREWAY 1X3
TB9
CUSTOMER WIREWAY 2X4
TB11
MFR WIREWAY 2X4
*
MFR WIREWAY 2X3
MFR WIREWAY 2X3
*
2
L1 40 W
MFR WIREWAY 1X3
TERMINAL BLOCK PANEL (PANEL DE BLOQUES DE TERMINALES)
TB1
BCT TERMINALS (TERMINALES DE LOS TC)
MECHANISM PANEL (PANEL DEL MECANISMO)
LS1
S4
S6
16A
PB1
S8
20A
4X
16A
MFR WIREWAY 1.5X3
PB1 CERRADO 1665
S1
S2
S3
S4
S6 S8 PB2
6X
3
PB2 DISPARO 1 1666
AT2
3
TB4
PB3
AT2
TB7
TB6
PB3 DISAPRO 2
TB5
1667
PL1 GFI
MFR WIREWAY 1X3
PL1 HT1
E-TRIP
MOUNTED THROUGH CABINET DOOR PUSH TO RESET
EE
H1 MOUNTED THROUGH CABINET (MONTADO A TAVÉS DEL CABINETE)
H1
LOCKOUT
EE
2X 95 W
LA1
DISPARO DE EMERGENCIA
HT1
RESET LA1
SEE PROCEDURE_0184 - (WIDE BOX) SEE PROCEDURE_0210 - (NARROW BOX) FOR INSTALLATION
GND1
MOUNTED TO ACCESS PANEL (MONTADO EN EL PANEL DE ACCESO)
NUMERO DE MATERIAL DE ALSTOM
CLIENTE: IN No. de PEDIDO: TC SUBESTACIÓN: No. de SERIE: 16
4
CCDT1-72.5FK-065
ALSTOM PEDIDO # REV.
DESCRIPCIÓN
COMPONENT LAYOUT PLANO DE LOS COMPONENTES
A
DIBUJADO
VERIFICADO
FECHA
W.Holt
A.Izvorean
02/21/14
DIBUJADO
VERIFICADO
FECHA
B
163783
No. de EQUIPO DEL CLIENTE: ALSTOM GRID Inc. One Power Lane Charleroi, PA 15022
C
NUMERO de DIBUJO:
E163783010
HOJA 8
D
de 14
4
A
1
2
B
C
ITEM 001 002 003 004 005 006 007 008 009 010 011 012 013
QTY 001 001 003 001 001 001 001 001 001 002 001 001 012
ALSTOM # CC410504-004 CC410504-005 CC410504-005 CC410508-006 CC410629-011 CC410632-019 CC417123-001 CC410634-009 CC410636-002 CC410640-019 CC410640-031 CC410640-005 CC410641-073
MFR # MAR1506STD73796 MAR1512STD73796 MAR1512STD73796 CR104 24203D 10D2L24A 1-410-632-P19 E69-30A TSA901 7360K8 IH3-1 BWFFG-1BCV GF5352A CLIPFIX35-5
MFR MARATHON MARATHON MARATHON GENERAL ELECTRIC ELECTROSWITCH ALSTOM CHERRY ELECTROMODE CUTLER HAMMER THOMAS & BETTS / RED DOT HUBBELL HUBBELL PHOENIX
DESCRIPTION TERMINAL BLOCK 6PT TERMINAL BLOCK 12PT, 30A, 600V TERMINAL BLOCK 12PT, 30A, 600V CONTACT BLOCK CONTROL SWITCH, LOCAL/REMOTE 3 STAGE CABINET LIGHT DOOR SWITCH, 10A, 125/250VAC ADJUSTABLE THERMOSTAT 45-90F (7-32C) PERMISSIVE CONTROL SWITCH RECEPTACLE, ENCLOSURE RECEPTACLE, WEATHERPROOF COVER RECEPTACLE, GFI, 120VAC, 20A, NEMA 5-20R END CLAMP
014 015 016 017 018 019 020 021 022 023 024 025 026 027 028 029 030 031 032 033 034 035 036 037 038 039 040 041 042 043 044 045 046
001 001 001 001 006 005 001 001 001 001 001 001 001 001 001 001 001 001 003 001 001 001 003 002 001 001 001 001 003 003 003 005 001
CC410666-034 CC410749-201 CC410749-201 CC410906 CC411107-003 CC413167-014 CC413167-001 CC413999-003 CC416206-004 CC416868-001 CC416868-002 CC417056-001 CC417125-001 CC417294-001 CC966957 CC990024-002 CC990035-001 CC990156-003 CC991268-001 CC410508-001 CC410748-001 CC410748-003 CC413166-023 CC413166-025 CC413166-026 CC410749-208
1_410_666_P34 CS8C-22Z-110D CS8C-22Z-110D 1_410_906 1506 SC E92SUCC-16 E91SULD20 17000_0, PCN 265480 1-416-206-P4 1-416-868-P1 1-416-868-P2 1-417-056-P1 GEL 40A15/120V 15199 1-417-294-G1 910-201-210 2-990-024-P2 2-990-035-P1 2-990-156-P3 2-991-268-P1 CR104PBG10B1 TB206 TB207 WNO SER B W22PB-FK SER B W22PB-FR SER B CS8-P22 GROUND_BAR_NEMA4X 1-417-254-G3 MAR1512STD73796 MAR1512STD73796 49.102.110-20 49.105.100-01 1-417-925-G2
ALSTOM SPRECHER + SCHUH SPRECHER + SCHUH ALSTOM MARATHON AEG AEG CHROMALOX ALSTOM ALSTOM ALSTOM ALSTOM GE ALSTOM AEG WIKA ALSTOM ALSTOM ALSTOM GENERAL ELECTRIC BUSSMANN BUSSMANN C3CONTROLS C3CONTROLS C3CONTROLS SPRECHER + SCHUH ALSTOM ALSTOM MARATHON MARATHON ALSTOM ALSTOM ALSTOM
KIRK KEY INTERLOCK ASSY - DT1-72FK,DT145F3 CONTROL RELAY 4NO 4NC (125 VDC) CONTROL RELAY 2NO 2NC (125 VDC) E-TRIP / 69 BLOCK TERMINAL BLOCK 6PT, SHORTING,30A, 600V MINIATURE CIRCUIT BREAKER, 2 POLE 16A MINIATURE CIRCUIT BREAKER, 1 POLE 20A ANTICONDENSATION HEATER ASSY 240VAC TERMINAL BLOCK COVER AUX 6PT PUSH BUTTON / IND LITE BRACKET CONTROL SWITCH BRACKET SWITCH BRACKET LIGHT BULB 40W 120VAC SPRING CHARGE MOTOR FOR FK3-1/131 MBS 25 THERMAL OVERLOAD 10-16A DENSITY MONITOR (67,52,48) PSIG-BAR SCALE-PURE SF6 MECHANISM PANEL DT72.5 RELAY PANEL, VERSION 3 6PT TB MOUNTING STRIP-NEW PUSHBUTTON, BLACK, 2NO AUX. TERMINAL BLOCK, 6 PT AUX. TERMINAL BLOCK, 7 PT PUSH-BUTTON NO CONTACT, SER B PUSHBUTTON, BLK, 1NO PUSHBUTTON, RED, 1NO AUXILIARY CONTACT GROUND BAR, 24PT - NEMA 4X KIRK KEY LOCK ASSY FK-1 TERMINAL BLOCK 12PT, 30A, 600V TERMINAL BLOCK 12PT, 30A, 600V COIL (125 VDC) AUXILIARY SWITCH FK3-X STANDARD CIRCUIT CONNECTOR
CC417254-003 CC410504-005 CC410504-005 CC49.102.110-20 CC49.105.100-01 CC417925-002
D
DEVICE ID TB4 TB11 TB1, TB2, TB3 EE ER L1 LS1 TH1 LA1 TH1, PL1 PL1 PL1 END10, END12, END18, END19, END20, END21, END24 END25, END26, END27, END28, END33 K1 EA1 ES LA1 4X, 5X, 6X, 1X, 2X, 3X S1, S2, S3, S4, S8 S6 H1 8 17 19 LS1 L1 M1 DT1 EGA PAN11 PAN17 PAN12, PAN14, PAN18 EE HT1 AT2 PB1, PB2, PB3 PB2, PB3 PB1 EA1 GND1 K1 TB5, TB6, TB7 TB10, TB8, TB9 MC, MD, ME MA1, MA2, MA3, MA4, MB1 SCC
1
2
3
3
NUMERO DE MATERIAL DE ALSTOM
CLIENTE: IN No. de PEDIDO: TC SUBESTACIÓN: No. de SERIE: 16
4
CCDT1-72.5FK-065
ALSTOM PEDIDO # REV.
DESCRIPCIÓN
BILL OF MATERIALS LISTA DE MATERIALES
A
DIBUJADO
VERIFICADO
FECHA
W.Holt
A.Izvorean
02/21/14
DIBUJADO
VERIFICADO
FECHA
B
163783
No. de EQUIPO DEL CLIENTE: ALSTOM GRID Inc. One Power Lane Charleroi, PA 15022
C
NUMERO de DIBUJO:
E163783010
HOJA 9
D
de 14
4
A
B 1
C
3
2
5
4
D BCT WIRING CABLEADO DE LOS TC
6
1 X1
X1 X2 X3
1X
2X
X4
X1
X2
X2
X3
X3
3X
X2
X3
X3
X2
5X
6X
X4
X4
X3
BCT NAMEPLATE PLACA DE DATOS DE LOS TC
X1 X2 X3 X4 X5
X1 X2 X3 X4 X5
CT WIRING NOTES: 1) LEADS TO BE TERMINATED WITH INSULATED TYPE LUGS. 2) ALL CT LEADS ARE TO BE SHORTED BEFORE SHIPMENT. IF TERMINAL BLOCKS ARE NOT EQUIPPED WITH INTEGRATED SHORTING BARS - SHORTING TO BE ACCOMPLISHED WITH 10GA GRAY SIS VW1 WIRE JUMPERS. WHT-BLK-GND. (IF LEADS ARE NOT COLOR CODED SHORT THE FIRST LEAD-THE LAST LEAD-GROUND) 3) ALL BCT LEADS ARE 10GA WIRE. 4) ALL GROUND WIRES ARE 10GA GREEN SIS WIRE.
GABINETE
3
2
1
4
3
6
5
RELACÍON: 600:5 PRECISÍON: 5P20 20VA @ 600:5 FRECUENCIA: 60Hz FACTOR TÉRMICO: 2.0 No. DE IDENTIFICACÍON: CC417048-11376P POSICÍON: 1X, 3X, 5X
X2-X3 X1-X2 X1-X3 X4-X5 X3-X4 X2-X4 X1-X4 X3-X5 X2-X5 X1-X5
CT MFG: MERAMEC FABRICANTE DE TC: MERAMEC AISLADOR
1 2 3 4 5 6 X X X X X X
RELACÍON: 600:5 PRECISÍON: 0.2 20VA @ 600:5 FRECUENCIA: 60Hz FACTOR TÉRMICO: 2.0 No. DE IDENTIFICACÍON: CC417048-11377P POSICÍON: 2X, 4X, 6X
50:5 100:5 150:5 200:5 250:5 300:5 400:5 450:5 500:5 600:5
X2-X3 X1-X2 X1-X3 X4-X5 X3-X4 X2-X4 X1-X4 X3-X5 X2-X5 X1-X5
50:5 100:5 150:5 200:5 250:5 300:5 400:5 450:5 500:5 600:5
3X-X1 3X-X2 3X-X3 3X-X4 3X-X5 GND
3X 3X1 3X2 3X3 3X4 3X5 GND
5X-X1 5X-X2 5X-X3 5X-X4 5X-X5 GND
5X 5X1 5X2 5X3 5X4 5X5 GND
2X-X1 2X-X2 2X-X3 2X-X4 2X-X5 GND
2X 2X1 2X2 2X3 2X4 2X5 GND
4X-X1 4X-X2 4X-X3 4X-X4 4X-X5 GND
4X 4X1 4X2 4X3 4X4 4X5 GND
6X-X1 6X-X2 6X-X3 6X-X4 6X-X5 GND
6X 6X1 6X2 6X3 6X4 6X5 GND
X5
POLE 3
POLE 2
1X 1X1 1X2 1X3 1X4 1X5 GND
1
X4
X5
X5
POLE 1
X1
X2
X5
X5
2
4X
X4
X4
X5
X1
X1
1X-X1 1X-X2 1X-X3 1X-X4 1X-X5 GND
BCT NAMEPLATE NOTES: 1) NAMEPLATE MATERIAL: STAINLESS STEEL 2) NAMEPLATE LOCATION: INTERNAL 3) NAMEPLATE DIMENSIONS AS SHOWN ON ALSTOM DRAWING 1_416_218_P3/4 4) NAMEPLATE IS TO BE ATTACHED WITH STAINLESS STEEL SCREWS
2
NOTAS DEL CABLEADO DE LOS TC: 1) LOS CABLES TIENEN QUE TERMINAR CON EXTREMIDADES TIPO AISLADAS 2) TODOS LOS CABLES DE LOS TC TIENEN QUE SER CORTO CIRCUITADOS ANTES DEL DESPACHO BLANCO-NEGRO-TIERRA CON PUENTE CON CABLE GRIS 10GA SIS (SI LOS CABLES NO TIENEN CODIGO DE COLORES CORTOCIRCUITAR PRIMERO CABLE -SEGUNDO-TIERRA) 3) TODOS LOS CABLES DE LOS TC SON DE 10GA 4) CABLES DE PUESTO A LA TIERRA SON DE 10GA SIS VERDE
NOTAS SOBRE LA PLACA DE DATOS LOS TC'S: 1) MATERIAL: ACERO INOXIDABLE 2) UBICACIÓN: INTERNA 3) DIMENSIONES COMO INDICADAS EN EL DIBUJO ALSTOM 1_416_218_P3/4
NUMERO DE MATERIAL DE ALSTOM
CLIENTE: IE No. de PEDIDO: TC SUBESTACIÓN: No. de SERIE: 16
4
3
CCDT1-72.5FK-065
ALSTOM PEDIDO # REV.
DESCRIPCIÓN
BCT NAMEPLATE & WIRING DIAGRAM PLACA DE DATOS & CABLEADO DE LOS TC
A
DIBUJADO
VERIFICADO
FECHA
W.Holt
A.Izvorean
02/21/14
DIBUJADO
VERIFICADO
FECHA
B
163783
No. de EQUIPO DEL CLIENTE: ALSTOM GRID Inc. One Power Lane Charleroi, PA 15022
C
NUMERO de DIBUJO:
E163783010
HOJA 10
D
de 14
4
A
B
C
1
D
1
RATINGS NAMEPLATE PLACA DE DATOS
Tipo:
Pedido/No. de contrato: TCM-ALSTOM-002-14 Referencia de ALSTOM 163783 Manual de operacion No.: IB-DT09-F1-ESP
DT1-72.5 FK
No. de Serie: Fecha de fabricacion:
Voltaje Nominal Maximo
Tiempo nominal de interrupcion
Frecuencia 60 Hz Secuencia nominal de operacion O-0.3s-CO-15s-CO
2
-Presion nominal
Desconexion de corrientes capacitivas 1.0(K)
Corriente nominal 1200 A Corriente nominal de corto circuito -Falla en terminales
20 kA
-Factor nominal de sobrevoltaje transitorio
E163783010
Presion (a 20˚ C) del gas SF6 Presion relativa
3.0 Ciclos
72.5 kV Factor nominal
163783-010
Lista de partes No: -40˚ C to +40˚ C Diagrama de control
Temperatura
2.0
66.7 psig [ 4.6 bar ]
-Corriente de carga de linea en vacio
100 A
-Presion de alarma baja 52.2 psig [ 3.6 bar ]
-Corriente de banco de capacitores aislado en paralelo
250 A
-Presion de bloqueo
-Corriente de banco de capacitores en presencia de otro banco energizado en paralelo
250 A
-Corriente transitoria de energizacion valor pico
20 kA
-Frecuencia de la corriente de energizacion
4250 Hz
47.9 psig [ 3.3 bar ] 29 lb [ 13 kg ] Peso total del interruptor 3203 lb [ 1456 kg ] Tipo de mecanismo
Duracion nominal de corto circuito
FK3-1/131
3s
Resorte
% Componente CC
-Falla de linea corta al 90% con capacitancia a tierra de 0nF (distancia < 100m)
67% 20 kA
Impulso de rayo
-Terminal a tierra 5 kA
-Terminal a terminal
Tension de control -de Cierre
452 kV al nivel del mar Corriente de interrupcion al impulso para soportar voltaje de
Corriente de interrupcion en oposicion de fases
2
Peso total de SF6
-de Disparo (cada uno) -Motor
125VDC, 3.5A 125VDC, 3.5A 125VDC, 1.6kW
N/A -Calefaccion del gabinete 208VAC, 190W N/A
ALSTOM GRID INC., HIGH VOLTAGE SWITCHGEAR MADE IN THE USA ONE POWER LANE - CHARLEROI, PA 15022
3
RATINGS NAMEPLATE NOTES: 1) NAMEPLATE MATERIAL: STAINLESS STEEL - MOUNT WITH SS SCREWS 2) NAMEPLATE LOCATION: EXTERNAL 3) NAMEPLATE DIMENSIONS AS SHOWN ON ALSTOM DRAWING 1_416_218_P1/P2 4) SERIAL NUMBERS AND MANUFACTURE DATE TO BE FILLED IN PRIOR TO ENGRAVING
3
Material: ACERO INOXIDABLE Material: STAINLESS STEEL Montaje: EXTERIOR Mounted: EXTERNALLY
NUMERO DE MATERIAL DE ALSTOM
CLIENTE: IN No. de PEDIDO: TC SUBESTACIÓN: No. de SERIE: 16
4
CCDT1-72.5FK-065
ALSTOM PEDIDO # REV.
DESCRIPCIÓN
GAS SCHEMATIC & NAMEPLATE TUBERÍAS DE GAS SF6 y PLACA DE DATOS
A
DIBUJADO
VERIFICADO
FECHA
W.Holt
A.Izvorean
02/21/14
DIBUJADO
VERIFICADO
FECHA
B
163783
No. de EQUIPO DEL CLIENTE: ALSTOM GRID Inc. One Power Lane Charleroi, PA 15022
C
NUMERO de DIBUJO:
E163783010
HOJA 11
D
de 14
4
A
B
C
D
SF6 GAS SCHEMATIC
1
POLO 2 POLE 2 RELEASE VALVE NUTS 5.0 mm FOR TESTING THE WIKA DENSITY MONITOR
POLO 1 POLE 1 POLE ISOLATION VALVE DETAIL (AISLAMIENTO DEL POLO DETALLE DE LA VÁLVULA) TESTING THE WIKA DENSITY MONITOR
DESTORNILLAR LA TUERCA DE VALVULA DE 5.0 mm PARA PROBAR EL MONITOR DE DENSIDAD WIKA
TUBERIAS PARA GAS SF6
(PROBAR EL DENSÍMETRO WIKA)
PRESSURE SWITCHES ARE LOCATED INSIDE THE DENSITY GAUGE HOUSING
1
LOS INTERRUPTORES DE PRESÍON ESTAN LOCALIZADOS DENTRO DE LA ENVOLTURA DEL DENSIMETRO
POLE ISOLATION VALVE AISLAMIENTO DE LOS POLOS
WIKA DENSITY MONITOR WIKA DENSIMETRO
VALVE NUT TUERCA DE LA VÁLVULA
POLE ISOLATION VALVE (VÁLVULA DE AISLAMIENTO DEL POLO)
5.0 mm FOR RELEASE VALVE NUTS (DESATORNILLAR LA TUERCA DE LA VÁLVULA DE 5 mm)
POLO 3 POLE 3
LEFT HANDED NUT FOR ALIGNMENT DENSITY MONITOR TUERCA DE ALINEAMIENTO (CON ROSCA A LA IZQUIERDA) DEL MONITOR DE DENSIDAD
VALVE NUT (TUERCA DE LA VÁLVULA)
STAINLESS STEEL TUBE 3/8" TUBO DE ACERO INOXIDABLE DE 3/8"
2
DILO FILL VALVE DN8 VÁLVULA DE LLENADO DILO-DN8
2
MANIFOLD WITH INTEGRATED VALVE FOR REMOVING THE WIKA DENSITY MONITOR BLOQUE DISTRIBUIDOR CON VALVULA INTEGRADA PARA REMOVER EL MONITOR DE DENSIDAD WIKA
CAP DILO VALVE TAPA DE LA VÁLVULA DILO
GAS PRESSURE REGULATOR WITH PRESSURE GAUGE REGULADOR DE PRESION CON MANOMETRO COUPLING SF6 BOTTLE ACOPLADOR A LA BOTELLA SF6
DILO COUPLING DN8 CONECTOR DILO-DN8
FILL HOSE MANGUERA DE LLENADO
66.7 psig - NORMAL 66.7 psig (4.6 bar) - NORMAL 52.2 psig - ALARM 52.2 psig (3.6 bar) - ALARMA 47.9 psig - LOCKOUT 47.9 psig (3.3 bar) - BLOQUEO ALSTOM GAUGE No. CC990024-002 MONITOR DE DENSIDAD WIKA CC990024-002
3
3
NOTES: 1) ALL TUBING IS 3/8" STAINLESS. 2) GAS SAMPLING CAN BE DONE THROUGH FILL VALVE. 3) POLE ISOLATION VALVES USED TO ISOLATE TANK FROM GAS PIPING. 4) PRESSURE SWITCHES ARE LOCATED INSIDE THE DENSITY GAUGE HOUSING NOTAS: 1) LA PLOMERIA ES DE ACERO INOXIDABLE 3/8". 2 )MUESTREO DE GAS SE PUEDE LLEVAR A CABO POR LA VALVULA DE LLENADO. 3) LAS VALVULAS DE AISLAMIENTO DEL POLSON UTILIZADAS PARA AISLAR EL TANQUE DE LA PLOMERIA DE GAS. 4) LOS CONTACTOS DE PRESION ESTAN UBICADOS ADENUTRO DEL MONITOR DE DENSIDAD.
NUMERO DE MATERIAL DE ALSTOM
CLIENTE: ID No. de PEDIDO: TC SUBESTACIÓN: No. de SERIE: A
4
CCDT1-72.5FK-065
ALSTOM PEDIDO # REV.
DESCRIPCIÓN
GAS SCHEMATIC & NAMEPLATE TUBERÍAS DE GAS SF6 y PLACA DE DATOS
A
DIBUJADO
VERIFICADO
FECHA
W.Holt
A.Izvorean
02/21/14
DIBUJADO
VERIFICADO
FECHA
B
163783
No. de EQUIPO DEL CLIENTE: ALSTOM GRID Inc. One Power Lane Charleroi, PA 15022
C
NUMERO de DIBUJO:
E163783010
HOJA 12
D
de 14
4
A
B
C
D
TERMINAL BLOCK MARKER STRIPS (BANDAS DE INDICACÍON DE LOS BLOQUES TERMINALES
TB1 TB2 TB3 TB5 TB6 TB7 TB8 TB9 TB10 TB11 7 1 13 51 63 75 87 99 111 123
DEVICE TAGS (ETI QUETAS DE LOS APARATOS)
1 DT1
EA1
49
63GX1
ER
ES
H1
L1
K1
MD
TH1
43L/R
52Y
2X 95 W
40 W
69-KI
52TC1
23-1
M1
MA2
MA1
MA3
MA4
MB1
MC
88
52-2
52-1
52-3
52-4
88LS
52CC
ME
PL1
S8
S1
S2
S3
S4
52TC2
GFI
16A
16A
16A
16A
16A
AT2
2
HT1
LS1
S6 20A
EE 52T3
DISPARO DE EMERGENCIA
17
52
64
76
88
100 112 124
1X2 2X2 3X2 4X2 5X2 6X2
1A
8
18
53
65
77
89
101 113 125
1X3
2X3 3X3 4X3
5X3 6X3
2A
9
19
54
66
78
90
102 114 126
1X4
2X4 3X4 4X4
5X4 6X4
1B
9R
20
55
67
79
91
103 115 127
1X5
2X5 3X5 4X5
5X5 6X5
2B
9A
21
56
68
80
92
104 116 128
GND GND GND GND GND GND
9AR 22
10
23
57
69
81
93
TB4 105 117 129 28
58
70
82
94
106 118 130
P8
3
RESETEO
P8
P8
P8
P8
5
10A
24
59
71
83
95
107 119 131
30
6
11
25
60
72
84
96
108 120 132
31
B1
11A
26
61
73
85
97
109 121 133
32
BCT TERMINAL MARKER STRIP NOTES: 1) STRIP MATERIAL: PLASTIC - YELLOW WITH BLACK LETTERS (MATERIAL - PLASTÍCO - AMARILLO CON LETRAS NEGRAS 2) STRIP DIMENSIONS AS SHOWN ON ALSTOM FABRICATION DRAWING 1_417_376_P... (SEE P#'S FOR EACH STRIP)
3
PB3 DISAPRO 2 52T2
PB2 DISPARO 1 52T1
COLOR - BLACK W/ WHITE TEXT
B2
B3
27
62
74
86
98
110 122 134
P4
P4
P4
P4
P4
P4
P4
P4
P4
P4
33 P5
TERMINAL MARKER STRIP NOTES: 1) STRIP MATERIAL: PLASTIC - BLACK WITH WHITE LETTERS 2) STRIP DIMENSIONS AS SHOWN ON ALSTOM FABRICATION DRAWING 1_417_376_P... (SEE P#'S FOR EACH STRIP)
48 mm
DEVICE TAG NOTES: 1) TAG MATERIAL: PLASTIC - YELLOW WITH BLACK LETTERS (MATERIAL: PLASTÍCO - AMARILLO CON LETRAS NEGRAS) 2) TAG DIMENSIONS AS SHOWN ABOVE (DIMENSIONES COMO INDICADAS ARRIBA)
COLOR - BLACK W/WHITE TEXT 30 mm
COLOR - BLACK W/WHITE TEXT
COLOR - BLACK W/WHITE TEXT
(COLOR - NEGRO CON LETRAS BLANCAS)
NOTAS: 1) MATERIAL - PLASTÍCO - NEGROS CON LETRAS BLANCO 2) DIMENSIONES DE LAS BANDAS COMO INDICADAS EN EL DIBUJO ALSTOM 1_417_376_P... ( VER No. P PARA CADA BANDA)
30 mm
30 mm
NUMERO DE MATERIAL DE ALSTOM
CLIENTE: IE No. de PEDIDO: T SUBESTACIÓN: No. de SERIE: 1
4
CCDT1-72.5FK-065
ALSTOM PEDIDO # REV.
2
P8
COLOR - RED W/ WHITE TEXT PB1 CERRADO 52C
1
29
LA1 - 69
BLOQUEO
5X 6X 5X1 6X1
7R
4
59 mm
2X 3X 4X 2X1 3X1 4X1
2
3 DEVICE TAG NOTES: 1) TAG MATERIAL: PLASTIC - YELLOW WITH BLACK LETTERS (MATERIAL: PLASTÍCO - AMARILLO CON LETRAS NEGRAS) 2) TAG DIMENSIONS PER ALSTOM DRAWING 1_417_376_P1
1X 1X1
DESCRIPCIÓN
DEVICE TAGS ETIQUETAS DE LOS APARATOS
A
DIBUJADO
VERIFICADO
FECHA
W.Holt
A.Izvorean
02/21/14
DIBUJADO
VERIFICADO
FECHA
B
163783
No. de EQUIPO DEL CLIENTE: ALSTOM GRID Inc. One Power Lane Charleroi, PA 15022
C
NUMERO de DIBUJO:
E163783010
HOJA 13
D
de 14
4
A
B
C
D
(1412.2 mm)
1
1
(864.0 mm)
(20.6 mm)
2
2
.56 TYP 4 PLACES 14
1.62 41
1.75 44
.56 TYP 4 PLACES 14
11.77 299
8 203
1.35 34
1.75 44
1.75 44
1.13 29
1.62 41
1.75 44
3
(PARTE DE SUPERIOR DEL TERMINAL) (ÁREA DE CONEXÍON)
TOP OF TERMINAL CONNECTION AREA
CL
BUSHING DATA
DATOS DE LA BOQUILLA
MATERIAL: PORCELAIN STRIKE DISTANCE: 730 mm / 28.7 in. CREEPAGE DISTANCE: 2235 mm / 88 in. BIL: 452 kV at sea level COLOR: GRAY HIGH VOLTAGE CONNECTION: NEMA 4 THRU HOLE TERMINAL MATERIAL : ALUMINUM
MATERIAL : PORCELANA DISTANCIA DE ARQUEO: 730 mm DISTANCIA DE FUGA: 2235 mm IMPULSO de RAYO: 452 kV BIL al nivel del mar COLOR: GRIS CONECTOR DE ALTA TENSIÓN: NEMA 4 MATERIAL DEL TERMINAL: ALUMINIO
3
BOTTOM OF TERMINAL CONNECTION AREA
BOTH SURFACES FINISHED FOR USE AS CONNECTION POINT (AMBAS SUPERFICIES ACABADAS PARA USAR COMO PUNTO DE CONEXÍON)
NUMERO DE MATERIAL DE ALSTOM
CLIENTE: IN No. de PEDIDO: T SUBESTACIÓN: No. de SERIE: A
4
CCDT1-72.5FK-065
ALSTOM PEDIDO # REV.
DESCRIPCIÓN
BUSHING OUTLINE DIBUJO DEL AISLADOR
A
DIBUJADO
VERIFICADO
FECHA
W.Holt
A.Izvorean
02/21/14
DIBUJADO
VERIFICADO
FECHA
B
163783
No. de EQUIPO DEL CLIENTE: ALSTOM GRID Inc. One Power Lane Charleroi, PA 15022
C
NUMERO de DIBUJO:
E163783010
HOJA 14
D
de 14
4