MRA4 woodwards relay

Share Embed Donate


Short Description

Multifunctional relay...

Description

MRA4 – Modbus HighPROTEC Data point list

Manual DOK-TD-MRA4MDE

Table of Contents MODBUS PARAMETERS.................................................................................................................................................................................................................3 Notes for the SCADA-System.......................................................................................................................................................................................................................4

SPECIFIC MODBUS FUNCTION CODES..............................................................................................................................................................................................5 Setting Date and Time...................................................................................................................................................................................................................................9 Supported MODBUS- Error Messages.......................................................................................................................................................................................................10

APPENDIX - DATA POINT LISTS....................................................................................................................................................................................................11 Signals........................................................................................................................................................................................................................................................11 Measuring values......................................................................................................................................................................................................................................101 Commands...............................................................................................................................................................................................................................................127 Settings.....................................................................................................................................................................................................................................................131

df79bde05d011db5d77e5c14aeae1dcd 5c39a8d1ecbf065b52d82dea56a335ef RMS_Handoff: ? Datei: ? This Manual is valid for version : Build: 10569 1.7.b

Page 2

EN MRA4 Modbus 05/10

Modbus Parameters

Modbus Parameters For the Modbus Protocol several parameters have to be set which are relevant for the communication between the control system (SCADA) and the device. The parameters and their setting possibilities or value ranges are shown in the table below. ATTENTION! The Parameters are described within the appendix of the device manual (chapter Modbus).

EN MRA4 Modbus 05/10

Page 3

Modbus Parameters

Notes for the SCADA-System When using Modbus RTU the following times have to be considered by the control system and are fixed within the device : The dwell times (tD ) before start of a telegram must at least be set to 3.5 characters. Examples: 3.5 characters 9600 Baud = 4 ms 3.5 characters 19200 Baud = 2 ms 3.6 3.5 characters 38400 Baud = 1 ms Start of a new telegram is expected when the dwell time (tD ) is > 3.5 characters. The fact that the probability of disruptions during transmission of a telegram increases with its length has to be taken into duly consideration and thus a query to the Slave should be possibly such that the response telegram is not much longer than 32 Byte.

Page 4

EN MRA4 Modbus 05/10

Specific Modbus Function Codes

Specific Modbus Function Codes For reading out data from the device or to carry out commands, the services listed in the table, also called »Function Codes«, are supported. Functioncode 3

Designation

Description

Read Holding Registers

4 5

Read Input Registers Write single Output (Bit)

There are single or several data words read as from a specific data word address. Only status addresses and parameter addresses can be read. There are single or several data words read as from a specific data word address. Only measuring values can be read. All other values are illegal and will not affect the output. Via this function code acknowledgments can be executed as well as counters reseted or blockings set. Test function for the communication system There are single or several data words written as from a specific data word address.

8 Loopback Test 16 Load Multiple Registers Table 3.1: function codes

EN MRA4 Modbus 05/10

Page 5

Specific Modbus Function Codes On the following pages the Modbus functions are described in detail: Function-Code 3/4: Query Slave address

3/4

Register address HI

Register address LO

Register number HI

Register number LO

Check-sum HI

Check-sum LO

Response Slave address

3/4

Byte number

Register 0 HI

Register 0 LO

...

Check-sum HI

Check-sum LO

Register address (HI*256 + LO) The data word address from where reading should start. Register number (HI*256 + LO) Number of data words to be read. Valid range: 1..125 Byte number Number of subsequent Bytes containing data words. Register Data words read out of the device (Highbyte and Lowbyte).

Page 6

EN MRA4 Modbus 05/10

Specific Modbus Function Codes Function Code 5: Query Slave address

5

Register address HI

Register address LO

Register data HI

Register data LO

Check-sum HI

Check-sum LO

Response Slave address

5

Register address HI

Register address LO

Register data HI

Register data LO

Check-sum HI

Check-sum LO

Register address (HI*256 + LO) Data word address to be written Register data Value of the data word to be written (Highbyte and Lowbyte). Permitted value range : FF00 hex request for a single bit to be on: This often means to reset a counter, execute acknowledgments or set blockings signals. 0000 hex request for a single bit to be off: This often means to deactivate blocking signals or to reset single bits.

Function Code 8: Query Slave address

8

Data Diag Code HI 0x00

Data Diag Code LO 0x00

Test data

Test data

Check-sum HI

Check-sum LO

Response Slave address

8

Data Diag Code HI

Data Diag Code LO

Test data

Test data

Check-sum HI

Check-sum LO

Data Diag Code HI (high), Data Diag Code LO ( Low) Diagnostic Code (subfunction code of function code 8) for testing the communication system. The Diagnostic Code „Return Query Data“ (0x00, 0x00) is being supported. Test Data By using the Diagnostic Code 0x00 0x00, the transmitted data is sent back to the Master unchanged.

EN MRA4 Modbus 05/10

Page 7

Specific Modbus Function Codes Function Code 16: Query Slave address Response Slave address

16

Register address HI 16

Register address LO

Register number HI

Register address HI

Register number LO

Register address LO

Byte number Register 0 HI

Register number HI

Register 0 LO

Register number LO

...

Check-sum HI

Check-sum HI

Check-sum LO

Check-sum LO

Register address (HI*256 + LO) Data word address as from where writing should start. Register number (HI*256 + LO) Query: Number of data words to be written. Valid range: 1..123 Response: Number of data words written. Byte number Number of subsequent Bytes to contain data words. Register Data words read out of the device (Highbyte und Lowbyte).

Page 8

EN MRA4 Modbus 05/10

Specific Modbus Function Codes

Setting Date and Time Date and time can be set by means of function code 16 and read with function code 3. If the device address 0 (broadcast address) is selected, the times of all devices connected to this bus are simultaneously reset. The devices do not respond to a broadcast command.

EN MRA4 Modbus 05/10

Page 9

Specific Modbus Function Codes

Supported MODBUS- Error Messages Exception Response Telegrams are described within the general “Modbus Application Protocol Specification". An exception response table with examples is shown there. For the device we want to supply more information on these. The table below contains just the actually used codes. In case the device has recognized an error it will react in the following way: Exception Code 1 2 3 4

Designation

Description

Illegal Function Illegal Data Address Illegal Data Value Slave Device Failure

The message received includes a function code which is not supported by the Slave. Access was sought on a data word address not included in the data module. The received message contains an invalid data structure (e.g. wrong number of data bytes). An unrecoverable error occurred while the server (or slave) was attempting to perform the requested action.

The response given by the device in a failure case has the following format: Slave Address

0x80 + Function Code

Exception Code

Checksum HI

Checksum LO

In the second Byte of the response the Function Code is sent with the highest Bit set to 1. This is equivalent to an addition by 0x80. The third Byte holds the Exception Code of the error message.

Page 10

EN MRA4 Modbus 05/10

Appendix - Data Point Lists

Appendix - Data Point Lists Signals Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

1

1

3

Struct

1

1

3

Bit

Bit Mask

Unit

Description

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Signal: active

-

Signal: External Blocking

-

Signal: GeneralAlarm L1

-

Signal: GeneralAlarm L2

-

Signal: GeneralAlarm L3

-

Signal: GeneralAlarm - Earth fault

-

Signal: General Alarm

/ (Bit Position)

Functions Prot ExBlo1-I

0x1 (1)

ExBlo2-I

1

1

3

Bit

0x2 (2)

active

1

1

3

Bit

0x4 (3)

ExBlo

1

1

3

Bit

0x8 (4)

Alarm L1

1

1

3

Bit

0x10 (5)

Alarm L2

1

1

3

Bit

0x20 (6)

Alarm L3

1

1

3

Bit

0x40 (7)

Alarm G

1

1

3

Bit

0x80 (8)

Alarm

1

1

3

Bit

0x100 (9)

EN MRA4 Modbus 05/10

Page 11

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

1

1

3

Format

Bit Mask

Unit

Description

-

Signal: General Trip L1

-

Signal: General Trip L2

-

Signal: General Trip L3

-

Signal: General Trip Ground fault

-

Signal: General Trip

-

Signal: Trip Command

-

Signal: Trip Command blocked

-

Module input state: External Blocking of the Trip Command

-

Signal: External Blocking of the Trip Command

-

Signal: Phase current failure forward direction

/ (Bit Position)

Functions Trip L1 (*)

Bit

0x200 (10)

Trip L2 (*)

1

1

3

Bit

0x400 (11)

Trip L3 (*)

1

1

3

Bit

0x800 (12)

Trip G (*)

1

1

3

Bit

0x1000 (13)

Trip (*)

1

1

3

Bit

0x2000 (14)

TripCmd (*)

1

1

3

Bit

0x4000 (15)

Prot Blo TripCmd

2

1

3

Struct

2

1

3

Bit

0x1 (1)

ExBlo TripCmd-I

2

1

3

Bit

0x2 (2)

ExBlo TripCmd

2

1

3

Bit

0x4 (3)

I dir fwd

2

1

3

Bit

0x80 (8)

Page 12

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

2

1

3

Format

Bit Mask

Unit

Description

-

Signal: Phase current failure reverse direction

-

Signal: Phase fault missing reference voltage

-

Signal: Earth fault forward

-

Signal: Earth fault reverse direction

-

Signal: Earth fault direction detection not possible

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Module input state: External reverse interlocking

-

Signal: active

/ (Bit Position)

Functions I dir rev

Bit

0x100 (9)

I dir n poss

2

1

3

Bit

0x200 (10)

IG dir fwd

2

1

3

Bit

0x400 (11)

IG rev dir

2

1

3

Bit

0x800 (12)

IG dir n poss

2

1

3

Bit

0x1000 (13)

I[1] ExBlo1-I

3

1

3

Struct

3

1

3

Bit

0x1 (1)

ExBlo2-I

3

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

3

1

3

Bit

0x4 (3)

Ex rev Interl-I

3

1

3

Bit

0x8 (4)

active

3

1

3

Bit

0x10 (5)

EN MRA4 Modbus 05/10

Page 13

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

3

1

3

Format

Bit Mask

Unit

Description

-

Signal: External Blocking

-

Signal: External reverse Interlocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: Blocking the trip command by an inrush

-

Signal: Alarm L1

-

Signal: Alarm L2

-

Signal: Alarm L3

-

Signal: Alarm

-

Signal: General Trip Phase L1

/ (Bit Position)

Functions ExBlo

Bit

0x20 (6)

Ex rev Interl

3

1

3

Bit

0x40 (7)

Blo TripCmd

3

1

3

Bit

0x80 (8)

ExBlo TripCmd

3

1

3

Bit

0x100 (9)

IH2 Blo

3

1

3

Bit

0x200 (10)

I[1] Alarm L1

4

1

3

Struct

4

1

3

Bit

0x1 (1)

Alarm L2

4

1

3

Bit

0x2 (2)

Alarm L3

4

1

3

Bit

0x4 (3)

Alarm

4

1

3

Bit

0x8 (4)

Trip L1 (*)

4

1

3

Bit

0x10 (5)

Page 14

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

4

1

3

Format

Bit Mask

Unit

Description

-

Signal: General Trip Phase L2

-

Signal: General Trip Phase L3

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Module input state: External reverse interlocking

-

Signal: active

-

Signal: External Blocking

/ (Bit Position)

Functions Trip L2 (*)

Bit

0x20 (6)

Trip L3 (*)

4

1

3

Bit

0x40 (7)

Trip (*)

4

1

3

Bit

0x80 (8)

TripCmd (*)

4

1

3

Bit

0x100 (9)

I[2] ExBlo1-I

5

1

3

Struct

5

1

3

Bit

0x1 (1)

ExBlo2-I

5

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

5

1

3

Bit

0x4 (3)

Ex rev Interl-I

5

1

3

Bit

0x8 (4)

active

5

1

3

Bit

0x10 (5)

ExBlo

5

1

3

Bit

0x20 (6)

EN MRA4 Modbus 05/10

Page 15

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

5

1

3

Format

Bit Mask

Unit

Description

-

Signal: External reverse Interlocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: Blocking the trip command by an inrush

-

Signal: Alarm L1

-

Signal: Alarm L2

-

Signal: Alarm L3

-

Signal: Alarm

-

Signal: General Trip Phase L1

-

Signal: General Trip Phase L2

/ (Bit Position)

Functions Ex rev Interl

Bit

0x40 (7)

Blo TripCmd

5

1

3

Bit

0x80 (8)

ExBlo TripCmd

5

1

3

Bit

0x100 (9)

IH2 Blo

5

1

3

Bit

0x200 (10)

I[2] Alarm L1

6

1

3

Struct

6

1

3

Bit

0x1 (1)

Alarm L2

6

1

3

Bit

0x2 (2)

Alarm L3

6

1

3

Bit

0x4 (3)

Alarm

6

1

3

Bit

0x8 (4)

Trip L1 (*)

6

1

3

Bit

0x10 (5)

Trip L2 (*)

6

1

3

Bit

0x20 (6)

Page 16

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

6

1

3

Format

Bit Mask

Unit

Description

-

Signal: General Trip Phase L3

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Module input state: External reverse interlocking

-

Signal: active

-

Signal: External Blocking

-

Signal: External reverse Interlocking

/ (Bit Position)

Functions Trip L3 (*)

Bit

0x40 (7)

Trip (*)

6

1

3

Bit

0x80 (8)

TripCmd (*)

6

1

3

Bit

0x100 (9)

I[3] ExBlo1-I

7

1

3

Struct

7

1

3

Bit

0x1 (1)

ExBlo2-I

7

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

7

1

3

Bit

0x4 (3)

Ex rev Interl-I

7

1

3

Bit

0x8 (4)

active

7

1

3

Bit

0x10 (5)

ExBlo

7

1

3

Bit

0x20 (6)

Ex rev Interl

7

1

3

Bit

0x40 (7)

EN MRA4 Modbus 05/10

Page 17

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

7

1

3

Format

Bit Mask

Unit

Description

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: Blocking the trip command by an inrush

-

Signal: Alarm L1

-

Signal: Alarm L2

-

Signal: Alarm L3

-

Signal: Alarm

-

Signal: General Trip Phase L1

-

Signal: General Trip Phase L2

-

Signal: General Trip Phase L3

/ (Bit Position)

Functions Blo TripCmd

Bit

0x80 (8)

ExBlo TripCmd

7

1

3

Bit

0x100 (9)

IH2 Blo

7

1

3

Bit

0x200 (10)

I[3] Alarm L1

8

1

3

Struct

8

1

3

Bit

0x1 (1)

Alarm L2

8

1

3

Bit

0x2 (2)

Alarm L3

8

1

3

Bit

0x4 (3)

Alarm

8

1

3

Bit

0x8 (4)

Trip L1 (*)

8

1

3

Bit

0x10 (5)

Trip L2 (*)

8

1

3

Bit

0x20 (6)

Trip L3 (*)

8

1

3

Bit

0x40 (7)

Page 18

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

8

1

3

Format

Bit Mask

Unit

Description

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Module input state: External reverse interlocking

-

Signal: active

-

Signal: External Blocking

-

Signal: External reverse Interlocking

-

Signal: Trip Command blocked

/ (Bit Position)

Functions Trip (*)

Bit

0x80 (8)

TripCmd (*)

8

1

3

Bit

0x100 (9)

I[4] ExBlo1-I

9

1

3

Struct

9

1

3

Bit

0x1 (1)

ExBlo2-I

9

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

9

1

3

Bit

0x4 (3)

Ex rev Interl-I

9

1

3

Bit

0x8 (4)

active

9

1

3

Bit

0x10 (5)

ExBlo

9

1

3

Bit

0x20 (6)

Ex rev Interl

9

1

3

Bit

0x40 (7)

Blo TripCmd

9

1

3

Bit

0x80 (8)

EN MRA4 Modbus 05/10

Page 19

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

9

1

3

Format

Bit Mask

Unit

Description

-

Signal: External Blocking of the Trip Command

-

Signal: Blocking the trip command by an inrush

-

Signal: Alarm L1

-

Signal: Alarm L2

-

Signal: Alarm L3

-

Signal: Alarm

-

Signal: General Trip Phase L1

-

Signal: General Trip Phase L2

-

Signal: General Trip Phase L3

-

Signal: Trip

/ (Bit Position)

Functions ExBlo TripCmd

Bit

0x100 (9)

IH2 Blo

9

1

3

Bit

0x200 (10)

I[4] Alarm L1

10

1

3

Struct

10

1

3

Bit

0x1 (1)

Alarm L2

10

1

3

Bit

0x2 (2)

Alarm L3

10

1

3

Bit

0x4 (3)

Alarm

10

1

3

Bit

0x8 (4)

Trip L1 (*)

10

1

3

Bit

0x10 (5)

Trip L2 (*)

10

1

3

Bit

0x20 (6)

Trip L3 (*)

10

1

3

Bit

0x40 (7)

Trip (*)

10

1

3

Bit

0x80 (8)

Page 20

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

10

1

3

Format

Bit Mask

Unit

Description

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Module input state: External reverse interlocking

-

Signal: active

-

Signal: External Blocking

-

Signal: External reverse Interlocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

/ (Bit Position)

Functions TripCmd (*)

Bit

0x100 (9)

I[5] ExBlo1-I

11

1

3

Struct

11

1

3

Bit

0x1 (1)

ExBlo2-I

11

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

11

1

3

Bit

0x4 (3)

Ex rev Interl-I

11

1

3

Bit

0x8 (4)

active

11

1

3

Bit

0x10 (5)

ExBlo

11

1

3

Bit

0x20 (6)

Ex rev Interl

11

1

3

Bit

0x40 (7)

Blo TripCmd

11

1

3

Bit

0x80 (8)

ExBlo TripCmd

11

1

3

Bit

0x100 (9)

EN MRA4 Modbus 05/10

Page 21

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

11

1

3

Format

Bit Mask

Unit

Description

-

Signal: Blocking the trip command by an inrush

-

Signal: Alarm L1

-

Signal: Alarm L2

-

Signal: Alarm L3

-

Signal: Alarm

-

Signal: General Trip Phase L1

-

Signal: General Trip Phase L2

-

Signal: General Trip Phase L3

-

Signal: Trip

-

Signal: Trip Command

/ (Bit Position)

Functions IH2 Blo

Bit

0x200 (10)

I[5] Alarm L1

12

1

3

Struct

12

1

3

Bit

0x1 (1)

Alarm L2

12

1

3

Bit

0x2 (2)

Alarm L3

12

1

3

Bit

0x4 (3)

Alarm

12

1

3

Bit

0x8 (4)

Trip L1 (*)

12

1

3

Bit

0x10 (5)

Trip L2 (*)

12

1

3

Bit

0x20 (6)

Trip L3 (*)

12

1

3

Bit

0x40 (7)

Trip (*)

12

1

3

Bit

0x80 (8)

TripCmd (*)

12

1

3

Bit

0x100 (9)

I[6]

Page 22

13

1

3

Struct

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

13

1

3

Format

Bit Mask

Unit

Description

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Module input state: External reverse interlocking

-

Signal: active

-

Signal: External Blocking

-

Signal: External reverse Interlocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: Blocking the trip command by an inrush

/ (Bit Position)

Functions ExBlo1-I

Bit

0x1 (1)

ExBlo2-I

13

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

13

1

3

Bit

0x4 (3)

Ex rev Interl-I

13

1

3

Bit

0x8 (4)

active

13

1

3

Bit

0x10 (5)

ExBlo

13

1

3

Bit

0x20 (6)

Ex rev Interl

13

1

3

Bit

0x40 (7)

Blo TripCmd

13

1

3

Bit

0x80 (8)

ExBlo TripCmd

13

1

3

Bit

0x100 (9)

IH2 Blo

13

1

3

Bit

0x200 (10)

I[6]

EN MRA4 Modbus 05/10

14

1

3

Struct

Page 23

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

14

1

3

Format

Bit Mask

Unit

Description

-

Signal: Alarm L1

-

Signal: Alarm L2

-

Signal: Alarm L3

-

Signal: Alarm

-

Signal: General Trip Phase L1

-

Signal: General Trip Phase L2

-

Signal: General Trip Phase L3

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

/ (Bit Position)

Functions Alarm L1

Bit

0x1 (1)

Alarm L2

14

1

3

Bit

0x2 (2)

Alarm L3

14

1

3

Bit

0x4 (3)

Alarm

14

1

3

Bit

0x8 (4)

Trip L1 (*)

14

1

3

Bit

0x10 (5)

Trip L2 (*)

14

1

3

Bit

0x20 (6)

Trip L3 (*)

14

1

3

Bit

0x40 (7)

Trip (*)

14

1

3

Bit

0x80 (8)

TripCmd (*)

14

1

3

Bit

0x100 (9)

IG[1] ExBlo1-I

15

1

3

Struct

15

1

3

Bit

0x1 (1)

ExBlo2-I

15

1

3

Bit

0x2 (2)

Page 24

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

15

1

3

Format

Bit Mask

Unit

Description

-

Module input state: External Blocking of the Trip Command

-

Module input state: External reverse interlocking

-

Signal: active

-

Signal: External Blocking

-

Signal: External reverse Interlocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: blocked by an inrush

-

Signal: Alarm IG

-

Signal: Trip

-

Signal: Trip Command

/ (Bit Position)

Functions ExBlo TripCmd-I

Bit

0x4 (3)

Ex rev Interl-I

15

1

3

Bit

0x8 (4)

active

15

1

3

Bit

0x10 (5)

ExBlo

15

1

3

Bit

0x20 (6)

Ex rev Interl

15

1

3

Bit

0x40 (7)

Blo TripCmd

15

1

3

Bit

0x80 (8)

ExBlo TripCmd

15

1

3

Bit

0x100 (9)

IGH2 Blo

15

1

3

Bit

0x200 (10)

Alarm

15

1

3

Bit

0x400 (11)

Trip (*)

15

1

3

Bit

0x800 (12)

TripCmd (*)

15

1

3

Bit

0x1000 (13)

EN MRA4 Modbus 05/10

Page 25

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

16

1

3

Struct

16

1

3

Bit

Bit Mask

Unit

Description

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Module input state: External reverse interlocking

-

Signal: active

-

Signal: External Blocking

-

Signal: External reverse Interlocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: blocked by an inrush

/ (Bit Position)

Functions IG[2] ExBlo1-I

0x1 (1)

ExBlo2-I

16

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

16

1

3

Bit

0x4 (3)

Ex rev Interl-I

16

1

3

Bit

0x8 (4)

active

16

1

3

Bit

0x10 (5)

ExBlo

16

1

3

Bit

0x20 (6)

Ex rev Interl

16

1

3

Bit

0x40 (7)

Blo TripCmd

16

1

3

Bit

0x80 (8)

ExBlo TripCmd

16

1

3

Bit

0x100 (9)

IGH2 Blo

16

1

3

Bit

0x200 (10)

Page 26

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

16

1

3

Format

Bit Mask

Unit

Description

-

Signal: Alarm IG

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Module input state: External reverse interlocking

-

Signal: active

-

Signal: External Blocking

-

Signal: External reverse Interlocking

/ (Bit Position)

Functions Alarm

Bit

0x400 (11)

Trip (*)

16

1

3

Bit

0x800 (12)

TripCmd (*)

16

1

3

Bit

0x1000 (13)

IG[3] ExBlo1-I

17

1

3

Struct

17

1

3

Bit

0x1 (1)

ExBlo2-I

17

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

17

1

3

Bit

0x4 (3)

Ex rev Interl-I

17

1

3

Bit

0x8 (4)

active

17

1

3

Bit

0x10 (5)

ExBlo

17

1

3

Bit

0x20 (6)

Ex rev Interl

17

1

3

Bit

0x40 (7)

EN MRA4 Modbus 05/10

Page 27

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

17

1

3

Format

Bit Mask

Unit

Description

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: blocked by an inrush

-

Signal: Alarm IG

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Module input state: External reverse interlocking

/ (Bit Position)

Functions Blo TripCmd

Bit

0x80 (8)

ExBlo TripCmd

17

1

3

Bit

0x100 (9)

IGH2 Blo

17

1

3

Bit

0x200 (10)

Alarm

17

1

3

Bit

0x400 (11)

Trip (*)

17

1

3

Bit

0x800 (12)

TripCmd (*)

17

1

3

Bit

0x1000 (13)

IG[4] ExBlo1-I

18

1

3

Struct

18

1

3

Bit

0x1 (1)

ExBlo2-I

18

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

18

1

3

Bit

0x4 (3)

Ex rev Interl-I

18

1

3

Bit

0x8 (4)

Page 28

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

18

1

3

Format

Bit Mask

Unit

Description

-

Signal: active

-

Signal: External Blocking

-

Signal: External reverse Interlocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: blocked by an inrush

-

Signal: Alarm IG

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

/ (Bit Position)

Functions active

Bit

0x10 (5)

ExBlo

18

1

3

Bit

0x20 (6)

Ex rev Interl

18

1

3

Bit

0x40 (7)

Blo TripCmd

18

1

3

Bit

0x80 (8)

ExBlo TripCmd

18

1

3

Bit

0x100 (9)

IGH2 Blo

18

1

3

Bit

0x200 (10)

Alarm

18

1

3

Bit

0x400 (11)

Trip (*)

18

1

3

Bit

0x800 (12)

TripCmd (*)

18

1

3

Bit

0x1000 (13)

ThR ExBlo1-I

19

1

3

Struct

19

1

3

Bit

0x1 (1)

EN MRA4 Modbus 05/10

Page 29

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

19

1

3

Format

Bit Mask

Unit

Description

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: Alarm Thermal Overload

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

/ (Bit Position)

Functions ExBlo2-I

Bit

0x2 (2)

ExBlo TripCmd-I

19

1

3

Bit

0x4 (3)

active

19

1

3

Bit

0x8 (4)

ExBlo

19

1

3

Bit

0x10 (5)

Blo TripCmd

19

1

3

Bit

0x20 (6)

ExBlo TripCmd

19

1

3

Bit

0x40 (7)

Alarm

19

1

3

Bit

0x80 (8)

Trip (*)

19

1

3

Bit

0x100 (9)

TripCmd (*)

19

1

3

Bit

0x200 (10)

IH2 ExBlo1-I

22

1

3

Struct

22

1

3

Bit

0x1 (1)

Page 30

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

22

1

3

Format

Bit Mask

Unit

Description

-

Module input state: External blocking2

-

Signal: active

-

Signal: External Blocking

-

Signal: Blocked L1

-

Signal: Blocked L2

-

Signal: Blocked L3

-

Signal: Blocking of the ground (earth) protection module (measured ground current)

-

Signal: Inrush was detected in at least one phase - trip command blocked.

-

Signal: Blocking of the ground (earth) protection module (calculated ground current)

/ (Bit Position)

Functions ExBlo2-I

Bit

0x2 (2)

active

22

1

3

Bit

0x4 (3)

ExBlo

22

1

3

Bit

0x8 (4)

Blo L1

22

1

3

Bit

0x10 (5)

Blo L2

22

1

3

Bit

0x20 (6)

Blo L3

22

1

3

Bit

0x40 (7)

Blo IG meas

22

1

3

Bit

0x80 (8)

3-ph Blo

22

1

3

Bit

0x100 (9)

Blo IG calc

22

1

3

Bit

0x200 (10)

EN MRA4 Modbus 05/10

Page 31

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

24

1

3

Struct

24

1

3

Bit

Bit Mask

Unit

Description

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: Alarm L1

-

Signal: Alarm L2

-

Signal: Alarm L3

/ (Bit Position)

Functions V[1] ExBlo1-I

0x1 (1)

ExBlo2-I

24

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

24

1

3

Bit

0x4 (3)

active

24

1

3

Bit

0x8 (4)

ExBlo

24

1

3

Bit

0x10 (5)

Blo TripCmd

24

1

3

Bit

0x20 (6)

ExBlo TripCmd

24

1

3

Bit

0x40 (7)

V[1] Alarm L1

25

1

3

Struct

25

1

3

Bit

0x1 (1)

Alarm L2

25

1

3

Bit

0x2 (2)

Alarm L3

25

1

3

Bit

0x4 (3)

Page 32

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

25

1

3

Format

Bit Mask

Unit

Description

-

Signal: Alarm voltage stage

-

Signal: General Trip Phase L1

-

Signal: General Trip Phase L2

-

Signal: General Trip Phase L3

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Signal: active

/ (Bit Position)

Functions Alarm

Bit

0x8 (4)

Trip L1 (*)

25

1

3

Bit

0x10 (5)

Trip L2 (*)

25

1

3

Bit

0x20 (6)

Trip L3 (*)

25

1

3

Bit

0x40 (7)

Trip (*)

25

1

3

Bit

0x80 (8)

TripCmd (*)

25

1

3

Bit

0x100 (9)

V[2] ExBlo1-I

26

1

3

Struct

26

1

3

Bit

0x1 (1)

ExBlo2-I

26

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

26

1

3

Bit

0x4 (3)

active

26

1

3

Bit

0x8 (4)

EN MRA4 Modbus 05/10

Page 33

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

26

1

3

Format

Bit Mask

Unit

Description

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: Alarm L1

-

Signal: Alarm L2

-

Signal: Alarm L3

-

Signal: Alarm voltage stage

-

Signal: General Trip Phase L1

-

Signal: General Trip Phase L2

-

Signal: General Trip Phase L3

/ (Bit Position)

Functions ExBlo

Bit

0x10 (5)

Blo TripCmd

26

1

3

Bit

0x20 (6)

ExBlo TripCmd

26

1

3

Bit

0x40 (7)

V[2] Alarm L1

27

1

3

Struct

27

1

3

Bit

0x1 (1)

Alarm L2

27

1

3

Bit

0x2 (2)

Alarm L3

27

1

3

Bit

0x4 (3)

Alarm

27

1

3

Bit

0x8 (4)

Trip L1 (*)

27

1

3

Bit

0x10 (5)

Trip L2 (*)

27

1

3

Bit

0x20 (6)

Trip L3 (*)

27

1

3

Bit

0x40 (7)

Page 34

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

27

1

3

Format

Bit Mask

Unit

Description

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: Alarm L1

/ (Bit Position)

Functions Trip (*)

Bit

0x80 (8)

TripCmd (*)

27

1

3

Bit

0x100 (9)

V[3] ExBlo1-I

28

1

3

Struct

28

1

3

Bit

0x1 (1)

ExBlo2-I

28

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

28

1

3

Bit

0x4 (3)

active

28

1

3

Bit

0x8 (4)

ExBlo

28

1

3

Bit

0x10 (5)

Blo TripCmd

28

1

3

Bit

0x20 (6)

ExBlo TripCmd

28

1

3

Bit

0x40 (7)

V[3] Alarm L1

29

1

3

Struct

29

1

3

Bit

0x1 (1)

EN MRA4 Modbus 05/10

Page 35

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

29

1

3

Format

Bit Mask

Unit

Description

-

Signal: Alarm L2

-

Signal: Alarm L3

-

Signal: Alarm voltage stage

-

Signal: General Trip Phase L1

-

Signal: General Trip Phase L2

-

Signal: General Trip Phase L3

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

/ (Bit Position)

Functions Alarm L2

Bit

0x2 (2)

Alarm L3

29

1

3

Bit

0x4 (3)

Alarm

29

1

3

Bit

0x8 (4)

Trip L1 (*)

29

1

3

Bit

0x10 (5)

Trip L2 (*)

29

1

3

Bit

0x20 (6)

Trip L3 (*)

29

1

3

Bit

0x40 (7)

Trip (*)

29

1

3

Bit

0x80 (8)

TripCmd (*)

29

1

3

Bit

0x100 (9)

V[4] ExBlo1-I

30

1

3

Struct

30

1

3

Bit

0x1 (1)

ExBlo2-I

30

1

3

Bit

0x2 (2)

Page 36

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

30

1

3

Format

Bit Mask

Unit

Description

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: Alarm L1

-

Signal: Alarm L2

-

Signal: Alarm L3

-

Signal: Alarm voltage stage

-

Signal: General Trip Phase L1

/ (Bit Position)

Functions ExBlo TripCmd-I

Bit

0x4 (3)

active

30

1

3

Bit

0x8 (4)

ExBlo

30

1

3

Bit

0x10 (5)

Blo TripCmd

30

1

3

Bit

0x20 (6)

ExBlo TripCmd

30

1

3

Bit

0x40 (7)

V[4] Alarm L1

31

1

3

Struct

31

1

3

Bit

0x1 (1)

Alarm L2

31

1

3

Bit

0x2 (2)

Alarm L3

31

1

3

Bit

0x4 (3)

Alarm

31

1

3

Bit

0x8 (4)

Trip L1 (*)

31

1

3

Bit

0x10 (5)

EN MRA4 Modbus 05/10

Page 37

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

31

1

3

Format

Bit Mask

Unit

Description

-

Signal: General Trip Phase L2

-

Signal: General Trip Phase L3

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

/ (Bit Position)

Functions Trip L2 (*)

Bit

0x20 (6)

Trip L3 (*)

31

1

3

Bit

0x40 (7)

Trip (*)

31

1

3

Bit

0x80 (8)

TripCmd (*)

31

1

3

Bit

0x100 (9)

VG[1] ExBlo1-I

32

1

3

Struct

32

1

3

Bit

0x1 (1)

ExBlo2-I

32

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

32

1

3

Bit

0x4 (3)

active

32

1

3

Bit

0x8 (4)

ExBlo

32

1

3

Bit

0x10 (5)

Blo TripCmd

32

1

3

Bit

0x20 (6)

Page 38

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

32

1

3

Format

Bit Mask

Unit

Description

-

Signal: External Blocking of the Trip Command

-

Signal: Alarm Residual Voltage Supervision-stage

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

/ (Bit Position)

Functions ExBlo TripCmd

Bit

0x40 (7)

Alarm

32

1

3

Bit

0x80 (8)

Trip (*)

32

1

3

Bit

0x100 (9)

TripCmd (*)

32

1

3

Bit

0x200 (10)

VG[2] ExBlo1-I

33

1

3

Struct

33

1

3

Bit

0x1 (1)

ExBlo2-I

33

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

33

1

3

Bit

0x4 (3)

active

33

1

3

Bit

0x8 (4)

ExBlo

33

1

3

Bit

0x10 (5)

Blo TripCmd

33

1

3

Bit

0x20 (6)

EN MRA4 Modbus 05/10

Page 39

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

33

1

3

Format

Bit Mask

Unit

Description

-

Signal: External Blocking of the Trip Command

-

Signal: Alarm Residual Voltage Supervision-stage

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Module is blocked by undervoltage.

/ (Bit Position)

Functions ExBlo TripCmd

Bit

0x40 (7)

Alarm

33

1

3

Bit

0x80 (8)

Trip (*)

33

1

3

Bit

0x100 (9)

TripCmd (*)

33

1

3

Bit

0x200 (10)

f[1] ExBlo1-I

34

1

3

Struct

34

1

3

Bit

0x1 (1)

ExBlo2-I

34

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

34

1

3

Bit

0x4 (3)

active

34

1

3

Bit

0x8 (4)

ExBlo

34

1

3

Bit

0x10 (5)

Blo by V<

34

1

3

Bit

0x20 (6)

Page 40

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

34

1

3

Format

Bit Mask

Unit

Description

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: Alarm Frequency Protection

-

Alarm instantaneous or average value of the rate-offrequency-change

-

Signal: Frequency has exceeded the limit.

-

Signal: Trip df/dt or DF/DT

-

Signal: Alarm Frequency Protection (collective signal)

-

Signal: Alarm Vector Surge

-

Signal: Trip Frequency Protection (collective signal)

/ (Bit Position)

Functions Blo TripCmd

Bit

0x40 (7)

ExBlo TripCmd

34

1

3

Bit

0x80 (8)

f[1] Alarm f

35

1

3

Struct

35

1

3

Bit

0x1 (1)

Alarm df/dt | DF/DT

35

1

3

Bit

0x2 (2)

Trip f (*)

35

1

3

Bit

0x4 (3)

Trip df/dt | DF/DT (*) 35

1

3

Bit

0x8 (4)

Alarm

35

1

3

Bit

0x10 (5)

Alarm delta phi

35

1

3

Bit

0x20 (6)

Trip (*)

35

1

3

Bit

0x40 (7)

EN MRA4 Modbus 05/10

Page 41

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

35

1

3

Format

Bit Mask

Unit

Description

-

Signal: Trip Vector Surge

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Module is blocked by undervoltage.

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

/ (Bit Position)

Functions Trip delta phi (*)

Bit

0x80 (8)

TripCmd (*)

35

1

3

Bit

0x100 (9)

f[2] ExBlo1-I

36

1

3

Struct

36

1

3

Bit

0x1 (1)

ExBlo2-I

36

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

36

1

3

Bit

0x4 (3)

active

36

1

3

Bit

0x8 (4)

ExBlo

36

1

3

Bit

0x10 (5)

Blo by V<

36

1

3

Bit

0x20 (6)

Blo TripCmd

36

1

3

Bit

0x40 (7)

ExBlo TripCmd

36

1

3

Bit

0x80 (8)

f[2] Page 42

37

1

3

Struct EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

37

1

3

Format

Bit Mask

Unit

Description

-

Signal: Alarm Frequency Protection

-

Alarm instantaneous or average value of the rate-offrequency-change

-

Signal: Frequency has exceeded the limit.

-

Signal: Trip df/dt or DF/DT

-

Signal: Alarm Frequency Protection (collective signal)

-

Signal: Alarm Vector Surge

-

Signal: Trip Frequency Protection (collective signal)

-

Signal: Trip Vector Surge

-

Signal: Trip Command

-

Module input state: External blocking1

/ (Bit Position)

Functions Alarm f

Bit

0x1 (1)

Alarm df/dt | DF/DT

37

1

3

Bit

0x2 (2)

Trip f (*)

37

1

3

Bit

0x4 (3)

Trip df/dt | DF/DT (*) 37

1

3

Bit

0x8 (4)

Alarm

37

1

3

Bit

0x10 (5)

Alarm delta phi

37

1

3

Bit

0x20 (6)

Trip (*)

37

1

3

Bit

0x40 (7)

Trip delta phi (*)

37

1

3

Bit

0x80 (8)

TripCmd (*)

37

1

3

Bit

0x100 (9)

f[3] ExBlo1-I

38

1

3

Struct

38

1

3

Bit

0x1 (1)

EN MRA4 Modbus 05/10

Page 43

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

38

1

3

Format

Bit Mask

Unit

Description

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Module is blocked by undervoltage.

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: Alarm Frequency Protection

-

Alarm instantaneous or average value of the rate-offrequency-change

/ (Bit Position)

Functions ExBlo2-I

Bit

0x2 (2)

ExBlo TripCmd-I

38

1

3

Bit

0x4 (3)

active

38

1

3

Bit

0x8 (4)

ExBlo

38

1

3

Bit

0x10 (5)

Blo by V<

38

1

3

Bit

0x20 (6)

Blo TripCmd

38

1

3

Bit

0x40 (7)

ExBlo TripCmd

38

1

3

Bit

0x80 (8)

f[3] Alarm f

39

1

3

Struct

39

1

3

Bit

0x1 (1)

Alarm df/dt | DF/DT

39

1

3

Bit

0x2 (2)

Page 44

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

39

1

3

Format

Bit Mask

Unit

Description

-

Signal: Frequency has exceeded the limit.

-

Signal: Trip df/dt or DF/DT

-

Signal: Alarm Frequency Protection (collective signal)

-

Signal: Alarm Vector Surge

-

Signal: Trip Frequency Protection (collective signal)

-

Signal: Trip Vector Surge

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

/ (Bit Position)

Functions Trip f (*)

Bit

0x4 (3)

Trip df/dt | DF/DT (*) 39

1

3

Bit

0x8 (4)

Alarm

39

1

3

Bit

0x10 (5)

Alarm delta phi

39

1

3

Bit

0x20 (6)

Trip (*)

39

1

3

Bit

0x40 (7)

Trip delta phi (*)

39

1

3

Bit

0x80 (8)

TripCmd (*)

39

1

3

Bit

0x100 (9)

f[4] ExBlo1-I

40

1

3

Struct

40

1

3

Bit

0x1 (1)

ExBlo2-I

40

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

40

1

3

Bit

0x4 (3)

EN MRA4 Modbus 05/10

Page 45

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

40

1

3

Format

Bit Mask

Unit

Description

-

Signal: active

-

Signal: External Blocking

-

Signal: Module is blocked by undervoltage.

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: Alarm Frequency Protection

-

Alarm instantaneous or average value of the rate-offrequency-change

-

Signal: Frequency has exceeded the limit.

-

Signal: Trip df/dt or DF/DT

/ (Bit Position)

Functions active

Bit

0x8 (4)

ExBlo

40

1

3

Bit

0x10 (5)

Blo by V<

40

1

3

Bit

0x20 (6)

Blo TripCmd

40

1

3

Bit

0x40 (7)

ExBlo TripCmd

40

1

3

Bit

0x80 (8)

f[4] Alarm f

41

1

3

Struct

41

1

3

Bit

0x1 (1)

Alarm df/dt | DF/DT

41

1

3

Bit

0x2 (2)

Trip f (*)

41

1

3

Bit

0x4 (3)

Trip df/dt | DF/DT (*) 41

1

3

Bit

0x8 (4)

Page 46

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

41

1

3

Format

Bit Mask

Unit

Description

-

Signal: Alarm Frequency Protection (collective signal)

-

Signal: Alarm Vector Surge

-

Signal: Trip Frequency Protection (collective signal)

-

Signal: Trip Vector Surge

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

/ (Bit Position)

Functions Alarm

Bit

0x10 (5)

Alarm delta phi

41

1

3

Bit

0x20 (6)

Trip (*)

41

1

3

Bit

0x40 (7)

Trip delta phi (*)

41

1

3

Bit

0x80 (8)

TripCmd (*)

41

1

3

Bit

0x100 (9)

f[5] ExBlo1-I

42

1

3

Struct

42

1

3

Bit

0x1 (1)

ExBlo2-I

42

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

42

1

3

Bit

0x4 (3)

active

42

1

3

Bit

0x8 (4)

ExBlo

42

1

3

Bit

0x10 (5)

EN MRA4 Modbus 05/10

Page 47

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

42

1

3

Format

Bit Mask

Unit

Description

-

Signal: Module is blocked by undervoltage.

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: Alarm Frequency Protection

-

Alarm instantaneous or average value of the rate-offrequency-change

-

Signal: Frequency has exceeded the limit.

-

Signal: Trip df/dt or DF/DT

-

Signal: Alarm Frequency Protection (collective signal)

-

Signal: Alarm Vector Surge

/ (Bit Position)

Functions Blo by V<

Bit

0x20 (6)

Blo TripCmd

42

1

3

Bit

0x40 (7)

ExBlo TripCmd

42

1

3

Bit

0x80 (8)

f[5] Alarm f

43

1

3

Struct

43

1

3

Bit

0x1 (1)

Alarm df/dt | DF/DT

43

1

3

Bit

0x2 (2)

Trip f (*)

43

1

3

Bit

0x4 (3)

Trip df/dt | DF/DT (*) 43

1

3

Bit

0x8 (4)

Alarm

43

1

3

Bit

0x10 (5)

Alarm delta phi

43

1

3

Bit

0x20 (6)

Page 48

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

43

1

3

Format

Bit Mask

Unit

Description

-

Signal: Trip Frequency Protection (collective signal)

-

Signal: Trip Vector Surge

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Module is blocked by undervoltage.

-

Signal: Trip Command blocked

/ (Bit Position)

Functions Trip (*)

Bit

0x40 (7)

Trip delta phi (*)

43

1

3

Bit

0x80 (8)

TripCmd (*)

43

1

3

Bit

0x100 (9)

f[6] ExBlo1-I

44

1

3

Struct

44

1

3

Bit

0x1 (1)

ExBlo2-I

44

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

44

1

3

Bit

0x4 (3)

active

44

1

3

Bit

0x8 (4)

ExBlo

44

1

3

Bit

0x10 (5)

Blo by V<

44

1

3

Bit

0x20 (6)

Blo TripCmd

44

1

3

Bit

0x40 (7)

EN MRA4 Modbus 05/10

Page 49

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

44

1

3

Format

Bit Mask

Unit

Description

-

Signal: External Blocking of the Trip Command

-

Signal: Alarm Frequency Protection

-

Alarm instantaneous or average value of the rate-offrequency-change

-

Signal: Frequency has exceeded the limit.

-

Signal: Trip df/dt or DF/DT

-

Signal: Alarm Frequency Protection (collective signal)

-

Signal: Alarm Vector Surge

-

Signal: Trip Frequency Protection (collective signal)

-

Signal: Trip Vector Surge

/ (Bit Position)

Functions ExBlo TripCmd

Bit

0x80 (8)

f[6] Alarm f

45

1

3

Struct

45

1

3

Bit

0x1 (1)

Alarm df/dt | DF/DT

45

1

3

Bit

0x2 (2)

Trip f (*)

45

1

3

Bit

0x4 (3)

Trip df/dt | DF/DT (*) 45

1

3

Bit

0x8 (4)

Alarm

45

1

3

Bit

0x10 (5)

Alarm delta phi

45

1

3

Bit

0x20 (6)

Trip (*)

45

1

3

Bit

0x40 (7)

Trip delta phi (*)

45

1

3

Bit

0x80 (8)

Page 50

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

45

1

3

Format

Bit Mask

Unit

Description

-

Signal: Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Auto Reclosing running

-

Signal: Dead time between trip and reclosure attempt

-

Signal: Auto Reclosing successful

-

Signal: Auto Reclosing failure

-

Module input state: Criterion by which the Circuit Breaker Switch Position is to be detected.

-

Signal: AR Supervision

/ (Bit Position)

Functions TripCmd (*)

Bit

0x100 (9)

AR active

46

1

3

Struct

46

1

3

Bit

0x1 (1)

ExBlo

46

1

3

Bit

0x2 (2)

running

46

1

3

Bit

0x8 (4)

t-dead

46

1

3

Bit

0x10 (5)

successful (*)

46

1

3

Bit

0x100 (9)

failed (*)

46

1

3

Bit

0x200 (10)

CB Pos Detect-I

46

1

3

Bit

0xc00 (11)

t-AR Supervision

46

1

3

Bit

0x1000 (13)

AR

EN MRA4 Modbus 05/10

47

1

3

Struct

Page 51

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

47

1

3

Format

Bit Mask

Unit

Description

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External synchronism signal

-

Module input state: CB ready

-

Signal: CB switch ON Command

-

Pre Shot Control

-

Shot Control

-

Shot Control

-

Shot Control

-

Shot Control

-

Shot Control

/ (Bit Position)

Functions ExBlo1-I

Bit

0x1 (1)

ExBlo2-I

47

1

3

Bit

0x2 (2)

Ex Sync running-I

47

1

3

Bit

0x4 (3)

Ready-I

47

1

3

Bit

0x8 (4)

CB ON Cmd

47

1

3

Bit

0x10 (5)

Pre Shot (*)

47

1

3

Bit

0x20 (6)

Shot 1 (*)

47

1

3

Bit

0x40 (7)

Shot 2 (*)

47

1

3

Bit

0x80 (8)

Shot 3 (*)

47

1

3

Bit

0x100 (9)

Shot 4 (*)

47

1

3

Bit

0x200 (10)

Shot 5 (*)

47

1

3

Bit

0x400 (11)

Page 52

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

47

1

3

Format

Bit Mask

Unit

Description

-

Shot Control

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Module input state: Alarm

-

Module input state: Trip

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

/ (Bit Position)

Functions Shot 6 (*)

Bit

0x800 (12)

ExP[1] ExBlo1-I

49

1

3

Struct

49

1

3

Bit

0x1 (1)

ExBlo2-I

49

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

49

1

3

Bit

0x4 (3)

Alarm-I

49

1

3

Bit

0x8 (4)

Trip-I

49

1

3

Bit

0x10 (5)

active

49

1

3

Bit

0x20 (6)

ExBlo

49

1

3

Bit

0x40 (7)

Blo TripCmd

49

1

3

Bit

0x80 (8)

ExBlo TripCmd

49

1

3

Bit

0x100 (9)

EN MRA4 Modbus 05/10

Page 53

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

49

1

3

Format

Bit Mask

Unit

Description

-

Signal: Alarm

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Module input state: Alarm

-

Module input state: Trip

-

Signal: active

-

Signal: External Blocking

/ (Bit Position)

Functions Alarm

Bit

0x200 (10)

Trip (*)

49

1

3

Bit

0x400 (11)

TripCmd (*)

49

1

3

Bit

0x800 (12)

ExP[2] ExBlo1-I

50

1

3

Struct

50

1

3

Bit

0x1 (1)

ExBlo2-I

50

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

50

1

3

Bit

0x4 (3)

Alarm-I

50

1

3

Bit

0x8 (4)

Trip-I

50

1

3

Bit

0x10 (5)

active

50

1

3

Bit

0x20 (6)

ExBlo

50

1

3

Bit

0x40 (7)

Page 54

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

50

1

3

Format

Bit Mask

Unit

Description

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: Alarm

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Module input state: Alarm

-

Module input state: Trip

/ (Bit Position)

Functions Blo TripCmd

Bit

0x80 (8)

ExBlo TripCmd

50

1

3

Bit

0x100 (9)

Alarm

50

1

3

Bit

0x200 (10)

Trip (*)

50

1

3

Bit

0x400 (11)

TripCmd (*)

50

1

3

Bit

0x800 (12)

ExP[3] ExBlo1-I

51

1

3

Struct

51

1

3

Bit

0x1 (1)

ExBlo2-I

51

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

51

1

3

Bit

0x4 (3)

Alarm-I

51

1

3

Bit

0x8 (4)

Trip-I

51

1

3

Bit

0x10 (5)

EN MRA4 Modbus 05/10

Page 55

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

51

1

3

Format

Bit Mask

Unit

Description

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: Alarm

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

/ (Bit Position)

Functions active

Bit

0x20 (6)

ExBlo

51

1

3

Bit

0x40 (7)

Blo TripCmd

51

1

3

Bit

0x80 (8)

ExBlo TripCmd

51

1

3

Bit

0x100 (9)

Alarm

51

1

3

Bit

0x200 (10)

Trip (*)

51

1

3

Bit

0x400 (11)

TripCmd (*)

51

1

3

Bit

0x800 (12)

ExP[4] ExBlo1-I

52

1

3

Struct

52

1

3

Bit

0x1 (1)

ExBlo2-I

52

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

52

1

3

Bit

0x4 (3)

Page 56

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

52

1

3

Format

Bit Mask

Unit

Description

-

Module input state: Alarm

-

Module input state: Trip

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: Alarm

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

/ (Bit Position)

Functions Alarm-I

Bit

0x8 (4)

Trip-I

52

1

3

Bit

0x10 (5)

active

52

1

3

Bit

0x20 (6)

ExBlo

52

1

3

Bit

0x40 (7)

Blo TripCmd

52

1

3

Bit

0x80 (8)

ExBlo TripCmd

52

1

3

Bit

0x100 (9)

Alarm

52

1

3

Bit

0x200 (10)

Trip (*)

52

1

3

Bit

0x400 (11)

TripCmd (*)

52

1

3

Bit

0x800 (12)

CBF ExBlo1-I

53

1

3

Struct

53

1

3

Bit

0x1 (1)

EN MRA4 Modbus 05/10

Page 57

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

53

1

3

Format

Bit Mask

Unit

Description

-

Module input state: External blocking2

-

Signal: active

-

Signal: External Blocking

-

Module Input: Trigger that will start the CBF

-

Module Input: Trigger that will start the CBF

-

Module Input: Trigger that will start the CBF

-

Signal: CBF-Module started

-

Signal: Circuit Breaker Failure

-

Module input state: External fuse failure voltage transformers

-

Module input state: External fuse failure earth voltage transformer

/ (Bit Position)

Functions ExBlo2-I

Bit

0x2 (2)

active

53

1

3

Bit

0x4 (3)

ExBlo

53

1

3

Bit

0x8 (4)

Trigger1

53

1

3

Bit

0x10 (5)

Trigger2

53

1

3

Bit

0x20 (6)

Trigger3

53

1

3

Bit

0x40 (7)

running

53

1

3

Bit

0x80 (8)

Alarm (*)

53

1

3

Bit

0x100 (9)

VTS Ex Fuse Fail VT-I

56

1

3

Struct

56

1

3

Bit

0x1 (1)

Ex Fuse Fail EVT-I

56

1

3

Bit

0x2 (2)

Page 58

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

56

1

3

Format

Bit Mask

Unit

Description

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Signal: active

-

Signal: External Blocking

-

Signal: Alarm ΔV Voltage Transformer Measuring Circuit Supervision

-

Signal: Alarm Voltage Transformer Measuring Circuit Supervision

-

Signal: Alarm Fuse Failure Voltage Transformers

-

Signal: Alarm Fuse Failure Earth Voltage Transformers

-

Disturbance No

/ (Bit Position)

Functions ExBlo1-I

Bit

0x4 (3)

ExBlo2-I

56

1

3

Bit

0x8 (4)

active

56

1

3

Bit

0x10 (5)

ExBlo

56

1

3

Bit

0x20 (6)

Alarm ΔV

56

1

3

Bit

0x40 (7)

Alarm

56

1

3

Bit

0x80 (8)

Ex FF VT

56

1

3

Bit

0x100 (9)

Ex FF EVT

56

1

3

Bit

0x200 (10)

Prot FaultNo

57

1

3

Struct

57

1

3

Bit

0xffff (1)

Prot

EN MRA4 Modbus 05/10

58

1

3

Struct

Page 59

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

58

1

3

Format

Bit Mask

Unit

Description

-

Number of grid faults: A grid fault, e.g. a short circuit, might cause several faults with trip and autoreclosing, each fault being identified by an increased fault number. In this case, the grid fault number remains the same.

-

Signal: Parameter Set 1

-

Signal: Parameter Set 2

-

Signal: Parameter Set 3

-

Signal: Parameter Set 4

-

Signal: Manual Switch over of a Parameter Set

-

Signal: Parameter Set Switch via Scada

/ (Bit Position)

Functions No of grid faults

Bit

0xffff (1)

PSet-Switch PS 1

59

1

3

Struct

59

1

3

Bit

0x1 (1)

PS 2

59

1

3

Bit

0x2 (2)

PS 3

59

1

3

Bit

0x4 (3)

PS 4

59

1

3

Bit

0x8 (4)

PSS manual

59

1

3

Bit

0x10 (5)

PSS via Scada

59

1

3

Bit

0x20 (6)

Page 60

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

59

1

3

Format

Bit Mask

Unit

Description

-

Signal: Parameter Set Switch via input function

-

State of the module input respectively of the signal, that should activate this Parameter Setting Group.

-

State of the module input respectively of the signal, that should activate this Parameter Setting Group.

-

State of the module input respectively of the signal, that should activate this Parameter Setting Group.

-

State of the module input respectively of the signal, that should activate this Parameter Setting Group.

-

Signal: At least one parameter has been changed

/ (Bit Position)

Functions PSS via Inp fct

Bit

0x40 (7)

PS1-I

59

1

3

Bit

0x80 (8)

PS2-I

59

1

3

Bit

0x100 (9)

PS3-I

59

1

3

Bit

0x200 (10)

PS4-I

59

1

3

Bit

0x400 (11)

min 1 param changed (*) EnergyCr EN MRA4 Modbus 05/10

59

1

3

Bit

0x800 (12)

60

1

3

Struct Page 61

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

60

1

3

Format

Bit Mask

Unit

Description

-

Signal: Counter Overflow Wp+

-

Signal: Counter Overflow Wp-

-

Signal: Counter Overflow Wq+

-

Signal: Counter Overflow Wq-

-

Signal: Counter Overflow Wp Net

-

Signal: Counter Overflow Wq Net

-

Signal: Counter Overflow Ws Net

-

Signal: Counter Wp+ will overflow soon

-

Signal: Counter Wpwill overflow soon

-

Signal: Counter Wq+ will overflow soon

-

Signal: Counter Wqwill overflow soon

/ (Bit Position)

Functions Cr Overflow Wp+

Bit

0x1 (1)

Cr Overflow Wp-

60

1

3

Bit

0x2 (2)

Cr Overflow Wq+

60

1

3

Bit

0x4 (3)

Cr Overflow Wq-

60

1

3

Bit

0x8 (4)

Cr Overflow Wp Net

60

1

3

Bit

0x10 (5)

Cr Overflow Wq Net

60

1

3

Bit

0x20 (6)

Cr Overflow Ws Net

60

1

3

Bit

0x40 (7)

Cr OverflwWarn Wp+ 60

1

3

Bit

0x80 (8)

Cr OverflwWarn Wp- 60

1

3

Bit

0x100 (9)

Cr OverflwWarn Wq+ 60

1

3

Bit

0x200 (10)

Cr OverflwWarn Wq- 60

1

3

Bit

0x400 (11)

Page 62

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup

Start Register Address

No. of Modbus Registers

Function Code

Cr OverflwWarn Wp Net

60

1

3

Cr OverflwWarn Wq Net

60

Cr OverflwWarn Ws Net

60

Names

Format

Bit Mask

Unit

Description

-

Signal: Counter Wp Net will overflow soon

-

Signal: Counter Wq Net will overflow soon

-

Signal: Counter Ws Net will overflow soon

-

Module input state: External blocking

-

Module input state: External blocking

-

Module input state: External Switch Onto Fault Alarm

-

Module input state: External reverse interlocking

-

Signal: active

-

Signal: External Blocking

-

Signal: External reverse Interlocking

/ (Bit Position)

Functions

SOTF ExBlo1-I

Bit

0x800 (12)

1

3

Bit

0x1000 (13)

1

3

Bit

0x2000 (14)

65

1

3

Struct

65

1

3

Bit

0x1 (1)

ExBlo2-I

65

1

3

Bit

0x2 (2)

Ext SOTF-I

65

1

3

Bit

0x4 (3)

Ex rev Interl-I

65

1

3

Bit

0x8 (4)

active

65

1

3

Bit

0x10 (5)

ExBlo

65

1

3

Bit

0x20 (6)

Ex rev Interl

65

1

3

Bit

0x40 (7)

EN MRA4 Modbus 05/10

Page 63

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

65

1

3

Format

Bit Mask

Unit

Description

-

Module input state: Criterion by which the Circuit Breaker Switch Position is to be detected.

-

Signal: Blocked by AR

-

Signal: Switch Onto Fault enabled. This Signal can be used to modify Overcurrent Protection Settings.

-

Module input state: Circuit breaker was switched on manually

-

Signal: No Load Current.

-

Module input state: External blocking

-

Module input state: External blocking

-

Module input state: External reverse interlocking

/ (Bit Position)

Functions CB Pos Detect-I

Bit

0x300 (9)

AR Blo

65

1

3

Bit

0x400 (11)

enabled

65

1

3

Bit

0x800 (12)

Manual ON-I (*)

65

1

3

Bit

0x1000 (13)

I<

65

1

3

Bit

0x2000 (14)

CLPU ExBlo1-I

66

1

3

Struct

66

1

3

Bit

0x1 (1)

ExBlo2-I

66

1

3

Bit

0x2 (2)

Ex rev Interl-I

66

1

3

Bit

0x4 (3)

Page 64

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

66

1

3

Format

Bit Mask

Unit

Description

-

Signal: active

-

Signal: External Blocking

-

Signal: External reverse Interlocking

-

Module input state: Criterion by which the Circuit Breaker Switch Position is to be detected.

-

Signal: Cold Load enabled

-

Signal: Cold Load detected

-

Signal: No Load Current.

-

Module input state: AR Blo

-

Signal: Load Inrush

-

Signal: Settle Time

/ (Bit Position)

Functions active

Bit

0x8 (4)

ExBlo

66

1

3

Bit

0x10 (5)

Ex rev Interl

66

1

3

Bit

0x20 (6)

CB Pos Detect-I

66

1

3

Bit

0x180 (8)

enabled

66

1

3

Bit

0x200 (10)

detected (*)

66

1

3

Bit

0x400 (11)

I<

66

1

3

Bit

0x800 (12)

AR Blo

66

1

3

Bit

0x1000 (13)

Load Inrush

66

1

3

Bit

0x2000 (14)

Settle Time

66

1

3

Bit

0x4000 (15)

PQS [1]

EN MRA4 Modbus 05/10

67

1

3

Struct

Page 65

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

67

1

3

Format

Bit Mask

Unit

Description

-

Module input state: External blocking

-

Module input state: External blocking

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: Alarm Power Protection

-

Signal: Trip Power Protection

-

Signal: Trip Command

/ (Bit Position)

Functions ExBlo1-I

Bit

0x1 (1)

ExBlo2-I

67

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

67

1

3

Bit

0x4 (3)

active

67

1

3

Bit

0x8 (4)

ExBlo

67

1

3

Bit

0x10 (5)

Blo TripCmd

67

1

3

Bit

0x20 (6)

ExBlo TripCmd

67

1

3

Bit

0x40 (7)

Alarm

67

1

3

Bit

0x80 (8)

Trip (*)

67

1

3

Bit

0x100 (9)

TripCmd (*)

67

1

3

Bit

0x200 (10)

PQS [2]

Page 66

68

1

3

Struct

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

68

1

3

Format

Bit Mask

Unit

Description

-

Module input state: External blocking

-

Module input state: External blocking

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: Alarm Power Protection

-

Signal: Trip Power Protection

-

Signal: Trip Command

/ (Bit Position)

Functions ExBlo1-I

Bit

0x1 (1)

ExBlo2-I

68

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

68

1

3

Bit

0x4 (3)

active

68

1

3

Bit

0x8 (4)

ExBlo

68

1

3

Bit

0x10 (5)

Blo TripCmd

68

1

3

Bit

0x20 (6)

ExBlo TripCmd

68

1

3

Bit

0x40 (7)

Alarm

68

1

3

Bit

0x80 (8)

Trip (*)

68

1

3

Bit

0x100 (9)

TripCmd (*)

68

1

3

Bit

0x200 (10)

PQS [3]

EN MRA4 Modbus 05/10

69

1

3

Struct

Page 67

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

69

1

3

Format

Bit Mask

Unit

Description

-

Module input state: External blocking

-

Module input state: External blocking

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: Alarm Power Protection

-

Signal: Trip Power Protection

-

Signal: Trip Command

/ (Bit Position)

Functions ExBlo1-I

Bit

0x1 (1)

ExBlo2-I

69

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

69

1

3

Bit

0x4 (3)

active

69

1

3

Bit

0x8 (4)

ExBlo

69

1

3

Bit

0x10 (5)

Blo TripCmd

69

1

3

Bit

0x20 (6)

ExBlo TripCmd

69

1

3

Bit

0x40 (7)

Alarm

69

1

3

Bit

0x80 (8)

Trip (*)

69

1

3

Bit

0x100 (9)

TripCmd (*)

69

1

3

Bit

0x200 (10)

PQS [4]

Page 68

70

1

3

Struct

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

70

1

3

Format

Bit Mask

Unit

Description

-

Module input state: External blocking

-

Module input state: External blocking

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: Alarm Power Protection

-

Signal: Trip Power Protection

-

Signal: Trip Command

/ (Bit Position)

Functions ExBlo1-I

Bit

0x1 (1)

ExBlo2-I

70

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

70

1

3

Bit

0x4 (3)

active

70

1

3

Bit

0x8 (4)

ExBlo

70

1

3

Bit

0x10 (5)

Blo TripCmd

70

1

3

Bit

0x20 (6)

ExBlo TripCmd

70

1

3

Bit

0x40 (7)

Alarm

70

1

3

Bit

0x80 (8)

Trip (*)

70

1

3

Bit

0x100 (9)

TripCmd (*)

70

1

3

Bit

0x200 (10)

PQS [5]

EN MRA4 Modbus 05/10

71

1

3

Struct

Page 69

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

71

1

3

Format

Bit Mask

Unit

Description

-

Module input state: External blocking

-

Module input state: External blocking

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: Alarm Power Protection

-

Signal: Trip Power Protection

-

Signal: Trip Command

/ (Bit Position)

Functions ExBlo1-I

Bit

0x1 (1)

ExBlo2-I

71

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

71

1

3

Bit

0x4 (3)

active

71

1

3

Bit

0x8 (4)

ExBlo

71

1

3

Bit

0x10 (5)

Blo TripCmd

71

1

3

Bit

0x20 (6)

ExBlo TripCmd

71

1

3

Bit

0x40 (7)

Alarm

71

1

3

Bit

0x80 (8)

Trip (*)

71

1

3

Bit

0x100 (9)

TripCmd (*)

71

1

3

Bit

0x200 (10)

PQS [6]

Page 70

72

1

3

Struct

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

72

1

3

Format

Bit Mask

Unit

Description

-

Module input state: External blocking

-

Module input state: External blocking

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: Alarm Power Protection

-

Signal: Trip Power Protection

-

Signal: Trip Command

/ (Bit Position)

Functions ExBlo1-I

Bit

0x1 (1)

ExBlo2-I

72

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

72

1

3

Bit

0x4 (3)

active

72

1

3

Bit

0x8 (4)

ExBlo

72

1

3

Bit

0x10 (5)

Blo TripCmd

72

1

3

Bit

0x20 (6)

ExBlo TripCmd

72

1

3

Bit

0x40 (7)

Alarm

72

1

3

Bit

0x80 (8)

Trip (*)

72

1

3

Bit

0x100 (9)

TripCmd (*)

72

1

3

Bit

0x200 (10)

PF[1]

EN MRA4 Modbus 05/10

73

1

3

Struct

Page 71

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

73

1

3

Format

Bit Mask

Unit

Description

-

Module input state: External blocking

-

Module input state: External blocking

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: Alarm Power Factor

-

Signal: Trip Power Factor

-

Signal: Trip Command

-

Signal: Compensation Signal

/ (Bit Position)

Functions ExBlo1-I

Bit

0x1 (1)

ExBlo2-I

73

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

73

1

3

Bit

0x4 (3)

active

73

1

3

Bit

0x8 (4)

ExBlo

73

1

3

Bit

0x10 (5)

Blo TripCmd

73

1

3

Bit

0x20 (6)

ExBlo TripCmd

73

1

3

Bit

0x40 (7)

Alarm

73

1

3

Bit

0x80 (8)

Trip (*)

73

1

3

Bit

0x100 (9)

TripCmd (*)

73

1

3

Bit

0x200 (10)

Compensator

73

1

3

Bit

0x400 (11)

Page 72

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

73

1

3

Format

Bit Mask

Unit

Description

-

Signal: Alarm Power Factor Impossible

-

Module input state: External blocking

-

Module input state: External blocking

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: Alarm Power Factor

-

Signal: Trip Power Factor

/ (Bit Position)

Functions Impossible

Bit

0x800 (12)

PF[2] ExBlo1-I

74

1

3

Struct

74

1

3

Bit

0x1 (1)

ExBlo2-I

74

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

74

1

3

Bit

0x4 (3)

active

74

1

3

Bit

0x8 (4)

ExBlo

74

1

3

Bit

0x10 (5)

Blo TripCmd

74

1

3

Bit

0x20 (6)

ExBlo TripCmd

74

1

3

Bit

0x40 (7)

Alarm

74

1

3

Bit

0x80 (8)

Trip (*)

74

1

3

Bit

0x100 (9)

EN MRA4 Modbus 05/10

Page 73

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

74

1

3

Format

Bit Mask

Unit

Description

-

Signal: Trip Command

-

Signal: Compensation Signal

-

Signal: Alarm Power Factor Impossible

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

/ (Bit Position)

Functions TripCmd (*)

Bit

0x200 (10)

Compensator

74

1

3

Bit

0x400 (11)

Impossible

74

1

3

Bit

0x800 (12)

I2>[1] ExBlo1-I

82

1

3

Struct

82

1

3

Bit

0x1 (1)

ExBlo2-I

82

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

82

1

3

Bit

0x4 (3)

active

82

1

3

Bit

0x8 (4)

ExBlo

82

1

3

Bit

0x10 (5)

Blo TripCmd

82

1

3

Bit

0x20 (6)

ExBlo TripCmd

82

1

3

Bit

0x40 (7)

Page 74

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

82

1

3

Format

Bit Mask

Unit

Description

-

Signal: Alarm Negative Sequence

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

/ (Bit Position)

Functions Alarm

Bit

0x80 (8)

Trip (*)

82

1

3

Bit

0x100 (9)

TripCmd (*)

82

1

3

Bit

0x200 (10)

I2>[2] ExBlo1-I

83

1

3

Struct

83

1

3

Bit

0x1 (1)

ExBlo2-I

83

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

83

1

3

Bit

0x4 (3)

active

83

1

3

Bit

0x8 (4)

ExBlo

83

1

3

Bit

0x10 (5)

Blo TripCmd

83

1

3

Bit

0x20 (6)

ExBlo TripCmd

83

1

3

Bit

0x40 (7)

EN MRA4 Modbus 05/10

Page 75

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

83

1

3

Format

Bit Mask

Unit

Description

-

Signal: Alarm Negative Sequence

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

/ (Bit Position)

Functions Alarm

Bit

0x80 (8)

Trip (*)

83

1

3

Bit

0x100 (9)

TripCmd (*)

83

1

3

Bit

0x200 (10)

V[5] ExBlo1-I

92

1

3

Struct

92

1

3

Bit

0x1 (1)

ExBlo2-I

92

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

92

1

3

Bit

0x4 (3)

active

92

1

3

Bit

0x8 (4)

ExBlo

92

1

3

Bit

0x10 (5)

Blo TripCmd

92

1

3

Bit

0x20 (6)

ExBlo TripCmd

92

1

3

Bit

0x40 (7)

Page 76

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

92

1

3

Format

Bit Mask

Unit

Description

-

Signal: Alarm voltage stage

-

Signal: Alarm L1

-

Signal: Alarm L2

-

Signal: Alarm L3

-

Signal: Trip

-

Signal: General Trip Phase L1

-

Signal: General Trip Phase L2

-

Signal: General Trip Phase L3

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

/ (Bit Position)

Functions Alarm

Bit

0x80 (8)

Alarm L1

92

1

3

Bit

0x100 (9)

Alarm L2

92

1

3

Bit

0x200 (10)

Alarm L3

92

1

3

Bit

0x400 (11)

Trip (*)

92

1

3

Bit

0x800 (12)

Trip L1 (*)

92

1

3

Bit

0x1000 (13)

Trip L2 (*)

92

1

3

Bit

0x2000 (14)

Trip L3 (*)

92

1

3

Bit

0x4000 (15)

TripCmd (*)

92

1

3

Bit

0x8000 (16)

V[6] ExBlo1-I

93

1

3

Struct

93

1

3

Bit

0x1 (1)

ExBlo2-I

93

1

3

Bit

0x2 (2)

EN MRA4 Modbus 05/10

Page 77

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

93

1

3

Format

Bit Mask

Unit

Description

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

-

Signal: Alarm voltage stage

-

Signal: Alarm L1

-

Signal: Alarm L2

-

Signal: Alarm L3

-

Signal: Trip

-

Signal: General Trip Phase L1

/ (Bit Position)

Functions ExBlo TripCmd-I

Bit

0x4 (3)

active

93

1

3

Bit

0x8 (4)

ExBlo

93

1

3

Bit

0x10 (5)

Blo TripCmd

93

1

3

Bit

0x20 (6)

ExBlo TripCmd

93

1

3

Bit

0x40 (7)

Alarm

93

1

3

Bit

0x80 (8)

Alarm L1

93

1

3

Bit

0x100 (9)

Alarm L2

93

1

3

Bit

0x200 (10)

Alarm L3

93

1

3

Bit

0x400 (11)

Trip (*)

93

1

3

Bit

0x800 (12)

Trip L1 (*)

93

1

3

Bit

0x1000 (13)

Page 78

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

93

1

3

Format

Bit Mask

Unit

Description

-

Signal: General Trip Phase L2

-

Signal: General Trip Phase L3

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

/ (Bit Position)

Functions Trip L2 (*)

Bit

0x2000 (14)

Trip L3 (*)

93

1

3

Bit

0x4000 (15)

TripCmd (*)

93

1

3

Bit

0x8000 (16)

V 012 [1] ExBlo1-I

100

1

3

Struct

100

1

3

Bit

0x1 (1)

ExBlo2-I

100

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

100

1

3

Bit

0x4 (3)

active

100

1

3

Bit

0x8 (4)

ExBlo

100

1

3

Bit

0x10 (5)

Blo TripCmd

100

1

3

Bit

0x20 (6)

ExBlo TripCmd

100

1

3

Bit

0x40 (7)

EN MRA4 Modbus 05/10

Page 79

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

100

1

3

Format

Bit Mask

Unit

Description

-

Signal: Alarm voltage asymmetry

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

/ (Bit Position)

Functions Alarm

Bit

0x80 (8)

Trip (*)

100

1

3

Bit

0x100 (9)

TripCmd (*)

100

1

3

Bit

0x200 (10)

V 012 [2] ExBlo1-I

101

1

3

Struct

101

1

3

Bit

0x1 (1)

ExBlo2-I

101

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

101

1

3

Bit

0x4 (3)

active

101

1

3

Bit

0x8 (4)

ExBlo

101

1

3

Bit

0x10 (5)

Blo TripCmd

101

1

3

Bit

0x20 (6)

ExBlo TripCmd

101

1

3

Bit

0x40 (7)

Page 80

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

101

1

3

Format

Bit Mask

Unit

Description

-

Signal: Alarm voltage asymmetry

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

/ (Bit Position)

Functions Alarm

Bit

0x80 (8)

Trip (*)

101

1

3

Bit

0x100 (9)

TripCmd (*)

101

1

3

Bit

0x200 (10)

V 012 [3] ExBlo1-I

102

1

3

Struct

102

1

3

Bit

0x1 (1)

ExBlo2-I

102

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

102

1

3

Bit

0x4 (3)

active

102

1

3

Bit

0x8 (4)

ExBlo

102

1

3

Bit

0x10 (5)

Blo TripCmd

102

1

3

Bit

0x20 (6)

ExBlo TripCmd

102

1

3

Bit

0x40 (7)

EN MRA4 Modbus 05/10

Page 81

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

102

1

3

Format

Bit Mask

Unit

Description

-

Signal: Alarm voltage asymmetry

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

/ (Bit Position)

Functions Alarm

Bit

0x80 (8)

Trip (*)

102

1

3

Bit

0x100 (9)

TripCmd (*)

102

1

3

Bit

0x200 (10)

V 012 [4] ExBlo1-I

103

1

3

Struct

103

1

3

Bit

0x1 (1)

ExBlo2-I

103

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

103

1

3

Bit

0x4 (3)

active

103

1

3

Bit

0x8 (4)

ExBlo

103

1

3

Bit

0x10 (5)

Blo TripCmd

103

1

3

Bit

0x20 (6)

ExBlo TripCmd

103

1

3

Bit

0x40 (7)

Page 82

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

103

1

3

Format

Bit Mask

Unit

Description

-

Signal: Alarm voltage asymmetry

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

/ (Bit Position)

Functions Alarm

Bit

0x80 (8)

Trip (*)

103

1

3

Bit

0x100 (9)

TripCmd (*)

103

1

3

Bit

0x200 (10)

V 012 [5] ExBlo1-I

104

1

3

Struct

104

1

3

Bit

0x1 (1)

ExBlo2-I

104

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

104

1

3

Bit

0x4 (3)

active

104

1

3

Bit

0x8 (4)

ExBlo

104

1

3

Bit

0x10 (5)

Blo TripCmd

104

1

3

Bit

0x20 (6)

ExBlo TripCmd

104

1

3

Bit

0x40 (7)

EN MRA4 Modbus 05/10

Page 83

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

104

1

3

Format

Bit Mask

Unit

Description

-

Signal: Alarm voltage asymmetry

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Module input state: External Blocking of the Trip Command

-

Signal: active

-

Signal: External Blocking

-

Signal: Trip Command blocked

-

Signal: External Blocking of the Trip Command

/ (Bit Position)

Functions Alarm

Bit

0x80 (8)

Trip (*)

104

1

3

Bit

0x100 (9)

TripCmd (*)

104

1

3

Bit

0x200 (10)

V 012 [6] ExBlo1-I

105

1

3

Struct

105

1

3

Bit

0x1 (1)

ExBlo2-I

105

1

3

Bit

0x2 (2)

ExBlo TripCmd-I

105

1

3

Bit

0x4 (3)

active

105

1

3

Bit

0x8 (4)

ExBlo

105

1

3

Bit

0x10 (5)

Blo TripCmd

105

1

3

Bit

0x20 (6)

ExBlo TripCmd

105

1

3

Bit

0x40 (7)

Page 84

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

105

1

3

Format

Bit Mask

Unit

Description

-

Signal: Alarm voltage asymmetry

-

Signal: Trip

-

Signal: Trip Command

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Signal: active

-

Signal: External Blocking

-

Signal: Maximum permissible Summation of the interruppting (tripping) currents exceeded in at least one phase.

/ (Bit Position)

Functions Alarm

Bit

0x80 (8)

Trip (*)

105

1

3

Bit

0x100 (9)

TripCmd (*)

105

1

3

Bit

0x200 (10)

BW ExBlo1-I

123

1

3

Struct

123

1

3

Bit

0x1 (1)

ExBlo2-I

123

1

3

Bit

0x2 (2)

active

123

1

3

Bit

0x4 (3)

ExBlo

123

1

3

Bit

0x8 (4)

Isum Intr trip

123

1

3

Bit

0x10 (5)

EN MRA4 Modbus 05/10

Page 85

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

123

1

3

Format

Bit Mask

Unit

Description

-

Signal: Maximum permissible Summation of the interruppting (tripping) currents exceeded: IL1

-

Signal: Maximum permissible Summation of the interruppting (tripping) currents exceeded: IL2

-

Signal: Maximum permissible Summation of the interruppting (tripping) currents exceeded: IL3

-

Signal: Service Alarm, too many Operations

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Signal: active

/ (Bit Position)

Functions Isum Intr trip: IL1

Bit

0x20 (6)

Isum Intr trip: IL2

123

1

3

Bit

0x40 (7)

Isum Intr trip: IL3

123

1

3

Bit

0x80 (8)

Operations Alarm

123

1

3

Bit

0x100 (9)

CTS ExBlo1-I

137

1

3

Struct

137

1

3

Bit

0x1 (1)

ExBlo2-I

137

1

3

Bit

0x2 (2)

active

137

1

3

Bit

0x4 (3)

Page 86

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

137

1

3

Format

Bit Mask

Unit

Description

-

Signal: External Blocking

-

Signal: Alarm Current Transformer Measuring Circuit Supervision

-

Signal: active

-

Signal: IRIG-B inverted

-

Signal: IRIG-B Control Signal

-

Signal: IRIG-B Control Signal

-

Signal: IRIG-B Control Signal

-

Signal: IRIG-B Control Signal

-

Signal: IRIG-B Control Signal

-

Signal: IRIG-B Control Signal

/ (Bit Position)

Functions ExBlo

Bit

0x8 (4)

Alarm

137

1

3

Bit

0x10 (5)

IRIG-B active

148

1

3

Struct

148

1

3

Bit

0x1 (1)

inverted

148

1

3

Bit

0x2 (2)

Control Signal1

148

1

3

Bit

0x4 (3)

Control Signal2

148

1

3

Bit

0x8 (4)

Control Signal4

148

1

3

Bit

0x10 (5)

Control Signal5

148

1

3

Bit

0x20 (6)

Control Signal6

148

1

3

Bit

0x40 (7)

Control Signal7

148

1

3

Bit

0x80 (8)

EN MRA4 Modbus 05/10

Page 87

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

148

1

3

Format

Bit Mask

Unit

Description

-

Signal: IRIG-B Control Signal

-

Signal: IRIG-B Control Signal

-

Signal: IRIG-B Control Signal

-

Signal: IRIG-B Control Signal

-

Signal: IRIG-B Control Signal

-

Signal: IRIG-B Control Signal

-

Signal: IRIG-B Control Signal

-

Signal: IRIG-B Control Signal

-

Signal: IRIG-B Control Signal

-

Signal: IRIG-B Control Signal

-

Signal: IRIG-B Control Signal

/ (Bit Position)

Functions Control Signal8

Bit

0x100 (9)

Control Signal9

148

1

3

Bit

0x200 (10)

Control Signal10

148

1

3

Bit

0x400 (11)

Control Signal11

148

1

3

Bit

0x800 (12)

Control Signal12

148

1

3

Bit

0x1000 (13)

Control Signal13

148

1

3

Bit

0x2000 (14)

Control Signal14

148

1

3

Bit

0x4000 (15)

Control Signal15

148

1

3

Bit

0x8000 (16)

IRIG-B Control Signal16

149

1

3

Struct

149

1

3

Bit

0x1 (1)

Control Signal17

149

1

3

Bit

0x2 (2)

Control Signal18

149

1

3

Bit

0x4 (3)

Page 88

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

150

1

3

Struct

150

1

3

Bit

Bit Mask

Unit

Description

-

Module input state: External blocking1

-

Module input state: External blocking2

-

Signal: active

-

Signal: External Blocking

-

Signal: Alarm Trip Circuit Supervision

-

Not possible because no state indicator assigned to the breaker.

-

Module input state: Criterion by which the Circuit Breaker Switch Position is to be detected.

-

Position indicator/check-back signal of the CB (52a)

/ (Bit Position)

Functions TCS ExBlo1-I

0x1 (1)

ExBlo2-I

150

1

3

Bit

0x2 (2)

active

150

1

3

Bit

0x4 (3)

ExBlo

150

1

3

Bit

0x8 (4)

Alarm

150

1

3

Bit

0x10 (5)

Not Possible

150

1

3

Bit

0x20 (6)

CB Pos Detect-I

150

1

3

Bit

0xc0 (7)

Aux ON

150

1

3

Bit

0x100 (9)

EN MRA4 Modbus 05/10

Page 89

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

150

1

3

Format

Bit Mask

Unit

Description

-

Module input state: Position indicator/check-back signal of the CB (52b)

-

Module input state: External AR lockout.

-

Module input state: The AR Shot counter will be incremented by this external Signal. This can be used for Zone Coordination (of upstream Auto Reclosure devices). Note: This parameter enables the functionallity only. The assignment has to be set within the global parameters.

-

Signal: Auto Reclosure is blocked

/ (Bit Position)

Functions Aux OFF

Bit

0x200 (10)

AR Ex Lock-I

156

1

3

Struct

156

1

3

Bit

0x1 (1)

Ex Shot Inc-I

156

1

3

Bit

0x2 (2)

Blo

156

1

3

Bit

0x4 (3)

Page 90

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup

Start Register Address

No. of Modbus Registers

Function Code

t-Blo after CB man ON

156

1

3

Lock

156

Names

Format

Bit Mask

Unit

Description

-

Signal: AR blocked after circuit breaker was switched on manually. This timer will be started if the circuit breaker was switched on manually. While this timer is running, AR cannot be started.

-

Signal: Auto Reclosure is locked out

-

Signal: Delay Timer for resetting the AR lockout. The reset of the AR lockout state will be delayed for this time, after the reset signal (e.g digital input or Scada) has been detected .

-

Signal: Ready to shoot

/ (Bit Position)

Functions Bit

0x8 (4)

1

3

Bit

0x10 (5)

t-Reset Lockout

156

1

3

Bit

0x20 (6)

Ready

156

1

3

Bit

0x40 (7)

EN MRA4 Modbus 05/10

Page 91

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

156

1

3

Format

Bit Mask

Unit

Description

-

Signal: Examination Time: If the Circuit Breaker remains after an reclosure attempt for the duration of this timer in the Closed position, the AR has been successful and the AR module returns into the ready state.

-

Signal: Standby

-

Signal: AR - Service Alarm 1, too many switching operations

-

Signal: AR - Service Alarm 2 - too many switching operations

-

Signal: The maximum allowed number of shots per hour has been exceeded.

-

Module input state: External blocking1

/ (Bit Position)

Functions t-Run2Ready

Bit

0x80 (8)

Standby

156

1

3

Bit

0x100 (9)

Service Alarm 1

156

1

3

Bit

0x200 (10)

Service Alarm 2

156

1

3

Bit

0x400 (11)

Max Shots / h exceeded

Q->&V< ExBlo1-I

156

1

3

Bit

0x800 (12)

157

1

3

Struct

157

1

3

Bit

0x1 (1)

Page 92

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

157

1

3

Format

Bit Mask

Unit

Description

-

Module input state: External blocking2

-

Signal: active

-

Signal: External Blocking

-

Signal: Blocked by Fuse Failure (VT)

-

Signal: Alarm Reactive Power Undervoltage Protection

-

Module input state: Release signal is beeing generated by the PCC (External Release)

-

Signal: Voltage Release from the Point of Common Coupling

-

Signal: Release Energy Resource. Internal (local) voltage release

-

Signal: Decoupling at the Point of Common Coupling

/ (Bit Position)

Functions ExBlo2-I

Bit

0x2 (2)

active

157

1

3

Bit

0x4 (3)

ExBlo

157

1

3

Bit

0x8 (4)

Fuse Fail VT Blo

157

1

3

Bit

0x10 (5)

Alarm

157

1

3

Bit

0x20 (6)

V Ext Release PCC

157

1

3

Bit

0x40 (7)

PCC (External Release)

157

Release Energy Resource

157

Decoupling PCC

157

1

3

Bit

0x80 (8)

1

3

Bit

0x100 (9)

1

3

Bit

0x200 (10)

EN MRA4 Modbus 05/10

Page 93

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

157

1

3

Format

Bit Mask

Unit

Description

-

Signal: Decoupling of the (local) Energy Resource

-

Signal: Digital Input

-

Signal: Digital Input

-

Signal: Digital Input

-

Signal: Digital Input

-

Signal: Digital Input

-

Signal: Digital Input

-

Signal: Digital Input

-

Signal: Digital Input

-

Signal: Digital Input

/ (Bit Position)

Functions Decoupling Energy Resource DI Slot X1 DI 1

Bit

0x400 (11)

1000

1

3

Struct

1000

1

3

Bit

0x1 (1)

DI 2

1000

1

3

Bit

0x2 (2)

DI 3

1000

1

3

Bit

0x4 (3)

DI 4

1000

1

3

Bit

0x8 (4)

DI 5

1000

1

3

Bit

0x10 (5)

DI 6

1000

1

3

Bit

0x20 (6)

DI 7

1000

1

3

Bit

0x40 (7)

DI 8

1000

1

3

Bit

0x80 (8)

DI Slot X6 DI 1

1001

1

3

Struct

1001

1

3

Bit

0x1 (1)

Page 94

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

1001

1

3

Format

Bit Mask

Unit

Description

-

Signal: Digital Input

-

Signal: Digital Input

-

Signal: Digital Input

-

Signal: Digital Input

-

Signal: Digital Input

-

Signal: Digital Input

-

Signal: Digital Input

-

Signal: Binary Output Relay

-

Signal: Binary Output Relay

-

Signal: Binary Output Relay

-

Signal: Binary Output Relay

/ (Bit Position)

Functions DI 2

Bit

0x2 (2)

DI 3

1001

1

3

Bit

0x4 (3)

DI 4

1001

1

3

Bit

0x8 (4)

DI 5

1001

1

3

Bit

0x10 (5)

DI 6

1001

1

3

Bit

0x20 (6)

DI 7

1001

1

3

Bit

0x40 (7)

DI 8

1001

1

3

Bit

0x80 (8)

BO Slot X2 BO 1

1003

1

3

Struct

1003

1

3

Bit

0x1 (1)

BO 2

1003

1

3

Bit

0x2 (2)

BO 3

1003

1

3

Bit

0x4 (3)

BO 4

1003

1

3

Bit

0x8 (4)

EN MRA4 Modbus 05/10

Page 95

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

1003

1

3

Format

Bit Mask

Unit

Description

-

Signal: Binary Output Relay

-

Signal: Binary Output Relay

-

Signal: CAUTION! RELAYS DISARMED in order to safely perform maintenance while eliminating the risk of taking an entire process offline. (Note: The Self Supervision Contact cannot be disarmed). YOU MUST ENSURE that the relays are ARMED AGAIN after maintenance

-

Signal: The State of at least one Relay Output has been set by force. That means that the state of at least one Relay is forced and hence does not show the state of the assigned signals.

/ (Bit Position)

Functions BO 5

Bit

0x10 (5)

BO 6

1003

1

3

Bit

0x20 (6)

DISARMED!

1003

1

3

Bit

0x40 (7)

Outs forced

1003

1

3

Bit

0x80 (8)

BO Slot X5

Page 96

1004

1

3

Struct

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

1004

1

3

Format

Bit Mask

Unit

Description

-

Signal: Binary Output Relay

-

Signal: Binary Output Relay

-

Signal: Binary Output Relay

-

Signal: Binary Output Relay

-

Signal: Binary Output Relay

-

Signal: Binary Output Relay

-

Signal: CAUTION! RELAYS DISARMED in order to safely perform maintenance while eliminating the risk of taking an entire process offline. (Note: The Self Supervision Contact cannot be disarmed). YOU MUST ENSURE that the relays are ARMED AGAIN after maintenance

/ (Bit Position)

Functions BO 1

Bit

0x1 (1)

BO 2

1004

1

3

Bit

0x2 (2)

BO 3

1004

1

3

Bit

0x4 (3)

BO 4

1004

1

3

Bit

0x8 (4)

BO 5

1004

1

3

Bit

0x10 (5)

BO 6

1004

1

3

Bit

0x20 (6)

DISARMED!

1004

1

3

Bit

0x40 (7)

EN MRA4 Modbus 05/10

Page 97

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

1004

1

3

Format

Bit Mask

Unit

Description

-

Signal: The State of at least one Relay Output has been set by force. That means that the state of at least one Relay is forced and hence does not show the state of the assigned signals.

-

Scada Command

-

Scada Command

-

Scada Command

-

Scada Command

-

Scada Command

-

Scada Command

-

Scada Command

/ (Bit Position)

Functions Outs forced

Bit

0x80 (8)

Modbus Scada Cmd 1

1005

1

3

Struct

1005

1

3

Bit

0x1 (1)

Scada Cmd 2

1005

1

3

Bit

0x2 (2)

Scada Cmd 3

1005

1

3

Bit

0x4 (3)

Scada Cmd 4

1005

1

3

Bit

0x8 (4)

Scada Cmd 5

1005

1

3

Bit

0x10 (5)

Scada Cmd 6

1005

1

3

Bit

0x20 (6)

Scada Cmd 7

1005

1

3

Bit

0x40 (7)

Page 98

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

1005

1

3

Format

Bit Mask

Unit

Description

-

Scada Command

-

Scada Command

-

Scada Command

-

Scada Command

-

Scada Command

-

Scada Command

-

Scada Command

-

Scada Command

-

Scada Command

-

Signal: SCADA active

/ (Bit Position)

Functions Scada Cmd 8

Bit

0x80 (8)

Scada Cmd 9

1005

1

3

Bit

0x100 (9)

Scada Cmd 10

1005

1

3

Bit

0x200 (10)

Scada Cmd 11

1005

1

3

Bit

0x400 (11)

Scada Cmd 12

1005

1

3

Bit

0x800 (12)

Scada Cmd 13

1005

1

3

Bit

0x1000 (13)

Scada Cmd 14

1005

1

3

Bit

0x2000 (14)

Scada Cmd 15

1005

1

3

Bit

0x4000 (15)

Scada Cmd 16

1005

1

3

Bit

0x8000 (16)

Modbus Transmission

1006

1

3

Struct

1006

1

3

Bit

0x1 (1)

CB

EN MRA4 Modbus 05/10

1010

1

3

Struct

Page 99

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

1010

1

3

Format

Bit Mask

Unit

Description

-

Signal: Circuit breaker is ready for operation.

-

Signal: Circuit Breaker Position (0 = Indeterminate, 1 = OFF, 2 = ON, 3 = Disturbed)

-

Signal: Circuit Breaker is in Indeterminate Position

-

Signal: Circuit Breaker is in OFFPosition

-

Signal: Circuit Breaker is in ONPosition

-

Signal: Circuit Breaker Disturbed Undefined Breaker Position. The Position Indicators contradict themselves. After expiring of a supervision timer this signal becomes true.

/ (Bit Position)

Functions Ready

Bit

0x1 (1)

Pos

1010

1

3

Bit

0x6 (2)

Pos Indeterm

1010

1

3

Bit

0x8 (4)

Pos OFF

1010

1

3

Bit

0x10 (5)

Pos ON

1010

1

3

Bit

0x20 (6)

Pos Disturb

1010

1

3

Bit

0x40 (7)

Legend * = These Signals have to be acknowledged by the Scada System.

Page 100

EN MRA4 Modbus 05/10

Appendix - Data Point Lists

Measuring values Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

20000

6

4

Struct

20000

6

4

Short

Bit Mask

Unit

Description

-

year

-

month

-

days

-

hours

-

minute

-

milliseconds

/ (Bit Position)

Functions Date and Time y

Word 0 (1)

m

20000

6

4

Short

Word 1 (17)

d

20000

6

4

Short

Word 2 (33)

h

20000

6

4

Short

Word 3 (49)

min

20000

6

4

Short

Word 4 (65)

ms

20000

6

4

Short

Word 5 (81)

BW

TripCmd Cr

20006

2

4

Float IEE754

-

Counter: Total number of trips of the switchgear (circuit breaker, load break switch…).

Values

Build

20008

2

4

Float IEE754

-

Build

Values

Operating hours Cr

20010

2

4

Float IEE754

h

Operating hours counter

EN MRA4 Modbus 05/10

Page 101

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions Current

IL1

20100

2

4

Float IEE754

A

Measured value: Phase current (fundamental)

Current

IL2

20102

2

4

Float IEE754

A

Measured value: Phase current (fundamental)

Current

IL3

20104

2

4

Float IEE754

A

Measured value: Phase current (fundamental)

Current

IG meas

20106

2

4

Float IEE754

A

Measured value (measured): IG (fundamental)

ThR

Thermal Cap Used

20110

2

4

Float IEE754

%

Measured value: Thermal Capacity Used

ThR

Time To Trip

20112

2

4

Float IEE754

s

Measured value (calculated/measured ): Remaining time until the thermal overload module will trip

Current

I0

20114

2

4

Float IEE754

A

Measured value (calculated): Zero current (fundamental)

Current

I1

20116

2

4

Float IEE754

A

Measured value (calculated): Positive phase sequence current (fundamental)

Page 102

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions Current

I2

20118

2

4

Float IEE754

A

Measured value (calculated): Unbalanced load current (fundamental)

Current

IL1 H2

20120

2

4

Float IEE754

%

Measured value: 2nd harmonic/1st harmonic of IL1

Current

IL2 H2

20122

2

4

Float IEE754

%

Measured value: 2nd harmonic/1st harmonic of IL2

Current

IL3 H2

20124

2

4

Float IEE754

%

Measured value: 2nd harmonic/1st harmonic of IL3

Current

IG H2 meas

20126

2

4

Float IEE754

%

Measured value: 2nd harmonic/1st harmonic of IG (measured)

Voltage

f

20128

2

4

Float IEE754

Hz

Measured value: Frequency

Voltage

VL12

20130

2

4

Float IEE754

V

Measured value: Phase-to-phase voltage (fundamental)

Voltage

VL23

20132

2

4

Float IEE754

V

Measured value: Phase-to-phase voltage (fundamental)

EN MRA4 Modbus 05/10

Page 103

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions Voltage

VL31

20134

2

4

Float IEE754

V

Measured value: Phase-to-phase voltage (fundamental)

Voltage

VL1

20136

2

4

Float IEE754

V

Measured value: Phase-to-neutral voltage (fundamental)

Voltage

VL2

20138

2

4

Float IEE754

V

Measured value: Phase-to-neutral voltage (fundamental)

Voltage

VL3

20140

2

4

Float IEE754

V

Measured value: Phase-to-neutral voltage (fundamental)

Voltage

VG meas

20142

2

4

Float IEE754

V

Measured value (measured): VG measured (fundamental)

Voltage

V0

20146

2

4

Float IEE754

V

Measured value (calculated): Symmetrical components Zero voltage(fundamental)

Voltage

V1

20148

2

4

Float IEE754

V

Measured value (calculated): Symmetrical components positive phase sequence voltage(fundamental)

Page 104

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions Voltage

V2

20150

2

4

Float IEE754

V

Measured value (calculated): Symmetrical components negative phase sequence voltage(fundamental)

EnergyCr

cos phi

20152

2

4

Float IEE754

-

Measured value (calculated): Power factor

EnergyCr

P

20154

2

4

Float IEE754

W

Measured value (calculated): Active power (P- = Fed Active Power, P+ = Consumpted Active Power) (fundamental)

EnergyCr

Q

20156

2

4

Float IEE754

VAr

Measured value (calculated): Reactive power (Q- = Fed Reactive Power, Q+ = Consumpted Reactive Power) (fundamental)

EnergyCr

S

20158

2

4

Float IEE754

VA

Measured Value (Calculated): Apparent power (fundamental)

Current

IG calc

20160

2

4

Float IEE754

A

Measured value (calculated): IG (fundamental)

EN MRA4 Modbus 05/10

Page 105

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions Voltage

VG calc

20162

2

4

Float IEE754

V

Measured value (calculated): VG (fundamental)

AR

Total number Cr

20164

2

4

Float IEE754

-

Total number of all executed Automatic Reclosures Attempts

AR

Cr failed

20166

2

4

Float IEE754

-

Total number of unsuccessfully executed automatic reclosure attempts

AR

Cr successfl

20168

2

4

Float IEE754

-

Total number of successfully executed Automatic Reclosures

AR

Cr Service Alarm1

20170

2

4

Float IEE754

-

Remaining numbers of ARs until Service Alarm 1

AR

Cr Service Alarm2

20172

2

4

Float IEE754

-

Remaining numbers of ARs until Service Alarm 2

EnergyCr

Wp+

20174

2

4

Float IEE754

kWh

Positive Active Power is consumed active energy

EnergyCr

Wp-

20176

2

4

Float IEE754

kWh

Negative Active Power (Fed Energy)

EnergyCr

Wq+

20178

2

4

Float IEE754

kVArh

Positive Reactive Power is consumed Reactive Energy

Page 106

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions EnergyCr

Wq-

20180

2

4

Float IEE754

kVArh

Negative Reactive Power (Fed Energy)

BW

Sum trip IL1

20182

2

4

Float IEE754

A

Summation of the tripping currents phase1

BW

Sum trip IL2

20184

2

4

Float IEE754

A

Summation of the tripping currents phase2

BW

Sum trip IL3

20186

2

4

Float IEE754

A

Summation of the tripping currents phase3

AR

AR Shot No.

20188

2

4

Float IEE754

-

Counter - Auto Reclosure Attempts

Current

phi IG calc

20200

2

4

Float IEE754

°

Measured value (calculated): Angle of Phasor IG calc

Current

phi IG meas

20202

2

4

Float IEE754

°

Measured value: Angle of Phasor IG meas

Current

phi IL1

20204

2

4

Float IEE754

°

Measured value (calculated): Angle of Phasor IL1

Current

phi IL2

20206

2

4

Float IEE754

°

Measured value (calculated): Angle of Phasor IL2

Current

phi IL3

20208

2

4

Float IEE754

°

Measured value (calculated): Angle of Phasor IL3

EN MRA4 Modbus 05/10

Page 107

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions IRIG-B

Edges

20298

2

4

Float IEE754

-

Edges

IRIG-B

NoOfFrameErrors

20300

2

4

Float IEE754

-

Total Number of Frame Errors. Physically corrupted Frame.

IRIG-B

NoOfFramesOK

20302

2

4

Float IEE754

-

Total Number valid Frames.

Current

IL1 RMS

20316

2

4

Float IEE754

A

Measured value: Phase current (RMS)

Current

IL2 RMS

20318

2

4

Float IEE754

A

Measured value: Phase current (RMS)

Current

IL3 RMS

20320

2

4

Float IEE754

A

Measured value: Phase current (RMS)

Current

IG meas RMS

20322

2

4

Float IEE754

A

Measured value (measured): IG (RMS)

Current

IG calc RMS

20324

2

4

Float IEE754

A

Measured value (calculated): IG (RMS)

AR

Max Shots / h Cr

20374

2

4

Float IEE754

-

Counter for the maximum allowed shots per hour.

Current

%(I2/I1)

20376

2

4

Float IEE754

%

Measured value (calculated): I2/I1 if ABC, I1/I2 if CBA

Page 108

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions Current

phi I0

20378

2

4

Float IEE754

°

Measured value (calculated): Angle Zero Sequence System

Current

phi I1

20380

2

4

Float IEE754

°

Measured value (calculated): Angle of Positive Sequence System

Current

phi I2

20382

2

4

Float IEE754

°

Measured Value (calculated): Angle of Negative Sequence System

Voltage

phi VG calc

20386

2

4

Float IEE754

°

Measured value (calculated): Angle of Phasor VG calc

Voltage

phi VG meas

20388

2

4

Float IEE754

°

Measured value: Angle of Phasor VG meas

Voltage

phi VL12

20390

2

4

Float IEE754

°

Measured value (calculated): Angle of Phasor VL12

Voltage

phi VL1

20392

2

4

Float IEE754

°

Measured value (calculated): Angle of Phasor VL1

Voltage

phi VL23

20394

2

4

Float IEE754

°

Measured value (calculated): Angle of Phasor VL23

Voltage

phi VL2

20396

2

4

Float IEE754

°

Measured value (calculated): Angle of Phasor VL2

EN MRA4 Modbus 05/10

Page 109

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions Voltage

phi VL31

20398

2

4

Float IEE754

°

Measured value (calculated): Angle of Phasor VL31

Voltage

phi VL3

20400

2

4

Float IEE754

°

Measured value (calculated): Angle of Phasor VL3

Voltage

phi V0

20402

2

4

Float IEE754

°

Measured value (calculated): Angle Zero Sequence System

Voltage

phi V1

20404

2

4

Float IEE754

°

Measured value (calculated): Angle of Positive Sequence System

Voltage

phi V2

20406

2

4

Float IEE754

°

Measured Value (calculated): Angle of Negative Sequence System

Voltage

VG calc RMS

20432

2

4

Float IEE754

V

Measured value (calculated): VG (RMS)

Voltage

VG meas RMS

20434

2

4

Float IEE754

V

Measured value (measured): VG measured (RMS)

Voltage

VL1 RMS

20436

2

4

Float IEE754

V

Measured value: Phase-to-neutral voltage (RMS)

Voltage

VL12 RMS

20438

2

4

Float IEE754

V

Measured value: Phase-to-phase voltage (RMS)

Page 110

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions Voltage

VL2 RMS

20440

2

4

Float IEE754

V

Measured value: Phase-to-neutral voltage (RMS)

Voltage

VL23 RMS

20442

2

4

Float IEE754

V

Measured value: Phase-to-phase voltage (RMS)

Voltage

VL3 RMS

20444

2

4

Float IEE754

V

Measured value: Phase-to-neutral voltage (RMS)

Voltage

VL31 RMS

20446

2

4

Float IEE754

V

Measured value: Phase-to-phase voltage (RMS)

Voltage

%(V2/V1)

20450

2

4

Float IEE754

%

Measured value (calculated): %V2/V1 if ABC, %V1/V2 if CBA

EnergyCr

P RMS

20452

2

4

Float IEE754

W

Measured value (calculated): Active power (P- = Fed Active Power, P+ = Consumpted Active Power) (RMS)

EnergyCr

S RMS

20454

2

4

Float IEE754

VA

Measured Value (Calculated): Apparent power (RMS)

EnergyCr

cos phi RMS

20456

2

4

Float IEE754

-

Measured value (calculated): Power factor

EN MRA4 Modbus 05/10

Page 111

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions EnergyCr

Wp Net

20460

2

4

Float IEE754

kWh

Absolute Active Power Hours

EnergyCr

Wq Net

20462

2

4

Float IEE754

kVArh

Absolute Reactive Power Hours

EnergyCr

Ws Net

20464

2

4

Float IEE754

kVAh

Absolute Apparent Power Hours

EnergyCr

P1

20496

2

4

Float IEE754

W

Measured value (calculated): Active power in positive sequence system (P= Fed Active Power, P+ = Consumpted Active Power)

EnergyCr

Q1

20498

2

4

Float IEE754

VAr

Measured value (calculated): Reactive power in positive sequence system (Q- = Fed Reactive Power, Q+ = Consumpted Reactive Power)

Current

IG H2 calc

20500

2

4

Float IEE754

%

Measured value (calculated): 2nd harmonic/1st harmonic of IG (calculated)

Voltage

f avg

21000

2

4

Float IEE754

Hz

Average frequency value

Page 112

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions Voltage

f max

21002

2

4

Float IEE754

Hz

Max. frequency value

Voltage

f min

21004

2

4

Float IEE754

Hz

Min. frequency value

Voltage

VL12 avg

21006

2

4

Float IEE754

V

VL12 average value (fundamental)

Voltage

VL12 max

21008

2

4

Float IEE754

V

VL12 maximum value (fundamental)

Voltage

VL12 min

21010

2

4

Float IEE754

V

VL12 minimum value (fundamental)

Voltage

VL23 avg

21012

2

4

Float IEE754

V

VL23 average value (fundamental)

Voltage

VL23 max

21014

2

4

Float IEE754

V

VL23 maximum value (fundamental)

Voltage

VL23 min

21016

2

4

Float IEE754

V

VL23 minimum value (fundamental)

Voltage

VL31 avg

21018

2

4

Float IEE754

V

VL31 average value (fundamental)

Voltage

VL31 max

21020

2

4

Float IEE754

V

VL31 maximum value (fundamental)

Voltage

VL31 min

21022

2

4

Float IEE754

V

VL31 minimum value (fundamental)

EN MRA4 Modbus 05/10

Page 113

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions Voltage

VL1 avg

21024

2

4

Float IEE754

V

VL1 average value (fundamental)

Voltage

VL1 max

21026

2

4

Float IEE754

V

VL1 maximum value (fundamental)

Voltage

VL1 min

21028

2

4

Float IEE754

V

VL1 minimum value (fundamental)

Voltage

VL2 avg

21030

2

4

Float IEE754

V

VL2 average value (fundamental)

Voltage

VL2 max

21032

2

4

Float IEE754

V

VL2 maximum value (fundamental)

Voltage

VL2 min

21034

2

4

Float IEE754

V

VL2 minimum value (fundamental)

Voltage

VL3 avg

21036

2

4

Float IEE754

V

VL3 average value (fundamental)

Voltage

VL3 max

21038

2

4

Float IEE754

V

VL3 maximum value (fundamental)

Voltage

VL3 min

21040

2

4

Float IEE754

V

VL3 minimum value (fundamental)

Voltage

V1 avg

21042

2

4

Float IEE754

V

Average value: Symmetrical components positive phase sequence voltage(fundamental)

Page 114

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions Voltage

V1 max

21044

2

4

Float IEE754

V

Maximum value: Symmetrical components positive phase sequence voltage(fundamental)

Voltage

V1 min

21046

2

4

Float IEE754

V

Minimum value: Symmetrical components positive phase sequence voltage(fundamental)

Voltage

V2 avg

21048

2

4

Float IEE754

V

Average value: Symmetrical components negative phase sequence voltage(fundamental)

Voltage

V2 max

21050

2

4

Float IEE754

V

Maximum value: Symmetrical components negative phase sequence voltage(fundamental)

Voltage

V2 min

21052

2

4

Float IEE754

V

Minimum value: Symmetrical components negative phase sequence voltage(fundamental)

Current

IL1 avg

21054

2

4

Float IEE754

A

IL1 average value (fundamental)

Current

IL1 max

21056

2

4

Float IEE754

A

IL1 maximum value (fundamental)

EN MRA4 Modbus 05/10

Page 115

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions Current

IL1 min

21058

2

4

Float IEE754

A

IL1 minimum value (fundamental)

Current

IL2 avg

21060

2

4

Float IEE754

A

IL2 average value (fundamental)

Current

IL2 max

21062

2

4

Float IEE754

A

IL2 maximum value (fundamental)

Current

IL2 min

21064

2

4

Float IEE754

A

IL2 minimum value (fundamental)

Current

IL3 avg

21066

2

4

Float IEE754

A

IL3 average value (fundamental)

Current

IL3 max

21068

2

4

Float IEE754

A

IL3 maximum value (fundamental)

Current

IL3 min

21070

2

4

Float IEE754

A

IL3 minimum value (fundamental)

Current

I1 avg

21072

2

4

Float IEE754

A

Average value positive phase sequence current (fundamental)

Current

I1 max

21074

2

4

Float IEE754

A

Maximum value positive phase sequence current (fundamental)

Current

I1 min

21076

2

4

Float IEE754

A

Minimum value positive phase sequence current (fundamental)

Page 116

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions Current

I2 avg

21078

2

4

Float IEE754

A

Average value unbalanced load current (fundamental)

Current

I2 max

21080

2

4

Float IEE754

A

Maximum value unbalanced load (fundamental)

Current

I2 min

21082

2

4

Float IEE754

A

Minimum value unbalanced load current (fundamental)

ThR

Thermal Cap avg

21084

2

4

Float IEE754

%

Thermal Capacity average value

ThR

Thermal Cap max

21086

2

4

Float IEE754

%

Thermal Capacity maximum value

ThR

Thermal Cap min

21088

2

4

Float IEE754

%

Thermal Capacity minimum value

EnergyCr

cos phi avg

21090

2

4

Float IEE754

-

Average of the power factor

EnergyCr

cos phi max

21092

2

4

Float IEE754

-

Maximum value of the power factor

EnergyCr

cos phi min

21094

2

4

Float IEE754

-

Minimum value of the power factor

EnergyCr

P avg

21096

2

4

Float IEE754

W

Average of the active power (fundamental)

EN MRA4 Modbus 05/10

Page 117

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions EnergyCr

P max

21098

2

4

Float IEE754

W

Maximum value of the active power (fundamental)

EnergyCr

P min

21100

2

4

Float IEE754

W

Minimum value of the active power (fundamental)

EnergyCr

Q avg

21102

2

4

Float IEE754

VAr

Average of the reactive power (fundamental)

EnergyCr

Q max

21104

2

4

Float IEE754

VAr

Maximum value of the reactive power (fundamental)

EnergyCr

Q min

21106

2

4

Float IEE754

VAr

Minimum value of the reactive power (fundamental)

EnergyCr

S avg

21108

2

4

Float IEE754

VA

Average of the apparent power (fundamental)

EnergyCr

S max

21110

2

4

Float IEE754

VA

Maximum value of the apparent power (fundamental)

EnergyCr

S min

21112

2

4

Float IEE754

VA

Minimum value of the apparent power (fundamental)

Page 118

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions Statistics

MeasPointNo

21114

2

4

Float IEE754

-

Each measuring point that is taken over by the statistics increments this counter. By means of this counter, the User can check whether the statistics are alive and if data are being acquired.

Current

IL1 avg RMS

21130

2

4

Float IEE754

A

IL1 average value (RMS)

Current

IL2 avg RMS

21132

2

4

Float IEE754

A

IL2 average value (RMS)

Current

IL3 avg RMS

21134

2

4

Float IEE754

A

IL3 average value (RMS)

Current

IL1 max RMS

21136

2

4

Float IEE754

A

IL1 maximum value (RMS)

Current

IL2 max RMS

21138

2

4

Float IEE754

A

IL2 maximum value (RMS)

Current

IL3 max RMS

21140

2

4

Float IEE754

A

IL3 maximum value (RMS)

Current

IL1 min RMS

21142

2

4

Float IEE754

A

IL1 minimum value (RMS)

Current

IL2 min RMS

21144

2

4

Float IEE754

A

IL2 minimum value (RMS)

EN MRA4 Modbus 05/10

Page 119

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions Current

IL3 min RMS

21146

2

4

Float IEE754

A

IL3 minimum value (RMS)

Current

IG H2 meas avg

21220

2

4

Float IEE754

%

Measured value: Average ratio of 2nd harmonic over fundamental of IG (measured)

Current

IG H2 meas max

21222

2

4

Float IEE754

%

Measured value: Maximum ratio of 2nd harmonic over fundamental of IG (measured)

Current

IG H2 meas min

21224

2

4

Float IEE754

%

Measured value: Minimum ratio of 2nd harmonic over fundamental of IG (measured)

Current

IL1 H2 avg

21226

2

4

Float IEE754

%

Average ratio of 2nd harmonic over fundamental of IL1

Current

IL1 H2 max

21228

2

4

Float IEE754

%

Maximum ratio of 2nd harmonic over fundamental of IL1

Current

IL1 H2 min

21230

2

4

Float IEE754

%

Minimum ratio of 2nd harmonic over fundamental of IL1

Current

IL2 H2 avg

21232

2

4

Float IEE754

%

Average ratio of 2nd harmonic over fundamental of IL2

Page 120

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions Current

IL2 H2 max

21234

2

4

Float IEE754

%

Maximum ratio of 2nd harmonic over fundamental of IL2

Current

IL2 H2 min

21236

2

4

Float IEE754

%

Minimum ratio of 2nd harmonic over fundamental of IL2

Current

IL3 H2 avg

21238

2

4

Float IEE754

%

Average ratio of 2nd harmonic over fundamental of IL3

Current

IL3 H2 max

21240

2

4

Float IEE754

%

Maximum ratio of 2nd harmonic over fundamental of IL3

Current

IL3 H2 min

21242

2

4

Float IEE754

%

Minimum ratio of 2nd harmonic/1st harmonic minimum value of IL3

Current

IG calc avg RMS

21454

2

4

Float IEE754

A

Measured value (calculated):IG average value (RMS)

Current

IG calc max RMS

21456

2

4

Float IEE754

A

Measured value (calculated):IG maximum value (RMS)

Current

IG calc min RMS

21458

2

4

Float IEE754

A

Measured value (calculated):IG minimum value (RMS)

Current

IG meas avg RMS

21460

2

4

Float IEE754

A

Measured value: IG average value (RMS)

EN MRA4 Modbus 05/10

Page 121

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions Current

IG meas max RMS

21462

2

4

Float IEE754

A

Measured value: IG maximum value (RMS)

Current

IG meas min RMS

21464

2

4

Float IEE754

A

Measured value: IG minimum value (RMS)

Current

%(I2/I1) avg

21466

2

4

Float IEE754

%

Measured value (calculated): I2/I1 maximum value if ABC, I1/I2 if CBA

Current

%(I2/I1) max

21468

2

4

Float IEE754

%

Measured value (calculated): I2/I1 maximum value if ABC, I1/I2 if CBA

Current

%(I2/I1) min

21470

2

4

Float IEE754

%

%(I2/I1) min

Voltage

VG calc avg RMS

21496

2

4

Float IEE754

V

Measured value (calculated):VG average value (RMS)

Voltage

VG calc max RMS

21498

2

4

Float IEE754

V

Measured value (calculated):VG maximum value (RMS)

Voltage

VG calc min RMS

21500

2

4

Float IEE754

V

Measured value (calculated):VG minimum value (RMS)

Voltage

VG meas avg RMS

21502

2

4

Float IEE754

V

Measured value: VG average value (RMS)

Page 122

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions Voltage

VG meas max RMS

21504

2

4

Float IEE754

V

Measured value: VG maximum value (RMS)

Voltage

VG meas min RMS

21506

2

4

Float IEE754

V

Measured value: VG minimum value (RMS)

Voltage

VL12 avg RMS

21508

2

4

Float IEE754

V

VL12 average value (RMS)

Voltage

VL12 max RMS

21510

2

4

Float IEE754

V

VL12 maximum value (RMS)

Voltage

VL12 min RMS

21512

2

4

Float IEE754

V

VL12 average value (RMS)

Voltage

VL1 avg RMS

21514

2

4

Float IEE754

V

VL1 average value (RMS)

Voltage

VL1 max RMS

21516

2

4

Float IEE754

V

VL1 maximum value (RMS)

Voltage

VL1 min RMS

21518

2

4

Float IEE754

V

VL1 minimum value (RMS)

Voltage

VL23 avg RMS

21520

2

4

Float IEE754

V

VL23 average value (RMS)

Voltage

VL23 max RMS

21522

2

4

Float IEE754

V

VL23 maximum value (RMS)

Voltage

VL23 min RMS

21524

2

4

Float IEE754

V

VL23 average value (RMS)

EN MRA4 Modbus 05/10

Page 123

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions Voltage

VL2 avg RMS

21526

2

4

Float IEE754

V

VL2 average value (RMS)

Voltage

VL2 max RMS

21528

2

4

Float IEE754

V

VL2 maximum value (RMS)

Voltage

VL2 min RMS

21530

2

4

Float IEE754

V

VL2 minimum value (RMS)

Voltage

VL31 avg RMS

21532

2

4

Float IEE754

V

VL31 average value (RMS)

Voltage

VL31 max RMS

21534

2

4

Float IEE754

V

VL31 maximum value (RMS)

Voltage

VL31 min RMS

21536

2

4

Float IEE754

V

VL31 average value (RMS)

Voltage

VL3 avg RMS

21538

2

4

Float IEE754

V

VL3 average value (RMS)

Voltage

VL3 max RMS

21540

2

4

Float IEE754

V

VL3 maximum value (RMS)

Voltage

VL3 min RMS

21542

2

4

Float IEE754

V

VL3 minimum value (RMS)

Voltage

%(V2/V1) mit

21550

2

4

Float IEE754

%

Measured value (calculated):%V2/V1 average value

Voltage

%(V2/V1) max

21552

2

4

Float IEE754

%

Measured value (calculated):%V2/V1 maximum value

Page 124

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions Voltage

%(V2/V1) min

21554

2

4

Float IEE754

%

Measured value (calculated):%V2/V1 minimum value

EnergyCr

P avg

21556

2

4

Float IEE754

W

Average of the active power

EnergyCr

P max

21558

2

4

Float IEE754

W

Maximum value of the active power

EnergyCr

P min

21560

2

4

Float IEE754

W

Minimum value of the active power

EnergyCr

S avg

21562

2

4

Float IEE754

VA

Average of the apparent power

EnergyCr

S max

21564

2

4

Float IEE754

VA

Maximum value of the apparent power

EnergyCr

S min

21566

2

4

Float IEE754

VA

Minimum value of the apparent power

EnergyCr

cos phi avg RMS

21568

2

4

Float IEE754

-

Average of the power factor

EnergyCr

cos phi max RMS

21570

2

4

Float IEE754

-

Maximum value of the power factor

EnergyCr

cos phi min RMS

21572

2

4

Float IEE754

-

Minimum value of the power factor

EN MRA4 Modbus 05/10

Page 125

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions Current

IG H2 calc avg

21772

2

4

Float IEE754

%

Measured value (calculated): Average ratio of 2nd harmonic over fundamental of IG (calculated)

Current

IG H2 calc max

21774

2

4

Float IEE754

%

Measured value (calculated): Maximum ratio of 2nd harmonic over fundamental of IG (calculated)

Current

IG H2 calc min

21776

2

4

Float IEE754

%

IG H2 calc min

Page 126

EN MRA4 Modbus 05/10

Appendix - Data Point Lists

Commands Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions Acknowledge

LEDs

22000

1

5

0xFF00

-

LEDs

Acknowledge

Binary Outputs

22001

1

5

0xFF00

-

Binary Outputs

Acknowledge

Scada

22002

1

5

0xFF00

-

Scada

Acknowledge

Device

22003

1

5

0xFF00

-

Device

Acknowledge

Ack TripCmd

22005

1

5

0xFF00

-

Signal: Acknowledge Trip Command

Reset

Modbus diagnosis counter

22006

1

5

0xFF00

-

Modbus diagnosis counter

Reset

Wp+ Reset Cr

22007

1

5

Short

-

Wp+ Reset Counter

Reset

Wp- Reset Cr

22008

1

5

Short

-

Wp- Reset Counter

Reset

Wq+ Reset Cr

22009

1

5

Short

-

Wq+ Reset Counter

Reset

Wq- Reset Cr

22010

1

5

Short

-

Wq- Reset Counter

EN MRA4 Modbus 05/10

Page 127

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

Bit Mask

Unit

Description

/ (Bit Position)

Functions Reset

Res all Energy Cr

22011

1

5

Short

-

Reset of all Energy Counters

Reset

Res Sum trip

22012

1

5

Short

-

Reset summation of the tripping currents

Scada Cmd

Assbl Scada Cmd 1

22020

1

5

0xFF00=On

-

Assignable Scada Command

-

Assignable Scada Command

-

Assignable Scada Command

-

Assignable Scada Command

-

Assignable Scada Command

-

Assignable Scada Command

0x0000=Off Scada Cmd

Assbl Scada Cmd 2

22021

1

5

0xFF00=On 0x0000=Off

Scada Cmd

Assbl Scada Cmd 3

22022

1

5

0xFF00=On 0x0000=Off

Scada Cmd

Assbl Scada Cmd 4

22023

1

5

0xFF00=On 0x0000=Off

Scada Cmd

Assbl Scada Cmd 5

22024

1

5

0xFF00=On 0x0000=Off

Scada Cmd

Assbl Scada Cmd 6

22025

1

5

0xFF00=On 0x0000=Off

Page 128

EN MRA4 Modbus 05/10

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

22026

1

5

Format

Bit Mask

Unit

Description

-

Assignable Scada Command

-

Assignable Scada Command

-

Assignable Scada Command

-

Assignable Scada Command

-

Assignable Scada Command

-

Assignable Scada Command

-

Assignable Scada Command

/ (Bit Position)

Functions Scada Cmd

Assbl Scada Cmd 7

0xFF00=On 0x0000=Off

Scada Cmd

Assbl Scada Cmd 8

22027

1

5

0xFF00=On 0x0000=Off

Scada Cmd

Assbl Scada Cmd 9

22028

1

5

0xFF00=On 0x0000=Off

Scada Cmd

Assbl Scada Cmd 10 22029

1

5

0xFF00=On 0x0000=Off

Scada Cmd

Assbl Scada Cmd 11 22030

1

5

0xFF00=On 0x0000=Off

Scada Cmd

Assbl Scada Cmd 12 22031

1

5

0xFF00=On 0x0000=Off

Scada Cmd

Assbl Scada Cmd 13 22032

1

5

0xFF00=On 0x0000=Off

EN MRA4 Modbus 05/10

Page 129

Appendix - Data Point Lists Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

1

5

Format

Bit Mask

Unit

Description

-

Assignable Scada Command

-

Assignable Scada Command

-

Assignable Scada Command

/ (Bit Position)

Functions Scada Cmd

Assbl Scada Cmd 14 22033

0xFF00=On 0x0000=Off

Scada Cmd

Assbl Scada Cmd 15 22034

1

5

0xFF00=On 0x0000=Off

Scada Cmd

Assbl Scada Cmd 16 22035

1

5

0xFF00=On 0x0000=Off

PSet-Switch

Scada PS1

22050

1

5

0xFF00

-

Scada Setting Group1

PSet-Switch

Scada PS2

22051

1

5

0xFF00

-

Scada Setting Group2

PSet-Switch

Scada PS3

22052

1

5

0xFF00

-

Scada Setting Group3

PSet-Switch

Scada PS4

22053

1

5

0xFF00

-

Scada Setting Group4

AFRMS Mode

AFRMS SCADA

22054

1

5

0xFF00

-

Signal: Arcflash Reduction Maintenance SCADA Mode

Page 130

EN MRA4 Modbus 05/10

Appendix - Data Point Lists

Settings Module

Subgroup Names

Start Register Address

No. of Modbus Registers

Function Code

Format

32500

6

3 16

Struct

32500

6

3 16

Short

Bit Mask

Unit

Description

-

year

-

month

-

days

-

hours

-

minute

-

milliseconds

/ (Bit Position)

Functions Date and Time y

Word 0 (1)

m

32500

6

3 16

Short

Word 1 (17)

d

32500

6

3 16

Short

Word 2 (33)

h

32500

6

3 16

Short

Word 3 (49)

min

32500

6

3 16

Short

Word 4 (65)

ms

32500

6

3 16

Short

Word 5 (81)

EN MRA4 Modbus 05/10

Page 131

Appendix - Data Point Lists We appreciate your comments about the content of our publications. Please send comments to: [email protected] Please include the manual number from the front cover of this publication. Woodward SEG reserves the right to update any portion of this publication at any time. Information provided by Woodward SEG is believed to be correct and reliable. However, Woodward SEG assumes no responsibility unless otherwise expressly undertaken. © Woodward SEG, all rights reserved

Woodward SEG GmbH & Co. KG Krefelder Weg 47 ⋅ D – 47906 Kempen (Germany) Postfach 10 07 55 (P.O.Box) ⋅ D – 47884 Kempen (Germany) Phone: +49 (0) 21 52 145 1 Internet Homepage http://www.woodward-seg.com Documentation http://doc.seg-pp.com Sales Phone: +49 (0) 21 52 145 635 Telefax: +49 (0) 21 52 145 354 e-mail: [email protected] Service Phone: +49 (0) 21 52 145 614 ⋅ Fax: +49 (0) 21 52 145 455 e-mail: [email protected]