NFPA 72E-1990

February 20, 2017 | Author: César Augusto Ortiz Rincón | Category: N/A
Share Embed Donate


Short Description

Download NFPA 72E-1990...

Description

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR ANSI/NFPA 72E permission An American August 17, [email protected]. 1990 AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written of NFPA. ForNational inquires or toStandard report unauthorized use, contact

I

I

I

I

I

I

I

I

I

I

I

NFPA 72F Automatic Fire r)etectors 1990 Fdition

,!

i/'

m

Customer ID

45634151

mm

NFPA ~ National Fire Protection Association 1 Batterymarch Park, PO Box 9101, Quincy, MA 02269-9101

I

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

NOTICE All questions or other communications relating to this document should be sent only to NFPA Headquarters, addressed to the attention of the Committee responsible for the document. For information on the procedures for requesting Technical Committees to issue Formal Interpretations, proposing Tentative Interim Amendments, proposing amendments for Committee consideration, and appeals on matters relating to the content of the document, write to the Secretary, Standards Council, National Fire Protection Association, 1 Batterymarch Park, P.O. Box 9101, Quincy, MA 02269-9101. A statement, written or oral, that is not processed in accordance with Section 16 of the Regulations Governing Committee Projects shall not be considered the official position of NFPA or any of its Committees and shall not be considered to be, nor be relied upon as, a Formal Interpretation. Users of this document should consult applicable Federal, State and local laws and regulations. NFPA does not, by the publication of this document, intend to urge action which is not in compliance with applicable laws and this document may not be construed as doing so.

Policy Adopted by NFPA Board of Directors on December 3, 1982 The Board of Directors reaffirms that the National Fire Protection Association recognizes that the toxicity of the products of combustion is an important factor in the loss of life from fire. NFPA has dealt with that subject in its technical committee documen'ts for many years. •There is a concern that the growing use of synthetic materials may produce more or additional toxic products of combustion in a fire environment. The Board has, therefore, asked all NFPA technical committees to review the documents for which they are responsible to be sure that the documents respond to this current concern. To assist the committees in meeting this request, the Board has appointed an advisory committee to provide specific guidance to the technical committees on questions relating to assessing the hazards of the products of combustion.

Licensing Provision - - This document is copyrighted by the National Fire Protection Association (NFPA).

1. Adoption by Reference - - Public authorities and others are urged to reference this document in laws, ordinances, regulations, administrative orders or similar instruments. Any deletions, additions and changes desired by the adopting authority must be noted separately. Those using this method are requested to notify the NFPA (Attention: Secretary, Standards Council) in writing of such use. The term "adoption by reference" means the citing of title and publishing information only. •.~ 2. Adoption by Transcription - - A. Public authorities with lawmaking or rule-making powers;dnly, upon written notice to the NFPA (Attention: Secretary, Standards Council), will be granted a royalty-free license to print and republish this document in whole or in part, with changes and additions, if any, noted separately, in laws, ordinances, regulations, administrative orders or similar instruments having the force of law, provided that: (1) due notice of NFPA's copyright is contained in each law and in each copy thereof; and, (2) that such printing and republication is limited to numbers sufficient to satisfy the jurisdiction's lawmaking or rulemaking process. B. Once this NFPA Code or Standard has been adopted into law, all printings of this document by public authorities with lawmaking or rulemaking powers or any other persons desiring to reproduce this document or its contents as adopted by the jurisdiction in whole or in part, in any form, upon written request to NFPA (Attention: Secretary, Standards Council), will be granted a nonexclusive license to print, republish, and vend this document in whole Or in part, with changes and additions, if any, noted separately provided that due notice of NFPA's copyright is contained in each copy. Such license shall be granted only upon agreement to pay NFPA a royalty. This royalty is required to provide funds for the research and development necessary to continue the work of NFPA and its volunteers in continually updating and revising NFPA standards. Under certain circumstances, public authorities with lawmaking or rulemaking powers may apply for and may receive a special royalty when the public interest will be served thereby. 3. Scope of License Grant - - The terms and conditions set forth above do not extend to the index to this document. ' (For further explanation, see the Policy Concerning the Adoption, Printing and Publication of NFPA Documents which is available upon request from the NFPA.)

Statement on NFPA Procedures This material has been developed under the published procedures of the National Fire Protection Association, which are designed to assure the appointment of technically competent Committees having balanced representation. While these procedures assure the highest degree of care, neither the National Fire Protection Association, its members, nor those participating in its activities accepts any liability resulting from compliance or noncompliance with the provisions given herein, for any restrictions imposed on materials or processes, or for the completeness of the text. NFPA has no power or authority to police or enforce compliance with the contents of this document and any certification of products stating compliance with requirements of this document is made at the peril of the certifier. SC AM-90

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

MORGAN TECHNICALUBRARY NATIONALRRE PROTECTIONASSN. BATTERYMARCHPARK QUINCY, MA 02269

Copyright © 1990 NFPA, All Rights Reserved l

NFPA 72E Standard on

A u t o m a t i c Fire D e t e c t o r s 1990 Edition

This edition of NFPA 72E, Standard on Automatic Fire Detectors, was prepared by the Technical Committee on Detection Devices, released by the Correlating Committee on Signaling Systems, and acted on by the National Fire Protection Association, Inc. at its Annual Meeting held May 21-24, 1990 in San Antonio, TX. It was issued by the Standards Council on July 20, 1990, with an effective date of August 17, 1990, and supersedes all previous editions. T h e 1990 edition of'this document has been approved by the American National Standards Institute. Changes other than editorial are indicated by a vertical rule in the margin of the pages on which they appear. These lines are included as an aid to the user in identifying changes from the previous edition.

Origin and Development of NFPA 72E This standard was written to assist in the proper use of automatic fire detectors. Technology has produced a large n u m b e r of devices that respond to some p h e n o m e n o n of fire. To operate effectively, these devices must be located properly within the protected space. There are various types of fires - - fast or slow, flaming or smoldering -- but each is a specific product of the type and form of fuel on which it feeds and the physical size and shape of the space in which it starts. An automatic fire detector should be selected after identification of both the type and size of fire to be detected and the response required. These detectors should be located in that space so that they are properly responsive to these fires. The Committee recognizes the need for additional fire research. The Fire Detection Institute (FD1) is expected to perform these needed tasks. The current edition of this standard is based on the best information known to date. The standard will be refined as results and additional information are received and studied. The first edition of this standard was submitted and adopted as a tentative standard in May 1972. The standard was adopted as an official standard in 1974. The 1978 edition contained a complete revision of Chapter 4, "Smoke Sensing Fire Detectors," a new Chapter 6, "Gas Sensing Fire Detectors," and other revisions. In 1982, a new table, "Fable 3-5.1.2, addressing spacing of heat detectors on. high ceilings, was added. In the 1984 edition, Chapter 9 was completely revised to cover the use of detectors in air duct systems and to provide guidance in correlation with NFPA 90A, Standard for the hlstallation of Air Conditioning and Ventilating Systems, on the use of detectors for control of smoke spread. Also, NFPA 72E-M was incorporated into NFPA 72E as new AppendiX C.

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

72E- 1

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-2

AUTOMATICFIRE DETECTORS

The new material is the result of data developed by the Fire Detection Institute as a guide to spacing of heat detectors on other than 15-ft ceilings. The 1987 edition was a complete rewrite of the standard. Many of the changes were for clarification. Appendix C was expanded to include tables used to analyze an existing heat detection system. The 1990 edition of NFPA 72E is a partial revision of this standard. The major change was a total revision and expansion of Chapter 5, "Flame Sensing Fire Detectors."

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

COMMI'Iq'EE PERSONNEL

72E-3

Committee on Signaling Systems 'Correlating Committee Patrick E. Phillips, Chairman U.S. bept. of Energy Richard P. Bielen, Secretary National Fire Protection Association (Nonvoting) Richard G. Bright, Mt. Airy, MD Irving Mande, Edwards Co. Inc. James C. Roberts, NC Dept. of Insurance

Dean K. Wilson, Industrial Risk Insurers Evan E. Stauffer, Jr., Naval Facilities Engineering Command

Technical Committee on Detection Devices James c. Roberts, Chairman NC Dept. of Insurance Joseph A. Drouin, Secretary Simplex Time Recorder Co. (Rep NEMA) Jack L. Abbott, Factory Mutual Research Corp. Brooks H. Baker III, University of Alabama at Birmingham Rep AHA R i c h a r d W. Bukowski, C e n t e r for Fire Research John M. Cholin, Firetek Corp. Ralph E. Collins, R. E. Collins Assoc. Donald A. Diehl, Alison Control Inc. Kenneth W. Dungan, Professional Loss Control Inc. C. Burton Ford, James M. Castle Inc. Rep FSSA Robert Hall, R. A. Hall and Associates Edward Hartfik, IRM Insurance Gregory S. Kelly, Automatic Sprinkler Corporation of America Rep NFSA James T. King, The Protectowire Co. Robert L. Langer, Ansul Fire Protection Rep FEMA

Dewey W. Lewis, Lewis Fire Equipment Inc. Rep NAFED Wayne D. Moore, Mass Fire Alarms of New England Rep AFAA Paul E. Patty, Underwriters Laboratories Inc. Patrick E. Phillips, U.S. Dept. of Energy Edward P. Reid, E. P. Reid Inc. Martin H. Reiss, The Gamewell Corp. Walter Schuchard, Electro Signal Lab. Robert Sears, Winegardner & Hammons Inc. Rep. AHMA J. Brooks Scruple, Smoke/Fire Risk Mgmt. Inc. Rep T/C Air Conditioning Timothy M. Soverino, Nantucket Fire Dept., MA Rep. IMSA Jeffrey L. Steplowski, U.S. Veterans Admin. Ralph E. Transue, Rolf Jensen & Associates Inc. Frank L. Van Overmeiren, FP&C Consuhants. Inc. Dean K. Wilson, Industrial Risk Insurers Alternates

Mark E. Agar, Fire Equipment Co. Inc. (Alternate to D. W. Lewis) Douglas S. Erickson, American Hospital Association (Alternate to B. H. Baker Iii)

Tate Gabbert, Sarasota Fire Department, FL Rep. AFAA (Alternate to W. D. Moore) Raymond A. Grill, RolfJensen & Assoc. Inc. (Alternate to R. E. Transue)

t 990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-4

AUTOMATIC FIRE DETECTORS Miguel G. Lopez, U.S. Veterans A d m i n . (Ahernate to J. L. Steplowski) Robert J. Pielow, FP&C C o n s u l t a n t s Inc. (Alternate to F. L. Van O v e r m e i r e n ) W i l l i a m W. R o g e r s , U n d e r w r i t e r s Laboratories Inc. (Alternate to P. E. Patty)

Robert C. Savery, Fenwal Inc. (Alternate to J. A. Drouin) A n d r e a s Scheidweiler, C e r b e r u s Ltd (Alternate to M. H. Reiss) T h o m a s D. Stilwell, Walter Kidde Co. (Alternate to R. L. Langer)

R i c h a r d P. Bielen, NFPA Staff Liaison This list represents the membership at the time the Committee was balloted on the text of thi.~ edition. Since that time, changes in the membership may have occurred.

NOTE: Membership on a Conmlittee shall not in and of itself constitute an endorsement of the Association o r ;lily document developed by the Committee on which the member serves.

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

t

CONTENTS

72E-5

Contents Chapter 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 P u r p o s e . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2 S c o p e . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Chapter 2 2-1 2-2 2-3 2-4 2-5 2-6 2-7

Common Requirements . .. . . . . . . . . . . . . . . . . . . . . . . . . . . General ........................................... Classification of Fire Detectors ............................ Shapes of Ceilings .................................... Ceiling Surfaces ...................................... Approval .......................................... Acceptance Test ...................................... Installation .........................................

Chapter 3 3-1 3-2 3-3 3-4 3-5

Heat Sensing Fire Detectors . . . . . . . . . . . . . . . . . . . . . . . . . ................................................. Operating Principles .................................. Temperature Classification .............................. Location ........................................... Spacing ...........................................

Chapter 4 4-1 4-2 4-3 4-4 4-5 4-6

Smoke Sensing Fire Detectors . . . . . . . . . . . . . . . . . . . . . . . . General ........................................... Principles of Detection ................................. Classification ........................................ Location and Spacing .................................. Heating, Ventilating, and Air Conditioning (HVAC) ............. Special Considerations .................................

Chapter 5 5-1 5-2 5-3 5-4 5-5 5-6

Flame Sensing Fire Detectors . . . . . . . . . . . . . . . . . . . . . . . . General ........................................... Definitions and Operating Principles ....... ................ Fire Characteristics and Detector Selection ................... Spacing Considerations ................................. Field of View Considerations ............................. Other Considerations ...................................

Chapter 6 6-1 6-2 6-3 6-4 6-5

Gas Sensing Fire Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . ............................... .................. Operating Principles .................................. Location and Spacing-. ................................. Heating, Ventilating, and Air Conditioning (HVAC) ............. Special Considerations .................................

Other Fire Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1 .......................... ' ....................... 7-2 Fire Characteristics ................................... 7-3 Location and Spacing .................................. 7-4 Special Considerations .................................

72E72E72E-

7 7 7

72E72E72E72E72E72E72E72E-

7 7 8 8 8 9 9 9

72E-10 72E-10 72E-10 72E-10 72E-11 72E-11 72E-12 72E-12 72E-12 72E-12 72E-12 72E-14 72E-14 72E-15 72E-15 72E-15 72E-16 72E-16 72E-17 72E-17 72E-17 72E-17 72E-18 72E-18 72E-18 72E-18

Chapter 7

72E-19 72E-19 72E-19 72E-19 7 2 E - 19

Chapter 8

72E-19 72E-19 72E-20 72E-20 72E-21 72E-21 72E-21

8-1 8-2 8-3 8-4 8-5 8-6

Inspections, Tests, and Maintenance . . . . . . . . . . . . . . . . . . . General ........................................... Initial Installation Inspection and Tests ...................... Periodic Inspection and Tests ............................ Detector Maintenance .................................. T e s t s F o l l o w i n g E x p o s u r e to F i r e C o n d i t i o n s . . . . . . . . . . . . . . . . . . Inspection Forms .....................................

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-6

AUTOMATIC FIRE DETECTORS

Chapter 9 9-1 9-2 9-3 9-4 9-5

Smoke Detectors for Control of Smoke Spread . . . . . . . . . . . . . General ........................................... Purposes .......................................... Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Location a n d Installation o f D e t e c t o r s in Air Duct Systems . . . . . . . . . S m o k e D e t e c t o r s for D o o r Release Service . . . . . . . . . . . . . . . . . . . .

Chapter 10

Referenced Publications ...........................

72E-22 72E-22 72E-22 72E-22 72E-22 72E-23 72E-25

Appendix A .............................................

72E-25

Appendix B

Spacing and Sensitivity . . . . . . . . . . . . . . . . . . . . . . . . . . .

72E-44

Appendix C

G u i d e f o r A u t o m a t i c Fire Detector S p a c i n g . . . . . . . . . . . . .

72E-44

Appendix D

Referenced Publications .........................

Index ................................................

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

72E-132 72E-133

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-7

INTRODUCTION/COMMON REQUIREMENTS

Chapter 2

NFPA 72E Standard on

A u t o m a t i c Fire D e t e c t o r s 1990 Edition NOTICE: An asterisk(*) following the number or letter designating a paragraph indicates explanatory material on that paragraph in Appendix A. Information on referenced publications can be found in Chapter l0 and Appendix D.

Chapter 1

Introduction

1-1 Purpose. 1-1.1 T h e purpose of this standard is to provide basic m i n i m u m requirements for the performance of automatic fire detectors to ensure timely warning for the purposes of life safety and property protection. 1-1.2 This standard is intended for use by persons knowledgeable in the application of fire detection as part of fire protection systems.

1-2 Scope. 1-2.1 This standard covers m i n i m u m performance, location, mounting, testing, and maintenance requirements of automatic fire detectors for protection of the occupant, building, space, structure, area, or object to be protected in accordance with the stated purpose. 1-2.2 This standard is intended to be used with other NFPA standards that deal specifically with fire alarm, extinguishment, or control. Automatic fire detectors add to fire protection by initiating emergency action, but only where used in conjunction with other equipment. 1-2.3 The interconnection of detectors, the control conf i g u r a t i o n s , the power supply, or the o u t p u t systems r e s p o n d i n g to a u t o m a t i c fire d e t e c t o r a c t u a t i o n are J detailed in NFPA 71, Standard for the Installation, Mainte-

Common Requirements

2-1 General. Fire is a p h e n o m e n o n that occurs when a substance reaches a critical temperature and reacts chemically with oxygen (for example) to produce heat, flame, light, smoke, water vapor, carbon monoxide, carbon dioxide, or other products and effects. An automatic fire detector is a device designed to detect the presence of fire and initiate action. 2-1.1 Definitions.

Approved. Acceptable to the "authority having jurisdiction." NOTE: The National Fire Protection Association does not approve, inspect or certify any installations, procedures, equipment, or materials nor does it approve or evaluate testing laboratories. In determining the acceptability of installations or procedures, equipment or materials, the authority having jurisdiction may base acceptance on compliance with NFPA or other appropriate standards. In the absence of such standards, said authority may require evidence of proper installation, procedure or use. The authority having jurisdiction may also refer to the listings or labeling practices of an organization concerned with product evaluations which is in a position to determine compliance with appropriate standards for the current production of listed items.

Authority Having Jurisdiction. The "authority having j u r i s d i c t i o n " is the o r g a n i z a t i o n , office or i n d i v i d u a l responsible for "approving" equipment, an installation or a procedure. NOTE: The phrase "authority having jurisdiction" is used in NFPA documents in a broad manner since jurisdictions and "approval" agencies vary as do their responsibilities. Where public safety is primary, the "authority having jurisdiction" may be a federal, state, local or other regional department or individual such as a fire chief, fire marshal, chief of a fire prevention bureau, labor department, health department, building official, electrical inspector, or others having statutory authority. For insurance purposes, an insurance inspection department, rating bureau, or other insurance company representative may be the "authority having jurisdiction." In many circumstarices the property owner or his designated agent assumes the role of the "authority having jurisdiction"; at government installations, the commanding officer or departmental official may be the "authority having jurisdiction." Ceiling. The upper surface of a space, regardless of height. Areas with a suspended ceiling would have two ceilings, one visible from the floor and one above the sus= pended ceiling.

nance, and Use of Signaling Systemsfor Central Station Service, NFPA 72, Standard for the Installation, Maintenance and Use of Protective Signaling Systems, NFPA 74, Standard for the Installation, Maintenance, and Use of Household Fire Warning Equipment, and others.

Ceiling Height. The height from the continuous floor of the room to the continuous ceiling of a room or space.

1-2.4 Nothing in this standard is intended to prevent the use of new methods or devices provided sufficient technical data are submitted to the authority having jurisdiction to demonstrate that the new method or device is equivalent in quality, effectiveness, durability, and safety to that prescribed by this standard.

Combination Detector. A device that either responds to more than one of the fire p h e n o m e n a classified i n 2-2.1.1 through 2-2.1.5, or employs more than one operating principle to sense one of these p h e n o m e n a . Typical examples are a combination of heat detector with smoke detector or a combination rate-of-rise and fixed temperature heat detector.

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-8

AUTOMATIC FIRE DETECTORS

Labeled. Equipment or materials to which has been attached a label, symbol or other identifying mark of an organization acceptable to the "authority having jurisdiction" and concerned with product evaluation, that maintains periodic inspection of production of labeled equipment or materials and by whose labeling the manufacturer indicates compliance with a p p r o p r i a t e standards or performance in a specified manner. Listed. Equipment or materials included in a list published by an organization acceptable to the "authority having jurisdiction" and concerned with p r o d u c t evaluation, that maintains periodic inspection of production of listed equipment or materials and whose listing states either that the equipment or material meets a p p r o p r i a t e standards or has been tested and found suitable for use in a specified manner. NOTE: The means for identifying listed equipment may vary for each organization concerned with product evaluation, some of which do not recognize equipment as listed unless it is also labeled. The "authority having jurisdiction" should utilize the system employed by the listing organization to identify a listed product. Shall.

2-2.2.2 Spot-type Detector. A device whose detecting elem e n t is c o n c e n t r a t e d at a p a r t i c u l a r location. Typical examples are bimetallic detectors, fusible alloy detectors, certain p n e u m a t i c rate-of-rise detectors, certain smoke detectors, and thermoelectric detectors. 2-2.2.3 Air Sampling-type Detector. A s a m p l i n g - t y p e detector consists of piping or tubing distribution from the detector unit to the area(s) to be protected. An air p u m p draws air from the protected area back to the detector through the air sampling ports and piping or tubing. At the detector, the air is analyzed for fire products.

2-2.3 Operating Modes. 2-2.3.1 Nonrestorable Detector. A device whose sensing e l e m e n t is designed to be d e s t r o y e d by the process of detecting a fire. 2-2.3.2 Restorable Detector. A device whose sensing element is not ordinarily destroyed by the process of detecting a fire. Restoration may be manual or automatic.

Indicates a mandatory requirement.

2-3 Shapes of Ceilings. Should. Indicates a recommendation or that which is advised but not required.

Spacing.

A horizontally m e a s u r e d linear dimension relating to the allowable coverage of fire detectors.

2-2 Classification of Fire Detectors. 2-2.1 For the p u r p o s e o f this standard, automatic fire detectors are classified as listed below. 2-2.1.1 Heat Detector. A device that detects abnormally high temperature or rate-of-temperature rise. 2-2.1.2 Smoke Detector. A device that detects the visible or invisible particles of combustion. 2-2.1.3 Radiant Energy Sensing Fire Detector. A device that detects radiant energy (ultraviolet, visible, or infrared radiation) that is emitted as a p r o d u c t of combustion reaction and obeys the laws of optics.

2-2.1.3.1 Flame Detector.

See 5-2.1.4.

2-2.1.3.2 Spark/Ember Detector. 2-2.1.4 Fire-Gas Detector. p r o d u c e d by a fire.

See 5-2.1.7.

A device that detects gases

2-2.1.5 Other Fire Detectors. Devices that detect a phen o m e n o n other than heat, smoke, flame, or gases produced by a fire.

2-2.2 Types of Detectors. 2-2.2.1 Line-type Detector. A device in which detection is continuous along a path. Typical examples are rate-ofrise pneumatic tubing detectors, projected beam smoke detectors, and heat-sensitive cable.

2-3.1

T h e shapes of ceilings are classified as follows.

2-3.1.1 Level Ceilings. Those that are actually level or have a slope of I I/2 in. (40 mm) or less p e r ft (0.3 m). 2-3.1.2 Sloping Ceilings. Those having a slope of more than 11/2 in. (40 mm) p e r ft (0.3 m). Sloping ceilings are further classified as follows: (a) Sloping-Peaked Type. T h o s e in which the ceiling slopes in two directions from the highest point. Curved or d o m e d ceilings may be considered peaked with the slope figured as the slope of the chord from highest to lowest point. (See Figure A-3-5.4.1.) (b) Sloping-Shed Type. Those in which the high point is at one side with the slope e x t e n d i n g toward the opposite side. (See Figure A-3-5.4.2.)

2-4 Ceiling Surfaces. 2-4.1 Ceiling surfaces referred to in conjunction with the locations of fire detectors are: 2-4.1.1 Beam Construction. Ceilings having solid structural or solid n o n s t r u c t u r a l m e m b e r s p r o j e c t i n g down from the ceiling surface more than 4 in. (100 ram) and spaced more than 3 ft (0.9 m), center to center. 2-4.1.2 Girders. Girders s u p p o r t beams or joists and run at right angles to the beams or joists. Where girders are within 4 in. (100 ram) of the ceiling, they are a factor in d e t e r m i n i n g the n u m b e r of detectors and are to be considered as beams. Where the top of the girder is more than 4 in. (100 mm) from the ceiling, it is not a factor in detector location. 2-4.1.3 Solid Joist Construction. Ceilings haying solid structural or solid nonstructural members projecting down

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-9

COMMON REQUIREMENTS

from the ceiling surface a distance of more than 4 in. (100 ram) and spaced at intervals 3 ft (0.9 m) or less, center to center. 2-4.1.4 Smooth Ceiling. A surface u n i n t e r r u p t e d by continuous projections, such as solid joists, beams, or ducts, extending more than 4 in. (100 mm) below the ceiling surface. NOTE: Open truss constructions are not considered to impede the flow of fire products unless the upper member in continuous contact with the ceiling projects below the ceiling more than 4 in. (100 mm).

[ 2-5 Approval. [ 2-5.1 All fire detection devices shall be listed or a p p r o v e d for the p u r p o s e for which they are intended and shall be installed in conformity with this standard. [ 2-5.1.1" All fire detection devices that receive their power from the initiating circuit of a fire alarm control unit shall be listed for use with the control unit. Where acceptable to the authority having jurisdiction, the manufacturer may provide information on the compatibility of the detection device with the control unit to satisfy this requirement. [ 2-5.1.2 Where required by the authority having jurisdiction, complete information r e g a r d i n g the fire detectors, including specifications and floor plans showing the location of the detectors, shall be submitted for approval prior to installation of the detectors. ] 2-5.1.3 Before requesting approval of the installation by the authority having jurisdiction, the installing contractor shall furnish a written statement to the effect that the detectors have been installed in accordance with a p p r o v e d plans and tested in accordance with Chapter 8 of this standard. Manufacturers' installation and service manuals shall also be furnished. [2-6 Acceptance Test. Upon completion of the installation, a satisfactory test of the fire detectors in accordance with Chapter 8 of this standard shall be made in the presence of a representative of the authority having jurisdiction.

] 2-7 Installation. ]2-7.1 W h e r e subject to mechanical d a m a g e , detectors shall be protected. [ 2-7.2 Detectors shall be supported, in all cases, independently of their attachment to the circuit conductors.

J 2-7.3

Detectors shall not be recessed in any way into the mounting surface unless they have been tested and listed for such recessed mounting.

]2-7.4 Detectors shall be installed in all areas w h e r e required by the a p p r o p r i a t e NFPA standard or the authority having jurisdiction. Each installed detector shall be

accessible for periodic maintenance and testing. Where total coverage is required, this shall include all rooms, halls, storage areas, basements, attics, lofts, spaces above suspended ceilings, and other subdivisions and accessible spaces, and inside all closets, elevator shafts, enclosed stairways, d u m b w a i t e r shafts, and chutes. Inaccessible areas that contain combustible material shall be made accessible and protected by detector(s).

Exception No. 1: Detectors may be omitted from combustible blind spaces where any of the following conditions prevail. (a) Where the ceiling is attached directly to the underside of the supporting beams of a combustible roof or floor deck. (b) Where the concealed space is entirely filled with a noncombustible insulation. In solid joist construction, the insulation need fill only the space from the ceiling to the bottom edge of the joist of the roof or floor deck. (c) Where there are small concealed spaces over rooms ~rovided any space in question does not exceed 50 sq fi (4. 6m ) in area. (d) In spaces formed by sets of facing studs or solid joists in walls, floors, or ceilings where the distance between the facing studs or solid joists is less than 6 in. (150 mm). Exception No. 2: Detectors may be omitted from below open grid ceilings where all of the following conditions prevail. (a) The openings of the grid are 1/4 in. (6.4 mm) or larger in the least dimension. (b) The thickness of the material does not exceed the least dimension. (c) The openings constitute at least 70 percent of the area of the ceiling material. 2-7.5* Detectors shall also be required u n d e r n e a t h open loading docks or platforms and their covers, and for accessible underfloor spaces of buildings without basements.

Exception: By permission of the authority having jurisdiction, detectors may be omitted when all of the following conditions prevail. (a) The space is not accessiblefor storage purposes or entrance of unauthorized persons and is protected against accumulation of windborne debris. (b) The space contains no equipment such as steam pipes, electric wiring, shafting, or conveyors. (c) The floor over the space is tight. (d) No flammable liquids are processed, handled, or stored on the floor above.

] 2-7.6

Where codes, standards, laws, or authorities having jurisdiction require the protection of selected areas only, the specified areas shall be protected in accordance with this standard.

[ 2-7.7* Duplicate terminals or leads, or equivalent, shall be provided on each automatic fire detector for the express p u r p o s e of connecting into tile fire alarm system to provide supervision o f the connections. Such terminals or leads are necessary to ensure that the wire run is broken and that the individual connections are made to the incoming and outgoing leads or other terminals for signaling and power.

Exception:

Detectors that provide

• equivalent supeTvision.

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E- 10

Chapter 3

AUTOMATIC FI RE DETECTORS

Heat Sensing Fire Detectors

3-1 Heat is a d d e d energy that causes substances to rise in t e m p e r a t u r e as well as the energy p r o d u c e d by a b u r n i n g substance.

3-1.1 General. 3.1.1.1 T h e p u r p o s e and scope of this chapter are to provide standards for location and spacing of fire detectors that sense heat p r o d u c e d by b u r n i n g substances. T h e detectors are usually refei'red to as heat detectors. 3-1.1.2 Heat detectors, shall be installed in all areas where required either by the a p p r o p r i a t e NFPA standard or the authority having jurisdiction.

3-2 Operating Principles.

3-2.2 Rate Compensation Detector. 3-2.2.1 A rate compensation detector is a device that will respond when the t e m p e r a t u r e of the air s u r r o u n d i n g the device reaches a p r e d e t e r m i n e d level, regardless of the rate of t e m p e r a t u r e rise. 3-2.2.2 A typical example is a spot-type detector with a tubular casing of a metal that tends to e x p a n d lengthwise as it is heated and an associated contact mechanism that will close at a certain point in the elongation. A second metallic element inside the tube exerts an opposing force on the contacts, tending to hold them open. T h e forces are balanced in such a way that, on a slow rate of t e m p e r a t u r e rise, there is more time for heat to penetrate to the inner element, which inhibits contact closure until the total device has been heated to its rated t e m p e r a t u r e level. However, on a fast rate of t e m p e r a t u r e rise, there is not as much time for heat to penetrate to the inner element, which exerts less of an inhibiting effect so that contact closure is obtained when the total device has been heated to a lower level. This, in effect, compensates for thermal lag.

3-2.1 Fixed Temperature Detector. 3-2.3 Rate.of-Rise Detector. 3-2.1.1 A fixed t e m p e r a t u r e detector is a device that will respond when its operating element becomes heated to a p r e d e t e r m i n e d level. 3-2.1.2 T h e r m a l Lag. When a fixed t e m p e r a t u r e device operates, the t e m p e r a t u r e of the s u r r o u n d i n g air will always be higher than the operating t e m p e r a t u r e of the device itself. This difference between the o p e r a t i n g temperature of the device and the actual air t e m p e r a t u r e is commonly spoken of as thermal lag, and is proportional to the rate at which the t e m p e r a t u r e is rising. 3-2.1.3 Typical examples of fixed t e m p e r a t u r e sensing elements are: (a) Bimetallic. A sensing element comprised of two metals having different coefficients o f t h e r m a l e x p a n s i o n arranged so that the effect will be deflection in one direction when heated and in the opposite direction when cooled. (b) Electrical Conductivity. A line-type or spot-type sensing element whose resistance varies as a function of temperature. (c) Fusible Alloy. A sensing element of a special compo, sition (eutectic) metal, which melts rapidly at the rated temperature. (d) Heat-Sensitive Cable. A line-type device whose sensing element comprises, in one type, two current-carrying wires held separated by a heat-sensitive insulation that softens at the rated temperature, thus allowing the wires to make electrical contact. In another type, a single wire is centered in a metallic tube and the intervening space is filled with a substance that, at a critical t e m p e r a t u r e , becomes conductive, thus establishing electrical contact between the tube and the wire.

(e) Liquid Expansion. A sensing element comprising a liquid capable of marked expansion in volume in response to temperature increase.

3-2.3.1 A rate-of-rise detector is a device that will respond when the t e m p e r a t u r e rises at a rate exceeding a predetermined amount. 3-2.3.2 Typical examples are: (a) Pneumatic Rate-of-Rise Tubing. A line-type detector comprising small diameter tubing, usually copper, which is installed on the ceiling or high on the walls t h r o u g h o u t the detected area. T h e tubing is terminated in a detector unit containing d i a p h r a g m s and associated contacts set to actuate at a p r e d e t e r m i n e d pressure. T h e system is sealed except for calibrated vents that compensate for normal changes in temperature. (b) Spot-type Pneumatic Rate-of-Rise Detector. A device consisting of an air chamber, d i a p h r a g m , con.tacts, and compensating vent in a single enclosure. T h e principle of operation is the same as that described in 3-2.3.2(a). (c) Thermoelectric Effect Detector. A device whose sensing element comprises a thermocouple or thermopile unit that produces an increase in electric potential in response to an increase in temperature. This potential js monitored by associated control equipment, and an alarm is initiated when the potential increases at an abnormal rate. (d) Electrical Conductivity Rate-of-Change Detector. A linetype sensing element whose resistance changes due to a change in temperature. T h e rate of change of resistance is monitored by associated control equipment, and an alarm is initiated when the rate of increase exceeds a preset value.

3-3 Temperature Classification. 3-3.1 Heat detectors of the f i x e d - t e m p e r a t u r e or ratecompensated spot-pattern type shall be classified as to the t e m p e r a t u r e of operation and marked with the a p p r o p r i ate color code. (See Table 3-3.1.) 3-3.1.1 Where the overall color of a detector is the same as the color code marking required for that detector, either one of the following arrangements, applied in a contrasting color and visible after installation, shall be employed:

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

HEAT SENSING FIRE DETECTORS (a) A ring on the surface of the detector. (b) T h e temperature rating in numerals at least 3/8 in. (9.5 mm) high. Table 3-3.1

Temperature Classification Low* Ordinary Intermediate High Extra High Very Extra High Ultra High

Temp. Rating Max.Ceiling Range °F Temp. °F 100 to 135 to 175 to 250 to 325 to 400 to 500 to

134 174 249 324 399 499 575

20 belowt 100 150 225 300 375 475

Color Code Uncolored Uncolored White Blue Red Green Orange

*Intended only for installationin controlledambientareas. Unitsmarked to indicatemaximumambientinstallationtemperature. tMaximum ceiling temperature has to be 20°F or more below detector rated temperature. NOTE: The difference between the rated temperature and the maximum ambient should be as small as possible to minimize the response time. For SI Units: °C = 5/9 (°F-32).

3-4 Location. 3-4.1" Spot-type heat detectors shall be located on the ceiling not less than 4 in. (100 ram) from the side wall or on the side walls between 4 in. (100 ram) and 12 in. (300 mm) from the ceiling. (See Figure A-3-4.1.)

Exception No. 1 :~ In the case of solid joist construction, detectors shall be mounted at the bottom of the joists. Exception No. 2: In the case of beam construction where beams are less than 12 in. (300 mm) in depth and less than 8 fi (2.4 m) on center, detectors may be installed on the bottom of beams. 3-4.2

Line-type heat detectors shall be located on the ceiling or on the side walls not more than 20 in. (500 mm) from the ceiling.

3-4.3 High-Temperature Areas.

Detectors having fixed t e m p e r a t u r e or rate c o m p e n s a t e d e l e m e n t s shall be selected in accordance with Table 3-3.1 for the maximum ceiling temperature that can be expected.

3-5 Spacing. 3-5.1" Smooth Ceiling Spacing. One of the following rules shall apply. (a) T h e distance between detectors shall not exceed their listed spacing, and there shall be detectors within a distance of one-half the listed spacing, measured at a right angle, from all walls or partitions extending to within 18 in. (460 mm) of the ceiling; or (h) All points on the ceiling shall have a detector within a distance equal to 0.7 times the listed spacing. This will be useful in calculating locations in corridors or irregular areas. 3-5.1.1" Irregular Areas. For irregularly shaped areas, the spacing between detectors may be greater than the listed spacing, provided the m a x i m u m spacing from a detector to the farthest point of a side wall or corner within its zone of protection is not greater than 0.7 times the listed spacing (0.7S). (See Figure A-3-5.1.1.)

72E-11

3-5.1.2" High Ceilings.

On ceilings 10 ft (3 m) to 30 fi (9.1 m) high, heat detector linear spacing shall be reduced in accordance with Table 3-5.1.2. Table 3-5.1.2

Above

Up To

Percent of Listed Spacing

0 10 12 14 16 18 20 22 24 26 28

10 12 14 16 18 20 22 24 26 28 30

100 91 84 77 71 64 58 52 46 40 34

Ceiling Height fit)

For Sl Units: 1 ft = 0.305 in.

Exception: Table 3-5.1.2 does not apply to the following detectors, which rely on the integration effect. (a) Line-type electrical conductivity detectors. [See 3-2.1.3(b).1 (b) Pneumatic rate-of-rise tubing. [See 3-2.3.2(a).] (c) Series connected thermoelectric effect detectors. [See 3-2.3.2(c).] In these cases, the manufacturer's recommendations shall be followed for appropriate alarvn point and spacing. NOTE: Table 3-5.1.2 provides for spacing modifications to take into account different ceiling heights for generalized fire conditions. An alternative design method, which allows a designer to take into account ceiling height, fire size, and ambient temperature, is provided in Appendix C.

3-5.2* Solid Joist Construction. T h e spacing of heat detectors, when measured at right angles to the solid joists, shall not exceed 50 percent of the smooth ceiling spacing allowable u n d e r 3-5.1 and 3-5.1.1. (See Figure A-3-5.2.) 3-5.3* Beam Construction. It shall be t r e a t e d as a smooth ceiling if the beams project no more than 4 in. (100 mm) below the ceiling. If the beams project more than 4 in. (100 ram) below the ceiling, the spacing of spot-type heat detectors at right angles to the direction of beam travel shall be not more than two-thirds the smooth ceiling spacing allowable u n d e r 3-5.1 and 3-5.1.1. If the beams project more than 18 in. (460 ram) below the ceiling, and are more than 8 fi (2.4 m) on centers, each bay formed by the beams shall be treated as a separate area.

3-5.4 Sloped Ceilings. 3-5.4.1" Peaked. A row of detectors shall first be spaced and located at or within 3 ft (0.9 m) of the peak of the ceiling, measured horizontally. T h e n u m b e r and spacing of additional detectors, if any, shall be based on the horizontal projection of the ceiling in accordance with the type of ceiling construction. (See Figure A-3-5.4.1.) 3-5.4.2" Shed. The shed shall have a row of detectors located on the ceiling within 3 ft (0.9 m) of the high side of the ceiling measured horizontally, spaced in accordance

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-12

A U T O M N I ' I C FIRE DETECTORS

with the type of construction. Remaining detectors, if any, shall then be located in the remaining area on the basis of the horizontal projection of the ceiling. (See Figure

A-3-5.4.2.) 3-5.4.3 For a roof slope of less than 30 degrees, all detectors will be spaced utilizing the height at the peak. For a roof slope of greater than 30 degrees, the average slope height will be used for all detectors other than those located in the peak.

tosensitive sensor. When smoke particles enter the light path, some of the light is scattered by reflection and refraction onto the sensor, causing the detector to respond. 4-2.2.1 Photoelectric light scattering detection is more responsive to visible (size more-than one micron) particles produced by most smoldering fires. It is somewhat less responsive to the smaller particles typical of most flaming fires. It is also less responsive to black smoke. 4-2.2.2 Smoke detectors utilizing the light scattering principle are usually of the spot type.

Chapter 4

S m o k e S e n s i n g Fire D e t e c t o r s

4-1.1" The purpose of this chapter is to provide information to assist in the design and installation of reliable early warning smoke detection systems for protection of life and property.

4-2.3* Photoelectric Light Obscuration Smoke Detection. In a photoelectric light obscuration smoke detector, the loss of light transmission between a light source and a photosensitive sensor is monitored. When smoke particles are introduced in the light path, some of the light is scattered and some absorbed, thereby reducing the light reaching the receiver, causing the detector to respond.

4-1.2 This chapter covers general area application of smoke detectors in ordinary indoor locations.

4.2.3.1 The response of photoelectric light obscuration smoke detectors is usually not affected by the color of smoke.

4-1.2.1 For information on use of smoke detectors for control of smoke spread, refer to Chapter 9 of this standard.

4-2.3.2 Smoke detectors utilizing the light obscuration principle are usually of the line type. These detectors are commonly called projected beam smoke detectors.

4-1.2.2 For additional guidance in the application of smoke detectors for flaming fires of various sizes and growth rates in areas of various ceiling heights, refer to Appendix C, Section C-5.

4-2.4 Cloud Chamber Smoke Detection. A smoke detector utilizing the cloud chamber principle is usually of the sampling type. An air p u m p draws a sample of air from the protected areas into a high humidity chamber within the detector. After the humidity of the sample has been raised, the pressure is lowered slightly. If smoke particles are present, the moisture in the air condenses on them, forming a cloud in the chamber. The density of this cloud is then measured by a photoelectric principle. When the density is greater than a predetermined level, the detector responds.

4-1 General.

4-1.3" Smoke detectors shall be installed in all areas where required either by the appropriate NFPA standard or by the authority having jurisdiction.

4-2 Principles of Detection. 4-2.1 Ionization Smoke Detection. An ionization smoke detector has a small amount of radioactive material that ionizes the air in the sensing chamber, thus rendering it conductive and permitting a current flow through the air between two charged electrodes. This gives the sensing chamber an effective electrical conductance. When smoke particles enter the ionization area, they decrease the conductance of the air by attaching themselves to the ions, causing a reduction in mobility. When the conductance is less than a predetermined level, the detector responds. 4-2.1.1 Ionization detection is more responsive to invisible (size less than one micron) particles produced by most flaming fires. It is somewhat less responsive to the larger particles typical of most smoldering fires. 4-2.1.2 Smoke detectors utilizing the ionization principal are usually of the spot type.

4-2.2* Photoelectric Light Scattering Smoke Detection. In a photoelectric light scattering smoke detector, a light source and a photosensitive sensor are so arranged that the rays from the light source do not normally fall on the pho-

4-3 Classification. 4-3.1 Spot-type Smoke Detectors. S p o t - t y p e s m o k e detectors shall be marked with their normal production sensitivity (percent per foot obscuration), measured as required by the listing. The production tolerance around the normal sensitivity shall also be indicated. 4-3.1.1 Smoke detectors that have provision for field adjustment of sensitivity shall have an adjustment range of not less than 0.6 percent/ft obscuration, and the adjusting means shall be marked to indicate its nominal factory calibration position.

4-4 Location and Spacing. 4-4.1" General. T h e location and spacing o f smoke detectors shall result from an evaluation based on engineering j u d g m e n t supplemented by the guidelines detailed in this standard. Ceiling shape and surfaces, ceiling height, configuration of contents, burning characteristics of combustible material present, and ventilation are some of the conditions that shall be considered.

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

SMOKE SENSING FIRE D E T E C T O R S

4-4.1.1 Where the intent is to protect against a specific hazard, the detector(s) may be installed closer to the hazard in a position where the detector will readily intercept the smoke. 4-4.1.2" Stratification. T h e possible effect of smoke stratification at levels below the ceiling shall also be considered. 4-4.2* Spot-type Smoke Detectors. S p o t - t y p e s m o k e detectors shall be located on the ceiling not less than 4 in. (100 mm) from a sidewall to the near edge or, if on a sidewail, between 4 in. and 12 in. (100 mm and 300 mm) down from the ceiling to the top of the detector. (See Figure

points on the ceiling shall have a detector within a distance equal to 0.7 times the selected spacing. This will be useful in calculating locations in corridors or irregular areas. (See A-3-5. I and Figure A-3-5.1.1.) For irregt, larly shaped areas, the spacing between detectors may be greater than the selected spacing, provided the m a x i m u m spacing from a detector to the furthest point of a sidewall or corner within its zone of protection is not greater than 0.7 times the selected spacing (0.7S). (See Figure A-3-5.1.1.)

4-4.5.2* Projected Beam-type Detectors.

For location and spacing of projected beam-type detectors, the manufacturer's installation instructions shall be followed. (See

A-3-4.1.)

Figure A-4-4.5.2.)

Exception No. 1: See 4-4.1.2. Exception No. 2: See 4-4.6. Exception No. 3: See 4-4.7.

4-4.6* Solid Joist Construction.

4-4.2.1" To minimize dust contamination of smoke detectors where installed u n d e r raised room floors and similar spaces, they shall only be m o u n t e d in an orientation for which they have been listed (see Figure A-4:4.2.1).

4-4.3 Projected Beam-type Smoke Detectors. Projected beam-type smoke detectors (see 4-2.3.1) shall normally be located with their projected beams parallel to the ceiling and in accordance with the manufacturer's instructions.

Exception No. 1: See 4-4.1.2. Exception No. 2: Beams may be installed vertically or at any angle needed to afford protection of the hazard involved. (Exampie: vertical beams through the open shaft area of a stairwell where there is a clear vertical space inside the handrails.) 4-4.3.1 T h e beam length shall not exceed the m a x i m u m permitted by the equipment listing. 4-4.3.1.1" Where mirrors are used with projected beams, they shall be installed in accordance with the nmnufacturer's recommendations. 4-4.3.1.2 T h e detector installation shall comply with the requirements contained in the listing.

7 2 E - 13

4-4.6.1 Ceiling construction where joists are 8 in. (200 mm) or less in depth shall be considered equivalenl to a smooth ceiling. Spot-type detectors shall be mounted on the bottom of the joists. (Also see 4-4.1.2.) 4-4.6.2 If joists exceed 8 in. (200 ram) in depth, the spacing of spot-type detectors in the direction p e r p e n d i c u l a r to the joists shall be reduced by onc-third. If the projected light beams of line-type detectors run p e r p e n d i c u l a r to the joists, no spacing reduction is necessary; however, if the projected light beanas are parallel to the.joists, thc spacing between light beams shall be reduced. Spot-type dctcctors shall be m o u n t e d on the bottom of the joists. (Also see

4-4.1.2.)

4-4.7 Beam Construction. 4-4.7.1 Ceiling construction where beams are 8 in. (200 ram) or less in depth shall be considered equivalent to a smooth ceiling. (Also see 4-4.1.2.) 4-4.7.2 If beams are over 8 in. (200 ram) in depth, the spacing of spot-type detectors in the direction perpendicular to the beams shall be rcduced. T h e spacing of projected light beam detectors run perpendicularly to the ceiling beams need not be reduced; however, if the projected light beams are run parallel to the ceiling beams, the spacing shall be reduced. (Also see 4-4.1.2.)

4-4.4 Sampling-type Smoke Dectector. Each sampling port of a sampling-type smoke detector shall be treated as a s p o H y p e detector for the p u r p o s e of location a n d spacing.

4-4.7.3 If beams are less than 12 in. (304 nun) in depth and less than 8 ft (2.4 m) on center, spot-type detectors shall be permitted to be installed on the bottom of beams.

4-4.5 Smooth Ceiling Spacing.

4-4.7.4* If the beams exceed 18 in. (460 ram) in depth and are more than 8 ft (2.4 in) on centers, each bay shall be treated as a separate area requiring at least one spottype or projected beam-type detector.

4-4.5.1 Spot-type Detectors. On smooth ceilings, spacing of 30 ft (9.1 m) may be used as a guide. In all cases, the manufacturer's recommendations shall be followed. Other spacing may be used d e p e n d i n g on ceiling height, dift~rent conditions, or response requirements. (See Appendix C for

detection of flaming fires. ) 4-4.5.1.1 W h e r e a specific spacing is selected by the authority having jurisdiction, by engineering j u d g m e n t , by Appendix C, or by another method for smooth ceilings, all

4-4.8 Sloped Ceilings. 4-4.8.1 P e a k e d . D e t e c t o r s shall first be s p a c e d a n d located within 3 ft (0.9 m) of the peak, measured horizontally. The n u m b e r and spacing of additional detectors, if any, shall be based on the horizontal projection of the ceiling. (See Figu,re A-3-5.4.1.)

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E- 14

AUTOMATIC FIRE DETECTORS

4-4.8.2 Shed. Detectors shall first be spaced and located within 3 ft (0.9 m) of the high side of the ceiling, measured horizontally. T h e n u m b e r and spacing of additional detectors, if any, shall be based on the horizontal projection of the ceiling. (See Figure A-3-5.4.2.) 4-4.9 Raised Floors and Suspended Ceilings. In underfloor spaces and above ceiling spaces that are not HVAC plenums, detector spacing shall be in accordance with Seeuon 4-4. 4-4.10 Partitions. W h e r e partitions extend u p w a r d to within 18 in. (460 ram) of the ceiling, they will not influence the spacing. Where the partition extends to within less than 18 in. (460 ram) of the ceiling, the effect of smoke travel shall be considered in reduction of spacing. 4-5 Heating, Ventilating, and Air Conditioning (HVAC). 4-5.1" In spaces served by air handling systems, detectors shall not be located where air from supply diffusers could dilute smoke before it reaches the detectors. Detectors shall be located to intercept the air flow toward the return air opening(s). This may require additional detectors, since placing detectors only near return air openings may leave the balance of the area with inadequate protection when the air handling system is shut down. T h e detector manufacturer shall be consulted before installation of detectors. 4-5.2 In spaces u n d e r floors and above ceiling spaces that are used as HVAC plenums, detectors shall be listed to be compatible with air velocities present. Detector spacings and locations shall be selected based upon anticipated airflow patterns and fire type. 4-5.2.1 Detectors placed in environmental air ducts or plenums shall not be used as a substitute for open area I detectors. (See Chapter 9 and "FableA-4-6.1.4.) Smoke may not be drawn into the duct or plenums when the ventilating system is shut down. Further, when the ventilating system is operating, the detector(s) may be less responsive to a fire condition in the room of fire origin due to dilution by clean air.

4-6 Special Considerations. 4-6.1 General. T h e selection and installation of smoke detectors shall take into consideration both the design characteristics of the detector and the areas into which the detectors will be installed so as to prevent false operation or nonoperation after installation. Some of the considerations are as follows. [4-6.1.1" T h e installation of smoke detectors shall take into consideration the e n v i r o n m e n t a l condition of the area(s). Smoke detectors are intended for installation in areas where the normal ambient conditions are not likely to: (a) Exceed 100°F (38°C) or fall below 32°F (0°C); or (b) Exceed 93 percent relative humidity; or (c) Exceed air velocity of 300 fpm (1.5 mps).

Exception: Detectors .specifically designed for use in ambients exceeding the above limits and listed for the temperature, humidity, and air velocity conditions expected. 14-6.1.2" T o avoid u n w a n t e d a l a r m s , the location o f smoke d e t e c t o r s shall take into c o n s i d e r a t i o n n o r m a l sources of smoke, moisture, dust or fumes, and electrical or mechanical influences. 4-6.1.3 Detectors shall not be installed until after the construction cleanup of all trades is complete and final.

Exception: Where required by the authority having jurisdiction for protection during construction. Detectors that have been installed prior to final cleanup by all trades shall be cleaned or replaced p e r Section 8-4.

4-6.2 Spot-type Detectors. 4-6.2.1 Smoke detectors having a fixed t e m p e r a t u r e element as part of the unit shall be selected in accordance with Table 3-3.1 for the m a x i m u m ceiling t e m p e r a t u r e that can be expected in service. 4-6.2.2* ered by shall be or from entry of

Air holes in the back of a detector shall be cova gasket, sealant, or equivalent, and the detector m o u n t e d so that air-flow from inside the housing the p e r i p h e r y of the housing will not prevent the smoke d u r i n g a fire or test condition.

4-6.3 Projected Beam-type Detectors. 4-6.3.1 Projected beam-type detectors and mirrors shall be firmly m o u n t e d on stable surfaces, so as to prevent false or erratic operation due to movement. T h e beam shall be so designed that small a n g u l a r movements of the light source or receiver do not prevent operation due to smoke and do not cause false alarms. Ordinarily, movement of I/4 degree shall be tolerated (1/2 degree circular included angle). 4-6.3.2 Since the projected beam-type unit will not operate for alarm but will give a trouble signal (see A-4-2.3) when the light-path to the receiver is abruptly i n t e r r u p t e d or obscured, the light-path shall be kept clear of opaque obstacles at all times. 4-6.4* H i g h Rack Storage. (See Figures A-4-6.4(a) and A-4-6.4(b).) Detection systems are often installed in addition to suppression systems. Where smoke detectors are installed for early warning in high rack storage areas, it shall be necessary to consider installing detectors at several levels in the racks to ensure quicker response to smoke. W h e r e detectors are installed to actuate a suppression system, see NFPA 231C, Standard for Rack Storage of Materials.

4-6.5 High Air Movement Areas. 4-6.5.1 General. T h e p u r p o s e and scope of this section are to provide location and spacing guidance for smoke detectors in high air movement areas for early warning of fire.

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

FLAMESENSING FIRE DETECTORS

Exception: Detectorsprovided for the control of smoke spread are covered by the requirements of Chapter 9. [4-6.5.2 A c c e p t a n c e Criteria. Detector response shall be determined by the authority having jurisdiction, which may utilize the detector manufacturer's recommendations. 4-6.5.3 Location. Smoke detectors shall not be located directly in the air stream of supply registers. (See A-4-5.1.) I 4-6.5.4 Spacing. Smoke detector spacing depends upon the movement of air within the room (including both supplied and recireulated air), which can be designated as minutes per air change or air changes per hour. Except where otherwise accepted by the authority having jurisdiction, spacing shall be in accordance with Figures 4-6.5.4(a) and (b). A projected beam smoke detector may be used in place of each row of spot detectors at the reduced spacing.

gO0

i

Z.

--,

600

/

500 40O 3O0 ZOO

i

i

125 250 375 500 625 750 875 900 900 900

For SI Units: 1 sq fi = 0.0929 m'2 Figure 4-6.5.4(b)

Chapter

5

Flame

Sensing

Fire Detectors

5-1 G e n e r a l .

Visible . . . . .

0.35 to 0.75 microns

Infrared . . . .

0.75 to 220 microns

5-1.2 The purpose and scope of this chapter are to provide standards for the selection, location, and spacing of fire detectors that sense the radiant energy produced by b u r n i n g substances. These detectors are categorized as flame detectors and spark/ember detectors.

!

5-2 D e f i n i t i o n s a n d O p e r a t i n g P r i n c i p l e s .

0 MINUTE$//A~R CHANGE I

Sq Ft/Detector

60 30 20 15 12 10 8.6 7.5 6.7 6

U l t r a v i o l e t . . . 0.1 to 0.35 microns

/~ 60

Air Changes/Hour

1 2 3 4 5 6 7 8 9 10

(1.0 micron - 1000 nanometers = 10,000 angstroms)

~00

AiR CHANGE/HOUR

Minutes/Air Change

5-1.1 R a d i a n t E n e r g y . For the purpose of this standard, r a d i a n t energy includes the electromagnetic radiation emitted as a by-product of the combustion reaction that obeys the laws of optics. This includes radiation in the ultraviolet, visible, a n d i n f r a r e d s p e c t r u m emitted by flames or glowing embers. These portions of the spectrum are distinguished by wavelength as follows:

900

700

72E- 15

250

20,

15

12

30

8.6

7.5

6.7

2

$

4

$

6

7

8

9

For SI Units: 1 sq ft = 0.0929 m L

volume of protected space

5-2.1 D e f i n i t i o n s .

5-2.1.1" Ember. A particle of solid material that is emitting radiant energy due either to its temperature or the process of combustion on its surface. (See 5-2.1.6.)

(a) Minutes per air change = cu ft per minute (cfm) of air supplied to the protected space

60 x cu ft per minute (cfm) of air supplied to the protected space (b) Air changes per hour = volume of protected space

NOTE: If a constant air volume system is not used. the maximum available cfm shall be used to determine the number of air changes.

Figure 4-6.5.4(a) High Air MovementAreas. (Not to be used for undertloor or above ceiling spaces.) ~t ~

5-2.1.2 Field of View. The solid cone extending out from the detector within which the effective sensitivity of the detector is at least 50 percent of its on-axis, listed, or approved sensitivity. 5-2.1.3 Flame. A flame is a body or stream of gaseous material involved in the combustion process and emitting radiant energy at specific wavelength bands determined by the combustion chemistry of the fuel. In most cases, some portion of the emitted radiant energy is visible to the h u m a n eye. 5-2.1.4 Flame Detectors. Radiant energy fire detectors that are intended to detect flames and are designed to operate in dark or normally lit environments where sunlight or other ambient lighting is assumed.

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

7 2 E - 16

AUTOMNI'IC FIRE DETECTORS

5-2.1.5 Flame Detector Sensitivity. T h e d i s t a n c e at which the detector will detect a fire of specified size and fuel within a given time frame. 5-2.1.6" Spark.

A moving ember.

5-2.1.7 Spark/Ember Detectors. R a d i a n t e n e r g y fire detectors that are designed to detect sparks, embers, or both. These devices are normally intended to operate in dark environments and operate in the infi'ared part of the spectrum. 5-2.1.8 Spark/Ember Detector Sensitivity. T h e n u m b e r of watts (or fractions of watts) of radiant power from a point source radiator, applied as a unit step signal at the wavelength of maximum detector sensitivity, that are necessary to produce an alarm signal from the detector within the specified response time.

5-2.1.9"

W a v e l e n g t h . All r a d i a n t e n e r g y can be described as a wave having a wavelength, the distance between the peaks of a sinusoidal wave. Wavelength is analogous to color in the visible part of the spectrum and serves as the unit of measure for distinguishing between different parts of the spectrum. Wavelengths are measured in microns (p.), nanometers (nM), or angstroms (~). 5-2.2 Operating Principles of Flame Detectors. 5-2.2.1 Ultraviolet flame detectors typically use a vacuum p h o t o d i o d e Geiger-Muller tube to detect the ultraviolet radiation that is p r o d u c e d by a flame. T h e p h o t o d i o d e allows a burst of c u r r e n t to flow for each ultraviolet photon that hits the active area of the tube. When the n u m b e r of current burst per unit time reaches a p r e d e t e r m i n e d level, either the detector or its control initiates an alarm. 5-2.2.2 A single wavelength infrared flame detector uses one of several different types of photocells to detect the infrared emissions in a single narrow wavelength band that are produced by a flame. These detectors generally include provisions to minimize alarms from commonly occurring infrared sources such as incandescent lighting or sunlight. 5-2.2.3 An ultraviolet/infrared (UV/IR) flame detector senses ultraviolet radiation using a vacuum p h o t o d i o d e tube and a selected wavelength of infrared radiation (usually the 4.35 micron, carbon dioxide band) using a photocell and uses the combined signal to indicate a fire. These detectors require both types of radiation to be present before an alarm signal is rendered.

5-2.2.4 A m u h i p l e wavelength infrared (IR/IR) flame detector senses radiation at two or more narrow bands of wavelengths in the infrared spectrum, using at least one wavelength as a background or reference band (usually the 3.8 micron or 5.6 micron band) and at least one wavelength to sense the flame emissions (usually the 4.35 micron, carbon dioxide band). These detectors compare the emissions between the reference band and the sample band electronically and r e n d e r a signal when the relationship between the two bands indicates a fire.

5-2.3 Operating Principles of Spark/Ember Detectors. 5-2.3.1 A s p a r k / e m b e r sensing detector usually uses a solid state p h o t o d i o d e or phototransistor to sense the radiant energy emitted by embers, typically between 0.5 and 2.0 microns in the visible and infrared portion of the spectrum, in normally dark environments. These detectors can be m a d e e x t r e m e l y sensitive (microwatts), a n d t h e i r response times can be made very short (microseconds).

5-3 Fire Characteristics and Detector Selection. 5-3.1" T h e type and quantity of radiant energy-sensing fire detectors will d e p e n d upon the hazard including the burning characteristics of the fuel, the fire growth rate, the environment, the ambient conditions, and the capabilities of the extinguishing m e d i a and equipment.

5-4 Spacing Considerations. 5-4.1 General Rules. 5-4.1.1" Radiant energy-sensing fire detectors shall be employed consistent with the listing or approval and the inverse square law which defines the fire size vs distance curve for the detector. 5-4.1.2 Detectors shall be used in sufficient quantity and positioned such that no point requiring detection in the hazard area is obstructed or outside the field of view of at least one detector. 5-4.1.3 T h e environment and ambient conditions anticipated in the area to be protected will impact on the choice of detector. All detectors have limitations on the range of ambient temperatures over which they will r e s p o n d consistent with t h e i r tested or a p p r o v e d sensitivities. T h e designer should make certain that the detector is compatible with the range of ambient t e m p e r a t u r e s anticipated in the area in which it is installed. In addition, rain, snow, and ice are all optically opaque at both uhraviolet and infrared wavelengths. Where applicable, provisions should be made to protect the detector from accumulations of these materials on the optical surfaces.

5-4.2 Spacing Considerations for Flame Detectors. 5-4.2.1" T h e location and spacing of detectors shall be the result of an engineering evaluation, taking into consideration: (a) T h e size of the fire that is to be detected. (b) T h e fuel involved. (c) T h e sensitivity of the detector. (d) T h e distance between the fire and the detector. (e) T h e radiant energy absorption of the atmosphere. (t) T h e presence of extraneous sources of radiant emissions. (g) T h e purpose of the detection system. 5-4.2.2 T h e designer shall define the size of the flaming fire of given fuel that is to be detected.

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

GAS SENSING FIRE DETECTORS 5-4.2.3" In applications where the fire to b e detected could occur in an area not on the optical axis of the detector, the distance shall be r e d u c e d or detectors a d d e d to compensate for the angular displacement of the fire in accordance with the manufacturer's recommendations. 5-4.2.4* In applications in which the fire to be detected is of a fuel different than the test fuel used in the process of listing or approval, the distance between the detector and the fire shall be adjusted, consistent with the fuel specificity of the detector as established by the manufacturer. 5-4.2.5 Since flame detectors are essentially line-of-sight devices, special care shall be taken to ensure that their ability to respond to the required area of fire in the zone that is to be protected will not be compromised by the presence of intervening structural members or other opaque objects or materials. 5-4.2.6" In applications where airborne particulates and aerosols coat the detector window d u r i n g intervals between maintenance and affect sensitivity, provisions shall be made to sustain the window clarity.

5-4.3 Spacing Considerations for Spark/Ember Detectors. 5-4.3.1" T h e location .and spacing of detectors shall be the result of an engineering evaluation taking into consideration: (a) T h e size of the spark or ember that is to be detected. (b) T h e fuel involved. (c) T h e sensitivity of the detector. (d) The distance between the fire and the detector. (e) T h e radiant energy absorption of the atmosphere. (t) T h e presence of extraneous sources of radiant emissions. (g) T h e purpose of the detection systems. 5-4.3.2* T h e designer shall define the size of the spark or ember of given fuel that the detection system is to detect. 5-4.3.3 Spark detectors shall be positioned such that all points within the cross section of the conveyance duct, conveyor, or chute where the detectors are located are within the field of view of at least one detector as defined in 5-2.1.2. 5-4.3.4 T h e location and spacing of the detectors shall be adjusted using the inverse square law, modified for the atmospheric absorption and the absorption of n o n b u r n i n g fuel suspended in the air in accordance with the manufacturer's recommendations. (See A-5-4.1.1.) 5-4.3.5" In applications where the sparks to be detected could occur in.an area not on the optical axis of the detector, the distance shall be reduced or detectors a d d e d to compensate for the angular displacement of the fire in accordance with the manufacturer's recommendations. 5-4.3.6* In applications where airborne particulates and aerosols coat the detector window and affect sensitivity, provisions shall be made to, sustain the window clarity.

72E-17

5-5 Field of View Considerations. 5-5.1 Since flame detectors are essentially line-of-sight devices, special care shall be taken to ensure that their ability to respond to the required area of fire in the zone that is to be protected will not be unduly compromised by the p r e s e n c e of i n t e r v e n i n g s t r u c t u r a l m e m b e r s o r o t h e r opaque objects or materials. 5-5.2 T h e overall situation shall be reviewed fi'equently to ensure that changes in structural or usage conditions that could interfere with fire detection capabilities are r e m e d i e d promptly.

5-6 Other Considerations. 5-6.1 Flame detectors shall have such spectral and optical response capabilities that they will initiate action from the specific spectral emission that occurs when the particular fuel(s) of the protected hazard is afire. 5-6.2 Detectors shall be designed, protected, or serviced so that interference with reception of radiation will not Occur, preventing operation. 5-6.3 Where necessary, detectors shall be shielded or otherwise a r r a n g e d to prevent action fi'om unwanted radiant energy. 5-6.4 Where used in o u t d o o r applications, detectors shall be shielded in a fashion to prevent diminishing sensitivity by rain, snow, etc., and yet allow a clear field of vision of the hazard area.

Chapter 6

Gas S e n s i n g Fire D e t e c t o r s

6-1 Gases are molecules without cohesion that are produced by a b u r n i n g substance and are subject to oxidation or reduction.

6-1.1 General. 6-1.1.1" T h e p u r p o s e and scope of this chapter are to provide standards for location and spacing of fire detectors that sense gases p r o d u c e d by burning substances. These detectors are hereafter referred to simply as fire-gas detectors. 6-1.1.2 Fire-gas detectors shall be installed in all areas where required either by the a p p r o p r i a t e NFPA standards or by the authority having jurisdiction. 6-1.1.3 Fire-gas detectors shall respond to one or more of the gases p r o d u c e d by a fire. 6-1.1.4 Although some fire-gas detectors are capable of detecting combustible gases or vapors prior to ignition, such applications are not within the scope of this standard.

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E- 18

AUTOMATIC FIRE DETECTORS

6-2 Operating Principles.

6-3.6 Beam Construction.

6-2.1 Semiconductor. Fire-gas detectors of the semiconductor type respond to either oxidizing or reducing gases by creating electrical changes in the semiconductor. T h e s u b s e q u e n t conductivity c h a n g e of the s e m i c o n d u c t o r causes actuation.

6-3.6.1 Ceiling construction where beams are 8 in. (200 mm) or less in depth shall be considered equivalent to a smooth ceiling. (See also A-4-4.1.2.)

6-2.2 Catalytic Element.

Fire-gas detcctors of the catalytic element type contain a material that, in itself, remains unchanged but accelerates the oxidation of combustible gases. T h e resulting t e m p e r a t u r e rise of the element causes actuation.

6-3.6.2 If beams are over 8 in. (200 mm) in depth, the spacing of spot-type detectors in the direction p e r p e n d i c u lar to the beams shall be reduced. (See also A-4-4.1.2.) 6-3.6.3* If the beams exceed 18 in. (460 mm) in depth and are more than 8 ft (2.4 m) on centers, each bay shall be treated as a separate area requiring at least one spottype detector.

6-3 Location and Spacing. 6-3.7 Sloped Ceilings. 6-3.1" G e n e r a l . T h e location a n d spacing of fire-gas detectors shall result from an evaluation based on engineering j u d g m e n t s u p p l e m e n t e d by the guidelines detailed in this standard. Ceiling shape and surfaces, ceiling height, configuration of contents, burning characteristics of combustible material present, and ventilation are some of the conditions that shall be considered.

6-3.7.1 P e a k e d . D e t e c t o r s shall first be s p a c e d a n d located within 3 ft (0.9 m) of the peak, measured horizontally. T h e n u m b e r and spacing of additional detectors, if any, shall be based on the horizontal projection of the ceiling. (See Figure A-3-5.4.1.)

6-3.1.1 Where the intent is to provide protection from a specific hazard, the detector(s) may be installed closer to the hazard in a position where the detector will readily intercept the fire gases.

6-3.7.2 Shed. Detectors shall first be spaced and located within 3 ft (0.9 m) of the high side of the ceiling, measured horizontally. T h e n u m b e r and spacing of additional detectors, if any, shall be based on the horizontal projection of the ceiling. (See Figure A-3-5.4.2.)

6-3.1.2 Stratification. T h e possible effect of gas stratification at levels below the ceiling shall also be considered. (See

6-3.8 Suspended Ceilings.

(See 2-7.4.)

A-4-4.1.2.) 6-3.2 Spot-type fire-gas detectors shall be located on the ceiling not less than 4 in. (100 mm) from a sidewall to the near edge, or if on a sidewall, between 4 in. and 12 in. (100 mm and 300 mm) down from the ceiling to the top of the detector. (See Figure A-3-4.1.)

Exception No. 1: See 6-3.1.2. Exception No. 2: In the case of solid joist construction, detectors shall be mounted at the bottom of the joists. Exception No. 3: In the case of beam construction where beants are less than 12 in. (300 ram) in depth and less than 8 ft (2.4 m) on center, detectors may be installed on the bottom of beams. 6-3.3* Each sampling p o r t of a sampling-type fire-gas detector shall be treated as a spot-type detector for the purpose of location and spacing.

6-3.4 Smooth Ceiling Spacing. 6-3.4.1 Spot-type Detectors. On smooth ceilings, spacing of 30 ft (9.1 In) may be used as a guide. In all cases, the manufacturer's recommendations shall be followed. Other spacing may be used d e p e n d i n g on ceiling height, varying conditions, or response requirements. 6-3.5 Solid Joist Construction.

(SeeA-4-4.6.)

6-3.9 P a r t i t i o n s . W h e r e partitions e x t e n d u p w a r d to within 18 in. (460 mm) of the ceiling, they will not influence the spacing. Where the partition extends to within less than 18 in. (460 mm) of the ceiling, the effect on gas travel shall be considered in reduction of spacing.

6-4 Heating, Ventilating, and Air Conditioning (HVAC). 6-4.1" In spaces served by air handling systems, detectors shall not be located where air from supply diffusers could dilute fire gases before they reach the detectors. Detectors shall be located to intercept the airflow toward the return air opening(s). 6-4.2 In spaces u n d e r floors and above ceiling spaces used as HVAC plenums, detectors shall be listed to be compatible with air velocities present. Detector spacings and locations shall be selected based on anticipated air-flow patterns and fire types. 6-4.2.1 Detectors placed in environmental air ducts or plenums shall not be used as a substitute for open area detectors. Fire gases may not be drawn into the duct or plenums when the ventilating system is shut down. Further, when the ventilating system is operating, the detector(s) may be less responsive to a fire condition in the room of fire origin due to dilution by clean air. (See Chapter 9 and

6-3.5.1 Ceiling construction in which joists are 8 in. (200 mm) or less in depth shall be considered equivalent to a smooth ceiling. (See also A-4-4.1.2.)

Figure A-4-6.1.1.)

6-3.5.2 If joists exceed 8 in. (200 ram) in depth, the spacing o f spot-type detectors in the direction perpendicular to the joists shall be reduced. (See also A-4-4.1.2.)

6-5.1 T h e selection and installation of fire-gas detectors shall take into consideration both the design characteristics of the detector and the areas into which the detectors will

6-5 Special Considerations.

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

OTHER FIRE DETECTORS/INSPECTIONS,TESTS, AND MAINTENANCE be installed to prevent false operation or n o n o p e r a t i o n after installation. Some of the considerations are as follows. 6-5.1.1 Fire-gas detectors may alarm in nonfire situations due to certain h u m a n activities. T h e use of some aerosol sprays and hydrocarbon solvents are examples. Accordingly, considerable care shall be employed when installing fire-gas detectors. T h e y shall not be installed where, u n d e r normal conditions, concentrations of detectable gases may be present. A garage is not a place to use fire-gas detectors for fire alarm purposes because the concentration of carbon monoxide may be high enough to trigger an alarm. 6-5.1.2 Fire-gas detectors having a fixed t e m p e r a t u r e element as part of the unit shall be selected in accordance with Table 3-3.1 for the m a x i m u m ceiling t e m p e r a t u r e that can be expected in service. 6-5.1.3" T h e installation of fire-gas detectors shall take into c o n s i d e r a t i o n the e n v i r o n m e n t a l condition of the area(s). (See Figure A-4-6.1.1.) Fire-gas d e t e c t o r s a r e intended for installation in areas where the normal ambient conditions are not likely to: (a) Exceed 100°F (38°C) or fall below 32°F (0°C); or (b) Have relative humidity outside the range of 10 to 93 percent; or (c) Exceed air velocity of 300 fpm (1.5 mps).

Exception: l~etectors specificaUy designed for use in ambients exceeding the above limits and listed for the temperature, humidity, and air velocity conditions expected.

Chapter 7

Other Fire Detectors

7-1 Detectors in the classification of "Other Fire Detectors" are those that operate on principles differing from those described in Chapters 3, 4, 5, and 6.

7-1.1 General. 7-1.1.1 Detectors in the classification of " O t h e r Fire Detectors" shall be installed in all areas where they are required either by the a p p r o p r i a t e NFPA standard or by the authority having jurisdiction. 7-1.1.2 Facilities for testing or metering or instrumentation to ensure adequate initial sensitivity and adequate retention thereof, relative to the protected hazard, shall be provided. T h e s e facilities shall be e m p l o y e d at r e g u l a r intervals.

7 2 E - 19

7-2.2 Room sizes and contours, airflow patterns, obstructions, and other characteristics of the protected hazard shall be taken into account.

7-3 Location and Spacing. 7-3.1 T h e location and spacing of detectors shall be based on the principle of operation and an engineering survey of the conditions anticipated in service. T h e manufacturer's technical bulletin shall be consulted for r e c o m m e n d e d detector uses and locations. 7-3.2 Detectors shall not be spaced beyond their listed or a p p r o v e d m a x i m u m s . Closer spacing shall be utilized where the structural or other characteristics of the protected hazard warrant. 7-3.3 Consideration shall be given to all factors with bearing on the location and sensitivity of the detectors, including structural features such as sizes and shapes of rooms and bays, their occupancies and uses, ceiling heights, ceiling and o t h e r obstructions, airflow patterns, stockpiles, files, and fire hazard locations. 7-3.4 T h e overall situation shall be reviewed frequently to assure that changes in structural or usage conditions that could interfere with fire detection are remedied. 7-4 Special Considerations. Conditions that could foster false operation or nonoperation of detectors shall be considered when installation of detectors in this g r o u p is being planned.

Chapter 8

Inspections, Tests, and Maintenance

8-1 General. 8-1.1 Each detector shall be in reliable operating condition. Inspections, tests, a n d maintenance shall be performed. 8-1.2 Inspections, tests, and maintenance p r o g r a m s shall satisfy the requirements of this standard s u p p l e m e n t e d by the manufacturer's instructions.

Exception: Detectorsinstalled to conform with the requirements of NFPA 74, Standard for the Installation, Maintenance, and Use of Household Fire Warning Equipment. 8-1.3 T h e owner or designated representative shall be responsible for inspections, tests, and maintenance. Delegation of authority shall be in writing. 8-1.3.1 T h e owner or designated representative shall be responsible for system alterations and additions.

7-2 Fire Characteristics. 7-2.1 These detectors shall operate when subjected to the abnormal concentration of combustion effects that occur d u r i n g a fire, such as water vapor, ionized molecules, or other p h e n o m e n a for which they are designed. Detection is d e p e n d e n t upon the size and intensity of fire to provide the necessary a m o u n t of required products and related thermal lift, circulation, or diffusion for adequate operation.

8-1.3.2" Service personnel shall be qualified and experienced in the inspection, testing, and maintenance of fire detection devices. 8-1.4 Before testing, people at all points where the alarm signals or reports shall be notified to prevent unnecessary response. At the conclusion of testing, those previously

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-20

A U T O M A T I C FIRE DETECTORS

notified (and others necessary) shall be further notified that testing has been concluded. 8-1.5 Any method or device used for testing in an atmosphere or process classified as hazardous by Article 500 o f NFPA 70, National Electrical Code, ~ shall be suitable for such use. 8-1.6 Records of all inspections, tests, and maintenance shall be kept on the premises for at least five years for review by the authority having jurisdiction. 8-2" Initial Installation Inspection and Tests. 8-2.1 After installation, a visual inspection o f all detectors shall be made to be sure that they are properly located. 8-2.2 After installation, each detector shall be inspected to ensure that it is properly m o u n t e d and connected in accordance with the manufacturer's reconamendations.

8-2.4.1.1" For spot-type or sampling-type detectors, the detectors shall be tested in place to ensure smoke entry into the sensing chamber and an alarm response. Testing with smoke or other aerosol acceptable to the detector manufacturer shall be permitted as one acceptable test method, 8-2.4.1.2 For projected beam-type smoke detectors, the detector shall be tested by introducing smoke, other aerosol, or an optical filter into the beam path. 8-2.5 Radiant E n e r g y - S e n s i n g Fire Detectors. Flame detectors and s p a r k / e m b e r detectors shall be tested in place in accordance with the manufacturer's instructions to d e t e r m i n e that each detector is operative. 8-2.6 Fire-Gas and Other Fire Detectors. Fire-gas detectors and other fire detectors shall be tested for operation in accordance with instructions supplied by the manufacturer or other test methods acceptable to the authority having jurisdiction. 8-3 Periodic Inspection and Tests.

8-2.3 Heat Detectors. 8-2.3.1" A restorable heat detector and the restorable element of a combination detector shall be tested by exposing the detector to a heat source, such as a hairdryer or a shielded heat lamp, until it responds. After each heat test, the detector shall reset. Precaution shall be taken to avoid damage to the nonrestorable fixed t e m p e r a t u r e element of a combination rate-of-rise/fixed t e m p e r a t u r e detector. Exception: A pneumatic tube line-type detector shall be tested either with a heat source (if a test chamber is in the circuit) or tested pneumatically with a pressure pump. The manufacturer's instructions shall be followed. 8-2.3.2 Line- o r spot-type nonrestorable fixed temperature heat detectors shall not be heat tested, but shall be tested mechanically or electrically to verify alarm function. 8-2.3.2.1 Detectors with a replaceable fusible alloy element shall be tested by first removing the fusible element to determine that the detector contacts operate properly and then reinstalling the fusible element. 8-2.3.3 W h e r e r e q u i r e d for p r o p e r p e r f o r m a n c e , the loop resistance of line-type detectors shall be measured to determine if it is within acceptable limits for the e q u i p m e n t being used. T h e loop resistance shall be r e c o r d e d for f u t u r e r e f e r e n c e . O t h e r tests shall be p e r f o r m e d as required by the manufacturers.

8-3.1" Detectors shall be tested as described in the following paragraphs. T h e method of test shall be a s o u t l i n e d in Section 8-2. T h e authority having jurisdiction may require testing at a greater frequency or may accept testing at a lesser frequency. 8-3.2 A visual inspection shall be made at least semiannually to ensure that each detector remains in good physical condition and that there are no changes that would affect d e t e c t o r p e r f o r m a n c e , such as b u i l d i n g modifications, occupancy hazards, and environmental effects. 8-3.3 Heat Detectors. 8-3.3.1 For no'nrestorable spot-type detectors, after the fifteenth year, at least two detectors out of every h u n d r e d , or fraction thereof, shall be removed every five years and sent to a testing laboratory. T h e detectors t h a t h a v e been removed shall be replaced with new detectors. If a failure occurs on any of the detectors removed, additional detectors shall be removed and tested as a further check on the installation until there is proven to exist either a general problem involving faulty detectors or a localized problem involving one or two defective detectors. 8-3.3.2 For restorable heat detectors (except pneumatic line-type), one. or more detectors on each signal-initiating circuit shall be tested at least semiannually and different detectors shall be selected for each test. Within five years, each detector shall have been tested.

8-2.4 Smoke Detectors. 8-2.4.1 To assure that each smoke detector is operative and produces the intended response, it shall be caused to initiate an alarm at its installed location. Before testing, each smoke detector shall be inspected to verify that any protection a d d e d d u r i n g the construction phase to guard against contamination by construction dust and dirt has b e e n r e m o v e d a n d t h a t s m o k e e n t r y has n o t b e e n impeded.

8-3.3.3 All pneumatic line-type detectors shall be tested for leaks and p r o p e r operation at least semiannually. 8-3.3.4 Nonrestorable line-type fixed t e m p e r a t u r e detectors shall be tested for alarm function at least semiannually. T h e loop resistance shall be measured, recorded, and compared with that previously recorded. Any change in loop resistance shall be investigated.

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-21

INSPECTIONS, TESTS, AND MAINTENANCE

Detectors found to be outside of the a p p r o v e d range of sensitivity shall be replaced or adjusted to bring them into the a p p r o v e d range if designed to be field adjustable.

8-3.4 Smoke Detectors. 8-3.4.1 All smoke detectors shall be tested at least annually in accordance with 8-2.4.1 to ensure that each detector is operative and produces the intended response.

Flame d e t e c t o r a n d s p a r k / e m b e r d e t e c t o r sensitivity shall not be d e t e r m i n e d using a light source that administers an u n m e a s u r e d quantity of radiation at an undefined distance from the detector.

8-3.4.2* Detector sensitivity shall be checked within one year after installation and every alternate year thereafter.

8-3.6 Fire-Gas and Other Fire Detectors. All fire-gas detectors and other fire detectors shall be tested at least semiannually as prescribed by the manufacturer and more often if found to be necessary for the application.

To assure that each smoke detector is within its listed and marked sensitivity range, it shall be tested using either: (a) A calibrated test method, or (b) T h e manufacturer's calibrated sensitivity test instrument, or

8-4 Detector Maintenance.

(c) Listed control equipment a r r a n g e d for the purpose,

8-4.1" Detectors shall be periodically cleaned in accordance with the manufacturer's instructions to remove dust or dirt. T h e frequency of cleaning will d e p e n d on the type of detector and the local ambient conditions.

or (d) A smoke detect0r/control unit a r r a n g e m e n t whereby the detector causes a signal at the control unit when its sensitivity is outside its acceptable sensitivity range. (e) Other calibrated sensitivity test method acceptable to the authority having jurisdiction..

8-4.2 T h e sensitivity test required by 8-3.4.2 shall be performed for detectors that have been partially disassembled or washed.

Detectors found to have a sensitivity 0.25 p e r c e n d f t obscuration or more outside t.he listed and marked.sensitivity range shall be cleaned and recalibrated or replaced.

NOTE: Removal of a detector from its plug-in base is not considered partial disassembly. ., 8-5 Tests Following Exposure to Fire Conditions.

Exception." Detectors listed as field adjustable may be either adjusted within the listed and marked sensivity range,, cleaned, and recalibrated or replaced.

8-5.1 All detectors suspected of exposure to a fire condition shall be tested in accordance with 8-1.2 and Section 8-2.

T h e detector sensitivity shall not be tested or measured using any device that administers an u n m e a s u r e d concentration of smoke or other aerosol into tile detector.

8-6 Inspection Forms.

8-3.4.3 In addition to .the tests required in 8-3.4.1 and 8-3.4.2, air d u c t . s m o k e d e t e c t o r s shall be t e s t e d o r inspected at least annually to ensure t h a t t h e device will sample the air stream. T h e test shall be made in accordance with the manufacturer's instructions (e.g., measuring the pressure d r o p of airflow through the detector for devices using sampling tubes is acceptable.)

8-6.1 An i n s p e c t i o n form shall .be p r o v i d e d by the installer/service company and include the following information on initial tests: (a) Date. (b) N a m e of property. (c) Address.

8-3.5 Radiant Energy Sensing Fire Detectors.

(d) .Installer/service c o m p a n y name, address, p h o n e number, and representative's name.

8-3.5.1 Flame detectors and spark/ember detectors shall be tested at least semiannually in accordance.with the manufacturer's instructions to determine that each detector is operative.

(e) Approving figency(ies) name, address, and representative.

(f) N u m b e r and type of detectors p e r zone for each zone.

8-3.5.2 Flame detector and spark/ember detector sensitivity shall be d e t e r m i n e d at least semiannually using either:

(g) Functional test of detectors. (See 8-1.4 and 8-2.4.1.) (h) Check of all smoke detectors. (See 8-2.4.2.)

ia) a calibrated test method, or

O) Loop resistance for all fixed t e m p e r a t u r e line-type detectors. (See 8-2.3.2.)

(b) the manufacturer's calibrated sensitivity test instrument, or

(j) Other tests as required by e q u i p m e n t manufacturers.

(c) listed control panel a r r a n g e d for the purpose, or (d) other.calibrated sensitivity.test method acceptable to the authority having jurisdiction, which is directly p r o p o r tional to the input signal from a fire consistent with the detector listing or approval.

I

(k) Other tests required by the authority, having jurisdiction. (1) Signature of tester and approval authority representative.

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-22

AUTOMNFICFIRE DETECTORS

8-6.2 An inspection form shall be provided and include the following information for periodic tests.

(b) Selective operation of equipment to exhaust smoke from a building. (c) Selective operation of e q u i p m e n t to pressurize smoke compartments.

(a) Date. (b) Test frequency.

(d) Operation of doors to close the openings in smoke compartments.

(c) Name of property. (d) Address. (e) Name of person performing inspection, maintenance and/or tests, affiliation, business address, and telephone number. (f) Approving agency(ies) name, address, and representative. (g) Designation of the detector(s) tested (tests performed in accordance with Section 8-3). (h) Functional test of detectors. (See 8-1.4 and 8-3.4.1.) (i) Check of all smoke detectors. (See 8-3.4.2.) (j) Loop resistance for all fixed temperature line-type heat detectors. (See 8-2.3.2.) (k) Other tests as required by equipment manufacturers. (I) Other tests as required by the authority having jurisdiction. (m) Signatures of tester and approved authority representative.

9-2.2 To prevent the recirculation of dangerous quantities of smoke, a detector approved for air duct use shall be installed on the supply side of air handling systems in accordance with NFPA 90A, Standard for the Installation of Air Conditioning and Ventilating Systems, and 9-3.2.1. 9-2.3 To selectively initiate the operation of equipment to control smoke spread, the requirements of 9-3.2.2 shall apply. 9-2.4 To initiate the operation of smoke doors, the requirements of Section 9-5 shall apply.

9-3 Application. 9-3.1 Area Detectors Within Smoke Compartments. Area smoke detectors located within a smoke compartment [ for complete area coverage may also be used to initiate control of smoke spread by operating doors, dampers, and other equipment where appropriate in the overall firesafety plan. 9-3.2 Smoke Detection for the Air Duct System.

Chapter 9

S m o k e D e t e c t o r s for C o n t r o l o f S m o k e Spread

9-1 General. Note: See NFPA 101, ® Life Safety Code,® for definition of smoke compartment and NFPA 90A, Standard for the Installation of Air Conditioning and Ventilating Systems, for definition of duct systems. 9-1.1" This chapter covers installation and use of all types of smoke detectors to prevent smoke spread by initiating control of fans, dampers, doors, and other equipment. Detectors for this use may be classified as: (a) Area detectors that are installed in the related smoke compartments. (b) Detectors that are installed in the air duct systems. 9-1.2" Detectors that are installed in the air duct system per 9-1.1 (b) shall not be used as a substitute for open area protection. 9-1.3 Smoke detectors in the related smoke compartment for open area protection are the preferred means to initiate control of smoke spread. 9-2 Purposes. 9-2.1 The purposes for which smoke detectors may be applied in order to initiate control of smoke spread are: (a) Prevention of the recirculation of dangerous quantities of smoke within a building.

9-3.2.1 Supply Air System. W h e r e the detection of smoke in the supply air system is required by other NFPA standards, the following alternative methods may be employed. (a) Detector(s) listed for the air velocity present and located in the supply air duct downstream of both the fan and the filters, or (b) Total smoke detector coverage within the smoke compartments served by the supply air system. 9-3.2.2* Return Air System. Where the detection of smoke in the return air system is required by other NFPA standards, detector(s) listed for the air velocity present shall be located at every return air opening within the smoke compartment, or where the air leaves each smoke compartment, or in the duct system before the air enters the return air system common to more than one smoke compartment. [See Figures A-9-3.2.2(a), (b), and (c).] Exception No. 1: Where complete smoke detection is installed in the smoke compartment, installation of air duct detectors in the return air system is not necessary if their function can be accom] plished by the design of the area detection system. Exception No. 2: Additional smoke detectors are not required to be installed in ducts where the air duct system passes through other smoke compartments not served by the duct.

9-4 Location and Installation of Detectors in Air Duct Systems. 9-4.1

Detectors shall be listed for the purpose.

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

SMOKE DETECTORS FOR C O N T R O L OF SMOKE SPREAD

72E-23

9-4.2 Air duct detectors shall be securely installed in such a way as to obtain a r e p r e s e n t a t i v e sample of the air stream. This may be achieved by any of the following methods. (a) Rigidly m o u n t e d within the duct.

9-5.3 Smoke detectors may be of the photoelectric, ionization, or other a p p r o v e d type.

(b) Rigidly m o u n t e d to the wall of the duct with the sensing element p r o t r u d i n g into the duct.

9-5.4.1 W h e r e d o o r s are to be closed in response to smoke flowing in e i t h e r direction, the following rules apply.

(c) Outside the duct with rigidly m o u n t e d sampling tubes p r o t r u d i n g into the duct. (d) With projected light beam through the duct. 9-4.3 Detectors shall be readily accessible for cleaning and shall be m o u n t e d in accordance with the manufacturer's recommendations. If necessary, access doors or panels shall be provided. 9-4.4 T h e location of all detectors in air duct systems shall be permanently and clearly identified and recorded. 9-4.5 Detectors m o u n t e d outside of a duct employing sampling tubes for t r a n s p o r t i n g smoke from inside the duct to the detector shall be a r r a n g e d to permit verification of airflow from the duct to the detector. 9-4.6 Detectors shall be suitable for p r o p e r operation over the complete range of air velocities, temperature, and humidity expected at the detector when the air handling system is operating. 9-4.7 All penetrations of a return air duct in the vicinity of detectors installed on or in an air duct shall be sealed to prevent entrance of outside air and possible dilution or redirection of smoke within the duct. [ 9-4.8* Location of detectors m o u n t e d in or on return air ducts shall be at least six duct widths downstream from any duct openings, deflection plates, sharp bends, or branch connections.

Exception No. 1: Where detectors are installed in accordance with 9-3.2.2, 9-4.8 does not apply. Exception No. 2: Where it is physically impossible to locate the detector according to 9-4.8, it shall be permissible to position the detector closer than the required six duct widths but as far as possible from the opening, bend, or deflection plate so that smoke can still adequately be detected in the air stream.

9-5.4 Number of Detectors Required.

9-5.4.1.1 Where the d e p t h of wall section above the d o o r is 24 in. (610 mm) or less, one ceiling-mounted detector shall be required on one side of the doorway only. (See Fig-

ure 9-5.4.1.1, parts B and C.) 9-5.4.1.2 Where the depth of wall section above the d o o r is g r e a t e r than 24 in. (610 mm), two c e i l i n g - m o u n t e d detectors shall be required, one on each side of the doorway. (See Figure 9-5.4.1.1, part F.) 9-5.4.1.3 Where the depth of wall section above the d o o r is 60 in. (1520 mm) or greater, additional detectors may be required as indicated by an engineering evaluation. 9-5.4.1.4 Where a detector is specifically listed for d o o r frame mounting, or where a listed combination or integral detector-door closer assembly is used, only one detector is required where installed in the m a n n e r r e c o m m e n d e d by the manufacturer. " 9-5.4.2 Where d o o r release is intended to prevent smoke transmission from one space to another in one direction only, one detector located in the space to which smoke is to be confined shall suffice regardless of the d e p t h of wall section above the door. Alternatively, a smoke detector conforming with 9-5.4.1.4 shall be used. 9-5.4.3 Where there are multiple doorways, additional ceiling-mounted detectors shall be required as follows. 9-5.4.3.1 W h e r e the s e p a r a t i o n b e t w e e n d o o r w a y s exceeds 24 in. (610 mm), each doorway must be treated separately. (See Figure 9-5.4.3.1.) 9-5.4.3.2* Each group of three doorway openings must be treated separately. (See Figure A-9-5.4.3.2, part A.)

9-5 Smoke Detectors for Door Release Service. 9-5.1 Smoke d o o r release not initiated by a fire alarm system that includes smoke detectors protecting the areas on both sides of the d o o r affected shall be accomplished by smoke detectors applied as specified in this section.

9-5.4.3.3" Each group of doorway openings that exceeds 20 ft (6 m) in width measured at its overall extremes must be treated separately. (See Figure A-9-5.4.3.3.)

9-5.2 Smoke detectors listed or a p p r o v e d exclusively for d o o r release service shall not be used for open area protection. (See 1-2.3.)

9-5.4.4 Where there are multiple doorways and listed d o o r frame-mounted detectors, or where listed combination or integral detector-door closer assemblies are used, there shall be one detector for each single or double doorway.

A smoke detector used concurrently for d o o r release service and open area protection shall be acceptable if listed or a p p r o v e d for open area protection and installed in accordance with Chapter 4 of this standard.

9-5.4.4.1 A double doorway is a single o p e n i n g that has no intervening wall space or d o o r trim separating the two doors. (See Figure 9-5.4.3.1.)

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-24

AUTOMATIC FiRE DETECTORS Depth of Wall Section above door

dad#,

Door Frame mounted

Ceiling Mounted

Smoke Detector listed for frame mounting or as part of closer assembly

Smoke Detector Ceiling Mounted

A

0--24" on both sides of doorway

Detector or Detector closer Mounted on either side

One detector mounted on either side

~ _ M a x . 5' j Min. = d 2 - I

Over 24" on one ride only

0 70L _j Detector or Detector closer Mounted on either side

d1=20"

i

One detector mounted on the higher side F

~

e Max. 5" _ ~

i~_.Max. 5'

°±U

Over 24" on both

ddes Detector or Detector closer Mounted on either side

Min-= d/

[Min.=d

1

D 3000' above sea level

X O O

X O O

Ion Photo Beam

72E-35

that I n f l u e n c e D e t e c t o r R e s p o n s e Humidity > 93%

T e m p . < 32 ° F > 100 ° F

Color of Smoke

X X X

O X O

X X X

X = May affect detector response. O = Generallydoes not aft~ct detector response. Table A-4-6.1.2(a) Common Sources of Aerosols and Particulate Matter Moisture

Moisture

Live steam Steam tables Showers Humidifiers Slop sink Humid outside air Water spray

Excessive tobacco smoke Heat treating Corrosive atmospheres Dust or lint Linen/bedding handling Sawing, drilling, and grinding Pneumatic transport Textile and agricultural processing

opment, when insufficient thermal energy is released to carry the smoke to the ceiling. Earliest detection of smoke is achieved by locating the intermediate level detectors adjacent to alternate pallet sections as shown in Figures A-4-6.4(a) and (b). Detector manufacturers' recommendations and engineering j u d g m e n t should be followed for specific installations. A protected beant-type detector may be used in lieu of a single row of individual spot-type smoke detectors.

Combustion Products and Fumes

Cooking equipment Ovens Dryers Fireplaces Exhaust hoods Cutting, welding, and brazing Machining Paint spray Curing Chemical fumes Cleaning fluids

Typical Clos~ osed Rack Storage Engine Exhaust I

0-----0

--

Gasoline forklift trucks Diesel trucks and locomotives Engines not vented to the outside b g""lD

Heating Element with Abnormal Conditions

Elevation

I

Dust accumulation Improper exhaust Incomplete combustion

.

Vibration or Shock Radiation Radio frequency Intense light Lightning Electrostatic discharge

I A-4-6.4 High Rack Storage.

_

Airflow

Gusts Excessive velocity Power supply

For most effective detection of fire in high rack storage areas, detectors should be located on the ceiling above each aisle and at intermediate levels in the racks. This is necessary to detect smoke that may be trapped in the racks at an early stage of fire devel-

.

.

4 - -

.__k, °, _

~01-- H

O O - - ~--, It q

- D q -'P-4 oI q( 0

Plan

I A-4-6.2.2 Airflow through holes in the rear of a smoke detector may interfere with smoke entry to the sensing chamber. Similarly, air from the conduit system may flow around the outside edges of the detector and again interfere with smoke reaching the sensing chamber. Additionally, holes in the rear of a detector provide a means for entry of dust, dirt, and insects, each of which can adversely affect the detector's performance.

.

r//llllilllllllll/

Table A-4-6.1.2(b) Sources of Electrical and Mechanical Influences on Smoke Detectors

Electrical Noise and Transients

I --

't

O-- ~--"I) (

t q I

- b q "-t--q - D ¢ --P-~ -)q.-t-~

-

O0--D

1~-

q I0

p t -.~-4

O DETECTORS ON CEILING • DETECTORS ON RACKS (UPPER INTERMEDIARY LEVEL) • DETECTORS ON RACKS (LOWER INTERMEDIARY LEVEL) Figure A-4-6.4(a) For Solid Storage in which Transverse and Longitudinal Flue Spaces are Irregular or Nonexistent, as for Slatted or Solid Shelved Storage.

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-36

AU'I'OMATIC FIRE DETECTORS

Typical Open Rack Storage -

-

Z

/-

-I

.-'--.--

-

Elevation

E

Kd

__

_

f[l¢llll/llll¥1[lllll

lglll[lllllllll¢¥J

! I -

- 0~5~-I=

I,=

Plan

OI

1= 1,= I=

0 •

~--~0

0

~--

F=~ :=~ I==

oh

~==~l==

i~ ~

O = a l==

~

.-, h-.-

L=

I==

==w

This interrelationship between wavelength and combustion chemistry affects the relative peHbrmance of various types of detectors to various fires.

==1

A-5-3.1 T h e radiant energy from a flame or spark/ember Is comprised of emissions in various bands of the ultraviolet, visible, and infrared portions of the spectrum. T h e relative quantities of radiation emitted in each part of the spectrum are d e t e r m i n e d by the fuel chemistry, the temperature, and the rate of combustion. T h e detector should be matched to the characteristics of the fire.

0

0 ~b== 0

l e n g t h o f light b e i n g e m i t t e d from a flame a n d the combustion chemistry producing the flame. Specific subatomic, atomic, and molecular events yield radiant energy of specific wavelengths. For example, uhraviolet photons are emitted as the result of the complete loss of electrons or very large changcs in electron energy levels. During combustion, molecules are violently torn a p a r t by the chemical reactivity of oxygen, and electrons are released in the process, recombining at drastically lower energy levels, thus giving rise to ultraviolet radiation. Visible radiant energy is generally the result of smaller changes in electron energy levels within the molecules of fuel, flame intermediates, and p r o d u c t s of combustion. I n f r a r e d radiation comes fi'om the vibration of molecules or parts of molecules when they are in the superheated state associated with combustion. Each chemical c o m p o u n d exhibits a g r o u p of wavelengths at which it is resonant. These wavelengths constitute the chemical's IR spectrum, which is usually unique to that chemical.

=n

0== ~I

DETECTORS ON CEILING DETECTORS IN RACKS AT UPPER INTERMEDIARY LEVEL

(]P DETECTORS IN RACKS AT LOWER INTERMEDIARY LEVEL

I Figure A-4-6.4(b) For Palletized Storage or No Shelved Storage in which Regular Transverse and Longitudinal Flue Spaces are Maintained.

A-5-2.1.1 Class A and D combustibles will burn as embers under conditions where the typical flame associated with fire does not necessarily exist. This "glowing combustion" yields radiant emissions in radically different parts of the radiant energy spectrum than does flaming combustion. Specialized detectors, specifically designed to detect those emissions, should be used in applications where this type of combustion is expected. In general, flame detectors are not intended for the detection of embers: A-5-2.1.6 T h e o v e r w h e l m i n g majority of a p p l i c a t i o n s involving the detection of Class A and D combustibles using radiant energy sensing detectors involve the transport of particulate solid materials t h r o u g h pneumatic conveyance ducts or mechanical conveyors. It is c o m m o n in the industries that include such hazards to call a moving piece of burning material a "spark" and systems for the detection of such fires "spark detection systems." A-5-2.1.9 T h e concept of wavelength is extremely important in selecting the p r o p e r detector for a particular application. T h e r e is a precise interrelation between the wave-

Almost all materials that participate in flaming combustion will emit ultraviolet radiation to some degree d u r i n g flaming combustion, whereas only carbon-containing fuels will emit significant radiation at the 4.35 micron (carbon dioxide) band used by many detector types to detect a flame. The radiant energy emitted from an e m b e r is determined primarily by the fuel t e m p e r a t u r e (Plank's Law o f Emissions ) and the emissivity of the fuel. Radiant energy from an e m b e r is p r i m a r i l y i n f r a r e d a n d , to a lesser degree, visible in wavelength. In general, embers do not emit ultraviolet energy in significant quantities (0.1 percent of total emissions) until the e m b e r achieves t e m p e r a t u r e s of 2000 K (1727°C or 3240°F). In most cases, the emissions will be included in the band of 0.8 to 2.0 microns, corresponding to t e m p e r a t u r e s of approximately 750°F (398°C) to 1830°F (1000°C). Most radiant energy detectors have some form of qualification circuitry within them that uses time to help distinguish between spurious, transient signals and legitimate fire alarms. These circuits become very i m p o r t a n t when one considers the anticipated fire scenario and the ability of the detector to r e s p o n d to that anticipated fire. For example, a detector that utilizes an integration circuit or a timing circuit to respond to the flickering light from a fire may not respond well to a deflagration resulting from the ~gnition of accumulated combustible vapors and gases, or where the fire is a spark that is traveling up to 100 meters ~er second past the detector. U n d e r these circumstances, a

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX A detector that has a high speed response capability would be most a p p r o p r i a t e . On the o t h e r hand, in applications where the d e v e l o p m e n t of the fire will be slower, a detector that utilizes time for the confirmation of repetitive signals would be appropriate. Consequently, the fire growth rate should be considered in selecting the detector. T h e detector performance should be selected to respond to the anticipated fire: T h e radiant emissions are not the only criterion to be considered. T h e medium between the anticipated fire and the detector is also very important, Different wavelengths of radiant energy are absorbed with varying degrees of efficiency by materials suspended in the air or by those that may accumulate on the optical surfaces of the detector. Generally, aerosols and surface deposits reduce the sensitivity of the detector. T h e detection technology utilized should take into account those normally occurring aerosols and surface deposits to minimize the reduction of system response between maintenance intervals. Note that the smoke evolved from the combustion of middle and heavy fraction petroleum distillates is highly absorptive in the ultraviolet end of the spectrum. Where using this type of detection, the system should be designed to minimize the interference of smoke on the response of the detection system. T h e environment and ambient conditions anticipated in the area to be protected will impact on the choice of detector. All detectors have limitations on the range of ambient temperatures over which they will respond consistent with their tested or a p p r o v e d sensitivities. T h e designer should make certain that the detector is compatible with the range of ambient temperatures anticipated in the area in which it is installed. In addition, rain, snow, and ice are all optically o p a q u e at both u l t r a v i o l e t a n d i n f r a r e d wavelengths. Where applicable, provisions should be made to protect the detector from accumulations of these materials on the optical surfaces. A-5-4.1.1 All optical detectors respond pursuant to the following theoretical equation:

S = k P e ~d dv

72E-37

Generalized Fire Size Vs. Distance Curves 5 m

4-Normalized Distance

3-

2-1--

I

I

I

]

2

4

Figure A - 5 - 4 . I . I

I

I

I

I

I

I

I

I

I

9 Normalized Fi~'e Size

I

I 16

G e n e r a l i z e d Fire Size vs. D i s t a n c e Curves.

T h e curve defines the maximum distance at which the detector consistently detects a fire of defined size and fuel. Detectors should only be employed in the shaded area beneath the curve. U n d e r the best of conditions, with no a t m o s p h e r i c absorption, the radiant power reaching the detector is reduced by a factor of 4 if the distance between the detector and the fire is doubled. For the consumption of the atmospheric extinction, the exponential term, Zeta (~) is a d d e d to the equation. Zeta (~) is a measure of the clarity of the air at the wavelength u n d e r consideration. Zeta (~) will be affected by humidity, dust, and any other contaminants in the air that are absorbant at the wavelength in question. Zeta (~) generally has values between -.001 and -.1. A-5-4.2.1 Extraneous sources of radiant emissions that have been identified as interfering with the stability of flame detectors include: (a) sunlight (b) l i g h t n i n g .

k = proportionality constant for the detector p = radiant power emitted by the fire e = Naperian logarithm base (2.7183) (Zeta) = the extinction coefficient of air d = the distance between the fire and the detector S = radiant power reaching the detector T h e sensitivity, S, would typically be measured in nanowatts. This equation yields a family of curves similar to the one shown in Figure A-5-4.1.1.

(c) x-rays (d) gamma rays (e) cosmic rays (f) ultraviolet radiation from arc welding (g) radio frequency interference (h) hot objects

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-38

A U T O M A T I C FIRE DETECTORS

A-5-4.2.3 T h e greater the displacement of the fire from the optical axis of the detector, the larger the fire must become before it is detected. This p h e n o m e n o n establishes the field of view of the detector. Figure A-5-4.2.3 shows an example of the effective sensitivity versus angular displacement of a flame detector.

Normalized Sensitivity Vs. Angular Displacement (Normal)

15

Angleof Incidence with Radiant

A-5-4.3.2 T h e r e is a minimum ignition power (watts) for all combustible dusts. If the spark or e m b e r is incapable of delivering that quantity of power to the adjacent combustible material (dust) and e x p a n d i n g dust, fire will not occur. T h e m i n i m u m ignition power is d e t e r m i n e d by the fuel chemistry, fuel particle size, fuel concentration in air, and ambient conditions such as t e m p e r a t u r e and humidity. A-5-4.3.5 T h e greater the displacement of the fire from the optical axis of the detector, the larger the fire must become before it is detected. This p h e n o m e n o n establishes the field of view of the detector. Figure A-5-4.3.5 shows an example of the effective sensitivity versus angular displacement of a flame detector.

Normalized Sensitivity Vs. Angular Displacement

. 1.0 .75

.50

.25

t¢ . .

(Normal) 0 15 , . ~ ~

Angleof Inodence with Radiator

.25 .50 .75 1.0 Normalized Distance from Detector

Figure A-5-4.2.3

Normalized Sensitivity vs. Angular Displacement.

A°5-4.2.4 Virtually all radiant energy sensing detectors exhibit some kind of "fuel specificity." Different fuels when b u r n e d at uniform rates (joules/sec or watts) will emit different levels of radiant power in the ultraviolet, visible, and infrared portions of the spectrum. U n d e r free-burn conditions, a fire of given surface area but of different fuels will burn at different rates (joules/sec or watts) and emit varying levels of radiation in each of the major portions of the spectrum. Most r a d i a n t e n e r g y d e t e c t o r s d e s i g n e d to detect flame are qualified based upon a defined fire u n d e r specific conditions. Where employing these detectors for fuels other than the defined fire, the designer should make certain that the a p p r o p r i a t e adjustments to the m a x i m u m distance between the detector and the fire are made consistent with the fuel specificity of the detector. A-5-4.2.6 T h e means by which this requirement has been satisfied include: (a) lens clarity monitoring and cleaning when a contaminated lens signal is r e n d e r e d , or (b) lens air purge. A-5-4.3.1 Spark/ember detectors are installed primarily to detect sparks and embers that may, if allowed to continue to burn, precipitate a much larger fire or explosion. S p a r k / e m b e r detectors are typically m o u n t e d on some form of conveyor monitoring the fuel as it passes by. Usually, it is necessary to enclose the portion of conveyor where the detectors are located as these devices generally require a dark environment. Extraneous sources of radiant emissions that have been identified as interfering with the stability of spark/ember detectors include: (a) ambient light (b) radio frequency interference (c) electrostatic discharge in the fuel stream

1.0 .75 .50 .25

.25 .50 .75

.0

Normalized Distance from Detector

Figure A-5-4.3.5

A-5-4.3.6 T h e means by which this r e q u i r e m e n t has been satisfied include: (a) lens clarity monitoring and cleaning when a contaminated lens signal is r e n d e r e d , or (b) lens air purge. A-6-1.1.1 Many gases may be p r o d u c e d by a fire. Fire-gas detectors are instruments that are triggered into alarm by one or more fire gases. Fire-gas detectors need not be able to differentiate a m o n g the various fire gases. D e p e n d i n g on the material being b u r n e d and the oxygen supply available, the quantity and composition of gases given off can vary greatly. If o r d i n a r y cellulosic material such as wood or p a p e r is b u r n e d with an abundance of oxygen, the gases given off are primarily carbon dioxide and water vapor. If, however, the same material is b u r n e d or smolders with a limited supply of oxygen, a host of additional gases will be evolved. A-6-3.1 Fire-gas detectors d e p e n d on fire gases reaching the sensing element. W h e n sufficient c o n c e n t r a t i o n is present, operation is obtained. Since the detectors are usually m o u n t e d on o r n e a r the ceiling, r e s p o n s e time d e p e n d s on the nature of the fire. A hot fire will drive fire gases up to the ceiling more rapidly. A smoldering fire produces little heat and, therefore, the detection time will be increased.

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX A

A-6-3.3 Gas transport to the sensor of a fire-gas detector may occur by diffusion where migration results fi'om concentration gradients or by sampling if pumps, fans, or aspirators are employed. A-6-3.6.3 Location and spacing of fire-gas detectors should consider beam depth, ceiling height, beam spacing, and anticipated fire type and location. For ceiling configurations where mixing of air into beam pockets is inhibited by ventilation systems, detectors will perform better if installed on the bottom of beams. To detect flaming fires (strong plumes), detectors should be installed as follows: (a) If the ratio of the beam depth, D, to ceiling height, H, (D/H) is greater than 0.10 and the ratio of beam spacing, W, to ceiling height (W/H) is greater than 0.40, detectors should be located in each beam pocket. (b) If either ratio of beam depth to ceiling heigl-it (D/H) is less than 0.10, or the ratio of beam spacing to ceiling height (W/H) is less than 0.40, detectors should be installed on the bottom of the beams. To detect smoldering fires (weak or no plumes), detectors should be instfilled as follows: (c) If air mixing into beam pockets is good (e.g. air-flow parallel to long beams) and condition (a) exists as above, a detector should be located in each beam pocket. (d) If air mixing into beam pockets is limited, or condition (b) exists as above, detectors should be located on the bottom of the beams. A-6-4.1 Detectors should not be located in a direct airflow nor closer than 3 ft (900 ram) from an air supply diffuser.

72E-39

A-8-2 Factors to be considered for inspection and tests of detectors include: (a) Operational range of voltage, current, and signaling technique of the detector with respect to the control equipment. (b) Polarity of power connection to the detector• (c) Integ~:ity of electrical connections. (d) Integrity of mechanical connections• (e) Mechanical support. A-8-2.3.1 T h e rate-of-rise element of a combination detector can also be tested by cooling the detector and then causing it to rise in temperatur& This will generally activate the rate-of-rise element without risk of damage to the nonrestorable fixed temperature element. A-8-2.4.1.1 Aerosols should be used in accordance with the detector manufacturer's instructions to avoid damage and contamination to the detector. If aerosols are sprayed directly into the detector at less than the recommended distance, or if aerosols are sprayed for too long a time, an excessive amount of aerosol may cause damage to the detector. A-8-3.1 Regardless of the type of detectors in use, the following detectors should either be replaced or representative samples sent to a testing laboratory or the manufacturer for testing: (a) Detectors on systems that are being restored to service after a period of disuse. (b) Detectors that are perceptibly corroded. (c) Detectors that have been painted in the field, unless they are of a type found by the testing laboratory to be unaffected by paintingl

A-6-5.1.3 Product listing standards include tests for temporary excursions beyond normal limits. In addition to temperature, humidity, and velocity variations, fire-gas detectors should operate reliably u n d e r such c o m m o n environmental conditions as mechanical vibration, electrical interference, and other environmental influences. These conditions are also included in tests conducted by the listing agencies.

(f) Detectors on circuits that have been subjected to surges'by overvoltages or lightning damage.

A-8-1.3.2 Examples of qualified personnel include but are not limited to:

(g) Detectors that are subjected to other conditions that may permanently affect their operation, such as grease or other deposits or corrosive atmospheres.

(d) Detectors that have been cleaned of paint. (e) Detectors that have been subjected to mechanical injury or similar abuse.

(a) Factory trained and certified. (b) National Institute for Certification in Engineering Technologies certified.

(c) International Municipal Signaling Association Certified. (d) Certified by State or Local Authority. (e) Trained and qualified personnel employed by an organization listed by a nationally recognized Testing Laboratory for the servicing of Fire Protective Signaling System.

A-8-3.4.2 In the determination of baseline detector sensitivity, the detectors should be isolated from the installed environmental factors (i.e., air velocity) that may affect the measurement. Detectors installed in environments subject to large amounts of dust and dirt or in areas recently renovated require more frequent sensitivity testing. In lieu of environmental isolation for test, analog type detectors may utilize listed control equipment that automatically compensates for environmental conditions and maintains the detector "sensitivity" (alarm point definition) within acceptable limits.

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-40

A U T O M N [ ' I C FIRE DETECTORS

There is a large population of installed smoke detectors that were manufactured in compliance with previous product standards that did not require a means for testing sensitivity within an acceptable listed range. It is the intent of this s t a n d a r d that these detectors need not be tested against current product standards.

The detectors should be installed up to 12 in. (0.3 m) in fi'ont of or behind the o p e n i n g and spaced according to the following o p e n i n g dimensions: (1)

In order to determine the effects of the e n v i r o n m e n t on the detector, a measurement of detector sensitivity in the installed e n v i r o n m e n t should be considered. A-8-4.1 Accumulation of dust and dirt adversely affect detector performance. Detectors that are visibly dirty or have significantly changed in sensitivity, should be cleaned. If after five years of field service, a detector has not been cleaned, it should be cleaned for the purpose of preventative maintenance to minimize false alarms. In an exceptionally clean e n v i r o n m e n t the time interval may be extended. Manufacturer's instructions may detail detector maintenance methods such as vacuuming to remove loose dirt and insects, and washing to remove greasy deposits. In lieu of these cleaning methods, the manufacturer may provide cleaning servce at the factory or field locations.

Width: up to 36 in. -up to 72 in. --

One detector centered in o p e n i n g Two detectors located at the I/,t points of the o p e n i n g One additional detector for each full 24 in. of o p e n i n g

over 72 in. -(2)

Depth: The n u m b e r and spacing of the detector(s) in the depth (vertical) of the o p e n i n g should be the same as those given tbr the width (horizonal) above. [See

Figure A-9-3.2.2(a).] (3)

Orientation: Detectors should be oriented in the most favorable position tbr smoke entry with respect to the direction of air flow. T h e path of a projected beamtype detector across the return air openings should be considered equivalent in coverage to a row of individual detectors.

width

width

t----up to-----I 36" /

I - - - - - ~ u p to / 72-

A-9-1.1 Smoke detectors located in the open area(s) are prefi:rred to duct-type detectors because of the dilution eltizct in air ducts.

V

A-9.1.2 Dilution of smoke-laden air by clean air from other parts of the building, or dilution by outside air intakes, may allow high densities of smoke in a single room with no appreciable smoke in the air duct at the detector location. Smoke may not be drawn from open areas when air conditioning systems or ventilating systems are shut down. A-9-3.2.2 Detectors listed for the air velocity present may be installed at the opening where the return air enters the common return air system.

/

7 I

~max.~ depth

up to 36"

T[]

evenly spaced []

d/2

I Figure A-9-3.2.2(a)

t 990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

for each full 24 inches of additional opening width

I

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

AI)PENDIX A

~.

,

a

"L •

~,'.

e.

,~

.,=.

;¢,

,Q



?,.'~=

:

",=

',~

72E-41

;

?..

..,

,=

.p

Smoke detector(s) here -- see Figure 9.3.2,2(a) or Paragraph 9.4.2

J Ceiling Non-ducted return air system

Smoke detector anywhere here

. /

IL Ducted return sir system Smoke barrier

L Figure A-9-3.2.2(b)

Common return air system serving more than one smoke compartment

Location O f Smoke Detector(s) in R e t u r n Air Systems for Selective O p e r a t i o n of Equipment.

Acceptable location tot' • Imoke detector in I n l i r duel

~

Preferred location of t h i detKtor in the duct; l o a t i o n it not rlquired.

~/III/IIIH~ [

.......' " i" ;"i..;.;

lll/lllllll/llll////lll/llllll//l~

JLpll,/i," / ........ ",;,,,i" ;;;,.,;,,;;;.;

/I t

Ceiling/ Smoke c ~ p a r t m e n t 1

S411okecom~trtmen! 2

Smoke barrier

Smoko cornp~rtmem 3

i

;I Common return

air W ~ n Figure A-9-3.2.2(c)

j

Detector Location in a Duct W h i c h Passes T h r o u g h Smoke C o m p a r t m e n t s not Served by the Duct.

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

AUTOMATC IFIREDETECTORS

72E-42

Air duct

C

o

n

d

E lee t r lea' b°x ~ ~ ~ 1 ~

u

~,,~)

~ I'~ie~tss~.

l/ Figure A-9-4.8(a)

(

~[~

/

Access panel door

Pendant Mounting Air Duct Installation.

Retu~'n air inlet ~ /

Bend or other obstruction //

@ .t---- 6 duet w i d t h s - - ~ minimum

I

1 I

p--~6

Figure A-9-4.8(b)

Typical Duct Detector Placement.

Tube support hole only for ducts more than 3 ft wide

L=,I

I~ Air flow direction -~

idth

~ l n s e r t rubber olug this end of inlet tube Expected air flow direction

Inlet tube holes face upstream of air flow

~'~" Return tube / s ant cut face oriented downstream of air flow Do not insert rubber plug Figure A-9-4.8(c)

I I

duct widths-~-----~ I minimum

Inlet Tube Orientation.

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

9

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX

A

72E-43

D e t e c t o r (s) Location

I a = 2 4 " or less 3 openings w = 2 0 ' or less

On c e n t e r line o f center opening

a = 2 4 " or less more than 3 openings

T r e a t in 2 or m o r e g r o u p s

A

!

!

B

ForSl

Units:

1 in. = 2 5 . 4 r a m ; I ft = 0 . 3 0 5 m

Figure A-9-5.4.3.2

a = 2 4 " o r less w = more than 20'

-" F o r SI U n i t s :

I in. = 2 5 . 4 m m ;

W

T r e a t as 2 or more groups

v

1 ft = 0 . 3 0 5 m

Figure A-9-5.4.3.3

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-44

AUTOMATIC FIRE DETECTORS

Appendix B

Spacing and Sensitivity

This Appendix is not a part of the requirements of this NFPA document, but is included for information purposes only.

Guide for Automatic Fire Detector Spacing

This Appendix is not a part of the requirements of this NFPA document, but is included for inforTnation purposes only.

NOTE: Superior numbers in the text correspond to references al the end of this Appendix.

B-I. General. B - I - I A detector will ordinarily operate sooner in detecting the fire if it is nearer the fire.

B-I-2 Generally, height is the most i m p o r t a n t single dimension where ceiling heights exceed 16 ft (4.9 m).

B-I-3 As smoke and heat rise from a fire, they tend to spread in the general form of an inverted cone. Therefore, the concentration within the cone varies inversely as a variable exponential function of the distance from the source. This effect is very significant in the early stages of a fire as the angle of the cone is wide. As a fire progresses in intensity, the angle of the cone narrows and the significance of the effect of height is lessened. B-I-4 H i g h Ceilings. As the ceiling height increases, a larger-size fire is required to actuate the same detector in the same time. In view of this, it is mandatory that the designer of a fire detection system calling for heat detectors consider the size of the fire and rate of heat release that may be permitted to develop be[bre detection is ultimately obtained. B-l-5 The most sensitive detectors suitable [br the maximum ambient t e m p e r a t u r e at heights above 30 ft (9.1 m) should be employed.

B-l-6 Spacing r e c o m m e n d e d by testing laboratories for the location of detectors is an indication of their relative sensitivity. This applies with each detection principle; however, detectors o p e r a t i n g on various physical principles have different inherent sensitivities to different types of fires and fuels.

B-l-7 Reduction of listed spacing may be required fro. any of the following purposes: (a) Faster response of the device to a fire. (b) Response of the device to a smaller fire. (c) Accommodation to room geometry. (d) Other special considerations, such as air movement, or ceiling or other obstructions.

1990 Edition

Appendix C

C-1 Introduction. C-I-1 Scope. This appendix provides information intended to s u p p l e m e n t NFPA 72E, Standard for Automatic Fire Detectors, and includes a p r o c e d u r e for deternfining heat detector spacing based on the size and rate of growth of fire to be detected, various ceiling heights, and ambient temperature. T h e effects of ceiling height and the size and rate of growth of a flaming fire on smoke detector spacing are also treated. A p r o c e d u r e for analyzing the response of existing heat detection systems is also presented. C-I-I.1 This a p p e n d i x utilizes the results of fire research funded by the Fire Detection Institute to provide test data and analysis to the NFPA Technical Committee on Detection Devices. (See reference 2.) C-1-1.2 This a p p e n d i x is based on full-scale fire tests in which all fires were geometrically growing flaming fires. C-1-1.3 T h e guidance applicable to smoke detectors is limited to a theoretical analysis based on the flaming fire test data and is not intended to address the detection of smoldering fires. C-1-2 Purpose. T h e purpose of this a p p e n d i x is to assist fire alarm system design engineers concerned with the spacing of heat or smoke detectors. C-1-2.1 This a p p e n d i x is intended to provide a method for modifying the listed spacing of both rate-of-rise and fixed t e m p e r a t u r e heat d e t e c t o r s r e q u i r e d to achieve detector response to a geometrically growing flaming fire, at a specific fire size, taking into account the height of the ceiling on which the detectors are mounted. This proced u r e also permits modification of listed spacing of fixed t e m p e r a t u r e heat detectors to account for variation o f ambient t e m p e r a t u r e (Ta) from standard test conditions. C-1-2.1.1 This a p p e n d i x may be used to estimate the fire size that can be detected by an existing array of listed heat detectors installed at a given spacing for a given ceiling height in known ambient conditions. C-1-2.2 T h e a p p e n d i x is also i n t e n d e d to explain the effect of rate of fire growth and fire size of a flaming fire, as well as the effect of ceiling height on the spacing of smoke detectors.

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX C C-1-2.3 This design m e t h o d o l o g y utilizes theories of fire development, fire p l u m e dynamics, a n d detector performance, which are the major factors i n f l u e n c i n g detector response. However, it does not consider several lesser phen o m e n a that, in general, are unlikely to have significant influence. A discussion of ceiling drag, heat loss to the ceiling, radiation to the detector from a fire, reradiation of heat from a detector to its s u r r o u n d i n g s , a n d the heat of fusion of eutectic materials in fusible e l e m e n t s of heat detectors a n d their possible l i m i t a t i o n s o n the d e s i g n m e t h o d are p r o v i d e d in reference 9.

C-1-3 Relationship to Listed Spacings. Listed spacings for h e a t d e t e c t o r s a r e b a s e d o n relatively large fires (approximately 1200 Btu/sec) b u r n i n g at a c o n s t a n t rate. [The listed spacing is based on the distance from a fire at which an o r d i n a r y d e g r e e heat detector actuates prior to operation o f a 160°F (71.1°C) sprinkler installed at a 10 ft (3 m) spacing. See Figure A-3-5.1(a).] Design spacing for this type of fire can be d e t e r m i n e d using the material of C h a p t e r 3. W h e n smaller fires a n d v a r y i n g growth rates m u s t be considered, the d e s i g n e r may use the material p r e s e n t e d by this a p p e n d i x . Cr2 Fire D e v e l o p m e n t and Ceiling H e i g h t Considerations. C-2-1 G e n e r a l . T h e p u r p o s e of this section is to discuss the ceiling height a n d the selection of a threshold fire size, which may be used as the basis for d e t e r m i n a t i o n of type a n d spacing of automatic fire d e t e c t o r s in a specific situation.

Warehouse Materials Classification Growth Heat (s - slow) Time Release (m - medium) (see) Density (q) ( f - fast) 1. Wood pallets, stack 11/2 ft high (6-12% moisture) 150-310 2. Wood pallets, stack 5 ft high (6-12% moisture) 90-190 3. Wood pallets, stack 10 ft high (6-12% moisture) 80-110 4. Wood pallets, stack 16 ft high (6-12% moisture) 75-105 5. Mail bags, filled, stored 5 ft high 190 6. Cartons, compartmented, stacked 15 ft high 60 7. Paper, vertical rolls, stacked 20 ft high 15-28 8. Cotton (also PE, PE/ Cot, Acrylic/Nylon/ PE), garments in 12 ft high rack 20-42 9. Cartons on pallets rack storage, 15-30 ft high 40-280 10. Paper products, densely packed in cartons, rack stora g e , 20 ft high

11.

C-2-2 Fire Development. C-2-2.1 Fire d e v e l o p m e n t will vary d e p e n d i n g o n the c o m b u s t i o n characteristics of the fuels involved a n d the physical c o n f i g u r a t i o n of the fuels. After ignition, most fires grow in an accelerating pattern.

C-2-2.2 Fire Size.

Table C-2-2.2.1(a)

12. 13. 14.

C-2-2.2.1 Fires can be characterized by their rate of heat release, m e a s u r e d in terms of the n u m b e r of Btu per seco n d (kW) g e n e r a t e d . Typical m a x i m u m heat release rates for a n u m b e r of different fuels a n d fuel configurations are provided in Tables C-2-2.2. l(a) a n d (b).

15. 16.

Maximum Heat Release Rates

17.

Qm = qA

18.

W h e r e Qm = M a x i m u m Heat Release Rate (Btu/sec) q = Heat Release Density (Btu/sec/ft ~) A = Floor Area (ft")

72E-45

19.

T h e following heat-release rates p e r u n i t floor area are for fully involved combustibles, a s s u m i n g 100 p e r c e n t combustion efficiency. T h e growth times shown are those r e q u i r e d to exceed 1000 Btu/sec heat release rate for d e v e l o p i n g fires a s s u m i n g 100 p e r c e n t c o m b u s t i o n efficiency.

20.

(PE = polyethylene; PS = polystyrene; PVC = polyvinyl chloride; PP -- p o l y p r o p y l e n e ; PU = p o l y u r e t h a n e ; FRP = fiberglass-reinforced polyester.)

22.

21.

PE letter trays filled, stacked 5 ft high on cart PE trash barrels in cartons stacked 15 ft high FRP shower stalls in cartons, stacked 15 fi high PE bottles packed in Item 6 PE bottles in cartons, stacked 15 fi high PE pallets, stacked 3 ft high PE pallets, stacked 6-8 ft high PU mattress, single, horizontal PE insulation board, rigid foam, stacked 15 ft high PSjars packed in Item 6 PS robs nested in cartons, stacked 14 ft high PS toy parts in cartons, stacked 15 ft high

110

m-f

330

f

600

f

900

f

35

f

200

t

-

t

t

-

111- f

470

-

llI-S

190

750

f

55

250

t

85

110

t

85

550

t

75

170

t

130

f

30-55

t

110

-

f

8

170

t

55

1200

t

105

450

f

110

180

f

1990

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Edition

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-46

AUTOMATIC FIRE DETECTORS

(Table C-2-2.1.1(a) cont.) Warehouse Materials Classification Growth Heat (s - slow) Time Release (m - medium) (sec) Density (q) ( f - fast)

PS insulation board, rigid, stacked 14 ft high 7 24. PVC bottles packed in Item 6 9 25. PP tubs packed in Item 6 10 26. PP and PE'film in rolls, stacked 14 ft high 40 27. Distilled spirits in barrels, stacked 20 ft high 23-40 28. Methyl alcohol 29. Gasoline 30. Kerosene 31. Diesel Oil tFire growth rate exceeds design data. ForSI Units: I fi = 0.305 m.

Q = X(t-T,,) ~ or

23.

Q = (lO00/tg) (t - %)2 = Btu/sec or kW 290

f

300

t

390

t

350

?

65 200 200 180

"l" -

Table C-2-2.2.1(b) Maximum Heat Release Rates from Fire Detection Institute Analysis Approximate Values Btu/sec

1. 2. 3. 4. 5.

which the fires began to obey the power-law fire growth model. Prior to t v, the fuels may have smoldered, b u t did n o t b u r n vigorously with an o p e n flame. T h e m o d e l curves are t h e n predicted by:

Medium wastebasket with milk cartons Large barrel with milk cartons Upholstered chair with polyurethane foam Latex tbam mattress (heat at room door) Furnished living room (heat at open door)

100 140 350 1200 4000-8000

I C-2-2.2.2 T h e National Institute of Standards a n d Technology has developed a large-scale calorimeter for measuring the heat release rates o f b u r n i n g f u r n i t u r e . T w o reports issued by T h e National Institute of S t a n d a r d s a n d T e c h n o l o g y (references 5 a n d 7) describe the a p p a r a t u s a n d data collected d u r i n g two test series. Test data from forty f u r n i t u r e calorimeter tests have b e e n used i n d e p e n d e n t l y to verify the power-law fire growth model, Q = Xt 2. H e r e Q is the i n s t a n t a n e o u s heat release rate. X is alpha, the fire intensity coefficient, a n d t is time. T h e fire growth time, t_, is arbitrarily defined as s the time, after established b u r n i n g , when the fire would reach a b u r n i n g rate of 1000 Btu/sec. In terms oftg: X = 1000/tg 2 = Btu sec "~or kW/sec 2 and

For tests 19, 2 2 , 2 9 , 42, a n d 67, different power-law curves were used to model the initial a n d the latter realms of b u r n i n g . I n examples such as these, e n g i n e e r s m u s t choose the fire growth p a r a m e t e r that best describes the r e a l m o f b u r n i n g t h a t the d e t e c t i o n system is b e i n g d e s i g n e d to r e s p o n d to. I n a d d i t i o n to h e a t release rate data, the o r i g i n a l National Institute of S t a n d a r d s a n d T e c h n o l o g y reports c o n t a i n data on particulate conversion a n d radiation from the test specimens. T h e s e data can be used to d e t e r m i n e the threshold fire size (heat release rate) at which tenability becomes e n d a n g e r e d or w h e n a d d i t i o n a l fuel packages might become involved in the fire. C-2-2.2.3 A fire d e t e c t i o n system can be d e s i g n e d to detect a fire at a certain size in terms of its heat release rate. This is called the threshold fire size, Qd. T h e threshold size is the rate of heat release at which detection is desired. C-2-2.2.4 T h e t h r e s h o l d fire sizes c o n s i d e r e d in this a p p e n d i x range from 100 Btu/sec (105 kW) to 2000 Btu/ sec (2110 kW).

C-2-2.3 Fire G r o w t h .

C-2-2.3.1 A second i m p o r t a n t c o n s i d e r a t i o n c o n c e r n i n g fire d e v e l o p m e n t is the time (tg) it takes for fire to reach a given heat release rate. TaBle C-2-2.2.1(a) a n d Table C-2-2.2.2 p r o v i d e the times r e q u i r e d to r e a c h a heat release rate of 1000 Btu/sec (1055 kW) for a variety of materials in various configurations. C-2-2.3.2 For purposes of this a p p e n d i x , fires are classified as b e i n g either slow, m e d i u m , or fast developing. C-2-2.3.2.1 that would onds) from fire reaches

T h e slowly d e v e l o p i n g fire is defined as o n e take 400 or m o r e seconds (6 minutes, 40 secthe time that o p e n flaming o c c u r r e d until the a heat release rate of 1000 Btu/sec (1055 kW).

Q = (1000/tg2)t ~- = Btu/sec or kW G r a p h s of heat release data from the forty f u r n i t u r e calo r i m e t e r tests can be f o u n d in reference 8. Best fit powerlaw fire growth curves have been s u p e r i m p o s e d on the graphs. Data from the best fit curves can be used with this a p p e n d i x to design or analyze fire detection systems that must r e s p o n d to similar items b u r n i n g u n d e r a flat ceiling. Table C-2-2.2.2 is a s u m m a r y of that data. For reference, the table contains the test n u m b e r s used in the original National Institute of S t a n d a r d s a n d Technology reports. T h e virtual time of origin, t,,, is the time at

C-2-2.3.2.2 T h e m e d i u m d e v e l o p i n g fire is o n e that would take 150 seconds (2 minutes, 30 seconds) or m o r e a n d less than 400 seconds (6 minutes, 40 seconds) from the time that o p e n flaming occurred until the fire reaches a heat release rate of 1000 Btu/sec (1055 kW). C-2-2.3.2.3 T h e last d e v e l o p i n g fire is o n e that would take less than 150 seconds (2 m i n u t e s , 30 seconds) from the time that o p e n flaming o c c u r r e d until the fire reaches a heat release rate of 1000 Btu/sec (1055 kW).

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX C

Table C-2-2.2.2

ITEM

NO. TEST 15 TEST 18 TEST 19 TEST "29 TEST 21 TEST 21 TEST 21 TEST 22 TEST 23 TEST 24 TEST 25" TEST 26 TEST 27 TEST 28 TEST 29 TEST 29 TEST 30 TEST 31 TEST 37 TEST 38 TEST 39 TEST 40 TEST 4t TEST 42 TEST 42 TEST 43 TEST 44 TEST 45 TEST 46 TEST 47 TEST 48 TEST 49 TEST 50 TEST 51 TEST 52 TEST 53 TEST 54 TEST 55 TEST 56 TEST 57 TEST 61 TEST 62 TEST 64 TEST 66 TEST 67 TEST 67

Furniture Heat Release Rates

GROWTH TIME ( t )

TEST MASS

DESCRIPTION

Metal Wardrobe 41.4 KG (Total) Chair F33 (Trial Loveseat) 39.2 KG .Chair F21 28.15 KG Chair F21 28.15 KG Metal Wardrobe 40.8 KG (Total) Metal Wardrobe 40.8 KG (Total) Metal Wardrobe 40.8 KG (Total) Chair F24 28.3 KG Chair F23 31.2 KG Chair F22 31.9 KG Chair F26 19.2'KG " Chair F27 29:0 KG • Chair F29 14.0 KG Chair F28 29.2 KG Chair F25 27.8 KG Chair F25.27.8 KG Chair F30.25.2 KG Chair F31 (Loveseat) 39.6 KG Chair F31 (Loveseat) 40.40 KG Chair F32 (So(a) 51.5 KG l,~ in. Plywood Wardrobe with Fabrics ".68.5 KG -. "" l~ in. Plywood Wardrobe with Fabrics 68.32 KG ' in. Plywood Wardrobe with Fabrics 36.0 KG in. Plywood Wardrobe w/FireRetardant Int. Fin. in. Plywood Wardrobe w/FireRetardant Int. Fin. Repeat of ~ in. Plywood'Wardrobe 67.62 KG in. Plywood Wardrobe w/F-R Latex Paint 37.26 KG C'hhir F21 28.34 KG" Chair F21 28.34 KG' Chair Adj. Back Metal Frame, Foam Cushions 20.82 KG Easy Chair CO7 (11.52 KG) Easy Chair 15.68 KG (F-34) Chair Metal Frame Minimum Cushion 16.52 KG Chair Molded Fiberglass No Cushion 5.28 KG Molded Plastic Patient Chair 11.26 KG Chair Metal Frame with Padded Seat and Back 15.54 KG Loveseat Metal Frame with Foam Cushions 27.26 KG Chair Wood Frame and Latex Foam Cushions 11.2 KG Loveseat Wood Frame and Foam Cushions 54.60 KG Wardrobe ~ in. Particleboard 120.33 KG Bookcase Plywood with Aluminum Frame 30.39 KGEasy Chair Molded. Flexible Urethane Frame 15.98 KG Easy Chair 23.02 KG Mattress and Boxspring 62.36 KG . Mattress and Boxspring 62.36 KG

72E-47

SECONI~S

CLASSIFICATION (s-slow) m-me di um) (f-fast)

MAXIMUM ALPHA

(x) KW/SEC SQ

VIRTUAL TIME (%) SECONDS

HEAT RELEASE RATES KW

10 140 110 190 10 60 30 400 100 150 90 360 70 90 175 100 70 145 100 5O

750 950 350 2000 250 250 140 700 700 300 800 900 1850 7OO 7OO 2000 950 2600 2750 3000

m

0.4220 0.0066 0.0344 0.4220 0.0169 0.0733 0.1055 0.0086 0.0066 0.0003 0.0264 0.0264

f

o.1055

s

f f f f f f

0.0058 0.2931 0.1055 0.2931 0.2931 0.1648 . 0.1055 ,

35

t

0.8612

20

3250

35

t

0.8612

40

3500

40

f

0.6594

40

6000

70

f

0.2153

50

2000

300

m

0.0117

100

5000

30

*

1.1722

50

3000

90 100 45

f f

0.1302 0.1055 0.5210

30 120 130

2900 2100 2600

30 90 50

250 950 200

50 .4O0 175 5O 25O 120 100 35O 400 2000 200 20O 100 425 6O 100 60 6O 8O 100

f m m

f m

f f m m s m

t

170 175 200

m m

0.0365 0.0344 0.0264

200

m

0.0264

120

3000

120 275

f m

0.0733 0.0140

20 2090

35 700

350

m

0.0086

50

280

0.0042

210

300

m

500

500

s

0.0042

50

85

350

m

0.0086

500

1000

150

0.0469

0

1200

65

0.2497

40

25

0.0011 0.1827 0.0086 . 0.0009

750 3700 4OO 90

1000 76 350 "..1100

s

f m s

450 600 500 400 '

t Fire growth exceeds design data For S! Units: 1 ft = 0.305 m, 1000 BTU/s = 1055 kW, 1 lb = 0.456 kg Q=

x ( t - t v ) , = 1000 ( t

',,

kv,)

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-48

AUTOMATICFIRE DETECTORS

C-2-2.3.3 T h e design fires used in this g u i d e ~row according to the following equation: Q = [1000/(tg) "] t 2, where Q is the heat release in Btu/sec; tg is the fire growth time (149 sec = fast, 150-399 sec = medium, 400 sec = slow); and t is the time, in seconds, after open flaming OCCURS.

C-2-2.4 Selection of Fire Size. The selection of threshold fire size, O~, should be based on an u n d e r s t a n d i n g of the characteristics of a specified space and firesafety objectives for that space. For example, in a particular installation it may be desirable to detect a typical wastebasket fire. Table C-2-2.2. l(b) includes a fire involving a comparable array of combustibles, specifically milk cartons in a wastebasket. Such a fire is indicated to produce a peak b u r n i n g rate of 100 Btu/sec. C-2-3 C e i l i n g H e i g h t .

C-2-3,1 The Fire Detection Institute data are based on the height of the ceiling above the fire. In this guide, it is recommended that the designer use the actual distance from floor to ceiling, since the ceiling height will thereby be more conservative, and actual detector response will improve when the potential fuel in a room is above floor level. C-2-3.2 W h e r e the d e s i g n e r desires to c o n s i d e r the height of the potential fuel in the room, the distance between the fuel and the ceiling should be used as the ceiling height. This should be considered only when the minimum height of the potential fuel is always constant, and where the concept is acceptable to the authority having jurisdiction. C-2-3.3 The procedures presented in this appendix are based on an analysis of test data for ceiling heights up to 30 ft (9.1 m). No data was analyzed for ceilings greater than 30 ft (9.1 m). Therefore, in such installations engineering j u d g m e n t and manufacturers' recommendations should be used. C-3 H e a t Detectors. C-3-1 G e n e r a l .

C-3-1.1 This chapter discusses procedures for determination of installed spacing of listed heat detectors used to detect flaming fires. C-3-1.2 T h e d e t e r m i n a t i o n of the installed spacing of heat detectors using these procedures adjusts the listed spacing to reflect the effects of ceiling height, threshold fire size, rate of fire development, and, for fixed temperature detectors, the ambient temperature and the temperature rating of the detector.

possible. To reduce u n w a n t e d alarms, the difference between operating temperature and ambient temperature should be not less than 25°F (14°C). C-3-1.5 Listed rate-of-rise heat detectors are designed to activate at a nominal rate of temperature rise of 15°F per minute (8.3°C/rain). C-3-1.6 The listed spacing of a detector is an indicator of the detector's sensitivity. Given the same temperature rating, a detector listed for a 50 ft (15.2 m) spacing is more sensitive than one listed for a 20 ft (6.1 m) spacing. C-3-1.7 When using combination detectors incorporating both fixed t e m p e r a t u r e and rate-of-rise heat detection principles to detect a geometrically growing fire, the data herein for rate-of-rise detectors should be used in selecting an installed spacing because the rate-of-rise principle controls the response. C-3-1.8 Rate compensated detectors are not specifically covered by this appendix. However, a conservative approach .to predicting their performance is to use the fixed temperature guidance contained herein. C-3-2 F i x e d T e m p e r a t u r e H e a t D e t e c t o r S p a c i n g .

C-3-2.1 Tables C-3-2.1.1 and C-3-2.1.2(a) through (y) are to be used to determine the installed spacing of fixed temperature heat detectors. The analytical basis for the tables is presented in this appendix. This section describes how the tables are to be used. C-3-2.1.1 Except for ceiling height, the nearest value shown in the tables will provide sufficient accuracy for these calculations. Interpolation is allowable but not necessary except for ceiling height. Table C-3-2.1.1

Time Constants for any Listed Detector (BET TC) (sec)*

Listed Spacing fit)

UL 128 °

135 °

145 °

160 °

170 °

196 °

10 15 20 25 30 40 50 70

400 250 165 124 95 71 59 36

330 190 135 100 80 57 44 24

262 156 105 78 61 41 30 9

195 110 70 48 36 18

160 89 52 32 22

97 45 17

FM All Temp

195 110 70 48 36

NOTE 1: Thesetime constantsare based un an analysisof the Underwriters Laboratories Inc. and Factory Mutual listing test procedures. Phmge test~results performed on the detector to be used willgive a more accurate time constant. See Section C-6 of this appendix fi~r a further discussionof detector time constants. NOTE 2: These time constantscan be converted to response time index (RTI) values by multiplyingby ~//5 ft/sec.(See. C-6-3.) *At a reference velocityof 5 ft/sec.

C-3.1.3 Other factors that will affect detector response are treated in Chapter 3.

C-3-2.2 Given the detector's listed spacing and the detector's rated temperature (Ts), use Table C-3-2.1.1 to find the detector time constant (DET TC). The time constant is a measure of the detector's sensitivity. See Section C-5.

C-3-1.4 T h e difference between the rated temperature of a fixed temperature (T~) detector and the m a x i m u m ambient temperature (To) at the ceiling should be as small as

C-3-2.2.1 Response time index (RTI) can also be used to describe the sensitivity of a fixed temperature heat detector. See Section C-6.

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX C

72E-49 Table C-3-2.1.2(a) Threshold Fire Size at Respond: 250 BTU/SEC. Fire Growth Rate: 50 Seconds to 1000 BTU/SEC Alpha: 0.400 BTU/SEC'

Estimate the m i n i m u m a m b i e n t t e m p e r a t u r e (To) expected at the ceiling of the space to be protected• Calculate the t e m p e r a t u r e c h a n g e (&T) of the d e t e c t o r r e q u i r e d for detection (&T = T~ - To).

C-3-2.3

CEILING HEIGHT IN FEET

H a v i n g d e t e r m i n e d t h e d e t e c t o r ' s sensitivity (time constant o r RTI) (C-3-2.2), the t e m p e r a t u r e c h a n g e of the d e t e c t o r r e q u i r e d for detection (C-3-2.3), the threshold fire size (C-2-2.2), the fire g r o w t h rate (C-2-2.3), and the ceiling height, use Tables C-3-2.1.2(a) t h r o u g h (y) to d e t e r m i n e the r e q u i r e d installed spacing. C-3-2.4

C-3-2.5 Example.

Input."

Ceiling Height: Detector T y p e :

Spacing:

F r o m T a b l e C-3-2.1.1, the d e t e c t o r time constant is 80 seconds. (RTI = 80 ~/g'-- = 180 ft u~ sec I/=) ~ ' r = T , - T o = 135-55 = 80°V F r o m T a b l e C-3-2.1.1(j): For D E T T C = 75 s e c - - spacing = 17 ft For D E T T C -- 1 0 0 s e c - - spacing = 1 6 f t By interpolation: Spacing = 1 7 - [(17-16)(80-75/100-75)] = 16.8

8 ft Fixed t e m p e r a t u r e 30 ft U L listed spacing 135°F rated t e m p e r a t u r e Qd = 500 Btu/sec Fire G r o w t h Rate = slow tg = 600 sec. (X = .003 Btu/sec ~) M i n i m u m A m b i e n t T e m p e r a t u r e = 55°F

Note: If the ceiling height is 16 It, the spacing is 8.8 ft. Using the'detector in the above example, at a ceiling height of 28 ft, no practical spacing would ensure detection of the tire at the threshold fire size of 500 Btu/sec. A more sensitive detector would need to be used. These results clearly illustrate the need to consider ceiling height in the design of a detection system. For SI Units:

I ft = 0.305 m.

TAU RTI &T .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

.

12,0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20,0 .

.

.

.

.

.

.

24.0

28.0 .

.

INSTALLED SPACING OF DETECTORS 25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559

40 60 80 100 i20 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120

7 6 5 4 4 3 5 4 3 3 2 2 4 3 2 2 2 1 3 2 2 1 1 1 3 2 1 1 0 0 2 2 1 0 0 0 2 1 1 0 0 0 2 1 O 0 0 0 2 1 0 0 0 0 2 0 0 0 0

5 3 2 2 1 1 3 2 1 0 0 0 2 1 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 O 0 0 0 0 0 0 0 -0 0 0 0 0 0 0 0 0

2 1 0 0 0 O 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 O O 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 O 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-50

AUTOMATIC FIRE DE'I'ECTORS

Table C-3-2. 1.2(b) Threshold Fire Size at Response: 250 B T U / S E C . Fire Growth Rate: 150 Seconds to 1000 B T U / S E C Alpha: 0.044 BTU/SEC~

Table C-3-2.1:2(a) T h r e s h o l d Fire Size at Response: 250 B T U / S E C . Fire Growth Rate: 50 Seconds to 1000 B T U / S E C Alpha: 0.400 B T U / S E C s

CEILING HEIGHT IN FEET TAU RTI &T .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

CEILING HEIGHT IN FEET

24.0

28,0

.

TAU RTI &f .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

INSTALLED SPACING OF DEFECTORS 250 559 140 275 615 40 275 615 60 275 615 80 275 615 100 275 615 120 275 615 140 300 671 40 300 671 60 300 671 80 300 671 100 300 671 120 300 671 140 325 727 40 325 727 60 325 727 80 325 727 100 325 727 120 325 727 140 350 783 40 350 783 60 350 783 80 350 783 100 350.783 120 350 783 140 375 839 40 375 839 60 375 839 80 375 839 100 375 839 120 375 839 140 400 894 40 400 894 60 400 894 80 400 894 100 400 894 120 400 894 140

0 1 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

.

.

.

.

.

.

8.0 ..

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

.

.

.

.

.

28.0

.

INSTALLED SPACING OF DETECTORS 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 .0 0 0 0 0 0 0 0

NOTE: Detector time constant at a reference velocity of 5 ft/sec. For Sl Units: I ft = 0.$05 m 1000 BTU/sec --- 1055 kW

25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40

150 150 150 150 150 175 175 175 175

335 335 335 335 335 391 391 391 391

60 80 100 120 140 40 60 80 100

175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

15 12 10 9 8 7 11 9 7 6 6 5 9 7 6 5 4 4 8 6 5 4 4 3 7 5 4 4 3 3 6

12 9 7 6 4 4 9 6 5 4 3 2 7 5 3 3 2 1 6 4 3 2 1 1 .5 3 2 1 1 0 4

S 3 3 2 6 4 3 3

2 2 1 0 0 3 2 1 1

2 2 5 4 3 3 2 2 5 4 3 2 2 2 5 3 3 2 2 1 4 3 2 2

0 0 3 2 1 0 0 0 3 2 1 0 0 0 2 1 0 0 0 0 2 1 0 0

4

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

9 6 4 2 1 1. 6 3 2 1 1 0 4 2

6 3 1 0 0 0 3 1 0 0 b 0 2 0

1

0

0 0 0 3 2 1 0 0 0 2 1 0 0 0 0 2 1 0 0 0 0 1 0 0 0 0 0 I 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

.0 O. 0 1 0 0 0 '0 0 I 0 0 0 0 O. 0.. 0 O 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 I

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 O. 0 0 0 0 0 0 O, 0 0 O 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0" 0 0 0 0 0 0 0 0 0 0 0 0 0 O, 0 0 0 • 0 0 0 O. O. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX C

72E-51

Table'C-3-2. 1.2(c)

T a b l e C-3-2.1.2(b) T h r e s h o l d Fire Size at Response: 250 B T U / S E C . Fire G r o w t h g a t e : 150 Seconds to 1000 B T U / S E C A l p h a : 0.044 B T U / S E C 5

T h r e s h o l d G r o w t h Rate: 300 Seconds to 1000 B T U / S E C Fire G r o w t h Rate: 300 Seconds to 1000 B T U / S E C Alpha: 0 . 0 1 l B T U / S E C s

CEILING HEIGHT IN FEET TAU RTI 5T

4.0

8.0

12.0

16.0

20.0

24.0

CEILING HEIGHT IN FEET 28.0

TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

INS[ALLED SPACING OF DETECTORS 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 120 615 140 671 40 671 60 671 80 671 100 671 120 671 140 727 40 727 60 727 80 727 100 727 120 727 140 783 40 783 60 783 80 783 100 783 120 783 140 839 40 839 60 839 80 839 1.00 839 120 839 140 894 40 894 60 894 80 894 100 894 120 894140

2 1 4 3 2 2 1 1 4 3 2 2 1 1 4 3 2 2 1 1 3 2 2 1 1 0 3 2 2 1 1 0

0 0 2 1 0 0 0 0 2 1 0 0 0 0 2 0 0 0 0 0 1 0 "0 0 0 .0 1 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

1 ft = 0.305 m 1000 B T U / s e c = 1055 k W

.

.

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

.

20.0 .

24.0

28.0

.

INSTALLED SPACING OF DETECTORS 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 .0 0

N O T E : Detector time constant at a reference velocity of 5 ft/sec. ForS1 Units:

4.0 .

25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

21 17 14 12 11 10 17 13 11 10 8 8 14 11 9 8 7 6 12 10 8 7 6 5 11 9 7 6 5 5 10 8 6 8 S 4 9 7 6 5 4 4 9 7 5 5 4 3 8 6 S 4 4 3 8 6 5 4 3 3 7 6 4 4

18 13 10 8 7 6 4 0 8 6 5 4 1 8 6 5 4 3 10 7 5 4 3 3 9 6 4 3 3 2 8 5 4 3 2 2 7 5 3 3 2 1 6 4 3 2 2 1 6 4 3 2 1 1 5 3 2 2 1 1 5 3 2 1

14 9 6 4 3 2 11 7 5 3 2 1 8 5 3 2 1 1 7 4 3 2 1 0 6 3 2 1 1 0 5 3 2 1 0 0 4 2 1 1 0 0 4 2 1 0 0 0 3 2 1 0 0 0 3 1 0 0 0 0 3 1 0 0

10 6 5 2 3 0 1 0 0 0 0 0 7 4 4 1 2 0 0 0 0 0 0 0 6 3 3 1 1 0 0 0 0 0 0 0 4 2 2 0 1 0 0 0 0 0 0 0 3 1 1 0 0 0 0 0 0 0 0 0 3 1 1 " 0 0 0 0 0 0 0 0 0 2 1 1 0 0 0 0 0 0 0 0 0 2 0 0 0 0 0 0 0 0 0 0 0 2 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 0 0 0 0

3 0 0 0 0 0 2 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-52

A U T O M A T I C FIRE DETECTORS

T a b l e C-3-2.1.2(c) T h r e s h o l d G r o w t h Rate: 300 Seconds to 1000 B T U / S E C Fire G r o w t h Rate: 300 Seconds to 1000 B T U / S E C A l p h a : 0.011 B T U / S E C s

T a b l e C-3-2.1.2(d) T h r e s h o l d Fire Size at Response: 250 B T U / S E C . Fire G r o w t h Rate: 500 Seconds to 1000 B T U / S E C A l p h a : 0.004 B T U / S E C s

CEILING HEIGHT IN FEET TAU RTI &T .

.

.

.

.

.:

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

CEILING HEIGHT IN FEET 28.0

.

TAU .

.

.

.

.

RTI AT .

.

.

.

.

.

.

.

.

.

INSTALLED SPACING OF DETECTORS 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

3 3 7. 5 4 3 3 3 7 5 4 3 3 2 6 5 4 3 3 2 6 4 4 3 2 2 6 4 3 3 2 2

1 0 5 3 2 1 1 0 4 3 2 1 1 0 4 2 2 1 0 0 4 2 1 1 0 0 3 2 1 1 0 0

0 0 2 1 0 0 0 0 2 1 0 0 0 0 2 1 0 0 0 0 2 0 0 0 0 0 2 0 0 0 0 0

0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0' 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

1 ft = 0.305 m 1000 B T U / s e c -- 1055 k W

.

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0

28.0

5 0 0 0 0 0 4 0 0 0 0 0 3 0 0 0 0 0 2 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

1 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0' 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

.

INSTALLED SPACING OF DETECTORS 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

N O T E : Detector time constant at a reference velocity of 5 ft/sec. F o r S I Units:

4.0 .

25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

56 40 56 60 56 80 56 100 56 120 56 140 112 40 112 60 112 80 112 100 112 120 112 140 168 40 168 60 168 80 168 100 168 120 168 140 224 40 224 60 224 80 224 100 224 120 224 140 280 40 280 60 280 80 280 100 280 120 280 140 335 40 335 60 335 80 335 100 335 120 335 140 391 40 391 60 391 80 391 100 391 120 391 140 447 40 447 60 447 80 447 100 447 120 447 140 503 40 503 60 503 80 503 100 503 120 503 140 559 40 559 60 559 80 559 100 559 120 559 140 615 40 615 60 615. 80 615 100

26 20 17 15 13 11 21 17 14 12 11 9 18 14 12 10 9 8 16 13 11 9 8 7 15 12 10 8 7 6 14 11 9 8 7 6 13 10 8 7 6 5 12 9 8 6 6 5 11 9 7 6 5 5 11 8 7 6 5 4 10 8 6 5

22 16 12 10 8 7 18 13 10 8 7 6 15 11 9 7 6 5 14 10 8 6 5 4 12 9 7 5 4 3 11 8 6 5 4 3 10. 7 5 4 3 3 9 7 5 4 3 2 9 6 5 3 3 2 8 6 4 3 2 2 8 5 4 3

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

17 11 8 5 4 2 14 9 6 4 3 2 12 8 5 4 2 1 10 7 4 3 2 1 9 6 4 2 1 1 8 5 3 2 1 1 7 4 3 2 1 0 7 4 2 1 1 0 6 4 2 1 1 0 6 3 2 1 0 0 5 3 2 1

13 7 4 1 0 0 11 6 3 1 0 0 9 5 2 1 0 0 7 4 2 0 0 0 6 3 1 0 0 0 5 3 1 0 0 0 5 2 1 0 0 0 4 2 1 0 0 0 4 1 0 0 0 0 3 1 0 0 0 0 3 1 0 0

9 3 0 0 0 0 7 2 0 0 0 0 6 2 0 0 0 0 4 1 0 0 0 0 4 1 0 0 0 0 3 1 0 0 0 0 2 0 0 0 0 0 2 0 0 0 0 0 2 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

API'ENDIX C

72E-53

T a b l e C-3-2.1.2(d) T h r e s h o l d Fire Size at Response: 250 B T U / S E C . Fire Growth Rate: 500 Seconds to 1000 B T U / S E C Alpha: 0.004 B T U / S E C s

T a b l e C-3-2.1.2(e) T h r e s h o l d Fire Size at Response: 250 B T U / S E C . Fire Growth Rate: 600 Seconds to 1000 B T U / S E C Alpha: 0.003 B T U / S E C s

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU .

.

.

.

RTI &T .

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0

28.0

RTI &T

TAU .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

5 4 10 7 6 5 " 4 4 9 7 6 5 4 4 9 7 6 5 4 3 9 6 5 4 4 3 8 6 5 4 4 3

2 2 1 0 0 0 0 0 1 0 0 O 0 0 1 0 O. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 7 5 4 3 2 2 7 5 3 2 2 1 6 4 3 2 2 1 6 4 3 2 2 1 6 4 3 2 1 1

0 0 5 3 1 1 0 0 4 2 1 0 0 0 4 2 1 0 0 0 4 2 1 0 .0 0 4 2 1 0 0 .0

0 0 3 1 0 0 0 0 2 1 0 0 0 0 2 0 0 0 0 0 2 0 0 0 0 0 2 " 0 0 0 0 0

N O T E : Detector time constant at a reference velocity of 5 ft/sec. For SI Units:

I ft = 0.305 m 1000 B T U / s e c = 1055 k W

.

.

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

.

20.0

24.0

28.0

.

INSTALLED SPACING OF DETECTORS

INSTALLED SPACING OF DEFECTORS 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

4.0 .

25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

28 22 18 15 13 12 23 18 15 13 11 10 20 16 13 11 10 9 18 14 12 10 9 8 16 13 11 9 8 7 15 12 10 8 7 7 14 11 9 8 7 6 13 10 8 7 6 6 12 10 8 7 6 5 12 9 8 6 6 5 11 9 7 6

23 17 13 10 8 7 19 14 11 9 7 6 17 12 10 8 6 5 t5 11 8 7 5 5 14 10 8 6 5 4 12 9 7 5 4 4 11 8 6 5 4 3 11 8 6 4 4 3 10 7 5 4 3 3 9 7 5 4 3 2 9 6 5 3

18 12 8 6 4 3 15 10 7 5 3 2 13 9 6 4 3 2 12 8 5 4 2 1 10 7 4 3 2 1 9 6 4 3~ 2 ~ /9 5 3 2 1 1 8 5 3 2 1 1 7 4 3 2 1 0 7 4 2 1 1 0 6 4 2 1

14 8 4 2 0 0 12 6 3 1 0 0 10 5 3 1 0 0 9 . 4 2 1 0 0 7 4 2 O 0 0 7 3 1 0 0 0 6 3 1 0 0 0 5 2 1 0 0 0 5 2 1 0 0 0 4 2 1 0 0 0 4 1 0 0

9 4 0 0 0 0 8 3 0 0 0 0 7 2 0 0 0 0 5 2 0 0 0 0 5 1 0 0 0 0 4 1 0 0 0 0 3 1 0 0 0 0 3 1 0 0 0 0 2 0 0 0 0 0 2 O 0 0 0 0 2 0 0 0

5 0 0 0 0 0 4 0 0 0 O 0 3 0 0 0 0 0 3 0 0 0 0 0 2 0 0 0 0 0 2 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0

2 0 0 0 . 0 0 1 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-54

AUTOMATIC FIRE DE'I'ECI'ORS

T a b l e C-3-2. 1.2(f) T h r e s h o l d Fire Size at Response: 500 B T U / S E C . Fire Growth Rate: 50 Seconds to 1000 B T U / S E C Alpha: 0.400 B T U / S E C ~

T a b l e (]-3-2.1.2(e) T h r e s h o l d Fire Size at Response: 250 B T U / S E C . Fire Growth Rate: 600 Seconds to 1000 B T U / S E C Alpha: 0.005 B T U / S E C j

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET

TAU RTI AT .

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

8.0 .

.

.

.

.

TAU

1 2 . 0 1 6 . 0 2 0 . 0 2 4 . 0 28.0 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.. .

..

.

..

RTI aT .

.

.

.. .

..

.

.

.

.

.

4.0 .

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

NOTE:

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

5 5 11 8 7 6 5 4 10 8 6 6 5 4 10 8 6 5 5 4 10 7 6 5 4 4 9 7 6 5 4 4

3 2 8 6 4 3 2 2 8 5 4 3 2 2 7 5 4 3 2 2 7 5 3 3 2 1 7 5 3 2 2 1

1 0 6 3 2 1 0 0 5 3 2 1 0 0 5 3 2 1 0 0 5 3 1 1 0 0 4 2 1 0 0 0

0 0 3 1 0 0 0 0 3 1 0 0 0 0 3 1 0 0 0 0 3 1 0 0 0 0 2 1 0 0 0 0

0 0 1 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 1 0 0 O 0 0 1 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 -0 0 0 0 0 0 0 0 0 0 0 '0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 O 0 0 0 0 O 0 0 0 0 0

Detector t i m e c o n s t a n t at a r e f e r e n c e velocity Of 5 ft/sec.

F o r S l Units:

1990 Edition

lft = 0.305m 1000 B T U / s e c = 1055 k W

.

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0

28.0

.

INSTALLED SPACING OF DETECTORS

INSTALLED SPACING OF DETECTORS 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

.

25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

13 11 9 8 7 7 10 8 7 6 5 5 8 6 5 4 4 3 7 5 4 4 3 3 6 5 4 3 3 2 5 4 3 3 2 2 5 4 3 2 2 2 5 3 3 2 2 l 4 3 2 2 2 1 4 3 2 2 1 1 4 3 2 2

11 8 6 5 4 4 7 5 4 3 3 2 6 4 3 2 2 1 4 3 2 1 1 0 4 2 2 1 0 0 3 2 1 0 0 0 3 2 1 0 0 0 2 1 0 0 0 0 2 1 0 0 0 0 2 1 0 0 0 0 2 0 0 0

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

8 5 4 3 2 1 5 3 2 1 0 0 3 2 1 0 0 0 2 1 0 0 0 0 2 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 O O 0 0 0 0 0 0 0 0 0

5 3 1 1 0 0 2 1 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 O 0 0 0 0 O 0 0 0 0

2 1 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 O 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

1 0 0 O 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 O 0 O 0 0 0 0 0 0 0 O 0 0 0 0 0 0

0 0 0 0 0 0 0 O .0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 • 0. 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 O 0 0 0 0 0 0 0 0 O 0

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX C

72E-55

T a b l e C-3-2.1.2(g) T h r e s h o l d Fire Size at Response: `500 B T U / S E C . Fire G r o w t h Rate: 150 Seconds to 1000 B T U / S E C A l p h a : 0.044 B T U / S E C s

T a b l e C-3-2. 1,2(f) T h r e s h o l d Fire.Size at Response: 500 B T U / S E C . Fire G r o w t h Rate: 50 Seconds to 1000 B T U / S E C A l p h a : . 0.400 B T U / S E C s

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET IAU .

.

.

.

RTI AT .

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

.

.

12.0

.8.0 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0

28.0

TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

120 140 40 60 80 ,100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120

400 894 140

1 1 3 2 2 1 1 0 3 2 2 1 1 0 3 2 2 1 0 0 3 2 1 1 0 0 3 2 1 1 0 0

0 0 1 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 .0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 .0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ..0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 '0 0 0 0 0 0 0 0 0 0 0 0 0 0

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

28.0

.

INSTALLED SPACING OF DETECTORS

INSTALLED SPACING OF DETECTORS 275 615 275 615 300 671 300 671 300 671 300 671 300 671 300 671 325 727 325 727 325 727 325 727 325 727 325~727 350 783 350 783 350 783 350 783 350 783 350 783 375 839 375 839 375 839 375 839 375839 375 839 400 894 400 894 400 894 400 894 400 894

.

0 0 0 0 0 0 0 0 0 0 0 O O. 0 0 0 -0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

N O T E : Detector time constant at a reference velocity of ,5 ft/sec. For SI Units: 1 ft = 0.305 m 1000 B T U / s e c = 10,5,5 k W

25 25 25 25 25 25 50 50 . 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40. 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

24 20 17 15 13 12 19 15 13 11 10 9 16 13 11 10 8 8 14 1~ 10 8 7 7 13 10 8 7 6 6 12 9 8 7 6 5 11 8 7 6 5 5 108 7 6 5 4 9 7 6 5 5 4 9 7 6 5 4 4 8 7 5 5

22 18 17 13 14 10 11 8 10 6 8 5 16 14 13 10 10 7 9 5 7 4 6 3 14 11 10 8 8 5 7 4 6 3 5 2 12 9 9 6 7 4 6 3 5 2 4 . 2 10 8 8 5 6 3 5 2 4 2 3 1 9 7 7 4 5 3 4 2 3 1 3 1 8 6, 6 4 5 2 4 2 3 1 2 0 8 5 5 3 4 2 3 1 2 1 2 0 7 5 5 3 4 2 3 1 2 0 2 0 7 4 5 2 3 1 3 1 2 0 2 0 6 4 4 2 3 1 2 0

15 10 6 4 3 1 11 7

11 6 3 1 0 0 8 4

4

2

3 1 1 8 5 3 2 1 0 6 4 2 1 0 0 5 3 1 1 0 0 4 2 1 0 0 0 4 2 1 0 0 0 3 1 0 0 0 0 3 1 0 0 0 0 2 1 0 0 0 0 2 0 0 0

0 0 0 5 2 1 0 0 0 4 2 0 0 0 0 3 1 0 0 0 0 2 1 0 0 0 0 ,.2 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0

8

5

3 0 0 0 0 5 1 0 0 0 0 3 1 0 0 0 0 2 0 0 0 0 0 1. 0 0 0 0 0

0 0 0.. 0 0 2 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0

1

0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 . 0 0 0 0 0 0 0 0 0 0 0 0 0 O 0 0 0 0 0 0 0 0 0 0 0 0 0 0

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-56

A U T O M A T I C FIRE DETECTORS

Table C-3-2.1.2(g) Threshold Fire Size at Response: 500 B T U / S E C . Fire Growth Rate: 150 Seconds to 1000 B T U / S E C Alpha: 0.044 B T U / S E C '

T a b l e C,-3-2.1.2(h)

Threshold Fire Size at Response: 500 B T U / S E C . Fire Growth Rate: 300 Seconds to 1000 B T U / S E C Alpha: 0.011 B T U / S E C '

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

CEILING HEIGHT IN FEET

2 4 . 0 . 28.0

TAU RTI AT

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

INSTALLED SPACING OF DETECTORS 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

4 3 8 6 5 4 4 3 8 6 5 4 3 3 7 6 5 4 3 3 7 5 4 4 3 3 7 5 4 3 3 3

2 1 6 4 3 2 2 1 5 4 3 2 1 1 5 3 2 2 1 1 5 3 2 2 1 0 4 3 2 1 1 0

0 0 3 2 1 0 0 0 3 2 1 0 0 0 3 1 0 0 0 0 3 1 0 0 0 0 2 1 0 0 0 0

0 0 2 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 1 0 0 O" 0 0

, 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 ' 0 0 0 0 0 0 0 0 0 0

1990 Edition

I ft = 0 . S 0 5 m 1000 B T U / s e c = 1055 kW

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

24~0 .

.

.

.

.

.

.

28.0 .

.

.

.

INSTALLED SPACING OF DETECTORS 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 O' 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 .0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

N O T E : Detector time constant at a reference velocity of 5 ft/sec. F o r S l Units:

.

25 56 25 56 25 56 25 56 25 56 25 56 50 112 50 112 50 112 50 112 50 112 50 112 75 168 75 168 75 168 75 168 75 168 75 168 100 224 100 224 100 224 100 224 100 224 100 224 125 280 125 280 125 280 125 280 125 280 125 280 150 335 150.335 150 335 150 335 150 335 150 335 175 391 175 391 175 391 175 391 175 391 175 391 200 447 200 447 200 447 200 447 200 447 200 447 225 503 225 503 225 503 225 503 225 503 225 503 250 559 250 559 250 559 250 559 250 559 250 559 275 615 275 615 275 615 275 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80. 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

34 27 23 20 18 16 27 22 18 16 14 13 23 19 16 14 12 11 21 17 14 12 11 10 19 15 13 11 10 9 17 14 12 10 9 8 16 13 11 9 8 7 15 12 10 9 8 7 14 11 10 8 7 6 14 11 9 8 7 6 13 10 9 7

30 23 18 15 13 11 24 18 15 12 11 9 21 16 13 11 9 8 18 14 11 9 8 7 16 12 10 8 7 6 15 11 9 7 6 5 14 10 8 7 6 5 13 10 8 6 5 4 12 9 7 6 5 4 11 8 6 5 4 4 11 8 6 5

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

25 18 14 11 8 7 21 15 11 9 7 5 18 13 9 7 6 4 15 11 8 6 5 4 14 10 7 5 4 3 12 8 6 5 3 3 11 8 5 4 3 2 10 7 5 4 3 2 10 6 4 3 2 2 9 6 4 3 2 1 8 5 4 3

.21 14 9 7 4 3 17 11 8 5 3 2 14 9 6 4 3 1 12 8 5 3 2 1 11 7 4 3 2 1 10 6 4 2 1 1 9 5 3 2 1 0 8 4 3 1 1 0 7 4 2 1 1 0 6 3 2 1 0 0 6 3 2 1

17 10 5 3 1 0 14 8 4 2 0 0 11 6 3 1 0 0 9 5 2 1 0 0 8 4 2 1 0 0 7 3 1 0 0 0 6 3 1 0 0 0 5 2 1 0 0 0 5 2 1 0 0 0 4 2 0 0 0 0 4 1 0 0

13 6 2 0 0 0 10 4 1 0 0 0 8 3 1 0 0 0 6 2 0 0 0 0 5 2 0 0 0 0 4 1 0 0 0 0 4 1 0 0 0 0 3 1 0 0 0 0 3 0 0 0 0 0 2 0 0 0 0 0 2 0 0 0

9 2 0 0 0 0 7 1 0 0 0 0 5 1 0 0 0 0 4 0 0 0 0 0 3 0 0 0 0 0 2 0 0 0 0 0 2 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0

.

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-57

APPENDIX C

Table C-3-2.1.2(i) Threshold Fire Size at Response: 500 B T U / S E C . Fire Growth Rate: 500 Seconds to 1000 B T U / S E C Alpha: 0.004 B T U / S E C '

Table C-3-2. 1.2(h) T h r e s h o l d Fire Size at Response: 500 B T U / S E C . Fire Growth Rate: ~ 0 $ecemda to 1000 B T U / $ E C Alpha: 0.011 B T U / S E C !

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

.

24.0 .28.0 .

.

.

.

.

.

.

.

.

.

.

.

TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

NOTE:

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

6 6 12 10 8 7 6 6 12 9 8 7 6 5 12 9 7 6 6 5 11 9 7 6 5 5 11 8 7 6 5 5

4 3 10 7 6 5 4 3 10 7 5 4 3 3 9 7 5 4 3 3 9 6 5 4 3 2 8 6 4 3 3 2

2 1 8 5 3 2 2 1 7 5 3 2 1 1 7 4 3 2 1 1 6 4 3 2 1 0 6 4 2 1 1 0

0 0 5 3 1 1 0 0 5 2 1 0 0 0 4 2 1 0 0 0 4 2 1 0 0 0 4 2 1 0 0 0

0 0 3 1 0 0 0 0 3 1 0 0 0 0 3 1 0 0 0 0 2 0 0 0 0 0 2 0 0 0 0 0

0 0 2 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0

D e t e c t o r t i m e c o n s t a n t at a r e f e r e n c e velocity of 5 f t / s e c .

F o r S l Units:

1 ft = 0.SO5 m 1000 B T O / s e c = 1055 k W

.

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 2 0 . 0 .

.

.

.

.

.

.

.

.

.

.

.

24.0 .

.

.

.

.

.

.

28.0 .

.

.

.

.

.

INSTALLED SPACING OF DETECTORS

INSTALLED SPACING OF DETECTORS 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

4.0 .

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

25 56 25 56 25 56 25 56 25 56 25 56 50 112 50 112 50112 50 112 50 112 50 112 75 168 75 168 75 168 75 168 75 168 75 168 100 224 100 224 100 224 100 224 100 224 100 224 125 280 125 280 125 280 125 280 125 280 125 280 150 335 150 335 150 335 150 335 150 335 150 335 175 391 175 391 175 391 175 391 175 391 175 391 200 447 200 447 200 447 200 447 200 447 200 447 225 503 225 503 225 503 225 503 225 503 225 503 250 559 250 559 250 559 250 559 250 559 250 559 275 615 275 615 275 615 275 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

41 32 27 23 20 18 34 27 23 20 17 16 30 24 20 17 15 14 27 21 18 16 14 13 25 20 16 14 13 11 23 18 15 13 12 11 21 17 14 12 11 10 20 16 13 12 10 9 19 15 13 11 10 9 18 14 12 10 9 8 t7 14 12 10

35 26 21 17 15 13 30 23 18 15 13 11 26 20 16 14 11 10 24 18 15 12 10 9 22 17 13 11 9 8 20 15 12 10 9 7 19 14 11 9 8 7 18 13 11 9 7 6 17 13 10 8 7 6 16 12 9 8 6 6 15 11 9 7

30 21 16 .12 10 8 26 18 14 11 9 7 23 16 12 10 8 6 20 15 11 9 7 5 19 13 10 8 6 5 17 12 9 7 5 4 16 11 8 6 5 4 15 10 8 6 4 3 14 10 7 5 4 3 13 9 7 5 4 3 12 8 6 5

25 16 11 8 5 3 22 14 10 7 5 3 19 13 9 6 4 2 17 11 8 5 3 2 15 10 7 5 3 2 14 9 6 4 3 1 13 8 5 3 2 1 12 7 5 3 2 1 11 7 4 3 2 1 10 6 4 2 1 1 10 6 4 2

20 12 7 4 1 0 18 10 6 3 1 0 15 9 5 2 1 0 14 8 4 2 0 0 12 7 4 2 0 0 11 6 3 1 0 0 10 5 3 1 O 0 9 5 2 1 0 0 8 4 2 1 0 0 8 4 2 1 0 0 7 3 1 O

16 7 3 0 0 0 14 . 6 2 0 0 0 12 5 2 0 0 0 10 .4 1 0 0 0 9 4 1 0 0 0 8 3 1 0 0 0 7 3 1 0 0 0 6 2 0 0 0 0 6 2 0 0 0 O 5 2 O 0 0 0 5 1 0 0

11 3 0 0 0 0 10 3 0 0 0 0 8 2 0 0 0 0 7 2 0 0 0 0 6 1 0 0 0 0 5 1 0 0 0 0 4 1 0 0 0 0 4 1 0 0 0 0 3 0 0 0 0 0 3 0 0 0 0 0 2 0 0 0

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-58

A U T O M A T I C FIRE DETECTORS

Table C-3-2.1.2(i) T h r e s h o l d F i r e Size a t Responsi~: 500 B T U / S E C .

Table C-3-2.1 .')(j) Threshold Fire Size at Response: ~00 nTU/SE¢. Fire Growth Rate: 600 Seconds to I000 B T U / S E C Alpha: 0.003 B T U / S E C '

Fire Growth Rate: 500 Seconds to 1000 B T U / S E C Alpha: 0.004 B T U / S E C s

CEILING HEIGHT IN FEET TAU RTI &f .

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

.

.

CEILING HEIGHT IN FEET

24.0 "28.0

TAU RTI i f

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

INSTALLED SPACING OF DETECTORS 275 275 300 300 300 300 300 300 325 325. 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 639 839 839 839 839 894 694 894 894 894 894

NOTE:

120 140 40 60 80 100 120 140 40 60 80 100 t20 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

6 5 14 11 8 7 6 5 14 10 8 7 5 5 13 10 8 6 5 4 13 9 7 6 5 4 12 9 7 6 5 4

3 3 12 8 6 4 3 2 11 8 5 4 3 2 11 7 5 4 3 2 10 7 5 3 2 2 10 6 4 3 2 2

1 1 9 5 3 2 1 0 9 5 3 2 -1 .0 8 5 3 2 1 0 8 4 2 1 1 0 7 4 2 1 1 0

0 0 6 3 . 1 0 0 0 6 3 1 0 0 0 6 2 1 0 0 0 5 2 1 0 0 0 5 2 1 0 0 0

1 ft = 0 . 3 0 5 m 1000 B T U / s e c = 1.055 k W

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

12.O .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

.

28.0

.

INSTALLED SPACING OF DETECTORS 0 0 4 1 0 0 0 0 4 1 0 0 0 0 3 1 0 0 0 0 3 1 0 0 0 0 3 1 0 0 0 0

Detector t i m e c o n s t a n t at a r e f e r e n c e velocity of 5 ft/sec.

F o r S l Units:

1990

9 8 17 13 11 10 8 8 16 13 11 9 8 7 16 12 10 9 8 '7 "15 12 10 8 7 7 14 11 9 8 7 6

.

0 0 2 0 0 0 0 0 2 0 0 0 0 0 2 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0

25 56 2 5 56 25 56 25 56 26 56 25 56 50 112 50 112 50 112 50 112 50.112 50 112 75 168 75 168 75 168 75 168 75 168 75 168 100 224 100 224 100 224 100 224 100 224 100 224 125 280 125 280 125 280 125 280 125 280 125 280 150 335 150 335 150 335 150 335 150 335 150 335 175 391 175 391 175 391 175 391 175 391 175 391 200 447 200 447 200 447 200 447 200 447 200 447 225 503 225 503 225 503 225 503 225 503 225 503 25O 559 250 559 250 559 250 559 250 559 250 559 275 615 275 615 275 615 2 7 5 615

40 60 80 100 120 140 40 60 80 100 120 14~ 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 4O 60 80 100 120 140 40 60 80 100

43 34 28 24 21 19 36 29 24 21 18 17 32 26 21 19 17 15 .29 23 ,19 17 15 14 27 21 18 16 14 12 25 20 17 15 13 12 23 19 16 14 12 11 22 18 15 13 11 10 21 17 14 12 11 10 20 16 13 12 10 9 19 15 13 11

37 27 22 18 15 13 32 24 19 16 14 12 29 22 1? 14 12 11 26 20 16 13 11 10 24 18 15 12 10 9 22 17 14 11 10 8 21 16 13 10 9 8 19 15 12 10 8 7 18 14 11 9 8 7 18 13 11 9 7 6 17 13 10 8

Edition"

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

31 22 16 13 10 8 27 20 15 11 9 7 25 18 .13 10 8 7 22 16 12 9 7 6 20 15 11 9 7 5 19 14 10 8 6 5 18 13 9 7 6 4 17 t2 9 7 5 4 16 11 8 6 5 4 15 10 8 6 4 3 14 10 7 5

26 .17 12 8 6 4 23 15 10 7 5 3 21 14 9 6

21 12 7 4 1 0 19 11 6 3 1 0 17 10 6 3

, 4

1

3 19 12 8 6 4 2 17 11 8 5 3 2 16 10 7 5 3 2 15 9 6 4 3 2 14 9 6 4 2 1 13 8 5 3 2 1 12 7 5 3 2 1 11 7 4 3

0 15 9 5 2 1 0 14 8 4 2 1 0 13 7 4 2 0 0 12 6 3 1 0 0 tl 6 3 1 0 0 10 5 3 1 0 0 9 5 2 1 0 0 8 4 2 1

I

17 8 3 0 0 0 15 7 2 0 0 0 13 6 2 0 0 0 12 5 2 0 0 0 10 5 1 0 0 0 9 4 1 0 0 0 8 3 1 0 0 0 8 3 1 0 0 0 7 3 1 0 0 0 6 2 0 0 0 0 6 2 0 0

.12 4 O. 0 0 • 0 11 3 0 0 0 0 9 3, 0 O. 0 0 8 2 0 0 0 0 7 2 0 0 0 0 6 1 0 0 0 0 6 1 0 0 0 0 5 1 0 0 0 0 4 1 0 0 0 0 4 1 0 0 0 0 3 0 0 0

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX C

72E-59

Table C-3-2.1.2(k) Threshold Fire Size at Response: 750 B T U / S E C . Fire Growth Rate: 50 Seconds to 1000 B T U / S E C A l p h a : . 0.400 B T U / S E C s

Table C-3-2.1.2(j) Threshold Fire Size at Response: 500 B T U / S E C . Fire Growth Rate: 600 Seconds to 1000 B T U / S E C Alpha: "0.003 B T U / S E C '

CEILING HEIGHT IN FEET TAU RTI aT .

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

8.0 .

.

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

CEILING HEIGHT IN FEET

24.0 .

.

.

.

.

.

.

.

28.0

TAU RTI &T

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

INSTALLED SPACING OF DETECTORS 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 120 615 140 671 40 671 60 671 80 671 100 671 120 671 140 727 40 727. 60 727 80 727 100 727 120 727 140 783 40 783 60 783 80 783 100 783 120 783 140 839 40 839 60 839 80 839 100 839 120 839 140 894 40 894 60 894 80 894 100 894 120 894 140

NOTE:

10 9 18 15 12 11 9 8 18 14 12 10 9 8 17 13 11 10 9 8 17 13 11 9 8 7 16 13 11 9 8 7

7 6 16 12 10 8 7 6 15 11 9 7 6 5 15 11 9 7 6 5 14 11 8 7 6 5 14 10 8 6 5 5

4 3 13 9 7 5 4 3 13 9 6 5 4 3 12 8 6 4 3 2 12 8 6 4 3 2 11 7 5 4 3 2

2 1 11 6 4 2 1 1 10 6 4 2 1 1 9 6 3 2 1 1 9 5 3 2 1 0 9 5 3 2 1 0

0 0 8 4 2 1 0 0 7 4 2 1 0 0 7 3 1 0 0 0 6 3 1 0 0 0 6 3 1 0 0 0

1 ft = 0.305 m 1000 B T U / s e c = 1055 k W

.

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

28.0 .

.

.

.

.

.

INSTALLED SPACING OF DETECTORS 0 0 5 2 0 0 0 0 5 2 0 0 0 0 4 1 0 0 0 0 4 1 0 0 0 0 4 1 0 0 0 0

D e t e c t o r t i m e c o n s t a n t at a r e f e r e n c e velocity of 5 f t / s e c .

For SI Units:

4.0 .

0 0 3 0 0 0 0 0 3 0 0 0 0 0 2 0 0 0 0 0 2 0 0 0 0 0 2 0 0 0 0 0

25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

18 15 13 11 10 9 14 11 9 8 7 7 11 9 8 7 6 5 10 8 7 6 5 4 9 7 6 5 4 4 8 6 5 4 4 3 7 6 5 4 3 3 7 5 4 4 3 3 6 5 4 3 3 2 6 4 4 3 3 2 6 4 3 3

15 12 10 9 7 6 11 9 7 6 5 4 9 7 5 4 3 3 7 5 4 3 "3 2 6 5 3 3 2 2 6 4 3 2 2 1 5 3 2 2 1 t 4 3 2 1 1 0 4 3 2 1 1 0 4 2 2 1 0 0 3 2 1 1

13 9 7 6 4 4 9 6 4 3 2 2 6 4 3 2 1 1 5 3 2 1 1 0 4 2 1 1 0 0 3 2 1 0 0 0 3 1 0 0 0 0 2 1 0 0 0 0 2 1 0 0 0 0 2 0 0 0 0 0 1 0 0 0

10 6 4 3 2 1 6 3 2 1 0 0 4 2 1 0 0 0 3 1 0 0 0 0 2 1 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

7 4 2 1 0 0 3 1 0 0 0 0 2 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

4 1 0 0 0 0 2 0 0 0 0 0 0 O 0 ," Q 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

2 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-60

A U T O M A T I C FIRE DETECTORS

Table C-3.2.1.2(I) Threshold Fire Size at Response: 750 B T U / S E C . Fire Growth Rate: 150 Seconds to 1000 B T U / S E C Alpha: 0.044 B T U / S E C '

Table C-3-2.1.2(k) Threshold Fire Size at Response: 750 B T U / S E C . Fire Growth Rate: 50 Seconds to 1000 B T U / S E C Alpha: 0.400 B T U / S E C s

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI AT

4.0

8.0

12.0

16.0

20.0

24.0

28.0

TAU RTI AT

4.0

8.0

12.0

16.0

20.0

24.0

28.0

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INSTALLED SPACING OF DETECTORS

INSTALLED SPACING OF DETECTORS 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671' 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

2 2 5 4 3 3 2 2 5 4 3 2 2 2 5 4 3 2 2 2 5 3 3 2 2 1 4 3 2 2 2 1

0 0 3 2 1 0 0 0 3 2 1 0 0 0 3 1 1 0 0 0 2 1 0 ' 0 0 0 2 1 0 0 0 0

0 0 1 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 .0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 " 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

N O T E : Detector time constant at a reference velocity of 5 ft/sec. For S1 Units:

I ft = 0.305 m 1000 B T U / s e c = 1055 k W

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

25 56 40 . 32 25 56 60 26 25 56 80 23 25 56 100 20 25 56 120 18 25 56 140 16 50 112 40 25 50 112 60 21 50 112 80 18 50 112 100 16 50 112 120 14 50'112 140 13 75 168 40 22 75 168 60 18 75 168 80 15 75 168 100 13 75 168 120 12 75 168 140 11 100 224 40 19 100 224 60 16 100 224 80 13 100 224 100 12 100 224 120 10 100 224 140 9 125 280 40 17 125 280 60 14 125 280 80 12 125 280 100 10 125 280 120 9 125 280 140 8 150 335 40 16 150 335 60 13 150 335 80 11 150 335 100 9 150 335 120 8 150 335 140 8 175 391 40 15 175 391 60 12 175 391 80 10 175 391 100 9 175 391 120 8 175 391 140 7 200 447 40 14 200 447 60 11 200 447 80 9 200 447 100 8 200 447 120 7 200 447 140 6 225 503 40 13 225 503 60 10 225 503 80 9 225 503 100 8 225 503 120 7 225 503 140 6 250 559 40 12 250 559 60 10 250 559 80 8 250 559 100 7 250 559 120 6 250 559 140 6 275 615 40 12 275 615 60 9 275 615 80 8 275 615 100 7

29 23 19 16 14 12 23 18 15 13 11 10 19 15 12 10 9 8 17 13 11 9 8 7 15 12 9 8 7 6 14 10 8 ? 6 5 13 9 8 6 5 4 12 9 7 6 5 4 11 8 6 5 -4 4 10 7 6 5 4 3 10 7 5 4

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

26 19 15 12 10 8 20" 15 12 9 8 6 17 12 9 7 6 5 14 10 8 6 5 4 13 9 7 5 4 3 11 8 6 4 3 3 10 7 5 4 3 2 9 6 4 3 2 2 8 6 4 3 2 1 8 5 4 2 2 1 7 5 3 2

22 15 11 8 6 5 17 12 8 6 4 3 "14 9 6 5 3 2 12 8 5 3 2 1 10 6 4 3 2 1 9 5 3 2 1 1 8 5 3 2 1 0 7 4 2 1 1 0 6 3 2 1 0 0 5 3 2 1 0 0 5 3 1 1

18 12 8 5 3 1 14 8 5 3 2 1 11 6 4 2 1 0 9 5 3 1 1 0 7 4 2 1 0 0 6 3 1 1 0 0 5 2 1 0 0 0 4 2 1 0 0 0 4 2 0 0 0 0 3 1 0 0 0 0 3 1 0 0

15 8 4 1 0 0 11 5 2 1 0 0 8 4 1 0 0 0 6 3 1 0 0 0 5 2 0 0 0 0 4 1 0 0 0 0 3 1 0 0 0 0 3 1 0 0 0 0 2 0 0 0 0 0 2 0 0 0 0 0 1 0 0 0

11 4 1 0 0 0 8 3 0 0 0 0 5 1 0 0 0 0 4 1 0 0 0 0 3 1 0 0 0 0 2 0 0 0 0 0 2 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX C

72E-61

T a b l e C-3.2.1.2(1) T h r e s h o l d Fire Size at Response: 750 B T U / S E C . Fire G r o w t h Rate: 150 Seconds to 1000 B T U / S E C Alpha: 0.044 B T U / $ E C '

T a b l e C-3-2,1.2(m) T h r e s h o l d Fire Size at Response: 750 B T U / S E C . Fire Growth Rate: 300 Seconds to 1000 B T U / S E C Alpha: 0.011 B T U / S E C s

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

CEILING HEIGHT IN FEET

24.0 .

.

.

.

.

.

.

28.0 .

.

.

.

.

.

TAU RTI aT .

.

.

.

.

.

.

.

.

.

.

.

INSTALLED SPACING OF DETECTORS 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

6 5 11 9 7 6 6 5 11 9 7 6 5 5 10 8 7 6 5 5 10 8 6 6 5 4 10 8 6 5 5 4

4 3 9 7 5 4 3 3 9 6 5 4 3 2 8 6 4 3 3 2 8 6 4 3 3 2 7 5 4 3 2 2

2 1 7 4 3 2 '- 1 1 6 4 3 2 1 1 6 4 2 2 1 0 5 3 2 1 1 0 5 3 2 1 1 0

0 0 4 2 1 0 .0 0 4 2 1 0 0 0 4 2 1 0 0 0 3 2 0 0 0 0 3 1 0 0 0 0

0 0 3 1 0 0 0 0 2 1 0 0 0 0 2 0 0 0 0 0 2 0 0 0 0 0 2 0 0 0 0 0

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

.

28.0 .

.

.

.

.

INSTALLE0 SPACING OF DETECTORS 0 0 1 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 0 0 " 0 0 0 0 0 0 0 0 0 0

N O T E : D e t e c t o r t i m e c o n s t a n t at a r e f e r e n c e velocity of 5 ft/sec. For$1 Units: 1 ft = 0.305 m 1000 B T U / s e c = 1055 k W

0 0 0 0 0 0 0 0 0 0 0 . 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100. 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

43 35 30 26 23 21 36 29 24 21 19 17 31 25 21 19 17 15 28 22 19 17 15 14 25 20 17 15 14 12 23 19 16 14 13 11 22 18 15 13 12 11 21 17 14 12 11 10 20 16 13 12 10 9 19 15 13 11 10 9 18 14 12 10

39 30 24 21 18 15 32 25 21 17 15 13 28 22 18 15 13 12 25' 19 16 14 12 10 23 18 14 12 11 9 21 16 13 11 10 8 20 15 12 10 9 8 18 14 11 10 8 7 17 13 11 9 8 7 16 12 10 8 7 6 16 12 9 8

34 25 20 16 13 11 29 21 17 13 11 9 25 18 14 12 10 8 22 16 13 10 8 7 20 15 11 9 7 6 18 13 10 8 7 5 17 12 9 7 6 5 16 11 9 7 5 4 15 11 8 6 5 4 14 10 7 6 4 4 13 9 7 5

30 21 15 11 9 6 25 17 13 10 7 5 22 15 11 8 6 4 19 13 10 7 5 4 17 12 8 6 4 3 15 10 7 5 4 3 14 9 7 5 3 2 13 9 6 4 3 2 12 8 5 4 2 2 11 7 5 3 2 1 10 7 4 3

25 16 11 7 4 2 21 14 9 6 3 2 18 12 7 5 3 1 16 10 6 4 2 1 14 9 5 3 2 1 13 8 5 3 1 0 11 7 4 2 1 0 10 6 3 2 1 0 9 5 3 2 1 0 9 5 3 1 1 0 8 4 2 1

21 12 6 3 1 0 17 10 5 2 0 0 15 8 4 2 0 0 13 7 3 1 0 0 11 6 3 1 0 0 10 5 2 1 0 0 9 4 2 0 0 0 8 4 1 0 0 0 7 3 1 0 0 0 6 3 1 0 0 0 6 2 1 0

17 8 3 0 0 0 14 6 2 0 0 0 11 5 1 0 0 0 10 4 1 0 0 0 8 3 1 0 0 0 7 2 0 0 0 0 6 2 0 0 0 0 5 2 0 0 0 0 5 1 0 0 0 0 4 1 0 0 0 0 3 1 0 0

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-62

A U T O M N I ' I C FIRE I)ETECTORS

Table C-3.2.1.2(n) T h r e s h o l d Fire Size at Response: 750 B T U / S E C . Fire Growth Rate: 500 Seconds to I000 B T U / S E C Alpha: 0.004 B T U / S E C ~

Table C-3-2.1.2(m) T h r e s h o l d Fire Size at Response: 750 B T U / S E C . Fire Growth Rate: 300 Seconds to I000 B T U / S E C Alpha: 0.011 B T U / S E C j

CEILING HEIGHT IN FEET

TAU RTI AT .

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

8.0 .

.

.

.

.

CEILING HEIGHT IN FEET

12.0 16.0 20.0 24.0 28.0 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

TAU .

.

.

.

.

.. .

..

.

.

.

RTI AT .. .

..

.

.

.

.

.

.

.

.

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783. 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 : 140

9 8 17 14 11 10 9 8 16 13 11 10 8 8 16 13 11 9 8 7 15 t2 10 9 8 7 15 12 10 8 7 7

7 6 15 11 9 7 6 5 t4 11 9 7 6 5 14 10 8 7 6 5 13 10 8 6 5 5 13 9 7 6 5 4

4 3 12 9 6 5 4 3 12 8 6 5 3 3 11 8 6 4 3 2 11 7 5 4 3 2 10 7 5 4 3 2

2 1 10 6 4 3 2 1 9 6 4 2 1 1 9 5 3 2 1 1 8 5 3 2 1 1 8 5 3 2 1 0

0 0 7 4 2 1 0 0 7 3 2 1 0 0 6 3 1 1 0 0 6 3 1 0 0 0 5 3 1 0 0 0

0 0 5 2 1 0 0 0 5 2 0 0 0 0 4 1 0 0 0 0 4 1 0 0 0 0 3 1 0 0 0 0

0 0 3 1 0 0 0 0 3 0 0 "0 0 0 2 0 0 0 0 0 2 0 0 0 0 0 2 0 0 0 0 0

N O T E : Detector t i m e constant at a reference velocity of 5 ft/sec. F o r S I Units:

] ft = 0.305 m

1000 B T U / s e c = 1055 k W

.

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

24.0

28.0

.

'INSTALLED SPACING OF DETECTORS

INSTALLED SPACJ.NG OF DETECTORS 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

4.0 .

25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

52 41 34 29 26 23 44 35 30 26 23 21 39 31 26 23 20 18 35 28 24 21 19 17 32 26 22 19 17 16 30 24 21 18 16 15 28 23 19 17 15 14 27 22 18 16 14 13 26 20 17 15 13 12 24 19 16 14 13 12 23 19 16 14

45 34 28 23 20 17 40 30 25 21 18 16 35 27 .22 19 16 14 32 25 20 17 15 13 30 23 19 16 14 12 28 21 17 15 13 11 26 20 16 14 12 10 24 19 15 13 11 10 23 18 14 12 11 9 22 17 14 12 10 9 21 16 13 11

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

39 28 22 18 14 12 35 26 20 16 13 11 31 23 18 15 12 10 29 21 16 13 11 9 26 19 15 12 10 8 25 18 14 11 9 8 23 17 13 11 9 7 22 16 12 10 8 7 20 15 11 9 7 6 19 14 11 9 7 6 18 13 10 8

34 23 17 13 10 7 30 21 15 12 9 . 7 27 19 14 10 8 6 25 17 13 10 7 5 23 16 12 9 7 5 21 15 11 8 6 4 20 14 10 7 5 4 18 13 9 7 5 4 17 12 8 6 4 3 16 11 8 6 4 3 16 10 7 5

29 18 12 8 5 3 26 17 11 7 5 3 24 15 10 7 4 2 21 14 9 6 4 2 20 12 8 5 3 2 18 11 7 5 3 1 17 10 7 4 2 1 16 10 6 4 2 1 14 9 6 3 2 1 14 8 5 3 2 1 13 8 S 3

24 14 8 4 1 0 22 12 7 3 1 0 20 11 6 3 1 0 18 10 5 2 0 0 16 9 5 2 0 0 15 8 4 2 0 0 1'4 7 4 1 0 0 12 7 3 1 0 0 12 6 3 1 0 0 11 5 3 1 0 0 10 5 2 1

20 9 4 0 0 0 18 8 3 0 0 0 16 7 3 0 0 0 14 6 2 0 0 0 13 6 2 0 0 0 12 S 1 0 0 0 10 4 1 0 0 0 10 4 1 0 0 0 9 3 1 0 0 0 8 3 1 0 0 0 7 3 1 0

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX C

72E-63

T a b l e C-3-2.1.2(o) T h r e s h o l d Fire Size at Response: 750 B T U / S E C . Fire Growth Rate: 600 Seconds to 1000 B T U / S E C Alpha: 0.003 B T U / S E C ~

T a b l e C-3.2.1.2(n) T h r e s h o l d Fire Size at Response: 750 B T U / S E C . Fire Growth Rate: 500 Seconds to 1000 B T U / S E C Alpha: 0.004 B T U / S E C s

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU "RTI AT .

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

TAU RTI aT

24.0 "28.0 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

NOTE:

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

12 11 22 18 15 13 12 11 22 17 15 13 11 10 21 17 14 12 11 10 20 16 14 12 11 10 20 16 13 11 10 9

9 8 20 15 13 11 9 8 19 15 12 10 9 7 19 14 12 10 8 7 18 14 11 9 8 7 17 13 11 9 8 7

7 5 18 13 10 8 6 5 17 12 9 7 6 5 16 12 9 7 5 4 16 11 8 7 5 4 15 11 8 6 5 4

4 3 15 10 7 5 3 2 14 9 6 5 3 2 13 9 6 4 3 2 13 8 6 4 3 2 12 8 5 4 3 2

1 1 12 7 4 2 1 0 11 7 4 2 1 0 11 6 4 2 1 0 10 6 3 2 1 0 10 5 3 2 1 0

0 0 9 5 2 1 0 0 9 4 2 1 0 0 8 4 2 0 0 0 8 3 1 0 0 0 7 3 1 0 0 0

D e t e c t o r t i m e c o n s t a n t at a r e f e r e n c e velocity of 5 f t / s e c .

F o r S l Units:

1 ft = 0.305 m 1000 B T U / s e c = 1055 k W

.

.

.

8.0 .

.

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20,0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

28.0 .

.

.

.

.

.

.

INSTALLED SPACI NG OF DETECTORS

INSTALLED SPACING OF DETECTORS 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

.

0 0 7 2 0 0 0 0 6 2 0 0 0 0 6 2 0 0 0 0 5 2 0 0 0 0 5 1 0 0 0 0

25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 ' 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

55 43 36 31 27 24 47 37 31 27 24 22 42 33 28 24 22 20 38 30 26 22 20 18 35 28 24 21 19 17 33 26 22 19 17 16 31 25 21 18 16 15 29 23 20 17 15 14 28 22 19 16 15 13 27 21 18 16 14 13 26 21 17 15

47 36 28 24 20 18 42 32 26 22 19 16 38 29 24 20 17 15 35 27 22 18 16 14 32 25 20 17 15 13 30 23 19 16 14 12 28 22 18 15 13 11 27 21 17 14 12 11 26 20 16 13 12 10 24 19 15 13 11 10 23 18 15 12

41 29 23 18 15 12 37 27 21 17 14 11 34 25 19 15 13 11 31 23 18 14 12 10 29 21 16 13 11 9 27 20 15 12 10 8 25 18 14 12 10 8 24 17 14 11 9 7 23 17 13 10 8 7 21 16 12 10 8 7 20 15 12 9

35 24 18 13 10 8 32 22 16 12 9 7 29 20 15 11 9 6 27 19 14 10 8 6 25 17 13 10 7 5 23 16 12 9 7 5 22 15 11 8 6 5 21 14 10 8 6 4 19 13 10 7 5 4 18 13 9 7 5 4 18 12 9 6

30 19 13 9 6 3 28 18 12 8 5 3 25 16 11 7 5 3 23 15 10 7 4 2 22 14 9 6 4 2 20 13 8 5 3 2 19 12 8 5 3 1 17 11 7 4 3 1 16 10 7 4 2 1 15 10 6 4 2 1 15 9 6 3

25 14 8 4 1 0 23 13 8 4 1 0 21 12 7 3 1 0 19 11 6 3 1 0 18 10 6 3 1 0 17 9 5 2 0 0 15 9 4 2 0 0 14 8 4 2 0 0 13 7 4 1 0 0 12 7 3 1 0 0 12 6 3 1

21 10 4 0 0 0 19 9 4 0 0 0 17 8 3 0 0 0 16 7 3 0 0 0 14 7 2 0 0 0 13 6 2 0 0 0 12 5 2 0 0 0 11 5 1 0 0 0 10 4 1 0 0 0 10 4 1 0 0 0 9 4 1 0

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-64

AUTOMATIC FIRE DETECTORS

Table C-3-2.1.2(p) Threshold Fire Size at Response: 1000 B T U / S E C . Fire Growth Rate: 50 Seconds to 1000 B T U / S E C Alpha: 0.400 B T U / S E C '

Table C-3-2.1.2(0) Threshold Fire Size at Response: 750 B T U / S E C . Fire Growth Rate: 600 Seconds to 1000 B T U / S E C Alpha: 0.003 B T U / S E C '

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

.

28.0 .

.

.

.

.

.

TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 t00 120 140 40 60 80 100 120 140

13 12 25 20 17 15 13 12 24 19 16 14 12 11 23 18 15 13 12 11 22 18 15 13 12 11 22 17 15 13 11 10

11 9 22 17 14 12 10 9 22 16 13 11 10 8 21 16 13 11 9 8 20 15 12 10 9 8 19 15 12 10 9 7

7 6 20 14 11 9 7 6 19 14 10 8 7 5 18 13 10 8 6 5 17 13 10 8 6 5 17 12 9 7 6 5

5 3 17 11 8 6 4 3 16 11 8 5 4 3 15 10 7 5 4 3 15 10 7 5 3 2 14 9 6 5 3 2

2 1 14 8 5 3 2 1 13 8 5 3 2 1 13 7 5 3 1 1 12 7 4 2 1 0 11 7 4 2 1 0

0 0 11 6 3 1 0 0 10 5 2 1 0 0 10 5 2 1 0 0 9 5 2 1 0 0 9 4 2 1 0 0

N O T E : Detector t i m e constant at a reference velocity of 5 ft/sec. F o r S I Units:

I ft = 0 . 3 0 5 m 1000 B T U / s e c -- 1055 k W

.

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

.

28.0 .

.

.

.

INSTALLED SPACING OF DETECTORS

INSTALLED SPACING OF DETECTORS 275 615 275 615 300 671 300 671 300 671 300 671 300 671 300 671 325 727 325 727 325 727 325 727 325 727 325 727 350 783 350 783 350 783 350 783 350 783 350.783 375 839 375 839 375 839 375 839 375 839 375 839 400 894 400 894 400 894 400 894 400 894 400 894

4.0 .

0 0 8 3 1 0 0 0 8 3 1 0 0 0 7 3 1 0 0 0 7 2 0 0 0 0 6 2 0 0 0 0

25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 I00 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

22 18 16 14 13 12 17 14 12 11 10 9 14 12 10 9 8 7 12 10 8 7 7 6 11 9 8 7 6 5 0 8 7 6 5 5 9 7 6 5 5 4 9 7 6 5 4 4 8 6 5 5 4 3 8 6 5 4 4 3 7 6 5 4

20 16 13 11 10 9 15 11 9 8 7 6 12 9 7 "6 5 4 10 8 6 5 4 4 9 7 5 4 3 3 8 6 4 3 3 2 7 5 4 3 2 2 6 5 3 3 2 2 6 4 3 2 2 1 5 4 3 2 2 1 5 3 2 2

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

17 13 10 8 7 6 12 9 7 5 4 3 9 7 5 4 3 2 8 5 4 3 2 1 6 4 3 2 1 1 5 3 2 2 1 0 5 3 2 1 0 0 4 2 1 1 0 0 4 2 1 0 0 0 3 2 1 0 0 0 3 1 0 0

14 10 7 5 4 3 9 6 4 3 2 1 7 4 3 2 1 0 5 3 2 1 0 0 4 2 1 0 0 0 3 2 0 0 0 0 3 1 0 0 0 0 2 1 0 0 0 0 2 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0

11 7 4 3 1 1 7 4 2 1 0 0 4 2 1 0 0 0 3 1 0 0 0 0 2 1 0 0 0 0 2 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

8 4 2 0 0 0 4 2 0 0 0 0 2 1 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 O"

5 2 0 0 0 0 2 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

.

.

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX C

72E-65

T a b l e C-3-2.1.2(q) T h r e s h o l d Fire Size at Response: 1000 B T U / S E C . Fire Growth Rate: 150 Seconds to 1000 B T U / S E C Alpha: 0.044 B T U / S E C s

T a b l e C-3-2.1.2(p) T h r e s h o l d F i r e Size at Response: 1000 B T U / S E C . Fire G r o w t h Rate: 50 Seconds to 1000 B T U / S E C Alpha: 0.400 B T U / S E C s

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

4,0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

CEILING HEIGHT IN FEET

24.0 .

.

.

.

.

.

.

28.0 .

.

.

.

.

.

TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

INSTALLED SPACING OF DETECTORS 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727

783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

3 3 7 S 4 4 3 3 7 5 4 3 3 3 6 5 4 3 3 2 6 5 4 3 3 2 6 4 3 3 2 2

1 1 5 3 2 2 1 I 4 3 2 1 1 0 4 3 2 1 1 0 4 2 2 1 0 0 4 2 1 1 0 0

0 0 3 1 0 0

0 0 1 0 0 0

0 0 0 0 0 0

0 0 0 0 0 0

0 0 0 0 0 0

0

0

0

0

0

0 2 1 0 0 0 0 2 1 0 0 0 0 2 0 0 0 0 0 2 0 0 0 0 0

0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 .0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

I ft --- 0.305 m 1000 B T U / s e c = 1055 k W

.

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20,0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

.

28.0 .

.

.

.

.

INSTALLED SPACING OF DETECTORS

N O T E : Detector time constant at a reference velocity of 5 ft/sec. For ST Units:

4.0 .

25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280

335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

39 32 27 24 22 20 31 25 22 19 17 16 27 22 19 16 15 13 24 19 16 14 13 12 21 17 15 13 12 11 20 16 14 12 11 10 18 15 13 11 10 9 17 14 12 10 9 8 16 13 11 10 9 8 16 12 11 9 8 7 15 12 10 9

36 28 24 20 18 16 29 23 19 16 14 13 24 19 16 14 12 10 22 17 14 12 10 9 19 15 12 10 9 8 18 14 11 9 8 7 16 13 10 9 7 6 15 12 9 8 7 6 14 11 9 7 6 5 13 10 8 7 6 5 13 10 8 6

32 24 20 16 14 12 26 19 15 13 11 9 22 16 13 tl 9 7 19 14 11 9 7 6 17 12 10 8 6 5 15 11 9 7 5 4 14 10 8 6 5 4 13 9 7 5 4 3 12 8 6 5 4 3 11 8 6 4 3 3 10 7 5 4

28 21 16 12 10 8 22 16 12 9 7 6 19 13 10 7 6 4 16 11 8 6 5 3 14 10 7 5 4 3 13 8 6 4 3 2 11 7 5 4 2 2 10 7 4 3 2 1 9 6 4 3 2 1 9 5 3 2 1 1 8 5 3 2

25 17 12 8 6 4 19 13 9 6 4 2 16 10 ? 4 3 2 13 8 5 3 2 1 11 7 4 3 1 1 10 6 3 2 1 1 9 5 3 2 1 0 8 4 2 1 1 0 7 4 2 1 0 0 6 3 2 1 0 0 6 3 1 0

21 13 8 4 2 0 16 9 6 3 1 0 13 7 4 2 1 0 10 6 3 1 0 0 9 4 2 1 0 0 7 4 2 1 0 0 6 3 1 0 0 0 S 2 1 0 0 0 5 2 1 0 0 0 4 2 0 0 0 0 4 1 0 0

17 9 4 1 0 0 13 6 3 0 0 0 10 4 2 0 0 0 8 3 1 0 0 0 6 2 1 0 0 0 5 2 0 0 0 0 4 1 0 0 0 0 3 1 0 0 0 0 3 1 0 0 0 0 2 0 0 0 0 0 2 0 0 0

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

AUTOMATIC FIRE DETECTORS

72E-66

T a b l e C-3.2.1.2(r) T h r e s h o l d Fire Size at Response: 1000 B T U / S E C . Fire G r o w t h Rate: 300 Seconds to 1000 B T U / S E C Alpha: 0.011 B T U / S E C s

T a b l e C-3-2.1.2(q) T h r e s h o l d Fire Size at Response: 1000 B T U / S E C . Fire Growth Rate: 150 Seconds to 1000 B T U / S E C Alpha: 0.044 B T U / S E C s

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

.

8.0 .

.

.

.

12.0 --. .

.

.

.

16.0 .

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

24.0 .

.

.

.

.

.

.

.

28.0 .

TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 " 60 80 100 120 140

8 7 14 11 10 8 7 7 14 11 9 8 7 6 13 10 9 8 7 6 13 10 8 7 6 6 12 10 8 7 6 6

5 5 12 9 7 6 5 4 12 9 7 6 5 4 11 8 6 5 4 4 11 8 6 5 4 3 10 7 6 5 4 3

3 2 10 7 5 4 3 2 9 6 4 3 2 2 9 6 4 3 2 2 8 5 4 3 2 1 8 5 4 3 2 1

1 1 7 4 3 2 1 0 7 4 2 1 1 0 6 4 2 1 1 0 6 3 2 1 0 0 5 3 2 1 0 0

0 0 5 2 1 0 0 0 5 2 1 0 0 0 4 2 1 0 0 0 4 2 0 0 0 0 3 1 0 0 0 0

0 0 3 1 0 0 0 0 3 1 0 0 0 0 2 1 0 0 0 "0 2 0 0 0 0 0 2 0 0 0 0 0

N O T E : Detector t i m e constant at a reference velocity of 5 ft/sec. F o r S I Units:

1 ft = 0.305 m 1000 B T U / s e c = 1055 k W

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

24.0 .

.

.

.

28.0

.

INSTALLED SPACING OF DETECTORS

INSTALLED SPACING OF DETECTORS 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

4.0 .

0 0 2 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0

25 56 25 56 25 56 25 56 25 56 25 56 50 112 50 112 50 112 50 112 50 112 50 112 75 168 75 168 75 168 75 168 75 168 75 168 100 224 100 224 100 224 100.224 100 224 100 224 125 280 125,280 125 280 125 280 125 280 125 280 150 335 150 335 150 335 150 335 150 335 150 335 175 391 175 391 175 391 175 391 175 391 175 391 200 447 200 447 200 447 200 447 200 447 200 447 225 503 225 503 225 503 225 503 225 503 225 503 250 559 250 559 250 559 250 559 250 559 250 559 275 615 275 615 275 615 275 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

52 42 35 31 28 25 43 35 30 26 23 21 37 30 26 23 20 19 34 27 23 20 18 17 31 25 21 1'9 17 15 29 23 20 17 16 14 27 22 18 16 15 13 25 20 17 15 14 12 24 19 16 14 13 12 23 18 16 14 12 11 22 18 15 13

47 36 30 25 22 19 40 31 25 22 19 17 35 27 22 19 17 15 31 24 20 17 15 13 29 22 18 16 14 12 27 21 17 14 13 11 25 19 16 13 12 10 23 18 15 13 11 10 22 17 14 12 10 9 21 16 13 11 10 8 20 15 12 11

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

42 31 25 20 17 14 36 27 21 18 15 12 31 24 19 15 13 11 28 21 17 14 12 10 26 19 15 13 10 9 24 18 14 11 10 8 22 16 13 10 9 7 21 15 12 10 8 7 19 14 11 9 7 6 18 13 10 8 7 6 17 13 10 8

37 26 20 15 12 10 32 23 17 13 11 8 28 20 15 12 9 7 25 18 13 10 8 6 23 16 12 9 7 6 21 15 11 8 6 5 19 13 10 8 6 4 18 12 9 7 5 4 17 11 8 6 5 3 16 11 8 6 4 3 15 10 7 5

32 22 15 11 8 5 28 19 13 9 7 4 24 16 11 8 6 4 22 14 10 7 5 3 19 13 9 6 4 3 18 12 8 5 4 2 16 10 7 5 3 2 15 10 6 4 3 2 14 9 6 4 2 1 13 8 5 3 2 1 12 7 5 3

28 17 ,11 7 4 1 24 15 9 6 3 1 21 13 8 5 2 1 18 11 7 4 ' 2 0 .16 10 6 3 1 0 15 9 5 3 1 0 13 8 4 2 1 0 12 7 4 2 1 0 11 6 3 2 1 0 10 5 3 1 0 0 9 5 2 1

23 13 7 3 0 0 20 11 5 2 0 0 17 9 4 1 0 0 15 8 4 1 0 0 13 7 3 1 0 0 12 6 2 1 0 0 11 5 2 0 0 0 9 4 2 0 0 0 9 4 1 0 0 0 8 3 1 0 0 0 7 3 1 0

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX C

72E-67

T a b l e C-3,2.1.2(r) T h r e s h o l d Fire Size at Response: 1000 B T U / S E C . Fire G r o w t h Rate: 300 Seconds to 1000 B T U / S E C Alpha: 0.011 B T U / S E C s

T a b l e C-3-2.1.2(s) T h r e s h o l d Fire Size at Response: 1000 B T U / S E C . Fire G r o w t h Rate: 500 Seconds to 1000 B T U / S E C Alpha: 0.004 B T U / S E C '

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0

28.0

.

TAU RTI &f .

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

INSTALLED SPACING OF DETECTORS 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 ?27 727 727 727 783 783 ?83 783 783 ?83 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

12 11 21 17 14 13 '11 10 20 16 14 12 11 10 20 16 13 12 10 9 19 15 13 11 10 9 18 15 12 11 10 9

9 8 19 15 12 10 9 8 18 14 11 10 8 7 18 13 11 9 8 7 17 13 10 9 7 6 16 12 10 8 7 6

6 5 16 12 9 7 6 5 16 11 9 7 6 5 15 11 8 7 5 4 14 10 8 6 5 4 14 10 7 6 5 4

4 3 14 9 7 5 3 3 13 9 6 4 3 2 13 8 6 4 3 2 12 8 5 4 3 2 11 7 5 3 2 2

2 1 11 7 4 3 1 1 11 6 4 2 1 1 10 ' 6 3 2 1 '1 9 5 3 2 1 "0 9 5 3 2 1 0

.

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

24.0

28.0

31 19 12 8 4 2 29 18 11 7 4 2 26 16 10 6 3 1 24 15 9 6 3 1 22 14 ' 9 5 3 1 21 13 8 5 2 1 19 12 7 4 2 1 18 11 7 4 2 1 17 10 6 3 2 0 16 9 6 3 1 0 15 9 5 3

27 15 8 4 O" 0 24 14 7 3 0 0 22 12 6 3 0 0 20 11 6 2 0 0 19 10 5 2 0 0 17 9 5 2 0 O 16 8 4 1 0 0 15 8 4 1 0 0 14 7 3 1 0 0 13 7 3 1 0 0 12 6 3 1

.

INSTALLED SPACING OF DETECTORS 0 0 9 4 2 1 0 0 8 4 2 1 0 0 8 4 2 1 0 0 7 3 1 0 0 0 7 3 1 0 0 0

NOTE: Detector time constant at a reference velocity of 5 ft/sec. F o r S l Units: 1 ft = 0 . 3 0 5 m 1000 BTU/sec = 1055 k W

0 0 6 2 1 0 0 0 6 2 1 0 0 0 5 2 0 0 0 0 5 2 0 0 0 0 4 1 0 0 0 0

25 56 25 56 25 56 25 56 25 56 25 56 50 112 50 112 50 112 50 112 50 112 50 112 75 168 75 168 75 168 75 168 75 168 75 168 100 224 100 224 100 224 100 224 100 224 100 224 125 280 125 280 125 280 125 280 125 280 125 280 150 335 150 335 150 335 150 335 150335 150 335 175 391 175 391 175 391 175 391 175 391 175 391 200 447 200 447 200 447 200 447 200 447 200 447 225 503 225 503 225 503 225 503 225 503 225 503 250 559 250 559 250 559 250 559 250 559

250 559 275 275 275 275

615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

62 49 41 35 31 28 53 42 35 31 27 25 47 38 32 28 25 22 43 34 29 25 23 21 39 32 27 24 21 19 37 30 25 22 20 18 35 28 24 21 19 17 33 26 22 20 18 16 31 25 21 19 17 15 30 24 20 18 16 14 29 23 20 17

54 41 33 28 24 21 48 37 30 25 22 19 43 33 27 23 20 18 40 31 25 21 19 16 37 28 23 20 17 15 34 27 22 19 16 14 32 25 20 18 15 13 30 24 19 17 14 13 29 22 18 16 14 12 28 21 18 15 13 11 27 20 17 14

48 35 27 22 18 16 43 32 25 20 17 14 • 39 29 23 19 16 13 36 27 21 17 15 12 33 25 20 16 14 11 31 23 18 15 13 11 29 22 17 14 12 10 28 20 16 13 11 9 26 19 15 13 10 9 25 18 15 12 10 8 24 18 14 11

42 29 22 17 13 11 38 27 20 16 12 10 35 25 19 14 11 9 32 23 17 13 11 8 30 21 16 12 10 8 28 20 15 12 9 7 26 18 14 11 8 7 24 17 13 10 8 6 23 16 12 9 7 6 22 15 11 9 7 5 21 15 11 8

37 24 17 12 9 6 33 22 16 11 8 6 31 20 14 10 7 5 28 19 13 9 7 5 26 17 12 9 6 4 24 16 11 8 6 4 23" 15 10 7 5 3 21 14 10 7 5 3 20 13 9 6 4 3 19 12 8 6 4 2 18 12 8 5

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-68

A U T O M A T I C FIRE I)ETECTORS

T a b l e C-3.2.1.2(t) T h r e s h o l d Fire Size at Response: 1000 B T U / S E C . Fire Growth Rate: 600 Seconds to 1000 B T U / S E C Alpha: 0.003 B T U / S E C '

T a b l e C-3-2.1.2(s) T h r e s h o l d Fire Size at Response: 1000 B T U / S E C . Fire Growth Rate: 500 Seconds to 1000 B T U / S E C Alpha: 0.004 B T U / S E C '

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

24.0

28.0

TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

15 14 28 22 19 16 15 13 27 21 18 16 14 13 26 21 18 15 14 12 25 20 17 15 13 12 24 19 16 14 13 12

12 11 25 20 16 14 12 10 25 19 16 13 11 10 24 18 15 13 11 10 23 18 14 12 11 9 22 17 14 12 10 9

9 8 23 17 13 11 9 7 22 16 13 10 8 7 21 15 12 10 8 7 20 15 12 9 8 6 '20 14 11 9 7 6

6 5 20 14 10 8 6 5 19 13 10 7 6 4 18 13 9 7 5 4 18 12 9 7 5 4 17 12 8 6 5 4

4 2 17 11 7 5 3 2 16 10 7 5 3 2 15 10 7 4 3 2 15 9 6 4 3 1 14 9 6 4 2 1

1 0 14 8 5 2 1 0 13 8 4 2 1 0 13 7 4 2 1 0 12 7 4 2 1 O 11 6 3 2 1 O

N O T E : Detector t i m e constant at a reference velocity of 5 ft/sec. F o r S I Units:

1 ft = 0.305 m 1000 B T U / s e c = 1055 k W

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0

28.0

33 20 13 8 5 2 30 19 12 7 4 2 "28 17 11 7 4 2 26 16 10 6 3 1 24 15 10 6 3 1 23 14 9 5 3 1 21 13 8 5 3 1 20 12 8 4 2 1 19 12 7 4 2 1 18 11 7 4 2 1 17 10 6 3

28 15 8 4 1 0 26 14 8 3 0 0 24 13 7 3 0 0 22 12 6 3 0 0 21 11 6 2 0 0 19 11 5 2 0 0 18 10 5 2 0 0 17 9 4 2 0 0 -16 8 4 1 0 0 15 8 4 1 0 0 14 7 3 1

.

INSTALLED SPACING OF DETECTORS

INSTALLED SPACING OF DETECTORS 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

4.0 .

0 0 11 5 2 1 0 0 11 5 2 0 0 0 10 5 2 0 0 0 9 4 2 0 0 0 9 4 1 0 0 0

25 25 25 25 25 25 50 50 50 50 50 50 75 75 76 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 160 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

65 51 42 36 32 29 56 45 37 33 29 26 50 40 34 30 26 24 46 37 31 27 24 22 43 34 29 25 23 21 40 32 27 24 21 19 38 30 26 22 20 18 36 29 24 21 19 17 34 27 23 20 18 17 33 26 22 19 17 16 31 25 21 19

56 43 34 29 25 21 51 39 31 26 23 20 46 35 29 25 21 19 43 33 27 23 20 17 40 31 25 21 19 16 37 29 24 20 17 15 35 27 22 19 17 15 33 26 21 18 16 14 32 25 20 17 15 13 30 23 19 16 14 13 29 23 18 16

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

50 36 28 23 19 16 45 33 26 21 18 15 42 31 24 20 17 14 38 28 23 18 15 13 36 27 21 17 15 12 34 25 20 16 14 12 32 24 19 15 13 11 30 22 18 15 12 10 29 21 17 14 12 10 27 20 16 13 11 9 26 19 15 13

43 30 23 17 14 11 40 28 21 16 13 10 37 26 20 15 12 10 34 24 18 14 11 9 32 23 17 13 11 8 30 21 16 13 10 8 28 20 15 12 9 7 27 19 14 11 9 7 26 18 14 11 8 6 24 17 13 10 8 6 23 16 12 9

38 25 18 13 9 6 35 23 16 12 8 6 32 22 15 11 8 6 30 20 14 10 7 5 28 19 13 10 7 5 26 18 12 9 6 4 25 17 12 8 6 4 24 16 11 8 5 4 22 15 10 7 5 3 21 14 10 7 5 3 20 13 9 6

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

API'ENI)IX C

72E-69

T a b l e C-3.2.1.2(0 T h r e s h o l d Fire Size at Response: 1000 B T U / S E C . Fire G r o w t h Rate: 600 Seconds to 1000 B T U / S E C Alpha: 0.003 BTU/SEC 3

Table C-3.2.1.2(u) T h r e s h o l d F i r e Size a t R e s p o n s e : 2000 B T U / S E C . F i r e G r o w t h R a t e : 50 S e c o n d s to 1000 B T U / S E C Alpha: 0.400 BTU/SEC s

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

28.0 .

.

.

.

.

.

TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

NOTE:

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

17 15 30 24 21 18 18 15 29 23 20 17 "16 14 28 23 19 17 15 14 28 22 19 16 15 13 27 21 18 16 14 13

14 12 28 22 18 15 13 12 27 21 17 15 13 11 26 20 17 14 12 ' 11 25 19 16 14 12 10 25 19 15 13 11 10

11 9 25 19 15 12 10 8 24 18 14 12 10 8 23 17 14 11 9 8 23 17 13 11 9 7 22 16 13 10 8 7

7 6 22 16 12 9 7 5 21 15 11 8 7 5 21 14 11 8 6 5 20 14 10 8 6 5 19 13 10 7 6 4

4 3 19 13 9 6 4 3 18 12 8 6 4 2 18 11 8 5 3 2 17 11 7 5 3 2 16 10 7 5 3 2

2 0 16 10 6 3 1 0 15 9 5 3 1 0 15 9 5 3 1 0 14 8 S 2 1 0 13 8 4 2 1 0

0 0 13 7 3 1 0 0 13 6 3 1 0 0 12 6 3 1 0 0 11 5 2 1 0 0 11 5 2 1 0 0

D e t e c t o r t i m e c o n s t a n t at a reference velocity of 5 ft/sec.

F o r SI Units:

l ft = 0 . 3 0 5 m 1000 B T U / s e c = 1055 k W

.

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

28.0 .

.

.

.

.

.

INSTALLED SPACING OF DETECTORS

INSTALLED SPACING OF DETECTORS 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

4.0 .

25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 t00 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 "80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 t20 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

35 30 26 23 21 20 28 23 20 18 16 15 24 20 17 15 14 13 21 17 15 13 12 11 19 16 13 12 11 10 18 14 12 11 lO 9 16 13 11 10 9 8 15 12 11 9 8 8 15 12 10 9 8 7 14 11 9 8 7 7 13 10 9 8

33 27 23 21 18 17 26 21 18 15 14 12 22 17 15 13 11 10 19 15 13 11 10 8 17 13 11 10 8 7 16 12 10 8 ' 7 6 14 11 9 8 7 6 13 10 8 7 6 5 12 9 8 6 5 5 12 9 7 6 5 4 11 8 7 5

31 24 20 17 15 13 23 18 15 13 11 10 19 15 12 10 8 7 17 13 10 8 7 6 15 11 9 7 6 5 13 10 7 6. 5 4 12 9 7 5 4 3 11 8 6 5 4 3 10 7 5 4 3 3 9 6 5 4 3 2 9 6 4 3

28 21 17 14 12 10 21 15 12 10 8 7 17 12 9 7 6 5 14 10 7 6 4 3 12 8 6 5 3 3 11 7 5 4 3 2 9 6 4 3 2 2 8 5 4 3 2 1 8 5 3 2 1 1 7 4 3 2 1 1 6 4 2 2

25 18 14 11 8 7 18 13 9 7 5 4 14 9 7 5 3 2 11 7 5 3 2 2 10 6 4 2 2 1 8 5 3 2 1 0 7 4 2 1 1 0 6 3 2 1 0 0 5 3 2 1 0 0 5 2 1 0 0 0 4 2 1 0

21 15 10 7 5 3 15 10 6 4 3 2' 11 7 4 3 1 1 9 5 3 2 1 0 7 4 2 1 0 0 6 3 1 0 0 0 5 2 1 0 0 0 4 2 1 0 0 0 3 1 0 0 0 0 3 1 0 0 0 0 2 1 0 0

18 11 7 4 2 1 12 7 4 2 1 0 9 4 2 1 0 0 6 3 1 0 ' 0 0 5 2 1 0 0 0 4 1 0 0 0 0 3 1 0 0 0 0 2 O 0 0 0 O 2 0 0 0 0 0 2 0 0 0 0 0 1 0 O 0

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-70

AUTOMATIC FIRE DETECTORS

Table C-3-2.1.2(v) T h r e s h o l d Fire Size at Response: 2000 B T U / S E C . Fire Growth Rate: 150 Seconds to 1000 B T U / S E C Alpha: 0.044 B T U / S E C s

Table C-3.2.1.2(u) Threshold Fire Size at Response: 2000 B T U / S E C . Fire Growth Rate: 50 Seconds to 1000 B T U / S E C Alpha: 0.400 B T U / S E C s

CEILING HEIGHT IN 'FEET

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

.

28.0 .

.

.

.

.

.

TAU RTI &T .

.

.

.

.

.

.

.

.

.

.

4.0 .

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 6Q 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

7 6 13 10 8 7 7 6 12 10 8 7 6 6 12 9 8 7 6 5 11 9 7 6 6 5 11 9 7 6 5 5

5 4 10 8 6 5 4 4 10 7 6 5 4 3 9 7 5 4 4 3 9 7 5 4, 3 3 9 6 5 4 3 3

2 2 8 5 4 3 2 2 8 5 4 3 2 1 7 5 3 2 2 1 7 4 3 2 2 1 6 4 3 2 1 1

1 0 6 3 2 1 1 0 5 3 2 1 O 0 5 3 2 1 0 0 4 2 1 0 0 0 4 2 1 0 0 0

0 0 4 2 1 0 0 0 3 1 0 0 0 0 3 1 0 0 0 0 3 1 0 0 0 0 2 1 0 0 0 0

0 0 2 0 0 0 0 0 2 0 0 0 0 0 2 0 0 0 0 0 1 0 0 0 0 0 1 0 0 0 0 0

N O T E : Detector time constant at a reference velocity of .5 ft/sec,

For SI Units:

1990 Edition

1 ft = 0.305 rn 1000 B T U / s e c -- 1055 k W

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

.

28.0 .

.

.

.

.

.

INSTALLED SPACING OF DETECTORS

INSIALLED SPACING OF DETECTORS 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

.

0 0 1 0 0 0 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0

25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 76 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 176 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

56 40 56 60 56 80 56 100 56 120 56 140 112 40 112 60 112 80 112'100 112 120 112 140 168 40 168 60 168 80 168 100 168 120 168 140 224 40 224 60 224 80 224 100 224 120 224 140 280 40 280 60 280 80 280 100 280 120 280 140 335 40 335 60 335 80 335 100 335 120 335 140 391 40 391 60 391 80 391 100 391 120 391 140 447 40 447 60 447 80 447 100 447 120 447 140 503 40 503 60 503 80 503 100 503 120 503 140 559 40 559 60 559 80 569 100 569 120 559 140 615 40 615 60 615 80 615 100

60 50 43 38 34 31 49 40 35 31 28 26 43 35 30 27 24 22 38 31 27 24 22 20 35 29 25 22 20 18 32 27 23 20 18 17 30 25 21 19 17 16 29 23 20 18 16 15 27 22 19 17 15 14 26 21 18 16 14 13 25 20 17 15

57 46 38 33 29 26 47 38 32 28 24 22 41 33 28 24 21 19 36 29 25 21 19 17 33 27 22 19 17 16 31 24 20 18 16 14 29 23 19 16 15 13 27 21 18 15 14 12 26 20 17 14 13 11 24 19 16 14 12 11 23 18 15 13

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

53 41 34 28 25 21 44 34 28 24 21 18 38 30 24 21 18 16 34 26 22 18 16 14 31 24 19 16 14 12 28 22 18 15 13 11 26 20 16 14 12 10 25 19 15 13 11 9 23 18 14 12 10 9 22 16 13 11 9 8 21 16 13 10

49 37 29 24 20 17 40 31 24 20 17 14 35 26 21 17 14 12 31 23 18 15 13 11 28 21 16 13 11 9 26 19 15 12 10 8 24 17 14 11 9 7 22 16 12 10 8 7 21 15 11 9 7 6 19 14 11 8 7 5 18 13 10 8

44 32 25 19 15 13 37 27 21 16 13 10 32 23 18 14 11 9 28 20 15 12 9 7 25 18 13 10 8 6 23 16 12 9 7 5 21 15 11 8 6 5 19 13 10 7 5 4 18 12 9 7 5 4 17 11 8 6 4 3 16 11 7 5

40 28 20 15 11 8 33 23 17 12 9 7 28 20 14 10 8 5 25 17 12 9 "6 4 22 15 11 7 6 4 20 13 9 6 4 3 18 12 8 6 4 2 17 11 7 5 3 2 15 10 6 4 3 2 14 9 6 4 2 1 13 8 5 3

36 23. 16 11 7 4 30 19 13 9 6 3 25 16 11 7 4 2 22 14 9 6 3 2 19 12 8 6 3 1 17 10 6 4 2 1 15 9 6 3 2 1 14 8 5 3 1 1 13 7 4 2 1 0 12 6 4 2 1 0 11 6 3 2

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

API'ENI)IX C

72E-71

Table C-3-2.1.2(v) T h r e s h o l d Fire Size at Response: 2000 B T U / S E C . Fire G r o w t h Rate: 150 Seconds to 1000 B T U / S E C Alpha: 0.044 B T U / S E C '

T a b l e C-3-2.1.2(w) T h r e s h o l d Fire Size at Response: 2000 B T U / S E C . Fire Growth Rate: 300 Seconds to 1000 B T U / S E C Alpha: 0 . 0 l l B T U / S E C s

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0

CEILING HEIGHT IN FEET 28.0

.

TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

14 12 24 .19 17 15 13 12 23 19 16 14 13 11 22 18 15 13 12 '11 22 17 15 13 12 11 21 17 14 13 11 10

11 10 22 17 14 12 11 10 21 17 1.4 12 10 9 20 16 13 11 10 9 20 15 13 11 9 8 19 15 12 10 9 8

9 7 20 15 12 10 8 7 19 14 11 9 8 7 18 13 11 9 7 6 17 13 10 8 7 6 17 12 10 8 6 5

6 5 17 12 9 7 6 5 16 12 9 7 5 4 '16 11 8 6 5 4 15 10 8 6 5 3 14 10 7 5 4 3

4 3 15 10 7 5 3 2 14 9 6 4 3 2 13 9 6 4 3 2 12 8 5 '4 3 2 12 8 5 3 2 2

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

24.0, 28.0 .

.

INSTALLED SPACING OF DETECTORS

INSTALLED SPACING OF DETECTORS 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

.

2 1 12 7 5 3 2 1 11 7 4 2 1 1 11 6 4 2 1 1 10 6 3 2 1 0 9 5 3 2 1 0

1 0 10 5 3 1 0 0 9 5 2 1 0 0 8 4 2 1 0 0 8 4 2 1 0 0 7 3 2" 1 0 0

N O T E : D e t e c t o r t i m e c o n s t a n t at a r e f e r e n c e velocity of 5 ft/sec. ForSI Units: 1 ft = 0.305 m 1 0 0 0 B T U / s e c = 1055 k W

25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

56 40 56 60 56 80 56 100 56 120 56 140 112 40 112 60 112 80 112 100 112 120 112 140 168 40 168 60 168 80 168 100 168 120 168 140 224 40 224 60 224 80 224 100 224 120 224 140 280 40 280 60 280 80 280100 280 120 280 140 335 40 335 60 335 80 335 100 335 120 335 140 391 40 391 60 391 80 391 100 391 120 391 140 447 40 447 60 447 80 447 100 447 120 447 140 503 40 503 60 503 80 503 100 503 120 503 140 559 40 559 60 559 80 559 100 559 120 559 140 615 40 615 60 615 80 615 100

79 64 54 47 42 38 67 54 46 41 36 33 59 48 41 36 33 30 53 43 37 33 30 27 49 40 34 30 27 25 46 37 32 28 26 23 43 35 30 27 24 22 41 33 29 25 23 21 39 32 27 24 22 20 37 30 26 23 21 19 36 29 25 22

73 56 46 40 35 31 63 49 41 35 31 28 56 44 37 32 28 25 51 40 34 29 26 23 47 37 31 27 24 22 44 35 29 25 22 20 41 33 28 24 21 19 39 31 26 22 20 18 37 30 25 21 19 17 36 28 24 20 t8 16 34 27 23 19

66 50 40 33 29 25 58 45 36 30 26 23 52 40 33 .28 24 21 48 37 30 25 22 19 44 34 28 23 20 18 41 32 26 22 19 17 39 30 24 21 18 16 37 28 23 19 17 15 35 27 22 18 16 14 33 25 21 17 15 13 32 24 20 17

60 44 34 28 23 20 54 40 31 26 21 18 48 36 29 23 20 .17 44 33 26 22 18 15 41 31 24 20 17 14 38 28 23 19 15 13 36 27 21 17 14 12 34 25 20 16 14 11 32 24 19 15 13 11 30 23 18 14 12 10 29 21 17 14

55 39 29 23 18 15 49 35 27 21 17 14 44 32 24 19 15 12 41 29 22 18 14 11 37 27 21 16 13 11 35 25 19 15 12 10 33 23 18 14 11 9 31 22 17 13 10 8 29 21 16 12 10 8 28 19 15 11 9 7 26 18 14 11

49 33 24 18 14 10 ,44 30 22 17 13 . 9 40 28 20 15 11 9 37 25 19 14 10 8 34 23 17 13 9 7 32 22 16 12 9 6 29 20 15 11 8 6 28 19 14 10 7 5 26 18 13 9 7 5 25 17 12 8 6 4 23 16 11 8

44 29 20 ]4 9 6 40 26 18 12 8 5 3624. 16 11 7 5 33 22 15 10 .7 4 31 20 14 9 6 4 28 18 12 8 5 3 26 17 11 8 5 3 25 16 10 7 4 2 23 15 10 6 4 2 22 14 9 6 3 2 20 13 8 5

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

AUTOMATIC FIRE DETECTORS

72E-72

T a b l e C-3-2.1.2(w) T h r e s h o l d Fire Size at Response: 2000 B T U / S E C . Fire G r o w t h Rate: 300 Seconds to 1000 B T U / S E C Alpha: 0.011 B T U / S E C s

T a b l e C-3-2.1.2(x) T h r e s h o l d Fire Size at Response: 2000 B T U / S E C . Fire G r o w t h Rate: 500 Seconds to 1000 B T U / S E C Alpha: 0.004 B T U / S E C '

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RII &f .

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

.

.

8.0 .

.

.

12.0 "._ .

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20,0 .

.

.

.

.

.

.

24.0 .

.

.

.

.

.

.

.

28.0 .

TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

20 18 35 28 24 21 19 17 33 27 23 20 18 17 32 26 22 20 18 16 31 25 22 19 17 16 30 25 21 19 17 15

17 15 33 26 22 19 16 15 32 25 21 18 16 14 31 24 20 17 15 14 30 23 19 17 15 13 29 23 19 16 14 13

14 12 30 23 19 16 14 12 29 22 18 15 13 11 28 21 17 15 12 11 27 21 17 14 12 10 26 20 16 13 11 10

11 9 28 20 16 13 11 9 27 20 15 12 10 8 26 19 15 12 10 8 25 18 14 11 9 8 24 17 13 11 9 7

8 7 25 18 13 10 8 6 24 17 12 10 7 6 23 16 12 9 7 5 22 15 11 9 6 5 21 15 11 8 6 5

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12,0 .

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

.

.

28.0

.

INSTALLED SPACING OF DETECTORS

INSTALLED SPACING OF DETECTORS 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

4,0 .

6 4 22 15 10 7 5 4 21 14 10 7 5 3 20 13 9 6 4 3 19 13 9 6 4 3 18 12 8 6 4 2

3 2 19 12 8 5 3 1 18 11 7 4 2 1 17 11 7 4 2 1 16 10 6 4 2 1 16 9 6 3 2 1

N O T E : Detector time constant at a r e f e r e n c e velocity of 5 ft/sec. F o r S i Units: 1 ft = 0 . 3 0 5 m 1000 B T U / s e c = 1055 k W

25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

92 72 61 52 46 42 81 64 54 47 42 38 73 58 49 43 39 35 67 54 46 40 36 33 62 50 43 37 34 31 58 47 40 35 32 29 55 44 38 33 30 27 52 42 36 32 29 26 50 40 35 30 27 25 48 39 33 29 26 24 46 37 32 28

82 62 51 43 37 33 74 57 47 40 35 31 68 53 44 37 33 29 63 49 41 35 31 27 59 46 38 33 29 26 55 44 36 31 27 25 53 41 34 30 26 23 50 39 33 28 25 22 48 38 31 27 24 21 46 36 30 26 23 21 44 35 29 25

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

74 55 43 36 31 27 68 51 41 34 29 25 63 47 38 32 27 24 58 45 36 30 26 23 55 42 34 29 25 22 52 40 32 27 23 20 49 38 31 26 22 20 47 36 29 25 21 19 45 34 28 24 20 18 43 33 27 23 20 17 41 32 26 22

67 48 37 30 25 21 62 45 35 29 24 20 58 42 33 27 22 19 54 40 31 26 21 18 51 38 30 24 20 17 48 36 28 23 19 16 46 34 27 22 18 16 44 32 26 21 18 15 42 31 24 20 17 14 40 30 23 19 16 14 38 28 22 18

60 42 32 25 20 16 56 40 30 23 19 15 53 37 28 22 18 14 50 35 27 21 17 14 47 33 25 20 16 13 44 32 24 19 15 12 42 30 23 18 15 12 40 29 22 17 14 11 38 27 21 16 13 11 37 26 20 16 13 10 35 25 19 15

54 49 36 31 26 22 20 15 15 10 11 7 51 46 35 30 25 20 19 14 14 10 11 6 48 43 33 28 24 19 18 13 13 9 10 ' 6 45 41 31 .27 23 18 17 13 13 9 10 6 43 38 29 25 21 17 16 12 12 8 9 5 40 36 28 24 20 16 15 11 11 8 9 5 38 35 26 23 19 15 14 11 11 7 8 4 36 33 25 21 18 15 14 10 10 7 8 4 35 31 24 20 17 14 13 9 10 6 7 4 33 30 23 19 17 13 12 9 9 6 7 4 32 29 22 19 16 13 12 8

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-73

APPENDIX C

Table C-3-2.1.2(y) Threshold Fire Size at Response: 2000 B T U / S E C . Fire Growth Rate: 600 Seconds to 1000 B T U / S E C Alpha: 0.003 B T U / S E C '

Table C-3-2.1.2(x) Threshold Fire Size at Response: 2000 B T U / S E C . Fire Growth Rate: 500 Seconds to 1000 B T U / S E C Alpha: 0.004 B T U / S E C s

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI AT

4.0

8.0

12.0

16.0

20.0

24.0

28.0

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

TAU RTI AT

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

NOTE:

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

25 23 45 36 31 27 24 22 43 35 30 26 24 22 42 34 29 25 23 21 41 33 28 25 22 20 40 32 27 24 22 20

22 20 43 34 28 24 21 19 41 32 27 23 21 19 40 31 26 23 20 18 39 31 25 22 19 17 38 30 25 21 19 17

19 16 40 31 25 21 18 16 . 39 30 24 20 17 15 37 29 23 19 17 15 36 28 22 19 16 14 35 27 22 18 16 14

15 13 37 27 22 18 15 13 36 26 21 17 14 12 35 26 20 16 14 12 33 25 19 16 13 11 32 24 19 15 13 11

12 10 34 24 18 14 11 9 33 23 18 14 11 9 31 22 17 13 11 8 30 22 16 13 10 8 29 21 16 12 10 8

9 6 31 21 15 11 8 6 30 20 14 11 8 6 28 19 14 10 7 5 27 19 13 10 7 5 27 18 13 9 7 5

5 3 27 18 12 8 5 3 26 17 11 8 5 3 25 16 11 7 5 3 24 16 10 7 4 2 24 15 10 6 4 2

D e t e c t o r t i m e c o n s t a n t a t a r e f e r e n c e velocity o f 5 f t / s e c .

F o r SI U n i t s :

1 ft = 0 . 3 0 5 m

1000 B T U / s e c

=

105.5 k W

8.0

12.0

16.0

20.0

24.0

28.0

INSTALLED SPACING OF DETECTORS

INSTALLED SPACING OF DETECTORS 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

4.0

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

96 75 63 54 48 43 86 68 57 49 44 40 78 62 52 46 41 37 72 57 49 43 38 35 67 54 46 40 36 33 63 51 43 38 34 31 60 48 41 36 32 29 57 46 39 34 31 28 54 44 37 33 30 27 52 42 36 32 28 26 50 41 35 30

85 64 52 44 38 34 78 60 49 41 36 32 72 56 46 39 34 30 67 52 43 37 32 29 63 49 41 35 31 27 60 47 39 33 29 26 57 44 37 32 28 25 54 43 35 30 27 24 52 41 34 29 26 23 50 39 33 28 25 22 48 38 32 27

76 56 44 37 31 27 71 53 42 35 30 26 66 50 40 33 28 25 62 47 38 32 27 24 59 45 36 30 26 23 56 42 34 29 25 22 53 41 33 28 24 21 51 39 32 26 23 20 49 37 30 25 22 19 47 36 29 24 21 19 45 35 28 24

68 49 38 31 25 21 64 47 36 29 24 21 61 44 34 28 23 20 57 42 33 27 22 19 54 40 31 26 21 18 52 38 30 25 21 17 49 36 29 24 20 17 47 35 28 23 19 16 45 34 26 22 18 15 43 32 25 21 17 15 42 31 25 20

62 43 32 25 20 16 58 41 31 24 19 16 55 39 30 23 19 15 52 37 28 22 18 14 50 35 27 21 17 14 47 34 26 20 16 13 45 32 25 19 16 13 43 31 24 19 15 12 42 30 23 18 14 12 40 29 22 17 14 11 39 28 21 17

56 37 27 20 15 12 53 36 26 19 15 11 50 34 25 19 14 11 48 32 24 18 13 10 45 31 23 17 13 10 43 30 22 16 12 9 41 28 21 15 12 9 40 27 20 15 11 8 38 26 19 14 11 8 36 25 18 14 10 8 35 24 18 13

50 32 22 15 11 7 48 31 21 15 10 7 45 29 20 14 10 6 43 28 19 13 9 6 41 27 18 13 9 6 39 26 18 12 8 5 37 24 17 t2 8 5 36 23 16 11 7 5 34 22 15 11 7 4 33 21 15 10 7 4 32 21 14 10

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-74

AUTOMWI'IC FIRE DETECTORS

Table C-3-2.1.2(y) Threshold Fire Size at Response: 2000 BTU/SEC. Fire Growth Rate: 600 Seconds to 1000 BTU/SEC Alpha: 0.003 B T U / S E C s

Design Tables Index

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

24.0 .

.

.

.

.

INSTALLED SPACING OF DETECTORS 275 615 120 275 615 140 300 671 40 300 671 60 300 671 80 300 671 100 300 671 120 300 671 140 325 727 40 325 727 60 325 727 80 325.727 100 325 727 120 325 727 140 350 783 40 350 783 60 350 783 80" 350 783 100 350 783 120 350 783 140 375 839 40 375 839 60 375 839 80 375 839 100 375 839 120 375 839 140 400 894 40 400 894 60 400 894 80 400 894 100 400 894 120 400 894 140

27 25 49 39 33 29 26 24 47 38 32 29 26 23 46 37 31 28 25 23 44 36 31 27 24 22 43 35 30 26 23 21

24 22 47 37 3t 26 23 21 45 35 30 25 22 20 44 34 29 25 22 20 42 33 28 24 21 19 41 32 27 23 21 18

20 18 44 33 27 23 20 17 42 32 26 22 19 17 41 31 25 21 18 16 40 30 25 21 18 16 39 30 24 20 17 15

17 14 40 30 24 19 16 14 39 29 23 19 16 13 38 28 22 18 15 13 37 27 21 18 15 12 36 26 21 17 14 12

13 11 37 27 20 16 13 10 36 26 20 15 12 10 35 25 19 15 12 9 34 24 18 14 11 9 33 23 18 14 11 9

THRESHOLD FIRE SIZE BTU/SEC,

28.0

10 7 34 23 17 12 9 7 33 22 16 12 9 7 32 22 16 12 9 6 31 21 15 11 8 6 30 20 14 11 8 6

6 4 30 20 13 9 6 4 29 19 13 9 6 3 28 "18 12 8 S 3 27 18 12 8 5 3 26 17 11 8 5 3

FIRE ALPHA GROWTHPERIOD SEC. BTU/SEC 3

TABLE C-3-2.1.2(a) TABLE C-3-2.1.2(b) TABLE C - 3 - 2 . 1 . 2 ( c ) TABLE C - 3 - 2 . 1 . 2 ( d ) TABLE C-3-2.1.2(e)

250 250 250 250 250

50 150 300 500 600

0.400 0.044 0.011 0.004 0.003

fABLE TABLE TABLE TABLE TABLE

C-3-2.1.2(f) C-3-2.1.2(g) C-3-2.1.2(h) C-3-2.1.2(i) C-3-2.1.2(j)

500 500 500 500 500

50 150 300 500 600

0.400 0,044 0.011 0.004 0,003

TABLE fABLE TABLE TABLE fABLE

C-3-2.1.2(k) C-3.2,1.2(I) C-3-2.1.2(m) C-3.2.1.2(n) C-3-2.1,2(o)

750 750 750 750 750

50 150 300 500 600

0,400 0.044 0.011 0.004 0.003

TABLE fABLE TABLE fABLE fABLE

C-3-2.1.2(p) C-3.2.1.2(q) C-3.2.1.2(r) C-3-2.1.2(s) C-3-2.1.2(t)

1000 1000 1000 1000 1000

50 150 300 500 600

0.400 0.044 0.011 0,004 0.003

fABLE fABLE TABLE fABLE TABLE

C-3.2.1.2(u) C-3.2,1,2(v) C-3-2.1.2(w) C-3-2.1,2(x) C-3-2.1.2(y)

2000 2000 2000 2000 2000

50 150 300 500 600

'

0.400 0,044 0.011 0.004 0.003

NOTE: Detector time constant at a reference velocity of 5 ft/sec. 1 ft = 0.305 m 1000 BTU/sec = 1055 kW

For SI Units:

C-3-3 R a t e - o f - R i s e H e a t D e t e c t o r S p a c i n g .

C-3-3,1 Tables C-3-3.2 and C-3-3.3 a r e to be used to d e t e r m i n e the installed spacing of rate-of-rise heat detectors. T h e analytical basis for the, tables is p r e s e n t e d in Section C-6 o f this a p p e n d i x . This section shows how the tables are to be used.

C-3-3.2 Table C-3-3.2 p r o v i d e s installed spacings for rateof-rise heat detectors r e q u i r e d to achieve detection for a specific t h r e s h o l d fbr size, fire growth rate, and ceiling h e i g h t . T h i s table m a y be u s e d d i r e c t l y to d e t e r m i n e installed spacings for 50 ft (15.2 m) listed spacing detectors.

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX C

72E-75

T a b l e C-3-3.2 I n s t a l l e d S p a c i n g s for Rate o f R i s e H e a t D e t e c t o r s T h r e s h o l d F i r e Size a n d G r o w t h Rate

Ceai,~g

Height Oft)

Q~ = 750 Btu/sec.

Q~ = lOOO Btu/sec.

~

= 500

250

(2., =

Btu/sec.

~

= lOO Btu/sec.

Btu/sec.

s

m

f

s

m

f

S

m

f

s

m

f

S

m

f

4

28

32

32

26

28

27

22

24

23

16

17

16

1!

11

10

5

27

31

31

25

27

27

21

23

22

15

16

15

10

10

9

5

26

30

31

24

26

27

20

22

22

15

15

15

9

9

9

7 '

25

29

30

23

26

26

19

21

21

14

14

14

9

9

8

8

24

29

30

22

25

26

18

21

21

15

13

14

6

8

8

9

23

26

29

21

24

25

17

20

90

12

13

13

7

7

7

23

95

16

19

7

10

22

27

29

20

20

12

12

13

7

7

11

21

27

26

18

23

24

15

19

19

11

12

12

6

6

6

12

20

26

26

17

22

24

15

18

19

10

11

12

5

5

5

13

19

25

27

16

22

23

14

18

18

9

II

11

5

5

14

16

24

27

15

21

22

13

17

18

9

10

11

15

16

24

26

14

20

21

12

17

17

8

10

10

16

15

23

25

I$

19

21

11

16

16

7

9

10

6

17

14

22

25

12

19

20

10

15

16

9

9

18

13

22

24

11

18

20

9

14

15

8

8

23

19

12

21

10

17

19

8

14

14

8

8

20

11

20

9

16

19

7

13

14

7

7

21

10

19

8

15

18

12

13

7

22

9

19

7

15

17

12

13

6

23

6

18

14

17

I1

12

5

24

17

IS

16

11

11

5

25

16

12

15

10

10

4

26

15

12

15

9

10

27

14

11

14

9

28

13

11

13

29

13

10

8

10

7

30

12 s - "slow'" fire

and fire growth rate. This takes into account the difference i n s e n s i t i v i t y b e t w e e n t h e d e t e c t o r a n d a 5 0 ft ( 1 5 . 2 m ) listed detector.

5

4

8

- "fast" fire

m - '*medium" fire

C-3-3.3 For rate-of-rise heat detectors with a listed spacing of other than 50 ft (15.2 m), installed spacing obtained from Table C-3-3.2 must be multiplied by the modifier shown in Table C-3-3.3 for the appropriate listed spacing

I

T a b l e C-3-3.3

S p a c i n g M o d i f i e r s for Rate-of-Rise Heat Detectors

L i s t e d S p a c i n g ft 15 20 25 30 40 50 70 For SI Units:

(Fire G r o w t h Rate) Slow Medium Fast 0.57 0.72 0.84 0.92 0.98 1.00 1.00

0.55 0.63 0.78 0.86 0.96 1.00 1.01

0.45 0.62 0.76 0.85 0.95 1.00 1.02

1 ['t = 0.305 m.

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-76

AUTOMATICFIRE DETECTORS

C-3-3.4 Having determined the threshold fire size (C-2-2.2), the fire growth rate (C-2-2.3), the detector's listed spacing, and the ceiling height, use Table C-3-3.2 to determine the corrected spacing for 50 ft (15.2 m) listed detectors. Use Table C-3-3.3 to determine the spacing modifier. Find the required installed spacing by multiplying the corrected spacing by the spacing modifier.

C-3o3.4 Example.

Input:

Spacing:

Ceiling Height: Detector Type:

12 ft (3.7 m) Combination rate-ofrise, fixed temperature 30 ft (9.1 m) listed spacing Q , / = 500 Btu/sec Fire Growth Rate = medium From Table C-3-3.2, installed spacing = 18 ft (5.5 m) From Table C-3-3.3, spacing modifier = 0.86 Installed spacing = 18 x 0.86 = 15.5 ft (4.7 m).

C-3-4.1.4 Once a threshold size and expected fire growth rate have been selected, an installed detector spacing can be obtained from Figures C-3-4.1 (a)-(i) for a certain detector's listed spacing, ambient, temperature, and ceiling height. As in Section C-3-2.5, Example 1, to determine the installed spacing of 135°F (57.2°C) fixed temperature heat .detectors with a listed spacing of 30 It. (9.1 m), to detect a slowly developing fire at a threshold fire size of 500 Btu/sec (527 kW) in a room 10 ft (3 m) high with an ambient temperature of 70°F (21.1°C), the following procedure is used:

Example 1.

h,put:

10 fi (3 m) Fixed temperature 135°F (57.2°C) listed spacing, 30ft(9.1 m) O~: 500 Btu/sec (527 kW) Fire growth rate: slow Ambient temperature: 70°F (21. I°C); AT = 65°F (36.1°C)

Spacing:

From Figure C-3-4.1(a), use an installed spacing of 17 ft (5.2 m).

Ceiling Height: Detector Type:

C-3-4 Design Curves. C-3-4.1 The design curves [Figures C-3-4.1 (a)-(i)] may also be used to determine the installed spacings of heat detectors. However they are not as comprehensive as the tables because the tables include additional fire growth rates, fire sizes, and detector sensitivities.

Note that if the ceiling height is 15 ft (4.6 m), the same graph gives an installed spacing of 12 ft (3.5 m). A ceiling height of 20 ft (6.1 m) would require a spacing of 8 ft (2.4 m). Tiffs change in spacing clearly illustrates the need to consider ceiling height in the design of a detection system.

Co3-4.1.1 Fixed Temperature Heat Detectors.

Figures C-3-4.1 (a), (b), (c), (d), (e), and (f) can be used directly to determine the installed spacing for fixed temperature heat detectors having listed spacings of 30 ft and 50 ft (9.1 m and 15.2 m), respectively, when the difference between the detectors' rated temperature (Ts) and the ambient temperature (To) is 65°F (18.3°C). When AT is not 65°F (18.3°C), tables previously discussed in Section C-3-3 should be used.

C-3-4.1.5 Example 2.

Input:

C-3-4.1.2 Rate-of-Rise Heat Detectors. Figures C-3-4.1(g), (h), and (i) can be used directly to determine the installed spacing for rate-of-rise heat detectors having a listed spacing of 50 ft (15.2 m). C-3-4.1.3 To use the curves, the same format must be followed as with tables. The designer must first determine how large a fire can be tolerated before detection can occur. This is the threshold fire size, Q4. Curves are presented, in most cases, for values of Qa = 1000, 750, 500, 250, 100 Btu/sec (1055, 791,527, 264, and 105 kW). Interpolation between values of Q,/on a given graph is allowable. Table C-2-2.2.1(a) also contains examples of various fuels and their fire growth rates under specified conditions.

1990 Edition

Ceiling Height: Detector Type:

10 ft (3 m) Combination rate-of-rise and fixed temperature; 50 ft (15.2 m) listed spacing Q,/: 500 Btu/sec (527 kW) Fire growth rate: ifast Ambient temperature: 70°F (21.1°C); AT = 65°F (36.1°C)

Spacing:

From Figure C-3-4.1(i), use an installed spacing of 20 ft (5.8 m).

A 30 ft (9.1 m) fixed temperature detector would require a 7.5 ft (2.5 m) spacing. If the fire growth rate was slow, as in Example 1, the rate-of-rise detector would require an installed spacing of 16 ft (4.88 m).

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected]. APPENDIX

C

72E-77

40 L

I--=---

'

1 J

"--------

. . . . . . . . . . . .

........

-----'---t~

_j_ . . . . .

35

,

I

1

'

!

'

~ - 1 - - - - 4 - - - ~ - -

----------~~

r

__---~C--_--_--_--_~__ -E_~

~

-

-

-

-

30 ........

.......

....

.

j

.....

:-'-

----t

.

,

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

---4

. . . . .

i

25 A v I"

.-L . . . . . . .

I--

. . . . .

' -*

- "~ . . . . . . . . . . . . . . . . . .

~ - - - - - - - t

---T------t--:

--~ . . . . .

--

Qd = 1000 Btu/sec

20 "O

. . . . . .

-+

....

-

J.~

'

15

......

~ ...........

~ .... .~-~-,~

.

.

.

.

.

.

.

.

. . . . . .

~ - - ! - -

-I-

~,-~ ~ ' - ~ ' - - ~

................

__:_.__~

-

.

.....

~-_ ""--

.

- - C --t

...........

10

.... -

~o

~ - - : - -

. ~

_-~__~ _ _ ~

ram--

5

/ Example 1 3-4.1.4

F i g u r e C-3-4.1(a)

10

2015 Ceiling H e i g h t (ft)

Heat Detector, Fixed Temperature

25

30

L i s t e d S p a c i n g : 30 ft (9.1 m) S l o w Fire. T = 65°F (36.1°C)

1990

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Edition

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-78

AUTOMATIC

40

,,

FIRE

! '

,

:

,

,

,

,

,

I

DETECTORS

k

I~I:

i

!ill -i= ~, i! , li l i i J': :,:,l!

,

,i i: ~ I L

,

~

i

,

i

:

l

i

I

J

'

~

i

I

!

• •

,

'

~ ,

t

'

'

,

[

i i '

I

I

I

[

'

, i

'

, .

i

.

'

'

,

'

,

' '''111 i

i

'

!,ii;

, *

~

,i



. . . .

:i i

i ' i ~

I,

'

i I i!i~

!

" .

"

I

'

I

i I

1

ii!!:i

--I

,

'

'

35

~ Ii ~

l,li

,'

i

Ii=

II

i

30 I

,

t

;

l

t

., ! I i

:,

:~,"4:

A

~ ,

i i ! : i ~4

~

"

"~.

,

,

:

,

i

,

i

t '

I

i ,

i

, '

"

i

I

]



.,,

1

I . i I I

~

,I

I

'

*

I

I

. . . .

.:

I

:!~

r

'

'

,

I,

i I

i

,

,

~

,

!

T

b . - ~ ,.--r----t---~-~-. - - . - I - - - . ~ - . - . ~ . . ~ - - - - - - ,

, , '

j

:

.

' ,

i

/

', :

'

t

'

'

.

.

.

.

.

.

1---'-'-"-t-

"7. "

"

1--

20

: "

I

P

c P

"0

t

~!',Lill '! '

i I i '

: ~ z

x

!i

.

x

[ I,,

I

~ , !

l

i

;::,

t

:

i !\' I

,

! : ~

"!"-.,

~.

:

t

~

r .

, '

. '

,

:'I

I . . . . .

'

:,

! i"1,.;

:

: ]_!,

:

=

. . . . .

t

,

,

• i

i

i I i

i

;

15 ~

~

,

i ,~'

i

i, :ii ;

1

i

'~

I

i

;

i

I

r

:

;

i

i

:

l

l

I ~ |

til!

"

!

I

I

!

,'t.,,J :

'

I I ~II' ~ l

:I ! :

!1

!i-,,~

,'i'*

'

'

\

:

'

I i~'~

,

. ' I ' ' : ',J

Qd-

1000Btu/sec

I ,x~l,l:

!:i'

~,,'

i

!

:1,

._

10

....

~

: ! t

l

:,,

i

I,

'

i

:

'

~il

'

**'%L

;

i

I

:

i

:

i

,

:

*~i

!

l:i

5

i



~0

L

i

:

:

'

"!,,

~

,

,

'

J

,

'

.

", = . . . . .

[,,:!'~',lill

:

15 Ceiling

Figure C-3-4.1(b)

i



t

250

[:::i i

,

I

20 Height

!

25

(ft)

Heat Detector, Fixed Temperature Listed Spacing: 30 ft (9.1 m) Medium Fire. T = 65°F (36.10C)

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

30

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX

C

72E-79

40

~"

-

' '~ ' '~~ : :~ ' I' '

::

'] ' !:"I

! .....

I , I ~ : , ~

, .

' '

,

, !i ~: I

ii i ~i [ '

35 . . . . . . . . . .............

-I- ..................

.

30

"~

. . . .

.................... ........ ........

~,,

,

'

I

i]

. ; --.-.

i ,

!. . . . . . .

,

.

-"--" ,

'

, '

.

.

.

[

. ,

. ''

,

]

',

~

"--:

~-''

~ ,.:

~ : ; "'

,

-"'T

-

_'

,

.

- . ' * q !

,

~;

;~

-

4

, ~ ',1,, ...'.

----r-~-4 ~

"-'1--"

!

~ . ,- , - ,- * ,-. . -: ,-. ,

-r-"~"

I

i '

I



.

,

~ - - i

I

---

1

~

....

,'



.

: • , , ,

"

A ......... .~

: L . . . . . . . . '; , ,

~

.

_

~ ,

~ _ : _ ~ ., . . _ _ ,

:

. ;

:..

]

,

i

i i :

i

'

,

i

i

i,,

,ili.

25 .

.

.

.

.

.

.

.

.

.

i

i

!

-l-"-'t

O} t.

O~ Q.



20



'

:

,,,,

.---, . . . . . . . . . .

,

~.-. . . . . .

__~

{--.

, - " : - - ' - " "---'i"

?

. . . .

-_,._

.

. --T-,-,--,----~

.

. . . .

~ :.



,I,

:

_~

~

,,,

,:'

,, - - t

I~:!

.

"O (D

"

t""

........

,

"---'-'-'-~-~-~:

'

' ~ i

:, . . . , ~. . . . . . . . . . . . . -------~. . _ ~ ~- - ~ - ~ - ~ - - - ' . - '~ ~ - - ~

15

"x,~-'-'-!-,----~-....

'

:

:

i~ ' ', ,

~-----~-Y-'~--

, ,

~

:

";

,

,

':

i. t, i .

.

-

I

~

--.

i1~ ----

--

10

10

I

Figure

15 Ce(ling

C-3.4.1(c)

Heat

Detector,

Fixed

Temperature

Listed

20

Height

Spacing:

25

30

(It)

30

ft (9.1

m)

Fast

Fire;

T

=

65°F

(36.1°C)

1990

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Edition

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-80

AU'I'OMA'I'IC FIRE DETECTORS

m ~

45

=

,

40 "-

- . . . . "' ]-/

..J_

35 ,

i

i

30

25 •1"

'

A .

e" (J ¢0

.

.

.

t . . . . . . . . .

20

O. ¢/)

Qd= 1 0 0 0 B t u / s e c

15

____L_

750,

.

,

10

~ _

,

..~-._--

I~

.;

i

5

.-

.

~ -', 500 .----~----~ -2

h.

.

.

.

*

-

-

~ -

-

.... ,

0

~---~----~

- _ - ~ _ 100 ~-~-' J

,

10

15

20

25

Ceiling Height (ft) Figure C-3-4.1(d)

1990 Edition

Heat Detector, Fixed Temperature Listed Spacing: 50 ft (15.2 m) Slow Fire. T = 65°F (36.1"C)

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

30

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX

72E-81

C

I

4O

..............

4--" . . . . . . . . . . . .

t

...............

4 ..........

b ............

II

..............

4 ...............

-1

...............

1 ................

i

_ _~ . . . . .

~

L ....

-'

ti. . . . .

. . . . . . . . . .

-

~___

i .........

35

i

. . . . . . . . . . . . . .

i . . . . . . . . . . . . . . . .

: _--C._.._--.:Z _ - _ 2 _ - 1 - ~ _ - _ - 2 : - - - -

t ._-2-CZl

30 . . . . . . . . . . . . . .

!--=-4.--4

J~ ................

. . 2 Z c Z . . . . . :1_]2 2 : L ~ Z

Z

:

...... _1_-__

+

!

1

I

m

A

v

4

25 . . . . . . . . . . . . . .

i

i

..........

= 09

I

"0

t

i i

I

I , ,

I

20 ....

-----;

.........

......... " .........

---

-I-4 . . . .

................. ......... : ....... ....................

i f }

15 .................

~ ........

_

. . . .

Qd = 1000 Btu/sec

...--

......

~

. . . .

-L.---

10 P - - , - - - ~ I ..................

4-

I ..............

q

t .............

:-..-'-:4.4*

...................

250

,

......

]

,

~

~.

,

,

~

,

/~U

500

.--]

5

............

1

I

I

,

I !

__._,

4

.......

~. . . . .

:

~,___. '-

;I I

i

,'. . . . . . . . . . . . . .

0

~:'

-t

5

Figure C-3-4.1(e)

"' r - ' - - - f - - - - "

]

!

'

;

I

''

'

i.

I

10

i

i

] .....

llll

15

20

25

30

35

Heat Detector, Fixed Temperature Listed Spacing: 50 ft (15.2 m) Medium Fire. T = 65°F (36.1"C)

1 9 9 0 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-82

A U T O M A T I C FIRE DETECTORS

i

45

,

i

i

i

I

I

I p

I

-4-!40

-!

-Ib

I

35

r

f _1_ r I

30 J

Ii

I 25

-L

v

2-

.E m

.!

u~ 20

r

i

C I

15 .

I

+ 10 I

+ +

5

-t-J 0 0

,5

10

15

20

25

Ceiling Height (ft) Figure C-3-4.1(1~ H e a t Detector, Fixed Temperature Listed Spacing: 50 ft (15.2 m) Fast Fire.

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

30

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX C

'

/

---

i

I

--;--;----i - m :

~--:~

i

1

,

"~i~

'

,

=

i'I'~_ ...;.._: I._~_._. 4 _ .

-:-''~--'

'

,

i

'. . ~ .

. .

-

; ....

. . . . . . . . . ,

72E-83

i

i

. . . . .i

=

'

,

e

:I

.

I

"i '

q

+

. . . .

!, :

I ' I : ,

-:-'-"-'~-~'~-'~-'-' *

.

' ~

~

.

.

.

~ ~I

~

~

'

~

,

~

,

t

,

,

,

~T ' ~

~ ! ! ' = ' ; i [ '

' - ~' - - - - - "

" ~

~ - T - -

i

' ' I

~ '

'

25

.E

2(3

e~ ¢/}

e-

--

15

5

10

15 Ceiling

Height

20

25

30

{ft)

Figure C-3-4.1(g) Heat Detector, Rate-of-Rise Listed Spacing: 50 ft (15.2 m) Slow Fire.

1990

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Edition

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-84

AUTOMATIC; FIRE DETECTORS

°I I

:

30

A

25

0. 09

20

= 1000 Btu/sec

C

15

750 10

500

5

250

100

5

10

15

20

25

Ceiling Height (ft)

Figure C-3-4.1(h) Heat Detector, Rate-of-Rise Listed Spacing: 50 ft (15.2 m) Medium Fire.

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

30

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX C

72E-85



35

30

25 .----!

20 CL 03

= 1000 Btu o------

i

'

I, .................

I..................

-O

'

'

I

100

E_-7'E ....................................

~ ~ ; - - ; - 4

-! ....... . . . . .

0

5

~- ........ :L_ . . . . .

l ................... -L ..........

, .................

- ....

10 Ceiling H e i g h t

Figure C-3-4.1(i)

~

i .............. I........ ; ........

15

I

'

, ..............

t. . . . . . . . . . .

~-,

~ ................. I ...............

l

i ................... --I . . - : Y . . . . . . . . . . . . . . . . .

20

25

--i 30

(ft)

Heat Detector, Rate-of-Rise Listed Spacing: 50 ft (15.2 m) Fast Fire.

1990

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Edition

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-86

AUTOMATIC FIRE DETECTORS

C-4 Analysis of Existing Heat Detection Systems.

ANALYSIS TABLES INDEX INSTALLED SPACING FEET

I C-4-1 Tables C-4-1(a)-(nn) can be used to d e t e r m i n e the size fire (heat release rate) which existing fixed t e m p e r a t u r e heat detection systems will r e s p o n d to. .

T h e use of the analysis tables is similar to that described for new designs. T h e difference is that the spacing of the existing detectors m u s t be known. An estimate of the fire intensity coefficient alpha or the fire growth time, t,r m u s t also be m a d e for the fuel that is expected to b u r n .

Example. Input:

Ceiling Height: 8 ft Detector Type: Fixed t e m p e r a t u r e 30 ft. U.L. listed spacing 135°F rated t e m p e r a t u r e Installed Spacing: 15 ft Fire Growth Rate: slow t~, = 600 sec (X = 0.003 Btu/sec 3) M i n i m u m A m b i e n t T e m p e r a t u r e = 55°F

Threshold Fire Size

(~):

1990 Edition

F r o m Table C-3-2.1.1 the detector time c o n s t a n t is 80 seconds AT = T s . - T o = 1 3 5 - 55 = 80°F F r o m Table C-4-1 (t) For D E T T C = 75 s e c - Qa = 418 For D E T T C = 1 0 0 s e c - Q , t = 472 ., By interpolation: O--,I = 418 - [(75-80) (418-472)/(75-100)] Q,t = 429 Btu/sec

.

.

.

.

.

.

.

.

.

.

.

.

.

TABLE (a) TABLE (b) TABLE (c) TABLE (d) TABLE (e)

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

8. 8 8 8 8

.

FIRE ALPHA GROWTH RATE SEC BTU/SEC3 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

50 I$0 300 500 600

0,400 0.044 0.011 0.004 0.003

TABLE ( f ) TABLE (g) TABLE (h) TABLE ( i ) TABLE ( j )

10 10 I0 10 I0

50 150 300 500 600

0.400 0.044 0.011 0.004 0.003

TABLE (k) TABLE ( I ) TABLE (m) TABLE (n) TABLE (o)

12 12 12 12 12

S0 150 300 500 600

0.400 0.044 0.011 0.004 0.003

TABLE ip) TABLE (q) TABLE (r) TABLE (s) TABLE ( t )

15 15 15 15 15

50 150 300 500 800

0.400 0.044 0.011 0.004 0.003

TABLE (u) TABLE(v) TABLE (w) TABLE (x) TABLE (y)

20 20 20 20 20

50 150 300 500 600

0.400 0.044 0.011 0.004 0.003

TABLE (z) TABLE (aa) TABLE (bb) TABLE (cc) TABLE (dd)

25 25 25 25 25

50 150 300 500 600

0.400 0.044 0.011 0.004 0.003

TABLE (ee) TABLE ( f f ) TABLE (gg) TABLE (hh) TABLE ( i i )

30 30 30 30 30

50 150 300 500 600

0.400 0.044 0.011 0.004 0.003

TABLE ( j j ) TABLE (kk) TABLE (11) TABLE (mm) TABLE (nn)

S0 50 50 50 50

S0 150 300 500 600

0.400 0.044 0.011 0.004 0.003

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX C

T a b l e C-4-1(a) I n s t a l l e d S p a c i n g o f H e a t D e t e c t o r : 8 feet F i r e G r o w t h R a t e : 50 S e c o n d s to 1000 B T U / S E C Alpha: 0.400 BTU/SEC'

72E-87

T a b l e C-4-1 (a) I n s t a l l e d S p a c i n g of H e a t D e t e c t o r : 8 feet F i r e G r o w t h R a t e : 50 S e c o n d s to 1000 B T U / S E C Alpha: 0.400 BTU/SEC s

.

CEILING HEIGHT IN FEEl TAU RTI AT ' 4.0

8.0

12.0

16.0

20,0

24.0

CEILING HEIGHT IN FEEl 28,0

TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

FIRE SIZE AT DETECTOR RESPONSE (BfU / SEC) 25 56 40 25 .56 60 25 56 80 25 56 100 25 56 120 25' 56 140 50 112 40 50 112 60 . 50 112 80 50 112 100 50 112 120 50 J12 140' 75 168 40 75 168 60 75 168 80 75"168 100 75 '168 120 75 168 140 100 224 '40 100,224 60 100 224 80 100 224 100' 100 224 120 100 224 140 125 280 40 125 280 60 125 280 80 125 280 100 125 280 120. 125 280 140 150 335 40 150 335 60 150 335 80 150 335 100 150 335"120 150 335 140 175 391 40 175 391 60 175 391 80 175 391 100 ,175 391 120 175 391 140 .200 447 40 200 447 60 200 447 80 200 447 100 200 447 120 .200'447 140 225 503 40 225 503 60 225 503 '80 225 503 100 225 503 120 225 503 140 250 559 40 250 559 60 250 559' 80 250 559 100 250 559,120 250 559 140 275 615 40 275 615 60 275 616 80 275.615 100

300 402 368 508 450 618 512 716 573 815 654 919 422 571 546 738 642 883 .754 1033 865 1179 928 1305 542 722 702 '932 813 1111 931 1289 1 0 1 6 1451 1 1 4 9 1629 625 841 802 1087 944 1305 1 0 5 0 1503 ,1222 1723 '1360 1925 729 967 912 1238 1 0 3 6 1472 1 2 3 3 1730 1398 '1968" 1561 2201 793 1066 979 1362 1 1 8 5 1656 1 3 7 8 1933 1568 2201 1 7 5 7 2462 882 1175 1 0 4 6 1483 1 3 0 1 1819 1 5 2 0 2127 1 7 3 4 2423 1 9 4 7 2712 925 1 2 5 7 1 1 6 8 1625 1415 1977 1 6 5 8 2313 1 8 9 7 2637 21.33 2952 968 1 3 3 7 1254 1747 1 5 2 7 2129 1 7 9 4 2494 2057 2845 2317' 3185 1 0 1 1 1417 1339 1866 1 6 3 7 2278 1 9 2 8 2669 2215 3046 2499 3412 1093 1513 1 4 2 4 1982 1746 2422 2 0 6 1 2840

535 687 838 985 1132 1282 755 976 1181 1383 1582 1773 908 1219 1472 1718 1955 2193 1101 1427 1728 2012 2298 2573 1208 1622 1959 2294 2614 2926 1340 1797 2186 2554 2911 3257 1468 1965 2397 2802 3193 3573 1586 2136 2599 3040 3464 3875 1754 2294 2794 .3268 3724 4166 1865 2447 2982 3489 3890 4356 1981 2596 3165 3618

668 877 1102 1308 1517 1730 926 1211 1484 1752 2018 2318 1137 1492 1824 2146 2464 2778 1332 1742 2128 2501 2867 3226 1501 1972 2409 2830 3240 3642 1664 .2187 2673 3138 3590 4033 1818 2391 2923 3431 3923 4405 1964 2587 3162 3711 4242 4761 2111 2774 3392 3980 4549 5104 2247 2955 3614 4241 4842 5431 2380 3131 3829 4488

832 1106 1381 1661 1949 2265 1136 1496 1846 2194 2542 2895 1389 1826 2245 2656 3063 3470 1614 2122 2604 3074 3537 3995 1820 2394 2936 3461 3976 4484 2013 2649 3247 3825 4389 4944 2195 2890 3542 4170 4782 5382 2369 3121 3825 4501 5158 5802 2537 3342 4096 4819 5520 6206 2698 3556 4358 5126 5870 6597 2854 3763 4612 5424

1016 1365 1722 2090 2473 2870 1366 1811 2251 2692 3138 3592 1659 2193 2710 3221 3733 4247 1920 2535 3125 3703 4276 4849 2160 2850 3508 4150 4782 5411 2384 3145 3868 4570 5259 5942 2595 3425 4210 4970 5713 6447 2797 3692 4537 5352 6148 6932 2991 3949 4851 5720 6567 7400 3177 4197 5155 6076 6972 7852 3358 4437 5449 6421

1219 1657 21t0 2585 3082 3601 1614 2157 2699 3248 3810 4386 1948 2589 3217 3844 4475 5115 2246 "2978 3687 4388 5088 5791 2519 3337 4123 4895 5661 6426 2775 3674 4533 5373 620~ 7027 3016 3993 4923 5827 6718 7601 3247 4298 5295 6262 7212 8152 3468 4590 5653 6681 7689 8683 3681 4873 5999 7087 8150 9197 3887 5147 6334 7479

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

28.0 .

.

.

.

.

.

.

FIRE SIZE AT DETECTOR RESPONSE (8TU / SEC) 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

NOTE:

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

2371 2679 1151 1507 1853 2192 2526 2859 1208 1589 1959 2322 2680 3038 1265 1671 2064 2451 2834 3218 1321 1751 2169 2579 2987 3303 1377 1831 2272 2707 3141 3456

3242 3633 1595 2096 2563 3007 3434 3849 1677 2207 2701 3171 3623 4061 1756 2315 2836 3331 3808 4270 1835 2422 2969 3489 3990 4445 1912 2527 3100 3645 4169 4640

4128 4622 2089 2740 3259 3820 4359 4881 2194 2804 3428 4018 4585 5133 ,2297 2937 3592 4211 4805 5380 2398 3069 3753 4401 5021 5620 2423 3197 3911 4586 5233 5857

5129 5753 2508 3301 4032 4734 5409 6066 2633 3461 4236 ,4973 5682 6371 2754 3623 4435 5207 5949 6669 2874 3782 4630 5436 6210 6961 2982 3937 4821 5660 6466 7247

6209 7365 8597 6977 8291 9697 3005 3533 4087 3964 4670 5413 4859 5735 6661 5714 6756 7862 6540 7748 9033 7346 8718 10183 3152 3704 4282 4160 4898 5672 5100 6014 6978 5996 7 0 8 4 8234 6862 8121 9457 7706 9135 10657 3296 3871 4472 4352 5119 5925 5335 6287 7289 6272 7403 8599 7 1 7 7 8485 9872 8058 9542 11121 3437 4034 4658 4539 5336 6172 5565 6553 7592 6543 7716 8955 7486 8842 10279 8403 9941 11575 3574 4193 4840 4723 5549 6415 5791 6814 7890 6807 8023 9304 7788 9192 10677 8741 10332 12020

D e t e c t o r t i m e c o n s t a n t at a reference velocity of 5 ft/sec.

F o r SI Units:

I ft = 0 . 3 0 5 m 1000 B T U / s e c = 1055 k W

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-88

AUTOMATIC FIRE DETECTORS

T a b l e C-4-1(b) Installed Spacing of Heat Detector: 8 feet Fire Growth Rate: 150 Seconds to 1000 B T U / S E C Alpha: 0.044 B T U / S E C s

T a b l e C,-4-1(b) Ins t a l l e d Spacing of Heat Detector: 8 feet Fire Growth Rate: 150 Seconds to 1000 B T U / S E C Alpha: 0.044 B T U / S E C ~

CEILING HEIGHT IN FEET TAU Rll AT .

.

.

.

.

.

.

.

.

.

.

.

4,0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20,0 .

.

.

.

.

.

CEILING HEIGHT IN FEET

24,0 .

.

.

.

.

.

.

28.0 .

.

.

.

.

.

TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

4.0 .

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 ,56 25 56 25 56 25 56 25 56 25 56 50 112 50 112 50 112 50 112 50 112 50 112 75 168 75 168 75 168 75 168 75 168 75 168 100, 224 100 224 100 224 100 224 100 224 100 224 125 280 125 280 125 280 125 280 125.280 125 280 150,335 150 335 150 335 150 335 150 335 150 335 175 391 175 391 175 391 175 391 175 391 175 391 200 447 200 447 200 447 200 447 200 447 200 447 225 503 225 503 225 503 225 503 225 503 225 503 250 559 250 559 250 559 250 559 250 559 250 559 275 615 275 615 275 615 275 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140. 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

118 154 194 228 263 299 171 224 281 329 377 424 216 283 352 413 472 531 255 343 416 488 559 636 291 391 476 558 647 723 325 435 531 634 720 805 357 478 584 694 790 892 396 519 646 752 870 959 425 558 693 809 926 1026 453 596 738 876 982 1107 480 646 783 921

167 226 286 346 409 473 237 317 397 474 552 630 296 395 492 585 678 770 349 467 578 685 792 898 397 532 657 779 899 .1017 443 593 732 869 999 1128 486 650 803 952 1094 1236 530 705 873 1031 1188 1337 570 759 939 1108 1274 1434 608 810 1002 1185 1358 1531 645 863 1063 1256

232 322 415 512 614 721 320 435 550 666 785 906 395 533 668 803 939 1076 462 622 776 929 1081 1234 523 704 877 1046 1214 1382 581 '781 971 1157 1340 1522 637 854 1061 1262 1460 1656 676 924 1148 1363 1576 1785 726 992 1231 1461 1686 1909 774 1041 1311 1556 1794 2029 820 1103 1389 1647

311 440 579 726 883 1049 410 574 735 901 1074 1254 498 683 876 1063 1255 1451 577 788 996 1214 1424 1637 650 885 1114 1342 1571 1813 719 976 1226 1473 1719 1967 784 1063 1332 1598 1861 2125 846 1146 1435 1718 1998 2277 906 1227 1533 1833 2130 2425 964 1304 1629 1946 2258 2567 1021 1379 1722 2054

400 584 781 993 1221 1462 517 728 949 1185 1428 1683 620 861 1107 1360 1622 1901 713 983 1254 1530 1811 2101 799 1097 1392 1690 1992 2300 880 1204 1523 1842 2164 2491 957 1307 1649 1989 2330 2675 1031 1405 1769 2129 2490 2852 1102 1500 1885 2265 2645 3025 1170 1591 1997 2397 2795 3192 1237 1680 2107 2525

507 752 1026 1319 1633 1969 638 913 1205 1516 1846 2202 756 1063 1381 1714 2063 2427 863 1202 1548 1904 2273 2656 962 1333 1705 2086 2476 2878 1056 1456 1855 2259 2671 3093 1145 1574 1999 2427 2860 3301 1230 1687 2138 2588 3042 3503 1312 1797 2271 2744 3220 3700 1392 1902 2401 2896 3392 3891 1469 2005 2527 3043

631 952 1309 1699 2118 2573 775 1126 1504 1912 2347 2808 906 1291 1696 2125 2578 3055 1027 1446 1880 2333 2806 3301 1140 1593 2056 2534 3029 3543 1246. 1733 , 2224 2728 3245 3780 1347 1866 2386 2915 3456 4011 1444 1995 2543 3096 3660 4236 1538 2119 2694 3272 3859 4456 1628 2239 2841 3444 4053 4671 1716 2355 2984 3611

.

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

.

28.0 .

.

.

.

.

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

1'20 140 40 60 80 100 120 140 40 60 80 100 120 140 4060 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

103§ 1177 507 680 827 967 1109 1246 533 714 881 1014 1169 1314 559 747 917 1072 1228 1380 584 780 953 1122 1286 1446 609 813 989 1171 1343 1511

1440 1624 681 911 1123 1325 1523 1715 717 959 1184 1393 1601 1803 751 1005 1239 1462 1679 1890 785 1050 1294 1528 1754 1975 818 1094 1348 1593 1829 2058

18§8 2146 "865 1163 1445 1736 2000 2260 909 1222 1517 1823 2100 2371 952 1:280 1589 1885 2197 2480 994 1336 1658 1967 2292 2587 1036 1392 1726 2048 2359 2692

2382 2706 1075 1452 1811 216t 2503 2842 1129 ]524 1899 2264 2622 2974 1181 1594 1986 2365 2737 3104 1232 1662 2070 2464 2851 3231 1282 1729 21'53 2562 2962 3356

2941 3355 1301 1766 2213 2650 3083 3514 1365 1851 2317 2772 3222 3670 1426 1933 2418 2892 3359 3822 1486 2014 2518 3009 3492 3971 1545 2093 2615 3123 3623 4118

3560 4242 4078 4881 1 5 4 3 1801 2105 2469 2650 3123 3187 3774 3723 4427 4261 5087 1 6 1 6 1884 2203 2580 2770 3259 3328 3933 3884 "4608 4440 5288 1 6 8 8 1965 2298 2688 2887 3392 3466 4089 4041 4786 4615 5486 1757 2045 2391 2795 3002 3523 3601 "4242 4195 4960 4787 5681 1826 2122 2483 2899 3114 3651 3733 4393 4346 5132" 4956 5872

NOTE: Detector time constant at a reference vel6city of 5 ft/sec. F o r S l Units: 1 ft = 0 . 3 0 5 m 1000 BTU/sec = 1055 kW

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX C

72E-89

T a b l e C-4-1(c) I n s t a l l e d S p a c i n g of H e a t D e t e c t o r : 8 feet F i r e - G r o w t h R a t e : " 3 0 0 S e c o n d s to 1000 B T U / S E C Alpha: 0.011'BTU/SEC'

CEILING'HEIGHT TAU RTI &T ---~

.....

4.0

~7 ........

8.0

12.0-'16'.0

T a b l e C-4-1 (c) I n s t a l l e d S p a c i n g o f Heat Detector: 8 feet F i r e G r o w t h R a t e : 300 S e c o n d s to 1000 B T U / S E C A l p h a : 0.011 B T U / S E C s

CEILING HEIGHT IN FEET

IN FEET 20.0

24.0

28.0

TAU RTI &T

40 60 80 100 120 140 ~0 60 80 100 120 140 40 60 80 100' 120 1'40 .i0 60 '80 100 120 140 40

60

80 100 120 1~0 '40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

8.0

12.0

16.0

20.0

24.0

28.0

FIRE SIZE AT DETECTOR RESPONSE (8TU / SEC

FIRE SIZEAT DETECTOR RESPONSE (BTU / SEC) 2556 25 56 2556 25"56 25 56 25 56 50 112 50 112 50 112 50 112 50 112 50 112 75 168 75'168 75 168 75 168 75 168 75 168 100 224 100 224 100 224 100 224 100 224 100 224 125 280 125 280 125 280 125 280 125 280 125:280 150 335 150 335 150 335 150 335 150 335 150 335 175 391 175 391 175 391 175 391 175 391 175 391 200 447 200 447 200 447 200 447 200 447 200 447 225 503 225 503 225 503 225 503 225 503 225 503 250 559 250 559 250 559 250 559 250 559 25O 559 275 615 275 615 275 615 275 615

4.0

~ ....................................

70 95 122 148 174 201 101 136 172 205 ~39 273 127 170 215 255 296 356 150 201 253 "300 347 393 171 230 289 342 395 447 192 261 322 381 440 497 211 287 353 419 482 545 229 311 384 454 523 596 247 335 413 489 569 639 264 357 441 522 607 682 280 380 469 555

104 149 196 246 299 35i 144 200 257 315 374 437 178 245 311 378 445 514 209 286 361 436 511 587 237 323 408 490 573 656 264 360 451 542 631 721 289 394 493 591 687 784 314 426 533 638 741 844 337 458 572 684 794 ~02 360 488 610 728 844 959 382 518 646 771

152 223 302 387 479 576 200 284 372 465 563 666 242 339 438 540 646 756 281 390 500 611 725 843 317 43T 557 678 801 926 350 482 612 742 873 1006 383 525 664 803 943 1083 413 566 715 862 1010 1158 443 606 763 919 1075 1230 471 644 811 975 1138 1301 499 681 856 1028

211 321 442 575 719 873 267 389 520 661 811 970 318 453 595 745 903 1069 361 514 667 827 993 1167 403 567 736 906 1081 1262 443 619 801 981 1166 1356 481 670 859 1055 1248 1447 518 719 918 1119 1328 1535 553 766 976 1186 1406 1621 587 811 1032 1252 1474 1705 620 856 1086 1316

285 443 620 815 1027 1253 345 517 703 906 1124 1356 402 586 786 998 1223 1461 455 654 864 1088 1322 1568 504 719 941 1173 1420 1674 551 780 1015 1258 1511 1778 596 839 1087 1341 1603 1875 639 896 1156 1421 1694 1974 680 951 1223 1499 1782 2072 720 1005 1289 1576 1868 2167 759 1057 1352 1650

374 592 838 1110 1405 1721 439 668 926 1206 1508 1830 502 746 1012 1303 1612 1942 561 821 1099 1397 1714 2055 618 893 1184 1493 1819 2163 671 963 1267 1587 1923 2276 723 1030 1348 1679 2025 2387 772 1095 1427 1770 2126 2497 820 1158 1503 1858 2225 2605 866 1220 1578 1945 2322 .2712 911 1280 1651 2029

477 767 1099 1463 1858 2283 547 849 1187 1560 1963 2399 616 931 1280 1661 2072 2510 682 1013 1374 1764 2183 2628 745 1093 1466 1867 2294 2748 805 1170 1557 1969 2406 2867 863 1245 1646 2070 2517 2987 919 1318 1733 2169 2626 3106 973 1389 1819 2267 2735 3224 1025 1458 1902 2363 2842 3341 1076 1525 1984 2457

275 275 300 300 300 300 300 300 325 325 325 325 325 .325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

NOTE:

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

643 723 297 401 496 593 679 763 317 422 522 623 713 802 332 443 548 653 747 841 347 463 573 682 781 885 362 483 604 710 814 919

893 1014 403 546 682 813 941 1067 425 574 716 854 988 1119 445 602 750 894 1033 1171 465 629 783 933 1078 1221 485 655 817 971 1122 1270

1199 1369 520 717 90t 1081 1259 1436 546 753 945 1132 1317 1502 571 787 987 1182 1375 1566 596 821 1029 1232 1431 1629 620 846 1070 1280 1486 1690

1546 1779 652 899 1140 1378 1617 1858 684 941 1192 1439 1687 1936 714 982 1242 1499 1755 2012 744 1023 1292 1558 1822 2086 774 1062 134t 1615 1888 2t60

1953 2261 797 1108 1415 1723 2035 2352 834 1157 1476 1795 2116 2442 871 1206 1535 1865 2196 2531 906 1253 1594 1933 2274 2618 941 1300 1651 2001 2351 2704

2418 2817 955 1338 1722 2113 2512 2921 998 1395 1792 2194 2604 3023 1040 1451 1861 2274 2694 3123 1081 1506 1928 2353 2784 3222 1121 1560 1994 2430 2872 3320

2948 3456 1126 1591 2064 2550 3052 3571 1174 1656 2143 2641 3155 3684 1222 1719 2220 2731 3256 3795 1269 1781 2296 2820 3356 3906 1314 1842 2371 2907 3454 4015

Detector time c o n s t a n t at a reference velocity of 5 ft/sec.

For SI Units:

I ft = 0.~'08 m 1000 B T U / s e e = 1055 k W

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-90

A U T O M A T I C FIRE DETECI'ORS

T a b l e C - 4 - I (d) I n s t a l l e d Spacing of Heat Detector:

T a b l e C-4-1(d) I n s t a l l e d S p a c i n g of H e a t D e t e c t o r : 8 feet F i r e G r o w t h R a t e : 500 S e c o n d s to 1000 B T U / S E C Alpha: 0.004 BTU/SEC s

8 feet Fire Growth Rate: 500 Seconds ¢o 1000 B T U / S E C Alpha: 0.004 B T U / S E C s

CEILING HEIGHT IN FEET.

CEILING HEIGHT IN FEET TAU RTI &T .

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

8.0 .

.

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

TAU RTI &T

28.0 .

.

.

.

.

.

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

1990 Edition

49 78 70 11"6 91 1'58 113 203 136 252 160 304 70 104 96 149 124 196 150 246 178 298 206 353 87 126 120 ' 178 152 231 184 286 215 343 247 402 103 147 141 205 179 264 214 324 250 386 286 449 118 166 160 231 203 295 243 360 282 427 322 494 131 184 179 255 226 325 270 395 313 466 356 537 144 201 196 278 247 353 295 428 342 503 389 579 157 217 213 300 268 380 320 460 370 539 421 620 169 233 232 321 288 406 343 490 397 574 451 659 181 249 247 342 307 432 366 520 424 609 480 697 192 264 263 362 326 456 388 549

118 183 256 336 422 515 148 220 297 381 471 567 176 255 338 427 521 621 201 288 378 472 571 674 225 319 415 515 619 727 248 349 452 557 666 778 269 378 487 597 711 828 290 405 520 637 755 877 310 432 553 675 799 925 329 458 584 712 841 971 348 483 615 748

171 272 386 513 651 799 204 312 431 562 703 855 236 351 476 612 757 912 266 389 521 661 811 970 295 426 564 711 865 1028 320 462 607 759 918 1085 345 496 648 806 971 t142 370 526 688 852 1022 1199 394 558 727 897 1073 1254 417 588 765 941 1122 1309 439 618 798 984

237 385 553 740 944 1163 273 427 601 792 1000 1222 309 470 649 845 1057 1283 341 512 698 898 1114 1345 374 552 746 952 1173 1407 404 592 793 1005 1231 1469 434 631 837 1058 1289 1532 463 668 882 1107 1346 1594 491 705 926 1158 1403 1656 518 740 970 1208 1455 1717 544 775 1012 1257

318 523 759 1020 1306 1613 355 568 809 1075 1365 1676 393 612 860 1131 1425 1740 430 658 912 1188 1486 1805 466 702 961 1245 1548 1871 501 747 1013 1300 1610 1937 535 790 1063 1356 1669 2004 568 832 1113 1413 1731 2067 599 873 1162 1469 1792 2134 630 914 1211 1524 1853 2200 660 953 1258 1578

8.0

12.0

16.0

20.0

24.0

28.0

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 25O 250 250 275 275 275 275

4.0

.

413 689 1005 1357 1741 2154 453 735 1058 1415 1803 2221 493 782 1109 1471 1867 2289 533 830 1163 1530 1928 2354 573 878 1218 '1590 1993 2423 611 926 1273 1650 2058 2492 649 973 1327 1711 2123 2562 685 1020 1381 1771 2189 2633 721 1065 1435 1832 2254 2703 756 1110 1488 1892 2320 2774 789 1154 1541 1951

275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

NOTE:

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40. 60 80 100 120 140

449 509 203 277 345 410 474 541 214 292 362 431 498 568 224 306 380 452 522 594 235 320 397 472 545 619 245 333 414 492 572 645

642 734 278 381 481 578 674 770 292 400 504 606 706 806 306 419 527 633 737 841 320 437 550 659 767 875 333 455 572 685 798 908

882 1017 366 507 645 783 922 1062 384 531 675 818 961 1106 401 555 704 852 1000 1149 419 577 732 885 1038 1191 435 600 760 918 1075 1233

1171 1362 461 647 834 1026 1219 1415 482 676 869 1063 1266 1467 503 704 903 1104 1312 1518 523 731 937 1143 1357 1569 543 758 970 1182 1396 1619

1510 1773 569 809 1053 1305 1564 1833 594 843 1094 1352 1617 1892 619 875 1134 1398 1670 1949 643 907 1173 1444 1722 2007 666 939 1212 1489 1773 2063

1914 2266 690 992 1305 1632 1974 2331 719 1030 1351 1685 2033 2396 747 1068 1397, 1738 2092 2460 774 1104 1442 1790 2150 2524 801' 1141 1486 1841 2208 2588

2386 2844 823 1198 1593 2010 2451 2915 855 1240 1644 2069 2516 2985 887 1282 . 1694 .2126 2580 3055 918 1324 1744 2184 2644 3125 949 1364 1794 .2241 2707 3194

D e t e c t o r t i m e c o n s t a n t at a r e f e r e n c e velocity of 5 hlsec,

F o r S l Units:

l h = 0.305 m 1000 B T U / s e c = 1055 k W

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX C

72E-91

T a b l e C-4-I (e) I n s t a l l e d S p a c i n g of H e a t Detector: 8 feet Fire G r o w t h Rate: 600 Seconds to 1000 B T U / S E C A l p h a : 0.003 B T U / S E C j

T a b l e C-4-1(e) I n s t a l l e d S p a c i n g of H e a t Detector: 8 feet F i r e G r o w t h Rate: 600 Seconds to 1000 B T U / S E C A l p h a : 0.003 B T U / S E C '

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

TAU RTI AT

28.0 .

.

.

.

.

.

.

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60. 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

44 71 63 108 83 148 104 192 126 240 149 291 62 93 86 135 111 180 136 228 161 279 188 332 77 112 106 160 136 210 165 262 194 316 224 373 91 130 124 184 158 238 191 295 224 353 257 413 103 147 141 206 180 265 216 326 252 388 289 451 115 162 158 227 200 291 239 355 279 421 318 488 127 177 173 247 218 315 261 384 304 . 454 347 524 138 192 187 266 237 339 283 412 329 485 374 559 148 205 202 284 254 362 303 438 352 515 401 593 158 219 215 302 271 384 323 464 375 545 426 626 168 232 231 320 287 405 343 490

110 173 244 323 408 499 135 203 278 360 448 542 158 233 312 398 489 586 180 261 346 436 531 631 201 288 378 472 571 675 220 313 409 508 611 718 239 338 439 543 650 761 257 362 468 576 688 802 274 385 496 609 725 843 291 407 524 641 761. 884 307 429 550 673

160 259 372 497 633 780 188 292 409 537 676 826 215 325 446 578 720 872 241 357 483 619 765 920 265 388 520 660 810 968 '288 419 556 701 854 1016 309 448 591 741 898 1064 330 476 625 780 942 1111 351 504 658 818 985 1158 371 528 691 856 1027 1204 390 554 723 893

225 370 536 721 922 1139 254 404 575 763 968 1188 284 440 614 807 1015 1238 312 475 654 851 1062 1288 339 510 695 895 1110 1340 366 542 734 939 1158 1391 391 575 774 983 1206 1443 416 607 810 1027 1255 1495 440 639 848 1070 1302 1546 463 670 885 1110 1350 1598 486 700 921 1152

303 505 738 997 1279 1584 334 542 779 1042 1328 1636 365 579 821 1088 1378 1689 396 616 863 1134 1428 1742 427 653 905 t181 1478 1796 456 690 947 1229 1530 1851 485 727 989 1274 1581 1906 513 763 1031 1321 1630 1961 541 798 1073 1368 1681 2013 567 832 1114 1414 1732 2069 593 866 1155 1460

8.0

12.0

16.0' 20.0

24.0

28.0

FIRE SIZE AT DETECTOR RESPONSE (8fU / SEC)

FIRE. SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

4.0

.

397 668 980 1328 1709 2119' 429 705 1024 1376 1761 2175 462 744 1066 1425 1813 2231 495 784 1110 1471 1866 2287 528 824 1155 1520 1916 2341 561 863 1200 1570 1970 2398 593 903 1246 1620 2024 2456 624 942 1291 1670 2078 2513 654 981 1336 1720 2132 2572 684 1019 1380 1770 2187 2630 713 1056 1425 1820

275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80. 100 120 140 40 60 80 100 120 140 40 60 80 100 i20 140

397 451 178 244 303 362 419 475 187 256 319 380 440 499 196 269 334 398 461 523 205 281 349 416 481 549 214 292 364 433 501 571

574 658 244 337 426 514 602 690 257 353 447 538 630 721 269 370 467 562 65Z ' 751 281 386 486 585 683 781 292 401 506 608 709 810

797 923 323 451 577 703 831 962 339 471 602 733 865 999 354 492 627 763 899 1037 369 512 652 792 932 1073 383 531 676 820 964 1110

1069 1250 409 579 754 930 1110 1295 428 604 782 965 1150 1340 446 628 811 1000 1190 1384 464 652 841 1035 1229 1427 481 675 869 1065 t268 1470

1397 1649 508 729 957 1193 1440 1699 530 758 992 1234 1485 1746 551 786 1026 1274 1530 1796 572 8t4 1060 1313 1574 1844 592 841 1094 1352 1618 1893

1783 2241 2123 2689 619 742 900 1093 1 1 9 5 1469 1 5 0 6 1869 1 8 3 4 2296 2178 2747 644 770 933 1130 1234 .1512 1551 1919 1884 2350 2233 2806 668 797 965 1166 1273 1555 1596 1968 1 9 3 4 2404 2287 2864 692 824 997 1201 1312 1598 1640 2016 1983 2458 2341 2922 715 851 1 0 2 8 1236 1350 1640 1684 2065 2032 2511 2395 2981

N O T E : Detector time constant at a reference velocity of 5 ft/sec. For SI Units:

1 ft = 0.305 m 1000 B T U / s e c = 1055 k W

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-92

A U T O M A T I C FIRE DETECTORS

T a b l e C-4,l(f) Installed Spacing of Heat Detector: 10 feet Fire Growth Rate: 50 Seconds to 1 0 0 0 , B T U / S E C Alpha: 0.400 B T U / S E C ~

Table C-4-l(fi Installed Spacing of Heat Detector: 10 feet Fire Growth Rate: 50 Seconds to 1000 B T U / S E C Alpha: 0.400 B T U / S E C 3 '

CEILING HEIGHT IN FEET

:CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

24.0 .

.

IAU RTI ~T

28.0 .

.

.

.

.

.

.

.

.

.

.

.

.

.

56 40 56 60 56 80 56 100 56 120 56 140 112" 40 112 60 112 80 112 100 112 120 112 140 168 ~0 168 60 .168 80 168 100 168 120 168 140 224 40 224 60 224 80 224 100 224 120 224 140 280 40 280 60 280 80 280 100 280 120 280 140 335 40 335 60 335 80 335 100 335 120 335 140 391 40 391 60 391 80 391 100 391 120 391 140 447 40 447 60 447 80 447 100 447 120 447 140 503 40 503 60 503 80 503 100 503 120 503 140 559 40 559 60 559 80 559 100 559 120 559 140 615 40 615 60 615 80 615 100

376 499 623 486 641 811 570 769 1013 675 902 1193 751 1 0 2 4 1371 827 1 1 4 6 1551 552 692 904 .712 895 1171 828 1 1 0 6 1391 945 .1282 1633 1 0 3 5 1 4 4 6 1905 1 1 7 7 1 6 2 6 2143 673 890 1088 885 1 1 5 7 141.8 1 0 0 0 1370 1725 1 1 7 4 1 6 0 2 2024 1330 1 8 2 2 2315 1484 2037 2602 • 801 1051 1 2 7 6 985 1 3 3 7 1662 1195 1 6 2 3 2 0 2 6 1389 1893 2375 1581 2155 2714. 1771 2411 3046 908 1193 1 4 4 7 1130 1528 1 8 8 9 1 3 6 4 1853 2303 1595 2164 2699 1822 2466 3083 2046 2759 3458 971 1308 1 6 0 5 1 2 5 7 1702 2101 1528 2070 2564 1794 2421 3004 2055 2760 3430 2314 3089 3845 1035 1419 1 7 5 5 1381 1 8 6 9 2303 1688 2277 2811 1988 2666 3294 2284 3042 3760 2577 3406 4214 1151 1552 '1902 1503 2030 2495 1844 2477 3047 2179 2903 3571 2509 3313 4076 2837 3712 4567 1234 1667 2041 1622 2186 2681 1998 2671 3274 2367 3132 3838 2731 3577 4380 3096 3911 4902 1317 1778 2175 1740 2337 2860 2150 2859 3494 2553 3355 4096 2953 3739 4669 3267 4270 5234 1398 1886 2305 1855 2484 3033 2300 3042 3707 2737 3485 4340

779 1027 1271 1517 1766 2040 1084 1418 1738 2055 2371 2685 1331 1744 2136 2518 2893 3264 1554 2037 2494 2934 3365 3790 1759 2307 2823 3319 3803 4277 1949 2560 3132 3681 4214 4737 2130 2800 3426 4025 4606 5173 2302 3029 3706 4353 4980 5591 2468 3249 3976 4670 5340 5994 2628 3461 4237 4976 5689 6384 2783 3667 4489 5272

956 1273 1591 1916 2249 2593 1306 1723 2129 2531 2936 3343 1598 2104 2590 3066 3538 4010 1858 2446 3005 3550 4086 4618 2097 2761 3389 3997 4594 5183' 2320 3055 3749 4418 5072 5716 2531 3335 4091 4818 5527 6223 2732 3601 4417 5201 5962 6709 2925 3858 4731 5569 6382 7178 3111 4105 5035 5925 6787 7631 3291 4345 5329 6270

1 1 5 2 1366 1550 1860 1957 2371 2377 2906 2814 3465 3268 4050 1 5 5 0 1813 2059 2426 2561 3038 3064 3658 3575 4292 4094 4942 1885 2191 2495 2916 3086 3625 3670 4333 4255 5047 4843 5769 2183 2528 . 2885 3356 3560 4158 . 4221 4951 4877 5742 5532 6537 2457 2837 3246 3763 3998 4652 4732 5525 5456 6392 6175 7257 2713 3127 3583 4144 4410 5117 5213 6067 6002. 7006 6782 7939 2954 3400 3903 4505 4801 5558 5670 6582 6521 7591 7361 8590 3185 3661 4209. 4851 5175 5980 6108 7076 7019 8151 7917 9215 3406 3911 4503 5183 5535 6386 6529 7551 7499 8692 8452 9818 3620 4152 4786 5503 5882 6778 6936 8011 7963 9215 8970 10402 3826 4386 5061 5813 6219 7159 7331 8456

4.0 .

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

24,0 ' 2 8 . 0 " .

.

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

.

275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 3175 3975 140 3488 4440 40 1 4 7 8 1992 60 1970 2628 80 2448 3221 100 2922 3687 120 3301 4199 140 3705 4696 40 1557 2096 60 2084 2769 80 2596 3397 100 3106 3883 120 3 4 8 9 4 4 2 1 140 3919 4945' 40 1 6 3 5 2198 60 2196 2908 80 2744 3476 100 3291 4076 120 3675 4639 140 4130 5189 40 1 7 1 3 2298 60 2308 3044 80 2891 3636 100 .3366 4257 120 3858 4853 140 4339 5428 40 "'1790 2396 60 2419 3178 80 3 0 3 8 3 7 9 3 100 3522 4440 120 4040. 5062 140 4546 5662

4954 5548 2432 3202 3915 4584 5231 5858 2555 3367 4117 4821 5501 6160 2676 3528 4308 5052 5765 6456 .2794 3685 4501 5279 6024 6745 2909 3840 4691 5501 6278 7029

6027 7181 8413 9723 6761 8070 9472 10968 2933 3467 4027 4613 3867 4578 5328 6115 4735 5615 6547 7529 5560" 6605 7716 8890 6356 7563 8850 10217 7129 8498 9962 11520 3079"3637 4222 4834 4063 4805 5588 6409 4975 5894 6866 7889 5 8 4 2 6933 8090 9313 6677 7937 9278 10699 7488 8915 10439 12059 3222 3804 4413 5049 4253 5027 5842 6696 5209 6166 7178- 8241 6117 7253 8456 9726 6991 8302 9695 11170 . 7839 9323 10905 12585 3362 3966 4600 5260 4440 52~4 6090 6976 .5438 6433 7483 8586 6386 7566 8814 10130 7298 8659 10104 11631 8183 9723 11362 13100 3499 4126 4782 5466 4 6 2 2 5457 6334 7251 5 6 6 2 6694 7782 8923 6649 7 8 7 2 9165 10527 7599 "9009 10504 12083 8519 10115 11810 13606

N O T E : Detector time constant at a reference velocity of 5 ft/sec. F o r S ! Units:

1 ft = 0.305 m 1000 B T U / s e c = 1055 k W

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENI)IX C

72E-93

Table C-4-1(~ I n s t a l l e d S p a c i n g of H e a t Detector: 10 feet F i r e G r o w t h R a t e : 150 Seconds to 1000 B T U / S E C A l p h a : 0.044 B T U / S E C s

T a b l e C-4-1(g) I n s t a l l e d S p a c i n g of H e a t D e ~ c t o r : 10 ~ e t Fire G r o w t h Rate: 150 Seconds to 1000 B T U / S E C A l p h a : 0.044 B T U / S E C s

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

TAU RTI AT

28,0 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

56 56 56 56 56 56 112 t12 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

152 205 252 298 345 392 221 297 362 426 490 561 277 372 454 535 622 697 328 439 537 641 730 819 383 501 625 729 831 935 426 559 694 812 930 1034 467 628 760 899 1013 1146 506 678 825 966 1109 1247 544 727 895 1034 1195 1345 580 775 948 1116 1279 1440 616 822 1001 1187

209 284 358 435 514 595 296 398 496 593 691 791 369 495 614 731 848 963 435 582 720 857 990 1121 487 662 822 973 1121 1268 543 738 914 1081 1246 1406 595 798 1002 1186 1362 1540 646 866 1086 1284 1477 1667 694 931 1170 1378 1587 1790 742 994 1246 1473 1694 1909 787 1055 1322 1564

280 362 389 519 502 683 621 858 746 1044 877 1241 380 481 525 669 664 860 805 1 0 6 4 950 1 2 6 9 1098 1482 467 584 635 803 807 1 0 2 2 971 1 2 4 5 1 1 3 5 1472 1302 1 7 1 3 545 677 738 926 926 1171 1 1 2 2 1418 1 3 0 7 1667 1 4 9 2 1920 617 763 835 1040 1044 1310 1 2 4 9 1580 1 4 6 7 1850 1670 2123 685 844 925 1 1 4 7 1155 1442 1 3 8 0 1733 1602 2025 1839 2317 750 920 1011 1249 1261 1 5 6 7 1 5 0 4 1880 1744 2192 1981 2503 811 ' 994 1093 1 3 4 7 1362 1687 1623 2021 1880 2352 2133 2682 871 1 0 6 4 1173 1441 1460 1 8 0 3 1738 2157 2011 2507 2280 2856 928 1 1 3 2 1250 1 5 3 2 1555 1 9 1 5 1849 2289 2138 2658 2422 3024 984 1 1 9 8 1 3 2 4 1621 1 6 4 7 2024 1958 2417

461 671 904 1151 1416 1696 596 841 1097 1366 1649 1952 715 995 1280 1574 1879 2194 823 1136 1450 1770 2098 2434 923 1268 1611 1956 2307 2665 1017 1392 1762 2133 2507 2886 1106 1511 1907 2302 2699 3099 1191 1625 2047 2465 2884 3305 1273 1734 2181 2623 3063 3504 1352 1840 2311 2775 3237 3698 1429 1943 2438 2924

,576 856 1164 1504 1864 2247 727 1040 1374 1730 2107 2506 861 1212 1576 1957 2355 2772 983 1371 1766 2174 2596 3034 1097 1520 1947 2382 2828 3288 1204 1662 2119 2581 3052 3535 1306 1797 2283 2772 3268 3773 1403 1927 2442 2957 3478 4005 1497 2052 2595 3136 3680 4230 1588 2173 2743 3310 3878 4450 1676 2290 2888 3479

709 1071 1473 1912 2385 2890 872 1268 1695 2154 2645 3166 1021 1456 1913 2397 2908 3446 1158 1632 2122 2633 3168 3726 1286 1799 2322 2862 3421 4002 1406 1957 2513 3082 3667 4271 1521 2108 2697 3295 3906 4534 1631 2254 2874 3501 4138 4790 1737 2395 3046 3701 4364 5040 1840 2531 3212 3895 4585 5284 1939 2663 3375 4085

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

28.0 .

.

.

.

.

.

.

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

4.0 .

275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

1362 1534 663 880 1065 1256 1443 1625 695 918 1123 1325 1522 171,6 727 957 1179 1392 1600 1805 758 996 1234 1459 1678 1894 789 1035 1289 1524 1754 1982

1797 2025 832 1115 1398 1652 1898 2138 875 1172 1471 1738 1996 2249 918 1229 1542 1822 2093 2330 959 1304 1589 1880 2161 2434 1000 1359 1657 1959 2251 2536

2261 2560 1038 1397 1736 2063 2382 2695 1091 1467 1823 2166 2499 2827 1142 1537 1909 2266 2614 2955 1193 1605 1992 2364 2726 3081 1242 1671 2074 2461 2837 3205

2804 3187 1263 1707 2130 2542 2946 3346 1325 1791 2234 2664 3085 3502 1387 1873 2335 2783 3222 3655 1447 1954 2434 2900 3355 3804 1505 2032 2532 3014 3486 3951

3406 3887 1504 2043 2561 3069 3571 4071 1577 2141 2681 3210 3732 4252 1648 2236 2799 3348 3890 4428 1718 2330 2914 3484 4045 4601 1787 2422 3027 3617 4197 4771

4070 4664 1762 2405 3028 3644 4258 4873 1845 2516 3166 3805 4441 5078 1927 2626 3300 3963 4621 5279 2007 2733 3432 4118 4798 5476 2085 2837 3561 4269 4971 5669

4800 5523 2036 2792 3533 4270 5010 5757 2130 2918 3687 4451 5216 5986 2222 3041 3839 4628 5418 6211 2312 3162 3987 4802 5616 6431 2400 3280 4132 4973 5810 6648

N O T E : Detector time constant at a reference velocity of 5 ft/sec. F o r S I Units:

1 ft = 0 . 3 0 5 m 1000 B T U / s e c = 1055 k W

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-94

AUTOMATIC FIRE D E T E C T O R S

T a b l e C-4-1(h) Installed Spacing of Heat De~ctor: I0 feet Fire Growth Raw: 300 Seconds to I000 B T U / S E C Alpha: 0.011 B T U / S E C s

Table C-4-1(h) I n s t a l ~ d Spacing of Heat Detector: I0 ~ e t Fire G r o w t h Rate: 300 Seconds to I000 B T U / S E C Alpha: 0.011 B T U / S E C j

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET

TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

TAU RTI AT

28.0 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

91 126 160 195 230 267 131 179 224 269 314 359 164 224 279 333 386 440 194 265 328 391 453 519 222 302 374 445 514 587 248 336 417 495 577 651 273 370 458 544 631 712 301 401 497 595 684 771 323 432 535 639 734 828 345 461 572 682 783 888 366 490 613 723

131 187 246 309 377 448 180 250 322 395 470 549 222 306 389 473 558 645 260 357 451 545 639 735 296 404 508 612 716 820 329 448 563 676 789 901 361 490 615 737 858 979 386 531 665 796 925 1053 415 570 713 853 990 1125 443 608 759 907 1052 1t96 470 644 806 961

183 271 367 471 582 701 241 344 451 565 684 810 293 410 530 654 784 918 335 471 604 739 879 1022 377 528 673 820 969 1122 417 577 739 897 1056 1218 455 627 796 971 1140 1311 491 676 856 1042 1220 1400 526 723 914 1103 1299 1487 560 768 969 1168 1374 1572 593 812 1024 1232

249 379 524 682 853 1036 313 459 615 782 960 1150 371 532 703 881 1068 1266 424 602 784 977 1175 1380 474 667 863 1065 1278 1493 521 729 939 1153 1372 1603 566 789 1012 1237 1468 1703 609 846 1082 1319 1560 1806 650 901 1150 1399 1650 1906 690 955 1215 1476 1738 2003 729 1007 1280 1551

330 513 720 947 1193 1456 399 597 816 1051 1305 1575 465 679 909 1158 1420 1697 526 757 1001 1258 1534 1821 583 832 1090 1360 1642 1938 637 903 1176 1458 1752 2058 689 972 1259 1554 1859 2175 739 1038 1339 1647 1964 2290 787 1101 1417 1738 2066 2403 833 1163 1493 1826 2166 2514 878 1224 1567 1913

424 675 957 1268 1605 1967 500 762 1054 1377 1723 2092 572 851 1155 1485 1839 2220 640 937 1255 1596 1959 2344 705 1020 1353 1706 2079 2473 766 1100 1448 1814 2199 2602 825 1177 1541 1920 2316 2730 882 1251 1631 2023 2432 2856 936 1324 17t8 2125 2545 2980 989 1394 1804 2224 2656 3103 1041 1463 1888 2321

537 863 1234 1645 2091 2574 616 956 1338 1758 2213 2700 694 1050 1444 1874 2338 2833 769 1143 1550 1991 2464 2967 841 1234 1656 2108 2591 3103 909 1321 1759 2224 2718 3239 975 1407 1860 2339 2844 3375 1038 1489 1959 2452 2969 3510 1099 1570 2056 2563 3092 3645 1159 1649 2151 2672 3214 3778 1217 1725 2244 2780

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

28.0

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

.

275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

NOTE:

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

831 938 387 518 647 763 883 988 407 546 680 803 925 1038 427 572 713 842 967 1092 446 606 745 886 1009 1141 465 631 776 920 1055 1190

1113 1264 496 680 850 1012 1173 1330 521 715 892 1063 1230 1395 546 749 934 1113 1287 1459 571 774 976 1162 1342 1521 595 807 1016 1209 1397 1582

1439 1655 624 855 1077 1294 1510 1725 656 897 1128 1355 1579 1803 686 937 1179 1415 1647 1879 716 977 1228 1473 1714 1953 745 1017 1277 1530 1780 2027

1823 2098 767 1058 1342 1624 1907 2191 804 1107 1403 1696 1989 2283 840 1156 1463 1766 2069 2372 875 1203 1521 1835 2148 2460 910 1250 1579 1903 2225 2547

2264 2622 922 1283 1639 1997 2360 2728 965 1340 1710 2080 2454 2833 1007 1396 1779 2161 2546 2935 1048 1451 1847 2241 2637 3036 1089 1505 1913 2319 2726 3136

2766 3223 1091 1530 1969 2416 2873 3342 1140 1595 2050 2510 2979 3459 1188 1659 2128 2602 3083 3574 1235 1722 2205 2692 3185 3688 1281 1784 2281 2781 3286 3800

3334 3910 1273 1800 2335 2885 3453 4040 1328 1873 2425 2989 3570 4168 1382 1945 2513 3091 3685 4295 1435 2016 2599 3192 3798 4421 1487 2085 2684 3291 3910 4544

D e t e c t o r t i m e c o n s t a n t at a r e f e r e n c e velocity of 5 ft/sec.

F o r S l Units:

1 ft = 0 . 3 0 5 m 1000 B T U / s e c = 1055 k W

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

AI'PENDIX C

72E-95

T a b l e C-4-1(i) Installed Spacing of Heat Detector: 10 feet Fire G r o w t h Rate: 500 Seconds to 1000 B T U / S E C Alpha: 0.004 B T U / S E C j

T a b l e C-4-1(i) I n s ~ l l e d Spacing of H e a t D e ~ c t o r : 10 feet Fire G r o w t h Rate: 500 Seconds to 1000 B T U / S E C Alpha: 0.004 B T U / S E C s

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

.

20.0 .

.

.

24.0

TAU RTI AT

28.0 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

.65 92 121 150 181 214 91 127 162 198 235 272 114 158 199 241 283 326 134 185 233 '280 328 376 153 210 264 317 370 422 171 234 293 351 409 466 187 257 321 384 447 512 204 279 348 416 483 552 219 300 374 446 518 591 234 320 399 476 555 628 249 339 423 505

98 146 200 258 320 386 130 186 246 309 376 447 158 223 290 359 431 506 183 257 330 406 484 564 207 288 369 451 534 619 229 318 405 493 582 673 250 346 440 534 629 725 271 374 '474 574 674 775 291 400 507 612 717 823 310 426 538 649 760 870 328 451 569 685

143 222 312 410 516 630 179 266 361 464 574 692 212 308 410 519 634 756 243 348 458 572 693 819 272 386 503 624 751 882 297 422 546 674 807 944 322 456 588 723 861 1004 347 489 629 770 915 1062 370 518 668 816 966 1120 393 549 706 861 1017 1176 415 578 743 904

202 322 458 609 773 950 241 369 511 666 835 1015 279 415 564 725 898 1082 312 460 616 783 961 1150 345 501 667 841 1024 1218 377 542 717 897 "1087 1285 407 582 762 953 1148 1352 435 620 809 1007 1209 1419 463 657 854 1056 1268 1484 490 693 898 1107 1323 1548 517 728 941 1157

274 447 643 861 1098 1352 316 495 698 920 1162 1422 356 545 754 982 1228 1492 395 592 810 1044 1295 1563 432 640 863 1106 1362 1635 468 686 918 1165 1430 1707 503 731 971 1225 1494 1780 536 774 1023 1285 1560 1848 568 817 1074 1343 1625 1919 599 858 1124 1401 1689 1990 630 898 1173 1458

362 598 867 1166 1493 1844 405 649 924 1229 1561 1917 449 699 981 1293 1630 1991 491 751 1040 1356 1700 2065 533 803 1099 1421 1768 2141 572 853 1158 1486 1838 2213 611 903 1216 1551 1909 2289 648 951 1273 1616 1980 2365 685 998 1329 1680 2051 2441 720 1045 1385 1743 2121 2517 755 1090 1440 1806

465 775 1133 1530 1963 2430 510 828 1191 1593 2031 2506 556 882 1251 1660 2103 2580 602 937 1313 1727 2176 2657 647 992 1375 1795 2250 2736 690 1046 1437 1864 2324 2815 733 1100 1499 1933 2398 2895 774 1152 1561 2002 2473 2975 815 1204 1622 2070 2548 3055 854 1255 1683 2139 2623 3135 893 1305 1742 2206

4.0 .

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

.

20.0 .

.

.

24.0

28.0

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

.

275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

NOTE:

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

588 665 266 358 447 533 619 701 280 377 470 564 650 735 293 395 493 591 681 770 306 413 515 616 710 803 319 431 537 642 740 836

801 916 343 475 599 720 841 961 361 499 628 755 880 1005 378 522 657 789 919 1048 394 544 685 822 957 1091 410 567 712 854 994 1132

1066 1231 437 607 775 947 1115 1285 458 636 810 988 1162 1338 479 664 844 1024 1209 1389 499 691 878 1064 1254 1440 519 718 911 1102 1299 1490

1379 1611 542 762 983 1207 1435 1668 567 796 1024 1255 1489 1729 592 829 1064 1302 1543 1788 616 861 1104 1348 1596 1847 639 893 1143 1394 1648 1905

1753 2059 659 938 1221 1513 1815 2128 688 976 1269 t568 1877 2196 717 1014 1315 1622 1938 2263 744 1051 1360 1675 1998 2329 772 1088 1405 1728 2057 2395

2190 2697 2593 3216 788 930 1135 1355 1493 1801 1868 2273 2259 2772 2668 3296 821 967 1178 1 4 0 3 1546 1860 1929 2340 2327 2845 2742 3376 854 1003 1221 1451 1598 1917 1989 2406 2394 2919 2816 3456 885 1039 1263 1498 1649 1974 2048 2471 2461 2991 2889 3535 916 1074 1305 1544 1700 2030 2107 2536 2527 3063 2962 3614

D e t e c t o r t i m e c o n s t a n t at a r e f e r e n c e velocity of 5 ft/sec.

F o r S I Units:

1 ft = 0 . 3 0 5 m 1000 B T U / s e c = 1055 k W

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-96

AUTOMNFIC FIRE DETECTORS

T a b l e C-4-1 ~) Ins t a l l e d Spacing of H e a t Detector: 10 feet Fire G r o w t h Rate: 600 Seconds to 1000 B T U / S E C A l pha : 0.003 B T U / S E C s

T a b l e C-4-1(j) Installed Spacing of Heat Demcmr: 10 feet Fire Growth Ram: 600 Seconds to 1000 B T U / S E C Alp ha: 0.003 B T U / S E C s

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI AT

4.0

8.0

12.0

16.0

20.0

24.0

28.0

TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40, 60' 80 100 120 140 40 60 80 100

58 84 110 139 168 200 81 114 146 179 214 249 100 140 178 216 256 295 118 164 207 250 294 338 134 186 234 282 330 379 150 207 260 312 365 417 164 226 284 341 398 454 178 245 308 369 429 489 192 264 330 395 460 526 205 281 352 421 489 559 218 298 373 446

89 136 188 244 305 371 116 170 226 287 352 420 140 201 264 329 398 470 162 230 298 369 443 519 183 257 332 408 486 566 202 283 363 445 527 612 221 308 394 480 568 657 239 331 423 514 606 700 256 354 451 547 644 742 272 377 478 579 681 783 289 398 505 611

133 210 298 394 499 611 163 246 338 439 547 662 191 282 379 484 596 715 218 316 419 529 645 767 242 348 458 573 694 820 266 379 495 616 741 872 286 409 531 657 788 923 308 437 566 698 833 973 328 465 600 737 878 1022 348 492 633 776 921 1070 367 515 665 813

190 307 442 591 753 927 222 346 485 637 803 981 254 384 528 685 855 1036 283 422 572 734 907 1091 311 459 615 782 959 1148 338 493 657 829 1012 1204 364 527 698 876 1064 1260 389 559 736 922 1115 1316 413 591 775 968 1165 1371 437 623 813 1009 1215 1425 459 653 850 1052

260 429 623 838 1073 1325 295 469 668 887 1126 1382 328 510 714 937 1180 1440 361 550 760 988 1235 1498 393 590 806 1040 1290 1557 423 629 851 1091 1346 1617 453 667 896 1140 1402 1677 482 704 940 1190 1458 1737 509 741 984 1240 1510 1797 536 776 t026 1289 1564 1853 563 811 1068 1337

346 577 843 1139 1463 1811 381 619 890 1191 1519 1871 417 661 938 1244 1576 1932 452 704 985 1297 1633 1994 487 746 1034 1349 1692 2056 521 789 1083 1403 1747 2118 554 831 1131 1457 1806 2178 587 872 1180 1511 1865 2241 618 912 1227 1564 1924 2304 648 952 1274 1618 1982 2367 678 991 1321 1671

446 752 1105 1498 1928 2391 483 795 1153 1550 1987 2454 521 839 1203 1605 2043 2515 559 884 1253 1660 2103 2579 596 930 1304 1716 2164 2643 633 975 1356 1773 2225 2708 669 1020 1407 1830 2286 2774 705 1064 1459 1887 2348 2840 739 1108 1510 1944 2410 2906 773 1152 1561 2001 2472 2972 806 1194 1611 2058

.

.

.

.

8.0 .

.

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

.

28.0 .

.

.

.

.

.

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 25 25 25 25 25 50 50 50 50 50 50 75 75 ,75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

4.0 .

275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

518 591 230 315 394 471 549 622 242 331 414 495 576 652 257 347 434 518 602 682 268 363 453 545 628 711 280 378 472 567 654 740

716 823 304 419 531 641 752 862 320 440 557 671 786 900 332 460 581 701 819 937 346 480 606 730 852 974 361 499 630 758 884 1010

964 1118 '386 541 697 850 1006 1164 405 565 728 886 1047 1210 423. 589 754 922 1087 1254 440 613 783 957 1127 1299 458 636 812 991 1166 1342

1264 1479 482 683 886 1094 1309 1532 503 712 922 1136 1356 1585 525 740 957 1177 1402 1632 546 768 991 1217 1447 1683 566 796 1025 1257 1492 1733

1618 1912 588 845 1110 1385 1671 1970 614 879 1150 1432 1724 2028 638 911 1190 1478 1776 2085 662 944 1230 1524 1828 2142 686 975 1268 1569 1878 2198

2040 2430 707 1029 1367 1723 2098 2493 736 1067 1412 1775 2156 2556 764 1104 1457 1826 2213 2618 791 1140 1501 1877 2270 2680 818 1176 1544 1927 2326 2742

2534 3039 839 1237 1661 2114 2596 3106 871 1278 1711 2170 2658 3173 902 1319 1760 2226 2719 3239 933 1359 1808 2281 2781 3306 963 1399 1856 2336 2842 3372

NOTE: Detector time constant at a reference velocity of 5 ft/sec. For SI Units:

1 ft = 0.305 m 1000 BTU/sec = 1055 kW

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX C

72E-97

T a b l e C,-4- l (k) Installed Spacing of Heat Detector: 12 feet Fire Growth Rate: 50 Seconds to 1000 B T U / S E C Alpha: 0.400 B T U / S E C s

T a b l e C-4-1 (k) Installed Spacing of Heat Detector: 12 feet Fire G r o w t h Rate: 50 Seconds to 1000 B T U / S E C Alpha: 0.400 B T U / S E C 5

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET

TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

24.0 .

.

TAU RTI AT

28.0 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

56 40 482 56 60 593 56 80 722 56 100 821 56 120 927 56 140 1007 112 40 668 112 60 878 112 80 993 112 100 1162 112'120 1316 112 140 1469 168 40 867 168 60 1021 168 80 1255 168 100 1461 168 120 1665 168 140 1867 224 40 957 224 60 1226 224 80 1 4 8 6 224 100 1 7 4 2 224 120 1993 224 140 2242 280 40 1 0 4 7 280 60 1399 280 80 1708 280 100 2011 280 120 2309 280 140 2605 335 40 1199 335 60 1566 335 80 1923 335 100 2272 335 120 2618 335 140 2961 391 40 1313 391 60 1729 391 80 2133 391 100 2529 391 120 2922 391 140 3317 447 40 1425 447 60 1889 447 80 2339 447 100 2783 447 120 3226 447 140' 3538 503 40 1535 503 60 2046 503 80 2543 503 100 3036 503 120 3416 503 140 383~ 559 40 1643 559 60.... 2201 559 80":i'2,~46 559 100'3289 559 120 3671 559 140 4123 615 40 1750 615 60 2354 615 80 2947 615 100 3423

585 751 913 1090 1243 1389 831 1078 1328 1552 1766 1977 1043 1370 1668 1946 2216 2480 1257 1625 1971 2303 2624 2937 1409 1852 2253 2636 2933 3283 1584 2067 2520 2874 3277 3668 1736 2273 2699 3161 3605 4035 1882 2471 2933 3436 3919 4378 2023 2586 3159 3702 4215 4714 2161 2763 3378 3959 4505 5039 2294 2936 3590 4200

730 952 1168 1384 1598 1836 1026 1338 1635 1923 2206 2486 1273 1663 2030 2382 2726 3065 1497 1954 2383 2795 3195 3587 1695 2220 2709 3176 3625 4067 1886 2470 3015 3530 4032 4522 2064 2707 3300 3869 4419 4954 2234 2934 3577 4194 4789 5367 2398 3145 3843 4507 5145 5765 2556 3355 4~01 4809 5490 6151 2709 3558 4351 5102

897 1184 1467 1753 2043 2339 1244 1633 2006 2374 2739 3105 1533 2011 2466 2907 3342 3774 1790 2349 2878 3388 3888 4380 2026 2661 3258 3833 4393 4943 2246 2953 3615 4250 4868 5473 2455 3229 3953 4647 5319 5977 2654 3493 4277 5026 5752 6460 2845 3747 4588 5391 6168 6925 3029 3992 4889 5744 6570 7375 3208 4230 5181 6087

1085 1446 1810 2182 2565 2959 1482 1958 2422 2882 3345 3812 1815 2392 2947 3491 4031 4570 2111 2781 3420 4042 4654 5263 2382 3139 3857 4552 5233 5907 2636 3475 4267 5031 5778 6514 2876 3793 4656 5487 6297 7092 3105 4097 5028 5923 6793 7646 3325 4389 5386 6342 7271 8180 3537 4671 5732 6748 7733 8697 3742 4944 6067 7141

1291 1518 1740 2069 2200 2640 2675 3238 3169 3864 3683 4518 1 7 4 0 2017 2314 2702 2880 3385 3450 4079 4026 4788 4613 5516 2117 2438 2804 3248 3472 4042 4132 4834 4793 5632 5458 6441 2452 2814 3245 3741 4006 4638 4753 5525 5494 6410 6234 7300 2761 3160 3651 4195 4501 5190 5330 6168 6147 7137 6960 8106 3049 3483 4032 4622 4965 5710 5872 6774 6763 7824 7646 8870 3321 3789 4392 5026 5406 6204 6388 7350 7350 8479 8299 9599 3581 4081 4737 5412 5828 6676 6882 7903 7911 9107 8925 10298 3831 4360 5068 5783 6234 7130 7 3 5 7 8435 8452 9712 9529 10973 4071 4630 5388 6142 6626 7569 7816 8949 8976 10298 10114 11627 4304 4892 5698 6489. 7 0 0 6 7995 8262 9448

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

28.0

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 •150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

4.0 .

275 615 275 615 300 671 300 671 300 671 300 671 300 671 300 671 325 727 325 727 325.727 325 727 325 727 325 727 350 783 350 783 350 783 350 783 350 783 350 783 375 839 375 839 375 839 375 839 375 839 375 839 400 894 400 894 400 894 400 894 400 894 400 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

3921 4408 1856 2507 3149 3635 4168 4690 1960 2658 3259 3844 4412 4840 2064 2809 3430 4050 4653 5089 2166 2960 3599 4254 4765 5334 2268 3112 3766 4456 4979 5575

4788 5355 2425 3104 3797 4441 5063 5663 2475 3268 3992 4676 5331 5956 2594 3428 4188 4906 5594 6249 2712 3585 4379 5132 5844 6535 2827 3740 4567 5353 6095 6817

5824 6525 2858 3756 4594 5387 6150 6889 2995 3949 4831 5666 6467 7244 3136 4138 5062 5938 6778 7591 3275 4322 5289 6204 7081 7931 3410 4503 5511 6465 7379 8264

6961 8182 9484 10866 7811 9198 10681 12261 3381 3942 4531 5145 4461 5210 5999 6826 5465 6393 7375 8409 6420 7524 8696 9933 7341 8618 9978 11419 8236 9686 11233 12879 3550 4136 4751 5392 4686 5469 6292 7155 5741 6711 7736 8813 6745 7897 9118 10407 7711 9044 10460 11959 8651 10162 11772 13482 3715 4326 4966 5634 4906 5721 6579 7476 6012 7022 8087 9207 7 0 6 2 8262 9531 10869 8074 9460 10931 12486 9056 10627 12299 14071 3876 4511 5176 5869 5121 5969 6859 7790 6276 7326 8432 9593 7373 8619 9936 11322 8428 9867 11392 13003 9453 11082 12815 14649 4034 4693 5382 6100 5332 6211 7 1 3 4 8098 6535 7623 8769 9970 7677 8968 10332 11766 8776 10266 11845 13509 9842 11529 13321 15215

N O T E : Detector time constant at a reference velocity of 5 ft/sec. For SI Units:

1 ft = 0.305 m 1000 B T U / s e c = 1055 kW

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-98

AUTOMATIC FIRE DETECTORS

T a b l e C--4-1(!) Installed Spacing of H e a t Detector: 12 feet Fire Growth Rate: 150 Seconds to 1000 B T U / S E C Alpha: 0.044 B T U / S E C s

T a b l e C-4-1(1) Installed Spacing of Heat Detector: 12 feet Fire Growth Rate: 150 Seconds m 1000 B T U / S E C A l p h a : 0.044 B T U / S E C s

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0

.

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

CEILING HEIGHT. IN FEET

24.0 .

.

.

.

.

28.0

.

TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

FIRE SIZE AT DETECTORRESPONSE(BTU / SEC) 25 '25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 '100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 1.00 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

190 256 316 375 435 501 275 368 452 534 621 700 353 462 567 675 772 878 415 545 678 794 914 1017 472 634 771 910 1029 1168 526 704 871 1004 1159 1306 578 771 944 1111 1276 1438 640 836 1017 1209 1389 1566 685 905 1104 1304 1499 1691 729 958 1182 1396 1606 1813 772 1012 1257 1487

254 345 437 531 628 729 359 483 602 722 842 963 439 590 745 889 1030 1173 516 692 862 1039 1202 13~1 587 788 978 1164 1359 1540 654 877 1089 1293 1493 1708 717 962 1193 1416 1633 1847 779 1043 1293 1534 1768 1998 837 1122 1390 1647 1898 2143 894 1197 1483 1757 2024 2284 949 1271 i1574 1864

327 461 596 738 888 1045 447 613 779 954 1127 1303 549 747 943 1138 1334 1543 641 869 1091 1311 1531 1752 726 982 1230 1473 1715 1957 806 1088 1360 1626 1889 2152 881 1190 1484 1772 2056 2337 954 1286 1604 1912 2215 2515 1023 1380 1718 2047 2369 2688 1091 1470 1829 2178 2519 2855 1156 1557 1937 2305

418 602 794 999 1217 1448 556 774 997 1228 1475 1725 675 929 1184 1443 1708 1980 782 1070 1355 1642 1932 2227 881 1202 1516 1829 2144 2462 974 1326 1668 2006 2345 2686 1062 1443 1812 2176 2538 2900 1147 1556 1951 2339 2723 3107 1228 1665 2085 2496 2902 3307 1307 1771 2214 2648 3076 3501 1383 1873 2340 2796

525 766 1030 1318 1623 1946 679 959 1253 1561 1886 2227 814 1134 1461 1798 2148 2510 937 1295 1655 2021 2397 2783 1050 1445 1837 2233 2635 3045 1157 1587 2010 2434 2863 3297 1259 1722 2176 2627 3081 3540 1356 1852 2334 2813 3292 3775 1450 1976 2488 2993 3497 4002 1540 2097 2636 3167 3695 4223 1628 2215 2780 3336

.648 790 964 1194 1313 1644 1693 2136 2100 2665 2542 3230 818 972 1173 1415 1550 1893 1953 2407 2380 2957 2832 3540 969 1139 1366 1625 1778 2137 2209 2679 2660. 3251 3132T: 3854 1107 1292 1545 1822 1993 2371 2454 2943 2932 3542 3427 4168 1235 1435 1714 2009 2196 2594 2688 3199 3194 3826 3714 4476 1356 1570 1873 2186 2390 2809 2913 3446 3446 4101 3992 4778 1471 1698 2026 2356 2576 3014 3129 3684 3690 4369 4262 5072 1581 1821 2172 2519 2754 3213 3338 3915 3926 4629 4523 5359 1687 1940 2313 2676 2927 3405 3540 4139 4155 4882 4778 5639 1789 2054 2450 2829 3095 3592 3736 4357 4378 5129 5025 5913 1889 2166 2583 2977 3258 3774 3927 4569

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

12,0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

24.0 .

28.0

.

~ _ _ _

FIRE SIZE AT DETECTORRESPONSE(BTU / SEC) 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

1712 1934 814 1079 1332 1576 1816 2027 870 1137 1404 1664 1919 2136 90~ 1193 1476 1750 2021 2243 938 1249 1547 1836 2088 2348 973 1304 1617 1921 2180 2451

2146 2421 1002 1343 1662 1968 2265 2554 1055 1413 1749 2070 2381 2684 1105 1481 1833 2169 2495 2812 1155 1548 1916 2267 2606 2937 1203 1614 1997 2362 2715 3059

2664 3017 1220 1643 2042 2428 2805 3175 1282 1726 2145 2549 2943 3330 1342 1807 2245 2667 3078 3481 1401 1887 2343 2783 3210 3629 1460 1965 2440 2896 3340 3775

3245 3690 1458 1972 2463 2940 3409 3874 1530 2069 2582 3081 3570 4054 1601 2164 2699 3218 3727 4230 1670 2257 2814 3353 3881 4402 1738 2348 2926 3486 4033 4572

3888 4439 1713 2329 2921 3501 4076 4649 1796 2440 3058 3663 4260 4855 1878 2549 3192 3820 4440 5056 1957 2656 3324 3975 4617 5253 2035 2760 3453 4127 4790 5447

4595 5267 1985 2712 3417 4113 4807 5503 2080 2838 3572 4295 5014 5735 2172 2961 3723 4473 5218 5961 2262 3082 3872 4648 5417 6184 2350 3200 4018 4819 5612 6403

5370 6180 2274 3121 3951 4776 5605 6442 2379 3262 4124 4979 5836 6699 2483 3400 4293 5178 6062 6951 2583 3535 4459 5373 6284 7198 2682 3668 4622 5564 6502 7441

NOTE: Detector time constant at a reference velocity of 5 ft/sec. For SI Units:

1 ft = 0 . 3 0 5 m BTU/sec = 1055 kW

1000

i

1990Edition

.

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX C

72E-99

T a b l e C - 4 - I (m) I n s t a l l e d Spacing of H e a t D e t e c t o r : 12 feet Fire G r o w t h Rate: 300 Seconds to I000 B T U / S E C Alpha: 0.011 B T U / S E C s

Table C-4-I(m) Installed Spacing of Heat Detector: 12 feet Fire G r o w t h R a ~ : 300 Seconds to 1000 B T U / S E C Alpha: 0.011 B T U / S E C s

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

TAU RTI AT

28.0 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 S03 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

115 159 203 247 294 341 164 224 282 339 396 458 205 280 349 418 487 558 243 330 411 490 573 649 281 376 468 562 648 734 313 419 521 624 720 814 344 461 579 684 788 895 373 500 626 741 861 964 401 538 672 796 919 1034 428 575 717 849 977 1106 455 617 761 905

160 228 302 380 463 551 219 305 392 482 575 672 270 372 473 576 680 787 312 433 548 662 778 895 354 485 617 744 871 998 393 537 683 821 958 1095 430 587 739 895 1042 1189 466 635 798 958 1115 1279 500 682 855 1025 1201 1366 534 726 911 1090 1266 1451 566 770 964 1153

218 322 437 562 697 840 283 408 536 672 815 966 342 482 629 777 931 1092 395 552 711 877 1042 1213 445 618 791 966 1149 1331 491 680 867 1055 1245 1444 536 739 940 1140 1342 1546 578 796 1010 1222 1435 1649 619 851 1077 1301 1525 1750 659 904 1143 1378 1613 1848 697 956 1207 1453

290 442 611 797 998 1212 363 534 716 911 1121 1343 429 617 814 1025 1245 1476 491 697 910 1132 1367 1608 548 773 1001 1237 1480 1732 602 845 1089 1338 1594 1857 654 913 1172 1435 1704 1979 704 979 1253 1530 1811 2097 751 1043 1332 1621 1914 2212 798 1105 1408 1710 2015 2324 843 1165 1482 1797

375 588 825 1087 1370 1673 456 682 932 1206 1498 1809 530 776 1040 1322 1628 "1948 600 865 1145 1440 1753 2083 665 950 1246 1556 1880 2220 727 1031 1344 1668 2005 .2356 786 1109 1438 1777 2127 2490 842 1184 1530 1883 2247 2621 897 1257 1619 1987 2363 2750 950 1328 1705 2087 2477 2875 1002 1397 1789 2186

479 761 1082 1435 1818 2228 564 861 1192 1554 1946 2369 645 961 1305 1679 2080 2508 722 1058 1418 1804 2216 2653 795 1151 1528 1928 2352 2798 864 1241 1636 2050 2486 2943 930 1328 1740 2170 2618 3087 994 1413 1842 2287 2749 3230 1056 1494 1941 2401 2877 3370 1116 1574 2037 2513 3003 3508 1174 1651 2132 2623

599 964 1380 1840 2339 2875 688 1069 1496 1967 2476 3022 775 1174 1615 2096 2616 3170 859 1278 1734 2227 2757 3321 939 1379 1852 2359 2899 3473 1015 1477 1967 2489 3042 3626 1089 1573 2081 2617 3183 3778 1160 1666 2192 2744 3323 3930 1229 1756 2301 2869 3462 4081 1295 1844 2407 2991 3598 4230 1360 1930 2511 3111

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

28.0

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

4.0 .

275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

NOTE:

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

1035 1174 481 651 804 952 1097 1240 506 685 846 999 1155 1305 531 717 892 1047 1211 1368 555 749 929 1099 1267 1431 579 781 966 1146 1321 1493

1339 1522 598 812 1017 1215 1409 1601 628 854 1068 1275 1478 1679 658 894 1118 1334 1546 1754 688 934 1167 1392 1612 1828 717 972 1215 1448 1677 1901.

1699 1944 735 1006 1269 1526 1782 2037 771 1056 1329 1598 1864 2128 807 1104 1389 1668 1943 2218 842 1151 1447 1736 2022 2305 876 1197 1504 1803 2099 2391

2114 2434 886 1224 1554 1882 2211 2542 929 1281 1624 1965 2305 2647 971 1337 1693 2046 2398 2751 1011 1392 1761 2125 2488 2852 1052 1446 1827 2204 2578 2952

2588 2999 1052 1464 1872 2282 2698 3120 1101 1529 1952 2376 2805 3239 1148 1593 2031 2469 2910 3356 1195 1656 2109 2560 3013 3472 1241 1718 2185 2649 3115 3585

3126 3644 1231 1726 2224 2730 3248 3778 1286 1800 2315 2836 3367 3910 1340 1873 2403 2939 3484 4040 1393 1944 2490 3041 3600 4169 1445 2013 2576 3141 3714 4295

3733 4377 1423 2013 2613 3229 3865 4523 1485 2096 2713 3346 3996 4667 1546 2176 2812 3460 4125 4809 1605 2255 2908 3573 4252 4950 1663 2333 3003 3684 4378 5089

D e t e c t o r t i m e c o n s t a n t at a reference velocity of 5 ft/sec.

F o r SI Units:

1 ft = 0.30.5 m 1000 B T U / s e c = 1055 k W

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

7 2 E - 100

AUTOMNI'IC FIRE I)ETECTORS

T a b l e C-4-1 (n) Ins t a l l e d Spacing of H e a t Detector: 12 feet Fire G row t h Rate: 500 Seconds to 1000 B T U / S E C A l pha : 0.004 B T U / S E C '

T a b l e C-4-1(n) I n s t a l l e d Spacing of Heat Detector: 12 feet Fire G r o w t h Rate: 500 Seconds to 1000 B T U / S E C A l p h a : 0.004 B T U / S E C '

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0

TAU RTI AT

28,0 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

225 225 225 225 225 250 250 250 250 275 275 275 275 275 275

56 40 56 60 56 80 56 100 56 120 56 140 112 40 112 60 112 80 112 100 112 120 112 140 168 40 168 60 168 80 168 100 168 120 168 140 224 40 224 60 224 80 224 100 224 120 224 140 280 40 280 60 280 80 280 100 280"120 280 140 335 40 335 60 335 80 335 100 335 120 335 140 391 40 391 60 391 80 391 100 391 120 391 140 447 40 447 60 447 80 447 100 447 120 447 140 503 40 503 60 503 80 503 100 503 120 503 140 559 40 559 60 559 80 559 100 615 40 615 60 615 80 615 100 615 120 615 140

82 117 154 192 233 275 115 160 205 251 298 347 143 198 251 304 358 413 168 232 292 353 414 477 191 263 331 398 466 535 213 293 368 441 518 589 237 321 402 482 564 641 257 348 436 522 609 691 276 374 468 563 652 740 295 399 499 599 313 424 530 635 734 833

120 180 246 318 395 478 158 227 301 379 462 549 191 271 353 439 528 620 222 312 402 495 591 690 251 350 449 549 651 756 275 386 493 600 709 820 301 420 535 650 765 883 325 450 575 697 819 943 348 481 615 743 872 1001 371 512 653 788 393 541 685 832 972 1113

170 266 373 491 618 755 213 317 431 554 687 828 252 366 488 618 756 902 286 413 543 680 825 976 319 455 596 741 892 1050 350 496 647 800 958 1122 380 536 693 857 1022 1192 409 574 740 913 1085 1261 436 611 786 962 1146 1328 463 647 830 1014 489 682 873 1064 1258 1459

235 376 536 713 906 1113 280 430 596 779 976 1188 322 483 657 846 1048 1265 362 533 717 913 1121 1342 400 582 774 979 1194 1421 436 629 830 1042 1266 1498 471 675 885 1105 1337 1576 504 719 939 1167 1403 1~52 536 762 991 1227 1471 1723 567 803 1042 1286 598 844 1091 1344 1602 1868

314 512 738 989 1262 1556 361 568 801 1057 1336 1634 407 623 864 1127 1411 1714 451 678 926 1197 1487 1795 494 732 989 1265 1563 1877 535 784 1051 1335 1637 1959 574 835 1111 1403 1712 2038 612 885 1171 1471 1787 2119 648 933 1229 1538 1861 2200 684 980 1286 1604 719 1026 1342 1668 2007 2359

408 676 982 1321 1692 2090 457 732 1046 1392 1768 2173 506 790 1110 1462 1846 2256 555 849 1176 1535 1922 2336 601 907 1243 1608 2001 2421 646 964 1309 1682 2081 2506 690 1020 1374 1755 2161 2592 732 1074 1439 1828 2241 2678 773 1128 1503 1900 2320 2764 813 1180 1565 1972 852 1231 1627 2042 2478 2934

519 866 1265 1710 2195 2717 570 926 1332 1783 2274 2803 621 987 1400 1858 2355 2889 673 1048 1469 1933 2437 2976 723 1109 1539 2010 2519 3064 772 1170 1609 2087 2602 3153 819 1230 1678 '2164 2686 3242 866 1289 1747 2241 2770 3332 911 1348 1816 2318 2854 3422 955 1405 1884 2394 998 1461 1951 2470 3021. 3602

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0

28.0

.

FIRE SIZE AT DETECTOR RESPONSE (8TU / SEC)

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225

.

300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

671 871 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

330 447 563 669 774 881 348 471 592 703 813 922 364 493 619 736 851 963 381 516 646 768 891 1005 397 538 673 800 926 1047

414 570 721 874 1021 1168 435 598 755 910 1068 1221 455 626 789 950 1115 1272 475 653 823 989 1154 1323 495 679 856 1028 1198 1373

515 716 915 1114 1314 1517 539 750 956 1162 1369 1578 564 782 996 1209 1423 1638 587 814 1036 1256 1476 1697 611 846 1075 1301 1528 1756

627 883 1140 1400 1666 1939 656 922 1187 1456 1729 2009 685 960 1234 1510 1791 2077 712 997 1280 1564 1852 2145 739 1034 1325 1617 1912 2212

752 1071 1396 1732 2078 2437 785 1115 1450 1794 2148 2514 818 1158 1503 1855 2218 2591 849 1201 1555 1916 2286 2667 881 1243 1606 1976 2354 2741

890 1282 1688 2112 2555 3019 927 1331 1747 2181 2632 3103 964 1379 1806 2249 2708 3186 999 1427 1864 2316 2784 3269 1034 1474 1921 2382 2858 3351

1041 1516 2017 2546 3104 3692 1082 1570 2082 2620 3187 3782 1122 1624 2146 2694 3269 3871 1162 1676 2210 2767 3350 3960 1201 1728 2273 2840 3431 4048

NOTE: Detector time constant at a reference velocity of 5 ft/sec. For SI Units: .1 ft = 0.305 m 1000 BTU/sec = 1055 kW

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-101

APPENDIX C

T a b l e C - 4 - l (o) Installed Spacing of Heat Detector: 12 feet Fire Growth Rate: 600 Seconds to I000 B T U / S E C Alpha: 0.003 B T U / S E C ~

T a b l e C ~ - 1(o) Installed Spacing of Heat Detector: 12 ~ e t Fire Growth Rate: 600 Seconds to 1000 B T U / S E C Alpha: 0.003 B T U / S E C s

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

24.0 .

.

CEILING HEIGHT IN FEET 28.0

.

TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 56 25 56 25 56 25 56 25 56 25 56 50 112 50 112 50 112 50 112 50 112 50 112 75 168 75 168 75 168 75 168 75 168 75 168 100 224 100 224 100 224 100 224 100 224 100 224 125 280 125 280 125 280 125 280 125 280 125 280 150 335 150 335 150 335 150 335 150 335 150 335 175 391 175 391 175 391 175 391 1-75 391 17"5 391 200 447 200 447 200 447 200 447 200 447 200 447 225 503 225 503 225 503 225 503 225 503 225 503 250 559 250 559 250 559 250 559 250 559 250 559 275 615 275 615 275 615 275 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

74 106 141 178 217 258 102 143 185 228 273 319 126 176 224 274 324 375 148 205 261 316 372 429 168 233 294 355 417 481 187 259 326 393 460 528 206 283 356 429 503 573 225 307 385 463 542 617 242 329 414 496 580 659 259 351 441 532 616 700 274 373 467 562

110 167 232 302 378 459 142 207 278 353 433 518 171 245 322 403 488 577 197 280 364 451 542 636 222 312 404 497 593 692 246 344 442 541 643 747 266 373 478 584 691 801 287 402 513 625 738 853 307 427 547 665 783 ~03 327 454 581 704 828 952 346 479 613 742

159 251 356 472 598 734 194 293 404 524 654 793 227 335 451 577 711 854 258 374 498 630 769 916 285 412 543 681 825 977 312 447 587 731 881 1038 338 481 629 780 936 1097 363 514 668 827 989 1156 387 547 707 874 1041 1214 410 578 746 916 1093 1270 433 608 783 960

221 359 517 692 882 1087 259 403 566 745 940 1149 294 447 616 800 999 1212 328 491 666 856 1059 1276 361 531 716 911 1119 1340 392 572 762 966 1180 1405 422 611 809 1020 1239 1469 451 649 855 1070 1298 1534 478 686 900 1122 1353 1597 506 722 944 1173 1410 1660 532 757 986 1222

299 493 716 964 1234 1525 337 538 767 1020 1294 1590 375 585 819 1077 1356 1655 413 630 872 1134 1418 1722 449 675 922 1193 1481 1789 484 719 974 1249 1545 1857 517 763 1026 1306 1605 1925 550 805 1076 1364 1668 1990 582 847 1126 1420 1731 2057 613 887 1174 1476 1792 2125 643 927 1222 1531

391 654 955 1291 1658 2054 430 699 1008 1350 1721 2121 471 747 1061 1409 1786 2190 511 796 1115 1467 1848 2259 550 844 1170. 1527 1913 2326 589 892 1225 1588 1979 2396 626 939 1280 1649 2045 2467 662 985 1334 1710 2111 2538 698 1031 1388 1770 2177 2609 732 1076 144t 1830 2243 2680 766 1120 1494 1890

498 841 1235 1675 2156 2675 540 889 1290 1736 2222 2745 582 939 1346 1797 2288 2816 625 990 1403 1859 2355 2888 667 1040 1460 1922 2423 2961 708 1091 1517 1985 2491 3033 749 1141 1575 2049 2560 3107 788 1191 1633 2113 2629 3181 827 1240 1690 2177 2699 3255 865 1289 1747 2241 2769 3330 902 1337 1804 2304

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

28.0 .

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

NOTE:

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

651 740 290 393 493 592 686 779 305 414 518 622 720 817 319 434 543 650 753 854 334 453 571 679 785 894 348 472 594 706 817 928

871 1000 365 504 644 779 913 1047 383 529 671 815 954 1093 401 553 700 850 994 1138 418 576 729 880 1034 1183 435 599 758 914 1073 1226

1143 1326 455 638 819 1002 1188 1380 477 667 855 1044 1235 1434 498 695 890 1085 1282 1482 519 723 924 1126 1328 1533 539 750 958 1165 1373 1584

1466 1718 558 791 1028 1271 1521 1779 583 825 1069 1319 1575 1838 607 858 1110 1366 1628 1897 631 890 1150 1413 1681 1956 655 922 1189 1458 1733 2013

1854 2191 672 966 1269 1585 1914 2258 701 1004 1316 1639 1974 2323 729 1041 1361 1692 2034 2389 756 1078 1406 1744 2092 2453 783 1114 1450 1795 2150 2517

2309 2751 798 1163 1545 1949 2375 2822 831 1205 1597 2008 2440 2893 862 1247 1647 2066 2504 2963 893 1288 1697 2123 2568 3033 924 1329 1746 2180 2632 3103

2838 3404 938 1384 1860 2368 2908 3479 974 1431 1915 2430 2977 3554 1009 1476 1970 2493 3046 3629 1043 1522 2024 2555 3115 3703 1077 1566 2078 2617 3183 3777

D e t e c t o r t i m e c o n s t a n t at a r e f e r e n c e velocity of 5 f t / s e c .

F o r Si Units:

1 ft = 0 . 3 0 5 m 1000 B T U / s e c = 1055 k W

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E- 102

AUTOMNI'IC FIRE I ) E T E C T O R S

T a b l e C-4-1 (p) Ins~l~d Spacingof Heat De~cmr: 15 feet F i r e G r o w t h R a t e : 50 Seconds to 1000 B T U / S E C A l p h a : 0.400 B T U / S E C s

T a b l e C-4-1(p) I n s t a l l e d S p a c i n g o f Heat De~ctor: 15 ~ e t Fire Growth Rate: 50 Seconds to I000 B T U / S E C Alpha: 0.400 B T U / S E C '

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

TAU RTI &T

28.0 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

1990 Edition

618 790 935 1046 1215 1357 894 1098 1321 1541 1758 1974 1035 1370 1668 1960 2248 2533 1245 1625 1994 2356 2714 3071 1417 1870 2309 2Z~1 3172 3485 1584 2107 2616 3121 3501 3927 1746 2339 2920 3390 3879 4356 1906 2569 3224 3707 4247 4670 2062 2796 3407 4017 4609 5045 2217 3023 3660 4321 4835 5409 2370 3251 3909 4622

745 962 1169 1393 1600 1799 1063 1370 1664 1949 2226 2499 1356 1712 2083 2439 2783 3119 1547 2019 2460 2880 3285 3680 1760 2304 2809 3289 3752 4195 1960 2571 3137 3674 4183 4681 2151 2825 3449 4034 4598 5145 2333 3068 3749 4382 4995 5583 2508 3303 4029 4717 5378 6009 2678 3530 4305 5042 5740 6421 2843 3751 4573 5357

903 1181 1452 1722 1992 2266 1269 1656 2026 2385 2739 3091 1577 2055 2511 2951 3380 3804 1843 24~2 2947 3459 3958 4447 2091 2741 3348 3930 4493 5044 2323 3049 3726 4371 4995 5605 2543 3341 4083 4790 5473 6138 2753 3620 4426 5192 5930 6649 2955 3889 4755 5578 6371 7141 3150 4148 5073 5951 6796 7617 3339 4400 5381 6313

1085 1 2 8 7 1 5 0 9 1753 1434 1720 2040 2395 1781 2157 2583 3061 2131 2605 3146 3759 2488 3066 3731 4490 2852 3541 4340 5255 1 5 0 3 1758 2034 2331 1976 2327 2711 3128 2431 2883 3380 3925 2880 3435 4052 4735 3327 3991 4734 5563 3775 4552 5429 6412 1 8 5 2 2153 2476 2819 2432 2843 3286 3763 2986 3507 4074 4687 3525 4159 4853 5611 4055 4806 5634 6543 4582 5453 6420 7487 2162 2505 2870 3256 2841 3305 3803 4334 3484 4069 4701 5379 4105 4813 5582 6413 4714 5547 6457 7446 5315 6276 7332 8485 2447 2827 3231 3657 3218 3731 4280 4862 3944 4589 5281 6021 4643 5420 6259 7160 5325 6236 7224 8291 5996 7043 8184 9422 2713 3129 3569 4032 3570 4130 4726 5357 4375 5076 5827 6625 5148 5990 6896 7865 5900 6884 7947 9090 6637 7766 8989 10309 2965 3414 3889 4387 3905 4509 5150 5827 4784 5539 6345 7199 5627 6 5 3 2 7502 8535 6446 7501 8636 9851 7247 8454 9757 11157 3205 3687 4194 4726 4224 4870 5554 6276 5176 5982 6840 7748 6086 7051 8082 9177 6969 8092 9296 10581 7831 9113 10493 11970 3436 3948 4487 5051 4531 5 2 1 8 5943 6707 5553 6408 7317 8276 6528 7551 8640 9796 7472 8661 9932 11285 8393 9749 11203 12755 3659 4200 4769 5364 4828 5553 6319 7123 5917 6820 7777 8787 6955 8033 9180 10394 7959 9211 10547 11966 8938 10363 11889 13515 3875 4445 5043 5668 5115 5878 6683 7527 6269 7219 8224 9282 7369 8502 9704 10974

4.0 .

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

28.0 .

.

.

.

.

.

.

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

.

275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

5151 5765 2522 3362 4153 4785 5461 6114 2673 3552 4396 5049 5764 6456 2824 3739 4522 5308 6062 6793 2975 3925 4736 5563 6356 7126 3126 4108 4948 5814 6647 7455

6098 6821 3003 3956 4834 5655 6446 7211 3160 4163 5089 5953 6787 7591 3313 4366 5330 6244 7119 7963 3463 4564 5573 6530 7445 8328 3611 4759 5811 6809 7764 8685

7209 8432 9745 8079 9466 10960 3522 4085 4682 4644 5395 6194 5682 6613 7607 6666 7772 8957 7 6 1 2 8891 10265 8529 9980 11541 3701 4289 4913 4882 5 6 6 7 6502 5974 6947 7985 7009 8165 9402 8004 9340 10772 8968 10482 12108 3876 4489 5139 5115 5933 6803 6260 7274 8355 7345 8550 9836 8387 9778 11267 9397 10972 12662 4047 4684 5359 5342 6193 7097 6540 7594 8717 7674 8926 10261 8763 10207 11752 9817 11452 13204 4214 4875 5575 5566 6449 7386 6814 7908 9071 7997 9294 10677 9131 10628 12227 10229 11923 13736

11144 12627 12556 14254 5309 5963 7037 7919 8658 9763 10214 11539 11725 13271 13206 14973 5567 6250 7381 8302 9081 10232 10710 12089 12292 13898 13839 15674 5820 6530 7718 8675 9495 10691 11196 12628 12846 14512 14459 16360 6067 6804 8047 9040 9899 11139 11671 13154 13388 15113 15065 17032 6309 7072 8370 9398 10296 11579 12137 13670 13920 15702 15660 17690

N O T E : Detector time constant at a reference velocity of 5 ft/sec. For SI Units: 1 ft = 0.305 m 1000 B T U / s e c = 1055 k W

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX C

72E-103

T a b l e C-4-1 (q) I n s t a l l e d S p a c i n g of H e a t Detector: 15 feet F i r e G r o w t h R a t e : 150 Seconds to 1000 B T U / S E C A l p h a : 0.044 B T U / S E C s

T a b l e C-4-I (q) I n s t a l l e d S p a c i n g of H e a t Detector: 15 feet F i r e G r o w t h Rate: 150 Seconds to 1000 B T U / S E C A l p h a : 0.044 B T U / S E C '

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

TAU RTI AT

28.0 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

259 341 423 511 592 674 37t 488 610 718 826 936 463 622 758 900 1021 1161 546 729 900 1044 1212 1368 635 829 1011 1203 1384 1563 703 927 1.138 1345 1549 1750 768 1008 1252 1482 1708 1931 832 1103 1363 1615 1863 2081 902 1189 1471 1745 2015 2242 953 1273 1576 1873 2131 2398 1006 1354 1680 1999

322 447 567 691 819 951 451 610 767 923 1089 1247 560 755 943 1129 1314 1499 658 886 1103 1316 1527 1736 750 1006 1251 1490 1725 1957 834 1120 1391 1654 1912 2166 915 1228 1524 1810 2090 2366 992 1331 1651 1960 2261 2557 1067 1431 1774 2105 2426 2742 1138 1527 1893 2244 2586 2920 1208 1621 2008 2380

407 572 749 930 1120 1321 555 763 972 1186 1404 1637 681 929 1t73 1419 1667 1918 794 1079 1357 1633 1909 2187 899 1219 1528 1832 2136 2440 998 1350 1689 2021 2351 2679 1091 1475 1842 2201 2556 2908 1181 1594 1990 2374 2753 3129 1267 1710 2131 2541 2944 3342 1350 1821 2269 2703 3128 3548 1431 1929 2402 2859

509 731 968 1228 1498 1785 675 942 1216 1501 1798 2107 818 1129 1441 1759 2086 2421 947 1300 1648 2000 2356 2719 1067 1458 1842 2226 2612 3002 1180 1608 2026 2440 2855 3272 1287 1751 2201 2645 3088 3532 1389 1888 2369 2842 3312 3782 1488 2019 2531 3032 3529 4023 1583 2147 2687 3216 3739 4258 1675 2270 2840 3395

627 918 1237 1581 1950 2348 810 1147 1500 1873 2266 2679 970 1354 1747 2154 2575 3014 1116 1545 1978 2419 2872 3337 1251 1724 2195 2670 3154 3649 1378 1893 2400 2910 3425 3948 1499 2053 2597 3139 3685 4237 1615 2208 2786 3360 3936 4516 1726 2356 2968 3574 4179 4786 1834 2500 3145 3782 4415 5050 1938 2640 3317 3983

762 1137 1552 2003 2488 3004 961 1381 1829 2307 2815 3352 1138 1607 2095 2606 3142 3703 1300 1818 2347 2894 3461 4049 1450 2016 2586 3169 3768 4385 1592 2203 2814 3433 4064 4712 1727 2382 3032 3687 4351 5028 1857 2554 3242 3932 4628 5335 1981 2720 3445 4169 4897 5634 2101 2881 3642 4399 5159 5925 2218 3037 3834 4624

917 1390 1916 2492 3112 3774 1129 1645 2204 2806 3449 4132 1322 1889 2487 3121 3791 4497 1500 2118 2759 3428 4129 4861 1666 2335 3019" 3726 4458 5219 1822 2541 3268 4012 4779 5570 1972 2738 3507 4289 5090 5912 2115 2928 3738 4558 5392 6246 2253 3111 3962 4818 5687 6571 2386 3288 4179 5072 5974 68g0 2515 3461 4390 5319

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

28.0 .

.

.

.

.

.

.

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

25 56 40 25 56 60 25 56 80 25 56 100 25 56 120 25 56 140 50 112 40 50 112 60 50 112 80 50 112 100 50"112 120 50 112 140 75 168 40 75 168 60 75 168 80 75 168 100 75 168 120 75 168 140 100 224 40 100 224 60 100 224 80 100 224 100 100 224 120 100 224 140 125 280 40 125 280 60 125 280 80 125 280 100 125 280 120 125 280 140 150 335 40 t50 335 60 150 335 80 150 335 100 150 335.120 150 335 140 175 391 40 175 391 60 175 391 80 175 391 100 175 391 120 175 391 140 200 447 40 200 447 60 200 447 80 200 447 100 200 447 120 200 447 140 225 503 40 225 503 60 225 503 80 225 503 100 225 503 120 225 503 140 250 559 40 250 559 60 250 559 80 250 559 100 250 559 120 250 559 140 275 615 40 275 615 60 275 615 80 275 615 100

4.0 .

275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

2266 2550 1071 1434 1782 2089 2398 2699 1128 1513 1883 2202 2528 2846 1184 1591 1983 2312 2655 2989 1239 1667 2049 2421 2780 3131 1293 1743 2139 2528 2904 3271

2741 3094 1276 1712 2121 2512 2892 3264 1342 1801 2230 2641 3040 3429 1407 1888 2338 2767 3184 3591 1470 1973 2442 2891 3325 3749 1532 2056 2545 3012 3464 3905

3307 3748 1509 2034 2532 3012 3482 3944 1586 2137 2658 3161 3652 4135 1661 2238 2782 3307 3819 4322 1734 2336 2903 3450 3982 4505 1806 2432 3022 3590 4143 4684

3943 4487 1765 2391 2988 3570 4142 4709 1853 2508 3133 3740 4337 4927 1938 2623 3274 3906 4527 5140 2022 2735 3413 4070 4713 5349 2104 2845 3549 4230 4896 5554

4645 5306 2040 2776 3484 4180 4869 5556 2139 2908 3648 4372 5088 5801 2235 3038 3808 4560 5303 6041 2330 3165 3964 4744 5513 6276 2423 3289 4118 4925 5719 6507

5414 6209 2332 3188 4020 4843 5664 6487 2443 3337 4203 5057 5907 6759 2551 3482 4381 5266 6146 7026 2657 3623 4556 5472 6380 7287 2761 3763 4727 5673 6610 7544

6254 7201 2641 3629 4597 5560 6528 7506 2764 3793 4798 5796 6797 7804 2884 3953 4995 6027 7060 8098 3001 4111 5188 6254 7318 8385 3116 4265 5378 6477 7572 8669

N O T E : Detector time constant at a reference velocity of 5 ft/sec. F o r S I Units: 1 ft = 0 . 3 0 5 m 1000 B T U / s e c = 1055 k W

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

7 2 E - 104

AUTOMNI'IC FIRE DETECTORS

T a b l e C-4-1(r) Installed Spacing of H e a t Detector: 15 feet Fire Growth Rate: 300 Seconds to 1000 B T U / S E C Alpha: 0.011 B T U / S E C '

T a b l e C--4-1(r) Installed Spacing of H e a t Detector: 15 feet Fire Growth Rate: 300 Seconds to 1000 B T U / S E C Alpha: 0.011 B T U / S E C s

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

TAU RTI AT

28.0 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

56 40 56 60 56 80 56 100 56 120 56 140 112 40 112 60 112 80 112 100 112 120 112 140 168 40 168 60 168 80 168 100 168 120 168 140 224 40 224 60 224 80 224 100 224 120 224 140 280 40 280 60 280 80 280 100 280 120 280 140 335 40 335 60 335 80 335 100 335 120 335 140 391 40 391 60 391 80 391 100 391 120 391 140 447 40 447. 60 447 80 447 100 447 128 447 140 503 40 503 60 503 80 503 100 503 120 503 140 559 40 559 60 559 80 559 100 559 120 559 140 615 40 615 60 615 80 615 100

156 215 275 337 403 469 221 300 378 456 538 617 276 373 467 564 656 748 326 439 554 658 763 874 371 500 627 746 870 980 414 557 697 829 958 1088 454 617 764 911 1047 1191 493 668 828 982 1137 1289 530 718 894 1058 1222 1385 567 766 950 1129 1305 1478 609 813 1006 1199

207 297 394 498 608 725 279 394 508 626 749 877 342 475 611 745 882 1022 399 551 700 850 1006 1160 452 621 787 951 1117 1289 502 688 869 1047 1226 1405 549 752 947 1139 1331 1522 595 812 1022 1228 1431 1635 639 871 1095 1313 1529 1744 681 928 1165 1396 1623 1849 722 983 1233 1476

273 407 553 713 885 t069 353 508 674 847 1029 1222 426 602 784 976 1172 1376 491 688 888 1093 1303 1525 552 769 987 1207 1432 1663 610 846 1081 1317 1556 1800 665 919 1170 1422 1675 1932 717 990 1257 1523 1790 2060 768 1057 1340 1621 1902 2184 817 1123 1421 1716 2010 2305 864 1187 1500 1808

353 543 754 984 1234 1501 442 650 876 1121 1381 1657 523 753 996 1254 1526 1816 597 850 1112 1385 1671 1969 666 941 1222 1512 1812 2123 732 1028 1327 1633 1949 2273 794 1111 1428 1751 2081 2420 854 1191 1526 1865 2210 2562 912 1268 1621 1976 2335 2701 968 1343 1713 2083 2458 2837 1022 1416 1802 2188

451 706 997 1314 1657 2026 545 819 1121 1450 1808 2186 634 930 1249 1591 1957 2345 716 1036 1373 1731 2109 2508 794 1137 1493 1868 2260 2671 867 1233 1610 2001 2408 2832 938 1326 1722 2130 2553 2991 1005 1415 1831 2256 2695 3146 1070 1-502 1937 2379 2833 3299 1133 1586 2039 2499 2968 3449 1194 1668 2140 2616

565 900 1280 1700 2155 2648 664 1017 1411 1843 2309 2808 760 1134 1544 1988 2466 2975 850 1248 1676 2135 2624 3144 935 1358 1805 2280 2783 3314 1017 1464 1931 2423 2941 3484 1095 1566 2054 2563 3096 3653 1170 1665 2173 2700 3249 3820 1242 1760 2289 2835 3399 3984 1313 1854 2403 2966 3547 4147 1381 1945 2514 3095

697 1125 1612 2151 2736 3365 801 1246 1747 2298 2895 3535 902 1368 1885 2449 3057 3707 999 1489 2023 2601 3221 3882 1092 1606 2159 2753 3386 4059 1181 1721 2294 2904 3552 4236 1267 1832 2426 3054 3716 4413 1349 1940 2555 3201 3879 4589 1429 2044 2681 3346 4040 4764 1506 2147 2805 3488 4198 4938 1582 2247 2926 3628

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

28.0

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

.

275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 1385 140 1569 40 642 60 867 80 1066 100 1 2 6 7 120 1464 140 1 6 5 8 40 674 60 907 80 1122 100 1334 120 1541 140 1 7 4 6 40 706 60 947 80 1177 100 1 3 9 9 120 1 6 1 7 140 1819 40 738 60 988 80 1231 100 1464 120 1693 140 1900 40 769 60 1 0 3 0 80 1284 100 1528 120 1767 140 1 9 8 0

1715 1952 762 1037 1299 1554 1805 2053 801 1090 1364 1631 1892 2151 839 1141 1428 1706 1978 2247 877 1191 1490 1779 2062 2341 913 1241 1551 1851 2144 2433

2116 2423 910 1249 1576 1899 2219 2538 956 1310 1651 1987 2319 2651 1000 1369 1725 2073 2418 2761 1043 1427 1796 2158 2515 2870 1085 1484 1867 2241 2610 2976

2577 2970 1075 1486 1890 2291 2694 3100 1127 1556 1975 2391 2808 3227 1177 1624 2058 2489 2920 3352 1226 1690 2140 2586 3030 3475 1275 1755 2221 2680 3138 3596

3101 3596 1254 1748 2238 2731 3231 3740 1312 1826 2334 2843 3358 3881 1369 1902 2427 2953 3483 4021 1425 1977 2520 3061 3606 4158 1480 2051 2610 3168 3727 4293

3692 4306 1448 2033 2622 3221 3834 4464 1513 2120 2728 3345 3975 4619 1576 2205 2833 3467 4113 4772 1638 2289 2935 3587 4248 4923 1700 2371 3036 3705 4382 5071

4355 5109 1655 2344 3045 3765 4509 5279 1727 2440 3161 3901 4661 5446 1798 2534 3276 4034 4812 5612 1866 2626 3388 4165 4960 5775 1934 2716 3499 4294 5106 5937

NOTE: Detector time constant at a reference velocity of 5 ft/sec. For S1 Units:

1 ft = 0.30.5 m 1000 BTU/sec -- 1055 kW

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX C

7 2 E - 105

Table C-4-1(s) Installed Spacing of Heat Detector: 15 feet Fire Growth Rate: 500 Seconds m I000 B T U / S E C

Table C.-4-1(s) Installed Spacing of Heat De~cmr: 15 ~ e t Fire Growth Rate: 500 Seconds to 1000 B T U / S E C Alpha: 0.004 B T U / S E C s

Alpha:

0.004 B T U / S E C I

CEILING HEIC-i~IT IN FEET

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

24.0 .

.

.

FIRE SIZE AT DETECTOR RESPONSE (BTU 25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 112 60 160 80 210 100 264 120 321 140 381 40 155 60 216 80 278 100 341 120 408 140 474 40 192 60" 265 80 337 100 411 120 486 140 561 40 226 60 309 80 392 100 477 120 559 140 642 40 257 60 351 80 443 100 537 120 627 140 718 40 286 60 390 80 491 100 593 120 691 140 790 40 313 60 427 80 541 100 647 120 753 140 863 40 340 60 463 80 584 100 698 120 812 140 926 40 365 60 497 80 626 100 748 120 873 140 988 40 390 60 530 80 667 100 796 120 925 140 1052 40 414 60 567 80 706 100 843

156 235 323 419 523 633 204 295 392 496 606 722 245 351 458 571 688 811 283 400 521 642 768 898 319 448 579 710 844 982 353 492 632 776 918 1063 385 535 684 834 989 1142 416 577 735 894 1053 1218 445 617 784 951 1~19 1292 474 655 832 1007 1182 1359 502 693 878 1062

215 337 474 625 789 965 267 399 544 702 872 1053 313 460 614 780 956 1143 356 514 682 857 1041 1234 397 568 745 931 1123 1324 436 619 807 1000 1204 1412 472 668 866 1070 1279 1499 508 715 924 1137 1355 1579 542 761 980 1202 1429 1661 575 806 1035 1266 1501 1741 607 849 1088 1328

289 464 664 884 1124 1381 342 528 735 962 1208 1471 393 590 808 1042 1294 1563 442 652 878 1123 1381 1656 487 711 948 1199 1469 1750 531 768 1016 1277 1551 1840 573 823 1082 1353 1636 1931 613 876 1147 1427 1719 2022 652 928 1210 1500 1800 2112 690 978 1271 1571 1880 2200 726 1027 1331 1641

379 619 894 1198 1530 1887 433 683 967 1279 1617 1980 488 749 1040 1358 1705 2074 541 814 1115 1441 1792 2170 591 878 1189 1524 1882 2262 640 941 1262 1606 1972 2359 686 1001 1334 1687 2061 2455 731 1060 1405 1768 2150 2552 775 1117 1474 1847 2238 2647 817 1173 1542 1925 2325 2742 858 1228 1608 2001

TAU RTI AT

28.0

.

484 801 1164 1571 2013 2488 541 868 1239 1651 2099 2580 598 936 1316 1735 2190 2677 654 1004 1393 1820 2281 2775 709 1072 1471 1906 2374 2874 762 1139 1549 1992 2467 2973 813 1204 1626 2078 2561 3074 863 1269 1701 2163 2654 3174 911 1331 1776 2248 2748 3275 958 1393 1850 2332 2840 3375 1004 1453 1922 2415

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

28.0

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

SEC) 606 1013 1480 2001 2570 3183 665 1082 1558 2087 2663 3282 724 1152 1637 2173 2756 3382 784 1223 1717 2261 2851 3484 842 1294 1798 2350 2947 3586 899 1365 1879 2439 3043 3689 954 1435 1960 2529 3140 3792 1008 1504 2040 2618 3238 3896 1061 1571 2119 2707 3335 4001 1112 1638 2198 2796 3432 4106 1162 1703 2276 2885

4.0 .

275 615 275 615 300 671 300 671 300 671 300 671 300 671 300 671 325 727 325 727 325"727 325 727 325 727 325 727 350 783 350 783 350 783 350 783 350 783 350 783 375 839 375 839 375 839 375 839 375 839 375 839 400 894 400 894 400 894 400 894 400 894 400 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

978 1112 437 598 745 893 1030 1172 460 628 783 935 1083 1230 482 658 820 977 1134 1287 504 687 863 1020 1183 1343 525 715 895 1064 1232 1398

1245 1428 529 729 923 t115 1305 1496 555 765 968 1167 1365 1563 581 800 1011 1218 1423 1628 607 834 1053 1268 1480 1692 632 868 1095 1317 1536 1754

1572 1820 639 891 1140 1389 1641 1897 669 932 1191 1449 1709 1972 699 972 1240 1507 1776 2046 729 1012 1289 1565 1841 2119 758 1051 1337 1621 1905 2191

1959 2287 762 1075 1389 1709 2036 2372 797 1122 1447 1776 2112 2456 831 1168 1503 1842 2187 2539 865 1213 1558 1907 2261 2621 898 1257 1613 1971 2333 2702

2411 2836 899 1282 1673 2077 2495 2929 938 1334 1737 2151 2579 3021 976 1386 1800 2224 2661 3112 1014 1436 1862 2296 2742 3201 1051 1486 1922 2367 2823 3290

2932 3475 1048 1512 1993 2496 3023 3574 1092 1570 2063 2577 3113 3673 1135 1627 2132 2657 3203 3770 1177 1683 2201 2736 3291 3867 1218 1738 2268 2814 3379 3964

3529 4210 1212 1767 2353 2972 3626 4315 1260 1830 2429 3059 3722 4419 1307 1893 2504 3145 3818 4523 1353 1954 2578 3230 3912 4626 1399 2014 2651 3314 4006 4729

N O T E : Detector t i m e constant at a reference velocity of 5 ft/sec. For SI Units:

1 ft = 0.305 m 1000 B T U / s e c -- 1055 k W

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

7 2 E - 106

AUTOMATIC FIRE DETECTORS

Table C-4-1 (t) Installed Sparing of Heat Detector: 15 ~ e t Fire Growth R a ~ : 600 Seconds to 1000 B T U / S E C Alpha: 0.003 B T U / S E C =

T a b ~ C-4-1(0 l m m H e d Sparing of Heat Detector: 15 feet Fire Growth R a ~ : 600 Seconds to 1000 B T U / S E C Alpha: 0.005 B T U / S E C j

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI ~T .

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

8,0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

.

.

TAU RTI ~T

28.0 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 '40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

100 145 193 245 300 358 137 193 251 310 372 437 170 236 303 370 441 511 199 275 350 426 504 581 226 311 394 480 563 646 251 345 436 529 618 709 275 377 476 576 672 769 298 408 515 621 723 826 321 438 555 664 773 885 342 467 590 706 822 937 363 495 625 747

143 220 305 399 501 610 184 270 363 462 569 683 219 317 418 525 638 756 252 361 472 586 705 829 283 401 522 644 770 901 313 440 570 701 834 970 340 477 614 755 895 1038 367 513 658 803 954 1104 393 548 700 853 1012 1168 418 581 742 902 1063 1230 442 614 782 949

201 319 454 603 765 938 244 371 512 666 832 1011 283 421 570 730 902 1085 320 468 627 794 972 1160 355 514 683 857 1041 1234 389 558 734 919 1110 1309 421 601 785 976 1177 1382 452 642 835 1034 1239 1454 481 681 883 1090 1303 1521 510 720 931 1145 1365 1590 538 757 977 1199

273 444 640 858 1095 1350 316 497 699 922 1164 1424 360 548 759 988 1235 1499 401 600 819 1054 1307 1576 440 650 876 1121 1379 1653 478 699 934 1184 1451 1731 514 746 990 1248 1520 1808 549 792 1046 1311 1590 1881 582 837 1100 1373 1659 1957 615 880 1152 1434 1727 2032 647 923 1204 1494

360 596 867 1168 1496 1850 405 650 927 1234 1568 1927 450 703 987 1301 1641 2004 495 757 1049 1367 1714 2083 538 811 1110 1436 1786 2163 579 864 1172 1504 1860 2239 619 915 1233 1573 1935 2319 658 966 1293 1640 2009 2399 696 1015 1351 1707 2083 2479 732 1063 1409 1773 2156 2559 768 1110 1466 1839

462 775 1135 1536 1973 2445 509 830 1195 1602 2045 2525 557 885 1258 1671 2119 2601 604 942 1322 1.741 2~'95 2682 650 998 1386 1811 2271 2763 695 1055 1451 1882 2348 2845 738 1110 1515 1954 2425 2928 781 1164 1579 2025 2503 3011 822 1218 1642 2096 2580 3094 863 1270 1704 2166 2658 3177 902 1322 1766 2236

582 983 1445 1961 2525 3134 630 1040 1509 2032 2602 3216 679 1097 1574 2103 2679 3299 728 1156 1640 2175 2757 3382 777 1215 1706 2248 2836 3466 825 1273 1773 2322 2915 3551 872 1332 1840 2395 2995 3636 918 1390. 1907 2470 3075 3722 963 1447 1974 2544 3156 3808 1007 1504 2040 2618 3237 3895 1051 1559 2106 2692

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

.

.

28.0

.

FIRE SIZE AT DETECTORRESPONSE(6TU / SEC)

FIRE SIZE AT DETECTORRESPONSE (BTU / SEC) 25 56 25 56 25 56 25 56 25 56 25 56 50 112 50 112 50 112 50 112 50 112 50 112 75 168 75 168 75 168 75 168 75 168 75 168 100 224 100 224 100 224 100 224 100 224 100 224 125 280 125 280 125 280 125 280 125 280 125 280 150 335 150 335 150 335 150 335 150 335 150 335 175 391 175 391 175 391 175 391 175 391 175 391 200 447 200 447 200 447 200 447 200 447 200 447 225 503 225 503 225 503 225 503 225 503 225 503 250 559 250 559 250 559 250 559 250 559 250 559 275 615 275 615 275 615 275 615

4.0 .

275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

873 1117 989 1286 383 466 523 646 658 821 787 996 916 1170 1041 1345 403 489 554 677 691 860 826 1041 959 1222 1092 1403 423 512 580 707 723 898 869 1085 1003 1272 1141 1460 442 534 605 737 755 934 904 1129 1047 1322 1190 1515 460 555 630 767 786 971 939 .1171 1089 1371 1237 1570

1426 1658 565 794 1022 1252 1486 1724 592 830 1066 1303 1544 1789 618 865 1109 1354 1602 1854 644 899 i151 1404 1659 1917 669 933 1193 1453 1715 1979

1795 2106 678 964 1255 1553 1861 2179 708 1005 1305 1611 1926 2251 738 1045 1353 1668 1991 2322 767 1084 1401 1724 2054 2392 796 1122 1448 1779 2117 2462

2229 2638 803 1157 1522 1903 2301 2716 837 1202 1577 1967 2372 2794 871 1248 1631 2030 2443 2871 903 1290 1685 2092 2512 2948 936 1333 1737 D2153 2581 3024

2735 3261 941 1373 1827 2306 2812 3344 979 1423 1887 2375 2888 3427 1016 1472 1946 2443 2964 3509 1053 1520 2004 2510 3039 3591 1088 1567 2062 2577 3113 3673

3318 3982 1093 1614 2171 2766 3398 4068 1134 1668 2235 2839 3479 4155 1175 1722 2299 2911 3559 4242 1215 1774 2362 2984 3639 4329 1255 1826 2425 3055 3718 4415

NOTE: Detector time constant at a reference velocity of 5 ft/sec. For SI Units: I ft = 0 . $ 0 5 m 1000 BTU/sec = 1055 kW

1990Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX C

72E-107

T a b l e C-4-I (u) Ins t a l l e d Spacing of H e a t Detector: 20 feet Fire Growth Rate: 50 Seconds to I000 B T U / S E C Alpha: 0.400 B T u / S E C '

T a b l e C-4-1 (u) Installed Spacing of Heat Detector: 20 feet Fire Growth Rate: 50 Seconds to 1000 B T U / S E C Alpha: 0.400 B T u / S E C '

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

TAU RTI &T

28.0

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

906 1122 1351 1578 1804 2029 1236 1603 1960 2311 2657 3002 1543 2035 2514 2986 3362 3768 1831 2445 3048 3518 4022 4514 2109 2845 3451 4060 4651 5095 2379 3243 3886 4583 5111 5716 2646 3496 4309 4948 5642 6313 2910 3821 4603 5395 6155 6891 3174 4140 4969 5828 6654 7454 3323 4454 5325 6251 7142 8006 3543 4628 5672 6665'

1047 1221 1424 1650 1898 2169 1352 1602 1890 2214 2575 2974 1649 1975 2354 2786 3271 3813 1940 2347 2825 3373 3994 4693 2229 2722 3305 3979 4747 5616 2519 3103 3797 4605 5532 6583 1478 1711 1969 2251 2556 2883 1922 2239 2596 2989 3417 3881 2340 2744 3202 3710 4270 4881 2744 3236 3800 4431 5129 5898 3139 3723 4397 5156 6002 6940 3527 4207 4996 5891 6893 8010 1841 2 1 1 9 2425 2756 3110 3487 2402 2775 3192 3648 4139 4666 2926 3396 3925 4508 5141 5824 3429 3995 4641 5355 6135 6983 3912 4582 5347 6197 7131 8153 4387 5162 6050 7041 8136 9340 2165 2483 2830 3205 3605 4028 2833 3255 3726 4239 4789 5374 3454 3980 4576 5227 5929 6682 4039 4678 5400 6192 7051 7977 4608 5358 6208 7145 8166 9273 5164 6026 7007 8094 9282 10577 2465 2816 3202 3618 4059 4525 3231 3696 4219 4784 5388 6029 3934 4520 5177 5892 6660 7478 4606 5309 6103 6969 7903 8904 5254 6076 7007 8027 9131 10321 5877 6826 7897 9074 10354 11739 2746 3129 3550 4004 4484 4990 3607 4110 4680 5295 5950 6643 4389 5026 5742 6517 7346 8228 5139 5902 6763 7700 8705 9778 5853 6751 7758 8857 10042 11312 6553 7580 8736 10000 11368 12841 3014 3424 3880 4369 4887 5430 3952 4502 5117 5780 6483 7226 4821 5 5 0 7 6277 7110 7999 8940 5637 6465 7391 8394 9468 10610 6428 7392 8473 9648 10910 12257 7194 8296 9533 10882 12335 13893 3270 3706 4194 4718 5271 5850 4 2 8 9 4877 5535 6243 6993 7783 5227 5966 6790 7678 8622 9621 6120 7 0 0 4 7991 9059 10198 11408 6978 8006 9157 10405 11741 13164. 7 8 0 9 8983 10298 11727 13263 14903 3517 3978 4496 5052 5639 6254 4613 5237 5937 6688 7483 8318 5623 6408 7282 8223 9223 10277 6585 7523 8569 9699 10902 12176 7508 8598 9816 11134 12542 14038 8402 9644 11034 12541 14157 15879 3744 4239 4788 5375 5995 6643 4927 5586 6325 7118 7956 8836 6006 6835 7759 8751 9803 10911 7034 8024 9128 10317 11582 12919 8021 9170 10453 11839 13317 14885 8976 10283 11746 13329 15023 16823 3973 4492 5070 5688 6339 7019 5221 5 9 2 3 6701 7534 8414 9337 6377 7250 8221 9262 10366 11526 7471 8511 9670 10918 12242 13640

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

28.0

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

FIRE SIZE AT DETECTORRESPONSE(BTU / SEC) 25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

4.0 .

275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

7621 8519 9725 11072 12524 14070 15706 8373 9525 10904 12438 14095 15863 17740 3759 4195 4738 5344 5992 6674 7385 4901 5516 6251 7066 7939 8860 9824 6013 6739 7653 8670 9760 10913 12124 7071 7896 8984 10198 11502 12885 14342 7931 8996 10265 11674 13190 14802 16506 8867 10066 11508 13111 14839 16682 18634 3972 4411 4 9 7 8 5612 6288 7000 7742 5169 5803 6571 7423 8334 9294 10299 6348 7092 8046 9108 10245 11446 12707 7472 8311 9446 10712 12071 13511 15026 8362 9468 10792 12261 13840 15517 17286 9350 10593 12097 13767 15566 17481 19506 4182 4623 5213 5873 6577 7318 8089 5431 6083 6883 7771 8719 9718 10763 6678 7437 8431 9536 10719 11967 13277 7706 8707 9897 11215 12628 14123 15695 8784 9929 11307 12835 14475 16215 18049 9824 11109 12674 1.4409 16277 18261 20359 4392 4830 5442 6128 6860 7629 8430 5690 6358 7189 8112 9097 10133 11216 7003 7775 8807 9955 11182 12477 13834 8067 9103 10339 11707 13173 14722 16349 9199 10381 11811 13396 15097 16899 18796 10289 11615 13238 15038 16972 19026 21194 4470 5021 5666 6378 7137 7933 8763 5945 6627 7489 8445 9466 10540 11661 7326 8107 9175 10365 11637 12977 14380 8423 9491 10772 12190 13707 15309 16991 9606 10824 12306 13947 15707 17569 19528 10747 12111 13791 15654 17654 19776 22013

NOTE: Detector time constant at a reference velocity of 5 ft/sec. F o r S l Units:

1 ft = 0 . 3 0 5 m 1000 BTU/sec = 1055 kW

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E- 108

AUTOMATIC FIRE DETECTORS

Tab~

T a b l e C,-4-I (v)

C ~ - I (v)

Installed Spacing of Heat Detector: 20 feet Fire Growth Rate: 150 Seconds to I000 B T U / S E C Alpha: 0.044 B T U / S E C s

Installed Spacing of Heat Detector: 20 feet Fire Growth RaM: 150 Seconds to 1000 B T U / S E C Alpha: 0.044 B T U / S E C '

CEILING HEIGHT IN FEET TAU RTI &T .

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

.

20.0 .

.

.

.

.

.

CEILING HEIGHT IN FEET

24.0 .

.

.

.

.

.

TAU RTI AT

28.0 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

40 379 60 506 80 635 100 759 120 889 140 1009 40 540 60 723 80 898 100 1059 120 1226 140 1393 40 684 60 906 80 1111 100 1319 120 1525 140 1729 40 801 60 1061 80 1312 100 1558 120 1801 140 2043 40 915 60 1211 80 1501 100 1784 120 2064 140 2304 40 1007 60 1355 80 1681 100 2002 120 2278 140 2570 40 1114 60 1492 80 1856 100 2178 120 2504 140 2824 40 1211 60 1 6 2 6 80 2028 100 2367 120 2722 140 3070 40 1305 60 1757 80 2157 100 2551 120 2934 140 3309 40 1396 60 1886 80 2308 100 2730 120 3140 140 3542 40 1486 60 2013 80 2454 100 2905

456 629 805 994 1182 1378 635 863 1087 1312 1540 1771 787 1063 1331 1597 1862 2128 923 1244 1553 1856 2157 2457 1049 1412 1759 2098 2432 2763 1167 1570 1953 2326 2691 3053 1280 1720 2138 2542 2939 3330 1387 1864 2315 2750 3176 3596 1490 2002 2485 2951 3405 3852 1590 2136 2650 3145 3627 4100 1687 2267 2810 3334

556 786 1028 1285 1561 1845 754 1041 1331 1628 1934 2250 923 1263 1600 1939 2283 2634 1075 1465 1846 2225 2607 2992 1216 1652 2075 2493 2911 3330 1348 1828 2291 2747 3199 3651 1474 1996 2497 2988 3475 3959 1594 2156 2695 3220 3739 4254 1710 2311 2885 3444 3995 4540 1821 2461 3070 3661 4242 4817 1930 2606 3249 3872

675 975 1299 1646 2017 2417 891 1249 1619 2004 2407 2828 1078 1493 1911 2339 2780 3234 1247 1716 2182 2653 3132 3621 1404 1923 2435 2947 3465 3989 1551 2119 2675 3227 3782 4342 1691 2306 2904 3495 4086 4680 1825 2485 3123 3753 4379 5007 1954 2657 3335 4001 4663 5323 2078 2824 3540 4242 4937 5630 2199 2985 3740 4477

812 1197 1618 2074 2564 3085 1045 1487 1952 2444 2963 3510 1250 1751 2266 2800 3355 3933 1436 1996 2560 3138 3732 4345 1609 2224 2837 3459 4093 4742 1772 2440 3101 3765 4438 5124 1927 2646 3352 4059 4771 5493 2075 2843 3594 4342 5092 5850 2218 3034 3828 4616 5404 6196 2356 3218 4055 4881 5706 6533 2490 3397 4275 5140

969 1452 1988 2571 3199 3869 1217 1756 2333 2950 3606 4301 1439 2040 2666 3324 4014 4739 1642 2304 2982 3684 4413 5171 1832 2553 3282 4029 4798 5592 2011 2789 3569 4361 5171 6002 2181 3014 3843 4680 5531 6399 2343 3231 4108 4988 5880 6785 2500 3440 4364 5287 6218 7161 2652 3642 4612 5578 6548 7528 2799 3839 4853 5860

1145 1743 2410 3139 3926 4766 1406 2058 2764 3526 4341 5207 1645 2359 3114 3914 4762 5656 1866 2643 3450 4294 5179 6105 2072 2911 3772 4662 5587 6548 2266 3167 4080 5017 5984 6982 2451 3412 4377 5361 6369 7406 2629 3647 4664 5694 6744 7819 2800 3875 4942 6017 7110 8224 2966 4095 5212 6332 7466 8619 3126 4310 5474 6639

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

28.0 .

.

.

.

.

.

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 56 25 56 25 56 25 56 25 56 25 56 50 112 50 112 50 112 50 112 50 112 50 112 75 168 75 168 75 168 75 168 75 168 75 168 100 224 100 224 100 224 100 224 100 224 100 224 125 280 125 280 125 280 125 280 125 280 125 280 150 335 150 335 150 335 150 335 150 335 150 335 175 391 175 391 175"391 175 391 175 391 175 391 200 447 200 447 200 447 200 447 200 447 200 447 225 503 225 503 225 503 225 503 225 503 225 503 250 559 250 559 250 559 250 559 250 559 250 559 275 615 275 615 275 615 275 615

4.0 .

275 615 275 615 300 671 300 671 300 671 300 671 300 671 300 671 325 727 325 727 325 727 325 727 325 727 325 727 350 783 350 783 350 783 350 783 350 783 350 783 375 839 375 839 375 839 375,839 375 839 375 839 400 894 400 894 400 894 400 894 400 894 400 894

NOTE:

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

3342 3729 1574 2100 2598 3076 3541 3942 1661 2213 2739 3244 3690 4150 1746 2324 2877 3411 3871 4354 1831 2432 3014 3530 4050 4554 1916 2539 3149 3683 4225 4751

3843 4341 1782 2392 2966 3517 4053 4577 1874 2516 3119 3697 4257 4806 1964 2637 3268 3872 4458 5031 2052 2755 3413 4043 4654 5251 2139 2871 3557 4212 4847 5467

4483 5086 2035 2747 3423 4077 4717 5349 2138 2885 3593 4277 4946 5605 2239 3020 3760 4473 5170 5856 2337 3152 3923 4665 5390 6102 2433 3282 4082 4854 5605 6343

5205 5929 2317 3143 3934 4705 5465 6220 2431 3297 4123 4928 5720 6505 2543 3447 4308 5146 5969 6784 2653 3594 4490 5360 6213 7057 2761 3738 4668 5569 6453 7325

6000 6861 2620 3571 4489 5392 6288 7182 2747 3741 4699 5638 6568 7496 2871 3908 4904 5879 6843 7803 2992 4071 5105 6115 7113 8105 3111 4230 5301 6347 7378 8401

6869 7886 2942 4030 5088 6136 7184 8236 3082 4217 5318 6406 7491 8578 3218 4400 5543 6670 7792 8914 3352 4578 5763 6929 8087 9244 3483 4754 5980 7183 8377 9568

7814 9005 3283 4518 5730 6939 8155 9383 3435 4722 5981 7232 8488 9755 3584 4922 6226 7520 8815 10119 3730 5117 6466 7802 9136 10477 3873 5308 6702 8079 9452 10829

D e t e c t o r t i m e c o n s t a n t at a r e f e r e n c e velocity of 5 ft/sec.

F o r S 1 Units:

1 ft = 0 . 8 0 5 m 1000 B T U / s e c = 1055 k W

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

AVPENI)IX c

72E- 109

Table C-4-I (w) Installed Spacing of Heat Detector: 20 feet Fire Growth Rate: 300 Seconds to 1000 B T U / S E C Alpha: 0.011 B T U / S E C '

Table C - 4 - l ( w ) Installed S p a c i n g o f Heat Detector: 20 feet Fire Growth R a ~ : 300 Seconds to 1000 B T U / S E C Alpha: 0.011 B T U / S E C s

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI.&T .

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

.

.

.

.

28.0

.

TAU RTI &T

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

232 322 415 513 613 717 326 445 567 685 805 928 405 556 695 835 975 1118 477 650 812 971 1133 1294 543 737 922 1101 1280 1459 611 820 1020 1223 1420 1616 668 903 1122 1339 1554 1768 724 973 1216 1452 1685 1902 777 1045 1308 1561 1812 2040 830 1120 1397 1668 1919 2173 887 1189 1484 1773

294 429 572 726 890 1065 395 557 725 902 1082 1270 483 673 864 1059 1259 1469 562 778 992 1208 1427 1650 636 876 1112 1348 1586 1827 705 968 1226 1481 1738 1995 771 1057 1334 1609 1883 2157 834 1141 1439 1731 2022 2313 895 1223 1539 1850 2157 2464 954 1302 1637 1964 2288 2611 1011 1379 1731 2076

, 375 566 774 1002 1247 1508 484 700 929 1174 1436 1709 580 824 1077 1342 1618 1907 668 940 1217 1502 1797 2102 750 1049 1349 1655 1968 2291 827 1151 1474 1801 2133 2473 901 1250 1595 1942 2293 2650 971 1344 1711 2077 2447 2821 1039 1435 1822 2208 2596 2987 1105 1523 1931 2336 2741 3149 1169 1609 2037 2460

473 731 1022 1338 1681 2047 588 870 1177 1509 1865 2248 693 1004 1333 1683 2054 2445 790 1129 1482 1852 2240 2647 880 1248 1625 2017 2423 2846 966 1361 1763 2175 2601 3040 1048 1470 1895 2328 2773 3230 1126 1574 2022 2477 2941 3416 1202 1675 2146 2621 3104 3597 1275 1773 2266 2762 3264 3774 1346 1868 2383 2899

589 928 1311 1733 2190 2685 709 1071 1471 1908 2378 2881 821 1211 1632 2085 2570 3085 927 1346 1790 2262 2763 3292 1026 1474 1943 2436 2954 3498 1120 1598 2091 2605 3142 3702 1210 1716 2235 2770 3326 3904 1296 1831 2374 2931 3507 4102 1380 1942 2509 3088 3684 4296 1460 2049 2640 3242 3857 4487 1539 2154 2769 3391

723 876 1157 1419 1649 2037 2193 2720 2784 3464 3418 4264 847 1003 1303 1567 1 8 1 2 2203 2371 2902 2976 3660 3623 4473 966 1128 1448 1718 1 9 7 7 2372 2552 3087 3171 3860 3831 4685 1 0 7 9 1249 1591 1866 2142 2542 2735 3275 3369 4062 4041 4901 1187 1364 1728 2012 2304 "2711 2916 3462 3567 4265 4254 5118 1289 1474 1861 2154 2462 2877 3095 3649 3763 4469 4466 5337 1 3 8 7 1580 1989 2291 2616 3041 3271 3834 3958 4672 4677 5555 1482 1682 2114 2425 2766 3201 3443 4016 4149 4873 4886 5773 1573 1782 2235 2555 2912 3357 3612 4195 4338 5072 5092 5989 1661 1878 2352 2682 3055 3511 3777 4372 4523 5269 5295 6204 1 7 4 8 1972 2467 2806 3194 3661 3939 4545

8.0 7

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

24.0 .

.

.

.

.

.

.

.

28.0 .

.

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

FIRE SIZE AT DETECTOR RESPONSE (8TU / SEC) 25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

4.0

. . . . . . . . . . . . . . . . . . . . .

275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783, 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

2034 2303 932 1257 1570 1859 2147 2430 977 1324 1654 1956 2258 2554 1023 1389 1737 2050 2366 2676 1073 1453 1803 2142 2472 2795 1119 1517 1880 2233 .2576 2913

2416 2883 2753 3307 1 0 6 6 1231 1453 1692 1824 2140 2185 2581 2540 3021 2892 3461 1120 1292 1 5 2 6 1774 1 9 1 4 2240 2291 2700 2662 .3156 3029 3612 1173 1351 1598 1854 2002 2339 2395 2815 2780 3288 3162 3760 1225 1409 1 6 6 8 1932 2088 2435 2497 2929 2897 3418 3292 3906 1276 1466 1736 2008 2173 2530 2597 3041 3011 3546 3421 4048

3419 3947 1415 1961 2497 3033 3572 4117 1483 2052 2609 3164 3721 4283 1549 2140 2718 3292 3867 4446 1613 2227 2826 3419 .4011 4607 1677 2313 2931 3542 4152 4764

4026 4675 1615 2256 2894 3538 4192 4859 1690 2357 3017 3682 4355 5040 1763 2454 3138 3823 4515 5218 1835 2550 3256 3961 4673 5394 1905 2645 3372 4097 4828 5566

4706 5496 1831 2578 3331 4098 4885 5694 1913 2688 3465 4254 5061 5889 1994 2795 3596 4407 5235 6081 2072 2900 3725 4558 5406 6270 2149 3003 3852 4707 5574 6457

5463 6416 2063 2927 3808 4716 5654 6626 2152 3046 3953 4884 5843 6834 2240 3163 4095 5049 6029 7039 2325 3277 4235 5212 6213 7242 2409 3389 4373 5372 6394 7442

t

N O T E : Detector time constant at For SI Units:

a r e ~ r e n c e velocity of 5 ft/sec.

1 ~ = 0.305 m 1000 B T U / s e c = 1055 k W

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-l

10

AUTOMATIC FIRE I)ETECTORS

T a b l e C-4-1(x) Installed Spacing of Heat Detector: 20 feet Fire G r o w t h R a ~ : 500 Seconds to 1000 B T U / S E C Alpha: 0.004 B T U / S E C *

T a b ~ C-4-1(x) Installed Spacing of H e a t Detector: 20 feet Fire G r o w t h Rate: 500 Seconds m 1000 B T U / S E C Alpha: 0.004 B T U / S E C s

CEILING HEIGHT .IN FEET

CEILING HEIGHT IN FEET TAU RTI &T .

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

8.0 .

.

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

TAU RTI &T

28.0 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

1990 Edition

168 242 322 407 497 592' 230 323 418 517 618 723 284 394 506 617 730 846 332 458 585 709 834 962 377 522 658 795 933 1072 419 578 728 880 1025 1176 459 631 794 955 1116 1277 498 683 863 1030 1202 1374 535 732 921 1103 1286 1468 575 780 978 1174 1367 1559 609 827 1036 1243

226 343 474 617 772 938 290 425 568 721 884 1057 348 499 656 823 996 1177 401 569 741 918 1105 1296 450 634 820 1011 1206 1412 497 697 896 1099 1307 1519 541 756 969 1185 1403 1626 584 813 1040 1267 1497 1730 625 869 1108 1347 1587 1831 665 922 1174 1424 1676 1929 704 974 1238 1500

300 473 668 884 1118 1370 366 553 760 985 1227 1485 429 632 850 1087 1337 1603 487 707 939 1185 1448 1722 541 778 1025 1283 1553 1837 593 847 1107 1378 1659 1952 643 912 1187 1470 1763 2066 690 976 1265 1560 1864 2177 736 1037 1340 1647 1963 2286 781 1097 1413 1733 2059 2393 824 1155 1484 1816

390 631 904 1207 1537 1891 458 711 996 1308 1645 2006 525 792 1087 1407 1755 2124 587 872 1179 1510 1864 2240 647 948 1269 1611 '1975 2359 704 1022 1357 1711 2085 2478 759 1094 1444 1810 2194 2597 811 1164 1527 1906 2302 2714 862 1231 1609 2001 2407 2830 911 1297 1689 2093 2511 2944 959 1361 1767 2184

497 816 1184 1589 2032 2508 567 898 1273 1688 2138 2625 636 981 1367 1790 2249 2739 703 1064 1462 1894 2361 2859 767 1145 1556 1999 2474 2980 829 1225 1649 2103 2588 3102 889 1302 1740 2206 2701 3224 946 1377 1830 2309 2814 3346 1002 1450 1918 2409 2925 3467 1056 1522 2004 2509 3036 3587 1109 1592 2089 2606

622 1033 1505 2030 2603 3220 693 1116 1598 2132 2714 3339 764 1201 1693 2237 2827 3459 835 1286 1790 2343 2941 3581 903 1371 1887 2450 3056 3704 969 1455 1984 2557 3173 3829 1034 1537 2080 2664 3289 3954 1096 1617 2175 2771 3406 4079 1157 1696 2268 2877 3522 4204 1216 1773 2361 2982 3638 4330 1273 1849 2451 3086

764 1280 1875 2537 3260 4040 836 1365 1970 2642 3374 4162 910 1452 2067 2749 3489 4285 983 1540 2166 2857 3606 4410 1055 1627 2266 2966 3724 4536 1126 1715 2365 3076 3843 4663 1194 1801 2465 3186 3962 4790 1261 1886 2564 3297 4083 4919 1326 1970 2663 3407 4203 5048 1390 2052 2760 3517 4323 5177 1452 2133 2857 3626

.

.

.

.

8.0 .

.

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

28.0 .

.

.

.

.

.

.

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

4.0 .

275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

NOTE:

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

1446 1649 643 877 1094 1310 1524 1737 675 919 1150 1376 1601 1814 707 960 1204 1441 1676 1896 738 1002 1257 1505 1750 1977 769 1045 1310 1568 1811 2056

1762 2026 742 1025 1301 1574 1846 2120 779 1075 1362 1646 1928 2212 815 1123 1422 1716 2009 2302 850 1171 1481 1786 2088 2390 884 1217 1538 1854 2166 2478

2154 2498 866 1211 1553 1898 2246 2601 907 1266 1621 1977 2337 2702 947 1320 1688 2056 2426 2801 987 1374 1754 2133 2514 2899 1025 1426 1818 2208 2600 2995

2614 3057 1006 1423 1844 2273 2714 3168 1052 1484 1919 2361 2813 3277 1097 1544 1993 2447 2911 3385 1140 1603 2065 2532 3007 3492 1183 1661 2136 2615 3101 3597

3145 3707 1161 1660 2172 2703 3253 3825 1211 1727 2254 2797 3359 3942 1260 1793 2335 2891 3465 4058 1309 1858 2414 2983 3568 4172 1356 1921 2492 3074 3671 4286

3753 4454 1330 1923 2541 3188 3867 4579 1385 1996 2629 3290 3980 4702 1439 2068 2716 3390 4092 4824 1492 2138 2802 3489 4203 4946 1544 2207 2886 3587 4313 5067

4443 5306 1513 2213 2952 3735 4562 5435 1573 2291 3046 3842 4681 5564 1632 2368 3139 3948 4799 5692 1689 2444 3230 4054 4917 5820 1746 2519 3321 4158 5033 5947

D e t e c t o r t i m e c o n s t a n t a t a r e f e r e n c e velocity o f 5 ft/sec.

F o r S l Units:

1 ft = 0.305 m 1000 B T U / s e c = 1055 k W

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX C

72E-111

T a b l e C-4-1(y)

Tab~

Installed Spacing of Heat Detector: 20 feet Fire Growth Rate: 600 Seconds to 1000 B T U / S E C Alpha: 0.003 B T U / S E C j

CEtLING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI &T .

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

.

TAU RTI &T

28.0 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 "120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

151 222 298 380 467 560 205 290 379 472 569 669 251 352 455 558 664 774 293 408 524 '638 754 876 332 460 587 713 839 968 369 509 648 784 921 1059 404 559 705 852 998 1145 437 604 761 918 1073 1229 470 647 815 980 1146 1311 501 688 871 1042 1216 1390 531 729 918 1102

208 321 449 590 743 906 262 390 527 675 834 1003 312 453 603 760 927 1103 358 513 674 844 1019 1202 400 569 742 921 1108 1300 441 623 808 997 1192 1395 480 675 871 1071 1275 1484 517 725 932 1142 1355 1573 553 773 991 1211 1434 1661 587 819 1049 1278 1510 1746 621 865 1105 1344

280 449 641 854 1085 1334 336 517 717 936 1174 1428 389 582 793 1021 1265 1525 439 645 866 1105 1357 1623 486 706 939 1185 1448 1722 530 765 1010 1266 1535 1817 573 822 1078 1345 1623 1913 615 877 1145 1422 1709 2007 654 930 1210 1497 1794 2100 693 982 1273 1571 1877 2192 731 1032 1335 1643

369 605 874 1173 1499 1850 425 671 949 1255 1588 1945 481 738 1024 1340 1679 2042 534 804 1101 1422 1768 2140 585 869 1176 1507 1860 2235 634 933 1251 1591 1952 2334 681 994 1324 1674 2044 2433 727 1054 1396 1756 2134 2531 771 1112 1466 1836 2224 2629 814 1169 1535 1916 2312 2726 855 1224 1602 1994

474 787 1149 1551 1989 2461 531 855 1223 1632 2079 2558 588 923 1300 1716 2167 2652 645 992 1378 1802 2260 2750 699 1060 1456 1888 2353 2850 752 1127 1534 1974 2447 2950 803 1192 1611 2061 2541 3051 853 1257 1687 2146 2635 3152 901 1319 1762 2232 2729 3253 948 1381 1836 2316 2822 3354 994 1441 1908 2399

595 735 1000 1244 1466 1831 1986 2487 2554 3205 3167 3979 654 794 1069 1314 1543 1910 2071 2574 2646 3299 3265 4080 713 854 1138 1385 1622 1990 2157 2662 2739 3394 3365 4182 771 915 1209 1457 1701 2071 2244 2751 2833 3491 3465 4285 829 975 1279 1529 1781 2153 2332 2841 2928 3587 3566 4389 885 1035 1349 1602 1861 2235 2420 2931 3024 3685 3668 4493 940 1093 1418 1674 1941 2318 2509 3022 3120 3784 3771 4598 994 1150 1486 1746 2021 2401 2598 3114 3217 3883 3875 4704 1046 1206 1554 1816 2100 2483 2687 3206 3313 3982 3979 4810 1097 1260 1620 1886 2178. 2565 2775 3297 3410 4082 4083 4917 1146 1314 1684 1955 2255 2646 2863 3389

4.0 .

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

24.0 .

.

.

.

.

.

.

28.0 .

.

.

.

.

.

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

C-4-l(y)

I n s ~ l l e d Spacing of Heat D e ~ c m r : 20 feet Fire Growth Rate: 600 Seconds m 1000 B T U / S E C Alpha: 0.003 B T U / S E C =

275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

NOTE:

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

1285 1467 565 769 966 1160 1352 1543 594 808 1014 1217 1418 1617 621 846 1062 1274 1482 1691 648 886 1108 1329 1546 1763 675 921 1154 1383 1609 1824

1585 1829 654 909 1159 1408 1658 1911 686 952 1212 1471 1730 1990 717 994 1265 1532 1800 2069 748 1036 1316 1593 1869 2146 778 1077 1366 1652 1937 2222

1958 2282 767 1081 1395 1713 2038 2370 803 1129 1454 1782 2116 2457 838 1176 1512 1850 2194 2543 873 1222 1569 1917 2270 2628 906 1268 1625 1983 2344 2711

2400 2822 896 1278 1668 2070 2486 2916 936 1331 1733 2146 2571 3010 975 1383 1797 2220 2655 3103 1013 1434 1860 2293 2737 3194 1050 1485 1921 2365 2819 3284

2914 3455 1038 1500 1980 2481 3006 3554 1082 1558 2050 2562 3096 3653 1125 1615 2119 2642 3186 3752 1167 1671 2188 2721 3275 3849 1208 1726 2255 2799 3363 3946

3506 4187 1195 1748 2332 2949 3602 4291 1243 1811 2407 3036 3698 4394 1289 1873 2482 3121 3793 4497 1335 1933 2555 3205 3887 4600 1381 1993 2628 3289 3980 4702

4182 5024 1366 2023 2727 3479 4281 5131 1418 2091 2807 3570 4381 5239 1469 2157 2886 3660 4480 5346 1518 2222 2964 3749 4579 5453 1567 2287 3042 3838 4677 5559

D e t e c t o r t i m e c o n s t a n t at a reference velocity of 5 ft/sec,

F o r SI Units:

I ft = 0 . 3 0 5 m

1000 B T U / s e c = 1055 k W

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-112

AUTOMATIC FIRE DETECTORS

T a b l e C,..4-1(z) Ins t a l l e d Spacing of H e a t Detector: 25 feet Fire G row t h Rate: 50 Seconds to 1000 B T U / S E C Alpha: 0.400 B T U / S E C s

T a b l e C-4-1(z) Installed Spacing of Heat Detector: 25 feet Fire Growth Rate: 50 Seconds to 1000 B T U / S E C Alpha: 0.400 B T U / S E C s

"CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

TAU RTI AT

28.0

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

1187 1529 1864 2194 2520 2846 1687 2226 2752 3272 3655 4098 2138 2869 3467 4071 4657 5114 2567 3380 4147 4770 5433 6076 2988 3894 4675 5471 6236 6978 3296 4390 5239 6139 7003 7841 3641 4728 5781 6781 7744 8515 3977 5149 6305 7405 8293 9269 4308 5557 6816 7852 8944 9998 4498 5955 7316 8404 9576 10706 4783 6345 7635 8942

1381 1 5 7 5 1797 2046 2319 2617 1795 2072 2393 2756 3158 3601 2194 2560 2990 3477 4023 4630 2586 3050 3596 4220 4924 5711 2977 3545 4217 4989 5865 6847 3368 4048 4855 5786 6846 8038 1953 2201 2479 2786 3117 3472 2545 2885 3276 3708 4179 4688 3103 3541 4048 4613 5233 5908 3642 4183 4813 5518 6298 7152 4164 4818 5578 6432 7382 8429 4682 5452 6348 7360 8490 9742 2432 2722 3049 3407 3791 4199 3178 3570 4023 4520 5056 5631 3868 4373 4954 5595 6291 7041 4532 5151 5866 6656 7519 8455 5177 5915 6767 7713 8752 9884 5806 6670 7665 8774 9997 11336 2861 3187 3557 3961 4392 4849 3738 4183 4692 5249 5846 6483 4555 5120 5770 6482 7250 8073 5330 6024 6817 7688 8633 9650 6084 6906. 7845 8882 10010 11230 6820 7773 8864 10071 11390 12823 3258 3614 4024 4470 4945 5447 4257 4747 5309 5921 6576 7270 5183 5810 6523 7302 8139 9031 6070 6830 7697 8646 9670 10765 6926 7823 8846 9969 11185 12491 7760 8796 9979 11280 12694 14220 3620 4012 4460 4946 5462 6006 4745 5276 5887 6551 7260 8010 5777 6457 7231 8073 8975 9933 6765 7 5 8 8 8525 9548 10646 11818 7718 8686 9788 10994 12293 13685 8645 9759 11029 12422 13928 15546 3968 4390 4873 5397 5952 6536 5197 5776 6435 7149 7909 8711 6340 7071 7 9 0 2 8805 9769 10791 7426 8308 9312 10405 11575 12820 8471 9506 10684 11969 13350 14823 9479 10675 12030 13510 15106 16813 4301 4750 5267 5827 6420 7042 5637 6256 6959 7721 8530 9382 6880 7659 8545 9506 10529 11612 8059 8997 10065 11225 12465 13780 9185 10291 11542 12903 14363 15915 10283 11552 12988 14553 16235 18031 4621 5097 5646 6240 6868 7527 6060 6716 7463 8270 9127 10027 7399 8224 9163 10179 11261 12402 8660 9660 10790 12016 13323 14706 9877 11047 12368 13804 15339 16968 11057 12397 13911 15559 17325 19205 4918 5430 6011 6838 7301 7995 6469 7161 7 9 4 9 8801 9703 10650 7 9 0 2 8770 9760 10830 11968 13165 9247 10301 11491 12779 14151 15601 10547 11778 13168 14675 16283 17988 11807 13215 14805 16532 18380 20343 5216 5754 6365 7025 7721 8449 6866 7593 8421 9315 10261 11254 8379 9300 10339 11462 12653 13906 9818 10923 12171 13521 14956 16470

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

28.0

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

4.0 .

275 275 300 300 300 300 300 300 325 325 325 325 325 "325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

10192 11198 12487 11397 12534 14008 5061 5505 6069 6728 7 2 5 2 8012 8080 8852 9815 9468 10373 11528 10794 11831 13178 12074 13242 14780 5335 5787 6375 7107 7628 8421 8516 9312 10317 9982 10914 12119 11385 12449 13852 12737 13933 15534 5604 6063 6675 7308 7985 8820 8943 9763 10809 10488 11443 12696 11965 13053 14510 13391 14609 16271 5869 6333 6968 7647 8344 9211 9383 10204 11289 10985 11961 13260 12537 13645 15155 14034 15271 16992 6130 6597 7255 7979 8695 9594 9776 10636 11760 11475 12470 13814 13101 14225 15787 14670 15921 17700

13943 15672 6709 8880 10903 12833 14698 16516 7044 9327 11452 13478 15435 17340 7372 9763 11989 14109 16155 18146 7692 10190 12514 14726 16859 18934 8005 10609 13029 15331 17551 19707

15520 17200.18978 17477 19404 21449 7400 8128 8890 9815 10804 11841 12076 13320 14627 14242 15738 17316 16343 18093 19942 18397 20402 22526 7765 8525 9319 10302 11333 12413 12675 13970 15330 14945 16502 18140 17145 18963 20882 19294 21376 23577 8122 8913 9738 10778 11850 12972 13260 14605 16016 15633 17248 18946 17930 19815 21801 20171 22327 24605 8471 9292 10148 11244 12356 13518 13833 15227 16688 16305 17978 19735 18698 20648 22702 21031 23260 25611 8813 9663 10549 11700 12851 14054 14394 15836 17346 16965 18694 20509 19451 21465 23584 21873 24174 26598

NOTE: Detector time constant at a reference velocity of 5 ft/sec. For SI Units:

1 ft =

0.305

m

1000 BTU/sec = 1055 kW

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

API'ENDIX C

72E-113

T a b l e C-4-1(aa) I n s t a l l e d Spacing of Heat Detector: 25 feet Fire Growth R a ~ : 150 Seconds to 1000 B T U / S E C A l p h a : 0.044 B T U / S E C j

T a b l e C-4-1 (aa) Ins t a l l e d Spacing of H e a t Detector: 25 feet Fire Growth Rate: 150 Seconds to 1000 B T U / S E C Alpha: 0.044 B T U / S E C s

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

24.0 .

.

.

.

.

.

.

TAU RTI AT

28.0 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140' 40 60 80 100

520 701 881 1045 1231 1414 742 981 1223 1460 1696 1933 925 1228 1526 1820 2092 2371 1084 1451 1806 2129 2456 2778 1237 1661 2047 2426 2796 3160 1382 1863 2285 2707 3119 3524 1522 2031 2513 2978 3431 3839 1658 2207 2733 3239 3695 4164 1791 2378 2946 3494 3975 4477 1922 2544 3154 3697 4246 4781 2018 2706 3359 3927

609 843 1084 1335 1596 1875 843 1148 1450 1755 2065 2380 1042 1410 1770 2127 2484 2845 1220 1647 2060 2466 2869 3273 1385 1867 2329 2781 3228 3673 1540 2074 2583 3079 3568 4052 1687 2270 2825 3363 3891 4413 1828 2458 3056 3635 4202 4761 1963 2639 3279 3898 4501 5096 2095 2815 3495 4151 4792 5421 2221 2985 3705 4398

724 1029 1352 1695 2058 2449 97G 1352 1734 2127 2534 2955 1192 1635 2076 2522 2976 3440 1386 1893 2390 2887 3388 3896 1566 2132 2683 3229 3776 4326 1735 2357 2959 3552 4143 4735 1896 2571 3222 3861 4495 5128 2049 2776 3475 4158 4833 5505 2197 2974 3718 4444 5159 5870 2340 3166 3954 4721 5476 6223 2478 3351 4183 4990

861 1250 1672 2126 2611 3126 1130 1590 2068 2568 3092 3640 1364 1895 2433 2985 3554 4143 1576 2174 2771 3375 3993 4624 1772 2434 3088 3744 4409 5084 1957 2679 3388 4094 4805 5524 2132 2913 3674 4430 5186 5948 2300 3137 3950 4752 5553 6356 2462 3353 4215 5064 5908 6752 2618 3562 4473 5366 6252 7136 2770 3765 4722 5660

1018 1507 2045 2629 3256 3924 1303 1861 2452 3078 3740 4439 1555 2186 2837 3513 4219 4955 1785 2487 3198 3928 4681 5458 1998 2768 3539 4322 5123 5945 2199 3034 3864 4699 5549 6414 2390 3288 4174 5062 5958 6868 2573 3532 4473 5411 8354 7308 2749 3767 4761 5748 6738 7734 2919 3995 5041 6076 7!.11 8150 3085 4216 5312 6395

1195 1394 1801 2131 2472 2954 3205 3855 3994 4828 4836 5867 1495 1707 2166 2507 2887 3376 3659 4316 4483 5322 5355 6392 1765 1993 2510 2867 3290 3794 4110 4779 4974 5824 5881 6927 2012 2258 2831 3208 3673 4197 4546 5234 5456 8322 6403 7463 2243 2506 3134 3531 4037 4583 4965 5675 5923 6811 6913 7993 2480 2740 3421 3838 4385 4954 5368 6101 6374 7287 7409 8513 2667 2963 3695 4133 4719 5311 5756 6514 6812 7750 7891 9021 2866 3177 3959 4416 5041 5656 6 1 3 1 6915 7236 8201 8360 9518 3057 3383 4213 4690 5353 5991 6495 7304 7648 8640 8817 10004 3241 3583 4459 4956 5655 6316 6848 7683 8049 9069 9263 10479 3421 3776 4699 5214 5949 6832 7193 8053

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0

28.0

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

4.0 .

275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

4510 5077 2134 2865 3514 4152 4767 5366 2248 3022 3700 4371 5019 5650 2359 3176 3882 4586 5266 5928 2469 3288 4061 4798 5509 6201 2577 3429 4236 5006 5748 6471

5074 5737 2344 3151 3909 4638 5348 6044 2465 3312 4108 4873 5617 6345 2583 3470 4303 5102 5879 6639 2698 3624 4494 5327 6136 6927 2811 3776 4681 5548 6388 7209

5783 6567 2613 3532 4405 5252 6083 6903 2745 3709 4623 5508 6375 7230 2873 3881 4836 5759 6662 7551 2999 4050 5044 6004 6942 7865 3123 4215 5248 6245 7218 8174

6587 7474 8440 9488 7511 8555 9698 10944 2917 3245 3595 3965 3963 4431 4932 5466 4966 5577 6236 6941 5946 6706 7529 8414 6914 7828 8823 9898 7876 8951 10124 11399 3061 3402 3765 4148 4156 4641 5160 5711 5204 5836 6516 7242 6226 7010 7857 8767 7233 8175 9197 10299 8233 9338 10541 11846 3201 3555 3932 4328 4344 4846 5383 5952 5436 6089 6790 7538 6499 7308 8179 9114 7546 8514 9563 10693 8583 9717 10951 12285 3339 3705 4094 4504 4529 5048 5601 6187 5664 6337 7059 7827 6767 7599 8495 9453 7852 8847 9923 11080 8925 10089 11352 12716 3474 3852 4254 4676 4710 5245 5815 6418 5887 6580 7322 8111 7030 7885 8805 9787 8153 9174 10277 11460 9262 10455 11747 13140

NOTE: Detector time constant at a reference velocity of 5 ft/sec. For SI Units: 1 ft = 0 . 3 0 5 m 1000 BTU/sec -- 1 0 5 5 k W

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

7 2 E - l 14

AUTOMATIC FIRE DETECTORS

T a b l e C-4-1 (bb) Installed Spacing of H e a t Detector: 25 feet Fire G r o w t h Rate: 300 ~ c o n d s to 1000 B T U / S E C Alpha: 0.011 B T U / S E C t

T a b l e C-4-1(bb) Installed Spacing of Heat Detector: 25 feet Fire G r o w t h Rate: 300 seconds to 1000 B T U / S E C Alpha: 0.01l BTU/SEC j

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI &T

4.0

8.0

12.0

16.0

20.0

24.0

TAU RTI &T

28.0 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

56 40 56 60 56 80 56 100 56 120 56 140 112 40 112 60 112 80 112 100 112 120 112 140 168 40 168 60 168 80 168 100 168 120 168 140 224 40 224 60 224 80 224 100 224 120 224 140 280 40 280 60 280 80 280 100 280 120 280 140 335 40 335 60 335 80 335 100 335 120 335 140 391 40 391 60 391 80 391 100 391 120 391 140 447 40 447 60 447 80 447 100 447 120 447 140 503 40 503 60 503 80 503 100 503 120 503 140 559 40 559 60 559 80 559 100 559 120 559 140 615 40 615 60 615 80 615 100

321 451 582 719 866 1013 447 616 781 948 1119 1294 560 757

954 1151 13$b 1550 654 890 1113 1338 1563 1789 742 1002 1260 1513 1765 2004 825 1118 1401 1680 1944 2213 908 1226 1536 1842 2122 2412 979 1330 1667 1979 2294 2605 1054 1430 1794 2124 2460 2791 1126 1529 1900 2265 2621 2972 1196 1625 2016 2401

396 580 781 994 1223 1467 527 747 976 1214 1468 1729 642 897 1156 1422 1695 1978 746 1035 1323 1616 1914 2218 842 1163 1480 1799 2120 2447 932 1284 1629 1972 2318 2667 1019 1399 1771 2139 2507 2877 1101 1510 1907 2299 2689 3081 1181 1617 2039 2453 2866 3278 1258 1720 2166 2603 3037 3469 1333 1821 2290 2749

493 746 1030 1337 1667 2021 630 916 1223 1550 1898 2271 753 1075 1410 1761 2130 2517 865 1222 1587 1964 2356 2762 969 1360 1755 2158 2573 3001 1068 1491 1914 2344 2783 3232 1162 1616 2068 2523 2985 3456 1252 1737 2216 2696 3181 3674 1339 1853 2359 2863 3371 3885 1423 1966 2497 3026 3557 4092 1505 2075 2632 3184

609 " 744 946 1178 1324 1669 1740 2210 2194 2797 2675 3426 751 890 1118 1351 1518 1863 1952 2422 2418 3025 2914 3670 882 1028 1283 1522 1710 2059 2166 2638 2650 3258 3163 3918 1003 1157 1439 1687 1896 2251 2376 2853 2881 3492 3411 4169 1116 1279 1588 1845 2074 2439 2580 3065 3107 3725 3657 4420 1223 1395 1729 1997 2245 2621 2777 3273 3328 3955 3898 4669 1325 1506 1865 2143 2411 2797 2969 3475 3543 4181 4135 4915 1424 1613 1996 2284 2570 2968 3154 3673 3752 4402 4365 5158 1519 1715 2122 2420 2725 3134 3335 3866 3956 4619 4591 5396 1610 1815 2245 2553 2875 3297 3511 4055 4155 4832 4812 5631 1699 1912 2364 2683 3022 3455 3682 4239

899 1444 2063 2747 3491 4289 1048 1619 2258 2961 3721 4535 1192 1794 2457 3178 3956 4785 1329 1966 2655 3398 4193 5038 1459 2133 2851 3617 4431 5294 1584 2294 3042 3833 4669 5549 1703 2450 3228 4045 4904 5803 1818 2601 3410 4254 5135 6056 1929 2748 3588 4459 5364 6305 2037 2890 3761 4659 5589 6552 2142 3030 3931 4856

1074 1744 2508 3354 4275 5265 1225 1921 2706 3571 4509 5514 1374 2100 2907 3791 4746 5767 1518 2278 3110 4014 4987 6024 1656 2452 3312 4238 5230 6283 1789 2622 3511 4462 5473 6544 1917 2787 3707 4683 5715 6805 2040 2948 3899 4901 5956 7065 2159 3104 4087 5116 6195 7324 2275 3257 4271 5328 6430 7581 2388 3406 4452 5536

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0

28.0

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

4.0 .

275 615 275 615 300 671 300 671 300 671 300 671 300 671 300 671 325 727 325.727 325..727 325 727 325~727 325 727 350 783 350 783 350 783 350 783 350 783 350 783 375 839 375 839 375 839 375 839 375 839 375 839 400 894 400 894 400 894 400 894 400 894 400 894

120 1~ 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

2778 3149 1264 1720 2129 2535 2932 3323 1331 1797 2239 2666 3083 3493 1397 1884 2347 2794 3231 3638 1461 1970 2453 2920 3377 3797 1525 2053 2558 3045 3497 3953

3204 3656 1405 1919 2411 2891 3366 3837 1476 2014 2528 3030 3525 4015 1546 2107 2644 3166 3680 4189 1614 2199 2757 3299 3833 4360 1680 2288 2868 3430 3982 4528

3737 4293 1584 2182 2764 3339 3913 4490 1662 2286 2892 3490 4086 4682 1738 2388 3018 3638 4255 4871 1812 2488 3141 3783 4421 5057 1885 2586 3262 3926 4584 5239

4350 5028 1786 2481 3165 3850 4541 5241 1871 2594 3305 4014 4727 5449 1954 2706 3442 4175 4911 5653 2035 2815 3576 4333 5091 5854 2115 2922 3708 4488 5268 6051

5040 5861 2007 2809 3610 4420 5245 6088 2099 2932 3761 4597 5446 6310 2189 3053 3910 4771 5643 6530 2277 3172 4055 4942 5837 6746 2364 3288 4199 5110 6028 6958

5810 6795 2244 3166 4097 5049 6027 7035 2344 3299 4260 5239 6242 7271 2442 3430 4420 5426 6453 7505 2537 3558 4577 5609 6660 7735 2631 3684 4732 5790 6865 7962

6663 7835 2498 3552 4629 5741 6893 8087 2606 3695 4803 5943 7120 8336 2711 3835 4975 6142 7343 8583 2814 3973 5143 6337 7564 8827 2915 4108 5308 6531 7782 9067

NOTE: Detector time constant at a reference velocity of 5 ft/sec. For SI Units: l ft = 0.305 m 1000 BTU/sec = 1055 kW

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APF'ENDIX C

72E-1

Table C-4-1 (cc) Installed Spacing of Heat Detector: 25 feet Fire Growth Rate: 500 Seconds to 1000 B T U / S E C Alpha: 0.004 B T U / S E C s

Table C-4-1(cc) Installed Spacing of Heat Detector: 25 feet F i r e G r o w t h Rate: 500 Seconds to 1000 B T U / S E C Alpha: 0.004 B T U / S E C j

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

:16.0 .

.

.

.

.

.

.

20.0 .

.

.

.

.

.

CEILING HEIGHT IN FEET

24.0 .

.

.

.

.

.

26.0 .

.

.

.

.

.

TAU RTI ~T .

.

.

.

.

.

.

.

.

.

.

.

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

56 56 56 56 56 56 112 "112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

234 341 456 578 708 847 317 450 583 722 869 1017 389 545 698 855 1016 1182 45~ 631 804 978 1156 1337 515 712 905 1095 1289 1484 576 788 996 1206 1415 1626 629 865 1087 1312 1536 1763 680 931 1173 1414 1654 1887 729 996 1257 1513 1769 2012 778 1063 1338 1610 1871 2134 824 1126 1418 1705

307 470 652 853 1069 1301 389 573 772 984 1211 1452 465 670 885 1113 1354 1606 534 761 994 1237 1491 1758 598 846 1098 1357 1625 1902 659 927 1197 1472 1755 2044 718 1005 1292 1583 1880 2183 773 1080 1384 1691 2002 2318 827 1152 1473 1795 2120 2450 879 1222 1559 1896 2235 2578 930 1290 1643 1995

397 631 895 1186 1503 1843 481 730 1009 1312 1638 1987 559 829 1121 1436 1776 2134 633 924 1233 1562 1910 2278 703 1015 1341 1685 2046 2425 769 1102 1446 1805 2180 2571 832 1186 1548 1922 2310 2714 893 1266 1646 2036 2438 2855 951 1344 1741 2147 2564 2993 1008 1420 1835 2256 2686 3128 1063 1494 1925 2362

505 820 1181 1579 2013 2479 589 919 1291 1699 2146 2621 671 1020 1404 1824 2277 2761 750 1118 1518 1950 2413 2906 824 1213 1630 2075 2550 3053 895 1305 1739 2199 2686 3200 963 1395 1846 2321 2821 3346 1029 1482 1951 2441 2954 3491 1093 1566 2053 2559 3086 3634 1155 1648 2153 2674 3215 3776 1215 1728 2250 2788

632 1041 1510 2030 2599 3210 716 1140 1621 2153 2731 3352 801 1241 1735 2277 2865 3495 882 1342 1849 2403 3001 3640 961 1441 1964 2530 3139 3787 1037 1538 2077 2657 3277 3935 1110 1633 2189 2783 3415 4083 1181 1725 2299 2908 3552 4231 1250 1815 2407 3031 3689 4379 1317 1903 2514 3153 3824 4526 1382 1989 2618 3273

15

776 1293 1887 2548 3270 4048 861 1393 2000 2672 3404 4191 948 1495 2114 2797 3540 4336 1032 1598 2230 2925 3677 4483 1115 1700 2347 3053 3816 4631 1196 1801 2463 3182 3955 4780 1274 1900 2579 3311 4096 4930 1349 1998 2694 3440 4236 5081 1423 2093 2807 3568 4377 5232 1495 2187 2919 3695 4516 5383 1565 2279 3029 3821

939 1578 2314 3134 4030 4996 1026 1680 2428 3259 4166 5142 1113 1783 2544 3386 4304 5289 1201 1887 2661 3515 4443 5438 1287 1992 2780 3645 4583 5588 1371 2096 2899 3777 4725 5739 1454 2199 3018 3908 4867 5891 1534 2301 3136 4040 5011 6044 1612 2402 3254 4172 5154 6198 1689 2501 3371 4303 5298 6352 1764 2598 3486 4434

4.0 .

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

.

24.0 .

.

.

.

.

.

28.0 .

.

.

.

.

.

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

NOTE:

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

1976 2253 875 1188 1495 1788 2080 2369 916 1249 1571 1876 2181 2482 958 1308 1647 1962 2279 2593 1000 1367 1721 2047 2376 2702 1042 1424 1781 2130 2472 2809

2347 2703 980 1357 1725 2091 2457 2826 1028 1422 1805 2185 2565 2946 1075 1485 1884 2277 2670 3064 1121 1547 1960 2368 2774 3179 1166 1608 2036 2457 2875 3293

2807 3261 1117 1567 2014 2466 2924 3392 t170 1637 2101 2567 3040 3521 1221 1706 2186 2667 3153 3647 1272 1774 2269 2765 3265 3771 1321 1841 2352 2862 3375 3894

3343 3916 1273 1806 2346 2899 3468 4055 1331 1883 2440 3008 3591 4191 1387 1958 2532 3116 3713 4326 1442 2032 2623 3222 3833 4459 1496 2104 2712 3326 3951 4590

3957 4672 1446 2074 2720 3391 4090 4817 1508 2156 2821 3508 4220 4960 1569 2238 2920 3623 4349 5102 1628 2317 3017 3736 4477 5243 1687 2396 3113 3848 4603 5382

4655 5534 1633 2369 3138 3945 4793 5684 1701 2458 3245 4068 4930 5833 1766 2545 3350 4189 5066 5981 1831 2630 3454 4310 5200 6128 1894 2715 3557 4428 5334 6274

5441 6507 1837 2694 3601 4564 5584 6661 1909 2788 3714 4692 5726 6815 1980 2881 3825 4820 5868 6968 2049 2972 3935 4946 6008 7121 2117 3062 4044 5072 6148 7273

D e t e c t o r t i m e c o n s t a n t at a reference velocity of 5 f t / s e c .

F o r S l Units:

1 ft = 0 . 3 0 5 m 100O B T U / s e c = 1055 k W

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-I

AUTOMATIC FIRE DETECTORS

16

T a b l e C-4-1 (dd) Installed Spacing of heat Detector: 25 feet Fire G r o w t h Rate: 600 Seconds to 1000 B T U / S E C Alpha: 0.003 B T U / S E C '

T a b l e C-4-1(dd) I n s t a l l e d Spacing of heat Detector: 25 feet Fire Growth Kate: 600 Seconds to 1000 B T U / S E C A l p h a : 0.003 B T U / S E C s

CEILING HEIGHT IN FEET

CEIIJING HEIGHT IN FEET TAU RTI &T

4.0

8.0

12.0

16.0

20.0

24.0

28.0

TAU RTI AT

FiRE SIZE AT DETECTOR RESPONSE (gTU / SEC) 25 56 40 25 56 60 25 56 80 25 56 100 25 56 120 25 56 140 50 112 40 50 112 60 50 112 80 50 112 100 50 112 120 50 112 140 75 168 40 75 168 60 75 168 80 75 168 100 75 168 120 75 168 140 100 224 40 100 224 60 100 224 80 100 224 100 100 224 120 100 224 140 125 280 40 125 280 60 125 280 80 125 2,80. 100 125 280 120 125 280 140 150 335 40 150 335 60 150 335 80 150 335 100 150 335 120 150 335 140 175 391 40 175 391 60 175 391 80 175 391 100 175 391 120 175 391 140 200 447 40 200 447 60 200 447 80 200 447 100 200 447 120 200 447 140 225 503 40 225 503 60 225 503 80 225 503 100 225 503 120 225 503 140 250 559 40 250 559 60 250 559 80 250 559 100 250 559 120 250 559 140 275 615 40 275 615 60 275 615 80 275 615 100

211 313. 423 542 669 804 283 404 531 663 801 946 345 488 630 776 928 1085 402 563 721 885 1048 1218 454 633 807 983 1162 1344 504 699 891 1079 1271 1466 555 762 966 1171 1376 1583 599 822 1042, 1260 1478 1697 642 884 1114 1345 1576 1809 684 938 1185 1429 1673 1908 724 992 1253 1510

283 441 620 817 1030 1259 353 529 719 925 1146 1383 417 610 814 1034 1265 1509 47'? 688 907 1138 1383 1636 533 761 996 1240 1494 1762 586 832. 1082 1339 1605 1880. 637 899 1164 t435 1713 1999 685 964 1243 1527 1817 2114 732 1027 1320 1617 1919 2228 777 108B 1395 1705 2019 2338 822 1147 1468 1791

373 601 860 1148 1460 1797 442 683 954 1250 1571 1915 509 766 1047 1356 1685 2036 572 846 t1'41 1458 1796 2158 632 923 1233 1561 1910 2278 689 998 1322 1663 2022 2399 743 1070 1409 1763 2133 2520 796 1140 1494 1860 2242 2639 B47 1208 1576 1956 2349 2757 896 1273 1656 2049 2454 2872 944 1338 1735 2141

479 789 1143 1536 1965 2427 548" 869 1233 1638 2075 2544 617 952 1326 1738 2183 2663 683 1034 1421 1841 2295 2779. 747 1115 1514 1946 2408 2900 808 1193 1607 2049 2521 3021 866 1270' 1698 2152 2634 3143 923 1344 1787 2254 2746 3265 978 1417 1874 2354 2857 3385 1032 1488 1960 2452 2967 3505 1084 1557 2044 2549

603 1005 1468 1983 2546 3153 672 1087 1559 2084 2655 3269 742 1170 1653 2186 2766 3387 811 1253 1747 2290 2878 3507 878 1336 1842 2395 2991 3628 942 1418 1937 2500 3105 3750 1005 1498 2031 2605 3219 3872 1066 1577 2124 2710 3334 3995 1126 1654 2216 2814 3448 4118 1183 1730 2306 2916 3561 4241 1240 1804 2395 3018

744 1254 1841 2495 3211 3983 814 1336 1933 2597 3322 4102 885 1419 2027 2701 3434 4221 956 1504 2122 2805 3546 4342 1026 1589 2219 2911 3661 4464 1094 1673 2315 3017 3776 4587 1160 1757 2412 3124 3891 4710 1225 1839 2508 3231 4008 4835 1288 1921 2603 3338 4124 4960 1350 2001 2698 3445 4241 5085 1411 2079 2791 3550

904 1534 2262 3074 3964 4923 975 1618 2356 3178 4076 5044 1047 1702 2451 3283 4190 5166 1119 1788 2548 3389 4304 5288 1191 1874 2645 . 3496 4420 5412 1262 1961 2743 3604 4537 5536" 1332 2047 2842 3712 4654 5662 1400 2133 2941 3822 4772 5788 1467 £218 3039 3931 4891 5915 1533 2302 3137 4040 5010 6042 1597 2384 3234 4150

.4.0

8.0

12.0

16.0

20.0

24.0

28.0

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

1767 2011 764 1047 1320 1590 1850 2112 803 1100 1386 1669 1938 2210 841 1151 1451 1746 2024 2307 882 1202 1514 1812 2108 2402 916 1251 1577 1884 2191. 2495

2116 2447 865 1205 1540 1874 2212 2553 907 1261 1609 1956 2305. 2657 948 1316 1677 2036 2396 2759 988 1371 1744 2115 2486 2859 1027 1424 1810 2193 2575 2958

2557 2986 991 1400 1812 2230 2659 3099 1037 1462 1887 2318 2759 3209 1082 1522 1961 2405 2857 3318 1126 1581 2034 2490 2953 3425 1169 1639 2105 2574 3049 3531

3076 3624 1135 1625 2126 2645 3183 3742 1185 1691 2207 2739 3289 3858 1234 1756 2287 2832 3393 3973 1282 1820 2365 2923 3496 4087 1329 1883 2443 3013 3598 4199

3674 4363 1295 1877 2483 3119 3786 4485 1349 1948 2570 3219 3897 4606 1402 2018 2655 3317 4007 4727 1453 2087 2739 3414 4116 4846 1504 2155 2822 3510 4224 4965

4357 5210 1470 2157 2884 3656 4473 5336 1528 2233 2975 3760 4588 5461 1585 2308 3065 3863 4703 5585 1641 2382 3155 3966 4817 5709 1696 2455 3243 4067 4930 5833

5129 6170 1661 2466 3331 4258 5248 6298 1723 2547 3427 4367 5367 6426 1783 2626 3522 4474 5485 6554 1843 2705 3616 4581 5603 6682 1902 2782 3709 4688 5721 6809

NOTE: Detector time constant at a reference velocity of 5 ft/sec. F o r S l Units:

1 ft = 0.305 m 1000 BTU/sec = 1055 kW

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

AI'PFNDIX C

7 2 E - 1 17

Table C d - I (ee) Installed Spacing of Heat De~ctor: 30 feet Fire Growth Rate: 50 Seconds to 1000 B T U / S E C Alpha: 0.400 B T U / S E C s

Table C,-4-1(ee) Installed Spacing of Heat Detector: 30 feet Fire Growth Rate: 50 Seconds to 1000 B T U / S E C Alpha: 0.400 B T U / S E C s

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI AT

4.0

8.0

12.0

16.0

20.0

24.0

28.0

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

TAU RTI AT

8.0

12.0

16.0

20.0

24.0

28.0

FIRE SIZE AT DETECTORRESPONSE(BTU / SEC)

FIRE SIZE AT DETECTORRESPONSE(8TU / SEC) 25 56 40 1541 1757 1963 2204 2475 2773 3096 25 56 60 2013 2288 2589 2944 3344 3788 4276 25 56 80 2472 2801 3207 3687 4231 4839 5512 25 56 100 2925 3307 3828 4445 5148 5936 6813 25 56 120 3311 3811 4458 5223 6098 7084 8183 25 56 140 3718 4318 5100 6024 7084 8283 9621 50 112 40 2231 2480 2735 3032 3361 3718 4101 50 112 60 2986 3235 3592 4014 4484 4997 5550 50 112 80 3587 3941 4414 4970 5590 6270 7009 50 112 100 4208 4627 5222 5918 6698 7558 8499 50 112 120 4810 5300 6023 6868 7819 8873 10031 50 112 140 5293 5963 6823 7827 8959 10219 11610 75 168 40 2867 3087 3379 3725 4106 4517 4955 75 168 60 3727 4024 4437 4922 5458 6038 6659 75 168" 80 4572 4905 5441 6070 6768 7525 8340 75 168 100 5231 5745 6416 7196 8061 9006 10029 75 168 120 5958 6567 7375 8311 9354 10496 11739 75 168 140 6664 7375 8324 9424 10652 12003 13479 100 224 40 3365 3621 3952 4342 4771 5232 5719 100 224 60 4462 4734 5193 5736 6333 6976 7661 100 224 80 5310 5761 6363 7062 7832 8664 9554 100 224 100. 6213 6751 7492 8352 9300 10329 11434 100 224 120 7081 7711 8596 9621 10755 11989 13321 100 224 140 7923 8650 9684 10880 12207 13655 15225 125 280 40 3870 4115 4479 4909 5383 5888 6423 125 280 60 4990 5377 5889 6486 7141 7843 8588 125 280 80 6091 6557 7214 7978 8817 9720 10682 125 280 100. 7137 7682 8488" 9423 10450 11560 12747 125 280 120. 8143 8770 9728 10838 12060 13383 14805 125 280 140 8954 9826 10946 12235 13658 15203 16869 150 335 40 4248 4569. 4970 5440 5954 6503 7082 150 335. 60 5589 5987 654i 7189 7898 8656 9459 150 335 80 6837 7304 8013 8838 9743 10713 11744 150 335 100 7873 8550 9423 10430 11533 12720 13986 150 335 120 8963 9758 10793 11984 13291 14701 16210 150 335 140 10016 10935 12134 13513 15029 16669 18430 175 391 40 4673 5004 5436 5942 6496 7085 7706 175 391 60 6166 6565 7160 7856 8616 .9428 10285 175 391 80 7411 8005 8771 9655 10622 11657 12754 175 391 100 8667 9379 10311 11387 12563 13825 15166 175 391 120 9870 10702 11805 13073 14462 15956 17550 175 391 140 11031 11989 13264 14729 16336 18068 19921 200 447 40 5082 5421 5881 6422 7012 7641 8301 200 447 60 6726 7119 7752 8493 9303 10165 11075 200 447 80 8060 8681 9496 10437 11464 12561 13721 200 447 100 9432 10172 11162 12303 13549 14883 16298 200 447 120 10744 11607 12774 14117 15585 17160 18837' 200 447 140 12010 12999 14347 15895 17589 19411 21355 225 503 40 5480 5821 6 3 0 9 6882 7509 8174 8873 225 503 60 7117 7642 8320 9106 9963 10875 11835 225 503 80 8688 9332 10193 11189 12273 13430 14652 225 503 100 10171 10936 11980 13185 14498 15902 17388 225 503 120 11590 12477 13707 15122 16667 18321 20077 225 503 140 12998 13973 15390 17018 18797 20707 22739 250 559 40 5868 6207 6721 7327 7988 8689 9425 250 559 60 7610 8154 8869 9698 10600 11560 12569 250 559 80 9298 9962 10868 11915 13056.14271 15552 250 559 100 10891 11674 12772 14038 15416 16888 18443 250 559 120 12415 13320 14610 16095 17713 19444 21279 250 559 140 13884 14914 16399 18105 19967 21961 24080 275 615 40 6248 6582 7121 7758 8452 9188 9959 275 615 60 8091 8651 9402 10272 11218 12224 13280 275 615 80 9892 ~0572 11522 12620 13815 15086 16425 275 615 100 11594 12391 13540 14865 16307 17844 19467

4.0

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

275 615 120 13221 14137 15486 17039 18729 20535 22446 275 615 140 14789 15828 17379 19161 21102 23180 25383 300 671 40 6623 6947 7510 8176 8902 9672 10478 300 671 60 8560 9135 9919 10830 11819 12870 13972 300 671 80 10474 11166 12158 13306 14553 15879 17274 300 671 100 12283 13089 14287 15670 17174 18775 20464 300 671 120 14013 14933 16339 17957 19718 21596 23582 300-671 140 15680 16719 18333 20188 22208 24366 26652 325 727 40 6827 7290 7888 8584 9342 10144 10984 325 727 60 9019 9606 10424 11373 12405 13499 14646 325 727 80 11045 11746 12779 13974 15273 16652 18102 325 727 100 12961 13769 15016 16455 18019 19683 21436 325 727 120 14793 15710 17170 18853 20683 22632 24690 325 727 140 16294 17578 19263 21190 23287 25524 27891 350 783 40 7161 7635 8257 8982 9770 10605 11478 350 783 60 9470 10067 10917 11905 12977 14114 15305 350 783 80 11607 12312 13385 14627 15976 17408 18912 350 783 100 13629 14435 15728 17223 18845 20570 22386 350 783 120 15303 16459 17983 19729 21626 23645 25774 350 783 140 17103 18426 20172 22170 24341 26656 29103 375 839 40 7488 7973 8619 9371 10190 11055 11961 375 839 60 9914 10518 11400 12424 13537 14715 15949 375 839 80 12161 12867 13978 15266 16664 18147 19703 375 839 100 14054 15076 16425 17974 19654 21439 23316 375 839 120 16012 17201 18779 20587 22549 24636 26835 375 839 140 17897 19256 21063 23129 25374 27765 30289 400 894 40 7810 8304 8973 9753 10600 11497 12433 400 894 60 10351 10960 11873 12934 14085 15304 16580 400 894 80 12709 13411 14560 15893 17339 18872 20480 400 894 100 14664 15714 17108 18710 20447 22291 24228 400 894 120 16709 17929 19559 21427 23454 25608 27876 400 894 140.18677 20070 21936 24070 26387 28853 31453

NOTE: Detector time constant at a reference velocity of 5 ft/sec. F o r S l Units:

1 ft = 0 . 3 0 5 m 1000 BTU/sec = 1055 kW

/

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-1

18

AUTOMATIC FIRE DETECTORS

Table C - 4 - I ( f D Installed Spacing of Heat De~ctor: Fire Growth Ra~:

Table C-4-1(ff) Installed Spacing of Heat Detector: 30 feet Fire Growth Rate: 150 Seconds to 1000 B T U / S E C Alpha: 0.044 B T U / S E C s

30 feet

150 S e c o n d s to 1000 B T U / S E C

Alpha:

0.044 B T U / S E C s

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI &T .

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

8.0 .

.

.

.

.

.

12.0 .

.

.

.

.

.

16.0 .

.

.

.

.

.

20.0 .

.

.

.

.

.

24,0 .

.

.

.

.

.

TAU RTI &T

28.0 .

.

.

.

.

.

.

1990 Edition

684 919 1150 1387 1629 1877 958 1284 1603 1919 2217 2526 1194 1604 2004 2361 2732 3100 1409 1901 2335 2773 3203 3628 1611 2148 2662 3159 3647 4092 1806 2398 2972 3528 4029 4548 1996 2637 3271 3839 4417 4982 2137 2867 3521 4165 4790 5400 2301 3092 3788 4480 5150 5805 2461 3312 4047 4786 5501 6198 2616 3479 4299 5083

780 1084 1399 1728 2072 2432 1073 1465 1856 2251 2654 3066 1323 1795 2257 2716 3178 3645 1547 2093 2620 3141 3660 4180 1755 2368 2958 3537 4110 4682 1950 2628 3277 3911 4536 5157 2135 2875 3581 4267 4942 5611 2311 3111 3871 4609 5332 6047 2481 3339 4151 4938 5709 6468 2645 3559 4423 5257 6073 6876 2805 3772 4686 5567

911 1300 1715 2157 2626 3122 1220 1696 2182 2683 3203 3743 1486 2044 2602 3168 3745 4337 1726 2362 2988 3616 4251 4895 1948 2657 3349 4037 4728 5424 2157 2934 3689 4436 5181 5928 2355 3199 4014 4816 5614 6411 2544 3452 4326 5182 6030 6876 2727 3697 4626 5535 6433 7326 2903 3933 4917 5877 6823 7762 3075 4162 5200 6209

1066 1556 2088 2663 3278 3931 1391 1965 2563 3192 3852 4544 1675 2334 3004 3694 4408 5148 1932 2672 3414 4167 4938 5728 2171 2988 3798 4614 5441 6284 2396 3287 4163 5039 5923 6818 2609 3571 4511 5447 6385 7331 2813 3844 4846 5839 6830 7827 3010 4107 5169 6217 7262 8308 3200 4361 5482 6585 7680 8775 3385 4608 5786 6942

8.0

12.0

16.0

20.0

24.0

28.0

FIRE SIZE AT DETECTORRESPONSE(BTU / SEC)

FIRE SIZE AT DETECTORRESPONSE(BTU / SEC) 25 56 40 25 56 60 25 56 80 25 56 100 25 56 120 25 56 140 50 112 40 50 112 60 50 112 80 50 112 100 50 112 120 50 112 140 75 168 40 75 168 60 75 168 80 75 168 100 75 168 120 75 168 140 100 224 40 100 224 60 100 224 80 100 224 100 100 224 120 100 224 140 125 280 40 125 280 60 125 280 80 125 280 100 125 280 120 125 280 140 150 335 40 150 335 60 150 335 80 150 335 100 150 335 120 150 335 140 175 391 40 175 391 60 175 391 80 175 391 100 175 391 120 175 391 140 200 447 40 200 447 60 200 447 80 200 447 100 200 447 120 200 447 140 225 503 40 225 503 60 225 503 80 225 503 100 225 503 120 225 503 140 250 559 40 250 559 60 250 559 80 250 559 100 250 559 120 250 559 140 275 615 40 275 615 60 275 615 80 275 615 100

4.0

.

1243 1443 1665 1850 2183 2555 2518 3005 3550 3245 3904 4641 4026 4872 5819 4858 5906 7077 1583 1796 2030 2270 2613 2992 3000 3492 4042 3775 4436 5177 4598 5445 6394 5467 6514 7688 1885 2116 2366 2659 3019 3414 3459 3967 4529 4294 4967 5717 5166 6022 6978 6078 7131 8311 2161 2409 2678 3019 3399 3814 3891 4420 5001 4789 5481 6248 5716 6589 7560 6677 7745 8937 2417 2683 2969 3356 3758 4193 4300 4851 5454 5261 5977 6765 6245 7141 8131 7257 8346 9556 2658 2941 3244 3676 4098 4555 4689 5264 5890 5712 6454 7266 6754 7675 8689 7819 8933 10164 2888 3187 3507 3981 4424 4901 5061 5661 6310 6146 6914 7751 7245 8193 9233 8362 9504 10761 3108 3423 3759 4273 4738 5235 5420 6043 6716 6565 7359 8222 7720 8696 9762 ~888 10060 11344 3319 3650 4002 4556 5040 5558 5766 6413 7110 6971 7791 8680 8180 9185 10279 9400 10601 11914 3524 3870 4237 4829 5333 5871 6102 6772 7492 7364 8211 9126 8627 9662 10783 9898 11130 12472 3722 4083 4465 5095 5618 6175 6428 7122 7865 7747 8620 9561

275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

NOTE:

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

5842 6582 2769 3677 4545 5374 6177 6959 2919 3871 4786 5659 6505 7329 3066 4061 5022 5940 6828 7693 3213 4248 5254 6215 7147 7974 3308 4431 5482 6488 7389 8311

6427 7203 8087 9063 10126 11276 7272 8186 9230 10385 11647 13019 2960 3241 3564 3916 4291 4687 3980 4385 4848 5354 5895 6472 4942 5475 6082 6747 7463 8228 5869 6533 7290 8121 9020 9986 6772 7572 8485 9489 10581 11759 7659 8600 9674 10859 12153 13555 3112 3403 3739 4104 4493 4904 4183 4603 5083 5606 6166 6761 5193 5743 6371 7058 7796 8584 6164 6849 7630 8486 9411 10402 7109 7933 8873 9905 11025 12232 8036 9004 10108 11324 12649 14081 3260 3562 3910 4288 4691 5116 4382 4816 5312 5853 6431 7044 5437 6006 6654 7362 8122 8932 6452 7158 7963 8843 9793 10810 7439 8287 9253 10313 11461 12696 8405 9400 10533 11780 13135 14597 3405 3717 4077 4468 4884 5323 4576 5024 5537 6095 6691 7322 5677 6263 6931 7660 8441 9273 6734 7461 8289 9194 10168 11211 7762 8633 9625 10713 11889 13151 8766 9788 10950 12227 13612 15105 3546 3870 4242 4645 5074 5526 4766 5229 5757 6332 6945 7594 5912 6515 7203 7952 8755 9608 7011 7758 8609 9538 10537 11604 8077 8973 9991 11106 12309 13599 9121 10168 11359 12666 14081 15604

D e t e c t o r t i m e c o n s t a n t at a .reference velocity of 5 ft/sec.

F o r SI Units:

1 ft = 0 , 3 0 5 m 1000 B T U / s e c = 1055 k W

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

API'ENI)IX C

7 2 E - 119

Table C,-~I (gg) I n s ~ l l e d Spacing of Heat De~ctor: 30 feet Fire Growth Rate: 300 Seconds m 1000 B T U / S E C Alpha: 0.01l B T U / S E C s

Table G-4-1 (gg) Installed Spacing of Heat Detector: 30 feet Fire Growth Raw: 300 Seconds to 1000 B T U / S E C Alpha: 0.011 B T U / S E C j

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI &T .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0

TAU RTI &T

28.0 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

422 594 772 958 1154 1359 587 805 1023 1249 1478 1714 723 985 1248 1510 1775 2036 846 1152 1453 1753 2041 2337 959 1307 1646 1968 2294 2619 1068 1454 1831 2178 2534 2888 1171 1595 1989 2379 2763 3145 1270 1733 2152 2572 2985 3394 1367 1849 2310 2759 3200 3636 1460 1973 2464 2941 3409 3872 1552 2093 2613 3118

511 753 1018 1302 1606 1930 675 961 1259 1572 1901 2251 818 1148 1484 1830 2187 2558 949 1320 1693 2072 2459 2856 1069 1481 1889 2300 2717 3142 1183 1633 2075 2518 2964 3416 1292 1778 2253 2726 3201 3679 1395 1917 2424 2927 3429 3934 1495 2051 2589 3121 3651 4181 1592 2181 2749 3309 3865 4421 1686 2307 2905 3492

625 952 1316 1717 2147 2605 793 1159 1552 1974 2424 2901 943 1352 1780 2230 2705 3203 1081 1533 1997 2478 2979 3501 1210 1703 2203 2716 3245 3792 1332 1864 2399 2944 3502 4075 1448 2019 2588 3164 3751 4350 1559 2167 2770 3377 3991 4617 1666 2311 2946 3583 4226 4877 1770 2450 3117 3783 4453 5131 1871 2585 3284 3979

761 1187 1666 2194 2766 3378 931 1392 1898 2447 3038 3668 1089 1591 2128 2703 3315 3964 1235 1780 2352 2955 3592 4261 1373 1960 2567 3201 3864 4556 1503 2131 2774 3439 4130 4847 1627 2296 2974 3671 4389 5131 1747 2455 3168 3896 4642 5410 1862 2608 3356 4115 4889 5683 1974 2758 3539 4328 5131 5951 2082 2903 3717 4536

916 1456 2068 2743 3476 4262 1089 1661 2297 2993 3745 4549 1253 1864 2528 3248 4020 4842 1408 2060 2757 3503 4297 5138 1554 2249 2981 3755 4574 5436 1693 2430 3198 4003 4847 5732 1826 2605 3409 4245 5116 6025 1954 2774 3614 4481 5380 6313 2077 2938 3813 4712 5639 6598 2197 3098 4007 4938 5893 6878 2314 3253 4197 5159

1093 1761 2520 3361 4275 5257 1267 1965 2749 3611 4545 5545 1437 2171 2982 3867 4820 5838 1599 2374 3215 4124 5098 6135 1753 2571 3446 4381 5378 6434 1901 2761 3671 4636 5657 6734 2042 2946 3892 4887 5934 7034 2179 3125 4107 5133 6207 7331 2311 3299 4318 5375 6477 7625 2439 3469 4523 5613 6743 7916 2564 3635 4725 5846

1290 2101 3026 4052 5169 6369 1466 2307 3256 4304 5441 6660 1640 2515 3491 4561 5717 6955 1809 2723 3728 4821 5998 7253 1971 2927 3963 5082 6280 7555 2126 3126 4196 5342 6564 7859 2276 3319 4425 5601 6847 8163 2421 3508 4650 5856 7129 8467 2562 3692 4871 6108 7407 8770 2698 3872 5088 6357 7684 9070 2831 4048 5300 6601

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0

28.0

.

FIRE SIZE AT DETECTORRESPONSE(8TU / SEC)

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 56 40 25 56 60 25 56 80 25 56 100 25 56 120 25 56 140 50 112 40 50 112 60 50 112 80 50 112 100 50 112 120 50 112 140 75 168 40 75 168 60 75 168 80 75 168 100 75 168 120 75 168 140 100 224 40 100 224 60 100 224 80 100 224 100 100 224 120 100 224 140 125 280 40 125 280 60 125 280 80 125 280 100 125 280 120 125 280140 150 335 40 150 335 60 150 335 80 150 335 100 150 335 120 150 335 140 175 391 40 175 391 60 175 391 80 175 391 100 175 391 120 175 391 140 200 447 40 200 447 60 200 447 80 200 447 100 200 447 120 200 447 140 225 503 40 225 503 60 225 503 80 225 503 100 225 503 120 225 503 140 250 559 40 250 559 60 250 559 80 250 559 100 250.559 120 250 559 140 275 615 4 0 275 615 60 275 615 80 275 615 100

4.0 .

275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

3614 4074 1642 2211 2760 3293 3789 4292 1732 2325 2903 3464 3979 4505 1801 2438 3044 3605 4165 4714 1882 2549 3183 3764 4347 4918 1962 2657 3320 3920 4526 5119

4074 4654 1778 2430 3057 3671 4278 4882 1867 2550 3205 3845 4477 5105 1954 2667 3350 4016 4672 5324 2039 2782 3492 4183 4864 5538 2123 2894 3631 4347 5051 5748

4676 5378 1969 2717 3446 4169 4893 5621 2065 2845 3604 4356 5105 5858 2158 2971 3760 4538 5314 6091 2250 3094 3912 4717 5518 6319 2340 3215 4061 4893 5719 6544

5367 6213 2188 3044 3890 4740 5598 6470 2291 3182 4061 4939 5825 6722 2392 3318 4227 5135 6047 6970 2490 3450 4390 5326 6266 7213 2587 3580 4551 5515 6481 7453

6143 7153 .2427 3405 4383 5375 6388 7424 2538 3553 4565 5588 6628 7691 2646 3698 4743 5796 6865 7954 2753 3840 4918 6001 7098 8212 2857 3980 5090 6203 7327 8467

7005 7956 8204 9368 2685 2961 3796 4219 4922 5509 6075 6842 7263 8226 8487 9663 2804 3088 3955 4388 5116 5713 6300 7079 7516 8492 8767 9955 2920 3212 4110 4553 5305 5915 6522 7313 7767 8755 9044 10245 3034 3333 4262 4715 5492 6113 6740 7543 8013 9014 9317 10531 3146 3453 4412 4875 5676 6308 6954 7770 8256 9271 9586 10814

NOTE: Detector time constant at a reference velocity of 5 ft/sec. F o r S l Units: 1 ft = 0.505m 1000 BTU/sec = 1055 kW

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

7 2 E - 12 0

AUTOMA']'~C FI RE D E T E C T O R S

T a b l e C-4-1(hh) I n s ~ l l e d Spacing of H e a t D e ~ c t or: B0 feet Fire G r o w t h Kate: 500 Seconds to I000 B T U / S E C A l pha : 0.004 B T U / S E C 5

T a b l e C.4-l(hh) I n g a l l e d Spacing of H e a t Detector: 30 feet Fire Growth R a ~ : 500 Seconds to 1000 B T U / S E C Alpha: 0.004 B T U / S E C s

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

4.0

8.0

12.0

16.0

20.0

24.0

TAU RTI AT

28.0 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0

28.0

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

310 455 609 777 955 1145 416 591 770 958 1154 1359 512 712 918 1127 1344 1567 594 823 1053 1285 1522 1765 671 927 1180 1435 1693 1956 744 1023 1301 1578 1857 2128 813 1118 1417 1715 2004 2300 883 1208 1529 1840 2153 2466 943 1295 1638 1966 2296 2626 1004 1379 1745 2088 2436 2783 1066 1462 1837 2206

397 615 858 1124 1413 1722 501 742 1002 1285 1586 1906 595 862 1144 1443 1762 2095 682 975 1280 1598 1930 2277 763 1082 1409 1.747 2096 2459 839 1184 1533 1890 2258 2637 912 1281 1652 2029 2414 2809 982 1375 1767 2163 2566 2977 1050 1466 1878 2293 2714 3142 1116 1554 1986 2420 2858 3302 1179 1639 2092 2543

506 810 1153 1531 1943 2385 608 930 1288 1683 2106 2559 705 1050 1426 1832 2268 2736 795 1166 1562 1984 2434 2910 881 1277 1694 2134 2599 3087 962 1384 1822 2281 2761 3264 1040 1487 1947 2424 2921 3438 1115 1586 2067 2564 3077 3610 1187 1682 2185 2700 3231 3779 1257 1776 2299 2833 3381 3945 1325 1867 2411 2964

634 1034 1490 1997 2552 3145 735 1153 1623 2142 2705 3309 834 1272 1759 2291 2866 3480 928 1390 1894 2441 3028 3653 1018 1505 2029 2591 3191 3828 1104 1616 2161 2740 3354 4004 1187 1725 2290 2887 3516 4179 1267 1830 2416 3031 3677 4353 1344 1932 2540 3173 "3835 4525 1419 2031 2661 3313 3991 4696 1492 2129 2779 3450

781 1292 1877 2527 3237 4001 881 1409 2008 2672 3393 4169 981 1528 2142 2819 3552 4338 1078 1647 2278 2968 3713 4509 1173 1765 2414 3118 3875 4683 1263 1881 2549 3268 4038 4858 1351 1994 2682 3418 4202 5033 1436 2104 2813 3566 4365 5209 1518 2212 2942 3713 4527 5384 1599 2317 3069 3858 4688 5559 1677 2421 3193 4001

947 1582 2312 3125 4013 4970 1047 1699 2444 3270 4170 5138 1148 1818 2578 3417 4329 5308 1248 1939 2714 3566 4490 5480 1345 2059 2850 3716 4652 5653 1441 2178 2987 3868 4816 5828 1533 2295 3124 4020 4981 6004 1623 2410 3259 4171 5146 6181 1710 2523 3393 4322 5311 6359 1795 2634 3525 4471 5475 6536 1878 2743 3655 4620

1132 1906 2798 3793 4880 6052 1232 2024 2931 3939 5039 6222 1334 2144 3066 4087 5199 6394 1436 2266 3202 4237 5361 6567 1537 2388 3340 4389 5524 6742 1636 2509 3479 4541 5689 6918 1733 2630 3618 4695 5855 7095 1827 2749 3757 4849 6022 7274 1919 2867 3894 5003 6190 7453 2009 2983 4031 5156 6357 7633 2097 3097 4166 5309

275 615 120 275 615 140 300 671 40 300 671 60 300 671 80 300 671 100 300 671 120 300 671 140 325 727 40 325 727 60 325 727 80 325 72Z 100 325 727 120 325 727 140 350 783 40 350 783 60 350 783 80 350 783 100 350 783 120 350 783 140 375 839 40 3.75 839 60 375 839 80 375 839 100 375 839 120 375 839 140 400 894 40 400 894 60 400 894 80 400 894 100 400 894'120 400 894 140

2572 2935 1125 1543 1935 2322 2704 3084 1183 1623 2031 2435 2834 3230 1239 1701 2125 2546 2962 3374 1295 1766. 2217 2655 3087 3515 1349 1839 2307 2762 3210 3654

2998 3458 1241 1723 2194 2664 3136 3612 1302 1804 2295 2782 3271 3762 1361 1884 2393 2898 3403 3910 1419 1962 2490 3011 3532 4054 1476 2038 2584 3123 3660 4197

3529 4108 1392 1956 2520 3091 3673 4268 1457 2043 2627 3217 3815 4426 1520 2128 2732 3340 3955 4581 1582 2212 2835 3460 4092 4734 1643 2294 2936 3579 4228 4885

4145 4865 1564 2224 2895 3585 4296 5032 1633 2317 3009 3717 4446 5197 1701 2408 3121 3848 4593 5360 1768 2498 3230 3976 4738 5520 1834 2586 3339 4102 4881 5679

4847 5732 1753 2522 3316 4142 5005 5904 1828 2621 3436 4282 5161 6075 1901 2718 3555 4419 5315 6244 1973 2814 3672 4555 5467 6412 2043 2908 3787 4688 5618 6578

5639 6713 1960 2850 3784 4767 5802 6890 2039 2955 3910 4912 5963 7065 2117 3059 4035 5056 6124 7240 2194 3160 4159 5198 6283 7414 2270 3260 4280 5339 6440 7586

6525 7813 2183 3210 4300 5460 6691 7993 2268 3320 4433 5611 6858 8172 2351 3430 4564 5761 7023 8352 2433 3537 4693 5909 7188 8531 2513 3643 4821 6056 7351 8709

NOTE: Detector time constant at a reference velocity of 5 ft/sec. F o r S I Units:

I ft = 0 . ~ 0 5 m 1000 BTU/sec = 1055 kW

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

AI'PENDIX C

7 2 E - 121

T a b l e C-4-1 (ii) Ins t a l l e d Spacing of H e a t Detector: 30 ~ e t Fire G row t h Rate: 600 Seconds m 1000 B T U / S E C Alpha: 0.003 B T U / S E C s

T a b l e C-4-1(ii) In'stalled Spacing of Heat Detector: 30 feet Fire Growth Rate: 600 Seconds to 1000 B T U / S E C Alpha:

0.003 BTU/SEC j

CEILING HEIGHT "IN FEET TAU RTI &T .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

CEILING HEIGHT IN FEET TAU RTI &T

28.0 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140" 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

281 419 568 730 906 1091 372 534 703 883 1070 1268 451 639 829 1026 1230 1443 527 735 946 1162 1383 1611 594 825 1056 1290 1529 1773 657 911 1161 1413 1669 1930 717 990 1261 1532 1805 2073 774 1069 1358 1646 1929 2217 830 1144 1452 1758 2053 2356 887 1217 1543 1858 2175 2492 937 1289 1632 1961

369 579 817 1079 1364 1669 455 685 938 1211 1506 1820 536 787 1056 1345 1651 1975 610 884 1171 1473 1792 2131, 680 976 1281 1600 1933 2281 747 1064 1388 1723 2070 2431 810 1148 1491 1842 2204 2578 871 1229 1590 1958 2335 2723 930 1308 1686 2070 2462 2863 987 1384 1780 2180 2587 3001 1042 1459 1872 2287

476 773. 1110 1484 1890 2328 561 872 1221 1608 2024 2471 642 972 1335 1731 2161 2616 719 1070 1449 1857 2295 2760 793 1165 1561 1983 2432 2907 863 1256 1670 2107 2568 3054 930 1345 1776 2229 2703 3201 995 1430 1880 2348 2836 3346 1058 1514 1981 2465 2967 3489 1119 1595 2080 2579 3096 3631 1178 1674 2176 2691

602 995 1445 1948 2494 3082 685 1092 1554 2065 2620 3217 767 1191 1665 2187 2752 3358 847 1289 1777 2310 2886 3500 924 1386 1890 2435 3020 3644 998 1481 2001 2559 3156 3789 1069 1573 2110 2683 3291 3935 1138 1663 2217 2805 3426 4080 1205 1751 2323 2925 3559 4225 1270 1837 2427 3044 3691 4369 1333 1921 2528 3161

747 1249 1826 2470 3174 3932. 828 1345 1935 2589 3303 4070 911 1443 2045 2710 3433 4210 993 1542 2156 2833 3565 4351 1072 1640 2269 2956 3699 4494 1150 1737 2381 3081 3834 4637 1225 1833 2493 3205 3969 4782 1298 1927 2603 3330 4105 4928 1369 2019 2713 3453 4240 5073 1438 2110 2821 3575 4375 5219 1506 2198 2927 3697

909 1535 2257 3062 3943 4893 991 1631 2365 3181 4072 5032 1074 1729 2475 3302 4203 5172 1157 1828 2587 3425 4336 5314 1239 1928 2700 3549 4469 5456 1320 2027 2813 3674 4604 5600 1398 2126 2926 3799 4740 5745 1475 2223 3039 3925 4877 5891 1550 2319 3152 4051 5013 6038 1623 2413 3263 4176 5150 6185 1695 2507 3374 4301

1091 1855 2737 3723 4802 5967 1173 1952 2847 3844 4933 6107 1257 2050 2957 3966 5066 6249 1341 2150 3070 4089 5199 6392 1425 2250 3183 4214 5334 6536 1508 2351 3298 4339 5469 6681 1590 2452 3413 4466 5606 6827 1670 2552 3528 4593 5744 6974 1749 2651 3643 4721 5882 7122 1826 2750 3757 4848 6020 7270 1901 2847 3871 4976

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

28.0

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

4.0 .

275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

2293 2624 987 1358 1720 2062 2408 2753 1037 1427 1796 2160 2521 2879 1087 1494 1878 2257 2631 3003 1135 1560 1958 2351 2740 3125 1182 1625 2037 2444 2846 3245

2708 3137 1096 1531 1961 2392 2827 3269 1149 1602 2048 2495 2944 3399 1201 1671 2134 2595 3059 3527 1251 1740 2218 2694 3171 3653 1301 1806 2300 2791 3282 3777

3222 3770 1236 1751 2271 2802 3347 3907 1292 1827 2364 2910 3469 4043 1348 1901 2454 3016 3590 4177 1402 1973 2544 3121 3708 4308 1455 2045 2632 3224 3825 4438

3822 4512 1395 2003 2628 3277 3951 4653 1456 2084 2726 3391 4079 4794 1515 2163 2823 3503 4205 4932 1573 2241 2918 3613 4330 5070 1630 2317 3012 3722 4453 5206

4509 5364 1572 2285 3032 3817 4642 5509 1637 2371 3135 3936 4775 5653 1700 2455 3237 4053 4906 5798 1762 2538 3338 4169 5036 5939 1824 2619 3437 4284 5164 6080

5287 6332 1765 2598 3483 4424 5423 6479 1834 2688 3591 4548 5559 5626 1902 2777 3698 4670 5694 6773 1968 2865 3804 4791 5829 6919 2034 2951 3908 4911 5962 7065

6159 7419 1976 2943 3984 5103 6298 7568 2049 3037 4096 5229 6437 7717 2120 3131 4207 5355 6576 7867 2191 3223 4318 5481 6714 8016 2260 3314 4427 5605 "6851 8165

NOTE: Detector time constant at a reference velocity of 5 ft/sec. F o r S I Units: 1 ft = 0 . 3 0 5 m 1000 BTU/sec -- 1055 kW

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E- 122

AUTOMNI'IC FI RE DETECTORS

T a b l e C~-I ~j) I n s ~ l l e d Spacing of Heat Detector: 50 feet Fire Growth Rate: 50 Seconds to 1000 B T U / S E C Alpha: 0.400 B T U / S E C =

T a b l e C-4-1 (jj) Installed Spacing of Heat Detector: 50 feet Fire Growth Rate: 50 Seconds to 1000 B T U / S E C Alpha: 0.400 B T U / S E C =

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI &T .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

TAU RTI &T

28.0

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 497 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

1990 Edition

3499 3611 3846 4555 4723 5115 5425 5806 6382 6348 6890 7670 7255 7981 8987 8154 9087 10339 4909 5030 5295 6378 6566 6990 7744 8031 8633 9044 9459 10257 10300 10869 11881 11383 12270 13513 6159 6216 6507 7858 8112 8577 9536 9909 10558 11130 11646 12493 12669 13346 14407 14167 15023 16312 7107 7258 7585 9264 9497 9999 11254 11597 12290 13136 13616 14514 14944 15582 16698 16700 17513 18859 8093 8224 8576 10578 10773 11309 12863 13156 13891 15016 15438 16384 17078 17654 18823 19076 19822 21227 9028 9128 9503 11831 11970 12538 14401 14620 15394 16567 17143 18143 18854 19594 20824 21069 21988 23459 9927 9984 10381 12795 13093 13702 15570 15997 16820 18190 18766 19814 20701 21442 22727 23131 24052 25583 10597 10789 11218 13882 14175 14815 16902 17322 18185 19748 20319 21414 22474 23212 24549 25110 26028 27618 11385 11571 12023 14931 15215 15886 18187 18598 19498 21253 21815 22954 24186 24916 26304 27020 27932 29579 12148 12327 12799 15948 16220 16919 19433 19830 20766 22713 23260 24443 25848 26564 28002 28875 29774 31477 12890 13059 13552 16939 17194 17922 20648 21026 21997 24135 24663 25887

4155 4512 4907 5336 5604 6162 6780 7454 7078 7867 8740 9695 8597 9645 10804 12073 10169 11502 12976 14589 11799 13441 15255 17239 5650 6060 6511 6996 7530 8145 8819 9549 9376 10217 11141 12143 11224 12313 13511 14814 13089 14449 15946 17578 14982 16634 18454 20442 6906 7 3 6 8 7874 8417 9173 9851 10593 11390 11365 12277 13273 14347 13527 14690 15963 17337 15683 17116 18685 20385 17847 19567 21454 23502 8027 8537 9096 9692 10649 11389 12196 13060 13161 14144 15216 16366 15619 16861 18215 19671 18051 19567 21222 23005 20474 22281 24255 26387 9057 9613 10220 10868 12011 12809 13679 14607 14823 15876 17021 18247 17559 18880 20317 21856 20254 21856 23600 25472 22925 24823 26891 29115 10022 10620 11273 11969 13288 14142 15072 16063 16385 17505 18722 20021 19387 20784 22302 23924 22331 24018 25851 27814 25240 27230 29393 31714 !0935 11574 12271 13013 14500 15407 16394 17445 17869 19053 20339 21709 21124 22596 24192 25896 24308 26078 27999 30052 27445 29526 31784 34201 11806 12484 13223 14009 15658 16617 17659 18767 19288 20535 21888 23327 22788 24332 26005 27789 26202 28054 30060 32202 29560 31730 34082 36596 12643 13359 14138 14966 16771 17780 18875 20039 20654 21962 23379 24886 24389 26004 27752 29613 28028 29959 32049 34277 31599 33857 36301 38909 13451 14203 15021 15890 17841 18904 20050 21268 21974 23341 24820 26393 25938 27621 29442 31379 29794 31802 33974 36287 33573 35915 38450 41151 14234 15020 15876 16785 18890 19993 21189 22460 23255 24678 26219 27855 27442 29191 31083 33094

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20,0 .

.

.

.

.

.

.

.

24.0 .

28.0

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 25 25 25 25 25 50 50 50 50 50 50 75 15 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

4.0 .

275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

27466 30681 13614 17906 21835 25525 29048 32446 14322 18854 22998 26887 30598 34176 15017 19786 24142 28226 32121 35876 15700 20703 25267 29544 33621 37550 16373 21607 26378 30845 35101 39201

28163 31562 13770 18141 22189 26028 29720 33302 14463 19065 23323 27359 31238 35000 15141 19968 24431 28660 32723 36660 15803 20851 25516 29934 34176 38285 16452 21717 26580 31184 35602 39880

29649 33318 14283 18896 23194 27293 31253 35111 14995 19846 24361 28663 32817 36861 15691 20774 25501 30003 34346 38571 16371 21681 26617 31314 35842 40245 17038 22571 27711 32600 37310 41887

31508 35489 14994 19903 24501 28904 33176 37354 15735 20892 25715 30331 34804 39175 16459 21857 26902 31725 36395 40954 17166 22801 28063 33089 37953 42697 17859 23727 29201 34427 394~0 44406

33591 37915 15815 21052 25979 30719 35334 39863 16589 22084 27248 32208 37034 41763 17344 23093 28487 33665 38695 43622 18083 24079 29701 35090 40322 45442 18807 25046 30890 36488 41918 47227

35844 38240 40539 43332 16707 17655 22297 23618 27579 29278 32680 34763 37665 40143 42573 45456 17517 18502 23377 24748 28906 30665 34238 36392 39442 42000 44559 47531 18307 19329 24432 25851 30203 32021 35761 37984 41179 43815 46502 49561 19080 20137 25463 26930 31471 33348 37251 39543 42880'45594 48404 51549 19837 20929 26475 27988 32715 34649 38713 41071 44549 47338 50270 53499

N O T E : Detector t i m e constant at a reference velocity of 5 ft/sec. For SI Units:

1 ft = 0 . 3 0 5 m 1000 B T U / s e c = 1055 k W

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENI)IX (2

72E-123

Table C-4-l(kk)

Table C-4-1(kk)

Installed Spacing of Heat Detector: 50 feet Fire Growth Rate: IS0 Seconds to 1000 B T U / S E C Alpha: 0.044 B T U / S E C '

I n s m l ~ d Spacing of Heat De~cmr: 50 feet Fire Growth Rate: 150 Seconds to 1000 B T U / S E C Alpha: 0.044 B T U / S E C s

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

CEILING HEIGHT IN FEET 28.0

.

TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 1494 1637 1837 60 2041 2305 2663 80 2568 3009 3555 100 3120 3754 4516 120 3687 4541 5542 140 4272 5369 6630 40 2075 2207 2409 60 2794 3039 3386 80 3496 3880 4398 100 4193 4741 5456 120 4893 5628 6564 140 5571 6544 7724 40 2572 2696 2907 60 3460 3681 4034 80- 4274 4656 5174 100 5097 5637 6343 120 5914 6633 7549 140 6730 7647 8794 40 3026 3136 3358 60 4020 4262 4627 80 4991 5364 5892 100 5937 6462 7174 120 6869 7564 8480 140 7793: 8678 9817 40 3409 3542 3775 60 4563 4802 5179 80 5658 6024 6566 100 6721 7233 7957 120 7762 8439 9364 140 8790 9650 10794 40 3791 3924 4167 60 5076 5310 5701 80 6292 6648 7204 100 7466 7962 8701 120 8612 9268 10207 140 9741 10574 11729 40 4156 4286 4540 60 5567 5794 6198 80 6900 7241 7812 100 8183 8658 9414 120 9367 10060 11016 140 10583 11457 12628 40 4507 4633 4897 60 6041 6257 6674 80 7427 7810 8397 100 8795 9326 10099 120 10128 10821 11795 140 11435 12307 13496 40 4846 4967 5241 60 6504 6703 7133 80 7974 8358 8961 100 9439 9970 10761 120 10862 11556 12549 140 12256 13128 14337 40 5177 5289 5573 60 6877 7133 7577 80 8503 8889 9508 100 10062 10594 11402 120 11574 12268 13280 140 13053 13924 15153 40 5500 5602 5895 60 7295 7552 8009 80 9018 9404 10039 100 10668 11200 12026

2075 3076 4177 5373 6658 8025 2651 3792 4998 6279 7635 9066 3163 4450 5778 7160 8603 10109 3628 5059 6510 8000 9538 11127 4060 5629 7201 8800 10434 12112 4468 6169 7859 9564 11296 13063 4855 6684 8489 10298 12126 13983 5226 7179 9094 11005 12929 14874 5584 7655 9679 11690 13707 15739 5929 8117 10246 12355 14463 16582 6264 8565 10798 13002

2342 2639 2963 3539 4049 4605 4868 5625 6449 6319 7353 8475 7883 9219 10667 9552 11213 13012 2924 3225 3553 4248 4753 5304 5672 6417 7232 7200 8217 9328 8831 10147 11583 10559 12199 13986 3450 3765 4105 4917 5431 5990 6455 7202 8018 8076 9087 10194 9784 11089 12517 11580 13204 14980 3932 4263 4621 5543 6072 6647 7201 7960 8787 8924 9942 11054 10721 12026 13453 12593 14211 15983 4381 4730 5105 6132 6681 7274 7911 8688 9531 9740 10773 11898 11630 12945 14381 13585 15208 16983 4805 5172 5564 6692 7261 7874 8590 9388 10251 10525 11577 12720 12510 13842 15293 14551 16188 17973 5209 5593 6003 7227 7817 8451 9241 10062 10947 11282 12357 13520 13362 14716 16185 15491 17146 18948 5596 5996 6424 7741 8352 9007 9870 10713 11621 12014 13113 14300 14189 15567 17059 16406 18084 19906 5969 6386 6830 8238 8869 9545 10478 11345 12276 12723 13848 15060 14993 16396 17913 17297 19000 20846 6329 6762 7224 8719 9371 10068 11068 11958 12914 13413 14563 15801 15776 17206 18749 18167 19897 21768 6679 7128 7606 9187 9859 10577 11642 12556 13535 14086 15262 16525

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16,0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

28.0

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

NOTE:

120 140 40 60 80 100 120 140 40 60 80 100 120 140 '40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

12266 12960 13992 15200 13828 14698 15948 17403 5818 5907 6209 6590 7702 7959 8428. 9002 9521 9906 10556 11335 11259 11790 12634 13633 12942 13635 14685 15919 14584 15453 16724 18205 6055 6202 6514 6908 8100 8356 8838 9428 10011 10396 11061 11860 11837 12367 13228 14250 13602 14293 15363 16622 15323 16190 17482 18991 6344 6491 6813 7219 8489 8745 9238 9845 10492 10875 11554 12373 12403 12930 13808 14853 14250 14937 16027 17310 16048 16911 18224 19760 6628 6775 7105 7523 8871 9125 9631 10253 10964 11344 12038 12876 12960 13482 14377 15445 14886 15568 16677 17986 16760 17618 18951 20515 6907 7053 7391 7822 9246 9498 10015 10653 11429 11804 12512 13369 13507 14024 14936 16025 15512 16187 17315 18649 17461 18311 19666 21256

16540 17997 19567 19077.20775 22674 7020 7484 7977 9642 10334 11072 12201 13139 14143 14742 15944 17234 17286 18772 20370 19848 21635 23563 7352 7831 8340 10087 10799 11557 12748 13710 14737 15384 16612 17928 18017 19531 21157 20663 22480 24437 7676 8170 8695 10522 11253 12031 13284 14268 15319 16012 17267 18610 18733 20276 21930 21462 23309 25296 7994 8503 9042 10948 11698 12496 13808 14815 15890 16629 17909 19278 19436 21007 22690 22246 24124 26141 8306 8828 9383 11365 12134 12952 14323 15353 16450 17234 18540 19936 20126 21725 23438 23017 24926 26973

D e t e c t o r t i m e c o n s t a n t at a reference velocity of 5 ftlsec.

F o r SI Units:

1 ft = 0 . 3 0 5 m 1000 B T U / s e c = 1055 k W

J

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

1990 Edition

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-124

AUTOMATIC FIRE I)ETECTORS

T a b l e C.-4-1 (11) I n s t a l l e d S p a c i n g of H e a t D e t e c t o r : 50 feet F i r e G r o w t h Rat: 300 Seconds to 1000 B T U / S E C A l p h a : 0.011 B T U / S E C s

T a b l e C-4-1 (!1) I n s t a l l e d S p a c i n g of H e a t Detector: 50 feet F i r e G r o w t h R a t : 300 Seconds to 1000 B T U / S E C Alpha: 0.0ll BTU/SEC s

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

8.0 .

.

.

.

.

.

.

12.0 .

.

.

.

.

.

1 6 : 0 20.0 .

.

.

.

.

.

.

.

.

.

.

.

TAU RTI AT

2 4 . 0 28.0 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

1990 Edition

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

942 1344 1772 2227 2703 3209 1272 1775 2275 2795 3333 3890 1559 2143 2728 3320 3922 4537 181.1 2484 3145 3807 4474 5150 2048 2802 3538 4269 4977 5706 2272 3104 3892 4680 5464 6249 2486 3395 4241 5089 5930 6770 2692 3648 4575 5482 6379 7271 2892 3910 4898 5862 6813 7757 3087 4164 5211 6231 7235 8229 3251 4410 5516 6591

1 1 0 0 1296 1 5 2 0 1769 2043 1649 2008 2409 2849 3328 2256 2807 3414 4075 4794 2923 3686 4523 5433 6420 3634 4636 5726 6908 8189 4392 5653 7016 8493 10091 1 4 1 2 1 5 9 8 1815 2058 2326 2039 2374 2758 3187 3660 2704 3221 3808 4454 5185 3413 4138 4951 5847 6826 4165 5123 6187 7355 8628 4959 6171 7508 8970 10560 1690 1 8 7 6 2094 2333 2607 2398 2726 '3104 3528 3996 3131 3630 4201 4840 5544 3895. 4593 5386 6269 7240 4695 5617 6657 7810 9074 5531 6699 8008 9454 11036 1 9 4 4 2133 2356 2605 2878 2731 3058 3438 3862 4330 3532 4025 4591 5 2 2 5 5925 4356 5040 5 8 2 2 6695 7659 5208 6107 7130 8271 9526 6091 7228 8515 9946 11518 2180 2374 2603 2858 3138 3043 3374 3758 4186 4658 3911 4404 4971 5605 6305 4795 5474 6251 7120 8080 5701 6589 7 6 0 2 8733 9982 6 6 3 2 7750 9023 10441 12005 2403 2602 2838 3101 3388 3339 3675 4065 4500 4978 4272 4768 5339 5977 6680 5 2 1 5 5893 6671 7541 8500 6175 7058 8067 9194 10439 7156 8264 9527 10938 12495 2615 2820 3063 3334 3629 3622 3963 4361 4804 5289 4618 5118 5696 6340 7048 5619 6300 7 0 8 2 7954 8916 6632 7514 8524 9851 10896 7663 8765 10025 11432 12985 2818 3028 3279 3558 3861 3893 4241 4647 5099 5593 4951 5 4 5 7 6043 6695 7410 6009 6694 7 4 8 2 8361 9327 7075 7959 8972 10102 11349 8154 9256 10516 11923 13475 3014 3230 3488 3775 4087 4155 4510 4924 5385 5888 5273 5786 6380 7041 7765 6386 7 0 7 7 7873 8759 9733 7503 8 3 9 2 9411 10547 11798 8631 9736 10999 12408 13963 3203 3425 3690 3985 4306 4409 4770 5194 5664 6177 5585 6106 6709 7380 8113 6752 7451 8255 9150 10132 7920 8815 9842 10985 12242 9096 10205 11474 12888 14446 3387 3614 3887 4190 4519 4655 5024 5456 5936 6459 5889 6417 7030 7711 8454 7109 7815 8629 9534 10525

2340 3848 5572 7487 9573 11818 2620 4175 5939 7889 10008 12283 2901 4508 6313 8298 10449 12754 3176 4842 6691 8713 10896 13231 3442 5173 7070 9131 11348 13712 3699 5498 7447 9550 11802 14198 3948 5816 7821 9968 12258 14686 4188 6128 8189 10383 12712 15175 4422 6432 8551 10794 13165 15663 4649 6730 8908 11201 13614 16150 4871 7021 9259 11602

4.0 .

.

.

.

.

.

8.0 .

.

.

.

.

.

12.O 1 6 . 0 2 0 . 0 24.0 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

28.0 .

.

.

.

.

.

.

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

.

275 275 300 300 300 300 •300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

7646 8327 9229 10264 11416 12681 14060 8690 9549 10664 11940 13362 14926 16634 3429 3566 3799 4078 4390 ~727 5088 4651 4896 5271 5712 6202 6734 7307 5814 6185 6721 7344 8035 8789 9604 6942 7457 8171 8996 9911 10912 11999 8049 8724 9633 10679 11841 13115 14502 9141 9993 11114 12399 13829 15401 17115 3603 3741 3979 4265 4585 4930 5300 4886 5130 5512 5963 6462 7005 7587 6105 6474 7018 7651 8353 9118 9943 7287 7797 8520 9355 10282 11294 12390 8443 9112 10030 11086 12259 13543 14939 9583 10426 11556 12851 14291 15871 17593 3774 3911 4154 4448 4775 5129 5507 5116 5359 5748 6208 6717 7270 7863 6391 6757 7309 7 9 5 2 8665 9441 10277 7625 8130 8861 9707 10646 11669 12776 8831 9492 10419 11486 12670 13965 15371 10018 10851 11990 13295 14746 16336 18067 3941 4079 4327 4628 4962 5324 5710 5342 5584 5980 6448 6967 7530 8133 6672 7034 7594 8248 8972 9759 10607 7958 8456 9196 10054 11004 12039 13158 9214 9865 10801 11880 13076 14382 15799 10397 11268 12416 13733 15195 16796 18537 4105 4242 4496 4803 5146 5516 5910 5564 5805 6207 6684 7213 7786 8399 6949 7306 7874 8538 9274 10072 10931 8287 8777 9526 10395 11357 12404 13534 9536 10231 11177 12267 13475 14794 16222 10806 11678 12835 14164 15638 17251 19002

N O T E : Detector t i m e constant at a reference velocity of 5 ft/sec. F o r S l Units:

1 ft = 0.305 m 1000 B T U / s e c = 1055 k W

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

At'PEr~DIX C:

72E-

Tab~ C-4-l(mm)

Table C-4-1(mm)

Installed Spacing of Heat Detecmr~ 50 feet Fire Growth R a ~ : 500 Seconds to 1000 B T U / S E C Alpha: 0.004 B T U / S E C '

Installed Spacing of Heat Detector: 50 feet Fire Growth Rate: 500 Seconds to I000 B T U / S E C Alpha: 0.004 B T U / S E C s

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI &T .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

28.0

.

TAU RTI AT .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

56" 40 706 56 60 1053 56 80 1435 56 100 1851 56 120 2299 56 140 2777 112 40 920 112 60 1322 112 80 1748 112 100 2200 112 120 2672 112 140 3173 168 40 1107 168 60 1568 168 80 2039 168 100 2529 168 120 3040 168 140 3572 224 40 1278 224 60 1798 224 80 2312 224 100 2845 224 120 3393 224 140 3959 280 40 1 4 3 9 280 60 2004 280 80 2571 280 100 3146 280 120 3732 280 140 4333 335 40 1 5 9 2 335 60 2204 335 80 2817 335 100 3433 335 120 4058 335 140 4694 391 40 1740 391 60 2396 391 80 3053 391 100 3710 391 120 4373 391 140 5045 447 40 1 8 6 7 447 60 2580 447 80 3280 447 100 3978 447 120 4679 447 140 5369 503 40 2000 503 60 2759 503 80 3501 503 100 4240 503 120 4958 503 140 5695 559 40 2128 559 60 2932 559 80 3717 559 100 4474 559 120 5241 559 140 6011 615 40 2253 615 60 3101 615 80 3910 615 100 4716

875 1381 1948 2574 3253 3981 1068 1610 2208 2859 3564 4311 1247 1836 2469 3148 3874 4644 1415 205i 2724 3435 4188 4981 1572 2257 2969 3715 4498 5317 1721 2453 3206 3988 4801 5648 1863 2642 3436 4253 5098 5973 2000 2824 3658 4511 5388 6292 2132 3000 3873 4762 5671 6605 2260 3172 4083 5006 5948 6911 2385 3338 4287 5245

1073 1738 2496 3337 4258 5241 1252 1950 2734 3597 4532 5535 1427 2163 2975 3862 4818 5840 1593 2372 3217 4130 5108 6149 1751 2574 3455 4396 5399 6461 1902 2771 3688 4660 5689 6773 2047. 2960 3916 4920 5976 7084 2187 3145 4138 5175 6259 7392 2322 3324 4355 5425 6538 7697 2453 3498 4567 5670 6813 7999 2581 3668 4774 5911

125

1 2 9 2 1 5 3 2 1793 2076 2130 2557 3020 3520 3091 3735 4432 5186 4159 5047 6008 7047 5323 6481 7732 9083 6577 8025 9590 11280 1 4 6 2 1 6 9 7 1955 2236 2331 2751 3210 3708 3316 3953 4647 5399 4406 5287 6245 7281 5590 6740 7988 9337 ' 6863 8303 9864 11552 1633 1864 2119 2398 2534 2948 3403 3899 3545 4175 4864 5614 4657 5531 6484 7518 5862 7003 8246 9594 7152 8584 10141 11827 1799 2029 2284 2562 2738 3147 3599 4093 3777 4400 5085 5832 4912 5777 6726 7757 6136 7270 8508 9853 7446 8869 10420 12104 1 9 5 8 2190 2446 2725 2939 3346 3796 4288 4009 4626 5308 6052 5168 6026 6970 7999 6414 7539 8772 10114 7742 9156 10702 12383 2112 2347 2605 2886 3135 3542 3992 4484 4238 4853 5532 6274 5425 6277 7216 8243 6693 7810 9038 10377 8041 9445 10986 12664 2260 2499 2760 3044 3327 3736 4186 4679 4465 5078 5755 6497 5680 6528 7464 8488 6972 8082 9306 10642 8340 9737 11273 12948 2404 2646 2911 3199 3514 3925 4378 4873 4687 5301 5979 6720 5932 6778 7712 8735 7250 8356 9575 10909 8640 10030 11561 13232 2544 2790 3059 3351 3696 4112 4568 5065 4906 5522 6200 6943 6182 7 0 2 7 7960 8982 7526 8628 9845 11177 8939 10323 11850 13519 2679 2930 3204 3500 3875 4294 4754 5255 5121 ,5740 6420 7164 6428 7274 8208 9229 7799 8900 10115 11445 9236 10617 12140 13806 2811 3067 3345 3646 4050 4474 4938 5442 5332 5954 6638 7384 6 6 7 1 7519 8453 9476

4.0 .

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

.

24.0 .

28.0

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671 671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 839 894 894 894 894 894 894

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

5517 6319 2374 3267 4111 4952 5787 6621 2493 3430 4307 5182 6050 6916 2610 3570 4498 5408 6309 7205 2724 3722 4686 5630 6562 7489 2837 3871 4871 5848 6812 7768

6219 7212 2506 3501 4487 5479 6485 7507 2624 3660 4683 5709 6745 7797 2740 3815 4874 5933 7001 8082 2854 3968 5062 6154 7252 8362 2965 4117 5247 6371 7500 8638

7084 8297 2706 3835 4977 6147 7350 8590 2828 3997 5176 6379 7612 8880 2947 4157 5372 6607 7871 9166 3063 4313 5564 6832 8125 9448 3178 4467 5753 7053 8376 9727

8070 9531 2940 4221 5540 6910 8337 9824 3066 4388 5744 7146 8602 10114 3190 4553 5944 7379 8864 10402 3311 4715 6142 7609 9122 10686 3430 4874 6336 7835 9377 10968

9170 10385 11715 10909 12430 14095 3200 3484 3789 4650 5119 5627 6166 6853 7603 7761 8698 9722 9439 10654 11984 11201 12720 14384 3331 3619 3929 4822 5296 5810 6375 7066 7820 8001 8940 9967 9705 10922 12252 11491 13010 14673 3460 3753 4068 4992 5472 5990 6580 7277 8035 8237 9181 10211 9970 11188 12521 11779 13299 14963 3586 3884 4204 5160 5644 6168 6783 7485 8247 8472 9420 10453 10232 11453 12788 12066 13587 15252 3710 4012 4337 5324 5815 6344 6983 7691 8458 8703 9656 10694 10491 11716 13054 12351 13874 15540

N O T E : Detector time c o n s t a n t at a reference velocity of 5 ft/sec. F o r S I Units:

1 ft = 0.305 m 1000 B T U / s e c = 1055 k W

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E--126

A U T O M A T I C FIRE DETECTORS

Table C - 4 - 1 ( n n ) I n s ~ i l e d Spacing of Heat Detector: 50 feet Fire Growth Rate: 600 Seconds to 1000 B T U / S E C Alpha: 0.003 B T U / S E C j

Table C.,-4-1 ( n n ) Installed Spacing of Heat Detector: 50 feet Fire Growth R a ~ : 600 Seconds to 1000 B T U / S E C Alpha: 0.003 B T U / S E C s

CEILING HEIGHT IN FEET

CEILING HEIGHT IN FEET TAU RTI &T .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

4.0 .

.

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16,0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

24.0

TAU RTI &T

28.0

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

56 56 56 56 56 56 112 112 112 112 112 112 168 168 168 168 168 168 224 224 224 224 224 224 280 280 280 280 280 280 335 335 335 335 335 335 391 391 391 391 391 391 447 447 447 447 447 447 503 503 503 503 503 503 559 559 559 559 559 559 615 615 615 615

40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100

645 979 1350 1757 2195 2665 826 1204 1610 2044 2503 2991 987 1414 1860 2322 2811 3323 1136 1610 2092 2591 3110 3649 1274 1797 2314 2849 3399 3967 1406 1965 2526 3096 3678 4275 1532 2131 2730 3335 3948 4574 1654 2291 2927 3565 4211 4866 1762 2445 3117 3790 4467 5152 1874 2595 3303 4009 4718 5414 1982 2741 3484 4223

818 1016 1311 1669 1868 2416 2484 3250 3154 4156 3874 5130 978 1163 1500 1842 2081 2611 2721 3460 3409 4382 4145 5372 1131 1309 1689 2018 2298 2809 2958 3677 3665 4617 4423 5623 1274 1450 1 8 7 2 2193 2512 3010 3 1 9 7 3898 3926 4856 4698 5878 1410 1 5 8 6 2048 2364 2721 3209 3433 4120 4185 5096 4978 6135 1 5 3 8 1715 2217 2531 2924 3405 3664 4340 4441 5337 5256 6393 1 6 6 2 1840 2380 2694 3120 3598 3890 4559 4693 5577 5530 6652 1781 1961 2537 2852 3311 3788 4111 4775 4 9 4 1 5816 5801 6910 1895 2078 2690 3007 3497 3974 4327 4988 5183 6052 6068 7 1 6 7 2006 2192 2838 3157 3679 4156 4538 5197 5421 6285 6330 7421 2115 2303 2983 3304 3856 4334 4745 5403

1233 2058 3006 4063 5217 6460 1373 2222 3191 4266 5437 6696 1514 2390 3379 4473 5660 6935 1653 2558 3570 4682 5886 7176 1789 2726 3762 4894 6115 7420 1920 2892 3954 5106 6345 7666 2047 3054 4144 5319 6576 7914 2171 3214 4332 5530 6807 8162 2291 3370 4518 5740 7038 8411 2408 3523 4701 5949 7268 8659 2522 3674 4882 6155

1 4 7 0 1728 2007 2480 2938 3432 3645 4336 5082 4945 5898 6928 6366 7608 8950 7899 9454 11133 1 6 0 5 1860 2137 2639 3094 3587 3824 4513 5258 5142 6093 7122 6581 7G20 9160 8129 9681 11359 1 7 4 3 1995 2271 2801 3253 3744 4007 4692 5435 5343 6290 7317 6798 8034 9372 8362 9910 11587 1 8 8 0 2131 2406 2966 3414 3903 4192 4873 5614 5546 6489 7514 7017 8249 9586 8596 10141 11815 2016 2266 2541 3130 3576 4064 4378 5056 5795 5751 6690 7713 7238 8466 9801 8832 10373 12046 2148 2400 2675 3294 3739 4226 4566 5240 5978 5957 6893 7914 7461 8685 10018 9071 10607 12277 2278 2532 2808 3457 3901 4388 4753 5426 6162 6165 7097 8116 7686 8906 10236 9311 10843 12510 2404 2660 2939 3618 4063 4549 4940 5611 6346 6373 7302 8319 7912 9128 10456 9552 11080 12745 2528 2787 3068 3776 4222 4710 5126 5797 6531 6581 7508 8523 8138 9351 10676 9795 11318 12981 2648 2911 3195 3932 4380 4870 5310 5981 6716 6788 7714 8728 8365 9574 10898 10038 11557 13218 2766 3032 3320 4085 4536 5029 5492 6164 6900 6994 7919 8933

.

.

.

.

.

.

.

.

8.0 .

.

.

.

.

.

.

.

12.0 .

.

.

.

.

.

.

.

16.0 .

.

.

.

.

.

.

.

20.0 .

.

.

.

.

.

.

24.0

28.0

.

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC)

FIRE SIZE AT DETECTOR RESPONSE (BTU / SEC) 25 25 25 25 25 25 50 50 50 50 50 50 75 75 75 75 75 75 100 100 100 100 100 100 125 125 125 125 125 125 150 150 150 150 150 150 175 175 175 175 175 175 200 200 200 200 200 200 225 225 225 225 225 225 250 250 250 250 250 250 275 275 275 275

4.0 .

275 275 300 300 300 300 300 300 325 325 325 325 325 325 350 350 350 350 350 350 375 375 375 375 375 375 400 400 400 400 400 400

615 615 671 671 671671 671 671 727 727 727 727 727 727 783 783 783 783 783 783 839 839 839 839 839 ~39 894 894 894 894 894 894

NOTE:

120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140 40 60 80 100 120 140

4944 5681 2087 2884 3662 4415 5178 5943 2190' 3024 3837 4616 5407 6199 2291 3161 3989 .4812 5631 6450 2390 3296 4152 5005 5852 6697 2487 3429 4313 5195 6068 6939

5654 6588 2220 3124 4029 4947 5883 6842 2323 3262 4199 5145 6108 7091 2424 3397 4365 5340 6330 7337 2523 3530 4528 5532 6547 7579 2620 3660 4689 5720 6762 7818

6516 7674 2411 3448 4509 5606 6743 7924 2517 3589 4682 5806 6968 8171 2621 3728 4851 6003 7190 8415 2722 3863 5017 6197 7409 8657 2822 3997 5181 6388 7625 8896

7496 8907 2634 3821 5059 6359 7723 9153 2744 3966 5234 6560 7947 9398 2851 4108 5407 6759 8170 9641 2956 4248 5577 6956 8391 9883 3059 4386 5745 7151 8609 10123

8591 9798 10281 11798 2882 3151 4236 4691 5672 6346 7198 8124 8816 10023 10525 12038 2995 3269 4384 4843 5850 6527 7401 8328 9040 10246 10768 12279 3106 3384 4531 4993 6026 6706 7602 8531 9263 10470 11010 12520 3215 3497 4675 5141 6200 6883 7802 8733 9485 10692 11251 12761 3323 3608 4817 5288 6372 7059 8000 8933 9706 10914 11491 13001

11120 13456 3443 5186 7083 9138 11343 13694 3564 5341 7266 " 9342 11567 13934 3683 5495 7448 9546 11790 14174 3800 5647 7628 9750 12013 14414 3916 5797 7807 9953 12236 14654

D e t e c t o r t i m e c o n s t a n t a t a r e f e r e n c e velocity of 5 f t / s e c .

F o r S I Units:

l ft = 0 . S 0 5 m I 0 0 0 B T U / s e c = 1055 k W

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX C

C-5 Smoke Detector Spacing For Flaming Fires. C-5-1 General. C-5-1.1 Ideally, the placement of smoke detectors should be based on a knowledge of fire plume and ceiling j e t flows, smoke production rates, particulate changes due to aging, and the unique o p e r a t i n g characteristics of the detector being used. Knowledge of plume and j e t flows enabled the heat detector spacing information presented in Section C-3 to be developed. Unfortunately, that knowledge does not apply to smoke originating from smoldering fires. U n d e r s t a n d i n g of smoke production and aging lags considerably behind that of heat production. The operating characterisitics of smoke detectors in specific fire environments are not often measured or made generally available for o t h e r than a very few combustible materials. Hence, the existing data base precludes the development of complete e n g i n e e r i n g design information for smoke detector location and spacing. C-5-1.2 In flaming fire, s m o k e d e t e c t o r r e s p o n s e is affected by ceiling height, size, and rate of growth of the fire in much the same way as heat detector response. T h e thermal energy of the flaming fire transports smoke particles to the smoke sensor just as it does heat to a heat sensor. While the relationship between the a m o u n t of smoke and the a m o u n t of heat p r o d u c e d by a fire is highly depend e n t upon the t"uel and the way it is burning, research has shown that the relationship between t e m p e r a t u r e and optical density of smoke remains essentially constant within the fire p l u m e and on the ceiling in the proximity of the phnne. C-5-1.3 In smoldering fires, thermal energy also provides a force for transporting smoke particles to the smoke sensor. However, because the rate of energy release is usually small and the rate of growth of the fire is slow, other factors such as airflow may have a stronger influence on the transport of smoke particles to the smoke sensor. Additionally, for smoldering fires, the relationship between temperature and the optical density of smoke is not constant and therefore not useful. C-5-1.4 S m o k e detectors, r e g a r d l e s s of w h e t h e r they detect by sensing scattered light, loss of light transmission (light extinction), or reduction of ion current, are particle detectors. Particle concentration, size, color, and size distribution affect each sensing technology differently. It is generally a c c e p t e d that the c o n c e n t r a t i o n o f s u b - m i c r o n diameter particles p r o d u c e d by a flaming fire is greater than that p r o d u c e d by a smoldering fire. Conversely, the concentration of larger particles is greater from a smoldering fire. It is also known that the smaller particles agglomerate and form larger ones as they age and are carried away from the fire source. More research is required to provide sufficient data to first predict particle concentration and behavior and secondly to predict the response of a particular detector.

C-5-2 Smoke Detector Spacing for Flaming Fires. C-5-2.1 Unlike heat detectors, listed smoke detectors are not given a listed spacing. It has become general practice to install smoke detectors on 30 ft (9.1 m) centers on

72E- 127

smooth ceilings with reductions made empirically to that spacing for beamed or joisted ceilings and fi)r areas having high rates of air movement. Adjustments of spacing fi)r ceiling height are also necessary as discussed herein. (1-5-2.1.1 Figures C-5-2.l.l(a), (b), and (c) are based on the assumption that smoke t r a n s p o r t to the detector is entirely from fire plume dynamics. It assumes that the ratio of the gas t e m p e r a t u r e rise to the optical density of the smoke is a constant and that the detector will actuate at a constant value of optical density. T h e data presented in Figures C-5-2.1.1 (a), (b), and (c) clearly indicate that spacings considerably greater than 30 ft (9.1 m) are acceptable for detecting geometrically growing flaming fires when Q,t is 1000 Btu/sec or more. C-5-2.1.2 In the early stages of development of a growing fire, when the heat release rate is approximately 250 Btu/sec or less, the environmental effects in spaces having high ceilings may dominate the transportation of smoke. Examples of such environmental effects are heating, cooling, humidity, and ventilation. G r e a t e r thermal energy release fi-om the fire may be required to overcome such environmental effects. Until the growing fire reaches a sufficiently high level of heat release, closer spacing of smoke detectors on the ceiling will not significantly improve the response of the detectors to the fire. Therefore, when considering ceiling height alone, smoke detectors should not be placed closer than 30 ft (9.1 m) spacing except in unt, sual instances where an engineering analysis indicates additional benefit will result. Other construction characteristics must also be considered; see Chapters 4 and 9. C-5-2.2 T h e method used to determine the spacing of smoke detectors is similar to that used for heat detectors and is based on fire size, fire growth rate, and ceiling height. C-5-2.2.1 In o r d e r to use Figures C-5-2.1.1(a), (b), or (c) to d e t e r m i n e the installed spacing of a smoke detector, the designer must first select, Qa, the threshold flaming fire size at which detection is desired• C-5-2.2.2 In addition to threshold flaming fire size, 0.,/, the designer must consider the expected fire growth rate. Figures C-5-2.1. l(a), (b), and (c) are used for fast, medium, and slowly growing flaming fires, respectively. See Table C-2-2.2.1(a) for heat release rates and fire growth rates. Co5-2.2.3 As an example, to determine the installed spacing of a smoke detector on a 30-ft (9. l-m) ceiling required to detect a 750 Btu/sec fire that is growing at a medium rate, use Figure C-5-2.1.1 (b).

Example 3.

Input:

Ceiling Height: 30 ft (9.1 m) O~t = 750 Btu/sec (791 kW) Fire growth rate: medium

Spacing:

From Figure C-5-2.1.1(b), using the 750 Btu/sec (791 kW) curve, installed spacing is 41 ft (12.8 In).

As another example, consider a 20-ft (6. l-m) ceiling with a threshold fire size of 250 Btu/sec growing at a meditnn rate.

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

7 2 E - 128

AUTOMATIC FI RE DETECTORS

9O

80

60

50 t~3

(/3 "10

t-

30

",=.2 :;: :;. :=~= : ".::, .... ".~:~ =~: ="i • ""'?'~v ':" ':~:.:~.

: =..:+~ ~,=;...=...i.!.~.,i.=.=.=,. ~=...i,:,.:i,:::; ~..=:,..i; :~~=~ ".' i~"~ii;';" :'~:':.'~: ", 'i'~'i; ',~=' i~'::"': :!:~: i~=.

= 1000 Btu/sec

,.:i~i~,.',.,:i~i=.~i~,. " '!:'.% : ..=~~U':='~:

10

'i '"" ! "~i"

20

30

40 Ceiling

F i g u r e C-5-2.1.1(a)

1990

Height

50 (ft)

S m o k e D e t e c t o r - - Fast Fire.

Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

60

'

:

.

~

.....

:

70

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX C

7 2 E - 129

go

8O

70

6C

50

A

e"

"~

40

¢0

_.m

3O

,

! L::!.:;::. :

~:-i" v"

.....

.:~"~;: ~'"~'.'~,-:~'. -. : -, ......... " ...... :-, '

20

.~:.::....~ .;:,,'.'-:+.~:~.:.,.

;.::,I...:L.~:,::..:,~I.,~,

i"i :i;:. J,:., !

i'/~" i :

i

......

'.":":

12

:.::~::::~"~:: "::: ~:--,:

500 ;.~::.i: :i i,!~ii,..,::,-~

"!':~'"~"~""; :':i':: .~ ?,; ...................

.., ........

:~:'~':,::~.~:'+:".~.:~ :~0-

i:.::::.~.i;.:,..!:.!.

~:~

i.

" '": ": ~'.~,- ~, ,.~:.. :ii i

10

20

30

40 C e i l i n g Height

Figure C-5-2.1.I(b)

50

6O

70

(ft)

Smoke Detector -- Medium Fire.

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-130

AUTOMATIC FIRE I)ETECI'ORS

90

80

,o

\

60

A

a,

50

e-

t,/} m

t'~

40

°:~ .,U= =-:.~ q: ,i., ~:=~",~=.=.!.

::. ""

20

'~" -~' ~"' :'~ 1'I: .: " ~'~'~,.~. ?' .......... ~ ........................

f:!::~,:'.~:~'.~';~. :~.'.;i:.~..~::~.;'[~:.;ii~:~

12

!'~i~'~:-' "~.i °' '~ "=' "~::~"

10

20

FigurerC-5-2.1.1(c)

1990 Edition

30 4O Ceiling Height (ft)

5O

S m o k e D e t e c t o r - - S l o w Fire.

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

60

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

APPENDIX

Example 4.

Input:

Ceiling Height: 20 ft (6.1 m) Q,t = 250 Btu/sec (264 kW) Fire growth rate: medium

Spacing:

From Figure C-5-2.1.1(b), using the 250 Btu/ sec (264 kW) curve, installed spacing for the smoke detector is 30 ft (9.1 m) since the intersect of a vertical line at 20 ft (6.1 m) and the O~t = 250 curve falls within the shaded area below 30 ft (9.1 m) spacing. See C-5-2.1.2.

Note: Both a slow and fast rate of growth fire would resuh in the same 30 [i (9. I m) spacing using Figures C-5-2.1. l(c) and C-5-2.1.1(a).

C-5-2.2.4 Smoke detector spacings of less than 30 ft (9.1 m) nmy be used for detection of flaming fires where no other detector type is suitable and where environmental conditions allow the use of a smoke detector. C-6 Theoretical Considerations. c-6-1 I n t r o d u c t i o n . The design methods of this Appendix are the joint result of extensive experimental work and of mathematical modeling of the heat and mass transfer • t 1,2,8,t.) processes m~olved. This section outlines models and data correlations used to generate the design data presented in this appendix. Only the general principles are described. More detailed information may be obtained from the references.

C-6-2 Temperature and Velocity Correlations. In order to predict the operation of any detector, it is necessary to characterize the local e n v i r o n m e n t created by the fire at the detector location. For a heat detector the important variables are temperature and velocity of the gases at the detector. T h r o u g h a program of full-scale tests and using mathematical modeling techniques, general expressions for temperature and velocity at a detector location have been developed. ''~'~':~The expressions are valid for fires that grow according to Q = xff where Q is the theoretical fire heat release rate, X is the fire intensity coefficient characteristic of a particular fuel and configuration, and t is time. The calculations used to produce the spacing curves assume that the ratio of the actual convective heat release to the theoretical heat release for all fuels is equal to that ratio for wood crib fires.

C-6-3 Heat Detector Model. The heating of a heat detector is given by the equation, s dTo dt

_ (l) ( T ~ - T d ) (Y)

, where: T a = temperature rating of the detector .~..g= gas temperature at the detector = detector time constant (DET TC)

72E-131

C

The time constant is a measure of the detector's sensitivity and is given by: MC yhA where: M C h A

= = = =

the detector element mass detector element specific heat convection heat transfer coefficient surface area of detector element

h varies approximately as the square root of the gas velocity, U. It is customary to speak of the time constant Y at a reference velocity of U o = 5fps. Y = Y,, (Uo / U) "~ Y can be measured most easily by a "phmge test. '':* It can also be related to the listed spacing of a detector through a calculation;z Table C-3-2.1.1 results fi'om these calculations. This model uses the temperature and velocity of the gases at the detector to predict the temperature rise of the detector element. Detector operation occurs when the preset conditions are reached. The detector's sensitivity can also be expressed in units that are i n d e p e n d e n t of the air velocity used in the test to d e t e r m i n e the time c o n s t a n t . T h i s is k n o w n as the Response Time Index, RTI. m

RI1 = 'r V U The RTl value can therefore be obtained by multiplying T,, values by X/U~:,;for example, when 67U'.~ 5 ft/sec, a % of 30 sec corresponds to an RTI of sec '/'' ft ~/'' or 35.9 sec I/~ m '/''A detector having a RTI of 67.1 sec'/'' ft '/~ would have a "r of 23.7 sec, if measured in an air velocity of 8 ft/seo

C-6-4 Ambient Temperature Considerations. (Reference also 3-2.1.2.) T h e m a x i m u m a m b i e n t t e m p e r a t u r e expected to occur at the ceiling dictates the choice of temp e r a t u r e rating for a fixed t e m p e r a t u r e heat detector application. But the m i n i m u m ambient temperature likely at the ceiling constitutes the worst-case condition for response by that detector to a fire. The mass, specific heat, heat transfer coefficient, and surface area of a detector's sensing element characterize that detector's time constant. The response time by a given detector to a given fire depends only on the detector's time constant and the difference between the detector's temperature rating and the ambient temperature at the detector when the fire starts. When ambient temperature at the ceiling decreases, more heat from a fire will be needed to bring the air s u r r o u n d i n g the detector's sensing element up to its rated (operating) temperature; this translates into slower response and, in the case of a growing fire, a larger fire size at the time of detection. In a room or work area that has central heating, the m i n i m u m ambient temperature would usually be 70°F (21.1°C). Certain warehouse occupancies may only be heated enough to prevent water pipe freeze-up; in that case the m i n i m u m ambient should be considered 35°F (2°C) even though d u r i n g many

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E- 132

AUTOMATIC FIRE i)ETECTORS

months of the year the actual ambient is much higher. An unheated building in northern states and Canada should be p r e s u m e d to have a minimum ambient o f - 4 0 ° F (-40°C) or lower. C-6-5 H e a t and S m o k e A n a l o g y -- S m o k e D e t e c t o r Model. For smoke cletectors, the t e m p e r a t u r e of the gases at the detector is not directly rclcvant to detection, but the mass concentration and size distribution of particulates are relevant. For many types of smoke, the mass concentration of particles is directly proportional to the optical density of tlae smoke, D,,. A general correlation for flaming fires has been shown to exist between the temperature rise of the fire gases at a given location and the optical density. If the optical density at which a detector responds, Do, was known and was i n d e p e n d e n t of particle size distribution, tbc response of the detector could be a p p r o x i m a t e d as a function of heat release rate of the burning fuel, rate of fire growth, and ceiling height, assuming that the above correlation held. However, the more popular ionization and light scattering detecto,'s cxhibit widely different D o whcn particle size distribution is changed; hence, whcn DOfor these detectors is meast, rcd in o r d e r to predict response, the test aerosol used must be vet'), carefully controlled so that particle size distribution is constant.

Appendix

D

Referenced Publications

D-I The following doct, ments or portions t h e r e o f are referenced within this standard tbr informational purposes only and thus are not considcred part of the requircments of this document. T h e edition indicated for each reference is the current edition as of the date of the NFPA issuance of this document. D-I.I NFPA Publications. National Fire Protection Association. 1 Batterymarch Park, P.O. Box 9101, Quincy, MA 02269-9101. N FPA 71-1989, Standard for the Installation, Maintenance, and Use of Signaling Systermfor" Central Station Service N FPA 74-1989, Standard for the Installation, Maintenance, and Use of Household Fire Warning Equipment N Ir PA 90A- 1989, Standard for the lnstallatimt of Air Conditioning and.Ventilating Systems NFPA 101-1988, Life Safety, Code NFPA 231 C- 1986, Standard for Rack Storage of Materials

D-I.2 Other Publications. D-I.2.1 National Electrical Manufacturers Association, Signaling Protection and Communications Section, Washington, DC.

Guide Jbr Proper Use of Smoke Detectors"i, Duct Applications. I. Heskes|ad, G., "The Initial Co,wective Flow in Fire: Seventeenth Synq~osium on Combustion," T h e Combustion Institute, l'ittsburgh, PA (1979). 2. Heskestad, G. and Delichatsios, M.A., "Environments of Fire Detectors - - Phase 1: Effect of Fire Size, Ceiling Height and Material." Volume ! - - "Measurements" (NBS-GCR-77-86), Volume I1 - - "Analysis" (NBSGCR-77-95). N a t i o n a l T e c h n i c a l l n f i ) r m a t i o n Service (NTIS), Springfield, VA 22151. 3. Heskestad, G., "Investigation of a New Sprinkler Sensitivity Approval Test: T h e Plunge Test," FMCR Tech. Report 22485, Factory Mutual Research Corporation, I 151 Providence T u r n p i k e , Norwood, MA 02062. 4. Heskestad, G., "Characterization of Smoke Entry and Responsc for l~roducts-of-Conabustion Detectors," Proceedings, 7th International Conference on Problems of Automatic Fire Detection, Rheini~h-Westt, dischen Technischen Hochschule Aachen (March 1975). 5. Vytenis Babrauskas, J. Randall Lawson, W.D. Walton and William H. Twilley: National Bureau of Standards: "Upholstered Furniture Heat Release Rates Measured With a Furniture Calorimeter," Dec. 1982 (NBSIR 82-2604). National Institute of Standards and Technology, Center tbr Fire Research, Gaithersburg, MD 20889. 6. NFPA 204M, Standard o'n Smoke and Heat Venting, National Fire Protection Association, 1 Batterymarch Park, P.O. Box 9101, Quincy, MA 02269-9101. 7. J.R. Lawson, W.D. Walton and W.H. Twilley, "Fire Performance of Furnishings as Measured in the NBS Ftn'nittn'e Calorimeter, Part 1," National Institute of Standards and Technology, Center fi)r Fire Research, Gaithersburg, MD 20889, N u m b e r NBSIR 83-2787, August 1983. 8. R. Schifiliti, "Use of Fire Phune T h e o r y in the Design a n d Analysis o f Fire D e t e c t o r a n d S p r i n k l e r Response," Masters Thesis, Worcester Polytechnic Institute, Center fiar Firesafety Studies, Worcester, MA, 1986. 9. C. Beyler, "A Design Method for Flaming Fire Detection", Fire Technology, Volume 20, N u m b e r 4, November- 1984. 10. D . D . Evans and D.W. S t r o u p , " M e t h o d s to Calculate Response T i m e o f H e a t a n d S m o k e Detectors Installed Below Large Unobstrncted Ceilings," National Institute of Standards and Technology, Gaithcrsburg, M D 20889, N u m b c r NBSIR 85-3167, Fcbrnary 1985, lsstmd July 1986. 11. Alpcrt, "Ceiling Jets," Fire Technology, August 1972. Alpcrt and Ward, SFPE Technology Report 1984.

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

INDEX

72E-133

Index © 1 9 9 0 N a t i o n a l F i r e P r o t e c t i o n A s s o c i a t i o n , All R i g h t s R e s e r v e d . "1"he c o p y r i g h t in this i n d e x is s e p a r a t e a n d d i s t i n c t f i ' o m t b e c o p y r i g h t in t h e d o c u m e n t w h i c h it i n d e x e s . T h e l i c e n s i n g p r o v i s i o n s set f o r t h t b r t h e d o c t n n e n t a r c n o t a p p l i c a b l e to t h i s i n d e x . T h i s i n d e x m a y n o t b e r e p r o d u c e d in w h o l e o r in p a r t b y a n y m e a n s w i t h o u t t h e e x p r e s s w r i t t e n p e r m i s s i o n o f t h e N a t i o n a l F i r e P r o t e c t i o n A s s o c i a t i o n , Inc.

Combination detectors

-AAcceptance tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Air c o n d i t i o n i n g s y s t e m s

see T e s t s , A c c e p t a n c e

Fire-gas detectors and .................................. 6 - 4 , A-6-4.1 Smoke detectors and ................................... 4 - 5 , A-4-5.1 Air duct systems, s m o k e detectors in . . . . . . . . . . . . . . 4 - 5 . 2 . 1 , 6 - 4 . 2 . 1 , 8-3.4.3, 9-3.2, A-9-3.2.2 Installation of .................................... . ... 9 - 4 , A - 9 - 4 . 8

Air sampling-type detector Dcfimtion .......................................................

2-2.2.3

Air s y s t e m s

Definition ......................................................... 2-1. I . . . . . . . . . see s p c c i t i c t y p e s u c h as B e a m c o n s t r u c t i o n

Construction

-DDesign curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-3-4 Detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . see Fire d e t e c t o r s , specific t y p e s s u c h as H e a t d e t e c t o r s 9 - 5 , Figs. A - 9 - 5 . 4 . I. 1, A-9-5.4.:4.1 t h r u A - 9 - 5 . 4 . 3 . 3 Location .......................................................... 9-5.5 Number required ..................................... 9 - 5 . 4 , A-9-5~4

D o o r release service, smoke detectors for . . . . . . . . . . . . . . . .

Return .............................................. 9-3.2.2, A-9-3.2.2 Suppl) .......................................................... 9-3.2.1 Approval of d e w c e s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 - a , A-2-5.1

Area detectors, within s m o k e compartments . . . . . . . . . . . . . . . . . .

9-3.1

Dust contamination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

-BBeam construction

-E-

..............................................

Fire-gas detectors and ............................. Heat detectors and ................................... Smoke detectors and ...............................

Bimetallic s e n s i n g e l e m e n t

2-4. I. 1

6-3.6, A-6-3.6.3 3-5.3, A-3-5.3 4-4.7, A-4-4.7.4

.................................

3-2.1.3(a)

Electrical conductivity rate-of-change detector . . . . . . . . Electrical conductivity s e n s i n g element . . . . . . . . . . . . . . . . . . Ember Definiiion ..........................................

Cable, heat-sensitive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2. 1.3(d) Catalytic e l e m e n t type of fire-gas detectors . . . . . . . . . . . . . . . . . . . 6 - 2 . 2 Ceiling(s) Beamed ..................................... .. see B e a m c o n s t r u c t i o n Dethfition 2-1. I Height D e f i n i t i o n ". . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1. I Determination ............................................... C-2-3 Fire d e v e l o p m e n t a n d . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . : ....... C-2 High ...................................................... B-I-4, B-I-7 Heat detcctors and ............................ 3-5. 1.2, A - 3 - 5 . 1 . 2 Level ............................................... '............. 2-3.1.1 Peaked ............................................. 3-5.4.1, A-3-5.4. I Fire-gas detectors and 6-3:7.1 Smoke detectors and .... 4-4.8.1 Shapes of ........................................................... 2-3 Shed Fire-gas detectors and .................................... 6-3.7.2 Heat detc,ctors and ...................... 3 - 5 . 4 . 2 , Fig. A - 3 - 5 . 4 . 2 Smoke detectors and ..................................... 4-4.8.2 Sloped ....................................................... 2-3.1.2 Fire-gas detectors and ....................................... 6-3.7 H e a t d e t e c t o r s find . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 5 . 4 , Fig. A - 3 - 5 . 4 Smoke detectors and ........................................ 4-4.8 Smooth ......................................................... 2-4. 1.4 Fire-gas detectors ............................................ 6-3.4 Heat detectors ..................................... 3 - 5 . 1 , A-3-5.1 S m o k e d e t e c t o r s . . . . . . . . . . . . . . . 4 - 4 . 5 , A - 4 - 4 . 5 . 2 , Fig. A - 4 - 4 . 5 . 2 Surfaces ............................................................. 2-4 Suspended Fire-gas detectors and ....................................... 6-3.8 Smoke detectors and ........................................ 4-4.9 Temperature ........................... 3 - 4 . 3 , 4 - 6 . 2 . 1 , T a b l e '.4-3. I • i on of fire detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 -2, 4 - 3 Classtficat C l e a n i n g of detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-4. I, A-8-4.1 Cloud chamber s m o k e detection . . . . . . . . . . . . . . . . . . . . . . . . . !~ . . . . " 4 - 2 . 4 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

3-2.3.2(d)

3-2.1.3(b)

5 - 2 . 1 . I, A - 5 - 2 . 1 . 1

-F-

-C-

.

4-4.2.1

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

Field of view . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5-5 5-2.1.2

Definition .......................................................

Fire detectors Classilications ................................................. 2-2, 4-3 I)efinitio,~ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 Operating modes ................................................ 2-2.3 Other . ......................................................... Chap. 7 Definition 2-2.1.5 Principles of ................................................ 4-2, A-4-2 Selection .................................................. 5-3, A-5-3. I Types of .......................................................... 2-2.2 Fire-gas detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C h a p . 6, A - 6 Definition ....................................................... 2-2.1.4 H e a t i n g , v e n t i l a t i n g , a n d a i r c o n d i t i o n i n g . .' . . . . . . . . 6 - 4 , A - 6 - 4 . I Location and spacing ................................... 6-'1, A - 6 - 3 . I O p e r a t i n g prin-ciples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2 Special considerations ................................ 6-5, A - 6 - 5 . 1 . 3 "1 c s t i n g . . . . . . . . . . . . . . . . . . . . . . . . . . . . .....- . . . . . . . . . . . . . . . . . . . . 8-2.6, 8-3.6 .

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

.

Fire[s] C h a r a c t e r i s t i c s , and d e t e c t o r s e l e c t i o n . . . . . . . . . 5-3, 7-2, A-5-3.1 Development of . .................................... C-2-2, C-5-2.1.2 E x p o s u r c to, tests t b l l o w i n g . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5 Flaming, smoke detector spacing tbr .......................... C-5 Growth of. ........................ .~. . . . . . . . . . . . . . . . . . . . . . . . . . . . C-2-2.3 Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-2-2.2, C-2-2.4

Fixed temperature detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Spacing of ...............

3-2. I

C - 3 - 2 , C - 3 - 4 . I. 1, Figs. C - 3 - 4 . I (a t h r u [)

Flame Definition ............................................

". . . . . . . . . . .

5-2; 1.3 Chap. a Delinition .......................................... 2-2. 1.3.1, 5-2. 1.4 Field o f view c o n s i d e r a t i o n s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5 Fire characteristics and selection ................................ 5-3 Operating principles .............................................. 5 -9 Other co{tsklcrations 5-6 Sensitivity Delinition ................................................... 5-2.1.5

Flame detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

72E-134

AUTOMATIC FIRE DETECTORS

Spacing considerations ................................... 5-4, A - 5 - 4 Testing .................................................... 8-2.6, 8-3.5 Floors, raised ....................................................... 4-4.9 Fusible alloy ................................................... 3-2.1.3(c)

-MMaintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

8 - 1 , 8-4, A-8-4.1 Multiple wavelength infrared detectors ...................... 5-2.2.4

-N-

-GGas sensing f i r e d e t e c t o r s . . . . . . . . . . . . . . . . . . . . Gases

see F i r e - g a s d e t e c t o r s

Definition ........................................................... Girders .............................................................

Nonrestorable d e t e c t o r s Definition .......................................................

2-2.3.1

6-1 2-4.1.2 -O-

-HHazards, specific .................................................

6-3.1. I

Heat Definition ...........................................................

3-1

Other fire detectors ........................................... Chap. 7 Classification ..................................................... 7-1. I Fire characteristics ................................................ 7-2 Location and spacing ............................................. 7-3 Special considerations ............................................ 7-4 Testing .................................................... 8-2.6, 8-3.5

Heat detection systems, analysis o f . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-4 Heat d e t e c t o r s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C h a p . 3, C - 3 Definition ....................................................... 2-2.1.1 Location ........................ 3-4, A-3-4. I, A - 3 - 5 . 3 , Fig. A - 3 - 4 . 1 Model ............................................................. C-6-3 Operating principles .............................................. 3-2 Spacing ............................................. 3-5, A-3-5.1, C-3 Testing ........................................ 8-2.3,.8-3.3, A-8-2.3. I H e a t release rates . . . . . . . . . . . . . T a b l e s C - 2 - 2 . 2 . 1 ( a a n d b), C - 2 - 2 . 2 . 2 H e a t i n g systems Fire-gas detectors and .................................. 6-4, A-6-4.1 Smoke detectors and ................................... 4 - 5 , A-4-5.1 Heat-sensitive cable .......................................... 3-2.1.3(d) H i g h a i r m o v e m e n t areas, smoke d e t e c t o r s . . . . . . . . . . . . . . . . . . . 4-6.5 H i g h rack storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6.4, A-4-6.4 High-temperature area ............................................ 3-4.3 H V A C s y s t e m s ... see Ah" c o n d i t i o n i n g s y s t e m s ; H e a t i n g s y s t e m s , Ventilating systems

-IInfrared detectors ............................... 5-2.2.2 thru 5-2.2.4 Inspection forms ..................................................... 8-6 I n s p e c t i o n s . . . . . . . . . . . 8 - 1 , 8-2, A-8-2; see a l s o M a i n t e n a n c e ; T e s t s Initial i n s t a l l a t i o n . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . '8-2, A - 8 - 2 Periodic ................................................... 8-3, A - 8 - 3 . I Installation .................................................... 2-7, A-2-7 Fire-gas detectors ................................... 6-5.1, A-6-5.1.3 Inspection of .................................. .. . . . . . . . . . . . . 8 - 2 , A - 8 - 2 S m o k e d e t e c t o r s . . . . . . . . 4 - 6 . I. 1, 4 - 6 . 1 . 3 , 9 - 4 , A - 4 - ! .3, A - 4 - 6 . 1 . 1 In a i r d u c t s y s t e m s . . . . . . . . . . 9 - 1 . 2 , 9 - 3 . 2 , 9 - 4 , A - 9 - 1 . 2 , A - 9 - 3 . 2 . 2 Ionization smoke detectors ....................................... 4-2.1 Irregular areas ....................................... 3-5.1.1, A-3-5.1.1

-LL i g h t scattering smoke d e t e c t o r s . . . . . . . . . . . . . . . . . . . . . 4-2.2, A-4-2.2 Line-type detectors ................................................ 3-4.2 Definition ....................................................... 2-2.2.1 Liquid expansion sensing element ........................ 3-2. 1.3(e) Location ................................................ see a l s o S p a c i n g Fire-gas detectors ......................................... 6-3, A-6-3 Heat detectors ................................. 3-4, A-3-4. I, A - 3 - 5 . 3 Other detectors .................................................... 7-3 Smoke detectors .................... 4 - 4 , 4-6. 1.2, 4 - 6 . 5 . 3 , A - 4 - 4 . 1 , A-6-5.3, A-4-6.1.2 For door release service .................................... 9-5.5 In a i r d u c t s y s t e m . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-4, A-9-4.8

.p. Partitions Fire-gas detectors and .......................................... 6-3.9 Smoke detectors and .......................................... 4-4.10 P h o t o e l e c t r i c l i g h t o b s c u r a t i o n s m o k e d e t e c t i o n .. 4 - 2 . 3 , A - 4 - 2 . 3 P h o t o e l e c t r i c . l i g h t s c a t t e r i n. g. s m o k e d e t e c t i o n . . . 4 .- 2.2 . A . -.4 - 2 2 Pneumatsc • r a t e - o f - r i s e t u b m g . . . . . . . . . . . . . . . . . . . . .3.- .2.3. 2 ( a a n d b) Projected b e a m - t y p e d e t e c t o r s . . . . . . . . . . . . . . . . 4 - 4 . 3 , 4 - 4 . 5 . 2 , 4 - 6 . 3 , A - 4 - 4 . 3 . 1 . 1 , Fig. A - 4 - 4 . 5 . 2 Purpose of standard ................................................. 1-1

-RRadiant energy Definition ......................................................... 5-1. I R a d i a n t e n e r g y - s e n s i n g f i r e d e t e c t o r s . . . . . 5 - 3 . 1 , 5 - 4 . 1 . 1 , A - 5 - 3 . I, A-5-4.1.1 Definition ....................................................... 2-2.1.3 Testing .................................................... 8-2.5, 8-3.5 Rate compensation detectors ..................................... 3-2.2 Rate-of-rise detectors .............................................. 3-2.3 S p a c i n g . . . . . . . . . . . . . . . . C - 3 - 3 , C - 3 - 4 . i . 2 , Figs. C - 3 - 4 . l ( g ) t h r u ( i ) Records of inspection, maintenance, and tests ................. 86Requirements, common ....................................... Chap. 2 Restorable detectors Definition ....................................................... 2-2.3.2 Return air system ................................... 9-3.2.2, A-9-3.2.2

-SSampling-type fire-gas detectors ...................... 6-3.3, A-6-3.3 Sampling-type smoke detectors .................................. 4-4.4 Scope o f s t a n d a r d . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2 Semiconductor type of fire-gas detectors ...................... 6-2. I Single wavelength i n f r a r e d d e t e c t o r s . . . . . . . . . . . . . . . . . . . . . . . . 5-2.2.2 Smoke d e t e c t o r s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C h a p . 4, A-4 A r e a . . . . . . . . . . . . . . ". . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . '... 9-3. I Classification ....................................................... 4-3 Definition ....................................................... 2-2.1.2 For control of smoke.spread ......................... C h a p . 9, A - 9 For door release service .......................................... 9-5 Heating, ventilating, and air conditioning .......... 4-5, A-4-5. I Installation .. ........................................... 4-1.3, A-4-1.3 Location and spacing ..................................... 4-4, A-4-4 F o r f l a m i n g fires . . . . . . . . . . . . . . . . . . . . . . . . . . . ...; ................ C-5 Model ............................................................. C-6-5 Operating principles .............................................. 4-2 Special considerations ................ 4-6, 8-3.4, A-4-4, A-8-3.4.2 Testing .................................................. 8-2.4, 8-3.4.1

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

INt)VX

Solid joist construction ......................................... 2-4.1.3 Fire-gas detectors and .......................................... 6-3.5 Heat detectors and .......................... 3-5.2, Figure A-3-5.2 Smoke detectors and ................................. 4-4.6, A-4-4.6

Spacing

Definition ......................................................... 2-1.1 Fire-gas detectors and .................................... 6-3, A-6-3 Flame detectors and .............................................. 5-4 G u i d e to . . . . . . . . . . . . . . . . . . . . . . .

H e a t detectors . . . . . . . . ".'.'.'.'.'.'.'.'.'.'.'.'.." ....... ".'.' 3"-'5 ~"A" ~,'-'51.... C-I-3,ApP'c-3C O t h e r detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-3 Sensitivity and . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . App. B S m o k e detectors . . . . . . . . . . . . . . . 4-4, 4-6.2.4, 4-6.5.4, A-4-4. |,-C-5

Spark

Definition ..........................................

Spark/ember d e t e c t o r s

5-2.1.6, A-5-2.1.6

Definition ....................................................... 5-2.1.7 Operating principles ............................................ 5-2.3 Sensitivity Definition ................................................... 5-2.1.8 Testing .......................................................... 8-3.5.2 Spot-t,y p e d e t e c t o r s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 - 2 . 3 . 2 ( b ) , 4-3.1 Dennition ....................................................... 2-2.2.2 Location Fire-gas detectors .................................. 6-3.2, 6-3.4.1 Heat detectors ...................... 3 - 2 . 2 . 2 , 3-5. I, Fig. A-3-4.1 Smoke detectors ....................... 4-4.2, 4-4.5.1, A-4-4.2.1 Stora[~e . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . see H i g h r a c k s t o r a g e Stratification F i r e - g as. . .d. e. .t.e. .c.t.o. .r.s. . .a. n. .d. . . . . . . . . . . . . . . . . . . . . . . 6-3 I 2 Smoke detectors and ............................. 4 - 4 . 1 . 2 , A - 4 - 4 . 1.2 Supply air system, smoke detectors in ............... 9-3.2.1, 9-4.7

72E- 135

-T-

Temperature Ambient, considerations ....................................... C-6-4 Classification ........................................ :¢-3, T a b l e 3-3.1 Correlations ..................................................... C-6-2 Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Chap. 8 Acceptance .......................................................... 2-6 Following an alarm ................................................ 8-5 Initial . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2, A - 8 - 2 Periodic ..................................... .. . . . . . . . . . . . . . 8 - 3 , A-8-3.1 Thermal lag ....................................................... 3-2.1.2 Thermoelectric effect detector .............................. 3-2.3.2(c) Total coverage ...................................................... 2-7.4

-UUltraviolet detector ............................................. Ultraviolet/infrared detectors ..................................

5-9.2.1 5-2.2.3

-VVelocity correlations ............................................. C-6-2 V e n t i l a t i n g systems Fire-gas detectors and .................................. 6 - 4 , A-6-4.1 Smoke detectors and . . . . . . . . . . 4 - 5 , A-4-5.1

-W-

Wavelength Detinition ..........................................

5-2.1.9, A-5-2.1.9

1990 Edition

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

SUBMITTING PROPOSALS ON NFPA TECHNICAL COMMITTEE DOCUMENTS Contact NFPA Standards Administration for final date for receipt of proposals on a specific document.

INSTRUCTIONS Please use the forms which follow for submitting proposed a m e n d m e n t s . Use a separate form for each proposal. 1.

For each d o c u m e n t on which you are proposing a m e n d m e n t indicate: (a)

T h e n u m b e r a n d title of the d o c u m e n t

(b)

T h e specific section or paragraph.

2.

Check the box i n d i c a t i n g whether or not this proposal r e c o m m e n d s new text, revised text, or to delete text. \

3.

In the space identified as "Proposal" include the wording you propose as new or revised text, or indicate if you wish to delete text.

4.

In the space titled "Statement of Problem a n d Substantiation for Proposal" state the problem which will be resolved by your r e c o m m e n d a t i o n a n d give the specific reason for your proposal inc l u d i n g copies of tests, research papers, fire experience, etc. If a statement is more than 200 words in length, the technical committee is authorized to abstract it for the Technical Committee Report,

5.

Check the box i n d i c a t i n g whether or not this proposal is original material, a n d if it is not, indicate source.

6.

If s u p p l e m e n t a r y material (photographs, diagrams, reports, etc.) is included, you may be required to submit sufficient copies for all m e m b e r s and alternates of the technical committee.

7.

T y p e or print legibly in black ink.

NOTE: The NFPA Regulations GoverningCommittee Projects in Paragraph 10-10 state: Each proposal shall be submitted to the Council Secretary and shall include: (a) identification of the submitter and his affiliation (Committee. organization, company) where appropriate, and (b) identification of the document, paragraph of the document to which the proposal i:s directed, and (c) a statement of the problem and substantiation for the proposal, and (d) proposed text of proposal, including the wording to be added, revised (and how revised), or deleted.

86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association onIMarch SAS for designated user FORM F O R (NFPA). P R O PLicensed, O S A Lby S agreement, O N N Ffor P Aindividual T E C use H Nand I Csingle A L download COMM T T E28, E 2014 D otocINNOVAR U M E NESPACIOS TS CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

Mail to: Secretary, Standards Council National Fire Protection Association, 1 Batterymarch Park, P.O. Box 9101, Quincy, MA 02269-9101 Note: All proposals must be received by 5:00 p . m . E . S . T . / E . S . D . T , on the published proposal closing date.

Date 5/18/85

Name John B. Smith

Tel. No. 617-555-1212

Address 9 Seattle St.. Seattle, WA 02255 Representing (Please indicate organization, company or self) 1. a) Document Title:

Protective SignalingSYstems

b) Section/Paragraph: 2-7.1

Fire Marshals Assn. of North America

N F P A No. &Year NFPA 72D

(Exception)

FOR OFFICE USE ONLY Log #:

2. Proposal recommends: (Check one) [] new text [] revised text P~ deleted text.

Date Rec'd: Proposal #:

3. Proposal (include proposed new or revised wording, or identification of wording to be deleted):

Delete exception.

4. Statement of Problem and

A properly installed and maint~ =4 The occurrence of one or mo "trouble" signal because it in to future malfunctior o / ~ e s available on these sys~rpcv~aC,,y it on all systems will h

"s~s~buld be free of ground faults. ~a~a~fs should be required to cause a a~Y~dition that could contribute ./',Ground fault protection has been widely and its cost is negligible. Requiring • installations, maintenance and reliability.

5. [] This Proposal is original material. [] This Proposal is not original material; its source (if known) is as follows:

( N o t e : O r i g i n a l m a t e r i a l is c o n s i d e r e d t~* be the submitter*s tlwn idea based t m o r as a result o f his o w n e x p c r l e n c e , t h o u g h t , t~r research a n d . |o t h e best o f his k n o w l e d g e , is n o t copied from another s~urce.)

I agree to give NFPA all and full rights, including rights of copyright, in this Proposal and I understand that I acquire no rights in any publication of NFPA in which this Proposal in this or another similar or analogous form is used.

86E4DE1D-09B1-418B-ACA0-44A93BD8E902 PT F'~'F TT~ eFp'l~'T1;" FNDM FN !) l~''rFl PDNPN"AT

FORM FOR PROPOSALS ON N F P A T E C H N I C A L C O M M I T T E E D O C U M E N T S

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

Mail to: Secretary, Standards Council National Fire Protection Association, 1 Batterymarch Park, P.O. Box 9101, Quincy, MA 02269-9101 Note: All proposals must be received by 5:00 p . m . E . S . T . / E . S . D . T , on the published proposal closing date. Date

Name

Tel. No.

Address Representing (Please indicate organization, company or self) 1 . a) Document Title:

N F P A No. & Year FOR OFFICE USE ONLY

b) Section/Paragraph:

Log #:

2. Proposal recommends: (Check one) [] new text [] revised text [] deleted text.

Date Rec'd: Proposal #:

3. Proposal (include proposed new or revised wording, or identification of wording to be deleted):

4. Statement of Problem and Substantiation for Proposal:

5. [] This Proposal is original material. [] This Proposal is not original material; its source (if known) is as follows:

( N o t e : O r i g i n a l m a t e r i a l is c o n s i d e r e d to be t h e s u b m i t t e r ' s o w n idea based t)n or as a result c~f his o w n e x p e r i e n c e , t h o u g h t , or research a n d . to the best of his knowledge, is not copied from another source.)

I agree to give NFPA all and full rights, including rights of copyright, in this Proposal and I understand that I acquire no rights in any publication of NFPA in which this Proposal in this or another similar or analogous form is used.

Signature

PLEASE USE S E P A R A T E FORM FOR EACH PROPOSAL 86E4DE1D-09B1-418B-ACA0-44A93BD8E902

Copyright 2014 National Fire Protection Association (NFPA). Licensed, by agreement, for individual use and single download on March 28, 2014 to INNOVAR ESPACIOS SAS for designated user CESAR AUGUSTO ORTIZ RINCON. No other reproduction or transmission in any form permitted without written permission of NFPA. For inquires or to report unauthorized use, contact [email protected].

uedo ""e~io 'Z~H @ szuewJeE) "lOJd uo!loun=l IJoddns £66L se!oue~JeuJ3 'meqo "Z~H Jo! elln S e^!lomOJd-qseld S p!nb!7 g66L se!oue6JeUJ~ "uJeqo •ZeH Jo| s~ns eNloe~,OJd-JOdeA t66t edoEI flexes ei!7 £g6L sJelqB~d eJLd Jot uJeZSXSXleles UelV leUOSJed ~g6L 'ddv 6u!qleeJ8 peulmuoo-JleS L86~ SUJJOI!UJ'I)~JOM/UOI|e|SSL6L Ou!lqfl!=l eJL-I 'lonJ~S 3ee~oo-j "lOJd t,/.6L sJetq6L-I eJ!~ leJnionJiS JOl se~OlO P.J..6L 6u!iq6!=l eJ!=l leJnDnJiS 'sieuJleH ~J.6L 6u!qlOlO e~lDe~,OJd W-ilL (d!l pue goinqs) selZZON Xmds t~96¢ spemqJ, uo!toeuuoo esoH 896t esn 'eJeO esoH eJL-I ~96t ecJOH eJH L96~ 0u!tsel "tu!evl 'es(1 'sJepp~T1 punoJ O "ldeQ OJL-I ~£6L sJeppe-I punoJ O 'ldeQ eJ!:l Lg6L s~!U~l 6u!duJnd elqeuod L~6L seo!^eo le]Jev 'O'-I Ou!lse.Lt~L6t sn|emdclv 6u!duJn d 'O'-I ~o s~sel LL6L snleJeddv eJ!d eA!|OLUO|nV ¢06L "]S,~S lUeLueR~UelN tuep!ou I "(3':1 L9SL JeO!llO ,~,e~es '~deo eJ!d LOSL 'fiOJd qlleeH pus /4eleS leUO!~ednooo "),deo m!:l 00gL suJ~JDO~d "p~ "lOJd 9Jld 10 uoIle:l!PmOOV t9~L Hoe~v m!-I le!l!Ul 0WL seJ!d iosseA eu!m~l ol puodseld oq M sueiq6!=l eJ!d peses-pue7 SOI~L ~ueJfiOJd VgOS O:J t,Ot,~ SUO!lnlOA::l DU!U!eJ1 eJ!-I OA!7 £0~L suelueo 6u!u!ml ~u!pl!n8 ;~0t,L spJoosl:l 'slJOdel:l ~u~u~J1 L0t% se!lddns JOI~M leJnEI '~ ueqJnqns L£~L 'wwo O "AJeS eJpi o!lqnd L;~;~L o!lqnd JOj seo!~Je S d-I "le^eQ L0~L sdnoJ~) 6u!Pl!n 8 peuueld u! '1o~d m!:J tl~tL '0#iN 'mo~oIN le)10OH lepO/~l g~tL "1~1~|~"~Ul~J/ " ~ 'b'~JOM~J!-I ~ . L /~eldS!o o!lqn d 'sNJoMeJ!-I ~:~LL e~oo ~eNoou peuuewun ~LL 'leno '~OJd Jo~rutsul mid ¢~0L 'lenO "#CUdJOl~onp:l eJ!:l o!lqnd g£0L 'lenO "|CUd JOleO!|se^ul eJ!:l C£0L •lenO 'JOJd JoloedSul eJi-i L£0L 'leno "JOJd JO0!~O DJH L~0L sue!o!uLioe 1 leo!pew Je|Ll~!::l eJ!.l I~00L •leno 'joJ d Je|~!.40J!-I blodJ!v ~00 I "leno "lOJd JO~!JC] ~00L "leno 'lO~d ~e~,qD!-I eJ!:l L00L 'onJ|S o!JOlS!H lo "qeqeEI t~L6 sel!S pue seJn:lonJl8 o!JOiS!H £L6 d!qsJoM to seOeld ;~L6 suo!~oelloO uJnesn~ pue suJnesnw Lt6 suot~oellOO ~e~q!'l pus se!Jmq!7 0L6

selo!qeA leUO!leeJoeEI 0L0g sells "le~Sul emOH peJnioejnue[N VL0g 'uJJel JO]O~ 'se^!SOldx3 86t, suo!leOO'l (pe!J!SSglO) •ZeH u! "d!nb=l "oel=l JO# s~sno 'sJodeA 'sese O ~o sselo I~lL6t~ "lSUl "oelq JOj suo!teoo'l 'ze H I sselo jo 'ss~elO V/.6P seJnsoloU=l peOJnd 96t~ Sle!Je~elAI eAlsOIdx3 S6t~ suo!to~eH 'uJeqO ~lL61~ eleJl!N uJnluouJuJV 06t~ tun!uooJ!Z ~81~ wnluel!l LSt, uJn!seu6elN 08t~ 'duJoo "lOJd mepuodseEI 'OUl 'lain 'zeH g/.t, ~ueploul 'lel~l "Z~H ol 6utpuodseEI LLI~ 6UlUUeld "~JeLU3 ~l~unuJLuOO/1JOdJwI~11~1~ se!i!l!oed lsel eu!6u=l l~l~JOJ!V~:~t~ lenueIN sJOle6!lseAUl eJ!-I ~eJOJ!V I ~ J ~ stue],s~S JeleM UOdJ!V 6W ' suOd!leH doHooEI 8Lt, sXeM~IleM Ou!peo'l L~t~ sleu!tuJe£ uodJw 9L~ 06eu!eJO dLueEI 6U!lend gLt, Selo!qeA enoseEI t~Lt~ selotqeA weo-j '6u~lsez ~tt~ eoueuelu~el~l lJeJOJ!VOLt~ sJe6UeH ~JsJOJ!V60b sJeqs!n6u!ix=l ~eJoJ!v 80b 0u!o!~JeS len-I HeJOJ!VL0b seo!~JeS enoseEI ~JeJoJ!VgOt, seJnpeooJd 'do 6U~|q6!:l eJ!-I 'enoseEI ~Jl~JOJ!VJ~J~0~ sp!nb!7 "uJel.-I "6i$ uJJe:l g6£ s'4Uel 6u!dd!qs elqeZJOd 98g selolqeA ~luel gsg ~Uel p!nbt'l "uJel=l 'eSe~lee7 punojnjepuR 6~g u! seseo pus sp!nb!7 'UJel=l 'sJoMes 'seloquelN 9~£ s~lUel II~UJS Ru!ueelO L~£ ~ sp!nb!7 "tuel-I "doJd ~lg~£ sp!nb!'l 'UJel-I 'ssel 0 L~£ .qedeH "J~,suo0 '$1esseA ;~L£ se~JeqM pug 'sJe!d 'sleu!mJel eu!JelN L0£ sleSSeA uo spmzeH seE) 90£ spJe/~|eo8 pue seu!Je~N g0£ ~eJO

ULO~O

'oe13 1o seJ!.lIo uo(teo!iseAul IAIL06 se~ON Ple!=l luep!oul eJ!d IN906 lenue~ IJodekl e^!:leO!tseAul INt~06 lenuel/1 ,~e,uns/~edmd I~£06 lenueIPt ~uep!oul PleH ~;~06 "d "-IJO| 6U~pOO wJoi~un t06 s~u~ld 6u!teJeue~ o~J~Oel~oJp~H Lgg ~Ul~ld 'ue 0 'Oel:~ illee~S Pelen=l t!sso-j 0~8 s~Ueld |ueuJleeJ/Je~eMe~eM 0~B s~Ueld ~e~od JeelonN ~e~eM lqfl!7 g08 sJo~oeeEi qoJeeseEI JeelonN ~08 "1!0~4 'I,leVl eA!]Oeo!pel:i L08 sleueleiN ~o 'luePl I~0L "Sl,~elN

6u!~u0MpooM 'Ru!sseooJd pOOM ~gg seJ!=l Jn|lnS cJg9 "|ue^eJd "ldx3 'sop,Seld t~g9 JepMod uJn!seuSe~l 'uJnu!uJnlV Lg9 •s~sXs 6u!Xe^uoo o!teuJneud 0~9 suo!leJedO P~eno ~09 e:)!~eS PJeno t09 sepe6!J8 m!-I ele^!J d 009 eeJ.L s~deouoo ,~e,~eseJ!-i 0g5 SleU!wJej. ~q6!oJ-i JOlOW CLg uo!DmOJd eJ!d ~lonJ1 ~Lg t~lonJ.L le!J~,snpul peJeMOd g0g se6p!J8 'sleuunl 'S,~eMqS!H g0S

"~PI~] ,(o siue,,,tgeJ 1 ),uepJeleEI-eJ!-I £:0L SWl!=l 'sel!~Xel 'slSel eJi=i L0L

JOtO~ le!oJetutuoo pue eJnseeld ~0g IOJlUOO e4!-I PueiPI!M JoJ 'uJeqo uJeO-j 86~ ~J~soJo-j Imnl:l JOl suo!1eolunwuJooelel/.~ seJ!-I lsoJo=l JO| 'Jed0 J!V 96
View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF