p632 Testing Procedure of Tranformer Diffrential Protection
August 21, 2017 | Author: Bedabyas_dehury | Category: N/A
Short Description
Power Transformer Differential relay testing procedure.(Relay Type:p632)...
Description
Page 1 of 14
TESTING PROCEDURE FOR TRANSFORMER DIFFERENTIAL PROTECTION RELAY USING CONVENTIONAL KIT
This test procedure is not for circulation and should be carried out by well trained person. This procedure explained about operating value test and operating time test only. Individual function only is considered for testing purposes and suitable setting can be adopted and tested. It is not necessary to test the relay at all setting and one setting is enough for confirming relay operation .Since P633/P32 is a numerical relay ,scheme operation check and load check should be carried out by seeing measurement CHAPTER and DISTURBANCE RECORDER WAVE FORM only. Particulars of apparatus to be tested: Designation : Transformer Differential Protection Device(Relay) Type P631/ P632/ P633/P634 Model No. : Sl.No. : Rating : In=1/5 A, Vx=48-250 VDC/100-230VAC,Vn=50-130V AC Rated Auxiliary supply : 220 VDC Identification No. : Drawing No. : P632 Mounting : Vertical [Normal service] Condition of sample : New Tests to be conducted: PRODUCT DETAILS: Rated Input current
: 1/5 A
Operating characteristics
:Differential Over current
Setting
: Idiff>0.1to2.5Amp,Idiff>>2.5to30Amp, Idiff>>>2.5to30Amp,
Rated Auxiliary supply
: 220 VDC
Range
: 48-250 VDC/100-230VAC
TERMINAL DETAILS: Auxiliary supply terminals Current input terminals a- side (HV SIDE )
b-side ( LV SIDE)
: 20X25 (+) & 20X26 (-) : 1/5 A A -Phase 04X1 & 04X 2 B -Phase 04X3 & 04X 4 C -Phase 04X5 & 04X 6 N 04X7 & 04X 8 A -Phase 06X1 & 06X 2 B -Phase 06X3 & 06X 4 C -Phase 06X5 & 06X 6 N 06X7 & 06X 8
Page 2 of 14
Voltage input terminals
:
Output contacts (O/C) : Relay
OPTO INPUT
:
U1 U2 U3 U4
Test conditions: Auxiliary voltage to be applied
04X13 & 04X16 K1 (Tripping) 20X1 & 20X 2 (N/O) 20X3 & 20X 4 (N/O) K2 20X5 & 20X 6 (N/C) 20X7 & 20X 6 (N/O) K3 20X8 & 20X 9 (N/O) K4 20X10 & 20X11 (N/O) K5 20X10 & 20X12 (N/O) K6 20X10 & 20X13 (N/O) K7 20X10 & 20X14 (N/O) K8 20X15 & 20X16 (N/C) 20X17 & 20X16 (N/O) 20X18 (+ ive)& 20X19 (-ive) 20X20 (+ ive)& 20X21 (-ive) 20X22 (+ ive)& 20X24 (-ive) 20X23 (+ ive)& 20X24 (-ive) : 220 VDC
1.0 ACCURACY TEST: 1.1 Determination of errors relating to characteristic quantity: Output RL-3 is assigned permanently for following FUNCTIONS
Id>A Id>B Id>C Id>>A Id>>B Id>>C Io> HV Io> LV1 Io> LV2 Aux0 Relay Setting -- Operating value test: 1) DIFFERETIAL FUNCTION TEST Relay setting
/Parameters/Function parameters/Parameter subset 1/DIFF DIFF Enable PS1--Yes DIFF Idiff> PS1--0.20 Iref DIFF Idiff>> PS1--15.0 Iref DIFF Idiff>>> PS1--BLOCKED DIFF m1 PS1--0.20 DIFF m2 PS1--0.80 DIFF IR,m2 PS1--1.5 Iref
A
Page 3 of 14
DIFF DIFF DIFF
Op.mode rush rst.PS1--With RushI(2f0)/I(f0) PS1--20 % 0-seq. filt.a en.PS1--No
DIFF DIFF DIFF DIFF DIFF
0-seq. filt.b en.PS1--No Overflux.bl. en. PS1--No Ov. I(5f0)/I(f0) PS1--20 % Op.del.,trip sig.PS1--0.00 s Hyst. effective PS1--No
Procedure: Input energizing quantity (current) is increased slowly until relay contact operates a- SIDE (HV SIDE ) Sl No
Idiff>
Measured Operating Value A-PHASE B-PHASE
(Amp) C-PHASE
0.20 Iref 1.00 Iref 2.00 Iref
Sl No
Idiff>>
Claimed Value (Amp) 0.099 to 0.121 0.198 to 0.242 0.297 to 0.363
Measured Operating Value A-PHASE B-PHASE
(Amp) C-PHASE
3.00 Iref 10.0 Iref 25.0 Iref
Claimed Value (Amp) 0.099 to 0.121 0.198 to 0.242 0.297 to 0.363
b- SIDE (LV SIDE ) Sl No
Idiff>
Measured Operating Value A-PHASE B-PHASE
(Amp) C-PHASE
0.20 Iref 1.00 Iref 2.00 Iref
Sl No
Idiff>> 3.00 Iref 10.0 Iref 25.0 Iref
Claimed Value (Amp) 0.099 to 0.121 0.198 to 0.242 0.297 to 0.363
Measured Operating Value A-PHASE B-PHASE
(Amp) C-PHASE
Claimed Value (Amp) 0.099 to 0.121 0.198 to 0.242 0.297 to 0.363
Bias Test Procedure: Apply equal value of current in a-SIDE (HV SIDE ) & b-SIDE (LV SIDE ). a-SIDE (HV SIDE ) input energizing quantity (current) is increased slowly until relay contact operates Actual Differential Current = Vector sum of both current Bias Current = ( Magnitude sum of currents) / 2
A
Page 4 of 14
Theoretical Diffl current = 0.2+0.2 XIb (for slope=20%) =0.2 +0.2 X 1.5 +(Ib-1.5) X 0.8 (for slope=80%) Phase s
A-Ph
B-Ph
C-Ph
Applied Current (LV1)
Measured Current (HVside1)
0.2 A 0.5 A 1.0 A 2.5 A 5.0 A 0.2 A 0.5 A 1.0 A 2.5 A 5.0 A 0.2 A 0.5 A 1.0 A 2.5 A 5.0 A
Calculated Calculated Claimed value Diffl. Bias Diffl Current Current (Amp) 0.239 to 0.293 0.301 to 0.369 0.582 to 0.712 2.381 to 2.911 5.418 to 6.622 0.239 to 0.293 0.301 to 0.369 0.582 to 0.712 2.381 to 2.911 5.418 to 6.622 0.239 to 0.293 0.301 to 0.369 0.582 to 0.712 2.381 to 2.911 5.418 to 6.622
SECOND HARMONIC TEST Procedure: Rated Input energizing quantity (current-1A/50Hz is applied in A-PHASE and relay is found to be in the operated condition .Apply current with frequency 100Hz in phase with 50Hz current in A-PHASE and increase slowly until relay contact opens. Record 100Hz current as Second harmonic restrain current Sl No
RushI(2f0)/I(f0)
Applied 50Hz current (Amp)
Measured Resetting Value of 100Hz (Amp)
20 % 30%
Claimed Value (Amp) 0.0925 to 0.1075 0.0925 to 0.1075
REF TEST Procedure: Input energizing quantity (current) is increased slowly until relay contact operates a- SIDE REF (HV SIDE ) Relay setting
/Parameters/Function parameters/Parameter subset 1/REF_1 REF_1 Enable PS1--Yes REF_1 Operating mode PS1--High impedance REF_1 Idiff> PS1--1.00 Iref REF_1 Idiff>>> PS1--Blocked
K
Page 5 of 14
Sl No
REF_1 REF_1
m1 m2
PS1--0.20 PS1--1.50
REF_1
IR,m2
PS1--1.00 Iref
Measured Operating Value
Idiff>
(Amp)
Setting 0.2 Iref 0.3 Iref 0.5 Iref 0.7 Iref 1.0 Iref
Claimed Value (Amp) 0.19 to 0.21 0.285 to 0.315 0.475 to 0.525 0.665 to 0.735 0..95 to 1.05
b- SIDE REF (LV SIDE ) Relay Setting
/Parameters/Function parameters/Parameter subset 1/REF_2 REF_2 Enable PS1-- Yes REF_2 Operating mode PS1-- High impedance REF_2 Idiff> PS1-- 0.20 Iref REF_2 Idiff>>> PS1-- Blocked REF_2 m1 PS1-- 0.20 REF_2 m2 PS1-- 1.50 REF_2 IR,m2 PS1-- 1.00 Iref
Sl No
Measured Operating Value
Idiff>
(Amp)
Setting 0.2 Iref 0.3 Iref 0.5 Iref 0.7 Iref 1.0 Iref
Claimed Value (Amp) 0.19 to 0.21 0.285 to 0.315 0.475 to 0.525 0.665 to 0.735 0.95 to 1.05
DTOC FUNCTION TEST
Procedure: Input energizing quantity (current) is increased slowly until relay contact operates RELAY SETTING
/Parameters/Function parameters/Parameter subset 1/DTOC1
DTOC1 DTOC1 DTOC1 DTOC1
Enable PS1--Yes Block tim.st. IN PS1--Without Gen.starting modePS1--W/o start. IN/Ineg tGS PS1--0.00 s
Page 6 of 14
DTOC1 DTOC1 DTOC1 DTOC1 DTOC1 DTOC1 DTOC1 DTOC1 DTOC1 DTOC1 DTOC1 DTOC1 DTOC1 DTOC1 DTOC1 DTOC1 DTOC1 DTOC1 DTOC1 DTOC1 DTOC1 DTOC1 DTOC1 DTOC1 DTOC1 DTOC1 DTOC1 DTOC1
Rush restr.enabl PS1--No I> PS1--1.00 Inom I>> PS1--30.00 Inom I>>> PS1--30.00 Inom I> dynamic PS1--1.00 Inom I>> dynamic PS1--1.00 Inom I>>> dynamic PS1--1.00 Inom tI> PS1--0.00 s tI>> PS1--0.00 s tI>>> PS1--0.00 s Ineg> PS1--0.25 Inom Ineg>> PS1--8.00 Inom Ineg>>> PS1--8.00 Inom Ineg> dynamic PS1--1.00 Inom Ineg>> dynamic PS1--1.00 Inom Ineg>>> dynamic PS1--1.00 Inom tIneg> PS1--0.00 s tIneg>> PS1--0.00 s tIneg>>> PS1--0.00 s IN> PS1--0.25 Inom IN>> PS1--8.00 Inom IN>>> PS1--8.00 Inom IN> dynamic PS1--1.00 Inom IN>> dynamic PS1--1.00 Inom IN>>> dynamic PS1--1.00 Inom tIN> PS1--0.00 s tIN>> PS1--0.00 s tIN>>> PS1--0.00 s
a.2.1) For phase fault (A,B,C) I >; tI> 0 sec I> Setting
Value(A AC)
I nom
0.5 I nom 5 I nom 20 I nom
0.5 5 20
1 1 1
Measured operating value A Ph B Ph C Ph
Claimed operating value (AAC) 0.475 – 0.525 4.75 – 5.25 19 – 21
a.2.2) For phase fault (A,B,C) I>>; tI >> 0 sec I>> Setting
Value(A AC)
I nom
0.5 I nom 5 I nom 20 I nom
0.5 5 20
1 1 1
Measured operating value A Ph B Ph C Ph
Claimed operating value (AAC) 0.475 – 0.525 4.75 – 5.25 19 – 21
a.2.3) For phase fault (A,B,C) I >>> ; tI>>> 0 sec I>>> Setting Value(A AC)
I nom
Measured operating value
Claimed operating value
Page 7 of 14
A Ph 0.5 I nom 5 I nom 20 I nom
0.5 5 20
B Ph
C Ph
(AAC) 0.475 – 0.525 4.75 – 5.25 19 – 21
1 1 1
a.2.5) For earth fault IN> ; tIN> 0 sec IN> Setting
Value(A AC)
I nom
0.2 I nom 1 I nom 8.0 I nom
0.2 1.0 8.0
1 1 1
Measured operating value I neutral>
Claimed operating value (AAC) 0.19 – 0.21 0.95 – 1.05 7.60– 8.40
a.2.6) For earth fault IN>> ; tIN>> 0 sec IN>> Setting
Value(A AC)
I nom
0.2 I nom 1 I nom 8.0 I nom
0.2 1.0 8.0
1 1 1
Measured operating value I neutral>>
Claimed operating value (AAC) 0.19 – 0.21 0.95 – 1.05 7.60 – 8.40
a.2.7) For earth fault IN>>> ; tIN>>> 0 sec IN>>> Setting
Value(A AC)
I nom
0.2 I nom 1 I nom 8.0 I nom
0.2 1.0 8
1 1 1
Measured operating value I neutral>>>
Claimed operating value (AAC) 0.19 – 0.21 0.95 – 1.05 7.60– 8.40
a.2.9) For NEGATIVE SEQUENCE Ineg > ; tIneg > 0 sec Procedure: Apply 3 phase Negative sequence current and increase till the function assigned contact closes INEG> Setting Value(A AC)
I nom
0.5 I nom 5 I nom 8.0 I nom
1 1 1
0.5 5 8.0
Measured operating value Ineg>
Claimed operating value (AAC) 0.475 – 0.525 4.75 – 5.25 7.60 – 8.40
a.2.10) For NEGATIVE SEQUEMCE Ineg > >; tIneg >> 0 sec INEG>> Setting 0.5 A 5A 8.0 I nom
Value(A AC) 0.5 5 8.0
I nom 1 1 1
Measured operating value Ineg>>
Claimed operating value (AAC) 0.475 – 0.525 4.75 – 5.25 7.60 – 8.40
a.2.11) For NEGATIVE SEQUEMCE Ineg > >>; tIneg >>> 0 sec
Page 8 of 14
INEG>>> Setting 0.5 I nom 5 I nom 8.0 I nom
Value(A AC)
I nom
0.5 5 8.0
1 1 1
Measured operating value I neg>>>
Claimed operating value (AAC) 0.475 – 0.525 4.75 – 5.25 7.60 – 8.40
a.3) IDMT FUNCTION TEST
/Parameters/Function parameters/Parameter subset 1/IDMT1
IDMT1 IDMT1 IDMT1 IDMT1 IDMT1 IDMT1 IDMT1 IDMT1 IDMT1 IDMT1 IDMT1 IDMT1 IDMT1 IDMT1 IDMT1 IDMT1 IDMT1 IDMT1 IDMT1 IDMT1 IDMT1 IDMT1 IDMT1 IDMT1 IDMT1 IDMT1
Enable PS1-- Yes Block tim.st. IN PS1-- Without Gen.starting modePS1-- W/o start. IN/Ineg tGS PS1-- 0.00 s Rush restr.enabl PS1-- No Iref,P PS1-- 1.00 Inom Iref,P dynamic PS1-- 1.00 Inom Characteristic P PS1-- Definite Time Factor kt,P PS1-- 1.00 Min. trip t. P PS1-- 0.00 s Hold time P PS1-- 0.00 s Release P PS1-- Without delay Iref,neg PS1-- 0.80 Inom Iref,neg dynamic PS1-- Blocked Character. neg. PS1-- Definite Time Factor kt,neg PS1-- 1.00 Min. trip t. neg PS1-- 1.00 s Hold time neg PS1-- 0.00 s Release neg PS1-- Without delay Iref,N PS1-- 0.80 Inom Iref,N dynamic PS1-- Blocked Characteristic N PS1-- Definite Time Factor kt,N PS1-- 1.00 Min. trip t. N PS1-- 1.00 s Hold time N PS1-- 0.00 s Release N PS1-- Without delay
a.3.1) For phase fault (A,B,C) ; Min. trip t. P= 0 sec
Iref,P
Value(A AC)
I nom
Setting 0.2 I nom 1 I nom 4 I nom
0.2 1.0 4.0
1 1 1
Measured operating value A Ph B Ph C Ph
Claimed operating value (AAC) 0.19 – 2.1 0.95 – 1.05 3.8 – 4.2
Page 9 of 14
a.3.2) For NEGATIVE SEQUENCE Iref,neg Min. trip t. neg= 0 sec Procedure: Apply 3 phase Negative sequence current and increase till the function assigned contact closes
Iref,neg
Value(A AC)
I nom
Setting 0.2 I nom 0.4 I nom 0.8 I nom
0.2 0.4 0.8
1 1 1
Measured operating value Ineg
Claimed operating value (AAC) 0.19 – 2.1 0.38—0.42 0.76 – 0.84
a.3.3) For earth fault Iref,N ; Min. trip t. N= 0 sec
Iref,N Setting
Value(A AC)
I nom
0.2 I nom 0.4 I nom 0.8 I nom
0.2 0.4 0.8
1 1 1
Measured operating value I neutral
Claimed operating value (AAC) 0.19 – 2.1 0.38—0.42 0.76 – 0.84
a.4 ) V < > (UNDER/OVER VOLTAGE) Procedure: Apply 3ph-n voltage(63.5V) and increase one phase voltage for over voltage or decrease one phase voltage for under voltage function till the function assigned contact closes RELAY SETTING
/Parameters/Function parameters/Parameter subset 1/V V V V V V V V V V V V V
Enable PS1-- Yes V> PS1-- 1. Vnom V>> PS1-- 1. Vnom tV> PS1-- 0.00 s tV>> PS1-- 0.00 s V< PS1-- 0.80 Vnom V PS1-- 0.25 Vnom tV< PS1-- Blocked tV ;tV > 0 sec V> Setting 1.1 V nom
Value(V AC) 69.859/121
V nom 110/3 V
Measured operating value V> AN BN CN
Claimed operating value (V AC) 67.763—71.955
Page 10 of 14
1.25 V nom 1.5 V nom
79.385/137 .5 95.263/165
110/3 V
77.003 --- 81.766
110/3 V
92.405—98.121
a.3.2) OVER VOLTAGE V>> ;tV> > 0 sec V> > Setting 1.1 V nom 1.25 V nom 1.5 V nom
Value(V AC) 69.859 79.385 95.263
V nom
Measured operating value V>> AN BN CN
Claimed operating value (V AC) 67.763—71.955 77.003 --- 81.766 92.405—98.121
110/3 V 110/3 V 110/3 V
a.3.3) UNDER VOLTAGE V< ;tV< 0 sec V< Setting
Value(V AC)
V nom
Measured operating value V< AN BN CN
0.3 V nom 0.6 V nom 0.9 V nom
19.05 38.10 57.15
110/3 V 110/3 V 110/3 V
Claimed operating value (V AC) 18.478—19.622 36.957---39.243 55.435—58.865
a.3.4) UNDER VOLTAGE V> PS1-- Blocked V/f tV/f> PS1-- 0 s V/f t at V/f=1.05 PS1-- 72.8 s V/f t at V/f=1.10 PS1-- 18.8 s V/f t at V/f=1.15 PS1-- 8.8 s V/f t at V/f=1.20 PS1-- 5.3 s V/f t at V/f=1.25 PS1-- 3.7 s
Page 12 of 14
V/f V/f V/f V/f V/f V/f V/f V/f V/f
t at V/f=1.30 PS1-- 2.8 s t at V/f=1.35 PS1-- 2.3 s t at V/f=1.40 PS1-- 1.9 s t at V/f=1.45 PS1-- 1.7 s t at V/f=1.50 PS1-- 1.5 s t at V/f=1.55 PS1-- 1.4 s t at V/f=1.60 PS1-- 1.3 s Reset time PS1-- 0 s tV/f>> PS1-- 0 s
Procedure :Apply AC voltage (50Hz) less than setting and increase the voltage with time delay of 200mSec till it operates. Record the value (Operating value = setting X supply frequency ) Sl No
V/f> (alarm)
Value(V AC)
Measured Operating Value (Volt)
Setting (Vnom/fnom)
1.00 110.0 1.10 121.0 1.19 130.9
Claimed Value (Volt) 106.70 to 113.30 117.37 to 124.63 126.973 to 134.83
1.2 Operating time test LOW SET OPERATING TIME; Relay Setting
SETTINGS(1) S1 Id> 200.0e-3PU Procedure: Apply 1ph current with 5 times setting value & measure operating time .. HV SIDE1 Sl No Measured Operating Time Claimed Operating Time A-PHASE
B-PHASE
C-PHASE 30 to 40 m Sec
HIGH SET OPERATING TIME; Relay Setting
SETTINGS(1) S1 Id>>
5 PU
Procedure: Apply 1ph current with 5 times setting value & measure operating time .. LV 1 Sl No Measured Operating Time Claimed Operating Time A-PHASE
B-PHASE
C-PHASE 10 to 20 m Sec
REF OPERATING TIME; Relay Setting
Page 13 of 14
SETTINGS(1) S1 Io> HV S1 Io> LV1 S1 Io> LV2
100.0e-3PU 100.0e-3PU 100.0e-3PU
Procedure: Apply 1ph current with 5 times setting value & measure operating time .. Sl No Measured Operating Time Claimed Operating Time HV
LV1
LV2 20 to 40 m Sec
OVERFLUX OPERATING TIME(TRIP); Relay Setting
SETTINGS(1) S1 V/f(Trip)Char DT S1 V/f (Trip) 2.20Procedure: Apply voltage 121VAC (110% OF SETTING) ,50Hz and measure operating time Sl No tV/f (Trip) setting Measured Operating Time Claimed Operating Time (Sec)
(Sec) 1.90 to 2.1S 19.0 to 21.0S 47.5 to 52.5
2S 20 S 50 S Relay Setting
SETTINGS(1) S1 V/f(Trip) I DMT S1 V/f (Trip) 2.20S1 TMS 1 Procedure: Apply voltage 121VAC (110% OF SETTING) ,50Hz and measure operating time Sl No Applied Voltage Measured Operating Time Claimed Operating Time (Sec)
(Sec) 16.92 to 20.68 4.770 to 5.83 2.520 to 3.08
121V 132V 143V OVERFLUX OPERATING TIME(ALARM); Relay Setting
SETTINGS(1) S1 V/f(Trip)Char DT S1 V/f (ALARM) 2.20Procedure: Apply voltage 121VAC (110% OF SETTING) ,50Hz and measure operating time Sl No tV/f (ALARM) setting Measured Operating Time Claimed Operating Time (Sec) 2S 20 S
(Sec) 1.90 to 2.1S 19.0 to 21.0S
Page 14 of 14
50 S
47.5 to 52.5