Download MR Tx Voltage regulator TAPCON® 260...
Voltage regulator TAPCON® 260 Operating Instructions 1801003/04 Protocol description for IEC 61850
© All rights reserved by Maschinenfabrik Reinhausen Copying and distribution of this document and utilization and communication of its contents are strictly prohibited unless expressly authorized. Offenders will be held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility model or ornamental design registration. The product may have been modified after this document went to press. We expressly reserve the right to make changes to the technical data, the design or the scope of delivery. Generally, the information provided and the arrangements agreed during processing of the relevant quotations and orders are binding. The original operating instructions were drawn up in German.
Table of Contents
Table of Contents 1
Introduction .................................................................................. 9
1.1
Manufacturer ............................................................................................. 9
1.2
Subject to change without notice .............................................................. 9
1.3
Completeness ........................................................................................... 9
1.4
Supporting documents ............................................................................ 10
1.5
Safekeeping ............................................................................................ 10
1.6
Notation conventions .............................................................................. 10
1.6.1
Abbreviations used ............................................................................................. 11
1.6.2
Hazard communication system ........................................................................... 12
1.6.3
Information system.............................................................................................. 13
2
Safety .......................................................................................... 15
2.1
General safety information ...................................................................... 15
2.2
Appropriate use ....................................................................................... 15
2.3
Inappropriate use .................................................................................... 16
2.4
Personnel qualification ............................................................................ 16
2.5
Operator duty of care .............................................................................. 16
3
Product description ................................................................... 19
3.1
Performance features ............................................................................. 21
3.2
Relay of the signals via IEC 61850 ......................................................... 22
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
3
Table of Contents
3.2.1
LLN0 - Logical node............................................................................................ 22
3.2.2
LPHD - Physical device ...................................................................................... 23
3.2.3
LPHD - Physical device ...................................................................................... 24
3.2.4
GGIO1 - IO card inputs ....................................................................................... 27
3.2.5
GGIO2 - UC1 card inputs ................................................................................... 28
3.2.6
GGIO3 - UC2 card inputs ................................................................................... 29
3.2.7
GGIO4 - UC3 card inputs (optional) ................................................................... 30
3.2.8
YLTC1 - On-load tap-changer control/monitoring (optional) .............................. 32
3.2.9
YPTR - Transformer (optional) ........................................................................... 33
3.3
Operating modes .................................................................................... 35
3.4
Scope of delivery .................................................................................... 35
3.5
Hardware description.............................................................................. 36
3.5.1
Internal design .................................................................................................... 37
3.5.2
Communication Interfaces .................................................................................. 37
3.6
Operation and indicator elements ........................................................... 42
3.6.1
Operating concept .............................................................................................. 43
3.6.2
Description of the display ................................................................................... 44
3.6.3
Description of key functions ................................................................................ 46
3.6.4
Description of LEDs ............................................................................................ 47
4
Packaging, Transport and Storage ........................................... 49
4.1
Packaging ............................................................................................... 49
4.1.1
Purpose .............................................................................................................. 49
4.1.2
Suitability, structure and production ................................................................... 49
4.1.3
Markings ............................................................................................................. 50
4.2
Transportation, receipt and handling of shipments ................................. 50
4.3
Storage of shipments .............................................................................. 51
4
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
Table of Contents
5
Mounting ..................................................................................... 53
5.1
Unpacking ............................................................................................... 53
5.2
Mounting ................................................................................................. 53
5.3
Connection .............................................................................................. 54
5.3.1
Cable recommendation for standard connections .............................................. 54
5.3.2
Cable recommendation for optional connections ............................................... 55
5.3.3
Electromagnetic compatibility ............................................................................. 55
5.3.4
Connecting lines to the system periphery ........................................................... 62
5.3.5
Voltage regulator power supply .......................................................................... 63
5.3.6
Wiring the voltage regulator ................................................................................ 63
5.4
Function check ........................................................................................ 64
6
Commissioning .......................................................................... 65
6.1
Configuration ........................................................................................... 65
6.1.1
Setting the language ........................................................................................... 65
6.1.2
Selecting the control mode ................................................................................. 66
6.1.3
Controlling remote tap position indicator with BCD signal .................................. 67
6.2
Function tests .......................................................................................... 69
6.2.1
Function tests for control functions ..................................................................... 69
6.2.2
Function tests for additional functions ................................................................ 71
6.2.3
Function tests for parallel operation.................................................................... 74
7
Functions and settings .............................................................. 79
7.1
Key lock .................................................................................................. 79
7.1.1
Activating key lock .............................................................................................. 79
7.1.2
Deactivating key lock .......................................................................................... 79
7.2
NORMset ................................................................................................ 80
7.2.1
Entering NORMset desired value 1 .................................................................... 82
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
5
Table of Contents
7.2.2
Setting the primary voltage ................................................................................. 83
7.2.3
Setting the secondary voltage ............................................................................ 84
7.3
Parameters ............................................................................................. 85
7.3.1
Setting control parameters ................................................................................. 85
7.3.2
Setting desired value 1 ....................................................................................... 86
7.3.3
Setting desired value 2 ....................................................................................... 87
7.3.4
Setting desired value 3 ....................................................................................... 88
7.3.5
Bandwidth ........................................................................................................... 89
7.3.6
Setting delay time T1 .......................................................................................... 93
7.3.7
Setting control response T1 ................................................................................ 95
7.3.8
Activating/deactivating delay time T2 ................................................................. 96
7.3.9
Setting delay time T2 .......................................................................................... 97
7.3.10
Limit values ......................................................................................................... 97
7.3.11
Abnormal control response ............................................................................... 107
7.3.12
Compensation................................................................................................... 111
7.3.13
Cross-monitoring .............................................................................................. 120
7.4
Configuration ........................................................................................ 129
7.4.1
Transformer data .............................................................................................. 129
7.4.2
General ............................................................................................................. 138
7.4.3
Parallel operation .............................................................................................. 151
7.4.4
Configuring analog inputs ................................................................................. 162
7.4.5
LED selection.................................................................................................... 170
7.4.6
Configuring transducer function........................................................................ 173
7.4.7
Configuring measured value memory function (optional) ................................. 179
7.4.8
Communication interface SID ........................................................................... 196
7.5
Info........................................................................................................ 201
7.5.1
Carrying out LED test ....................................................................................... 203
7.5.2
Querying status................................................................................................. 204
7.5.3
Resetting parameters ....................................................................................... 206
7.5.4
Displaying real-time clock ................................................................................. 206
7.5.5
Displaying parallel operation ............................................................................ 206
7.5.6
Displaying data on CAN bus ............................................................................. 207
7.5.7
Displaying measured value memory ................................................................ 209
6
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
Table of Contents
7.5.8
Displaying peak memory................................................................................... 209
7.5.9
Displaying CIC1 card SCADA information ........................................................ 210
7.5.10
Displaying CIC2 card SCADA information ........................................................ 211
7.5.11
Displaying upcoming messages ....................................................................... 212
8
Interface description for IEC 61850 protocol ......................... 213
8.1
Physical connection .............................................................................. 213
8.2
Device-specific data points for TAPCON® 260 .................................... 213
8.3
Downloading the ICD file ...................................................................... 214
9
Fault elimination ....................................................................... 215
9.1
Operating faults ..................................................................................... 215
9.1.1
No control in AUTO mode ................................................................................. 215
9.1.2
Man Machine Interface ..................................................................................... 216
9.1.3
Incorrect measured values................................................................................ 217
9.1.4
Parallel operation faults .................................................................................... 218
9.1.5
Tap position capture incorrect .......................................................................... 219
9.1.6
Digital inputs ..................................................................................................... 220
9.1.7
General fault ..................................................................................................... 220
9.1.8
No solution ........................................................................................................ 220
9.2
Event message ..................................................................................... 222
10
Technical Data .......................................................................... 223
10.1
Indicator elements ................................................................................. 223
10.2
Electrical data ....................................................................................... 223
10.3
Inputs and outputs ................................................................................ 223
10.4
Dimensions and weight ......................................................................... 224
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
7
Table of Contents
10.5
Voltage and current measurement ....................................................... 225
10.6
Ambient conditions ............................................................................... 225
10.7
Tests ..................................................................................................... 225
10.7.1
Electrical safety................................................................................................. 225
10.7.2
EMC tests ......................................................................................................... 226
10.7.3
Environmental durability tests........................................................................... 226
11
MR worldwide ........................................................................... 227
8
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
1 Introduction
1
Introduction This technical file contains detailed descriptions on the safe and proper mounting, connection, commissioning and monitoring of the product. It also includes safety instructions and general information about the product. This technical file is intended solely for specially trained and authorized personnel.
1.1
Manufacturer The product is manufactured by: Maschinenfabrik Reinhausen GmbH Falkensteinstraße 8 93059 Regensburg Tel.: (+49) 9 41/40 90-0 Fax: (+49) 9 41/40 90-7001 E-Mail:
[email protected] Further information on the product and copies of this technical file are available from this address if required.
1.2
Subject to change without notice The information contained in this technical file comprise the technical specifications approved at the time of printing. Significant modifications will be included in a new edition of the technical file. The document and version numbers of this technical file are shown in the footer.
1.3
Completeness This technical file is incomplete without the supporting documentation.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
9
1 Introduction
1.4
Supporting documents The following documents apply to this product:
Operating instructions
Quick reference guide
Connection diagrams
In addition, generally applicable legal and other binding regulations of European and national law and the regulations for accident prevention and environmental protection in force in the country of use must be complied with.
1.5
Safekeeping This technical file and all supporting documents must be kept ready to hand and accessible for future use at all times.
1.6
Notation conventions This section contains an overview of the abbreviations, symbols and textual emphasis used.
10
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
1 Introduction
1.6.1
Abbreviations used Abbreviation
Definition
°C A AC B BCD ca. CAN CIC CPU CT DC
Degrees Celcius Ampere Alternating Current Bandwidth Binary Coded Decimal circa Regulator Area Network Communication Interface Card Central Processing Unit Current Transformer Direct Current Deutsches Institut für Normung (German Institute for Standardization) Distributed Network Protocol Electromagnetic compatibility Escape Hertz Current International Electrotechnical Commission Internet Protocol Kilobaud Kilogram Kilovolt Line Drop Compensation Light Emitting Diode Fiber-optic cable
DIN DNP EMC ESC Hz I IEC IP kBaud kg kV LDC LED Fiber-optic cable max. MB MR MHz min. mm ms
maximum Megabyte Maschinenfabrik Reinhausen Megahertz minimum Millimeter Millisecond
N PH Phi (φ) ppm
Neutral Phase Phase angle Parts per million
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
11
1 Introduction
Abbreviation
Definition
s SCADA T TCP V VAct VRef V VT
Second Supervisory Control and Data Acquisition Time Transmission Control Protocol Voltage Actual voltage Reference voltage Volt Voltage Transformer
Table 1
1.6.2
Abbreviations used
Hazard communication system Warnings in this technical file use the following format: DANGER! Danger Consequences ► Action ► Action
The following signal words are used: Signal word
Hazard level
Consequence of failure to comply
Danger Warning
Immediate threat of danger Possible threat of danger Possible dangerous situation
Death or serious injury could occur Death or serious injury could occur Minor or moderate injury could occur Damage to property could occur
Attention Note Table 2
12
Possible dangerous situation Signal words in warning notices
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
1 Introduction
Pictograms warn of dangers: Picto gram
Meaning Danger
Dangerous electrical voltage
Fire hazard
Danger of tipping
Table 3
Symbols used in warning notices
1.6.3
Information system Information is designed to simplify and improve understanding of particular procedures. In this technical file they are laid out as follows: Important information
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
13
2 Safety
2
Safety
2.1
General safety information This technical file contains detailed descriptions on the safe and proper mounting, connection, commissioning and monitoring of the product. Read this technical file through carefully to familiarize yourself with the product. Particular attention should be paid to the information given in this chapter.
2.2
Appropriate use The product and associated equipment and special tools supplied with it comply with the relevant legislation, regulations and standards, particularly health and safety requirements, applicable at the time of delivery. If used as intended and in compliance with the specified requirements and conditions in this technical file as well as the warning notices in this technical file and attached to the product, then the product does not present any hazards to people, property or the environment. This applies throughout the product's full life, from delivery through installation and operation to disassembly and disposal. The operational quality assurance system ensures a consistently high quality standard, particularly in regard to the observance of health and safety requirements. Use is considered to be appropriate if
the product is operated in accordance with this technical file and the agreed delivery conditions and technical data, and
the associated equipment and special tools supplied with it are used solely for the intended purpose and in accordance with the specifications of this technical file.
the product is used only with the transformer specified in the order.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
15
2 Safety
2.3
Inappropriate use Use is considered to be inappropriate if the product is used other than as described in Appropriate use on page 15. Maschinenfabrik Reinhausen does not accept liability for damage resulting from unauthorized or inappropriate changes to the product. Inappropriate changes to the product without consultation with Maschinenfabrik Reinhausen can lead to personal injury, damage to property and operational disruption.
2.4
Personnel qualification The product is designed solely for use in electrical energy systems and facilities operated by appropriately trained staff. This staff comprises people who are familiar with the installation, assembly, commissioning and operation of such products.
2.5
Operator duty of care To prevent accidents, disruptions and damages as well as unacceptable adverse effects on the environment, those responsible for transport, installation, operation, maintenance and disposal of the product or parts of the product must ensure the following:
16
All warning and hazard notices are complied with.
Personnel are instructed regularly in all relevant aspects of operational safety, the operating instructions and particularly the safety instructions contained therein.
Regulations and operating instructions for safe working as well as the relevant instructions for staff procedures in the case of accidents and fires are kept on hand at all times and are displayed in the workplace where applicable.
The product is only used when in a sound operational condition and safety equipment in particular is checked regularly for operational reliability.
Only replacement parts, lubricants and auxiliary materials which are authorized by the manufacturer are used.
The specified operating conditions and requirements of the installation location are complied with.
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
2 Safety
All necessary devices and personal protective equipment for each activity are made available.
The prescribed maintenance intervals and the relevant regulations are complied with.
Fitting, electrical connection and commissioning of the product may only be carried out by qualified and trained personnel in accordance with this technical file.
The operator must ensure appropriate use of the product.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
17
3 Product description
3
Product description The voltage regulator serves to keep constant the output voltage of a transformer with an on-load tap-changer. To do this, the voltage regulator compares the transformer's measured output voltage (Vactual) with a defined reference voltage (Vreference). The difference between Vactual and Vdesired is the control deviation (dV). If the control deviation is greater than the specified bandwidth (B%), the voltage regulator emits a switching pulse after a defined delay time T1. The switching pulse triggers an on-load tap-changer tap change which corrects the transformer's output voltage. The voltage regulator parameters can be optimally adjusted to the line voltage behavior to achieve a balanced control response with a small number of on-load tap-changer operations. The following diagram (on page 20) shows an overview of voltage regulation.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
19
3 Product description
Figure 1
20
Overview of voltage regulation
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
3 Product description
3.1
Performance features The voltage regulator is responsible for controlling tapped transformers. Apart from control tasks, the voltage regulator provides additional functions such as:
Integrated protective functions: Undervoltage and overcurrent blocking Overvoltage detection with high-speed return
Line drop compensation
Z compensation to compensate for voltage fluctuations in the meshed grid
Digital inputs and outputs which can be individually programmed on-site by the user
Additional indicators using LEDs outside the display for freely selectable functions
Display of all measured values such as voltage, current, active power, apparent power or reactive power, cos φ
Cable connection using modern plug terminals
Selection of 3 different desired values
When ordering you can choose between tap position capture using analog signal 4…20 mA analog signal via resistor contact series digital signal via BCD code
Additional digital inputs and outputs which can be freely parameterized by the customer
Parallel operation of up to 16 transformers in 2 groups using the methods Master / Follower Circulating reactive current minimization
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
21
3 Product description
3.2
Relay of the signals via IEC 61850 The following signals are relayed via IEC 61850.
3.2.1
LLN0 - Logical node LLN0 class
Attribute name
Attribute type
Extra used attribute
Explanation
T
M/O
Common logical node information Mod
INC
Mode
N
Y
M
Beh
INS
Behavior
N
Y
M
Health
INS
Health
N
Y
M
NamPlt
LPL
Name plate
N
Y
M
Loc
SPS
Local operation for complete logical device
N
N
O
EEHealth
INS
External equipment health
N
N
O
EEName
DPL
External equipment name plate
N
N
O
OpCntRs
INC
Operation counter resettable
N
N
O
OpCnt
INS
Operation counter
N
N
O
OpTmh
INS
Operation time
N
N
O
Diag
SPC
Run diagnostics
N
N
O
LEDRs
SPC
LED reset
N
N
Controls
Table 4
22
T
O
IEC 61850 data points (LLNO - Logical node)
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
3 Product description
3.2.2
LPHD - Physical device LPHD class (LPHD1)
Attribute name
Attribute type
Explanation
Extra used attribute
T
M/O
PhyNam
DPL
Physical device name plate
N
Y
M
PhyHealth
INS
Physical device health
N
Y
M
OutOv
SPS
Output communications buffer overflow
N
N
O
Proxy
SPS
Indicates if this LN is a proxy
N
Y
M
InOv
SPS
Input communications buffer overflow
N
N
O
NumPwrUp
INS
Number of power ups
N
N
O
WrmStr
INS
Number of warm starts
N
N
O
WacTrg
INS
Number of watchdog device resets N detected
N
O
PwrUp
SPS
Power up detected
N
N
O
PwrDn
SPS
Power down detected
N
N
O
PwrSupAlm
SPS
External power supply alarm
N
N
O
RsStat
SPC
Reset device statistics
N
N
Table 5
T
O
IEC 61850 data points (LPHD - Physical device)
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
23
3 Product description
3.2.3
LPHD - Physical device ATCC class (ATCC1)
Attribute name
Attribute type
Explanation
Extra used attribute
T
M/O
Common logical node information Mod
INC
Mode
N
Y
M
Beh
INS
Behavior
N
Y
M
Health
INS
Health
N
Y
M
NamPlt
LPL
Name plate
N
Y
M
Loc
SPS
Local operation
N
Y
O
EEHealth
INS
External equipment health
N
N
O
EEName
DPL
External equipment name plate
N
N
O
OpCntRs
INC
Resettable operation counter
N
N
O
OpCnt
INS
Operation counter
N
N
O
OpTmh
INS
Operation time
N
N
O
TapChg
BSC
Change tap position (stop, higher, lower)
N
Y
C
TapPos
ISC
Tap position
N
N
C
ParOp
DPC
Parallel/Independent operation
N
Y
M
LTCBlk
SPC
N
Y
O
N
N
Controls
LTCDragRs SPC
Block (inhibit) automatic control of LTC Reset LTC drag hands
VRed1
SPC
Voltage reduction step 1
N
N
O
VRed2
SPC
Voltage reduction step 2
N
N
O
T
O
Measured values CtlV
MV
Control voltage
N
Y
M
LodA
MV
Load current (total transformer secondary current)
N
Y
O
CircA
MV
Circulating current
N
N
O
PhAng
MV
Phase angle of LodA relative to CtlV at 1.0 power factor, FPF
N
N
O
Highest control voltage
N
N
O
Metered values HiCtlV
24
MV
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
3 Product description
ATCC class (ATCC1) Attribute name
Attribute type
Extra used attribute
Explanation
T
M/O
LoCtlV
MV
Lowest control voltage
N
N
O
HiDmdA
MV
High current demand (load current demand)
N
N
O
Status information Auto
SPS
Automatic/manual operation
N
Y
O
HiTapPos
INS
High tap position
N
N
O
LoTapPos
INS
Low tap position
N
N
O
N
Y
O
N
Y
O
N
Y
O
N
Y
O
N
Y
O
N
Y
O
N
N
O
N
N
O
N
Y
O
N
Y
O
N
Y
O
N
Y
O
N
N
O
N
Y
O
Settings BndCtr
ASG
BndWid
ASG
CtlDlTmms
ING
LDCR
ASG
LDCX
ASG
BlkLV
ASG
BlkRV
ASG
RnbkRV
ASG
LimLodA
ASG
LDC
SPG
TmDlChr
SPG
LDCZ
ASG
VRedVal
ASG
TapBlkR
ING
Band center voltage (FPF presumed) Band width voltage (as voltage or percent of nominal voltage, FPF presumed) Control intentional time delay (FPF presumed) Line drop voltage due to line resistance component Line drop voltage due to line resistance component Control voltage below which auto lower commands blocked Control voltage above which auto raise commands blocked Runback raise voltage Limit load current (LTC block load current) Line drop compensation is R&X or Z model Time delay linear or inverse characteristic Line drop voltage due to line total impedance Reduction of band center (percentage) when voltage step 1 is active Tap position of load tap changer where automatic raise commands are blocked.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
25
3 Product description
ATCC class (ATCC1) Attribute name TapBlkL
Attribute type ING
Extra used attribute
Explanation
T
M/O
Tap position of load tap changer where automatic lower commands are blocked.
N
Y
O
Extra attributes CirCur
SPC
Circulating reactive current (parallel control)
Y
Y
O
Master
SPC
Master mode (parallel control)
Y
Y
O
Follower
SPC
Follower mode (parallel control)
Y
Y
O
SICmd1
SPC
Serial interface command 1
Y
Y
O
SICmd2
SPC
Serial interface command 2
Y
Y
O
SICmd3
SPC
Serial interface command 3
Y
Y
O
VoltLvl1
SPC
Voltage level 1
Y
Y
O
VoltLvl2
SPC
Voltage level 2
Y
Y
O
VoltLvl3
SPC
Voltage level 3
Y
Y
O
OverV
SPS
Voltage high limit reached
Y
Y
O
UnderV
SPS
Voltage low limit reached
Y
Y
O
OverC
SPS
Current overload
Y
Y
O
MotDrv
SPS
Motor drive running
Y
Y
O
UInd1
SPS
User indication 1
Y
Y
O
Uind2
SPS
User indication 2
Y
Y
O
Uind3
SPS
User indication 3
Y
Y
O
Uind4
SPS
User indication 4
Y
Y
O
FuncMon
SPS
Function monitoring
Y
Y
O
ParErr
SPS
Parameter error
Y
Y
O
Table 6
26
IEC 61850 data points (ATCC - Voltage regulation)
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
3 Product description
3.2.4
GGIO1 - IO card inputs GGIO class (GGIO1)
Attribute name
Attribute type
Extra used attribute
Explanation
T
M/O
Common logical node information Mod
INC
Mode
N
Y
M
Beh
INS
Behavior
N
Y
M
Health
INS
Health
N
Y
M
NamPlt
LPL
Name plate
N
Y
M
EEHealth
INS
External equipment health
N
N
O
EEName
DPL
External equipment name plate
N
N
O
Loc
SPS
Local operation
N
N
O
OpCntRs
INC
Operation counter resettable
N
N
O
OpCnt
INS
Operation counter
N
N
O
Analogue input
N
N
O
N
N
O
N
N
O
N
N
O
Measured values AnIn
MV
Controls SPCSO
SPC
DPCSO
DPC
ISCSO
INC
Single point controllable status output Double point controllable status output Integer status controllable status output
Status information IntIn
INS
Integer status input
N
N
O
Alm
SPS
General single alarm
N
N
O
Ind
SPS
General indication (binary input)
N
N
O
Extra attributes Ind1
SPS
IO X1:31
Y
Y
O
Ind2
SPS
IO X1:33
Y
Y
O
Table 7
IEC 61850 data points (GGIO1 - IO card inputs)
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
27
3 Product description
3.2.5
GGIO2 - UC1 card inputs GGIO class (GGIO2)
Attribute name
Attribute type
Explanation
Extra used attribute
T
M/O
Common logical node information Mod
INC
Mode
N
Y
M
Beh
INS
Behavior
N
Y
M
Health
INS
Health
N
Y
M
NamPlt
LPL
Name plate
N
Y
M
EEHealth
INS
External equipment health
N
N
O
EEName
DPL
External equipment name plate
N
N
O
Loc
SPS
Local operation
N
N
O
OpCntRs
INC
Operation counter resettable
N
N
O
OpCnt
INS
Operation counter
N
N
O
Analogue input
N
N
O
N
N
O
N
N
O
N
N
O
Measured values AnIn
MV
Controls SPCSO
SPC
DPCSO
DPC
ISCSO
INC
Single point controllable status output Double point controllable status output Integer status controllable status output
Status information IntIn
INS
Integer status input
N
N
O
Alm
SPS
General single alarm
N
N
O
Ind
SPS
General indication (binary input)
N
N
O
Extra attributes Ind1
SPS
UC1 X1:11
Y
Y
O
Ind2
SPS
UC1 X1:12
Y
Y
O
Ind3
SPS
UC1 X1:14
Y
Y
O
Ind4
SPS
UC1 X1:15
Y
Y
O
Ind5
SPS
UC1 X1:16
Y
Y
O
Ind6
SPS
UC1 X1:17
Y
Y
O
28
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
3 Product description
GGIO class (GGIO2) Attribute name
Attribute type
Extra used attribute
Explanation
T
M/O
Ind7
SPS
UC1 X1:30
Y
Y
O
Ind8
SPS
UC1 X1:31
Y
Y
O
Ind9
SPS
UC1 X1:32
Y
Y
O
Ind10
SPS
UC1 X1:33
Y
Y
O
Table 8
IEC 61850 data points (GGIO2 - UC1 card inputs)
3.2.6
GGIO3 - UC2 card inputs GGIO class (GGIO3)
Attribute name
Attribute type
Extra attribute
Explanation
use d
T
M/O
Common logical node information Mod
INC
Mode
N
Y
M
Beh
INS
Behavior
N
Y
M
Health
INS
Health
N
Y
M
NamPlt
LPL
Name plate
N
Y
M
EEHealth
INS
External equipment health
N
N
O
EEName
DPL
External equipment name plate
N
N
O
Loc
SPS
Local operation
N
N
O
OpCntRs
INC
Operation counter resettable
N
N
O
OpCnt
INS
Operation counter
N
N
O
Analogue input
N
N
O
N
N
O
N
N
O
N
N
O
Measured values AnIn
MV
Controls SPCSO
SPC
DPCSO
DPC
ISCSO
INC
Single point controllable status output Double point controllable status output Integer status controllable status output
Status information
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
29
3 Product description
GGIO class (GGIO3) Attribute name
Attribute type
Explanation
Extra attribute
use d
T
M/O
IntIn
INS
Integer status input
N
N
O
Alm
SPS
General single alarm
N
N
O
Ind
SPS
General indication (binary input)
N
N
O
Extra attributes Ind1
SPS
UC2 X1:11
Y
Y
O
Ind2
SPS
UC2 X1:12
Y
Y
O
Ind3
SPS
UC2 X1:14
Y
Y
O
Ind4
SPS
UC2 X1:15
Y
Y
O
Ind5
SPS
UC2 X1:16
Y
Y
O
Ind6
SPS
UC2 X1:17
Y
Y
O
Ind7
SPS
UC2 X1:30
Y
Y
O
Ind8
SPS
UC2 X1:31
Y
Y
O
Ind9
SPS
UC2 X1:32
Y
Y
O
Ind10
SPS
UC2 X1:33
Y
Y
O
Table 9
IEC 61850 data points (GGIO3 - UC2 card inputs)
3.2.7
GGIO4 - UC3 card inputs (optional) GGIO class (GGIO4)
Attribute name
Attribute type
Explanation
Extra used attribute
T
M/O
Common logical node information Mod
INC
Mode
N
Y
M
Beh
INS
Behavior
N
Y
M
Health
INS
Health
N
Y
M
NamPlt
LPL
Name plate
N
Y
M
EEHealth
INS
External equipment health
N
N
O
EEName
DPL
External equipment name plate
N
N
O
Loc
SPS
Local operation
N
N
O
30
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
3 Product description
GGIO class (GGIO4) Attribute name
Attribute type
Extra used attribute
Explanation
T
M/O
OpCntRs
INC
Operation counter resettable
N
N
O
OpCnt
INS
Operation counter
N
N
O
Analogue input
N
N
O
N
N
O
N
N
O
N
N
O
Measured values AnIn
MV
Controls SPCSO
SPC
DPCSO
DPC
ISCSO
INC
Single point controllable status output Double point controllable status output Integer status controllable status output
Status information IntIn
INS
Integer status input
N
N
O
Alm
SPS
General single alarm
N
N
O
Ind
SPS
General indication (binary input)
N
N
O
Extra attributes Ind1
SPS
UC3 X1:11
Y
Y
O
Ind2
SPS
UC3 X1:12
Y
Y
O
Ind3
SPS
UC3 X1:14
Y
Y
O
Ind4
SPS
UC3 X1:15
Y
Y
O
Ind5
SPS
UC3 X1:16
Y
Y
O
Ind6
SPS
UC3 X1:17
Y
Y
O
Ind7
SPS
UC3 X1:30
Y
Y
O
Ind8
SPS
UC3 X1:31
Y
Y
O
Ind9
SPS
UC3 X1:32
Y
Y
O
Ind10
SPS
UC3 X1:33
Y
Y
O
Table 10
IEC 61850 data points (GGIO4 - UC3 card inputs)
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
31
3 Product description
3.2.8
YLTC1 - On-load tap-changer control/monitoring (optional) YLTC class (YLTC1)
Attribute name
Attribute type
Explanation
Extra used attribute
T
M/O
Common logical node information Mod
INC
Mode
N
Y
M
Beh
INS
Behavior
N
Y
M
Health
INS
Health
N
Y
M
NamPlt
LPL
Name plate
N
Y
M
Loc
SPS
Local operation
N
N
O
EEHealth
INS
External equipment health
N
N
O
EEName
DPL
External equipment name plate
N
N
O
OpCntRs
INC
Operation counter resettable
N
N
O
OpCnt
INS
Operation counter
N
Y
O
OpTmh
INS
Operation time
N
N
O
Measured values Torq
MV
Drive torque
N
N
O
MotDrvA
MV
Motor drive current
N
N
O
N
C
Y
C
Controls TapPos
ISC
TapChg
BSC
Change tap position to dedicated N position Change tap position (higher, lowN er)
Status information EndPosR
SPS
End position raise reached
N
Y
M
EndPosL
SPS
End position lower reached
N
Y
M
OilFil
SPS
Oil filtration
N
N
O
Extra attributes MotDrv
SPS
Motor-drive unit lowering/raising tap position
Y
Y
O
SigGRE
SPS
signal green
Y
Y
O
SigYEL
SPS
signal yellow
Y
Y
O
SigRED
SPS
signal red
Y
Y
O
USigYEL
SPS
user signal yellow
Y
Y
O
32
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
3 Product description
YLTC class (YLTC1) Attribute name
Attribute type
Extra used attribute
Explanation
T
M/O
USigRED
SPS
user signal red
Y
Y
O
AbrPrts
MV
Percentage abrasion parts
Y
Y
O
OilExCl
MV
Percentage oil exchange and cleaning
Y
Y
O
AbsWPt
MV
Percentage absolute wear point
Y
Y
O
OilSamp
MV
Percentage oil sampling
Y
Y
O
OnSTmIntv
MV
Percentage on-site time-Interval
Y
Y
O
Table 11
IEC 61850 data points (YLTC1 - On-load tap-changer control/monitoring)
3.2.9
YPTR - Transformer (optional) YPTR class (YPTR1)
Attribute name
Attribute type
Extra used attribute
Explanation
T
M/O
Common logical node information Mod
INC
Mode
N
Y
M
Beh
INS
Behavior
N
Y
M
Health
INS
Health
N
Y
M
NamPlt
LPL
Name plate
N
Y
M
EEHealth
INS
External equipment health
N
N
O
EEName
DPL
External equipment name plate
N
N
O
OpTmh
INS
Operation time
N
N
O
Winding hotspot temperature (in °C)
N
N
O
N
N
O
N
N
N
N
Measured values HPTmp
MV
Status information HPTmpAlm
SPS
HPTmpTr
SPS
OANL
SPS
Winding hot point temperature alarm Winding hot point temperature trip Operation at no load
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
T
O O
33
3 Product description
YPTR class (YPTR1) Attribute name
Attribute type
Explanation
Extra used attribute
T
M/O
OpOvA
SPS
Operation at overcurrent
N
N
O
OpOvV
SPS
Operation at overvoltage
N
N
O
OpUnV
SPS
Operation at undervoltage
N
N
O
CGAlm
SPS
Core ground alarm
N
N
O
HiVRtg
ASG
Rated voltage (high voltage level) N
N
O
LoVRtg
ASG
Rated voltage (low voltage level)
N
N
O
PwrRtg
ASG
Rated power
N
N
O
Y
O
Y
O
Y
O
Settings
Extra attributes HVTmp SPS LVTmp OilTmp Table 12
34
SPS SPS
winding temperature high volY tage; AD1 input1 winding temperature low voltage; Y AD1 input 2 oil temperature AD2 Y
IEC 61850 data points (YPTR1)
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
3 Product description
3.3
Operating modes The voltage regulator can be operated in the following operating modes: AUTO/MANUAL In automatic mode (AUTO), the voltage is automatically controlled in accordance with the set parameters. The voltage regulator settings cannot be changed in automatic mode. In manual mode (MANUAL), no automatic control occurs. The motor-drive unit can be controlled via the voltage regulator's operating panel. The voltage regulator settings can be changed. LOCAL/REMOTE In remote mode (REMOTE), commands from an external control interface are executed. In this mode, manual operation of the RAISE, LOWER, MANUAL and AUTO keys is disabled.
3.4
Scope of delivery The following items are included in the delivery: Scope of delivery Voltage regulator TAPCON® 260 Technical files Table 13
Scope of delivery
Please note the following: 1.
Use dispatch documents to check that the delivery is complete.
2.
Store the parts in a dry place until installation.
The functional range of the product is dependent on the equipment ordered or the product version and not on the content of this technical file.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
35
3 Product description
3.5
Hardware description The individual assemblies are fitted in a standardized 19-inch plug-in housing. The front panels of the assemblies are secured to the plug-in housing at the top and bottom. An IEC 60603-2 plug connector provides the electrical connection. The assemblies are connected to one another via a data bus and separate direct current (DC) supply. This allows for an upgrade with additional plug-in units and extension cards at a later date. An LCD graphic display, LEDs and function keys are integrated in the front panel of the product.
Figure 2 1 2 3
36
TAPCON® 260
Front view of device
19-inch plug-in housing (in accordance with DIN 41494 Part 5) Operating panel with display and LEDs Assembly for optional add-ons (e.g. TAPCON 240 LV)
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
3 Product description
3.5.1
Internal design The device is controlled by a microregulator and includes isolated optocoupler inputs and floating output relay contacts in addition to the voltage and current transformers.
3.5.2
Communication Interfaces
3.5.2.1
Serial interface The parameters for the product can be set using a PC. The COM 1 (RS232) serial interface on the front panel is provided for this purpose. TAPCON®trol software is needed for parameterization. It can be obtained from the Download Center on the Maschinenfabrik Reinhausen website (www.reinhausen.com).
Figure 3
Voltage regulator connection to a PC.
1
PC with TAPCON®-trol software
2
Connection cable with RS232 / USB port
3
Voltage regulator
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
37
3 Product description
3.5.2.2
SID card The SID interface card is used to connect the device to the control station system. The IEC 61850 protocol transfers the data. The diagram below shows the interfaces available and the operating and display elements on the SID card.
Figure 4 1 2 3 4
38
TAPCON® 260
SID card
Reset key Status LED Interface for SIC card updates Ethernet RJ45
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
3 Product description
3.5.2.3
MC1 card The optional MC1 card is used to convert the SID card's electrical connection into a FH-ST type fiber-optic cable connection. In this case the wave length of the fiber-optic cable is 1300 nm. Terminals 1 and 2 on the MC1 card should be used to connect the voltage supply. Before commissioning, the TAPCON® 260 connection diagrams should be checked. The diagram below shows the interfaces available and the operating and display elements on the MC1 card.
Figure 5 1 2 3
MC1 card
Terminal 1 and terminal 2 for the voltage supply Switch M/L ON/LINK TST Switch A/N ON/OFF
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
39
3 Product description
3.5.2.3.1
Technical Data Power supply 85~ V AC 110 V DC, 220 V DC 47...63 Hz approx. 6 W 4242 V DC
Voltage Frequency Power consumption Insulation Temperature range Operation Transportation and storage
0...40 °C -20...85 °C
Requirement of the fiber-optic cable Connection type Fiber type Max. cable length Wave length Transmitted power (dBm) Received power (dBm) Table 14
3.5.2.3.2
FH-ST Multimode 2 km 1310 nm Max. -14.0; typ. -16.8; min. -19.0 Min. rec. -31.8; typ. rec. -34.5; saturation -14.0
Technical data for MC1 card
Voltage supply connection The voltage is supplied via terminals 1 and 2 on the MC1 card. Terminal
AC
DC
1 2
85...264 V
110/220 V GND
Table 15
40
TAPCON® 260
Voltage supply connection
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
3 Product description
3.5.2.3.3
Configuration The table below lists the positions and descriptions of the switches on the MC1 card. Switch
Description
MDI MDI-X
Button not pressed When using a crossed or so-called patch cable between SID and MC1 card. Button pressed 100 Mbit for TX and RX position in "full duplex" or "half duplex" mode. If "M/L" (“missing link”) is activated, Button pressed an incorrect fiber-optic cable connection also indicates a fault with the electrical cable between the SID and MC1 card.
A/N ON A/N OFF M/L ON LNK TST
Table 16
3.5.2.3.4
Switch position
Positions and descriptions of the switches on the MC1 card
LED status The MC1 card features various LEDs for displaying the current status. You will find an overview in the table below. LED
Status
Color
Description
PWR ON
ON ON OFF ON
Green Green
ON ON OFF
Green Green
Supply created on MC1 card The connection operates in full duplex mode The connection operates in half duplex mode A connection has been established on the port Network traffic on port MissingLink is activated MissingLink is deactivated, the MC1 card operates in link test mode
FDX LINK ACT M/L ON Table 17
Green
LED status of MC1 card
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
41
3 Product description
3.6
Operation and indicator elements The front of the voltage regulator is split into different areas for operating the device and displaying information. Below you can see an overview of the individual elements.
Figure 6 1 2 3 4 5 6
42
TAPCON® 260
Voltage regulator operating panel
LEDs Keys for parameterization and configuration COM1 serial interface (RS232) Keys for operating the device Labeling strip for LEDs Setting options for display contrast
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
3 Product description
3.6.1
Operating concept The voltage regulator's operating panel is split into an operation control level and a level for parameterization and configuration. The keys for operating the device are completely separate from those used for parameterization. At the operation control level, key activation is signaled visually by means of LEDs. The LEDs integrated in the RAISE/LOWER keys are illuminated during the entire tap change operation of the on-load tap-changer if "motor running" is signaled at the status input. This signal must have previously been parameterized. This visual monitoring option simplifies operation of the voltage regulator. The voltage regulator is equipped with a key lock to protect against unintentional operation. To activate or deactivate, press the ESC and F5 keys simultaneously.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
43
3 Product description
3.6.2
Description of the display
Figure 7
Main screen
1 2 3
Status line Measured voltage Vactual Reference voltage Vreference
4 5 6 7 8
Other measured values (use Tap position (n-1, n, n+1) Bandwidth (upper and lower limit) Time bar for delay time T1 Highlighting for reference voltage
9 10
Highlighting for measured voltage Remaining delay time T1
or
to switch between them)
In auto and manual mode the measured value display can be set using the or
44
keys. The following measured values can be displayed:
Control deviation (dV:)
Current (I:)
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
3 Product description
Apparent power (Powr.:)
Active power (P:)
Reactive power (Q:)
Phase angle (Phase:)
Cosine (Cos:)
In the case of an event or a setting, the associated comments are displayed in the status line (display text "Messages").
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
45
3 Product description
3.6.3
Description of key functions
Key
Symbol RAISE
Function In manual mode the motor-drive unit can be operated directly using the RAISE key. When RAISE is used, the motor-drive unit changes the on-load tap-changer and therefore the step voltage. In manual mode the motor-drive unit can be operated directly using the LOWER key. When LOWER is used, the motor-drive unit changes the on-load tap-changer and therefore the step voltage. Key without function. "Remote" operating mode is enabled or disabled via input IO-X1:31.
LOWER
REMOTE MANUAL
Manual mode. For manual control of the motor-drive unit and parameterization of the voltage regulator. Auto mode. Voltage is controlled automatically.
AUTO Arrow keys NEXT/ PREV
In auto and manual mode, the measured value display can be set using the arrow keys. They can also be used to switch between windows in the submenus.
ENTER
Confirms or saves a changed parameter in the parameter menu.
ESC
Pressing the ESC key takes you to the menu level above, in other words, always back one menu level.
MENU
Pressing this key displays the menu selection window.
F1-F5
The function keys are menu selection keys. They are also used to scroll through the menu subgroups and input screens and to highlight decimal points which can be set by the user.
The parameters can only be changed in manual mode, see table above.
46
TAPCON® 260
1801003/04 EN
key in the
© Maschinenfabrik Reinhausen 2011
3 Product description
3.6.4
Description of LEDs The voltage regulator has 10 LEDs above the display. These indicate various operating statuses or events.
Figure 8 1 2 3 4 5 6 7 8 9 10
Description of LEDs
Green Red Red Red Green Green Yellow Yellow Yellow Green/yellow/red
© Maschinenfabrik Reinhausen 2011
Operating display Overcurrent blocking Undervoltage blocking Overvoltage blocking Parallel operation On NORMset On Freely configurable (LED1) Freely configurable (LED2) Freely configurable (LED3) Freely configurable (LED4)
1801003/04 EN
TAPCON® 260
47
4 Packaging, Transport and Storage
4
Packaging, Transport and Storage
4.1
Packaging
4.1.1
Purpose The packaging is designed to protect the packaged goods both during transport and for loading and unloading as well as during periods of storage in such a way that no (detrimental) changes occur. The packaging must protect the goods against permitted transport stresses such as vibration, knocks and moisture (rain, snow, condensation). The packaging also prevents undesired position changes of the packaged goods within the packaging during storage. The packaged goods must be prepared for shipment before actually being packed so that the goods can be transported safely, economically and in accordance with regulations.
4.1.2
Suitability, structure and production The goods are packaged in a sturdy cardboard box. This ensures that the shipment remains in the intended transport position and that none of its components touches the load surface during transport or the floor after it is unloaded. The box is designed for a maximum load of 10 kg. Inlays inside the box stabilize the goods, preventing impermissible changes of position, and protect them from vibration.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
49
4 Packaging, Transport and Storage
4.1.3
Markings The packaging bears a signature with symbols with instructions for safe transport and correct storage. The following symbols apply to the dispatch (of non-hazardous goods). Adherence to these symbols is mandatory.
Protect against moisture Figure 9
4.2
Top
Fragile
Shipping pictograms
Transportation, receipt and handling of shipments In addition to oscillation and shock stress, jolts must also be expected during transportation. In order to prevent possible damage, avoid dropping, tipping, knocking over and colliding with the product. If a crate falls from a particular height (e.g. when slings tear) or experiences an unbroken fall, damage must be expected regardless of the weight. Before acceptance, all deliveries must be checked by the recipient (acknowledgement of receipt) for the following:
Completeness based on the delivery slip
External damage of any type.
The checks must take place after unloading when the crate can be accessed from all sides. If external transport damage is detected on receipt of the shipment, proceed as follows:
50
Immediately record the transport damage found in the shipping documents and have this countersigned by the carrier.
In the event of severe damage, total loss or high damage costs, immediately notify the sales department at Maschinenfabrik Reinhausen and the relevant insurance company.
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
4 Packaging, Transport and Storage
After identifying the damage do not modify the condition of the shipment further and also retain the packaging material, until an inspection decision has been made by the transport company or the insurance company.
Record the details of the damage immediately together with the carrier involved. This is essential for any claim for damages!
If possible, photograph damage to packaging and packaged goods. This also applies to signs of corrosion on the packaged goods due to moisture inside the packaging (rain, snow, condensation).
Name the damaged parts.
When damages are hidden, i.e. damages which are not determined until unpacking after the receipt of the shipment, proceed as follows:
Make the party responsible for the damage liable as soon as possible by telephone and in writing, and prepare a damage report.
Observe, in this regard, the time periods applicable to such actions in the respective country. Inquire about these in good time.
With hidden damage, it is very hard to make the transportation company (or other responsible party) liable. Any insurance claims for such damages can only be successful if relevant provisions are expressly included in the insurance terms and conditions.
4.3
Storage of shipments Selection and arrangement of the storage location should meet the following requirements:
Stored goods are protected against moisture (flooding, water from melting snow and ice), dirt, pests such as rats, mice, termites and so on, and against unauthorized access.
Store the box on timber beams and planks as a protection against rising damp and for better ventilation.
Carrying capacity of the ground under the goods is sufficient.
Entrance and exit paths are kept free.
Check stored goods at regular intervals. Also take appropriate action after storms, heavy rain or snow and so on.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
51
5 Mounting
5
Mounting
5.1
Unpacking The goods are packaged in a sturdy cardboard box. This ensures that the shipment remains in the intended transport position and that none of its components touches the load surface during transport or the floor after it is unloaded. Inlays inside the box stabilize the goods, preventing impermissible changes of position, and protect them from vibration. Unpack the voltage regulator as follows: 1.
Remove the lid from the lower part of the cardboard box. The upper inlay contains the accessories supplied, the separate box labeled "Documentation" contains the device documents.
2.
Check scope of supply for accessories.
3.
Take the box labeled "Documentation" out of the cardboard box.
4.
Remove the upper inlay from the packaging.
5.
The voltage regulator in the underlying inlay can now be freely accessed.
6.
Remove voltage regulator from the packaging.
The voltage regulator has been unpacked and can be mounted. For mounting, proceed as described in the Mounting section.
5.2
Mounting After unpacking, the voltage regulator can be mounted. The voltage regulator's standardized plug-in housing is intended for fitting in a 19-inch control cabinet. We would recommend a design with a pivoting frame to allow easy access to the connections on the rear of the voltage regulator. The voltage regulator can be mounted in 4 different ways:
Flush panel mounting 19" housing
Flush panel mounting for half 19" housing
Wall mounting for half 19" housing
Wall mounting with terminal strip for half 19" housing
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
53
5 Mounting
5.3
Connection
5.3.1
Cable recommendation for standard connections When wiring the voltage regulator, comply with the following recommendations from Maschinenfabrik Reinhausen.
Cable
Card
Power supply Voltage measurement Current measurement Relay*
SU MI/MI1 MI/MI1 IO
Relay* Signal inputs Signal inputs CAN bus Table 18
Terminal
Cable type
Wire diameter Max. length
X1: 1/2 unshielded 1.5 mm² 1/2 shielded 1.5 mm² 5/6/9/10 unshielded 4 mm² X1:1...10 unshielded 1.5 mm² X1:19...26 UC X1:1...10 unshielded 1.5 mm² IO X1:11...17 shielded 1.0 mm² X1:27...34 UC X1:11...17 shielded 1.0 mm² X1:27...34 CPU 1...5 shielded 1.0 mm² * Observe notices (see below)
2000 m
Recommendation for connection cable
NOTE Output relay malfunction Excessive electrical power can prevent the relay contacts from breaking the contact current. ► The effect of the cable capacitance of long control lines in control circuits operated with alternating current on the function of the relay contacts must be taken into account.
54
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
5 Mounting
5.3.2
Cable recommendation for optional connections
Cable
Card
Terminal
Cable type
Wire diameter Max. length
AC Analog inputs
SU AD/AD 1 AN/AN 1 CIC CIC
X1/2:1/2 X1:1...3
unshielded shielded
1.5 mm² 1.5 mm²
X1
shielded
1mm²
X8 X9
shielded shielded
0.25 mm² 0.75 mm²
SID CIC MC1
RJ45 X7
shielded, CAT 7
-
25 m 1000 m (< 50 Ω/km) 100 m
Optical fiber with MTRJ-ST duplex patch cable
-
-
Analog outputs RS-232 RS-485 Ethernet Media converter
Table 19
Recommendation for connection cable
5.3.3
Electromagnetic compatibility
400 m (< 25 Ω/km) -
The product was developed in compliance with the relevant EMC standards. To ensure compliance with the EMC standards, please note the following points. 5.3.3.1
Wiring requirement of installation site Note the following when selecting the installation site:
The system's overvoltage protection must be effective.
The system's ground connection must comply with all technical regulations.
Separate system parts must be joined by a potential equalization.
The voltage regulator and its wiring must be at least 10 m away from circuit-breakers, load disconnectors and busbars.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
55
5 Mounting
5.3.3.2
Wiring requirement of operating site Note the following when wiring the operating site:
The connection cables must be laid in metallic cable ducts with a ground connection.
Do not route lines which cause interference (e.g. power lines) and lines susceptible to interference (e.g. signal lines) in the same cable duct.
Maintain a gap of at least 10 cm between lines causing interference and those susceptible to interference.
Reserve lines must be grounded at both ends.
The voltage regulator must never be connected using four-pin collective cables.
Figure 10 1 2 3 4
56
TAPCON® 260
Recommended wiring
Cable duct for lines causing interference Interference-causing line (e.g. power line) Cable duct for lines susceptible to interference Line susceptible to interference (e.g. signal line)
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
5 Mounting
Signal lines must be routed in shielded cables.
The individual conductors in the cable core (outgoing/return conductors) must be twisted in pairs.
The shield must be fully (360º) connected to the voltage regulator or a nearby ground rail.
Figure 11
Recommended shielding connection, do not extend the shield to the grounding point with a wire (pigtail).
NOTE Reduced effectiveness of the shielding. Using "pigtails" may considerably reduce the effectiveness of the shielding. ► Connect shield to cover all areas.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
57
5 Mounting
5.3.3.3
Wiring requirement in control cabinet Note the following when wiring the control cabinet:
The control cabinet for fitting the voltage regulator must be prepared in accordance with EMC requirements: functional division of control cabinet (physical separation) constant potential equalization (all metal parts are joined) line routing in accordance with EMC requirements (separation of lines which cause interference and those susceptible to interference) optimum shielding (metal housing) overvoltage protection (lightning protection) collective grounding (main grounding rail) cable bushings in accordance with EMC requirements any protective inductors present must be interconnected
58
The voltage regulator's connection cables must be laid in contact with the grounded metal housing or in metallic cable ducts with a ground connection.
Signal and power/switching lines should be laid in separate cable ducts.
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
5 Mounting
The voltage regulator must be grounded at the screw provided using a ground strap (cross-section min. 8 mm²). The voltage regulator's ground connection is a functional ground and serves to dissipate interfering currents.
Figure 12
Ground strap connection
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
59
5 Mounting
5.3.3.4
Information about shielding the CAN bus To ensure that the CAN bus operates correctly, the shielding must be connected as detailed for the following variants. Both voltage regulators share the same potential To ensure potential equalization between the voltage regulators, all voltage regulators must be connected to the same potential equalization rail. If the voltage regulators share the same potential, the CAN bus cable's shielding must be connected to both voltage regulators. Both voltage regulators have different potentials If the voltage regulators have different potentials, the CAN bus cable's shielding may only be connected to one voltage regulator. Note that the effectiveness of the shielding is less than if connected to both voltage regulators. NOTE Damage to the voltage regulator If the CAN bus cable's shielding is connected to 2 voltage regulators with different potentials, current may flow over the shielding. This current may damage the communication cards. ► Ensure that the CAN bus cable's shielding is only connected to one voltage regulator if both voltage regulators have different potentials. If neither connection variant is possible, we would recommend using fiber optic cables. Fiber optic cables decouple the voltage regulators and are not sensitive to electromagnetic interferences (surge and burst).
60
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
5 Mounting
Connecting the shielding The CAN bus cable's shielding must be secured to the intended point on the housing using the cable clips provided (see diagram below).
Figure 13
1
Securing the CAN bus cable's shielding to the intended point on the housing
Securing the CAN bus cable's shielding
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
61
5 Mounting
5.3.4
Connecting lines to the system periphery Connect the lines, which are to be wired with the voltage regulator, to the system periphery, as shown in the connection diagrams supplied. WARNING! Electric shock Connection mistakes may endanger life ► Earth the voltage regulator using the grounding screw attached to the housing. ► Pay attention to the phase difference of the secondary terminals for the current and voltage transformers. ► Connect the output relays correctly to the motor-drive unit. NOTE Damages to the voltage regulator and system periphery An incorrectly connected voltage regulator can lead to damages in the monitoring system and system periphery. ► Prior to commissioning, be sure to check the entire configuration and the measuring and operating voltage.
To obtain a better overview when connecting cables, only use as many leads as necessary.
Use only the specified cables for connection. You will find a cable recommendation in the corresponding section (see "Cable recommendation for standard connections" on page 54). The voltage regulator is fully connected and can be wired up. To carry out the wiring, proceed as described in the Wiring (see "Wiring the voltage regulator" on page 63) section.
62
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
5 Mounting
5.3.5
Voltage regulator power supply In the standard design, the voltage regulator is supplied with power via a multi-voltage mains unit. The permissible supply voltage is 93...265 V AC, DC. Alternatively the voltage regulator can be supplied with a supply mains unit for the 18...36 V DC or 36...72 V DC range.
5.3.6
Wiring the voltage regulator Wire the voltage regulator as shown in the connection diagram. WARNING! Electric shock Connection mistakes may endanger life ► Earth the voltage regulator using the grounding screw attached to the housing. ► Pay attention to the phase difference of the secondary terminals for the current and voltage transformers. ► Connect the output relays correctly to the motor-drive unit. NOTE Damages to the voltage regulator and system periphery An incorrectly connected voltage regulator can lead to damages in the monitoring system and system periphery. ► Prior to commissioning, be sure to check the entire configuration and the measuring and operating voltage.
To obtain a better overview when connecting cables, only use as many leads as necessary.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
63
5 Mounting
5.4
Function check Carry out a function check to test that the voltage regulator is wired correctly. Check the following:
After being switched on, the screen displays the MR logo and then a voltage value.
The green "Operating display" LED in the top left on the voltage regulator lights up.
The voltage regulator can now be configured. The actions required for this are described in the following chapter (see "Commissioning" on page 65).
64
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
6 Commissioning
6
Commissioning Several parameters need to be set and function tests performed before commissioning the device. These are described in the following chapter.
6.1
Configuration The relevant settings for commissioning are described in more detail in the following sections. A detailed description of the functions can be found in the associated operating instructions.
6.1.1
Setting the language The display language can be set or changed as desired. The following languages are available:
English
German
French
Spanish
Italian
Portuguese
1.
> Configuration > Language.
2. Press language. 3. Press
or
General.
to select the required
.
The language is set.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
65
6 Commissioning
6.1.2
Selecting the control mode The voltage regulator can be commissioned in NORMset mode or manually. Instead of parameterizing the voltage regulator manually, the NORMset mode enables easy and user-friendly commissioning of the voltage regulator with a limited set of parameters. When this mode is selected, the factory settings for voltage regulation are accepted. NOTE Damages to the voltage regulator and system periphery An incorrectly connected voltage regulator can lead to damages in the monitoring system and system periphery. ► Prior to commissioning, be sure to check the entire configuration and the measuring and operating voltage.
We recommend using a registration device to record the transformer voltage (actual value) in order to evaluate how the voltage regulator is functioning.
1.
Press
to select manual mode.
2.
Select the NORMset mode.
3.
Set desired value 1.
4.
Set the primary voltage.
5.
Set the secondary voltage.
6.
Execute one tap-change operation manually.
When these parameters have been set, the regulator is ready to operate. The compensation settings cannot be carried out in NORMset mode. The desired value will be compared with the measured voltage on the voltage regulator. The actual value display can be set in V (voltage transformer secondary voltage) or kV (voltage transformer primary voltage) depending on the setting.
66
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
6 Commissioning
6.1.3
Controlling remote tap position indicator with BCD signal The voltage regulator is equipped with a digital tap position indicator. The indicator is controlled as standard with a BCD signal or optionally with an analog signal. The tap position indicator signal must be converted into and transferred in BCD code if the digital remote tap position indicator is to function. The following is necessary in the motor-drive unit:
a resistor contact series
a downstream diode matrix
the corresponding transfer lines between motor-drive unit and voltage regulator
Figure 14
BCD signal transfer between motor-drive unit and voltage regulator
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
67
6 Commissioning
1 2 3 4
Resistor contact series Diode matrix Transfer line Voltage regulator
Thanks to the diode matrix's linking function, the relevant parallel BCD signal is assigned to every on-load tap-changer operating position which is reproduced by the motor-drive unit's resistor contact series. BCD signal Operating position 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 Table 20
68
TAPCON® 260
10
8
4
2
1
0 0 0 0 0 0 0 0 0 1 1 1 1 1 1 1 1 1 1
0 0 0 0 0 0 0 1 1 0 0 0 0 0 0 0 0 1 1
0 0 0 1 1 1 1 0 0 0 1 0 0 1 1 1 1 0 0
0 1 1 0 0 1 1 0 0 0 0 1 1 0 0 1 1 0 0
1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1
BCD code table for operating positions
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
6 Commissioning
6.2
Function tests Before switching the voltage regulator from manual to automatic mode and therefore activating the automatic voltage regulation for your system, Maschinenfabrik Reinhausen recommends carrying out function tests. These function tests are described in the following sections. HINWEIS Schäden an Spannungsregler und Anlagenperipherie Ein unsachgemäß angeschlossener Spannungsregler kann zu Schäden an Spannungsregler und Anlagenperipherie führen. ► Kontrollieren Sie vor Inbetriebnahme die Gesamtschaltung sowie Ist- und Betriebsspannung.
We recommend using a registration device to record the transformer voltage (actual value) in order to evaluate how the voltage regulator is functioning.
6.2.1
Function tests for control functions The on-load tap-changer can only be controlled in manual mode using the or
keys.
1.
Establish supply voltage
2.
Press
3.
Set transformation ratios for voltage and current transformers and measuring set-up.
4.
Measure actual voltage and compare with that displayed by the voltage regulator.
5.
Press several times to display the operating values for current, output and phase angle.
6.
Compare operating values with operating measurement devices.
© Maschinenfabrik Reinhausen 2011
to select manual mode.
1801003/04 EN
TAPCON® 260
69
6 Commissioning
7.
To set the desired value, manually control the on-load tap-changer until the desired voltage value is reached.
8.
Set desired voltage value Vdesired to this value.
9.
Set bandwidth "B %" depending on step voltage. Vn-1 Un [±B % ] 0.6
100 % Vnominal
10. Set switch time delay T1 to 20 s and control response to T1 linearly. 11. Press
to raise the on-load tap-changer 1 step.
12. Press
to select automatic mode.
After 20 s, the voltage regulator returns the on-load tap-changer to the original operating position.
13. Press
to select manual mode.
14. Press
to lower the on-load tap-changer 1 step.
15. Activate the time delay T2 and set it to 10s. 16. Press
twice to raise the on-load tap-changer 2 steps.
17. Press
to select automatic mode.
After 20 s, the voltage regulator lowers the on-load tap-changer one step and after another 10 seconds another step.
18. Press
to select manual mode.
19. Set the delay times T1 and T2 to the desired values. If T2 is not used, it must be set to "OFF". We recommend a temporary setting of 100 seconds for the delay time T1 when commissioning the transformer. Depending on the operating conditions, you can also specify the delay time following a longer observation period. In this regard, it is useful to register the actual voltage process and the number of tap-change operations per day. If you wish the voltage regulator to exhibit an integral time response, set an integral control response for time delay T1. The greater the control deviation, the shorter the delay time.
70
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
6 Commissioning
6.2.2
Function tests for additional functions The on-load tap-changer can only be controlled in manual mode using the or
keys.
Checking and setting undervoltage blocking V< 1.
Press
2.
Set the undervoltage blocking V< to 85 %.
3.
The desired voltage value should be adjusted such that the actual voltage is below the undervoltage blocking V 1.
Press
2.
Set overvoltage detection V> to 115 %.
3.
The desired voltage value should be adjusted such that the actual voltage is above the overvoltage detection V>.
to select manual mode.
Example: Actual voltage = 100 V, set desired value to a value less than 100 V / 1.15 = 87 V.
The overvoltage V> LED will light up.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
71
6 Commissioning
The overvoltage message appears and the signaling relay is acti-
vated. Contact IO-X1:18/19 opens and contact IO-X1:18/20 closes.
4.
Press
to select automatic mode.
The LOWER output relay periodically emits a control command at approx. 1.5 s intervals.
5.
Press
6.
Set the operating values you want for desired value and overvoltage detection.
to select manual mode.
Set overcurrent blocking I> (and optionally undercurrent blocking I (optionally undercurrent blocking I Normset. Normset activation.
2. To activate Normset, press select "On" . 3. Press
or
to
.
4. Press or to perform a manual tap-change operation. The LED for the NORMset operating display lights up. The NORMset mode is activated.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
81
7 Functions and settings
7.2.1
Entering NORMset desired value 1 Desired values set in kV apply to the primary voltage of the connected voltage transformer. Desired values set in V apply to the secondary voltage of the connected voltage transformer. All transformer data (see "Transformer data" on page 129) must be entered correctly. Settings in kV are only possible if you have previously entered the parameters for primary and secondary voltage.
Setting range
Step size
Factory setting
49 V – 140 V
0.1 V
100 V
Table 21
Setting range for NORMset desired value 1 in V
Setting range
Step size
Factory setting
0 kV...9999 kV 0 kV...999.9 kV 0 kV...99.99 kV
1 kV 0.1 kV 0.01 kV
1 kV
Table 22
Setting range for NORMset desired value 1 in kV
To set desired voltage value 1, proceed as follows: 1.
> Normset > 1x Desired value 1.
.
2. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press
to increase the value or
to
.
Desired value 1 is set.
82
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.2.2
Setting the primary voltage In general, the regulator only indicates the secondary voltage in V if you have not set the primary voltage. The primary voltage is only displayed if parameter "Display kV / V" has been set to kV (see "Setting the voltage display kV/V" on page 141). Example: Primary voltage
Secondary voltage
kV or V
Display
No parameterization 110 kV
100 V 100 V
V kV
100 V 110 kV
Table 23
Example of displayed values in V or kV
Setting range
Step size
Factory setting
0 kV...9999 kV 0 kV...999.9 kV 0 kV...99.99 kV
1 kV 0.1 kV 0.01 kV
0 kV
Table 24
Setting range for primary voltage in kV
To set the primary voltage, proceed as follows: 1.
> Normset > 2x Primary voltage.
.
2. Press to highlight the decimal place. The decimal place is defined and the value can be changed. 3. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 4. Press reduce it. 5. Press
to increase the value or
to
.
The primary voltage is set.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
83
7 Functions and settings
7.2.3
Setting the secondary voltage The secondary voltage is displayed and entered in V. Setting range
Step size
Factory setting
57 V – 125 V
0.1 V
100 V
Table 25
Setting range for secondary voltage in V
To set the secondary voltage, proceed as follows: 1.
> Normset > 3x Secondary voltage.
.
2. If necessary Press to highlight the decimal place. The decimal place is defined and the value can be changed. 3. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 4. Press reduce it. 5. Press
to increase the value or
to
.
The secondary voltage is set.
84
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.3
Parameters This section describes all the functions, parameters and recommended setting ranges for voltage regulation with the voltage regulator. To make it easier for you to find specific parameters, the description refers to subgroups of individual parameters with related functions.
7.3.1
Setting control parameters This submenu contains all the parameters required for the control function.
Desired values 1/2/3
Bandwidth
Delay time T1
Control response T1
Delay time T2
The desired voltage level, Vtarget is specified as a fixed value. The desired value can be entered using the voltage regulator user interface, both in the NORMset mode subgroup and in the parameter mode subgroup. In addition, the voltage regulator also allows you to change the desired value during operation if this is necessary. The desired values are activated using binary inputs. Up to 3 desired values can be entered in parameter mode:
Desired value 1
Desired value 2
Desired value 3
Desired value 1 is the default desired value.Desired values 2 or 3 are activated if there is a continuous signal at the pre-assigned IO-X1/17 or IO-X1/16 inputs (factory preset).If there is a signal at both inputs at the same time, desired value 2 is active. The following sections describe how to set the desired values.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
85
7 Functions and settings
7.3.2
Setting desired value 1 Desired values set in kV apply to the primary voltage of the voltage transformer. Desired values set in V apply to the secondary voltage of the voltage transformer. The transformer data (see "Transformer data" on page 129) must be entered correctly. Setting range
Step size
Factory setting
49 V – 140 V
0.1 V
100 V
Table 26
Setting range for desired value 1 in V
Setting range
Step size
Factory setting
0.1 kV...999.9 kV 0.1 kV...99.9 kV 0.1 kV...99.99 kV
1 kV 0.1 kV 0.01 kV
1kV
Table 27
Setting range for desired voltage value 1 in kV
To set desired voltage value 1, proceed as follows: 1.
> Parameter > rameter. Desired value 1.
Control pa-
2. If you have already entered the transformer data, press "V" or "kV".
to select the unit you want:
3. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 4. Press reduce it. 5. Press
to increase the value or
to
.
Desired value 1 is set.
86
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.3.3
Setting desired value 2 Desired value 2 is activated if there is a continuous signal at IO X1/17 or IO-X1/16 provided you previously programmed the IOs accordingly (on page 146). Setting range
Step size
Factory setting
49 V – 140 V
1V
100 V
Table 28
Setting range for desired value 2 in V
Setting range
Step size
Factory setting
0.1 kV...999.9 kV 0.1 kV...999.9 kV 0.1 kV...99.99 kV
1 kV 0.1 kV 0.01 kV
1 kV
Table 29
Setting range for desired voltage value 2 in kV
To set desired voltage value 2, proceed as follows: 1.
>
Parameter >
Control pa-
rameter > 1x . Desired value 2 2. If you have already entered the transformer data, press "V" or "kV".
to select the unit you want:
3. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 4. Press reduce it.. 5. Press
to increase the value or
to
.
Desired value 2 is set.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
87
7 Functions and settings
7.3.4
Setting desired value 3 Desired value 3 is activated if there is a continuous signal at IO X1/17 or IO-X1/16 provided you previously programmed the IOs accordingly (see "Configuring control inputs IO1-X1:33/31" on page 145). Setting range
Step size
Factory setting
49 V – 140 V
1V
100 V
Table 30
Setting range for desired value 3 in V
Setting range
Step size
Factory setting
0 kV...999.9 kV 0 kV...999.9 kV 0 kV...99.99 kV
1 kV 0.1 kV 0.01 kV
1 kV
Table 31
Setting range for desired voltage value 3 in kV
To set desired value 3, proceed as follows: 1.
> rameter.
Parameter >
Control pa-
> 2x . Desired value 3. 2. If you have already entered the transformer data, press "V" or "kV".
to select the unit you want:
3. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 4. Press reduce it. 5. Press
to increase the value or
to
.
Desired value 3 is set.
88
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.3.5
Bandwidth The bandwidth is the permitted deviation of the measured voltage from the selected desired value. If the measured voltage is inside the bandwidth, then no control commands are issued to the on-load tap-changer. If the measured voltage deviates from the specified bandwidth, a tap-change command occurs after the set delay time T1. The on-load tap-changer carries out a tap-change in a positive or negative direction. If the level is persistently above or below the bandwidth, the "Function monitoring" alarm message is triggered after 15 minutes. The corresponding relay is also activated. The alarm message is only reset when the measured voltage returns to within the set.
Figure 15
1 2 3 4 5 a b c d e
Measured voltage and bandwidth over time
ΔVstep: Step voltage Vdesired: Desired value in V B%: Bandwidth range T1: Set delay time Vactual: Measured voltage Vactual outside the bandwidth, T1 starts Vactual within bandwidth before T1 lapses, no tap-change operation Vactual outside the bandwidth, T1 starts Vactual outside B% before T1 lapses, tap-change operation initiated Tap-change operation complete, Vactual within the bandwidth
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
89
7 Functions and settings
7.3.5.1
Visual display The deviation from the set bandwidth is shown visually in the voltage regulator display. The measured voltage mark shows whether the measured voltage is above, inside or below the set bandwidth. Progress of delay time T1 is indicated by the gradual filling of the time bar in the voltage regulator's display. The seconds display above this indicates the remaining delay time T1.
Figure 16
1 2 3 4 5 7.3.5.2
Visual display of deviation from desired value
Bandwidth (upper and lower limit) Time bar for delay time T1 Desired voltage value Measured voltage Remaining delay time T1
Determining bandwidth In order to be able to set the value correctly, the transformer's step voltage and nominal voltage must be known. The following value is recommended for the bandwidth "B %": Vn-1 Un [±B % ] 0.6
100 % Vnominal
90
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
where: Vn-1:
Step voltage of position n-1
Vn:
Step voltage of position n
Vnominal
Nominal voltage
The bandwidth must be selected in such a way that the output voltage of the transformer (Vactual) returns to within the specified tolerance range after the tap change. If too small a bandwidth is defined, the output voltage exceeds the bandwidth selected and the voltage regulator must immediately issue a tap-change command in the opposite direction. If a very large bandwidth is selected, this results in a major control deviation.
Sample calculation The following transformer parameters are used by way of example for determining the recommended bandwidth: Nominal voltage: Step voltage of position 4: Step voltage of position 5:
Vnominal = 11000 V Vstep4 = 11275 V Vstep5 = 11000 V
Following the recommendation for calculating bandwidth, our example results in: UStep4UStep5 [±B % ]0.6
100 % Vnominal 11275 V11000 V
[±B % ]0.6
100 % 11000 V
[±B % ]1.5 %
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
91
7 Functions and settings
7.3.5.3
Setting the bandwidth Setting range
Step size
Factory setting
0.5 %...9 %
0.01 %...1 %
1%
Table 32
Setting range for bandwidth
The calculated bandwidth is entered as follows: 1.
>
Parameter >
Control pa-
rameter > 3x . Bandwidth. 2. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press
to increase the value or
to
.
The bandwidth is set.
92
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.3.6
Setting delay time T1 Delay time T1 delays the issuing of a tap-change command for a defined period. This function prevents unnecessary tap-change operations if the tolerance bandwidth is exited for a short time. If the current measured voltage leaves the bandwidth, delay time T1 starts. This is shown visually in the display by the time bar filling and the remaining time being indicated. If the control deviation is still present after the delay time, a tap-change command is issued. If during the delay time the measured voltage returns to within the bandwidth range, the delay time still running is counted down in seconds starting from the time already expired. The absolute time display disappears from the display. The time bar graph is shown hatched and shrinks steadily. If the measured voltage exceeds the set bandwidth once more whilst the time is not displayed, then the time delay is restarted from the remaining time. The advantage of counting the time back down is that, if the bandwidth is exceeded frequently, the voltage regulator does not start counting again at 0 seconds, but uses the time already elapsed as the starting point for beginning the next delay time.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
93
7 Functions and settings
Setting range
Step size
Factory setting
0 s...600 s
1s
40 s
Table 33
Setting range for delay time T1
To set the delay time T1, proceed as follows: 1.
>
Parameter >
Control pa-
rameter > 4x . Delay time T1. 2. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press
to increase the time or
to
.
The delay time T1 is set.
94
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.3.7
Setting control response T1 The delay time T1 can be set to linear or integral. With "Linear time" the voltage regulator responds with a constant delay time which is independent of the control deviation. If "Integral time" is set, the delay time decreases depending on the ratio of current control deviation to set bandwidth B, to a minimum of 1 second. The greater the control deviation (ΔV) the shorter the response time. This means that the voltage regulator reacts faster to unexpectedly large voltage changes in the grid. The regulation accuracy therefore increases at the expense of switching frequency (see diagram).
Figure 17 1
∆V/B voltage change
"Delay time T1" parameter
ΔV/B: Control deviation "ΔV" as % of desired value as ratio to the set bandwidth "B" as % of desired value.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
95
7 Functions and settings
To set the control response T1, proceed as follows: 1.
>
Parameter >
Control pa-
rameter > 5x . Control response T1. 2. Press to select "T1 linear" or select "T1 integral". 3. Press
to
.
The control response T1 is set.
7.3.8
Activating/deactivating delay time T2 The delay time T2 only takes effect if more than one tap-change operation is required for returning the voltage to within the specified bandwidth.With integral control response in particular, the time until release of an output pulse would increase after each tap change process. The first output pulse occurs after the set delay time T1. After the set delay time T2 has elapsed, additional pulses occur. These are needed to correct the existing control deviation. To activate/deactivate the delay time T2, proceed as follows: 1.
>
Parameter >
Control pa-
rameters > 6x . T2 activation. 2. Press 3. Press
or
to activate/deactivate T2.
.
The delay time T2 is activated/deactivated.
96
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.3.9
Setting delay time T2 The following section describes how to set the delay time T2. Setting range
Step size
Factory setting
1 s...10 s
0.1 s
10 s
Table 34
Setting range for delay time T2
In general, the delay time T2 should be greater than the pulse duration and the maximum operating time of the motor-drive unit. This applies to continuous settings in particular.
To set the delay time T2, proceed as follows: 1.
>
Parameter >
Control pa-
rameter > 7x . Delay time T2. 2. Press reduce it. 3. Press
to increase the time or
to
.
The delay time T2 is set.
7.3.10
Limit values This subgroup contains all the parameters required for monitoring the limit values. The limit values can be set as percentages or absolute values. For the "undervoltage" and "overvoltage" parameters, the inputs basically relate to the specified desired value. For "overcurrent" and "undercurrent", the values relate to the set rated current of the current transformer or the selected current transformer connection, respectively.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
97
7 Functions and settings
7.3.10.1
Activating/deactivating absolute limit values When you activate absolute limit values, these are used in place of those relating to the desired value. The following settings are possible: Setting
Effect
Off On
The percentage values entered are used The absolute values entered are used
Table 35
Activation/deactivation of absolute limit values
To activate/deactivate the absolute limit values, proceed as follows: 1.
> Parameter > Limit values. Absolute limit values.
2. Press setting. 3. Press
for "On" setting or
for "Off"
.
The absolute limit value is activated/deactivated. 7.3.10.2
Setting the undervoltage V< limit value Undervoltage blocking prevents tap-change operations if there is a power cut. The voltage regulator output pulses are blocked and the red "V" LED is illuminated and a signaling relay is activated (IO-X1-X1/19, IO-X1/20 contacts) as long as there is overvoltage. You can set the interval for LOWER (see "Setting the switching pulse time" on page 142). Instead of the high-speed return control function, the control can also be blocked if the overvoltage value is exceeded. The V> overvoltage limit is entered as a percentage of the set desired value. Setting range
Step size
Factory setting
100 %...140 % of desired value
1%
110 %
Table 39
Setting range for V> overvoltage limit as percentage
To set overvoltage blocking, proceed as follows: 1.
>
Parameter >
Limit values
> 3x . Overvoltage V> [%]. 2. Press reduce it. 3. Press
to increase the value or
to
.
V> overvoltage blocking is set.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
101
7 Functions and settings
7.3.10.4
Setting the V> overvoltage limit value as an absolute value You can also set the "Overvoltage blocking" function as an absolute value. To do this, you must have also activated the "On" selection under "Absolute limit values". This setting is made as an absolute value in unit V. This value relates to the secondary transformer voltage. Setting range
Step size
Factory setting
100 V – 160 V
0.1 V
110 V
Table 40
Setting range for overvoltage blocking V> in V, absolute value
If you use the key to change the display to unit kV, this value relates to the primary transformer voltage. Setting range
Step size
Factory setting
100 %...160 % of the primary transformer voltage
1 kV
1 kV
Table 41
Setting range for overvoltage blocking V> in kV, absolute value
This, for example, results in a setting range of 50 kV to 80 kV at a primary transformer voltage of 50 kV. To set overvoltage blocking, proceed as follows: 1.
>
Parameter >
Limit values
> 4x . Overvoltage V> [V]. 2. If necessary press want, "V" or "kV". 3. Press reduce it. 4. Press
to select the unit you
to increase the value or
to
.
V> overvoltage blocking is set.
102
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.3.10.5
Setting limit value I> overcurrent The I> overcurrent blocking prevents tap-change operations during load currents which are higher than the selected limit value (e.g. overload). As soon as the measured current exceeds the set blocking value, control is blocked. The "I>" LED lights up and the relevant signaling relay is permanently activated (IO-X1/18, IO-X1/19, IO-X1/20 contacts). The value is entered as a percentage. You can use the key to change the input from a percentage [%] to absolute values in amps [A]. In both cases, the value relates to the primary transformer current. Setting range
Step size
Factory setting
50 %...210 %
1%
110 %
Table 42
Setting range for I> overcurrent blocking as %
Setting range
Step size
Factory setting
50 %...210 % of primary transformer current
1A
1A
Table 43
Setting range for I> overcurrent blocking in A
This, for example, results in a setting range of 50 A to 210 A at a primary transformer current of 100 A. To set the limit value I> overcurrent for overcurrent blocking, proceed as follows: 1.
>
Parameter >
Limit values
> 5x . Overcurrent I>. 2. If necessary press want: "%" or "A". 3. Press reduce it. 4. Press
to select the unit you
to increase the value or
to
.
I> overcurrent blocking is set.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
103
7 Functions and settings
7.3.10.6
Activating/deactivating function monitoring If the measured value leaves the current bandwidth (desired value+/- bandwidth) for more than 15 minutes, the function monitoring relay is activated. This results in an alarm message on the display which is only reset when the measured value returns to within the current bandwidth. If the measured voltage is below 30 V, then the measured value is outside the bandwidth and the relevant relay is also activated after 15 minutes. You can deactivate this function if you want to avoid a function monitoring message when the transformer is switched off: 1.
>
Parameter >
Limit values
> 6x . Function monitoring. 2. Press or to activate (On)/deactivate (Off) function monitoring. 3. Press
.
The function monitoring is activated/deactivated for voltages
Parameter >
Limit values
> 7x . Delay time V
Limit values
> 8x . Blocking V
Limit values
> 9x . V< also below 30 V. 2. Press or to activate (on)/deactivate (Off) the signal for undervoltage V
Parameter >
Limit values
> 10x . Max. operations in time. 2. Press reduce it. 3. Press
to increase the value or
to
.
The maximum number of RAISE operations is set.
7.3.11.2
Setting time window for monitoring RAISE operations This parameter is used to define the time window for monitoring the number of consecutive RAISE operations. Setting range
Step size
Factory setting
0...1800 s
1s
120 s
Table 46
108
TAPCON® 260
Setting range for time period for monitoring RAISE operations
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
To set the time window, proceed as follows: 1.
>
Parameter >
Limit values
> 11x . Time window for steps. 2. Press reduce it. 3. Press
to increase the value or
to
.
The time window is set.
7.3.11.3
Setting maximum number of RAISE operations This parameter is used to define the blocking time after the maximum permissible number of consecutive RAISE operations has been reached. Any further RAISE command during this blocking time is blocked. Setting range
Step size
Factory setting
0...600 s
1s
300 s
Table 47
Setting range for blocking time after the maximum permissible number of RAISE operations has been reached
To set the blocking time, proceed as follows: 1.
>
Parameter >
Limit values
> 12x . T block max. number of steps 2. Press reduce it. 3. Press
to increase the value or
to
.
The blocking time is set.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
109
7 Functions and settings
7.3.11.4
Setting counting behavior This parameter can be used to define the counting behavior. All RAISE operations within the defined time period are counted as standard, even if they have been interrupted by a LOWER operation. Alternatively, you can stipulate that the counter is set to 0 during a LOWER operation. Parameters
Function
Off On
LOWER operations do not affect the counting method. The counter is reset during a LOWER operation.
Table 48
Setting range for blocking time after the maximum permissible number of RAISE operations has been reached
To set the blocking time, proceed as follows: 1.
>
Parameter >
Limit values
> 13x . Lower -> Raise counter 0. 2. Press want. 3. Press
or
to set the option you
.
The required option is selected.
110
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.3.12
Compensation The quality of the energy supply depends not only on the voltage at the busbar of the supply transformer (measurement value V), but also the voltage directly at the equipment. In some cases the line impedance - of the cables or overhead lines - needs to be taken into account for voltage regulation. A significant (load-dependent) voltage drop can occur in these cables. This voltage drop is dependent on the following factors at the consumer:
Impedance (apparent resistance)
Cable
Electrical current
Phase angle φ
The voltage regulator has two possible ways of balancing a load-related voltage drop between the transformer and the consumer:
Line drop compensation
Z compensation
Comparison between line drop compensation and Z Compensation Line drop compensation (vectorial compensation):
provides more precise compensation of cable voltage drops
requires several parameters
requires full knowledge of the cable data
Z compensation:
can be used with minor changes in the phase angle cos φ
is not dependent on phase angle cos φ
is simple to set
can also be used in meshed grids
Both methods are described in more detail in the following sections.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
111
7 Functions and settings
7.3.12.1
Line drop compensation Line drop compensation requires exact cable data. Line voltage drops can be compensated very accurately using LDC. To set the line drop compensation correctly, you have to calculate the ohmic and inductive voltage drop, in relation to the secondary side of the voltage transformer in V. The existing measuring circuit also has to be set correctly. The setting values must first be calculated in order to enter the correct values for the ohmic and inductive voltage drops. Sample calculation: Vr Vx IN kCT kVT r x L
LDC setting for ohmic line voltage drop in V LDC setting for inductive line voltage drop in V Nominal current in A of selected current transformer connection on voltage regulator: 0.2 A; 1 A or 5 A Current transformer ratio; for example 200 A/5 A Voltage transformer ratio Ohmic line resistance in Ω/km per phase Inductive line resistance in Ω/km per phase Length of line in km
Formula for calculating the ohmic voltage drop:
Formula for calculating the inductive voltage drop:
112
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
Calculation:
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
113
7 Functions and settings
If the active and reactive voltage drops "Vr" and "Vx" are set correctly, then the voltage at the line end remains constant irrespective of the load. Figure name
Table 49
Line drop equivalent circuit
Table 50
Line drop compensation
The settings for the compensation methods are described in more detail below: 7.3.12.2
Setting the ohmic voltage drop Vr The calculated ohmic voltage drop must be entered in the "Vr" display. The compensation effect can be rotated by 180° in the display using a plus or minus sign. Line drop compensation and Z compensation can be used at the same time. So make sure that you set the parameter for the method of compensation not used to "0".
114
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
Setting range
Step size
Factory setting
-25 V...25 V
0.1 V
0V
Table 51
Setting range for ohmic voltage drop Vr
To set the ohmic voltage drop Vr, proceed as follows: 1.
>
Parameter >
Compensa-
tion. Line drop compensation Vr. 2. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press
to increase the value or
to
.
The ohmic voltage drop Vr is set. 7.3.12.3
Setting the inductive voltage drop Vx The calculated inductive voltage drop must be entered in the "Vx" display. The compensation effect can be rotated by 180° in the display using a plus or minus sign. If you do not want to use a method of compensation, a "0" must be entered for both methods.
Line drop compensation and Z compensation can be used at the same time. So make sure that you set the parameter for the method of compensation not used to "0".
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
115
7 Functions and settings
Setting range
Step size
Factory setting
-25 V...25 V
0.1 V
0V
Table 52
Setting range for inductive voltage drop Vx
To set the inductive voltage drop Vx, proceed as follows: 1.
>
Parameter >
Compensa-
tion > 1x . I> Line drop compensation Vx. 2. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press
to increase the value or
to
.
The inductive voltage drop Vx is set. 7.3.12.4
Setting Z compensation Z compensation can be used for example for minor changes to the phase angle cos φ. It can also be used for meshed grids. Z compensation is not however dependent on cos φ. To correctly set the parameters, you need to calculate the voltage increase (ΔV) taking the current into account. Sample calculation: ΔV VTr VLa I IN kCT
116
TAPCON® 260
Z compensation setting as % Transformer voltage with current I Voltage on line end with current I and on-load tap-changer in same operating position Load current in A Nominal current in A of selected current transformer connection on voltage regulator: 0.2 A, 1 A or 5 A Current transformer ratio; for example 200 A or 5 A
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
Formula for determining the voltage increase ΔV:
Calculation:
The calculated voltage increase percentage relates to the desired voltage value and must be entered in this display. If you do not want to use a method of compensation, a "0" must be entered for both methods.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
117
7 Functions and settings
Setting range
Step size
Factory setting
0 %...15 % of desired value
0.1 %
0%
Table 53
Setting range for Z compensation
To set the Z compensation, proceed as follows: 1.
>
Parameter >
Compensa-
tion > 2x . I> Z compensation. 2. Press reduce it. 3. Press
to increase the value or
to
.
The Z compensation is set.
118
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.3.12.5
Setting the Z compensation limit value ΔV If Z compensation is activated, you must limit the maximum permissible increase in voltage, with reference to the desired value, to avoid excessive voltage on the transformer. Setting range
Step size
Factory setting
0 %...15 % of desired value
0.1 %
0%
Table 54
Setting range for Z compensation limit value ΔV
To set the limit value ΔV, proceed as follows: 1.
>
Parameter >
Compensa-
tion > 3x . Z compensation limit value. 2. Press reduce it.
to increase the value or
to
3. Press . The limit value ΔV is set.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
119
7 Functions and settings
7.3.13
Cross-monitoring Cross-monitoring permits the reciprocal monitoring of 2 voltage regulators. The voltage regulator detects potential errors in the following parts and reports them via the standard self-monitoring:
Mains unit
Processor error
No program
Should an error occur, this is signaled via the status contact. The reciprocal cross-monitoring can therefore only be restricted to the following: No measured value and/or measurement card error With voltage regulators which check one another, the measured value of the other voltage regulator is supplied via second measurement inputs. The measured values calculated accordingly for the voltage regulators are obtained via the CAN bus and compared with the original measured values. If the measured values deviate, the "Measured value error" signal is issued via an output relay. The second measurement inputs should be considered separately from the first ones. This allows voltage regulators from different voltage levels to be checked. Checking voltage regulation within definable upper and lower limits A measured voltage is supplied to a voltage regulator via a second measurement input. In addition to this measured value, a separate desired value, a lower limit and an upper limit and a time delay can be set. If one of these limits is exceeded, a signal is issued via an output relay after the set time. If wired accordingly, relay contacts can block the raise/lower pulse to the motor-drive unit. Regulation of individual voltage regulators is not affected by limit value monitoring. In order to ensure communication between the monitoring voltage regulators via the CAN bus interface, the CAN address must be entered. "1" must be assigned as the CAN address for the first voltage regulator and "2" for the second one.
120
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.3.13.1
Setting V-desired for regulator 2 You can set the desired value of the voltage regulator to be monitored as an absolute value in V or kV units under this menu item. If you use the key to change the display, this value relates to the primary transformer voltage. If you change the display to V, this relates to the secondary voltage. Setting range
Step size
Factory setting
49 V – 140 V
0.1 V
100 V
Table 55
Setting range for desired value for regulator 2 (V)
To enter the desired value for voltage regulator 2, proceed as follows: 1.
> Parameter > Cross-monitoring. Vdesiredregulator 2.
2. Press reduce it. 3. Press
to increase the value or
to
.
The desired value for voltage regulator 2 is set.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
121
7 Functions and settings
7.3.13.2
Setting undervoltage blocking V< (%) for regulator 2 You can set the limit value for undervoltage blocking of the voltage regulator to be monitored as an absolute value under this menu item. Setting range
Step size
Factory setting
34 V – 160 V
1V
60 V
Table 56
Setting range for undervoltage blocking for regulator 2 (V)
To enter the limit value for undervoltage blocking for voltage regulator 2, proceed as follows: 1.
>
Parameter >
Cross-monitoring > 2x V< regulator 2. 2. Press reduce it. 3. Press
.
to increase the value or
to
.
The limit value for undervoltage blocking is set as an absolute value.
122
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.3.13.3
Setting undervoltage blocking V< (%) for regulator 2 You can set the limit value for overvoltage blocking of the voltage regulator to be monitored as a percentage in this display. Setting range
Step size
Factory setting
60 %...100 %
1%
60 %
Table 57
Setting range for undervoltage blocking for regulator 2 (%)
To enter the limit value for undervoltage blocking for voltage regulator 2, proceed as follows: 1.
>
Parameter >
Cross-monitoring > 1x V< regulator 2. 2. Press reduce it. 3. Press
.
to increase the value or
to
.
The limit value for undervoltage blocking is set as a %.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
123
7 Functions and settings
7.3.13.4
Setting V> overvoltage blocking for regulator 2 (%) You can set the limit value for overvoltage blocking of the voltage regulator to be monitored as a percentage in this display. Setting range
Step size
Factory setting
100 %...140 %
1%
140 %
Table 58
Setting range for overvoltage blocking for regulator 2 (%)
To enter the limit value for overvoltage blocking for voltage regulator 2, proceed as follows: 1.
>
Parameter >
Cross-monitoring > 3x V< regulator 2. 2. Press reduce it. 3. Press
.
to increase the value or
to
.
The limit value for overvoltage blocking is set as a %.
124
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.3.13.5
Setting V> overvoltage blocking for regulator 2 (absolute values) You can set the limit value for overvoltage blocking of the voltage regulator to be monitored as an absolute value in this display. Setting range
Step size
Factory setting
34 V – 160 V
1V
140 V
Table 59
Setting range for overvoltage blocking for regulator 2 (V)
To enter the limit value for overvoltage blocking for voltage regulator 2, proceed as follows: 1.
>
Parameter >
Cross-monitoring > 4x V< regulator 2. 2. Press reduce it. 3. Press
.
to increase the value or
to
.
The limit value for overvoltage blocking is set as an absolute value.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
125
7 Functions and settings
7.3.13.6
Setting delay time for error message If an error is recorded by a monitoring voltage regulator, you can set the error message delay time in this display. Setting range
Step size
Factory setting
0 s...10 s
1s
10 s
Table 60
Setting range for error message delay time
To set the error message delay time for voltage regulator 2, proceed as follows: 1.
>
Parameter >
Cross-monitoring > 5x Error message. 2. Press reduce it. 3. Press
.
to increase the value or
to
.
The error message delay time for regulator 2 is set.
126
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.3.13.7
Setting the secondary transformer voltage for regulator 2 In this display, you can set the secondary transformer voltage of the voltage regulator to be monitored. Setting range
Step size
Factory setting
57 V – 110 V
1V
100 V
Table 61
Setting range for secondary transformer voltage for regulator 2 - V
Setting range
Step size
Factory setting
0 kV...9999 kV 0 kV...999.9 kV 0 kV...99.99 kV
1 kV 0.1 kV 0.01 kV
0 kV
Table 62
Setting range for secondary transformer voltage for regulator 2 - kV
To set the secondary transformer voltage of voltage regulator 2, proceed as follows: 1.
>
Parameter >
Cross-monitoring > 6x . V sec regulator 2. 2. Press reduce it. 3. Press
to increase the value or
to
.
The secondary transformer voltage of voltage regulator 2 is set.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
127
7 Functions and settings
7.3.13.8
Setting primary transformer voltage for regulator 2 In this display you can set the primary transformer voltage of the voltage regulator to be monitored. Setting range
Step size
Factory setting
0 kV...9999 kV 0 kV...999.9 kV 0 kV...99.99 kV
1 kV 0.1 kV 0.01 kV
0 kV
Table 63
Setting range for primary transformer voltage for voltage regulator 2
To set the primary transformer voltage of voltage regulator 2, proceed as follows: 1.
>
Parameter >
Cross-monitoring > 7x . V prim voltage reg 2. 2. Press to highlight the decimal place. The decimal place is defined and the value can be changed. 3. Press reduce it. 4. Press
to increase the value or
to
.
The primary transformer voltage of voltage regulator 2 is set.
128
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.4
Configuration This section describes how to carry out all the settings for configuring system-specific data. To make it easier for you to find specific parameters, the description refers to subgroups of individual parameters with related functions.
7.4.1
Transformer data The transformation ratios and measuring set-up for the voltage and current transformers used can be set in the relevant displays. The relevant settings are described in the following sections.
7.4.1.1
Setting the primary transformer voltage In general, the regulator only displays the secondary transformer voltage in V if you have not set the primary transformer voltage. The primary voltage is only displayed if you have previously set the "Display V / kV" parameter. The setting variants are shown in the table below. Primary voltage
With a kV or V setDisplay ting
Secondary voltage
No parameterization 100 V 110 kV 100 V Table 64
V kV
100 V 110 kV
Example of display variants
Setting range
Step size
Factory setting
0 kV... 9999 kV 0 kV...999.9 kV 0 kV...99.99 kV
1 kV 0.1 kV 0.01 kV
100 kV
Table 65
Setting range for primary transformer voltage
To set the primary transformer voltage, proceed as follows:
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
129
7 Functions and settings
1.
> Configuration > mer data. Primary voltage.
Transfor-
2. Press to highlight the decimal place. The decimal place is defined and the value can be changed. 3. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 4. Press reduce it. 5. Press
to increase the value or
to
.
The primary transformer voltage is set.
130
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.4.1.2
Setting the secondary transformer voltage The secondary transformer voltage is displayed and entered in V. Setting range
Step size
Factory setting
100 V – 110 V
0.1 V
100 V
Table 66
Setting range for secondary transformer voltage
To set the secondary transformer voltage, proceed as follows: 1.
>
Configuration >
Transfor-
mer data > 1x . Secondary voltage. 2. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 3. Press reduce it.
to increase the value or
to
4. Press . The transformer secondary voltage is set.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
131
7 Functions and settings
7.4.1.3
Setting the primary transformer current In general the voltage regulator displays the percentage current of the chosen measurement input. As soon as the primary rated current (e.g. 50 A) is set on the voltage regulator, the display in the Info menu switches over to "A" (amperes). The primary current is always displayed in "A" on the main screen or as "0" if no primary current is specified. Current feed
Setting parameter Primary current
Secondary current
Electrical connection
Unknown
1A
Info screen Primary / secondary current 100 %
1A
1A
1A
0A
Unknown
1A
1A
1A
100 % (of primary current) 1A (of secondary current)
50 A (of primary current) 50 A (of primary current)
No parameterization No parameterization 50 A
50 A Table 67
132
Display Main screen 0A
Example of unit displayed: % / A
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
Setting range
Step size
Factory setting
100 A – 10,000 A
1A
200 A
Table 68
Setting range for primary transformer current
To set the primary transformer current, proceed as follows: 1.
>
Configuration >
Transfor-
mer data > 2x . Primary current. 2. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press
to increase the value or
to
..
The primary transformer current is set.
7.4.1.4
Setting the current transformer connection The current transformer connection must be selected in order to obtain the correct display. If you set the current transformer connection to "Unknown" in the display, the percentage value is shown. However, if a connection is selected, the absolute value (in amps) is displayed. The following values can be set:
0.2 A
1A
5A
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
133
7 Functions and settings
To set the current transformer connection, proceed as follows: 1.
>
Configuration >
Transfor-
mer data > 3x . Current transformer connection. 2. Press terminal. 3. Press
or
to select the required
.
The current transformer connection has been set.
7.4.1.5
Setting the phase difference for the current/voltage transformer The normal measuring circuit values can be set as follows: System
Setting
Display
Single-phase Three-phase Three-phase Three-phase Three-phase
0 0 90 30 -30
0 1PH 0 3PH 90 3PH 30 3PH -30 3PH
Table 69
Setting options for the measuring circuits
Circuit a:
Figure 19
134
Circuit a - phase angle to be set 0;1PH
Voltage transformer VT is connected to phase and neutral.
Current transformer CT is looped in phase.
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
Voltage VU and current IU are in phase.
The line phase voltage drop is determined by current IU.
Circuit a:
Figure 20
Circuit a - phase angle to be set 0;3PH
Voltage transformer VT is connected to U and N.
Current transformer CT is looped in U.
Voltage VU and current IU are in phase.
The line phase voltage drop is determined by current IU.
Circuit b:
Figure 21
Circuit b - phase angle to be set 0;3PH
Voltage transformer VT is connected to U and V.
Current transformer CT1 is looped in U and CT2 in V.
Current transformer CT1and CT2 are connected crosswise in parallel. Current summation = IU + IV.
Current IU + IV and voltage VU V are in phase.
The line phase voltage drop is determined by current: (IU + IV)/ 3.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
135
7 Functions and settings
Circuit c:
Figure 22
Circuit c - phase angle to be set 90;3PH
Voltage transformer VT is connected to U and V.
Current transformer CT is looped in W.
Current IW ahead of voltage VU V by 90°.
The line phase voltage drop is determined by current IW.
Circuit d:
Figure 23
136
Circuit d - phase angle to be set 30;3PH
Voltage transformer VT is connected to U and V.
Current transformer CT is looped in V.
Current IV ahead of voltage VU v by 30°.
The line phase voltage drop is determined by current IV.
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
Circuit e
Figure 24
Circuit e - phase angle to be set -30;3PH
Voltage transformer VT is connected to U and V.
Current transformer CT is looped in U.
Current IU lags behind voltage VU V by -30°. The line phase voltage drop is determined by current IU.
To set the phase difference for the measured transformer circuit, proceed as follows: 1.
>
Configuration >
Transfor-
mer data > 4x . Transformer circuit. 2. Press or phase difference. 3. Press
to select the required
.
The phase difference is set.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
137
7 Functions and settings
7.4.2
General This submenu enables general settings, which are also required for commissioning, to be made on the device. You can change the following general settings:
7.4.2.1
Language
Regulator ID
Baud rate (COM1 setting)
Voltage display kV / V
Current display %/A
Duration of raise and lower pulse
Configuration of free inputs/outputs (IOs)
Display dimming
Motor runtime
Setting the language The display language can be set or changed as desired. The following languages are available:
English
German
French
Spanish
Italian
Portuguese
1.
> Configuration > Language.
2. Press language. 3. Press
or
General.
to select the required
.
The language is set.
138
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.4.2.2
Setting the regulator ID The regulator ID consists of a 4-digit sequence of digits and is used as additional identification for a voltage regulator. Identification is only used for the "TAPCON®-trol - Software" visualization. If you do not want to set the regulator ID, the serial number and firmware version are the only features. The regulator ID can be used to ensure that the connection is established between the visualization software and a specific voltage regulator. During online communication, the software running on the PC queries this ID and compares it with the regulator data available. This enables accurate assignment of data or parameters.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
139
7 Functions and settings
To set the regulator ID, proceed as follows: 1.
>
Configuration >
General >
1x . Regulator ID. 2. Press
to change the first digit.
If you wish to enter a multi-digit sequence, proceed to step 3. If you do not wish to enter additional digits, proceed to step 7:
3. Press repeatedly (digit > 9) until another position appears. 4. If necessary press to highlight a digit position. The digit position you want is highlighted and can be changed. 5. Press
or
to change the digit.
6. Repeat steps 3 to 5 until all required digits have been entered. 7. Press
.
8. The regulator ID is set.
7.4.2.3
Setting the baud rate In this display, you can set the baud rate for the COM1 interface, for example to define the speed of transfer for communication with the TAPCON®-trol software. The following values can be set:
140
9.6 kilobaud
19.2 kilobaud
38.4 kilobaud
57.6 kilobaud
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
To set the baud rate, proceed as follows: 1.
>
Configuration >
General >
2x . Baud rate. 2. Press baud rate. 3. Press
or
to select the required
.
The baud rate is set. 7.4.2.4
Setting the voltage display kV/V Switching the display from V to kV converts the measurements and setting values in the device on the primary side of the voltage transformer and displays them accordingly. However, the primary side is always displayed in kV and the secondary side always in V. The display can only be changed from V to kV if all the transformer data have previously been entered.
To change the desired unit for the voltage display, proceed as follows: 1.
>
Configuration >
General >
3x . Display kV/V. 2. Press unit. 3. Press
or
to to select the kV or V
.
The required unit is set for the voltage display.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
141
7 Functions and settings
7.4.2.5
Setting current display unit In this display, you can set the unit for the limit values displayed for overcurrent and undercurrent as a percentage ("%") or absolute value ("A"). It is only possible to change from % to A if all the transformer data have previously been entered.
To set the desired unit for the current display, proceed as follows: 1.
>
Configuration >
General
> 4x . Display %/A. 2. Press unit. 3. Press
or
to to select the % or A
.
The required unit is set for the current display.
7.4.2.6
Setting the switching pulse time This display can be used to set the duration of the switching pulse for the motor-drive unit. If you set the raise or lower switching pulse time to 1.5 seconds for example, after the set delay time T1 or T2 there will be a switching pulse of 1.5 seconds. The waiting time between 2 consecutive switching pulses corresponds to the set delay time T1 or T2.
142
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
Figure 25
1 2 3 4
Switching pulse in standard operating mode
T1 = set delay time Start of first raise/lower switching pulse Ti = switching pulse time (1.5 seconds) Start of second raise/lower pulse
In Quick Tap mode the next switching pulse can only take place after 1.5 seconds.
Figure 26
1 2 3
Switching pulse in Quick Tap mode
Start of first raise/lower switching pulse Ti = set switching pulse time (1.5 seconds) Earliest time for the next raise/lower switching pulse (1.5 seconds)
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
143
7 Functions and settings
A continuous pulse is output if you set the raise/lower switching pulse duration to 0. If the motor-drive unit does not start using the default setting (1.5 seconds), then please increase the pulse time.
Setting range
Step size
Factory setting
0 s...10 s
0.1 s
1.5 s
Table 70
Setting range for raise/lower switching pulse duration
To set the pulse duration, proceed as follows: 1.
>
Configuration >
General >
5x . R/L pulse duration. 2. Press you want. 3. Press
or
to set the pulse duration
.
The R/L pulse duration is now set.
144
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.4.2.7
Configuring control inputs IO1-X1:33/31 You can assign functions to freely configurable control inputs in this display. You can assign the following functions to control inputs IO1-X1:33 and IO-X1:31: Possible function
Function description
Off Master/Follower
No function selected Master mode active when signal on. Follower mode active when signal off. "Local" mode active. "Remote" mode off. Automatic regulation blocked T1/T2 deactivated. Raise/lower switching pulse occurs when value exceeds/falls below bandwidth. Signal: Motor protective switch was triggered. "Remote" mode active. "Local" mode off.
Local/Rem. Blocking LV S operation
MPS tripped Remote/Loc. Table 71
Possible functions for control inputs
You can assign the "Local/Remote" function to either control input IO-X1:z 2 0 or control input IO-X1:d 20. The functions described below can be set for this assignment:
Setting at control input
Signal
Manual/Auto and Raise/Lower can be set with F keys on the front panel
Off Local/Rem. Local/Rem. Remote/Local Remote/Local
0 or 1 0 1 0 1
Yes No Yes Yes No
Table 72
Manual/Auto and Raise/Lower can be set via control inputs for remote control or via a serial interface Yes Yes No No Yes
Setting options for "Local" and "Remote" modes
If both freely configurable control inputs, IO-X1:31 and IO-X1:33, have different or reversed settings, all voltage regulator functions are blocked. Example: If you have set both control inputs to "Local/Remote", and the signal is high (1), but low (0) on the other control input, the "Manual/Auto" and "Raise/lower" functions are not possible with either the F keys on the front panel or the inputs for remote messages or serial interface.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
145
7 Functions and settings
To assign functions to the control inputs, proceed as follows 1.
>
Configuration >
General >
6x . IO1-X1:33. 2. Press or repeatedly until the required function appears in the display. 3. Press
.
The function is assigned. All control inputs can be configured as described above. All the following control inputs are available: Control input IO1-X1:33 IO1-X1:31 Table 73
146
TAPCON® 260
Press 6x 7x
Page number in the display
.
Freely configurable control inputs (IOs)
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.4.2.8
Configuring output relays IO1-X1:25/26 and IO1-X1:23/24 You can assign functions to freely configurable output relays in this display. You can assign the following functions to output relays IO1-X1:25/26 and IO-X1:23/24: Possible function
Function description
Off Master/Follower
Undervoltage Overvoltage Desired value 2
No function selected Master mode active when signal on. Follower mode active when signal off. "Local" mode active. "Remote" mode off. Message: Undervoltage blocking. Message: Overvoltage blocking. Message: Desired value 2
Desired value 3 Motor drive runtime pulse> Motor drive runtime continuous> Motor running Bandwidth < Bandwidth >
Message: Desired value 3 Message: Pulse triggered; motor runtime exceeded. Message: Continuous signal; motor runtime exceeded. Message: Motor running Message: Value below bandwidth. Message: Bandwidth exceeded.
Local/Rem.
Table 74
Possible functions for output relays
To assign functions to the output relays, proceed as follows: 1.
>
Configuration >
General >
8x . IO1-X1:25/26. 2. Press or repeatedly until the desired function appears in the display. 3. Press
.
The function is assigned.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
147
7 Functions and settings
All output relays can be configured as described above. All the following outputs are available: Output relay
Press 8x 9x
IO1-X1:25/26 IO1-X1:23/24 Table 75
7.4.2.9
Page number in the display
.
Freely configurable output relays (IOs)
Activating/deactivating display dimming If you activate this function, the display is automatically dimmed if no key is pressed within a period of 15 minutes. However, the display can still be read. Activating this function extends the lifespan of the display. The display returns to full brightness by pressing any key. 1.
>
Configuration >
General >
10x . Display off. 2. Press or or off (OFF). 3. Press
to switch display on (ON)
.
Display is switched ON/OFF.
7.4.2.10
Monitoring motor runtime The motor-drive unit's runtime can also be monitored by the voltage regulator. This function is used to identify motor-drive unit malfunctions during the tap-change operation and to trigger any actions needed. The corresponding control input must be correctly wired and parameterized to "Motor running" in order to use runtime monitoring. The motor runtime must also be set.
148
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
The motor-drive unit supplies the "Motor-drive unit running" signal during the tap-change operation. This signal is present until the tap-change operation is complete. The voltage regulator compares the duration of this signal with the motor runtime set. If the set motor runtime is exceeded, the voltage regulator triggers various actions:
7.4.2.11
1.
"Motor runtime monitoring" message
2.
Continuous signal via output relay "Motor-drive unit runtime exceeded" (optional)
3.
Impulse signal via output relay "Trigger motor protective switch" (optional)
Wiring and parameterizing control input/output relay If you want to monitor the motor runtime, the voltage regulator and motor-drive unit must be connected and parameterized as shown below.
Figure 27 1 2 3 4
Wiring for motor runtime monitoring
"Motor running" control input I/O "Motor protective switch triggered" control input I/O (optional) "Trigger motor protective switch" output relay I/O (optional) "Motor-drive unit runtime exceeded" output relay I/O (optional)
If you want to use the output relay, the feedback from the motor-drive unit "Motor protective switch triggered" must be wired to a control input and parameterized. This message resets the "Motor runtime exceeded" output relay when the motor protective switch is switched back on and activates the "Motor protective switch triggered" message.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
149
7 Functions and settings
Setting range
Step size
Factory setting
0 s...30 s
0.1 s
0s
Table 76
Setting range for motor runtime
To set the motor runtime, proceed as follows: If the runtime monitoring is set to "0.0 s" this equates to it being switched off.
1.
>
Configuration >
General
> 11x . Motor runtime. 2. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press
to increase the value or
to
.
The motor runtime is set.
150
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.4.3
Parallel operation Mains power supply sometimes requires an increase in the short-circuit capacity or the throughput capacity at a site. For this reason, tapped transformers are connected in parallel. A safer and more cost effective parallel operation is achieved if the joint capacity of the transformers connected in parallel is utilized without overloading individual transformers. Compliance with the following general conditions is recommended for operating transformers in parallel: Identical rated voltage Ratio of transformer output ( Configuration > Parallel operation. Parallel operation method.
2. Press or to Deactivate the parallel operation method by selecting "Off". 3. Press
.
The parallel operation method is deactivated. 7.4.3.3
Selecting circulating reactive current sensitivity When circulating reactive current is selected, then parallel operation is carried out using the circulating reactive current minimization method. The circulating reactive current is calculated from the transformer currents and their phase angles. A voltage proportional to the circulating reactive current is added to the independently operating voltage regulators as a correction for the measurement voltage. This voltage correction can be reduced or increased using the circulating reactive current sensitivity setting. The circulating reactive current sensitivity method is suited to transformers connected in parallel with a similar nominal output and nominal voltage VK and to vector groups with the same and different step voltages. This does not require any information about the tap position. This parallel operation method requires each transformer in the parallel vector group to be controlled by a separate voltage regulator.
When setting the "circulating reactive current" parallel operation method, the values for blocking and circulating reactive current sensitivity must first be set.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
153
7 Functions and settings
To select the "circulating reactive current" parallel operation method, proceed as follows: 1.
> Configuration > Parallel operation. Parallel operation method.
2. Press or repeatedly until "circulating reactive current" appears in the display The parallel operation method "Circulating reactive current" is selected.
7.4.3.4
Defining the master tap synchronization method With this parallel operation method the voltage regulator is designated as the master. This voltage regulator takes control while all other follower voltage regulators comply with the control commands of the master. The master compares the tap positions of the followers with its own tap position using the CAN bus. If there is a tap difference, the master directs the followers to be adjusted to the same tap position. If the specified master fails, then the error message "Parallel operation error: no master available" appears in the display. In addition, depending on the configuration of the "Simplex mode blocking" parameter, those voltage regulators which are set accordingly are blocked or continue in simplex mode.
Please note that each voltage regulator must be assigned an address using the "CAN Address" display. Each address may only be used once. Only when all voltage regulators are registered can they communicate with one another using the CAN bus and use the "master/follower" method.
154
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
To specify the "master" parallel operation method, proceed as follows: 1.
> Configuration > Parallel operation. Parallel operation method.
2. Press or repeatedly until "Master" appears in the display. 3. Press
.
The "Master" parallel operation method is selected. 7.4.3.5
Specifying the follower tap synchronization method With this parallel operation method the voltage regulator is designated as the follower. This voltage regulator receives the control commands from the master and as the follower has to comply with them. To define the "Follower" parallel operation method, proceed as follows: 1.
> Configuration > Parallel operation. Parallel operation method.
2. Press or repeatedly until "Follower" appears in the display. 3. Press
.
The "Follower" parallel operation method is selected.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
155
7 Functions and settings
7.4.3.6
Specifying the follower tap synchronization method With this parallel operation method, the voltage regulator with the lowest CAN address within the same parallel operation group is automatically selected as master. This voltage regulator undertakes the measurement and adjusts the on-load tap-changer in order to correct the voltage if a deviation occurs. As with the "Master" parallel operation method, the voltage regulator compares the tap position of the followers with its own tap position using the CAN bus. If there is a tap difference, the voltage regulator directs the followers to be adjusted to the same tap position. If there is a tap position difference between the master and follower which is larger than the maximum set tap difference , then the "Parallel operation error" signal is issued. Automatic regulation blocks. Please note that each voltage regulator must be assigned an address using the "CAN Address" display. Each address may only be used once. Only when all voltage regulators are registered can they communicate with one another using the CAN bus and use the "master/follower" method.
To specify the "Automatic tap synchronization" parallel operation method, proceed as follows: 1.
> Configuration > Parallel operation. Parallel operation method.
2. Press or repeatedly until "Auto synchronization" appears in the display. 3. Press
.
The "Automatic tap synchronization" parallel operation method is selected.
156
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.4.3.7
Selecting parallel operation control As an option, the voltage regulator can be fitted with a plug-in card for parallel operation with an existing parallel operation control unit when extending existing systems. The following parallel control units can be connected:
SKB 30E
VC 100E-PM/PC
The settings required for parallel control must be undertaken in accordance with the relevant valid operating instructions. If you do not have a parallel control unit, you must select the "Off" selection in the "SKB parallel operation" display. The possible selections are described in more detail in the table below. Selection
Function Parallel operation control with existing parallel control unit (plug-in card needed; see above) Parallel operation control via CAN bus
On Off Table 77
Possible setting for SKB
To select the type of parallel operation control, proceed as follows: 1.
>
Configuration >
Parallel
operation > 1x . SKB parallel operation. 2. Press "Off". 3. Press
to select "On" or
to select
.
The type of parallel control is set.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
157
7 Functions and settings
7.4.3.8
Entering CAN bus address So that all voltage regulators can communicate using the CAN bus, each voltage regulator requires a unique identifier. Addresses can be set from 1 to 16. If the value is set to 0, then no communication takes place. Setting range
Step size
Factory setting
0...16
1
1
Table 78
Setting range for CAN bus address
To enter the CAN bus address, proceed as follows: 1.
>
Configuration >
Parallel
. operation > 2x CAN address. 2. Press reduce it. 3. Press
to increase the value or
to
.
The CAN bus address is saved. 7.4.3.9
Specifying circulating reactive current sensitivity The sensitivity of the circulating reactive current is a measure of its effect on the behavior of the voltage regulator. A setting of 0% has no effect. With circulating reactive current relating to the rated current on the current transformer, if you set the value to 10 % for example, this would cause the voltage in the voltage regulator to be corrected by 10%. This correction to the voltage can be increased or decreased with this setting to attain the optimum value. As soon as you change the circulating reactive current sensitivity value, the value for the result changes in the help text in the display.
158
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
Setting range
Step size
Factory setting
0 %...100 %
0.1 %
0%
Table 79
Setting range for circulating reactive current sensitivity.
To set the circulating reactive current sensitivity, proceed as follows: 1.
>
Configuration >
Parallel
operation > 3x . Stability. 2. Press reduce it.
to increase the value or
to
3. Press to highlight the decimal place. The decimal place is highlighted and the value can be changed. 4. Press
.
The circulating reactive current sensitivity is set. 7.4.3.10
Setting the blocking threshold for the maximum permitted circulating reactive current In this display, you can set the limit value for the maximum permitted circulating reactive current in relation to the rated current of the current transformer. If, during parallel operation, the circulating reactive current exceeds the set limit value, then the following event is activated.
"Problem with parallel operation"
As a result, all voltage regulators operating in parallel are blocked. Depending on the set delay time, the "Parallel operation fault" signaling relay is activated (UC-X1/1 and UC-X1/2 signaling relay contact). The corresponding LED lights up. Setting the delay time for the parallel operation error message (see "Setting the delay time for the parallel operation error message" on page 160).
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
159
7 Functions and settings
Setting range
Step size
Factory setting
0.5 %...20 %
0.1 %
20 %
Table 80
Setting range for circulating reactive current blocking
To set the blocking threshold for the maximum permitted circulating reactive current, proceed as follows: 1.
>
Configuration >
Parallel
operation > 4x . Blocking. 2. Press reduce it. 3. Press
to increase the value or
to
.
The blocking threshold for the maximum permitted circulating reactive current is set. 7.4.3.11
Setting the delay time for the parallel operation error message If the voltage regulator detects an error during parallel operation, the following error message is issued:
"Problem with parallel operation"
This message can be issued with a delay so that there is no brief fault message if the motor-drive units involved in the parallel operation have different runtimes. If a parallel operation error occurs, then the relevant LED immediately lights up. The message is however only issued at the output relay after the set delay time. Automatic regulation is blocked and the on-load tap-changers can only be adjusted in manual mode. Setting range
Step size
Factory setting
1 s...30 s
1s
5s
Table 81
160
TAPCON® 260
Setting range for parallel operation error message delay time
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
To set the delay time for the parallel operation error message, proceed as follows: 1.
>
Configuration >
General >
5x . Error message. 2. Press reduce it. 3. Press
to increase the value or
to
.
The delay time for the parallel operation error message is set. 7.4.3.12
Selecting the follower tapping direction As in parallel operation the tap positions of the transformers which are running in parallel are compared according to the "Tap synchronization master/follower" method, it is absolutely essential that these transformers have the same position designation and that the "Raise" or "Lower" signals produce the same voltage change in all transformers. Should a scenario arise where the follower switches in the opposite direction to the master's tap change, you will have to change this parameter setting from "Default" to "Swapped". The following settings are possible: Default Swapped Table 82
dV>0 = tapping direction toward position 1 dV
Configuration >
Parallel
. operation > 6x Tapping direction swapped. 2. Press or tapping direction. 3. Press
to select the required
.
The tapping direction is selected.
7.4.4
Configuring analog inputs The analog input is used to record the tap position of an analog signal transmitter:
Resistor contact series (200 - 2,000 ohms)
Or injected current (0/4 - 20 mA)
Adjustment to the existing signal transmitter must be carried out during commissioning. 7.4.4.1
Setting lower limit value (%) for input 1 To configure the analog input, the lower value of the input signal must be specified. With injected current as the transmitter signal, 0 % should be entered for 0 mA. 20 % should be entered for 4 mA. Example: Tap position
Current
Value
Minimum tap position 1
4 mA
20 % of analog input signal range
Table 83
Example for configuring the analog input
If the signal transmitter for capturing the tap position is a resistor contact series, then 20 % should generally be set.
162
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
Setting range
Step size
Factory setting
0 %...100 %
0.1 %
0%
Table 84
Setting range of analog value - lower limit value as %
To assign the analog value for the lower limit, proceed as follows: 1.
>
Configuration >
Continue
> Analog inputs. Input 1, lower limit. 2. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press
to increase the value or
to
.
The analog value for the lower limit is assigned. 7.4.4.2
Setting upper limit value (%) for input 1 To configure the analog input, the upper value of the input signal must be specified. With impressed current as the transmitter signal, 20 % should be entered for 0 mA. Example: Tap position
Current
Value
Maximum tap position 19
20 mA
100 % of analog input signal range
Table 85
Example for configuring the analog input (maximum)
If the signal transmitter for capturing the tap position is a resistor contact series, then 100 % should generally be set.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
163
7 Functions and settings
Setting range
Step size
Factory setting
0 %...100 %
0.1 %
100 %
Table 86
Setting range of analog value - upper limit value as %
To assign the analog value for the upper limit, proceed as follows: 1.
>
Configuration >
> Analog inputs > 1x Input 1, upper limit.
Continue .
2. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press
to increase the value or
to
.
The analog value for the upper limit is assigned. 7.4.4.3
Setting lower limit value (absolute) of input 1 To configure the analog input, an absolute value must be assigned to the lower value of the applied signal. Example: You can set "1" for the lowest tap position.
164
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
Setting range
Step size
Factory setting
-999.9...999.9
0.1 / 1
0.0
Table 87
1.
Setting range for lower limit value (absolute value)
>
Configuration >
Continue
> Analog inputs > 2x Input 1, lower value. 2. Press reduce it. 3. Press
.
to increase the value or
to
.
The lowest tap position is set. 7.4.4.4
Setting upper limit value (absolute) for input 1 To configure the analog input, an absolute value must be assigned to the upper value of the applied signal. Example: You can set "25" for the highest tap position. Setting range
Step size
Factory setting
-999.9...999.9
0.1 / 1
0.0
Table 88
Setting range for upper limit value (absolute value)
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
165
7 Functions and settings
To set the highest tap position, proceed as follows: 1.
>
Configuration >
Continue
> Analog inputs > 3x . Input 1, upper value. 2. Press reduce it. 3. Press
to increase the value or
to
.
The highest tap position is set. 7.4.4.5
Setting lower limit value (%) for input 2 To configure the analog input, the lower value of the input signal must be specified. With injected current as the transmitter signal, 0 % should be entered for 0 mA. 20 % should be entered for 4 mA. Example: Tap position
Current
Value
Minimum tap position 1
4 mA
20 % of analog input signal range
Table 89
Example for configuring the analog input
If the signal transmitter for capturing the tap position is a resistor contact series, then 20 % should generally be set. Setting range
Step size
Factory setting
0 %...100 %
0.1 %
0%
Table 90
166
TAPCON® 260
Setting range of analog value - lower limit value as %
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
To assign the analog value for the lower limit, proceed as follows: 1.
>
Configuration >
Continue
> Analog inputs > 4x Input 2, lower limit.
.
2. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press
to increase the value or
to
.
The analog value for the lower limit is assigned. 7.4.4.6
Setting upper limit value (%) for input 2 To configure the analog input, the upper value of the input signal must be specified. With impressed current as the transmitter signal, 20 % should be entered for 0 mA. Example: Tap position
Current
Value
Maximum tap position 19
20 mA
100 % of analog input signal range
Table 91
Example for configuring the analog input (maximum)
If the signal transmitter for capturing the tap position is a resistor contact series, then 100 % should generally be set. Setting range
Step size
Factory setting
0 %...100 %
0.1 %
100 %
Table 92
Setting range of analog value - upper limit value as %
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
167
7 Functions and settings
To assign the analog value for the upper limit, proceed as follows: 1.
>
Configuration >
> Analog inputs > 5x Input 2, upper limit.
Continue .
2. Press to highlight a digit. The digit position you want is highlighted and the value can be changed. 3. Press reduce it. 4. Press
to increase the value or
to
.
The analog value for the upper limit is assigned. 7.4.4.7
Setting lower limit value (absolute) of input 2 To configure the analog input, an absolute value must be assigned to the lower value of the applied signal. Example: You can set "1" for the lowest tap position.
168
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
Setting range
Step size
Factory setting
-999.9...999.9
0.1 / 1
0.0
Table 93
1.
Setting range for lower limit value (absolute value)
>
Configuration >
Continue
> Analog inputs > 6x Input 2, lower value. 2. Press reduce it. 3. Press
.
to increase the value or
to
.
The lowest tap position is set. 7.4.4.8
Setting upper limit value (absolute) for input 2 To configure the analog input, an absolute value must be assigned to the upper value of the applied signal. Example: You can set "25" for the highest tap position. Setting range
Step size
Factory setting
-999.9...999.9
0.1 / 1
0.0
Table 94
Setting range for upper limit value (absolute value)
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
169
7 Functions and settings
To set the highest tap position, proceed as follows: 1.
>
Configuration >
Continue
> Analog inputs > 7x . Input 2, upper value. 2. Press reduce it. 3. Press
to increase the value or
to
.
The highest tap position is set.
7.4.5
LED selection The settings in this subgroup can be used to assign inputs or functions to the 4 free LEDs. These would then light up during an event. The function required must have been set in advance. To label the LEDs, you can remove the label strip underneath and label individually using transferable lettering.
170
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.4.5.1
Functions available for LEDs An overview of all possible functions which you can assign to the LEDs is provided in the table below. Possible functions
Function description
Off IO1:25 IO1:23 IO1:21 IO1:18 UC1:2 UC1:4 UC1:6 UC1:8 UC1:10 UC1:19 UC1:21 UC1:23 UC1:25 UC1:27 UC2:2 UC2:4 UC2:6 UC2:8 UC2:10 UC2:19 UC2:21 UC2:23 UC2:25 UC2:27 IO1:33 IO1:31 IO1:29 IO1:28 IO1:17 IO1:16 IO1:14 IO1:13 IO1:11 IO1:12
LED deactivated Signal issued at IO1:25 input Signal issued at IO1:23 input Signal issued at IO1:21 input Signal issued at IO1:18 input Signal issued at UC1:2 input Signal issued at UC1:4 input Signal issued at UC1:6 input Signal issued at UC1:8 input Signal issued at UC1:10 input Signal issued at UC1:19 input Signal issued at UC1:21 input Signal issued at UC1:23 input Signal issued at UC1:25 input Signal issued at UC1:27 input Signal issued at UC2:2 input Signal issued at UC2:4 input Signal issued at UC2:6 input Signal issued at UC2:8 input Signal issued at UC2:10 input Signal issued at UC2:19 input Signal issued at UC2:21 input Signal issued at UC2:23 input Signal issued at UC2:25 input Signal issued at UC2:27 input Signal issued at IO1:33 input Signal issued at IO1:31 input Signal issued at IO1:29 input Signal issued at IO1:28 input Signal issued at IO1:17 input Signal issued at IO1:16 input Signal issued at IO1:14 input Signal issued at IO1:13 input Signal issued at IO1:11 input Signal issued at IO1:12 input
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
171
7 Functions and settings
Possible functions
Function description
UC1:33 UC1:32 UC1:31 UC1:30 UC1:17 UC1:16 UC1:15 UC1:14 UC1:12 UC1:11 UC2:33 UC2:32 UC2:31 UC2:30 UC2:17 UC2:16 UC2:15 UC2:14 UC2:12 UC2:11 SI:bef1 SI:bef2 Undervoltage Overvoltage Overcurrent Parameter error Motor protection Blocking Circulating reactive current
Signal issued at UC1:33 input Signal issued at UC1:32 input Signal issued at UC1:31 input Signal issued at UC1:30 input Signal issued at UC1:17 input Signal issued at UC1:16 input Signal issued at UC1:15 input Signal issued at UC1:14 input Signal issued at UC1:12 input Signal issued at UC1:11 input Signal issued at UC2:33 input Signal issued at UC2:32 input Signal issued at UC2:31 input Signal issued at UC2:30 input Signal issued at UC2:17 input Signal issued at UC2:16 input Signal issued at UC2:15 input Signal issued at UC2:14 input Signal issued at UC2:12 input Signal issued at UC2:11 input Signal issued at SI:bef1 input Signal issued at SI:bef2 input Undervoltage present Overvoltage present Overcurrent present Parallel operation error present Motor protective switch tripped Control blocked Parallel operation selected using circulating reactive current method Voltage regulator in parallel operation activated as master Voltage regulator in parallel operation activated as follower Auto mode active Value below bandwidth Value above bandwidth
Master Follower Automatic Bandwidth < Bandwidth > Table 95
172
TAPCON® 260
Possible functions for LEDs
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
A function can be assigned to an LED if desired. As soon as the corresponding event occurs, the selected LED lights up. There is a total of 6 LEDs available, each of which can be assigned an input or a function. To assign a function to an LED, proceed as follows (Example: "LED 1"): 1.
> Continue > LED 1.
LED selection.
2. Press or repeatedly until the required function appears in the display. 3. Press
.
The function is assigned. All additional LEDs can be assigned as described above. The LEDs available can be called up as follows: Press LED
Characteristics
LED 1 LED 2 LED 3 LED 4 red LED 4 green
Single-colored Single-colored Single-colored Two-colored Two-colored
.
Table 96
7.4.6
1x 2x 3x 4x
Page number in the display
Freely-configurable LEDs
Configuring transducer function Depending on the configuration and version of the transducer module 2 or 4, the transducer module can be used to obtain measured values as analog values in the following ranges: The following values are available:
V1
V2 (optional via a second measurement input)
I1
Active current
Reactive current
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
173
7 Functions and settings
Active power
Reactive power
Apparent power
Tap position
Desired value
If the analog outputs have not been set as you want them in the factory, the section below describes how you can change them for measuring transducer 1. Please undertake the settings form measuring transducers 2 to 4 in the same way. 7.4.6.1
Assigning measurement parameter of outputs 1 to 4 In this display you can assign a measurement parameter to be transferred to the transducer output. Possible settings
Factory setting
Off (no assignment) V1 (kV) I1 (A) Tap position Desired value V2 (kV) - optional via a second measurement input Active current Reactive current Apparent power Active power Reactive power Table 97
174
TAPCON® 260
Off
Measurement parameters for outputs 1 to 4
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
In order to assign a measurement parameter to the measuring transducer output, proceed as follows (example using transducer 1/2; "output 1 measured value"): 1.
>
Configuration >
Continue
> Continue > Measuring transducer 1/2. Output 1 measured value. 2. Press or repeatedly until the desired measurement parameter is displayed. 3. Press
.
The desired measurement parameter is assigned. 7.4.6.2
Assigning minimum physical parameter In this display you can assign a minimum physical parameter to the transducer output. Possible settings
Factory setting
4 mA 0 mA -1 mA -4 mA -10 mA -20 mA 0V -10 V Table 98
4 mA
Minimum physical parameters for outputs 1 to 4
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
175
7 Functions and settings
To assign the lower physical parameter to the measuring transducer, proceed as follows: 1.
> >
Configuration > Continue >
Continue
Measuring trans-
ducer 1/2 > 1x . Output 1, lower. 2. Press or repeatedly until the desired physical parameter is displayed. 3. Press
.
The desired physical parameter is assigned. 7.4.6.3
Assigning maximum physical parameter In this display you can assign a maximum physical parameter to the transducer output. Possible settings
Factory setting
1 mA 10 mA 20 mA 10 V Table 99
176
TAPCON® 260
20 mA
Maximum physical parameters for outputs 1 to 4
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
To assign the upper physical parameter to the measuring transducer, proceed as follows: 1.
> >
Configuration > Continue >
Continue
Measuring trans-
ducer 1/2 > 2x . Output 1, top. 2. Press or repeatedly until the desired physical parameter is displayed. 3. Press
.
The desired physical parameter is assigned. 7.4.6.4
Assigning minimum absolute value In this display you can assign a minimum limit value to the transducer output as an absolute value. Setting range
Step size
Factory setting
-9999...9999 -999.9...999.9 -99.99..99.99
1 0.1 0.01
0
Table 100
Setting range for lower limit value for measuring transducer.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
177
7 Functions and settings
To assign the minimum absolute value, proceed as follows: 1.
> >
Configuration > Continue >
Continue
Measuring trans-
ducer 1/2 > 3x . Output 1, lower value. 2. Press reduce it. 3. Press
to increase the value or
to
.
The minimum absolute value is assigned. 7.4.6.5
Assigning maximum absolute value In this display you can assign a maximum limit value to the transducer output as an absolute value. Setting range
Step size
Factory setting
-9999...9999 -999.9...999.9 -99.99..99.99
1 0.1 0.01
0
Table 101
Setting range for upper limit value for measuring transducer
To assign the maximum absolute value, proceed as follows: 1.
> >
Configuration > Continue >
Continue
Measuring trans-
ducer 1/2 > 4x . Output 1, value top. 2. Press reduce it. 3. Press
to increase the value or
to
.
The minimum absolute value is assigned.
178
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.4.7
Configuring measured value memory function (optional) You can undertake measured value memory settings in this subgroup. This configures the event memory and plotter function. The "Measured value plotter" module (8MB) can be used to save the data listed below and display and evaluate this either on the display or using the TAPCON®trol visualization software. For more detailed information, please refer to the respective technical files for both the hardware and visualization software. The following values are displayed:
Measured values On-load tap-changer position Voltage Active current Reactive current
Calculated values Active power Reactive power Apparent power Output factor
Calculation of the values stated depends on the measured values captured and the parameters set, for example: Current measuring circuit Primary current Voltage transformer data from primary and secondary sides A correct calculation can only be undertaken if the configuration data are correctly entered in full.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
179
7 Functions and settings
7.4.7.1
Average value memory and event memory The measured value plotter is split into the following areas: Average value memory In the average value memory, all measured and calculated values are averaged and saved using the average value intervals you set. You can set the average value intervals in stages between 1 and 40 seconds. You can set the average value interval (see "Setting time difference of average value interval" on page 186). Event memory Data is always saved to the event memory with the highest resolution without first being averaged. You can also determine how much memory space is to be made available exclusively for the event memory (see "Setting size of event memory" on page 187). The memory size is 8MB. The measured value plotter is equipped with event triggering such that an event is triggered depending on the undervoltage and/or overvoltage limit value that you can set. The data recorded here are stored in the measured value memory's event memory. To allow instances where values exceed or fall below the limit values to be better evaluated, the chronological sequence for the measured and calculated values also includes the last 10 seconds before the value exceeds or falls below the limit value. Event is saved for a maximum of 5 minutes. Only the time-based processes for values measured and calculated during the event are stored in the event memory.
If the event memory is full, the oldest values are overwritten by the new values measured. You can access information about the current event memory content via the "Info" menu.
180
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.4.7.2
Chronological sequence of voltage's effective value The measured value memory records the chronological sequence of the voltage's effective value. The chronological sequence for the tap positions is also shown to allow the control path to undergo an initial analysis. The voltage sequence can be displayed on the voltage regulator. The voltage and tap position can be displayed jointly using the TAPCON®trol visualization software. You must set the system date and system time if records are to feature the right times. The following sections describe how you can set these.
7.4.7.3
Setting system time You can set the system time in this display. The time format can be set using the 24-hour format: HH:MM:SS
To set the system time, proceed as follows: 1.
>
Configuration >
> Continue > Time.
Continue
Memory > 6x
.
2. Press or to select the number to be edited. The digit position you want is highlighted and can be changed. 3. Press 4. Press
or
to edit the digit.
.
The system time is set.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
181
7 Functions and settings
7.4.7.4
Setting system date You can set the system date in this display. The system date can be set from 01.01.2001 to 12.29.2099 and has the following format: DD:MM:YY
To set the system date, proceed as follows: 1.
>
Configuration >
Continue > > Date.
Continue
Memory > 7x
.
2. Press or to select the number to be edited. The digit position you want is highlighted and can be changed. 3. Press 4. Press
or
to edit the digit.
.
The system date is set. 7.4.7.5
Setting undervoltage threshold (%) In this display you can set the undervoltage threshold as a percentage. If the voltage falls below the set undervoltage threshold, high-resolution measured values are saved for as long as this situation prevails. Setting range
Step size
Factory setting
60 %...100 %
1%
90 %
Table 102
182
TAPCON® 260
Setting range for undervoltage V< threshold as percentage
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
To set the undervoltage threshold, proceed as follows: 1.
>
Configuration >
Continue
> Continue > Memory. Threshold V
Configuration >
Continue
> Continue > Memory. 1x Threshold V overvoltage threshold as percentage
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
To set the overvoltage threshold, proceed as follows: 1.
>
Configuration >
Continue
> Continue > Memory > 2x Threshold V>. 2. Press reduce it. 3. Press
to increase the value or
.
to
.
The overvoltage threshold is set. 7.4.7.8
Setting overvoltage threshold (absolute value) In this display you can set the overvoltage threshold as an absolute value. If the voltage exceeds the set overvoltage threshold, high-resolution measured values are saved for as long as this situation prevails. Entries can be made either in V or kV. If you enter the absolute value in V, it relates to the secondary transformer voltage. If you enter the absolute value in KV, it relates to the primary voltage. Setting range
Step size
Factory setting
40 V – 160 V 0 kV...2 kV
0.1 V / 1 V 1 kV
110 V 1 kV
Table 105
Setting range for V> overvoltage threshold as absolute values
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
185
7 Functions and settings
To set the overvoltage threshold, proceed as follows: 1.
>
Configuration >
> Continue > V> memory. 2. If necessary press want, "V" or "kV".
Continue
Memory. 3x
to select the unit you
3. If V is selected, press to highlight the decimal place. The decimal place is highlighted and the value can be changed. 4. Press reduce it. 5. Press
to increase the value or
to
.
The overvoltage threshold is set. 7.4.7.9
Setting time difference of average value interval The voltage regulator's long-term memory has a capacity of 8 MB. The memory is split into the average value memory and event memory. Depending on the setting, intervals of 1; 2; 4; 10; 20 or 40 (on page 189) seconds are saved in the average value memory. Setting range
Step size
Factory setting
1 s...40 s
1 s / 2 s / 6 s / 10 s / 40 s
1s
Table 106
Setting range for average value interval
When you set the average value interval, the complete memory is cleared once the change is confirmed.
186
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
To set the mean value interval, proceed as follows: 1.
>
Configuration >
Continue
> Continue > Memory > 4x Average value interval. 2. Press reduce it. 3. Press
to increase the time or
.
to
.
The mean value interval is set.
7.4.7.10
Setting size of event memory The event memory stores instances of values exceeding or falling below the preset threshold values. It stores this information in high resolution. Refer to the table below for the maximum number of events, depending on the size of the event memory: Size of event memory
256 kB
512 kB
1024 kB
2048 kB
Maximum number of events
20
40
80
160
Table 107
Size of event memory
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
187
7 Functions and settings
Below you will find examples which illustrate how the event memory works:
Figure 28
1 2 3 4
Duration: 10 seconds Duration: 10 seconds High-resolution recording Low-resolution recording
Figure 29
1 2 3 4 5 6
188
TAPCON® 260
For an event lasting less than 5 minutes
For an event lasting more than 5 minutes
Duration: 10 seconds Duration: Around 5 minutes Duration: 10 seconds Duration: 10 seconds High-resolution recordings Low-resolution recording
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
The high-resolution data are first saved 10 seconds before the event. After an event has lasted 5 minutes, data are saved with a low resolution. If the voltage returns to the bandwidth, this is considered a new event. This new event has a 10-second run-in time and a 10-second follow-up time. The table below shows the memory time. Depending on the average value interval and the size of the event memory, it is a maximum of 401 days. Size of event memory
Average value interval 256 kB 10 d 20 d 40 d 100 d 201 d 401 d
1s 2s 4s 10 s 20 s 40 s Table 108
512 kB 9d 19 d 38 d 96 d 193 d 386 d
1024 kB 8d 17 d 35 d 89 d 178 d 356 d
2048 kB 7d 14 d 29 d 73 d 147 d 295 d
Memory time of measured value memory
When you set the average value interval, the complete memory is cleared once the change is confirmed.
To set the size of the event memory, proceed as follows: 1.
>
Configuration >
Continue
> Continue > Memory > 5x Event memory. 2. Press or size you want. 3. Press
.
to set the event memory
.
The event memory size is set.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
189
7 Functions and settings
7.4.7.11
Time plotter You will find the time plotter function under "Info". The desired value you have set is automatically displayed here. The units of voltage per unit are defined by the software and you can change them at any time. However, the set values which are dependent on parameterization are adopted when you call the time plotter function back up again. You can undertake the following settings in the time plotter function:
7.4.7.11.1
Division of time axis
Voltage range
Retrace time
Retrace date
Visual display of time plotter function The time plotter is displayed as follows: Desired value/actual value display
Figure 30
1 2 3 4
190
TAPCON® 260
Desired value and actual value display of time plotter
Desired value display Actual value display Actual value display Desired value display
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
Overvoltage/undervoltage display
Figure 31
1 2 3
Voltage display of time plotter
Overvoltage and undervoltage bar Undervoltage value Overvoltage value
Description of symbols
Figure 32
1 2 3 4 5
Other time plotter symbols
Move time axis back Move time axis forward Increase set values by one unit Select values to set Decrease set values by one unit
The following sections describe how to run the above functions.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
191
7 Functions and settings
7.4.7.11.2
Moving time axis Here you can set the reporting times in the setting box. We would always recommend choosing the highest possible resolution given the range displayed. Refer to the table for the time axis division and the resulting duration of the range shown.
Figure 33
1 2
Reporting times which can be set
Horizontal grid lines (the set reporting time range is between the horizontal grid lines) Setting box for reporting times displayed
Steps which can be set (grid width)
15 s
30 s
1 min
2.5 min
5 min
10 min
Displayed range (in full display)
3.5 min
7 min
14 min
35 min
70 min
140 min
Table 109
192
Duration of range displayed
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
Proceed as follows to undertake settings: 1.
> Info > 1x Time plotter.
.
2. Press to highlight the setting box for the reporting times. The setting box is highlighted and the value can be changed. 3. Press
to move the display forwards one
step or
to move it back one step.
The time axis is set.
7.4.7.11.3
Setting voltage range In this display the voltage range is shown in the area between the horizontal grid lines. You can restrict the area between the horizontal grid lines in the corresponding setting box. Depending on the display setting, you can display the voltage range to be displayed in V or kV (see "Setting the voltage display kV/V" on page 141).
Figure 34
1 2
Voltage range which can be set
Horizontal grid lines (the set voltage range is between the horizontal grid lines) Setting box for voltage range displayed
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
193
7 Functions and settings
The voltage range to be displayed is divided as follows: Division of ranges Table 110
0.5 V 1 V 2V 0.1kV 0.2 kV 0.5 kV
5V 1kV
10 V 2 kV
15 V 5 kV 10 kV 20 kV
Voltage range between the horizontal grid lines
To set the voltage range, proceed as follows: 1.
> Info > 1x Time plotter.
.
2. Press twice to highlight the setting box for voltage range. The setting box is highlighted and the value can be changed. 3. Press to advance one unit or move back one unit.
to
The voltage range is set.
7.4.7.11.4
Setting retrace time This function allows you to move the sequence to a precise time in order to trace how voltage has behaved in the past. Any time between the present time and the oldest time in the memory can be set. The time is entered in the following format: HH:MM:SS
194
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
To move the sequence to a precise time, proceed as follows: 1.
> Info > 1x Time plotter.
.
2. Press three times to highlight the setting box for retracing. The setting box is highlighted and the value can be changed. 3. Press to advance the time or move it back.
to
The retrace time is set. The sequence for the specified time appears in the display.
7.4.7.11.5
Setting retrace date This function allows you to move the sequence to a precise date in order to trace how voltage has behaved in the past. Any date between the present date and the oldest time in the memory can be set. The date is entered in the following format: DD:MM:YY
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
195
7 Functions and settings
To move the sequence to a precise time, proceed as follows: 1.
> Info > 1x Time plotter.
.
2. Press four times to highlight the setting box for retracing. The setting box is highlighted and the value can be changed. 3. Press or
to advance the date by one digit to move it back one digit.
The retrace date is set. The sequence for the specified day appears in the display.
7.4.8
Communication interface SID The following section describes how to configure the communication interface.
7.4.8.1
Assigning a network mask In this display, you can assign a valid, individual IP address to the Ethernet module of the SID card. Setting range
Step size
Factory setting
0.0.0.0...255255255255
1
0.0.0.0
Table 111
196
TAPCON® 260
Setting range for the network mask
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
To assign a network mask, proceed as follows: 1.
>
Configuration >
General >
12x Network screen. 2. Press to mark a position. The desired position is marked and the value can be changed. 3. Press reduce it. 4. Press
to increase the value or
to
.
The network mask is assigned.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
197
7 Functions and settings
7.4.8.2
Assigning network address In this display, you can assign a valid, individual IP address to the Ethernet module of the SID card. Setting range
Step size
Factory setting
0.0.0.0...255255255255
1
0.0.0.0
Table 112
Setting range for network address
To assign a network address, proceed as follows: 1.
>
Configuration >
General >
13x . Network address. 2. Press to mark a position. The desired position is marked and the value can be changed. 3. Press reduce it. 4. Press
to increase the value or
to
.
The network address is assigned.
198
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.4.8.3
Entering the time server address In this display, you can enter the IP address of the SNTP time server to ensure that time is synchronized in the communication network. Setting range
Step size
Factory setting
0.0.0.0...255255255255
1
0.0.0.0
Table 113
Setting range for the time server address
In order to enter the time server address of the SNTP server, proceed as follows: 1.
>
Configuration >
General >
14x . Time server address. 2. Press to mark a position. The desired position is marked and the value can be changed. 3. Press reduce it. 4. Press
to increase the value or
to
.
The time server IP address is entered.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
199
7 Functions and settings
7.4.8.4
Entering gateway You can enter the gateway address in this display. Setting range
Step size
Factory setting
0.0.0.0...255255255255
1
0.0.0.0
Table 114
Setting range for gateway
To enter the gateway address, proceed as follows: 1.
>
Configuration >
General >
15x . Gateway. 2. Press to mark a position. The desired position is marked and the value can be changed. 3. Press reduce it. 4. Press
to increase the value or
to
.
The gateway address is entered.
200
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
7.4.8.5
Entering IED name You can assign a device name (IED Name) in this display. To enter the IED name, proceed as follows: 1.
>
Configuration >
General >
16x . IED name. 2. Press to mark a position. The desired position is marked and the value can be changed. 3. Press reduce it. 4. Press
to increase the value or
to
.
The IED name is entered.
7.5
Info You can view general information about on the voltage regulator in this display. You can call up the following information:
General information about the device
Functional reliability of the LEDs (LED test)
Parallel operation
Parameters
Upcoming messages
Input/output status
Status of UC1 card
Status of UC2 card
RTC (real-time clock)
Data on CAN bus
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
201
7 Functions and settings
Measured values
Peak memory
Measured value memory
Time plotter
Figure 35
1 2 3 4 5 6
Info screen
Type designation Software version Date of issue Size of EEPROM / ID number of module Flash memory RAM memory
The current measured values are shown in this display. The following measured values can be displayed:
Figure 36
202
TAPCON® 260
Measured values
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
1 2 3 4 5 6
V1 = voltage at first measurement input I1 = current at first measurement input Phase difference of V1 to I1 V2 = voltage at second measurement input Reactive current at first measurement input Iactive1 = active current at first measurement input
To display the measured values, proceed as follows: ►
7.5.1
> Info > 1x Measured values.
Carrying out LED test An LED function test can be carried out based on the information displayed. This checks whether all the LEDs are functioning properly. This function only tests the functional reliability of the LEDs. The underlying function is not therefore tested.
To carry out the LED test, proceed as follows: 1.
> Info > 2x LED TEST.
.
2. To carry out the function test, press any F key for the LED you want to test.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
203
7 Functions and settings
Key
LED no. LED 1 ... LED 5
... +
...
+
LED 6 ... LED 9 All LEDs
Table 115
7.5.2
Selecting the LEDs for tests
Querying status All active messages or signals from all cards are displayed in the status displays. The displays have the following structure:
Figure 37
1 2 3 4
Status display
Signalling status Control inputs/output relays Signalling status Control inputs/output relays
The following sections describe how you can display the respective status windows. 7.5.2.1
Displaying input/output status The status of the respective optocoupler inputs is shown under "INPUT / OUTPUT-STATUS". As soon as a continuous signal is present at the input, it is shown in the display with a "1". "0" indicates no signal at the input.
204
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
To query the status, proceed as follows: ►
7.5.2.2
> Info > 3x INPUT/OUTPUT STATUS.
Querying status of UC1 card The status of the respective optocoupler inputs is shown under "UC1 CARD STATUS". As soon as a continuous signal is present at the input, it is shown in the display with a "1". "0" indicates no signal at the input. To query the status, proceed as follows: ►
7.5.2.3
> Info > 4x UC1 CARD STATUS.
Querying status of UC2 card The status of the respective optocoupler inputs is shown under "UC2 CARD STATUS". As soon as a continuous signal is present at the input, it is shown in the display with a "1". "0" indicates no signal at the input. To query the status, proceed as follows: ►
> Info > 5x UC3 CARD STATUS.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
205
7 Functions and settings
7.5.3
Resetting parameters With this display you can reset your settings to the factory settings. To reset the parameters, proceed as follows: If you reset the parameters to the factory settings, then your settings are permanently deleted.
1.
> Info > 6x Parameter.
2. Press 3. Press
and
.
at the same time.
.
All parameters have been reset to the factory settings.
7.5.4
Displaying real-time clock A counter is started when the voltage regulator is first switched on. This continues to run even if the device is switched off. To display the real-time clock, proceed as follows: ►
7.5.5
> Info > 7x RTC.
.
Displaying parallel operation This display indicates the control number for parallel operation (= CAN bus address) and the number of voltage regulators which are currently operating in parallel.
206
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
Proceed as follows to display the parallel operation data: ►
7.5.6
> Info > 8x . Parallel operation.
Displaying data on CAN bus The CAN bus data of all voltage regulators running in parallel are shown in this display.
Figure 38 1 2 3 4 5
Display for CAN bus data
CAN bus address of voltage regulator Voltage in volts Active current in % Reactive current in % Tap position
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
207
7 Functions and settings
The additional CAN bus data of all voltage regulators running in parallel can also be shown in this display.
Figure 39
1 2 3 4 5 6 7
208
TAPCON® 260
Display for additional CAN bus data
Group input 1 Group input 2 Circulating reactive current parallel operation (0 = deactivated; 1 = activated) "Master" tap synchronization (0 = deactivated; 1 = activated) "Follower" tap synchronization (0 = deactivated; 1 = activated) "Auto" tap synchronization (0 = deactivated; 1 = activated) Voltage regulator blocks group because parallel operation is experiencing a fault (0 = is not blocked; 1 = is blocked)
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
To display the CAN bus data, proceed as follows: 1.
> Info > 9x . DATA ON CAN BUS.
The CAN bus data are displayed. If you want to display more data, go to step 2: 2. Press
and keep held down.
The additional information is displayed until you release the key.
7.5.7
Displaying measured value memory As an option, the voltage regulator can be equipped with a long-term memory module. You can display information about the memory in this window. To display the measured value memory, proceed as follows: ►
7.5.8
> Info > 12x . MEASURED VALUE MEMORY.
Displaying peak memory The minimum and maximum voltage measured since the last reset and the minimum and maximum on-load tap-changer tap positions are shown here. All values recorded are stored with a time and date. The minimum and maximum values continue to be stored in an internal fixed value memory even in the event of power failure.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
209
7 Functions and settings
Figure 40
1 2 3 4 5 6 7 8
Peak memory: Minimum (left) and maximum values (right)
Maximum measured voltage V1 Maximum on-load tap-changer tap position Time (HH:MM:SS) and date (DD.MM.YY) of maximum measured voltage V1 Time (HH:MM:SS) and date (DD.MM.YY) of maximum recorded tap position Time (HH:MM:SS) and date (DD.MM.YY) of minimum recorded tap position Time (HH:MM:SS) and date (DD.MM.YY) of minimum measured voltage V1 Minimum on-load tap-changer tap position Minimum measured voltage V1
To display the peak memory, proceed as follows: ►
7.5.9
> Info > 13x Peak memory.
.
Displaying CIC1 card SCADA information The following information on the SCADA connection is displayed under "CIC1 card SCADA information".
210
Protocol
Data format
BOOT version
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
7 Functions and settings
If necessary, you can also reset the Ethernet connection. To display the SCADA information on the CIC1 card, proceed as follows: ►
> Info > 14x CIC1 card SCADA information.
The SCADA information on the CIC1 card is displayed. If necessary, you can reset the Ethernet connection. ► Press and at the same time to reset the Ethernet connection.
7.5.10
Displaying CIC2 card SCADA information The following information on the SCADA connection is displayed under "CIC2 card SCADA information".
Protocol
Data format
BOOT version
If necessary, you can also reset the Ethernet connection. To display the SCADA information on the CIC2 card, proceed as follows: ►
> Info > 15x CIC2 card SCADA information.
The SCADA information on the CIC2 card is displayed. If necessary, you can reset the Ethernet connection. ► Press and at the same time to reset the Ethernet connection.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
211
7 Functions and settings
7.5.11
Displaying upcoming messages This display shows upcoming messages, such as:
Undervoltage
Overvoltage
Fault in parallel operation
etc.
To display the upcoming messages, proceed as follows: ►
212
> Info > 13x . UPCOMING MESSAGES.
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
8 Interface description for IEC 61850 protocol
8
Interface description for IEC 61850 protocol
8.1
Physical connection The connection to system level takes the form of a network cable via the RJ45 port on the rear of the TAPCON® 260. The speed is automatically set to 10 or 100 Mbit. Before commissioning the TAPCON® 260, the customer/system developer and MR should compare configuration data. On request, MR will send the ICD (Intelligent electronic device Configuration Description) file to the customer/system developer and the compared configuration details are returned as a CID (Configured Intelligent electronic Device) file. The parameters for the TCP/IP address, subnet mask and time server address can also be set later on. This can either be done directly via corresponding screens on the TAPCON® 260 itself or via the "TAPCON®-trol system" visualization software, i.e. on a PC or laptop. The system time for the SID card is set via the SNTP (Simple Network Time Protocol) time server. The product was developed in compliance with the relevant EMC standards. In order to maintain EMC standards, note the descriptions provided in the Electromagnetic compatibility (see "Electromagnetic compatibility" on page 55) chapter.
8.2
Device-specific data points for TAPCON® 260 The device-specific data points and presettings can be found in the device's ICD file. The MICS (Model Implementation Conformance Statement) and PICS (Protocol Implementation Conformance Statement) can be requested for the device.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
213
8 Interface description for IEC 61850 protocol
8.3
Downloading the ICD file You can download the ICD file via FTP from the communication unit (SID) using an Internet browser. To do this, you need to know the configured IP address in order to establish the Ethernet connection. Proceed as follows to download the ICD file: 1.
Enter ftp://gast@ in your browser (in the example in the diagram below, the IP address is 192.168.0.1).
2.
Use "Save as" to save the ICD file (in this example ATCC.ICD) on the local PC.
3.
Other files, such as the Model Implementation Conformance Statement, are located in the misc folder and can also be saved on the local PC using "Save as".
The ICD file is downloaded.
Figure 41
214
TAPCON® 260
Downloading the ICD file using an Internet browser
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
9 Fault elimination
9
Fault elimination The following chapter describes how to eliminate simple operating faults and the meaning of possible event messages.
9.1
Operating faults If faults occur in the device during operation, these can usually be remedied by the user. The tables below are intended to provide assistance in recognizing and remedying faults.
9.1.1
No control in AUTO mode
Characteristics/detail Voltage regulator control commands have no effect. RAISE/LOWER LEDs light up periodically
Blocking
Cause Local/Remote switch in motor-drive unit switched to LOCAL Connection missing.
Remedy Check operating mode. Correct if necessary.
Check wiring as per connection diagram. Reverse power lock active. Check parameter. Correct if necessary. Negative power flow. Check current transformer polarity. Check parameterization of IOs. Control inputs (IOs) have duplicate parameterization. Correct if necessary. One of the IOs is paramete- Check parameterization and rized with "Blocking" and status in info screen (inhas an appropriate input put/output status). signal. Correct if necessary. NORMset active. Carry out manual tap-change
Undercurrent blocking active.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
operation with or keys. Check parameter. Correct if necessary.
TAPCON® 260
215
9 Fault elimination
Characteristics/detail Blocking LED V< illuminated
Cause Undervoltage blocking active
Blocking LED V> illuminated
Overvoltage blocking active. Check parameter. Correct if necessary.
Blocking LED I> illuminated
Overcurrent blocking active. Check parameter. Correct if necessary.
Bandwidth set too high
-
Table 116
Troubleshooting: No control in AUTO mode
9.1.2
Man Machine Interface
Remedy Check parameter. Correct if necessary.
Calculate sensitivity:Step voltage x 100 / nominal voltage
Characteristics/detail Keys Does not switch between MANUAL/AUTO
Cause REMOTE selected.
Remedy Select LOCAL mode.
Keys MANUAL and AUTO LEDs do not light up.
Parameter error.
Reset to factory settings.
Contrast incorrectly set. Voltage supply interrupted.
Set contrast using resistor contact series in front panel. Check voltage supply.
Fuse faulty.
Replace fuse.
Display No display.
216
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
9 Fault elimination
Characteristics/detail Display Different brightness on several voltage regulators.
Cause Display dimming activated/deactivated.
Remedy Check "Display dimming" setting.
LEDs Freely configurable LED lights up.
Customized LED parameterization.
Check parameter. Correct if necessary.
LEDs LED flashes irregularly.
Input signal not constant.
Check input signal.
LEDs Status LED of SID card not flashing.
Network address, network mask, gateway addresses, time server address or IED name not set. Different baud rates set.
Check the network address, network mask, gateway addresses, time server address and IED name parameters. Check "Baud rate" parameter (voltage regulator and TAPCON®trol). Correct if necessary.
COM1 Cannot be connected to PC using TAPCONtrol. Table 117
Troubleshooting: Man Machine Interface
9.1.3
Incorrect measured values
Characteristics/detail
Measured voltage No measured value.
Measured voltage Measured value too low. Measured voltage Measured value fluctuates too much.
Cause Connection has no contact in the plug terminal. Insulation trapped. Wire not inserted far enough. Circuit breaker tripped. Voltage drop on measuring lead.
Remedy
Possible sources of fault: Leads laid in parallel.
Check measured voltage at plug terminal. Increase distance from source of interference. Install filter if necessary.
Tap-change operations.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
Check wiring and plug terminal.
Check fuse. Check measured voltage at plug terminal.
TAPCON® 260
217
9 Fault elimination
Characteristics/detail Measured current No measured value. Measured current Measured value too high.
Cause Line to current transformer interrupted. Do not remove short-circuiting jumper in current transformer. Ratio not correctly parameterized. Incorrect input connected.
Measured value too low.
Remove short-circuiting jumper.
Correct parameterization. Check assignment of plug terminals.
Fault in external transformer Check transformer circuit . circuit. Compare with system connection diagram. Correct parameters. Compare measurement values on info screen. Transpose current transformer connection. Transformer circuit Check polarity of transformer incorrectly parameterized. circuit. Correct if necessary. Check circuit. Correct if necessary. Check measurement points. Correct if necessary.
Phase angle V/I.
Table 118
Troubleshooting: Incorrect measured values
9.1.4
Parallel operation faults
Characteristics/detail Parallel operation cannot be activated. LED not lit up.
218
Remedy Check wiring.
TAPCON® 260
Cause "Parallel operation method" parameter deactivated.
Remedy Activate "Parallel operation method" parameter Select parallel operation method (see "Selecting parallel operation method" on page 152). CAN bus address of voltage Set CAN bus address (anything regulator set to "0". but 0)
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
9 Fault elimination
Characteristics/detail
Problem with CAN bus. Device not listed.
Cause Voltage regulator incorrectly connected (plug twisted, offset). Voltage regulators have the same CAN bus addresses.
Table 119
Troubleshooting: Parallel operation
9.1.5
Tap position capture incorrect
Remedy Check connections. Connect as shown in connection diagram. Issue different CAN bus addresses Enter CAN bus address (1) (see "Entering CAN bus address" on page 158).
Characteristics/detail
Cause
Remedy
Step display incorrect. Plus or minus sign incorrect.
Digital input activated.
Check wiring. Connect as shown in connection diagram.
"Lower value" analog input not correctly parameterized
Step display incorrect. Display fluctuates.
Interference.
No step display. "-" is displayed.
No measurement signal. No L- for digital input.
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
Check parameter. Set parameter Lower limit value (%) for input 1 and 2 FB. Shield line. Increase distance from source of interference. Lay interference lines separately. Route signal in separate lines (filter, shielded lines). Connect signal as shown in connection diagram. Check wiring Display UC1 card status FB (see "Querying status of UC1 card" on page 205)/Display UC2 card status FB (see "Querying status of UC2 card" on page 205). Connect as shown in connection diagram.
TAPCON® 260
219
9 Fault elimination
Characteristics/detail
Cause Impermissible signal combination.
No step display. "?" is displayed. "Motor running" signal present.
Table 120
Troubleshooting: Tap position capture
9.1.6
Digital inputs
Characteristics/detail
Cause
Signal discontinuous.
Intermittent DC voltage.
No signal Info screen showing 0.
Supply voltage too low.
Table 121
Troubleshooting: Digital inputs
9.1.7
General fault
Remedy Check wiring Display UC1 card status FB (see "Querying status of UC1 card" on page 205)/Display UC2 card status FB (see "Querying status of UC2 card" on page 205). Check signal sequence Display input/output status FB (see "Displaying input/output status" on page 204).
Remedy Check source of DC voltage. Check signal transmitter. Check wiring. Reset parameter to factory settings.
Characteristics/detail No function Supply voltage.
Cause Fuse tripped.
Remedy Check all fuses. Replace if necessary.
Relays chatter
Supply voltage too low.
Check supply voltage.
Table 122
Troubleshooting: General faults
9.1.8
No solution If you cannot resolve a problem, please contact Maschinenfabrik Reinhausen. Please have the following data to hand:
220
Serial number
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
9 Fault elimination
This can be found: Outer right side when viewed from the front Info screen (
>
Info)
Please provide answers to the following questions:
Has a firmware update been carried out?
Has there previously been a problem with this device?
Have you previously contacted Maschinenfabrik Reinhausen about this issue? If yes, then who was the contact?
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
221
9 Fault elimination
9.2
Event message
Event message
Remark
Undervoltage
Message is displayed if the voltage falls below the set "V" limit value. Parameter setting: (see "Setting the V> overvoltage limit value [%]" on page 101) Message is displayed in the event of overcurrent. Parameter setting: (see "Setting limit value I> overcurrent" on page 103). With tap synchronization: The tap positions of the voltage regulators running in parallel were not the same for longer than the set parallel operation signal delay.
Overvoltage
Overcurrent
Parameter error
One of the voltage regulators running in parallel is not signaling a valid tap position. Neither of the voltage regulators running in parallel is set as master. One of the voltage regulators running in parallel is using the circulating reactive current method. There is no information about the system topology. With circulating reactive current method: The voltage regulator's circulating reactive current was longer than the set parallel operation signal delay and greater than the set limit value One of the voltage regulators running in parallel is using the tap synchronization method. There is no information about the system topology. There is a signal on at least one of the group inputs, but no other voltage regulator was found in the same group. Motor protection Function monitoring Table 123
222
Signal issued at "Motor protective switch" input. A message is issued if the voltage regulator detects a control deviation for 15 minutes and this is not compensated for.
Possible events
TAPCON® 260
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
10 Technical Data
10
Technical Data
10.1
Indicator elements LCD, monochrome, graphics-capable 128 x 128 pixels 15 LEDs for operation display and messages of which 4 LEDs are freely programmable (3x yellow, 1x green/red)
Display LEDs
Table 124
10.2
Indicator elements
Electrical data Power supply
Power consumption Table 125
10.3
110 (-20%)...350 V DC 88...265 V AC Optional: 36...72 V DC or 18...36 V DC 25 VA
Electrical data
Inputs and outputs Control voltage of inputs Contact loadability of outputs Table 126
40...250 V DC With pulsating DC voltage, the voltage minimum must always exceed 40 V. min. 12 V / 100 mA max. AC 250 V / 5 A max. DC see diagram
Inputs and outputs
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
223
10 Technical Data
Figure 42 1
10.4
Ohmic load
Dimensions and weight Housing (W x H x D) Weight Table 127
224
Maximum contact loadability of outputs with direct current
TAPCON® 260
19-inch plug-in housing in accordance with DIN 41494 Part 5 483 x 133 x 178 mm 5.0 kg Dimensions and weight
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
10 Technical Data
10.5
Voltage and current measurement Voltage transformer
Current transformer
Measuring error Table 128
10.6
Measuring range: 49...140 V Effective value: 40...60 Hz Intrinsic consumption: < 1 VA 0.2 / 1 / 5 A Effective value: 40...60 Hz Intrinsic consumption: < 1 VA Overload capacity: 2 x IN (continuously), 40 x IN / 1s Voltage measuring: < 0.3 % ± 40 ppm/°C Current measuring: < 0.5 % ± 40 ppm/°C
Voltage and current measurement
Ambient conditions Operating temperature Storage temperature Table 129
Permissible ambient conditions
10.7
Tests
10.7.1
Electrical safety EN 61010-1
Safety requirements for electrical measurement and control and regulation equipment and laboratory instruments Dielectric test with operating frequency 2.5 kV / 1 min Dielectric test with impulse voltage 5 kV, 1.2 / 50 μs Level of contamination 2, overvoltage category III
IEC 61131-2 IEC 60255 IEC 60 644-1 Table 130
-25°C...+70°C -30°C...+85°C
Electrical safety
© Maschinenfabrik Reinhausen 2011
1801003/04 EN
TAPCON® 260
225
10 Technical Data
10.7.2
EMC tests IEC 61000-4-2
Electrostatic discharges (ESD) 6 kV /8 kV
IEC 61000-4-3
Electromagnetic fields (HF) 10 V/m 80...3000 MHz Fast transients (burst) 2 kV Surge transient immunity 2 kV
IEC 61000-4-4 IEC 61000-4-5 IEC 61000-4-6
HF interference immunity (lines) 10 V, 150 kHz...80 MHz Power frequency magnetic field immunity 30 A/m, 50 Hz, continuous
IEC 61000-4-8 IEC 61000-4-11
Voltage dips, short interruptions and voltage variations immunity tests Voltage dips, short interruptions and voltage variations on d.c. input power port immunity tests
IEC 61000-4-29 IEC 61000-6-2
Immunity requirements for industrial environments Emission standard for industrial environments
IEC 61000-6-4 Table 131
10.7.3
EMC tests
Environmental durability tests DIN EN 60529 IEC 60068-2-1
Degree of protection IP20 Dry cold - 25 °C / 20 hours
IEC 60068-2-2 IEC 60068-2-3
Dry heat + 70 °C / 16 hours Constant moist heat + 40 °C / 93% / 2 days, no dew Cyclic moist heat (12 + 12 hours) + 55 °C / 93 % / 6 cycles
IEC 60068-2-30 Table 132
226
TAPCON® 260
Environmental durability tests
1801003/04 EN
© Maschinenfabrik Reinhausen 2011
11 MR worldwide
11
MR worldwide
Australia Reinhausen Australia Pty. Ltd. Ground Floor 6-10 Geeves Avenue Rockdale N. S. W. 2216 Phone: +61 2 9556 2133 Fax: +61 2 9597 1339 E-mail:
[email protected] Brazil MR do Brasil Indústria Mecánica Ltda. Av. Elias Yazbek, 465 CEP: 06803-000 Embu - São Paulo Phone: +55 11 4785 2150 Fax: +55 11 4785 2185 E-mail:
[email protected] Canada Reinhausen Canada Inc. 1010 Sherbrooke West, Suite 1800 Montréal, Québec H3A 2R7, Canada Phone: +1 514 286 1075 Fax: +1 514 286 0520 Mobile: +49 170 7807 696 E-mail:
[email protected] India Easun-MR Tap Changers Ltd. 612, CTH Road Tiruninravur, Chennai 602 024 Phone: +91 44 26300883 Fax: +91 44 26390881 E-mail:
[email protected] Indonesia Pt. Reinhausen Indonesia German Center, Suite 6310, Jl. Kapt. Subijanto Dj. BSD City, Tangerang Phone: +62 21 5315-3183 Fax: +62 21 5315-3184 E-Mail:
[email protected] Iran Iran Transfo After Sales Services Co. Zanjan, Industrial Township No. 1 (Aliabad) Corner of Morad Str. Postal Code 4533144551 E-mail:
[email protected]
© Maschinenfabrik Reinhausen 2011
Italy Reinhausen Italia S.r.l. Via Alserio, 16 20159 Milan Phone: +39 02 6943471 Fax: +39 02 69434766 E-mail:
[email protected] Japan MR Japan Corporation German Industry Park 1-18-2 Hakusan, Midori-ku Yokohama 226-0006 Phone: +81 45 929 5728 Fax: +81 45 929 5741 Luxembourg Reinhausen Luxembourg S.A. 72, Rue de Prés L-7333 Steinsel Phone: +352 27 3347 1 Fax: +352 27 3347 99 E-mail:
[email protected] Malaysia Reinhausen Asia-Pacific Sdn. Bhd Level 11 Chulan Tower No. 3 Jalan Conlay 50450 Kuala Lumpur Phone: +60 3 2142 6481 Fax: +60 3 2142 6422 E-mail:
[email protected]
Russian Federation OOO MR Naberezhnaya Akademika Tupoleva 15, Bld. 2 ("Tupolev Plaza") 105005 Moscow Phone: +7 495 980 89 67 Fax: +7 495 980 89 67 E-mail:
[email protected] South Africa Reinhausen South Africa (Pty) Ltd. No. 15, Third Street, Booysens Reserve Johannesburg Phone: +27 11 8352077 Fax: +27 11 8353806 E-Mail:
[email protected] South Korea Reinhausen Korea Ltd. Baek Sang Bldg. Room No. 1500 197-28, Kwanhun-Dong, Chongro-Ku Seoul 110-718, Korea Phone: +82 2 767 4909 Fax: +82 2 736 0049 E-mail:
[email protected] U.S.A. Reinhausen Manufacturing Inc. 2549 North 9th Avenue Humboldt, TN 38343 Phone: +1 731 784 7681 Fax: +1 731 784 7682 E-mail:
[email protected]
P.R.C. (China) MR China Ltd. (MRT) 开德贸易(上海)有限公司 中国上海浦东新区浦东南路360号 新上海国际大厦4楼E座 邮编: 200120 电话:+86 21 61634588 传真:+86 21 61634582 邮箱:
[email protected] [email protected]
1801003/04 EN
TAPCON® 260
227
1801003/04 EN 07/11
Maschinenfabrik Reinhausen GmbH Falkensteinstrasse 8 93059 Regensburg
Phone: Fax: Email:
+49 941 4090 0 +49 941 4090 7001
[email protected]
www.reinhausen.com