NERA CityLink - User Manual_2.pdf
March 15, 2017 | Author: Riky Fitriadi | Category: N/A
Short Description
Download NERA CityLink - User Manual_2.pdf...
Description
User Manual CityLink B4008 Rev. M
Section I
:
Equipment Description
Section II
:
ODU Type I Installation
Section III
:
ODU Type II Installation
Section IV
:
ODU Type III Installation
Section V
:
IDU Installation
Section VI
:
Preparations for Operation
Section VII
:
Configuration with NEW-NMS
Section VIII :
Fast Ethernet Configuration
Section IX
:
Troubleshooting
Section X
:
Appendices
© Nera Networks AS
CityLink This section applies only to CE marked equipment
0889 WARNING: Use of this equipment requires a separate license to be applied for by the operator.
DECLARATION OF CONFORMITY (INFORMAL) English Finnish Dutch
French
Swedish Danish German
Hereby, Nera Networks AS, declares that this CityLink is in compliance with the essential requirements and other relevant provisions of Directive 1999/5/EC. Nera Networks AS vakuuttaa täten että CityLink tyyppinen laite on direktiivin 1999/5/EY oleellisten vaatimusten ja sitä koskevien direktiivin muiden ehtojen mukainen. Hierbij verklaart Nera Networks AS dat het toestel CityLink in overeenstemming is met de essentiële eisen en de andere relevante bepalingen van richtlijn 1999/5/EG Bij deze verklaart Nera Networks AS dat deze CityLink voldoet aan de essentiële eisen en aan de overige relevante bepalingen van Richtlijn 1999/5/EC. Par la présente Nera Networks AS déclare que l’appareil CityLink est conforme aux exigences essentielles et aux autres dispositions pertinentes de la directive 1999/5/CE. Par la présente, Nera Networks AS déclare que ce CityLink est conforme aux exigences essentielles et aux autres dispositions de la directive 1999/5/CE qui lui sont applicables. Härmed intygar Nera Networks AS att denna CityLink står I överensstämmelse med de väsentliga egenskapskrav och övriga relevanta bestämmelser som framgår av direktiv 1999/5/EG. Undertegnede Nera Networks AS erklærer herved, at følgende udstyr CityLink overholder de væsentlige krav og øvrige relevante krav i direktiv 1999/5/EF Hiermit erklärt Nera Networks AS, dass sich dieser CityLink in Übereinstimmung mit den grundlegenden Anforderungen und den anderen relevanten Vorschriften der Richtlinie 1999/5/EG befindet“. (BMWi) Hiermit erklärt Nera Networks AS die Übereinstimmung des Gerätes CityLink mit den grundlegenden Anforderungen und den anderen relevanten Festlegungen der Richtlinie 1999/5/EG. (Wien)
Refer to Declaration of Conformity for further details.
2
B4008 Rev. M
CityLink
B4008 Rev. M
3
CityLink
4
B4008 Rev. M
CityLink
B4008 Rev. M
5
CityLink
6
B4008 Rev. M
CityLink
WARNING!
WARNING!
DO NOT remove or insert the Transmitter Unit with DC power on.
This equipment contains components which are sensitive to "ESD" (Electro Static Discharge).
Power to the OutDoor Unit (ODU) is carried on the coaxial cable between the InDoor Unit (IDU) and the ODU. Before connecting or removing the cable, ensure that the primary power to the IDU has been switched off.
It is therefore essential that whenever disassembling the equipment and/or handling PC boards, special precautions to avoid ESD have to be made.
CAUTION! Exposure to strong high frequency electromagnetic fields may cause thermal damage to personnel. The eye (Cornea and lens) is easily exposed.
These precautions include personnel grounding, grounding of work bench, grounding of tools and instruments as well as transport and storage in special antistatic bags and boxes.
CAUTION!
Any unnecessary exposure is undesirable and should be avoided. In Radio-Relay communication installations, orderly setup for normal operation, the general RF radiation level will be well below the safety limit. CLASS 1 LASER PRODUCT
In the antennas and directly in front of them the RF intensity normally will exceed the danger level, within limited portions of space.
IEC825-2: 1993
Dangerous radiation may be found in the neighbourhood of open waveguide flanges or horns where the power is radiated into space.
Use of controls or adjustments or performance of procedures other than those specified herein may result in hazardous radiation exposure.
To avoid dangerous radiation the following precautions must be taken:
The Optical Interface must only be serviced by qualified personnel, who are aware of the hazards involved to repair Laser products.
During work within and close to the front of the antenna; make sure that transmitters will remain turned off. Before opening coaxial - or waveguide connectors carrying RF power, turn off transmitters. Consider any incidentally open RF connector as carrying power, until otherwise proved. Do not look into coaxial connectors at closer than reading distance (30 cm). Do not look into an open waveguide unless you are absolutely sure that the power is turned off.
B4008 Rev. M
When handling Laser products the following precautions must be taken: Never look directly into an open connector or optical cable Before disconnecting an optical cable, the power should be switched off. If this is not possible, the cable must be disconnected from the STM-1 output before it is disconnected from the STM-1 input. When the cable is reconnected it must be connected to the STM-1 input before it is connected to the STM-1 output.
7
CityLink
List of Revisions
8
Rev.
Date
What is changed
C D E
01-10-05 01-12-18 02-02-28
F
02-05-07
G
02-09-18
H
02-10-07
I J
02-12-19
K
03-05-23
L
03-11-25
ODU Type II Installation introduced ODU Type III Installation introduced Section II; 13 & 15GHz ODU included. Section IV; Additional info on installation added. Section VII Chapter 5.2 Switch Criteria changed. Section IX: Additional info about connectors and interfaces in Appendix 1 Fast Ethernet introduced Section VII; New subchapter 5.1.5 Reconfiguring a 1+0 IDU for use in Hot StandBy Configuration 21x2Mbit/s (CityLink ADM) introduced. Section VIII: Updated bitmaps in Ch. 16.6 and 16.8. Frequency tuning of 13GHz Transceiver included (Section II Chapter 5.0). Not used Section V: New chapter 4.0 Installation of 21x2Mbit/s Tributary Unit Section II: Chapter 5.0; new frequency (Table II-5) Installation of ODU Type I on Type III suspension introduced Section IV: New subchapter: Mounting the transceiver (without antenna) to a column. Section VIII: Changed bitmaps in Ch. 16.1, 16.2, 16.6 and 16.8, Changes in Ch. 8.9.1 and 8.9.2. New commands included in Ch. 3.0 and 4.0. Section X: New alarms in Alarm list DMD IDU introduced. ADM STM-1 and DS3/E3 ext.boards introduced . New optical interfaces (2NYD5392A and 2NYD5368A) introduced.
M
04-10-26
New Version of NEW. (Section VII and VIII) Added info about System Configuration (Section I) Added info about IP Routing (Section VII) Section X: Improved description of Power Connector
B4008 Rev. M
CityLink
Table of Contents SECTION I Equipment Description .................. 21 1.0
Introduction ................................................................. 22
2.0
IDU ................................................................................ 2.1 IDU Description ................................................... 2.2 Hot Standby IDU Description............................... 2.3 Line Interface Boards .......................................... 2.4 Service Telephone .............................................. 2.5 21x2Mbit/s Extension Board (option) ................... 2.6 ADM STM-1 (X-Connect) Extension Board (option) 2.6 3xDS3/E3 and DS1 Extension Board (option) .... 2.6 Ethernet Extension Board (CityLink Fast Ethernet)
24 24 26 28 28 30 30 32 33
3.0
ODU .............................................................................. 3.1 ODU Type I Description ...................................... 3.2 ODU Type II Description ..................................... 3.3 ODU Type III Description .....................................
34 34 36 38
4.0
Management ................................................................ 40
5.0
System Configurations ............................................... 5.1 1+0Configuration ................................................. 5.2 Hot Standby Configuration .................................. 5.3 1+1 Frequency Diversity ..................................... 5.4 Hot Standby Configuration – Dual Antenna ......... 5.5 Hot Standby Configuration – Dual Baseband ...... 5.6 2+0 Configuration ................................................ 5.7 Space Diversity ................................................... 5.8 Hybrid Space Diversity ........................................ 5.9 Radio Terminal Configurations ............................ 5.10 Radio Repeater Configurations ........................... 5.11 Radio Channel Identification ................................
B4008 Rev. M
40 41 42 42 43 44 45 46 46 48 48 48
9
CityLink
SECTION II Installation of ODU Type I and Antenna ................. 49 1.0
General ........................................................................ 1.1 Packing ............................................................... 1.2 Marking ................................................................ 1.3 Transportation ..................................................... 1.4 Radio Equipment Inventory Check ...................... 1.5 Preparation for Installation ................................... 1.6 Handling & Storage .............................................
50 50 50 50 51 51 51
2.0
Installation Equipment required ................................ 2.1 Tools ................................................................... 2.1.1 Tools for Antenna Installation .............................. 2.1.2 Tools for IDU- ODU Cable /Connector Mounting. 2.2 Equipment external to the Radio Equipment .......
52 52 52 52 53
3.0
ODU / Antenna Installation, 1+0 Equipment ............. 3.1 Installation of 0.6m and 0.45m Antenna ............. 3.1.1 Preparing the Suspension for ODU Mounting ..... 3.1.2 Mounting the Antenna to the Suspension ............ 3.1.3 Mounting the Branching Support Bracket ............ 3.1.4 Mounting the Rear Travers .................................. 3.1.5 Mounting the Suspension Support Bracket ......... 3.1.6 Mounting the Bend on the Branching Unit ........... 3.1.7 Installation of the Branching Unit ........................ 3.1.8 Attachment of the Sunshield Support .................. 3.1.9 Installation of the Flexible Waveguide ................ 3.1.10 Installation of the Sunshield ................................ 3.1.11 Mounting the Suspension/Antenna to a Column or a Wall ............................................ 3.1.12 Mounting the ODU to the Antenna Assembly ..... 3.1.13 Pole Mount ......................................................... 3.2 Installation of 1.2m Antenna ............................... 3.2.1 Assembly of Branching Support Bracket ............ 3.2.3 Installation of Branching Unit, Sun-shield and Flexible Waveguide ....................
54 54 54 55 56 57 57 58 59 59 60 61
4.0 10
62 65 67 68 68 69
ODU / Antenna Installation, Hot Standby Equipment and 2+0 Equipment ........... 70 B4008 Rev. M
CityLink 4.1 4.1.1
0.45m and 0.6m Antenna ................................ Installation of Hot Standby (HSB) and 2+0 Dual Frequency Single Polarization Equipment . 4.1.1.1 Preparing the Suspension for ODU Mounting and Mounting the Antenna to the Suspension . 4.1.1.2 Mounting the Branching Support Bracket ........ 4.1.1.3 Mounting the Rear Travers, Mounting the Suspension Support Bracket and Mounting the Feed on the Branching Unit ....................... 4.1.1.4 Installation of the HSB Branching Unit ............. 4.1.1.5 Installation of the Flexible Waveguide ............. 4.1.1.6 Installation of the Sunshield Support Bracket .. 4.1.1.7 Installation of the Sunshield............................. 4.1.1.8 Mounting the Suspension/ODU to a Column or a Wall ............................................ 4.1.1.9 Mounting the ODU to the Antenna Assembly .. 4.1.1.10 Pole Mount ...................................................... 4.1.2 Installation of 2+0 Equipment (Single Frequency Dual polarity) ..................... 4.1.2.1 Preparing the Suspension for ODU Mounting and Mounting the Antenna to the Suspension . 4.1.2.2 Mounting the Branching Support Bracket, the Rear Travers, the Suspension Support Bracket and the Feed on the Branching Units ................ 4.1.2.3 Installation of the Branching Units ................... 4.1.2.4 Installation of the Flexible Waveguide ............. 4.1.2.5 Installation of the Sunshield............................. 4.1.2.6 Mounting the Suspension/ODU to a Column or a Wall ............................................ 4.1.2.7 Mounting the ODU to the Antenna Assembly .. 4.1.2.9 Pole Mount ...................................................... 4.2 1.2m Antenna .................................................. 4.2.1 Assembly of Branching Support Bracket ........ 4.2.2 Installation of Branching Unit, Sun-shield and Flexible Waveguide ......................................... 4.2.2.1 Hot Standby and 2+0 Dual Frequency Single Polarization ......... 4.2.2.2 2+0 Single Frequency Dual Polarization .........
B4008 Rev. M
70 70 70 70 71 71 72 73 73 74 74 75 76 76 76 76 77 78 79 79 80 81 81 82 82 83
11
CityLink 5.0
Frequency Tuning at 13GHz &15GHz Transceiver ... 84
6.0
Cable Connections ..................................................... 90
7.0
Antenna Alignment ...................................................... 90
SECTION III Installation of ODU Type II and Antenna .................. 91 1.0
General ........................................................................ 1.1 Packing ............................................................... 1.2 Marking ................................................................ 1.3 Transportation ..................................................... 1.4 Radio Equipment Inventory Check ...................... 1.5 Preparation for Installation ................................... 1.6 Handling & Storage .............................................
92 92 92 92 93 93 93
2.0
Installation Equipment required ................................ 2.1 Tools ................................................................... 2.1.1 Tools for Antenna Installation .............................. 2.1.2 Tools for IDU- ODU Cable /Connector Mounting. 2.2 Equipment external to the Radio Equipment .......
94 94 94 94 95
3.0
ODU Installation .......................................................... 96 3.1 Mounting the ODU to the Pole ............................. 96 3.2 Cable Connections.............................................. 97
4.0
Antenna and Waveguide Installation ........................ 4.1 0.6m Antenna ...................................................... 4.2 1.2m Antenna ...................................................... 4.3 2m Antenna ......................................................... 4.4 2.4m .................................................................... 4.5 3m .......................................................................
12
98 98 99 100 101 102
B4008 Rev. M
CityLink
SECTION IV Installation of ODU Type III and Antenna ............ 103 1.0
General ........................................................................ 1.1 Packing ............................................................... 1.2 Marking ................................................................ 1.3 Transportation ..................................................... 1.4 Radio Equipment Inventory Check ...................... 1.5 Preparation for Installation ................................... 1.6 Handling & Storage .............................................
104 104 104 104 105 105 105
2.0
Installation Equipment required ................................ 2.1 Tools ................................................................... 2.1.1 Tools for Antenna Installation and Adjustment .... 2.1.2 Tools for IDU- ODU Cable /Connector Mounting. 2.2 Equipment external to the Radio Equipment .......
106 106 106 106 107
3.0
ODU / Antenna Installation, 1+0 Equipment ............. 3.1 Mounting the Antenna to the Suspension ............ 3.2 Mounting the Sunshield ....................................... 3.3 Mounting the Suspension/Antenna to a Column by using the U-bolts ............................ 3.4 Mounting the Suspension/Antenna to a Column by using the Clamps ........................... 3.5 Mounting the Transceiver (without Antenna) to a Column ............................ 3.6 Mounting the Suspension/Antenna to a Wall ....... 3.7 Mounting the ODU to the Antenna Assembly ......
108 108 109
ODU / Antenna Installation, HSB and 2+0 Equipment 4.1 Preparing the Suspension ................................... 4.2 Mounting the Antenna to the Supension .............. 4.3 Mounting the Hybrid Frame to the Antenna ......... 4.3 Mounting the CityLink III ODUs to the Antenna Assembly ........................................ 4.4 Mounting the Transceiver (without Antenna) to the Column ......................... 4.5 Mounting the Suspension/Antenna to a Wall .......
121 121 122 123
4.0
B4008 Rev. M
110 111 112 117 118
125 126 126 13
CityLink 5.0
Cable Connections ..................................................... 127
6.0
Antenna Alignment ...................................................... 6.1 Azimuth and Elevation Adjustment ...................... 6.2 Coarse adjustment.............................................. 6.3 Fine adjustment .................................................. 6.4 Final Control ........................................................ 6.5 Polarisation alignment .........................................
128 128 128 128 129 129
SECTION V IDU Installation............................... 131 1.0
General ........................................................................ 1.1 Packing ............................................................... 1.2 Marking ................................................................ 1.3 Transportation ..................................................... 1.4 Radio Equipment Inventory Check ...................... 1.5 Preparation for Installation ................................... 1.6 Handling & Storage .............................................
132 132 132 132 133 133 133
2.0
IDU Installation ............................................................ 134 2.1. Mounting the IDU in an ANSI (19") or an ETSI Rack ... 134 2.2 Cable Installation ................................................. 135
3.0
Hot Standby IDU Installation ...................................... 136 3.1 Mounting the Hot Standby IDUs in a Rack ........... 136 3.2 Interconnections in a Hot Standby System ......... 137
4.0
Installation of Optional Extension Boards ............... 138
5.0
IDU/ODU Cable Installation........................................ 141
6.0
Change of Fan-Cassette ............................................ 146
SECTION VI Preparations for Operation ........ 147 1.0 14
General ........................................................................ 148 B4008 Rev. M
CityLink 1.1 1.2 2.0
Equipment required ............................................. 148 Connections ........................................................ 148
Power on ...................................................................... 2.1 NEW-NMS/NEW-Configurator Startup and connecting to Network Elements ........................ 2.1.1 Starting NEW-NMS/NEW-Configurator with Serial Connection (RS-232/ LCT). ...................... 2.1.2 Starting NEW-NMS/NEW-Configurator with TCP/IP Connection. ............................................ 2.2 Initial configuration ...............................................
148 149 149 150 150
SECTION VII Configuration by NEW Configurator 151 1.0
General ........................................................................ 152
2.0
Element Node .............................................................. 2.1 Element Id ........................................................... 2.2 Available Functions ............................................. 2.3 Notifications ......................................................... 2.4 NE Clock Page .................................................... 2.5 Software Download ............................................. 2.6 Software Versions ...............................................
154 154 156 157 159 160 161
3.0
Transmission Node ..................................................... 3.1 Section Termination ............................................ 3.1.1 Section Termination, SW-version < R2A00 ........ 3.1.2 Section Termination, SW-version ³ R2A00 ......... 3.1.3 SSM - Synchronization Status Message ............. 3.2 Alarm Indication Signal Insert .............................. 3.3 Path Trace ..........................................................
163 163 163 164 172 173 176
4.0
Equipment Node ......................................................... 4.1 Network Routing .................................................. 4.2 IP Routing............................................................ 4.2.1 General Settings ................................................. 4.2.2 Active Routes ......................................................
178 178 181 182 184
B4008 Rev. M
15
CityLink 4.2.3 Static Routes ...................................................... 4.2.4 RIP Interfaces ..................................................... 4.2.5 OSPF Interfaces ................................................. 4.2.6 OSPF Areas ........................................................ 4.3 Communication Ports ......................................... 4.3.1 DCC (Data Communication Channel) ................ 4.3.2 NI (Network Interface) .......................................... 4.3.3 LCT ..................................................................... 4.3.4 Ethernet .............................................................. 4.3.5 IP Settings ........................................................... 4.3.6 IP Tunneling ........................................................ 4.3.7 OSI TP4 Tunneling .............................................. 4.4 Looping ............................................................... 4.4.1 Main Looping ....................................................... 4.4.2 64 Kbit/s Looping ................................................ 4.4.3 2 Mbit/s Wayside Looping ................................... 4.4.4 21x2Mbit/s Looping.............................................. 4.4.5 DS3/E3 Looping .................................................. 4.5 In Door Unit (IDU) ................................................ 4.5.1 IDU Production Data ........................................... 4.5.2 64 kbit/s Channels .............................................. 4.5.3 2 Mbit/s Wayside Channel .................................. 4.5.4 SOH X-Connect .................................................. 4.5.5 Error Pulse Output .............................................. 4.5.6 Auxiliary Output Configuration ............................. 4.5.7 Diagnose ............................................................. 4.5.8 Self Test .............................................................. 4.5.9 BER Thresholds ................................................. 4.5.10 OSI Configuration ................................................ 4.5.11 Laser Control ...................................................... 4.5.12 IDU Replace Unit Wizard .................................... 4.6 Out Door Unit (ODU) ........................................... 4.6.1 Type I ODU ......................................................... 4.6.2 Type II ODU ......................................................... 4.6.3 Type III ODU ........................................................ 4.6.4 Antenna Data ...................................................... 4.6.5 ODU Replace Unit Wizard .................................. 5.0 16
185 186 187 188 189 189 191 193 194 195 196 197 198 198 200 202 205 207 210 210 211 213 215 216 217 219 220 220 222 227 229 230 230 235 247 252 253
CityLink ADM ............................................................... 254 B4008 Rev. M
CityLink 5.1 5.1.1 5.1.2 5.1.3 5.1.4 5.2 5.2.1 5.2.2 5.3 5.3.1 5.3.2 6.0
21x2 Mbit/s Extension Board ............................... Drop or Continue ................................................. PRBS Test - Check ............................................ PRBS Test - Generators ..................................... Production Data - 21x2Mbit/s Extension board ... DS3/E3 Extension Board .................................... DS3/E3 Configuration ......................................... DS3/E3 Frame Structure Configuration .............. ADM STM-1 Extension Board (X-Connect) ......... X-Connect Frame Structure Configuration .......... X-Connect Configuration .....................................
254 254 258 260 262 263 263 265 267 267 268
Hot Standby ................................................................. 6.1 General ............................................................... 6.1.1 Functionality ........................................................ 6.1.2 Element ID .......................................................... 6.1.2 Looping Configuration ......................................... 6.1.3 Hot Standby Configuration .................................. 6.1.4 Hot Standby Switching Criteria ............................ 6.1.4 Reconfiguring a Hot Standby IDU for use in 1+0 Configuration ..................................... 6.1.5 Reconfiguring a 1+0 IDU for use in Hot StandBy Configuration ......................
270 270 270 271 273 275 276 278 278
SECTION VIII CityLink Fast Ethernet Configuration 279 Hyperterminal & Telnet .................................................... 280 1.0
Hyperterminal & Telnet Commands .......................... 280
2.0
How to get this link alive ............................................ 281 2.1 How to get this link alive, parameters .................. 281 2.2 Testing ................................................................ 281
3.0
Top Level Commands ................................................ 282 3.1 Top Level Commands, Example ......................... 283
B4008 Rev. M
17
CityLink 4.0
Submenu Commands .................................................. 4.1 EEB Submenu .................................................... 4.2 Baseband Submenu ........................................... 4.3 Modem Submenu (part of IDU) ........................... 4.4 Radio Submenu (part of ODU) ............................ 4.4.1 Radio Status, Example ....................................... 4.4.2 Radio Commands, Example of Error Message .. 4.5 SU Submenu (part of IDU) .................................. 4.6 Security Submenu .............................................. 4.7 Performance Submenu ....................................... 4.8 Configuration Submenu ...................................... 4.8.1 Management Settings ......................................... 4.9 Test & Fault Submenu ........................................ 4.10 Q1module Submenu ...........................................
284 284 285 286 287 288 288 289 289 290 290 291 291 292
5.0
Software Upgrade Procedure for the CityLink Fast Ethernet Device ............................ 5.1 How to download a file to the IDU: ....................... 5.1.1 Using the Console FTP Client ............................. 5.1.2 Using the Internet Explorer .................................. 5.2 How to download a file to the ODU .....................
293 294 294 295 296
NEW Network Management System ............................... 297 6.0
Start NEW-NMS & Connect........................................ 297
7.0
Network Element Configuration ................................ 300
8.0
Element Node .............................................................. 8.1 Element Id ........................................................... 8.2 NE Clock ............................................................. 8.3 Software Versions ............................................... 8.4 Production Data .................................................. 8.5 SNMP Agent(s) Settings ..................................... 8.6 Trap Table ........................................................... 8.7 MIB II - System Group ......................................... 8.8 MIB-II SNMP Group.............................................. 8.9 Looping ............................................................... 8.9.1 Main Traffic Loops ...............................................
18
302 302 303 304 305 306 308 309 311 312 313 B4008 Rev. M
CityLink 8.9.2 Wayside Loops ................................................... 315 8.9.3 64 kbit/s Loops .................................................... 316 9.0
In Door Unit (IDU) ....................................................... 9.1 64 kbit/s Channels .............................................. 9.2 Ethernet Extension Board ................................... 9.2.1 Ethernet Ports ..................................................... 9.2.2 2 Mbit/s Ports ...................................................... 9.3 Wayside Channel ................................................ 9.4 Auxiliary Output ................................................... 9.5 BER Thresholds ................................................. 9.6 Laser Control ......................................................
317 317 317 318 319 320 321 323 325
10.0
Out Door Unit (ODU) .................................................. 10.1 Antenna Data ...................................................... 10.2 Power Settings .................................................... 10.3 Frequency Settings .............................................
327 327 328 330
11.0
Performance ................................................................ 11.1 G826 Performance.............................................. 11.2 Port Performance ............................................... 11.3 Repeater Performance .......................................
332 332 334 335
12.0
Fault .............................................................................. 336 12.1 NE Alarm Log ...................................................... 336
13.0
Security ........................................................................ 337 13.1 Security Log ........................................................ 337
SNMP & MIB Description ................................................. 338 14.0
General ........................................................................ 338
15.0
Supported MIB’s ......................................................... 338
16.0
MIB Overview ............................................................. 339 16.1 Unit ...................................................................... 340 16.2 IDU ...................................................................... 341
B4008 Rev. M
19
CityLink 16.3 16.4 16.5 16.6 16.7 16.8
ODU .................................................................... Test Manager ...................................................... Performance Manager ........................................ Fault Manager ..................................................... Analogue Value ................................................... Security Manager ................................................
SECTION IX
342 343 344 345 346 346
Troubleshooting ......................... 347
1.0
General ........................................................................ 348
2.0
Description of Alarm LEDs ......................................... 2.1 IDU Alarm LEDs .................................................. 2.2 HSB-IDU Alarm LEDs and Switch Indicators ..... 2.3 LEDs on Line Interface Plug-in Boards ...............
348 348 348 349
3.0
Troubleshooting by NEW-NMS Configurator .......... 3.1 Introduction .......................................................... 3.2 Information Acquisition ........................................ 3.2.1 Polling ................................................................. 3.2.2 Event Notification ................................................ 3.3 Alarm Presentation.............................................. 3.4 Visual Alarm Notification ...................................... 3.4.1 Alarms on a Tree node/leaf in the Explorer view . 3.4.2 Alarms on a Node symbol in the Map view .......... 3.4.3 Viewing Alarms in the Current Alarms View ........
349 349 349 349 350 350 351 351 352 353
SECTION X Appendices................................... 355 Appendix I: IDU / HSB-IDU Interface Description .................. 356 Appendix II: ODU Interface Description ................................. 370 Appendix III: Alarm List & Alarm Description .......................... 371
20
B4008 Rev. M
Equipment Description
SECTION I Equipment Description
B4008 Rev. M
21
CityLink
1.0
Introduction CityLink is a super compact SDH radio-relay transmission system with STM1 capacity. The equipment is split mounted with one single coaxial cable between the InDoor Unit (IDU) and the OutDoor Unit (ODU). The ODU and antenna can be located up to 300 meter apart from the IDU. The equipment is available in 1+0 (single), 2+0 or 1+1 hot standby configurations. Various line and tributary interface options are available as plug-in modules. The equipment is also prepared for 21x2Mbit/s terminal multiplexer functionality. The network applications foreseen for this equipment are mainly for increased connectivity in urban area as well as closure of fiber optic rings. Additionally, in the fixed part of mobile networks, this equipment is suitable. Built-in supervision enables easy installation and configuration, and system status and availability data may be recorded. Advanced management with standardized use of the Embedded Control Channel (ECC) allows for easy access to this equipment. Broadband RF design enables easy channel selection.
22
B4008 Rev. M
Equipment Description Key features • Easy installation • Frequency agility • 155 Mb/s Line interface plug-ins available: Unbalanced 75Ω coaxial Balanced, Category 5 UTP, 100 Ω Single Mode fiber optic Multi Mode fiber optic • SW managed configuration of 32, 64 and 128 TCM modulation • SW managed configuration of STM-0 or STM-1 capacity • 21x2Mbits/s terminal multiplexer option • 3xDS3/E3 and DS1 option • ADM STM-1 option (STM-1 cross-connect) • Fast ethernet radio option • 64kbit/s and 2Mbit/s insert channels • Service Channel / Engineering Orderwire • Line extensions (2) for Service Channel • Built-in diagnostics with local and remote loopback • Available Configurations: 1+0 (Unprotected) (STM-1 & STM-0) 1+1 (Hot Standby) (STM-1 & STM-0) 2+0 Dual frequency, Single Polarisation (DF-SP) (2xSTM-1&STM-0) 2+0 Single frequency, Dual Polarisation (SF-DP) (2xSTM-1&STM-0) • High system gain • Automatic/Manual Transmitter Power Control (ATPC/MTPC) • Standardized use of the ECC • Embedded SNMP (Option) • 14, 28, 50 & 55 (56) MHz channel arrangements • 2MHz synchronization interfaces (SETS) • Interface for local and subnetwork management (LAN or RS-232)
B4008 Rev. M
23
CityLink
2.0 2.1
IDU IDU Description Figures X-1 shows the IDU front layout. All the connectors are located on the front for easy operation. In addition to the line interface, 2Mbit/s wayside and 64kbit/s data channels are available. As options, a 21x2 Mbit/ s terminal multiplexer, ADM STM-1 (X-Connect) or DS3/E3 can be configured by adding a second circuit board. The IDU is equipped with an integrated supervisory system for local and remote configuration and control. The supervisory system communicates with the ODU by use of an FSK modulated channel on the coaxial cable. The same coaxial cable also carries power to the ODU. For configuration and management purposes the IDU is equipped with two LCT interfaces for connection to the PC, one with RS-232 interface and one LAN TP interface. In addition NI interfaces for connection to other IDUs or other Nera equipment are provided. A SETS function is incorporated into the unit, conforming to ITU-T rec. G.823 with balanced 120Ω interface. The IDU has a connector for alarm input/output functionality (ALM/AUX). Alarm and warning LEDs are located on right hand side of front. Located close to the power connector is a power indicating LED. Figure I-1 shows a block schematic view of the IDU with various optional line interface plug-in boards and also a 21x2 Mbit/s Extension Board. In radio transmit direction, the 155 Mb/s input signal from the line interface board is fed to the “SORP” ASIC. It performs all the SOH processing and radio scrambling. Then, the TX FPGA encodes the signal by use of a convolution code and an optional Reed Solomom code. The signal is then mapped into a “32TCM”, “64TCM” or “128TCM” constellation, as required. It also performs the necessary pulse shaping by use of a digital FIR-filter. The signal is then digitally I-Q modulated, and the 350MHz IF signal is fed to the ODU interface and applied to the IF coaxial connector. In receive direction the 140MHz IF from the ODU will interface the IDU on the same connector. The necessary cable equalizing functions are provided in the ODU interface and the equalized IF is presented to the coherent demodulator. From the demodulator the signal is fed to the RX FPGA, which perform slope equalization and receive filtering. Then the “ATDEC” ASIC, performs Trellis decoding, by use of soft decision and the “Viterbi” algorithm for error correction. The optional Reed Solomon decoding is performed in the RX FPGA. The decoded signal is then fed to the SORP ASIC for radio descrambling and SOH processing, and is finally fed to the line interface board.
24
B4008 Rev. M
Figure I-1
B4008 Rev. M
File: IDU-HRQI.DSF
48V DC
2 x NI
FIFO BUS
LCT LAN (10BASE-T)
ALARMS
2 x PHONE EXT.
PHONE
2 x 64 Kb/s
2Mb/s WAYSIDE
HSB IDU INTFC.
Optical MMF ~2Km or Optical SMF ~15Km or Optical SMF ~40Km or Optical SMF ~80Km or Electr. CAT5 UTP or Electr. G.703
G.703
2MHz SYNC
21x2 Mb/s G.703
21
1
FPGA
155 Mb/s LINE INTERFACE
"E1"
TRIBUTARY INTERFACE BLOCK NO. 2
"H2"
MAIN BD.
ALM/AUX INTFC.
INTERFACE
V11/G.703
DCC
SUPERVISORY SYSTEM
SVCE PHONE INTERFACE
"SORP" STM-1 OVERHEAD AND RADIO PROCESSOR
ASIC
SYNC. INTERFACE
TRIBUTARY DATA MAPPER NO. 1
TRIBUTARY DATA MAPPER NO. 1
ASIC's
21x2 Mb/s LINE INTFC./ADD-DROP EXTENSION BD.
TRELLIS DECODER
"ATDEC"
ASIC
DC / DC
CARRIER REC. CLOCK REC. DEMAPPER DECODER
FPGA RX:
ENCODER MAPPER FILTER
FPGA TX:
INTERFACE
REGULATED OUTPUTS
ODU
87.5 MHz OSC. SOURCE
MODEM TRANSCEIVER COMMUNICATION
93.3 MHz OSC. SOURCE
2x
DOWNCONVERSION A/D CONVERSION
INTERPOLATION MODULATION D/A CONVERSION UPCONVERSION
4x 3x
ODU
Equipment Description
Block schematic view of the IDU
25
CityLink 2.2
Hot Standby IDU Description Figure X-2 shows the HSB IDU front layout. The connectors on the front are identical to the ones used on the IDU and is therefore not further described here. Additionally, a second power connector is added for power redundancy enabling separate battery courses. Figure I-2 shows a block schematic view of the IDU with various optional line interface plugin boards. Interconnection of data and control signals between IDUs (A and B) and HSB IDU is by means of a connector and special split cable. This cable is part of the HSB cable kit. In a 1+1 HSB system, all the customer interfaces are towards the HSB IDU. These signals are disabled on the IDU in such a configuration. The same alarm and warning LEDs used on IDU is also used here. Additionally, a second power indicating LED is located close to the redundant power connector. Also, an array of four LEDs, located on the right hand side in close proximity to the alarm/warning LEDs, indicates switching status in transmit and receive direction.
26
B4008 Rev. M
Equipment Description 3xE3/DS3 EXTENSION BD. ASIC's
TRIBUTARY DATA MAPPER NO. 1
FPGA
TRIBUTARY INTERFACE BLOCK
3x34/45 Mb/s G.703
TRIBUTARY DATA MAPPER NO. 1
PHY
1.5 Mb/s WAYSIDE
"E1"
SYNC.
2MHz SYNC
INTERFACE
G.703 Optical MMF ~2Km or Optical SMF ~15Km or Optical SMF ~40Km or Optical SMF ~80Km or Electr. CAT5 UTP or Electr. G.703
ASIC
155 Mb/s LINE INTERFACE
"H1"
"SORP" SDH OVERHEAD AND RADIO PROCESSOR
IDU A INTFC. (R) IDU B INTFC. (P)
DCC
2Mb/s WAYSIDE
V11/G.703
2 x 64 Kb/s
INTERFACE
SVCE PHONE INTERFACE
PHONE 2 x PHONE EXT.
ALM/AUX INTFC.
ALARMS LCT LAN (10BASE-T)
SUPERVISORY SYSTEM
FIFO BUS 2 x NI 48V DC
DC / DC
REGULATED OUTPUTS
MAIN BD HSB IDU. File: HSBIDU-HRQE.DRW
Figure I-2
B4008 Rev. M
Block schematic view of the HSB IDU (shown here with DS3/E3 Extension Board)
27
CityLink 2.3
Line Interface Boards Six different versions of 155 Mb/s line interface boards are presently available as plug-in modules. These are: • Electrical, 75Ω unbalanced interface bd. according to ITU-T rec. G.703. • CAT-5 UTP electrical interface bd. according to ATM Forum rec. af-phy-0015.000. • Multimode Fiber optical interface bd. according to ANSI rec. T1.646 and T1.105.06 type “SR-0”. • Singelmode Fiber optical interface bd. according to ITU-T rec. G.957, type “S-1.1”. • Singelmode Fiber optical interface bd. according to ITU-T rec. G.957, type “L-1.1”. • Singelmode Fiber optical interface bd. according to ITU-T rec. G.957, type “L-1.2”. In a 1+1 HSB system, the line interface board will only be used on the HSB IDU. All the interface boards have an input signal indicating LED.
2.4
Service Telephone A service telephone with collective call is provided in both the IDU and HSB IDU. In a 1+1 HSB system, the customer interface connection must be towards the HSB IDU. External connection to two other similar equipment can take place via two RJ-45 ports on the front. Refer to Appendix I for connector pin-out and description and Figure I-3 for circuit diagram of the service channel interface. The balanced interfaces have a nominal level of -6dBm and 600Ω impedance. Connect OUT to INP and vice versa. Service channel signalling is based on collective call. The DTMF-star sequence is used as collective call to interface with other Nera equipment. If other equipment connected have a different calling system than DTMFstar, they may use CALL INP/CALL OUT. Station ground connected to CALL INP will start transmission of DTMF-star as well as activating a buzzer. A detected DTMF-star will activate the CALL OUT by opening an optocoupler to station ground. For Nera PDH-radio equipped with Service Board 2NF467A, CALL INP has to be connected to CALL OUT and vice versa.
28
B4008 Rev. M
Equipment Description A control signal can be transferred over the radio hop. Station ground connected to CTRL INP will set a signalling bit which is detected on the other side and activates CTRL OUT by opening an optocoupler to station ground. See Figure I-3. The control signal is used to control PABXadapters and to switch off loudspeakers on Nera service boards with selective call (e.g. 2NF4688, 2NF533B and 2KNF232A). The control signal is transferred only if SOH-byte “E1”, “E2” or “F1” is used for transmission of service channel. For setup by NEW, refer to Section VII.
1k
2
2
3
BYM122
15
2
BSR19A
2 1
1
10k
2
CALLOUT/ CTRLOUT
BSR19A CALLINP/ CTRLINP
2
BAS16
1
3
1
10k
+5V
1
3 PC3Q66Q
1
1
CALL_INP/ CTRL_INP
1
2 1
3
14
1k
1
10k
2
+3.3V
PC3Q66Q 2 2
CALL_OUT/ CTRL_OUT
16
4
13
-48V
Figure I-3 “Service Channel CALL" Circuit Diagram
B4008 Rev. M
29
CityLink 2.5
21x2Mbit/s Extension Board (option) In Figure I-4, a block schematic depiction of a 21x2Mbit/s Extension Board function are given. This function enables twenty-one 2Mbit/s channels to be multiplexed/demultiplexed, enabling a terminal multiplex function. It is possible to configure the unit to drop a certain number of 2Mbit/s channels while delivering the rest as a part of the STM-1 payload in a “drop-andcontinue” configuration. In a standard terminal multiplexer configuration, the plug-in line interface board is omitted. The 2Mbit/s channels conform to ITU-T rec. G.703, balanced 120Ω. Also provided on the same circuit board is the option of using one of the 2Mbit/s channels as SETS reference clock input/output, according to ITU-T rec. G.823. In a 1+1 HSB system, this interface board will be mounted in the HSB IDU. In a 1+0 system it will be included in the IDU. 21x2 Mb/s LINE INTFC./ADD-DROP EXTENSION BD. ASIC's
ASIC
1 21x2 Mb/s G.703
21
TRIBUTARY INTERFACE BLOCK NO. 1
TRIBUTARY DATA MAPPER NO. 1
TRIBUTARY DATA MAPPER NO. 1
To/from the IDU's SDH Overhead and Radio Processor (SORP)
Figure I-4 Block schematic view of the 21x2Mbit/s Extension Board
2.6
ADM STM-1 (X-Connect) Extension Board (option) The Extension Bd. ADM STM-1, which is a part of the Indoor unit in the NERA CityLink, is an optional ITU-T standard STM-1 interface implemented for 155 Mbit/s signal entry and exit in a ring topology. The STM-1 entry signal into the ring is split and transmitted to line and radio side in parallel. Signals exiting the ring are received from line and radio side. These are up to 63xVC12s from either side and they are protected, i.e. they shall be switched individually if a break somewhere in the ring occurs. Also, the system will handle any allowed combination of VC-3s and VC-12s. In Figure I-5, a block schematic of the STM-1 Extension Board functions is shown. The STM-1Extension Board will interface one STM-1 line signal in Tx- and Rx-direction. The STM-1 interface is interchangeable in the following
30
B4008 Rev. M
Equipment Description way: In a slot in the STM-1Extension Board, a line interface board is inserted. Presently one type of board is implemented: The plug-in board compliant with ITU-T G.703 CMI encoded 155 Mbit/s customer interface; 2LN24C. A green LED, located on the front of the board indicates presence of an input signal. The line interface board is mounted on the extension board prior to this being mounted within the IDU cabinet. This means that the line interface board will not be used as a plug-in type board in this application. SOH processing and line scrambling /descrambling on the STM-1 interface are performed by the SORP ASIC. The TDM1 ASICs perform insertion, extraction, signal processing and cross-connection of data in the payload of the STM-1 frame and also make error and performance measurements on VC-3 and error measurements on VC-12. The PLD14 FPGA makes performance measurements on VC-12s embedded in the STM-1 datastreams from two TDM1 ASICs. The measurement results are used to choose individual VC-12s from the two datastreams in TDM1 ASIC no.1 and TDM1 ASIC no.2. The selection is done by the SU in TDM1 ASIC no. 3. See Figure I-5.
IDU CONN
TDM1 ASIC no 1——→ PLD14 FPGA———————→ TDM1 ASIC no 3 ————————→
TDM1 RADIO
PLD14 FPGA
TDM1 LINE
TDM1 ASIC no 2 ————————-→
TDM1 LINE EXTENSION BOARD
SORP ASIC no 2 —————————→
SORP EXT BOARD
Line Interface Board ———————-→
LINE INTERFACE CARD
Figure I-5 Block schematic view of the ADM STM-1 Extension Board B4008 Rev. M
31
CityLink 2.6
3xDS3/E3 and DS1 Extension Board (option) DS3 is a 45Mbit/s PDH standard used for the North American marked, E3 is 34Mb/s PDH standard used for the European marked and the DS1 is a 1.5Mbit/s PDH standard used for the North American marked. The 3xDS3/ E3 and DS1 Ext. Bd., which is a part of the Indoor unit in the NERA CityLink, will perform add-drop of 3xDS3/E3 PDH channels to-from a STM-1 frame. In additional it will perform insertion and extraction of 1.5 Mbit/s wayside (DS1/ T1). In Figure I-6, a block schematic of the 3xDS3/E3 and DS1 Ext. Bd. functions are shown. The 3xDS3/E3 and DS1 Ext. Bd. will interface three DS3/E3 and one DS1 line signal in Tx- and Rx-direction. The line interface circuit includes; cable equalizer, line coding and pulse shaping functions. This is performed by two Line Interface Unites (LIU), one for DS3/E3 an one for DS1. SOH overhead and radio processor is located oh the motherboard in the IDU. The PLD15 FPGA maps the 3xDS3/E3 into three VC3s, then into a VC4 and then into a STM-1 signal and de-maps in the opposite direction. The STM1 signal is locked to a 2.048 MHz input (SETS) coming from the motherboard. The TDM1 ASIC performs insertion, extraction and cross-connection of data in the payload of the STM-1 frame. Together, the two TDM1s and PLD15 implement the core of a DS3/E3 add-drop multiplexer. The 1.5 Mbit/s Wayside (DS1/T1) function is implemented in PLD15 and is independent of the TDM1 ASICs. 3xDS3/E3 and T1 EXT. BOARD IDU CONNECTOR
TDM1 No. 1 LINE
48 V DC/DC PLD15
TDM1 No. 2 RADIO
+3.3 V +1.5 V T1 LIU
3xDS3/E3
Figure I-6 Block schematic view of the 3xDS3/E3 Extension Board 32
B4008 Rev. M
Equipment Description 2.6
Ethernet Extension Board (CityLink Fast Ethernet) In Figure I-7, a block schematic description of an Ethernet Extension Board (EEB) is given. This function enables 4 separate Ethernet channels 10BASET/100BASE-TX and 4 separate 2Mbit channels conforming to ITU-T rec. G.703. The EEB will treat all 8 channels separately, meaning that all data entering on one channel will leave on the same channel on the other side of the radio hop. All channels are full duplex. The four Ethernet and four 2Mbit/ s channels shares the STM-1 data capacity. The 2Mbit channels, if enabled, will always be guaranteed full bandwidth. The 4 Ethernet channels can be configured to either equally share the STM-1 data frame, or one channel can be given priority. The EEB has a limited on board Ethernet package buffer capacity. This gives the ability to handle short time 100Mbit/s bursts on all four channels without package loss. Also the EEB supports flow control, making it possible to configure a 400Mbit full duplex network without package loss, even though the radio hop is limited to STM-1 data rate.
4x RJ45 Ethernet
Ethernet Interface
Ethernet to/from STM1 and 2Mbit/s mapper/demapper Ethernet to/from STM1 and 2Mbit mapper/demapper
4x RJ45 2Mbit
To from IDU main board
22/1.5Mbit Mbit/s Interface Interface
Figure I-7 Block schematic view of the Ethernet Extension Board
B4008 Rev. M
33
CityLink
3.0 3.1
ODU ODU Type I Description The ODU Type I is an assembly of branching unit and transceiver unit mounted behind the antenna or on a mounting frame on a pole/column. The ODU is connected to the IDU with a single coaxial cable. The coaxial cable provides Tx-IF, Rx-IF, signalling and power supply. For flexibility and easy installation, the coaxial cable is connected to the transceiver through the branching unit. The transceiver is attached to the branching with a snap on system. With this solution, the coaxial cable may remain connected during transceiver replacement. In 1+0 configuration the branching unit is for a single transceiver and in Hot Standby configurations the branching is for dual transceivers. The ODU and the antenna are assembled very closely together making it very compact. Nevertheless the antenna can be separated from the ODU by use of a flexible waveguide. The branching unit contains RF channel filters, circulators and overvoltage protection. The Hot Standby branching contains in addition a RF switch for transmit direction and a RF power splitter for the receive direction. The transceiver unit contains a microwave Tx/Rx module, a synthesised local oscillator and a transceiver main board, all in a waterproof housing. The transceiver is based on dual frequency conversion in the transmitter and triple conversion in the receiver. This radio architecture with high IF frequencies allows for use of wide band branching filters while still maintaining excellent spectrum purity in transmitter and high selectivity in receiver. The use of wide band branching filters allows for a wide choice of remote channel frequency selection without changing hardware. The microwave module is an integrated multi-chip module with GaAs HEMT MMICs for Power Amplifier and Low Noise Amplifier. The necessary LO frequencies for the frequency converters are generated in a low phase noise synthesiser unit. The channel frequency is remotely programmed from the indoor unit. Transmit/receive IF-chain, controlcircuits, signalling and power supply are integrated on the transceiver main board.
34
B4008 Rev. M
Figure I-8
B4008 Rev. M
IF IN / OUT
140 MHz
350 MHz
IF LOOP
350 MHz
UHF LO
UHF LO
210 MHz
PREDIST
CTRL / M/T COM / POWER
350 MHz
CAB. EQ.
SYNTHESIZER
UHF IF
7 GHz FIXED
2 GHz SYNTH
DUPLEX FREQ
TRANSCEIVER UNIT
TRANSCEIVER MAIN BOARD
XN
MICROWAVE MODULE
PWR
BRANCHING UNIT
IF IN / OUT M / T COM DC PWR
ANTENNA UNIT
Equipment Description
Block schematic view of the ODU Type I, 18GHz, in 1+0 configuration
35
CityLink 3.2
ODU Type II Description The Type II of the ODU consists of a weatherproof box containing the branching system. The ODU box is mounted on a pole/column behind the antenna. The Transceiver unit is a plug-in unit mounted in the box. In 1+0 configuration the ODU box contains a 1+0 branching unit for a single transceiver and in Hot Standby configurations the ODU box contains a Hot Standby branching unit and dual transceivers. The branching unit contains RF channel filters and the diplexer. The Hot Standby branching contains in addition an RF switch for transmit direction and an RF power splitter for the receive direction. The transceiver unit contains 7 modules/sub-units; a microwave transmitter module, a receiver module, 3 local oscillators, an IF &controller board and a detector board. The transceiver is connected to the modem/IDU with a single coaxial cable that carries Tx-IF, Rx-IF and signalling (MTcom). Power is supplied through a separate connector (D-sub), and for the split mount case this power is separated from the coaxial cable in the ODU container (box). The transceiver utilises a single conversion scheme in the transmitter and a dual conversion in the receiver. In order to obtain an optimum spectrum mask, the transmitter chain contains predistortion circuitry at IF before the microwave upconverter and power amplifier. Narrow channel filters in the branching unit further reduces the spectrum mask. The second converter in the receive chain allows for an IF loop-back facility for diagnostics purposes. LO frequencies for the microwave frequency converters are generated in synthesised DROs. The oscillators are by nature fixed in frequency, i.e. they can only be remotely programmed within a narrow range. When necessary, the oscillators can be adjusted within a range of approx. 200 MHz with a mechanical screw (see Section VII Chapter 4.5.2.3 for guidance). Power supply, transmit/receive IF-chain, signalling and controller (DSP) for the transceiver are integrated on the IF &controller board. The branching unit contains narrow RF channel filters and circulators.
36
B4008 Rev. M
Figure I-9
B4008 Rev. M
48V
MTcom
Rx IF 140 MHz
Tx IF 350 MHz
CTRL
140 MHz
IF&CTRL Bd.
DC/DC
MTCom.
Multiplexer
350 MHz
Predistortion & AGC
140 MHz
DSB Mixer
210 MHz
IFSynt.
Synthesizer Unit
FLTR & AGC
IF loop
AGC & Cable equalizer
FLTR & AGC
RxSynt.
TxSynt.
350 MHz
Rx LO
Tx LO
RCVR Module
IMR Mixer
SSB Upconverter
XMTR Module
IMD Det.
LO Det.
Low Noise Amplifier
350 MHz
LO, IMD mxr
Power Amplifier
RF in
RF out
Equipment Description
Block schematic view of the ODU Type II, 7GHz, in 1+0 configuration
37
CityLink 3.3
ODU Type III Description Type III of the ODU consists of a single ODU (in 1+0 configuration) mounted behind the antenna and attached to the antenna by means of four snap-on clamps. The ODU is connected to the IDU via a single coaxial cable which carries transmitter IF, receive IF and control and monitoring signals, as well as DC power. In 2+0 and 1+1 hot standby configurations both ODUs are attached by the same snap-on clamps to a branching hybrid. This hybrid can either be bolted directly to the antenna or via a short length of flexible waveguide. The branching hybrid contains an RF splitter and combiner. The ODU consists of a weatherproof housing containing a microwave transmit/receive module, a synthesised local oscillator module and an IF and control transceiver main board. The transceiver is based on a dual upconversion and triple down-conversion scheme, which allows the use of wide-band duplex filters and therefore a wide choice of remote channel frequency selection. To optimise the transmitter spectrum the transmitter employs pre-distortion at IF as well as cable equalisation to correct for variable loss and slope in the cable. The microwave transmit/receive module consists of a multi-chip module using a set of GaAs HEMT MMICs, both for the transmitter power amplifier and the low-noise receiver. The required local oscillator signals are fed from the synthesised local oscillator module and up-converted using a diode multiplier. The channel frequency is remotely selected via the IDU. Transmit/receive IF multiplexing, control and monitoring and power supply functions are all integrated on the transceiver main board.
38
B4008 Rev. M
Figure I-10
B4008 Rev. M
DIPLEXER
EQUALISER
SLOPE
MAIN BOARD
PREDIST
210MHz
DUPLEX FREQ.
TRANSCEIVER
SYNTHEZISER 7-9 GHz
MICROWAVE CONVERTER
UHF LO2 (LO1)
UHF LO1 (LO2)
DIPLEXER
ANTENNA
Equipment Description
Block schematic view of the ODU Type III
39
CityLink
4.0
Management An integrated supervision system makes the CityLink capable of functioning as a Network Element (NE) in a managed SDH transmission network. Management and supervision of the CityLink can be performed in various ways from very simple alarm monitoring to standardised management through optional built-in NE agents. Standardised use of QECC, according to ITU-T Rec. G.784, is provided. As an option, the CityLink also supports embedded SNMP agent that can be controlled by SNMP based manager supplied by the service provider. For element and network management the NEW-NMS (Nera Element vieW - Network Management System) software provides the full range of management functionality; Fault, Performance, Security and Configuration. The integrated SNMP agent provides interface to higher level Network Management Systems. The alternative interfaces available at the IDU are described in Appendix I; IDU Interface Description.
5.0
System Configurations CityLink is available in the following configurations: Frequency Band
L6 – 11 GHz
13 – 15 GHz
1+0 (Unprotected)
OK
1+1 (Hot Standby)
OK
1+1 Frequency Diversity
OK
26 – 38 GHz
NA
1+1 (Hot Standby) – Dual Baseband
OK
OK
OK
NA
1+1 (Hot Standby) – Dual antenna
TBD
TBD
TBD
OK
32 TCM only
32 TCM only 1
2+0 Dual frequency – Single polarisation (DF-SP) 2+0 Single frequency – Dual Polarisation (SF-DP)
OK NA
NA
2+0 Alternating Polarisation (AP)
OK 1
1+0 prepared for 2+0
OK
Table I-1
40
18 – 23 GHz
System Configurations
B4008 Rev. M
Equipment Description Space Diversity and Hybrid Space Diversity is available as specified in the table below. L6 – 11 GHz
13 – 15 GHz
18 – 23 GHz
26 – 38 GHz
Space Diversity with IF combining 1+0,1+1 FD, HSB
Frequency Band
OK
NA
NA
NA
Hybrid Space Diversity (HSB)
OK
NA
NA
NA
Hybrid Space Diversity (1+1 FD)
OK
OK
OK
NA
Table I-2
5.1
Space Diversity Configurations
1+0Configuration This system consists of one indoor unit and one outdoor unit interconnected with a single coaxial cable. Figure1-11 shows a 1+0 system overview. Each of the shaded area represents a function or unit. The IDU is a single unit with plug-in STM-1 line interface and the optional Multiplexer Unit. The ODU is assembled by transceiver and branching.
Aux traffic
SDH/SONET Processing
Management
Management & SNMP Agent
Optional Plug-in Multiplex Unit DC power feeding & overvoltage protection
STM-1/OC-3 Plug-in Line Interface
Modulator Demodulator
155 Mb/s
Transceiver
Branching
Antenna
Coaxial cable (up to 300 m)
Indoor unit (IDU)
Figure I-11
B4008 Rev. M
1+0 System Overview
41
CityLink 5.2
Hot Standby Configuration In Hot Standby configuration the IDU, the transceiver unit, and the coaxial cable between IDU and ODU are duplicated. The two transceivers share the same branching unit/hybrid. A switch at radio frequency level, included in the branching unit 1, allows for switching between the two transmitters. A Switching Unit is placed between the two IDUs and performs hitless switching in the receive direction. The STM-1 line interface and Multiplex plug-in modules are mounted in this switching unit. Signal interconnection between the IDUs and the switching unit is by a multi connector and a split cable.
155Mbit/s
Aux traffic Management
STM-1/OC-3 Plug-in Line Interface Management & SNMP Agent
SDH/SONET Processing
Management
DC power feeding & overvoltage protection
Optional plug-in Multiplex Unit SDH/SONET Processing
DC power feeding & overvoltage protection
Management
Modulator Demodulator
SDH/SONET Processing
Modulator Demodulator
1) Some ODU types use a passive combiner/splitter at RF level.
Coaxial cable (up to 300 m)
Transceiver Unit Branching Unit
Antenna unit
Transceiver Unit
Outdoor unit (ODU)
Indoor unit (IDU)
Figure I-12
5.3
1+1 Frequency Diversity and Hot Standby System Overview
1+1 Frequency Diversity A 1+1 Frequency Diversity system contains duplicated IDU and ODU and a 1+1 FD branching. (Dual polarised branching can also be used.). A switching Unit is placed between the two IDUs and performs hitless switching in the receive direction. The interface units are mounted in the switching unit. Signal interconnection between the IDUs and the switching unit is by a multi connector and a split cable.
42
B4008 Rev. M
Equipment Description 5.4
Hot Standby Configuration – Dual Antenna
155Mbit/s
Aux traffic Management
STM-1/OC-3 Plug-in Line Interface Management & SNMP Agent
SDH/SONET Processing
Management
DC power feeding & overvoltage protection
Optional plug-in Multiplex Unit
Coaxial cable (up to 300 m)
Transceiver Unit Branching Unit
Antenna unit
Branching Unit
Antenna unit
SDH/SONET Processing
DC power feeding & overvoltage protection
Management
Modulator Demodulator
SDH/SONET Processing
Modulator Demodulator
The Hot Standby configuration is for 26-38 GHz also available with duplicated antenna. There is no Tx-switch at radio frequency level and the standby transmitter is muted. Both receivers are active and selection of receive signal is performed by the IDU-switch. This configuration gives better system gain as no HSB-hybrid loss is added.
Transceiver Unit
Outdoor unit (ODU)
Indoor unit (IDU)
Figure I-13
B4008 Rev. M
Hot Standby-Dual Antenna System Overview
43
CityLink 5.5
Hot Standby Configuration – Dual Baseband A special variant of the Hot Standby system is the Dual baseband option. In this configuration both IDUs are equipped with STM-1 line interface units. The switching unit is not used in this configuration. The feature enables line protection when used with muxes with dual/protected interfaces
SDH/SONET Processing
Management
Management & SNMP Agent
Aux traffic
SDH/SONET Processing
Management
Management & SNMP Agent
Coaxial cable (up to 300 m)
Transceiver Unit
Branching Unit
STM-1/OC-3 Plug-in Line Interface DC power feeding & overvoltage protection
155 Mb/s
DC power feeding & overvoltage protection
Aux traffic
Modulator Demodulator
STM-1/OC-3 Plug-in Line Interface
Modulator Demodulator
155 Mb/s
Antenna unit
Transceiver Unit
Outdoor unit (ODU)
Indoor unit (IDU)
Figure I-14
44
Hot Standby-Dual Baseband System Overview
B4008 Rev. M
Equipment Description 5.6
2+0 Configuration The 2+0 system can be used in two types of configuration, using one or two polarisations. Single Frequency – Dual Polarisation (SF-DP) and Alternating Polarisation (AP) utilise both polarisations in order to double the capacity. Dual Frequency – Single Polarisation (DF-SP) requires two channels in order to transmit 2xSTM-1. With this configuration, adjacent channels cannot be used. Figure I-15 and Figure I-16 show block diagrams of the 2+0 configurations.
Aux traffic
SDH/SONET Processing
Management
Management & SNMP Agent
Optional Plug-in Multiplex Unit DC power feeding & overvoltage protection
STM-1/OC-3 Plug-in Line Interface
Modulator Demodulator
155 Mb/s
Transceiver
Coaxial cable (up to 300 m)
Branching
H-pol
Antenna
Indoor unit (IDU)
Aux traffic
SDH/SONET Processing
Management
Management & SNMP Agent
Transceiver
Optional Plug-in Multiplex Unit DC power feeding & overvoltage protection
STM-1/OC-3 Plug-in Line Interface
Modulator Demodulator
155 Mb/s
V-pol
Branching Coaxial cable (up to 300 m)
Outdoor unit (ODU)
Indoor unit (IDU)
STM-1/OC-3 Plug-in Line Interface
Aux traffic
SDH/SONET Processing
Management
Management & SNMP Agent
Optional Plug-in Multiplex Unit DC power feeding & overvoltage protection
155 Mb/s
Single Frequency - Dual Polarisation / Alternating Polarisation
Modulator Demodulator
Figure I-15
Indoor unit (IDU)
Aux traffic
SDH/SONET Processing
Management
Management & SNMP Agent
Optional Plug-in Multiplex Unit DC power feeding & overvoltage protection
STM-1/OC-3 Plug-in Line Interface
Modulator Demodulator
155 Mb/s
Coaxial cable (up to 300 m)
Transceiver
Branching
Antenna
Transceiver
Outdoor unit (ODU)
Indoor unit (IDU)
Figure I-16 B4008 Rev. M
Dual Frequency - Single Polarisation 45
CityLink 5.7
Space Diversity
Management
DC power feeding & overvoltage protection
SDH/SONET Processing
Modulator Demodulator
Space diversity with IF combining is available in the frequencies from L6 to 11GHz. It can be used in combination with all other configurations. The figure below shows a 1+1 Frequency Diversity or HSB system.
Outdoor unit (ODU) Coaxial cable (up to 300 m)
155Mbit/s
Aux traffic Management
STM-1/OC-3 Plug-in Line Interface
Optional plug-in Multiplex Unit
Main Antenna
SD Transceiver Main Branching SD Branching
Management & SNMP Agent
SDH/SONET Processing
SD Transceiver
DC power feeding & overvoltage protection
Management
Modulator Demodulator
WG SDH/SONET Processing
SD Antenna
Indoor unit (IDU)
Figure I-17
5.8
Space Diversity
Hybrid Space Diversity Hybrid Space Diversity using standard XCVRs without IF combining is available for 1+1 FD and HSB. In HSB configuration the splitter in the receiver branch is omitted and each receiver is connected to separate antennas. The transmitters are using the main antenna. Waveguide is needed from the ODU to the SD antenna. The configuration is available for L6-11 GHz systems.
46
B4008 Rev. M
Management
DC power feeding & overvoltage protection
SDH/SONET Processing
Modulator Demodulator
Equipment Description
Outdoor unit (ODU) Coaxial cable (up to 300 m)
155Mbit/s
Aux traffic Management
STM-1/OC-3 Plug-in Line Interface
Main Antenna
Transceiver
Optional plug-in Multiplex Unit
M ain Branching SD Branching
Management & SNMP Agent
SDH/SONET Processing
Transceiver
DC power feeding & overvoltage protection
Management
Modulator Demodulator
WG SDH/SONET Processing
SD Antenna
Indoor unit (IDU)
Figure I-18
HSB Hybrid Space Diversity
In 1+1 system hybrid diversity is implemented by using two antennas at one of the sites. At this site one channel is connected to each antenna. In principle it is two 1+0 ODU operating at differnet frequencies. At the other site normal 1+1 FD system is used.
IDU User Interfaces
Figure I-19
IDU
f1 1+1 ODU
Switch
IDU
B4008 Rev. M
1+0 ODU
1+0 ODU
f2
Switch
User Interfaces
IDU
1+1 Hybrid Space Diversity
47
CityLink 5.9
Radio Terminal Configurations The radio channel can be configured with RS- or MS-termination according to ITU-T Rec.G.783. Figure 1-20 shows examples of various configurations. MST configuration requires the optional SETS function.
RRT
RRT
RS Other MS equipment
MS
Figure I-20
5.10
RRT
RRT
RS MS
RS
MS
MS
Other MS equipment
Configuration Examples
Radio Repeater Configurations A radio repeater is built by using two terminals. The interface between the terminals is at STM-1. The repeater can be configured with RS-termination according to ITU-T Rec. G.783.
5.11
Radio Channel Identification The radio channel is identified by two allocated bits in the media specific byte (MS#3) in the SOH. The channel identification can be configured by the user.
This page is intentionally left blank. 48
B4008 Rev. M
ODU Type I Installation
SECTION II Installation of ODU Type I and Antenna
B4008 Rev. M
49
CityLink
1.0
General This section assumes that pre-planning of the link has been performed, i.e. path budgeting & survey to ensure good line-of sight between the two link ends.
1.1
Packing Any sensitive product, i.e. IDU and Printed Circuit Boards, are packed in special antistatic handling bags or boxes. It is therefore essential that whenever unpacking or disassembling the equipment and or handling printed circuit boards etc., special precautions to avoid ESD (Electro Static Discharge) should be taken, such as using wrist grounding or corresponding protection. The equipment is packed in sealed plastic bags which are equipped with required moisture protection. All equipment is further packed in special designed cases prepared for transportation. Dimensions and weight of each case are specified in the "Packing specifications" issued for the respective shipment.
1.2
Marking Marking is done according to customers requirements. If such information is unavailable, the equipment is marked in the following way: Customer address Contract No. Site Name (if known) Case No.
1.3
Transportation The transport containers are prepared for shipment by air, truck, railway and sea, suitable for handling by fork-lift trucks and slings. The cargo must be kept dry during transport and storage. For sea-transport, deck-side shipment is not permitted and carrier-owned cargo containers should be used.
50
B4008 Rev. M
ODU Type I Installation 1.4
Radio Equipment Inventory Check Look for damage on the cases. Ensure that correct quantities of goods have arrived, according to the packing list in each package/unit. Check also that the part description on the outside of each box corresponds to the components required for the installation, i.e. correct antenna and frequency, ODU frequency band and sub-band, IDU configuration. Report any damages or missing items to Nera ASA by e-mail or fax. A short description of damages, preferably including photographs, should be sent as soon as possible.
1.5
Preparation for Installation Complete the required civil works. Transport all the equipment to site. Unpack the equipment and inspect for damage during transit to site and make sure that the correct quantities of goods have arrived. Units with static discharge protection should not be unpacked until the equipment installation takes place. Ensure you are grounded at a controlled ESD point before and during insertion, and during any subsequent unpacking of the unit.
1.6
Handling & Storage It is recommended that components are stored and transported to the installation site in their original packing cases. If items are unpacked for storage, they should be handled with care and protected during transportation by similar protective materials. The equipment is an electronic device which should be handled with care. It should be stored in dry, cool conditions, out of direct sunlight. A moisture absorbing bag is taped inside the transportation unit to minimise condensation during transportation. This is to be removed at installation. No maintenance is required when stored according to particulars above. To avoid damage to the sealing components and unwanted moist in the interconnection interfaces, the transportation protection lids on the branching and the transceiver must be kept on until mounting of waveguide components and connection of the transceiver to the branching unit.
B4008 Rev. M
51
CityLink
2.0 2.1
Installation Equipment required Tools The tools needed to install the equipment are listed in the following subchapters.
2.1.1
Tools for Antenna Installation • • • •
2.1.2
52
2 pcs Combination Wrench 13 mm 2 pcs Combination Wrench 16 mm 2 pcs Combination Wrench 17 mm 1 pc Torque Wrench 16 mm, 40 - 50 Nm
Tools for IDU- ODU Cable /Connector Mounting • • • • • • • • • •
1 Hacksaw, fine-toothed 1 Soldering Iron, 50-150W Solder 36/37 RMA flux core Cloth 1 Knife 1 Flat file, fine 1 Wire brush 1 Tape rule (or caliper) 1 Heat gun, 1000W 1 Cutting pliers
for • • • •
hexagon coupling nut : 1 Wrench 1/2" (13mm) 1 Wrench 9/16" (15mm) 1 Wrench 11/16" (18mm) 1 Wrench 13/16" (21mm)
B4008 Rev. M
ODU Type I Installation 2.2
Equipment external to the Radio Equipment In addition to the necessary radio equipment & antenna the following items are needed: • • • • • • • • •
B4008 Rev. M
Coaxial cable between IDU and ODU. See Section V, chapter 5 for advise on which cable to use. At least two N-type connectors suitable for termination of the selected coaxial cable. Suitable waveguide & flanges between antenna and branching unit if remote mount option is used. Cable to ground the ODU. Cable to ground the IDU. Cable to power the IDU. Cable to connect the PC, running the configuration & set-up program, to the IDU. Cable ties to secure cable runs. Cables for user interfaces.
53
CityLink
3.0
ODU / Antenna Installation, 1+0 Equipment
3.1
Installation of 0.6m and 0.45m Antenna
3.1.1
Preparing the Suspension for ODU Mounting Loosen this nut one turn.
Bracket Rotate the bracket 1800 by turning this bolt CW.
54
B4008 Rev. M
ODU Type I Installation 3.1.2
Mounting the Antenna to the Suspension All the described nuts and washers are included in the antenna assembly and come attached to the antenna.
4ea M8 Nuts and washers
B4008 Rev. M
55
CityLink 3.1.3
Mounting the Branching Support Bracket
M8x25
BRANCHING SUPPORT BRACKET
56
B4008 Rev. M
ODU Type I Installation 3.1.4
Mounting the Rear Travers
M8x25 REAR TRAVERS
3.1.5
Mounting the Suspension Support Bracket
SUSPENSION SUPPORT BRACKET
M8x25 B4008 Rev. M
57
CityLink 3.1.6
Mounting the Bend on the Branching Unit
M3 STUDS, NUTS AND WASHERS
FEED
O-RING
58
B4008 Rev. M
ODU Type I Installation 3.1.7
Installation of the Branching Unit
BRANCHING UNIT
M8 STUDS, NUTS AND WASHERS
Grounding point. See Section V Chapter 5.0 Fig. V-8
3.1.8
Attachment of the Sunshield Support M8x30 SCREW, NUT AND WASHERS
SUNSHIELD SUPPORT M8x30 SCREW, NUT AND WASHERS B4008 Rev. M
59
CityLink 3.1.9
Installation of the Flexible Waveguide M3 ALLEN SCREWS, NUT AND WASHERS
2 O-RINGS
60
O-RING
M3 STUDS, NUT AND WASHERS
R220 FLEXIBLE WAVEGUIDE
B4008 Rev. M
ODU Type I Installation 3.1.10
Installation of the Sunshield M6x25 SCREWS, NUTS, LARGE WASHERS AND WASHERS
(PLACING OF LARGE WASHER)
M4 ALLEN SCREW (FOUND MOUNTED ON THE BRANCHING UNIT)
M4x16 SCREWS, NUTS AND WASHERS
SUNSHIELD
B4008 Rev. M
61
CityLink 3.1.11
Mounting the Suspension/Antenna to a Column or a Wall
3.1.11.1
Mounting the Suspension/Antenna to a Column by using the U-bolts
U-BOLTS (ABZ5479 for column diameter Ø115mm, ABZ5480 for column diameter Ø75mm)
M10 Nuts, washers and lock washers, 4ea Torque: 25-30Nm
62
B4008 Rev. M
ODU Type I Installation 3.1.11.2
Mounting the Suspension/Antenna to a Column by using the Clamps
CLAMPS, 2ea (ABZ5481)
Column diameter: 60-115mm M10 Nuts and washers, 4ea Torque: 35Nm
B4008 Rev. M
63
CityLink 3.1.11.3
Mounting the Suspension/Antenna to a Wall
M10 Expansion bolts (type dependant on the nature of the wall
M10 Nuts and washers
64
B4008 Rev. M
ODU Type I Installation 3.1.12
Mounting the ODU to the Antenna Assembly Before mounting the ODU to the antenna assembly, it is necessary to remove the protection lid from the antenna feed. See below.
Protection lid
First remove the nuts using a 5,5mm wrench.
Then remove the set screws using a 1,5 mm allen key.
B4008 Rev. M
65
CityLink
66
B4008 Rev. M
ODU Type I Installation 3.1.13
Pole Mount
3.1.13.1
Assembly of Branching Support Bracket
CLAMP
M12 (Torque 19 NM)
BRANCHING SUPPORT BRACKET
3.1.13.2
Installation of Branching Unit and Sun-shield
BRANCHING UNIT SUN-SHIELD
M4 M8 Grounding point. See Section V Chapter 5.0 Fig. V-8 B4008 Rev. M
67
CityLink 3.2
Installation of 1.2m Antenna This chapter only descibes how to install the CityLink branching support bracket and the branching unit. For further instructions please refer to the handbook supplied with the antenna (H2602; Installation Procedure for 1.2m Antenna). For installation of the transceiver, see Chapter 3.1.7.
3.2.1
Assembly of Branching Support Bracket
HORIZONTAL GIRDER
VERTICAL GIRDER
BRANCHING SUPPORT BRACKET
HORIZONTAL GIRDER
105mm ± 5
Make sure that the distance between the top of the branching support bracket and the horizontal girder is 105mm ±5mm.
BRANCHING SUPPORT BRACKET
68
B4008 Rev. M
ODU Type I Installation 3.2.3
Installation of Branching Unit, Sun-shield and Flexible Waveguide FLEXIBLE WAVEGUIDE BRANCHING UNIT SUN-SHIELD
M4
M8 ANTENNA FEED FLEXIBLE WAVEGUIDE
NOTE! Most antennas are delivered with a bimetallic shim. This MUST NOT be mounted for 18-26GHz equipment as the ODU, the flexible waveguide and the antenna all have aluminium waveguide connectors. Flexible waveguides for 13-15GHz have silver plated brass flanges and the bimetallic shim MUST be used (copper side facing flex-wg). Mount gasket(s) between the antenna feed and the flexible waveguide and also gasket(s) between the flexible waveguide and the branching unit. If the installation is placed in a very corrosive environment, further protection can be achieved by adding silicon rubber.
B4008 Rev. M
69
CityLink
4.0
ODU / Antenna Installation, Hot Standby Equipment and 2+0 Equipment
4.1
0.45m and 0.6m Antenna
4.1.1
Installation of Hot Standby (HSB) and 2+0 Dual Frequency Single Polarization Equipment
4.1.1.1
Preparing the Suspension for ODU Mounting and Mounting the Antenna to the Suspension Please refer to Chapters 3.1.1 and 3.1.2 (this Section).
4.1.1.2
Mounting the Branching Support Bracket
M8x25
BRANCHING SUPPORT BRACKET
70
B4008 Rev. M
ODU Type I Installation 4.1.1.3
Mounting the Rear Travers, Mounting the Suspension Support Bracket and Mounting the Feed on the Branching Unit Please refer to Chapters 3.1.4 to 3.1.6 (this Section).
4.1.1.4
Installation of the HSB Branching Unit
M8x25 STUDS, NUTS AND WASHERS
BRANCHING UNIT
B4008 Rev. M
71
CityLink 4.1.1.5
Installation of the Flexible Waveguide M3 ALLEN SCREWS, NUT AND WASHERS
2 O-RINGS
72
O-RING
M3 STUDS, NUT AND WASHERS
R220 FLEXIBLE WAVEGUIDE
B4008 Rev. M
ODU Type I Installation 4.1.1.6
Installation of the Sunshield Support Bracket Please refer to Chapter 3.1.8 (this Section).
4.1.1.7
Installation of the Sunshield
M6x25 SCREWS, NUTS, LARGE WASHERS AND WASHERS (PLACING OF LARGE WASHER)
M4 ALLEN SCREW (FOUND MOUNTED ON THE BRANCHING UNIT)
M4x16 SCREWS, NUTS AND WASHERS
SUNSHIELD
B4008 Rev. M
73
CityLink 4.1.1.8
Mounting the Suspension/ODU to a Column or a Wall Please refer to Chapter 3.1.11 (this Section).
4.1.1.9
Mounting the ODU to the Antenna Assembly Before mounting the ODU to the antenna assembly, it is necessary to remove the protection lid from the antenna feed. Please refer to Chapter 3.1.12 (this Section) for details.
74
B4008 Rev. M
ODU Type I Installation 4.1.1.10
Pole Mount
4.1.1.10.1 Assembly of Branching Support Bracket
CLAMP M12 (Torque 19 NM)
BRANCHING SUPPORT BRACKET
4.1.10.1.2 Installation of Branching Unit and Sunshield
BRANCHING UNIT SUN-SHIELD
M4 M8 Grounding point. See Section V Chapter 5.0 Fig. V-9 B4008 Rev. M
75
CityLink 4.1.2
Installation of 2+0 Equipment (Single Frequency Dual polarity)
4.1.2.1
Preparing the Suspension for ODU Mounting and Mounting the Antenna to the Suspension Please refer to Chapters 3.1.1 and 3.1.2 (this Section).
4.1.2.2
Mounting the Branching Support Bracket, Mounting the Rear Travers, Mounting the Suspension Support Bracket and Mounting the Feed on the Branching Units Please refer to Chapters 3.1.3 to 3.1.6 (this Section).
4.1.2.3
Installation of the Branching Units
M8 STUDS, NUTS AND WASHERS
76
B4008 Rev. M
ODU Type I Installation 4.1.2.4
Installation of the Flexible Waveguide M3 ALLEN SCREWS, NUT AND WASHERS
M3 STUDS, NUT AND WASHERS 2 O-RINGS
R220 FLEXIBLE WAVEGUIDE
M3 ALLEN SCREWS, NUT AND WASHERS
O-RING
2 O-RINGS
M3 STUDS, NUT AND WASHERS
B4008 Rev. M
77
CityLink 4.1.2.5
Installation of the Sunshield M6x25 SCREWS, NUTS, LARGE WASHERS AND WASHERS (PLACING OF LARGE WASHER)
M4 ALLEN SCREW (FOUND MOUNTED ON THE BRANCHING UNIT)
78
SUNSHIELDS
M4 ALLEN SCREW (FOUND MOUNTED ON THE BRANCHING UNIT)
B4008 Rev. M
ODU Type I Installation 4.1.2.6
Mounting the Suspension/ODU to a Column or a Wall Please refer to Chapter 3.1.11 (this Section).
4.1.2.7
Mounting the ODU to the Antenna Assembly Before mounting the ODU to the antenna assembly, it is necessary to remove the protection lid from the antenna feed. Please refer to Chapter 3.1.12 (this Section) for details.
B4008 Rev. M
79
CityLink 4.1.2.9
Pole Mount
4.1.2.9.1
Assembly of Branching Support Bracket
CLAMP M12 (Torque 19 NM)
BRANCHING SUPPORT BRACKET
4.1.2.9.2
Installation of Branching Units and Sunshields
BRANCHING UNITS SUN-SHIELDS
M4 M8 Grounding point. See Section V Chapter 5.0 Fig. V-9 80
B4008 Rev. M
ODU Type I Installation 4.2
1.2m Antenna This chapter only descibes how to install the CityLink branching support bracket and the branching unit. For further instructions please refer to the handbook supplied with the antenna (H2602; Installation Procedure for 1.2m Antenna). For installation of the transceiver, see Chapter 4.1.5.
4.2.1
Assembly of Branching Support Bracket
HORIZONTAL GIRDER BRANCHING SUPPORT BRACKET VERTICAL GIRDER
HORIZONTAL GIRDER
130mm 5 87mm±±3mm
Make sure that the distance between the top of the branching support bracket and the horizontal girder is 130mm ±3mm.
BRANCHING SUPPORT BRACKET
B4008 Rev. M
81
CityLink 4.2.2
Installation of Branching Unit, Sun-shield and Flexible Waveguide
4.2.2.1
Hot Standby and 2+0 Dual Frequency Single Polarization
FLEXIBLE WAVEGUIDE BRANCHING UNIT
SUN-SHIELD
M4
M8
Grounding point. See Section V Chapter 5.0 Fig. V-9 NOTE! Most antennas are delivered with a bimetallic shim. This MUST NOT be mounted for CityLink installations as the ODU, the flexible waveguide and the antenna all have aluminium waveguide connectors. Mount gasket(s) between the antenna feed and the flexible waveguide and also gasket(s) between the flexible waveguide and the branching unit. If the installation is placed in a very corrosive environment, further protection can be achieved by adding silicon rubber.
82
B4008 Rev. M
ODU Type I Installation 4.2.2.2
2+0 Single Frequency Dual Polarization
FLEXIBLE WAVEGUIDES BRANCHING UNITS SUN-SHIELDS
M4 M8 Grounding point. See Section V Chapter 5.0 Fig. V-9
NOTE! Most antennas are delivered with a bimetallic shim. This MUST NOT be mounted for 18-26GHz equipment as the ODU, the flexible waveguide and the antenna all have aluminium waveguide connectors. Flexible waveguides for 13-15GHz have silver plated brass flanges and the bimetallic shim MUST be used (copper side facing flex-wg). Mount gasket(s) between the antenna feed and the flexible waveguide and also gasket(s) between the flexible waveguide and the branching unit. If the installation is placed in a very corrosive environment, further protection can be achieved by adding silicon rubber.
B4008 Rev. M
83
CityLink
5.0 Frequency Tuning at 13GHz &15GHz Transceiver This chapter gives a short description of how to set and change frequency channel on the transceiver. To perform this operation it is necessary to remove the cover and mount the transceiver to a branching connected to an IDU. A PC (where Nera software NEW is installed) and power are further connected to the IDU. A voltage meter and a screwdriver must also be available. • Switch on the power at the system • Set wanted frequency in New. Tables II-1 to II-9 give the relation between selected channel, duplex, TX High/Low and RX High/Low. The illustration on the next page gives an overview of the tuning voltage connectors (VT TX and VT RX) and tuning screws. WARNING! This equipment contains components which are sensitive to "ESD" (Electro Static Discharge). It is therefore essential that whenever disassembling the equipment and/or handling PC boards, special precautions to avoid ESD have to be made. This includes personnel grounding, grounding of work bench, grounding of tools and instruments. For the tuning process, it is also recommended to use a ceramic screw driver. • Measure the tuning voltage VT TX continuously while adjusting the tuning screw. First turn the tuning screw CCW as far as it goes. Then adjust it CW until VT TX reaches the correct voltage: For 15GHz Transceiver; 4±0.5[V] For 13GHz Transceiver; 3±0.5[V] • Measure the tuning voltage VT RX continuously when adjusting the tuning screw. First turn the tuning screw CCW as far as it goes. Then adjust it CW until VT TX reaches the correct voltage: For 15GHz Transceiver; 4±0.5[V] For 13GHz Transceiver; 3±0.5[V] After tuning VT TX and VT RX to the correct voltage, the transceiver is configured to the correct frequency channel. Inspect the gasket and replace the cover with use of correct torque (1.25Nm).
84
B4008 Rev. M
ODU Type I Installation
VT TX
GND
VT RX
B4008 Rev. M
Tx High
Rx High
Tx Low
Rx Low
85
CityLink Duplex frequency: 490 MHz Channel spacing: 28MHz TX Ch. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
TX Freq. 14417 14445 14473 14501 14529 14557 14585 14613 14641 14669 14697 14725 14753 14781 14809 14837
10L15L01A TX RX DRO Ch. Low 1’ Low 2’ Low 3’ Low 4’ Low 5’ Low 6’ Low 7’ Low 8’ Low 9’ High 10’ High 11’ High 12’ High 13’ High 14’ High 15’ High 16’
RX Freq. 14907 14935 14963 14991 15019 15047 15075 15103 15131 15159 15187 15215 15243 15271 15299 15327
RX DRO Low Low Low Low Low Low Low Low Low Low Low High High High High High
TX Ch. 1’ 2’ 3’ 4’ 5’ 6’ 7’ 8’ 9’ 10’ 11’ 12’ 13’ 14’ 15’ 16’
TX Freq. 14907 14935 14963 14991 15019 15047 15075 15103 15131 15159 15187 15215 15243 15271 15299 15327
10L15U01A TX RX DRO Ch. Low 1 Low 2 Low 3 Low 4 Low 5 Low 6 Low 7 Low 8 High 9 High 10 High 11 High 12 High 13 High 14 High 15 High 16
RX Freq. 14417 14445 14473 14501 14529 14557 14585 14613 14641 14669 14697 14725 14753 14781 14809 14837
RX DRO Low Low Low Low Low Low Low Low Low Low High High High High High High
10L15U01A TX RX DRO Ch. Low 1 Low 2 Low 3 Low 4 Low 5 Low 6 Low 7 High 8 High 9 High 10 High 11 High 12 High 13 High 14 High 15
RX Freq. 14515 14543 14571 14599 14627 14655 14683 14711 14739 14767 14795 14823 14851 14879 14907
RX DRO Low Low Low Low Low Low High High High High High High High High High
10L15U01A TX RX DRO Ch. High 1 High 2 High 3 High 4
RX Freq. 14515 14543 14571 14599
RX DRO Low Low Low Low
Table II-1 Duplex frequency: 420 MHz Channel spacing: 28MHz TX Ch. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
TX Freq. 14515 14543 14571 14599 14627 14655 14683 14711 14739 14767 14795 14823 14851 14879 14907
10L15L01A TX RX DRO Ch. Low 1’ Low 2’ Low 3’ Low 4’ Low 5’ Low 6’ High 7’ High 8’ High 9’ High 10’ High 11’ High 12’ High 13’ High 14’ High 15’
RX Freq. 14935 14963 14991 15019 15047 15075 15103 15131 15159 15187 15215 15243 15271 15299 15327
RX DRO Low Low Low Low Low Low Low High High High High High High High High
TX Ch. 1’ 2’ 3’ 4’ 5’ 6’ 7’ 8’ 9’ 10’ 11’ 12’ 13’ 14’ 15’
TX Freq. 14935 14963 14991 15019 15047 15075 15103 15131 15159 15187 15215 15243 15271 15299 15327
Table II-2 Duplex frequency: 728 MHz Channel spacing: 28MHz TX Ch. 1 2 3 4
TX Freq. 14515 14543 14571 14599
10L15L01A TX RX DRO Ch. Low 1’ Low 2’ Low 3’ Low 4’
RX Freq. 15243 15271 15299 15327
RX DRO High High High High
TX Ch. 1’ 2’ 3’ 4’
TX Freq. 15243 15271 15299 15327
Table II-3
86
B4008 Rev. M
ODU Type I Installation Duplex frequency: 315 MHz Channel spacing: 28MHz TX Ch. 1 2 3 4 5 6 7 8 9
TX Freq. 14662 14690 14718 14746 14774 14802 14830 14858 14886
10L15L01A TX RX DRO Ch. Low 1’ High 2’ High 3’ High 4’ High 5’ High 6’ High 7’ High 8’ High 9’
RX Freq. 14977 15005 15033 15061 15089 15117 15145 15173 15201
RX DRO Low Low Low Low Low Low High High High
TX Ch. 1’ 2’ 3’ 4’ 5’ 6’ 7’ 8’ 9’
TX Freq. 14977 15005 15033 15061 15089 15117 15145 15173 15201
10L15U01A TX RX DRO Ch. Low 1 Low 2 Low 3 Low 4 Low 5 Low 6 High 7 High 8 High 9
RX Freq. 14662 14690 14718 14746 14774 14802 14830 14858 14886
RX DRO Low High High High High High High High High
10L15U01A TX RX DRO Ch. High 1 High 2 High 3 High 4 High 5 High 6 High 7
RX Freq. 14515 14543 14571 14599 14627 14655 14683
RX DRO Low Low Low Low Low Low High
10L15U01A TX RX DRO Ch. Low 1 Low 2 Low 3 Low 4 Low 5 Low 6 Low 7 Low 8 Low 9 Low 10 Low 11 Low 12 Low 13 Low 14 High 15 High 16 High 17 High 18 High 19 High 20 High 21 High 22 High 23 High 24 High 25 High 26 High 27 High 28 High 29 High 30
RX Freq. 14515 14529 14543 14557 14571 14585 14599 14613 14627 14641 14655 14669 14683 14697 14711 14725 14739 14753 14767 14781 14795 14809 14823 14837 14851 14865 14879 14893 14907 14921
RX DRO Low Low Low Low Low Low Low Low Low Low Low Low High High High High High High High High High High High High High High High High High High
Table II-4 Duplex frequency: 644 MHz Channel spacing: 28MHz TX Ch. 1 2 3 4 5 6 7
TX Freq. 14515 14543 14571 14599 14627 14655 14683
10L15L01A TX RX DRO Ch. Low 1’ Low 2’ Low 3’ Low 4’ Low 5’ Low 6’ High 7’
RX Freq. 15159 15187 15215 15243 15271 15299 15327
RX DRO High High High High High High High
TX Ch. 1’ 2’ 3’ 4’ 5’ 6’ 7’
TX Freq. 15159 15187 15215 15243 15271 15299 15327
Table II-5 Duplex frequency: 420 MHz Channel spacing: 14MHz TX Ch. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30
TX Freq. 14515 14529 14543 14557 14571 14585 14599 14613 14627 14641 14655 14669 14683 14697 14711 14725 14739 14753 14767 14781 14795 14809 14823 14837 14851 14865 14879 14893 14907 14921
10L15L01A TX RX DRO Ch. Low 1’ Low 2’ Low 3’ Low 4’ Low 5’ Low 6’ Low 7’ Low 8’ Low 9’ Low 10’ Low 11’ High 12’ High 13’ High 14’ High 15’ High 16’ High 17’ High 18’ High 19’ High 20’ High 21’ High 22’ High 23’ High 24’ High 25’ High 26’ High 27’ High 28’ High 29’ High 30’
RX Freq. 14935 14949 14963 14977 14991 15005 15019 15033 15047 15061 15075 15089 15103 15117 15131 15145 15159 15173 15187 15201 15215 15229 15243 15257 15271 15285 15299 15313 15327 15341
RX DRO Low Low Low Low Low Low Low Low Low Low Low Low Low Low High High High High High High High High High High High High High High High High
TX Ch. 1’ 2’ 3’ 4’ 5’ 6’ 7’ 8’ 9’ 10’ 11’ 12’ 13’ 14’ 15’ 16’ 17’ 18’ 19’ 20’ 21’ 22’ 23’ 24’ 25’ 26’ 27’ 28’ 29’ 30’
TX Freq. 14935 14949 14963 14977 14991 15005 15019 15033 15047 15061 15075 15089 15103 15117 15131 15145 15159 15173 15187 15201 15215 15229 15243 15257 15271 15285 15299 15313 15327 15341
Table II-6 B4008 Rev. M
87
CityLink Duplex frequency: 490 MHz Channel spacing: 14MHz TX Ch. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
TX Freq. 14417 14431 14445 14459 14473 14487 14501 14515 14529 14543 14557 14571 14585 14599 14613 14627 14641 14655 14669 14683 14697 14711 14725 14739 14753 14767 14781 14795 14809 14823 14837 14851
10L15L01A TX RX DRO Ch. Low 1’ Low 2’ Low 3’ Low 4’ Low 5’ Low 6’ Low 7’ Low 8’ Low 9’ Low 10’ Low 11’ Low 12’ Low 13’ Low 14’ Low 15’ Low 16’ High 17’ High 18’ High 19’ High 20’ High 21’ High 22’ High 23’ High 24’ High 25’ High 26’ High 27’ High 28’ High 29’ High 30’ High 31’ High 32’
RX Freq. 14907 14921 14935 14949 14963 14977 14991 15005 15019 15033 15047 15061 15075 15089 15103 15117 15131 15145 15159 15173 15187 15201 15215 15229 15243 15257 15271 15285 15299 15313 15327 15341
RX DRO Low Low Low Low Low Low Low Low Low Low Low Low Low Low Low Low Low Low High High High High High High High High High High High High High High
TX Ch. 1’ 2’ 3’ 4’ 5’ 6’ 7’ 8’ 9’ 10’ 11’ 12’ 13’ 14’ 15’ 16’ 17’ 18’ 19’ 20’ 21’ 22’ 23’ 24’ 25’ 26’ 27’ 28’ 29’ 30’ 31’ 32’
TX Freq. 14907 14921 14935 14949 14963 14977 14991 15005 15019 15033 15047 15061 15075 15089 15103 15117 15131 15145 15159 15173 15187 15201 15215 15229 15243 15257 15271 15285 15299 15313 15327 15341
10L15U01A TX RX DRO Ch. Low 1 Low 2 Low 3 Low 4 Low 5 Low 6 Low 7 Low 8 Low 9 Low 10 Low 11 Low 12 Low 13 Low 14 Low 15 Low 16 High 17 High 18 High 19 High 20 High 21 High 22 High 23 High 24 High 25 High 26 High 27 High 28 High 29 High 30 High 31 High 32
RX Freq. 14417 14431 14445 14459 14473 14487 14501 14515 14529 14543 14557 14571 14585 14599 14613 14627 14641 14655 14669 14683 14697 14711 14725 14739 14753 14767 14781 14795 14809 14823 14837 14851
RX DRO Low Low Low Low Low Low Low Low Low Low Low Low Low Low Low Low Low Low Low High High High High High High High High High High High High High
10L13U01A TX RX DRO Ch. High 1 High 2 High 3 High 4 High 5 High 6 High 7 High 8
RX Freq. 12765 12793 12821 12849 12877 12905 12933 12961
RX DRO Low Low Low Low Low Low Low Low
Table II-7 Duplex frequency: 266 MHz Channel spacing: 28MHz TX Ch. 1 2 3 4 5 6 7 8
TX Freq. 12765 12793 12821 12849 12877 12905 12933 12961
10L13L01A TX RX DRO Ch. Low 1’ Low 2’ Low 3’ Low 4’ Low 5’ Low 6’ Low 7’ Low 8’
RX Freq. 13031 13059 13087 13115 13143 13171 13199 13227
RX DRO High High High High High High High High
TX Ch. 1’ 2’ 3’ 4’ 5’ 6’ 7’ 8’
TX Freq. 13031 13059 13087 13115 13143 13171 13199 13227
Table II-8
88
B4008 Rev. M
ODU Type I Installation Duplex frequency: 266 MHz Channel spacing: 14MHz TX Ch. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
TX Freq. 12758 12772 12786 12800 12814 12828 12842 12856 12870 12884 12898 12912 12926 12940 12954 12968
10L13L01A TX RX DRO Ch. Low 1’ Low 2’ Low 3’ Low 4’ Low 5’ Low 6’ Low 7’ Low 8’ Low 9’ Low 10’ Low 11’ Low 12’ Low 13’ Low 14’ Low 15’ Low 16’
RX Freq. 13024 13038 13052 13066 13080 13094 13108 13122 13136 13150 13164 13178 13192 13206 13220 13234
RX DRO High High High High High High High High High High High High High High High High
TX Ch. 1’ 2’ 3’ 4’ 5’ 6’ 7’ 8’ 9’ 10’ 11’ 12’ 13’ 14’ 15’ 16’
TX Freq. 13024 13038 13052 13066 13080 13094 13108 13122 13136 13150 13164 13178 13192 13206 13220 13234
10L13U01A TX RX DRO Ch. High 1 High 2 High 3 High 4 High 5 High 6 High 7 High 8 High 9 High 10 High 11 High 12 High 13 High 14 High 15 High 16
RX Freq. 12758 12772 12786 12800 12814 12828 12842 12856 12870 12884 12898 12912 12926 12940 12954 12968
RX DRO Low Low Low Low Low Low Low Low Low Low Low Low Low Low Low Low
Table II-9
B4008 Rev. M
89
CityLink
6.0
Cable Connections Please refer to Section V Chapter 5.0.
7.0
Antenna Alignment Please refer to Section IV Chapter 6.0.
90
B4008 Rev. M
ODU Type II Installation
SECTION III Installation of ODU Type II and Antenna
B4008 Rev. M
91
CityLink
1.0
General This section assumes that pre-planning of the link has been performed, i.e. path budgeting & survey to ensure good line-of sight between the two link ends.
1.1
Packing Any sensitive product, i.e. IDU and Printed Circuit Boards, are packed in special antistatic handling bags or boxes. It is therefore essential that whenever unpacking or disassembling the equipment and or handling printed circuit boards etc., special precautions to avoid ESD (Electro Static Discharge) should be taken, such as using wrist grounding or corresponding protection. The equipment is packed in sealed plastic bags which are equipped with required moisture protection. All equipment is further packed in special designed cases prepared for transportation. Dimensions and weight of each case are specified in the "Packing specifications" issued for the respective shipment.
1.2
Marking Marking is done according to customers requirements. If such information is unavailable, the equipment is marked in the following way: Customer address Contract No. Site Name (if known) Case No.
1.3
Transportation The transport containers are prepared for shipment by air, truck, railway and sea, suitable for handling by fork-lift trucks and slings. The cargo must be kept dry during transport and storage. For sea-transport, deck-side shipment is not permitted and carrier-owned cargo containers should be used.
92
B4008 Rev. M
ODU Type II Installation 1.4
Radio Equipment Inventory Check Look for damage on the cases. Ensure that correct quantities of goods have arrived, according to the packing list in each package/unit. Check also that the part description on the outside of each box corresponds to the components required for the installation, i.e. correct antenna and frequency, ODU frequency band and sub-band, IDU configuration. Report any damages or missing items to Nera ASA by e-mail or fax. A short description of damages, preferably including photographs, should be sent as soon as possible.
1.5
Preparation for Installation Complete the required civil works. Transport all the equipment to site. Unpack the equipment and inspect for damage during transit to site and make sure that the correct quantities of goods have arrived. Units with static discharge protection should not be unpacked until the equipment installation takes place. Ensure you are grounded at a controlled ESD point before and during insertion, and during any subsequent unpacking of the unit.
1.6
Handling & Storage It is recommended that components are stored and transported to the installation site in their original packing cases. If items are unpacked for storage, they should be handled with care and protected during transportation by similar protective materials. The equipment is an electronic device which should be handled with care. It should be stored in dry, cool conditions, out of direct sunlight. A moisture absorbing bag is taped inside the transportation unit to minimise condensation during transportation. This is to be removed at installation. No maintenance is required when stored according to particulars above. To avoid damage to the sealing components and unwanted moist in the interconnection interfaces, the transportation protection lids on the branching and the transceiver must be kept on until mounting of waveguide components and connection of the transceiver to the branching unit.
B4008 Rev. M
93
CityLink
2.0 2.1
Installation Equipment required Tools The tools needed to install the equipment are listed in the following subchapters.
2.1.1
Tools for Antenna Installation • • • •
2.1.2
94
2 pcs Combination Wrench 13 mm 2 pcs Combination Wrench 16 mm 2 pcs Combination Wrench 17 mm 1 pc Torque Wrench 16 mm, 40 - 50 Nm
Tools for IDU- ODU Cable /Connector Mounting • • • • • • • • • •
1 Hacksaw, fine-toothed 1 Soldering Iron, 50-150W Solder 36/37 RMA flux core Cloth 1 Knife 1 Flat file, fine 1 Wire brush 1 Tape rule (or caliper) 1 Heat gun, 1000W 1 Cutting pliers
for • • • •
hexagon coupling nut : 1 Wrench 1/2" (13mm) 1 Wrench 9/16" (15mm) 1 Wrench 11/16" (18mm) 1 Wrench 13/16" (21mm)
B4008 Rev. M
ODU Type II Installation 2.2
Equipment external to the Radio Equipment In addition to the necessary radio equipment & antenna the following items are needed: • • • • • • • • •
B4008 Rev. M
Coaxial cable between IDU and ODU. See Section V, chapter 5 for advise on which cable to use. At least two N-type connectors suitable for termination of the selected coaxial cable. Suitable waveguide & flanges between antenna and branching unit if remote mount option is used. Cable to ground the ODU. Cable to ground the IDU. Cable to power the IDU. Cable to connect the PC, running the configuration & set-up program, to the IDU. Cable ties to secure cable runs. Cables for user interfaces.
95
CityLink
3.0 3.1
ODU Installation Mounting the ODU to the Pole The ODU can be mounted to a Ø75mm or a Ø115mm pole, see figure below.
2 x M10 NUTS AND WASHER
U-BOLTS
Waveguide Flange type: PDR84 SUN-SHIELD
96
B4008 Rev. M
ODU Type II Installation 3.2
Cable Connections ODU BOTTOM VIEW: Pressure equalizer
AGC Connector
Ground connection. Attach grounding cable (10mm2) to this point with the M6 nut and washers.
IDU - ODU Cable Connector, N-50W For details please see Figure V-7.
B4008 Rev. M
97
CityLink
4.0
Antenna and Waveguide Installation
4.1
0.6m Antenna
Shim Copper/ Aluminium Copper side
Alu side
Flange Adapter (NL2007 only)
98
B4008 Rev. M
ODU Type II Installation 4.2
B4008 Rev. M
1.2m Antenna
99
CityLink 4.3
100
2m Antenna
B4008 Rev. M
ODU Type II Installation 4.4
B4008 Rev. M
2.4m
101
CityLink 4.5
3m
317±20
102
B4008 Rev. M
ODU Type III Installation
SECTION IV Installation of ODU Type III and Antenna
B4008 Rev. M
103
CityLink
1.0
General This section assumes that pre-planning of the link has been performed, i.e. path budgeting & survey to ensure good line-of sight between the two link ends.
1.1
Packing Any sensitive product, i.e. IDU and Printed Circuit Boards, are packed in special antistatic handling bags or boxes. It is therefore essential that whenever unpacking or disassembling the equipment and or handling printed circuit boards etc., special precautions to avoid ESD (Electro Static Discharge) should be taken, such as using wrist grounding or corresponding protection. The equipment is packed in sealed plastic bags which are equipped with required moisture protection. All equipment is further packed in special designed cases prepared for transportation. Dimensions and weight of each case are specified in the "Packing specifications" issued for the respective shipment.
1.2
Marking Marking is done according to customers requirements. If such information is unavailable, the equipment is marked in the following way: Customer address Contract No. Site Name (if known) Case No.
1.3
Transportation The transport containers are prepared for shipment by air, truck, railway and sea, suitable for handling by fork-lift trucks and slings. The cargo must be kept dry during transport and storage. For sea-transport, deck-side shipment is not permitted and carrier-owned cargo containers should be used.
104
B4008 Rev. M
ODU Type III Installation 1.4
Radio Equipment Inventory Check Look for damage on the cases. Ensure that correct quantities of goods have arrived, according to the packing list in each package/unit. Check also that the part description on the outside of each box corresponds to the components required for the installation, i.e. correct antenna and frequency, ODU frequency band and sub-band, IDU configuration. Report any damages or missing items to Nera ASA by e-mail or fax. A short description of damages, preferably including photographs, should be sent as soon as possible.
1.5
Preparation for Installation Complete the required civil works. Transport all the equipment to site. Unpack the equipment and inspect for damage during transit to site and make sure that the correct quantities of goods have arrived. Units with static discharge protection should not be unpacked until the equipment installation takes place. Ensure you are grounded at a controlled ESD point before and during insertion, and during any subsequent unpacking of the unit.
1.6
Handling & Storage It is recommended that components are stored and transported to the installation site in their original packing cases. If items are unpacked for storage, they should be handled with care and protected during transportation by similar protective materials. The equipment is an electronic device which should be handled with care. It should be stored in dry, cool conditions, out of direct sunlight. A moisture absorbing bag is taped inside the transportation unit to minimise condensation during transportation. This is to be removed at installation. No maintenance is required when stored according to particulars above. To avoid damage to the sealing components and unwanted moist in the interconnection interfaces, the transportation protection lids on the branching and the transceiver must be kept on until mounting of waveguide components and connection of the transceiver to the branching unit.
B4008 Rev. M
105
CityLink
2.0 2.1
Installation Equipment required Tools The tools needed to install the equipment are listed in the following subchapters.
2.1.1
Tools for Antenna Installation and Adjustment • • • • •
2.1.2
106
2 pcs Combination Wrench M8, 13 mm 2 pcs Combination Wrench M10, 16 mm 2 pcs Combination Wrench M6, 10 mm 1 pc Combination Wrench 10 mm 1 pc Torque Wrench, M16, 24 mm, 120 Nm
Tools for IDU- ODU Cable /Connector Mounting • • • • • • • • • •
1 Hacksaw, fine-toothed 1 Soldering Iron, 50-150W Solder 36/37 RMA flux core Cloth 1 Knife 1 Flat file, fine 1 Wire brush 1 Tape rule (or caliper) 1 Heat gun, 1000W 1 Cutting pliers
for • • • •
hexagon coupling nut : 1 Wrench 1/2" (13mm) 1 Wrench 9/16" (15mm) 1 Wrench 11/16" (18mm) 1 Wrench 13/16" (21mm)
B4008 Rev. M
ODU Type III Installation 2.2
Equipment external to the Radio Equipment In addition to the necessary radio equipment & antenna the following items are needed: • • • • • • • • •
B4008 Rev. M
Coaxial cable between IDU and ODU. See Section V, chapter 5 for advise on which cable to use. At least two N-type connectors suitable for termination of the selected coaxial cable. Suitable waveguide & flanges between antenna and branching unit if remote mount option is used. Cable to ground the ODU. Cable to ground the IDU. Cable to power the IDU. Cable to connect the PC, running the configuration & set-up program, to the IDU. Cable ties to secure cable runs. Cables for user interfaces.
107
CityLink
3.0 3.1
ODU / Antenna Installation, 1+0 Equipment Mounting the Antenna to the Suspension All the described nuts and washers are included in the antenna assembly and come attached to the antenna. SUSPENSION (3AB5158A) ANTENNA (0,3m 0,45m and 0,6m)
4ea M8 Nuts, washers and lock washers
108
B4008 Rev. M
ODU Type III Installation 3.2
Mounting the Sunshield The Sunshield, screws, nuts and washers are found in the kit AZZ5495.
M6 Nuts, washers and lock washers (4ea) SUNSHIELD M6 Screws (4ea)
B4008 Rev. M
109
CityLink 3.3
Mounting the Suspension/Antenna to a Column by using the U-bolts
U-BOLTS (ABZ5479 for column diameter Ø115mm, ABZ5480 for column diameter Ø75mm)
M10 Nuts, washers and lock washers, 4ea Torque: 25-30Nm
110
B4008 Rev. M
ODU Type III Installation 3.4
Mounting the Suspension/Antenna to a Column by using the Clamps
CLAMPS, 2ea (ABZ5481)
Column diameter: 60-115mm M10 Nuts and washers, 4ea Torque: 35Nm
B4008 Rev. M
111
CityLink 3.5
Mounting the Transceiver (without Antenna) to a Column STEP 1
Mounting the Brackets on the Frame
Bracket (Kit: ABZ5774)
4ea M8x20 screws 8ea Flat washers 4ea Lock washers 4ea M8 Nuts (Kit:ABZ5774)
Bracket (Kit: ABZ5774)
112
B4008 Rev. M
ODU Type III Installation STEP 2
Attaching the Frame to the Column
4ea M10 Flat washers 8ea M10 Nuts (Kit:ABZ5774)
2ea M10 U-bolts (Kit: ABZ5774)
B4008 Rev. M
113
CityLink STEP 3
Mounting the Sunshields Sunshields (Kit: ABZ5779)
2ea M5x12 screws 8ea M5 flat washers 4ea M5 lock washers 4ea M5 nuts (Kit: ABZ5774)
114
B4008 Rev. M
ODU Type III Installation STEP 4
Mounting the Transceiver
1+0 Configuration
1+1/HSB Configuration
B4008 Rev. M
115
CityLink STEP 5
Mounting the Flexible Waveguide
1+0 Configuration
Mounting flange for flexible waveguide
1+1/HSB Configuration
Mounting flange for flexible waveguide
116
B4008 Rev. M
ODU Type III Installation 3.6
Mounting the Suspension/Antenna to a Wall
M10 Expansion bolts (type dependant on the nature of the wall
Ø10mm Predrilled holes M10 Nuts and washers
B4008 Rev. M
117
CityLink 3.7
Mounting the ODU to the Antenna Assembly Before mounting the ODU to the antenna assembly, it is necessary to remove the protection lid from the antenna feed. See below.
Protection lid
First remove the nuts using a 5,5mm wrench.
Then remove the set screws using a 1,5 mm allen key.
118
B4008 Rev. M
ODU Type III Installation
After adjustment; M16 torque = 110-120Nm For adjustment see Chapter 6.0.
For correct polarisation; see next page
LATCHES (4ea, one in each corner) To unlock the latches, push this handle forward
B4008 Rev. M
119
CityLink Polarization The electrical field is always orthogonal to the two opposing sides of the two broad sides of the rectangular waveguide. It is important to mount the ODU to the antenna with the right orientation. The arrows on the ODU's handle shall indicate the polarisation (vertical or horizontal). UP
DOWN Waveguide feed with vertical polarisation
Waveguide feed with horizontal polarisation
UP POLARIZATION POLARIZATION
POLARIZATION
POLARIZATION
DOWN ODU orientation for vertical polarisation
120
ODU orientation for horizontal polarisation
B4008 Rev. M
ODU Type III Installation
4.0 4.1
ODU / Antenna Installation, HSB and 2+0 Equipment Preparing the Suspension for HSB and 2+0 Mounting
Loosen this nut one turn. (See also Chapter 6.0)
Bracket Rotate the bracket 1800 by turning this bolt CW.
B4008 Rev. M
121
CityLink 4.2
Mounting the Antenna to the Supension
4ea M8 Nuts and washers
122
B4008 Rev. M
ODU Type III Installation 4.3
Mounting the Hybrid Frame to the Antenna STEP 1 Note! Mounting sequence is important!
2ea M8 Set screws, nuts, washers and lock washers
B4008 Rev. M
123
CityLink STEP 2 Note! Mounting sequence is important!
M8 Screws,nuts and washers
M8 Screws,nuts and washers
124
B4008 Rev. M
ODU Type III Installation 4.3
Mounting the CityLink III ODUs to the Antenna Assembly
LATCHES (1 in each corner of each ODU)
B4008 Rev. M
125
CityLink 4.4
Mounting the Transceiver (without Antenna) to the Column Please refer to Chapter 3.5 (this Section).
4.5
Mounting the Suspension/Antenna to a Wall Please refer to Chapter 3.6 (this Section).
126
B4008 Rev. M
ODU Type III Installation
5.0
Cable Connections ODU BOTTOM VIEW: IDU - ODU Cable Connector, N-50W For details please see Figure V-7.
Pressure equalizer
AGC Connector. In a 1+1 configuation, this connector is used for interconnection between the two ODUs.
B4008 Rev. M
Ground connection. Attach grounding cable (10mm2) to this point with the M6 nut and washers.
127
CityLink
6.0 6.1
Antenna Alignment Azimuth and Elevation Adjustment
Azimuth Adjustment Torque: 110-120Nm
• Unlock securing nut approx. 1 turn before azimuth adjusting • Adjust azimuth • Lock securing nut after adjustment
Elevation Adjustment • Unlock securing nut approx. 1/2 turn before elevation adjusting • Adjust elevation • Lock securing nut after adjustment
Torque: 110-120Nm
6.2
Coarse adjustment. Adjust both antennas to correct direction as possible by using magnetic compass or optical sight.
6.3
Fine adjustment Fine adjustment is achieved by setting up a connection between the antennas. When the connection is established a readout of the AGC voltage can be used to align the antennas. Loosen the antenna in both elevation and azimuth according to figure and adjust both azimuth and elevation until maximum signal is recived. Try a few times in each direction. The antenna should be turned so much that the first sidelobes are seen, thereby ensure that the antenna is aligned on the mainlobe. When the antenna is aligned in both azimuth and elevation the polarization of the feed shall be realigned. Finally ensure that all bolts and nuts are properly mounted and tighten. The same procedure shall than be repeated on the opposite antenna.
128
B4008 Rev. M
ODU Type III Installation 6.4
Final Control When all adjustments are performed, check that the input level agrees with the calculated level. If the input level is to low, realign the antenna once more. Finally ensure that all bolts and nuts are properly mounted and tighten.
6.5
Polarisation alignment Align the antenna approximately in both elevation and azimuth. Then use a water level to align the polarisation of the antenna feed to correct polarisation according to figures below. Loosen the six M8 nuts that are securing the feed to the reflector and rotate the feed according to readout of the water level. When the feed is in correct alignment, tighten the six M8 nuts properly (do not overtight the nuts). Then the ODU can be mounted and the antenna has to be aligned. If the antenna has to be rotated several degrees in azimuth or elevation, the polarisation has to be realigned according to prior procedures.
Horizontal Polarisation: When the H mark is in upwards position, this shows that the antenna is Horizontal Polarized
Water level
Use these stud screws for aligning the feed with water level.
B4008 Rev. M
129
CityLink Vertical Polarisation:
When the V mark is in upwards position, this showes that the antenna are Vertical Polarised
Water level
Use these stud screws for aligning the feed with water level.
130
B4008 Rev. M
IDU Installation
SECTION V IDU Installation
64kb/s 64kb/s SVCE Phone Phone 64kb/s 2Mb/s 2Mb/s SVCE SVCE Phone G.703 Ext. 1 11 G.703Wayside WaysideExt. Ext.
POWER 1
POWER POWER2 POWER
ODU ODU
B4008 Rev. M
-48VDC -48VDC -48VDC
NI NI NI 111 155 Mb/s LINE 155 Mb/s LINE 155 Mb/s LINE RXDIRA
G.703 G.703
PWR PWR1 PWR 2
RXDIRB
INP INP OUT OUT 64kb/s 2MHz 2MHz SVCE SVCE10BaseT 10BaseT 2MHz SVCE 64kb/s 64kb/s V.11 Sync. Sync. Ext. Ext. LAN Sync. 2 2 LAN V.11
IDU- HSB - HSBINTFC INTFC IDU IDU INTFC
CALL CALL CALL
ALM&& &AUX AUX ALM ALM AUX
LCT LCT LCT
NI NI NI 22
TXDIRA TXDIRB
CRITICAL CRITICAL CRITICAL MAJOR MAJOR MAJOR MINOR MINOR MINOR WARNING WARNING WARNING
131
CityLink
1.0
General This section assumes that pre-planning of the link has been performed, i.e. path budgeting & survey to ensure good line-of sight between the two link ends.
1.1
Packing Any sensitive product, i.e. IDU and Printed Circuit Boards, are packed in special antistatic handling bags or boxes. It is therefore essential that whenever unpacking or disassembling the equipment and or handling printed circuit boards etc., special precautions to avoid ESD (Electro Static Discharge) should be taken, such as using wrist grounding or corresponding protection. The equipment is packed in sealed plastic bags which are equipped with required moisture protection. All equipment is further packed in special designed cases prepared for transportation. Dimensions and weight of each case are specified in the "Packing specifications" issued for the respective shipment.
1.2
Marking Marking is done according to customers requirements. If such information is unavailable, the equipment is marked in the following way: Customer address Contract No. Site Name (if known) Case No.
1.3
Transportation The transport containers are prepared for shipment by air, truck, railway and sea, suitable for handling by fork-lift trucks and slings. The cargo must be kept dry during transport and storage. For sea-transport, deck-side shipment is not permitted and carrier-owned cargo containers should be used.
132
B4008 Rev. M
IDU Installation 1.4
Radio Equipment Inventory Check Look for damage on the cases. Ensure that correct quantities of goods have arrived, according to the packing list in each package/unit. Check also that the part description on the outside of each box corresponds to the components required for the installation, i.e. correct antenna and frequency, ODU frequency band and sub-band, IDU configuration. Report any damages or missing items to Nera ASA by e-mail or fax. A short description of damages, preferably including photographs, should be sent as soon as possible.
1.5
Preparation for Installation Complete the required civil works. Transport all the equipment to site. Unpack the equipment and inspect for damage during transit to site and make sure that the correct quantities of goods have arrived. Units with static discharge protection should not be unpacked until the equipment installation takes place. Ensure you are grounded at a controlled ESD point before and during insertion, and during any subsequent unpacking of the unit.
1.6
Handling & Storage It is recommended that components are stored and transported to the installation site in their original packing cases. If items are unpacked for storage, they should be handled with care and protected during transportation by similar protective materials. The equipment is an electronic device which should be handled with care. It should be stored in dry, cool conditions, out of direct sunlight. A moisture absorbing bag is taped inside the transportation unit to minimise condensation during transportation. This is to be removed at installation. No maintenance is required when stored according to particulars above.
B4008 Rev. M
133
CityLink
2.0 2.1.
IDU Installation Mounting the IDU in an ANSI (19") or an ETSI Rack Mount the relevant mechanical adapters provided in the IDU package by using the M3-6mm TORX screws also provided in the IDU package. The long adapters are for ETSI Rack, while the short are for ANSI Rack. See Figure V-1. Position the IDU in the rack and secure it by using the four M6-12mm screws provided in the IDU package. See Figure V-2.
ANSI Rack Adapter
ETSI Rack Adapter
Figure V-1 Mounting the Mechanical Adapters for ANSI or ETSI Rack
64kb/s 64kb/s 2Mb/s SVCE Phone Phone 2Mb/s SVCE G.703 G.703Wayside WaysideExt. 1 1 Ext.
POWER 1
POWER POWER2 POWER
ODU ODU
-48VDC -48VDC
NI NI 11 155 Mb/s LINE 155 Mb/s LINE G.703 G.703
PWR PWR1 PWR 2
RXDIRA
CRITICAL CRITICAL CRITICAL
RXDIRB
MAJOR MAJOR MAJOR
INP INP OUT OUT 2MHz SVCE SVCE10BaseT 10BaseT 64kb/s 64kb/s 2MHz Sync. Ext. V.11 Sync. Ext. 2 2 LAN LAN V.11
MINOR MINOR MINOR
IDU IDU- HSB - HSBINTFC INTFC
CALL CALL CALL
ALM&&AUX AUX ALM ALM AUX
LCT LCT LCT
NI22 NI NI
TXDIRA TXDIRB
WARNING WARNING W ARNING
FLAT WASHER WASHER M6x12
Figure V-2 Mounting the IDU in a Rack 134
B4008 Rev. M
IDU Installation 2.2
Cable Installation ❒ Route, secure if necessary with cable ties, and terminate ground cable between the IDU safety ground post and a nearby local safety ground point. Use the 6mm2 cable (2.5m long) included in the grounding kit. Refer to Figures X-1 and X-2 (Section X, Appendix 1) for the IDU safety ground post location. ❒ Route, secure if necessary with cable ties, the terminated IDU/ODU cable and connect to the ODU port of the IDU. See Chapter 5.0 (this Section) for further details. NOTE! Max torque = 5Nm when mounting the IDU/ODU cable. ❒ Route and secure the power cable. The CityLink requires DC power (-40,5 to -57V) via a 2-pin connector. Refer to Figure X-7 (Section X, Appendix 1) for a pinout of the connectors. It is recommended to use the supplied power cable, UWMK5051. The cable is left unconnected in one end. The black conductor must be connected to 0V (station gnd) and the blue conductor must be connected to -48V. After connecting the cable to the power supply, measure polarity on power connector terminals. ❒ Dependent on the purchased configuration of the IDU, route and attach all cables except the power cable. Refer to Section X, Appendix 1 for wiring details.
B4008 Rev. M
135
CityLink
3.0
Hot Standby IDU Installation (2+0 IDU installation is similar to ordinary IDU installation, see Ch. 2.0)
3.1
Mounting the Hot Standby IDUs in a Rack Mount the relevant mechanical adapters provided in the IDU package by using the M3-6mm TORX screws also provided in the IDU package.See Figure V-1 (Chapter 2.1). Position the IDUs in the rack and secure them by using the four M6-12mm screws provided in each IDU package. See Figures V-3 & V-4.
IDU A 64kb/s 64kb/s 2Mb/s 2Mb/s SVCE SVCE Phone Phone G.703 1 1 G.703Wayside WaysideExt. Ext.
POWER 1
POWER POWER2 POWER
ODU ODU
64kb/s 64kb/s 2Mb/s 2Mb/s SVCE SVCE Phone Phone G.703 G.703Wayside WaysideExt. Ext. 1 1
POWER POWER2 POWER
ODU ODU
ALM&&AUX AUX ALM ALM AUX
NI22 NI NI
LCT LCT
TXDIRA TXDIRB
WARNING WARNING
NI NI 11
RXDIRA RXDIRB
INP INP OUT OUT
CRITICAL CRITICAL MAJOR MAJOR MINOR MINOR
IDU IDU- HSB - HSBINTFC INTFC
CALL CALL
ALM ALM&&AUX AUX
NI NI 22
LCT LCT
TXDIRA TXDIRB
WARNING WARNING
RXDIRA
CRITICAL CRITICAL MAJOR MAJOR MAJOR
NI NI NI11 155 Mb/s LINE 155 Mb/s LINE G.703 G.703
PWR PWR1 PWR 2
RXDIRB
INP INP OUT OUT SVCE10BaseT 2MHz SVCE 10BaseT 64kb/s 2MHz 64kb/s Sync. Ext. LAN Ext. 2 2 LAN V.11 Sync. V.11
-48VDC -48VDC
CALL CALL CALL
155 Mb/s LINE 155 Mb/s LINE
2MHz SVCE SVCE10BaseT 10BaseT 64kb/s 64kb/s 2MHz Sync. Ext. Ext. 2 2 LAN LAN V.11 V.11 Sync.
64kb/s 64kb/s 2Mb/s 2Mb/s SVCE SVCE Phone Phone G.703 WaysideExt. Ext. 1 1 G.703Wayside
CRITICAL CRITICAL CRITICAL MAJOR MAJOR MAJOR MINOR MINOR MINOR
IDU HSBINTFC IDU - -HSB IDU HSB INTFC
G.703 G.703
PWR PWR 1 2
-48VDC -48VDC
POWER 1
RXDIRA RXDIRB
INP INP OUT OUT 2MHz SVCE SVCE10BaseT 10BaseT 64kb/s 64kb/s 2MHz 2 2 LAN Sync. Ext. Ext. LAN V.11 V.11 Sync.
-48VDC -48VDC
POWER POWER 2
NI NI 111 155 Mb/s LINE 155 Mb/s LINE G.703 G.703
PWR PWR1 PWR 2
POWER 1
ODU
HSB-IDU
IDU IDU- HSB - HSBINTFC INTFC
CALL CALL
ALM ALM&&AUX AUX
LCT LCT LCT
TXDIRA TXDIRB
NI NI 222
MINOR MINOR MINOR WARNING WARNING WARNING
IDU B
M6x12
FLAT WASHER WASHER
Figure V-3 Mounting the Hot Standby IDUs in an ANSI Rack
IDU A
HSB-IDU
64kb/s 2Mb/s SVCE G.703 Wayside Ext. 1
Phone
NI 1 155 Mb/s LINE CRITICAL
POWER
MAJOR
PWR
MINOR WARNING
ODU
64kb/s V.11
-48VDC
SVCE 10BaseT Ext. 2 LAN
64kb/s 2Mb/s SVCE G.703 Wayside Ext. 1
POWER 1
POWER2 POWER
2MHz Sync.
IDU - HSB INTFC
CALL
ALM & AUX
LCT
Phone
NI 2
NI 1 155 Mb/s LINE G.703
PWR PWR1
ODU
64kb/s V.11
-48VDC
RXDIRA
CRITICAL
RXDIRB
MAJOR
INP OUT
MINOR
2 2MHz Sync.
SVCE 10BaseT Ext. 2 LAN
64kb/s 2Mb/s SVCE G.703 Wayside Ext. 1
IDU - HSB INTFC
CALL
ALM & AUX
LCT
Phone
NI 2
TXDIRA TXDIRB
WARNING
NI 1 155 Mb/s LINE CRITICAL
POWER
MAJOR
PWR
MINOR WARNING
ODU
-48VDC
64kb/s V.11
2MHz Sync.
SVCE 10BaseT Ext. 2 LAN
IDU - HSB INTFC
CALL
ALM & AUX
LCT
NI 2
IDU B FLAT WASHER WASHER M6x12
Figure V-4 Mounting the Hot Standby IDUs in an ETSI Rack 136
B4008 Rev. M
IDU Installation 3.2
Interconnections in a Hot Standby System Interconnections between the IDUs in a Hot Standby system are done by means of a Y-cable. The cabel connectors are marked respectively IDU A, HSB-IDU and IDU B and this indicates which IDU they shall be connected to. See Figure V-5. Y-Cable
IDU A HSB IDU IDU B
Figure V-5 Interconnections in a Hot Standby System
WARNING! If the Y-cable connectors marked with IDU A and IDU B are swapped, the IDUs must always be rebooted after this operation.
NOTE! Max torque = 5Nm when mounting the IDU/ODU cable.
B4008 Rev. M
137
CityLink
4.0
Installation of Optional Extension Boards WARNING! This equipment contains components which are sensitive to "ESD" (Electro Static Discharge). It is therefore essential that whenever disassembling the equipment and/or handling PC boards, special precautions to avoid ESD have to be made. This includes personnel grounding, grounding of work bench, grounding of tools and instruments.
Step 1 Remove the four screws that holds the lid
Step 2 Use a flat screwdriver to carefully remove the lid.
138
B4008 Rev. M
IDU Installation Step 3 Remove screws and bushings (2ea) from the spacers and also the three screws from the IDU front as shown below.
Step 4 Remove the blindplates from the front of the IDU.
B4008 Rev. M
139
CityLink Step 5 Mount the extension board. Press the extension board towards the IDU's front and push the rear edge downwards until you are able to mount the screws and bushings in the spacers.
Step 6 Mount the new front using the three screws removed in Step 4 (only two screws for the 21x2Mbit/s Extension Board).
Step 7 Remount the lid.
140
B4008 Rev. M
IDU Installation
5.0
IDU/ODU Cable Installation Both ends of the cable must be terminated with N-male connectors. We recommend to use cables with outer conductor of solid corrugated copper. For other cable types, the cable and all necessary installation materials must be arranged by the purchaser. Cable length limitations are dependent upon cable type used. The table below show limtations for some cables. Cable lenghts include cable ties.See Table V-1. Cable Type
DC resistance R
FSJ1-50A
16.3 Ω/km
If the length is 100 m minimum voltage to IDU must be
If the length is 200 m minimum voltage to IDU must be
If the length is 300 m minimum voltage to IDU must be
90 m (-40.5 V)* 100 m (-40.7 V) Dev. 0.2V
Bending radius 25 mm
200 m (-43.5 V)
See Note 1
300 m (-46.0 V)
LDF1-50 See Note 2
8,48 Ω/km
180 m (-40.5 V)* 200 m (- 40.8 V) Deviation 0.3 V
LCF14-50J See Note 3 LCF38-50J See Note 4
9.6 Ω/km
160 m (-40.5 V)* 200 m (-41.1 V) Deviation 0.6 V
75 mm 300 m (- 42.5 V) 40 / 120 mm single / rptd 300 m (-42.9 V)
5.0 Ω/km
50 / 95 mm single / rptd
*) Standard (ETSI) specified minimum supply voltage to IDU is –40,5 V
Table V-1
Cable length limitation due to different DC resistance
Notes: 1. Not selected as standard stock item. 2. Standard cable kits are available as 100 m and 200 m 3. Standard cable kits are available as 100 m, 150 m and 200 m 4. Standard cable kits are available as 250 m and 300 m. Standard version of LCF38-50 (6.7 Ω/km) can not be used. Only the cable type LCF38-50 with solid copper inner conductor must be used (RFS part no. 152 225 11). IDU to ODU Coax Cable 1 2 3 4 5 6
Cable Kit 100 m LCF14-50 Cable Kit 150 m LCF14-50 Cable Kit 200 m LCF14-50 N-Connector Kit Preparation Tool for LCF14 For cable run 200 –300 m: Cable & Connector Kit 300 m LCF38-50
7
Extra Connector Kit
8
Preparation Tool for LCF38
Table V-2
B4008 Rev. M
100 m ¼” Coax Cable including 200 Cable Ties 150 m ¼” Coax Cable including 300 Cable Ties 200 m ¼” Coax Cable including 400 Cable Ties Connectors for IDU & ODU and Cable Grounding Easy cable preparation for connector attachment
85W5147-100 85W5147-150 85W5147-200 87K5148-N 85W5147-TL
300 m 3/8” Coax Cable including 600 Cable Ties and Connectors for ODU & IDU including jumper cable and Cable Grounding Kit Connectors for ODU & IDU including jumper cable and Cable Grounding Kit Easy cable preparation for connector attachment
85W5011-K300 87K5013-1A 85W5011-TL
Selected Coax Cables and Connector Kits
141
CityLink • • • •
Avoid excessive bending. Run the cable where it is reasonable well protected and will not rub against sharp edges or overly abrasive surfaces. The N-connectors should be tightened to the IDU and ODU according to the manufacturers installation instructions (provided with the connectors) but with a max torque of 5Nm on the IDU. Leave enough slack in the cable termination to the ODU to allow antenna re-positioning. The cable connection to the ODU should be made weatherproof using the cable connector weatherproof sleeve provided in the installation kit. See Figure V-7.
See Figure V-6 for Cable Arrangement.
142
B4008 Rev. M
IDU Installation Antenna
ODU
Grounding point. (See Figure V-8)
2a
NOTE 1 Weather protection kit ABZ278 (See Figure V-7)
3a 1
1a
2b
1 2c
IDU A
3c Tower Structure
HSB-IDU IDU B
4
3b Equipment Earthing Bar
Buried Earthing Network
Item
Description
Part No.
Remarks
1 1a 2a 2b 2c 3a 3b 3c 4
Coax Cable Cable Tie Connector, N-male, straight for ODU Connector, N-male, angle for IDU Grounding Kit for coax cable Grounding Cable for ODU Grounding Cable for IDU Grounding Jumper Cable IDU/SW DC Power Supply Cable
See Table V-1, -2a & -2b
Supplied as Cable Kit, cable with ties (2 per m).
See Table V2a & -2b
Supplied as Connector Kit.
UWA7
Supplied as separate kit UWA7.
UWMK5051
Included in IDU connection kit and HSB IDU interconnection kit.
Figure V-6
B4008 Rev. M
Cable Arrangement, Mandatory Items
143
CityLink BOTTOM OF BRANCHING UNIT
OUTDOOR UNIT ODU
N - CONNECTOR female, chassis
SEALING 75N06D-1
BOTTOM OF BRANCHING UNIT
N - CONNECTOR male, cable
APPLY SEALING COMPOUND HERE
PROTECTION SLEEVE
HOSE CLAMP 97Z6A-5 N - CONNECTOR
PROTECTION SLEEVE 97E12A-1 HOSE CLAMP
NOTE: (NOTE 1) ALL CODED ITEMS ARE INCLUDED IN KIT ABZ278
CABLE CONNECTION 1. Slide the Protection Sleeve and the Hose Clamp over the connector and onto the cable. 2. Connect the cable to the ODU. Press the protection sleeve over the connector and tighten the connector by hand (using the sleeve gives a good hand-grip when tightening). 3. Pull the protection sleeve backwards and apply Sealing Compound (Plast 2000) onto the top end of the sleeve. Press the sleeve upwards and over the connector until it stops into the groove around the ODU connector‘s nut and washer. 4. Adjust the clamp diameter with a screwdriver and slide in the clamp between the sleeve and the ODU‘s cooling ribs and place it over the connector head.Tighten the clamp with a screwdriver.
Figure V-7 144
Coax Cable Connection B4008 Rev. M
IDU Installation WARNING! Do not use the Branching Unit's sealing screw for grounding purpose.
Attach grounding cable (10mm2) to this point with the M8 nut and washers. Figure V-8
Branching Unit Grounding Point
WARNING! Do not use the Branching Unit's sealing screws for grounding purpose.
Attach grounding cable (10mm2) to this point with the M6 nut and washers. Figure V-9 B4008 Rev. M
Hot Standby and 2+0 DF-SP Branching Unit Grounding Point 145
CityLink
6.0
Change of Fan-Cassette Fan cassette (if equipped) is located on the right hand side of the IDU. The cassette may be replaced on live unit, without traffic interrupt. Withdraw old cassette by pulling on knob on front of unit and replace with new unit. Some combinations of circuit boards requires the use of fan-cassette in order to control heat. In case a fan-cassette is to be installed in a unit not previously having one, a blind front cover will have to be unscrewed and discarded before installing a new cassette.
This page is intentionally left blank. 146
B4008 Rev. M
Preparations for Operation
SECTION VI Preparations for Operation
B4008 Rev. M
147
CityLink
1.0
General This section assumes that the radio terminal has been installed according to the guidelines in Sections II - V.
1.1
Equipment required • •
1.2
Voltmeter for AGC voltage monitoring (with cable to connect to BNC-connector) Cable for connection between AGC monitoring point and voltmeter.
Connections See Appendix I for a more detailed description of connectors. Verify the following: • Correct line interface plug-in board is installed. • Cable for main traffic is connected. • Connection of IDU safety ground. Use min. 10 mm2 cable. • Coaxial cable between IDU and ODU is connected. • Cable between IDU and the PC running the configuration & set-up program is connected. NOTE: RJ-45 modular plugs used on patch cables etc. must mechanically comply with Federal Communications Commission - Part 68 (FCC-68). Optionally the following connections may be used: • ALM/AUX connector for parallel alarm inputs and outputs. • 2x64kbit/s connector for 64kbit/s serial channels utilising bytes in the Section Overhead. • NI-1 and/or NI-2 connectors for interface to other Nera equipment. • 2Mbit/s WAYSIDE connectors for interface to 2Mbit/s wayside traffic channel utilising bytes in the Section Overhead. • 2MHz SYNC connectors for synchronisation purposes. • Handset and extension connectors. • LAN Interface connectors.
2.0
Power on Apply power to the IDU by connecting the power cable. The radio link start-up procedure and self-diagnostics will start to execute. When power is applied to the IDU the system will perform self test, this will take a few seconds.
148
B4008 Rev. M
Preparations for Operation 2.1
NEW-NMS/NEW-Configurator Startup and connecting to Network Elements The NEW-NMS/NEW-Configurator (Nera Element vieW-Network Management System/ -Configurator) program must be installed on a PC satisfying the following minimum requirements: • • • • • •
NT4.0/Win95/Win98 operating system Pentium 133MHz processor 32MB memory 200MB disk size 1 COM port CD-ROM drive
Follow carefully the program installation instructions to make sure the program is successfully installed. The element viewer can monitor the Network Elements (NEs) using a serial connection (RS-232) or a TCP/IP connection (or both for different network elements). Apply all external connections to the PC before the program is started. A serial connection must be used the first time the network manager/ configurator is connected to the CityLink, because the IP address must be set in the CityLink, before a TCP/IP connection can be established.
2.1.1
Starting NEW-NMS/NEW-Configurator with Serial Connection (RS-232/ LCT). Apply the serial cable to one of the serial ports of the PC and the LCT port of the CityLink. Start the program. A Log on dialog box pops up. Log on to the network with your user id and password. Note! NEW-NMS' security system has initially one user account: User ID: admin Password: adminpasswd It is strongly recommended to change this password! The program has an auto discover function which automatically discovers NEs connected to the serial ports of the PC when starting. If some NEs are connected to the serial ports of the PC, the network topology is automatically discovered and presented in the Explorer view. Press Add to include discovered elements in the network topology of the program. The auto discover function can also be manually executed by selecting Discover
B4008 Rev. M
149
CityLink from the File menu. When discovering the network manually, the program looks for NEs at the open ports listed in the Communication dialog box (select Communication from the Configuration menu).
2.1.2
Starting NEW-NMS/NEW-Configurator with TCP/IP Connection. (Assumes the TCP/IP address is configured in the CityLink ) Apply Ethernet connections to both the CityLink and PC. Start the program. A Log on dialog box pops up. Log on to the network with your user id and password. Note! NEW-NMS' security system has initially one user account: User ID: admin Password: adminpasswd It is strongly recommended to change this password! The program does not know the IP-address of the network element so the connection must be manually established. To configure a TCP/IP connection to the network element, select Communication from the Configuration menu. Press the Add button and type the IP address of the NE in the address field of the dialog box which pops up. Press OK to save the changes, and OK to close the Communication Configuration dialog box. Select Discover from the File menu. Press Add to include discovered elements in the network topology of the program. The accepted network elements will be discovered and presented in the Explorer view.
2.2
Initial configuration When the program has established contact with the CityLink, some configurations must be set before antenna alignment can be performed. A Configuration Wizard will guide you through the initial configurations. Start the Wizard by selecting the network element in the Explorer view. Then select Configuration > Wizard from the right mousebutton context menu. Follow the Wizard instructions. All the configuration settings are described in Section VII; Configuration. You are now ready to proceed with antenna alignment. Please refer to Section IV Chapter 6.0 (ODU Type I & III) or the installation manual for the actual antenna (ODU Type II)
150
B4008 Rev. M
Configuration with NEW-Configurator
SECTION VII Configuration by NEW Configurator
B4008 Rev. M
151
CityLink
1.0
General This section assumes that the Preparations for Operation described in Section VI has been performed for the complete radio link hop. Configuration of the Network Elements is done from the Explorer View which can be launched by selecting Explore Net from the View menu. Configuration of Network Elements is achieved using a set of propertysheets. The property-sheets are modeless, so configuration of several different modules can be displayed simultaneously. To open the configuration property-sheets: Press the Right mouse-button on the Network Element node/leaf you want to view/change the current configurations. A dynamic menu pops up. Open the Configuration sub-menu and select the configuration-specific menu item. The configuration property sheets can also be launched by selecting/ marking an NE node/leaf in the Explorer View and then selecting the configuration-specific menu item under the Edit sub menu in the Configuration menu. The property-sheets are divided into two categories by means of functionality: Configuration Property sheets with Multiple Settings: The program retrieves the current settings from the NE when the propertysheet is opened. No message is sent to the element and no data is modified in NEW’s data structure before the user presses one of the property-sheet buttons:
Figure VII-1 Buttons on Configuration property sheets with multiple settings
Buttons: Get: Set: Close: Help:
Retrieves the current settings from the NE. Sends the current settings to the NE. Closes the property-sheet without saving or setting any data Displays help for the active property-page.
. 152
B4008 Rev. M
Configuration with NEW-Configurator • To change the settings: 1 Get the current settings from the NE by pressing Get. The current NE settings are automatically retrieved when the propertysheet is opened. 2 Alter the settings. 3 Press Set to send the changes to the NE. Configuration Property sheets with Single Interactive Settings: The program retrieves the current NE settings when the property-sheet is opened. Has no Get, Set or Save buttons; All functional buttons are placed in the property-pages. A message is sent to the Network Element immediately when a control is changed or a button is pressed. Property-sheet buttons:
Figure VII-2 Buttons on Configuration property sheets with single interactive settings
Buttons: Close:Closes the property-sheet. Help: Displays help for the active property-page. All property-pages have an information field at the bottom reflecting the current status of the data shown in the property-page and the date and time the property sheet data was retrieved from the network element.
Figure VII-3 Configuration property sheet information field
B4008 Rev. M
153
CityLink
2.0 2.1
Element Node Element Id The CityLink Element Id property sheet shows some main information about the Network Element like name, type, serial number and different addresses. The fields with white background can be altered by users with proper user privileges. The gray fields are non editable. The Element Id configuration sheet can be opened from the Configuration context menu of the Element node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Element node in the Explorer view and then selecting Edit Element Id from the Configuration menu.
Figure VII-4 Element ID Configuration Sheet
154
B4008 Rev. M
Configuration with NEW-Configurator Fields:
Description:
Serial number: NE type: Name: Section address: NE address:
The serial number of the NE. (Not editable) The type of NE. (Not editable) The name of the NE (max. 32 characters) The section address of the NE. (1-254) The NE address (1-128). Used for identification of NEs within a section. The Media Access Control address of the NE. Used for OSI-Management. (Not editable) The Network Service Access Point address of the NE. Used for OSI-Management. The Internet Protocol address of the NE. This field is checked if the NE is a hot standby element.
MAC address: NSAP address: IP address Hot standby:
To change the settings: 1 First, get the current settings from the NE by pressing Get. (The settings are automatically retrieved from the NE when the property-sheet is opened.) 2 Alter the settings you want to change. 3 Press Set to send the changes to the NE.
B4008 Rev. M
155
CityLink 2.2
Available Functions The available functions property sheet shows the functions available at the network element. All these functions are additional CityLink functions. The user has paid extra to get these functions. Contact your Nera equipment supplier to order functions. You will get an encrypted authentication string in return. The Available Functions configuration sheet can be opened from the Configuration context menu of the Element node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Element node in the Explorer view and then selecting Edit Available Functions from the Configuration menu.
Figure VII-5 Available Functions Configuration Sheet
Fields: Automatic transmitted power control (ATPC) IP stack Synchronous equipment timing source Simple network management protocol (SNMP) 64 Kbit/s channels 2 Mbit/s wayside channel Alarm auxiliary function
Description: ATPC is a function for effectively reducing interference probabilities.. The NE has an integrated IP stack. Synchronous equipment timing source is (SETS) available. An SNMP management agent is available. Two 64 Kbit/s channels can be inserted into the STM-1 Section Overhead (SOH ). One 2Mbit/s wayside channel can be inserted into the STM-1 Section Overhead (SOH ). A unit containing an auxiliary alarm unit and an auxiliary output unit is available.
STM-1 156
B4008 Rev. M
Configuration with NEW-Configurator 2.3
Notifications The NE can send notifications to NEW when specific events occur. When using notifications, NEW gets new information faster than if only polling is used. Polling should however be used in addition to notifications. The NE keeps individual notification settings for each NEW that is logged on to the NE, such that the settings made from one NEW only apply to that NEW. Note that the settings will be reset to default when NEW logs on to the NE or when the IDU is reset. A notification is enabled when the corresponding checkbox is checked ( ). The Notifications configuration sheet can be opened from the Configuration context menu of the Element node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Element node in the Explorer view and then selecting Edit Notifications from the Configuration menu.
Figure VII-6
B4008 Rev. M
Notifications Configuration Sheet
157
CityLink Fields:
Choices:
Description:
Event s Alarm
When checked, Alarm notifications will be sent from the NE to the program. Security When checked, Security notifications will be sent from the NE to the program. Switching When checked, Switching notifications will be sent from the NE to the program.
Alarm severity Critical
Major Minor
Warning
158
(When the Alarm Events is disabled, these functions are inactive) When checked, Alarm notifications will be sent from the NE to the program if Critical alarms occur. When checked, Alarm notifications will be sent from the NE to the program if Major alarms occur. When checked, Alarm notifications will be sent from the NE to the program if Minor alarms occur. When checked, Alarm notifications will be sent from the NE to the program if Warnings occur.
B4008 Rev. M
Configuration with NEW-Configurator 2.4
NE Clock Page The NE Clock sheet lets you synchronize the Network Element Date/Time with the NEW-NMS / PC Date/Time. (The NE Clock is set to the same date/time as the PC Clock). The NE Clock configuration sheet can be opened from the Configuration context menu of the Element node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Element node in the Explorer view and then selecting Edit NE Clock from the Configuration menu.
Figure VII-7 NE Clock Configuration Sheet
Fields:
Description:
The NE's Clock:
The Date and Time retrieved from the Network Element. The difference between the PC clock and the Network Element Clock.
Difference from
B4008 Rev. M
159
CityLink 2.5
Software Download CityLink Application software can be downloaded through the NEW-NMS/ NEW-Configurator program. The SW Download configuration can be started from the Configuration context menu of the Element node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Element node in the Explorer view and then selecting Edit SW Download from the Configuration menu. To download new NE application code: 1. The process of downloading starts with selecting the file containing the application code. The file has extension: .bin. When a .bin-file is selected, a dialog box will appear. 2. Verify that the correct version of the code file is chosen. Press Cancel if wrong code file is chosen. 3. Press Start Download 4. Wait until the download is finished. New application software is now downloaded at the NE. Now the NE must start to use the new software. The new software will not start to execute until it is activated. This is done from the SW Version property sheet.
160
B4008 Rev. M
Configuration with NEW-Configurator 2.6
Software Versions The SW versions property sheet shows the software revisions and their status. The IDU contains two application code memory banks for both the SU (IDU) and the Transceiver (ODU). Both the IDU and the ODU use application code from one bank, while the other bank is available for SW download. New software can be downloaded (see Chapter 2.5 SW Download) in the unused bank while the IDU or ODU is executing the code of the other bank. The user may also select which bank to execute the application from if both banks contain valid software. The ODU contains an application code software bank in addition to the two banks in the IDU. The ODU software is copied from the active IDU bank to the ODU bank during the ODU boot process. The SW Versions configuration sheet can be opened from the Configuration context menu of the Element node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Element node in the Explorer view and then selecting Edit SW Versions from the Configuration menu.
Figure VII-8 SW Version Configuration Sheet
B4008 Rev. M
161
CityLink Fields:
Description:
SW Component Bank Revision Status
Name of the software Software location Software revision Idle:Software is not being executed. Active:Software is being executed. Loading: SW is downloading to this bank. Invalid: Incomplete or invalid SW; SW bank has not been used or a SW download has failed. Not contact with unit: The IDU does not have contact with the unit containing this SW.
To activate a memory bank: 1 Select the unused bank (status: Idle) by clicking the left mouse button. 2 Press the Set Active button The NE will be reset and when it starts, the application code of the chosen bank will be executed.
162
B4008 Rev. M
Configuration with NEW-Configurator
3.0
Transmission Node
3.1
Transmission Configuration (Section Termination)
3.1.1
Section Termination, SW-version < R2A00 The CityLink Section Termination sheet shows the channel configuration of the network element. For CityLink systems, the number of the different channel settings is fixed. Only the Channel Termination can be changed. The Section Termination configuration sheet can be opened from the Configuration context menu of the Transmission node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Transmission node in the Explorer view and then selecting Edit Section Termination from the Configuration menu.
Figure VII-9 Section Termination Configuration Sheet
Fields:
Description:
Regular channels: Protection channels: Regular co. channels: Protection co. channels: Channels: Channel Termination
The Number of Regular Channels. The Number of Protection Channels. The Number of Regular Co. Channels. The Number of Protection Co. Channels. List of NE Channels with the channel properties. Name of the channel. MS (Multiplexer section) or RS (Regenerator Section) (Double-click the field to edit). The MS and RS are parts of the STM-1 Section overhead. Together MS and RS form the total SOH.
To change the settings: 1. Get the current settings from the NE by pressing Get. 2. Alter the settings you want to change. To change the Termination settings, double-click in the appropriate cell in the list. A Combo-box where you can select RS or MS is then displayed 3. Press Set to send the changes to the NE. B4008 Rev. M
163
CityLink 3.1.2
Transmission Configuration, SW-version ≥ R2A00 The Transmission Configuration sheet is used to set the transmission standard and termination on the element. When the applied termination is different from RST, the sheet is also used to configure the SETS functionality. A CityLink element may support different extension boards. This includes the DS3/E3 Extension Board, the STM-1 Extension Board or the 21x2Mbit/ s tributary board. Each element will, however, only support one extension board at a time. From the Transmission Configuration sheet the user can enable the functionality of the specific extension board. The 21x2Mbit/s extension board assumes a frame structure which contains 63 E1s. To enable this board, select the termination to be Lower Order Path Termination LOPT. If the DS3/E3 Extension Board or the STM-1 Extension Board is mounted, the frame structure must be set explicitly. The Transmission Configuration configuration sheet can be opened from the Configuration context menu of the Transmission node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Transmission node in the Explorer view and then selecting Edit Transmission Configuration from the Configuration menu.
Figure VII-10 Section Termination Configuration Sheet
164
B4008 Rev. M
Configuration with NEW-Configurator Fields:
Description:
Termination Enabling The type of termination this element shall support. Legal values are: • RST • MST • Lower Order Path Termination - LOPT • Enable X-Connect (available only if XConnect Extension Board is equipped) • Enable DS3/E3 (available only if DS3/E3 Extension Board is equipped) Note: If this setting is changed and applied to the element, the equipment will perform a software reset. Transmission Standard The Transmission System used. Legal values are: • SDH • SONET Element Type
The type of «timing element» we’re supposed to be. This is important in a network where SETS is applied. Legal values are: • SEC • SSU Local (G.812 Local) • SSU Transit (G812 Transit) • PRC
SSU Clock Source
This field will only be enabled whenever the Element Type is set to either SSU (G.812 Local) or SSU (G.812 Transit). The SSU is an external clock regenerator or filter that will remove jitter from the clock on its input. It will then output a regenerated clock on its output. The SSU is connected to the element via the 2MHz synch RJ-45 plug on the front of the IDU. The clock source can be one of the following: • LINE • RADIO • Any dropped 2Mbit/s • LINE EXT The last option will only be available if the XConnect Extension Board is present.
B4008 Rev. M
165
CityLink
166
SSU Squelch Level
This field will only be enabled whenever the Element Type is set to either SSU (G.812 Local) or SSU (G.812 Transit). If the quality of the clock source changes to a quality that is below this «quality squelch» level, the 2MHz synch output to the SSU will be squelched. This in turn will cause the SSU to enter holdover mode (or free-running), i.e. the clock quality it sends to the 2MHz synch input will have a G.812 quality (ref. ITU-T Recommendation G.812) that is based upon the internal oscillator in the SSU. Legal squelch levels are: • Better or equal G.813 • Better or equal G.812 Local • Better or equal G.812 Transit • Equal G.811
Clock Priority
This is the first column in the Clock Priority list view. This field will only be enabled whenever the Element Type is set to SEC. This is just a number specifying the priority of the rows where 1 is the higher priority. The user can not change anything in this column.
Clock Source
This is the second column in the Clock Priority list view. This field will only be enabled whenever the Element Type is set to SEC. If e.g. the user double clicks the first cell in this column, a combobox will be shown over the cell. The user can than select from where the clock to this priority list item shall be taken. This can also be done for the 2nd and 3rd cell in this column. The 4th cell, on the other hand, is the internal oscillator which will be used whenever the element is in holdover mode. This cell can’t be altered. Legal values are: • LINE • RADIO • 2MHz Synch • LINE EXT Note: Only one of the priority list items can be configured to take its clock source from a 2Mbit/s tributary at the time. This is due to HW constraints.
B4008 Rev. M
Configuration with NEW-Configurator Clock Quality This is the third column in the Clock Priority list view. This field will only be enabled whenever the Element Type is set to SEC. If the Clock Source field for a specific priority list item is set to either STM-1 LINE or STM-1 RADIO, the corresponding cell in this column will be set to SSM and will be grayed out (i.e. disabled). This means that the content of the S1-byte (located in the MSOH) will inform the element of which clock quality the traffic in the specific directions is clocked with. If the Clock Source field for a specific priority list item is set to be taken from the 2MHz Synch input, or it is to be taken from a 2Mbit/s tributary, their clock quality aren’t embedded in the traffic in any way. This means that the user will have to set their clock qualities manually. In these cases, the cell in question in this column will be enabled and the user can set the quality. Legal values are: • G.813 • G.812 Local • G.812 Transit • G.811 In addition to these, SSM will also be present in the list but can not be selected. Note: Ref. ITU-T for more information regarding the different G.8xx recommendations. Enabled
This is the fourth column in the Clock Priority list view. This field will only be enabled whenever the Element Type is set to SEC. If a specific priority list item has this cell checked it will be present in the clock priority scheme. If not it is ignored.
Active Priority This is the fifth column in the Clock Priority list view. This field presents the currently active clock. The field is updated each time the “GET” button is pressed. Note: If the user, by means of the Drop or Continue dialog, removes any of the tributaries in the list above, they will automatically be removed from the list!
Buttons: SSM Dialog:
B4008 Rev. M
This button will only be visible when the in user level of the logged in user is equal to or greater than Administrator. It will spawn a new dialog that will poll for the SSM in both radio- and line direction of the STM-1 traffic. 167
CityLink Get:
Click this button to retrieve the current settings from the NE. Any modifications done to the GUI elements will be lost and the «dirty» token will be removed. Set: Click this button to send the settings to the NE. Any modifications done to the GUI elements will be applied the NE and the «dirty» token will be removed. Close: Click this button to close the property sheet. Help: Press this button to get help on the current property sheet. For help on an item, click at the top of the dialog box, then click the item. A brief description of the different terminations: RST: This is the default setting on the element when delivered from the factory. With this configuration the SDH structure is ignored, i.e. it can be anything because the virtual containers will not be accessed. The equipment will monitor and re-generate B1 pulses. M1 REI and B2 will only be monitored. Figure VII-11 shows the Transmission Configuration dialog when this setting is applied. Note: When the element is RST, all the SETS elements of the dialog are disabled. This is because SETS only is used when the element is configured as MST or Lower Order Path Termination - LOPT. Even though the SETS functionality is disabled, the user can see the last applied MST settings.
Figure VII-11 Transmission Configuration, RST 168
B4008 Rev. M
Configuration with NEW-Configurator MST: With this configuration the SDH structure is ignored, i.e. it can be anything because the virtual containers will not be accessed. The equipment will monitor and regenerate B1-, M1 REI- and B2-pulses. Figure VII-12 shows how the dialog looks when this setting is applied.
Figure VII-12 Transmission Configuration, MST Lower Order Path Termination - LOPT: With this configuration the SDH structure is assumed to have a VC-12 mapping and the the equipment will monitor and regenerate B1, M1 REI, B2 and BIP-2 pulses. Figure VII-13 shows how the dialog looks when this setting is applied.
Figure VII-13 Transmission Configuration, LOPT B4008 Rev. M
169
CityLink Enable X-Connect: To enable the X-Connect functionality, select “Enable X-Connect” from the “Termination enabling” combo box and press the “SET” button. The SDH structure may be configured from the “Frame Structure” page.
Figure VII-14 Transmission Configuration, Enable X-Connect Enable DS3/E3: To enable the DS3/E3 functionality, select “Enable DS3/E3” from the “Termination enabling” combo box and press the “SET” button. The SDH structure may be configured from the “Frame Structure” page.
Figure VII-15 Transmission Configuration, Enable DS3/E3 170
B4008 Rev. M
Configuration with NEW-Configurator Enable 21x2: This functionality is only available with new target software. To enable the 21x2 functionality, select “Enable 21x2” from the “Termination enabling” combo box and press the “SET” button. The SDH structure may be configured from the “Frame Structure” page.
Figure VII-16 Transmission Configuration, Enable 21x2
B4008 Rev. M
171
CityLink 3.1.3
SSM - Synchronization Status Message The SSM sheet is used to monitor the received S1-byte in the two STM1 directions; LINE and RADIO. The SSM - Synchronization Status Message configuration sheet can be opened from the Section Termination sheet by clicking the SSM Dialog button on this sheet. Note: The SSM Dialog button will only be visible for Administrator users in the Section Termination sheet.
Figure VII-17 The SSM Configuration Sheet
Fields:
Description:
Direction
From which STM-1 direction the S1 byte is monitored. This can be either Line or Radio Will show the last time the specific S1 byte changed it’s value. The current content of the specific S1 byte. A human readable interpretation of the S1 byte. These can be:
Last change S1 byte Description
172
B4008 Rev. M
Configuration with NEW-Configurator S1 byte 0000 0001 0010 0011 0100 0101 0110 0111 1000 1001 1010 1011 1100 1101 1110 1111
3.2
SDH synchronization quality level description Quality unknown (existing sync network) Reserved G.811 Reserved G.812 transit Reserved Reserved Reserved G.812 local Reserved Reserved Synchronous equipment timing source (SETS) Reserved Reserved Reserved Do not use for synchronization
Alarm Indication Signal Insert (For advanced users) The Path Trace functionality and the AIS (Alarm Indicator Signal) functionality are used for verifying that the received STM-1 frames are the frames we want to receive (correct routing, frequency alignment...). This is done by either inserting a fixed byte or a user defined ASCII string in the J0 slot in the RSOH, or a two bit RF ID symbol at the transmit end. This is done from the path trace sheet. The RF ID functionality is only available at the Radio side. The radio that receives the STM-1 frames must have the same Trace string (J0) or RF ID defined in the AIS insert sheet. If there is a mismatch, an AIS can be inserted. An AIS can also be inserted if the HBER threshold is exceeded. The AIS Insert configuration sheet can be opened from the Configuration context menu of both the Transmission Radio and Line Rx nodes in the Explorer view. The sheet can also be invoked by selecting (highlighting) one of the Transmission Radio and Line Rx nodes in the Explorer view and then selecting Edit AIS Insert from the Configuration menu.
B4008 Rev. M
173
CityLink
Figure VII-18 AIS Insert Configuration Sheet
Fields:
Insert AIS when Viterbi HBER threshold exceeded
An AIS is inserted when the Viterbi HBER threshold is exceeded. (See Chapter 4.4.9 for setting of BER threshold.)
Insert AIS when trace mismatch
An AIS is inserted when there is a mismatch between the Trace String set in the Path Trace sheet and Trace String set on this sheet.
Insert AIS when RF ID mismatch
An AIS is inserted when there is a mismatch between the RF ID set in the Path Trace sheet and RF ID bit set on this sheet. The RF ID functionality is only available at the Radio node.
AIS remove delay
1 - 200 seconds
Regenerator section trace (J0)
174
Subfields: Description:
Not used
The Regenerator Section Trace String is not used. Fixed byte The Regenerator Section Trace String is one byte ( =8 bit) long. B4008 Rev. M
Configuration with NEW-Configurator Fields: Subfields:
Description:
User message The Regenerator Section Trace String is a user de(ASCII) fined message ASCII (sixteen bytes =128bits long) Expected: The ASCII string or fixed byte to be compared with received J0 in RSOH. If mismatch, AIS will be inserted if the Insert AIS when trace mismatch box is checked. The Expected field normally contains the same values as the Trace string in the Path trace property sheet at the transmit end of the path. Received: The ASCII string or fixed byte in received J0 in RSOH. Status: The status of the Regenerator Section Trace: • OK: Expected and received Regenerator Section Trace are identical. • RS-TIM alarm: (Regenerator Section Trace Identifier Mismatch) Mismath between expected and received RS Trace. • LOF error: Loss of frame alarm on received STM-1 signal. Thus, J0 is not available. Alarm status, OK or RS-TIM alarm will be latched. • CRC error: CRC error in received Regenerator Section Trace. (Only in User Message mode) • Invalid: Not valid User Message received. RF ID:
B4008 Rev. M
(The RF ID functionality is only available at the Radio node) Not used/Used: RF_ID MS3 bit on/off Expected: The value to be compared with the RF ID byte in the received SOH. If mismatch, AIS will be inserted if the Insert AIS when RF ID mismatch box is checked. The Expected field normally contains the same values as the RF ID value in the Path Trace property sheet at the transmit end of the path. Received: The received RF ID value. Status: The status of the RF ID: • OK: Expected and received RF ID values are identical. • RF-ID alarm: Mismatch between expected and received RF ID values. • Invalid: Not valid RF ID value received. 175
CityLink 3.3
Path Trace (For advanced users) The Path Trace functionality and the AIS (Alarm Indicator Signal) functionality are used to test that the received STM-1 frames are the frames we want to receive (correct routing, frequency alignment. . . . ). This is done by either inserting a fixed byte or an user defined ASCII sting in the J0 slot in the RSOH, or a two bit RF ID symbol at the transmit end. This is done from the path trace sheet. The RF ID functionality is only available at the Radio side. The radio that receives the STM-1 frames must have the same Trace string (J0) or RF ID defined in the AIS insert sheet. If there is a mismatch, an AIS can be inserted. An AIS can also be inserted if the HBER threshold is exceeded. The Path Trace configuration sheet can be opened from the Configuration context menu of both the Transmission Radio and Line Tx nodes in the Explorer view. The sheet can also be invoked by selecting (highlighting) the one of the Transmission Radio and Line Tx nodes in the Explorer view and then selecting Edit Path Trace from the Configuration menu.
Figure VII-19 Path Trace Configuration Sheet
176
B4008 Rev. M
Configuration with NEW-Configurator Fields:
Subfields
Description:
Regenerator section trace string Enabled
When checked the specific Trace String is sent in the J0 byte. Fixed byte The Regenerator Section Trace String is one byte ( =8bit) long. User message The Regenerator Section Trace (ASCII) String is a user defined message ASCII (sixteen bytes =128bits long) Trace string Specifies the data (Fixed byte or User Message) to be inserted into the J0 byte. RF ID Not used/Used RF_ID MS3 bit on/off Two bit combination.
B4008 Rev. M
177
CityLink
4.0 4.1
Equipment Node Network Routing The active and initial routing tables map incoming messages that are addressed to other NEs, to different communication ports. The active routing table is used by the IDU to route messages to other NEs, using the best path detected. The IDU regularly searches for connected NEs through all enabled communication ports to detect any changes in the network topology. This table is initialised with the initial routing entries when the IDU is rebooted (and when the initial routing table is configured by the user) and then evolves towards an optimal routing table. The initial routing table is used after the IDU has been booted. This table is used as a starting point for the routing mechanism, and will thus, if properly set, decrease the time the NE uses to create a sufficient active routing table. Initial routing entries can be manually added and active routing entries can be copied to the initial table. The Routing Table configuration sheet can be opened from the Configuration context menu of the Equipment node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Equipment node in the Explorer view and then selecting Edit Routing Table from the Configuration menu.
178
B4008 Rev. M
Configuration with NEW-Configurator
Figure VII-20 Routing Table Configuration Sheet, Active Tab (top) and Initial Tab (bottom)
B4008 Rev. M
179
CityLink Fields:
Description:
Auto/Manual
If Auto, the router may update the entry in the active routing table automatically based on shortest path/ lowest weight. If Manual, the entry is never changed by the router and fixed route configuration is used. The Section number of the addressed NE (1-128). The NE address of the destination NE. If this number is 255, section routing is used. That means that this routing entry is used for all NEs in the specified section. Possible values: 1...62 (and broadcast address 255). The communication port of which the messages are to be routed through. Possible values: • NI1 • NI2 • DCC Line • DCC Radio • OSI TP4 tunnel 1 (Server) • OSI TP4 tunnel 2 (Server) • OSI TP4 tunnel 1 (Client) • OSI TP4 tunnel 2 (Client) • TCP/IP tunnel 1 (Server) • TCP/IP tunnel 2 (Server) • TCP/IP tunnel 1 (Client) • TCP/IP tunnel 2 (Client) A computed weight that gives an indication of the communication capacity to the destination network element. A high number denotes a longer response time.
Section NE
Port
Weight
Buttons: Add:
Displays the Add Routing Entry dialog box where a new initial routing entry can be configured. Edit: Displays the Edit Routing Entry dialog box where the selected initial routing entry can be configured. Delete: Deletes the selected routing entries. Add to static: Copies the selected routing entries to the initial routing table.
180
B4008 Rev. M
Configuration with NEW-Configurator 4.2
IP Routing Static Routes Maximum 20 static routes can be configured on a Nera OSPF router. Active Routes An Nera OSPF router supports approximately 200 active routes. OSPF areas It is not recomended to have more than 25 OSPF routers per OSPF area. Each area may export up to 8 address ranges. Fixed configuration options The Nera OSPF implementation is not a dedicated router implementation and as such some parameters that would normally be configurable are fixed. For interoperability with other equipment it is however sometimes important that the configuration of external equipment match these values. Name Inject default route into stub area Router dead interval Hello interval Retransmit delay Retransmit interval Authentication
Value YES 40 sec 10 sec 1 sec 5 sec NO
Limitations This implementation supports a basic implementation of OSPF v.2 (RFC 2823). It does not support virtual links and MD5 authentication. Other options This implementation supports a rudimentary mechanism for distribution of static and RIP2 routes. The implementation also supports exporting routes to RIP2.
B4008 Rev. M
181
CityLink 4.2.1
General Settings The general settings page allows the user to control the general use of the OSPF and RIP 2 protocols for the selected NE. Enabling of protocols on specific interfaces are performed in the Rip Interfaces and OSPF Interfaces property pages.
Figure VII-21 IP Routing Configuration Sheet,General Settings
182
B4008 Rev. M
Configuration with NEW-Configurator Property page controls: OSPF Protocol: Select parameter settings for OSPF routing protocol. Enable: Enables the NE to handle OSPF routing. Redistribute RIP: Allows OSPF to redistribute routing information from RIP v2 routing protocol. Redistribute Static: Allows OSPF to redistribute static routing information. Default Cost: Setting of default cost value used for OSPF protocol. The “Redistribute” options allow the OSPF protocol to pass the routing information of other routing protocols. For information to be passed between the OSPF and RIP protocols, the current NE must have both protocols enabled. RIP Protocol:
Select parameter settings for RIP routing protocol. Enable: Enables the NE to handle RIP routing. Redistribute OSPF: Allows RIP to redistribute routing information from OSPF routing protocol. Redistribute Static: Allows RIP to redistribute static routing information. Default Metric: Setting of default metric value used for RIP protocol. The “Redistribute” options allow the RIP protocol to pass the routing information of other routing protocols. For information to be passed between the OSPF and RIP protocols, the current NE must have both protocols enabled.
IP Configurable List of interfaces available on the current NE for the OSPF Interfaces: and RIP protocols (IP enabled interfaces). Interfaces may be enabled for IP in the Communication Ports page for the specific interface (e.g. NI interface on CityLink).
B4008 Rev. M
183
CityLink 4.2.2
Active Routes Monitor active routes for current NE from this page.
Figure VII-22 IP Routing Configuration Sheet, Active Routes
184
B4008 Rev. M
Configuration with NEW-Configurator 4.2.3
Static Routes Edit static routes regarding IP Routing using this page.
Figure VII-23
IP Routing Configuration Sheet, Static Routes
Property page controls: Add: Edit:
Add a new static route to the list using the appearing dialog. Select a row and press ‘Edit’ to open the ‘Edit Static Route’ dialog. In this dialog the settings for the selected route may be changed. Delete: Deletes the selected row(s) from the list. Note! Changes to the Static Routes are not transferred to the NE before ‘Set’ is pressed.
B4008 Rev. M
185
CityLink 4.2.4
RIP Interfaces Edit RIP Interfaces for current NE from this page. Note! In order to edit the ‘RIP areas’ settings, the RIP protocol must be disabled in the General Settings page.
Figure VII-24
IP Routing Configuration Sheet, RIP Interfaces
Property page controls: Add: Edit:
Add a new RIP interface to the list using the appearing dialog. Select a row and press ‘Edit’ to open the ‘Edit RIP Interface’ dialog. In this dialog the settings for the selected interface may be changed. Delete: Deletes the selected row(s) from the list. Note! Changes to the RIP Interfaces are not transferred to the NE before ‘Set’ is pressed.
186
B4008 Rev. M
Configuration with NEW-Configurator 4.2.5
OSPF Interfaces Edit OSPF Interfaces for current NE from this page. Note! In order to edit the ‘OSPF Interfaces’ settings, the OSPF protocol must be disabled in the General Settings page.
Figure VII-25
IP Routing Configuration Sheet, OSPF Interfaces
Property page controls: Add: Edit:
Add a new OSPF interface to the list using the appearing dialog. Select a row and press ‘Edit’ to open the ‘Edit OSPF Interface’ dialog. In this dialog the settings for the selected interface may be changed. Delete: Deletes the selected row(s) from the list. Note! Changes to the OSPF Interfaces are not transferred to the NE before ‘Set’ is pressed.
B4008 Rev. M
187
CityLink 4.2.6
OSPF Areas Edit settings for ‘OSPF areas’ for current NE from this page. Note! In order to edit the ‘OSPF Areas’ settings, the OSPF protocol must be disabled in the General Settings page.
Figure VII-26
IP Routing Configuration Sheet, OSPF Interfaces
Property page controls: Add:
Add a new OSPF area to the list using the appearing dialog. Note! Use ‘Edit’ dialog to add new network ranges to existing areas. Edit: Select a row and press ‘Edit’ to open the ‘Edit OSPF Area’ dialog. In this dialog the settings for the area which the row belongs to may be changed. Delete: Deletes the selected row(s) from the list. If a network range row is selected, only the network range is deleted. In all other cases, the entire area is deleted. Note! Changes to the OSPF areas are not transferred to the NE before ‘Set’ is pressed.
188
B4008 Rev. M
Configuration with NEW-Configurator 4.3 4.3.1
Communication Ports DCC (Data Communication Channel) The CityLink DCC (Data Communication Channel) is used to communicate between the Supervisory Unit of the Network Element and Supervisory Units of other Network Elements through the SOH of the STM-1 traffic. There are two DCC ports. DCC Line at the line side and DCC Radio at the radio side. The DCC Radio is always enabled. Nera Stack will always be enabled at DCC Radio. The Communication Ports configuration sheet can be opened from the Configuration context menu of the Equipment node in the Explorer view. Press the DCC tab to view/change the DCC settings. The sheet can also be invoked by selecting (highlighting) the Equipment node in the Explorer view and then selecting Edit Communication Ports from the Configuration menu.
Fields:
Choices:
Description:
Figure VII-27 DCC Tab in Communication Ports Configuration Sheet
B4008 Rev. M
189
CityLink Enabled Channel: Ch. 1-Ch XX
Switches the DCC communication ports on/off. The Channel where the DCC are inserted in the SOH. CityLink has only one channel. This field will always be ‘Ch. 1’ at CityLink.
Direction Line Radio Timeslot:
DCC Line is inserted the line side of the radio. DCC Radio is inserted the radio side of the radio. Shows which timeslot in the SOH the DCC channels use. The user can change the used timeslot by pressing SOH. The SDH Frame Section Overhead Dialog box will appear.
Stack Nera
QECC TCP/IP LAPD
Network side User side PPP:
Active mode Demand dial Direct mode Passive mode
190
NERA Stack. Nera stack is always enabled on the radio side (DCC Radio). QECC Stack TCP/IP Stack Data link layer for the QECC protocol. For more information refer to ITU-T G.784 and ITU-T Q.921. Server for the LAPD requests. Client for the LAPD requests. (Point to Point Protocol) Data link layer for the TCP/IP protocol. (currently not implemented) (currently not implemented) (currently not implemented) (currently not implemented) (currently not implemented)
B4008 Rev. M
Configuration with NEW-Configurator 4.3.2
NI (Network Interface) The CityLink NI (Network Interface) ports (NI-1 and NI-2) are used to connect the Supervisory Unit of the Network Element to Supervisory Units of other Network Elements. The NI ports on the front panel of the CityLink IDU are used to connect the Network Elements. The NI ports can be set to a variety of different configurations. The NI 2 port, in the CityLink Radio, can be Enabled only if the Ethernet function is Disabled, and vice versa. The Communication Ports configuration sheet can be opened from the Configuration context menu of the Equipment node in the Explorer view. Press the NI tab to view/change the NI settings. The sheet can also be invoked by selecting (highlighting) the Equipment node in the Explorer view and then selecting Edit Communication Ports from the Configuration menu.
Figure VII-28 NI Tab in Communication Ports Configuration Sheet
B4008 Rev. M
191
CityLink Fields: Enabled Function
Choices: CityLink NL29x NI NL29x Qx PDH Synchronous PDH Asynchronous V.11 contra dir master V.11 contra dir slave V.11 co dir Q1 V.11 NL29x V.11 contra dir slave
Baudrate
1200 to 200000
Description: Enables the NI port The functionality of the NI port. The baud rate and stack are grayed/whitened to indicate which settings are necessary for the different functionalities.
The baud rate (symbols pr. second) of the NI port. If the field is grayed, no baud rate is necessary to set. Baud
Stack Nera OSI LAPD
Network side User side PPP:
Active mode Demand dial Direct mode Passive mode
192
NERA Stack. OSI Stack Data link layer for the QECC protocol. For more information refer to ITU-T G.784 and ITU-T Q.921. Server for the LAPD requests. Client for the LAPD requests. (Point to Point Protocol) Data link layer for the TCP/IP protocol. (currently not implemented) (currently not implemented) (currently not implemented) (currently not implemented) (currently not implemented)
B4008 Rev. M
Configuration with NEW-Configurator 4.3.3
LCT The LCT port is the serial port (RS-232) that can be used to communicate with a PC executing NEW-NMS. In this sheet the baud rate of the LCT port can be changed. WARNING! If you are communicating with the NE through the LCT (Serial) port and you change the LCT baud rate you will loose contact with the NE until you configure the NEW-NMS communication settings to the same baud rate as the NE baud rate. The Communication Ports configuration sheet can be opened from the Configuration context menu of the Equipment node in the Explorer view. Press the LCT tab to view/change the LCT settings. The sheet can also be invoked by selecting (highlighting) the Equipment node in the Explorer view and then selecting Edit Communication Ports from the Configuration menu.
Figure VII-29 LCT Tab in Communication Ports Configuration Sheet
B4008 Rev. M
Fields:
Choices:
Description:
Baudrate:
1200 - 115200
Baudrate. The default baudrate is 115200.
193
CityLink 4.3.4
Ethernet In the CityLink Radio the Ethernet port can be Enabled only if the NI 2 port is Disabled, and vice versa. See chapter 4.3.2. The Communication Ports configuration sheet can be opened from the Configuration context menu of the Equipment node in the Explorer view. Press the Ethernet tab to view/change the Ethernet settings. The sheet can also be invoked by selecting (highlighting) the Equipment node in the Explorer view and then selecting Edit Communication Ports from the Configuration menu.
Figure VII-30 Ethernet Tab in Communication Ports Configuration Sheet
194
Fields:
Choices:
Enabled Stack
Description:
Toggles Ethernet on/off OSI TP4 OSI Stack TCP/IP TCP/IP Stack. Must be selected if IP Tunneling is enabled.
B4008 Rev. M
Configuration with NEW-Configurator 4.3.5
IP Settings The IP Settings sheet lets you view the IP address of the NE and configure the subnet mask and default gateway. The IP address can be set in the Element Id property sheet. The Communication Ports configuration sheet can be opened from the Configuration context menu of the Equipment node in the Explorer view. Press the IP Settings tab to view/change the NI settings. The sheet can also be invoked by selecting (highlighting) the Equipment node in the Explorer view and then selecting Edit Communication Ports from the Configuration menu.
Figure VII-31 IP Settings Tab in Communication Ports Configuration Sheet
Fields:
Description:
IP address Subnet mask
Shows the Internet Protocol (IP) address of the NE. Type the Subnet Mask number obtained from your network administrator. This number, combined with the IP address, identifies which network your NE is on. For each adapter, type the correct IP address of the default gateway used for forwarding packets to other networks or subnets. This address should be provided by the network administrator and is required for nodes on internetworks. If this is not provided, IP functionality will be limited to the local subnet unless a route is specified with the TCP/IP route command.
Default gateway
B4008 Rev. M
195
CityLink 4.3.6
IP Tunneling A connection can be set up between two NEs through another network, using the Internet Protocol. This is called IP Tunneling. Two connections, IP Tunnel 1 and IP Tunnel 2, can be configured. Ethernet must be enabled with TCP/IP Stack in order to use IP tunnels. Internet Protocol (IP)address, Section address and NE address are used for set up of IP tunnels to other NEs. The IP tunnel must only be set up at one side of the tunnel. The Communication Ports configuration sheet can be opened from the Configuration context menu of the Equipment node in the Explorer view. Press the IP Tunneling tab to view/change the IP Tunneling settings. The sheet can also be invoked by selecting (highlighting) the Equipment node in the Explorer view and then selecting Edit Communication Ports from the Configuration menu.
Figure VII-32 IP Tunneling Tab in Comm. Ports Configuration Sheet
Fields:
Choices: Description:
Enabled On/Off Toggles IP Tunneling on/off. Remote section address The section address of the NE addressed through the IP tunnel. Remote NE address The NE address of the NE addressed through the IP tunnel. Remote IP address The Internet Protocol (IP) address of the NE addressed through the IP tunnel. 196
B4008 Rev. M
Configuration with NEW-Configurator 4.3.7
OSI TP4 Tunneling A connection can be set up between two NEs through another network, using the OSI protocol. This is called OSI Tunneling. Two connections, OSI TP4 Tunnel 1 and OSI TP4 Tunnel 2, can be configured. Ethernet must be enabled with OSI Stack in order to use OSI TP4 Tunneling. Network Service Access Point (NSAP)- address, Section address and NE address are used for set up of IP tunnels to other NEs. The Communication Ports configuration sheet can be opened from the Configuration context menu of the Equipment node in the Explorer view. Press the OSI TP4 Tunneling tab to view/change the OSI TP4 Tunneling settings. The sheet can also be invoked by selecting (highlighting) the Equipment node in the Explorer view and then selecting Edit Communication Ports from the Configuration menu.
Figure VII-33 OSI TP4 Tunneling Tab in Comm. Ports Configuration Sheet
Fields:
Choices: Description:
Enabled: On/Off Remote section address: Remote NE address: Remote NSAP address: B4008 Rev. M
Toggles OSI Tunneling on/off Shows the section address of the NE addressed though OSI TP4 Tunnel Shows the SU address of the NE addressed though OSI TP4 Tunnel 0 to 20 bytes 197
CityLink 4.4
Looping The loop settings are divided into five categories: Main traffic looping, 2Mbit/s Wayside traffic looping, 64kbit/s looping, 21x2Mbit/s looping and DS3/E3 looping.
4.4.1
Main Looping The Looping configuration sheet can be opened from the Configuration context menu of the Equipment node in the Explorer view. Press the Main tab to view/change the Main looping settings. The sheet can also be invoked by selecting (highlighting) the Equipment node in the Explorer view and then selecting Edit Looping from the Configuration menu.
Figure VII-34 Looping Configuration Sheet
198
B4008 Rev. M
Configuration with NEW-Configurator Fields:
Description:
Loop buttons:
One button for each loop where the arrow indicates which way the signal is looped. The colour of the loop arrows describes the status of the loop: Blue: The status of the loop is unknown. Loop information has not been retrieved from the NE, or a loop message has just been sent to the NE and the GUI (Graphical User Interface) is waiting for a response from the NE. (The loop settings have not been confirmed by the NE). Note that the loop cannot be toggled when the status is unknown. Black: The loop is off (inactive) Red: The loop is on (active) Displays the time of which all main traffic loops in the NE will be cleared. This time is set by the user when activating a loop.
Loops will be automatically cleared after:
The different main traffic loops (from left to right in Figure 34): • 4. SORP, LT output to LR input loop, far-end (IDU) • 1. SORP LR output to LT input loop, near-end (IDU) • 14. IF loop, near-end (IDU) • 15. IF loop, near-end (ODU) • 16. RF loop, near-end (ODU)
Buttons: Close: Closes the property sheet. Help: Press this button to get help on the current property sheet page. For help on an item, click at the top of the dialog box, then click the item.
B4008 Rev. M
199
CityLink 4.4.2
64 Kbit/s Looping The Looping configuration sheet can be opened from the Configuration context menu of the Equipment node in the Explorer view. Press the 64 Kbit/s Looping tab to view/change the looping settings. The sheet can also be invoked by selecting the Equipment node in the Explorer view and then selecting Edit Looping from the Configuration menu.
Figure VII-35 Looping Configuration Sheet. 64kbit/s Tab
200
B4008 Rev. M
Configuration with NEW-Configurator Fields: Loop buttons: One button for each loop where the arrow indicates which way the signal is looped. The colour of the loop arrows describes the status of the loop: • Blue: The status of the loop is unknown. Loop information has yet not been retrieved from the NE, or a loop message has just been sent to the NE and the GUI is waiting for a response from the NE. (The loop settings have not yet been confirmed by the NE). Note that the loop cannot be toggled when the status is unknown. • Black: The loop is off (inactive) • Red: The loop is on (active) • Grey: The corresponding 64kbit/s channel is not enabled. The different 64Kbit/s loops: (Figure VII-35 describes the loops) • 40. 64Kbit/s G.703 (near end) • 41. 64Kbit/s G.703 (far end) • 42. 64Kbit/s V.11 (near end) • 43. 64Kbit/s V.11 (far end)
Buttons: Close: Closes the property sheet. Help: Press this button to get help on the current property sheet page. For help on an item, click at the top of the dialog box, then click the item.
B4008 Rev. M
201
CityLink 4.4.3
2 Mbit/s Wayside Looping The Looping configuration sheet can be opened from the Configuration context menu of the Equipment node in the Explorer view. Press the 2 Mbit/s Wayside tab to view/change the looping settings. The sheet can also be invoked by selecting (highlighting) the Equipment node in the Explorer view and then selecting Edit Looping from the Configuration menu.
Figure VII-36 Looping Configuration Sheet, Wayside Tab
202
B4008 Rev. M
Configuration with NEW-Configurator Fields: Loop buttons: One button for each loop where the arrow indicates which way the signal is looped. The colour of the loop arrows describes the status of the loop: • Blue: The status of the loop is unknown. Loop information has yet not been retrieved from the NE, or a loop message has just been sent to the NE and the GUI is waiting for a response from the NE. (The loop settings have not yet been confirmed by the NE). Note that the loop cannot be toggled when the status is unknown. • Black: The loop is off (inactive) • Red: The loop is on (active) • Grey: The corresponding 2Mbit/s channel is not enabled. The different wayside loops: (Figure VII-36 describes the loops) • 30. Wayside near end loop. • 32. Wayside far end loop.
B4008 Rev. M
203
CityLink PRBS Settings: PRBS Generator:
PRBS Check:
Generates a PRBS signal that can be inserted into the transmit direction of the wayside channel. Arrow buttons: Press a button to insert the PRBS signal from the generator to the wayside channel. There is one button for normal PRBS insert and one button for inverted PRBS insert. Red=enabled, black=disabled, blue=unknown status, grey=wayside disabled. Counts PRBS errors (An error is detected when the signal differs from the expected PRBS signal). Errors can be counted at the receive direction of the wayside channel. Arrow buttons: Press a button to enable the error detection for the desired traffic direction. There is one button for normal PRBS check and one button for inverted PRBS check. Red=enabled, black=disabled, blue=unknown status, grey=wayside disabled. Count: The total number of deviations detected between the received signal and expected PRBS signal. Rate: The number of deviations detected between the received signal and expected PRBS signal per second. Reset button. Resets the cumulative counter. Status: · OK: Error check is valid. · 2Mbit/s Wayside disabled: Wayside channel is not enabled (See the 2Mbit/s Wayside property sheet). · Counter overflow: The error check is not valid because the counter has exceeded its limit (=232) and wrapped around. Sync loss: The error check is not valid due to sync loss on the PRBS sequence.
Buttons: Reset: Close: Help:
204
Resets the PRBS Counter (includes the PRBS Rate) Closes the property sheet. Press this button to get help on the current property sheet page. For help on an item, click at the top of the dialog box, then click the item. B4008 Rev. M
Configuration with NEW-Configurator 4.4.4
21x2Mbit/s Looping (IDU: EMDK42A, 21x2Mbit/s Extension board: 2NCS635A) It is possible to set loops on each individual dropped 2Mbit/s. These loops are further explained later in this chapter. It is only possible to set one kind of loop at the time on a specific 2Mbit/s tributary. The Looping configuration sheet can be opened from the Configuration context menu of the Equipment node in the Explorer view. Press the 21x2Mbit/s tab to view/change the tributary looping settings. The sheet can also be invoked by selecting (highlighting) the Equipment node in the Explorer view and then selecting Edit Looping from the Configuration menu.
Figure VII-37 Looping Configuration Sheet, 21x2Mbit/s Tab
B4008 Rev. M
205
CityLink Fields:
Description:
2Mbit/s
The physical port number on the 21x2Mbit/s tributary board. Loop type The user can select between three different loops. Legal values are: • None • 2Mbit-In → 2Mbit-Out Near End • TMX → DXC Near End • 2Mbit-Out → 2Mbit-In Far End Remaining time This is a status field for the remaining time the loop will be present. When the time has expired, i.e. the loops is switched off, this field will be set to Loop cleared. ON/OFF This column will contain cells that functions as checkboxes. If the user clicks a cell that isn’t checked, a Loop Timer dialog will be launched (see Figure VII38). The user can set the duration of the loop from this dialog. If the Loop type is None for a specific loop item, the user can’t check this loop item’s checkbox. Note: If the user, by means of the Drop or Continue dialog, removes any of the tributaries in the list above, they will automatically be removed from the list! This means that the number of loop items in the list (eight in the figure above) will not be constant, but will be the same as in the Drop or Continue dialog.
Figure VII-38 The Loop Timer Dialog Box
206
B4008 Rev. M
Configuration with NEW-Configurator To change the settings:
.
1 First, double-click the desired cell in the Looping type column. A combobox with the available loops will be shown over the cell. 2 Select a looping type from the combobox’s drop down list. Click anywhere outside the cell in question to apply the setting 3 Click on the ON/OFF checkbox of the loop item in question. A Loop Timer dialog will be launched (see Figure VII-38). 4 In the Loop Timer dialog set the desired expire time for the loop item in question and close this dialog by clicking the OK button. 5 The checkbox of the loop item in question will now have been checked. The Remaining time cell of the loop item in question will be updated every 5th second with the remaining time of the loop. 6 To clear a loop just click the checked checkbox of the loop item in question. Note: Every altered setting to any item in the list will be applied the target immediately.
4.4.5
DS3/E3 Looping The DS3/E3 card includes three PDH ports, each of which supports looping. The card supports Far End Loop, Near End Loop, PRBS insertion and PRBS verification. The loops are available when the PDH Ports on the DS3/E3 card have been configured to add or drop traffic. A PRBS signal can be inserted on all three PDH ports instead of the regular traffic. The incoming PRBS signal can then be checked in order to verify the quality of the communication path. To check the quality of the signal, a PRBS counter is configured to count the errors on one of the PDH Ports in one of the DS3/E3 directions. An error is detected when the signal differs from the expected PRBS signal. The DS3/E3 card has one PRBS generator that can be muxed into either inbound or outbound direction on one or more ports simultaneously. The PRBS generator can be inverted. For E3 the PRBS polynom is 223 - 1 and for DS3 the PRBS polynom is 215 -1. The PRBS checker is available at one of the PDH ports in either inbound or outbound direction and can also check inverted PRBS signals.
B4008 Rev. M
207
CityLink The Looping Configuration Property sheet can be opened from the Configuration context menu of the Equipment node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Equipment node in the Explorer view and then selecting Edit Looping from the Configuration menu .
Figure VII-39
Looping Configuration Sheet, DS3/E3
Property page controls: Loop buttons: One button for each loop where the arrow indicates which way the signal is looped. The colour of the loop arrows describes the status of the loop: Blue: The status of the loop is unknown. Loop information has not been retrieved from the NE, or a loop message has just been sent to the NE and the GUI is waiting for a response from the NE. (The loop settings have not been confirmed by the NE). Note that the loop cannot be toggled when the status is unknown. Black:The loop is off (inactive) Red: The loop is on (active)
208
B4008 Rev. M
Configuration with NEW-Configurator PRBS Generator:
Generates a PRBS signal that can be inserted into one or both directions of the PDH Port. Arrow buttons: Press a button to insert the PRBS signal from the generator to the PDH Port. Red=enabled, black=disabled, blue=unknown status. Inverted: When checked, the generated PRBS signal is inverted.
PRBS Check:
Counts PRBS errors. Errors can be counted on one of the PDH ports in one of the DS3/E3 directions at a time. Arrow buttons: Press a button to enable the error detection for the desired traffic direction. Red=enabled, black= disabled, blue=unknown status. Inverted: When checked, an inverted PRBS signal is expected. Count: The total number of deviations detected between the received signal and expected PRBS signal. Rate: The number of deviations detected between the received signal and expected PRBS signal per second. Reset button: Resets the cumulative counter. Status: • OK: Error check is valid. • Counter overflow: The error check is not valid because the counter has exceeded its limit (=232) and wrapped around. • Sync loss: The error check is not valid due to sync loss on the PRBS sequence.
Message info field: Displays status of data exchange between GUI and NE. Loop status is updated regularly (5 second interval) as long as this property sheet is open.
B4008 Rev. M
209
CityLink 4.5 4.5.1
In Door Unit (IDU) IDU Production Data The IDU production data property sheet shows the production serial numbers and the production and test dates of the IDU. Only an administrator can change the settings. This sheet is also used for calibrating the Optical Line interface. Calibration is only needed when the optical unit is beginning to get old. The IDU Production Data configuration sheet can be opened from the Configuration context menu of the IDU node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the IDU node in the Explorer view and then selecting Edit Production Data from the Configuration menu.
Figure VII-40 IDU Production Data Configuration Sheet
Fields:
Description:
Article code: Serial no: HW revision: MAC address:
The Article Code The Serial number. Hardware revision The Media Access Control address of the NE. The date when the article was produced. The date when the article was tested. The date when the Factory Acceptance Test was found to be satisfactory.
Production date: Test date: FAT date:
210
B4008 Rev. M
Configuration with NEW-Configurator 4.5.2
64 kbit/s Channels Two 64 kbit/s channels can be inserted into the SOH. Each of the 64 kbit/s channel will occupy one byte of the SOH frame. Press the SOH Frame button to select which bytes of the SOH that are used by the 64 kbit/s Channels. One channel is the V.1l. This channel has to be of type V.11 Contra. The other is the G.703 Channel. This channel can be either G.703 Co or G.703 Contra. Both channels can be retrieved from and inserted into the line and radio side independently. The 64 kbit/s Channels configuration sheet can be opened from the Configuration context menu of the IDU node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the IDU node in the Explorer view and then selecting Edit 64 kbit/s Channels from the Configuration menu.
Figure VII-41 64 kbit/s Channels Configuration Sheet
B4008 Rev. M
211
CityLink Fields:
Choices:
Description
Enabled Disabled
Enables the 64 kbit/s Channel. Disables the 64 kbit/s Channel.
Status:
Type:
Choose linecode for 64 kbit/s Channel. V.11 Contra (Channel V.11) G.703 Co (Channel G.703) G.703 Contra (Channel G.703)
Direction: Line Radio
Timeslot:
212
Choose the direction the 64 kbit/s Rx Channel should be extracted from. 64 kbit/s Rx is inserted from line SOH frames. 64 kbit/s Rx is inserted from radio SOH frames. Shows which timeslot in the SOH the 64 kbit/s Rx Channel occupy.
B4008 Rev. M
Configuration with NEW-Configurator 4.5.3
2 Mbit/s Wayside Channel A 2 Mbit/s channel can be inserted in the SOH in either line-direction or radiodirection. The 2 Mbit/s channel will occupy 33 bytes (32 bytes data + 1 byte alignment information) of the SOH. Press the SOH Frame button to view which bytes of the SOH that are used by the 2 Mbit/s Wayside Channel. The 2 Mbit/s channel uses the Rx and Tx connection at the front panel of the IDU. Rx is received data and Tx is sent data. The 2 Mbit/s Wayside configuration sheet can be opened from the Configuration context menu of the IDU node in the Explorer view. The sheet can also be invoked by selecting the IDU node in the Explorer view and then selecting Edit 2 Mbit/s Wayside from the Configuration menu.
Figure VII-42
2 Mbit/s Wayside Channel Configuration Sheet
Fields:
Options: Description:
Status
Enabled Disabled
Direction Line Radio
B4008 Rev. M
Enables the Wayside Channel Disables the Wayside Channel Choose the direction the Wayside Rx channel should be extracted from. The Wayside channel is extracted from line SOH. When the rate is set to DS1, the Line direction is not available. The Wayside channel is extracted from radio SOH.
213
CityLink Rate
E1 DS1 Coding
HDB3 AMI B8ZS Sensitivity
-30dB -36dB Cable Length
Choose the rate of the Wayside channel. This field is only available when the NE supports DS1 Wayside functionality. If not, the rate is assumed to be E1. 2 Mbit/s 1.5 Mbit/s Choose the coding of the Wayside channel. This field is only available when the NE supports DS1 Wayside functionality. If not, the coding is assumed to be of type HDB3. Only available for E1 Only available for DS1 Only available for DS1 This field is only available when the NE is equipped with the DS3/E3 Extension Board and the DS1 rate is selected Only available for DS1 Only available for DS1 This field is only available when the NE is equipped with the DS3/E3 Extension Board and the DS1 rate is selected
133-266 feet 266-399 feet 399-533 feet 533-655 feet -7.5dB CSU -15dB CSU -22dB CSU
Buttons: SOH frame
214
Press this button to view which timeslots in the SOH the Wayside channel occupies.
B4008 Rev. M
Configuration with NEW-Configurator 4.5.4
SOH X-Connect Two 64kbit/s (one SOH timeslot) cross-connections can be set up. The cross-connections bypass the SORP so that the SOH time-slots are sent from the Line receive unit directly to the Radio transmit unit. The SOH X-Connect configuration sheet can be opened from the Configuration context menu of the IDU node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the IDU node in the Explorer view and then selecting Edit X-Connect from the Configuration menu.
Figure VII-43
B4008 Rev. M
SOH X-Connect Configuration Sheet
Fields:
Description:
Enabled/Disabled Line timeslot Radio timeslot
Switches SOH X-Connect on/off The time slot to bypass the SORP. The destination time slot.
215
CityLink 4.5.5
Error Pulse Output For test purposes. The SORP and Viterbi asics give error pulses when they recognize errors. The number of error pulses per second is a measurement of the quality of the received signals. These error pulses can be sent out on the ALM/AUX port. The Error Pulse Output configuration sheet can be opened from the Configuration context menu of the IDU node in the Explorer view. The sheet can also be invoked by selecting the IDU node in the Explorer view and then selecting Edit Error Pulse Output from the Configuration menu.
216
Figure VII-44
Error Pulse Output Configuration Sheet
Fields:
Choices:
Enabled/Disabled Source
Toggles Error Pulse Output On/Off Only one source at a time. FEC radio The output pin reflects the FEC on the Viterbi asic. B1 line The output pin reflects the B1 on the Line Receive side of the SORP. B2 line The output pin reflects the B2 on the Line Receive side of the SORP. B1 radio The output pin reflects the B1 on the Radio Receive side of the SORP. B2 radio The output pin reflects the B2 on the Radio Receive side of the SORP.
Description:
B4008 Rev. M
Configuration with NEW-Configurator 4.5.6
Auxiliary Output Configuration The auxiliary output function must be enabled in the Available Functions property sheet (see Chapter 2.2, this Section) to use the function. There are four configurable auxiliary output pins in the ALM/AUX port. The pins are connected to a relay, which can either be controlled manually, or triggered automatically on a user selectable set of alarms. The Auxiliary Output Configuration sheet can be opened from the Configuration context menu of the IDU node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the IDU node in the Explorer view and then selecting Edit Auxiliary Output from the Configuration menu.
Figure VII-45
B4008 Rev. M
Auxiliary Output Configuration Sheet
Controls:
Choices:
Description:
Output control radio buttons
Manual Control or Alarm Trigger
Manual relay status radio buttons
Closed or Open
Set the usage of the aux.output pin. (This will be disabled if the CityLink does not support alarm triggers.) If the aux. output is set to manual control, these buttons will be enabled, and can be used to manually control the state of the relay. 217
CityLink Controls:
Choices:
Equipment tree
Alarm trigger list
Add alarm button
Remove alarm button
Alarm triggered radio buttons
Closed or Open
Description: Displays and selects the alarms available for alarm triggers. This will be disabled if the aux. output is set to manual control. Displays the alarm triggers configured. This will be disabled if the aux. output is set to manual control. Adds the currently selected alarm in the equipment tree to the alarm trigger list. If there is no selection, or if the selected tree node doesn’t correspond to an alarm, nothing happens. Disabled if the output is on manual control. Removes the currently selected alarm from the alarm trigger list. Disabled if the output is on manual control. If the aux. output is set to alarm triggered control, these buttons will be enabled, and can be used to control the state of the relay when the alarm conditions are raised.
Buttons: Get:
Press this button to retrieve the current settings from the NE. (The settings are automatically retrieved from the NE when the dialog box is opened). Set: Press this button to update the element with any changes made to any of the Auxiliary Output pages in the dialog box. Close: Closes the dialog box. Help: Press this button to get help on the current property sheet. For help on an item, click at the top of the dialog box, then click the item.
218
B4008 Rev. M
Configuration with NEW-Configurator 4.5.7
Diagnose The Diagnose function retrieves data about memory, boot errors and warnings, boot version and number of resets of the SU of the NE. Press Get to retrieve the data from the NE. The diagnose tests are performed at IDU reset. (Note that the Viterbi decoder and SORP1 are only tested at cold reset) The Diagnose configuration sheet can be opened from the Configuration context menu of the IDU node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the IDU node in the Explorer view and then selecting Edit Diagnose from the Configuration menu.
Figure VII-46
Module
Diagnose Configuration Sheet
Status
Comments
CPLD
OK/Not OK A write/read test sequence was performed at last reset/startup. RTC OK/Low bat/ A write/read test sequence was performed Not running at last reset/startup. LCD OK/Not OK A write/read test sequence was performed at last reset/startup. DRAM OK/Not OK A write/read test sequence was performed at last reset/startup. SRAM OK/Not OK A write/read test sequence was performed at last reset/startup. Code FLASH OK/Not OK A write/read test sequence was performed at last reset/startup. Boot FLASH OK/Not OK A write/read test sequence was performed at last reset/startup. Viterbi Decoder OK/Not OK A write/read test sequence was performed at last startup. SORP OK/Not OK A write/read test sequence was performed at last startup. B4008 Rev. M
219
CityLink 4.5.8
Self Test The Self Test function uses a two step procedure for testing the IDU. The first test sets a CMI loop, while the second test sets an IF loop. For both loops, a PRBS is created in the SORP and errors are counted and synchronization losses are registered as the signal returns from the loops. Press Test to start the Self Test. WARNING! When performing a Self Test the STM-1 traffic will be destroyed. The Self Test dialog box can be opened from the Configuration context menu of the IDU node in the Explorer view. The dialog box can also be invoked by selecting (highlighting) the IDU node in the Explorer view and then selecting Edit Self Test from the Configuration menu.
Figure VII-47
4.5.9
Selt Test Dialog Box
BER Thresholds The Viterbi decoder is a component using a Viterbi low complexity algorithm for decoding/error correcting the received bit-sequence in the NE. The Viterbi error rate is used as a quality measurement for the radio hop. When the Viterbi error rate exceeds certain values, alarms are generated. The threshold values decide when alarms are generated. The threshold values can be changed by the user. Alarm Id HBER LBER EW-BER
220
Default value Indicator for BER > 1e-3 Indicator for LBER > 1e-6 Indicator for EW-BER > 1e-10
Alarm severity MAJOR MINOR WARNING B4008 Rev. M
Configuration with NEW-Configurator Internal proportions: HBER > LBER > EW The BER Threshold configuration sheet can be opened from the Configuration context menu of the Radio node under the IDU node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Radio node under the IDU node in the Explorer view and then selecting Edit BER Threshold from the Configuration menu.
Figure VII-48
BER Threshold Configuration Sheet
Fields: Choices:
Description:
HBER
Error bit rate A Major alarm is generated when the Viterbi error rate exceeds the HBER threshold value. AIS is inserted when the HBER threshold value is exceeded. Error bit rate A Minor alarm is generated when the Viterbi error rate exceeds the LBER threshold value. Error bit rate. A Warning is generated when the Viterbi error rate exceeds the Error Warning threshold value.
1.0·10-3 - 1.0·10-10
LBER 1.0·10-3 - 1.0·10-11
EW
B4008 Rev. M
1.0·10-3 - 1.0·10-12
221
CityLink 4.5.10
OSI Configuration The OSI configuration has to be set to get OSI traffic on your LAN, routed through the Nera network.
4.5.10.1
OSI Line Coding Choose the scheme for the encoding of the binary data stream in the communication channels. The two ends of a communications line must be configured with the same Line Encoding in order to communicate!
Figure VII-49
Fields:
OSI Configuration Sheet, Line Coding Tab
Description:
NI1: The line coding for the NI1 interface. Can be NRZ or NRZI. NI2: The line coding for the NI2 interface. Can be NRZ or NRZI. DCC Line: The line coding for the DCC Line interface. Can be NRZ or NRZI. DCC Radio: The line coding for the DCC Radio interface. Can be NRZ or NRZI.
222
B4008 Rev. M
Configuration with NEW-Configurator 4.5.10.2
OSI Parameters Configure the OSI parameters for the different communication channels. To enable OSI for the different channels, do this at the appropriate Communication ports configuration page. Link state protocol buffer size apply to all channels.
Figure VII-50
B4008 Rev. M
OSI Configuration Sheet, Parameters Tab
223
CityLink Fields:
Subfield:
Description:
NSAP Address
Area ID Host ID End Selector
Subnet address. End system address. Type of service. Always 01.
Link state protocol buffer size Parameters
224
Transmitted buffer length size of IS hello-packets.(512-1492 bytes)
MTU size
Maximum Transmission Unit size. (512-1497 bytes) Default Metric Cost of path. LAPD Role: Client/Server role The two ends of a communications line must be configured with the opposite roles in order to communicate! OSI Enabled This control is checked if OSI is enabled for the respective interface. This is set in the NI or DCC Communication Ports Configuration pages
B4008 Rev. M
Configuration with NEW-Configurator 4.5.10.3
OSI Routing Table This page shows the OSI Routing Table contained in the IDU. The list shows Host Id and Metric for all entries in the table. To get an updated Routing Table, press the Get Button.
Figure VII-51
B4008 Rev. M
OSI Configuration Sheet, Routing Table Tab
Fields:
Description:
Host Id Metric
End system address. Cost of path.
225
CityLink 4.5.10.4
OSI Interface Information There will be one line in the table for each channel enabled for OSI.
226
Figure VII-52
OSI Configuration Sheet, Interface Information Tab
Fields:
Description:
Id InterfaceName Media Status MTU Size
Numbering of interfaces in the network Network user Type of media Indication of connection status (Up or Down) Maximum transmission unit size
B4008 Rev. M
Configuration with NEW-Configurator 4.5.11
Laser Control The optical port may or may not have implemented Automatic Laser Shutdown (ALS). This is a function designed for eye safety purposes, according to ITU-T rec. G.958. When implemented, ALS may be enabled or disabled. When ALS is not implemented or enabled the laser must be turned on/off manually. When ALS is enabled, the laser automatically will restart after a waiting time period (selectable), when having previously been turned off. (If the section of operation is not connected or Loss Of Optical Signal from far end is detected, the laser will again be turned off after 2 sec.) The waiting period is by default set to 1 minute. The Laser Control configuration sheet can be opened from the Configuration context menu of the Optical Line node under the IDU node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Optical Line node under the IDU node in the Explorer view and then selecting Edit Laser Control from the Configuration menu.
Figure VII-503
B4008 Rev. M
Laser Control Configuration Sheet
227
CityLink Fields:
Buttons:
Description:
ALS: Enabled/Disabled Waiting Time
Toggles ALS On/Off (1.0 - 5.0 minutes ) Specifies waiting time before the laser is turned on. If section of operation is connected and optical signal from far end is present, laser will remain on, if not laser will be turned off after 2 seconds. Get Retrieves Laser Control settings from the NE. Set Sends Laser Control settings to the NE. Restart (2 Seconds) Manually restart the laser for 2 seconds. Restart (90 Seconds) Manually restart the laser for 90 seconds for testing purposes. Manual Control: On Off Status:
228
(ALS disabled or not implemented) Manually turn the laser on. Manually turn the laser off. Shows the status of the Laser Unit.
B4008 Rev. M
Configuration with NEW-Configurator 4.5.12
IDU Replace Unit Wizard The Replace Unit Wizard simplifies the process of replacing an IDU. The wizard copies configuration data from “old” IDU to the “new” IDU.
Note: • The NEW program must be directly connected to the LCT port on the IDU (serial communication). • The “old” NEs configuration data is copied to the “new” IDU, including Element ID. Thus the addresses of the “new” IDU become equal to the addresses of the “old” IDU. • Available Functions data is not copied. The “new” IDU may have other optional functions available than the “old” IDU. The wizard describes each step in the replacement process.
Figure VII-54
B4008 Rev. M
The IDU Replace Unit Wizard
229
CityLink 4.6
Out Door Unit (ODU)
4.6.1
Type I ODU
4.6.1.1
Frequency Settings The Duplex Distance between the Rx and Tx band is fixed. The user can set the Tx frequency by clicking on the frequency slots. Since the duplex distance is fixed the Rx frequency will be automatically set. The corresponding Tx and Rx frequency must be set in the opposite NE. Note! Dual Frequency - Single Polarisation (DF-SP) requires two channels in order to transmit 2xSTM-1. With this configuration, adjacent channels can not be used. NEW NMS/Configurator receives the frequency plan from the NE. When no NE is connected (off-line), no frequency plan will be shown. The output power is automatically muted when the frequency setting is executed. The Frequency configuration sheet can be opened from the Configuration context menu of the ODU node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the ODU node in the Explorer view and then selecting Edit Frequency from the Configuration menu.
Figure VII-55
230
Frequency Configuration Sheet
B4008 Rev. M
Configuration with NEW-Configurator Fields:
Description:
Frequency plan Coding
Select the desired frequency plan. The frequency plan must correspond to your transceiver. The coding function used in the modulator/ demodulator. These coding functions may be selectable depending on frequency plan: TCM (Trellis coded modulation) and TCM + RS (Trellis coded modulation and Reed Solomon). Modulation The modulation scheme used with this frequency plan Data Rate The data rate(s) supported by this frequency plan. The available data rates may also be dependent on radio type, radio software version and coding. Channel Spacing (MHz) The distance between the channels in this frequency plan Duplex Distance (MHz) The distance between the TX and the RX carrier frequency. Innermost Spacing (MHz)The distance between the highest selectable freqquency in the lower half of the plan and the lowest selectable frequency in the upper half og the plan. TX Frequency (GHz) The used TX Carrier frequency RX Frequency (GHz) The used RX Carrier frequency TX (min) (GHz) TX Lower sideband frequency for this frequency plan TX(max)(GHz) TX Upper sideband frequency for this frequency plan RX(min)(GHz) RX Lower sideband frequency for this frequency plan RX(max)(GHz) RX Upper sideband frequency for this frequency plan
• To change the settings:
1. Get the current settings from the Network element by pressing Get. (The settings are automatically retrieved from the NE when the property-sheet is opened) 2. Alter the settings by clicking the frequency band you want to transmit your TX data. The RX frequency is automatically updated since the duplex Distance is fixed. 3. Press Set to send the changes to the NE.
B4008 Rev. M
231
CityLink 4.6.1.2
ODU Transceiver - Power Configuration The Transceiver Power Configuration sheet lets the user set some Output Power settings, some RF Input warning thresholds and ATPC settings. ATPC (Automatic Transceiver Power Control) is a function for effectively reducing the interference probability in your network. The output power from the transceiver is automatic controlled. If the regulation loop for the ATPC stops functioning, an alarm is generated. This alarm can be delayed. The output power is automatically muted when the frequency setting is executed. The Power configuration sheet can be opened from the Configuration context menu of the ODU node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the ODU node in the Explorer view and then selecting Edit Power from the Configuration menu.
Figure VII-56
232
Power Configuration Sheet
B4008 Rev. M
Configuration with NEW-Configurator Fields:
Denomination: Description:
RF input level warning, high
dBm
The upper threshold value for when to generate an RF input level warning (Alarm no. 1504)
RF input level warning, low
dBm
The lower threshold value for when to generate an RF input level warning (Alarm no. 1504)
ATPC alarm level
dBm
Set the power level to use when an ATPC alarm occurs.
ATPC reference level
dBm
The wanted input level when ATPC is activated.
Mute output power Maximum output power
dBm
Maximum output power for transmitting
Manual output level
dBm
The output power level used when ATPC is not activated
ATPC status
ATPC Disabled/ Enabled
ATPC mode
ATPC can operate in four different modes: Automatic Regulation: The transceiver automatically regulates the transmitter power Minimum Output: A min. amount of power is used for transmitting. Maximum Output: A max. amount of power is used for transmitting. Freeze Output Power: A fixed amount of power is used for transmitting.
ATPC alarm delay
B4008 Rev. M
Mutes the output power. No output power is sent.
Seconds
The ATPC alarm can be delayed from 1 to 15 seconds.
233
CityLink 4.6.1.3
ODU Production Data The ODU production data property sheet shows the production serial numbers and the production and test dates of the ODU. Only an administrator can change the settings. The ODU Production Data configuration sheet can be opened from the Configuration context menu of the ODU node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the ODU node in the Explorer view and then selecting Edit Production Data from the Configuration menu.
Figure VII-57
Fields:
Description:
Article code: Serial no: HW revision: Sales order: Production date: Test date: FAT date:
The article code The serial number. Hardware revision The purchase order. The date when the article was produced. The date when the article was tested. The date when the Factory Acceptance Test was found to be satisfactory. The date when the Site Acceptance Test was found to be satisfactory.
SAT date: 234
ODU Production Data Configuration Sheet
B4008 Rev. M
Configuration with NEW-Configurator 4.6.2
Type II ODU
4.6.2.1
RF Power The XCVR Unit provides a set of RF power control functions: • RF input alarm thresholds can be set such that an alarm is raised when the input level exceeds the upper or lower limits. • ATPC (Automatic Transmitter Power Control) is a function for effectively reducing the interference probability in the network. When ATPC is enabled, the output power from the transmitter is automatically controlled according the received input power on the other side of the hop. The ”ATPC” alarm is generated if the ATPC regulation loop fails. This alarm can be optionally delayed. • If ATPC is not enabled, the transmitted output level can be set. The transmitter can also be muted. The RF Power property sheet is used to display/configure the RF Power control settings.
Figure VII-58
B4008 Rev. M
RF Power Configuration Sheet
235
CityLink Fields: Mute output power: When checked the output power is muted. Maximum output level (dBm): The transmitter’s maximum output power. Manual Transmit Output Power (MTPC): ATPC is disabled. Constant manual output level is used. Automatic Transmit Output Power (ATPC): ATPC is enabled. Output level is automatically adjusted using the specified ATPC settings. Alarm Thresholds: • RF-INPUT-WARNING, high (dBm): If the RF input level exceeds this value the ”RF-INPUT-WARNING” alarm is raised. • RF-INPUT-WARNING, low (dBm): If the RF input level goes below this value the ”RF-INPUT-WARNING” alarm is raised. MTPC: • Manual output level (dBm): The output power used when ATPC is disabled. ATPC: • Reference input level (dBm): The desired input level. If ATPC is enabled on the transmitter across the hop, that transmitter will regulate its output power such that the received input level at this receiver is equal to the reference level. • Default output level (dBm): The output power to be used if the ATPC regulation loop fails. (The ”ATPC” alarm is raised). • Alarm delay (s): The delay (in seconds) before the ATPC alarm is raised after the ATPC regulation loop fails. Message info field: Displays status of data exchange between GUI and NE.
236
B4008 Rev. M
Configuration with NEW-Configurator 4.6.2.2
Frequency Settings The Frequency property sheet displays the frequency settings for the transceiver unit. Available frequency plans and their parameters are stored in a table in the NEW-NMS database. If the wanted frequency plan cannot be found in the combo box, please contact Nera for upgrading the database table. When frequency data is retrieved from the NE, the data are matched against frequency plans stored in your database system. If a match is found the appropriate frequency plan is selected, otherwise a frequency plan can be selected from the combo box. To change the frequencies: 1. Select a frequency plan from the combo box. 2. Select a TX frequency by pressing a button in the frequency plan. The RX frequency will be calculated from TX frequency and the duplex distance. 3. Send the new settings to the NE. (Press the Set button in the property sheet). A message box will be displayed asking whether to apply the contrary frequencies to the other side of the hop (if the remote NE is present in NEW).
Figure VII-59
B4008 Rev. M
Frequency Configuration Sheet
237
CityLink Fields: Frequency Plan: • Selected plan: The currently selected frequency plan. The graphical presentation of the plan contains channel buttons that can be used to set the TX and RX frequencies for the selected channel in the list. • Modulation: modulation method: 32TCM, 64TCM or 128 TCM. • Channel spacing: The distance in MHz between two consecutive channels. • Data rate: STM-1 or STM-0. Current Setting: • TX frequency (GHz): The Transmitter frequency. • RX frequency (GHz): The Receiver frequency. Transceiver limits: The frequency band limits of the transceiver. Status: Frequency status: • OK: Frequency settings are OK. • Frequency shifting: The frequencies are changed on both sides of the hop. If no connection is established within 10 seconds the frequencies will be reverted. Message info field: Displays status of data exchange between GUI and NE.
238
B4008 Rev. M
Configuration with NEW-Configurator 4.6.2.3
DRO Tuning The XCVR Unit’s DRO Tuning property sheet is used to enable and disable DRO Tuning mode for the individual XCVR unit. The tuning of the DRO frequency is performed manually on the XCVR unit. See Chapter 4.6.2.2.
Disabled Tx tuning Rx tuning
Figure VII-60
Fields: DRO Tuning Mode: • Disabled: • TX Tuning: • RX Tuning: Status TX: Status RX:
B4008 Rev. M
DRO Tuning Configuration Sheet
Description: DRO Tuning mode is disabled for both DRO’s Enables DRO Tuning mode for TX DRO Enables DRO Tuning mode for RX DRO Displays information concerning frequency lock and screw direction for TX DRO Displays information concerning frequency lock and screw direction for RX DRO
239
CityLink 4.6.2.3
DRO Tuning Procedure
Tx Tuning
Rx Tuning
Figure VII-61
240
DRO Tuning Procedure
B4008 Rev. M
Configuration with NEW-Configurator 4.6.2.3.1
Frequency Setting Highlight the actual Transceiver unit to be tuned. Right click and choose Configuration and Frequency.
Transceiver Unit Ch1
Figure VII-62 Selecting in Explorer View the Transceiver to be tuned
Figure VII-63
Frequency Configuration Sheet
See Chapter 4.6.2.2 for setting of frequency.
B4008 Rev. M
241
CityLink 4.6.2.3.2
DRO Tuning Highlight the actual Transceiver unit to be tuned. Right click and choose Configuration and DRO Tuning
Figure VII-64
Selecting DRO tuning from the Explorer View
Tx tuning
Disabled Tx tuning Rx tuning
Figure VII-65
DRO Tuning Configuration Sheet
Select Tx tuning in the DRO Tuning Mode field. Press the Set button. 242
B4008 Rev. M
Configuration with NEW-Configurator
Figure VII-66
DRO Tuning Configuration Sheet, Tx tuning
The red arrow indicates which way to adjust the DRO. In addition, the Alarm LED on the front of the Transceiver will blink when the DRO must be turned clockwise. If the Alarm LED is OFF, the DRO must be turned counter-clockwise. When the Alarm LED is ON, the Synthesizer is in lock. Press the Set button to update the window.
B4008 Rev. M
243
CityLink Rx Tuning
Disabled Tx tuning Rx tuning
Figure VII-67
DRO Tuning Configuration Sheet
Select Rx tuning in the DRO Tuning Mode field. Press the Set button.
244
B4008 Rev. M
Configuration with NEW-Configurator
Figure VII-68
DRO Tuning Configuration Sheet, Rx tuning
The red arrow indicates which way to adjust the DRO. In addition, the Alarm LED on front of the Transceiver will blink when the DRO must be turned clockwise. If the Alarm LED is OFF, the DRO must be turned counter-clockwise. When the Alarm LED is ON the Synthesizer is in lock. Press the Set button to update the window.
B4008 Rev. M
245
CityLink 4.6.2.4
Production Data The different boards/units contain some production information. This information is displayed in the Production Data property sheet.
Figure VII-69
Fields:
Production Data Configuration Sheet
Description:
Article code: Serial no.: HW revision: Production date:
Uniquely identifies the type of board/unit. The serial number of the board/unit. The hardware revision. When the production process was completed for this board/unit. Test date: When this product was tested by the factory testdepartment. Message info field: Displays status of data exchange between GUI and NE.
246
B4008 Rev. M
Configuration with NEW-Configurator 4.6.3
Type III ODU
4.6.3.1
RF Power The XCVR Unit provides a set of RF power control functions: • RF input alarm thresholds can be set such that an alarm is raised when the input level exceeds the upper or lower limits. • ATPC (Automatic Transmitter Power Control) is a function for effectively reducing the interference probability in the network. When ATPC is enabled, the output power from the transmitter is automatically controlled according the received input power on the other side of the hop. The ”ATPC” alarm is generated if the ATPC regulation loop fails. This alarm can be optionally delayed. • If ATPC is not enabled, the transmitted output level can be set. The transmitter can also be muted. The RF Power property sheet is used to display/configure the RF Power control settings.
Figure VII-70
B4008 Rev. M
Power Configuration Sheet
247
CityLink Fields: Mute output power: When checked the output power is muted. Maximum output level (dBm): The transmitter’s maximum output power. Manual Transmit Output Power (MTPC): ATPC is disabled. Constant manual output level is used. Automatic Transmit Output Power (ATPC): ATPC is enabled. Output level is automatically adjusted using the specified ATPC settings. Alarm Thresholds: • RF-INPUT-WARNING, high (dBm): If the RF input level exceeds this value the ”RF-INPUT-WARNING” alarm is raised. • RF-INPUT-WARNING, low (dBm): If the RF input level goes below this value the ”RF-INPUT-WARNING” alarm is raised. MTPC: • Manual output level (dBm): The output power used when ATPC is disabled. ATPC: • Reference input level (dBm): The desired input level. If ATPC is enabled on the transmitter across the hop, that transmitter will regulate its output power such that the received input level at this receiver is equal to the reference level. • Default output level (dBm): The output power to be used if the ATPC regulation loop fails. (The ”ATPC” alarm is raised). • Alarm delay (s): The delay (in seconds) before the ATPC alarm is raised after the ATPC regulation loop fails. Message info field: Displays status of data exchange between GUI and NE.
248
B4008 Rev. M
Configuration with NEW-Configurator 4.6.3.2
Frequency Settings The Frequency property sheet displays the frequency settings for the transceiver unit. Available frequency plans and their parameters are stored in a table in the NEW-NMS database. If the wanted frequency plan cannot be found in the combo box, please contact Nera for upgrading the database table. When frequency data is retrieved from the NE, the data are matched against frequency plans stored in your database system. If a match is found the appropriate frequency plan is selected, otherwise a frequency plan can be selected from the combo box. To change the frequencies: 1. Select a frequency plan from the combo box. 2. Select a TX frequency by pressing a button in the frequency plan. The RX frequency will be calculated from TX frequency and the duplex distance. 3. Send the new settings to the NE. (Press the Set button in the property sheet). A message box will be displayed asking whether to apply the contrary frequencies to the other side of the hop (if the remote NE is present in NEW).
Figure VII-71
B4008 Rev. M
Frequency Configuration Sheet
249
CityLink Fields: Frequency Plan: • Selected plan: The currently selected frequency plan. The graphical presentation of the plan contains channel buttons that can be used to set the TX and RX frequencies for the selected channel in the list. • Modulation: modulation method: 32TCM or 128 TCM. • Channel spacing: The distance in MHz between two consecutive channels. • Data rate: STM-1 or STM-0. Current Setting: • TX frequency (GHz): The Transmitter frequency. • RX frequency (GHz): The Receiver frequency. Transceiver limits: The frequency band limits of the transceiver. Status: Frequency status: • OK: Frequency settings are OK. • Frequency shifting: The frequencies are changed on both sides of the hop. If no connection is established within 10 seconds the frequencies will be reverted. Message info field: Displays status of data exchange between GUI and NE.
250
B4008 Rev. M
Configuration with NEW-Configurator 4.6.3.3
Production Data The ODU production data property sheet shows the production serial numbers and the production and test dates of the ODU. Only an administrator can change the settings. The ODU Production Data configuration sheet can be opened from the Configuration context menu of the ODU node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the ODU node in the Explorer view and then selecting Edit Production Data from the Configuration menu.
Figure VII-72
Fields:
Description:
Article code: Serial no: HW revision: Sales order: Production date: Test date: FAT date:
The article code The serial number. Hardware revision The purchase order. The date when the article was produced. The date when the article was tested. The date when the Factory Acceptance Test was found to be satisfactory. The date when the Site Acceptance Test was found to be satisfactory.
SAT date: B4008 Rev. M
Production Data Configuration Sheet
251
CityLink 4.6.4
Antenna Data This sheet shows some main characteristics of the antenna. Only the Antenna code can be altered. The antenna data are stored in a database file. The Antenna Data configuration sheet can be opened from the Configuration context menu of the Antenna node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Antenna node in the Explorer view and then selecting Edit Antenna from the Configuration menu.
Figure VII-73
Fields:
Antenna Data Configuration Sheet
Description:
Antenna code Gain
The antenna code. Unique code for each antenna type. The antenna gain (dB). Gain is a measurement of the antenna's ability to transform electrical signals to electromagnetic waves. Diameter The physical antenna diameter. [meter] Polarization The polarization direction of the antenna. Front/Back ratio Front/Back Ratio. Ratio between the gain in forward direction and the gain in backward direction. Frequency range The frequency range where the antenna can be expected to operate successfully. 252
B4008 Rev. M
Configuration with NEW-Configurator 4.6.5
ODU Replace Unit Wizard The Replace Unit Wizard simplifies the process of replacing an ODU. The wizard copies configuration data from “old” ODU to the “new” ODU. The wizard describes each step in the replacement process.
Figure VII-74
B4008 Rev. M
The ODU Replace Unit Wizard
253
CityLink
5.0
CityLink ADM
5.1
21x2 Mbit/s Extension Board
5.1.1
Drop or Continue The Drop or Continue sheet is used to drop or remove a 2Mbit/s stream(E1). The 21x2Mbit/s extension board supports 21 physical 2Mbit/s ports. The user can assign any VC-12, out of the 63 available in the STM1 structure, to a specific 2Mbit/s port on this board. From which direction the drop is to be taken must also be configurated. The Drop or Continue configuration sheet can be opened from the Configuration context menu of the 21x2 Extension board node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the 21x2 Extension board node in the Explorer view and then selecting Edit Drop or Continue from the Configuration menu. Note: Even though the 21x2Mbit/s extension board is present in the equipment this dialog will not be shown if the 21x2Mbits/s extension board isn’t enabled. This enabling must be done in the Section Termination dialog which can be opened from the Configuration context menu of the Transmission node in the Explorer view.
Figure VII-75 254
The Drop or Continue Configuration Sheet B4008 Rev. M
Configuration with NEW-Configurator Fields:
Description:
Port Number
The physical port number on the 21x2Mbit/s extension board. VC-12 Number The VC-12 number that the 2Mbit/s PDH stream attached to the Port Number shall be routed to/from (the numbers in the parenthesis is the VC-12 given in KLM notation). It is possible to re-use a given VC-12 as long as the Direction is different. Direction This parmeter indicates which direction the VC-12 is to be routed to/from. It can either be line or radio. Configured Check this to add a drop or uncheck it to remove a drop. If the checkbox is checked a new dialog will be launched. This dialog is used to select the VC-12 Number and the Direction. This dialog is explained in chapter 4.13.1.1. Note1: If the user, by means of the VC-12 Selector Dialog, specifies a VC-12 and a direction that is already in use, the setting will not be applied! Note2: If one attempts to remove a dropped VC-12 that is in use by the clock synchronization in the Section Termination, the removing will be rejected!
Buttons: Clear selected item(s): With the mouse one can select one or several items in the listview. When items are selected, this button will be enabled. Click the button if you wish to uncheck the selected items. Modifications that leads to a mismatch between the dialog settings and the settings on the NE will be tagged with a «dirty» token; *. Get: Click this button to retrieve the current settings from the NE. Any modifications done to the GUI elements will be lost and the «dirty» token will be removed. Set: Click this button to send the settings to the NE. Any modifications done to the GUI elements will be applied the NE and the «dirty» token will be removed. Close: Click this button to close the property sheet. Help: Press this button to get help on the current property sheet. For help on an item, click at the top of the dialog box, then click the item. B4008 Rev. M
255
CityLink 5.1.1.1
VC-12 Selector This dialog is used to select a specific VC-12 from the 63 available in the STM-1 payload. In addition to the VC-12 number, the direction from which the specific VC-12 is routed to/from is also specified. This dialog will be launched immediately after the user has checked an item in the Drop or Continue dialog.
Figure VII-76
The VC-12 Selector Dialog Box
Fields:
Description:
VC-12 # K
The VC-12 number. It must be in the interval [1,63]. The first of the three numbers in the KLM numbering scheme. The number must be in the interval [1,3]. Note that the user can either enter the K number directly or use the up/down buttons to traverse the number range. L The second of the three numbers in the KLM numbering scheme. The number must be in the interval [1,7]. Note that the user can either enter the L number directly or use the up/down buttons to traverse the number range. M The third of the three numbers in the KLM numbering scheme. The number must be in the interval [1,3]. Note that the user can either enter the M number directly or use the up/down buttons to traverse the number range. Drop From Line If selected, the VC-12 will be routed to/from the line interface of the NE. Drop From Radio If selected, the VC-12 will be routed to/from the radio interface of the NE.
256
B4008 Rev. M
Configuration with NEW-Configurator Sub Network SNCP performs path protection switching (called Connection dedicated protection) which manages all traffics by Protection - SNCP a path. Working traffic is transmitted in one direction, and protection traffic in opposite direction around the ring, and traffic is selected at each end of the path. So, SNCP supports multiple rings, and offers suitable solution for access and metro network where hub node terminates most various traffics. SNCP can also transmit signal to only one direction, west or east, and the products can be used as 1+0 Linear ADM mode as well as SNCP mode.
Buttons: OK: Click this button to close the dialog and apply the setting. Cancel: Click this button to close the dialog without applying the setting.
B4008 Rev. M
257
CityLink 5.1.2
PRBS Test - Check The PRBS Test - Check sheet is used to set up which of the dropped 2Mbit/s tributaries that shall check a given PRBS. Only one 2Mbit/s tributary can perform this test at the time. The PRBS Test - Check configuration sheet can be opened from the Configuration context menu of the 21x2 Extension board node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the 21x2 Extension board node in the Explorer view and then selecting Edit PRBS Test from the Configuration menu.
Figure VII-77
258
The PRBS Test Check Configuration Sheet
B4008 Rev. M
Configuration with NEW-Configurator Fields:
Description:
2Mbit/s The physical port number on the 21x2Mbit/s tributary board. Direction Used to set from which Direction the tributary board shall check PRBS. To change the setting, the user must doubleclick the Direction cell in question. When this happens, a combobox will be displayed in the cell and the user can select a new setting for the cell. Inverted If this checkbox is checked, it will be assumed that the received PRBS is inverted. If not checked, it’s assumed to not be inverted. Clear If this checkbox is checked the Count cell will be cleared when Set button is clicked. Check Only one tributary can be set to check PRBS at the time. This means that only one item in the list above can be active at the same time. In the figure above this is item-1. Item-2 through item-8 aren’t active. If e.g. the radio button in item-1 in the figure is clicked (the one that is active), it will be cleared. In this case none of the tributaries will check PRBS. Count This cell will contain the number of error pulses. It’s a 2^16 bits wrap-around counter. If the Status cell is Sync Loss, this counter will not count but instead be set to «—». If the Status cell is No Sync Loss, this counter will count errors. Status The status of the counter. Note: If the user, by means of the Drop or Continue dialog, removes any of the tributaries in the list above, they will automatically be removed from the list!
B4008 Rev. M
259
CityLink 5.1.3
PRBS Test - Generators The PRBS Test - Generators sheet is used to set up which of the dropped 2Mbit/s tributaries that shall generate PRBS. All tributaries can insert PRBS simultaneously. The PRBS Test - Generators configuration sheet can be opened from the Configuration context menu of the 21x2 Extension board node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the 21x2 Extension board node in the Explorer view and then selecting Edit PRBS Test from the Configuration menu.
Figure VII-78
260
The PRBS Test Generators Configuration Sheet
B4008 Rev. M
Configuration with NEW-Configurator Fields:
Description:
2Mbit/s
The physical port number on the 21x2Mbit/s tributary board. Direction Used to set in which Direction the tributary board shall insert a PRBS. To change the setting the user must double click the Direction cell in question. When this happens, a combobox will be displayed in the cell and the user can select a new setting for the cell. Legal values are: • 2Mbit/s • STM-1 • 2Mbit/s & STM-1 • Both off Insert If this checkbox is checked a PRBS will be inserted in the direction(s) specified by Direction. Insert inverted PRBS If this checkbox is checked all checked tributaries in the list will be inserted inverted PRBS. If not checked it’s assumed to not be inverted. Note: If the user, by means of the Drop or Continue dialog, removes any of the tributaries in the list above, they will automatically be removed from the list!
B4008 Rev. M
261
CityLink 5.1.4
Production Data - 21x2Mbit/s Extension board (2NCS635A) Production data for the 21x2Mbit/s extension board, displayed on a separate page in the Production Data configuration sheet. Only an administrator can change the settings. The Production Data configuration sheet can be opened from the Configuration context menu of the IDU- or Switch node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the IDU- or Switch node in the Explorer view and then selecting Edit Production Data from the Configuration menu. Then the production data is located under the Tab named 21x2Mbit/s Extension Board.
262
Fields:
Description:
Article Code Serial no. HW revision Production date Test date
The Article Code of the card/unit. The Serial number of the card/unit. Hardware revision of the card/unit. The date when the article was produced. The date when the article was tested.
B4008 Rev. M
Configuration with NEW-Configurator 5.2
DS3/E3 Extension Board
5.2.1
DS3/E3 Configuration The DS3/E3 functionality allows the operator to connect two Virtual Containers (VC) in different ports. The connections are identified by using the background colour of the ports together with the KLM address of the virtual container. The background colour of a virtual container identifies the source port, while the KLM address identifies the source address. As an example consider the marked VCs in Figure VII-79. The VC on the Line Port is connected with the VC having a KLM address of 1,2,1 on the Radio Port. While the VC on the Radio Port is connected with the VC having a KLM address of 1,1,1 on the Line Port. SNCP functionality is available on the DS3/E3 Port and is identified with a split cell. Traffic Looping is achieved by connecting VCs on the same port and is only available for the line - and radio port. The DS3/E3 port does not support traffic looping, but does however support test looping. DS3/E3 looping is only available on the connected when the port has been configured to add/drop traffic. The DS3/E3 Configuration sheet can be opened from the Configuration context menu of the DS3/E3 Extension Board node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the DS3/E3 Extension Board node in the Explorer view and then selecting Edit DS3/E3 from the Configuration menu .
B4008 Rev. M
263
CityLink
Figure VII-79
DS3/E3 Configuration Sheet
Buttons: SNCP:
Press this button to establish an SNCP connection. The SNCP functionality will apply to the same virtual container on all ports. SNCP is available on the DS3/E3 Port. Source: To establish a connection, select a virtual container from one of the ports. Press this button to set the selected container as the source. Destination: Select a virtual container from one of the ports and press this button to set the selected container as the destination. Disconnect: Select a virtual container which already has an established connection. Press this button to remove the connection. Cancel: Press this button to undo the current operation. Get: Press this button to retrieve the current settings from the NE. (The settings are automatically retrieved from the NE when the dialog box is opened). Set: Press this button to send the settings to the NE. Close: Closes the property sheet. Help: Press this button to get help on the current property sheet. For help on an item, click at the top of the dialog box, then click the item. 264
B4008 Rev. M
Configuration with NEW-Configurator 5.2.2
DS3/E3 Frame Structure Configuration The operator may configure the frame structure on the three ports. Each port consists of three TUG-3’s ( SDH Multiplex Structure). Each TUG-3 contains either a VC-3 structure or a VC-12 structure. The virtual containers on the ports are identified using KLM notation:
Figure VII-80
B4008 Rev. M
Virtual Containers
265
CityLink
Figure VII-81
DS3/E3 Frame Structure Configuration Sheet
Buttons: VC-3: VC-12: Get:
Set: Close: Help:
SDH: SONET:
266
Sets the current structure to VC-3. Sets the current structure to VC-12. Press this button to retrieve the current settings from the NE. (The settings are automatically retrieved from the NE when the dialog box is opened). Press this button to send the settings to the NE. Closes the property sheet. Press this button to get help on the current property sheet. For help on an item, click at the top of the dialog box, then click the item. This button indicates that the transmission standard is set to SDH. This button indicates that the transmission standard is set to SONET.
B4008 Rev. M
Configuration with NEW-Configurator 5.3 5.3.1
ADM STM-1 Extension Board (X-Connect) X-Connect Frame Structure Configuration The operator may configure the frame structure on the three ports. For more info, please refer to Chapter 5.2.2 (this Section) The Frame Structure Configuration property page is available from the Transmission Configuration property sheet. Select “Enable X-Connect” from the “Termination Enabling” combo box in the “Termination and SETS” property page. The Transmission Configuration property sheet can be opened from the Configuration context menu of the transmission node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the transmission node in the Explorer view and then selecting Edit Transmission Configuration from the Configuration menu .
Figure VII-82
Frame Structure Configuration Sheet
Buttons: VC-3: VC-12:
B4008 Rev. M
Sets the current structure to VC-3. Sets the current structure to VC-12.
267
CityLink 5.3.2
X-Connect Configuration The X-connect functionality allows the operator to connect two Virtual Containers (VC) in different ports. The connections are identified by using the background colour of the ports together with the KLM address of the virtual container. The background colour of a VC identifies the source port, while the KLM address identifies the source address. As an example consider the marked VCs in the figure below. The VC on the Line Port is X-connected with the virtual container having a KLM address of 1,2,1 on the Radio Port. While the VC on the Radio Port is X-connected with the VC having a KLM address of 1,1,1 on the Line Port. SNCP functionality is available on the Line Port and is identified with a split cell. Looping is achieved by connecting VCs on the same port (Traffic Looping). The X-Connect Configuration sheet can be opened from the Configuration context menu of the X-Connect Extension Board node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the X-Connect Extension Board node in the Explorer view and then selecting Edit XConnect from the Configuration menu .
Figure VII-83 268
X-Connect Frame Structure Configuration Sheet B4008 Rev. M
Configuration with NEW-Configurator Buttons: SNCP:
Press this button to establish an SNCP connection. The SNCP functionality will apply to the same virtual container on all ports. SNCP is available on the Line Port. Source: To establish a connection, select a virtual container from one of the ports. Press this button to set the selected container as the source. Destination: Select a virtual container from one of the ports and press this button to set the selected container as the destination. Disconnect: Select a virtual container which already has an established connection. Press this button to remove the connection. Cancel: Press this button to undo the current operation.
B4008 Rev. M
269
CityLink
6.0 6.1
Hot Standby General A CityLink Hot Standby system consists of two InDoor Units connected to an IDU Switch and two OutDoor Units connected to the a HSB branching unit. The IDU switch performs switching in the Rx direction, while the branching unit has an RF-switch in the Tx direction.
Figure VII-84
6.1.1
Hot Standby Explorer view
Functionality The IDU switch will perform most of the normal tasks of an IDU, with the two IDUs maintaining modem functionality. Thus, configuration of line inputs, wayside channels etc will be handled on the switch, while modem-specific functionality (e.g Viterbi error pulses) is found on the IDU. Some functionality, like auxiliary outputs, are found in both places.
270
B4008 Rev. M
Configuration with NEW-Configurator 6.1.2
Element ID The CityLink Element ID property sheet shows some main information about the Network Element like name, type, serial number and different addresses. The enabled fields can be altered by users with proper user privileges. The Element ID configuration sheet can be opened from the Configuration context menu of the Element node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Element node in the Explorer view and then selecting Edit Element ID from the Configuration menu.
Figure VII-85 Element ID Configuration Sheet
B4008 Rev. M
271
CityLink Fields:
Description:
Serial number: NE type: Name: Section address: NE address:
The serial number of the NE. (Not editable) The type of NE. (Not editable) The name of the NE (max. 32 characters) The section address of the NE. (1-254) The NE address (1-128). Used for identification of NEs within a section. MAC address: The Media Access Control address of the NE. Used for OSI-Management. (Not editable) NSAP address: The Network Service Access Point address of the NE. Used for OSI-Management. IP address The Internet Protocol address of the NE. 1+1 Hot Standby: Select this option in order to set up a hot standby element. A list of choices are displayed in the droplist; Standard, SD Combiner (Space Diversity Combiner), SD Hybrid (Space Diversity Hybrid) and Dual Antenna. 1+1 Freq. Diversity: Select this option in order to set up a frequency diversity element. A list of choices are displayed in the droplist; Standard, SD Combiner (Space Diversity Combiner) and SD Hybrid (Space Diversity Hybrid)
To change the settings: 1 First, get the current settings from the NE by pressing Get. (The settings are automatically retrieved from the NE when the property-sheet is opened.) 2 Alter the settings you want to change. 3 Press Set to send the changes to the NE.
272
B4008 Rev. M
Configuration with NEW-Configurator 6.1.2
Looping Configuration When opening the Looping Sheet on a HSB NE, the pages for main, wayside and 64Kbit looping will apply for both IDUs. If a loop is set on the IDU and the system switches, the signal will still be looped.
6.1.2.1
HSB Main Looping The Looping configuration sheet can be opened from the Configuration context menu of the Equipment node in the Explorer view. Press the Main tab to view/change the Main looping settings. The sheet can also be invoked by selecting (highlighting) the Equipment node in the Explorer view and then selecting Edit Looping from the Configuration menu.
Figure VII-86
B4008 Rev. M
HSB Looping Configuration Sheet
273
CityLink Fields: Loop buttons:
Loops will be automatically cleared after:
One button for each loop where the arrow indicates which way the signal is looped. The colour of the loop arrows describes the status of the loop: Blue: The status of the loop is unknown. Loop information has not been retrieved from the NE, or a loop message has just been sent to the NE and the GUI is waiting for a response from the NE. (The loop settings have not been confirmed by the NE). Note that the loop cannot be toggled when the status is unknown. Black: The loop is off (inactive) Red: The loop is on (active) Displays the time of which all main traffic loops in the NE will be cleared. This time is set by the user when activating a loop.
The different main traffic loops (from left to right in the respective blocks in Figure 70): • 4S. SORP LT output to LR input loop, far-end (IDU Switch) • 1S. SORP LR output to LT input loop, near-end (IDU Switch) • 12S. SORP RT output to RR input loop, near-end (IDU Switch) • 14A. IF loop, near-end (IDU A) • 15A. IF loop, near-end (ODU A) • 16A. RF loop, near-end (ODU A) • 14B. IF loop, near-end (IDU B) • 15B. IF loop, near-end (ODU B) • 16B. RF loop, near-end (ODU B)
Buttons: Close: Closes the property sheet. Help: Press this button to get help on the current property sheet page. For help on an item, click at the top of the dialog box, then click the item.
6.1.2.2
HSB 64Kbit/s Looping Please refer to Chapter 4.4.2 (this Section).
6.1.2.3
HSB Wayside Looping Please refer to Chapter 4.4.3 (this Section).
274
B4008 Rev. M
Configuration with NEW-Configurator 6.1.3
Hot Standby Configuration The Hot Standby configuration sheet shows the switching configurations for the IDU-Switch. The Hot Standby configuration sheet can be opened from the Configuration context menu of the IDU-Switch node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the IDU-Switch node in the Explorer view and then selecting Edit Hot Standby from the Configuration menu.
Figure VII-87
Fields:
Common Tab in Element ID Configuration Sheet
Description
Auto / manual: Active branch:
Select between automatic or manual hot standby switching Select which branch that should be active. Active branch is available in Manual mode only Switching mode: In Bidirectional mode both Tx and Rx direction switches at the same time. In Unidirectional mode Tx and Rx can switch independent of each other. Switching mode can only be set Automatic mode. In Manual mode, the switching mode is always Bidirectional. Status list: Displays the active branch(es) in the TX and RX directions and whether there are RX/TX alarms in any of the branches.
B4008 Rev. M
275
CityLink 6.1.4
Hot Standby Switching Criteria The Hot Standby Switching Criteria page shows the automatic switching criteria for the hot standby element, and enables the user to alter these criteria. The Hot Standby Switching Criteria page can be opened from the Configuration context menu of the IDU-Switch node in the Explorer view. The Hot Standby configuration sheet then appears, and the switching criteria page can be selected. The sheet can also be invoked by selecting (highlighting) the IDU-Switch node in the Explorer view and then selecting Edit Hot Standby from the Configuration menu. Note that setting switching criteria is only allowed on Citylink 2 Hot Standby elements running with IDU software version R3C or higher. Also, the switching mode set in the Hot Standby Config page must be set to Automatic.
Figure VII-88
Hot Standby Switching Criteria
Field descriptions: The page consists of two lists; one for each branch. Each list contains alarm names/categories and a checkbox for each name/category.
276
B4008 Rev. M
Configuration with NEW-Configurator Switching algorithm The following algorithm is applied in automatic switching mode: Compute the total severity factor of each branch (SA, SB) using the following formula:
SCenabled1is 1 if the switching criteria “RF Input Alarm” is enabled (checked), else it is 0. SCactive1 is 1 if the alarm/category “RF Input alarm” is active (present) on the element, else it is 0. If SA = SB, switch to the preferred branch (The preferred branch is set in the Hot Standby Config page) If SA > SB, switch to SB if branch A is active. If SB > SA, switch to SA if branch B is active. Automatic Switch Mode The IDU switch checks the state of both channel A and channel B regularly. This task decides whether an Rx switch is needed or not. Similarly, the Tx switching is controlled by the ODU. For the Tx switching to work, the connected IDU signals the ODU when at least one of the switching criteria are present on the IDU. In automatic switch mode the following rule constrain switching: A channel switch is performed if, and only if, the channel switched to, has no switch conditions true. On IDU A and IDU B, a dedicated task is continuously checking whether the Rx or Tx switch criteria status has changed, and if so, notifies the IDU switch and ODU about the change. Currently, bi-directional switching is not implemented in automatic mode. Manual Switch Mode In manual switch mode, bi-directional switching is performed only as a result of a Q1 message from external management software (e.g. NEW-NMS). Currently, unidirectional switching is not implemented in manual mode.
B4008 Rev. M
277
CityLink 6.1.4
Reconfiguring a Hot Standby IDU for use in 1+0 Configuration An IDU that has been used in a HSB configuration will continue to be configured as a HSB element until explicitly reconfigured. To do this, first disconnect the IDU from the switch. Then use NEW-NMS to connect to the element with a serial cable. NEW-NMS’ explorer view should now display an equipment tree with a single node. Bring up the Element ID dialog from the Configuration menu, and disable the Hot Standby checkbox. When the element is next power cycled, it will start up in 1+0 configuration. This can be verified with the Element ID dialog.
6.1.5
Reconfiguring a 1+0 IDU for use in Hot StandBy Configuration If the IDU used in a 1+0 is to be prepared for an IDU in a HSB system, it is very important to do the following procedure : 1.Connect the HSB cable between the IDUs and the switch 2.Power up the HSB IDU 3.Power up the IDU A and IDU B The IDUs will now be automatically reconfigured as IDUs used in a HSB system. WARNING! If the Y-cable connectors marked with IDU A and IDU B are swapped, the IDUs must always be rebooted after this operation.
278
B4008 Rev. M
Fast Ethernet Configuration
SECTION VIII CityLink Fast Ethernet Configuration
B4008 Rev. M
279
CityLink
Hyperterminal & Telnet 1.0
Hyperterminal & Telnet Commands • First time configuration with hyper-terminal to IDU's LCTport. – Settings on com port; 9600, 8, 1, none. – Terminal emulation; VT100. • Normal operation via IP. – Telnet session to IP-address on management port or one of the four ethernet port’s.
Figure VIII-1
Starting up and logging in
Login as admin with the password; adminpasswd
Note! NEW-NMS' security system has initially one user account: User ID: admin Password: adminpasswd It is strongly recommended to change this password!
280
B4008 Rev. M
Fast Ethernet Configuration
2.0
How to get this link alive Where to start – Status? – Do we want a IP connection to the IDU? If you have NEW-NMS, then the answer is yes. Enable IP one of the four traffic port’s and do all settings from NEW-NMS.
2.1
How to get this link alive, parameters • Enable IP as described in Chapter 4.8.1 (this Section). Enable IP on one of the four traffic port’s and do settings from NEW-NMS. – Frequency on both elements must match (Tx to Rx). – Maximum output power. – Tune antennas for maximum Rx-levels. • Verify that transmission is OK over the hop. – Enable and test on a 2Mb/s or connect with computers on the LAN.
LAN 1
M o d u le
CityLink IDU
2 (1 .5 ) M b /s c irc u it 1 - 4
Ethernet Fast Extension EBoard th e rn e t T rib u ta ry (EEB)
CityLink IDU
2 (1 .5 ) M b /s c ircu it 1 - 4
Ethernet F a st Extension EBoard th e rn e t T rib u ta ry (EEB)
LAN 1
M o d u le
LAN 2
LAN 2
LAN 3
LAN 3
LAN 4
Figure VIII-2
2.2
LAN 4
Radio Connection
Testing • How to verify transmission quality and capacity ? – One way to do this is to set up two computers and do a file transfer (FTP) between them over the hop. One PC working as FTP-server and one as FTP-client, check the time for transfer of the file and calculate throughput. Do not have any HUBs connected during this test. – Stability of the equipment and hop will be easiest monitored on BER test with pattern-generator on a 2Mb/s.
B4008 Rev. M
281
CityLink
3.0
Top Level Commands After logon you should have this text on your screen; Welcome to CityLink. Copyright (c) Nera ASA. CityLink> Then type help and press enter: Welcome to CityLink. Copyright (c) Nera ASA. CityLink> help Help: The following commands are available: Command alarms cls coldstart enter env exit gettime help list ping quit reboot settime tracert
Function lists alarms clear screen shutdown the system and make a cold start of the system enter submenu list environment variables exit submenu display system timezone, time and date get help on commands list available commands ping the specified host quit shell shutdown the system and reboot set system timezone, time and date trace route to target
Use "help " to get help on specific command. Example for usage of "Help": CityLink> help gettime gettime: display system timezone, time and date Usage: gettime CityLink> 282
B4008 Rev. M
Fast Ethernet Configuration 3.1
Top Level Commands, Example CityLink (radio)> alarms
B4008 Rev. M
Active alarms: TIME
ID
NAME
CLASS
STATE
Modem. 2001.11.19 11.04.50 2001.11.19 11.04.50 2001.11.19 11.04.50
1104 1103 1102
E-WARNING LBER HBER
WARNING MINOR MAJOR
Raised Raised Raised
Baseband 2001.11.19.11.04.50 2001.11.19.11.04.50 2001.11.19.11.04.50
32808 32809 32811
LOS_RR LOF_RR MS-AIS_INSERT_RR
MAJOR MAJOR MAJOR
Raised Raised Raised
EEB 2001.11.19.11.04.50 2001.11.19.11.04.50 2001.11.19.11.04.50
32785 32786 32787
ETHERNET_PORT_2 ETHERNET_PORT_3 ETHERNET_PORT_4
INFO INFO INFO
Raised Raised Raised
PerfManager 2001.11.19.11.15.01 2001.11.20.00.00.01
3000 3003
G826-15MIN-B1 G826-24HOUR-B1
WARNING WARNING
Raised Raised
CLIServer 2001.11.20.14.35.20
32782
CONSOLE_USER_LOGGED_IN INFO
Raised
283
CityLink
4.0
Submenu Commands The command structure is top level commands and submenu commands. Top level commands are also available at submenu levels. The following submenus are available by typing enter and then submenu:
Submenu commands: Submenu Function
Security Level eeb monitor and control of EEB passive baseband perform baseband module commands passive modem perform modem module commands passive radio monitor and control of ODU passive su monitor and control of SU passive security perform security administration passive perform monitor and control of Performance data passive config Lists and modifies configuration settings passive test perform test function commands passive fault Query and manipulate alarms and alarm settings active q1module Lists and modifies q1 and nnp protocol settings master
4.1
EEB Submenu Configuration of Ethernet module – Enable LAN ports – Select the important LAN port – Enable 2Mbit/s ports
EEB submenu commands: Command autopartition eebstatus get2mbport getethmode gettribmode gettribport getethport getflowctrl listportmib selectpriport set2mbport
284
Function enable / disable autopartition show GT-48350 link/partition status get 2MBit E1/T1 port state (from SW Version R1C0 this command has been replaced by gettribport) get Ethernet ports speed and duplex mode get tributary E1/T1 ports mode get tributary E1/T1 port state get Ethernet port state get flow control for Ethernet port list the MIB-statistics of a port select priority Ethernet port set 2MBit E1/T1 port state (from SW Version R1C0 this command has been replaced by settribport)
B4008 Rev. M
Fast Ethernet Configuration setethmode settribmode settribport setethport
set Ethernet port speed and duplex mode set tributary E1/T1 ports mode set tributary E1/T1 port state set Ethernet port state
If Flow control is set this will cause a feedback to the “sender” if the port have to much to do. In this case you will avoid lost or dumped packages and you may see an improvement of the throughput if “sender” support flow control!
4.2
Baseband Submenu Configuration of IDU – Enable 2Mbit/s Wayside – Enable 64kbit/s channels
Baseband submenu commands: Command get64kg703 get64kv11 getlaser getwayside resetbaseband set64kg703 set64kv11 setlaser setwayside startlaser
B4008 Rev. M
Function get g703 enable/disable get v11 enable/disable get current laser state get wayside enable/disable reset eeb module set g703 enable/disable set v11 enable/disable sets the laser state set wayside enable/disable starts the laser
285
CityLink 4.3
Modem Submenu (part of IDU) validberlevels – BER = Bit Error Ratio, Number of errored bit’s divided on total number of bits. High BER = 1x10-3 Low BER = 1x10-6 Early Warning (BER) = 1x10-9
Modem submenu commands Command getberlevels getfirindex getserfindex resetmodem setberlevels setfirindex setserfindex tempcomp validberlevels
Function get HBER, LBER and ER levels get current fir tap index get current serf set index reset modem set HBER, LBER and EW levels set current fir tap index set current serf set index get temperature compensation data show valid HBER, LBER and ER levels
Settings of FIR and SERF index are set from factory! Do not change them! Contact Nera to get FIR and SERF index if necessary. Remember to use NEW-NMS or NEW-Configurator when changing frequency plan used on the system, because then these setting will be correct.
286
B4008 Rev. M
Fast Ethernet Configuration 4.4
Radio Submenu (part of ODU) Configuration of ODU – Set frequency, normally done during installation. However, this will be necessary to set for spare parts.
Radio submenu commands: Command
Function
Usage
Security Level master
downloadodusw transfer ODU SW No parameters from IDU to ODU drotuning get/set ODU DRO drotuning [disable | tx | rx] master tuning mode/status getatpc get AutomaticNo parameters passive PowerControl settings getfrequency get tx and No parameters passive rx frequency getmutestate get radio mute state No parameters passive getrfpower get rf output No parameters passive and input power getrfwarning get RfInputLevel- No parameters passive Warning up and down radiostatus display all No parameters passive radio settings reloadfreq transfer current No parameters master frequency settings to ODU setatpc set Automaticsetatpc master PowerControl state: state functions rxref: rxref almoutlevel: almoutlevel almdelay: almdelay setfrequency set tx and setfrequency master rx frequency setmutestate set radio mute state setmutestate < on | off> master setrfpower set rf output power setrfpower master setrfwarning set RfInputLevel- inputwarning master Warning up and down
B4008 Rev. M
287
CityLink 4.4.1
Radio Status, Example CityLink (radio)> radiostatus Radio Configuration Tx Frequency Rx Frequency Last FrqShift Tx Frequency Min Tx Frequency Max Rx Frequency Min Rx Frequency Max Duplex Distance Rf Output Power Rf Output Power Max Rf Output Power Min Rf Input Warning Low Rf Input Warning Up ATPC state ATPC Rx Ref Level ATPC alm Out Level ATPC alarm Delay
4.4.2
= 23198000 kHz = 22190000 kHz = Ok = 23086000 kHz = 23534000 kHz = 22078000 kHz = 22526000 kHz = 1008000 kHz = 15 dBm = 18 dBm = 8 dBm = -60 dBm = -35 dBm =0 = -10 dBm = 15 dBm = 12 sec.
ODU:RF input ODU:RF output ODU:+48V Radio Muted Loop status Loop capability Transceiver S/N Radio Type Transceiver Type Boot Code Version App. Code Version App. Code Date
= -113.00 dBm = 14.00 dBm = 48.00 V =0 =0 =3 = 96 =1 = 10 = 1A0 = 4D2 =2001-12-0417:04:55
Radio Alarms. Alarm : 1502 LOS_RF_INPUT Alarm : 1504 RF_INPUT_WARNING
Radio Commands, Example of Error Message CityLink (radio)> setfrequency 22190000 23198000 Frequency out of range! TxFrequency: 23198000 kHz RxFrequency: 22190000 kHz TxFreq.Min : 23086000 kHz TxFreq.Max : 23534000 kHz RxFreq.Min : 22078000 kHz RxFreq.Max : 22526000 kHz DuplexDistance: 1008000 kHz CityLink (radio)> setfrequency 23198000 22190000
288
B4008 Rev. M
Fast Ethernet Configuration 4.5
SU Submenu (part of IDU) Important issues for maintenance and troubleshooting could be to investigate RF-input level and DC-level in ODU.
SU submenu commands: Command getanaloge getauxinput getauxoutput getfan setauxinput setauxoutput
4.6
Function list analogue sensor measurements list aux port inputs signals and configuartion list aux port outputs signals and configuration get fan status configure aux port inputs signals configure aux port outputs signals
Security Submenu It is important to limit the valid range of IP-addresses to reduce possibility of “hacking”. It is also recommended to customize the SNMP password (community strings), also in NEW-NMS.
Security submenu commands: Command adduser changename changepwd changesnmppwd deleteuser getiprange getlog getsnmppwd getuser resetlog resetsecurity setiprange setusername setuserpwd who
B4008 Rev. M
Function make a new user account change «current user» description name change «current user» password change SNMP password (community string) delete user account list secure IP ranges list security log list SNMP password (community strings) list users resetlog deletes all entries in security log reset security to factory settings set secure IP range set User description name set User password list users logged on
289
CityLink 4.7
Performance Submenu The Performance submenu shows the quality on your received signal from opposite Citylink.
Perform submenu commands: Command getfec getg826 getpulses getthreshold performstatus resetfec resetg826 resetpulses setthreshold
4.8
Function list FEC counter list G.826 performance values list error pulses list G.826 Thresholds list all performance parameters available reset FEC counter reset G.826 performance values reset error pulses set G.826 Thresholds
Configuration Submenu Configuration of the CL Element – Set system type. – Set section and station address, name etc... – Important to execute command "setinterface" in order to enable management via IP.
Config submenu commands: Command addroute authenticate deleteroute eebni getsysmode inventory listnetconfig listroute listsysconfig setantennatype setgateway setinterface setsectionaddr setstationaddr setstationname setsysconfig setsysmode 290
Function Adds routes to the routing table Authenticates access keys to enable licensed functionallity Deletes routes from the routing table Sets or gets state on EEB network interface Gets the system operation mode Prints inventory data Lists the network configuration Lists the routing table Lists current system configuration Sets the antennatype Sets the default gateway Sets the IP address and netmask of an interface Sets the section address Sets the station address Sets the station name Sets system configuration Sets the system operation mode B4008 Rev. M
Fast Ethernet Configuration snmpagent stationinfo updatesw
4.8.1
Enables or disables the SNMP agent Lists Station/Section info Updates the system software
Management Settings CityLink (config)> setinterface help Usage: setinterface < [ ] | []> if# : Interface no (1-5) ipaddress : IP Address netmask : Subnet Mask disable : Disable Interface if# CityLink (config)> setinterface 02 192.168.1.1 255.255.248.0 CityLink (config)> setgateway 192.168.7.15 CityLink (config)> listnetconfig Network interfaces. # Address Netmask Description 01 192.168.0.32.1 255.255.255.255 Management port
02 192.168.1.1 03 Disabled 04 Disabled 05 Disabled
255.255.248.0
EEB interface 1 EEB interface 2 EEB interface 3 EEB interface 4
Default gateway : 192.168.7.15
4.9
Test & Fault Submenu Test submenu commands: Command getloop setloop
Function get current looping state toggle looping state on/off
Fault submenu commands: Command alarmlog clearalarm maskalarm raisealarm unmaskalarm B4008 Rev. M
Function lists alarmlog entries clears an alarm masks an alarm raises an alarm unmasks an alarm 291
CityLink 4.10
Q1module Submenu Q1module submenu commands: Command listinterface listroutes setaddress
292
Function List the nnp interfaces Lists the nnp routing table Set the Q1 address of the element
B4008 Rev. M
Fast Ethernet Configuration
5.0
Software Upgrade Procedure for the CityLink Fast Ethernet Device 1. Download software file to IDU via ftp (1). Note: the filename must be in 8.3 (xxxxxxxx.eee) format. See Chapter 5.1 (this Section) 2. Log in on console or telnet session to the IDU and in the “config” submenu issue the command “updatesw [filename]”, where [filename] is substituted for the name given to the file in step 1. 3. After the file is loaded to flash, reboot the IDU.
Figure VIII-3
B4008 Rev. M
293
CityLink 5.1
How to download a file to the IDU: [host] : is either the host name for your IDU or the IP address in xxx.xxx.xxx.xxx format.
5.1.1
Using the Console FTP Client In a dos prompt go to the folder where your file is stored. Issue the command “ftp [host]” and log in with your administrator password. On the ftp client prompt issue the following commands: “bin” to enable binary transfers. “hash” to toggle printing `#' for each buffer transferred “put [filename]” to transfer the file. “bye” or “quit” to exit the ftp client.
Figure VIII-4
294
Downloading using the Console FTP Client
B4008 Rev. M
Fast Ethernet Configuration 5.1.2
Using the Internet Explorer (This requires downloading the browsing enhancements from Microsoft) Go to the URL “ftp://[host]” and log in with your administrator password. Drag the software file from a local folder to the Internet explorer window. Close Internet explorer to terminate the connection
Figure VIII-5
B4008 Rev. M
Downloading using the Internet Explorer
295
CityLink 5.2
How to download a file to the ODU 1. Download ODU software file to IDU via ftp. Ref. 5.1 above. 2. Log in on console or telnet session to the IDU and in the “radio” submenu issue the command “downloadodusw”. 3. After the file is downloaded to ODU, ODU is automatically rebooted.
Figure VIII-6
296
B4008 Rev. M
Fast Ethernet Configuration
NEW Network Management System The management and supervision of CityLink Fast Ethernet may be performed in various ways depending on the actual application. • NERA’s NEW-NMS can work as an SNMP-manager and control and supervise the radio-relay (described in the follwing chapters). • The CityLink Fast Ethernet may be treated as just another LAN device and controlled and supervised via the built in SNMP agent (described directly after the NEW-chapters). • Interfaces: 10Base-T LAN port or one of the 4 Ethernet ports.
6.0
Start NEW-NMS & Connect First set master as community name.The SNMP Settings configuration sheet can be opened from the Configuration menu. Use same community name as in Chapter 4.6 (this Section) Security Submenu.
Figure VIII-7
Setting Community Name in SNMP Settings
Add IP with SNMP checked or specify Search area and do a discover. For details regarding adding elements and discover; see the NEW-NMS manual (B1091).
B4008 Rev. M
297
CityLink Fields:
Description:
Get:
The community string used during discovery of SNMP elements NOT defined in any search area. Set: Default Set community string for elements NOT defined in any search area. SNMP: The UDP port used as destination port for discovery of SNMP elements. Trap: UDP port used by NEW-NMS for receiving Traps. Start Address: Starting IP address of the range to be searched. Format of the address must be xxx.xxx.xxx.xxx. Stop Address: Stop IP address of the range to be searched. Stop address must be equal or greater than start address. Format of the address must be xxx.xxx.xxx.xxx.
Add an entry to the search area: 1.Press the Add button, an entry is added to the list. By default start address = «0.0.0.0», stop address = «0.0.0.0», read community = «public», and write community = «private». 2.To change the default values dobbel click the entry in question and enter the wanted value. 3.To save your settings press OK.
Remove an entry from the search area: 1.Select the entry from the list. 2.Press the Remove button. 3.To save your settings press OK.
298
B4008 Rev. M
Fast Ethernet Configuration
Figure VIII-8 Adding IP Address
B4008 Rev. M
299
CityLink
7.0
Network Element Configuration Configuration of Network Elements is achieved using a set of propertysheets. The property-sheets are modeless, so configuration of several different modules can be displayed simultaneously. • To open the configuration property sheets: Select the object you want to view or change either from the Explorer View or a Map View. Select a Configuration command either from the context Edit sensitive menu (right mouse-button) or from the Configuration menu. The property-sheets are divided into two categories by means of functionality:
Figure VIII-9
Buttons on Configuration property sheets with multiple settings
Configuration Property sheets with Multiple Settings: The program retrieves the current settings from the Network Element (NE) when the property-sheet is opened. No set-messages is sent to the element and no data is modified in program’s data structure before the user presses one of the property-sheet buttons:
Buttons: Set: Get: Close: Help:
Applies the current settings in the Network Element (NE). Retrieves the current settings of the Network Element (NE). Closes the property-sheet without saving or setting any data. Displays help for the active property-page.
To change the settings: 1 First, get the current settings from the NE by pressing Get. (The settings are automatically retrieved from the NE when the propertysheet is opened). 2 Alter the settings you want to change. 3 Press Set to send the changes to the NE.
300
B4008 Rev. M
Fast Ethernet Configuration Configuration Property sheets with Single Interactive Settings: The program retrieves the current NE settings when the property-sheet is opened. Has no Get or Set buttons; All functional buttons are placed in the property-pages. A message is sent to the Network Element immediately when a control is changed or a button is pressed. Property-sheet buttons:
Figure VIII-10
Buttons on Configuration property sheets with single active settings
Buttons: Close: Closes the property-sheet. Help: Displays help for the active property-page. All property-pages have an information field at the bottom reflecting the current status of the data shown in the property-page and the date and time the property sheet data was retrieved from the Network Element.
Figure VIII-11
B4008 Rev. M
Configuration property sheet information field
301
CityLink
8.0 8.1
Element Node Element Id The CityLink Element Id property sheet shows main information about the Network Element like name, type, serial number and different addresses. The fields with white background can be altered by users with proper user privileges The gray fields are non-editable. The Element Id configuration sheet can be opened from the Configuration context menu of the Element node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Element node in the Explorer view and then selecting Edit Element ID from the Configuration menu.
Figure VIII-12
Element ID Configuration Sheet
Fields:
Description
Serial Number: NE Type: Name: Section Address: NE Address:
The serial number of the NE. (Not editable) The type of NE. (Not editable) The name of the NE. (max. 32 characters) The section address of the NE. The NE address. Used to identify NEs within a section. The Media Access Control address of the NE. (Not editable) The Internet Protocol address of the NE.
MAC Address: IP Address:
302
B4008 Rev. M
Fast Ethernet Configuration 8.2
NE Clock The NE Clock sheet lets you synchronize the Network Element Date/Time with the NEW-NMS/PC Date/Time. (The NE Clock is set to the same date/ time as the PC Clock) The NE Clock configuration sheet can be opened from the Configuration context menu of the Element node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Element node in the Explorer view and then selecting Edit NE Clock from the Configuration menu.
Figure VIII-13
Fields:
NE Clock Configuration Sheet
Description:
The Element’s Clock: The Date and Time retrieved from the NE. Difference from The difference between the PC clock and the NEW-NMS (your PC): NE Clock
B4008 Rev. M
303
CityLink 8.3
Software Versions The software versions property sheet displays the software revisions and status of the SU and the available subunits The SW Versions configuration sheet can be opened from the Configuration context menu of the Element node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Element node in the Explorer view and then selecting Edit SW Versions from the Configuration menu.
Figure VIII-14
SW Versions Configuration Sheet
Fields:
Description:
SW Component: Bank: Revision:
Software title Software location Sofware revision. The field will display “unknown” if the system has this unit present, but is unable to retrieve the information from it. Valid: Complete or valid software.
Status:
304
B4008 Rev. M
Fast Ethernet Configuration 8.4
Production Data The production data property sheet presents details about the HW components within CityLink Fast Ethernet. The Production Data configuration sheet can be opened from the Configuration context menu of the Element node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Element node in the Explorer view and then selecting Edit Production Data from the Configuration menu.
Figure VIII-15
B4008 Rev. M
Production Data Property Sheet
Fields:
Description:
InventoryName: InventorySerialNumber: InventoryVersion:
The name of the HW component. The serial number of the HW component. The HW component version.
305
CityLink 8.5
SNMP Agent(s) Settings The SNMP Agent(s) property sheet shows the current SNMP settings. The Element SNMP Settings configuration sheet can be opened from the Configuration context menu of the Element node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Element node in the Explorer view and then selecting Edit SNMP Settings from the Configuration menu. All information presented in the configuration sheet is set locally and not retrieved from the element. NOTE! In order for NEW-NMS to manage the SNMP element, the SNMP Agent settings configured locally must match the settings in the NEWNMS. Please see the CityLink Fast Ethernet Agent Configuration. NEW-NMS is using received traps for keeping an accurate element status. SNMP Traps are unreliable and no delivery guarantee is given, to overcome this weakness a query for number of traps sent from the SNMP element must be performed from NEW-NMS at given time intervals. If the number of traps sent from the element is not equal to the number of traps received from the element, traps have been lost and alarm synchronization is needed.
Figure VIII-16
306
Element SNMP Settings Property Sheet
B4008 Rev. M
Fast Ethernet Configuration Columns:
Description:
IP address
The Internet Protocol address of the NE (not editable). The community string used when setting information at the element (set request). The community string used when retrieving information at the element (get/getNext request). Element UDP Port for Get/Getnext/Set Number of Managers set up to receive traps from this element.(Not used)
Set Community:
Get Community:
Port: No. Receivers:
• Edit values in the list:
The values of the columns SetCommunity, GetCommunity, Port, and No Trap receiving Managers can be modified: 1. Double click cell to be edited. 2. Type new value. 3. Click outside cell. 4. To save your settings press Set.
B4008 Rev. M
307
CityLink 8.6
Trap Table The trap table presents information about the managers currently registered to receive traps. The Trap Table configuration sheet can be opened from the Configuration context menu of the Element node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Element node in the Explorer view and then selecting Edit Trap Table from the Configuration menu.
Figure VIII-17
Fields:
Trap Table Configuration Sheet
Description:
IP Address: IP address of the registered SNMP manager trap Port: Which port is used for sending Traps to managers Last access: Time the agent was last accessed by the SNMP manager
308
B4008 Rev. M
Fast Ethernet Configuration 8.7
MIB II - System Group The System Info property page shows some of the MIB-II System Group attributes. The fields with white background can be altered by users with proper user privileges. The gray fields are non-editable.
Figure VIII-18
System Info Property Sheet
The MIB II Info configuration sheet can be opened from the Configuration context menu of the Element node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Element node in the Explorer view and then selecting Edit MIB II Information from the Configuration menu.
B4008 Rev. M
309
CityLink Fields:
Description:
Sys Description: A textual description of the entity. This value should include the full name and version identification of the system’s hardware type, software operating-system, and networking software. It is mandatory that this only contain printable ASCII characters. Sys OID: The vendor’s authoritative identification of the network management subsystem contained in the entity. This value is allocated within the SMI. enterprises subtree (1.3.6.1.4.1) and provides an easy and unambiguous means for determining ‘what kind of box’ is being managed. Name: The name of the Network Element. Location: The physical location of this node (e.g., ‘telephone closet, 3rd floor’). Contact: The textual identification of the contact person for this managed node, together with information on how to contact this person. Sys Uptime: The time since the network management portion of the system was last re-initialized.
• To change the settings:
In order for the user to change settings the Set Community name must be configured as described in SNMP Agent(s) settings. 1 First, get the current settings from the NE by pressing Get. (The settings are automatically retrieved from the NE when the propertysheet is opened). 2 Alter the settings you want to change. 3 Press Set to send the changes to the NE.
310
B4008 Rev. M
Fast Ethernet Configuration 8.8
MIB-II SNMP Group The MIB-II SNMP property page presents the performance of the underlaying SNMP implementation on the managed entity and tracks things such as the number of SNMP packets sent and received. A complete description of each field is available by holding the mouse cursor over wanted item in the dialog and the description found in RFC1213 will be displayed.
Figure VIII-19
Fields:
Description:
OID
Object IDentifier, uniquely defines a managed objects. These can appear in two forms: numeric (i.e. 1.3.6. 1.2.1.11.1) and «human readable» (i.e. iso.org.dod.internet.mgmt.mib2.snmp.snmpInPkts) NEW-NMS uses «human readable» form and will display the above example as snmpInPkts. Value contained in this OID.
Value
B4008 Rev. M
MIB-II SNMP Property Sheet
311
CityLink 8.9
Looping The Looping configuration sheet can be opened from the Configuration context menu of the Element node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Element node in the Explorer view and then selecting Edit looping from the configuration menu. The loop settings are divided into three categories: Main Traffic Loops, 2Mbit/s Wayside traffic looping, and 64kbit/s looping. Loops can be toggled on/off by pressing the loop-buttons placed on top of a schematic bitmap. Only one loop can be active at any given time. The Loop Expire time has to be set to a time later than the current time. This time must not be more than 30 days from the current time. The loop will stay active until the Loop Expire Time is exceeded even if the looping page is closed. When a loop button is pressed, but no response from the NE is received, the loop button is colored blue. When a loop is confirmed on, it is colored red.
312
B4008 Rev. M
Fast Ethernet Configuration 8.9.1
Main Traffic Loops
8.9.1.1
Radio Terminal
Figure VIII-20
Looping Configuration Sheet, Radio Terminal
The different main traffic loops: All main traffic near end loops are swapped (port 1 → port 2, port 3 → port 4). Baseband Loop (far end) - Outgoing line traffic to incoming line traffic. Baseband Loop (near end) - Incoming line traffic to outgoing line traffic. IF Loop IDU IF Loop Transceiver RF Loop Transceiver Ethernet Loop near end with swap E1/T1 loops near end E1/T1 loops far end Note! FAR end loop will break management traffic to other side.
B4008 Rev. M
313
CityLink 8.9.1.2
Line Terminal
Figure VIII-21
Looping Configuration Sheet, Line Terminal
The different main traffic loops: All main traffic near end loops are swapped (port 1 → port 2, port 3 → port 4). Ethernet Loop near end with swap E1/T1 loops near end E1/T1 loops far end Line TX SORP LR out to LT in loop end Line RX SORP LT out to LR in loop near end Note! FAR end loop will break management traffic to other side.
314
B4008 Rev. M
Fast Ethernet Configuration 8.9.2
Wayside Loops
Figure VIII-22
Looping Configuration Sheet, Wayside Channel Tab
The different 2 Mbit/s Wayside Loops: Wayside Loop (far end) Wayside Loop (near end)
B4008 Rev. M
315
CityLink 8.9.3
64 kbit/s Loops
Figure VIII-23
Looping Configuration Sheet, 64kbit/s Tab
The different 64kbit/s loops: 64kbit/s Channel 1 Loop (far end) 64kbit/s Channel 1 Loop (near end) 64kbit/s Channel 2 Loop (far end) 64kbit/s Channel 2 Loop (near end)
316
B4008 Rev. M
Fast Ethernet Configuration
9.0 9.1
In Door Unit (IDU) 64 kbit/s Channels Two 64 kbit/s channels can be inserted into the SOH. Each of the 64kbit/s channel will occupy one byte of the SOH frame. Both channels can be retrieved from and inserted into the line and radio side independently. The 64 kbit/s Channels configuration sheet can be opened from the Configuration context menu of the IDU node in the Explorer view. The sheet can also be invoked by selecting the IDU node in the Explorer view and then selecting Edit 64 kbit/s Channels from the Configuration menu.
Figure VIII-24 Fields:
Choices:
Description:
Status:
Enabled Disabled
Enables the 64 kbit/s Channel Disables the 64 kbit/s Channel Choose the direction the 64 kbit/s Rx channel should be extracted from. 64 kbit/s Rx is inserted from line SOH frames 64 kbit/s Rx is inserted from radio SOH frames
Direction: Line Radio
9.2
64kbit/s Channels Configuration Sheet
Ethernet Extension Board The main purpose of the Ethernet Extension Board (EEB) is to convert Ethernet to/from STM-1 frames. The EEB also multiplexes 4 E1/T1 channels into the STM-1 frames. The EEB configuration sheet can be opened from the Configuration context menu of the IDU node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the IDU node in the Explorer view and then selecting Edit Ethernet Extension Board from the Configuration menu
B4008 Rev. M
317
CityLink 9.2.1
Ethernet Ports
Figure VIII-25
Ethernet Ports Configuration Sheet
Fields:
Description:
portEthStatus portEthFlowCtrl portEthLinkStatus portEthPartitionStatus
This entry enables/disables the port. This entry controls flow control setting. This entry shows the current link status. This entry shows the current partiton status for the port. portEthLinkSpeed This entry controls the link speed for the port. portEthLinkDuplex This entry controls the link duplex mode for the port. portEthLinkFailureShutdown This entry controls the Link Failure Shutdown mode for the port. When enabled port is forced shutdown due to SDH alarm or remote ETH-port no Link. Note: Port is NOT forced shutdown as described above if IP management is enabled on port. 318
B4008 Rev. M
Fast Ethernet Configuration Priority Port Auto Partition
Designates the prioritized port.(Guaranteed 100Mb operation.) Auto partition state for the EEB ethernet ports.
Note : Ethernet Port fixed speed / duplex mode setting: 1) Set user terminal equipment speed / duplex mode to Auto. 2) On CityLink FastEthernet port sett required link speed. Note: It is not recommended to use 10Mb Half duplex .
9.2.2
2 Mbit/s Ports Configuration of tributary E1/T1 ports (2Mbit/s or 1.5Mbit/s).
B4008 Rev. M
Figure VIII-26
2Mbit/s Ports Configuration Sheet
Fields:
Description:
port2MBIndex port2MBStatus
Tributary E1/T1 port index . Presents the status of the tributary E1/T1 port.
319
CityLink 9.3
Wayside Channel A Wayside channel can be inserted in the SOH in either line-direction or radio-direction. The Wayside channel will occupy 33 bytes (32 bytes data + 1 byte alignment information) of the SOH. The Wayside channel use the Rx and Tx connection at the front panel of the IDU. Rx is received data and Tx is sent data. The Wayside configuration sheet can be opened from the Configuration context menu of the IDU node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the IDU node in the Explorer view and then selecting Edit Wayside from the Configuration menu.
Figure VIII-27
Fields: Status:
Wayside Channel Configuration Sheet
Options:
Enabled Disabled Direction: Line Radio
320
Description Enables the Wayside Channel Disables the Wayside Channel Wayside Rx is extracted from line SOH Rx is extracted from radio SOH.
B4008 Rev. M
Fast Ethernet Configuration 9.4
Auxiliary Output There are four configurable auxiliary output pins in the ALM/AUX port. The pins are connected to a relay, which can either be controlled manually, or triggered automatically on a user selectable alarm. The Auxiliary Output Configuration sheet can be opened from the Configuration context menu of the IDU node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the IDU node in the Explorer view and then selecting Edit Auxiliary Output from the Configuration menu.
Figure VIII-28
B4008 Rev. M
Auxiliary Output Configuration Sheet
321
CityLink Controls:
Choices:
Description:
Output control radio buttons:
Manual control Set the usage of the auxiliary or output pin. (Disabled if the Alarm triggered CityLink does not support alarm triggers.)
Manual Relay status radio buttons
Closed or open
If the auxiliary output is set to manual control, these buttons will be enabled, and can be used to manually control the state of the relay.
Equipment tree
-
Displays and selects the alarms available for alarm triggers. This will be disabled if the auxiliary output is set to manual control.
Alarm trigger list
-
Displays the alarm triggers configured. Disabled if the auxiliary output is set to manual control.
Add alarm button
-
Adds the currently selected alarm in the equipment tree to the alarm trigger list. If there is no selection, or if the selected tree node doesn’t correspond to an alarm, nothing happens. Disabled if the output is on manual control.
Remove alarm button
-
Removes the currently selected alarm from the alarm trigger list. Disabled if the output is on manual control.
Alarm triggered relay Closed or Open If the auxiliary output is set to status radio buttons alarm triggered control, these buttons will be enabled, and can be used to control the state of the relay when the alarmconditions are raised. 322
B4008 Rev. M
Fast Ethernet Configuration 9.5
BER Thresholds The Viterbi decoder is a component using a Viterbi low complexity algorithm for decoding/error correcting the received bit-sequence in the NE. The viterbi error rate is used as a quality measurement for the radio hop. When the Viterbi error rate exceeds certain values, alarms are generated. The threshold values decides when alarms are generated. The threshold values can be changed by the user. Alarm Id HBER LBER EW-BER
Default value Indicator for BER >1exp-3 Indicator for LBER >1exp-6 Indicator for EW-BER >1exp-10
Alarm severity MAJOR MINOR WARNING
Internal proportions: HBER > LBER > EW The BER Threshold configuration sheet can be opened from the Configuration context menu of the Radio node under the IDU node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Radio node under the IDU node in the Explorer view and then selecting Edit BER Threshold from the Configuration menu.
Figure VIII-29
B4008 Rev. M
BER Threshold Configuration Sheet
323
CityLink
324
Fields:
Choices:
Description:
HBER
1.0e - 1.0e
-10
Range. A Major alarm is generated when the Viterbi error rate exceeds the High BER threshold value. AIS is inserted when the HBER threshold value is exceeded.
LBER
1.0e-3 - 1.0e-11
Range. A Minor alarm is generated when the Viterbi error rate exceeds the Low BER threshold value.
EW
1.0e-3 - 1.0e-12
Range. A Warning is generated when the Viterbi error rate exceeds the Error Warning threshold value.
-3
B4008 Rev. M
Fast Ethernet Configuration 9.6
Laser Control Available on CityLink Fast Ethernet Line Terminal only. The optical port may or may not have implemented Automatic Laser Shutdown (ALS). This is a function designed for eye safety purposes, according to ITU-T rec. G.958. When implemented, ALS may be enabled or disabled. When ALS is not implemented or enabled the laser must be turned on/off manually. When ALS is enabled, the laser automatically will restart after a waiting time period (selectable), when having previously been turned off. (If the section of operation is not connected or Loss Of Optical Signal from far end is detected, the laser will again be turned off after 2 sec.) The waiting period is by default set to 1 minute. The Laser Control configuration sheet can be opened from the Configuration context menu of the Optical Line node under the IDU node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Optical Line node under the IDU node in the Explorer view and then selecting Edit Laser Control from the Configuration menu.
Figure VIII-30
B4008 Rev. M
Laser Control Configuration Sheet
325
CityLink Fields:
Buttons:
Description:
ALS: Enabled/Disabled Waiting Time
Toggles ALS On/Off (1.0 - 5.0 minutes ) Specifies waiting time before the laser is turned on. If section of operation is connected and optical signal from far end is present, laser will remain on, if not laser will be turned off after 2 seconds. Get Retrieves Laser Control settings from the NE. Set Sends Laser Control settings to the NE. Restart (2 Seconds) Manually restart the laser for 2 seconds. Restart (90 Seconds) Manually restart the laser for 90 seconds for testing purposes. Manual Control: On Off Status:
326
(ALS disabled or not implemented) Manually turn the laser on. Manually turn the laser off. Shows the status of the Laser Unit.
B4008 Rev. M
Fast Ethernet Configuration
10.0 10.1
Out Door Unit (ODU) Antenna Data This sheet shows some main characteristics of the antenna. Only the antenna code can be altered. The antenna data are stored in a database file. The Antenna Data configuration sheet can be opened from the Configuration context menu of the Antenna node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Antenna node in the Explorer view and then selecting Edit Antenna from the Configuration menu.
Figure VIII-31
Antenna Data Configuration Sheet
Fields:
Description:
Antenna code Gain
The antenna code. Unique code for each antenna type. The antenna Gain. (dB) Gain is a measurement of the antennas ability to transform electrical signals to electromagnetic waves. The polarization direction of the antenna. Front/Back Ratio. Ratio between the Gain in forward direction and Gain in backward direction. The physical antenna diameter. [ Meter] The frequency range where the antenna can be expected to operate successfully.
Polarization FB Diameter Frequency range
B4008 Rev. M
327
CityLink 10.2
Power Settings ATPC (Automatic Transceiver Power Control) is a function for effectively reducing the interference probability in your network. The output power from the transceiver is automatic controlled. If the regulation loop for the ATPC stops functioning, an alarm is generated. This alarm can be delayed. The output power should be muted when the frequency setting is changed. The Power Settings configuration sheet can be opened from the Configuration context menu of the ODU node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the ODU node in the Explorer view and then selecting Edit Power Settings from the Configuration menu.
Figure VIII-32
328
Power Settings Configuration Sheet
B4008 Rev. M
Fast Ethernet Configuration Fields:
B4008 Rev. M
Denomination: Description:
RF-INPUT- dBm WARNINGhigh
The upper threshold value for when to generate a RF Input Level Warning (Alarm nr. 1504).
RF-INPUT- dBm WARNINGlow
The lower threshold value for when to generate a RF Input Level Warning (Alarm nr. 1504).
Manual dBm output level
The output power level used when ATPC not is activated.
Mute output power
Mutes the output power. No output power is sent.
Maximum dBm output power
Maximum output power for transmitting.
Manual Transmit Output Power (MTPC)
Disable ATPC.
Automatic Transmit Output Power (ATPC)
Enable ATPC.
Reference input level
The wanted input level when ATPC is activated.
dBm
Default dBm output level
Set the Power Level to use when an ATPC alarm occurs.
ATPC alarm seconds delay
The ATPC alarm can be delayed a certain number of seconds.
329
CityLink 10.3
Frequency Settings The Duplex Distance between the Rx and Tx band is fixed. The user can set the Tx frequency by clicking on the frequency slots. Since the duplex distance is fixed the Rx frequency will be automatically set. The corresponding Tx and Rx frequency must be set in the opposite NE. NEW-NMS/-Configurator receives the frequency plan from the NE. When no NE is connected (off-line) no frequency plan will be shown. The output power should be muted when the frequency setting is changed. The Frequency configuration sheet can be opened from the Configuration context menu of the ODU node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the ODU node in the Explorer view and then selecting Edit Frequency from the Configuration menu.
Figure VIII-33
330
Frequency Configuration Sheet
B4008 Rev. M
Fast Ethernet Configuration Fields:
Denomination: Description:
Frequency plan
Choose the wanted frequency plan. The frequency plan must. correspond to your transceiver. MHz The used Tx Carrier frequency. MHz The used Rx Carrier frequency. TCM or TCM+RS The coding scheme The modulation scheme used with this frequency plan. STM-1 or STM-0 MHz The distance between the channels in this frequency plan. MHz The distance between the Tx and the Rx carrier frequency. MHz The distance between the highest frequency in lower half and the lowest frequency in the upper half of the frequency plan. Digital filters in the Modem Board compensating for RF Filter and branching characteristics. MHz Tx Lower sideband frequency for this frequency plan. MHz Tx Upper sideband frequency for this frequency plan. MHz Rx Lower sideband frequency for this frequency plan. MHz Rx Upper sideband frequency for this frequency plan. The result of the last frequency change operation (unknown, ok, executing, failed). When this item is checked the modem will be reset when applying selected frequency data. Only to be used when changing frequency plan.
TX Frequency RX Frequency Coding Modulation Data rate Channel spacing Duplex Distance Innermost spacing Compensation filter TX Frequency Band,Min TX Frequency Band,Max RX Frequency Band,Min RX Frequency Band,Max Status Reset Modem
NOTE! Both the IDU and the ODU must be rebooted after a change of frequency and/ or Reed Solomon code. This is done by disconnecting and reconnecting power to the IDU.
B4008 Rev. M
331
CityLink
11.0 11.1
Performance G826 Performance G.826 is an ITU-T quality recommendation for SDH networks. The Network Element has several registers for collecting G.826 performance data. The G.826 data is divided into three categories; G.826 15min, G.826 Day and G.826 Month and they show the B1 measurements for 16 periods of the category. (4 hours of 15min data, 16 days and 16 months are available in the NE). The G-826 Performance configuration sheet can be opened from the Performance context menu of the Element node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Element node in the Explorer view and then selecting Performance Registers from the Main menu.
Figure VIII-34
332
G-826 Performance Configuration Sheet
B4008 Rev. M
Fast Ethernet Configuration Fields:
Description:
Time interval Period
The interval of the measurement (15 min., day, month). The sequence number of the performance register. Register 0 is the running measurement, register 1 is the latest completed measurement. Severely Errored Seconds. The number of one-second periods which contains > 30% errored blocks or at least one Severely Disturbed. The number of UnAvailable Seconds. A period of unavailable time begins at the onset of 10 consecutive SES events. These ten seconds are considered to be a part of the unavailable time. A new period of available time begins at the onset of ten consecutive non-SES events. These 10 seconds are considered to be part of available time. The number of Background Block Errors. An errored block not occurring as part of an SES. Errored Second. The number of one second periods with one or more errored blocks. The start time of the measurement period. Status of the counter.
SES UAS
BBE ES Start Time Status
B4008 Rev. M
333
CityLink 11.2
Port Performance The Repeater port information property sheet presents performance and error statistics for the individual ports on the Network Element. Each entry in the table contains information for a single port. The data are gathered from the RFC-2108 MIB. The Port Performance configuration sheet can be opened from the Performance context menu of the IDU node in the Explorer view.
334
Figure VIII-35
Port Performance Configuration Sheet
Fields :
Description:
Readable frames Readable octets Runts Late events Autopartition Total errors
Please Please Please Please Please Please
refer refer refer refer refer refer
to to to to to to
RFC-2108 RFC-2108 RFC-2108 RFC-2108 RFC-2108 RFC-2108
MIB. MIB. MIB. MIB. MIB. MIB.
B4008 Rev. M
Fast Ethernet Configuration 11.3
Repeater Performance The Repeater Information Property sheet presents Ethernet performance. The figures presented are based on the performance of every port on the Network Element. Each entry in the table contains information about a single non-trivial repeater.The data are gathered from the RFC-2108 MIB. The Repeater Performance configuration sheet can be opened from the Performance context menu of the IDU node in the Explorer view.
B4008 Rev. M
Figure VIII-36
Repeater Performance Configuration Sheet
Fields:
Description:
Tx Collisions Total Frames Total errors Total octets
Please Please Please Please
refer refer refer refer
to to to to
RFC-2108 RFC-2108 RFC-2108 RFC-2108
MIB. MIB. MIB. MIB.
335
CityLink
12.0 12.1
Fault NE Alarm Log The NE Alarm Log property sheet displays the settings and content of the NE alarm log. The NE Alarm Log configuration sheet can be opened from the context menu of the Element node in the Explorer view. The sheet can also be invoked by selecting (highlighting) the Element node in the Explorer view and then selecting NE Log Manager from the Fault menu.
Figure VIII-37
NE Alarm Log Configuration Sheet
When pressing View in the NE Alarm Log Manager, a dialog box is displayed prompting for the number of records to retrieve.
336
Figure VIII-38
Number of Records Dialog Box
Controls: Log full action Max. number of events Number of events
Options: Description: Wrap or Halt Actions to take when the log is full. The number of entries theNE alarm log can hold. Current number of log entries.
B4008 Rev. M
Fast Ethernet Configuration
13.0 13.1
Security Security Log CityLink Fast Ethernet has an internal security log that can contain up to 1000 events. To view the local security log, select a CityLink Fast Ethernet object (in a map or explorer view), and select the NE Security Log command either from the context menu or from the Security main menu.
Figure VIII-39
B4008 Rev. M
Security Log
Fields:
Description:
Security Log Index Security log entry text Security log entry time
The index of the Security log A descriptive text of the event. The time of the event.
337
CityLink
SNMP & MIB Description 14.0
General • SNMP = Simple Network Management Protocol – Open internet protocol, requires IP connection. • MIB = Media Information Base – File describing all details about the equipment. – This file must be copied into SNMP-manager
15.0
Supported MIB’s The CityLink Fast Ethernet embedded application supports the following MIBs Name Description NERA-FAST-ETHERNET-MIB Specific management of CityLink Fast Ethernet devices. NERA-MIB General management of Nera radio equipment. SNMP-REPEATER-MIB General management/ monitoring of repeater units. RFC1213-MIB (mib2) General management of network devices.
Defined in Nera_Clip.mib
Nera.mib
RFC 2108
RFC 1213
NERA-FAST-ETHERNET-MIB purposes: • To support common management task through SNMP. • To provide network management with an acceptable security level. • To support industry standard MIB definitions where appropriate. • To create a modular MIB design to reflect the modularity of the agent software. • To facilitate future updates and configuration changes. • To conform to the established conventions of the “NERA-MIB” MIB.
338
B4008 Rev. M
Fast Ethernet Configuration
16.0
MIB Overview The MIB is separated into 8 sub-modules as shown below.
Figure VIII-40
B4008 Rev. M
MIB Overview
339
CityLink 16.1
Unit This unit contains entries related to overall system properties. This includes system time, status, transmission settings and management addressing
Figure VIII-41
340
MIB Sub-modules, Unit
B4008 Rev. M
Fast Ethernet Configuration 16.2
IDU This module provides configuration and monitoring of IDU hardware interfaces. This includes the Ethernet ports, 2Mbit/s ports, 64kbit/s ports and the auxiliary port. The module also contains the global error level limits for the IDUs data inputs.
Figure VIII-42
B4008 Rev. M
MIB Sub-modules, IDU
341
CityLink 16.3
ODU This module contains the ODU specific control settings and operational status. The ODU functional capabilities are obtainable through the “capabilities” sub module.
Figure VIII-43
342
MIB Sub-modules, ODU
B4008 Rev. M
Fast Ethernet Configuration 16.4
Test Manager This Module provides means to perform test functions on the equipment. The design provides an extensible way of generating traffic loops on various interfaces and test points. It is possible at run time to query for possible loop settings and perform tests without previous knowledge of the test loops provided by the equipment.
Figure VIII-44
B4008 Rev. M
MIB Sub-modules, Test Manager
343
CityLink 16.5
Performance Manager The module provides means of access to traffic performance data. The current design only supports the G826 B1 measurement type but the layout of the module makes feasible to extend this in future versions.
Figure VIII-45
344
MIB Sub-modules, Performance Manager
B4008 Rev. M
Fast Ethernet Configuration 16.6
Fault Manager This module is an extension to the fault management framework defined by the “NERA-MIB” specification. It supplies an extension to the previous fault log which is more configurable than the previous. In addition it supplies new functionality where a manager can query all supported alarm types from the equipment and retrieve descriptions and node information for each one. This will reduce the linking between the management software and the agent considerable.
Figure VIII-46
B4008 Rev. M
MIB Sub-modules, Fault Manager
345
CityLink 16.7
Analogue Value This module simply supplies analogue measurements from the agent system. The module is completely independent of the measurements presented and is therefore highly extendable
Figure VIII-47
16.8
MIB Sub-modules, Analogue Value
Security Manager This module implements a simple facility to retrieve security related information from the system.
Figure VIII-48
346
MIB Sub-modules, Security Manager
B4008 Rev. M
Troubleshooting
SECTION IX Troubleshooting
B4008 Rev. M
347
CityLink
1.0
General This Section describes two ways of troubleshooting; by means of LEDS located at the In Door Unit's front panel and by means of NEW-NMS Configurator.
2.0 2.1
Description of Alarm LEDs IDU Alarm LEDs The functions of the alarm LEDs are as follows: CRITICAL Red Will be activated when one or more critical alarms are activated MAJOR Red Will be activated when one or more major alarms are activated MINOR Red Will be activated when one or more minor alarms are activated WARNING Orange Will be activated when one or more warnings are activated POWER ON Green Will be on when main power is > 39V
2.2
HSB-IDU Alarm LEDs and Switch Indicators The functions of the alarm LEDs are as follows: CRITICAL Red Will be activated when one or more critical alarms are activated MAJOR Red Will be activated when one or more major alarms are activated MINOR Red Will be activated when one or more minor alarms are activated WARNING Orange Will be activated when one or more warnings are activated PWR 1 Green Will be on when main power is > 39V PWR 2 Green Will be on when main power is > 39V The functions of the Switch indicators are as follows: RX DIRA Green Will be on when receiving on A-branch RX DIRB Green Will be on when receiving on B-branch TX DIRA Green Will be on when transmitting on A-branch TX DIRB Green Will be on when transmitting on B-branch
348
B4008 Rev. M
Troubleshooting 2.3
LEDs on Line Interface Plug-in Boards G.703 Line interface: Green LED is activated when input signal is present. Multimode Fiber Line interface: Green LED is activated when input signal is present. Singelmode Fiber Line interfaces (1310 Nm and 1550 Nm): Green LED is activated when input signal is present. CAT-5 UTP Line interface: Bicolor LED. Emits red when input signal is present and loss of frame (LOF) alarm is activated. Emits green when input is normal and LOF is low.
3.0
Troubleshooting by NEW-NMS Configurator
3.1
Introduction Fault management is the process of locating and correcting network problems or faults. Fault management is possibly the most important task in network management. It consists of identifying the occurrence of a fault, isolating the cause of the fault and correcting it if possible. The fault management increases the network reliability by giving the network operator a tool that quickly detects problems and initiates recovery procedures. NEW contains functions for acquisition, presentation and storage of alarms and events from the network to be managed.
3.2
Information Acquisition In order to detect faults, information must be gathered from the network. The state of the network is monitored using two different methods.
3.2.1
Polling The various network elements should be polled on a regular basis, so that changes in Network Elements (NE) are detected and network connectivity is checked. Which NE to poll, the polling rate and what to be polled for a specific NE is user definable.
B4008 Rev. M
349
CityLink 3.2.2
Event Notification In addition to polling, some NEs have the ability to spontaneously report events. The NEW will gather this information in addition to polling. This feature will decrease the managers response time to network events considerably.
3.3
Alarm Presentation In all views, where network information is presented, colors are used to indicate the alarm severity status of the NEs. To easily identify the status of the NEs, all alarms are classified according to their severity. Each alarm severity class has a color. In the different views, the NEs change colors according to the color of their most severe alarm. The alarm classifications are described in the table below. Severity Normal
Colour (default) Green
Description
No alarms or warning have been reported from the NE. Warning Yellow Indicates the detection of a potential or impending service-affecting fault, before any significant affects have been felt. Action should be taken to further diagnose and correct the problem in order to prevent it from becoming a more serious serviceaffecting fault. Minor alarm Dark Yellow Indicates the existence of a non-serviceaffecting fault condition and that corrective action should be taken in order to prevent a more serious fault. Major alarm Orange Signifies that a service-affecting condition has occurred and urgent corrective action is required. Critical alarm Red The most severe alarm. It signifies that a service-affecting condition has occurred and an immediate corrective action is required. No contact Blue Indicates that no contact is achieved with the NE. The communication settings should be checked in order to obtain contact with the element. Misconfigured Magenta The NE has not been properly configured.
350
B4008 Rev. M
Troubleshooting 3.4
Visual Alarm Notification There are four different ways of monitoring alarms in NEW. These methods are described in the following subchapters. The NEW context sensitive help system offers a more comprehensive support on all features in the NEW program.
3.4.1
Alarms on a Tree node/leaf in the Explorer view The Explorer View is opened by selecting Explore Net from the View Menu. Figure IX-1 shows an example of the Explorer view. The Explorer View shows the Network information in a logical manner. Each NE is divided into two main branches; a Transmission branch and an Equipment branch. The sub-branches and leaves under the Transmission branch concern the transmission aspects of the NE. The sub-branches and leaves under the Equipment branch concern the physical equipment of the NE.
Figure IX-1 Example of Explorer View B4008 Rev. M
351
CityLink The Explorer view use the severity colours to indicate alarm events. The alarms are presented in a hierarchical manner. The colour of the most severe alarm is inherited from the leaf where the alarm was identified, to all branch leaves up to the section symbol. E.g. the section and NE symbols will always show the alarm colour of the most severe alarm identified in the sub-branches in the Explorer view. By pressing the right mouse button on any nodes/leaves in the Explorer View and selecting Current Alarms from the context menu, a Current Alarm List (ref. Appendix III) is opened showing all alarms Hierarchical below the selected leaf.
3.4.2
Alarms on a Node symbol in the Map view The Map View is opened by selecting Map Navigator from the View Menu. Follow the instructions in the Help file to create a map. Figure IX2 shows an example of the view. The Map View shows the Network information in a physical manner. Each NE is showed as an NE icon. Graphic-files can be added as background images in the view. NE icons grouped together with bindings form networks. The NE icons change their severity colours according to the current most severe alarm of the NE.
Figure IX-2 Example of Map View By pressing the right mouse button on a NE icon in the Map View and selecting Alarms from the context menu, a Current Alarm List (ref. Appendix III) is opened showing all alarms of the NE.
352
B4008 Rev. M
Troubleshooting 3.4.3
Viewing Alarms in the Current Alarms View The Current Alarm View can be opened by selecting Current Alarms from the Fault Menu. Figure IX-3 shows an example of the Current Alarms List. Each alarm is listed as a row in the list as shown in Table IX-1. The Current Alarms List can also be opened from both the Explorer View and the Map View by selecting Current Alarms from the right-mousebutton-click context menu. The filter is then automatically set up to show only the alarms hierarchically below the node/leaf the alarm list was opened from.
Figure IX-3 Example of Current Alarms Fields Severity Alarm text Node
Description The severity of the alarm A short description of the alarm The name of the node where the alarm occurred
Table IX-1 Fields in the Current Alarms List Alarms can also be logged to files. Consult the NEW NMS Manual or the NEW NMS Help system for further information.
B4008 Rev. M
353
CityLink
4.0
Cable Fault If a cable fault is indicated, it indicates that the microprocessor communications between the IDU and ODU have failed. The fault is most probably with the cable connection. It may be open or shorted. Disconnect the cable from the IDU and leave the ODU connected. Measure the DC cable resistance between the centre pin and the outer conductor of the N-type connector terminating the cable by means of a multi-meter. Ω to a few MΩ Ω: If resistance is in the order of some hundreds kΩ Probably no cable fault. Replace IDU or ODU, one at the time. If alarm persists, swap the replaced unit for the original and replace the other unit. Ω: If resistance is less than some hundreds kΩ Probably cable or connector damage. Check the cable and connectors at both ends for defects or for reasons that would cause the problem. Remeasure DC resistance, now with both cable ends disconnected. The resistance should be “open circuit” and if not replace the entire cable run, terminating with new N-type connectors. If resistance is immeasurable (high impedance): Typically reasons are connectors not terminated correctly or cable cut. Check the cable and connectors at both ends for defects or for reasons that would cause the problem. Remeasure DC resistance, with the outer end still connected to the ODU. If still immeasurable impedance, replace the entire cable run, terminating with new N-type connectors.
354
B4008 Rev. M
Appendices
SECTION X Appendices
B4008 Rev. M
355
356
-48VDC
POWER
PWR
64kb/s V.11
2MHz SYNC (Later release)
2MHz Sync.
Phone
CALL
ALM & AUX
COLLECTIVE CALL
IDU - HSB INTFC
Slot for optional Extension Board
10 BaseT Ethernet Off the shelf standard ethernet cable
NI 2
CRITICAL
WARNING
MINOR
MAJOR
LOCAL CRAFT TERMINAL (RS232) Connector : D-SUB 9-PIN MALE Cable : UWMK3123
LCT
NI 1
NETWORK INTERFACE (RS485) Connector : D-SUB 9-PIN FEMALE Cable : UWMK3078 , UWMK3079
ALARM & AUXILLARY FUNCTIONS Connector : D-SUB 25-PIN FEMALE Cable : UWMK3076
Hot Standby Interconnection Connector : 68-PIN VHDCI receptacle Cable : 87W5066-1A
155 Mb/s LINE
Slot for optional Line Interface Plug-In Board Ref. Fig. X-6
SERVICE CHANNEL EXTENSION 2 Connector : RJ-45 8-PIN Cable : 87W5097-1A
SVCE 10BaseT Ext. 2 LAN
64kb/s 2Mb/s SVCE G.703 Wayside Ext. 1
64kbit/s SERVICE CHANNEL (V.11) Connector : RJ45 8-PIN Cable : UWMK3077
POWER Connector : PO WER D-SUB 2-PIN Cable : UWMK5051
ODU INTERFACE N-TYPE FEMALE
SAFETY GROUND
PHONE Connector : RJ-45 8-PIN Kit : 4CZ5
SERVICE CHANNEL EXTENSION 1 Connector : RJ-45 8-PIN Cable : 87W5097-1A
Appendix I:
64kbit/s SERVICE CHANNEL (G.703) Connector : RJ45 8-PIN Cable : UWMK3077
2Mbit/s WAYSIDE CHANNEL Connector : RJ45 8-PIN Cable : 87W5097-2A, 10m patch cable
CityLink
IDU / HSB-IDU Interface Description
Figure X-1 CityLink IDU
B4008 Rev. M
B4008 Rev. M
-48VDC
POWER 2
POWER 1
1 2
PWR
64kb/s V.11
2MHz SYNC (Later release)
2MHz Sync.
Phone
CALL
ALM & AUX
COLLECTIVE CALL
IDU - HSB INTFC
Slot for optional Extension Board
SERVICE CHANNEL EXTENSION 2 Connector : RJ-45 8-PIN Cable : 87W5097-1A
10 BaseT Ethernet Off the shelf standard ethernet cable
RX DIR.A
TX DIR.B
TX DIR.A
RX DIR.B
WARNING
MINOR
MAJOR
CRITICAL
LOCAL CRAFT TERMINAL (RS232) Connector : D-SUB 9-PIN MALE Cable : UWMK3123
LCT
NI 2
NI 1
NETWORK INTERFACE (RS485) Connector : D-SUB 9-PIN FEMALE Cable : UWMK3078 , UWMK3079
ALARM & AUXILLARY FUNCTIONS Connector : D-SUB 25-PIN FEMALE Cable : UWMK3076
Hot Standby Interconnection Connector : 68-PIN VHDCI receptacle Cable : 87W5066-1A
155 Mb/s LINE
Slot for optional Line Interface Plug-In Board Ref. Fig. X-6
PHONE Connector : RJ-45 8-PIN Kit : 4CZ5
SERVICE CHANNEL EXTENSION 1 Connector : RJ-45 8-PIN Cable : 87W5097-1A
SVCE 10BaseT Ext. 2 LAN
64kb/s 2Mb/s SVCE G.703 Wayside Ext. 1
64kbit/s SERVICE CHANNEL (V.11) Connector : RJ45 8-PIN Cable : UWMK3077
POWER Connector : POWER D-SUB 2-PIN Cable : UWMK5051
SAFETY GROUND
64kbit/s SERVICE CHANNEL (G.703) Connector : RJ45 8-PIN Cable : UWMK3077
2Mbit/s WAYSIDE CHANNEL Connector : RJ45 8-PIN Cable : 87W5097-2A, 10m patch cable
Appendices
Figure X-2 CityLink HSB-IDU
357
358
-48VDC
POWER
PWR
64kb/s V.11
2MHz SYNC (Later release)
64kbit/s SERVICE CHANNEL (V.11) Connector : RJ45 8-PIN Cable : UWMK3077
2MHz Sync.
Phone SIGNAL
CALL
Not used for CityLink Fast Ethernet
COLLECTIVE CALL
IDU - HSB INTFC
10Base-T/100Base-TX
Not used for CityLink Fast Ethernet
SERVICE CHANNEL EXTENSION 2
10BaseT Ethernet Off the shelf standard ethernet cable
NI 2
NI 1
WARNING
MINOR
MAJOR
CRITICAL
LOCAL CRAFT TERMINAL (RS232) Connector : D-SUB 9-PIN MALE Cable : UWMK3123
Not used for CityLink Fast Ethernet
NETWORK INTERFACE (RS485)
LCT
SIGNAL
ALARM & AUXILLARY FUNCTIONS Connector : D-SUB 25-PIN FEMALE Cable : UWMK3076
ALM & AUX
T1/E1
TRIBUTARY T1/E1 INTERFACE (2Mbit/s or 1.5Mbit/s) Connector : RJ45 8-PIN Cable : 87W5097-2A, 10m patch cable
10Base-T/100Base-TX Ethernet Off the shelf shielded twisted pair ethernet cable
Hot Standby Interconnection Not used for CityLink Fast Ethernet
155 Mb/s LINE
Slot for optional Line Interface Plug-In Board Ref. Fig. X-6
Not used for CityLink Fast Ethernet
PHONE
Not used for CityLink Fast Ethernet
SERVICE CHANNEL EXTENSION 1
SVCE 10BaseT Ext. 2 LAN
64kb/s 2Mb/s SVCE G.703 Wayside Ext. 1
POWER Connector : PO WER D-SUB 2-PIN Cable : UWMK5051
ODU INTERFACE N-TYPE FEMALE
ODU
SAFETY GROUND
64kbit/s SERVICE CHANNEL (G.703) Connector : RJ45 8-PIN Cable : UWMK3077
2Mbit/s WAYSIDE CHANNEL Connector : RJ45 8-PIN Cable : 87W5097-2A, 10m patch cable
CityLink
Figure X-3 CityLink Fast Ethernet IDU
B4008 Rev. M
Appendices
G.703 INP OUT
155 Mbit/s STM-1 Ω G.703, 75Ω Connector : DIN47297, 1.0/2.3mm Cable : UWMH3080
CAT-5 UTP
INP
155 Mbit/s STM-1 CAT-5, UTP Connector: RJ45 (FCC-8 compl.), 8-pin Connector Cable alt.1: 87W5111-CAT5E02S, 2m straight patch cable Cable alt.2: 87W5111-CAT5E02C, 2m crossed patch cable
MM Fiber
INP
1310 nm MMF Optical Interface Connector: MT-RJ Cable: 87W5078-SCxx/MTRJxx/STxx/FCxx
SM Fiber OUT INP
INP
1310 nm SMF and 1550 nm SMF Optical Interface Connector: LC Cable: 87W5080-SCxx/LCxx/FCxx
Figure X-4 B4008 Rev. M
Optional Line Interface Plug-in Boards 359
CityLink Optional Extension Boards 21x2Mbit/s Extension Board: TRIBUTARY
STM1 Extension Board: G.703 INP OUT
Line Extension STM1 / STS-3 (155Mb/s)
DS3/E3 Extension Board: SIGNAL 0 1 2 3
Figure X-5
360
DS1-0
DS3/E3-1
OUT
IN
DS3/E3-2
OUT
IN
DS3/E3-3
OUT
IN
Optional Extension Boards Boards
B4008 Rev. M
Appendices Power Connector
0V STATION GROUND (FEMALE ) IN DOOR UNIT'S FRONT VIEW
-48VDC (MALE ) Figure X-6 IDU Power Connector Pinout
RJ-45 Connectors With reference to Figure X-7, several connector pin-outs will be described. Note that the upper connector pins are reversed with respect to the lower connector pins, i.e. the lower plug is “mirrored”. Refer to Figure X-1-3 for location of 2-by-4 port RJ-45. IN DOOR UNIT'S FRONT VIEW Pin no. 8
Pin no. 1
U
L
A
B
Pin no. 8
C
D
Pin no. 1
Figure X-7 RJ-45 (P5001A-D) connector detail.
B4008 Rev. M
361
CityLink 64kbit/s G.703 Jack, RJ-45 Connector Pin. no: 1UA 2UA 3UA 4UA 5UA 6UA 7UA 8UA Table X-1
Function: TxD- (Neg. Tx. data) TxD+ (Pos. Tx. data) TxC+ (Pos. Tx. clock) TxC- (Neg. Tx. clock) RxD+ (Pos. Rx. data) RxD- (Neg. Rx. data) RxC+ (Pos. Rx. clock) RxC- (Neg. Rx. clock) 64kbit/s G.703 Jack, 8-PIN Pinout
64kbit/s V.11 Jack, RJ-45 Connector Pin. no: 1LA 2LA 3LA 4LA 5LA 6LA 7LA 8LA
Function: TxD- (Neg. Tx. data) TxD+ (Pos. Tx. data) TxC- (Neg. Tx. clock) TxC+ (Pos. Tx. clock) RxD- (Neg. Rx. data) RxD+ (Pos. Rx. data) RxC- (Neg. Rx. clock) RxC+ (Pos. Rx. clock)
Table X-2 64kbit/s V.11 Jack, 8-PIN Pinout
2Mbit/s Wayside Jack, RJ-45 Connector Pin. no: 1UB 2UB 3UB 4UB 5UB 6UB 7UB 8UB Table X-3 362
Function: IND+ (Pos. Rx. data) IND- (Neg. Rx. data) shield OUTD+ (Pos. Tx. data) OUTD- (Neg. Tx data) shield Not Connected Not Connected 2Mbit/s Wayside Jack, 8-PIN Pinout B4008 Rev. M
Appendices 2.048 MHz SYNC Jack, RJ-45 Connector Pin. no: 1LB 2LB 3LB 4LB 5LB 6LB 7LB 8LB
Function: INP+ (Pos. Rx. pulse) INP- (Neg. Rx. pulse) shield OUTP+ (Pos. Tx. pulse) OUTP- (Neg. Tx pulse) shield Not Connected Not Connected
Table X-4 2.048 MHz SYNC Jack, 8-PIN Pinout
Service Channel Extension 1 and 2 Jacks, RJ-45 Connector Pin. no: 1UC 2UC 3UC 4UC 5UC 6UC 7UC 8UC
Function: OE1_INP_A OE1_INP_B OE1_OUT_A OE1_OUT_B CALL_INP CALL_OUT CTRL_INP CTRL_OUT
Table X-5 Service Channel Extension 1 Jack, 8-PIN Pinout Pin. no: 1LC 2LC 3LC 4LC 5LC 6LC 7LC 8LC
Function: OE2_INP_A OE2_INP_B OE2_OUT_A OE2_OUT_B CALL_INP CALL_OUT CTRL_INP CTRL_OUT
Table X-6 Service Channel Extension 2 Jack, 8-PIN Pinout
B4008 Rev. M
363
CityLink Service Phone Jack, RJ-45 Connector Pin. no: 1UD 2UD 3UD 4UD 5UD 6UD 7UD 8UD Table X-7
Function: Not Connected Not Connected TELA MIC+ MICTELB Not Connected LOOP_OE Service Phone Handset Connector, 8-PIN Pinout
10Base-T (“TP-LAN”) Jack, RJ-45 Connector (normal) Pin. no: 1LD 2LD 3LD 4LD 5LD 6LD 7LD 8LD
Function: TPTX+ (Pos. Tx. data) TPTX- (NEG. Tx. data) TPRX+ (Pos. Rx. data) Not Connected Not Connected TPRX- (Neg. Rx. data) Not Connected Not Connected
Table X-8 10Base-T, 8-PIN Pinout
10Base-T / 100Base-TX Jack, RJ-45 Connector (uplink) (Used only in Fast Ethernet configuration) Pin. no: 1LD 2LD 3LD 4LD 5LD 6LD 7LD 8LD
Function: TPRX+ (Pos. Rx. data) TPRX- (NEG. Rx. data) TPTX+ (Pos. Tx. data) Not Connected Not Connected TPTX- (Neg. Tx. data) Not Connected Not Connected
Table X-9 10Base-T / 100Base-TX, 8-PIN Pinout 364
B4008 Rev. M
Appendices IDU to HSB Interface Connector The connector is 68 pin VHDCI receptacle. This is a shielded connector type and the screen is terminated to chassis ground. PIN Pos.34 34
PIN Pos. 11
IN DOOR UNIT'S FRONT VIEW Pos.35 35 PIN
Figure X-8
IDU to HSB-IDU Interface Connector
NI1 and NI2, Network Interface Connector Detail PIN 5
PIN 1 IN DOOR UNIT'S FRONT VIEW
PIN 9
PIN 6
Figure X-9 “NI1” and “NI2” D-SUB 9 PIN Pinout NI1 and NI2 D-SUB 9-PIN FEMALE 1 2 3
Signal Name
Signal Description
RxDRxD+ GND
4 5 6 7 8 9
TxD+ TxDRxCRxC+ TxC+ TxC-
Data Input Data Input Signal Ground. Normally this pin shall not be connected. Data Output Data Output Clock Input Clock Input Clock Output Clock Output
Table X-10 “NI1” and “NI2” D-SUB 9-PIN Pinout
B4008 Rev. M
365
CityLink ALM & AUX Connector Detail PIN 13
PIN 1 IDU FRONT VIEW
PIN 25
PIN 14 Figure X-10 “ALM & AUX” D-SUB 25-PIN Pinout ALM & AUX D-SUB 25-PIN FEMALE 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 Table X-11
Signal Name
Signal Description
USER1A USER1B USER2A USER2B USER3A USER3B USER4A USER4B ALM1 AGND ALM2 ALM3 AGND AGND ALM4 AGND ALM5 AGND ALM6 ALM7 ALM8 ERRP_V11+ ERRP_V11ERRP_OPEN_COL
Relay output 1A Relay output 1B Relay output 2A Relay output 2B Relay output 3A Relay output 3B Relay output 4A Relay output 4B Alarm input 1 (TTL level) Analog GND* Alarm input 2 (TTL level) Alarm input 3 (TTL level) Analog GND* Analog GND* Alarm input 4 (TTL level) Analog GND* Alarm input 5 (relay input) Analog GND* Alarm input 6 (relay input) Alarm input 7 (relay input) Alarm input 8 (relay input) Error pulses (V.11 output)** Error pulses (V.11 output)** Error pulses open collector output Error pulses opto coupler driver output
ERRP_OPTO
“ALM & AUX” D-SUB 15-PIN Female Pinout
* Analog GND is floating relative scussi GND. ** Selectable from NEW-NMS: B1, B2 or Trellis decoder. See Section VII Ch.4.4.5. 366
B4008 Rev. M
Appendices LCT Connector Detail
PIN 1
PIN 5 IDU FRONT VIEW
PIN 6
PIN 9
Figure X-11 “LCT” D-SUB 9 PIN male, Pinout LCT D-SUB 9-PIN MALE 1 2 3 4 5 6 7 8 9 Table X-12
B4008 Rev. M
Signal Name
Signal Description
NC RxD TxD GND NC
Not Connected City Link Data Input City Link Data Output Internally connected to pin 6 Signal ground Internally connected to pin 4 Internally connected to pin 8 Internally connected to pin 7 Not connected
“LCT” D-SUB 9-PIN Pinout
367
CityLink 21x2Mbit/s Extension board G.703 Connector Details Figures X-12 and X-13 shows the 4 connectors J1001 to J1004 and their pinout. For location of the 4 connectors on the IDU; see Figur X-5. For configuration of 21x 2.048 Mb/s input- and output- signals in connectors and cables , see Table X-13.
J1001
J1002
J1003
J1004
Figure X-12 The 21x2 Mb/s interface connectors from left to right, IDU front view. 1D
6D
IDU FRONT VIEW
1A
6A
Figure X-13 21x2Mbit/s Connector Detail
368
B4008 Rev. M
Appendices Pin no in connec -tor
Colour code of pairs in cable
Connector J1001
Connector J1002
Connector J1003
Connector J1004
2 Mb/s Ch. No
Signal
2 Mb/s Ch. No
Signal
2 Mb/s Ch. No
Signal
2 Mb/s Ch. No
Signal
1A 1B 1C 1D
White / Blue White / Orange
Ch.1 Ch.1 Ch.1 Ch.1
Input, A Input, B Output, A Output, B
Ch.7 Ch.7 Ch.7 Ch.7
Input, A Input, B Output, A Output, B
Ch.13 Ch.13 Ch.13 Ch.13
Input, A Input, B Output, A Output, B
Ch.19 Ch.19 Ch.19 Ch.19
Input, A Input, B Output, A Output, B
2A 2B 2C 2D
White / Green White / Brown
Ch.2 Ch.2 Ch.2 Ch.2
Input, A Input, B Output, A Output, B
Ch.8 Ch.8 Ch.8 Ch.8
Input, A Input, B Output, A Output, B
Ch.14 Ch.14 Ch.14 Ch.14
Input, A Input, B Output, A Output, B
Ch.20 Ch.20 Ch.20 Ch.20
Input, A Input, B Output, A Output, B
3A 3B 3C 3D
Red / Blue Red / Orange
Ch.3 Ch.3 Ch.3 Ch.3
Input, A Input, B Output, A Output, B
Ch.9 Ch.9 Ch.9 Ch.9
Input, A Input, B Output, A Output, B
Ch.15 Ch.15 Ch.15 Ch.15
Input, A Input, B Output, A Output, B
Ch.21 Ch.21 Ch.21 Ch.21
Input, A Input, B Output, A Output, B
4A 4B 4C 4D
Red / Green Red / Brown
Ch.4 Ch.4 Ch.4 Ch.4
Input, A Input, B Output, A Output, B
Ch.10 Ch.10 Ch.10 Ch.10
Input, A Input, B Output, A Output, B
Ch.16 Ch.16 Ch.16 Ch.16
Input, A Input, B Output, A Output, B
5A 5B 5C 5D
Black / Blue Black / Orange
Ch.5 Ch.5 Ch.5 Ch.5
Input, A Input, B Output, A Output, B
Ch.11 Ch.11 Ch.11 Ch.11
Input, A Input, B Output, A Output, B
Ch.17 Ch.17 Ch.17 Ch.17
Input, A Input, B Output, A Output, B
6A 6B 6C 6D
Black/ Green Black / Brown
Ch.6 Ch.6 Ch.6 Ch.6
Input, A Input, B Output, A Output, B
Ch.12 Ch.12 Ch.12 Ch.12
Input, A Input, B Output, A Output, B
Ch.18 Ch.18 Ch.18 Ch.18
Input, A Input, B Output, A Output, B
N.c.
N.c. N.c. N.c. N.c.
N.c. N.c. N.c. N.c.
N.c. N.c. N.c.
Table X-13 Configuration of 21x 2Mbit/s input- and output- signals in connectors and cables • Input, A / Output, A, refers to the positive pulse of the signal. • Input, B / Output, B, refers to the negative pulse of the signal.
ADM STM-1 Extension Board Connectors The type and configuration of connectors used for the 155 Mbit/s customer line interface on the Extension Board are the same as used for the G.703 CMI encoded 155 Mb/s customer line interface on the main board in the IDU.
B4008 Rev. M
369
CityLink
Appendix II:
ODU Interface Description
ODU/IDU Interface ❒ N-connector female for: Transmit and Receive IF, Modem/Transceiver communication and power supply.
Branching / Antenna Interface ❒ ❒ ❒ ❒ ❒ ❒
370
PBR320 waveguide (38GHz). PBR220 waveguide (18GHz, 23GHz and 26GHz). PDR120 waveguide (for 13GHz). PBR140 waveguide (for 15GHz). PDR84 waveguide (for 7GHz and 8GHz). Grounding cable for Branching Unit.
B4008 Rev. M
Appendices
Appendix III:Alarm List & Alarm Description Alarm Name BASEBAND LOS LOF MS-AIS MS-AIS-INS MS-RDI 2M-WAYSIDE-INP 2M-WAYSIDE-AIS-INP TRELLIS-PLL RT-PLL 2M-SYNC RS-TRACE-MISMATCH LOC BASEBAND DIRECTION RADIO TO LINE LT-PLL 2M-WAYSIDE-OUTP-AIS HBER LBER EW-BER RF-ID MODULATOR IF-MOD DEMODULATOR IF-DEM OPTICAL INTERFACE TX-OUT LASER-OFF BIAS TRANSCEIVER IF-INP RF-OUT LOS-RF-INPUT RF-INPUT-WARNING LO UNIT-ALM ATPC
RF-MUTE LOOPING-IF-EN LOOPING-RF-EN
MISSING_LO_SYNCHRONIZATION LO-TUNING-WARNING HIGH_TEMP_POWER_TRANSISTOR RF_RX_LOW RF_RX_HIGH NO_CALIBRATION_DATA HSB_CABLE_BREAK RF_TX_LOW RF_TX_HIGH IF_TX_LOW IF_TX_HIGH POWER_15 POWER_NEG15 POWER_6 POWER_48
B4008 Rev. M
Description
Id
Severity
1000
MAJOR
1001 1002
MAJOR WARNING
1003 1004
MAJOR WARNING
1005 1006 1007
MINOR WARNING CRITICAL
1008 1009
CRITICAL MINOR
1010 1011
MAJOR CRITICAL
The Line Transmit 155MHz PLL is out of lock. AIS is detected on the Wayside traffic output. Indicator for BER > 1e-3 Indicator for BER > 1e-6 Indicator for BER > 1e-10 Wrong RF-ID received compared to configuration.
1100 1101 1102 1103 1104 1105
CRITICAL WARNING MAJOR MINOR WARNING MAJOR
Loss of IF 350MHz
1200
CRITICAL
Loss Of Signal: - Optical or electrical CMI Loss of Frame Alarm indication signal detected. MS termination only Alarm indication signal is inserted. Remote defect indicator detected. MS termination only 2Mbit wayside input is missing. 2Mbit wayside input AIS detected. Indicates that the Trellis coder is out of lock.(CNF35C Asic) The Sorp 38,88 MHz PLL is out of lock. Selected synchronisation for Line Transmit direction is missing. Mismatch between configured string and received string Loss of clock (SORP)
Loss of INCOMING 140MHz.
1300
CRITICAL
The output power has increased 2dB, or the analoge measurement of PO_MON is outside predefined limits The laser is off. It could be manual shutdown The laser bias is out of limits. Sign of age and degradation
1400
CRITICAL
1401 1402
WARNING WARNING
No IF into transceiver The output power is low No signal into receiver. The RF level is either above the upward fading threshold or The RF level is below the down fading threshold. Local Oscillator is out of lock. The transceiver is not responding The regulation loop for the ATPC is not working. Software generated alarm based on alarm condition on local LOF on Rx and remote LOF on Rx . The RF transmitter is muted. The transceiver looping on IF is enabled The transceiver on RF is enabled. (If near-end and far end depends on the node where alarm is reported) XPIC LO synch missing The LO needs to be tuned
1500 1501 1502 1504
CRITICAL MAJOR MAJOR WARNING
1505 1506 1507
MAJOR MAJOR MINOR
1508 1509 1510
WARNING WARNING WARNING
1511 1512 1513 1514 1515 1516 1517
CRITICAL WARNING WARNING MAJOR MAJOR MAJOR MAJOR
1518 1519 1520 1521 1522 1523 1524 1525
MAJOR MAJOR MAJOR MAJOR WARNING WARNING WARNING WARNING
No calibration data The cable between the ODUs is broken. This will cause the switch to perform the TX-switching.
371
CityLink Alarm Name SYNTH_HEADER SHF_LO UHF_TX_LO UHF_RX_LO DUPLEX_LO VHF_LO TX_SWITCH_MAN OTHER ALM MEN-AT-WORK DROP-IN+48V BELOW+3.3V BELOW+5V BELOW-5V OVER-CURRENT WAYSIDE-LOOP FE WAYSIDE-LOOP NE PRBS-INSERTED LOOPING_EN EVENT-LOG-EXC-LIMIT DOWNLOAD-IN-PROGRESS NEED_FREQUENCY SECURITY-LOG-EXC-LIMIT 64K-LOOPING-1 64K-LOOPING-2 RTC-LOW BATTERY
BELOW+48V BELOW+11V BELOW+15V BELOW-15V MISSING-CALIBRATION-DATA FAN-ALARM DEFAULT_SYSTEM_PARAMETERS DEFAULT_ANALOGE_PARAMETERS FAN2-ALARM HSB-RELAY IDUA-ACTIVE IDUB-ACTIVE HSB-MANUAL CHANNEL-ACTIVE NEED-SW BOOT-MONITOR-IN-USE BOOT-HW-ERROR-DETECTED IDU_A_NEEDS_SW IDU_B_NEEDS_SW HDLC_LOC_A HDLC_LOC_B HDLC_LOC DROP-IN-48V-A DROP-IN-48V-B AUXILIARY ALARMS EXTERN-ALARM-1
EXTERN-ALARM-2 EXTERN-ALARM-3 EXTERN-ALARM-4
372
Description
Software generated. Operator set men at work before doing repairs. The battery supply voltage is dropped below acceptable limit Voltage from the DC-DC converter below limit Voltage from the DC-DC converter below limit Voltage from the DC-DC converter below limit Detects short current on ODU cable. Wayside looping Far End Wayside looping Near End PRBS inserted in wayside Looping enabled Event log has exceeded the capacity threshold Download of software is under progress. A RF unit need to be configured with Tx and Rx frequency. Security log has exceeded the capacity threshold 64 kb channel looping Channel1 64 kb channel looping Channel2 The battery that powers the Real Time clock is low
Voltage from the DC-DC converter below limit Voltage from the DC-DC converter below limit Voltage from the DC-DC converter below limit Voltage from the DC-DC converter below limit Modem or transceiver are missing their calibration data in flash No system configuration stored in NV config, using default (stm1,128TCM,28kHz) No analoge configuration stored in flash, using predefined defaults. IDUswitch/Transceiver relay mismatch Idu A is active in receiving direction Idu B is active in receiving direction The iduswitch is operated manually This ODU is active Board needs SW The transceiver is in boot monitor mode Errors detected by boot code when startup. Reported to app. code Reported from the IDU A Reported from IDU B The IDU switch has no RX-clock on port A The IDU switch has no RX-clock on port B The IDU(either A or B) has no RX-clock The IDU switch power source 1 has a drop The IDU switch power source 2 has a drop
Multipurpose port. Configured as Alarm Output, Alarm Input or Remote Control. External alarm reported if port configured as alarm input. Alarm name configurable from management system. ref External alarm 1 ref External alarm 1 ref External alarm 1
Id 1526 1527 1528 1529 1530 1531 1532
Severity MAJOR MAJOR MAJOR MAJOR MAJOR MAJOR WARNING
2000
WARNING
2001
WARNING
2002 2003 2005 2006 2007 2008 2009 2010 2011 2012 2013
WARNING WARNING WARNING MAJOR WARNING WARNING WARNING WARNING WARNING WARNING MAJOR
2014 2015 2016 2017
2020 2022 2023 2024 2032
WARNING WARNING WARNING WARNING/ MINOR on NL2000 WARNING WARNING WARNING WARNING MAJOR
2034 2035
WARNING CRITICAL
2036
MAJOR
2037 2200 2201 2202 2203 2216 2221 2224 2225
WARNING CRITICAL INFO INFO WARNING INFO MAJOR WARNING MINOR
2226 2227 2228 2229 2230 2231 2232
WARNING WARNING MAJOR MAJOR MAJOR MAJOR MAJOR
2500
WARNING
2501 2502 2503
WARNING WARNING WARNING
B4008 Rev. M
Appendices Alarm Name EXTERN-ALARM-5 EXTERN-ALARM-6 EXTERN-ALARM-7 EXTERN-ALARM-8 OUTPUT-ALARM-1 OUTPUT-ALARM-2 OUTPUT-ALARM-3 OUTPUT-ALARM-4 SEVERITY ALARMS CRITICAL-ALARM
MAJOR-ALARM
MINOR-ALARM
WARNING-ALARM
PERFORMANCE ALARMS G826-THRESHOLD-15MIN-B1
G826-THRESHOLD-15MIN-B2
G826-THRESHOLD-15MIN-REI
G826-THRESHOLD-24Hour-B1
G826-THRESHOLD-24HOUR-B2
G826-THRESHOLD-24HOUR-REI
G826-THRESHOLD-MONTH-B1
G826-THRESHOLD-MONTH_B2
G826-THRESHOLD-MONTH-REI
TRESHOLD-15MIN-OOF
TRESHOLD-24HOUR-OOF
TRESHOLD-MONTH-OOF
HIGHER ORDER POH ALARMS HP-RDI HP-TIM
B4008 Rev. M
Description ref External alarm 1 ref External alarm 1 ref External alarm 1 ref External alarm 1 Output alarm reported if auxilary output port configured as alarm output. ref Output alarm 1 ref Output alarm 1 ref Output alarm 1 For alarm output function If any alarms with severity set to critical, this alarm is raised. This can be combined in the alarm output expression. If any alarms with severity set to major, this alarm is raised. This can be combined in the alarm output expression. If any alarms with severity set to minor, this alarm is raised. This can be combined in the alarm output expression. If any alarms with severity set to warning, this alarm is raised. This can be combined in the alarm output expression. All software generated If the current 15 minute period exceeds the set threshold for B1, this alarm is set(period 1). After a whole period has expired without exceeding the alarm threshold(period 2), the alarm will be cleared when the next period starts(period 3). If the current 15 minute period exceeds the set threshold for B2, this alarm is set. Ref. G826-THRESHOLD-15MINB1 for method of clearing. Only for MS termination. If the current 15 minute period exceeds the set threshold for REI, this alarm is set. Ref. G826-THRESHOLD15MIN-B1 for method of clearing. Only for MS termination. If the current 24 hour period exceeds the set threshold for B1, this alarm is set. Ref. G826-THRESHOLD-15MIN-B1 for method of clearing. If the current 24 hour period exceeds the set threshold for B2, this alarm is set. Ref. G826-THRESHOLD-15MIN-B1 for method of clearing. Only for MS termination. If the current 24 hour period exceeds the set threshold for REI, this alarm is set. Ref. G826-THRESHOLD-15MINB1 for method of clearing. Only for MS termination. If the current month period exceeds the set threshold for month, this alarm is set. Ref. G826-THRESHOLD-15MINB1 for method of clearing. If the current month period exceeds the set threshold for month, this alarm is set. Ref. G826-THRESHOLD-15MINB1 for method of clearing. Only for MS termination. If the current month period exceeds the set threshold for REI, this alarm is set. Ref. G826-THRESHOLD-15MIN-B1 for method of clearing. Only for MS termination. If the current 15 minute period exceeds the set threshold for OOF, this alarm is set. Ref. G826-THRESHOLD15MIN-B1 for method of clearing. If the current 24 hour period exceeds the set threshold for OOF, this alarm is set. Ref. G826-THRESHOLD-15MINB1 for method of clearing. If the current month period exceeds the set threshold for month, this alarm is set. Ref. G826-THRESHOLD-15MINB1 for method of clearing. Description Higher order Path Remote Defect Indicator Higher order Path Trace Identifier Mismatch
Id 2504 2505 2506 2507 2550
Severity WARNING WARNING WARNING WARNING INFO
2551 2552 2553
INFO INFO INFO
2600
NA
2601
NA
2602
NA
2603
NA
3000
WARNING
3001
WARNING
3002
WARNING
3003
WARNING
3004
WARNING
3005
WARNING
3006
WARNING
3007
WARNING
3008
WARNING
3015
WARNING
3016
WARNING
3017
WARNING
5050 5054
WARNING MAJOR
373
CityLink Fast Ethernet Alarms Alarm Name FTP_USER_LOGGED_IN ILLEGAL_DATE_OR_TIME IDU_TEMPERATURE1_HIGH IDU_TEMPERATURE2_HIGH FAN1_MANUAL_STOP FAN2_MANUAL_STOP FAN1_NOT_RUNNING FAN2_NOT_RUNNING I2C_BUS_FAILURE BASEBAND_DEVICE_INIT_FAILURE MODEM_DEVICE_INIT_FAILURE EEB_DEVICE_INIT_FAILURE COMMAND_LINE_INIT_FAILURE CONSOLE_USER_LOGGED_IN TELNET_USER_LOGGED_IN ETHERNET_PORT_1 ETHERNET_PORT_2 ETHERNET_PORT_3 ETHERNET_PORT_4 LOS_2MBIT_PORT_1 LOS_2MBIT_PORT_2 LOS_2MBIT_PORT_3 LOS_2MBIT_PORT_4 AIS_INPUT_2MBIT_PORT_1 AIS_INPUT_2MBIT_PORT_2 AIS_INPUT_2MBIT_PORT_3 AIS_INPUT_2MBIT_PORT_4 AIS_OUTPUT_2MBIT_PORT_1 AIS_OUTPUT_2MBIT_PORT_2 AIS_OUTPUT_2MBIT_PORT_3 AIS_OUTPUT_2MBIT_PORT_4 AIS_INSERT_2MBIT_PORT_1_RX AIS_INSERT_2MBIT_PORT_2_RX AIS_INSERT_2MBIT_PORT_3_RX AIS_INSERT_2MBIT_PORT_4_RX LOC_RT LOC_RR LOC_LT LOC_LR LOS_RR LOF_RR MS-AIS_RR MS-AIS_INSERT_RR MS-RDI_RR LOS_LR LOF_LR MS-AIS_LR MS-AIS_INSERT_LR MS-RDI_LR MS-AIS_INSERT_RT MS-AIS_INSERT_LT RS-TRACE-MISMATCH_RR RS-TRACE-MISMATCH_LR LOOP_MAIN LOOP_WAYSIDE LOOP_64K SW_UPDATE_IN_PROGRESS FREQUENCY_SHIFT
374
Description FTP user logged in Illegal Date or Time SU Temperature 1 (CPU) exceeded high limitWARNING SU Temperature 2 (DC/DC) exceeded high limit SU Fan 1 is set in manual stop SU Fan 2 is set in manual stop SU Fan 1 is not running SU Fan 2 is not running SU internal problem at I2C bus There was a hardware error in the baseband module during startup of the IDU There was a hardware error in the modem module during startup of the IDU There was a hardware error in the ethernet extension board module during startup of the IDU There was a hardware error in the command line interface module during startup of the IDU A user is currently using the command-line interface shell on the IDU via the LCT port A user is currently using the command-line interface shell on the IDU via the telnet EEB Port 1 link lost. EEB Port 2 link lost. EEB Port 3 link lost. EEB Port 4 link lost. EEB LOS port 1. EEB LOS port 2. EEB LOS port 3. EEB LOS port 4. EEB AIS input port 1. EEB AIS input port 2. EEB AIS input port 3. EEB AIS input port 4. EEB AIS output port 1. EEB AIS output port 2. EEB AIS output port 3. EEB AIS output port 4. EEB AIS insert port 1 input. EEB AIS insert port 2 input. EEB AIS insert port 3 input. EEB AIS insert port 4 input. Loss of clock in the RT module of the baseband unit (SORP) Loss of clock in the RR module of the baseband unit (SORP) Loss of clock in the LT module of the baseband unit (SORP) Loss of clock in the LR module of the baseband unit (SORP) Loss of signal on radio receive (RR) Loss of frame on radio receive (RR) Alarm indication signal detected on radio receive (RR) Alarm indication signal is inserted on radio receive (RR) Remote defect indicator detected on radio receive (RR) Loss of signal on line receive (LR): - optical or electrical CMI. Loss of frame on line receive (LR) Alarm indication signal detected on line receive (LR) Alarm indication signal is inserted on line receive (LR) Remote defect indicator detected on line receive (LR) Alarm indication signal is inserted on radio transmit (RT) Alarm indication signal is inserted on line transmit (LT) Mismatch between configured string and received string (RR) Mismatch between configured string and received string (LR) Main traffic looping is active Wayside channel looping is active 64 kb/s channel looping is active A software update is in progress A frequency shift is in progress
Id 32768 32770 32771
Severity NORMAL WARNING
32772 32773 32774 32775 32776 32777 32778
WARNING WARNING WARNING MAJOR MAJOR WARNING MAJOR
32779
MAJOR
32780
MAJOR
32781
WARNING
32782
NORMAL
32783
NORMAL
32784 32785 32786 32787 32788 32789 32790 32791 32792 32793 32794 32795 32796 32797 32798 32799 32800 32801 32802 32803 32804
NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL NORMAL WARNING WARNING WARNING WARNING WARNING WARNING WARNING WARNING WARNING WARNING WARNING WARNING CRITICAL
32805
CRITICAL
32806
CRITICAL
32807
CRITICAL
32808 32809 32810 32811 32812 32813
MAJOR MAJOR WARNING MAJOR WARNING MAJOR
32814 32815 32816 32817 32818
MAJOR WARNING WARNING WARNING MAJOR
32819 32820
MAJOR MAJOR
32821
MAJOR
32822 32823 32824 32825 32826
WARNING WARNING WARNING WARNING WARNING
B4008 Rev. M
Appendices Alarm Name BELOW_11V_ODU BELOW_3.3V_ODU BELOW_48V_ODU BELOW_-15V_ODU BELOW_15V_ODU BELOW_5V_ODU FAN_ODU FAN2_ODU RX-LO TX-LO RX-LO-TUNING-WARNING TX-LO-TUNING-WARNING NEED-RX-DRO-TUNING NEED-TX-DRO-TUNING IDU-RESTARTED NETWORK-INTERFACE-CHANGED TRIBUTARY ALARMS AIS-1 AIS-2
M AIS-84 SIGNAL-LABEL-MISMATCH-1
SIGNAL-LABEL-MISMATCH-2
M SIGNAL-LABEL-MISMATCH-84 LOS-1 LOS-2
M LOS-84 LP-RDI-1 LP-RDI-2
M
WARNING WARNING WARNING WARNING WARNING MAJOR MAJOR WARNING WARNING WARNING WARNING INFO INFO
Alarm Indication Signal detected in VC-12 #1. Ref: AIS-1
4200 4201
WARNING WARNING
M Ref: AIS-1 Signal Label Mismatch detected on VC-12 #1. Is set when the signal label in the LO-POH is set to unequipped. Ref: SIGNAL-LABEL-MISMATCH-1
M Ref: SIGNAL-LABEL-MISMATCH-1 Loss Of Signal in VC-12 #1. Ref: LOS-1
M M Ref: LP-RDI-1 Low order Path Remote Failure Indication in VC-12 #1. Ref: LP-RFI-1
M
B4008 Rev. M
IDU has been Restarted Changed has been made to the network interface
Id 32827 32828 32829 32830 32831 32832 32833 32834 32835 32836 32837 32838 32839 32840 32841 32842
Ref: LOS-1 Low order Path Remote Defect Indication in VC-12 #1. Ref: LP-RDI-1
LP-RDI-84 LP-RFI-1 LP-RFI-2
LP-RFI-84
Description Voltage from the DC-DC converter below limit Voltage from the DC-DC converter below limit Voltage from the DC-DC converter below limit Voltage from the DC-DC converter below limit Voltage from the DC-DC converter below limit Voltage from the DC-DC converter below limit
M Ref: LP-RFI-1
M 4283 4284
4285
M 4367 4368 4369
M 4451 4452 4453
M 4535 4536 4537
M 4619
Severity WARNING WARNING
M WARNING
WARNING
M WARNING MAJOR MAJOR
M MAJOR WARNING WARNING
M WARNING WARNING WARNING
M WARNING
375
View more...
Comments