Over Current Co Ord
Short Description
over...
Description
Overcurrent Protection & Coordination for Industrial Applications Doug Durand, P.E. (PowerPoint assistance by Alok Gupta)
IEEE Continuing Education Seminar - Houston, TX February 16-17, 2010
Presenter Bio 1986 – Received BSEE degree from University of Texas at Austin and joined the Planning department of West Texas Utility 1987 – Joined Brown & Root (now KBR). Currently Senior Principal Engineer in charge of KBR’s Technical Services group. The group’s primary tasks involve power system studies including shortcircuit, load flow, motor starting, overcurrent coordination, underground cable ampacity, ground mat, arc-flash, harmonic load flow, transient stability, and relay configuration/setting. Professional Engineer (Texas) IEEE Member Assistant Technical Editor of the IEEE Std 399 – Brown Book (revision 1990)
1
Agenda Day 2
Day 1
▫ ▫ ▫ ▫ ▫ ▫ ▫ ▫
Introduction Information Required Using Log-Log Paper & TCCs Types of Fault Current Protective Devices & Characteristic Curves Coordination Time Intervals (CTIs) Effect of Fault Current Variations Multiple Source Buses
▫ ▫ ▫ ▫ ▫
Transformer Overcurrent Protection Motor Overcurrent Protection Conductor Overcurrent Protection Generator Overcurrent Protection Coordinating a System
Introduction
2
Protection Objectives • Personnel Safety
Protection Objectives • Equipment Protection
3
Protection Objectives • Service Continuity & Selective Fault Isolation 13.8 kV • Faults should be quickly detected and cleared with a minimum disruption of service. 13.8 kV/480 V 2.5 MVA 5.75%
480 V
• Protective devices perform this function and must be adequately specified and coordinated. • Errors in either specification or setting can cause nuisance outages.
Types of Protection • • • • • • • •
Distance High Impedance Differential Current Differential Under/Over Frequency Under/Over Voltage Over Temperature Overcurrent Overload
4
Coordinating Overcurrent Devices • Tools of the trade “in the good ole days…”
Coordinating Overcurrent Devices • Tools of the trade “in the good ole days…”
5
Coordinating Overcurrent Devices • Tools of the trade “in the good ole days…”
Coordinating Overcurrent Devices • Tools of the trade “in the good ole days…”
6
Coordinating Overcurrent Devices • Tools of the trade “in the good ole days…”
Coordinating Overcurrent Devices • Tools of the trade today…
7
Using Log-Log Paper & TCCs
Log-Log Plots Time-Current Characteristic Curve (TCC) 1000 effectively steady state
Time In Seconds
100
Why log-log paper? I2t withstand curves plot as straight lines
1 minute
• Log-Log scale compresses values to a more manageable range.
10 typical motor acceleration
• I2t withstand curves plot as straight lines.
1
0.1
typical fault clearing 5 cycles (interrupting)
1 cycle (momentary) 0.01 0.5
FLC = 1 pu
1
Fs = 13.9 pu 10
100`
Fp = 577 pu
1000
10000
Current in Amperes
8
Plotting A Curve 5000 hp Motor TCC 1000
FLC = 598.9 A
13.8 kV
Time In Seconds
100 13.8/4.16 kV 10 MVA 6.5%
10
Accel. Time = 2 s 4.16 kV 1
M 4.16 kV 5000 hp 90% PF, 96% η, 598.9 A 3593.5 LRA, 2 s start
0.1
LRA = 3593.5 A 0.01 0.5
1
10
100`
1000
10000
Current in Amperes
Plotting Fault Current & Scale Adjustment 5000 hp Motor TCC with Fault on Motor Terminal 1000 13.8 kV
FLC = 598.9 A
Time In Seconds
100 13.8/4.16 kV 10 MVA 6.5% 10
Accel. Time = 2 s
4.16 kV 15 kA
1
M 4.16 kV 5000 hp 90% PF, 96% η, 598.9 A 3593.5 LRA, 2 s start
0.1
15 kA
LRA = 3593.5 A 0.01 0.5
1
10
100`
1000
10000
Current in Amperes x 10 A
9
Voltage Scales 5000 hp Motor TCC with Fault on Transformer Primary
45 kA @ 13.8 kV = ? @ 4.16 kV
13.8 kV 45 kA
100
Time In Seconds
= (45 x 13.8/4.16) = 149.3 kA @ 4.16 kV
1000
13.8/4.16 kV 10 MVA 6.5% 10 4.16 kV 15 kA
1
M 4.16 kV 5000 hp 90% PF, 96% η, 598.9 A 3593.5 LRA, 2 s start
0.1
15 kA 0.01 0.5
1
10
100`
1000
149.3 kA
10000
100AA @ 4.16 kV Current in Amperes x 10
Types of Fault Currents
10
Fault Current Options Crest/Peak Current
Interrupting/Breaking
Momentary Initial Symmetrical
ANSI
IEC
• • • • •
• • • •
Momentary Symmetrical Momentary Asymmetrical Momentary Crest Interrupting Symmetrical Adjusted Interrupting Symmetrical
Initial Symmetrical (Ik’’) Peak (Ip) Breaking (Ib) Asymmetrical Breaking (Ib,asym)
Fault Current Options Crest/Peak Current
Momentary
Interrupting/Breaking
Initial Symmetrical
• Symmetrical currents are most appropriate. • Momentary asymmetrical should be considered when setting instantaneous functions. • Use of duties not strictly appropriate, but okay. • Use of momentary/initial symmetrical currents lead to conservative CTIs. • Use of interrupting currents will lead to lower, but still conservative CTIs.
11
Protective Devices & Characteristic Curves
Electromechanical Relays (EM) 100
Very Inverse Time Time-Current Curves
1
10
3 2
0.1
Time Dial Settings
TIME IN SECONDS
10
IFC 53 RELAY
1 ½
0.01 1
10
100
MULTIPLES OF PICK-UP SETTING
12
Electromechanical Relays – Pickup Calculation The relay should pick-up for current values above the motor FLC ( ~ 600 A).
4.16 kV
IFC 53
For the IFC53 pictured, the available ampere-tap (AT) settings are 0.5, 0.6, 0.7, 0.8, 1, 1.2, 1.5, 2, 2.5, 3, & 4.
800/5
For this type of relay, the primary pickup current was calculated as: PU = CT Ratio x AT
4.16 kV 5000 hp FLC = 598.9 A SF = 1.0
Set AT = 4
M
PU = (800/5) x 3 = 480 A (too low) = (800/5) x 4 = 640 A (107%, okay)
Electromechanical Relays – Operating Time Calculation 4.16 kV
IFC 53 RELAY Very Inverse Time Time-Current Curves
10
IFC 53
800/5
Setting = 4 AT, ?? TD
10 kA 15 kA M
1.21 1 1.05
10
0.34 0.30
3 2
0.1 0.08 0.07
1 ½
0.01
15.6 1
Time Dial Settings
TIME IN SECONDS
100
23.4
4.16 kV 5000 hp 598.9 A, SF = 1
IFC 53 Relay Operating Times Fault Current
15 kA
10 kA
15000/640 = 23.4
10000/640 = 15.6
Time Dial ½
0.07 s
0.08 s
Time Dial 3
0.30 s
0.34 s
Time Dial 10
1.05 s
1.21 s
Multiple of Pick-up
10 100 MULTIPLES OF PICK-UP SETTING
13
Solid-State Relays (SS)
Microprocessor-Based Relays 52B
2000/5 01-52B
41-SWGR-01B 13.8 kV OCR F15B 400/5 01-F15B
Seconds
52B OC1 ANSI-Normal Inverse Pickup = 2.13 (0.05 – 20 xCT Sec) Time Dial = 0.96 Inst = 20 (0.05 – 20 xCT Sec) Time Delay = 0.01 s
F15B OC1 ANSI-Extremely Inverse Pickup = 8 (0.05 – 20 xCT Sec) Time Dial = 0.43 Inst = 20 (0.05 – 20 xCT Sec) Time Delay = 0.02 s
52B – 3P F15B – 3P 30 kA @ 13.8 kV
Amps X 100 (Plot Ref. kV=13.8)
14
Power CBs PWR MCB 3200 A
LT Pickup
16-SWGR-02A 0.48 kV PWR FCB 1600 A
LT Band Power MCB Seconds
Cutler-Hammer RMS 520 Series Sensor = 3200 LT Pickup = 1 (3200 Amps) LT Band = 4 ST Pickup = 2.5 (8000 Amps) ST Band = 0.3 (I^x)t = OUT
Power FCB Cutler-Hammer RMS 520 Series Sensor = 1200 LT Pickup = 1 (1200 Amps) LT Band = 2 ST Pickup = 4 (4500 Amps) ST Band = 0.1 (I^x)t = OUT
ST Pickup ST Band
Power MCB – 3P 47.4 kA @ 0.48 kV
Power FCB – 3P 90.2 kA @ 0.48 kV
Amps X 100 (Plot Ref. kV=0.48)
Insulated & Molded Case CB Insulated Case MCB 1200 A 16-SWGR-02A 0.48 kV Molded Case CB 250 A
Insulated Case MCB Seconds
Frame = 1250 Plug = 1200 A LT Pickup = Fixed (1200 A) LT Band = Fixed ST Pickup = 4 x (4000 A) ST Band = Fixed (I^2)t = IN Override = 14000 A
Molded Case CB HKD Size = 250 A Terminal Trip = Fixed Magnetic Trip = 10
Fault current < Inst. Override
Insulated Case MCB 11 kA @ 0.48 kV
Amps X 100 (Plot Ref. kV=0.48)
15
Insulated & Molded Case CB Insulated Case MCB 1200 A 16-SWGR-02A 0.48 kV Molded Case CB 250 A Insulated Case MCB Seconds
Frame = 1250 Plug = 1200 A LT Pickup = Fixed (1200 A) LT Band = Fixed ST Pickup = 4 x (4000 A) ST Band = Fixed (I^2)t = IN Override = 14000 A
Molded Case CB HKD Size = 250 A Terminal Trip = Fixed Magnetic Trip = 10
Fault current > Inst. Override
Insulated Case MCB 42 kA @ 0.48 kV
Amps X 100 (Plot Ref. kV=0.48)
Power Fuses MCC 1 4.16 kV Mtr Fuse
Seconds
Mtr Fuse JCL (2/03) Standard 5.08 kV 5R
Minimum Melting
Total Clearing
Mtr Fuse 15 kA @ 4.16 kV
Amps X 10 (Plot Ref. kV=4.16 kV)
16
Coordination Time Intervals (CTIs)
Coordination Time Intervals (CTIs) The CTI is the amount of time allowed between a primary device and its upstream backup.
Backup devices wait for sufficient time to allow operation of primary devices.
Primary devices sense, operate & clear the fault first.
Main
Feeder
When two such devices are coordinated such that the primary device “should” operate first at all fault levels, they are “selectively” coordinated.
17
Coordination Time Intervals – EM In the good old days, Main
What typical CTI would we want between the feeder and the main breaker relays? Seconds
Feeder
It depends.
30 kA
Main
Feeder ?s
30 kA Amps X 100 (Plot Ref. kV=13.8)
Coordination Time Intervals – EM On what did it depend? Remember the TD setting? It is continuously adjustable and not exact. So how do you really know where TD = 5? FIELD TESTING ! (not just hand set)
18
Coordination Time Intervals – EM Plotting the field test points.
“3x” means 3 times pickup 3 * 8 = 24 A (9.6 kA primary) 5 * 8 = 40 A (16 kA primary) 8 * 8 = 64 A (25.6 kA primary)
Seconds
Feeder
3x (9.6 kA), 3.3 s 5x (16 kA), 1.24 s 8x (25.6 kA), 0.63 s
30 kA Amps X 100 (Plot Ref. kV=13.8)
Coordination Time Intervals – EM So now, if test points are not provided what should the CTI be?
Main
0.4 s
Feeder
But, if test points are provided what should the CTI be?
0.3 s
Seconds
30 kA Main w/ testing Main w/o testing Feeder
0.3 s 0.4 s
30 kA Amps X 100 (Plot Ref. kV=13.8)
19
Coordination Time Intervals – EM Where does the 0.3 s or 0.4 s come from? 1. 2. 3.
breaker operating time (Feeder breaker) CT, relay errors (both) disk overtravel (Main relay only) Tested
Hand Set
breaker 5 cycle
0.08 s
0.08 s
Disk over travel
0.10 s
0.10 s
CT, relay errors
0.12 s
0.22 s
TOTAL
0.30 s
0.40 s
Main
Feeder
30 kA
Coordination Time Intervals – EM Red Book (per Section 5.7.2.1) Components
Obviously, CTIs can be a subjective issue. Buff Book (taken from Tables 15-1 & 15-2) Field Tested
Components 0.08 s 0.10 s 0.17 s 0.35 s
0.08 s 0.10 s 0.12 s 0.30 s
20
Coordination Time Intervals – EM & SS So, lets move forward a few years…. For a modern (static) relay what part of the margin can be dropped?
Disk overtravel
So if one of the two relays is static, we can use 0.2 s, right?
It depends
Main (EM)
CTI = 0.2 s
CTI = 0.3 s
Main (SS)
(because disk OT is still in play) Feeder (SS)
Feeder (EM)
Coordination Time Intervals – EM & SS Main (EM)
Main (SS)
Feeder (SS)
Feeder (SS)
Main (SS)
Seconds
Main (EM)
Feeder (EM)
Feeder EM 0.3 s
0.2 s
disk OT still applicable Main (EM)
Main (SS)
Feeder (SS) 30 kA @ 13.8 kV
Feeder (EM) 30 kA @ 13.8 kV
Amps X 100 (Plot Ref. kV=13.8)
Amps X 100 (Plot Ref. kV=13.8)
21
Coordination Time Intervals – EM/SS with Banded Devices OC Relay combinations with banded devices EM Relay
Power Fuse
Static Trip or Molded Case Breaker
Static Relay
Power Fuse
Static Trip or Molded Case Breaker
disk over travel √ CT, relay errors √ operating time x CTI
0.1 s 0.12 s 0.22 s
disk over travel x CT, relay errors √ operating time x CTI
0.12 s 0.12 s
Coordination Time Intervals – EM/SS with Banded Devices EM-Banded
SS-Banded
EM Relay
SS Relay
PWR MCB
PWR MCB
PWR MCB
EM Relay
SS Relay
Seconds
PWR MCB
0.22 s
25 kA Amps X 100 (Plot Ref. kV=0.48)
0.12 s
25 kA Amps X 100 (Plot Ref. kV=0.48)
22
Coordination Time Intervals – Banded Devices • Banded characteristics include tolerances & operating times.
Seconds
• There is no intentional/additional time delay needed between two banded devices. • All that is required is clear space (CS).
Amps X 100 (Plot Ref. kV=0.48)
Coordination Time Intervals – Summary
Buff Book (Table 15-3 – Minimum CTIsa)
23
Effect of Fault Current Variations
CTI & Fault Current Magnitude Inverse relay characteristics imply Operating Time
For a fault current of 10 kA the CTI is 0.2 s. For a fault current of 20 kA the CTI is 0.06 s. If CTI is set based on 10 kA, it reduces to less than the desired value at 20 kA.
Feeder
F1 = 10 kA Seconds
Relay Current
Main
Main
F2 = 20 kA
Feeder
0.2 s 0.06 s
F1 = 10 kA
F2 = 20 kA
Amps X 100 (Plot Ref. kV=13.8)
24
Total Bus Fault versus Branch Currents 10 kA 15 kA
1.2 kA
0.8 kA
M
1 kA
2 kA
M
M
•
For a typical distribution bus all feeder relays will see a slightly different maximum fault current.
•
Years back, the simple approach was to use the total bus fault current as the basis of the CTI, including main incomer.
•
Using the same current for the main led to a margin of conservatism.
Total Bus Fault versus Branch Currents
Using Total Bus Fault Current of 15 kA
10 kA
Using Actual Maximum Relay Current of 10 kA
15 kA
Feeder
Feeder
M
0.2 s
15 kA Amps X 100 (Plot Ref. kV=13.8)
Seconds
Main Main
0.8 s
10 kA
15 kA
Amps X 100 (Plot Ref. kV=13.8)
25
Curve Shaping
Using a definite time characteristic (or delayed instantaneous) can eliminate the affect of varying fault current levels.
Seconds
Most modern relays include multiple OC Elements.
0.2 s 20 kA 15 kA 10 kA Amps X 100 (Plot Ref. kV=13.8)
Multiple Source Buses
26
Multiple Source Buses
•
When a bus includes multiple sources, care must be taken to not coordinate all source relays at the total fault current.
•
Source relays should be plotted only to their respective fault currents or their “normalized” plots.
•
Plotting the source curves to the total bus fault current will lead to much larger than actual CTIs.
Multiple Source Buses
Plot to Full Fault Level
2
Plot to Actual Relay Current
3
18 kA
12 kA
2
2
30 kA
1
1
Seconds
1
1.1 s
0.2 s
12 kA
30 kA
Amps X 100 (Plot Ref. kV=13.8)
12 kA
30 kA
Amps X 100 (Plot Ref. kV=13.8)
27
Adjusted Pickup Method
•
Many software packages include the facility to adjust/shift the characteristics of the source relays to line up at the bus maximum fault currents.
•
The shift factor (SF) is calculated using: SF = Bus Fault / Relay Current
Adjusted Pickup Method
Without shift factor both pickups = 3000 A.
2
12 kA
1
30 kA
1
With shift factor relay 2 pickup shifts to 7500 A. SF = (30/12) * 3000 A
1
2
Seconds
2
3
18 kA
12 kA
0.2 s
0.2 s
30 kA
30 kA
Amps X 100 (Plot Ref. kV=13.8)
Amps X 100 (Plot Ref. kV=13.8)
28
Multiple Source Buses
10 kA Bus A
10 kA
5 kA
Bus B
15 kA (Fa) 10 kA (Fb) Fb = 25 kA
Fa = 25 kA
• Different fault locations cause different flows in tie. SF(Fa) = 25 / (10 + 5) = 1.67 SF(Fb) = 25 / 10 =2 • Preparing a TCC for each unique location can confirm defining case. • Cases can be done for varying sources out of service & breaker logic used to enable different setting groups.
Partial Differential Relaying
Source 1 Ip1
Is1
51A
51B
Is1+Is2
0
Is2 Bus A
Source 2 Is2
Ip2
Is2 Bus B
Ip2
Ip1+Ip2 Feeder A
Feeder B
• Typically used on double-ended systems with normally closed ties. • Automatically discriminates between Bus A and Bus B faults. • Eliminates need for relay on tie breaker. • Saves coordination step.
29
Partial Differential Relaying Embellish notes Source 1 Ip1
Is1
51A
51B
0
Is1
Is1 Bus A
Source 2 0
Scheme works even with one source out of service.
0 Open
Is1
Bus B
Ip1
However, the relay in the open source must remain in operation since the relay in the remaining source sees no operating current.
Ip1 Feeder A
Feeder B
Partial Differential Relaying Show same 3 source 1 tie example
30
Directional Current Relaying
67
Bus A
67
Bus B
• Directional overcurrent (67) relays should be used on double-ended line-ups with normally closed ties and buses with multiple sources. • Protection is intended to provide more sensitive and faster detection of faults in the upstream supply system.
Transformer Overcurrent Protection
31
Transformer Overcurrent Protection NEC Table 450.3(A) defines overcurrent setting requirements for primary & secondary protection pickup settings.
Transformer Overcurrent Protection C37.91 defines the ANSI withstand protection limits. Withstand curve defines thermal & mechanical limits of a transformer experiencing a through-fault.
mechanical withstand thermal withstand based on transformer Z
25 x FLC @ 2s
32
Transformer Overcurrent Protection Requirement to protect for mechanical damage is based on frequency of through faults & transformer size. Right-hand side (thermal) used for setting primary protection. Left-hand side (mechanical) used for setting secondary protection.
mechanical withstand thermal withstand 25 x FLC @2s
based on transformer Z
Transformer Overcurrent Protection FLC = 2.4 MVA/(√3 x 13.8) = 100.4 A Relay PU must be ≤ 600% FLC = 602.4 A
PWR-MCB
400 / 100.4 = 398% so okay Time Dial depends on level of protection desired.
Seconds
Using a relay setting of 2.0 x CT, the relay PU = 2 x 200 = 400 A
2.4 MVA, 5.75% Z ∆-Y Resistor Ground
13.8 kV
13.8/0.48 kV 2.4 MVA 5.75% PWR-MCB 480 V
Amps X 10 (Plot Ref. kV=13.8)
33
Transformer Overcurrent Protection ∆-Y Connections – Phase-To-Phase Faults A
0.5
a
0 .5
0
1.0 B
0.866 b
0 .5
0.5
c
C
0.866
• Assume 1:1 turns ratio X1 = X2 = X0 3-Phase fault current = base current. • Phase-phase fault current is typically 0.866 per unit. • This current transforms to 0.5 (0.866/√3) per unit on the delta phase winding and adds up to 1.0 per unit on the line-side.
Add TCC here to show primary relay clipped at 100% secondary fault current coordinated with a secondary relay clipped at 86% of the secondary fault current. Trim down notes on left and summarize that we normally don’t mess with this issue…
• The CTIs need to be set assuming 1.15 (1/0.866) per unit fault current.
Transformer Overcurrent Protection ∆-Y Connections – Phase-To-Ground Faults 1.0
0.577 A
B
a 0
0
0.577
0 0
0.577
0 b
Add TCC with a shifted and non-shifted transformer damage curve….
c
C
• Assume 1:1 turns ratio X1 = X2 = X0 3-Phase fault current = base current. • The 1 per unit phase-ground fault current transforms to 0.577 (1/√3) per unit on the delta phase. • The transformer damage curve is shifted to the left to ensure protection.
34
Will be deleted once the previous page is fixed. For a solidly-grounded secondary
For resistancegrounded secondary PWR-MCB
PWR-MCB
2.4 MVA, 5.75% Z ∆-Y Solid Ground
Seconds
2.4 MVA, 5.75% Z ∆-Y Resistor Ground
13.8 kV
13.8/0.48 kV 2.4 MVA 5.75%
• Withstand curve shifted left due to ∆-Y xfmr. • More difficult to provide protection.
PWR-MCB 480 V
Amps X 10 (Plot Ref. kV=13.8)
Amps X 10 (Plot Ref. kV=13.8)
Transformer Overcurrent Protection Inrush Current PWR-MCB
• Use of 8-12 times FLC @ 0.1 s is an empirical approach based on EM relays. • The instantaneous peak value of the inrush current can actually be much higher than 12 times FLC.
Seconds
2.4 MVA, 5.75% Z ∆-Y Resistor Ground
• The inrush is not over at 0.1 s, the dot just represents a typical rms equivalent of the inrush from energization to this point in time.
13.8 kV
13.8/0.48 kV 2.4 MVA 5.75%
8-12 x FLC (typical)
PWR-MCB 480 V
Amps X 10 (Plot Ref. kV=13.8)
35
Transformer Overcurrent Protection Setting the primary inst. protection PWR-MCB
• The primary relay instantaneous (50) setting should clear both the inrush & the secondary fault current. • It was common to use the asymmetrical rms value of secondary fault current (1.6 x sym) to establish the instantaneous pickup, but most modern relays filter out the DC component.
Seconds
2.4 MVA, 5.75% Z ∆-Y Resistor Ground
13.8 kV
13.8/0.48 kV 2.4 MVA 5.75%
8-12 x FLC (typical)
PWR-MCB 480 V
Amps X 10 (Plot Ref. kV=13.8)
Transformer Overcurrent Protection ∆-Y Connection & Ground Faults
0
0
0
• A secondary L-G fault is not sensed by the ground devices on the primary (∆) side. • Low-resistance and solidly grounded systems are coordinated as separately derived systems.
36
Transformer Overcurrent Protection ∆-Y Connection & Ground Faults • The ground resistor size is selected to limit the fault current while still providing sufficient current for coordination. • The resistor ratings include a maximum continuous current that must be considered.
Motor Overcurrent Protection
37
Motor Overcurrent Protection • Fuse provides short-circuit protection.
GE Multilin 469 Standard O/L Curve Pickup = 1.01 X FLC Curve Multiplier = 3
• 49 or 51 device provide motor overload protection.
Bussmann JCL Size 9R Hot 1000 hp 4.16 kV 650% LRC Seconds
• Overload pickup depends on motor FLC and service factor. • The time delay for the 49/51 protection is based on motor stall time.
M Amps X 10 (Plot Ref. kV=4.16)
Motor Overcurrent Protection GE Multilin 469 Standard O/L Curve Pickup = 1.01 X FLC Curve Multiplier = 3
• In the past, instantaneous OC protection was avoided on contactorfed motors since the contactors could not clear high short-circuits. Hot 1000 hp 4.16 kV 650% LRC Seconds
• With modern relays, a delayed instantaneous can be used if its setting is coordinated with the contactor interrupting rating.
Bussmann JCL Size 9R
Contactor 6 kA Int. M Amps X 10 (Plot Ref. kV=4.16)
38
Motor Overcurrent Protection • The instantaneous setting for a breaker-fed motor must be set to pass the motor asymmetrical inrush. • Can be done with a pickup over the asymmetrical current.
GE Multilin 469 Standard O/L Curve Pickup = 1.01 X FLC Curve Multiplier = 3
1000 hp 4.16 kV 650% LRC
Hot
Seconds
• Can be done using a lower pickup with time delay to allow DC component to decay out.
3 kA @ 4.16 kV
M
Amps X 10 (Plot Ref. kV=4.16)
Conductor Overcurrent Protection
39
Conductor Overcurrent Protection LV Cables NEC 240.4 Protection of Conductors – conductors shall be protected against overcurrent in accordance with their ampacities (B) Devices Rated 800 A or Less – the next higher standard device rating shall be permitted (C) Devices Rated over 800 A – the ampacity of the conductors shall be ≥ the device rating
NEC 240.6 Standard Ampere Ratings (A) Fuses & Fixed-Trip Circuit Breakers – cites all standard ratings (B) Adjustable Trip Circuit Breakers – Rating shall be equal to maximum setting (C) Restricted Access Adjustable-Trip Circuit Breakers – Rating can be equal to setting if access is restricted
Conductor Overcurrent Protection MV Cables NEC 240.101 (A) Rating or Setting of Overcurrent Protective Devices Fuse rating ≤ 3 times conductor ampacity Relay setting ≤ 6 times conductor ampacity
40
Conductor Overcurrent Protection • The insulation temperature rating is typically used as the operating temperature (To).
Seconds
• The final temperature (Tf) depends on the insulation type (typically 150 deg. C or 250 deg. C).
1 – 3/C 350 kcmil Copper Rubber Tc = 90 deg. C
• When calculated by hand, you only need one point and then draw in at a -2 slope.
Amps X 100 (Plot Ref. V=600)
Generator Overcurrent Protection
41
Generator Overcurrent Protection •
A generators fault current contribution decays over time.
•
Overcurrent protection must allow both for moderate overloads & be sensitive enough to detect the steady state contribution to a system fault.
Generator Overcurrent Protection FLC/Xd
•
Voltage controlled/ restrained relays (51V) are commonly used.
•
The pickup at full restraint is typically ≥ 150% of Full Load Current (FLC).
•
The pickup at no restraint must be < FLC/Xd.
42
Generator 51V Pickup Setting Example
Fg
19500 kVA 903 A Xd = 280%
1200/5
51V
12.47 kV
Fg = FLC/Xd = 903 / 2.8 = 322.5 A 51V pickup (full restraint)
> 150% FLC = 1354 A
51V pickup (no restraint)
< 322.5 A
Generator 51V Pickup Setting Example 51V Setting > 1354/1200 Using 1.15, 51V pickup With old EM relays, 51V pickup (no restraint)
= 1.13 = 1.15 x 1200 A = 1380 A
= 25% of 1380 A = 345 A (> 322.5 A, not good)
With new relays a lower MF can be set, such that 51V pickup (no restraint) = 15% of 1380 A = 207 A (< 322.5, so okay)
43
Generator 51V Settings on TCC
Seconds
15% x Pickup
Pickup = 1.15 x CT-Sec
GTG-101A No Load Constant Excitation Total Fault Current
• Limited guidance on overcurrent protection (C37.102 Section 4.1.1) with respect to time delay. • Want to avoid nuisance tripping, especially on islanded systems, so higher TDs are better.
30 kA
Amps X 10 (Plot Ref. kV=12.47)
Coordinating a System
44
Coordinating a System • TCCs show both protection & coordination. • Most OC settings should be shown/confirmed on TCCs. • Showing too much on a single TCC can make it impossible to read.
Coordinating a System Showing a vertical slice of the system can reduce crowding, but still be hard to read. Upstream equipment is shown on multiple and redundant TCCs.
45
TCC Zone Map
TCC-6 TCC-3 TCC-2
TCC-5 TCC-1
TCC-Comp
TCC-4
TCC-307J TCC-101J
TCC-212J
Coordinating a System: TCC-1 Zone Map
•Motor starting & protection is adequate. •Cable withstand protection is adequate. •The MCC main breaker may trip for faults above 11 kA, but this cannot be helped. •The switchgear feeder breaker is selective with the MCC main breaker, although not necessarily required
46
Coordinating a System: TCC-2 Zone Map
•
• •
•
The switchgear feeder breaker settings established on TCC-1 set the basis for this curve. The main breaker is set to be selective with the feeder at all fault levels. A CTI marker is not required since the characteristic curves include all margins and breaker operating times. The main breaker curve is clipped at its through-fault current instead of the total bus fault current to allow tighter coordination of the upstream relay.
Coordinating a System: TCC-3 Zone Map
• •
•
•
The LV switchgear main breaker settings established on TCC-2 set the basis for this curve. The transformer damage curve is based on frequent faults and is not shifted since the transformer is resistance grounded. The primary side OC relay is selective with the secondary main and provides adequate transformer and feeder cable protection. The OC relay instantaneous high enough to pass the secondary fault current and transformer inrush current.
47
Coordinating a System: TCC-307J Zone Map
•
This curve sets the basis for the upstream devices since its motor is the largest on the MCC. Motor starting and overload protection is acceptable. Motor feeder cable protection is acceptable The motor relay includes a second definite time unit to provide enhanced protection. The definite time function is delay to allow the asymmetrical inrush current to pass.
• • • •
Coordinating a System: TCC-4 Zone Map
• • • •
• •
The 307J motor relay settings established on TCC-307J set the basis for this curve. The tie breaker relay curve is plotted to the total bus fault current to be conservative. The main breaker relay curve is plotted to its let-through current. A coordination step is provided between the tie and main relay although this decision is discretionary. All devices are selectively coordinated at all fault current levels. The definite time functions insulation the CTIs from minor fault current variations..
48
Coordinating a System: TCC-5 Zone Map
•
The MV MCC main breaker settings established on TCC-4 set the basis for this curve. The transformer damage curve is based on frequent faults and is not shifted since the transformer is resistance grounded. The primary side OC relay is selective with the secondary main and provides adequate transformer and feeder cable protection. The OC relay instantaneous high enough to pass the secondary fault current and transformer inrush current.
•
•
•
Coordinating a System: TCC-Comp Zone Map
•
• •
•
Due to the compressor size, this curve may set the basis for the MV switchgear main breaker. Motor starting and overload protection is acceptable. Short-circuit protection is provided by the relay/breaker instead of a fuse as with the 1000 hp motor. The short-circuit protection is delay 50 ms to avoid nuisance tripping.
49
Coordinating a System: TCC-6 Zone Map
•
•
•
• •
The feeder breaker settings established on TCC-3, TCC-4, and TCC-Comp are shown as the basis for this curve. The settings for feeder 52A1 (to the 2.4 MVA) could be omitted since it does not define any requirements. A coordination step is provided between the tie and main relay although this decision is discretionary. All devices are selectively coordinated at all fault current levels. The definite time functions insulation the CTIs from minor fault current variations.
TCC Zone Map
TCC-G1
TCC-G2
50
Coordination Pop Quiz #1 2000/5
OCR
Does this TCC look good??
Main SWGR-1 400/5
OCR 600/5 TR-FDR1
OCR
•
There is no need to maintain a coordination interval between feeder breakers.
•
The CTI between the main and feeder 2 is appropriate unless all relays are electromechanical and hand set.
TR-FDR2
0.301 s 0.3 s
Coordination Pop Quiz #2 2000/5
Does this TCC look good??
OCR
Main-1 SWGR-3 400/5
OCR
600/5 FDR-1
•
The CTIs shown between main and both feeders are sufficient.
•
Assuming testing EM relays, the 0.615s CTI cannot be reduced since the 0.304s CTI is at the limit.
•
The main relay time delay is actually too fast since the CTI at 30 kA is less than 0.2s.
OCR
FDR-2
0.615 s 0.304 s
51
Coordination Pop Quiz #3 Does this TCC look good?? •
The marked CTIs are okay, but….
•
A main should never include an instantaneous setting.
0.472 s 0.325 s
Coordination Pop Quiz #4 Does this TCC look good?? •
Primary relay pickup is 525% of transformer FLC, thus okay.
•
Transformer frequent fault protection is not provided by the primary relay, but this is okay – adequate protection is provided by the secondary main.
•
Cable withstand protection is inadequate. Adding a 50 to the primary relay would be appropriate and fix this.
52
Coordination Pop Quiz #5 Does this TCC look good?? •
Crossing of feeder characteristics is no problem.
•
There is no need to maintain an intentional time margin between two LV static trip units – clear space is sufficient.
0.021 s
Coordination Pop Quiz #6 Does this TCC look good??
0.03 s
•
The source relays should not be plotted to the full bus fault level unless their plots are shifted based on: SF = Total fault current / relay current.
•
Assuming each relay actually sees only half of the total fault current, the CTI is actually much higher than 0.3s.
53
Coordination Pop Quiz #7 Does this TCC look good?? •
There are two curves to be concerned with for a 51V – full restraint and zero restraint.
•
Assuming the full restraint curve is shown, it is coordinated too tightly with the feeder.
•
The 51V curve will shift left and lose selectivity with the feeder if a close-in fault occurs and the voltage drops.
0.302 s
Coordination Software • Computer-aided coordination software programs originated in the late 1980s. • The accuracy of the device characteristic curves was often highly questionable. • There are numerous, much more powerful programs available today, many of which are very mature. • Even still, the accuracy of the protective devices functions and characteristics is still extremely critical.
54
Coordination Software • For many years clients maintained separate impedance models for power studies and protective device models for coordination studies. • Integrated models are now the norm and are required to support arc-flash studies.
Information Required
55
Accurate One-Line Diagram
Equipment Ratings
• drive short-circuit calculations • affect asymmetrical currents
56
Equipment Ratings
• drives short-circuit calculations • affects transformer through-fault protection • inrush affects settings
Equipment Ratings
• • • •
size and construction ampacity insulation type/rating affects I2t damage curve
57
Equipment Ratings
• bus continuous rating affects relay pickup (different for LV and MV) • short-circuit rating must be adequate but does not affect overcurrent coordination • differing fault current affect coordination
Equipment Ratings
• adds to short-circuit • LRC, acceleration time, & hot/ cold stall times affect time curve selection
58
Protective Devices • Make & model • CT Ratio • Tap & time dial settings (old days) • setting files (today) • Trip device type • LT, ST, Inst settings
References
59
Selected References • • • • • • • • •
Applied Protective Relaying – Westinghouse Protective Relaying – Blackburn IEEE Std 242 – Buff Book IEEE Std 141 – Red Book IEEE Std 399 – Brown Book IEEE C37.90 – Relays IEEE C37.91 – Transformer Protection IEEE C37.102 – Guide for AC Generator Protection NFPA 70 – National Electrical Code
120
60
View more...
Comments