E TITLE:
LT CABLE SIZING CALCULATION
BLT Hydraulic System- Filling Pump
### kw
SOURCE :
Parameter
DESIGNED
CHECKED
SHEET
ACH
MMR
A4
MCC-WT
APPROX. LENGTH210 m
Basis / Formula Used
Value
15
15
Demand Factor
Assumed
1
Consumed Load
Mr / F
15
Motor rating / Total Load
Unit Kw
Symbol Mr
Kw
Mc
F
0.83
cos φr
Running sin φ
0.56
sin φr
Starting cos φ
0.30
cos φs
0.95
sin φs
Running cos φ (consumed load)
Refer motor catalogue Assumed
Starting sin φ
0.9
Refer motor catalogue
Consumed Load Efficiency
Mc / (cos φr x ηr)
Load in kVA System Voltage Sytem Voltage for calculation
Vs= V X (1 0.60% ) (P x 1000) / (1.732 x Vs)
Full Load Current
ηr
20.08
kVA
415
Volts
V
412.51
Volts
Vs
28.11
Amps
P
I flc
Temperature Deration
(refer Table - A)
0.9
Grouping Deration
(refer Table - B)
0.68
TDF GDF
Other Derating Factor
1
RDF
Total Derating Factor
TDFx GDF x RDF
0.61
I flc / DF
45.92
Amps
Ir
63
Amps
Ic
Running Current after derations Current carrying capacity 3cx25
PVC
(refer catalogue)
AL
0.73
Ir / Ic
No. of Runs of cable
DF
1
No. of runs of selected cable
No.
3.08 %
Using 210 Mtr cable, Actual % Voltage drop w.r.t 415V =
N
3.68
Check for voltage drop Allowable voltage drop (%) starting
15
%
%Vdsa
Allowable voltage drop (%) running
4.40
%
%Vdra
Allowable voltage drop at starting
Vs x %Vdsa/100
61.877
Volt
Vdsa
Allowable voltage drop at running
Vs x %Vdra/100
18.150
Volt
Vdra
Max. Conductor Resistance at 70 degC
(refer cable catalogue)
1.44
Ohm / km
R
Reactance at 50 c/s
(refer cable catalogue)
0.1
Ohm / km
Xl
Running current
Full load current ( Iflc )
28.11
Amps
Ir
Starting current
7.2 x Ir (Vdsa x N) / (1.732 x Is x (Rcos φs + Xl sin φs)) (Vdra x N) / (1.732 x Ir x (Rcos φr + Xl sin φr))
202.36
Amps
Is
336
Mtrs
298
Mtrs
Max. length for starting condition Max. length for running condition
Hence, Cable Size Selected (As per Calculation) Table - A (Temp. Derating factor) Deg C PVC
HR PVC
LT XLPE
1
3cx25
6
8
AL
Table - B (Grouping factor)
HT EPR XLPE CSP
No. of cables / tray
No. of Trays 1
2
3
4
25
1.25
1.16
1.14
1.14
1.28
1
1
1
1
1
1
1
30
1.16
1.1
1.1
1.1
1.22
2
0.84
0.8
0.78
0.77
0.76
0.75
35
1.09
1.05
1.04
1.04
1.13
3
0.8
0.76
0.74
0.73
0.72
0.71
40
1
1
1
1
1
4
0.78
0.74
0.72
0.71
0.7
0.69
0.95
0.95
0.98
5
0.7
0.69
0.68
0.67
45
PVC
0.9
0.94
0.77
0.73
50
0.8
0.88
0.9
0.9
0.88
6
0.75
0.71
0.7
0.68
0.68
0.66
55
0.69
0.82
0.85
0.85
0.77
7
0.74
0.69
0.68
0.66
0.66
0.64
60
0.62
0.74
0.8
0.8
0.66
8
0.73
0.69
0.68
0.67
0.66
0.64
Note: A) As per above calculation, the Cable Size of
1 R-
3cx25 Sqmm is found to be OK.
B) In above calculation, Consumed Load have been considered as Motor rating. C) The above cable size selected for motor is based on Average length of 150 Mtr, However, the final cable sizes for individual motors shall be based on the actual cable lengths considering the voltage drop.
in 5% voltage drop
GN-ST-06(Design Sheet) Two formats of design sheets are enclosed. These sheets can be used as per the convenience (i) (ii) The ‘designed’ and ‘checked’ columns of design sheet shall have the signature of the person responsible for design & checking respectively.