DeltaV De ltaV v14.LT v14.LTS S (Long Te Term rm Suppo rt) / v 14 14.3 .3.1 .1 S Soft oft ware Upd Updates ates    Ar ti cl  Arti cle e ID: Publish Date:  Ar  Arti ti cl cle e Stat us :  Ar  Arti ti cl cle e Type: Typ e: Required Required Actio n:

NK-1900-0840 13 Jul 2021  Ap pr ov ed Product Issues  As Needed

Recent Article Revision History: Re Revision/Publish vision/Publish De Description scription of Re Revision vision  Added  Ad ded Delt aV_1431_WS_21_CSS as Tar Target get ed Dist Di st ri bu ti tion on bu nd le. Mov ed 13 Jul 2021  DeltaV_1431_WS_20_CSS to General Maintenance bundle. (See end of article for a complete revision hi story listing .) (See end  AfProduct fec ted Pro duct du ct s: Line DeltaV 

DeltaV DeltaV DeltaV

Category Upgrade Upgrade Work stati on Softw are Workstatio n Software

Device Offline Upgrade Service Online Upgrade Service VE210 VE2104P01 4P01 DeltaV Liv e VE2 VE210x 10x DeltaV Workstation

Version

v14.LTS v14.LT v14.LTS S

 

1  Introduction  2  Download Links   2.1  Controller   2.2  Workstation and Batch  2.3  I/O  2.4  Safety Logic Solver   2.5  Independent DeltaV Domain Controller   2.6  Targeted Distribution Bundle 

3  Resolved Issues   3.1  Controller   3.2  Workstation and Batch  3.3  I/O  3.4  Safety Logic Solver   3.5  Independent DeltaV Domain Controller  

1

Introduction

 

This Knowledge Base Article, NK-1900-0840 , provides a list of hotfixes for DeltaV v14.LTS (previously known as v14.3.1). Note: Long-term Support (LTS) refers to a major DeltaV version as an example of what we previously denote as DeltaV v14.3.1 English. DeltaV v14.3.1 LTS is the same as DeltaV v14.LTS. For more information, refer to KBA  KBA NK-1900-0775: DeltaV v14.LTS (Long Term Support) and v14.FP (Feature Pack) Release Notes. 

Hotfixes are organized into bundles. A hotfix bundle combines several patches into a single installer package. Hotfixes within bundles are categorized based on various hardware types. When a new bundle is required for a specific category, the new bundle will always include all patches contained in the preceding bundles for that category. When installing a new bundle for any hotfix category, the previous bundle must be removed first. This is enforced by the installer for the newer bundle.  After downloading the zip file, extract the compressed compr file. Eachhotfix compressed file will instructions. contai contain n a ReadMe file and an installer executable. Refer to the ReadMe file in essed each individual for installation In some cases, it will be necessary to remove hotfixes previously installed on the system . Each ReadMe file contains a list of these hotfixes to be removed. Targeted Distribution

 

Distribution is intended for customers who who are a att risk of experiencing a specific issue where Emerson has created a hotfix bundle in response.

 

Installation of the Targeted Hotfix bundle is typically an accelerated  action, and reactive to the issue experienced.

 

Resolved issues are listed in the Hotfix B Bundle undle Readme File and the Software Software U Updates pdates KB KBA. A.

 

Installation method recommended is via manual installation, this hotfix bu bundle ndle is not available for Automated Patch Management

 

Installation of the Targeted Hotfix Hotfix bundle resolve resolves s issues identified for for impact impacted ed custom customers. ers.











Page 2 of 56 

 

General Ge neral Ma Maintenance intenance Distrib ution

 

Distribution is intended for customers who will will proactively install hotfix bundles on a regular or scheduled basis.

 

Installation of the General Maintenance Hotfix bundle is typically a scheduled , and proactive action to keep system in best state to address Guardian Health Score and is recommended for most users.

 

Installation method can be either through Automated Automated Patch Management or via manual installation.







Targeted Distribution Bundles will move to the General Maintenance designation roughly 4-8 4 -8 weeks after introduction to field  To run the hotfix, double-click on the exe file. Note:  After installing the latest hotfix/es, rerun the rregistration egistration utility and submit the system content data. This ensures that the information in Emerson’s database remains current, thus enabling Emerson to provide system-content-specific product service notifications and effective technical support.



Download Links Important: DeltaV binaries and files are signed with Emerson certificates that have limited validity period. When an Emerson certificate expires, new DeltaV binaries are signed with a new certificate with extended validity. DeltaV Systems with Emerson’s Application Whi telisting installed and Solidcore set to Enabled mode will block DeltaV binaries and files signed si gned with the new certificate if the existing Application Whitelisting installation is not yet updated with the latest DeltaV Trusted Publishers Rule Group. Always check and apply the latest available Application Whitelisting for DeltaV Hotfix Bundle before installing installi ng new DeltaV Hotfixes as special prerequisite for systems with Emerson’s Application Whitelisting installed.  

See KBA  KBA NK-2000-0514: DeltaV Systems v2.3 Application Whitelisting for Solidcore Blocks Binaries Signed using the New Emerson Certificate  for more information.

2.1

Controller

Controllerr Controlle

MD+ and SD+

Download Downloa d Link

https://gsuds.emerson.com/pickup/psg/DeltaV_1431_C TRL_P_04_CSS.zip: zip: (Size: https://gsuds.emerson.com/pickup/psg/DeltaV_1431_CTRL_P_04_CSS. 12369 KB)  KB)  Checksum: 5F066770FE7434E3576B8DDDA6012F2D17500A0D750B 5F066770FE7434E3576B8DDD A6012F2D17500A0D750BFF9E47E08C9B04C4AFB FF9E47E08C9B04C4AFBA A

Software Revision

14.3.1.7313

https://gsuds.emerson.com/pickup/psg/DeltaV_1431_CTRL_Q_05_CSS.zip: https://gsuds.emerson.com/pickup/psg/DeltaV_1431_C TRL_Q_05_CSS.zip: (Size: MQ, MX, SQ, and SX

SZ

PK

29146 KB)  KB)  Checksum: BA1EA4FF270A81C390C43616D5299863679B058A9A19D2D5C23C65840D6ED7F2 https://gsuds.emer https://gsuds.emerson.com/pickup/psg/DeltaV_1431_C son.com/pickup/psg/DeltaV_1431_CTRL_SZ_05_CSS. TRL_SZ_05_CSS.zip: zip: (Size: 18442 KB)  KB)  Checksum: 5B6631D523929425302F46ED1FECE86C64D366078C2E2A32728D54199C4D2720 https://gsuds.emerson.com/pickup/psg/DeltaV_1431_C TRL_PK_08_CSS.zip: .zip: (Size: https://gsuds.emerson.com/pickup/psg/DeltaV_1431_CTRL_PK_08_CSS 30667 KB)  KB)  Checksum: 780F43511030DEC69787F28BA0A175711C58B81F58E2F923E448610DBB286646

14.3.1.7313

14.3.1.7313

14.3.1.7313

For the list of resolved issues, refer to Section 3.1. Section 3.1.  

Page 3 of 56 

 

Note: Do not upgrade a simplex controller on a running process. Only redundant controllers should be upgraded on a live process. Refer to the text file included with the hotfix installer for additional considerations before flash upgrading controllers.

2.2 2.2

Workstation and Batch Download Downloa d Link For General General Ma Maintenance intenance Distribut ion

Workstation and Batch

https://gsuds.emerson.com/pickup/PSG/DeltaV_1431_WS_20_CSS https://gsuds.emerson.com/pickup/PSG /DeltaV_1431_WS_20_CSS.zip: .zip: (Size: 540632 KB)  KB)  Checksum: 17A84E74848178433897BBCA4ED75A92C85837C 17A84E74848178433897BBC A4ED75A92C85837C4230DBB1781FC42645A9A 4230DBB1781FC42645A9AE7A4 E7A4 https://gsuds.emerson.com/pickup/PSG/DeltaV_1431_TFSB158919_BHS https://gsuds.emerson.com/pickup/PSG /DeltaV_1431_TFSB158919_BHServer.zip: erver.zip: (Size: 6965 KB)  KB)  Checksum: 9FD4983362FB8F7E486508E1915A368D7FF8455D89C880D05E22E1EAC420287F

Standalone Hotfixes

https://gsuds.emerson.com/pickup/PSG/DeltaV_1431_TFSB437235_BHS https://gsuds.emerson.com/pickup/PSG /DeltaV_1431_TFSB437235_BHServer.zip: erver.zip: (Size: 3 KB)  KB)   Checksum: 7876751054A0B711A7E4E424B5BBD8FF534D88681FE 7876751054A0B711A7E4E42 4B5BBD8FF534D88681FEB800B4A2CDF3B6B B800B4A2CDF3B6B30C6D0 30C6D0 https://gsuds.emerson.com/pickup/PSG rson.com/pickup/PSG/SOA_Gateway_1431_TFS3 /SOA_Gateway_1431_TFS338729.zip: 38729.zip: (Size: https://gsuds.eme 82251 KB)  KB)  Checksum: BFACCC63BC21F3B055BD2C546537B5A BFACCC63B C21F3B055BD2C546537B5A12EFC18EA2872D50926B 12EFC18EA2872D50926B1A825167A3515 1A825167A3515

For the list of resolved issues, refer to Section 3.2. Section 3.2.   Important: Installing hotfix bundles DeltaV_1431_WS_01_CSS through DeltaV_1431_WS_15_CSS DeltaV_1431_WS_15_CSS resets the startup type of the DeltaV OPC.NET Server and DeltaV OPC UA Server to “Automatic.” For redundant application stations, please reset the startup type of the services back to “Automatic (Delayed start)” to prevent the issue described in KBA KBA  NK-2000-0621: Redundant Application Station Have Bad Redundancy and Failed Component Status After a Switchover .  Important: Important note for customers considering upgrading to DeltaV v14.FP1 using the DeltaV_1431_FP_01 installer. An issue has been found with the original release of this installer, located on iso file DeltaV14.3.1_FP1_13P0855A_DeltaV.iso DeltaV14.3.1_FP1_13P0855A_DeltaV.iso and equivale equivalent nt physical media. The installer is supposed to

automatically remove all installed DeltaV_1431 hotfixes before it is installed. The issue is that the installer will only detect and remove DeltaV_1431 hotfixes that were created before it was created. DeltaV De ltaV hotfixes not detected by this hotfix include DeltaV_1431_EIOC_07_CSS, DeltaV_1431_EIOC_07_CSS, DeltaV_1431_WS_11_CSS DeltaV_1431_WS_11_CSS,, DeltaV_1431_WS_12_CSS, DeltaV_1431_WS_12_CS S, DeltaV_1431_WS_13_CSS, and any hotfix added after the date of this note (September 17th). A new DeltaV_1431_FP_01 is being created to address this issue. is sue. See KBA  KBA NK-20000622: Installing DeltaV_1431_FP_01 May Allow Corruption of the DeltaV v14.FP1 Upgrade Installation  for additional details on the issue and for details on the release of the replacement installer package. Important: Special Installation Instructions when updating Batch Historian workstations from hotfix bundle DeltaV_1431_WS_06_CSS or earlier to hotfix bundle DeltaV_1431_WS_07_CSS DeltaV_1431_WS_06_CSS DeltaV_1431_WS_07_CSS or later:

Hotfix bundle DeltaV_1431_WS_07_CSS contains fixes for TFSB164663 and TFSB171847. (See description of these issues in the resolved issues Section 3.2. Section 3.2.)) The first time these hotfixes are installed on a system with a Batch Historian workstation they must be installed on the Batch Historian workstation BEFORE they are installed on the following workstations:  

Batch Executive.

 

Any E Event vent Chronicle workstation that is reporting Alarms Alarms & Events d data ata to the Batch Historian.





Page 4 of 56 

 

This is only a requirement r equirement the first time that the fixes for TFSB164663 and TFSB171847 are installed. install ed. That means that when the system is updated from DeltaV_1431_WS_06_CSS (or an earlier bundle) to DeltaV_1431_WS_07_CSS DeltaV_1431_WS_07_CS S (or later) this installation order must be followed but on future updates from DeltaV_1431_WS_07_CSS DeltaV_1431_WS_07_CS S (or later) to a subsequent hotfix bundle, the installation order on workstations does not matter. Note: Bundles DeltaV_1431_WS_02_CSS to DeltaV_1431_WS_06_CSS will not be uninstalled automatically when DeltaV v14.3.1 is uninstalled. These bundles will need to be manually uninstalled prior to uninstalling DeltaV. Bundle DeltaV_1431_WS_07_CSS and later do not exhibit this issue. Note: This bundle includes DeltaV Data Collector software version DDC_5101. The DDC software is located in the DeltaV\DVData folder. For more information refer to KBA KBA  NK-1100-1172: DeltaV Data Collector Utility Quick Start Installation and Usage Guide . 

2.3

I/O I/O I/O

CHARMs I/O Card

CHARMs I/O Card 2

Ethernet I/O Card

Wireless I/O Card

Download Link

https://gsuds.emerson.com/pickup/PSG/DeltaV_1431_CIOC_02_CS https://gsuds.emerson.com/pickup/PSG/D eltaV_1431_CIOC_02_CSS.zip: S.zip: (Size: 14892 KB)   KB) Checksum: 0E53F81CC40E6B58A46618F78160D0633B173A2C41C8A4EEF07F16FA623BF3A8 https://gsuds.emerson.com/pickup/PSG/D son.com/pickup/PSG/DeltaV_1431_CIOC2_02_CS eltaV_1431_CIOC2_02_CSS.zip: S.zip: (Size: https://gsuds.emer 15765 KB)  KB)  Checksum: 4A238EBF0B2AE0D0BDDD0BD00619069BB00C0FCC5E 4A238EBF0B2AE0D0BDDD0B D00619069BB00C0FCC5E7602942C7D76655A2B8A2A 7602942C7D76655A2B8A2A https://gsuds.emer https://gsuds.emerson.com/pickup/psg/DeltaV_14 son.com/pickup/psg/DeltaV_1431_EIOC_08_CSS. 31_EIOC_08_CSS.zip: zip: (Size: 22485 KB)   KB) Checksum: 342AAD0323F9E5CB883AAFF48B913395F073045F466AB2E17F612C8B4EA680F6 https://gsuds.emerson.com/pickup/psg/DeltaV_14 son.com/pickup/psg/DeltaV_1431_WIOC_02_CSS.zip 31_WIOC_02_CSS.zip:: (Size: 24530 https://gsuds.emer KB)   KB) Checksum: 33D17CABAEC956E9F464F4723AE98E05D 33D17CABAE C956E9F464F4723AE98E05DDA7CCE40C303408136B DA7CCE40C303408136BCF9D55CB7232 CF9D55CB7232

Software Revision

14.3.1.7301

14.3.1.7301

14.3.1.7313

14.3.1.7293

For the list of resolved issues, refer to Section 3.3. Section 3.3.   For the complete list of I/O release independent software updates, refer to KBA  KBA  NK-2000-0197: DeltaV I/O Release Independent Software Updates . 

2.4

Safety Safety Logic Log ic Solver

For more information and to download the latest Safety Logic Server hotfix bundle, refer to KBA  KBA  AP-0800-0154: AP-0800-0154: DeltaV Safety Instrumented Systems (SIS) Software Updates . Refer to the ReadMe file for the installation instructions.

2.5

Independent DeltaV DeltaV Domain Contro ller ll er Download Downloa d Link

Standalone Hotfixes

https://gsuds.emerson.com/pickup/PSG/DeltaV_1431_B180903_IDDC https://gsuds.emerson.com/pickup/PSG /DeltaV_1431_B180903_IDDC.zip: .zip: (Size: 8412 KB)   KB) Checksum: EFBC08ADED7BC6CD7FB5692E EFBC08ADE D7BC6CD7FB5692E71D48AAA5A265FFB4E 71D48AAA5A265FFB4E5B68CAD59828465FB683F4 5B68CAD59828465FB683F4

For the list of resolved issues, refer to Section 3.5. Section 3.5.  

Page 5 of 56 

 

2.6 2. 6

Targeted Targeted Distribut ion Bundle

Controllerr Controlle

MD+ and SD+

MQ, MX, SQ, and SX

Download Downloa d Link

https://gsuds.emerson.com/pickup/psg/DeltaV_1431_CTRL_P_05_CSS. https://gsuds.emerson.com/pickup/psg/DeltaV_1431_C TRL_P_05_CSS.zip: zip: (Size: 12747 KB)  KB)  Checksum: 83CE78AE936AA0ECC533AA9AE 83CE78AE936AA 0ECC533AA9AEF026A45F29E28FBB4F18B6A5938 F026A45F29E28FBB4F18B6A5938991DFE82E1D0 991DFE82E1D0

Checksum: 4AAA3860D1E2E99A4B75595BE33ED 4AAA3860D1E2E 99A4B75595BE33ED8E08A89C92498269C44072B7B82 8E08A89C92498269C44072B7B827AA9A6D9 7AA9A6D9

Checksum: 80783656367667C4069B026318ACD3F49CBBFF478ED29A650E82840CA8200763 https://gsuds.emerson.com/pickup/psg/DeltaV_1431_C TRL_PK_09_CSS.zip: zip: (Size: https://gsuds.emerson.com/pickup/psg/DeltaV_1431_CTRL_PK_09_CSS. 31865 KB)  KB) 

PK

Checksum: 4158E6D5C4851405AB07DCFDC744A7922049C9ED 4158E6D5C4851405AB07D CFDC744A7922049C9ED9C3E4893EE985892DC 9C3E4893EE985892DCEE0D63 EE0D63

Workstation and Batch

Workstation and Batch

CHARMs I/O Card 2

Ethernet I/O Card

Wireless I/O Card

14.3.1.7332

14.3.1.7331

14.3.1.7332

Download Downloa d Lin k

https://gsuds.emerson.com/pickup/PSG/DeltaV_1431_WS_21_CSS https://gsuds.emerson.com/pickup/PSG /DeltaV_1431_WS_21_CSS.zip: .zip: (Size: 565961 KB)   KB) Checksum: 79395CD04C60B1E07DAF643A1BC926149580D4E3C990C60D6EE188FF4394F738

I/O

CHARMs I/O Card

14.3.1.7332

https://gsuds.emerson.com/pickup/psg/DeltaV_1431_C TRL_Q_06_CSS.zip: (Size: https://gsuds.emerson.com/pickup/psg/DeltaV_1431_CTRL_Q_06_CSS.zip: 31540 KB)  KB) 

https://gsuds.emerson.com/pickup/psg/DeltaV_1431_C TRL_SZ_06_CSS.zip: zip: (Size: https://gsuds.emerson.com/pickup/psg/DeltaV_1431_CTRL_SZ_06_CSS. 19797 KB)  KB) 

SZ

Software Revision

Download Link

https://gsuds.emerson.com/pickup/PSG/DeltaV_1431_CIOC_03_CS https://gsuds.emerson.com/pickup/PSG /DeltaV_1431_CIOC_03_CSS.zip: S.zip: (Size: 16145 KB)   KB) Checksum: 350CEA50FA737B941111E8DC04AF23F8D9B 350CEA50FA737B94 1111E8DC04AF23F8D9BEE7140DB2724E0E69D46044A24 EE7140DB2724E0E69D46044A24A28 A28 https://gsuds.emerson.com/pickup/PSG/DeltaV_1431_CIOC2_03_CS https://gsuds.emerson.com/pickup/PSG /DeltaV_1431_CIOC2_03_CSS.zip: S.zip: (Size: 16830 KB)  KB)  Checksum: 1896D545161EF9E9D436CE99875B5AA303FB3FEBA3F71744A0A4934C487A789C https://gsuds.emerson.com/pickup/psg/DeltaV_1431_EIOC_09_CSS. https://gsuds.emerson.com/pickup/psg/DeltaV _1431_EIOC_09_CSS.zip: zip: (Size: 23845 KB)   KB) Checksum: C20E45371BC4E7AA3084B07C414892E61F80345826A C20E45371BC4E 7AA3084B07C414892E61F80345826AF3CB840F8B6ECC1B F3CB840F8B6ECC1B4B6DC 4B6DC https://gsuds.emerson.com/pickup/psg/DeltaV _1431_WIOC_03_CSS.zip: zip: (Size: 25242 https://gsuds.emerson.com/pickup/psg/DeltaV_1431_WIOC_03_CSS. KB)   KB) Checksum:

Software Revision

14.3.1.7331

14.3.1.7331

14.3.1.7331

14.3.1.7331

276976B2EC7388C3B9D4BDCDEA8 276976B2EC7388C3B9 D4BDCDEA87AF85AB0C1AAD 7AF85AB0C1AAD234BB6025FD7B520416D6D 234BB6025FD7B520416D6D87 87

Page 6 of 56 

 

I/O

Software Revision

Download Link

Remote I/O Card Zone 1

Remote I/O Card Zone 2

https://gsuds.emerson.com/pickup/psg/DeltaV_1431_RIOZ1_01_CSS. https://gsuds.emerson.com/pickup/psg/DeltaV _1431_RIOZ1_01_CSS.zip: zip: (Size: 11893 KB)   KB) Checksum: DD361017C50BA367BDFD027EA48FE26 DD361017C50BA3 67BDFD027EA48FE26D7BFDACF396B04E D7BFDACF396B04E78E552B8E84CFBBF78 78E552B8E84CFBBF78 https://gsuds.emerson.com/pickup/psg/DeltaV_1431_RIOZ2_01_CSS. https://gsuds.emerson.com/pickup/psg/DeltaV _1431_RIOZ2_01_CSS.zip: zip: (Size: 11915 KB)   KB) Checksum:

14.3.1.7329

14.3.1.7330

F29017C446EEADA6DC1C5074E76BD F29017C446EEAD A6DC1C5074E76BD27A5825DDACCF3 27A5825DDACCF3011093DCB67F5923FAB0A 011093DCB67F5923FAB0A For information about Targeted Distribution, refer to Section 1. Section 1.   2. 2.6. 6.1 1

Resolved Resolved Issues for Targeted Targeted Distribu tion Bundle

2.6.1.1 2.6 .1.1 MD+ and SD+ Contr oll ers

The MD+ and SD+ Controller Targeted Distribution Bundle, DeltaV_1431_CTRL_P_05_CSS, addresses issues resolved in previous hotfix bundles and the following issues: Incident Number

TFSB132803

Descrip Descrip tion

Security hardening on embedded nodes maintenance port.

Re Reference ference KBA

Not Applicable NK-2000-0116: Redundant DO Series 2 Plus, 32Channel, 24V DC High-Side: Enabling Channel(s) followed by a Card Download may cause all the outputs to momentarily toggle from 1 to 0 

TFSB172725

Redundant DO Series 2 Plus, 32-Channel, 24V DC High-Side Enabling Channel(s) followed by a Card Download may cause all the outputs to momentarily toggle from 1 to 0.

TFSB190119

Cannot connect to Telnet service after TCP Timestamp Manipulation test in ISA testing.

Not Applicable

Controller redundancy can be lost following a Foundation Fieldbus download.

NK-2000-0586: Controller Redundancy Can Be Lost Following a Foundation Fieldbus Download 

TFSB477165

Controller encounters deadlock condition when downloading HART IO Channels.

NK-2100-0179: Controller Encounters Deadlock Condition When Downloading HART IO Channels 

TFSB487740

Unverified "cold_restart" commands on controllers.

Not Applicable

TFSB286933

MPC-PRO optimizer does not calculate optimal solution.

Not Applicable

TFSB177596

Virtual Controllers showing RedX intermittently on DeltaV Explorer and Diagnostics.

KBA NK-2100-0201 is being written to document this issue.

TFSB505864

 A status of “Bad -Configuration Error” in Diagnostics has rarely been seen on associated I/O cards causing Bad Function Block Status, mostly affecting High Density products.

NK-2100-0155: Getting "BAD - Configuration Error" Status for DeltaV I/O Cards in DeltaV Diagnostics 

TFSB453636

Page 7 of 56 

 

2.6.1.2 2.6 .1.2 MQ, MX, SQ, SQ, and SX Contr oll ers

The MQ, MX, SQ, and SX Controller Targeted Distribution Bundle, DeltaV_1431_CTRL_Q_06_CSS, addresses issues resolved in previous hotfix bundles and the following issues: Incident Number

TFSB132803

Descrip Descrip tion

Re Reference ference KBA

Security hardening on embedded nodes maintenance port.

Not Applicable

TFSB172725

Redundant DO Series 2 Plus, 32-Channel, 24V DC High-Side Enabling Channel(s) followed by a Card Download may cause all the outputs to momentarily toggle from 1 to 0.

NK-2000-0116: Redundant DO Series 2 Plus, 32Channel, 24V DC High-Side: Enabling Channel(s) followed by a Card Download may cause all the outputs to momentarily toggle from 1 to 0 

TFSB190119

Cannot connect to Telnet service after TCP Timestamp Manipulation test in ISA testing.

Not Applicable

QNX Controller Reset when Named Set Parameter Wired to External Reference to String IO DST.

NK-2000-0541: DeltaV Controller Reset When a Named Set Parameter Is Wired to External Reference to String IO DST  

TFSB446363

NK-2000-0586: Controller TFSB453636

Controller redundancy can be lost following a Foundation Fou ndation Fieldbus download.

Redundancy Can Be Lost Following a Foundation Fieldbus Download 

TRUNC function with a logarithmic parameter returns an inconsistent result depending on module assignment.

NK-2000-0722: LOG2 Function Can Return Incorrect Values When Used with Large Integers in Control Modules 

TFSB477165

Controller encounters deadlock condition when downloading HART IO Channels.

NK-2100-0179: Controller Encounters Deadlock Condition When Downloading HART IO Channels 

TFSB487740

Unverified "cold_restart" commands on controllers.

Not Applicable

TFSB492873

Internal/External/Dynamic Reference Parameter values infrequently Internal/External/Dynamic go off-scale high and could go up to 3.4e+38.

NK-2100-0156: Getting High Floating Value on Some Function Block Parameters of Control Modules Assigned to PK Controller  

TFSB286933

MPC-PRO optimizer does not calculate optimal solution.

Not Applicable

TFSB177596

Virtual Controllers showing RedX intermittently on DeltaV Explorer and Diagnostics.

KBA NK-2100-0201 is being written to document this issue.

TFSB505864

 A status of “Bad -Configuration Error” in Diagnostics has rarely been seen on associated I/O cards causing Bad Function Block Status, mostly affecting High Density products.

NK-2100-0155: Getting "BAD - Configuration Error" Status for DeltaV I/O Cards in DeltaV Diagnostics 

TFSB460801

Page 8 of 56 

 

2.6.1.3 SZ Controller

The SZ Controller Targeted Distribution Bundle, DeltaV_1431_CTRL_SZ_06_CSS, addresses issues resolved in previous hotfix bundles and the following issues: Incident Number

Descrip Descrip tion

Re Reference ference KBA

TFSB132803

Security hardening on embedded nodes maintenance port.

Not Applicable

TFSB190119

Cannot connect to Telnet service after TCP Timestamp Manipulation test in ISA testing.

Not Applicable

TFSB446363

QNX Controller Reset when Named Set Parameter Wired to External Reference to String IO DST.

NK-2000-0541: DeltaV Controller Reset When a Named Set Parameter Is Wired to External Reference to String IO DST  

TFSB453636

Controller redundancy can be lost following a Foundation Fou ndation Fieldbus download.

NK-2000-0586: Controller Redundancy Can Be Lost Following a Foundation Fieldbus Download 

TRUNC function with a logarithmic parameter returns an inconsistent result depending on module assignment.

NK-2000-0722: LOG2 Function Can Return Incorrect Values When Used with Large Integers in Control Modules 

TFSB477165

Controller encounters deadlock condition when downloading HART IO Channels.

NK-2100-0179: Controller Encounters Deadlock Condition When Downloading HART IO Channels 

TFSB487740

Unverified "cold_restart" commands on controllers.

Not Applicable

TFSB492873

Internal/External/Dynamic Reference Parameter values infrequently Internal/External/Dynamic go off-scale high and could go up to 3.4e+38.

NK-2100-0156: Getting High Floating Value on Some Function Block Parameters of Control Modules Assigned to PK Controller  

TFSB286933

MPC-PRO optimizer does not calculate optimal solution.

Not Applicable

TFSB460801

TFSB177596

Virtual Controllers showing RedX intermittently on DeltaV Explorer and Diagnostics.

KBA NK-2100-0201 is being written to document this issue.

2.6.1.4 PK Controllers

The PK Controller Targeted Distribution Bundle, DeltaV_1431_CTRL_PK_09_CSS, DeltaV_1431_CTRL_PK_09_CSS, addresses issues resolved in previous hotfix bundles and the following issues: Incident Number

TFSB132803

Descrip Descrip tion

Security hardening on embedded nodes maintenance port.

Re Reference ference KBA

Not Applicable

Page 9 of 56 

 

Incident Number

Descrip Descrip tion

Re Reference ference KBA

TFSB172725

Redundant DO Series 2 Plus, 32-Channel, 24V DC High-Side Enabling Channel(s) followed by a Card Download may cause all the outputs to momentarily toggle from 1 to 0.

NK-2000-0116: Redundant DO Series 2 Plus, 32Channel, 24V DC High-Side: Enabling Channel(s) followed by a Card Download may cause all the outputs to momentarily toggle from 1 to 0 

TFSB190119

Cannot connect to Telnet service after TCP Timestamp Manipulation test in ISA testing.

Not Applicable

QNX Controller Reset when Named Set Parameter Wired to External Reference to String IO DST.

NK-2000-0541: DeltaV Controller Reset When a Named Set Parameter Is Wired to External Reference to String IO DST  

Controller redundancy can be lost following a Foundation Fou ndation Fieldbus download.

NK-2000-0586: Controller Redundancy Can Be Lost Following a Foundation Fieldbus Download 

TFSB446363

TFSB453636

TFSB460801

TRUNC function with a logarithmic parameter returns an inconsistent result depending on module assignment.

NK-2000-0722: LOG2 Function Can Return Incorrect Values When Used with Large Integers in Control Modules 

TFSB477165

Controller encounters deadlock condition when downloading HART IO Channels.

NK-2100-0179: Controller Encounters Deadlock Condition When Downloading HART IO Channels 

TFSB487740

Unverified "cold_restart" commands on controllers.

Not Applicable

TFSB492873

Internal/External/Dynamic Reference Parameter values infrequently Internal/External/Dynamic go off-scale high and could go up to 3.4e+38.

NK-2100-0156: Getting High Floating Value on Some Function Block Parameters of Control Modules Assigned to PK Controller  

TFSB286933

MPC-PRO optimizer does not calculate optimal solution.

TFSB466198

PK controller doesn't perform a Local Download after a power failure when Cold Restart is configured for Always Enabled if the PK was powered down for more than 31 days.

TFSB177596

Virtual Controllers showing RedX intermittently on DeltaV Explorer and Diagnostics.

TFSB505864

 A status of “Bad -Configuration Error” in Diagnostics has rarely been seen on associated I/O cards causing Bad Function Block Status,

mostly affecting High Density products.

Not Applicable NK-2000-0742: PK Controller Does Not Perform a Local Download after Being Powered down for More Than 31 Days Even When Cold Restart Is Configured as  Always Enabled   KBA NK-2100-0201 is being written to document this issue. NK-2100-0155: Getting "BAD - Configuration Error" Status for DeltaV I/O Cards in DeltaV Diagnostics 

Page 10 of 56 

 

2.6.1.5 2.6 .1.5 Work stati on and Batch

The Workstation and Batch Targeted Distribution Bundle, DeltaV_1431_WS_21_CSS, addresses issues resolved in previous hotfix bundles and the following issues: Note: This bundle includes DeltaV Data Collector software version DDC_5110. The DDC software is located in the DeltaV\DVData folder. For more information refer to KBA KBA  NK-1100-1172: DeltaV Data Collector Utility Quick Start Installation and Usage Guide .  Incident Number  

TFSB285737 (Batch)

TFSB146287

Description  

Reference KBA  

Verify Recipe does not detect a carriage return or if the maximum number of characters in the description field is exceeded.

KBA NK-2100-0319 is being written to document this issue.

DeltaV OPC UA does not recognize aliases in the nodeset xml.

KBA NK-2100-0318 is being written to document this issue.

Batch prompts timeout enhancement. Note:  After hotfix installation, installation, please see the following Books Online sections for instructions on use of the new functionality: Batch Executive action confirmation, Phase request codes. In DeltaV Explorer Help, see the help section: Batch Executive Properties dialog (Action

TFSB281808

Not Applicable

Confirmation tab). TFSBB471914

WinUpgrade enhancements.

Not Applicable

TFSBB475820 (Batch)

The DeltaV Database Server may terminate and corrupt the database when downloading a Unit if a re-assigned phase is referenced by a Control Module Function Block Expression.

KBA NK-2100-0320 is being written to document this issue.

TFSB478602/ TFS395478

 A Database Internal Internal Error occurs when attempting to set a DeviceNet device revision when signals are configured.

KBA NK-2100-0321 is being written to document this issue.

2.6.1.6 CHARM I/O Card

The CHARM I/O Card Targeted Distribution Bundle, DeltaV_1431_CIOC_03_CSS, addresses issues resolved in previous hotfix bundles and the following issues: Incident Number

Descrip Descrip tion

Re Reference ference KBA

TFSB132803

Security hardening on embedded nodes maintenance port.

Not Applicable

TFSB190119

Cannot connect to Telnet service after TCP Timestamp Manipulation test in ISA testing.

Not Applicable

TFSB487740

Unverified "cold_restart" commands on controllers.

Not Applicable

TFSB177596

Virtual Controllers showing RedX intermittently on DeltaV Explorer and Diagnostics.

KBA NK-2100-0201 is being written to document this issue.

2.6.1.7 CHARM I/O Card 2

The CHARM I/O Card 2 Targeted Distribution Bundle, DeltaV_1431_CIOC2_03_CS DeltaV_1431_CIOC2_03_CSS, S, addresses issues resolved in previous hotfix bundles and the following issues:

Page 11 of 56 

 

Incident Number

Descrip Descrip tion

Re Reference ference KBA

TFSB132803

Security hardening on embedded nodes maintenance port.

Not Applicable

TFSB190119

Cannot connect to Telnet service after TCP Timestamp Manipulation test in ISA testing.

Not Applicable

TFSB487740

Unverified "cold_restart" commands on controllers.

Not Applicable

TFSB177596

Virtual Controllers showing RedX intermittently on DeltaV Explorer and Diagnostics.

KBA NK-2100-0201 is being written to document this issue.

2.6.1.8 2.6 .1.8 Ethernet I/O Card Card

The Ethernet I/O Card Targeted Distribution Bundle, DeltaV_1431_EIOC_09_CSS, addresses issues resolved in previous hotfix bundles and the following issues: Incident Number

Descrip Descrip tion

Re Reference ference KBA

TFSB132803

Security hardening on embedded nodes maintenance port.

Not Applicable

TFSB190119

Cannot connect to Telnet service after TCP Timestamp Manipulation test in ISA testing.

Not Applicable NK-2000-0722: LOG2 Function Can Return

TFSB460801

TRUNC function with a logarithmic parameter returns an inconsistent result depending on module assignment.

TFSB487740

Unverified "cold_restart" commands on controllers.

Not Applicable

TFSB492873

Internal/External/Dynamic Reference Parameter values Internal/External/Dynamic val ues infrequently go off-scale high and could go up to 3.4e+38.

NK-2100-0156: Getting High Floating Value on Some Function Block Parameters of Control Modules Assigned to PK Controller  

TFSB177596

Virtual Controllers showing RedX intermittently on DeltaV Explorer and Diagnostics.

KBA NK-2100-0201 is being written to document this issue.

Incorrect When Used with LargeValues Integers in Control Modules 

2.6.1.9 2.6 .1.9 Wireless I/O Card Card

The Wireless I/O Card Targeted Distribution Bundle, DeltaV_1431_WIOC_03_CSS, DeltaV_1431_WIOC_03_CSS, addresses issues resolved in previous hotfix bundles and the following issues: Incident Number

Descrip Descrip tion

Re Reference ference KBA

TFSB132803

Security hardening on embedded nodes maintenance port.

Not Applicable

TFSB190119

Cannot connect to Telnet service after TCP Timestamp Manipulation test in ISA testing.

Not Applicable

TFSB487740

Unverified "cold_restart" commands on controllers.

Not Applicable

TFSB177596

Virtual Controllers showing RedX intermittently on DeltaV Explorer and Diagnostics.

KBA NK-2100-0201 is being written to document this issue.

Page 12 of 56 

 

2.6.1.10 2.6.1.1 0 Remot e I/O Card Zon Zon e 1

The Remote I/O Card Zone 1Targeted Distribution Bundle, DeltaV_1431_RIOZ1_01_CSS, addresses the following issues: Incident Number

Descrip Descrip tion

TFSB190119

Cannot connect to Telnet service after TCP Timestamp Manipulation test in ISA testing. Virtual Controllers showing RedX intermittently on DeltaV Explorer

TFSB177596

and Diagnostics.

TFSB234443

RIO Scanner Switchover has the potential to cause cards in Slot 1 to stop responding 5 to 10% of the time.

Re Reference ference KBA

Not Applicable KBA NK-2100-0201 is being written to document this issue. NK-2000-0542: Controller Switchover Can Causes Bus Cards In SLOT1 to Fail  

2.6.1.11 2.6.1.1 1 Remot e I/O Card Zon Zon e 2

The Remote I/O Card Zone 2 Targeted Distribution Bundle, DeltaV_1431_RIOZ2_01_CSS, addresses the following issues: Incident Number

Descrip Descrip tion

Re Reference ference KBA

TFSB190119

Cannot connect to Telnet service after TCP Timestamp Manipulation test in ISA testing.

Not Applicable

TFSB487740

Unverified "cold_restart" commands on controllers.

Not Applicable

TFSB177596

Virtual Controllers showing RedX intermittently on DeltaV Explorer and Diagnostics.

KBA NK-2100-0201 is being written to document this issue.



Resolved Issues

3.1

Controller

3.1.1

MD+ and SD+

To download the General Maintenance Distribution MD+ and SD+ controller hotfix bundle, go to Section Section 2.1.  2.1.   The General Maintenance Distribution MD+ and SD+ Controller Hotfix Bundle DeltaV_1431_CTRL_P_04_CSS, reflects version 14.3.1.7313 in DeltaV Diagnostics. This hotfix bundle addresses the following issues: Incident Number

TFSB300885

Descrip Descrip tion

 Analog Tracking function block no longer responds to interlock conditions after controller switchover

Re Reference ference KBA

NK-2000-0558: Analog Tracking Function Block No Longer Responds to Interlock Conditions after Controller Switchover  

Page 13 of 56 

 

Incident Number

Descrip Descrip tion

Re Reference ference KBA

 Analog Tracking and Discrete Discrete Control Condition blocks gene generated rated Event Chronicle entries report the Composite not the Module

NK-2000-0626: Analog Tracking and Discrete Control Condition Blocks' Generated Event Chronicle Entries Report the Composite Not the Module 

Changing a namedset assigned to condition on DCC block is not reflected in CS online

NK-2000-0139: Changing a Named Set Assigned to a Condition on a DCC Block is not Reflected in Control Studio Online 

TFSB163681

PSOS controller resets or crashes when bypassing a LSAVTR function block with a DESCx of more than 40 characters

NK-1900-0006: SZ Controllers May Lose Configuration or pSOS Controller Resets if the DESCx Field of the Advanced Function Blocks Has More Than 40 Characters  

TFSB234443

Controller switchover causes Profibus DP card in slot 1 to fail 5 to 10% of the time

NK-2000-0542: Controller Switchover Can Causes Bus Cards In SLOT1 to Fail  

TFSB183109

TFSB174704

3.1.1.1 3.1 .1.1 Previou s MD MD+ + and SD+ SD+ Cont rol ler Hotfix Bu ndl es

The following hotfixes have been superseded by DeltaV_1431_CTRL_P_04_CSS: 3.1.1.1.1

DeltaV_1431_CTRL_P_03_CSS

Controllers flashed with DeltaV_1431_CTRL_P_03_CSS reflect version 14.3.1.7304 in DeltaV Diagnostics. This hotfix bundle addressed the following issues: Incident Number

TFSB118967

Descrip Descrip tion

Download can fail after an upload followed by download

Re Reference ference KBA

NK-1900-0825: Download of PK, MQ, MX, SX, SQ, and SZ Controllers May Fail When the Download Starts at the Same Time as the Upload Completes 

 Analog Outputs of CHARMs CHARMs unexpectedly unexpectedly change after enabling HART followed by a download when XD_SCALE of the function TFSB124417 block (0-100 no units) and the scale (4-20mA) of HART device are mismatched

TFSB138281

Unresolved references are evaluated as true when wired to discrete inputs even when the value is #IGNORE

 AK-1900-0005: Analog Outputs of CHARMs may Unexpectedly Change after Enabling HART followed by a Download  NK-1900-1017: Unresolved References are Evaluated as True When Wired into Discrete Inputs Even if the Reference Value is #IGNORE  

Page 14 of 56 

 

Incident Number

TFSB176767

TFSB94445

TFSB139817

TFSB154270

TFSB143825

TFSB143955

3.1.1.1.2

Descrip Descrip tion

Re Reference ference KBA

EDC Block - Control Studio Online - IGNORE_PV_ACT parameter does not track IGNORE_PV correctly

NK-2000-0427: EDC Block's IGNORE_PV_ACT Parameter is Not Tracking IGNORE_PV Correctly in Control Studio Online 

Enhanced Control Selector OP_SELECTION name set change does not propagate on download

NK-1900-0718: Partial Download Does Not Update OP_SELECTION Parameter Configured Name Set on Enhanced Control Selector Function Block  

PID function block - TR14.3.1L - PV filter does not initialize i nitialize during a simulate restore

NK-2000-0120: Known Issues in Save/Restore to XML-format on v14.3 and v14.LTS DeltaV SimulatePro 

PID function blocks - TR14.3.1L - PV filter is incorrectly executing even when PID block is in Out Of Service mode

NK-2000-0120: Known Issues in Save/Restore to XML-format on v14.3 and v14.LTS DeltaV SimulatePro 

Simulate – XML save/restore does not work for conditional alarm

NK-2000-0120: Known Issues in Save/Restore to

parameters

XML-format on v14.3 and v14.LTS DeltaV SimulatePro 

Simulate – Temporary variables in expressions are not n ot saved and restored during XML operations but are during DAT operations

NK-2000-0120: Known Issues in Save/Restore to XML-format on v14.3 and v14.LTS DeltaV SimulatePro 

DeltaV_1431_CTRL_P_02_CSS

Controllers flashed with DeltaV_1431_CTRL_P_02_CSS reflect version 14.3.1.7291 in DeltaV Diagnostics. This hotfix bundle addressed the following issues: Incident Number

TFSB97679

TFSB134779

TFSB112281

Descrip Descrip tion

Re Reference ference KBA

EDC function block's status (CMD_D and OUT_D) bumps to zero for one scan after a controller switchover

NK-1900-0544: Enhanced Device Control Function Block Parameters Bumps to Zero One Scan after a Controller Switchover  

Controllers can lose communications to other nodes due to a deadlock condition

NK-1900-1052: Controllers May lose Communications to Other Nodes Due to a Deadlock Condition  

Controller resets when running batch phases simultaneously

NK-1900-1035: Controller Resets When Running Batch Phases Simultaneously 

Page 15 of 56 

 

3.1.2 3.1 .2

MQ, MX, SQ, and SX Cont rol lers

To download the General Maintenance Distribution MQ, MX, SQ, and SX controller hotfix bundle, go to Section Section 2.1.  2.1.   The General Maintenance Distribution MQ, MX, SQ, and SX Controller Hotfix Bundle DeltaV_1431_CTRL_Q_05_CSS, reflects version 14.3.1.7313 in DeltaV Diagnostics. This hotfix bundle addresses the following issues: Incident Number

Descrip Descrip tion

Re Reference ference KBA

NK-2000-0558: Analog TFSB300885

TFSB183109

TFSB174704

TFSB234443

 Analog Tracking function block no longer responds to interlock conditions after controller switchover

 Analog Tracking and Discrete Discrete Control Condition blocks gene generated rated Event Chronicle entries report the Composite not the Module

Changing a namedset assigned to condition on DCC block is not reflected in CS online

Controller switchover causes Profibus DP card in slot 1 to fail 5 to 10% of the time

Tracking Function Block No Longer Responds to Interlock Conditions after Controller Switchover  

NK-2000-0626: Analog Tracking and Discrete Control Condition Blocks' Generated Event Chronicle Entries Report the Composite Not the Module  NK-2000-0139: Changing a Named Set Assigned to a Condition on a DCC Block is not Reflected in Control Studio Online  NK-2000-0542: Controller Switchover Can Causes Bus Cards In SLOT1 to Fail  

3.1.2.1 3.1 .2.1 Previou s MQ, MX, SQ, and SX Contr oll er Hotfix Bu ndl es

The following hotfixes have been superseded by DeltaV_1431_CTRL_Q_05_CSS: 3.1.2.1.1

DeltaV_1431_CTRL_Q_04_CSS

Controllers flashed with DeltaV_1431_CTRL_Q_04_CSS reflect version 14.3.1.7304 in DeltaV Diagnostics. This hotfix bundle addressed the following issues: Incident Number

TFSB118967

Descrip Descrip tion

Download can fail after an upload followed by download

 Analog Outputs of CHARMs CHARMs unexpectedly unexpectedly change after enabling HART followed by a download when XD_SCALE of the function TFSB124417 block (0-100 no units) and the scale (4-20mA) of HART device are mismatched

Re Reference ference KBA

NK-1900-0825: Download of PK, MQ, MX, SX, SQ, and SZ Controllers May Fail When the Download Starts at the Same Time as the Upload Completes   AK-1900-0005: Analog Outputs of CHARMs may Unexpectedly Change after Enabling HART followed by a Download 

Page 16 of 56 

 

Incident Number

TFSB138281

Descrip Descrip tion

Re Reference ference KBA

Unresolved references are evaluated as true when wired to discrete inputs even when the value is #IGNORE

NK-1900-1017: Unresolved References are Evaluated as True When Wired into Discrete Inputs Even if the Reference Value is #IGNORE  

EDC Block - Control Studio Online - IGNORE_PV_ACT parameter TFSB176767

TFSB94445

TFSB139817

does not track IGNORE_PV correctly

NK-2000-0427: EDC Block's IGNORE_PV_ACT Parameter is Not Tracking IGNORE_PV Correctly in Control Studio Online 

Enhanced Control Selector OP_SELECTION name set change does not propagate on download

NK-1900-0718: Partial Download Does Not Update OP_SELECTION Parameter Configured Name Set on Enhanced Control Selector Function Block  

PID function block - TR14.3.1L - PV filter does not initialize i nitialize during a simulate restore

NK-2000-0120: Known Issues in Save/Restore to XML-format on v14.3 and v14.LTS DeltaV SimulatePro  NK-2000-0120: Known

TFSB154270

TFSB143825

TFSB143955

3.1.2.1.2

PID function blocks - TR14.3.1L - PV filter is incorrectly executing even when PID block is in Out Of Service mode

Issues in Save/Restore to XML-format on v14.3 and v14.LTS DeltaV SimulatePro 

Simulate – XML save/restore does not work for conditional alarm parameters

NK-2000-0120: Known Issues in Save/Restore to XML-format on v14.3 and v14.LTS DeltaV SimulatePro 

Simulate – Temporary variables in expressions are not n ot saved and restored during XML operations but are during DAT operations

NK-2000-0120: Known Issues in Save/Restore to XML-format on v14.3 and v14.LTS DeltaV SimulatePro 

DeltaV_1431_CTRL_Q_03_CSS

Controllers flashedthe with DeltaV_1431_CTRL_Q_03_CSS reflect version 14.3.1.7291 in DeltaV Diagnostics. This hotfix bundle addressed following issues: Incident Number

TFSB97679

TFSB134779

Descrip Descrip tion

Re Reference ference KBA

EDC function block's status (CMD_D and OUT_D) bumps to zero for one scan after a controller switchover

NK-1900-0544: Enhanced Device Control Function Block Parameters Bumps to Zero One Scan after a Controller Switchover  

Controllers can lose communications to other nodes due to a deadlock condition

NK-1900-1052: Controllers May lose Communications to Other Nodes Due to a Deadlock Condition  

Page 17 of 56 

 

Incident Number

Descrip Descrip tion

TFSB112281

3.1.2.1.3

Controller resets when running batch phases simultaneously

Re Reference ference KBA

NK-1900-1035: Controller Resets When Running Batch Phases Simultaneously 

DeltaV_1431_CTRL_Q_02_CSS

Controllers flashed with DeltaV_1431_CTRL_Q_02_CSS reflect version 14.3.1.7289 in DeltaV Diagnostics. This hotfix bundle addressed the following issues: Incident Number

TFS440185

3.1.3 3.1 .3

Descrip Descrip tion

Controller can briefly lose connection to other nodes on o n the system when many CIOCs are assigned

Re Reference ference KBA

NK-1900-1006: Controller Can Briefly Lose Connection to Other Nodes on the System when Many CIOCs  Are Assigned  

SZ Contr oll ers

To download the General Maintenance Distribution SZ controller hotfix bundle, go to Section 2.1. Section 2.1.   The General Maintenance Distribution SZ Controller Hotfix Bundle DeltaV_1431_CTRL_SZ_05_CSS, reflects version 14.3.1.7313 in DeltaV Diagnostics. This hotfix bundle addresses the following issues: Incident Number

TFSB300885

TFSB183109

TFSB174704

Descrip Descrip tion

 Analog Tracking function block no longer responds to interlock conditions after controller switchover

 Analog Tracking and Discrete Discrete Control Condition blocks generated Event Chronicle entries report the Composite not the Module

Changing a namedset assigned to condition on DCC block is not reflected in CS online

Re Reference ference KBA

NK-2000-0558: Analog Tracking Function Block No Longer Responds to Interlock Conditions after Controller Switchover   NK-2000-0626: Analog Tracking and Discrete Control Condition Blocks' Generated Event Chronicle Entries Report the Composite Not the Module  NK-2000-0139: Changing a Named Set Assigned to a Condition on a DCC Block is not Reflected in Control Studio Online 

3. 3.1. 1.3.1 3.1 Previous SZ Controll er Hotfix Bundles

The following hotfixes have been superseded by DeltaV_1431_CTRL_SZ_05_CSS: DeltaV_1431_CTRL_SZ_05_CSS: 3.1.3.1.1

DeltaV_1431_CTRL_SZ_04_CSS

Controllers flashed with DeltaV_1431_CTRL_SZ_04_CSS reflect version 14.3.1.7304 in DeltaV Diagnostics. This hotfix bundle addressed the following issues:

Page 18 of 56 

 

Incident Number

TFSB118967

Descrip Descrip tion

Download can fail after an upload followed by download

 Analog Outputs of CHARMs CHARMs unexpectedly unexpectedly change after enabling TFSB124417

TFSB138281

TFSB176767

TFSB94445

TFSB139817

TFSB154270

TFSB143825

TFSB143955

3.1.3.1.2

Re Reference ference KBA

NK-1900-0825: Download of PK, MQ, MX, SX, SQ, and SZ Controllers May Fail When the Download Starts at the Same Time as the Upload Completes   AK-1900-0005: Analog

HART followed by a download when XD_SCALE of the function block (0-100 no units) and the scale (4-20mA) of HART device are mismatched

Outputs of CHARMs may Unexpectedly Change after Enabling HART followed by a Download 

Unresolved references are evaluated as true when wired to discrete inputs even when the value is #IGNORE

NK-1900-1017: Unresolved References are Evaluated as True When Wired into Discrete Inputs Even if the Reference Value is #IGNORE  

EDC Block - Control Studio Online - IGNORE_PV_ACT parameter does not track IGNORE_PV correctly

NK-2000-0427: EDC Block's IGNORE_PV_ACT Parameter is Not Tracking IGNORE_PV Correctly in Control Studio Online 

Enhanced Control Selector OP_SELECTION name set change does not propagate on download

NK-1900-0718: Partial Download Does Not Update OP_SELECTION Parameter Configured Name Set on Enhanced Control Selector Function Block  

PID function block - TR14.3.1L - PV filter does not initialize i nitialize during a simulate restore

NK-2000-0120: Known Issues in Save/Restore to XML-format on v14.3 and v14.LTS DeltaV SimulatePro 

PID function blocks - TR14.3.1L - PV filter is incorrectly executing even when PID block is in Out Of Service mode

NK-2000-0120: Known Issues in Save/Restore to XML-format on v14.3 and v14.LTS DeltaV SimulatePro 

Simulate – XML save/restore does not work for conditional alarm parameters

NK-2000-0120: Known Issues in Save/Restore to XML-format on v14.3 and v14.LTS DeltaV SimulatePro 

Simulate – Temporary variables in expressions are not n ot saved and restored during XML operations but are during DAT operations

NK-2000-0120: Known Issues in Save/Restore to XML-format on v14.3 and v14.LTS DeltaV SimulatePro 

DeltaV_1431_CTRL_SZ_03_CSS

Controllers flashed with DeltaV_1431_CTRL_SZ_03_CSS reflect version 14.3.1.7292 in DeltaV Diagnostics. This hotfix bundle addressed the following issues:

Page 19 of 56 

 

Incident Number

Descrip Descrip tion

TFSB139782

TFSB97679

14.3.1 hotfix release of Distributed Charms for the CSLS

EDC function block's status (CMD_D and OUT_D) bumps to zero for one scan after a controller switchover

Re Reference ference KBA

NK-2000-0052: DeltaV Distributed CHARMs for CSLS Software Release Information   NK-1900-0544: Enhanced Device Control Function Block Parameters Bumps to Zero One Scan after a  Controller Switchover 

TFSB134779

TFSB112281

3.1.3.1.3

Controllers can lose communications to other nodes due to a deadlock condition

NK-1900-1052: Controllers May lose Communications to Other Nodes Due to a Deadlock Condition  

Controller resets when running batch phases simultaneously

NK-1900-1035: Controller Resets When Running Batch Phases Simultaneously 

DeltaV_1431_CTRL_SZ_02_CSS

Controllers flashed with DeltaV_1431_CTRL_SZ_02_CSS reflect version 14.3.1.7289 in DeltaV Diagnostics. This hotfix bundle addressed the following issues: Incident Number

TFS440185

3.1.4 3.1 .4

Descrip Descrip tion

Controller can briefly lose connection to other nodes on o n the system when many CIOCs are assigned

Re Reference ference KBA

NK-1900-1006: Controller Can Briefly Lose Connection to Other Nodes on the System when Many CIOCs  Are Assigned  

PK Contr oll ers

To download the General Maintenance Distribution PK controller hotfix bundle, go to Section 2.1. Section 2.1.   The General Maintenance Distribution PK Controller Hotfix Bundle DeltaV_1431_CTRL_PK_08_CSS, reflects version 14.3.1.7313 in DeltaV Diagnostics. This hotfix bundle addresses the following issues: Incident Number

TFSB300885

Descrip Descrip tion

 Analog Tracking function block no longer responds to interlock conditions after controller switchover

EIOC/PK:: Performing downloads results in EIOC reporting alarm EIOC/PK TFSB180946  ADVISE_ALM=  ADVISE_ALM= Redundancy: Not Communicating – Secondary Network

Re Reference ference KBA

NK-2000-0558: Analog Tracking Function Block No Longer Responds to Interlock Conditions after Controller Switchover   NK-1900-1133: Downloads of Other Nodes via DeltaV Explorer Might Trigger the EIOC/PK/SZ Controller to Log the Alarm "Redundancy: Not Communicating – Communicating –   Secondary Network" for 10 Seconds 

Page 20 of 56 

 

Incident Number

Descrip Descrip tion

Re Reference ference KBA

TFSB182611

EIOC/PK Controller Controller / All Ethernet/IP Messaging Classes / Redundant: PDTs with either Primary or Secondary Device Network cable removed may results with all its LDTs with permanent BAD OInteg / Signal Data in CS Online until both b oth Networks are reconnected

NK-2000-0651: PDTs With Redundant Communications May Result To All LDTs With Permanent BAD OInteg and Signal Data In Control Studio With BAD Status   NK-2000-0626: Analog

TFSB183109

 Analog Tracking and Discrete Discrete Control Condition blocks gene generated rated Event Chronicle entries report the Composite not the Module

Tracking Discrete Control Conditionand Blocks' Generated Event Chronicle Entries Report the Composite Not the Module 

TFSB174704

Changing a namedset assigned to condition on DCC block is not reflected in CS online

NK-2000-0139: Changing a Named Set Assigned to a Condition on a DCC Block is not Reflected in Control Studio Online 

TFSB234443

Controller switchover causes Profibus DP card in slot 1 to fail 5 to 10% of the time

NK-2000-0542: Controller Switchover Can Causes Bus Cards In SLOT1 to Fail  

3. 3.1. 1.4.1 4.1 Previous PK Controll er Hotfix Bundles The following hotfixes have been superseded by DeltaV_1431_CTRL_PK_08_C DeltaV_1431_CTRL_PK_08_CSS: SS:

3.1.4.1.1

DeltaV_1431_PK_07_CSS

Controllers flashed with DeltaV_1431_PK_07_CSS reflect version 14.3.1.7304 in DeltaV Diagnostics. This hotfix bundle addressed the following issues: Incident Number

TFSB118967

Descrip Descrip tion

Download can fail after an upload followed by download

Re Reference ference KBA

NK-1900-0825: Download of PK, MQ, MX, SX, SQ, and SZ Controllers May Fail When the Download Starts at the Same Time as the Upload Completes 

 Analog Outputs of CHARMs CHARMs unexpectedly unexpectedly change after enabling HART followed by a download when XD_SCALE of the function TFSB124417 block (0-100 no units) and the scale (4-20mA) of HART device are mismatched

TFSB138281

Unresolved references are evaluated as true when wired to discrete inputs even when the value is #IGNORE

 AK-1900-0005: Analog Outputs of CHARMs may Unexpectedly Change after Enabling HART followed by a Download  NK-1900-1017: Unresolved References are Evaluated as True When Wired into Discrete Inputs Even if the Reference Value is #IGNORE  

Page 21 of 56 

 

Incident Number

TFSB176767

Descrip Descrip tion

EDC Block - Control Studio Online - IGNORE_PV_ACT parameter does not track IGNORE_PV correctly

Redundancy statistics in Runtime Recorder for PK controller TFSB140001

displays inaccurate data

Re Reference ference KBA

NK-2000-0427: EDC Block's IGNORE_PV_ACT Parameter is Not Tracking IGNORE_PV Correctly in Control Studio Online  NK-2000-0432: DeltaV PK Controller Redundancy Statistics Runtime Recorder in Displays Inaccurate Data 

PK and EIOC lose connection to Class 1 Ethernet device when RPI is changed

NK-2000-0133: PK Controllers and Ethernet I/O Cards Lose Connection to Class 1 Ethernet Devices When RPI is Changed 

TFSB94445

Enhanced Control Selector OP_SELECTION name set change does not propagate on download

NK-1900-0718: Partial Download Does Not Update OP_SELECTION Parameter Configured Name Set on Enhanced Control Selector Function Block  

TFSB139817

PID function block - TR14.3.1L - PV filter does not initialize i nitialize during a simulate restore

NK-2000-0120: Known Issues in Save/Restore to XML-format on v14.3 and v14.LTS DeltaV SimulatePro 

TFSB154270

PID function blocks - TR14.3.1L - PV filter is incorrectly executing even when PID block is in Out Of Service mode

NK-2000-0120: Known Issues in Save/Restore to XML-format on v14.3 and v14.LTS DeltaV SimulatePro 

TFSB143825

Simulate – XML save/restore does not work for conditional alarm parameters

NK-2000-0120: Known Issues in Save/Restore to XML-format on v14.3 and v14.LTS DeltaV SimulatePro 

TFSB143955

Simulate – Temporary variables in expressions are not n ot saved and restored during XML operations but are during DAT operations

NK-2000-0120: Known Issues in Save/Restore to XML-format on v14.3 and v14.LTS DeltaV SimulatePro 

TFSB131251

3.1.4.1.2

DeltaV_1431_PK_06_CSS

Controllers flashed with DeltaV_1431_PK_06_CSS reflect version 14.3.1.7291 in DeltaV Diagnostics. This hotfix bundle addressed the following issues: Incident Number

TFSB91137

Descrip Descrip tion

Output bump for 1 module scan due to Modbus TCP\IP - Buffered Write

Re Reference ference KBA

NK-1900-1004: Modbus TCP Write on Device Reconnection with EIOC or PK Controllers 

Page 22 of 56 

 

Incident Number

TFSB97679

TFSB134779

TFSB112281

Descrip Descrip tion

EDC function block's status (CMD_D and OUT_D) bumps to zero for one scan after a controller switchover

Re Reference ference KBA

NK-1900-0544: Enhanced Device Control Function Block Parameters Bumps to Zero One Scan after a Controller Switchover  

Controllers can lose communications to other nodes due to a

NK-1900-1052: Controllers May lose Communications to

deadlock condition

Other Nodes Due to  a Deadlock Condition

Controller resets when running batch phases simultaneously

NK-1900-1035: Controller Resets When Running Batch Phases Simultaneously 

3.1.4.1.3

DeltaV_1431_PK_05_CSS

Controllers flashed with DeltaV_1431_PK_05_CSS reflect version 14.3.1.7289 in DeltaV Diagnostics. This hotfix bundle addressed the following issues: Incident Number

TFS440185

Descrip Descrip tion

Controller can briefly lose connection to other nodes on o n the system when many CIOCs are assigned

3.2 3. 2

Workstation and Batch

3. 3.2. 2.1 1

Workstation and Batch Hotfix Bundle

Re Reference ference KBA

NK-1900-1006: Controller Can Briefly Lose Connection to Other Nodes on the System when Many CIOCs  Are Assigned  

3. 3.2. 2.1.1 1.1 Ge General neral Ma Maintenance intenance Distribut ion Workst ation Hotfix

To download the General Maintenance Distribution Workstation and Batch Hotfix Bundle, go to Section 2.2. Section 2.2.   The latest hotfix bundle, DeltaV_1431_WS_20_CSS, addresses the following issues: Note: This bundle includes DeltaV Data Collector software version DDC_5110. The DDC software is located

in the DeltaV\DVData For more information refer to KBA KBA  NK-1100-1172: DeltaV Data Collector Utility Quick Start Installationfolder. and Usage Guide .  Incident Number

De Descrip scrip tion

Re Reference ference KBA

TFSB91222/ TFS421253

KBA NK-2100-0266 is being In PredictPro, the Create Model and Verify against original data does written to document this not read data correctly when the data source is a text file. issue.

TFSB164402

Alarm Summary Filters cannot be set by Area in DeltaV Live.

Not Applicable

Page 23 of 56 

 

TFSB183258

NK-2000-0675: DeltaV Process History View The Process History View application is closed and disappears from Disappears from the Task the “Bring to Front” taskbar when Process History View is launched Bar/Bring to Front List When again from the DeltaV Operate toolbar while the application is Relaunched from the minimized. Operate Toolbar While  Application Is Minimized  

TFSB184805

Event Chronicle active dataset may run out of space sp ace due to index fragmentation.

NK-2000-0387: SQL Server 2016 Event Chronicle Active Dataset Runs Out of Space Due to Index Fragmentation  

TFSB455403

SIS Alarm Group data displayed in DeltaV Operate pictures and DeltaV Live displays may be incorrect or have bad status on some Operator Stations.

NK-2100-0205: PRODUCT SAFETY CONCERN: Process Systems and Solutions -- DeltaV Live and DeltaV Operate Show Incorrect Value on Datalinks or Animations When Referencing SIS Module Parameters Utilizing Alarm Group Name 

TFSB479982

Renaming a Display or updating Module Properties causes Primary Control Displays to fail to launch in DeltaV Live.

Not Applicable

TFSB483028

DeltaV Live throws errors after multiple days of constant use.

Not Applicable

TFSB489021

DeltaV Live backups do not notify user when target directory is full.

Not Applicable

TFSB498251

Updates to Open-Source utilities.

Not Applicable

TFSB505218

DeltaV Live throws errors when launched automatically at logon.

Not Applicable

TFSB505864

 A status of “Bad -Configuration Error” may be seen in Diagnostics for a 32-Channel DO card.

NK-2100-0155: Getting "BAD - Configuration Error" Status for DeltaV I/O Cards in DeltaV Diagnostics 

TFSB507185

DeltaV Live does not properly capture hardware disconnects.

Not Applicable

TFSB509696

DeltaV Live now supports storing high quality images and video while using minimal bandwidth.

Not Applicable

TFSB510308

DeltaV Live performance degrades when using .NUM field.

Not Applicable

TFSB513307

DeltaV Live numeric data links sometimes read NaN.

Not Applicable

TFSB514901/ TFS43833

NK-2100-0154: Values In “Message” Column of Deactivated/Inactive, The DeltaV Operate and DeltaV Live Alarm Summary Control’s %P1 Unacknowledged Alarm In and %P2 values are not updated with their current values val ues when an DeltaV Alarm Summary inactive/unacknowledged alarm is triggered again. Control Do Not Get Updated  After Alarm Is Triggered  Again 

Page 24 of 56 

 

3.2.1.2 DeltaV_1431_TFSB158919_BHServer

Standalone hotfix, DeltaV_1431_TFSB158919_BHServer, addressed the following issue: Incident Number

Descrip Descrip tion

Reference Reference KBA

TFS327311 

The DVHisDBInstallVersion Table of the DVHisDB and archive databases shows VV.VV.VV instead of 13.3.1 or v14.3.1

TFS348017 

DVHisUser and DVHisAdmin DVHisAdmin accounts are not created on SQL Logins and on the Users and Schemas of the DVHisDB and archive databases

TFS386206 

DVHisDBInstallVersion becomes VV.VV.VV when using the BH DVHisDBInstallVersion installer that was created for TFS 348017 and TFS 327311

TFS434805 / TFSB98019 

DVHisDBInstallVersion remains VV.VV.VV DVHisDBInstallVersion VV.VV.VV for archive databases that contain either a hyphen or space or start with a number in the name using the BH installer created for TFS386206

TFSB158919 

Batch Historian installation issues using the original DeltaV v14.3.1 installer

NK-1800-0059: DeltaV v13.3.1 and v14.LTS Batch Historian Installation Issues 

3.2.1.3 SOA_Gateway_1431_TFS338729

Standalone hotfix, SOA_Gateway_1431_TFS338729, addressed the following issue: is sue: Incident Number

TFS338729 

Descrip Descrip tion

The SOA Gateway software from the DeltaV v14.3.1 v1 4.3.1 installation media is not installing correctly on machines running Windows Server 2016 operating system.

Re Reference ference KBA

NK-1700-0211: Error installing Campaign Manager SOA Gateway on a nonDeltaV node with Windows Server 2016 OS 

3.2.1.4 DeltaV_1431_TFSB437235_BHServer

Standalone hotfix, DeltaV_1431_TFSB437235_BHServer, addressed the following issue: Incident Number

TFSB437235 

3. 3.2. 2.2 2

Descrip Descrip tion

Sequence of the Batch Historian AutoArchive does not automatically increase when the AutoArchive name has a hyphen symbol (-).

Reference Reference KBA

NK-2000-0478: DeltaV Batch Historian Archive Issues When the Archive Name Starts With a Number or Has a Hyphen Character (-) 

Previous Workstation and Batch Hotfix Bundl es

The following hotfixes have been superseded by DeltaV_1431_WS_20_CSS: 3.2.2.1 3.2 .2.1 DeltaV_1431 DeltaV_1431_WS_ _WS_19_ 19_CSS CSS address ed the foll owi ng is sues: Note: This bundle includes DeltaV Data Collector software version DDC_5101. The DDC software is located in the DeltaV\DVData folder. For more information refer to KBA KBA  NK-1100-1172: DeltaV Data Collector Utility Quick Start Installation and Usage Guide  

Page 25 of 56 

 

Incident

Description

Number

Reference KBA

NK-2100-0153: DeltaV The Auto-Update Service (YellowPages) only replicates one display TFSB514855

or chart each time the Setup Data is downloaded to the destination node. This issue was introduced by the hotfix for TFS477060, provided in DeltaV_1431_WS_18_CSS.

Operate - Auto-Update Service (YellowPages) Replicates Only One Display or Chart Each Time the Setup Data Is Downloaded to Destination Node  Node  NK-2000-0498: DeltaV

TFSB92877/ TFS433916 (Batch)

The sequence number of the Transtate.dat file is reset and some of

Batch Historian - Sequence

the SeqXXXXXX.dat files of the Batch Executive’s

Number of the

DVData\Batch\Working Folder are deleted. When these issues

Transtate.Dat File Is Reset

occur, the Batch Historian stops collecting new batch data.

and the SeqXXXXX.Dat Files  Are Deleted  

TFSB94442/

DeltaV Live SIS write pop-up shows on wrong screen in multiple

TFS434073

monitor setup.

Not Applicable

TFSB103653/T FS435290 TFSB140139

Enabling and disabling the Grid in Graphics Studio fails. Graphics Studio stops unexpectedly when ungrouping certain objects. Addition of a Control Performance Statistics (CPS) application on

TFSB162851

the ProPlus. CPS runs in the background and collects data from the Advanced Control Server, Alarms and Events database, and controllers. Resulting analyzed data is displayed in Guardian.

TFSB165123

TFSB176080

Not Applicable Not Applicable NK-1900-0820: DeltaV Insight Control Performance Monitor (CPM) Data Collection Release Information   Information

DeltaV security issue.

Not Applicable

DeltaV Operate takes approximately 5 minutes to open o pen when Color

NK-2000-0223: DeltaV Operate Issues When Color

Set TMP files are present prese nt in Graphics-iFix/Pic folder.

Set tmp Files are Present in Graphics-iFix/Pic Folder  

TFSB177596

TFSB178409

Virtual Controllers showing Red X intermittently on DeltaV Explorer and Diagnostics. Graphics Studio stops unexpectedly when verifying a display after deleting property groups.

KBA NK-2100-0201 is being written to document this issue. Not Applicable

TFSB185830

Display opening improvements for DeltaV Live.

Not Applicable

TFSB188149

DeltaV security issue.

Not Applicable Page 26 of 56 

 

Incident

Description

Number

TFSB203271

Graphics Studio imports non-active languages regardless of settings.

Reference KBA

Not Applicable

TFSB286466

Improvements to SFC Visualization in DeltaV Live.

Not Applicable

TFSB286933

MPC-PRO optimizer does not calculate optimal solution.

Not Applicable

TFSB438148

DeltaV security issue.

Not Applicable NK-2100-0199: Enterprise

TFSB447860

DeltaV OPC DA Server / Enterprise Historian data collection has

Historian / DeltaV OPC DA

been improved.

Server Improvements with Data Collection  Collection  NK-2100-0012: DeltaV

TFSB450190/T

On Redundant Batch Executive nodes acquired Units may remain

FS417032

retained after a switchover, with Units not released at the end of

(Batch)

the batch.

Batch - Acquired Equipment Might Not Get Released after a Batch Executive Warm Restart or Redundant Batch Executive Switchover   NK-2100-0200: Embedded Trends Are Unable to Access

DeltaV Operate/Embedded Trend Charts are unable to access TFSB457921

historical data in ACH or EntPI when PI AF Client 2018 SP3 PatchYYY is installed.

Historical Data in DeltaV  Advanced Continuous Historian or Enterprise Historian When PI AF Client 2018 SP3 Patch 2 Is Installed  

TFSB458700

TFSB466011

Display History navigation button does not capture changes generated by GEM interactions.

Not Applicable

DeltaV Operate now supports an option to enable e nable and disable the

NK-2000-0734: Option to

ability to resize the DeltaV Operate Oper ate window. By default this option

Enable and Disable the

is disabled. To enable it, add WorkSpaceEnableResizing

 Ability to Resize of DeltaV

(REG_DWORD) in the Registry (DeltaV\CurrentVersion) and set its

Operate Window is Not

value to 1.

 Available    Available

Page 27 of 56 

 

Incident

Description

Number

Reference KBA

NK-2000-0742: PK Controller Does Not Perform PK Controller doesn't perform a Local Download D ownload after a power TFSB466198

failure when Cold Restart is configured for Always Enabled if the PK was powered down for more than 31 days.

a Local Download after Being Powered down for More Than 31 Days Even When Cold Restart Is Configured as Always Enabled  

DeltaV import fails when importing a SIS module where w here a SIS TFSB469501

composite has an internal read parameter with write access set to

Not applicable

“Not writeable” or “Not Operator writeable when locked”. 

TFSB488056 TFSB489642

Display Generation improvements in Graphics Studio. DeltaV Live Application server fails unexpectedly when DeltaV Free Fre e Memory drops.

Not Applicable Not Applicable NK-2100-0060: DeltaV

TFSB490110

RtYellowPagesService process termination does not trigger the ProPlus to give up the YellowPages Master Role.

ProfessionalPLUS Retains  Auto-Update Master Server Role after RtYellowPagesService Process Stops Responding or Exits  Exits 

3.2.2.2 DeltaV_1431_WS_18_CSS Note: DeltaV_1431_WS_18_CS DeltaV_1431_WS_18_CSS S has been pulled back from distribution. Refer to KBA KBA  NK-2100-0153: DeltaV Operate - Auto-Update Service (YellowPages) Replicates Only One Display or Chart Each Time the Setup Data Is Downloaded to Destination Node for more information about the issue. This bundle includes DeltaV Data Collector software version DDC_5101. The DDC software is located in the DeltaV\DVData DeltaV\DVDat a folder. For more information refer to KBA  KBA  NK-1100-1172: DeltaV Data Collector Utility Quick Start Installation and Usage Guide . 

DeltaV_1431_WS_18_CSS DeltaV_1431_WS_18_CS S addressed the fol following lowing issues: Incident Number

TFSB134904

De Descrip scrip tion

Re Reference ference KBA

DeltaV Live freezes when using the ALT+Space key combination.

Not Applicable

TFSB168184

DeltaV Live is failing to search for modules.

KBA NK-2100-0109 is being written to document this issue.

TFSB168633

Data Entry faceplate shows long decimal values for whole numbers.

Not Applicable

Page 28 of 56 

 

Incident Number

De Descrip scrip tion

TFSB178831

DeltaV Live fails to start on first login if Autorun DeltaV Live is enabled.

TFSB282288

Simulate conversion corrupts an SFC, turning steps, transitions, etc. into composites. Simulate conversion does not convert Equipment Modules

TFSB351576

TFSB459491

TFSB459754

TFSB462038 TFSB467895

correctly. Modules cannot be opened or downloaded.

Re Reference ference KBA

KBA NK-2100-0099 is being written to document this issue. NK-2100-0100: Simulate Convert Does Not Convert Equipment Module Correctly  

Not able to write to external references to DST OUT & OUT_D parameters for Profibus & Devicenet IO simulation on a virtual controller.

NK-2000-0784: DeltaV IO Simulation - Unable to Write to DST Outputs For Profibus or Devicenet via External References 

"Unspecified Error" appears when user attempts to adjust configurable parameters of a Rockwell Automation – Allen Bradley E3/E300 Plus Device.

NK-2000-0665: "Unspecified Error" Appears When a User Attempts to Modify Bitmask Configurable Parameters of a DeviceNet Device  

DeltaV Live occasionally throws an error when changing the Mode of a module from a Faceplate. Invalid values in the Data Entry faceplate cause unexpected writes.

TFSB477060

SIS alarm groups intermittently become unconfigured.

TFSB480224

DeltaV Live occasionally appears sluggish.

TFSB489041

Improved internal diagnostics for DeltaV Live communications.

Not Applicable NK-2100-0101: SIS Alarm Groups Intermittently Become Unconfigured in DeltaV Live  Not Applicable

3.2.2.3 DeltaV_1431_WS_17_CSS

DeltaV_1431_WS_17_CSS DeltaV_1431_WS_17_CS S addressed the following issues: Note: This bundle includes DeltaV Data Collector software version DDC_5101. The DDC software is located in the DeltaV\DVData folder. For more information refer to KBA KBA  NK-1100-1172: DeltaV Data Collector Utility Quick Start Installation and Usage Guide .  Incident Number

TFSB118854 /TFS436700

TFSB145022

De Descrip scrip tion

Re Reference ference KBA

Remnants of panel borders sometimes appear in DeltaV Control Studio when panels are resized on physical workstations and on Remote Client Sessions. Panel borders are sometimes not displayed on Remote Client Sessions.

NK-2100-0053: Issues Displaying Panel Border in Control Studio on Local and Remote Client Sessions 

Historical Tags shows Historizing attribute = FALSE in the OPC UA Historical Access Server

NK-2100-0054: OPC UA Historical Access Server Sets Historizing Attribute = FALSE For Tags Being Historized In DeltaV 

Page 29 of 56 

 

Incident Number

TFSB183666

TFSB188548 (Batch)

De Descrip scrip tion

On a Simulate Pro system, a save operation may fail if the ASN contains a module with a somewhat complex MPCP block

Parallel transitions in a recipe are not always processed correctly when returning from HOLD

Re Reference ference KBA

NK-2100-0055: Save Function on SimulatePro Cannot Handle Modules With MPCP Block   NK-2000-0670: Parallel Transitions In a Recipe Are Not Always Processed Correctly When Returning from HOLD 

TFSB188992/ TFS335635 (Batch)

TFSB452712

 A phase may become disconnected disconnected after a recipe transition transition fires if the phase executed no stopping logic

NK-2000-0463: DeltaV Batch - Phase Becomes Disconnected After Recipe Transition Fires and Executes a Null Stopping Logic 

Forced Values are not removed with Control Studio mode change from Debug to On-line mode

NK-2000-0583: Forced Values Are Not Removed in Control Studio Mode When Changed from Debug to Online Mode  

TFSB459428

DeltaV Live throws an error when using the Acknowledge All Functions

TFSB459673

Quick Online View fails to launch from Graphics Studio

TFSB463107

DeltaV Live throws an uncommon error message on launch

TFSB464135

Minor issues occur when Electronic Signatures are used on data links with Zone names in the path

TFSB464950

DeltaV Live data periodically shows as “unconfigured”  

TFSB467239

Improvements to 3rd Party tools utilized by DeltaV Live

TFSB469510

Electronic Signature requirement check for Acknowledge All Alarm function times out when executed on a large number of Alarms

Not Applicable

3.2.2.4 DeltaV_1431_WS_16_CSS

DeltaV_1431_WS_16_CSS DeltaV_1431_WS_16_CS S addressed the following issues: Note: This bundle includes DeltaV Data Collector software version DDC_5101. The DDC software is located in the DeltaV\DVData folder. For more information refer to KBA KBA  NK-1100-1172: DeltaV Data Collector Utility Quick Start Installation and Usage Guide .  Incident Number

TFSB168261

Descrip Descrip tion

Multiple Bad Writes are seen in DeltaV Diagnostics for tags of  Advanced Continuous Historian Historian (ACH) afte afterr a reboot.

TFSB186624

Batch does not use the recipe parameter values, formula description and version defined by the recipe formulas if the TAB or ENTER key is

Re Reference ference KBA

NK-2000-0496: DeltaV  Advanced Continuous Historian May Show Bad Writes in DeltaV Diagnostics  NK-1200-0191: Batch Does Not Use the

Page 30 of 56 

 

Incident Number

Descrip Descrip tion

Re Reference ference KBA

used to select the recipe formula during batch creation in DeltaV Operate or DeltaV Live Batch Controls.

Correct Recipe Information Defined By the Recipe Formula During Batch Creation When Using the TAB or ENTER Key from DeltaV Operate or DeltaV Live  

TFSB300885

Analog Tracking block no longer responds to interlock conditions after afunction controller switchover.

NK-2000-0558:  Analog Tracking Function Block No Longer Responds to Interlock Conditions after Controller Switchover  

TFSB454397

DeltaV Device Commissioner with AMS 14.5 cannot complete configure phase due to a failure to identify the device.

NK-2000-0766: DeltaV Device Commissioner With AMS Device Manager v14.5 Cannot Complete Configure Phase Due to Failure to Identify Device 

TFSB463057

In DeltaV Live, the mode, named sets, and scaling parameters in contextual displays is taking time to resolve after the hotfix for

Not Applicable

TFSB286077 (in WS_12) is installed. 3.2.2.5 DeltaV_1431_WS_15_CSS

DeltaV_1431_WS_15_CSS DeltaV_1431_WS_15_CS S addressed the following issues: Note: This bundle includes DeltaV Data Collector software version DDC_5101. The DDC software is located in the DeltaV\DVData folder. For more information refer to KBA KBA  NK-1100-1172: DeltaV Data Collector Utility Quick Start Installation and Usage Guide .  Incident Number

TFSB158167

Descrip Descrip tion

DeltaV Live fails to find modules with braces in the description in the search bar

Re Reference ference KBA

Not Applicable

TFSB188550

DeltaV Live contextual display OnClose scripting events periodically do not function

Not Applicable

TFSB189889

Copying a Standard causes Graphics Studio to close abruptly

Not Applicable

TFSB282421

DeltaV Live locks up when activating a link to a display that does not exist

TFSB352137

DeltaV Live performance improvements to Contextual Display call up performance

TFSB410119

Boxes around writable datalinks is persistent until another writeable datalink is selected

TFSB441284

Invalid characters and symbols cause the data entry object to write 0

TFSB442058

DeltaV Live fails to write to SIS Parameters if the Zone Name is included in the path

Not Applicable Not Applicable Not Applicable Not Applicable Not Applicable

Page 31 of 56 

 

Incident Number

TFSB443991

Descrip Descrip tion

Certain configuration causes DeltaV Live contextual displays and displays to launch without data or rendered text fields

TFSB444889

DeltaV Live DisplayLink objects stop working after following rapid execution between displays and levels

TFSB444936

Dragging and dropping library objects causes Graphics Studio to close abruptly

TFSB451134

Software updates to DeltaV Live third party components

Re Reference ference KBA

Not Applicable Not Applicable Not Applicable Not Applicable

3.2.2.6 DeltaV_1431_WS_14_CSS

DeltaV_1431_WS_14_CSS DeltaV_1431_WS_14_CS S addressed the following issues: Note: This bundle includes DeltaV Data Collector software version DDC_5101. The DDC software is located in the DeltaV\DVData folder. For more information refer to KBA KBA  NK-1100-1172: DeltaV Data Collector Utility Quick Start Installation and Usage Guide .  Incident Number

Descrip Descrip tion

Re Reference ference KBA

NK-1800-0989: Batch TFSB188003 (Batch)

TFSB445860

Batch Manager disconnects all batch clients due to a DCOM lock issue, caused by Microsoft file msxml3.dll.

The Process History View chart opened from a PID Faceplate does not display the SP parameter’s default plot method (Step).  

With the hotfix to B186056 installed DeltaV Operate (WorkSpace.exe) TFSB454167

TFSB458028

sometimes terminates (Faulting Trends. Module PEGRP32G. PEGRP32G.dll) dll) when opening graphics containing Embedded

Process History View (PHV) trends are shifted (advanced or delayed) by an hour and not in sync with the timestamp in the legend l egend section when the time zone has Daylight Saving Time (DST).

Manager Disconnects Batch Clients due to All Distributed COM Lock Issue 

NK-2000-0711: DeltaV Process History View Chart Opened from a PID Faceplate Does Not Display the Default Plot Method Selection for the SP Parameter   NK-2000-0623: DeltaV Operate (WorkSpace.exe) Intermittently Crashes When Opening Graphics Containing Embedded Trends 

NK-2000-0654: DeltaV Process History View Trend May Be Displayed With an Offset of One Hour When Time Zone Has Daylight Saving Time 

3.2.2.7 DeltaV_1431_WS_13_CSS

DeltaV_1431_WS_13_CSS DeltaV_1431_WS_13_CS S addressed the following issues:

Page 32 of 56 

 

Important: Installation of this bundle may cause an issue discussed in KBA  KBA  NK-2000-0654: DeltaV Process History View Trend May Be Displayed With an Offset of One Hour When Time Zone Has Daylight Saving Time. This is resolved in DeltaV_1431_WS_14_CSS or later.

Do not install when using Operate with Embedded Trends. Revert to DeltaV_1431_WS_09_CSS or install DeltaV_1431_WS_14_CSS DeltaV_1431_WS_14_CS S or later. Please refer to KBA  KBA NK-2000-0623: DeltaV Operate (WorkSpace.exe) Intermittently Crashes When Opening Graphics Containing Embedded Trends  for further information. Note: This bundle includes DeltaV Data Collector software version DDC_5101. The DDC software is located in the DeltaV\DVData folder. For more information refer to KBA KBA  NK-1100-1172: DeltaV Data Collector Utility Quick Start Installation and Usage Guide .  Incident Number

TFSB122575/ TFS437135/ TFSB145306

TFSB127667/ TFS438225

TFSB163071

TFSB168828

Descrip Descrip tion

 ACH scanner efficiency efficiency has been improved with regard regard to sample collection.

Re Reference ference KBA

NK-2000-0364:  Advanced Continuous Historian (ACH) Improvements with Performance and Data Collection 

 Advanced Continuous Historian Historian stops collecting data for a certain period after making changes to history collection and downloading the Continuous Historian Subsystem.

NK-2000-0495: DeltaV  Advanced Continuous Historian Temporarily Stops Collecting Data  After a Download of the Continuous Historian Subsystem 

If VCAT is enabled, editing a property of the endpoint URL on a OPC UA Workstation Server from DeltaV Explorer may cause the error "The name 'OPC.tcp://localhost:49321/DvOpcUaServer' 'OPC.tcp://localhost:49321/DvOpcUaServer' was not found in this context".

NK-2000-0624: Deltav Explorer Error Is Encountered When Editing a Property of an Endpoint URL of the Workstation OPC UA Server  

In Advanced Continuous Historian, PI tag parameters are reset to default values after a download of the Continuous Historian Subsystem.

NK-2000-0497: DeltaV  Advanced Continuous Historian PI Tag Parameters Are Reset to Default Values After a Download of the Continuous Historian Subsystem 

Changing the named set assigned to a condition on a DCC block is not reflected in Control Studio online.

NK-2000-0139: Changing a Named Set  Assigned to a Condition on a DCC Block is not Reflected in Control Studio Online 

TFSB178632

DeltaV OPC UA Client is intermittently missing item reads from the Ovizio OPC UA Server.

NK-2000-0491: DeltaV OPC UA Client Intermittently Missing Item READS from a OPC UA Server  

TFSB180339

Tag Group Definition (TGD) files have been added to the files

NK-2000-0625: Custom

TFSB174704

Page 33 of 56 

 

Incident Number

Descrip Descrip tion

propagated by the Auto-Update Service (YellowPages).

TFSB183109

Event Chronicle entries generated by Analog Tracking and Discrete Control Condition Blocks report the composite, not the module.

Re Reference ference KBA Tag Group Definition Files in TGDFiles Folder are Not Propagated by YellowPages 

NK-2000-0626: Analog Tracking and Discrete Control Condition Blocks' Generated Event Chronicle Entries Report the Composite Not the Module 

TFSB188578

The DeltaV registration utility needs to support sending Insight CPM files.

NK-1900-0820: DeltaV Insight Control Performance Monitor (CPM) Data Collection Release Information 

TFSB188580

The DeltaV registration utility needs to collect DeltaV Live information in the registration file.

Not applicable

The NTP Server may lose time synchronization.

NK-2000-0500: NTPServer Might Become NONE in Diagnostics for DeltaV Workstations  

DVSYS sometimes crashes when DeltaV Operate pictures with references to SIS Alarm Groups are opened.

NK-2000-0627: DVSYS Crashes When Pictures with SIS Alarm Groups  Are Opened in DeltaV Operate 

TFSB189277

TFSB189790

TFSB440865

Network component Failure (i.e. switch or cable fault) affects workstation redundancy communication services, causing datalinks in Operate or Live to revert to cycling magenta status.

NK-2000-0490: Datalinks in DeltaV Operate Show @@@@ Characters with Magenta Background When Either of the Redundant DeltaV Network Connections Become Unavailable 

3.2.2.8 DeltaV_1431_WS_12_CSS

DeltaV_1431_WS_12_CSS DeltaV_1431_WS_12_CS S addressed the following issues: Important: Installation of this bundle may cause an issue discussed in KBA  KBA  NK-2000-0654: DeltaV Process History View Trend May Be Displayed With an Offset of One Hour When Time Zone Has Daylight Saving Time. This is resolved in DeltaV_1431_WS_14_CSS or later.

Do not install when using Operate with Embedded Trends. Revert to Delt aV_1431_WS_09_CSS or install DeltaV_1431_WS_14_CSS DeltaV_1431_WS_14_CS S or later. Please refer to KBA  KBA NK-2000-0623: DeltaV Operate (WorkSpace.exe) Intermittently Crashes When Opening Graphics Containing Embedded Trends  for further information. Note: This bundle includes DeltaV Data Collector software version DDC_5101. The DDC software is located in the DeltaV\DVData folder. For more information refer to KBA KBA  NK-1100-1172: DeltaV Data Collector Utility Quick Start Installation and Usage Guide . 

Page 34 of 56 

 

Incident Number

De Descrip scrip tion

TFSB143308

Displays failed to import when certain GEM Properties are overridden.

TFSB177991

Writes to discrete parameter with status may fail.

TFSB178866

Alarm Suppression icon sometimes becomes unselectable.

TFSB182616

DeltaV Live Import utility imports all content languages.

TFSB183327

Data Links and Text sometimes do not align in runtime.

TFSB183837

Diagnostics warnings are thrown for Out of the Box objects are configured without a PV Scale set.

TFSB184596

DeltaV Live performance degrades severely when left idle for a long period of time.

TFSB190310

DeltaV Live may fail to connect to multiple historians after several days.

TFSB198296

Certain configuration causes DeltaV Live to fail to resolve alarm data properly.

TFSB283569

DeltaV Live Webserver causes performance degradation over time.

TFSB286077

DeltaV Live services high amounts of memory causes performance degradation.

TFSB286627

Architectural Software updates to improve DeltaV Live.

Re Reference ference KBA

Not applicable

3.2.2.9 DeltaV_1431_WS_11_CSS

DeltaV_1431_WS_11_CSS DeltaV_1431_WS_11_CS S addressed the following issues: Important: Installation of this bundle may cause an issue discussed in KBA  KBA  NK-2000-0654: DeltaV Process History View Trend May Be Displayed With an Offset of One Hour When Time Zone Has Daylight Saving Time. This is resolved in DeltaV_1431_WS_14_CSS or later.

Do not install when using Operate with Embedded Trends. Revert to DeltaV_1431_WS_09_CSS or install DeltaV_1431_WS_14_CSS DeltaV_1431_WS_14_CS S or later. Please refer to KBA  KBA NK-2000-0623: DeltaV Operate (WorkSpace.exe) Intermittently Crashes When Opening Graphics Containing Embedded Trends  for further information. Note: This bundle includes DeltaV Data Collector software version DDC_5101. The DDC software is located in the DeltaV\DVData folder. For more information refer to KBA KBA  NK-1100-1172: DeltaV Data Collector Utility Quick Start Installation and Usage Guide .  Incident Number

De Descrip scrip tion

Re Reference ference KBA

DeltaV Operate does not use the full monitor on Windows Wind ows 10 and Windows Server 2016.

NK-2000-0529: DeltaV Operate Does Not Use the Full Monitor on Windows 10 and Windows Server 2016  

TFSB185121

DeltaV Operate allows resizing the WorkSpace window.

NK-2000-0530: DeltaV Operate Full Screen in Run Mode Functionality 

TFSB186056

The PID setpoint trend is not visible in Process History View when opened from a faceplate.

NK-2000-0433: PHV Charts from Faceplate are Not Plotting the Parameter's Data 

TFSB184672/ TFS373507

Page 35 of 56 

 

Incident Number

De Descrip scrip tion

The hotfix to B270047 is causing SIS secure writes from a workstation to fail after installing the DeltaV_1431_WS_10_CSS hotfix bundle.

TFSB443353

3.2.2.10

Re Reference ference KBA

NK-2000-0540: PRODUCT SAFETY CONCERN: Process Systems and Solutions -DeltaV Installation of DeltaV_1431_WS_10_C SS Bundle Causes SIS Secure Write Parameter Error  

DeltaV_1431_WS_10_CSS

DeltaV_1431_WS_10_CSS DeltaV_1431_WS_10_CS S addressed the following issues: Important: Installation of this bundle may cause an issue discussed in KBA  KBA  NK-2000-0654: DeltaV Process History View Trend May Be Displayed With an Offset of One Hour When Time Zone Has Daylight Saving Time. This is resolved in DeltaV_1431_WS_14_CSS or later.

Do not install when using Operate with Embedded Trends. Revert to DeltaV_1431_WS_09_CSS or install DeltaV_1431_WS_14_CSS DeltaV_1431_WS_14_CS S or later. Please refer to KBA  KBA NK-2000-0623: DeltaV Operate (WorkSpace.exe) Intermittently Crashes When Opening Graphics Containing Embedded Trends  for further information. Installation of this bundle may cause an issue discussed in KBA  KBA  NK-2000-0540: PRODUCT SAFETY CONCERN: Process Systems and Solutions -- DeltaV Installation of DeltaV_1431_WS_10_CSS Bundle Causes SIS Secure Write Parameter Error . This is resolved in DeltaV_1431_WS_11_CSS DeltaV_1431_WS_11_CSS or later. Note: This bundle includes DeltaV Data Collector software version DDC_5101. The DDC software is located in the DeltaV\DVData folder. For more information refer to KBA KBA  NK-1100-1172: DeltaV Data Collector Utility Quick Start Installation and Usage Guide .  Incident Number

TFSB8271/ TFS311127

De Descrip scrip tion

MPC PredictPro incorrectly identifies data with bad status when "Verify Against Selected Data" option is chosen.

DeltaV OPC DA Server remote clients are not always removed when no longer in use. TFSB12052/ TFS409227

TFSB118639

Note: This update also has to be b e installed OPC Remote machines. Refer to KBA  KBA  AK-1900-0002: AK-1900-0002: Software Updates for OPC Remote for DeltaV  for the installer download link for OPC Remote machines.

Re Reference ference KBA

NK-2000-0487: DeltaV PredictPro Incorrectly Identifies Data with Bad Status when "Verify Against Selected Data" Option is Selected 

 AK-1700-0073: OPC Client Connections Are Not Released Causing Multiple Client Instances in Diagnostics 

DeltaV security issue.

Not applicable

TFSB125224/ TFS437836

The Neural application crashes when performing sensitivity analysis using data that spans several months.

NK-2000-0480: DeltaV Neural Application Crashes When Performing Sensitivity  Analysis Using Large  Amounts of Historical Data  

TFSB135485/ TFS415367

The controller firewall successfully blocks controller unlock but does not generate a dialog.

NK-2000-0481: Deltav Controller Firewall Does Not

Page 36 of 56 

 

Incident Number

De Descrip scrip tion

Re Reference ference KBA Generate an Error Dialog When an Unlock Attempt in the DMZ Was Successfully Blocked 

TFSB135623/ TFS439801

TFSB138281/ TFS440258

TFSB148975

Predict generates an error message when connecting to MPC block.

Unresolved References are evaluated as True when wired into discrete inputs, even when the value is #IGNORE.

HART long tag is not processed properly during binding (hybrid mode) if the DST and HART long tag are longer than 8 characters.

NK-2000-0488: DeltaV Predict Generates an Error Message when Connecting to an MPC Block   NK-1900-1017: Unresolved References are Evaluated as True When Wired into Discrete Inputs Even if the Reference Value is #IGNORE 

NK-2000-0482: DeltaV HART Long Tag or Message Field Might Not Be Processed Properly during the Binding Phase (Hybrid Mode) If the DST and HART Long Tag (Or Message Field) Are Longer Than Eight Characters  

TFSB158419

TFSB159487 (Batch)

InSight plots in Detailed Performance reports do not work.

In a workgroup environment, adding a new batch in BatchListView using Batch Controls takes 45 seconds to 1 minute when using a non-DeltaV Admin account.

NK-2000-0333: DeltaV Insight - Performance Reports Do Not Plot or Display Historically Collected Parameters Such as PV and SP for Detail Control Loop Reports  NK-2000-0350: In a Workgroup Environment,  Adding a New Batch In Batchlistview Using Batch Controls Takes 45 Seconds to 1 Minute When a   Non-DeltaV AdminUsing Account

TFSB167469

TFSB171118 (Batch)

TFSB176359

 ACH: Continuous Continuous Historian Diagnostic Parameter Parameter LOAD is higher on virtual machines compared to physical machine.

When the "Allow Multiple Selection" option is unchecked in the DVBCrtlBatchList ActiveX Control, the selected Batch changes DVBCrtlBatchList when the ActiveX Control updates.

In PK Assistant, Project Backup fails when fully qualified file name exceeds 260 characters.

NK-2000-0364: Advanced Continuous Historian (ACH) Improvements with Performance and Data Collection   NK-2000-0398: The Selected Batch Changes When the ActiveX Control Updates When the "Allow Multiple Selection" Option is Unchecked  NK-2000-0483: Standalone DeltaV PK Controller Project Backup Fails When the

Page 37 of 56 

 

Incident Number

De Descrip scrip tion

Re Reference ference KBA Local Path Length Exceeds 260 Characters  

TFSB176767

When using Control Studio Online the EDC Block IGNORE_PV_ACT IGNORE_P V_ACT parameter does not track IGNORE_PV correctly.

NK-2000-0427: EDC Block's IGNORE_PV_ACT Parameter is Not Tracking IGNORE_PV Correctly in Control Studio Online  

TFSB178644

DeltaV Live: Certain alarms in control tag faceplates are blinking.

Not applicable

In Device Signal Simulator, the OUT_VALUE is not getting displayed when the input function block is inside a composite function block.

NK-2000-0485: In Device Signal Simulator, the OUT_VALUE is Not Displayed when the Input Function Block is Inside a Composite Function Block 

DeltaV Live is experiencing significant performance degradation when a high number of alarms are active.

NK-2000-0486: DeltaV Live Experiences Significant Performance Degradation when a High Number of  Alarms are Active  

TFSB188867

TFSB270047

3.2.2.11 DeltaV_1431_WS_09_CSS DeltaV_1431_WS_09_CSS DeltaV_1431_WS_09_CS S addressed the following issues: Important: Installation of this bundle may cause an issue discussed in KBA  KBA  NK-2000-0654: DeltaV Process History View Trend May Be Displayed With an Offset of One Hour When Time Zone Has Daylight Saving Time. This is resolved in DeltaV_1431_WS_14_CSS or later. Note: This bundle includes DeltaV Data Collector software version DDC_5101. The DDC software is located in the DeltaV\DVData folder. For more information refer to KBA KBA  NK-1100-1172: DeltaV Data Collector Utility Quick Start Installation and Usage Guide .  Incident Number

De Descript script ion

Reference Reference KBA

NK-2000-0409: DeltaV Virtualization theon Primary ACN disabling connection active partner causes switchover on the redundant application station  

TFSB91110/ TFS432988

Disabling just the Primary ACN connection on the active partner causes a switchover on the redundant application station.

TFSB91232/ TFS430809

Enforced Formula recipe property is changed from TRUE to FALSE during an import.

NK-1900-0880: Enforced Formula recipe property is changed from TRUE to FALSE after the Import 

TFSB123247/ TFS437302

Trends in DeltaV Operate are inconsistent with PHV in specific circumstances.

NK-2000-0410: Embedded Trends in DeltaV Operate are Inconsistent with PHV in Specific Circumstances  

TFSB123485/ TFS437476

The DCC block will fail to update u pdate when a Control Module is converted to a class-based module.

NK-1900-0756: Configuration Errors on a Discrete Control Condition (DCC) Function Block

Page 38 of 56 

 

Incident Number

De Descript script ion

Reference Reference KBA May Cause a Controller to Reset or the Standby Controller to Become Unavailable  

TFSB134560

TFSB135455

Version control is requiring user to check out Batch Executive to update recipes.

Logging hotfix for investigation: Batch Manager Disconnects All Batch Clients due to Distributed COM Lock Issue.

NK-2000-0412: VCAT is Requiring the Batch Executive Node to be Checked Out to Update Recipes in DeltaV Recipe Studio  NK-1800-0989: Batch Manager Disconnects All Batch Clients due to Distributed COM Lock Issue 

TFSB147848

Security issue with DeltaV passwords.

NK-2000-0366: Flexlock Allows User to Re-use Same Password 

TFSB154207

The SFC Action Confirm Expression not selectable when viewed online/read-only.

NK-2000-0413: The SFC Action Confirm Expression is Not Selectable When Viewed Online or Read-Only   NK-1900-1224: Engineering

TFSB158849

In WatchIt, engineering unit value for IO function blocks can no longer be changed with an input of type string.

TFSB161475

Can't change an expired password via FlexLock.

NK-2000-0414: DeltaV Flexlock Does Not Allow Users to Change Expired Password  

Unable to open Process History View on a DeltaV RAS client due to a licensing issue.

NK-2000-0224: Unable to Open Process History View and Control Studio in Remote Operator station/RAS Client Due to Insufficient License Error  

TFSB174237

Healthy virtual controller nodes are appearing as disconnected in in DeltaV Explorer.

NK-2000-0415: DeltaV Virtual Machines Incorrectly Appear as Not Communicating in DeltaV Explorer  

TFSB175248

DeltaV Live is failing to audit custom scale correctly.

Not applicable

TFSB176402

Modules with a scan rate set 10 seconds or slower cannot be opened in Control Studio Debug mode.

NK-2000-0416: DeltaV Control Studio Modules with Scan Rate Set to 10 Seconds or Slower Cannot be Opened in Debug mode 

TFSB176404

DeltaV PID block dynamic values (e.g. Gain, Reset) in Simulate tuning are not properly restored to the snapshot values on a snapshot restore.

NK-2000-0417: DeltaV Simulate PID Block Dynamic Values in Tuning Is Not Properly Restored after Snapshot Restore 

TFSB176768

DeltaV Security Administrator does not work on a Domain when only a single dot "." is in the FQDN.

NK-2000-0419: Deltav Security  Administrator Does Not Work Wor k

TFSB172691

Unit Value for IO function Blocks Can No Longer be Changed with an Input of Type String 

Page 39 of 56 

 

Incident Number

De Descript script ion

Reference Reference KBA on a Domain When Only a Single Dot Is in the FQDN  

TFSB177757

 An application station DeltaV runtime software ffails ails when an Initial Conditions backup containing uninitialized parameter values is restored.

NK-2000-0420: DeltaV  Applications Crash When an IC Containing an Uninitialized Parameter Value is Restored from SimulatePro 

TFSB180037

The 1508 Logic Solver can't be downloaded when using an inverted scale in an LSAI (OUT_SCALE) or an AVTR block (IN_SCALE).

NK-2000-0421: DeltaV Smart Logic Solvers (SLS1508) Cannot Be Downloaded When Using an Inverted Scale In LSAI or LSAVTR Function Blocks  

TFSB182381

Size and shape of GEMs change when moving between 14.3.1 bundles.

Not applicable

TFSB185544

GEM instance configuration is defaulting to class values in some circumstances.

Not applicable

TFSB188016

Parameter write popup window in DeltaV Live is not accurately capturing parameter range.

Not applicable

TFSB189265

TFSB190250

3.2.2.12

Some datalinks are incorrectly returning a null value after installation of WS_08.

NK-2000-0380: DeltaV Live Displays Fail to Render When Objects on the Display Contain Custom OnWrite interactions with METAOF or DLPATH Functions 

Specific configuration in the OnWrite event for variables in DeltaV Live causes Displays to appear broken online.

NK-2000-0380: DeltaV Live Displays Fail to Render When Objects on the Display Contain Custom OnWrite interactions with METAOF or DLPATH Functions 

DeltaV_1431_WS_08_CSS

DeltaV_1431_WS_08_CSS DeltaV_1431_WS_08_CS S addressed the following issues: Note: This bundle includes DeltaV Data Collector software version DDC_5101. The DDC software is located in the DeltaV\DVData folder. For more information refer to KBA KBA  NK-1100-1172: DeltaV Data Collector Utility Quick Start Installation and Usage Guide .  Incident Number

De Descript script ion

TFSB107243/ TFS423577

DeltaV Live Combo-box drop-down menus on Faceplates appear in unpredictable places.

Not applicable

TFSB133487/ TFS439176

DeltaV Live Checkboxes temporarily appear as checked when evaluating user write privileges.

Not applicable

TFSB134914

DeltaV Live Yes-No prompt fails to write as expected.

Not applicable

TFSB136266

Switching between faceplates in DeltaV Live causes unpredictable behavior on GEM selection indication.

Not applicable

Reference Reference KBA

Page 40 of 56 

 

Incident Number

De Descript script ion

TFSB138050/ TFS441624

Nested SIS function blocks do not open Out of Box SIS Function Black Faceplates properly in DeltaV Live.

Not applicable

TFSB149351

Security issue.

Not applicable

TFSB159725

DeltaV Live faceplates do not open Process History View properly for inter-zone tags.

Not applicable

Certain DeltaV Live pop-ups are not opening on the correct monitor in a multi-monitor setup.

TFSB164132

Reference Reference KBA

Not applicable

TFSB164453

Command Driven Equipment Module commands take 15 seconds to populate on DeltaV Live faceplates.

Not applicable

TFSB167714

DeltaV Live Alarm List text properties make the Alarm List difficult to read in some configurations.

Not applicable

TFSB168016

DeltaV Live Combo-box occasionally displays the incorrect Boolean parameter value.

Not applicable

TFSB168659/ TFS437950

 Alarms which are shelved and set to Out of Service show on neither the Supression List nor the Out of Service list in i n DeltaV Live.

Not applicable

TFSB168826

Custom class-based GEMs size changes are not shown in DeltaV Live.

Not applicable

TFSB171301

DeltaV Live OnWrite for certain items is not executing.

Not applicable

DeltaV Live data links with specific expressions intermittently are

TFSB174912

unable to show the resultant value.

Not applicable

TFSB178432

DeltaV Live can sometimes consume memory over several weeks.

Not applicable

TFSB182445

DeltaV Live Application Server can use a high amount of CPU under certain conditions.

Not applicable

DeltaV Live Alarm List check box colors are not configurable.

Not applicable

TFSB94444/ TFS434157 3.2.2.13

DeltaV_1431_WS_07_CSS

DeltaV_1431_WS_07_CSS DeltaV_1431_WS_07_CS S addressed the following issues: Note: This bundle includes DeltaV Data Collector software version DDC_5101. The DDC software is located in the DeltaV\DVData folder. For more information refer to KBA KBA  NK-1100-1172: DeltaV Data Collector Utility Quick Start Installation and Usage Guide .  Incident Number

TFSB123249/ TFS437300

De Descript script ion

Neural application terminates when autogenerating from a file or performing sensitivity analysis from file.

In DeltaV Explorer Version Control, the error "The parameter is TFSB137155/ TFS440075

incorrect." is displayed in VCatConfigView when clicking on the

Reference Reference KBA

 AK-1900-0042: Neural  Application Stops Responding When Performing Sensitivity  Analysis or Autogenerate From an External Data File  NK-1900-1212: Error Message "The parameter is incorrect."  Appears When Clicking the

Page 41 of 56 

 

Incident Number

De Descript script ion

Reference Reference KBA

Failure Monitor block of a phase class.

Failure Monitor Block of a Phase Class From VCATConfigView in DeltaV Explorer  

TFSB147861/ TFS424011

Security issue in DeltaV graphics.

Not Applicable

TFSB163464

Unit Module’s BATCH_INFO Parameter Values Toggle or Are Not Cleared Properly.

NK-2000-0029: Unit Module’s BATCH_INFO Parameter Values Toggle Or Are Not Cleared Properly 

Loss of Synchronization Between the Batch Historian and Batch Executive Can Occur in Certain Circumstances.

TFSB164663

Note: The hotfix for B164663 should be installed install ed on the Batch Historian workstation before installing it on the following workstations:

- Batch Executive.

NK-2000-0079: Loss of Synchronization of Batch Historian with Batch Executive and Event Chronicle Can Occur in Certain Circumstances  

- Any Event Chronicle workstation that is reporting  Alarms & Events Events data to the Batch Historian.

TFSB168478

Security issue with DeltaV Operate and DeltaV Live.

NK-2000-0104: Parameters Can Be Changed in DeltaV Operate or DeltaV Live When There is No DeltaV User Logged On  NK-2000-0273: DSN20003-1 Privilege Escalation in DeltaV Operate and DeltaV Live 

Batch Historian may stop collecting Alarms and Events data if there is a gap in the Event Chronicle sequence numbers.

TFSB171847

Note: The hotfix for B171847 should be installed on the Batch Historian workstation before installing it

NK-2000-0079: Loss of Synchronization of Batch

on the following workstations: - Batch Executive.

Historian Batch Executive and Eventwith Chronicle Can Occur in Certain Circumstances  

- Any Event Chronicle workstation that is reporting  Alarms & Events Events data to the Batch Historian.

TFSB172407

SIS Unsolicited Data Shows Incorrect Values on Some Operator Stations and in Control Studio Online.

NK-2000-0156: SIS Unsolicited Data Shows Incorrect Values on Some Operator Stations and in Control Studio Online  

TFSB175880

Online simulated values from Device Signal Simulator application do not always update with the online CSLS simulated value.

NK-2000-0272: Device Signal Simulator does not always update the CSLS Simulated Values 

Page 42 of 56 

 

3.2.2.14

DeltaV_1431_WS_06_CSS

DeltaV_1431_WS_06_CSS DeltaV_1431_WS_06_CS S addressed the following issues: Note: This bundle includes DeltaV Data Collector software version DDC_5101. The DDC software is located in the DeltaV\DVData folder. For more information refer to KBA KBA  NK-1100-1172: DeltaV Data Collector Utility Quick Start Installation and Usage Guide .  Incident Number

TFSB98014/ TFS434813

TFSB123551/ TFS223210

De Descript script ion

Slew buttons in DeltaV Live stop updating after consecutive clicks. Multiple errors may occur when launching DeltaV Operate if the workstation has not been downloaded yet or if the download did not complete.

Reference Reference KBA

Not Applicable NK-1900-0986: Multiple Errors May Occur in DeltaV Operate if the Workstation has Not been Downloaded Yet or if the Download did Not Complete 

TFSB123553/ TFS437539

DvRocService process exits on the ProPLUS or Application Station that Virtual Logic Solvers are assigned to when Faceplates and Pictures containing Virtual SIS Module Alarm Group references are opened on another workstation.

NK-2000-0234: Instances When the DvRocService Might Stop Responding on the ProfessionalPLUS or  Application Station with  Assigned Simulated Logic Solvers 

TFSB135661

Cannot download a recipe that is System Assignment only from DeltaV Recipe Studio

NK-2000-0204: Cannot download a recipe that is System Assignment only from DeltaV Recipe Studio 

TFSB138989/ TFS387718

Shelved Timer in DeltaV Live Alarm Suppression List may be inaccurate by up to one minute.

Not Applicable

TFSB140014/ TFS440866

DeltaV Live Graphics sometimes are unable to be edited or exported from Graphics Studio.

Not Applicable

TFSB142845/ TFS441349

TFSB155522

On DeltaV Live the Ack and Description columns may stop working when the Alarm List is open for extended periods of time.

DeltaV Live import may change certain values in Gem instances.

NK-1900-1111: Alarm Summary Control's "Ack" and "Description" Columns Stop Working When DeltaV Operate Has Been Running for an Extended Period (~25 Days)  Not Applicable

On a Remote Client Server, CPU usage remains high for each instance of Workspace.exe that opens after the first one.

NK-2000-0205: Subsequent Workspace.exe Instances Remain on High CPU Usage  After the First One  

TFSB165467

Unit Aliasing list takes slower to populate when creating batches on systems where the domain controller is an IDDC.

NK-2000-0206: Unit Aliasing List Takes Slower to Populate when the Domain Controller is an Independent DeltaV Domain Controller  

TFSB167624/ TFS413473

DeltaV Live pop ups may cause erratic behavior upon closing.

Not Applicable

TFSB171755

DeltaV Live in a Terminal Server session may occasionally

Not Applicable

TFSB157933

Page 43 of 56 

 

Incident Number

De Descript script ion

Reference Reference KBA

launch a white screen. TFSB172855

Improvements to the robustness of the DeltaV Live Display Frame and Windowing process.

Not Applicable

TFSB173381

Improvements in DeltaV Live display call-up time and Graphics Studio display generation performance.

Not Applicable

TFSB173382 TFSB176776

Routine security and maintenance updates for DeltaV Live architecture. SQL data source query fails in DeltaV Live.

Not Applicable Not Applicable

TFSB177747

In DeltaV Live Graphics Studio, a display with an instance of a nested GEM fails to open after a custom selection property was deleted from the nested GEM.

Not Applicable

TFSB178570

Open Source Notice For CIF web packages needs to be updated.

Not Applicable

3.2.2.15

DeltaV_1431_WS_05_CSS

DeltaV_1431_WS_05_CSS DeltaV_1431_WS_05_CS S addressed the following issues: Note: This bundle includes DeltaV Data Collector software version DDC_5101. The DDC software is located in the DeltaV\DVData folder. For more information refer to KBA KBA  NK-1100-1172: DeltaV Data Collector Utility Quick Start Installation and Usage Guide .  Incident Number

TFSB88925/ TFS268237/ TFS430417

TFSB94445/ TFS434172

De Descript script ion

The DeltaV heap memory size is insufficient for the multiple remote sessions used on Terminal Server nodes.  

Enhanced Control Selector OP_SELECTION Name Set change does not propagate on download.

Reference Reference KBA

NK-1900-0384: DeltaV Shared Heap Memory Size (FREMEM) may be Insufficient for Multiple Remote Client Sessions used on Remote Client Server Nodes   NK-1900-0718: Partial Download Does Not Update OP_SELECTION Parameter Configured Name Set on Enhanced Control Selector Function Block  

When using Simulate Pro to pause and then resume execution, many timers jump rather than continue from the paused value.

NK-2000-0120: Known Issues in Save/Restore to XML-format on v14.3 and v14.LTS DeltaV SimulatePro  

TFSB96560/ TFS434471

On OPCUA server, monitoring ClientSoftwareCer ClientSoftwareCertificates tificates item from AuditActivateSessionEventType may cause performance issues on an OPCUA client and subsequent connection requests to OPCUA Server will be denied.

NK-1900-1142: Monitoring Clientsoftwarecertificates Item from DeltaV OPC UA Server Might Cause Performance Issues in a Client and Denial of Connection Requests to the Server  

TFSB112258

When using Simulate, extensible parameters OUT1/OUT_D1/IN1/IN_D1 OUT1/OUT_D 1/IN1/IN_D1 are saved as OUT/OUT_D/IN/IN_D in XML.

NK-2000-0120: Known Issues in Save/Restore to XML-format on v14.3 and v14.LTS DeltaV

TFSB96307/ TFS326583

Page 44 of 56 

 

Incident Number

De Descript script ion

Reference Reference KBA SimulatePro  

TFSB112281/ TFS436055 (Batch)

Controller resets when running Batch phases simultaneously.

NK-1900-1035: Controller Resets When Running Batch Phases Simultaneously 

TFS436490

Process History View leaks GDI objects continuously when Group Policy is configured or when "gpudate /force" is run manually.

NK-1900-1041: Process History View's GDI Object Leaks During Group Policy Update 

TFSB124230/ TFS437623

The DeltaV System Registration Utility is terminating on access or creation of PlusRegUtil.txt_1 and PlusRegDeviceInfo.txt_1 if they exceed the 450KB size limit.

NK-1900-1102: DeltaV System Registration Utility Stops Unexpectedly or Fails to Retrieve IO Cards and Device Information  

Support for Distributed CHARMs on the CSLS in DeltaV v14.3.1. TFSB139782/ TFS440742

Note: This Note:  This is the workstation component of a hotfix that must be installed on all workstations along with the hotfix bundles DeltaV_1431_CTRL_SZ_03_CSS and DeltaV_RI_CSLS_05_CSS, and DeltaV_RI_DCSM_02_CSS (and these devices flashed) to provide the CSLS distribute CHARMs functionality. 

NK-2000-0052: DeltaV Distributed CHARMs for CSLS Software Release Information  

The PID function block PV filter does not initialize during a simulate restore.

NK-2000-0120: Known Issues in Save/Restore to XML-format on v14.3 and v14.LTS DeltaV SimulatePro  

TFSB140217

Modules fail to import into v14.3.x if some of the default engineering units are being used before v14.

NK-2000-0110: Control Modules Fail to Import to DeltaV v14.3.x if Some of the Default Engineering Units are Being Used 

TFSB142595/ TFS441315 (Batch)

Some batches may go to LOST state and MANUAL mode after a Batch Executive switchover.

NK-1900-1215: Some Batches May Go to LOST State and/or MANUAL Mode After a Batch Executive Switchover  

TFSB139817/ TFS440878

NK-2000-0120: Known Issues String parameters in function blocks are not restored during a TFSB142680

Simulate XML restore operation.

in to XML-format onSave/Restore v14.3 and v14.LTS DeltaV SimulatePro  

On Simulate Pro, restoring an IC containing FB with parameter of data type DT_OPT_BITSTRING_NEW caused ASN fault.

NK-2000-0122: DeltaV  Applications on the ASN crash when a Snapshot containing any Function Block with Parameters of type DT_OPT_BITSTRING_NEW is Restored in DeltaV SimulatePro  

TFSB143825

XML save/restore does not work for conditional alarm parameters in Simulate.

NK-2000-0120: Known Issues in Save/Restore to XML-format on v14.3 and v14.LTS DeltaV SimulatePro  

TFSB143955

In Simulate, temporary variables in expressions are not saved and restored during XML operations but are during DAT

NK-2000-0120: Known Issues in Save/Restore to XML-format

TFSB143336/ TFS441480

Page 45 of 56 

 

Incident Number

De Descript script ion

operations.

on v14.3 and v14.LTS DeltaV SimulatePro  

In Simulate, the PID function block PV filter is incorrectly executing even when the PID block is in Out Of Service mode.

TFSB154270

Reference Reference KBA

NK-2000-0120: Known Issues in Save/Restore to XML-format on v14.3 and v14.LTS DeltaV SimulatePro  

Using the “Acknowledge All” function to acknowledge all alarms  

TFSB162114

associated with a module may cause DeltaV Live to fail. f ail.

Not Applicable

TFSB163420

DeltaV Live Displays are opening in separate windows and unexpected locations.

Not Applicable

TFSB167217

DeltaV Live Web Server occasionally can leak memory.

Not Applicable

TFSB167232

DeltaV Live failed when a large number of alarms are active.

Not Applicable

TFSB167755

DeltaV Live Alarm Rollup faults with a large number of alarms active.

Not Applicable

TFSB171887

Using the “Acknowledge All” function on a DeltaV Live faceplate throws an error message.

Not Applicable

3.2.2.16

DeltaV_1431_WS_04_CSS

DeltaV_1431_WS_04_CSS DeltaV_1431_WS_04_CS S addressed the following issues: Note: This bundle includes DeltaV Data Collector software version DDC_5101. The DDC software is located in the DeltaV\DVData folder. For more information refer to KBA KBA  NK-1100-1172: DeltaV Data Collector Utility Quick Start Installation and Usage Guide .  Incident Number

De Descript script ion

TFSB111120/ TFS435613

SIS modules cause a Workstation FREMEM leak when logged into DeltaV with DeltaV Operate (Run) open. op en. 

Reference Reference KBA

NK-1900-0795: DeltaV Shared Heap Memory (FREMEM) leaks on v14.3 and v14.LTS Workstations running DeltaV Operate on Systems with SIS Modules when Alarm Groups are Configured 

3.2.2.17

DeltaV_1431_WS_03_CSS

DeltaV_1431_WS_03_CSS DeltaV_1431_WS_03_CS S addressed the following issues: Note: This bundle includes DeltaV Data Collector software version DDC_5101. The DDC software is located in the DeltaV\DVData folder. For more information refer to KBA KBA  NK-1100-1172: DeltaV Data Collector Utility Quick Start Installation and Usage Guide .  Incident Number

TFSB123246/ TFS437288

De Descript script ion

In DeltaV Live an alarm list with actively changing alarms is causing performance issues on the workstation. 

TFSB147919/  A faceplate pinning feature feature has been added to DeltaV Live. TFS440598

Reference Reference KBA

Not Applicable NK-1900-1222: DeltaV Live Faceplate Pinning and

Page 46 of 56 

 

Incident Number

De Descript script ion

Reference Reference KBA Replacement 

TFSB148645

Opening a module in Control Studio Online may take 1-8 minutes.

NK-1900-1179: Opening Module In Control Studio Online Takes 1-8 Minutes  

TFSB157917

In DeltaV Live the Writes Selection parameter on some GEMs is broken after DeltaV_1431_WS_02_CSS is installed.

Not Applicable

TFSB159306

DeltaV Live exits when opening a large number of faceplates.

Not Applicable

In DeltaV Live the memory usage of the OeWeb.exe TFSB159311

3.2.2.18

process is not being released, causing it to eventually become very high.

Not Applicable

DeltaV_1431_WS_02_CSS

DeltaV_1431_WS_02_CSS DeltaV_1431_WS_02_CS S addressed the following issues: Note: This bundle includes DeltaV Data Collector software version DDC_590. The DDC software is located in the DeltaV\DVData folder. For more information refer to KBA KBA  NK-1100-1172: DeltaV Data Collector Utility Quick Start Installation and Usage Guide .  Incident

De Descript script ion

Reference Reference KBA

Number

TFSB8199/ TFS415437 TFSB91113/ TFS432971

Certain analog gem watch areas do not work.  

Not Applicable

Tool tips for trending parameters block a trend object.

Not Applicable

TFSB94438/

Publishing a display causes DeltaV Live application to become

TFS434171

sluggish.

TFSB95484/

Not Applicable

DeltaV Live named set changes are not captured properly.

Not Applicable

TFSB119838/ TFS436883

Equipment Module command changes are not captured by DeltaV Live.

Not Applicable

TFSB121390

Graphics Studio closes unexpectedly when shapes are renamed from the Configuration Pane.

Not Applicable

TFSB121955/ TFS437127

In certain situations, DeltaV Live is not updating with published publ ished data from Graphics Studio.

Not Applicable

TFSB123612

 A combination of copying copying and pasting displays causes Graphics Studio to quit unexpectedly.

Not Applicable

TFS434283

TFSB126020

Connector with arrow causes Graphics Studio to quit unexpectedly.

Not Applicable

TFSB126760

Secondary click chart builder menu sometimes opens in the wrong region of DeltaV Live.

Not Applicable

TFSB132012/ TFS403248

Hover and Context menu overlap on high performance GEMs.

Not Applicable

TFSB134761

Acknowledge all is incorrectly evaluating which alarms require

Not Applicable

Page 47 of 56 

 

Incident Number

De Descript script ion

Reference Reference KBA

electronic signatures. TFSB135488/ TFS439666

DeltaV Live Web Server is leaking memory.

Not Applicable

TFSB138128

Incident # TFSB138128 OOB Import utility may quit unexpectedly in atypical situations.

Not Applicable

OOB Import Utility can be closed too easily in the middle of TFSB138129

running a task.

Not Applicable

TFSB139004/ TFS440671

Detail display write parameters are not writing.

Not Applicable

TFSB143156

Navigation bar is sometimes not visible after importing a layout.

Not Applicable

TFSB143799

3.2.2.19

Some display frame borders in OOB layouts are larger than their screens.

Not Applicable

DeltaV_1431_WS_01_CSS

DeltaV_1431_WS_01_CSS DeltaV_1431_WS_01_CS S addressed the following issues: Note: This bundle includes DeltaV Data Collector software version DDC_590. The DDC software is located in the DeltaV\DVData folder. For more information refer to KBA KBA  NK-1100-1172: DeltaV Data Collector Utility Quick Start Installation and Usage Guide .  Incident Number

De Descrip scrip tion

Re Reference ference KBA

Support for Distributed CHARMs on CIOCs in DeltaV v14.3.1.

TFS438667

3.3

Note: This Note:  This is the workstation component of a hotfix that must be installed on all workstations along with the CIOC Hotfix (using DeltaV_1431_CIOC_01_CSS and DeltaV_1431_CIOC2_01_CSS) and Scanner Module Hotfix (using DeltaV_RI_DCSM_01_CSS) to fully support Distributed CHARMs on CIOCs in DeltaV v14.3.1.

NK-1900-1029: DeltaV Distributed CHARMs for CIOCs Software Release Information  

I/O

To download the latest I/O Hotfix Bundles, go to Section Section 2.3.  2.3.   3.3.1

CHARM I/O Card

The latest CHARM I/O Card Hotfix Bundle, DeltaV_1431_CIOC_02_CSS, reflects version 14.3.1.7301 in DeltaV Diagnostics. This hotfix bundle addresses the following issues: Incident Number

TFSB174328

TFSB163932

Descrip Descrip tion

Re Reference ference KBA

CHARM has a BAD OInteg, Hardware Error status, and bad references after being upgraded

NK-2000-0306: CHARMs has a BAD OInteg, Hardware Error status, and bad references after flash upgrade 

Firmware support for CIOC EOL flash chip replacement

NK-2000-0312: Firmware Support for CIOC EOL Flash Chip Replacement 

Page 48 of 56 

 

3.3.1.1 3.3 .1.1 Previou s C CHARM HARM I/O Card H Hotf otf ix Bundl es

3.3.1.1.1

DeltaV_1431_CIOC_01_CSS

CHARM I/O Card flashed with DeltaV_1431_CIOC_01_CSS reflects version 14.3.1.7288 in DeltaV Diagnostics. This hotfix bundle addresses the following issues: Incident Number

Descrip Descrip tion

Re Reference ference KBA

Support for Distributed CHARMs on CIOCs in DeltaV v14.3.1.

TFS438667

Note: This is the CIOC component of a hotfix that must be Flash upgraded to CIOCs along with the Workstation Hotfix (using DeltaV_1431_WS_01_CSS) DeltaV_1431_WS_01_CSS) and Scanner Module Hotfix (using DeltaV_RI_DCSM_01_CSS) DeltaV_RI_DCS M_01_CSS) to fully support Distributed CHARMs on CIOCs in DeltaV v14.3.1. Note:  AO CHARMs CHARMs may report a H Hardware ardware Error status after they are flash upgraded when the CHARM I/O Card is at this revision. The Software Revision shows 'Unsupported' after the upgrade. The behavior can be corrected by reseating the CHARM.

3.3.2

NK-1900-1029: DeltaV Distributed CHARMs for CIOCs Software Release Information  

CHARM I/O Card 2

The latest CHARM I/O Card 2 Hotfix Bundle, DeltaV_1431_CIOC2_02_CSS, reflects version 14.3.1.7301 in DeltaV Diagnostics. This hotfix bundle addresses the following issues: Incident Number

TFSB174328

Descrip Descrip tion

CHARM has a BAD OInteg, Hardware Error status, and bad references after being upgraded

Re Reference ference KBA

NK-2000-0306: CHARMs has a BAD OInteg, Hardware Error status, and bad references after flash upgrade 

Page 49 of 56 

 

3.3.2.1 3.3 .2.1 Previou s CH CHARM ARM I/O Card 2 Hotf ix Bund les

3.3.2.1.1

DeltaV_1431_CIOC2_01_CSS

CHARM I/O Card 2 flashed with DeltaV_1431_CIOC2_01_CSS reflects version 14.3.1.7288 in DeltaV Diagnostics. This hotfix bundle addresses the following issues: Incident Number

Descrip Descrip tion

Re Reference ference KBA

Support for Distributed CHARMs on CIOCs in DeltaV v14.3.1.

TFS438667

Note: This is the CIOC component of a hotfix that must be Flash upgraded to CIOCs along with the Workstation Hotfix (using DeltaV_1431_WS_01_CSS) DeltaV_1431_WS_01_CSS) and Scanner Module Hotfix (using DeltaV_RI_DCSM_01_CSS) DeltaV_RI_DCS M_01_CSS) to fully support Distributed CHARMs on CIOCs in DeltaV v14.3.1. Note:  AO CHARMs CHARMs may report a H Hardware ardware Error status after they are flash upgraded when the CHARM I/O Card is at this revision. The Software Revision shows 'Unsupported' after the upgrade. The behavior can be corrected by reseating the CHARM.  

3.3.3 3.3 .3

NK-1900-1029: DeltaV Distributed CHARMs for CIOCs Software Release Information  

Ethernet I/O Card

The latest Ethernet I/O Card Hotfix Bundle, DeltaV_1431_EIOC_08_CSS, reflects version 14.3.1.7313 in DeltaV Diagnostics. This hotfix bundle addresses the following issues: Incident Number

TFSB300885

Descrip Descrip tion

 Analog Tracking function block no longer responds to interlock conditions after controller switchover

EIOC/PK: Performing downloads results in EIOC reporting alarm EIOC/PK:  ADVISE_ALM= LM= Redundancy: Not Communicating – Secondary TFSB180946  ADVISE_A Network

TFSB182611

TFSB183109

EIOC/PK Controller Controller / All Ethernet/IP Messaging Classes / Redundant: PDTs with either Primary or Secondary Device Network cable removed may results with all its LDTs with permanent BAD OInteg / Signal Data in CS Online until both b oth Networks are reconnected

 Analog Tracking and Discrete Discrete Control Condition blocks gene generated rated Event Chronicle entries report the Composite not the Module

Re Reference ference KBA

NK-2000-0558: Analog Tracking Function Block No Longer Responds to Interlock Conditions after Controller Switchover   NK-1900-1133: Downloads of Other Nodes via DeltaV Explorer Might Trigger the EIOC/PK/SZ Controller to Log the Alarm "Redundancy: Not Communicating – Communicating –   Secondary Network" for 10 Seconds 

NK-2000-0651: PDTs With Redundant Communications May Result To All LDTs With Permanent BAD OInteg and Signal Data In Control Studio With BAD Status   NK-2000-0626: Analog Tracking and Discrete Control Condition Blocks' Generated Event Chronicle Entries Report the Composite Not the Module 

Page 50 of 56 

 

Incident Number

TFSB174704

Descrip Descrip tion

Changing a namedset assigned to condition on DCC block is not reflected in CS online

Re Reference ference KBA

NK-2000-0139: Changing a Named Set Assigned to a Condition on a DCC Block is not Reflected in Control Studio Online 

3.3.3.1 3.3 .3.1 Previou s Ethernet I/O I/O Card Hotfi x Bun dles

3.3.3.1.1

DeltaV_1431_EIOC_07_CSS

Ethernet I/O Card flashed with DeltaV_1431_EIOC_07_CSS reflects version 14.3.1.7305 in DeltaV Diagnostics. This hotfix bundle addresses the following issues: Incident Number

TFSB118967

TFSB138281

TFSB176767

TFSB178632

3.3.3.1.2

Descrip Descrip tion

Re Reference ference KBA

Download can fail after an upload followed by download

NK-1900-0825: Download of PK, MQ, MX, SX, SQ, and SZ Controllers May Fail When the Download Starts at the Same Time as the Upload Completes 

Unresolved References are evaluated as true when wired into discrete inputs even when the value is #IGNORE

NK-1900-1017: Unresolved References are Evaluated as True When Wired into Discrete Inputs Even if the Reference Value is #IGNORE  

EDC Block - Control Studio Online - IGNORE_PV_ACT parameter does not track IGNORE_PV correctly

NK-2000-0427: EDC Block's IGNORE_PV_ACT Parameter is Not Tracking IGNORE_PV Correctly in Control Studio Online 

DeltaV OPC UA Client intermittently missing item READS from the Ovizio OPC UA Server

NK-2000-0491: DeltaV OPC UA Client Intermittently Missing Item READS from a OPC UA Server  

DeltaV_1431_EIOC_06_CSS

Ethernet I/O Card flashed with DeltaV_1431_EIOC_06_CSS reflects version 14.3.1.7296 in DeltaV Diagnostics. This hotfix bundle addresses the following issues: Incident Number

TFSB131251

Descrip Descrip tion

PK and EIOC lose connection to Class 1 Ethernet device when RPI is changed

Re Reference ference KBA

NK-2000-0133: PK Controllers and Ethernet I/O Cards Lose Connection to Class 1 Ethernet Devices When RPI is Changed 

Page 51 of 56 

 

Incident Number

TFSB143825

TFSB94445

Descrip Descrip tion

Simulate - XML save/restore does not work for conditional alarm parameters

Enhanced Control Selector OP_SELECTION Name Set change does not propagate on Download

TFSB139817

TFSB154270

TFSB143955

3.3.3.1.3

PID function block - TR14.3.1 - PV filter does not initialize in itialize during a simulate restore

PID function blocks - TR14.3.1 - PV filter is incorrect executing even when PID function block is in Out Of Service mode

Simulate - temporary variables in expressions are not saved and restored during XML operations but are during DAT operations

Re Reference ference KBA

NK-2000-0120: Known Issues in Save/Restore to XML-format on v14.3 and v14.LTS DeltaV SimulatePro  NK-1900-0718: Partial Download Does Not Update OP_SELECTION Parameter Configured Name Set on Enhanced Control Selector Function Block  

NK-2000-0120: Known Issues in Save/Restore to XML-format on v14.3 and v14.LTS DeltaV SimulatePro  NK-2000-0120: Known Issues in Save/Restore to XML-format on v14.3 and v14.LTS DeltaV SimulatePro  NK-2000-0120: Known Issues in Save/Restore to XML-format on v14.3 and v14.LTS DeltaV SimulatePro 

DeltaV_1431_EIOC_05_CSS

Ethernet I/O Card flashed with DeltaV_1431_EIOC_05_CSS reflects version 14.3.1.7291 in DeltaV Diagnostics. This hotfix bundle addresses the following issues: Incident Number

TFSB91137

Descrip Descrip tion

Output bump for 1 module scan due to Modbus TCP\IP - Buffered Write

Re Reference ference KBA

NK-1900-1004: Modbus TCP Write on Device Reconnection with EIOC or PK Controllers  NK-1900-0544: Enhanced Device Control Function Block Parameters Bumps to Zero One Scan after a Controller Switchover  

TFSB97679

EDC function block's status (CMD_D and OUT_D) bumps to zero for one scan after a controller switchover

TFSB134779

Controllers can lose communications to other nodes due to a deadlock condition

NK-1900-1052: Controllers May lose Communications to Other Nodes Due to a Deadlock Condition  

TFSB112281

Controller resets when running batch phases simultaneously

NK-1900-1035: Controller Resets When Running Batch Phases Simultaneously 

3.3.3.1.4

DeltaV_1431_EIOC_04_CSS

Ethernet I/O Card flashed with DeltaV_1431_EIOC_04_CSS reflects version 14.3.1.7289 in DeltaV Diagnostics. This hotfix bundle addresses the following issues:

Page 52 of 56 

 

Incident Number

TFS440185

3.3.4

Descrip Descrip tion

Controller can briefly lose connection to other nodes on o n the system when many CIOCs are assigned

Re Reference ference KBA

NK-1900-1006: Controller Can Briefly Lose Connection to Other Nodes on the System when Many CIOCs  Are Assigned  

Remot e I/O Card Zone 1

This KBA will be updated as Remote I/O Card Zone 1 hotfix bundle becomes available.   3.3.5

Remot e I/O Card Zone 2

This KBA will be updated as Remote I/O Card Zone 2 hotfix bundle becomes available.   3.3.6 3.3 .6

Wireless I/O Card

The latest Wireless I/O Card Hotfix Bundle, DeltaV_1431_WIOC_02_CSS, reflects version 14.3.1.7293 in DeltaV Diagnostics This hotfix bundle addresses the following issues Incident Number

TFSB132164

3.4

Descrip Descrip tion

Re Reference ference KBA

NK-1900-0913: DSN19005-4 - Linux Kernel Vulnerabilities with DeltaV WIOC, Emerson Smart Firewall, Security Information & Event Management (SIEM), Network Security Monitoring (NSM), and System Health Monitor (SHM) 

WIOC Linux TCP Handling

Safety Safety Logic Log ic Solver

For more information and to download the latest Safety Logic Server hotfix bundle, refer to KBA  KBA  AP-0800-0154: AP-0800-0154: DeltaV Safety Instrumented Systems (SIS) Software Updates . Refer to the ReadMe file for the installation instructions.

3.5

Independent DeltaV DeltaV Domain Contro ller ll er

Standalone hotfix DeltaV_1431_B180903_IDDC addressed the following issues: Incident Number

TFSB8705/ TFS420306 

TFSB180903

De Descrip scrip tion

Re Reference ference KBA

DeltaV security issue.

Not Applicable

NTP on IDDC node is not configured to get the time from the Master Time Server (or even from the ProPlus).

NK-2000-0311: IDDC Node is Not Configured to Synchronize the Time from the DeltaV NTP Master Time Server  

Page 53 of 56 

 

Contact Information

Services are delivered through our global services network. To contact your Emerson local service provider, click click   Contact Us.. To contact the Global Service Center, click  Us click  Technical Support Support.. 

Link  Download the Sigcheck tool: Click This Link  To get information on how to use the Sigcheck tool: Click This Link  Link 

DCS  | Lifecycle Services  Related products and services: DeltaV DCS

Complete Article Revision History: Revision/Pu blish

De Description scription of Revision

 Added ded Delt aV_1431_WS_21_CSS as Tar Target get ed Di Dist st ri bu tio n b un dl e. Moved Delt aV_1431_WS_20_CSS to 13 Jul 2021   Ad

23 Jun 2021 15 Jun 2021 18 May 2021 13 May 2021 11 May 2021 29 Apr 2021 31 Mar 2021 30 Mar 2021 10 Mar 2021 04 Mar 2021 04 Feb 2021 09 Dec 2020 12 Nov 2020 30 Oct 2020

General Maintenance Maintenance bu ndle.  Ad ded Delt aV_1431_TFSB437235_BHServ er i n Sect io n 2.2 and 3.2.1.4  Added  Ad ded Delt aV_1431_WS_20_CSS as Tar geted Dist ri bu ti  Added tion on bu nd le. Mov ed Del taV_1431_WS_19_CSS to General Maintenance Maintenance bu ndle. DeltaV_1431_CTRL_P_05_CSS, DeltaV_1431_CTRL_Q_06_CSS, DeltaV_1431_CTRL_SZ_06_CSS, DeltaV_1431_CTRL_PK_09_CSS, DELTAV_1431_RIOZ1_01_CSS installer checksums were updated due to changes in r eadme files.  Added  Ad ded Delt aV_1431_CIOC_03_CSS aV_1431_CIOC_03_CSS,, Delt aV_1431_CIOC2_03_CSS aV_1431_CIOC2_03_CSS,, DeltaV_1431_EIOC_09_CSS Delta V_1431_EIOC_09_CSS,, DeltaV_1431_  Delta V_1431_  WIOC_03_CS WIOC _03_CSS, S, DeltaV_1431 DeltaV_1431_RIOZ _RIOZ1_01_C 1_01_CSS SS and DeltaV_143 DeltaV_1431_RIO 1_RIOZ2_01 Z2_01_CSS _CSS as targ eted dis tri bu tio n bundles.  Added  Ad ded Delt aV_CTRL_P_05_CSS, DeltaV_1431_CTRL_Q_06_CSS, Delt aV_CTRL_SZ_06_CSS and DeltaV_CT DeltaV _CTRL_PK_ RL_PK_09_ 09_CSS CSS a as s t argeted di stri butio n b undl es.  Added  Ad ded in form fo rmati ati on abo ut Targ Targeted eted and Gener General al Main ten tenanc anc e Dis tr ib ut io n in i n Sec 1. Ad ded Sec 2.6 and DeltaV_14 DeltaV _1431_ 31_WS_ WS_19_ 19_CSS CSS as targeted distr ibuti on bund le.  Added  Ad ded in form fo rmati ati on and rec om ommen men dat io n in i n r efer enc e to Del taV_1431_WS_18_CSS pul l o out ut in Secti on 1.1 Pulled-out DeltaV DeltaV_14 _1431_ 31_WS WS_18 _18_CS _CSS S due to an on going investig ation  Added  Ad ded ref eren ce KB A fo r TFSB168184  Added  Ad ded Delt aV_1431_WS_18_CSS  Added  Ad ded so ftw are u upd pd ate li nk an d i nf or mat io n fo r Del taV_1431_WS_17_CSS  Added  Ad ded so ftw are u upd pd ate li nk an d i nf or mat io n fo r Del taV_1431_WS_16_CSS  Added  Ad ded so ftw are u upd pd ate li nk an d i nf or mat io n fo r Del taV_1431_WS_15_CSS.  Added  Ad ded Delt aV_1431_WS_14_CSS ho tf ix bu nd le an and d ad added ded an Imp or tan t no te in Secti on 2.2.

Page 54 of 56 

 

02 Oct 2020 22 Sep 2020 02 Sep 2020 27 Aug 2020 26 Aug 2020 13 Aug 2020 04 Aug 2020 31 Jul 2020 23 Jul 2020 15 Jul 2020 03 Jul 2020 08 Jun 2020 05 Jun 2020 22 Apr 2020 08 Apr 2020 23 Mar 2020 20 Mar 2020 14 Feb 2020 06 Feb 2020 30 Jan 2020 22 Jan 2020 07 Jan 2020 19 Dec 2019 18 Dec 2019 12 Dec 2019 10 Dec 2019 31 Oct 2019 04 Oct 2019 30 Aug 2019

 Ad ded Delt aV_1431_EIOC_08_CS  Added aV_1431_EIOC_08_CSS, S, DeltaV_1431_CTRL DeltaV_1431_CTRL_SZ_05_CSS, _SZ_05_CSS, DeltaV_1431_CTRL_PK_08_CSS, DeltaV_1431_CTRL_Q_ DeltaV_1431 _CTRL_Q_05_CS 05_CSS, S, and DeltaV_1431_C DeltaV_1431_CTRL_P_0 TRL_P_04_CSS 4_CSS.. Added not e in Sect ion 2.2 in ref erence t o NK-2000-0654  Added  Ad ded Delt aV_1431_WS_13_CSS aV_1431_WS_13_CSS.. Add ed n not ot e in Sec ti tion on 2.2, 3.2.3.1, 3. 3.2.3.2 2.3.2 and 3.2.3.3 in ref eren ce to NK2000-0623.  Added  Ad ded Delt aV_1431_WS_12_CSS  Ad ded no te in Secti on 2 in ref eren ce to NK-2000-0514. Ad ded no te in  Added i n Sect io n 3.2.3.1 fo forr TFSB12052/TFS TFSB1205 2/TFS40922 409227 7 in r eferenc e to A K-1900-000 K-1900-0002. 2. Updated K BA r eferenc e of TFS443353 TFS443353 in Section 3.2. 3.2.1. 1.  Added  Ad ded Delt aV_1431_B180903_IDDC in Sec ti tion on 2.5 and Sec ti tion on 3.5. Add ed not n ot e fo r v 14.3.1 Lon g Term Ter m Sup po rt (LTS). Added Del taV_143 taV_1431_TF 1_TFSB158919 SB158919_BHServer _BHServer i n Secti on 2.2 and Sectio n 3.2.2.1. 3.2.2.1.  Added  Ad ded Delt av_1431_WS_11_CSS  Added  Ad ded Delt aV_1431_EIOC_07_CSS Pulled-out DeltaV DeltaV_14 _1431_ 31_WS WS_10 _10_CS _CSS S due to an on goin g in vestigatio n  Added  Ad ded Delt aV_1431_WS_10_CSS aV_1431_WS_10_CSS.. Deleted I/O Release Ind epen dent den t h ot fi fix x llin in ks an d rrefer efer us ers i ns tead to K BA NK-2000NK-20 00-019 0197 7 fo r these l inks. Updated Section 2.2 - added warning on i nstallatio n o f DeltaV_ DeltaV_143 1431_W 1_WS_0 S_07_C 7_CSS SS or later  Added  Ad ded Delt aV_1431_CTRL_P_03_CSS, DeltaV_1431_CTRL_Q_04_CSS, Delt aV_1431_CTRL_PK_07_CSS and DeltaV_1431_CTRL_SZ_04_CSS  Added  Ad ded Delt aV_1431_WS_09_CSS  Added  Ad ded SOA_Gatew ay_1431_TFS338729  Ad ded Delt aV_1431_WS_08_CSS  Added aV_1431_WS_08_CSS,, Delt aV_1431_CIOC_02_CSS, Delt aV_1431_CIOC2_02_CSS, aV_1431_CIOC2_02_CSS, and DeltaV_1431_WIOC_02_CSS  Added  Ad ded Delt aV_1431_WS_07_CSS and Delt aV_RI_RAIAO_02_CSS  Added  Ad ded Delt aV_RI_CIO_10_CS aV_RI_CIO_10_CSS S  Added  Ad ded Delt aV_1431_WS_06_CSS  Added  Ad ded Delt aV_1431_EIOC_06_CSS  Added  Ad ded Delt aV_1431_WS_05_CSS and Delt aV_RI_DCSM_02_CSS  Added  Ad ded Delt aV_RI_L1AIA O_05_CSS  Ad ded Delt aV_1431_CTRL_P_02_CSS, DeltaV_1431_CTRL_Q_03_CSS, Delt aV_1431_CTRL_SZ_03_CSS,  Added DeltaV_1431_CTRL_PK_06_CSS and DeltaV_1431_EIOC_05_CSS. Updated PK controller hotfix bundle file names to match the name shown in Programs and Features. There is no need to reinstall the bundle if it is already installed. Corrected issue resolved for DeltaV_1431_CTRL_PK_05_CSS  Added  Ad ded Delt aV_1431_WS_04_CSS  Added  Ad ded Delt aV_1431_WS_03_CSS  Ad ded Delt aV_1431_CTRL_PK_05_CSS, Delt aV_1431_CTRL_Q_02_CSS, DeltaV_1431_CTRL_SZ_02_CSS  Added DeltaV_1431_CTRL _SZ_02_CSS and DeltaV_1431_EIOC_04_CSS  Added  Ad ded Delt aV_1431_WS_02_CSS  Ad ded Delt aV_1431_WS_01_CSS  Added aV_1431_WS_01_CSS,, DeltaV_1431_CIOC_01_CSS, DeltaV_1431_CIOC2_01_CSS and DeltaV_RI_DSCM_01_CSS Original Release of Article

Page 55 of 56 

 

©Emerson Automation Solutions 2009-2021. All rights reserved. For Emerson Automation Solutions trademarks and service marks , click this link to see trademarks.  trademarks. All other marks are properties of their respective owners. The contents of this publication are presented for informational purposes only, and while diligent effort has been made to ensure their accuracy, they are not to be construed as warrantees or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are governed by our terms and conditions, which are available on request. We reserve the right to modify or improve the design or specification of such products at any time without notice.

View Emerson Products and Services: Click This Link

 

Page 56 of 56 

View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF