MEDUIM VOLTAGE CABLE SIZING 1- Assumptions: 1.1 Minimum cable size for Meduim Voltage feeders is 50 sq.mm 1.2 Circuit breaker tripping time on short circuit is 200ms. 1.3 Constant reflecting conductor material constant and temperature rise during short circuit condition is 143 for XLPE. 1.4 As per client requirement, cable sizes above 185 sq.mm shall be single core installed in trefoil. 1.5 Starting current for medium voltage motors are equals to 5 times the full load current. 2- References: 2.1 Electrical design basis specification no.. 24613-200-3DR-E12F-00001. 2.2 PIRELLI Cables catalogue for 300V-33000V cables 3- Calculations 3.1 Medium Voltage Cable size based on short circuit current check: Table below reflects the designed cable sizes for diffirent effective short circuit current values. Ieffective (KA) 10 16 20 25 31.5 40 50 65 80
3.2 Medium Voltage cable size based on current carrying capacity check: Table below reflects the designed cable sizes based on the maximum premissible current through the MV cable after consideration of de-rating factor. cable size (sq.mm) 3 x 50 3 x 70 3 x 95 3 x 120 3 x 150 3 x 185 3(1 x 240) 3(1 x 300)
3.3 Medium Voltage power feeder cable size based on voltage drop check: a) Table below reflects the designed cable sizes based on the maximum premissible voltage drop for the medium voltage power feeders. cable size (sq.mm) 3 x 50 3 x 70 3 x 95 3 x 120 3 x 150 3 x 185 3(1 x 240) 3(1 x 300)
R (uohm/m) 494 343 248 196 159 128 98 80
X Voltage (uohm/m) (kVolts) 107 3.3 101 3.3 95.3 3.3 92.2 3.3 89.9 3.3 87.3 3.3 105 3.3 103 3.3