NFPA 20 - Checklist-firepump

March 2, 2017 | Author: pepitorodirguez | Category: N/A
Share Embed Donate


Short Description

NFPA requirements for fire pumps...

Description

NB:

CHECK LIST FOR FIRE PUMP- NFPA 20 SYSTEMSGENERAL SUBMITTAL REQUIREMENTS:

(i)

This checklist must be completed/answered by consultant(s) by ticking [ √] appropriate boxes (ii) Submit a separate sheet containing explanatory notes against all negated answers (iii) It is axiomatic that the submission has been made by the consultants only upon having read and clearly understood all the relevant provisions of the current Fire Protection, Fire Prevention and Fire/Emergency Control(FP, FP&FF) Regulations

FIRE PUMP INFORMATION [ horizontal or vertical]

1 Manufacturer details provided

YES

NO

2 Model number details provided

YES

NO

3 Manufacturer specification sheet(s) provided

YES

NO

4 Proof that all equipment components are listed

YES

NO

5 GPM rating provided on the plans

YES

NO

6 Head rating provided on the plans

YES

NO

7 RPM's provided on the plans

YES

NO

8 Piping size and type is detailed

YES

NO

OS & Y valve in suction pipe is correctly detailed in the YES plans

NO

10 Size of suction pipe and type is detailed

YES

NO

11 Check valve in pump discharge assembly

YES

NO

YES

NO

13 Vortex plate is provided when stored water is used

YES

NO

14 Indicating valve on the system side of the check valve

YES

NO

Pressure relief valve located between pump and pump discharge

YES

NO

9

12

15

Eccentric taper reducer for suction is detailed (taper at bottom)

FIRE PUMP INFORMATION [horizontal or vertical]

1 Emergency lighting provided in pump room

YES

NO

Automatic sprinkler protection provided in the pump room

YES

NO

YES

NO

Pump room wiring in rigid or liquid tight flexible metal YES conduit

NO

YES

NO

1 Submergence level of pump impellers

YES

NO

2 Well screen and suction and strainer details

YES

NO

3 Dimensions of well

YES

NO

Air relief valves, water level detectors, pressure gauges, YES etc DRIVER INFORMATION

NO

YES

NO

3 Rated horsepower provided

YES

NO

4 RPM's provided

YES

NO

5 Electric or diesel information provided

YES

NO

6 Hours of fuel supply given

YES

NO

YES

NO

2

3 Pump room floor drain provided

4 5

Double backflow preventer valve is detailed

ADDITIONAL INFORMATION VERTICAL PUMPS

4

1 Manufacturer and specification information provided 2 Model number provided

ELECTRIC DRIVERS 1 Electrical circuit schematic provided 2

Schematic for secondary power circuit and transfer equipment

YES

NO

3

Controller near motors(more than 12" above floor and 3 YES ½' clearance to the rear)

NO

YES

NO

4 Controller listed for electric motor drivers

5 Alarm signal provided to an attended location

YES

NO

6 Transfer switch specification and listing provided

YES

NO

7 One transfer switch provided for each individual pump

YES

NO

YES

NO

Closed circuit and liquid cooling details provided in the YES plans

NO

YES

NO

YES

NO

5 Two batteries provided for each engine- rack supported YES

NO

YES

NO

7 Pump room & engine has adequate ventilation provided YES

NO

DIESEL DRIVERS 1 Listed fire pump used 2

3 Equipped with over speed shutdown device 4

Instrument panel with tachometer, oil pressure, and temperature gauges

6 Batteries have two means for recharging shown

Fuel tank is at least 1 gallon per horsepower plus a 5% cushion

YES

NO

YES

NO

YES

NO

1 Jockey pump location and piping is detailed

YES

NO

Jockey pump specification sheet(s) provided with the plans Jockey pump check valve is detailed on the discharge 3 pipe

YES

NO

YES

NO

1 Minimum supply provided

YES

NO

2 Connection to water supply

YES

NO

YES

NO

8

9 The controller is listed for diesel pump use 10

Controller near motors(more than 12" above floor and 3 ½' clearance to the rear)

11 Alarm signal provided to an attended location JOCKEY PUMP INFORMATION

2

WATER SUPPLY INFORMATION

3

FDC location is acceptable (within 50' of a public fire hydrant)

OTHER DETAILS Dedicated ATS for individual Fire pumps sets provided 1 YES for electric driven pumps Dedicated and direct Power supply for the fire pumps 2 sets provided from the main distributin board of the source (DEWA Transformer)

NO

YES

NO

Minimum 1m from all sides provided for easy 3 access/maintenance of fire protection system maintained YES inside the room

NO

Controllers are placed inside the pump room with easy accessiblity

YES

NO

5 Control logic/pressure switch setting details provided

YES

NO

6 Adequate and appropriate ventilations for pump

YES

NO

7 Factory test curve & related test documents provided

YES

NO

For Contractor

Title

Date

For Client/Consultant

Title

Date

4

Signatures/S eals