NOVEC 1230 Total Flooding System Calculations Hazard Area No.1 Protected Hazard Dimensions Name of Protected Hazard Area Height Area
Tel 3.0
m
100.0
m2
Volume
300
m3
Volume of Fixed Structures Impervious to Agent vapor
0.0
m3
Design Parameters Class of Fire Hazard Net Volume of Hazard Area Design Temperature in Hazard Area Agent Specific Volume @ 1 Atm. pressure
A 300.0 20 0.072
m3 o
C
m3/kg
Minimum Design Concentration
4.2
% per volume
Agent Design Concentration
5.4
% per volume
Tee Count of Piping System
6.0
Hazard Area Pressure
1.0
Design Safety Factor
0.02
atm
System Sizing Agent Net Capacity
243.0
kg
Computed By:
Project:
Checked By:
Date:
Agent Net Capacity Percentage Total Agent Flow Rate Required No. of discharge Nozzels Acual Flow per Nozzel
Approved By:
67 24.3
% kg/sec
3 8.1
kg/sec
Nozzel and Branch Pipe Diameters
1 1/2
inch
Main Pipe Diameter
2 1/2
inch
Computed By:
Project:
Checked By:
Date:
Approved By:
Hazard Area No.2 Protected Hazard Dimensions Name of Protected Hazard Area Height
elect 3.0
m
Area
50.0
m2
Volume
150
m3
Volume of Fixed Structures Impervious to Agent vapor
0.0
m3
Design Parameters Class of Fire Hazard Net Volume of Hazard Area Design Temperature in Hazard Area Agent Specific Volume @ 1 Atm. pressure
C 150.0 20 0.072
m3 o
C
m3/kg
Minimum Design Concentration
4.2
% per volume
Agent Design Concentration
5.4
% per volume
Tee Count of Piping System
6.0
Hazard Area Pressure
1.0
Design Safety Factor
0.02
atm
System Sizing Agent Net Capacity Agent Net Capacity Percentage
121.5
kg
33
%
Computed By:
Project:
Checked By:
Date:
Total Agent Flow Rate Required No. of discharge Nozzels Acual Flow per Nozzel Nozzel and Branch Pipe Diameters Main Pipe Diameter
Approved By:
12.1
kg/sec
2 6.1
kg/sec
1 1/2
inch
2
inch
Computed By:
Project:
Checked By:
Date:
Approved By:
Combined System Sizing Agent Total Net Capacity
364.5
Container Size Selection
Container Size 900 Ib
Total Required No. of Containers
kg
1
Agent Net Capacity in Each Container
364.5 803.5
kg Ibs
Total Agent Flow Rate
36.4
kg/sec
Maximum Agent Flow Rate per Nozzel
9.07
kg/sec
Total Required No. of discharge Nozzels
5
System Main Pipe Diameter
3
inch
Checking Agent Concentration in a Combind Space with Directional Valve Name of Protected Hazard Area Height Area
Tel 3.0
m
200.0
m2
Volume
600
m3
Volume of Fixed Structures Impervious to Agent vapor
0.0
m3
Design Parameters Class of Fire Hazard Minimum Design Concentration Net Volume of Hazard Area
B 4.2 600.0
% per volume m3
Computed By:
Project:
Checked By:
Date:
Design Temperature in Hazard Area Agent Specific Volume @ 1 Atm. pressure
Approved By:
27 0.074
Tee Count of Piping System
6.0
Hazard Area Pressure
1.0
Design Safety Factor
0.02
Agent Design Concentration
4.2
o
C
m3/kg
atm
%
Computed By:
Project:
Checked By:
Date:
Approved By:
General Design Considerations - Max. No. of Nozzels in the System - Maximum Agent Flow Rate per Nozzel - Maximum Discharge Time - Nozzel Maximum Coverage Radius - Min. Nozzel Pressure - Maximum Ceiling Height - Nozzel Max. Distance from Ceiling - False Ceiling or Raised Floor Min. Height - Space Min. agent percentage in combind system
20 9.07 10 8.70 10.90 73 4.87 0.30 0.30 10
kg/sec sec m psi m m m %
- Beams that are less than 0.3 m below the slab need not be considered. Obstructions greater than 300 mm (12”) can affect the distribution of agent and may require additional nozzles. - The max. elevation difference between the container outlet and the furthest horizontal pipe run or discharge nozzle (whichever is furthest) shall not exceed 9.1 m.
- The max. elevation difference between the furthest horizontal pipe runs or discharge nozzles (whicheve is furthest) shall not exceed 9.1 m. - The agent design concentration shall be checked to insure that it is under NOAEL at maximum anticipated temperature in the hazard space. - Sizing is based on NFPA-2001
Eng. H.S & E.S Eng. M. Gamal Dr. H. Soliman
em Calculations
1076.4
ft2
535.7
Ibs
ّّ
Eng. H.S & E.S Eng. M. Gamal Dr. H. Soliman
Accepted 53.6
Ibs/sec
17.9 Ibs/sec
3
Eng. H.S & E.S Eng. M. Gamal Dr. H. Soliman
538.2
ft2
267.8
Ibs
ّّ
Accepted
Eng. H.S & E.S Eng. M. Gamal Dr. H. Soliman
26.8
Ibs/sec
13.4 Ibs/sec
2 1/2
Eng. H.S & E.S Eng. M. Gamal Dr. H. Soliman
803.5
Ibs
Minimum Fill ###Ibs 455
Accepted 80.4
Ibs/sec
20
Ibs/sec
Accepted 3
with Directional Valve
2152.8
ft2
Eng. H.S & E.S Eng. M. Gamal Dr. H. Soliman
Accepted
Eng. H.S & E.S Eng. M. Gamal Dr. H. Soliman
20
Ibs/sec
360o Nozzel Type 180o Nozzel Type
dered. Obstructions greater than 300 onal nozzles.